Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: ApartmentMidRise
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2024-07-03 12:21:23
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 1245.15 | 397.23 | 440.92 |
| Net Site Energy | 1245.15 | 397.23 | 440.92 |
| Total Source Energy | 3097.34 | 988.11 | 1096.80 |
| Net Source Energy | 3097.34 | 988.11 | 1096.80 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 3134.61 |
| Net Conditioned Building Area | 2823.98 |
| Unconditioned Building Area | 310.64 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 23.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 152.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 73.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 33.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 454.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 102.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 406.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.51 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 838.98 | 406.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.51 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 23.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 152.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 67.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 5.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 33.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | ElevatorLift | 67.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLightsFan | 0.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MiscPlug | 386.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 102.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.51 | |
| Water Heater | 0.00 | 406.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 23.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 152.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 73.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 33.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 454.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 102.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 0.00 | 406.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.51 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 37.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 98.77 | 143.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Other | 160.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 297.09 | 143.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 33.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 88.99 | 129.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Other | 144.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 267.65 | 129.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 838.984 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 838.984 | 100.00 |
| Total On-Site and Utility Electric Sources | 838.984 | 100.00 |
| Total Electricity End Uses | 838.984 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | 0.00 |
| Air to Air Heat Recovery for Cooling | 50.13 | 23.73 |
| Air to Air Heat Recovery for Heating | 161.10 | 76.27 |
| High-Temperature Geothermal* | 0.00 | 0.00 |
| Solar Water Thermal | 0.00 | 0.00 |
| Solar Air Thermal | 0.00 | 0.00 |
| Total On-Site Thermal Sources | 211.23 | 100.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 1875.51 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 1875.51 | 100.00 |
| Total Water End Uses | 1875.51 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8760.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneHeatingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneElectricSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PeakSpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainComponentsAtCoolingPeakMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ComfortReportSimple55Monthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |OccupantComfortDataSummaryMonthly
| OCCUP_GSW | OCCUP_GNW | OCCUP_OFFICE | OCCUP_GNE | OCCUP_GN1 | OCCUP_GN2 | OCCUP_GS1 | OCCUP_GS2 | OCCUP_MSW | OCCUP_MNW | OCCUP_MSE | OCCUP_MNE | OCCUP_MN1 | OCCUP_MN2 | OCCUP_MS1 | OCCUP_MS2 | OCCUP_TSW | OCCUP_TNW | OCCUP_TSE | OCCUP_TNE | OCCUP_TN1 | OCCUP_TN2 | OCCUP_TS1 | OCCUP_TS2 | OCCUP_T CORRIDOR | OCCUP_G CORRIDOR | OCCUP_M CORRIDOR |DXReportMonthly
| SPLIT GSW HP COOLING COIL | SPLIT GNW HP COOLING COIL | SPLIT OFFICE HP COOLING COIL | SPLIT GNE HP COOLING COIL | SPLIT GN1 HP COOLING COIL | SPLIT GN2 HP COOLING COIL | SPLIT GS1 HP COOLING COIL | SPLIT GS2 HP COOLING COIL | SPLIT MSW HP COOLING COIL | SPLIT MNW HP COOLING COIL | SPLIT MSE HP COOLING COIL | SPLIT MNE HP COOLING COIL | SPLIT MN1 HP COOLING COIL | SPLIT MN2 HP COOLING COIL | SPLIT MS1 HP COOLING COIL | SPLIT MS2 HP COOLING COIL | SPLIT TSW HP COOLING COIL | SPLIT TNW HP COOLING COIL | SPLIT TSE HP COOLING COIL | SPLIT TNE HP COOLING COIL | SPLIT TN1 HP COOLING COIL | SPLIT TN2 HP COOLING COIL | SPLIT TS1 HP COOLING COIL | SPLIT TS2 HP COOLING COIL |WindowReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowEnergyReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |WindowEnergyZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| SPLIT GSW HEATING COIL | SPLIT GNW HEATING COIL | SPLIT OFFICE HEATING COIL | SPLIT GNE HEATING COIL | SPLIT GN1 HEATING COIL | SPLIT GN2 HEATING COIL | SPLIT GS1 HEATING COIL | SPLIT GS2 HEATING COIL | SPLIT MSW HEATING COIL | SPLIT MNW HEATING COIL | SPLIT MSE HEATING COIL | SPLIT MNE HEATING COIL | SPLIT MN1 HEATING COIL | SPLIT MN2 HEATING COIL | SPLIT MS1 HEATING COIL | SPLIT MS2 HEATING COIL | SPLIT TSW HEATING COIL | SPLIT TNW HEATING COIL | SPLIT TSE HEATING COIL | SPLIT TNE HEATING COIL | SPLIT TN1 HEATING COIL | SPLIT TN2 HEATING COIL | SPLIT TS1 HEATING COIL | SPLIT TS2 HEATING COIL | SPLIT GSW_SUPPHEATCOIL | SPLIT GNW_SUPPHEATCOIL | SPLIT OFFICE_SUPPHEATCOIL | SPLIT GNE_SUPPHEATCOIL | SPLIT GN1_SUPPHEATCOIL | SPLIT GN2_SUPPHEATCOIL | SPLIT GS1_SUPPHEATCOIL | SPLIT GS2_SUPPHEATCOIL | SPLIT MSW_SUPPHEATCOIL | SPLIT MNW_SUPPHEATCOIL | SPLIT MSE_SUPPHEATCOIL | SPLIT MNE_SUPPHEATCOIL | SPLIT MN1_SUPPHEATCOIL | SPLIT MN2_SUPPHEATCOIL | SPLIT MS1_SUPPHEATCOIL | SPLIT MS2_SUPPHEATCOIL | SPLIT TSW_SUPPHEATCOIL | SPLIT TNW_SUPPHEATCOIL | SPLIT TSE_SUPPHEATCOIL | SPLIT TNE_SUPPHEATCOIL | SPLIT TN1_SUPPHEATCOIL | SPLIT TN2_SUPPHEATCOIL | SPLIT TS1_SUPPHEATCOIL | SPLIT TS2_SUPPHEATCOIL | SPLIT GSW HP COOLING COIL | SPLIT GNW HP COOLING COIL | SPLIT OFFICE HP COOLING COIL | SPLIT GNE HP COOLING COIL | SPLIT GN1 HP COOLING COIL | SPLIT GN2 HP COOLING COIL | SPLIT GS1 HP COOLING COIL | SPLIT GS2 HP COOLING COIL | SPLIT MSW HP COOLING COIL | SPLIT MNW HP COOLING COIL | SPLIT MSE HP COOLING COIL | SPLIT MNE HP COOLING COIL | SPLIT MN1 HP COOLING COIL | SPLIT MN2 HP COOLING COIL | SPLIT MS1 HP COOLING COIL | SPLIT MS2 HP COOLING COIL | SPLIT TSW HP COOLING COIL | SPLIT TNW HP COOLING COIL | SPLIT TSE HP COOLING COIL | SPLIT TNE HP COOLING COIL | SPLIT TN1 HP COOLING COIL | SPLIT TN2 HP COOLING COIL | SPLIT TS1 HP COOLING COIL | SPLIT TS2 HP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| SPLIT GSW SUPPLY FAN | G SW APARTMENT ERV SUP FAN | G SW APARTMENT ERV EXH FAN | SPLIT GNW SUPPLY FAN | G NW APARTMENT ERV SUP FAN | G NW APARTMENT ERV EXH FAN | SPLIT OFFICE SUPPLY FAN | SPLIT GNE SUPPLY FAN | G NE APARTMENT ERV SUP FAN | G NE APARTMENT ERV EXH FAN | SPLIT GN1 SUPPLY FAN | G N1 APARTMENT ERV SUP FAN | G N1 APARTMENT ERV EXH FAN | SPLIT GN2 SUPPLY FAN | G N2 APARTMENT ERV SUP FAN | G N2 APARTMENT ERV EXH FAN | SPLIT GS1 SUPPLY FAN | G S1 APARTMENT ERV SUP FAN | G S1 APARTMENT ERV EXH FAN | SPLIT GS2 SUPPLY FAN | G S2 APARTMENT ERV SUP FAN | G S2 APARTMENT ERV EXH FAN | SPLIT MSW SUPPLY FAN | M SW APARTMENT ERV SUP FAN | M SW APARTMENT ERV EXH FAN | SPLIT MNW SUPPLY FAN | M NW APARTMENT ERV SUP FAN | M NW APARTMENT ERV EXH FAN | SPLIT MSE SUPPLY FAN | M SE APARTMENT ERV SUP FAN | M SE APARTMENT ERV EXH FAN | SPLIT MNE SUPPLY FAN | M NE APARTMENT ERV SUP FAN | M NE APARTMENT ERV EXH FAN | SPLIT MN1 SUPPLY FAN | M N1 APARTMENT ERV SUP FAN | M N1 APARTMENT ERV EXH FAN | SPLIT MN2 SUPPLY FAN | M N2 APARTMENT ERV SUP FAN | M N2 APARTMENT ERV EXH FAN | SPLIT MS1 SUPPLY FAN | M S1 APARTMENT ERV SUP FAN | M S1 APARTMENT ERV EXH FAN | SPLIT MS2 SUPPLY FAN | M S2 APARTMENT ERV SUP FAN | M S2 APARTMENT ERV EXH FAN | SPLIT TSW SUPPLY FAN | T SW APARTMENT ERV SUP FAN | T SW APARTMENT ERV EXH FAN | SPLIT TNW SUPPLY FAN | T NW APARTMENT ERV SUP FAN | T NW APARTMENT ERV EXH FAN | SPLIT TSE SUPPLY FAN | T SE APARTMENT ERV SUP FAN | T SE APARTMENT ERV EXH FAN | SPLIT TNE SUPPLY FAN | T NE APARTMENT ERV SUP FAN | T NE APARTMENT ERV EXH FAN | SPLIT TN1 SUPPLY FAN | T N1 APARTMENT ERV SUP FAN | T N1 APARTMENT ERV EXH FAN | SPLIT TN2 SUPPLY FAN | T N2 APARTMENT ERV SUP FAN | T N2 APARTMENT ERV EXH FAN | SPLIT TS1 SUPPLY FAN | T S1 APARTMENT ERV SUP FAN | T S1 APARTMENT ERV EXH FAN | SPLIT TS2 SUPPLY FAN | T S2 APARTMENT ERV SUP FAN | T S2 APARTMENT ERV EXH FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AirLoopSystemEnergyAndWaterUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentLoadsMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentEnergyUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |MechanicalVentilationLoadsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
| Latitude [deg] | 33.63 |
| Longitude [deg] | -84.4 |
| Elevation [m] | 308.00 |
| Time Zone | -5.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Above Ground Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Window Opening Area [m2] | 306.92 | 112.97 | 43.82 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Above Ground Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Above Ground Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Above Ground Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Total | |
| Gross Roof Area [m2] | 783.65 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 7.4895 | 18.58 | 6.6700 |
| G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 1.11 | 1.11 | 5.2871 | 18.58 | 0.0000 |
| G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 3.32 | 3.32 | 5.2871 | 18.58 | 515.3919 |
| M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 0.00 | 1.11 | 1.11 | 5.2871 | 18.58 | 0.0000 |
| Total | 3134.61 | 9553.84 | 1542.04 | 0.00 | 306.92 | 306.92 | 5.5258 | 31.67 | 18.7777 | |||
| Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 0.00 | 300.26 | 300.26 | 5.5521 | 34.33 | 6.6700 | |||
| Unconditioned Total | 310.64 | 946.78 | 40.87 | 0.00 | 6.66 | 6.66 | 5.2871 | 18.58 | 128.8480 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| G SW APARTMENT | 88.25 | Yes | Yes | 1.00 | G SW APARTMENT | GENERAL | G SW APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| G NW APARTMENT | 88.25 | Yes | Yes | 1.00 | G NW APARTMENT | GENERAL | G NW APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| OFFICE | 88.25 | Yes | Yes | 1.00 | OFFICE | GENERAL | OFFICE | 7.4895 | 18.58 | 6.6700 | |
| G NE APARTMENT | 88.25 | Yes | Yes | 1.00 | G NE APARTMENT | GENERAL | G NE APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| G N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N1 APARTMENT | GENERAL | G N1 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| G N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N2 APARTMENT | GENERAL | G N2 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| G S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S1 APARTMENT | GENERAL | G S1 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| G S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S2 APARTMENT | GENERAL | G S2 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M SW APARTMENT | 88.25 | Yes | Yes | 2.00 | M SW APARTMENT | GENERAL | M SW APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M NW APARTMENT | 88.25 | Yes | Yes | 2.00 | M NW APARTMENT | GENERAL | M NW APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M SE APARTMENT | 88.25 | Yes | Yes | 2.00 | M SE APARTMENT | GENERAL | M SE APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M NE APARTMENT | 88.25 | Yes | Yes | 2.00 | M NE APARTMENT | GENERAL | M NE APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M N1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N1 APARTMENT | GENERAL | M N1 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M N2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N2 APARTMENT | GENERAL | M N2 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M S1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S1 APARTMENT | GENERAL | M S1 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M S2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S2 APARTMENT | GENERAL | M S2 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T SW APARTMENT | 88.25 | Yes | Yes | 1.00 | T SW APARTMENT | GENERAL | T SW APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T NW APARTMENT | 88.25 | Yes | Yes | 1.00 | T NW APARTMENT | GENERAL | T NW APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T SE APARTMENT | 88.25 | Yes | Yes | 1.00 | T SE APARTMENT | GENERAL | T SE APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T NE APARTMENT | 88.25 | Yes | Yes | 1.00 | T NE APARTMENT | GENERAL | T NE APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N1 APARTMENT | GENERAL | T N1 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N2 APARTMENT | GENERAL | T N2 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S1 APARTMENT | GENERAL | T S1 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S2 APARTMENT | GENERAL | T S2 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T CORRIDOR | 77.66 | No | Yes | 1.00 | T CORRIDOR | GENERAL | T CORRIDOR | 5.2871 | 18.58 | 0.0000 | |
| G CORRIDOR | 77.66 | No | Yes | 1.00 | G CORRIDOR | GENERAL | G CORRIDOR | 5.2871 | 18.58 | 515.3919 | |
| M CORRIDOR | 77.66 | No | Yes | 2.00 | M CORRIDOR | GENERAL | M CORRIDOR | 5.2871 | 18.58 | 0.0000 | |
| Total | 3134.61 | 5.5258 | 15.84 | 18.7777 | |||||||
| Conditioned Total | 2823.98 | 5.5521 | 17.17 | 6.6700 | |||||||
| Unconditioned Total | 310.64 | 5.2871 | 9.29 | 128.8480 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 3134.61 | 2823.98 | 310.64 | 0.00 | 4.1584 | 41.91 | 17.2755 |
| Total | 3134.61 | 2823.98 | 310.64 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 12-FEB-07:10 | 03-FEB-07:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-07:10 |
| Heating | 32880.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 2425.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 2101.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 15793.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 13031.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 14.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 28641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 66247.06 | 28641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 32880.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 2230.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 194.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 2101.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | ElevatorLift | 3772.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLightsFan | 31.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MiscPlug | 11989.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 13031.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 14.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Water Heater | 0.00 | 28641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 73.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 482.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 231.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 104.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1437.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 325.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 1.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 440.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 2657.06 | 440.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 26.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 170.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 81.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 37.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 509.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 115.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 155.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 940.89 | 155.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 23.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 153.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 73.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 33.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 458.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 103.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 140.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 847.65 | 140.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
ZoneHVAC:EnergyRecoveryVentilator| User-Specified Supply Air Flow Rate [m3/s] | User-Specified Exhaust Air Flow Rate [m3/s] | |
| G SW APARTMENT ERV | 0.025955 | 0.025955 |
| G NW APARTMENT ERV | 0.025955 | 0.025955 |
| G NE APARTMENT ERV | 0.025955 | 0.025955 |
| G N1 APARTMENT ERV | 0.025955 | 0.025955 |
| G N2 APARTMENT ERV | 0.025955 | 0.025955 |
| G S1 APARTMENT ERV | 0.025955 | 0.025955 |
| G S2 APARTMENT ERV | 0.025955 | 0.025955 |
| M SW APARTMENT ERV | 0.051909 | 0.051909 |
| M NW APARTMENT ERV | 0.051909 | 0.051909 |
| M SE APARTMENT ERV | 0.051909 | 0.051909 |
| M NE APARTMENT ERV | 0.051909 | 0.051909 |
| M N1 APARTMENT ERV | 0.051909 | 0.051909 |
| M N2 APARTMENT ERV | 0.051909 | 0.051909 |
| M S1 APARTMENT ERV | 0.051909 | 0.051909 |
| M S2 APARTMENT ERV | 0.051909 | 0.051909 |
| T SW APARTMENT ERV | 0.025955 | 0.025955 |
| T NW APARTMENT ERV | 0.025955 | 0.025955 |
| T SE APARTMENT ERV | 0.025955 | 0.025955 |
| T NE APARTMENT ERV | 0.025955 | 0.025955 |
| T N1 APARTMENT ERV | 0.025955 | 0.025955 |
| T N2 APARTMENT ERV | 0.025955 | 0.025955 |
| T S1 APARTMENT ERV | 0.025955 | 0.025955 |
| T S2 APARTMENT ERV | 0.025955 | 0.025955 |
| Design Size Maximum Flow Rate [m3/s] | |
| G SW APARTMENT ERV SUP FAN | 0.025955 |
| G SW APARTMENT ERV EXH FAN | 0.025955 |
| G NW APARTMENT ERV SUP FAN | 0.025955 |
| G NW APARTMENT ERV EXH FAN | 0.025955 |
| G NE APARTMENT ERV SUP FAN | 0.025955 |
| G NE APARTMENT ERV EXH FAN | 0.025955 |
| G N1 APARTMENT ERV SUP FAN | 0.025955 |
| G N1 APARTMENT ERV EXH FAN | 0.025955 |
| G N2 APARTMENT ERV SUP FAN | 0.025955 |
| G N2 APARTMENT ERV EXH FAN | 0.025955 |
| G S1 APARTMENT ERV SUP FAN | 0.025955 |
| G S1 APARTMENT ERV EXH FAN | 0.025955 |
| G S2 APARTMENT ERV SUP FAN | 0.025955 |
| G S2 APARTMENT ERV EXH FAN | 0.025955 |
| M SW APARTMENT ERV SUP FAN | 0.051909 |
| M SW APARTMENT ERV EXH FAN | 0.051909 |
| M NW APARTMENT ERV SUP FAN | 0.051909 |
| M NW APARTMENT ERV EXH FAN | 0.051909 |
| M SE APARTMENT ERV SUP FAN | 0.051909 |
| M SE APARTMENT ERV EXH FAN | 0.051909 |
| M NE APARTMENT ERV SUP FAN | 0.051909 |
| M NE APARTMENT ERV EXH FAN | 0.051909 |
| M N1 APARTMENT ERV SUP FAN | 0.051909 |
| M N1 APARTMENT ERV EXH FAN | 0.051909 |
| M N2 APARTMENT ERV SUP FAN | 0.051909 |
| M N2 APARTMENT ERV EXH FAN | 0.051909 |
| M S1 APARTMENT ERV SUP FAN | 0.051909 |
| M S1 APARTMENT ERV EXH FAN | 0.051909 |
| M S2 APARTMENT ERV SUP FAN | 0.051909 |
| M S2 APARTMENT ERV EXH FAN | 0.051909 |
| T SW APARTMENT ERV SUP FAN | 0.025955 |
| T SW APARTMENT ERV EXH FAN | 0.025955 |
| T NW APARTMENT ERV SUP FAN | 0.025955 |
| T NW APARTMENT ERV EXH FAN | 0.025955 |
| T SE APARTMENT ERV SUP FAN | 0.025955 |
| T SE APARTMENT ERV EXH FAN | 0.025955 |
| T NE APARTMENT ERV SUP FAN | 0.025955 |
| T NE APARTMENT ERV EXH FAN | 0.025955 |
| T N1 APARTMENT ERV SUP FAN | 0.025955 |
| T N1 APARTMENT ERV EXH FAN | 0.025955 |
| T N2 APARTMENT ERV SUP FAN | 0.025955 |
| T N2 APARTMENT ERV EXH FAN | 0.025955 |
| T S1 APARTMENT ERV SUP FAN | 0.025955 |
| T S1 APARTMENT ERV EXH FAN | 0.025955 |
| T S2 APARTMENT ERV SUP FAN | 0.025955 |
| T S2 APARTMENT ERV EXH FAN | 0.025955 |
| SPLIT GSW SUPPLY FAN | 0.309917 |
| SPLIT GNW SUPPLY FAN | 0.300752 |
| SPLIT OFFICE SUPPLY FAN | 0.353159 |
| SPLIT GNE SUPPLY FAN | 0.275763 |
| SPLIT GN1 SUPPLY FAN | 0.248779 |
| SPLIT GN2 SUPPLY FAN | 0.248414 |
| SPLIT GS1 SUPPLY FAN | 0.257526 |
| SPLIT GS2 SUPPLY FAN | 0.259979 |
| SPLIT MSW SUPPLY FAN | 0.741377 |
| SPLIT MNW SUPPLY FAN | 0.724393 |
| SPLIT MSE SUPPLY FAN | 0.675164 |
| SPLIT MNE SUPPLY FAN | 0.658531 |
| SPLIT MN1 SUPPLY FAN | 0.582038 |
| SPLIT MN2 SUPPLY FAN | 0.580295 |
| SPLIT MS1 SUPPLY FAN | 0.602791 |
| SPLIT MS2 SUPPLY FAN | 0.601927 |
| SPLIT TSW SUPPLY FAN | 0.419231 |
| SPLIT TNW SUPPLY FAN | 0.414489 |
| SPLIT TSE SUPPLY FAN | 0.370727 |
| SPLIT TNE SUPPLY FAN | 0.365949 |
| SPLIT TN1 SUPPLY FAN | 0.337972 |
| SPLIT TN2 SUPPLY FAN | 0.336592 |
| SPLIT TS1 SUPPLY FAN | 0.343562 |
| SPLIT TS2 SUPPLY FAN | 0.342185 |
| Design Size Nominal Supply Air Flow Rate [m3/s] | |
| G SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| M SW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M SE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| T SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T SE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| G SW APARTMENT DIRECT AIR | 0.309917 |
| G NW APARTMENT DIRECT AIR | 0.300752 |
| OFFICE DIRECT AIR | 0.353159 |
| G NE APARTMENT DIRECT AIR | 0.275763 |
| G N1 APARTMENT DIRECT AIR | 0.248779 |
| G N2 APARTMENT DIRECT AIR | 0.248414 |
| G S1 APARTMENT DIRECT AIR | 0.257526 |
| G S2 APARTMENT DIRECT AIR | 0.259979 |
| M SW APARTMENT DIRECT AIR | 0.741377 |
| M NW APARTMENT DIRECT AIR | 0.724393 |
| M SE APARTMENT DIRECT AIR | 0.675164 |
| M NE APARTMENT DIRECT AIR | 0.658531 |
| M N1 APARTMENT DIRECT AIR | 0.582038 |
| M N2 APARTMENT DIRECT AIR | 0.580295 |
| M S1 APARTMENT DIRECT AIR | 0.602791 |
| M S2 APARTMENT DIRECT AIR | 0.601927 |
| T SW APARTMENT DIRECT AIR | 0.419231 |
| T NW APARTMENT DIRECT AIR | 0.414489 |
| T SE APARTMENT DIRECT AIR | 0.370727 |
| T NE APARTMENT DIRECT AIR | 0.365949 |
| T N1 APARTMENT DIRECT AIR | 0.337972 |
| T N2 APARTMENT DIRECT AIR | 0.336592 |
| T S1 APARTMENT DIRECT AIR | 0.343562 |
| T S2 APARTMENT DIRECT AIR | 0.342185 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| SPLIT GSW | 0.309917 | 0.309917 | 0.309917 | 0.309917 | 0.309917 | 0.309917 | 1.00 | 1.00 | 0.309917 |
| SPLIT GNW | 0.300752 | 0.300752 | 0.300752 | 0.300752 | 0.300752 | 0.300752 | 1.00 | 1.00 | 0.300752 |
| SPLIT OFFICE | 0.353159 | 0.353159 | 0.353159 | 0.353159 | 0.353159 | 0.353159 | 1.00 | 1.00 | 0.353159 |
| SPLIT GNE | 0.275763 | 0.275763 | 0.275763 | 0.275763 | 0.275763 | 0.275763 | 1.00 | 1.000000 | 0.275763 |
| SPLIT GN1 | 0.248779 | 0.248779 | 0.248779 | 0.248779 | 0.248779 | 0.248779 | 1.00 | 1.00 | 0.248779 |
| SPLIT GN2 | 0.248414 | 0.248414 | 0.248414 | 0.248414 | 0.248414 | 0.248414 | 1.00 | 1.000000 | 0.248414 |
| SPLIT GS1 | 0.257526 | 0.257526 | 0.257526 | 0.257526 | 0.257526 | 0.257526 | 1.00 | 1.00 | 0.257526 |
| SPLIT GS2 | 0.259979 | 0.259979 | 0.259979 | 0.259979 | 0.259979 | 0.259979 | 1.00 | 1.00 | 0.259979 |
| SPLIT MSW | 0.741377 | 0.741377 | 0.741377 | 0.741377 | 0.741377 | 0.741377 | 1.00 | 1.00 | 0.741377 |
| SPLIT MNW | 0.724393 | 0.724393 | 0.724393 | 0.724393 | 0.724393 | 0.724393 | 1.00 | 1.00 | 0.724393 |
| SPLIT MSE | 0.675164 | 0.675164 | 0.675164 | 0.675164 | 0.675164 | 0.675164 | 1.00 | 1.00 | 0.675164 |
| SPLIT MNE | 0.658531 | 0.658531 | 0.658531 | 0.658531 | 0.658531 | 0.658531 | 1.00 | 1.00 | 0.658531 |
| SPLIT MN1 | 0.582038 | 0.582038 | 0.582038 | 0.582038 | 0.582038 | 0.582038 | 1.00 | 1.00 | 0.582038 |
| SPLIT MN2 | 0.580295 | 0.580295 | 0.580295 | 0.580295 | 0.580295 | 0.580295 | 1.00 | 1.00 | 0.580295 |
| SPLIT MS1 | 0.602791 | 0.602791 | 0.602791 | 0.602791 | 0.602791 | 0.602791 | 1.00 | 1.00 | 0.602791 |
| SPLIT MS2 | 0.601927 | 0.601927 | 0.601927 | 0.601927 | 0.601927 | 0.601927 | 1.00 | 1.00 | 0.601927 |
| SPLIT TSW | 0.419231 | 0.419231 | 0.419231 | 0.419231 | 0.419231 | 0.419231 | 1.00 | 1.00 | 0.419231 |
| SPLIT TNW | 0.414489 | 0.414489 | 0.414489 | 0.414489 | 0.414489 | 0.414489 | 1.00 | 1.00 | 0.414489 |
| SPLIT TSE | 0.370727 | 0.370727 | 0.370727 | 0.370727 | 0.370727 | 0.370727 | 1.00 | 1.00 | 0.370727 |
| SPLIT TNE | 0.365949 | 0.365949 | 0.365949 | 0.365949 | 0.365949 | 0.365949 | 1.00 | 1.00 | 0.365949 |
| SPLIT TN1 | 0.337972 | 0.337972 | 0.337972 | 0.337972 | 0.337972 | 0.337972 | 1.00 | 1.000000 | 0.337972 |
| SPLIT TN2 | 0.336592 | 0.336592 | 0.336592 | 0.336592 | 0.336592 | 0.336592 | 1.00 | 1.00 | 0.336592 |
| SPLIT TS1 | 0.343562 | 0.343562 | 0.343562 | 0.343562 | 0.343562 | 0.343562 | 1.00 | 1.000000 | 0.343562 |
| SPLIT TS2 | 0.342185 | 0.342185 | 0.342185 | 0.342185 | 0.342185 | 0.342185 | 1.00 | 1.00 | 0.342185 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| SPLIT GSW_OA_CONTROLLER | 0.309917 | 0.025955 |
| SPLIT GNW_OA_CONTROLLER | 0.300752 | 0.025955 |
| SPLIT OFFICE_OA_CONTROLLER | 0.353159 | 0.038106 |
| SPLIT GNE_OA_CONTROLLER | 0.275763 | 0.025955 |
| SPLIT GN1_OA_CONTROLLER | 0.248779 | 0.025955 |
| SPLIT GN2_OA_CONTROLLER | 0.248414 | 0.025955 |
| SPLIT GS1_OA_CONTROLLER | 0.257526 | 0.025955 |
| SPLIT GS2_OA_CONTROLLER | 0.259979 | 0.025955 |
| SPLIT MSW_OA_CONTROLLER | 0.741377 | 0.051909 |
| SPLIT MNW_OA_CONTROLLER | 0.724393 | 0.051909 |
| SPLIT MSE_OA_CONTROLLER | 0.675164 | 0.051909 |
| SPLIT MNE_OA_CONTROLLER | 0.658531 | 0.051909 |
| SPLIT MN1_OA_CONTROLLER | 0.582038 | 0.051909 |
| SPLIT MN2_OA_CONTROLLER | 0.580295 | 0.051909 |
| SPLIT MS1_OA_CONTROLLER | 0.602791 | 0.051909 |
| SPLIT MS2_OA_CONTROLLER | 0.601927 | 0.051909 |
| SPLIT TSW_OA_CONTROLLER | 0.419231 | 0.025955 |
| SPLIT TNW_OA_CONTROLLER | 0.414489 | 0.025955 |
| SPLIT TSE_OA_CONTROLLER | 0.370727 | 0.025955 |
| SPLIT TNE_OA_CONTROLLER | 0.365949 | 0.025955 |
| SPLIT TN1_OA_CONTROLLER | 0.337972 | 0.025955 |
| SPLIT TN2_OA_CONTROLLER | 0.336592 | 0.025955 |
| SPLIT TS1_OA_CONTROLLER | 0.343562 | 0.025955 |
| SPLIT TS2_OA_CONTROLLER | 0.342185 | 0.025955 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | User-Specified Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| SPLIT GSW_UNITARY_PACKAGE_DX | 0.309917 | 0.309917 | 0.309917 | 0.309917 | 5412.40 | 3626.31 | 40.00 | 5412.40 | 1.00 |
| SPLIT GNW_UNITARY_PACKAGE_DX | 0.300752 | 0.300752 | 0.300752 | 0.300752 | 5243.78 | 3513.33 | 40.00 | 5243.78 | 1.00 |
| SPLIT OFFICE_UNITARY_PACKAGE_DX | 0.353159 | 0.353159 | 0.353159 | 0.353159 | 6100.13 | 4087.08 | 40.00 | 6100.13 | 1.00 |
| SPLIT GNE_UNITARY_PACKAGE_DX | 0.275763 | 0.275763 | 0.275763 | 0.275763 | 4877.85 | 3268.16 | 40.00 | 4877.85 | 1.00 |
| SPLIT GN1_UNITARY_PACKAGE_DX | 0.248779 | 0.248779 | 0.248779 | 0.248779 | 4458.35 | 2987.09 | 40.00 | 4458.35 | 1.00 |
| SPLIT GN2_UNITARY_PACKAGE_DX | 0.248414 | 0.248414 | 0.248414 | 0.248414 | 4452.77 | 2983.36 | 40.00 | 4452.77 | 1.00 |
| SPLIT GS1_UNITARY_PACKAGE_DX | 0.257526 | 0.257526 | 0.257526 | 0.257526 | 4639.74 | 3108.63 | 40.00 | 4639.74 | 1.00 |
| SPLIT GS2_UNITARY_PACKAGE_DX | 0.259979 | 0.259979 | 0.259979 | 0.259979 | 4675.15 | 3132.35 | 40.00 | 4675.15 | 1.00 |
| SPLIT MSW_UNITARY_PACKAGE_DX | 0.741377 | 0.741377 | 0.741377 | 0.741377 | 12669.47 | 8488.54 | 40.00 | 12669.47 | 1.00 |
| SPLIT MNW_UNITARY_PACKAGE_DX | 0.724393 | 0.724393 | 0.724393 | 0.724393 | 12373.00 | 8289.91 | 40.00 | 12373.00 | 1.00 |
| SPLIT MSE_UNITARY_PACKAGE_DX | 0.675164 | 0.675164 | 0.675164 | 0.675164 | 11708.77 | 7844.87 | 40.00 | 11708.77 | 1.00 |
| SPLIT MNE_UNITARY_PACKAGE_DX | 0.658531 | 0.658531 | 0.658531 | 0.658531 | 11408.38 | 7643.61 | 40.00 | 11408.38 | 1.00 |
| SPLIT MN1_UNITARY_PACKAGE_DX | 0.582038 | 0.582038 | 0.582038 | 0.582038 | 10223.39 | 6849.67 | 40.00 | 10223.39 | 1.00 |
| SPLIT MN2_UNITARY_PACKAGE_DX | 0.580295 | 0.580295 | 0.580295 | 0.580295 | 10196.26 | 6831.50 | 40.00 | 10196.26 | 1.00 |
| SPLIT MS1_UNITARY_PACKAGE_DX | 0.602791 | 0.602791 | 0.602791 | 0.602791 | 10606.26 | 7106.19 | 40.00 | 10606.26 | 1.00 |
| SPLIT MS2_UNITARY_PACKAGE_DX | 0.601927 | 0.601927 | 0.601927 | 0.601927 | 10593.28 | 7097.50 | 40.00 | 10593.28 | 1.00 |
| SPLIT TSW_UNITARY_PACKAGE_DX | 0.419231 | 0.419231 | 0.419231 | 0.419231 | 7074.58 | 4739.97 | 40.00 | 7074.58 | 1.00 |
| SPLIT TNW_UNITARY_PACKAGE_DX | 0.414489 | 0.414489 | 0.414489 | 0.414489 | 6987.64 | 4681.72 | 40.00 | 6987.64 | 1.00 |
| SPLIT TSE_UNITARY_PACKAGE_DX | 0.370727 | 0.370727 | 0.370727 | 0.370727 | 6355.25 | 4258.01 | 40.00 | 6355.25 | 1.00 |
| SPLIT TNE_UNITARY_PACKAGE_DX | 0.365949 | 0.365949 | 0.365949 | 0.365949 | 6265.50 | 4197.88 | 40.00 | 6265.50 | 1.00 |
| SPLIT TN1_UNITARY_PACKAGE_DX | 0.337972 | 0.337972 | 0.337972 | 0.337972 | 5801.54 | 3887.03 | 40.00 | 5801.54 | 1.00 |
| SPLIT TN2_UNITARY_PACKAGE_DX | 0.336592 | 0.336592 | 0.336592 | 0.336592 | 5781.04 | 3873.30 | 40.00 | 5781.04 | 1.00 |
| SPLIT TS1_UNITARY_PACKAGE_DX | 0.343562 | 0.343562 | 0.343562 | 0.343562 | 5906.45 | 3957.32 | 40.00 | 5906.45 | 1.00 |
| SPLIT TS2_UNITARY_PACKAGE_DX | 0.342185 | 0.342185 | 0.342185 | 0.342185 | 5886.11 | 3943.69 | 40.00 | 5886.11 | 1.00 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| SPLIT GSW HP COOLING COIL | 0.309917 | 5412.40 | 0.800487 |
| SPLIT GNW HP COOLING COIL | 0.300752 | 5243.78 | 0.800057 |
| SPLIT OFFICE HP COOLING COIL | 0.353159 | 6100.13 | 0.800341 |
| SPLIT GNE HP COOLING COIL | 0.275763 | 4877.85 | 0.800064 |
| SPLIT GN1 HP COOLING COIL | 0.248779 | 4458.35 | 0.800603 |
| SPLIT GN2 HP COOLING COIL | 0.248414 | 4452.77 | 0.800529 |
| SPLIT GS1 HP COOLING COIL | 0.257526 | 4639.74 | 0.800800 |
| SPLIT GS2 HP COOLING COIL | 0.259979 | 4675.15 | 0.800434 |
| SPLIT MSW HP COOLING COIL | 0.741377 | 12669.47 | 0.800133 |
| SPLIT MNW HP COOLING COIL | 0.724393 | 12373.00 | 0.800313 |
| SPLIT MSE HP COOLING COIL | 0.675164 | 11708.77 | 0.800938 |
| SPLIT MNE HP COOLING COIL | 0.658531 | 11408.38 | 0.800305 |
| SPLIT MN1 HP COOLING COIL | 0.582038 | 10223.39 | 0.800488 |
| SPLIT MN2 HP COOLING COIL | 0.580295 | 10196.26 | 0.800369 |
| SPLIT MS1 HP COOLING COIL | 0.602791 | 10606.26 | 0.800889 |
| SPLIT MS2 HP COOLING COIL | 0.601927 | 10593.28 | 0.800816 |
| SPLIT TSW HP COOLING COIL | 0.419231 | 7074.58 | 0.800649 |
| SPLIT TNW HP COOLING COIL | 0.414489 | 6987.64 | 0.800006 |
| SPLIT TSE HP COOLING COIL | 0.370727 | 6355.25 | 0.800021 |
| SPLIT TNE HP COOLING COIL | 0.365949 | 6265.50 | 0.800465 |
| SPLIT TN1 HP COOLING COIL | 0.337972 | 5801.54 | 0.800543 |
| SPLIT TN2 HP COOLING COIL | 0.336592 | 5781.04 | 0.800348 |
| SPLIT TS1 HP COOLING COIL | 0.343562 | 5906.45 | 0.800006 |
| SPLIT TS2 HP COOLING COIL | 0.342185 | 5886.11 | 0.800806 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Heating Capacity [W] | |
| SPLIT GSW HEATING COIL | 0.309917 | 5412.40 |
| SPLIT GNW HEATING COIL | 0.300752 | 5243.78 |
| SPLIT OFFICE HEATING COIL | 0.353159 | 6100.13 |
| SPLIT GNE HEATING COIL | 0.275763 | 4877.85 |
| SPLIT GN1 HEATING COIL | 0.248779 | 4458.35 |
| SPLIT GN2 HEATING COIL | 0.248414 | 4452.77 |
| SPLIT GS1 HEATING COIL | 0.257526 | 4639.74 |
| SPLIT GS2 HEATING COIL | 0.259979 | 4675.15 |
| SPLIT MSW HEATING COIL | 0.741377 | 12669.47 |
| SPLIT MNW HEATING COIL | 0.724393 | 12373.00 |
| SPLIT MSE HEATING COIL | 0.675164 | 11708.77 |
| SPLIT MNE HEATING COIL | 0.658531 | 11408.38 |
| SPLIT MN1 HEATING COIL | 0.582038 | 10223.39 |
| SPLIT MN2 HEATING COIL | 0.580295 | 10196.26 |
| SPLIT MS1 HEATING COIL | 0.602791 | 10606.26 |
| SPLIT MS2 HEATING COIL | 0.601927 | 10593.28 |
| SPLIT TSW HEATING COIL | 0.419231 | 7074.58 |
| SPLIT TNW HEATING COIL | 0.414489 | 6987.64 |
| SPLIT TSE HEATING COIL | 0.370727 | 6355.25 |
| SPLIT TNE HEATING COIL | 0.365949 | 6265.50 |
| SPLIT TN1 HEATING COIL | 0.337972 | 5801.54 |
| SPLIT TN2 HEATING COIL | 0.336592 | 5781.04 |
| SPLIT TS1 HEATING COIL | 0.343562 | 5906.45 |
| SPLIT TS2 HEATING COIL | 0.342185 | 5886.11 |
| Design Size Nominal Capacity [W] | |
| SPLIT GSW_SUPPHEATCOIL | 5412.40 |
| SPLIT GNW_SUPPHEATCOIL | 5243.78 |
| SPLIT OFFICE_SUPPHEATCOIL | 6100.13 |
| SPLIT GNE_SUPPHEATCOIL | 4877.85 |
| SPLIT GN1_SUPPHEATCOIL | 4458.35 |
| SPLIT GN2_SUPPHEATCOIL | 4452.77 |
| SPLIT GS1_SUPPHEATCOIL | 4639.74 |
| SPLIT GS2_SUPPHEATCOIL | 4675.15 |
| SPLIT MSW_SUPPHEATCOIL | 12669.47 |
| SPLIT MNW_SUPPHEATCOIL | 12373.00 |
| SPLIT MSE_SUPPHEATCOIL | 11708.77 |
| SPLIT MNE_SUPPHEATCOIL | 11408.38 |
| SPLIT MN1_SUPPHEATCOIL | 10223.39 |
| SPLIT MN2_SUPPHEATCOIL | 10196.26 |
| SPLIT MS1_SUPPHEATCOIL | 10606.26 |
| SPLIT MS2_SUPPHEATCOIL | 10593.28 |
| SPLIT TSW_SUPPHEATCOIL | 7074.58 |
| SPLIT TNW_SUPPHEATCOIL | 6987.64 |
| SPLIT TSE_SUPPHEATCOIL | 6355.25 |
| SPLIT TNE_SUPPHEATCOIL | 6265.50 |
| SPLIT TN1_SUPPHEATCOIL | 5801.54 |
| SPLIT TN2_SUPPHEATCOIL | 5781.04 |
| SPLIT TS1_SUPPHEATCOIL | 5906.45 |
| SPLIT TS2_SUPPHEATCOIL | 5886.11 |
| Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
| SWHSYS1 | 0.000113 | 0.013615 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | |
| SWHSYS1 PUMP | 0.000113 | 14.49 |
| Use Side Design Flow Rate [m3/s] | |
| SWHSYS1 WATER HEATER | 0.000113 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| G SWALL SWA | GWINDOW1 S SWA | |
| G WWALL SWA | GWINDOW1 W SWA | |
| G NWALL NWA | GWINDOW1 N NWA | |
| G WWALL NWA | GWINDOW1 W NWA | |
| G SWALL SEA | GWINDOW1 S SEA | |
| G EWALL SEA | GWINDOW1 E SEA | |
| G NWALL NEA | GWINDOW1 N NEA | |
| G EWALL NEA | GWINDOW1 E NEA | |
| G NWALL N1A | GWINDOW1 N N1A | |
| G NWALL N2A | GWINDOW1 N N2A | |
| G SWALL S1A | GWINDOW1 S S1A | |
| G SWALL S2A | GWINDOW1 S S2A | |
| M WWALL SWA | MWINDOW1 W SWA | |
| M SWALL SWA | MWINDOW1 S SWA | |
| M NWALL NWA | MWINDOW1 N NWA | |
| M WWALL NWA | MWINDOW1 W NWA | |
| M EWALL SEA | MWINDOW1 E SEA | |
| M SWALL SEA | MWINDOW1 S SEA | |
| M NWALL NEA | MWINDOW1 N NEA | |
| M EWALL NEA | MWINDOW1 E NEA | |
| M NWALL N1A | MWINDOW1 N N1A | |
| M NWALL N2A | MWINDOW1 N N2A | |
| M SWALL S1A | MWINDOW1 S S1A | |
| M SWALL S2A | MWINDOW1 S S2A | |
| T WWALL SWA | TWINDOW1 W SWA | |
| T SWALL SWA | TWINDOW1 S SWA | |
| T NWALL NWA | TWINDOW1 N NWA | |
| T WWALL NWA | TWINDOW1 W NWA | |
| T EWALL SEA | TWINDOW1 E SEA | |
| T SWALL SEA | TWINDOW1 S SEA | |
| T NWALL NEA | TWINDOW1 N NEA | |
| T EWALL NEA | TWINDOW1 E NEA | |
| T NWALL N1A | TWINDOW1 N N1A | |
| T NWALL N2A | TWINDOW1 N N2A | |
| T SWALL S1A | TWINDOW1 S S1A | |
| T SWALL S2A | TWINDOW1 S S2A | |
| T EWALL C | TWINDOW14 | |
| G EWALL C | ENTRANCE DOOR | |
| M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 16.60 | 22.50 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | ApartmentMidRise | 0.000 | City | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Clockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 27 | 243 | 39 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | G SW APARTMENT | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 2 | G NW APARTMENT | 0.0 | 0.00 | 9.30 | 0.00 | 5.79 | 13.11 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 3 | OFFICE | 0.0 | 34.75 | 0.00 | 0.00 | 40.54 | 3.81 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 4 | G NE APARTMENT | 0.0 | 34.75 | 9.30 | 0.00 | 40.54 | 13.11 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 5 | G N1 APARTMENT | 0.0 | 11.58 | 9.30 | 0.00 | 17.37 | 13.11 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 6 | G N2 APARTMENT | 0.0 | 23.16 | 9.30 | 0.00 | 28.95 | 13.11 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 7 | G S1 APARTMENT | 0.0 | 11.58 | 0.00 | 0.00 | 17.37 | 3.81 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 8 | G S2 APARTMENT | 0.0 | 23.16 | 0.00 | 0.00 | 28.95 | 3.81 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 9 | M SW APARTMENT | 0.0 | 0.00 | 0.00 | 3.05 | 5.79 | 3.81 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 10 | M NW APARTMENT | 0.0 | 0.00 | 9.30 | 3.05 | 5.79 | 13.11 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 11 | M SE APARTMENT | 0.0 | 34.75 | 0.00 | 3.05 | 40.54 | 3.81 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 12 | M NE APARTMENT | 0.0 | 34.75 | 9.30 | 3.05 | 40.54 | 13.11 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 13 | M N1 APARTMENT | 0.0 | 11.58 | 9.30 | 3.05 | 17.37 | 13.11 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 14 | M N2 APARTMENT | 0.0 | 23.16 | 9.30 | 3.05 | 28.95 | 13.11 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 15 | M S1 APARTMENT | 0.0 | 11.58 | 0.00 | 3.05 | 17.37 | 3.81 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 16 | M S2 APARTMENT | 0.0 | 23.16 | 0.00 | 3.05 | 28.95 | 3.81 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 17 | T SW APARTMENT | 0.0 | 0.00 | 0.00 | 9.14 | 5.79 | 3.81 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 18 | T NW APARTMENT | 0.0 | 0.00 | 9.30 | 9.14 | 5.79 | 13.11 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 19 | T SE APARTMENT | 0.0 | 34.75 | 0.00 | 9.14 | 40.54 | 3.81 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 20 | T NE APARTMENT | 0.0 | 34.75 | 9.30 | 9.14 | 40.54 | 13.11 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 21 | T N1 APARTMENT | 0.0 | 11.58 | 9.30 | 9.14 | 17.37 | 13.11 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 22 | T N2 APARTMENT | 0.0 | 23.16 | 9.30 | 9.14 | 28.95 | 13.11 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 23 | T S1 APARTMENT | 0.0 | 11.58 | 0.00 | 9.14 | 17.37 | 3.81 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 24 | T S2 APARTMENT | 0.0 | 23.16 | 0.00 | 9.14 | 28.95 | 3.81 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 25 | T CORRIDOR | 0.0 | 0.00 | 7.62 | 9.14 | 23.16 | 8.46 | 10.67 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 9.14 | 12.19 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| 26 | G CORRIDOR | 0.0 | 0.00 | 7.62 | 0.00 | 23.16 | 8.46 | 1.52 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 0.00 | 3.05 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 6.90 | 3.32 | 12 | 1 | 0 | Yes |
| 27 | M CORRIDOR | 0.0 | 0.00 | 7.62 | 3.05 | 23.16 | 8.46 | 4.57 | 1 | 1 | 2 | 0.00 | 46.33 | 7.62 | 9.30 | 3.05 | 6.10 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | G SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 2 | G NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 3 | OFFICE | 88.25 | 4.7 | 18.581 | 5.382E-002 | 7.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 14.160 | No |
| 4 | G NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 5 | G N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 6 | G N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 7 | G S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 8 | G S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 9 | M SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 10 | M NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 11 | M SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 12 | M NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 13 | M N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 14 | M N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 15 | M S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 16 | M S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 17 | T SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 18 | T NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 19 | T SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 20 | T NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 21 | T N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 22 | T N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 23 | T S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 24 | T S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 25 | T CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 5.287 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.287 | No |
| 26 | G CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 5.287 | 515.392 | 0.000 | 0.000 | 0.000 | 0.000 | 520.679 | No |
| 27 | M CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 5.287 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.287 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | OCCUP_GSW | OCC_APT_SCH_WORKING_FAMILY | G SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 2 | OCCUP_GNW | OCC_APT_SCH_STAY_HOME_FAMILY | G NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 3 | OCCUP_OFFICE | OCC_OFF_W_SB_SCH | OFFICE | 88.25 | 4.7 | 4.7 | 5.382E-002 | 18.581 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
| 4 | OCCUP_GNE | OCC_APT_SCH_STAY_HOME_FAMILY | G NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 5 | OCCUP_GN1 | OCC_APT_SCH_STAY_HOME_FAMILY | G N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 6 | OCCUP_GN2 | OCC_APT_SCH_STAY_HOME_FAMILY | G N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 7 | OCCUP_GS1 | OCC_APT_SCH_WORKING_FAMILY | G S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 8 | OCCUP_GS2 | OCC_APT_SCH_WORKING_FAMILY | G S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 9 | OCCUP_MSW | OCC_APT_SCH_WORKING_FAMILY | M SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 10 | OCCUP_MNW | OCC_APT_SCH_STAY_HOME_FAMILY | M NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 11 | OCCUP_MSE | OCC_APT_SCH_WORKING_FAMILY | M SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 12 | OCCUP_MNE | OCC_APT_SCH_STAY_HOME_FAMILY | M NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 13 | OCCUP_MN1 | OCC_APT_SCH_STAY_HOME_FAMILY | M N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 14 | OCCUP_MN2 | OCC_APT_SCH_STAY_HOME_FAMILY | M N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 15 | OCCUP_MS1 | OCC_APT_SCH_WORKING_FAMILY | M S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 16 | OCCUP_MS2 | OCC_APT_SCH_WORKING_FAMILY | M S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 17 | OCCUP_TSW | OCC_APT_SCH_WORKING_FAMILY | T SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 18 | OCCUP_TNW | OCC_APT_SCH_STAY_HOME_FAMILY | T NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 19 | OCCUP_TSE | OCC_APT_SCH_WORKING_FAMILY | T SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 20 | OCCUP_TNE | OCC_APT_SCH_STAY_HOME_FAMILY | T NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 21 | OCCUP_TN1 | OCC_APT_SCH_STAY_HOME_FAMILY | T N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 22 | OCCUP_TN2 | OCC_APT_SCH_STAY_HOME_FAMILY | T N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 23 | OCCUP_TS1 | OCC_APT_SCH_WORKING_FAMILY | T S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 24 | OCCUP_TS2 | OCC_APT_SCH_WORKING_FAMILY | T S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 25 | OCCUP_T CORRIDOR | OCC_APT_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 26 | OCCUP_G CORRIDOR | OCC_APT_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 27 | OCCUP_M CORRIDOR | OCC_APT_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | LIGHTING_HARDWIRED_GSW | LTG_SCH_APARTMENT_HARDWIRED | G SW APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 2 | LIGHTING_HARDWIRED_GNW | LTG_SCH_APARTMENT_HARDWIRED | G NW APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 3 | LIGHTING_HARDWIRED_OFFICE | LTG_SCH_OFFICE | OFFICE | 88.25 | 4.7 | 660.945 | 7.490 | 139.160 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 660.945 |
| 4 | LIGHTING_HARDWIRED_GNE | LTG_SCH_APARTMENT_HARDWIRED | G NE APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 5 | LIGHTING_HARDWIRED_GN1 | LTG_SCH_APARTMENT_HARDWIRED | G N1 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 6 | LIGHTING_HARDWIRED_GN2 | LTG_SCH_APARTMENT_HARDWIRED | G N2 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 7 | LIGHTING_HARDWIRED_GS1 | LTG_SCH_APARTMENT_HARDWIRED | G S1 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 8 | LIGHTING_HARDWIRED_GS2 | LTG_SCH_APARTMENT_HARDWIRED | G S2 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 9 | LIGHTING_HARDWIRED_MSW | LTG_SCH_APARTMENT_HARDWIRED | M SW APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 10 | LIGHTING_HARDWIRED_MNW | LTG_SCH_APARTMENT_HARDWIRED | M NW APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 11 | LIGHTING_HARDWIRED_MSE | LTG_SCH_APARTMENT_HARDWIRED | M SE APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 12 | LIGHTING_HARDWIRED_MNE | LTG_SCH_APARTMENT_HARDWIRED | M NE APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 13 | LIGHTING_HARDWIRED_MN1 | LTG_SCH_APARTMENT_HARDWIRED | M N1 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 14 | LIGHTING_HARDWIRED_MN2 | LTG_SCH_APARTMENT_HARDWIRED | M N2 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 15 | LIGHTING_HARDWIRED_MS1 | LTG_SCH_APARTMENT_HARDWIRED | M S1 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 16 | LIGHTING_HARDWIRED_MS2 | LTG_SCH_APARTMENT_HARDWIRED | M S2 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 17 | LIGHTING_HARDWIRED_TSW | LTG_SCH_APARTMENT_HARDWIRED | T SW APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 18 | LIGHTING_HARDWIRED_TNW | LTG_SCH_APARTMENT_HARDWIRED | T NW APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 19 | LIGHTING_HARDWIRED_TSE | LTG_SCH_APARTMENT_HARDWIRED | T SE APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 20 | LIGHTING_HARDWIRED_TNE | LTG_SCH_APARTMENT_HARDWIRED | T NE APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 21 | LIGHTING_HARDWIRED_TN1 | LTG_SCH_APARTMENT_HARDWIRED | T N1 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 22 | LIGHTING_HARDWIRED_TN2 | LTG_SCH_APARTMENT_HARDWIRED | T N2 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 23 | LIGHTING_HARDWIRED_TS1 | LTG_SCH_APARTMENT_HARDWIRED | T S1 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 24 | LIGHTING_HARDWIRED_TS2 | LTG_SCH_APARTMENT_HARDWIRED | T S2 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 25 | LIGHTING_HARDWIRED_GC | LTG_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 410.594 | 5.287 | 98.228 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 410.594 |
| 26 | LIGHTING_HARDWIRED_MC | LTG_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 410.594 | 5.287 | 98.228 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 410.594 |
| 27 | LIGHTING_HARDWIRED_TC | LTG_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 410.594 | 5.287 | 98.228 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 410.594 |
| 28 | LIGHTING_PLUGIN_GSW | LTG_SCH_APARTMENT_PLUGIN | G SW APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 29 | LIGHTING_PLUGIN_GNW | LTG_SCH_APARTMENT_PLUGIN | G NW APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 30 | LIGHTING_PLUGIN_GNE | LTG_SCH_APARTMENT_PLUGIN | G NE APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 31 | LIGHTING_PLUGIN_GN1 | LTG_SCH_APARTMENT_PLUGIN | G N1 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 32 | LIGHTING_PLUGIN_GN2 | LTG_SCH_APARTMENT_PLUGIN | G N2 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 33 | LIGHTING_PLUGIN_GS1 | LTG_SCH_APARTMENT_PLUGIN | G S1 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 34 | LIGHTING_PLUGIN_GS2 | LTG_SCH_APARTMENT_PLUGIN | G S2 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 35 | LIGHTING_PLUGIN_MSW | LTG_SCH_APARTMENT_PLUGIN | M SW APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 36 | LIGHTING_PLUGIN_MNW | LTG_SCH_APARTMENT_PLUGIN | M NW APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 37 | LIGHTING_PLUGIN_MSE | LTG_SCH_APARTMENT_PLUGIN | M SE APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 38 | LIGHTING_PLUGIN_MNE | LTG_SCH_APARTMENT_PLUGIN | M NE APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 39 | LIGHTING_PLUGIN_MN1 | LTG_SCH_APARTMENT_PLUGIN | M N1 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 40 | LIGHTING_PLUGIN_MN2 | LTG_SCH_APARTMENT_PLUGIN | M N2 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 41 | LIGHTING_PLUGIN_MS1 | LTG_SCH_APARTMENT_PLUGIN | M S1 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 42 | LIGHTING_PLUGIN_MS2 | LTG_SCH_APARTMENT_PLUGIN | M S2 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 43 | LIGHTING_PLUGIN_TSW | LTG_SCH_APARTMENT_PLUGIN | T SW APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 44 | LIGHTING_PLUGIN_TNW | LTG_SCH_APARTMENT_PLUGIN | T NW APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 45 | LIGHTING_PLUGIN_TSE | LTG_SCH_APARTMENT_PLUGIN | T SE APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 46 | LIGHTING_PLUGIN_TNE | LTG_SCH_APARTMENT_PLUGIN | T NE APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 47 | LIGHTING_PLUGIN_TN1 | LTG_SCH_APARTMENT_PLUGIN | T N1 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 48 | LIGHTING_PLUGIN_TN2 | LTG_SCH_APARTMENT_PLUGIN | T N2 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 49 | LIGHTING_PLUGIN_TS1 | LTG_SCH_APARTMENT_PLUGIN | T S1 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 50 | LIGHTING_PLUGIN_TS2 | LTG_SCH_APARTMENT_PLUGIN | T S2 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | G CORRIDOR | 77.66 | 4.2 | 38362.000 | 493.978 | 9177.512 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 0.000 | 2585.215 |
| 2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | G CORRIDOR | 77.66 | 4.2 | 1600.000 | 20.603 | 382.775 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 1187.152 | 1600.000 |
| 3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | G CORRIDOR | 77.66 | 4.2 | 63.000 | 0.811 | 15.072 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLightsFan | 3.150 | 31.500 |
| 4 | PLUG_GSW | EQP_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 5 | PLUG_GNW | EQP_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 6 | PLUG_OFFICE | EQP_OFF_SCH | OFFICE | 88.25 | 4.7 | 588.623 | 6.670 | 123.933 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 588.623 |
| 7 | PLUG_GNE | EQP_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 8 | PLUG_GN1 | EQP_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 9 | PLUG_GN2 | EQP_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 10 | PLUG_GS1 | EQP_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 11 | PLUG_GS2 | EQP_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 12 | PLUG_MSW | EQP_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 13 | PLUG_MNW | EQP_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 14 | PLUG_MSE | EQP_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 15 | PLUG_MNE | EQP_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 16 | PLUG_MN1 | EQP_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 17 | PLUG_MN2 | EQP_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 18 | PLUG_MS1 | EQP_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 19 | PLUG_MS2 | EQP_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 20 | PLUG_TSW | EQP_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 21 | PLUG_TNW | EQP_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 22 | PLUG_TSE | EQP_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 23 | PLUG_TNE | EQP_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 24 | PLUG_TN1 | EQP_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 25 | PLUG_TN2 | EQP_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 26 | PLUG_TS1 | EQP_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 27 | PLUG_TS2 | EQP_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.9460 | 53912.0 | 11.449 | 0.4600 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | G SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 2 | GWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 3 | G WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 4 | GWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 5 | G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 6 | G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 7 | G GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 8 | G CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 9 | G INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 10 | G NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 11 | GWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 12 | G WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 13 | GWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 14 | G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 15 | G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 16 | G GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 17 | G CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 18 | G INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 19 | G SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 20 | GWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 21 | G EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 22 | GWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 23 | G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 24 | iz-G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 25 | G GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 26 | G CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 27 | G INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 28 | G NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 29 | GWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 30 | G EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 31 | GWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 32 | G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 33 | iz-G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 34 | G GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 35 | G CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 36 | G INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 37 | G NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 38 | GWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 39 | G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 40 | G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 41 | iz-G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 42 | G GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 43 | G CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 44 | G INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 45 | G NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 46 | GWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 47 | G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 48 | G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 49 | iz-G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 50 | G GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 51 | G CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 52 | G INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 53 | G SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 54 | GWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 55 | G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 56 | G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 57 | iz-G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 58 | G GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 59 | G CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 60 | G INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 61 | G SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 62 | GWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 63 | G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 64 | G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 65 | iz-G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 66 | G GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 67 | G CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 68 | G INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 69 | M WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 70 | MWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 71 | M SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 72 | MWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 73 | M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 74 | M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 75 | M GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 76 | M CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 77 | M INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 78 | M NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 79 | MWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 80 | M WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 81 | MWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 82 | M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 83 | M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 84 | M GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 85 | M CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 86 | M INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 87 | M EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 88 | MWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 89 | M SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 90 | MWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 91 | M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 92 | iz-M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 93 | M GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 94 | M CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 95 | M INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 96 | M NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 97 | MWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 98 | M EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 99 | MWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 100 | M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 101 | iz-M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 102 | M GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 103 | M CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 104 | M INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 105 | M NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 106 | MWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 107 | M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 108 | M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 109 | iz-M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 110 | M GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 111 | M CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 112 | M INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 113 | M NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 114 | MWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 115 | M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 116 | M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 117 | iz-M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 118 | M GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 119 | M CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 120 | M INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 121 | M SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 122 | MWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 123 | M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 124 | M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 125 | iz-M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 126 | M GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 127 | M CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 128 | M INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 129 | M SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 130 | MWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 131 | M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 132 | M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 133 | iz-M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 134 | M GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 135 | M CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 136 | M INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 137 | T WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 138 | TWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 139 | T SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 140 | TWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 141 | T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 142 | T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 143 | T GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 144 | T ROOF SWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 145 | T INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 146 | T NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 147 | TWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 148 | T WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 149 | TWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 150 | T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 151 | T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 152 | T GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 153 | T ROOF NWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 154 | T INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 155 | T EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 156 | TWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 157 | T SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 158 | TWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 159 | T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 160 | iz-T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 161 | T GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 162 | T ROOF SEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 163 | T INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 164 | T NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 165 | TWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 166 | T EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 167 | TWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 168 | T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 169 | iz-T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 170 | T GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 171 | T ROOF NEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 172 | T INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 173 | T NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 174 | TWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 175 | T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 176 | T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 177 | iz-T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 178 | T GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 179 | T ROOF N1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 180 | T INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 181 | T NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 182 | TWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 183 | T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 184 | T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 185 | iz-T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 186 | T GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 187 | T ROOF N2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 188 | T INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 189 | T SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 190 | TWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 191 | T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 192 | T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 193 | iz-T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 194 | T GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 195 | T ROOF S1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 196 | T INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 197 | T SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 198 | TWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 199 | T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 200 | T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 201 | iz-T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 202 | T GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 203 | T ROOF S2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 204 | T INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 205 | T WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 206 | T EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 207 | TWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 208 | iz-T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 209 | iz-T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 210 | iz-T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 211 | iz-T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 212 | iz-T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 213 | iz-T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 214 | iz-T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 215 | iz-T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 216 | T FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 217 | T ROOF C | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 218 | G WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 219 | G EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 220 | ENTRANCE DOOR | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 1 | No | No |
| 221 | iz-G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 222 | iz-G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 223 | iz-G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 224 | iz-G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 225 | iz-G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 226 | iz-G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 227 | iz-G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 228 | iz-G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 229 | G FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 230 | G CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 231 | M WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 4 | No | No |
| 232 | M EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 233 | MWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 234 | iz-M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 235 | iz-M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 236 | iz-M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 237 | iz-M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 238 | iz-M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 239 | iz-M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 240 | iz-M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 241 | iz-M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 242 | M FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 243 | M CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | INFIL_GSW | INF_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | INFIL_GNW | INF_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | INFIL_OFFICE | INF_OFF_SCH | OFFICE | 88.25 | 4.7 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | INFIL_GNE | INF_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | INFIL_GN1 | INF_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | INFIL_GN2 | INF_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | INFIL_GS1 | INF_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | INFIL_GS2 | INF_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | INFIL_MSW | INF_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | INFIL_MNW | INF_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | INFIL_MSE | INF_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | INFIL_MNE | INF_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | INFIL_MN1 | INF_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | INFIL_MN2 | INF_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | INFIL_MS1 | INF_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | INFIL_MS2 | INF_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | INFIL_SW | INF_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 1.022E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | INFIL_NW | INF_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 1.022E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | INFIL_SE | INF_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 1.022E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | INFIL_NE | INF_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 1.022E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | INFIL_TN1 | INF_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 7.323E-005 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | INFIL_TN2 | INF_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 7.323E-005 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | INFIL_TS1 | INF_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 7.323E-005 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | INFIL_TS2 | INF_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 7.323E-005 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | INFIL_GC | INF_COR_SCH | G CORRIDOR | 77.66 | 4.2 | 2.619E-003 | 3.372E-005 | 2.563E-004 | 3.983E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | DOOR_INFIL_GC | INFIL_DOOR_OPENING_SCH | G CORRIDOR | 77.66 | 4.2 | 0.328 | 4.218E-003 | 3.205E-002 | 4.982 | 1.000 | 0.000 | 0.000 | 0.000 |
| 27 | INFIL_MC | INF_COR_SCH | M CORRIDOR | 77.66 | 4.2 | 2.619E-003 | 3.372E-005 | 2.563E-004 | 3.983E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | INFIL_TC | INF_COR_SCH | T CORRIDOR | 77.66 | 4.2 | 2.619E-003 | 3.372E-005 | 2.980E-005 | 3.983E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | G SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | G NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | G NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | G N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | G N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | G S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | G S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | M SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | M NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | M SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | M NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | M N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | M N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | M S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | M S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | T SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | T NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | T SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | T NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | T N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | T N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 22 | T S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 23 | T S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | G SW APARTMENT | Mixing/Well-Stirred |
| 2 | G NW APARTMENT | Mixing/Well-Stirred |
| 3 | OFFICE | Mixing/Well-Stirred |
| 4 | G NE APARTMENT | Mixing/Well-Stirred |
| 5 | G N1 APARTMENT | Mixing/Well-Stirred |
| 6 | G N2 APARTMENT | Mixing/Well-Stirred |
| 7 | G S1 APARTMENT | Mixing/Well-Stirred |
| 8 | G S2 APARTMENT | Mixing/Well-Stirred |
| 9 | M SW APARTMENT | Mixing/Well-Stirred |
| 10 | M NW APARTMENT | Mixing/Well-Stirred |
| 11 | M SE APARTMENT | Mixing/Well-Stirred |
| 12 | M NE APARTMENT | Mixing/Well-Stirred |
| 13 | M N1 APARTMENT | Mixing/Well-Stirred |
| 14 | M N2 APARTMENT | Mixing/Well-Stirred |
| 15 | M S1 APARTMENT | Mixing/Well-Stirred |
| 16 | M S2 APARTMENT | Mixing/Well-Stirred |
| 17 | T SW APARTMENT | Mixing/Well-Stirred |
| 18 | T NW APARTMENT | Mixing/Well-Stirred |
| 19 | T SE APARTMENT | Mixing/Well-Stirred |
| 20 | T NE APARTMENT | Mixing/Well-Stirred |
| 21 | T N1 APARTMENT | Mixing/Well-Stirred |
| 22 | T N2 APARTMENT | Mixing/Well-Stirred |
| 23 | T S1 APARTMENT | Mixing/Well-Stirred |
| 24 | T S2 APARTMENT | Mixing/Well-Stirred |
| 25 | T CORRIDOR | Mixing/Well-Stirred |
| 26 | G CORRIDOR | Mixing/Well-Stirred |
| 27 | M CORRIDOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | G SW APARTMENT | Cooling | 3535.84425 | 4243.01310 | 0.25826 | 0.30992 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 2 | G SW APARTMENT | Heating | 1449.43448 | 1739.32137 | 6.47770E-002 | 7.77324E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 3 | G NW APARTMENT | Cooling | 3433.58468 | 4120.30161 | 0.25063 | 0.30075 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 4 | G NW APARTMENT | Heating | 1333.97228 | 1600.76673 | 5.96184E-002 | 7.15421E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 5 | OFFICE | Cooling | 3867.09155 | 4640.50985 | 0.29430 | 0.35316 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 29.71333 | 1.44647E-002 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 6 | OFFICE | Heating | 1873.94045 | 2248.72854 | 8.37502E-002 | 0.10050 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | -6.30000 | 2.29779E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 7 | G NE APARTMENT | Cooling | 3156.54056 | 3787.84867 | 0.22980 | 0.27576 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 8 | G NE APARTMENT | Heating | 1328.38633 | 1594.06360 | 5.93688E-002 | 7.12425E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 9 | G N1 APARTMENT | Cooling | 2856.12669 | 3427.35203 | 0.20732 | 0.24878 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 10 | G N1 APARTMENT | Heating | 755.03224 | 906.03869 | 3.37444E-002 | 4.04933E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 11 | G N2 APARTMENT | Cooling | 2852.06659 | 3422.47991 | 0.20701 | 0.24841 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 12 | G N2 APARTMENT | Heating | 754.86003 | 905.83203 | 3.37367E-002 | 4.04841E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 13 | G S1 APARTMENT | Cooling | 2953.27963 | 3543.93555 | 0.21461 | 0.25753 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 14 | G S1 APARTMENT | Heating | 874.42042 | 1049.30451 | 3.90794E-002 | 4.68953E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 15 | G S2 APARTMENT | Cooling | 2980.26256 | 3576.31507 | 0.21665 | 0.25998 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 16 | G S2 APARTMENT | Heating | 884.79493 | 1061.75392 | 3.95431E-002 | 4.74517E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 17 | M SW APARTMENT | Cooling | 8422.77000 | 10107.32399 | 0.61781 | 0.74138 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 18 | M SW APARTMENT | Heating | 2788.62550 | 3346.35060 | 0.12463 | 0.14955 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 19 | M NW APARTMENT | Cooling | 8234.42684 | 9881.31220 | 0.60366 | 0.72439 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 20 | M NW APARTMENT | Heating | 2522.70765 | 3027.24918 | 0.11274 | 0.13529 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 21 | M SE APARTMENT | Cooling | 7689.57324 | 9227.48789 | 0.56264 | 0.67516 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 22 | M SE APARTMENT | Heating | 2775.20178 | 3330.24214 | 0.12403 | 0.14883 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 23 | M NE APARTMENT | Cooling | 7504.75745 | 9005.70894 | 0.54878 | 0.65853 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 24 | M NE APARTMENT | Heating | 2509.22615 | 3011.07138 | 0.11214 | 0.13457 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 25 | M N1 APARTMENT | Cooling | 6650.89434 | 7981.07321 | 0.48503 | 0.58204 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 26 | M N1 APARTMENT | Heating | 1302.37562 | 1562.85074 | 5.82061E-002 | 6.98473E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 27 | M N2 APARTMENT | Cooling | 6631.36706 | 7957.64047 | 0.48358 | 0.58029 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 28 | M N2 APARTMENT | Heating | 1302.01364 | 1562.41636 | 5.81899E-002 | 6.98279E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 29 | M S1 APARTMENT | Cooling | 6882.25478 | 8258.70573 | 0.50233 | 0.60279 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 30 | M S1 APARTMENT | Heating | 1561.04130 | 1873.24956 | 6.97652E-002 | 8.37182E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 31 | M S2 APARTMENT | Cooling | 6872.64936 | 8247.17923 | 0.50161 | 0.60193 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 32 | M S2 APARTMENT | Heating | 1560.68414 | 1872.82097 | 6.97492E-002 | 8.36991E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 33 | T SW APARTMENT | Cooling | 4754.25002 | 5705.10003 | 0.34936 | 0.41923 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 34 | T SW APARTMENT | Heating | 2327.21068 | 2792.65282 | 0.10400 | 0.12480 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 35 | T NW APARTMENT | Cooling | 4701.00056 | 5641.20068 | 0.34541 | 0.41449 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 36 | T NW APARTMENT | Heating | 2186.72376 | 2624.06852 | 9.77264E-002 | 0.11727 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 37 | T SE APARTMENT | Cooling | 4213.80591 | 5056.56710 | 0.30894 | 0.37073 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 38 | T SE APARTMENT | Heating | 2318.94402 | 2782.73282 | 0.10363 | 0.12436 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 39 | T NE APARTMENT | Cooling | 4160.49184 | 4992.59020 | 0.30496 | 0.36595 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 40 | T NE APARTMENT | Heating | 2178.38246 | 2614.05895 | 9.73536E-002 | 0.11682 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 41 | T N1 APARTMENT | Cooling | 3849.98058 | 4619.97670 | 0.28164 | 0.33797 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 42 | T N1 APARTMENT | Heating | 1498.64939 | 1798.37927 | 6.69774E-002 | 8.03729E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 43 | T N2 APARTMENT | Cooling | 3834.69298 | 4601.63158 | 0.28049 | 0.33659 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 44 | T N2 APARTMENT | Heating | 1498.40706 | 1798.08847 | 6.69666E-002 | 8.03599E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 45 | T S1 APARTMENT | Cooling | 3912.08288 | 4694.49946 | 0.28630 | 0.34356 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 46 | T S1 APARTMENT | Heating | 1639.09073 | 1966.90888 | 7.32527E-002 | 8.79032E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 47 | T S2 APARTMENT | Cooling | 3896.81349 | 4676.17618 | 0.28515 | 0.34219 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 48 | T S2 APARTMENT | Heating | 1638.85250 | 1966.62300 | 7.32420E-002 | 8.78904E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -6.30000 | 2.29779E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | SPLIT GSW | Cooling | Sensible | 4262.58 | 0.30992 | 0.30992 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 2 | SPLIT GSW | Heating | Sensible | 2543.61 | 7.77324E-002 | 7.77324E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 |
| 3 | SPLIT GNW | Cooling | Sensible | 4141.24 | 0.30075 | 0.30075 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | SPLIT GNW | Heating | Sensible | 2407.09 | 7.15421E-002 | 7.15421E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
| 5 | SPLIT OFFICE | Cooling | Sensible | 4831.38 | 0.35316 | 0.35316 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | SPLIT OFFICE | Heating | Sensible | 3434.03 | 0.10050 | 0.10050 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 |
| 7 | SPLIT GNE | Cooling | Sensible | 3811.32 | 0.27576 | 0.27576 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 8 | SPLIT GNE | Heating | Sensible | 2400.49 | 7.12425E-002 | 7.12425E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
| 9 | SPLIT GN1 | Cooling | Sensible | 3454.62 | 0.24878 | 0.24878 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 10 | SPLIT GN1 | Heating | Sensible | 1722.49 | 4.04933E-002 | 4.04933E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
| 11 | SPLIT GN2 | Cooling | Sensible | 3449.79 | 0.24841 | 0.24841 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 12 | SPLIT GN2 | Heating | Sensible | 1722.28 | 4.04841E-002 | 4.04841E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
| 13 | SPLIT GS1 | Cooling | Sensible | 3570.03 | 0.25753 | 0.25753 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 14 | SPLIT GS1 | Heating | Sensible | 1863.65 | 4.68953E-002 | 4.68953E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 |
| 15 | SPLIT GS2 | Cooling | Sensible | 3601.95 | 0.25998 | 0.25998 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 16 | SPLIT GS2 | Heating | Sensible | 1875.92 | 4.74517E-002 | 4.74517E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 |
| 17 | SPLIT MSW | Cooling | Sensible | 10129.39 | 0.74138 | 0.74138 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 18 | SPLIT MSW | Heating | Sensible | 4956.85 | 0.14955 | 0.14955 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 19 | SPLIT MNW | Cooling | Sensible | 9905.45 | 0.72439 | 0.72439 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 20 | SPLIT MNW | Heating | Sensible | 4642.41 | 0.13529 | 0.13529 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 21 | SPLIT MSE | Cooling | Sensible | 9257.11 | 0.67516 | 0.67516 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 22 | SPLIT MSE | Heating | Sensible | 4940.97 | 0.14883 | 0.14883 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 23 | SPLIT MNE | Cooling | Sensible | 9037.51 | 0.65853 | 0.65853 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 24 | SPLIT MNE | Heating | Sensible | 4626.47 | 0.13457 | 0.13457 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 25 | SPLIT MN1 | Cooling | Sensible | 8025.76 | 0.58204 | 0.58204 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 26 | SPLIT MN1 | Heating | Sensible | 3199.36 | 6.98473E-002 | 6.98473E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 27 | SPLIT MN2 | Cooling | Sensible | 8002.40 | 0.58029 | 0.58029 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 28 | SPLIT MN2 | Heating | Sensible | 3198.94 | 6.98279E-002 | 6.98279E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 29 | SPLIT MS1 | Cooling | Sensible | 8300.64 | 0.60279 | 0.60279 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 30 | SPLIT MS1 | Heating | Sensible | 3505.22 | 8.37182E-002 | 8.37182E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 31 | SPLIT MS2 | Cooling | Sensible | 8289.24 | 0.60193 | 0.60193 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 32 | SPLIT MS2 | Heating | Sensible | 3504.80 | 8.36991E-002 | 8.36991E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 33 | SPLIT TSW | Cooling | Sensible | 5707.10 | 0.41923 | 0.41923 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 34 | SPLIT TSW | Heating | Sensible | 3581.59 | 0.12480 | 0.12480 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 35 | SPLIT TNW | Cooling | Sensible | 5644.32 | 0.41449 | 0.41449 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 36 | SPLIT TNW | Heating | Sensible | 3415.47 | 0.11727 | 0.11727 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 37 | SPLIT TSE | Cooling | Sensible | 5067.18 | 0.37073 | 0.37073 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 38 | SPLIT TSE | Heating | Sensible | 3571.81 | 0.12436 | 0.12436 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 39 | SPLIT TNE | Cooling | Sensible | 5004.04 | 0.36595 | 0.36595 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 40 | SPLIT TNE | Heating | Sensible | 3405.60 | 0.11682 | 0.11682 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 41 | SPLIT TN1 | Cooling | Sensible | 4635.43 | 0.33797 | 0.33797 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 42 | SPLIT TN1 | Heating | Sensible | 2601.82 | 8.03729E-002 | 8.03729E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 43 | SPLIT TN2 | Cooling | Sensible | 4617.26 | 0.33659 | 0.33659 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 44 | SPLIT TN2 | Heating | Sensible | 2601.53 | 8.03599E-002 | 8.03599E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 45 | SPLIT TS1 | Cooling | Sensible | 4709.20 | 0.34356 | 0.34356 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 46 | SPLIT TS1 | Heating | Sensible | 2767.88 | 8.79032E-002 | 8.79032E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 47 | SPLIT TS2 | Cooling | Sensible | 4691.07 | 0.34219 | 0.34219 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 48 | SPLIT TS2 | Heating | Sensible | 2767.60 | 8.78904E-002 | 8.78904E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 2 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 3 | Fan:OnOff | G SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 4 | Fan:OnOff | G SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 5 | HeatExchanger:AirToAir:SensibleAndLatent | G SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.30992 |
| 7 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 8 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 9 | Fan:OnOff | G NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 10 | Fan:OnOff | G NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 11 | HeatExchanger:AirToAir:SensibleAndLatent | G NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.30075 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.35316 |
| 14 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 15 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 16 | Fan:OnOff | G NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 17 | Fan:OnOff | G NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 18 | HeatExchanger:AirToAir:SensibleAndLatent | G NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.27576 |
| 20 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 21 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 22 | Fan:OnOff | G N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 23 | Fan:OnOff | G N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 24 | HeatExchanger:AirToAir:SensibleAndLatent | G N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 25 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.24878 |
| 26 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 27 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 28 | Fan:OnOff | G N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 29 | Fan:OnOff | G N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 30 | HeatExchanger:AirToAir:SensibleAndLatent | G N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 31 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.24841 |
| 32 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 33 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 34 | Fan:OnOff | G S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 35 | Fan:OnOff | G S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 36 | HeatExchanger:AirToAir:SensibleAndLatent | G S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 37 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.25753 |
| 38 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 39 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 40 | Fan:OnOff | G S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 41 | Fan:OnOff | G S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 42 | HeatExchanger:AirToAir:SensibleAndLatent | G S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 43 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.25998 |
| 44 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 45 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 46 | Fan:OnOff | M SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 47 | Fan:OnOff | M SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 48 | HeatExchanger:AirToAir:SensibleAndLatent | M SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 49 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.74138 |
| 50 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 51 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 52 | Fan:OnOff | M NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 53 | Fan:OnOff | M NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 54 | HeatExchanger:AirToAir:SensibleAndLatent | M NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 55 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.72439 |
| 56 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 57 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 58 | Fan:OnOff | M SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 59 | Fan:OnOff | M SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 60 | HeatExchanger:AirToAir:SensibleAndLatent | M SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.67516 |
| 62 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 63 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 64 | Fan:OnOff | M NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 65 | Fan:OnOff | M NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 66 | HeatExchanger:AirToAir:SensibleAndLatent | M NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 67 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.65853 |
| 68 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 69 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 70 | Fan:OnOff | M N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 71 | Fan:OnOff | M N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 72 | HeatExchanger:AirToAir:SensibleAndLatent | M N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 73 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.58204 |
| 74 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 75 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 76 | Fan:OnOff | M N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 77 | Fan:OnOff | M N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 78 | HeatExchanger:AirToAir:SensibleAndLatent | M N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 79 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.58029 |
| 80 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 81 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 82 | Fan:OnOff | M S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 83 | Fan:OnOff | M S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 84 | HeatExchanger:AirToAir:SensibleAndLatent | M S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 85 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.60279 |
| 86 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 87 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 88 | Fan:OnOff | M S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 89 | Fan:OnOff | M S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 90 | HeatExchanger:AirToAir:SensibleAndLatent | M S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 91 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.60193 |
| 92 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 93 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 94 | Fan:OnOff | T SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 95 | Fan:OnOff | T SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 96 | HeatExchanger:AirToAir:SensibleAndLatent | T SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.41923 |
| 98 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 99 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 100 | Fan:OnOff | T NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 101 | Fan:OnOff | T NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 102 | HeatExchanger:AirToAir:SensibleAndLatent | T NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 103 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.41449 |
| 104 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 105 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 106 | Fan:OnOff | T SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 107 | Fan:OnOff | T SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 108 | HeatExchanger:AirToAir:SensibleAndLatent | T SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 109 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37073 |
| 110 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 111 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 112 | Fan:OnOff | T NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 113 | Fan:OnOff | T NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 114 | HeatExchanger:AirToAir:SensibleAndLatent | T NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 115 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.36595 |
| 116 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 117 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 118 | Fan:OnOff | T N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 119 | Fan:OnOff | T N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 120 | HeatExchanger:AirToAir:SensibleAndLatent | T N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 121 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33797 |
| 122 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 123 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 124 | Fan:OnOff | T N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 125 | Fan:OnOff | T N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 126 | HeatExchanger:AirToAir:SensibleAndLatent | T N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33659 |
| 128 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 129 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 130 | Fan:OnOff | T S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 131 | Fan:OnOff | T S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 132 | HeatExchanger:AirToAir:SensibleAndLatent | T S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 133 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34356 |
| 134 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 135 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 136 | Fan:OnOff | T S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 137 | Fan:OnOff | T S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 138 | HeatExchanger:AirToAir:SensibleAndLatent | T S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 139 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34219 |
| 140 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.30992 |
| 141 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.30992 |
| 142 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.30992 |
| 143 | AirLoopHVAC | SPLIT GSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.30992 |
| 144 | AirLoopHVAC | SPLIT GSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.30992 |
| 145 | AirLoopHVAC | SPLIT GSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.30992 |
| 146 | AirLoopHVAC | SPLIT GSW | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | SPLIT GSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.30075 |
| 149 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.30075 |
| 150 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.30075 |
| 151 | AirLoopHVAC | SPLIT GNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.30075 |
| 152 | AirLoopHVAC | SPLIT GNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.30075 |
| 153 | AirLoopHVAC | SPLIT GNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.30075 |
| 154 | AirLoopHVAC | SPLIT GNW | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | SPLIT GNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.35316 |
| 157 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.35316 |
| 158 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.35316 |
| 159 | AirLoopHVAC | SPLIT OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.35316 |
| 160 | AirLoopHVAC | SPLIT OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.35316 |
| 161 | AirLoopHVAC | SPLIT OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.35316 |
| 162 | AirLoopHVAC | SPLIT OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | SPLIT OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.27576 |
| 165 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.27576 |
| 166 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.27576 |
| 167 | AirLoopHVAC | SPLIT GNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.27576 |
| 168 | AirLoopHVAC | SPLIT GNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.27576 |
| 169 | AirLoopHVAC | SPLIT GNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.27576 |
| 170 | AirLoopHVAC | SPLIT GNE | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | SPLIT GNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.24878 |
| 173 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.24878 |
| 174 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.24878 |
| 175 | AirLoopHVAC | SPLIT GN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.24878 |
| 176 | AirLoopHVAC | SPLIT GN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.24878 |
| 177 | AirLoopHVAC | SPLIT GN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.24878 |
| 178 | AirLoopHVAC | SPLIT GN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 179 | AirLoopHVAC | SPLIT GN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 180 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.24841 |
| 181 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.24841 |
| 182 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.24841 |
| 183 | AirLoopHVAC | SPLIT GN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.24841 |
| 184 | AirLoopHVAC | SPLIT GN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.24841 |
| 185 | AirLoopHVAC | SPLIT GN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.24841 |
| 186 | AirLoopHVAC | SPLIT GN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 187 | AirLoopHVAC | SPLIT GN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 188 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.25753 |
| 189 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.25753 |
| 190 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.25753 |
| 191 | AirLoopHVAC | SPLIT GS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.25753 |
| 192 | AirLoopHVAC | SPLIT GS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.25753 |
| 193 | AirLoopHVAC | SPLIT GS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.25753 |
| 194 | AirLoopHVAC | SPLIT GS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 195 | AirLoopHVAC | SPLIT GS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 196 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.25998 |
| 197 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.25998 |
| 198 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.25998 |
| 199 | AirLoopHVAC | SPLIT GS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.25998 |
| 200 | AirLoopHVAC | SPLIT GS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.25998 |
| 201 | AirLoopHVAC | SPLIT GS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.25998 |
| 202 | AirLoopHVAC | SPLIT GS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 203 | AirLoopHVAC | SPLIT GS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 204 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.74138 |
| 205 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.74138 |
| 206 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.74138 |
| 207 | AirLoopHVAC | SPLIT MSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.74138 |
| 208 | AirLoopHVAC | SPLIT MSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.74138 |
| 209 | AirLoopHVAC | SPLIT MSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.74138 |
| 210 | AirLoopHVAC | SPLIT MSW | User Heating Air Flow Ratio [] | 1.00000 |
| 211 | AirLoopHVAC | SPLIT MSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 212 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.72439 |
| 213 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.72439 |
| 214 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.72439 |
| 215 | AirLoopHVAC | SPLIT MNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.72439 |
| 216 | AirLoopHVAC | SPLIT MNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.72439 |
| 217 | AirLoopHVAC | SPLIT MNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.72439 |
| 218 | AirLoopHVAC | SPLIT MNW | User Heating Air Flow Ratio [] | 1.00000 |
| 219 | AirLoopHVAC | SPLIT MNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 220 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.67516 |
| 221 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.67516 |
| 222 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.67516 |
| 223 | AirLoopHVAC | SPLIT MSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.67516 |
| 224 | AirLoopHVAC | SPLIT MSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.67516 |
| 225 | AirLoopHVAC | SPLIT MSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.67516 |
| 226 | AirLoopHVAC | SPLIT MSE | User Heating Air Flow Ratio [] | 1.00000 |
| 227 | AirLoopHVAC | SPLIT MSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 228 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.65853 |
| 229 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.65853 |
| 230 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.65853 |
| 231 | AirLoopHVAC | SPLIT MNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.65853 |
| 232 | AirLoopHVAC | SPLIT MNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.65853 |
| 233 | AirLoopHVAC | SPLIT MNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.65853 |
| 234 | AirLoopHVAC | SPLIT MNE | User Heating Air Flow Ratio [] | 1.00000 |
| 235 | AirLoopHVAC | SPLIT MNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 236 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.58204 |
| 237 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.58204 |
| 238 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.58204 |
| 239 | AirLoopHVAC | SPLIT MN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.58204 |
| 240 | AirLoopHVAC | SPLIT MN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.58204 |
| 241 | AirLoopHVAC | SPLIT MN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.58204 |
| 242 | AirLoopHVAC | SPLIT MN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 243 | AirLoopHVAC | SPLIT MN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 244 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.58029 |
| 245 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.58029 |
| 246 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.58029 |
| 247 | AirLoopHVAC | SPLIT MN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.58029 |
| 248 | AirLoopHVAC | SPLIT MN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.58029 |
| 249 | AirLoopHVAC | SPLIT MN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.58029 |
| 250 | AirLoopHVAC | SPLIT MN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 251 | AirLoopHVAC | SPLIT MN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 252 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.60279 |
| 253 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.60279 |
| 254 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.60279 |
| 255 | AirLoopHVAC | SPLIT MS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.60279 |
| 256 | AirLoopHVAC | SPLIT MS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.60279 |
| 257 | AirLoopHVAC | SPLIT MS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.60279 |
| 258 | AirLoopHVAC | SPLIT MS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 259 | AirLoopHVAC | SPLIT MS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 260 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.60193 |
| 261 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.60193 |
| 262 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.60193 |
| 263 | AirLoopHVAC | SPLIT MS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.60193 |
| 264 | AirLoopHVAC | SPLIT MS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.60193 |
| 265 | AirLoopHVAC | SPLIT MS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.60193 |
| 266 | AirLoopHVAC | SPLIT MS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 267 | AirLoopHVAC | SPLIT MS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 268 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.41923 |
| 269 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.41923 |
| 270 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.41923 |
| 271 | AirLoopHVAC | SPLIT TSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.41923 |
| 272 | AirLoopHVAC | SPLIT TSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.41923 |
| 273 | AirLoopHVAC | SPLIT TSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.41923 |
| 274 | AirLoopHVAC | SPLIT TSW | User Heating Air Flow Ratio [] | 1.00000 |
| 275 | AirLoopHVAC | SPLIT TSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 276 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.41449 |
| 277 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.41449 |
| 278 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.41449 |
| 279 | AirLoopHVAC | SPLIT TNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.41449 |
| 280 | AirLoopHVAC | SPLIT TNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.41449 |
| 281 | AirLoopHVAC | SPLIT TNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.41449 |
| 282 | AirLoopHVAC | SPLIT TNW | User Heating Air Flow Ratio [] | 1.00000 |
| 283 | AirLoopHVAC | SPLIT TNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 284 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37073 |
| 285 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37073 |
| 286 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37073 |
| 287 | AirLoopHVAC | SPLIT TSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37073 |
| 288 | AirLoopHVAC | SPLIT TSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37073 |
| 289 | AirLoopHVAC | SPLIT TSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.37073 |
| 290 | AirLoopHVAC | SPLIT TSE | User Heating Air Flow Ratio [] | 1.00000 |
| 291 | AirLoopHVAC | SPLIT TSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 292 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.36595 |
| 293 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.36595 |
| 294 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.36595 |
| 295 | AirLoopHVAC | SPLIT TNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.36595 |
| 296 | AirLoopHVAC | SPLIT TNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.36595 |
| 297 | AirLoopHVAC | SPLIT TNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.36595 |
| 298 | AirLoopHVAC | SPLIT TNE | User Heating Air Flow Ratio [] | 1.00000 |
| 299 | AirLoopHVAC | SPLIT TNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 300 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33797 |
| 301 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33797 |
| 302 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33797 |
| 303 | AirLoopHVAC | SPLIT TN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33797 |
| 304 | AirLoopHVAC | SPLIT TN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33797 |
| 305 | AirLoopHVAC | SPLIT TN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33797 |
| 306 | AirLoopHVAC | SPLIT TN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 307 | AirLoopHVAC | SPLIT TN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 308 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33659 |
| 309 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33659 |
| 310 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33659 |
| 311 | AirLoopHVAC | SPLIT TN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33659 |
| 312 | AirLoopHVAC | SPLIT TN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33659 |
| 313 | AirLoopHVAC | SPLIT TN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33659 |
| 314 | AirLoopHVAC | SPLIT TN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 315 | AirLoopHVAC | SPLIT TN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 316 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34356 |
| 317 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34356 |
| 318 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34356 |
| 319 | AirLoopHVAC | SPLIT TS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34356 |
| 320 | AirLoopHVAC | SPLIT TS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34356 |
| 321 | AirLoopHVAC | SPLIT TS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.34356 |
| 322 | AirLoopHVAC | SPLIT TS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 323 | AirLoopHVAC | SPLIT TS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 324 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34219 |
| 325 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34219 |
| 326 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34219 |
| 327 | AirLoopHVAC | SPLIT TS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34219 |
| 328 | AirLoopHVAC | SPLIT TS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34219 |
| 329 | AirLoopHVAC | SPLIT TS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.34219 |
| 330 | AirLoopHVAC | SPLIT TS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 331 | AirLoopHVAC | SPLIT TS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 332 | AirLoopHVAC | SPLIT GSW | Design Supply Air Flow Rate [m3/s] | 0.30992 |
| 333 | AirLoopHVAC | SPLIT GNW | Design Supply Air Flow Rate [m3/s] | 0.30075 |
| 334 | AirLoopHVAC | SPLIT OFFICE | Design Supply Air Flow Rate [m3/s] | 0.35316 |
| 335 | AirLoopHVAC | SPLIT GNE | Design Supply Air Flow Rate [m3/s] | 0.27576 |
| 336 | AirLoopHVAC | SPLIT GN1 | Design Supply Air Flow Rate [m3/s] | 0.24878 |
| 337 | AirLoopHVAC | SPLIT GN2 | Design Supply Air Flow Rate [m3/s] | 0.24841 |
| 338 | AirLoopHVAC | SPLIT GS1 | Design Supply Air Flow Rate [m3/s] | 0.25753 |
| 339 | AirLoopHVAC | SPLIT GS2 | Design Supply Air Flow Rate [m3/s] | 0.25998 |
| 340 | AirLoopHVAC | SPLIT MSW | Design Supply Air Flow Rate [m3/s] | 0.74138 |
| 341 | AirLoopHVAC | SPLIT MNW | Design Supply Air Flow Rate [m3/s] | 0.72439 |
| 342 | AirLoopHVAC | SPLIT MSE | Design Supply Air Flow Rate [m3/s] | 0.67516 |
| 343 | AirLoopHVAC | SPLIT MNE | Design Supply Air Flow Rate [m3/s] | 0.65853 |
| 344 | AirLoopHVAC | SPLIT MN1 | Design Supply Air Flow Rate [m3/s] | 0.58204 |
| 345 | AirLoopHVAC | SPLIT MN2 | Design Supply Air Flow Rate [m3/s] | 0.58029 |
| 346 | AirLoopHVAC | SPLIT MS1 | Design Supply Air Flow Rate [m3/s] | 0.60279 |
| 347 | AirLoopHVAC | SPLIT MS2 | Design Supply Air Flow Rate [m3/s] | 0.60193 |
| 348 | AirLoopHVAC | SPLIT TSW | Design Supply Air Flow Rate [m3/s] | 0.41923 |
| 349 | AirLoopHVAC | SPLIT TNW | Design Supply Air Flow Rate [m3/s] | 0.41449 |
| 350 | AirLoopHVAC | SPLIT TSE | Design Supply Air Flow Rate [m3/s] | 0.37073 |
| 351 | AirLoopHVAC | SPLIT TNE | Design Supply Air Flow Rate [m3/s] | 0.36595 |
| 352 | AirLoopHVAC | SPLIT TN1 | Design Supply Air Flow Rate [m3/s] | 0.33797 |
| 353 | AirLoopHVAC | SPLIT TN2 | Design Supply Air Flow Rate [m3/s] | 0.33659 |
| 354 | AirLoopHVAC | SPLIT TS1 | Design Supply Air Flow Rate [m3/s] | 0.34356 |
| 355 | AirLoopHVAC | SPLIT TS2 | Design Supply Air Flow Rate [m3/s] | 0.34219 |
| 356 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.30992 |
| 357 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 358 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.30992 |
| 359 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.30992 |
| 360 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.30992 |
| 361 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.30992 |
| 362 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5412.40428 |
| 363 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 3626.31086 |
| 364 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 365 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 5412.40428 |
| 366 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 367 | Fan:OnOff | SPLIT GSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.30992 |
| 368 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.30992 |
| 369 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5412.40428 |
| 370 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80049 |
| 371 | Coil:Heating:DX:SingleSpeed | SPLIT GSW HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.30992 |
| 372 | Coil:Heating:DX:SingleSpeed | SPLIT GSW HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 5412.40428 |
| 373 | Coil:Heating:Electric | SPLIT GSW_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5412.40428 |
| 374 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.30075 |
| 375 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 376 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.30075 |
| 377 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.30075 |
| 378 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.30075 |
| 379 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.30075 |
| 380 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5243.78237 |
| 381 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 3513.33419 |
| 382 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 383 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 5243.78237 |
| 384 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 385 | Fan:OnOff | SPLIT GNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.30075 |
| 386 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.30075 |
| 387 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5243.78237 |
| 388 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80006 |
| 389 | Coil:Heating:DX:SingleSpeed | SPLIT GNW HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.30075 |
| 390 | Coil:Heating:DX:SingleSpeed | SPLIT GNW HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 5243.78237 |
| 391 | Coil:Heating:Electric | SPLIT GNW_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5243.78237 |
| 392 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.35316 |
| 393 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.81060E-002 |
| 394 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.35316 |
| 395 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.35316 |
| 396 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.35316 |
| 397 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.35316 |
| 398 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6100.12596 |
| 399 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4087.08439 |
| 400 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 401 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 6100.12596 |
| 402 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 403 | Fan:OnOff | SPLIT OFFICE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.35316 |
| 404 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.35316 |
| 405 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6100.12596 |
| 406 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80034 |
| 407 | Coil:Heating:DX:SingleSpeed | SPLIT OFFICE HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.35316 |
| 408 | Coil:Heating:DX:SingleSpeed | SPLIT OFFICE HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6100.12596 |
| 409 | Coil:Heating:Electric | SPLIT OFFICE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6100.12596 |
| 410 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.27576 |
| 411 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 412 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.27576 |
| 413 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.27576 |
| 414 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.27576 |
| 415 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.27576 |
| 416 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4877.85081 |
| 417 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 3268.16004 |
| 418 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 419 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 4877.85081 |
| 420 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 421 | Fan:OnOff | SPLIT GNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.27576 |
| 422 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.27576 |
| 423 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4877.85081 |
| 424 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80006 |
| 425 | Coil:Heating:DX:SingleSpeed | SPLIT GNE HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.27576 |
| 426 | Coil:Heating:DX:SingleSpeed | SPLIT GNE HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 4877.85081 |
| 427 | Coil:Heating:Electric | SPLIT GNE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 4877.85081 |
| 428 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.24878 |
| 429 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 430 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.24878 |
| 431 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.24878 |
| 432 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.24878 |
| 433 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.24878 |
| 434 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4458.34580 |
| 435 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 2987.09169 |
| 436 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 437 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 4458.34580 |
| 438 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 439 | Fan:OnOff | SPLIT GN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.24878 |
| 440 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.24878 |
| 441 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4458.34580 |
| 442 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80060 |
| 443 | Coil:Heating:DX:SingleSpeed | SPLIT GN1 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.24878 |
| 444 | Coil:Heating:DX:SingleSpeed | SPLIT GN1 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 4458.34580 |
| 445 | Coil:Heating:Electric | SPLIT GN1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 4458.34580 |
| 446 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.24841 |
| 447 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 448 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.24841 |
| 449 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.24841 |
| 450 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.24841 |
| 451 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.24841 |
| 452 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4452.77453 |
| 453 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 2983.35893 |
| 454 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 455 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 4452.77453 |
| 456 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 457 | Fan:OnOff | SPLIT GN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.24841 |
| 458 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.24841 |
| 459 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4452.77453 |
| 460 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80053 |
| 461 | Coil:Heating:DX:SingleSpeed | SPLIT GN2 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.24841 |
| 462 | Coil:Heating:DX:SingleSpeed | SPLIT GN2 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 4452.77453 |
| 463 | Coil:Heating:Electric | SPLIT GN2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 4452.77453 |
| 464 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.25753 |
| 465 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 466 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.25753 |
| 467 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.25753 |
| 468 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.25753 |
| 469 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.25753 |
| 470 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4639.74125 |
| 471 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 3108.62664 |
| 472 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 473 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 4639.74125 |
| 474 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 475 | Fan:OnOff | SPLIT GS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.25753 |
| 476 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.25753 |
| 477 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4639.74125 |
| 478 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80080 |
| 479 | Coil:Heating:DX:SingleSpeed | SPLIT GS1 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.25753 |
| 480 | Coil:Heating:DX:SingleSpeed | SPLIT GS1 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 4639.74125 |
| 481 | Coil:Heating:Electric | SPLIT GS1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 4639.74125 |
| 482 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.25998 |
| 483 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 484 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.25998 |
| 485 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.25998 |
| 486 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.25998 |
| 487 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.25998 |
| 488 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4675.15093 |
| 489 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 3132.35112 |
| 490 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 491 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 4675.15093 |
| 492 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 493 | Fan:OnOff | SPLIT GS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.25998 |
| 494 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.25998 |
| 495 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4675.15093 |
| 496 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80043 |
| 497 | Coil:Heating:DX:SingleSpeed | SPLIT GS2 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.25998 |
| 498 | Coil:Heating:DX:SingleSpeed | SPLIT GS2 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 4675.15093 |
| 499 | Coil:Heating:Electric | SPLIT GS2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 4675.15093 |
| 500 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.74138 |
| 501 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 502 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.74138 |
| 503 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.74138 |
| 504 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.74138 |
| 505 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74138 |
| 506 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12669.46737 |
| 507 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8488.54314 |
| 508 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 509 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 12669.46737 |
| 510 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 511 | Fan:OnOff | SPLIT MSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.74138 |
| 512 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.74138 |
| 513 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12669.46737 |
| 514 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80013 |
| 515 | Coil:Heating:DX:SingleSpeed | SPLIT MSW HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.74138 |
| 516 | Coil:Heating:DX:SingleSpeed | SPLIT MSW HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 12669.46737 |
| 517 | Coil:Heating:Electric | SPLIT MSW_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 12669.46737 |
| 518 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.72439 |
| 519 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 520 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.72439 |
| 521 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.72439 |
| 522 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.72439 |
| 523 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72439 |
| 524 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12372.99909 |
| 525 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8289.90939 |
| 526 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 527 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 12372.99909 |
| 528 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 529 | Fan:OnOff | SPLIT MNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.72439 |
| 530 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.72439 |
| 531 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12372.99909 |
| 532 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80031 |
| 533 | Coil:Heating:DX:SingleSpeed | SPLIT MNW HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.72439 |
| 534 | Coil:Heating:DX:SingleSpeed | SPLIT MNW HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 12372.99909 |
| 535 | Coil:Heating:Electric | SPLIT MNW_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 12372.99909 |
| 536 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.67516 |
| 537 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 538 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.67516 |
| 539 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.67516 |
| 540 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.67516 |
| 541 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67516 |
| 542 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 11708.76865 |
| 543 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7844.87499 |
| 544 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 545 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 11708.76865 |
| 546 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 547 | Fan:OnOff | SPLIT MSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.67516 |
| 548 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.67516 |
| 549 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11708.76865 |
| 550 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80094 |
| 551 | Coil:Heating:DX:SingleSpeed | SPLIT MSE HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.67516 |
| 552 | Coil:Heating:DX:SingleSpeed | SPLIT MSE HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 11708.76865 |
| 553 | Coil:Heating:Electric | SPLIT MSE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11708.76865 |
| 554 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.65853 |
| 555 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 556 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.65853 |
| 557 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.65853 |
| 558 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.65853 |
| 559 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65853 |
| 560 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 11408.37924 |
| 561 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7643.61409 |
| 562 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 563 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 11408.37924 |
| 564 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 565 | Fan:OnOff | SPLIT MNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.65853 |
| 566 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65853 |
| 567 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11408.37924 |
| 568 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80031 |
| 569 | Coil:Heating:DX:SingleSpeed | SPLIT MNE HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65853 |
| 570 | Coil:Heating:DX:SingleSpeed | SPLIT MNE HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 11408.37924 |
| 571 | Coil:Heating:Electric | SPLIT MNE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11408.37924 |
| 572 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.58204 |
| 573 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 574 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.58204 |
| 575 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.58204 |
| 576 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.58204 |
| 577 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.58204 |
| 578 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10223.38714 |
| 579 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6849.66938 |
| 580 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 581 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 10223.38714 |
| 582 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 583 | Fan:OnOff | SPLIT MN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.58204 |
| 584 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58204 |
| 585 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10223.38714 |
| 586 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80049 |
| 587 | Coil:Heating:DX:SingleSpeed | SPLIT MN1 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58204 |
| 588 | Coil:Heating:DX:SingleSpeed | SPLIT MN1 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 10223.38714 |
| 589 | Coil:Heating:Electric | SPLIT MN1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 10223.38714 |
| 590 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.58029 |
| 591 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 592 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.58029 |
| 593 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.58029 |
| 594 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.58029 |
| 595 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.58029 |
| 596 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10196.26362 |
| 597 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6831.49663 |
| 598 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 599 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 10196.26362 |
| 600 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 601 | Fan:OnOff | SPLIT MN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.58029 |
| 602 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58029 |
| 603 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10196.26362 |
| 604 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80037 |
| 605 | Coil:Heating:DX:SingleSpeed | SPLIT MN2 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58029 |
| 606 | Coil:Heating:DX:SingleSpeed | SPLIT MN2 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 10196.26362 |
| 607 | Coil:Heating:Electric | SPLIT MN2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 10196.26362 |
| 608 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.60279 |
| 609 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 610 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.60279 |
| 611 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.60279 |
| 612 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.60279 |
| 613 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60279 |
| 614 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10606.25632 |
| 615 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7106.19174 |
| 616 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 617 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 10606.25632 |
| 618 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 619 | Fan:OnOff | SPLIT MS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.60279 |
| 620 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60279 |
| 621 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10606.25632 |
| 622 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80089 |
| 623 | Coil:Heating:DX:SingleSpeed | SPLIT MS1 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60279 |
| 624 | Coil:Heating:DX:SingleSpeed | SPLIT MS1 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 10606.25632 |
| 625 | Coil:Heating:Electric | SPLIT MS1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 10606.25632 |
| 626 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.60193 |
| 627 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 628 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.60193 |
| 629 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.60193 |
| 630 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.60193 |
| 631 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60193 |
| 632 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10593.27828 |
| 633 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7097.49645 |
| 634 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 635 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 10593.27828 |
| 636 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 637 | Fan:OnOff | SPLIT MS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.60193 |
| 638 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60193 |
| 639 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10593.27828 |
| 640 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80082 |
| 641 | Coil:Heating:DX:SingleSpeed | SPLIT MS2 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60193 |
| 642 | Coil:Heating:DX:SingleSpeed | SPLIT MS2 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 10593.27828 |
| 643 | Coil:Heating:Electric | SPLIT MS2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 10593.27828 |
| 644 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.41923 |
| 645 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 646 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.41923 |
| 647 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.41923 |
| 648 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.41923 |
| 649 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.41923 |
| 650 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7074.58227 |
| 651 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4739.97012 |
| 652 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 653 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 7074.58227 |
| 654 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 655 | Fan:OnOff | SPLIT TSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.41923 |
| 656 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.41923 |
| 657 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7074.58227 |
| 658 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80065 |
| 659 | Coil:Heating:DX:SingleSpeed | SPLIT TSW HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.41923 |
| 660 | Coil:Heating:DX:SingleSpeed | SPLIT TSW HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 7074.58227 |
| 661 | Coil:Heating:Electric | SPLIT TSW_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7074.58227 |
| 662 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.41449 |
| 663 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 664 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.41449 |
| 665 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.41449 |
| 666 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.41449 |
| 667 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.41449 |
| 668 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6987.64053 |
| 669 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4681.71915 |
| 670 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 671 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 6987.64053 |
| 672 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 673 | Fan:OnOff | SPLIT TNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.41449 |
| 674 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.41449 |
| 675 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6987.64053 |
| 676 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80001 |
| 677 | Coil:Heating:DX:SingleSpeed | SPLIT TNW HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.41449 |
| 678 | Coil:Heating:DX:SingleSpeed | SPLIT TNW HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6987.64053 |
| 679 | Coil:Heating:Electric | SPLIT TNW_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6987.64053 |
| 680 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37073 |
| 681 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 682 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37073 |
| 683 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37073 |
| 684 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37073 |
| 685 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37073 |
| 686 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6355.24577 |
| 687 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4258.01466 |
| 688 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 689 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 6355.24577 |
| 690 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 691 | Fan:OnOff | SPLIT TSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37073 |
| 692 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37073 |
| 693 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6355.24577 |
| 694 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80002 |
| 695 | Coil:Heating:DX:SingleSpeed | SPLIT TSE HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37073 |
| 696 | Coil:Heating:DX:SingleSpeed | SPLIT TSE HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6355.24577 |
| 697 | Coil:Heating:Electric | SPLIT TSE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6355.24577 |
| 698 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.36595 |
| 699 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 700 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.36595 |
| 701 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36595 |
| 702 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36595 |
| 703 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36595 |
| 704 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6265.49593 |
| 705 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4197.88228 |
| 706 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 707 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 6265.49593 |
| 708 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 709 | Fan:OnOff | SPLIT TNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36595 |
| 710 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36595 |
| 711 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6265.49593 |
| 712 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80047 |
| 713 | Coil:Heating:DX:SingleSpeed | SPLIT TNE HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36595 |
| 714 | Coil:Heating:DX:SingleSpeed | SPLIT TNE HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6265.49593 |
| 715 | Coil:Heating:Electric | SPLIT TNE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6265.49593 |
| 716 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33797 |
| 717 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 718 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33797 |
| 719 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33797 |
| 720 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33797 |
| 721 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33797 |
| 722 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5801.53901 |
| 723 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 3887.03114 |
| 724 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 725 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 5801.53901 |
| 726 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 727 | Fan:OnOff | SPLIT TN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33797 |
| 728 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33797 |
| 729 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5801.53901 |
| 730 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80054 |
| 731 | Coil:Heating:DX:SingleSpeed | SPLIT TN1 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33797 |
| 732 | Coil:Heating:DX:SingleSpeed | SPLIT TN1 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 5801.53901 |
| 733 | Coil:Heating:Electric | SPLIT TN1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5801.53901 |
| 734 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33659 |
| 735 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 736 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33659 |
| 737 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33659 |
| 738 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33659 |
| 739 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33659 |
| 740 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5781.04269 |
| 741 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 3873.29860 |
| 742 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 743 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 5781.04269 |
| 744 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 745 | Fan:OnOff | SPLIT TN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33659 |
| 746 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33659 |
| 747 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5781.04269 |
| 748 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80035 |
| 749 | Coil:Heating:DX:SingleSpeed | SPLIT TN2 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33659 |
| 750 | Coil:Heating:DX:SingleSpeed | SPLIT TN2 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 5781.04269 |
| 751 | Coil:Heating:Electric | SPLIT TN2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5781.04269 |
| 752 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34356 |
| 753 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 754 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34356 |
| 755 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34356 |
| 756 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34356 |
| 757 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34356 |
| 758 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5906.45444 |
| 759 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 3957.32448 |
| 760 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 761 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 5906.45444 |
| 762 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 763 | Fan:OnOff | SPLIT TS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34356 |
| 764 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34356 |
| 765 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5906.45444 |
| 766 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80001 |
| 767 | Coil:Heating:DX:SingleSpeed | SPLIT TS1 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34356 |
| 768 | Coil:Heating:DX:SingleSpeed | SPLIT TS1 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 5906.45444 |
| 769 | Coil:Heating:Electric | SPLIT TS1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5906.45444 |
| 770 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34219 |
| 771 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 772 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34219 |
| 773 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34219 |
| 774 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34219 |
| 775 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34219 |
| 776 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5886.10910 |
| 777 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 3943.69309 |
| 778 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 779 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 5886.10910 |
| 780 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 781 | Fan:OnOff | SPLIT TS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34219 |
| 782 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34219 |
| 783 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5886.10910 |
| 784 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80081 |
| 785 | Coil:Heating:DX:SingleSpeed | SPLIT TS2 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34219 |
| 786 | Coil:Heating:DX:SingleSpeed | SPLIT TS2 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 5886.10910 |
| 787 | Coil:Heating:Electric | SPLIT TS2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5886.10910 |
| 788 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.13460E-004 |
| 789 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.36152E-002 |
| 790 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.13460E-004 |
| 791 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 14.49330 |
| 792 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.13460E-004 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW HP COOLING COIL | 5169.3 | 3.10 | 10.58 | 11.00 | 10.41 | 10.36 |
| 2 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW HP COOLING COIL | 5007.9 | 3.10 | 10.58 | 11.00 | 10.40 | 10.36 |
| 3 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE HP COOLING COIL | 5823.2 | 3.09 | 10.56 | 10.98 | 10.38 | 10.33 |
| 4 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE HP COOLING COIL | 4661.5 | 3.11 | 10.61 | 11.03 | 10.43 | 10.40 |
| 5 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 HP COOLING COIL | 4263.2 | 3.12 | 10.63 | 11.06 | 10.46 | 10.44 |
| 6 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 HP COOLING COIL | 4257.9 | 3.12 | 10.63 | 11.06 | 10.46 | 10.44 |
| 7 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 HP COOLING COIL | 4437.7 | 3.12 | 10.64 | 11.07 | 10.47 | 10.45 |
| 8 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 HP COOLING COIL | 4471.2 | 3.12 | 10.64 | 11.06 | 10.47 | 10.45 |
| 9 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW HP COOLING COIL | 12088.2 | 3.09 | 10.54 | 10.95 | 10.36 | 10.30 |
| 10 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW HP COOLING COIL | 11805.1 | 3.09 | 10.53 | 10.95 | 10.36 | 10.30 |
| 11 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE HP COOLING COIL | 11179.3 | 3.10 | 10.57 | 10.99 | 10.39 | 10.34 |
| 12 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE HP COOLING COIL | 10892.0 | 3.10 | 10.56 | 10.98 | 10.39 | 10.34 |
| 13 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 HP COOLING COIL | 9766.9 | 3.10 | 10.59 | 11.01 | 10.42 | 10.38 |
| 14 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 HP COOLING COIL | 9741.1 | 3.10 | 10.59 | 11.01 | 10.42 | 10.38 |
| 15 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 HP COOLING COIL | 10133.5 | 3.10 | 10.59 | 11.02 | 10.42 | 10.38 |
| 16 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 HP COOLING COIL | 10121.2 | 3.11 | 10.60 | 11.02 | 10.42 | 10.38 |
| 17 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW HP COOLING COIL | 6746.0 | 3.08 | 10.51 | 10.93 | 10.33 | 10.26 |
| 18 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW HP COOLING COIL | 6662.7 | 3.08 | 10.51 | 10.92 | 10.33 | 10.26 |
| 19 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE HP COOLING COIL | 6064.6 | 3.09 | 10.54 | 10.96 | 10.37 | 10.31 |
| 20 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE HP COOLING COIL | 5978.6 | 3.09 | 10.54 | 10.96 | 10.37 | 10.30 |
| 21 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 HP COOLING COIL | 5536.5 | 3.09 | 10.54 | 10.96 | 10.37 | 10.31 |
| 22 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 HP COOLING COIL | 5517.1 | 3.09 | 10.55 | 10.96 | 10.37 | 10.31 |
| 23 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 HP COOLING COIL | 5637.1 | 3.09 | 10.55 | 10.97 | 10.37 | 10.32 |
| 24 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 HP COOLING COIL | 5617.8 | 3.09 | 10.55 | 10.97 | 10.38 | 10.32 |
| Component Type | Component Name | High Temperature Heating (net) Rating Capacity {W} | Low Temperature Heating (net) Rating Capacity {W} | HSPF {Btu/W-h} | Region Number | |
| 1 | Coil:Heating:DX:SingleSpeed | SPLIT GSW HEATING COIL | 5658.6 | 3145.7 | 8.07 | 4 |
| 2 | Coil:Heating:DX:SingleSpeed | SPLIT GNW HEATING COIL | 5482.7 | 3048.1 | 8.06 | 4 |
| 3 | Coil:Heating:DX:SingleSpeed | SPLIT OFFICE HEATING COIL | 6380.6 | 3548.4 | 8.12 | 4 |
| 4 | Coil:Heating:DX:SingleSpeed | SPLIT GNE HEATING COIL | 5097.0 | 2832.3 | 8.14 | 4 |
| 5 | Coil:Heating:DX:SingleSpeed | SPLIT GN1 HEATING COIL | 4656.1 | 2586.1 | 8.13 | 4 |
| 6 | Coil:Heating:DX:SingleSpeed | SPLIT GN2 HEATING COIL | 4650.3 | 2582.9 | 8.13 | 4 |
| 7 | Coil:Heating:DX:SingleSpeed | SPLIT GS1 HEATING COIL | 4844.5 | 2690.3 | 8.16 | 4 |
| 8 | Coil:Heating:DX:SingleSpeed | SPLIT GS2 HEATING COIL | 4881.9 | 2711.2 | 8.16 | 4 |
| 9 | Coil:Heating:DX:SingleSpeed | SPLIT MSW HEATING COIL | 13258.1 | 7375.8 | 8.04 | 4 |
| 10 | Coil:Heating:DX:SingleSpeed | SPLIT MNW HEATING COIL | 12948.2 | 7203.5 | 8.12 | 4 |
| 11 | Coil:Heating:DX:SingleSpeed | SPLIT MSE HEATING COIL | 12245.1 | 6808.8 | 8.10 | 4 |
| 12 | Coil:Heating:DX:SingleSpeed | SPLIT MNE HEATING COIL | 11931.5 | 6634.6 | 8.09 | 4 |
| 13 | Coil:Heating:DX:SingleSpeed | SPLIT MN1 HEATING COIL | 10685.9 | 5939.2 | 8.11 | 4 |
| 14 | Coil:Heating:DX:SingleSpeed | SPLIT MN2 HEATING COIL | 10657.4 | 5923.3 | 8.11 | 4 |
| 15 | Coil:Heating:DX:SingleSpeed | SPLIT MS1 HEATING COIL | 11085.3 | 6160.8 | 8.07 | 4 |
| 16 | Coil:Heating:DX:SingleSpeed | SPLIT MS2 HEATING COIL | 11071.6 | 6153.2 | 8.07 | 4 |
| 17 | Coil:Heating:DX:SingleSpeed | SPLIT TSW HEATING COIL | 7407.4 | 4122.7 | 8.07 | 4 |
| 18 | Coil:Heating:DX:SingleSpeed | SPLIT TNW HEATING COIL | 7316.6 | 4072.3 | 8.06 | 4 |
| 19 | Coil:Heating:DX:SingleSpeed | SPLIT TSE HEATING COIL | 6649.6 | 3698.9 | 8.04 | 4 |
| 20 | Coil:Heating:DX:SingleSpeed | SPLIT TNE HEATING COIL | 6556.1 | 3647.0 | 8.12 | 4 |
| 21 | Coil:Heating:DX:SingleSpeed | SPLIT TN1 HEATING COIL | 6069.9 | 3376.3 | 8.09 | 4 |
| 22 | Coil:Heating:DX:SingleSpeed | SPLIT TN2 HEATING COIL | 6048.3 | 3364.2 | 8.09 | 4 |
| 23 | Coil:Heating:DX:SingleSpeed | SPLIT TS1 HEATING COIL | 6179.3 | 3437.0 | 8.10 | 4 |
| 24 | Coil:Heating:DX:SingleSpeed | SPLIT TS2 HEATING COIL | 6157.9 | 3425.0 | 8.10 | 4 |
| Zone Name | # Surfaces | |
| 1 | G SW APARTMENT | 9 |
| 2 | G NW APARTMENT | 9 |
| 3 | OFFICE | 9 |
| 4 | G NE APARTMENT | 9 |
| 5 | G N1 APARTMENT | 8 |
| 6 | G N2 APARTMENT | 8 |
| 7 | G S1 APARTMENT | 8 |
| 8 | G S2 APARTMENT | 8 |
| 9 | M SW APARTMENT | 9 |
| 10 | M NW APARTMENT | 9 |
| 11 | M SE APARTMENT | 9 |
| 12 | M NE APARTMENT | 9 |
| 13 | M N1 APARTMENT | 8 |
| 14 | M N2 APARTMENT | 8 |
| 15 | M S1 APARTMENT | 8 |
| 16 | M S2 APARTMENT | 8 |
| 17 | T SW APARTMENT | 9 |
| 18 | T NW APARTMENT | 9 |
| 19 | T SE APARTMENT | 9 |
| 20 | T NE APARTMENT | 9 |
| 21 | T N1 APARTMENT | 8 |
| 22 | T N2 APARTMENT | 8 |
| 23 | T S1 APARTMENT | 8 |
| 24 | T S2 APARTMENT | 8 |
| 25 | T CORRIDOR | 13 |
| 26 | G CORRIDOR | 13 |
| 27 | M CORRIDOR | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | G SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.712 | 0.644 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | GWINDOW1 S SWA | Window | G SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | G WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.712 | 0.644 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | GWINDOW1 W SWA | Window | G WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | G GFLOOR SWA | Floor | CTF - ConductionTransferFunction | GGFLOORSWA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 8 | G CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 9 | G INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 10 | G NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.712 | 0.644 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | GWINDOW1 N NWA | Window | G NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 12 | G WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.712 | 0.644 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | GWINDOW1 W NWA | Window | G WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | G GFLOOR NWA | Floor | CTF - ConductionTransferFunction | GGFLOORNWA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | G CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | G INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | G SWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.804 | 0.717 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | GWINDOW1 S SEA | Window | G SWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 21 | G EWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.804 | 0.717 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | GWINDOW1 E SEA | Window | G EWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 23 | G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | iz-G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | G GFLOOR SEA | Floor | CTF - ConductionTransferFunction | GGFLOORSEA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 26 | G CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 27 | G INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 28 | G NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.712 | 0.644 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | GWINDOW1 N NEA | Window | G NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 30 | G EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.712 | 0.644 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 31 | GWINDOW1 E NEA | Window | G EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 32 | G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | iz-G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | G GFLOOR NEA | Floor | CTF - ConductionTransferFunction | GGFLOORNEA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 35 | G CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 36 | G INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 37 | G NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.712 | 0.644 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | GWINDOW1 N N1A | Window | G NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 39 | G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 40 | G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | iz-G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | G GFLOOR N1A | Floor | CTF - ConductionTransferFunction | GGFLOORN1A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | G CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | G INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | G NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.712 | 0.644 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | GWINDOW1 N N2A | Window | G NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 47 | G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 50 | G GFLOOR N2A | Floor | CTF - ConductionTransferFunction | GGFLOORN2A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 51 | G CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 52 | G INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | G SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.712 | 0.644 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | GWINDOW1 S S1A | Window | G SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 57 | iz-G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | G GFLOOR S1A | Floor | CTF - ConductionTransferFunction | GGFLOORS1A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 59 | G CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 60 | G INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 61 | G SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.712 | 0.644 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | GWINDOW1 S S2A | Window | G SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 63 | G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 65 | iz-G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | G GFLOOR S2A | Floor | CTF - ConductionTransferFunction | GGFLOORS2A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 67 | G CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 68 | G INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 69 | M WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.727 | 0.655 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 70 | MWINDOW1 W SWA | Window | M WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | M SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.727 | 0.655 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 72 | MWINDOW1 S SWA | Window | M SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 73 | M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 3.05 | 7.62 | 0.00 | iz-M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | M GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 76 | M CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 77 | M INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | M NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.727 | 0.655 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | MWINDOW1 N NWA | Window | M NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 80 | M WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.727 | 0.655 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | MWINDOW1 W NWA | Window | M WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 82 | M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | M GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 85 | M CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 86 | M INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 87 | M EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.727 | 0.655 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 88 | MWINDOW1 E SEA | Window | M EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 89 | M SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.727 | 0.655 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | MWINDOW1 S SEA | Window | M SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 91 | M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | iz-M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 93 | M GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | M CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | M INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 96 | M NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.727 | 0.655 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | MWINDOW1 N NEA | Window | M NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | M EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.727 | 0.655 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | MWINDOW1 E NEA | Window | M EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | M GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 103 | M CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 104 | M INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | M NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.727 | 0.655 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | MWINDOW1 N N1A | Window | M NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 109 | iz-M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | M GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | M CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | M INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | M NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.727 | 0.655 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | MWINDOW1 N N2A | Window | M NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 115 | M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | iz-M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | M GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 119 | M CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 120 | M INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 121 | M SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.727 | 0.655 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 122 | MWINDOW1 S S1A | Window | M SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 123 | M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | iz-M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 3.05 | 7.62 | 0.00 | M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | M GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 127 | M CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 128 | M INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 129 | M SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.727 | 0.655 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | MWINDOW1 S S2A | Window | M SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 131 | M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | iz-M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | M GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 135 | M CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 136 | M INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 137 | T WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.957 | 0.837 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | TWINDOW1 W SWA | Window | T WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 139 | T SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.957 | 0.837 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | TWINDOW1 S SWA | Window | T SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 141 | T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | T GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 144 | T ROOF SWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 145 | T INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 146 | T NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.957 | 0.837 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | TWINDOW1 N NWA | Window | T NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 148 | T WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.957 | 0.837 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | TWINDOW1 W NWA | Window | T WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 151 | T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 152 | T GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 153 | T ROOF NWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 154 | T INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 155 | T EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.957 | 0.837 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 156 | TWINDOW1 E SEA | Window | T EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 157 | T SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.957 | 0.837 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | TWINDOW1 S SEA | Window | T SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 159 | T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | iz-T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | T GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 162 | T ROOF SEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 163 | T INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 164 | T NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.957 | 0.837 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | TWINDOW1 N NEA | Window | T NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 166 | T EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.957 | 0.837 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | TWINDOW1 E NEA | Window | T EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 168 | T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | T GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 171 | T ROOF NEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 172 | T INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 173 | T NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.957 | 0.837 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | TWINDOW1 N N1A | Window | T NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | iz-T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | T GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 179 | T ROOF N1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 180 | T INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 181 | T NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.957 | 0.837 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | TWINDOW1 N N2A | Window | T NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 183 | T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | iz-T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | T GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 187 | T ROOF N2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 188 | T INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 189 | T SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.957 | 0.837 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | TWINDOW1 S S1A | Window | T SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 191 | T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | iz-T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | T GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 195 | T ROOF S1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 196 | T INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 197 | T SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.957 | 0.837 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | TWINDOW1 S S2A | Window | T SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 199 | T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | iz-T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | T GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 203 | T ROOF S2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 204 | T INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 205 | T WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.055 | 0.911 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 206 | T EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.055 | 0.911 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | TWINDOW14 | Window | T EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 208 | iz-T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | iz-T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | iz-T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | iz-T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | iz-T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | iz-T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | iz-T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | iz-T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | T FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | T FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 217 | T ROOF C | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 218 | G WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.804 | 0.717 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | G EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.804 | 0.717 | 1.79 | 5.11 | 1.79 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | ENTRANCE DOOR | Window | G EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 3.32 | 3.32 | 3.32 | 90.00 | 90.00 | 1.57 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | iz-G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 222 | iz-G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 223 | iz-G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | iz-G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | iz-G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | iz-G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | iz-G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 228 | iz-G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 229 | G FLOOR C | Floor | CTF - ConductionTransferFunction | GFLOORC_FFACTOR | 4.061E-002 | 4.021E-002 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 230 | G CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | G CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 231 | M WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.818 | 0.729 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | M EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.818 | 0.729 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | MWINDOW14 | Window | M EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.245 | N/A | 2.557 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 234 | iz-M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | iz-M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | iz-M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | iz-M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | iz-M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | iz-M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 240 | iz-M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 241 | iz-M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 242 | M FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | M FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | M CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | M CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEAR'S DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | G SW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.2891788487E-002 | 1.4406264788E-002 | Pass | Pass | 0.1051098651 | 0.4610599039 | Pass | Pass |
| 2 | G NW APARTMENT | RunPeriod: RUNPERIOD 1 | 8.9692579580E-003 | 1.3782178748E-002 | Pass | Pass | 0.1932653650 | 0.7282876712 | Pass | Pass |
| 3 | OFFICE | RunPeriod: RUNPERIOD 1 | 2.5674193197E-002 | 2.7841927778E-002 | Pass | Pass | 0.1621992514 | 0.3661179125 | Pass | Pass |
| 4 | G NE APARTMENT | RunPeriod: RUNPERIOD 1 | 9.2659292860E-003 | 1.4050119886E-002 | Pass | Pass | 0.2849797903 | 1.4912350801 | Pass | Pass |
| 5 | G N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.3722375644E-002 | 1.2855064657E-002 | Pass | Pass | 1.5824478848E-002 | 2.8144296781E-002 | Pass | Pass |
| 6 | G N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.3736602203E-002 | 1.2856409865E-002 | Pass | Pass | 1.5812871153E-002 | 2.8128157307E-002 | Pass | Pass |
| 7 | G S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.4454519231E-002 | 1.3388015748E-002 | Pass | Pass | 1.5281719077E-002 | 2.7391461706E-002 | Pass | Pass |
| 8 | G S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.4275433929E-002 | 1.3162391449E-002 | Pass | Pass | 1.5730058131E-002 | 2.8242120239E-002 | Pass | Pass |
| 9 | M SW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6793513900E-002 | 1.6138137638E-002 | Pass | Pass | 1.5090976717E-002 | 2.7282894576E-002 | Pass | Pass |
| 10 | M NW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6030874053E-002 | 1.5507752125E-002 | Pass | Pass | 1.5728281533E-002 | 2.8230183503E-002 | Pass | Pass |
| 11 | M SE APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6926856201E-002 | 1.6349266136E-002 | Pass | Pass | 1.4979789379E-002 | 2.7135619778E-002 | Pass | Pass |
| 12 | M NE APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6128806172E-002 | 1.5631423074E-002 | Pass | Pass | 1.5608346199E-002 | 2.8070964915E-002 | Pass | Pass |
| 13 | M N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.2931430495E-002 | 1.3301951998E-002 | Pass | Pass | 1.4159633551E-002 | 2.5146983726E-002 | Pass | Pass |
| 14 | M N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.2951554830E-002 | 1.3327119069E-002 | Pass | Pass | 1.4143397340E-002 | 2.5119369532E-002 | Pass | Pass |
| 15 | M S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.3915791583E-002 | 1.3820624048E-002 | Pass | Pass | 1.3610207722E-002 | 2.4326452665E-002 | Pass | Pass |
| 16 | M S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.3934124891E-002 | 1.3845867126E-002 | Pass | Pass | 1.3595502509E-002 | 2.4300976845E-002 | Pass | Pass |
| 17 | T SW APARTMENT | RunPeriod: RUNPERIOD 1 | 6.7482882689E-003 | 1.9800690259E-002 | Pass | Pass | 0.2939137270 | 1.2026757025 | Pass | Pass |
| 18 | T NW APARTMENT | RunPeriod: RUNPERIOD 1 | 4.1666401077E-003 | 1.2868337355E-002 | Pass | Pass | 7.3907429027E-002 | 0.1460379151 | Pass | Pass |
| 19 | T SE APARTMENT | RunPeriod: RUNPERIOD 1 | 7.4924438610E-003 | 2.1705848089E-002 | Pass | Pass | 0.2682024983 | 1.0805816174 | Pass | Pass |
| 20 | T NE APARTMENT | RunPeriod: RUNPERIOD 1 | 4.4339976069E-003 | 1.2934269200E-002 | Pass | Pass | 0.2114232902 | 1.2249970034 | Pass | Pass |
| 21 | T N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 8.0632563189E-003 | 1.7423903513E-002 | Pass | Pass | 0.1472665940 | 0.4209004033 | Pass | Pass |
| 22 | T N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 8.0983738569E-003 | 1.7478052662E-002 | Pass | Pass | 0.1557951132 | 0.5427520558 | Pass | Pass |
| 23 | T S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.2535604358E-002 | 1.9637569154E-002 | Pass | Pass | 0.5851203186 | 5.4670654394 | Pass | Pass |
| 24 | T S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.2582063489E-002 | 1.9678148258E-002 | Pass | Pass | 0.3985054318 | 3.2106785083 | Pass | Pass |
| 25 | T CORRIDOR | RunPeriod: RUNPERIOD 1 | 1.2021852650E-002 | 7.2761057135E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 26 | G CORRIDOR | RunPeriod: RUNPERIOD 1 | 0.1394014311 | 0.4202884905 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 27 | M CORRIDOR | RunPeriod: RUNPERIOD 1 | 4.0648507727E-003 | 3.2184555694E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 1452.13 | 62.87 | 0.00 | 8.81 | 713.07 | 2236.88 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
| ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 0.00 | 0 | |||
| Feb | 0.00 | 0 | |||
| Mar | 0.00 | 0 | |||
| Apr | 0.00 | 0 | |||
| May | 0.00 | 0 | |||
| Jun | 0.00 | 0 | |||
| Jul | 0.00 | 0 | |||
| Aug | 0.00 | 0 | |||
| Sep | 90.00 | 25 | |||
| Oct | 0.00 | 0 | |||
| Nov | 0.00 | 0 | |||
| Dec | 0.00 | 0 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G SWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.644 | 0.712 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G WWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.644 | 0.712 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR SWA | GGFLOORSWA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.644 | 0.712 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G WWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.644 | 0.712 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR NWA | GGFLOORNWA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.717 | 0.804 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G EWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.717 | 0.804 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR SEA | GGFLOORSEA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.644 | 0.712 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G EWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.644 | 0.712 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR NEA | GGFLOORNEA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N1A | RES_EXT_WALL_GRD | 0.30 | 0.644 | 0.712 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N1A | GGFLOORN1A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N2A | RES_EXT_WALL_GRD | 0.30 | 0.644 | 0.712 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N2A | GGFLOORN2A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S1A | RES_EXT_WALL_GRD | 0.30 | 0.644 | 0.712 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S1A | GGFLOORS1A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S2A | RES_EXT_WALL_GRD | 0.30 | 0.644 | 0.712 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S2A | GGFLOORS2A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| M WWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.655 | 0.727 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M SWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.655 | 0.727 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.655 | 0.727 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M WWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.655 | 0.727 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M EWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.655 | 0.727 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M SWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.655 | 0.727 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.655 | 0.727 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M EWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.655 | 0.727 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M NWALL N1A | RES_EXT_WALL_MID | 0.30 | 0.655 | 0.727 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M NWALL N2A | RES_EXT_WALL_MID | 0.30 | 0.655 | 0.727 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M SWALL S1A | RES_EXT_WALL_MID | 0.30 | 0.655 | 0.727 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M SWALL S2A | RES_EXT_WALL_MID | 0.30 | 0.655 | 0.727 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| T WWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.837 | 0.957 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T SWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.837 | 0.957 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SWA | RES_ROOF | 0.55 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.837 | 0.957 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T WWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.837 | 0.957 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T ROOF NWA | RES_ROOF | 0.55 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T EWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.837 | 0.957 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T SWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.837 | 0.957 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SEA | RES_ROOF | 0.55 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.837 | 0.957 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T EWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.837 | 0.957 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T ROOF NEA | RES_ROOF | 0.55 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N1A | RES_EXT_WALL_TOP | 0.30 | 0.837 | 0.957 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N1A | RES_ROOF | 0.55 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N2A | RES_EXT_WALL_TOP | 0.30 | 0.837 | 0.957 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N2A | RES_ROOF | 0.55 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S1A | RES_EXT_WALL_TOP | 0.30 | 0.837 | 0.957 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S1A | RES_ROOF | 0.55 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S2A | RES_EXT_WALL_TOP | 0.30 | 0.837 | 0.957 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S2A | RES_ROOF | 0.55 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T WWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.911 | 1.055 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| T EWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.911 | 1.055 | 5.11 | 3.99 | 90.00 | 90.00 | E |
| T ROOF C | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 77.66 | 77.66 | 180.00 | 0.00 | |
| G WWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.717 | 0.804 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| G EWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.717 | 0.804 | 5.11 | 1.79 | 90.00 | 90.00 | E |
| G FLOOR C | GFLOORC_FFACTOR | 1.00 | 0.040 | 0.041 | 77.66 | 77.66 | 90.00 | 180.00 | |
| M WWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.729 | 0.818 | 10.22 | 10.22 | 270.00 | 90.00 | W |
| M EWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.729 | 0.818 | 10.22 | 7.99 | 90.00 | 90.00 | E |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| iz-T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 77.66 | 77.66 | 90.00 | 180.00 | |
| iz-G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 77.66 | 77.66 | 180.00 | 0.00 | |
| iz-M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 155.32 | 155.32 | 90.00 | 180.00 | |
| M CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 155.32 | 155.32 | 180.00 | 0.00 | |
| G INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| GWINDOW1 S SWA | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | G SWALL SWA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 W SWA | RESWINDOW_U_0.45_SHGC_0.245 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.557 | 0.246 | 0.270 | No | G WWALL SWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 N NWA | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | G NWALL NWA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 W NWA | RESWINDOW_U_0.45_SHGC_0.245 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.557 | 0.246 | 0.270 | No | G WWALL NWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 S SEA | NONRESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | G SWALL SEA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 E SEA | NONRESWINDOW_U_0.45_SHGC_0.245 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.557 | 0.246 | 0.270 | No | G EWALL SEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N NEA | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | G NWALL NEA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 E NEA | RESWINDOW_U_0.45_SHGC_0.245 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.557 | 0.246 | 0.270 | No | G EWALL NEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N N1A | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | G NWALL N1A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 N N2A | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | G NWALL N2A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 S S1A | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | G SWALL S1A | 180.00 | 90.00 | S | |||||||
| GWINDOW1 S S2A | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | G SWALL S2A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 W SWA | RESWINDOW_U_0.45_SHGC_0.245 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.557 | 0.246 | 0.270 | No | M WWALL SWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 S SWA | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.557 | 0.246 | 0.270 | No | M SWALL SWA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NWA | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.557 | 0.246 | 0.270 | No | M NWALL NWA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 W NWA | RESWINDOW_U_0.45_SHGC_0.245 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.557 | 0.246 | 0.270 | No | M WWALL NWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 E SEA | RESWINDOW_U_0.45_SHGC_0.245 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.557 | 0.246 | 0.270 | No | M EWALL SEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 S SEA | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.557 | 0.246 | 0.270 | No | M SWALL SEA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NEA | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.557 | 0.246 | 0.270 | No | M NWALL NEA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 E NEA | RESWINDOW_U_0.45_SHGC_0.245 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.557 | 0.246 | 0.270 | No | M EWALL NEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 N N1A | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.557 | 0.246 | 0.270 | No | M NWALL N1A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 N N2A | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.557 | 0.246 | 0.270 | No | M NWALL N2A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 S S1A | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.557 | 0.246 | 0.270 | No | M SWALL S1A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 S S2A | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.557 | 0.246 | 0.270 | No | M SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 W SWA | RESWINDOW_U_0.45_SHGC_0.245 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.557 | 0.246 | 0.270 | No | T WWALL SWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 S SWA | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | T SWALL SWA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NWA | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | T NWALL NWA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 W NWA | RESWINDOW_U_0.45_SHGC_0.245 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.557 | 0.246 | 0.270 | No | T WWALL NWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 E SEA | RESWINDOW_U_0.45_SHGC_0.245 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.557 | 0.246 | 0.270 | No | T EWALL SEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 S SEA | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | T SWALL SEA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NEA | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | T NWALL NEA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 E NEA | RESWINDOW_U_0.45_SHGC_0.245 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.557 | 0.246 | 0.270 | No | T EWALL NEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 N N1A | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | T NWALL N1A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 N N2A | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | T NWALL N2A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 S S1A | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | T SWALL S1A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 S S2A | RESWINDOW_U_0.45_SHGC_0.245 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.557 | 0.246 | 0.270 | No | T SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW14 | NONRESWINDOW_U_0.45_SHGC_0.245 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.557 | 0.246 | 0.270 | No | T EWALL C | 90.00 | 90.00 | E | |||||||
| ENTRANCE DOOR | NONRESWINDOW_U_0.45_SHGC_0.245 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.557 | 0.246 | 0.270 | No | G EWALL C | 90.00 | 90.00 | E | |||||||
| MWINDOW14 | NONRESWINDOW_U_0.45_SHGC_0.245 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.557 | 0.246 | 0.270 | No | M EWALL C | 90.00 | 90.00 | E | |||||||
| Total or Average | 306.92 | 2.557 | 0.246 | 0.270 | |||||||||||||||||
| North Total or Average | 112.97 | 2.557 | 0.246 | 0.270 | |||||||||||||||||
| Non-North Total or Average | 193.95 | 2.557 | 0.246 | 0.270 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| LIGHTING_HARDWIRED_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_OFFICE | OFFICE | OFFICE | GENERAL | 7.4895 | 88.25 | 660.94 | LightsWired | LTG_SCH_OFFICE | 46.69 | 168.00 | 45.77 | 0.0000 | Y | 5.68 |
| LIGHTING_HARDWIRED_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_GC | G CORRIDOR | G CORRIDOR | GENERAL | 5.2871 | 77.66 | 410.59 | LightsWired | LTG_SCH_CORRIDOR | 126.00 | 168.00 | 126.00 | 0.0000 | N | 9.71 |
| LIGHTING_HARDWIRED_MC | M CORRIDOR | M CORRIDOR | GENERAL | 5.2871 | 155.32 | 821.19 | LightsWired | LTG_SCH_CORRIDOR | 126.00 | 168.00 | 126.00 | 0.0000 | N | 19.42 |
| LIGHTING_HARDWIRED_TC | T CORRIDOR | T CORRIDOR | GENERAL | 5.2871 | 77.66 | 410.59 | LightsWired | LTG_SCH_CORRIDOR | 126.00 | 168.00 | 126.00 | 0.0000 | N | 9.71 |
| LIGHTING_PLUGIN_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| Interior Lighting Total | 2.9507 | 5870.34 | 17321.34 | 55.94 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| FACADE LIGHTING | 2101.03 | AstronomicalClock | - | 83.77 | 83.77 | 33.04 | |
| Exterior Lighting Total | 2101.03 | 33.04 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| SPLIT GSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5412.40 | 4332.56 | 1079.84 | 0.80 | 3.82 | |||
| SPLIT GNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5243.78 | 4195.33 | 1048.46 | 0.80 | 3.82 | |||
| SPLIT OFFICE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6100.13 | 4882.18 | 1217.95 | 0.80 | 3.82 | |||
| SPLIT GNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4877.85 | 3902.59 | 975.26 | 0.80 | 3.82 | |||
| SPLIT GN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4458.35 | 3569.37 | 888.98 | 0.80 | 3.82 | |||
| SPLIT GN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4452.77 | 3564.57 | 888.20 | 0.80 | 3.82 | |||
| SPLIT GS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4639.74 | 3715.50 | 924.24 | 0.80 | 3.82 | |||
| SPLIT GS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4675.15 | 3742.15 | 933.00 | 0.80 | 3.82 | |||
| SPLIT MSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12669.47 | 10137.26 | 2532.20 | 0.80 | 3.82 | |||
| SPLIT MNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12373.00 | 9902.27 | 2470.73 | 0.80 | 3.82 | |||
| SPLIT MSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11708.77 | 9378.00 | 2330.77 | 0.80 | 3.82 | |||
| SPLIT MNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11408.38 | 9130.18 | 2278.20 | 0.80 | 3.82 | |||
| SPLIT MN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10223.39 | 8183.70 | 2039.68 | 0.80 | 3.82 | |||
| SPLIT MN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10196.26 | 8160.78 | 2035.49 | 0.80 | 3.82 | |||
| SPLIT MS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10606.26 | 8494.43 | 2111.83 | 0.80 | 3.82 | |||
| SPLIT MS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10593.28 | 8483.27 | 2110.01 | 0.80 | 3.82 | |||
| SPLIT TSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7074.58 | 5664.26 | 1410.33 | 0.80 | 3.82 | |||
| SPLIT TNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6987.64 | 5590.16 | 1397.48 | 0.80 | 3.82 | |||
| SPLIT TSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6355.25 | 5084.33 | 1270.91 | 0.80 | 3.82 | |||
| SPLIT TNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6265.50 | 5015.31 | 1250.18 | 0.80 | 3.82 | |||
| SPLIT TN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5801.54 | 4644.38 | 1157.16 | 0.80 | 3.82 | |||
| SPLIT TN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5781.04 | 4626.85 | 1154.20 | 0.80 | 3.82 | |||
| SPLIT TS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5906.45 | 4725.20 | 1181.26 | 0.80 | 3.82 | |||
| SPLIT TS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5886.11 | 4713.63 | 1172.48 | 0.80 | 3.82 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| SPLIT GSW HP COOLING COIL | 5169.3 | 3.10 | 10.58 | 11.00 | 10.41 | 10.36 | |
| SPLIT GNW HP COOLING COIL | 5007.9 | 3.10 | 10.58 | 11.00 | 10.40 | 10.36 | |
| SPLIT OFFICE HP COOLING COIL | 5823.2 | 3.09 | 10.56 | 10.98 | 10.38 | 10.33 | |
| SPLIT GNE HP COOLING COIL | 4661.5 | 3.11 | 10.61 | 11.03 | 10.43 | 10.40 | |
| SPLIT GN1 HP COOLING COIL | 4263.2 | 3.12 | 10.63 | 11.06 | 10.46 | 10.44 | |
| SPLIT GN2 HP COOLING COIL | 4257.9 | 3.12 | 10.63 | 11.06 | 10.46 | 10.44 | |
| SPLIT GS1 HP COOLING COIL | 4437.7 | 3.12 | 10.64 | 11.07 | 10.47 | 10.45 | |
| SPLIT GS2 HP COOLING COIL | 4471.2 | 3.12 | 10.64 | 11.06 | 10.47 | 10.45 | |
| SPLIT MSW HP COOLING COIL | 12088.2 | 3.09 | 10.54 | 10.95 | 10.36 | 10.30 | |
| SPLIT MNW HP COOLING COIL | 11805.1 | 3.09 | 10.53 | 10.95 | 10.36 | 10.30 | |
| SPLIT MSE HP COOLING COIL | 11179.3 | 3.10 | 10.57 | 10.99 | 10.39 | 10.34 | |
| SPLIT MNE HP COOLING COIL | 10892.0 | 3.10 | 10.56 | 10.98 | 10.39 | 10.34 | |
| SPLIT MN1 HP COOLING COIL | 9766.9 | 3.10 | 10.59 | 11.01 | 10.42 | 10.38 | |
| SPLIT MN2 HP COOLING COIL | 9741.1 | 3.10 | 10.59 | 11.01 | 10.42 | 10.38 | |
| SPLIT MS1 HP COOLING COIL | 10133.5 | 3.10 | 10.59 | 11.02 | 10.42 | 10.38 | |
| SPLIT MS2 HP COOLING COIL | 10121.2 | 3.11 | 10.60 | 11.02 | 10.42 | 10.38 | |
| SPLIT TSW HP COOLING COIL | 6746.0 | 3.08 | 10.51 | 10.93 | 10.33 | 10.26 | |
| SPLIT TNW HP COOLING COIL | 6662.7 | 3.08 | 10.51 | 10.92 | 10.33 | 10.26 | |
| SPLIT TSE HP COOLING COIL | 6064.6 | 3.09 | 10.54 | 10.96 | 10.37 | 10.31 | |
| SPLIT TNE HP COOLING COIL | 5978.6 | 3.09 | 10.54 | 10.96 | 10.37 | 10.30 | |
| SPLIT TN1 HP COOLING COIL | 5536.5 | 3.09 | 10.54 | 10.96 | 10.37 | 10.31 | |
| SPLIT TN2 HP COOLING COIL | 5517.1 | 3.09 | 10.55 | 10.96 | 10.37 | 10.31 | |
| SPLIT TS1 HP COOLING COIL | 5637.1 | 3.09 | 10.55 | 10.97 | 10.37 | 10.32 | |
| SPLIT TS2 HP COOLING COIL | 5617.8 | 3.09 | 10.55 | 10.97 | 10.38 | 10.32 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| SPLIT GSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT OFFICE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| SPLIT GSW HEATING COIL | Coil:Heating:DX:SingleSpeed | 5658.6 | 3145.7 | 8.07 | 4 |
| SPLIT GNW HEATING COIL | Coil:Heating:DX:SingleSpeed | 5482.7 | 3048.1 | 8.06 | 4 |
| SPLIT OFFICE HEATING COIL | Coil:Heating:DX:SingleSpeed | 6380.6 | 3548.4 | 8.12 | 4 |
| SPLIT GNE HEATING COIL | Coil:Heating:DX:SingleSpeed | 5097.0 | 2832.3 | 8.14 | 4 |
| SPLIT GN1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 4656.1 | 2586.1 | 8.13 | 4 |
| SPLIT GN2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 4650.3 | 2582.9 | 8.13 | 4 |
| SPLIT GS1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 4844.5 | 2690.3 | 8.16 | 4 |
| SPLIT GS2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 4881.9 | 2711.2 | 8.16 | 4 |
| SPLIT MSW HEATING COIL | Coil:Heating:DX:SingleSpeed | 13258.1 | 7375.8 | 8.04 | 4 |
| SPLIT MNW HEATING COIL | Coil:Heating:DX:SingleSpeed | 12948.2 | 7203.5 | 8.12 | 4 |
| SPLIT MSE HEATING COIL | Coil:Heating:DX:SingleSpeed | 12245.1 | 6808.8 | 8.10 | 4 |
| SPLIT MNE HEATING COIL | Coil:Heating:DX:SingleSpeed | 11931.5 | 6634.6 | 8.09 | 4 |
| SPLIT MN1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 10685.9 | 5939.2 | 8.11 | 4 |
| SPLIT MN2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 10657.4 | 5923.3 | 8.11 | 4 |
| SPLIT MS1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 11085.3 | 6160.8 | 8.07 | 4 |
| SPLIT MS2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 11071.6 | 6153.2 | 8.07 | 4 |
| SPLIT TSW HEATING COIL | Coil:Heating:DX:SingleSpeed | 7407.4 | 4122.7 | 8.07 | 4 |
| SPLIT TNW HEATING COIL | Coil:Heating:DX:SingleSpeed | 7316.6 | 4072.3 | 8.06 | 4 |
| SPLIT TSE HEATING COIL | Coil:Heating:DX:SingleSpeed | 6649.6 | 3698.9 | 8.04 | 4 |
| SPLIT TNE HEATING COIL | Coil:Heating:DX:SingleSpeed | 6556.1 | 3647.0 | 8.12 | 4 |
| SPLIT TN1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6069.9 | 3376.3 | 8.09 | 4 |
| SPLIT TN2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6048.3 | 3364.2 | 8.09 | 4 |
| SPLIT TS1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6179.3 | 3437.0 | 8.10 | 4 |
| SPLIT TS2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6157.9 | 3425.0 | 8.10 | 4 |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| SPLIT GSW HEATING COIL | Coil:Heating:DX:SingleSpeed | 5412.40 | 3.81 | |
| SPLIT GSW_SUPPHEATCOIL | Coil:Heating:Electric | 5412.40 | 1.00 | |
| SPLIT GNW HEATING COIL | Coil:Heating:DX:SingleSpeed | 5243.78 | 3.81 | |
| SPLIT GNW_SUPPHEATCOIL | Coil:Heating:Electric | 5243.78 | 1.00 | |
| SPLIT OFFICE HEATING COIL | Coil:Heating:DX:SingleSpeed | 6100.13 | 3.81 | |
| SPLIT OFFICE_SUPPHEATCOIL | Coil:Heating:Electric | 6100.13 | 1.00 | |
| SPLIT GNE HEATING COIL | Coil:Heating:DX:SingleSpeed | 4877.85 | 3.81 | |
| SPLIT GNE_SUPPHEATCOIL | Coil:Heating:Electric | 4877.85 | 1.00 | |
| SPLIT GN1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 4458.35 | 3.81 | |
| SPLIT GN1_SUPPHEATCOIL | Coil:Heating:Electric | 4458.35 | 1.00 | |
| SPLIT GN2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 4452.77 | 3.81 | |
| SPLIT GN2_SUPPHEATCOIL | Coil:Heating:Electric | 4452.77 | 1.00 | |
| SPLIT GS1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 4639.74 | 3.81 | |
| SPLIT GS1_SUPPHEATCOIL | Coil:Heating:Electric | 4639.74 | 1.00 | |
| SPLIT GS2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 4675.15 | 3.81 | |
| SPLIT GS2_SUPPHEATCOIL | Coil:Heating:Electric | 4675.15 | 1.00 | |
| SPLIT MSW HEATING COIL | Coil:Heating:DX:SingleSpeed | 12669.47 | 3.81 | |
| SPLIT MSW_SUPPHEATCOIL | Coil:Heating:Electric | 12669.47 | 1.00 | |
| SPLIT MNW HEATING COIL | Coil:Heating:DX:SingleSpeed | 12373.00 | 3.81 | |
| SPLIT MNW_SUPPHEATCOIL | Coil:Heating:Electric | 12373.00 | 1.00 | |
| SPLIT MSE HEATING COIL | Coil:Heating:DX:SingleSpeed | 11708.77 | 3.81 | |
| SPLIT MSE_SUPPHEATCOIL | Coil:Heating:Electric | 11708.77 | 1.00 | |
| SPLIT MNE HEATING COIL | Coil:Heating:DX:SingleSpeed | 11408.38 | 3.81 | |
| SPLIT MNE_SUPPHEATCOIL | Coil:Heating:Electric | 11408.38 | 1.00 | |
| SPLIT MN1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 10223.39 | 3.81 | |
| SPLIT MN1_SUPPHEATCOIL | Coil:Heating:Electric | 10223.39 | 1.00 | |
| SPLIT MN2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 10196.26 | 3.81 | |
| SPLIT MN2_SUPPHEATCOIL | Coil:Heating:Electric | 10196.26 | 1.00 | |
| SPLIT MS1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 10606.26 | 3.81 | |
| SPLIT MS1_SUPPHEATCOIL | Coil:Heating:Electric | 10606.26 | 1.00 | |
| SPLIT MS2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 10593.28 | 3.81 | |
| SPLIT MS2_SUPPHEATCOIL | Coil:Heating:Electric | 10593.28 | 1.00 | |
| SPLIT TSW HEATING COIL | Coil:Heating:DX:SingleSpeed | 7074.58 | 3.81 | |
| SPLIT TSW_SUPPHEATCOIL | Coil:Heating:Electric | 7074.58 | 1.00 | |
| SPLIT TNW HEATING COIL | Coil:Heating:DX:SingleSpeed | 6987.64 | 3.81 | |
| SPLIT TNW_SUPPHEATCOIL | Coil:Heating:Electric | 6987.64 | 1.00 | |
| SPLIT TSE HEATING COIL | Coil:Heating:DX:SingleSpeed | 6355.25 | 3.81 | |
| SPLIT TSE_SUPPHEATCOIL | Coil:Heating:Electric | 6355.25 | 1.00 | |
| SPLIT TNE HEATING COIL | Coil:Heating:DX:SingleSpeed | 6265.50 | 3.81 | |
| SPLIT TNE_SUPPHEATCOIL | Coil:Heating:Electric | 6265.50 | 1.00 | |
| SPLIT TN1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 5801.54 | 3.81 | |
| SPLIT TN1_SUPPHEATCOIL | Coil:Heating:Electric | 5801.54 | 1.00 | |
| SPLIT TN2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 5781.04 | 3.81 | |
| SPLIT TN2_SUPPHEATCOIL | Coil:Heating:Electric | 5781.04 | 1.00 | |
| SPLIT TS1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 5906.45 | 3.81 | |
| SPLIT TS1_SUPPHEATCOIL | Coil:Heating:Electric | 5906.45 | 1.00 | |
| SPLIT TS2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 5886.11 | 3.81 | |
| SPLIT TS2_SUPPHEATCOIL | Coil:Heating:Electric | 5886.11 | 1.00 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| G SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| M SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| T SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 347.14 | 1120.11 | 1.00 | 1.87 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 336.88 | 1120.11 | 1.00 | 1.89 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 395.58 | 1120.11 | 1.00 | 1.79 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 |
| SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 308.88 | 1120.11 | 1.00 | 1.96 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 278.66 | 1120.11 | 1.00 | 2.04 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 278.25 | 1120.11 | 1.00 | 2.04 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 288.46 | 1120.11 | 1.00 | 2.01 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 291.20 | 1120.11 | 1.00 | 2.00 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.74 | 830.42 | 1120.11 | 1.00 | 1.46 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.72 | 811.40 | 1120.11 | 1.00 | 1.46 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.68 | 756.26 | 1120.11 | 1.00 | 1.49 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.66 | 737.63 | 1120.11 | 1.00 | 1.50 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.58 | 651.95 | 1120.11 | 1.00 | 1.54 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.58 | 649.99 | 1120.11 | 1.00 | 1.54 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.60 | 675.19 | 1120.11 | 1.00 | 1.53 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.60 | 674.22 | 1120.11 | 1.00 | 1.53 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 469.58 | 1120.11 | 1.00 | 1.69 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.41 | 464.27 | 1120.11 | 1.00 | 1.70 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 415.25 | 1120.11 | 1.00 | 1.76 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 409.90 | 1120.11 | 1.00 | 1.77 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 378.56 | 1120.11 | 1.00 | 1.82 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 377.02 | 1120.11 | 1.00 | 1.82 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 384.83 | 1120.11 | 1.00 | 1.81 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 383.28 | 1120.11 | 1.00 | 1.81 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000113 | 14.49 | 127739.32 | 0.30 | General |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.95 | 53912.00 | 0.80 | 11.45 | 0.46 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 3535.84 | 4243.01 | 48.08 | 0.258 | 0.310 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00825 | 30.70 | 0.01447 | 0.026 | 0.00 |
| G NW APARTMENT | 3433.58 | 4120.30 | 46.69 | 0.251 | 0.301 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00822 | 30.70 | 0.01447 | 0.026 | 0.00 |
| OFFICE | 3867.09 | 4640.51 | 52.58 | 0.294 | 0.353 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 23.90 | 23.90 | 0.00808 | 29.71 | 0.01446 | 0.038 | 0.00 |
| G NE APARTMENT | 3156.54 | 3787.85 | 42.92 | 0.230 | 0.276 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00825 | 30.70 | 0.01447 | 0.026 | 0.00 |
| G N1 APARTMENT | 2856.13 | 3427.35 | 38.84 | 0.207 | 0.249 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00826 | 30.70 | 0.01447 | 0.026 | 0.00 |
| G N2 APARTMENT | 2852.07 | 3422.48 | 38.78 | 0.207 | 0.248 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00826 | 30.70 | 0.01447 | 0.026 | 0.00 |
| G S1 APARTMENT | 2953.28 | 3543.94 | 40.16 | 0.215 | 0.258 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00833 | 30.70 | 0.01447 | 0.026 | 0.00 |
| G S2 APARTMENT | 2980.26 | 3576.32 | 40.53 | 0.217 | 0.260 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00833 | 30.70 | 0.01447 | 0.026 | 0.00 |
| M SW APARTMENT | 8422.77 | 10107.32 | 114.53 | 0.618 | 0.741 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00822 | 30.70 | 0.01447 | 0.052 | 0.00 |
| M NW APARTMENT | 8234.43 | 9881.31 | 111.97 | 0.604 | 0.724 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00820 | 30.70 | 0.01447 | 0.052 | 0.00 |
| M SE APARTMENT | 7689.57 | 9227.49 | 104.56 | 0.563 | 0.675 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00826 | 30.70 | 0.01447 | 0.052 | 0.00 |
| M NE APARTMENT | 7504.76 | 9005.71 | 102.05 | 0.549 | 0.659 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00824 | 30.70 | 0.01447 | 0.052 | 0.00 |
| M N1 APARTMENT | 6650.89 | 7981.07 | 90.44 | 0.485 | 0.582 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00824 | 30.70 | 0.01447 | 0.052 | 0.00 |
| M N2 APARTMENT | 6631.37 | 7957.64 | 90.17 | 0.484 | 0.580 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00825 | 30.70 | 0.01447 | 0.052 | 0.00 |
| M S1 APARTMENT | 6882.25 | 8258.71 | 93.58 | 0.502 | 0.603 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00829 | 30.70 | 0.01447 | 0.052 | 0.00 |
| M S2 APARTMENT | 6872.65 | 8247.18 | 93.45 | 0.502 | 0.602 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00829 | 30.70 | 0.01447 | 0.052 | 0.00 |
| T SW APARTMENT | 4754.25 | 5705.10 | 64.65 | 0.349 | 0.419 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00820 | 30.70 | 0.01447 | 0.026 | 0.00 |
| T NW APARTMENT | 4701.00 | 5641.20 | 63.92 | 0.345 | 0.414 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00819 | 30.70 | 0.01447 | 0.026 | 0.00 |
| T SE APARTMENT | 4213.81 | 5056.57 | 57.30 | 0.309 | 0.371 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00824 | 30.70 | 0.01447 | 0.026 | 0.00 |
| T NE APARTMENT | 4160.49 | 4992.59 | 56.57 | 0.305 | 0.366 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00822 | 30.70 | 0.01447 | 0.026 | 0.00 |
| T N1 APARTMENT | 3849.98 | 4619.98 | 52.35 | 0.282 | 0.338 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00819 | 30.70 | 0.01447 | 0.026 | 0.00 |
| T N2 APARTMENT | 3834.69 | 4601.63 | 52.14 | 0.280 | 0.337 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00819 | 30.70 | 0.01447 | 0.026 | 0.00 |
| T S1 APARTMENT | 3912.08 | 4694.50 | 53.20 | 0.286 | 0.344 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00821 | 30.70 | 0.01447 | 0.026 | 0.00 |
| T S2 APARTMENT | 3896.81 | 4676.18 | 52.99 | 0.285 | 0.342 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00821 | 30.70 | 0.01447 | 0.026 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 1449.43 | 1739.32 | 19.71 | 0.065 | 0.078 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 21.10 | 21.10 | 0.00761 | -6.30 | 0.00230 | 0.026 | 0.00 |
| G NW APARTMENT | 1333.97 | 1600.77 | 18.14 | 0.060 | 0.072 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00775 | -6.30 | 0.00230 | 0.026 | 0.00 |
| OFFICE | 1873.94 | 2248.73 | 25.48 | 0.084 | 0.101 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 21.10 | 21.10 | 0.00769 | -6.30 | 0.00230 | 0.038 | 0.00 |
| G NE APARTMENT | 1328.39 | 1594.06 | 18.06 | 0.059 | 0.071 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00774 | -6.30 | 0.00230 | 0.026 | 0.00 |
| G N1 APARTMENT | 755.03 | 906.04 | 10.27 | 0.034 | 0.040 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00788 | -6.30 | 0.00230 | 0.026 | 0.00 |
| G N2 APARTMENT | 754.86 | 905.83 | 10.26 | 0.034 | 0.040 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00788 | -6.30 | 0.00230 | 0.026 | 0.00 |
| G S1 APARTMENT | 874.42 | 1049.30 | 11.89 | 0.039 | 0.047 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 21.10 | 21.10 | 0.00761 | -6.30 | 0.00230 | 0.026 | 0.00 |
| G S2 APARTMENT | 884.79 | 1061.75 | 12.03 | 0.040 | 0.047 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 21.10 | 21.10 | 0.00761 | -6.30 | 0.00230 | 0.026 | 0.00 |
| M SW APARTMENT | 2788.63 | 3346.35 | 37.92 | 0.125 | 0.150 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00744 | -6.30 | 0.00230 | 0.052 | 0.00 |
| M NW APARTMENT | 2522.71 | 3027.25 | 34.30 | 0.113 | 0.135 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00762 | -6.30 | 0.00230 | 0.052 | 0.00 |
| M SE APARTMENT | 2775.20 | 3330.24 | 37.74 | 0.124 | 0.149 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00744 | -6.30 | 0.00230 | 0.052 | 0.00 |
| M NE APARTMENT | 2509.23 | 3011.07 | 34.12 | 0.112 | 0.135 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00762 | -6.30 | 0.00230 | 0.052 | 0.00 |
| M N1 APARTMENT | 1302.38 | 1562.85 | 17.71 | 0.058 | 0.070 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00772 | -6.30 | 0.00230 | 0.052 | 0.00 |
| M N2 APARTMENT | 1302.01 | 1562.42 | 17.70 | 0.058 | 0.070 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00772 | -6.30 | 0.00230 | 0.052 | 0.00 |
| M S1 APARTMENT | 1561.04 | 1873.25 | 21.23 | 0.070 | 0.084 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00739 | -6.30 | 0.00230 | 0.052 | 0.00 |
| M S2 APARTMENT | 1560.68 | 1872.82 | 21.22 | 0.070 | 0.084 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00739 | -6.30 | 0.00230 | 0.052 | 0.00 |
| T SW APARTMENT | 2327.21 | 2792.65 | 31.65 | 0.104 | 0.125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00755 | -6.30 | 0.00230 | 0.026 | 0.00 |
| T NW APARTMENT | 2186.72 | 2624.07 | 29.73 | 0.098 | 0.117 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00766 | -6.30 | 0.00230 | 0.026 | 0.00 |
| T SE APARTMENT | 2318.94 | 2782.73 | 31.53 | 0.104 | 0.124 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00755 | -6.30 | 0.00230 | 0.026 | 0.00 |
| T NE APARTMENT | 2178.38 | 2614.06 | 29.62 | 0.097 | 0.117 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00766 | -6.30 | 0.00230 | 0.026 | 0.00 |
| T N1 APARTMENT | 1498.65 | 1798.38 | 20.38 | 0.067 | 0.080 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00777 | -6.30 | 0.00230 | 0.026 | 0.00 |
| T N2 APARTMENT | 1498.41 | 1798.09 | 20.38 | 0.067 | 0.080 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00777 | -6.30 | 0.00230 | 0.026 | 0.00 |
| T S1 APARTMENT | 1639.09 | 1966.91 | 22.29 | 0.073 | 0.088 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00761 | -6.30 | 0.00230 | 0.026 | 0.00 |
| T S2 APARTMENT | 1638.85 | 1966.62 | 22.28 | 0.073 | 0.088 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00761 | -6.30 | 0.00230 | 0.026 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| SPLIT GSW | 0.31 | 0.31 | 0.08 | 0.08 | 0.3099 | 0.3099 | 0.3099 | 1.0000 | 1.0000 |
| SPLIT GNW | 0.30 | 0.30 | 0.07 | 0.07 | 0.3008 | 0.3008 | 0.3008 | 1.0000 | 1.0000 |
| SPLIT OFFICE | 0.35 | 0.35 | 0.10 | 0.10 | 0.3532 | 0.3532 | 0.3532 | 1.0000 | 1.0000 |
| SPLIT GNE | 0.28 | 0.28 | 0.07 | 0.07 | 0.2758 | 0.2758 | 0.2758 | 1.0000 | 1.0000 |
| SPLIT GN1 | 0.25 | 0.25 | 0.04 | 0.04 | 0.2488 | 0.2488 | 0.2488 | 1.0000 | 1.0000 |
| SPLIT GN2 | 0.25 | 0.25 | 0.04 | 0.04 | 0.2484 | 0.2484 | 0.2484 | 1.0000 | 1.0000 |
| SPLIT GS1 | 0.26 | 0.26 | 0.05 | 0.05 | 0.2575 | 0.2575 | 0.2575 | 1.0000 | 1.0000 |
| SPLIT GS2 | 0.26 | 0.26 | 0.05 | 0.05 | 0.2600 | 0.2600 | 0.2600 | 1.0000 | 1.0000 |
| SPLIT MSW | 0.74 | 0.74 | 0.15 | 0.15 | 0.7414 | 0.7414 | 0.7414 | 1.0000 | 1.0000 |
| SPLIT MNW | 0.72 | 0.72 | 0.14 | 0.14 | 0.7244 | 0.7244 | 0.7244 | 1.0000 | 1.0000 |
| SPLIT MSE | 0.68 | 0.68 | 0.15 | 0.15 | 0.6752 | 0.6752 | 0.6752 | 1.0000 | 1.0000 |
| SPLIT MNE | 0.66 | 0.66 | 0.13 | 0.13 | 0.6585 | 0.6585 | 0.6585 | 1.0000 | 1.0000 |
| SPLIT MN1 | 0.58 | 0.58 | 0.07 | 0.07 | 0.5820 | 0.5820 | 0.5820 | 1.0000 | 1.0000 |
| SPLIT MN2 | 0.58 | 0.58 | 0.07 | 0.07 | 0.5803 | 0.5803 | 0.5803 | 1.0000 | 1.0000 |
| SPLIT MS1 | 0.60 | 0.60 | 0.08 | 0.08 | 0.6028 | 0.6028 | 0.6028 | 1.0000 | 1.0000 |
| SPLIT MS2 | 0.60 | 0.60 | 0.08 | 0.08 | 0.6019 | 0.6019 | 0.6019 | 1.0000 | 1.0000 |
| SPLIT TSW | 0.42 | 0.42 | 0.12 | 0.12 | 0.4192 | 0.4192 | 0.4192 | 1.0000 | 1.0000 |
| SPLIT TNW | 0.41 | 0.41 | 0.12 | 0.12 | 0.4145 | 0.4145 | 0.4145 | 1.0000 | 1.0000 |
| SPLIT TSE | 0.37 | 0.37 | 0.12 | 0.12 | 0.3707 | 0.3707 | 0.3707 | 1.0000 | 1.0000 |
| SPLIT TNE | 0.37 | 0.37 | 0.12 | 0.12 | 0.3659 | 0.3659 | 0.3659 | 1.0000 | 1.0000 |
| SPLIT TN1 | 0.34 | 0.34 | 0.08 | 0.08 | 0.3380 | 0.3380 | 0.3380 | 1.0000 | 1.0000 |
| SPLIT TN2 | 0.34 | 0.34 | 0.08 | 0.08 | 0.3366 | 0.3366 | 0.3366 | 1.0000 | 1.0000 |
| SPLIT TS1 | 0.34 | 0.34 | 0.09 | 0.09 | 0.3436 | 0.3436 | 0.3436 | 1.0000 | 1.0000 |
| SPLIT TS2 | 0.34 | 0.34 | 0.09 | 0.09 | 0.3422 | 0.3422 | 0.3422 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| SPLIT GSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GSW | 5412.404 | 4332.561 | 0.309917 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5233.94 | 4650.50 | 0.309917 | 25.53 | 16.78 | 0.00877229 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 8.3747 | 24.00 | 0.00825183 | 42.8454 | 3535.84 | 0.00 | 5411.48 | 4246.53 |
| SPLIT GSW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GSW | 5412.404 | 5412.404 | 0.309917 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5412.40 | 5412.40 | 0.309917 | 18.80 | 12.88 | 0.00716808 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.3747 | 21.10 | 0.00761323 | 47.1919 | 1449.43 | 0.00 | 5419.52 | 5419.52 |
| SPLIT GSW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GSW | 5412.404 | 5412.404 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5412.40 | 5412.40 | 0.309917 | 18.80 | 12.88 | 0.00716808 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.3747 | 21.10 | 0.00761323 | 47.1919 | 1449.43 | 0.00 | -999.00 | -999.00 |
| SPLIT GNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNW | 5243.782 | 4195.325 | 0.300752 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5069.81 | 4515.60 | 0.300752 | 25.55 | 16.77 | 0.00875616 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 8.6299 | 24.00 | 0.00821682 | 42.6658 | 3433.58 | 0.00 | 5242.89 | 4112.21 |
| SPLIT GNW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GNW | 5243.782 | 5243.782 | 0.300752 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 5243.78 | 5243.78 | 0.300752 | 18.74 | 12.96 | 0.00727494 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.6299 | 21.10 | 0.00774503 | 47.9977 | 1333.97 | 0.00 | 5250.67 | 5250.67 |
| SPLIT GNW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GNW | 5243.782 | 5243.782 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 5243.78 | 5243.78 | 0.300752 | 18.74 | 12.96 | 0.00727494 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.6299 | 21.10 | 0.00774503 | 47.9977 | 1333.97 | 0.00 | -999.00 | -999.00 |
| SPLIT OFFICE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT OFFICE | 6100.126 | 4882.179 | 0.353159 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 5935.95 | 5274.80 | 0.353159 | 25.47 | 16.75 | 0.00876846 | 12.80 | 11.27 | 0.00800000 | 29.71 | 0.01446471 | 22.27 | 10.7901 | 23.90 | 0.00806732 | 42.1514 | 3788.90 | 0.00 | 6099.09 | 4785.61 |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT OFFICE | 6100.126 | 6100.126 | 0.353159 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 6100.13 | 6100.13 | 0.353159 | 18.14 | 12.57 | 0.00711003 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 10.7901 | 21.10 | 0.00769208 | 47.6740 | 1873.94 | 0.00 | 6108.14 | 6108.14 |
| SPLIT OFFICE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT OFFICE | 6100.126 | 6100.126 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 6100.13 | 6100.13 | 0.353159 | 18.14 | 12.57 | 0.00711003 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 10.7901 | 21.10 | 0.00769208 | 47.6740 | 1873.94 | 0.00 | -999.00 | -999.00 |
| SPLIT GNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNE | 4877.851 | 3902.591 | 0.275763 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4725.37 | 4161.56 | 0.275763 | 25.59 | 16.85 | 0.00883707 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 9.4119 | 24.00 | 0.00825219 | 42.8471 | 3156.54 | 0.00 | 4877.02 | 3826.32 |
| SPLIT GNE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GNE | 4877.851 | 4877.851 | 0.275763 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4877.85 | 4877.85 | 0.275763 | 18.52 | 12.83 | 0.00723157 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 9.4119 | 21.10 | 0.00774418 | 47.9925 | 1328.39 | 0.00 | 4884.26 | 4884.26 |
| SPLIT GNE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GNE | 4877.851 | 4877.851 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4877.85 | 4877.85 | 0.275763 | 18.52 | 12.83 | 0.00723157 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 9.4119 | 21.10 | 0.00774418 | 47.9925 | 1328.39 | 0.00 | -999.00 | -999.00 |
| SPLIT GN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN1 | 4458.346 | 3569.365 | 0.248779 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4326.88 | 3775.36 | 0.248779 | 25.65 | 16.93 | 0.00890580 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 10.4328 | 24.00 | 0.00825810 | 42.8773 | 2856.13 | 0.00 | 4457.59 | 3498.87 |
| SPLIT GN1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GN1 | 4458.346 | 4458.346 | 0.248779 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4458.35 | 4458.35 | 0.248779 | 18.24 | 12.79 | 0.00730009 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 10.4328 | 21.10 | 0.00788276 | 48.8400 | 755.03 | 0.00 | 4464.20 | 4464.20 |
| SPLIT GN1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GN1 | 4458.346 | 4458.346 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4458.35 | 4458.35 | 0.248779 | 18.24 | 12.79 | 0.00730009 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 10.4328 | 21.10 | 0.00788276 | 48.8400 | 755.03 | 0.00 | -999.00 | -999.00 |
| SPLIT GN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN2 | 4452.775 | 3564.575 | 0.248414 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4321.61 | 3770.14 | 0.248414 | 25.65 | 16.93 | 0.00890701 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 10.4481 | 24.00 | 0.00825838 | 42.8788 | 2852.07 | 0.00 | 4452.02 | 3494.18 |
| SPLIT GN2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GN2 | 4452.775 | 4452.775 | 0.248414 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4452.77 | 4452.77 | 0.248414 | 18.24 | 12.79 | 0.00729922 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 10.4481 | 21.10 | 0.00788274 | 48.8399 | 754.86 | 0.00 | 4458.63 | 4458.63 |
| SPLIT GN2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GN2 | 4452.775 | 4452.775 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4452.77 | 4452.77 | 0.248414 | 18.24 | 12.79 | 0.00729922 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 10.4481 | 21.10 | 0.00788274 | 48.8399 | 754.86 | 0.00 | -999.00 | -999.00 |
| SPLIT GS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS1 | 4639.741 | 3715.504 | 0.257526 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4506.19 | 3906.46 | 0.257526 | 25.63 | 16.96 | 0.00895070 | 12.80 | 11.27 | 0.00800000 | 30.69 | 0.01446650 | 22.54 | 10.0784 | 24.00 | 0.00833248 | 43.2589 | 2953.28 | 0.00 | 4638.95 | 3641.77 |
| SPLIT GS1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GS1 | 4639.741 | 4639.741 | 0.257526 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4639.74 | 4639.74 | 0.257526 | 18.34 | 12.61 | 0.00707250 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 10.0784 | 21.10 | 0.00760765 | 47.1571 | 874.42 | 0.00 | 4645.84 | 4645.84 |
| SPLIT GS1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GS1 | 4639.741 | 4639.741 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4639.74 | 4639.74 | 0.257526 | 18.34 | 12.61 | 0.00707250 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 10.0784 | 21.10 | 0.00760765 | 47.1571 | 874.42 | 0.00 | -999.00 | -999.00 |
| SPLIT GS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS2 | 4675.151 | 3742.150 | 0.259979 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4539.38 | 3940.81 | 0.259979 | 25.62 | 16.94 | 0.00894017 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 9.9833 | 24.00 | 0.00832727 | 43.2322 | 2980.26 | 0.00 | 4674.36 | 3668.07 |
| SPLIT GS2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GS2 | 4675.151 | 4675.151 | 0.259979 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4675.15 | 4675.15 | 0.259979 | 18.36 | 12.63 | 0.00708175 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 9.9833 | 21.10 | 0.00761232 | 47.1857 | 884.79 | 0.00 | 4681.29 | 4681.29 |
| SPLIT GS2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GS2 | 4675.151 | 4675.151 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4675.15 | 4675.15 | 0.259979 | 18.36 | 12.63 | 0.00708175 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 9.9833 | 21.10 | 0.00761232 | 47.1857 | 884.79 | 0.00 | -999.00 | -999.00 |
| SPLIT MSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSW | 12669.467 | 10137.264 | 0.741377 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12215.63 | 11030.76 | 0.741377 | 25.46 | 16.65 | 0.00865792 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 7.0017 | 24.00 | 0.00822060 | 42.6853 | 16845.54 | 0.00 | 12667.31 | 9937.21 |
| SPLIT MSW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MSW | 12669.467 | 12669.467 | 0.741377 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12669.47 | 12669.47 | 0.741377 | 19.18 | 12.95 | 0.00708062 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.0017 | 21.10 | 0.00744071 | 46.1358 | 5577.25 | 0.00 | 12686.12 | 12686.12 |
| SPLIT MSW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MSW | 12669.467 | 12669.467 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12669.47 | 12669.47 | 0.741377 | 19.18 | 12.95 | 0.00708062 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.0017 | 21.10 | 0.00744071 | 46.1358 | 5577.25 | 0.00 | -999.00 | -999.00 |
| SPLIT MNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNW | 12372.999 | 9902.266 | 0.724393 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11929.06 | 10783.70 | 0.724393 | 25.47 | 16.65 | 0.00865095 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 7.1659 | 24.00 | 0.00820205 | 42.5901 | 16468.85 | 0.00 | 12370.89 | 9706.69 |
| SPLIT MNW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MNW | 12372.999 | 12372.999 | 0.724393 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12373.00 | 12373.00 | 0.724393 | 19.14 | 13.08 | 0.00723611 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.1659 | 21.10 | 0.00761729 | 47.2165 | 5045.42 | 0.00 | 12389.26 | 12389.26 |
| SPLIT MNW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MNW | 12372.999 | 12372.999 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12373.00 | 12373.00 | 0.724393 | 19.14 | 13.08 | 0.00723611 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.1659 | 21.10 | 0.00761729 | 47.2165 | 5045.42 | 0.00 | -999.00 | -999.00 |
| SPLIT MSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSE | 11708.769 | 9377.996 | 0.675164 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11311.77 | 10096.19 | 0.675164 | 25.50 | 16.74 | 0.00873940 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 7.6884 | 24.00 | 0.00826241 | 42.8997 | 15379.15 | 0.00 | 11706.78 | 9191.86 |
| SPLIT MSE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MSE | 11708.769 | 11708.769 | 0.675164 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11708.77 | 11708.77 | 0.675164 | 18.99 | 12.84 | 0.00704303 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.6884 | 21.10 | 0.00743824 | 46.1207 | 5550.40 | 0.00 | 11724.16 | 11724.16 |
| SPLIT MSE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MSE | 11708.769 | 11708.769 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11708.77 | 11708.77 | 0.675164 | 18.99 | 12.84 | 0.00704303 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.6884 | 21.10 | 0.00743824 | 46.1207 | 5550.40 | 0.00 | -999.00 | -999.00 |
| SPLIT MNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNE | 11408.379 | 9130.183 | 0.658531 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11020.10 | 9852.61 | 0.658531 | 25.51 | 16.73 | 0.00872822 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 7.8826 | 24.00 | 0.00823719 | 42.7703 | 15009.51 | 0.00 | 11406.44 | 8949.48 |
| SPLIT MNE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MNE | 11408.379 | 11408.379 | 0.658531 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11408.38 | 11408.38 | 0.658531 | 18.94 | 12.96 | 0.00719627 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.8826 | 21.10 | 0.00761543 | 47.2051 | 5018.45 | 0.00 | 11423.37 | 11423.37 |
| SPLIT MNE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MNE | 11408.379 | 11408.379 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11408.38 | 11408.38 | 0.658531 | 18.94 | 12.96 | 0.00719627 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.8826 | 21.10 | 0.00761543 | 47.2051 | 5018.45 | 0.00 | -999.00 | -999.00 |
| SPLIT MN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN1 | 10223.387 | 8183.704 | 0.582038 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 9894.18 | 8758.58 | 0.582038 | 25.56 | 16.81 | 0.00879968 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 8.9185 | 24.00 | 0.00824479 | 42.8092 | 13301.79 | 0.00 | 10221.65 | 8020.82 |
| SPLIT MN1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MN1 | 10223.387 | 10223.387 | 0.582038 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10223.39 | 10223.39 | 0.582038 | 18.66 | 12.89 | 0.00723573 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.9185 | 21.10 | 0.00771924 | 47.8398 | 2604.75 | 0.00 | 10236.82 | 10236.82 |
| SPLIT MN1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MN1 | 10223.387 | 10223.387 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10223.39 | 10223.39 | 0.582038 | 18.66 | 12.89 | 0.00723573 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.9185 | 21.10 | 0.00771924 | 47.8398 | 2604.75 | 0.00 | -999.00 | -999.00 |
| SPLIT MN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN2 | 10196.264 | 8160.777 | 0.580295 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 9868.40 | 8733.38 | 0.580295 | 25.57 | 16.81 | 0.00880162 | 12.80 | 11.27 | 0.00800000 | 30.69 | 0.01446650 | 22.54 | 8.9453 | 24.00 | 0.00824510 | 42.8108 | 13262.73 | 0.00 | 10194.53 | 7998.39 |
| SPLIT MN2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MN2 | 10196.264 | 10196.264 | 0.580295 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10196.26 | 10196.26 | 0.580295 | 18.65 | 12.88 | 0.00723420 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.9453 | 21.10 | 0.00771916 | 47.8393 | 2604.03 | 0.00 | 10209.66 | 10209.66 |
| SPLIT MN2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MN2 | 10196.264 | 10196.264 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10196.26 | 10196.26 | 0.580295 | 18.65 | 12.88 | 0.00723420 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.9453 | 21.10 | 0.00771916 | 47.8393 | 2604.03 | 0.00 | -999.00 | -999.00 |
| SPLIT MS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS1 | 10606.256 | 8494.431 | 0.602791 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 10267.04 | 9064.26 | 0.602791 | 25.55 | 16.82 | 0.00881757 | 12.80 | 11.27 | 0.00800000 | 30.69 | 0.01446650 | 22.54 | 8.6115 | 24.00 | 0.00828528 | 43.0169 | 13764.51 | 0.00 | 10604.45 | 8326.71 |
| SPLIT MS1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MS1 | 10606.256 | 10606.256 | 0.602791 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10606.26 | 10606.26 | 0.602791 | 18.74 | 12.65 | 0.00695077 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.6115 | 21.10 | 0.00738922 | 45.8194 | 3122.08 | 0.00 | 10620.19 | 10620.19 |
| SPLIT MS1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MS1 | 10606.256 | 10606.256 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10606.26 | 10606.26 | 0.602791 | 18.74 | 12.65 | 0.00695077 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.6115 | 21.10 | 0.00738922 | 45.8194 | 3122.08 | 0.00 | -999.00 | -999.00 |
| SPLIT MS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS2 | 10593.278 | 8483.272 | 0.601927 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 10254.77 | 9051.98 | 0.601927 | 25.55 | 16.82 | 0.00881872 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 8.6238 | 24.00 | 0.00828570 | 43.0191 | 13745.30 | 0.00 | 10591.48 | 8315.80 |
| SPLIT MS2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MS2 | 10593.278 | 10593.278 | 0.601927 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10593.28 | 10593.28 | 0.601927 | 18.74 | 12.65 | 0.00695002 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.6238 | 21.10 | 0.00738909 | 45.8186 | 3121.37 | 0.00 | 10607.20 | 10607.20 |
| SPLIT MS2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MS2 | 10593.278 | 10593.278 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10593.28 | 10593.28 | 0.601927 | 18.74 | 12.65 | 0.00695002 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.6238 | 21.10 | 0.00738909 | 45.8186 | 3121.37 | 0.00 | -999.00 | -999.00 |
| SPLIT TSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSW | 7074.582 | 5664.256 | 0.419231 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6809.68 | 6207.71 | 0.419231 | 25.41 | 16.59 | 0.00859232 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 6.1910 | 24.00 | 0.00820464 | 42.6036 | 4754.25 | 0.00 | 7073.38 | 5552.11 |
| SPLIT TSW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TSW | 7074.582 | 7074.582 | 0.419231 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 7074.58 | 7074.58 | 0.419231 | 19.40 | 13.17 | 0.00722385 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 6.1910 | 21.10 | 0.00754895 | 46.7998 | 2327.21 | 0.00 | 7083.88 | 7083.88 |
| SPLIT TSW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TSW | 7074.582 | 7074.582 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 7074.58 | 7074.58 | 0.419231 | 19.40 | 13.17 | 0.00722385 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 6.1910 | 21.10 | 0.00754895 | 46.7998 | 2327.21 | 0.00 | -999.00 | -999.00 |
| SPLIT TNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNW | 6987.641 | 5590.156 | 0.414489 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6725.14 | 6137.91 | 0.414489 | 25.42 | 16.58 | 0.00858452 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 6.2618 | 24.00 | 0.00819160 | 42.5366 | 4701.00 | 0.00 | 6986.45 | 5479.84 |
| SPLIT TNW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TNW | 6987.641 | 6987.641 | 0.414489 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6987.64 | 6987.64 | 0.414489 | 19.38 | 13.26 | 0.00732206 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 6.2618 | 21.10 | 0.00765769 | 47.4647 | 2186.72 | 0.00 | 6996.82 | 6996.82 |
| SPLIT TNW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TNW | 6987.641 | 6987.641 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6987.64 | 6987.64 | 0.414489 | 19.38 | 13.26 | 0.00732206 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 6.2618 | 21.10 | 0.00765769 | 47.4647 | 2186.72 | 0.00 | -999.00 | -999.00 |
| SPLIT TSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSE | 6355.246 | 5084.331 | 0.370727 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6130.15 | 5520.40 | 0.370727 | 25.46 | 16.67 | 0.00867673 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 7.0010 | 24.00 | 0.00824087 | 42.7893 | 4213.81 | 0.00 | 6354.16 | 4984.02 |
| SPLIT TSE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TSE | 6355.246 | 6355.246 | 0.370727 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6355.25 | 6355.25 | 0.370727 | 19.18 | 13.04 | 0.00717994 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.0010 | 21.10 | 0.00754747 | 46.7907 | 2318.94 | 0.00 | 6363.60 | 6363.60 |
| SPLIT TSE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TSE | 6355.246 | 6355.246 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6355.25 | 6355.25 | 0.370727 | 19.18 | 13.04 | 0.00717994 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.0010 | 21.10 | 0.00754747 | 46.7907 | 2318.94 | 0.00 | -999.00 | -999.00 |
| SPLIT TNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNE | 6265.496 | 5015.313 | 0.365949 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6042.60 | 5449.87 | 0.365949 | 25.47 | 16.67 | 0.00866656 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 7.0924 | 24.00 | 0.00822381 | 42.7017 | 4160.49 | 0.00 | 6264.43 | 4916.17 |
| SPLIT TNE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TNE | 6265.496 | 6265.496 | 0.365949 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6265.50 | 6265.50 | 0.365949 | 19.16 | 13.12 | 0.00727643 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.0924 | 21.10 | 0.00765648 | 47.4573 | 2178.38 | 0.00 | 6273.73 | 6273.73 |
| SPLIT TNE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TNE | 6265.496 | 6265.496 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6265.50 | 6265.50 | 0.365949 | 19.16 | 13.12 | 0.00727643 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.0924 | 21.10 | 0.00765648 | 47.4573 | 2178.38 | 0.00 | -999.00 | -999.00 |
| SPLIT TN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN1 | 5801.539 | 4644.383 | 0.337972 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5597.20 | 5046.66 | 0.337972 | 25.50 | 16.68 | 0.00867011 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 7.6795 | 24.00 | 0.00818795 | 42.5177 | 3849.98 | 0.00 | 5800.55 | 4552.52 |
| SPLIT TN1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TN1 | 5801.539 | 5801.539 | 0.337972 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 5801.54 | 5801.54 | 0.337972 | 19.00 | 13.13 | 0.00735370 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.6795 | 21.10 | 0.00777426 | 48.1770 | 1498.65 | 0.00 | 5809.16 | 5809.16 |
| SPLIT TN1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TN1 | 5801.539 | 5801.539 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 5801.54 | 5801.54 | 0.337972 | 19.00 | 13.13 | 0.00735370 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.6795 | 21.10 | 0.00777426 | 48.1770 | 1498.65 | 0.00 | -999.00 | -999.00 |
| SPLIT TN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN2 | 5781.043 | 4626.846 | 0.336592 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5577.84 | 5027.13 | 0.336592 | 25.50 | 16.68 | 0.00867301 | 12.80 | 11.27 | 0.00800000 | 30.69 | 0.01446650 | 22.54 | 7.7110 | 24.00 | 0.00818895 | 42.5228 | 3834.69 | 0.00 | 5780.06 | 4535.41 |
| SPLIT TN2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TN2 | 5781.043 | 5781.043 | 0.336592 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 5781.04 | 5781.04 | 0.336592 | 18.99 | 13.13 | 0.00735194 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.7110 | 21.10 | 0.00777423 | 48.1768 | 1498.41 | 0.00 | 5788.64 | 5788.64 |
| SPLIT TN2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TN2 | 5781.043 | 5781.043 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 5781.04 | 5781.04 | 0.336592 | 18.99 | 13.13 | 0.00735194 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.7110 | 21.10 | 0.00777423 | 48.1768 | 1498.41 | 0.00 | -999.00 | -999.00 |
| SPLIT TS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS1 | 5906.454 | 4725.197 | 0.343562 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5699.54 | 5129.08 | 0.343562 | 25.49 | 16.69 | 0.00868289 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 7.5545 | 24.00 | 0.00821026 | 42.6322 | 3912.08 | 0.00 | 5905.45 | 4631.95 |
| SPLIT TS1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TS1 | 5906.454 | 5906.454 | 0.343562 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 5906.45 | 5906.45 | 0.343562 | 19.03 | 13.01 | 0.00720731 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.5545 | 21.10 | 0.00760851 | 47.1633 | 1639.09 | 0.00 | 5914.22 | 5914.22 |
| SPLIT TS1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TS1 | 5906.454 | 5906.454 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 5906.45 | 5906.45 | 0.343562 | 19.03 | 13.01 | 0.00720731 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.5545 | 21.10 | 0.00760851 | 47.1633 | 1639.09 | 0.00 | -999.00 | -999.00 |
| SPLIT TS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS2 | 5886.109 | 4713.630 | 0.342185 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5680.34 | 5109.60 | 0.342185 | 25.50 | 16.69 | 0.00868591 | 12.80 | 11.27 | 0.00800000 | 30.70 | 0.01446650 | 22.54 | 7.5849 | 24.00 | 0.00821147 | 42.6384 | 3896.81 | 0.00 | 5885.11 | 4620.27 |
| SPLIT TS2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TS2 | 5886.109 | 5886.109 | 0.342185 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 5886.11 | 5886.11 | 0.342185 | 19.02 | 13.00 | 0.00720565 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.5849 | 21.10 | 0.00760846 | 47.1630 | 1638.85 | 0.00 | 5893.84 | 5893.84 |
| SPLIT TS2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TS2 | 5886.109 | 5886.109 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 5886.11 | 5886.11 | 0.342185 | 19.02 | 13.00 | 0.00720565 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 7.5849 | 21.10 | 0.00760846 | 47.1630 | 1638.85 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| SPLIT GSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5412.404 | 4332.561 | 0.309917 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1472 | 1004.8586 | 1.1610 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.309917 | 0.35980619 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5233.94 | 4650.50 | 0.9670 | 0.35980619 | 0.309917 | 25.53 | 16.78 | 0.00877229 | 48013.4 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 347.140 | 4886.80 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 8.3747 | 24.03 | 0.00825183 | 24.00 | 0.00825183 | 42.8454 | 3535.84 | 0.00 | 5411.48 | 4246.53 | 0.34559656 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.66 | 14.15 | 0.00986303 | 39664.0 | |
| SPLIT GSW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 5412.404 | 5412.404 | 0.309917 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.309917 | 0.35980619 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | Sensible | 5412.40 | 5412.40 | 1.0000 | 0.35980619 | 0.309917 | 18.80 | 12.88 | 0.00716808 | 37073.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5412.40 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 8.3747 | 21.10 | 0.00761323 | 21.10 | 0.00761323 | 47.1919 | 1449.43 | 0.00 | 5419.52 | 5419.52 | 0.35344830 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.13 | 20.57 | 0.00875166 | 58777.4 | |
| SPLIT GSW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5412.404 | 5412.404 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.309917 | 0.35980619 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | Sensible | 5412.40 | 5412.40 | 1.0000 | 0.35980619 | 0.309917 | 18.80 | 12.88 | 0.00716808 | 37073.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5412.40 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 8.3747 | 21.10 | 0.00761323 | 21.10 | 0.00761323 | 47.1919 | 1449.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5243.782 | 4195.325 | 0.300752 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1173 | 1004.8586 | 1.1610 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.300752 | 0.34916655 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5069.81 | 4515.60 | 0.9668 | 0.34916655 | 0.300752 | 25.55 | 16.77 | 0.00875616 | 47986.0 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 336.875 | 4732.93 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 8.6299 | 24.03 | 0.00821682 | 24.00 | 0.00821682 | 42.6658 | 3433.58 | 0.00 | 5242.89 | 4112.21 | 0.33537711 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.68 | 14.16 | 0.00986283 | 39689.6 | |
| SPLIT GNW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 5243.782 | 5243.782 | 0.300752 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.300752 | 0.34916655 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 5243.78 | 5243.78 | 1.0000 | 0.34916655 | 0.300752 | 18.74 | 12.96 | 0.00727494 | 37273.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5243.78 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 8.6299 | 21.10 | 0.00774503 | 21.10 | 0.00774503 | 47.9977 | 1333.97 | 0.00 | 5250.67 | 5250.67 | 0.34299667 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.10 | 20.56 | 0.00875166 | 58752.3 | |
| SPLIT GNW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5243.782 | 5243.782 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.300752 | 0.34916655 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 5243.78 | 5243.78 | 1.0000 | 0.34916655 | 0.300752 | 18.74 | 12.96 | 0.00727494 | 37273.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5243.78 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 8.6299 | 21.10 | 0.00774503 | 21.10 | 0.00774503 | 47.9977 | 1333.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT OFFICE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6100.126 | 4882.179 | 0.353159 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1401 | 1004.8586 | 1.1610 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.353159 | 0.41000881 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | Sensible | 5935.95 | 5274.80 | 0.9731 | 0.41000881 | 0.353159 | 25.47 | 16.75 | 0.00876846 | 47939.3 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 395.576 | 5540.38 | 29.71 | 0.01446471 | 22.27 | 0.03810604 | 10.7901 | 23.90 | 0.00807949 | 23.90 | 0.00806732 | 42.1514 | 3788.90 | 0.00 | 6099.09 | 4785.61 | 0.39381657 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.79 | 14.22 | 0.00987698 | 39835.3 | |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6100.126 | 6100.126 | 0.353159 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.353159 | 0.41000881 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | Sensible | 6100.13 | 6100.13 | 1.0000 | 0.41000881 | 0.353159 | 18.14 | 12.57 | 0.00711003 | 36252.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6100.13 | -6.30 | 0.00229779 | -6.30 | 0.03810604 | 10.7901 | 21.10 | 0.00769208 | 21.10 | 0.00769208 | 47.6740 | 1873.94 | 0.00 | 6108.14 | 6108.14 | 0.40276383 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 35.96 | 20.52 | 0.00875166 | 58609.7 | |
| SPLIT OFFICE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6100.126 | 6100.126 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.353159 | 0.41000881 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | Sensible | 6100.13 | 6100.13 | 1.0000 | 0.41000881 | 0.353159 | 18.14 | 12.57 | 0.00711003 | 36252.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6100.13 | -6.30 | 0.00229779 | -6.30 | 0.03810604 | 10.7901 | 21.10 | 0.00769208 | 21.10 | 0.00769208 | 47.6740 | 1873.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4877.851 | 3902.591 | 0.275763 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2677 | 1004.8586 | 1.1610 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.275763 | 0.32015390 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4725.37 | 4161.56 | 0.9687 | 0.32015390 | 0.275763 | 25.59 | 16.85 | 0.00883707 | 48237.1 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 308.884 | 4416.49 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 9.4119 | 24.02 | 0.00825219 | 24.00 | 0.00825219 | 42.8471 | 3156.54 | 0.00 | 4877.02 | 3826.32 | 0.30751024 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 14.08 | 0.00984502 | 39462.7 | |
| SPLIT GNE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 4877.851 | 4877.851 | 0.275763 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.275763 | 0.32015390 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 4877.85 | 4877.85 | 1.0000 | 0.32015390 | 0.275763 | 18.52 | 12.83 | 0.00723157 | 36945.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4877.85 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 9.4119 | 21.10 | 0.00774418 | 21.10 | 0.00774418 | 47.9925 | 1328.39 | 0.00 | 4884.26 | 4884.26 | 0.31449668 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.32 | 20.63 | 0.00875166 | 58974.5 | |
| SPLIT GNE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4877.851 | 4877.851 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.275763 | 0.32015390 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 4877.85 | 4877.85 | 1.0000 | 0.32015390 | 0.275763 | 18.52 | 12.83 | 0.00723157 | 36945.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4877.85 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 9.4119 | 21.10 | 0.00774418 | 21.10 | 0.00774418 | 47.9925 | 1328.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4458.346 | 3569.365 | 0.248779 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3954 | 1004.8586 | 1.1610 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.248779 | 0.28882638 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4326.88 | 3775.36 | 0.9705 | 0.28882638 | 0.248779 | 25.65 | 16.93 | 0.00890580 | 48469.3 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 278.659 | 4048.22 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 10.4328 | 24.01 | 0.00825810 | 24.00 | 0.00825810 | 42.8773 | 2856.13 | 0.00 | 4457.59 | 3498.87 | 0.27741992 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.34 | 14.00 | 0.00982971 | 39254.4 | |
| SPLIT GN1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 4458.346 | 4458.346 | 0.248779 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.248779 | 0.28882638 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 4458.35 | 4458.35 | 1.0000 | 0.28882638 | 0.248779 | 18.24 | 12.79 | 0.00730009 | 36834.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4458.35 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 10.4328 | 21.10 | 0.00788276 | 21.10 | 0.00788276 | 48.8400 | 755.03 | 0.00 | 4464.20 | 4464.20 | 0.28372273 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.52 | 20.69 | 0.00875166 | 59178.5 | |
| SPLIT GN1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4458.346 | 4458.346 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.248779 | 0.28882638 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 4458.35 | 4458.35 | 1.0000 | 0.28882638 | 0.248779 | 18.24 | 12.79 | 0.00730009 | 36834.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4458.35 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 10.4328 | 21.10 | 0.00788276 | 21.10 | 0.00788276 | 48.8400 | 755.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4452.775 | 3564.575 | 0.248414 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3977 | 1004.8586 | 1.1610 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.248414 | 0.28840242 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4321.61 | 3770.14 | 0.9705 | 0.28840242 | 0.248414 | 25.65 | 16.93 | 0.00890701 | 48473.2 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 278.250 | 4043.36 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 10.4481 | 24.00 | 0.00825838 | 24.00 | 0.00825838 | 42.8788 | 2852.07 | 0.00 | 4452.02 | 3494.18 | 0.27701271 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.34 | 14.00 | 0.00982896 | 39250.9 | |
| SPLIT GN2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 4452.775 | 4452.775 | 0.248414 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.248414 | 0.28840242 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 4452.77 | 4452.77 | 1.0000 | 0.28840242 | 0.248414 | 18.24 | 12.79 | 0.00729922 | 36827.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4452.77 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 10.4481 | 21.10 | 0.00788274 | 21.10 | 0.00788274 | 48.8399 | 754.86 | 0.00 | 4458.63 | 4458.63 | 0.28330626 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.52 | 20.69 | 0.00875166 | 59181.9 | |
| SPLIT GN2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4452.775 | 4452.775 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.248414 | 0.28840242 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 4452.77 | 4452.77 | 1.0000 | 0.28840242 | 0.248414 | 18.24 | 12.79 | 0.00729922 | 36827.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4452.77 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 10.4481 | 21.10 | 0.00788274 | 21.10 | 0.00788274 | 48.8399 | 754.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4639.741 | 3715.504 | 0.257526 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4789 | 1004.8586 | 1.1610 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.257526 | 0.29898176 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4506.19 | 3906.46 | 0.9712 | 0.29898176 | 0.257526 | 25.63 | 16.96 | 0.00895070 | 48563.0 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 288.457 | 4217.73 | 30.69 | 0.01446650 | 22.54 | 0.02595455 | 10.0784 | 24.01 | 0.00833248 | 24.00 | 0.00833248 | 43.2589 | 2953.28 | 0.00 | 4638.95 | 3641.77 | 0.28717424 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.27 | 13.97 | 0.00982322 | 39168.6 | |
| SPLIT GS1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 4639.741 | 4639.741 | 0.257526 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.257526 | 0.29898176 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | Sensible | 4639.74 | 4639.74 | 1.0000 | 0.29898176 | 0.257526 | 18.34 | 12.61 | 0.00707250 | 36355.9 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4639.74 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 10.0784 | 21.10 | 0.00760765 | 21.10 | 0.00760765 | 47.1571 | 874.42 | 0.00 | 4645.84 | 4645.84 | 0.29369866 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.60 | 20.71 | 0.00875166 | 59262.5 | |
| SPLIT GS1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4639.741 | 4639.741 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.257526 | 0.29898176 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | Sensible | 4639.74 | 4639.74 | 1.0000 | 0.29898176 | 0.257526 | 18.34 | 12.61 | 0.00707250 | 36355.9 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4639.74 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 10.0784 | 21.10 | 0.00760765 | 21.10 | 0.00760765 | 47.1571 | 874.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4675.151 | 3742.150 | 0.259979 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4593 | 1004.8586 | 1.1610 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.259979 | 0.30182918 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4539.38 | 3940.81 | 0.9710 | 0.30182918 | 0.259979 | 25.62 | 16.94 | 0.00894017 | 48529.2 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 291.204 | 4248.18 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 9.9833 | 24.01 | 0.00832727 | 24.00 | 0.00832727 | 43.2322 | 2980.26 | 0.00 | 4674.36 | 3668.07 | 0.28990921 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.98 | 0.00982375 | 39198.9 | |
| SPLIT GS2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 4675.151 | 4675.151 | 0.259979 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.259979 | 0.30182918 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | Sensible | 4675.15 | 4675.15 | 1.0000 | 0.30182918 | 0.259979 | 18.36 | 12.63 | 0.00708175 | 36405.9 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4675.15 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 9.9833 | 21.10 | 0.00761232 | 21.10 | 0.00761232 | 47.1857 | 884.79 | 0.00 | 4681.29 | 4681.29 | 0.29649577 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.57 | 20.70 | 0.00875166 | 59232.8 | |
| SPLIT GS2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4675.151 | 4675.151 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.259979 | 0.30182918 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | Sensible | 4675.15 | 4675.15 | 1.0000 | 0.30182918 | 0.259979 | 18.36 | 12.63 | 0.00708175 | 36405.9 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4675.15 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 9.9833 | 21.10 | 0.00761232 | 21.10 | 0.00761232 | 47.1857 | 884.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12669.467 | 10137.264 | 0.741377 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9346 | 1004.8586 | 1.1610 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.741377 | 0.86072141 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12215.63 | 11030.76 | 0.9642 | 0.86072141 | 0.741377 | 25.46 | 16.65 | 0.00865792 | 47642.5 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 830.422 | 11385.21 | 30.70 | 0.01446650 | 22.54 | 0.05190911 | 7.0017 | 24.05 | 0.00822060 | 24.00 | 0.00822060 | 42.6853 | 16845.54 | 0.00 | 12667.31 | 9937.21 | 0.82672942 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.92 | 14.28 | 0.00988991 | 40000.2 | |
| SPLIT MSW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 12669.467 | 12669.467 | 0.741377 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.741377 | 0.86072141 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 12669.47 | 12669.47 | 1.0000 | 0.86072141 | 0.741377 | 19.18 | 12.95 | 0.00708062 | 37234.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12669.47 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 7.0017 | 21.10 | 0.00744071 | 21.10 | 0.00744071 | 46.1358 | 5577.25 | 0.00 | 12686.12 | 12686.12 | 0.84551220 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 35.80 | 20.47 | 0.00875166 | 58448.2 | |
| SPLIT MSW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12669.467 | 12669.467 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.741377 | 0.86072141 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 12669.47 | 12669.47 | 1.0000 | 0.86072141 | 0.741377 | 19.18 | 12.95 | 0.00708062 | 37234.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12669.47 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 7.0017 | 21.10 | 0.00744071 | 21.10 | 0.00744071 | 46.1358 | 5577.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12372.999 | 9902.266 | 0.724393 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9217 | 1004.8586 | 1.1610 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.724393 | 0.84100306 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11929.06 | 10783.70 | 0.9641 | 0.84100306 | 0.724393 | 25.47 | 16.65 | 0.00865095 | 47634.5 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 811.398 | 11117.66 | 30.70 | 0.01446650 | 22.54 | 0.05190911 | 7.1659 | 24.04 | 0.00820205 | 24.00 | 0.00820205 | 42.5901 | 16468.85 | 0.00 | 12370.89 | 9706.69 | 0.80778979 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.92 | 14.28 | 0.00989153 | 40007.9 | |
| SPLIT MNW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 12372.999 | 12372.999 | 0.724393 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.724393 | 0.84100306 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 12373.00 | 12373.00 | 1.0000 | 0.84100306 | 0.724393 | 19.14 | 13.08 | 0.00723611 | 37583.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12373.00 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 7.1659 | 21.10 | 0.00761729 | 21.10 | 0.00761729 | 47.2165 | 5045.42 | 0.00 | 12389.26 | 12389.26 | 0.82614227 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 35.80 | 20.47 | 0.00875166 | 58440.6 | |
| SPLIT MNW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12372.999 | 12372.999 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.724393 | 0.84100306 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 12373.00 | 12373.00 | 1.0000 | 0.84100306 | 0.724393 | 19.14 | 13.08 | 0.00723611 | 37583.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12373.00 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 7.1659 | 21.10 | 0.00761729 | 21.10 | 0.00761729 | 47.2165 | 5045.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11708.769 | 9377.996 | 0.675164 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0861 | 1004.8586 | 1.1610 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.675164 | 0.78384996 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11311.77 | 10096.19 | 0.9661 | 0.78384996 | 0.675164 | 25.50 | 16.74 | 0.00873940 | 47891.9 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 756.257 | 10555.51 | 30.70 | 0.01446650 | 22.54 | 0.05190911 | 7.6884 | 24.04 | 0.00826241 | 24.00 | 0.00826241 | 42.8997 | 15379.15 | 0.00 | 11706.78 | 9191.86 | 0.75289381 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.73 | 14.19 | 0.00987499 | 39773.3 | |
| SPLIT MSE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 11708.769 | 11708.769 | 0.675164 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.675164 | 0.78384996 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11708.77 | 11708.77 | 1.0000 | 0.78384996 | 0.675164 | 18.99 | 12.84 | 0.00704303 | 36947.4 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11708.77 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 7.6884 | 21.10 | 0.00743824 | 21.10 | 0.00743824 | 46.1207 | 5550.40 | 0.00 | 11724.16 | 11724.16 | 0.76999909 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.02 | 20.54 | 0.00875166 | 58670.3 | |
| SPLIT MSE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11708.769 | 11708.769 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.675164 | 0.78384996 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11708.77 | 11708.77 | 1.0000 | 0.78384996 | 0.675164 | 18.99 | 12.84 | 0.00704303 | 36947.4 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11708.77 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 7.6884 | 21.10 | 0.00743824 | 21.10 | 0.00743824 | 46.1207 | 5550.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11408.379 | 9130.183 | 0.658531 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0653 | 1004.8586 | 1.1610 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.658531 | 0.76453931 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11020.10 | 9852.61 | 0.9660 | 0.76453931 | 0.658531 | 25.51 | 16.73 | 0.00872822 | 47874.7 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 737.626 | 10282.47 | 30.70 | 0.01446650 | 22.54 | 0.05190911 | 7.8826 | 24.04 | 0.00823719 | 24.00 | 0.00823719 | 42.7703 | 15009.51 | 0.00 | 11406.44 | 8949.48 | 0.73434578 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.76 | 14.20 | 0.00987286 | 39789.6 | |
| SPLIT MNE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 11408.379 | 11408.379 | 0.658531 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.658531 | 0.76453931 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11408.38 | 11408.38 | 1.0000 | 0.76453931 | 0.658531 | 18.94 | 12.96 | 0.00719627 | 37282.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11408.38 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 7.8826 | 21.10 | 0.00761543 | 21.10 | 0.00761543 | 47.2051 | 5018.45 | 0.00 | 11423.37 | 11423.37 | 0.75102966 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.01 | 20.53 | 0.00875166 | 58654.4 | |
| SPLIT MNE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11408.379 | 11408.379 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.658531 | 0.76453931 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11408.38 | 11408.38 | 1.0000 | 0.76453931 | 0.658531 | 18.94 | 12.96 | 0.00719627 | 37282.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11408.38 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 7.8826 | 21.10 | 0.00761543 | 21.10 | 0.00761543 | 47.2051 | 5018.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10223.387 | 8183.704 | 0.582038 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1982 | 1004.8586 | 1.1610 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.582038 | 0.67573294 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 9894.18 | 8758.58 | 0.9678 | 0.67573294 | 0.582038 | 25.56 | 16.81 | 0.00879968 | 48113.8 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 651.946 | 9242.24 | 30.70 | 0.01446650 | 22.54 | 0.05190911 | 8.9185 | 24.02 | 0.00824479 | 24.00 | 0.00824479 | 42.8092 | 13301.79 | 0.00 | 10221.65 | 8020.82 | 0.64904660 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.59 | 14.12 | 0.00985518 | 39573.7 | |
| SPLIT MN1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 10223.387 | 10223.387 | 0.582038 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.582038 | 0.67573294 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10223.39 | 10223.39 | 1.0000 | 0.67573294 | 0.582038 | 18.66 | 12.89 | 0.00723573 | 37093.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10223.39 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 8.9185 | 21.10 | 0.00771924 | 21.10 | 0.00771924 | 47.8398 | 2604.75 | 0.00 | 10236.82 | 10236.82 | 0.66379253 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.21 | 20.60 | 0.00875166 | 58865.8 | |
| SPLIT MN1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10223.387 | 10223.387 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.582038 | 0.67573294 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10223.39 | 10223.39 | 1.0000 | 0.67573294 | 0.582038 | 18.66 | 12.89 | 0.00723573 | 37093.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10223.39 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 8.9185 | 21.10 | 0.00771924 | 21.10 | 0.00771924 | 47.8398 | 2604.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10196.264 | 8160.777 | 0.580295 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2018 | 1004.8586 | 1.1610 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.580295 | 0.67370842 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 9868.40 | 8733.38 | 0.9678 | 0.67370842 | 0.580295 | 25.57 | 16.81 | 0.00880162 | 48119.8 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 649.993 | 9218.40 | 30.69 | 0.01446650 | 22.54 | 0.05190911 | 8.9453 | 24.02 | 0.00824510 | 24.00 | 0.00824510 | 42.8108 | 13262.73 | 0.00 | 10194.53 | 7998.39 | 0.64710203 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.59 | 14.12 | 0.00985403 | 39568.3 | |
| SPLIT MN2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 10196.264 | 10196.264 | 0.580295 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.580295 | 0.67370842 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10196.26 | 10196.26 | 1.0000 | 0.67370842 | 0.580295 | 18.65 | 12.88 | 0.00723420 | 37082.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10196.26 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 8.9453 | 21.10 | 0.00771916 | 21.10 | 0.00771916 | 47.8393 | 2604.03 | 0.00 | 10209.66 | 10209.66 | 0.66180379 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.22 | 20.60 | 0.00875166 | 58871.1 | |
| SPLIT MN2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10196.264 | 10196.264 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.580295 | 0.67370842 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10196.26 | 10196.26 | 1.0000 | 0.67370842 | 0.580295 | 18.65 | 12.88 | 0.00723420 | 37082.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10196.26 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 8.9453 | 21.10 | 0.00771916 | 21.10 | 0.00771916 | 47.8393 | 2604.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10606.256 | 8494.431 | 0.602791 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2314 | 1004.8586 | 1.1610 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.602791 | 0.69982593 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 10267.04 | 9064.26 | 0.9680 | 0.69982593 | 0.602791 | 25.55 | 16.82 | 0.00881757 | 48143.0 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 675.191 | 9591.84 | 30.69 | 0.01446650 | 22.54 | 0.05190911 | 8.6115 | 24.03 | 0.00828528 | 24.00 | 0.00828528 | 43.0169 | 13764.51 | 0.00 | 10604.45 | 8326.71 | 0.67218809 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.56 | 14.11 | 0.00985609 | 39546.4 | |
| SPLIT MS1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 10606.256 | 10606.256 | 0.602791 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.602791 | 0.69982593 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10606.26 | 10606.26 | 1.0000 | 0.69982593 | 0.602791 | 18.74 | 12.65 | 0.00695077 | 36456.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10606.26 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 8.6115 | 21.10 | 0.00738922 | 21.10 | 0.00738922 | 45.8194 | 3122.08 | 0.00 | 10620.19 | 10620.19 | 0.68745979 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.24 | 20.60 | 0.00875166 | 58892.6 | |
| SPLIT MS1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10606.256 | 10606.256 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.602791 | 0.69982593 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10606.26 | 10606.26 | 1.0000 | 0.69982593 | 0.602791 | 18.74 | 12.65 | 0.00695077 | 36456.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10606.26 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 8.6115 | 21.10 | 0.00738922 | 21.10 | 0.00738922 | 45.8194 | 3122.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10593.278 | 8483.272 | 0.601927 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2336 | 1004.8586 | 1.1610 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.601927 | 0.69882362 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 10254.77 | 9051.98 | 0.9680 | 0.69882362 | 0.601927 | 25.55 | 16.82 | 0.00881872 | 48146.7 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 674.224 | 9580.55 | 30.70 | 0.01446650 | 22.54 | 0.05190911 | 8.6238 | 24.03 | 0.00828570 | 24.00 | 0.00828570 | 43.0191 | 13745.30 | 0.00 | 10591.48 | 8315.80 | 0.67122537 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.56 | 14.11 | 0.00985539 | 39543.1 | |
| SPLIT MS2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 10593.278 | 10593.278 | 0.601927 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.601927 | 0.69882362 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10593.28 | 10593.28 | 1.0000 | 0.69882362 | 0.601927 | 18.74 | 12.65 | 0.00695002 | 36450.9 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10593.28 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 8.6238 | 21.10 | 0.00738909 | 21.10 | 0.00738909 | 45.8186 | 3121.37 | 0.00 | 10607.20 | 10607.20 | 0.68647519 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.24 | 20.60 | 0.00875166 | 58895.8 | |
| SPLIT MS2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10593.278 | 10593.278 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.601927 | 0.69882362 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10593.28 | 10593.28 | 1.0000 | 0.69882362 | 0.601927 | 18.74 | 12.65 | 0.00695002 | 36450.9 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10593.28 | -6.30 | 0.00229779 | -6.30 | 0.05190911 | 8.6238 | 21.10 | 0.00738909 | 21.10 | 0.00738909 | 45.8186 | 3121.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7074.582 | 5664.256 | 0.419231 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8127 | 1004.8586 | 1.1610 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.419231 | 0.48671742 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6809.68 | 6207.71 | 0.9626 | 0.48671742 | 0.419231 | 25.41 | 16.59 | 0.00859232 | 47431.9 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 469.584 | 6340.10 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 6.1910 | 24.06 | 0.00820464 | 24.00 | 0.00820464 | 42.6036 | 4754.25 | 0.00 | 7073.38 | 5552.11 | 0.46749576 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.06 | 14.35 | 0.00990881 | 40192.0 | |
| SPLIT TSW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 7074.582 | 7074.582 | 0.419231 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.419231 | 0.48671742 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 7074.58 | 7074.58 | 1.0000 | 0.48671742 | 0.419231 | 19.40 | 13.17 | 0.00722385 | 37823.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7074.58 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 6.1910 | 21.10 | 0.00754895 | 21.10 | 0.00754895 | 46.7998 | 2327.21 | 0.00 | 7083.88 | 7083.88 | 0.47811698 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 35.62 | 20.42 | 0.00875166 | 58260.3 | |
| SPLIT TSW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7074.582 | 7074.582 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.419231 | 0.48671742 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 7074.58 | 7074.58 | 1.0000 | 0.48671742 | 0.419231 | 19.40 | 13.17 | 0.00722385 | 37823.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7074.58 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 6.1910 | 21.10 | 0.00754895 | 21.10 | 0.00754895 | 46.7998 | 2327.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6987.641 | 5590.156 | 0.414489 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7982 | 1004.8586 | 1.1610 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.414489 | 0.48121241 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6725.14 | 6137.91 | 0.9624 | 0.48121241 | 0.414489 | 25.42 | 16.58 | 0.00858452 | 47415.8 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 464.273 | 6260.86 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 6.2618 | 24.06 | 0.00819160 | 24.00 | 0.00819160 | 42.5366 | 4701.00 | 0.00 | 6986.45 | 5479.84 | 0.46220816 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.08 | 14.36 | 0.00990665 | 40207.0 | |
| SPLIT TNW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6987.641 | 6987.641 | 0.414489 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.414489 | 0.48121241 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 6987.64 | 6987.64 | 1.0000 | 0.48121241 | 0.414489 | 19.38 | 13.26 | 0.00732206 | 38053.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6987.64 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 6.2618 | 21.10 | 0.00765769 | 21.10 | 0.00765769 | 47.4647 | 2186.72 | 0.00 | 6996.82 | 6996.82 | 0.47270924 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 35.61 | 20.41 | 0.00875166 | 58245.6 | |
| SPLIT TNW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6987.641 | 6987.641 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.414489 | 0.48121241 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 6987.64 | 6987.64 | 1.0000 | 0.48121241 | 0.414489 | 19.38 | 13.26 | 0.00732206 | 38053.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6987.64 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 6.2618 | 21.10 | 0.00765769 | 21.10 | 0.00765769 | 47.4647 | 2186.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6355.246 | 5084.331 | 0.370727 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9696 | 1004.8586 | 1.1610 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.370727 | 0.43040582 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6130.15 | 5520.40 | 0.9646 | 0.43040582 | 0.370727 | 25.46 | 16.67 | 0.00867673 | 47695.0 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 415.255 | 5714.90 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 7.0010 | 24.05 | 0.00824087 | 24.00 | 0.00824087 | 42.7893 | 4213.81 | 0.00 | 6354.16 | 4984.02 | 0.41340804 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.88 | 14.26 | 0.00988522 | 39952.2 | |
| SPLIT TSE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6355.246 | 6355.246 | 0.370727 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.370727 | 0.43040582 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 6355.25 | 6355.25 | 1.0000 | 0.43040582 | 0.370727 | 19.18 | 13.04 | 0.00717994 | 37486.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6355.25 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 7.0010 | 21.10 | 0.00754747 | 21.10 | 0.00754747 | 46.7907 | 2318.94 | 0.00 | 6363.60 | 6363.60 | 0.42280041 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 35.85 | 20.49 | 0.00875166 | 58495.2 | |
| SPLIT TSE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6355.246 | 6355.246 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.370727 | 0.43040582 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 6355.25 | 6355.25 | 1.0000 | 0.43040582 | 0.370727 | 19.18 | 13.04 | 0.00717994 | 37486.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6355.25 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 7.0010 | 21.10 | 0.00754747 | 21.10 | 0.00754747 | 46.7907 | 2318.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6265.496 | 5015.313 | 0.365949 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9507 | 1004.8586 | 1.1610 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.365949 | 0.42485855 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6042.60 | 5449.87 | 0.9644 | 0.42485855 | 0.365949 | 25.47 | 16.67 | 0.00866656 | 47674.3 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 409.903 | 5632.70 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 7.0924 | 24.05 | 0.00822381 | 24.00 | 0.00822381 | 42.7017 | 4160.49 | 0.00 | 6264.43 | 4916.17 | 0.40807985 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.89 | 14.27 | 0.00988927 | 39971.4 | |
| SPLIT TNE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6265.496 | 6265.496 | 0.365949 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.365949 | 0.42485855 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 6265.50 | 6265.50 | 1.0000 | 0.42485855 | 0.365949 | 19.16 | 13.12 | 0.00727643 | 37705.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6265.50 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 7.0924 | 21.10 | 0.00765648 | 21.10 | 0.00765648 | 47.4573 | 2178.38 | 0.00 | 6273.73 | 6273.73 | 0.41735117 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 35.83 | 20.48 | 0.00875166 | 58476.4 | |
| SPLIT TNE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6265.496 | 6265.496 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.365949 | 0.42485855 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 6265.50 | 6265.50 | 1.0000 | 0.42485855 | 0.365949 | 19.16 | 13.12 | 0.00727643 | 37705.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6265.50 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 7.0924 | 21.10 | 0.00765648 | 21.10 | 0.00765648 | 47.4573 | 2178.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5801.539 | 4644.383 | 0.337972 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9573 | 1004.8586 | 1.1610 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.337972 | 0.39237730 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5597.20 | 5046.66 | 0.9648 | 0.39237730 | 0.337972 | 25.50 | 16.68 | 0.00867011 | 47719.4 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 378.565 | 5218.63 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 7.6795 | 24.05 | 0.00818795 | 24.00 | 0.00818795 | 42.5177 | 3849.98 | 0.00 | 5800.55 | 4552.52 | 0.37688136 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.86 | 14.25 | 0.00988631 | 39931.5 | |
| SPLIT TN1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 5801.539 | 5801.539 | 0.337972 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.337972 | 0.39237730 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 5801.54 | 5801.54 | 1.0000 | 0.39237730 | 0.337972 | 19.00 | 13.13 | 0.00735370 | 37738.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5801.54 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 7.6795 | 21.10 | 0.00777426 | 21.10 | 0.00777426 | 48.1770 | 1498.65 | 0.00 | 5809.16 | 5809.16 | 0.38544387 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 35.87 | 20.49 | 0.00875166 | 58515.5 | |
| SPLIT TN1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5801.539 | 5801.539 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.337972 | 0.39237730 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 5801.54 | 5801.54 | 1.0000 | 0.39237730 | 0.337972 | 19.00 | 13.13 | 0.00735370 | 37738.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5801.54 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 7.6795 | 21.10 | 0.00777426 | 21.10 | 0.00777426 | 48.1770 | 1498.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5781.043 | 4626.846 | 0.336592 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9627 | 1004.8586 | 1.1610 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.336592 | 0.39077580 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5577.84 | 5027.13 | 0.9648 | 0.39077580 | 0.336592 | 25.50 | 16.68 | 0.00867301 | 47728.8 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 377.020 | 5200.82 | 30.69 | 0.01446650 | 22.54 | 0.02595455 | 7.7110 | 24.05 | 0.00818895 | 24.00 | 0.00818895 | 42.5228 | 3834.69 | 0.00 | 5780.06 | 4535.41 | 0.37534311 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.86 | 14.25 | 0.00988452 | 39923.0 | |
| SPLIT TN2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 5781.043 | 5781.043 | 0.336592 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.336592 | 0.39077580 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 5781.04 | 5781.04 | 1.0000 | 0.39077580 | 0.336592 | 18.99 | 13.13 | 0.00735194 | 37725.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5781.04 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 7.7110 | 21.10 | 0.00777423 | 21.10 | 0.00777423 | 48.1768 | 1498.41 | 0.00 | 5788.64 | 5788.64 | 0.38387067 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 35.88 | 20.49 | 0.00875166 | 58523.8 | |
| SPLIT TN2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5781.043 | 5781.043 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.336592 | 0.39077580 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 5781.04 | 5781.04 | 1.0000 | 0.39077580 | 0.336592 | 18.99 | 13.13 | 0.00735194 | 37725.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5781.04 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 7.7110 | 21.10 | 0.00777423 | 21.10 | 0.00777423 | 48.1768 | 1498.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5906.454 | 4725.197 | 0.343562 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9811 | 1004.8586 | 1.1610 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.343562 | 0.39886735 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5699.54 | 5129.08 | 0.9650 | 0.39886735 | 0.343562 | 25.49 | 16.69 | 0.00868289 | 47744.6 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 384.826 | 5314.72 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 7.5545 | 24.05 | 0.00821026 | 24.00 | 0.00821026 | 42.6322 | 3912.08 | 0.00 | 5905.45 | 4631.95 | 0.38311511 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.85 | 14.24 | 0.00988137 | 39908.1 | |
| SPLIT TS1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 5906.454 | 5906.454 | 0.343562 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.343562 | 0.39886735 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 5906.45 | 5906.45 | 1.0000 | 0.39886735 | 0.343562 | 19.03 | 13.01 | 0.00720731 | 37401.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5906.45 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 7.5545 | 21.10 | 0.00760851 | 21.10 | 0.00760851 | 47.1633 | 1639.09 | 0.00 | 5914.22 | 5914.22 | 0.39181924 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 35.89 | 20.50 | 0.00875166 | 58538.3 | |
| SPLIT TS1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5906.454 | 5906.454 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.343562 | 0.39886735 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 5906.45 | 5906.45 | 1.0000 | 0.39886735 | 0.343562 | 19.03 | 13.01 | 0.00720731 | 37401.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5906.45 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 7.5545 | 21.10 | 0.00760851 | 21.10 | 0.00760851 | 47.1633 | 1639.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5886.109 | 4713.630 | 0.342185 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9867 | 1004.8586 | 1.1610 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.342185 | 0.39726900 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5680.34 | 5109.60 | 0.9650 | 0.39726900 | 0.342185 | 25.50 | 16.69 | 0.00868591 | 47754.2 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 383.284 | 5297.06 | 30.70 | 0.01446650 | 22.54 | 0.02595455 | 7.5849 | 24.05 | 0.00821147 | 24.00 | 0.00821147 | 42.6384 | 3896.81 | 0.00 | 5885.11 | 4620.27 | 0.38157988 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.83 | 14.24 | 0.00988503 | 39899.4 | |
| SPLIT TS2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 5886.109 | 5886.109 | 0.342185 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.342185 | 0.39726900 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 5886.11 | 5886.11 | 1.0000 | 0.39726900 | 0.342185 | 19.02 | 13.00 | 0.00720565 | 37388.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5886.11 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 7.5849 | 21.10 | 0.00760846 | 21.10 | 0.00760846 | 47.1630 | 1638.85 | 0.00 | 5893.84 | 5893.84 | 0.39024914 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 35.90 | 20.50 | 0.00875166 | 58546.9 | |
| SPLIT TS2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5886.109 | 5886.109 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.342185 | 0.39726900 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 5886.11 | 5886.11 | 1.0000 | 0.39726900 | 0.342185 | 19.02 | 13.00 | 0.00720565 | 37388.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5886.11 | -6.30 | 0.00229779 | -6.30 | 0.02595455 | 7.5849 | 21.10 | 0.00760846 | 21.10 | 0.00760846 | 47.1630 | 1638.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| G SW APARTMENT | 3354.33 | 2764.50 | 791.17 |
| G NW APARTMENT | 5028.17 | 4622.00 | 1724.67 |
| OFFICE | 1072.83 | 623.17 | 147.67 |
| G NE APARTMENT | 5054.50 | 4620.67 | 1718.67 |
| G N1 APARTMENT | 4798.00 | 4364.67 | 1441.83 |
| G N2 APARTMENT | 4800.17 | 4364.00 | 1441.50 |
| G S1 APARTMENT | 3238.00 | 2508.33 | 566.17 |
| G S2 APARTMENT | 3319.83 | 2492.50 | 593.17 |
| M SW APARTMENT | 3414.17 | 2470.17 | 591.17 |
| M NW APARTMENT | 5117.50 | 4165.50 | 1471.33 |
| M SE APARTMENT | 3388.67 | 2489.17 | 595.83 |
| M NE APARTMENT | 5160.83 | 4151.00 | 1486.00 |
| M N1 APARTMENT | 4779.17 | 3949.50 | 1219.33 |
| M N2 APARTMENT | 4780.00 | 3946.17 | 1217.83 |
| M S1 APARTMENT | 3276.17 | 2230.17 | 453.00 |
| M S2 APARTMENT | 3278.50 | 2230.83 | 452.67 |
| T SW APARTMENT | 3780.00 | 3289.00 | 1450.33 |
| T NW APARTMENT | 5731.17 | 5052.00 | 2568.83 |
| T SE APARTMENT | 3769.00 | 3309.67 | 1464.83 |
| T NE APARTMENT | 5739.83 | 5031.50 | 2565.33 |
| T N1 APARTMENT | 5477.50 | 4901.83 | 2288.67 |
| T N2 APARTMENT | 5481.00 | 4898.83 | 2287.50 |
| T S1 APARTMENT | 3545.83 | 3066.83 | 1116.50 |
| T S2 APARTMENT | 3548.33 | 3071.83 | 1122.50 |
| T CORRIDOR | 8603.17 | 8760.00 | 8603.17 |
| G CORRIDOR | 6233.17 | 6563.50 | 4496.00 |
| M CORRIDOR | 8760.00 | 8760.00 | 8760.00 |
| Facility | 8760.00 | 8760.00 | 8760.00 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 0.67 | 11.67 | 0.00 | 0.00 |
| G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.67 | 11.67 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.043 | 0.000 | 0.052 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.045 | 0.000 | 0.068 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.519 | 0.050 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.045 | 0.000 | 0.067 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.027 | 0.000 | 0.070 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.027 | 0.000 | 0.070 |
| G S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.026 | 0.000 | 0.053 |
| G S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.026 | 0.000 | 0.051 |
| M SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.061 | 0.000 | 0.055 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.064 | 0.000 | 0.079 |
| M SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.061 | 0.000 | 0.056 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.064 | 0.000 | 0.078 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.039 | 0.000 | 0.086 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.039 | 0.000 | 0.086 |
| M S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.355 | 0.037 | 0.000 | 0.058 |
| M S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.355 | 0.037 | 0.000 | 0.059 |
| T SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.081 | 0.000 | 0.063 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.085 | 0.000 | 0.088 |
| T SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.081 | 0.000 | 0.064 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.085 | 0.000 | 0.088 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.051 | 0.000 | 0.093 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.051 | 0.000 | 0.093 |
| T S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.049 | 0.000 | 0.066 |
| T S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.049 | 0.000 | 0.066 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.498 | 0.000 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| G S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
| G S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
| M SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| M SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| M S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
| M S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
| T SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| T SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| T S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
| T S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G NW APARTMENT | SPLIT GNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| OFFICE | SPLIT OFFICE | 4.75 | 4.75 | 268.97 | 88.25 | 0.0381 | 0.038 |
| G NE APARTMENT | SPLIT GNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N1 APARTMENT | SPLIT GN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N2 APARTMENT | SPLIT GN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S1 APARTMENT | SPLIT GS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S2 APARTMENT | SPLIT GS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| M SW APARTMENT | SPLIT MSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NW APARTMENT | SPLIT MNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M SE APARTMENT | SPLIT MSE | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NE APARTMENT | SPLIT MNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N1 APARTMENT | SPLIT MN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N2 APARTMENT | SPLIT MN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S1 APARTMENT | SPLIT MS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S2 APARTMENT | SPLIT MS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| T SW APARTMENT | SPLIT TSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NW APARTMENT | SPLIT TNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T SE APARTMENT | SPLIT TSE | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NE APARTMENT | SPLIT TNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N1 APARTMENT | SPLIT TN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N2 APARTMENT | SPLIT TN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S1 APARTMENT | SPLIT TS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S2 APARTMENT | SPLIT TS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| Total Facility | 68.21 | 82.25 | 8607.06 | 2823.98 | 0.8427 | 1.258 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| G SW APARTMENT | 818502.78 | 153684.68 | 972187.45 | 103869.49 | 1076056.95 | 818502.78 | 0.00 | 7239.06 | 1520.94 | 2615.00 |
| G NW APARTMENT | 818502.78 | 155693.39 | 974196.17 | 103869.49 | 1078065.66 | 818502.78 | 0.00 | 7146.69 | 1613.31 | 0.00 |
| OFFICE | 1153041.97 | 0.00 | 1153041.97 | 103869.49 | 1256911.46 | 1201711.97 | 500.00 | 8260.00 | 0.00 | 6935.42 |
| G NE APARTMENT | 818502.78 | 154025.76 | 972528.54 | 103869.49 | 1076398.03 | 818502.78 | 0.00 | 7177.87 | 1582.13 | 0.00 |
| G N1 APARTMENT | 818502.78 | 161494.15 | 979996.93 | 62651.44 | 1042648.37 | 818502.78 | 0.00 | 7101.99 | 1658.01 | 0.00 |
| G N2 APARTMENT | 818502.78 | 161323.16 | 979825.94 | 62651.44 | 1042477.38 | 818502.78 | 0.00 | 7104.59 | 1655.41 | 0.00 |
| G S1 APARTMENT | 818502.78 | 154231.85 | 972734.62 | 62651.44 | 1035386.07 | 818502.78 | 0.00 | 7247.04 | 1512.96 | 2615.00 |
| G S2 APARTMENT | 818502.78 | 148713.61 | 967216.38 | 62651.44 | 1029867.82 | 818502.78 | 0.00 | 7315.61 | 1444.39 | 2615.00 |
| M SW APARTMENT | 1637005.55 | 167868.87 | 1804874.42 | 149268.40 | 1954142.83 | 1637005.55 | 0.00 | 7353.82 | 1406.18 | 2615.00 |
| M NW APARTMENT | 1637005.55 | 181102.03 | 1818107.58 | 149268.40 | 1967375.98 | 1637005.55 | 0.00 | 7194.84 | 1565.16 | 0.00 |
| M SE APARTMENT | 1637005.55 | 163601.17 | 1800606.73 | 149268.40 | 1949875.13 | 1637005.55 | 0.00 | 7412.85 | 1347.15 | 2615.00 |
| M NE APARTMENT | 1637005.55 | 179311.77 | 1816317.32 | 149268.40 | 1965585.72 | 1637005.55 | 0.00 | 7233.90 | 1526.10 | 0.00 |
| M N1 APARTMENT | 1637005.55 | 196999.67 | 1834005.23 | 90034.91 | 1924040.14 | 1637005.55 | 0.00 | 7055.63 | 1704.37 | 0.00 |
| M N2 APARTMENT | 1637005.55 | 196871.27 | 1833876.82 | 90034.91 | 1923911.73 | 1637005.55 | 0.00 | 7057.88 | 1702.13 | 0.00 |
| M S1 APARTMENT | 1637005.55 | 173813.42 | 1810818.97 | 90034.91 | 1900853.89 | 1637005.55 | 0.00 | 7304.73 | 1455.27 | 2615.00 |
| M S2 APARTMENT | 1637005.55 | 173815.03 | 1810820.59 | 90034.91 | 1900855.50 | 1637005.55 | 0.00 | 7306.45 | 1453.55 | 2615.00 |
| T SW APARTMENT | 818502.78 | 194232.18 | 1012734.96 | 197451.26 | 1210186.22 | 818502.78 | 0.00 | 7343.49 | 1416.51 | 2615.00 |
| T NW APARTMENT | 818502.78 | 203387.80 | 1021890.58 | 197451.26 | 1219341.84 | 818502.78 | 0.00 | 7224.90 | 1535.10 | 0.00 |
| T SE APARTMENT | 818502.78 | 188531.74 | 1007034.51 | 197451.26 | 1204485.78 | 818502.78 | 0.00 | 7407.84 | 1352.16 | 2615.00 |
| T NE APARTMENT | 818502.78 | 202410.59 | 1020913.37 | 197451.26 | 1218364.63 | 818502.78 | 0.00 | 7254.40 | 1505.60 | 0.00 |
| T N1 APARTMENT | 818502.78 | 214156.06 | 1032658.84 | 119097.59 | 1151756.43 | 818502.78 | 0.00 | 7148.54 | 1611.46 | 0.00 |
| T N2 APARTMENT | 818502.78 | 214176.16 | 1032678.94 | 119097.59 | 1151776.53 | 818502.78 | 0.00 | 7149.78 | 1610.22 | 0.00 |
| T S1 APARTMENT | 818502.78 | 199036.93 | 1017539.71 | 119097.59 | 1136637.30 | 818502.78 | 0.00 | 7319.95 | 1440.05 | 2615.00 |
| T S2 APARTMENT | 818502.78 | 198781.25 | 1017284.03 | 119097.59 | 1136381.62 | 818502.78 | 0.00 | 7322.82 | 1437.18 | 2615.00 |
| Total Facility | 39622672.50 | 5570645.77 | 45193318.27 | 3846705.65 | 49040023.93 | 39671342.50 | 500.00 | 8676.72 | 1851.58 | 8760.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| G SW APARTMENT | 0.0260 | 0.0038 | 0.0298 | 0.0031 | 0.0329 | 0.0260 | 0.00 | 5276.46 | 868.54 |
| G NW APARTMENT | 0.0260 | 0.0049 | 0.0309 | 0.0033 | 0.0342 | 0.0260 | 0.00 | 7146.69 | 1613.31 |
| OFFICE | 0.0381 | 0.0000 | 0.0381 | 0.0037 | 0.0418 | 0.0381 | 0.00 | 1750.00 | 0.00 |
| G NE APARTMENT | 0.0260 | 0.0049 | 0.0308 | 0.0033 | 0.0341 | 0.0260 | 0.00 | 7177.87 | 1582.13 |
| G N1 APARTMENT | 0.0260 | 0.0051 | 0.0311 | 0.0020 | 0.0331 | 0.0260 | 0.00 | 7101.99 | 1658.01 |
| G N2 APARTMENT | 0.0260 | 0.0051 | 0.0311 | 0.0020 | 0.0331 | 0.0260 | 0.00 | 7104.59 | 1655.41 |
| G S1 APARTMENT | 0.0260 | 0.0039 | 0.0298 | 0.0019 | 0.0317 | 0.0260 | 0.00 | 5268.45 | 876.55 |
| G S2 APARTMENT | 0.0260 | 0.0037 | 0.0297 | 0.0019 | 0.0316 | 0.0260 | 0.00 | 5310.18 | 834.82 |
| M SW APARTMENT | 0.0519 | 0.0040 | 0.0559 | 0.0045 | 0.0604 | 0.0519 | 0.00 | 5353.21 | 791.79 |
| M NW APARTMENT | 0.0519 | 0.0057 | 0.0577 | 0.0047 | 0.0624 | 0.0519 | 0.00 | 7194.84 | 1565.16 |
| M SE APARTMENT | 0.0519 | 0.0041 | 0.0560 | 0.0045 | 0.0605 | 0.0519 | 0.00 | 5343.98 | 801.02 |
| M NE APARTMENT | 0.0519 | 0.0057 | 0.0576 | 0.0047 | 0.0623 | 0.0519 | 0.00 | 7233.90 | 1526.10 |
| M N1 APARTMENT | 0.0519 | 0.0062 | 0.0582 | 0.0029 | 0.0610 | 0.0519 | 0.00 | 7055.63 | 1704.37 |
| M N2 APARTMENT | 0.0519 | 0.0062 | 0.0582 | 0.0029 | 0.0610 | 0.0519 | 0.00 | 7057.88 | 1702.13 |
| M S1 APARTMENT | 0.0519 | 0.0042 | 0.0562 | 0.0027 | 0.0589 | 0.0519 | 0.00 | 5308.57 | 836.43 |
| M S2 APARTMENT | 0.0519 | 0.0043 | 0.0562 | 0.0027 | 0.0589 | 0.0519 | 0.00 | 5306.95 | 838.05 |
| T SW APARTMENT | 0.0260 | 0.0046 | 0.0305 | 0.0059 | 0.0365 | 0.0260 | 0.00 | 5352.63 | 792.37 |
| T NW APARTMENT | 0.0260 | 0.0064 | 0.0324 | 0.0063 | 0.0387 | 0.0260 | 0.00 | 7224.90 | 1535.10 |
| T SE APARTMENT | 0.0260 | 0.0047 | 0.0306 | 0.0059 | 0.0366 | 0.0260 | 0.00 | 5346.97 | 798.03 |
| T NE APARTMENT | 0.0260 | 0.0064 | 0.0324 | 0.0063 | 0.0386 | 0.0260 | 0.00 | 7254.40 | 1505.60 |
| T N1 APARTMENT | 0.0260 | 0.0068 | 0.0327 | 0.0038 | 0.0365 | 0.0260 | 0.00 | 7148.54 | 1611.46 |
| T N2 APARTMENT | 0.0260 | 0.0068 | 0.0327 | 0.0038 | 0.0365 | 0.0260 | 0.00 | 7149.78 | 1610.22 |
| T S1 APARTMENT | 0.0260 | 0.0048 | 0.0307 | 0.0036 | 0.0343 | 0.0260 | 0.00 | 5323.19 | 821.81 |
| T S2 APARTMENT | 0.0260 | 0.0048 | 0.0308 | 0.0036 | 0.0343 | 0.0260 | 0.00 | 5321.32 | 823.68 |
| Total Facility | 1.2580 | 0.1579 | 1.4158 | 0.1193 | 1.5352 | 1.2580 | 500.00 | 8676.69 | 1851.58 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| SPLIT GSW | 0.00 | 153684.68 | 153684.68 | 818502.78 | 7776.00 | 42.19 | 941.82 | 652.40 |
| SPLIT GNW | 0.00 | 155693.39 | 155693.39 | 818502.78 | 7841.75 | 50.81 | 867.44 | 0.00 |
| SPLIT OFFICE | 1554146.68 | 0.00 | 1554146.68 | 1201711.97 | 499.17 | 0.50 | 8260.33 | 6930.33 |
| SPLIT GNE | 0.00 | 154025.76 | 154025.76 | 818502.78 | 7825.28 | 52.02 | 882.70 | 0.00 |
| SPLIT GN1 | 0.00 | 161494.15 | 161494.15 | 818502.78 | 7784.43 | 52.75 | 922.81 | 0.00 |
| SPLIT GN2 | 0.00 | 161323.16 | 161323.16 | 818502.78 | 7784.45 | 51.96 | 923.59 | 0.00 |
| SPLIT GS1 | 0.00 | 154231.85 | 154231.85 | 818502.78 | 7768.71 | 38.51 | 952.78 | 636.41 |
| SPLIT GS2 | 0.00 | 148713.61 | 148713.61 | 818502.78 | 7782.42 | 36.13 | 941.45 | 609.57 |
| SPLIT MSW | 0.00 | 167868.87 | 167868.87 | 1637005.55 | 8709.14 | 7.79 | 43.07 | 614.39 |
| SPLIT MNW | 0.00 | 181102.03 | 181102.03 | 1637005.55 | 8722.89 | 5.50 | 31.61 | 0.00 |
| SPLIT MSE | 0.00 | 163601.17 | 163601.17 | 1637005.55 | 8709.97 | 7.18 | 42.85 | 546.13 |
| SPLIT MNE | 0.00 | 179311.77 | 179311.77 | 1637005.55 | 8722.53 | 5.58 | 31.89 | 0.00 |
| SPLIT MN1 | 0.00 | 196999.67 | 196999.67 | 1637005.55 | 8720.64 | 6.16 | 33.19 | 0.00 |
| SPLIT MN2 | 0.00 | 196871.27 | 196871.27 | 1637005.55 | 8720.64 | 5.99 | 33.36 | 0.00 |
| SPLIT MS1 | 0.00 | 173813.42 | 173813.42 | 1637005.55 | 8707.79 | 7.64 | 44.57 | 618.83 |
| SPLIT MS2 | 0.00 | 173815.03 | 173815.03 | 1637005.55 | 8707.79 | 7.64 | 44.57 | 615.49 |
| SPLIT TSW | 0.00 | 194232.18 | 194232.18 | 818502.78 | 7543.56 | 17.16 | 1199.28 | 624.15 |
| SPLIT TNW | 0.00 | 203387.80 | 203387.80 | 818502.78 | 7471.31 | 19.37 | 1269.32 | 0.00 |
| SPLIT TSE | 0.00 | 188531.74 | 188531.74 | 818502.78 | 7578.44 | 13.21 | 1168.35 | 554.13 |
| SPLIT TNE | 0.00 | 202410.59 | 202410.59 | 818502.78 | 7468.21 | 16.21 | 1275.58 | 0.00 |
| SPLIT TN1 | 0.00 | 214156.06 | 214156.06 | 818502.78 | 7402.49 | 21.55 | 1335.96 | 0.00 |
| SPLIT TN2 | 0.00 | 214176.16 | 214176.16 | 818502.78 | 7401.52 | 21.94 | 1336.53 | 0.00 |
| SPLIT TS1 | 0.00 | 199036.93 | 199036.93 | 818502.78 | 7516.24 | 14.97 | 1228.79 | 618.24 |
| SPLIT TS2 | 0.00 | 198781.25 | 198781.25 | 818502.78 | 7517.00 | 14.80 | 1228.20 | 613.50 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| SPLIT GSW | 0.0000 | 0.0038 | 0.0038 | 0.0260 | 5632.21 | 27.25 | 485.53 |
| SPLIT GNW | 0.0000 | 0.0049 | 0.0049 | 0.0260 | 7841.75 | 50.81 | 867.44 |
| SPLIT OFFICE | 0.0514 | 0.0000 | 0.0514 | 0.0381 | 0.00 | 0.00 | 1750.00 |
| SPLIT GNE | 0.0000 | 0.0049 | 0.0049 | 0.0260 | 7825.28 | 52.02 | 882.70 |
| SPLIT GN1 | 0.0000 | 0.0051 | 0.0051 | 0.0260 | 7784.43 | 52.75 | 922.81 |
| SPLIT GN2 | 0.0000 | 0.0051 | 0.0051 | 0.0260 | 7784.45 | 51.96 | 923.59 |
| SPLIT GS1 | 0.0000 | 0.0039 | 0.0039 | 0.0260 | 5624.32 | 25.51 | 495.16 |
| SPLIT GS2 | 0.0000 | 0.0037 | 0.0037 | 0.0260 | 5629.17 | 24.05 | 491.78 |
| SPLIT MSW | 0.0000 | 0.0040 | 0.0040 | 0.0519 | 6131.54 | 2.83 | 10.62 |
| SPLIT MNW | 0.0000 | 0.0057 | 0.0057 | 0.0519 | 8722.89 | 5.50 | 31.61 |
| SPLIT MSE | 0.0000 | 0.0041 | 0.0041 | 0.0519 | 6131.60 | 2.61 | 10.79 |
| SPLIT MNE | 0.0000 | 0.0057 | 0.0057 | 0.0519 | 8722.53 | 5.58 | 31.89 |
| SPLIT MN1 | 0.0000 | 0.0062 | 0.0062 | 0.0519 | 8720.64 | 6.16 | 33.19 |
| SPLIT MN2 | 0.0000 | 0.0062 | 0.0062 | 0.0519 | 8720.64 | 5.99 | 33.36 |
| SPLIT MS1 | 0.0000 | 0.0042 | 0.0042 | 0.0519 | 6130.83 | 2.71 | 11.46 |
| SPLIT MS2 | 0.0000 | 0.0043 | 0.0043 | 0.0519 | 6130.83 | 2.71 | 11.46 |
| SPLIT TSW | 0.0000 | 0.0046 | 0.0046 | 0.0260 | 5497.96 | 11.54 | 635.50 |
| SPLIT TNW | 0.0000 | 0.0064 | 0.0064 | 0.0260 | 7471.31 | 19.37 | 1269.32 |
| SPLIT TSE | 0.0000 | 0.0047 | 0.0047 | 0.0260 | 5483.93 | 10.11 | 650.97 |
| SPLIT TNE | 0.0000 | 0.0064 | 0.0064 | 0.0260 | 7468.21 | 16.21 | 1275.58 |
| SPLIT TN1 | 0.0000 | 0.0068 | 0.0068 | 0.0260 | 7402.49 | 21.55 | 1335.96 |
| SPLIT TN2 | 0.0000 | 0.0068 | 0.0068 | 0.0260 | 7401.52 | 21.94 | 1336.53 |
| SPLIT TS1 | 0.0000 | 0.0048 | 0.0048 | 0.0260 | 5468.28 | 11.27 | 665.44 |
| SPLIT TS2 | 0.0000 | 0.0048 | 0.0048 | 0.0260 | 5465.74 | 11.27 | 667.98 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| SPLIT GSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT OFFICE | 8680.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| SPLIT GSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT OFFICE | 0.0514 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Surfaces by Class| Total | Outdoors | |
| Wall | 126 | 42 |
| Floor | 27 | 9 |
| Roof | 27 | 9 |
| Internal Mass | 24 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 39 | 39 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 24 |
| Conditioned Zones | 24 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1588 |
| Defaulted Fields | 1666 |
| Fields with Defaults | 5801 |
| Autosized Fields | 648 |
| Autosizable Fields | 770 |
| Autocalculated Fields | 332 |
| Autocalculatable Fields | 509 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 838.98 | 14104.84 | 20-JAN-03:10 | 66247.06 | 12-FEB-07:10 |
| Electricity:Building | 527.01 | 10157.12 | 01-JAN-03:10 | 25266.90 | 03-JAN-17:10 |
| Electricity:Zone:G SW APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 527.01 | 10157.12 | 01-JAN-03:10 | 25266.90 | 03-JAN-17:10 |
| InteriorLights:Electricity | 73.00 | 1491.31 | 01-JAN-00:10 | 4040.47 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:G SW APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 73.00 | 1491.31 | 01-JAN-00:10 | 4040.47 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 67.97 | 1461.31 | 01-JAN-00:10 | 3560.62 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 67.97 | 1461.31 | 01-JAN-00:10 | 3560.62 | 01-JAN-19:10 |
| Electricity:Zone:G NW APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NW APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:OFFICE | 13.20 | 218.21 | 01-JAN-00:10 | 992.54 | 03-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICE | 5.68 | 89.52 | 01-JAN-00:10 | 447.62 | 03-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICE | 5.68 | 89.52 | 01-JAN-00:10 | 447.62 | 03-JAN-08:10 |
| Electricity:Zone:G NE APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NE APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:G N1 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:G N2 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:G S1 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:G S2 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:M SW APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SW APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SW APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M NW APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NW APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NW APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M SE APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SE APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SE APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M NE APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NE APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NE APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M N1 APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M N2 APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M S1 APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M S2 APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:T SW APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SW APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T NW APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NW APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T SE APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SE APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T NE APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NE APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T N1 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T N2 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T S1 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T S2 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:G CORRIDOR | 77.61 | 1911.10 | 01-JAN-00:10 | 4111.81 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:G CORRIDOR | 9.71 | 307.95 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:G CORRIDOR | 9.71 | 307.95 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 |
| Electricity:Zone:M CORRIDOR | 19.42 | 615.89 | 01-JAN-00:10 | 615.89 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:M CORRIDOR | 19.42 | 615.89 | 01-JAN-00:10 | 615.89 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:M CORRIDOR | 19.42 | 615.89 | 01-JAN-00:10 | 615.89 | 01-JAN-00:10 |
| Electricity:Zone:T CORRIDOR | 9.71 | 307.95 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:T CORRIDOR | 9.71 | 307.95 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:T CORRIDOR | 9.71 | 307.95 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 |
| LightsPlugIn:InteriorLights:Electricity | 5.02 | 30.00 | 01-JAN-00:10 | 479.85 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:SpaceType:GENERAL | 5.02 | 30.00 | 01-JAN-00:10 | 479.85 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SW APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NW APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SE APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NE APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N1 APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N2 APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S1 APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S2 APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 454.01 | 8665.81 | 01-JAN-03:10 | 22246.15 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G CORRIDOR | 67.90 | 1603.15 | 01-JAN-00:10 | 3803.87 | 01-JAN-07:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 454.01 | 8665.81 | 01-JAN-03:10 | 22246.15 | 03-JAN-17:10 |
| ElevatorLift:InteriorEquipment:Electricity | 67.41 | 1600.00 | 01-JAN-00:10 | 3772.37 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:G CORRIDOR | 67.41 | 1600.00 | 01-JAN-00:10 | 3772.37 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 67.41 | 1600.00 | 01-JAN-00:10 | 3772.37 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 0.49 | 3.15 | 01-JAN-00:10 | 31.50 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:G CORRIDOR | 0.49 | 3.15 | 01-JAN-00:10 | 31.50 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.49 | 3.15 | 01-JAN-00:10 | 31.50 | 01-JAN-07:10 |
| InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity | 386.12 | 7062.66 | 01-JAN-03:10 | 18442.28 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 386.12 | 7062.66 | 01-JAN-03:10 | 18442.28 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:OFFICE | 7.52 | 128.69 | 01-JAN-00:10 | 544.92 | 03-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICE | 7.52 | 128.69 | 01-JAN-00:10 | 544.92 | 03-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| Fans:Electricity | 102.87 | 1436.61 | 19-JAN-12:10 | 13031.43 | 12-FEB-06:00 |
| Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 838.98 | 14104.84 | 20-JAN-03:10 | 66247.06 | 12-FEB-07:10 |
| ElectricityPurchased:Plant | 838.98 | 14104.84 | 20-JAN-03:10 | 66247.06 | 12-FEB-07:10 |
| Cogeneration:ElectricityPurchased | 838.98 | 14104.84 | 20-JAN-03:10 | 66247.06 | 12-FEB-07:10 |
| General:Cogeneration:ElectricityPurchased | 838.98 | 14104.84 | 20-JAN-03:10 | 66247.06 | 12-FEB-07:10 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 838.98 | 14104.84 | 20-JAN-03:10 | 66247.06 | 12-FEB-07:10 |
| ElectricityNet:Plant | 838.98 | 14104.84 | 20-JAN-03:10 | 66247.06 | 12-FEB-07:10 |
| Cogeneration:ElectricityNet | 838.98 | 14104.84 | 20-JAN-03:10 | 66247.06 | 12-FEB-07:10 |
| General:Cogeneration:ElectricityNet | 838.98 | 14104.84 | 20-JAN-03:10 | 66247.06 | 12-FEB-07:10 |
| Electricity:HVAC | 278.48 | 1436.61 | 19-JAN-12:10 | 48328.02 | 12-FEB-06:00 |
| HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Fans:Electricity | 102.87 | 1436.61 | 19-JAN-12:10 | 13031.43 | 12-FEB-06:00 |
| Cooling:Electricity | 152.39 | 0.00 | 01-JAN-00:10 | 27145.80 | 29-AUG-08:40 |
| General:Cooling:Electricity | 152.39 | 0.00 | 01-JAN-00:10 | 27145.80 | 29-AUG-08:40 |
| Heating:Electricity | 23.22 | 0.00 | 01-JAN-11:30 | 35296.60 | 12-FEB-06:00 |
| General:Heating:Electricity | 23.22 | 0.00 | 01-JAN-11:30 | 35296.60 | 12-FEB-06:00 |
| ExteriorLights:Electricity | 33.04 | 0.00 | 01-JAN-07:50 | 2101.03 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 33.04 | 0.00 | 01-JAN-07:50 | 2101.03 | 01-JAN-00:10 |
| Electricity:Plant | 0.46 | 14.49 | 01-JAN-00:10 | 14.49 | 01-JAN-17:10 |
| Pumps:Electricity | 0.46 | 14.49 | 01-JAN-00:10 | 14.49 | 01-JAN-17:10 |
| General:Pumps:Electricity | 0.46 | 14.49 | 01-JAN-00:10 | 14.49 | 01-JAN-17:10 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 406.16 | 0.00 | 02-JAN-03:40 | 28641.30 | 03-FEB-08:00 |
| NaturalGas:Plant | 406.16 | 0.00 | 02-JAN-03:40 | 28641.30 | 03-FEB-08:00 |
| WaterSystems:NaturalGas | 406.16 | 0.00 | 02-JAN-03:40 | 28641.30 | 03-FEB-08:00 |
| Water Heater:WaterSystems:NaturalGas | 406.16 | 0.00 | 02-JAN-03:40 | 28641.30 | 03-FEB-08:00 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water:Plant | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:Water | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterUse:WaterSystems:Water | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Facility | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Plant | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:MainsWater | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterUse:WaterSystems:MainsWater | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 1670.53 | 6650.50 | 20-JAN-00:10 | 195752.21 | 29-AUG-08:40 |
| EnergyTransfer:Building | 512.60 | 152.96 | 07-AUG-05:50 | 70895.56 | 13-SEP-13:50 |
| EnergyTransfer:Zone:G SW APARTMENT | 15.25 | 0.02 | 17-JAN-07:20 | 2565.26 | 22-OCT-16:10 |
| Heating:EnergyTransfer | 38.99 | 0.00 | 01-JAN-15:30 | 35465.79 | 12-FEB-06:00 |
| Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.63 | 0.00 | 01-JAN-00:30 | 1110.48 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer | 38.99 | 0.00 | 01-JAN-15:30 | 35465.79 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.63 | 0.00 | 01-JAN-00:30 | 1110.48 | 12-FEB-06:00 |
| Cooling:EnergyTransfer | 473.61 | 0.00 | 09-JAN-07:10 | 70734.34 | 13-SEP-13:50 |
| Cooling:EnergyTransfer:Zone:G SW APARTMENT | 14.62 | 0.00 | 01-JAN-00:10 | 2565.26 | 22-OCT-16:10 |
| General:Cooling:EnergyTransfer | 473.61 | 0.00 | 09-JAN-07:10 | 70734.34 | 13-SEP-13:50 |
| General:Cooling:EnergyTransfer:Zone:G SW APARTMENT | 14.62 | 0.00 | 01-JAN-00:10 | 2565.26 | 22-OCT-16:10 |
| EnergyTransfer:Zone:G NW APARTMENT | 13.51 | 0.01 | 28-MAR-13:10 | 2050.96 | 07-JUN-18:30 |
| Heating:EnergyTransfer:Zone:G NW APARTMENT | 1.58 | 0.00 | 01-JAN-03:40 | 1252.30 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:G NW APARTMENT | 1.58 | 0.00 | 01-JAN-03:40 | 1252.30 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:G NW APARTMENT | 11.93 | 0.00 | 01-JAN-00:10 | 2047.86 | 07-JUN-18:30 |
| General:Cooling:EnergyTransfer:Zone:G NW APARTMENT | 11.93 | 0.00 | 01-JAN-00:10 | 2047.86 | 07-JUN-18:30 |
| EnergyTransfer:Zone:OFFICE | 16.56 | 0.00 | 04-JAN-12:10 | 5091.24 | 13-FEB-07:10 |
| Heating:EnergyTransfer:Zone:OFFICE | 2.78 | 0.00 | 01-JAN-00:10 | 5086.95 | 13-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:OFFICE | 2.78 | 0.00 | 01-JAN-00:10 | 5086.95 | 13-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:OFFICE | 13.78 | 0.00 | 01-JAN-01:00 | 3534.12 | 14-AUG-06:20 |
| General:Cooling:EnergyTransfer:Zone:OFFICE | 13.78 | 0.00 | 01-JAN-01:00 | 3534.12 | 14-AUG-06:20 |
| EnergyTransfer:Zone:G NE APARTMENT | 13.57 | 0.00 | 29-AUG-07:50 | 1930.94 | 25-JUL-09:40 |
| Heating:EnergyTransfer:Zone:G NE APARTMENT | 1.55 | 0.00 | 01-JAN-02:00 | 1267.34 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:G NE APARTMENT | 1.55 | 0.00 | 01-JAN-02:00 | 1267.34 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:G NE APARTMENT | 12.02 | 0.00 | 01-JAN-00:10 | 1927.88 | 04-JUN-09:20 |
| General:Cooling:EnergyTransfer:Zone:G NE APARTMENT | 12.02 | 0.00 | 01-JAN-00:10 | 1927.88 | 04-JUN-09:20 |
| EnergyTransfer:Zone:G N1 APARTMENT | 11.72 | 0.01 | 23-JUN-07:50 | 1857.50 | 08-AUG-18:00 |
| Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.51 | 0.00 | 01-JAN-00:10 | 633.73 | 12-FEB-08:20 |
| General:Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.51 | 0.00 | 01-JAN-00:10 | 633.73 | 12-FEB-08:20 |
| Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 11.21 | 0.00 | 04-JAN-00:50 | 1848.19 | 08-AUG-18:00 |
| General:Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 11.21 | 0.00 | 04-JAN-00:50 | 1848.19 | 08-AUG-18:00 |
| EnergyTransfer:Zone:G N2 APARTMENT | 11.73 | 0.01 | 12-MAY-18:10 | 1857.28 | 08-AUG-18:00 |
| Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.51 | 0.00 | 01-JAN-00:10 | 633.70 | 12-FEB-08:20 |
| General:Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.51 | 0.00 | 01-JAN-00:10 | 633.70 | 12-FEB-08:20 |
| Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 11.22 | 0.00 | 04-JAN-00:50 | 1847.96 | 08-AUG-18:00 |
| General:Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 11.22 | 0.00 | 04-JAN-00:50 | 1847.96 | 08-AUG-18:00 |
| EnergyTransfer:Zone:G S1 APARTMENT | 14.70 | 0.01 | 02-JUN-08:40 | 2242.78 | 15-OCT-16:10 |
| Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.09 | 0.00 | 01-JAN-00:10 | 458.49 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.09 | 0.00 | 01-JAN-00:10 | 458.49 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 14.61 | 0.00 | 05-JAN-03:20 | 2238.28 | 15-OCT-16:10 |
| General:Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 14.61 | 0.00 | 05-JAN-03:20 | 2238.28 | 15-OCT-16:10 |
| EnergyTransfer:Zone:G S2 APARTMENT | 15.51 | 0.00 | 27-JUN-08:00 | 2291.40 | 15-OCT-16:10 |
| Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.15 | 0.00 | 01-JAN-00:10 | 565.00 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.15 | 0.00 | 01-JAN-00:10 | 565.00 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 15.36 | 0.00 | 04-JAN-01:10 | 2291.40 | 15-OCT-16:10 |
| General:Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 15.36 | 0.00 | 04-JAN-01:10 | 2291.40 | 15-OCT-16:10 |
| EnergyTransfer:Zone:M SW APARTMENT | 36.86 | 0.00 | 02-SEP-14:20 | 6287.42 | 22-OCT-16:10 |
| Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.62 | 0.00 | 01-JAN-00:10 | 2141.01 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.62 | 0.00 | 01-JAN-00:10 | 2141.01 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:M SW APARTMENT | 36.24 | 0.00 | 03-JAN-09:10 | 6287.42 | 22-OCT-16:10 |
| General:Cooling:EnergyTransfer:Zone:M SW APARTMENT | 36.24 | 0.00 | 03-JAN-09:10 | 6287.42 | 22-OCT-16:10 |
| EnergyTransfer:Zone:M NW APARTMENT | 31.48 | 0.05 | 15-MAY-09:50 | 5265.70 | 07-JUN-18:30 |
| Heating:EnergyTransfer:Zone:M NW APARTMENT | 2.18 | 0.00 | 01-JAN-00:10 | 2464.14 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:M NW APARTMENT | 2.18 | 0.00 | 01-JAN-00:10 | 2464.14 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:M NW APARTMENT | 29.30 | 0.00 | 03-JAN-00:50 | 5260.03 | 07-JUN-18:30 |
| General:Cooling:EnergyTransfer:Zone:M NW APARTMENT | 29.30 | 0.00 | 03-JAN-00:50 | 5260.03 | 07-JUN-18:30 |
| EnergyTransfer:Zone:M SE APARTMENT | 37.08 | 0.00 | 14-AUG-06:50 | 5620.53 | 09-OCT-13:00 |
| Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.62 | 0.00 | 01-JAN-00:10 | 2169.95 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.62 | 0.00 | 01-JAN-00:10 | 2169.95 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:M SE APARTMENT | 36.46 | 0.00 | 03-JAN-09:10 | 5620.53 | 09-OCT-13:00 |
| General:Cooling:EnergyTransfer:Zone:M SE APARTMENT | 36.46 | 0.00 | 03-JAN-09:10 | 5620.53 | 09-OCT-13:00 |
| EnergyTransfer:Zone:M NE APARTMENT | 31.52 | 0.00 | 26-DEC-21:30 | 4599.40 | 11-JUN-10:10 |
| Heating:EnergyTransfer:Zone:M NE APARTMENT | 2.10 | 0.00 | 01-JAN-00:10 | 2501.97 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:M NE APARTMENT | 2.10 | 0.00 | 01-JAN-00:10 | 2501.97 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:M NE APARTMENT | 29.42 | 0.00 | 03-JAN-00:40 | 4584.77 | 11-JUN-10:10 |
| General:Cooling:EnergyTransfer:Zone:M NE APARTMENT | 29.42 | 0.00 | 03-JAN-00:40 | 4584.77 | 11-JUN-10:10 |
| EnergyTransfer:Zone:M N1 APARTMENT | 27.07 | 0.00 | 12-DEC-13:20 | 3840.74 | 08-AUG-18:00 |
| Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.40 | 0.00 | 01-JAN-00:10 | 1053.35 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.40 | 0.00 | 01-JAN-00:10 | 1053.35 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 26.67 | 0.00 | 05-JAN-01:30 | 3840.74 | 08-AUG-18:00 |
| General:Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 26.67 | 0.00 | 05-JAN-01:30 | 3840.74 | 08-AUG-18:00 |
| EnergyTransfer:Zone:M N2 APARTMENT | 27.10 | 0.00 | 12-DEC-13:20 | 3839.62 | 08-AUG-18:00 |
| Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.40 | 0.00 | 01-JAN-00:10 | 1055.48 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.40 | 0.00 | 01-JAN-00:10 | 1055.48 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 26.70 | 0.00 | 05-JAN-01:40 | 3839.62 | 08-AUG-18:00 |
| General:Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 26.70 | 0.00 | 05-JAN-01:40 | 3839.62 | 08-AUG-18:00 |
| EnergyTransfer:Zone:M S1 APARTMENT | 34.83 | 0.04 | 21-JUN-07:50 | 5339.52 | 22-OCT-15:10 |
| Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.06 | 0.00 | 01-JAN-00:10 | 604.37 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.06 | 0.00 | 01-JAN-00:10 | 604.37 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 34.77 | 0.00 | 07-JAN-02:20 | 5339.52 | 22-OCT-15:10 |
| General:Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 34.77 | 0.00 | 07-JAN-02:20 | 5339.52 | 22-OCT-15:10 |
| EnergyTransfer:Zone:M S2 APARTMENT | 34.87 | 0.03 | 30-JUN-07:50 | 5336.54 | 22-OCT-15:10 |
| Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.06 | 0.00 | 01-JAN-00:10 | 606.49 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.06 | 0.00 | 01-JAN-00:10 | 606.49 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 34.81 | 0.00 | 07-JAN-02:20 | 5336.54 | 22-OCT-15:10 |
| General:Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 34.81 | 0.00 | 07-JAN-02:20 | 5336.54 | 22-OCT-15:10 |
| EnergyTransfer:Zone:T SW APARTMENT | 19.84 | 0.03 | 17-APR-10:20 | 3986.99 | 22-OCT-16:10 |
| Heating:EnergyTransfer:Zone:T SW APARTMENT | 3.25 | 0.00 | 01-JAN-10:30 | 2520.13 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T SW APARTMENT | 3.25 | 0.00 | 01-JAN-10:30 | 2520.13 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T SW APARTMENT | 16.59 | 0.00 | 01-JAN-00:10 | 3986.99 | 22-OCT-16:10 |
| General:Cooling:EnergyTransfer:Zone:T SW APARTMENT | 16.59 | 0.00 | 01-JAN-00:10 | 3986.99 | 22-OCT-16:10 |
| EnergyTransfer:Zone:T NW APARTMENT | 19.03 | 0.00 | 02-AUG-06:50 | 3412.79 | 07-JUN-18:30 |
| Heating:EnergyTransfer:Zone:T NW APARTMENT | 5.04 | 0.00 | 01-JAN-11:10 | 2595.70 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T NW APARTMENT | 5.04 | 0.00 | 01-JAN-11:10 | 2595.70 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T NW APARTMENT | 13.98 | 0.00 | 01-JAN-00:10 | 3412.79 | 07-JUN-18:30 |
| General:Cooling:EnergyTransfer:Zone:T NW APARTMENT | 13.98 | 0.00 | 01-JAN-00:10 | 3412.79 | 07-JUN-18:30 |
| EnergyTransfer:Zone:T SE APARTMENT | 19.76 | 0.00 | 06-JUL-06:40 | 3476.70 | 09-OCT-13:00 |
| Heating:EnergyTransfer:Zone:T SE APARTMENT | 3.19 | 0.00 | 01-JAN-10:10 | 2525.08 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T SE APARTMENT | 3.19 | 0.00 | 01-JAN-10:10 | 2525.08 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T SE APARTMENT | 16.57 | 0.00 | 01-JAN-00:10 | 3476.70 | 09-OCT-13:00 |
| General:Cooling:EnergyTransfer:Zone:T SE APARTMENT | 16.57 | 0.00 | 01-JAN-00:10 | 3476.70 | 09-OCT-13:00 |
| EnergyTransfer:Zone:T NE APARTMENT | 18.89 | 0.01 | 14-DEC-07:50 | 3004.89 | 07-JUN-15:40 |
| Heating:EnergyTransfer:Zone:T NE APARTMENT | 4.92 | 0.00 | 01-JAN-11:10 | 2598.70 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T NE APARTMENT | 4.92 | 0.00 | 01-JAN-11:10 | 2598.70 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T NE APARTMENT | 13.97 | 0.00 | 01-JAN-00:10 | 3004.89 | 07-JUN-15:40 |
| General:Cooling:EnergyTransfer:Zone:T NE APARTMENT | 13.97 | 0.00 | 01-JAN-00:10 | 3004.89 | 07-JUN-15:40 |
| EnergyTransfer:Zone:T N1 APARTMENT | 14.66 | 0.01 | 25-JUL-19:30 | 2429.86 | 07-JUN-18:30 |
| Heating:EnergyTransfer:Zone:T N1 APARTMENT | 2.76 | 0.00 | 01-JAN-09:30 | 1720.27 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T N1 APARTMENT | 2.76 | 0.00 | 01-JAN-09:30 | 1720.27 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 11.90 | 0.00 | 01-JAN-00:10 | 2426.98 | 07-JUN-18:30 |
| General:Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 11.90 | 0.00 | 01-JAN-00:10 | 2426.98 | 07-JUN-18:30 |
| EnergyTransfer:Zone:T N2 APARTMENT | 14.68 | 0.02 | 18-JAN-15:50 | 2464.41 | 07-JUN-15:40 |
| Heating:EnergyTransfer:Zone:T N2 APARTMENT | 2.76 | 0.00 | 01-JAN-09:30 | 1721.24 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T N2 APARTMENT | 2.76 | 0.00 | 01-JAN-09:30 | 1721.24 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 11.92 | 0.00 | 01-JAN-00:10 | 2459.06 | 07-JUN-15:40 |
| General:Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 11.92 | 0.00 | 01-JAN-00:10 | 2459.06 | 07-JUN-15:40 |
| EnergyTransfer:Zone:T S1 APARTMENT | 16.16 | 0.01 | 05-MAY-10:00 | 3349.27 | 22-OCT-16:10 |
| Heating:EnergyTransfer:Zone:T S1 APARTMENT | 1.41 | 0.00 | 01-JAN-08:20 | 1639.70 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T S1 APARTMENT | 1.41 | 0.00 | 01-JAN-08:20 | 1639.70 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 14.75 | 0.00 | 01-JAN-00:10 | 3349.27 | 22-OCT-16:10 |
| General:Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 14.75 | 0.00 | 01-JAN-00:10 | 3349.27 | 22-OCT-16:10 |
| EnergyTransfer:Zone:T S2 APARTMENT | 16.19 | 0.00 | 08-JUL-06:50 | 3338.37 | 22-OCT-15:10 |
| Heating:EnergyTransfer:Zone:T S2 APARTMENT | 1.41 | 0.00 | 01-JAN-08:20 | 1640.94 | 12-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T S2 APARTMENT | 1.41 | 0.00 | 01-JAN-08:20 | 1640.94 | 12-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 14.78 | 0.00 | 01-JAN-00:10 | 3338.37 | 22-OCT-15:10 |
| General:Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 14.78 | 0.00 | 01-JAN-00:10 | 3338.37 | 22-OCT-15:10 |
| EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Facility | 313.70 | 158.85 | 03-AUG-02:50 | 22066.76 | 01-FEB-07:40 |
| PlantLoopHeatingDemand:Plant | 313.70 | 158.85 | 03-AUG-02:50 | 22066.76 | 01-FEB-07:40 |
| WaterSystems:PlantLoopHeatingDemand | 313.70 | 158.85 | 03-AUG-02:50 | 22066.76 | 01-FEB-07:40 |
| General:WaterSystems:PlantLoopHeatingDemand | 313.70 | 158.85 | 03-AUG-02:50 | 22066.76 | 01-FEB-07:40 |
| EnergyTransfer:HVAC | 844.24 | 78.68 | 31-MAY-21:20 | 126270.98 | 19-JUL-11:20 |
| HeatRecoveryForHeating:EnergyTransfer | 161.10 | 0.00 | 28-FEB-14:30 | 22455.75 | 12-FEB-07:00 |
| HeatRecoveryForCooling:EnergyTransfer | 50.13 | 0.00 | 01-JAN-00:10 | 12463.30 | 08-JUL-14:00 |
| CoolingCoils:EnergyTransfer | 585.24 | 0.00 | 01-JAN-00:10 | 123589.15 | 29-AUG-08:40 |
| HeatingCoils:EnergyTransfer | 47.77 | 0.00 | 01-JAN-11:30 | 38024.60 | 12-FEB-05:50 |
| EnergyTransfer:Plant | 313.70 | 158.85 | 03-AUG-02:50 | 22064.50 | 01-FEB-07:40 |
| WaterSystems:EnergyTransfer | 313.70 | 158.85 | 03-AUG-02:50 | 22064.50 | 01-FEB-07:40 |
| WaterUse:WaterSystems:EnergyTransfer | 313.70 | 158.85 | 03-AUG-02:50 | 22064.50 | 01-FEB-07:40 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| G SW APARTMENT | 0.481 | -2.002 | 1.049 | -13.520 | 0.000 | 0.000 | 3.634 | 0.918 | 12.213 | 8.483 | 0.000 | 0.097 | 0.000 | 0.000 | -4.890 | 0.000 | -2.061 | -4.402 |
| G NW APARTMENT | 0.483 | -1.893 | 2.323 | -11.267 | 0.000 | 0.000 | 3.743 | 0.918 | 12.213 | 4.972 | 0.000 | 0.097 | 0.000 | 0.000 | -5.019 | 0.000 | -1.933 | -4.637 |
| OFFICE | 0.000 | 0.000 | 2.781 | -13.778 | 0.000 | 0.000 | 2.060 | 5.679 | 7.520 | 8.294 | 0.000 | 0.056 | 0.000 | 0.000 | -4.965 | 0.000 | -1.087 | -6.560 |
| G NE APARTMENT | 0.482 | -1.897 | 2.294 | -11.341 | 0.000 | 0.000 | 3.745 | 0.918 | 12.213 | 4.812 | 0.000 | 0.097 | 0.000 | 0.000 | -4.791 | 0.000 | -1.943 | -4.590 |
| G N1 APARTMENT | 0.482 | -1.948 | 1.020 | -10.253 | 0.000 | 0.000 | 3.709 | 0.918 | 12.213 | 1.915 | 0.000 | 0.059 | 0.000 | 0.000 | -3.221 | 0.000 | -1.602 | -3.290 |
| G N2 APARTMENT | 0.482 | -1.948 | 1.020 | -10.267 | 0.000 | 0.000 | 3.708 | 0.918 | 12.213 | 1.914 | 0.000 | 0.059 | 0.000 | 0.000 | -3.221 | 0.000 | -1.602 | -3.275 |
| G S1 APARTMENT | 0.480 | -2.068 | 0.262 | -13.194 | 0.000 | 0.000 | 3.592 | 0.918 | 12.213 | 5.489 | 0.000 | 0.059 | 0.000 | 0.000 | -3.021 | 0.000 | -1.686 | -3.044 |
| G S2 APARTMENT | 0.480 | -2.064 | 0.379 | -14.002 | 0.000 | 0.000 | 3.595 | 0.918 | 12.213 | 5.484 | 0.000 | 0.059 | 0.000 | 0.000 | -3.018 | 0.000 | -1.662 | -2.381 |
| M SW APARTMENT | 0.959 | -4.120 | 1.147 | -33.608 | 0.000 | 0.000 | 7.193 | 1.837 | 24.426 | 16.682 | 0.000 | 0.278 | 0.749 | 0.000 | -10.141 | 0.000 | -5.402 | -0.001 |
| M NW APARTMENT | 0.958 | -3.915 | 3.514 | -27.674 | 0.000 | 0.000 | 7.396 | 1.837 | 24.426 | 9.715 | 0.000 | 0.278 | 0.000 | 0.000 | -10.488 | 0.000 | -5.275 | -0.770 |
| M SE APARTMENT | 0.958 | -4.130 | 1.146 | -33.811 | 0.000 | 0.000 | 7.197 | 1.837 | 24.426 | 16.578 | 0.000 | 0.278 | 0.840 | 0.000 | -9.897 | 0.000 | -5.424 | -0.001 |
| M NE APARTMENT | 0.957 | -3.924 | 3.439 | -27.794 | 0.000 | 0.000 | 7.401 | 1.837 | 24.426 | 9.377 | 0.000 | 0.278 | 0.000 | 0.000 | -10.011 | 0.000 | -5.324 | -0.660 |
| M N1 APARTMENT | 0.959 | -4.011 | 1.112 | -24.324 | 0.000 | 0.000 | 7.339 | 1.837 | 24.426 | 3.749 | 0.000 | 0.168 | 0.000 | 0.000 | -6.711 | 0.000 | -4.311 | -0.232 |
| M N2 APARTMENT | 0.959 | -4.011 | 1.114 | -24.358 | 0.000 | 0.000 | 7.339 | 1.837 | 24.426 | 3.748 | 0.000 | 0.168 | 0.000 | 0.000 | -6.711 | 0.000 | -4.313 | -0.195 |
| M S1 APARTMENT | 0.959 | -4.258 | 0.184 | -31.597 | 0.000 | 0.000 | 7.105 | 1.837 | 24.426 | 10.833 | 0.000 | 0.168 | 0.903 | 0.000 | -6.253 | 0.000 | -4.306 | -0.000 |
| M S2 APARTMENT | 0.959 | -4.258 | 0.184 | -31.638 | 0.000 | 0.000 | 7.105 | 1.837 | 24.426 | 10.831 | 0.000 | 0.168 | 0.948 | 0.000 | -6.253 | 0.000 | -4.309 | -0.001 |
| T SW APARTMENT | 0.480 | -1.918 | 4.105 | -16.004 | 0.000 | 0.000 | 3.688 | 0.918 | 12.213 | 8.338 | 0.000 | 0.182 | 0.000 | 0.000 | -4.679 | 0.000 | -3.134 | -4.189 |
| T NW APARTMENT | 0.480 | -1.825 | 6.153 | -13.745 | 0.000 | 0.000 | 3.779 | 0.918 | 12.213 | 4.866 | 0.000 | 0.182 | 0.000 | 0.000 | -4.856 | 0.000 | -3.005 | -5.160 |
| T SE APARTMENT | 0.479 | -1.929 | 4.031 | -15.961 | 0.000 | 0.000 | 3.693 | 0.918 | 12.213 | 8.286 | 0.000 | 0.182 | 0.000 | 0.000 | -4.567 | 0.000 | -3.165 | -4.180 |
| T NE APARTMENT | 0.479 | -1.830 | 6.034 | -13.728 | 0.000 | 0.000 | 3.786 | 0.918 | 12.213 | 4.715 | 0.000 | 0.182 | 0.000 | 0.000 | -4.637 | 0.000 | -3.050 | -5.081 |
| T N1 APARTMENT | 0.480 | -1.846 | 3.757 | -11.537 | 0.000 | 0.000 | 3.768 | 0.918 | 12.213 | 1.884 | 0.000 | 0.110 | 0.000 | 0.000 | -3.086 | 0.000 | -2.317 | -4.345 |
| T N2 APARTMENT | 0.480 | -1.846 | 3.760 | -11.559 | 0.000 | 0.000 | 3.768 | 0.918 | 12.213 | 1.882 | 0.000 | 0.110 | 0.000 | 0.000 | -3.084 | 0.000 | -2.320 | -4.323 |
| T S1 APARTMENT | 0.480 | -1.965 | 2.063 | -13.922 | 0.000 | 0.000 | 3.661 | 0.918 | 12.213 | 5.433 | 0.000 | 0.110 | 0.000 | 0.000 | -2.879 | 0.000 | -2.427 | -3.684 |
| T S2 APARTMENT | 0.480 | -1.966 | 2.067 | -13.953 | 0.000 | 0.000 | 3.661 | 0.918 | 12.213 | 5.431 | 0.000 | 0.110 | 0.000 | 0.000 | -2.878 | 0.000 | -2.430 | -3.653 |
| T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.887 | 9.711 | 0.000 | 0.701 | 0.000 | 0.015 | 0.000 | 0.000 | -0.496 | 0.000 | -0.359 | -15.459 |
| G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.501 | 9.711 | 3.395 | 2.048 | 0.000 | 0.669 | 0.000 | 0.000 | -1.541 | 0.000 | -13.971 | -5.812 |
| M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11.109 | 19.423 | 0.000 | 1.373 | 0.000 | 0.026 | 0.000 | 0.000 | -1.093 | 0.000 | -0.611 | -30.228 |
| Total Facility | 14.875 | -61.571 | 54.937 | -442.836 | 0.000 | 0.000 | 138.163 | 72.996 | 389.511 | 167.832 | 0.000 | 4.241 | 3.442 | 0.000 | -132.406 | 0.000 | -89.031 | -120.154 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 14-OCT-21:52 | 0.00 | -65.41 | 0.00 | -4820.69 | 0.00 | 0.00 | 145.43 | 32.89 | 417.92 | 0.00 | 0.00 | 0.00 | 4637.05 | 0.00 | -321.52 | 0.00 | -25.67 | 0.00 |
| G NW APARTMENT | 03-OCT-20:12 | 0.00 | -80.12 | 0.00 | -4653.66 | 0.00 | 0.00 | 146.55 | 60.30 | 500.33 | 0.00 | 0.00 | 0.00 | 4412.01 | 0.00 | -347.08 | 0.00 | -38.34 | 0.00 |
| OFFICE | 12-OCT-06:01 | 0.00 | 0.00 | 0.00 | -5936.81 | 0.00 | 0.00 | 0.00 | 89.52 | 194.98 | 0.00 | 0.00 | 0.00 | 6184.09 | 0.00 | -478.83 | 0.00 | -52.96 | 0.00 |
| G NE APARTMENT | 03-OCT-20:12 | 0.00 | -81.89 | 0.00 | -4366.51 | 0.00 | 0.00 | 146.15 | 60.30 | 500.33 | 0.00 | 0.00 | 0.00 | 4125.42 | 0.00 | -345.21 | 0.00 | -38.60 | 0.00 |
| G N1 APARTMENT | 03-OCT-20:12 | 0.00 | -84.15 | 0.00 | -4003.47 | 0.00 | 0.00 | 145.82 | 60.30 | 500.33 | 0.00 | 0.00 | 0.00 | 3613.46 | 0.00 | -208.82 | 0.00 | -23.47 | 0.00 |
| G N2 APARTMENT | 03-OCT-20:12 | 0.00 | -84.18 | 0.00 | -3999.31 | 0.00 | 0.00 | 145.83 | 60.30 | 500.33 | 0.00 | 0.00 | 0.00 | 3609.34 | 0.00 | -208.85 | 0.00 | -23.47 | 0.00 |
| G S1 APARTMENT | 14-OCT-21:52 | 0.00 | -68.76 | 0.00 | -4184.16 | 0.00 | 0.00 | 145.47 | 32.89 | 417.92 | 0.00 | 0.00 | 0.00 | 3867.07 | 0.00 | -194.79 | 0.00 | -15.65 | 0.00 |
| G S2 APARTMENT | 14-OCT-21:52 | 0.00 | -68.72 | 0.00 | -4215.61 | 0.00 | 0.00 | 145.53 | 32.89 | 417.92 | 0.00 | 0.00 | 0.00 | 3898.78 | 0.00 | -195.16 | 0.00 | -15.64 | 0.00 |
| M SW APARTMENT | 14-MAR-19:52 | 0.00 | -135.26 | 0.00 | -11164.54 | 0.00 | 0.00 | 294.46 | 175.43 | 1047.75 | 0.00 | 0.00 | 0.00 | 10651.82 | 0.00 | -628.98 | 0.00 | -240.68 | 0.00 |
| M NW APARTMENT | 24-APR-21:02 | 0.00 | -159.52 | 0.00 | -10861.86 | 0.00 | 0.00 | 292.86 | 65.79 | 835.84 | 0.00 | 0.00 | 0.00 | 10665.97 | 0.00 | -732.18 | 0.00 | -106.90 | 0.00 |
| M SE APARTMENT | 14-MAR-19:52 | 0.00 | -139.30 | 0.00 | -10360.80 | 0.00 | 0.00 | 293.00 | 175.43 | 1047.75 | 0.00 | 0.00 | 0.00 | 9848.56 | 0.00 | -621.47 | 0.00 | -243.17 | 0.00 |
| M NE APARTMENT | 11-MAY-21:52 | 0.00 | -93.70 | 0.00 | -10147.86 | 0.00 | 0.00 | 290.27 | 65.79 | 835.84 | 0.00 | 0.00 | 0.00 | 9621.83 | 0.00 | -522.95 | 0.00 | -49.22 | 0.00 |
| M N1 APARTMENT | 11-MAY-21:52 | 0.00 | -97.70 | 0.00 | -9160.95 | 0.00 | 0.00 | 291.73 | 65.79 | 835.84 | 0.00 | 0.00 | 0.00 | 8405.00 | 0.00 | -309.94 | 0.00 | -29.77 | 0.00 |
| M N2 APARTMENT | 11-MAY-21:52 | 0.00 | -97.97 | 0.00 | -9139.55 | 0.00 | 0.00 | 291.55 | 65.79 | 835.84 | 0.00 | 0.00 | 0.00 | 8384.31 | 0.00 | -310.18 | 0.00 | -29.80 | 0.00 |
| M S1 APARTMENT | 14-OCT-21:52 | 0.00 | -132.83 | 0.00 | -9477.47 | 0.00 | 0.00 | 290.91 | 65.79 | 835.84 | 0.00 | 0.00 | 0.00 | 8856.11 | 0.00 | -393.62 | 0.00 | -44.73 | 0.00 |
| M S2 APARTMENT | 14-OCT-21:52 | 0.00 | -132.85 | 0.00 | -9466.53 | 0.00 | 0.00 | 290.91 | 65.79 | 835.84 | 0.00 | 0.00 | 0.00 | 8845.14 | 0.00 | -393.57 | 0.00 | -44.73 | 0.00 |
| T SW APARTMENT | 22-OCT-17:42 | 0.00 | -13.38 | 0.00 | -6306.91 | 0.00 | 0.00 | 125.17 | 74.01 | 588.62 | 43.46 | 0.00 | 0.00 | 5535.46 | 0.00 | -0.00 | 0.00 | -46.43 | 0.00 |
| T NW APARTMENT | 24-APR-17:22 | 0.00 | -21.39 | 0.00 | -6229.25 | 0.00 | 0.00 | 104.86 | 74.01 | 588.62 | 647.24 | 0.00 | 0.00 | 4907.40 | 0.00 | -0.00 | 0.00 | -71.50 | 0.00 |
| T SE APARTMENT | 24-APR-15:42 | 0.00 | -23.84 | 0.00 | -5692.71 | 0.00 | 0.00 | 0.00 | 38.37 | 470.90 | 287.67 | 0.00 | 0.00 | 5011.78 | 0.00 | -0.00 | 0.00 | -92.17 | 0.00 |
| T NE APARTMENT | 07-JUN-13:22 | 0.00 | 0.15 | 0.00 | -5621.05 | 0.00 | 0.00 | 30.11 | 10.96 | 382.60 | 194.56 | 0.00 | 0.00 | 5041.74 | 0.00 | -0.00 | 0.00 | -39.08 | 0.00 |
| T N1 APARTMENT | 24-APR-17:22 | 0.00 | -14.94 | 0.00 | -5185.07 | 0.00 | 0.00 | 116.84 | 74.01 | 588.62 | 3.72 | 0.00 | 0.00 | 4453.47 | 0.00 | -0.00 | 0.00 | -36.65 | 0.00 |
| T N2 APARTMENT | 11-MAY-21:52 | 0.00 | -46.38 | 0.00 | -5129.57 | 0.00 | 0.00 | 145.15 | 32.89 | 417.92 | 0.00 | 0.00 | 0.00 | 4755.87 | 0.00 | -156.19 | 0.00 | -19.69 | 0.00 |
| T S1 APARTMENT | 24-APR-15:42 | 0.00 | -23.85 | 0.00 | -5309.62 | 0.00 | 0.00 | 0.00 | 38.37 | 470.90 | 231.95 | 0.00 | 0.00 | 4646.78 | 0.00 | -0.00 | 0.00 | -54.53 | 0.00 |
| T S2 APARTMENT | 24-APR-15:42 | 0.00 | -24.34 | 0.00 | -5297.43 | 0.00 | 0.00 | 0.00 | 38.37 | 470.90 | 231.42 | 0.00 | 0.00 | 4635.97 | 0.00 | -0.00 | 0.00 | -54.90 | 0.00 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 03-OCT-20:12 | 0.00 | -2453.35 | 0.00 | -153066.13 | 0.00 | 0.00 | 5474.72 | 3190.75 | 15719.84 | 0.00 | 0.00 | 0.00 | 142432.89 | 0.00 | -9199.61 | 0.00 | -2099.11 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 12-FEB-06:00 | -304.83 | 0.00 | 1415.30 | 0.00 | 0.00 | 0.00 | 194.99 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -844.84 | 0.00 | -296.16 | -453.20 |
| G NW APARTMENT | 12-FEB-06:00 | -304.83 | 0.00 | 1557.10 | 0.00 | 0.00 | 0.00 | 194.99 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -857.89 | 0.00 | -296.16 | -581.96 |
| OFFICE | 14-FEB-07:01 | 0.00 | 0.00 | 9086.83 | 0.00 | 0.00 | 0.00 | 0.00 | 89.52 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -444.63 | 0.00 | -107.57 | -8819.13 |
| G NE APARTMENT | 12-FEB-06:00 | -304.83 | 0.00 | 1572.14 | 0.00 | 0.00 | 0.00 | 194.99 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -846.04 | 0.00 | -296.16 | -608.84 |
| G N1 APARTMENT | 12-FEB-08:12 | -299.39 | 0.00 | 933.15 | 0.00 | 0.00 | 0.00 | 76.05 | 16.45 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -459.29 | 0.00 | -118.69 | -536.76 |
| G N2 APARTMENT | 12-FEB-08:12 | -299.39 | 0.00 | 933.12 | 0.00 | 0.00 | 0.00 | 76.05 | 16.45 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -459.28 | 0.00 | -118.69 | -536.74 |
| G S1 APARTMENT | 12-FEB-06:00 | -304.92 | 0.00 | 763.40 | 0.00 | 0.00 | 0.00 | 194.99 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -510.46 | 0.00 | -178.64 | -253.11 |
| G S2 APARTMENT | 12-FEB-06:00 | -304.93 | 0.00 | 869.92 | 0.00 | 0.00 | 0.00 | 194.99 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -508.57 | 0.00 | -178.64 | -361.52 |
| M SW APARTMENT | 12-FEB-06:00 | -609.44 | 0.00 | 2750.43 | 0.00 | 0.00 | 0.00 | 389.98 | 71.26 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1722.75 | 0.00 | -851.72 | -533.97 |
| M NW APARTMENT | 12-FEB-06:00 | -609.44 | 0.00 | 3073.55 | 0.00 | 0.00 | 0.00 | 389.98 | 71.26 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1752.42 | 0.00 | -851.72 | -827.42 |
| M SE APARTMENT | 12-FEB-06:00 | -609.44 | 0.00 | 2779.37 | 0.00 | 0.00 | 0.00 | 389.98 | 71.26 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1696.17 | 0.00 | -851.72 | -589.50 |
| M NE APARTMENT | 12-FEB-06:00 | -609.44 | 0.00 | 3111.38 | 0.00 | 0.00 | 0.00 | 389.98 | 71.26 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1725.91 | 0.00 | -851.72 | -891.77 |
| M N1 APARTMENT | 12-FEB-06:00 | -609.65 | 0.00 | 1662.98 | 0.00 | 0.00 | 0.00 | 389.98 | 71.26 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1070.09 | 0.00 | -513.74 | -436.97 |
| M N2 APARTMENT | 12-FEB-06:00 | -609.65 | 0.00 | 1665.11 | 0.00 | 0.00 | 0.00 | 389.98 | 71.26 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1070.04 | 0.00 | -513.74 | -439.15 |
| M S1 APARTMENT | 12-FEB-06:00 | -609.66 | 0.00 | 1214.02 | 0.00 | 0.00 | 0.00 | 389.98 | 71.26 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1042.19 | 0.00 | -513.74 | -15.89 |
| M S2 APARTMENT | 12-FEB-06:00 | -609.66 | 0.00 | 1216.14 | 0.00 | 0.00 | 0.00 | 389.98 | 71.26 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1042.15 | 0.00 | -513.74 | -18.06 |
| T SW APARTMENT | 12-FEB-06:00 | -304.69 | 0.00 | 2824.79 | 0.00 | 0.00 | 0.00 | 194.99 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -836.39 | 0.00 | -564.00 | -1603.44 |
| T NW APARTMENT | 12-FEB-06:00 | -304.69 | 0.00 | 2900.35 | 0.00 | 0.00 | 0.00 | 194.99 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -854.48 | 0.00 | -564.00 | -1660.91 |
| T SE APARTMENT | 12-FEB-06:00 | -304.68 | 0.00 | 2829.72 | 0.00 | 0.00 | 0.00 | 194.98 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -822.96 | 0.00 | -564.01 | -1621.80 |
| T NE APARTMENT | 12-FEB-06:00 | -304.69 | 0.00 | 2903.35 | 0.00 | 0.00 | 0.00 | 194.99 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -841.11 | 0.00 | -564.00 | -1677.28 |
| T N1 APARTMENT | 12-FEB-06:00 | -304.81 | 0.00 | 2025.05 | 0.00 | 0.00 | 0.00 | 194.99 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -522.20 | 0.00 | -340.19 | -1341.58 |
| T N2 APARTMENT | 12-FEB-06:00 | -304.81 | 0.00 | 2026.02 | 0.00 | 0.00 | 0.00 | 194.99 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -522.18 | 0.00 | -340.19 | -1342.57 |
| T S1 APARTMENT | 12-FEB-06:00 | -304.81 | 0.00 | 1944.48 | 0.00 | 0.00 | 0.00 | 194.99 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -503.34 | 0.00 | -340.19 | -1279.87 |
| T S2 APARTMENT | 12-FEB-06:00 | -304.81 | 0.00 | 1945.73 | 0.00 | 0.00 | 0.00 | 194.99 | 35.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -503.32 | 0.00 | -340.19 | -1281.13 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 12-FEB-06:00 | -9907.96 | 459.45 | 44913.82 | -459.45 | 0.00 | 0.00 | 7373.61 | 2425.88 | 8055.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22370.60 | 0.00 | -11221.53 | -19268.88 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3099 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3099 | 0.0837 | 1.0000 | Not calculated | 0.0260 | 0.0837 | ||
| SPLIT GNW | 0.3008 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3008 | 0.0863 | 1.0000 | Not calculated | 0.0260 | 0.0863 | ||
| SPLIT OFFICE | 0.3532 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.3532 | 0.1079 | 1.0000 | Not calculated | 0.0381 | 0.1079 | ||
| SPLIT GNE | 0.2758 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2758 | 0.0941 | 1.0000 | Not calculated | 0.0260 | 0.0941 | ||
| SPLIT GN1 | 0.2488 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2488 | 0.1043 | 1.0000 | Not calculated | 0.0260 | 0.1043 | ||
| SPLIT GN2 | 0.2484 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2484 | 0.1045 | 1.0000 | Not calculated | 0.0260 | 0.1045 | ||
| SPLIT GS1 | 0.2575 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2575 | 0.1008 | 1.0000 | Not calculated | 0.0260 | 0.1008 | ||
| SPLIT GS2 | 0.2600 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2600 | 0.0998 | 1.0000 | Not calculated | 0.0260 | 0.0998 | ||
| SPLIT MSW | 0.7414 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7414 | 0.0700 | 1.0000 | Not calculated | 0.0519 | 0.0700 | ||
| SPLIT MNW | 0.7244 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7244 | 0.0717 | 1.0000 | Not calculated | 0.0519 | 0.0717 | ||
| SPLIT MSE | 0.6752 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6752 | 0.0769 | 1.0000 | Not calculated | 0.0519 | 0.0769 | ||
| SPLIT MNE | 0.6585 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6585 | 0.0788 | 1.0000 | Not calculated | 0.0519 | 0.0788 | ||
| SPLIT MN1 | 0.5820 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.5820 | 0.0892 | 1.0000 | Not calculated | 0.0519 | 0.0892 | ||
| SPLIT MN2 | 0.5803 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.5803 | 0.0895 | 1.0000 | Not calculated | 0.0519 | 0.0895 | ||
| SPLIT MS1 | 0.6028 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6028 | 0.0861 | 1.0000 | Not calculated | 0.0519 | 0.0861 | ||
| SPLIT MS2 | 0.6019 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6019 | 0.0862 | 1.0000 | Not calculated | 0.0519 | 0.0862 | ||
| SPLIT TSW | 0.4192 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4192 | 0.0619 | 1.0000 | Not calculated | 0.0260 | 0.0619 | ||
| SPLIT TNW | 0.4145 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4145 | 0.0626 | 1.0000 | Not calculated | 0.0260 | 0.0626 | ||
| SPLIT TSE | 0.3707 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3707 | 0.0700 | 1.0000 | Not calculated | 0.0260 | 0.0700 | ||
| SPLIT TNE | 0.3659 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3659 | 0.0709 | 1.0000 | Not calculated | 0.0260 | 0.0709 | ||
| SPLIT TN1 | 0.3380 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3380 | 0.0768 | 1.0000 | Not calculated | 0.0260 | 0.0768 | ||
| SPLIT TN2 | 0.3366 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3366 | 0.0771 | 1.0000 | Not calculated | 0.0260 | 0.0771 | ||
| SPLIT TS1 | 0.3436 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3436 | 0.0755 | 1.0000 | Not calculated | 0.0260 | 0.0755 | ||
| SPLIT TS2 | 0.3422 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3422 | 0.0758 | 1.0000 | Not calculated | 0.0260 | 0.0758 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3099 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3099 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0837 | ||
| SPLIT GNW | 0.3008 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3008 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0863 | ||
| SPLIT OFFICE | 0.3532 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.3532 | 1.0000 | 1.0000 | Not calculated | 0.0381 | 0.1079 | ||
| SPLIT GNE | 0.2758 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2758 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0941 | ||
| SPLIT GN1 | 0.2488 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2488 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.1043 | ||
| SPLIT GN2 | 0.2484 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2484 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.1045 | ||
| SPLIT GS1 | 0.2575 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2575 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.1008 | ||
| SPLIT GS2 | 0.2600 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2600 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0998 | ||
| SPLIT MSW | 0.7414 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7414 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0700 | ||
| SPLIT MNW | 0.7244 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7244 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0717 | ||
| SPLIT MSE | 0.6752 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6752 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0769 | ||
| SPLIT MNE | 0.6585 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6585 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0788 | ||
| SPLIT MN1 | 0.5820 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.5820 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0892 | ||
| SPLIT MN2 | 0.5803 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.5803 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0895 | ||
| SPLIT MS1 | 0.6028 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6028 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0861 | ||
| SPLIT MS2 | 0.6019 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6019 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0862 | ||
| SPLIT TSW | 0.4192 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4192 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0619 | ||
| SPLIT TNW | 0.4145 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4145 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0626 | ||
| SPLIT TSE | 0.3707 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3707 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0700 | ||
| SPLIT TNE | 0.3659 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3659 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0709 | ||
| SPLIT TN1 | 0.3380 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3380 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0768 | ||
| SPLIT TN2 | 0.3366 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3366 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0771 | ||
| SPLIT TS1 | 0.3436 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3436 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0755 | ||
| SPLIT TS2 | 0.3422 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3422 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0758 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G NW APARTMENT | SPLIT GNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| OFFICE | SPLIT OFFICE | 0.000000 | 4.7495 | 0.000432 | 88.25 | 0.0381 | 1.0000 | 0.0381 | 1.000 | 0.0381 |
| G NE APARTMENT | SPLIT GNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N1 APARTMENT | SPLIT GN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N2 APARTMENT | SPLIT GN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S1 APARTMENT | SPLIT GS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S2 APARTMENT | SPLIT GS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| M SW APARTMENT | SPLIT MSW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NW APARTMENT | SPLIT MNW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M SE APARTMENT | SPLIT MSE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NE APARTMENT | SPLIT MNE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N1 APARTMENT | SPLIT MN1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N2 APARTMENT | SPLIT MN2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S1 APARTMENT | SPLIT MS1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S2 APARTMENT | SPLIT MS2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| T SW APARTMENT | SPLIT TSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NW APARTMENT | SPLIT TNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T SE APARTMENT | SPLIT TSE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NE APARTMENT | SPLIT TNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N1 APARTMENT | SPLIT TN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N2 APARTMENT | SPLIT TN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S1 APARTMENT | SPLIT TS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S2 APARTMENT | SPLIT TS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| SPLIT GSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT OFFICE | 0.000000 | 4.75 | 0.000432 | 88.2493 | 0.0381 | 0.0381 | 0.0381 |
| SPLIT GNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT MSW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MSE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT TSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TSE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3099 | 0.3099 | 0.3099 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3008 | 0.3008 | 0.3008 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3532 | 0.3532 | 0.3532 | No | 0.0381 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2758 | 0.2758 | 0.2758 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2488 | 0.2488 | 0.2488 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2484 | 0.2484 | 0.2484 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2575 | 0.2575 | 0.2575 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2600 | 0.2600 | 0.2600 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7414 | 0.7414 | 0.7414 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7244 | 0.7244 | 0.7244 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6752 | 0.6752 | 0.6752 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6585 | 0.6585 | 0.6585 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5820 | 0.5820 | 0.5820 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5803 | 0.5803 | 0.5803 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6028 | 0.6028 | 0.6028 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6019 | 0.6019 | 0.6019 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4192 | 0.4192 | 0.4192 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4145 | 0.4145 | 0.4145 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3707 | 0.3707 | 0.3707 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3659 | 0.3659 | 0.3659 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3380 | 0.3380 | 0.3380 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3366 | 0.3366 | 0.3366 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3436 | 0.3436 | 0.3436 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3422 | 0.3422 | 0.3422 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3099 | 0.3099 | 0.3099 | 0.3099 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3008 | 0.3008 | 0.3008 | 0.3008 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.3532 | 0.3532 | 0.3532 | 0.3532 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.2758 | 0.2758 | 0.2758 | 0.2758 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2488 | 0.2488 | 0.2488 | 0.2488 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2484 | 0.2484 | 0.2484 | 0.2484 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.2575 | 0.2575 | 0.2575 | 0.2575 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.2600 | 0.2600 | 0.2600 | 0.2600 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.7414 | 0.7414 | 0.7414 | 0.7414 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.7244 | 0.7244 | 0.7244 | 0.7244 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.6752 | 0.6752 | 0.6752 | 0.6752 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.6585 | 0.6585 | 0.6585 | 0.6585 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.5820 | 0.5820 | 0.5820 | 0.5820 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.5803 | 0.5803 | 0.5803 | 0.5803 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.6028 | 0.6028 | 0.6028 | 0.6028 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.6019 | 0.6019 | 0.6019 | 0.6019 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4192 | 0.4192 | 0.4192 | 0.4192 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4145 | 0.4145 | 0.4145 | 0.4145 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.3707 | 0.3707 | 0.3707 | 0.3707 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.3659 | 0.3659 | 0.3659 | 0.3659 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3380 | 0.3380 | 0.3380 | 0.3380 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3366 | 0.3366 | 0.3366 | 0.3366 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3436 | 0.3436 | 0.3436 | 0.3436 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3422 | 0.3422 | 0.3422 | 0.3422 | 0.0260 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3099 | 0.3099 | 0.3099 | No | 0.0260 | 0.3339 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3008 | 0.3008 | 0.3008 | No | 0.0260 | 0.3628 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3532 | 0.3532 | 0.3532 | No | 0.0381 | 0.3792 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2758 | 0.2758 | 0.2758 | No | 0.0260 | 0.3643 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2488 | 0.2488 | 0.2488 | No | 0.0260 | 0.6410 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2484 | 0.2484 | 0.2484 | No | 0.0260 | 0.6411 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2575 | 0.2575 | 0.2575 | No | 0.0260 | 0.5535 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2600 | 0.2600 | 0.2600 | No | 0.0260 | 0.5470 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7414 | 0.7414 | 0.7414 | No | 0.0519 | 0.3471 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7244 | 0.7244 | 0.7244 | No | 0.0519 | 0.3837 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6752 | 0.6752 | 0.6752 | No | 0.0519 | 0.3488 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6585 | 0.6585 | 0.6585 | No | 0.0519 | 0.3857 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5820 | 0.5820 | 0.5820 | No | 0.0519 | 0.7432 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5803 | 0.5803 | 0.5803 | No | 0.0519 | 0.7434 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6028 | 0.6028 | 0.6028 | No | 0.0519 | 0.6200 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6019 | 0.6019 | 0.6019 | No | 0.0519 | 0.6202 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4192 | 0.4192 | 0.4192 | No | 0.0260 | 0.2080 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4145 | 0.4145 | 0.4145 | No | 0.0260 | 0.2213 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3707 | 0.3707 | 0.3707 | No | 0.0260 | 0.2087 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3659 | 0.3659 | 0.3659 | No | 0.0260 | 0.2222 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3380 | 0.3380 | 0.3380 | No | 0.0260 | 0.3229 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3366 | 0.3366 | 0.3366 | No | 0.0260 | 0.3230 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3436 | 0.3436 | 0.3436 | No | 0.0260 | 0.2953 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3422 | 0.3422 | 0.3422 | No | 0.0260 | 0.2953 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3099 | 0.3099 | 0.3099 | 0.3099 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3008 | 0.3008 | 0.3008 | 0.3008 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.3532 | 0.3532 | 0.3532 | 0.3532 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.2758 | 0.2758 | 0.2758 | 0.2758 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2488 | 0.2488 | 0.2488 | 0.2488 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2484 | 0.2484 | 0.2484 | 0.2484 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.2575 | 0.2575 | 0.2575 | 0.2575 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.2600 | 0.2600 | 0.2600 | 0.2600 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.7414 | 0.7414 | 0.7414 | 0.7414 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.7244 | 0.7244 | 0.7244 | 0.7244 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.6752 | 0.6752 | 0.6752 | 0.6752 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.6585 | 0.6585 | 0.6585 | 0.6585 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.5820 | 0.5820 | 0.5820 | 0.5820 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.5803 | 0.5803 | 0.5803 | 0.5803 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.6028 | 0.6028 | 0.6028 | 0.6028 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.6019 | 0.6019 | 0.6019 | 0.6019 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4192 | 0.4192 | 0.4192 | 0.4192 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4145 | 0.4145 | 0.4145 | 0.4145 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.3707 | 0.3707 | 0.3707 | 0.3707 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.3659 | 0.3659 | 0.3659 | 0.3659 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3380 | 0.3380 | 0.3380 | 0.3380 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3366 | 0.3366 | 0.3366 | 0.3366 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3436 | 0.3436 | 0.3436 | 0.3436 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3422 | 0.3422 | 0.3422 | 0.3422 | 0.0260 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
| Total gross floor area [m2] | 3134.61 |
| Principal Heating Source | Electricity |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| G SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| OFFICE | 88.25 | 88.25 | 0.00 | 33.56 |
| G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| G CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| M CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| Totals | 3134.61 | 2823.98 | 310.64 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.00 |
| Number of hours not met | 0.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 23.22 | 35296.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 152.39 | 27145.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 67.97 | 3560.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsPlugIn | 5.02 | 479.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 33.04 | 2101.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 67.41 | 3772.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 0.49 | 31.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 386.12 | 18442.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 102.87 | 13031.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- General | 0.46 | 14.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 0.00 | 0.00 | 406.16 | 28641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 454.01 | 838.98 |
| Natural Gas | 0.00 | 406.16 |
| Additional | 0.00 | 0.00 |
| Total | 454.01 | 1245.15 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 23.29 |
| Space Heating | 7.41 |
| Space Cooling | 48.62 |
| Fans (All) | 32.82 |
| Service Water Heating | 0.00 |
| Receptacle Equipment | 144.84 |
| Miscellaneous (All) | 267.65 |
| Subtotal | 267.65 |
| Natural Gas [MJ/m2] | |
| Space Heating | 0.00 |
| Service Water Heating | 129.57 |
| Miscellaneous (All) | 129.57 |
| Subtotal | 129.57 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 5.86 |
| Space Heating | 1.86 |
| Space Cooling | 12.24 |
| Fans (All) | 8.26 |
| Service Water Heating | 32.62 |
| Receptacle Equipment | 36.46 |
| Miscellaneous | 2.69 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| ELEVATOR_RUNNING_SCH | 146. | 3285. |
| ELEVATOR_STANDBY_SCH | 8201. | 8760. |
| OCC_APT_SCH_STAY_HOME_FAMILY | 5993. | 8760. |
| OCC_APT_SCH_CORRIDOR | 5993. | 8760. |
| OCC_APT_SCH_WORKING_FAMILY | 5845. | 6055. |
| OCC_OFF_SCH | 2210. | 2340. |
| OCC_OFF_W_SB_SCH | 1820. | 1820. |
| LTG_SCH_OFFICE | 2435. | 8760. |
| LTG_SCH_CORRIDOR | 6570. | 8760. |
| LTG_SCH_APARTMENT_HARDWIRED | 527. | 8760. |
| LTG_SCH_APARTMENT_PLUGIN | 527. | 8760. |
| EQP_APT_SCH | 5763. | 8760. |
| EQP_OFF_SCH | 3614. | 8760. |
| INF_APT_SCH | 8760. | 8760. |
| INF_OFF_SCH | 8760. | 8760. |
| INF_COR_SCH | 8760. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1399. | 5840. |
| ALL OFF | 0. | 0. |
| ALL ON | 8760. | 8760. |
| ALWAYS_ON | 8760. | 8760. |
| ALLON_EXCEPT_DD | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| FAN_OFF_W_SB_SCH | 8240. | 8240. |
| APT_DHW_SCH | 4592. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 5840. | 5840. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_APT_SCH | APTHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| HTGSETP_DESIGN_OFF_SCH | OFFHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| CLGSETP_APT_SCH | APTCOOLINGSETPOINT | July | 24.00 | 365 | 24.00 | 365 |
| CLGSETP_DESIGN_OFF_SCH | OFFCOOLINGSETPOINT | July | 23.90 | 365 | 23.90 | 365 |
| S HTGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| S CLGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| N HTGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| N CLGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_OFF_SCH_NO_OPTIMUM | OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
| CLGSETP_OFF_SCH_NO_OPTIMUM | OFFICE DUAL SP CONTROL | July | 24.00 | 365 | 29.40 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6645.67 | 2092.67 | 21.67 | 0.00 | 0.00 |
| G NE APARTMENT | 8752.83 | 7.17 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8694.67 | 65.33 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8703.33 | 56.67 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8667.50 | 92.50 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8675.17 | 84.83 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8737.33 | 22.67 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8737.17 | 22.83 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8725.33 | 34.67 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8726.00 | 34.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 5161.83 | 3243.33 | 354.83 | 0.00 | 0.00 |
| G CORRIDOR | 5261.67 | 3161.67 | 336.67 | 0.00 | 0.00 |
| M CORRIDOR | 3469.50 | 5290.50 | 0.00 | 0.00 | 0.00 |
| Min | 3469.50 | 0.33 | 0.00 | 0.00 | 0.00 |
| Max | 8759.67 | 5290.50 | 354.83 | 0.00 | 0.00 |
| Average | 8205.78 | 527.81 | 26.41 | 0.00 | 0.00 |
| Sum | 221556.00 | 14250.83 | 713.17 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 11825.17 | 4.83 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10582.17 | 2.83 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10583.00 | 2.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10584.17 | 0.83 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10583.83 | 1.17 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11828.17 | 1.83 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11824.00 | 6.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11821.50 | 8.50 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10580.17 | 4.83 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11819.17 | 10.83 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10582.00 | 3.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10584.33 | 0.67 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10584.33 | 0.67 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11828.83 | 1.17 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11828.83 | 1.17 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11740.17 | 89.83 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10508.33 | 76.67 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11757.67 | 72.33 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10542.83 | 42.17 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10557.83 | 27.17 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10558.67 | 26.33 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11784.33 | 45.67 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11786.67 | 43.33 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 13655.83 | 8354.00 | 985.17 | 0.00 | 0.00 |
| G CORRIDOR | 13363.50 | 8289.67 | 1341.83 | 0.00 | 0.00 |
| M CORRIDOR | 9018.17 | 13976.83 | 0.00 | 0.00 | 0.00 |
| Min | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 13655.83 | 13976.83 | 1341.83 | 0.00 | 0.00 |
| Average | 11100.51 | 1151.64 | 86.19 | 0.00 | 0.00 |
| Sum | 299713.67 | 31094.33 | 2327.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 7856.33 | 903.67 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 7854.17 | 905.83 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6118.00 | 2642.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 7847.33 | 912.67 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 7855.17 | 904.83 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 7855.33 | 904.67 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 7843.83 | 916.17 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 7857.83 | 902.17 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 7841.67 | 918.33 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 7833.83 | 926.17 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 7834.83 | 925.17 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 7828.17 | 931.83 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 7815.83 | 944.17 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 7816.50 | 943.50 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 7815.50 | 944.50 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 7815.83 | 944.17 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 7792.83 | 967.17 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 7791.50 | 968.50 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 7776.33 | 983.67 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 7764.83 | 995.17 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 7803.50 | 956.50 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 7804.33 | 955.67 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 7803.83 | 956.17 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 7800.00 | 960.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 1571.00 | 5904.83 | 1284.17 | 0.00 | 0.00 |
| G CORRIDOR | 4324.67 | 4044.83 | 390.50 | 0.00 | 0.00 |
| M CORRIDOR | 17.33 | 7497.67 | 1245.00 | 0.00 | 0.00 |
| Min | 17.33 | 902.17 | 0.00 | 0.00 | 0.00 |
| Max | 7857.83 | 7497.67 | 1284.17 | 0.00 | 0.00 |
| Average | 7108.90 | 1542.96 | 108.14 | 0.00 | 0.00 |
| Sum | 191940.33 | 41660.00 | 2919.67 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 10765.33 | 1064.67 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 9744.67 | 840.33 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6990.00 | 10.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 9739.67 | 845.33 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 9770.00 | 815.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 9771.00 | 814.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 10758.17 | 1071.83 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 10771.00 | 1059.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 10776.50 | 1053.50 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 9758.17 | 826.83 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 10766.50 | 1063.50 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 9752.50 | 832.50 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 9755.83 | 829.17 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 9756.17 | 828.83 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 10744.67 | 1085.33 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 10745.33 | 1084.67 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 10650.33 | 1179.67 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 9633.83 | 951.17 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 10625.00 | 1205.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 9599.00 | 986.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 9672.67 | 912.33 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 9673.33 | 911.67 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 10681.50 | 1148.50 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 10675.67 | 1154.33 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 4041.00 | 15545.50 | 3408.50 | 0.00 | 0.00 |
| G CORRIDOR | 10634.83 | 10798.17 | 1562.00 | 0.00 | 0.00 |
| M CORRIDOR | 48.83 | 19810.50 | 3135.67 | 0.00 | 0.00 |
| Min | 48.83 | 10.00 | 0.00 | 0.00 | 0.00 |
| Max | 10776.50 | 19810.50 | 3408.50 | 0.00 | 0.00 |
| Average | 9492.65 | 2545.46 | 300.23 | 0.00 | 0.00 |
| Sum | 256301.50 | 68727.33 | 8106.17 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 3.965 |
| February | 7.937 |
| March | 13.764 |
| April | 17.213 |
| May | 20.837 |
| June | 24.797 |
| July | 26.063 |
| August | 26.547 |
| September | 22.525 |
| October | 16.026 |
| November | 11.940 |
| December | 7.696 |
| Annual Sum or Average | 16.653 |
| Minimum of Months | 3.965 |
| Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 3.965 |
| February | 7.937 |
| March | 13.764 |
| April | 17.213 |
| May | 20.837 |
| June | 24.797 |
| July | 26.063 |
| August | 26.547 |
| September | 22.525 |
| October | 16.026 |
| November | 11.940 |
| December | 7.696 |
| Annual Sum or Average | 16.653 |
| Minimum of Months | 3.965 |
| Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 3.965 |
| February | 7.937 |
| March | 13.764 |
| April | 17.213 |
| May | 20.837 |
| June | 24.797 |
| July | 26.063 |
| August | 26.547 |
| September | 22.525 |
| October | 16.026 |
| November | 11.940 |
| December | 7.696 |
| Annual Sum or Average | 16.653 |
| Minimum of Months | 3.965 |
| Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 3.965 |
| February | 7.937 |
| March | 13.764 |
| April | 17.213 |
| May | 20.837 |
| June | 24.797 |
| July | 26.063 |
| August | 26.547 |
| September | 22.525 |
| October | 16.026 |
| November | 11.940 |
| December | 7.696 |
| Annual Sum or Average | 16.653 |
| Minimum of Months | 3.965 |
| Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 3.965 |
| February | 7.937 |
| March | 13.764 |
| April | 17.213 |
| May | 20.837 |
| June | 24.797 |
| July | 26.063 |
| August | 26.547 |
| September | 22.525 |
| October | 16.026 |
| November | 11.940 |
| December | 7.696 |
| Annual Sum or Average | 16.653 |
| Minimum of Months | 3.965 |
| Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 3.965 |
| February | 7.937 |
| March | 13.764 |
| April | 17.213 |
| May | 20.837 |
| June | 24.797 |
| July | 26.063 |
| August | 26.547 |
| September | 22.525 |
| October | 16.026 |
| November | 11.940 |
| December | 7.696 |
| Annual Sum or Average | 16.653 |
| Minimum of Months | 3.965 |
| Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 3.965 |
| February | 7.937 |
| March | 13.764 |
| April | 17.213 |
| May | 20.837 |
| June | 24.797 |
| July | 26.063 |
| August | 26.547 |
| September | 22.525 |
| October | 16.026 |
| November | 11.940 |
| December | 7.696 |
| Annual Sum or Average | 16.653 |
| Minimum of Months | 3.965 |
| Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 3.965 |
| February | 7.937 |
| March | 13.764 |
| April | 17.213 |
| May | 20.837 |
| June | 24.797 |
| July | 26.063 |
| August | 26.547 |
| September | 22.525 |
| October | 16.026 |
| November | 11.940 |
| December | 7.696 |
| Annual Sum or Average | 16.653 |
| Minimum of Months | 3.965 |
| Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 3.965 |
| February | 7.937 |
| March | 13.764 |
| April | 17.213 |
| May | 20.837 |
| June | 24.797 |
| July | 26.063 |
| August | 26.547 |
| September | 22.525 |
| October | 16.026 |
| November | 11.940 |
| December | 7.696 |
| Annual Sum or Average | 16.653 |
| Minimum of Months | 3.965 |
| Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.144942E+09 | 201.43 | 26-JAN-20:40 | -1.5 | -4.7 | 82741828.26 | 66.97 | 29-JAN-17:00 | 14.40 | 5.85 |
| February | 0.185100E+09 | 4706.21 | 28-FEB-22:52 | 17.30 | 10.02 | 83476082.64 | 92.43 | 27-FEB-18:19 | 17.30 | 10.02 |
| March | 0.426978E+09 | 4853.98 | 14-MAR-17:42 | 18.27 | 12.47 | 0.116481E+09 | 92.43 | 14-MAR-17:49 | 18.27 | 12.47 |
| April | 0.638632E+09 | 4836.71 | 12-APR-19:32 | 21.67 | 14.49 | 0.125220E+09 | 93.02 | 12-APR-19:10 | 21.67 | 14.49 |
| May | 0.117909E+10 | 4844.09 | 12-MAY-20:02 | 20.32 | 13.54 | 0.131897E+09 | 95.73 | 09-MAY-17:49 | 20.32 | 13.54 |
| June | 0.206351E+10 | 4828.96 | 07-JUN-21:12 | 18.53 | 12.48 | 0.125416E+09 | 102.43 | 07-JUN-17:00 | 18.53 | 12.48 |
| July | 0.247978E+10 | 4349.24 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134914E+09 | 98.27 | 13-JUL-21:10 | 23.30 | 21.29 |
| August | 0.283850E+10 | 4101.26 | 30-AUG-21:52 | 22.80 | 20.81 | 0.128259E+09 | 99.88 | 31-AUG-17:49 | 22.80 | 20.15 |
| September | 0.212012E+10 | 4855.67 | 14-SEP-21:52 | 18.90 | 14.00 | 0.132744E+09 | 102.28 | 13-SEP-17:10 | 18.90 | 14.00 |
| October | 0.136790E+10 | 4886.10 | 14-OCT-21:52 | 15.00 | 11.33 | 0.135097E+09 | 105.49 | 14-OCT-15:09 | 15.00 | 11.33 |
| November | 0.776159E+09 | 4843.87 | 06-NOV-13:02 | 19.18 | 12.72 | 0.124610E+09 | 98.99 | 05-NOV-16:49 | 19.18 | 12.72 |
| December | 0.400797E+09 | 4651.96 | 10-DEC-19:22 | 14.15 | 7.08 | 0.102327E+09 | 84.37 | 12-DEC-22:00 | 18.30 | 14.87 |
| Annual Sum or Average | 0.146215E+11 | 0.142318E+10 | ||||||||
| Minimum of Months | 0.144942E+09 | 201.43 | -1.5 | -4.7 | 82741828.26 | 66.97 | 14.40 | 5.85 | ||
| Maximum of Months | 0.283850E+10 | 4886.10 | 22.80 | 20.81 | 0.135097E+09 | 105.49 | 23.30 | 21.29 |
Report: ZoneCoolingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 24407226.93 | 131.47 | 21-JAN-19:40 | 5.77 | 2.99 | 78578752.58 | 50.36 | 20-JAN-21:10 | 5.77 | 2.99 |
| February | 65838742.83 | 2712.90 | 28-FEB-17:52 | 22.80 | 12.36 | 76326670.70 | 69.92 | 28-FEB-21:10 | 20.32 | 11.65 |
| March | 0.222303E+09 | 4164.88 | 30-MAR-21:52 | 22.80 | 16.45 | 0.105939E+09 | 79.93 | 30-MAR-21:00 | 22.80 | 16.45 |
| April | 0.418673E+09 | 4654.15 | 24-APR-21:02 | 13.22 | 9.86 | 0.121321E+09 | 85.88 | 16-APR-20:10 | 13.22 | 9.86 |
| May | 0.105015E+10 | 4701.06 | 12-MAY-20:02 | 20.32 | 13.54 | 0.134616E+09 | 92.69 | 27-MAY-20:19 | 21.50 | 18.76 |
| June | 0.204355E+10 | 4686.37 | 07-JUN-20:52 | 18.90 | 12.65 | 0.129579E+09 | 97.37 | 26-JUN-20:00 | 23.30 | 21.67 |
| July | 0.243345E+10 | 4220.49 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134165E+09 | 98.15 | 13-JUL-21:10 | 23.30 | 21.29 |
| August | 0.262290E+10 | 3944.63 | 30-AUG-21:52 | 22.80 | 20.81 | 0.133156E+09 | 97.29 | 31-AUG-20:49 | 21.78 | 20.15 |
| September | 0.174588E+10 | 4714.59 | 14-SEP-21:52 | 18.90 | 14.00 | 0.132786E+09 | 99.22 | 09-SEP-20:49 | 18.90 | 14.00 |
| October | 0.812455E+09 | 4733.77 | 03-OCT-20:12 | 13.53 | 10.58 | 0.134980E+09 | 95.13 | 18-OCT-20:19 | 23.30 | 22.56 |
| November | 0.336776E+09 | 4648.86 | 09-NOV-21:22 | 14.45 | 11.06 | 0.114463E+09 | 85.39 | 05-NOV-21:49 | 14.45 | 11.06 |
| December | 0.155971E+09 | 228.80 | 01-DEC-06:12 | -3.9 | -4.8 | 84915949.59 | 66.93 | 13-DEC-21:10 | 13.80 | 13.42 |
| Annual Sum or Average | 0.119324E+11 | 0.138083E+10 | ||||||||
| Minimum of Months | 24407226.93 | 131.47 | -3.9 | -4.8 | 76326670.70 | 50.36 | 5.77 | 2.99 | ||
| Maximum of Months | 0.262290E+10 | 4733.77 | 22.80 | 20.81 | 0.134980E+09 | 99.22 | 23.30 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.608511E+09 | 981.60 | 27-JAN-07:04 | -6.7 | -7.9 | 44011047.54 | 133.51 | 31-JAN-16:00 | 19.40 | 13.37 |
| February | 0.504522E+09 | 1254.43 | 28-FEB-15:30 | 24.15 | 13.12 | 47335883.37 | 133.51 | 22-FEB-16:00 | 24.15 | 13.12 |
| March | 0.622833E+09 | 4650.10 | 31-MAR-06:02 | 17.30 | 16.12 | 73213603.90 | 133.52 | 30-MAR-14:39 | 17.30 | 16.12 |
| April | 0.704576E+09 | 5795.33 | 17-APR-06:01 | 13.58 | 10.46 | 66248374.87 | 133.53 | 19-APR-12:00 | 25.00 | 17.82 |
| May | 0.106142E+10 | 5435.86 | 17-MAY-06:01 | 16.78 | 13.17 | 74012599.25 | 133.53 | 30-MAY-15:30 | 29.20 | 21.54 |
| June | 0.168738E+10 | 5828.27 | 08-JUN-06:01 | 12.07 | 8.47 | 74020350.79 | 133.54 | 26-JUN-15:00 | 28.90 | 23.31 |
| July | 0.180910E+10 | 4870.81 | 03-JUL-06:01 | 18.68 | 16.73 | 67292913.44 | 133.54 | 05-JUL-08:39 | 27.57 | 23.31 |
| August | 0.218625E+10 | 4454.78 | 14-AUG-06:01 | 23.40 | 20.72 | 77387045.79 | 133.54 | 07-AUG-07:10 | 23.40 | 20.72 |
| September | 0.168237E+10 | 5693.49 | 14-SEP-06:01 | 12.30 | 11.00 | 67291849.23 | 133.54 | 11-SEP-08:30 | 12.30 | 11.00 |
| October | 0.129329E+10 | 5936.80 | 12-OCT-06:01 | 8.12 | 5.86 | 70043645.76 | 133.53 | 10-OCT-08:00 | 8.12 | 5.86 |
| November | 0.913916E+09 | 4846.62 | 03-NOV-06:01 | 13.80 | 12.88 | 65522418.28 | 133.52 | 06-NOV-10:39 | 16.27 | 12.91 |
| December | 0.704162E+09 | 2701.31 | 13-DEC-07:02 | 16.70 | 15.65 | 55921709.80 | 133.52 | 11-DEC-15:50 | 16.70 | 15.65 |
| Annual Sum or Average | 0.137783E+11 | 0.782301E+09 | ||||||||
| Minimum of Months | 0.504522E+09 | 981.60 | -6.7 | -7.9 | 44011047.54 | 133.51 | 8.12 | 5.86 | ||
| Maximum of Months | 0.218625E+10 | 5936.80 | 24.15 | 20.72 | 77387045.79 | 133.54 | 29.20 | 23.31 |
Report: ZoneCoolingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 23095940.08 | 124.07 | 01-JAN-18:01 | 6.70 | 6.36 | 78543122.73 | 50.51 | 31-JAN-21:10 | 16.82 | 12.20 |
| February | 67731605.22 | 2441.57 | 28-FEB-17:52 | 22.80 | 12.36 | 76535624.89 | 70.39 | 28-FEB-21:10 | 20.32 | 11.65 |
| March | 0.209032E+09 | 3843.74 | 30-MAR-21:52 | 22.80 | 16.45 | 0.105044E+09 | 78.60 | 30-MAR-21:00 | 22.80 | 16.45 |
| April | 0.409206E+09 | 4333.37 | 15-APR-21:52 | 19.40 | 12.51 | 0.120739E+09 | 86.04 | 16-APR-20:10 | 22.12 | 14.23 |
| May | 0.106308E+10 | 4367.53 | 14-MAY-21:52 | 17.20 | 12.41 | 0.134661E+09 | 92.12 | 31-MAY-20:10 | 22.20 | 18.22 |
| June | 0.207881E+10 | 4384.66 | 09-JUN-21:52 | 21.70 | 12.59 | 0.129770E+09 | 95.77 | 26-JUN-20:00 | 23.30 | 21.67 |
| July | 0.247974E+10 | 3932.12 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134319E+09 | 97.83 | 25-JUL-20:49 | 22.80 | 21.95 |
| August | 0.262875E+10 | 3669.65 | 30-AUG-21:52 | 22.80 | 20.81 | 0.133194E+09 | 97.74 | 07-AUG-21:10 | 22.80 | 20.81 |
| September | 0.174846E+10 | 4411.64 | 14-SEP-21:52 | 18.90 | 14.00 | 0.132835E+09 | 98.49 | 09-SEP-20:49 | 18.90 | 14.00 |
| October | 0.812236E+09 | 4448.40 | 03-OCT-20:12 | 13.53 | 10.58 | 0.134350E+09 | 95.35 | 18-OCT-20:19 | 23.30 | 22.56 |
| November | 0.332965E+09 | 4350.61 | 09-NOV-21:22 | 14.45 | 11.06 | 0.114272E+09 | 84.95 | 03-NOV-21:00 | 14.45 | 11.06 |
| December | 0.163123E+09 | 228.96 | 01-DEC-06:12 | -3.9 | -4.8 | 84750709.99 | 67.01 | 13-DEC-21:10 | 13.80 | 13.42 |
| Annual Sum or Average | 0.120162E+11 | 0.137901E+10 | ||||||||
| Minimum of Months | 23095940.08 | 124.07 | -3.9 | -4.8 | 76535624.89 | 50.51 | 13.80 | 11.06 | ||
| Maximum of Months | 0.262875E+10 | 4448.40 | 22.80 | 20.81 | 0.134661E+09 | 98.49 | 23.30 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 84606148.52 | 171.87 | 22-JAN-18:40 | 1.67 | -1.0 | 80078690.99 | 54.08 | 20-JAN-21:10 | 1.67 | -1.0 |
| February | 93361202.80 | 3209.66 | 28-FEB-17:52 | 22.80 | 12.36 | 80428671.74 | 73.45 | 28-FEB-22:49 | 17.57 | 10.18 |
| March | 0.257018E+09 | 3921.76 | 13-MAR-20:52 | 21.10 | 14.16 | 0.115624E+09 | 80.21 | 30-MAR-21:00 | 22.80 | 16.45 |
| April | 0.478440E+09 | 4029.24 | 24-APR-21:02 | 13.22 | 9.86 | 0.125395E+09 | 86.01 | 21-APR-21:00 | 13.22 | 9.86 |
| May | 0.103868E+10 | 4034.32 | 11-MAY-21:52 | 16.70 | 12.59 | 0.134958E+09 | 92.10 | 27-MAY-20:30 | 21.40 | 18.77 |
| June | 0.178927E+10 | 4019.64 | 07-JUN-21:52 | 17.80 | 12.14 | 0.129478E+09 | 95.13 | 26-JUN-20:00 | 23.30 | 21.67 |
| July | 0.207880E+10 | 3588.29 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134184E+09 | 95.50 | 27-JUL-20:40 | 20.97 | 20.35 |
| August | 0.219849E+10 | 3353.54 | 30-AUG-21:52 | 22.80 | 20.81 | 0.133029E+09 | 96.73 | 31-AUG-20:49 | 21.78 | 20.15 |
| September | 0.155964E+10 | 4060.17 | 14-SEP-21:52 | 18.90 | 14.00 | 0.132737E+09 | 96.47 | 09-SEP-20:49 | 18.90 | 14.00 |
| October | 0.881697E+09 | 4087.62 | 03-OCT-20:12 | 13.53 | 10.58 | 0.135364E+09 | 94.99 | 01-OCT-20:00 | 13.53 | 10.58 |
| November | 0.434864E+09 | 4029.07 | 09-NOV-21:22 | 14.45 | 11.06 | 0.121493E+09 | 87.62 | 04-NOV-21:00 | 14.45 | 11.06 |
| December | 0.314224E+09 | 508.01 | 13-DEC-21:02 | 13.80 | 13.42 | 92903765.85 | 71.26 | 13-DEC-21:10 | 13.80 | 13.42 |
| Annual Sum or Average | 0.112091E+11 | 0.141567E+10 | ||||||||
| Minimum of Months | 84606148.52 | 171.87 | 1.67 | -1.0 | 80078690.99 | 54.08 | 1.67 | -1.0 | ||
| Maximum of Months | 0.219849E+10 | 4087.62 | 22.80 | 20.81 | 0.135364E+09 | 96.73 | 23.30 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 84569015.90 | 169.13 | 22-JAN-18:25 | 1.95 | -0.9 | 80081191.82 | 54.03 | 20-JAN-21:10 | 1.95 | -0.9 |
| February | 93575318.97 | 3305.83 | 28-FEB-17:52 | 22.80 | 12.36 | 80481651.41 | 73.66 | 28-FEB-22:49 | 17.57 | 10.18 |
| March | 0.256794E+09 | 3916.74 | 13-MAR-20:52 | 21.10 | 14.16 | 0.115606E+09 | 80.16 | 30-MAR-21:00 | 22.80 | 16.45 |
| April | 0.479223E+09 | 4023.94 | 24-APR-21:02 | 13.22 | 9.86 | 0.125388E+09 | 86.04 | 21-APR-21:00 | 13.22 | 9.86 |
| May | 0.104220E+10 | 4029.07 | 11-MAY-21:52 | 16.70 | 12.59 | 0.134974E+09 | 92.00 | 27-MAY-20:30 | 21.40 | 18.77 |
| June | 0.179308E+10 | 4014.81 | 07-JUN-21:52 | 17.80 | 12.14 | 0.129487E+09 | 95.06 | 26-JUN-20:00 | 23.30 | 21.67 |
| July | 0.208211E+10 | 3584.52 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134189E+09 | 95.52 | 27-JUL-20:40 | 20.97 | 20.35 |
| August | 0.219942E+10 | 3349.25 | 30-AUG-21:52 | 22.80 | 20.81 | 0.133028E+09 | 96.72 | 31-AUG-20:49 | 21.78 | 20.15 |
| September | 0.156179E+10 | 4055.50 | 14-SEP-21:52 | 18.90 | 14.00 | 0.132745E+09 | 96.47 | 09-SEP-20:49 | 18.90 | 14.00 |
| October | 0.882007E+09 | 4083.48 | 03-OCT-20:12 | 13.53 | 10.58 | 0.135360E+09 | 94.94 | 01-OCT-20:00 | 13.53 | 10.58 |
| November | 0.434217E+09 | 4024.17 | 09-NOV-21:22 | 14.45 | 11.06 | 0.121518E+09 | 87.58 | 04-NOV-21:00 | 14.45 | 11.06 |
| December | 0.314192E+09 | 504.29 | 13-DEC-21:02 | 13.80 | 13.42 | 92915576.09 | 71.25 | 13-DEC-21:10 | 13.80 | 13.42 |
| Annual Sum or Average | 0.112232E+11 | 0.141577E+10 | ||||||||
| Minimum of Months | 84569015.90 | 169.13 | 1.95 | -0.9 | 80081191.82 | 54.03 | 1.95 | -0.9 | ||
| Maximum of Months | 0.219942E+10 | 4083.48 | 22.80 | 20.81 | 0.135360E+09 | 96.72 | 23.30 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.308692E+09 | 588.53 | 29-JAN-17:52 | 14.40 | 5.85 | 90009157.31 | 71.39 | 29-JAN-17:00 | 14.40 | 5.85 |
| February | 0.334749E+09 | 4115.58 | 28-FEB-22:52 | 17.30 | 10.02 | 89781350.80 | 92.43 | 27-FEB-18:10 | 17.30 | 10.02 |
| March | 0.593077E+09 | 4213.91 | 14-MAR-19:52 | 14.40 | 8.86 | 0.123334E+09 | 92.12 | 14-MAR-17:49 | 14.40 | 8.86 |
| April | 0.752212E+09 | 4196.59 | 24-APR-21:02 | 13.22 | 9.86 | 0.128026E+09 | 91.83 | 20-APR-18:00 | 13.22 | 9.86 |
| May | 0.117673E+10 | 4209.00 | 11-MAY-21:52 | 16.70 | 12.59 | 0.132261E+09 | 92.75 | 28-MAY-18:00 | 22.20 | 19.19 |
| June | 0.181746E+10 | 4175.11 | 07-JUN-19:42 | 20.87 | 13.07 | 0.125342E+09 | 96.26 | 26-JUN-17:00 | 23.30 | 21.67 |
| July | 0.213666E+10 | 3736.99 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134993E+09 | 97.42 | 27-JUL-19:10 | 21.70 | 20.50 |
| August | 0.242755E+10 | 3528.43 | 30-AUG-21:52 | 22.80 | 20.81 | 0.128172E+09 | 98.71 | 31-AUG-19:19 | 22.20 | 20.07 |
| September | 0.195029E+10 | 4219.69 | 14-SEP-21:52 | 18.90 | 14.00 | 0.132896E+09 | 99.53 | 02-SEP-19:19 | 18.90 | 14.00 |
| October | 0.148993E+10 | 4252.92 | 14-OCT-21:52 | 15.00 | 11.33 | 0.135641E+09 | 102.95 | 14-OCT-15:09 | 15.00 | 11.33 |
| November | 0.104615E+10 | 4223.32 | 09-NOV-21:22 | 14.45 | 11.06 | 0.127725E+09 | 96.95 | 02-NOV-17:10 | 14.45 | 11.06 |
| December | 0.576713E+09 | 4077.51 | 10-DEC-19:22 | 14.15 | 7.08 | 0.117155E+09 | 88.51 | 12-DEC-22:00 | 18.30 | 14.87 |
| Annual Sum or Average | 0.146102E+11 | 0.146534E+10 | ||||||||
| Minimum of Months | 0.308692E+09 | 588.53 | 13.22 | 5.85 | 89781350.80 | 71.39 | 13.22 | 5.85 | ||
| Maximum of Months | 0.242755E+10 | 4252.92 | 22.80 | 20.81 | 0.135641E+09 | 102.95 | 23.30 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.275129E+09 | 233.27 | 26-JAN-08:50 | -4.6 | -6.8 | 87749173.77 | 69.27 | 29-JAN-17:00 | 14.40 | 5.85 |
| February | 0.305740E+09 | 4143.55 | 28-FEB-22:52 | 17.30 | 10.02 | 88853495.58 | 92.43 | 26-FEB-18:10 | 17.30 | 10.02 |
| March | 0.589056E+09 | 4243.20 | 14-MAR-19:52 | 14.40 | 8.86 | 0.123059E+09 | 92.22 | 14-MAR-17:49 | 14.40 | 8.86 |
| April | 0.776367E+09 | 4226.53 | 24-APR-21:02 | 13.22 | 9.86 | 0.128141E+09 | 92.43 | 20-APR-18:00 | 13.22 | 9.86 |
| May | 0.124585E+10 | 4239.44 | 11-MAY-21:52 | 16.70 | 12.59 | 0.132638E+09 | 93.83 | 20-MAY-20:10 | 20.60 | 17.97 |
| June | 0.197040E+10 | 4202.89 | 07-JUN-19:42 | 20.87 | 13.07 | 0.125757E+09 | 97.76 | 26-JUN-17:00 | 23.30 | 21.67 |
| July | 0.234413E+10 | 3797.79 | 02-JUL-21:52 | 22.80 | 18.09 | 0.135528E+09 | 98.57 | 27-JUL-19:10 | 21.70 | 20.50 |
| August | 0.264455E+10 | 3594.27 | 30-AUG-21:52 | 22.80 | 20.81 | 0.128543E+09 | 99.94 | 31-AUG-19:19 | 22.20 | 20.07 |
| September | 0.209111E+10 | 4250.10 | 14-SEP-21:52 | 18.90 | 14.00 | 0.133409E+09 | 101.21 | 09-SEP-20:49 | 18.90 | 14.00 |
| October | 0.153664E+10 | 4284.33 | 14-OCT-21:52 | 15.00 | 11.33 | 0.135805E+09 | 103.48 | 14-OCT-15:09 | 15.00 | 11.33 |
| November | 0.102896E+10 | 4251.66 | 09-NOV-21:22 | 14.45 | 11.06 | 0.127545E+09 | 96.85 | 05-NOV-16:00 | 14.45 | 11.06 |
| December | 0.552108E+09 | 4099.41 | 10-DEC-19:22 | 14.15 | 7.08 | 0.115581E+09 | 87.88 | 12-DEC-22:00 | 18.30 | 14.87 |
| Annual Sum or Average | 0.153600E+11 | 0.146261E+10 | ||||||||
| Minimum of Months | 0.275129E+09 | 233.27 | -4.6 | -6.8 | 87749173.77 | 69.27 | 13.22 | 5.85 | ||
| Maximum of Months | 0.264455E+10 | 4284.33 | 22.80 | 20.81 | 0.135805E+09 | 103.48 | 23.30 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.268518E+09 | 4149.42 | 29-JAN-17:52 | 14.40 | 5.85 | 90918701.73 | 79.20 | 29-JAN-17:00 | 14.40 | 5.85 |
| February | 0.445440E+09 | 5484.43 | 26-FEB-22:52 | 15.00 | 8.88 | 93607859.39 | 100.94 | 26-FEB-17:40 | 15.00 | 8.88 |
| March | 0.102810E+10 | 5649.93 | 14-MAR-19:52 | 14.40 | 8.86 | 0.127755E+09 | 103.24 | 14-MAR-17:30 | 14.40 | 8.86 |
| April | 0.139572E+10 | 5638.19 | 24-APR-21:02 | 13.22 | 9.86 | 0.132266E+09 | 108.30 | 09-APR-16:30 | 13.22 | 9.86 |
| May | 0.191071E+10 | 5626.03 | 11-MAY-21:52 | 16.70 | 12.59 | 0.134808E+09 | 104.85 | 01-MAY-17:40 | 16.70 | 12.59 |
| June | 0.253085E+10 | 5596.33 | 07-JUN-18:02 | 23.12 | 13.70 | 0.125635E+09 | 105.11 | 07-JUN-17:00 | 23.12 | 13.70 |
| July | 0.279646E+10 | 5047.98 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134891E+09 | 98.96 | 27-JUL-19:10 | 21.70 | 20.50 |
| August | 0.300535E+10 | 4681.84 | 30-AUG-21:52 | 22.80 | 20.81 | 0.127763E+09 | 99.65 | 31-AUG-17:49 | 22.80 | 20.15 |
| September | 0.214479E+10 | 5607.55 | 13-SEP-18:42 | 20.87 | 14.62 | 0.131706E+09 | 101.10 | 13-SEP-17:19 | 20.87 | 14.62 |
| October | 0.135743E+10 | 5636.73 | 14-OCT-21:52 | 15.00 | 11.33 | 0.134518E+09 | 106.47 | 07-OCT-17:19 | 15.00 | 11.33 |
| November | 0.777873E+09 | 5593.62 | 06-NOV-13:02 | 19.18 | 12.72 | 0.123209E+09 | 100.05 | 11-NOV-17:10 | 18.95 | 10.47 |
| December | 0.460213E+09 | 5433.39 | 11-DEC-16:02 | 21.02 | 15.88 | 0.103716E+09 | 93.67 | 10-DEC-16:40 | 21.02 | 15.88 |
| Annual Sum or Average | 0.181214E+11 | 0.146079E+10 | ||||||||
| Minimum of Months | 0.268518E+09 | 4149.42 | 13.22 | 5.85 | 90918701.73 | 79.20 | 13.22 | 5.85 | ||
| Maximum of Months | 0.300535E+10 | 5649.93 | 23.12 | 20.81 | 0.134891E+09 | 108.30 | 23.12 | 20.50 |
Report: ZoneCoolingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 78583951.05 | 180.51 | 22-JAN-19:40 | 0.77 | -1.5 | 80935850.46 | 59.39 | 20-JAN-21:10 | 0.77 | -1.5 |
| February | 0.142068E+09 | 5350.79 | 28-FEB-22:52 | 17.30 | 10.02 | 87602714.01 | 91.59 | 28-FEB-21:10 | 17.30 | 10.02 |
| March | 0.572330E+09 | 5496.67 | 14-MAR-19:52 | 14.40 | 8.86 | 0.127641E+09 | 93.16 | 29-MAR-21:19 | 22.43 | 16.94 |
| April | 0.107643E+10 | 5510.68 | 24-APR-21:02 | 13.22 | 9.86 | 0.131416E+09 | 96.63 | 14-APR-20:10 | 13.22 | 9.86 |
| May | 0.177116E+10 | 5508.71 | 11-MAY-21:52 | 16.70 | 12.59 | 0.137886E+09 | 100.58 | 27-MAY-20:19 | 21.50 | 18.76 |
| June | 0.250378E+10 | 5482.40 | 07-JUN-18:02 | 23.12 | 13.70 | 0.129792E+09 | 98.59 | 26-JUN-20:00 | 23.30 | 21.67 |
| July | 0.273852E+10 | 4938.76 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134135E+09 | 97.30 | 27-JUL-20:40 | 20.97 | 20.35 |
| August | 0.277086E+10 | 4534.01 | 30-AUG-21:52 | 22.80 | 20.81 | 0.132665E+09 | 97.34 | 31-AUG-20:49 | 21.78 | 20.15 |
| September | 0.174185E+10 | 5476.21 | 14-SEP-21:52 | 18.90 | 14.00 | 0.131716E+09 | 97.26 | 09-SEP-20:49 | 18.90 | 14.00 |
| October | 0.769093E+09 | 5481.61 | 03-OCT-20:12 | 13.53 | 10.58 | 0.133140E+09 | 92.92 | 18-OCT-20:19 | 23.30 | 22.56 |
| November | 0.314538E+09 | 5268.68 | 06-NOV-19:12 | 13.87 | 6.89 | 0.112031E+09 | 85.96 | 03-NOV-21:00 | 13.87 | 6.89 |
| December | 0.169657E+09 | 1747.76 | 13-DEC-21:02 | 13.80 | 13.42 | 87170808.18 | 73.95 | 13-DEC-21:10 | 13.80 | 13.42 |
| Annual Sum or Average | 0.146489E+11 | 0.142613E+10 | ||||||||
| Minimum of Months | 78583951.05 | 180.51 | 0.77 | -1.5 | 80935850.46 | 59.39 | 0.77 | -1.5 | ||
| Maximum of Months | 0.277086E+10 | 5510.68 | 23.12 | 20.81 | 0.137886E+09 | 100.58 | 23.30 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.270676E+09 | 3431.68 | 29-JAN-17:52 | 14.40 | 5.85 | 90679713.16 | 77.57 | 29-JAN-17:00 | 14.40 | 5.85 |
| February | 0.471232E+09 | 5108.28 | 26-FEB-22:52 | 15.00 | 8.88 | 93358004.66 | 97.66 | 27-FEB-19:10 | 19.82 | 10.52 |
| March | 0.100503E+10 | 5250.08 | 14-MAR-19:52 | 14.40 | 8.86 | 0.126467E+09 | 100.45 | 14-MAR-17:30 | 14.40 | 8.86 |
| April | 0.138524E+10 | 5229.47 | 14-APR-21:52 | 17.20 | 12.41 | 0.131672E+09 | 104.00 | 09-APR-16:30 | 17.20 | 12.41 |
| May | 0.192744E+10 | 5235.95 | 11-MAY-21:52 | 16.70 | 12.59 | 0.134994E+09 | 101.00 | 07-MAY-09:50 | 16.70 | 12.59 |
| June | 0.256853E+10 | 5196.41 | 09-JUN-21:52 | 21.70 | 12.59 | 0.125882E+09 | 100.73 | 11-JUN-09:00 | 25.00 | 14.66 |
| July | 0.284095E+10 | 4674.97 | 02-JUL-21:52 | 22.80 | 18.09 | 0.135045E+09 | 99.98 | 09-JUL-08:00 | 25.00 | 22.22 |
| August | 0.301082E+10 | 4361.58 | 08-AUG-17:52 | 26.70 | 23.52 | 0.127828E+09 | 99.05 | 31-AUG-17:49 | 22.80 | 20.15 |
| September | 0.215073E+10 | 5216.69 | 14-SEP-21:52 | 18.90 | 14.00 | 0.131705E+09 | 101.28 | 23-SEP-09:39 | 24.07 | 17.84 |
| October | 0.136162E+10 | 5246.59 | 14-OCT-21:52 | 15.00 | 11.33 | 0.134218E+09 | 104.47 | 14-OCT-15:09 | 15.00 | 11.33 |
| November | 0.776466E+09 | 5229.93 | 06-NOV-13:02 | 19.18 | 12.72 | 0.122997E+09 | 96.55 | 05-NOV-16:00 | 19.18 | 12.72 |
| December | 0.461643E+09 | 5026.96 | 10-DEC-19:22 | 14.15 | 7.08 | 0.103805E+09 | 88.31 | 12-DEC-22:00 | 18.30 | 14.87 |
| Annual Sum or Average | 0.182304E+11 | 0.145865E+10 | ||||||||
| Minimum of Months | 0.270676E+09 | 3431.68 | 14.15 | 5.85 | 90679713.16 | 77.57 | 14.40 | 5.85 | ||
| Maximum of Months | 0.301082E+10 | 5250.08 | 26.70 | 23.52 | 0.135045E+09 | 104.47 | 25.00 | 22.22 |
Report: ZoneCoolingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 72284423.65 | 157.27 | 21-JAN-24:00 | 3.30 | 0.92 | 80826633.94 | 59.62 | 31-JAN-22:40 | 13.37 | 10.31 |
| February | 0.144577E+09 | 4952.53 | 28-FEB-22:52 | 17.30 | 10.02 | 87549725.57 | 86.36 | 28-FEB-22:49 | 17.30 | 10.02 |
| March | 0.543521E+09 | 5053.70 | 14-MAR-19:52 | 14.40 | 8.86 | 0.126443E+09 | 91.14 | 28-MAR-20:49 | 22.38 | 17.34 |
| April | 0.106122E+10 | 5115.25 | 11-APR-21:52 | 17.20 | 12.68 | 0.131017E+09 | 94.83 | 20-APR-20:30 | 19.45 | 15.20 |
| May | 0.178807E+10 | 5120.78 | 11-MAY-21:52 | 16.70 | 12.59 | 0.138098E+09 | 97.85 | 27-MAY-20:19 | 21.50 | 18.76 |
| June | 0.254344E+10 | 5067.76 | 09-JUN-21:52 | 21.70 | 12.59 | 0.130039E+09 | 96.89 | 17-JUN-20:40 | 22.07 | 20.98 |
| July | 0.278476E+10 | 4559.76 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134221E+09 | 97.92 | 25-JUL-20:49 | 22.80 | 21.95 |
| August | 0.277619E+10 | 4197.12 | 08-AUG-17:52 | 26.70 | 23.52 | 0.132726E+09 | 96.91 | 31-AUG-20:49 | 21.78 | 20.15 |
| September | 0.174425E+10 | 5088.74 | 13-SEP-19:02 | 20.22 | 14.52 | 0.131883E+09 | 96.44 | 09-SEP-20:49 | 20.22 | 14.52 |
| October | 0.767624E+09 | 5091.49 | 03-OCT-20:12 | 13.53 | 10.58 | 0.132266E+09 | 93.08 | 18-OCT-20:19 | 23.30 | 22.56 |
| November | 0.310368E+09 | 4885.24 | 06-NOV-19:12 | 13.87 | 6.89 | 0.111721E+09 | 86.11 | 03-NOV-21:00 | 13.87 | 6.89 |
| December | 0.175827E+09 | 1823.06 | 13-DEC-21:02 | 13.80 | 13.42 | 86969781.13 | 74.11 | 13-DEC-21:10 | 13.80 | 13.42 |
| Annual Sum or Average | 0.147121E+11 | 0.142376E+10 | ||||||||
| Minimum of Months | 72284423.65 | 157.27 | 3.30 | 0.92 | 80826633.94 | 59.62 | 13.37 | 6.89 | ||
| Maximum of Months | 0.278476E+10 | 5120.78 | 26.70 | 23.52 | 0.138098E+09 | 97.92 | 23.30 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.188450E+09 | 210.88 | 23-JAN-01:00 | -2.2 | -3.0 | 85389694.08 | 64.01 | 20-JAN-21:10 | -2.2 | -3.0 |
| February | 0.242017E+09 | 4492.69 | 28-FEB-22:52 | 17.30 | 10.02 | 91618482.32 | 87.96 | 28-FEB-22:00 | 17.30 | 10.02 |
| March | 0.655149E+09 | 4584.59 | 14-MAR-19:52 | 14.40 | 8.86 | 0.130544E+09 | 91.22 | 28-MAR-20:00 | 22.20 | 17.27 |
| April | 0.102699E+10 | 4605.47 | 24-APR-21:02 | 13.22 | 9.86 | 0.130995E+09 | 94.96 | 22-APR-21:19 | 13.22 | 9.86 |
| May | 0.154517E+10 | 4629.33 | 11-MAY-21:52 | 16.70 | 12.59 | 0.137218E+09 | 97.51 | 27-MAY-20:19 | 21.50 | 18.76 |
| June | 0.205852E+10 | 4575.60 | 07-JUN-20:52 | 18.90 | 12.65 | 0.129445E+09 | 95.33 | 26-JUN-20:00 | 23.30 | 21.67 |
| July | 0.222509E+10 | 4073.85 | 02-JUL-21:52 | 22.80 | 18.09 | 0.133882E+09 | 95.98 | 27-JUL-20:40 | 20.97 | 20.35 |
| August | 0.223491E+10 | 3751.80 | 30-AUG-21:52 | 22.80 | 20.81 | 0.132490E+09 | 96.52 | 31-AUG-20:49 | 21.78 | 20.15 |
| September | 0.152962E+10 | 4601.18 | 13-SEP-19:02 | 20.22 | 14.52 | 0.131692E+09 | 94.40 | 09-SEP-20:49 | 20.22 | 14.52 |
| October | 0.850542E+09 | 4596.60 | 21-OCT-21:52 | 14.40 | 11.34 | 0.134182E+09 | 93.45 | 01-OCT-20:00 | 14.40 | 11.34 |
| November | 0.445242E+09 | 4567.80 | 09-NOV-21:22 | 14.45 | 11.06 | 0.120233E+09 | 88.76 | 03-NOV-21:00 | 14.45 | 11.06 |
| December | 0.331919E+09 | 3446.47 | 12-DEC-22:52 | 18.30 | 14.87 | 97120365.25 | 79.22 | 13-DEC-21:10 | 13.80 | 13.42 |
| Annual Sum or Average | 0.133336E+11 | 0.145481E+10 | ||||||||
| Minimum of Months | 0.188450E+09 | 210.88 | -2.2 | -3.0 | 85389694.08 | 64.01 | -2.2 | -3.0 | ||
| Maximum of Months | 0.223491E+10 | 4629.33 | 22.80 | 20.81 | 0.137218E+09 | 97.51 | 23.30 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.187864E+09 | 210.78 | 23-JAN-01:00 | -2.2 | -3.0 | 85391124.98 | 63.94 | 20-JAN-21:10 | -2.2 | -3.0 |
| February | 0.243784E+09 | 4481.60 | 28-FEB-22:52 | 17.30 | 10.02 | 91638526.70 | 87.93 | 28-FEB-22:00 | 17.30 | 10.02 |
| March | 0.653589E+09 | 4573.60 | 14-MAR-19:52 | 14.40 | 8.86 | 0.130503E+09 | 91.31 | 28-MAR-20:00 | 22.20 | 17.27 |
| April | 0.102887E+10 | 4592.37 | 24-APR-21:02 | 13.22 | 9.86 | 0.131003E+09 | 94.96 | 22-APR-21:19 | 13.22 | 9.86 |
| May | 0.154990E+10 | 4618.76 | 11-MAY-21:52 | 16.70 | 12.59 | 0.137232E+09 | 97.40 | 27-MAY-20:19 | 21.50 | 18.76 |
| June | 0.206286E+10 | 4564.24 | 07-JUN-20:52 | 18.90 | 12.65 | 0.129455E+09 | 95.24 | 26-JUN-20:00 | 23.30 | 21.67 |
| July | 0.222783E+10 | 4063.44 | 02-JUL-21:52 | 22.80 | 18.09 | 0.133872E+09 | 95.98 | 27-JUL-20:40 | 20.97 | 20.35 |
| August | 0.223619E+10 | 3741.75 | 30-AUG-21:52 | 22.80 | 20.81 | 0.132489E+09 | 96.50 | 31-AUG-20:49 | 21.78 | 20.15 |
| September | 0.153254E+10 | 4589.88 | 13-SEP-19:02 | 20.22 | 14.52 | 0.131701E+09 | 94.25 | 09-SEP-20:49 | 20.22 | 14.52 |
| October | 0.850329E+09 | 4585.27 | 21-OCT-21:52 | 14.40 | 11.34 | 0.134174E+09 | 93.38 | 01-OCT-20:00 | 14.40 | 11.34 |
| November | 0.444605E+09 | 4556.39 | 09-NOV-21:22 | 14.45 | 11.06 | 0.120254E+09 | 88.76 | 03-NOV-21:00 | 14.45 | 11.06 |
| December | 0.331843E+09 | 3421.55 | 12-DEC-22:52 | 18.30 | 14.87 | 97126523.15 | 79.22 | 13-DEC-21:10 | 13.80 | 13.42 |
| Annual Sum or Average | 0.133502E+11 | 0.145484E+10 | ||||||||
| Minimum of Months | 0.187864E+09 | 210.78 | -2.2 | -3.0 | 85391124.98 | 63.94 | -2.2 | -3.0 | ||
| Maximum of Months | 0.223619E+10 | 4618.76 | 22.80 | 20.81 | 0.137232E+09 | 97.40 | 23.30 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.455925E+09 | 4499.26 | 29-JAN-17:52 | 14.40 | 5.85 | 0.105375E+09 | 84.19 | 29-JAN-17:00 | 14.40 | 5.85 |
| February | 0.632628E+09 | 4690.57 | 26-FEB-22:52 | 15.00 | 8.88 | 0.102784E+09 | 98.49 | 21-FEB-19:10 | 15.00 | 8.88 |
| March | 0.118961E+10 | 4790.11 | 14-MAR-19:52 | 14.40 | 8.86 | 0.129106E+09 | 99.34 | 14-MAR-17:30 | 14.40 | 8.86 |
| April | 0.135649E+10 | 4782.39 | 24-APR-21:02 | 13.22 | 9.86 | 0.131807E+09 | 101.35 | 09-APR-16:30 | 13.22 | 9.86 |
| May | 0.168391E+10 | 4788.82 | 11-MAY-21:52 | 16.70 | 12.59 | 0.134230E+09 | 98.49 | 01-MAY-17:40 | 16.70 | 12.59 |
| June | 0.208519E+10 | 4741.54 | 09-JUN-21:52 | 21.70 | 12.59 | 0.125301E+09 | 96.26 | 17-JUN-19:10 | 22.80 | 20.15 |
| July | 0.228436E+10 | 4227.13 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134717E+09 | 98.24 | 29-JUL-18:40 | 21.87 | 21.75 |
| August | 0.247068E+10 | 3936.62 | 30-AUG-21:52 | 22.80 | 20.81 | 0.127613E+09 | 97.78 | 31-AUG-19:19 | 22.20 | 20.07 |
| September | 0.193574E+10 | 4768.38 | 14-SEP-21:52 | 18.90 | 14.00 | 0.131821E+09 | 98.41 | 02-SEP-19:19 | 18.90 | 14.00 |
| October | 0.149520E+10 | 4805.15 | 14-OCT-21:52 | 15.00 | 11.33 | 0.135369E+09 | 103.24 | 14-OCT-15:09 | 15.00 | 11.33 |
| November | 0.108894E+10 | 4773.66 | 06-NOV-13:02 | 19.18 | 12.72 | 0.127414E+09 | 97.71 | 18-NOV-16:30 | 20.55 | 9.53 |
| December | 0.707534E+09 | 4637.49 | 10-DEC-19:22 | 14.15 | 7.08 | 0.119238E+09 | 95.44 | 10-DEC-16:40 | 14.15 | 7.08 |
| Annual Sum or Average | 0.173862E+11 | 0.150478E+10 | ||||||||
| Minimum of Months | 0.455925E+09 | 3936.62 | 13.22 | 5.85 | 0.102784E+09 | 84.19 | 13.22 | 5.85 | ||
| Maximum of Months | 0.247068E+10 | 4805.15 | 22.80 | 20.81 | 0.135369E+09 | 103.24 | 22.80 | 21.75 |
Report: ZoneCoolingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.456969E+09 | 4494.53 | 29-JAN-17:52 | 14.40 | 5.85 | 0.105347E+09 | 84.23 | 29-JAN-17:00 | 14.40 | 5.85 |
| February | 0.634104E+09 | 4685.50 | 26-FEB-22:52 | 15.00 | 8.88 | 0.102794E+09 | 98.52 | 21-FEB-19:10 | 15.00 | 8.88 |
| March | 0.118631E+10 | 4784.69 | 14-MAR-19:52 | 14.40 | 8.86 | 0.129050E+09 | 99.37 | 14-MAR-17:30 | 14.40 | 8.86 |
| April | 0.135846E+10 | 4775.45 | 24-APR-21:02 | 13.22 | 9.86 | 0.131803E+09 | 101.45 | 09-APR-16:30 | 13.22 | 9.86 |
| May | 0.168813E+10 | 4783.82 | 11-MAY-21:52 | 16.70 | 12.59 | 0.134239E+09 | 98.24 | 01-MAY-17:40 | 16.70 | 12.59 |
| June | 0.208975E+10 | 4736.83 | 09-JUN-21:52 | 21.70 | 12.59 | 0.125308E+09 | 96.29 | 17-JUN-19:10 | 22.80 | 20.15 |
| July | 0.228683E+10 | 4222.01 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134690E+09 | 97.73 | 29-JUL-18:40 | 21.87 | 21.75 |
| August | 0.247200E+10 | 3931.61 | 30-AUG-21:52 | 22.80 | 20.81 | 0.127612E+09 | 97.76 | 31-AUG-19:19 | 22.20 | 20.07 |
| September | 0.193827E+10 | 4763.16 | 14-SEP-21:52 | 18.90 | 14.00 | 0.131827E+09 | 98.41 | 02-SEP-19:19 | 18.90 | 14.00 |
| October | 0.149655E+10 | 4799.69 | 14-OCT-21:52 | 15.00 | 11.33 | 0.135367E+09 | 103.34 | 14-OCT-15:09 | 15.00 | 11.33 |
| November | 0.108881E+10 | 4768.92 | 06-NOV-13:02 | 19.18 | 12.72 | 0.127410E+09 | 97.67 | 18-NOV-16:30 | 20.55 | 9.53 |
| December | 0.710176E+09 | 4631.99 | 10-DEC-19:22 | 14.15 | 7.08 | 0.119254E+09 | 95.41 | 10-DEC-16:40 | 14.15 | 7.08 |
| Annual Sum or Average | 0.174064E+11 | 0.150470E+10 | ||||||||
| Minimum of Months | 0.456969E+09 | 3931.61 | 13.22 | 5.85 | 0.102794E+09 | 84.23 | 13.22 | 5.85 | ||
| Maximum of Months | 0.247200E+10 | 4799.69 | 22.80 | 20.81 | 0.135367E+09 | 103.34 | 22.80 | 21.75 |
Report: ZoneCoolingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.124786E+09 | 5835.57 | 29-JAN-17:52 | 14.40 | 5.85 | 83316951.91 | 88.68 | 29-JAN-17:00 | 14.40 | 5.85 |
| February | 0.231169E+09 | 6075.17 | 20-FEB-18:42 | 14.87 | 8.36 | 83636178.22 | 110.23 | 20-FEB-18:10 | 14.87 | 8.36 |
| March | 0.594581E+09 | 6239.64 | 14-MAR-19:52 | 14.40 | 8.86 | 0.112661E+09 | 113.61 | 14-MAR-17:30 | 14.40 | 8.86 |
| April | 0.113351E+10 | 6312.94 | 24-APR-15:42 | 20.50 | 13.54 | 0.126911E+09 | 118.05 | 25-APR-17:30 | 16.40 | 9.18 |
| May | 0.184001E+10 | 6231.68 | 12-MAY-18:32 | 22.57 | 14.82 | 0.133228E+09 | 118.53 | 01-MAY-17:30 | 22.57 | 14.82 |
| June | 0.272588E+10 | 6286.75 | 07-JUN-18:02 | 23.12 | 13.70 | 0.125002E+09 | 123.28 | 07-JUN-17:00 | 23.12 | 13.70 |
| July | 0.308513E+10 | 5611.04 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134330E+09 | 108.50 | 01-JUL-19:19 | 22.80 | 18.09 |
| August | 0.331922E+10 | 5299.24 | 08-AUG-17:52 | 26.70 | 23.52 | 0.127387E+09 | 109.42 | 31-AUG-17:49 | 22.80 | 20.15 |
| September | 0.206173E+10 | 6243.05 | 13-SEP-13:42 | 23.98 | 15.53 | 0.129819E+09 | 111.36 | 13-SEP-17:19 | 22.93 | 15.03 |
| October | 0.961162E+09 | 6320.37 | 22-OCT-17:42 | 20.87 | 14.13 | 0.122677E+09 | 117.03 | 21-OCT-16:10 | 20.87 | 14.13 |
| November | 0.335560E+09 | 6187.69 | 06-NOV-14:12 | 20.60 | 11.13 | 0.103141E+09 | 109.39 | 05-NOV-16:00 | 20.60 | 11.13 |
| December | 0.176608E+09 | 6015.55 | 11-DEC-16:02 | 21.02 | 15.88 | 87705812.94 | 103.76 | 10-DEC-16:40 | 21.02 | 15.88 |
| Annual Sum or Average | 0.165894E+11 | 0.136982E+10 | ||||||||
| Minimum of Months | 0.124786E+09 | 5299.24 | 14.40 | 5.85 | 83316951.91 | 88.68 | 14.40 | 5.85 | ||
| Maximum of Months | 0.331922E+10 | 6320.37 | 26.70 | 23.52 | 0.134330E+09 | 123.28 | 23.12 | 20.15 |
Report: ZoneCoolingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 17351775.76 | 128.31 | 11-JAN-17:03 | 6.02 | 1.58 | 79265021.02 | 57.14 | 31-JAN-21:10 | 16.82 | 12.20 |
| February | 64764037.05 | 5949.11 | 28-FEB-22:52 | 17.30 | 10.02 | 79406216.70 | 92.68 | 28-FEB-21:10 | 17.30 | 10.02 |
| March | 0.311959E+09 | 6147.09 | 14-MAR-19:52 | 14.40 | 8.86 | 0.108503E+09 | 96.68 | 29-MAR-21:19 | 22.43 | 16.94 |
| April | 0.844766E+09 | 6250.73 | 24-APR-17:22 | 20.85 | 13.50 | 0.125078E+09 | 107.28 | 14-APR-20:10 | 20.85 | 13.50 |
| May | 0.169058E+10 | 6162.57 | 11-MAY-16:52 | 22.80 | 14.90 | 0.136364E+09 | 109.52 | 27-MAY-20:19 | 21.50 | 18.76 |
| June | 0.268809E+10 | 6219.40 | 07-JUN-18:02 | 23.12 | 13.70 | 0.129296E+09 | 108.12 | 26-JUN-20:00 | 23.30 | 21.67 |
| July | 0.302018E+10 | 5549.29 | 02-JUL-21:52 | 22.80 | 18.09 | 0.133682E+09 | 105.96 | 13-JUL-21:10 | 23.30 | 21.29 |
| August | 0.306504E+10 | 5179.00 | 08-AUG-17:52 | 26.70 | 23.52 | 0.132359E+09 | 103.03 | 31-AUG-20:49 | 21.78 | 20.15 |
| September | 0.164165E+10 | 6160.25 | 18-SEP-18:22 | 21.70 | 15.69 | 0.129939E+09 | 104.36 | 09-SEP-20:49 | 21.70 | 15.69 |
| October | 0.497315E+09 | 6126.68 | 22-OCT-17:52 | 20.60 | 14.06 | 0.117081E+09 | 97.76 | 03-OCT-17:30 | 20.60 | 14.06 |
| November | 0.100849E+09 | 5268.55 | 05-NOV-17:42 | 19.45 | 17.51 | 92605473.15 | 88.49 | 05-NOV-17:30 | 19.45 | 17.51 |
| December | 38943374.20 | 1371.99 | 12-DEC-22:52 | 18.30 | 14.87 | 81625618.08 | 72.65 | 12-DEC-22:00 | 18.30 | 14.87 |
| Annual Sum or Average | 0.139815E+11 | 0.134520E+10 | ||||||||
| Minimum of Months | 17351775.76 | 128.31 | 6.02 | 1.58 | 79265021.02 | 57.14 | 16.82 | 10.02 | ||
| Maximum of Months | 0.306504E+10 | 6250.73 | 26.70 | 23.52 | 0.136364E+09 | 109.52 | 23.30 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.118695E+09 | 5269.54 | 29-JAN-17:52 | 14.40 | 5.85 | 82853599.17 | 83.06 | 29-JAN-17:00 | 14.40 | 5.85 |
| February | 0.238865E+09 | 5476.56 | 20-FEB-16:52 | 18.30 | 9.92 | 83261568.88 | 101.09 | 26-FEB-17:40 | 23.17 | 11.79 |
| March | 0.557563E+09 | 5655.67 | 14-MAR-19:52 | 14.40 | 8.86 | 0.110386E+09 | 108.08 | 14-MAR-17:30 | 14.40 | 8.86 |
| April | 0.110483E+10 | 5716.54 | 24-APR-15:42 | 20.50 | 13.54 | 0.125735E+09 | 117.02 | 09-APR-16:30 | 20.50 | 13.54 |
| May | 0.184109E+10 | 5696.43 | 09-MAY-15:32 | 22.80 | 12.34 | 0.133404E+09 | 111.96 | 07-MAY-09:50 | 22.80 | 12.34 |
| June | 0.275904E+10 | 5692.04 | 07-JUN-12:52 | 22.80 | 14.87 | 0.125373E+09 | 113.28 | 11-JUN-09:00 | 25.00 | 14.66 |
| July | 0.312714E+10 | 5044.58 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134531E+09 | 110.39 | 09-JUL-08:00 | 25.00 | 22.22 |
| August | 0.332090E+10 | 4806.71 | 08-AUG-17:52 | 26.70 | 23.52 | 0.127505E+09 | 108.34 | 31-AUG-17:49 | 22.80 | 20.15 |
| September | 0.206124E+10 | 5662.50 | 14-SEP-12:22 | 24.15 | 14.30 | 0.129692E+09 | 105.96 | 23-SEP-09:39 | 24.07 | 17.84 |
| October | 0.946057E+09 | 5669.36 | 03-OCT-14:02 | 21.78 | 13.31 | 0.122174E+09 | 115.71 | 07-OCT-15:30 | 23.85 | 13.02 |
| November | 0.322900E+09 | 5652.16 | 06-NOV-13:02 | 19.18 | 12.72 | 0.102662E+09 | 103.48 | 05-NOV-16:00 | 19.18 | 12.72 |
| December | 0.172381E+09 | 5424.53 | 10-DEC-16:52 | 17.20 | 8.59 | 87158241.75 | 93.87 | 10-DEC-16:40 | 17.20 | 8.59 |
| Annual Sum or Average | 0.165707E+11 | 0.136473E+10 | ||||||||
| Minimum of Months | 0.118695E+09 | 4806.71 | 14.40 | 5.85 | 82853599.17 | 83.06 | 14.40 | 5.85 | ||
| Maximum of Months | 0.332090E+10 | 5716.54 | 26.70 | 23.52 | 0.134531E+09 | 117.02 | 25.00 | 22.22 |
Report: ZoneCoolingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 14068378.04 | 93.89 | 31-JAN-24:00 | 10.30 | 8.37 | 79144124.38 | 57.15 | 31-JAN-21:10 | 10.30 | 8.37 |
| February | 65166101.81 | 5365.27 | 28-FEB-17:52 | 22.80 | 12.36 | 78784810.20 | 81.27 | 28-FEB-22:49 | 17.57 | 10.18 |
| March | 0.282870E+09 | 5552.37 | 14-MAR-19:52 | 14.40 | 8.86 | 0.106260E+09 | 94.47 | 28-MAR-20:40 | 22.57 | 17.40 |
| April | 0.812792E+09 | 5582.21 | 24-APR-17:22 | 20.85 | 13.50 | 0.123743E+09 | 99.97 | 20-APR-20:30 | 20.85 | 13.50 |
| May | 0.169198E+10 | 5614.24 | 14-MAY-11:22 | 24.15 | 15.36 | 0.136597E+09 | 104.00 | 27-MAY-20:19 | 21.50 | 18.76 |
| June | 0.272518E+10 | 5620.92 | 07-JUN-13:22 | 23.05 | 14.91 | 0.129670E+09 | 105.01 | 26-JUN-20:00 | 23.30 | 21.67 |
| July | 0.306483E+10 | 4985.04 | 02-JUL-21:52 | 22.80 | 18.09 | 0.133781E+09 | 105.00 | 25-JUL-20:49 | 22.80 | 21.95 |
| August | 0.306677E+10 | 4722.43 | 26-AUG-08:52 | 24.40 | 19.19 | 0.132470E+09 | 102.37 | 31-AUG-20:49 | 21.78 | 20.15 |
| September | 0.163464E+10 | 5584.53 | 14-SEP-12:22 | 24.15 | 14.30 | 0.129971E+09 | 101.68 | 09-SEP-20:49 | 24.15 | 14.30 |
| October | 0.480602E+09 | 5563.66 | 03-OCT-20:12 | 13.53 | 10.58 | 0.115641E+09 | 96.68 | 18-OCT-20:19 | 23.30 | 22.56 |
| November | 96826943.47 | 4695.55 | 05-NOV-17:42 | 19.45 | 17.51 | 91213436.67 | 82.83 | 03-NOV-21:00 | 19.45 | 17.51 |
| December | 34023700.97 | 1040.63 | 12-DEC-22:52 | 18.30 | 14.87 | 81213330.12 | 72.05 | 12-DEC-22:00 | 18.30 | 14.87 |
| Annual Sum or Average | 0.139698E+11 | 0.133849E+10 | ||||||||
| Minimum of Months | 14068378.04 | 93.89 | 10.30 | 8.37 | 78784810.20 | 57.15 | 10.30 | 8.37 | ||
| Maximum of Months | 0.306677E+10 | 5620.92 | 24.40 | 19.19 | 0.136597E+09 | 105.01 | 24.15 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 25169828.87 | 120.53 | 01-JAN-17:30 | 6.95 | 6.65 | 79700179.20 | 60.41 | 20-JAN-21:10 | 12.62 | 8.75 |
| February | 76214005.40 | 5010.63 | 28-FEB-22:52 | 17.30 | 10.02 | 81081390.25 | 84.46 | 28-FEB-22:00 | 17.30 | 10.02 |
| March | 0.308142E+09 | 5193.46 | 14-MAR-19:52 | 14.40 | 8.86 | 0.109978E+09 | 94.58 | 28-MAR-20:40 | 22.57 | 17.40 |
| April | 0.748686E+09 | 5200.09 | 24-APR-17:22 | 20.85 | 13.50 | 0.125662E+09 | 100.39 | 20-APR-20:30 | 20.85 | 13.50 |
| May | 0.144115E+10 | 5192.14 | 11-MAY-21:52 | 16.70 | 12.59 | 0.136437E+09 | 104.55 | 27-MAY-20:19 | 21.50 | 18.76 |
| June | 0.222597E+10 | 5167.93 | 07-JUN-18:02 | 23.12 | 13.70 | 0.129335E+09 | 104.61 | 26-JUN-20:00 | 23.30 | 21.67 |
| July | 0.248526E+10 | 4630.63 | 02-JUL-21:52 | 22.80 | 18.09 | 0.133663E+09 | 103.59 | 27-JUL-20:40 | 20.97 | 20.35 |
| August | 0.250964E+10 | 4301.31 | 08-AUG-17:52 | 26.70 | 23.52 | 0.132420E+09 | 103.32 | 31-AUG-20:49 | 21.78 | 20.15 |
| September | 0.140760E+10 | 5164.04 | 13-SEP-19:02 | 20.22 | 14.52 | 0.130531E+09 | 101.14 | 09-SEP-20:49 | 20.22 | 14.52 |
| October | 0.475600E+09 | 5165.41 | 03-OCT-20:12 | 13.53 | 10.58 | 0.119903E+09 | 96.63 | 18-OCT-20:19 | 23.30 | 22.56 |
| November | 0.139173E+09 | 4418.12 | 02-NOV-21:52 | 16.10 | 14.10 | 94926244.27 | 86.70 | 03-NOV-21:00 | 17.80 | 16.05 |
| December | 61026169.83 | 3068.14 | 12-DEC-22:52 | 18.30 | 14.87 | 82770461.50 | 75.84 | 12-DEC-22:00 | 18.30 | 14.87 |
| Annual Sum or Average | 0.119036E+11 | 0.135641E+10 | ||||||||
| Minimum of Months | 25169828.87 | 120.53 | 6.95 | 6.65 | 79700179.20 | 60.41 | 12.62 | 8.75 | ||
| Maximum of Months | 0.250964E+10 | 5200.09 | 26.70 | 23.52 | 0.136437E+09 | 104.61 | 23.30 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 25068029.04 | 120.55 | 01-JAN-17:30 | 6.95 | 6.65 | 79696693.28 | 60.34 | 31-JAN-22:40 | 13.37 | 10.31 |
| February | 76518596.44 | 4992.33 | 28-FEB-22:52 | 17.30 | 10.02 | 81069186.39 | 84.09 | 28-FEB-22:00 | 17.30 | 10.02 |
| March | 0.306422E+09 | 5170.81 | 14-MAR-19:52 | 14.40 | 8.86 | 0.109780E+09 | 94.66 | 28-MAR-20:40 | 22.57 | 17.40 |
| April | 0.750535E+09 | 5173.21 | 24-APR-21:02 | 13.22 | 9.86 | 0.125611E+09 | 100.41 | 20-APR-20:30 | 13.22 | 9.86 |
| May | 0.144724E+10 | 5175.95 | 11-MAY-21:52 | 16.70 | 12.59 | 0.136460E+09 | 104.22 | 27-MAY-20:19 | 21.50 | 18.76 |
| June | 0.223156E+10 | 5156.03 | 07-JUN-13:22 | 23.05 | 14.91 | 0.129345E+09 | 104.35 | 26-JUN-20:00 | 23.30 | 21.67 |
| July | 0.248911E+10 | 4613.36 | 02-JUL-21:52 | 22.80 | 18.09 | 0.133660E+09 | 103.54 | 27-JUL-20:40 | 20.97 | 20.35 |
| August | 0.251135E+10 | 4287.99 | 08-AUG-17:52 | 26.70 | 23.52 | 0.132418E+09 | 103.26 | 31-AUG-20:49 | 21.78 | 20.15 |
| September | 0.141095E+10 | 5146.23 | 13-SEP-19:02 | 20.22 | 14.52 | 0.130533E+09 | 100.96 | 09-SEP-20:49 | 20.22 | 14.52 |
| October | 0.476604E+09 | 5153.28 | 03-OCT-20:12 | 13.53 | 10.58 | 0.119865E+09 | 96.64 | 18-OCT-20:19 | 23.30 | 22.56 |
| November | 0.138190E+09 | 4395.24 | 02-NOV-21:52 | 16.10 | 14.10 | 94807494.20 | 86.72 | 03-NOV-21:00 | 17.80 | 16.05 |
| December | 60760042.35 | 3015.06 | 12-DEC-22:52 | 18.30 | 14.87 | 82738890.53 | 75.74 | 12-DEC-22:00 | 18.30 | 14.87 |
| Annual Sum or Average | 0.119243E+11 | 0.135598E+10 | ||||||||
| Minimum of Months | 25068029.04 | 120.55 | 6.95 | 6.65 | 79696693.28 | 60.34 | 13.22 | 9.86 | ||
| Maximum of Months | 0.251135E+10 | 5175.95 | 26.70 | 23.52 | 0.136460E+09 | 104.35 | 23.30 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.177665E+09 | 4955.65 | 29-JAN-17:52 | 14.40 | 5.85 | 85773923.49 | 86.45 | 29-JAN-17:00 | 14.40 | 5.85 |
| February | 0.280217E+09 | 5150.31 | 20-FEB-18:42 | 14.87 | 8.36 | 87564110.45 | 103.05 | 20-FEB-18:30 | 14.87 | 8.36 |
| March | 0.610471E+09 | 5310.60 | 14-MAR-19:52 | 14.40 | 8.86 | 0.115948E+09 | 107.16 | 14-MAR-17:30 | 14.40 | 8.86 |
| April | 0.103984E+10 | 5333.47 | 24-APR-15:42 | 20.50 | 13.54 | 0.128155E+09 | 114.66 | 09-APR-16:30 | 20.50 | 13.54 |
| May | 0.159194E+10 | 5279.98 | 09-MAY-15:32 | 22.80 | 12.34 | 0.133456E+09 | 108.40 | 01-MAY-17:40 | 22.80 | 12.34 |
| June | 0.226181E+10 | 5248.52 | 07-JUN-18:02 | 23.12 | 13.70 | 0.125064E+09 | 107.33 | 26-JUN-17:00 | 23.30 | 21.67 |
| July | 0.255067E+10 | 4700.16 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134394E+09 | 106.50 | 27-JUL-19:10 | 21.70 | 20.50 |
| August | 0.276519E+10 | 4435.47 | 08-AUG-17:52 | 26.70 | 23.52 | 0.127458E+09 | 107.12 | 31-AUG-17:49 | 22.80 | 20.15 |
| September | 0.183607E+10 | 5283.07 | 13-SEP-13:42 | 23.98 | 15.53 | 0.130496E+09 | 103.97 | 02-SEP-16:40 | 23.98 | 15.53 |
| October | 0.963036E+09 | 5282.86 | 05-OCT-14:52 | 20.60 | 15.46 | 0.127215E+09 | 113.77 | 07-OCT-15:30 | 23.85 | 13.02 |
| November | 0.425984E+09 | 5279.26 | 06-NOV-13:02 | 19.18 | 12.72 | 0.109143E+09 | 104.05 | 02-NOV-17:10 | 19.18 | 12.72 |
| December | 0.249974E+09 | 5077.88 | 10-DEC-16:52 | 17.20 | 8.59 | 91821323.41 | 97.80 | 10-DEC-16:40 | 17.20 | 8.59 |
| Annual Sum or Average | 0.147529E+11 | 0.139649E+10 | ||||||||
| Minimum of Months | 0.177665E+09 | 4435.47 | 14.40 | 5.85 | 85773923.49 | 86.45 | 14.40 | 5.85 | ||
| Maximum of Months | 0.276519E+10 | 5333.47 | 26.70 | 23.52 | 0.134394E+09 | 114.66 | 23.98 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.178294E+09 | 4940.83 | 29-JAN-17:52 | 14.40 | 5.85 | 85738445.94 | 86.33 | 29-JAN-17:00 | 14.40 | 5.85 |
| February | 0.281984E+09 | 5133.34 | 20-FEB-18:42 | 14.87 | 8.36 | 87544224.78 | 102.71 | 20-FEB-18:30 | 14.87 | 8.36 |
| March | 0.611006E+09 | 5293.93 | 14-MAR-19:52 | 14.40 | 8.86 | 0.115806E+09 | 107.19 | 14-MAR-17:30 | 14.40 | 8.86 |
| April | 0.104317E+10 | 5321.76 | 24-APR-15:42 | 20.50 | 13.54 | 0.128093E+09 | 114.86 | 09-APR-16:30 | 20.50 | 13.54 |
| May | 0.159760E+10 | 5265.54 | 09-MAY-15:32 | 22.80 | 12.34 | 0.133458E+09 | 107.96 | 01-MAY-17:40 | 22.80 | 12.34 |
| June | 0.226775E+10 | 5232.83 | 07-JUN-18:02 | 23.12 | 13.70 | 0.125073E+09 | 107.14 | 07-JUN-17:00 | 23.12 | 13.70 |
| July | 0.255411E+10 | 4686.93 | 02-JUL-21:52 | 22.80 | 18.09 | 0.134357E+09 | 106.44 | 27-JUL-19:10 | 21.70 | 20.50 |
| August | 0.276697E+10 | 4425.05 | 08-AUG-17:52 | 26.70 | 23.52 | 0.127456E+09 | 107.08 | 31-AUG-17:49 | 22.80 | 20.15 |
| September | 0.183914E+10 | 5270.51 | 13-SEP-13:42 | 23.98 | 15.53 | 0.130485E+09 | 103.96 | 02-SEP-16:40 | 23.98 | 15.53 |
| October | 0.965940E+09 | 5269.36 | 03-OCT-14:02 | 21.78 | 13.31 | 0.127197E+09 | 114.10 | 07-OCT-15:30 | 23.85 | 13.02 |
| November | 0.426303E+09 | 5266.63 | 06-NOV-13:02 | 19.18 | 12.72 | 0.109047E+09 | 103.94 | 02-NOV-17:10 | 19.18 | 12.72 |
| December | 0.251374E+09 | 5061.89 | 10-DEC-16:52 | 17.20 | 8.59 | 91790978.99 | 97.75 | 10-DEC-16:40 | 17.20 | 8.59 |
| Annual Sum or Average | 0.147837E+11 | 0.139605E+10 | ||||||||
| Minimum of Months | 0.178294E+09 | 4425.05 | 14.40 | 5.85 | 85738445.94 | 86.33 | 14.40 | 5.85 | ||
| Maximum of Months | 0.276697E+10 | 5321.76 | 26.70 | 23.52 | 0.134357E+09 | 114.86 | 23.98 | 20.50 |
Report: ZoneCoolingSummaryMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 | 0.121444E+09 | 114.41 | 31-JAN-21:10 | 16.82 | 12.20 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 | 0.138053E+09 | 155.49 | 28-FEB-21:10 | 20.32 | 11.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.51 | 0.212631E+09 | 165.98 | 14-MAR-20:10 | 13.95 | 8.71 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.82 | 0.245160E+09 | 174.56 | 22-APR-20:10 | 19.40 | 17.21 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.278716E+09 | 177.11 | 27-MAY-20:40 | 21.30 | 18.78 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 | 0.278298E+09 | 179.68 | 26-JUN-20:10 | 22.88 | 21.59 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 | 0.293444E+09 | 178.69 | 07-JUL-20:10 | 31.02 | 23.15 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 | 0.292507E+09 | 177.34 | 31-AUG-20:10 | 22.12 | 20.22 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.46 | 0.267854E+09 | 175.15 | 09-SEP-20:10 | 22.80 | 21.19 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 | 0.232899E+09 | 166.47 | 03-OCT-20:10 | 13.72 | 10.57 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.60 | 0.179648E+09 | 159.18 | 05-NOV-20:10 | 16.70 | 16.70 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 | 0.140593E+09 | 138.06 | 12-DEC-21:10 | 18.30 | 14.62 |
| Annual Sum or Average | 0.00 | 0.268125E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.121444E+09 | 114.41 | 13.72 | 8.71 | ||
| Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.293444E+09 | 179.68 | 31.02 | 23.15 |
Report: ZoneCoolingSummaryMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 | 0.126649E+09 | 115.52 | 31-JAN-22:40 | 13.37 | 10.31 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 | 0.142459E+09 | 153.27 | 28-FEB-22:40 | 17.83 | 10.34 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.51 | 0.228199E+09 | 162.36 | 30-MAR-22:30 | 22.25 | 16.14 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.82 | 0.257459E+09 | 172.47 | 17-APR-22:10 | 19.72 | 13.80 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.300244E+09 | 180.28 | 21-MAY-21:40 | 21.10 | 18.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 | 0.319362E+09 | 205.55 | 06-JUN-17:10 | 33.72 | 21.43 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 | 0.341222E+09 | 217.00 | 08-JUL-17:10 | 34.40 | 23.36 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 | 0.344482E+09 | 214.55 | 01-AUG-17:10 | 34.72 | 23.57 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.46 | 0.314878E+09 | 192.89 | 09-SEP-21:49 | 22.80 | 21.51 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 | 0.282540E+09 | 186.62 | 11-OCT-21:40 | 14.97 | 9.20 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.60 | 0.233200E+09 | 173.87 | 05-NOV-21:40 | 15.97 | 15.97 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 | 0.175675E+09 | 146.77 | 13-DEC-22:40 | 12.97 | 12.59 |
| Annual Sum or Average | 0.00 | 0.306637E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.126649E+09 | 115.52 | 12.97 | 9.20 | ||
| Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.344482E+09 | 217.00 | 34.72 | 23.57 |
Report: ZoneCoolingSummaryMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 | 0.171458E+09 | 123.95 | 31-JAN-21:30 | 16.05 | 11.74 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 | 0.181977E+09 | 159.76 | 28-FEB-21:19 | 20.03 | 11.51 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.51 | 0.261997E+09 | 161.90 | 14-MAR-20:10 | 13.95 | 8.71 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.82 | 0.268345E+09 | 166.97 | 22-APR-20:10 | 19.40 | 17.21 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.287588E+09 | 168.35 | 27-MAY-20:49 | 21.20 | 18.80 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 | 0.278141E+09 | 167.28 | 07-JUN-20:10 | 20.32 | 12.95 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 | 0.289610E+09 | 166.47 | 29-JUL-20:40 | 20.77 | 20.77 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 | 0.287790E+09 | 165.80 | 31-AUG-21:19 | 21.67 | 19.98 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.46 | 0.276578E+09 | 166.35 | 02-SEP-21:19 | 22.20 | 20.95 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 | 0.271903E+09 | 163.48 | 15-OCT-21:10 | 19.03 | 16.06 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.60 | 0.239000E+09 | 158.87 | 05-NOV-20:10 | 16.70 | 16.70 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 | 0.198776E+09 | 143.62 | 13-DEC-21:40 | 13.50 | 13.12 |
| Annual Sum or Average | 0.00 | 0.301316E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.171458E+09 | 123.95 | 13.50 | 8.71 | ||
| Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.289610E+09 | 168.35 | 22.20 | 20.95 |
Report: ZoneHeatingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.379079E+09 | 883.22 | 08-JAN-02:70 | -5.6 |
| February | 0.240679E+09 | 1110.48 | 12-FEB-06:00 | -12.2 |
| March | 568831.53 | 38.16 | 11-MAR-13:45 | 24.72 |
| April | 1284486.49 | 48.17 | 17-APR-11:05 | 25.78 |
| May | 1366872.40 | 55.21 | 30-MAY-08:45 | 26.23 |
| June | 1353220.93 | 58.23 | 30-JUN-09:00 | 27.20 |
| July | 670565.92 | 52.96 | 13-JUL-08:00 | 26.70 |
| August | 472893.36 | 47.47 | 29-AUG-08:37 | 25.93 |
| September | 383401.88 | 47.86 | 08-SEP-08:57 | 26.10 |
| October | 223179.86 | 37.51 | 18-OCT-13:57 | 25.00 |
| November | 37372.17 | 21.49 | 02-NOV-14:15 | 23.13 |
| December | 2170871.70 | 117.24 | 26-DEC-08:25 | 3.30 |
| Annual Sum or Average | 0.628290E+09 | |||
| Minimum of Months | 37372.17 | 21.49 | -12.2 | |
| Maximum of Months | 0.379079E+09 | 1110.48 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.891772E+09 | 997.80 | 08-JAN-02:70 | -5.6 |
| February | 0.564079E+09 | 1252.30 | 12-FEB-06:00 | -12.2 |
| March | 3723734.08 | 90.37 | 23-MAR-03:00 | 5.00 |
| April | 2956295.66 | 54.20 | 14-APR-11:53 | 26.10 |
| May | 1781629.77 | 55.18 | 20-MAY-09:55 | 26.10 |
| June | 929402.07 | 50.49 | 09-JUN-10:25 | 25.55 |
| July | 415216.95 | 50.15 | 13-JUL-07:47 | 26.13 |
| August | 427505.01 | 45.37 | 18-AUG-07:47 | 25.73 |
| September | 687835.31 | 54.22 | 09-SEP-08:27 | 26.65 |
| October | 464866.46 | 55.08 | 10-OCT-11:05 | 26.38 |
| November | 271094.08 | 35.09 | 19-NOV-15:35 | 24.07 |
| December | 0.110180E+09 | 391.56 | 04-DEC-08:13 | -2.2 |
| Annual Sum or Average | 0.157769E+10 | |||
| Minimum of Months | 271094.08 | 35.09 | -12.2 | |
| Maximum of Months | 0.891772E+09 | 1252.30 | 26.65 |
Report: ZoneHeatingSummaryMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.321528E+09 | 8872.99 | 05-JAN-07:01 | -2.8 |
| February | 0.236188E+09 | 9086.83 | 14-FEB-07:01 | 1.02 |
| March | 98553609.37 | 5237.71 | 23-MAR-06:01 | 6.10 |
| April | 0.171687E+09 | 521.12 | 17-APR-16:12 | 28.70 |
| May | 0.263936E+09 | 598.61 | 19-MAY-16:12 | 30.60 |
| June | 0.397217E+09 | 718.27 | 06-JUN-16:12 | 33.90 |
| July | 0.436369E+09 | 760.77 | 07-JUL-16:13 | 35.40 |
| August | 0.421158E+09 | 751.44 | 01-AUG-16:13 | 35.00 |
| September | 0.266229E+09 | 582.60 | 07-SEP-16:13 | 31.33 |
| October | 91630395.75 | 509.96 | 10-OCT-16:13 | 29.63 |
| November | 40303833.51 | 5349.09 | 22-NOV-07:01 | -3.2 |
| December | 35781225.26 | 8491.97 | 04-DEC-07:01 | -3.3 |
| Annual Sum or Average | 0.278058E+10 | |||
| Minimum of Months | 35781225.26 | 509.96 | -3.3 | |
| Maximum of Months | 0.436369E+09 | 9086.83 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.887751E+09 | 1007.75 | 08-JAN-02:70 | -5.6 |
| February | 0.555985E+09 | 1267.34 | 12-FEB-06:00 | -12.2 |
| March | 4005817.05 | 101.30 | 23-MAR-03:00 | 5.00 |
| April | 2642025.80 | 59.14 | 16-APR-11:15 | 26.47 |
| May | 1130279.90 | 57.40 | 23-MAY-15:07 | 27.12 |
| June | 420236.81 | 50.20 | 22-JUN-07:57 | 26.10 |
| July | 286220.50 | 49.25 | 13-JUL-07:47 | 26.13 |
| August | 361049.08 | 53.80 | 08-AUG-17:57 | 26.70 |
| September | 524769.24 | 55.90 | 09-SEP-08:27 | 26.65 |
| October | 312978.62 | 50.11 | 10-OCT-11:07 | 26.38 |
| November | 298711.55 | 33.86 | 19-NOV-15:35 | 24.07 |
| December | 0.100104E+09 | 398.33 | 04-DEC-05:00 | -2.8 |
| Annual Sum or Average | 0.155382E+10 | |||
| Minimum of Months | 286220.50 | 33.86 | -12.2 | |
| Maximum of Months | 0.887751E+09 | 1267.34 | 27.12 |
Report: ZoneHeatingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.300706E+09 | 501.07 | 08-JAN-02:70 | -5.6 |
| February | 0.198986E+09 | 633.76 | 12-FEB-08:12 | -11.7 |
| March | 1450254.28 | 47.03 | 11-MAR-14:30 | 25.55 |
| April | 2411136.13 | 54.71 | 16-APR-11:15 | 26.47 |
| May | 1830148.08 | 58.55 | 23-MAY-15:07 | 27.12 |
| June | 916142.53 | 53.24 | 29-JUN-09:07 | 26.57 |
| July | 495255.24 | 53.69 | 13-JUL-08:00 | 26.70 |
| August | 671218.59 | 55.89 | 08-AUG-17:57 | 26.70 |
| September | 837024.85 | 58.68 | 09-SEP-08:40 | 27.20 |
| October | 582501.44 | 52.66 | 09-OCT-12:55 | 26.10 |
| November | 199529.29 | 31.21 | 19-NOV-15:35 | 24.07 |
| December | 180669.52 | 15.18 | 12-DEC-14:23 | 22.80 |
| Annual Sum or Average | 0.509266E+09 | |||
| Minimum of Months | 180669.52 | 15.18 | -11.7 | |
| Maximum of Months | 0.300706E+09 | 633.76 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.300961E+09 | 501.13 | 08-JAN-02:70 | -5.6 |
| February | 0.198720E+09 | 633.73 | 12-FEB-08:12 | -11.7 |
| March | 1444599.77 | 47.11 | 11-MAR-14:30 | 25.55 |
| April | 2393612.95 | 55.02 | 16-APR-11:15 | 26.47 |
| May | 1809791.15 | 58.67 | 23-MAY-15:07 | 27.12 |
| June | 900788.60 | 53.39 | 29-JUN-09:07 | 26.57 |
| July | 481970.44 | 53.68 | 13-JUL-08:00 | 26.70 |
| August | 649685.34 | 55.92 | 08-AUG-17:57 | 26.70 |
| September | 818925.75 | 58.62 | 09-SEP-08:40 | 27.20 |
| October | 573622.39 | 52.56 | 09-OCT-12:55 | 26.10 |
| November | 200857.30 | 31.24 | 19-NOV-15:35 | 24.07 |
| December | 180655.76 | 15.19 | 12-DEC-14:23 | 22.80 |
| Annual Sum or Average | 0.509136E+09 | |||
| Minimum of Months | 180655.76 | 15.19 | -11.7 | |
| Maximum of Months | 0.300961E+09 | 633.73 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 55540083.18 | 363.38 | 08-JAN-02:20 | -5.6 |
| February | 27970778.45 | 458.49 | 12-FEB-06:00 | -12.2 |
| March | 469436.01 | 41.58 | 29-MAR-14:25 | 25.00 |
| April | 1050936.16 | 51.66 | 17-APR-11:05 | 25.78 |
| May | 1346020.92 | 58.39 | 23-MAY-14:57 | 27.20 |
| June | 1327764.87 | 59.03 | 30-JUN-09:00 | 27.20 |
| July | 908977.47 | 54.09 | 01-JUL-08:50 | 26.73 |
| August | 572479.56 | 54.73 | 08-AUG-17:57 | 26.70 |
| September | 381278.09 | 50.05 | 08-SEP-08:57 | 26.10 |
| October | 227025.90 | 50.92 | 10-OCT-11:07 | 26.38 |
| November | 33418.78 | 27.83 | 19-NOV-15:17 | 24.23 |
| December | 2213.43 | 3.01 | 12-DEC-15:00 | 22.80 |
| Annual Sum or Average | 89830412.81 | |||
| Minimum of Months | 2213.43 | 3.01 | -12.2 | |
| Maximum of Months | 55540083.18 | 458.49 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.100666E+09 | 493.19 | 08-JAN-03:00 | -5.6 |
| February | 46039012.33 | 565.00 | 12-FEB-06:00 | -12.2 |
| March | 471655.88 | 41.76 | 29-MAR-14:25 | 25.00 |
| April | 996949.15 | 51.05 | 17-APR-11:05 | 25.78 |
| May | 1232681.13 | 58.64 | 23-MAY-14:57 | 27.20 |
| June | 1004779.80 | 58.66 | 30-JUN-09:00 | 27.20 |
| July | 473512.63 | 53.12 | 13-JUL-08:00 | 26.70 |
| August | 472028.36 | 54.57 | 08-AUG-17:57 | 26.70 |
| September | 381689.12 | 50.65 | 08-SEP-08:57 | 26.10 |
| October | 215266.39 | 50.61 | 10-OCT-11:07 | 26.38 |
| November | 36759.41 | 27.62 | 19-NOV-15:17 | 24.23 |
| December | 2796.41 | 3.88 | 12-DEC-15:00 | 22.80 |
| Annual Sum or Average | 0.151993E+09 | |||
| Minimum of Months | 2796.41 | 3.88 | -12.2 | |
| Maximum of Months | 0.100666E+09 | 565.00 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.204461E+09 | 843.47 | 08-JAN-02:70 | -5.6 |
| February | 96065224.03 | 1070.51 | 12-FEB-06:00 | -12.2 |
| March | 144928.07 | 42.56 | 29-MAR-14:25 | 25.00 |
| April | 355173.11 | 50.78 | 17-APR-11:05 | 25.78 |
| May | 622941.90 | 66.55 | 23-MAY-14:55 | 27.20 |
| June | 884223.57 | 59.03 | 05-JUN-09:05 | 26.57 |
| July | 703045.56 | 49.06 | 26-JUL-09:57 | 26.10 |
| August | 702528.26 | 61.34 | 08-AUG-17:55 | 26.70 |
| September | 475612.02 | 46.17 | 09-SEP-08:05 | 25.55 |
| October | 248279.75 | 55.05 | 10-OCT-11:05 | 26.38 |
| November | 43912.81 | 33.62 | 19-NOV-15:15 | 24.23 |
| December | 4849994.75 | 213.47 | 26-DEC-05:00 | 3.90 |
| Annual Sum or Average | 0.309557E+09 | |||
| Minimum of Months | 43912.81 | 33.62 | -12.2 | |
| Maximum of Months | 0.204461E+09 | 1070.51 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.603800E+09 | 942.22 | 08-JAN-02:70 | -5.6 |
| February | 0.340114E+09 | 1232.07 | 12-FEB-06:00 | -12.2 |
| March | 318637.29 | 51.34 | 30-MAR-12:25 | 25.85 |
| April | 984040.12 | 56.30 | 16-APR-11:15 | 26.47 |
| May | 782506.22 | 64.43 | 23-MAY-15:05 | 27.12 |
| June | 611673.00 | 53.12 | 05-JUN-08:55 | 26.10 |
| July | 415883.46 | 45.50 | 26-JUL-09:47 | 25.73 |
| August | 724171.78 | 59.80 | 25-AUG-09:35 | 26.67 |
| September | 1028881.00 | 58.09 | 09-SEP-08:25 | 26.65 |
| October | 537562.97 | 56.38 | 10-OCT-11:05 | 26.38 |
| November | 5634737.54 | 264.64 | 22-NOV-06:00 | -3.3 |
| December | 0.134449E+09 | 506.86 | 03-DEC-09:00 | -1.1 |
| Annual Sum or Average | 0.108940E+10 | |||
| Minimum of Months | 318637.29 | 45.50 | -12.2 | |
| Maximum of Months | 0.603800E+09 | 1232.07 | 27.12 |
Report: ZoneHeatingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.206959E+09 | 856.67 | 08-JAN-02:70 | -5.6 |
| February | 97151772.65 | 1084.98 | 12-FEB-06:00 | -12.2 |
| March | 143560.35 | 41.93 | 29-MAR-14:25 | 25.00 |
| April | 323840.19 | 49.33 | 17-APR-11:05 | 25.78 |
| May | 411018.40 | 63.90 | 23-MAY-14:55 | 27.20 |
| June | 461247.29 | 54.47 | 25-JUN-08:57 | 26.70 |
| July | 363399.97 | 49.82 | 01-JUL-08:37 | 26.27 |
| August | 506560.62 | 43.44 | 18-AUG-07:47 | 25.73 |
| September | 322104.63 | 46.24 | 08-SEP-08:57 | 26.10 |
| October | 198311.39 | 36.24 | 18-OCT-13:57 | 25.00 |
| November | 54017.64 | 33.27 | 19-NOV-15:15 | 24.23 |
| December | 4688405.45 | 212.21 | 26-DEC-05:00 | 3.90 |
| Annual Sum or Average | 0.311583E+09 | |||
| Minimum of Months | 54017.64 | 33.27 | -12.2 | |
| Maximum of Months | 0.206959E+09 | 1084.98 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.592340E+09 | 957.13 | 08-JAN-02:70 | -5.6 |
| February | 0.327922E+09 | 1250.98 | 12-FEB-06:00 | -12.2 |
| March | 349049.08 | 45.66 | 11-MAR-14:15 | 25.37 |
| April | 642273.48 | 59.99 | 16-APR-11:15 | 26.47 |
| May | 485365.18 | 51.14 | 03-MAY-15:05 | 25.92 |
| June | 375305.45 | 53.54 | 29-JUN-09:07 | 26.57 |
| July | 277524.59 | 48.63 | 13-JUL-07:47 | 26.13 |
| August | 495366.45 | 44.20 | 18-AUG-07:47 | 25.73 |
| September | 604692.74 | 52.59 | 09-SEP-08:27 | 26.65 |
| October | 341848.88 | 54.23 | 09-OCT-12:55 | 26.10 |
| November | 3670583.17 | 231.02 | 22-NOV-06:00 | -3.3 |
| December | 0.122367E+09 | 523.39 | 03-DEC-07:00 | -3.3 |
| Annual Sum or Average | 0.104987E+10 | |||
| Minimum of Months | 277524.59 | 44.20 | -12.2 | |
| Maximum of Months | 0.592340E+09 | 1250.98 | 26.65 |
Report: ZoneHeatingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.124482E+09 | 402.67 | 08-JAN-02:70 | -5.6 |
| February | 69251819.62 | 526.67 | 12-FEB-06:00 | -12.2 |
| March | 397572.34 | 45.46 | 11-MAR-14:15 | 25.37 |
| April | 1049964.16 | 58.24 | 16-APR-11:15 | 26.47 |
| May | 875587.86 | 52.70 | 16-MAY-10:55 | 26.10 |
| June | 798126.65 | 51.14 | 29-JUN-09:07 | 26.57 |
| July | 568544.17 | 48.90 | 13-JUL-07:47 | 26.13 |
| August | 895988.51 | 46.60 | 29-AUG-08:37 | 25.93 |
| September | 1144521.93 | 54.98 | 24-SEP-10:05 | 26.38 |
| October | 619156.54 | 55.11 | 10-OCT-11:05 | 26.38 |
| November | 217785.71 | 33.08 | 19-NOV-15:35 | 24.07 |
| December | 867024.09 | 69.31 | 04-DEC-05:00 | -2.8 |
| Annual Sum or Average | 0.201168E+09 | |||
| Minimum of Months | 217785.71 | 33.08 | -12.2 | |
| Maximum of Months | 0.124482E+09 | 526.67 | 26.57 |
Report: ZoneHeatingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.124498E+09 | 402.95 | 08-JAN-02:70 | -5.6 |
| February | 69182117.45 | 527.74 | 12-FEB-06:00 | -12.2 |
| March | 395631.03 | 45.51 | 11-MAR-14:15 | 25.37 |
| April | 1030109.34 | 58.61 | 16-APR-11:15 | 26.47 |
| May | 856254.55 | 52.44 | 16-MAY-10:55 | 26.10 |
| June | 784473.33 | 51.32 | 29-JUN-09:07 | 26.57 |
| July | 559914.65 | 48.97 | 13-JUL-07:47 | 26.13 |
| August | 889234.49 | 44.04 | 18-AUG-07:47 | 25.73 |
| September | 1131480.35 | 54.77 | 24-SEP-10:05 | 26.38 |
| October | 607827.38 | 54.88 | 10-OCT-11:05 | 26.38 |
| November | 217511.81 | 33.10 | 19-NOV-15:35 | 24.07 |
| December | 915440.76 | 71.65 | 04-DEC-05:00 | -2.8 |
| Annual Sum or Average | 0.201068E+09 | |||
| Minimum of Months | 217511.81 | 33.10 | -12.2 | |
| Maximum of Months | 0.124498E+09 | 527.74 | 26.57 |
Report: ZoneHeatingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 19659834.07 | 277.81 | 08-JAN-02:70 | -5.6 |
| February | 5106158.37 | 302.18 | 12-FEB-06:00 | -12.2 |
| March | 129357.11 | 36.76 | 11-MAR-13:45 | 24.72 |
| April | 358520.52 | 51.43 | 17-APR-11:05 | 25.78 |
| May | 734758.97 | 52.44 | 16-MAY-10:55 | 26.10 |
| June | 1060742.41 | 55.99 | 25-JUN-08:57 | 26.70 |
| July | 853451.40 | 50.94 | 01-JUL-08:37 | 26.27 |
| August | 843586.68 | 43.53 | 07-AUG-07:57 | 25.60 |
| September | 476546.85 | 47.26 | 08-SEP-08:57 | 26.10 |
| October | 229403.33 | 37.40 | 18-OCT-13:57 | 25.00 |
| November | 22829.95 | 13.30 | 02-NOV-15:55 | 22.20 |
| December | 3167.89 | 16.77 | 12-DEC-14:45 | 22.80 |
| Annual Sum or Average | 29478357.52 | |||
| Minimum of Months | 3167.89 | 13.30 | -12.2 | |
| Maximum of Months | 19659834.07 | 302.18 | 26.70 |
Report: ZoneHeatingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 19593963.83 | 277.63 | 08-JAN-02:70 | -5.6 |
| February | 5153375.68 | 303.24 | 12-FEB-06:00 | -12.2 |
| March | 129060.30 | 36.64 | 11-MAR-13:45 | 24.72 |
| April | 350950.66 | 51.48 | 17-APR-11:05 | 25.78 |
| May | 718688.63 | 52.20 | 16-MAY-10:55 | 26.10 |
| June | 1040441.25 | 56.10 | 25-JUN-08:57 | 26.70 |
| July | 844295.94 | 50.82 | 01-JUL-08:37 | 26.27 |
| August | 839933.06 | 43.63 | 07-AUG-07:57 | 25.60 |
| September | 472196.51 | 47.47 | 08-SEP-08:57 | 26.10 |
| October | 224314.25 | 37.45 | 18-OCT-13:57 | 25.00 |
| November | 25351.80 | 13.40 | 02-NOV-15:55 | 22.20 |
| December | 2219.84 | 11.00 | 12-DEC-16:25 | 21.95 |
| Annual Sum or Average | 29394791.75 | |||
| Minimum of Months | 2219.84 | 11.00 | -12.2 | |
| Maximum of Months | 19593963.83 | 303.24 | 26.70 |
Report: ZoneHeatingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.134772E+10 | 1819.93 | 08-JAN-02:70 | -5.6 |
| February | 0.774317E+09 | 2520.13 | 12-FEB-06:00 | -12.2 |
| March | 86111292.75 | 672.88 | 18-MAR-07:02 | 2.30 |
| April | 26529550.70 | 675.30 | 06-APR-06:00 | 1.10 |
| May | 549211.64 | 61.43 | 23-MAY-14:55 | 27.20 |
| June | 743257.05 | 62.14 | 05-JUN-09:05 | 26.57 |
| July | 677743.47 | 52.85 | 13-JUL-07:45 | 26.13 |
| August | 795548.91 | 61.99 | 25-AUG-09:35 | 26.67 |
| September | 570124.13 | 53.08 | 08-SEP-08:55 | 26.10 |
| October | 44603703.68 | 666.75 | 26-OCT-06:00 | 2.20 |
| November | 0.216512E+09 | 1375.04 | 21-NOV-07:00 | -2.8 |
| December | 0.752663E+09 | 1489.21 | 01-DEC-07:00 | -3.9 |
| Annual Sum or Average | 0.325179E+10 | |||
| Minimum of Months | 549211.64 | 52.85 | -12.2 | |
| Maximum of Months | 0.134772E+10 | 2520.13 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.196197E+10 | 1927.35 | 14-JAN-07:00 | -6.7 |
| February | 0.113556E+10 | 2595.70 | 12-FEB-06:00 | -12.2 |
| March | 0.161934E+09 | 857.56 | 18-MAR-07:23 | 2.50 |
| April | 42150218.31 | 746.42 | 06-APR-06:00 | 1.10 |
| May | 588324.95 | 56.74 | 06-MAY-09:55 | 26.10 |
| June | 532240.51 | 57.59 | 05-JUN-08:55 | 26.10 |
| July | 377138.01 | 50.03 | 03-JUL-08:45 | 25.40 |
| August | 710991.53 | 61.95 | 25-AUG-09:35 | 26.67 |
| September | 1094335.67 | 60.17 | 09-SEP-08:25 | 26.65 |
| October | 68698935.00 | 872.23 | 26-OCT-06:00 | 2.20 |
| November | 0.441093E+09 | 1577.27 | 22-NOV-06:00 | -3.3 |
| December | 0.122937E+10 | 1664.25 | 18-DEC-07:00 | -5.0 |
| Annual Sum or Average | 0.504408E+10 | |||
| Minimum of Months | 377138.01 | 50.03 | -12.2 | |
| Maximum of Months | 0.196197E+10 | 2595.70 | 26.67 |
Report: ZoneHeatingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.133425E+10 | 1837.99 | 08-JAN-02:70 | -5.6 |
| February | 0.763915E+09 | 2525.08 | 12-FEB-06:00 | -12.2 |
| March | 84390381.83 | 711.34 | 18-MAR-06:50 | 2.30 |
| April | 22761905.54 | 692.62 | 06-APR-06:00 | 1.10 |
| May | 275996.14 | 49.58 | 15-MAY-10:55 | 25.60 |
| June | 323544.53 | 53.33 | 06-JUN-08:55 | 26.10 |
| July | 314180.07 | 48.70 | 06-JUL-07:47 | 26.23 |
| August | 548564.75 | 58.25 | 25-AUG-09:35 | 26.67 |
| September | 276240.66 | 45.68 | 06-SEP-08:37 | 25.93 |
| October | 43971906.93 | 704.07 | 26-OCT-06:00 | 2.20 |
| November | 0.206256E+09 | 1365.40 | 21-NOV-07:00 | -2.8 |
| December | 0.733681E+09 | 1483.15 | 01-DEC-07:00 | -3.9 |
| Annual Sum or Average | 0.319097E+10 | |||
| Minimum of Months | 275996.14 | 45.68 | -12.2 | |
| Maximum of Months | 0.133425E+10 | 2525.08 | 26.67 |
Report: ZoneHeatingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.194924E+10 | 1940.79 | 14-JAN-07:00 | -6.7 |
| February | 0.111281E+10 | 2598.70 | 12-FEB-06:00 | -12.2 |
| March | 0.150318E+09 | 864.67 | 18-MAR-06:50 | 2.30 |
| April | 36919038.33 | 770.35 | 06-APR-06:00 | 1.10 |
| May | 348397.68 | 50.62 | 15-MAY-10:55 | 25.60 |
| June | 292870.50 | 50.21 | 03-JUN-08:55 | 25.60 |
| July | 251643.32 | 48.50 | 13-JUL-07:47 | 26.13 |
| August | 511524.20 | 58.38 | 25-AUG-09:35 | 26.67 |
| September | 494106.64 | 55.16 | 24-SEP-10:05 | 26.38 |
| October | 66369943.67 | 926.97 | 26-OCT-06:00 | 2.20 |
| November | 0.414674E+09 | 1569.09 | 22-NOV-06:00 | -3.3 |
| December | 0.119102E+10 | 1668.43 | 18-DEC-07:00 | -5.0 |
| Annual Sum or Average | 0.492325E+10 | |||
| Minimum of Months | 251643.32 | 48.50 | -12.2 | |
| Maximum of Months | 0.194924E+10 | 2598.70 | 26.67 |
Report: ZoneHeatingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.117544E+10 | 1246.37 | 14-JAN-07:00 | -6.7 |
| February | 0.659896E+09 | 1720.27 | 12-FEB-06:00 | -12.2 |
| March | 50676177.94 | 508.46 | 19-MAR-07:23 | 2.50 |
| April | 11502417.69 | 297.05 | 06-APR-06:00 | 1.10 |
| May | 588588.74 | 55.98 | 16-MAY-10:55 | 26.10 |
| June | 551287.49 | 52.99 | 05-JUN-08:55 | 26.10 |
| July | 385270.07 | 49.39 | 13-JUL-07:47 | 26.13 |
| August | 745644.74 | 60.04 | 25-AUG-09:35 | 26.67 |
| September | 1068507.70 | 57.62 | 09-SEP-08:25 | 26.65 |
| October | 19178801.01 | 474.69 | 26-OCT-06:00 | 2.20 |
| November | 0.184809E+09 | 1008.54 | 22-NOV-06:00 | -3.3 |
| December | 0.652972E+09 | 1094.90 | 18-DEC-05:00 | -5.0 |
| Annual Sum or Average | 0.275781E+10 | |||
| Minimum of Months | 385270.07 | 49.39 | -12.2 | |
| Maximum of Months | 0.117544E+10 | 1720.27 | 26.67 |
Report: ZoneHeatingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.117602E+10 | 1248.10 | 14-JAN-07:00 | -6.7 |
| February | 0.659852E+09 | 1721.24 | 12-FEB-06:00 | -12.2 |
| March | 51401771.19 | 511.65 | 19-MAR-07:23 | 2.50 |
| April | 11407618.93 | 299.21 | 06-APR-06:00 | 1.10 |
| May | 581440.49 | 55.88 | 16-MAY-10:55 | 26.10 |
| June | 527943.00 | 52.64 | 29-JUN-09:07 | 26.57 |
| July | 375946.82 | 49.49 | 13-JUL-07:47 | 26.13 |
| August | 711832.38 | 59.68 | 25-AUG-09:35 | 26.67 |
| September | 992285.86 | 58.15 | 24-SEP-10:05 | 26.38 |
| October | 19417480.51 | 481.80 | 26-OCT-06:00 | 2.20 |
| November | 0.185116E+09 | 1008.16 | 22-NOV-06:00 | -3.3 |
| December | 0.653162E+09 | 1095.70 | 18-DEC-05:00 | -5.0 |
| Annual Sum or Average | 0.275956E+10 | |||
| Minimum of Months | 375946.82 | 49.49 | -12.2 | |
| Maximum of Months | 0.117602E+10 | 1721.24 | 26.67 |
Report: ZoneHeatingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.658683E+09 | 1185.70 | 08-JAN-02:70 | -5.6 |
| February | 0.368166E+09 | 1639.70 | 12-FEB-06:00 | -12.2 |
| March | 18405391.99 | 340.84 | 23-MAR-03:00 | 5.00 |
| April | 3904539.16 | 235.24 | 06-APR-07:13 | 2.80 |
| May | 517911.41 | 56.06 | 16-MAY-10:55 | 26.10 |
| June | 747682.40 | 58.41 | 05-JUN-09:05 | 26.57 |
| July | 716561.85 | 52.57 | 01-JUL-08:37 | 26.27 |
| August | 790985.19 | 59.96 | 25-AUG-09:35 | 26.67 |
| September | 470558.06 | 46.86 | 08-SEP-08:57 | 26.10 |
| October | 7191041.20 | 255.83 | 26-OCT-06:00 | 2.20 |
| November | 62323426.29 | 763.49 | 21-NOV-07:00 | -2.8 |
| December | 0.286508E+09 | 918.44 | 01-DEC-07:00 | -3.9 |
| Annual Sum or Average | 0.140843E+10 | |||
| Minimum of Months | 470558.06 | 46.86 | -12.2 | |
| Maximum of Months | 0.658683E+09 | 1639.70 | 26.67 |
Report: ZoneHeatingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.660146E+09 | 1186.44 | 08-JAN-02:70 | -5.6 |
| February | 0.368730E+09 | 1640.94 | 12-FEB-06:00 | -12.2 |
| March | 18724800.91 | 342.22 | 23-MAR-03:00 | 5.00 |
| April | 3909561.00 | 234.52 | 06-APR-07:13 | 2.80 |
| May | 480856.88 | 55.63 | 16-MAY-10:55 | 26.10 |
| June | 719064.38 | 58.40 | 05-JUN-09:05 | 26.57 |
| July | 663058.20 | 52.65 | 01-JUL-08:37 | 26.27 |
| August | 770040.18 | 59.64 | 25-AUG-09:35 | 26.67 |
| September | 448023.87 | 47.11 | 08-SEP-08:57 | 26.10 |
| October | 7315709.86 | 260.57 | 26-OCT-06:00 | 2.20 |
| November | 62223046.49 | 763.23 | 21-NOV-07:00 | -2.8 |
| December | 0.286992E+09 | 918.37 | 01-DEC-07:00 | -3.9 |
| Annual Sum or Average | 0.141112E+10 | |||
| Minimum of Months | 448023.87 | 47.11 | -12.2 | |
| Maximum of Months | 0.660146E+09 | 1640.94 | 26.67 |
Report: ZoneHeatingSummaryMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 1.80 | |
| Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 1.80 | |
| Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 1.80 | |
| Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.468251E+09 | 447.62 | 03-JAN-08:09 | 0.621586E+09 | 544.92 | 03-JAN-08:09 |
| February | 0.433623E+09 | 447.62 | 01-FEB-08:09 | 0.574385E+09 | 544.92 | 01-FEB-08:09 |
| March | 0.502522E+09 | 447.62 | 01-MAR-08:09 | 0.663122E+09 | 544.92 | 01-MAR-08:09 |
| April | 0.460516E+09 | 447.62 | 03-APR-07:10 | 0.610467E+09 | 544.92 | 03-APR-07:10 |
| May | 0.491098E+09 | 447.62 | 01-MAY-07:10 | 0.649277E+09 | 544.92 | 01-MAY-07:10 |
| June | 0.483363E+09 | 447.62 | 01-JUN-07:10 | 0.638158E+09 | 544.92 | 01-JUN-07:10 |
| July | 0.468251E+09 | 447.62 | 03-JUL-07:10 | 0.621586E+09 | 544.92 | 03-JUL-07:10 |
| August | 0.502522E+09 | 447.62 | 01-AUG-07:10 | 0.663122E+09 | 544.92 | 01-AUG-07:10 |
| September | 0.460516E+09 | 447.62 | 01-SEP-07:10 | 0.610467E+09 | 544.92 | 01-SEP-07:10 |
| October | 0.479675E+09 | 447.62 | 02-OCT-07:10 | 0.635432E+09 | 544.92 | 02-OCT-07:10 |
| November | 0.460516E+09 | 447.62 | 01-NOV-07:10 | 0.610467E+09 | 544.92 | 01-NOV-07:10 |
| December | 0.468251E+09 | 447.62 | 01-DEC-08:09 | 0.621586E+09 | 544.92 | 01-DEC-08:09 |
| Annual Sum or Average | 0.567911E+10 | 0.751966E+10 | ||||
| Minimum of Months | 0.433623E+09 | 447.62 | 0.574385E+09 | 544.92 | ||
| Maximum of Months | 0.502522E+09 | 447.62 | 0.663122E+09 | 544.92 |
Report: ZoneElectricSummaryMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.824800E+09 | 307.95 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.744981E+09 | 307.95 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.824800E+09 | 307.95 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.798194E+09 | 307.95 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.824800E+09 | 307.95 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.798194E+09 | 307.95 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.824800E+09 | 307.95 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.824800E+09 | 307.95 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.798194E+09 | 307.95 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.824800E+09 | 307.95 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.798194E+09 | 307.95 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.824800E+09 | 307.95 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.971136E+10 | 0.00 | 0.00 | ||
| Minimum of Months | 0.744981E+09 | 307.95 | 0.00 | 0.00 | |
| Maximum of Months | 0.824800E+09 | 307.95 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.824800E+09 | 307.95 | 01-JAN-00:10 | 0.576651E+10 | 3803.87 | 01-JAN-07:10 |
| February | 0.744981E+09 | 307.95 | 01-FEB-00:10 | 0.520846E+10 | 3803.87 | 01-FEB-07:10 |
| March | 0.824800E+09 | 307.95 | 01-MAR-00:10 | 0.576651E+10 | 3803.87 | 01-MAR-07:10 |
| April | 0.798194E+09 | 307.95 | 01-APR-00:10 | 0.558049E+10 | 3803.87 | 01-APR-06:10 |
| May | 0.824800E+09 | 307.95 | 01-MAY-00:10 | 0.576651E+10 | 3803.87 | 01-MAY-06:10 |
| June | 0.798194E+09 | 307.95 | 01-JUN-00:10 | 0.558049E+10 | 3803.87 | 01-JUN-06:10 |
| July | 0.824800E+09 | 307.95 | 01-JUL-00:10 | 0.576651E+10 | 3803.87 | 01-JUL-06:10 |
| August | 0.824800E+09 | 307.95 | 01-AUG-00:10 | 0.576651E+10 | 3803.87 | 01-AUG-06:10 |
| September | 0.798194E+09 | 307.95 | 01-SEP-00:10 | 0.558049E+10 | 3803.87 | 01-SEP-06:10 |
| October | 0.824800E+09 | 307.95 | 01-OCT-00:10 | 0.576651E+10 | 3803.87 | 01-OCT-06:10 |
| November | 0.798194E+09 | 307.95 | 01-NOV-00:10 | 0.558049E+10 | 3803.87 | 01-NOV-06:10 |
| December | 0.824800E+09 | 307.95 | 01-DEC-00:10 | 0.576651E+10 | 3803.87 | 01-DEC-07:10 |
| Annual Sum or Average | 0.971136E+10 | 0.678960E+11 | ||||
| Minimum of Months | 0.744981E+09 | 307.95 | 0.520846E+10 | 3803.87 | ||
| Maximum of Months | 0.824800E+09 | 307.95 | 0.576651E+10 | 3803.87 |
Report: ZoneElectricSummaryMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.824800E+09 | 307.95 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.744981E+09 | 307.95 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.824800E+09 | 307.95 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.798194E+09 | 307.95 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.824800E+09 | 307.95 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.798194E+09 | 307.95 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.824800E+09 | 307.95 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.824800E+09 | 307.95 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.798194E+09 | 307.95 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.824800E+09 | 307.95 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.798194E+09 | 307.95 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.824800E+09 | 307.95 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.971136E+10 | 0.00 | 0.00 | ||
| Minimum of Months | 0.744981E+09 | 307.95 | 0.00 | 0.00 | |
| Maximum of Months | 0.824800E+09 | 307.95 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214792E+09 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73089.60 | 0.179873E+09 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 845635.33 | 0.122005E+09 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2186248.89 | 68255772.48 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6642917.47 | 38085562.45 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25617817.43 | 15063958.06 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25358474.11 | 10747435.62 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26915344.66 | 5222760.43 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8026949.21 | 22491724.93 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1470940.55 | 87216699.22 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2956.79 | 0.129557E+09 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190123E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97140374.05 | 0.108343E+10 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5222760.43 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26915344.66 | 0.214792E+09 |
Report: SpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211076E+09 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 150377.70 | 0.173303E+09 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 859776.59 | 0.110682E+09 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2192695.86 | 65694134.78 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6620915.99 | 37853155.42 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25684818.43 | 15069104.15 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25418831.22 | 10737488.11 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26903025.83 | 5233835.91 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7973405.70 | 22315460.34 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1472535.60 | 85896579.46 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2337.69 | 0.121852E+09 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176717E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97278720.62 | 0.103643E+10 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5233835.91 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26903025.83 | 0.211076E+09 |
Report: SpaceGainsMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.227408E+09 | 0.468251E+09 | 0.621586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192653E+09 |
| February | 0.216037E+09 | 0.433623E+09 | 0.574385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51859.48 | 0.166185E+09 |
| March | 0.261519E+09 | 0.502522E+09 | 0.663122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 395851.13 | 0.121178E+09 |
| April | 0.227408E+09 | 0.460516E+09 | 0.610467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1253868.40 | 71225885.84 |
| May | 0.250148E+09 | 0.491098E+09 | 0.649277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3694345.09 | 45108321.93 |
| June | 0.250148E+09 | 0.483363E+09 | 0.638158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16850113.33 | 24538415.05 |
| July | 0.227408E+09 | 0.468251E+09 | 0.621586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13580831.90 | 19964808.09 |
| August | 0.261519E+09 | 0.502522E+09 | 0.663122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14752993.21 | 16227372.66 |
| September | 0.227408E+09 | 0.460516E+09 | 0.610467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4262766.60 | 31402876.14 |
| October | 0.238778E+09 | 0.479675E+09 | 0.635432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 945568.40 | 92716219.03 |
| November | 0.227408E+09 | 0.460516E+09 | 0.610467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126827E+09 |
| December | 0.227408E+09 | 0.468251E+09 | 0.621586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178640E+09 |
| Annual Sum or Average | 0.284259E+10 | 0.567911E+10 | 0.751966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55788197.54 | 0.108667E+10 |
| Minimum of Months | 0.216037E+09 | 0.433623E+09 | 0.574385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16227372.66 |
| Maximum of Months | 0.261519E+09 | 0.502522E+09 | 0.663122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16850113.33 | 0.192653E+09 |
Report: SpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211062E+09 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 120768.24 | 0.173743E+09 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 864985.34 | 0.110666E+09 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2168709.57 | 65951455.46 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6614237.63 | 38205307.54 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25677499.71 | 15367727.43 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25416197.26 | 10841255.35 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26900821.06 | 5278197.94 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7970608.56 | 22505909.88 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1470555.41 | 85984047.93 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.07 | 0.122008E+09 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176756E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97206864.85 | 0.103837E+10 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5278197.94 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26900821.06 | 0.211062E+09 |
Report: SpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128017E+09 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65687.22 | 0.106293E+09 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 508933.63 | 70865463.40 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1299067.63 | 41105841.90 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3992740.14 | 23010191.12 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15490080.87 | 9093241.92 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15329651.01 | 6495117.73 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16225450.63 | 3127973.32 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4807277.81 | 13522159.59 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 887735.69 | 52063234.95 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.11 | 76170288.17 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110333E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58607087.74 | 0.640095E+09 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3127973.32 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16225450.63 | 0.128017E+09 |
Report: SpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128018E+09 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63586.24 | 0.106318E+09 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 508820.70 | 70868586.85 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1298286.19 | 41111647.30 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3992499.35 | 23020526.53 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15489886.82 | 9100362.26 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15329592.49 | 6496909.80 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16225418.52 | 3127977.47 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4807189.74 | 13526146.19 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 887643.47 | 52069113.15 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.29 | 76185794.46 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110346E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58603395.81 | 0.640189E+09 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3127977.47 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16225418.52 | 0.128018E+09 |
Report: SpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132971E+09 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43578.07 | 0.111607E+09 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 509756.08 | 76499646.37 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1317220.84 | 42272764.95 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4004564.43 | 23164205.30 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15449860.16 | 9094098.08 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15293562.08 | 6506915.08 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16233336.92 | 3133470.26 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4840473.54 | 13670892.48 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 886745.37 | 52915836.17 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1800.59 | 79248267.84 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120727E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58580898.09 | 0.671811E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3133470.26 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16233336.92 | 0.132971E+09 |
Report: SpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132005E+09 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43584.58 | 0.111154E+09 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 509792.35 | 76422138.91 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1317129.11 | 42331948.71 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4003948.13 | 23292739.03 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15448563.08 | 9218955.40 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15293643.50 | 6665451.33 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16233539.26 | 3237553.75 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4840640.88 | 13804613.97 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 886752.67 | 52979811.32 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1798.88 | 79188762.99 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120110E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58579392.43 | 0.670411E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3237553.75 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16233539.26 | 0.132005E+09 |
Report: SpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317698E+09 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 101528.85 | 0.269971E+09 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1200222.15 | 0.186804E+09 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3101661.26 | 0.104277E+09 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9477922.43 | 57195004.49 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36669799.78 | 21879296.70 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36309882.48 | 15497989.69 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38514263.42 | 7254425.77 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11463138.06 | 31636198.07 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2093149.84 | 0.124755E+09 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3853.75 | 0.185135E+09 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274536E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138935E+09 | 0.159664E+10 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7254425.77 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38514263.42 | 0.317698E+09 |
Report: SpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306355E+09 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84790.38 | 0.260628E+09 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1171276.18 | 0.180974E+09 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3022948.95 | 0.102737E+09 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9444525.04 | 57087079.60 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36763613.15 | 21896294.03 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36394606.98 | 15506282.33 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38497879.45 | 7268902.63 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11390214.30 | 31302453.62 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2098215.29 | 0.121794E+09 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2135.90 | 0.172749E+09 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256274E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138870E+09 | 0.153457E+10 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7268902.63 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38497879.45 | 0.306355E+09 |
Report: SpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317950E+09 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 101057.18 | 0.270136E+09 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1199565.78 | 0.186270E+09 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3100047.84 | 0.104667E+09 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9474292.20 | 57794814.74 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36665572.69 | 22419550.56 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36306565.51 | 15648707.76 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38512293.39 | 7335108.02 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11459510.90 | 31924153.43 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2092110.29 | 0.125037E+09 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3871.22 | 0.185159E+09 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275294E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138915E+09 | 0.159964E+10 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7335108.02 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38512293.39 | 0.317950E+09 |
Report: SpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306275E+09 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85607.62 | 0.261049E+09 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1170516.18 | 0.180833E+09 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3021286.94 | 0.103244E+09 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9441084.23 | 57770703.96 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36757146.37 | 22416691.20 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36392263.94 | 15617108.32 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38494962.54 | 7353924.94 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11384618.46 | 31683804.51 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2093633.05 | 0.121831E+09 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2070.46 | 0.172998E+09 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256373E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138843E+09 | 0.153745E+10 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7353924.94 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38494962.54 | 0.306275E+09 |
Report: SpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187731E+09 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51746.07 | 0.159970E+09 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 706058.19 | 0.110978E+09 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1822999.03 | 61972889.78 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5694668.04 | 34220738.93 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22173830.26 | 13103507.90 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21950761.51 | 9250690.40 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23219714.35 | 4316659.32 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6868573.67 | 18975894.95 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1264399.47 | 74246466.37 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 892.64 | 0.108829E+09 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161214E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83753643.23 | 0.944808E+09 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4316659.32 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23219714.35 | 0.187731E+09 |
Report: SpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187736E+09 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51769.37 | 0.159992E+09 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 706050.65 | 0.110972E+09 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1822871.77 | 61991083.07 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5694444.23 | 34238261.99 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22173508.20 | 13114824.31 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21950634.29 | 9245255.86 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23219601.25 | 4316881.15 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6868346.32 | 18982915.66 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1264262.98 | 74255932.15 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 918.00 | 0.108853E+09 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161232E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83752407.06 | 0.944930E+09 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4316881.15 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23219601.25 | 0.187736E+09 |
Report: SpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200637E+09 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60853.84 | 0.169474E+09 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 722911.29 | 0.113555E+09 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1869251.54 | 62816365.84 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5714755.56 | 34334207.76 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22117679.08 | 13086993.80 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21899825.05 | 9268267.52 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23230023.05 | 4316479.58 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6912017.07 | 19224898.04 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1261837.44 | 75898901.30 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2234.51 | 0.113834E+09 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174817E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83791388.45 | 0.991262E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4316479.58 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23230023.05 | 0.200637E+09 |
Report: SpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200635E+09 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60837.97 | 0.169495E+09 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 722909.37 | 0.113540E+09 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1869245.41 | 62830268.39 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5714619.74 | 34346925.13 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22117325.22 | 13098533.60 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21899671.52 | 9257359.66 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23229962.51 | 4317258.36 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6911981.27 | 19229660.56 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1261818.04 | 75907638.70 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2234.57 | 0.113834E+09 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174828E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83790605.62 | 0.991319E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4317258.36 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23229962.51 | 0.200635E+09 |
Report: SpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411186E+09 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 125743.19 | 0.344932E+09 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1551075.27 | 0.227135E+09 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4012299.17 | 0.132450E+09 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12369393.28 | 74052770.73 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48125077.34 | 28564115.55 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47676064.02 | 20297658.29 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50507134.59 | 9543485.69 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14966816.89 | 39931226.88 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2712695.20 | 0.152045E+09 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4152.54 | 0.222360E+09 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344032E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182050E+09 | 0.200653E+10 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9543485.69 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50507134.59 | 0.411186E+09 |
Report: SpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403589E+09 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 136411.69 | 0.334042E+09 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1516077.10 | 0.214084E+09 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3914479.35 | 0.128398E+09 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12328558.27 | 73991537.57 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48244155.56 | 28700033.25 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47784886.32 | 20349042.53 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50485661.12 | 9626319.68 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14875306.93 | 39419330.49 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2722816.42 | 0.142854E+09 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13094.40 | 0.206206E+09 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331992E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182021E+09 | 0.193325E+10 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9626319.68 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50485661.12 | 0.403589E+09 |
Report: SpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411078E+09 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 125598.03 | 0.345397E+09 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1550245.05 | 0.227345E+09 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4008709.17 | 0.134229E+09 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12360226.21 | 75509487.12 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48115180.75 | 29767296.23 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47668071.48 | 20593272.42 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50503473.48 | 9724099.47 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14960075.59 | 40539152.53 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2710491.18 | 0.153310E+09 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4072.60 | 0.223015E+09 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344547E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182006E+09 | 0.201505E+10 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9724099.47 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50503473.48 | 0.411078E+09 |
Report: SpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403518E+09 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 106677.95 | 0.334344E+09 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1517914.85 | 0.213619E+09 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3911516.94 | 0.129814E+09 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12319145.47 | 75607304.83 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48233176.09 | 29859734.59 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47778891.25 | 20560615.09 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50481602.71 | 9816404.58 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14864362.11 | 40146399.33 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2715391.88 | 0.143686E+09 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32305.28 | 0.205594E+09 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331494E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181961E+09 | 0.193806E+10 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9816404.58 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50481602.71 | 0.403518E+09 |
Report: SpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243759E+09 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77145.07 | 0.202965E+09 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 915779.02 | 0.130501E+09 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2365581.55 | 78203523.44 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7432659.62 | 44848504.11 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29097357.72 | 17410809.19 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28820115.87 | 12268057.95 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30449760.03 | 5844115.82 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8969673.99 | 24274027.88 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1640670.29 | 88464268.28 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18609.53 | 0.125860E+09 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201029E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109787E+09 | 0.117543E+10 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5844115.82 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30449760.03 | 0.243759E+09 |
Report: SpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243762E+09 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73406.27 | 0.203003E+09 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 915878.04 | 0.130455E+09 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2363569.71 | 78277094.78 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7432422.72 | 44899630.21 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29097018.58 | 17440212.68 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28820058.46 | 12268103.35 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30449577.32 | 5845049.76 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8969186.08 | 24291603.72 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1640008.99 | 88531963.61 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19315.24 | 0.125838E+09 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201018E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109780E+09 | 0.117563E+10 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5845049.76 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30449577.32 | 0.243762E+09 |
Report: SpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250649E+09 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75762.11 | 0.211606E+09 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 934841.06 | 0.140273E+09 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2419483.55 | 80992582.53 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7457678.38 | 44981275.86 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29024782.59 | 17330779.17 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28753948.45 | 12263734.72 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30462682.54 | 5795286.89 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9024120.50 | 24639145.39 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1635036.47 | 94877280.66 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2610.47 | 0.138420E+09 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211038E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109791E+09 | 0.123287E+10 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5795286.89 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30462682.54 | 0.250649E+09 |
Report: SpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250667E+09 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75684.31 | 0.211642E+09 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 934785.79 | 0.140265E+09 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2419344.59 | 81078718.74 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7457434.64 | 45017745.77 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29024510.65 | 17362797.00 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28753817.07 | 12245553.79 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30462576.94 | 5796434.40 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9023958.52 | 24650463.20 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1634988.23 | 94924659.82 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2611.22 | 0.138424E+09 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211067E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109790E+09 | 0.123314E+10 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5796434.40 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30462576.94 | 0.250667E+09 |
Report: SpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68547213.56 |
| February | 0.657255E+09 | 0.744981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.72 | 58575148.10 |
| March | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32313.22 | 41031262.60 |
| April | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135238.06 | 25236846.10 |
| May | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668654.68 | 15737618.86 |
| June | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4411209.45 | 7097473.19 |
| July | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4483925.44 | 5245938.86 |
| August | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4444112.52 | 3368946.45 |
| September | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975123.74 | 9077746.86 |
| October | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104801.25 | 28383996.98 |
| November | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5812.96 | 38696733.41 |
| December | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58058325.67 |
| Annual Sum or Average | 0.856778E+10 | 0.971136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15261779.04 | 0.359057E+09 |
| Minimum of Months | 0.657255E+09 | 0.744981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3368946.45 |
| Maximum of Months | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4483925.44 | 68547213.56 |
Report: SpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246753E+10 |
| February | 0.657255E+09 | 0.744981E+09 | 0.260423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180051E+10 |
| March | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1536565.50 | 0.142823E+10 |
| April | 0.704201E+09 | 0.798194E+09 | 0.279025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8272162.82 | 0.100354E+10 |
| May | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33056678.25 | 0.675456E+09 |
| June | 0.704201E+09 | 0.798194E+09 | 0.279025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168241E+09 | 0.348535E+09 |
| July | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225193E+09 | 0.308558E+09 |
| August | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195003E+09 | 0.239478E+09 |
| September | 0.704201E+09 | 0.798194E+09 | 0.279025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34948837.16 | 0.561559E+09 |
| October | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2779551.95 | 0.131023E+10 |
| November | 0.704201E+09 | 0.798194E+09 | 0.279025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169689E+10 |
| December | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213034E+10 |
| Annual Sum or Average | 0.856778E+10 | 0.971136E+10 | 0.339480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669031E+09 | 0.139709E+11 |
| Minimum of Months | 0.657255E+09 | 0.744981E+09 | 0.260423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239478E+09 |
| Maximum of Months | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225193E+09 | 0.246753E+10 |
Report: SpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57392403.31 |
| February | 0.657255E+09 | 0.744981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49539565.24 |
| March | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31534.25 | 35938594.53 |
| April | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114048.41 | 20975508.97 |
| May | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605856.84 | 12492748.18 |
| June | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3760090.12 | 5553001.66 |
| July | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3847269.84 | 4042660.92 |
| August | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3876329.65 | 2547018.25 |
| September | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 839407.90 | 7383807.28 |
| October | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85626.48 | 24692510.48 |
| November | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34514778.83 |
| December | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50270114.91 |
| Annual Sum or Average | 0.856778E+10 | 0.971136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13160163.50 | 0.305343E+09 |
| Minimum of Months | 0.657255E+09 | 0.744981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2547018.25 |
| Maximum of Months | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3876329.65 | 57392403.31 |
Report: PeakSpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 281.65 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 28-FEB-13:55 | 310.77 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 | 30-MAR-16:00 | 181.99 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 04-APR-15:00 | 180.58 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.27 | 19-MAY-13:00 | 78.10 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 | 06-JUN-14:00 | 57.15 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.51 | 22-JUL-14:00 | 46.72 | 28-JUL-16:50 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.60 | 07-AUG-15:00 | 26.36 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.42 | 06-SEP-12:00 | 57.48 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 | 11-OCT-14:00 | 173.25 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 19-NOV-15:20 | 187.50 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 290.58 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 | 310.77 |
Report: PeakSpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 281.65 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 | 28-FEB-15:00 | 310.77 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 | 30-MAR-16:00 | 169.68 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 04-APR-15:00 | 177.48 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.27 | 19-MAY-13:00 | 78.10 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 | 06-JUN-14:00 | 57.15 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.51 | 22-JUL-14:00 | 51.29 | 28-JUL-17:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.60 | 07-AUG-15:00 | 25.98 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.42 | 06-SEP-12:00 | 57.13 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 | 11-OCT-14:00 | 172.38 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 | 19-NOV-15:35 | 181.02 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 280.46 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.98 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 | 310.77 |
Report: PeakSpaceGainsMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 451.21 | 03-JAN-08:09 | 447.62 | 03-JAN-08:09 | 544.92 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 229.87 | 07-JAN-10:00 |
| February | 451.21 | 01-FEB-08:09 | 447.62 | 01-FEB-08:09 | 544.92 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 | 28-FEB-15:00 | 259.37 | 12-FEB-01:00 |
| March | 451.21 | 01-MAR-08:09 | 447.62 | 01-MAR-08:09 | 544.92 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 30-MAR-16:00 | 173.98 | 22-MAR-03:00 |
| April | 451.21 | 03-APR-07:10 | 447.62 | 03-APR-07:10 | 544.92 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 04-APR-15:00 | 187.56 | 05-APR-11:00 |
| May | 451.21 | 01-MAY-07:10 | 447.62 | 01-MAY-07:10 | 544.92 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.27 | 19-MAY-13:00 | 78.10 | 10-MAY-08:00 |
| June | 451.21 | 01-JUN-07:10 | 447.62 | 01-JUN-07:10 | 544.92 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 | 06-JUN-14:00 | 59.83 | 07-JUN-03:00 |
| July | 451.21 | 03-JUL-07:10 | 447.62 | 03-JUL-07:10 | 544.92 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.25 | 10-JUL-15:00 | 51.53 | 28-JUL-18:00 |
| August | 451.21 | 01-AUG-07:10 | 447.62 | 01-AUG-07:10 | 544.92 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.59 | 07-AUG-15:00 | 39.35 | 07-AUG-21:00 |
| September | 451.21 | 01-SEP-07:10 | 447.62 | 01-SEP-07:10 | 544.92 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.42 | 06-SEP-12:00 | 62.96 | 28-SEP-18:00 |
| October | 451.21 | 02-OCT-07:10 | 447.62 | 02-OCT-07:10 | 544.92 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 | 11-OCT-14:00 | 175.38 | 25-OCT-10:00 |
| November | 451.21 | 01-NOV-07:10 | 447.62 | 01-NOV-07:10 | 544.92 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 185.46 | 20-NOV-09:00 |
| December | 451.21 | 01-DEC-08:09 | 447.62 | 01-DEC-08:09 | 544.92 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 272.13 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 451.21 | 447.62 | 544.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.35 | |||||
| Maximum of Months | 451.21 | 447.62 | 544.92 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 | 272.13 |
Report: PeakSpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 281.65 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 | 28-FEB-15:00 | 310.77 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 | 30-MAR-16:00 | 169.68 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 04-APR-15:00 | 180.93 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.27 | 19-MAY-13:00 | 78.10 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 | 06-JUN-14:00 | 57.15 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.51 | 22-JUL-14:00 | 50.14 | 28-JUL-17:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.60 | 07-AUG-15:00 | 26.48 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.42 | 06-SEP-12:00 | 57.02 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 | 11-OCT-14:00 | 172.19 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.69 | 19-NOV-15:35 | 180.79 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 280.46 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.48 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 | 310.77 |
Report: PeakSpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 169.89 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.19 | 28-FEB-14:15 | 187.45 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 30-MAR-16:00 | 109.43 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.42 | 04-APR-15:00 | 112.52 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 19-MAY-13:00 | 47.11 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 06-JUN-14:00 | 34.47 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.51 | 22-JUL-14:00 | 30.95 | 28-JUL-17:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.58 | 07-AUG-15:00 | 15.08 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 06-SEP-12:00 | 34.86 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 | 11-OCT-14:00 | 107.76 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 05-NOV-15:57 | 112.90 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 176.91 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.08 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 187.45 |
Report: PeakSpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 169.89 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.29 | 28-FEB-14:15 | 187.45 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 30-MAR-16:00 | 109.40 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.42 | 04-APR-15:00 | 112.55 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 19-MAY-13:00 | 47.11 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 06-JUN-14:00 | 34.47 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.51 | 22-JUL-14:00 | 30.94 | 28-JUL-17:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.58 | 07-AUG-15:00 | 15.10 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 06-SEP-12:00 | 34.86 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 | 11-OCT-14:00 | 107.74 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 05-NOV-15:57 | 112.88 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 177.00 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.10 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 187.45 |
Report: PeakSpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 169.89 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 28-FEB-15:00 | 187.45 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 30-MAR-16:00 | 117.31 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.42 | 04-APR-15:00 | 113.13 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 19-MAY-13:00 | 47.11 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 06-JUN-14:00 | 34.47 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.51 | 22-JUL-14:00 | 28.18 | 28-JUL-16:45 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.58 | 07-AUG-15:00 | 15.38 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 06-SEP-12:00 | 35.13 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 | 11-OCT-14:00 | 108.21 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 19-NOV-15:17 | 113.60 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 184.17 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.38 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 187.45 |
Report: PeakSpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 169.89 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 28-FEB-15:00 | 187.45 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 30-MAR-16:00 | 116.91 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.42 | 04-APR-15:00 | 113.13 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 19-MAY-13:00 | 47.11 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 06-JUN-14:00 | 34.47 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.51 | 22-JUL-14:00 | 28.18 | 28-JUL-16:50 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.58 | 07-AUG-15:00 | 16.13 | 31-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 06-SEP-12:00 | 35.37 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 | 11-OCT-14:00 | 108.30 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | 19-NOV-15:17 | 113.60 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 183.56 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 187.45 |
Report: PeakSpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 405.08 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.46 | 28-FEB-13:55 | 446.89 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.08 | 30-MAR-16:00 | 278.48 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 | 04-APR-15:00 | 269.86 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.09 | 19-MAY-13:00 | 112.41 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 06-JUN-14:00 | 82.30 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.89 | 22-JUL-14:00 | 68.66 | 28-JUL-18:30 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 07-AUG-15:00 | 35.80 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 | 06-SEP-12:00 | 81.20 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.53 | 11-OCT-14:00 | 243.02 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 19-NOV-15:15 | 267.03 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 414.23 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.80 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 446.89 |
Report: PeakSpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 405.08 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.57 | 28-FEB-14:15 | 446.89 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.08 | 30-MAR-16:00 | 272.21 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 | 04-APR-15:00 | 269.70 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.09 | 19-MAY-13:00 | 112.41 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 06-JUN-14:00 | 82.30 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.89 | 22-JUL-14:00 | 75.07 | 28-JUL-17:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 07-AUG-15:00 | 35.33 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 | 06-SEP-12:00 | 81.04 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.53 | 11-OCT-14:00 | 242.42 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 | 19-NOV-15:35 | 259.02 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 403.44 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 446.89 |
Report: PeakSpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 405.08 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 | 28-FEB-15:00 | 446.89 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.08 | 30-MAR-16:00 | 277.91 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 | 04-APR-15:00 | 269.86 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.09 | 19-MAY-13:00 | 112.41 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 06-JUN-14:00 | 82.30 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.89 | 22-JUL-14:00 | 67.33 | 28-JUL-16:50 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 07-AUG-15:00 | 36.47 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 | 06-SEP-12:00 | 81.11 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.53 | 11-OCT-14:00 | 245.52 | 25-OCT-10:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 | 19-NOV-15:15 | 267.04 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 415.18 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.47 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 446.89 |
Report: PeakSpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 405.08 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 | 28-FEB-14:15 | 446.89 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.08 | 30-MAR-16:00 | 271.94 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 | 04-APR-15:00 | 269.86 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.09 | 19-MAY-13:00 | 112.41 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 06-JUN-14:00 | 82.30 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.89 | 22-JUL-14:00 | 74.38 | 28-JUL-17:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 07-AUG-15:00 | 36.00 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 | 06-SEP-12:00 | 80.92 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.53 | 11-OCT-14:00 | 242.10 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 19-NOV-15:35 | 258.68 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 403.44 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 446.89 |
Report: PeakSpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 244.33 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.27 | 28-FEB-14:15 | 269.55 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 30-MAR-16:00 | 172.37 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 04-APR-15:00 | 162.77 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.61 | 19-MAY-13:00 | 67.80 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.55 | 06-JUN-14:00 | 49.64 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 | 22-JUL-14:00 | 43.71 | 28-JUL-17:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.06 | 07-AUG-15:00 | 19.95 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 06-SEP-12:00 | 49.63 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 | 11-OCT-14:00 | 153.46 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 19-NOV-15:35 | 162.63 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 257.25 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 71.55 | 269.55 |
Report: PeakSpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 244.33 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 28-FEB-14:15 | 269.55 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 30-MAR-16:00 | 172.37 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 04-APR-15:00 | 162.77 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.61 | 19-MAY-13:00 | 67.80 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.55 | 06-JUN-14:00 | 49.64 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 | 22-JUL-14:00 | 42.24 | 28-JUL-17:30 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.06 | 07-AUG-15:00 | 19.97 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 06-SEP-12:00 | 49.63 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 | 11-OCT-14:00 | 153.43 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 19-NOV-15:35 | 162.57 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 257.42 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.97 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 71.55 | 269.55 |
Report: PeakSpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 244.33 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 28-FEB-15:00 | 269.55 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 30-MAR-16:00 | 174.86 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 04-APR-15:00 | 162.77 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.61 | 19-MAY-13:00 | 67.80 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.55 | 06-JUN-14:00 | 49.64 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 | 22-JUL-14:00 | 40.61 | 28-JUL-16:45 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.06 | 07-AUG-15:00 | 20.65 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 06-SEP-12:00 | 49.73 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 | 11-OCT-14:00 | 153.67 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 | 19-NOV-15:20 | 163.42 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 264.10 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 71.55 | 269.55 |
Report: PeakSpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 244.33 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 28-FEB-15:00 | 269.55 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 30-MAR-16:00 | 174.83 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 04-APR-15:00 | 162.77 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.61 | 19-MAY-13:00 | 67.80 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.55 | 06-JUN-14:00 | 49.64 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 | 22-JUL-14:00 | 40.61 | 28-JUL-16:45 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.06 | 07-AUG-15:00 | 20.68 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 06-SEP-12:00 | 49.74 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 | 11-OCT-14:00 | 153.65 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 | 19-NOV-15:20 | 163.42 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 264.17 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.68 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 71.55 | 269.55 |
Report: PeakSpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 536.69 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 28-FEB-13:55 | 591.90 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.22 | 30-MAR-16:00 | 323.93 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 04-APR-15:00 | 331.41 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.51 | 19-MAY-13:00 | 135.97 | 10-MAY-04:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.29 | 06-JUN-14:00 | 109.27 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.56 | 22-JUL-14:00 | 97.34 | 28-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.30 | 07-AUG-15:00 | 55.66 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 06-SEP-12:00 | 101.05 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.35 | 11-OCT-14:00 | 283.90 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 19-NOV-15:15 | 303.48 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 534.70 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.66 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 156.29 | 591.90 |
Report: PeakSpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 536.69 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 28-FEB-15:00 | 591.90 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.22 | 30-MAR-16:00 | 323.93 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 04-APR-15:00 | 324.81 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.51 | 19-MAY-13:00 | 135.26 | 10-MAY-04:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.29 | 06-JUN-14:00 | 109.32 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.56 | 22-JUL-14:00 | 106.47 | 28-JUL-17:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.30 | 07-AUG-15:00 | 55.05 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 06-SEP-12:00 | 100.93 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.35 | 11-OCT-14:00 | 283.90 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 19-NOV-15:00 | 302.74 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 534.70 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.05 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 156.29 | 591.90 |
Report: PeakSpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 536.69 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 28-FEB-15:00 | 591.90 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.22 | 30-MAR-16:00 | 323.93 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 04-APR-15:00 | 346.91 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.51 | 19-MAY-13:00 | 139.27 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.29 | 06-JUN-14:00 | 109.32 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.56 | 22-JUL-14:00 | 89.57 | 28-JUL-16:50 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.30 | 07-AUG-15:00 | 56.30 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 06-SEP-12:00 | 101.02 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.35 | 11-OCT-14:00 | 283.90 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 | 19-NOV-15:15 | 304.20 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 534.70 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.30 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 156.29 | 591.90 |
Report: PeakSpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 536.69 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | 28-FEB-14:15 | 591.90 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.22 | 30-MAR-16:00 | 323.93 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 04-APR-15:00 | 340.22 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.51 | 19-MAY-13:00 | 140.06 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.29 | 06-JUN-14:00 | 109.32 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.56 | 22-JUL-14:00 | 104.38 | 28-JUL-17:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.30 | 07-AUG-15:00 | 55.67 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 06-SEP-12:00 | 100.79 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.35 | 11-OCT-14:00 | 283.90 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 | 19-NOV-15:00 | 302.74 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 534.70 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 156.29 | 591.90 |
Report: PeakSpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 323.72 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 | 28-FEB-14:15 | 357.02 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 30-MAR-16:00 | 195.39 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.91 | 04-APR-15:00 | 207.15 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.91 | 19-MAY-13:00 | 85.70 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.27 | 06-JUN-14:00 | 65.94 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.53 | 22-JUL-14:00 | 63.03 | 28-JUL-17:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.40 | 07-AUG-15:00 | 32.52 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.52 | 06-SEP-12:00 | 62.70 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 | 11-OCT-14:00 | 171.24 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.66 | 19-NOV-15:00 | 188.59 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 322.52 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.52 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 94.27 | 357.02 |
Report: PeakSpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 323.72 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.12 | 28-FEB-14:15 | 357.02 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 30-MAR-16:00 | 195.39 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.91 | 04-APR-15:00 | 207.74 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.91 | 19-MAY-13:00 | 85.75 | 10-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.27 | 06-JUN-14:00 | 65.94 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.53 | 22-JUL-14:00 | 62.96 | 28-JUL-17:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.40 | 07-AUG-15:00 | 32.55 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.52 | 06-SEP-12:00 | 62.72 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 | 11-OCT-14:00 | 171.24 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 19-NOV-15:00 | 188.39 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 322.52 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 94.27 | 357.02 |
Report: PeakSpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 323.72 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 28-FEB-13:55 | 357.02 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 30-MAR-16:00 | 196.37 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.91 | 04-APR-15:00 | 211.29 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.91 | 19-MAY-13:00 | 85.52 | 10-MAY-04:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.27 | 06-JUN-14:00 | 65.94 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.53 | 22-JUL-14:00 | 55.29 | 28-JUL-19:30 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.40 | 07-AUG-15:00 | 32.91 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.52 | 06-SEP-12:00 | 62.82 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 | 11-OCT-14:00 | 171.24 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 | 19-NOV-15:15 | 195.31 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 322.52 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.91 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 94.27 | 357.02 |
Report: PeakSpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 323.72 | 07-JAN-10:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 | 28-FEB-15:00 | 357.02 | 12-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 30-MAR-16:00 | 196.30 | 22-MAR-03:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.91 | 04-APR-15:00 | 211.89 | 05-APR-11:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.91 | 19-MAY-13:00 | 85.48 | 10-MAY-04:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.27 | 06-JUN-14:00 | 65.94 | 07-JUN-07:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.53 | 22-JUL-14:00 | 54.02 | 28-JUL-16:50 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.40 | 07-AUG-15:00 | 32.94 | 07-AUG-21:00 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.52 | 06-SEP-12:00 | 62.85 | 28-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 | 11-OCT-14:00 | 171.24 | 25-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 19-NOV-15:15 | 195.21 | 20-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 322.52 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.94 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 94.27 | 357.02 |
Report: PeakSpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 86.71 | 07-JAN-10:00 |
| February | 397.10 | 01-FEB-00:10 | 307.95 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 | 26-FEB-15:00 | 96.69 | 12-FEB-01:00 |
| March | 397.10 | 01-MAR-00:10 | 307.95 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 30-MAR-16:00 | 59.85 | 22-MAR-03:00 |
| April | 397.10 | 01-APR-00:10 | 307.95 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 | 12-APR-14:00 | 61.64 | 05-APR-11:00 |
| May | 397.10 | 01-MAY-00:10 | 307.95 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 | 19-MAY-13:00 | 26.13 | 10-MAY-04:00 |
| June | 397.10 | 01-JUN-00:10 | 307.95 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 06-JUN-14:00 | 20.99 | 07-JUN-07:00 |
| July | 397.10 | 01-JUL-00:10 | 307.95 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.37 | 22-JUL-14:00 | 17.76 | 28-JUL-18:00 |
| August | 397.10 | 01-AUG-00:10 | 307.95 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 07-AUG-15:00 | 9.36 | 07-AUG-21:00 |
| September | 397.10 | 01-SEP-00:10 | 307.95 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 06-SEP-12:00 | 20.73 | 28-SEP-18:00 |
| October | 397.10 | 01-OCT-00:10 | 307.95 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 10-OCT-16:00 | 50.10 | 25-OCT-08:00 |
| November | 397.10 | 01-NOV-00:10 | 307.95 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 | 19-NOV-15:00 | 57.58 | 20-NOV-09:00 |
| December | 397.10 | 01-DEC-00:10 | 307.95 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 90.19 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.36 | ||||
| Maximum of Months | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 96.69 |
Report: PeakSpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 | 190.19 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 10733.92 | 27-JAN-07:01 |
| February | 397.10 | 01-FEB-00:10 | 307.95 | 01-FEB-00:10 | 190.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 13097.68 | 12-FEB-07:01 |
| March | 397.10 | 01-MAR-00:10 | 307.95 | 01-MAR-00:10 | 190.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.10 | 30-MAR-16:03 | 8164.62 | 19-MAR-06:01 |
| April | 397.10 | 01-APR-00:10 | 307.95 | 01-APR-00:10 | 190.19 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 593.18 | 17-APR-16:03 | 8521.31 | 06-APR-06:01 |
| May | 397.10 | 01-MAY-00:10 | 307.95 | 01-MAY-00:10 | 190.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1057.26 | 19-MAY-16:03 | 6327.93 | 11-MAY-06:01 |
| June | 397.10 | 01-JUN-00:10 | 307.95 | 01-JUN-00:10 | 190.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1966.59 | 06-JUN-16:02 | 5113.23 | 08-JUN-06:01 |
| July | 397.10 | 01-JUL-00:10 | 307.95 | 01-JUL-00:10 | 190.19 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.69 | 08-JUL-16:02 | 3104.03 | 29-JUL-06:02 |
| August | 397.10 | 01-AUG-00:10 | 307.95 | 01-AUG-00:10 | 190.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2318.93 | 01-AUG-16:02 | 2991.94 | 25-AUG-06:01 |
| September | 397.10 | 01-SEP-00:10 | 307.95 | 01-SEP-00:10 | 190.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1170.89 | 07-SEP-16:02 | 5114.55 | 14-SEP-06:01 |
| October | 397.10 | 01-OCT-00:10 | 307.95 | 01-OCT-00:10 | 190.19 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 743.94 | 10-OCT-16:02 | 8331.68 | 26-OCT-06:01 |
| November | 397.10 | 01-NOV-00:10 | 307.95 | 01-NOV-00:10 | 190.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10135.93 | 21-NOV-07:01 |
| December | 397.10 | 01-DEC-00:10 | 307.95 | 01-DEC-00:10 | 190.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 10586.13 | 18-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 397.10 | 307.95 | 190.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2991.94 | |||||
| Maximum of Months | 397.10 | 307.95 | 190.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.69 | 13097.68 |
Report: PeakSpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 71.12 | 07-JAN-10:00 |
| February | 397.10 | 01-FEB-00:10 | 307.95 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 79.24 | 12-FEB-01:00 |
| March | 397.10 | 01-MAR-00:10 | 307.95 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 30-MAR-16:00 | 53.43 | 22-MAR-03:00 |
| April | 397.10 | 01-APR-00:10 | 307.95 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 12-APR-14:00 | 50.98 | 05-APR-11:00 |
| May | 397.10 | 01-MAY-00:10 | 307.95 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 19-MAY-13:00 | 22.18 | 10-MAY-08:00 |
| June | 397.10 | 01-JUN-00:10 | 307.95 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 06-JUN-14:00 | 17.10 | 07-JUN-07:00 |
| July | 397.10 | 01-JUL-00:10 | 307.95 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.42 | 22-JUL-14:00 | 13.16 | 28-JUL-18:00 |
| August | 397.10 | 01-AUG-00:10 | 307.95 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 | 07-AUG-15:00 | 7.05 | 25-AUG-05:00 |
| September | 397.10 | 01-SEP-00:10 | 307.95 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 | 06-SEP-12:00 | 16.29 | 28-SEP-18:00 |
| October | 397.10 | 01-OCT-00:10 | 307.95 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 | 10-OCT-16:00 | 46.70 | 25-OCT-08:00 |
| November | 397.10 | 01-NOV-00:10 | 307.95 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 49.83 | 20-NOV-09:00 |
| December | 397.10 | 01-DEC-00:10 | 307.95 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 79.03 | 17-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 | ||||
| Maximum of Months | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 79.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 201.43 | 26-JAN-20:40 | 237.50 | 87.71 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.89 |
| February | 4706.21 | 28-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.31 |
| March | 4853.98 | 14-MAR-17:42 | 1425.00 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.26 |
| April | 4836.71 | 12-APR-19:32 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.76 |
| May | 4844.09 | 12-MAY-20:02 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 |
| June | 4828.96 | 07-JUN-21:12 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.72 |
| July | 4349.24 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 |
| August | 4101.26 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 |
| September | 4855.67 | 14-SEP-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4886.10 | 14-OCT-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 |
| November | 4843.87 | 06-NOV-13:02 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.91 |
| December | 4651.96 | 10-DEC-19:22 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.35 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 201.43 | 0.00 | 65.78 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4886.10 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 131.47 | 21-JAN-19:40 | 206.62 | 87.71 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.65 |
| February | 2712.90 | 28-FEB-17:52 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 |
| March | 4164.88 | 30-MAR-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 |
| April | 4654.15 | 24-APR-21:02 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.44 |
| May | 4701.06 | 12-MAY-20:02 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 |
| June | 4686.37 | 07-JUN-20:52 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 |
| July | 4220.49 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
| August | 3944.63 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 |
| September | 4714.59 | 14-SEP-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4733.77 | 03-OCT-20:12 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.34 |
| November | 4648.86 | 09-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 |
| December | 228.80 | 01-DEC-06:12 | 950.00 | 153.49 | 1271.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.45 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 131.47 | 206.62 | 87.71 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4733.77 | 1425.00 | 361.83 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 981.60 | 27-JAN-07:04 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.79 |
| February | 1254.43 | 28-FEB-15:30 | 451.21 | 447.62 | 544.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 0.00 |
| March | 4650.10 | 31-MAR-06:02 | 0.00 | 537.15 | 1169.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.30 |
| April | 5795.33 | 17-APR-06:01 | 0.00 | 805.72 | 1754.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.59 |
| May | 5435.86 | 17-MAY-06:01 | 0.00 | 626.67 | 1364.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 |
| June | 5828.27 | 08-JUN-06:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.87 |
| July | 4870.81 | 03-JUL-06:01 | 0.00 | 805.72 | 1754.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.05 |
| August | 4454.78 | 14-AUG-06:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
| September | 5693.49 | 14-SEP-06:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 |
| October | 5936.80 | 12-OCT-06:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 |
| November | 4846.62 | 03-NOV-06:01 | 0.00 | 805.72 | 1754.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 |
| December | 2701.31 | 13-DEC-07:02 | 0.00 | 537.15 | 1169.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 981.60 | 0.00 | 447.62 | 544.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5936.80 | 451.21 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 133.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 124.07 | 01-JAN-18:01 | 1446.38 | 518.07 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.96 |
| February | 2441.57 | 28-FEB-17:52 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.07 |
| March | 3843.74 | 30-MAR-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 |
| April | 4333.37 | 15-APR-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 |
| May | 4367.53 | 14-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 |
| June | 4384.66 | 09-JUN-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.59 |
| July | 3932.12 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 |
| August | 3669.65 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 |
| September | 4411.64 | 14-SEP-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4448.40 | 03-OCT-20:12 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.60 |
| November | 4350.61 | 09-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.86 |
| December | 228.96 | 01-DEC-06:12 | 950.00 | 153.49 | 1271.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.51 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 124.07 | 741.00 | 153.49 | 1271.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4448.40 | 1446.38 | 518.07 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 171.87 | 22-JAN-18:40 | 413.25 | 148.02 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.73 |
| February | 3209.66 | 28-FEB-17:52 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 |
| March | 3921.76 | 13-MAR-20:52 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
| April | 4029.24 | 24-APR-21:02 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.27 |
| May | 4034.32 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 |
| June | 4019.64 | 07-JUN-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.61 |
| July | 3588.29 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
| August | 3353.54 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 |
| September | 4060.17 | 14-SEP-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4087.62 | 03-OCT-20:12 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 |
| November | 4029.07 | 09-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.61 |
| December | 508.01 | 13-DEC-21:02 | 1187.50 | 301.52 | 2501.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 171.87 | 413.25 | 148.02 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4087.62 | 1425.00 | 361.83 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 169.13 | 22-JAN-18:25 | 413.25 | 148.02 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 |
| February | 3305.83 | 28-FEB-17:52 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 |
| March | 3916.74 | 13-MAR-20:52 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 |
| April | 4023.94 | 24-APR-21:02 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 |
| May | 4029.07 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 |
| June | 4014.81 | 07-JUN-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 |
| July | 3584.52 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
| August | 3349.25 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 |
| September | 4055.50 | 14-SEP-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4083.48 | 03-OCT-20:12 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 |
| November | 4024.17 | 09-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 |
| December | 504.29 | 13-DEC-21:02 | 1187.50 | 301.52 | 2501.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 169.13 | 413.25 | 148.02 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4083.48 | 1425.00 | 361.83 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 588.53 | 29-JAN-17:52 | 1187.50 | 274.10 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 |
| February | 4115.58 | 28-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.18 |
| March | 4213.91 | 14-MAR-19:52 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.04 |
| April | 4196.59 | 24-APR-21:02 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 |
| May | 4209.00 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.84 |
| June | 4175.11 | 07-JUN-19:42 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 |
| July | 3736.99 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 |
| August | 3528.43 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 |
| September | 4219.69 | 14-SEP-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4252.92 | 14-OCT-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.65 |
| November | 4223.32 | 09-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.29 |
| December | 4077.51 | 10-DEC-19:22 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 588.53 | 1187.50 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4252.92 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 233.27 | 26-JAN-08:50 | 0.00 | 32.89 | 776.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.47 |
| February | 4143.55 | 28-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.14 |
| March | 4243.20 | 14-MAR-19:52 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.06 |
| April | 4226.53 | 24-APR-21:02 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.68 |
| May | 4239.44 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 |
| June | 4202.89 | 07-JUN-19:42 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 |
| July | 3797.79 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 |
| August | 3594.27 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 |
| September | 4250.10 | 14-SEP-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4284.33 | 14-OCT-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 |
| November | 4251.66 | 09-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 |
| December | 4099.41 | 10-DEC-19:22 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.19 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 233.27 | 0.00 | 32.89 | 776.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4284.33 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4149.42 | 29-JAN-17:52 | 1187.50 | 274.10 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.96 |
| February | 5484.43 | 26-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 |
| March | 5649.93 | 14-MAR-19:52 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.34 |
| April | 5638.19 | 24-APR-21:02 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.23 |
| May | 5626.03 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.30 |
| June | 5596.33 | 07-JUN-18:02 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 |
| July | 5047.98 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 |
| August | 4681.84 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 |
| September | 5607.55 | 13-SEP-18:42 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.12 |
| October | 5636.73 | 14-OCT-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 |
| November | 5593.62 | 06-NOV-13:02 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.19 |
| December | 5433.39 | 11-DEC-16:02 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4149.42 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | |
| Maximum of Months | 5649.93 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 180.51 | 22-JAN-19:40 | 206.62 | 87.71 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.23 |
| February | 5350.79 | 28-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.16 |
| March | 5496.67 | 14-MAR-19:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.24 |
| April | 5510.68 | 24-APR-21:02 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.45 |
| May | 5508.71 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 |
| June | 5482.40 | 07-JUN-18:02 | 1239.75 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 |
| July | 4938.76 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 |
| August | 4534.01 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 |
| September | 5476.21 | 14-SEP-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 5481.61 | 03-OCT-20:12 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 |
| November | 5268.68 | 06-NOV-19:12 | 1239.75 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.90 |
| December | 1747.76 | 13-DEC-21:02 | 1187.50 | 301.52 | 2501.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.36 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 180.51 | 206.62 | 87.71 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5510.68 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3431.68 | 29-JAN-17:52 | 1187.50 | 274.10 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.86 |
| February | 5108.28 | 26-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.88 |
| March | 5250.08 | 14-MAR-19:52 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.58 |
| April | 5229.47 | 14-APR-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.43 |
| May | 5235.95 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.53 |
| June | 5196.41 | 09-JUN-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.27 |
| July | 4674.97 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
| August | 4361.58 | 08-AUG-17:52 | 1425.00 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 5216.69 | 14-SEP-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 5246.59 | 14-OCT-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.78 |
| November | 5229.93 | 06-NOV-13:02 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.26 |
| December | 5026.96 | 10-DEC-19:22 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.90 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3431.68 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5250.08 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 157.27 | 21-JAN-24:00 | 237.50 | 13.71 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.93 |
| February | 4952.53 | 28-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.68 |
| March | 5053.70 | 14-MAR-19:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.83 |
| April | 5115.25 | 11-APR-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.94 |
| May | 5120.78 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 |
| June | 5067.76 | 09-JUN-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 |
| July | 4559.76 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 |
| August | 4197.12 | 08-AUG-17:52 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 5088.74 | 13-SEP-19:02 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.96 |
| October | 5091.49 | 03-OCT-20:12 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.66 |
| November | 4885.24 | 06-NOV-19:12 | 1239.75 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.69 |
| December | 1823.06 | 13-DEC-21:02 | 1187.50 | 301.52 | 2501.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.37 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 157.27 | 237.50 | 13.71 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5120.78 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 210.88 | 23-JAN-01:00 | 237.50 | 5.48 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.68 |
| February | 4492.69 | 28-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 |
| March | 4584.59 | 14-MAR-19:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.04 |
| April | 4605.47 | 24-APR-21:02 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.20 |
| May | 4629.33 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 |
| June | 4575.60 | 07-JUN-20:52 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
| July | 4073.85 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 |
| August | 3751.80 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
| September | 4601.18 | 13-SEP-19:02 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 |
| October | 4596.60 | 21-OCT-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 |
| November | 4567.80 | 09-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 |
| December | 3446.47 | 12-DEC-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 210.88 | 237.50 | 5.48 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | |
| Maximum of Months | 4629.33 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 210.78 | 23-JAN-01:00 | 237.50 | 5.48 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.65 |
| February | 4481.60 | 28-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.97 |
| March | 4573.60 | 14-MAR-19:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.08 |
| April | 4592.37 | 24-APR-21:02 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.14 |
| May | 4618.76 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 |
| June | 4564.24 | 07-JUN-20:52 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
| July | 4063.44 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 |
| August | 3741.75 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
| September | 4589.88 | 13-SEP-19:02 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 |
| October | 4585.27 | 21-OCT-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 |
| November | 4556.39 | 09-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 |
| December | 3421.55 | 12-DEC-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 210.78 | 237.50 | 5.48 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | |
| Maximum of Months | 4618.76 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4499.26 | 29-JAN-17:52 | 1187.50 | 274.10 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.07 |
| February | 4690.57 | 26-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 |
| March | 4790.11 | 14-MAR-19:52 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.59 |
| April | 4782.39 | 24-APR-21:02 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 |
| May | 4788.82 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 |
| June | 4741.54 | 09-JUN-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 |
| July | 4227.13 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 |
| August | 3936.62 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 |
| September | 4768.38 | 14-SEP-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4805.15 | 14-OCT-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.37 |
| November | 4773.66 | 06-NOV-13:02 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.57 |
| December | 4637.49 | 10-DEC-19:22 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3936.62 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4805.15 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4494.53 | 29-JAN-17:52 | 1187.50 | 274.10 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.09 |
| February | 4685.50 | 26-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 |
| March | 4784.69 | 14-MAR-19:52 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.59 |
| April | 4775.45 | 24-APR-21:02 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 |
| May | 4783.82 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.96 |
| June | 4736.83 | 09-JUN-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 |
| July | 4222.01 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 |
| August | 3931.61 | 30-AUG-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 |
| September | 4763.16 | 14-SEP-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4799.69 | 14-OCT-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.37 |
| November | 4768.92 | 06-NOV-13:02 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.59 |
| December | 4631.99 | 10-DEC-19:22 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.74 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3931.61 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4799.69 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5835.57 | 29-JAN-17:52 | 1187.50 | 274.10 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.22 |
| February | 6075.17 | 20-FEB-18:42 | 1425.00 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.39 |
| March | 6239.64 | 14-MAR-19:52 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.02 |
| April | 6312.94 | 24-APR-15:42 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.19 |
| May | 6231.68 | 12-MAY-18:32 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 |
| June | 6286.75 | 07-JUN-18:02 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.70 |
| July | 5611.04 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 |
| August | 5299.24 | 08-AUG-17:52 | 1425.00 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 6243.05 | 13-SEP-13:42 | 0.00 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.63 |
| October | 6320.37 | 22-OCT-17:42 | 950.00 | 296.04 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 |
| November | 6187.69 | 06-NOV-14:12 | 0.00 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.62 |
| December | 6015.55 | 11-DEC-16:02 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 5299.24 | 0.00 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6320.37 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 128.31 | 11-JAN-17:03 | 1235.00 | 548.21 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.92 |
| February | 5949.11 | 28-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.23 |
| March | 6147.09 | 14-MAR-19:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.42 |
| April | 6250.73 | 24-APR-17:22 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 |
| May | 6162.57 | 11-MAY-16:52 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 |
| June | 6219.40 | 07-JUN-18:02 | 1239.75 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.77 |
| July | 5549.29 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 |
| August | 5179.00 | 08-AUG-17:52 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 6160.25 | 18-SEP-18:22 | 1239.75 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.20 |
| October | 6126.68 | 22-OCT-17:52 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.37 |
| November | 5268.55 | 05-NOV-17:42 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 |
| December | 1371.99 | 12-DEC-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.37 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 128.31 | 741.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6250.73 | 1425.00 | 548.21 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5269.54 | 29-JAN-17:52 | 1187.50 | 274.10 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.21 |
| February | 5476.56 | 20-FEB-16:52 | 1425.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.03 |
| March | 5655.67 | 14-MAR-19:52 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.49 |
| April | 5716.54 | 24-APR-15:42 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 |
| May | 5696.43 | 09-MAY-15:32 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.46 |
| June | 5692.04 | 07-JUN-12:52 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.79 |
| July | 5044.58 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.22 |
| August | 4806.71 | 08-AUG-17:52 | 1425.00 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 5662.50 | 14-SEP-12:22 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 |
| October | 5669.36 | 03-OCT-14:02 | 0.00 | 115.13 | 2401.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.75 |
| November | 5652.16 | 06-NOV-13:02 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.90 |
| December | 5424.53 | 10-DEC-16:52 | 1425.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4806.71 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5716.54 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 93.89 | 31-JAN-24:00 | 237.50 | 13.71 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.37 |
| February | 5365.27 | 28-FEB-17:52 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.41 |
| March | 5552.37 | 14-MAR-19:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.20 |
| April | 5582.21 | 24-APR-17:22 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.81 |
| May | 5614.24 | 14-MAY-11:22 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 |
| June | 5620.92 | 07-JUN-13:22 | 356.25 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.08 |
| July | 4985.04 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.25 |
| August | 4722.43 | 26-AUG-08:52 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 |
| September | 5584.53 | 14-SEP-12:22 | 356.25 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 |
| October | 5563.66 | 03-OCT-20:12 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.92 |
| November | 4695.55 | 05-NOV-17:42 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 |
| December | 1040.63 | 12-DEC-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.36 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 93.89 | 237.50 | 13.71 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | |
| Maximum of Months | 5620.92 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 120.53 | 01-JAN-17:30 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.06 |
| February | 5010.63 | 28-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.08 |
| March | 5193.46 | 14-MAR-19:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.98 |
| April | 5200.09 | 24-APR-17:22 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.65 |
| May | 5192.14 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 |
| June | 5167.93 | 07-JUN-18:02 | 1239.75 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 |
| July | 4630.63 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 |
| August | 4301.31 | 08-AUG-17:52 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 5164.04 | 13-SEP-19:02 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 |
| October | 5165.41 | 03-OCT-20:12 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 |
| November | 4418.12 | 02-NOV-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 |
| December | 3068.14 | 12-DEC-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 120.53 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5200.09 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 120.55 | 01-JAN-17:30 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.08 |
| February | 4992.33 | 28-FEB-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.89 |
| March | 5170.81 | 14-MAR-19:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.90 |
| April | 5173.21 | 24-APR-21:02 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.85 |
| May | 5175.95 | 11-MAY-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 |
| June | 5156.03 | 07-JUN-13:22 | 356.25 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.08 |
| July | 4613.36 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 |
| August | 4287.99 | 08-AUG-17:52 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 5146.23 | 13-SEP-19:02 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 |
| October | 5153.28 | 03-OCT-20:12 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 |
| November | 4395.24 | 02-NOV-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 |
| December | 3015.06 | 12-DEC-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 120.55 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5175.95 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4955.65 | 29-JAN-17:52 | 1187.50 | 274.10 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.04 |
| February | 5150.31 | 20-FEB-18:42 | 1425.00 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.65 |
| March | 5310.60 | 14-MAR-19:52 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.59 |
| April | 5333.47 | 24-APR-15:42 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.53 |
| May | 5279.98 | 09-MAY-15:32 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
| June | 5248.52 | 07-JUN-18:02 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 |
| July | 4700.16 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 |
| August | 4435.47 | 08-AUG-17:52 | 1425.00 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 5283.07 | 13-SEP-13:42 | 0.00 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 |
| October | 5282.86 | 05-OCT-14:52 | 0.00 | 95.95 | 2001.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.43 |
| November | 5279.26 | 06-NOV-13:02 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 |
| December | 5077.88 | 10-DEC-16:52 | 1425.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.44 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4435.47 | 0.00 | 65.78 | 2001.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5333.47 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4940.83 | 29-JAN-17:52 | 1187.50 | 274.10 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.01 |
| February | 5133.34 | 20-FEB-18:42 | 1425.00 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.66 |
| March | 5293.93 | 14-MAR-19:52 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.58 |
| April | 5321.76 | 24-APR-15:42 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.90 |
| May | 5265.54 | 09-MAY-15:32 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.05 |
| June | 5232.83 | 07-JUN-18:02 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.98 |
| July | 4686.93 | 02-JUL-21:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 |
| August | 4425.05 | 08-AUG-17:52 | 1425.00 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 5270.51 | 13-SEP-13:42 | 0.00 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.45 |
| October | 5269.36 | 03-OCT-14:02 | 0.00 | 115.13 | 2401.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 |
| November | 5266.63 | 06-NOV-13:02 | 0.00 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.07 |
| December | 5061.89 | 10-DEC-16:52 | 1425.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.43 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4425.05 | 0.00 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5321.76 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.78 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.04 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.58 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | |
| Maximum of Months | 0.00 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.35 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | |
| Maximum of Months | 0.00 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.25 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.56 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.74 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.47 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | |
| Maximum of Months | 0.00 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.47 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.669909E+11 | 45612.34 | 07-JAN-17:00 | 0.398059E+11 | 28594.84 | 27-JAN-07:30 |
| February | 0.565608E+11 | 66247.06 | 12-FEB-07:10 | 0.359863E+11 | 28641.30 | 03-FEB-07:00 |
| March | 0.583487E+11 | 45408.45 | 30-MAR-16:10 | 0.384950E+11 | 27845.40 | 02-MAR-07:30 |
| April | 0.615277E+11 | 51642.55 | 02-APR-16:00 | 0.349487E+11 | 26582.95 | 01-APR-06:00 |
| May | 0.722820E+11 | 52458.36 | 27-MAY-17:00 | 0.332984E+11 | 24776.85 | 01-MAY-06:19 |
| June | 0.831990E+11 | 54326.36 | 26-JUN-19:49 | 0.298049E+11 | 23009.85 | 01-JUN-06:00 |
| July | 0.909295E+11 | 56087.10 | 08-JUL-16:10 | 0.292974E+11 | 21162.79 | 01-JUL-06:00 |
| August | 0.938694E+11 | 55265.51 | 31-AUG-16:40 | 0.291889E+11 | 21099.11 | 31-AUG-06:00 |
| September | 0.759874E+11 | 54907.20 | 16-SEP-16:00 | 0.295338E+11 | 22530.06 | 27-SEP-06:00 |
| October | 0.640441E+11 | 55102.57 | 19-OCT-16:10 | 0.329306E+11 | 24334.81 | 31-OCT-06:40 |
| November | 0.565634E+11 | 47902.97 | 05-NOV-16:19 | 0.346008E+11 | 26440.84 | 30-NOV-07:49 |
| December | 0.586815E+11 | 38757.74 | 12-DEC-17:49 | 0.382732E+11 | 27734.67 | 31-DEC-07:49 |
| Annual Sum or Average | 0.838984E+12 | 0.406164E+12 | ||||
| Minimum of Months | 0.565608E+11 | 38757.74 | 0.291889E+11 | 21099.11 | ||
| Maximum of Months | 0.938694E+11 | 66247.06 | 0.398059E+11 | 28641.30 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 0.618562E+10 | 0.327004E+10 | 0.385428E+11 | 0.00 | 0.743782E+10 | 38818862.27 | 0.113998E+11 | 0.115896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.559770E+10 | 0.279101E+10 | 0.348258E+11 | 0.00 | 0.617144E+10 | 35062198.18 | 0.609627E+10 | 0.104346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.621989E+10 | 0.285404E+10 | 0.385844E+11 | 0.00 | 0.608492E+10 | 38818862.27 | 0.375807E+09 | 0.419083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.599345E+10 | 0.252628E+10 | 0.373085E+11 | 0.00 | 0.704749E+10 | 37566640.91 | 0.173351E+09 | 0.844109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.620847E+10 | 0.240526E+10 | 0.385705E+11 | 0.00 | 0.916319E+10 | 38818862.27 | 0.00 | 0.158958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.601630E+10 | 0.223760E+10 | 0.373361E+11 | 0.00 | 0.115574E+11 | 37566640.91 | 0.00 | 0.260140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.618562E+10 | 0.234601E+10 | 0.385428E+11 | 0.00 | 0.129247E+11 | 38818862.27 | 0.00 | 0.308915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.621989E+10 | 0.251745E+10 | 0.385844E+11 | 0.00 | 0.134826E+11 | 38818862.27 | 0.00 | 0.330263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.599345E+10 | 0.265990E+10 | 0.373085E+11 | 0.00 | 0.100387E+11 | 37566640.91 | 0.00 | 0.199494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.619704E+10 | 0.299271E+10 | 0.385567E+11 | 0.00 | 0.727599E+10 | 38818862.27 | 0.151387E+09 | 0.883152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.599345E+10 | 0.310994E+10 | 0.373085E+11 | 0.00 | 0.578368E+10 | 37566640.91 | 0.117364E+10 | 0.315669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.618562E+10 | 0.332803E+10 | 0.385428E+11 | 0.00 | 0.590623E+10 | 38818862.27 | 0.384541E+10 | 0.834564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.729965E+11 | 0.330383E+11 | 0.454012E+12 | 0.00 | 0.102874E+12 | 0.457061E+09 | 0.232157E+11 | 0.152391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.559770E+10 | 0.223760E+10 | 0.348258E+11 | 0.00 | 0.578368E+10 | 35062198.18 | 0.00 | 0.115896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.621989E+10 | 0.332803E+10 | 0.385844E+11 | 0.00 | 0.134826E+11 | 38818862.27 | 0.113998E+11 | 0.330263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.398059E+11 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.359863E+11 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.384950E+11 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.349487E+11 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.332984E+11 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.298049E+11 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.292974E+11 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.291889E+11 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.295338E+11 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.329306E+11 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.346008E+11 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.382732E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.406164E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.291889E+11 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.398059E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 4040.47 | 01-JAN-19:10 | 2101.03 | 01-JAN-00:10 | 22246.15 | 03-JAN-17:10 | 0.00 | 6165.40 | 08-JAN-01:10 | 14.49 | 01-JAN-17:10 | 18260.00 | 10-JAN-07:10 |
| February | 4040.47 | 01-FEB-19:10 | 2101.03 | 01-FEB-00:10 | 22246.15 | 01-FEB-17:10 | 0.00 | 13031.43 | 12-FEB-05:00 | 14.49 | 01-FEB-06:10 | 35296.60 | 12-FEB-05:00 |
| March | 4040.47 | 01-MAR-19:10 | 2101.03 | 01-MAR-00:10 | 22246.15 | 01-MAR-17:10 | 0.00 | 6369.32 | 30-MAR-12:30 | 14.49 | 01-MAR-06:10 | 3222.19 | 19-MAR-06:49 |
| April | 4040.47 | 01-APR-18:10 | 2101.03 | 01-APR-00:10 | 22246.15 | 03-APR-16:10 | 0.00 | 7335.95 | 29-APR-17:10 | 14.49 | 01-APR-16:19 | 3499.18 | 06-APR-04:00 |
| May | 4040.47 | 01-MAY-18:10 | 2101.03 | 01-MAY-00:10 | 22246.15 | 01-MAY-16:10 | 0.00 | 8337.65 | 26-MAY-12:00 | 14.49 | 01-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 4040.47 | 01-JUN-18:10 | 2101.03 | 01-JUN-00:10 | 22246.15 | 01-JUN-16:10 | 0.00 | 8772.80 | 23-JUN-08:00 | 14.49 | 01-JUN-06:19 | 0.00 | 01-JUN-00:10 |
| July | 4040.47 | 01-JUL-18:10 | 2101.03 | 01-JUL-00:10 | 22246.15 | 03-JUL-16:10 | 0.00 | 8919.22 | 30-JUL-09:39 | 14.49 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 |
| August | 4040.47 | 01-AUG-18:10 | 2101.03 | 01-AUG-00:10 | 22246.15 | 01-AUG-16:10 | 0.00 | 8921.14 | 29-AUG-08:39 | 14.49 | 01-AUG-07:19 | 0.00 | 01-AUG-00:10 |
| September | 4040.47 | 01-SEP-18:10 | 2101.03 | 01-SEP-00:10 | 22246.15 | 01-SEP-16:10 | 0.00 | 8275.52 | 27-SEP-14:30 | 14.49 | 01-SEP-06:19 | 0.00 | 01-SEP-00:10 |
| October | 4040.47 | 01-OCT-18:10 | 2101.03 | 01-OCT-00:10 | 22246.15 | 02-OCT-16:10 | 0.00 | 8234.06 | 19-OCT-14:00 | 14.49 | 01-OCT-06:19 | 3005.88 | 26-OCT-05:00 |
| November | 4040.47 | 01-NOV-18:10 | 2101.03 | 01-NOV-00:10 | 22246.15 | 01-NOV-16:10 | 0.00 | 7016.15 | 05-NOV-15:00 | 14.49 | 01-NOV-06:10 | 7303.64 | 22-NOV-07:10 |
| December | 4040.47 | 01-DEC-19:10 | 2101.03 | 01-DEC-00:10 | 22246.15 | 01-DEC-17:10 | 0.00 | 4161.75 | 12-DEC-13:09 | 14.49 | 01-DEC-07:10 | 9616.71 | 04-DEC-07:10 |
| Annual Sum or Average | 0.00 | ||||||||||||
| Minimum of Months | 4040.47 | 2101.03 | 22246.15 | 0.00 | 4161.75 | 14.49 | 0.00 | ||||||
| Maximum of Months | 4040.47 | 2101.03 | 22246.15 | 0.00 | 13031.43 | 14.49 | 35296.60 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 3640.75 | 29-JAN-17:00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 14715.33 | 28-FEB-17:00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 17071.68 | 30-MAR-12:30 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 19540.40 | 29-APR-17:10 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 24170.85 | 26-MAY-12:00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 26241.99 | 23-JUN-08:00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 27048.59 | 19-JUL-11:20 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 27145.80 | 29-AUG-08:39 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 24419.94 | 06-SEP-08:39 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 23516.99 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 18561.18 | 05-NOV-15:00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 9330.85 | 12-DEC-14:50 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 3640.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 27145.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 45612.34 | 07-JAN-17:00 | 3020.75 | 22179.86 | 2101.03 | 0.00 | 5001.79 | 14.49 | 13294.42 | 0.00 | 0.00 |
| February | 66247.06 | 12-FEB-07:10 | 2425.88 | 15793.30 | 2101.03 | 0.00 | 13031.43 | 14.49 | 32880.93 | 0.00 | 0.00 |
| March | 45408.45 | 30-MAR-16:10 | 3020.75 | 22246.15 | 0.00 | 0.00 | 5769.95 | 14.49 | 0.00 | 14357.11 | 0.00 |
| April | 51642.55 | 02-APR-16:00 | 3020.75 | 22179.86 | 0.00 | 0.00 | 7149.88 | 14.49 | 0.00 | 19277.57 | 0.00 |
| May | 52458.36 | 27-MAY-17:00 | 3615.61 | 20849.51 | 0.00 | 0.00 | 7574.52 | 14.49 | 0.00 | 20404.23 | 0.00 |
| June | 54326.36 | 26-JUN-19:49 | 4040.47 | 17993.99 | 2101.03 | 0.00 | 8038.65 | 14.49 | 0.00 | 22137.73 | 0.00 |
| July | 56087.10 | 08-JUL-16:10 | 3020.75 | 22179.86 | 0.00 | 0.00 | 7596.08 | 14.49 | 0.00 | 23275.93 | 0.00 |
| August | 55265.51 | 31-AUG-16:40 | 3020.75 | 22246.15 | 0.00 | 0.00 | 7983.67 | 14.49 | 0.00 | 22000.46 | 0.00 |
| September | 54907.20 | 16-SEP-16:00 | 3020.75 | 22179.86 | 0.00 | 0.00 | 7801.57 | 14.49 | 0.00 | 21890.54 | 0.00 |
| October | 55102.57 | 19-OCT-16:10 | 3020.75 | 22246.15 | 0.00 | 0.00 | 7934.61 | 14.49 | 0.00 | 21886.57 | 0.00 |
| November | 47902.97 | 05-NOV-16:19 | 3020.75 | 22179.86 | 0.00 | 0.00 | 6417.13 | 14.49 | 0.00 | 16270.74 | 0.00 |
| December | 38757.74 | 12-DEC-17:49 | 3020.75 | 22246.15 | 2101.03 | 0.00 | 3930.06 | 14.49 | 0.00 | 7445.26 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||||||||
| Minimum of Months | 38757.74 | 2425.88 | 15793.30 | 0.00 | 0.00 | 3930.06 | 14.49 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 66247.06 | 4040.47 | 22246.15 | 2101.03 | 0.00 | 13031.43 | 14.49 | 32880.93 | 23275.93 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 28594.84 | 27-JAN-07:30 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 28641.30 | 03-FEB-07:00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 27845.40 | 02-MAR-07:30 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 26582.95 | 01-APR-06:00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 24776.85 | 01-MAY-06:19 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 23009.85 | 01-JUN-06:00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 21162.79 | 01-JUL-06:00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 21099.11 | 31-AUG-06:00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 22530.06 | 27-SEP-06:00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 24334.81 | 31-OCT-06:40 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 26440.84 | 30-NOV-07:49 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 27734.67 | 31-DEC-07:49 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21099.11 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28641.30 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.50 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
| February | 0.17 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.76 | 0.00 | 24.76 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.01 | 0.00 | 25.01 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 25.28 | 0.00 | 25.28 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.93 | 0.00 | 24.93 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.00 | 24.62 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.67 | 20.13 | 0.00 | 20.13 | 11.67 | 24.76 | 0.00 | 24.76 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.50 | 20.18 | 0.00 | 20.18 | 4.00 | 25.28 | 0.00 | 25.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.38 | 241.00 | 21.30 | 241.00 | 21.25 |
| February | 453.83 | 21.89 | 150.17 | 21.71 | 148.50 | 21.59 |
| March | 367.17 | 23.28 | 31.83 | 23.41 | 0.00 | 23.41 |
| April | 202.50 | 23.66 | 161.83 | 24.07 | 29.67 | 24.10 |
| May | 73.67 | 24.51 | 389.83 | 24.42 | 54.67 | 24.45 |
| June | 48.00 | 25.16 | 423.83 | 24.39 | 48.00 | 24.46 |
| July | 100.00 | 25.17 | 533.00 | 24.42 | 100.00 | 24.52 |
| August | 62.00 | 25.39 | 506.00 | 24.35 | 62.00 | 24.45 |
| September | 60.17 | 25.42 | 494.67 | 24.56 | 60.17 | 24.64 |
| October | 90.33 | 24.17 | 277.00 | 24.62 | 31.50 | 24.64 |
| November | 279.33 | 23.71 | 126.83 | 24.05 | 12.67 | 24.09 |
| December | 494.50 | 22.38 | 18.33 | 22.45 | 3.00 | 22.46 |
| Annual Sum or Average | 2764.50 | 22.85 | 3354.33 | 23.50 | 791.17 | 23.45 |
| Minimum of Months | 48.00 | 21.38 | 18.33 | 21.30 | 0.00 | 21.25 |
| Maximum of Months | 533.00 | 25.42 | 533.00 | 24.62 | 241.00 | 24.64 |
Report: ComfortReportSimple55Monthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.14 | 556.67 | 21.13 | 556.67 | 21.12 |
| February | 672.00 | 21.51 | 291.00 | 21.39 | 291.00 | 21.32 |
| March | 679.83 | 22.61 | 11.83 | 22.63 | 2.00 | 22.63 |
| April | 395.17 | 23.43 | 173.67 | 23.76 | 40.50 | 23.79 |
| May | 141.17 | 24.50 | 569.83 | 24.43 | 110.83 | 24.46 |
| June | 84.83 | 25.07 | 639.17 | 24.40 | 84.83 | 24.47 |
| July | 154.83 | 25.16 | 744.00 | 24.44 | 154.83 | 24.55 |
| August | 125.00 | 25.27 | 744.00 | 24.40 | 125.00 | 24.51 |
| September | 110.50 | 25.43 | 691.50 | 24.64 | 110.50 | 24.74 |
| October | 227.00 | 24.03 | 348.00 | 24.53 | 72.50 | 24.57 |
| November | 543.67 | 23.16 | 104.33 | 23.39 | 21.83 | 23.42 |
| December | 744.00 | 21.55 | 154.17 | 21.49 | 154.17 | 21.44 |
| Annual Sum or Average | 4622.00 | 22.58 | 5028.17 | 23.19 | 1724.67 | 23.12 |
| Minimum of Months | 84.83 | 21.14 | 11.83 | 21.13 | 2.00 | 21.12 |
| Maximum of Months | 744.00 | 25.43 | 744.00 | 24.64 | 556.67 | 24.74 |
Report: ComfortReportSimple55Monthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 140.00 | 21.48 | 83.33 | 21.34 | 83.33 | 21.28 |
| February | 125.50 | 22.01 | 49.33 | 21.76 | 49.33 | 21.61 |
| March | 103.50 | 23.44 | 27.17 | 23.56 | 0.00 | 23.56 |
| April | 43.17 | 23.69 | 57.83 | 23.87 | 0.00 | 23.87 |
| May | 4.67 | 24.00 | 134.17 | 24.00 | 0.67 | 24.00 |
| June | 0.33 | 24.00 | 149.67 | 24.00 | 0.33 | 24.00 |
| July | 1.50 | 24.00 | 140.00 | 24.00 | 1.50 | 24.00 |
| August | 2.67 | 24.00 | 161.00 | 24.00 | 2.67 | 24.00 |
| September | 0.00 | 0.00 | 139.00 | 24.00 | 0.00 | 24.00 |
| October | 19.00 | 23.58 | 92.17 | 23.93 | 0.83 | 23.93 |
| November | 62.00 | 23.61 | 21.67 | 23.71 | 0.00 | 23.71 |
| December | 120.83 | 22.63 | 17.50 | 22.62 | 9.00 | 22.52 |
| Annual Sum or Average | 623.17 | 22.60 | 1072.83 | 23.24 | 147.67 | 23.08 |
| Minimum of Months | 0.00 | 0.00 | 17.50 | 21.34 | 0.00 | 21.28 |
| Maximum of Months | 140.00 | 24.00 | 161.00 | 24.00 | 83.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.14 | 557.67 | 21.13 | 557.67 | 21.12 |
| February | 672.00 | 21.55 | 294.67 | 21.41 | 294.67 | 21.34 |
| March | 688.17 | 22.64 | 7.50 | 22.65 | 0.50 | 22.65 |
| April | 397.67 | 23.46 | 180.83 | 23.80 | 42.67 | 23.83 |
| May | 136.00 | 24.55 | 577.17 | 24.47 | 110.50 | 24.50 |
| June | 83.83 | 25.19 | 648.67 | 24.44 | 83.83 | 24.51 |
| July | 148.33 | 25.27 | 744.00 | 24.46 | 148.33 | 24.58 |
| August | 126.50 | 25.29 | 744.00 | 24.41 | 126.50 | 24.52 |
| September | 109.00 | 25.50 | 689.83 | 24.68 | 109.00 | 24.77 |
| October | 217.83 | 24.04 | 357.00 | 24.54 | 69.50 | 24.58 |
| November | 553.50 | 23.21 | 101.00 | 23.41 | 23.33 | 23.45 |
| December | 743.83 | 21.55 | 152.17 | 21.49 | 152.17 | 21.44 |
| Annual Sum or Average | 4620.67 | 22.60 | 5054.50 | 23.21 | 1718.67 | 23.14 |
| Minimum of Months | 83.83 | 21.14 | 7.50 | 21.13 | 0.50 | 21.12 |
| Maximum of Months | 744.00 | 25.50 | 744.00 | 24.68 | 557.67 | 24.77 |
Report: ComfortReportSimple55Monthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.24 | 463.17 | 21.19 | 463.17 | 21.17 |
| February | 672.00 | 21.77 | 256.33 | 21.59 | 256.33 | 21.48 |
| March | 640.83 | 23.15 | 16.00 | 23.18 | 0.00 | 23.18 |
| April | 304.00 | 23.76 | 207.17 | 24.08 | 30.67 | 24.10 |
| May | 119.83 | 24.71 | 554.33 | 24.50 | 92.33 | 24.55 |
| June | 88.33 | 25.10 | 636.00 | 24.41 | 88.33 | 24.48 |
| July | 156.67 | 25.18 | 744.00 | 24.45 | 156.67 | 24.56 |
| August | 132.83 | 25.19 | 744.00 | 24.39 | 132.83 | 24.49 |
| September | 116.33 | 25.43 | 691.00 | 24.65 | 116.33 | 24.75 |
| October | 146.33 | 24.40 | 350.50 | 24.66 | 61.17 | 24.71 |
| November | 507.33 | 23.63 | 113.00 | 23.81 | 21.50 | 23.84 |
| December | 736.17 | 22.01 | 22.50 | 22.00 | 22.50 | 21.99 |
| Annual Sum or Average | 4364.67 | 22.84 | 4798.00 | 23.40 | 1441.83 | 23.35 |
| Minimum of Months | 88.33 | 21.24 | 16.00 | 21.19 | 0.00 | 21.17 |
| Maximum of Months | 744.00 | 25.43 | 744.00 | 24.66 | 463.17 | 24.75 |
Report: ComfortReportSimple55Monthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.24 | 463.50 | 21.19 | 463.50 | 21.17 |
| February | 672.00 | 21.77 | 256.17 | 21.59 | 256.17 | 21.48 |
| March | 640.50 | 23.15 | 16.50 | 23.18 | 0.00 | 23.18 |
| April | 304.33 | 23.76 | 206.67 | 24.08 | 31.00 | 24.11 |
| May | 119.67 | 24.71 | 556.00 | 24.50 | 92.33 | 24.55 |
| June | 88.33 | 25.10 | 635.83 | 24.41 | 88.33 | 24.48 |
| July | 156.33 | 25.19 | 744.00 | 24.45 | 156.33 | 24.56 |
| August | 132.67 | 25.19 | 744.00 | 24.39 | 132.67 | 24.49 |
| September | 116.17 | 25.43 | 691.17 | 24.66 | 116.17 | 24.75 |
| October | 146.50 | 24.40 | 351.00 | 24.66 | 61.33 | 24.71 |
| November | 507.33 | 23.64 | 113.17 | 23.82 | 21.50 | 23.85 |
| December | 736.17 | 22.01 | 22.17 | 22.00 | 22.17 | 21.99 |
| Annual Sum or Average | 4364.00 | 22.84 | 4800.17 | 23.40 | 1441.50 | 23.35 |
| Minimum of Months | 88.33 | 21.24 | 16.50 | 21.19 | 0.00 | 21.17 |
| Maximum of Months | 744.00 | 25.43 | 744.00 | 24.66 | 463.50 | 24.75 |
Report: ComfortReportSimple55Monthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.82 | 119.83 | 21.70 | 119.83 | 21.61 |
| February | 439.00 | 22.24 | 70.33 | 22.13 | 65.17 | 22.01 |
| March | 312.67 | 23.74 | 46.50 | 23.88 | 0.00 | 23.88 |
| April | 135.67 | 23.97 | 182.33 | 24.33 | 19.17 | 24.36 |
| May | 62.17 | 24.72 | 382.50 | 24.47 | 43.67 | 24.52 |
| June | 49.17 | 25.20 | 427.83 | 24.39 | 49.17 | 24.46 |
| July | 99.00 | 25.23 | 533.00 | 24.43 | 99.00 | 24.54 |
| August | 64.50 | 25.35 | 506.00 | 24.34 | 64.50 | 24.45 |
| September | 60.33 | 25.45 | 500.83 | 24.57 | 60.33 | 24.65 |
| October | 50.33 | 24.63 | 296.17 | 24.72 | 29.83 | 24.75 |
| November | 220.17 | 23.98 | 144.67 | 24.32 | 12.50 | 24.36 |
| December | 482.33 | 23.25 | 28.00 | 23.31 | 3.00 | 23.32 |
| Annual Sum or Average | 2508.33 | 23.22 | 3238.00 | 23.79 | 566.17 | 23.80 |
| Minimum of Months | 49.17 | 21.82 | 28.00 | 21.70 | 0.00 | 21.61 |
| Maximum of Months | 533.00 | 25.45 | 533.00 | 24.72 | 119.83 | 24.75 |
Report: ComfortReportSimple55Monthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.69 | 148.33 | 21.57 | 148.33 | 21.49 |
| February | 440.33 | 22.18 | 93.17 | 22.03 | 88.00 | 21.90 |
| March | 314.00 | 23.72 | 46.33 | 23.86 | 0.00 | 23.86 |
| April | 134.83 | 23.97 | 185.83 | 24.34 | 18.83 | 24.37 |
| May | 58.67 | 24.77 | 395.17 | 24.48 | 41.50 | 24.53 |
| June | 44.17 | 25.33 | 436.83 | 24.41 | 44.17 | 24.49 |
| July | 92.00 | 25.39 | 533.00 | 24.47 | 92.00 | 24.58 |
| August | 58.17 | 25.54 | 506.00 | 24.37 | 58.17 | 24.48 |
| September | 56.83 | 25.58 | 504.67 | 24.59 | 56.83 | 24.68 |
| October | 51.67 | 24.61 | 300.33 | 24.72 | 29.50 | 24.76 |
| November | 223.50 | 23.97 | 142.83 | 24.30 | 12.83 | 24.34 |
| December | 485.33 | 23.16 | 27.33 | 23.23 | 3.00 | 23.23 |
| Annual Sum or Average | 2492.50 | 23.16 | 3319.83 | 23.75 | 593.17 | 23.75 |
| Minimum of Months | 44.17 | 21.69 | 27.33 | 21.57 | 0.00 | 21.49 |
| Maximum of Months | 533.00 | 25.58 | 533.00 | 24.72 | 148.33 | 24.76 |
Report: ComfortReportSimple55Monthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 529.17 | 21.85 | 139.00 | 21.70 | 139.00 | 21.60 |
| February | 396.83 | 22.25 | 102.17 | 22.26 | 75.83 | 22.10 |
| March | 240.83 | 23.74 | 140.00 | 24.19 | 0.00 | 24.19 |
| April | 81.50 | 24.00 | 262.00 | 24.66 | 11.00 | 24.68 |
| May | 43.67 | 25.05 | 429.00 | 24.58 | 33.00 | 24.64 |
| June | 43.83 | 25.22 | 425.17 | 24.40 | 43.83 | 24.47 |
| July | 97.17 | 25.22 | 533.00 | 24.42 | 97.17 | 24.53 |
| August | 72.67 | 25.12 | 506.00 | 24.31 | 72.67 | 24.40 |
| September | 65.17 | 25.22 | 475.33 | 24.51 | 65.17 | 24.59 |
| October | 114.17 | 24.01 | 259.83 | 24.55 | 39.00 | 24.56 |
| November | 293.33 | 23.58 | 119.67 | 23.96 | 12.33 | 23.99 |
| December | 491.83 | 22.43 | 23.00 | 22.53 | 2.17 | 22.54 |
| Annual Sum or Average | 2470.17 | 23.02 | 3414.17 | 23.75 | 591.17 | 23.74 |
| Minimum of Months | 43.67 | 21.85 | 23.00 | 21.70 | 0.00 | 21.60 |
| Maximum of Months | 529.17 | 25.22 | 533.00 | 24.66 | 139.00 | 24.68 |
Report: ComfortReportSimple55Monthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.29 | 424.67 | 21.23 | 424.67 | 21.19 |
| February | 631.83 | 22.03 | 222.50 | 21.85 | 211.33 | 21.71 |
| March | 456.83 | 23.55 | 141.67 | 23.85 | 0.00 | 23.85 |
| April | 168.67 | 23.88 | 324.67 | 24.54 | 18.67 | 24.56 |
| May | 93.00 | 25.09 | 630.67 | 24.66 | 74.50 | 24.73 |
| June | 79.50 | 25.14 | 642.33 | 24.41 | 79.50 | 24.48 |
| July | 153.17 | 25.18 | 744.00 | 24.44 | 153.17 | 24.55 |
| August | 140.50 | 25.04 | 744.00 | 24.35 | 140.50 | 24.45 |
| September | 123.00 | 25.16 | 662.50 | 24.57 | 123.00 | 24.65 |
| October | 291.83 | 23.88 | 328.33 | 24.35 | 78.00 | 24.39 |
| November | 562.33 | 23.00 | 102.17 | 23.21 | 25.50 | 23.22 |
| December | 720.83 | 21.60 | 150.00 | 21.56 | 142.50 | 21.51 |
| Annual Sum or Average | 4165.50 | 22.76 | 5117.50 | 23.42 | 1471.33 | 23.36 |
| Minimum of Months | 79.50 | 21.29 | 102.17 | 21.23 | 0.00 | 21.19 |
| Maximum of Months | 744.00 | 25.18 | 744.00 | 24.66 | 424.67 | 24.73 |
Report: ComfortReportSimple55Monthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 529.00 | 21.84 | 143.67 | 21.69 | 143.67 | 21.59 |
| February | 397.00 | 22.25 | 101.17 | 22.26 | 73.83 | 22.11 |
| March | 250.00 | 23.73 | 121.50 | 24.08 | 0.00 | 24.08 |
| April | 85.17 | 23.98 | 256.83 | 24.63 | 11.33 | 24.65 |
| May | 44.17 | 25.08 | 425.00 | 24.61 | 32.33 | 24.66 |
| June | 44.50 | 25.26 | 429.83 | 24.42 | 44.50 | 24.49 |
| July | 95.33 | 25.29 | 533.00 | 24.43 | 95.33 | 24.55 |
| August | 76.17 | 25.09 | 506.00 | 24.32 | 76.17 | 24.41 |
| September | 64.50 | 25.25 | 474.67 | 24.52 | 64.50 | 24.60 |
| October | 116.50 | 23.99 | 257.67 | 24.54 | 39.00 | 24.55 |
| November | 295.00 | 23.59 | 117.50 | 23.95 | 12.50 | 23.98 |
| December | 491.83 | 22.44 | 21.83 | 22.53 | 2.67 | 22.54 |
| Annual Sum or Average | 2489.17 | 23.03 | 3388.67 | 23.74 | 595.83 | 23.74 |
| Minimum of Months | 44.17 | 21.84 | 21.83 | 21.69 | 0.00 | 21.59 |
| Maximum of Months | 529.00 | 25.29 | 533.00 | 24.63 | 143.67 | 24.66 |
Report: ComfortReportSimple55Monthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.29 | 438.67 | 21.22 | 438.67 | 21.19 |
| February | 630.33 | 22.06 | 227.00 | 21.84 | 219.50 | 21.69 |
| March | 461.33 | 23.58 | 136.33 | 23.85 | 0.00 | 23.85 |
| April | 163.33 | 23.94 | 330.83 | 24.58 | 19.17 | 24.61 |
| May | 85.50 | 25.21 | 635.67 | 24.72 | 70.50 | 24.79 |
| June | 77.33 | 25.28 | 650.50 | 24.46 | 77.33 | 24.53 |
| July | 147.00 | 25.28 | 744.00 | 24.46 | 147.00 | 24.58 |
| August | 140.17 | 25.09 | 744.00 | 24.37 | 140.17 | 24.47 |
| September | 120.50 | 25.24 | 665.17 | 24.61 | 120.50 | 24.70 |
| October | 279.33 | 23.87 | 332.50 | 24.34 | 77.83 | 24.39 |
| November | 578.17 | 23.06 | 96.33 | 23.27 | 23.33 | 23.29 |
| December | 724.00 | 21.61 | 159.83 | 21.56 | 152.00 | 21.51 |
| Annual Sum or Average | 4151.00 | 22.78 | 5160.83 | 23.43 | 1486.00 | 23.37 |
| Minimum of Months | 77.33 | 21.29 | 96.33 | 21.22 | 0.00 | 21.19 |
| Maximum of Months | 744.00 | 25.28 | 744.00 | 24.72 | 438.67 | 24.79 |
Report: ComfortReportSimple55Monthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.55 | 327.67 | 21.42 | 327.67 | 21.35 |
| February | 609.17 | 22.24 | 174.50 | 22.02 | 168.00 | 21.86 |
| March | 422.83 | 23.87 | 139.17 | 24.08 | 0.00 | 24.08 |
| April | 162.00 | 24.06 | 293.50 | 24.56 | 18.50 | 24.59 |
| May | 94.33 | 25.08 | 601.17 | 24.66 | 75.33 | 24.73 |
| June | 85.83 | 25.11 | 631.00 | 24.41 | 85.83 | 24.48 |
| July | 157.33 | 25.13 | 744.00 | 24.43 | 157.33 | 24.53 |
| August | 150.67 | 24.95 | 744.00 | 24.34 | 150.67 | 24.43 |
| September | 124.50 | 25.19 | 660.17 | 24.59 | 124.50 | 24.67 |
| October | 180.50 | 24.25 | 316.83 | 24.52 | 64.83 | 24.57 |
| November | 508.67 | 23.52 | 109.00 | 23.72 | 18.50 | 23.75 |
| December | 709.67 | 22.17 | 38.17 | 22.18 | 28.17 | 22.16 |
| Annual Sum or Average | 3949.50 | 23.04 | 4779.17 | 23.61 | 1219.33 | 23.59 |
| Minimum of Months | 85.83 | 21.55 | 38.17 | 21.42 | 0.00 | 21.35 |
| Maximum of Months | 744.00 | 25.19 | 744.00 | 24.66 | 327.67 | 24.73 |
Report: ComfortReportSimple55Monthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.55 | 328.17 | 21.42 | 328.17 | 21.35 |
| February | 609.17 | 22.24 | 174.67 | 22.02 | 168.33 | 21.86 |
| March | 422.83 | 23.87 | 139.00 | 24.08 | 0.00 | 24.08 |
| April | 161.33 | 24.06 | 293.00 | 24.56 | 18.50 | 24.59 |
| May | 93.33 | 25.09 | 602.33 | 24.67 | 74.67 | 24.73 |
| June | 85.67 | 25.12 | 631.00 | 24.41 | 85.67 | 24.49 |
| July | 157.17 | 25.13 | 744.00 | 24.43 | 157.17 | 24.53 |
| August | 150.67 | 24.95 | 744.00 | 24.34 | 150.67 | 24.43 |
| September | 124.33 | 25.19 | 660.17 | 24.59 | 124.33 | 24.67 |
| October | 179.50 | 24.25 | 317.33 | 24.52 | 64.33 | 24.58 |
| November | 508.50 | 23.53 | 108.83 | 23.73 | 18.50 | 23.75 |
| December | 709.67 | 22.17 | 37.50 | 22.18 | 27.50 | 22.16 |
| Annual Sum or Average | 3946.17 | 23.04 | 4780.00 | 23.61 | 1217.83 | 23.59 |
| Minimum of Months | 85.67 | 21.55 | 37.50 | 21.42 | 0.00 | 21.35 |
| Maximum of Months | 744.00 | 25.19 | 744.00 | 24.67 | 328.17 | 24.73 |
Report: ComfortReportSimple55Monthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 524.67 | 22.67 | 51.83 | 22.55 | 50.50 | 22.44 |
| February | 328.17 | 22.73 | 50.83 | 22.93 | 15.00 | 22.86 |
| March | 198.00 | 23.95 | 133.83 | 24.31 | 0.00 | 24.31 |
| April | 65.00 | 24.19 | 249.83 | 24.69 | 11.50 | 24.72 |
| May | 44.33 | 25.12 | 410.33 | 24.59 | 35.00 | 24.65 |
| June | 48.83 | 25.19 | 421.33 | 24.39 | 48.83 | 24.47 |
| July | 100.67 | 25.18 | 533.00 | 24.41 | 100.67 | 24.52 |
| August | 78.67 | 25.02 | 506.00 | 24.30 | 78.67 | 24.38 |
| September | 65.50 | 25.24 | 480.00 | 24.52 | 65.50 | 24.60 |
| October | 54.67 | 24.51 | 270.50 | 24.74 | 32.00 | 24.76 |
| November | 245.50 | 23.93 | 137.00 | 24.28 | 12.33 | 24.32 |
| December | 476.17 | 23.35 | 31.67 | 23.43 | 3.00 | 23.44 |
| Annual Sum or Average | 2230.17 | 23.54 | 3276.17 | 24.06 | 453.00 | 24.10 |
| Minimum of Months | 44.33 | 22.67 | 31.67 | 22.55 | 0.00 | 22.44 |
| Maximum of Months | 524.67 | 25.24 | 533.00 | 24.74 | 100.67 | 24.76 |
Report: ComfortReportSimple55Monthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 524.67 | 22.66 | 52.17 | 22.55 | 50.33 | 22.44 |
| February | 327.83 | 22.73 | 51.00 | 22.94 | 15.00 | 22.87 |
| March | 199.00 | 23.95 | 133.67 | 24.31 | 0.00 | 24.31 |
| April | 65.00 | 24.19 | 250.00 | 24.69 | 11.50 | 24.72 |
| May | 44.17 | 25.12 | 412.00 | 24.59 | 34.67 | 24.65 |
| June | 49.17 | 25.20 | 421.83 | 24.39 | 49.17 | 24.47 |
| July | 100.67 | 25.17 | 533.00 | 24.41 | 100.67 | 24.52 |
| August | 78.67 | 25.02 | 506.00 | 24.30 | 78.67 | 24.38 |
| September | 65.50 | 25.24 | 480.00 | 24.52 | 65.50 | 24.60 |
| October | 54.50 | 24.51 | 270.67 | 24.74 | 31.83 | 24.76 |
| November | 245.50 | 23.93 | 136.50 | 24.28 | 12.33 | 24.32 |
| December | 476.17 | 23.35 | 31.67 | 23.43 | 3.00 | 23.44 |
| Annual Sum or Average | 2230.83 | 23.54 | 3278.50 | 24.06 | 452.67 | 24.10 |
| Minimum of Months | 44.17 | 22.66 | 31.67 | 22.55 | 0.00 | 22.44 |
| Maximum of Months | 524.67 | 25.24 | 533.00 | 24.74 | 100.67 | 24.76 |
Report: ComfortReportSimple55Monthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 531.17 | 21.40 | 350.67 | 21.28 | 350.67 | 21.23 |
| February | 430.67 | 21.70 | 208.33 | 21.65 | 188.83 | 21.52 |
| March | 331.33 | 22.51 | 129.67 | 22.97 | 36.17 | 22.83 |
| April | 200.67 | 23.24 | 230.50 | 24.13 | 26.50 | 24.13 |
| May | 95.50 | 24.17 | 369.67 | 24.50 | 44.83 | 24.54 |
| June | 89.50 | 24.53 | 418.33 | 24.33 | 61.67 | 24.39 |
| July | 124.83 | 24.88 | 529.83 | 24.37 | 124.83 | 24.45 |
| August | 136.67 | 24.56 | 504.50 | 24.26 | 136.67 | 24.31 |
| September | 126.33 | 24.41 | 413.67 | 24.41 | 89.67 | 24.47 |
| October | 306.00 | 22.96 | 222.33 | 23.68 | 67.00 | 23.71 |
| November | 407.83 | 22.32 | 158.67 | 22.56 | 88.67 | 22.46 |
| December | 508.50 | 21.52 | 243.83 | 21.43 | 234.83 | 21.36 |
| Annual Sum or Average | 3289.00 | 22.49 | 3780.00 | 23.12 | 1450.33 | 23.02 |
| Minimum of Months | 89.50 | 21.40 | 129.67 | 21.28 | 26.50 | 21.23 |
| Maximum of Months | 531.17 | 24.88 | 529.83 | 24.50 | 350.67 | 24.54 |
Report: ComfortReportSimple55Monthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.18 | 604.50 | 21.15 | 604.50 | 21.13 |
| February | 649.17 | 21.55 | 353.67 | 21.46 | 340.50 | 21.37 |
| March | 564.67 | 22.23 | 177.50 | 22.46 | 82.67 | 22.32 |
| April | 311.00 | 23.01 | 323.33 | 23.89 | 43.00 | 23.85 |
| May | 159.00 | 24.33 | 568.83 | 24.54 | 91.00 | 24.60 |
| June | 130.33 | 24.66 | 634.50 | 24.36 | 100.00 | 24.43 |
| July | 181.00 | 24.92 | 740.67 | 24.39 | 181.00 | 24.48 |
| August | 212.17 | 24.67 | 740.33 | 24.31 | 212.17 | 24.38 |
| September | 209.83 | 24.41 | 591.67 | 24.44 | 146.67 | 24.51 |
| October | 511.67 | 22.63 | 278.00 | 23.28 | 104.00 | 23.33 |
| November | 650.83 | 21.90 | 246.00 | 21.96 | 196.67 | 21.88 |
| December | 728.33 | 21.27 | 472.17 | 21.23 | 466.67 | 21.20 |
| Annual Sum or Average | 5052.00 | 22.31 | 5731.17 | 22.92 | 2568.83 | 22.81 |
| Minimum of Months | 130.33 | 21.18 | 177.50 | 21.15 | 43.00 | 21.13 |
| Maximum of Months | 744.00 | 24.92 | 740.67 | 24.54 | 604.50 | 24.60 |
Report: ComfortReportSimple55Monthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 531.33 | 21.39 | 354.17 | 21.27 | 354.17 | 21.22 |
| February | 428.50 | 21.68 | 212.17 | 21.65 | 189.67 | 21.52 |
| March | 340.83 | 22.51 | 114.67 | 22.84 | 35.33 | 22.72 |
| April | 202.67 | 23.15 | 226.17 | 24.04 | 23.33 | 24.01 |
| May | 92.33 | 24.24 | 371.67 | 24.53 | 44.83 | 24.58 |
| June | 91.17 | 24.57 | 417.83 | 24.36 | 65.17 | 24.42 |
| July | 123.83 | 24.94 | 529.50 | 24.39 | 123.83 | 24.47 |
| August | 148.00 | 24.54 | 503.33 | 24.26 | 148.00 | 24.31 |
| September | 128.67 | 24.40 | 413.50 | 24.41 | 91.33 | 24.47 |
| October | 303.83 | 22.92 | 226.67 | 23.65 | 66.00 | 23.67 |
| November | 408.50 | 22.32 | 155.17 | 22.55 | 88.00 | 22.45 |
| December | 510.00 | 21.51 | 244.17 | 21.43 | 235.17 | 21.35 |
| Annual Sum or Average | 3309.67 | 22.48 | 3769.00 | 23.11 | 1464.83 | 23.01 |
| Minimum of Months | 91.17 | 21.39 | 114.67 | 21.27 | 23.33 | 21.22 |
| Maximum of Months | 531.33 | 24.94 | 529.50 | 24.53 | 354.17 | 24.58 |
Report: ComfortReportSimple55Monthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.18 | 608.17 | 21.14 | 608.17 | 21.13 |
| February | 651.83 | 21.58 | 342.83 | 21.45 | 336.17 | 21.36 |
| March | 573.67 | 22.27 | 164.33 | 22.49 | 74.00 | 22.37 |
| April | 300.00 | 23.06 | 330.67 | 23.95 | 38.67 | 23.91 |
| May | 147.33 | 24.54 | 581.50 | 24.66 | 91.00 | 24.72 |
| June | 130.50 | 24.87 | 642.83 | 24.44 | 104.67 | 24.53 |
| July | 175.83 | 25.02 | 740.50 | 24.42 | 175.83 | 24.52 |
| August | 215.83 | 24.71 | 740.17 | 24.33 | 215.83 | 24.40 |
| September | 202.17 | 24.50 | 600.17 | 24.49 | 144.00 | 24.57 |
| October | 503.17 | 22.69 | 271.50 | 23.29 | 107.33 | 23.36 |
| November | 658.17 | 21.89 | 234.00 | 21.94 | 191.00 | 21.87 |
| December | 729.00 | 21.25 | 483.17 | 21.21 | 478.67 | 21.19 |
| Annual Sum or Average | 5031.50 | 22.33 | 5739.83 | 22.94 | 2565.33 | 22.83 |
| Minimum of Months | 130.50 | 21.18 | 164.33 | 21.14 | 38.67 | 21.13 |
| Maximum of Months | 744.00 | 25.02 | 740.50 | 24.66 | 608.17 | 24.72 |
Report: ComfortReportSimple55Monthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.21 | 579.33 | 21.16 | 579.33 | 21.14 |
| February | 655.00 | 21.71 | 303.00 | 21.53 | 299.67 | 21.43 |
| March | 564.83 | 22.45 | 129.83 | 22.65 | 43.67 | 22.56 |
| April | 282.83 | 23.18 | 298.83 | 23.97 | 31.33 | 23.95 |
| May | 131.50 | 24.56 | 580.33 | 24.57 | 79.50 | 24.62 |
| June | 114.17 | 24.79 | 628.67 | 24.38 | 90.33 | 24.45 |
| July | 172.67 | 24.99 | 744.00 | 24.40 | 172.67 | 24.50 |
| August | 211.83 | 24.69 | 743.83 | 24.32 | 211.83 | 24.39 |
| September | 175.00 | 24.70 | 604.50 | 24.50 | 139.00 | 24.58 |
| October | 489.33 | 22.94 | 259.33 | 23.45 | 96.33 | 23.52 |
| November | 641.83 | 22.02 | 198.33 | 22.12 | 145.83 | 22.05 |
| December | 718.83 | 21.30 | 407.50 | 21.26 | 399.17 | 21.23 |
| Annual Sum or Average | 4901.83 | 22.40 | 5477.50 | 23.00 | 2288.67 | 22.90 |
| Minimum of Months | 114.17 | 21.21 | 129.83 | 21.16 | 31.33 | 21.14 |
| Maximum of Months | 744.00 | 24.99 | 744.00 | 24.57 | 579.33 | 24.62 |
Report: ComfortReportSimple55Monthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.21 | 578.83 | 21.16 | 578.83 | 21.14 |
| February | 654.50 | 21.71 | 302.33 | 21.53 | 299.50 | 21.43 |
| March | 567.17 | 22.45 | 130.00 | 22.65 | 44.17 | 22.56 |
| April | 281.33 | 23.18 | 299.50 | 23.98 | 31.00 | 23.96 |
| May | 130.50 | 24.57 | 580.33 | 24.57 | 79.33 | 24.63 |
| June | 114.33 | 24.79 | 630.00 | 24.38 | 90.67 | 24.45 |
| July | 171.50 | 25.00 | 744.00 | 24.40 | 171.50 | 24.50 |
| August | 211.83 | 24.69 | 743.83 | 24.32 | 211.83 | 24.39 |
| September | 174.83 | 24.71 | 605.50 | 24.51 | 139.00 | 24.58 |
| October | 487.33 | 22.94 | 260.83 | 23.45 | 96.67 | 23.52 |
| November | 642.00 | 22.01 | 198.33 | 22.11 | 145.83 | 22.05 |
| December | 719.50 | 21.30 | 407.50 | 21.26 | 399.17 | 21.23 |
| Annual Sum or Average | 4898.83 | 22.40 | 5481.00 | 23.00 | 2287.50 | 22.90 |
| Minimum of Months | 114.33 | 21.21 | 130.00 | 21.16 | 31.00 | 21.14 |
| Maximum of Months | 744.00 | 25.00 | 744.00 | 24.57 | 578.83 | 24.63 |
Report: ComfortReportSimple55Monthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 531.17 | 21.55 | 289.00 | 21.40 | 289.00 | 21.32 |
| February | 422.50 | 21.95 | 162.83 | 21.89 | 140.83 | 21.74 |
| March | 321.33 | 22.88 | 96.83 | 23.26 | 12.67 | 23.20 |
| April | 172.50 | 23.41 | 224.00 | 24.24 | 13.83 | 24.26 |
| May | 70.83 | 24.40 | 382.33 | 24.51 | 34.00 | 24.55 |
| June | 75.67 | 24.68 | 413.00 | 24.35 | 53.00 | 24.41 |
| July | 114.00 | 24.99 | 533.00 | 24.38 | 114.00 | 24.47 |
| August | 133.83 | 24.59 | 506.00 | 24.27 | 133.83 | 24.32 |
| September | 93.33 | 24.78 | 427.83 | 24.47 | 81.17 | 24.54 |
| October | 256.00 | 23.26 | 228.50 | 23.96 | 54.33 | 23.99 |
| November | 373.83 | 22.63 | 127.33 | 22.94 | 47.83 | 22.88 |
| December | 501.83 | 21.74 | 155.17 | 21.67 | 142.00 | 21.58 |
| Annual Sum or Average | 3066.83 | 22.66 | 3545.83 | 23.31 | 1116.50 | 23.23 |
| Minimum of Months | 70.83 | 21.55 | 96.83 | 21.40 | 12.67 | 21.32 |
| Maximum of Months | 531.17 | 24.99 | 533.00 | 24.51 | 289.00 | 24.55 |
Report: ComfortReportSimple55Monthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 531.17 | 21.55 | 290.17 | 21.39 | 290.17 | 21.32 |
| February | 422.33 | 21.95 | 163.33 | 21.89 | 141.33 | 21.73 |
| March | 322.00 | 22.87 | 96.33 | 23.25 | 12.67 | 23.19 |
| April | 172.50 | 23.41 | 224.17 | 24.24 | 13.83 | 24.25 |
| May | 70.67 | 24.41 | 382.33 | 24.51 | 34.33 | 24.56 |
| June | 75.67 | 24.68 | 414.17 | 24.35 | 53.17 | 24.41 |
| July | 114.83 | 24.98 | 533.00 | 24.38 | 114.83 | 24.47 |
| August | 136.00 | 24.58 | 506.00 | 24.26 | 136.00 | 24.32 |
| September | 94.00 | 24.78 | 427.83 | 24.47 | 81.67 | 24.54 |
| October | 256.17 | 23.26 | 229.00 | 23.96 | 54.67 | 23.99 |
| November | 374.67 | 22.63 | 127.17 | 22.94 | 48.17 | 22.89 |
| December | 501.83 | 21.74 | 154.83 | 21.67 | 141.67 | 21.58 |
| Annual Sum or Average | 3071.83 | 22.66 | 3548.33 | 23.30 | 1122.50 | 23.23 |
| Minimum of Months | 70.67 | 21.55 | 96.33 | 21.39 | 12.67 | 21.32 |
| Maximum of Months | 531.17 | 24.98 | 533.00 | 24.51 | 290.17 | 24.56 |
Report: ComfortReportSimple55Monthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.73 | 689.00 | 20.74 | 689.00 | 20.74 |
| February | 672.00 | 21.79 | 571.00 | 21.87 | 571.00 | 21.89 |
| March | 744.00 | 23.74 | 744.00 | 23.74 | 744.00 | 23.74 |
| April | 720.00 | 25.03 | 720.00 | 25.03 | 720.00 | 25.03 |
| May | 744.00 | 25.86 | 744.00 | 25.86 | 744.00 | 25.86 |
| June | 720.00 | 26.17 | 720.00 | 26.17 | 720.00 | 26.17 |
| July | 744.00 | 26.32 | 744.00 | 26.32 | 744.00 | 26.32 |
| August | 744.00 | 26.31 | 744.00 | 26.31 | 744.00 | 26.31 |
| September | 720.00 | 25.83 | 720.00 | 25.83 | 720.00 | 25.83 |
| October | 744.00 | 24.40 | 744.00 | 24.40 | 744.00 | 24.40 |
| November | 720.00 | 22.93 | 720.00 | 22.93 | 720.00 | 22.93 |
| December | 744.00 | 21.43 | 743.17 | 21.43 | 743.17 | 21.43 |
| Annual Sum or Average | 8760.00 | 24.22 | 8603.17 | 24.25 | 8603.17 | 24.27 |
| Minimum of Months | 672.00 | 20.73 | 571.00 | 20.74 | 571.00 | 20.74 |
| Maximum of Months | 744.00 | 26.32 | 744.00 | 26.32 | 744.00 | 26.32 |
Report: ComfortReportSimple55Monthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.55 | 406.67 | 20.13 | 406.67 | 19.92 |
| February | 619.00 | 21.43 | 279.17 | 21.04 | 257.67 | 20.75 |
| March | 423.67 | 23.41 | 270.17 | 24.09 | 66.33 | 24.10 |
| April | 285.67 | 24.92 | 534.67 | 25.57 | 193.67 | 25.62 |
| May | 445.50 | 26.46 | 727.33 | 26.50 | 436.83 | 26.51 |
| June | 595.33 | 27.39 | 715.17 | 27.36 | 593.17 | 27.37 |
| July | 744.00 | 27.59 | 744.00 | 27.59 | 744.00 | 27.59 |
| August | 742.83 | 27.68 | 744.00 | 27.68 | 742.83 | 27.68 |
| September | 574.50 | 27.29 | 716.33 | 27.21 | 573.50 | 27.24 |
| October | 344.17 | 25.86 | 626.83 | 26.13 | 283.17 | 26.24 |
| November | 351.00 | 23.72 | 345.17 | 24.62 | 100.83 | 24.71 |
| December | 693.83 | 22.24 | 123.67 | 22.13 | 97.33 | 21.97 |
| Annual Sum or Average | 6563.50 | 24.85 | 6233.17 | 25.37 | 4496.00 | 25.50 |
| Minimum of Months | 285.67 | 20.55 | 123.67 | 20.13 | 66.33 | 19.92 |
| Maximum of Months | 744.00 | 27.68 | 744.00 | 27.68 | 744.00 | 27.68 |
Report: ComfortReportSimple55Monthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 22.54 | 744.00 | 22.54 | 744.00 | 22.54 |
| February | 672.00 | 23.49 | 672.00 | 23.49 | 672.00 | 23.49 |
| March | 744.00 | 25.37 | 744.00 | 25.37 | 744.00 | 25.37 |
| April | 720.00 | 25.82 | 720.00 | 25.82 | 720.00 | 25.82 |
| May | 744.00 | 26.13 | 744.00 | 26.13 | 744.00 | 26.13 |
| June | 720.00 | 26.14 | 720.00 | 26.14 | 720.00 | 26.14 |
| July | 744.00 | 26.20 | 744.00 | 26.20 | 744.00 | 26.20 |
| August | 744.00 | 26.15 | 744.00 | 26.15 | 744.00 | 26.15 |
| September | 720.00 | 26.09 | 720.00 | 26.09 | 720.00 | 26.09 |
| October | 744.00 | 25.66 | 744.00 | 25.66 | 744.00 | 25.66 |
| November | 720.00 | 24.94 | 720.00 | 24.94 | 720.00 | 24.94 |
| December | 744.00 | 23.44 | 744.00 | 23.44 | 744.00 | 23.44 |
| Annual Sum or Average | 8760.00 | 25.17 | 8760.00 | 25.17 | 8760.00 | 25.17 |
| Minimum of Months | 672.00 | 22.54 | 672.00 | 22.54 | 672.00 | 22.54 |
| Maximum of Months | 744.00 | 26.20 | 744.00 | 26.20 | 744.00 | 26.20 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 147.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 1750.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: SPLIT GSW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 56169771.43 | 14308323.18 | 29.54 | 56169771.43 | 0.00 | 0.00 | 1.00 | 21-FEB-15:32 | 0.00 | 01-FEB-00:10 | 5324.84 | 28-FEB-19:02 | 5324.84 | 28-FEB-19:02 | 0.00 | 27-FEB-13:12 | 1232.52 | 28-FEB-13:52 | 0.00 |
| March | 0.255849E+09 | 65937052.42 | 154.57 | 0.239288E+09 | 16560617.86 | 0.00 | 1.00 | 03-MAR-16:42 | 0.00 | 01-MAR-04:00 | 5708.58 | 30-MAR-11:32 | 5456.59 | 14-MAR-17:42 | 1294.89 | 30-MAR-11:32 | 1261.93 | 29-MAR-14:22 | 0.00 |
| April | 0.613194E+09 | 0.159124E+09 | 274.49 | 0.562766E+09 | 50428080.88 | 0.00 | 1.00 | 02-APR-14:32 | 0.00 | 01-APR-00:10 | 5845.63 | 30-APR-21:52 | 5474.40 | 12-APR-19:32 | 2020.95 | 30-APR-21:52 | 1266.58 | 02-APR-16:52 | 0.00 |
| May | 0.148056E+10 | 0.382945E+09 | 440.97 | 0.125151E+10 | 0.229049E+09 | 0.00 | 1.00 | 01-MAY-14:12 | 0.00 | 01-MAY-05:05 | 5937.30 | 31-MAY-10:12 | 5470.32 | 12-MAY-20:02 | 2243.21 | 26-MAY-10:03 | 1303.41 | 23-MAY-14:52 | 0.00 |
| June | 0.284228E+10 | 0.752891E+09 | 567.53 | 0.233916E+10 | 0.503116E+09 | 0.00 | 1.00 | 01-JUN-09:22 | 0.00 | 01-JUN-05:20 | 6047.61 | 18-JUN-10:02 | 5474.41 | 09-JUN-21:52 | 2675.68 | 23-JUN-08:55 | 1303.06 | 25-JUN-08:52 | 0.00 |
| July | 0.358621E+10 | 0.949179E+09 | 601.24 | 0.284236E+10 | 0.743852E+09 | 0.00 | 1.00 | 01-JUL-08:32 | 0.00 | 01-JUL-05:15 | 6125.56 | 30-JUL-09:32 | 4963.55 | 02-JUL-21:52 | 2964.76 | 30-JUL-09:35 | 1293.86 | 01-JUL-08:33 | 0.00 |
| August | 0.412500E+10 | 0.107987E+10 | 642.31 | 0.325073E+10 | 0.874274E+09 | 0.00 | 1.00 | 01-AUG-07:32 | 0.00 | 01-AUG-05:15 | 6050.74 | 11-AUG-08:52 | 4702.36 | 30-AUG-21:52 | 2652.73 | 11-AUG-08:55 | 1296.11 | 25-AUG-09:32 | 0.00 |
| September | 0.279857E+10 | 0.713680E+09 | 494.16 | 0.232510E+10 | 0.473472E+09 | 0.00 | 1.00 | 01-SEP-10:22 | 0.00 | 01-SEP-05:15 | 6080.96 | 17-SEP-08:42 | 5467.82 | 14-SEP-21:52 | 2800.74 | 17-SEP-08:45 | 1289.89 | 08-SEP-08:52 | 0.00 |
| October | 0.147725E+10 | 0.373038E+09 | 456.57 | 0.130969E+10 | 0.167554E+09 | 0.00 | 1.00 | 01-OCT-13:32 | 0.00 | 01-OCT-05:20 | 6037.69 | 18-OCT-11:22 | 5477.22 | 21-OCT-16:02 | 2603.93 | 18-OCT-11:25 | 1288.23 | 10-OCT-11:02 | 0.00 |
| November | 0.600914E+09 | 0.154669E+09 | 353.91 | 0.561385E+09 | 39528825.16 | 0.00 | 1.00 | 01-NOV-13:42 | 0.00 | 01-NOV-00:10 | 5866.77 | 27-NOV-22:52 | 5443.77 | 06-NOV-13:02 | 1940.22 | 27-NOV-22:52 | 1251.50 | 19-NOV-15:12 | 0.00 |
| December | 75461230.10 | 19700995.29 | 83.29 | 70621606.83 | 4839623.27 | 0.00 | 1.00 | 10-DEC-15:12 | 0.00 | 01-DEC-00:10 | 5769.57 | 13-DEC-21:02 | 5213.60 | 10-DEC-19:22 | 1656.48 | 13-DEC-21:02 | 1245.23 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.179115E+11 | 0.466534E+10 | 4098.57 | 0.148088E+11 | 0.310267E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.412500E+10 | 0.107987E+10 | 642.31 | 0.325073E+10 | 0.874274E+09 | 0.00 | 1.00 | 0.00 | 6125.56 | 5477.22 | 2964.76 | 1303.41 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 1000574.79 | 264859.11 | 1.50 | 1000574.79 | 0.00 | 0.00 | 0.64 | 28-FEB-17:52 | 0.00 | 01-FEB-00:10 | 3048.49 | 28-FEB-17:52 | 3048.49 | 28-FEB-17:52 | 0.00 | 28-FEB-17:52 | 748.46 | 28-FEB-17:52 | 0.00 |
| March | 61429533.37 | 16229948.69 | 38.62 | 54160994.76 | 7268538.61 | 0.00 | 1.00 | 30-MAR-12:22 | 0.00 | 01-MAR-00:10 | 5495.23 | 30-MAR-12:22 | 4765.70 | 30-MAR-21:52 | 1349.67 | 30-MAR-12:22 | 1238.77 | 30-MAR-12:22 | 0.00 |
| April | 0.367966E+09 | 95843740.35 | 201.57 | 0.328415E+09 | 39551400.06 | 0.00 | 1.00 | 02-APR-15:32 | 0.00 | 01-APR-00:10 | 5656.69 | 04-APR-14:12 | 5239.59 | 24-APR-17:42 | 1976.25 | 04-APR-14:12 | 1231.96 | 04-APR-14:12 | 0.00 |
| May | 0.132968E+10 | 0.344072E+09 | 426.06 | 0.111130E+10 | 0.218382E+09 | 0.00 | 1.00 | 01-MAY-14:22 | 0.00 | 01-MAY-01:10 | 5764.19 | 31-MAY-10:02 | 5301.69 | 12-MAY-20:02 | 2230.39 | 26-MAY-10:13 | 1262.84 | 23-MAY-15:02 | 0.00 |
| June | 0.282724E+10 | 0.747521E+09 | 571.46 | 0.231853E+10 | 0.508715E+09 | 0.00 | 1.00 | 01-JUN-09:12 | 0.00 | 01-JUN-05:20 | 5866.23 | 23-JUN-08:52 | 5301.76 | 09-JUN-21:52 | 2621.33 | 23-JUN-08:55 | 1259.76 | 29-JUN-09:02 | 0.00 |
| July | 0.353801E+10 | 0.934986E+09 | 605.81 | 0.279292E+10 | 0.745085E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:15 | 5912.46 | 30-JUL-09:32 | 4809.78 | 02-JUL-21:52 | 2777.64 | 30-JUL-09:35 | 1250.99 | 13-JUL-07:42 | 0.00 |
| August | 0.388053E+10 | 0.101520E+10 | 640.26 | 0.301830E+10 | 0.862225E+09 | 0.00 | 1.00 | 01-AUG-07:22 | 0.00 | 01-AUG-05:15 | 5874.91 | 11-AUG-08:52 | 4518.37 | 30-AUG-21:52 | 2621.59 | 11-AUG-08:55 | 1256.45 | 25-AUG-09:32 | 0.00 |
| September | 0.236358E+10 | 0.604438E+09 | 481.00 | 0.191984E+10 | 0.443738E+09 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-05:15 | 5884.45 | 17-SEP-09:12 | 5306.13 | 13-SEP-19:02 | 2683.32 | 17-SEP-09:15 | 1260.12 | 09-SEP-08:22 | 0.00 |
| October | 0.846757E+09 | 0.214854E+09 | 365.46 | 0.706820E+09 | 0.139936E+09 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-05:20 | 5880.61 | 18-OCT-11:42 | 5309.32 | 22-OCT-17:52 | 2643.05 | 18-OCT-11:45 | 1250.81 | 10-OCT-11:02 | 0.00 |
| November | 0.120007E+09 | 30621300.82 | 111.94 | 0.101845E+09 | 18162049.04 | 0.00 | 1.00 | 02-NOV-21:52 | 0.00 | 01-NOV-00:10 | 5658.60 | 04-NOV-17:32 | 5196.99 | 09-NOV-21:22 | 1704.78 | 05-NOV-21:52 | 1215.36 | 05-NOV-15:52 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.153362E+11 | 0.400403E+10 | 3443.69 | 0.123531E+11 | 0.298306E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.388053E+10 | 0.101520E+10 | 640.26 | 0.301830E+10 | 0.862225E+09 | 0.00 | 1.00 | 0.00 | 5912.46 | 5309.32 | 2777.64 | 1262.84 | 0.00 |
Report: DXReportMonthly
For: SPLIT OFFICE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 1572045.29 | 420014.02 | 2.67 | 1497348.31 | 74696.98 | 0.00 | 0.05 | 31-JAN-15:20 | 0.00 | 01-JAN-00:10 | 239.49 | 31-JAN-15:20 | 230.16 | 31-JAN-15:20 | 9.98 | 31-JAN-16:50 | 63.91 | 31-JAN-15:20 | 0.00 |
| February | 0.114588E+09 | 30481821.29 | 41.75 | 0.114568E+09 | 19768.97 | 0.00 | 0.32 | 28-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1656.62 | 28-FEB-15:30 | 1656.62 | 28-FEB-15:30 | 12.92 | 22-FEB-17:00 | 434.35 | 28-FEB-13:53 | 0.00 |
| March | 0.441795E+09 | 0.115252E+09 | 151.08 | 0.403821E+09 | 37973320.79 | 0.00 | 1.00 | 31-MAR-06:02 | 0.00 | 01-MAR-00:10 | 6294.80 | 31-MAR-06:02 | 5021.92 | 31-MAR-06:02 | 1272.87 | 31-MAR-06:02 | 1396.50 | 31-MAR-06:02 | 0.00 |
| April | 0.733441E+09 | 0.190999E+09 | 177.07 | 0.679810E+09 | 53631594.99 | 0.00 | 1.00 | 17-APR-06:01 | 0.00 | 01-APR-00:10 | 6233.02 | 19-APR-06:01 | 5947.13 | 17-APR-06:01 | 1190.20 | 21-APR-06:01 | 1392.95 | 19-APR-06:01 | 0.00 |
| May | 0.147109E+10 | 0.374903E+09 | 222.24 | 0.124868E+10 | 0.222411E+09 | 0.00 | 1.00 | 08-MAY-06:01 | 0.00 | 01-MAY-00:10 | 6710.46 | 31-MAY-06:02 | 5764.81 | 17-MAY-06:01 | 2617.33 | 31-MAY-06:03 | 1403.96 | 30-MAY-06:02 | 0.00 |
| June | 0.256110E+10 | 0.651991E+09 | 241.27 | 0.207643E+10 | 0.484670E+09 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 6945.70 | 26-JUN-06:01 | 5883.76 | 09-JUN-06:01 | 3137.17 | 23-JUN-06:05 | 1403.97 | 15-JUN-06:02 | 0.00 |
| July | 0.290885E+10 | 0.733673E+09 | 286.38 | 0.227824E+10 | 0.630610E+09 | 0.00 | 1.00 | 03-JUL-06:01 | 0.00 | 01-JUL-00:10 | 7010.79 | 27-JUL-06:01 | 5166.18 | 25-JUL-06:01 | 3631.88 | 27-JUL-06:07 | 1416.14 | 07-JUL-06:25 | 0.00 |
| August | 0.356052E+10 | 0.886866E+09 | 313.18 | 0.272636E+10 | 0.834162E+09 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 7042.07 | 24-AUG-06:01 | 4787.83 | 14-AUG-06:01 | 3656.22 | 24-AUG-06:07 | 1420.25 | 10-AUG-06:25 | 0.00 |
| September | 0.232371E+10 | 0.575019E+09 | 227.00 | 0.194071E+10 | 0.382996E+09 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:10 | 6904.90 | 07-SEP-06:01 | 5825.23 | 15-SEP-06:01 | 3083.38 | 07-SEP-06:06 | 1403.97 | 26-SEP-06:01 | 0.00 |
| October | 0.131218E+10 | 0.328673E+09 | 195.84 | 0.114832E+10 | 0.163853E+09 | 0.00 | 1.00 | 02-OCT-06:01 | 0.00 | 01-OCT-00:10 | 6911.44 | 19-OCT-06:01 | 5803.98 | 12-OCT-06:01 | 3420.79 | 19-OCT-06:06 | 1403.47 | 17-OCT-06:01 | 0.00 |
| November | 0.531823E+09 | 0.138471E+09 | 152.94 | 0.505798E+09 | 26025440.74 | 0.00 | 0.96 | 03-NOV-06:01 | 0.00 | 01-NOV-00:10 | 5903.67 | 03-NOV-06:01 | 4968.93 | 03-NOV-06:01 | 934.74 | 03-NOV-06:01 | 1337.01 | 03-NOV-06:01 | 0.00 |
| December | 0.126462E+09 | 32929376.24 | 61.07 | 0.111897E+09 | 14565498.78 | 0.00 | 0.64 | 13-DEC-07:02 | 0.00 | 01-DEC-00:10 | 3820.03 | 13-DEC-07:02 | 2932.03 | 13-DEC-07:02 | 888.00 | 13-DEC-07:02 | 899.60 | 13-DEC-07:02 | 0.00 |
| Annual Sum or Average | 0.160871E+11 | 0.405968E+10 | 2072.49 | 0.132361E+11 | 0.285099E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 1572045.29 | 420014.02 | 2.67 | 1497348.31 | 19768.97 | 0.00 | 0.05 | 0.00 | 239.49 | 230.16 | 9.98 | 63.91 | 0.00 | ||||||
| Maximum of Months | 0.356052E+10 | 0.886866E+09 | 313.18 | 0.272636E+10 | 0.834162E+09 | 0.00 | 1.00 | 0.00 | 7042.07 | 5947.13 | 3656.22 | 1420.25 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 1234697.66 | 327615.71 | 1.25 | 1234697.66 | 0.00 | 0.00 | 0.62 | 28-FEB-17:52 | 0.00 | 01-FEB-00:10 | 2733.36 | 28-FEB-17:52 | 2733.36 | 28-FEB-17:52 | 0.00 | 28-FEB-15:00 | 673.52 | 28-FEB-17:52 | 0.00 |
| March | 45938239.83 | 12164411.64 | 35.46 | 39873967.28 | 6064272.56 | 0.00 | 1.00 | 30-MAR-12:22 | 0.00 | 01-MAR-00:10 | 5117.48 | 30-MAR-12:22 | 4377.78 | 30-MAR-21:52 | 1225.61 | 30-MAR-12:22 | 1152.61 | 30-MAR-12:22 | 0.00 |
| April | 0.355545E+09 | 92523116.56 | 199.55 | 0.317226E+09 | 38318936.50 | 0.00 | 1.00 | 02-APR-15:32 | 0.00 | 01-APR-00:10 | 5260.34 | 04-APR-14:12 | 4879.05 | 17-APR-11:12 | 1845.15 | 04-APR-14:12 | 1145.97 | 04-APR-14:12 | 0.00 |
| May | 0.134209E+10 | 0.346335E+09 | 429.66 | 0.112288E+10 | 0.219216E+09 | 0.00 | 1.00 | 01-MAY-14:22 | 0.00 | 01-MAY-00:10 | 5358.81 | 31-MAY-10:02 | 4917.43 | 12-MAY-18:32 | 2063.47 | 26-MAY-10:13 | 1173.97 | 23-MAY-15:02 | 0.00 |
| June | 0.286582E+10 | 0.754397E+09 | 578.27 | 0.235232E+10 | 0.513497E+09 | 0.00 | 1.00 | 01-JUN-09:12 | 0.00 | 01-JUN-05:20 | 5455.98 | 23-JUN-08:52 | 4933.89 | 09-JUN-21:52 | 2425.84 | 23-JUN-08:55 | 1171.86 | 29-JUN-09:02 | 0.00 |
| July | 0.358870E+10 | 0.943282E+09 | 606.95 | 0.283763E+10 | 0.751073E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:15 | 5499.53 | 30-JUL-09:32 | 4457.93 | 02-JUL-21:52 | 2577.00 | 30-JUL-09:35 | 1163.68 | 13-JUL-07:42 | 0.00 |
| August | 0.388357E+10 | 0.101154E+10 | 640.42 | 0.301917E+10 | 0.864403E+09 | 0.00 | 1.00 | 01-AUG-07:22 | 0.00 | 01-AUG-05:15 | 5462.00 | 11-AUG-08:52 | 4191.26 | 08-AUG-17:52 | 2419.35 | 11-AUG-08:55 | 1168.71 | 25-AUG-09:32 | 0.00 |
| September | 0.236368E+10 | 0.602265E+09 | 481.46 | 0.191872E+10 | 0.444955E+09 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-05:15 | 5472.48 | 17-SEP-09:12 | 4935.45 | 13-SEP-19:02 | 2482.81 | 17-SEP-09:15 | 1172.01 | 09-SEP-08:22 | 0.00 |
| October | 0.844066E+09 | 0.213764E+09 | 356.62 | 0.705306E+09 | 0.138759E+09 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-05:20 | 5464.38 | 18-OCT-11:42 | 4936.86 | 22-OCT-17:52 | 2434.33 | 18-OCT-11:45 | 1163.35 | 10-OCT-11:02 | 0.00 |
| November | 0.113375E+09 | 28969040.02 | 114.30 | 96374981.38 | 16999748.03 | 0.00 | 1.00 | 02-NOV-21:52 | 0.00 | 01-NOV-00:10 | 5257.62 | 04-NOV-17:32 | 4831.15 | 09-NOV-21:22 | 1606.86 | 05-NOV-21:52 | 1130.63 | 05-NOV-15:52 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.154040E+11 | 0.400557E+10 | 3443.94 | 0.124107E+11 | 0.299329E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.388357E+10 | 0.101154E+10 | 640.42 | 0.301917E+10 | 0.864403E+09 | 0.00 | 1.00 | 0.00 | 5499.53 | 4936.86 | 2577.00 | 1173.97 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 1742228.63 | 453824.08 | 1.81 | 1742228.63 | -0.0 | 0.00 | 0.85 | 28-FEB-17:52 | 0.00 | 01-FEB-00:10 | 3603.31 | 28-FEB-17:52 | 3603.31 | 28-FEB-17:52 | 0.00 | 28-FEB-22:52 | 852.50 | 28-FEB-17:52 | 0.00 |
| March | 71233782.56 | 18675901.29 | 78.58 | 62907470.40 | 8326312.16 | 0.00 | 1.00 | 11-MAR-22:52 | 0.00 | 01-MAR-00:10 | 4677.06 | 30-MAR-12:22 | 4401.48 | 13-MAR-20:52 | 1122.20 | 30-MAR-12:22 | 1053.47 | 30-MAR-12:22 | 0.00 |
| April | 0.440871E+09 | 0.113927E+09 | 292.38 | 0.386440E+09 | 54431281.10 | 0.00 | 1.00 | 02-APR-15:32 | 0.00 | 01-APR-00:10 | 4817.13 | 04-APR-14:12 | 4449.70 | 16-APR-20:12 | 1675.61 | 04-APR-14:13 | 1047.52 | 04-APR-14:12 | 0.00 |
| May | 0.131886E+10 | 0.339307E+09 | 443.47 | 0.109442E+10 | 0.224445E+09 | 0.00 | 1.00 | 01-MAY-14:22 | 0.00 | 01-MAY-05:05 | 4898.40 | 31-MAY-10:02 | 4492.08 | 12-MAY-18:32 | 1836.07 | 26-MAY-10:13 | 1073.32 | 23-MAY-15:02 | 0.00 |
| June | 0.251183E+10 | 0.660473E+09 | 570.48 | 0.203583E+10 | 0.475998E+09 | 0.00 | 1.00 | 01-JUN-09:12 | 0.00 | 01-JUN-05:20 | 4982.15 | 23-JUN-08:52 | 4484.04 | 09-JUN-21:52 | 2203.07 | 23-JUN-08:55 | 1071.05 | 29-JUN-09:02 | 0.00 |
| July | 0.309649E+10 | 0.813178E+09 | 604.50 | 0.239992E+10 | 0.696566E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:15 | 5016.27 | 27-JUL-11:42 | 4046.88 | 02-JUL-21:52 | 2283.83 | 27-JUL-11:45 | 1063.61 | 13-JUL-07:42 | 0.00 |
| August | 0.334607E+10 | 0.870816E+09 | 637.08 | 0.254907E+10 | 0.796996E+09 | 0.00 | 1.00 | 01-AUG-07:22 | 0.00 | 01-AUG-05:15 | 4993.42 | 11-AUG-08:52 | 3797.77 | 30-AUG-21:52 | 2220.39 | 11-AUG-09:05 | 1068.40 | 25-AUG-09:32 | 0.00 |
| September | 0.213213E+10 | 0.542260E+09 | 482.23 | 0.171166E+10 | 0.420467E+09 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-05:15 | 4997.90 | 17-SEP-09:12 | 4510.10 | 13-SEP-19:02 | 2256.03 | 17-SEP-09:25 | 1071.64 | 09-SEP-08:22 | 0.00 |
| October | 0.920524E+09 | 0.233639E+09 | 427.62 | 0.778098E+09 | 0.142426E+09 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-05:20 | 4996.22 | 18-OCT-11:42 | 4511.28 | 22-OCT-17:52 | 2221.25 | 18-OCT-11:45 | 1063.38 | 10-OCT-11:02 | 0.00 |
| November | 0.220816E+09 | 57011335.94 | 221.47 | 0.195846E+09 | 24970235.34 | 0.00 | 1.00 | 01-NOV-21:52 | 0.00 | 01-NOV-00:10 | 4813.45 | 04-NOV-17:32 | 4435.26 | 09-NOV-21:22 | 1474.00 | 05-NOV-21:53 | 1033.37 | 05-NOV-15:52 | 0.00 |
| December | 995572.82 | 264463.84 | 3.95 | 932052.95 | 63519.87 | 0.00 | 0.17 | 13-DEC-21:02 | 0.00 | 01-DEC-00:10 | 687.27 | 13-DEC-21:02 | 476.11 | 13-DEC-21:02 | 211.16 | 13-DEC-21:02 | 170.81 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.140616E+11 | 0.365001E+10 | 3763.55 | 0.112169E+11 | 0.284469E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.334607E+10 | 0.870816E+09 | 637.08 | 0.254907E+10 | 0.796996E+09 | 0.00 | 1.00 | 0.00 | 5016.27 | 4511.28 | 2283.83 | 1073.32 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 1844903.02 | 479545.81 | 1.97 | 1844903.02 | 0.00 | 0.00 | 0.88 | 28-FEB-17:52 | 0.00 | 01-FEB-00:10 | 3713.69 | 28-FEB-17:52 | 3713.69 | 28-FEB-17:52 | 0.00 | 28-FEB-17:52 | 874.99 | 28-FEB-17:52 | 0.00 |
| March | 70974962.81 | 18607320.66 | 78.07 | 62646859.71 | 8328103.10 | 0.00 | 1.00 | 11-MAR-22:52 | 0.00 | 01-MAR-00:10 | 4671.44 | 30-MAR-12:22 | 4395.51 | 13-MAR-20:52 | 1120.04 | 30-MAR-12:22 | 1052.17 | 30-MAR-12:22 | 0.00 |
| April | 0.441644E+09 | 0.114132E+09 | 291.75 | 0.387263E+09 | 54381216.16 | 0.00 | 1.00 | 02-APR-15:32 | 0.00 | 01-APR-00:10 | 4810.90 | 04-APR-14:12 | 4444.53 | 16-APR-20:12 | 1674.85 | 04-APR-14:13 | 1046.21 | 04-APR-14:12 | 0.00 |
| May | 0.132293E+10 | 0.340326E+09 | 443.55 | 0.109819E+10 | 0.224734E+09 | 0.00 | 1.00 | 01-MAY-14:22 | 0.00 | 01-MAY-05:05 | 4892.59 | 31-MAY-10:02 | 4486.50 | 12-MAY-18:32 | 1881.58 | 31-MAY-10:05 | 1071.94 | 23-MAY-15:02 | 0.00 |
| June | 0.251623E+10 | 0.661574E+09 | 570.59 | 0.203988E+10 | 0.476352E+09 | 0.00 | 1.00 | 01-JUN-09:12 | 0.00 | 01-JUN-05:20 | 4975.94 | 23-JUN-08:52 | 4479.09 | 09-JUN-21:52 | 2200.52 | 23-JUN-08:55 | 1069.71 | 29-JUN-09:02 | 0.00 |
| July | 0.310049E+10 | 0.814144E+09 | 604.80 | 0.240344E+10 | 0.697052E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:15 | 5009.84 | 27-JUL-11:42 | 4042.22 | 02-JUL-21:52 | 2280.16 | 27-JUL-11:45 | 1062.28 | 13-JUL-07:42 | 0.00 |
| August | 0.334719E+10 | 0.871064E+09 | 637.47 | 0.255003E+10 | 0.797162E+09 | 0.00 | 1.00 | 01-AUG-07:22 | 0.00 | 01-AUG-05:15 | 4986.98 | 11-AUG-08:52 | 3792.59 | 30-AUG-21:52 | 2216.95 | 11-AUG-09:05 | 1066.98 | 25-AUG-09:32 | 0.00 |
| September | 0.213464E+10 | 0.542865E+09 | 482.53 | 0.171393E+10 | 0.420701E+09 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-05:15 | 4991.56 | 17-SEP-09:12 | 4504.28 | 13-SEP-19:02 | 2252.98 | 17-SEP-09:25 | 1070.30 | 09-SEP-08:22 | 0.00 |
| October | 0.920902E+09 | 0.233722E+09 | 427.75 | 0.778400E+09 | 0.142502E+09 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-05:20 | 4989.69 | 18-OCT-11:42 | 4505.76 | 22-OCT-17:52 | 2217.73 | 18-OCT-11:45 | 1062.08 | 10-OCT-11:02 | 0.00 |
| November | 0.219948E+09 | 56790248.45 | 221.21 | 0.195074E+09 | 24873395.24 | 0.00 | 1.00 | 01-NOV-21:52 | 0.00 | 01-NOV-00:10 | 4807.30 | 04-NOV-17:32 | 4429.45 | 09-NOV-21:22 | 1492.29 | 27-NOV-22:52 | 1032.08 | 05-NOV-15:52 | 0.00 |
| December | 1010126.51 | 268419.63 | 4.12 | 947128.88 | 62997.63 | 0.00 | 0.17 | 13-DEC-21:02 | 0.00 | 01-DEC-00:10 | 681.29 | 13-DEC-21:02 | 471.92 | 13-DEC-21:02 | 209.37 | 13-DEC-21:02 | 169.35 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.140778E+11 | 0.365397E+10 | 3763.80 | 0.112317E+11 | 0.284615E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.334719E+10 | 0.871064E+09 | 637.47 | 0.255003E+10 | 0.797162E+09 | 0.00 | 1.00 | 0.00 | 5009.84 | 4505.76 | 2280.16 | 1071.94 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 735970.80 | 200434.68 | 2.08 | 735970.80 | 0.00 | 0.00 | 0.15 | 29-JAN-17:52 | 0.00 | 01-JAN-00:10 | 563.57 | 29-JAN-17:52 | 563.57 | 29-JAN-17:52 | 0.00 | 29-JAN-14:50 | 151.29 | 29-JAN-17:52 | 0.00 |
| February | 0.110396E+09 | 28638562.53 | 74.97 | 0.110140E+09 | 255995.26 | 0.00 | 1.00 | 21-FEB-13:02 | 0.00 | 01-FEB-00:10 | 4570.73 | 28-FEB-19:02 | 4570.73 | 28-FEB-19:02 | 25.54 | 22-FEB-22:00 | 1057.06 | 28-FEB-13:52 | 0.00 |
| March | 0.429471E+09 | 0.111570E+09 | 316.34 | 0.407038E+09 | 22433175.73 | 0.00 | 1.00 | 02-MAR-17:52 | 0.00 | 02-MAR-01:10 | 4898.57 | 30-MAR-11:32 | 4678.32 | 11-MAR-19:32 | 1131.17 | 30-MAR-11:33 | 1082.02 | 29-MAR-14:22 | 0.00 |
| April | 0.746723E+09 | 0.192998E+09 | 372.82 | 0.679498E+09 | 67224783.35 | 0.00 | 1.00 | 01-APR-21:12 | 0.00 | 01-APR-12:00 | 5021.46 | 30-APR-21:52 | 4690.00 | 12-APR-19:32 | 1674.86 | 04-APR-13:43 | 1085.76 | 02-APR-16:52 | 0.00 |
| May | 0.147898E+10 | 0.380375E+09 | 448.97 | 0.124368E+10 | 0.235300E+09 | 0.00 | 1.00 | 01-MAY-14:12 | 0.00 | 01-MAY-05:05 | 5086.79 | 31-MAY-10:12 | 4683.96 | 12-MAY-20:02 | 1864.04 | 26-MAY-10:03 | 1117.08 | 23-MAY-14:52 | 0.00 |
| June | 0.253627E+10 | 0.668388E+09 | 566.96 | 0.206473E+10 | 0.471541E+09 | 0.00 | 1.00 | 01-JUN-09:22 | 0.00 | 01-JUN-05:20 | 5180.55 | 18-JUN-10:02 | 4656.85 | 07-JUN-13:12 | 2265.87 | 23-JUN-08:55 | 1117.03 | 25-JUN-08:52 | 0.00 |
| July | 0.315783E+10 | 0.830879E+09 | 598.45 | 0.246077E+10 | 0.697058E+09 | 0.00 | 1.00 | 01-JUL-08:32 | 0.00 | 01-JUL-05:15 | 5220.96 | 30-JUL-09:32 | 4219.54 | 02-JUL-21:52 | 2414.22 | 30-JUL-09:45 | 1116.08 | 09-JUL-09:25 | 0.00 |
| August | 0.360708E+10 | 0.939836E+09 | 641.28 | 0.279477E+10 | 0.812311E+09 | 0.00 | 1.00 | 01-AUG-07:32 | 0.00 | 01-AUG-05:15 | 5184.15 | 11-AUG-08:52 | 3997.41 | 30-AUG-21:52 | 2250.80 | 11-AUG-08:55 | 1111.20 | 25-AUG-09:32 | 0.00 |
| September | 0.258539E+10 | 0.655854E+09 | 495.30 | 0.213264E+10 | 0.452751E+09 | 0.00 | 1.00 | 01-SEP-10:22 | 0.00 | 01-SEP-05:15 | 5200.48 | 17-SEP-08:42 | 4688.57 | 14-SEP-21:52 | 2347.16 | 17-SEP-08:55 | 1105.70 | 08-SEP-08:52 | 0.00 |
| October | 0.160397E+10 | 0.405081E+09 | 499.89 | 0.143408E+10 | 0.169889E+09 | 0.00 | 1.00 | 01-OCT-13:32 | 0.00 | 01-OCT-05:20 | 5167.70 | 18-OCT-11:22 | 4696.54 | 04-OCT-21:52 | 2189.64 | 18-OCT-11:25 | 1103.83 | 10-OCT-11:02 | 0.00 |
| November | 0.891056E+09 | 0.230662E+09 | 468.87 | 0.845997E+09 | 45058839.29 | 0.00 | 1.00 | 01-NOV-13:42 | 0.00 | 01-NOV-11:10 | 5039.32 | 27-NOV-22:52 | 4692.18 | 01-NOV-13:42 | 1666.34 | 27-NOV-22:54 | 1072.78 | 19-NOV-15:12 | 0.00 |
| December | 0.237748E+09 | 62873105.40 | 205.71 | 0.228697E+09 | 9051056.49 | 0.00 | 1.00 | 05-DEC-17:01 | 0.00 | 01-DEC-00:10 | 4963.64 | 13-DEC-21:02 | 4514.09 | 11-DEC-14:42 | 1353.74 | 13-DEC-21:02 | 1067.67 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.173856E+11 | 0.450736E+10 | 4691.63 | 0.144028E+11 | 0.298287E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 735970.80 | 200434.68 | 2.08 | 735970.80 | 0.00 | 0.00 | 0.15 | 0.00 | 563.57 | 563.57 | 0.00 | 151.29 | 0.00 | ||||||
| Maximum of Months | 0.360708E+10 | 0.939836E+09 | 641.28 | 0.279477E+10 | 0.812311E+09 | 0.00 | 1.00 | 0.00 | 5220.96 | 4696.54 | 2414.22 | 1117.08 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 22254.14 | 6086.88 | 0.17 | 22254.14 | -0.0 | 0.00 | 0.01 | 29-JAN-14:50 | 0.00 | 01-JAN-00:10 | 37.09 | 29-JAN-14:50 | 37.09 | 29-JAN-14:50 | 0.00 | 01-JAN-00:10 | 10.14 | 29-JAN-14:50 | 0.00 |
| February | 0.106958E+09 | 27736708.83 | 72.60 | 0.106725E+09 | 232858.04 | 0.00 | 1.00 | 21-FEB-13:02 | 0.00 | 01-FEB-00:10 | 4605.33 | 28-FEB-19:02 | 4605.33 | 28-FEB-19:02 | 23.59 | 22-FEB-22:00 | 1065.09 | 28-FEB-13:52 | 0.00 |
| March | 0.425705E+09 | 0.110555E+09 | 308.81 | 0.403114E+09 | 22590766.78 | 0.00 | 1.00 | 02-MAR-17:52 | 0.00 | 02-MAR-00:50 | 4936.88 | 30-MAR-11:32 | 4713.96 | 11-MAR-19:32 | 1136.66 | 30-MAR-11:33 | 1090.30 | 29-MAR-14:22 | 0.00 |
| April | 0.774684E+09 | 0.200166E+09 | 373.53 | 0.705625E+09 | 69059054.96 | 0.00 | 1.00 | 01-APR-21:12 | 0.00 | 01-APR-12:00 | 5059.34 | 30-APR-21:52 | 4726.31 | 12-APR-19:32 | 1688.45 | 30-APR-21:52 | 1094.04 | 02-APR-16:52 | 0.00 |
| May | 0.156102E+10 | 0.401174E+09 | 453.50 | 0.131827E+10 | 0.242749E+09 | 0.00 | 1.00 | 01-MAY-14:12 | 0.00 | 01-MAY-05:05 | 5124.87 | 31-MAY-10:12 | 4720.31 | 12-MAY-20:02 | 1906.47 | 31-MAY-10:15 | 1125.26 | 23-MAY-14:52 | 0.00 |
| June | 0.271465E+10 | 0.714072E+09 | 571.75 | 0.222987E+10 | 0.484775E+09 | 0.00 | 1.00 | 01-JUN-09:22 | 0.00 | 01-JUN-05:20 | 5209.84 | 18-JUN-10:02 | 4705.61 | 09-JUN-21:52 | 2242.77 | 23-JUN-08:55 | 1125.34 | 25-JUN-08:52 | 0.00 |
| July | 0.340014E+10 | 0.892782E+09 | 604.27 | 0.268454E+10 | 0.715600E+09 | 0.00 | 1.00 | 01-JUL-08:32 | 0.00 | 01-JUL-05:15 | 5251.03 | 30-JUL-09:32 | 4281.18 | 02-JUL-21:52 | 2394.26 | 30-JUL-09:45 | 1124.37 | 09-JUL-09:25 | 0.00 |
| August | 0.386119E+10 | 0.100390E+10 | 641.00 | 0.302859E+10 | 0.832599E+09 | 0.00 | 1.00 | 01-AUG-07:32 | 0.00 | 01-AUG-05:15 | 5211.53 | 11-AUG-08:52 | 4070.37 | 30-AUG-21:52 | 2217.81 | 11-AUG-08:55 | 1119.57 | 25-AUG-09:32 | 0.00 |
| September | 0.274744E+10 | 0.695943E+09 | 493.99 | 0.228396E+10 | 0.463481E+09 | 0.00 | 1.00 | 01-SEP-10:22 | 0.00 | 01-SEP-05:15 | 5224.21 | 17-SEP-08:42 | 4724.20 | 14-SEP-21:52 | 2300.95 | 17-SEP-08:55 | 1113.78 | 08-SEP-08:52 | 0.00 |
| October | 0.165731E+10 | 0.418276E+09 | 498.94 | 0.148460E+10 | 0.172716E+09 | 0.00 | 1.00 | 01-OCT-13:32 | 0.00 | 01-OCT-05:20 | 5202.22 | 18-OCT-11:22 | 4732.51 | 04-OCT-21:52 | 2192.22 | 18-OCT-11:25 | 1111.85 | 10-OCT-11:02 | 0.00 |
| November | 0.872762E+09 | 0.225874E+09 | 459.85 | 0.827843E+09 | 44918857.39 | 0.00 | 1.00 | 01-NOV-13:42 | 0.00 | 01-NOV-11:10 | 5075.65 | 27-NOV-22:52 | 4727.99 | 01-NOV-13:42 | 1691.31 | 27-NOV-22:54 | 1080.98 | 19-NOV-15:12 | 0.00 |
| December | 0.212978E+09 | 56301803.55 | 190.73 | 0.204430E+09 | 8548434.57 | 0.00 | 1.00 | 05-DEC-17:01 | 0.00 | 01-DEC-00:10 | 5000.63 | 13-DEC-21:02 | 4525.18 | 10-DEC-19:22 | 1369.91 | 13-DEC-21:02 | 1075.81 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.183349E+11 | 0.474679E+10 | 4669.12 | 0.152776E+11 | 0.305727E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 22254.14 | 6086.88 | 0.17 | 22254.14 | -0.0 | 0.00 | 0.01 | 0.00 | 37.09 | 37.09 | 0.00 | 10.14 | 0.00 | ||||||
| Maximum of Months | 0.386119E+10 | 0.100390E+10 | 641.00 | 0.302859E+10 | 0.832599E+09 | 0.00 | 1.00 | 0.00 | 5251.03 | 4732.51 | 2394.26 | 1125.34 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 16293199.21 | 4392715.10 | 12.30 | 16289146.16 | 4053.05 | 0.00 | 0.80 | 29-JAN-17:52 | 0.00 | 01-JAN-00:10 | 9375.55 | 29-JAN-17:52 | 9375.55 | 29-JAN-17:52 | 17.74 | 31-JAN-22:33 | 2257.32 | 29-JAN-17:52 | 0.00 |
| February | 0.518995E+09 | 0.134940E+09 | 105.33 | 0.516759E+09 | 2236196.28 | 0.00 | 1.00 | 20-FEB-15:32 | 0.00 | 01-FEB-00:10 | 12549.12 | 22-FEB-16:32 | 12549.12 | 22-FEB-16:32 | 349.37 | 19-FEB-20:53 | 2885.98 | 28-FEB-13:52 | 0.00 |
| March | 0.183614E+10 | 0.475659E+09 | 377.80 | 0.175575E+10 | 80392430.60 | 0.00 | 1.00 | 02-MAR-17:52 | 0.00 | 02-MAR-00:10 | 13410.72 | 30-MAR-11:32 | 12787.57 | 08-MAR-18:12 | 2856.22 | 30-MAR-11:33 | 2955.60 | 29-MAR-14:22 | 0.00 |
| April | 0.297003E+10 | 0.765874E+09 | 429.18 | 0.275896E+10 | 0.211079E+09 | 0.00 | 1.00 | 02-APR-14:32 | 0.00 | 01-APR-12:10 | 13732.43 | 04-APR-13:42 | 12821.27 | 16-APR-19:32 | 4340.20 | 04-APR-13:43 | 2963.81 | 02-APR-16:52 | 0.00 |
| May | 0.470720E+10 | 0.121204E+10 | 476.13 | 0.409561E+10 | 0.611598E+09 | 0.00 | 1.00 | 01-MAY-14:12 | 0.00 | 01-MAY-05:15 | 13898.52 | 31-MAY-10:12 | 12808.15 | 11-MAY-21:52 | 5021.02 | 31-MAY-10:13 | 3044.38 | 23-MAY-14:52 | 0.00 |
| June | 0.682926E+10 | 0.181106E+10 | 573.40 | 0.570733E+10 | 0.112193E+10 | 0.00 | 1.00 | 01-JUN-09:22 | 0.00 | 01-JUN-05:20 | 14191.00 | 23-JUN-08:52 | 12831.24 | 07-JUN-18:02 | 6303.54 | 23-JUN-08:53 | 3050.35 | 25-JUN-08:52 | 0.00 |
| July | 0.799692E+10 | 0.212482E+10 | 599.04 | 0.639153E+10 | 0.160539E+10 | 0.00 | 1.00 | 01-JUL-08:32 | 0.00 | 01-JUL-05:15 | 14316.00 | 30-JUL-09:32 | 11666.50 | 02-JUL-21:52 | 6758.49 | 30-JUL-09:33 | 3028.53 | 01-JUL-08:33 | 0.00 |
| August | 0.874113E+10 | 0.230193E+10 | 635.74 | 0.688716E+10 | 0.185397E+10 | 0.00 | 1.00 | 01-AUG-07:32 | 0.00 | 01-AUG-05:15 | 14302.23 | 20-AUG-07:32 | 10888.10 | 30-AUG-21:52 | 6757.95 | 20-AUG-07:33 | 3033.89 | 25-AUG-09:32 | 0.00 |
| September | 0.570227E+10 | 0.146266E+10 | 493.14 | 0.472248E+10 | 0.979781E+09 | 0.00 | 1.00 | 01-SEP-10:22 | 0.00 | 01-SEP-05:15 | 14339.04 | 17-SEP-08:42 | 12816.06 | 14-SEP-11:12 | 7029.09 | 17-SEP-08:43 | 3020.48 | 08-SEP-08:52 | 0.00 |
| October | 0.295112E+10 | 0.746108E+09 | 437.59 | 0.260883E+10 | 0.342283E+09 | 0.00 | 1.00 | 01-OCT-13:32 | 0.00 | 01-OCT-05:20 | 14222.05 | 18-OCT-11:22 | 12831.32 | 21-OCT-16:02 | 6377.46 | 18-OCT-11:23 | 3017.07 | 10-OCT-11:02 | 0.00 |
| November | 0.121823E+10 | 0.312982E+09 | 313.80 | 0.113534E+10 | 82890970.88 | 0.00 | 1.00 | 01-NOV-13:42 | 0.00 | 01-NOV-00:10 | 13729.79 | 27-NOV-22:52 | 12732.74 | 06-NOV-13:02 | 4554.71 | 27-NOV-22:52 | 2930.30 | 19-NOV-15:12 | 0.00 |
| December | 0.290552E+09 | 76117710.53 | 104.30 | 0.274440E+09 | 16112117.32 | 0.00 | 1.00 | 10-DEC-15:12 | 0.00 | 01-DEC-00:10 | 13514.73 | 13-DEC-21:02 | 12437.98 | 11-DEC-16:02 | 3744.21 | 13-DEC-21:02 | 2914.98 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.437781E+11 | 0.114286E+11 | 4557.76 | 0.368705E+11 | 0.690767E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 16293199.21 | 4392715.10 | 12.30 | 16289146.16 | 4053.05 | 0.00 | 0.80 | 0.00 | 9375.55 | 9375.55 | 17.74 | 2257.32 | 0.00 | ||||||
| Maximum of Months | 0.874113E+10 | 0.230193E+10 | 635.74 | 0.688716E+10 | 0.185397E+10 | 0.00 | 1.00 | 0.00 | 14339.04 | 12831.32 | 7029.09 | 3050.35 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 73763183.18 | 19461677.45 | 36.07 | 72815033.83 | 948149.35 | 0.00 | 1.00 | 27-FEB-22:52 | 0.00 | 01-FEB-00:10 | 12203.73 | 28-FEB-22:52 | 12203.73 | 28-FEB-22:52 | 76.68 | 22-FEB-22:00 | 2815.51 | 28-FEB-14:12 | 0.00 |
| March | 0.840954E+09 | 0.218928E+09 | 225.91 | 0.777660E+09 | 63294144.41 | 0.00 | 1.00 | 04-MAR-16:52 | 0.00 | 01-MAR-23:50 | 13060.52 | 30-MAR-12:22 | 12450.84 | 14-MAR-19:52 | 2864.94 | 30-MAR-12:23 | 2927.43 | 30-MAR-12:22 | 0.00 |
| April | 0.226298E+10 | 0.585094E+09 | 382.62 | 0.206612E+10 | 0.196858E+09 | 0.00 | 1.00 | 02-APR-15:32 | 0.00 | 01-APR-12:00 | 13429.43 | 04-APR-14:12 | 12518.94 | 11-APR-21:52 | 4367.34 | 04-APR-14:13 | 2907.60 | 04-APR-14:12 | 0.00 |
| May | 0.439157E+10 | 0.113106E+10 | 468.85 | 0.379179E+10 | 0.599785E+09 | 0.00 | 1.00 | 01-MAY-14:22 | 0.00 | 01-MAY-05:15 | 13597.76 | 31-MAY-10:02 | 12518.25 | 15-MAY-21:52 | 4979.89 | 31-MAY-10:03 | 2973.75 | 23-MAY-15:02 | 0.00 |
| June | 0.678148E+10 | 0.179573E+10 | 577.45 | 0.564987E+10 | 0.113162E+10 | 0.00 | 1.00 | 01-JUN-09:12 | 0.00 | 01-JUN-05:20 | 13876.37 | 23-JUN-08:52 | 12546.38 | 07-JUN-18:02 | 6224.49 | 23-JUN-08:53 | 2972.68 | 29-JUN-09:02 | 0.00 |
| July | 0.787180E+10 | 0.208923E+10 | 603.72 | 0.626667E+10 | 0.160513E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:15 | 13957.27 | 26-JUL-08:62 | 11398.06 | 02-JUL-21:52 | 6554.51 | 26-JUL-08:03 | 2951.83 | 13-JUL-07:42 | 0.00 |
| August | 0.820767E+10 | 0.216034E+10 | 634.44 | 0.637971E+10 | 0.182796E+10 | 0.00 | 1.00 | 01-AUG-07:22 | 0.00 | 01-AUG-05:15 | 13988.74 | 11-AUG-08:52 | 10534.35 | 30-AUG-21:52 | 6773.31 | 20-AUG-07:43 | 2964.09 | 25-AUG-09:32 | 0.00 |
| September | 0.475902E+10 | 0.122446E+10 | 475.56 | 0.384645E+10 | 0.912573E+09 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-05:15 | 13983.01 | 17-SEP-09:12 | 12512.45 | 13-SEP-19:02 | 6809.17 | 17-SEP-09:13 | 2974.27 | 09-SEP-08:22 | 0.00 |
| October | 0.161476E+10 | 0.409956E+09 | 316.97 | 0.133048E+10 | 0.284281E+09 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-05:10 | 13925.67 | 18-OCT-11:42 | 12509.64 | 22-OCT-17:52 | 6397.76 | 18-OCT-11:43 | 2951.14 | 10-OCT-11:02 | 0.00 |
| November | 0.236868E+09 | 60250518.27 | 97.00 | 0.197807E+09 | 39060807.96 | 0.00 | 1.00 | 02-NOV-21:52 | 0.00 | 01-NOV-00:10 | 13349.21 | 04-NOV-17:32 | 11955.61 | 06-NOV-19:12 | 4009.70 | 05-NOV-21:52 | 2867.54 | 05-NOV-15:52 | 0.00 |
| December | 5456313.27 | 1421826.40 | 6.51 | 4767518.53 | 688794.74 | 0.00 | 0.45 | 13-DEC-21:02 | 0.00 | 01-DEC-00:10 | 5427.48 | 13-DEC-21:02 | 3818.08 | 13-DEC-21:02 | 1609.40 | 13-DEC-21:02 | 1289.39 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.370463E+11 | 0.969593E+10 | 3825.10 | 0.303841E+11 | 0.666219E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.820767E+10 | 0.216034E+10 | 634.44 | 0.637971E+10 | 0.182796E+10 | 0.00 | 1.00 | 0.00 | 13988.74 | 12546.38 | 6809.17 | 2974.27 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 20409797.79 | 5492020.97 | 13.48 | 20404583.06 | 5214.73 | 0.00 | 0.72 | 29-JAN-17:52 | 0.00 | 01-JAN-00:10 | 7637.33 | 29-JAN-17:52 | 7637.33 | 29-JAN-17:52 | 16.21 | 31-JAN-22:33 | 1866.38 | 29-JAN-17:52 | 0.00 |
| February | 0.563900E+09 | 0.146598E+09 | 109.22 | 0.561566E+09 | 2333631.27 | 0.00 | 1.00 | 20-FEB-15:32 | 0.00 | 01-FEB-00:10 | 11604.54 | 22-FEB-16:32 | 11604.54 | 22-FEB-16:32 | 251.83 | 19-FEB-20:53 | 2666.83 | 28-FEB-13:52 | 0.00 |
| March | 0.178047E+10 | 0.461525E+09 | 382.44 | 0.170367E+10 | 76800568.63 | 0.00 | 1.00 | 02-MAR-17:52 | 0.00 | 02-MAR-00:10 | 12379.03 | 30-MAR-11:32 | 11821.04 | 08-MAR-19:42 | 2538.76 | 30-MAR-11:33 | 2731.67 | 29-MAR-14:22 | 0.00 |
| April | 0.293560E+10 | 0.755741E+09 | 431.16 | 0.272932E+10 | 0.206278E+09 | 0.00 | 1.00 | 02-APR-14:32 | 0.00 | 01-APR-12:10 | 12710.08 | 30-APR-21:52 | 11853.02 | 16-APR-19:32 | 4047.90 | 30-APR-21:53 | 2739.20 | 02-APR-16:52 | 0.00 |
| May | 0.473263E+10 | 0.121419E+10 | 476.21 | 0.412133E+10 | 0.611301E+09 | 0.00 | 1.00 | 01-MAY-14:12 | 0.00 | 01-MAY-05:15 | 12801.90 | 26-MAY-10:02 | 11827.30 | 13-MAY-11:02 | 4371.03 | 26-MAY-10:03 | 2811.64 | 23-MAY-14:52 | 0.00 |
| June | 0.690633E+10 | 0.182266E+10 | 578.05 | 0.577747E+10 | 0.112886E+10 | 0.00 | 1.00 | 01-JUN-09:22 | 0.00 | 01-JUN-05:20 | 13111.20 | 23-JUN-08:52 | 11839.63 | 09-JUN-21:52 | 5896.69 | 23-JUN-08:55 | 2818.80 | 25-JUN-08:52 | 0.00 |
| July | 0.809080E+10 | 0.213757E+10 | 603.72 | 0.647559E+10 | 0.161521E+10 | 0.00 | 1.00 | 01-JUL-08:32 | 0.00 | 01-JUL-05:15 | 13231.79 | 30-JUL-09:32 | 10733.95 | 02-JUL-21:52 | 6328.04 | 30-JUL-09:35 | 2815.64 | 09-JUL-09:25 | 0.00 |
| August | 0.874467E+10 | 0.229171E+10 | 639.71 | 0.688612E+10 | 0.185855E+10 | 0.00 | 1.00 | 01-AUG-07:32 | 0.00 | 01-AUG-05:15 | 13220.50 | 20-AUG-07:32 | 10097.52 | 08-AUG-17:52 | 6339.64 | 20-AUG-07:35 | 2803.81 | 25-AUG-09:32 | 0.00 |
| September | 0.570532E+10 | 0.145707E+10 | 495.68 | 0.472527E+10 | 0.980049E+09 | 0.00 | 1.00 | 01-SEP-10:22 | 0.00 | 01-SEP-05:15 | 13253.89 | 17-SEP-08:42 | 11826.27 | 14-SEP-21:52 | 6552.17 | 17-SEP-08:45 | 2790.52 | 08-SEP-08:52 | 0.00 |
| October | 0.295065E+10 | 0.744408E+09 | 432.92 | 0.261105E+10 | 0.339604E+09 | 0.00 | 1.00 | 01-OCT-13:32 | 0.00 | 01-OCT-05:20 | 13135.92 | 18-OCT-11:22 | 11805.37 | 03-OCT-14:02 | 5854.46 | 18-OCT-11:25 | 2785.02 | 10-OCT-11:02 | 0.00 |
| November | 0.120843E+10 | 0.310711E+09 | 320.43 | 0.112919E+10 | 79240102.98 | 0.00 | 1.00 | 01-NOV-13:42 | 0.00 | 01-NOV-00:10 | 12689.63 | 27-NOV-22:52 | 11774.46 | 06-NOV-13:02 | 4193.92 | 27-NOV-22:52 | 2707.98 | 19-NOV-15:12 | 0.00 |
| December | 0.292098E+09 | 76569788.35 | 109.26 | 0.276504E+09 | 15593454.61 | 0.00 | 1.00 | 10-DEC-15:12 | 0.00 | 01-DEC-00:10 | 12492.33 | 13-DEC-21:02 | 11323.16 | 10-DEC-19:22 | 3437.19 | 13-DEC-21:02 | 2693.97 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.439313E+11 | 0.114242E+11 | 4592.27 | 0.370175E+11 | 0.691382E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 20409797.79 | 5492020.97 | 13.48 | 20404583.06 | 5214.73 | 0.00 | 0.72 | 0.00 | 7637.33 | 7637.33 | 16.21 | 1866.38 | 0.00 | ||||||
| Maximum of Months | 0.874467E+10 | 0.229171E+10 | 639.71 | 0.688612E+10 | 0.185855E+10 | 0.00 | 1.00 | 0.00 | 13253.89 | 11853.02 | 6552.17 | 2818.80 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 84403770.55 | 22284097.99 | 44.30 | 83346932.71 | 1056837.84 | 0.00 | 1.00 | 27-FEB-22:52 | 0.00 | 01-FEB-00:10 | 11232.59 | 28-FEB-17:52 | 11232.59 | 28-FEB-17:52 | 83.65 | 22-FEB-22:00 | 2598.30 | 28-FEB-14:12 | 0.00 |
| March | 0.774287E+09 | 0.201763E+09 | 230.22 | 0.714312E+09 | 59974722.96 | 0.00 | 1.00 | 04-MAR-16:52 | 0.00 | 01-MAR-23:20 | 12041.22 | 29-MAR-13:52 | 11386.68 | 13-MAR-21:52 | 2580.67 | 30-MAR-12:23 | 2698.81 | 30-MAR-12:22 | 0.00 |
| April | 0.222204E+10 | 0.573879E+09 | 392.82 | 0.202807E+10 | 0.193976E+09 | 0.00 | 1.00 | 02-APR-15:32 | 0.00 | 01-APR-12:00 | 12380.95 | 04-APR-14:12 | 11538.56 | 16-APR-20:12 | 4004.67 | 04-APR-14:13 | 2680.91 | 04-APR-14:12 | 0.00 |
| May | 0.442014E+10 | 0.113473E+10 | 472.95 | 0.381874E+10 | 0.601390E+09 | 0.00 | 1.00 | 01-MAY-14:22 | 0.00 | 01-MAY-05:15 | 12511.15 | 26-MAY-10:12 | 11541.35 | 11-MAY-21:52 | 4420.87 | 26-MAY-10:13 | 2739.32 | 23-MAY-15:02 | 0.00 |
| June | 0.686682E+10 | 0.180927E+10 | 582.42 | 0.572440E+10 | 0.114242E+10 | 0.00 | 1.00 | 01-JUN-09:12 | 0.00 | 01-JUN-05:20 | 12788.62 | 23-JUN-08:52 | 11528.99 | 09-JUN-21:52 | 5799.88 | 23-JUN-08:55 | 2740.91 | 29-JUN-09:02 | 0.00 |
| July | 0.797416E+10 | 0.210403E+10 | 607.93 | 0.635492E+10 | 0.161924E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:15 | 12858.79 | 26-JUL-08:62 | 10456.00 | 02-JUL-21:52 | 6035.78 | 26-JUL-08:05 | 2721.70 | 13-JUL-07:42 | 0.00 |
| August | 0.821513E+10 | 0.215202E+10 | 638.96 | 0.637998E+10 | 0.183516E+10 | 0.00 | 1.00 | 01-AUG-07:22 | 0.00 | 01-AUG-05:15 | 12895.64 | 20-AUG-07:42 | 9724.62 | 08-AUG-17:52 | 6318.30 | 20-AUG-07:45 | 2733.37 | 25-AUG-09:32 | 0.00 |
| September | 0.475990E+10 | 0.122013E+10 | 480.40 | 0.384400E+10 | 0.915896E+09 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-05:15 | 12896.61 | 17-SEP-09:12 | 11539.41 | 13-SEP-19:02 | 6316.97 | 17-SEP-09:15 | 2742.39 | 09-SEP-08:22 | 0.00 |
| October | 0.160801E+10 | 0.407477E+09 | 310.71 | 0.132536E+10 | 0.282650E+09 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-05:10 | 12838.28 | 18-OCT-11:42 | 11513.26 | 22-OCT-15:52 | 5953.89 | 18-OCT-11:45 | 2721.76 | 10-OCT-11:02 | 0.00 |
| November | 0.217313E+09 | 55329301.10 | 94.96 | 0.181046E+09 | 36266884.89 | 0.00 | 1.00 | 02-NOV-21:52 | 0.00 | 01-NOV-00:10 | 12280.70 | 05-NOV-21:52 | 11000.14 | 06-NOV-19:12 | 3760.42 | 05-NOV-21:52 | 2644.16 | 05-NOV-15:52 | 0.00 |
| December | 5994836.41 | 1565270.25 | 8.67 | 5292340.02 | 702496.39 | 0.00 | 0.51 | 13-DEC-21:02 | 0.00 | 01-DEC-00:10 | 5660.04 | 13-DEC-21:02 | 3984.31 | 13-DEC-21:02 | 1675.74 | 13-DEC-21:02 | 1332.71 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.371482E+11 | 0.968248E+10 | 3864.34 | 0.304595E+11 | 0.668873E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.821513E+10 | 0.215202E+10 | 638.96 | 0.637998E+10 | 0.183516E+10 | 0.00 | 1.00 | 0.00 | 12896.61 | 11541.35 | 6318.30 | 2742.39 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 0.147936E+09 | 39176022.28 | 75.60 | 0.145747E+09 | 2189738.38 | 0.00 | 1.00 | 21-FEB-22:12 | 0.00 | 01-FEB-00:10 | 10102.25 | 22-FEB-16:32 | 10102.25 | 22-FEB-16:32 | 357.13 | 19-FEB-20:53 | 2326.00 | 28-FEB-14:12 | 0.00 |
| March | 0.100882E+10 | 0.263680E+09 | 345.86 | 0.944254E+09 | 64561438.67 | 0.00 | 1.00 | 02-MAR-17:52 | 0.00 | 02-MAR-06:00 | 10789.75 | 30-MAR-12:22 | 10214.13 | 13-MAR-21:52 | 2359.12 | 30-MAR-12:23 | 2418.76 | 30-MAR-12:22 | 0.00 |
| April | 0.214832E+10 | 0.554094E+09 | 412.38 | 0.195163E+10 | 0.196684E+09 | 0.00 | 1.00 | 01-APR-21:12 | 0.00 | 01-APR-12:10 | 11091.85 | 04-APR-14:12 | 10346.34 | 12-APR-19:32 | 3612.68 | 04-APR-14:13 | 2402.43 | 04-APR-14:12 | 0.00 |
| May | 0.385387E+10 | 0.988122E+09 | 465.41 | 0.328962E+10 | 0.564253E+09 | 0.00 | 1.00 | 01-MAY-07:12 | 0.00 | 01-MAY-05:15 | 11237.13 | 31-MAY-10:02 | 10341.77 | 12-MAY-21:42 | 4125.81 | 31-MAY-10:03 | 2458.95 | 23-MAY-15:02 | 0.00 |
| June | 0.569536E+10 | 0.150088E+10 | 573.19 | 0.466667E+10 | 0.102869E+10 | 0.00 | 1.00 | 01-JUN-09:12 | 0.00 | 01-JUN-05:20 | 11453.73 | 23-JUN-08:52 | 10325.15 | 09-JUN-21:52 | 5203.92 | 23-JUN-08:55 | 2456.22 | 29-JUN-09:02 | 0.00 |
| July | 0.660053E+10 | 0.174078E+10 | 601.83 | 0.513242E+10 | 0.146811E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:15 | 11513.30 | 26-JUL-08:62 | 9274.53 | 02-JUL-21:52 | 5419.55 | 26-JUL-08:05 | 2439.00 | 13-JUL-07:42 | 0.00 |
| August | 0.685681E+10 | 0.179414E+10 | 632.89 | 0.519511E+10 | 0.166170E+10 | 0.00 | 1.00 | 01-AUG-07:22 | 0.00 | 01-AUG-05:15 | 11562.50 | 11-AUG-08:52 | 8588.81 | 30-AUG-21:52 | 5689.65 | 20-AUG-07:45 | 2449.01 | 25-AUG-09:32 | 0.00 |
| September | 0.423181E+10 | 0.108172E+10 | 472.97 | 0.337226E+10 | 0.859550E+09 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-05:15 | 11541.74 | 17-SEP-09:12 | 10341.46 | 13-SEP-19:02 | 5623.76 | 17-SEP-09:15 | 2457.66 | 09-SEP-08:22 | 0.00 |
| October | 0.178938E+10 | 0.454811E+09 | 410.60 | 0.149737E+10 | 0.292005E+09 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-05:20 | 11500.42 | 18-OCT-11:42 | 10316.69 | 22-OCT-17:52 | 5339.01 | 18-OCT-11:45 | 2438.22 | 10-OCT-11:02 | 0.00 |
| November | 0.476368E+09 | 0.122860E+09 | 205.55 | 0.420242E+09 | 56125427.96 | 0.00 | 1.00 | 01-NOV-21:52 | 0.00 | 01-NOV-00:10 | 11035.47 | 04-NOV-17:32 | 10168.00 | 09-NOV-21:22 | 3506.73 | 27-NOV-22:52 | 2369.52 | 05-NOV-15:52 | 0.00 |
| December | 37458822.91 | 9743272.30 | 23.79 | 33125698.54 | 4333124.37 | 0.00 | 1.00 | 13-DEC-21:02 | 0.00 | 01-DEC-00:10 | 10888.97 | 13-DEC-21:02 | 7772.80 | 13-DEC-21:02 | 3116.17 | 13-DEC-21:02 | 2351.95 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.328467E+11 | 0.855001E+10 | 4220.06 | 0.266485E+11 | 0.619820E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.685681E+10 | 0.179414E+10 | 632.89 | 0.519511E+10 | 0.166170E+10 | 0.00 | 1.00 | 0.00 | 11562.50 | 10346.34 | 5689.65 | 2458.95 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 0.151711E+09 | 40180489.48 | 76.29 | 0.149513E+09 | 2198280.90 | 0.00 | 1.00 | 21-FEB-22:12 | 0.00 | 01-FEB-00:10 | 10076.03 | 22-FEB-16:32 | 10076.03 | 22-FEB-16:32 | 349.84 | 19-FEB-20:53 | 2320.01 | 28-FEB-14:12 | 0.00 |
| March | 0.100550E+10 | 0.262818E+09 | 345.67 | 0.940857E+09 | 64644674.19 | 0.00 | 1.00 | 02-MAR-17:52 | 0.00 | 02-MAR-06:00 | 10761.69 | 30-MAR-12:22 | 10188.98 | 13-MAR-21:52 | 2350.99 | 30-MAR-12:23 | 2412.36 | 30-MAR-12:22 | 0.00 |
| April | 0.215237E+10 | 0.555114E+09 | 412.05 | 0.195554E+10 | 0.196832E+09 | 0.00 | 1.00 | 01-APR-21:12 | 0.00 | 01-APR-12:10 | 11062.46 | 04-APR-14:12 | 10318.41 | 12-APR-19:32 | 3603.50 | 04-APR-14:13 | 2396.05 | 04-APR-14:12 | 0.00 |
| May | 0.386465E+10 | 0.990758E+09 | 466.06 | 0.329962E+10 | 0.565027E+09 | 0.00 | 1.00 | 01-MAY-07:12 | 0.00 | 01-MAY-05:15 | 11208.14 | 31-MAY-10:02 | 10314.59 | 12-MAY-21:42 | 4110.54 | 31-MAY-10:03 | 2452.30 | 23-MAY-15:02 | 0.00 |
| June | 0.570537E+10 | 0.150328E+10 | 573.19 | 0.467581E+10 | 0.102956E+10 | 0.00 | 1.00 | 01-JUN-09:12 | 0.00 | 01-JUN-05:20 | 11423.36 | 23-JUN-08:52 | 10297.76 | 09-JUN-21:52 | 5190.68 | 23-JUN-08:55 | 2449.71 | 29-JUN-09:02 | 0.00 |
| July | 0.660676E+10 | 0.174220E+10 | 601.71 | 0.513813E+10 | 0.146863E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:15 | 11482.69 | 26-JUL-08:62 | 9249.09 | 02-JUL-21:52 | 5401.19 | 26-JUL-08:05 | 2432.53 | 13-JUL-07:42 | 0.00 |
| August | 0.685994E+10 | 0.179475E+10 | 632.94 | 0.519768E+10 | 0.166227E+10 | 0.00 | 1.00 | 01-AUG-07:22 | 0.00 | 01-AUG-05:15 | 11531.91 | 11-AUG-08:52 | 8564.25 | 30-AUG-21:52 | 5674.57 | 20-AUG-07:45 | 2442.54 | 25-AUG-09:32 | 0.00 |
| September | 0.423901E+10 | 0.108340E+10 | 473.08 | 0.337845E+10 | 0.860563E+09 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-05:15 | 11511.14 | 17-SEP-09:12 | 10313.83 | 13-SEP-19:02 | 5608.75 | 17-SEP-09:15 | 2451.15 | 09-SEP-08:22 | 0.00 |
| October | 0.178849E+10 | 0.454565E+09 | 410.79 | 0.149679E+10 | 0.291695E+09 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-05:20 | 11466.12 | 18-OCT-11:42 | 10287.78 | 22-OCT-17:52 | 5301.63 | 18-OCT-11:45 | 2431.82 | 10-OCT-11:02 | 0.00 |
| November | 0.474589E+09 | 0.122410E+09 | 205.77 | 0.418698E+09 | 55890606.85 | 0.00 | 1.00 | 01-NOV-21:52 | 0.00 | 01-NOV-00:10 | 11005.97 | 04-NOV-17:32 | 10140.37 | 09-NOV-21:22 | 3569.89 | 27-NOV-22:52 | 2363.23 | 05-NOV-15:52 | 0.00 |
| December | 37591488.32 | 9779925.96 | 23.79 | 33278666.28 | 4312822.04 | 0.00 | 1.00 | 13-DEC-21:02 | 0.00 | 01-DEC-00:10 | 10860.05 | 13-DEC-21:02 | 7751.00 | 13-DEC-21:02 | 3109.05 | 13-DEC-21:02 | 2345.71 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.328860E+11 | 0.855925E+10 | 4221.36 | 0.266844E+11 | 0.620162E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.685994E+10 | 0.179475E+10 | 632.94 | 0.519768E+10 | 0.166227E+10 | 0.00 | 1.00 | 0.00 | 11531.91 | 10318.41 | 5674.57 | 2452.30 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.137710E+09 | 37110298.77 | 82.29 | 0.137643E+09 | 67023.41 | 0.00 | 1.00 | 29-JAN-17:52 | 0.00 | 01-JAN-00:10 | 10151.57 | 29-JAN-17:52 | 10151.57 | 29-JAN-17:52 | 23.58 | 31-JAN-23:10 | 2356.55 | 29-JAN-17:52 | 0.00 |
| February | 0.720283E+09 | 0.187485E+09 | 177.24 | 0.713764E+09 | 6519167.40 | 0.00 | 1.00 | 20-FEB-15:32 | 0.00 | 01-FEB-01:40 | 10529.65 | 22-FEB-16:32 | 10529.65 | 22-FEB-16:32 | 654.55 | 19-FEB-20:53 | 2416.33 | 28-FEB-13:52 | 0.00 |
| March | 0.217400E+10 | 0.564582E+09 | 481.51 | 0.209346E+10 | 80544483.31 | 0.00 | 1.00 | 02-MAR-17:52 | 0.00 | 02-MAR-12:50 | 11227.16 | 30-MAR-11:32 | 10710.67 | 08-MAR-19:42 | 2342.89 | 30-MAR-11:33 | 2474.70 | 29-MAR-14:22 | 0.00 |
| April | 0.287355E+10 | 0.739668E+09 | 449.45 | 0.266397E+10 | 0.209583E+09 | 0.00 | 1.00 | 01-APR-21:12 | 0.00 | 01-APR-12:10 | 11524.11 | 30-APR-21:52 | 10742.65 | 16-APR-19:32 | 3610.24 | 04-APR-13:43 | 2481.38 | 02-APR-16:52 | 0.00 |
| May | 0.416578E+10 | 0.106844E+10 | 475.61 | 0.358991E+10 | 0.575873E+09 | 0.00 | 1.00 | 01-MAY-07:12 | 0.00 | 01-MAY-05:15 | 11638.23 | 31-MAY-10:12 | 10733.65 | 12-MAY-21:42 | 4211.25 | 31-MAY-10:13 | 2550.27 | 23-MAY-14:52 | 0.00 |
| June | 0.574127E+10 | 0.151625E+10 | 570.55 | 0.472289E+10 | 0.101838E+10 | 0.00 | 1.00 | 01-JUN-09:22 | 0.00 | 01-JUN-05:20 | 11861.63 | 23-JUN-08:52 | 10720.80 | 09-JUN-21:52 | 5342.14 | 23-JUN-08:55 | 2553.64 | 25-JUN-08:52 | 0.00 |
| July | 0.672792E+10 | 0.177774E+10 | 597.83 | 0.525924E+10 | 0.146868E+10 | 0.00 | 1.00 | 01-JUL-08:32 | 0.00 | 01-JUL-05:15 | 11943.86 | 30-JUL-09:32 | 9639.41 | 02-JUL-21:52 | 5584.39 | 26-JUL-08:05 | 2535.83 | 01-JUL-08:35 | 0.00 |
| August | 0.739512E+10 | 0.193790E+10 | 634.43 | 0.570377E+10 | 0.169135E+10 | 0.00 | 1.00 | 01-AUG-07:32 | 0.00 | 01-AUG-05:15 | 11976.18 | 11-AUG-08:52 | 9020.30 | 30-AUG-21:52 | 5783.92 | 20-AUG-07:35 | 2539.69 | 25-AUG-09:32 | 0.00 |
| September | 0.517898E+10 | 0.132100E+10 | 497.24 | 0.425159E+10 | 0.927384E+09 | 0.00 | 1.00 | 01-SEP-10:22 | 0.00 | 01-SEP-05:15 | 11985.26 | 17-SEP-08:42 | 10740.18 | 14-SEP-11:12 | 5847.39 | 17-SEP-08:45 | 2528.53 | 08-SEP-08:52 | 0.00 |
| October | 0.323884E+10 | 0.819340E+09 | 490.75 | 0.289098E+10 | 0.347865E+09 | 0.00 | 1.00 | 01-OCT-13:32 | 0.00 | 01-OCT-05:20 | 11895.72 | 18-OCT-11:22 | 10735.68 | 04-OCT-21:52 | 5352.87 | 18-OCT-11:25 | 2524.79 | 10-OCT-11:02 | 0.00 |
| November | 0.188664E+10 | 0.487944E+09 | 446.52 | 0.179137E+10 | 95277950.83 | 0.00 | 1.00 | 01-NOV-13:42 | 0.00 | 01-NOV-11:10 | 11518.64 | 27-NOV-22:52 | 10726.66 | 01-NOV-13:42 | 3832.25 | 27-NOV-22:54 | 2453.00 | 19-NOV-15:12 | 0.00 |
| December | 0.759369E+09 | 0.200649E+09 | 254.18 | 0.735961E+09 | 23408657.18 | 0.00 | 1.00 | 05-DEC-17:01 | 0.00 | 01-DEC-00:10 | 11353.95 | 13-DEC-21:02 | 10450.46 | 11-DEC-16:02 | 3000.42 | 13-DEC-21:02 | 2440.72 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.409995E+11 | 0.106581E+11 | 5157.60 | 0.345545E+11 | 0.644493E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.137710E+09 | 37110298.77 | 82.29 | 0.137643E+09 | 67023.41 | 0.00 | 1.00 | 0.00 | 10151.57 | 9020.30 | 23.58 | 2356.55 | 0.00 | ||||||
| Maximum of Months | 0.739512E+10 | 0.193790E+10 | 634.43 | 0.570377E+10 | 0.169135E+10 | 0.00 | 1.00 | 0.00 | 11985.26 | 10742.65 | 5847.39 | 2553.64 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.140276E+09 | 37797742.50 | 83.65 | 0.140206E+09 | 69579.46 | 0.00 | 1.00 | 29-JAN-17:52 | 0.00 | 01-JAN-00:10 | 10139.45 | 29-JAN-17:52 | 10139.45 | 29-JAN-17:52 | 24.04 | 31-JAN-23:10 | 2353.70 | 29-JAN-17:52 | 0.00 |
| February | 0.723429E+09 | 0.188296E+09 | 177.74 | 0.716979E+09 | 6450585.64 | 0.00 | 1.00 | 20-FEB-15:32 | 0.00 | 01-FEB-01:40 | 10517.05 | 22-FEB-16:32 | 10517.05 | 22-FEB-16:32 | 651.17 | 19-FEB-20:53 | 2413.36 | 28-FEB-13:52 | 0.00 |
| March | 0.216648E+10 | 0.562654E+09 | 481.27 | 0.208628E+10 | 80203856.66 | 0.00 | 1.00 | 02-MAR-17:52 | 0.00 | 02-MAR-12:50 | 11213.22 | 30-MAR-11:32 | 10697.00 | 08-MAR-19:42 | 2339.78 | 30-MAR-11:33 | 2471.66 | 29-MAR-14:22 | 0.00 |
| April | 0.287770E+10 | 0.740717E+09 | 449.85 | 0.266808E+10 | 0.209624E+09 | 0.00 | 1.00 | 01-APR-21:12 | 0.00 | 01-APR-12:10 | 11510.07 | 30-APR-21:52 | 10729.37 | 16-APR-19:32 | 3605.94 | 04-APR-13:43 | 2478.34 | 02-APR-16:52 | 0.00 |
| May | 0.417530E+10 | 0.107081E+10 | 476.09 | 0.359885E+10 | 0.576449E+09 | 0.00 | 1.00 | 01-MAY-07:12 | 0.00 | 01-MAY-05:15 | 11624.90 | 31-MAY-10:12 | 10720.46 | 12-MAY-21:42 | 4200.77 | 31-MAY-10:13 | 2547.03 | 23-MAY-14:52 | 0.00 |
| June | 0.575159E+10 | 0.151884E+10 | 571.08 | 0.473261E+10 | 0.101898E+10 | 0.00 | 1.00 | 01-JUN-09:22 | 0.00 | 01-JUN-05:20 | 11847.15 | 23-JUN-08:52 | 10708.92 | 09-JUN-21:52 | 5336.18 | 23-JUN-08:55 | 2550.52 | 25-JUN-08:52 | 0.00 |
| July | 0.673346E+10 | 0.177912E+10 | 597.91 | 0.526447E+10 | 0.146899E+10 | 0.00 | 1.00 | 01-JUL-08:32 | 0.00 | 01-JUL-05:15 | 11934.70 | 30-JUL-09:32 | 9626.82 | 02-JUL-21:52 | 5567.29 | 26-JUL-08:05 | 2532.72 | 01-JUL-08:35 | 0.00 |
| August | 0.739810E+10 | 0.193858E+10 | 634.51 | 0.570647E+10 | 0.169164E+10 | 0.00 | 1.00 | 01-AUG-07:32 | 0.00 | 01-AUG-05:15 | 11961.62 | 11-AUG-08:52 | 9007.99 | 30-AUG-21:52 | 5776.89 | 20-AUG-07:35 | 2536.62 | 25-AUG-09:32 | 0.00 |
| September | 0.518460E+10 | 0.132233E+10 | 497.09 | 0.425691E+10 | 0.927687E+09 | 0.00 | 1.00 | 01-SEP-10:22 | 0.00 | 01-SEP-05:15 | 11970.59 | 17-SEP-08:42 | 10726.20 | 14-SEP-11:12 | 5840.47 | 17-SEP-08:45 | 2525.44 | 08-SEP-08:52 | 0.00 |
| October | 0.324151E+10 | 0.819968E+09 | 490.53 | 0.289377E+10 | 0.347747E+09 | 0.00 | 1.00 | 01-OCT-13:32 | 0.00 | 01-OCT-05:20 | 11881.41 | 18-OCT-11:22 | 10723.25 | 04-OCT-21:52 | 5345.00 | 18-OCT-11:25 | 2521.67 | 10-OCT-11:02 | 0.00 |
| November | 0.188621E+10 | 0.487844E+09 | 447.04 | 0.179103E+10 | 95171879.88 | 0.00 | 1.00 | 01-NOV-13:42 | 0.00 | 01-NOV-11:10 | 11504.68 | 27-NOV-22:52 | 10713.54 | 01-NOV-13:42 | 3827.36 | 27-NOV-22:54 | 2450.00 | 19-NOV-15:12 | 0.00 |
| December | 0.764993E+09 | 0.202143E+09 | 255.87 | 0.741597E+09 | 23395874.31 | 0.00 | 1.00 | 05-DEC-17:01 | 0.00 | 01-DEC-00:10 | 11340.17 | 13-DEC-21:02 | 10436.72 | 11-DEC-16:02 | 2996.95 | 13-DEC-21:02 | 2437.73 | 13-DEC-21:02 | 0.00 |
| Annual Sum or Average | 0.410437E+11 | 0.106691E+11 | 5162.64 | 0.345972E+11 | 0.644641E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.140276E+09 | 37797742.50 | 83.65 | 0.140206E+09 | 69579.46 | 0.00 | 1.00 | 0.00 | 10139.45 | 9007.99 | 24.04 | 2353.70 | 0.00 | ||||||
| Maximum of Months | 0.739810E+10 | 0.193858E+10 | 634.51 | 0.570647E+10 | 0.169164E+10 | 0.00 | 1.00 | 0.00 | 11970.59 | 10729.37 | 5840.47 | 2550.52 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 27754119.66 | 7500350.56 | 20.73 | 27754119.66 | 0.00 | 0.00 | 1.00 | 29-JAN-17:52 | 0.00 | 01-JAN-00:10 | 6795.32 | 29-JAN-17:52 | 6795.32 | 29-JAN-17:52 | 0.00 | 28-JAN-15:10 | 1574.83 | 29-JAN-17:52 | 0.00 |
| February | 0.137902E+09 | 35017212.37 | 45.16 | 0.137869E+09 | 32632.02 | 0.00 | 1.00 | 20-FEB-15:32 | 0.00 | 01-FEB-00:10 | 7047.68 | 20-FEB-18:22 | 7047.68 | 20-FEB-18:22 | 5.76 | 22-FEB-19:00 | 1611.52 | 28-FEB-13:52 | 0.00 |
| March | 0.510182E+09 | 0.129595E+09 | 138.86 | 0.482325E+09 | 27856391.41 | 0.00 | 1.00 | 03-MAR-16:42 | 0.00 | 01-MAR-01:50 | 7491.54 | 30-MAR-11:32 | 7276.80 | 14-MAR-17:22 | 1496.66 | 30-MAR-11:33 | 1649.63 | 29-MAR-14:22 | 0.00 |
| April | 0.120262E+10 | 0.308360E+09 | 263.90 | 0.112236E+10 | 80262921.38 | 0.00 | 1.00 | 02-APR-14:32 | 0.00 | 01-APR-00:10 | 7641.59 | 23-APR-12:32 | 7270.71 | 12-APR-19:12 | 2305.59 | 04-APR-13:43 | 1654.59 | 02-APR-16:52 | 0.00 |
| May | 0.225764E+10 | 0.581795E+09 | 424.90 | 0.197804E+10 | 0.279605E+09 | 0.00 | 1.00 | 01-MAY-14:12 | 0.00 | 01-MAY-05:05 | 7765.49 | 31-MAY-10:12 | 7263.90 | 12-MAY-19:42 | 2808.15 | 31-MAY-10:13 | 1698.66 | 23-MAY-14:52 | 0.00 |
| June | 0.364377E+10 | 0.970476E+09 | 559.50 | 0.307086E+10 | 0.572910E+09 | 0.00 | 1.00 | 01-JUN-09:22 | 0.00 | 01-JUN-05:20 | 7938.63 | 23-JUN-08:52 | 7238.55 | 07-JUN-18:02 | 3586.22 | 23-JUN-08:53 | 1703.42 | 25-JUN-08:52 | 0.00 |
| July | 0.433774E+10 | 0.115851E+10 | 600.31 | 0.351524E+10 | 0.822495E+09 | 0.00 | 1.00 | 01-JUL-08:32 | 0.00 | 01-JUL-05:15 | 8030.25 | 30-JUL-09:32 | 6536.56 | 02-JUL-21:52 | 3936.98 | 30-JUL-09:33 | 1690.77 | 01-JUL-08:33 | 0.00 |
| August | 0.474893E+10 | 0.125597E+10 | 638.24 | 0.379037E+10 | 0.958564E+09 | 0.00 | 1.00 | 01-AUG-07:32 | 0.00 | 01-AUG-05:15 | 8054.93 | 20-AUG-07:32 | 6174.87 | 08-AUG-17:52 | 4054.48 | 20-AUG-07:33 | 1694.59 | 25-AUG-09:32 | 0.00 |
| September | 0.274216E+10 | 0.705822E+09 | 455.47 | 0.227762E+10 | 0.464533E+09 | 0.00 | 1.00 | 01-SEP-10:22 | 0.00 | 01-SEP-05:15 | 8037.11 | 17-SEP-08:42 | 7282.50 | 18-SEP-15:22 | 3990.58 | 17-SEP-08:43 | 1686.83 | 08-SEP-08:52 | 0.00 |
| October | 0.105945E+10 | 0.263860E+09 | 207.50 | 0.917906E+09 | 0.141542E+09 | 0.00 | 1.00 | 01-OCT-13:32 | 0.00 | 01-OCT-00:10 | 7958.39 | 18-OCT-11:22 | 7313.84 | 05-OCT-18:02 | 3626.57 | 18-OCT-11:23 | 1686.72 | 10-OCT-11:02 | 0.00 |
| November | 0.225108E+09 | 55507273.96 | 80.69 | 0.206334E+09 | 18773641.59 | 0.00 | 1.00 | 01-NOV-13:42 | 0.00 | 01-NOV-00:10 | 7653.49 | 04-NOV-16:42 | 7144.46 | 06-NOV-15:02 | 2344.02 | 27-NOV-22:52 | 1636.07 | 19-NOV-15:12 | 0.00 |
| December | 69202563.21 | 18106497.00 | 42.02 | 67326807.50 | 1875755.71 | 0.00 | 1.00 | 10-DEC-15:12 | 0.00 | 01-DEC-00:10 | 7370.11 | 12-DEC-13:02 | 6950.50 | 11-DEC-16:02 | 1197.10 | 12-DEC-13:02 | 1622.85 | 12-DEC-13:02 | 0.00 |
| Annual Sum or Average | 0.209625E+11 | 0.549052E+10 | 3477.27 | 0.175940E+11 | 0.336845E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 27754119.66 | 7500350.56 | 20.73 | 27754119.66 | 0.00 | 0.00 | 1.00 | 0.00 | 6795.32 | 6174.87 | 0.00 | 1574.83 | 0.00 | ||||||
| Maximum of Months | 0.474893E+10 | 0.125597E+10 | 638.24 | 0.379037E+10 | 0.958564E+09 | 0.00 | 1.00 | 0.00 | 8054.93 | 7313.84 | 4054.48 | 1703.42 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 14803132.07 | 3888097.38 | 5.81 | 14803132.07 | -0.0 | 0.00 | 1.00 | 28-FEB-14:12 | 0.00 | 01-FEB-00:10 | 6871.32 | 28-FEB-22:52 | 6871.32 | 28-FEB-22:52 | 0.00 | 28-FEB-17:58 | 1588.66 | 28-FEB-14:12 | 0.00 |
| March | 0.230502E+09 | 59548777.77 | 71.52 | 0.208790E+09 | 21712238.18 | 0.00 | 1.00 | 04-MAR-16:52 | 0.00 | 01-MAR-01:10 | 7366.14 | 30-MAR-12:22 | 7034.61 | 14-MAR-19:52 | 1470.67 | 30-MAR-12:23 | 1652.83 | 30-MAR-12:22 | 0.00 |
| April | 0.888541E+09 | 0.228907E+09 | 225.21 | 0.814166E+09 | 74375621.28 | 0.00 | 1.00 | 02-APR-15:32 | 0.00 | 01-APR-00:10 | 7569.76 | 30-APR-21:52 | 7164.77 | 12-APR-19:12 | 2360.25 | 04-APR-14:13 | 1641.80 | 04-APR-14:12 | 0.00 |
| May | 0.209040E+10 | 0.539275E+09 | 419.46 | 0.181549E+10 | 0.274905E+09 | 0.00 | 1.00 | 01-MAY-14:22 | 0.00 | 01-MAY-05:05 | 7680.17 | 26-MAY-10:12 | 7170.21 | 12-MAY-19:42 | 2820.14 | 31-MAY-10:03 | 1678.11 | 23-MAY-15:02 | 0.00 |
| June | 0.361111E+10 | 0.961060E+09 | 564.39 | 0.303082E+10 | 0.580290E+09 | 0.00 | 1.00 | 01-JUN-09:12 | 0.00 | 01-JUN-05:20 | 7847.39 | 23-JUN-08:52 | 7156.00 | 07-JUN-18:02 | 3570.07 | 23-JUN-08:53 | 1678.83 | 29-JUN-09:03 | 0.00 |
| July | 0.427141E+10 | 0.114038E+10 | 606.19 | 0.344580E+10 | 0.825606E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:15 | 7932.21 | 26-JUL-08:62 | 6459.78 | 02-JUL-21:52 | 3892.95 | 26-JUL-08:03 | 1667.03 | 13-JUL-07:43 | 0.00 |
| August | 0.446426E+10 | 0.118144E+10 | 637.03 | 0.351590E+10 | 0.948362E+09 | 0.00 | 1.00 | 01-AUG-07:22 | 0.00 | 01-AUG-05:15 | 7962.28 | 20-AUG-07:42 | 6041.42 | 08-AUG-17:52 | 4044.66 | 20-AUG-07:43 | 1674.38 | 25-AUG-09:32 | 0.00 |
| September | 0.225238E+10 | 0.582408E+09 | 435.14 | 0.182080E+10 | 0.431578E+09 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-05:15 | 7925.20 | 17-SEP-09:12 | 7124.94 | 18-SEP-18:22 | 3887.71 | 17-SEP-09:13 | 1680.29 | 09-SEP-08:22 | 0.00 |
| October | 0.545677E+09 | 0.137300E+09 | 128.54 | 0.428500E+09 | 0.117177E+09 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-00:10 | 7866.30 | 18-OCT-11:42 | 7060.46 | 22-OCT-17:52 | 3605.26 | 18-OCT-11:43 | 1667.35 | 10-OCT-11:02 | 0.00 |
| November | 27013595.80 | 6496125.17 | 16.64 | 20176296.90 | 6837298.90 | 0.00 | 1.00 | 02-NOV-21:52 | 0.00 | 01-NOV-00:10 | 7528.97 | 04-NOV-17:32 | 6119.76 | 05-NOV-17:42 | 2356.22 | 05-NOV-21:52 | 1619.11 | 05-NOV-15:52 | 0.00 |
| December | 217201.12 | 54818.29 | 0.19 | 179976.22 | 37224.90 | 0.00 | 0.28 | 12-DEC-22:52 | 0.00 | 01-DEC-00:10 | 1802.21 | 12-DEC-22:52 | 1496.23 | 12-DEC-22:52 | 305.98 | 12-DEC-22:52 | 451.54 | 12-DEC-22:52 | 0.00 |
| Annual Sum or Average | 0.183963E+11 | 0.484076E+10 | 3110.12 | 0.151154E+11 | 0.328088E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.446426E+10 | 0.118144E+10 | 637.03 | 0.351590E+10 | 0.948362E+09 | 0.00 | 1.00 | 0.00 | 7962.28 | 7170.21 | 4044.66 | 1680.29 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 19142626.71 | 5155708.85 | 17.90 | 19142626.71 | -0.0 | 0.00 | 1.00 | 29-JAN-17:52 | 0.00 | 01-JAN-00:10 | 6069.08 | 29-JAN-17:52 | 6069.08 | 29-JAN-17:52 | 0.00 | 29-JAN-13:10 | 1410.31 | 29-JAN-17:52 | 0.00 |
| February | 0.141799E+09 | 36031620.54 | 49.10 | 0.141751E+09 | 48093.61 | 0.00 | 1.00 | 20-FEB-15:32 | 0.00 | 01-FEB-00:10 | 6283.33 | 21-FEB-15:12 | 6283.33 | 21-FEB-15:12 | 6.86 | 22-FEB-19:00 | 1447.64 | 28-FEB-13:52 | 0.00 |
| March | 0.465352E+09 | 0.118196E+09 | 144.97 | 0.438867E+09 | 26485214.05 | 0.00 | 1.00 | 03-MAR-16:42 | 0.00 | 01-MAR-01:50 | 6710.62 | 30-MAR-11:32 | 6415.95 | 08-MAR-18:12 | 1359.22 | 30-MAR-11:33 | 1481.86 | 29-MAR-14:22 | 0.00 |
| April | 0.116381E+10 | 0.297196E+09 | 260.62 | 0.108503E+10 | 78776501.04 | 0.00 | 1.00 | 02-APR-14:32 | 0.00 | 01-APR-00:10 | 6867.78 | 30-APR-21:52 | 6542.95 | 14-APR-11:02 | 2067.83 | 30-APR-21:53 | 1486.41 | 02-APR-16:52 | 0.00 |
| May | 0.225421E+10 | 0.577204E+09 | 423.67 | 0.197294E+10 | 0.281269E+09 | 0.00 | 1.00 | 01-MAY-14:12 | 0.00 | 01-MAY-05:05 | 7025.57 | 31-MAY-09:53 | 6540.32 | 13-MAY-10:42 | 2443.75 | 26-MAY-10:03 | 1524.88 | 23-MAY-14:52 | 0.00 |
| June | 0.368059E+10 | 0.973219E+09 | 562.07 | 0.309983E+10 | 0.580756E+09 | 0.00 | 1.00 | 01-JUN-09:22 | 0.00 | 01-JUN-05:20 | 7125.70 | 23-JUN-08:52 | 6508.72 | 07-JUN-12:52 | 3191.24 | 23-JUN-08:53 | 1530.09 | 25-JUN-08:52 | 0.00 |
| July | 0.438696E+10 | 0.116225E+10 | 603.59 | 0.355348E+10 | 0.833486E+09 | 0.00 | 1.00 | 01-JUL-08:32 | 0.00 | 01-JUL-05:15 | 7209.16 | 30-JUL-09:32 | 5825.18 | 02-JUL-21:52 | 3551.73 | 30-JUL-07:53 | 1527.88 | 09-JUL-09:25 | 0.00 |
| August | 0.474888E+10 | 0.124743E+10 | 642.15 | 0.378433E+10 | 0.964543E+09 | 0.00 | 1.00 | 01-AUG-07:32 | 0.00 | 01-AUG-05:15 | 7235.62 | 20-AUG-07:32 | 5549.60 | 08-AUG-17:52 | 3679.78 | 20-AUG-07:35 | 1521.71 | 25-AUG-09:32 | 0.00 |
| September | 0.273957E+10 | 0.700575E+09 | 456.66 | 0.227180E+10 | 0.467767E+09 | 0.00 | 1.00 | 01-SEP-10:22 | 0.00 | 01-SEP-05:15 | 7218.24 | 17-SEP-08:42 | 6550.89 | 19-SEP-11:32 | 3613.68 | 17-SEP-08:45 | 1514.96 | 08-SEP-08:52 | 0.00 |
| October | 0.103801E+10 | 0.257274E+09 | 213.21 | 0.897382E+09 | 0.140631E+09 | 0.00 | 1.00 | 01-OCT-13:32 | 0.00 | 01-OCT-00:10 | 7143.94 | 18-OCT-11:22 | 6573.85 | 08-OCT-11:42 | 3227.50 | 18-OCT-11:23 | 1513.19 | 10-OCT-11:02 | 0.00 |
| November | 0.205213E+09 | 50547598.70 | 81.21 | 0.187832E+09 | 17381118.59 | 0.00 | 1.00 | 01-NOV-13:42 | 0.00 | 01-NOV-00:10 | 6878.02 | 04-NOV-16:42 | 6405.64 | 06-NOV-15:02 | 2376.32 | 27-NOV-22:52 | 1469.46 | 19-NOV-15:12 | 0.00 |
| December | 59318514.94 | 15493408.35 | 42.15 | 57490788.46 | 1827726.47 | 0.00 | 1.00 | 10-DEC-15:12 | 0.00 | 01-DEC-00:10 | 6628.55 | 12-DEC-13:02 | 6178.60 | 10-DEC-16:52 | 1036.46 | 12-DEC-13:02 | 1458.16 | 12-DEC-13:02 | 0.00 |
| Annual Sum or Average | 0.209029E+11 | 0.544058E+10 | 3497.31 | 0.175099E+11 | 0.339297E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 19142626.71 | 5155708.85 | 17.90 | 19142626.71 | -0.0 | 0.00 | 1.00 | 0.00 | 6069.08 | 5549.60 | 0.00 | 1410.31 | 0.00 | ||||||
| Maximum of Months | 0.474888E+10 | 0.124743E+10 | 642.15 | 0.378433E+10 | 0.964543E+09 | 0.00 | 1.00 | 0.00 | 7235.62 | 6573.85 | 3679.78 | 1530.09 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 13237739.78 | 3462462.69 | 5.35 | 13237739.78 | 0.00 | 0.00 | 1.00 | 28-FEB-14:12 | 0.00 | 01-FEB-00:10 | 6167.60 | 28-FEB-17:52 | 6167.60 | 28-FEB-17:52 | 0.00 | 28-FEB-14:50 | 1427.24 | 28-FEB-14:12 | 0.00 |
| March | 0.194112E+09 | 50093621.00 | 67.90 | 0.173832E+09 | 20279921.35 | 0.00 | 1.00 | 08-MAR-15:32 | 0.00 | 01-MAR-00:50 | 6604.08 | 29-MAR-13:52 | 6286.62 | 14-MAR-19:52 | 1378.86 | 30-MAR-12:23 | 1481.26 | 30-MAR-12:22 | 0.00 |
| April | 0.847124E+09 | 0.217682E+09 | 217.13 | 0.774945E+09 | 72178840.71 | 0.00 | 1.00 | 02-APR-15:32 | 0.00 | 01-APR-00:10 | 6783.92 | 30-APR-21:52 | 6415.80 | 14-APR-11:32 | 2095.31 | 04-APR-14:13 | 1472.04 | 04-APR-14:12 | 0.00 |
| May | 0.208613E+10 | 0.535065E+09 | 418.40 | 0.181073E+10 | 0.275400E+09 | 0.00 | 1.00 | 01-MAY-14:22 | 0.00 | 01-MAY-05:05 | 6941.73 | 31-MAY-09:43 | 6440.95 | 14-MAY-11:22 | 2454.13 | 26-MAY-10:13 | 1503.63 | 23-MAY-15:02 | 0.00 |
| June | 0.365056E+10 | 0.964489E+09 | 566.11 | 0.306380E+10 | 0.586755E+09 | 0.00 | 1.00 | 01-JUN-09:12 | 0.00 | 01-JUN-05:20 | 7030.85 | 23-JUN-08:52 | 6432.10 | 07-JUN-13:22 | 3168.57 | 23-JUN-08:53 | 1505.33 | 29-JUN-09:02 | 0.00 |
| July | 0.432140E+10 | 0.114436E+10 | 608.48 | 0.348671E+10 | 0.834686E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:15 | 7100.33 | 26-JUL-08:62 | 5751.69 | 02-JUL-21:52 | 3429.88 | 30-JUL-07:52 | 1494.75 | 13-JUL-07:43 | 0.00 |
| August | 0.446367E+10 | 0.117337E+10 | 640.21 | 0.351048E+10 | 0.953191E+09 | 0.00 | 1.00 | 01-AUG-07:22 | 0.00 | 01-AUG-05:15 | 7139.15 | 20-AUG-07:42 | 5476.40 | 26-AUG-08:52 | 3653.16 | 20-AUG-07:45 | 1500.92 | 25-AUG-09:32 | 0.00 |
| September | 0.224275E+10 | 0.576842E+09 | 435.83 | 0.180892E+10 | 0.433834E+09 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-05:15 | 7096.93 | 17-SEP-09:12 | 6426.14 | 13-SEP-13:22 | 3453.23 | 17-SEP-09:15 | 1506.81 | 09-SEP-08:22 | 0.00 |
| October | 0.524241E+09 | 0.131290E+09 | 127.90 | 0.408158E+09 | 0.116083E+09 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-00:10 | 7047.10 | 18-OCT-11:42 | 6327.05 | 22-OCT-15:52 | 3197.79 | 18-OCT-11:43 | 1495.63 | 10-OCT-11:02 | 0.00 |
| November | 20874150.99 | 5008400.31 | 14.39 | 15448338.60 | 5425812.39 | 0.00 | 1.00 | 03-NOV-21:52 | 0.00 | 01-NOV-00:10 | 6726.77 | 04-NOV-17:32 | 5404.32 | 05-NOV-17:42 | 2164.98 | 05-NOV-21:52 | 1452.20 | 05-NOV-15:52 | 0.00 |
| December | 134793.85 | 34020.84 | 0.03 | 111846.44 | 22947.41 | 0.00 | 0.24 | 12-DEC-22:52 | 0.00 | 01-DEC-00:10 | 1347.94 | 12-DEC-22:52 | 1118.46 | 12-DEC-22:52 | 229.47 | 12-DEC-22:52 | 340.21 | 12-DEC-22:52 | 0.00 |
| Annual Sum or Average | 0.183642E+11 | 0.480170E+10 | 3101.72 | 0.150664E+11 | 0.329786E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.446367E+10 | 0.117337E+10 | 640.21 | 0.351048E+10 | 0.953191E+09 | 0.00 | 1.00 | 0.00 | 7139.15 | 6440.95 | 3653.16 | 1506.81 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 11331200.15 | 2959881.22 | 10.93 | 11277648.47 | 53551.68 | 0.00 | 1.00 | 28-FEB-14:12 | 0.00 | 01-FEB-00:10 | 5710.43 | 28-FEB-17:52 | 5710.43 | 28-FEB-17:52 | 6.25 | 22-FEB-21:00 | 1318.57 | 28-FEB-14:12 | 0.00 |
| March | 0.198067E+09 | 51138773.59 | 82.88 | 0.176956E+09 | 21110744.61 | 0.00 | 1.00 | 04-MAR-16:52 | 0.00 | 01-MAR-02:70 | 6118.55 | 30-MAR-12:22 | 5844.01 | 14-MAR-19:52 | 1310.61 | 30-MAR-12:23 | 1372.40 | 30-MAR-12:22 | 0.00 |
| April | 0.776780E+09 | 0.199631E+09 | 270.16 | 0.698835E+09 | 77945066.52 | 0.00 | 1.00 | 02-APR-15:32 | 0.00 | 01-APR-00:10 | 6292.19 | 30-APR-21:52 | 5875.61 | 24-APR-17:22 | 1956.09 | 04-APR-14:13 | 1363.12 | 04-APR-14:12 | 0.00 |
| May | 0.180121E+10 | 0.463394E+09 | 433.06 | 0.153890E+10 | 0.262303E+09 | 0.00 | 1.00 | 01-MAY-14:22 | 0.00 | 01-MAY-05:05 | 6373.83 | 26-MAY-10:12 | 5868.07 | 11-MAY-21:52 | 2317.51 | 31-MAY-10:03 | 1393.71 | 23-MAY-15:02 | 0.00 |
| June | 0.304827E+10 | 0.808351E+09 | 573.26 | 0.252173E+10 | 0.526535E+09 | 0.00 | 1.00 | 01-JUN-09:12 | 0.00 | 01-JUN-05:20 | 6508.85 | 23-JUN-08:52 | 5894.00 | 07-JUN-15:12 | 2978.54 | 23-JUN-08:55 | 1393.85 | 29-JUN-09:03 | 0.00 |
| July | 0.361155E+10 | 0.959578E+09 | 607.71 | 0.285638E+10 | 0.755167E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:15 | 6562.26 | 26-JUL-08:62 | 5318.59 | 02-JUL-21:52 | 3166.84 | 26-JUL-08:05 | 1384.06 | 13-JUL-07:43 | 0.00 |
| August | 0.376205E+10 | 0.991116E+09 | 637.24 | 0.290339E+10 | 0.858663E+09 | 0.00 | 1.00 | 01-AUG-07:22 | 0.00 | 01-AUG-05:15 | 6587.93 | 20-AUG-07:42 | 4970.36 | 08-AUG-17:52 | 3289.69 | 20-AUG-07:45 | 1390.26 | 25-AUG-09:32 | 0.00 |
| September | 0.196671E+10 | 0.506056E+09 | 458.98 | 0.156066E+10 | 0.406057E+09 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-05:15 | 6561.16 | 17-SEP-09:12 | 5866.36 | 13-SEP-19:02 | 3177.56 | 17-SEP-09:15 | 1395.14 | 09-SEP-08:22 | 0.00 |
| October | 0.494386E+09 | 0.123787E+09 | 144.25 | 0.382088E+09 | 0.112298E+09 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-00:10 | 6524.82 | 18-OCT-11:42 | 5859.43 | 22-OCT-17:52 | 2955.31 | 18-OCT-11:43 | 1384.40 | 10-OCT-11:02 | 0.00 |
| November | 37096234.97 | 9069345.88 | 26.81 | 27532570.12 | 9563664.85 | 0.00 | 1.00 | 02-NOV-21:52 | 0.00 | 01-NOV-00:10 | 6244.76 | 05-NOV-21:52 | 5030.98 | 02-NOV-21:52 | 1921.23 | 05-NOV-21:52 | 1344.73 | 05-NOV-15:52 | 0.00 |
| December | 1822558.43 | 453304.83 | 2.64 | 1413730.01 | 408828.41 | 0.00 | 0.72 | 12-DEC-22:52 | 0.00 | 01-DEC-00:10 | 4124.03 | 12-DEC-22:52 | 3448.10 | 12-DEC-22:52 | 779.63 | 13-DEC-21:02 | 960.39 | 12-DEC-22:52 | 0.00 |
| Annual Sum or Average | 0.157093E+11 | 0.411553E+10 | 3247.92 | 0.126792E+11 | 0.303010E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.376205E+10 | 0.991116E+09 | 637.24 | 0.290339E+10 | 0.858663E+09 | 0.00 | 1.00 | 0.00 | 6587.93 | 5894.00 | 3289.69 | 1395.14 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 11618335.42 | 3037247.51 | 11.19 | 11559830.61 | 58504.81 | 0.00 | 1.00 | 28-FEB-14:12 | 0.00 | 01-FEB-00:10 | 5690.12 | 28-FEB-17:52 | 5690.12 | 28-FEB-17:52 | 6.77 | 22-FEB-21:00 | 1314.17 | 28-FEB-14:12 | 0.00 |
| March | 0.196455E+09 | 50723910.66 | 83.29 | 0.175379E+09 | 21075669.84 | 0.00 | 1.00 | 04-MAR-16:52 | 0.00 | 01-MAR-02:70 | 6096.41 | 30-MAR-12:22 | 5817.06 | 14-MAR-19:52 | 1303.87 | 30-MAR-12:23 | 1367.52 | 30-MAR-12:22 | 0.00 |
| April | 0.778644E+09 | 0.200111E+09 | 269.72 | 0.700767E+09 | 77876559.62 | 0.00 | 1.00 | 02-APR-15:32 | 0.00 | 01-APR-00:10 | 6269.83 | 30-APR-21:52 | 5848.32 | 16-APR-20:12 | 1949.87 | 30-APR-21:53 | 1358.28 | 04-APR-14:12 | 0.00 |
| May | 0.180803E+10 | 0.465038E+09 | 433.28 | 0.154527E+10 | 0.262763E+09 | 0.00 | 1.00 | 01-MAY-14:22 | 0.00 | 01-MAY-05:05 | 6351.21 | 26-MAY-10:12 | 5847.72 | 11-MAY-21:52 | 2286.30 | 31-MAY-10:03 | 1388.67 | 23-MAY-15:02 | 0.00 |
| June | 0.305479E+10 | 0.809884E+09 | 573.71 | 0.252759E+10 | 0.527199E+09 | 0.00 | 1.00 | 01-JUN-09:12 | 0.00 | 01-JUN-05:20 | 6485.91 | 23-JUN-08:52 | 5877.76 | 07-JUN-15:12 | 2968.40 | 23-JUN-08:55 | 1388.93 | 29-JUN-09:03 | 0.00 |
| July | 0.361631E+10 | 0.960609E+09 | 607.63 | 0.286038E+10 | 0.755938E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:15 | 6538.47 | 26-JUL-08:62 | 5297.31 | 02-JUL-21:52 | 3153.38 | 26-JUL-08:05 | 1379.17 | 13-JUL-07:43 | 0.00 |
| August | 0.376421E+10 | 0.991508E+09 | 637.68 | 0.290509E+10 | 0.859124E+09 | 0.00 | 1.00 | 01-AUG-07:22 | 0.00 | 01-AUG-05:15 | 6564.66 | 20-AUG-07:42 | 4953.40 | 08-AUG-17:52 | 3278.28 | 20-AUG-07:45 | 1385.40 | 25-AUG-09:32 | 0.00 |
| September | 0.197088E+10 | 0.507034E+09 | 459.58 | 0.156423E+10 | 0.406649E+09 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-05:15 | 6537.93 | 17-SEP-09:12 | 5845.46 | 13-SEP-19:02 | 3166.30 | 17-SEP-09:15 | 1390.22 | 09-SEP-08:22 | 0.00 |
| October | 0.495638E+09 | 0.124079E+09 | 144.24 | 0.383142E+09 | 0.112496E+09 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-00:10 | 6501.48 | 18-OCT-11:42 | 5838.45 | 22-OCT-17:52 | 2944.07 | 18-OCT-11:43 | 1379.62 | 10-OCT-11:02 | 0.00 |
| November | 36433760.67 | 8903873.95 | 25.93 | 27019946.33 | 9413814.33 | 0.00 | 1.00 | 02-NOV-21:52 | 0.00 | 01-NOV-00:10 | 6221.74 | 05-NOV-21:52 | 5003.94 | 02-NOV-21:52 | 1920.10 | 05-NOV-21:52 | 1339.99 | 05-NOV-15:52 | 0.00 |
| December | 1817688.67 | 452102.27 | 2.81 | 1406710.68 | 410977.99 | 0.00 | 0.71 | 12-DEC-22:52 | 0.00 | 01-DEC-00:10 | 4051.16 | 12-DEC-22:52 | 3385.49 | 12-DEC-22:52 | 789.98 | 13-DEC-21:02 | 944.92 | 12-DEC-22:52 | 0.00 |
| Annual Sum or Average | 0.157348E+11 | 0.412138E+10 | 3249.05 | 0.127018E+11 | 0.303301E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.376421E+10 | 0.991508E+09 | 637.68 | 0.290509E+10 | 0.859124E+09 | 0.00 | 1.00 | 0.00 | 6564.66 | 5877.76 | 3278.28 | 1390.22 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 32570556.23 | 8799323.45 | 27.43 | 32570556.23 | -0.0 | 0.00 | 1.00 | 29-JAN-17:52 | 0.00 | 01-JAN-00:10 | 5662.37 | 29-JAN-17:52 | 5662.37 | 29-JAN-17:52 | 0.00 | 29-JAN-17:52 | 1313.46 | 29-JAN-17:52 | 0.00 |
| February | 0.151742E+09 | 38715680.17 | 60.25 | 0.151363E+09 | 378344.05 | 0.00 | 1.00 | 20-FEB-15:32 | 0.00 | 01-FEB-00:10 | 5839.25 | 22-FEB-16:32 | 5839.25 | 22-FEB-16:32 | 66.05 | 19-FEB-20:53 | 1345.43 | 28-FEB-13:52 | 0.00 |
| March | 0.492787E+09 | 0.125414E+09 | 179.66 | 0.463558E+09 | 29229173.20 | 0.00 | 1.00 | 03-MAR-16:42 | 0.00 | 01-MAR-03:20 | 6252.75 | 30-MAR-11:32 | 5964.24 | 08-MAR-18:12 | 1323.53 | 30-MAR-11:33 | 1377.55 | 29-MAR-14:22 | 0.00 |
| April | 0.109071E+10 | 0.279329E+09 | 315.93 | 0.100610E+10 | 84618626.17 | 0.00 | 1.00 | 02-APR-14:32 | 0.00 | 01-APR-00:10 | 6381.83 | 23-APR-12:32 | 6057.05 | 24-APR-15:42 | 1929.22 | 04-APR-13:43 | 1381.53 | 02-APR-16:52 | 0.00 |
| May | 0.197108E+10 | 0.506603E+09 | 438.54 | 0.170247E+10 | 0.268610E+09 | 0.00 | 1.00 | 01-MAY-14:12 | 0.00 | 01-MAY-05:05 | 6481.25 | 31-MAY-10:12 | 6006.56 | 12-MAY-15:32 | 2326.59 | 31-MAY-10:13 | 1418.56 | 23-MAY-14:52 | 0.00 |
| June | 0.308109E+10 | 0.818017E+09 | 567.36 | 0.255982E+10 | 0.521274E+09 | 0.00 | 1.00 | 01-JUN-09:22 | 0.00 | 01-JUN-05:20 | 6621.10 | 23-JUN-08:52 | 5991.10 | 07-JUN-15:22 | 2958.84 | 23-JUN-08:53 | 1422.14 | 25-JUN-08:52 | 0.00 |
| July | 0.368134E+10 | 0.978894E+09 | 601.31 | 0.292634E+10 | 0.754995E+09 | 0.00 | 1.00 | 01-JUL-08:32 | 0.00 | 01-JUL-05:15 | 6694.21 | 30-JUL-09:32 | 5405.65 | 02-JUL-21:52 | 3279.19 | 30-JUL-09:35 | 1411.66 | 01-JUL-08:33 | 0.00 |
| August | 0.405232E+10 | 0.106757E+10 | 638.78 | 0.317916E+10 | 0.873158E+09 | 0.00 | 1.00 | 01-AUG-07:32 | 0.00 | 01-AUG-05:15 | 6709.71 | 20-AUG-07:32 | 5119.30 | 08-AUG-17:52 | 3354.65 | 20-AUG-07:35 | 1414.86 | 25-AUG-09:32 | 0.00 |
| September | 0.246895E+10 | 0.632566E+09 | 478.36 | 0.202572E+10 | 0.443232E+09 | 0.00 | 1.00 | 01-SEP-10:22 | 0.00 | 01-SEP-05:15 | 6694.96 | 17-SEP-08:42 | 6049.10 | 13-SEP-13:22 | 3300.56 | 17-SEP-08:45 | 1408.29 | 08-SEP-08:52 | 0.00 |
| October | 0.103684E+10 | 0.257831E+09 | 263.02 | 0.896771E+09 | 0.140066E+09 | 0.00 | 1.00 | 01-OCT-13:32 | 0.00 | 01-OCT-00:10 | 6638.01 | 18-OCT-11:22 | 6100.40 | 22-OCT-13:42 | 2990.65 | 18-OCT-11:23 | 1407.49 | 10-OCT-11:02 | 0.00 |
| November | 0.276739E+09 | 68867483.30 | 131.33 | 0.252388E+09 | 24350553.45 | 0.00 | 1.00 | 01-NOV-13:42 | 0.00 | 01-NOV-00:10 | 6393.01 | 27-NOV-22:52 | 5965.11 | 06-NOV-15:02 | 2148.70 | 27-NOV-22:52 | 1365.83 | 19-NOV-15:12 | 0.00 |
| December | 94019349.21 | 24625111.66 | 70.73 | 90499767.08 | 3519582.12 | 0.00 | 1.00 | 10-DEC-15:12 | 0.00 | 01-DEC-00:10 | 6175.67 | 12-DEC-13:02 | 5741.42 | 10-DEC-16:52 | 1569.36 | 13-DEC-21:02 | 1355.78 | 12-DEC-13:02 | 0.00 |
| Annual Sum or Average | 0.184302E+11 | 0.480723E+10 | 3772.69 | 0.152868E+11 | 0.314343E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 32570556.23 | 8799323.45 | 27.43 | 32570556.23 | -0.0 | 0.00 | 1.00 | 0.00 | 5662.37 | 5119.30 | 0.00 | 1313.46 | 0.00 | ||||||
| Maximum of Months | 0.405232E+10 | 0.106757E+10 | 638.78 | 0.317916E+10 | 0.873158E+09 | 0.00 | 1.00 | 0.00 | 6709.71 | 6100.40 | 3354.65 | 1422.14 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 33398393.10 | 9020844.92 | 28.09 | 33398393.10 | -0.0 | 0.00 | 1.00 | 29-JAN-17:52 | 0.00 | 01-JAN-00:10 | 5642.81 | 29-JAN-17:52 | 5642.81 | 29-JAN-17:52 | 0.00 | 15-JAN-16:10 | 1308.93 | 29-JAN-17:52 | 0.00 |
| February | 0.153810E+09 | 39239918.13 | 60.39 | 0.153432E+09 | 377650.82 | 0.00 | 1.00 | 20-FEB-15:32 | 0.00 | 01-FEB-00:10 | 5820.62 | 22-FEB-16:32 | 5820.62 | 22-FEB-16:32 | 54.24 | 19-FEB-20:53 | 1340.86 | 28-FEB-13:52 | 0.00 |
| March | 0.493274E+09 | 0.125517E+09 | 179.47 | 0.464233E+09 | 29040948.38 | 0.00 | 1.00 | 03-MAR-16:42 | 0.00 | 01-MAR-03:20 | 6230.81 | 30-MAR-11:32 | 5944.10 | 08-MAR-18:12 | 1311.98 | 30-MAR-11:33 | 1372.80 | 29-MAR-14:22 | 0.00 |
| April | 0.109350E+10 | 0.279976E+09 | 316.05 | 0.100942E+10 | 84080797.06 | 0.00 | 1.00 | 02-APR-14:32 | 0.00 | 01-APR-00:10 | 6359.69 | 23-APR-12:32 | 6041.05 | 24-APR-15:42 | 1914.78 | 04-APR-13:43 | 1376.78 | 02-APR-16:52 | 0.00 |
| May | 0.197639E+10 | 0.507791E+09 | 438.55 | 0.170832E+10 | 0.268073E+09 | 0.00 | 1.00 | 01-MAY-14:12 | 0.00 | 01-MAY-05:05 | 6457.87 | 31-MAY-10:12 | 5988.35 | 12-MAY-15:32 | 2308.83 | 31-MAY-10:13 | 1413.62 | 23-MAY-14:52 | 0.00 |
| June | 0.308645E+10 | 0.819190E+09 | 567.65 | 0.256593E+10 | 0.520523E+09 | 0.00 | 1.00 | 01-JUN-09:22 | 0.00 | 01-JUN-05:20 | 6598.46 | 23-JUN-08:52 | 5974.12 | 07-JUN-15:22 | 2946.62 | 23-JUN-08:53 | 1417.24 | 25-JUN-08:52 | 0.00 |
| July | 0.368395E+10 | 0.979314E+09 | 601.61 | 0.292979E+10 | 0.754157E+09 | 0.00 | 1.00 | 01-JUL-08:32 | 0.00 | 01-JUL-05:15 | 6671.32 | 30-JUL-09:32 | 5388.59 | 02-JUL-21:52 | 3266.56 | 30-JUL-09:35 | 1406.82 | 01-JUL-08:33 | 0.00 |
| August | 0.405286E+10 | 0.106743E+10 | 639.25 | 0.318075E+10 | 0.872112E+09 | 0.00 | 1.00 | 01-AUG-07:32 | 0.00 | 01-AUG-05:15 | 6686.84 | 20-AUG-07:32 | 5105.44 | 08-AUG-17:52 | 3342.12 | 20-AUG-07:35 | 1410.05 | 25-AUG-09:32 | 0.00 |
| September | 0.247131E+10 | 0.632970E+09 | 478.38 | 0.202879E+10 | 0.442521E+09 | 0.00 | 1.00 | 01-SEP-10:22 | 0.00 | 01-SEP-05:15 | 6672.01 | 17-SEP-08:42 | 6032.14 | 13-SEP-13:22 | 3287.57 | 17-SEP-08:45 | 1403.44 | 08-SEP-08:52 | 0.00 |
| October | 0.103954E+10 | 0.258415E+09 | 264.36 | 0.899808E+09 | 0.139730E+09 | 0.00 | 1.00 | 01-OCT-13:32 | 0.00 | 01-OCT-00:10 | 6614.98 | 18-OCT-11:22 | 6080.97 | 22-OCT-13:42 | 2976.77 | 18-OCT-11:23 | 1402.60 | 10-OCT-11:02 | 0.00 |
| November | 0.276821E+09 | 68887905.70 | 131.10 | 0.252727E+09 | 24094034.19 | 0.00 | 1.00 | 01-NOV-13:42 | 0.00 | 01-NOV-00:10 | 6371.09 | 27-NOV-22:52 | 5948.72 | 06-NOV-15:02 | 2137.09 | 27-NOV-22:52 | 1361.12 | 19-NOV-15:12 | 0.00 |
| December | 95486648.90 | 25017091.99 | 71.56 | 91992231.61 | 3494417.29 | 0.00 | 1.00 | 10-DEC-15:12 | 0.00 | 01-DEC-00:10 | 6154.50 | 12-DEC-13:02 | 5722.10 | 10-DEC-16:52 | 1577.34 | 13-DEC-21:02 | 1351.11 | 12-DEC-13:02 | 0.00 |
| Annual Sum or Average | 0.184568E+11 | 0.481277E+10 | 3776.46 | 0.153186E+11 | 0.313820E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 33398393.10 | 9020844.92 | 28.09 | 33398393.10 | -0.0 | 0.00 | 1.00 | 0.00 | 5642.81 | 5105.44 | 0.00 | 1308.93 | 0.00 | ||||||
| Maximum of Months | 0.405286E+10 | 0.106743E+10 | 639.25 | 0.318075E+10 | 0.872112E+09 | 0.00 | 1.00 | 0.00 | 6686.84 | 6080.97 | 3342.12 | 1417.24 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.87 | 106.53 | 47.34 | 180.94 | 181.57 | 0.00 | 0.00 | 0.00 |
| February | 146.91 | 98.84 | 48.07 | 189.52 | 153.65 | 0.00 | 0.00 | 0.00 |
| March | 130.59 | 67.81 | 62.77 | 180.72 | 108.98 | 0.00 | 0.00 | 0.00 |
| April | 101.14 | 34.91 | 66.23 | 156.62 | 88.57 | 0.00 | 0.00 | 0.00 |
| May | 79.90 | 9.79 | 70.12 | 130.84 | 57.08 | 0.00 | 0.00 | 0.00 |
| June | 73.71 | 4.44 | 69.27 | 144.50 | 33.49 | 0.00 | 0.00 | 0.00 |
| July | 73.97 | 5.34 | 68.63 | 153.29 | 22.05 | 0.00 | 0.00 | 0.00 |
| August | 88.04 | 16.04 | 72.00 | 184.44 | 17.60 | 0.00 | 0.00 | 0.00 |
| September | 101.08 | 39.92 | 61.16 | 176.34 | 48.96 | 0.00 | 0.00 | 0.00 |
| October | 139.89 | 90.18 | 49.71 | 209.10 | 106.56 | 0.00 | 0.00 | 0.00 |
| November | 153.17 | 102.10 | 51.07 | 204.47 | 139.48 | 0.00 | 0.00 | 0.00 |
| December | 153.46 | 107.81 | 45.65 | 188.79 | 162.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.16 | 56.76 | 59.40 | 174.89 | 93.08 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.71 | 4.44 | 45.65 | 130.84 | 17.60 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 153.87 | 107.81 | 72.00 | 209.10 | 181.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.68 | 20.37 | 23.32 | 34.43 | 135.57 | 0.00 | 0.00 | 0.00 |
| February | 49.81 | 23.29 | 26.52 | 51.73 | 112.14 | 0.00 | 0.00 | 0.00 |
| March | 73.25 | 35.34 | 37.91 | 92.48 | 74.36 | 0.00 | 0.00 | 0.00 |
| April | 82.37 | 37.62 | 44.75 | 121.10 | 57.46 | 0.00 | 0.00 | 0.00 |
| May | 83.00 | 31.48 | 51.52 | 134.52 | 36.92 | 0.00 | 0.00 | 0.00 |
| June | 87.39 | 33.75 | 53.64 | 161.14 | 21.75 | 0.00 | 0.00 | 0.00 |
| July | 82.18 | 30.44 | 51.73 | 157.64 | 14.29 | 0.00 | 0.00 | 0.00 |
| August | 80.53 | 30.09 | 50.45 | 155.27 | 11.53 | 0.00 | 0.00 | 0.00 |
| September | 65.85 | 27.51 | 38.34 | 107.89 | 32.23 | 0.00 | 0.00 | 0.00 |
| October | 58.30 | 30.18 | 28.12 | 77.95 | 74.49 | 0.00 | 0.00 | 0.00 |
| November | 46.43 | 20.70 | 25.73 | 48.87 | 101.86 | 0.00 | 0.00 | 0.00 |
| December | 38.61 | 16.94 | 21.67 | 31.27 | 121.86 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.03 | 28.16 | 37.87 | 98.11 | 65.97 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38.61 | 16.94 | 21.67 | 31.27 | 11.53 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.39 | 37.62 | 53.64 | 161.14 | 135.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.68 | 20.37 | 23.32 | 36.46 | 131.23 | 0.00 | 0.00 | 0.00 |
| February | 49.81 | 23.29 | 26.52 | 54.54 | 106.69 | 0.00 | 0.00 | 0.00 |
| March | 73.25 | 35.34 | 37.91 | 96.72 | 67.94 | 0.00 | 0.00 | 0.00 |
| April | 82.37 | 37.62 | 44.75 | 123.02 | 55.59 | 0.00 | 0.00 | 0.00 |
| May | 83.00 | 31.48 | 51.52 | 135.01 | 36.63 | 0.00 | 0.00 | 0.00 |
| June | 87.39 | 33.75 | 53.64 | 161.26 | 21.76 | 0.00 | 0.00 | 0.00 |
| July | 82.18 | 30.44 | 51.73 | 157.82 | 14.27 | 0.00 | 0.00 | 0.00 |
| August | 80.53 | 30.09 | 50.45 | 155.79 | 11.32 | 0.00 | 0.00 | 0.00 |
| September | 65.85 | 27.51 | 38.34 | 108.82 | 31.54 | 0.00 | 0.00 | 0.00 |
| October | 58.30 | 30.18 | 28.12 | 79.77 | 72.44 | 0.00 | 0.00 | 0.00 |
| November | 46.43 | 20.70 | 25.73 | 51.93 | 95.56 | 0.00 | 0.00 | 0.00 |
| December | 38.61 | 16.94 | 21.67 | 34.57 | 111.68 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.03 | 28.16 | 37.87 | 99.89 | 62.83 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38.61 | 16.94 | 21.67 | 34.57 | 11.32 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.39 | 37.62 | 53.64 | 161.26 | 131.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.20 | 0.00 | 29.20 | 4.48 | 216.75 | 0.00 | 0.00 | 0.00 |
| February | 32.37 | 0.00 | 32.37 | 15.17 | 172.43 | 0.00 | 0.00 | 0.00 |
| March | 45.46 | 0.00 | 45.46 | 34.02 | 107.38 | 0.00 | 0.00 | 0.00 |
| April | 55.04 | 0.29 | 54.75 | 63.64 | 85.23 | 0.00 | 0.00 | 0.00 |
| May | 65.74 | 2.05 | 63.69 | 95.44 | 53.46 | 0.00 | 0.00 | 0.00 |
| June | 72.10 | 4.53 | 67.57 | 136.63 | 30.92 | 0.00 | 0.00 | 0.00 |
| July | 68.28 | 3.33 | 64.96 | 138.13 | 20.83 | 0.00 | 0.00 | 0.00 |
| August | 60.86 | 0.77 | 60.09 | 125.38 | 16.66 | 0.00 | 0.00 | 0.00 |
| September | 45.92 | 0.02 | 45.90 | 68.84 | 48.65 | 0.00 | 0.00 | 0.00 |
| October | 34.89 | 0.00 | 34.89 | 27.61 | 113.32 | 0.00 | 0.00 | 0.00 |
| November | 31.23 | 0.00 | 31.23 | 13.14 | 151.52 | 0.00 | 0.00 | 0.00 |
| December | 27.00 | 0.00 | 27.00 | 4.37 | 179.93 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.42 | 0.92 | 46.50 | 60.83 | 99.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 0.00 | 27.00 | 4.37 | 16.66 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.10 | 4.53 | 67.57 | 138.13 | 216.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.87 | 106.53 | 47.34 | 186.42 | 163.69 | 0.00 | 0.00 | 0.00 |
| February | 146.91 | 98.84 | 48.07 | 192.89 | 143.71 | 0.00 | 0.00 | 0.00 |
| March | 130.59 | 67.81 | 62.77 | 181.46 | 108.27 | 0.00 | 0.00 | 0.00 |
| April | 101.14 | 34.91 | 66.23 | 154.84 | 91.83 | 0.00 | 0.00 | 0.00 |
| May | 79.90 | 9.79 | 70.12 | 126.43 | 65.27 | 0.00 | 0.00 | 0.00 |
| June | 73.71 | 4.44 | 69.27 | 134.80 | 47.20 | 0.00 | 0.00 | 0.00 |
| July | 73.97 | 5.34 | 68.63 | 139.44 | 38.05 | 0.00 | 0.00 | 0.00 |
| August | 88.04 | 16.04 | 72.00 | 171.81 | 35.02 | 0.00 | 0.00 | 0.00 |
| September | 101.08 | 39.92 | 61.16 | 169.54 | 64.29 | 0.00 | 0.00 | 0.00 |
| October | 139.89 | 90.18 | 49.71 | 207.72 | 112.94 | 0.00 | 0.00 | 0.00 |
| November | 153.17 | 102.10 | 51.07 | 206.42 | 138.55 | 0.00 | 0.00 | 0.00 |
| December | 153.46 | 107.81 | 45.65 | 192.32 | 155.18 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.16 | 56.76 | 59.40 | 171.90 | 96.74 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.71 | 4.44 | 45.65 | 126.43 | 35.02 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 153.87 | 107.81 | 72.00 | 207.72 | 163.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.63 | 19.47 | 23.16 | 32.00 | 118.24 | 0.00 | 0.00 | 0.00 |
| February | 53.05 | 28.44 | 24.61 | 53.80 | 99.20 | 0.00 | 0.00 | 0.00 |
| March | 67.11 | 30.56 | 36.54 | 78.02 | 69.60 | 0.00 | 0.00 | 0.00 |
| April | 81.05 | 36.99 | 44.05 | 114.93 | 56.03 | 0.00 | 0.00 | 0.00 |
| May | 89.01 | 37.69 | 51.32 | 138.79 | 39.60 | 0.00 | 0.00 | 0.00 |
| June | 92.05 | 38.60 | 53.45 | 161.08 | 28.54 | 0.00 | 0.00 | 0.00 |
| July | 89.76 | 37.75 | 52.02 | 160.06 | 23.44 | 0.00 | 0.00 | 0.00 |
| August | 82.04 | 32.48 | 49.56 | 148.33 | 21.93 | 0.00 | 0.00 | 0.00 |
| September | 67.21 | 29.64 | 37.58 | 104.52 | 41.02 | 0.00 | 0.00 | 0.00 |
| October | 57.65 | 30.03 | 27.62 | 71.54 | 74.03 | 0.00 | 0.00 | 0.00 |
| November | 45.87 | 20.72 | 25.15 | 42.59 | 93.91 | 0.00 | 0.00 | 0.00 |
| December | 39.88 | 18.19 | 21.69 | 29.37 | 109.25 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.35 | 30.04 | 37.30 | 94.80 | 64.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.88 | 18.19 | 21.69 | 29.37 | 21.93 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 92.05 | 38.60 | 53.45 | 161.08 | 118.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.63 | 19.47 | 23.16 | 31.18 | 126.55 | 0.00 | 0.00 | 0.00 |
| February | 53.05 | 28.44 | 24.61 | 54.56 | 100.99 | 0.00 | 0.00 | 0.00 |
| March | 67.11 | 30.56 | 36.54 | 81.35 | 63.26 | 0.00 | 0.00 | 0.00 |
| April | 81.05 | 36.99 | 44.05 | 117.46 | 51.69 | 0.00 | 0.00 | 0.00 |
| May | 89.01 | 37.69 | 51.32 | 141.89 | 34.09 | 0.00 | 0.00 | 0.00 |
| June | 92.05 | 38.60 | 53.45 | 167.54 | 20.11 | 0.00 | 0.00 | 0.00 |
| July | 89.76 | 37.75 | 52.02 | 169.68 | 13.59 | 0.00 | 0.00 | 0.00 |
| August | 82.04 | 32.48 | 49.56 | 157.40 | 10.57 | 0.00 | 0.00 | 0.00 |
| September | 67.21 | 29.64 | 37.58 | 109.59 | 30.25 | 0.00 | 0.00 | 0.00 |
| October | 57.65 | 30.03 | 27.62 | 73.81 | 67.35 | 0.00 | 0.00 | 0.00 |
| November | 45.87 | 20.72 | 25.15 | 44.39 | 88.36 | 0.00 | 0.00 | 0.00 |
| December | 39.88 | 18.19 | 21.69 | 30.62 | 104.50 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.35 | 30.04 | 37.30 | 98.52 | 59.06 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.88 | 18.19 | 21.69 | 30.62 | 10.57 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 92.05 | 38.60 | 53.45 | 169.68 | 126.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.20 | 0.00 | 29.20 | 4.42 | 216.68 | 0.00 | 0.00 | 0.00 |
| February | 32.37 | 0.00 | 32.37 | 14.82 | 172.62 | 0.00 | 0.00 | 0.00 |
| March | 45.46 | 0.00 | 45.46 | 33.62 | 106.86 | 0.00 | 0.00 | 0.00 |
| April | 55.04 | 0.29 | 54.75 | 62.96 | 84.79 | 0.00 | 0.00 | 0.00 |
| May | 65.74 | 2.05 | 63.69 | 94.66 | 53.31 | 0.00 | 0.00 | 0.00 |
| June | 72.10 | 4.53 | 67.57 | 135.94 | 30.82 | 0.00 | 0.00 | 0.00 |
| July | 68.28 | 3.33 | 64.96 | 137.65 | 20.78 | 0.00 | 0.00 | 0.00 |
| August | 60.86 | 0.77 | 60.09 | 125.13 | 16.50 | 0.00 | 0.00 | 0.00 |
| September | 45.92 | 0.02 | 45.90 | 68.35 | 48.51 | 0.00 | 0.00 | 0.00 |
| October | 34.89 | 0.00 | 34.89 | 27.20 | 112.96 | 0.00 | 0.00 | 0.00 |
| November | 31.23 | 0.00 | 31.23 | 12.91 | 151.44 | 0.00 | 0.00 | 0.00 |
| December | 27.00 | 0.00 | 27.00 | 4.28 | 179.93 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.42 | 0.92 | 46.50 | 60.43 | 99.23 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 0.00 | 27.00 | 4.28 | 16.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.10 | 4.53 | 67.57 | 137.65 | 216.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.20 | 0.00 | 29.20 | 4.22 | 221.65 | 0.00 | 0.00 | 0.00 |
| February | 32.37 | 0.00 | 32.37 | 14.30 | 177.71 | 0.00 | 0.00 | 0.00 |
| March | 45.46 | 0.00 | 45.46 | 31.94 | 113.77 | 0.00 | 0.00 | 0.00 |
| April | 55.04 | 0.29 | 54.75 | 62.28 | 88.21 | 0.00 | 0.00 | 0.00 |
| May | 65.74 | 2.05 | 63.69 | 95.28 | 54.06 | 0.00 | 0.00 | 0.00 |
| June | 72.10 | 4.53 | 67.57 | 137.56 | 30.64 | 0.00 | 0.00 | 0.00 |
| July | 68.28 | 3.33 | 64.96 | 139.43 | 20.50 | 0.00 | 0.00 | 0.00 |
| August | 60.86 | 0.77 | 60.09 | 126.95 | 16.05 | 0.00 | 0.00 | 0.00 |
| September | 45.92 | 0.02 | 45.90 | 69.53 | 48.34 | 0.00 | 0.00 | 0.00 |
| October | 34.89 | 0.00 | 34.89 | 27.67 | 114.43 | 0.00 | 0.00 | 0.00 |
| November | 31.23 | 0.00 | 31.23 | 12.31 | 157.11 | 0.00 | 0.00 | 0.00 |
| December | 27.00 | 0.00 | 27.00 | 3.79 | 187.93 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.42 | 0.92 | 46.50 | 60.71 | 102.15 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 0.00 | 27.00 | 3.79 | 16.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.10 | 4.53 | 67.57 | 139.43 | 221.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.20 | 0.00 | 29.20 | 4.22 | 221.65 | 0.00 | 0.00 | 0.00 |
| February | 32.37 | 0.00 | 32.37 | 14.28 | 177.75 | 0.00 | 0.00 | 0.00 |
| March | 45.46 | 0.00 | 45.46 | 31.92 | 113.75 | 0.00 | 0.00 | 0.00 |
| April | 55.04 | 0.29 | 54.75 | 62.25 | 88.19 | 0.00 | 0.00 | 0.00 |
| May | 65.74 | 2.05 | 63.69 | 95.24 | 54.06 | 0.00 | 0.00 | 0.00 |
| June | 72.10 | 4.53 | 67.57 | 137.52 | 30.65 | 0.00 | 0.00 | 0.00 |
| July | 68.28 | 3.33 | 64.96 | 139.41 | 20.50 | 0.00 | 0.00 | 0.00 |
| August | 60.86 | 0.77 | 60.09 | 126.94 | 16.04 | 0.00 | 0.00 | 0.00 |
| September | 45.92 | 0.02 | 45.90 | 69.51 | 48.34 | 0.00 | 0.00 | 0.00 |
| October | 34.89 | 0.00 | 34.89 | 27.64 | 114.42 | 0.00 | 0.00 | 0.00 |
| November | 31.23 | 0.00 | 31.23 | 12.29 | 157.13 | 0.00 | 0.00 | 0.00 |
| December | 27.00 | 0.00 | 27.00 | 3.79 | 187.95 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.42 | 0.92 | 46.50 | 60.69 | 102.15 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 0.00 | 27.00 | 3.79 | 16.04 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.10 | 4.53 | 67.57 | 139.41 | 221.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.87 | 106.53 | 47.34 | 178.07 | 188.42 | 0.00 | 0.00 | 0.00 |
| February | 146.91 | 98.84 | 48.07 | 186.91 | 159.97 | 0.00 | 0.00 | 0.00 |
| March | 130.59 | 67.81 | 62.77 | 178.32 | 113.72 | 0.00 | 0.00 | 0.00 |
| April | 101.14 | 34.91 | 66.23 | 155.24 | 91.03 | 0.00 | 0.00 | 0.00 |
| May | 79.90 | 9.79 | 70.12 | 130.67 | 57.73 | 0.00 | 0.00 | 0.00 |
| June | 73.71 | 4.44 | 69.27 | 145.39 | 33.25 | 0.00 | 0.00 | 0.00 |
| July | 73.97 | 5.34 | 68.63 | 154.54 | 21.75 | 0.00 | 0.00 | 0.00 |
| August | 88.04 | 16.04 | 72.00 | 185.89 | 17.03 | 0.00 | 0.00 | 0.00 |
| September | 101.08 | 39.92 | 61.16 | 176.87 | 48.78 | 0.00 | 0.00 | 0.00 |
| October | 139.89 | 90.18 | 49.71 | 208.84 | 107.65 | 0.00 | 0.00 | 0.00 |
| November | 153.17 | 102.10 | 51.07 | 203.31 | 142.26 | 0.00 | 0.00 | 0.00 |
| December | 153.46 | 107.81 | 45.65 | 185.33 | 171.96 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.16 | 56.76 | 59.40 | 174.05 | 95.79 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.71 | 4.44 | 45.65 | 130.67 | 17.03 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 153.87 | 107.81 | 72.00 | 208.84 | 188.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.87 | 106.53 | 47.34 | 178.77 | 186.44 | 0.00 | 0.00 | 0.00 |
| February | 146.91 | 98.84 | 48.07 | 187.28 | 158.91 | 0.00 | 0.00 | 0.00 |
| March | 130.59 | 67.81 | 62.77 | 178.36 | 113.51 | 0.00 | 0.00 | 0.00 |
| April | 101.14 | 34.91 | 66.23 | 155.07 | 91.17 | 0.00 | 0.00 | 0.00 |
| May | 79.90 | 9.79 | 70.12 | 130.30 | 58.10 | 0.00 | 0.00 | 0.00 |
| June | 73.71 | 4.44 | 69.27 | 144.75 | 33.81 | 0.00 | 0.00 | 0.00 |
| July | 73.97 | 5.34 | 68.63 | 153.70 | 22.41 | 0.00 | 0.00 | 0.00 |
| August | 88.04 | 16.04 | 72.00 | 185.12 | 17.71 | 0.00 | 0.00 | 0.00 |
| September | 101.08 | 39.92 | 61.16 | 176.34 | 49.47 | 0.00 | 0.00 | 0.00 |
| October | 139.89 | 90.18 | 49.71 | 208.65 | 107.88 | 0.00 | 0.00 | 0.00 |
| November | 153.17 | 102.10 | 51.07 | 203.39 | 142.06 | 0.00 | 0.00 | 0.00 |
| December | 153.46 | 107.81 | 45.65 | 185.70 | 170.86 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.16 | 56.76 | 59.40 | 173.89 | 95.70 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.71 | 4.44 | 45.65 | 130.30 | 17.71 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 153.87 | 107.81 | 72.00 | 208.65 | 186.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.87 | 106.53 | 47.34 | 175.73 | 191.09 | 0.00 | 0.00 | 0.00 |
| February | 146.91 | 98.84 | 48.07 | 183.55 | 165.31 | 0.00 | 0.00 | 0.00 |
| March | 130.59 | 67.81 | 62.77 | 173.83 | 118.52 | 0.00 | 0.00 | 0.00 |
| April | 101.14 | 34.91 | 66.23 | 150.93 | 95.56 | 0.00 | 0.00 | 0.00 |
| May | 79.90 | 9.79 | 70.12 | 127.13 | 60.56 | 0.00 | 0.00 | 0.00 |
| June | 73.71 | 4.44 | 69.27 | 143.43 | 33.98 | 0.00 | 0.00 | 0.00 |
| July | 73.97 | 5.34 | 68.63 | 153.02 | 21.93 | 0.00 | 0.00 | 0.00 |
| August | 88.04 | 16.04 | 72.00 | 184.77 | 16.71 | 0.00 | 0.00 | 0.00 |
| September | 101.08 | 39.92 | 61.16 | 176.53 | 47.80 | 0.00 | 0.00 | 0.00 |
| October | 139.89 | 90.18 | 49.71 | 208.29 | 106.21 | 0.00 | 0.00 | 0.00 |
| November | 153.17 | 102.10 | 51.07 | 203.36 | 139.49 | 0.00 | 0.00 | 0.00 |
| December | 153.46 | 107.81 | 45.65 | 186.56 | 165.73 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.16 | 56.76 | 59.40 | 172.21 | 96.54 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.71 | 4.44 | 45.65 | 127.13 | 16.71 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 153.87 | 107.81 | 72.00 | 208.29 | 191.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.68 | 20.37 | 23.32 | 32.36 | 143.17 | 0.00 | 0.00 | 0.00 |
| February | 49.81 | 23.29 | 26.52 | 48.87 | 120.76 | 0.00 | 0.00 | 0.00 |
| March | 73.25 | 35.34 | 37.91 | 88.32 | 81.03 | 0.00 | 0.00 | 0.00 |
| April | 82.37 | 37.62 | 44.75 | 117.10 | 61.93 | 0.00 | 0.00 | 0.00 |
| May | 83.00 | 31.48 | 51.52 | 131.79 | 39.10 | 0.00 | 0.00 | 0.00 |
| June | 87.39 | 33.75 | 53.64 | 160.10 | 22.07 | 0.00 | 0.00 | 0.00 |
| July | 82.18 | 30.44 | 51.73 | 157.27 | 14.21 | 0.00 | 0.00 | 0.00 |
| August | 80.53 | 30.09 | 50.45 | 155.38 | 10.96 | 0.00 | 0.00 | 0.00 |
| September | 65.85 | 27.51 | 38.34 | 108.04 | 31.49 | 0.00 | 0.00 | 0.00 |
| October | 58.30 | 30.18 | 28.12 | 77.58 | 74.33 | 0.00 | 0.00 | 0.00 |
| November | 46.43 | 20.70 | 25.73 | 48.37 | 102.01 | 0.00 | 0.00 | 0.00 |
| December | 38.61 | 16.94 | 21.67 | 30.47 | 124.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.03 | 28.16 | 37.87 | 96.56 | 68.51 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38.61 | 16.94 | 21.67 | 30.47 | 10.96 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.39 | 37.62 | 53.64 | 160.10 | 143.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.68 | 20.37 | 23.32 | 35.07 | 136.57 | 0.00 | 0.00 | 0.00 |
| February | 49.81 | 23.29 | 26.52 | 51.53 | 115.51 | 0.00 | 0.00 | 0.00 |
| March | 73.25 | 35.34 | 37.91 | 90.75 | 78.29 | 0.00 | 0.00 | 0.00 |
| April | 82.37 | 37.62 | 44.75 | 118.33 | 61.18 | 0.00 | 0.00 | 0.00 |
| May | 83.00 | 31.48 | 51.52 | 132.14 | 38.96 | 0.00 | 0.00 | 0.00 |
| June | 87.39 | 33.75 | 53.64 | 160.22 | 22.09 | 0.00 | 0.00 | 0.00 |
| July | 82.18 | 30.44 | 51.73 | 157.44 | 14.20 | 0.00 | 0.00 | 0.00 |
| August | 80.53 | 30.09 | 50.45 | 155.85 | 10.81 | 0.00 | 0.00 | 0.00 |
| September | 65.85 | 27.51 | 38.34 | 108.94 | 30.94 | 0.00 | 0.00 | 0.00 |
| October | 58.30 | 30.18 | 28.12 | 79.62 | 72.27 | 0.00 | 0.00 | 0.00 |
| November | 46.43 | 20.70 | 25.73 | 51.81 | 95.50 | 0.00 | 0.00 | 0.00 |
| December | 38.61 | 16.94 | 21.67 | 33.77 | 114.50 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.03 | 28.16 | 37.87 | 98.21 | 65.64 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38.61 | 16.94 | 21.67 | 33.77 | 10.81 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.39 | 37.62 | 53.64 | 160.22 | 136.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.20 | 0.00 | 29.20 | 3.83 | 225.82 | 0.00 | 0.00 | 0.00 |
| February | 32.37 | 0.00 | 32.37 | 12.19 | 186.84 | 0.00 | 0.00 | 0.00 |
| March | 45.46 | 0.00 | 45.46 | 27.13 | 124.39 | 0.00 | 0.00 | 0.00 |
| April | 55.04 | 0.29 | 54.75 | 57.72 | 94.11 | 0.00 | 0.00 | 0.00 |
| May | 65.74 | 2.05 | 63.69 | 91.42 | 56.96 | 0.00 | 0.00 | 0.00 |
| June | 72.10 | 4.53 | 67.57 | 135.52 | 31.36 | 0.00 | 0.00 | 0.00 |
| July | 68.28 | 3.33 | 64.96 | 137.93 | 20.75 | 0.00 | 0.00 | 0.00 |
| August | 60.86 | 0.77 | 60.09 | 125.95 | 15.88 | 0.00 | 0.00 | 0.00 |
| September | 45.92 | 0.02 | 45.90 | 69.45 | 47.66 | 0.00 | 0.00 | 0.00 |
| October | 34.89 | 0.00 | 34.89 | 27.86 | 112.96 | 0.00 | 0.00 | 0.00 |
| November | 31.23 | 0.00 | 31.23 | 13.24 | 151.25 | 0.00 | 0.00 | 0.00 |
| December | 27.00 | 0.00 | 27.00 | 3.82 | 184.41 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.42 | 0.92 | 46.50 | 59.11 | 103.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 0.00 | 27.00 | 3.82 | 15.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.10 | 4.53 | 67.57 | 137.93 | 225.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.87 | 106.53 | 47.34 | 175.21 | 190.69 | 0.00 | 0.00 | 0.00 |
| February | 146.91 | 98.84 | 48.07 | 182.93 | 164.98 | 0.00 | 0.00 | 0.00 |
| March | 130.59 | 67.81 | 62.77 | 173.49 | 117.71 | 0.00 | 0.00 | 0.00 |
| April | 101.14 | 34.91 | 66.23 | 150.06 | 95.08 | 0.00 | 0.00 | 0.00 |
| May | 79.90 | 9.79 | 70.12 | 126.21 | 60.38 | 0.00 | 0.00 | 0.00 |
| June | 73.71 | 4.44 | 69.27 | 142.66 | 33.87 | 0.00 | 0.00 | 0.00 |
| July | 73.97 | 5.34 | 68.63 | 152.53 | 21.84 | 0.00 | 0.00 | 0.00 |
| August | 88.04 | 16.04 | 72.00 | 184.51 | 16.55 | 0.00 | 0.00 | 0.00 |
| September | 101.08 | 39.92 | 61.16 | 175.97 | 47.62 | 0.00 | 0.00 | 0.00 |
| October | 139.89 | 90.18 | 49.71 | 207.70 | 105.89 | 0.00 | 0.00 | 0.00 |
| November | 153.17 | 102.10 | 51.07 | 202.97 | 139.14 | 0.00 | 0.00 | 0.00 |
| December | 153.46 | 107.81 | 45.65 | 185.93 | 165.62 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.16 | 56.76 | 59.40 | 171.63 | 96.25 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.71 | 4.44 | 45.65 | 126.21 | 16.55 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 153.87 | 107.81 | 72.00 | 207.70 | 190.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.63 | 19.47 | 23.16 | 28.30 | 139.57 | 0.00 | 0.00 | 0.00 |
| February | 53.05 | 28.44 | 24.61 | 49.16 | 115.00 | 0.00 | 0.00 | 0.00 |
| March | 67.11 | 30.56 | 36.54 | 72.83 | 75.66 | 0.00 | 0.00 | 0.00 |
| April | 81.05 | 36.99 | 44.05 | 111.38 | 57.69 | 0.00 | 0.00 | 0.00 |
| May | 89.01 | 37.69 | 51.32 | 138.36 | 36.45 | 0.00 | 0.00 | 0.00 |
| June | 92.05 | 38.60 | 53.45 | 166.33 | 20.38 | 0.00 | 0.00 | 0.00 |
| July | 89.76 | 37.75 | 52.02 | 169.07 | 13.54 | 0.00 | 0.00 | 0.00 |
| August | 82.04 | 32.48 | 49.56 | 157.01 | 10.22 | 0.00 | 0.00 | 0.00 |
| September | 67.21 | 29.64 | 37.58 | 108.84 | 30.21 | 0.00 | 0.00 | 0.00 |
| October | 57.65 | 30.03 | 27.62 | 71.68 | 69.32 | 0.00 | 0.00 | 0.00 |
| November | 45.87 | 20.72 | 25.15 | 41.05 | 94.71 | 0.00 | 0.00 | 0.00 |
| December | 39.88 | 18.19 | 21.69 | 27.01 | 117.65 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.35 | 30.04 | 37.30 | 95.33 | 64.78 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.88 | 18.19 | 21.69 | 27.01 | 10.22 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 92.05 | 38.60 | 53.45 | 169.07 | 139.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.63 | 19.47 | 23.16 | 29.92 | 131.78 | 0.00 | 0.00 | 0.00 |
| February | 53.05 | 28.44 | 24.61 | 51.22 | 109.31 | 0.00 | 0.00 | 0.00 |
| March | 67.11 | 30.56 | 36.54 | 75.03 | 72.90 | 0.00 | 0.00 | 0.00 |
| April | 81.05 | 36.99 | 44.05 | 112.50 | 56.91 | 0.00 | 0.00 | 0.00 |
| May | 89.01 | 37.69 | 51.32 | 138.67 | 36.31 | 0.00 | 0.00 | 0.00 |
| June | 92.05 | 38.60 | 53.45 | 166.46 | 20.39 | 0.00 | 0.00 | 0.00 |
| July | 89.76 | 37.75 | 52.02 | 169.27 | 13.51 | 0.00 | 0.00 | 0.00 |
| August | 82.04 | 32.48 | 49.56 | 157.49 | 10.07 | 0.00 | 0.00 | 0.00 |
| September | 67.21 | 29.64 | 37.58 | 109.70 | 29.68 | 0.00 | 0.00 | 0.00 |
| October | 57.65 | 30.03 | 27.62 | 73.69 | 67.06 | 0.00 | 0.00 | 0.00 |
| November | 45.87 | 20.72 | 25.15 | 44.28 | 88.20 | 0.00 | 0.00 | 0.00 |
| December | 39.88 | 18.19 | 21.69 | 29.73 | 107.09 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.35 | 30.04 | 37.30 | 96.74 | 61.69 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.88 | 18.19 | 21.69 | 29.73 | 10.07 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 92.05 | 38.60 | 53.45 | 169.27 | 131.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.20 | 0.00 | 29.20 | 3.74 | 225.69 | 0.00 | 0.00 | 0.00 |
| February | 32.37 | 0.00 | 32.37 | 11.84 | 186.95 | 0.00 | 0.00 | 0.00 |
| March | 45.46 | 0.00 | 45.46 | 26.73 | 123.77 | 0.00 | 0.00 | 0.00 |
| April | 55.04 | 0.29 | 54.75 | 56.89 | 93.72 | 0.00 | 0.00 | 0.00 |
| May | 65.74 | 2.05 | 63.69 | 90.46 | 56.79 | 0.00 | 0.00 | 0.00 |
| June | 72.10 | 4.53 | 67.57 | 134.73 | 31.22 | 0.00 | 0.00 | 0.00 |
| July | 68.28 | 3.33 | 64.96 | 137.43 | 20.62 | 0.00 | 0.00 | 0.00 |
| August | 60.86 | 0.77 | 60.09 | 125.65 | 15.71 | 0.00 | 0.00 | 0.00 |
| September | 45.92 | 0.02 | 45.90 | 68.83 | 47.53 | 0.00 | 0.00 | 0.00 |
| October | 34.89 | 0.00 | 34.89 | 27.37 | 112.43 | 0.00 | 0.00 | 0.00 |
| November | 31.23 | 0.00 | 31.23 | 12.95 | 151.11 | 0.00 | 0.00 | 0.00 |
| December | 27.00 | 0.00 | 27.00 | 3.72 | 184.39 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.42 | 0.92 | 46.50 | 58.63 | 103.74 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 0.00 | 27.00 | 3.72 | 15.71 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.10 | 4.53 | 67.57 | 137.43 | 225.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.20 | 0.00 | 29.20 | 3.52 | 232.32 | 0.00 | 0.00 | 0.00 |
| February | 32.37 | 0.00 | 32.37 | 11.63 | 192.05 | 0.00 | 0.00 | 0.00 |
| March | 45.46 | 0.00 | 45.46 | 26.70 | 126.89 | 0.00 | 0.00 | 0.00 |
| April | 55.04 | 0.29 | 54.75 | 58.11 | 94.22 | 0.00 | 0.00 | 0.00 |
| May | 65.74 | 2.05 | 63.69 | 92.40 | 56.54 | 0.00 | 0.00 | 0.00 |
| June | 72.10 | 4.53 | 67.57 | 136.99 | 30.75 | 0.00 | 0.00 | 0.00 |
| July | 68.28 | 3.33 | 64.96 | 139.58 | 20.22 | 0.00 | 0.00 | 0.00 |
| August | 60.86 | 0.77 | 60.09 | 127.64 | 15.27 | 0.00 | 0.00 | 0.00 |
| September | 45.92 | 0.02 | 45.90 | 70.14 | 47.44 | 0.00 | 0.00 | 0.00 |
| October | 34.89 | 0.00 | 34.89 | 27.84 | 114.54 | 0.00 | 0.00 | 0.00 |
| November | 31.23 | 0.00 | 31.23 | 12.20 | 157.89 | 0.00 | 0.00 | 0.00 |
| December | 27.00 | 0.00 | 27.00 | 3.21 | 193.93 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.42 | 0.92 | 46.50 | 59.44 | 106.40 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 0.00 | 27.00 | 3.21 | 15.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.10 | 4.53 | 67.57 | 139.58 | 232.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.20 | 0.00 | 29.20 | 3.52 | 232.32 | 0.00 | 0.00 | 0.00 |
| February | 32.37 | 0.00 | 32.37 | 11.61 | 192.07 | 0.00 | 0.00 | 0.00 |
| March | 45.46 | 0.00 | 45.46 | 26.68 | 126.85 | 0.00 | 0.00 | 0.00 |
| April | 55.04 | 0.29 | 54.75 | 58.06 | 94.21 | 0.00 | 0.00 | 0.00 |
| May | 65.74 | 2.05 | 63.69 | 92.35 | 56.54 | 0.00 | 0.00 | 0.00 |
| June | 72.10 | 4.53 | 67.57 | 136.95 | 30.76 | 0.00 | 0.00 | 0.00 |
| July | 68.28 | 3.33 | 64.96 | 139.56 | 20.22 | 0.00 | 0.00 | 0.00 |
| August | 60.86 | 0.77 | 60.09 | 127.63 | 15.27 | 0.00 | 0.00 | 0.00 |
| September | 45.92 | 0.02 | 45.90 | 70.11 | 47.45 | 0.00 | 0.00 | 0.00 |
| October | 34.89 | 0.00 | 34.89 | 27.81 | 114.52 | 0.00 | 0.00 | 0.00 |
| November | 31.23 | 0.00 | 31.23 | 12.19 | 157.90 | 0.00 | 0.00 | 0.00 |
| December | 27.00 | 0.00 | 27.00 | 3.20 | 193.95 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.42 | 0.92 | 46.50 | 59.42 | 106.40 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 0.00 | 27.00 | 3.20 | 15.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.10 | 4.53 | 67.57 | 139.56 | 232.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.87 | 106.53 | 47.34 | 171.91 | 201.51 | 0.00 | 0.00 | 0.00 |
| February | 146.91 | 98.84 | 48.07 | 180.98 | 173.06 | 0.00 | 0.00 | 0.00 |
| March | 130.59 | 67.81 | 62.77 | 173.43 | 119.97 | 0.00 | 0.00 | 0.00 |
| April | 101.14 | 34.91 | 66.23 | 151.20 | 95.60 | 0.00 | 0.00 | 0.00 |
| May | 79.90 | 9.79 | 70.12 | 128.00 | 60.11 | 0.00 | 0.00 | 0.00 |
| June | 73.71 | 4.44 | 69.27 | 144.86 | 33.36 | 0.00 | 0.00 | 0.00 |
| July | 73.97 | 5.34 | 68.63 | 154.66 | 21.41 | 0.00 | 0.00 | 0.00 |
| August | 88.04 | 16.04 | 72.00 | 186.40 | 16.11 | 0.00 | 0.00 | 0.00 |
| September | 101.08 | 39.92 | 61.16 | 177.10 | 47.64 | 0.00 | 0.00 | 0.00 |
| October | 139.89 | 90.18 | 49.71 | 208.01 | 107.48 | 0.00 | 0.00 | 0.00 |
| November | 153.17 | 102.10 | 51.07 | 202.00 | 142.77 | 0.00 | 0.00 | 0.00 |
| December | 153.46 | 107.81 | 45.65 | 182.98 | 175.36 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.16 | 56.76 | 59.40 | 171.75 | 99.14 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.71 | 4.44 | 45.65 | 128.00 | 16.11 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 153.87 | 107.81 | 72.00 | 208.01 | 201.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.87 | 106.53 | 47.34 | 171.89 | 201.49 | 0.00 | 0.00 | 0.00 |
| February | 146.91 | 98.84 | 48.07 | 180.95 | 173.06 | 0.00 | 0.00 | 0.00 |
| March | 130.59 | 67.81 | 62.77 | 173.42 | 119.92 | 0.00 | 0.00 | 0.00 |
| April | 101.14 | 34.91 | 66.23 | 151.16 | 95.59 | 0.00 | 0.00 | 0.00 |
| May | 79.90 | 9.79 | 70.12 | 127.95 | 60.11 | 0.00 | 0.00 | 0.00 |
| June | 73.71 | 4.44 | 69.27 | 144.83 | 33.36 | 0.00 | 0.00 | 0.00 |
| July | 73.97 | 5.34 | 68.63 | 154.64 | 21.40 | 0.00 | 0.00 | 0.00 |
| August | 88.04 | 16.04 | 72.00 | 186.39 | 16.11 | 0.00 | 0.00 | 0.00 |
| September | 101.08 | 39.92 | 61.16 | 177.08 | 47.64 | 0.00 | 0.00 | 0.00 |
| October | 139.89 | 90.18 | 49.71 | 207.98 | 107.47 | 0.00 | 0.00 | 0.00 |
| November | 153.17 | 102.10 | 51.07 | 201.98 | 142.76 | 0.00 | 0.00 | 0.00 |
| December | 153.46 | 107.81 | 45.65 | 182.95 | 175.37 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.16 | 56.76 | 59.40 | 171.73 | 99.14 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.71 | 4.44 | 45.65 | 127.95 | 16.11 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 153.87 | 107.81 | 72.00 | 207.98 | 201.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.87 | 106.53 | 47.34 | 177.55 | 179.99 | 0.00 | 0.00 | 0.00 |
| February | 146.91 | 98.84 | 48.07 | 185.45 | 153.88 | 0.00 | 0.00 | 0.00 |
| March | 130.59 | 67.81 | 62.77 | 176.98 | 106.65 | 0.00 | 0.00 | 0.00 |
| April | 101.14 | 34.91 | 66.23 | 150.91 | 90.19 | 0.00 | 0.00 | 0.00 |
| May | 79.90 | 9.79 | 70.12 | 125.26 | 58.48 | 0.00 | 0.00 | 0.00 |
| June | 73.71 | 4.44 | 69.27 | 140.31 | 33.07 | 0.00 | 0.00 | 0.00 |
| July | 73.97 | 5.34 | 68.63 | 149.45 | 21.29 | 0.00 | 0.00 | 0.00 |
| August | 88.04 | 16.04 | 72.00 | 180.91 | 16.15 | 0.00 | 0.00 | 0.00 |
| September | 101.08 | 39.92 | 61.16 | 174.92 | 45.59 | 0.00 | 0.00 | 0.00 |
| October | 139.89 | 90.18 | 49.71 | 209.41 | 96.23 | 0.00 | 0.00 | 0.00 |
| November | 153.17 | 102.10 | 51.07 | 208.17 | 124.03 | 0.00 | 0.00 | 0.00 |
| December | 153.46 | 107.81 | 45.65 | 190.31 | 150.46 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.16 | 56.76 | 59.40 | 172.41 | 89.32 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.71 | 4.44 | 45.65 | 125.26 | 16.15 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 153.87 | 107.81 | 72.00 | 209.41 | 179.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.68 | 20.37 | 23.32 | 32.48 | 134.75 | 0.00 | 0.00 | 0.00 |
| February | 49.81 | 23.29 | 26.52 | 48.91 | 111.92 | 0.00 | 0.00 | 0.00 |
| March | 73.25 | 35.34 | 37.91 | 89.05 | 71.82 | 0.00 | 0.00 | 0.00 |
| April | 82.37 | 37.62 | 44.75 | 116.52 | 57.85 | 0.00 | 0.00 | 0.00 |
| May | 83.00 | 31.48 | 51.52 | 130.31 | 37.54 | 0.00 | 0.00 | 0.00 |
| June | 87.39 | 33.75 | 53.64 | 157.72 | 21.37 | 0.00 | 0.00 | 0.00 |
| July | 82.18 | 30.44 | 51.73 | 154.79 | 13.75 | 0.00 | 0.00 | 0.00 |
| August | 80.53 | 30.09 | 50.45 | 152.77 | 10.57 | 0.00 | 0.00 | 0.00 |
| September | 65.85 | 27.51 | 38.34 | 106.78 | 29.86 | 0.00 | 0.00 | 0.00 |
| October | 58.30 | 30.18 | 28.12 | 77.22 | 66.58 | 0.00 | 0.00 | 0.00 |
| November | 46.43 | 20.70 | 25.73 | 49.51 | 89.60 | 0.00 | 0.00 | 0.00 |
| December | 38.61 | 16.94 | 21.67 | 31.02 | 112.14 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.03 | 28.16 | 37.87 | 95.84 | 62.89 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38.61 | 16.94 | 21.67 | 31.02 | 10.57 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.39 | 37.62 | 53.64 | 157.72 | 134.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.68 | 20.37 | 23.32 | 35.49 | 131.03 | 0.00 | 0.00 | 0.00 |
| February | 49.81 | 23.29 | 26.52 | 52.66 | 108.16 | 0.00 | 0.00 | 0.00 |
| March | 73.25 | 35.34 | 37.91 | 93.43 | 68.50 | 0.00 | 0.00 | 0.00 |
| April | 82.37 | 37.62 | 44.75 | 118.60 | 56.98 | 0.00 | 0.00 | 0.00 |
| May | 83.00 | 31.48 | 51.52 | 130.77 | 37.46 | 0.00 | 0.00 | 0.00 |
| June | 87.39 | 33.75 | 53.64 | 157.85 | 21.44 | 0.00 | 0.00 | 0.00 |
| July | 82.18 | 30.44 | 51.73 | 155.00 | 13.77 | 0.00 | 0.00 | 0.00 |
| August | 80.53 | 30.09 | 50.45 | 153.39 | 10.47 | 0.00 | 0.00 | 0.00 |
| September | 65.85 | 27.51 | 38.34 | 108.09 | 29.38 | 0.00 | 0.00 | 0.00 |
| October | 58.30 | 30.18 | 28.12 | 81.23 | 63.41 | 0.00 | 0.00 | 0.00 |
| November | 46.43 | 20.70 | 25.73 | 54.70 | 83.93 | 0.00 | 0.00 | 0.00 |
| December | 38.61 | 16.94 | 21.67 | 34.74 | 107.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.03 | 28.16 | 37.87 | 98.24 | 60.73 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38.61 | 16.94 | 21.67 | 34.74 | 10.47 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.39 | 37.62 | 53.64 | 157.85 | 131.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.20 | 0.00 | 29.20 | 4.11 | 217.16 | 0.00 | 0.00 | 0.00 |
| February | 32.37 | 0.00 | 32.37 | 13.74 | 175.55 | 0.00 | 0.00 | 0.00 |
| March | 45.46 | 0.00 | 45.46 | 30.97 | 109.10 | 0.00 | 0.00 | 0.00 |
| April | 55.04 | 0.29 | 54.75 | 58.63 | 88.02 | 0.00 | 0.00 | 0.00 |
| May | 65.74 | 2.05 | 63.69 | 89.90 | 55.09 | 0.00 | 0.00 | 0.00 |
| June | 72.10 | 4.53 | 67.57 | 132.59 | 30.72 | 0.00 | 0.00 | 0.00 |
| July | 68.28 | 3.33 | 64.96 | 134.60 | 20.31 | 0.00 | 0.00 | 0.00 |
| August | 60.86 | 0.77 | 60.09 | 122.47 | 15.46 | 0.00 | 0.00 | 0.00 |
| September | 45.92 | 0.02 | 45.90 | 68.42 | 45.42 | 0.00 | 0.00 | 0.00 |
| October | 34.89 | 0.00 | 34.89 | 30.32 | 99.34 | 0.00 | 0.00 | 0.00 |
| November | 31.23 | 0.00 | 31.23 | 16.94 | 132.90 | 0.00 | 0.00 | 0.00 |
| December | 27.00 | 0.00 | 27.00 | 4.69 | 172.60 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.42 | 0.92 | 46.50 | 59.21 | 96.40 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 0.00 | 27.00 | 4.11 | 15.46 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.10 | 4.53 | 67.57 | 134.60 | 217.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.87 | 106.53 | 47.34 | 176.85 | 179.29 | 0.00 | 0.00 | 0.00 |
| February | 146.91 | 98.84 | 48.07 | 184.25 | 153.17 | 0.00 | 0.00 | 0.00 |
| March | 130.59 | 67.81 | 62.77 | 175.55 | 105.16 | 0.00 | 0.00 | 0.00 |
| April | 101.14 | 34.91 | 66.23 | 148.94 | 89.15 | 0.00 | 0.00 | 0.00 |
| May | 79.90 | 9.79 | 70.12 | 123.56 | 58.00 | 0.00 | 0.00 | 0.00 |
| June | 73.71 | 4.44 | 69.27 | 139.02 | 32.79 | 0.00 | 0.00 | 0.00 |
| July | 73.97 | 5.34 | 68.63 | 148.72 | 21.08 | 0.00 | 0.00 | 0.00 |
| August | 88.04 | 16.04 | 72.00 | 180.50 | 15.91 | 0.00 | 0.00 | 0.00 |
| September | 101.08 | 39.92 | 61.16 | 173.95 | 45.17 | 0.00 | 0.00 | 0.00 |
| October | 139.89 | 90.18 | 49.71 | 207.94 | 95.52 | 0.00 | 0.00 | 0.00 |
| November | 153.17 | 102.10 | 51.07 | 207.12 | 123.28 | 0.00 | 0.00 | 0.00 |
| December | 153.46 | 107.81 | 45.65 | 189.45 | 149.89 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.16 | 56.76 | 59.40 | 171.26 | 88.69 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.71 | 4.44 | 45.65 | 123.56 | 15.91 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 153.87 | 107.81 | 72.00 | 207.94 | 179.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.63 | 19.47 | 23.16 | 29.46 | 131.96 | 0.00 | 0.00 | 0.00 |
| February | 53.05 | 28.44 | 24.61 | 50.32 | 107.37 | 0.00 | 0.00 | 0.00 |
| March | 67.11 | 30.56 | 36.54 | 75.04 | 68.07 | 0.00 | 0.00 | 0.00 |
| April | 81.05 | 36.99 | 44.05 | 111.48 | 54.57 | 0.00 | 0.00 | 0.00 |
| May | 89.01 | 37.69 | 51.32 | 136.97 | 35.33 | 0.00 | 0.00 | 0.00 |
| June | 92.05 | 38.60 | 53.45 | 164.06 | 19.90 | 0.00 | 0.00 | 0.00 |
| July | 89.76 | 37.75 | 52.02 | 166.57 | 13.16 | 0.00 | 0.00 | 0.00 |
| August | 82.04 | 32.48 | 49.56 | 154.34 | 9.86 | 0.00 | 0.00 | 0.00 |
| September | 67.21 | 29.64 | 37.58 | 107.69 | 28.76 | 0.00 | 0.00 | 0.00 |
| October | 57.65 | 30.03 | 27.62 | 72.33 | 62.84 | 0.00 | 0.00 | 0.00 |
| November | 45.87 | 20.72 | 25.15 | 43.91 | 84.21 | 0.00 | 0.00 | 0.00 |
| December | 39.88 | 18.19 | 21.69 | 29.12 | 106.81 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.35 | 30.04 | 37.30 | 95.35 | 60.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.88 | 18.19 | 21.69 | 29.12 | 9.86 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 92.05 | 38.60 | 53.45 | 166.57 | 131.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.63 | 19.47 | 23.16 | 30.64 | 126.44 | 0.00 | 0.00 | 0.00 |
| February | 53.05 | 28.44 | 24.61 | 53.12 | 102.62 | 0.00 | 0.00 | 0.00 |
| March | 67.11 | 30.56 | 36.54 | 78.78 | 64.03 | 0.00 | 0.00 | 0.00 |
| April | 81.05 | 36.99 | 44.05 | 113.32 | 53.37 | 0.00 | 0.00 | 0.00 |
| May | 89.01 | 37.69 | 51.32 | 137.36 | 35.22 | 0.00 | 0.00 | 0.00 |
| June | 92.05 | 38.60 | 53.45 | 164.19 | 19.94 | 0.00 | 0.00 | 0.00 |
| July | 89.76 | 37.75 | 52.02 | 166.80 | 13.17 | 0.00 | 0.00 | 0.00 |
| August | 82.04 | 32.48 | 49.56 | 154.96 | 9.76 | 0.00 | 0.00 | 0.00 |
| September | 67.21 | 29.64 | 37.58 | 108.89 | 28.25 | 0.00 | 0.00 | 0.00 |
| October | 57.65 | 30.03 | 27.62 | 76.07 | 59.21 | 0.00 | 0.00 | 0.00 |
| November | 45.87 | 20.72 | 25.15 | 48.29 | 77.36 | 0.00 | 0.00 | 0.00 |
| December | 39.88 | 18.19 | 21.69 | 31.27 | 100.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.35 | 30.04 | 37.30 | 97.21 | 57.22 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.88 | 18.19 | 21.69 | 30.64 | 9.76 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 92.05 | 38.60 | 53.45 | 166.80 | 126.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.20 | 0.00 | 29.20 | 3.98 | 216.97 | 0.00 | 0.00 | 0.00 |
| February | 32.37 | 0.00 | 32.37 | 13.08 | 175.12 | 0.00 | 0.00 | 0.00 |
| March | 45.46 | 0.00 | 45.46 | 29.74 | 107.53 | 0.00 | 0.00 | 0.00 |
| April | 55.04 | 0.29 | 54.75 | 56.76 | 86.83 | 0.00 | 0.00 | 0.00 |
| May | 65.74 | 2.05 | 63.69 | 88.14 | 54.63 | 0.00 | 0.00 | 0.00 |
| June | 72.10 | 4.53 | 67.57 | 131.27 | 30.40 | 0.00 | 0.00 | 0.00 |
| July | 68.28 | 3.33 | 64.96 | 133.86 | 20.07 | 0.00 | 0.00 | 0.00 |
| August | 60.86 | 0.77 | 60.09 | 122.01 | 15.21 | 0.00 | 0.00 | 0.00 |
| September | 45.92 | 0.02 | 45.90 | 67.34 | 44.99 | 0.00 | 0.00 | 0.00 |
| October | 34.89 | 0.00 | 34.89 | 28.93 | 98.32 | 0.00 | 0.00 | 0.00 |
| November | 31.23 | 0.00 | 31.23 | 16.37 | 131.79 | 0.00 | 0.00 | 0.00 |
| December | 27.00 | 0.00 | 27.00 | 4.54 | 172.25 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.42 | 0.92 | 46.50 | 58.26 | 95.78 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 0.00 | 27.00 | 3.98 | 15.21 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.10 | 4.53 | 67.57 | 133.86 | 216.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.20 | 0.00 | 29.20 | 3.98 | 220.56 | 0.00 | 0.00 | 0.00 |
| February | 32.37 | 0.00 | 32.37 | 13.51 | 178.96 | 0.00 | 0.00 | 0.00 |
| March | 45.46 | 0.00 | 45.46 | 30.77 | 110.77 | 0.00 | 0.00 | 0.00 |
| April | 55.04 | 0.29 | 54.75 | 58.97 | 88.83 | 0.00 | 0.00 | 0.00 |
| May | 65.74 | 2.05 | 63.69 | 90.95 | 55.26 | 0.00 | 0.00 | 0.00 |
| June | 72.10 | 4.53 | 67.57 | 134.30 | 30.41 | 0.00 | 0.00 | 0.00 |
| July | 68.28 | 3.33 | 64.96 | 136.59 | 20.03 | 0.00 | 0.00 | 0.00 |
| August | 60.86 | 0.77 | 60.09 | 124.56 | 15.10 | 0.00 | 0.00 | 0.00 |
| September | 45.92 | 0.02 | 45.90 | 69.21 | 45.71 | 0.00 | 0.00 | 0.00 |
| October | 34.89 | 0.00 | 34.89 | 30.00 | 101.88 | 0.00 | 0.00 | 0.00 |
| November | 31.23 | 0.00 | 31.23 | 16.54 | 135.68 | 0.00 | 0.00 | 0.00 |
| December | 27.00 | 0.00 | 27.00 | 4.44 | 175.87 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.42 | 0.92 | 46.50 | 59.75 | 97.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 0.00 | 27.00 | 3.98 | 15.10 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.10 | 4.53 | 67.57 | 136.59 | 220.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.20 | 0.00 | 29.20 | 3.97 | 220.55 | 0.00 | 0.00 | 0.00 |
| February | 32.37 | 0.00 | 32.37 | 13.45 | 178.93 | 0.00 | 0.00 | 0.00 |
| March | 45.46 | 0.00 | 45.46 | 30.66 | 110.61 | 0.00 | 0.00 | 0.00 |
| April | 55.04 | 0.29 | 54.75 | 58.82 | 88.75 | 0.00 | 0.00 | 0.00 |
| May | 65.74 | 2.05 | 63.69 | 90.82 | 55.23 | 0.00 | 0.00 | 0.00 |
| June | 72.10 | 4.53 | 67.57 | 134.21 | 30.39 | 0.00 | 0.00 | 0.00 |
| July | 68.28 | 3.33 | 64.96 | 136.55 | 20.01 | 0.00 | 0.00 | 0.00 |
| August | 60.86 | 0.77 | 60.09 | 124.53 | 15.08 | 0.00 | 0.00 | 0.00 |
| September | 45.92 | 0.02 | 45.90 | 69.14 | 45.68 | 0.00 | 0.00 | 0.00 |
| October | 34.89 | 0.00 | 34.89 | 29.87 | 101.82 | 0.00 | 0.00 | 0.00 |
| November | 31.23 | 0.00 | 31.23 | 16.49 | 135.57 | 0.00 | 0.00 | 0.00 |
| December | 27.00 | 0.00 | 27.00 | 4.43 | 175.84 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.42 | 0.92 | 46.50 | 59.68 | 97.80 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 0.00 | 27.00 | 3.97 | 15.08 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.10 | 4.53 | 67.57 | 136.55 | 220.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.87 | 106.53 | 47.34 | 175.83 | 184.16 | 0.00 | 0.00 | 0.00 |
| February | 146.91 | 98.84 | 48.07 | 183.88 | 158.22 | 0.00 | 0.00 | 0.00 |
| March | 130.59 | 67.81 | 62.77 | 176.02 | 109.39 | 0.00 | 0.00 | 0.00 |
| April | 101.14 | 34.91 | 66.23 | 150.92 | 91.24 | 0.00 | 0.00 | 0.00 |
| May | 79.90 | 9.79 | 70.12 | 126.20 | 58.65 | 0.00 | 0.00 | 0.00 |
| June | 73.71 | 4.44 | 69.27 | 142.03 | 32.79 | 0.00 | 0.00 | 0.00 |
| July | 73.97 | 5.34 | 68.63 | 151.48 | 21.05 | 0.00 | 0.00 | 0.00 |
| August | 88.04 | 16.04 | 72.00 | 182.95 | 15.81 | 0.00 | 0.00 | 0.00 |
| September | 101.08 | 39.92 | 61.16 | 175.55 | 45.91 | 0.00 | 0.00 | 0.00 |
| October | 139.89 | 90.18 | 49.71 | 208.47 | 99.30 | 0.00 | 0.00 | 0.00 |
| November | 153.17 | 102.10 | 51.07 | 206.26 | 128.46 | 0.00 | 0.00 | 0.00 |
| December | 153.46 | 107.81 | 45.65 | 188.46 | 154.99 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.16 | 56.76 | 59.40 | 172.28 | 91.30 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.71 | 4.44 | 45.65 | 126.20 | 15.81 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 153.87 | 107.81 | 72.00 | 208.47 | 184.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.87 | 106.53 | 47.34 | 175.77 | 184.11 | 0.00 | 0.00 | 0.00 |
| February | 146.91 | 98.84 | 48.07 | 183.78 | 158.17 | 0.00 | 0.00 | 0.00 |
| March | 130.59 | 67.81 | 62.77 | 175.91 | 109.27 | 0.00 | 0.00 | 0.00 |
| April | 101.14 | 34.91 | 66.23 | 150.77 | 91.18 | 0.00 | 0.00 | 0.00 |
| May | 79.90 | 9.79 | 70.12 | 126.08 | 58.63 | 0.00 | 0.00 | 0.00 |
| June | 73.71 | 4.44 | 69.27 | 141.94 | 32.78 | 0.00 | 0.00 | 0.00 |
| July | 73.97 | 5.34 | 68.63 | 151.45 | 21.03 | 0.00 | 0.00 | 0.00 |
| August | 88.04 | 16.04 | 72.00 | 182.93 | 15.80 | 0.00 | 0.00 | 0.00 |
| September | 101.08 | 39.92 | 61.16 | 175.49 | 45.89 | 0.00 | 0.00 | 0.00 |
| October | 139.89 | 90.18 | 49.71 | 208.37 | 99.26 | 0.00 | 0.00 | 0.00 |
| November | 153.17 | 102.10 | 51.07 | 206.19 | 128.39 | 0.00 | 0.00 | 0.00 |
| December | 153.46 | 107.81 | 45.65 | 188.40 | 154.95 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.16 | 56.76 | 59.40 | 172.20 | 91.26 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.71 | 4.44 | 45.65 | 126.08 | 15.80 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 153.87 | 107.81 | 72.00 | 208.37 | 184.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW14
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 10.23 | 4.67 | 5.56 | 6.98 | 32.48 | 590.00 | 0.00 | 0.00 |
| February | 12.73 | 6.82 | 5.91 | 12.15 | 27.02 | 427.67 | 0.00 | 0.00 |
| March | 16.10 | 7.33 | 8.77 | 17.89 | 17.85 | 429.50 | 0.00 | 0.00 |
| April | 19.45 | 8.88 | 10.57 | 26.25 | 14.74 | 389.17 | 0.00 | 0.00 |
| May | 21.36 | 9.04 | 12.31 | 31.76 | 10.05 | 378.17 | 0.00 | 0.00 |
| June | 22.09 | 9.26 | 12.83 | 37.83 | 6.08 | 315.17 | 0.00 | 0.00 |
| July | 21.54 | 9.06 | 12.48 | 38.20 | 4.43 | 315.00 | 0.00 | 0.00 |
| August | 19.69 | 7.79 | 11.89 | 35.32 | 3.62 | 318.17 | 0.00 | 0.00 |
| September | 16.13 | 7.11 | 9.02 | 24.91 | 8.47 | 415.67 | 0.00 | 0.00 |
| October | 13.83 | 7.21 | 6.63 | 17.28 | 16.70 | 467.00 | 0.00 | 0.00 |
| November | 11.01 | 4.97 | 6.03 | 10.67 | 21.37 | 481.33 | 0.00 | 0.00 |
| December | 9.57 | 4.37 | 5.20 | 6.96 | 26.57 | 577.00 | 0.00 | 0.00 |
| Annual Sum or Average | 16.16 | 7.21 | 8.95 | 22.24 | 15.72 | 5103.83 | 0.00 | 0.00 |
| Minimum of Months | 9.57 | 4.37 | 5.20 | 6.96 | 3.62 | 315.00 | 0.00 | 0.00 |
| Maximum of Months | 22.09 | 9.26 | 12.83 | 38.20 | 32.48 | 590.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ENTRANCE DOOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.47 | 13.91 | 16.55 | 21.28 | 94.03 | 3.00 | 0.00 | 0.00 |
| February | 37.91 | 20.32 | 17.59 | 36.75 | 78.00 | 4.33 | 0.00 | 0.00 |
| March | 47.96 | 21.84 | 26.12 | 53.06 | 53.54 | 0.00 | 0.00 | 0.00 |
| April | 57.92 | 26.44 | 31.48 | 78.35 | 43.67 | 10.83 | 0.00 | 0.00 |
| May | 63.61 | 26.93 | 36.68 | 94.62 | 30.50 | 37.50 | 0.00 | 0.00 |
| June | 65.78 | 27.59 | 38.20 | 110.63 | 20.33 | 57.00 | 0.00 | 0.00 |
| July | 64.15 | 26.98 | 37.17 | 111.05 | 15.69 | 105.67 | 0.00 | 0.00 |
| August | 58.63 | 23.21 | 35.42 | 102.33 | 13.92 | 134.83 | 0.00 | 0.00 |
| September | 48.03 | 21.18 | 26.85 | 71.80 | 28.87 | 66.83 | 0.00 | 0.00 |
| October | 41.20 | 21.46 | 19.74 | 48.93 | 55.16 | 30.33 | 0.00 | 0.00 |
| November | 32.78 | 14.81 | 17.97 | 28.87 | 70.83 | 14.00 | 0.00 | 0.00 |
| December | 28.50 | 13.00 | 15.50 | 19.80 | 83.70 | 6.83 | 0.00 | 0.00 |
| Annual Sum or Average | 48.13 | 21.47 | 26.66 | 64.94 | 48.87 | 471.17 | 0.00 | 0.00 |
| Minimum of Months | 28.50 | 13.00 | 15.50 | 19.80 | 13.92 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.78 | 27.59 | 38.20 | 111.05 | 94.03 | 134.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW14
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 10.23 | 4.67 | 5.56 | 6.40 | 35.93 | 690.50 | 0.00 | 0.00 |
| February | 12.73 | 6.82 | 5.91 | 11.28 | 29.94 | 558.33 | 0.00 | 0.00 |
| March | 16.10 | 7.33 | 8.77 | 16.54 | 20.17 | 565.17 | 0.00 | 0.00 |
| April | 19.45 | 8.88 | 10.57 | 25.50 | 15.62 | 446.67 | 0.00 | 0.00 |
| May | 21.36 | 9.04 | 12.31 | 31.62 | 10.33 | 403.67 | 0.00 | 0.00 |
| June | 22.09 | 9.26 | 12.83 | 38.09 | 6.15 | 317.17 | 0.00 | 0.00 |
| July | 21.54 | 9.06 | 12.48 | 38.63 | 4.44 | 311.83 | 0.00 | 0.00 |
| August | 19.69 | 7.79 | 11.89 | 35.80 | 3.62 | 305.33 | 0.00 | 0.00 |
| September | 16.13 | 7.11 | 9.02 | 24.83 | 8.85 | 427.83 | 0.00 | 0.00 |
| October | 13.83 | 7.21 | 6.63 | 16.42 | 18.65 | 545.33 | 0.00 | 0.00 |
| November | 11.01 | 4.97 | 6.03 | 9.32 | 24.63 | 613.67 | 0.00 | 0.00 |
| December | 9.57 | 4.37 | 5.20 | 6.11 | 30.34 | 682.67 | 0.00 | 0.00 |
| Annual Sum or Average | 16.16 | 7.21 | 8.95 | 21.77 | 17.32 | 5868.17 | 0.00 | 0.00 |
| Minimum of Months | 9.57 | 4.37 | 5.20 | 6.11 | 3.62 | 305.33 | 0.00 | 0.00 |
| Maximum of Months | 22.09 | 9.26 | 12.83 | 38.63 | 35.93 | 690.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.484617E+09 | 0.486327E+09 |
| February | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.458498E+09 | 0.371708E+09 |
| March | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.484040E+09 | 0.291882E+09 |
| April | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.405959E+09 | 0.229566E+09 |
| May | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.350450E+09 | 0.152891E+09 |
| June | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.374549E+09 | 86795460.07 |
| July | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.410583E+09 | 59067680.98 |
| August | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.493992E+09 | 47127662.92 |
| September | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.457065E+09 | 0.126899E+09 |
| October | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.560048E+09 | 0.285419E+09 |
| November | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.529982E+09 | 0.361528E+09 |
| December | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.505658E+09 | 0.436115E+09 |
| Annual Sum or Average | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.551544E+10 | 0.293533E+10 |
| Minimum of Months | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.350450E+09 | 47127662.92 |
| Maximum of Months | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.560048E+09 | 0.486327E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.117006E+09 | 54557234.10 | 62448390.99 | 92212713.88 | 0.363121E+09 |
| February | 0.120495E+09 | 56341097.18 | 64154071.29 | 0.125146E+09 | 0.271295E+09 |
| March | 0.196181E+09 | 94648481.84 | 0.101532E+09 | 0.247704E+09 | 0.199178E+09 |
| April | 0.213510E+09 | 97521745.30 | 0.115988E+09 | 0.313890E+09 | 0.148948E+09 |
| May | 0.222316E+09 | 84311468.47 | 0.138004E+09 | 0.360293E+09 | 98884353.00 |
| June | 0.226513E+09 | 87480231.16 | 0.139033E+09 | 0.417674E+09 | 56363127.39 |
| July | 0.220101E+09 | 81542048.64 | 0.138559E+09 | 0.422235E+09 | 38273426.59 |
| August | 0.215699E+09 | 80584545.23 | 0.135114E+09 | 0.415872E+09 | 30871138.61 |
| September | 0.170686E+09 | 71311707.53 | 99374068.44 | 0.279646E+09 | 83542149.84 |
| October | 0.156145E+09 | 80832908.90 | 75311721.06 | 0.208787E+09 | 0.199522E+09 |
| November | 0.120345E+09 | 53661756.34 | 66683003.62 | 0.126660E+09 | 0.264027E+09 |
| December | 0.103419E+09 | 45383902.30 | 58035106.06 | 83743879.24 | 0.326398E+09 |
| Annual Sum or Average | 0.208241E+10 | 0.888177E+09 | 0.119424E+10 | 0.309386E+10 | 0.208042E+10 |
| Minimum of Months | 0.103419E+09 | 45383902.30 | 58035106.06 | 83743879.24 | 30871138.61 |
| Maximum of Months | 0.226513E+09 | 97521745.30 | 0.139033E+09 | 0.422235E+09 | 0.363121E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.117006E+09 | 54557234.10 | 62448390.99 | 97646490.61 | 0.351497E+09 |
| February | 0.120495E+09 | 56341097.18 | 64154071.29 | 0.131949E+09 | 0.258110E+09 |
| March | 0.196181E+09 | 94648481.84 | 0.101532E+09 | 0.259051E+09 | 0.181978E+09 |
| April | 0.213510E+09 | 97521745.30 | 0.115988E+09 | 0.318862E+09 | 0.144086E+09 |
| May | 0.222316E+09 | 84311468.47 | 0.138004E+09 | 0.361623E+09 | 98117455.06 |
| June | 0.226513E+09 | 87480231.16 | 0.139033E+09 | 0.417991E+09 | 56414073.39 |
| July | 0.220101E+09 | 81542048.64 | 0.138559E+09 | 0.422704E+09 | 38207476.71 |
| August | 0.215699E+09 | 80584545.23 | 0.135114E+09 | 0.417268E+09 | 30318030.31 |
| September | 0.170686E+09 | 71311707.53 | 99374068.44 | 0.282064E+09 | 81761769.17 |
| October | 0.156145E+09 | 80832908.90 | 75311721.06 | 0.213658E+09 | 0.194021E+09 |
| November | 0.120345E+09 | 53661756.34 | 66683003.62 | 0.134612E+09 | 0.247701E+09 |
| December | 0.103419E+09 | 45383902.30 | 58035106.06 | 92594170.15 | 0.299121E+09 |
| Annual Sum or Average | 0.208241E+10 | 0.888177E+09 | 0.119424E+10 | 0.315002E+10 | 0.198133E+10 |
| Minimum of Months | 0.103419E+09 | 45383902.30 | 58035106.06 | 92594170.15 | 30318030.31 |
| Maximum of Months | 0.226513E+09 | 97521745.30 | 0.139033E+09 | 0.422704E+09 | 0.351497E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78218996.00 | 0.00 | 78218996.00 | 11997141.07 | 0.580536E+09 |
| February | 78307946.70 | 0.00 | 78307946.70 | 36687820.14 | 0.417136E+09 |
| March | 0.121754E+09 | 6487.33 | 0.121748E+09 | 91121151.38 | 0.287612E+09 |
| April | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.164954E+09 | 0.220925E+09 |
| May | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.255614E+09 | 0.143183E+09 |
| June | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.354140E+09 | 80155648.37 |
| July | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.369964E+09 | 55796170.38 |
| August | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.335816E+09 | 44615094.68 |
| September | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.178423E+09 | 0.126101E+09 |
| October | 93456920.53 | 0.00 | 93456920.53 | 73962277.21 | 0.303504E+09 |
| November | 80942560.83 | 0.00 | 80942560.83 | 34055939.99 | 0.392735E+09 |
| December | 72307654.87 | 0.00 | 72307654.87 | 11715390.80 | 0.481926E+09 |
| Annual Sum or Average | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.191845E+10 | 0.313422E+10 |
| Minimum of Months | 72307654.87 | 0.00 | 72307654.87 | 11715390.80 | 44615094.68 |
| Maximum of Months | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.369964E+09 | 0.580536E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.499302E+09 | 0.438425E+09 |
| February | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.466640E+09 | 0.347673E+09 |
| March | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.486029E+09 | 0.289983E+09 |
| April | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.401336E+09 | 0.238028E+09 |
| May | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.338640E+09 | 0.174821E+09 |
| June | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.349413E+09 | 0.122352E+09 |
| July | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.373464E+09 | 0.101921E+09 |
| August | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.460163E+09 | 93795930.65 |
| September | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.439441E+09 | 0.166651E+09 |
| October | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.556364E+09 | 0.302509E+09 |
| November | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.535041E+09 | 0.359124E+09 |
| December | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.515109E+09 | 0.415642E+09 |
| Annual Sum or Average | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.542094E+10 | 0.305092E+10 |
| Minimum of Months | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.338640E+09 | 93795930.65 |
| Maximum of Months | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.556364E+09 | 0.438425E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.114189E+09 | 52148537.34 | 62039993.58 | 85708958.16 | 0.316707E+09 |
| February | 0.128338E+09 | 68792629.26 | 59545196.04 | 0.130162E+09 | 0.239992E+09 |
| March | 0.179737E+09 | 81856768.46 | 97880591.31 | 0.208968E+09 | 0.186410E+09 |
| April | 0.210070E+09 | 95890089.91 | 0.114180E+09 | 0.297908E+09 | 0.145218E+09 |
| May | 0.238402E+09 | 0.100946E+09 | 0.137456E+09 | 0.371741E+09 | 0.106076E+09 |
| June | 0.238599E+09 | 0.100058E+09 | 0.138541E+09 | 0.417523E+09 | 73972851.16 |
| July | 0.240418E+09 | 0.101101E+09 | 0.139317E+09 | 0.428705E+09 | 62773601.21 |
| August | 0.219749E+09 | 86999749.78 | 0.132749E+09 | 0.397298E+09 | 58737584.43 |
| September | 0.174212E+09 | 76817168.85 | 97394647.06 | 0.270918E+09 | 0.106337E+09 |
| October | 0.154398E+09 | 80431456.59 | 73966215.97 | 0.191602E+09 | 0.198286E+09 |
| November | 0.118901E+09 | 53715015.09 | 65186252.29 | 0.110405E+09 | 0.243403E+09 |
| December | 0.106820E+09 | 48728649.93 | 58091386.96 | 78677023.36 | 0.292613E+09 |
| Annual Sum or Average | 0.212383E+10 | 0.947485E+09 | 0.117635E+10 | 0.298962E+10 | 0.203053E+10 |
| Minimum of Months | 0.106820E+09 | 48728649.93 | 58091386.96 | 78677023.36 | 58737584.43 |
| Maximum of Months | 0.240418E+09 | 0.101101E+09 | 0.139317E+09 | 0.428705E+09 | 0.316707E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.114189E+09 | 52148537.34 | 62039993.58 | 83504002.98 | 0.338944E+09 |
| February | 0.128338E+09 | 68792629.26 | 59545196.04 | 0.131994E+09 | 0.244327E+09 |
| March | 0.179737E+09 | 81856768.46 | 97880591.31 | 0.217895E+09 | 0.169441E+09 |
| April | 0.210070E+09 | 95890089.91 | 0.114180E+09 | 0.304454E+09 | 0.133973E+09 |
| May | 0.238402E+09 | 0.100946E+09 | 0.137456E+09 | 0.380032E+09 | 91295349.51 |
| June | 0.238599E+09 | 0.100058E+09 | 0.138541E+09 | 0.434272E+09 | 52120615.45 |
| July | 0.240418E+09 | 0.101101E+09 | 0.139317E+09 | 0.454466E+09 | 36406562.19 |
| August | 0.219749E+09 | 86999749.78 | 0.132749E+09 | 0.421579E+09 | 28322094.07 |
| September | 0.174212E+09 | 76817168.85 | 97394647.06 | 0.284062E+09 | 78404414.64 |
| October | 0.154398E+09 | 80431456.59 | 73966215.97 | 0.197706E+09 | 0.180381E+09 |
| November | 0.118901E+09 | 53715015.09 | 65186252.29 | 0.115062E+09 | 0.229032E+09 |
| December | 0.106820E+09 | 48728649.93 | 58091386.96 | 82025183.97 | 0.279883E+09 |
| Annual Sum or Average | 0.212383E+10 | 0.947485E+09 | 0.117635E+10 | 0.310705E+10 | 0.186253E+10 |
| Minimum of Months | 0.106820E+09 | 48728649.93 | 58091386.96 | 82025183.97 | 28322094.07 |
| Maximum of Months | 0.240418E+09 | 0.101101E+09 | 0.139317E+09 | 0.454466E+09 | 0.338944E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78218996.00 | 0.00 | 78218996.00 | 11849332.02 | 0.580349E+09 |
| February | 78307946.70 | 0.00 | 78307946.70 | 35841198.66 | 0.417612E+09 |
| March | 0.121754E+09 | 6487.33 | 0.121748E+09 | 90052842.05 | 0.286225E+09 |
| April | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.163192E+09 | 0.219770E+09 |
| May | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.253535E+09 | 0.142787E+09 |
| June | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.352358E+09 | 79884271.85 |
| July | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.368687E+09 | 55646274.09 |
| August | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.335138E+09 | 44202853.21 |
| September | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.177160E+09 | 0.125728E+09 |
| October | 93456920.53 | 0.00 | 93456920.53 | 72852374.23 | 0.302545E+09 |
| November | 80942560.83 | 0.00 | 80942560.83 | 33462399.74 | 0.392534E+09 |
| December | 72307654.87 | 0.00 | 72307654.87 | 11470362.34 | 0.481923E+09 |
| Annual Sum or Average | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.190560E+10 | 0.312921E+10 |
| Minimum of Months | 72307654.87 | 0.00 | 72307654.87 | 11470362.34 | 44202853.21 |
| Maximum of Months | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.368687E+09 | 0.580349E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78218996.00 | 0.00 | 78218996.00 | 11312611.79 | 0.593660E+09 |
| February | 78307946.70 | 0.00 | 78307946.70 | 34604589.31 | 0.429915E+09 |
| March | 0.121754E+09 | 6487.33 | 0.121748E+09 | 85554340.71 | 0.304708E+09 |
| April | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.161439E+09 | 0.228637E+09 |
| May | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.255204E+09 | 0.144788E+09 |
| June | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.356546E+09 | 79429196.01 |
| July | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.373445E+09 | 54896408.75 |
| August | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.340015E+09 | 42984587.26 |
| September | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.180233E+09 | 0.125300E+09 |
| October | 93456920.53 | 0.00 | 93456920.53 | 74101655.83 | 0.306499E+09 |
| November | 80942560.83 | 0.00 | 80942560.83 | 31902094.31 | 0.407234E+09 |
| December | 72307654.87 | 0.00 | 72307654.87 | 10157830.32 | 0.503346E+09 |
| Annual Sum or Average | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.191452E+10 | 0.322140E+10 |
| Minimum of Months | 72307654.87 | 0.00 | 72307654.87 | 10157830.32 | 42984587.26 |
| Maximum of Months | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.373445E+09 | 0.593660E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78218996.00 | 0.00 | 78218996.00 | 11305069.12 | 0.593659E+09 |
| February | 78307946.70 | 0.00 | 78307946.70 | 34536171.52 | 0.430006E+09 |
| March | 0.121754E+09 | 6487.33 | 0.121748E+09 | 85484966.32 | 0.304656E+09 |
| April | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.161350E+09 | 0.228598E+09 |
| May | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.255091E+09 | 0.144805E+09 |
| June | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.356455E+09 | 79440050.29 |
| July | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.373388E+09 | 54903881.79 |
| August | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.339990E+09 | 42972810.29 |
| September | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.180172E+09 | 0.125307E+09 |
| October | 93456920.53 | 0.00 | 93456920.53 | 74043647.89 | 0.306472E+09 |
| November | 80942560.83 | 0.00 | 80942560.83 | 31865256.40 | 0.407275E+09 |
| December | 72307654.87 | 0.00 | 72307654.87 | 10147440.84 | 0.503400E+09 |
| Annual Sum or Average | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.191383E+10 | 0.322149E+10 |
| Minimum of Months | 72307654.87 | 0.00 | 72307654.87 | 10147440.84 | 42972810.29 |
| Maximum of Months | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.373388E+09 | 0.593659E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.476947E+09 | 0.504669E+09 |
| February | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.452161E+09 | 0.386994E+09 |
| March | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.477619E+09 | 0.304594E+09 |
| April | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.402394E+09 | 0.235959E+09 |
| May | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.349999E+09 | 0.154618E+09 |
| June | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.376863E+09 | 86174044.46 |
| July | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.413932E+09 | 58267907.28 |
| August | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.497888E+09 | 45624026.42 |
| September | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.458445E+09 | 0.126434E+09 |
| October | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.559367E+09 | 0.288319E+09 |
| November | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.526990E+09 | 0.368726E+09 |
| December | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.496389E+09 | 0.460570E+09 |
| Annual Sum or Average | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.548899E+10 | 0.302095E+10 |
| Minimum of Months | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.349999E+09 | 45624026.42 |
| Maximum of Months | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.559367E+09 | 0.504669E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.478825E+09 | 0.499370E+09 |
| February | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.453075E+09 | 0.384443E+09 |
| March | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.477716E+09 | 0.304038E+09 |
| April | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.401943E+09 | 0.236315E+09 |
| May | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.349004E+09 | 0.155619E+09 |
| June | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.375191E+09 | 87645663.77 |
| July | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.411681E+09 | 60025845.54 |
| August | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.495831E+09 | 47426801.02 |
| September | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.457078E+09 | 0.128224E+09 |
| October | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.558858E+09 | 0.288947E+09 |
| November | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.527177E+09 | 0.368212E+09 |
| December | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.497373E+09 | 0.457619E+09 |
| Annual Sum or Average | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.548375E+10 | 0.301789E+10 |
| Minimum of Months | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.349004E+09 | 47426801.02 |
| Maximum of Months | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.558858E+09 | 0.499370E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.470688E+09 | 0.511809E+09 |
| February | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.444036E+09 | 0.399916E+09 |
| March | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.465593E+09 | 0.317451E+09 |
| April | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.391207E+09 | 0.247687E+09 |
| May | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.340493E+09 | 0.162208E+09 |
| June | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.371770E+09 | 88078507.34 |
| July | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.409862E+09 | 58733445.92 |
| August | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.494900E+09 | 44746215.43 |
| September | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.457566E+09 | 0.123890E+09 |
| October | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.557886E+09 | 0.284481E+09 |
| November | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.527122E+09 | 0.361561E+09 |
| December | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.499680E+09 | 0.443885E+09 |
| Annual Sum or Average | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.543080E+10 | 0.304445E+10 |
| Minimum of Months | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.340493E+09 | 44746215.43 |
| Maximum of Months | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.557886E+09 | 0.511809E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.117006E+09 | 54557234.10 | 62448390.99 | 86661486.43 | 0.383474E+09 |
| February | 0.120495E+09 | 56341097.18 | 64154071.29 | 0.118238E+09 | 0.292139E+09 |
| March | 0.196181E+09 | 94648481.84 | 0.101532E+09 | 0.236563E+09 | 0.217042E+09 |
| April | 0.213510E+09 | 97521745.30 | 0.115988E+09 | 0.303517E+09 | 0.160517E+09 |
| May | 0.222316E+09 | 84311468.47 | 0.138004E+09 | 0.352996E+09 | 0.104731E+09 |
| June | 0.226513E+09 | 87480231.16 | 0.139033E+09 | 0.414984E+09 | 57212489.51 |
| July | 0.220101E+09 | 81542048.64 | 0.138559E+09 | 0.421233E+09 | 38061586.89 |
| August | 0.215699E+09 | 80584545.23 | 0.135114E+09 | 0.416180E+09 | 29360917.25 |
| September | 0.170686E+09 | 71311707.53 | 99374068.44 | 0.280044E+09 | 81631927.07 |
| October | 0.156145E+09 | 80832908.90 | 75311721.06 | 0.207789E+09 | 0.199075E+09 |
| November | 0.120345E+09 | 53661756.34 | 66683003.62 | 0.125364E+09 | 0.264416E+09 |
| December | 0.103419E+09 | 45383902.30 | 58035106.06 | 81624075.27 | 0.332921E+09 |
| Annual Sum or Average | 0.208241E+10 | 0.888177E+09 | 0.119424E+10 | 0.304519E+10 | 0.216058E+10 |
| Minimum of Months | 0.103419E+09 | 45383902.30 | 58035106.06 | 81624075.27 | 29360917.25 |
| Maximum of Months | 0.226513E+09 | 97521745.30 | 0.139033E+09 | 0.421233E+09 | 0.383474E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.117006E+09 | 54557234.10 | 62448390.99 | 93944811.67 | 0.365777E+09 |
| February | 0.120495E+09 | 56341097.18 | 64154071.29 | 0.124667E+09 | 0.279452E+09 |
| March | 0.196181E+09 | 94648481.84 | 0.101532E+09 | 0.243076E+09 | 0.209695E+09 |
| April | 0.213510E+09 | 97521745.30 | 0.115988E+09 | 0.306701E+09 | 0.158573E+09 |
| May | 0.222316E+09 | 84311468.47 | 0.138004E+09 | 0.353915E+09 | 0.104352E+09 |
| June | 0.226513E+09 | 87480231.16 | 0.139033E+09 | 0.415290E+09 | 57265505.72 |
| July | 0.220101E+09 | 81542048.64 | 0.138559E+09 | 0.421696E+09 | 38023778.55 |
| August | 0.215699E+09 | 80584545.23 | 0.135114E+09 | 0.417437E+09 | 28953842.93 |
| September | 0.170686E+09 | 71311707.53 | 99374068.44 | 0.282384E+09 | 80189597.24 |
| October | 0.156145E+09 | 80832908.90 | 75311721.06 | 0.213245E+09 | 0.193557E+09 |
| November | 0.120345E+09 | 53661756.34 | 66683003.62 | 0.134295E+09 | 0.247545E+09 |
| December | 0.103419E+09 | 45383902.30 | 58035106.06 | 90453454.86 | 0.306678E+09 |
| Annual Sum or Average | 0.208241E+10 | 0.888177E+09 | 0.119424E+10 | 0.309710E+10 | 0.207006E+10 |
| Minimum of Months | 0.103419E+09 | 45383902.30 | 58035106.06 | 90453454.86 | 28953842.93 |
| Maximum of Months | 0.226513E+09 | 97521745.30 | 0.139033E+09 | 0.421696E+09 | 0.365777E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78218996.00 | 0.00 | 78218996.00 | 10246699.90 | 0.604841E+09 |
| February | 78307946.70 | 0.00 | 78307946.70 | 29482499.18 | 0.451993E+09 |
| March | 0.121754E+09 | 6487.33 | 0.121748E+09 | 72654511.42 | 0.333168E+09 |
| April | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.149620E+09 | 0.243921E+09 |
| May | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.244847E+09 | 0.152563E+09 |
| June | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.351262E+09 | 81280070.23 |
| July | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.369435E+09 | 55567254.66 |
| August | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.337343E+09 | 42521023.14 |
| September | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.180002E+09 | 0.123540E+09 |
| October | 93456920.53 | 0.00 | 93456920.53 | 74609613.86 | 0.302541E+09 |
| November | 80942560.83 | 0.00 | 80942560.83 | 34330084.70 | 0.392037E+09 |
| December | 72307654.87 | 0.00 | 72307654.87 | 10229405.59 | 0.493917E+09 |
| Annual Sum or Average | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.186406E+10 | 0.327789E+10 |
| Minimum of Months | 72307654.87 | 0.00 | 72307654.87 | 10229405.59 | 42521023.14 |
| Maximum of Months | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.369435E+09 | 0.604841E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.469272E+09 | 0.510748E+09 |
| February | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.442550E+09 | 0.399129E+09 |
| March | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.464672E+09 | 0.315283E+09 |
| April | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.388958E+09 | 0.246458E+09 |
| May | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.338047E+09 | 0.161722E+09 |
| June | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.369783E+09 | 87802162.58 |
| July | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.408545E+09 | 58487997.02 |
| August | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.494188E+09 | 44326981.58 |
| September | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.456106E+09 | 0.123430E+09 |
| October | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.556302E+09 | 0.283609E+09 |
| November | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.526103E+09 | 0.360648E+09 |
| December | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.497982E+09 | 0.443597E+09 |
| Annual Sum or Average | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.541251E+10 | 0.303524E+10 |
| Minimum of Months | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.338047E+09 | 44326981.58 |
| Maximum of Months | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.556302E+09 | 0.510748E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.114189E+09 | 52148537.34 | 62039993.58 | 75810004.82 | 0.373811E+09 |
| February | 0.128338E+09 | 68792629.26 | 59545196.04 | 0.118922E+09 | 0.278205E+09 |
| March | 0.179737E+09 | 81856768.46 | 97880591.31 | 0.195077E+09 | 0.202654E+09 |
| April | 0.210070E+09 | 95890089.91 | 0.114180E+09 | 0.288691E+09 | 0.149541E+09 |
| May | 0.238402E+09 | 0.100946E+09 | 0.137456E+09 | 0.370582E+09 | 97630636.67 |
| June | 0.238599E+09 | 0.100058E+09 | 0.138541E+09 | 0.431134E+09 | 52834436.45 |
| July | 0.240418E+09 | 0.101101E+09 | 0.139317E+09 | 0.452845E+09 | 36262696.01 |
| August | 0.219749E+09 | 86999749.78 | 0.132749E+09 | 0.420546E+09 | 27374472.22 |
| September | 0.174212E+09 | 76817168.85 | 97394647.06 | 0.282106E+09 | 78307990.17 |
| October | 0.154398E+09 | 80431456.59 | 73966215.97 | 0.191985E+09 | 0.185662E+09 |
| November | 0.118901E+09 | 53715015.09 | 65186252.29 | 0.106409E+09 | 0.245479E+09 |
| December | 0.106820E+09 | 48728649.93 | 58091386.96 | 72355699.23 | 0.315119E+09 |
| Annual Sum or Average | 0.212383E+10 | 0.947485E+09 | 0.117635E+10 | 0.300646E+10 | 0.204288E+10 |
| Minimum of Months | 0.106820E+09 | 48728649.93 | 58091386.96 | 72355699.23 | 27374472.22 |
| Maximum of Months | 0.240418E+09 | 0.101101E+09 | 0.139317E+09 | 0.452845E+09 | 0.373811E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.114189E+09 | 52148537.34 | 62039993.58 | 80129908.82 | 0.352959E+09 |
| February | 0.128338E+09 | 68792629.26 | 59545196.04 | 0.123909E+09 | 0.264433E+09 |
| March | 0.179737E+09 | 81856768.46 | 97880591.31 | 0.200969E+09 | 0.195264E+09 |
| April | 0.210070E+09 | 95890089.91 | 0.114180E+09 | 0.291592E+09 | 0.147520E+09 |
| May | 0.238402E+09 | 0.100946E+09 | 0.137456E+09 | 0.371407E+09 | 97258537.30 |
| June | 0.238599E+09 | 0.100058E+09 | 0.138541E+09 | 0.431465E+09 | 52841117.79 |
| July | 0.240418E+09 | 0.101101E+09 | 0.139317E+09 | 0.453377E+09 | 36184157.23 |
| August | 0.219749E+09 | 86999749.78 | 0.132749E+09 | 0.421827E+09 | 26984101.94 |
| September | 0.174212E+09 | 76817168.85 | 97394647.06 | 0.284334E+09 | 76940617.94 |
| October | 0.154398E+09 | 80431456.59 | 73966215.97 | 0.197368E+09 | 0.179607E+09 |
| November | 0.118901E+09 | 53715015.09 | 65186252.29 | 0.114785E+09 | 0.228621E+09 |
| December | 0.106820E+09 | 48728649.93 | 58091386.96 | 79622315.70 | 0.286831E+09 |
| Annual Sum or Average | 0.212383E+10 | 0.947485E+09 | 0.117635E+10 | 0.305078E+10 | 0.194544E+10 |
| Minimum of Months | 0.106820E+09 | 48728649.93 | 58091386.96 | 79622315.70 | 26984101.94 |
| Maximum of Months | 0.240418E+09 | 0.101101E+09 | 0.139317E+09 | 0.453377E+09 | 0.352959E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78218996.00 | 0.00 | 78218996.00 | 10016086.39 | 0.604477E+09 |
| February | 78307946.70 | 0.00 | 78307946.70 | 28643252.02 | 0.452280E+09 |
| March | 0.121754E+09 | 6487.33 | 0.121748E+09 | 71583491.05 | 0.331498E+09 |
| April | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.147469E+09 | 0.242926E+09 |
| May | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.242280E+09 | 0.152116E+09 |
| June | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.349209E+09 | 80912639.57 |
| July | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.368095E+09 | 55238050.64 |
| August | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.336538E+09 | 42078826.12 |
| September | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.178409E+09 | 0.123194E+09 |
| October | 93456920.53 | 0.00 | 93456920.53 | 73309327.59 | 0.301145E+09 |
| November | 80942560.83 | 0.00 | 80942560.83 | 33565484.06 | 0.391672E+09 |
| December | 72307654.87 | 0.00 | 72307654.87 | 9973519.10 | 0.493883E+09 |
| Annual Sum or Average | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.184909E+10 | 0.327142E+10 |
| Minimum of Months | 72307654.87 | 0.00 | 72307654.87 | 9973519.10 | 42078826.12 |
| Maximum of Months | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.368095E+09 | 0.604477E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78218996.00 | 0.00 | 78218996.00 | 9431490.74 | 0.622247E+09 |
| February | 78307946.70 | 0.00 | 78307946.70 | 28133837.47 | 0.464596E+09 |
| March | 0.121754E+09 | 6487.33 | 0.121748E+09 | 71520802.40 | 0.339858E+09 |
| April | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.150615E+09 | 0.244211E+09 |
| May | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.247474E+09 | 0.151425E+09 |
| June | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.355074E+09 | 79715948.17 |
| July | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.373846E+09 | 54162640.60 |
| August | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.341883E+09 | 40906697.37 |
| September | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.181793E+09 | 0.122973E+09 |
| October | 93456920.53 | 0.00 | 93456920.53 | 74565707.89 | 0.306772E+09 |
| November | 80942560.83 | 0.00 | 80942560.83 | 31634809.41 | 0.409246E+09 |
| December | 72307654.87 | 0.00 | 72307654.87 | 8588437.83 | 0.519427E+09 |
| Annual Sum or Average | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.187456E+10 | 0.335554E+10 |
| Minimum of Months | 72307654.87 | 0.00 | 72307654.87 | 8588437.83 | 40906697.37 |
| Maximum of Months | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.373846E+09 | 0.622247E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78218996.00 | 0.00 | 78218996.00 | 9420343.75 | 0.622243E+09 |
| February | 78307946.70 | 0.00 | 78307946.70 | 28075527.73 | 0.464653E+09 |
| March | 0.121754E+09 | 6487.33 | 0.121748E+09 | 71463067.96 | 0.339763E+09 |
| April | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.150499E+09 | 0.244198E+09 |
| May | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.247338E+09 | 0.151434E+09 |
| June | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.354977E+09 | 79719978.60 |
| July | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.373802E+09 | 54154407.85 |
| August | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.341854E+09 | 40893498.34 |
| September | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.181718E+09 | 0.122979E+09 |
| October | 93456920.53 | 0.00 | 93456920.53 | 74494224.52 | 0.306723E+09 |
| November | 80942560.83 | 0.00 | 80942560.83 | 31586103.83 | 0.409288E+09 |
| December | 72307654.87 | 0.00 | 72307654.87 | 8578921.54 | 0.519473E+09 |
| Annual Sum or Average | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.187381E+10 | 0.335552E+10 |
| Minimum of Months | 72307654.87 | 0.00 | 72307654.87 | 8578921.54 | 40893498.34 |
| Maximum of Months | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.373802E+09 | 0.622243E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.460432E+09 | 0.539725E+09 |
| February | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.437825E+09 | 0.418656E+09 |
| March | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.464519E+09 | 0.321316E+09 |
| April | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.391909E+09 | 0.247802E+09 |
| May | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.342823E+09 | 0.161007E+09 |
| June | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.375486E+09 | 86456606.10 |
| July | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.414232E+09 | 57338732.01 |
| August | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.499266E+09 | 43161641.18 |
| September | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.459048E+09 | 0.123493E+09 |
| October | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.557121E+09 | 0.287862E+09 |
| November | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.523575E+09 | 0.370051E+09 |
| December | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.490087E+09 | 0.469695E+09 |
| Annual Sum or Average | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.541632E+10 | 0.312656E+10 |
| Minimum of Months | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.342823E+09 | 43161641.18 |
| Maximum of Months | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.557121E+09 | 0.539725E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.460386E+09 | 0.539678E+09 |
| February | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.437749E+09 | 0.418662E+09 |
| March | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.464489E+09 | 0.321200E+09 |
| April | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.391805E+09 | 0.247777E+09 |
| May | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.342703E+09 | 0.161011E+09 |
| June | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.375389E+09 | 86462637.31 |
| July | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.414191E+09 | 57318708.97 |
| August | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.499238E+09 | 43147349.79 |
| September | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.458988E+09 | 0.123491E+09 |
| October | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.557046E+09 | 0.287843E+09 |
| November | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.523537E+09 | 0.370025E+09 |
| December | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.490018E+09 | 0.469720E+09 |
| Annual Sum or Average | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.541554E+10 | 0.312634E+10 |
| Minimum of Months | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.342703E+09 | 43147349.79 |
| Maximum of Months | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.557046E+09 | 0.539678E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.475563E+09 | 0.482084E+09 |
| February | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.448639E+09 | 0.372271E+09 |
| March | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.474027E+09 | 0.285664E+09 |
| April | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.391165E+09 | 0.233778E+09 |
| May | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.335484E+09 | 0.156632E+09 |
| June | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.363682E+09 | 85712961.62 |
| July | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.400291E+09 | 57011277.30 |
| August | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.484546E+09 | 43260554.51 |
| September | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.453397E+09 | 0.118167E+09 |
| October | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.560885E+09 | 0.257744E+09 |
| November | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.539583E+09 | 0.321476E+09 |
| December | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.509732E+09 | 0.402992E+09 |
| Annual Sum or Average | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.543700E+10 | 0.281679E+10 |
| Minimum of Months | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.335484E+09 | 43260554.51 |
| Maximum of Months | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.560885E+09 | 0.482084E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.117006E+09 | 54557234.10 | 62448390.99 | 86998543.78 | 0.360922E+09 |
| February | 0.120495E+09 | 56341097.18 | 64154071.29 | 0.118315E+09 | 0.270756E+09 |
| March | 0.196181E+09 | 94648481.84 | 0.101532E+09 | 0.238499E+09 | 0.192367E+09 |
| April | 0.213510E+09 | 97521745.30 | 0.115988E+09 | 0.302023E+09 | 0.149944E+09 |
| May | 0.222316E+09 | 84311468.47 | 0.138004E+09 | 0.349020E+09 | 0.100551E+09 |
| June | 0.226513E+09 | 87480231.16 | 0.139033E+09 | 0.408822E+09 | 55394711.03 |
| July | 0.220101E+09 | 81542048.64 | 0.138559E+09 | 0.414603E+09 | 36819372.45 |
| August | 0.215699E+09 | 80584545.23 | 0.135114E+09 | 0.409166E+09 | 28316076.32 |
| September | 0.170686E+09 | 71311707.53 | 99374068.44 | 0.276765E+09 | 77388792.48 |
| October | 0.156145E+09 | 80832908.90 | 75311721.06 | 0.206827E+09 | 0.178324E+09 |
| November | 0.120345E+09 | 53661756.34 | 66683003.62 | 0.128324E+09 | 0.232255E+09 |
| December | 0.103419E+09 | 45383902.30 | 58035106.06 | 83081190.73 | 0.300362E+09 |
| Annual Sum or Average | 0.208241E+10 | 0.888177E+09 | 0.119424E+10 | 0.302244E+10 | 0.198340E+10 |
| Minimum of Months | 0.103419E+09 | 45383902.30 | 58035106.06 | 83081190.73 | 28316076.32 |
| Maximum of Months | 0.226513E+09 | 97521745.30 | 0.139033E+09 | 0.414603E+09 | 0.360922E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.117006E+09 | 54557234.10 | 62448390.99 | 95052384.34 | 0.350956E+09 |
| February | 0.120495E+09 | 56341097.18 | 64154071.29 | 0.127404E+09 | 0.261672E+09 |
| March | 0.196181E+09 | 94648481.84 | 0.101532E+09 | 0.250233E+09 | 0.183480E+09 |
| April | 0.213510E+09 | 97521745.30 | 0.115988E+09 | 0.307406E+09 | 0.147695E+09 |
| May | 0.222316E+09 | 84311468.47 | 0.138004E+09 | 0.350248E+09 | 0.100328E+09 |
| June | 0.226513E+09 | 87480231.16 | 0.139033E+09 | 0.409139E+09 | 55568375.76 |
| July | 0.220101E+09 | 81542048.64 | 0.138559E+09 | 0.415146E+09 | 36889151.14 |
| August | 0.215699E+09 | 80584545.23 | 0.135114E+09 | 0.410832E+09 | 28054044.36 |
| September | 0.170686E+09 | 71311707.53 | 99374068.44 | 0.280182E+09 | 76158664.26 |
| October | 0.156145E+09 | 80832908.90 | 75311721.06 | 0.217565E+09 | 0.169850E+09 |
| November | 0.120345E+09 | 53661756.34 | 66683003.62 | 0.141783E+09 | 0.217552E+09 |
| December | 0.103419E+09 | 45383902.30 | 58035106.06 | 93052211.81 | 0.286981E+09 |
| Annual Sum or Average | 0.208241E+10 | 0.888177E+09 | 0.119424E+10 | 0.309804E+10 | 0.191518E+10 |
| Minimum of Months | 0.103419E+09 | 45383902.30 | 58035106.06 | 93052211.81 | 28054044.36 |
| Maximum of Months | 0.226513E+09 | 97521745.30 | 0.139033E+09 | 0.415146E+09 | 0.350956E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78218996.00 | 0.00 | 78218996.00 | 11004534.95 | 0.581639E+09 |
| February | 78307946.70 | 0.00 | 78307946.70 | 33250362.30 | 0.424680E+09 |
| March | 0.121754E+09 | 6487.33 | 0.121748E+09 | 82956723.41 | 0.292201E+09 |
| April | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.151971E+09 | 0.228143E+09 |
| May | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.240776E+09 | 0.147543E+09 |
| June | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.343674E+09 | 79622525.18 |
| July | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.360513E+09 | 54410856.54 |
| August | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.328027E+09 | 41409328.50 |
| September | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.177342E+09 | 0.117724E+09 |
| October | 93456920.53 | 0.00 | 93456920.53 | 81197155.84 | 0.266073E+09 |
| November | 80942560.83 | 0.00 | 80942560.83 | 43918440.71 | 0.344465E+09 |
| December | 72307654.87 | 0.00 | 72307654.87 | 12557275.15 | 0.462303E+09 |
| Annual Sum or Average | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.186719E+10 | 0.304021E+10 |
| Minimum of Months | 72307654.87 | 0.00 | 72307654.87 | 11004534.95 | 41409328.50 |
| Maximum of Months | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.360513E+09 | 0.581639E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.473687E+09 | 0.480202E+09 |
| February | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.445741E+09 | 0.370557E+09 |
| March | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.470183E+09 | 0.281672E+09 |
| April | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.386045E+09 | 0.231077E+09 |
| May | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.330939E+09 | 0.155352E+09 |
| June | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.360337E+09 | 84996456.17 |
| July | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.398338E+09 | 56466734.70 |
| August | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.483462E+09 | 42619981.15 |
| September | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.450869E+09 | 0.117077E+09 |
| October | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.556956E+09 | 0.255853E+09 |
| November | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.536843E+09 | 0.319547E+09 |
| December | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.507425E+09 | 0.401454E+09 |
| Annual Sum or Average | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.540083E+10 | 0.279687E+10 |
| Minimum of Months | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.330939E+09 | 42619981.15 |
| Maximum of Months | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.556956E+09 | 0.480202E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.114189E+09 | 52148537.34 | 62039993.58 | 78904584.65 | 0.353437E+09 |
| February | 0.128338E+09 | 68792629.26 | 59545196.04 | 0.121730E+09 | 0.259743E+09 |
| March | 0.179737E+09 | 81856768.46 | 97880591.31 | 0.200980E+09 | 0.182308E+09 |
| April | 0.210070E+09 | 95890089.91 | 0.114180E+09 | 0.288964E+09 | 0.141454E+09 |
| May | 0.238402E+09 | 0.100946E+09 | 0.137456E+09 | 0.366860E+09 | 94617306.59 |
| June | 0.238599E+09 | 0.100058E+09 | 0.138541E+09 | 0.425242E+09 | 51589294.13 |
| July | 0.240418E+09 | 0.101101E+09 | 0.139317E+09 | 0.446132E+09 | 35260368.70 |
| August | 0.219749E+09 | 86999749.78 | 0.132749E+09 | 0.413392E+09 | 26417014.49 |
| September | 0.174212E+09 | 76817168.85 | 97394647.06 | 0.279128E+09 | 74533087.68 |
| October | 0.154398E+09 | 80431456.59 | 73966215.97 | 0.193728E+09 | 0.168312E+09 |
| November | 0.118901E+09 | 53715015.09 | 65186252.29 | 0.113812E+09 | 0.218262E+09 |
| December | 0.106820E+09 | 48728649.93 | 58091386.96 | 77999193.72 | 0.286078E+09 |
| Annual Sum or Average | 0.212383E+10 | 0.947485E+09 | 0.117635E+10 | 0.300687E+10 | 0.189201E+10 |
| Minimum of Months | 0.106820E+09 | 48728649.93 | 58091386.96 | 77999193.72 | 26417014.49 |
| Maximum of Months | 0.240418E+09 | 0.101101E+09 | 0.139317E+09 | 0.446132E+09 | 0.353437E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.114189E+09 | 52148537.34 | 62039993.58 | 82057038.39 | 0.338656E+09 |
| February | 0.128338E+09 | 68792629.26 | 59545196.04 | 0.128509E+09 | 0.248267E+09 |
| March | 0.179737E+09 | 81856768.46 | 97880591.31 | 0.211001E+09 | 0.171495E+09 |
| April | 0.210070E+09 | 95890089.91 | 0.114180E+09 | 0.293720E+09 | 0.138341E+09 |
| May | 0.238402E+09 | 0.100946E+09 | 0.137456E+09 | 0.367893E+09 | 94337797.50 |
| June | 0.238599E+09 | 0.100058E+09 | 0.138541E+09 | 0.425583E+09 | 51687808.19 |
| July | 0.240418E+09 | 0.101101E+09 | 0.139317E+09 | 0.446766E+09 | 35265582.63 |
| August | 0.219749E+09 | 86999749.78 | 0.132749E+09 | 0.415057E+09 | 26153413.50 |
| September | 0.174212E+09 | 76817168.85 | 97394647.06 | 0.282253E+09 | 73221354.88 |
| October | 0.154398E+09 | 80431456.59 | 73966215.97 | 0.203742E+09 | 0.158593E+09 |
| November | 0.118901E+09 | 53715015.09 | 65186252.29 | 0.125171E+09 | 0.200511E+09 |
| December | 0.106820E+09 | 48728649.93 | 58091386.96 | 83742433.13 | 0.267907E+09 |
| Annual Sum or Average | 0.212383E+10 | 0.947485E+09 | 0.117635E+10 | 0.306550E+10 | 0.180444E+10 |
| Minimum of Months | 0.106820E+09 | 48728649.93 | 58091386.96 | 82057038.39 | 26153413.50 |
| Maximum of Months | 0.240418E+09 | 0.101101E+09 | 0.139317E+09 | 0.446766E+09 | 0.338656E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78218996.00 | 0.00 | 78218996.00 | 10661083.57 | 0.581138E+09 |
| February | 78307946.70 | 0.00 | 78307946.70 | 31641136.38 | 0.423661E+09 |
| March | 0.121754E+09 | 6487.33 | 0.121748E+09 | 79662471.09 | 0.288000E+09 |
| April | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.147121E+09 | 0.225071E+09 |
| May | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.236068E+09 | 0.146312E+09 |
| June | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.340259E+09 | 78785173.18 |
| July | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.358534E+09 | 53748856.43 |
| August | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.326786E+09 | 40727462.21 |
| September | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.174543E+09 | 0.116608E+09 |
| October | 93456920.53 | 0.00 | 93456920.53 | 77487428.28 | 0.263348E+09 |
| November | 80942560.83 | 0.00 | 80942560.83 | 42420179.14 | 0.341608E+09 |
| December | 72307654.87 | 0.00 | 72307654.87 | 12146637.98 | 0.461365E+09 |
| Annual Sum or Average | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.183733E+10 | 0.302037E+10 |
| Minimum of Months | 72307654.87 | 0.00 | 72307654.87 | 10661083.57 | 40727462.21 |
| Maximum of Months | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.358534E+09 | 0.581138E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78218996.00 | 0.00 | 78218996.00 | 10652053.49 | 0.590760E+09 |
| February | 78307946.70 | 0.00 | 78307946.70 | 32692290.72 | 0.432937E+09 |
| March | 0.121754E+09 | 6487.33 | 0.121748E+09 | 82409583.60 | 0.296673E+09 |
| April | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.152849E+09 | 0.230253E+09 |
| May | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.243593E+09 | 0.147995E+09 |
| June | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.348095E+09 | 78816047.98 |
| July | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.365836E+09 | 53637404.37 |
| August | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.333617E+09 | 40438493.24 |
| September | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.179404E+09 | 0.118470E+09 |
| October | 93456920.53 | 0.00 | 93456920.53 | 80356980.09 | 0.272885E+09 |
| November | 80942560.83 | 0.00 | 80942560.83 | 42873983.08 | 0.351675E+09 |
| December | 72307654.87 | 0.00 | 72307654.87 | 11902640.40 | 0.471050E+09 |
| Annual Sum or Average | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.188428E+10 | 0.308559E+10 |
| Minimum of Months | 72307654.87 | 0.00 | 72307654.87 | 10652053.49 | 40438493.24 |
| Maximum of Months | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.365836E+09 | 0.590760E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78218996.00 | 0.00 | 78218996.00 | 10626510.17 | 0.590729E+09 |
| February | 78307946.70 | 0.00 | 78307946.70 | 32537115.95 | 0.432877E+09 |
| March | 0.121754E+09 | 6487.33 | 0.121748E+09 | 82111732.35 | 0.296258E+09 |
| April | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.152458E+09 | 0.230048E+09 |
| May | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.243241E+09 | 0.147939E+09 |
| June | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.347880E+09 | 78778000.69 |
| July | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.365743E+09 | 53602586.03 |
| August | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.333553E+09 | 40398878.13 |
| September | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.179219E+09 | 0.118412E+09 |
| October | 93456920.53 | 0.00 | 93456920.53 | 80008854.78 | 0.272703E+09 |
| November | 80942560.83 | 0.00 | 80942560.83 | 42747731.09 | 0.351387E+09 |
| December | 72307654.87 | 0.00 | 72307654.87 | 11871963.32 | 0.470962E+09 |
| Annual Sum or Average | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.188200E+10 | 0.308409E+10 |
| Minimum of Months | 72307654.87 | 0.00 | 72307654.87 | 10626510.17 | 40398878.13 |
| Maximum of Months | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.365743E+09 | 0.590729E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.470935E+09 | 0.493243E+09 |
| February | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.444835E+09 | 0.382756E+09 |
| March | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.471444E+09 | 0.292993E+09 |
| April | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.391189E+09 | 0.236485E+09 |
| May | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.338021E+09 | 0.157095E+09 |
| June | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.368133E+09 | 84998525.26 |
| July | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.405736E+09 | 56389294.87 |
| August | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.490020E+09 | 42357704.44 |
| September | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.455014E+09 | 0.118997E+09 |
| October | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.558375E+09 | 0.265967E+09 |
| November | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.534638E+09 | 0.332975E+09 |
| December | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.504777E+09 | 0.415121E+09 |
| Annual Sum or Average | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.543312E+10 | 0.287938E+10 |
| Minimum of Months | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.338021E+09 | 42357704.44 |
| Maximum of Months | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.558375E+09 | 0.493243E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.470774E+09 | 0.493114E+09 |
| February | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.444607E+09 | 0.382653E+09 |
| March | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.471156E+09 | 0.292671E+09 |
| April | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.390796E+09 | 0.236329E+09 |
| May | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.337700E+09 | 0.157024E+09 |
| June | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.367911E+09 | 84962921.06 |
| July | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.405635E+09 | 56327268.96 |
| August | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.489960E+09 | 42317732.62 |
| September | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.454866E+09 | 0.118940E+09 |
| October | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.558086E+09 | 0.265870E+09 |
| November | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.534436E+09 | 0.332797E+09 |
| December | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.504602E+09 | 0.415031E+09 |
| Annual Sum or Average | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.543053E+10 | 0.287804E+10 |
| Minimum of Months | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.337700E+09 | 42317732.62 |
| Maximum of Months | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.558086E+09 | 0.493114E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW14
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 27400002.79 | 12513253.80 | 14886748.99 | 18703768.94 | 87002557.16 |
| February | 30795183.57 | 16507071.40 | 14288112.16 | 29393254.29 | 65363071.49 |
| March | 43128711.08 | 19641864.78 | 23486846.30 | 47912814.80 | 47805224.51 |
| April | 50407240.69 | 23009217.38 | 27398023.30 | 68030118.37 | 38201666.99 |
| May | 57205624.99 | 24222414.34 | 32983210.64 | 85072844.12 | 26920985.35 |
| June | 57252776.02 | 24009259.17 | 33243516.85 | 98050095.31 | 15751539.22 |
| July | 57689323.58 | 24259634.88 | 33429688.70 | 0.102307E+09 | 11854319.98 |
| August | 52729619.27 | 20875944.08 | 31853675.19 | 94591632.67 | 9708814.80 |
| September | 41802834.34 | 18432592.34 | 23370242.00 | 64560580.65 | 21956653.44 |
| October | 37048349.99 | 19299855.40 | 17748494.59 | 46280149.28 | 44726960.09 |
| November | 28530843.08 | 12889136.51 | 15641706.57 | 27656766.25 | 55397470.13 |
| December | 25631902.65 | 11692637.90 | 13939264.76 | 18654416.87 | 71164624.03 |
| Annual Sum or Average | 0.509622E+09 | 0.227353E+09 | 0.282270E+09 | 0.701213E+09 | 0.495854E+09 |
| Minimum of Months | 25631902.65 | 11692637.90 | 13939264.76 | 18654416.87 | 9708814.80 |
| Maximum of Months | 57689323.58 | 24259634.88 | 33429688.70 | 0.102307E+09 | 87002557.16 |
Report: WindowEnergyReportMonthly
For: ENTRANCE DOOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 81604027.15 | 37267583.90 | 44336443.25 | 56985663.11 | 0.251840E+09 |
| February | 91715720.45 | 49162166.65 | 42553553.81 | 88900508.27 | 0.188692E+09 |
| March | 0.128448E+09 | 58498361.46 | 69949673.29 | 0.142125E+09 | 0.143406E+09 |
| April | 0.150125E+09 | 68527175.52 | 81598131.76 | 0.203071E+09 | 0.113196E+09 |
| May | 0.170373E+09 | 72140377.99 | 98232209.61 | 0.253434E+09 | 81689824.43 |
| June | 0.170513E+09 | 71505548.85 | 99007466.27 | 0.286743E+09 | 52705819.77 |
| July | 0.171813E+09 | 72251230.02 | 99561932.38 | 0.297435E+09 | 42024481.21 |
| August | 0.157042E+09 | 62173756.74 | 94868171.92 | 0.274074E+09 | 37292104.27 |
| September | 0.124499E+09 | 54896847.19 | 69602396.66 | 0.186098E+09 | 74820429.33 |
| October | 0.110339E+09 | 57479772.40 | 52859433.85 | 0.131050E+09 | 0.147739E+09 |
| November | 84971950.98 | 38387056.17 | 46584894.82 | 74839118.00 | 0.183603E+09 |
| December | 76338184.94 | 34823585.52 | 41514599.41 | 53036258.71 | 0.224169E+09 |
| Annual Sum or Average | 0.151778E+10 | 0.677113E+09 | 0.840669E+09 | 0.204779E+10 | 0.154118E+10 |
| Minimum of Months | 76338184.94 | 34823585.52 | 41514599.41 | 53036258.71 | 37292104.27 |
| Maximum of Months | 0.171813E+09 | 72251230.02 | 99561932.38 | 0.297435E+09 | 0.251840E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW14
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 27400002.79 | 12513253.80 | 14886748.99 | 17146241.02 | 96221639.98 |
| February | 30795183.57 | 16507071.40 | 14288112.16 | 27292031.56 | 72423395.07 |
| March | 43128711.08 | 19641864.78 | 23486846.30 | 44296949.38 | 54022284.63 |
| April | 50407240.69 | 23009217.38 | 27398023.30 | 66100511.16 | 40483380.76 |
| May | 57205624.99 | 24222414.34 | 32983210.64 | 84699686.75 | 27657315.96 |
| June | 57252776.02 | 24009259.17 | 33243516.85 | 98738872.88 | 15933887.81 |
| July | 57689323.58 | 24259634.88 | 33429688.70 | 0.103457E+09 | 11881489.74 |
| August | 52729619.27 | 20875944.08 | 31853675.19 | 95880738.13 | 9703222.51 |
| September | 41802834.34 | 18432592.34 | 23370242.00 | 64367731.65 | 22941441.47 |
| October | 37048349.99 | 19299855.40 | 17748494.59 | 43989604.69 | 49963730.70 |
| November | 28530843.08 | 12889136.51 | 15641706.57 | 24165954.33 | 63833566.84 |
| December | 25631902.65 | 11692637.90 | 13939264.76 | 16378328.13 | 81253116.14 |
| Annual Sum or Average | 0.509622E+09 | 0.227353E+09 | 0.282270E+09 | 0.686514E+09 | 0.546318E+09 |
| Minimum of Months | 25631902.65 | 11692637.90 | 13939264.76 | 16378328.13 | 9703222.51 |
| Maximum of Months | 57689323.58 | 24259634.88 | 33429688.70 | 0.103457E+09 | 96221639.98 |
Report: WindowZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 203.92 | 305.71 | 197.56 | 126.90 | 70.66 | 0.00 | 0.00 |
| February | 232.07 | 256.61 | 196.72 | 122.13 | 74.58 | 0.00 | 0.00 |
| March | 269.65 | 179.79 | 203.83 | 103.15 | 100.68 | 0.00 | 0.00 |
| April | 275.67 | 143.98 | 183.51 | 72.53 | 110.98 | 0.00 | 0.00 |
| May | 264.78 | 93.42 | 162.90 | 41.26 | 121.64 | 0.00 | 0.00 |
| June | 305.49 | 55.08 | 161.09 | 38.19 | 122.91 | 0.00 | 0.00 |
| July | 310.92 | 36.32 | 156.15 | 35.78 | 120.36 | 0.00 | 0.00 |
| August | 339.70 | 29.12 | 168.57 | 46.12 | 122.45 | 0.00 | 0.00 |
| September | 283.84 | 80.80 | 166.93 | 67.44 | 99.50 | 0.00 | 0.00 |
| October | 283.80 | 177.80 | 198.19 | 120.36 | 77.83 | 0.00 | 0.00 |
| November | 246.50 | 234.51 | 199.60 | 122.80 | 76.80 | 0.00 | 0.00 |
| December | 209.27 | 273.91 | 192.07 | 124.75 | 67.32 | 0.00 | 0.00 |
| Annual Sum or Average | 269.00 | 155.05 | 182.19 | 84.92 | 97.27 | 0.00 | 0.00 |
| Minimum of Months | 203.92 | 29.12 | 156.15 | 35.78 | 67.32 | 0.00 | 0.00 |
| Maximum of Months | 339.70 | 305.71 | 203.83 | 126.90 | 122.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 29.60 | 336.65 | 72.89 | 20.37 | 52.52 | 0.00 | 0.00 |
| February | 62.55 | 271.96 | 82.18 | 23.29 | 58.89 | 0.00 | 0.00 |
| March | 128.24 | 172.83 | 118.70 | 35.34 | 83.36 | 0.00 | 0.00 |
| April | 185.33 | 139.49 | 137.41 | 37.91 | 99.50 | 0.00 | 0.00 |
| May | 229.86 | 89.50 | 148.75 | 33.53 | 115.22 | 0.00 | 0.00 |
| June | 297.07 | 51.87 | 159.49 | 38.28 | 121.21 | 0.00 | 0.00 |
| July | 295.46 | 34.61 | 150.46 | 33.77 | 116.69 | 0.00 | 0.00 |
| August | 281.01 | 27.81 | 141.40 | 30.86 | 110.54 | 0.00 | 0.00 |
| September | 177.42 | 79.95 | 111.77 | 27.53 | 84.24 | 0.00 | 0.00 |
| October | 105.08 | 183.45 | 93.19 | 30.18 | 63.01 | 0.00 | 0.00 |
| November | 61.64 | 243.65 | 77.66 | 20.70 | 56.95 | 0.00 | 0.00 |
| December | 32.47 | 285.14 | 65.61 | 16.94 | 48.66 | 0.00 | 0.00 |
| Annual Sum or Average | 157.67 | 159.16 | 113.46 | 29.08 | 84.37 | 0.00 | 0.00 |
| Minimum of Months | 29.60 | 27.81 | 65.61 | 16.94 | 48.66 | 0.00 | 0.00 |
| Maximum of Months | 297.07 | 336.65 | 159.49 | 38.28 | 121.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 209.86 | 273.38 | 196.51 | 126.00 | 70.51 | 0.00 | 0.00 |
| February | 241.34 | 237.57 | 199.96 | 127.28 | 72.68 | 0.00 | 0.00 |
| March | 255.80 | 174.19 | 197.69 | 98.38 | 99.32 | 0.00 | 0.00 |
| April | 264.92 | 143.01 | 182.18 | 71.90 | 110.28 | 0.00 | 0.00 |
| May | 261.97 | 101.62 | 168.91 | 47.47 | 121.44 | 0.00 | 0.00 |
| June | 293.36 | 73.21 | 165.76 | 43.04 | 122.72 | 0.00 | 0.00 |
| July | 297.82 | 59.81 | 163.73 | 43.09 | 120.64 | 0.00 | 0.00 |
| August | 318.98 | 55.79 | 170.08 | 48.52 | 121.56 | 0.00 | 0.00 |
| September | 272.42 | 103.68 | 168.29 | 69.56 | 98.73 | 0.00 | 0.00 |
| October | 276.55 | 184.27 | 197.54 | 120.21 | 77.33 | 0.00 | 0.00 |
| November | 245.95 | 229.40 | 199.04 | 122.82 | 76.22 | 0.00 | 0.00 |
| December | 215.60 | 258.34 | 193.34 | 126.00 | 67.34 | 0.00 | 0.00 |
| Annual Sum or Average | 262.99 | 157.43 | 183.50 | 86.80 | 96.70 | 0.00 | 0.00 |
| Minimum of Months | 209.86 | 55.79 | 163.73 | 43.04 | 67.34 | 0.00 | 0.00 |
| Maximum of Months | 318.98 | 273.38 | 199.96 | 127.28 | 122.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 20.98 | 328.61 | 71.84 | 19.47 | 52.37 | 0.00 | 0.00 |
| February | 55.04 | 259.29 | 85.42 | 28.44 | 56.98 | 0.00 | 0.00 |
| March | 107.27 | 162.42 | 112.56 | 30.56 | 82.00 | 0.00 | 0.00 |
| April | 175.28 | 131.34 | 136.08 | 37.28 | 98.80 | 0.00 | 0.00 |
| May | 235.40 | 86.24 | 154.75 | 39.74 | 115.01 | 0.00 | 0.00 |
| June | 303.22 | 50.67 | 164.15 | 43.13 | 121.02 | 0.00 | 0.00 |
| July | 307.26 | 34.30 | 158.04 | 41.07 | 116.97 | 0.00 | 0.00 |
| August | 282.36 | 26.91 | 142.91 | 33.25 | 109.66 | 0.00 | 0.00 |
| September | 176.09 | 76.90 | 113.13 | 29.65 | 83.48 | 0.00 | 0.00 |
| October | 93.40 | 172.69 | 92.54 | 30.03 | 62.51 | 0.00 | 0.00 |
| November | 46.90 | 229.40 | 77.10 | 20.72 | 56.38 | 0.00 | 0.00 |
| December | 21.38 | 270.90 | 66.88 | 18.19 | 48.69 | 0.00 | 0.00 |
| Annual Sum or Average | 152.59 | 151.93 | 114.77 | 30.96 | 83.81 | 0.00 | 0.00 |
| Minimum of Months | 20.98 | 26.91 | 66.88 | 18.19 | 48.69 | 0.00 | 0.00 |
| Maximum of Months | 307.26 | 328.61 | 164.15 | 43.13 | 121.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 4.22 | 221.65 | 29.20 | 0.00 | 29.20 | 0.00 | 0.00 |
| February | 14.30 | 177.71 | 32.37 | 0.00 | 32.37 | 0.00 | 0.00 |
| March | 31.94 | 113.77 | 45.46 | 0.00 | 45.46 | 0.00 | 0.00 |
| April | 62.28 | 88.21 | 55.04 | 0.29 | 54.75 | 0.00 | 0.00 |
| May | 95.28 | 54.06 | 65.74 | 2.05 | 63.69 | 0.00 | 0.00 |
| June | 137.56 | 30.64 | 72.10 | 4.53 | 67.57 | 0.00 | 0.00 |
| July | 139.43 | 20.50 | 68.28 | 3.33 | 64.96 | 0.00 | 0.00 |
| August | 126.95 | 16.05 | 60.86 | 0.77 | 60.09 | 0.00 | 0.00 |
| September | 69.53 | 48.34 | 45.92 | 0.02 | 45.90 | 0.00 | 0.00 |
| October | 27.67 | 114.43 | 34.89 | 0.00 | 34.89 | 0.00 | 0.00 |
| November | 12.31 | 157.11 | 31.23 | 0.00 | 31.23 | 0.00 | 0.00 |
| December | 3.79 | 187.93 | 27.00 | 0.00 | 27.00 | 0.00 | 0.00 |
| Annual Sum or Average | 60.71 | 102.15 | 47.42 | 0.92 | 46.50 | 0.00 | 0.00 |
| Minimum of Months | 3.79 | 16.05 | 27.00 | 0.00 | 27.00 | 0.00 | 0.00 |
| Maximum of Months | 139.43 | 221.65 | 72.10 | 4.53 | 67.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 4.22 | 221.65 | 29.20 | 0.00 | 29.20 | 0.00 | 0.00 |
| February | 14.28 | 177.75 | 32.37 | 0.00 | 32.37 | 0.00 | 0.00 |
| March | 31.92 | 113.75 | 45.46 | 0.00 | 45.46 | 0.00 | 0.00 |
| April | 62.25 | 88.19 | 55.04 | 0.29 | 54.75 | 0.00 | 0.00 |
| May | 95.24 | 54.06 | 65.74 | 2.05 | 63.69 | 0.00 | 0.00 |
| June | 137.52 | 30.65 | 72.10 | 4.53 | 67.57 | 0.00 | 0.00 |
| July | 139.41 | 20.50 | 68.28 | 3.33 | 64.96 | 0.00 | 0.00 |
| August | 126.94 | 16.04 | 60.86 | 0.77 | 60.09 | 0.00 | 0.00 |
| September | 69.51 | 48.34 | 45.92 | 0.02 | 45.90 | 0.00 | 0.00 |
| October | 27.64 | 114.42 | 34.89 | 0.00 | 34.89 | 0.00 | 0.00 |
| November | 12.29 | 157.13 | 31.23 | 0.00 | 31.23 | 0.00 | 0.00 |
| December | 3.79 | 187.95 | 27.00 | 0.00 | 27.00 | 0.00 | 0.00 |
| Annual Sum or Average | 60.69 | 102.15 | 47.42 | 0.92 | 46.50 | 0.00 | 0.00 |
| Minimum of Months | 3.79 | 16.04 | 27.00 | 0.00 | 27.00 | 0.00 | 0.00 |
| Maximum of Months | 139.41 | 221.65 | 72.10 | 4.53 | 67.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 178.07 | 188.42 | 153.87 | 106.53 | 47.34 | 0.00 | 0.00 |
| February | 186.91 | 159.97 | 146.91 | 98.84 | 48.07 | 0.00 | 0.00 |
| March | 178.32 | 113.72 | 130.59 | 67.81 | 62.77 | 0.00 | 0.00 |
| April | 155.24 | 91.03 | 101.14 | 34.91 | 66.23 | 0.00 | 0.00 |
| May | 130.67 | 57.73 | 79.90 | 9.79 | 70.12 | 0.00 | 0.00 |
| June | 145.39 | 33.25 | 73.71 | 4.44 | 69.27 | 0.00 | 0.00 |
| July | 154.54 | 21.75 | 73.97 | 5.34 | 68.63 | 0.00 | 0.00 |
| August | 185.89 | 17.03 | 88.04 | 16.04 | 72.00 | 0.00 | 0.00 |
| September | 176.87 | 48.78 | 101.08 | 39.92 | 61.16 | 0.00 | 0.00 |
| October | 208.84 | 107.65 | 139.89 | 90.18 | 49.71 | 0.00 | 0.00 |
| November | 203.31 | 142.26 | 153.17 | 102.10 | 51.07 | 0.00 | 0.00 |
| December | 185.33 | 171.96 | 153.46 | 107.81 | 45.65 | 0.00 | 0.00 |
| Annual Sum or Average | 174.05 | 95.79 | 116.16 | 56.76 | 59.40 | 0.00 | 0.00 |
| Minimum of Months | 130.67 | 17.03 | 73.71 | 4.44 | 45.65 | 0.00 | 0.00 |
| Maximum of Months | 208.84 | 188.42 | 153.87 | 107.81 | 72.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 178.77 | 186.44 | 153.87 | 106.53 | 47.34 | 0.00 | 0.00 |
| February | 187.28 | 158.91 | 146.91 | 98.84 | 48.07 | 0.00 | 0.00 |
| March | 178.36 | 113.51 | 130.59 | 67.81 | 62.77 | 0.00 | 0.00 |
| April | 155.07 | 91.17 | 101.14 | 34.91 | 66.23 | 0.00 | 0.00 |
| May | 130.30 | 58.10 | 79.90 | 9.79 | 70.12 | 0.00 | 0.00 |
| June | 144.75 | 33.81 | 73.71 | 4.44 | 69.27 | 0.00 | 0.00 |
| July | 153.70 | 22.41 | 73.97 | 5.34 | 68.63 | 0.00 | 0.00 |
| August | 185.12 | 17.71 | 88.04 | 16.04 | 72.00 | 0.00 | 0.00 |
| September | 176.34 | 49.47 | 101.08 | 39.92 | 61.16 | 0.00 | 0.00 |
| October | 208.65 | 107.88 | 139.89 | 90.18 | 49.71 | 0.00 | 0.00 |
| November | 203.39 | 142.06 | 153.17 | 102.10 | 51.07 | 0.00 | 0.00 |
| December | 185.70 | 170.86 | 153.46 | 107.81 | 45.65 | 0.00 | 0.00 |
| Annual Sum or Average | 173.89 | 95.70 | 116.16 | 56.76 | 59.40 | 0.00 | 0.00 |
| Minimum of Months | 130.30 | 17.71 | 73.71 | 4.44 | 45.65 | 0.00 | 0.00 |
| Maximum of Months | 208.65 | 186.44 | 153.87 | 107.81 | 72.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 195.72 | 321.89 | 197.56 | 126.90 | 70.66 | 0.00 | 0.00 |
| February | 222.39 | 276.03 | 196.72 | 122.13 | 74.58 | 0.00 | 0.00 |
| March | 257.83 | 195.23 | 203.83 | 103.15 | 100.68 | 0.00 | 0.00 |
| April | 265.51 | 154.97 | 183.51 | 72.53 | 110.98 | 0.00 | 0.00 |
| May | 258.23 | 98.97 | 162.90 | 41.26 | 121.64 | 0.00 | 0.00 |
| June | 303.37 | 55.89 | 161.09 | 38.19 | 122.91 | 0.00 | 0.00 |
| July | 310.27 | 36.12 | 156.15 | 35.78 | 120.36 | 0.00 | 0.00 |
| August | 340.15 | 27.66 | 168.57 | 46.12 | 122.45 | 0.00 | 0.00 |
| September | 284.20 | 78.92 | 166.93 | 67.44 | 99.50 | 0.00 | 0.00 |
| October | 282.61 | 177.28 | 198.19 | 120.36 | 77.83 | 0.00 | 0.00 |
| November | 244.89 | 234.67 | 199.60 | 122.80 | 76.80 | 0.00 | 0.00 |
| December | 206.02 | 279.01 | 192.07 | 124.75 | 67.32 | 0.00 | 0.00 |
| Annual Sum or Average | 264.50 | 160.78 | 182.19 | 84.92 | 97.27 | 0.00 | 0.00 |
| Minimum of Months | 195.72 | 27.66 | 156.15 | 35.78 | 67.32 | 0.00 | 0.00 |
| Maximum of Months | 340.15 | 321.89 | 203.83 | 126.90 | 122.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 27.00 | 350.49 | 72.89 | 20.37 | 52.52 | 0.00 | 0.00 |
| February | 55.92 | 294.55 | 82.18 | 23.29 | 58.89 | 0.00 | 0.00 |
| March | 114.35 | 199.15 | 118.70 | 35.34 | 83.36 | 0.00 | 0.00 |
| April | 174.26 | 153.49 | 137.41 | 37.91 | 99.50 | 0.00 | 0.00 |
| May | 222.90 | 95.27 | 148.75 | 33.53 | 115.22 | 0.00 | 0.00 |
| June | 294.91 | 52.62 | 159.49 | 38.28 | 121.21 | 0.00 | 0.00 |
| July | 294.89 | 34.46 | 150.46 | 33.77 | 116.69 | 0.00 | 0.00 |
| August | 281.64 | 26.52 | 141.40 | 30.86 | 110.54 | 0.00 | 0.00 |
| September | 178.16 | 78.37 | 111.77 | 27.53 | 84.24 | 0.00 | 0.00 |
| October | 105.17 | 182.92 | 93.19 | 30.18 | 63.01 | 0.00 | 0.00 |
| November | 61.71 | 243.40 | 77.66 | 20.70 | 56.95 | 0.00 | 0.00 |
| December | 30.95 | 292.27 | 65.61 | 16.94 | 48.66 | 0.00 | 0.00 |
| Annual Sum or Average | 154.03 | 166.29 | 113.46 | 29.08 | 84.37 | 0.00 | 0.00 |
| Minimum of Months | 27.00 | 26.52 | 65.61 | 16.94 | 48.66 | 0.00 | 0.00 |
| Maximum of Months | 294.91 | 350.49 | 159.49 | 38.28 | 121.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 192.26 | 319.00 | 196.51 | 126.00 | 70.51 | 0.00 | 0.00 |
| February | 225.26 | 273.15 | 199.96 | 127.28 | 72.68 | 0.00 | 0.00 |
| March | 242.03 | 189.08 | 197.69 | 98.38 | 99.32 | 0.00 | 0.00 |
| April | 256.06 | 147.40 | 182.18 | 71.90 | 110.28 | 0.00 | 0.00 |
| May | 261.31 | 93.57 | 168.91 | 47.47 | 121.44 | 0.00 | 0.00 |
| June | 306.85 | 52.11 | 165.76 | 43.04 | 122.72 | 0.00 | 0.00 |
| July | 320.51 | 34.28 | 163.73 | 43.09 | 120.64 | 0.00 | 0.00 |
| August | 340.83 | 26.07 | 170.08 | 48.52 | 121.56 | 0.00 | 0.00 |
| September | 283.40 | 76.43 | 168.29 | 69.56 | 98.73 | 0.00 | 0.00 |
| October | 276.77 | 172.60 | 197.54 | 120.21 | 77.33 | 0.00 | 0.00 |
| November | 240.70 | 230.52 | 199.04 | 122.82 | 76.22 | 0.00 | 0.00 |
| December | 205.75 | 276.08 | 193.34 | 126.00 | 67.34 | 0.00 | 0.00 |
| Annual Sum or Average | 262.85 | 156.91 | 183.50 | 86.80 | 96.70 | 0.00 | 0.00 |
| Minimum of Months | 192.26 | 26.07 | 163.73 | 43.04 | 67.34 | 0.00 | 0.00 |
| Maximum of Months | 340.83 | 319.00 | 199.96 | 127.28 | 122.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 18.69 | 342.50 | 71.84 | 19.47 | 52.37 | 0.00 | 0.00 |
| February | 47.47 | 280.67 | 85.42 | 28.44 | 56.98 | 0.00 | 0.00 |
| March | 92.41 | 187.33 | 112.56 | 30.56 | 82.00 | 0.00 | 0.00 |
| April | 163.49 | 144.73 | 136.08 | 37.28 | 98.80 | 0.00 | 0.00 |
| May | 227.84 | 91.82 | 154.75 | 39.74 | 115.01 | 0.00 | 0.00 |
| June | 300.90 | 51.32 | 164.15 | 43.13 | 121.02 | 0.00 | 0.00 |
| July | 306.63 | 34.06 | 158.04 | 41.07 | 116.97 | 0.00 | 0.00 |
| August | 282.99 | 25.63 | 142.91 | 33.25 | 109.66 | 0.00 | 0.00 |
| September | 176.72 | 75.41 | 113.13 | 29.65 | 83.48 | 0.00 | 0.00 |
| October | 93.47 | 171.91 | 92.54 | 30.03 | 62.51 | 0.00 | 0.00 |
| November | 46.91 | 228.99 | 77.10 | 20.72 | 56.38 | 0.00 | 0.00 |
| December | 19.68 | 277.71 | 66.88 | 18.19 | 48.69 | 0.00 | 0.00 |
| Annual Sum or Average | 148.67 | 158.72 | 114.77 | 30.96 | 83.81 | 0.00 | 0.00 |
| Minimum of Months | 18.69 | 25.63 | 66.88 | 18.19 | 48.69 | 0.00 | 0.00 |
| Maximum of Months | 306.63 | 342.50 | 164.15 | 43.13 | 121.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 3.52 | 232.32 | 29.20 | 0.00 | 29.20 | 0.00 | 0.00 |
| February | 11.63 | 192.05 | 32.37 | 0.00 | 32.37 | 0.00 | 0.00 |
| March | 26.70 | 126.89 | 45.46 | 0.00 | 45.46 | 0.00 | 0.00 |
| April | 58.11 | 94.22 | 55.04 | 0.29 | 54.75 | 0.00 | 0.00 |
| May | 92.40 | 56.54 | 65.74 | 2.05 | 63.69 | 0.00 | 0.00 |
| June | 136.99 | 30.75 | 72.10 | 4.53 | 67.57 | 0.00 | 0.00 |
| July | 139.58 | 20.22 | 68.28 | 3.33 | 64.96 | 0.00 | 0.00 |
| August | 127.64 | 15.27 | 60.86 | 0.77 | 60.09 | 0.00 | 0.00 |
| September | 70.14 | 47.44 | 45.92 | 0.02 | 45.90 | 0.00 | 0.00 |
| October | 27.84 | 114.54 | 34.89 | 0.00 | 34.89 | 0.00 | 0.00 |
| November | 12.20 | 157.89 | 31.23 | 0.00 | 31.23 | 0.00 | 0.00 |
| December | 3.21 | 193.93 | 27.00 | 0.00 | 27.00 | 0.00 | 0.00 |
| Annual Sum or Average | 59.44 | 106.40 | 47.42 | 0.92 | 46.50 | 0.00 | 0.00 |
| Minimum of Months | 3.21 | 15.27 | 27.00 | 0.00 | 27.00 | 0.00 | 0.00 |
| Maximum of Months | 139.58 | 232.32 | 72.10 | 4.53 | 67.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 3.52 | 232.32 | 29.20 | 0.00 | 29.20 | 0.00 | 0.00 |
| February | 11.61 | 192.07 | 32.37 | 0.00 | 32.37 | 0.00 | 0.00 |
| March | 26.68 | 126.85 | 45.46 | 0.00 | 45.46 | 0.00 | 0.00 |
| April | 58.06 | 94.21 | 55.04 | 0.29 | 54.75 | 0.00 | 0.00 |
| May | 92.35 | 56.54 | 65.74 | 2.05 | 63.69 | 0.00 | 0.00 |
| June | 136.95 | 30.76 | 72.10 | 4.53 | 67.57 | 0.00 | 0.00 |
| July | 139.56 | 20.22 | 68.28 | 3.33 | 64.96 | 0.00 | 0.00 |
| August | 127.63 | 15.27 | 60.86 | 0.77 | 60.09 | 0.00 | 0.00 |
| September | 70.11 | 47.45 | 45.92 | 0.02 | 45.90 | 0.00 | 0.00 |
| October | 27.81 | 114.52 | 34.89 | 0.00 | 34.89 | 0.00 | 0.00 |
| November | 12.19 | 157.90 | 31.23 | 0.00 | 31.23 | 0.00 | 0.00 |
| December | 3.20 | 193.95 | 27.00 | 0.00 | 27.00 | 0.00 | 0.00 |
| Annual Sum or Average | 59.42 | 106.40 | 47.42 | 0.92 | 46.50 | 0.00 | 0.00 |
| Minimum of Months | 3.20 | 15.27 | 27.00 | 0.00 | 27.00 | 0.00 | 0.00 |
| Maximum of Months | 139.56 | 232.32 | 72.10 | 4.53 | 67.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 171.91 | 201.51 | 153.87 | 106.53 | 47.34 | 0.00 | 0.00 |
| February | 180.98 | 173.06 | 146.91 | 98.84 | 48.07 | 0.00 | 0.00 |
| March | 173.43 | 119.97 | 130.59 | 67.81 | 62.77 | 0.00 | 0.00 |
| April | 151.20 | 95.60 | 101.14 | 34.91 | 66.23 | 0.00 | 0.00 |
| May | 128.00 | 60.11 | 79.90 | 9.79 | 70.12 | 0.00 | 0.00 |
| June | 144.86 | 33.36 | 73.71 | 4.44 | 69.27 | 0.00 | 0.00 |
| July | 154.66 | 21.41 | 73.97 | 5.34 | 68.63 | 0.00 | 0.00 |
| August | 186.40 | 16.11 | 88.04 | 16.04 | 72.00 | 0.00 | 0.00 |
| September | 177.10 | 47.64 | 101.08 | 39.92 | 61.16 | 0.00 | 0.00 |
| October | 208.01 | 107.48 | 139.89 | 90.18 | 49.71 | 0.00 | 0.00 |
| November | 202.00 | 142.77 | 153.17 | 102.10 | 51.07 | 0.00 | 0.00 |
| December | 182.98 | 175.36 | 153.46 | 107.81 | 45.65 | 0.00 | 0.00 |
| Annual Sum or Average | 171.75 | 99.14 | 116.16 | 56.76 | 59.40 | 0.00 | 0.00 |
| Minimum of Months | 128.00 | 16.11 | 73.71 | 4.44 | 45.65 | 0.00 | 0.00 |
| Maximum of Months | 208.01 | 201.51 | 153.87 | 107.81 | 72.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 171.89 | 201.49 | 153.87 | 106.53 | 47.34 | 0.00 | 0.00 |
| February | 180.95 | 173.06 | 146.91 | 98.84 | 48.07 | 0.00 | 0.00 |
| March | 173.42 | 119.92 | 130.59 | 67.81 | 62.77 | 0.00 | 0.00 |
| April | 151.16 | 95.59 | 101.14 | 34.91 | 66.23 | 0.00 | 0.00 |
| May | 127.95 | 60.11 | 79.90 | 9.79 | 70.12 | 0.00 | 0.00 |
| June | 144.83 | 33.36 | 73.71 | 4.44 | 69.27 | 0.00 | 0.00 |
| July | 154.64 | 21.40 | 73.97 | 5.34 | 68.63 | 0.00 | 0.00 |
| August | 186.39 | 16.11 | 88.04 | 16.04 | 72.00 | 0.00 | 0.00 |
| September | 177.08 | 47.64 | 101.08 | 39.92 | 61.16 | 0.00 | 0.00 |
| October | 207.98 | 107.47 | 139.89 | 90.18 | 49.71 | 0.00 | 0.00 |
| November | 201.98 | 142.76 | 153.17 | 102.10 | 51.07 | 0.00 | 0.00 |
| December | 182.95 | 175.37 | 153.46 | 107.81 | 45.65 | 0.00 | 0.00 |
| Annual Sum or Average | 171.73 | 99.14 | 116.16 | 56.76 | 59.40 | 0.00 | 0.00 |
| Minimum of Months | 127.95 | 16.11 | 73.71 | 4.44 | 45.65 | 0.00 | 0.00 |
| Maximum of Months | 207.98 | 201.49 | 153.87 | 107.81 | 72.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 198.34 | 303.05 | 197.56 | 126.90 | 70.66 | 0.00 | 0.00 |
| February | 225.14 | 256.58 | 196.72 | 122.13 | 74.58 | 0.00 | 0.00 |
| March | 262.44 | 174.89 | 203.83 | 103.15 | 100.68 | 0.00 | 0.00 |
| April | 264.83 | 145.43 | 183.51 | 72.53 | 110.98 | 0.00 | 0.00 |
| May | 254.77 | 95.23 | 162.90 | 41.26 | 121.64 | 0.00 | 0.00 |
| June | 297.82 | 54.23 | 161.09 | 38.19 | 122.91 | 0.00 | 0.00 |
| July | 304.23 | 35.01 | 156.15 | 35.78 | 120.36 | 0.00 | 0.00 |
| August | 333.66 | 26.71 | 168.57 | 46.12 | 122.45 | 0.00 | 0.00 |
| September | 281.31 | 75.06 | 166.93 | 67.44 | 99.50 | 0.00 | 0.00 |
| October | 283.98 | 160.16 | 198.19 | 120.36 | 77.83 | 0.00 | 0.00 |
| November | 252.19 | 208.15 | 199.60 | 122.80 | 76.80 | 0.00 | 0.00 |
| December | 211.61 | 252.88 | 192.07 | 124.75 | 67.32 | 0.00 | 0.00 |
| Annual Sum or Average | 264.41 | 148.37 | 182.19 | 84.92 | 97.27 | 0.00 | 0.00 |
| Minimum of Months | 198.34 | 26.71 | 156.15 | 35.78 | 67.32 | 0.00 | 0.00 |
| Maximum of Months | 333.66 | 303.05 | 203.83 | 126.90 | 122.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 27.95 | 336.54 | 72.89 | 20.37 | 52.52 | 0.00 | 0.00 |
| February | 58.77 | 276.07 | 82.18 | 23.29 | 58.89 | 0.00 | 0.00 |
| March | 121.19 | 174.39 | 118.70 | 35.34 | 83.36 | 0.00 | 0.00 |
| April | 175.32 | 143.09 | 137.41 | 37.91 | 99.50 | 0.00 | 0.00 |
| May | 220.02 | 91.90 | 148.75 | 33.53 | 115.22 | 0.00 | 0.00 |
| June | 289.66 | 51.38 | 159.49 | 38.28 | 121.21 | 0.00 | 0.00 |
| July | 289.15 | 33.64 | 150.46 | 33.77 | 116.69 | 0.00 | 0.00 |
| August | 275.69 | 25.77 | 141.40 | 30.86 | 110.54 | 0.00 | 0.00 |
| September | 176.24 | 74.52 | 111.77 | 27.53 | 84.24 | 0.00 | 0.00 |
| October | 109.40 | 160.61 | 93.19 | 30.18 | 63.01 | 0.00 | 0.00 |
| November | 68.70 | 213.88 | 77.66 | 20.70 | 56.95 | 0.00 | 0.00 |
| December | 33.22 | 273.54 | 65.61 | 16.94 | 48.66 | 0.00 | 0.00 |
| Annual Sum or Average | 154.30 | 153.98 | 113.46 | 29.08 | 84.37 | 0.00 | 0.00 |
| Minimum of Months | 27.95 | 25.77 | 65.61 | 16.94 | 48.66 | 0.00 | 0.00 |
| Maximum of Months | 289.66 | 336.54 | 159.49 | 38.28 | 121.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 195.13 | 300.06 | 196.51 | 126.00 | 70.51 | 0.00 | 0.00 |
| February | 227.86 | 253.83 | 199.96 | 127.28 | 72.68 | 0.00 | 0.00 |
| March | 246.81 | 169.46 | 197.69 | 98.38 | 99.32 | 0.00 | 0.00 |
| April | 255.69 | 139.00 | 182.18 | 71.90 | 110.28 | 0.00 | 0.00 |
| May | 257.63 | 90.43 | 168.91 | 47.47 | 121.44 | 0.00 | 0.00 |
| June | 301.13 | 50.75 | 165.76 | 43.04 | 122.72 | 0.00 | 0.00 |
| July | 314.31 | 33.27 | 163.73 | 43.09 | 120.64 | 0.00 | 0.00 |
| August | 334.23 | 25.16 | 170.08 | 48.52 | 121.56 | 0.00 | 0.00 |
| September | 280.40 | 72.69 | 168.29 | 69.56 | 98.73 | 0.00 | 0.00 |
| October | 277.88 | 155.97 | 197.54 | 120.21 | 77.33 | 0.00 | 0.00 |
| November | 247.87 | 204.33 | 199.04 | 122.82 | 76.22 | 0.00 | 0.00 |
| December | 211.65 | 249.78 | 193.34 | 126.00 | 67.34 | 0.00 | 0.00 |
| Annual Sum or Average | 262.74 | 144.82 | 183.50 | 86.80 | 96.70 | 0.00 | 0.00 |
| Minimum of Months | 195.13 | 25.16 | 163.73 | 43.04 | 67.34 | 0.00 | 0.00 |
| Maximum of Months | 334.23 | 300.06 | 199.96 | 127.28 | 122.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 19.96 | 328.75 | 71.84 | 19.47 | 52.37 | 0.00 | 0.00 |
| February | 51.90 | 263.45 | 85.42 | 28.44 | 56.98 | 0.00 | 0.00 |
| March | 101.22 | 164.25 | 112.56 | 30.56 | 82.00 | 0.00 | 0.00 |
| April | 165.26 | 135.39 | 136.08 | 37.28 | 98.80 | 0.00 | 0.00 |
| May | 224.43 | 88.78 | 154.75 | 39.74 | 115.01 | 0.00 | 0.00 |
| June | 295.20 | 50.08 | 164.15 | 43.13 | 121.02 | 0.00 | 0.00 |
| July | 300.61 | 33.18 | 158.04 | 41.07 | 116.97 | 0.00 | 0.00 |
| August | 276.84 | 24.84 | 142.91 | 33.25 | 109.66 | 0.00 | 0.00 |
| September | 174.71 | 71.71 | 113.13 | 29.65 | 83.48 | 0.00 | 0.00 |
| October | 98.97 | 151.51 | 92.54 | 30.03 | 62.51 | 0.00 | 0.00 |
| November | 55.77 | 200.26 | 77.10 | 20.72 | 56.38 | 0.00 | 0.00 |
| December | 22.77 | 259.25 | 66.88 | 18.19 | 48.69 | 0.00 | 0.00 |
| Annual Sum or Average | 149.51 | 147.03 | 114.77 | 30.96 | 83.81 | 0.00 | 0.00 |
| Minimum of Months | 19.96 | 24.84 | 66.88 | 18.19 | 48.69 | 0.00 | 0.00 |
| Maximum of Months | 300.61 | 328.75 | 164.15 | 43.13 | 121.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 3.98 | 220.56 | 29.20 | 0.00 | 29.20 | 0.00 | 0.00 |
| February | 13.51 | 178.96 | 32.37 | 0.00 | 32.37 | 0.00 | 0.00 |
| March | 30.77 | 110.77 | 45.46 | 0.00 | 45.46 | 0.00 | 0.00 |
| April | 58.97 | 88.83 | 55.04 | 0.29 | 54.75 | 0.00 | 0.00 |
| May | 90.95 | 55.26 | 65.74 | 2.05 | 63.69 | 0.00 | 0.00 |
| June | 134.30 | 30.41 | 72.10 | 4.53 | 67.57 | 0.00 | 0.00 |
| July | 136.59 | 20.03 | 68.28 | 3.33 | 64.96 | 0.00 | 0.00 |
| August | 124.56 | 15.10 | 60.86 | 0.77 | 60.09 | 0.00 | 0.00 |
| September | 69.21 | 45.71 | 45.92 | 0.02 | 45.90 | 0.00 | 0.00 |
| October | 30.00 | 101.88 | 34.89 | 0.00 | 34.89 | 0.00 | 0.00 |
| November | 16.54 | 135.68 | 31.23 | 0.00 | 31.23 | 0.00 | 0.00 |
| December | 4.44 | 175.87 | 27.00 | 0.00 | 27.00 | 0.00 | 0.00 |
| Annual Sum or Average | 59.75 | 97.84 | 47.42 | 0.92 | 46.50 | 0.00 | 0.00 |
| Minimum of Months | 3.98 | 15.10 | 27.00 | 0.00 | 27.00 | 0.00 | 0.00 |
| Maximum of Months | 136.59 | 220.56 | 72.10 | 4.53 | 67.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 3.97 | 220.55 | 29.20 | 0.00 | 29.20 | 0.00 | 0.00 |
| February | 13.45 | 178.93 | 32.37 | 0.00 | 32.37 | 0.00 | 0.00 |
| March | 30.66 | 110.61 | 45.46 | 0.00 | 45.46 | 0.00 | 0.00 |
| April | 58.82 | 88.75 | 55.04 | 0.29 | 54.75 | 0.00 | 0.00 |
| May | 90.82 | 55.23 | 65.74 | 2.05 | 63.69 | 0.00 | 0.00 |
| June | 134.21 | 30.39 | 72.10 | 4.53 | 67.57 | 0.00 | 0.00 |
| July | 136.55 | 20.01 | 68.28 | 3.33 | 64.96 | 0.00 | 0.00 |
| August | 124.53 | 15.08 | 60.86 | 0.77 | 60.09 | 0.00 | 0.00 |
| September | 69.14 | 45.68 | 45.92 | 0.02 | 45.90 | 0.00 | 0.00 |
| October | 29.87 | 101.82 | 34.89 | 0.00 | 34.89 | 0.00 | 0.00 |
| November | 16.49 | 135.57 | 31.23 | 0.00 | 31.23 | 0.00 | 0.00 |
| December | 4.43 | 175.84 | 27.00 | 0.00 | 27.00 | 0.00 | 0.00 |
| Annual Sum or Average | 59.68 | 97.80 | 47.42 | 0.92 | 46.50 | 0.00 | 0.00 |
| Minimum of Months | 3.97 | 15.08 | 27.00 | 0.00 | 27.00 | 0.00 | 0.00 |
| Maximum of Months | 136.55 | 220.55 | 72.10 | 4.53 | 67.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 175.83 | 184.16 | 153.87 | 106.53 | 47.34 | 0.00 | 0.00 |
| February | 183.88 | 158.22 | 146.91 | 98.84 | 48.07 | 0.00 | 0.00 |
| March | 176.02 | 109.39 | 130.59 | 67.81 | 62.77 | 0.00 | 0.00 |
| April | 150.92 | 91.24 | 101.14 | 34.91 | 66.23 | 0.00 | 0.00 |
| May | 126.20 | 58.65 | 79.90 | 9.79 | 70.12 | 0.00 | 0.00 |
| June | 142.03 | 32.79 | 73.71 | 4.44 | 69.27 | 0.00 | 0.00 |
| July | 151.48 | 21.05 | 73.97 | 5.34 | 68.63 | 0.00 | 0.00 |
| August | 182.95 | 15.81 | 88.04 | 16.04 | 72.00 | 0.00 | 0.00 |
| September | 175.55 | 45.91 | 101.08 | 39.92 | 61.16 | 0.00 | 0.00 |
| October | 208.47 | 99.30 | 139.89 | 90.18 | 49.71 | 0.00 | 0.00 |
| November | 206.26 | 128.46 | 153.17 | 102.10 | 51.07 | 0.00 | 0.00 |
| December | 188.46 | 154.99 | 153.46 | 107.81 | 45.65 | 0.00 | 0.00 |
| Annual Sum or Average | 172.28 | 91.30 | 116.16 | 56.76 | 59.40 | 0.00 | 0.00 |
| Minimum of Months | 126.20 | 15.81 | 73.71 | 4.44 | 45.65 | 0.00 | 0.00 |
| Maximum of Months | 208.47 | 184.16 | 153.87 | 107.81 | 72.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 175.77 | 184.11 | 153.87 | 106.53 | 47.34 | 0.00 | 0.00 |
| February | 183.78 | 158.17 | 146.91 | 98.84 | 48.07 | 0.00 | 0.00 |
| March | 175.91 | 109.27 | 130.59 | 67.81 | 62.77 | 0.00 | 0.00 |
| April | 150.77 | 91.18 | 101.14 | 34.91 | 66.23 | 0.00 | 0.00 |
| May | 126.08 | 58.63 | 79.90 | 9.79 | 70.12 | 0.00 | 0.00 |
| June | 141.94 | 32.78 | 73.71 | 4.44 | 69.27 | 0.00 | 0.00 |
| July | 151.45 | 21.03 | 73.97 | 5.34 | 68.63 | 0.00 | 0.00 |
| August | 182.93 | 15.80 | 88.04 | 16.04 | 72.00 | 0.00 | 0.00 |
| September | 175.49 | 45.89 | 101.08 | 39.92 | 61.16 | 0.00 | 0.00 |
| October | 208.37 | 99.26 | 139.89 | 90.18 | 49.71 | 0.00 | 0.00 |
| November | 206.19 | 128.39 | 153.17 | 102.10 | 51.07 | 0.00 | 0.00 |
| December | 188.40 | 154.95 | 153.46 | 107.81 | 45.65 | 0.00 | 0.00 |
| Annual Sum or Average | 172.20 | 91.26 | 116.16 | 56.76 | 59.40 | 0.00 | 0.00 |
| Minimum of Months | 126.08 | 15.80 | 73.71 | 4.44 | 45.65 | 0.00 | 0.00 |
| Maximum of Months | 208.37 | 184.11 | 153.87 | 107.81 | 72.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 6.98 | 32.48 | 10.23 | 4.67 | 5.56 | 0.00 | 0.00 |
| February | 12.15 | 27.02 | 12.73 | 6.82 | 5.91 | 0.00 | 0.00 |
| March | 17.89 | 17.85 | 16.10 | 7.33 | 8.77 | 0.00 | 0.00 |
| April | 26.25 | 14.74 | 19.45 | 8.88 | 10.57 | 0.00 | 0.00 |
| May | 31.76 | 10.05 | 21.36 | 9.04 | 12.31 | 0.00 | 0.00 |
| June | 37.83 | 6.08 | 22.09 | 9.26 | 12.83 | 0.00 | 0.00 |
| July | 38.20 | 4.43 | 21.54 | 9.06 | 12.48 | 0.00 | 0.00 |
| August | 35.32 | 3.62 | 19.69 | 7.79 | 11.89 | 0.00 | 0.00 |
| September | 24.91 | 8.47 | 16.13 | 7.11 | 9.02 | 0.00 | 0.00 |
| October | 17.28 | 16.70 | 13.83 | 7.21 | 6.63 | 0.00 | 0.00 |
| November | 10.67 | 21.37 | 11.01 | 4.97 | 6.03 | 0.00 | 0.00 |
| December | 6.96 | 26.57 | 9.57 | 4.37 | 5.20 | 0.00 | 0.00 |
| Annual Sum or Average | 22.24 | 15.72 | 16.16 | 7.21 | 8.95 | 0.00 | 0.00 |
| Minimum of Months | 6.96 | 3.62 | 9.57 | 4.37 | 5.20 | 0.00 | 0.00 |
| Maximum of Months | 38.20 | 32.48 | 22.09 | 9.26 | 12.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 21.28 | 94.03 | 30.47 | 13.91 | 16.55 | 0.00 | 0.00 |
| February | 36.75 | 78.00 | 37.91 | 20.32 | 17.59 | 0.00 | 0.00 |
| March | 53.06 | 53.54 | 47.96 | 21.84 | 26.12 | 0.00 | 0.00 |
| April | 78.35 | 43.67 | 57.92 | 26.44 | 31.48 | 0.00 | 0.00 |
| May | 94.62 | 30.50 | 63.61 | 26.93 | 36.68 | 0.00 | 0.00 |
| June | 110.63 | 20.33 | 65.78 | 27.59 | 38.20 | 0.00 | 0.00 |
| July | 111.05 | 15.69 | 64.15 | 26.98 | 37.17 | 0.00 | 0.00 |
| August | 102.33 | 13.92 | 58.63 | 23.21 | 35.42 | 0.00 | 0.00 |
| September | 71.80 | 28.87 | 48.03 | 21.18 | 26.85 | 0.00 | 0.00 |
| October | 48.93 | 55.16 | 41.20 | 21.46 | 19.74 | 0.00 | 0.00 |
| November | 28.87 | 70.83 | 32.78 | 14.81 | 17.97 | 0.00 | 0.00 |
| December | 19.80 | 83.70 | 28.50 | 13.00 | 15.50 | 0.00 | 0.00 |
| Annual Sum or Average | 64.94 | 48.87 | 48.13 | 21.47 | 26.66 | 0.00 | 0.00 |
| Minimum of Months | 19.80 | 13.92 | 28.50 | 13.00 | 15.50 | 0.00 | 0.00 |
| Maximum of Months | 111.05 | 94.03 | 65.78 | 27.59 | 38.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 6.40 | 35.93 | 10.23 | 4.67 | 5.56 | 0.00 | 0.00 |
| February | 11.28 | 29.94 | 12.73 | 6.82 | 5.91 | 0.00 | 0.00 |
| March | 16.54 | 20.17 | 16.10 | 7.33 | 8.77 | 0.00 | 0.00 |
| April | 25.50 | 15.62 | 19.45 | 8.88 | 10.57 | 0.00 | 0.00 |
| May | 31.62 | 10.33 | 21.36 | 9.04 | 12.31 | 0.00 | 0.00 |
| June | 38.09 | 6.15 | 22.09 | 9.26 | 12.83 | 0.00 | 0.00 |
| July | 38.63 | 4.44 | 21.54 | 9.06 | 12.48 | 0.00 | 0.00 |
| August | 35.80 | 3.62 | 19.69 | 7.79 | 11.89 | 0.00 | 0.00 |
| September | 24.83 | 8.85 | 16.13 | 7.11 | 9.02 | 0.00 | 0.00 |
| October | 16.42 | 18.65 | 13.83 | 7.21 | 6.63 | 0.00 | 0.00 |
| November | 9.32 | 24.63 | 11.01 | 4.97 | 6.03 | 0.00 | 0.00 |
| December | 6.11 | 30.34 | 9.57 | 4.37 | 5.20 | 0.00 | 0.00 |
| Annual Sum or Average | 21.77 | 17.32 | 16.16 | 7.21 | 8.95 | 0.00 | 0.00 |
| Minimum of Months | 6.11 | 3.62 | 9.57 | 4.37 | 5.20 | 0.00 | 0.00 |
| Maximum of Months | 38.63 | 35.93 | 22.09 | 9.26 | 12.83 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.546190E+09 | 0.818808E+09 | 0.529140E+09 | 0.339884E+09 | 0.189256E+09 | 0.00 | 0.00 |
| February | 0.561431E+09 | 0.620791E+09 | 0.475895E+09 | 0.295461E+09 | 0.180434E+09 | 0.00 | 0.00 |
| March | 0.722224E+09 | 0.481540E+09 | 0.545944E+09 | 0.276284E+09 | 0.269660E+09 | 0.00 | 0.00 |
| April | 0.714528E+09 | 0.373193E+09 | 0.475662E+09 | 0.188002E+09 | 0.287660E+09 | 0.00 | 0.00 |
| May | 0.709188E+09 | 0.250220E+09 | 0.436322E+09 | 0.110520E+09 | 0.325801E+09 | 0.00 | 0.00 |
| June | 0.791842E+09 | 0.142777E+09 | 0.417558E+09 | 98982541.45 | 0.318575E+09 | 0.00 | 0.00 |
| July | 0.832756E+09 | 97278886.45 | 0.418220E+09 | 95846267.74 | 0.322374E+09 | 0.00 | 0.00 |
| August | 0.909850E+09 | 77984907.91 | 0.451492E+09 | 0.123534E+09 | 0.327958E+09 | 0.00 | 0.00 |
| September | 0.735703E+09 | 0.209433E+09 | 0.432688E+09 | 0.174796E+09 | 0.257891E+09 | 0.00 | 0.00 |
| October | 0.760120E+09 | 0.476226E+09 | 0.530827E+09 | 0.322370E+09 | 0.208457E+09 | 0.00 | 0.00 |
| November | 0.638939E+09 | 0.607851E+09 | 0.517367E+09 | 0.318307E+09 | 0.199059E+09 | 0.00 | 0.00 |
| December | 0.560518E+09 | 0.733629E+09 | 0.514452E+09 | 0.334140E+09 | 0.180312E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.848329E+10 | 0.488973E+10 | 0.574557E+10 | 0.267813E+10 | 0.306744E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.546190E+09 | 77984907.91 | 0.417558E+09 | 95846267.74 | 0.180312E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.909850E+09 | 0.818808E+09 | 0.545944E+09 | 0.339884E+09 | 0.327958E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 79290672.58 | 0.901680E+09 | 0.195225E+09 | 54557234.10 | 0.140667E+09 | 0.00 | 0.00 |
| February | 0.151321E+09 | 0.657930E+09 | 0.198803E+09 | 56341097.18 | 0.142462E+09 | 0.00 | 0.00 |
| March | 0.343478E+09 | 0.462896E+09 | 0.317935E+09 | 94654969.17 | 0.223280E+09 | 0.00 | 0.00 |
| April | 0.480365E+09 | 0.361560E+09 | 0.356163E+09 | 98267746.93 | 0.257895E+09 | 0.00 | 0.00 |
| May | 0.615649E+09 | 0.239712E+09 | 0.398402E+09 | 89806325.54 | 0.308595E+09 | 0.00 | 0.00 |
| June | 0.770018E+09 | 0.134457E+09 | 0.413403E+09 | 99226246.06 | 0.314177E+09 | 0.00 | 0.00 |
| July | 0.791364E+09 | 92699826.48 | 0.402985E+09 | 90447785.63 | 0.312537E+09 | 0.00 | 0.00 |
| August | 0.752646E+09 | 74495402.12 | 0.378713E+09 | 82645856.35 | 0.296067E+09 | 0.00 | 0.00 |
| September | 0.459864E+09 | 0.207239E+09 | 0.289718E+09 | 71360148.52 | 0.218358E+09 | 0.00 | 0.00 |
| October | 0.281441E+09 | 0.491346E+09 | 0.249602E+09 | 80832908.90 | 0.168769E+09 | 0.00 | 0.00 |
| November | 0.159771E+09 | 0.631539E+09 | 0.201287E+09 | 53661756.34 | 0.147626E+09 | 0.00 | 0.00 |
| December | 86974932.32 | 0.763712E+09 | 0.175727E+09 | 45383902.30 | 0.130343E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.497218E+10 | 0.501926E+10 | 0.357796E+10 | 0.917186E+09 | 0.266078E+10 | 0.00 | 0.00 |
| Minimum of Months | 79290672.58 | 74495402.12 | 0.175727E+09 | 45383902.30 | 0.130343E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.791364E+09 | 0.901680E+09 | 0.413403E+09 | 99226246.06 | 0.314177E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.562097E+09 | 0.732218E+09 | 0.526323E+09 | 0.337475E+09 | 0.188848E+09 | 0.00 | 0.00 |
| February | 0.583858E+09 | 0.574721E+09 | 0.483738E+09 | 0.307912E+09 | 0.175825E+09 | 0.00 | 0.00 |
| March | 0.685148E+09 | 0.466543E+09 | 0.529500E+09 | 0.263492E+09 | 0.266008E+09 | 0.00 | 0.00 |
| April | 0.686680E+09 | 0.370681E+09 | 0.472223E+09 | 0.186370E+09 | 0.285853E+09 | 0.00 | 0.00 |
| May | 0.701669E+09 | 0.272184E+09 | 0.452408E+09 | 0.127155E+09 | 0.325253E+09 | 0.00 | 0.00 |
| June | 0.760382E+09 | 0.189771E+09 | 0.429643E+09 | 0.111560E+09 | 0.318083E+09 | 0.00 | 0.00 |
| July | 0.797678E+09 | 0.160204E+09 | 0.438537E+09 | 0.115405E+09 | 0.323132E+09 | 0.00 | 0.00 |
| August | 0.854348E+09 | 0.149420E+09 | 0.455542E+09 | 0.129950E+09 | 0.325593E+09 | 0.00 | 0.00 |
| September | 0.706112E+09 | 0.268741E+09 | 0.436214E+09 | 0.180302E+09 | 0.255912E+09 | 0.00 | 0.00 |
| October | 0.740713E+09 | 0.493542E+09 | 0.529080E+09 | 0.321968E+09 | 0.207111E+09 | 0.00 | 0.00 |
| November | 0.637515E+09 | 0.594595E+09 | 0.515923E+09 | 0.318361E+09 | 0.197563E+09 | 0.00 | 0.00 |
| December | 0.577476E+09 | 0.691945E+09 | 0.517853E+09 | 0.337484E+09 | 0.180368E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.829368E+10 | 0.496457E+10 | 0.578698E+10 | 0.273743E+10 | 0.304955E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.562097E+09 | 0.149420E+09 | 0.429643E+09 | 0.111560E+09 | 0.175825E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.854348E+09 | 0.732218E+09 | 0.529500E+09 | 0.337484E+09 | 0.325593E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 56198587.98 | 0.880139E+09 | 0.192408E+09 | 52148537.34 | 0.140259E+09 | 0.00 | 0.00 |
| February | 0.133162E+09 | 0.627265E+09 | 0.206646E+09 | 68792629.26 | 0.137853E+09 | 0.00 | 0.00 |
| March | 0.287308E+09 | 0.435025E+09 | 0.301492E+09 | 81863255.78 | 0.219628E+09 | 0.00 | 0.00 |
| April | 0.454323E+09 | 0.340421E+09 | 0.352724E+09 | 96636091.55 | 0.256088E+09 | 0.00 | 0.00 |
| May | 0.630483E+09 | 0.230998E+09 | 0.414488E+09 | 0.106441E+09 | 0.308048E+09 | 0.00 | 0.00 |
| June | 0.785952E+09 | 0.131326E+09 | 0.425489E+09 | 0.111804E+09 | 0.313685E+09 | 0.00 | 0.00 |
| July | 0.822956E+09 | 91855905.90 | 0.423302E+09 | 0.110007E+09 | 0.313295E+09 | 0.00 | 0.00 |
| August | 0.756277E+09 | 72084254.65 | 0.382763E+09 | 89061060.90 | 0.293702E+09 | 0.00 | 0.00 |
| September | 0.456419E+09 | 0.199329E+09 | 0.293244E+09 | 76865609.84 | 0.216379E+09 | 0.00 | 0.00 |
| October | 0.250155E+09 | 0.462524E+09 | 0.247855E+09 | 80431456.59 | 0.167423E+09 | 0.00 | 0.00 |
| November | 0.121565E+09 | 0.594606E+09 | 0.199844E+09 | 53715015.09 | 0.146129E+09 | 0.00 | 0.00 |
| December | 57263777.66 | 0.725574E+09 | 0.179128E+09 | 48728649.93 | 0.130399E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.481206E+10 | 0.479115E+10 | 0.361938E+10 | 0.976494E+09 | 0.264289E+10 | 0.00 | 0.00 |
| Minimum of Months | 56198587.98 | 72084254.65 | 0.179128E+09 | 48728649.93 | 0.130399E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.822956E+09 | 0.880139E+09 | 0.425489E+09 | 0.111804E+09 | 0.313685E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 11312611.79 | 0.593660E+09 | 78218996.00 | 0.00 | 78218996.00 | 0.00 | 0.00 |
| February | 34604589.31 | 0.429915E+09 | 78307946.70 | 0.00 | 78307946.70 | 0.00 | 0.00 |
| March | 85554340.71 | 0.304708E+09 | 0.121754E+09 | 6487.33 | 0.121748E+09 | 0.00 | 0.00 |
| April | 0.161439E+09 | 0.228637E+09 | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.00 | 0.00 |
| May | 0.255204E+09 | 0.144788E+09 | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.00 | 0.00 |
| June | 0.356546E+09 | 79429196.01 | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.00 | 0.00 |
| July | 0.373445E+09 | 54896408.75 | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.00 | 0.00 |
| August | 0.340015E+09 | 42984587.26 | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.00 | 0.00 |
| September | 0.180233E+09 | 0.125300E+09 | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.00 | 0.00 |
| October | 74101655.83 | 0.306499E+09 | 93456920.53 | 0.00 | 93456920.53 | 0.00 | 0.00 |
| November | 31902094.31 | 0.407234E+09 | 80942560.83 | 0.00 | 80942560.83 | 0.00 | 0.00 |
| December | 10157830.32 | 0.503346E+09 | 72307654.87 | 0.00 | 72307654.87 | 0.00 | 0.00 |
| Annual Sum or Average | 0.191452E+10 | 0.322140E+10 | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.00 | 0.00 |
| Minimum of Months | 10157830.32 | 42984587.26 | 72307654.87 | 0.00 | 72307654.87 | 0.00 | 0.00 |
| Maximum of Months | 0.373445E+09 | 0.593660E+09 | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 11305069.12 | 0.593659E+09 | 78218996.00 | 0.00 | 78218996.00 | 0.00 | 0.00 |
| February | 34536171.52 | 0.430006E+09 | 78307946.70 | 0.00 | 78307946.70 | 0.00 | 0.00 |
| March | 85484966.32 | 0.304656E+09 | 0.121754E+09 | 6487.33 | 0.121748E+09 | 0.00 | 0.00 |
| April | 0.161350E+09 | 0.228598E+09 | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.00 | 0.00 |
| May | 0.255091E+09 | 0.144805E+09 | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.00 | 0.00 |
| June | 0.356455E+09 | 79440050.29 | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.00 | 0.00 |
| July | 0.373388E+09 | 54903881.79 | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.00 | 0.00 |
| August | 0.339990E+09 | 42972810.29 | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.00 | 0.00 |
| September | 0.180172E+09 | 0.125307E+09 | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.00 | 0.00 |
| October | 74043647.89 | 0.306472E+09 | 93456920.53 | 0.00 | 93456920.53 | 0.00 | 0.00 |
| November | 31865256.40 | 0.407275E+09 | 80942560.83 | 0.00 | 80942560.83 | 0.00 | 0.00 |
| December | 10147440.84 | 0.503400E+09 | 72307654.87 | 0.00 | 72307654.87 | 0.00 | 0.00 |
| Annual Sum or Average | 0.191383E+10 | 0.322149E+10 | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.00 | 0.00 |
| Minimum of Months | 10147440.84 | 42972810.29 | 72307654.87 | 0.00 | 72307654.87 | 0.00 | 0.00 |
| Maximum of Months | 0.373388E+09 | 0.593659E+09 | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.476947E+09 | 0.504669E+09 | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.00 | 0.00 |
| February | 0.452161E+09 | 0.386994E+09 | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.00 | 0.00 |
| March | 0.477619E+09 | 0.304594E+09 | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.00 | 0.00 |
| April | 0.402394E+09 | 0.235959E+09 | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.00 | 0.00 |
| May | 0.349999E+09 | 0.154618E+09 | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.00 | 0.00 |
| June | 0.376863E+09 | 86174044.46 | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.00 | 0.00 |
| July | 0.413932E+09 | 58267907.28 | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.00 | 0.00 |
| August | 0.497888E+09 | 45624026.42 | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.00 | 0.00 |
| September | 0.458445E+09 | 0.126434E+09 | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.00 | 0.00 |
| October | 0.559367E+09 | 0.288319E+09 | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.00 | 0.00 |
| November | 0.526990E+09 | 0.368726E+09 | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.00 | 0.00 |
| December | 0.496389E+09 | 0.460570E+09 | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.548899E+10 | 0.302095E+10 | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.349999E+09 | 45624026.42 | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.559367E+09 | 0.504669E+09 | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.478825E+09 | 0.499370E+09 | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.00 | 0.00 |
| February | 0.453075E+09 | 0.384443E+09 | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.00 | 0.00 |
| March | 0.477716E+09 | 0.304038E+09 | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.00 | 0.00 |
| April | 0.401943E+09 | 0.236315E+09 | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.00 | 0.00 |
| May | 0.349004E+09 | 0.155619E+09 | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.00 | 0.00 |
| June | 0.375191E+09 | 87645663.77 | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.00 | 0.00 |
| July | 0.411681E+09 | 60025845.54 | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.00 | 0.00 |
| August | 0.495831E+09 | 47426801.02 | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.00 | 0.00 |
| September | 0.457078E+09 | 0.128224E+09 | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.00 | 0.00 |
| October | 0.558858E+09 | 0.288947E+09 | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.00 | 0.00 |
| November | 0.527177E+09 | 0.368212E+09 | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.00 | 0.00 |
| December | 0.497373E+09 | 0.457619E+09 | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.548375E+10 | 0.301789E+10 | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.349004E+09 | 47426801.02 | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.558858E+09 | 0.499370E+09 | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.524227E+09 | 0.862161E+09 | 0.529140E+09 | 0.339884E+09 | 0.189256E+09 | 0.00 | 0.00 |
| February | 0.537998E+09 | 0.667779E+09 | 0.475895E+09 | 0.295461E+09 | 0.180434E+09 | 0.00 | 0.00 |
| March | 0.690573E+09 | 0.522910E+09 | 0.545944E+09 | 0.276284E+09 | 0.269660E+09 | 0.00 | 0.00 |
| April | 0.688196E+09 | 0.401676E+09 | 0.475662E+09 | 0.188002E+09 | 0.287660E+09 | 0.00 | 0.00 |
| May | 0.691644E+09 | 0.265095E+09 | 0.436322E+09 | 0.110520E+09 | 0.325801E+09 | 0.00 | 0.00 |
| June | 0.786336E+09 | 0.144873E+09 | 0.417558E+09 | 98982541.45 | 0.318575E+09 | 0.00 | 0.00 |
| July | 0.831036E+09 | 96736324.33 | 0.418220E+09 | 95846267.74 | 0.322374E+09 | 0.00 | 0.00 |
| August | 0.911067E+09 | 74094538.27 | 0.451492E+09 | 0.123534E+09 | 0.327958E+09 | 0.00 | 0.00 |
| September | 0.736636E+09 | 0.204549E+09 | 0.432688E+09 | 0.174796E+09 | 0.257891E+09 | 0.00 | 0.00 |
| October | 0.756952E+09 | 0.474832E+09 | 0.530827E+09 | 0.322370E+09 | 0.208457E+09 | 0.00 | 0.00 |
| November | 0.634764E+09 | 0.608256E+09 | 0.517367E+09 | 0.318307E+09 | 0.199059E+09 | 0.00 | 0.00 |
| December | 0.551807E+09 | 0.747309E+09 | 0.514452E+09 | 0.334140E+09 | 0.180312E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.834124E+10 | 0.507027E+10 | 0.574557E+10 | 0.267813E+10 | 0.306744E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.524227E+09 | 74094538.27 | 0.417558E+09 | 95846267.74 | 0.180312E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.911067E+09 | 0.862161E+09 | 0.545944E+09 | 0.339884E+09 | 0.327958E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 72323773.94 | 0.938751E+09 | 0.195225E+09 | 54557234.10 | 0.140667E+09 | 0.00 | 0.00 |
| February | 0.135274E+09 | 0.712570E+09 | 0.198803E+09 | 56341097.18 | 0.142462E+09 | 0.00 | 0.00 |
| March | 0.306278E+09 | 0.533410E+09 | 0.317935E+09 | 94654969.17 | 0.223280E+09 | 0.00 | 0.00 |
| April | 0.451670E+09 | 0.397843E+09 | 0.356163E+09 | 98267746.93 | 0.257895E+09 | 0.00 | 0.00 |
| May | 0.597017E+09 | 0.255170E+09 | 0.398402E+09 | 89806325.54 | 0.308595E+09 | 0.00 | 0.00 |
| June | 0.764404E+09 | 0.136398E+09 | 0.413403E+09 | 99226246.06 | 0.314177E+09 | 0.00 | 0.00 |
| July | 0.789830E+09 | 92290931.48 | 0.402985E+09 | 90447785.63 | 0.312537E+09 | 0.00 | 0.00 |
| August | 0.754341E+09 | 71035712.59 | 0.378713E+09 | 82645856.35 | 0.296067E+09 | 0.00 | 0.00 |
| September | 0.461780E+09 | 0.203124E+09 | 0.289718E+09 | 71360148.52 | 0.218358E+09 | 0.00 | 0.00 |
| October | 0.281678E+09 | 0.489921E+09 | 0.249602E+09 | 80832908.90 | 0.168769E+09 | 0.00 | 0.00 |
| November | 0.159948E+09 | 0.630904E+09 | 0.201287E+09 | 53661756.34 | 0.147626E+09 | 0.00 | 0.00 |
| December | 82899625.03 | 0.782811E+09 | 0.175727E+09 | 45383902.30 | 0.130343E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.485744E+10 | 0.524423E+10 | 0.357796E+10 | 0.917186E+09 | 0.266078E+10 | 0.00 | 0.00 |
| Minimum of Months | 72323773.94 | 71035712.59 | 0.175727E+09 | 45383902.30 | 0.130343E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.789830E+09 | 0.938751E+09 | 0.413403E+09 | 99226246.06 | 0.314177E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.514942E+09 | 0.854420E+09 | 0.526323E+09 | 0.337475E+09 | 0.188848E+09 | 0.00 | 0.00 |
| February | 0.544941E+09 | 0.660804E+09 | 0.483738E+09 | 0.307912E+09 | 0.175825E+09 | 0.00 | 0.00 |
| March | 0.648250E+09 | 0.506437E+09 | 0.529500E+09 | 0.263492E+09 | 0.266008E+09 | 0.00 | 0.00 |
| April | 0.663711E+09 | 0.382061E+09 | 0.472223E+09 | 0.186370E+09 | 0.285853E+09 | 0.00 | 0.00 |
| May | 0.699886E+09 | 0.250610E+09 | 0.452408E+09 | 0.127155E+09 | 0.325253E+09 | 0.00 | 0.00 |
| June | 0.795344E+09 | 0.135063E+09 | 0.429643E+09 | 0.111560E+09 | 0.318083E+09 | 0.00 | 0.00 |
| July | 0.858448E+09 | 91808588.28 | 0.438537E+09 | 0.115405E+09 | 0.323132E+09 | 0.00 | 0.00 |
| August | 0.912866E+09 | 69834397.58 | 0.455542E+09 | 0.129950E+09 | 0.325593E+09 | 0.00 | 0.00 |
| September | 0.734572E+09 | 0.198098E+09 | 0.436214E+09 | 0.180302E+09 | 0.255912E+09 | 0.00 | 0.00 |
| October | 0.741300E+09 | 0.462284E+09 | 0.529080E+09 | 0.321968E+09 | 0.207111E+09 | 0.00 | 0.00 |
| November | 0.623892E+09 | 0.597508E+09 | 0.515923E+09 | 0.318361E+09 | 0.197563E+09 | 0.00 | 0.00 |
| December | 0.551083E+09 | 0.739461E+09 | 0.517853E+09 | 0.337484E+09 | 0.180368E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.828924E+10 | 0.494839E+10 | 0.578698E+10 | 0.273743E+10 | 0.304955E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.514942E+09 | 69834397.58 | 0.429643E+09 | 0.111560E+09 | 0.175825E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.912866E+09 | 0.854420E+09 | 0.529500E+09 | 0.337484E+09 | 0.325593E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 50060335.95 | 0.917351E+09 | 0.192408E+09 | 52148537.34 | 0.140259E+09 | 0.00 | 0.00 |
| February | 0.114838E+09 | 0.678998E+09 | 0.206646E+09 | 68792629.26 | 0.137853E+09 | 0.00 | 0.00 |
| March | 0.247524E+09 | 0.501733E+09 | 0.301492E+09 | 81863255.78 | 0.219628E+09 | 0.00 | 0.00 |
| April | 0.423758E+09 | 0.375142E+09 | 0.352724E+09 | 96636091.55 | 0.256088E+09 | 0.00 | 0.00 |
| May | 0.610248E+09 | 0.245935E+09 | 0.414488E+09 | 0.106441E+09 | 0.308048E+09 | 0.00 | 0.00 |
| June | 0.779943E+09 | 0.133022E+09 | 0.425489E+09 | 0.111804E+09 | 0.313685E+09 | 0.00 | 0.00 |
| July | 0.821281E+09 | 91231806.19 | 0.423302E+09 | 0.110007E+09 | 0.313295E+09 | 0.00 | 0.00 |
| August | 0.757950E+09 | 68648008.10 | 0.382763E+09 | 89061060.90 | 0.293702E+09 | 0.00 | 0.00 |
| September | 0.458070E+09 | 0.195462E+09 | 0.293244E+09 | 76865609.84 | 0.216379E+09 | 0.00 | 0.00 |
| October | 0.250361E+09 | 0.460436E+09 | 0.247855E+09 | 80431456.59 | 0.167423E+09 | 0.00 | 0.00 |
| November | 0.121596E+09 | 0.593538E+09 | 0.199844E+09 | 53715015.09 | 0.146129E+09 | 0.00 | 0.00 |
| December | 52698709.93 | 0.743816E+09 | 0.179128E+09 | 48728649.93 | 0.130399E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.468833E+10 | 0.500531E+10 | 0.361938E+10 | 0.976494E+09 | 0.264289E+10 | 0.00 | 0.00 |
| Minimum of Months | 50060335.95 | 68648008.10 | 0.179128E+09 | 48728649.93 | 0.130399E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.821281E+09 | 0.917351E+09 | 0.425489E+09 | 0.111804E+09 | 0.313685E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 9431490.74 | 0.622247E+09 | 78218996.00 | 0.00 | 78218996.00 | 0.00 | 0.00 |
| February | 28133837.47 | 0.464596E+09 | 78307946.70 | 0.00 | 78307946.70 | 0.00 | 0.00 |
| March | 71520802.40 | 0.339858E+09 | 0.121754E+09 | 6487.33 | 0.121748E+09 | 0.00 | 0.00 |
| April | 0.150615E+09 | 0.244211E+09 | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.00 | 0.00 |
| May | 0.247474E+09 | 0.151425E+09 | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.00 | 0.00 |
| June | 0.355074E+09 | 79715948.17 | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.00 | 0.00 |
| July | 0.373846E+09 | 54162640.60 | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.00 | 0.00 |
| August | 0.341883E+09 | 40906697.37 | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.00 | 0.00 |
| September | 0.181793E+09 | 0.122973E+09 | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.00 | 0.00 |
| October | 74565707.89 | 0.306772E+09 | 93456920.53 | 0.00 | 93456920.53 | 0.00 | 0.00 |
| November | 31634809.41 | 0.409246E+09 | 80942560.83 | 0.00 | 80942560.83 | 0.00 | 0.00 |
| December | 8588437.83 | 0.519427E+09 | 72307654.87 | 0.00 | 72307654.87 | 0.00 | 0.00 |
| Annual Sum or Average | 0.187456E+10 | 0.335554E+10 | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.00 | 0.00 |
| Minimum of Months | 8588437.83 | 40906697.37 | 72307654.87 | 0.00 | 72307654.87 | 0.00 | 0.00 |
| Maximum of Months | 0.373846E+09 | 0.622247E+09 | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 9420343.75 | 0.622243E+09 | 78218996.00 | 0.00 | 78218996.00 | 0.00 | 0.00 |
| February | 28075527.73 | 0.464653E+09 | 78307946.70 | 0.00 | 78307946.70 | 0.00 | 0.00 |
| March | 71463067.96 | 0.339763E+09 | 0.121754E+09 | 6487.33 | 0.121748E+09 | 0.00 | 0.00 |
| April | 0.150499E+09 | 0.244198E+09 | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.00 | 0.00 |
| May | 0.247338E+09 | 0.151434E+09 | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.00 | 0.00 |
| June | 0.354977E+09 | 79719978.60 | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.00 | 0.00 |
| July | 0.373802E+09 | 54154407.85 | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.00 | 0.00 |
| August | 0.341854E+09 | 40893498.34 | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.00 | 0.00 |
| September | 0.181718E+09 | 0.122979E+09 | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.00 | 0.00 |
| October | 74494224.52 | 0.306723E+09 | 93456920.53 | 0.00 | 93456920.53 | 0.00 | 0.00 |
| November | 31586103.83 | 0.409288E+09 | 80942560.83 | 0.00 | 80942560.83 | 0.00 | 0.00 |
| December | 8578921.54 | 0.519473E+09 | 72307654.87 | 0.00 | 72307654.87 | 0.00 | 0.00 |
| Annual Sum or Average | 0.187381E+10 | 0.335552E+10 | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.00 | 0.00 |
| Minimum of Months | 8578921.54 | 40893498.34 | 72307654.87 | 0.00 | 72307654.87 | 0.00 | 0.00 |
| Maximum of Months | 0.373802E+09 | 0.622243E+09 | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.460432E+09 | 0.539725E+09 | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.00 | 0.00 |
| February | 0.437825E+09 | 0.418656E+09 | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.00 | 0.00 |
| March | 0.464519E+09 | 0.321316E+09 | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.00 | 0.00 |
| April | 0.391909E+09 | 0.247802E+09 | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.00 | 0.00 |
| May | 0.342823E+09 | 0.161007E+09 | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.00 | 0.00 |
| June | 0.375486E+09 | 86456606.10 | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.00 | 0.00 |
| July | 0.414232E+09 | 57338732.01 | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.00 | 0.00 |
| August | 0.499266E+09 | 43161641.18 | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.00 | 0.00 |
| September | 0.459048E+09 | 0.123493E+09 | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.00 | 0.00 |
| October | 0.557121E+09 | 0.287862E+09 | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.00 | 0.00 |
| November | 0.523575E+09 | 0.370051E+09 | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.00 | 0.00 |
| December | 0.490087E+09 | 0.469695E+09 | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.541632E+10 | 0.312656E+10 | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.342823E+09 | 43161641.18 | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.557121E+09 | 0.539725E+09 | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.460386E+09 | 0.539678E+09 | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.00 | 0.00 |
| February | 0.437749E+09 | 0.418662E+09 | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.00 | 0.00 |
| March | 0.464489E+09 | 0.321200E+09 | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.00 | 0.00 |
| April | 0.391805E+09 | 0.247777E+09 | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.00 | 0.00 |
| May | 0.342703E+09 | 0.161011E+09 | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.00 | 0.00 |
| June | 0.375389E+09 | 86462637.31 | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.00 | 0.00 |
| July | 0.414191E+09 | 57318708.97 | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.00 | 0.00 |
| August | 0.499238E+09 | 43147349.79 | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.00 | 0.00 |
| September | 0.458988E+09 | 0.123491E+09 | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.00 | 0.00 |
| October | 0.557046E+09 | 0.287843E+09 | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.00 | 0.00 |
| November | 0.523537E+09 | 0.370025E+09 | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.00 | 0.00 |
| December | 0.490018E+09 | 0.469720E+09 | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.541554E+10 | 0.312634E+10 | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.342703E+09 | 43147349.79 | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.557046E+09 | 0.539678E+09 | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.531234E+09 | 0.811679E+09 | 0.529140E+09 | 0.339884E+09 | 0.189256E+09 | 0.00 | 0.00 |
| February | 0.544656E+09 | 0.620729E+09 | 0.475895E+09 | 0.295461E+09 | 0.180434E+09 | 0.00 | 0.00 |
| March | 0.702914E+09 | 0.468418E+09 | 0.545944E+09 | 0.276284E+09 | 0.269660E+09 | 0.00 | 0.00 |
| April | 0.686429E+09 | 0.376962E+09 | 0.475662E+09 | 0.188002E+09 | 0.287660E+09 | 0.00 | 0.00 |
| May | 0.682375E+09 | 0.255054E+09 | 0.436322E+09 | 0.110520E+09 | 0.325801E+09 | 0.00 | 0.00 |
| June | 0.771960E+09 | 0.140565E+09 | 0.417558E+09 | 98982541.45 | 0.318575E+09 | 0.00 | 0.00 |
| July | 0.814844E+09 | 93780886.88 | 0.418220E+09 | 95846267.74 | 0.322374E+09 | 0.00 | 0.00 |
| August | 0.893685E+09 | 71549407.52 | 0.451492E+09 | 0.123534E+09 | 0.327958E+09 | 0.00 | 0.00 |
| September | 0.729157E+09 | 0.194551E+09 | 0.432688E+09 | 0.174796E+09 | 0.257891E+09 | 0.00 | 0.00 |
| October | 0.760613E+09 | 0.428969E+09 | 0.530827E+09 | 0.322370E+09 | 0.208457E+09 | 0.00 | 0.00 |
| November | 0.653688E+09 | 0.539512E+09 | 0.517367E+09 | 0.318307E+09 | 0.199059E+09 | 0.00 | 0.00 |
| December | 0.566767E+09 | 0.677309E+09 | 0.514452E+09 | 0.334140E+09 | 0.180312E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.833832E+10 | 0.467908E+10 | 0.574557E+10 | 0.267813E+10 | 0.306744E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.531234E+09 | 71549407.52 | 0.417558E+09 | 95846267.74 | 0.180312E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.893685E+09 | 0.811679E+09 | 0.545944E+09 | 0.339884E+09 | 0.327958E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 74848224.29 | 0.901386E+09 | 0.195225E+09 | 54557234.10 | 0.140667E+09 | 0.00 | 0.00 |
| February | 0.142180E+09 | 0.667878E+09 | 0.198803E+09 | 56341097.18 | 0.142462E+09 | 0.00 | 0.00 |
| March | 0.324589E+09 | 0.467080E+09 | 0.317935E+09 | 94654969.17 | 0.223280E+09 | 0.00 | 0.00 |
| April | 0.454417E+09 | 0.370878E+09 | 0.356163E+09 | 98267746.93 | 0.257895E+09 | 0.00 | 0.00 |
| May | 0.589292E+09 | 0.246139E+09 | 0.398402E+09 | 89806325.54 | 0.308595E+09 | 0.00 | 0.00 |
| June | 0.750788E+09 | 0.133166E+09 | 0.413403E+09 | 99226246.06 | 0.314177E+09 | 0.00 | 0.00 |
| July | 0.774469E+09 | 90109171.78 | 0.402985E+09 | 90447785.63 | 0.312537E+09 | 0.00 | 0.00 |
| August | 0.738414E+09 | 69017716.46 | 0.378713E+09 | 82645856.35 | 0.296067E+09 | 0.00 | 0.00 |
| September | 0.456802E+09 | 0.193162E+09 | 0.289718E+09 | 71360148.52 | 0.218358E+09 | 0.00 | 0.00 |
| October | 0.293005E+09 | 0.430166E+09 | 0.249602E+09 | 80832908.90 | 0.168769E+09 | 0.00 | 0.00 |
| November | 0.178067E+09 | 0.554382E+09 | 0.201287E+09 | 53661756.34 | 0.147626E+09 | 0.00 | 0.00 |
| December | 88975903.93 | 0.732651E+09 | 0.175727E+09 | 45383902.30 | 0.130343E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.486585E+10 | 0.485601E+10 | 0.357796E+10 | 0.917186E+09 | 0.266078E+10 | 0.00 | 0.00 |
| Minimum of Months | 74848224.29 | 69017716.46 | 0.175727E+09 | 45383902.30 | 0.130343E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.774469E+09 | 0.901386E+09 | 0.413403E+09 | 99226246.06 | 0.314177E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.522646E+09 | 0.803693E+09 | 0.526323E+09 | 0.337475E+09 | 0.188848E+09 | 0.00 | 0.00 |
| February | 0.551232E+09 | 0.614061E+09 | 0.483738E+09 | 0.307912E+09 | 0.175825E+09 | 0.00 | 0.00 |
| March | 0.661066E+09 | 0.453883E+09 | 0.529500E+09 | 0.263492E+09 | 0.266008E+09 | 0.00 | 0.00 |
| April | 0.662759E+09 | 0.360282E+09 | 0.472223E+09 | 0.186370E+09 | 0.285853E+09 | 0.00 | 0.00 |
| May | 0.690047E+09 | 0.242217E+09 | 0.452408E+09 | 0.127155E+09 | 0.325253E+09 | 0.00 | 0.00 |
| June | 0.780528E+09 | 0.131535E+09 | 0.429643E+09 | 0.111560E+09 | 0.318083E+09 | 0.00 | 0.00 |
| July | 0.841839E+09 | 89097142.43 | 0.438537E+09 | 0.115405E+09 | 0.323132E+09 | 0.00 | 0.00 |
| August | 0.895210E+09 | 67392625.60 | 0.455542E+09 | 0.129950E+09 | 0.325593E+09 | 0.00 | 0.00 |
| September | 0.726800E+09 | 0.188414E+09 | 0.436214E+09 | 0.180302E+09 | 0.255912E+09 | 0.00 | 0.00 |
| October | 0.744263E+09 | 0.417745E+09 | 0.529080E+09 | 0.321968E+09 | 0.207111E+09 | 0.00 | 0.00 |
| November | 0.642477E+09 | 0.529631E+09 | 0.515923E+09 | 0.318361E+09 | 0.197563E+09 | 0.00 | 0.00 |
| December | 0.566893E+09 | 0.669001E+09 | 0.517853E+09 | 0.337484E+09 | 0.180368E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.828576E+10 | 0.456695E+10 | 0.578698E+10 | 0.273743E+10 | 0.304955E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.522646E+09 | 67392625.60 | 0.429643E+09 | 0.111560E+09 | 0.175825E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.895210E+09 | 0.803693E+09 | 0.529500E+09 | 0.337484E+09 | 0.325593E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 53460452.30 | 0.880536E+09 | 0.192408E+09 | 52148537.34 | 0.140259E+09 | 0.00 | 0.00 |
| February | 0.125558E+09 | 0.637336E+09 | 0.206646E+09 | 68792629.26 | 0.137853E+09 | 0.00 | 0.00 |
| March | 0.271100E+09 | 0.439932E+09 | 0.301492E+09 | 81863255.78 | 0.219628E+09 | 0.00 | 0.00 |
| April | 0.428357E+09 | 0.350926E+09 | 0.352724E+09 | 96636091.55 | 0.256088E+09 | 0.00 | 0.00 |
| May | 0.601108E+09 | 0.237797E+09 | 0.414488E+09 | 0.106441E+09 | 0.308048E+09 | 0.00 | 0.00 |
| June | 0.765164E+09 | 0.129795E+09 | 0.425489E+09 | 0.111804E+09 | 0.313685E+09 | 0.00 | 0.00 |
| July | 0.805144E+09 | 88858584.74 | 0.423302E+09 | 0.110007E+09 | 0.313295E+09 | 0.00 | 0.00 |
| August | 0.741485E+09 | 66523516.37 | 0.382763E+09 | 89061060.90 | 0.293702E+09 | 0.00 | 0.00 |
| September | 0.452839E+09 | 0.185873E+09 | 0.293244E+09 | 76865609.84 | 0.216379E+09 | 0.00 | 0.00 |
| October | 0.265082E+09 | 0.405794E+09 | 0.247855E+09 | 80431456.59 | 0.167423E+09 | 0.00 | 0.00 |
| November | 0.144552E+09 | 0.519080E+09 | 0.199844E+09 | 53715015.09 | 0.146129E+09 | 0.00 | 0.00 |
| December | 60999016.22 | 0.694382E+09 | 0.179128E+09 | 48728649.93 | 0.130399E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.471485E+10 | 0.463683E+10 | 0.361938E+10 | 0.976494E+09 | 0.264289E+10 | 0.00 | 0.00 |
| Minimum of Months | 53460452.30 | 66523516.37 | 0.179128E+09 | 48728649.93 | 0.130399E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.805144E+09 | 0.880536E+09 | 0.425489E+09 | 0.111804E+09 | 0.313685E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 10652053.49 | 0.590760E+09 | 78218996.00 | 0.00 | 78218996.00 | 0.00 | 0.00 |
| February | 32692290.72 | 0.432937E+09 | 78307946.70 | 0.00 | 78307946.70 | 0.00 | 0.00 |
| March | 82409583.60 | 0.296673E+09 | 0.121754E+09 | 6487.33 | 0.121748E+09 | 0.00 | 0.00 |
| April | 0.152849E+09 | 0.230253E+09 | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.00 | 0.00 |
| May | 0.243593E+09 | 0.147995E+09 | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.00 | 0.00 |
| June | 0.348095E+09 | 78816047.98 | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.00 | 0.00 |
| July | 0.365836E+09 | 53637404.37 | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.00 | 0.00 |
| August | 0.333617E+09 | 40438493.24 | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.00 | 0.00 |
| September | 0.179404E+09 | 0.118470E+09 | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.00 | 0.00 |
| October | 80356980.09 | 0.272885E+09 | 93456920.53 | 0.00 | 93456920.53 | 0.00 | 0.00 |
| November | 42873983.08 | 0.351675E+09 | 80942560.83 | 0.00 | 80942560.83 | 0.00 | 0.00 |
| December | 11902640.40 | 0.471050E+09 | 72307654.87 | 0.00 | 72307654.87 | 0.00 | 0.00 |
| Annual Sum or Average | 0.188428E+10 | 0.308559E+10 | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.00 | 0.00 |
| Minimum of Months | 10652053.49 | 40438493.24 | 72307654.87 | 0.00 | 72307654.87 | 0.00 | 0.00 |
| Maximum of Months | 0.365836E+09 | 0.590760E+09 | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 10626510.17 | 0.590729E+09 | 78218996.00 | 0.00 | 78218996.00 | 0.00 | 0.00 |
| February | 32537115.95 | 0.432877E+09 | 78307946.70 | 0.00 | 78307946.70 | 0.00 | 0.00 |
| March | 82111732.35 | 0.296258E+09 | 0.121754E+09 | 6487.33 | 0.121748E+09 | 0.00 | 0.00 |
| April | 0.152458E+09 | 0.230048E+09 | 0.142653E+09 | 746001.63 | 0.141907E+09 | 0.00 | 0.00 |
| May | 0.243241E+09 | 0.147939E+09 | 0.176086E+09 | 5494857.08 | 0.170591E+09 | 0.00 | 0.00 |
| June | 0.347880E+09 | 78778000.69 | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.00 | 0.00 |
| July | 0.365743E+09 | 53602586.03 | 0.182884E+09 | 8905736.99 | 0.173978E+09 | 0.00 | 0.00 |
| August | 0.333553E+09 | 40398878.13 | 0.163014E+09 | 2061311.12 | 0.160953E+09 | 0.00 | 0.00 |
| September | 0.179219E+09 | 0.118412E+09 | 0.119033E+09 | 48440.99 | 0.118984E+09 | 0.00 | 0.00 |
| October | 80008854.78 | 0.272703E+09 | 93456920.53 | 0.00 | 93456920.53 | 0.00 | 0.00 |
| November | 42747731.09 | 0.351387E+09 | 80942560.83 | 0.00 | 80942560.83 | 0.00 | 0.00 |
| December | 11871963.32 | 0.470962E+09 | 72307654.87 | 0.00 | 72307654.87 | 0.00 | 0.00 |
| Annual Sum or Average | 0.188200E+10 | 0.308409E+10 | 0.149555E+10 | 29008850.03 | 0.146654E+10 | 0.00 | 0.00 |
| Minimum of Months | 10626510.17 | 40398878.13 | 72307654.87 | 0.00 | 72307654.87 | 0.00 | 0.00 |
| Maximum of Months | 0.365743E+09 | 0.590729E+09 | 0.186890E+09 | 11746014.89 | 0.175144E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.470935E+09 | 0.493243E+09 | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.00 | 0.00 |
| February | 0.444835E+09 | 0.382756E+09 | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.00 | 0.00 |
| March | 0.471444E+09 | 0.292993E+09 | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.00 | 0.00 |
| April | 0.391189E+09 | 0.236485E+09 | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.00 | 0.00 |
| May | 0.338021E+09 | 0.157095E+09 | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.00 | 0.00 |
| June | 0.368133E+09 | 84998525.26 | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.00 | 0.00 |
| July | 0.405736E+09 | 56389294.87 | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.00 | 0.00 |
| August | 0.490020E+09 | 42357704.44 | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.00 | 0.00 |
| September | 0.455014E+09 | 0.118997E+09 | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.00 | 0.00 |
| October | 0.558375E+09 | 0.265967E+09 | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.00 | 0.00 |
| November | 0.534638E+09 | 0.332975E+09 | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.00 | 0.00 |
| December | 0.504777E+09 | 0.415121E+09 | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.543312E+10 | 0.287938E+10 | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.338021E+09 | 42357704.44 | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.558375E+09 | 0.493243E+09 | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.470774E+09 | 0.493114E+09 | 0.412134E+09 | 0.285326E+09 | 0.126808E+09 | 0.00 | 0.00 |
| February | 0.444607E+09 | 0.382653E+09 | 0.355400E+09 | 0.239120E+09 | 0.116280E+09 | 0.00 | 0.00 |
| March | 0.471156E+09 | 0.292671E+09 | 0.349763E+09 | 0.181635E+09 | 0.168128E+09 | 0.00 | 0.00 |
| April | 0.390796E+09 | 0.236329E+09 | 0.262153E+09 | 90480274.67 | 0.171672E+09 | 0.00 | 0.00 |
| May | 0.337700E+09 | 0.157024E+09 | 0.214006E+09 | 26209001.18 | 0.187797E+09 | 0.00 | 0.00 |
| June | 0.367911E+09 | 84962921.06 | 0.191044E+09 | 11502310.29 | 0.179542E+09 | 0.00 | 0.00 |
| July | 0.405635E+09 | 56327268.96 | 0.198119E+09 | 14304219.10 | 0.183815E+09 | 0.00 | 0.00 |
| August | 0.489960E+09 | 42317732.62 | 0.235793E+09 | 42949951.49 | 0.192844E+09 | 0.00 | 0.00 |
| September | 0.454866E+09 | 0.118940E+09 | 0.262002E+09 | 0.103485E+09 | 0.158517E+09 | 0.00 | 0.00 |
| October | 0.558086E+09 | 0.265870E+09 | 0.374682E+09 | 0.241537E+09 | 0.133145E+09 | 0.00 | 0.00 |
| November | 0.534436E+09 | 0.332797E+09 | 0.397022E+09 | 0.264646E+09 | 0.132376E+09 | 0.00 | 0.00 |
| December | 0.504602E+09 | 0.415031E+09 | 0.411033E+09 | 0.288756E+09 | 0.122277E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.543053E+10 | 0.287804E+10 | 0.366315E+10 | 0.178995E+10 | 0.187320E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.337700E+09 | 42317732.62 | 0.191044E+09 | 11502310.29 | 0.116280E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.558086E+09 | 0.493114E+09 | 0.412134E+09 | 0.288756E+09 | 0.192844E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 18703768.94 | 87002557.16 | 27400002.79 | 12513253.80 | 14886748.99 | 0.00 | 0.00 |
| February | 29393254.29 | 65363071.49 | 30795183.57 | 16507071.40 | 14288112.16 | 0.00 | 0.00 |
| March | 47912814.80 | 47805224.51 | 43128711.08 | 19641864.78 | 23486846.30 | 0.00 | 0.00 |
| April | 68030118.37 | 38201666.99 | 50407240.69 | 23009217.38 | 27398023.30 | 0.00 | 0.00 |
| May | 85072844.12 | 26920985.35 | 57205624.99 | 24222414.34 | 32983210.64 | 0.00 | 0.00 |
| June | 98050095.31 | 15751539.22 | 57252776.02 | 24009259.17 | 33243516.85 | 0.00 | 0.00 |
| July | 0.102307E+09 | 11854319.98 | 57689323.58 | 24259634.88 | 33429688.70 | 0.00 | 0.00 |
| August | 94591632.67 | 9708814.80 | 52729619.27 | 20875944.08 | 31853675.19 | 0.00 | 0.00 |
| September | 64560580.65 | 21956653.44 | 41802834.34 | 18432592.34 | 23370242.00 | 0.00 | 0.00 |
| October | 46280149.28 | 44726960.09 | 37048349.99 | 19299855.40 | 17748494.59 | 0.00 | 0.00 |
| November | 27656766.25 | 55397470.13 | 28530843.08 | 12889136.51 | 15641706.57 | 0.00 | 0.00 |
| December | 18654416.87 | 71164624.03 | 25631902.65 | 11692637.90 | 13939264.76 | 0.00 | 0.00 |
| Annual Sum or Average | 0.701213E+09 | 0.495854E+09 | 0.509622E+09 | 0.227353E+09 | 0.282270E+09 | 0.00 | 0.00 |
| Minimum of Months | 18654416.87 | 9708814.80 | 25631902.65 | 11692637.90 | 13939264.76 | 0.00 | 0.00 |
| Maximum of Months | 0.102307E+09 | 87002557.16 | 57689323.58 | 24259634.88 | 33429688.70 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 56985663.11 | 0.251840E+09 | 81604027.15 | 37267583.90 | 44336443.25 | 0.00 | 0.00 |
| February | 88900508.27 | 0.188692E+09 | 91715720.45 | 49162166.65 | 42553553.81 | 0.00 | 0.00 |
| March | 0.142125E+09 | 0.143406E+09 | 0.128448E+09 | 58498361.46 | 69949673.29 | 0.00 | 0.00 |
| April | 0.203071E+09 | 0.113196E+09 | 0.150125E+09 | 68527175.52 | 81598131.76 | 0.00 | 0.00 |
| May | 0.253434E+09 | 81689824.43 | 0.170373E+09 | 72140377.99 | 98232209.61 | 0.00 | 0.00 |
| June | 0.286743E+09 | 52705819.77 | 0.170513E+09 | 71505548.85 | 99007466.27 | 0.00 | 0.00 |
| July | 0.297435E+09 | 42024481.21 | 0.171813E+09 | 72251230.02 | 99561932.38 | 0.00 | 0.00 |
| August | 0.274074E+09 | 37292104.27 | 0.157042E+09 | 62173756.74 | 94868171.92 | 0.00 | 0.00 |
| September | 0.186098E+09 | 74820429.33 | 0.124499E+09 | 54896847.19 | 69602396.66 | 0.00 | 0.00 |
| October | 0.131050E+09 | 0.147739E+09 | 0.110339E+09 | 57479772.40 | 52859433.85 | 0.00 | 0.00 |
| November | 74839118.00 | 0.183603E+09 | 84971950.98 | 38387056.17 | 46584894.82 | 0.00 | 0.00 |
| December | 53036258.71 | 0.224169E+09 | 76338184.94 | 34823585.52 | 41514599.41 | 0.00 | 0.00 |
| Annual Sum or Average | 0.204779E+10 | 0.154118E+10 | 0.151778E+10 | 0.677113E+09 | 0.840669E+09 | 0.00 | 0.00 |
| Minimum of Months | 53036258.71 | 37292104.27 | 76338184.94 | 34823585.52 | 41514599.41 | 0.00 | 0.00 |
| Maximum of Months | 0.297435E+09 | 0.251840E+09 | 0.171813E+09 | 72251230.02 | 99561932.38 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 17146241.02 | 96221639.98 | 27400002.79 | 12513253.80 | 14886748.99 | 0.00 | 0.00 |
| February | 27292031.56 | 72423395.07 | 30795183.57 | 16507071.40 | 14288112.16 | 0.00 | 0.00 |
| March | 44296949.38 | 54022284.63 | 43128711.08 | 19641864.78 | 23486846.30 | 0.00 | 0.00 |
| April | 66100511.16 | 40483380.76 | 50407240.69 | 23009217.38 | 27398023.30 | 0.00 | 0.00 |
| May | 84699686.75 | 27657315.96 | 57205624.99 | 24222414.34 | 32983210.64 | 0.00 | 0.00 |
| June | 98738872.88 | 15933887.81 | 57252776.02 | 24009259.17 | 33243516.85 | 0.00 | 0.00 |
| July | 0.103457E+09 | 11881489.74 | 57689323.58 | 24259634.88 | 33429688.70 | 0.00 | 0.00 |
| August | 95880738.13 | 9703222.51 | 52729619.27 | 20875944.08 | 31853675.19 | 0.00 | 0.00 |
| September | 64367731.65 | 22941441.47 | 41802834.34 | 18432592.34 | 23370242.00 | 0.00 | 0.00 |
| October | 43989604.69 | 49963730.70 | 37048349.99 | 19299855.40 | 17748494.59 | 0.00 | 0.00 |
| November | 24165954.33 | 63833566.84 | 28530843.08 | 12889136.51 | 15641706.57 | 0.00 | 0.00 |
| December | 16378328.13 | 81253116.14 | 25631902.65 | 11692637.90 | 13939264.76 | 0.00 | 0.00 |
| Annual Sum or Average | 0.686514E+09 | 0.546318E+09 | 0.509622E+09 | 0.227353E+09 | 0.282270E+09 | 0.00 | 0.00 |
| Minimum of Months | 16378328.13 | 9703222.51 | 25631902.65 | 11692637.90 | 13939264.76 | 0.00 | 0.00 |
| Maximum of Months | 0.103457E+09 | 96221639.98 | 57689323.58 | 24259634.88 | 33429688.70 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
| February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
| March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
| April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
| May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
| June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
| July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
| August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
| September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
| October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
| November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
| December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
| Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
| Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
| Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
| February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
| March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
| April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
| May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
| June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
| July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
| August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
| September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
| October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
| November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
| December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
| Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
| February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
| March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
| April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
| May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
| June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
| July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
| August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
| September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
| October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
| November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
| December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
| Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
| February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
| March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
| April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
| May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
| June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
| July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
| August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
| September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
| October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
| November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
| December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
| Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
| February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
| March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
| April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
| May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
| June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
| July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
| August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
| September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
| October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
| November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
| December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
| Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.318450E+11 | -0.307896E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.105531E+10 | 59.95 | 0.00 | 0.00 |
| February | 0.287889E+11 | -0.278642E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -924771212.4 | 59.95 | 0.00 | 0.00 |
| March | 0.307961E+11 | -0.298381E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -957952066.4 | 59.95 | 0.00 | 0.00 |
| April | 0.279590E+11 | -0.270634E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -895524166.3 | 59.95 | 0.00 | 0.00 |
| May | 0.266386E+11 | -0.257412E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -897415883.6 | 59.95 | 0.00 | 0.00 |
| June | 0.238438E+11 | -0.229976E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -846180514.8 | 59.95 | 0.00 | 0.00 |
| July | 0.234381E+11 | -0.225717E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -866458209.0 | 59.95 | 0.00 | 0.00 |
| August | 0.233511E+11 | -0.224870E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -864074494.8 | 59.95 | 0.00 | 0.00 |
| September | 0.236268E+11 | -0.227763E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -850558004.4 | 59.95 | 0.00 | 0.00 |
| October | 0.263445E+11 | -0.254304E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -914126956.5 | 59.95 | 0.00 | 0.00 |
| November | 0.276806E+11 | -0.267635E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -917168057.0 | 59.95 | 0.00 | 0.00 |
| December | 0.306185E+11 | -0.296130E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100546E+10 | 59.95 | 0.00 | 0.00 |
| Annual Sum or Average | 0.324931E+12 | -0.313936E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.109950E+11 | 59.95 | 0.00 | 0.00 |
| Minimum of Months | 0.233511E+11 | -0.307896E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.105531E+10 | 59.95 | 0.00 | 0.00 |
| Maximum of Months | 0.318450E+11 | -0.224870E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -846180514.8 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 351.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 407.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 411.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 390.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 293.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4071.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.573604E+09 | 986.79 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.344985E+09 | 1187.73 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 9822822.31 | 252.01 | 26-DEC-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.928412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.573604E+09 | 1187.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.114159E+10 | 1088.03 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.688527E+09 | 1311.09 | 12-FEB-08:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 12753719.35 | 213.16 | 23-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 631746.49 | 79.17 | 22-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.243510E+09 | 534.92 | 04-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.208701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.114159E+10 | 1311.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.463713E+09 | 6999.01 | 19-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.266495E+09 | 6444.23 | 16-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 2215707.27 | 5711.42 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 58860.50 | 268.98 | 06-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1547936.65 | 3354.80 | 22-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 56194574.27 | 5620.50 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.790225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.463713E+09 | 6999.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.114115E+10 | 1099.48 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.682269E+09 | 1328.40 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13288865.32 | 223.52 | 23-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 73976.62 | 30.65 | 22-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.228008E+09 | 545.80 | 04-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.206479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.114115E+10 | 1328.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.556054E+09 | 653.22 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.343683E+09 | 795.73 | 12-FEB-08:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 11638394.75 | 169.67 | 04-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.911375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.556054E+09 | 795.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.556336E+09 | 653.29 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.343421E+09 | 795.74 | 12-FEB-08:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 11719821.83 | 169.95 | 04-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.911477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.556336E+09 | 795.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.149321E+09 | 532.09 | 08-JAN-02:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 77987667.56 | 639.40 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.227308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.149321E+09 | 639.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.215760E+09 | 646.39 | 08-JAN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.115406E+09 | 729.85 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.331166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.215760E+09 | 729.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.646039E+09 | 1896.05 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.319672E+09 | 2283.78 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 30483647.53 | 670.17 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.996195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.646039E+09 | 2283.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.166108E+10 | 2069.70 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.915553E+09 | 2561.84 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 37541569.12 | 854.19 | 22-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.513891E+09 | 1275.30 | 03-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.312806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.166108E+10 | 2561.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.651810E+09 | 1923.85 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.314676E+09 | 2316.46 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 31598911.78 | 668.67 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.998085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.651810E+09 | 2316.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.165463E+10 | 2100.98 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.900635E+09 | 2603.60 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 28834026.34 | 796.46 | 22-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.481671E+09 | 1318.53 | 03-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.306577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.165463E+10 | 2603.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.617886E+09 | 1129.17 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.331649E+09 | 1383.93 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 29517824.06 | 504.59 | 04-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.979052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.617886E+09 | 1383.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.619021E+09 | 1129.72 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.331551E+09 | 1385.87 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 29939443.52 | 508.77 | 04-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.980512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.619021E+09 | 1385.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.126860E+09 | 910.25 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 26895050.65 | 997.21 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.153755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.126860E+09 | 997.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.126966E+09 | 909.97 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 27072484.28 | 999.06 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.154038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.126966E+09 | 999.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.148583E+10 | 1804.82 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.839526E+09 | 2378.12 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.119228E+09 | 767.70 | 18-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 36600042.55 | 763.54 | 06-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 58797206.92 | 763.56 | 26-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.269075E+09 | 1408.13 | 21-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.874135E+09 | 1512.16 | 01-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.368319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.148583E+10 | 2378.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.211023E+10 | 1904.58 | 14-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.120723E+10 | 2444.85 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.208054E+09 | 935.75 | 18-MAR-07:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 53483036.55 | 826.57 | 06-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 88206352.97 | 951.97 | 26-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.519123E+09 | 1587.59 | 22-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.136935E+10 | 1675.25 | 18-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.555567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.211023E+10 | 2444.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.147511E+10 | 1826.55 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.829582E+09 | 2393.85 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.116510E+09 | 804.23 | 18-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 31905098.63 | 779.93 | 06-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 58205868.68 | 799.01 | 26-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.257764E+09 | 1403.14 | 21-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.854432E+09 | 1510.91 | 01-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.362350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.147511E+10 | 2393.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.210630E+10 | 1922.73 | 14-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.118780E+10 | 2424.74 | 12-FEB-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.194715E+09 | 945.11 | 18-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 47895935.18 | 849.76 | 06-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 86057652.90 | 1003.81 | 26-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.494323E+09 | 1584.64 | 22-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.134020E+10 | 1683.72 | 18-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.545729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.210630E+10 | 2424.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.139582E+10 | 1310.15 | 14-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.773244E+09 | 1707.35 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 84994231.86 | 616.10 | 19-MAR-07:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 19805341.04 | 425.00 | 06-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 29022333.44 | 588.60 | 26-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.257984E+09 | 1086.35 | 22-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.823161E+09 | 1174.43 | 18-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.338403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.139582E+10 | 1707.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.139653E+10 | 1311.81 | 14-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.773257E+09 | 1708.47 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 85867128.96 | 619.88 | 19-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 19814019.13 | 426.96 | 06-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 29336621.17 | 595.16 | 26-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.258695E+09 | 1086.11 | 22-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.823586E+09 | 1175.25 | 18-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.338709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.139653E+10 | 1708.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.828174E+09 | 1250.78 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.453733E+09 | 1636.59 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 34017107.98 | 444.18 | 23-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 8943249.98 | 364.45 | 06-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 14299795.53 | 387.89 | 26-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 93850126.22 | 867.35 | 21-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.407772E+09 | 1009.95 | 01-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.184079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.828174E+09 | 1636.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.829684E+09 | 1251.55 | 08-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.454442E+09 | 1637.93 | 12-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 34399207.71 | 445.47 | 23-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 8948264.18 | 364.68 | 06-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 14464161.59 | 392.25 | 26-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 93764457.00 | 867.19 | 21-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.408252E+09 | 1009.98 | 01-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.184395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.829684E+09 | 1637.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 7994106.23 | 1068.14 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 7994106.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 7994106.23 | 1068.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 9218573.79 | 1220.22 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 9218573.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 9218573.79 | 1220.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 21718823.33 | 6100.13 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 15646050.28 | 6100.13 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 174110.71 | 2901.85 | 22-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 3655869.49 | 6100.13 | 18-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 41194853.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 21718823.33 | 6100.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 9433544.75 | 1263.25 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 9433544.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 9433544.75 | 1263.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 4826568.00 | 652.60 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4826568.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4826568.00 | 652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 4836746.64 | 653.97 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4836746.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4836746.64 | 653.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3392329.38 | 474.94 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3392329.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3392329.38 | 474.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 4238135.69 | 578.71 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4238135.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4238135.69 | 578.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 13717786.06 | 1919.95 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 13717786.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 13717786.06 | 1919.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 16454789.05 | 2262.09 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 16454789.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 16454789.05 | 2262.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 14232602.80 | 2023.07 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 14232602.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 14232602.80 | 2023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 17011661.73 | 2373.71 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 17011661.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 17011661.73 | 2373.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 6840893.76 | 1011.01 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 6840893.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6840893.76 | 1011.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 6871477.58 | 1015.10 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 6871477.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6871477.58 | 1015.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3241930.37 | 538.82 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3241930.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3241930.37 | 538.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3264793.42 | 541.91 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3264793.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3264793.42 | 541.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 17558559.80 | 2355.21 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 17558559.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 17558559.80 | 2355.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 18257916.14 | 2436.09 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 18257916.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 18257916.14 | 2436.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 17813150.99 | 2414.23 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 17813150.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 17813150.99 | 2414.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 18538593.49 | 2493.48 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 18538593.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 18538593.49 | 2493.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 12262130.41 | 1646.48 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 12262130.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 12262130.41 | 1646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 12279805.84 | 1648.99 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 12279805.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 12279805.84 | 1648.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 11523602.87 | 1559.64 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 11523602.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 11523602.87 | 1559.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 11543121.81 | 1562.43 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 11543121.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 11543121.81 | 1562.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 56169771.43 | 56169771.43 | 5324.84 | 28-FEB-19:02 | 5324.84 | 0.00 |
| March | 0.00 | 0.00 | 0.255849E+09 | 0.239288E+09 | 5708.58 | 30-MAR-11:32 | 4413.69 | 0.00 |
| April | 0.00 | 0.00 | 0.613194E+09 | 0.562766E+09 | 5845.63 | 30-APR-21:52 | 3824.68 | 0.00 |
| May | 0.00 | 0.00 | 0.148056E+10 | 0.125151E+10 | 5937.30 | 31-MAY-10:12 | 3777.66 | 0.00 |
| June | 0.00 | 0.00 | 0.284228E+10 | 0.233916E+10 | 6047.61 | 18-JUN-10:02 | 3491.98 | 0.00 |
| July | 0.00 | 0.00 | 0.358621E+10 | 0.284236E+10 | 6125.56 | 30-JUL-09:32 | 3231.88 | 0.00 |
| August | 0.00 | 0.00 | 0.412500E+10 | 0.325073E+10 | 6050.74 | 11-AUG-08:52 | 3496.54 | 0.00 |
| September | 0.00 | 0.00 | 0.279857E+10 | 0.232510E+10 | 6080.96 | 17-SEP-08:42 | 3368.67 | 0.00 |
| October | 0.00 | 0.00 | 0.147725E+10 | 0.130969E+10 | 6037.69 | 18-OCT-11:22 | 3535.83 | 0.00 |
| November | 0.00 | 0.00 | 0.600914E+09 | 0.561385E+09 | 5866.77 | 27-NOV-22:52 | 3926.55 | 0.00 |
| December | 0.00 | 0.00 | 75461230.10 | 70621606.83 | 5769.57 | 13-DEC-21:02 | 4113.08 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.179115E+11 | 0.148088E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.412500E+10 | 0.325073E+10 | 6125.56 | 5324.84 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 1000574.79 | 1000574.79 | 3048.49 | 28-FEB-17:52 | 3048.49 | 0.00 |
| March | 0.00 | 0.00 | 61429533.37 | 54160994.76 | 5495.23 | 30-MAR-12:22 | 4145.56 | 0.00 |
| April | 0.00 | 0.00 | 0.367966E+09 | 0.328415E+09 | 5656.69 | 04-APR-14:12 | 3680.44 | 0.00 |
| May | 0.00 | 0.00 | 0.132968E+10 | 0.111130E+10 | 5764.19 | 31-MAY-10:02 | 3617.56 | 0.00 |
| June | 0.00 | 0.00 | 0.282724E+10 | 0.231853E+10 | 5866.23 | 23-JUN-08:52 | 3332.67 | 0.00 |
| July | 0.00 | 0.00 | 0.353801E+10 | 0.279292E+10 | 5912.46 | 30-JUL-09:32 | 3209.89 | 0.00 |
| August | 0.00 | 0.00 | 0.388053E+10 | 0.301830E+10 | 5874.91 | 11-AUG-08:52 | 3341.47 | 0.00 |
| September | 0.00 | 0.00 | 0.236358E+10 | 0.191984E+10 | 5884.45 | 17-SEP-09:12 | 3284.75 | 0.00 |
| October | 0.00 | 0.00 | 0.846757E+09 | 0.706820E+09 | 5880.61 | 18-OCT-11:42 | 3323.84 | 0.00 |
| November | 0.00 | 0.00 | 0.120007E+09 | 0.101845E+09 | 5658.60 | 04-NOV-17:32 | 4071.14 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.153362E+11 | 0.123531E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.388053E+10 | 0.301830E+10 | 5912.46 | 4145.56 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 1572045.29 | 1497348.31 | 239.49 | 31-JAN-15:20 | 230.16 | 0.00 |
| February | 0.00 | 0.00 | 0.114588E+09 | 0.114568E+09 | 1656.62 | 28-FEB-15:30 | 1656.62 | 0.00 |
| March | 0.00 | 0.00 | 0.441795E+09 | 0.403821E+09 | 6294.80 | 31-MAR-06:02 | 5021.92 | 0.00 |
| April | 0.00 | 0.00 | 0.733441E+09 | 0.679810E+09 | 6233.02 | 19-APR-06:01 | 5218.28 | 0.00 |
| May | 0.00 | 0.00 | 0.147109E+10 | 0.124868E+10 | 6710.46 | 31-MAY-06:02 | 4165.01 | 0.00 |
| June | 0.00 | 0.00 | 0.256110E+10 | 0.207643E+10 | 6945.70 | 26-JUN-06:01 | 4202.85 | 0.00 |
| July | 0.00 | 0.00 | 0.290885E+10 | 0.227824E+10 | 7010.79 | 27-JUL-06:01 | 3503.08 | 0.00 |
| August | 0.00 | 0.00 | 0.356052E+10 | 0.272636E+10 | 7042.07 | 24-AUG-06:01 | 3529.57 | 0.00 |
| September | 0.00 | 0.00 | 0.232371E+10 | 0.194071E+10 | 6904.90 | 07-SEP-06:01 | 4067.28 | 0.00 |
| October | 0.00 | 0.00 | 0.131218E+10 | 0.114832E+10 | 6911.44 | 19-OCT-06:01 | 3615.17 | 0.00 |
| November | 0.00 | 0.00 | 0.531823E+09 | 0.505798E+09 | 5903.67 | 03-NOV-06:01 | 4968.93 | 0.00 |
| December | 0.00 | 0.00 | 0.126462E+09 | 0.111897E+09 | 3820.03 | 13-DEC-07:02 | 2932.03 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.160871E+11 | 0.132361E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 1572045.29 | 1497348.31 | 239.49 | 230.16 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.356052E+10 | 0.272636E+10 | 7042.07 | 5218.28 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 1234697.66 | 1234697.66 | 2733.36 | 28-FEB-17:52 | 2733.36 | 0.00 |
| March | 0.00 | 0.00 | 45938239.83 | 39873967.28 | 5117.48 | 30-MAR-12:22 | 3891.87 | 0.00 |
| April | 0.00 | 0.00 | 0.355545E+09 | 0.317226E+09 | 5260.34 | 04-APR-14:12 | 3415.19 | 0.00 |
| May | 0.00 | 0.00 | 0.134209E+10 | 0.112288E+10 | 5358.81 | 31-MAY-10:02 | 3465.90 | 0.00 |
| June | 0.00 | 0.00 | 0.286582E+10 | 0.235232E+10 | 5455.98 | 23-JUN-08:52 | 3105.48 | 0.00 |
| July | 0.00 | 0.00 | 0.358870E+10 | 0.283763E+10 | 5499.53 | 30-JUL-09:32 | 2987.68 | 0.00 |
| August | 0.00 | 0.00 | 0.388357E+10 | 0.301917E+10 | 5462.00 | 11-AUG-08:52 | 3120.82 | 0.00 |
| September | 0.00 | 0.00 | 0.236368E+10 | 0.191872E+10 | 5472.48 | 17-SEP-09:12 | 3062.28 | 0.00 |
| October | 0.00 | 0.00 | 0.844066E+09 | 0.705306E+09 | 5464.38 | 18-OCT-11:42 | 3106.47 | 0.00 |
| November | 0.00 | 0.00 | 0.113375E+09 | 96374981.38 | 5257.62 | 04-NOV-17:32 | 3770.82 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.154040E+11 | 0.124107E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.388357E+10 | 0.301917E+10 | 5499.53 | 3891.87 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 1742228.63 | 1742228.63 | 3603.31 | 28-FEB-17:52 | 3603.31 | 0.00 |
| March | 0.00 | 0.00 | 71233782.56 | 62907470.40 | 4677.06 | 30-MAR-12:22 | 3554.87 | 0.00 |
| April | 0.00 | 0.00 | 0.440871E+09 | 0.386440E+09 | 4817.13 | 04-APR-14:12 | 3183.63 | 0.00 |
| May | 0.00 | 0.00 | 0.131886E+10 | 0.109442E+10 | 4898.40 | 31-MAY-10:02 | 3104.17 | 0.00 |
| June | 0.00 | 0.00 | 0.251183E+10 | 0.203583E+10 | 4982.15 | 23-JUN-08:52 | 2847.18 | 0.00 |
| July | 0.00 | 0.00 | 0.309649E+10 | 0.239992E+10 | 5016.27 | 27-JUL-11:42 | 2775.42 | 0.00 |
| August | 0.00 | 0.00 | 0.334607E+10 | 0.254907E+10 | 4993.42 | 11-AUG-08:52 | 2850.75 | 0.00 |
| September | 0.00 | 0.00 | 0.213213E+10 | 0.171166E+10 | 4997.90 | 17-SEP-09:12 | 2815.04 | 0.00 |
| October | 0.00 | 0.00 | 0.920524E+09 | 0.778098E+09 | 4996.22 | 18-OCT-11:42 | 2841.50 | 0.00 |
| November | 0.00 | 0.00 | 0.220816E+09 | 0.195846E+09 | 4813.45 | 04-NOV-17:32 | 3474.51 | 0.00 |
| December | 0.00 | 0.00 | 995572.82 | 932052.95 | 687.27 | 13-DEC-21:02 | 476.11 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.140616E+11 | 0.112169E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.334607E+10 | 0.254907E+10 | 5016.27 | 3603.31 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 1844903.02 | 1844903.02 | 3713.69 | 28-FEB-17:52 | 3713.69 | 0.00 |
| March | 0.00 | 0.00 | 70974962.81 | 62646859.71 | 4671.44 | 30-MAR-12:22 | 3551.40 | 0.00 |
| April | 0.00 | 0.00 | 0.441644E+09 | 0.387263E+09 | 4810.90 | 04-APR-14:12 | 3177.97 | 0.00 |
| May | 0.00 | 0.00 | 0.132293E+10 | 0.109819E+10 | 4892.59 | 31-MAY-10:02 | 3102.41 | 0.00 |
| June | 0.00 | 0.00 | 0.251623E+10 | 0.203988E+10 | 4975.94 | 23-JUN-08:52 | 2843.28 | 0.00 |
| July | 0.00 | 0.00 | 0.310049E+10 | 0.240344E+10 | 5009.84 | 27-JUL-11:42 | 2772.35 | 0.00 |
| August | 0.00 | 0.00 | 0.334719E+10 | 0.255003E+10 | 4986.98 | 11-AUG-08:52 | 2847.66 | 0.00 |
| September | 0.00 | 0.00 | 0.213464E+10 | 0.171393E+10 | 4991.56 | 17-SEP-09:12 | 2811.62 | 0.00 |
| October | 0.00 | 0.00 | 0.920902E+09 | 0.778400E+09 | 4989.69 | 18-OCT-11:42 | 2838.25 | 0.00 |
| November | 0.00 | 0.00 | 0.219948E+09 | 0.195074E+09 | 4807.30 | 04-NOV-17:32 | 3469.04 | 0.00 |
| December | 0.00 | 0.00 | 1010126.51 | 947128.88 | 681.29 | 13-DEC-21:02 | 471.92 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.140778E+11 | 0.112317E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.334719E+10 | 0.255003E+10 | 5009.84 | 3713.69 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 735970.80 | 735970.80 | 563.57 | 29-JAN-17:52 | 563.57 | 0.00 |
| February | 0.00 | 0.00 | 0.110396E+09 | 0.110140E+09 | 4570.73 | 28-FEB-19:02 | 4570.73 | 0.00 |
| March | 0.00 | 0.00 | 0.429471E+09 | 0.407038E+09 | 4898.57 | 30-MAR-11:32 | 3831.49 | 0.00 |
| April | 0.00 | 0.00 | 0.746723E+09 | 0.679498E+09 | 5021.46 | 30-APR-21:52 | 3349.02 | 0.00 |
| May | 0.00 | 0.00 | 0.147898E+10 | 0.124368E+10 | 5086.79 | 31-MAY-10:12 | 3270.14 | 0.00 |
| June | 0.00 | 0.00 | 0.253627E+10 | 0.206473E+10 | 5180.55 | 18-JUN-10:02 | 3010.66 | 0.00 |
| July | 0.00 | 0.00 | 0.315783E+10 | 0.246077E+10 | 5220.96 | 30-JUL-09:32 | 2881.20 | 0.00 |
| August | 0.00 | 0.00 | 0.360708E+10 | 0.279477E+10 | 5184.15 | 11-AUG-08:52 | 3011.56 | 0.00 |
| September | 0.00 | 0.00 | 0.258539E+10 | 0.213264E+10 | 5200.48 | 17-SEP-08:42 | 2935.14 | 0.00 |
| October | 0.00 | 0.00 | 0.160397E+10 | 0.143408E+10 | 5167.70 | 18-OCT-11:22 | 3058.08 | 0.00 |
| November | 0.00 | 0.00 | 0.891056E+09 | 0.845997E+09 | 5039.32 | 27-NOV-22:52 | 3432.69 | 0.00 |
| December | 0.00 | 0.00 | 0.237748E+09 | 0.228697E+09 | 4963.64 | 13-DEC-21:02 | 3609.90 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.173856E+11 | 0.144028E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 735970.80 | 735970.80 | 563.57 | 563.57 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.360708E+10 | 0.279477E+10 | 5220.96 | 4570.73 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 22254.14 | 22254.14 | 37.09 | 29-JAN-14:50 | 37.09 | 0.00 |
| February | 0.00 | 0.00 | 0.106958E+09 | 0.106725E+09 | 4605.33 | 28-FEB-19:02 | 4605.33 | 0.00 |
| March | 0.00 | 0.00 | 0.425705E+09 | 0.403114E+09 | 4936.88 | 30-MAR-11:32 | 3865.44 | 0.00 |
| April | 0.00 | 0.00 | 0.774684E+09 | 0.705625E+09 | 5059.34 | 30-APR-21:52 | 3370.90 | 0.00 |
| May | 0.00 | 0.00 | 0.156102E+10 | 0.131827E+10 | 5124.87 | 31-MAY-10:12 | 3325.63 | 0.00 |
| June | 0.00 | 0.00 | 0.271465E+10 | 0.222987E+10 | 5209.84 | 18-JUN-10:02 | 3064.46 | 0.00 |
| July | 0.00 | 0.00 | 0.340014E+10 | 0.268454E+10 | 5251.03 | 30-JUL-09:32 | 2936.65 | 0.00 |
| August | 0.00 | 0.00 | 0.386119E+10 | 0.302859E+10 | 5211.53 | 11-AUG-08:52 | 3076.07 | 0.00 |
| September | 0.00 | 0.00 | 0.274744E+10 | 0.228396E+10 | 5224.21 | 17-SEP-08:42 | 3012.05 | 0.00 |
| October | 0.00 | 0.00 | 0.165731E+10 | 0.148460E+10 | 5202.22 | 18-OCT-11:22 | 3091.19 | 0.00 |
| November | 0.00 | 0.00 | 0.872762E+09 | 0.827843E+09 | 5075.65 | 27-NOV-22:52 | 3443.90 | 0.00 |
| December | 0.00 | 0.00 | 0.212978E+09 | 0.204430E+09 | 5000.63 | 13-DEC-21:02 | 3630.72 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.183349E+11 | 0.152776E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 22254.14 | 22254.14 | 37.09 | 37.09 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.386119E+10 | 0.302859E+10 | 5251.03 | 4605.33 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 16293199.21 | 16289146.16 | 9375.55 | 29-JAN-17:52 | 9375.55 | 0.00 |
| February | 0.00 | 0.00 | 0.518995E+09 | 0.516759E+09 | 12549.12 | 22-FEB-16:32 | 12549.12 | 0.00 |
| March | 0.00 | 0.00 | 0.183614E+10 | 0.175575E+10 | 13410.72 | 30-MAR-11:32 | 10802.85 | 0.00 |
| April | 0.00 | 0.00 | 0.297003E+10 | 0.275896E+10 | 13732.43 | 04-APR-13:42 | 9581.38 | 0.00 |
| May | 0.00 | 0.00 | 0.470720E+10 | 0.409561E+10 | 13898.52 | 31-MAY-10:12 | 9033.61 | 0.00 |
| June | 0.00 | 0.00 | 0.682926E+10 | 0.570733E+10 | 14191.00 | 23-JUN-08:52 | 7988.28 | 0.00 |
| July | 0.00 | 0.00 | 0.799692E+10 | 0.639153E+10 | 14316.00 | 30-JUL-09:32 | 7639.89 | 0.00 |
| August | 0.00 | 0.00 | 0.874113E+10 | 0.688716E+10 | 14302.23 | 20-AUG-07:32 | 7628.25 | 0.00 |
| September | 0.00 | 0.00 | 0.570227E+10 | 0.472248E+10 | 14339.04 | 17-SEP-08:42 | 7380.62 | 0.00 |
| October | 0.00 | 0.00 | 0.295112E+10 | 0.260883E+10 | 14222.05 | 18-OCT-11:22 | 7945.90 | 0.00 |
| November | 0.00 | 0.00 | 0.121823E+10 | 0.113534E+10 | 13729.79 | 27-NOV-22:52 | 9175.09 | 0.00 |
| December | 0.00 | 0.00 | 0.290552E+09 | 0.274440E+09 | 13514.73 | 13-DEC-21:02 | 9770.52 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.437781E+11 | 0.368705E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16293199.21 | 16289146.16 | 9375.55 | 7380.62 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.874113E+10 | 0.688716E+10 | 14339.04 | 12549.12 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 73763183.18 | 72815033.83 | 12203.73 | 28-FEB-22:52 | 12203.73 | 0.00 |
| March | 0.00 | 0.00 | 0.840954E+09 | 0.777660E+09 | 13060.52 | 30-MAR-12:22 | 10432.15 | 0.00 |
| April | 0.00 | 0.00 | 0.226298E+10 | 0.206612E+10 | 13429.43 | 04-APR-14:12 | 9240.64 | 0.00 |
| May | 0.00 | 0.00 | 0.439157E+10 | 0.379179E+10 | 13597.76 | 31-MAY-10:02 | 8765.63 | 0.00 |
| June | 0.00 | 0.00 | 0.678148E+10 | 0.564987E+10 | 13876.37 | 23-JUN-08:52 | 7743.97 | 0.00 |
| July | 0.00 | 0.00 | 0.787180E+10 | 0.626667E+10 | 13957.27 | 26-JUL-08:62 | 7485.64 | 0.00 |
| August | 0.00 | 0.00 | 0.820767E+10 | 0.637971E+10 | 13988.74 | 11-AUG-08:52 | 7395.30 | 0.00 |
| September | 0.00 | 0.00 | 0.475902E+10 | 0.384645E+10 | 13983.01 | 17-SEP-09:12 | 7242.82 | 0.00 |
| October | 0.00 | 0.00 | 0.161476E+10 | 0.133048E+10 | 13925.67 | 18-OCT-11:42 | 7618.30 | 0.00 |
| November | 0.00 | 0.00 | 0.236868E+09 | 0.197807E+09 | 13349.21 | 04-NOV-17:32 | 9601.26 | 0.00 |
| December | 0.00 | 0.00 | 5456313.27 | 4767518.53 | 5427.48 | 13-DEC-21:02 | 3818.08 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.370463E+11 | 0.303841E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.820767E+10 | 0.637971E+10 | 13988.74 | 12203.73 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 20409797.79 | 20404583.06 | 7637.33 | 29-JAN-17:52 | 7637.33 | 0.00 |
| February | 0.00 | 0.00 | 0.563900E+09 | 0.561566E+09 | 11604.54 | 22-FEB-16:32 | 11604.54 | 0.00 |
| March | 0.00 | 0.00 | 0.178047E+10 | 0.170367E+10 | 12379.03 | 30-MAR-11:32 | 10049.72 | 0.00 |
| April | 0.00 | 0.00 | 0.293560E+10 | 0.272932E+10 | 12710.08 | 30-APR-21:52 | 8831.21 | 0.00 |
| May | 0.00 | 0.00 | 0.473263E+10 | 0.412133E+10 | 12801.90 | 26-MAY-10:02 | 8581.24 | 0.00 |
| June | 0.00 | 0.00 | 0.690633E+10 | 0.577747E+10 | 13111.20 | 23-JUN-08:52 | 7404.68 | 0.00 |
| July | 0.00 | 0.00 | 0.809080E+10 | 0.647559E+10 | 13231.79 | 30-JUL-09:32 | 7063.65 | 0.00 |
| August | 0.00 | 0.00 | 0.874467E+10 | 0.688612E+10 | 13220.50 | 20-AUG-07:32 | 7056.74 | 0.00 |
| September | 0.00 | 0.00 | 0.570532E+10 | 0.472527E+10 | 13253.89 | 17-SEP-08:42 | 6836.02 | 0.00 |
| October | 0.00 | 0.00 | 0.295065E+10 | 0.261105E+10 | 13135.92 | 18-OCT-11:22 | 7411.32 | 0.00 |
| November | 0.00 | 0.00 | 0.120843E+10 | 0.112919E+10 | 12689.63 | 27-NOV-22:52 | 8495.71 | 0.00 |
| December | 0.00 | 0.00 | 0.292098E+09 | 0.276504E+09 | 12492.33 | 13-DEC-21:02 | 9055.13 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.439313E+11 | 0.370175E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 20409797.79 | 20404583.06 | 7637.33 | 6836.02 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.874467E+10 | 0.688612E+10 | 13253.89 | 11604.54 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 84403770.55 | 83346932.71 | 11232.59 | 28-FEB-17:52 | 11232.59 | 0.00 |
| March | 0.00 | 0.00 | 0.774287E+09 | 0.714312E+09 | 12041.22 | 29-MAR-13:52 | 9816.16 | 0.00 |
| April | 0.00 | 0.00 | 0.222204E+10 | 0.202807E+10 | 12380.95 | 04-APR-14:12 | 8529.08 | 0.00 |
| May | 0.00 | 0.00 | 0.442014E+10 | 0.381874E+10 | 12511.15 | 26-MAY-10:12 | 8222.54 | 0.00 |
| June | 0.00 | 0.00 | 0.686682E+10 | 0.572440E+10 | 12788.62 | 23-JUN-08:52 | 7162.93 | 0.00 |
| July | 0.00 | 0.00 | 0.797416E+10 | 0.635492E+10 | 12858.79 | 26-JUL-08:62 | 7003.98 | 0.00 |
| August | 0.00 | 0.00 | 0.821513E+10 | 0.637998E+10 | 12895.64 | 20-AUG-07:42 | 6765.73 | 0.00 |
| September | 0.00 | 0.00 | 0.475990E+10 | 0.384400E+10 | 12896.61 | 17-SEP-09:12 | 6704.49 | 0.00 |
| October | 0.00 | 0.00 | 0.160801E+10 | 0.132536E+10 | 12838.28 | 18-OCT-11:42 | 7075.06 | 0.00 |
| November | 0.00 | 0.00 | 0.217313E+09 | 0.181046E+09 | 12280.70 | 05-NOV-21:52 | 8520.28 | 0.00 |
| December | 0.00 | 0.00 | 5994836.41 | 5292340.02 | 5660.04 | 13-DEC-21:02 | 3984.31 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.371482E+11 | 0.304595E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.821513E+10 | 0.637998E+10 | 12896.61 | 11232.59 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.147936E+09 | 0.145747E+09 | 10102.25 | 22-FEB-16:32 | 10102.25 | 0.00 |
| March | 0.00 | 0.00 | 0.100882E+10 | 0.944254E+09 | 10789.75 | 30-MAR-12:22 | 8595.08 | 0.00 |
| April | 0.00 | 0.00 | 0.214832E+10 | 0.195163E+10 | 11091.85 | 04-APR-14:12 | 7602.80 | 0.00 |
| May | 0.00 | 0.00 | 0.385387E+10 | 0.328962E+10 | 11237.13 | 31-MAY-10:02 | 7214.28 | 0.00 |
| June | 0.00 | 0.00 | 0.569536E+10 | 0.466667E+10 | 11453.73 | 23-JUN-08:52 | 6398.93 | 0.00 |
| July | 0.00 | 0.00 | 0.660053E+10 | 0.513242E+10 | 11513.30 | 26-JUL-08:62 | 6239.53 | 0.00 |
| August | 0.00 | 0.00 | 0.685681E+10 | 0.519511E+10 | 11562.50 | 11-AUG-08:52 | 6032.02 | 0.00 |
| September | 0.00 | 0.00 | 0.423181E+10 | 0.337226E+10 | 11541.74 | 17-SEP-09:12 | 6025.22 | 0.00 |
| October | 0.00 | 0.00 | 0.178938E+10 | 0.149737E+10 | 11500.42 | 18-OCT-11:42 | 6315.61 | 0.00 |
| November | 0.00 | 0.00 | 0.476368E+09 | 0.420242E+09 | 11035.47 | 04-NOV-17:32 | 7963.36 | 0.00 |
| December | 0.00 | 0.00 | 37458822.91 | 33125698.54 | 10888.97 | 13-DEC-21:02 | 7772.80 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.328467E+11 | 0.266485E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.685681E+10 | 0.519511E+10 | 11562.50 | 10102.25 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.151711E+09 | 0.149513E+09 | 10076.03 | 22-FEB-16:32 | 10076.03 | 0.00 |
| March | 0.00 | 0.00 | 0.100550E+10 | 0.940857E+09 | 10761.69 | 30-MAR-12:22 | 8574.43 | 0.00 |
| April | 0.00 | 0.00 | 0.215237E+10 | 0.195554E+10 | 11062.46 | 04-APR-14:12 | 7581.88 | 0.00 |
| May | 0.00 | 0.00 | 0.386465E+10 | 0.329962E+10 | 11208.14 | 31-MAY-10:02 | 7200.33 | 0.00 |
| June | 0.00 | 0.00 | 0.570537E+10 | 0.467581E+10 | 11423.36 | 23-JUN-08:52 | 6380.84 | 0.00 |
| July | 0.00 | 0.00 | 0.660676E+10 | 0.513813E+10 | 11482.69 | 26-JUL-08:62 | 6227.09 | 0.00 |
| August | 0.00 | 0.00 | 0.685994E+10 | 0.519768E+10 | 11531.91 | 11-AUG-08:52 | 6016.52 | 0.00 |
| September | 0.00 | 0.00 | 0.423901E+10 | 0.337845E+10 | 11511.14 | 17-SEP-09:12 | 6008.99 | 0.00 |
| October | 0.00 | 0.00 | 0.178849E+10 | 0.149679E+10 | 11466.12 | 18-OCT-11:42 | 6321.37 | 0.00 |
| November | 0.00 | 0.00 | 0.474589E+09 | 0.418698E+09 | 11005.97 | 04-NOV-17:32 | 7939.69 | 0.00 |
| December | 0.00 | 0.00 | 37591488.32 | 33278666.28 | 10860.05 | 13-DEC-21:02 | 7751.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.328860E+11 | 0.266844E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.685994E+10 | 0.519768E+10 | 11531.91 | 10076.03 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.137710E+09 | 0.137643E+09 | 10151.57 | 29-JAN-17:52 | 10151.57 | 0.00 |
| February | 0.00 | 0.00 | 0.720283E+09 | 0.713764E+09 | 10529.65 | 22-FEB-16:32 | 10529.65 | 0.00 |
| March | 0.00 | 0.00 | 0.217400E+10 | 0.209346E+10 | 11227.16 | 30-MAR-11:32 | 9061.67 | 0.00 |
| April | 0.00 | 0.00 | 0.287355E+10 | 0.266397E+10 | 11524.11 | 30-APR-21:52 | 8061.94 | 0.00 |
| May | 0.00 | 0.00 | 0.416578E+10 | 0.358991E+10 | 11638.23 | 31-MAY-10:12 | 7539.61 | 0.00 |
| June | 0.00 | 0.00 | 0.574127E+10 | 0.472289E+10 | 11861.63 | 23-JUN-08:52 | 6683.14 | 0.00 |
| July | 0.00 | 0.00 | 0.672792E+10 | 0.525924E+10 | 11943.86 | 30-JUL-09:32 | 6550.47 | 0.00 |
| August | 0.00 | 0.00 | 0.739512E+10 | 0.570377E+10 | 11976.18 | 11-AUG-08:52 | 6334.25 | 0.00 |
| September | 0.00 | 0.00 | 0.517898E+10 | 0.425159E+10 | 11985.26 | 17-SEP-08:42 | 6261.82 | 0.00 |
| October | 0.00 | 0.00 | 0.323884E+10 | 0.289098E+10 | 11895.72 | 18-OCT-11:22 | 6725.83 | 0.00 |
| November | 0.00 | 0.00 | 0.188664E+10 | 0.179137E+10 | 11518.64 | 27-NOV-22:52 | 7836.33 | 0.00 |
| December | 0.00 | 0.00 | 0.759369E+09 | 0.735961E+09 | 11353.95 | 13-DEC-21:02 | 8353.54 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.409995E+11 | 0.345545E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.137710E+09 | 0.137643E+09 | 10151.57 | 6261.82 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.739512E+10 | 0.570377E+10 | 11985.26 | 10529.65 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.140276E+09 | 0.140206E+09 | 10139.45 | 29-JAN-17:52 | 10139.45 | 0.00 |
| February | 0.00 | 0.00 | 0.723429E+09 | 0.716979E+09 | 10517.05 | 22-FEB-16:32 | 10517.05 | 0.00 |
| March | 0.00 | 0.00 | 0.216648E+10 | 0.208628E+10 | 11213.22 | 30-MAR-11:32 | 9050.48 | 0.00 |
| April | 0.00 | 0.00 | 0.287770E+10 | 0.266808E+10 | 11510.07 | 30-APR-21:52 | 8048.64 | 0.00 |
| May | 0.00 | 0.00 | 0.417530E+10 | 0.359885E+10 | 11624.90 | 31-MAY-10:12 | 7536.70 | 0.00 |
| June | 0.00 | 0.00 | 0.575159E+10 | 0.473261E+10 | 11847.15 | 23-JUN-08:52 | 6674.06 | 0.00 |
| July | 0.00 | 0.00 | 0.673346E+10 | 0.526447E+10 | 11934.70 | 30-JUL-09:32 | 6522.68 | 0.00 |
| August | 0.00 | 0.00 | 0.739810E+10 | 0.570647E+10 | 11961.62 | 11-AUG-08:52 | 6327.18 | 0.00 |
| September | 0.00 | 0.00 | 0.518460E+10 | 0.425691E+10 | 11970.59 | 17-SEP-08:42 | 6253.67 | 0.00 |
| October | 0.00 | 0.00 | 0.324151E+10 | 0.289377E+10 | 11881.41 | 18-OCT-11:22 | 6719.18 | 0.00 |
| November | 0.00 | 0.00 | 0.188621E+10 | 0.179103E+10 | 11504.68 | 27-NOV-22:52 | 7826.90 | 0.00 |
| December | 0.00 | 0.00 | 0.764993E+09 | 0.741597E+09 | 11340.17 | 13-DEC-21:02 | 8343.22 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.410437E+11 | 0.345972E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.140276E+09 | 0.140206E+09 | 10139.45 | 6253.67 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.739810E+10 | 0.570647E+10 | 11970.59 | 10517.05 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 27754119.66 | 27754119.66 | 6795.32 | 29-JAN-17:52 | 6795.32 | 0.00 |
| February | 0.00 | 0.00 | 0.137902E+09 | 0.137869E+09 | 7047.68 | 20-FEB-18:22 | 7047.68 | 0.00 |
| March | 0.00 | 0.00 | 0.510182E+09 | 0.482325E+09 | 7491.54 | 30-MAR-11:32 | 6023.01 | 0.00 |
| April | 0.00 | 0.00 | 0.120262E+10 | 0.112236E+10 | 7641.59 | 23-APR-12:32 | 5518.14 | 0.00 |
| May | 0.00 | 0.00 | 0.225764E+10 | 0.197804E+10 | 7765.49 | 31-MAY-10:12 | 5029.45 | 0.00 |
| June | 0.00 | 0.00 | 0.364377E+10 | 0.307086E+10 | 7938.63 | 23-JUN-08:52 | 4412.63 | 0.00 |
| July | 0.00 | 0.00 | 0.433774E+10 | 0.351524E+10 | 8030.25 | 30-JUL-09:32 | 4138.36 | 0.00 |
| August | 0.00 | 0.00 | 0.474893E+10 | 0.379037E+10 | 8054.93 | 20-AUG-07:32 | 4040.40 | 0.00 |
| September | 0.00 | 0.00 | 0.274216E+10 | 0.227762E+10 | 8037.11 | 17-SEP-08:42 | 4089.52 | 0.00 |
| October | 0.00 | 0.00 | 0.105945E+10 | 0.917906E+09 | 7958.39 | 18-OCT-11:22 | 4396.08 | 0.00 |
| November | 0.00 | 0.00 | 0.225108E+09 | 0.206334E+09 | 7653.49 | 04-NOV-16:42 | 5479.80 | 0.00 |
| December | 0.00 | 0.00 | 69202563.21 | 67326807.50 | 7370.11 | 12-DEC-13:02 | 6173.01 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.209625E+11 | 0.175940E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 27754119.66 | 27754119.66 | 6795.32 | 4040.40 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.474893E+10 | 0.379037E+10 | 8054.93 | 7047.68 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 14803132.07 | 14803132.07 | 6871.32 | 28-FEB-22:52 | 6871.32 | 0.00 |
| March | 0.00 | 0.00 | 0.230502E+09 | 0.208790E+09 | 7366.14 | 30-MAR-12:22 | 5918.79 | 0.00 |
| April | 0.00 | 0.00 | 0.888541E+09 | 0.814166E+09 | 7569.76 | 30-APR-21:52 | 5298.20 | 0.00 |
| May | 0.00 | 0.00 | 0.209040E+10 | 0.181549E+10 | 7680.17 | 26-MAY-10:12 | 4970.52 | 0.00 |
| June | 0.00 | 0.00 | 0.361111E+10 | 0.303082E+10 | 7847.39 | 23-JUN-08:52 | 4334.11 | 0.00 |
| July | 0.00 | 0.00 | 0.427141E+10 | 0.344580E+10 | 7932.21 | 26-JUL-08:62 | 4084.56 | 0.00 |
| August | 0.00 | 0.00 | 0.446426E+10 | 0.351590E+10 | 7962.28 | 20-AUG-07:42 | 3963.14 | 0.00 |
| September | 0.00 | 0.00 | 0.225238E+10 | 0.182080E+10 | 7925.20 | 17-SEP-09:12 | 4081.21 | 0.00 |
| October | 0.00 | 0.00 | 0.545677E+09 | 0.428500E+09 | 7866.30 | 18-OCT-11:42 | 4319.24 | 0.00 |
| November | 0.00 | 0.00 | 27013595.80 | 20176296.90 | 7528.97 | 04-NOV-17:32 | 5429.18 | 0.00 |
| December | 0.00 | 0.00 | 217201.12 | 179976.22 | 1802.21 | 12-DEC-22:52 | 1496.23 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.183963E+11 | 0.151154E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.446426E+10 | 0.351590E+10 | 7962.28 | 6871.32 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 19142626.71 | 19142626.71 | 6069.08 | 29-JAN-17:52 | 6069.08 | 0.00 |
| February | 0.00 | 0.00 | 0.141799E+09 | 0.141751E+09 | 6283.33 | 21-FEB-15:12 | 6283.33 | 0.00 |
| March | 0.00 | 0.00 | 0.465352E+09 | 0.438867E+09 | 6710.62 | 30-MAR-11:32 | 5461.95 | 0.00 |
| April | 0.00 | 0.00 | 0.116381E+10 | 0.108503E+10 | 6867.78 | 30-APR-21:52 | 4900.34 | 0.00 |
| May | 0.00 | 0.00 | 0.225421E+10 | 0.197294E+10 | 7025.57 | 31-MAY-09:53 | 4835.14 | 0.00 |
| June | 0.00 | 0.00 | 0.368059E+10 | 0.309983E+10 | 7125.70 | 23-JUN-08:52 | 3982.84 | 0.00 |
| July | 0.00 | 0.00 | 0.438696E+10 | 0.355348E+10 | 7209.16 | 30-JUL-09:32 | 3733.25 | 0.00 |
| August | 0.00 | 0.00 | 0.474888E+10 | 0.378433E+10 | 7235.62 | 20-AUG-07:32 | 3629.98 | 0.00 |
| September | 0.00 | 0.00 | 0.273957E+10 | 0.227180E+10 | 7218.24 | 17-SEP-08:42 | 3679.18 | 0.00 |
| October | 0.00 | 0.00 | 0.103801E+10 | 0.897382E+09 | 7143.94 | 18-OCT-11:22 | 3967.82 | 0.00 |
| November | 0.00 | 0.00 | 0.205213E+09 | 0.187832E+09 | 6878.02 | 04-NOV-16:42 | 4909.46 | 0.00 |
| December | 0.00 | 0.00 | 59318514.94 | 57490788.46 | 6628.55 | 12-DEC-13:02 | 5592.09 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.209029E+11 | 0.175099E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 19142626.71 | 19142626.71 | 6069.08 | 3629.98 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.474888E+10 | 0.378433E+10 | 7235.62 | 6283.33 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 13237739.78 | 13237739.78 | 6167.60 | 28-FEB-17:52 | 6167.60 | 0.00 |
| March | 0.00 | 0.00 | 0.194112E+09 | 0.173832E+09 | 6604.08 | 29-MAR-13:52 | 5420.65 | 0.00 |
| April | 0.00 | 0.00 | 0.847124E+09 | 0.774945E+09 | 6783.92 | 30-APR-21:52 | 4702.21 | 0.00 |
| May | 0.00 | 0.00 | 0.208613E+10 | 0.181073E+10 | 6941.73 | 31-MAY-09:43 | 4730.50 | 0.00 |
| June | 0.00 | 0.00 | 0.365056E+10 | 0.306380E+10 | 7030.85 | 23-JUN-08:52 | 3908.50 | 0.00 |
| July | 0.00 | 0.00 | 0.432140E+10 | 0.348671E+10 | 7100.33 | 26-JUL-08:62 | 3709.96 | 0.00 |
| August | 0.00 | 0.00 | 0.446367E+10 | 0.351048E+10 | 7139.15 | 20-AUG-07:42 | 3557.18 | 0.00 |
| September | 0.00 | 0.00 | 0.224275E+10 | 0.180892E+10 | 7096.93 | 17-SEP-09:12 | 3694.60 | 0.00 |
| October | 0.00 | 0.00 | 0.524241E+09 | 0.408158E+09 | 7047.10 | 18-OCT-11:42 | 3898.38 | 0.00 |
| November | 0.00 | 0.00 | 20874150.99 | 15448338.60 | 6726.77 | 04-NOV-17:32 | 4767.07 | 0.00 |
| December | 0.00 | 0.00 | 134793.85 | 111846.44 | 1347.94 | 12-DEC-22:52 | 1118.46 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.183642E+11 | 0.150664E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.446367E+10 | 0.351048E+10 | 7139.15 | 6167.60 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 11331200.15 | 11277648.47 | 5710.43 | 28-FEB-17:52 | 5710.43 | 0.00 |
| March | 0.00 | 0.00 | 0.198067E+09 | 0.176956E+09 | 6118.55 | 30-MAR-12:22 | 4911.42 | 0.00 |
| April | 0.00 | 0.00 | 0.776780E+09 | 0.698835E+09 | 6292.19 | 30-APR-21:52 | 4426.17 | 0.00 |
| May | 0.00 | 0.00 | 0.180121E+10 | 0.153890E+10 | 6373.83 | 26-MAY-10:12 | 4140.95 | 0.00 |
| June | 0.00 | 0.00 | 0.304827E+10 | 0.252173E+10 | 6508.85 | 23-JUN-08:52 | 3624.18 | 0.00 |
| July | 0.00 | 0.00 | 0.361155E+10 | 0.285638E+10 | 6562.26 | 26-JUL-08:62 | 3479.69 | 0.00 |
| August | 0.00 | 0.00 | 0.376205E+10 | 0.290339E+10 | 6587.93 | 20-AUG-07:42 | 3374.20 | 0.00 |
| September | 0.00 | 0.00 | 0.196671E+10 | 0.156066E+10 | 6561.16 | 17-SEP-09:12 | 3457.31 | 0.00 |
| October | 0.00 | 0.00 | 0.494386E+09 | 0.382088E+09 | 6524.82 | 18-OCT-11:42 | 3611.82 | 0.00 |
| November | 0.00 | 0.00 | 37096234.97 | 27532570.12 | 6244.76 | 05-NOV-21:52 | 4323.53 | 0.00 |
| December | 0.00 | 0.00 | 1822558.43 | 1413730.01 | 4124.03 | 12-DEC-22:52 | 3448.10 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.157093E+11 | 0.126792E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.376205E+10 | 0.290339E+10 | 6587.93 | 5710.43 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 11618335.42 | 11559830.61 | 5690.12 | 28-FEB-17:52 | 5690.12 | 0.00 |
| March | 0.00 | 0.00 | 0.196455E+09 | 0.175379E+09 | 6096.41 | 30-MAR-12:22 | 4894.67 | 0.00 |
| April | 0.00 | 0.00 | 0.778644E+09 | 0.700767E+09 | 6269.83 | 30-APR-21:52 | 4403.52 | 0.00 |
| May | 0.00 | 0.00 | 0.180803E+10 | 0.154527E+10 | 6351.21 | 26-MAY-10:12 | 4125.84 | 0.00 |
| June | 0.00 | 0.00 | 0.305479E+10 | 0.252759E+10 | 6485.91 | 23-JUN-08:52 | 3610.55 | 0.00 |
| July | 0.00 | 0.00 | 0.361631E+10 | 0.286038E+10 | 6538.47 | 26-JUL-08:62 | 3468.97 | 0.00 |
| August | 0.00 | 0.00 | 0.376421E+10 | 0.290509E+10 | 6564.66 | 20-AUG-07:42 | 3361.70 | 0.00 |
| September | 0.00 | 0.00 | 0.197088E+10 | 0.156423E+10 | 6537.93 | 17-SEP-09:12 | 3444.69 | 0.00 |
| October | 0.00 | 0.00 | 0.495638E+09 | 0.383142E+09 | 6501.48 | 18-OCT-11:42 | 3599.44 | 0.00 |
| November | 0.00 | 0.00 | 36433760.67 | 27019946.33 | 6221.74 | 05-NOV-21:52 | 4301.64 | 0.00 |
| December | 0.00 | 0.00 | 1817688.67 | 1406710.68 | 4051.16 | 12-DEC-22:52 | 3385.49 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.157348E+11 | 0.127018E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.376421E+10 | 0.290509E+10 | 6564.66 | 5690.12 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 32570556.23 | 32570556.23 | 5662.37 | 29-JAN-17:52 | 5662.37 | 0.00 |
| February | 0.00 | 0.00 | 0.151742E+09 | 0.151363E+09 | 5839.25 | 22-FEB-16:32 | 5839.25 | 0.00 |
| March | 0.00 | 0.00 | 0.492787E+09 | 0.463558E+09 | 6252.75 | 30-MAR-11:32 | 5033.88 | 0.00 |
| April | 0.00 | 0.00 | 0.109071E+10 | 0.100610E+10 | 6381.83 | 23-APR-12:32 | 4599.22 | 0.00 |
| May | 0.00 | 0.00 | 0.197108E+10 | 0.170247E+10 | 6481.25 | 31-MAY-10:12 | 4205.33 | 0.00 |
| June | 0.00 | 0.00 | 0.308109E+10 | 0.255982E+10 | 6621.10 | 23-JUN-08:52 | 3706.50 | 0.00 |
| July | 0.00 | 0.00 | 0.368134E+10 | 0.292634E+10 | 6694.21 | 30-JUL-09:32 | 3490.54 | 0.00 |
| August | 0.00 | 0.00 | 0.405232E+10 | 0.317916E+10 | 6709.71 | 20-AUG-07:32 | 3426.86 | 0.00 |
| September | 0.00 | 0.00 | 0.246895E+10 | 0.202572E+10 | 6694.96 | 17-SEP-08:42 | 3467.16 | 0.00 |
| October | 0.00 | 0.00 | 0.103684E+10 | 0.896771E+09 | 6638.01 | 18-OCT-11:22 | 3692.84 | 0.00 |
| November | 0.00 | 0.00 | 0.276739E+09 | 0.252388E+09 | 6393.01 | 27-NOV-22:52 | 4244.31 | 0.00 |
| December | 0.00 | 0.00 | 94019349.21 | 90499767.08 | 6175.67 | 12-DEC-13:02 | 5289.95 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.184302E+11 | 0.152868E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 32570556.23 | 32570556.23 | 5662.37 | 3426.86 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.405232E+10 | 0.317916E+10 | 6709.71 | 5839.25 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 33398393.10 | 33398393.10 | 5642.81 | 29-JAN-17:52 | 5642.81 | 0.00 |
| February | 0.00 | 0.00 | 0.153810E+09 | 0.153432E+09 | 5820.62 | 22-FEB-16:32 | 5820.62 | 0.00 |
| March | 0.00 | 0.00 | 0.493274E+09 | 0.464233E+09 | 6230.81 | 30-MAR-11:32 | 5023.13 | 0.00 |
| April | 0.00 | 0.00 | 0.109350E+10 | 0.100942E+10 | 6359.69 | 23-APR-12:32 | 4588.40 | 0.00 |
| May | 0.00 | 0.00 | 0.197639E+10 | 0.170832E+10 | 6457.87 | 31-MAY-10:12 | 4198.25 | 0.00 |
| June | 0.00 | 0.00 | 0.308645E+10 | 0.256593E+10 | 6598.46 | 23-JUN-08:52 | 3696.10 | 0.00 |
| July | 0.00 | 0.00 | 0.368395E+10 | 0.292979E+10 | 6671.32 | 30-JUL-09:32 | 3480.52 | 0.00 |
| August | 0.00 | 0.00 | 0.405286E+10 | 0.318075E+10 | 6686.84 | 20-AUG-07:32 | 3416.69 | 0.00 |
| September | 0.00 | 0.00 | 0.247131E+10 | 0.202879E+10 | 6672.01 | 17-SEP-08:42 | 3457.42 | 0.00 |
| October | 0.00 | 0.00 | 0.103954E+10 | 0.899808E+09 | 6614.98 | 18-OCT-11:22 | 3683.70 | 0.00 |
| November | 0.00 | 0.00 | 0.276821E+09 | 0.252727E+09 | 6371.09 | 27-NOV-22:52 | 4234.00 | 0.00 |
| December | 0.00 | 0.00 | 95486648.90 | 91992231.61 | 6154.50 | 12-DEC-13:02 | 5278.23 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.184568E+11 | 0.153186E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 33398393.10 | 33398393.10 | 5642.81 | 3416.69 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.405286E+10 | 0.318075E+10 | 6686.84 | 5820.62 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 11508.80 | 22119.48 | 31-JAN-07:50 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11531.24 | 22120.05 | 01-FEB-07:40 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11152.94 | 21766.26 | 01-MAR-07:40 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 10453.15 | 20648.38 | 01-APR-06:40 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 9622.99 | 19129.00 | 01-MAY-06:40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 8885.59 | 17535.73 | 01-JUN-06:50 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 8441.04 | 16379.89 | 01-JUL-06:50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 8409.48 | 16264.26 | 31-AUG-06:50 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 8800.33 | 17335.53 | 30-SEP-06:50 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 9507.02 | 18896.28 | 31-OCT-06:40 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10337.40 | 20445.93 | 30-NOV-07:40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 11068.79 | 21650.29 | 31-DEC-07:40 |
| Annual Sum or Average | 0.00 | 9967.70 | ||||
| Minimum of Months | 0.00 | 0.00 | 8409.48 | 16264.26 | ||
| Maximum of Months | 0.00 | 0.00 | 11531.24 | 22120.05 |
Report: FanReportMonthly
For: SPLIT GSW SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 68899659.92 | 0.62 | 141.06 | 08-JAN-01:10 | 1.05 |
| February | 46555893.78 | 0.48 | 347.14 | 12-FEB-06:00 | 0.96 |
| March | 18590079.17 | 0.23 | 347.14 | 03-MAR-16:42 | 0.95 |
| April | 44334644.76 | 0.42 | 347.14 | 02-APR-14:32 | 0.94 |
| May | 0.105068E+09 | 0.64 | 347.14 | 01-MAY-14:12 | 0.94 |
| June | 0.201710E+09 | 0.84 | 347.14 | 01-JUN-09:22 | 0.94 |
| July | 0.251661E+09 | 0.85 | 347.14 | 01-JUL-08:32 | 0.93 |
| August | 0.287824E+09 | 0.90 | 347.14 | 01-AUG-07:32 | 0.94 |
| September | 0.195446E+09 | 0.73 | 347.14 | 01-SEP-10:22 | 0.94 |
| October | 0.104453E+09 | 0.66 | 347.14 | 01-OCT-13:32 | 0.94 |
| November | 44080219.25 | 0.54 | 347.14 | 01-NOV-13:42 | 0.95 |
| December | 6495542.76 | 0.15 | 347.14 | 10-DEC-15:12 | 0.95 |
| Annual Sum or Average | 0.137512E+10 | 0.59 | |||
| Minimum of Months | 6495542.76 | 0.15 | 141.06 | 0.93 | |
| Maximum of Months | 0.287824E+09 | 0.90 | 347.14 | 1.05 |
Report: FanReportMonthly
For: G SW APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: G SW APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT GNW SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.125708E+09 | 0.95 | 155.06 | 08-JAN-01:10 | 1.04 |
| February | 76996556.09 | 0.61 | 336.88 | 12-FEB-06:00 | 0.96 |
| March | 5542130.53 | 0.11 | 336.88 | 30-MAR-12:22 | 0.94 |
| April | 26649699.70 | 0.31 | 336.88 | 02-APR-15:32 | 0.94 |
| May | 94462905.88 | 0.62 | 336.88 | 01-MAY-14:22 | 0.94 |
| June | 0.200665E+09 | 0.84 | 336.88 | 01-JUN-09:12 | 0.94 |
| July | 0.248394E+09 | 0.86 | 336.88 | 01-JUL-08:62 | 0.93 |
| August | 0.270898E+09 | 0.90 | 336.88 | 01-AUG-07:22 | 0.94 |
| September | 0.165547E+09 | 0.71 | 336.88 | 01-SEP-11:02 | 0.94 |
| October | 59950169.15 | 0.53 | 336.88 | 01-OCT-14:22 | 0.94 |
| November | 8744907.26 | 0.18 | 336.88 | 02-NOV-21:52 | 0.94 |
| December | 23666886.10 | 0.49 | 68.98 | 18-DEC-08:00 | 1.09 |
| Annual Sum or Average | 0.130723E+10 | 0.59 | |||
| Minimum of Months | 5542130.53 | 0.11 | 68.98 | 0.93 | |
| Maximum of Months | 0.270898E+09 | 0.95 | 336.88 | 1.09 |
Report: FanReportMonthly
For: G NW APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: G NW APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT OFFICE SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.100530E+10 | 0.92 | 395.58 | 01-JAN-00:10 | 0.95 |
| February | 0.906482E+09 | 0.93 | 395.58 | 01-FEB-00:10 | 0.95 |
| March | 0.100227E+10 | 0.95 | 395.58 | 01-MAR-00:10 | 0.95 |
| April | 0.980745E+09 | 0.95 | 395.58 | 01-APR-00:10 | 0.95 |
| May | 0.101793E+10 | 0.95 | 395.58 | 01-MAY-00:10 | 0.94 |
| June | 0.995830E+09 | 0.95 | 395.58 | 01-JUN-00:10 | 0.94 |
| July | 0.103771E+10 | 0.94 | 395.58 | 01-JUL-00:10 | 0.93 |
| August | 0.103680E+10 | 0.94 | 395.58 | 01-AUG-00:10 | 0.93 |
| September | 0.999492E+09 | 0.94 | 395.58 | 01-SEP-00:10 | 0.94 |
| October | 0.102070E+10 | 0.95 | 395.58 | 01-OCT-00:10 | 0.94 |
| November | 0.979226E+09 | 0.95 | 395.58 | 01-NOV-00:10 | 0.95 |
| December | 0.100535E+10 | 0.93 | 395.58 | 01-DEC-00:10 | 0.95 |
| Annual Sum or Average | 0.119878E+11 | 0.94 | |||
| Minimum of Months | 0.906482E+09 | 0.92 | 395.58 | 0.93 | |
| Maximum of Months | 0.103771E+10 | 0.95 | 395.58 | 0.95 |
Report: FanReportMonthly
For: SPLIT GNE SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.123414E+09 | 0.95 | 153.59 | 08-JAN-01:10 | 1.04 |
| February | 74763372.34 | 0.61 | 308.88 | 12-FEB-06:00 | 0.96 |
| March | 4396219.68 | 0.11 | 308.88 | 30-MAR-12:22 | 0.94 |
| April | 25338607.04 | 0.30 | 308.88 | 02-APR-15:32 | 0.94 |
| May | 93723261.92 | 0.62 | 308.88 | 01-MAY-14:22 | 0.94 |
| June | 0.199680E+09 | 0.85 | 308.88 | 01-JUN-09:12 | 0.94 |
| July | 0.247182E+09 | 0.85 | 308.88 | 01-JUL-08:62 | 0.94 |
| August | 0.266103E+09 | 0.90 | 308.88 | 01-AUG-07:22 | 0.94 |
| September | 0.162564E+09 | 0.71 | 308.88 | 01-SEP-11:02 | 0.94 |
| October | 58809100.39 | 0.52 | 308.88 | 01-OCT-14:22 | 0.94 |
| November | 8088552.30 | 0.18 | 308.88 | 02-NOV-21:52 | 0.94 |
| December | 21877288.66 | 0.48 | 67.52 | 04-DEC-05:00 | 1.09 |
| Annual Sum or Average | 0.128594E+10 | 0.59 | |||
| Minimum of Months | 4396219.68 | 0.11 | 67.52 | 0.94 | |
| Maximum of Months | 0.266103E+09 | 0.95 | 308.88 | 1.09 |
Report: FanReportMonthly
For: G NE APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: G NE APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT GN1 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62586695.43 | 0.80 | 92.35 | 08-JAN-01:10 | 1.07 |
| February | 40031764.71 | 0.54 | 278.66 | 12-FEB-06:00 | 0.96 |
| March | 5067598.78 | 0.12 | 278.66 | 11-MAR-22:52 | 0.94 |
| April | 30918403.29 | 0.44 | 278.66 | 02-APR-15:32 | 0.94 |
| May | 90885908.62 | 0.64 | 278.66 | 01-MAY-14:22 | 0.94 |
| June | 0.172706E+09 | 0.84 | 278.66 | 01-JUN-09:12 | 0.94 |
| July | 0.210346E+09 | 0.85 | 278.66 | 01-JUL-08:62 | 0.94 |
| August | 0.226101E+09 | 0.90 | 278.66 | 01-AUG-07:22 | 0.94 |
| September | 0.144600E+09 | 0.71 | 278.66 | 01-SEP-11:02 | 0.94 |
| October | 63611579.91 | 0.62 | 278.66 | 01-OCT-14:22 | 0.94 |
| November | 15748397.75 | 0.34 | 278.66 | 01-NOV-21:52 | 0.94 |
| December | 1275871.02 | 0.08 | 46.42 | 13-DEC-21:02 | 1.08 |
| Annual Sum or Average | 0.106388E+10 | 0.57 | |||
| Minimum of Months | 1275871.02 | 0.08 | 46.42 | 0.94 | |
| Maximum of Months | 0.226101E+09 | 0.90 | 278.66 | 1.08 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT GN2 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62604164.11 | 0.80 | 92.34 | 08-JAN-01:10 | 1.07 |
| February | 40003398.61 | 0.54 | 278.25 | 12-FEB-06:00 | 0.96 |
| March | 5047428.03 | 0.12 | 278.25 | 11-MAR-22:52 | 0.94 |
| April | 30965865.36 | 0.44 | 278.25 | 02-APR-15:32 | 0.94 |
| May | 91140148.73 | 0.64 | 278.25 | 01-MAY-14:22 | 0.94 |
| June | 0.172961E+09 | 0.84 | 278.25 | 01-JUN-09:12 | 0.94 |
| July | 0.210555E+09 | 0.85 | 278.25 | 01-JUL-08:62 | 0.94 |
| August | 0.226116E+09 | 0.90 | 278.25 | 01-AUG-07:22 | 0.94 |
| September | 0.144731E+09 | 0.71 | 278.25 | 01-SEP-11:02 | 0.94 |
| October | 63619652.98 | 0.62 | 278.25 | 01-OCT-14:22 | 0.94 |
| November | 15684354.04 | 0.34 | 278.25 | 01-NOV-21:52 | 0.94 |
| December | 1282601.96 | 0.08 | 46.01 | 13-DEC-21:02 | 1.08 |
| Annual Sum or Average | 0.106471E+10 | 0.57 | |||
| Minimum of Months | 1282601.96 | 0.08 | 46.01 | 0.94 | |
| Maximum of Months | 0.226116E+09 | 0.90 | 278.25 | 1.08 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT GS1 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 19160851.63 | 0.28 | 75.08 | 08-JAN-01:10 | 1.08 |
| February | 20098594.94 | 0.34 | 288.46 | 12-FEB-06:00 | 0.96 |
| March | 30685208.52 | 0.47 | 288.46 | 02-MAR-17:52 | 0.95 |
| April | 52293190.33 | 0.56 | 288.46 | 01-APR-21:12 | 0.95 |
| May | 0.101427E+09 | 0.65 | 288.46 | 01-MAY-14:12 | 0.94 |
| June | 0.173793E+09 | 0.83 | 288.46 | 01-JUN-09:22 | 0.94 |
| July | 0.213709E+09 | 0.85 | 288.46 | 01-JUL-08:32 | 0.93 |
| August | 0.242858E+09 | 0.90 | 288.46 | 01-AUG-07:32 | 0.94 |
| September | 0.174228E+09 | 0.72 | 288.46 | 01-SEP-10:22 | 0.94 |
| October | 0.110155E+09 | 0.72 | 288.46 | 01-OCT-13:32 | 0.94 |
| November | 63826435.31 | 0.71 | 288.46 | 01-NOV-13:42 | 0.95 |
| December | 17509396.90 | 0.31 | 288.46 | 05-DEC-17:01 | 0.96 |
| Annual Sum or Average | 0.121974E+10 | 0.61 | |||
| Minimum of Months | 17509396.90 | 0.28 | 75.08 | 0.93 | |
| Maximum of Months | 0.242858E+09 | 0.90 | 288.46 | 1.08 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT GS2 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 27076005.10 | 0.36 | 90.39 | 08-JAN-01:10 | 1.07 |
| February | 23987420.11 | 0.40 | 291.20 | 12-FEB-06:00 | 0.96 |
| March | 30454845.36 | 0.46 | 291.20 | 02-MAR-17:52 | 0.95 |
| April | 54342615.55 | 0.57 | 291.20 | 01-APR-21:12 | 0.95 |
| May | 0.107226E+09 | 0.65 | 291.20 | 01-MAY-14:12 | 0.94 |
| June | 0.186244E+09 | 0.84 | 291.20 | 01-JUN-09:22 | 0.94 |
| July | 0.230419E+09 | 0.85 | 291.20 | 01-JUL-08:32 | 0.93 |
| August | 0.260256E+09 | 0.90 | 291.20 | 01-AUG-07:32 | 0.94 |
| September | 0.185366E+09 | 0.72 | 291.20 | 01-SEP-10:22 | 0.94 |
| October | 0.113973E+09 | 0.72 | 291.20 | 01-OCT-13:32 | 0.94 |
| November | 62613455.72 | 0.70 | 291.20 | 01-NOV-13:42 | 0.95 |
| December | 15702144.21 | 0.28 | 291.20 | 05-DEC-17:01 | 0.96 |
| Annual Sum or Average | 0.129766E+10 | 0.62 | |||
| Minimum of Months | 15702144.21 | 0.28 | 90.39 | 0.93 | |
| Maximum of Months | 0.260256E+09 | 0.90 | 291.20 | 1.07 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT MSW SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 86180718.68 | 0.38 | 667.99 | 29-JAN-17:52 | 0.99 |
| February | 88601136.96 | 0.43 | 830.42 | 12-FEB-06:00 | 0.96 |
| March | 0.138073E+09 | 0.56 | 830.42 | 02-MAR-17:52 | 0.95 |
| April | 0.219435E+09 | 0.65 | 830.42 | 02-APR-14:32 | 0.94 |
| May | 0.341576E+09 | 0.69 | 830.42 | 01-MAY-14:12 | 0.94 |
| June | 0.496692E+09 | 0.85 | 830.42 | 01-JUN-09:22 | 0.94 |
| July | 0.575999E+09 | 0.85 | 830.42 | 01-JUL-08:32 | 0.93 |
| August | 0.626502E+09 | 0.90 | 830.42 | 01-AUG-07:32 | 0.94 |
| September | 0.408931E+09 | 0.73 | 830.42 | 01-SEP-10:22 | 0.94 |
| October | 0.213322E+09 | 0.64 | 830.42 | 01-OCT-13:32 | 0.94 |
| November | 91141157.91 | 0.48 | 830.42 | 01-NOV-13:42 | 0.95 |
| December | 25265852.55 | 0.21 | 830.42 | 10-DEC-15:12 | 0.95 |
| Annual Sum or Average | 0.331172E+10 | 0.61 | |||
| Minimum of Months | 25265852.55 | 0.21 | 667.99 | 0.93 | |
| Maximum of Months | 0.626502E+09 | 0.90 | 830.42 | 0.99 |
Report: FanReportMonthly
For: M SW APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: M SW APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: SPLIT MNW SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.197281E+09 | 0.78 | 304.32 | 08-JAN-01:10 | 1.06 |
| February | 0.120297E+09 | 0.56 | 811.40 | 12-FEB-06:00 | 0.96 |
| March | 63046366.74 | 0.33 | 811.40 | 04-MAR-16:52 | 0.94 |
| April | 0.167387E+09 | 0.58 | 811.40 | 02-APR-15:32 | 0.94 |
| May | 0.318798E+09 | 0.68 | 811.40 | 01-MAY-14:22 | 0.94 |
| June | 0.492881E+09 | 0.85 | 811.40 | 01-JUN-09:12 | 0.94 |
| July | 0.566823E+09 | 0.86 | 811.40 | 01-JUL-08:62 | 0.93 |
| August | 0.588014E+09 | 0.90 | 811.40 | 01-AUG-07:22 | 0.94 |
| September | 0.341988E+09 | 0.71 | 811.40 | 01-SEP-11:02 | 0.94 |
| October | 0.116546E+09 | 0.46 | 811.40 | 01-OCT-14:22 | 0.94 |
| November | 21829682.93 | 0.19 | 811.40 | 02-NOV-21:52 | 0.94 |
| December | 53099693.31 | 0.46 | 367.64 | 13-DEC-21:02 | 1.03 |
| Annual Sum or Average | 0.304799E+10 | 0.61 | |||
| Minimum of Months | 21829682.93 | 0.19 | 304.32 | 0.93 | |
| Maximum of Months | 0.588014E+09 | 0.90 | 811.40 | 1.06 |
Report: FanReportMonthly
For: M NW APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: M NW APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: SPLIT MSE SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 85712351.13 | 0.39 | 544.67 | 29-JAN-17:52 | 1.00 |
| February | 89371195.63 | 0.42 | 756.26 | 12-FEB-06:00 | 0.96 |
| March | 0.132097E+09 | 0.56 | 756.26 | 02-MAR-17:52 | 0.95 |
| April | 0.213327E+09 | 0.65 | 756.26 | 02-APR-14:32 | 0.94 |
| May | 0.337159E+09 | 0.68 | 756.26 | 01-MAY-14:12 | 0.94 |
| June | 0.492678E+09 | 0.85 | 756.26 | 01-JUN-09:22 | 0.94 |
| July | 0.571346E+09 | 0.85 | 756.26 | 01-JUL-08:32 | 0.93 |
| August | 0.614746E+09 | 0.90 | 756.26 | 01-AUG-07:32 | 0.94 |
| September | 0.401387E+09 | 0.73 | 756.26 | 01-SEP-10:22 | 0.94 |
| October | 0.209773E+09 | 0.63 | 756.26 | 01-OCT-13:32 | 0.94 |
| November | 89189771.01 | 0.49 | 756.26 | 01-NOV-13:42 | 0.95 |
| December | 25131384.41 | 0.21 | 756.26 | 10-DEC-15:12 | 0.95 |
| Annual Sum or Average | 0.326192E+10 | 0.61 | |||
| Minimum of Months | 25131384.41 | 0.21 | 544.67 | 0.93 | |
| Maximum of Months | 0.614746E+09 | 0.90 | 756.26 | 1.00 |
Report: FanReportMonthly
For: M SE APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: M SE APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: SPLIT MNE SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.193194E+09 | 0.81 | 303.02 | 08-JAN-01:10 | 1.05 |
| February | 0.116822E+09 | 0.58 | 737.63 | 12-FEB-06:00 | 0.96 |
| March | 57298685.54 | 0.34 | 737.63 | 04-MAR-16:52 | 0.94 |
| April | 0.161806E+09 | 0.59 | 737.63 | 02-APR-15:32 | 0.94 |
| May | 0.315326E+09 | 0.68 | 737.63 | 01-MAY-14:22 | 0.94 |
| June | 0.489788E+09 | 0.85 | 737.63 | 01-JUN-09:12 | 0.94 |
| July | 0.563236E+09 | 0.86 | 737.63 | 01-JUL-08:62 | 0.94 |
| August | 0.577677E+09 | 0.90 | 737.63 | 01-AUG-07:22 | 0.94 |
| September | 0.335927E+09 | 0.71 | 737.63 | 01-SEP-11:02 | 0.94 |
| October | 0.114252E+09 | 0.45 | 737.63 | 01-OCT-14:22 | 0.94 |
| November | 19170106.38 | 0.18 | 737.63 | 02-NOV-21:52 | 0.94 |
| December | 49253915.60 | 0.45 | 374.65 | 13-DEC-21:02 | 1.02 |
| Annual Sum or Average | 0.299375E+10 | 0.62 | |||
| Minimum of Months | 19170106.38 | 0.18 | 303.02 | 0.94 | |
| Maximum of Months | 0.577677E+09 | 0.90 | 737.63 | 1.05 |
Report: FanReportMonthly
For: M NE APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: M NE APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: SPLIT MN1 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 76483022.99 | 0.56 | 164.12 | 08-JAN-01:10 | 1.08 |
| February | 57687645.79 | 0.47 | 651.95 | 12-FEB-06:00 | 0.96 |
| March | 74172722.72 | 0.51 | 651.95 | 02-MAR-17:52 | 0.95 |
| April | 0.154398E+09 | 0.62 | 651.95 | 01-APR-21:12 | 0.95 |
| May | 0.271137E+09 | 0.67 | 651.95 | 01-MAY-07:12 | 0.94 |
| June | 0.400891E+09 | 0.84 | 651.95 | 01-JUN-09:12 | 0.94 |
| July | 0.459536E+09 | 0.85 | 651.95 | 01-JUL-08:62 | 0.93 |
| August | 0.474993E+09 | 0.90 | 651.95 | 01-AUG-07:22 | 0.94 |
| September | 0.294120E+09 | 0.70 | 651.95 | 01-SEP-11:02 | 0.94 |
| October | 0.126221E+09 | 0.60 | 651.95 | 01-OCT-14:22 | 0.94 |
| November | 34602767.34 | 0.31 | 651.95 | 01-NOV-21:52 | 0.94 |
| December | 6155160.44 | 0.10 | 651.95 | 13-DEC-21:02 | 0.94 |
| Annual Sum or Average | 0.243040E+10 | 0.60 | |||
| Minimum of Months | 6155160.44 | 0.10 | 164.12 | 0.93 | |
| Maximum of Months | 0.474993E+09 | 0.90 | 651.95 | 1.08 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: SPLIT MN2 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 76581980.54 | 0.56 | 164.12 | 08-JAN-01:10 | 1.08 |
| February | 57942051.74 | 0.47 | 649.99 | 12-FEB-06:00 | 0.96 |
| March | 73901792.92 | 0.51 | 649.99 | 02-MAR-17:52 | 0.95 |
| April | 0.154625E+09 | 0.62 | 649.99 | 01-APR-21:12 | 0.95 |
| May | 0.271768E+09 | 0.67 | 649.99 | 01-MAY-07:12 | 0.94 |
| June | 0.401404E+09 | 0.84 | 649.99 | 01-JUN-09:12 | 0.94 |
| July | 0.459754E+09 | 0.85 | 649.99 | 01-JUL-08:62 | 0.93 |
| August | 0.474989E+09 | 0.90 | 649.99 | 01-AUG-07:22 | 0.94 |
| September | 0.294475E+09 | 0.70 | 649.99 | 01-SEP-11:02 | 0.94 |
| October | 0.126105E+09 | 0.60 | 649.99 | 01-OCT-14:22 | 0.94 |
| November | 34465887.84 | 0.32 | 649.99 | 01-NOV-21:52 | 0.94 |
| December | 6207214.25 | 0.10 | 649.99 | 13-DEC-21:02 | 0.94 |
| Annual Sum or Average | 0.243222E+10 | 0.60 | |||
| Minimum of Months | 6207214.25 | 0.10 | 164.12 | 0.93 | |
| Maximum of Months | 0.474989E+09 | 0.90 | 649.99 | 1.08 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: SPLIT MS1 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 27887060.23 | 0.24 | 675.19 | 29-JAN-17:52 | 0.96 |
| February | 63151001.94 | 0.32 | 675.19 | 12-FEB-06:00 | 0.96 |
| March | 0.159561E+09 | 0.71 | 675.19 | 02-MAR-17:52 | 0.95 |
| April | 0.206116E+09 | 0.68 | 675.19 | 01-APR-21:12 | 0.95 |
| May | 0.292731E+09 | 0.68 | 675.19 | 01-MAY-07:12 | 0.94 |
| June | 0.404119E+09 | 0.84 | 675.19 | 01-JUN-09:22 | 0.94 |
| July | 0.468260E+09 | 0.85 | 675.19 | 01-JUL-08:32 | 0.93 |
| August | 0.512320E+09 | 0.90 | 675.19 | 01-AUG-07:32 | 0.94 |
| September | 0.359026E+09 | 0.73 | 675.19 | 01-SEP-10:22 | 0.94 |
| October | 0.228057E+09 | 0.71 | 675.19 | 01-OCT-13:32 | 0.94 |
| November | 0.138267E+09 | 0.68 | 675.19 | 01-NOV-13:42 | 0.95 |
| December | 57288972.23 | 0.38 | 675.19 | 05-DEC-17:01 | 0.96 |
| Annual Sum or Average | 0.291679E+10 | 0.64 | |||
| Minimum of Months | 27887060.23 | 0.24 | 675.19 | 0.93 | |
| Maximum of Months | 0.512320E+09 | 0.90 | 675.19 | 0.96 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: SPLIT MS2 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 28095661.77 | 0.24 | 674.22 | 29-JAN-17:52 | 0.96 |
| February | 63389537.29 | 0.32 | 674.22 | 12-FEB-06:00 | 0.96 |
| March | 0.158982E+09 | 0.71 | 674.22 | 02-MAR-17:52 | 0.95 |
| April | 0.206363E+09 | 0.68 | 674.22 | 01-APR-21:12 | 0.95 |
| May | 0.293317E+09 | 0.68 | 674.22 | 01-MAY-07:12 | 0.94 |
| June | 0.404732E+09 | 0.84 | 674.22 | 01-JUN-09:22 | 0.94 |
| July | 0.468523E+09 | 0.85 | 674.22 | 01-JUL-08:32 | 0.93 |
| August | 0.512390E+09 | 0.90 | 674.22 | 01-AUG-07:32 | 0.94 |
| September | 0.359313E+09 | 0.73 | 674.22 | 01-SEP-10:22 | 0.94 |
| October | 0.228185E+09 | 0.71 | 674.22 | 01-OCT-13:32 | 0.94 |
| November | 0.138214E+09 | 0.68 | 674.22 | 01-NOV-13:42 | 0.95 |
| December | 57707312.39 | 0.38 | 674.22 | 05-DEC-17:01 | 0.96 |
| Annual Sum or Average | 0.291921E+10 | 0.64 | |||
| Minimum of Months | 28095661.77 | 0.24 | 674.22 | 0.93 | |
| Maximum of Months | 0.512390E+09 | 0.90 | 674.22 | 0.96 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.76 | 46.34 | 01-JAN-00:10 | 0.76 |
| February | 0.112112E+09 | 0.76 | 46.34 | 01-FEB-00:10 | 0.76 |
| March | 0.124124E+09 | 0.76 | 46.34 | 01-MAR-00:10 | 0.76 |
| April | 0.120120E+09 | 0.75 | 46.34 | 01-APR-00:10 | 0.76 |
| May | 0.124124E+09 | 0.75 | 46.34 | 01-MAY-00:10 | 0.75 |
| June | 0.120120E+09 | 0.75 | 46.34 | 01-JUN-00:10 | 0.75 |
| July | 0.124124E+09 | 0.75 | 46.34 | 01-JUL-00:10 | 0.75 |
| August | 0.124124E+09 | 0.75 | 46.34 | 01-AUG-00:10 | 0.75 |
| September | 0.120120E+09 | 0.75 | 46.34 | 01-SEP-00:10 | 0.75 |
| October | 0.124124E+09 | 0.75 | 46.34 | 01-OCT-00:10 | 0.75 |
| November | 0.120120E+09 | 0.76 | 46.34 | 01-NOV-00:10 | 0.76 |
| December | 0.124124E+09 | 0.76 | 46.34 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.146145E+10 | 0.75 | |||
| Minimum of Months | 0.112112E+09 | 0.75 | 46.34 | 0.75 | |
| Maximum of Months | 0.124124E+09 | 0.76 | 46.34 | 0.76 |
Report: FanReportMonthly
For: SPLIT TSW SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.175123E+09 | 0.77 | 469.58 | 29-JAN-17:52 | 0.96 |
| February | 0.111118E+09 | 0.57 | 469.58 | 12-FEB-06:00 | 0.96 |
| March | 47976684.09 | 0.35 | 469.58 | 03-MAR-16:42 | 0.95 |
| April | 92581099.31 | 0.44 | 469.58 | 02-APR-14:32 | 0.94 |
| May | 0.165237E+09 | 0.61 | 469.58 | 01-MAY-14:12 | 0.94 |
| June | 0.268254E+09 | 0.83 | 469.58 | 01-JUN-09:22 | 0.94 |
| July | 0.316732E+09 | 0.85 | 469.58 | 01-JUL-08:32 | 0.93 |
| August | 0.344984E+09 | 0.90 | 469.58 | 01-AUG-07:32 | 0.93 |
| September | 0.198914E+09 | 0.67 | 469.58 | 01-SEP-10:22 | 0.94 |
| October | 80563361.31 | 0.38 | 469.58 | 01-OCT-13:32 | 0.94 |
| November | 43404656.84 | 0.37 | 469.58 | 01-NOV-13:42 | 0.95 |
| December | 90946084.35 | 0.66 | 469.58 | 10-DEC-15:12 | 0.95 |
| Annual Sum or Average | 0.193583E+10 | 0.62 | |||
| Minimum of Months | 43404656.84 | 0.35 | 469.58 | 0.93 | |
| Maximum of Months | 0.344984E+09 | 0.90 | 469.58 | 0.96 |
Report: FanReportMonthly
For: T SW APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: T SW APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT TNW SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.235425E+09 | 0.96 | 275.50 | 14-JAN-07:00 | 1.02 |
| February | 0.138982E+09 | 0.66 | 464.27 | 12-FEB-06:00 | 0.96 |
| March | 34656216.19 | 0.33 | 464.27 | 04-MAR-16:52 | 0.94 |
| April | 71041784.19 | 0.39 | 464.27 | 02-APR-15:32 | 0.94 |
| May | 0.153241E+09 | 0.61 | 464.27 | 01-MAY-14:22 | 0.94 |
| June | 0.266013E+09 | 0.83 | 464.27 | 01-JUN-09:12 | 0.94 |
| July | 0.312228E+09 | 0.86 | 464.27 | 01-JUL-08:62 | 0.93 |
| August | 0.324742E+09 | 0.90 | 464.27 | 01-AUG-07:22 | 0.93 |
| September | 0.163989E+09 | 0.65 | 464.27 | 01-SEP-11:02 | 0.94 |
| October | 46185366.16 | 0.30 | 464.27 | 01-OCT-14:22 | 0.94 |
| November | 49990047.41 | 0.46 | 464.27 | 02-NOV-21:52 | 0.94 |
| December | 0.129446E+09 | 0.84 | 225.28 | 18-DEC-07:00 | 1.04 |
| Annual Sum or Average | 0.192594E+10 | 0.65 | |||
| Minimum of Months | 34656216.19 | 0.30 | 225.28 | 0.93 | |
| Maximum of Months | 0.324742E+09 | 0.96 | 464.27 | 1.04 |
Report: FanReportMonthly
For: T NW APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: T NW APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT TSE SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.169753E+09 | 0.75 | 415.25 | 29-JAN-17:52 | 0.96 |
| February | 0.107579E+09 | 0.57 | 415.25 | 12-FEB-06:00 | 0.96 |
| March | 43729295.90 | 0.35 | 415.25 | 03-MAR-16:42 | 0.95 |
| April | 87537245.94 | 0.43 | 415.25 | 02-APR-14:32 | 0.94 |
| May | 0.161354E+09 | 0.61 | 415.25 | 01-MAY-14:12 | 0.94 |
| June | 0.264928E+09 | 0.83 | 415.25 | 01-JUN-09:22 | 0.94 |
| July | 0.313109E+09 | 0.85 | 415.25 | 01-JUL-08:32 | 0.93 |
| August | 0.337481E+09 | 0.91 | 415.25 | 01-AUG-07:32 | 0.94 |
| September | 0.194356E+09 | 0.67 | 415.25 | 01-SEP-10:22 | 0.94 |
| October | 77399758.60 | 0.38 | 415.25 | 01-OCT-13:32 | 0.94 |
| November | 40100337.63 | 0.36 | 415.25 | 01-NOV-13:42 | 0.95 |
| December | 86593258.30 | 0.64 | 415.25 | 10-DEC-15:12 | 0.95 |
| Annual Sum or Average | 0.188392E+10 | 0.61 | |||
| Minimum of Months | 40100337.63 | 0.35 | 415.25 | 0.93 | |
| Maximum of Months | 0.337481E+09 | 0.91 | 415.25 | 0.96 |
Report: FanReportMonthly
For: T SE APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: T SE APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT TNE SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.229804E+09 | 0.96 | 270.80 | 14-JAN-07:00 | 1.01 |
| February | 0.133640E+09 | 0.65 | 409.90 | 12-FEB-05:40 | 0.96 |
| March | 30375561.20 | 0.31 | 409.90 | 08-MAR-15:32 | 0.95 |
| April | 66275726.94 | 0.37 | 409.90 | 02-APR-15:32 | 0.94 |
| May | 0.149678E+09 | 0.60 | 409.90 | 01-MAY-14:22 | 0.94 |
| June | 0.262994E+09 | 0.83 | 409.90 | 01-JUN-09:12 | 0.94 |
| July | 0.308821E+09 | 0.86 | 409.90 | 01-JUL-08:62 | 0.93 |
| August | 0.317722E+09 | 0.90 | 409.90 | 01-AUG-07:22 | 0.94 |
| September | 0.159876E+09 | 0.65 | 409.90 | 01-SEP-11:02 | 0.94 |
| October | 43642850.65 | 0.29 | 409.90 | 01-OCT-14:22 | 0.94 |
| November | 46668563.22 | 0.44 | 409.90 | 03-NOV-21:52 | 0.94 |
| December | 0.124459E+09 | 0.86 | 220.99 | 18-DEC-07:00 | 1.03 |
| Annual Sum or Average | 0.187396E+10 | 0.64 | |||
| Minimum of Months | 30375561.20 | 0.29 | 220.99 | 0.93 | |
| Maximum of Months | 0.317722E+09 | 0.96 | 409.90 | 1.03 |
Report: FanReportMonthly
For: T NE APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: T NE APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT TN1 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.156068E+09 | 0.93 | 189.03 | 14-JAN-07:00 | 1.04 |
| February | 90970778.82 | 0.62 | 378.56 | 12-FEB-06:00 | 0.96 |
| March | 21720016.01 | 0.26 | 378.56 | 04-MAR-16:52 | 0.94 |
| April | 58431406.14 | 0.44 | 378.56 | 02-APR-15:32 | 0.94 |
| May | 0.129425E+09 | 0.62 | 378.56 | 01-MAY-14:22 | 0.94 |
| June | 0.219954E+09 | 0.85 | 378.56 | 01-JUN-09:12 | 0.94 |
| July | 0.258264E+09 | 0.86 | 378.56 | 01-JUL-08:62 | 0.93 |
| August | 0.267719E+09 | 0.90 | 378.56 | 01-AUG-07:22 | 0.94 |
| September | 0.140072E+09 | 0.68 | 378.56 | 01-SEP-11:02 | 0.94 |
| October | 37138986.00 | 0.26 | 378.56 | 01-OCT-14:22 | 0.94 |
| November | 27284303.48 | 0.37 | 378.56 | 02-NOV-21:52 | 0.94 |
| December | 78709019.10 | 0.76 | 273.81 | 12-DEC-22:52 | 0.99 |
| Annual Sum or Average | 0.148576E+10 | 0.63 | |||
| Minimum of Months | 21720016.01 | 0.26 | 189.03 | 0.93 | |
| Maximum of Months | 0.267719E+09 | 0.93 | 378.56 | 1.04 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT TN2 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.156042E+09 | 0.94 | 189.10 | 14-JAN-07:00 | 1.04 |
| February | 90929744.55 | 0.62 | 377.02 | 12-FEB-06:00 | 0.96 |
| March | 21664289.32 | 0.27 | 377.02 | 04-MAR-16:52 | 0.94 |
| April | 58534056.57 | 0.44 | 377.02 | 02-APR-15:32 | 0.94 |
| May | 0.129814E+09 | 0.62 | 377.02 | 01-MAY-14:22 | 0.94 |
| June | 0.220258E+09 | 0.85 | 377.02 | 01-JUN-09:12 | 0.94 |
| July | 0.258408E+09 | 0.86 | 377.02 | 01-JUL-08:62 | 0.93 |
| August | 0.267679E+09 | 0.90 | 377.02 | 01-AUG-07:22 | 0.94 |
| September | 0.140264E+09 | 0.68 | 377.02 | 01-SEP-11:02 | 0.94 |
| October | 37226730.93 | 0.26 | 377.02 | 01-OCT-14:22 | 0.94 |
| November | 27279278.18 | 0.37 | 377.02 | 02-NOV-21:52 | 0.94 |
| December | 78704195.34 | 0.76 | 269.26 | 12-DEC-22:52 | 0.99 |
| Annual Sum or Average | 0.148680E+10 | 0.63 | |||
| Minimum of Months | 21664289.32 | 0.26 | 189.10 | 0.93 | |
| Maximum of Months | 0.267679E+09 | 0.94 | 377.02 | 1.04 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT TS1 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.100718E+09 | 0.66 | 384.83 | 29-JAN-17:52 | 0.96 |
| February | 68196796.19 | 0.51 | 384.83 | 12-FEB-06:00 | 0.96 |
| March | 38870938.72 | 0.32 | 384.83 | 03-MAR-16:42 | 0.95 |
| April | 80103711.51 | 0.49 | 384.83 | 02-APR-14:32 | 0.94 |
| May | 0.141351E+09 | 0.63 | 384.83 | 01-MAY-14:12 | 0.94 |
| June | 0.222156E+09 | 0.84 | 384.83 | 01-JUN-09:22 | 0.94 |
| July | 0.262938E+09 | 0.85 | 384.83 | 01-JUL-08:32 | 0.93 |
| August | 0.288022E+09 | 0.90 | 384.83 | 01-AUG-07:32 | 0.93 |
| September | 0.175165E+09 | 0.71 | 384.83 | 01-SEP-10:22 | 0.94 |
| October | 74066248.28 | 0.41 | 384.83 | 01-OCT-13:32 | 0.94 |
| November | 30190949.64 | 0.32 | 384.83 | 01-NOV-13:42 | 0.95 |
| December | 48069680.62 | 0.56 | 384.83 | 10-DEC-15:12 | 0.95 |
| Annual Sum or Average | 0.152985E+10 | 0.60 | |||
| Minimum of Months | 30190949.64 | 0.32 | 384.83 | 0.93 | |
| Maximum of Months | 0.288022E+09 | 0.90 | 384.83 | 0.96 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: SPLIT TS2 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.100898E+09 | 0.66 | 383.28 | 29-JAN-17:52 | 0.96 |
| February | 68383696.16 | 0.51 | 383.28 | 12-FEB-06:00 | 0.96 |
| March | 38911783.24 | 0.32 | 383.28 | 03-MAR-16:42 | 0.95 |
| April | 80238910.37 | 0.50 | 383.28 | 02-APR-14:32 | 0.94 |
| May | 0.141593E+09 | 0.63 | 383.28 | 01-MAY-14:12 | 0.94 |
| June | 0.222339E+09 | 0.84 | 383.28 | 01-JUN-09:22 | 0.94 |
| July | 0.262886E+09 | 0.85 | 383.28 | 01-JUL-08:32 | 0.93 |
| August | 0.287804E+09 | 0.90 | 383.28 | 01-AUG-07:32 | 0.93 |
| September | 0.175168E+09 | 0.71 | 383.28 | 01-SEP-10:22 | 0.94 |
| October | 74202238.93 | 0.42 | 383.28 | 01-OCT-13:32 | 0.94 |
| November | 30168006.40 | 0.32 | 383.28 | 01-NOV-13:42 | 0.95 |
| December | 48205491.93 | 0.56 | 383.28 | 10-DEC-15:12 | 0.95 |
| Annual Sum or Average | 0.153080E+10 | 0.60 | |||
| Minimum of Months | 30168006.40 | 0.32 | 383.28 | 0.93 | |
| Maximum of Months | 0.287804E+09 | 0.90 | 383.28 | 0.96 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.76 | 23.17 | 01-JAN-00:10 | 0.76 |
| February | 56055778.84 | 0.76 | 23.17 | 01-FEB-00:10 | 0.76 |
| March | 62061755.14 | 0.76 | 23.17 | 01-MAR-00:10 | 0.76 |
| April | 60059763.04 | 0.75 | 23.17 | 01-APR-00:10 | 0.76 |
| May | 62061755.14 | 0.75 | 23.17 | 01-MAY-00:10 | 0.75 |
| June | 60059763.04 | 0.75 | 23.17 | 01-JUN-00:10 | 0.75 |
| July | 62061755.14 | 0.75 | 23.17 | 01-JUL-00:10 | 0.75 |
| August | 62061755.14 | 0.75 | 23.17 | 01-AUG-00:10 | 0.75 |
| September | 60059763.04 | 0.75 | 23.17 | 01-SEP-00:10 | 0.75 |
| October | 62061755.14 | 0.75 | 23.17 | 01-OCT-00:10 | 0.75 |
| November | 60059763.04 | 0.76 | 23.17 | 01-NOV-00:10 | 0.76 |
| December | 62061755.14 | 0.76 | 23.17 | 01-DEC-00:10 | 0.76 |
| Annual Sum or Average | 0.730727E+09 | 0.75 | |||
| Minimum of Months | 56055778.84 | 0.75 | 23.17 | 0.75 | |
| Maximum of Months | 62061755.14 | 0.76 | 23.17 | 0.76 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 38818862.27 | 11645658.68 | 14.49 | 01-JAN-00:10 | 4.35 | 4.35 | 55.35 | 0.11 |
| February | 35062198.18 | 10518659.46 | 14.49 | 01-FEB-00:10 | 4.35 | 4.35 | 55.26 | 0.11 |
| March | 38818862.27 | 11645658.68 | 14.49 | 01-MAR-00:10 | 4.35 | 4.35 | 55.33 | 0.11 |
| April | 37566640.91 | 11269992.27 | 14.49 | 01-APR-00:10 | 4.35 | 4.35 | 58.05 | 0.11 |
| May | 38818862.27 | 11645658.68 | 14.49 | 01-MAY-00:10 | 4.35 | 4.35 | 58.19 | 0.11 |
| June | 37566640.91 | 11269992.27 | 14.49 | 01-JUN-00:10 | 4.35 | 4.35 | 58.33 | 0.11 |
| July | 38818862.27 | 11645658.68 | 14.49 | 01-JUL-00:10 | 4.35 | 4.35 | 58.44 | 0.11 |
| August | 38818862.27 | 11645658.68 | 14.49 | 01-AUG-00:10 | 4.35 | 4.35 | 58.49 | 0.11 |
| September | 37566640.91 | 11269992.27 | 14.49 | 01-SEP-00:10 | 4.35 | 4.35 | 58.45 | 0.11 |
| October | 38818862.27 | 11645658.68 | 14.49 | 01-OCT-00:10 | 4.35 | 4.35 | 58.35 | 0.11 |
| November | 37566640.91 | 11269992.27 | 14.49 | 01-NOV-00:10 | 4.35 | 4.35 | 58.20 | 0.11 |
| December | 38818862.27 | 11645658.68 | 14.49 | 01-DEC-00:10 | 4.35 | 4.35 | 55.60 | 0.11 |
| Annual Sum or Average | 0.457061E+09 | 0.137118E+09 | ||||||
| Minimum of Months | 35062198.18 | 10518659.46 | 14.49 | 4.35 | 4.35 | 55.26 | 0.11 | |
| Maximum of Months | 38818862.27 | 11645658.68 | 14.49 | 4.35 | 4.35 | 58.49 | 0.11 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 55.35 | 59.95 | 11508.80 | 22119.48 | 31-JAN-07:50 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 55.26 | 59.95 | 11531.24 | 22120.05 | 01-FEB-07:40 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 55.33 | 59.95 | 11152.94 | 21766.26 | 01-MAR-07:40 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 58.05 | 59.95 | 10453.15 | 20648.38 | 01-APR-06:40 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 58.19 | 59.95 | 9622.99 | 19129.00 | 01-MAY-06:40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 58.33 | 59.95 | 8885.59 | 17535.73 | 01-JUN-06:50 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 58.44 | 59.94 | 8441.04 | 16379.89 | 01-JUL-06:50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 58.49 | 59.95 | 8409.48 | 16264.26 | 31-AUG-06:50 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 58.45 | 59.95 | 8800.33 | 17335.53 | 30-SEP-06:50 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 58.35 | 59.95 | 9507.02 | 18896.28 | 31-OCT-06:40 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 58.20 | 59.95 | 10337.40 | 20445.93 | 30-NOV-07:40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 55.60 | 59.95 | 11068.79 | 21650.29 | 31-DEC-07:40 |
| Annual Sum or Average | 0.00 | 9967.70 | ||||||
| Minimum of Months | 0.00 | 0.00 | 55.26 | 59.94 | 8409.48 | 16264.26 | ||
| Maximum of Months | 0.00 | 0.00 | 58.49 | 59.95 | 11531.24 | 22120.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.387471E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.235476E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 84527131.59 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.203459E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.488012E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.954601E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.120084E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.136769E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.909126E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.477491E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.199103E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 32242931.21 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.654004E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 32242931.21 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.136769E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.665333E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.384206E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 26264592.96 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.122493E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.438535E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.948187E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.118338E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.128610E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.769985E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.274804E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 40351805.05 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.138597E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.627824E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 26264592.96 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.128610E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.128648E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.108824E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.112172E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.117546E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.139283E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.164782E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.177138E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.192367E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.157451E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.135078E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.113173E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.109580E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.165604E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108824E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.192367E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.660548E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.377992E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 21735661.86 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.117862E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.440058E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.954078E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.119046E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.127764E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.764829E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.272573E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 37298333.60 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.130354E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.624544E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21735661.86 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.127764E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.369694E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.214120E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 23743500.08 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.144845E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.430193E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.833179E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.102352E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.109692E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.686860E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.297251E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 72759733.68 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 14069575.99 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.520716E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 14069575.99 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.109692E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.369868E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.214022E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 23654748.69 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.145097E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.431466E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.834535E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.102470E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.109718E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.687596E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.297342E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 72474602.49 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 14100627.62 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.521203E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 14100627.62 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.109718E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.127093E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.102705E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.142255E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.245351E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.481802E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.842182E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.104459E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.118269E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.830082E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.515355E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.298351E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 81985650.62 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.589444E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 81985650.62 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.118269E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.173007E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.124583E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.141010E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.254568E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.508401E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.900317E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.112320E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.126416E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.881310E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.532368E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.291869E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 73311974.54 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.626810E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 73311974.54 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.126416E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.450022E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.396960E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.613732E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.985545E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.155362E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.230776E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.270082E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.292843E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.187159E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.959431E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.404153E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.117454E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.152895E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.117454E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.292843E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.995460E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.561573E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.281974E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.752541E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.144986E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.228861E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.265605E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.274836E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.156644E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.526502E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.104185E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.275674E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.142072E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104185E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.274836E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.452749E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.406335E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.593622E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.969166E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.155135E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.231534E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.270891E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.290645E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.185846E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.954180E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.400050E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.117832E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.152344E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.117832E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.290645E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.987166E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.553435E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.259062E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.735684E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.145005E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.229906E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.266727E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.272970E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.155606E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.521730E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 92694089.91 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.259157E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.141111E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 92694089.91 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.272970E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.422269E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.273531E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.337853E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.708875E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.125926E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.190177E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.220032E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.226913E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.137584E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.581033E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.157463E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 35296208.50 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.115226E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 35296208.50 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.226913E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.423056E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.274804E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.336720E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.710062E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.126253E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.190469E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.220195E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.226973E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.137788E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.580671E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.156876E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 35515141.01 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.115345E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 35515141.01 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.226973E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.150146E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.272377E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.725108E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.946713E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.136117E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.192037E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.224600E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.245022E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.168003E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.104740E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.629016E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.260393E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.136890E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.150146E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.245022E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.151177E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.273617E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.722602E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.948009E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.136413E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.192357E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.224764E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.245097E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.168164E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.104815E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.628848E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.262361E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.137027E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.151177E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.245097E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.871603E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.525661E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.219340E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.417412E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.747031E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.123873E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.147525E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.160095E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.904736E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.364034E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.213915E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.450873E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.902953E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.213915E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.160095E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.115844E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.656683E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.164148E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.322480E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.692516E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.122707E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.145261E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.150618E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.746397E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.212091E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.252955E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.636024E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.902759E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.164148E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.150618E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.855409E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.516094E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.202683E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.399879E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.738558E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.123815E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.147536E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.158492E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.894931E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.354071E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.200749E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.435065E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.889586E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.200749E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.158492E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.114403E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.640386E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.146178E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.304845E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.684743E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.122748E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.145318E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.149110E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.736718E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.202914E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.239323E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.618903E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.888980E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.146178E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.149110E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.798639E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.441903E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.103889E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.267845E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.592819E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.102830E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.121784E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.125883E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.646128E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.171514E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.144106E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.401521E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.707335E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103889E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.125883E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.798787E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.441865E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.103731E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.268439E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.594852E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.103014E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.121902E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.125919E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.647298E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.171996E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.144147E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.401624E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.708108E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103731E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.125919E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.527154E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.330731E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.177646E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.364708E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.647954E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.104017E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.124183E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.135559E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.807732E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.337610E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.148152E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.249323E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.722860E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.148152E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.135559E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.528240E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.331662E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.177914E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.365529E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.649384E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.104153E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.124220E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.135524E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.808138E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.338382E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.148095E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.250043E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.723635E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.148095E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.135524E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 68899659.92 | 0.00 | 0.573604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 46555893.78 | 56169771.43 | 0.352979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 18590079.17 | 0.255849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 44334644.76 | 0.613194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.105068E+09 | 0.148056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.201710E+09 | 0.284228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.251661E+09 | 0.358621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.287824E+09 | 0.412500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.195446E+09 | 0.279857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.104453E+09 | 0.147725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 44080219.25 | 0.600914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 6495542.76 | 75461230.10 | 9822822.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.137512E+10 | 0.179115E+11 | 0.936406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6495542.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.287824E+09 | 0.412500E+10 | 0.573604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.125708E+09 | 0.00 | 0.114159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 76996556.09 | 1000574.79 | 0.697746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5542130.53 | 61429533.37 | 12753719.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 26649699.70 | 0.367966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 94462905.88 | 0.132968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.200665E+09 | 0.282724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.248394E+09 | 0.353801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.270898E+09 | 0.388053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.165547E+09 | 0.236358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 59950169.15 | 0.846757E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 8744907.26 | 0.120007E+09 | 631746.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 23666886.10 | 0.00 | 0.243510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.130723E+10 | 0.153362E+11 | 0.209623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5542130.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.270898E+09 | 0.388053E+10 | 0.114159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.100530E+10 | 1572045.29 | 0.485432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.906482E+09 | 0.114588E+09 | 0.282141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.100227E+10 | 0.441795E+09 | 2215707.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.980745E+09 | 0.733441E+09 | 58860.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.101793E+10 | 0.147109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.995830E+09 | 0.256110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.103771E+10 | 0.290885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.103680E+10 | 0.356052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.999492E+09 | 0.232371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.102070E+10 | 0.131218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.979226E+09 | 0.531823E+09 | 1722047.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.100535E+10 | 0.126462E+09 | 59850443.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.119878E+11 | 0.160871E+11 | 0.831420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.906482E+09 | 1572045.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.103771E+10 | 0.356052E+10 | 0.485432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.123414E+09 | 0.00 | 0.114115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 74763372.34 | 1234697.66 | 0.691703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 4396219.68 | 45938239.83 | 13288865.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 25338607.04 | 0.355545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 93723261.92 | 0.134209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.199680E+09 | 0.286582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.247182E+09 | 0.358870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.266103E+09 | 0.388357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.162564E+09 | 0.236368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 58809100.39 | 0.844066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 8088552.30 | 0.113375E+09 | 73976.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 21877288.66 | 0.00 | 0.228008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128594E+10 | 0.154040E+11 | 0.207423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4396219.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.266103E+09 | 0.388357E+10 | 0.114115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 62586695.43 | 0.00 | 0.556054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 40031764.71 | 1742228.63 | 0.348509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5067598.78 | 71233782.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 30918403.29 | 0.440871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 90885908.62 | 0.131886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.172706E+09 | 0.251183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.210346E+09 | 0.309649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.226101E+09 | 0.334607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.144600E+09 | 0.213213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 63611579.91 | 0.920524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 15748397.75 | 0.220816E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1275871.02 | 995572.82 | 11638394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.106388E+10 | 0.140616E+11 | 0.916201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1275871.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.226101E+09 | 0.334607E+10 | 0.556054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 62604164.11 | 0.00 | 0.556336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 40003398.61 | 1844903.02 | 0.348258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5047428.03 | 70974962.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 30965865.36 | 0.441644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 91140148.73 | 0.132293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.172961E+09 | 0.251623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.210555E+09 | 0.310049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.226116E+09 | 0.334719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.144731E+09 | 0.213464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 63619652.98 | 0.920902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 15684354.04 | 0.219948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1282601.96 | 1010126.51 | 11719821.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.106471E+10 | 0.140778E+11 | 0.916314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1282601.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.226116E+09 | 0.334719E+10 | 0.556336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 19160851.63 | 735970.80 | 0.149321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 20098594.94 | 0.110396E+09 | 81379996.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 30685208.52 | 0.429471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 52293190.33 | 0.746723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.101427E+09 | 0.147898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.173793E+09 | 0.253627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.213709E+09 | 0.315783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.242858E+09 | 0.360708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.174228E+09 | 0.258539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.110155E+09 | 0.160397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 63826435.31 | 0.891056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 17509396.90 | 0.237748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121974E+10 | 0.173856E+11 | 0.230701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 17509396.90 | 735970.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.242858E+09 | 0.360708E+10 | 0.149321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 27076005.10 | 22254.14 | 0.215760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 23987420.11 | 0.106958E+09 | 0.119644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 30454845.36 | 0.425705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 54342615.55 | 0.774684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.107226E+09 | 0.156102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.186244E+09 | 0.271465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.230419E+09 | 0.340014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.260256E+09 | 0.386119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.185366E+09 | 0.274744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.113973E+09 | 0.165731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 62613455.72 | 0.872762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 15702144.21 | 0.212978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.129766E+10 | 0.183349E+11 | 0.335405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 15702144.21 | 22254.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.260256E+09 | 0.386119E+10 | 0.215760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 86180718.68 | 16293199.21 | 0.646039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 88601136.96 | 0.518995E+09 | 0.333390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.138073E+09 | 0.183614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.219435E+09 | 0.297003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.341576E+09 | 0.470720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.496692E+09 | 0.682926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.575999E+09 | 0.799692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.626502E+09 | 0.874113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.408931E+09 | 0.570227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.213322E+09 | 0.295112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 91141157.91 | 0.121823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 25265852.55 | 0.290552E+09 | 30483647.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.331172E+10 | 0.437781E+11 | 0.100991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25265852.55 | 16293199.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.626502E+09 | 0.874113E+10 | 0.646039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.197281E+09 | 0.00 | 0.166108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.120297E+09 | 73763183.18 | 0.932008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 63046366.74 | 0.840954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.167387E+09 | 0.226298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.318798E+09 | 0.439157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.492881E+09 | 0.678148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.566823E+09 | 0.787180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.588014E+09 | 0.820767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.341988E+09 | 0.475902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.116546E+09 | 0.161476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 21829682.93 | 0.236868E+09 | 37541569.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 53099693.31 | 5456313.27 | 0.513891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.304799E+10 | 0.370463E+11 | 0.314452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21829682.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.588014E+09 | 0.820767E+10 | 0.166108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 85712351.13 | 20409797.79 | 0.651810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 89371195.63 | 0.563900E+09 | 0.328908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.132097E+09 | 0.178047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.213327E+09 | 0.293560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.337159E+09 | 0.473263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.492678E+09 | 0.690633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.571346E+09 | 0.809080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.614746E+09 | 0.874467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.401387E+09 | 0.570532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.209773E+09 | 0.295065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 89189771.01 | 0.120843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 25131384.41 | 0.292098E+09 | 31598911.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.326192E+10 | 0.439313E+11 | 0.101232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25131384.41 | 20409797.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.614746E+09 | 0.874467E+10 | 0.651810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.193194E+09 | 0.00 | 0.165463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.116822E+09 | 84403770.55 | 0.917647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 57298685.54 | 0.774287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.161806E+09 | 0.222204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.315326E+09 | 0.442014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.489788E+09 | 0.686682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.563236E+09 | 0.797416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.577677E+09 | 0.821513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.335927E+09 | 0.475990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.114252E+09 | 0.160801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 19170106.38 | 0.217313E+09 | 28834026.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 49253915.60 | 5994836.41 | 0.481671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.299375E+10 | 0.371482E+11 | 0.308278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19170106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.577677E+09 | 0.821513E+10 | 0.165463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 76483022.99 | 0.00 | 0.617886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 57687645.79 | 0.147936E+09 | 0.338490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 74172722.72 | 0.100882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.154398E+09 | 0.214832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.271137E+09 | 0.385387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.400891E+09 | 0.569536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.459536E+09 | 0.660053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.474993E+09 | 0.685681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.294120E+09 | 0.423181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.126221E+09 | 0.178938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 34602767.34 | 0.476368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 6155160.44 | 37458822.91 | 29517824.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.243040E+10 | 0.328467E+11 | 0.985893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6155160.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.474993E+09 | 0.685681E+10 | 0.617886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 76581980.54 | 0.00 | 0.619021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 57942051.74 | 0.151711E+09 | 0.338423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 73901792.92 | 0.100550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.154625E+09 | 0.215237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.271768E+09 | 0.386465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.401404E+09 | 0.570537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.459754E+09 | 0.660676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.474989E+09 | 0.685994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.294475E+09 | 0.423901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.126105E+09 | 0.178849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 34465887.84 | 0.474589E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 6207214.25 | 37591488.32 | 29939443.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.243222E+10 | 0.328860E+11 | 0.987383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6207214.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.474989E+09 | 0.685994E+10 | 0.619021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 27887060.23 | 0.137710E+09 | 0.126860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 63151001.94 | 0.720283E+09 | 30136981.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.159561E+09 | 0.217400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.206116E+09 | 0.287355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.292731E+09 | 0.416578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.404119E+09 | 0.574127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.468260E+09 | 0.672792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.512320E+09 | 0.739512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.359026E+09 | 0.517898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.228057E+09 | 0.323884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.138267E+09 | 0.188664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 57288972.23 | 0.759369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.291679E+10 | 0.409995E+11 | 0.156997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27887060.23 | 0.137710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.512320E+09 | 0.739512E+10 | 0.126860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 28095661.77 | 0.140276E+09 | 0.126966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 63389537.29 | 0.723429E+09 | 30337277.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.158982E+09 | 0.216648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.206363E+09 | 0.287770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.293317E+09 | 0.417530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.404732E+09 | 0.575159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.468523E+09 | 0.673346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.512390E+09 | 0.739810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.359313E+09 | 0.518460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.228185E+09 | 0.324151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.138214E+09 | 0.188621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 57707312.39 | 0.764993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.291921E+10 | 0.410437E+11 | 0.157303E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28095661.77 | 0.140276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.512390E+09 | 0.739810E+10 | 0.126966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.175123E+09 | 27754119.66 | 0.148583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.111118E+09 | 0.137902E+09 | 0.857085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 47976684.09 | 0.510182E+09 | 0.119228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 92581099.31 | 0.120262E+10 | 36600042.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.165237E+09 | 0.225764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.268254E+09 | 0.364377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.316732E+09 | 0.433774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.344984E+09 | 0.474893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.198914E+09 | 0.274216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 80563361.31 | 0.105945E+10 | 58797206.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 43404656.84 | 0.225108E+09 | 0.269075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 90946084.35 | 69202563.21 | 0.874135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.193583E+10 | 0.209625E+11 | 0.370075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 43404656.84 | 27754119.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.344984E+09 | 0.474893E+10 | 0.148583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.235425E+09 | 0.00 | 0.211023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.138982E+09 | 14803132.07 | 0.122549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 34656216.19 | 0.230502E+09 | 0.208054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 71041784.19 | 0.888541E+09 | 53483036.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.153241E+09 | 0.209040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.266013E+09 | 0.361111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.312228E+09 | 0.427141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.324742E+09 | 0.446426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.163989E+09 | 0.225238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 46185366.16 | 0.545677E+09 | 88206352.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 49990047.41 | 27013595.80 | 0.519123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.129446E+09 | 217201.12 | 0.136935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.192594E+10 | 0.183963E+11 | 0.557393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34656216.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.324742E+09 | 0.446426E+10 | 0.211023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.169753E+09 | 19142626.71 | 0.147511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.107579E+09 | 0.141799E+09 | 0.847395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 43729295.90 | 0.465352E+09 | 0.116510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 87537245.94 | 0.116381E+10 | 31905098.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.161354E+09 | 0.225421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.264928E+09 | 0.368059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.313109E+09 | 0.438696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.337481E+09 | 0.474888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.194356E+09 | 0.273957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 77399758.60 | 0.103801E+10 | 58205868.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 40100337.63 | 0.205213E+09 | 0.257764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 86593258.30 | 59318514.94 | 0.854432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.188392E+10 | 0.209029E+11 | 0.364132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40100337.63 | 19142626.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.337481E+09 | 0.474888E+10 | 0.147511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.229804E+09 | 0.00 | 0.210630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.133640E+09 | 13237739.78 | 0.120633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 30375561.20 | 0.194112E+09 | 0.194715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 66275726.94 | 0.847124E+09 | 47895935.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.149678E+09 | 0.208613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.262994E+09 | 0.365056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.308821E+09 | 0.432140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.317722E+09 | 0.446367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.159876E+09 | 0.224275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 43642850.65 | 0.524241E+09 | 86057652.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 46668563.22 | 20874150.99 | 0.494323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.124459E+09 | 134793.85 | 0.134020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.187396E+10 | 0.183642E+11 | 0.547583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30375561.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.317722E+09 | 0.446367E+10 | 0.210630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.156068E+09 | 0.00 | 0.139582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 90970778.82 | 11331200.15 | 0.785506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 21720016.01 | 0.198067E+09 | 84994231.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 58431406.14 | 0.776780E+09 | 19805341.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.129425E+09 | 0.180121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.219954E+09 | 0.304827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.258264E+09 | 0.361155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.267719E+09 | 0.376205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.140072E+09 | 0.196671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 37138986.00 | 0.494386E+09 | 29022333.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 27284303.48 | 37096234.97 | 0.257984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 78709019.10 | 1822558.43 | 0.823161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.148576E+10 | 0.157093E+11 | 0.339629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21720016.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.267719E+09 | 0.376205E+10 | 0.139582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.156042E+09 | 0.00 | 0.139653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 90929744.55 | 11618335.42 | 0.785537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 21664289.32 | 0.196455E+09 | 85867128.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 58534056.57 | 0.778644E+09 | 19814019.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.129814E+09 | 0.180803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.220258E+09 | 0.305479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.258408E+09 | 0.361631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.267679E+09 | 0.376421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.140264E+09 | 0.197088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 37226730.93 | 0.495638E+09 | 29336621.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 27279278.18 | 36433760.67 | 0.258695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 78704195.34 | 1817688.67 | 0.823586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.148680E+10 | 0.157348E+11 | 0.339937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21664289.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.267679E+09 | 0.376421E+10 | 0.139653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.100718E+09 | 32570556.23 | 0.828174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 68196796.19 | 0.151742E+09 | 0.465256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 38870938.72 | 0.492787E+09 | 34017107.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 80103711.51 | 0.109071E+10 | 8943249.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.141351E+09 | 0.197108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.222156E+09 | 0.308109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.262938E+09 | 0.368134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.288022E+09 | 0.405232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.175165E+09 | 0.246895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 74066248.28 | 0.103684E+10 | 14299795.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 30190949.64 | 0.276739E+09 | 93850126.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 48069680.62 | 94019349.21 | 0.407772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.152985E+10 | 0.184302E+11 | 0.185231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30190949.64 | 32570556.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.288022E+09 | 0.405232E+10 | 0.828174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.100898E+09 | 33398393.10 | 0.829684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 68383696.16 | 0.153810E+09 | 0.465985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 38911783.24 | 0.493274E+09 | 34399207.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 80238910.37 | 0.109350E+10 | 8948264.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.141593E+09 | 0.197639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.222339E+09 | 0.308645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.262886E+09 | 0.368395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.287804E+09 | 0.405286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.175168E+09 | 0.247131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 74202238.93 | 0.103954E+10 | 14464161.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 30168006.40 | 0.276821E+09 | 93764457.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 48205491.93 | 95486648.90 | 0.408252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.153080E+10 | 0.184568E+11 | 0.185550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30168006.40 | 33398393.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.287804E+09 | 0.405286E+10 | 0.829684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 68899659.92 | 0.00 | 0.00 | 0.318572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 46555893.78 | 0.00 | 0.00 | 0.166618E+09 | 14308323.18 | 7994106.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 18590079.17 | 0.00 | 0.00 | 0.00 | 65937052.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 44334644.76 | 0.00 | 0.00 | 0.00 | 0.159124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.105068E+09 | 0.00 | 0.00 | 0.00 | 0.382945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.201710E+09 | 0.00 | 0.00 | 0.00 | 0.752891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.251661E+09 | 0.00 | 0.00 | 0.00 | 0.949179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.287824E+09 | 0.00 | 0.00 | 0.00 | 0.107987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.195446E+09 | 0.00 | 0.00 | 0.00 | 0.713680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.104453E+09 | 0.00 | 0.00 | 0.00 | 0.373038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 44080219.25 | 0.00 | 0.00 | 353089.53 | 0.154669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 6495542.76 | 0.00 | 0.00 | 6046393.17 | 19700995.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.137512E+10 | 0.00 | 0.00 | 0.491589E+09 | 0.466534E+10 | 7994106.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6495542.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.287824E+09 | 0.00 | 0.00 | 0.318572E+09 | 0.107987E+10 | 7994106.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.125708E+09 | 0.00 | 0.00 | 0.539625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 76996556.09 | 0.00 | 0.00 | 0.297726E+09 | 264859.11 | 9218573.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5542130.53 | 0.00 | 0.00 | 4492513.73 | 16229948.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 26649699.70 | 0.00 | 0.00 | 0.00 | 95843740.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 94462905.88 | 0.00 | 0.00 | 0.00 | 0.344072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.200665E+09 | 0.00 | 0.00 | 0.00 | 0.747521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.248394E+09 | 0.00 | 0.00 | 0.00 | 0.934986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.270898E+09 | 0.00 | 0.00 | 0.00 | 0.101520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.165547E+09 | 0.00 | 0.00 | 0.00 | 0.604438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 59950169.15 | 0.00 | 0.00 | 0.00 | 0.214854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 8744907.26 | 0.00 | 0.00 | 985596.98 | 30621300.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 23666886.10 | 0.00 | 0.00 | 0.114930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.130723E+10 | 0.00 | 0.00 | 0.957759E+09 | 0.400403E+10 | 9218573.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5542130.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.270898E+09 | 0.00 | 0.00 | 0.539625E+09 | 0.101520E+10 | 9218573.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.100530E+10 | 0.00 | 0.00 | 0.259042E+09 | 420014.02 | 21718823.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.906482E+09 | 0.00 | 0.00 | 0.135627E+09 | 30481821.29 | 15646050.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.100227E+10 | 0.00 | 0.00 | 4201853.38 | 0.115252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.980745E+09 | 0.00 | 0.00 | 3717735.86 | 0.190999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.101793E+10 | 0.00 | 0.00 | 0.00 | 0.374903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.995830E+09 | 0.00 | 0.00 | 0.00 | 0.651991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.103771E+10 | 0.00 | 0.00 | 0.00 | 0.733673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.103680E+10 | 0.00 | 0.00 | 0.00 | 0.886866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.999492E+09 | 0.00 | 0.00 | 0.00 | 0.575019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.102070E+10 | 0.00 | 0.00 | 1410000.00 | 0.328673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.979226E+09 | 0.00 | 0.00 | 13858837.28 | 0.138471E+09 | 174110.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.100535E+10 | 0.00 | 0.00 | 53859318.87 | 32929376.24 | 3655869.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.119878E+11 | 0.00 | 0.00 | 0.471717E+09 | 0.405968E+10 | 41194853.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.906482E+09 | 0.00 | 0.00 | 0.00 | 420014.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.103771E+10 | 0.00 | 0.00 | 0.259042E+09 | 0.886866E+09 | 21718823.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.123414E+09 | 0.00 | 0.00 | 0.537134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 74763372.34 | 0.00 | 0.00 | 0.293468E+09 | 327615.71 | 9433544.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 4396219.68 | 0.00 | 0.00 | 5175030.54 | 12164411.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 25338607.04 | 0.00 | 0.00 | 0.00 | 92523116.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 93723261.92 | 0.00 | 0.00 | 0.00 | 0.346335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.199680E+09 | 0.00 | 0.00 | 0.00 | 0.754397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.247182E+09 | 0.00 | 0.00 | 0.00 | 0.943282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.266103E+09 | 0.00 | 0.00 | 0.00 | 0.101154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.162564E+09 | 0.00 | 0.00 | 0.00 | 0.602265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 58809100.39 | 0.00 | 0.00 | 0.00 | 0.213764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 8088552.30 | 0.00 | 0.00 | 240741.29 | 28969040.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 21877288.66 | 0.00 | 0.00 | 0.108477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128594E+10 | 0.00 | 0.00 | 0.944494E+09 | 0.400557E+10 | 9433544.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4396219.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.266103E+09 | 0.00 | 0.00 | 0.537134E+09 | 0.101154E+10 | 9433544.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 62586695.43 | 0.00 | 0.00 | 0.307108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 40031764.71 | 0.00 | 0.00 | 0.168808E+09 | 453824.08 | 4826568.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5067598.78 | 0.00 | 0.00 | 0.00 | 18675901.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 30918403.29 | 0.00 | 0.00 | 0.00 | 0.113927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 90885908.62 | 0.00 | 0.00 | 0.00 | 0.339307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.172706E+09 | 0.00 | 0.00 | 0.00 | 0.660473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.210346E+09 | 0.00 | 0.00 | 0.00 | 0.813178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.226101E+09 | 0.00 | 0.00 | 0.00 | 0.870816E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.144600E+09 | 0.00 | 0.00 | 0.00 | 0.542260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 63611579.91 | 0.00 | 0.00 | 0.00 | 0.233639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 15748397.75 | 0.00 | 0.00 | 0.00 | 57011335.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1275871.02 | 0.00 | 0.00 | 12529241.14 | 264463.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.106388E+10 | 0.00 | 0.00 | 0.488445E+09 | 0.365001E+10 | 4826568.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1275871.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.226101E+09 | 0.00 | 0.00 | 0.307108E+09 | 0.870816E+09 | 4826568.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 62604164.11 | 0.00 | 0.00 | 0.307264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 40003398.61 | 0.00 | 0.00 | 0.168703E+09 | 479545.81 | 4836746.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5047428.03 | 0.00 | 0.00 | 0.00 | 18607320.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 30965865.36 | 0.00 | 0.00 | 0.00 | 0.114132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 91140148.73 | 0.00 | 0.00 | 0.00 | 0.340326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.172961E+09 | 0.00 | 0.00 | 0.00 | 0.661574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.210555E+09 | 0.00 | 0.00 | 0.00 | 0.814144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.226116E+09 | 0.00 | 0.00 | 0.00 | 0.871064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.144731E+09 | 0.00 | 0.00 | 0.00 | 0.542865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 63619652.98 | 0.00 | 0.00 | 0.00 | 0.233722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 15684354.04 | 0.00 | 0.00 | 0.00 | 56790248.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1282601.96 | 0.00 | 0.00 | 12549606.03 | 268419.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.106471E+10 | 0.00 | 0.00 | 0.488516E+09 | 0.365397E+10 | 4836746.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1282601.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.226116E+09 | 0.00 | 0.00 | 0.307264E+09 | 0.871064E+09 | 4836746.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 19160851.63 | 0.00 | 0.00 | 0.107732E+09 | 200434.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 20098594.94 | 0.00 | 0.00 | 50575977.82 | 28638562.53 | 3392329.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 30685208.52 | 0.00 | 0.00 | 0.00 | 0.111570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 52293190.33 | 0.00 | 0.00 | 59310.14 | 0.192998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.101427E+09 | 0.00 | 0.00 | 0.00 | 0.380375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.173793E+09 | 0.00 | 0.00 | 0.00 | 0.668388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.213709E+09 | 0.00 | 0.00 | 0.00 | 0.830879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.242858E+09 | 0.00 | 0.00 | 0.00 | 0.939836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.174228E+09 | 0.00 | 0.00 | 0.00 | 0.655854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.110155E+09 | 0.00 | 0.00 | 119172.70 | 0.405081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 63826435.31 | 0.00 | 0.00 | 3862136.79 | 0.230662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 17509396.90 | 0.00 | 0.00 | 1603148.32 | 62873105.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121974E+10 | 0.00 | 0.00 | 0.163952E+09 | 0.450736E+10 | 3392329.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 17509396.90 | 0.00 | 0.00 | 0.00 | 200434.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.242858E+09 | 0.00 | 0.00 | 0.107732E+09 | 0.939836E+09 | 3392329.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 27076005.10 | 0.00 | 0.00 | 0.145925E+09 | 6086.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 23987420.11 | 0.00 | 0.00 | 68620561.23 | 27736708.83 | 4238135.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 30454845.36 | 0.00 | 0.00 | 0.00 | 0.110555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 54342615.55 | 0.00 | 0.00 | 59295.25 | 0.200166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.107226E+09 | 0.00 | 0.00 | 0.00 | 0.401174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.186244E+09 | 0.00 | 0.00 | 0.00 | 0.714072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.230419E+09 | 0.00 | 0.00 | 0.00 | 0.892782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.260256E+09 | 0.00 | 0.00 | 0.00 | 0.100390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.185366E+09 | 0.00 | 0.00 | 0.00 | 0.695943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.113973E+09 | 0.00 | 0.00 | 119201.39 | 0.418276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 62613455.72 | 0.00 | 0.00 | 3381971.12 | 0.225874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 15702144.21 | 0.00 | 0.00 | 1308026.78 | 56301803.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.129766E+10 | 0.00 | 0.00 | 0.219414E+09 | 0.474679E+10 | 4238135.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 15702144.21 | 0.00 | 0.00 | 0.00 | 6086.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.260256E+09 | 0.00 | 0.00 | 0.145925E+09 | 0.100390E+10 | 4238135.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 86180718.68 | 0.00 | 0.00 | 0.359449E+09 | 4392715.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 88601136.96 | 0.00 | 0.00 | 0.159702E+09 | 0.134940E+09 | 13717786.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.138073E+09 | 0.00 | 0.00 | 0.00 | 0.475659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.219435E+09 | 0.00 | 0.00 | 236051.89 | 0.765874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.341576E+09 | 0.00 | 0.00 | 0.00 | 0.121204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.496692E+09 | 0.00 | 0.00 | 0.00 | 0.181106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.575999E+09 | 0.00 | 0.00 | 0.00 | 0.212482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.626502E+09 | 0.00 | 0.00 | 0.00 | 0.230193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.408931E+09 | 0.00 | 0.00 | 0.00 | 0.146266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.213322E+09 | 0.00 | 0.00 | 0.00 | 0.746108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 91141157.91 | 0.00 | 0.00 | 29867.12 | 0.312982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 25265852.55 | 0.00 | 0.00 | 16070239.01 | 76117710.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.331172E+10 | 0.00 | 0.00 | 0.535486E+09 | 0.114286E+11 | 13717786.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25265852.55 | 0.00 | 0.00 | 0.00 | 4392715.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.626502E+09 | 0.00 | 0.00 | 0.359449E+09 | 0.230193E+10 | 13717786.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.197281E+09 | 0.00 | 0.00 | 0.798179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.120297E+09 | 0.00 | 0.00 | 0.405359E+09 | 19461677.45 | 16454789.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 63046366.74 | 0.00 | 0.00 | 0.00 | 0.218928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.167387E+09 | 0.00 | 0.00 | 59691.58 | 0.585094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.318798E+09 | 0.00 | 0.00 | 0.00 | 0.113106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.492881E+09 | 0.00 | 0.00 | 0.00 | 0.179573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.566823E+09 | 0.00 | 0.00 | 0.00 | 0.208923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.588014E+09 | 0.00 | 0.00 | 0.00 | 0.216034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.341988E+09 | 0.00 | 0.00 | 0.00 | 0.122446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.116546E+09 | 0.00 | 0.00 | 0.00 | 0.409956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 21829682.93 | 0.00 | 0.00 | 22105033.60 | 60250518.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 53099693.31 | 0.00 | 0.00 | 0.221152E+09 | 1421826.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.304799E+10 | 0.00 | 0.00 | 0.144686E+10 | 0.969593E+10 | 16454789.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21829682.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.588014E+09 | 0.00 | 0.00 | 0.798179E+09 | 0.216034E+10 | 16454789.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 85712351.13 | 0.00 | 0.00 | 0.361545E+09 | 5492020.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 89371195.63 | 0.00 | 0.00 | 0.156133E+09 | 0.146598E+09 | 14232602.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.132097E+09 | 0.00 | 0.00 | 0.00 | 0.461525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.213327E+09 | 0.00 | 0.00 | 98499.78 | 0.755741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.337159E+09 | 0.00 | 0.00 | 0.00 | 0.121419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.492678E+09 | 0.00 | 0.00 | 0.00 | 0.182266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.571346E+09 | 0.00 | 0.00 | 0.00 | 0.213757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.614746E+09 | 0.00 | 0.00 | 0.00 | 0.229171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.401387E+09 | 0.00 | 0.00 | 0.00 | 0.145707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.209773E+09 | 0.00 | 0.00 | 0.00 | 0.744408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 89189771.01 | 0.00 | 0.00 | 148618.07 | 0.310711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 25131384.41 | 0.00 | 0.00 | 16130655.25 | 76569788.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.326192E+10 | 0.00 | 0.00 | 0.534056E+09 | 0.114242E+11 | 14232602.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25131384.41 | 0.00 | 0.00 | 0.00 | 5492020.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.614746E+09 | 0.00 | 0.00 | 0.361545E+09 | 0.229171E+10 | 14232602.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.193194E+09 | 0.00 | 0.00 | 0.793971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.116822E+09 | 0.00 | 0.00 | 0.397317E+09 | 22284097.99 | 17011661.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 57298685.54 | 0.00 | 0.00 | 0.00 | 0.201763E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.161806E+09 | 0.00 | 0.00 | 0.00 | 0.573879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.315326E+09 | 0.00 | 0.00 | 0.00 | 0.113473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.489788E+09 | 0.00 | 0.00 | 0.00 | 0.180927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.563236E+09 | 0.00 | 0.00 | 0.00 | 0.210403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.577677E+09 | 0.00 | 0.00 | 0.00 | 0.215202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.335927E+09 | 0.00 | 0.00 | 0.00 | 0.122013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.114252E+09 | 0.00 | 0.00 | 0.00 | 0.407477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 19170106.38 | 0.00 | 0.00 | 18194682.44 | 55329301.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 49253915.60 | 0.00 | 0.00 | 0.208338E+09 | 1565270.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.299375E+10 | 0.00 | 0.00 | 0.141782E+10 | 0.968248E+10 | 17011661.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19170106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.577677E+09 | 0.00 | 0.00 | 0.793971E+09 | 0.215202E+10 | 17011661.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 76483022.99 | 0.00 | 0.00 | 0.345786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 57687645.79 | 0.00 | 0.00 | 0.169827E+09 | 39176022.28 | 6840893.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 74172722.72 | 0.00 | 0.00 | 0.00 | 0.263680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.154398E+09 | 0.00 | 0.00 | 382866.19 | 0.554094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.271137E+09 | 0.00 | 0.00 | 0.00 | 0.988122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.400891E+09 | 0.00 | 0.00 | 0.00 | 0.150088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.459536E+09 | 0.00 | 0.00 | 0.00 | 0.174078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.474993E+09 | 0.00 | 0.00 | 0.00 | 0.179414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.294120E+09 | 0.00 | 0.00 | 0.00 | 0.108172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.126221E+09 | 0.00 | 0.00 | 0.00 | 0.454811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 34602767.34 | 0.00 | 0.00 | 0.00 | 0.122860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 6155160.44 | 0.00 | 0.00 | 19397775.75 | 9743272.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.243040E+10 | 0.00 | 0.00 | 0.535393E+09 | 0.855001E+10 | 6840893.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6155160.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.474993E+09 | 0.00 | 0.00 | 0.345786E+09 | 0.179414E+10 | 6840893.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 76581980.54 | 0.00 | 0.00 | 0.346474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 57942051.74 | 0.00 | 0.00 | 0.169810E+09 | 40180489.48 | 6871477.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 73901792.92 | 0.00 | 0.00 | 0.00 | 0.262818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.154625E+09 | 0.00 | 0.00 | 323195.63 | 0.555114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.271768E+09 | 0.00 | 0.00 | 0.00 | 0.990758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.401404E+09 | 0.00 | 0.00 | 0.00 | 0.150328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.459754E+09 | 0.00 | 0.00 | 0.00 | 0.174220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.474989E+09 | 0.00 | 0.00 | 0.00 | 0.179475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.294475E+09 | 0.00 | 0.00 | 0.00 | 0.108340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.126105E+09 | 0.00 | 0.00 | 0.00 | 0.454565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 34465887.84 | 0.00 | 0.00 | 0.00 | 0.122410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 6207214.25 | 0.00 | 0.00 | 19528000.80 | 9779925.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.243222E+10 | 0.00 | 0.00 | 0.536134E+09 | 0.855925E+10 | 6871477.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6207214.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.474989E+09 | 0.00 | 0.00 | 0.346474E+09 | 0.179475E+10 | 6871477.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 27887060.23 | 0.00 | 0.00 | 85148473.74 | 37110298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 63151001.94 | 0.00 | 0.00 | 18499931.53 | 0.187485E+09 | 3241930.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.159561E+09 | 0.00 | 0.00 | 965169.71 | 0.564582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.206116E+09 | 0.00 | 0.00 | 928001.89 | 0.739668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.292731E+09 | 0.00 | 0.00 | 0.00 | 0.106844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.404119E+09 | 0.00 | 0.00 | 0.00 | 0.151625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.468260E+09 | 0.00 | 0.00 | 0.00 | 0.177774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.512320E+09 | 0.00 | 0.00 | 0.00 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.359026E+09 | 0.00 | 0.00 | 0.00 | 0.132100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.228057E+09 | 0.00 | 0.00 | 0.00 | 0.819340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.138267E+09 | 0.00 | 0.00 | 2805355.45 | 0.487944E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 57288972.23 | 0.00 | 0.00 | 2455392.44 | 0.200649E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.291679E+10 | 0.00 | 0.00 | 0.110802E+09 | 0.106581E+11 | 3241930.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27887060.23 | 0.00 | 0.00 | 0.00 | 37110298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.512320E+09 | 0.00 | 0.00 | 85148473.74 | 0.193790E+10 | 3241930.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 28095661.77 | 0.00 | 0.00 | 85283520.35 | 37797742.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 63389537.29 | 0.00 | 0.00 | 18667510.61 | 0.188296E+09 | 3264793.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.158982E+09 | 0.00 | 0.00 | 966340.15 | 0.562654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.206363E+09 | 0.00 | 0.00 | 928396.65 | 0.740717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.293317E+09 | 0.00 | 0.00 | 0.00 | 0.107081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.404732E+09 | 0.00 | 0.00 | 0.00 | 0.151884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.468523E+09 | 0.00 | 0.00 | 0.00 | 0.177912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.512390E+09 | 0.00 | 0.00 | 0.00 | 0.193858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.359313E+09 | 0.00 | 0.00 | 0.00 | 0.132233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.228185E+09 | 0.00 | 0.00 | 0.00 | 0.819968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.138214E+09 | 0.00 | 0.00 | 2790575.31 | 0.487844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 57707312.39 | 0.00 | 0.00 | 2510971.70 | 0.202143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.291921E+10 | 0.00 | 0.00 | 0.111147E+09 | 0.106691E+11 | 3264793.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28095661.77 | 0.00 | 0.00 | 0.00 | 37797742.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.512390E+09 | 0.00 | 0.00 | 85283520.35 | 0.193858E+10 | 3264793.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.175123E+09 | 0.00 | 0.00 | 0.688980E+09 | 7500350.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.111118E+09 | 0.00 | 0.00 | 0.361967E+09 | 35017212.37 | 17558559.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 47976684.09 | 0.00 | 0.00 | 41768668.27 | 0.129595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 92581099.31 | 0.00 | 0.00 | 16470247.11 | 0.308360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.165237E+09 | 0.00 | 0.00 | 0.00 | 0.581795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.268254E+09 | 0.00 | 0.00 | 0.00 | 0.970476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.316732E+09 | 0.00 | 0.00 | 0.00 | 0.115851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.344984E+09 | 0.00 | 0.00 | 0.00 | 0.125597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.198914E+09 | 0.00 | 0.00 | 0.00 | 0.705822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 80563361.31 | 0.00 | 0.00 | 19610855.14 | 0.263860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 43404656.84 | 0.00 | 0.00 | 0.115003E+09 | 55507273.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 90946084.35 | 0.00 | 0.00 | 0.341820E+09 | 18106497.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.193583E+10 | 0.00 | 0.00 | 0.158562E+10 | 0.549052E+10 | 17558559.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 43404656.84 | 0.00 | 0.00 | 0.00 | 7500350.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.344984E+09 | 0.00 | 0.00 | 0.688980E+09 | 0.125597E+10 | 17558559.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.235425E+09 | 0.00 | 0.00 | 0.923013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.138982E+09 | 0.00 | 0.00 | 0.495555E+09 | 3888097.38 | 18257916.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 34656216.19 | 0.00 | 0.00 | 69943494.13 | 59548777.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 71041784.19 | 0.00 | 0.00 | 22530427.10 | 0.228907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.153241E+09 | 0.00 | 0.00 | 0.00 | 0.539275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.266013E+09 | 0.00 | 0.00 | 0.00 | 0.961060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.312228E+09 | 0.00 | 0.00 | 0.00 | 0.114038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.324742E+09 | 0.00 | 0.00 | 0.00 | 0.118144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.163989E+09 | 0.00 | 0.00 | 0.00 | 0.582408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 46185366.16 | 0.00 | 0.00 | 28605236.45 | 0.137300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 49990047.41 | 0.00 | 0.00 | 0.196469E+09 | 6496125.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.129446E+09 | 0.00 | 0.00 | 0.506524E+09 | 54818.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.192594E+10 | 0.00 | 0.00 | 0.224264E+10 | 0.484076E+10 | 18257916.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34656216.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.324742E+09 | 0.00 | 0.00 | 0.923013E+09 | 0.118144E+10 | 18257916.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.169753E+09 | 0.00 | 0.00 | 0.680501E+09 | 5155708.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.107579E+09 | 0.00 | 0.00 | 0.354671E+09 | 36031620.54 | 17813150.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 43729295.90 | 0.00 | 0.00 | 40757655.89 | 0.118196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 87537245.94 | 0.00 | 0.00 | 15145571.52 | 0.297196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.161354E+09 | 0.00 | 0.00 | 0.00 | 0.577204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.264928E+09 | 0.00 | 0.00 | 0.00 | 0.973219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.313109E+09 | 0.00 | 0.00 | 0.00 | 0.116225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.337481E+09 | 0.00 | 0.00 | 0.00 | 0.124743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.194356E+09 | 0.00 | 0.00 | 0.00 | 0.700575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 77399758.60 | 0.00 | 0.00 | 19397339.97 | 0.257274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 40100337.63 | 0.00 | 0.00 | 0.110101E+09 | 50547598.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 86593258.30 | 0.00 | 0.00 | 0.332978E+09 | 15493408.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.188392E+10 | 0.00 | 0.00 | 0.155355E+10 | 0.544058E+10 | 17813150.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40100337.63 | 0.00 | 0.00 | 0.00 | 5155708.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.337481E+09 | 0.00 | 0.00 | 0.680501E+09 | 0.124743E+10 | 17813150.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.229804E+09 | 0.00 | 0.00 | 0.914224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.133640E+09 | 0.00 | 0.00 | 0.484744E+09 | 3462462.69 | 18538593.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 30375561.20 | 0.00 | 0.00 | 65708754.73 | 50093621.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 66275726.94 | 0.00 | 0.00 | 20887290.99 | 0.217682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.149678E+09 | 0.00 | 0.00 | 0.00 | 0.535065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.262994E+09 | 0.00 | 0.00 | 0.00 | 0.964489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.308821E+09 | 0.00 | 0.00 | 0.00 | 0.114436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.317722E+09 | 0.00 | 0.00 | 0.00 | 0.117337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.159876E+09 | 0.00 | 0.00 | 0.00 | 0.576842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 43642850.65 | 0.00 | 0.00 | 27980411.96 | 0.131290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 46668563.22 | 0.00 | 0.00 | 0.187646E+09 | 5008400.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.124459E+09 | 0.00 | 0.00 | 0.494410E+09 | 34020.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.187396E+10 | 0.00 | 0.00 | 0.219560E+10 | 0.480170E+10 | 18538593.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30375561.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.317722E+09 | 0.00 | 0.00 | 0.914224E+09 | 0.117337E+10 | 18538593.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.156068E+09 | 0.00 | 0.00 | 0.642571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 90970778.82 | 0.00 | 0.00 | 0.335710E+09 | 2959881.22 | 12262130.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 21720016.01 | 0.00 | 0.00 | 31030403.27 | 51138773.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 58431406.14 | 0.00 | 0.00 | 9782778.97 | 0.199631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.129425E+09 | 0.00 | 0.00 | 0.00 | 0.463394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.219954E+09 | 0.00 | 0.00 | 0.00 | 0.808351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.258264E+09 | 0.00 | 0.00 | 0.00 | 0.959578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.267719E+09 | 0.00 | 0.00 | 0.00 | 0.991116E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.140072E+09 | 0.00 | 0.00 | 0.00 | 0.506056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 37138986.00 | 0.00 | 0.00 | 10588136.87 | 0.123787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 27284303.48 | 0.00 | 0.00 | 0.107753E+09 | 9069345.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 78709019.10 | 0.00 | 0.00 | 0.322359E+09 | 453304.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.148576E+10 | 0.00 | 0.00 | 0.145979E+10 | 0.411553E+10 | 12262130.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21720016.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.267719E+09 | 0.00 | 0.00 | 0.642571E+09 | 0.991116E+09 | 12262130.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.156042E+09 | 0.00 | 0.00 | 0.642745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 90929744.55 | 0.00 | 0.00 | 0.335618E+09 | 3037247.51 | 12279805.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 21664289.32 | 0.00 | 0.00 | 31342314.31 | 50723910.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 58534056.57 | 0.00 | 0.00 | 9793329.30 | 0.200111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.129814E+09 | 0.00 | 0.00 | 0.00 | 0.465038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.220258E+09 | 0.00 | 0.00 | 0.00 | 0.809884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.258408E+09 | 0.00 | 0.00 | 0.00 | 0.960609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.267679E+09 | 0.00 | 0.00 | 0.00 | 0.991508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.140264E+09 | 0.00 | 0.00 | 0.00 | 0.507034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 37226730.93 | 0.00 | 0.00 | 10689783.04 | 0.124079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 27279278.18 | 0.00 | 0.00 | 0.107964E+09 | 8903873.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 78704195.34 | 0.00 | 0.00 | 0.322468E+09 | 452102.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.148680E+10 | 0.00 | 0.00 | 0.146062E+10 | 0.412138E+10 | 12279805.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21664289.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.267679E+09 | 0.00 | 0.00 | 0.642745E+09 | 0.991508E+09 | 12279805.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.100718E+09 | 0.00 | 0.00 | 0.417636E+09 | 8799323.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 68196796.19 | 0.00 | 0.00 | 0.212295E+09 | 38715680.17 | 11523602.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 38870938.72 | 0.00 | 0.00 | 13361688.05 | 0.125414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 80103711.51 | 0.00 | 0.00 | 5274573.62 | 0.279329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.141351E+09 | 0.00 | 0.00 | 0.00 | 0.506603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.222156E+09 | 0.00 | 0.00 | 0.00 | 0.818017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.262938E+09 | 0.00 | 0.00 | 0.00 | 0.978894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.288022E+09 | 0.00 | 0.00 | 0.00 | 0.106757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.175165E+09 | 0.00 | 0.00 | 0.00 | 0.632566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 74066248.28 | 0.00 | 0.00 | 5712513.77 | 0.257831E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 30190949.64 | 0.00 | 0.00 | 49093671.39 | 68867483.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 48069680.62 | 0.00 | 0.00 | 0.176628E+09 | 24625111.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.152985E+10 | 0.00 | 0.00 | 0.880002E+09 | 0.480723E+10 | 11523602.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30190949.64 | 0.00 | 0.00 | 0.00 | 8799323.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.288022E+09 | 0.00 | 0.00 | 0.417636E+09 | 0.106757E+10 | 11523602.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.100898E+09 | 0.00 | 0.00 | 0.418322E+09 | 9020844.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 68383696.16 | 0.00 | 0.00 | 0.212495E+09 | 39239918.13 | 11543121.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 38911783.24 | 0.00 | 0.00 | 13485479.88 | 0.125517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 80238910.37 | 0.00 | 0.00 | 5314073.57 | 0.279976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.141593E+09 | 0.00 | 0.00 | 0.00 | 0.507791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.222339E+09 | 0.00 | 0.00 | 0.00 | 0.819190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.262886E+09 | 0.00 | 0.00 | 0.00 | 0.979314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.287804E+09 | 0.00 | 0.00 | 0.00 | 0.106743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.175168E+09 | 0.00 | 0.00 | 0.00 | 0.632970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 74202238.93 | 0.00 | 0.00 | 5764810.38 | 0.258415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 30168006.40 | 0.00 | 0.00 | 49038904.53 | 68887905.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 48205491.93 | 0.00 | 0.00 | 0.176820E+09 | 25017091.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.153080E+10 | 0.00 | 0.00 | 0.881241E+09 | 0.481277E+10 | 11543121.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30168006.40 | 0.00 | 0.00 | 0.00 | 9020844.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.287804E+09 | 0.00 | 0.00 | 0.418322E+09 | 0.106743E+10 | 11543121.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.203344E+09 | 0.00 | 0.00 | 0.00 | 38737.43 | 0.267185E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.173584E+09 | 570220.09 | 0.00 | 160699.58 | 1186247.51 | 0.164002E+09 | 11394783.18 | 0.00 | 0.35 |
| March | 0.221304E+09 | 6371606.53 | 0.00 | 596440.92 | 2664379.49 | 0.00 | 57571046.11 | 0.00 | 0.35 |
| April | 0.121465E+09 | 15008257.39 | 0.00 | 806524.10 | 4934731.06 | 0.00 | 68444710.36 | 0.00 | 0.35 |
| May | 27101762.00 | 94714280.90 | 0.00 | 789363.29 | 16644966.63 | 0.00 | 42465867.59 | 0.00 | 0.36 |
| June | 6470331.33 | 0.368630E+09 | 0.00 | 433190.49 | 28394044.97 | 0.00 | 19542311.58 | 0.00 | 0.36 |
| July | 3300032.18 | 0.564616E+09 | 0.00 | 73631.30 | 41427301.68 | 0.00 | 344248.10 | 0.00 | 0.36 |
| August | 493827.60 | 0.701106E+09 | 0.00 | 2615.04 | 44449187.59 | 0.00 | 28674.74 | 0.00 | 0.36 |
| September | 16295429.79 | 0.283980E+09 | 0.00 | 699160.83 | 36418576.63 | 0.00 | 15689289.91 | 0.00 | 0.36 |
| October | 65639869.42 | 57097292.11 | 0.00 | 2941999.49 | 12316343.35 | 0.00 | 0.150061E+09 | 0.00 | 0.36 |
| November | 0.144823E+09 | 1197973.64 | 0.00 | 2116032.90 | 1528236.94 | 0.00 | 0.182684E+09 | 0.00 | 0.35 |
| December | 0.369643E+09 | 10149.55 | 0.00 | 276159.73 | 294596.72 | 5514184.55 | 43602246.91 | 0.00 | 0.35 |
| Annual Sum or Average | 0.135347E+10 | 0.209330E+10 | 0.00 | 8895817.66 | 0.190297E+09 | 0.436701E+09 | 0.591829E+09 | 0.00 | 0.35 |
| Minimum of Months | 493827.60 | 0.00 | 0.00 | 0.00 | 38737.43 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.369643E+09 | 0.701106E+09 | 0.00 | 2941999.49 | 44449187.59 | 0.267185E+09 | 0.182684E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 44004968.25 | 0.00 | 24057.20 | 0.00 | 99643.32 | 0.414777E+09 | 0.00 | 498.37 | 0.35 |
| February | 97045082.04 | 138443.09 | 0.00 | 873.58 | 2586601.67 | 0.234817E+09 | 211.54 | 0.00 | 0.35 |
| March | 0.241354E+09 | 4149931.90 | 0.00 | 25241.95 | 4137047.55 | 6004292.64 | 4746640.80 | 0.00 | 0.35 |
| April | 0.146331E+09 | 12072349.62 | 0.00 | 392440.99 | 6074528.77 | 0.00 | 39833577.19 | 0.00 | 0.35 |
| May | 33116464.13 | 89483790.70 | 0.00 | 684475.93 | 15838477.54 | 0.00 | 40304483.15 | 0.00 | 0.36 |
| June | 6612794.79 | 0.370718E+09 | 0.00 | 425549.98 | 27414586.31 | 0.00 | 19290795.17 | 0.00 | 0.36 |
| July | 3714522.61 | 0.566493E+09 | 0.00 | 75507.35 | 39942104.62 | 0.00 | 404682.84 | 0.00 | 0.36 |
| August | 600345.24 | 0.686938E+09 | 0.00 | 4980.68 | 43371978.76 | 0.00 | 34377.55 | 0.00 | 0.36 |
| September | 17515827.47 | 0.265833E+09 | 0.00 | 621013.24 | 36445653.66 | 0.00 | 17044606.10 | 0.00 | 0.36 |
| October | 96655581.29 | 47520552.75 | 0.00 | 1181865.67 | 12369543.11 | 0.00 | 0.129326E+09 | 0.00 | 0.36 |
| November | 0.262149E+09 | 256552.02 | 0.00 | 363692.04 | 1866213.07 | 0.00 | 51670707.44 | 0.00 | 0.35 |
| December | 0.225663E+09 | 0.00 | 0.00 | 0.00 | 802723.42 | 0.151844E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.117476E+10 | 0.204360E+10 | 24057.20 | 3775641.42 | 0.190949E+09 | 0.807442E+09 | 0.302657E+09 | 498.37 | 0.35 |
| Minimum of Months | 600345.24 | 0.00 | 0.00 | 0.00 | 99643.32 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.262149E+09 | 0.686938E+09 | 24057.20 | 1181865.67 | 43371978.76 | 0.414777E+09 | 0.129326E+09 | 498.37 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.153780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283939E+09 | 0.00 | 0.00 | 0.48 |
| February | 0.118965E+10 | 54772.50 | 0.00 | 313889.36 | 111829.56 | 0.161653E+09 | 39876473.79 | 0.00 | 0.48 |
| March | 0.101759E+10 | 4562127.91 | 0.00 | 804367.22 | 3467824.54 | 2085220.84 | 0.144326E+09 | 0.00 | 0.49 |
| April | 0.731976E+09 | 17538626.50 | 0.00 | 770154.67 | 3118187.66 | 0.00 | 0.121398E+09 | 0.00 | 0.50 |
| May | 0.491946E+09 | 0.115763E+09 | 0.00 | 1269477.99 | 20106143.16 | 0.00 | 65736868.11 | 0.00 | 0.50 |
| June | 0.300166E+09 | 0.405326E+09 | 0.00 | 1570679.94 | 93250058.50 | 0.00 | 19855164.84 | 0.00 | 0.51 |
| July | 0.240579E+09 | 0.501225E+09 | 0.00 | 1281467.87 | 0.142890E+09 | 0.00 | 715648.73 | 0.00 | 0.52 |
| August | 0.184871E+09 | 0.650564E+09 | 0.00 | 1265003.21 | 0.155849E+09 | 0.00 | 1449543.83 | 0.00 | 0.52 |
| September | 0.432014E+09 | 0.246847E+09 | 0.00 | 1887553.24 | 38462209.30 | 0.00 | 30392393.90 | 0.00 | 0.52 |
| October | 0.894361E+09 | 77049470.43 | 0.00 | 2433427.84 | 11223952.13 | 0.00 | 0.185851E+09 | 0.00 | 0.50 |
| November | 0.117889E+10 | 3093366.50 | 0.00 | 1288312.89 | 1048920.98 | 128517.22 | 0.204699E+09 | 0.00 | 0.50 |
| December | 0.154932E+10 | 229940.30 | 0.00 | 202125.97 | 0.00 | 41622416.35 | 70165766.93 | 0.00 | 0.49 |
| Annual Sum or Average | 0.974915E+10 | 0.202225E+10 | 0.00 | 13086460.20 | 0.469528E+09 | 0.489429E+09 | 0.884466E+09 | 0.00 | 0.50 |
| Minimum of Months | 0.184871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
| Maximum of Months | 0.154932E+10 | 0.650564E+09 | 0.00 | 2433427.84 | 0.155849E+09 | 0.283939E+09 | 0.204699E+09 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 39970253.96 | 0.00 | 4373.63 | 0.00 | 100991.95 | 0.418646E+09 | 0.00 | 282.13 | 0.35 |
| February | 95724127.86 | 129058.14 | 0.00 | 785.20 | 2449026.01 | 0.236871E+09 | 262.45 | 0.00 | 0.35 |
| March | 0.241302E+09 | 3860399.57 | 0.00 | 18337.21 | 3879248.22 | 5999015.85 | 4628653.15 | 0.00 | 0.35 |
| April | 0.148618E+09 | 11885547.53 | 0.00 | 378025.44 | 5780704.87 | 0.00 | 37961747.81 | 0.00 | 0.35 |
| May | 33434316.40 | 92272677.96 | 0.00 | 712218.56 | 14479531.60 | 0.00 | 41639716.26 | 0.00 | 0.36 |
| June | 7302013.99 | 0.375466E+09 | 0.00 | 468956.96 | 25010825.18 | 0.00 | 19520866.10 | 0.00 | 0.36 |
| July | 3674845.22 | 0.572679E+09 | 0.00 | 74242.06 | 39216445.67 | 0.00 | 408105.83 | 0.00 | 0.36 |
| August | 648275.73 | 0.688364E+09 | 0.00 | 5619.55 | 42461779.45 | 0.00 | 27037.61 | 0.00 | 0.36 |
| September | 18426733.98 | 0.266694E+09 | 0.00 | 647590.62 | 36198180.37 | 0.00 | 17183049.61 | 0.00 | 0.36 |
| October | 97028882.53 | 48104862.03 | 0.00 | 1157622.97 | 11649348.00 | 0.00 | 0.128952E+09 | 0.00 | 0.36 |
| November | 0.261118E+09 | 218539.44 | 0.00 | 343106.23 | 1841034.66 | 0.00 | 53692280.16 | 0.00 | 0.35 |
| December | 0.240249E+09 | 0.00 | 0.00 | 0.00 | 783383.73 | 0.136991E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.118750E+10 | 0.205967E+10 | 4373.63 | 3806504.80 | 0.183850E+09 | 0.798507E+09 | 0.304014E+09 | 282.13 | 0.35 |
| Minimum of Months | 648275.73 | 0.00 | 0.00 | 0.00 | 100991.95 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.261118E+09 | 0.688364E+09 | 4373.63 | 1157622.97 | 42461779.45 | 0.418646E+09 | 0.128952E+09 | 282.13 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.142936E+09 | 0.00 | 0.00 | 0.00 | 80920.95 | 0.325403E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.149328E+09 | 127137.26 | 0.00 | 3289.00 | 2163621.86 | 0.196581E+09 | 287943.98 | 0.00 | 0.35 |
| March | 0.250810E+09 | 3956326.57 | 0.00 | 99228.98 | 3491594.18 | 0.00 | 26524965.58 | 0.00 | 0.35 |
| April | 0.102576E+09 | 12783247.75 | 0.00 | 680049.76 | 5552716.25 | 0.00 | 86433900.66 | 0.00 | 0.35 |
| May | 25294375.79 | 89272637.94 | 0.00 | 811090.77 | 15703579.80 | 0.00 | 42876700.23 | 0.00 | 0.36 |
| June | 6854090.40 | 0.362027E+09 | 0.00 | 433382.54 | 27632821.90 | 0.00 | 19451886.98 | 0.00 | 0.36 |
| July | 3587874.64 | 0.550579E+09 | 0.00 | 87097.04 | 40653480.34 | 0.00 | 509168.89 | 0.00 | 0.36 |
| August | 594064.25 | 0.664059E+09 | 0.00 | 5168.65 | 44128094.94 | 0.00 | 29417.22 | 0.00 | 0.36 |
| September | 17700268.79 | 0.257371E+09 | 0.00 | 677166.83 | 36053665.75 | 0.00 | 16926948.72 | 0.00 | 0.36 |
| October | 58704315.52 | 47077262.75 | 0.00 | 1516338.68 | 12302653.36 | 0.00 | 0.164496E+09 | 0.00 | 0.36 |
| November | 0.199251E+09 | 545222.11 | 0.00 | 721904.81 | 1421376.94 | 0.00 | 0.130384E+09 | 0.00 | 0.35 |
| December | 0.400262E+09 | 0.00 | 0.00 | 8254.30 | 677842.22 | 0.00 | 3291905.80 | 0.00 | 0.35 |
| Annual Sum or Average | 0.135790E+10 | 0.198780E+10 | 0.00 | 5042971.36 | 0.189862E+09 | 0.521984E+09 | 0.491213E+09 | 0.00 | 0.35 |
| Minimum of Months | 594064.25 | 0.00 | 0.00 | 0.00 | 80920.95 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.400262E+09 | 0.664059E+09 | 0.00 | 1516338.68 | 44128094.94 | 0.325403E+09 | 0.164496E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.142549E+09 | 0.00 | 0.00 | 0.00 | 80182.71 | 0.325798E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.149540E+09 | 127080.07 | 0.00 | 3452.15 | 2142532.46 | 0.196477E+09 | 287889.28 | 0.00 | 0.35 |
| March | 0.250586E+09 | 3959964.72 | 0.00 | 99030.80 | 3487823.93 | 0.00 | 26747819.79 | 0.00 | 0.35 |
| April | 0.102734E+09 | 12780535.09 | 0.00 | 678941.74 | 5530806.11 | 0.00 | 86301534.05 | 0.00 | 0.35 |
| May | 25307386.68 | 89474037.15 | 0.00 | 812805.35 | 15722464.55 | 0.00 | 42866445.31 | 0.00 | 0.36 |
| June | 6863320.59 | 0.362266E+09 | 0.00 | 436325.40 | 27648368.71 | 0.00 | 19474337.37 | 0.00 | 0.36 |
| July | 3587588.17 | 0.551078E+09 | 0.00 | 86984.79 | 40559236.22 | 0.00 | 509122.28 | 0.00 | 0.36 |
| August | 591024.23 | 0.664330E+09 | 0.00 | 4840.12 | 44028950.02 | 0.00 | 28390.21 | 0.00 | 0.36 |
| September | 17698468.52 | 0.257579E+09 | 0.00 | 677545.45 | 36060838.75 | 0.00 | 16925048.34 | 0.00 | 0.36 |
| October | 59152555.35 | 47130501.63 | 0.00 | 1515178.82 | 12297796.93 | 0.00 | 0.164089E+09 | 0.00 | 0.36 |
| November | 0.199275E+09 | 536638.45 | 0.00 | 718864.87 | 1423920.92 | 0.00 | 0.130498E+09 | 0.00 | 0.35 |
| December | 0.400263E+09 | 0.00 | 0.00 | 8338.99 | 676936.45 | 0.00 | 3341192.68 | 0.00 | 0.35 |
| Annual Sum or Average | 0.135815E+10 | 0.198926E+10 | 0.00 | 5042308.48 | 0.189660E+09 | 0.522275E+09 | 0.491068E+09 | 0.00 | 0.35 |
| Minimum of Months | 591024.23 | 0.00 | 0.00 | 0.00 | 80182.71 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.400263E+09 | 0.664330E+09 | 0.00 | 1515178.82 | 44028950.02 | 0.325798E+09 | 0.164089E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.398383E+09 | 0.00 | 0.00 | 3605.10 | 2666.12 | 95467416.70 | 1275841.35 | 0.00 | 0.35 |
| February | 0.288398E+09 | 617997.71 | 0.00 | 364266.26 | 980000.55 | 46100340.14 | 34606685.85 | 0.00 | 0.35 |
| March | 0.153612E+09 | 6378598.13 | 0.00 | 1149765.84 | 2414805.94 | 0.00 | 0.141246E+09 | 0.00 | 0.35 |
| April | 75690467.64 | 15998120.82 | 0.00 | 1237239.17 | 4767085.47 | 0.00 | 0.113141E+09 | 0.00 | 0.35 |
| May | 23741859.96 | 95516854.43 | 0.00 | 932898.21 | 16356344.69 | 0.00 | 41481339.58 | 0.00 | 0.36 |
| June | 6606296.77 | 0.361274E+09 | 0.00 | 442314.14 | 28489798.41 | 0.00 | 19790185.34 | 0.00 | 0.36 |
| July | 3174173.51 | 0.549888E+09 | 0.00 | 83410.65 | 42909018.53 | 0.00 | 430051.52 | 0.00 | 0.36 |
| August | 481991.66 | 0.683374E+09 | 0.00 | 2896.03 | 44752129.38 | 0.00 | 29782.22 | 0.00 | 0.36 |
| September | 16287323.29 | 0.278911E+09 | 0.00 | 758112.48 | 36392311.31 | 0.00 | 15419071.11 | 0.00 | 0.36 |
| October | 41511899.05 | 57735800.92 | 0.00 | 3402400.13 | 12560682.23 | 0.00 | 0.172796E+09 | 0.00 | 0.36 |
| November | 77404787.04 | 1428322.39 | 0.00 | 3000203.76 | 1613179.75 | 0.00 | 0.257538E+09 | 0.00 | 0.35 |
| December | 0.330892E+09 | 18618.30 | 0.00 | 779274.24 | 252109.66 | 0.00 | 0.125398E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.141618E+10 | 0.205114E+10 | 0.00 | 12156386.01 | 0.191490E+09 | 0.141568E+09 | 0.923152E+09 | 0.00 | 0.35 |
| Minimum of Months | 481991.66 | 0.00 | 0.00 | 2896.03 | 2666.12 | 0.00 | 29782.22 | 0.00 | 0.35 |
| Maximum of Months | 0.398383E+09 | 0.683374E+09 | 0.00 | 3402400.13 | 44752129.38 | 95467416.70 | 0.257538E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.366717E+09 | 0.00 | 0.00 | 305.03 | 9302.70 | 0.122427E+09 | 472911.64 | 0.00 | 0.35 |
| February | 0.268877E+09 | 616381.31 | 0.00 | 349528.88 | 997719.32 | 65204336.47 | 32862553.15 | 0.00 | 0.35 |
| March | 0.156859E+09 | 6430622.47 | 0.00 | 1125513.55 | 2437877.61 | 0.00 | 0.137481E+09 | 0.00 | 0.35 |
| April | 75646877.29 | 16218461.99 | 0.00 | 1270326.30 | 4756839.48 | 0.00 | 0.112411E+09 | 0.00 | 0.35 |
| May | 23474493.53 | 99292398.24 | 0.00 | 954778.25 | 16523496.64 | 0.00 | 40655149.73 | 0.00 | 0.36 |
| June | 6586774.90 | 0.372709E+09 | 0.00 | 474691.48 | 28945415.32 | 0.00 | 19468069.05 | 0.00 | 0.36 |
| July | 3130997.18 | 0.568333E+09 | 0.00 | 82825.81 | 43623054.43 | 0.00 | 423329.73 | 0.00 | 0.36 |
| August | 378160.01 | 0.700978E+09 | 0.00 | 2989.38 | 47284010.79 | 0.00 | 18175.56 | 0.00 | 0.36 |
| September | 16281400.42 | 0.286257E+09 | 0.00 | 782761.71 | 38822782.43 | 0.00 | 14719425.27 | 0.00 | 0.36 |
| October | 42659536.78 | 58907210.28 | 0.00 | 3455697.66 | 12832328.52 | 0.00 | 0.171085E+09 | 0.00 | 0.36 |
| November | 82341686.36 | 1406331.33 | 0.00 | 2933555.55 | 1639570.27 | 0.00 | 0.252389E+09 | 0.00 | 0.35 |
| December | 0.340163E+09 | 13878.65 | 0.00 | 696820.66 | 257953.60 | 0.00 | 0.113156E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.138312E+10 | 0.211116E+10 | 0.00 | 12129794.24 | 0.198130E+09 | 0.187631E+09 | 0.895142E+09 | 0.00 | 0.35 |
| Minimum of Months | 378160.01 | 0.00 | 0.00 | 305.03 | 9302.70 | 0.00 | 18175.56 | 0.00 | 0.35 |
| Maximum of Months | 0.366717E+09 | 0.700978E+09 | 0.00 | 3455697.66 | 47284010.79 | 0.122427E+09 | 0.252389E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.638487E+09 | 0.00 | 0.00 | 74211.09 | 4054.22 | 0.313491E+09 | 16431831.68 | 0.00 | 0.35 |
| February | 0.451994E+09 | 1148099.05 | 0.00 | 1502058.83 | 1497230.20 | 0.178383E+09 | 97264612.34 | 0.00 | 0.35 |
| March | 0.265720E+09 | 17082753.91 | 0.00 | 4273444.32 | 4210395.09 | 0.00 | 0.309805E+09 | 0.00 | 0.35 |
| April | 0.117844E+09 | 42651668.71 | 0.00 | 4314273.52 | 8818340.11 | 0.00 | 0.233518E+09 | 0.00 | 0.35 |
| May | 42994397.01 | 0.239330E+09 | 0.00 | 2399228.40 | 35487150.12 | 0.00 | 74020888.05 | 0.00 | 0.36 |
| June | 11427856.67 | 0.770779E+09 | 0.00 | 985155.05 | 54436363.58 | 0.00 | 37604950.69 | 0.00 | 0.36 |
| July | 6621016.31 | 0.114993E+10 | 0.00 | 155359.70 | 81427515.64 | 0.00 | 841538.88 | 0.00 | 0.36 |
| August | 1058842.95 | 0.139179E+10 | 0.00 | 4816.69 | 85280592.16 | 0.00 | 31454.81 | 0.00 | 0.36 |
| September | 31062783.59 | 0.558499E+09 | 0.00 | 1276639.86 | 65222943.34 | 0.00 | 32432851.70 | 0.00 | 0.36 |
| October | 0.153564E+09 | 0.111161E+09 | 0.00 | 5636179.96 | 23127218.01 | 0.00 | 0.274313E+09 | 0.00 | 0.36 |
| November | 0.339732E+09 | 2480659.45 | 0.00 | 4094622.34 | 2845872.56 | 0.00 | 0.297951E+09 | 0.00 | 0.35 |
| December | 0.712048E+09 | 33360.60 | 0.00 | 879147.93 | 441809.94 | 12240106.68 | 0.101299E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.277255E+10 | 0.428489E+10 | 0.00 | 25595137.68 | 0.362799E+09 | 0.504114E+09 | 0.147551E+10 | 0.00 | 0.35 |
| Minimum of Months | 1058842.95 | 0.00 | 0.00 | 4816.69 | 4054.22 | 0.00 | 31454.81 | 0.00 | 0.35 |
| Maximum of Months | 0.712048E+09 | 0.139179E+10 | 0.00 | 5636179.96 | 85280592.16 | 0.313491E+09 | 0.309805E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.227561E+09 | 0.00 | 0.00 | 0.00 | 86065.99 | 0.690114E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.279950E+09 | 839711.95 | 0.00 | 184358.73 | 1964924.24 | 0.388477E+09 | 28812039.60 | 0.00 | 0.35 |
| March | 0.381524E+09 | 13721721.17 | 0.00 | 1351299.09 | 4796865.61 | 0.00 | 0.180582E+09 | 0.00 | 0.35 |
| April | 0.144034E+09 | 37261537.92 | 0.00 | 3069359.60 | 9765114.98 | 0.00 | 0.204883E+09 | 0.00 | 0.35 |
| May | 46169708.17 | 0.229921E+09 | 0.00 | 2225447.31 | 33816723.08 | 0.00 | 73703087.63 | 0.00 | 0.36 |
| June | 11577791.73 | 0.773757E+09 | 0.00 | 982636.30 | 53079173.02 | 0.00 | 37423487.07 | 0.00 | 0.36 |
| July | 7491272.14 | 0.115172E+10 | 0.00 | 148105.46 | 79476951.66 | 0.00 | 982970.52 | 0.00 | 0.36 |
| August | 1254153.81 | 0.136331E+10 | 0.00 | 6946.12 | 81677651.07 | 0.00 | 20369.70 | 0.00 | 0.36 |
| September | 34090489.49 | 0.519862E+09 | 0.00 | 1099901.36 | 66903120.84 | 0.00 | 34212699.58 | 0.00 | 0.36 |
| October | 0.230306E+09 | 93279037.95 | 0.00 | 1924037.30 | 23081157.12 | 0.00 | 0.209831E+09 | 0.00 | 0.36 |
| November | 0.494970E+09 | 500071.68 | 0.00 | 657732.61 | 3639844.81 | 23869572.80 | 84374422.64 | 0.00 | 0.35 |
| December | 0.468223E+09 | 0.00 | 0.00 | 27995.34 | 1227218.89 | 0.276227E+09 | 7278512.34 | 0.00 | 0.35 |
| Annual Sum or Average | 0.232715E+10 | 0.418417E+10 | 0.00 | 11677819.20 | 0.359515E+09 | 0.137869E+10 | 0.862104E+09 | 0.00 | 0.35 |
| Minimum of Months | 1254153.81 | 0.00 | 0.00 | 0.00 | 86065.99 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.494970E+09 | 0.136331E+10 | 0.00 | 3069359.60 | 81677651.07 | 0.690114E+09 | 0.209831E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.642733E+09 | 0.00 | 0.00 | 64458.83 | 4676.53 | 0.312805E+09 | 13066308.66 | 0.00 | 0.35 |
| February | 0.452345E+09 | 1085297.72 | 0.00 | 1612301.03 | 1480008.73 | 0.172675E+09 | 0.103104E+09 | 0.00 | 0.35 |
| March | 0.257833E+09 | 16498315.01 | 0.00 | 4042105.27 | 4138138.68 | 0.00 | 0.310754E+09 | 0.00 | 0.35 |
| April | 0.117241E+09 | 42253844.66 | 0.00 | 4370618.43 | 8135619.23 | 0.00 | 0.236549E+09 | 0.00 | 0.35 |
| May | 46456146.15 | 0.242930E+09 | 0.00 | 2521168.48 | 33738530.22 | 0.00 | 74377398.31 | 0.00 | 0.36 |
| June | 12995772.09 | 0.778266E+09 | 0.00 | 1085326.86 | 50640374.28 | 0.00 | 38201660.59 | 0.00 | 0.36 |
| July | 6688920.02 | 0.116347E+10 | 0.00 | 141952.49 | 77537073.00 | 0.00 | 551507.26 | 0.00 | 0.36 |
| August | 1107085.82 | 0.139662E+10 | 0.00 | 6246.26 | 80945474.47 | 0.00 | 68936.39 | 0.00 | 0.36 |
| September | 32541326.71 | 0.561885E+09 | 0.00 | 1344980.35 | 62610701.44 | 0.00 | 32899640.04 | 0.00 | 0.36 |
| October | 0.155946E+09 | 0.111892E+09 | 0.00 | 5593232.65 | 22553200.43 | 0.00 | 0.274426E+09 | 0.00 | 0.36 |
| November | 0.332134E+09 | 2265540.76 | 0.00 | 4051396.79 | 2769428.89 | 0.00 | 0.307623E+09 | 0.00 | 0.35 |
| December | 0.705434E+09 | 22516.00 | 0.00 | 846925.57 | 419303.50 | 12824918.83 | 0.109813E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.276345E+10 | 0.431719E+10 | 0.00 | 25680713.01 | 0.344973E+09 | 0.498305E+09 | 0.150143E+10 | 0.00 | 0.35 |
| Minimum of Months | 1107085.82 | 0.00 | 0.00 | 6246.26 | 4676.53 | 0.00 | 68936.39 | 0.00 | 0.35 |
| Maximum of Months | 0.705434E+09 | 0.139662E+10 | 0.00 | 5593232.65 | 80945474.47 | 0.312805E+09 | 0.310754E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.211723E+09 | 0.00 | 0.00 | 0.00 | 61140.87 | 0.705379E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.262777E+09 | 820011.46 | 0.00 | 203621.02 | 1831732.42 | 0.395331E+09 | 39703422.53 | 0.00 | 0.35 |
| March | 0.373996E+09 | 13019236.07 | 0.00 | 1261692.41 | 4390469.48 | 0.00 | 0.185651E+09 | 0.00 | 0.35 |
| April | 0.140280E+09 | 37147971.58 | 0.00 | 3024497.21 | 8637128.20 | 0.00 | 0.210642E+09 | 0.00 | 0.35 |
| May | 49133505.32 | 0.235110E+09 | 0.00 | 2354898.07 | 31905575.80 | 0.00 | 74732669.88 | 0.00 | 0.36 |
| June | 13474462.92 | 0.782604E+09 | 0.00 | 1086932.57 | 49239814.61 | 0.00 | 37644238.83 | 0.00 | 0.36 |
| July | 7126779.06 | 0.116722E+10 | 0.00 | 142019.00 | 75704023.29 | 0.00 | 907276.38 | 0.00 | 0.36 |
| August | 1295050.81 | 0.137050E+10 | 0.00 | 8837.69 | 77525371.18 | 0.00 | 70574.01 | 0.00 | 0.36 |
| September | 35568499.96 | 0.524975E+09 | 0.00 | 1155652.68 | 64724874.32 | 0.00 | 35216434.40 | 0.00 | 0.36 |
| October | 0.244391E+09 | 94328951.71 | 0.00 | 1852245.54 | 21394918.80 | 0.00 | 0.193660E+09 | 0.00 | 0.36 |
| November | 0.498832E+09 | 390339.99 | 0.00 | 604507.07 | 3601721.22 | 20463033.50 | 85849160.61 | 0.00 | 0.35 |
| December | 0.492579E+09 | 0.00 | 0.00 | 30629.34 | 1194992.23 | 0.250096E+09 | 8492172.87 | 0.00 | 0.35 |
| Annual Sum or Average | 0.233118E+10 | 0.422611E+10 | 0.00 | 11725532.60 | 0.340212E+09 | 0.137127E+10 | 0.872570E+09 | 0.00 | 0.35 |
| Minimum of Months | 1295050.81 | 0.00 | 0.00 | 0.00 | 61140.87 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.498832E+09 | 0.137050E+10 | 0.00 | 3024497.21 | 77525371.18 | 0.705379E+09 | 0.210642E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.565227E+09 | 0.00 | 0.00 | 0.00 | 31701.65 | 0.388023E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.433062E+09 | 854592.53 | 0.00 | 411570.27 | 1723260.48 | 0.216009E+09 | 78800062.27 | 0.00 | 0.35 |
| March | 0.268759E+09 | 12767920.41 | 0.00 | 2098234.64 | 4619283.70 | 0.00 | 0.312292E+09 | 0.00 | 0.35 |
| April | 0.109462E+09 | 36670437.36 | 0.00 | 3386624.34 | 9608330.87 | 0.00 | 0.241198E+09 | 0.00 | 0.35 |
| May | 45736434.81 | 0.220504E+09 | 0.00 | 2254046.07 | 32022055.63 | 0.00 | 72725889.31 | 0.00 | 0.36 |
| June | 12438776.69 | 0.746935E+09 | 0.00 | 952548.58 | 53579943.70 | 0.00 | 37667817.17 | 0.00 | 0.36 |
| July | 6903858.62 | 0.111169E+10 | 0.00 | 153823.61 | 79479484.90 | 0.00 | 946849.29 | 0.00 | 0.36 |
| August | 1228518.95 | 0.131465E+10 | 0.00 | 6590.20 | 80882998.71 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 34666150.52 | 0.502204E+09 | 0.00 | 1228521.87 | 67153702.04 | 0.00 | 32601771.21 | 0.00 | 0.36 |
| October | 0.131825E+09 | 92754857.03 | 0.00 | 2727934.35 | 23457761.52 | 0.00 | 0.302793E+09 | 0.00 | 0.36 |
| November | 0.408558E+09 | 1209875.88 | 0.00 | 1383426.46 | 2607215.91 | 0.00 | 0.231349E+09 | 0.00 | 0.35 |
| December | 0.771850E+09 | 0.00 | 0.00 | 111823.43 | 986326.86 | 11180202.56 | 29305743.88 | 0.00 | 0.35 |
| Annual Sum or Average | 0.278972E+10 | 0.404024E+10 | 0.00 | 14715143.82 | 0.356152E+09 | 0.615213E+09 | 0.133968E+10 | 0.00 | 0.35 |
| Minimum of Months | 1228518.95 | 0.00 | 0.00 | 0.00 | 31701.65 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.771850E+09 | 0.131465E+10 | 0.00 | 3386624.34 | 80882998.71 | 0.388023E+09 | 0.312292E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.565974E+09 | 0.00 | 0.00 | 0.00 | 30670.45 | 0.387300E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.431395E+09 | 853295.53 | 0.00 | 419402.78 | 1707441.76 | 0.216419E+09 | 80145885.98 | 0.00 | 0.35 |
| March | 0.269080E+09 | 12757303.88 | 0.00 | 2091298.72 | 4583808.56 | 0.00 | 0.311982E+09 | 0.00 | 0.35 |
| April | 0.109263E+09 | 36687632.26 | 0.00 | 3385497.32 | 9612526.10 | 0.00 | 0.241411E+09 | 0.00 | 0.35 |
| May | 45625765.72 | 0.221060E+09 | 0.00 | 2267567.56 | 31997585.06 | 0.00 | 72940514.00 | 0.00 | 0.36 |
| June | 12492671.04 | 0.747448E+09 | 0.00 | 959065.90 | 53539078.08 | 0.00 | 37680989.11 | 0.00 | 0.36 |
| July | 6997583.43 | 0.111251E+10 | 0.00 | 145808.70 | 79453432.27 | 0.00 | 770279.10 | 0.00 | 0.36 |
| August | 1229960.71 | 0.131494E+10 | 0.00 | 6637.91 | 81020127.65 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 34680556.09 | 0.502640E+09 | 0.00 | 1231819.63 | 67124781.55 | 0.00 | 32589075.64 | 0.00 | 0.36 |
| October | 0.132604E+09 | 93157141.46 | 0.00 | 2719860.55 | 23500423.25 | 0.00 | 0.302075E+09 | 0.00 | 0.36 |
| November | 0.408913E+09 | 1204258.98 | 0.00 | 1377685.67 | 2600635.21 | 0.00 | 0.231294E+09 | 0.00 | 0.35 |
| December | 0.771074E+09 | 0.00 | 0.00 | 114515.60 | 984290.48 | 11459920.75 | 29891661.22 | 0.00 | 0.35 |
| Annual Sum or Average | 0.278933E+10 | 0.404326E+10 | 0.00 | 14719160.36 | 0.356155E+09 | 0.615180E+09 | 0.134078E+10 | 0.00 | 0.35 |
| Minimum of Months | 1229960.71 | 0.00 | 0.00 | 0.00 | 30670.45 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.771074E+09 | 0.131494E+10 | 0.00 | 3385497.32 | 81020127.65 | 0.387300E+09 | 0.311982E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.844448E+09 | 0.00 | 0.00 | 524372.87 | 0.00 | 88419509.15 | 0.119768E+09 | 0.00 | 0.35 |
| February | 0.555222E+09 | 1352815.47 | 0.00 | 2218425.51 | 1152412.93 | 22795232.56 | 0.205273E+09 | 0.00 | 0.35 |
| March | 0.145733E+09 | 16600903.50 | 0.00 | 5412625.82 | 4059422.86 | 0.00 | 0.441980E+09 | 0.00 | 0.35 |
| April | 90054116.90 | 42405359.35 | 0.00 | 4706231.14 | 8157286.99 | 0.00 | 0.261920E+09 | 0.00 | 0.35 |
| May | 41508360.08 | 0.230648E+09 | 0.00 | 2427065.09 | 33414679.71 | 0.00 | 74675103.02 | 0.00 | 0.36 |
| June | 11978553.29 | 0.744387E+09 | 0.00 | 971036.67 | 54000172.29 | 0.00 | 38442578.97 | 0.00 | 0.36 |
| July | 6285378.47 | 0.111093E+10 | 0.00 | 171417.59 | 81029089.39 | 0.00 | 894975.65 | 0.00 | 0.36 |
| August | 1043890.97 | 0.134921E+10 | 0.00 | 4849.48 | 84602792.27 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 31120805.88 | 0.547268E+09 | 0.00 | 1403892.13 | 64896942.97 | 0.00 | 31275119.66 | 0.00 | 0.36 |
| October | 92326885.09 | 0.113350E+09 | 0.00 | 6648445.92 | 23070864.85 | 0.00 | 0.334135E+09 | 0.00 | 0.36 |
| November | 0.189699E+09 | 3244826.24 | 0.00 | 6052014.46 | 2930995.28 | 0.00 | 0.469217E+09 | 0.00 | 0.35 |
| December | 0.613325E+09 | 177261.26 | 0.00 | 2234828.45 | 405824.55 | 0.00 | 0.292896E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.262274E+10 | 0.415958E+10 | 0.00 | 32775205.13 | 0.357720E+09 | 0.111215E+09 | 0.227048E+10 | 0.00 | 0.35 |
| Minimum of Months | 1043890.97 | 0.00 | 0.00 | 4849.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.844448E+09 | 0.134921E+10 | 0.00 | 6648445.92 | 84602792.27 | 88419509.15 | 0.469217E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.843599E+09 | 0.00 | 0.00 | 528647.31 | 0.00 | 88087654.51 | 0.120874E+09 | 0.00 | 0.35 |
| February | 0.553964E+09 | 1348180.70 | 0.00 | 2230036.84 | 1142464.44 | 23776827.19 | 0.205763E+09 | 0.00 | 0.35 |
| March | 0.146419E+09 | 16606385.44 | 0.00 | 5383139.56 | 4068298.02 | 0.00 | 0.440916E+09 | 0.00 | 0.35 |
| April | 90575944.66 | 42478031.98 | 0.00 | 4707185.56 | 8129330.95 | 0.00 | 0.261410E+09 | 0.00 | 0.35 |
| May | 41577149.75 | 0.231089E+09 | 0.00 | 2437329.43 | 33337652.34 | 0.00 | 74720779.25 | 0.00 | 0.36 |
| June | 11987083.72 | 0.744969E+09 | 0.00 | 978021.63 | 53923235.74 | 0.00 | 38530833.28 | 0.00 | 0.36 |
| July | 6330612.33 | 0.111162E+10 | 0.00 | 163157.30 | 80820780.80 | 0.00 | 806541.38 | 0.00 | 0.36 |
| August | 1045414.45 | 0.134959E+10 | 0.00 | 4895.30 | 84570309.21 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 31124068.09 | 0.547644E+09 | 0.00 | 1402349.14 | 64894211.26 | 0.00 | 31266475.02 | 0.00 | 0.36 |
| October | 92498454.49 | 0.113646E+09 | 0.00 | 6655324.02 | 23082762.60 | 0.00 | 0.334063E+09 | 0.00 | 0.36 |
| November | 0.189676E+09 | 3240237.32 | 0.00 | 6051592.97 | 2916518.63 | 0.00 | 0.469356E+09 | 0.00 | 0.35 |
| December | 0.611933E+09 | 176813.09 | 0.00 | 2246211.60 | 405973.63 | 0.00 | 0.294374E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.262073E+10 | 0.416241E+10 | 0.00 | 32787890.65 | 0.357292E+09 | 0.111864E+09 | 0.227208E+10 | 0.00 | 0.35 |
| Minimum of Months | 1045414.45 | 0.00 | 0.00 | 4895.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.843599E+09 | 0.134959E+10 | 0.00 | 6655324.02 | 84570309.21 | 88087654.51 | 0.469356E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.110387E+09 | 0.00 | 0.00 | 102526.45 | 57772.93 | 0.340099E+09 | 11613674.75 | 0.00 | 0.35 |
| February | 0.125265E+09 | 610662.59 | 124045.34 | 436519.78 | 793148.38 | 0.201058E+09 | 13590426.41 | 1342.53 | 0.35 |
| March | 0.173360E+09 | 8360199.70 | 0.00 | 1176959.28 | 2060172.02 | 48307815.82 | 35135662.92 | 0.00 | 0.35 |
| April | 0.114679E+09 | 20461946.89 | 0.00 | 1353228.65 | 4729241.86 | 15318197.59 | 46406751.87 | 0.00 | 0.35 |
| May | 44709689.14 | 0.114460E+09 | 0.00 | 925159.60 | 17153857.75 | 0.00 | 22331279.81 | 0.00 | 0.36 |
| June | 13048935.91 | 0.382606E+09 | 0.00 | 349356.82 | 21604417.03 | 0.00 | 12775272.33 | 0.00 | 0.36 |
| July | 3652136.20 | 0.568863E+09 | 0.00 | 74511.66 | 34398090.11 | 0.00 | 408742.22 | 0.00 | 0.36 |
| August | 732978.76 | 0.688045E+09 | 0.00 | 3107.07 | 34919222.85 | 0.00 | 5031.07 | 0.00 | 0.36 |
| September | 28905974.57 | 0.267463E+09 | 0.00 | 415783.65 | 28489807.19 | 0.00 | 11229390.30 | 0.00 | 0.36 |
| October | 0.145691E+09 | 51078886.84 | 0.00 | 1913762.37 | 10465248.10 | 23710140.19 | 34045736.62 | 0.00 | 0.35 |
| November | 0.170784E+09 | 823925.88 | 0.00 | 1045510.55 | 2144519.63 | 87475971.96 | 27548323.31 | 0.00 | 0.35 |
| December | 0.123842E+09 | 11858.26 | 0.00 | 239559.59 | 368116.57 | 0.235111E+09 | 17670319.88 | 0.00 | 0.35 |
| Annual Sum or Average | 0.105506E+10 | 0.210278E+10 | 124045.34 | 8035985.48 | 0.157184E+09 | 0.951080E+09 | 0.232761E+09 | 1342.53 | 0.35 |
| Minimum of Months | 732978.76 | 0.00 | 0.00 | 3107.07 | 57772.93 | 0.00 | 5031.07 | 0.00 | 0.35 |
| Maximum of Months | 0.173360E+09 | 0.688045E+09 | 124045.34 | 1913762.37 | 34919222.85 | 0.340099E+09 | 46406751.87 | 1342.53 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 25005495.72 | 0.00 | 34796.33 | 0.00 | 49998.60 | 0.425004E+09 | 0.00 | 670.93 | 0.35 |
| February | 71603973.49 | 294769.85 | 154116.83 | 21746.65 | 1397365.47 | 0.254977E+09 | 648242.27 | 1595.37 | 0.35 |
| March | 0.154756E+09 | 6883803.60 | 0.00 | 157765.75 | 3061558.60 | 73147841.68 | 12572153.81 | 0.00 | 0.35 |
| April | 0.117067E+09 | 17940878.20 | 0.00 | 825258.01 | 5419164.76 | 19542154.71 | 36132841.91 | 0.00 | 0.35 |
| May | 46749820.45 | 0.110961E+09 | 0.00 | 848287.08 | 16198301.18 | 0.00 | 21942257.59 | 0.00 | 0.36 |
| June | 12821979.13 | 0.384553E+09 | 0.00 | 366961.69 | 21413306.31 | 0.00 | 13041348.20 | 0.00 | 0.36 |
| July | 3990201.69 | 0.571780E+09 | 0.00 | 71325.48 | 33285762.64 | 0.00 | 494103.07 | 0.00 | 0.36 |
| August | 825422.85 | 0.677132E+09 | 0.00 | 5655.73 | 33786184.81 | 0.00 | 282.91 | 0.00 | 0.36 |
| September | 32139865.30 | 0.251201E+09 | 0.00 | 312104.04 | 29112418.27 | 0.00 | 10181606.76 | 0.00 | 0.36 |
| October | 0.148048E+09 | 42795549.82 | 0.00 | 325503.37 | 11489945.15 | 32815182.08 | 13535822.56 | 0.00 | 0.35 |
| November | 0.114495E+09 | 148307.52 | 153919.44 | 65868.53 | 2665431.29 | 0.144414E+09 | 3942047.32 | 595.18 | 0.35 |
| December | 52018408.96 | 0.00 | 42533.72 | 1612.19 | 711082.20 | 0.306283E+09 | 173234.47 | 299.34 | 0.35 |
| Annual Sum or Average | 0.779521E+09 | 0.206369E+10 | 385366.33 | 3002088.53 | 0.158591E+09 | 0.125618E+10 | 0.112664E+09 | 3160.83 | 0.35 |
| Minimum of Months | 825422.85 | 0.00 | 0.00 | 0.00 | 49998.60 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.154756E+09 | 0.677132E+09 | 154116.83 | 848287.08 | 33786184.81 | 0.425004E+09 | 36132841.91 | 1595.37 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.114212E+09 | 0.00 | 0.00 | 57618.54 | 43753.57 | 0.336706E+09 | 10698628.40 | 0.00 | 0.35 |
| February | 0.129605E+09 | 566985.30 | 172489.38 | 438237.83 | 707367.77 | 0.196660E+09 | 13816224.40 | 1973.68 | 0.35 |
| March | 0.171294E+09 | 8150282.52 | 0.00 | 1004459.42 | 1943661.48 | 46350958.68 | 36459544.43 | 0.00 | 0.35 |
| April | 0.119580E+09 | 20608249.10 | 0.00 | 1291824.18 | 4271108.69 | 13546740.79 | 45432009.98 | 0.00 | 0.35 |
| May | 47120949.17 | 0.117048E+09 | 0.00 | 1009473.01 | 15785600.94 | 0.00 | 23631259.56 | 0.00 | 0.36 |
| June | 13684646.71 | 0.386474E+09 | 0.00 | 416515.14 | 20477271.07 | 0.00 | 13688091.48 | 0.00 | 0.36 |
| July | 3644956.27 | 0.577237E+09 | 0.00 | 68700.78 | 31958880.85 | 0.00 | 482878.99 | 0.00 | 0.36 |
| August | 769384.25 | 0.692385E+09 | 0.00 | 3666.52 | 32804026.87 | 0.00 | 31431.50 | 0.00 | 0.36 |
| September | 30680748.08 | 0.269649E+09 | 0.00 | 476375.70 | 26992816.71 | 0.00 | 10716969.99 | 0.00 | 0.36 |
| October | 0.146207E+09 | 51711654.66 | 0.00 | 1847122.66 | 9980605.26 | 23554513.61 | 35611024.84 | 0.00 | 0.35 |
| November | 0.173929E+09 | 752037.39 | 0.00 | 968897.90 | 2093396.62 | 84643604.21 | 28224296.12 | 0.00 | 0.35 |
| December | 0.129390E+09 | 8170.92 | 0.00 | 194918.80 | 320593.50 | 0.230622E+09 | 16520501.19 | 0.00 | 0.35 |
| Annual Sum or Average | 0.108012E+10 | 0.212459E+10 | 172489.38 | 7777810.48 | 0.147379E+09 | 0.932083E+09 | 0.235313E+09 | 1973.68 | 0.35 |
| Minimum of Months | 769384.25 | 0.00 | 0.00 | 3666.52 | 43753.57 | 0.00 | 31431.50 | 0.00 | 0.35 |
| Maximum of Months | 0.173929E+09 | 0.692385E+09 | 172489.38 | 1847122.66 | 32804026.87 | 0.336706E+09 | 45432009.98 | 1973.68 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 20264231.26 | 0.00 | 0.00 | 0.00 | 70487.39 | 0.429401E+09 | 0.00 | 0.00 | 0.35 |
| February | 72879214.23 | 269226.73 | 154151.44 | 14588.12 | 1200942.59 | 0.253160E+09 | 383560.11 | 2269.82 | 0.35 |
| March | 0.159856E+09 | 6568252.27 | 0.00 | 133631.78 | 2565942.53 | 68150466.41 | 11228869.01 | 0.00 | 0.35 |
| April | 0.124092E+09 | 17938628.46 | 0.00 | 725553.43 | 4595516.76 | 17937241.14 | 31332630.05 | 0.00 | 0.35 |
| May | 48761717.02 | 0.113037E+09 | 0.00 | 908372.65 | 15166395.88 | 0.00 | 23773276.48 | 0.00 | 0.36 |
| June | 13654036.05 | 0.387914E+09 | 0.00 | 433220.94 | 20286165.87 | 0.00 | 13861302.92 | 0.00 | 0.36 |
| July | 3877883.36 | 0.578960E+09 | 0.00 | 68754.54 | 31415597.67 | 0.00 | 520216.90 | 0.00 | 0.36 |
| August | 886695.14 | 0.680354E+09 | 0.00 | 6069.50 | 31904053.82 | 0.00 | 24606.50 | 0.00 | 0.36 |
| September | 34115258.86 | 0.253148E+09 | 0.00 | 349798.61 | 27426950.76 | 0.00 | 9781818.90 | 0.00 | 0.36 |
| October | 0.149967E+09 | 43570921.68 | 0.00 | 260327.82 | 9918497.13 | 32151161.77 | 12643233.68 | 0.00 | 0.35 |
| November | 0.116572E+09 | 65705.66 | 196405.47 | 54003.73 | 2602279.09 | 0.141095E+09 | 3330408.96 | 683.91 | 0.35 |
| December | 49794652.81 | 0.00 | 7062.29 | 1191.42 | 712752.99 | 0.307354E+09 | 138142.10 | 48.14 | 0.35 |
| Annual Sum or Average | 0.794721E+09 | 0.208183E+10 | 357619.19 | 2955512.54 | 0.147866E+09 | 0.124925E+10 | 0.107018E+09 | 3001.87 | 0.35 |
| Minimum of Months | 886695.14 | 0.00 | 0.00 | 0.00 | 70487.39 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.159856E+09 | 0.680354E+09 | 196405.47 | 908372.65 | 31904053.82 | 0.429401E+09 | 31332630.05 | 2269.82 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 39136860.67 | 0.00 | 5672.85 | 0.00 | 72372.73 | 0.419773E+09 | 0.00 | 58.39 | 0.35 |
| February | 96171897.84 | 394523.22 | 28070.57 | 22686.37 | 1427916.80 | 0.241342E+09 | 1107380.83 | 107.24 | 0.35 |
| March | 0.187565E+09 | 6306665.37 | 0.00 | 178151.76 | 3044053.80 | 44632832.11 | 17102574.93 | 0.00 | 0.35 |
| April | 0.108091E+09 | 17691004.12 | 0.00 | 871633.77 | 5121477.13 | 11747002.80 | 55179743.54 | 0.00 | 0.35 |
| May | 39539603.56 | 0.107548E+09 | 0.00 | 835295.48 | 15575618.42 | 0.00 | 28221836.53 | 0.00 | 0.36 |
| June | 8629111.46 | 0.378230E+09 | 0.00 | 370271.21 | 22224510.01 | 0.00 | 17906082.64 | 0.00 | 0.36 |
| July | 3626988.78 | 0.561797E+09 | 0.00 | 71633.87 | 33760708.76 | 0.00 | 471256.47 | 0.00 | 0.36 |
| August | 787483.43 | 0.664279E+09 | 0.00 | 5915.07 | 34893713.00 | 0.00 | 708.39 | 0.00 | 0.36 |
| September | 24225987.41 | 0.245964E+09 | 0.00 | 370969.82 | 29393427.72 | 0.00 | 17408938.24 | 0.00 | 0.36 |
| October | 0.167838E+09 | 43022453.65 | 0.00 | 331393.55 | 10666484.06 | 14838864.39 | 21676652.40 | 0.00 | 0.35 |
| November | 0.156639E+09 | 103769.45 | 0.00 | 99066.83 | 2734840.64 | 0.105949E+09 | 9336936.40 | 0.00 | 0.35 |
| December | 85424178.06 | 0.00 | 0.00 | 8067.96 | 775512.88 | 0.282088E+09 | 1598723.06 | 0.00 | 0.35 |
| Annual Sum or Average | 0.917676E+09 | 0.202534E+10 | 33743.42 | 3165085.68 | 0.159691E+09 | 0.112037E+10 | 0.170011E+09 | 165.63 | 0.35 |
| Minimum of Months | 787483.43 | 0.00 | 0.00 | 0.00 | 72372.73 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.187565E+09 | 0.664279E+09 | 28070.57 | 871633.77 | 34893713.00 | 0.419773E+09 | 55179743.54 | 107.24 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 38962386.33 | 0.00 | 5684.84 | 0.00 | 71187.75 | 0.419941E+09 | 0.00 | 47.89 | 0.35 |
| February | 96420321.28 | 413943.72 | 28075.94 | 22156.57 | 1383741.83 | 0.241110E+09 | 1097966.79 | 117.19 | 0.35 |
| March | 0.187707E+09 | 6297051.26 | 0.00 | 175980.84 | 3030347.32 | 44514592.80 | 16989517.57 | 0.00 | 0.35 |
| April | 0.108394E+09 | 17835212.80 | 0.00 | 865460.26 | 4967518.30 | 11665221.29 | 55051749.20 | 0.00 | 0.35 |
| May | 39673187.68 | 0.107941E+09 | 0.00 | 842570.75 | 15523585.52 | 0.00 | 28214815.06 | 0.00 | 0.36 |
| June | 8680209.33 | 0.378622E+09 | 0.00 | 374883.61 | 22120168.60 | 0.00 | 17889657.69 | 0.00 | 0.36 |
| July | 3626740.23 | 0.562402E+09 | 0.00 | 72279.35 | 33622954.01 | 0.00 | 481379.19 | 0.00 | 0.36 |
| August | 789540.76 | 0.664668E+09 | 0.00 | 5992.24 | 34776462.91 | 0.00 | 701.45 | 0.00 | 0.36 |
| September | 24390711.28 | 0.246430E+09 | 0.00 | 372027.37 | 29175528.47 | 0.00 | 17344891.65 | 0.00 | 0.36 |
| October | 0.167734E+09 | 43145556.61 | 0.00 | 328162.38 | 10637785.75 | 15036343.68 | 21740505.44 | 0.00 | 0.35 |
| November | 0.156805E+09 | 99979.09 | 0.00 | 97303.68 | 2734721.94 | 0.106170E+09 | 8876834.59 | 0.00 | 0.35 |
| December | 85174680.32 | 0.00 | 0.00 | 7995.40 | 773930.04 | 0.282272E+09 | 1599056.70 | 0.00 | 0.35 |
| Annual Sum or Average | 0.918358E+09 | 0.202785E+10 | 33760.78 | 3164812.43 | 0.158818E+09 | 0.112071E+10 | 0.169287E+09 | 165.07 | 0.35 |
| Minimum of Months | 789540.76 | 0.00 | 0.00 | 0.00 | 71187.75 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.187707E+09 | 0.664668E+09 | 28075.94 | 865460.26 | 34776462.91 | 0.419941E+09 | 55051749.20 | 117.19 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.170150E+09 | 0.00 | 0.00 | 109091.48 | 35215.26 | 0.290848E+09 | 16337922.60 | 0.00 | 0.35 |
| February | 0.169123E+09 | 598909.70 | 28847.64 | 499884.49 | 864407.11 | 0.165789E+09 | 21550193.83 | 206.67 | 0.35 |
| March | 0.194607E+09 | 8025016.44 | 0.00 | 1189960.93 | 2037132.04 | 19788998.74 | 55232214.86 | 0.00 | 0.35 |
| April | 0.104677E+09 | 20663401.06 | 0.00 | 1387799.86 | 4370808.63 | 5823640.96 | 69289413.37 | 0.00 | 0.35 |
| May | 37105429.41 | 0.112622E+09 | 0.00 | 907089.89 | 16713844.92 | 0.00 | 28958806.50 | 0.00 | 0.36 |
| June | 9242192.48 | 0.377219E+09 | 0.00 | 366311.19 | 22658674.46 | 0.00 | 17263914.22 | 0.00 | 0.36 |
| July | 3382275.94 | 0.560380E+09 | 0.00 | 76514.95 | 35084109.28 | 0.00 | 395709.83 | 0.00 | 0.36 |
| August | 686641.14 | 0.679284E+09 | 0.00 | 3310.21 | 35887855.19 | 0.00 | 4975.95 | 0.00 | 0.36 |
| September | 21595596.12 | 0.266069E+09 | 0.00 | 482480.98 | 28803148.37 | 0.00 | 17229587.23 | 0.00 | 0.36 |
| October | 0.145565E+09 | 52445477.24 | 0.00 | 2028401.91 | 10298826.27 | 10490210.44 | 59302047.40 | 0.00 | 0.36 |
| November | 0.203936E+09 | 873728.91 | 0.00 | 1245000.71 | 1881199.89 | 45491161.11 | 52530618.91 | 0.00 | 0.35 |
| December | 0.178627E+09 | 8434.17 | 0.00 | 316825.55 | 290101.14 | 0.183930E+09 | 32085441.13 | 0.00 | 0.35 |
| Annual Sum or Average | 0.123870E+10 | 0.207819E+10 | 28847.64 | 8612672.15 | 0.158925E+09 | 0.722161E+09 | 0.370181E+09 | 206.67 | 0.35 |
| Minimum of Months | 686641.14 | 0.00 | 0.00 | 3310.21 | 35215.26 | 0.00 | 4975.95 | 0.00 | 0.35 |
| Maximum of Months | 0.203936E+09 | 0.679284E+09 | 28847.64 | 2028401.91 | 35887855.19 | 0.290848E+09 | 69289413.37 | 206.67 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.169425E+09 | 0.00 | 0.00 | 110037.42 | 34627.14 | 0.291116E+09 | 16788774.47 | 0.00 | 0.35 |
| February | 0.168890E+09 | 600254.77 | 28853.65 | 507252.73 | 856611.09 | 0.166070E+09 | 21561256.13 | 217.30 | 0.35 |
| March | 0.194869E+09 | 8003334.06 | 0.00 | 1187491.74 | 2009498.36 | 19886646.20 | 54817661.55 | 0.00 | 0.35 |
| April | 0.104612E+09 | 20600078.98 | 0.00 | 1390661.61 | 4311750.40 | 5822569.82 | 69694146.45 | 0.00 | 0.35 |
| May | 37213462.92 | 0.112478E+09 | 0.00 | 917448.45 | 16594720.49 | 0.00 | 29173528.10 | 0.00 | 0.36 |
| June | 9294289.52 | 0.376891E+09 | 0.00 | 372631.53 | 22526264.73 | 0.00 | 17355847.63 | 0.00 | 0.36 |
| July | 3443136.22 | 0.560100E+09 | 0.00 | 72578.72 | 34781055.65 | 0.00 | 356100.26 | 0.00 | 0.36 |
| August | 690565.26 | 0.678583E+09 | 0.00 | 3394.48 | 35772512.64 | 0.00 | 4979.73 | 0.00 | 0.36 |
| September | 21766145.24 | 0.265766E+09 | 0.00 | 488143.98 | 28636268.98 | 0.00 | 17220747.55 | 0.00 | 0.36 |
| October | 0.145224E+09 | 52386148.33 | 0.00 | 2040982.29 | 10246891.86 | 10603821.49 | 59774975.41 | 0.00 | 0.36 |
| November | 0.204114E+09 | 862910.69 | 0.00 | 1249179.74 | 1870005.02 | 45599339.57 | 52638394.03 | 0.00 | 0.35 |
| December | 0.178584E+09 | 8359.20 | 0.00 | 318468.94 | 286688.22 | 0.183684E+09 | 32399239.88 | 0.00 | 0.35 |
| Annual Sum or Average | 0.123813E+10 | 0.207628E+10 | 28853.65 | 8658271.62 | 0.157927E+09 | 0.722782E+09 | 0.371786E+09 | 217.30 | 0.35 |
| Minimum of Months | 690565.26 | 0.00 | 0.00 | 3394.48 | 34627.14 | 0.00 | 4979.73 | 0.00 | 0.35 |
| Maximum of Months | 0.204114E+09 | 0.678583E+09 | 28853.65 | 2040982.29 | 35772512.64 | 0.291116E+09 | 69694146.45 | 217.30 | 0.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.101101E+12 | 0.101897E+11 | 0.00 | 0.188679E+10 | -0.106036E+11 |
| February | 0.960553E+11 | 0.957376E+10 | 0.00 | 0.142729E+10 | -0.165595E+10 |
| March | 0.134341E+12 | 0.101678E+11 | 0.00 | 0.117032E+10 | 0.198304E+11 |
| April | 0.144117E+12 | 0.690988E+10 | 0.00 | 0.833488E+09 | 0.411454E+11 |
| May | 0.155340E+12 | 0.428415E+10 | 0.00 | 0.423083E+09 | 0.777572E+11 |
| June | 0.148787E+12 | -851616315.3 | 0.00 | -176984238.8 | 0.124524E+12 |
| July | 0.145234E+12 | -0.191314E+10 | 0.00 | -401538755.8 | 0.147781E+12 |
| August | 0.137449E+12 | -0.325908E+10 | 0.00 | -618827369.7 | 0.159113E+12 |
| September | 0.110992E+12 | 0.211969E+10 | 0.00 | 0.178984E+09 | 0.980141E+11 |
| October | 0.111375E+12 | 0.720109E+10 | 0.00 | 0.994686E+09 | 0.436040E+11 |
| November | 0.842479E+11 | 0.922909E+10 | 0.00 | 0.138607E+10 | 0.142976E+11 |
| December | 0.830872E+11 | 0.921592E+10 | 0.00 | 0.170588E+10 | -732380778.7 |
| Annual Sum or Average | 0.145213E+13 | 0.628673E+11 | 0.00 | 0.880924E+10 | 0.713075E+12 |
| Minimum of Months | 0.830872E+11 | -0.325908E+10 | 0.00 | -618827369.7 | -0.106036E+11 |