Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: ApartmentMidRise
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2024-07-03 12:21:23
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 1437.43 | 458.57 | 509.01 |
| Net Site Energy | 1437.43 | 458.57 | 509.01 |
| Total Source Energy | 3936.49 | 1255.81 | 1393.95 |
| Net Source Energy | 3936.49 | 1255.81 | 1393.95 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 3134.61 |
| Net Conditioned Building Area | 2823.98 |
| Unconditioned Building Area | 310.64 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 422.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 73.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 33.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 454.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 159.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 295.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.51 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1141.78 | 295.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.51 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 422.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 67.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 5.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 33.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | ElevatorLift | 67.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLightsFan | 0.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MiscPlug | 386.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 159.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.51 | |
| Water Heater | 0.00 | 295.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 422.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 73.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 33.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 454.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 159.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 0.00 | 295.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.51 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 37.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 205.99 | 104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Other | 160.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 404.31 | 104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 33.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 185.57 | 94.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Other | 144.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 364.25 | 94.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1141.776 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1141.776 | 100.00 |
| Total On-Site and Utility Electric Sources | 1141.776 | 100.00 |
| Total Electricity End Uses | 1141.776 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | 0.00 |
| Air to Air Heat Recovery for Cooling | 213.44 | 87.81 |
| Air to Air Heat Recovery for Heating | 29.62 | 12.19 |
| High-Temperature Geothermal* | 0.00 | 0.00 |
| Solar Water Thermal | 0.00 | 0.00 |
| Solar Air Thermal | 0.00 | 0.00 |
| Total On-Site Thermal Sources | 243.06 | 100.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 1875.51 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 1875.51 | 100.00 |
| Total Water End Uses | 1875.51 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8760.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneHeatingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneElectricSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PeakSpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainComponentsAtCoolingPeakMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ComfortReportSimple55Monthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |OccupantComfortDataSummaryMonthly
| OCCUP_GSW | OCCUP_GNW | OCCUP_OFFICE | OCCUP_GNE | OCCUP_GN1 | OCCUP_GN2 | OCCUP_GS1 | OCCUP_GS2 | OCCUP_MSW | OCCUP_MNW | OCCUP_MSE | OCCUP_MNE | OCCUP_MN1 | OCCUP_MN2 | OCCUP_MS1 | OCCUP_MS2 | OCCUP_TSW | OCCUP_TNW | OCCUP_TSE | OCCUP_TNE | OCCUP_TN1 | OCCUP_TN2 | OCCUP_TS1 | OCCUP_TS2 | OCCUP_T CORRIDOR | OCCUP_G CORRIDOR | OCCUP_M CORRIDOR |DXReportMonthly
| SPLIT GSW HP COOLING COIL | SPLIT GNW HP COOLING COIL | SPLIT OFFICE HP COOLING COIL | SPLIT GNE HP COOLING COIL | SPLIT GN1 HP COOLING COIL | SPLIT GN2 HP COOLING COIL | SPLIT GS1 HP COOLING COIL | SPLIT GS2 HP COOLING COIL | SPLIT MSW HP COOLING COIL | SPLIT MNW HP COOLING COIL | SPLIT MSE HP COOLING COIL | SPLIT MNE HP COOLING COIL | SPLIT MN1 HP COOLING COIL | SPLIT MN2 HP COOLING COIL | SPLIT MS1 HP COOLING COIL | SPLIT MS2 HP COOLING COIL | SPLIT TSW HP COOLING COIL | SPLIT TNW HP COOLING COIL | SPLIT TSE HP COOLING COIL | SPLIT TNE HP COOLING COIL | SPLIT TN1 HP COOLING COIL | SPLIT TN2 HP COOLING COIL | SPLIT TS1 HP COOLING COIL | SPLIT TS2 HP COOLING COIL |WindowReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowEnergyReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |WindowEnergyZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| SPLIT GSW HEATING COIL | SPLIT GNW HEATING COIL | SPLIT OFFICE HEATING COIL | SPLIT GNE HEATING COIL | SPLIT GN1 HEATING COIL | SPLIT GN2 HEATING COIL | SPLIT GS1 HEATING COIL | SPLIT GS2 HEATING COIL | SPLIT MSW HEATING COIL | SPLIT MNW HEATING COIL | SPLIT MSE HEATING COIL | SPLIT MNE HEATING COIL | SPLIT MN1 HEATING COIL | SPLIT MN2 HEATING COIL | SPLIT MS1 HEATING COIL | SPLIT MS2 HEATING COIL | SPLIT TSW HEATING COIL | SPLIT TNW HEATING COIL | SPLIT TSE HEATING COIL | SPLIT TNE HEATING COIL | SPLIT TN1 HEATING COIL | SPLIT TN2 HEATING COIL | SPLIT TS1 HEATING COIL | SPLIT TS2 HEATING COIL | SPLIT GSW_SUPPHEATCOIL | SPLIT GNW_SUPPHEATCOIL | SPLIT OFFICE_SUPPHEATCOIL | SPLIT GNE_SUPPHEATCOIL | SPLIT GN1_SUPPHEATCOIL | SPLIT GN2_SUPPHEATCOIL | SPLIT GS1_SUPPHEATCOIL | SPLIT GS2_SUPPHEATCOIL | SPLIT MSW_SUPPHEATCOIL | SPLIT MNW_SUPPHEATCOIL | SPLIT MSE_SUPPHEATCOIL | SPLIT MNE_SUPPHEATCOIL | SPLIT MN1_SUPPHEATCOIL | SPLIT MN2_SUPPHEATCOIL | SPLIT MS1_SUPPHEATCOIL | SPLIT MS2_SUPPHEATCOIL | SPLIT TSW_SUPPHEATCOIL | SPLIT TNW_SUPPHEATCOIL | SPLIT TSE_SUPPHEATCOIL | SPLIT TNE_SUPPHEATCOIL | SPLIT TN1_SUPPHEATCOIL | SPLIT TN2_SUPPHEATCOIL | SPLIT TS1_SUPPHEATCOIL | SPLIT TS2_SUPPHEATCOIL | SPLIT GSW HP COOLING COIL | SPLIT GNW HP COOLING COIL | SPLIT OFFICE HP COOLING COIL | SPLIT GNE HP COOLING COIL | SPLIT GN1 HP COOLING COIL | SPLIT GN2 HP COOLING COIL | SPLIT GS1 HP COOLING COIL | SPLIT GS2 HP COOLING COIL | SPLIT MSW HP COOLING COIL | SPLIT MNW HP COOLING COIL | SPLIT MSE HP COOLING COIL | SPLIT MNE HP COOLING COIL | SPLIT MN1 HP COOLING COIL | SPLIT MN2 HP COOLING COIL | SPLIT MS1 HP COOLING COIL | SPLIT MS2 HP COOLING COIL | SPLIT TSW HP COOLING COIL | SPLIT TNW HP COOLING COIL | SPLIT TSE HP COOLING COIL | SPLIT TNE HP COOLING COIL | SPLIT TN1 HP COOLING COIL | SPLIT TN2 HP COOLING COIL | SPLIT TS1 HP COOLING COIL | SPLIT TS2 HP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| SPLIT GSW SUPPLY FAN | G SW APARTMENT ERV SUP FAN | G SW APARTMENT ERV EXH FAN | SPLIT GNW SUPPLY FAN | G NW APARTMENT ERV SUP FAN | G NW APARTMENT ERV EXH FAN | SPLIT OFFICE SUPPLY FAN | SPLIT GNE SUPPLY FAN | G NE APARTMENT ERV SUP FAN | G NE APARTMENT ERV EXH FAN | SPLIT GN1 SUPPLY FAN | G N1 APARTMENT ERV SUP FAN | G N1 APARTMENT ERV EXH FAN | SPLIT GN2 SUPPLY FAN | G N2 APARTMENT ERV SUP FAN | G N2 APARTMENT ERV EXH FAN | SPLIT GS1 SUPPLY FAN | G S1 APARTMENT ERV SUP FAN | G S1 APARTMENT ERV EXH FAN | SPLIT GS2 SUPPLY FAN | G S2 APARTMENT ERV SUP FAN | G S2 APARTMENT ERV EXH FAN | SPLIT MSW SUPPLY FAN | M SW APARTMENT ERV SUP FAN | M SW APARTMENT ERV EXH FAN | SPLIT MNW SUPPLY FAN | M NW APARTMENT ERV SUP FAN | M NW APARTMENT ERV EXH FAN | SPLIT MSE SUPPLY FAN | M SE APARTMENT ERV SUP FAN | M SE APARTMENT ERV EXH FAN | SPLIT MNE SUPPLY FAN | M NE APARTMENT ERV SUP FAN | M NE APARTMENT ERV EXH FAN | SPLIT MN1 SUPPLY FAN | M N1 APARTMENT ERV SUP FAN | M N1 APARTMENT ERV EXH FAN | SPLIT MN2 SUPPLY FAN | M N2 APARTMENT ERV SUP FAN | M N2 APARTMENT ERV EXH FAN | SPLIT MS1 SUPPLY FAN | M S1 APARTMENT ERV SUP FAN | M S1 APARTMENT ERV EXH FAN | SPLIT MS2 SUPPLY FAN | M S2 APARTMENT ERV SUP FAN | M S2 APARTMENT ERV EXH FAN | SPLIT TSW SUPPLY FAN | T SW APARTMENT ERV SUP FAN | T SW APARTMENT ERV EXH FAN | SPLIT TNW SUPPLY FAN | T NW APARTMENT ERV SUP FAN | T NW APARTMENT ERV EXH FAN | SPLIT TSE SUPPLY FAN | T SE APARTMENT ERV SUP FAN | T SE APARTMENT ERV EXH FAN | SPLIT TNE SUPPLY FAN | T NE APARTMENT ERV SUP FAN | T NE APARTMENT ERV EXH FAN | SPLIT TN1 SUPPLY FAN | T N1 APARTMENT ERV SUP FAN | T N1 APARTMENT ERV EXH FAN | SPLIT TN2 SUPPLY FAN | T N2 APARTMENT ERV SUP FAN | T N2 APARTMENT ERV EXH FAN | SPLIT TS1 SUPPLY FAN | T S1 APARTMENT ERV SUP FAN | T S1 APARTMENT ERV EXH FAN | SPLIT TS2 SUPPLY FAN | T S2 APARTMENT ERV SUP FAN | T S2 APARTMENT ERV EXH FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AirLoopSystemEnergyAndWaterUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentLoadsMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentEnergyUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |MechanicalVentilationLoadsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
| Latitude [deg] | 25.25 |
| Longitude [deg] | 55.33 |
| Elevation [m] | 5.00 |
| Time Zone | 4.00 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Above Ground Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Window Opening Area [m2] | 306.92 | 112.97 | 43.82 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Above Ground Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Above Ground Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Above Ground Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Total | |
| Gross Roof Area [m2] | 783.65 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 7.4895 | 18.58 | 6.6700 |
| G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 5.4896 | 35.30 | 6.6700 |
| T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 5.4896 | 35.30 | 6.6700 |
| T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 1.11 | 1.11 | 5.2871 | 18.58 | 0.0000 |
| G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 3.32 | 3.32 | 5.2871 | 18.58 | 515.3919 |
| M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 0.00 | 1.11 | 1.11 | 5.2871 | 18.58 | 0.0000 |
| Total | 3134.61 | 9553.84 | 1542.04 | 0.00 | 306.92 | 306.92 | 5.5258 | 31.67 | 18.7777 | |||
| Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 0.00 | 300.26 | 300.26 | 5.5521 | 34.33 | 6.6700 | |||
| Unconditioned Total | 310.64 | 946.78 | 40.87 | 0.00 | 6.66 | 6.66 | 5.2871 | 18.58 | 128.8480 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| G SW APARTMENT | 88.25 | Yes | Yes | 1.00 | G SW APARTMENT | GENERAL | G SW APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| G NW APARTMENT | 88.25 | Yes | Yes | 1.00 | G NW APARTMENT | GENERAL | G NW APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| OFFICE | 88.25 | Yes | Yes | 1.00 | OFFICE | GENERAL | OFFICE | 7.4895 | 18.58 | 6.6700 | |
| G NE APARTMENT | 88.25 | Yes | Yes | 1.00 | G NE APARTMENT | GENERAL | G NE APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| G N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N1 APARTMENT | GENERAL | G N1 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| G N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N2 APARTMENT | GENERAL | G N2 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| G S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S1 APARTMENT | GENERAL | G S1 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| G S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S2 APARTMENT | GENERAL | G S2 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M SW APARTMENT | 88.25 | Yes | Yes | 2.00 | M SW APARTMENT | GENERAL | M SW APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M NW APARTMENT | 88.25 | Yes | Yes | 2.00 | M NW APARTMENT | GENERAL | M NW APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M SE APARTMENT | 88.25 | Yes | Yes | 2.00 | M SE APARTMENT | GENERAL | M SE APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M NE APARTMENT | 88.25 | Yes | Yes | 2.00 | M NE APARTMENT | GENERAL | M NE APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M N1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N1 APARTMENT | GENERAL | M N1 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M N2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N2 APARTMENT | GENERAL | M N2 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M S1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S1 APARTMENT | GENERAL | M S1 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| M S2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S2 APARTMENT | GENERAL | M S2 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T SW APARTMENT | 88.25 | Yes | Yes | 1.00 | T SW APARTMENT | GENERAL | T SW APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T NW APARTMENT | 88.25 | Yes | Yes | 1.00 | T NW APARTMENT | GENERAL | T NW APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T SE APARTMENT | 88.25 | Yes | Yes | 1.00 | T SE APARTMENT | GENERAL | T SE APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T NE APARTMENT | 88.25 | Yes | Yes | 1.00 | T NE APARTMENT | GENERAL | T NE APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N1 APARTMENT | GENERAL | T N1 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N2 APARTMENT | GENERAL | T N2 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S1 APARTMENT | GENERAL | T S1 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S2 APARTMENT | GENERAL | T S2 APARTMENT | 5.4896 | 35.30 | 6.6700 | |
| T CORRIDOR | 77.66 | No | Yes | 1.00 | T CORRIDOR | GENERAL | T CORRIDOR | 5.2871 | 18.58 | 0.0000 | |
| G CORRIDOR | 77.66 | No | Yes | 1.00 | G CORRIDOR | GENERAL | G CORRIDOR | 5.2871 | 18.58 | 515.3919 | |
| M CORRIDOR | 77.66 | No | Yes | 2.00 | M CORRIDOR | GENERAL | M CORRIDOR | 5.2871 | 18.58 | 0.0000 | |
| Total | 3134.61 | 5.5258 | 15.84 | 18.7777 | |||||||
| Conditioned Total | 2823.98 | 5.5521 | 17.17 | 6.6700 | |||||||
| Unconditioned Total | 310.64 | 5.2871 | 9.29 | 128.8480 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 3134.61 | 2823.98 | 310.64 | 0.00 | 4.1584 | 41.91 | 17.2755 |
| Total | 3134.61 | 2823.98 | 310.64 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 10-AUG-16:10 | 13-JAN-07:00 | - | - | - | - | - | - | - | - | - | - | 23-JAN-07:10 |
| Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 36096.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 3020.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 22246.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 9758.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 14.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 21361.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 71136.83 | 21361.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 36096.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 2720.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 299.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | ElevatorLift | 3772.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLightsFan | 31.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MiscPlug | 18442.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 9758.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 14.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Water Heater | 0.00 | 21361.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 1336.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 231.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 104.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1437.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 504.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 1.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 320.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 3616.00 | 320.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 473.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 81.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 37.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 509.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 178.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 113.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1280.47 | 113.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 426.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 73.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 33.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 458.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 160.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 102.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1153.57 | 102.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
ZoneHVAC:EnergyRecoveryVentilator| User-Specified Supply Air Flow Rate [m3/s] | User-Specified Exhaust Air Flow Rate [m3/s] | |
| G SW APARTMENT ERV | 0.025955 | 0.025955 |
| G NW APARTMENT ERV | 0.025955 | 0.025955 |
| G NE APARTMENT ERV | 0.025955 | 0.025955 |
| G N1 APARTMENT ERV | 0.025955 | 0.025955 |
| G N2 APARTMENT ERV | 0.025955 | 0.025955 |
| G S1 APARTMENT ERV | 0.025955 | 0.025955 |
| G S2 APARTMENT ERV | 0.025955 | 0.025955 |
| M SW APARTMENT ERV | 0.051909 | 0.051909 |
| M NW APARTMENT ERV | 0.051909 | 0.051909 |
| M SE APARTMENT ERV | 0.051909 | 0.051909 |
| M NE APARTMENT ERV | 0.051909 | 0.051909 |
| M N1 APARTMENT ERV | 0.051909 | 0.051909 |
| M N2 APARTMENT ERV | 0.051909 | 0.051909 |
| M S1 APARTMENT ERV | 0.051909 | 0.051909 |
| M S2 APARTMENT ERV | 0.051909 | 0.051909 |
| T SW APARTMENT ERV | 0.025955 | 0.025955 |
| T NW APARTMENT ERV | 0.025955 | 0.025955 |
| T SE APARTMENT ERV | 0.025955 | 0.025955 |
| T NE APARTMENT ERV | 0.025955 | 0.025955 |
| T N1 APARTMENT ERV | 0.025955 | 0.025955 |
| T N2 APARTMENT ERV | 0.025955 | 0.025955 |
| T S1 APARTMENT ERV | 0.025955 | 0.025955 |
| T S2 APARTMENT ERV | 0.025955 | 0.025955 |
| Design Size Maximum Flow Rate [m3/s] | |
| G SW APARTMENT ERV SUP FAN | 0.025955 |
| G SW APARTMENT ERV EXH FAN | 0.025955 |
| G NW APARTMENT ERV SUP FAN | 0.025955 |
| G NW APARTMENT ERV EXH FAN | 0.025955 |
| G NE APARTMENT ERV SUP FAN | 0.025955 |
| G NE APARTMENT ERV EXH FAN | 0.025955 |
| G N1 APARTMENT ERV SUP FAN | 0.025955 |
| G N1 APARTMENT ERV EXH FAN | 0.025955 |
| G N2 APARTMENT ERV SUP FAN | 0.025955 |
| G N2 APARTMENT ERV EXH FAN | 0.025955 |
| G S1 APARTMENT ERV SUP FAN | 0.025955 |
| G S1 APARTMENT ERV EXH FAN | 0.025955 |
| G S2 APARTMENT ERV SUP FAN | 0.025955 |
| G S2 APARTMENT ERV EXH FAN | 0.025955 |
| M SW APARTMENT ERV SUP FAN | 0.051909 |
| M SW APARTMENT ERV EXH FAN | 0.051909 |
| M NW APARTMENT ERV SUP FAN | 0.051909 |
| M NW APARTMENT ERV EXH FAN | 0.051909 |
| M SE APARTMENT ERV SUP FAN | 0.051909 |
| M SE APARTMENT ERV EXH FAN | 0.051909 |
| M NE APARTMENT ERV SUP FAN | 0.051909 |
| M NE APARTMENT ERV EXH FAN | 0.051909 |
| M N1 APARTMENT ERV SUP FAN | 0.051909 |
| M N1 APARTMENT ERV EXH FAN | 0.051909 |
| M N2 APARTMENT ERV SUP FAN | 0.051909 |
| M N2 APARTMENT ERV EXH FAN | 0.051909 |
| M S1 APARTMENT ERV SUP FAN | 0.051909 |
| M S1 APARTMENT ERV EXH FAN | 0.051909 |
| M S2 APARTMENT ERV SUP FAN | 0.051909 |
| M S2 APARTMENT ERV EXH FAN | 0.051909 |
| T SW APARTMENT ERV SUP FAN | 0.025955 |
| T SW APARTMENT ERV EXH FAN | 0.025955 |
| T NW APARTMENT ERV SUP FAN | 0.025955 |
| T NW APARTMENT ERV EXH FAN | 0.025955 |
| T SE APARTMENT ERV SUP FAN | 0.025955 |
| T SE APARTMENT ERV EXH FAN | 0.025955 |
| T NE APARTMENT ERV SUP FAN | 0.025955 |
| T NE APARTMENT ERV EXH FAN | 0.025955 |
| T N1 APARTMENT ERV SUP FAN | 0.025955 |
| T N1 APARTMENT ERV EXH FAN | 0.025955 |
| T N2 APARTMENT ERV SUP FAN | 0.025955 |
| T N2 APARTMENT ERV EXH FAN | 0.025955 |
| T S1 APARTMENT ERV SUP FAN | 0.025955 |
| T S1 APARTMENT ERV EXH FAN | 0.025955 |
| T S2 APARTMENT ERV SUP FAN | 0.025955 |
| T S2 APARTMENT ERV EXH FAN | 0.025955 |
| SPLIT GSW SUPPLY FAN | 0.399689 |
| SPLIT GNW SUPPLY FAN | 0.387246 |
| SPLIT OFFICE SUPPLY FAN | 0.458620 |
| SPLIT GNE SUPPLY FAN | 0.370495 |
| SPLIT GN1 SUPPLY FAN | 0.318347 |
| SPLIT GN2 SUPPLY FAN | 0.318025 |
| SPLIT GS1 SUPPLY FAN | 0.331986 |
| SPLIT GS2 SUPPLY FAN | 0.334741 |
| SPLIT MSW SUPPLY FAN | 0.835589 |
| SPLIT MNW SUPPLY FAN | 0.808232 |
| SPLIT MSE SUPPLY FAN | 0.794723 |
| SPLIT MNE SUPPLY FAN | 0.767504 |
| SPLIT MN1 SUPPLY FAN | 0.657268 |
| SPLIT MN2 SUPPLY FAN | 0.656534 |
| SPLIT MS1 SUPPLY FAN | 0.687562 |
| SPLIT MS2 SUPPLY FAN | 0.686818 |
| SPLIT TSW SUPPLY FAN | 0.457144 |
| SPLIT TNW SUPPLY FAN | 0.445881 |
| SPLIT TSE SUPPLY FAN | 0.428046 |
| SPLIT TNE SUPPLY FAN | 0.416802 |
| SPLIT TN1 SUPPLY FAN | 0.369527 |
| SPLIT TN2 SUPPLY FAN | 0.368543 |
| SPLIT TS1 SUPPLY FAN | 0.381595 |
| SPLIT TS2 SUPPLY FAN | 0.380617 |
| Design Size Nominal Supply Air Flow Rate [m3/s] | |
| G SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| M SW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M SE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| T SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T SE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| G SW APARTMENT DIRECT AIR | 0.399689 |
| G NW APARTMENT DIRECT AIR | 0.387246 |
| OFFICE DIRECT AIR | 0.458620 |
| G NE APARTMENT DIRECT AIR | 0.370495 |
| G N1 APARTMENT DIRECT AIR | 0.318347 |
| G N2 APARTMENT DIRECT AIR | 0.318025 |
| G S1 APARTMENT DIRECT AIR | 0.331986 |
| G S2 APARTMENT DIRECT AIR | 0.334741 |
| M SW APARTMENT DIRECT AIR | 0.835589 |
| M NW APARTMENT DIRECT AIR | 0.808232 |
| M SE APARTMENT DIRECT AIR | 0.794723 |
| M NE APARTMENT DIRECT AIR | 0.767504 |
| M N1 APARTMENT DIRECT AIR | 0.657268 |
| M N2 APARTMENT DIRECT AIR | 0.656534 |
| M S1 APARTMENT DIRECT AIR | 0.687562 |
| M S2 APARTMENT DIRECT AIR | 0.686818 |
| T SW APARTMENT DIRECT AIR | 0.457144 |
| T NW APARTMENT DIRECT AIR | 0.445881 |
| T SE APARTMENT DIRECT AIR | 0.428046 |
| T NE APARTMENT DIRECT AIR | 0.416802 |
| T N1 APARTMENT DIRECT AIR | 0.369527 |
| T N2 APARTMENT DIRECT AIR | 0.368543 |
| T S1 APARTMENT DIRECT AIR | 0.381595 |
| T S2 APARTMENT DIRECT AIR | 0.380617 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| SPLIT GSW | 0.399689 | 0.399689 | 0.399689 | 0.399689 | 0.399689 | 0.399689 | 1.00 | 1.00 | 0.399689 |
| SPLIT GNW | 0.387246 | 0.387246 | 0.387246 | 0.387246 | 0.387246 | 0.387246 | 1.00 | 1.00 | 0.387246 |
| SPLIT OFFICE | 0.458620 | 0.458620 | 0.458620 | 0.458620 | 0.458620 | 0.458620 | 1.00 | 1.00 | 0.458620 |
| SPLIT GNE | 0.370495 | 0.370495 | 0.370495 | 0.370495 | 0.370495 | 0.370495 | 1.00 | 1.000000 | 0.370495 |
| SPLIT GN1 | 0.318347 | 0.318347 | 0.318347 | 0.318347 | 0.318347 | 0.318347 | 1.00 | 1.00 | 0.318347 |
| SPLIT GN2 | 0.318025 | 0.318025 | 0.318025 | 0.318025 | 0.318025 | 0.318025 | 1.00 | 1.00 | 0.318025 |
| SPLIT GS1 | 0.331986 | 0.331986 | 0.331986 | 0.331986 | 0.331986 | 0.331986 | 1.00 | 1.000000 | 0.331986 |
| SPLIT GS2 | 0.334741 | 0.334741 | 0.334741 | 0.334741 | 0.334741 | 0.334741 | 1.00 | 1.00 | 0.334741 |
| SPLIT MSW | 0.835589 | 0.835589 | 0.835589 | 0.835589 | 0.835589 | 0.835589 | 1.00 | 1.000000 | 0.835589 |
| SPLIT MNW | 0.808232 | 0.808232 | 0.808232 | 0.808232 | 0.808232 | 0.808232 | 1.00 | 1.00 | 0.808232 |
| SPLIT MSE | 0.794723 | 0.794723 | 0.794723 | 0.794723 | 0.794723 | 0.794723 | 1.00 | 1.00 | 0.794723 |
| SPLIT MNE | 0.767504 | 0.767504 | 0.767504 | 0.767504 | 0.767504 | 0.767504 | 1.00 | 1.00 | 0.767504 |
| SPLIT MN1 | 0.657268 | 0.657268 | 0.657268 | 0.657268 | 0.657268 | 0.657268 | 1.00 | 1.00 | 0.657268 |
| SPLIT MN2 | 0.656534 | 0.656534 | 0.656534 | 0.656534 | 0.656534 | 0.656534 | 1.00 | 1.00 | 0.656534 |
| SPLIT MS1 | 0.687562 | 0.687562 | 0.687562 | 0.687562 | 0.687562 | 0.687562 | 1.00 | 1.00 | 0.687562 |
| SPLIT MS2 | 0.686818 | 0.686818 | 0.686818 | 0.686818 | 0.686818 | 0.686818 | 1.00 | 1.00 | 0.686818 |
| SPLIT TSW | 0.457144 | 0.457144 | 0.457144 | 0.457144 | 0.457144 | 0.457144 | 1.00 | 1.00 | 0.457144 |
| SPLIT TNW | 0.445881 | 0.445881 | 0.445881 | 0.445881 | 0.445881 | 0.445881 | 1.00 | 1.00 | 0.445881 |
| SPLIT TSE | 0.428046 | 0.428046 | 0.428046 | 0.428046 | 0.428046 | 0.428046 | 1.00 | 1.00 | 0.428046 |
| SPLIT TNE | 0.416802 | 0.416802 | 0.416802 | 0.416802 | 0.416802 | 0.416802 | 1.00 | 1.00 | 0.416802 |
| SPLIT TN1 | 0.369527 | 0.369527 | 0.369527 | 0.369527 | 0.369527 | 0.369527 | 1.00 | 1.00 | 0.369527 |
| SPLIT TN2 | 0.368543 | 0.368543 | 0.368543 | 0.368543 | 0.368543 | 0.368543 | 1.00 | 1.00 | 0.368543 |
| SPLIT TS1 | 0.381595 | 0.381595 | 0.381595 | 0.381595 | 0.381595 | 0.381595 | 1.00 | 1.00 | 0.381595 |
| SPLIT TS2 | 0.380617 | 0.380617 | 0.380617 | 0.380617 | 0.380617 | 0.380617 | 1.00 | 1.00 | 0.380617 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| SPLIT GSW_OA_CONTROLLER | 0.399689 | 0.025955 |
| SPLIT GNW_OA_CONTROLLER | 0.387246 | 0.025955 |
| SPLIT OFFICE_OA_CONTROLLER | 0.458620 | 0.038106 |
| SPLIT GNE_OA_CONTROLLER | 0.370495 | 0.025955 |
| SPLIT GN1_OA_CONTROLLER | 0.318347 | 0.025955 |
| SPLIT GN2_OA_CONTROLLER | 0.318025 | 0.025955 |
| SPLIT GS1_OA_CONTROLLER | 0.331986 | 0.025955 |
| SPLIT GS2_OA_CONTROLLER | 0.334741 | 0.025955 |
| SPLIT MSW_OA_CONTROLLER | 0.835589 | 0.051909 |
| SPLIT MNW_OA_CONTROLLER | 0.808232 | 0.051909 |
| SPLIT MSE_OA_CONTROLLER | 0.794723 | 0.051909 |
| SPLIT MNE_OA_CONTROLLER | 0.767504 | 0.051909 |
| SPLIT MN1_OA_CONTROLLER | 0.657268 | 0.051909 |
| SPLIT MN2_OA_CONTROLLER | 0.656534 | 0.051909 |
| SPLIT MS1_OA_CONTROLLER | 0.687562 | 0.051909 |
| SPLIT MS2_OA_CONTROLLER | 0.686818 | 0.051909 |
| SPLIT TSW_OA_CONTROLLER | 0.457144 | 0.025955 |
| SPLIT TNW_OA_CONTROLLER | 0.445881 | 0.025955 |
| SPLIT TSE_OA_CONTROLLER | 0.428046 | 0.025955 |
| SPLIT TNE_OA_CONTROLLER | 0.416802 | 0.025955 |
| SPLIT TN1_OA_CONTROLLER | 0.369527 | 0.025955 |
| SPLIT TN2_OA_CONTROLLER | 0.368543 | 0.025955 |
| SPLIT TS1_OA_CONTROLLER | 0.381595 | 0.025955 |
| SPLIT TS2_OA_CONTROLLER | 0.380617 | 0.025955 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | User-Specified Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| SPLIT GSW_UNITARY_PACKAGE_DX | 0.399689 | 0.399689 | 0.399689 | 0.399689 | 7395.65 | 4955.09 | 40.00 | 7395.65 | 1.00 |
| SPLIT GNW_UNITARY_PACKAGE_DX | 0.387246 | 0.387246 | 0.387246 | 0.387246 | 7171.63 | 4804.99 | 40.00 | 7171.63 | 1.00 |
| SPLIT OFFICE_UNITARY_PACKAGE_DX | 0.458620 | 0.458620 | 0.458620 | 0.458620 | 8322.19 | 5575.87 | 40.00 | 8322.19 | 1.00 |
| SPLIT GNE_UNITARY_PACKAGE_DX | 0.370495 | 0.370495 | 0.370495 | 0.370495 | 6893.72 | 4618.79 | 40.00 | 6893.72 | 1.00 |
| SPLIT GN1_UNITARY_PACKAGE_DX | 0.318347 | 0.318347 | 0.318347 | 0.318347 | 6014.87 | 4029.96 | 40.00 | 6014.87 | 1.00 |
| SPLIT GN2_UNITARY_PACKAGE_DX | 0.318025 | 0.318025 | 0.318025 | 0.318025 | 6009.52 | 4026.38 | 40.00 | 6009.52 | 1.00 |
| SPLIT GS1_UNITARY_PACKAGE_DX | 0.331986 | 0.331986 | 0.331986 | 0.331986 | 6269.50 | 4200.56 | 40.00 | 6269.50 | 1.00 |
| SPLIT GS2_UNITARY_PACKAGE_DX | 0.334741 | 0.334741 | 0.334741 | 0.334741 | 6315.17 | 4231.16 | 40.00 | 6315.17 | 1.00 |
| SPLIT MSW_UNITARY_PACKAGE_DX | 0.835589 | 0.835589 | 0.835589 | 0.835589 | 15426.35 | 10335.65 | 40.00 | 15426.35 | 1.00 |
| SPLIT MNW_UNITARY_PACKAGE_DX | 0.808232 | 0.808232 | 0.808232 | 0.808232 | 14939.32 | 10009.34 | 40.00 | 14939.32 | 1.00 |
| SPLIT MSE_UNITARY_PACKAGE_DX | 0.794723 | 0.794723 | 0.794723 | 0.794723 | 14751.62 | 9883.59 | 40.00 | 14751.62 | 1.00 |
| SPLIT MNE_UNITARY_PACKAGE_DX | 0.767504 | 0.767504 | 0.767504 | 0.767504 | 14263.49 | 9556.54 | 40.00 | 14263.49 | 1.00 |
| SPLIT MN1_UNITARY_PACKAGE_DX | 0.657268 | 0.657268 | 0.657268 | 0.657268 | 12398.66 | 8307.10 | 40.00 | 12398.66 | 1.00 |
| SPLIT MN2_UNITARY_PACKAGE_DX | 0.656534 | 0.656534 | 0.656534 | 0.656534 | 12386.47 | 8298.94 | 40.00 | 12386.47 | 1.00 |
| SPLIT MS1_UNITARY_PACKAGE_DX | 0.687562 | 0.687562 | 0.687562 | 0.687562 | 12953.64 | 8678.94 | 40.00 | 12953.64 | 1.00 |
| SPLIT MS2_UNITARY_PACKAGE_DX | 0.686818 | 0.686818 | 0.686818 | 0.686818 | 12941.47 | 8670.79 | 40.00 | 12941.47 | 1.00 |
| SPLIT TSW_UNITARY_PACKAGE_DX | 0.457144 | 0.457144 | 0.457144 | 0.457144 | 8384.28 | 5617.47 | 40.00 | 8384.28 | 1.00 |
| SPLIT TNW_UNITARY_PACKAGE_DX | 0.445881 | 0.445881 | 0.445881 | 0.445881 | 8183.87 | 5483.19 | 40.00 | 8183.87 | 1.00 |
| SPLIT TSE_UNITARY_PACKAGE_DX | 0.428046 | 0.428046 | 0.428046 | 0.428046 | 7900.35 | 5293.24 | 40.00 | 7900.35 | 1.00 |
| SPLIT TNE_UNITARY_PACKAGE_DX | 0.416802 | 0.416802 | 0.416802 | 0.416802 | 7698.66 | 5158.10 | 40.00 | 7698.66 | 1.00 |
| SPLIT TN1_UNITARY_PACKAGE_DX | 0.369527 | 0.369527 | 0.369527 | 0.369527 | 6885.11 | 4613.02 | 40.00 | 6885.11 | 1.00 |
| SPLIT TN2_UNITARY_PACKAGE_DX | 0.368543 | 0.368543 | 0.368543 | 0.368543 | 6868.73 | 4602.05 | 40.00 | 6868.73 | 1.00 |
| SPLIT TS1_UNITARY_PACKAGE_DX | 0.381595 | 0.381595 | 0.381595 | 0.381595 | 7103.48 | 4759.33 | 40.00 | 7103.48 | 1.00 |
| SPLIT TS2_UNITARY_PACKAGE_DX | 0.380617 | 0.380617 | 0.380617 | 0.380617 | 7087.26 | 4748.47 | 40.00 | 7087.26 | 1.00 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| SPLIT GSW HP COOLING COIL | 0.399689 | 7395.65 | 0.800910 |
| SPLIT GNW HP COOLING COIL | 0.387246 | 7171.63 | 0.800626 |
| SPLIT OFFICE HP COOLING COIL | 0.458620 | 8322.19 | 0.800388 |
| SPLIT GNE HP COOLING COIL | 0.370495 | 6893.72 | 0.800085 |
| SPLIT GN1 HP COOLING COIL | 0.318347 | 6014.87 | 0.800112 |
| SPLIT GN2 HP COOLING COIL | 0.318025 | 6009.52 | 0.800073 |
| SPLIT GS1 HP COOLING COIL | 0.331986 | 6269.50 | 0.800270 |
| SPLIT GS2 HP COOLING COIL | 0.334741 | 6315.17 | 0.800594 |
| SPLIT MSW HP COOLING COIL | 0.835589 | 15426.35 | 0.800656 |
| SPLIT MNW HP COOLING COIL | 0.808232 | 14939.32 | 0.800259 |
| SPLIT MSE HP COOLING COIL | 0.794723 | 14751.62 | 0.800875 |
| SPLIT MNE HP COOLING COIL | 0.767504 | 14263.49 | 0.800482 |
| SPLIT MN1 HP COOLING COIL | 0.657268 | 12398.66 | 0.800626 |
| SPLIT MN2 HP COOLING COIL | 0.656534 | 12386.47 | 0.800583 |
| SPLIT MS1 HP COOLING COIL | 0.687562 | 12953.64 | 0.800037 |
| SPLIT MS2 HP COOLING COIL | 0.686818 | 12941.47 | 0.800991 |
| SPLIT TSW HP COOLING COIL | 0.457144 | 8384.28 | 0.800833 |
| SPLIT TNW HP COOLING COIL | 0.445881 | 8183.87 | 0.800583 |
| SPLIT TSE HP COOLING COIL | 0.428046 | 7900.35 | 0.800744 |
| SPLIT TNE HP COOLING COIL | 0.416802 | 7698.66 | 0.800493 |
| SPLIT TN1 HP COOLING COIL | 0.369527 | 6885.11 | 0.800639 |
| SPLIT TN2 HP COOLING COIL | 0.368543 | 6868.73 | 0.800546 |
| SPLIT TS1 HP COOLING COIL | 0.381595 | 7103.48 | 0.800937 |
| SPLIT TS2 HP COOLING COIL | 0.380617 | 7087.26 | 0.800844 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Heating Capacity [W] | |
| SPLIT GSW HEATING COIL | 0.399689 | 7395.65 |
| SPLIT GNW HEATING COIL | 0.387246 | 7171.63 |
| SPLIT OFFICE HEATING COIL | 0.458620 | 8322.19 |
| SPLIT GNE HEATING COIL | 0.370495 | 6893.72 |
| SPLIT GN1 HEATING COIL | 0.318347 | 6014.87 |
| SPLIT GN2 HEATING COIL | 0.318025 | 6009.52 |
| SPLIT GS1 HEATING COIL | 0.331986 | 6269.50 |
| SPLIT GS2 HEATING COIL | 0.334741 | 6315.17 |
| SPLIT MSW HEATING COIL | 0.835589 | 15426.35 |
| SPLIT MNW HEATING COIL | 0.808232 | 14939.32 |
| SPLIT MSE HEATING COIL | 0.794723 | 14751.62 |
| SPLIT MNE HEATING COIL | 0.767504 | 14263.49 |
| SPLIT MN1 HEATING COIL | 0.657268 | 12398.66 |
| SPLIT MN2 HEATING COIL | 0.656534 | 12386.47 |
| SPLIT MS1 HEATING COIL | 0.687562 | 12953.64 |
| SPLIT MS2 HEATING COIL | 0.686818 | 12941.47 |
| SPLIT TSW HEATING COIL | 0.457144 | 8384.28 |
| SPLIT TNW HEATING COIL | 0.445881 | 8183.87 |
| SPLIT TSE HEATING COIL | 0.428046 | 7900.35 |
| SPLIT TNE HEATING COIL | 0.416802 | 7698.66 |
| SPLIT TN1 HEATING COIL | 0.369527 | 6885.11 |
| SPLIT TN2 HEATING COIL | 0.368543 | 6868.73 |
| SPLIT TS1 HEATING COIL | 0.381595 | 7103.48 |
| SPLIT TS2 HEATING COIL | 0.380617 | 7087.26 |
| Design Size Nominal Capacity [W] | |
| SPLIT GSW_SUPPHEATCOIL | 7395.65 |
| SPLIT GNW_SUPPHEATCOIL | 7171.63 |
| SPLIT OFFICE_SUPPHEATCOIL | 8322.19 |
| SPLIT GNE_SUPPHEATCOIL | 6893.72 |
| SPLIT GN1_SUPPHEATCOIL | 6014.87 |
| SPLIT GN2_SUPPHEATCOIL | 6009.52 |
| SPLIT GS1_SUPPHEATCOIL | 6269.50 |
| SPLIT GS2_SUPPHEATCOIL | 6315.17 |
| SPLIT MSW_SUPPHEATCOIL | 15426.35 |
| SPLIT MNW_SUPPHEATCOIL | 14939.32 |
| SPLIT MSE_SUPPHEATCOIL | 14751.62 |
| SPLIT MNE_SUPPHEATCOIL | 14263.49 |
| SPLIT MN1_SUPPHEATCOIL | 12398.66 |
| SPLIT MN2_SUPPHEATCOIL | 12386.47 |
| SPLIT MS1_SUPPHEATCOIL | 12953.64 |
| SPLIT MS2_SUPPHEATCOIL | 12941.47 |
| SPLIT TSW_SUPPHEATCOIL | 8384.28 |
| SPLIT TNW_SUPPHEATCOIL | 8183.87 |
| SPLIT TSE_SUPPHEATCOIL | 7900.35 |
| SPLIT TNE_SUPPHEATCOIL | 7698.66 |
| SPLIT TN1_SUPPHEATCOIL | 6885.11 |
| SPLIT TN2_SUPPHEATCOIL | 6868.73 |
| SPLIT TS1_SUPPHEATCOIL | 7103.48 |
| SPLIT TS2_SUPPHEATCOIL | 7087.26 |
| Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
| SWHSYS1 | 0.000113 | 0.013615 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | |
| SWHSYS1 PUMP | 0.000113 | 14.49 |
| Use Side Design Flow Rate [m3/s] | |
| SWHSYS1 WATER HEATER | 0.000113 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| G SWALL SWA | GWINDOW1 S SWA | |
| G WWALL SWA | GWINDOW1 W SWA | |
| G NWALL NWA | GWINDOW1 N NWA | |
| G WWALL NWA | GWINDOW1 W NWA | |
| G SWALL SEA | GWINDOW1 S SEA | |
| G EWALL SEA | GWINDOW1 E SEA | |
| G NWALL NEA | GWINDOW1 N NEA | |
| G EWALL NEA | GWINDOW1 E NEA | |
| G NWALL N1A | GWINDOW1 N N1A | |
| G NWALL N2A | GWINDOW1 N N2A | |
| G SWALL S1A | GWINDOW1 S S1A | |
| G SWALL S2A | GWINDOW1 S S2A | |
| M WWALL SWA | MWINDOW1 W SWA | |
| M SWALL SWA | MWINDOW1 S SWA | |
| M NWALL NWA | MWINDOW1 N NWA | |
| M WWALL NWA | MWINDOW1 W NWA | |
| M EWALL SEA | MWINDOW1 E SEA | |
| M SWALL SEA | MWINDOW1 S SEA | |
| M NWALL NEA | MWINDOW1 N NEA | |
| M EWALL NEA | MWINDOW1 E NEA | |
| M NWALL N1A | MWINDOW1 N N1A | |
| M NWALL N2A | MWINDOW1 N N2A | |
| M SWALL S1A | MWINDOW1 S S1A | |
| M SWALL S2A | MWINDOW1 S S2A | |
| T WWALL SWA | TWINDOW1 W SWA | |
| T SWALL SWA | TWINDOW1 S SWA | |
| T NWALL NWA | TWINDOW1 N NWA | |
| T WWALL NWA | TWINDOW1 W NWA | |
| T EWALL SEA | TWINDOW1 E SEA | |
| T SWALL SEA | TWINDOW1 S SEA | |
| T NWALL NEA | TWINDOW1 N NEA | |
| T EWALL NEA | TWINDOW1 E NEA | |
| T NWALL N1A | TWINDOW1 N N1A | |
| T NWALL N2A | TWINDOW1 N N2A | |
| T SWALL S1A | TWINDOW1 S S1A | |
| T SWALL S2A | TWINDOW1 S S2A | |
| T EWALL C | TWINDOW14 | |
| G EWALL C | ENTRANCE DOOR | |
| M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 27.75 | 16.10 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | ApartmentMidRise | 0.000 | City | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Clockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 27 | 243 | 39 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | G SW APARTMENT | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 2 | G NW APARTMENT | 0.0 | 0.00 | 9.30 | 0.00 | 5.79 | 13.11 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 3 | OFFICE | 0.0 | 34.75 | 0.00 | 0.00 | 40.54 | 3.81 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 4 | G NE APARTMENT | 0.0 | 34.75 | 9.30 | 0.00 | 40.54 | 13.11 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 5 | G N1 APARTMENT | 0.0 | 11.58 | 9.30 | 0.00 | 17.37 | 13.11 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 6 | G N2 APARTMENT | 0.0 | 23.16 | 9.30 | 0.00 | 28.95 | 13.11 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 7 | G S1 APARTMENT | 0.0 | 11.58 | 0.00 | 0.00 | 17.37 | 3.81 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 8 | G S2 APARTMENT | 0.0 | 23.16 | 0.00 | 0.00 | 28.95 | 3.81 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 9 | M SW APARTMENT | 0.0 | 0.00 | 0.00 | 3.05 | 5.79 | 3.81 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 10 | M NW APARTMENT | 0.0 | 0.00 | 9.30 | 3.05 | 5.79 | 13.11 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 11 | M SE APARTMENT | 0.0 | 34.75 | 0.00 | 3.05 | 40.54 | 3.81 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 12 | M NE APARTMENT | 0.0 | 34.75 | 9.30 | 3.05 | 40.54 | 13.11 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 13 | M N1 APARTMENT | 0.0 | 11.58 | 9.30 | 3.05 | 17.37 | 13.11 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 14 | M N2 APARTMENT | 0.0 | 23.16 | 9.30 | 3.05 | 28.95 | 13.11 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 15 | M S1 APARTMENT | 0.0 | 11.58 | 0.00 | 3.05 | 17.37 | 3.81 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 16 | M S2 APARTMENT | 0.0 | 23.16 | 0.00 | 3.05 | 28.95 | 3.81 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 17 | T SW APARTMENT | 0.0 | 0.00 | 0.00 | 9.14 | 5.79 | 3.81 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 18 | T NW APARTMENT | 0.0 | 0.00 | 9.30 | 9.14 | 5.79 | 13.11 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 19 | T SE APARTMENT | 0.0 | 34.75 | 0.00 | 9.14 | 40.54 | 3.81 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 20 | T NE APARTMENT | 0.0 | 34.75 | 9.30 | 9.14 | 40.54 | 13.11 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 21 | T N1 APARTMENT | 0.0 | 11.58 | 9.30 | 9.14 | 17.37 | 13.11 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 22 | T N2 APARTMENT | 0.0 | 23.16 | 9.30 | 9.14 | 28.95 | 13.11 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 23 | T S1 APARTMENT | 0.0 | 11.58 | 0.00 | 9.14 | 17.37 | 3.81 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 24 | T S2 APARTMENT | 0.0 | 23.16 | 0.00 | 9.14 | 28.95 | 3.81 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 25 | T CORRIDOR | 0.0 | 0.00 | 7.62 | 9.14 | 23.16 | 8.46 | 10.67 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 9.14 | 12.19 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| 26 | G CORRIDOR | 0.0 | 0.00 | 7.62 | 0.00 | 23.16 | 8.46 | 1.52 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 0.00 | 3.05 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 6.90 | 3.32 | 12 | 1 | 0 | Yes |
| 27 | M CORRIDOR | 0.0 | 0.00 | 7.62 | 3.05 | 23.16 | 8.46 | 4.57 | 1 | 1 | 2 | 0.00 | 46.33 | 7.62 | 9.30 | 3.05 | 6.10 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | G SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 2 | G NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 3 | OFFICE | 88.25 | 4.7 | 18.581 | 5.382E-002 | 7.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 14.160 | No |
| 4 | G NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 5 | G N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 6 | G N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 7 | G S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 8 | G S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 9 | M SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 10 | M NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 11 | M SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 12 | M NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 13 | M N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 14 | M N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 15 | M S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 16 | M S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 17 | T SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 18 | T NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 19 | T SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 20 | T NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 21 | T N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 22 | T N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 23 | T S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 24 | T S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 5.490 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 12.160 | No |
| 25 | T CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 5.287 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.287 | No |
| 26 | G CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 5.287 | 515.392 | 0.000 | 0.000 | 0.000 | 0.000 | 520.679 | No |
| 27 | M CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 5.287 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.287 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | OCCUP_GSW | OCC_APT_SCH_WORKING_FAMILY | G SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 2 | OCCUP_GNW | OCC_APT_SCH_STAY_HOME_FAMILY | G NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 3 | OCCUP_OFFICE | OCC_OFF_W_SB_SCH | OFFICE | 88.25 | 4.7 | 4.7 | 5.382E-002 | 18.581 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
| 4 | OCCUP_GNE | OCC_APT_SCH_STAY_HOME_FAMILY | G NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 5 | OCCUP_GN1 | OCC_APT_SCH_STAY_HOME_FAMILY | G N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 6 | OCCUP_GN2 | OCC_APT_SCH_STAY_HOME_FAMILY | G N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 7 | OCCUP_GS1 | OCC_APT_SCH_WORKING_FAMILY | G S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 8 | OCCUP_GS2 | OCC_APT_SCH_WORKING_FAMILY | G S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 9 | OCCUP_MSW | OCC_APT_SCH_WORKING_FAMILY | M SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 10 | OCCUP_MNW | OCC_APT_SCH_STAY_HOME_FAMILY | M NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 11 | OCCUP_MSE | OCC_APT_SCH_WORKING_FAMILY | M SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 12 | OCCUP_MNE | OCC_APT_SCH_STAY_HOME_FAMILY | M NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 13 | OCCUP_MN1 | OCC_APT_SCH_STAY_HOME_FAMILY | M N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 14 | OCCUP_MN2 | OCC_APT_SCH_STAY_HOME_FAMILY | M N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 15 | OCCUP_MS1 | OCC_APT_SCH_WORKING_FAMILY | M S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 16 | OCCUP_MS2 | OCC_APT_SCH_WORKING_FAMILY | M S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 17 | OCCUP_TSW | OCC_APT_SCH_WORKING_FAMILY | T SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 18 | OCCUP_TNW | OCC_APT_SCH_STAY_HOME_FAMILY | T NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 19 | OCCUP_TSE | OCC_APT_SCH_WORKING_FAMILY | T SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 20 | OCCUP_TNE | OCC_APT_SCH_STAY_HOME_FAMILY | T NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 21 | OCCUP_TN1 | OCC_APT_SCH_STAY_HOME_FAMILY | T N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 22 | OCCUP_TN2 | OCC_APT_SCH_STAY_HOME_FAMILY | T N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 23 | OCCUP_TS1 | OCC_APT_SCH_WORKING_FAMILY | T S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 24 | OCCUP_TS2 | OCC_APT_SCH_WORKING_FAMILY | T S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 25 | OCCUP_T CORRIDOR | OCC_APT_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 26 | OCCUP_G CORRIDOR | OCC_APT_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 27 | OCCUP_M CORRIDOR | OCC_APT_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | LIGHTING_HARDWIRED_GSW | LTG_SCH_APARTMENT_HARDWIRED | G SW APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 2 | LIGHTING_HARDWIRED_GNW | LTG_SCH_APARTMENT_HARDWIRED | G NW APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 3 | LIGHTING_HARDWIRED_OFFICE | LTG_SCH_OFFICE | OFFICE | 88.25 | 4.7 | 660.945 | 7.490 | 139.160 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 660.945 |
| 4 | LIGHTING_HARDWIRED_GNE | LTG_SCH_APARTMENT_HARDWIRED | G NE APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 5 | LIGHTING_HARDWIRED_GN1 | LTG_SCH_APARTMENT_HARDWIRED | G N1 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 6 | LIGHTING_HARDWIRED_GN2 | LTG_SCH_APARTMENT_HARDWIRED | G N2 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 7 | LIGHTING_HARDWIRED_GS1 | LTG_SCH_APARTMENT_HARDWIRED | G S1 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 8 | LIGHTING_HARDWIRED_GS2 | LTG_SCH_APARTMENT_HARDWIRED | G S2 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 9 | LIGHTING_HARDWIRED_MSW | LTG_SCH_APARTMENT_HARDWIRED | M SW APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 10 | LIGHTING_HARDWIRED_MNW | LTG_SCH_APARTMENT_HARDWIRED | M NW APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 11 | LIGHTING_HARDWIRED_MSE | LTG_SCH_APARTMENT_HARDWIRED | M SE APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 12 | LIGHTING_HARDWIRED_MNE | LTG_SCH_APARTMENT_HARDWIRED | M NE APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 13 | LIGHTING_HARDWIRED_MN1 | LTG_SCH_APARTMENT_HARDWIRED | M N1 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 14 | LIGHTING_HARDWIRED_MN2 | LTG_SCH_APARTMENT_HARDWIRED | M N2 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 15 | LIGHTING_HARDWIRED_MS1 | LTG_SCH_APARTMENT_HARDWIRED | M S1 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 16 | LIGHTING_HARDWIRED_MS2 | LTG_SCH_APARTMENT_HARDWIRED | M S2 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 17 | LIGHTING_HARDWIRED_TSW | LTG_SCH_APARTMENT_HARDWIRED | T SW APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 18 | LIGHTING_HARDWIRED_TNW | LTG_SCH_APARTMENT_HARDWIRED | T NW APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 19 | LIGHTING_HARDWIRED_TSE | LTG_SCH_APARTMENT_HARDWIRED | T SE APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 20 | LIGHTING_HARDWIRED_TNE | LTG_SCH_APARTMENT_HARDWIRED | T NE APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 21 | LIGHTING_HARDWIRED_TN1 | LTG_SCH_APARTMENT_HARDWIRED | T N1 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 22 | LIGHTING_HARDWIRED_TN2 | LTG_SCH_APARTMENT_HARDWIRED | T N2 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 23 | LIGHTING_HARDWIRED_TS1 | LTG_SCH_APARTMENT_HARDWIRED | T S1 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 24 | LIGHTING_HARDWIRED_TS2 | LTG_SCH_APARTMENT_HARDWIRED | T S2 APARTMENT | 88.25 | 2.5 | 398.961 | 4.521 | 159.584 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 398.961 |
| 25 | LIGHTING_HARDWIRED_GC | LTG_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 410.594 | 5.287 | 98.228 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 410.594 |
| 26 | LIGHTING_HARDWIRED_MC | LTG_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 410.594 | 5.287 | 98.228 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 410.594 |
| 27 | LIGHTING_HARDWIRED_TC | LTG_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 410.594 | 5.287 | 98.228 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 410.594 |
| 28 | LIGHTING_PLUGIN_GSW | LTG_SCH_APARTMENT_PLUGIN | G SW APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 29 | LIGHTING_PLUGIN_GNW | LTG_SCH_APARTMENT_PLUGIN | G NW APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 30 | LIGHTING_PLUGIN_GNE | LTG_SCH_APARTMENT_PLUGIN | G NE APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 31 | LIGHTING_PLUGIN_GN1 | LTG_SCH_APARTMENT_PLUGIN | G N1 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 32 | LIGHTING_PLUGIN_GN2 | LTG_SCH_APARTMENT_PLUGIN | G N2 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 33 | LIGHTING_PLUGIN_GS1 | LTG_SCH_APARTMENT_PLUGIN | G S1 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 34 | LIGHTING_PLUGIN_GS2 | LTG_SCH_APARTMENT_PLUGIN | G S2 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 35 | LIGHTING_PLUGIN_MSW | LTG_SCH_APARTMENT_PLUGIN | M SW APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 36 | LIGHTING_PLUGIN_MNW | LTG_SCH_APARTMENT_PLUGIN | M NW APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 37 | LIGHTING_PLUGIN_MSE | LTG_SCH_APARTMENT_PLUGIN | M SE APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 38 | LIGHTING_PLUGIN_MNE | LTG_SCH_APARTMENT_PLUGIN | M NE APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 39 | LIGHTING_PLUGIN_MN1 | LTG_SCH_APARTMENT_PLUGIN | M N1 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 40 | LIGHTING_PLUGIN_MN2 | LTG_SCH_APARTMENT_PLUGIN | M N2 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 41 | LIGHTING_PLUGIN_MS1 | LTG_SCH_APARTMENT_PLUGIN | M S1 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 42 | LIGHTING_PLUGIN_MS2 | LTG_SCH_APARTMENT_PLUGIN | M S2 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 43 | LIGHTING_PLUGIN_TSW | LTG_SCH_APARTMENT_PLUGIN | T SW APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 44 | LIGHTING_PLUGIN_TNW | LTG_SCH_APARTMENT_PLUGIN | T NW APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 45 | LIGHTING_PLUGIN_TSE | LTG_SCH_APARTMENT_PLUGIN | T SE APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 46 | LIGHTING_PLUGIN_TNE | LTG_SCH_APARTMENT_PLUGIN | T NE APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 47 | LIGHTING_PLUGIN_TN1 | LTG_SCH_APARTMENT_PLUGIN | T N1 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 48 | LIGHTING_PLUGIN_TN2 | LTG_SCH_APARTMENT_PLUGIN | T N2 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 49 | LIGHTING_PLUGIN_TS1 | LTG_SCH_APARTMENT_PLUGIN | T S1 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| 50 | LIGHTING_PLUGIN_TS2 | LTG_SCH_APARTMENT_PLUGIN | T S2 APARTMENT | 88.25 | 2.5 | 85.491 | 0.969 | 34.197 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 85.491 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | G CORRIDOR | 77.66 | 4.2 | 38362.000 | 493.978 | 9177.512 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 0.000 | 2585.215 |
| 2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | G CORRIDOR | 77.66 | 4.2 | 1600.000 | 20.603 | 382.775 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 1187.152 | 1600.000 |
| 3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | G CORRIDOR | 77.66 | 4.2 | 63.000 | 0.811 | 15.072 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLightsFan | 3.150 | 31.500 |
| 4 | PLUG_GSW | EQP_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 5 | PLUG_GNW | EQP_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 6 | PLUG_OFFICE | EQP_OFF_SCH | OFFICE | 88.25 | 4.7 | 588.623 | 6.670 | 123.933 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 588.623 |
| 7 | PLUG_GNE | EQP_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 8 | PLUG_GN1 | EQP_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 9 | PLUG_GN2 | EQP_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 10 | PLUG_GS1 | EQP_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 11 | PLUG_GS2 | EQP_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 12 | PLUG_MSW | EQP_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 13 | PLUG_MNW | EQP_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 14 | PLUG_MSE | EQP_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 15 | PLUG_MNE | EQP_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 16 | PLUG_MN1 | EQP_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 17 | PLUG_MN2 | EQP_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 18 | PLUG_MS1 | EQP_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 19 | PLUG_MS2 | EQP_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 20 | PLUG_TSW | EQP_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 21 | PLUG_TNW | EQP_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 22 | PLUG_TSE | EQP_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 23 | PLUG_TNE | EQP_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 24 | PLUG_TN1 | EQP_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 25 | PLUG_TN2 | EQP_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 26 | PLUG_TS1 | EQP_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 27 | PLUG_TS2 | EQP_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.9460 | 53912.0 | 11.449 | 0.4600 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | G SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 2 | GWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 3 | G WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 4 | GWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 5 | G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 6 | G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 7 | G GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 8 | G CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 9 | G INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 10 | G NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 11 | GWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 12 | G WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 13 | GWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 14 | G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 15 | G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 16 | G GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 17 | G CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 18 | G INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 19 | G SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 20 | GWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 21 | G EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 22 | GWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 23 | G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 24 | iz-G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 25 | G GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 26 | G CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 27 | G INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 28 | G NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 29 | GWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 30 | G EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 31 | GWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 32 | G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 33 | iz-G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 34 | G GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 35 | G CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 36 | G INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 37 | G NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 38 | GWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 39 | G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 40 | G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 41 | iz-G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 42 | G GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 43 | G CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 44 | G INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 45 | G NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 46 | GWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 47 | G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 48 | G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 49 | iz-G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 50 | G GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 51 | G CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 52 | G INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 53 | G SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 54 | GWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 55 | G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 56 | G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 57 | iz-G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 58 | G GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 59 | G CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 60 | G INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 61 | G SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 62 | GWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 63 | G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 64 | G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 65 | iz-G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 66 | G GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 67 | G CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 68 | G INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 69 | M WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 70 | MWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 71 | M SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 72 | MWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 73 | M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 74 | M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 75 | M GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 76 | M CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 77 | M INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 78 | M NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 79 | MWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 80 | M WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 81 | MWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 82 | M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 83 | M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 84 | M GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 85 | M CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 86 | M INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 87 | M EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 88 | MWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 89 | M SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 90 | MWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 91 | M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 92 | iz-M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 93 | M GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 94 | M CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 95 | M INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 96 | M NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 97 | MWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 98 | M EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 99 | MWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 100 | M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 101 | iz-M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 102 | M GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 103 | M CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 104 | M INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 105 | M NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 106 | MWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 107 | M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 108 | M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 109 | iz-M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 110 | M GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 111 | M CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 112 | M INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 113 | M NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 114 | MWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 115 | M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 116 | M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 117 | iz-M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 118 | M GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 119 | M CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 120 | M INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 121 | M SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 122 | MWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 123 | M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 124 | M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 125 | iz-M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 126 | M GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 127 | M CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 128 | M INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 129 | M SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 130 | MWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 131 | M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 132 | M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 133 | iz-M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 134 | M GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 135 | M CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 136 | M INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 137 | T WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 138 | TWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 139 | T SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 140 | TWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 141 | T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 142 | T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 143 | T GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 144 | T ROOF SWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 145 | T INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 146 | T NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 147 | TWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 148 | T WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 149 | TWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 150 | T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 151 | T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 152 | T GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 153 | T ROOF NWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 154 | T INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 155 | T EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 156 | TWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 157 | T SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 158 | TWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 159 | T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 160 | iz-T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 161 | T GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 162 | T ROOF SEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 163 | T INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 164 | T NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 165 | TWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 166 | T EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 167 | TWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 168 | T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 169 | iz-T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 170 | T GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 171 | T ROOF NEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 172 | T INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 173 | T NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 174 | TWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 175 | T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 176 | T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 177 | iz-T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 178 | T GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 179 | T ROOF N1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 180 | T INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 181 | T NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 182 | TWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 183 | T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 184 | T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 185 | iz-T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 186 | T GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 187 | T ROOF N2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 188 | T INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 189 | T SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 190 | TWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 191 | T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 192 | T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 193 | iz-T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 194 | T GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 195 | T ROOF S1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 196 | T INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 197 | T SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 198 | TWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 199 | T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 200 | T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 201 | iz-T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 202 | T GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 203 | T ROOF S2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 204 | T INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 205 | T WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 206 | T EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 207 | TWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 208 | iz-T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 209 | iz-T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 210 | iz-T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 211 | iz-T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 212 | iz-T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 213 | iz-T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 214 | iz-T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 215 | iz-T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 216 | T FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 217 | T ROOF C | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 218 | G WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 219 | G EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 220 | ENTRANCE DOOR | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 1 | No | No |
| 221 | iz-G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 222 | iz-G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 223 | iz-G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 224 | iz-G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 225 | iz-G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 226 | iz-G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 227 | iz-G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 228 | iz-G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 229 | G FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 230 | G CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 231 | M WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 4 | No | No |
| 232 | M EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 233 | MWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 234 | iz-M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 235 | iz-M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 236 | iz-M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 237 | iz-M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 238 | iz-M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 239 | iz-M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 240 | iz-M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 241 | iz-M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 242 | M FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 243 | M CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | INFIL_GSW | INF_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | INFIL_GNW | INF_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | INFIL_OFFICE | INF_OFF_SCH | OFFICE | 88.25 | 4.7 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | INFIL_GNE | INF_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | INFIL_GN1 | INF_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | INFIL_GN2 | INF_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | INFIL_GS1 | INF_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | INFIL_GS2 | INF_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | INFIL_MSW | INF_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | INFIL_MNW | INF_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | INFIL_MSE | INF_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | INFIL_MNE | INF_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 2.563E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | INFIL_MN1 | INF_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | INFIL_MN2 | INF_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | INFIL_MS1 | INF_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | INFIL_MS2 | INF_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 2.563E-004 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | INFIL_SW | INF_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 1.022E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | INFIL_NW | INF_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 1.022E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | INFIL_SE | INF_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 1.022E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | INFIL_NE | INF_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 1.500E-002 | 1.700E-004 | 1.022E-004 | 0.201 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | INFIL_TN1 | INF_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 7.323E-005 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | INFIL_TN2 | INF_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 7.323E-005 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | INFIL_TS1 | INF_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 7.323E-005 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | INFIL_TS2 | INF_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 9.048E-003 | 1.025E-004 | 7.323E-005 | 0.121 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | INFIL_GC | INF_COR_SCH | G CORRIDOR | 77.66 | 4.2 | 2.619E-003 | 3.372E-005 | 2.563E-004 | 3.983E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | DOOR_INFIL_GC | INFIL_DOOR_OPENING_SCH | G CORRIDOR | 77.66 | 4.2 | 0.521 | 6.703E-003 | 5.094E-002 | 7.917 | 1.000 | 0.000 | 0.000 | 0.000 |
| 27 | INFIL_MC | INF_COR_SCH | M CORRIDOR | 77.66 | 4.2 | 2.619E-003 | 3.372E-005 | 2.563E-004 | 3.983E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | INFIL_TC | INF_COR_SCH | T CORRIDOR | 77.66 | 4.2 | 2.619E-003 | 3.372E-005 | 2.980E-005 | 3.983E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | G SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | G NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | G NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | G N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | G N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | G S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | G S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | M SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | M NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | M SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | M NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | M N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | M N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | M S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | M S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | T SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | T NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | T SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | T NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | T N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | T N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 22 | T S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 23 | T S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | G SW APARTMENT | Mixing/Well-Stirred |
| 2 | G NW APARTMENT | Mixing/Well-Stirred |
| 3 | OFFICE | Mixing/Well-Stirred |
| 4 | G NE APARTMENT | Mixing/Well-Stirred |
| 5 | G N1 APARTMENT | Mixing/Well-Stirred |
| 6 | G N2 APARTMENT | Mixing/Well-Stirred |
| 7 | G S1 APARTMENT | Mixing/Well-Stirred |
| 8 | G S2 APARTMENT | Mixing/Well-Stirred |
| 9 | M SW APARTMENT | Mixing/Well-Stirred |
| 10 | M NW APARTMENT | Mixing/Well-Stirred |
| 11 | M SE APARTMENT | Mixing/Well-Stirred |
| 12 | M NE APARTMENT | Mixing/Well-Stirred |
| 13 | M N1 APARTMENT | Mixing/Well-Stirred |
| 14 | M N2 APARTMENT | Mixing/Well-Stirred |
| 15 | M S1 APARTMENT | Mixing/Well-Stirred |
| 16 | M S2 APARTMENT | Mixing/Well-Stirred |
| 17 | T SW APARTMENT | Mixing/Well-Stirred |
| 18 | T NW APARTMENT | Mixing/Well-Stirred |
| 19 | T SE APARTMENT | Mixing/Well-Stirred |
| 20 | T NE APARTMENT | Mixing/Well-Stirred |
| 21 | T N1 APARTMENT | Mixing/Well-Stirred |
| 22 | T N2 APARTMENT | Mixing/Well-Stirred |
| 23 | T S1 APARTMENT | Mixing/Well-Stirred |
| 24 | T S2 APARTMENT | Mixing/Well-Stirred |
| 25 | T CORRIDOR | Mixing/Well-Stirred |
| 26 | G CORRIDOR | Mixing/Well-Stirred |
| 27 | M CORRIDOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | G SW APARTMENT | Cooling | 4699.67011 | 5639.60413 | 0.33307 | 0.39969 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 2 | G SW APARTMENT | Heating | 169.99132 | 203.98958 | 7.32840E-003 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 3 | G NW APARTMENT | Cooling | 4556.56439 | 5467.87726 | 0.32271 | 0.38725 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 4 | G NW APARTMENT | Heating | 11.04586 | 13.25503 | 4.76193E-004 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 5 | OFFICE | Cooling | 5317.30173 | 6380.76207 | 0.38218 | 0.45862 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 37.46500 | 1.07727E-002 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 6 | OFFICE | Heating | 434.21154 | 521.05384 | 1.87190E-002 | 3.81060E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 12.70000 | 9.15345E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 7 | G NE APARTMENT | Cooling | 4363.98897 | 5236.78677 | 0.30875 | 0.37049 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 8 | G NE APARTMENT | Heating | 7.95972 | 9.55166 | 3.43147E-004 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 9 | G N1 APARTMENT | Cooling | 3764.02591 | 4516.83109 | 0.26529 | 0.31835 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 10 | G N1 APARTMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 2.59546E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 | |
| 11 | G N2 APARTMENT | Cooling | 3760.29581 | 4512.35497 | 0.26502 | 0.31803 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 12 | G N2 APARTMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 2.59546E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 | |
| 13 | G S1 APARTMENT | Cooling | 3921.94812 | 4706.33775 | 0.27666 | 0.33199 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 14 | G S1 APARTMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 2.59546E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 | |
| 15 | G S2 APARTMENT | Cooling | 3953.63073 | 4744.35688 | 0.27895 | 0.33474 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 16 | G S2 APARTMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 2.59546E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 | |
| 17 | M SW APARTMENT | Cooling | 9818.21366 | 11781.85639 | 0.69632 | 0.83559 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 18 | M SW APARTMENT | Heating | 749.20930 | 899.05116 | 3.22987E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 19 | M NW APARTMENT | Cooling | 9502.70569 | 11403.24683 | 0.67353 | 0.80823 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 20 | M NW APARTMENT | Heating | 465.50095 | 558.60114 | 2.00683E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 21 | M SE APARTMENT | Cooling | 9346.64411 | 11215.97293 | 0.66227 | 0.79472 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 22 | M SE APARTMENT | Heating | 744.80859 | 893.77030 | 3.21090E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 23 | M NE APARTMENT | Cooling | 9033.31784 | 10839.98141 | 0.63959 | 0.76750 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 24 | M NE APARTMENT | Heating | 461.43734 | 553.72481 | 1.98931E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 25 | M N1 APARTMENT | Cooling | 7767.58823 | 9321.10587 | 0.54772 | 0.65727 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 26 | M N1 APARTMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 5.19091E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 | |
| 27 | M N2 APARTMENT | Cooling | 7759.05718 | 9310.86862 | 0.54711 | 0.65653 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 28 | M N2 APARTMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 5.19091E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 | |
| 29 | M S1 APARTMENT | Cooling | 8115.03118 | 9738.03742 | 0.57297 | 0.68756 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 30 | M S1 APARTMENT | Heating | 234.61625 | 281.53950 | 1.01144E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 31 | M S2 APARTMENT | Cooling | 8106.50384 | 9727.80461 | 0.57235 | 0.68682 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 32 | M S2 APARTMENT | Heating | 234.41140 | 281.29368 | 1.01056E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 33 | T SW APARTMENT | Cooling | 5366.57773 | 6439.89328 | 0.38095 | 0.45714 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 34 | T SW APARTMENT | Heating | 712.82994 | 855.39593 | 3.07304E-002 | 3.68765E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 35 | T NW APARTMENT | Cooling | 5237.17481 | 6284.60977 | 0.37157 | 0.44588 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 36 | T NW APARTMENT | Heating | 574.39386 | 689.27263 | 2.47629E-002 | 2.97154E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 37 | T SE APARTMENT | Cooling | 5030.58382 | 6036.70058 | 0.35671 | 0.42805 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 38 | T SE APARTMENT | Heating | 710.16513 | 852.19815 | 3.06155E-002 | 3.67387E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 39 | T NE APARTMENT | Cooling | 4900.43375 | 5880.52050 | 0.34733 | 0.41680 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 40 | T NE APARTMENT | Heating | 571.89987 | 686.27984 | 2.46553E-002 | 2.95864E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 41 | T N1 APARTMENT | Cooling | 4354.88783 | 5225.86539 | 0.30794 | 0.36953 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 42 | T N1 APARTMENT | Heating | 317.54553 | 381.05464 | 1.36898E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 43 | T N2 APARTMENT | Cooling | 4343.55148 | 5212.26177 | 0.30712 | 0.36854 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 44 | T N2 APARTMENT | Heating | 317.44505 | 380.93406 | 1.36855E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 45 | T S1 APARTMENT | Cooling | 4494.05131 | 5392.86157 | 0.31800 | 0.38159 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 46 | T S1 APARTMENT | Heating | 456.27391 | 547.52869 | 1.96701E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 47 | T S2 APARTMENT | Cooling | 4482.76525 | 5379.31830 | 0.31718 | 0.38062 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 39.01700 | 1.07753E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 48 | T S2 APARTMENT | Heating | 456.17004 | 547.40405 | 1.96657E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12.70000 | 9.15345E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | SPLIT GSW | Cooling | Sensible | 5907.98 | 0.39969 | 0.39969 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 2 | SPLIT GSW | Heating | Sensible | 856.96 | 2.59546E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 3 | SPLIT GNW | Cooling | Sensible | 5738.04 | 0.38725 | 0.38725 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 4 | SPLIT GNW | Heating | Sensible | 856.96 | 2.59546E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 5 | SPLIT OFFICE | Cooling | Sensible | 6814.37 | 0.45862 | 0.45862 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 6 | SPLIT OFFICE | Heating | Sensible | 1258.18 | 3.81060E-002 | 3.81060E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 7 | SPLIT GNE | Cooling | Sensible | 5509.15 | 0.37049 | 0.37049 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 8 | SPLIT GNE | Heating | Sensible | 856.96 | 2.59546E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 9 | SPLIT GN1 | Cooling | Sensible | 4796.52 | 0.31835 | 0.31835 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 10 | SPLIT GN1 | Heating | Sensible | 856.96 | 2.59546E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 11 | SPLIT GN2 | Cooling | Sensible | 4792.10 | 0.31803 | 0.31803 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 12 | SPLIT GN2 | Heating | Sensible | 856.96 | 2.59546E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 13 | SPLIT GS1 | Cooling | Sensible | 4983.32 | 0.33199 | 0.33199 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 14 | SPLIT GS1 | Heating | Sensible | 856.96 | 2.59546E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 15 | SPLIT GS2 | Cooling | Sensible | 5020.88 | 0.33474 | 0.33474 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 16 | SPLIT GS2 | Heating | Sensible | 856.96 | 2.59546E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 17 | SPLIT MSW | Cooling | Sensible | 12312.21 | 0.83559 | 0.83559 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 18 | SPLIT MSW | Heating | Sensible | 1713.92 | 5.19091E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 19 | SPLIT MNW | Cooling | Sensible | 11938.23 | 0.80823 | 0.80823 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 20 | SPLIT MNW | Heating | Sensible | 1713.92 | 5.19091E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 21 | SPLIT MSE | Cooling | Sensible | 11753.18 | 0.79472 | 0.79472 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 22 | SPLIT MSE | Heating | Sensible | 1713.92 | 5.19091E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 23 | SPLIT MNE | Cooling | Sensible | 11381.30 | 0.76750 | 0.76750 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 24 | SPLIT MNE | Heating | Sensible | 1713.92 | 5.19091E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 25 | SPLIT MN1 | Cooling | Sensible | 9875.96 | 0.65727 | 0.65727 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 26 | SPLIT MN1 | Heating | Sensible | 1713.92 | 5.19091E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 27 | SPLIT MN2 | Cooling | Sensible | 9865.89 | 0.65653 | 0.65653 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 28 | SPLIT MN2 | Heating | Sensible | 1713.92 | 5.19091E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 29 | SPLIT MS1 | Cooling | Sensible | 10289.57 | 0.68756 | 0.68756 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 30 | SPLIT MS1 | Heating | Sensible | 1713.92 | 5.19091E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 31 | SPLIT MS2 | Cooling | Sensible | 10279.42 | 0.68682 | 0.68682 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 32 | SPLIT MS2 | Heating | Sensible | 1713.92 | 5.19091E-002 | 5.19091E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 33 | SPLIT TSW | Cooling | Sensible | 6696.17 | 0.45714 | 0.45714 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 34 | SPLIT TSW | Heating | Sensible | 1106.62 | 3.68765E-002 | 3.68765E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 35 | SPLIT TNW | Cooling | Sensible | 6542.55 | 0.44588 | 0.44588 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 36 | SPLIT TNW | Heating | Sensible | 942.93 | 2.97154E-002 | 2.97154E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 37 | SPLIT TSE | Cooling | Sensible | 6298.35 | 0.42805 | 0.42805 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 38 | SPLIT TSE | Heating | Sensible | 1103.47 | 3.67387E-002 | 3.67387E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 39 | SPLIT TNE | Cooling | Sensible | 6144.47 | 0.41680 | 0.41680 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 40 | SPLIT TNE | Heating | Sensible | 939.98 | 2.95864E-002 | 2.95864E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 41 | SPLIT TN1 | Cooling | Sensible | 5498.21 | 0.36953 | 0.36953 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 42 | SPLIT TN1 | Heating | Sensible | 856.96 | 2.59546E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 43 | SPLIT TN2 | Cooling | Sensible | 5484.77 | 0.36854 | 0.36854 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 44 | SPLIT TN2 | Heating | Sensible | 856.96 | 2.59546E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 45 | SPLIT TS1 | Cooling | Sensible | 5663.15 | 0.38159 | 0.38159 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 46 | SPLIT TS1 | Heating | Sensible | 856.96 | 2.59546E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 47 | SPLIT TS2 | Cooling | Sensible | 5649.78 | 0.38062 | 0.38062 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 48 | SPLIT TS2 | Heating | Sensible | 856.96 | 2.59546E-002 | 2.59546E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 2 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 3 | Fan:OnOff | G SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 4 | Fan:OnOff | G SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 5 | HeatExchanger:AirToAir:SensibleAndLatent | G SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.39969 |
| 7 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 8 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 9 | Fan:OnOff | G NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 10 | Fan:OnOff | G NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 11 | HeatExchanger:AirToAir:SensibleAndLatent | G NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.38725 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45862 |
| 14 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 15 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 16 | Fan:OnOff | G NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 17 | Fan:OnOff | G NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 18 | HeatExchanger:AirToAir:SensibleAndLatent | G NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37049 |
| 20 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 21 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 22 | Fan:OnOff | G N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 23 | Fan:OnOff | G N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 24 | HeatExchanger:AirToAir:SensibleAndLatent | G N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 25 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.31835 |
| 26 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 27 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 28 | Fan:OnOff | G N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 29 | Fan:OnOff | G N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 30 | HeatExchanger:AirToAir:SensibleAndLatent | G N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 31 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.31803 |
| 32 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 33 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 34 | Fan:OnOff | G S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 35 | Fan:OnOff | G S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 36 | HeatExchanger:AirToAir:SensibleAndLatent | G S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 37 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33199 |
| 38 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 39 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 40 | Fan:OnOff | G S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 41 | Fan:OnOff | G S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 42 | HeatExchanger:AirToAir:SensibleAndLatent | G S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 43 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33474 |
| 44 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 45 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 46 | Fan:OnOff | M SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 47 | Fan:OnOff | M SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 48 | HeatExchanger:AirToAir:SensibleAndLatent | M SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 49 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83559 |
| 50 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 51 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 52 | Fan:OnOff | M NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 53 | Fan:OnOff | M NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 54 | HeatExchanger:AirToAir:SensibleAndLatent | M NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 55 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.80823 |
| 56 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 57 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 58 | Fan:OnOff | M SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 59 | Fan:OnOff | M SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 60 | HeatExchanger:AirToAir:SensibleAndLatent | M SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.79472 |
| 62 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 63 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 64 | Fan:OnOff | M NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 65 | Fan:OnOff | M NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 66 | HeatExchanger:AirToAir:SensibleAndLatent | M NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 67 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.76750 |
| 68 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 69 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 70 | Fan:OnOff | M N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 71 | Fan:OnOff | M N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 72 | HeatExchanger:AirToAir:SensibleAndLatent | M N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 73 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.65727 |
| 74 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 75 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 76 | Fan:OnOff | M N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 77 | Fan:OnOff | M N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 78 | HeatExchanger:AirToAir:SensibleAndLatent | M N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 79 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.65653 |
| 80 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 81 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 82 | Fan:OnOff | M S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 83 | Fan:OnOff | M S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 84 | HeatExchanger:AirToAir:SensibleAndLatent | M S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 85 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.68756 |
| 86 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 87 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 88 | Fan:OnOff | M S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 89 | Fan:OnOff | M S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 90 | HeatExchanger:AirToAir:SensibleAndLatent | M S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 91 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.68682 |
| 92 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 93 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 94 | Fan:OnOff | T SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 95 | Fan:OnOff | T SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 96 | HeatExchanger:AirToAir:SensibleAndLatent | T SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45714 |
| 98 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 99 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 100 | Fan:OnOff | T NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 101 | Fan:OnOff | T NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 102 | HeatExchanger:AirToAir:SensibleAndLatent | T NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 103 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44588 |
| 104 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 105 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 106 | Fan:OnOff | T SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 107 | Fan:OnOff | T SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 108 | HeatExchanger:AirToAir:SensibleAndLatent | T SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 109 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.42805 |
| 110 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 111 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 112 | Fan:OnOff | T NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 113 | Fan:OnOff | T NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 114 | HeatExchanger:AirToAir:SensibleAndLatent | T NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 115 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.41680 |
| 116 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 117 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 118 | Fan:OnOff | T N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 119 | Fan:OnOff | T N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 120 | HeatExchanger:AirToAir:SensibleAndLatent | T N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 121 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.36953 |
| 122 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 123 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 124 | Fan:OnOff | T N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 125 | Fan:OnOff | T N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 126 | HeatExchanger:AirToAir:SensibleAndLatent | T N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.36854 |
| 128 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 129 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 130 | Fan:OnOff | T S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 131 | Fan:OnOff | T S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 132 | HeatExchanger:AirToAir:SensibleAndLatent | T S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 133 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.38159 |
| 134 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 135 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 136 | Fan:OnOff | T S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 137 | Fan:OnOff | T S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 138 | HeatExchanger:AirToAir:SensibleAndLatent | T S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 139 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.38062 |
| 140 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.39969 |
| 141 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.39969 |
| 142 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.39969 |
| 143 | AirLoopHVAC | SPLIT GSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.39969 |
| 144 | AirLoopHVAC | SPLIT GSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.39969 |
| 145 | AirLoopHVAC | SPLIT GSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.39969 |
| 146 | AirLoopHVAC | SPLIT GSW | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | SPLIT GSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.38725 |
| 149 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.38725 |
| 150 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.38725 |
| 151 | AirLoopHVAC | SPLIT GNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.38725 |
| 152 | AirLoopHVAC | SPLIT GNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.38725 |
| 153 | AirLoopHVAC | SPLIT GNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.38725 |
| 154 | AirLoopHVAC | SPLIT GNW | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | SPLIT GNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45862 |
| 157 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45862 |
| 158 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45862 |
| 159 | AirLoopHVAC | SPLIT OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45862 |
| 160 | AirLoopHVAC | SPLIT OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45862 |
| 161 | AirLoopHVAC | SPLIT OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.45862 |
| 162 | AirLoopHVAC | SPLIT OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | SPLIT OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37049 |
| 165 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37049 |
| 166 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37049 |
| 167 | AirLoopHVAC | SPLIT GNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37049 |
| 168 | AirLoopHVAC | SPLIT GNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37049 |
| 169 | AirLoopHVAC | SPLIT GNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.37049 |
| 170 | AirLoopHVAC | SPLIT GNE | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | SPLIT GNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.31835 |
| 173 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.31835 |
| 174 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.31835 |
| 175 | AirLoopHVAC | SPLIT GN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.31835 |
| 176 | AirLoopHVAC | SPLIT GN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.31835 |
| 177 | AirLoopHVAC | SPLIT GN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.31835 |
| 178 | AirLoopHVAC | SPLIT GN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 179 | AirLoopHVAC | SPLIT GN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 180 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.31803 |
| 181 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.31803 |
| 182 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.31803 |
| 183 | AirLoopHVAC | SPLIT GN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.31803 |
| 184 | AirLoopHVAC | SPLIT GN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.31803 |
| 185 | AirLoopHVAC | SPLIT GN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.31803 |
| 186 | AirLoopHVAC | SPLIT GN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 187 | AirLoopHVAC | SPLIT GN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 188 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33199 |
| 189 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33199 |
| 190 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33199 |
| 191 | AirLoopHVAC | SPLIT GS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33199 |
| 192 | AirLoopHVAC | SPLIT GS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33199 |
| 193 | AirLoopHVAC | SPLIT GS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33199 |
| 194 | AirLoopHVAC | SPLIT GS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 195 | AirLoopHVAC | SPLIT GS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 196 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33474 |
| 197 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33474 |
| 198 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33474 |
| 199 | AirLoopHVAC | SPLIT GS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33474 |
| 200 | AirLoopHVAC | SPLIT GS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33474 |
| 201 | AirLoopHVAC | SPLIT GS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33474 |
| 202 | AirLoopHVAC | SPLIT GS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 203 | AirLoopHVAC | SPLIT GS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 204 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.83559 |
| 205 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.83559 |
| 206 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.83559 |
| 207 | AirLoopHVAC | SPLIT MSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.83559 |
| 208 | AirLoopHVAC | SPLIT MSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.83559 |
| 209 | AirLoopHVAC | SPLIT MSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.83559 |
| 210 | AirLoopHVAC | SPLIT MSW | User Heating Air Flow Ratio [] | 1.00000 |
| 211 | AirLoopHVAC | SPLIT MSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 212 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.80823 |
| 213 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.80823 |
| 214 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.80823 |
| 215 | AirLoopHVAC | SPLIT MNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.80823 |
| 216 | AirLoopHVAC | SPLIT MNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.80823 |
| 217 | AirLoopHVAC | SPLIT MNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.80823 |
| 218 | AirLoopHVAC | SPLIT MNW | User Heating Air Flow Ratio [] | 1.00000 |
| 219 | AirLoopHVAC | SPLIT MNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 220 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.79472 |
| 221 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.79472 |
| 222 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.79472 |
| 223 | AirLoopHVAC | SPLIT MSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.79472 |
| 224 | AirLoopHVAC | SPLIT MSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.79472 |
| 225 | AirLoopHVAC | SPLIT MSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.79472 |
| 226 | AirLoopHVAC | SPLIT MSE | User Heating Air Flow Ratio [] | 1.00000 |
| 227 | AirLoopHVAC | SPLIT MSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 228 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.76750 |
| 229 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.76750 |
| 230 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.76750 |
| 231 | AirLoopHVAC | SPLIT MNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.76750 |
| 232 | AirLoopHVAC | SPLIT MNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.76750 |
| 233 | AirLoopHVAC | SPLIT MNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.76750 |
| 234 | AirLoopHVAC | SPLIT MNE | User Heating Air Flow Ratio [] | 1.00000 |
| 235 | AirLoopHVAC | SPLIT MNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 236 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.65727 |
| 237 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.65727 |
| 238 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.65727 |
| 239 | AirLoopHVAC | SPLIT MN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.65727 |
| 240 | AirLoopHVAC | SPLIT MN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.65727 |
| 241 | AirLoopHVAC | SPLIT MN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.65727 |
| 242 | AirLoopHVAC | SPLIT MN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 243 | AirLoopHVAC | SPLIT MN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 244 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.65653 |
| 245 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.65653 |
| 246 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.65653 |
| 247 | AirLoopHVAC | SPLIT MN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.65653 |
| 248 | AirLoopHVAC | SPLIT MN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.65653 |
| 249 | AirLoopHVAC | SPLIT MN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.65653 |
| 250 | AirLoopHVAC | SPLIT MN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 251 | AirLoopHVAC | SPLIT MN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 252 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.68756 |
| 253 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.68756 |
| 254 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.68756 |
| 255 | AirLoopHVAC | SPLIT MS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.68756 |
| 256 | AirLoopHVAC | SPLIT MS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.68756 |
| 257 | AirLoopHVAC | SPLIT MS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.68756 |
| 258 | AirLoopHVAC | SPLIT MS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 259 | AirLoopHVAC | SPLIT MS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 260 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.68682 |
| 261 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.68682 |
| 262 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.68682 |
| 263 | AirLoopHVAC | SPLIT MS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.68682 |
| 264 | AirLoopHVAC | SPLIT MS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.68682 |
| 265 | AirLoopHVAC | SPLIT MS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.68682 |
| 266 | AirLoopHVAC | SPLIT MS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 267 | AirLoopHVAC | SPLIT MS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 268 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45714 |
| 269 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45714 |
| 270 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45714 |
| 271 | AirLoopHVAC | SPLIT TSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45714 |
| 272 | AirLoopHVAC | SPLIT TSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45714 |
| 273 | AirLoopHVAC | SPLIT TSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.45714 |
| 274 | AirLoopHVAC | SPLIT TSW | User Heating Air Flow Ratio [] | 1.00000 |
| 275 | AirLoopHVAC | SPLIT TSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 276 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44588 |
| 277 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44588 |
| 278 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44588 |
| 279 | AirLoopHVAC | SPLIT TNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44588 |
| 280 | AirLoopHVAC | SPLIT TNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44588 |
| 281 | AirLoopHVAC | SPLIT TNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.44588 |
| 282 | AirLoopHVAC | SPLIT TNW | User Heating Air Flow Ratio [] | 1.00000 |
| 283 | AirLoopHVAC | SPLIT TNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 284 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.42805 |
| 285 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.42805 |
| 286 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.42805 |
| 287 | AirLoopHVAC | SPLIT TSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.42805 |
| 288 | AirLoopHVAC | SPLIT TSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.42805 |
| 289 | AirLoopHVAC | SPLIT TSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.42805 |
| 290 | AirLoopHVAC | SPLIT TSE | User Heating Air Flow Ratio [] | 1.00000 |
| 291 | AirLoopHVAC | SPLIT TSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 292 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.41680 |
| 293 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.41680 |
| 294 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.41680 |
| 295 | AirLoopHVAC | SPLIT TNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.41680 |
| 296 | AirLoopHVAC | SPLIT TNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.41680 |
| 297 | AirLoopHVAC | SPLIT TNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.41680 |
| 298 | AirLoopHVAC | SPLIT TNE | User Heating Air Flow Ratio [] | 1.00000 |
| 299 | AirLoopHVAC | SPLIT TNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 300 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.36953 |
| 301 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.36953 |
| 302 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.36953 |
| 303 | AirLoopHVAC | SPLIT TN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.36953 |
| 304 | AirLoopHVAC | SPLIT TN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.36953 |
| 305 | AirLoopHVAC | SPLIT TN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.36953 |
| 306 | AirLoopHVAC | SPLIT TN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 307 | AirLoopHVAC | SPLIT TN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 308 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.36854 |
| 309 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.36854 |
| 310 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.36854 |
| 311 | AirLoopHVAC | SPLIT TN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.36854 |
| 312 | AirLoopHVAC | SPLIT TN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.36854 |
| 313 | AirLoopHVAC | SPLIT TN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.36854 |
| 314 | AirLoopHVAC | SPLIT TN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 315 | AirLoopHVAC | SPLIT TN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 316 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.38159 |
| 317 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.38159 |
| 318 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.38159 |
| 319 | AirLoopHVAC | SPLIT TS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.38159 |
| 320 | AirLoopHVAC | SPLIT TS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.38159 |
| 321 | AirLoopHVAC | SPLIT TS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.38159 |
| 322 | AirLoopHVAC | SPLIT TS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 323 | AirLoopHVAC | SPLIT TS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 324 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.38062 |
| 325 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.38062 |
| 326 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.38062 |
| 327 | AirLoopHVAC | SPLIT TS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.38062 |
| 328 | AirLoopHVAC | SPLIT TS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.38062 |
| 329 | AirLoopHVAC | SPLIT TS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.38062 |
| 330 | AirLoopHVAC | SPLIT TS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 331 | AirLoopHVAC | SPLIT TS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 332 | AirLoopHVAC | SPLIT GSW | Design Supply Air Flow Rate [m3/s] | 0.39969 |
| 333 | AirLoopHVAC | SPLIT GNW | Design Supply Air Flow Rate [m3/s] | 0.38725 |
| 334 | AirLoopHVAC | SPLIT OFFICE | Design Supply Air Flow Rate [m3/s] | 0.45862 |
| 335 | AirLoopHVAC | SPLIT GNE | Design Supply Air Flow Rate [m3/s] | 0.37049 |
| 336 | AirLoopHVAC | SPLIT GN1 | Design Supply Air Flow Rate [m3/s] | 0.31835 |
| 337 | AirLoopHVAC | SPLIT GN2 | Design Supply Air Flow Rate [m3/s] | 0.31803 |
| 338 | AirLoopHVAC | SPLIT GS1 | Design Supply Air Flow Rate [m3/s] | 0.33199 |
| 339 | AirLoopHVAC | SPLIT GS2 | Design Supply Air Flow Rate [m3/s] | 0.33474 |
| 340 | AirLoopHVAC | SPLIT MSW | Design Supply Air Flow Rate [m3/s] | 0.83559 |
| 341 | AirLoopHVAC | SPLIT MNW | Design Supply Air Flow Rate [m3/s] | 0.80823 |
| 342 | AirLoopHVAC | SPLIT MSE | Design Supply Air Flow Rate [m3/s] | 0.79472 |
| 343 | AirLoopHVAC | SPLIT MNE | Design Supply Air Flow Rate [m3/s] | 0.76750 |
| 344 | AirLoopHVAC | SPLIT MN1 | Design Supply Air Flow Rate [m3/s] | 0.65727 |
| 345 | AirLoopHVAC | SPLIT MN2 | Design Supply Air Flow Rate [m3/s] | 0.65653 |
| 346 | AirLoopHVAC | SPLIT MS1 | Design Supply Air Flow Rate [m3/s] | 0.68756 |
| 347 | AirLoopHVAC | SPLIT MS2 | Design Supply Air Flow Rate [m3/s] | 0.68682 |
| 348 | AirLoopHVAC | SPLIT TSW | Design Supply Air Flow Rate [m3/s] | 0.45714 |
| 349 | AirLoopHVAC | SPLIT TNW | Design Supply Air Flow Rate [m3/s] | 0.44588 |
| 350 | AirLoopHVAC | SPLIT TSE | Design Supply Air Flow Rate [m3/s] | 0.42805 |
| 351 | AirLoopHVAC | SPLIT TNE | Design Supply Air Flow Rate [m3/s] | 0.41680 |
| 352 | AirLoopHVAC | SPLIT TN1 | Design Supply Air Flow Rate [m3/s] | 0.36953 |
| 353 | AirLoopHVAC | SPLIT TN2 | Design Supply Air Flow Rate [m3/s] | 0.36854 |
| 354 | AirLoopHVAC | SPLIT TS1 | Design Supply Air Flow Rate [m3/s] | 0.38159 |
| 355 | AirLoopHVAC | SPLIT TS2 | Design Supply Air Flow Rate [m3/s] | 0.38062 |
| 356 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.39969 |
| 357 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 358 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.39969 |
| 359 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.39969 |
| 360 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.39969 |
| 361 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.39969 |
| 362 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7395.65342 |
| 363 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4955.08779 |
| 364 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 365 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 7395.65342 |
| 366 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 367 | Fan:OnOff | SPLIT GSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.39969 |
| 368 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39969 |
| 369 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7395.65342 |
| 370 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80091 |
| 371 | Coil:Heating:DX:SingleSpeed | SPLIT GSW HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39969 |
| 372 | Coil:Heating:DX:SingleSpeed | SPLIT GSW HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 7395.65342 |
| 373 | Coil:Heating:Electric | SPLIT GSW_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7395.65342 |
| 374 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.38725 |
| 375 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 376 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.38725 |
| 377 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.38725 |
| 378 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.38725 |
| 379 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.38725 |
| 380 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7171.62999 |
| 381 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4804.99210 |
| 382 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 383 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 7171.62999 |
| 384 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 385 | Fan:OnOff | SPLIT GNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.38725 |
| 386 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38725 |
| 387 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7171.62999 |
| 388 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80063 |
| 389 | Coil:Heating:DX:SingleSpeed | SPLIT GNW HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38725 |
| 390 | Coil:Heating:DX:SingleSpeed | SPLIT GNW HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 7171.62999 |
| 391 | Coil:Heating:Electric | SPLIT GNW_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7171.62999 |
| 392 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45862 |
| 393 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.81060E-002 |
| 394 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.45862 |
| 395 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.45862 |
| 396 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.45862 |
| 397 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.45862 |
| 398 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8322.19149 |
| 399 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 5575.86830 |
| 400 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 401 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 8322.19149 |
| 402 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 403 | Fan:OnOff | SPLIT OFFICE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45862 |
| 404 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45862 |
| 405 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8322.19149 |
| 406 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80039 |
| 407 | Coil:Heating:DX:SingleSpeed | SPLIT OFFICE HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45862 |
| 408 | Coil:Heating:DX:SingleSpeed | SPLIT OFFICE HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 8322.19149 |
| 409 | Coil:Heating:Electric | SPLIT OFFICE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8322.19149 |
| 410 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37049 |
| 411 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 412 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37049 |
| 413 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37049 |
| 414 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37049 |
| 415 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37049 |
| 416 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6893.71671 |
| 417 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4618.79019 |
| 418 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 419 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 6893.71671 |
| 420 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 421 | Fan:OnOff | SPLIT GNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37049 |
| 422 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37049 |
| 423 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6893.71671 |
| 424 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80008 |
| 425 | Coil:Heating:DX:SingleSpeed | SPLIT GNE HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37049 |
| 426 | Coil:Heating:DX:SingleSpeed | SPLIT GNE HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6893.71671 |
| 427 | Coil:Heating:Electric | SPLIT GNE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6893.71671 |
| 428 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.31835 |
| 429 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 430 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.31835 |
| 431 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.31835 |
| 432 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.31835 |
| 433 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.31835 |
| 434 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6014.86572 |
| 435 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4029.96004 |
| 436 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 437 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 6014.86572 |
| 438 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 439 | Fan:OnOff | SPLIT GN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.31835 |
| 440 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.31835 |
| 441 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6014.86572 |
| 442 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80011 |
| 443 | Coil:Heating:DX:SingleSpeed | SPLIT GN1 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.31835 |
| 444 | Coil:Heating:DX:SingleSpeed | SPLIT GN1 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6014.86572 |
| 445 | Coil:Heating:Electric | SPLIT GN1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6014.86572 |
| 446 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.31803 |
| 447 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 448 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.31803 |
| 449 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.31803 |
| 450 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.31803 |
| 451 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.31803 |
| 452 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6009.51764 |
| 453 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4026.37682 |
| 454 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 455 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 6009.51764 |
| 456 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 457 | Fan:OnOff | SPLIT GN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.31803 |
| 458 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.31803 |
| 459 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6009.51764 |
| 460 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80007 |
| 461 | Coil:Heating:DX:SingleSpeed | SPLIT GN2 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.31803 |
| 462 | Coil:Heating:DX:SingleSpeed | SPLIT GN2 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6009.51764 |
| 463 | Coil:Heating:Electric | SPLIT GN2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6009.51764 |
| 464 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33199 |
| 465 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 466 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33199 |
| 467 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33199 |
| 468 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33199 |
| 469 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33199 |
| 470 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6269.49668 |
| 471 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4200.56278 |
| 472 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 473 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 6269.49668 |
| 474 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 475 | Fan:OnOff | SPLIT GS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33199 |
| 476 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33199 |
| 477 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6269.49668 |
| 478 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80027 |
| 479 | Coil:Heating:DX:SingleSpeed | SPLIT GS1 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33199 |
| 480 | Coil:Heating:DX:SingleSpeed | SPLIT GS1 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6269.49668 |
| 481 | Coil:Heating:Electric | SPLIT GS1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6269.49668 |
| 482 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33474 |
| 483 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 484 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33474 |
| 485 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33474 |
| 486 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33474 |
| 487 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33474 |
| 488 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6315.17083 |
| 489 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4231.16446 |
| 490 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 491 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 6315.17083 |
| 492 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 493 | Fan:OnOff | SPLIT GS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33474 |
| 494 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33474 |
| 495 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6315.17083 |
| 496 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80059 |
| 497 | Coil:Heating:DX:SingleSpeed | SPLIT GS2 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33474 |
| 498 | Coil:Heating:DX:SingleSpeed | SPLIT GS2 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6315.17083 |
| 499 | Coil:Heating:Electric | SPLIT GS2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6315.17083 |
| 500 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.83559 |
| 501 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 502 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.83559 |
| 503 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.83559 |
| 504 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.83559 |
| 505 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83559 |
| 506 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 15426.35056 |
| 507 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10335.65488 |
| 508 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 509 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 15426.35056 |
| 510 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 511 | Fan:OnOff | SPLIT MSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.83559 |
| 512 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.83559 |
| 513 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 15426.35056 |
| 514 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 515 | Coil:Heating:DX:SingleSpeed | SPLIT MSW HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.83559 |
| 516 | Coil:Heating:DX:SingleSpeed | SPLIT MSW HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 15426.35056 |
| 517 | Coil:Heating:Electric | SPLIT MSW_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 15426.35056 |
| 518 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.80823 |
| 519 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 520 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.80823 |
| 521 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.80823 |
| 522 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.80823 |
| 523 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80823 |
| 524 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14939.32052 |
| 525 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10009.34475 |
| 526 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 527 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 14939.32052 |
| 528 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 529 | Fan:OnOff | SPLIT MNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.80823 |
| 530 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.80823 |
| 531 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14939.32052 |
| 532 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80026 |
| 533 | Coil:Heating:DX:SingleSpeed | SPLIT MNW HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.80823 |
| 534 | Coil:Heating:DX:SingleSpeed | SPLIT MNW HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 14939.32052 |
| 535 | Coil:Heating:Electric | SPLIT MNW_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14939.32052 |
| 536 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.79472 |
| 537 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 538 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.79472 |
| 539 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.79472 |
| 540 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.79472 |
| 541 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79472 |
| 542 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14751.62254 |
| 543 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9883.58710 |
| 544 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 545 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 14751.62254 |
| 546 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 547 | Fan:OnOff | SPLIT MSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.79472 |
| 548 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.79472 |
| 549 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14751.62254 |
| 550 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80087 |
| 551 | Coil:Heating:DX:SingleSpeed | SPLIT MSE HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.79472 |
| 552 | Coil:Heating:DX:SingleSpeed | SPLIT MSE HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 14751.62254 |
| 553 | Coil:Heating:Electric | SPLIT MSE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14751.62254 |
| 554 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.76750 |
| 555 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 556 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.76750 |
| 557 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.76750 |
| 558 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.76750 |
| 559 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76750 |
| 560 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14263.48990 |
| 561 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9556.53824 |
| 562 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 563 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 14263.48990 |
| 564 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 565 | Fan:OnOff | SPLIT MNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.76750 |
| 566 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.76750 |
| 567 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14263.48990 |
| 568 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80048 |
| 569 | Coil:Heating:DX:SingleSpeed | SPLIT MNE HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.76750 |
| 570 | Coil:Heating:DX:SingleSpeed | SPLIT MNE HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 14263.48990 |
| 571 | Coil:Heating:Electric | SPLIT MNE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14263.48990 |
| 572 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.65727 |
| 573 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 574 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.65727 |
| 575 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.65727 |
| 576 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.65727 |
| 577 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65727 |
| 578 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12398.66136 |
| 579 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8307.10311 |
| 580 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 581 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 12398.66136 |
| 582 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 583 | Fan:OnOff | SPLIT MN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.65727 |
| 584 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65727 |
| 585 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12398.66136 |
| 586 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80063 |
| 587 | Coil:Heating:DX:SingleSpeed | SPLIT MN1 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65727 |
| 588 | Coil:Heating:DX:SingleSpeed | SPLIT MN1 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 12398.66136 |
| 589 | Coil:Heating:Electric | SPLIT MN1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 12398.66136 |
| 590 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.65653 |
| 591 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 592 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.65653 |
| 593 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.65653 |
| 594 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.65653 |
| 595 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65653 |
| 596 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12386.47294 |
| 597 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8298.93687 |
| 598 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 599 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 12386.47294 |
| 600 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 601 | Fan:OnOff | SPLIT MN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.65653 |
| 602 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65653 |
| 603 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12386.47294 |
| 604 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80058 |
| 605 | Coil:Heating:DX:SingleSpeed | SPLIT MN2 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65653 |
| 606 | Coil:Heating:DX:SingleSpeed | SPLIT MN2 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 12386.47294 |
| 607 | Coil:Heating:Electric | SPLIT MN2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 12386.47294 |
| 608 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.68756 |
| 609 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 610 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.68756 |
| 611 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.68756 |
| 612 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.68756 |
| 613 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68756 |
| 614 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12953.64275 |
| 615 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8678.94064 |
| 616 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 617 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 12953.64275 |
| 618 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 619 | Fan:OnOff | SPLIT MS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.68756 |
| 620 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.68756 |
| 621 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12953.64275 |
| 622 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80004 |
| 623 | Coil:Heating:DX:SingleSpeed | SPLIT MS1 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.68756 |
| 624 | Coil:Heating:DX:SingleSpeed | SPLIT MS1 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 12953.64275 |
| 625 | Coil:Heating:Electric | SPLIT MS1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 12953.64275 |
| 626 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.68682 |
| 627 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 628 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.68682 |
| 629 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.68682 |
| 630 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.68682 |
| 631 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68682 |
| 632 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12941.47282 |
| 633 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8670.78679 |
| 634 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 635 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 12941.47282 |
| 636 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 637 | Fan:OnOff | SPLIT MS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.68682 |
| 638 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.68682 |
| 639 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12941.47282 |
| 640 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80099 |
| 641 | Coil:Heating:DX:SingleSpeed | SPLIT MS2 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.68682 |
| 642 | Coil:Heating:DX:SingleSpeed | SPLIT MS2 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 12941.47282 |
| 643 | Coil:Heating:Electric | SPLIT MS2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 12941.47282 |
| 644 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45714 |
| 645 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 646 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.45714 |
| 647 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.45714 |
| 648 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.45714 |
| 649 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.45714 |
| 650 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8384.28488 |
| 651 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 5617.47087 |
| 652 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 653 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 8384.28488 |
| 654 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 655 | Fan:OnOff | SPLIT TSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45714 |
| 656 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45714 |
| 657 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8384.28488 |
| 658 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80083 |
| 659 | Coil:Heating:DX:SingleSpeed | SPLIT TSW HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45714 |
| 660 | Coil:Heating:DX:SingleSpeed | SPLIT TSW HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 8384.28488 |
| 661 | Coil:Heating:Electric | SPLIT TSW_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8384.28488 |
| 662 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44588 |
| 663 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 664 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.44588 |
| 665 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.44588 |
| 666 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.44588 |
| 667 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.44588 |
| 668 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8183.87245 |
| 669 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 5483.19454 |
| 670 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 671 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 8183.87245 |
| 672 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 673 | Fan:OnOff | SPLIT TNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44588 |
| 674 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44588 |
| 675 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8183.87245 |
| 676 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80058 |
| 677 | Coil:Heating:DX:SingleSpeed | SPLIT TNW HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44588 |
| 678 | Coil:Heating:DX:SingleSpeed | SPLIT TNW HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 8183.87245 |
| 679 | Coil:Heating:Electric | SPLIT TNW_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8183.87245 |
| 680 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.42805 |
| 681 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 682 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.42805 |
| 683 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.42805 |
| 684 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.42805 |
| 685 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.42805 |
| 686 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7900.35488 |
| 687 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 5293.23777 |
| 688 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 689 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 7900.35488 |
| 690 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 691 | Fan:OnOff | SPLIT TSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.42805 |
| 692 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.42805 |
| 693 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7900.35488 |
| 694 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80074 |
| 695 | Coil:Heating:DX:SingleSpeed | SPLIT TSE HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.42805 |
| 696 | Coil:Heating:DX:SingleSpeed | SPLIT TSE HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 7900.35488 |
| 697 | Coil:Heating:Electric | SPLIT TSE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7900.35488 |
| 698 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.41680 |
| 699 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 700 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.41680 |
| 701 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.41680 |
| 702 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.41680 |
| 703 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.41680 |
| 704 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7698.66149 |
| 705 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 5158.10320 |
| 706 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 707 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 7698.66149 |
| 708 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 709 | Fan:OnOff | SPLIT TNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.41680 |
| 710 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.41680 |
| 711 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7698.66149 |
| 712 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80049 |
| 713 | Coil:Heating:DX:SingleSpeed | SPLIT TNE HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.41680 |
| 714 | Coil:Heating:DX:SingleSpeed | SPLIT TNE HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 7698.66149 |
| 715 | Coil:Heating:Electric | SPLIT TNE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7698.66149 |
| 716 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.36953 |
| 717 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 718 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.36953 |
| 719 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36953 |
| 720 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36953 |
| 721 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36953 |
| 722 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6885.10556 |
| 723 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4613.02072 |
| 724 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 725 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 6885.10556 |
| 726 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 727 | Fan:OnOff | SPLIT TN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36953 |
| 728 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36953 |
| 729 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6885.10556 |
| 730 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80064 |
| 731 | Coil:Heating:DX:SingleSpeed | SPLIT TN1 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36953 |
| 732 | Coil:Heating:DX:SingleSpeed | SPLIT TN1 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6885.10556 |
| 733 | Coil:Heating:Electric | SPLIT TN1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6885.10556 |
| 734 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.36854 |
| 735 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 736 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.36854 |
| 737 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36854 |
| 738 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36854 |
| 739 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36854 |
| 740 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6868.73474 |
| 741 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4602.05228 |
| 742 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 743 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 6868.73474 |
| 744 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 745 | Fan:OnOff | SPLIT TN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36854 |
| 746 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36854 |
| 747 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6868.73474 |
| 748 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80055 |
| 749 | Coil:Heating:DX:SingleSpeed | SPLIT TN2 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36854 |
| 750 | Coil:Heating:DX:SingleSpeed | SPLIT TN2 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6868.73474 |
| 751 | Coil:Heating:Electric | SPLIT TN2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6868.73474 |
| 752 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.38159 |
| 753 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 754 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.38159 |
| 755 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.38159 |
| 756 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.38159 |
| 757 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.38159 |
| 758 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7103.47510 |
| 759 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4759.32832 |
| 760 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 761 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 7103.47510 |
| 762 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 763 | Fan:OnOff | SPLIT TS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.38159 |
| 764 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38159 |
| 765 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7103.47510 |
| 766 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80094 |
| 767 | Coil:Heating:DX:SingleSpeed | SPLIT TS1 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38159 |
| 768 | Coil:Heating:DX:SingleSpeed | SPLIT TS1 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 7103.47510 |
| 769 | Coil:Heating:Electric | SPLIT TS1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7103.47510 |
| 770 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.38062 |
| 771 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 772 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.38062 |
| 773 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.38062 |
| 774 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.38062 |
| 775 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.38062 |
| 776 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7087.26481 |
| 777 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 4748.46742 |
| 778 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 779 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 7087.26481 |
| 780 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 781 | Fan:OnOff | SPLIT TS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.38062 |
| 782 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 HP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38062 |
| 783 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 HP COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7087.26481 |
| 784 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 HP COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80084 |
| 785 | Coil:Heating:DX:SingleSpeed | SPLIT TS2 HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38062 |
| 786 | Coil:Heating:DX:SingleSpeed | SPLIT TS2 HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 7087.26481 |
| 787 | Coil:Heating:Electric | SPLIT TS2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7087.26481 |
| 788 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.13460E-004 |
| 789 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.36152E-002 |
| 790 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.13460E-004 |
| 791 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 14.49330 |
| 792 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.13460E-004 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW HP COOLING COIL | 7081.9 | 3.13 | 10.69 | 11.13 | 10.52 | 10.53 |
| 2 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW HP COOLING COIL | 6867.7 | 3.13 | 10.70 | 11.13 | 10.53 | 10.53 |
| 3 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE HP COOLING COIL | 7962.3 | 3.12 | 10.66 | 11.08 | 10.48 | 10.47 |
| 4 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE HP COOLING COIL | 6602.9 | 3.14 | 10.70 | 11.14 | 10.53 | 10.54 |
| 5 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 HP COOLING COIL | 5764.9 | 3.15 | 10.73 | 11.17 | 10.56 | 10.59 |
| 6 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 HP COOLING COIL | 5759.8 | 3.15 | 10.73 | 11.17 | 10.57 | 10.59 |
| 7 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 HP COOLING COIL | 6008.8 | 3.15 | 10.73 | 11.17 | 10.56 | 10.59 |
| 8 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 HP COOLING COIL | 6052.4 | 3.14 | 10.73 | 11.17 | 10.56 | 10.58 |
| 9 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW HP COOLING COIL | 14770.5 | 3.13 | 10.69 | 11.12 | 10.52 | 10.52 |
| 10 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW HP COOLING COIL | 14304.9 | 3.13 | 10.69 | 11.12 | 10.52 | 10.53 |
| 11 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE HP COOLING COIL | 14127.8 | 3.14 | 10.70 | 11.13 | 10.53 | 10.54 |
| 12 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE HP COOLING COIL | 13661.0 | 3.14 | 10.70 | 11.13 | 10.53 | 10.54 |
| 13 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 HP COOLING COIL | 11882.6 | 3.14 | 10.73 | 11.17 | 10.56 | 10.58 |
| 14 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 HP COOLING COIL | 11871.0 | 3.14 | 10.73 | 11.17 | 10.56 | 10.58 |
| 15 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 HP COOLING COIL | 12413.8 | 3.14 | 10.73 | 11.16 | 10.56 | 10.58 |
| 16 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 HP COOLING COIL | 12402.2 | 3.14 | 10.73 | 11.16 | 10.56 | 10.58 |
| 17 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW HP COOLING COIL | 8025.5 | 3.13 | 10.68 | 11.11 | 10.51 | 10.50 |
| 18 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW HP COOLING COIL | 7833.9 | 3.13 | 10.68 | 11.11 | 10.51 | 10.51 |
| 19 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE HP COOLING COIL | 7564.4 | 3.13 | 10.69 | 11.12 | 10.52 | 10.52 |
| 20 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE HP COOLING COIL | 7371.5 | 3.13 | 10.69 | 11.12 | 10.52 | 10.52 |
| 21 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 HP COOLING COIL | 6595.0 | 3.14 | 10.71 | 11.14 | 10.54 | 10.55 |
| 22 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 HP COOLING COIL | 6579.4 | 3.14 | 10.71 | 11.14 | 10.54 | 10.55 |
| 23 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 HP COOLING COIL | 6803.9 | 3.14 | 10.71 | 11.14 | 10.54 | 10.55 |
| 24 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 HP COOLING COIL | 6788.5 | 3.14 | 10.71 | 11.14 | 10.54 | 10.55 |
| Component Type | Component Name | High Temperature Heating (net) Rating Capacity {W} | Low Temperature Heating (net) Rating Capacity {W} | HSPF {Btu/W-h} | Region Number | |
| 1 | Coil:Heating:DX:SingleSpeed | SPLIT GSW HEATING COIL | 7713.7 | 4279.9 | 8.15 | 4 |
| 2 | Coil:Heating:DX:SingleSpeed | SPLIT GNW HEATING COIL | 7479.8 | 4150.0 | 8.13 | 4 |
| 3 | Coil:Heating:DX:SingleSpeed | SPLIT OFFICE HEATING COIL | 8686.9 | 4823.0 | 8.11 | 4 |
| 4 | Coil:Heating:DX:SingleSpeed | SPLIT GNE HEATING COIL | 7188.6 | 3987.9 | 8.12 | 4 |
| 5 | Coil:Heating:DX:SingleSpeed | SPLIT GN1 HEATING COIL | 6268.3 | 3475.7 | 8.17 | 4 |
| 6 | Coil:Heating:DX:SingleSpeed | SPLIT GN2 HEATING COIL | 6262.7 | 3472.5 | 8.17 | 4 |
| 7 | Coil:Heating:DX:SingleSpeed | SPLIT GS1 HEATING COIL | 6533.8 | 3622.9 | 8.19 | 4 |
| 8 | Coil:Heating:DX:SingleSpeed | SPLIT GS2 HEATING COIL | 6581.7 | 3649.6 | 8.19 | 4 |
| 9 | Coil:Heating:DX:SingleSpeed | SPLIT MSW HEATING COIL | 16091.2 | 8928.8 | 8.17 | 4 |
| 10 | Coil:Heating:DX:SingleSpeed | SPLIT MNW HEATING COIL | 15582.4 | 8646.2 | 8.15 | 4 |
| 11 | Coil:Heating:DX:SingleSpeed | SPLIT MSE HEATING COIL | 15384.1 | 8535.0 | 8.15 | 4 |
| 12 | Coil:Heating:DX:SingleSpeed | SPLIT MNE HEATING COIL | 14874.3 | 8251.8 | 8.13 | 4 |
| 13 | Coil:Heating:DX:SingleSpeed | SPLIT MN1 HEATING COIL | 12922.0 | 7165.3 | 8.19 | 4 |
| 14 | Coil:Heating:DX:SingleSpeed | SPLIT MN2 HEATING COIL | 12909.2 | 7158.2 | 8.19 | 4 |
| 15 | Coil:Heating:DX:SingleSpeed | SPLIT MS1 HEATING COIL | 13501.0 | 7486.7 | 8.11 | 4 |
| 16 | Coil:Heating:DX:SingleSpeed | SPLIT MS2 HEATING COIL | 13488.3 | 7479.6 | 8.11 | 4 |
| 17 | Coil:Heating:DX:SingleSpeed | SPLIT TSW HEATING COIL | 8748.0 | 4855.2 | 8.12 | 4 |
| 18 | Coil:Heating:DX:SingleSpeed | SPLIT TNW HEATING COIL | 8538.6 | 4738.9 | 8.11 | 4 |
| 19 | Coil:Heating:DX:SingleSpeed | SPLIT TSE HEATING COIL | 8240.9 | 4572.9 | 8.10 | 4 |
| 20 | Coil:Heating:DX:SingleSpeed | SPLIT TNE HEATING COIL | 8030.3 | 4455.9 | 8.17 | 4 |
| 21 | Coil:Heating:DX:SingleSpeed | SPLIT TN1 HEATING COIL | 7179.2 | 3982.5 | 8.12 | 4 |
| 22 | Coil:Heating:DX:SingleSpeed | SPLIT TN2 HEATING COIL | 7162.1 | 3972.9 | 8.12 | 4 |
| 23 | Coil:Heating:DX:SingleSpeed | SPLIT TS1 HEATING COIL | 7407.2 | 4109.1 | 8.13 | 4 |
| 24 | Coil:Heating:DX:SingleSpeed | SPLIT TS2 HEATING COIL | 7390.2 | 4099.6 | 8.13 | 4 |
| Zone Name | # Surfaces | |
| 1 | G SW APARTMENT | 9 |
| 2 | G NW APARTMENT | 9 |
| 3 | OFFICE | 9 |
| 4 | G NE APARTMENT | 9 |
| 5 | G N1 APARTMENT | 8 |
| 6 | G N2 APARTMENT | 8 |
| 7 | G S1 APARTMENT | 8 |
| 8 | G S2 APARTMENT | 8 |
| 9 | M SW APARTMENT | 9 |
| 10 | M NW APARTMENT | 9 |
| 11 | M SE APARTMENT | 9 |
| 12 | M NE APARTMENT | 9 |
| 13 | M N1 APARTMENT | 8 |
| 14 | M N2 APARTMENT | 8 |
| 15 | M S1 APARTMENT | 8 |
| 16 | M S2 APARTMENT | 8 |
| 17 | T SW APARTMENT | 9 |
| 18 | T NW APARTMENT | 9 |
| 19 | T SE APARTMENT | 9 |
| 20 | T NE APARTMENT | 9 |
| 21 | T N1 APARTMENT | 8 |
| 22 | T N2 APARTMENT | 8 |
| 23 | T S1 APARTMENT | 8 |
| 24 | T S2 APARTMENT | 8 |
| 25 | T CORRIDOR | 13 |
| 26 | G CORRIDOR | 13 |
| 27 | M CORRIDOR | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | G SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 1.154 | 0.984 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | GWINDOW1 S SWA | Window | G SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | G WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 1.154 | 0.984 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | GWINDOW1 W SWA | Window | G WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | G GFLOOR SWA | Floor | CTF - ConductionTransferFunction | GGFLOORSWA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 8 | G CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 9 | G INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 10 | G NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 1.154 | 0.984 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | GWINDOW1 N NWA | Window | G NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 12 | G WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 1.154 | 0.984 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | GWINDOW1 W NWA | Window | G WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | G GFLOOR NWA | Floor | CTF - ConductionTransferFunction | GGFLOORNWA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | G CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | G INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | G SWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.154 | 0.984 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | GWINDOW1 S SEA | Window | G SWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 21 | G EWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.154 | 0.984 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | GWINDOW1 E SEA | Window | G EWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 23 | G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | iz-G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | G GFLOOR SEA | Floor | CTF - ConductionTransferFunction | GGFLOORSEA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 26 | G CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 27 | G INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 28 | G NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 1.154 | 0.984 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | GWINDOW1 N NEA | Window | G NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 30 | G EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 1.154 | 0.984 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 31 | GWINDOW1 E NEA | Window | G EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 32 | G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | iz-G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | G GFLOOR NEA | Floor | CTF - ConductionTransferFunction | GGFLOORNEA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 35 | G CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 36 | G INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 37 | G NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 1.154 | 0.984 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | GWINDOW1 N N1A | Window | G NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 39 | G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 40 | G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | iz-G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | G GFLOOR N1A | Floor | CTF - ConductionTransferFunction | GGFLOORN1A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | G CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | G INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | G NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 1.154 | 0.984 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | GWINDOW1 N N2A | Window | G NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 47 | G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 50 | G GFLOOR N2A | Floor | CTF - ConductionTransferFunction | GGFLOORN2A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 51 | G CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 52 | G INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | G SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 1.154 | 0.984 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | GWINDOW1 S S1A | Window | G SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 57 | iz-G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | G GFLOOR S1A | Floor | CTF - ConductionTransferFunction | GGFLOORS1A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 59 | G CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 60 | G INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 61 | G SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 1.154 | 0.984 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | GWINDOW1 S S2A | Window | G SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 63 | G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 65 | iz-G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | G GFLOOR S2A | Floor | CTF - ConductionTransferFunction | GGFLOORS2A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 67 | G CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 68 | G INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 69 | M WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.171 | 0.996 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 70 | MWINDOW1 W SWA | Window | M WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | M SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.171 | 0.996 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 72 | MWINDOW1 S SWA | Window | M SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 73 | M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 3.05 | 7.62 | 0.00 | iz-M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | M GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 76 | M CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 77 | M INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | M NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.171 | 0.996 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | MWINDOW1 N NWA | Window | M NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 80 | M WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.171 | 0.996 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | MWINDOW1 W NWA | Window | M WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 82 | M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | M GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 85 | M CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 86 | M INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 87 | M EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.171 | 0.996 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 88 | MWINDOW1 E SEA | Window | M EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 89 | M SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.171 | 0.996 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | MWINDOW1 S SEA | Window | M SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 91 | M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | iz-M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 93 | M GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | M CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | M INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 96 | M NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.171 | 0.996 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | MWINDOW1 N NEA | Window | M NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | M EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.171 | 0.996 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | MWINDOW1 E NEA | Window | M EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | M GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 103 | M CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 104 | M INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | M NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.171 | 0.996 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | MWINDOW1 N N1A | Window | M NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 109 | iz-M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | M GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | M CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | M INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | M NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.171 | 0.996 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | MWINDOW1 N N2A | Window | M NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 115 | M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | iz-M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | M GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 119 | M CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 120 | M INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 121 | M SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.171 | 0.996 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 122 | MWINDOW1 S S1A | Window | M SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 123 | M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | iz-M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 3.05 | 7.62 | 0.00 | M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | M GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 127 | M CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 128 | M INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 129 | M SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.171 | 0.996 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | MWINDOW1 S S2A | Window | M SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 131 | M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | iz-M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | M GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 135 | M CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 136 | M INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 137 | T WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.430 | 1.178 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | TWINDOW1 W SWA | Window | T WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 139 | T SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.430 | 1.178 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | TWINDOW1 S SWA | Window | T SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 141 | T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | T GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 144 | T ROOF SWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 145 | T INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 146 | T NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.430 | 1.178 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | TWINDOW1 N NWA | Window | T NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 148 | T WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.430 | 1.178 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | TWINDOW1 W NWA | Window | T WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 151 | T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 152 | T GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 153 | T ROOF NWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 154 | T INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 155 | T EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.430 | 1.178 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 156 | TWINDOW1 E SEA | Window | T EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 157 | T SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.430 | 1.178 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | TWINDOW1 S SEA | Window | T SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 159 | T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | iz-T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | T GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 162 | T ROOF SEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 163 | T INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 164 | T NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.430 | 1.178 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | TWINDOW1 N NEA | Window | T NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 166 | T EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.430 | 1.178 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | TWINDOW1 E NEA | Window | T EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 168 | T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | T GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 171 | T ROOF NEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 172 | T INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 173 | T NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.430 | 1.178 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | TWINDOW1 N N1A | Window | T NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | iz-T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | T GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 179 | T ROOF N1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 180 | T INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 181 | T NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.430 | 1.178 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | TWINDOW1 N N2A | Window | T NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 183 | T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | iz-T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | T GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 187 | T ROOF N2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 188 | T INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 189 | T SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.430 | 1.178 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | TWINDOW1 S S1A | Window | T SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 191 | T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | iz-T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | T GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 195 | T ROOF S1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 196 | T INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 197 | T SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.430 | 1.178 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | TWINDOW1 S S2A | Window | T SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 199 | T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | iz-T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | T GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 203 | T ROOF S2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 204 | T INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 205 | T WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.430 | 1.178 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 206 | T EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.430 | 1.178 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | TWINDOW14 | Window | T EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 208 | iz-T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | iz-T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | iz-T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | iz-T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | iz-T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | iz-T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | iz-T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | iz-T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | T FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | T FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 217 | T ROOF C | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 218 | G WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.154 | 0.984 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | G EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.154 | 0.984 | 1.79 | 5.11 | 1.79 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | ENTRANCE DOOR | Window | G EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 3.32 | 3.32 | 3.32 | 90.00 | 90.00 | 1.57 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | iz-G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 222 | iz-G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 223 | iz-G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | iz-G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | iz-G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | iz-G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | iz-G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 228 | iz-G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 229 | G FLOOR C | Floor | CTF - ConductionTransferFunction | GFLOORC_FFACTOR | 5.502E-002 | 5.429E-002 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 230 | G CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | G CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 231 | M WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.171 | 0.996 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | M EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.171 | 0.996 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | MWINDOW14 | Window | M EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.53_SHGC_0.215 | N/A | 3.013 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 234 | iz-M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | iz-M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | iz-M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | iz-M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | iz-M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | iz-M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 240 | iz-M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 241 | iz-M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 242 | M FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | M FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | M CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | M CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEAR'S DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | G SW APARTMENT | RunPeriod: RUNPERIOD 1 | 0.1243362992 | 0.3160596863 | Pass | Pass | 155.0478834847 | 1817.1668860760 | Pass | Pass |
| 2 | G NW APARTMENT | RunPeriod: RUNPERIOD 1 | 3.6318504955E-002 | 0.1051756704 | Pass | Pass | 0.1150880684 | 0.2340505297 | Pass | Pass |
| 3 | OFFICE | RunPeriod: RUNPERIOD 1 | 3.2839460020E-002 | 2.4279634832E-002 | Pass | Pass | 0.2199175442 | 0.8988420287 | Pass | Pass |
| 4 | G NE APARTMENT | RunPeriod: RUNPERIOD 1 | 3.3780960616E-002 | 9.5227680914E-002 | Pass | Pass | 0.1388665682 | 0.3893004582 | Pass | Pass |
| 5 | G N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.2900682905E-002 | 0.1121964015 | Pass | Pass | 0.1469045177 | 0.5374544800 | Pass | Pass |
| 6 | G N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.2896267792E-002 | 0.1120782989 | Pass | Pass | 0.1499499592 | 0.5610874585 | Pass | Pass |
| 7 | G S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 0.1196090174 | 0.3112031511 | Pass | Pass | 33.2049169305 | 319.4908887864 | Pass | Pass |
| 8 | G S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 0.1214406047 | 0.3129807770 | Pass | Pass | 20.0213175851 | 155.1230010388 | Pass | Pass |
| 9 | M SW APARTMENT | RunPeriod: RUNPERIOD 1 | 0.1179261271 | 0.3072572347 | Pass | Pass | 6.3281227049 | 52.1895951376 | Pass | Pass |
| 10 | M NW APARTMENT | RunPeriod: RUNPERIOD 1 | 3.7158981257E-002 | 8.8288821747E-002 | Pass | Pass | 0.1677990378 | 0.5157666058 | Pass | Pass |
| 11 | M SE APARTMENT | RunPeriod: RUNPERIOD 1 | 0.1007774892 | 0.2678461246 | Pass | Pass | 8.2841174172 | 77.4056214703 | Pass | Pass |
| 12 | M NE APARTMENT | RunPeriod: RUNPERIOD 1 | 3.5127329818E-002 | 7.7339669820E-002 | Pass | Pass | 0.1788180278 | 0.6009619627 | Pass | Pass |
| 13 | M N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.0625023005E-002 | 0.1097508730 | Pass | Pass | 0.1741941198 | 0.5138473868 | Pass | Pass |
| 14 | M N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.0654546708E-002 | 0.1097080491 | Pass | Pass | 0.1746879938 | 0.5146690777 | Pass | Pass |
| 15 | M S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 0.1090190821 | 0.3061262669 | Pass | Pass | 70.1741860831 | 780.2573547130 | Pass | Pass |
| 16 | M S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 0.1088620011 | 0.3058874146 | Pass | Pass | 58.7127388138 | 641.9330892330 | Pass | Pass |
| 17 | T SW APARTMENT | RunPeriod: RUNPERIOD 1 | 0.1584701149 | 0.2968025232 | Pass | Pass | 4.7660840185 | 36.2138637645 | Pass | Pass |
| 18 | T NW APARTMENT | RunPeriod: RUNPERIOD 1 | 5.1188242588E-002 | 3.6044545485E-002 | Pass | Pass | 0.1687280261 | 0.6211635244 | Pass | Pass |
| 19 | T SE APARTMENT | RunPeriod: RUNPERIOD 1 | 0.1425802985 | 0.2810198505 | Pass | Pass | 11.7067172773 | 88.6107323299 | Pass | Pass |
| 20 | T NE APARTMENT | RunPeriod: RUNPERIOD 1 | 4.6628922577E-002 | 3.5294485449E-002 | Pass | Pass | 0.1501003352 | 0.4590075353 | Pass | Pass |
| 21 | T N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.6399692133E-002 | 6.1366753523E-002 | Pass | Pass | 0.1494670476 | 0.3593414753 | Pass | Pass |
| 22 | T N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.6046308257E-002 | 5.9473707407E-002 | Pass | Pass | 0.1503468115 | 0.3617681157 | Pass | Pass |
| 23 | T S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 0.1543295070 | 0.3105447622 | Pass | Pass | 52.3288873422 | 583.4069196194 | Pass | Pass |
| 24 | T S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 0.1538886983 | 0.3097118633 | Pass | Pass | 41.8057271897 | 456.2332066644 | Pass | Pass |
| 25 | T CORRIDOR | RunPeriod: RUNPERIOD 1 | 3.1479355646E-002 | 2.0011864660E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 26 | G CORRIDOR | RunPeriod: RUNPERIOD 1 | 0.1218795859 | 0.3592457829 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 27 | M CORRIDOR | RunPeriod: RUNPERIOD 1 | 8.2437286714E-003 | 6.9552383895E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 989.07 | -25.5 | 0.00 | -8.0 | 1921.25 | 2876.87 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
| DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 2.40 | 26 | |||
| Feb | 9.60 | 38 | |||
| Mar | 3.60 | 37 | |||
| Apr | 0.00 | 0 | |||
| May | 0.00 | 0 | |||
| Jun | 0.00 | 0 | |||
| Jul | 1.20 | 13 | |||
| Aug | 0.00 | 0 | |||
| Sep | 0.00 | 0 | |||
| Oct | 0.00 | 0 | |||
| Nov | 0.00 | 0 | |||
| Dec | 18.00 | 37 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G SWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G WWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR SWA | GGFLOORSWA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G WWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR NWA | GGFLOORNWA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G EWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR SEA | GGFLOORSEA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G EWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR NEA | GGFLOORNEA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N1A | RES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N1A | GGFLOORN1A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N2A | RES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N2A | GGFLOORN2A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S1A | RES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S1A | GGFLOORS1A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S2A | RES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S2A | GGFLOORS2A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| M WWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M SWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M WWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M EWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M SWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M EWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M NWALL N1A | RES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M NWALL N2A | RES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M SWALL S1A | RES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M SWALL S2A | RES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| T WWALL SWA | RES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T SWALL SWA | RES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SWA | RES_ROOF | 0.55 | 0.182 | 0.186 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NWA | RES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T WWALL NWA | RES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T ROOF NWA | RES_ROOF | 0.55 | 0.182 | 0.186 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T EWALL SEA | RES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T SWALL SEA | RES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SEA | RES_ROOF | 0.55 | 0.182 | 0.186 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NEA | RES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T EWALL NEA | RES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T ROOF NEA | RES_ROOF | 0.55 | 0.182 | 0.186 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N1A | RES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N1A | RES_ROOF | 0.55 | 0.182 | 0.186 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N2A | RES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N2A | RES_ROOF | 0.55 | 0.182 | 0.186 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S1A | RES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S1A | RES_ROOF | 0.55 | 0.182 | 0.186 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S2A | RES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S2A | RES_ROOF | 0.55 | 0.182 | 0.186 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T WWALL C | NONRES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| T EWALL C | NONRES_EXT_WALL_TOP | 0.30 | 1.178 | 1.430 | 5.11 | 3.99 | 90.00 | 90.00 | E |
| T ROOF C | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 77.66 | 77.66 | 180.00 | 0.00 | |
| G WWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| G EWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.984 | 1.154 | 5.11 | 1.79 | 90.00 | 90.00 | E |
| G FLOOR C | GFLOORC_FFACTOR | 1.00 | 0.055 | 0.055 | 77.66 | 77.66 | 90.00 | 180.00 | |
| M WWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 10.22 | 10.22 | 270.00 | 90.00 | W |
| M EWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.996 | 1.171 | 10.22 | 7.99 | 90.00 | 90.00 | E |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| iz-T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 77.66 | 77.66 | 90.00 | 180.00 | |
| iz-G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 77.66 | 77.66 | 180.00 | 0.00 | |
| iz-M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 155.32 | 155.32 | 90.00 | 180.00 | |
| M CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 155.32 | 155.32 | 180.00 | 0.00 | |
| G INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| GWINDOW1 S SWA | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | G SWALL SWA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 W SWA | RESWINDOW_U_0.53_SHGC_0.215 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.013 | 0.216 | 0.237 | No | G WWALL SWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 N NWA | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | G NWALL NWA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 W NWA | RESWINDOW_U_0.53_SHGC_0.215 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.013 | 0.216 | 0.237 | No | G WWALL NWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 S SEA | NONRESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | G SWALL SEA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 E SEA | NONRESWINDOW_U_0.53_SHGC_0.215 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.013 | 0.216 | 0.237 | No | G EWALL SEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N NEA | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | G NWALL NEA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 E NEA | RESWINDOW_U_0.53_SHGC_0.215 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.013 | 0.216 | 0.237 | No | G EWALL NEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N N1A | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | G NWALL N1A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 N N2A | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | G NWALL N2A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 S S1A | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | G SWALL S1A | 180.00 | 90.00 | S | |||||||
| GWINDOW1 S S2A | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | G SWALL S2A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 W SWA | RESWINDOW_U_0.53_SHGC_0.215 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.013 | 0.216 | 0.237 | No | M WWALL SWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 S SWA | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.013 | 0.216 | 0.237 | No | M SWALL SWA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NWA | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.013 | 0.216 | 0.237 | No | M NWALL NWA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 W NWA | RESWINDOW_U_0.53_SHGC_0.215 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.013 | 0.216 | 0.237 | No | M WWALL NWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 E SEA | RESWINDOW_U_0.53_SHGC_0.215 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.013 | 0.216 | 0.237 | No | M EWALL SEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 S SEA | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.013 | 0.216 | 0.237 | No | M SWALL SEA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NEA | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.013 | 0.216 | 0.237 | No | M NWALL NEA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 E NEA | RESWINDOW_U_0.53_SHGC_0.215 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.013 | 0.216 | 0.237 | No | M EWALL NEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 N N1A | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.013 | 0.216 | 0.237 | No | M NWALL N1A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 N N2A | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.013 | 0.216 | 0.237 | No | M NWALL N2A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 S S1A | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.013 | 0.216 | 0.237 | No | M SWALL S1A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 S S2A | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.013 | 0.216 | 0.237 | No | M SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 W SWA | RESWINDOW_U_0.53_SHGC_0.215 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.013 | 0.216 | 0.237 | No | T WWALL SWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 S SWA | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | T SWALL SWA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NWA | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | T NWALL NWA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 W NWA | RESWINDOW_U_0.53_SHGC_0.215 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.013 | 0.216 | 0.237 | No | T WWALL NWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 E SEA | RESWINDOW_U_0.53_SHGC_0.215 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.013 | 0.216 | 0.237 | No | T EWALL SEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 S SEA | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | T SWALL SEA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NEA | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | T NWALL NEA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 E NEA | RESWINDOW_U_0.53_SHGC_0.215 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.013 | 0.216 | 0.237 | No | T EWALL NEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 N N1A | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | T NWALL N1A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 N N2A | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | T NWALL N2A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 S S1A | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | T SWALL S1A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 S S2A | RESWINDOW_U_0.53_SHGC_0.215 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.013 | 0.216 | 0.237 | No | T SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW14 | NONRESWINDOW_U_0.53_SHGC_0.215 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 3.013 | 0.216 | 0.237 | No | T EWALL C | 90.00 | 90.00 | E | |||||||
| ENTRANCE DOOR | NONRESWINDOW_U_0.53_SHGC_0.215 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 3.013 | 0.216 | 0.237 | No | G EWALL C | 90.00 | 90.00 | E | |||||||
| MWINDOW14 | NONRESWINDOW_U_0.53_SHGC_0.215 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 3.013 | 0.216 | 0.237 | No | M EWALL C | 90.00 | 90.00 | E | |||||||
| Total or Average | 306.92 | 3.013 | 0.216 | 0.237 | |||||||||||||||||
| North Total or Average | 112.97 | 3.013 | 0.216 | 0.237 | |||||||||||||||||
| Non-North Total or Average | 193.95 | 3.013 | 0.216 | 0.237 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| LIGHTING_HARDWIRED_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_OFFICE | OFFICE | OFFICE | GENERAL | 7.4895 | 88.25 | 660.94 | LightsWired | LTG_SCH_OFFICE | 46.69 | 168.00 | 45.77 | 0.0000 | Y | 5.68 |
| LIGHTING_HARDWIRED_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 4.5208 | 176.50 | 797.92 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.51 |
| LIGHTING_HARDWIRED_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 4.5208 | 88.25 | 398.96 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.76 |
| LIGHTING_HARDWIRED_GC | G CORRIDOR | G CORRIDOR | GENERAL | 5.2871 | 77.66 | 410.59 | LightsWired | LTG_SCH_CORRIDOR | 126.00 | 168.00 | 126.00 | 0.0000 | N | 9.71 |
| LIGHTING_HARDWIRED_MC | M CORRIDOR | M CORRIDOR | GENERAL | 5.2871 | 155.32 | 821.19 | LightsWired | LTG_SCH_CORRIDOR | 126.00 | 168.00 | 126.00 | 0.0000 | N | 19.42 |
| LIGHTING_HARDWIRED_TC | T CORRIDOR | T CORRIDOR | GENERAL | 5.2871 | 77.66 | 410.59 | LightsWired | LTG_SCH_CORRIDOR | 126.00 | 168.00 | 126.00 | 0.0000 | N | 9.71 |
| LIGHTING_PLUGIN_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 0.9688 | 176.50 | 170.98 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.32 |
| LIGHTING_PLUGIN_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 0.9688 | 88.25 | 85.49 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.16 |
| Interior Lighting Total | 2.9507 | 5870.34 | 17321.34 | 55.94 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| FACADE LIGHTING | 2101.03 | AstronomicalClock | - | 83.85 | 83.85 | 33.07 | |
| Exterior Lighting Total | 2101.03 | 33.07 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| SPLIT GSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7395.65 | 5923.25 | 1472.40 | 0.80 | 3.82 | |||
| SPLIT GNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7171.63 | 5741.79 | 1429.84 | 0.80 | 3.82 | |||
| SPLIT OFFICE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8322.19 | 6660.98 | 1661.21 | 0.80 | 3.82 | |||
| SPLIT GNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6893.72 | 5515.56 | 1378.16 | 0.80 | 3.82 | |||
| SPLIT GN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6014.87 | 4812.57 | 1202.30 | 0.80 | 3.82 | |||
| SPLIT GN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6009.52 | 4808.05 | 1201.47 | 0.80 | 3.82 | |||
| SPLIT GS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6269.50 | 5017.29 | 1252.21 | 0.80 | 3.82 | |||
| SPLIT GS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6315.17 | 5055.89 | 1259.28 | 0.80 | 3.82 | |||
| SPLIT MSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15426.35 | 12351.20 | 3075.15 | 0.80 | 3.82 | |||
| SPLIT MNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14939.32 | 11955.32 | 2984.00 | 0.80 | 3.82 | |||
| SPLIT MSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14751.62 | 11814.20 | 2937.42 | 0.80 | 3.82 | |||
| SPLIT MNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14263.49 | 11417.66 | 2845.83 | 0.80 | 3.82 | |||
| SPLIT MN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12398.66 | 9926.69 | 2471.97 | 0.80 | 3.82 | |||
| SPLIT MN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12386.47 | 9916.40 | 2470.07 | 0.80 | 3.82 | |||
| SPLIT MS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12953.64 | 10363.39 | 2590.25 | 0.80 | 3.82 | |||
| SPLIT MS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12941.47 | 10366.00 | 2575.47 | 0.80 | 3.82 | |||
| SPLIT TSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8384.28 | 6714.41 | 1669.88 | 0.80 | 3.82 | |||
| SPLIT TNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8183.87 | 6551.87 | 1632.00 | 0.80 | 3.82 | |||
| SPLIT TSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7900.35 | 6326.16 | 1574.20 | 0.80 | 3.82 | |||
| SPLIT TNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7698.66 | 6162.73 | 1535.94 | 0.80 | 3.82 | |||
| SPLIT TN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6885.11 | 5512.48 | 1372.62 | 0.80 | 3.82 | |||
| SPLIT TN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6868.73 | 5498.74 | 1370.00 | 0.80 | 3.82 | |||
| SPLIT TS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7103.48 | 5689.43 | 1414.04 | 0.80 | 3.82 | |||
| SPLIT TS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7087.26 | 5675.80 | 1411.47 | 0.80 | 3.82 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| SPLIT GSW HP COOLING COIL | 7081.9 | 3.13 | 10.69 | 11.13 | 10.52 | 10.53 | |
| SPLIT GNW HP COOLING COIL | 6867.7 | 3.13 | 10.70 | 11.13 | 10.53 | 10.53 | |
| SPLIT OFFICE HP COOLING COIL | 7962.3 | 3.12 | 10.66 | 11.08 | 10.48 | 10.47 | |
| SPLIT GNE HP COOLING COIL | 6602.9 | 3.14 | 10.70 | 11.14 | 10.53 | 10.54 | |
| SPLIT GN1 HP COOLING COIL | 5764.9 | 3.15 | 10.73 | 11.17 | 10.56 | 10.59 | |
| SPLIT GN2 HP COOLING COIL | 5759.8 | 3.15 | 10.73 | 11.17 | 10.57 | 10.59 | |
| SPLIT GS1 HP COOLING COIL | 6008.8 | 3.15 | 10.73 | 11.17 | 10.56 | 10.59 | |
| SPLIT GS2 HP COOLING COIL | 6052.4 | 3.14 | 10.73 | 11.17 | 10.56 | 10.58 | |
| SPLIT MSW HP COOLING COIL | 14770.5 | 3.13 | 10.69 | 11.12 | 10.52 | 10.52 | |
| SPLIT MNW HP COOLING COIL | 14304.9 | 3.13 | 10.69 | 11.12 | 10.52 | 10.53 | |
| SPLIT MSE HP COOLING COIL | 14127.8 | 3.14 | 10.70 | 11.13 | 10.53 | 10.54 | |
| SPLIT MNE HP COOLING COIL | 13661.0 | 3.14 | 10.70 | 11.13 | 10.53 | 10.54 | |
| SPLIT MN1 HP COOLING COIL | 11882.6 | 3.14 | 10.73 | 11.17 | 10.56 | 10.58 | |
| SPLIT MN2 HP COOLING COIL | 11871.0 | 3.14 | 10.73 | 11.17 | 10.56 | 10.58 | |
| SPLIT MS1 HP COOLING COIL | 12413.8 | 3.14 | 10.73 | 11.16 | 10.56 | 10.58 | |
| SPLIT MS2 HP COOLING COIL | 12402.2 | 3.14 | 10.73 | 11.16 | 10.56 | 10.58 | |
| SPLIT TSW HP COOLING COIL | 8025.5 | 3.13 | 10.68 | 11.11 | 10.51 | 10.50 | |
| SPLIT TNW HP COOLING COIL | 7833.9 | 3.13 | 10.68 | 11.11 | 10.51 | 10.51 | |
| SPLIT TSE HP COOLING COIL | 7564.4 | 3.13 | 10.69 | 11.12 | 10.52 | 10.52 | |
| SPLIT TNE HP COOLING COIL | 7371.5 | 3.13 | 10.69 | 11.12 | 10.52 | 10.52 | |
| SPLIT TN1 HP COOLING COIL | 6595.0 | 3.14 | 10.71 | 11.14 | 10.54 | 10.55 | |
| SPLIT TN2 HP COOLING COIL | 6579.4 | 3.14 | 10.71 | 11.14 | 10.54 | 10.55 | |
| SPLIT TS1 HP COOLING COIL | 6803.9 | 3.14 | 10.71 | 11.14 | 10.54 | 10.55 | |
| SPLIT TS2 HP COOLING COIL | 6788.5 | 3.14 | 10.71 | 11.14 | 10.54 | 10.55 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| SPLIT GSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT OFFICE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| SPLIT GSW HEATING COIL | Coil:Heating:DX:SingleSpeed | 7713.7 | 4279.9 | 8.15 | 4 |
| SPLIT GNW HEATING COIL | Coil:Heating:DX:SingleSpeed | 7479.8 | 4150.0 | 8.13 | 4 |
| SPLIT OFFICE HEATING COIL | Coil:Heating:DX:SingleSpeed | 8686.9 | 4823.0 | 8.11 | 4 |
| SPLIT GNE HEATING COIL | Coil:Heating:DX:SingleSpeed | 7188.6 | 3987.9 | 8.12 | 4 |
| SPLIT GN1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6268.3 | 3475.7 | 8.17 | 4 |
| SPLIT GN2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6262.7 | 3472.5 | 8.17 | 4 |
| SPLIT GS1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6533.8 | 3622.9 | 8.19 | 4 |
| SPLIT GS2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6581.7 | 3649.6 | 8.19 | 4 |
| SPLIT MSW HEATING COIL | Coil:Heating:DX:SingleSpeed | 16091.2 | 8928.8 | 8.17 | 4 |
| SPLIT MNW HEATING COIL | Coil:Heating:DX:SingleSpeed | 15582.4 | 8646.2 | 8.15 | 4 |
| SPLIT MSE HEATING COIL | Coil:Heating:DX:SingleSpeed | 15384.1 | 8535.0 | 8.15 | 4 |
| SPLIT MNE HEATING COIL | Coil:Heating:DX:SingleSpeed | 14874.3 | 8251.8 | 8.13 | 4 |
| SPLIT MN1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 12922.0 | 7165.3 | 8.19 | 4 |
| SPLIT MN2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 12909.2 | 7158.2 | 8.19 | 4 |
| SPLIT MS1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 13501.0 | 7486.7 | 8.11 | 4 |
| SPLIT MS2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 13488.3 | 7479.6 | 8.11 | 4 |
| SPLIT TSW HEATING COIL | Coil:Heating:DX:SingleSpeed | 8748.0 | 4855.2 | 8.12 | 4 |
| SPLIT TNW HEATING COIL | Coil:Heating:DX:SingleSpeed | 8538.6 | 4738.9 | 8.11 | 4 |
| SPLIT TSE HEATING COIL | Coil:Heating:DX:SingleSpeed | 8240.9 | 4572.9 | 8.10 | 4 |
| SPLIT TNE HEATING COIL | Coil:Heating:DX:SingleSpeed | 8030.3 | 4455.9 | 8.17 | 4 |
| SPLIT TN1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 7179.2 | 3982.5 | 8.12 | 4 |
| SPLIT TN2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 7162.1 | 3972.9 | 8.12 | 4 |
| SPLIT TS1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 7407.2 | 4109.1 | 8.13 | 4 |
| SPLIT TS2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 7390.2 | 4099.6 | 8.13 | 4 |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| SPLIT GSW HEATING COIL | Coil:Heating:DX:SingleSpeed | 7395.65 | 3.81 | |
| SPLIT GSW_SUPPHEATCOIL | Coil:Heating:Electric | 7395.65 | 1.00 | |
| SPLIT GNW HEATING COIL | Coil:Heating:DX:SingleSpeed | 7171.63 | 3.81 | |
| SPLIT GNW_SUPPHEATCOIL | Coil:Heating:Electric | 7171.63 | 1.00 | |
| SPLIT OFFICE HEATING COIL | Coil:Heating:DX:SingleSpeed | 8322.19 | 3.81 | |
| SPLIT OFFICE_SUPPHEATCOIL | Coil:Heating:Electric | 8322.19 | 1.00 | |
| SPLIT GNE HEATING COIL | Coil:Heating:DX:SingleSpeed | 6893.72 | 3.81 | |
| SPLIT GNE_SUPPHEATCOIL | Coil:Heating:Electric | 6893.72 | 1.00 | |
| SPLIT GN1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6014.87 | 3.81 | |
| SPLIT GN1_SUPPHEATCOIL | Coil:Heating:Electric | 6014.87 | 1.00 | |
| SPLIT GN2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6009.52 | 3.81 | |
| SPLIT GN2_SUPPHEATCOIL | Coil:Heating:Electric | 6009.52 | 1.00 | |
| SPLIT GS1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6269.50 | 3.81 | |
| SPLIT GS1_SUPPHEATCOIL | Coil:Heating:Electric | 6269.50 | 1.00 | |
| SPLIT GS2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6315.17 | 3.81 | |
| SPLIT GS2_SUPPHEATCOIL | Coil:Heating:Electric | 6315.17 | 1.00 | |
| SPLIT MSW HEATING COIL | Coil:Heating:DX:SingleSpeed | 15426.35 | 3.81 | |
| SPLIT MSW_SUPPHEATCOIL | Coil:Heating:Electric | 15426.35 | 1.00 | |
| SPLIT MNW HEATING COIL | Coil:Heating:DX:SingleSpeed | 14939.32 | 3.81 | |
| SPLIT MNW_SUPPHEATCOIL | Coil:Heating:Electric | 14939.32 | 1.00 | |
| SPLIT MSE HEATING COIL | Coil:Heating:DX:SingleSpeed | 14751.62 | 3.81 | |
| SPLIT MSE_SUPPHEATCOIL | Coil:Heating:Electric | 14751.62 | 1.00 | |
| SPLIT MNE HEATING COIL | Coil:Heating:DX:SingleSpeed | 14263.49 | 3.81 | |
| SPLIT MNE_SUPPHEATCOIL | Coil:Heating:Electric | 14263.49 | 1.00 | |
| SPLIT MN1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 12398.66 | 3.81 | |
| SPLIT MN1_SUPPHEATCOIL | Coil:Heating:Electric | 12398.66 | 1.00 | |
| SPLIT MN2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 12386.47 | 3.81 | |
| SPLIT MN2_SUPPHEATCOIL | Coil:Heating:Electric | 12386.47 | 1.00 | |
| SPLIT MS1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 12953.64 | 3.81 | |
| SPLIT MS1_SUPPHEATCOIL | Coil:Heating:Electric | 12953.64 | 1.00 | |
| SPLIT MS2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 12941.47 | 3.81 | |
| SPLIT MS2_SUPPHEATCOIL | Coil:Heating:Electric | 12941.47 | 1.00 | |
| SPLIT TSW HEATING COIL | Coil:Heating:DX:SingleSpeed | 8384.28 | 3.81 | |
| SPLIT TSW_SUPPHEATCOIL | Coil:Heating:Electric | 8384.28 | 1.00 | |
| SPLIT TNW HEATING COIL | Coil:Heating:DX:SingleSpeed | 8183.87 | 3.81 | |
| SPLIT TNW_SUPPHEATCOIL | Coil:Heating:Electric | 8183.87 | 1.00 | |
| SPLIT TSE HEATING COIL | Coil:Heating:DX:SingleSpeed | 7900.35 | 3.81 | |
| SPLIT TSE_SUPPHEATCOIL | Coil:Heating:Electric | 7900.35 | 1.00 | |
| SPLIT TNE HEATING COIL | Coil:Heating:DX:SingleSpeed | 7698.66 | 3.81 | |
| SPLIT TNE_SUPPHEATCOIL | Coil:Heating:Electric | 7698.66 | 1.00 | |
| SPLIT TN1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6885.11 | 3.81 | |
| SPLIT TN1_SUPPHEATCOIL | Coil:Heating:Electric | 6885.11 | 1.00 | |
| SPLIT TN2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 6868.73 | 3.81 | |
| SPLIT TN2_SUPPHEATCOIL | Coil:Heating:Electric | 6868.73 | 1.00 | |
| SPLIT TS1 HEATING COIL | Coil:Heating:DX:SingleSpeed | 7103.48 | 3.81 | |
| SPLIT TS1_SUPPHEATCOIL | Coil:Heating:Electric | 7103.48 | 1.00 | |
| SPLIT TS2 HEATING COIL | Coil:Heating:DX:SingleSpeed | 7087.26 | 3.81 | |
| SPLIT TS2_SUPPHEATCOIL | Coil:Heating:Electric | 7087.26 | 1.00 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| G SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| G S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| M SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| M S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.05 | 46.34 | 892.76 | 1.00 | 3.85 | General | ||
| T SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| T S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 270.65 | 0.03 | 23.17 | 892.76 | 1.00 | 6.84 | General | ||
| SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 447.69 | 1120.11 | 1.00 | 1.72 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 433.76 | 1120.11 | 1.00 | 1.73 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 513.70 | 1120.11 | 1.00 | 1.65 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
| SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 414.99 | 1120.11 | 1.00 | 1.76 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 356.58 | 1120.11 | 1.00 | 1.85 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 356.22 | 1120.11 | 1.00 | 1.86 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 371.86 | 1120.11 | 1.00 | 1.83 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 374.95 | 1120.11 | 1.00 | 1.82 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.84 | 935.95 | 1120.11 | 1.00 | 1.42 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.81 | 905.31 | 1120.11 | 1.00 | 1.43 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.79 | 890.18 | 1120.11 | 1.00 | 1.44 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.77 | 859.69 | 1120.11 | 1.00 | 1.45 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.66 | 736.21 | 1120.11 | 1.00 | 1.50 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.66 | 735.39 | 1120.11 | 1.00 | 1.50 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.69 | 770.14 | 1120.11 | 1.00 | 1.48 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.69 | 769.31 | 1120.11 | 1.00 | 1.48 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 512.05 | 1120.11 | 1.00 | 1.65 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 499.43 | 1120.11 | 1.00 | 1.66 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 479.46 | 1120.11 | 1.00 | 1.68 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 466.86 | 1120.11 | 1.00 | 1.69 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 413.91 | 1120.11 | 1.00 | 1.76 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 412.81 | 1120.11 | 1.00 | 1.76 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 427.43 | 1120.11 | 1.00 | 1.74 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 426.33 | 1120.11 | 1.00 | 1.74 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000113 | 14.49 | 127739.32 | 0.30 | General |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.95 | 53912.00 | 0.80 | 11.45 | 0.46 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 4699.67 | 5639.60 | 63.91 | 0.333 | 0.400 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 39.02 | 0.01078 | 0.026 | 0.00 |
| G NW APARTMENT | 4556.56 | 5467.88 | 61.96 | 0.323 | 0.387 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00810 | 39.02 | 0.01078 | 0.026 | 0.00 |
| OFFICE | 5317.30 | 6380.76 | 72.30 | 0.382 | 0.459 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.90 | 23.90 | 0.00803 | 37.46 | 0.01077 | 0.038 | 0.00 |
| G NE APARTMENT | 4363.99 | 5236.79 | 59.34 | 0.309 | 0.370 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 39.02 | 0.01078 | 0.026 | 0.00 |
| G N1 APARTMENT | 3764.03 | 4516.83 | 51.18 | 0.265 | 0.318 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 39.02 | 0.01078 | 0.026 | 0.00 |
| G N2 APARTMENT | 3760.30 | 4512.35 | 51.13 | 0.265 | 0.318 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 39.02 | 0.01078 | 0.026 | 0.00 |
| G S1 APARTMENT | 3921.95 | 4706.34 | 53.33 | 0.277 | 0.332 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00815 | 39.02 | 0.01078 | 0.026 | 0.00 |
| G S2 APARTMENT | 3953.63 | 4744.36 | 53.76 | 0.279 | 0.335 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00815 | 39.02 | 0.01078 | 0.026 | 0.00 |
| M SW APARTMENT | 9818.21 | 11781.86 | 133.51 | 0.696 | 0.836 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 39.02 | 0.01078 | 0.052 | 0.00 |
| M NW APARTMENT | 9502.71 | 11403.25 | 129.22 | 0.674 | 0.808 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 39.02 | 0.01078 | 0.052 | 0.00 |
| M SE APARTMENT | 9346.64 | 11215.97 | 127.09 | 0.662 | 0.795 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 39.02 | 0.01078 | 0.052 | 0.00 |
| M NE APARTMENT | 9033.32 | 10839.98 | 122.83 | 0.640 | 0.768 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 39.02 | 0.01078 | 0.052 | 0.00 |
| M N1 APARTMENT | 7767.59 | 9321.11 | 105.62 | 0.548 | 0.657 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 39.02 | 0.01078 | 0.052 | 0.00 |
| M N2 APARTMENT | 7759.06 | 9310.87 | 105.51 | 0.547 | 0.657 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 39.02 | 0.01078 | 0.052 | 0.00 |
| M S1 APARTMENT | 8115.03 | 9738.04 | 110.35 | 0.573 | 0.688 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00815 | 39.02 | 0.01078 | 0.052 | 0.00 |
| M S2 APARTMENT | 8106.50 | 9727.80 | 110.23 | 0.572 | 0.687 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00815 | 39.02 | 0.01078 | 0.052 | 0.00 |
| T SW APARTMENT | 5366.58 | 6439.89 | 72.97 | 0.381 | 0.457 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 39.02 | 0.01078 | 0.026 | 0.00 |
| T NW APARTMENT | 5237.17 | 6284.61 | 71.21 | 0.372 | 0.446 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 39.02 | 0.01078 | 0.026 | 0.00 |
| T SE APARTMENT | 5030.58 | 6036.70 | 68.41 | 0.357 | 0.428 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 39.02 | 0.01078 | 0.026 | 0.00 |
| T NE APARTMENT | 4900.43 | 5880.52 | 66.64 | 0.347 | 0.417 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 39.02 | 0.01078 | 0.026 | 0.00 |
| T N1 APARTMENT | 4354.89 | 5225.87 | 59.22 | 0.308 | 0.370 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 39.02 | 0.01078 | 0.026 | 0.00 |
| T N2 APARTMENT | 4343.55 | 5212.26 | 59.06 | 0.307 | 0.369 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 39.02 | 0.01078 | 0.026 | 0.00 |
| T S1 APARTMENT | 4494.05 | 5392.86 | 61.11 | 0.318 | 0.382 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 39.02 | 0.01078 | 0.026 | 0.00 |
| T S2 APARTMENT | 4482.77 | 5379.32 | 60.96 | 0.317 | 0.381 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 39.02 | 0.01078 | 0.026 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 169.99 | 203.99 | 2.31 | 0.007 | 0.026 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00833 | 12.70 | 0.00915 | 0.026 | 0.00 |
| G NW APARTMENT | 11.05 | 13.26 | 0.15 | 0.000 | 0.026 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.01535 | 12.70 | 0.00915 | 0.026 | 0.00 |
| OFFICE | 434.21 | 521.05 | 5.90 | 0.019 | 0.038 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 21.10 | 21.10 | 0.00810 | 12.70 | 0.00915 | 0.038 | 0.00 |
| G NE APARTMENT | 7.96 | 9.55 | 0.11 | 0.000 | 0.026 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.01540 | 12.70 | 0.00915 | 0.026 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.026 | 00:10:00 | 21.10 | 22.32 | 0.01702 | 12.70 | 0.00915 | 0.026 | 0.00 | |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.026 | 00:10:00 | 21.10 | 22.33 | 0.01702 | 12.70 | 0.00915 | 0.026 | 0.00 | |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.026 | 00:10:00 | 21.10 | 21.61 | 0.00915 | 12.70 | 0.00915 | 0.026 | 0.00 | |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.026 | 00:10:00 | 21.10 | 21.55 | 0.00915 | 12.70 | 0.00915 | 0.026 | 0.00 | |
| M SW APARTMENT | 749.21 | 899.05 | 10.19 | 0.032 | 0.052 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00817 | 12.70 | 0.00915 | 0.052 | 0.00 |
| M NW APARTMENT | 465.50 | 558.60 | 6.33 | 0.020 | 0.052 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00946 | 12.70 | 0.00915 | 0.052 | 0.00 |
| M SE APARTMENT | 744.81 | 893.77 | 10.13 | 0.032 | 0.052 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00817 | 12.70 | 0.00915 | 0.052 | 0.00 |
| M NE APARTMENT | 461.44 | 553.72 | 6.27 | 0.020 | 0.052 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00947 | 12.70 | 0.00915 | 0.052 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.052 | 00:10:00 | 21.10 | 21.65 | 0.01596 | 12.70 | 0.00915 | 0.052 | 0.00 | |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.052 | 00:10:00 | 21.10 | 21.65 | 0.01596 | 12.70 | 0.00915 | 0.052 | 0.00 | |
| M S1 APARTMENT | 234.62 | 281.54 | 3.19 | 0.010 | 0.052 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00851 | 12.70 | 0.00915 | 0.052 | 0.00 |
| M S2 APARTMENT | 234.41 | 281.29 | 3.19 | 0.010 | 0.052 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00851 | 12.70 | 0.00915 | 0.052 | 0.00 |
| T SW APARTMENT | 712.83 | 855.40 | 9.69 | 0.031 | 0.037 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00811 | 12.70 | 0.00915 | 0.026 | 0.00 |
| T NW APARTMENT | 574.39 | 689.27 | 7.81 | 0.025 | 0.030 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00865 | 12.70 | 0.00915 | 0.026 | 0.00 |
| T SE APARTMENT | 710.17 | 852.20 | 9.66 | 0.031 | 0.037 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00811 | 12.70 | 0.00915 | 0.026 | 0.00 |
| T NE APARTMENT | 571.90 | 686.28 | 7.78 | 0.025 | 0.030 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00865 | 12.70 | 0.00915 | 0.026 | 0.00 |
| T N1 APARTMENT | 317.55 | 381.05 | 4.32 | 0.014 | 0.026 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00910 | 12.70 | 0.00915 | 0.026 | 0.00 |
| T N2 APARTMENT | 317.45 | 380.93 | 4.32 | 0.014 | 0.026 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00910 | 12.70 | 0.00915 | 0.026 | 0.00 |
| T S1 APARTMENT | 456.27 | 547.53 | 6.20 | 0.020 | 0.026 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00812 | 12.70 | 0.00915 | 0.026 | 0.00 |
| T S2 APARTMENT | 456.17 | 547.40 | 6.20 | 0.020 | 0.026 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00812 | 12.70 | 0.00915 | 0.026 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| SPLIT GSW | 0.40 | 0.40 | 0.03 | 0.03 | 0.3997 | 0.3997 | 0.3997 | 1.0000 | 1.0000 |
| SPLIT GNW | 0.39 | 0.39 | 0.03 | 0.03 | 0.3872 | 0.3872 | 0.3872 | 1.0000 | 1.0000 |
| SPLIT OFFICE | 0.46 | 0.46 | 0.04 | 0.04 | 0.4586 | 0.4586 | 0.4586 | 1.0000 | 1.0000 |
| SPLIT GNE | 0.37 | 0.37 | 0.03 | 0.03 | 0.3705 | 0.3705 | 0.3705 | 1.0000 | 1.0000 |
| SPLIT GN1 | 0.32 | 0.32 | 0.03 | 0.03 | 0.3183 | 0.3183 | 0.3183 | 1.0000 | 1.0000 |
| SPLIT GN2 | 0.32 | 0.32 | 0.03 | 0.03 | 0.3180 | 0.3180 | 0.3180 | 1.0000 | 1.0000 |
| SPLIT GS1 | 0.33 | 0.33 | 0.03 | 0.03 | 0.3320 | 0.3320 | 0.3320 | 1.0000 | 1.0000 |
| SPLIT GS2 | 0.33 | 0.33 | 0.03 | 0.03 | 0.3347 | 0.3347 | 0.3347 | 1.0000 | 1.0000 |
| SPLIT MSW | 0.84 | 0.84 | 0.05 | 0.05 | 0.8356 | 0.8356 | 0.8356 | 1.0000 | 1.0000 |
| SPLIT MNW | 0.81 | 0.81 | 0.05 | 0.05 | 0.8082 | 0.8082 | 0.8082 | 1.0000 | 1.0000 |
| SPLIT MSE | 0.79 | 0.79 | 0.05 | 0.05 | 0.7947 | 0.7947 | 0.7947 | 1.0000 | 1.0000 |
| SPLIT MNE | 0.77 | 0.77 | 0.05 | 0.05 | 0.7675 | 0.7675 | 0.7675 | 1.0000 | 1.0000 |
| SPLIT MN1 | 0.66 | 0.66 | 0.05 | 0.05 | 0.6573 | 0.6573 | 0.6573 | 1.0000 | 1.0000 |
| SPLIT MN2 | 0.66 | 0.66 | 0.05 | 0.05 | 0.6565 | 0.6565 | 0.6565 | 1.0000 | 1.0000 |
| SPLIT MS1 | 0.69 | 0.69 | 0.05 | 0.05 | 0.6876 | 0.6876 | 0.6876 | 1.0000 | 1.0000 |
| SPLIT MS2 | 0.69 | 0.69 | 0.05 | 0.05 | 0.6868 | 0.6868 | 0.6868 | 1.0000 | 1.0000 |
| SPLIT TSW | 0.46 | 0.46 | 0.04 | 0.04 | 0.4571 | 0.4571 | 0.4571 | 1.0000 | 1.0000 |
| SPLIT TNW | 0.45 | 0.45 | 0.03 | 0.03 | 0.4459 | 0.4459 | 0.4459 | 1.0000 | 1.0000 |
| SPLIT TSE | 0.43 | 0.43 | 0.04 | 0.04 | 0.4280 | 0.4280 | 0.4280 | 1.0000 | 1.0000 |
| SPLIT TNE | 0.42 | 0.42 | 0.03 | 0.03 | 0.4168 | 0.4168 | 0.4168 | 1.0000 | 1.0000 |
| SPLIT TN1 | 0.37 | 0.37 | 0.03 | 0.03 | 0.3695 | 0.3695 | 0.3695 | 1.0000 | 1.0000 |
| SPLIT TN2 | 0.37 | 0.37 | 0.03 | 0.03 | 0.3685 | 0.3685 | 0.3685 | 1.0000 | 1.0000 |
| SPLIT TS1 | 0.38 | 0.38 | 0.03 | 0.03 | 0.3816 | 0.3816 | 0.3816 | 1.0000 | 1.0000 |
| SPLIT TS2 | 0.38 | 0.38 | 0.03 | 0.03 | 0.3806 | 0.3806 | 0.3806 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| SPLIT GSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GSW | 7395.653 | 5923.253 | 0.399689 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6608.35 | 6309.23 | 0.399689 | 25.93 | 16.88 | 0.00828910 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 6.4937 | 24.00 | 0.00811644 | 43.6988 | 4699.67 | 0.00 | 7394.39 | 5917.72 |
| SPLIT GSW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GSW | 7395.653 | 7395.653 | 0.399689 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | 7395.65 | 7395.65 | 0.399689 | 20.55 | 15.03 | 0.00838441 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.4937 | 21.10 | 0.00841312 | 53.9936 | 109.45 | 0.00 | 7405.37 | 7405.37 |
| SPLIT GSW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GSW | 7395.653 | 7395.653 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | 7395.65 | 7395.65 | 0.399689 | 20.55 | 15.03 | 0.00838441 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.4937 | 21.10 | 0.00841312 | 53.9936 | 109.45 | 0.00 | -999.00 | -999.00 |
| SPLIT GNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNW | 7171.630 | 5741.790 | 0.387246 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6409.26 | 6125.17 | 0.387246 | 25.96 | 16.89 | 0.00828337 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 6.7023 | 24.00 | 0.00810436 | 43.6343 | 4556.56 | 0.00 | 7170.41 | 5736.29 |
| SPLIT GNW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GNW | 7171.630 | 7171.630 | 0.387246 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7171.63 | 7171.63 | 0.387246 | 20.54 | 20.34 | 0.01493646 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.7023 | 21.28 | 0.01518064 | 95.3320 | 13.26 | 0.00 | 7181.05 | 7181.05 |
| SPLIT GNW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GNW | 7171.630 | 7171.630 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7171.63 | 7171.63 | 0.387246 | 20.54 | 20.34 | 0.01493646 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.7023 | 21.28 | 0.01518064 | 95.3320 | 13.26 | 0.00 | -999.00 | -999.00 |
| SPLIT OFFICE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT OFFICE | 8322.191 | 6660.980 | 0.458620 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 7576.48 | 7267.96 | 0.458620 | 26.00 | 16.88 | 0.00825992 | 12.80 | 11.59 | 0.00800000 | 37.46 | 0.01077266 | 22.39 | 8.3088 | 23.90 | 0.00803222 | 43.5109 | 5317.30 | 0.00 | 8320.78 | 6654.94 |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT OFFICE | 8322.191 | 8322.191 | 0.458620 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8322.19 | 8322.19 | 0.458620 | 20.40 | 14.79 | 0.00818376 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 8.3088 | 21.10 | 0.00809700 | 51.9910 | 408.38 | 0.00 | 8333.13 | 8333.13 |
| SPLIT OFFICE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT OFFICE | 8322.191 | 8322.191 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8322.19 | 8322.19 | 0.458620 | 20.40 | 14.79 | 0.00818376 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 8.3088 | 21.10 | 0.00809700 | 51.9910 | 408.38 | 0.00 | -999.00 | -999.00 |
| SPLIT GNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNE | 6893.717 | 5515.559 | 0.370495 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6166.00 | 5880.16 | 0.370495 | 26.01 | 16.92 | 0.00829782 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 7.0054 | 24.00 | 0.00811119 | 43.6707 | 4363.99 | 0.00 | 6892.54 | 5509.54 |
| SPLIT GNE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GNE | 6893.717 | 6893.717 | 0.370495 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6893.72 | 6893.72 | 0.370495 | 20.51 | 20.34 | 0.01495891 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.0054 | 21.29 | 0.01519027 | 95.3398 | 9.55 | 0.00 | 6902.78 | 6902.78 |
| SPLIT GNE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GNE | 6893.717 | 6893.717 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6893.72 | 6893.72 | 0.370495 | 20.51 | 20.34 | 0.01495891 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.0054 | 21.29 | 0.01519027 | 95.3398 | 9.55 | 0.00 | -999.00 | -999.00 |
| SPLIT GN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN1 | 6014.866 | 4812.567 | 0.318347 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5394.71 | 5115.63 | 0.318347 | 26.17 | 17.01 | 0.00833775 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 8.1529 | 24.00 | 0.00812138 | 43.7248 | 3764.03 | 0.00 | 6013.84 | 4800.86 |
| SPLIT GN1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GN1 | 6014.866 | 6014.866 | 0.318347 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6014.87 | 6014.87 | 0.318347 | 20.42 | 14.71 | 0.00809404 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 8.1529 | 22.32 | 0.01702219 | 99.9999 | 0.00 | 0.00 | 6022.77 | 6022.77 |
| SPLIT GN1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GN1 | 6014.866 | 6014.866 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6014.87 | 6014.87 | 0.318347 | 20.42 | 14.71 | 0.00809404 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 8.1529 | 22.32 | 0.01702219 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 |
| SPLIT GN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN2 | 6009.518 | 4808.050 | 0.318025 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5390.03 | 5110.90 | 0.318025 | 26.17 | 17.01 | 0.00833815 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 8.1612 | 24.00 | 0.00812157 | 43.7258 | 3760.30 | 0.00 | 6008.49 | 4796.28 |
| SPLIT GN2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GN2 | 6009.518 | 6009.518 | 0.318025 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6009.52 | 6009.52 | 0.318025 | 20.41 | 14.71 | 0.00809413 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 8.1612 | 22.33 | 0.01702367 | 99.9999 | 0.00 | 0.00 | 6017.41 | 6017.41 |
| SPLIT GN2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GN2 | 6009.518 | 6009.518 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6009.52 | 6009.52 | 0.318025 | 20.41 | 14.71 | 0.00809413 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 8.1612 | 22.33 | 0.01702367 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 |
| SPLIT GS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS1 | 6269.497 | 5017.288 | 0.331986 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5622.41 | 5318.91 | 0.331986 | 26.12 | 17.00 | 0.00835221 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 7.8180 | 24.00 | 0.00814671 | 43.8599 | 3921.95 | 0.00 | 6268.43 | 5005.38 |
| SPLIT GS1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GS1 | 6269.497 | 6269.497 | 0.331986 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6269.50 | 6269.50 | 0.331986 | 20.44 | 14.72 | 0.00809018 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.8180 | 21.61 | 0.00915345 | 56.8537 | 0.00 | 0.00 | 6277.74 | 6277.74 |
| SPLIT GS1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GS1 | 6269.497 | 6269.497 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6269.50 | 6269.50 | 0.331986 | 20.44 | 14.72 | 0.00809018 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.8180 | 21.61 | 0.00915345 | 56.8537 | 0.00 | 0.00 | -999.00 | -999.00 |
| SPLIT GS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS2 | 6315.171 | 5055.887 | 0.334741 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5662.35 | 5359.14 | 0.334741 | 26.11 | 17.00 | 0.00834903 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 7.7536 | 24.00 | 0.00814509 | 43.8513 | 3953.63 | 0.00 | 6314.10 | 5044.52 |
| SPLIT GS2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT GS2 | 6315.171 | 6315.171 | 0.334741 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6315.17 | 6315.17 | 0.334741 | 20.45 | 14.72 | 0.00808943 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.7536 | 21.55 | 0.00915345 | 57.0705 | 0.00 | 0.00 | 6323.47 | 6323.47 |
| SPLIT GS2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT GS2 | 6315.171 | 6315.171 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6315.17 | 6315.17 | 0.334741 | 20.45 | 14.72 | 0.00808943 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.7536 | 21.55 | 0.00915345 | 57.0705 | 0.00 | 0.00 | -999.00 | -999.00 |
| SPLIT MSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSW | 15426.351 | 12351.203 | 0.835589 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 13778.46 | 13153.44 | 0.835589 | 25.90 | 16.87 | 0.00828903 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 6.2123 | 24.00 | 0.00812434 | 43.7408 | 19636.43 | 0.00 | 15423.73 | 12337.76 |
| SPLIT MSW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MSW | 15426.351 | 15426.351 | 0.835589 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 16:40:00 | 15426.35 | 15426.35 | 0.835589 | 20.58 | 14.90 | 0.00823300 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.2123 | 21.10 | 0.00821854 | 52.7611 | 1177.80 | 0.00 | 15446.62 | 15446.62 |
| SPLIT MSW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MSW | 15426.351 | 15426.351 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 16:40:00 | 15426.35 | 15426.35 | 0.835589 | 20.58 | 14.90 | 0.00823300 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.2123 | 21.10 | 0.00821854 | 52.7611 | 1177.80 | 0.00 | -999.00 | -999.00 |
| SPLIT MNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNW | 14939.321 | 11955.318 | 0.808232 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 13346.48 | 12749.15 | 0.808232 | 25.93 | 16.88 | 0.00828554 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 6.4226 | 24.00 | 0.00811465 | 43.6891 | 19005.41 | 0.00 | 14936.78 | 11944.45 |
| SPLIT MNW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MNW | 14939.321 | 14939.321 | 0.808232 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14939.32 | 14939.32 | 0.808232 | 20.56 | 15.97 | 0.00943923 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.4226 | 21.10 | 0.00953965 | 61.1133 | 660.38 | 0.00 | 14958.95 | 14958.95 |
| SPLIT MNW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MNW | 14939.321 | 14939.321 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14939.32 | 14939.32 | 0.808232 | 20.56 | 15.97 | 0.00943923 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.4226 | 21.10 | 0.00953965 | 61.1133 | 660.38 | 0.00 | -999.00 | -999.00 |
| SPLIT MSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSE | 14751.623 | 11814.204 | 0.794723 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 13188.32 | 12555.63 | 0.794723 | 25.94 | 16.90 | 0.00830740 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 6.5317 | 24.00 | 0.00813493 | 43.7972 | 18693.29 | 0.00 | 14749.11 | 11802.19 |
| SPLIT MSE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MSE | 14751.623 | 14751.623 | 0.794723 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14751.62 | 14751.62 | 0.794723 | 20.55 | 14.89 | 0.00823723 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.5317 | 21.10 | 0.00822009 | 52.7709 | 1169.16 | 0.00 | 14771.01 | 14771.01 |
| SPLIT MSE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MSE | 14751.623 | 14751.623 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14751.62 | 14751.62 | 0.794723 | 20.55 | 14.89 | 0.00823723 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.5317 | 21.10 | 0.00822009 | 52.7709 | 1169.16 | 0.00 | -999.00 | -999.00 |
| SPLIT MNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNE | 14263.490 | 11417.663 | 0.767504 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 12754.84 | 12153.11 | 0.767504 | 25.97 | 16.91 | 0.00830268 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 6.7634 | 24.00 | 0.00812332 | 43.7352 | 18066.64 | 0.00 | 14261.06 | 11405.63 |
| SPLIT MNE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MNE | 14263.490 | 14263.490 | 0.767504 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | 14263.49 | 14263.49 | 0.767504 | 20.53 | 15.96 | 0.00944975 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.7634 | 21.10 | 0.00955367 | 61.2017 | 652.48 | 0.00 | 14282.23 | 14282.23 |
| SPLIT MNE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MNE | 14263.490 | 14263.490 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | 14263.49 | 14263.49 | 0.767504 | 20.53 | 15.96 | 0.00944975 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.7634 | 21.10 | 0.00955367 | 61.2017 | 652.48 | 0.00 | -999.00 | -999.00 |
| SPLIT MN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN1 | 12398.661 | 9926.692 | 0.657268 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 11116.96 | 10537.04 | 0.657268 | 26.14 | 17.00 | 0.00834000 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 7.8977 | 24.00 | 0.00813118 | 43.7769 | 15535.18 | 0.00 | 12396.55 | 9904.49 |
| SPLIT MN1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MN1 | 12398.661 | 12398.661 | 0.657268 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 12398.66 | 12398.66 | 0.657268 | 20.44 | 14.72 | 0.00809110 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.8977 | 21.65 | 0.01595813 | 97.8468 | 0.00 | 0.00 | 12414.95 | 12414.95 |
| SPLIT MN1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MN1 | 12398.661 | 12398.661 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 12398.66 | 12398.66 | 0.657268 | 20.44 | 14.72 | 0.00809110 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.8977 | 21.65 | 0.01595813 | 97.8468 | 0.00 | 0.00 | -999.00 | -999.00 |
| SPLIT MN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN2 | 12386.473 | 9916.399 | 0.656534 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 11106.30 | 10526.26 | 0.656534 | 26.14 | 17.00 | 0.00834044 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 7.9065 | 24.00 | 0.00813140 | 43.7781 | 15518.11 | 0.00 | 12384.36 | 9894.06 |
| SPLIT MN2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MN2 | 12386.473 | 12386.473 | 0.656534 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 12386.47 | 12386.47 | 0.656534 | 20.44 | 14.72 | 0.00809120 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.9065 | 21.65 | 0.01595866 | 97.8470 | 0.00 | 0.00 | 12402.75 | 12402.75 |
| SPLIT MN2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MN2 | 12386.473 | 12386.473 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 12386.47 | 12386.47 | 0.656534 | 20.44 | 14.72 | 0.00809120 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.9065 | 21.65 | 0.01595866 | 97.8470 | 0.00 | 0.00 | -999.00 | -999.00 |
| SPLIT MS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS1 | 12953.643 | 10363.390 | 0.687562 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 11611.58 | 10986.20 | 0.687562 | 26.09 | 16.99 | 0.00835053 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 7.5497 | 24.00 | 0.00815252 | 43.8907 | 16230.06 | 0.00 | 12951.44 | 10352.53 |
| SPLIT MS1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MS1 | 12953.643 | 12953.643 | 0.687562 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:40:00 | 12953.64 | 12953.64 | 0.687562 | 20.47 | 15.15 | 0.00855401 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.5497 | 21.10 | 0.00860619 | 55.2159 | 151.43 | 0.00 | 12970.67 | 12970.67 |
| SPLIT MS1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MS1 | 12953.643 | 12953.643 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:40:00 | 12953.64 | 12953.64 | 0.687562 | 20.47 | 15.15 | 0.00855401 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.5497 | 21.10 | 0.00860619 | 55.2159 | 151.43 | 0.00 | -999.00 | -999.00 |
| SPLIT MS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS2 | 12941.473 | 10366.000 | 0.686818 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 11600.96 | 10975.34 | 0.686818 | 26.09 | 16.99 | 0.00835104 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 7.5579 | 24.00 | 0.00815283 | 43.8924 | 16213.01 | 0.00 | 12939.27 | 10355.30 |
| SPLIT MS2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT MS2 | 12941.473 | 12941.473 | 0.686818 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 12941.47 | 12941.47 | 0.686818 | 20.47 | 15.15 | 0.00855458 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.5579 | 21.10 | 0.00860680 | 55.2198 | 150.92 | 0.00 | 12958.48 | 12958.48 |
| SPLIT MS2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT MS2 | 12941.473 | 12941.473 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 12941.47 | 12941.47 | 0.686818 | 20.47 | 15.15 | 0.00855458 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.5579 | 21.10 | 0.00860680 | 55.2198 | 150.92 | 0.00 | -999.00 | -999.00 |
| SPLIT TSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSW | 8384.285 | 6714.408 | 0.457144 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 7479.97 | 7156.41 | 0.457144 | 25.82 | 16.83 | 0.00827372 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 5.6775 | 24.00 | 0.00812315 | 43.7345 | 5366.58 | 0.00 | 8382.86 | 6706.75 |
| SPLIT TSW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TSW | 8384.285 | 8384.285 | 0.457144 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8384.28 | 8384.28 | 0.457144 | 20.62 | 14.86 | 0.00816993 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 5.6775 | 21.10 | 0.00811073 | 52.0778 | 712.83 | 0.00 | 8395.30 | 8395.30 |
| SPLIT TSW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TSW | 8384.285 | 8384.285 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8384.28 | 8384.28 | 0.457144 | 20.62 | 14.86 | 0.00816993 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 5.6775 | 21.10 | 0.00811073 | 52.0778 | 712.83 | 0.00 | -999.00 | -999.00 |
| SPLIT TNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNW | 8183.872 | 6551.868 | 0.445881 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 7302.21 | 6990.26 | 0.445881 | 25.84 | 16.84 | 0.00827054 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 5.8210 | 24.00 | 0.00811573 | 43.6949 | 5237.17 | 0.00 | 8182.48 | 6544.29 |
| SPLIT TNW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TNW | 8183.872 | 8183.872 | 0.445881 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8183.87 | 8183.87 | 0.445881 | 20.61 | 15.31 | 0.00867632 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 5.8210 | 21.10 | 0.00864683 | 55.4716 | 574.39 | 0.00 | 8194.63 | 8194.63 |
| SPLIT TNW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TNW | 8183.872 | 8183.872 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8183.87 | 8183.87 | 0.445881 | 20.61 | 15.31 | 0.00867632 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 5.8210 | 21.10 | 0.00864683 | 55.4716 | 574.39 | 0.00 | -999.00 | -999.00 |
| SPLIT TSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSE | 7900.355 | 6326.158 | 0.428046 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 7056.01 | 6730.54 | 0.428046 | 25.88 | 16.87 | 0.00829380 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 6.0635 | 24.00 | 0.00813362 | 43.7902 | 5030.58 | 0.00 | 7899.01 | 6319.32 |
| SPLIT TSE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TSE | 7900.355 | 7900.355 | 0.428046 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 7900.35 | 7900.35 | 0.428046 | 20.59 | 14.85 | 0.00817435 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.0635 | 21.10 | 0.00811115 | 52.0805 | 710.17 | 0.00 | 7910.74 | 7910.74 |
| SPLIT TSE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TSE | 7900.355 | 7900.355 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 7900.35 | 7900.35 | 0.428046 | 20.59 | 14.85 | 0.00817435 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.0635 | 21.10 | 0.00811115 | 52.0805 | 710.17 | 0.00 | -999.00 | -999.00 |
| SPLIT TNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNE | 7698.661 | 6162.725 | 0.416802 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6876.87 | 6564.04 | 0.416802 | 25.90 | 16.87 | 0.00828999 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 6.2271 | 24.00 | 0.00812495 | 43.7439 | 4900.43 | 0.00 | 7697.35 | 6157.24 |
| SPLIT TNE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TNE | 7698.661 | 7698.661 | 0.416802 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 7698.66 | 7698.66 | 0.416802 | 20.58 | 15.30 | 0.00868084 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.2271 | 21.10 | 0.00864945 | 55.4882 | 571.90 | 0.00 | 7708.78 | 7708.78 |
| SPLIT TNE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TNE | 7698.661 | 7698.661 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 7698.66 | 7698.66 | 0.416802 | 20.58 | 15.30 | 0.00868084 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.2271 | 21.10 | 0.00864945 | 55.4882 | 571.90 | 0.00 | -999.00 | -999.00 |
| SPLIT TN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN1 | 6885.106 | 5512.481 | 0.369527 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6159.76 | 5868.80 | 0.369527 | 26.01 | 16.92 | 0.00830389 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 7.0237 | 24.00 | 0.00811719 | 43.7025 | 4354.89 | 0.00 | 6883.93 | 5506.28 |
| SPLIT TN1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TN1 | 6885.106 | 6885.106 | 0.369527 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6885.11 | 6885.11 | 0.369527 | 20.51 | 15.65 | 0.00910190 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.0237 | 21.10 | 0.00914601 | 58.6280 | 232.98 | 0.00 | 6894.15 | 6894.15 |
| SPLIT TN1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TN1 | 6885.106 | 6885.106 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6885.11 | 6885.11 | 0.369527 | 20.51 | 15.65 | 0.00910190 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.0237 | 21.10 | 0.00914601 | 58.6280 | 232.98 | 0.00 | -999.00 | -999.00 |
| SPLIT TN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN2 | 6868.735 | 5498.736 | 0.368543 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6145.42 | 5854.41 | 0.368543 | 26.02 | 16.93 | 0.00830475 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 7.0425 | 24.00 | 0.00811758 | 43.7046 | 4343.55 | 0.00 | 6867.57 | 5492.50 |
| SPLIT TN2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TN2 | 6868.735 | 6868.735 | 0.368543 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6868.73 | 6868.73 | 0.368543 | 20.51 | 15.65 | 0.00910222 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.0425 | 21.10 | 0.00914636 | 58.6302 | 232.88 | 0.00 | 6877.76 | 6877.76 |
| SPLIT TN2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TN2 | 6868.735 | 6868.735 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6868.73 | 6868.73 | 0.368543 | 20.51 | 15.65 | 0.00910222 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.0425 | 21.10 | 0.00914636 | 58.6302 | 232.88 | 0.00 | -999.00 | -999.00 |
| SPLIT TS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS1 | 7103.475 | 5689.433 | 0.381595 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6353.98 | 6047.55 | 0.381595 | 25.98 | 16.92 | 0.00830996 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 6.8016 | 24.00 | 0.00813004 | 43.7710 | 4494.05 | 0.00 | 7102.27 | 5683.20 |
| SPLIT TS1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TS1 | 7103.475 | 7103.475 | 0.381595 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 18:20:00 | 7103.48 | 7103.48 | 0.381595 | 20.53 | 14.84 | 0.00818609 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.8016 | 21.10 | 0.00815035 | 52.3290 | 359.80 | 0.00 | 7112.81 | 7112.81 |
| SPLIT TS1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TS1 | 7103.475 | 7103.475 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 18:20:00 | 7103.48 | 7103.48 | 0.381595 | 20.53 | 14.84 | 0.00818609 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.8016 | 21.10 | 0.00815035 | 52.3290 | 359.80 | 0.00 | -999.00 | -999.00 |
| SPLIT TS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS2 | 7087.265 | 5675.797 | 0.380617 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6339.80 | 6033.24 | 0.380617 | 25.99 | 16.92 | 0.00831087 | 12.80 | 11.59 | 0.00800000 | 39.02 | 0.01077531 | 22.82 | 6.8191 | 24.00 | 0.00813052 | 43.7736 | 4482.77 | 0.00 | 7086.06 | 5669.53 |
| SPLIT TS2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoopHVAC | SPLIT TS2 | 7087.265 | 7087.265 | 0.380617 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7087.26 | 7087.26 | 0.380617 | 20.53 | 14.84 | 0.00818630 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.8191 | 21.10 | 0.00815040 | 52.3293 | 359.70 | 0.00 | 7096.58 | 7096.58 |
| SPLIT TS2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | SPLIT TS2 | 7087.265 | 7087.265 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7087.26 | 7087.26 | 0.380617 | 20.53 | 14.84 | 0.00818630 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.8191 | 21.10 | 0.00815040 | 52.3293 | 359.70 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| SPLIT GSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7395.653 | 5923.253 | 0.399689 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2490 | 1004.8586 | 1.2036 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.399689 | 0.48106313 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6608.35 | 6309.23 | 0.8935 | 0.48106313 | 0.399689 | 25.93 | 16.88 | 0.00828910 | 47189.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 447.694 | 6160.65 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 6.4937 | 24.05 | 0.00811644 | 24.00 | 0.00811644 | 43.6988 | 4699.67 | 0.00 | 7394.39 | 5917.72 | 0.46206477 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.15 | 14.02 | 0.00993166 | 39319.4 | |
| SPLIT GSW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 7395.653 | 7395.653 | 0.399689 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.399689 | 0.48106313 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | Sensible | 7395.65 | 7395.65 | 1.0000 | 0.48106313 | 0.399689 | 20.55 | 15.03 | 0.00838441 | 41943.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7395.65 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 6.4937 | 21.10 | 0.00833100 | 21.10 | 0.00841312 | 53.9936 | 109.45 | 0.00 | 7405.37 | 7405.37 | 0.47256260 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.46 | 20.67 | 0.00875166 | 59114.8 | |
| SPLIT GSW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7395.653 | 7395.653 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.399689 | 0.48106313 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | Sensible | 7395.65 | 7395.65 | 1.0000 | 0.48106313 | 0.399689 | 20.55 | 15.03 | 0.00838441 | 41943.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7395.65 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 6.4937 | 21.10 | 0.00833100 | 21.10 | 0.00841312 | 53.9936 | 109.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7171.630 | 5741.790 | 0.387246 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2384 | 1004.8586 | 1.2036 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.387246 | 0.46608769 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6409.26 | 6125.17 | 0.8937 | 0.46608769 | 0.387246 | 25.96 | 16.89 | 0.00828337 | 47205.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 433.758 | 5975.50 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 6.7023 | 24.05 | 0.00810436 | 24.00 | 0.00810436 | 43.6343 | 4556.56 | 0.00 | 7170.41 | 5736.29 | 0.44768075 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.15 | 14.02 | 0.00992866 | 39305.6 | |
| SPLIT GNW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 7171.630 | 7171.630 | 0.387246 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.387246 | 0.46608769 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 7171.63 | 7171.63 | 1.0000 | 0.46608769 | 0.387246 | 20.54 | 20.34 | 0.01493646 | 58561.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7171.63 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 6.7023 | 21.10 | 0.01535191 | 21.28 | 0.01518064 | 95.3320 | 13.26 | 0.00 | 7181.05 | 7181.05 | 0.45785177 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.47 | 20.67 | 0.00875166 | 59128.3 | |
| SPLIT GNW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7171.630 | 7171.630 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.387246 | 0.46608769 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 7171.63 | 7171.63 | 1.0000 | 0.46608769 | 0.387246 | 20.54 | 20.34 | 0.01493646 | 58561.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7171.63 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 6.7023 | 21.10 | 0.01535191 | 21.28 | 0.01518064 | 95.3320 | 13.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT OFFICE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8322.191 | 6660.980 | 0.458620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1948 | 1004.8586 | 1.2036 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.458620 | 0.55199259 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | Sensible | 7576.48 | 7267.96 | 0.9104 | 0.55199259 | 0.458620 | 26.00 | 16.88 | 0.00825992 | 47180.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 513.704 | 7062.77 | 37.46 | 0.01077266 | 22.39 | 0.03810604 | 8.3088 | 23.96 | 0.00803222 | 23.90 | 0.00803222 | 43.5109 | 5317.30 | 0.00 | 8320.78 | 6654.94 | 0.53019305 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.40 | 14.14 | 0.00995278 | 39628.5 | |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 8322.191 | 8322.191 | 0.458620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.458620 | 0.55199259 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8322.19 | 8322.19 | 1.0000 | 0.55199259 | 0.458620 | 20.40 | 14.79 | 0.00818376 | 41278.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8322.19 | 12.70 | 0.00915345 | 12.70 | 0.03810604 | 8.3088 | 21.10 | 0.00809588 | 21.10 | 0.00809700 | 51.9910 | 408.38 | 0.00 | 8333.13 | 8333.13 | 0.54223871 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.16 | 20.58 | 0.00875166 | 58812.1 | |
| SPLIT OFFICE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8322.191 | 8322.191 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.458620 | 0.55199259 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8322.19 | 8322.19 | 1.0000 | 0.55199259 | 0.458620 | 20.40 | 14.79 | 0.00818376 | 41278.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8322.19 | 12.70 | 0.00915345 | 12.70 | 0.03810604 | 8.3088 | 21.10 | 0.00809588 | 21.10 | 0.00809700 | 51.9910 | 408.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6893.717 | 5515.559 | 0.370495 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2652 | 1004.8586 | 1.2036 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.370495 | 0.44592566 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6166.00 | 5880.16 | 0.8944 | 0.44592566 | 0.370495 | 26.01 | 16.92 | 0.00829782 | 47286.2 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 414.994 | 5751.00 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 7.0054 | 24.05 | 0.00811119 | 24.00 | 0.00811119 | 43.6707 | 4363.99 | 0.00 | 6892.54 | 5509.54 | 0.42831497 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.10 | 13.99 | 0.00991867 | 39230.2 | |
| SPLIT GNE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6893.717 | 6893.717 | 0.370495 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.370495 | 0.44592566 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6893.72 | 6893.72 | 1.0000 | 0.44592566 | 0.370495 | 20.51 | 20.34 | 0.01495891 | 58592.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6893.72 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 7.0054 | 21.10 | 0.01539625 | 21.29 | 0.01519027 | 95.3398 | 9.55 | 0.00 | 6902.78 | 6902.78 | 0.43804601 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.54 | 20.70 | 0.00875166 | 59202.2 | |
| SPLIT GNE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6893.717 | 6893.717 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.370495 | 0.44592566 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6893.72 | 6893.72 | 1.0000 | 0.44592566 | 0.370495 | 20.51 | 20.34 | 0.01495891 | 58592.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6893.72 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 7.0054 | 21.10 | 0.01539625 | 21.29 | 0.01519027 | 95.3398 | 9.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6014.866 | 4812.567 | 0.318347 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3395 | 1004.8586 | 1.2036 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.318347 | 0.38316118 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5394.71 | 5115.63 | 0.8969 | 0.38316118 | 0.318347 | 26.17 | 17.01 | 0.00833775 | 47554.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 356.583 | 5038.13 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 8.1529 | 24.04 | 0.00812138 | 24.00 | 0.00812138 | 43.7248 | 3764.03 | 0.00 | 6013.84 | 4800.86 | 0.36802921 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.92 | 13.90 | 0.00989241 | 38981.7 | |
| SPLIT GN1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6014.866 | 6014.866 | 0.318347 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.318347 | 0.38316118 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6014.87 | 6014.87 | 1.0000 | 0.38316118 | 0.318347 | 20.42 | 14.71 | 0.00809404 | 41063.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6014.87 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 8.1529 | 21.10 | 0.00800000 | 22.32 | 0.01702219 | 99.9999 | 0.00 | 0.00 | 6022.77 | 6022.77 | 0.37639060 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.78 | 20.77 | 0.00875166 | 59445.5 | |
| SPLIT GN1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6014.866 | 6014.866 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.318347 | 0.38316118 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6014.87 | 6014.87 | 1.0000 | 0.38316118 | 0.318347 | 20.42 | 14.71 | 0.00809404 | 41063.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6014.87 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 8.1529 | 21.10 | 0.00800000 | 22.32 | 0.01702219 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6009.518 | 4808.050 | 0.318025 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3402 | 1004.8586 | 1.2036 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.318025 | 0.38277345 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5390.03 | 5110.90 | 0.8969 | 0.38277345 | 0.318025 | 26.17 | 17.01 | 0.00833815 | 47556.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 356.222 | 5033.81 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 8.1612 | 24.04 | 0.00812157 | 24.00 | 0.00812157 | 43.7258 | 3760.30 | 0.00 | 6008.49 | 4796.28 | 0.36765679 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.92 | 13.89 | 0.00989193 | 38979.7 | |
| SPLIT GN2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6009.518 | 6009.518 | 0.318025 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.318025 | 0.38277345 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6009.52 | 6009.52 | 1.0000 | 0.38277345 | 0.318025 | 20.41 | 14.71 | 0.00809413 | 41063.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6009.52 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 8.1612 | 21.10 | 0.00800000 | 22.33 | 0.01702367 | 99.9999 | 0.00 | 0.00 | 6017.41 | 6017.41 | 0.37600972 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.78 | 20.77 | 0.00875166 | 59447.5 | |
| SPLIT GN2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6009.518 | 6009.518 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.318025 | 0.38277345 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6009.52 | 6009.52 | 1.0000 | 0.38277345 | 0.318025 | 20.41 | 14.71 | 0.00809413 | 41063.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6009.52 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 8.1612 | 21.10 | 0.00800000 | 22.33 | 0.01702367 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6269.497 | 5017.288 | 0.331986 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3663 | 1004.8586 | 1.2036 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.331986 | 0.39957700 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5622.41 | 5318.91 | 0.8968 | 0.39957700 | 0.331986 | 26.12 | 17.00 | 0.00835221 | 47543.7 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 371.860 | 5250.54 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 7.8180 | 24.04 | 0.00814671 | 24.00 | 0.00814671 | 43.8599 | 3921.95 | 0.00 | 6268.43 | 5005.38 | 0.38379673 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.92 | 13.90 | 0.00989436 | 38989.7 | |
| SPLIT GS1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6269.497 | 6269.497 | 0.331986 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.331986 | 0.39957700 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6269.50 | 6269.50 | 1.0000 | 0.39957700 | 0.331986 | 20.44 | 14.72 | 0.00809018 | 41082.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6269.50 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 7.8180 | 21.10 | 0.00800000 | 21.61 | 0.00915345 | 56.8537 | 0.00 | 0.00 | 6277.74 | 6277.74 | 0.39251635 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.77 | 20.76 | 0.00875166 | 59437.7 | |
| SPLIT GS1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6269.497 | 6269.497 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.331986 | 0.39957700 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6269.50 | 6269.50 | 1.0000 | 0.39957700 | 0.331986 | 20.44 | 14.72 | 0.00809018 | 41082.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6269.50 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 7.8180 | 21.10 | 0.00800000 | 21.61 | 0.00915345 | 56.8537 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6315.171 | 5055.887 | 0.334741 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3604 | 1004.8586 | 1.2036 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.334741 | 0.40289281 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5662.35 | 5359.14 | 0.8966 | 0.40289281 | 0.334741 | 26.11 | 17.00 | 0.00834903 | 47526.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 374.946 | 5287.40 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 7.7536 | 24.04 | 0.00814509 | 24.00 | 0.00814509 | 43.8513 | 3953.63 | 0.00 | 6314.10 | 5044.52 | 0.38698159 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.93 | 13.90 | 0.00989836 | 39006.1 | |
| SPLIT GS2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6315.171 | 6315.171 | 0.334741 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.334741 | 0.40289281 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6315.17 | 6315.17 | 1.0000 | 0.40289281 | 0.334741 | 20.45 | 14.72 | 0.00808943 | 41086.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6315.17 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 7.7536 | 21.10 | 0.00800000 | 21.55 | 0.00915345 | 57.0705 | 0.00 | 0.00 | 6323.47 | 6323.47 | 0.39577357 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.76 | 20.76 | 0.00875166 | 59421.6 | |
| SPLIT GS2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6315.171 | 6315.171 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.334741 | 0.40289281 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6315.17 | 6315.17 | 1.0000 | 0.40289281 | 0.334741 | 20.45 | 14.72 | 0.00808943 | 41086.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6315.17 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 7.7536 | 21.10 | 0.00800000 | 21.55 | 0.00915345 | 57.0705 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 15426.351 | 12351.203 | 0.835589 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2489 | 1004.8586 | 1.2036 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.835589 | 1.00571019 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 13778.46 | 13153.44 | 0.8932 | 1.00571019 | 0.835589 | 25.90 | 16.87 | 0.00828903 | 47150.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 935.949 | 12842.51 | 39.02 | 0.01077531 | 22.82 | 0.05190911 | 6.2123 | 24.05 | 0.00812434 | 24.00 | 0.00812434 | 43.7408 | 19636.43 | 0.00 | 15423.73 | 12337.76 | 0.96599224 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.19 | 14.04 | 0.00993213 | 39355.7 | |
| SPLIT MSW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 15426.351 | 15426.351 | 0.835589 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.835589 | 1.00571019 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 16:40:00 | Sensible | 15426.35 | 15426.35 | 1.0000 | 1.00571019 | 0.835589 | 20.58 | 14.90 | 0.00823300 | 41583.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15426.35 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 6.2123 | 21.10 | 0.00817203 | 21.10 | 0.00821854 | 52.7611 | 1177.80 | 0.00 | 15446.62 | 15446.62 | 0.98793898 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.42 | 20.66 | 0.00875166 | 59079.3 | |
| SPLIT MSW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15426.351 | 15426.351 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.835589 | 1.00571019 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 16:40:00 | Sensible | 15426.35 | 15426.35 | 1.0000 | 1.00571019 | 0.835589 | 20.58 | 14.90 | 0.00823300 | 41583.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15426.35 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 6.2123 | 21.10 | 0.00817203 | 21.10 | 0.00821854 | 52.7611 | 1177.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14939.321 | 11955.318 | 0.808232 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2424 | 1004.8586 | 1.2036 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.808232 | 0.97278368 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 13346.48 | 12749.15 | 0.8934 | 0.97278368 | 0.808232 | 25.93 | 16.88 | 0.00828554 | 47171.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 905.307 | 12441.17 | 39.02 | 0.01077531 | 22.82 | 0.05190911 | 6.4226 | 24.05 | 0.00811465 | 24.00 | 0.00811465 | 43.6891 | 19005.41 | 0.00 | 14936.78 | 11944.45 | 0.93436608 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.17 | 14.03 | 0.00992902 | 39336.4 | |
| SPLIT MNW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 14939.321 | 14939.321 | 0.808232 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.808232 | 0.97278368 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14939.32 | 14939.32 | 1.0000 | 0.97278368 | 0.808232 | 20.56 | 15.97 | 0.00943923 | 44628.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14939.32 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 6.4226 | 21.10 | 0.00945884 | 21.10 | 0.00953965 | 61.1133 | 660.38 | 0.00 | 14958.95 | 14958.95 | 0.95559429 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.44 | 20.66 | 0.00875166 | 59098.2 | |
| SPLIT MNW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14939.321 | 14939.321 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.808232 | 0.97278368 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14939.32 | 14939.32 | 1.0000 | 0.97278368 | 0.808232 | 20.56 | 15.97 | 0.00943923 | 44628.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14939.32 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 6.4226 | 21.10 | 0.00945884 | 21.10 | 0.00953965 | 61.1133 | 660.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14751.623 | 11814.204 | 0.794723 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2830 | 1004.8586 | 1.2036 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.794723 | 0.95652501 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 13188.32 | 12555.63 | 0.8940 | 0.95652501 | 0.794723 | 25.94 | 16.90 | 0.00830740 | 47242.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 890.176 | 12298.14 | 39.02 | 0.01077531 | 22.82 | 0.05190911 | 6.5317 | 24.05 | 0.00813493 | 24.00 | 0.00813493 | 43.7972 | 18693.29 | 0.00 | 14749.11 | 11802.19 | 0.91874950 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.11 | 14.00 | 0.00992706 | 39268.9 | |
| SPLIT MSE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 14751.623 | 14751.623 | 0.794723 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.794723 | 0.95652501 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14751.62 | 14751.62 | 1.0000 | 0.95652501 | 0.794723 | 20.55 | 14.89 | 0.00823723 | 41566.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14751.62 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 6.5317 | 21.10 | 0.00817320 | 21.10 | 0.00822009 | 52.7709 | 1169.16 | 0.00 | 14771.01 | 14771.01 | 0.93962291 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.51 | 20.68 | 0.00875166 | 59164.2 | |
| SPLIT MSE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14751.623 | 14751.623 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.794723 | 0.95652501 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14751.62 | 14751.62 | 1.0000 | 0.95652501 | 0.794723 | 20.55 | 14.89 | 0.00823723 | 41566.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14751.62 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 6.5317 | 21.10 | 0.00817320 | 21.10 | 0.00822009 | 52.7709 | 1169.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14263.490 | 11417.663 | 0.767504 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2743 | 1004.8586 | 1.2036 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.767504 | 0.92376453 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 12754.84 | 12153.11 | 0.8942 | 0.92376453 | 0.767504 | 25.97 | 16.91 | 0.00830268 | 47264.2 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 859.688 | 11895.15 | 39.02 | 0.01077531 | 22.82 | 0.05190911 | 6.7634 | 24.05 | 0.00812332 | 24.00 | 0.00812332 | 43.7352 | 18066.64 | 0.00 | 14261.06 | 11405.63 | 0.88728282 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.10 | 14.00 | 0.00992289 | 39249.7 | |
| SPLIT MNE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 14263.490 | 14263.490 | 0.767504 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.767504 | 0.92376453 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | Sensible | 14263.49 | 14263.49 | 1.0000 | 0.92376453 | 0.767504 | 20.53 | 15.96 | 0.00944975 | 44625.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14263.49 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 6.7634 | 21.10 | 0.00947125 | 21.10 | 0.00955367 | 61.2017 | 652.48 | 0.00 | 14282.23 | 14282.23 | 0.90744133 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.52 | 20.69 | 0.00875166 | 59183.1 | |
| SPLIT MNE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14263.490 | 14263.490 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.767504 | 0.92376453 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | Sensible | 14263.49 | 14263.49 | 1.0000 | 0.92376453 | 0.767504 | 20.53 | 15.96 | 0.00944975 | 44625.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14263.49 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 6.7634 | 21.10 | 0.00947125 | 21.10 | 0.00955367 | 61.2017 | 652.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12398.661 | 9926.692 | 0.657268 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3436 | 1004.8586 | 1.2036 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.657268 | 0.79108427 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 11116.96 | 10537.04 | 0.8966 | 0.79108427 | 0.657268 | 26.14 | 17.00 | 0.00834000 | 47525.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 736.211 | 10380.75 | 39.02 | 0.01077531 | 22.82 | 0.05190911 | 7.8977 | 24.04 | 0.00813118 | 24.00 | 0.00813118 | 43.7769 | 15535.18 | 0.00 | 12396.55 | 9904.49 | 0.75984242 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.93 | 13.90 | 0.00989876 | 39007.8 | |
| SPLIT MN1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 12398.661 | 12398.661 | 0.657268 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.657268 | 0.79108427 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 12398.66 | 12398.66 | 1.0000 | 0.79108427 | 0.657268 | 20.44 | 14.72 | 0.00809110 | 41078.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12398.66 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 7.8977 | 21.10 | 0.00800000 | 21.65 | 0.01595813 | 97.8468 | 0.00 | 0.00 | 12414.95 | 12414.95 | 0.77710556 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.76 | 20.76 | 0.00875166 | 59420.0 | |
| SPLIT MN1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12398.661 | 12398.661 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.657268 | 0.79108427 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 12398.66 | 12398.66 | 1.0000 | 0.79108427 | 0.657268 | 20.44 | 14.72 | 0.00809110 | 41078.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12398.66 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 7.8977 | 21.10 | 0.00800000 | 21.65 | 0.01595813 | 97.8468 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12386.473 | 9916.399 | 0.656534 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3445 | 1004.8586 | 1.2036 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.656534 | 0.79020079 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 11106.30 | 10526.26 | 0.8966 | 0.79020079 | 0.656534 | 26.14 | 17.00 | 0.00834044 | 47527.7 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 735.389 | 10370.91 | 39.02 | 0.01077531 | 22.82 | 0.05190911 | 7.9065 | 24.04 | 0.00813140 | 24.00 | 0.00813140 | 43.7781 | 15518.11 | 0.00 | 12384.36 | 9894.06 | 0.75899384 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.93 | 13.90 | 0.00989823 | 39005.6 | |
| SPLIT MN2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 12386.473 | 12386.473 | 0.656534 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.656534 | 0.79020079 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 12386.47 | 12386.47 | 1.0000 | 0.79020079 | 0.656534 | 20.44 | 14.72 | 0.00809120 | 41077.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12386.47 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 7.9065 | 21.10 | 0.00800000 | 21.65 | 0.01595866 | 97.8470 | 0.00 | 0.00 | 12402.75 | 12402.75 | 0.77623770 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.76 | 20.76 | 0.00875166 | 59422.1 | |
| SPLIT MN2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12386.473 | 12386.473 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.656534 | 0.79020079 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 12386.47 | 12386.47 | 1.0000 | 0.79020079 | 0.656534 | 20.44 | 14.72 | 0.00809120 | 41077.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12386.47 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 7.9065 | 21.10 | 0.00800000 | 21.65 | 0.01595866 | 97.8470 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12953.643 | 10363.390 | 0.687562 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3632 | 1004.8586 | 1.2036 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.687562 | 0.82754614 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 11611.58 | 10986.20 | 0.8964 | 0.82754614 | 0.687562 | 26.09 | 16.99 | 0.00835053 | 47501.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 770.144 | 10841.43 | 39.02 | 0.01077531 | 22.82 | 0.05190911 | 7.5497 | 24.04 | 0.00815252 | 24.00 | 0.00815252 | 43.8907 | 16230.06 | 0.00 | 12951.44 | 10352.53 | 0.79486433 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.94 | 13.91 | 0.00990272 | 39028.5 | |
| SPLIT MS1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 12953.643 | 12953.643 | 0.687562 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.687562 | 0.82754614 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:40:00 | Sensible | 12953.64 | 12953.64 | 1.0000 | 0.82754614 | 0.687562 | 20.47 | 15.15 | 0.00855401 | 42283.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12953.64 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 7.5497 | 21.10 | 0.00850506 | 21.10 | 0.00860619 | 55.2159 | 151.43 | 0.00 | 12970.67 | 12970.67 | 0.81292315 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.74 | 20.75 | 0.00875166 | 59399.7 | |
| SPLIT MS1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12953.643 | 12953.643 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.687562 | 0.82754614 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:40:00 | Sensible | 12953.64 | 12953.64 | 1.0000 | 0.82754614 | 0.687562 | 20.47 | 15.15 | 0.00855401 | 42283.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12953.64 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 7.5497 | 21.10 | 0.00850506 | 21.10 | 0.00860619 | 55.2159 | 151.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12941.473 | 10366.000 | 0.686818 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3642 | 1004.8586 | 1.2036 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.686818 | 0.82665109 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 11600.96 | 10975.34 | 0.8964 | 0.82665109 | 0.686818 | 26.09 | 16.99 | 0.00835104 | 47503.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 769.311 | 10831.65 | 39.02 | 0.01077531 | 22.82 | 0.05190911 | 7.5579 | 24.04 | 0.00815283 | 24.00 | 0.00815283 | 43.8924 | 16213.01 | 0.00 | 12939.27 | 10355.30 | 0.79400462 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.92 | 13.91 | 0.00990871 | 39026.2 | |
| SPLIT MS2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 12941.473 | 12941.473 | 0.686818 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.686818 | 0.82665109 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 12941.47 | 12941.47 | 1.0000 | 0.82665109 | 0.686818 | 20.47 | 15.15 | 0.00855458 | 42284.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12941.47 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 7.5579 | 21.10 | 0.00850561 | 21.10 | 0.00860680 | 55.2198 | 150.92 | 0.00 | 12958.48 | 12958.48 | 0.81204391 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.74 | 20.75 | 0.00875166 | 59402.0 | |
| SPLIT MS2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12941.473 | 12941.473 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.686818 | 0.82665109 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 12941.47 | 12941.47 | 1.0000 | 0.82665109 | 0.686818 | 20.47 | 15.15 | 0.00855458 | 42284.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12941.47 | 12.70 | 0.00915345 | 12.70 | 0.05190911 | 7.5579 | 21.10 | 0.00850561 | 21.10 | 0.00860680 | 55.2198 | 150.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8384.285 | 6714.408 | 0.457144 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2204 | 1004.8586 | 1.2036 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.457144 | 0.55021626 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 7479.97 | 7156.41 | 0.8921 | 0.55021626 | 0.457144 | 25.82 | 16.83 | 0.00827372 | 47037.7 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 512.051 | 6967.92 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 5.6775 | 24.06 | 0.00812315 | 24.00 | 0.00812315 | 43.7345 | 5366.58 | 0.00 | 8382.86 | 6706.75 | 0.52848687 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.27 | 14.08 | 0.00994118 | 39460.4 | |
| SPLIT TSW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 8384.285 | 8384.285 | 0.457144 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.457144 | 0.55021626 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 8384.28 | 8384.28 | 1.0000 | 0.55021626 | 0.457144 | 20.62 | 14.86 | 0.00816993 | 41468.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8384.28 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 5.6775 | 21.10 | 0.00811073 | 21.10 | 0.00811073 | 52.0778 | 712.83 | 0.00 | 8395.30 | 8395.30 | 0.54049376 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.32 | 20.63 | 0.00875166 | 58976.8 | |
| SPLIT TSW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8384.285 | 8384.285 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.457144 | 0.55021626 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 8384.28 | 8384.28 | 1.0000 | 0.55021626 | 0.457144 | 20.62 | 14.86 | 0.00816993 | 41468.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8384.28 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 5.6775 | 21.10 | 0.00811073 | 21.10 | 0.00811073 | 52.0778 | 712.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNW HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8183.872 | 6551.868 | 0.445881 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2145 | 1004.8586 | 1.2036 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.445881 | 0.53666022 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 7302.21 | 6990.26 | 0.8923 | 0.53666022 | 0.445881 | 25.84 | 16.84 | 0.00827054 | 47051.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 499.435 | 6802.78 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 5.8210 | 24.06 | 0.00811573 | 24.00 | 0.00811573 | 43.6949 | 5237.17 | 0.00 | 8182.48 | 6544.29 | 0.51546620 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.26 | 14.07 | 0.00993861 | 39448.4 | |
| SPLIT TNW HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 8183.872 | 8183.872 | 0.445881 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.445881 | 0.53666022 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 8183.87 | 8183.87 | 1.0000 | 0.53666022 | 0.445881 | 20.61 | 15.31 | 0.00867632 | 42742.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8183.87 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 5.8210 | 21.10 | 0.00864683 | 21.10 | 0.00864683 | 55.4716 | 574.39 | 0.00 | 8194.63 | 8194.63 | 0.52717727 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.33 | 20.63 | 0.00875166 | 58988.4 | |
| SPLIT TNW_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8183.872 | 8183.872 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.445881 | 0.53666022 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 8183.87 | 8183.87 | 1.0000 | 0.53666022 | 0.445881 | 20.61 | 15.31 | 0.00867632 | 42742.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8183.87 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 5.8210 | 21.10 | 0.00864683 | 21.10 | 0.00864683 | 55.4716 | 574.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7900.355 | 6326.158 | 0.428046 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2578 | 1004.8586 | 1.2036 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.428046 | 0.51519456 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 7056.01 | 6730.54 | 0.8931 | 0.51519456 | 0.428046 | 25.88 | 16.87 | 0.00829380 | 47144.8 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 479.458 | 6576.55 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 6.0635 | 24.06 | 0.00813362 | 24.00 | 0.00813362 | 43.7902 | 5030.58 | 0.00 | 7899.01 | 6319.32 | 0.49484827 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.19 | 14.04 | 0.00993304 | 39359.9 | |
| SPLIT TSE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 7900.355 | 7900.355 | 0.428046 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.428046 | 0.51519456 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 7900.35 | 7900.35 | 1.0000 | 0.51519456 | 0.428046 | 20.59 | 14.85 | 0.00817435 | 41446.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7900.35 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 6.0635 | 21.10 | 0.00811115 | 21.10 | 0.00811115 | 52.0805 | 710.17 | 0.00 | 7910.74 | 7910.74 | 0.50609091 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.42 | 20.66 | 0.00875166 | 59075.2 | |
| SPLIT TSE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7900.355 | 7900.355 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.428046 | 0.51519456 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 7900.35 | 7900.35 | 1.0000 | 0.51519456 | 0.428046 | 20.59 | 14.85 | 0.00817435 | 41446.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7900.35 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 6.0635 | 21.10 | 0.00811115 | 21.10 | 0.00811115 | 52.0805 | 710.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNE HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7698.661 | 6162.725 | 0.416802 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2507 | 1004.8586 | 1.2036 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.416802 | 0.50166057 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6876.87 | 6564.04 | 0.8933 | 0.50166057 | 0.416802 | 25.90 | 16.87 | 0.00828999 | 47158.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 466.863 | 6410.01 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 6.2271 | 24.06 | 0.00812495 | 24.00 | 0.00812495 | 43.7439 | 4900.43 | 0.00 | 7697.35 | 6157.24 | 0.48184877 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.18 | 14.03 | 0.00993148 | 39347.8 | |
| SPLIT TNE HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 7698.661 | 7698.661 | 0.416802 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.416802 | 0.50166057 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 7698.66 | 7698.66 | 1.0000 | 0.50166057 | 0.416802 | 20.58 | 15.30 | 0.00868084 | 42719.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7698.66 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 6.2271 | 21.10 | 0.00864945 | 21.10 | 0.00864945 | 55.4882 | 571.90 | 0.00 | 7708.78 | 7708.78 | 0.49279608 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.43 | 20.66 | 0.00875166 | 59087.0 | |
| SPLIT TNE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7698.661 | 7698.661 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.416802 | 0.50166057 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 7698.66 | 7698.66 | 1.0000 | 0.50166057 | 0.416802 | 20.58 | 15.30 | 0.00868084 | 42719.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7698.66 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 6.2271 | 21.10 | 0.00864945 | 21.10 | 0.00864945 | 55.4882 | 571.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6885.106 | 5512.481 | 0.369527 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2765 | 1004.8586 | 1.2036 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.369527 | 0.44476073 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6159.76 | 5868.80 | 0.8947 | 0.44476073 | 0.369527 | 26.01 | 16.92 | 0.00830389 | 47309.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 413.910 | 5745.85 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 7.0237 | 24.05 | 0.00811719 | 24.00 | 0.00811719 | 43.7025 | 4354.89 | 0.00 | 6883.93 | 5506.28 | 0.42719604 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.07 | 13.98 | 0.00992026 | 39208.2 | |
| SPLIT TN1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6885.106 | 6885.106 | 0.369527 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.369527 | 0.44476073 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6885.11 | 6885.11 | 1.0000 | 0.44476073 | 0.369527 | 20.51 | 15.65 | 0.00910190 | 43720.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6885.11 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 7.0237 | 21.10 | 0.00909800 | 21.10 | 0.00914601 | 58.6280 | 232.98 | 0.00 | 6894.15 | 6894.15 | 0.43690167 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.56 | 20.70 | 0.00875166 | 59223.7 | |
| SPLIT TN1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6885.106 | 6885.106 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.369527 | 0.44476073 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6885.11 | 6885.11 | 1.0000 | 0.44476073 | 0.369527 | 20.51 | 15.65 | 0.00910190 | 43720.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6885.11 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 7.0237 | 21.10 | 0.00909800 | 21.10 | 0.00914601 | 58.6280 | 232.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6868.735 | 5498.736 | 0.368543 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2781 | 1004.8586 | 1.2036 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.368543 | 0.44357704 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6145.42 | 5854.41 | 0.8947 | 0.44357704 | 0.368543 | 26.02 | 16.93 | 0.00830475 | 47314.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 412.808 | 5732.62 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 7.0425 | 24.05 | 0.00811758 | 24.00 | 0.00811758 | 43.7046 | 4343.55 | 0.00 | 6867.57 | 5492.50 | 0.42605910 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.07 | 13.98 | 0.00991927 | 39203.6 | |
| SPLIT TN2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6868.735 | 6868.735 | 0.368543 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.368543 | 0.44357704 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6868.73 | 6868.73 | 1.0000 | 0.44357704 | 0.368543 | 20.51 | 15.65 | 0.00910222 | 43719.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6868.73 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 7.0425 | 21.10 | 0.00909834 | 21.10 | 0.00914636 | 58.6302 | 232.88 | 0.00 | 6877.76 | 6877.76 | 0.43573889 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.57 | 20.70 | 0.00875166 | 59228.2 | |
| SPLIT TN2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6868.735 | 6868.735 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.368543 | 0.44357704 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6868.73 | 6868.73 | 1.0000 | 0.44357704 | 0.368543 | 20.51 | 15.65 | 0.00910222 | 43719.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6868.73 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 7.0425 | 21.10 | 0.00909834 | 21.10 | 0.00914636 | 58.6302 | 232.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS1 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7103.475 | 5689.433 | 0.381595 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2878 | 1004.8586 | 1.2036 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.381595 | 0.45928550 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6353.98 | 6047.55 | 0.8945 | 0.45928550 | 0.381595 | 25.98 | 16.92 | 0.00830996 | 47292.7 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 427.427 | 5926.56 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 6.8016 | 24.05 | 0.00813004 | 24.00 | 0.00813004 | 43.7710 | 4494.05 | 0.00 | 7102.27 | 5683.20 | 0.44114719 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.08 | 13.99 | 0.00992344 | 39222.8 | |
| SPLIT TS1 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 7103.475 | 7103.475 | 0.381595 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.381595 | 0.45928550 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 18:20:00 | Sensible | 7103.48 | 7103.48 | 1.0000 | 0.45928550 | 0.381595 | 20.53 | 14.84 | 0.00818609 | 41413.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7103.48 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 6.8016 | 21.10 | 0.00811549 | 21.10 | 0.00815035 | 52.3290 | 359.80 | 0.00 | 7112.81 | 7112.81 | 0.45116978 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.55 | 20.70 | 0.00875166 | 59209.4 | |
| SPLIT TS1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7103.475 | 7103.475 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.381595 | 0.45928550 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 18:20:00 | Sensible | 7103.48 | 7103.48 | 1.0000 | 0.45928550 | 0.381595 | 20.53 | 14.84 | 0.00818609 | 41413.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7103.48 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 6.8016 | 21.10 | 0.00811549 | 21.10 | 0.00815035 | 52.3290 | 359.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS2 HP COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7087.265 | 5675.797 | 0.380617 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2895 | 1004.8586 | 1.2036 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.380617 | 0.45810836 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6339.80 | 6033.24 | 0.8945 | 0.45810836 | 0.380617 | 25.99 | 16.92 | 0.00831087 | 47297.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 426.332 | 5913.47 | 39.02 | 0.01077531 | 22.82 | 0.02595455 | 6.8191 | 24.05 | 0.00813052 | 24.00 | 0.00813052 | 43.7736 | 4482.77 | 0.00 | 7086.06 | 5669.53 | 0.44001654 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.08 | 13.98 | 0.00992246 | 39218.3 | |
| SPLIT TS2 HEATING COIL | COIL:HEATING:DX:SINGLESPEED | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 7087.265 | 7087.265 | 0.380617 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.380617 | 0.45810836 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 7087.26 | 7087.26 | 1.0000 | 0.45810836 | 0.380617 | 20.53 | 14.84 | 0.00818630 | 41412.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7087.26 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 6.8191 | 21.10 | 0.00811552 | 21.10 | 0.00815040 | 52.3293 | 359.70 | 0.00 | 7096.58 | 7096.58 | 0.45001344 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.55 | 20.70 | 0.00875166 | 59213.8 | |
| SPLIT TS2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7087.265 | 7087.265 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.380617 | 0.45810836 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 7087.26 | 7087.26 | 1.0000 | 0.45810836 | 0.380617 | 20.53 | 14.84 | 0.00818630 | 41412.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7087.26 | 12.70 | 0.00915345 | 12.70 | 0.02595455 | 6.8191 | 21.10 | 0.00811552 | 21.10 | 0.00815040 | 52.3293 | 359.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| G SW APARTMENT | 5776.17 | 207.00 | 203.67 |
| G NW APARTMENT | 8101.50 | 300.83 | 294.00 |
| OFFICE | 1737.50 | 5.50 | 5.50 |
| G NE APARTMENT | 8130.67 | 304.83 | 297.83 |
| G N1 APARTMENT | 8061.33 | 545.33 | 542.50 |
| G N2 APARTMENT | 8062.83 | 545.17 | 542.33 |
| G S1 APARTMENT | 5866.83 | 379.33 | 379.33 |
| G S2 APARTMENT | 5940.83 | 234.33 | 234.33 |
| M SW APARTMENT | 5495.17 | 439.83 | 432.67 |
| M NW APARTMENT | 7695.17 | 633.83 | 606.33 |
| M SE APARTMENT | 5487.50 | 460.67 | 453.50 |
| M NE APARTMENT | 7760.67 | 630.00 | 610.00 |
| M N1 APARTMENT | 7529.50 | 939.50 | 932.67 |
| M N2 APARTMENT | 7532.33 | 939.00 | 932.17 |
| M S1 APARTMENT | 5528.50 | 662.67 | 660.83 |
| M S2 APARTMENT | 5535.83 | 674.67 | 672.83 |
| T SW APARTMENT | 5113.50 | 934.33 | 593.83 |
| T NW APARTMENT | 7393.83 | 1350.67 | 806.33 |
| T SE APARTMENT | 5124.00 | 946.17 | 615.67 |
| T NE APARTMENT | 7466.50 | 1303.83 | 804.00 |
| T N1 APARTMENT | 7448.33 | 1196.50 | 923.83 |
| T N2 APARTMENT | 7451.83 | 1194.50 | 923.50 |
| T S1 APARTMENT | 5219.33 | 794.67 | 684.67 |
| T S2 APARTMENT | 5218.50 | 796.50 | 685.67 |
| T CORRIDOR | 8760.00 | 8760.00 | 8760.00 |
| G CORRIDOR | 8649.83 | 6997.83 | 6936.50 |
| M CORRIDOR | 8760.00 | 8760.00 | 8760.00 |
| Facility | 8760.00 | 8760.00 | 8760.00 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 0.00 | 40.50 | 0.00 | 0.00 |
| G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 40.50 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.031 | 0.000 | 0.031 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.036 | 0.000 | 0.034 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.526 | 0.045 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.036 | 0.000 | 0.033 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.022 | 0.000 | 0.036 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.022 | 0.000 | 0.036 |
| G S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.019 | 0.000 | 0.030 |
| G S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.019 | 0.000 | 0.028 |
| M SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.045 | 0.000 | 0.038 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.052 | 0.000 | 0.046 |
| M SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.045 | 0.000 | 0.038 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.052 | 0.000 | 0.047 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.031 | 0.000 | 0.051 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.031 | 0.000 | 0.050 |
| M S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.027 | 0.000 | 0.037 |
| M S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.027 | 0.000 | 0.037 |
| T SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.059 | 0.000 | 0.044 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.069 | 0.000 | 0.050 |
| T SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.059 | 0.000 | 0.044 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.069 | 0.000 | 0.051 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.042 | 0.000 | 0.055 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.042 | 0.000 | 0.054 |
| T S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.036 | 0.000 | 0.043 |
| T S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.036 | 0.000 | 0.043 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.513 | 0.000 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| G S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| G S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| M SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| M SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| M S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| M S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| T SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
| T SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| T S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
| T S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.349 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G NW APARTMENT | SPLIT GNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| OFFICE | SPLIT OFFICE | 4.75 | 4.75 | 268.97 | 88.25 | 0.0381 | 0.038 |
| G NE APARTMENT | SPLIT GNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N1 APARTMENT | SPLIT GN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N2 APARTMENT | SPLIT GN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S1 APARTMENT | SPLIT GS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S2 APARTMENT | SPLIT GS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| M SW APARTMENT | SPLIT MSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NW APARTMENT | SPLIT MNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M SE APARTMENT | SPLIT MSE | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NE APARTMENT | SPLIT MNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N1 APARTMENT | SPLIT MN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N2 APARTMENT | SPLIT MN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S1 APARTMENT | SPLIT MS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S2 APARTMENT | SPLIT MS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| T SW APARTMENT | SPLIT TSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NW APARTMENT | SPLIT TNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T SE APARTMENT | SPLIT TSE | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NE APARTMENT | SPLIT TNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N1 APARTMENT | SPLIT TN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N2 APARTMENT | SPLIT TN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S1 APARTMENT | SPLIT TS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S2 APARTMENT | SPLIT TS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| Total Facility | 68.21 | 82.25 | 8607.06 | 2823.98 | 0.8427 | 1.258 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| G SW APARTMENT | 818502.78 | 72275.77 | 890778.54 | 82424.94 | 973203.48 | 818502.78 | 0.00 | 7929.11 | 830.89 | 2615.00 |
| G NW APARTMENT | 818502.78 | 76979.92 | 895482.69 | 82424.94 | 977907.63 | 818502.78 | 0.00 | 7860.03 | 899.97 | 0.00 |
| OFFICE | 1167565.73 | 0.00 | 1167565.73 | 82424.94 | 1249990.67 | 1201711.97 | 500.00 | 8260.00 | 0.00 | 7010.00 |
| G NE APARTMENT | 818502.78 | 75725.53 | 894228.30 | 82424.94 | 976653.24 | 818502.78 | 0.00 | 7886.83 | 873.17 | 0.00 |
| G N1 APARTMENT | 818502.78 | 81931.42 | 900434.19 | 49716.63 | 950150.82 | 818502.78 | 0.00 | 7813.01 | 946.99 | 0.00 |
| G N2 APARTMENT | 818502.78 | 81831.50 | 900334.28 | 49716.63 | 950050.91 | 818502.78 | 0.00 | 7814.69 | 945.31 | 0.00 |
| G S1 APARTMENT | 818502.78 | 70956.22 | 889458.99 | 49716.63 | 939175.62 | 818502.78 | 0.00 | 7946.81 | 813.19 | 2615.00 |
| G S2 APARTMENT | 818502.78 | 66162.40 | 884665.18 | 49716.63 | 934381.81 | 818502.78 | 0.00 | 8008.58 | 751.42 | 2615.00 |
| M SW APARTMENT | 1637005.55 | 94382.10 | 1731387.65 | 118450.56 | 1849838.22 | 1637005.55 | 0.00 | 7793.93 | 966.07 | 2615.00 |
| M NW APARTMENT | 1637005.55 | 106672.96 | 1743678.51 | 118450.56 | 1862129.07 | 1637005.55 | 0.00 | 7638.95 | 1121.05 | 0.00 |
| M SE APARTMENT | 1637005.55 | 92089.35 | 1729094.91 | 118450.56 | 1847545.47 | 1637005.55 | 0.00 | 7827.25 | 932.75 | 2615.00 |
| M NE APARTMENT | 1637005.55 | 107148.15 | 1744153.70 | 118450.56 | 1862604.26 | 1637005.55 | 0.00 | 7652.44 | 1107.56 | 0.00 |
| M N1 APARTMENT | 1637005.55 | 116180.04 | 1753185.59 | 71446.37 | 1824631.96 | 1637005.55 | 0.00 | 7571.59 | 1188.41 | 0.00 |
| M N2 APARTMENT | 1637005.55 | 115817.80 | 1752823.36 | 71446.37 | 1824269.73 | 1637005.55 | 0.00 | 7575.51 | 1184.49 | 0.00 |
| M S1 APARTMENT | 1637005.55 | 92435.81 | 1729441.36 | 71446.37 | 1800887.74 | 1637005.55 | 0.00 | 7821.17 | 938.83 | 2615.00 |
| M S2 APARTMENT | 1637005.55 | 92310.92 | 1729316.48 | 71446.37 | 1800762.85 | 1637005.55 | 0.00 | 7822.72 | 937.28 | 2615.00 |
| T SW APARTMENT | 818502.78 | 108914.67 | 927417.45 | 156684.64 | 1084102.09 | 818502.78 | 0.00 | 7758.74 | 1001.26 | 2615.00 |
| T NW APARTMENT | 818502.78 | 115589.76 | 934092.54 | 156684.64 | 1090777.19 | 818502.78 | 0.00 | 7661.36 | 1098.64 | 0.00 |
| T SE APARTMENT | 818502.78 | 107295.45 | 925798.23 | 156684.64 | 1082482.87 | 818502.78 | 0.00 | 7784.64 | 975.36 | 2615.00 |
| T NE APARTMENT | 818502.78 | 117449.75 | 935952.52 | 156684.64 | 1092637.17 | 818502.78 | 0.00 | 7659.17 | 1100.83 | 0.00 |
| T N1 APARTMENT | 818502.78 | 125514.61 | 944017.38 | 94508.20 | 1038525.58 | 818502.78 | 0.00 | 7603.82 | 1156.18 | 0.00 |
| T N2 APARTMENT | 818502.78 | 125227.30 | 943730.08 | 94508.20 | 1038238.28 | 818502.78 | 0.00 | 7606.41 | 1153.59 | 0.00 |
| T S1 APARTMENT | 818502.78 | 107770.04 | 926272.82 | 94508.20 | 1020781.02 | 818502.78 | 0.00 | 7784.79 | 975.21 | 2615.00 |
| T S2 APARTMENT | 818502.78 | 107740.01 | 926242.79 | 94508.20 | 1020750.99 | 818502.78 | 0.00 | 7785.49 | 974.51 | 2615.00 |
| Total Facility | 39637196.26 | 3075438.60 | 42712634.86 | 3052513.14 | 45765148.00 | 39671342.50 | 500.00 | 8755.09 | 1334.73 | 8760.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| G SW APARTMENT | 0.0260 | 0.0022 | 0.0282 | 0.0023 | 0.0304 | 0.0260 | 0.00 | 5583.00 | 562.00 |
| G NW APARTMENT | 0.0260 | 0.0024 | 0.0284 | 0.0026 | 0.0310 | 0.0260 | 0.00 | 7860.03 | 899.97 |
| OFFICE | 0.0381 | 0.0000 | 0.0381 | 0.0032 | 0.0413 | 0.0381 | 0.00 | 1750.00 | 0.00 |
| G NE APARTMENT | 0.0260 | 0.0024 | 0.0284 | 0.0026 | 0.0310 | 0.0260 | 0.00 | 7886.83 | 873.17 |
| G N1 APARTMENT | 0.0260 | 0.0026 | 0.0286 | 0.0016 | 0.0301 | 0.0260 | 0.00 | 7813.01 | 946.99 |
| G N2 APARTMENT | 0.0260 | 0.0026 | 0.0285 | 0.0016 | 0.0301 | 0.0260 | 0.00 | 7814.69 | 945.31 |
| G S1 APARTMENT | 0.0260 | 0.0022 | 0.0282 | 0.0014 | 0.0295 | 0.0260 | 0.00 | 5589.65 | 555.35 |
| G S2 APARTMENT | 0.0260 | 0.0021 | 0.0280 | 0.0014 | 0.0294 | 0.0260 | 0.00 | 5631.83 | 513.17 |
| M SW APARTMENT | 0.0519 | 0.0028 | 0.0547 | 0.0032 | 0.0579 | 0.0519 | 0.00 | 5508.34 | 636.66 |
| M NW APARTMENT | 0.0519 | 0.0034 | 0.0553 | 0.0038 | 0.0590 | 0.0519 | 0.00 | 7638.95 | 1121.05 |
| M SE APARTMENT | 0.0519 | 0.0028 | 0.0547 | 0.0032 | 0.0579 | 0.0519 | 0.00 | 5513.38 | 631.62 |
| M NE APARTMENT | 0.0519 | 0.0034 | 0.0553 | 0.0038 | 0.0591 | 0.0519 | 0.00 | 7652.44 | 1107.56 |
| M N1 APARTMENT | 0.0519 | 0.0037 | 0.0556 | 0.0023 | 0.0579 | 0.0519 | 0.00 | 7571.59 | 1188.41 |
| M N2 APARTMENT | 0.0519 | 0.0037 | 0.0556 | 0.0023 | 0.0578 | 0.0519 | 0.00 | 7575.51 | 1184.49 |
| M S1 APARTMENT | 0.0519 | 0.0027 | 0.0546 | 0.0020 | 0.0566 | 0.0519 | 0.00 | 5524.33 | 620.67 |
| M S2 APARTMENT | 0.0519 | 0.0027 | 0.0546 | 0.0020 | 0.0566 | 0.0519 | 0.00 | 5525.06 | 619.94 |
| T SW APARTMENT | 0.0260 | 0.0032 | 0.0291 | 0.0043 | 0.0334 | 0.0260 | 0.00 | 5490.14 | 654.86 |
| T NW APARTMENT | 0.0260 | 0.0037 | 0.0296 | 0.0050 | 0.0346 | 0.0260 | 0.00 | 7661.36 | 1098.64 |
| T SE APARTMENT | 0.0260 | 0.0032 | 0.0292 | 0.0043 | 0.0334 | 0.0260 | 0.00 | 5487.23 | 657.77 |
| T NE APARTMENT | 0.0260 | 0.0037 | 0.0297 | 0.0050 | 0.0346 | 0.0260 | 0.00 | 7659.17 | 1100.83 |
| T N1 APARTMENT | 0.0260 | 0.0040 | 0.0299 | 0.0030 | 0.0329 | 0.0260 | 0.00 | 7603.82 | 1156.18 |
| T N2 APARTMENT | 0.0260 | 0.0040 | 0.0299 | 0.0030 | 0.0329 | 0.0260 | 0.00 | 7606.41 | 1153.59 |
| T S1 APARTMENT | 0.0260 | 0.0031 | 0.0291 | 0.0026 | 0.0317 | 0.0260 | 0.00 | 5505.02 | 639.98 |
| T S2 APARTMENT | 0.0260 | 0.0031 | 0.0291 | 0.0026 | 0.0317 | 0.0260 | 0.00 | 5503.58 | 641.42 |
| Total Facility | 1.2580 | 0.0948 | 1.3527 | 0.0912 | 1.4439 | 1.2580 | 500.00 | 8755.09 | 1334.73 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| SPLIT GSW | 0.00 | 72275.77 | 72275.77 | 818502.78 | 8420.07 | 26.69 | 313.23 | 268.89 |
| SPLIT GNW | 0.00 | 76979.92 | 76979.92 | 818502.78 | 8434.37 | 26.88 | 298.76 | 0.00 |
| SPLIT OFFICE | 1691383.44 | 0.00 | 1691383.44 | 1201711.97 | 423.17 | 12.50 | 8324.33 | 7010.00 |
| SPLIT GNE | 0.00 | 75725.53 | 75725.53 | 818502.78 | 8423.22 | 27.80 | 308.98 | 0.00 |
| SPLIT GN1 | 0.00 | 81931.42 | 81931.42 | 818502.78 | 8400.44 | 26.78 | 332.78 | 0.00 |
| SPLIT GN2 | 0.00 | 81831.50 | 81831.50 | 818502.78 | 8400.04 | 26.81 | 333.15 | 0.00 |
| SPLIT GS1 | 0.00 | 70956.22 | 70956.22 | 818502.78 | 8421.99 | 23.63 | 314.38 | 257.84 |
| SPLIT GS2 | 0.00 | 66162.40 | 66162.40 | 818502.78 | 8430.19 | 20.42 | 309.39 | 238.24 |
| SPLIT MSW | 0.00 | 94382.10 | 94382.10 | 1637005.55 | 8751.71 | 1.41 | 6.88 | 329.41 |
| SPLIT MNW | 0.00 | 106672.96 | 106672.96 | 1637005.55 | 8754.61 | 0.50 | 4.89 | 0.00 |
| SPLIT MSE | 0.00 | 92089.35 | 92089.35 | 1637005.55 | 8751.90 | 1.56 | 6.54 | 301.13 |
| SPLIT MNE | 0.00 | 107148.15 | 107148.15 | 1637005.55 | 8754.00 | 0.83 | 5.17 | 0.00 |
| SPLIT MN1 | 0.00 | 116180.04 | 116180.04 | 1637005.55 | 8748.67 | 2.67 | 8.67 | 0.00 |
| SPLIT MN2 | 0.00 | 115817.80 | 115817.80 | 1637005.55 | 8748.72 | 2.61 | 8.67 | 0.00 |
| SPLIT MS1 | 0.00 | 92435.81 | 92435.81 | 1637005.55 | 8751.94 | 1.52 | 6.54 | 318.17 |
| SPLIT MS2 | 0.00 | 92310.92 | 92310.92 | 1637005.55 | 8751.94 | 1.52 | 6.54 | 317.34 |
| SPLIT TSW | 0.00 | 108914.67 | 108914.67 | 818502.78 | 8121.39 | 26.33 | 612.28 | 346.40 |
| SPLIT TNW | 0.00 | 115589.76 | 115589.76 | 818502.78 | 8113.44 | 30.31 | 616.25 | 0.00 |
| SPLIT TSE | 0.00 | 107295.45 | 107295.45 | 818502.78 | 8117.49 | 26.86 | 615.65 | 317.59 |
| SPLIT TNE | 0.00 | 117449.75 | 117449.75 | 818502.78 | 8081.88 | 31.53 | 646.59 | 0.00 |
| SPLIT TN1 | 0.00 | 125514.61 | 125514.61 | 818502.78 | 8028.51 | 28.71 | 702.78 | 0.00 |
| SPLIT TN2 | 0.00 | 125227.30 | 125227.30 | 818502.78 | 8029.38 | 28.66 | 701.96 | 0.00 |
| SPLIT TS1 | 0.00 | 107770.04 | 107770.04 | 818502.78 | 8114.91 | 26.17 | 618.92 | 335.23 |
| SPLIT TS2 | 0.00 | 107740.01 | 107740.01 | 818502.78 | 8114.21 | 25.77 | 620.02 | 333.08 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| SPLIT GSW | 0.0000 | 0.0022 | 0.0022 | 0.0260 | 5907.50 | 17.52 | 219.97 |
| SPLIT GNW | 0.0000 | 0.0024 | 0.0024 | 0.0260 | 8434.37 | 26.88 | 298.76 |
| SPLIT OFFICE | 0.0552 | 0.0000 | 0.0552 | 0.0381 | 0.00 | 0.00 | 1750.00 |
| SPLIT GNE | 0.0000 | 0.0024 | 0.0024 | 0.0260 | 8423.22 | 27.80 | 308.98 |
| SPLIT GN1 | 0.0000 | 0.0026 | 0.0026 | 0.0260 | 8400.44 | 26.78 | 332.78 |
| SPLIT GN2 | 0.0000 | 0.0026 | 0.0026 | 0.0260 | 8400.04 | 26.81 | 333.15 |
| SPLIT GS1 | 0.0000 | 0.0022 | 0.0022 | 0.0260 | 5911.21 | 15.78 | 218.01 |
| SPLIT GS2 | 0.0000 | 0.0021 | 0.0021 | 0.0260 | 5917.35 | 12.86 | 214.79 |
| SPLIT MSW | 0.0000 | 0.0028 | 0.0028 | 0.0519 | 6139.10 | 0.73 | 5.17 |
| SPLIT MNW | 0.0000 | 0.0034 | 0.0034 | 0.0519 | 8754.61 | 0.50 | 4.89 |
| SPLIT MSE | 0.0000 | 0.0028 | 0.0028 | 0.0519 | 6139.35 | 0.85 | 4.80 |
| SPLIT MNE | 0.0000 | 0.0034 | 0.0034 | 0.0519 | 8754.00 | 0.83 | 5.17 |
| SPLIT MN1 | 0.0000 | 0.0037 | 0.0037 | 0.0519 | 8748.67 | 2.67 | 8.67 |
| SPLIT MN2 | 0.0000 | 0.0037 | 0.0037 | 0.0519 | 8748.72 | 2.61 | 8.67 |
| SPLIT MS1 | 0.0000 | 0.0027 | 0.0027 | 0.0519 | 6139.46 | 0.77 | 4.77 |
| SPLIT MS2 | 0.0000 | 0.0027 | 0.0027 | 0.0519 | 6139.46 | 0.77 | 4.77 |
| SPLIT TSW | 0.0000 | 0.0032 | 0.0032 | 0.0260 | 5732.87 | 17.68 | 394.46 |
| SPLIT TNW | 0.0000 | 0.0037 | 0.0037 | 0.0260 | 8113.44 | 30.31 | 616.25 |
| SPLIT TSE | 0.0000 | 0.0032 | 0.0032 | 0.0260 | 5724.43 | 19.05 | 401.51 |
| SPLIT TNE | 0.0000 | 0.0037 | 0.0037 | 0.0260 | 8081.88 | 31.53 | 646.59 |
| SPLIT TN1 | 0.0000 | 0.0040 | 0.0040 | 0.0260 | 8028.51 | 28.71 | 702.78 |
| SPLIT TN2 | 0.0000 | 0.0040 | 0.0040 | 0.0260 | 8029.38 | 28.66 | 701.96 |
| SPLIT TS1 | 0.0000 | 0.0031 | 0.0031 | 0.0260 | 5732.78 | 17.58 | 394.64 |
| SPLIT TS2 | 0.0000 | 0.0031 | 0.0031 | 0.0260 | 5731.32 | 17.35 | 396.33 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| SPLIT GSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT OFFICE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| SPLIT GSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT OFFICE | 0.0552 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Surfaces by Class| Total | Outdoors | |
| Wall | 126 | 42 |
| Floor | 27 | 9 |
| Roof | 27 | 9 |
| Internal Mass | 24 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 39 | 39 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 24 |
| Conditioned Zones | 24 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1588 |
| Defaulted Fields | 1666 |
| Fields with Defaults | 5801 |
| Autosized Fields | 648 |
| Autosizable Fields | 770 |
| Autocalculated Fields | 332 |
| Autocalculatable Fields | 509 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1141.78 | 14963.80 | 01-JAN-04:00 | 71136.83 | 10-AUG-16:10 |
| Electricity:Building | 527.01 | 10157.12 | 01-JAN-03:10 | 25266.90 | 03-JAN-17:10 |
| Electricity:Zone:G SW APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 527.01 | 10157.12 | 01-JAN-03:10 | 25266.90 | 03-JAN-17:10 |
| InteriorLights:Electricity | 73.00 | 1491.31 | 01-JAN-00:10 | 4040.47 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:G SW APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 73.00 | 1491.31 | 01-JAN-00:10 | 4040.47 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 67.97 | 1461.31 | 01-JAN-00:10 | 3560.62 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 67.97 | 1461.31 | 01-JAN-00:10 | 3560.62 | 01-JAN-19:10 |
| Electricity:Zone:G NW APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NW APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:OFFICE | 13.20 | 218.21 | 01-JAN-00:10 | 992.54 | 03-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICE | 5.68 | 89.52 | 01-JAN-00:10 | 447.62 | 03-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICE | 5.68 | 89.52 | 01-JAN-00:10 | 447.62 | 03-JAN-08:10 |
| Electricity:Zone:G NE APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NE APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:G N1 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:G N2 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:G S1 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:G S2 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:M SW APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SW APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SW APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M NW APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NW APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NW APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M SE APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SE APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SE APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M NE APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NE APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NE APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M N1 APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M N2 APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M S1 APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:M S2 APARTMENT | 26.26 | 458.32 | 01-JAN-03:10 | 1325.26 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.84 | 10.97 | 01-JAN-00:10 | 175.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.51 | 9.03 | 01-JAN-00:10 | 144.47 | 01-JAN-19:10 |
| Electricity:Zone:T SW APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SW APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T NW APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NW APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T SE APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SE APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T NE APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NE APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T N1 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T N2 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T S1 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:T S2 APARTMENT | 13.13 | 229.16 | 01-JAN-03:10 | 662.63 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.92 | 5.48 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.76 | 4.52 | 01-JAN-00:10 | 72.24 | 01-JAN-19:10 |
| Electricity:Zone:G CORRIDOR | 77.61 | 1911.10 | 01-JAN-00:10 | 4111.81 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:G CORRIDOR | 9.71 | 307.95 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:G CORRIDOR | 9.71 | 307.95 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 |
| Electricity:Zone:M CORRIDOR | 19.42 | 615.89 | 01-JAN-00:10 | 615.89 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:M CORRIDOR | 19.42 | 615.89 | 01-JAN-00:10 | 615.89 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:M CORRIDOR | 19.42 | 615.89 | 01-JAN-00:10 | 615.89 | 01-JAN-00:10 |
| Electricity:Zone:T CORRIDOR | 9.71 | 307.95 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:T CORRIDOR | 9.71 | 307.95 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:T CORRIDOR | 9.71 | 307.95 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 |
| LightsPlugIn:InteriorLights:Electricity | 5.02 | 30.00 | 01-JAN-00:10 | 479.85 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:SpaceType:GENERAL | 5.02 | 30.00 | 01-JAN-00:10 | 479.85 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SW APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NW APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SE APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NE APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N1 APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N2 APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S1 APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S2 APARTMENT | 0.32 | 1.94 | 01-JAN-00:10 | 30.96 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.16 | 0.97 | 01-JAN-00:10 | 15.48 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 454.01 | 8665.81 | 01-JAN-03:10 | 22246.15 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G CORRIDOR | 67.90 | 1603.15 | 01-JAN-00:10 | 3803.87 | 01-JAN-07:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 454.01 | 8665.81 | 01-JAN-03:10 | 22246.15 | 03-JAN-17:10 |
| ElevatorLift:InteriorEquipment:Electricity | 67.41 | 1600.00 | 01-JAN-00:10 | 3772.37 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:G CORRIDOR | 67.41 | 1600.00 | 01-JAN-00:10 | 3772.37 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 67.41 | 1600.00 | 01-JAN-00:10 | 3772.37 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 0.49 | 3.15 | 01-JAN-00:10 | 31.50 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:G CORRIDOR | 0.49 | 3.15 | 01-JAN-00:10 | 31.50 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.49 | 3.15 | 01-JAN-00:10 | 31.50 | 01-JAN-07:10 |
| InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity | 386.12 | 7062.66 | 01-JAN-03:10 | 18442.28 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 386.12 | 7062.66 | 01-JAN-03:10 | 18442.28 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:OFFICE | 7.52 | 128.69 | 01-JAN-00:10 | 544.92 | 03-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICE | 7.52 | 128.69 | 01-JAN-00:10 | 544.92 | 03-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| Fans:Electricity | 159.24 | 1565.52 | 04-JAN-12:10 | 9758.92 | 10-AUG-16:10 |
| Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 1141.78 | 14963.80 | 01-JAN-04:00 | 71136.83 | 10-AUG-16:10 |
| ElectricityPurchased:Plant | 1141.78 | 14963.80 | 01-JAN-04:00 | 71136.83 | 10-AUG-16:10 |
| Cogeneration:ElectricityPurchased | 1141.78 | 14963.80 | 01-JAN-04:00 | 71136.83 | 10-AUG-16:10 |
| General:Cogeneration:ElectricityPurchased | 1141.78 | 14963.80 | 01-JAN-04:00 | 71136.83 | 10-AUG-16:10 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1141.78 | 14963.80 | 01-JAN-04:00 | 71136.83 | 10-AUG-16:10 |
| ElectricityNet:Plant | 1141.78 | 14963.80 | 01-JAN-04:00 | 71136.83 | 10-AUG-16:10 |
| Cogeneration:ElectricityNet | 1141.78 | 14963.80 | 01-JAN-04:00 | 71136.83 | 10-AUG-16:10 |
| General:Cogeneration:ElectricityNet | 1141.78 | 14963.80 | 01-JAN-04:00 | 71136.83 | 10-AUG-16:10 |
| Electricity:HVAC | 581.24 | 1950.32 | 01-JAN-09:30 | 46303.74 | 10-AUG-16:00 |
| HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Fans:Electricity | 159.24 | 1565.52 | 04-JAN-12:10 | 9758.92 | 10-AUG-16:10 |
| Cooling:Electricity | 422.00 | 0.00 | 01-JAN-09:30 | 36725.58 | 10-AUG-16:00 |
| General:Cooling:Electricity | 422.00 | 0.00 | 01-JAN-09:30 | 36725.58 | 10-AUG-16:00 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ExteriorLights:Electricity | 33.07 | 0.00 | 01-JAN-07:10 | 2101.03 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 33.07 | 0.00 | 01-JAN-07:10 | 2101.03 | 01-JAN-00:10 |
| Electricity:Plant | 0.46 | 14.49 | 01-JAN-00:10 | 14.49 | 01-JAN-06:10 |
| Pumps:Electricity | 0.46 | 14.49 | 01-JAN-00:10 | 14.49 | 01-JAN-06:10 |
| General:Pumps:Electricity | 0.46 | 14.49 | 01-JAN-00:10 | 14.49 | 01-JAN-06:10 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 295.65 | 0.00 | 01-JAN-02:30 | 21361.32 | 13-JAN-08:00 |
| NaturalGas:Plant | 295.65 | 0.00 | 01-JAN-02:30 | 21361.32 | 13-JAN-08:00 |
| WaterSystems:NaturalGas | 295.65 | 0.00 | 01-JAN-02:30 | 21361.32 | 13-JAN-08:00 |
| Water Heater:WaterSystems:NaturalGas | 295.65 | 0.00 | 01-JAN-02:30 | 21361.32 | 13-JAN-08:00 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 23-JAN-07:10 |
| Water:Plant | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 23-JAN-07:10 |
| WaterSystems:Water | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 23-JAN-07:10 |
| WaterUse:WaterSystems:Water | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 23-JAN-07:10 |
| MainsWater:Facility | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 23-JAN-07:10 |
| MainsWater:Plant | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 23-JAN-07:10 |
| WaterSystems:MainsWater | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 23-JAN-07:10 |
| WaterUse:WaterSystems:MainsWater | 1875.51 | 0.00 | 01-JAN-02:10 | 0.00 | 23-JAN-07:10 |
| Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 3036.55 | 6505.41 | 06-DEC-23:10 | 220977.93 | 10-AUG-16:00 |
| EnergyTransfer:Building | 1067.95 | 137.93 | 25-SEP-05:50 | 76520.90 | 10-AUG-15:30 |
| EnergyTransfer:Zone:G SW APARTMENT | 39.58 | 0.01 | 12-MAR-09:50 | 2839.18 | 04-SEP-16:30 |
| Heating:EnergyTransfer | 4.71 | 0.00 | 01-JAN-03:20 | 1755.62 | 22-JUN-08:40 |
| Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 88.09 | 22-JUN-09:00 |
| General:Heating:EnergyTransfer | 4.71 | 0.00 | 01-JAN-03:20 | 1755.62 | 22-JUN-08:40 |
| General:Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 88.09 | 22-JUN-09:00 |
| Cooling:EnergyTransfer | 1063.24 | 0.00 | 04-FEB-09:50 | 76520.90 | 10-AUG-15:30 |
| Cooling:EnergyTransfer:Zone:G SW APARTMENT | 39.57 | 0.00 | 01-JAN-14:50 | 2839.18 | 04-SEP-16:30 |
| General:Cooling:EnergyTransfer | 1063.24 | 0.00 | 04-FEB-09:50 | 76520.90 | 10-AUG-15:30 |
| General:Cooling:EnergyTransfer:Zone:G SW APARTMENT | 39.57 | 0.00 | 01-JAN-14:50 | 2839.18 | 04-SEP-16:30 |
| EnergyTransfer:Zone:G NW APARTMENT | 35.75 | 0.00 | 12-DEC-09:00 | 2743.67 | 05-AUG-17:10 |
| Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 113.48 | 22-JUN-09:00 |
| General:Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 113.48 | 22-JUN-09:00 |
| Cooling:EnergyTransfer:Zone:G NW APARTMENT | 35.74 | 0.00 | 04-JAN-13:50 | 2743.67 | 05-AUG-17:10 |
| General:Cooling:EnergyTransfer:Zone:G NW APARTMENT | 35.74 | 0.00 | 04-JAN-13:50 | 2743.67 | 05-AUG-17:10 |
| EnergyTransfer:Zone:OFFICE | 32.96 | 0.00 | 03-FEB-05:40 | 5105.71 | 07-AUG-06:20 |
| Heating:EnergyTransfer:Zone:OFFICE | 4.49 | 0.00 | 01-JAN-03:20 | 965.65 | 21-JUL-17:10 |
| General:Heating:EnergyTransfer:Zone:OFFICE | 4.49 | 0.00 | 01-JAN-03:20 | 965.65 | 21-JUL-17:10 |
| Cooling:EnergyTransfer:Zone:OFFICE | 28.47 | 0.00 | 01-JAN-00:10 | 5105.71 | 07-AUG-06:20 |
| General:Cooling:EnergyTransfer:Zone:OFFICE | 28.47 | 0.00 | 01-JAN-00:10 | 5105.71 | 07-AUG-06:20 |
| EnergyTransfer:Zone:G NE APARTMENT | 35.89 | 0.02 | 20-MAR-10:20 | 2567.03 | 05-AUG-17:10 |
| Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 114.16 | 22-JUN-09:00 |
| General:Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 114.16 | 22-JUN-09:00 |
| Cooling:EnergyTransfer:Zone:G NE APARTMENT | 35.89 | 0.00 | 04-JAN-13:50 | 2567.03 | 05-AUG-17:10 |
| General:Cooling:EnergyTransfer:Zone:G NE APARTMENT | 35.89 | 0.00 | 04-JAN-13:50 | 2567.03 | 05-AUG-17:10 |
| EnergyTransfer:Zone:G N1 APARTMENT | 29.41 | 0.00 | 29-NOV-22:00 | 1965.89 | 05-AUG-17:20 |
| Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 110.66 | 25-APR-08:00 |
| General:Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 110.66 | 25-APR-08:00 |
| Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 29.40 | 0.00 | 04-JAN-13:30 | 1965.89 | 05-AUG-17:20 |
| General:Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 29.40 | 0.00 | 04-JAN-13:30 | 1965.89 | 05-AUG-17:20 |
| EnergyTransfer:Zone:G N2 APARTMENT | 29.42 | 0.00 | 29-NOV-22:00 | 1964.02 | 05-AUG-17:20 |
| Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 110.63 | 25-APR-08:00 |
| General:Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 110.63 | 25-APR-08:00 |
| Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 29.41 | 0.00 | 04-JAN-13:30 | 1964.02 | 05-AUG-17:20 |
| General:Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 29.41 | 0.00 | 04-JAN-13:30 | 1964.02 | 05-AUG-17:20 |
| EnergyTransfer:Zone:G S1 APARTMENT | 33.45 | 0.00 | 24-MAR-09:30 | 2531.63 | 18-DEC-13:40 |
| Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 77.72 | 14-APR-10:00 |
| General:Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 77.72 | 14-APR-10:00 |
| Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 33.44 | 0.00 | 01-JAN-14:50 | 2524.93 | 18-DEC-13:40 |
| General:Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 33.44 | 0.00 | 01-JAN-14:50 | 2524.93 | 18-DEC-13:40 |
| EnergyTransfer:Zone:G S2 APARTMENT | 36.15 | 0.01 | 03-FEB-18:30 | 2584.51 | 18-DEC-13:40 |
| Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 77.49 | 14-APR-10:00 |
| General:Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 77.49 | 14-APR-10:00 |
| Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 36.15 | 0.00 | 01-JAN-14:50 | 2577.88 | 18-DEC-13:40 |
| General:Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 36.15 | 0.00 | 01-JAN-14:50 | 2577.88 | 18-DEC-13:40 |
| EnergyTransfer:Zone:M SW APARTMENT | 75.26 | 0.08 | 23-MAR-06:00 | 5856.71 | 27-FEB-16:30 |
| Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 118.75 | 25-APR-07:40 |
| General:Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 118.75 | 25-APR-07:40 |
| Cooling:EnergyTransfer:Zone:M SW APARTMENT | 75.25 | 0.00 | 04-JAN-13:00 | 5849.13 | 27-FEB-16:30 |
| General:Cooling:EnergyTransfer:Zone:M SW APARTMENT | 75.25 | 0.00 | 04-JAN-13:00 | 5849.13 | 27-FEB-16:30 |
| EnergyTransfer:Zone:M NW APARTMENT | 67.08 | 0.00 | 08-FEB-21:20 | 5525.17 | 21-JUL-16:30 |
| Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.02 | 0.00 | 01-JAN-00:10 | 118.94 | 25-APR-07:40 |
| General:Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.02 | 0.00 | 01-JAN-00:10 | 118.94 | 25-APR-07:40 |
| Cooling:EnergyTransfer:Zone:M NW APARTMENT | 67.07 | 0.00 | 01-JAN-13:30 | 5525.17 | 21-JUL-16:30 |
| General:Cooling:EnergyTransfer:Zone:M NW APARTMENT | 67.07 | 0.00 | 01-JAN-13:30 | 5525.17 | 21-JUL-16:30 |
| EnergyTransfer:Zone:M SE APARTMENT | 75.62 | 0.01 | 20-OCT-06:30 | 5679.16 | 27-FEB-15:20 |
| Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 111.54 | 22-JUN-08:40 |
| General:Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 111.54 | 22-JUN-08:40 |
| Cooling:EnergyTransfer:Zone:M SE APARTMENT | 75.61 | 0.00 | 01-JAN-14:50 | 5670.23 | 27-FEB-15:20 |
| General:Cooling:EnergyTransfer:Zone:M SE APARTMENT | 75.61 | 0.00 | 01-JAN-14:50 | 5670.23 | 27-FEB-15:20 |
| EnergyTransfer:Zone:M NE APARTMENT | 67.42 | 0.01 | 09-DEC-10:10 | 5093.50 | 21-JUL-16:30 |
| Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 108.71 | 22-JUN-08:40 |
| General:Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 108.71 | 22-JUN-08:40 |
| Cooling:EnergyTransfer:Zone:M NE APARTMENT | 67.40 | 0.00 | 01-JAN-13:30 | 5093.50 | 21-JUL-16:30 |
| General:Cooling:EnergyTransfer:Zone:M NE APARTMENT | 67.40 | 0.00 | 01-JAN-13:30 | 5093.50 | 21-JUL-16:30 |
| EnergyTransfer:Zone:M N1 APARTMENT | 54.28 | 0.02 | 04-DEC-23:10 | 4026.36 | 14-DEC-17:30 |
| Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.02 | 0.00 | 01-JAN-00:10 | 125.93 | 23-APR-08:50 |
| General:Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.02 | 0.00 | 01-JAN-00:10 | 125.93 | 23-APR-08:50 |
| Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 54.27 | 0.00 | 01-JAN-13:40 | 4014.78 | 14-DEC-17:30 |
| General:Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 54.27 | 0.00 | 01-JAN-13:40 | 4014.78 | 14-DEC-17:30 |
| EnergyTransfer:Zone:M N2 APARTMENT | 54.31 | 0.02 | 04-DEC-23:10 | 4027.37 | 14-DEC-17:30 |
| Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.02 | 0.00 | 01-JAN-00:10 | 125.78 | 23-APR-08:50 |
| General:Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.02 | 0.00 | 01-JAN-00:10 | 125.78 | 23-APR-08:50 |
| Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 54.30 | 0.00 | 01-JAN-13:40 | 4015.77 | 14-DEC-17:30 |
| General:Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 54.30 | 0.00 | 01-JAN-13:40 | 4015.77 | 14-DEC-17:30 |
| EnergyTransfer:Zone:M S1 APARTMENT | 62.62 | 0.02 | 10-DEC-22:40 | 5352.31 | 18-DEC-13:40 |
| Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 125.30 | 22-JUN-08:40 |
| General:Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 125.30 | 22-JUN-08:40 |
| Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 62.61 | 0.00 | 01-JAN-14:50 | 5339.35 | 18-DEC-13:40 |
| General:Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 62.61 | 0.00 | 01-JAN-14:50 | 5339.35 | 18-DEC-13:40 |
| EnergyTransfer:Zone:M S2 APARTMENT | 62.65 | 0.02 | 10-DEC-22:40 | 5365.98 | 18-DEC-13:40 |
| Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 125.14 | 22-JUN-08:40 |
| General:Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 125.14 | 22-JUN-08:40 |
| Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 62.64 | 0.00 | 01-JAN-14:50 | 5353.03 | 18-DEC-13:40 |
| General:Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 62.64 | 0.00 | 01-JAN-14:50 | 5353.03 | 18-DEC-13:40 |
| EnergyTransfer:Zone:T SW APARTMENT | 39.87 | 0.01 | 16-NOV-08:50 | 3568.89 | 10-AUG-16:10 |
| Heating:EnergyTransfer:Zone:T SW APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 72.40 | 24-APR-08:30 |
| General:Heating:EnergyTransfer:Zone:T SW APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 72.40 | 24-APR-08:30 |
| Cooling:EnergyTransfer:Zone:T SW APARTMENT | 39.87 | 0.00 | 03-JAN-11:40 | 3568.89 | 10-AUG-16:10 |
| General:Cooling:EnergyTransfer:Zone:T SW APARTMENT | 39.87 | 0.00 | 03-JAN-11:40 | 3568.89 | 10-AUG-16:10 |
| EnergyTransfer:Zone:T NW APARTMENT | 35.76 | 0.01 | 08-MAR-09:40 | 3564.46 | 21-JUL-16:30 |
| Heating:EnergyTransfer:Zone:T NW APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 75.16 | 02-APR-08:40 |
| General:Heating:EnergyTransfer:Zone:T NW APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 75.16 | 02-APR-08:40 |
| Cooling:EnergyTransfer:Zone:T NW APARTMENT | 35.75 | 0.00 | 01-JAN-12:30 | 3564.46 | 21-JUL-16:30 |
| General:Cooling:EnergyTransfer:Zone:T NW APARTMENT | 35.75 | 0.00 | 01-JAN-12:30 | 3564.46 | 21-JUL-16:30 |
| EnergyTransfer:Zone:T SE APARTMENT | 40.07 | 0.01 | 09-DEC-10:20 | 3440.15 | 27-FEB-15:20 |
| Heating:EnergyTransfer:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 64.71 | 27-MAR-07:30 |
| General:Heating:EnergyTransfer:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 64.71 | 27-MAR-07:30 |
| Cooling:EnergyTransfer:Zone:T SE APARTMENT | 40.06 | 0.00 | 01-JAN-14:50 | 3435.98 | 27-FEB-15:20 |
| General:Cooling:EnergyTransfer:Zone:T SE APARTMENT | 40.06 | 0.00 | 01-JAN-14:50 | 3435.98 | 27-FEB-15:20 |
| EnergyTransfer:Zone:T NE APARTMENT | 35.93 | 0.01 | 01-APR-08:50 | 3260.70 | 21-JUL-16:20 |
| Heating:EnergyTransfer:Zone:T NE APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 76.73 | 22-JUN-09:00 |
| General:Heating:EnergyTransfer:Zone:T NE APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 76.73 | 22-JUN-09:00 |
| Cooling:EnergyTransfer:Zone:T NE APARTMENT | 35.92 | 0.00 | 01-JAN-12:40 | 3260.70 | 21-JUL-16:20 |
| General:Cooling:EnergyTransfer:Zone:T NE APARTMENT | 35.92 | 0.00 | 01-JAN-12:40 | 3260.70 | 21-JUL-16:20 |
| EnergyTransfer:Zone:T N1 APARTMENT | 28.98 | 0.02 | 28-NOV-09:10 | 2494.15 | 21-JUL-16:30 |
| Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 77.66 | 21-OCT-09:00 |
| General:Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 77.66 | 21-OCT-09:00 |
| Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 28.97 | 0.00 | 01-JAN-12:50 | 2494.15 | 21-JUL-16:30 |
| General:Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 28.97 | 0.00 | 01-JAN-12:50 | 2494.15 | 21-JUL-16:30 |
| EnergyTransfer:Zone:T N2 APARTMENT | 29.00 | 0.00 | 12-APR-07:40 | 2488.83 | 21-JUL-16:30 |
| Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 76.88 | 14-APR-10:00 |
| General:Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 76.88 | 14-APR-10:00 |
| Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 28.99 | 0.00 | 01-JAN-12:50 | 2488.83 | 21-JUL-16:30 |
| General:Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 28.99 | 0.00 | 01-JAN-12:50 | 2488.83 | 21-JUL-16:30 |
| EnergyTransfer:Zone:T S1 APARTMENT | 33.23 | 0.01 | 11-DEC-09:50 | 3149.52 | 07-JAN-14:50 |
| Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 76.60 | 14-APR-10:00 |
| General:Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 76.60 | 14-APR-10:00 |
| Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 33.22 | 0.00 | 04-JAN-13:00 | 3149.52 | 07-JAN-14:50 |
| General:Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 33.22 | 0.00 | 04-JAN-13:00 | 3149.52 | 07-JAN-14:50 |
| EnergyTransfer:Zone:T S2 APARTMENT | 33.24 | 0.01 | 12-APR-07:40 | 3161.54 | 07-JAN-14:50 |
| Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 72.73 | 24-APR-08:30 |
| General:Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 72.73 | 24-APR-08:30 |
| Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 33.24 | 0.00 | 04-JAN-13:00 | 3161.54 | 07-JAN-14:50 |
| General:Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 33.24 | 0.00 | 04-JAN-13:00 | 3161.54 | 07-JAN-14:50 |
| EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Facility | 226.29 | 107.07 | 14-JUL-02:00 | 16666.46 | 12-JAN-07:20 |
| PlantLoopHeatingDemand:Plant | 226.29 | 107.07 | 14-JUL-02:00 | 16666.46 | 12-JAN-07:20 |
| WaterSystems:PlantLoopHeatingDemand | 226.29 | 107.07 | 14-JUL-02:00 | 16666.46 | 12-JAN-07:20 |
| General:WaterSystems:PlantLoopHeatingDemand | 226.29 | 107.07 | 14-JUL-02:00 | 16666.46 | 12-JAN-07:20 |
| EnergyTransfer:HVAC | 1742.31 | 45.23 | 27-NOV-22:10 | 138658.70 | 10-AUG-16:00 |
| HeatRecoveryForHeating:EnergyTransfer | 29.62 | 0.00 | 09-JAN-13:30 | 9994.81 | 16-JAN-06:00 |
| HeatRecoveryForCooling:EnergyTransfer | 213.44 | 0.00 | 01-JAN-00:10 | 23008.80 | 30-JUL-16:00 |
| CoolingCoils:EnergyTransfer | 1499.25 | 0.00 | 01-JAN-09:30 | 119173.20 | 30-APR-09:00 |
| HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Plant | 226.29 | 107.07 | 14-JUL-02:00 | 16664.75 | 12-JAN-07:20 |
| WaterSystems:EnergyTransfer | 226.29 | 107.07 | 14-JUL-02:00 | 16664.75 | 12-JAN-07:20 |
| WaterUse:WaterSystems:EnergyTransfer | 226.29 | 107.07 | 14-JUL-02:00 | 16664.75 | 12-JAN-07:20 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| G SW APARTMENT | 2.321 | -0.310 | 0.000 | -41.579 | 0.000 | 0.000 | 3.508 | 0.918 | 12.213 | 10.503 | 0.000 | 0.617 | 13.974 | 0.000 | -1.610 | 0.000 | -0.556 | -0.000 |
| G NW APARTMENT | 2.317 | -0.303 | 0.000 | -37.749 | 0.000 | 0.000 | 3.556 | 0.918 | 12.213 | 8.217 | 0.000 | 0.617 | 12.410 | 0.000 | -1.630 | 0.000 | -0.565 | -0.000 |
| OFFICE | 0.000 | 0.000 | 4.491 | -28.471 | 0.000 | 0.000 | 2.001 | 5.679 | 7.520 | 9.245 | 0.000 | 0.416 | 1.595 | 0.000 | -2.289 | 0.000 | -0.188 | -0.000 |
| G NE APARTMENT | 2.317 | -0.305 | 0.000 | -37.893 | 0.000 | 0.000 | 3.556 | 0.918 | 12.213 | 8.102 | 0.000 | 0.617 | 12.595 | 0.000 | -1.550 | 0.000 | -0.570 | -0.000 |
| G N1 APARTMENT | 2.317 | -0.302 | 0.000 | -31.407 | 0.000 | 0.000 | 3.556 | 0.918 | 12.213 | 4.176 | 0.000 | 0.372 | 9.700 | 0.000 | -0.992 | 0.000 | -0.552 | -0.000 |
| G N2 APARTMENT | 2.317 | -0.302 | 0.000 | -31.420 | 0.000 | 0.000 | 3.556 | 0.918 | 12.213 | 4.176 | 0.000 | 0.372 | 9.713 | 0.000 | -0.992 | 0.000 | -0.551 | -0.000 |
| G S1 APARTMENT | 2.321 | -0.312 | 0.000 | -35.446 | 0.000 | 0.000 | 3.507 | 0.918 | 12.213 | 6.489 | 0.000 | 0.372 | 11.406 | 0.000 | -0.961 | 0.000 | -0.507 | -0.000 |
| G S2 APARTMENT | 2.321 | -0.316 | 0.000 | -38.147 | 0.000 | 0.000 | 3.504 | 0.918 | 12.213 | 6.455 | 0.000 | 0.372 | 14.143 | 0.000 | -0.975 | 0.000 | -0.487 | -0.000 |
| M SW APARTMENT | 4.642 | -0.600 | 0.000 | -79.282 | 0.000 | 0.000 | 7.028 | 1.837 | 24.426 | 21.308 | 0.000 | 1.770 | 23.370 | 0.000 | -3.106 | 0.000 | -1.392 | -0.000 |
| M NW APARTMENT | 4.638 | -0.578 | 0.000 | -71.109 | 0.000 | 0.000 | 7.129 | 1.837 | 24.426 | 16.769 | 0.000 | 1.769 | 19.730 | 0.000 | -3.146 | 0.000 | -1.463 | -0.000 |
| M SE APARTMENT | 4.641 | -0.605 | 0.000 | -79.636 | 0.000 | 0.000 | 7.028 | 1.837 | 24.426 | 21.146 | 0.000 | 1.770 | 23.795 | 0.000 | -3.012 | 0.000 | -1.389 | -0.000 |
| M NE APARTMENT | 4.635 | -0.582 | 0.000 | -71.444 | 0.000 | 0.000 | 7.129 | 1.837 | 24.426 | 16.545 | 0.000 | 1.769 | 20.177 | 0.000 | -2.990 | 0.000 | -1.501 | -0.000 |
| M N1 APARTMENT | 4.637 | -0.580 | 0.000 | -58.304 | 0.000 | 0.000 | 7.128 | 1.837 | 24.426 | 8.541 | 0.000 | 1.067 | 14.615 | 0.000 | -1.924 | 0.000 | -1.442 | -0.000 |
| M N2 APARTMENT | 4.637 | -0.581 | 0.000 | -58.335 | 0.000 | 0.000 | 7.128 | 1.837 | 24.426 | 8.540 | 0.000 | 1.067 | 14.645 | 0.000 | -1.924 | 0.000 | -1.439 | -0.000 |
| M S1 APARTMENT | 4.641 | -0.607 | 0.000 | -66.632 | 0.000 | 0.000 | 7.024 | 1.837 | 24.426 | 13.139 | 0.000 | 1.067 | 18.225 | 0.000 | -1.863 | 0.000 | -1.257 | -0.000 |
| M S2 APARTMENT | 4.641 | -0.607 | 0.000 | -66.661 | 0.000 | 0.000 | 7.024 | 1.837 | 24.426 | 13.138 | 0.000 | 1.067 | 18.254 | 0.000 | -1.863 | 0.000 | -1.256 | -0.000 |
| T SW APARTMENT | 2.322 | -0.283 | 0.000 | -41.901 | 0.000 | 0.000 | 3.527 | 0.918 | 12.213 | 10.465 | 0.000 | 1.165 | 13.816 | 0.000 | -1.481 | 0.000 | -0.760 | -0.000 |
| T NW APARTMENT | 2.320 | -0.267 | 0.000 | -37.790 | 0.000 | 0.000 | 3.578 | 0.918 | 12.213 | 8.226 | 0.000 | 1.165 | 11.889 | 0.000 | -1.495 | 0.000 | -0.757 | -0.001 |
| T SE APARTMENT | 2.321 | -0.287 | 0.000 | -42.093 | 0.000 | 0.000 | 3.527 | 0.918 | 12.213 | 10.386 | 0.000 | 1.165 | 14.062 | 0.000 | -1.438 | 0.000 | -0.773 | -0.000 |
| T NE APARTMENT | 2.318 | -0.270 | 0.000 | -37.963 | 0.000 | 0.000 | 3.579 | 0.918 | 12.213 | 8.121 | 0.000 | 1.164 | 12.136 | 0.000 | -1.425 | 0.000 | -0.791 | -0.000 |
| T N1 APARTMENT | 2.319 | -0.277 | 0.000 | -30.997 | 0.000 | 0.000 | 3.571 | 0.918 | 12.213 | 4.195 | 0.000 | 0.702 | 9.030 | 0.000 | -0.931 | 0.000 | -0.744 | -0.000 |
| T N2 APARTMENT | 2.319 | -0.278 | 0.000 | -31.016 | 0.000 | 0.000 | 3.571 | 0.918 | 12.213 | 4.194 | 0.000 | 0.702 | 9.050 | 0.000 | -0.930 | 0.000 | -0.744 | -0.000 |
| T S1 APARTMENT | 2.321 | -0.294 | 0.000 | -35.241 | 0.000 | 0.000 | 3.519 | 0.918 | 12.213 | 6.472 | 0.000 | 0.703 | 10.986 | 0.000 | -0.903 | 0.000 | -0.695 | -0.000 |
| T S2 APARTMENT | 2.321 | -0.294 | 0.000 | -35.260 | 0.000 | 0.000 | 3.519 | 0.918 | 12.213 | 6.471 | 0.000 | 0.703 | 11.007 | 0.000 | -0.902 | 0.000 | -0.696 | -0.000 |
| T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.148 | 9.711 | 0.000 | 0.900 | 0.000 | 0.139 | 0.000 | 0.000 | -0.169 | 0.000 | -0.049 | -15.681 |
| G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.408 | 9.711 | 3.395 | 2.459 | 0.000 | 6.733 | 0.000 | 0.000 | -0.593 | 0.000 | -5.592 | -20.521 |
| M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.308 | 19.423 | 0.000 | 1.823 | 0.000 | 0.226 | 0.000 | 0.000 | -0.353 | 0.000 | -0.079 | -31.348 |
| Total Facility | 71.903 | -9.137 | 4.491 | -1125.777 | 0.000 | 0.000 | 131.613 | 72.996 | 389.511 | 240.201 | 0.000 | 29.669 | 330.323 | 0.000 | -41.447 | 0.000 | -26.796 | -67.554 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 11-FEB-17:02 | 0.00 | -1.48 | 0.00 | -6616.58 | 0.00 | 0.00 | 145.07 | 54.82 | 588.62 | 164.59 | 0.00 | 0.00 | 5693.22 | 0.00 | -0.00 | 0.00 | -28.27 | 0.00 |
| G NW APARTMENT | 12-FEB-17:12 | 0.00 | -2.49 | 0.00 | -6409.12 | 0.00 | 0.00 | 75.44 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 5721.44 | 0.00 | -6.96 | 0.00 | -21.75 | 0.00 |
| OFFICE | 20-OCT-06:01 | 0.00 | 0.00 | 0.00 | -8003.77 | 0.00 | 0.00 | 0.00 | 89.52 | 194.98 | 0.00 | 0.00 | 0.00 | 7927.52 | 0.00 | -197.09 | 0.00 | -11.16 | 0.00 |
| G NE APARTMENT | 05-JAN-18:12 | 0.00 | -1.66 | 0.00 | -6178.32 | 0.00 | 0.00 | 126.21 | 74.01 | 588.62 | 0.00 | 0.00 | 0.00 | 5605.64 | 0.00 | -199.59 | 0.00 | -14.90 | 0.00 |
| G N1 APARTMENT | 15-JAN-22:52 | 0.00 | -54.46 | 0.00 | -5407.96 | 0.00 | 0.00 | 146.60 | 32.89 | 417.92 | 0.00 | 0.00 | 0.00 | 5076.18 | 0.00 | -194.35 | 0.00 | -16.82 | 0.00 |
| G N2 APARTMENT | 15-JAN-22:52 | 0.00 | -54.48 | 0.00 | -5403.50 | 0.00 | 0.00 | 146.61 | 32.89 | 417.92 | 0.00 | 0.00 | 0.00 | 5071.71 | 0.00 | -194.34 | 0.00 | -16.82 | 0.00 |
| G S1 APARTMENT | 15-JAN-22:32 | 0.00 | -51.93 | 0.00 | -5638.44 | 0.00 | 0.00 | 145.07 | 32.89 | 417.92 | 0.00 | 0.00 | 0.00 | 5309.22 | 0.00 | -198.30 | 0.00 | -16.44 | 0.00 |
| G S2 APARTMENT | 15-JAN-22:32 | 0.00 | -51.94 | 0.00 | -5680.03 | 0.00 | 0.00 | 145.07 | 32.89 | 417.92 | 0.00 | 0.00 | 0.00 | 5351.79 | 0.00 | -199.26 | 0.00 | -16.45 | 0.00 |
| M SW APARTMENT | 11-FEB-17:02 | 0.00 | -2.47 | 0.00 | -13796.06 | 0.00 | 0.00 | 290.14 | 109.64 | 1177.25 | 313.88 | 0.00 | 0.00 | 11989.11 | 0.00 | -0.00 | 0.00 | -81.49 | 0.00 |
| M NW APARTMENT | 11-FEB-18:12 | 0.00 | -21.22 | 0.00 | -13293.75 | 0.00 | 0.00 | 252.42 | 148.02 | 1177.25 | 0.00 | 0.00 | 0.00 | 12263.05 | 0.00 | -450.66 | 0.00 | -75.11 | 0.00 |
| M SE APARTMENT | 11-FEB-17:02 | 0.00 | -3.76 | 0.00 | -13229.86 | 0.00 | 0.00 | 290.14 | 109.64 | 1177.25 | 0.00 | 0.00 | 0.00 | 11769.64 | 0.00 | -31.17 | 0.00 | -81.89 | 0.00 |
| M NE APARTMENT | 12-FEB-17:12 | 0.00 | -5.11 | 0.00 | -12757.10 | 0.00 | 0.00 | 150.87 | 109.64 | 1177.25 | 0.00 | 0.00 | 0.00 | 11600.99 | 0.00 | -213.70 | 0.00 | -62.84 | 0.00 |
| M N1 APARTMENT | 12-FEB-17:12 | 0.00 | -14.34 | 0.00 | -11230.60 | 0.00 | 0.00 | 150.87 | 109.64 | 1177.25 | 0.00 | 0.00 | 0.00 | 9972.35 | 0.00 | -126.28 | 0.00 | -38.88 | 0.00 |
| M N2 APARTMENT | 12-FEB-17:12 | 0.00 | -14.33 | 0.00 | -11218.49 | 0.00 | 0.00 | 150.87 | 109.64 | 1177.25 | 0.00 | 0.00 | 0.00 | 9960.35 | 0.00 | -126.39 | 0.00 | -38.90 | 0.00 |
| M S1 APARTMENT | 11-FEB-17:02 | 0.00 | -10.78 | 0.00 | -11735.66 | 0.00 | 0.00 | 290.14 | 109.64 | 1177.25 | 46.63 | 0.00 | 0.00 | 10173.47 | 0.00 | -0.00 | 0.00 | -50.68 | 0.00 |
| M S2 APARTMENT | 11-FEB-17:02 | 0.00 | -10.82 | 0.00 | -11727.30 | 0.00 | 0.00 | 290.14 | 109.64 | 1177.25 | 46.63 | 0.00 | 0.00 | 10165.14 | 0.00 | -0.00 | 0.00 | -50.69 | 0.00 |
| T SW APARTMENT | 27-FEB-16:02 | 0.00 | 14.48 | 0.00 | -7630.04 | 0.00 | 0.00 | 0.00 | 38.37 | 470.90 | 605.93 | 0.00 | 0.00 | 6521.64 | 0.00 | -0.00 | 0.00 | -21.28 | 0.00 |
| T NW APARTMENT | 24-FEB-17:02 | 0.00 | -8.97 | 0.00 | -7352.63 | 0.00 | 0.00 | 66.31 | 54.82 | 588.62 | 103.10 | 0.00 | 0.00 | 6614.22 | 0.00 | -0.00 | 0.00 | -65.48 | 0.00 |
| T SE APARTMENT | 27-FEB-16:02 | 0.00 | 16.14 | 0.00 | -7197.00 | 0.00 | 0.00 | 0.00 | 38.37 | 470.90 | 310.43 | 0.00 | 0.00 | 6380.90 | 0.00 | -0.00 | 0.00 | -19.74 | 0.00 |
| T NE APARTMENT | 11-FEB-18:12 | 0.00 | -9.49 | 0.00 | -6834.54 | 0.00 | 0.00 | 126.21 | 74.01 | 588.62 | 0.00 | 0.00 | 0.00 | 6333.45 | 0.00 | -228.54 | 0.00 | -49.72 | 0.00 |
| T N1 APARTMENT | 11-FEB-18:12 | 0.00 | -13.00 | 0.00 | -6168.01 | 0.00 | 0.00 | 126.21 | 74.01 | 588.62 | 0.00 | 0.00 | 0.00 | 5560.62 | 0.00 | -137.83 | 0.00 | -30.62 | 0.00 |
| T N2 APARTMENT | 11-FEB-18:12 | 0.00 | -13.02 | 0.00 | -6154.21 | 0.00 | 0.00 | 126.21 | 74.01 | 588.62 | 0.00 | 0.00 | 0.00 | 5546.67 | 0.00 | -137.66 | 0.00 | -30.63 | 0.00 |
| T S1 APARTMENT | 27-FEB-16:02 | 0.00 | 14.76 | 0.00 | -6467.57 | 0.00 | 0.00 | 0.00 | 38.37 | 470.90 | 277.24 | 0.00 | 0.00 | 5677.70 | 0.00 | -0.00 | 0.00 | -11.39 | 0.00 |
| T S2 APARTMENT | 27-FEB-16:02 | 0.00 | 14.59 | 0.00 | -6455.44 | 0.00 | 0.00 | 0.00 | 38.37 | 470.90 | 277.18 | 0.00 | 0.00 | 5665.83 | 0.00 | -0.00 | 0.00 | -11.43 | 0.00 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 19-DEC-16:52 | 0.00 | 310.68 | 0.00 | -195907.92 | 0.00 | 0.00 | 1292.75 | 2868.98 | 15265.96 | 2262.73 | 0.00 | 0.00 | 175795.76 | 0.00 | -923.67 | 0.00 | -965.27 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 22-JUN-09:05 | 153.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 406.15 | 551.61 | 0.00 | 22.80 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1144.78 |
| G NW APARTMENT | 22-JUN-09:05 | 152.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.34 | 10.96 | 406.15 | 585.05 | 0.00 | 22.74 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1213.94 |
| OFFICE | 21-JUL-16:01 | 0.00 | 0.00 | 1120.07 | 0.00 | 0.00 | 0.00 | 0.00 | 89.52 | 194.98 | 731.27 | 0.00 | 107.13 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2242.98 |
| G NE APARTMENT | 22-JUN-09:05 | 149.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.40 | 10.96 | 406.15 | 952.12 | 0.00 | 22.37 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1577.33 |
| G N1 APARTMENT | 23-APR-08:55 | 111.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | 10.96 | 394.38 | 255.57 | 0.00 | 6.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -815.09 |
| G N2 APARTMENT | 23-APR-08:55 | 111.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | 10.96 | 394.38 | 255.50 | 0.00 | 6.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -815.06 |
| G S1 APARTMENT | 22-JUN-09:05 | 149.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 406.15 | 335.76 | 0.00 | 13.41 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -915.77 |
| G S2 APARTMENT | 22-JUN-09:05 | 149.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 406.15 | 334.30 | 0.00 | 13.44 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -914.68 |
| M SW APARTMENT | 22-JUN-09:05 | 303.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.93 | 812.30 | 1113.23 | 0.00 | 65.17 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2316.48 |
| M NW APARTMENT | 22-JUN-09:05 | 304.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.54 | 21.93 | 812.30 | 1177.74 | 0.00 | 65.24 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2454.71 |
| M SE APARTMENT | 22-JUN-09:05 | 303.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.93 | 812.30 | 1840.67 | 0.00 | 65.05 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3043.67 |
| M NE APARTMENT | 22-JUN-09:05 | 296.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.54 | 21.93 | 812.30 | 1905.64 | 0.00 | 63.84 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3172.48 |
| M N1 APARTMENT | 23-APR-08:55 | 218.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.99 | 21.93 | 788.75 | 510.70 | 0.00 | 17.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1630.65 |
| M N2 APARTMENT | 23-APR-08:55 | 218.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.96 | 21.93 | 788.75 | 510.48 | 0.00 | 17.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1630.59 |
| M S1 APARTMENT | 22-JUN-09:05 | 297.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.93 | 812.30 | 677.36 | 0.00 | 38.46 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1847.89 |
| M S2 APARTMENT | 22-JUN-09:05 | 297.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.93 | 812.30 | 677.20 | 0.00 | 38.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1847.77 |
| T SW APARTMENT | 22-JUN-09:05 | 150.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 406.15 | 546.17 | 0.00 | 42.79 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1156.68 |
| T NW APARTMENT | 22-JUN-09:05 | 150.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | 10.96 | 406.15 | 576.59 | 0.00 | 42.69 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1222.72 |
| T SE APARTMENT | 22-JUN-09:05 | 146.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 406.15 | 904.01 | 0.00 | 42.03 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1509.97 |
| T NE APARTMENT | 23-APR-08:55 | 106.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | 10.96 | 394.38 | 809.94 | 0.00 | 19.11 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1377.53 |
| T N1 APARTMENT | 22-JUN-09:05 | 149.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | 10.96 | 406.15 | 364.25 | 0.00 | 25.38 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -992.11 |
| T N2 APARTMENT | 22-JUN-09:05 | 148.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | 10.96 | 406.15 | 363.98 | 0.00 | 25.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -991.42 |
| T S1 APARTMENT | 22-JUN-09:05 | 153.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 406.15 | 332.70 | 0.00 | 25.94 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -929.36 |
| T S2 APARTMENT | 22-JUN-09:05 | 153.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 406.15 | 332.42 | 0.00 | 25.91 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -928.77 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 22-JUN-09:05 | -2992.92 | 7655.05 | 0.00 | -7655.05 | 0.00 | 0.00 | 1121.65 | 2019.26 | 13258.13 | 18471.74 | 0.00 | 1337.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33215.29 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3997 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3997 | 0.0649 | 1.0000 | Not calculated | 0.0260 | 0.0649 | ||
| SPLIT GNW | 0.3872 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3872 | 0.0670 | 1.0000 | Not calculated | 0.0260 | 0.0670 | ||
| SPLIT OFFICE | 0.4586 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4586 | 0.0831 | 1.0000 | Not calculated | 0.0381 | 0.0831 | ||
| SPLIT GNE | 0.3705 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3705 | 0.0701 | 1.0000 | Not calculated | 0.0260 | 0.0701 | ||
| SPLIT GN1 | 0.3183 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3183 | 0.0815 | 1.0000 | Not calculated | 0.0260 | 0.0815 | ||
| SPLIT GN2 | 0.3180 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3180 | 0.0816 | 1.0000 | Not calculated | 0.0260 | 0.0816 | ||
| SPLIT GS1 | 0.3320 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3320 | 0.0782 | 1.0000 | Not calculated | 0.0260 | 0.0782 | ||
| SPLIT GS2 | 0.3347 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3347 | 0.0775 | 1.0000 | Not calculated | 0.0260 | 0.0775 | ||
| SPLIT MSW | 0.8356 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8356 | 0.0621 | 1.0000 | Not calculated | 0.0519 | 0.0621 | ||
| SPLIT MNW | 0.8082 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8082 | 0.0642 | 1.0000 | Not calculated | 0.0519 | 0.0642 | ||
| SPLIT MSE | 0.7947 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7947 | 0.0653 | 1.0000 | Not calculated | 0.0519 | 0.0653 | ||
| SPLIT MNE | 0.7675 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7675 | 0.0676 | 1.0000 | Not calculated | 0.0519 | 0.0676 | ||
| SPLIT MN1 | 0.6573 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6573 | 0.0790 | 1.0000 | Not calculated | 0.0519 | 0.0790 | ||
| SPLIT MN2 | 0.6565 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6565 | 0.0791 | 1.0000 | Not calculated | 0.0519 | 0.0791 | ||
| SPLIT MS1 | 0.6876 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6876 | 0.0755 | 1.0000 | Not calculated | 0.0519 | 0.0755 | ||
| SPLIT MS2 | 0.6868 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6868 | 0.0756 | 1.0000 | Not calculated | 0.0519 | 0.0756 | ||
| SPLIT TSW | 0.4571 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4571 | 0.0568 | 1.0000 | Not calculated | 0.0260 | 0.0568 | ||
| SPLIT TNW | 0.4459 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4459 | 0.0582 | 1.0000 | Not calculated | 0.0260 | 0.0582 | ||
| SPLIT TSE | 0.4280 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4280 | 0.0606 | 1.0000 | Not calculated | 0.0260 | 0.0606 | ||
| SPLIT TNE | 0.4168 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4168 | 0.0623 | 1.0000 | Not calculated | 0.0260 | 0.0623 | ||
| SPLIT TN1 | 0.3695 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3695 | 0.0702 | 1.0000 | Not calculated | 0.0260 | 0.0702 | ||
| SPLIT TN2 | 0.3685 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3685 | 0.0704 | 1.0000 | Not calculated | 0.0260 | 0.0704 | ||
| SPLIT TS1 | 0.3816 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3816 | 0.0680 | 1.0000 | Not calculated | 0.0260 | 0.0680 | ||
| SPLIT TS2 | 0.3806 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3806 | 0.0682 | 1.0000 | Not calculated | 0.0260 | 0.0682 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3997 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3997 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0649 | ||
| SPLIT GNW | 0.3872 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3872 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0670 | ||
| SPLIT OFFICE | 0.4586 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4586 | 1.0000 | 1.0000 | Not calculated | 0.0381 | 0.0831 | ||
| SPLIT GNE | 0.3705 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3705 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0701 | ||
| SPLIT GN1 | 0.3183 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3183 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0815 | ||
| SPLIT GN2 | 0.3180 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3180 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0816 | ||
| SPLIT GS1 | 0.3320 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3320 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0782 | ||
| SPLIT GS2 | 0.3347 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3347 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0775 | ||
| SPLIT MSW | 0.8356 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8356 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0621 | ||
| SPLIT MNW | 0.8082 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8082 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0642 | ||
| SPLIT MSE | 0.7947 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7947 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0653 | ||
| SPLIT MNE | 0.7675 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7675 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0676 | ||
| SPLIT MN1 | 0.6573 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6573 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0790 | ||
| SPLIT MN2 | 0.6565 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6565 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0791 | ||
| SPLIT MS1 | 0.6876 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6876 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0755 | ||
| SPLIT MS2 | 0.6868 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6868 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0756 | ||
| SPLIT TSW | 0.4571 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4571 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0568 | ||
| SPLIT TNW | 0.4459 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4459 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0582 | ||
| SPLIT TSE | 0.4280 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4280 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0606 | ||
| SPLIT TNE | 0.4168 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4168 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0623 | ||
| SPLIT TN1 | 0.3695 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3695 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0702 | ||
| SPLIT TN2 | 0.3685 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3685 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0704 | ||
| SPLIT TS1 | 0.3816 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3816 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0680 | ||
| SPLIT TS2 | 0.3806 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3806 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0682 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G NW APARTMENT | SPLIT GNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| OFFICE | SPLIT OFFICE | 0.000000 | 4.7495 | 0.000432 | 88.25 | 0.0381 | 1.0000 | 0.0381 | 1.000 | 0.0381 |
| G NE APARTMENT | SPLIT GNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N1 APARTMENT | SPLIT GN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N2 APARTMENT | SPLIT GN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S1 APARTMENT | SPLIT GS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S2 APARTMENT | SPLIT GS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| M SW APARTMENT | SPLIT MSW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NW APARTMENT | SPLIT MNW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M SE APARTMENT | SPLIT MSE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NE APARTMENT | SPLIT MNE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N1 APARTMENT | SPLIT MN1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N2 APARTMENT | SPLIT MN2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S1 APARTMENT | SPLIT MS1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S2 APARTMENT | SPLIT MS2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| T SW APARTMENT | SPLIT TSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NW APARTMENT | SPLIT TNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T SE APARTMENT | SPLIT TSE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NE APARTMENT | SPLIT TNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N1 APARTMENT | SPLIT TN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N2 APARTMENT | SPLIT TN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S1 APARTMENT | SPLIT TS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S2 APARTMENT | SPLIT TS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| SPLIT GSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT OFFICE | 0.000000 | 4.75 | 0.000432 | 88.2493 | 0.0381 | 0.0381 | 0.0381 |
| SPLIT GNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT MSW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MSE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT TSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TSE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3997 | 0.3997 | 0.3997 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3872 | 0.3872 | 0.3872 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4586 | 0.4586 | 0.4586 | No | 0.0381 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3705 | 0.3705 | 0.3705 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3183 | 0.3183 | 0.3183 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3180 | 0.3180 | 0.3180 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3320 | 0.3320 | 0.3320 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3347 | 0.3347 | 0.3347 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8356 | 0.8356 | 0.8356 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8082 | 0.8082 | 0.8082 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7947 | 0.7947 | 0.7947 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7675 | 0.7675 | 0.7675 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6573 | 0.6573 | 0.6573 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6565 | 0.6565 | 0.6565 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6876 | 0.6876 | 0.6876 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6868 | 0.6868 | 0.6868 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4571 | 0.4571 | 0.4571 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4459 | 0.4459 | 0.4459 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4280 | 0.4280 | 0.4280 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4168 | 0.4168 | 0.4168 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3695 | 0.3695 | 0.3695 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3685 | 0.3685 | 0.3685 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3816 | 0.3816 | 0.3816 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3806 | 0.3806 | 0.3806 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3997 | 0.3997 | 0.3997 | 0.3997 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3872 | 0.3872 | 0.3872 | 0.3872 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4586 | 0.4586 | 0.4586 | 0.4586 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3705 | 0.3705 | 0.3705 | 0.3705 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.3183 | 0.3183 | 0.3183 | 0.3183 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.3180 | 0.3180 | 0.3180 | 0.3180 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3320 | 0.3320 | 0.3320 | 0.3320 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3347 | 0.3347 | 0.3347 | 0.3347 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.8356 | 0.8356 | 0.8356 | 0.8356 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.8082 | 0.8082 | 0.8082 | 0.8082 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.7947 | 0.7947 | 0.7947 | 0.7947 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.7675 | 0.7675 | 0.7675 | 0.7675 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6573 | 0.6573 | 0.6573 | 0.6573 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6565 | 0.6565 | 0.6565 | 0.6565 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.6876 | 0.6876 | 0.6876 | 0.6876 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.6868 | 0.6868 | 0.6868 | 0.6868 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4571 | 0.4571 | 0.4571 | 0.4571 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4459 | 0.4459 | 0.4459 | 0.4459 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4280 | 0.4280 | 0.4280 | 0.4280 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.4168 | 0.4168 | 0.4168 | 0.4168 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3695 | 0.3695 | 0.3695 | 0.3695 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3685 | 0.3685 | 0.3685 | 0.3685 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3816 | 0.3816 | 0.3816 | 0.3816 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3806 | 0.3806 | 0.3806 | 0.3806 | 0.0260 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3997 | 0.3997 | 0.3997 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3872 | 0.3872 | 0.3872 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4586 | 0.4586 | 0.4586 | No | 0.0381 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3705 | 0.3705 | 0.3705 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3183 | 0.3183 | 0.3183 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3180 | 0.3180 | 0.3180 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3320 | 0.3320 | 0.3320 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3347 | 0.3347 | 0.3347 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8356 | 0.8356 | 0.8356 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8082 | 0.8082 | 0.8082 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7947 | 0.7947 | 0.7947 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7675 | 0.7675 | 0.7675 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6573 | 0.6573 | 0.6573 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6565 | 0.6565 | 0.6565 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6876 | 0.6876 | 0.6876 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6868 | 0.6868 | 0.6868 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4571 | 0.4571 | 0.4571 | No | 0.0260 | 0.7038 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4459 | 0.4459 | 0.4459 | No | 0.0260 | 0.8734 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4280 | 0.4280 | 0.4280 | No | 0.0260 | 0.7065 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4168 | 0.4168 | 0.4168 | No | 0.0260 | 0.8772 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3695 | 0.3695 | 0.3695 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3685 | 0.3685 | 0.3685 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3816 | 0.3816 | 0.3816 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3806 | 0.3806 | 0.3806 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3997 | 0.3997 | 0.3997 | 0.3997 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3872 | 0.3872 | 0.3872 | 0.3872 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4586 | 0.4586 | 0.4586 | 0.4586 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3705 | 0.3705 | 0.3705 | 0.3705 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.3183 | 0.3183 | 0.3183 | 0.3183 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.3180 | 0.3180 | 0.3180 | 0.3180 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3320 | 0.3320 | 0.3320 | 0.3320 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3347 | 0.3347 | 0.3347 | 0.3347 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.8356 | 0.8356 | 0.8356 | 0.8356 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.8082 | 0.8082 | 0.8082 | 0.8082 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.7947 | 0.7947 | 0.7947 | 0.7947 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.7675 | 0.7675 | 0.7675 | 0.7675 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6573 | 0.6573 | 0.6573 | 0.6573 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6565 | 0.6565 | 0.6565 | 0.6565 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.6876 | 0.6876 | 0.6876 | 0.6876 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.6868 | 0.6868 | 0.6868 | 0.6868 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4571 | 0.4571 | 0.4571 | 0.4571 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4459 | 0.4459 | 0.4459 | 0.4459 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4280 | 0.4280 | 0.4280 | 0.4280 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.4168 | 0.4168 | 0.4168 | 0.4168 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3695 | 0.3695 | 0.3695 | 0.3695 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3685 | 0.3685 | 0.3685 | 0.3685 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3816 | 0.3816 | 0.3816 | 0.3816 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3806 | 0.3806 | 0.3806 | 0.3806 | 0.0260 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
| Total gross floor area [m2] | 3134.61 |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| G SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| OFFICE | 88.25 | 88.25 | 0.00 | 33.56 |
| G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| G CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| M CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| Totals | 3134.61 | 2823.98 | 310.64 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.00 |
| Number of hours not met | 0.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 422.00 | 36725.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 67.97 | 3560.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsPlugIn | 5.02 | 479.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 33.07 | 2101.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 67.41 | 3772.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 0.49 | 31.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 386.12 | 18442.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 159.24 | 9758.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- General | 0.46 | 14.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 0.00 | 0.00 | 295.65 | 21361.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 454.01 | 1141.78 |
| Natural Gas | 0.00 | 295.65 |
| Additional | 0.00 | 0.00 |
| Total | 454.01 | 1437.43 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 23.29 |
| Space Heating | 0.00 |
| Space Cooling | 134.63 |
| Fans (All) | 50.80 |
| Service Water Heating | 0.00 |
| Receptacle Equipment | 144.84 |
| Miscellaneous (All) | 364.25 |
| Subtotal | 364.25 |
| Natural Gas [MJ/m2] | |
| Space Heating | 0.00 |
| Service Water Heating | 94.32 |
| Miscellaneous (All) | 94.32 |
| Subtotal | 94.32 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 5.08 |
| Space Heating | 0.00 |
| Space Cooling | 29.36 |
| Fans (All) | 11.08 |
| Service Water Heating | 20.57 |
| Receptacle Equipment | 31.58 |
| Miscellaneous | 2.33 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| ELEVATOR_RUNNING_SCH | 146. | 3285. |
| ELEVATOR_STANDBY_SCH | 8201. | 8760. |
| OCC_APT_SCH_STAY_HOME_FAMILY | 5993. | 8760. |
| OCC_APT_SCH_CORRIDOR | 5993. | 8760. |
| OCC_APT_SCH_WORKING_FAMILY | 5845. | 6055. |
| OCC_OFF_SCH | 2210. | 2340. |
| OCC_OFF_W_SB_SCH | 1820. | 1820. |
| LTG_SCH_OFFICE | 2435. | 8760. |
| LTG_SCH_CORRIDOR | 6570. | 8760. |
| LTG_SCH_APARTMENT_HARDWIRED | 527. | 8760. |
| LTG_SCH_APARTMENT_PLUGIN | 527. | 8760. |
| EQP_APT_SCH | 5763. | 8760. |
| EQP_OFF_SCH | 3614. | 8760. |
| INF_APT_SCH | 8760. | 8760. |
| INF_OFF_SCH | 8760. | 8760. |
| INF_COR_SCH | 8760. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1466. | 5840. |
| ALL OFF | 0. | 0. |
| ALL ON | 8760. | 8760. |
| ALWAYS_ON | 8760. | 8760. |
| ALLON_EXCEPT_DD | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| FAN_OFF_W_SB_SCH | 8240. | 8240. |
| APT_DHW_SCH | 4592. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 5840. | 5840. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_APT_SCH | APTHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| HTGSETP_DESIGN_OFF_SCH | OFFHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| CLGSETP_APT_SCH | APTCOOLINGSETPOINT | July | 24.00 | 365 | 24.00 | 365 |
| CLGSETP_DESIGN_OFF_SCH | OFFCOOLINGSETPOINT | July | 23.90 | 365 | 23.90 | 365 |
| S HTGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| S CLGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| N HTGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| N CLGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_OFF_SCH_NO_OPTIMUM | OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
| CLGSETP_OFF_SCH_NO_OPTIMUM | OFFICE DUAL SP CONTROL | July | 24.00 | 365 | 29.40 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
| OFFICE | 3352.50 | 4396.00 | 1011.50 | 0.00 | 0.00 |
| G NE APARTMENT | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8743.50 | 16.50 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8716.83 | 43.17 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8737.67 | 22.33 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8720.17 | 39.83 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8733.17 | 26.83 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 1616.67 | 5294.67 | 1848.67 | 0.00 | 0.00 |
| G CORRIDOR | 1415.00 | 4488.17 | 2715.00 | 141.83 | 0.00 |
| M CORRIDOR | 38.83 | 8659.33 | 61.83 | 0.00 | 0.00 |
| Min | 38.83 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 8659.33 | 2715.00 | 141.83 | 0.00 |
| Average | 7690.33 | 855.64 | 208.78 | 5.25 | 0.00 |
| Sum | 207638.83 | 23102.33 | 5637.00 | 141.83 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 11818.83 | 11.17 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10584.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10584.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10584.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10584.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11809.83 | 20.17 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11798.67 | 31.33 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11827.67 | 2.33 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11828.00 | 2.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11828.33 | 1.67 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11828.33 | 1.67 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11805.83 | 24.17 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10571.33 | 13.67 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11815.00 | 15.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10582.50 | 2.50 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10582.00 | 3.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10582.33 | 2.67 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11815.33 | 14.67 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11815.33 | 14.67 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 4580.83 | 14042.83 | 4371.33 | 0.00 | 0.00 |
| G CORRIDOR | 3036.33 | 11444.67 | 8145.50 | 368.50 | 0.00 |
| M CORRIDOR | 99.33 | 22735.50 | 160.17 | 0.00 | 0.00 |
| Min | 99.33 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 11828.33 | 22735.50 | 8145.50 | 368.50 | 0.00 |
| Average | 10063.13 | 1792.04 | 469.52 | 13.65 | 0.00 |
| Sum | 271704.50 | 48385.00 | 12677.00 | 368.50 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 8082.67 | 677.33 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8031.33 | 728.67 | 0.00 | 0.00 | 0.00 |
| OFFICE | 3108.50 | 5209.83 | 441.67 | 0.00 | 0.00 |
| G NE APARTMENT | 8007.00 | 753.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 7760.17 | 999.83 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 7759.00 | 1001.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 7859.50 | 900.50 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8024.00 | 736.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 7834.67 | 925.33 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 7764.67 | 995.33 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 7815.83 | 944.17 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 7733.50 | 1026.50 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 7424.50 | 1335.50 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 7424.17 | 1335.83 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 7538.00 | 1222.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 7521.83 | 1238.17 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 7656.83 | 1103.17 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 7574.00 | 1186.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 7644.17 | 1115.83 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 7549.83 | 1210.17 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 7437.33 | 1322.67 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 7436.33 | 1323.67 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 7524.17 | 1235.83 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 7522.33 | 1237.67 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 5121.33 | 3638.67 | 0.00 | 0.00 |
| G CORRIDOR | 963.17 | 5335.50 | 2058.83 | 402.17 | 0.33 |
| M CORRIDOR | 0.00 | 5150.50 | 3609.50 | 0.00 | 0.00 |
| Min | 0.00 | 677.33 | 0.00 | 0.00 | 0.00 |
| Max | 8082.67 | 5335.50 | 3638.67 | 402.17 | 0.33 |
| Average | 6703.61 | 1680.42 | 361.06 | 14.90 | 0.01 |
| Sum | 180997.50 | 45371.33 | 9748.67 | 402.17 | 0.33 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 10898.83 | 931.17 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 9747.17 | 837.83 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6974.67 | 25.33 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 9724.33 | 860.67 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 9288.33 | 1296.67 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 9287.00 | 1298.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 10507.67 | 1322.33 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 10792.83 | 1037.17 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 10480.00 | 1350.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 9301.83 | 1283.17 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 10419.17 | 1410.83 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 9228.50 | 1356.50 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8797.33 | 1787.67 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8796.83 | 1788.17 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 9983.50 | 1846.50 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 9955.83 | 1874.17 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 10199.83 | 1630.17 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8982.33 | 1602.67 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 10145.50 | 1684.50 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8917.00 | 1668.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8757.33 | 1827.67 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8755.50 | 1829.50 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 9962.50 | 1867.50 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 9960.83 | 1869.17 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 13513.00 | 9482.00 | 0.00 | 0.00 |
| G CORRIDOR | 1722.67 | 13498.50 | 6426.17 | 1347.00 | 0.67 |
| M CORRIDOR | 0.00 | 13777.00 | 9218.00 | 0.00 | 0.00 |
| Min | 0.00 | 25.33 | 0.00 | 0.00 | 0.00 |
| Max | 10898.83 | 13777.00 | 9482.00 | 1347.00 | 0.67 |
| Average | 8577.31 | 2780.51 | 930.60 | 49.89 | 0.02 |
| Sum | 231587.33 | 75073.83 | 25126.17 | 1347.00 | 0.67 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:23
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.235 |
| February | 20.749 |
| March | 23.120 |
| April | 26.486 |
| May | 31.365 |
| June | 32.970 |
| July | 35.085 |
| August | 35.314 |
| September | 32.488 |
| October | 29.531 |
| November | 25.532 |
| December | 21.128 |
| Annual Sum or Average | 27.790 |
| Minimum of Months | 19.235 |
| Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.235 |
| February | 20.749 |
| March | 23.120 |
| April | 26.486 |
| May | 31.365 |
| June | 32.970 |
| July | 35.085 |
| August | 35.314 |
| September | 32.488 |
| October | 29.531 |
| November | 25.532 |
| December | 21.128 |
| Annual Sum or Average | 27.790 |
| Minimum of Months | 19.235 |
| Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.235 |
| February | 20.749 |
| March | 23.120 |
| April | 26.486 |
| May | 31.365 |
| June | 32.970 |
| July | 35.085 |
| August | 35.314 |
| September | 32.488 |
| October | 29.531 |
| November | 25.532 |
| December | 21.128 |
| Annual Sum or Average | 27.790 |
| Minimum of Months | 19.235 |
| Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.235 |
| February | 20.749 |
| March | 23.120 |
| April | 26.486 |
| May | 31.365 |
| June | 32.970 |
| July | 35.085 |
| August | 35.314 |
| September | 32.488 |
| October | 29.531 |
| November | 25.532 |
| December | 21.128 |
| Annual Sum or Average | 27.790 |
| Minimum of Months | 19.235 |
| Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.235 |
| February | 20.749 |
| March | 23.120 |
| April | 26.486 |
| May | 31.365 |
| June | 32.970 |
| July | 35.085 |
| August | 35.314 |
| September | 32.488 |
| October | 29.531 |
| November | 25.532 |
| December | 21.128 |
| Annual Sum or Average | 27.790 |
| Minimum of Months | 19.235 |
| Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.235 |
| February | 20.749 |
| March | 23.120 |
| April | 26.486 |
| May | 31.365 |
| June | 32.970 |
| July | 35.085 |
| August | 35.314 |
| September | 32.488 |
| October | 29.531 |
| November | 25.532 |
| December | 21.128 |
| Annual Sum or Average | 27.790 |
| Minimum of Months | 19.235 |
| Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.235 |
| February | 20.749 |
| March | 23.120 |
| April | 26.486 |
| May | 31.365 |
| June | 32.970 |
| July | 35.085 |
| August | 35.314 |
| September | 32.488 |
| October | 29.531 |
| November | 25.532 |
| December | 21.128 |
| Annual Sum or Average | 27.790 |
| Minimum of Months | 19.235 |
| Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.235 |
| February | 20.749 |
| March | 23.120 |
| April | 26.486 |
| May | 31.365 |
| June | 32.970 |
| July | 35.085 |
| August | 35.314 |
| September | 32.488 |
| October | 29.531 |
| November | 25.532 |
| December | 21.128 |
| Annual Sum or Average | 27.790 |
| Minimum of Months | 19.235 |
| Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.235 |
| February | 20.749 |
| March | 23.120 |
| April | 26.486 |
| May | 31.365 |
| June | 32.970 |
| July | 35.085 |
| August | 35.314 |
| September | 32.488 |
| October | 29.531 |
| November | 25.532 |
| December | 21.128 |
| Annual Sum or Average | 27.790 |
| Minimum of Months | 19.235 |
| Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.143830E+10 | 6609.70 | 26-JAN-16:42 | 21.08 | 15.08 | 0.142377E+09 | 107.20 | 07-JAN-16:40 | 21.08 | 15.08 |
| February | 0.150326E+10 | 6618.03 | 11-FEB-17:02 | 20.83 | 14.97 | 0.125178E+09 | 106.61 | 26-FEB-16:40 | 22.13 | 16.27 |
| March | 0.200664E+10 | 6575.84 | 07-MAR-15:42 | 23.67 | 15.43 | 0.131063E+09 | 100.82 | 18-MAR-18:10 | 22.83 | 16.10 |
| April | 0.250162E+10 | 6412.63 | 06-APR-08:22 | 26.50 | 15.88 | 0.126700E+09 | 95.59 | 04-APR-20:30 | 26.50 | 15.88 |
| May | 0.361193E+10 | 5863.35 | 15-MAY-07:42 | 26.50 | 17.86 | 0.126140E+09 | 92.51 | 15-MAY-06:00 | 26.50 | 17.86 |
| June | 0.393692E+10 | 5146.59 | 22-JUN-09:02 | 34.63 | 22.51 | 0.120422E+09 | 70.27 | 03-JUN-09:00 | 34.63 | 22.51 |
| July | 0.468736E+10 | 2671.50 | 21-JUL-17:01 | 42.00 | 23.59 | 0.129276E+09 | 70.27 | 20-JUL-21:00 | 42.00 | 23.59 |
| August | 0.515669E+10 | 2777.07 | 10-AUG-16:01 | 41.33 | 30.18 | 0.123963E+09 | 70.27 | 26-AUG-06:10 | 29.97 | 28.38 |
| September | 0.468146E+10 | 5261.52 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124216E+09 | 97.05 | 25-SEP-06:00 | 25.60 | 21.36 |
| October | 0.445762E+10 | 6356.22 | 20-OCT-07:32 | 24.30 | 16.01 | 0.128864E+09 | 100.52 | 21-OCT-08:30 | 26.50 | 14.81 |
| November | 0.348024E+10 | 6287.63 | 21-NOV-22:52 | 21.00 | 16.02 | 0.128730E+09 | 100.27 | 30-NOV-22:10 | 22.20 | 17.52 |
| December | 0.211183E+10 | 6613.23 | 16-DEC-13:52 | 21.00 | 14.47 | 0.142347E+09 | 105.25 | 24-DEC-16:19 | 23.33 | 20.19 |
| Annual Sum or Average | 0.395739E+11 | 0.154927E+10 | ||||||||
| Minimum of Months | 0.143830E+10 | 2671.50 | 20.83 | 14.47 | 0.120422E+09 | 70.27 | 21.08 | 14.81 | ||
| Maximum of Months | 0.515669E+10 | 6618.03 | 42.00 | 30.18 | 0.142377E+09 | 107.20 | 42.00 | 28.38 |
Report: ZoneCoolingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.917693E+09 | 6405.56 | 05-JAN-18:12 | 20.83 | 16.50 | 0.142810E+09 | 96.34 | 29-JAN-21:19 | 23.20 | 19.38 |
| February | 0.105780E+10 | 6411.68 | 12-FEB-17:12 | 20.67 | 14.90 | 0.126667E+09 | 96.49 | 11-FEB-21:10 | 20.67 | 14.90 |
| March | 0.164063E+10 | 6374.04 | 06-MAR-19:32 | 21.07 | 14.89 | 0.135789E+09 | 94.28 | 30-MAR-20:10 | 23.00 | 20.23 |
| April | 0.229010E+10 | 6234.63 | 06-APR-08:22 | 26.50 | 15.88 | 0.127082E+09 | 93.87 | 04-APR-20:30 | 26.50 | 15.88 |
| May | 0.361951E+10 | 5692.06 | 15-MAY-07:32 | 26.00 | 17.61 | 0.129276E+09 | 84.36 | 03-MAY-05:00 | 26.00 | 17.61 |
| June | 0.404724E+10 | 4993.78 | 22-JUN-09:02 | 34.63 | 22.51 | 0.124648E+09 | 70.27 | 27-JUN-04:19 | 28.53 | 26.68 |
| July | 0.472386E+10 | 2700.67 | 21-JUL-17:01 | 42.00 | 23.59 | 0.128775E+09 | 70.27 | 20-JUL-23:40 | 42.00 | 23.59 |
| August | 0.504234E+10 | 2743.70 | 05-AUG-17:01 | 40.83 | 26.31 | 0.128775E+09 | 70.27 | 26-AUG-05:40 | 30.33 | 28.76 |
| September | 0.430823E+10 | 5086.81 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124851E+09 | 88.33 | 30-SEP-05:40 | 25.60 | 21.36 |
| October | 0.382432E+10 | 6201.68 | 21-OCT-08:42 | 28.17 | 14.74 | 0.129834E+09 | 87.27 | 31-OCT-05:49 | 23.58 | 22.53 |
| November | 0.275607E+10 | 6100.40 | 21-NOV-22:52 | 21.00 | 16.02 | 0.128818E+09 | 96.80 | 30-NOV-22:10 | 22.20 | 17.52 |
| December | 0.151453E+10 | 6410.60 | 16-DEC-18:42 | 20.92 | 15.33 | 0.141335E+09 | 97.59 | 16-DEC-21:10 | 20.02 | 14.70 |
| Annual Sum or Average | 0.357423E+11 | 0.156866E+10 | ||||||||
| Minimum of Months | 0.917693E+09 | 2700.67 | 20.67 | 14.74 | 0.124648E+09 | 70.27 | 20.02 | 14.70 | ||
| Maximum of Months | 0.504234E+10 | 6411.68 | 42.00 | 26.31 | 0.142810E+09 | 97.59 | 42.00 | 28.76 |
Report: ZoneCoolingSummaryMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.140324E+10 | 7868.22 | 04-JAN-07:01 | 13.75 | 11.26 | 67289678.55 | 133.53 | 09-JAN-13:00 | 24.00 | 18.76 |
| February | 0.137844E+10 | 7907.74 | 13-FEB-07:01 | 13.33 | 11.04 | 63925617.26 | 133.54 | 07-FEB-15:39 | 13.33 | 11.04 |
| March | 0.170901E+10 | 7795.59 | 07-MAR-07:01 | 14.58 | 11.78 | 77384197.59 | 133.54 | 28-MAR-15:39 | 27.90 | 22.09 |
| April | 0.176153E+10 | 7931.41 | 24-APR-06:01 | 21.15 | 13.71 | 67290378.27 | 133.54 | 10-APR-15:20 | 21.15 | 13.71 |
| May | 0.259314E+10 | 7899.35 | 08-MAY-06:01 | 26.18 | 15.59 | 74022847.20 | 133.55 | 30-MAY-08:00 | 32.00 | 25.35 |
| June | 0.279312E+10 | 7724.19 | 02-JUN-06:01 | 27.33 | 18.09 | 74024313.90 | 133.55 | 26-JUN-08:50 | 32.67 | 27.62 |
| July | 0.296770E+10 | 7719.30 | 03-JUL-06:01 | 28.20 | 16.17 | 67297485.54 | 133.63 | 17-JUL-07:10 | 31.50 | 26.90 |
| August | 0.358377E+10 | 6487.99 | 07-AUG-06:01 | 31.98 | 22.90 | 77393395.33 | 133.72 | 22-AUG-07:10 | 31.58 | 28.58 |
| September | 0.308201E+10 | 6909.15 | 26-SEP-06:01 | 26.10 | 17.87 | 67297156.06 | 133.57 | 11-SEP-07:10 | 26.10 | 17.87 |
| October | 0.305667E+10 | 8003.81 | 20-OCT-06:01 | 23.82 | 15.96 | 70660137.84 | 133.55 | 02-OCT-07:00 | 23.82 | 15.96 |
| November | 0.242898E+10 | 7690.96 | 21-NOV-07:01 | 19.67 | 16.11 | 67294981.99 | 133.55 | 01-NOV-15:39 | 19.67 | 16.11 |
| December | 0.171544E+10 | 7969.66 | 18-DEC-07:01 | 14.00 | 10.71 | 67291638.05 | 133.54 | 04-DEC-10:39 | 14.00 | 10.71 |
| Annual Sum or Average | 0.284731E+11 | 0.841172E+09 | ||||||||
| Minimum of Months | 0.137844E+10 | 6487.99 | 13.33 | 10.71 | 63925617.26 | 133.53 | 13.33 | 10.71 | ||
| Maximum of Months | 0.358377E+10 | 8003.81 | 31.98 | 22.90 | 77393395.33 | 133.72 | 32.67 | 28.58 |
Report: ZoneCoolingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.924836E+09 | 6179.92 | 05-JAN-18:12 | 20.83 | 16.50 | 0.142659E+09 | 96.00 | 29-JAN-21:19 | 23.20 | 19.38 |
| February | 0.105291E+10 | 6176.57 | 12-FEB-17:12 | 20.67 | 14.90 | 0.126446E+09 | 94.41 | 11-FEB-21:10 | 20.67 | 14.90 |
| March | 0.161724E+10 | 6141.47 | 05-MAR-14:22 | 21.00 | 15.03 | 0.135649E+09 | 93.24 | 30-MAR-20:10 | 23.00 | 20.23 |
| April | 0.231794E+10 | 6026.08 | 06-APR-08:22 | 26.50 | 15.88 | 0.127172E+09 | 92.86 | 04-APR-20:30 | 26.50 | 15.88 |
| May | 0.366739E+10 | 5487.58 | 15-MAY-07:32 | 26.00 | 17.61 | 0.129293E+09 | 84.39 | 03-MAY-05:00 | 26.00 | 17.61 |
| June | 0.406202E+10 | 4861.82 | 22-JUN-09:02 | 34.63 | 22.51 | 0.124651E+09 | 70.27 | 27-JUN-04:19 | 28.53 | 26.68 |
| July | 0.474356E+10 | 2537.10 | 21-JUL-17:01 | 42.00 | 23.59 | 0.128775E+09 | 70.27 | 20-JUL-23:40 | 42.00 | 23.59 |
| August | 0.506607E+10 | 2567.06 | 05-AUG-17:01 | 40.83 | 26.31 | 0.128775E+09 | 70.27 | 26-AUG-05:10 | 30.83 | 29.25 |
| September | 0.432556E+10 | 4905.10 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124851E+09 | 88.25 | 30-SEP-05:40 | 25.60 | 21.36 |
| October | 0.384848E+10 | 5990.65 | 21-OCT-08:42 | 28.17 | 14.74 | 0.129848E+09 | 87.18 | 31-OCT-05:49 | 23.58 | 22.53 |
| November | 0.275825E+10 | 5879.63 | 21-NOV-22:52 | 21.00 | 16.02 | 0.128977E+09 | 96.49 | 30-NOV-22:10 | 22.20 | 17.52 |
| December | 0.150254E+10 | 6176.05 | 16-DEC-18:42 | 20.92 | 15.33 | 0.141350E+09 | 98.25 | 16-DEC-21:10 | 20.02 | 14.70 |
| Annual Sum or Average | 0.358868E+11 | 0.156845E+10 | ||||||||
| Minimum of Months | 0.924836E+09 | 2537.10 | 20.67 | 14.74 | 0.124651E+09 | 70.27 | 20.02 | 14.70 | ||
| Maximum of Months | 0.506607E+10 | 6179.92 | 42.00 | 26.31 | 0.142659E+09 | 98.25 | 42.00 | 29.25 |
Report: ZoneCoolingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.970080E+09 | 5462.41 | 15-JAN-22:52 | 16.00 | 12.61 | 0.142332E+09 | 95.87 | 25-JAN-22:10 | 19.25 | 14.67 |
| February | 0.105252E+10 | 5454.97 | 11-FEB-18:12 | 19.80 | 14.36 | 0.126751E+09 | 96.98 | 11-FEB-21:10 | 19.78 | 14.55 |
| March | 0.150278E+10 | 5427.56 | 07-MAR-20:52 | 20.00 | 14.20 | 0.135931E+09 | 92.46 | 18-MAR-20:40 | 22.00 | 15.86 |
| April | 0.197180E+10 | 5302.37 | 06-APR-08:22 | 26.50 | 15.88 | 0.127252E+09 | 92.38 | 04-APR-20:00 | 26.50 | 15.88 |
| May | 0.293424E+10 | 4812.44 | 15-MAY-07:32 | 26.00 | 17.61 | 0.129276E+09 | 84.51 | 03-MAY-05:00 | 26.00 | 17.61 |
| June | 0.321915E+10 | 4166.86 | 22-JUN-09:02 | 34.63 | 22.51 | 0.124646E+09 | 70.27 | 27-JUN-03:20 | 29.20 | 27.61 |
| July | 0.370021E+10 | 1941.93 | 21-JUL-17:16 | 42.00 | 23.65 | 0.128775E+09 | 70.27 | 20-JUL-22:40 | 42.00 | 23.65 |
| August | 0.389325E+10 | 1965.89 | 05-AUG-17:17 | 40.67 | 26.29 | 0.128775E+09 | 70.27 | 26-AUG-04:19 | 30.87 | 29.38 |
| September | 0.337092E+10 | 4211.33 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124834E+09 | 86.49 | 30-SEP-05:40 | 25.60 | 21.36 |
| October | 0.306021E+10 | 5269.16 | 21-OCT-08:42 | 28.17 | 14.74 | 0.129765E+09 | 85.76 | 31-OCT-05:49 | 23.58 | 22.53 |
| November | 0.230483E+10 | 5165.25 | 21-NOV-22:52 | 21.00 | 16.02 | 0.128639E+09 | 95.18 | 30-NOV-22:10 | 22.20 | 17.52 |
| December | 0.142058E+10 | 5449.16 | 16-DEC-18:42 | 20.92 | 15.33 | 0.141129E+09 | 99.09 | 16-DEC-21:10 | 20.02 | 14.70 |
| Annual Sum or Average | 0.294006E+11 | 0.156810E+10 | ||||||||
| Minimum of Months | 0.970080E+09 | 1941.93 | 16.00 | 12.61 | 0.124646E+09 | 70.27 | 19.25 | 14.55 | ||
| Maximum of Months | 0.389325E+10 | 5462.41 | 42.00 | 26.29 | 0.142332E+09 | 99.09 | 42.00 | 29.38 |
Report: ZoneCoolingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.971414E+09 | 5457.97 | 15-JAN-22:52 | 16.00 | 12.61 | 0.142347E+09 | 95.87 | 25-JAN-22:10 | 19.25 | 14.67 |
| February | 0.105332E+10 | 5450.34 | 12-FEB-17:12 | 20.67 | 14.90 | 0.126753E+09 | 96.92 | 11-FEB-21:10 | 20.67 | 14.90 |
| March | 0.150267E+10 | 5422.11 | 07-MAR-20:52 | 20.00 | 14.20 | 0.135921E+09 | 92.43 | 03-MAR-21:00 | 20.00 | 14.20 |
| April | 0.197385E+10 | 5298.14 | 06-APR-08:22 | 26.50 | 15.88 | 0.127253E+09 | 92.35 | 04-APR-20:00 | 26.50 | 15.88 |
| May | 0.293636E+10 | 4808.20 | 15-MAY-07:32 | 26.00 | 17.61 | 0.129276E+09 | 84.51 | 03-MAY-05:00 | 26.00 | 17.61 |
| June | 0.321980E+10 | 4163.97 | 22-JUN-09:02 | 34.63 | 22.51 | 0.124646E+09 | 70.27 | 27-JUN-04:19 | 28.53 | 26.68 |
| July | 0.370094E+10 | 1939.36 | 21-JUL-17:12 | 42.00 | 23.65 | 0.128775E+09 | 70.27 | 20-JUL-22:40 | 42.00 | 23.65 |
| August | 0.389415E+10 | 1964.03 | 05-AUG-17:17 | 40.67 | 26.29 | 0.128775E+09 | 70.27 | 26-AUG-05:00 | 30.00 | 28.44 |
| September | 0.337164E+10 | 4207.60 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124834E+09 | 86.48 | 30-SEP-05:40 | 25.60 | 21.36 |
| October | 0.306141E+10 | 5265.16 | 21-OCT-08:42 | 28.17 | 14.74 | 0.129765E+09 | 85.75 | 31-OCT-05:49 | 23.58 | 22.53 |
| November | 0.230606E+10 | 5160.34 | 21-NOV-22:52 | 21.00 | 16.02 | 0.128641E+09 | 95.17 | 30-NOV-22:10 | 22.20 | 17.52 |
| December | 0.142125E+10 | 5444.75 | 16-DEC-18:42 | 20.92 | 15.33 | 0.141134E+09 | 99.17 | 16-DEC-21:10 | 20.02 | 14.70 |
| Annual Sum or Average | 0.294129E+11 | 0.156812E+10 | ||||||||
| Minimum of Months | 0.971414E+09 | 1939.36 | 16.00 | 12.61 | 0.124646E+09 | 70.27 | 19.25 | 14.20 | ||
| Maximum of Months | 0.389415E+10 | 5457.97 | 42.00 | 26.29 | 0.142347E+09 | 99.17 | 42.00 | 28.44 |
Report: ZoneCoolingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.151937E+10 | 5690.34 | 15-JAN-22:32 | 16.30 | 12.69 | 0.142786E+09 | 104.29 | 07-JAN-16:40 | 16.30 | 12.69 |
| February | 0.151496E+10 | 5670.60 | 11-FEB-15:52 | 21.30 | 15.15 | 0.125525E+09 | 102.71 | 26-FEB-16:40 | 22.13 | 16.27 |
| March | 0.188854E+10 | 5655.76 | 07-MAR-20:22 | 21.00 | 14.39 | 0.131364E+09 | 97.62 | 09-MAR-18:19 | 22.97 | 16.16 |
| April | 0.219781E+10 | 5512.19 | 06-APR-08:22 | 26.50 | 15.88 | 0.126928E+09 | 94.12 | 04-APR-20:30 | 26.50 | 15.88 |
| May | 0.293957E+10 | 5010.91 | 15-MAY-07:42 | 26.50 | 17.86 | 0.126142E+09 | 92.08 | 15-MAY-06:00 | 26.50 | 17.86 |
| June | 0.311925E+10 | 4341.78 | 22-JUN-09:02 | 34.63 | 22.51 | 0.120421E+09 | 70.27 | 03-JUN-09:00 | 34.63 | 22.51 |
| July | 0.367590E+10 | 1917.23 | 21-JUL-17:12 | 42.00 | 23.65 | 0.129276E+09 | 70.27 | 20-JUL-22:30 | 42.00 | 23.65 |
| August | 0.402131E+10 | 1996.31 | 05-AUG-17:01 | 40.83 | 26.31 | 0.123963E+09 | 70.27 | 26-AUG-05:00 | 30.00 | 28.44 |
| September | 0.376164E+10 | 4460.70 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124197E+09 | 95.50 | 25-SEP-06:00 | 25.60 | 21.36 |
| October | 0.371593E+10 | 5445.71 | 20-OCT-07:32 | 24.30 | 16.01 | 0.128794E+09 | 99.23 | 21-OCT-08:30 | 26.50 | 14.81 |
| November | 0.305081E+10 | 5391.14 | 21-NOV-22:52 | 21.00 | 16.02 | 0.128631E+09 | 99.47 | 23-NOV-09:00 | 24.00 | 19.35 |
| December | 0.203830E+10 | 5676.41 | 19-DEC-19:02 | 20.83 | 15.30 | 0.142500E+09 | 103.90 | 16-DEC-16:49 | 20.83 | 15.30 |
| Annual Sum or Average | 0.334434E+11 | 0.155053E+10 | ||||||||
| Minimum of Months | 0.151496E+10 | 1917.23 | 16.30 | 12.69 | 0.120421E+09 | 70.27 | 16.30 | 12.69 | ||
| Maximum of Months | 0.402131E+10 | 5690.34 | 42.00 | 26.31 | 0.142786E+09 | 104.29 | 42.00 | 28.44 |
Report: ZoneCoolingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.159225E+10 | 5731.95 | 15-JAN-22:32 | 16.30 | 12.69 | 0.143222E+09 | 104.98 | 07-JAN-16:40 | 16.30 | 12.69 |
| February | 0.159845E+10 | 5714.55 | 11-FEB-15:52 | 21.30 | 15.15 | 0.126009E+09 | 103.85 | 26-FEB-16:40 | 22.13 | 16.27 |
| March | 0.201321E+10 | 5695.79 | 07-MAR-20:22 | 21.00 | 14.39 | 0.131785E+09 | 98.40 | 18-MAR-18:10 | 22.83 | 16.10 |
| April | 0.239908E+10 | 5553.79 | 06-APR-08:22 | 26.50 | 15.88 | 0.127271E+09 | 95.61 | 04-APR-20:30 | 26.50 | 15.88 |
| May | 0.323064E+10 | 5095.14 | 15-MAY-07:42 | 26.50 | 17.86 | 0.126203E+09 | 94.44 | 15-MAY-06:00 | 26.50 | 17.86 |
| June | 0.340962E+10 | 4427.11 | 22-JUN-09:02 | 34.63 | 22.51 | 0.120421E+09 | 70.27 | 03-JUN-09:00 | 34.63 | 22.51 |
| July | 0.400151E+10 | 2024.54 | 30-JUL-16:02 | 37.50 | 30.68 | 0.129276E+09 | 70.27 | 20-JUL-22:40 | 37.50 | 30.68 |
| August | 0.433859E+10 | 2158.28 | 06-AUG-17:02 | 39.83 | 26.14 | 0.123963E+09 | 70.27 | 26-AUG-04:40 | 30.93 | 29.39 |
| September | 0.407303E+10 | 4548.87 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124223E+09 | 98.15 | 25-SEP-06:00 | 25.60 | 21.36 |
| October | 0.402965E+10 | 5491.03 | 20-OCT-07:32 | 24.30 | 16.01 | 0.128923E+09 | 101.04 | 21-OCT-08:30 | 26.50 | 14.81 |
| November | 0.329868E+10 | 5438.45 | 21-NOV-22:52 | 21.00 | 16.02 | 0.129104E+09 | 101.58 | 26-NOV-10:09 | 24.42 | 18.42 |
| December | 0.216268E+10 | 5720.14 | 19-DEC-19:02 | 20.83 | 15.30 | 0.143063E+09 | 104.70 | 16-DEC-16:49 | 20.83 | 15.30 |
| Annual Sum or Average | 0.361474E+11 | 0.155346E+10 | ||||||||
| Minimum of Months | 0.159225E+10 | 2024.54 | 16.30 | 12.69 | 0.120421E+09 | 70.27 | 16.30 | 12.69 | ||
| Maximum of Months | 0.433859E+10 | 5731.95 | 39.83 | 30.68 | 0.143222E+09 | 104.98 | 37.50 | 30.68 |
Report: ZoneCoolingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.131038E+10 | 6876.65 | 26-JAN-16:42 | 21.08 | 15.08 | 0.141218E+09 | 106.25 | 07-JAN-16:40 | 21.08 | 15.08 |
| February | 0.154598E+10 | 6899.22 | 11-FEB-17:02 | 20.83 | 14.97 | 0.124948E+09 | 107.24 | 26-FEB-16:40 | 22.13 | 16.27 |
| March | 0.226070E+10 | 6857.43 | 07-MAR-15:42 | 23.67 | 15.43 | 0.131298E+09 | 101.74 | 16-MAR-18:10 | 22.83 | 16.65 |
| April | 0.283040E+10 | 6661.81 | 06-APR-08:22 | 26.50 | 15.88 | 0.126540E+09 | 94.97 | 04-APR-20:19 | 26.50 | 15.88 |
| May | 0.380727E+10 | 6095.75 | 15-MAY-07:42 | 26.50 | 17.86 | 0.126091E+09 | 89.85 | 16-MAY-06:00 | 26.00 | 20.80 |
| June | 0.397770E+10 | 5269.45 | 22-JUN-09:02 | 34.63 | 22.51 | 0.120422E+09 | 70.27 | 03-JUN-09:00 | 34.63 | 22.51 |
| July | 0.452040E+10 | 2740.28 | 21-JUL-16:30 | 42.05 | 24.24 | 0.129276E+09 | 70.27 | 20-JUL-21:00 | 42.05 | 24.24 |
| August | 0.469121E+10 | 2758.63 | 10-AUG-16:01 | 41.33 | 30.18 | 0.123963E+09 | 70.27 | 08-AUG-06:10 | 41.33 | 30.18 |
| September | 0.415670E+10 | 5176.66 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124148E+09 | 91.28 | 30-SEP-06:00 | 25.60 | 21.36 |
| October | 0.382321E+10 | 6644.50 | 21-OCT-08:42 | 28.17 | 14.74 | 0.128418E+09 | 92.43 | 21-OCT-08:50 | 28.17 | 14.74 |
| November | 0.291769E+10 | 6486.40 | 22-NOV-21:22 | 22.75 | 17.02 | 0.127078E+09 | 93.41 | 30-NOV-22:10 | 22.20 | 17.52 |
| December | 0.178408E+10 | 6880.07 | 27-DEC-17:12 | 21.67 | 15.45 | 0.139826E+09 | 102.04 | 24-DEC-16:19 | 21.67 | 15.45 |
| Annual Sum or Average | 0.376257E+11 | 0.154323E+10 | ||||||||
| Minimum of Months | 0.131038E+10 | 2740.28 | 20.83 | 14.74 | 0.120422E+09 | 70.27 | 21.08 | 14.74 | ||
| Maximum of Months | 0.469121E+10 | 6899.22 | 42.05 | 30.18 | 0.141218E+09 | 107.24 | 42.05 | 30.18 |
Report: ZoneCoolingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.755168E+09 | 6655.20 | 05-JAN-18:12 | 20.83 | 16.50 | 0.139799E+09 | 92.71 | 29-JAN-21:10 | 23.30 | 19.38 |
| February | 0.106431E+10 | 6657.48 | 11-FEB-18:12 | 19.80 | 14.36 | 0.126151E+09 | 96.04 | 11-FEB-21:10 | 19.78 | 14.55 |
| March | 0.186803E+10 | 6632.35 | 04-MAR-21:52 | 21.00 | 15.03 | 0.136082E+09 | 94.28 | 16-MAR-20:10 | 21.92 | 16.44 |
| April | 0.260114E+10 | 6467.53 | 06-APR-08:22 | 26.50 | 15.88 | 0.126961E+09 | 93.51 | 04-APR-20:19 | 26.50 | 15.88 |
| May | 0.380533E+10 | 5885.89 | 15-MAY-07:32 | 26.00 | 17.61 | 0.129222E+09 | 82.71 | 03-MAY-05:00 | 26.00 | 17.61 |
| June | 0.407967E+10 | 5106.52 | 22-JUN-09:02 | 34.63 | 22.51 | 0.124646E+09 | 70.27 | 27-JUN-03:20 | 29.20 | 27.61 |
| July | 0.454345E+10 | 2762.58 | 21-JUL-16:30 | 42.05 | 24.24 | 0.128775E+09 | 70.27 | 20-JUL-21:00 | 42.05 | 24.24 |
| August | 0.455968E+10 | 2676.52 | 10-AUG-16:01 | 41.33 | 30.18 | 0.128775E+09 | 70.27 | 08-AUG-05:00 | 41.33 | 30.18 |
| September | 0.375902E+10 | 4978.81 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124791E+09 | 83.26 | 30-SEP-05:40 | 25.60 | 21.36 |
| October | 0.315764E+10 | 6409.38 | 21-OCT-08:42 | 28.17 | 14.74 | 0.129483E+09 | 81.52 | 31-OCT-05:49 | 23.58 | 22.53 |
| November | 0.216800E+10 | 6191.71 | 18-NOV-10:02 | 27.42 | 16.54 | 0.127267E+09 | 89.61 | 30-NOV-22:10 | 22.20 | 17.52 |
| December | 0.117209E+10 | 6643.16 | 18-DEC-19:22 | 21.10 | 15.20 | 0.137975E+09 | 92.20 | 14-DEC-21:49 | 21.10 | 15.20 |
| Annual Sum or Average | 0.335335E+11 | 0.155993E+10 | ||||||||
| Minimum of Months | 0.755168E+09 | 2676.52 | 19.80 | 14.36 | 0.124646E+09 | 70.27 | 19.78 | 14.55 | ||
| Maximum of Months | 0.455968E+10 | 6657.48 | 42.05 | 30.18 | 0.139799E+09 | 96.04 | 42.05 | 30.18 |
Report: ZoneCoolingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.131904E+10 | 6597.95 | 26-JAN-17:52 | 20.00 | 15.15 | 0.141240E+09 | 104.67 | 07-JAN-16:40 | 20.00 | 15.15 |
| February | 0.154109E+10 | 6616.77 | 11-FEB-17:02 | 20.83 | 14.97 | 0.124910E+09 | 104.61 | 26-FEB-16:40 | 22.13 | 16.27 |
| March | 0.223699E+10 | 6575.55 | 07-MAR-20:22 | 21.00 | 14.39 | 0.131215E+09 | 98.91 | 16-MAR-18:10 | 22.83 | 16.65 |
| April | 0.286484E+10 | 6419.05 | 06-APR-08:22 | 26.50 | 15.88 | 0.126664E+09 | 94.19 | 30-APR-08:39 | 24.33 | 21.97 |
| May | 0.386036E+10 | 5863.51 | 15-MAY-07:42 | 26.50 | 17.86 | 0.126099E+09 | 90.68 | 16-MAY-06:00 | 26.00 | 20.80 |
| June | 0.399601E+10 | 5127.06 | 22-JUN-09:02 | 34.63 | 22.51 | 0.120422E+09 | 70.27 | 03-JUN-09:00 | 34.63 | 22.51 |
| July | 0.454361E+10 | 2532.23 | 21-JUL-16:01 | 42.08 | 24.71 | 0.129276E+09 | 70.27 | 20-JUL-22:10 | 42.08 | 24.71 |
| August | 0.471834E+10 | 2574.31 | 16-AUG-12:00 | 46.00 | 25.38 | 0.123963E+09 | 70.27 | 08-AUG-05:30 | 46.00 | 25.38 |
| September | 0.417775E+10 | 4979.03 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124148E+09 | 91.68 | 30-SEP-06:00 | 25.60 | 21.36 |
| October | 0.385139E+10 | 6391.36 | 21-OCT-08:42 | 28.17 | 14.74 | 0.128448E+09 | 95.17 | 21-OCT-08:30 | 28.17 | 14.74 |
| November | 0.292256E+10 | 6224.39 | 22-NOV-21:22 | 22.75 | 17.02 | 0.127251E+09 | 95.01 | 23-NOV-09:00 | 24.00 | 19.35 |
| December | 0.177220E+10 | 6598.19 | 27-DEC-17:12 | 21.67 | 15.45 | 0.139892E+09 | 99.87 | 24-DEC-16:19 | 21.67 | 15.45 |
| Annual Sum or Average | 0.378042E+11 | 0.154353E+10 | ||||||||
| Minimum of Months | 0.131904E+10 | 2532.23 | 20.00 | 14.39 | 0.120422E+09 | 70.27 | 20.00 | 14.74 | ||
| Maximum of Months | 0.471834E+10 | 6616.77 | 46.00 | 25.38 | 0.141240E+09 | 104.67 | 46.00 | 25.38 |
Report: ZoneCoolingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.761294E+09 | 6369.26 | 05-JAN-18:12 | 20.83 | 16.50 | 0.139570E+09 | 92.43 | 29-JAN-21:40 | 23.00 | 19.38 |
| February | 0.105895E+10 | 6381.18 | 12-FEB-17:12 | 20.67 | 14.90 | 0.126007E+09 | 94.11 | 11-FEB-21:10 | 20.67 | 14.90 |
| March | 0.184463E+10 | 6367.61 | 07-MAR-20:52 | 20.00 | 14.20 | 0.135963E+09 | 93.06 | 16-MAR-20:10 | 21.92 | 16.44 |
| April | 0.263468E+10 | 6220.88 | 06-APR-08:22 | 26.50 | 15.88 | 0.127059E+09 | 92.46 | 04-APR-20:49 | 26.50 | 15.88 |
| May | 0.385870E+10 | 5669.08 | 15-MAY-07:32 | 26.00 | 17.61 | 0.129242E+09 | 82.74 | 03-MAY-05:00 | 26.00 | 17.61 |
| June | 0.409822E+10 | 4969.72 | 22-JUN-09:02 | 34.63 | 22.51 | 0.124649E+09 | 70.27 | 27-JUN-04:19 | 28.53 | 26.68 |
| July | 0.456672E+10 | 2546.75 | 21-JUL-16:30 | 42.05 | 24.24 | 0.128775E+09 | 70.27 | 20-JUL-21:00 | 42.05 | 24.24 |
| August | 0.458685E+10 | 2470.29 | 05-AUG-11:40 | 43.67 | 25.00 | 0.128775E+09 | 70.27 | 08-AUG-05:49 | 30.00 | 29.16 |
| September | 0.377992E+10 | 4779.95 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124792E+09 | 83.17 | 30-SEP-05:40 | 25.60 | 21.36 |
| October | 0.318504E+10 | 6168.90 | 21-OCT-08:42 | 28.17 | 14.74 | 0.129506E+09 | 81.43 | 31-OCT-05:49 | 23.58 | 22.53 |
| November | 0.217022E+10 | 6017.70 | 18-NOV-10:02 | 27.42 | 16.54 | 0.127455E+09 | 89.07 | 22-NOV-22:10 | 22.25 | 16.62 |
| December | 0.115714E+10 | 6354.47 | 19-DEC-16:52 | 22.00 | 15.88 | 0.137920E+09 | 92.43 | 14-DEC-21:49 | 22.00 | 15.88 |
| Annual Sum or Average | 0.337024E+11 | 0.155971E+10 | ||||||||
| Minimum of Months | 0.761294E+09 | 2470.29 | 20.00 | 14.20 | 0.124649E+09 | 70.27 | 20.67 | 14.90 | ||
| Maximum of Months | 0.458685E+10 | 6381.18 | 43.67 | 25.00 | 0.139570E+09 | 94.11 | 42.05 | 29.16 |
Report: ZoneCoolingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.879241E+09 | 5607.04 | 05-JAN-18:12 | 20.83 | 16.50 | 0.140128E+09 | 92.43 | 31-JAN-21:30 | 19.45 | 15.76 |
| February | 0.105744E+10 | 5622.54 | 12-FEB-17:12 | 20.67 | 14.90 | 0.125776E+09 | 94.62 | 11-FEB-21:10 | 20.67 | 14.90 |
| March | 0.164572E+10 | 5598.54 | 07-MAR-20:52 | 20.00 | 14.20 | 0.135938E+09 | 92.96 | 09-MAR-21:40 | 22.00 | 15.42 |
| April | 0.213317E+10 | 5447.55 | 06-APR-08:22 | 26.50 | 15.88 | 0.127048E+09 | 91.45 | 04-APR-20:00 | 26.50 | 15.88 |
| May | 0.295260E+10 | 4910.88 | 15-MAY-07:32 | 26.00 | 17.61 | 0.129214E+09 | 82.70 | 03-MAY-05:00 | 26.00 | 17.61 |
| June | 0.312140E+10 | 4222.59 | 22-JUN-09:02 | 34.63 | 22.51 | 0.124644E+09 | 70.27 | 27-JUN-04:30 | 28.40 | 26.45 |
| July | 0.344123E+10 | 1865.32 | 21-JUL-17:01 | 42.00 | 23.59 | 0.128775E+09 | 70.27 | 20-JUL-22:19 | 42.00 | 23.59 |
| August | 0.343196E+10 | 1792.90 | 05-AUG-17:17 | 40.67 | 26.29 | 0.128775E+09 | 70.27 | 26-AUG-05:40 | 30.33 | 28.76 |
| September | 0.289487E+10 | 4132.85 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124784E+09 | 82.56 | 30-SEP-05:49 | 25.60 | 21.36 |
| October | 0.252991E+10 | 5393.33 | 21-OCT-08:42 | 28.17 | 14.74 | 0.129484E+09 | 81.26 | 31-OCT-05:49 | 23.58 | 22.53 |
| November | 0.186305E+10 | 5207.21 | 18-NOV-10:02 | 27.42 | 16.54 | 0.127422E+09 | 89.15 | 22-NOV-22:10 | 22.25 | 16.62 |
| December | 0.118229E+10 | 5602.21 | 16-DEC-18:42 | 20.92 | 15.33 | 0.138425E+09 | 93.17 | 14-DEC-21:40 | 20.92 | 15.33 |
| Annual Sum or Average | 0.271329E+11 | 0.156041E+10 | ||||||||
| Minimum of Months | 0.879241E+09 | 1792.90 | 20.00 | 14.20 | 0.124644E+09 | 70.27 | 19.45 | 14.90 | ||
| Maximum of Months | 0.344123E+10 | 5622.54 | 42.00 | 26.29 | 0.140128E+09 | 94.62 | 42.00 | 28.76 |
Report: ZoneCoolingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.880790E+09 | 5601.28 | 05-JAN-18:12 | 20.83 | 16.50 | 0.140143E+09 | 92.43 | 31-JAN-21:30 | 19.45 | 15.76 |
| February | 0.105918E+10 | 5616.48 | 12-FEB-17:12 | 20.67 | 14.90 | 0.125808E+09 | 94.58 | 11-FEB-21:10 | 20.67 | 14.90 |
| March | 0.164599E+10 | 5593.30 | 07-MAR-20:52 | 20.00 | 14.20 | 0.135923E+09 | 92.93 | 09-MAR-21:40 | 22.00 | 15.42 |
| April | 0.213550E+10 | 5442.77 | 06-APR-08:22 | 26.50 | 15.88 | 0.127049E+09 | 91.42 | 04-APR-20:00 | 26.50 | 15.88 |
| May | 0.295468E+10 | 4906.25 | 15-MAY-07:32 | 26.00 | 17.61 | 0.129214E+09 | 82.70 | 03-MAY-05:00 | 26.00 | 17.61 |
| June | 0.312213E+10 | 4219.08 | 22-JUN-09:02 | 34.63 | 22.51 | 0.124644E+09 | 70.27 | 27-JUN-04:19 | 28.53 | 26.68 |
| July | 0.344202E+10 | 1862.82 | 21-JUL-17:01 | 42.00 | 23.59 | 0.128775E+09 | 70.27 | 20-JUL-22:19 | 42.00 | 23.59 |
| August | 0.343289E+10 | 1790.59 | 05-AUG-17:17 | 40.67 | 26.29 | 0.128775E+09 | 70.27 | 26-AUG-05:19 | 30.67 | 29.08 |
| September | 0.289568E+10 | 4128.65 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124784E+09 | 82.56 | 30-SEP-05:49 | 25.60 | 21.36 |
| October | 0.253127E+10 | 5388.69 | 21-OCT-08:42 | 28.17 | 14.74 | 0.129484E+09 | 81.26 | 31-OCT-05:49 | 23.58 | 22.53 |
| November | 0.186486E+10 | 5204.32 | 18-NOV-10:02 | 27.42 | 16.54 | 0.127425E+09 | 89.15 | 22-NOV-22:10 | 22.25 | 16.62 |
| December | 0.118325E+10 | 5596.39 | 16-DEC-18:42 | 20.92 | 15.33 | 0.138431E+09 | 93.20 | 14-DEC-21:40 | 20.92 | 15.33 |
| Annual Sum or Average | 0.271483E+11 | 0.156045E+10 | ||||||||
| Minimum of Months | 0.880790E+09 | 1790.59 | 20.00 | 14.20 | 0.124644E+09 | 70.27 | 19.45 | 14.90 | ||
| Maximum of Months | 0.344202E+10 | 5616.48 | 42.00 | 26.29 | 0.140143E+09 | 94.58 | 42.00 | 29.08 |
Report: ZoneCoolingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.145743E+10 | 5862.41 | 26-JAN-17:52 | 20.00 | 15.15 | 0.141963E+09 | 103.84 | 07-JAN-16:40 | 20.00 | 15.15 |
| February | 0.155374E+10 | 5873.19 | 11-FEB-17:02 | 20.83 | 14.97 | 0.125286E+09 | 103.22 | 26-FEB-16:40 | 22.13 | 16.27 |
| March | 0.204558E+10 | 5843.64 | 07-MAR-20:22 | 21.00 | 14.39 | 0.131395E+09 | 97.62 | 07-MAR-18:00 | 21.00 | 14.39 |
| April | 0.236425E+10 | 5675.92 | 06-APR-08:22 | 26.50 | 15.88 | 0.126663E+09 | 92.75 | 04-APR-20:30 | 26.50 | 15.88 |
| May | 0.295476E+10 | 5152.56 | 15-MAY-07:42 | 26.50 | 17.86 | 0.126085E+09 | 88.85 | 16-MAY-06:00 | 26.00 | 20.80 |
| June | 0.301883E+10 | 4402.66 | 22-JUN-09:02 | 34.63 | 22.51 | 0.120421E+09 | 70.27 | 15-JUN-18:49 | 34.63 | 22.51 |
| July | 0.341777E+10 | 1838.01 | 21-JUL-17:12 | 42.00 | 23.65 | 0.129276E+09 | 70.27 | 20-JUL-22:30 | 42.00 | 23.65 |
| August | 0.356377E+10 | 1857.76 | 05-AUG-16:01 | 40.08 | 27.50 | 0.123963E+09 | 70.27 | 08-AUG-05:40 | 30.00 | 29.16 |
| September | 0.329479E+10 | 4358.58 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124142E+09 | 90.43 | 30-SEP-06:00 | 25.60 | 21.36 |
| October | 0.320113E+10 | 5654.98 | 21-OCT-08:42 | 28.17 | 14.74 | 0.128432E+09 | 92.43 | 21-OCT-08:50 | 28.17 | 14.74 |
| November | 0.262314E+10 | 5527.58 | 22-NOV-21:22 | 22.75 | 17.02 | 0.127289E+09 | 93.09 | 23-NOV-09:00 | 24.00 | 19.35 |
| December | 0.180956E+10 | 5858.03 | 27-DEC-17:12 | 21.67 | 15.45 | 0.140480E+09 | 99.91 | 17-DEC-17:19 | 21.67 | 15.45 |
| Annual Sum or Average | 0.313048E+11 | 0.154540E+10 | ||||||||
| Minimum of Months | 0.145743E+10 | 1838.01 | 20.00 | 14.39 | 0.120421E+09 | 70.27 | 20.00 | 14.39 | ||
| Maximum of Months | 0.356377E+10 | 5873.19 | 42.00 | 27.50 | 0.141963E+09 | 103.84 | 42.00 | 29.16 |
Report: ZoneCoolingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.145906E+10 | 5857.77 | 26-JAN-17:52 | 20.00 | 15.15 | 0.141971E+09 | 103.90 | 07-JAN-16:40 | 20.00 | 15.15 |
| February | 0.155487E+10 | 5869.02 | 11-FEB-17:02 | 20.83 | 14.97 | 0.125289E+09 | 103.23 | 26-FEB-16:40 | 22.13 | 16.27 |
| March | 0.204592E+10 | 5838.84 | 07-MAR-20:22 | 21.00 | 14.39 | 0.131386E+09 | 97.59 | 07-MAR-18:00 | 21.00 | 14.39 |
| April | 0.236652E+10 | 5671.98 | 06-APR-08:22 | 26.50 | 15.88 | 0.126665E+09 | 92.72 | 04-APR-20:30 | 26.50 | 15.88 |
| May | 0.295686E+10 | 5155.42 | 15-MAY-07:42 | 26.50 | 17.86 | 0.126085E+09 | 88.86 | 16-MAY-06:00 | 26.00 | 20.80 |
| June | 0.301957E+10 | 4405.68 | 22-JUN-09:02 | 34.63 | 22.51 | 0.120421E+09 | 70.27 | 15-JUN-19:10 | 34.63 | 22.51 |
| July | 0.341856E+10 | 1835.47 | 21-JUL-17:16 | 42.00 | 23.65 | 0.129276E+09 | 70.27 | 20-JUL-22:30 | 42.00 | 23.65 |
| August | 0.356470E+10 | 1856.97 | 05-AUG-16:01 | 40.08 | 27.50 | 0.123963E+09 | 70.27 | 08-AUG-05:49 | 30.00 | 29.16 |
| September | 0.329559E+10 | 4358.79 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124142E+09 | 90.43 | 30-SEP-06:00 | 25.60 | 21.36 |
| October | 0.320241E+10 | 5650.57 | 21-OCT-08:42 | 28.17 | 14.74 | 0.128432E+09 | 92.43 | 21-OCT-08:50 | 28.17 | 14.74 |
| November | 0.262460E+10 | 5522.20 | 22-NOV-21:22 | 22.75 | 17.02 | 0.127290E+09 | 93.17 | 23-NOV-09:00 | 24.00 | 19.35 |
| December | 0.181027E+10 | 5855.66 | 19-DEC-19:02 | 20.83 | 15.30 | 0.140485E+09 | 99.90 | 17-DEC-17:19 | 20.83 | 15.30 |
| Annual Sum or Average | 0.313189E+11 | 0.154541E+10 | ||||||||
| Minimum of Months | 0.145906E+10 | 1835.47 | 20.00 | 14.39 | 0.120421E+09 | 70.27 | 20.00 | 14.39 | ||
| Maximum of Months | 0.356470E+10 | 5869.02 | 42.00 | 27.50 | 0.141971E+09 | 103.90 | 42.00 | 29.16 |
Report: ZoneCoolingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.955820E+09 | 7447.82 | 07-JAN-16:32 | 23.13 | 17.58 | 0.137123E+09 | 117.02 | 07-JAN-16:40 | 23.13 | 17.58 |
| February | 0.131558E+10 | 7615.53 | 27-FEB-16:02 | 23.73 | 16.39 | 0.122522E+09 | 117.04 | 26-FEB-16:40 | 23.73 | 16.39 |
| March | 0.216085E+10 | 7466.76 | 07-MAR-15:22 | 23.80 | 15.36 | 0.129943E+09 | 110.88 | 16-MAR-18:10 | 22.83 | 16.65 |
| April | 0.296883E+10 | 7173.60 | 06-APR-08:22 | 26.50 | 15.88 | 0.125573E+09 | 99.98 | 04-APR-20:30 | 26.50 | 15.88 |
| May | 0.424808E+10 | 6525.83 | 15-MAY-07:42 | 26.50 | 17.86 | 0.126008E+09 | 88.73 | 16-MAY-06:00 | 26.00 | 20.80 |
| June | 0.449618E+10 | 5638.86 | 22-JUN-09:02 | 34.63 | 22.51 | 0.120422E+09 | 70.27 | 03-JUN-09:00 | 34.63 | 22.51 |
| July | 0.520851E+10 | 3545.63 | 21-JUL-16:17 | 42.07 | 24.48 | 0.129276E+09 | 70.27 | 20-JUL-21:40 | 42.07 | 24.48 |
| August | 0.537951E+10 | 3568.93 | 10-AUG-16:01 | 41.33 | 30.18 | 0.123963E+09 | 70.27 | 08-AUG-06:10 | 41.33 | 30.18 |
| September | 0.462227E+10 | 5388.36 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124124E+09 | 90.44 | 30-SEP-06:00 | 25.60 | 21.36 |
| October | 0.408042E+10 | 7160.54 | 21-OCT-08:42 | 28.17 | 14.74 | 0.128231E+09 | 92.43 | 21-OCT-08:50 | 28.17 | 14.74 |
| November | 0.290951E+10 | 6963.28 | 22-NOV-21:22 | 22.75 | 17.02 | 0.126015E+09 | 95.53 | 30-NOV-22:10 | 22.20 | 17.52 |
| December | 0.152312E+10 | 7456.31 | 27-DEC-16:02 | 21.83 | 15.42 | 0.137385E+09 | 111.06 | 24-DEC-16:19 | 21.83 | 15.42 |
| Annual Sum or Average | 0.398687E+11 | 0.153059E+10 | ||||||||
| Minimum of Months | 0.955820E+09 | 3545.63 | 21.83 | 14.74 | 0.120422E+09 | 70.27 | 21.83 | 14.74 | ||
| Maximum of Months | 0.537951E+10 | 7615.53 | 42.07 | 30.18 | 0.137385E+09 | 117.04 | 42.07 | 30.18 |
Report: ZoneCoolingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.464457E+09 | 7219.13 | 05-JAN-18:12 | 20.83 | 16.50 | 0.134212E+09 | 95.96 | 29-JAN-21:19 | 23.20 | 19.38 |
| February | 0.844993E+09 | 7361.55 | 24-FEB-17:02 | 21.00 | 15.92 | 0.123880E+09 | 96.94 | 11-FEB-21:10 | 21.00 | 15.92 |
| March | 0.175852E+10 | 7222.51 | 07-MAR-18:12 | 22.73 | 15.10 | 0.135230E+09 | 98.70 | 16-MAR-20:10 | 21.92 | 16.44 |
| April | 0.272683E+10 | 7016.55 | 06-APR-08:22 | 26.50 | 15.88 | 0.126147E+09 | 98.45 | 04-APR-20:40 | 26.50 | 15.88 |
| May | 0.424539E+10 | 6316.02 | 15-MAY-07:32 | 26.00 | 17.61 | 0.129143E+09 | 79.83 | 15-MAY-05:00 | 26.00 | 17.61 |
| June | 0.460164E+10 | 5520.84 | 22-JUN-09:02 | 34.63 | 22.51 | 0.124648E+09 | 70.27 | 09-JUN-05:00 | 34.63 | 22.51 |
| July | 0.522943E+10 | 3564.46 | 21-JUL-16:30 | 42.05 | 24.24 | 0.128775E+09 | 70.27 | 20-JUL-21:40 | 42.05 | 24.24 |
| August | 0.523583E+10 | 3460.19 | 10-AUG-16:01 | 41.33 | 30.18 | 0.128775E+09 | 70.27 | 08-AUG-05:00 | 41.33 | 30.18 |
| September | 0.420212E+10 | 5246.11 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124773E+09 | 81.63 | 30-SEP-05:00 | 25.60 | 21.36 |
| October | 0.338380E+10 | 6961.76 | 21-OCT-08:42 | 28.17 | 14.74 | 0.129350E+09 | 79.53 | 31-OCT-05:00 | 23.50 | 22.52 |
| November | 0.213598E+10 | 6694.53 | 18-NOV-10:02 | 27.42 | 16.54 | 0.126349E+09 | 91.62 | 29-NOV-22:49 | 23.10 | 20.94 |
| December | 0.919943E+09 | 7217.93 | 18-DEC-19:22 | 21.10 | 15.20 | 0.135096E+09 | 92.92 | 14-DEC-21:40 | 21.10 | 15.20 |
| Annual Sum or Average | 0.357489E+11 | 0.154638E+10 | ||||||||
| Minimum of Months | 0.464457E+09 | 3460.19 | 20.83 | 14.74 | 0.123880E+09 | 70.27 | 21.00 | 15.20 | ||
| Maximum of Months | 0.523583E+10 | 7361.55 | 42.05 | 30.18 | 0.135230E+09 | 98.70 | 42.05 | 30.18 |
Report: ZoneCoolingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.958650E+09 | 7044.03 | 26-JAN-16:42 | 21.08 | 15.08 | 0.137115E+09 | 113.99 | 07-JAN-16:40 | 21.08 | 15.08 |
| February | 0.130682E+10 | 7180.83 | 27-FEB-16:02 | 23.73 | 16.39 | 0.122356E+09 | 114.89 | 26-FEB-16:40 | 23.73 | 16.39 |
| March | 0.213480E+10 | 7061.18 | 07-MAR-15:22 | 23.80 | 15.36 | 0.129798E+09 | 105.27 | 16-MAR-18:10 | 22.83 | 16.65 |
| April | 0.300516E+10 | 6835.87 | 06-APR-08:22 | 26.50 | 15.88 | 0.125749E+09 | 97.76 | 04-APR-20:30 | 26.50 | 15.88 |
| May | 0.430708E+10 | 6177.32 | 15-MAY-07:42 | 26.50 | 17.86 | 0.126021E+09 | 90.19 | 16-MAY-06:00 | 26.00 | 20.80 |
| June | 0.452020E+10 | 5470.11 | 22-JUN-09:02 | 34.63 | 22.51 | 0.120422E+09 | 70.27 | 03-JUN-09:00 | 34.63 | 22.51 |
| July | 0.523647E+10 | 3329.82 | 30-JUL-14:00 | 44.00 | 24.47 | 0.129276E+09 | 70.27 | 20-JUL-21:49 | 44.00 | 24.47 |
| August | 0.541160E+10 | 3389.72 | 16-AUG-12:00 | 46.00 | 25.38 | 0.123963E+09 | 70.27 | 08-AUG-06:10 | 46.00 | 25.38 |
| September | 0.464827E+10 | 5121.08 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124125E+09 | 91.09 | 30-SEP-06:00 | 25.60 | 21.36 |
| October | 0.411215E+10 | 6799.38 | 21-OCT-08:42 | 28.17 | 14.74 | 0.128275E+09 | 96.41 | 21-OCT-08:30 | 28.17 | 14.74 |
| November | 0.291303E+10 | 6589.46 | 22-NOV-21:22 | 22.75 | 17.02 | 0.126268E+09 | 97.15 | 23-NOV-09:00 | 24.00 | 19.35 |
| December | 0.150925E+10 | 7061.53 | 27-DEC-16:02 | 21.83 | 15.42 | 0.137423E+09 | 107.08 | 24-DEC-16:19 | 21.83 | 15.42 |
| Annual Sum or Average | 0.400635E+11 | 0.153079E+10 | ||||||||
| Minimum of Months | 0.958650E+09 | 3329.82 | 21.08 | 14.74 | 0.120422E+09 | 70.27 | 21.08 | 14.74 | ||
| Maximum of Months | 0.541160E+10 | 7180.83 | 46.00 | 25.38 | 0.137423E+09 | 114.89 | 46.00 | 25.38 |
Report: ZoneCoolingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.461754E+09 | 6805.24 | 05-JAN-18:12 | 20.83 | 16.50 | 0.133742E+09 | 94.74 | 29-JAN-21:19 | 23.20 | 19.38 |
| February | 0.833547E+09 | 6844.03 | 11-FEB-18:12 | 19.80 | 14.36 | 0.123442E+09 | 96.81 | 09-FEB-21:10 | 19.80 | 14.36 |
| March | 0.173042E+10 | 6826.19 | 07-MAR-18:12 | 22.73 | 15.10 | 0.134926E+09 | 96.02 | 02-MAR-21:00 | 22.73 | 15.10 |
| April | 0.276210E+10 | 6678.39 | 06-APR-08:22 | 26.50 | 15.88 | 0.126288E+09 | 95.62 | 04-APR-20:40 | 26.50 | 15.88 |
| May | 0.430489E+10 | 6007.18 | 15-MAY-07:32 | 26.00 | 17.61 | 0.129172E+09 | 79.85 | 15-MAY-05:00 | 26.00 | 17.61 |
| June | 0.462593E+10 | 5350.12 | 22-JUN-09:02 | 34.63 | 22.51 | 0.124653E+09 | 70.27 | 27-JUN-03:09 | 29.30 | 27.73 |
| July | 0.525756E+10 | 3260.70 | 21-JUL-16:17 | 42.07 | 24.48 | 0.128775E+09 | 70.27 | 20-JUL-21:40 | 42.07 | 24.48 |
| August | 0.526804E+10 | 3250.15 | 04-AUG-13:00 | 44.50 | 24.79 | 0.128775E+09 | 70.27 | 08-AUG-05:49 | 30.00 | 29.16 |
| September | 0.422788E+10 | 4977.87 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124775E+09 | 81.56 | 30-SEP-05:00 | 25.60 | 21.36 |
| October | 0.341387E+10 | 6617.42 | 21-OCT-08:42 | 28.17 | 14.74 | 0.129387E+09 | 79.41 | 31-OCT-05:00 | 23.50 | 22.52 |
| November | 0.213318E+10 | 6420.73 | 18-NOV-10:02 | 27.42 | 16.54 | 0.126631E+09 | 91.51 | 29-NOV-22:49 | 23.10 | 20.94 |
| December | 0.902601E+09 | 6815.05 | 16-DEC-18:42 | 20.92 | 15.33 | 0.135031E+09 | 93.77 | 14-DEC-21:40 | 20.92 | 15.33 |
| Annual Sum or Average | 0.359218E+11 | 0.154560E+10 | ||||||||
| Minimum of Months | 0.461754E+09 | 3250.15 | 19.80 | 14.36 | 0.123442E+09 | 70.27 | 19.80 | 14.36 | ||
| Maximum of Months | 0.526804E+10 | 6844.03 | 44.50 | 24.79 | 0.135031E+09 | 96.81 | 42.07 | 29.16 |
Report: ZoneCoolingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.504142E+09 | 6166.37 | 05-JAN-18:12 | 20.83 | 16.50 | 0.137150E+09 | 95.05 | 29-JAN-21:19 | 23.20 | 19.38 |
| February | 0.805757E+09 | 6181.00 | 11-FEB-18:12 | 19.80 | 14.36 | 0.125124E+09 | 99.19 | 10-FEB-21:10 | 19.80 | 14.36 |
| March | 0.151675E+10 | 6156.55 | 04-MAR-21:52 | 21.00 | 15.03 | 0.135474E+09 | 98.41 | 02-MAR-21:00 | 21.00 | 15.03 |
| April | 0.223974E+10 | 6001.06 | 06-APR-08:22 | 26.50 | 15.88 | 0.126474E+09 | 95.56 | 04-APR-20:40 | 26.50 | 15.88 |
| May | 0.336676E+10 | 5398.76 | 15-MAY-07:32 | 26.00 | 17.61 | 0.129169E+09 | 80.50 | 03-MAY-05:00 | 26.00 | 17.61 |
| June | 0.361498E+10 | 4654.43 | 22-JUN-09:02 | 34.63 | 22.51 | 0.124646E+09 | 70.27 | 27-JUN-03:20 | 29.20 | 27.61 |
| July | 0.408740E+10 | 2494.15 | 21-JUL-16:30 | 42.05 | 24.24 | 0.128775E+09 | 70.27 | 20-JUL-22:10 | 42.05 | 24.24 |
| August | 0.406933E+10 | 2385.76 | 10-AUG-16:01 | 41.33 | 30.18 | 0.128775E+09 | 70.27 | 08-AUG-05:00 | 41.33 | 30.18 |
| September | 0.331283E+10 | 4476.47 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124777E+09 | 81.70 | 30-SEP-05:00 | 25.60 | 21.36 |
| October | 0.274041E+10 | 5947.98 | 21-OCT-08:42 | 28.17 | 14.74 | 0.129404E+09 | 79.87 | 20-OCT-05:00 | 28.17 | 14.74 |
| November | 0.181686E+10 | 5742.27 | 18-NOV-10:02 | 27.42 | 16.54 | 0.126796E+09 | 91.99 | 29-NOV-22:00 | 23.00 | 20.89 |
| December | 0.892615E+09 | 6148.56 | 19-DEC-16:52 | 22.00 | 15.88 | 0.136796E+09 | 95.26 | 14-DEC-21:40 | 22.00 | 15.88 |
| Annual Sum or Average | 0.289676E+11 | 0.155336E+10 | ||||||||
| Minimum of Months | 0.504142E+09 | 2385.76 | 19.80 | 14.36 | 0.124646E+09 | 70.27 | 19.80 | 14.36 | ||
| Maximum of Months | 0.408740E+10 | 6181.00 | 42.05 | 30.18 | 0.137150E+09 | 99.19 | 42.05 | 30.18 |
Report: ZoneCoolingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.505585E+09 | 6150.31 | 05-JAN-18:12 | 20.83 | 16.50 | 0.137147E+09 | 94.98 | 29-JAN-21:19 | 23.20 | 19.38 |
| February | 0.806869E+09 | 6167.23 | 11-FEB-18:12 | 19.80 | 14.36 | 0.125118E+09 | 99.03 | 10-FEB-21:10 | 19.80 | 14.36 |
| March | 0.151737E+10 | 6143.18 | 04-MAR-21:52 | 21.00 | 15.03 | 0.135452E+09 | 98.22 | 02-MAR-21:00 | 21.00 | 15.03 |
| April | 0.224285E+10 | 5988.64 | 06-APR-08:22 | 26.50 | 15.88 | 0.126476E+09 | 95.42 | 04-APR-20:40 | 26.50 | 15.88 |
| May | 0.336950E+10 | 5387.20 | 15-MAY-07:32 | 26.00 | 17.61 | 0.129170E+09 | 80.49 | 03-MAY-05:00 | 26.00 | 17.61 |
| June | 0.361614E+10 | 4646.33 | 22-JUN-09:02 | 34.63 | 22.51 | 0.124646E+09 | 70.27 | 27-JUN-03:30 | 29.10 | 27.49 |
| July | 0.408854E+10 | 2488.83 | 21-JUL-16:30 | 42.05 | 24.24 | 0.128775E+09 | 70.27 | 20-JUL-21:00 | 42.05 | 24.24 |
| August | 0.407062E+10 | 2379.41 | 10-AUG-16:01 | 41.33 | 30.18 | 0.128775E+09 | 70.27 | 08-AUG-05:00 | 41.33 | 30.18 |
| September | 0.331405E+10 | 4465.81 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124777E+09 | 81.69 | 30-SEP-05:00 | 25.60 | 21.36 |
| October | 0.274228E+10 | 5936.00 | 21-OCT-08:42 | 28.17 | 14.74 | 0.129404E+09 | 79.86 | 20-OCT-05:00 | 28.17 | 14.74 |
| November | 0.181921E+10 | 5736.75 | 18-NOV-10:02 | 27.42 | 16.54 | 0.126802E+09 | 91.98 | 29-NOV-22:00 | 23.00 | 20.89 |
| December | 0.893491E+09 | 6134.61 | 19-DEC-16:52 | 22.00 | 15.88 | 0.136786E+09 | 95.31 | 14-DEC-21:40 | 22.00 | 15.88 |
| Annual Sum or Average | 0.289865E+11 | 0.155333E+10 | ||||||||
| Minimum of Months | 0.505585E+09 | 2379.41 | 19.80 | 14.36 | 0.124646E+09 | 70.27 | 19.80 | 14.36 | ||
| Maximum of Months | 0.408854E+10 | 6167.23 | 42.05 | 30.18 | 0.137147E+09 | 99.03 | 42.05 | 30.18 |
Report: ZoneCoolingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.104292E+10 | 6392.93 | 26-JAN-16:42 | 21.08 | 15.08 | 0.140335E+09 | 113.21 | 07-JAN-16:40 | 21.08 | 15.08 |
| February | 0.129716E+10 | 6452.85 | 27-FEB-16:02 | 23.73 | 16.39 | 0.124082E+09 | 112.97 | 26-FEB-16:40 | 23.73 | 16.39 |
| March | 0.192766E+10 | 6391.84 | 07-MAR-15:22 | 23.80 | 15.36 | 0.130445E+09 | 104.03 | 09-MAR-18:19 | 22.97 | 16.16 |
| April | 0.248424E+10 | 6174.27 | 06-APR-08:22 | 26.50 | 15.88 | 0.125952E+09 | 96.96 | 04-APR-20:30 | 26.50 | 15.88 |
| May | 0.336927E+10 | 5604.31 | 15-MAY-07:42 | 26.50 | 17.86 | 0.126030E+09 | 88.89 | 16-MAY-06:00 | 26.00 | 20.80 |
| June | 0.350835E+10 | 4785.54 | 22-JUN-09:02 | 34.63 | 22.51 | 0.120422E+09 | 70.27 | 16-JUN-17:10 | 34.63 | 22.51 |
| July | 0.406593E+10 | 2482.84 | 21-JUL-16:01 | 42.08 | 24.71 | 0.129276E+09 | 70.27 | 20-JUL-22:10 | 42.08 | 24.71 |
| August | 0.421376E+10 | 2533.07 | 16-AUG-14:10 | 43.33 | 26.52 | 0.123963E+09 | 70.27 | 08-AUG-06:10 | 43.33 | 26.52 |
| September | 0.373661E+10 | 4636.09 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124129E+09 | 90.90 | 30-SEP-06:00 | 25.60 | 21.36 |
| October | 0.344482E+10 | 6155.57 | 21-OCT-08:42 | 28.17 | 14.74 | 0.128302E+09 | 92.73 | 21-OCT-08:30 | 28.17 | 14.74 |
| November | 0.260370E+10 | 5991.24 | 22-NOV-21:22 | 22.75 | 17.02 | 0.126479E+09 | 95.53 | 30-NOV-22:10 | 22.20 | 17.52 |
| December | 0.152544E+10 | 6401.60 | 27-DEC-16:02 | 21.83 | 15.42 | 0.139026E+09 | 106.78 | 24-DEC-16:19 | 21.83 | 15.42 |
| Annual Sum or Average | 0.332198E+11 | 0.153844E+10 | ||||||||
| Minimum of Months | 0.104292E+10 | 2482.84 | 21.08 | 14.74 | 0.120422E+09 | 70.27 | 21.08 | 14.74 | ||
| Maximum of Months | 0.421376E+10 | 6452.85 | 43.33 | 26.52 | 0.140335E+09 | 113.21 | 43.33 | 26.52 |
Report: ZoneCoolingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.104433E+10 | 6379.55 | 26-JAN-16:42 | 21.08 | 15.08 | 0.140299E+09 | 113.21 | 07-JAN-16:40 | 21.08 | 15.08 |
| February | 0.129872E+10 | 6440.88 | 27-FEB-16:02 | 23.73 | 16.39 | 0.124074E+09 | 112.95 | 26-FEB-16:40 | 23.73 | 16.39 |
| March | 0.192814E+10 | 6378.87 | 07-MAR-15:22 | 23.80 | 15.36 | 0.130423E+09 | 103.86 | 09-MAR-18:19 | 22.97 | 16.16 |
| April | 0.248725E+10 | 6162.07 | 06-APR-08:22 | 26.50 | 15.88 | 0.125954E+09 | 96.83 | 04-APR-20:30 | 26.50 | 15.88 |
| May | 0.337201E+10 | 5589.03 | 15-MAY-07:42 | 26.50 | 17.86 | 0.126030E+09 | 88.91 | 16-MAY-06:00 | 26.00 | 20.80 |
| June | 0.350952E+10 | 4777.26 | 22-JUN-09:02 | 34.63 | 22.51 | 0.120422E+09 | 70.27 | 16-JUN-17:10 | 34.63 | 22.51 |
| July | 0.406708E+10 | 2478.56 | 21-JUL-16:01 | 42.08 | 24.71 | 0.129276E+09 | 70.27 | 20-JUL-22:10 | 42.08 | 24.71 |
| August | 0.421506E+10 | 2536.56 | 16-AUG-14:10 | 43.33 | 26.52 | 0.123963E+09 | 70.27 | 08-AUG-06:10 | 43.33 | 26.52 |
| September | 0.373783E+10 | 4625.54 | 30-SEP-06:52 | 25.60 | 21.36 | 0.124129E+09 | 90.90 | 30-SEP-06:00 | 25.60 | 21.36 |
| October | 0.344661E+10 | 6142.85 | 21-OCT-08:42 | 28.17 | 14.74 | 0.128302E+09 | 92.88 | 21-OCT-08:30 | 28.17 | 14.74 |
| November | 0.260571E+10 | 5977.93 | 22-NOV-21:22 | 22.75 | 17.02 | 0.126482E+09 | 95.48 | 30-NOV-22:10 | 22.20 | 17.52 |
| December | 0.152673E+10 | 6387.43 | 27-DEC-16:02 | 21.83 | 15.42 | 0.139024E+09 | 106.70 | 24-DEC-16:19 | 21.83 | 15.42 |
| Annual Sum or Average | 0.332390E+11 | 0.153838E+10 | ||||||||
| Minimum of Months | 0.104433E+10 | 2478.56 | 21.08 | 14.74 | 0.120422E+09 | 70.27 | 21.08 | 14.74 | ||
| Maximum of Months | 0.421506E+10 | 6440.88 | 43.33 | 26.52 | 0.140299E+09 | 113.21 | 43.33 | 26.52 |
Report: ZoneCoolingSummaryMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.262484E+09 | 164.99 | 24-JAN-21:10 | 20.88 | 17.09 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 | 0.244682E+09 | 172.27 | 27-FEB-21:10 | 20.92 | 16.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 | 0.276104E+09 | 169.65 | 27-MAR-20:10 | 30.67 | 16.51 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.273988E+09 | 174.92 | 28-APR-20:10 | 32.67 | 18.30 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.56 | 0.302367E+09 | 186.62 | 31-MAY-20:10 | 39.87 | 21.29 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 | 0.298902E+09 | 186.77 | 09-JUN-20:10 | 36.83 | 25.99 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 | 0.317850E+09 | 191.18 | 21-JUL-20:10 | 40.83 | 20.42 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 | 0.319030E+09 | 191.30 | 16-AUG-20:10 | 37.67 | 28.77 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 | 0.296718E+09 | 183.11 | 04-SEP-20:10 | 35.27 | 26.62 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.293617E+09 | 173.51 | 05-OCT-20:10 | 32.83 | 25.03 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 | 0.266612E+09 | 166.06 | 01-NOV-20:10 | 30.00 | 23.04 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 | 0.267501E+09 | 164.34 | 27-DEC-21:10 | 19.73 | 15.03 |
| Annual Sum or Average | 0.00 | 0.341986E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.244682E+09 | 164.34 | 19.73 | 15.03 | ||
| Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.319030E+09 | 191.30 | 40.83 | 28.77 |
Report: ZoneCoolingSummaryMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.290674E+09 | 186.52 | 29-JAN-23:19 | 22.00 | 19.30 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 | 0.269997E+09 | 194.53 | 05-FEB-18:10 | 30.53 | 19.22 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 | 0.310904E+09 | 224.18 | 27-MAR-17:10 | 33.85 | 18.25 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.322919E+09 | 229.02 | 29-APR-17:10 | 33.67 | 22.47 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.56 | 0.374475E+09 | 272.25 | 30-MAY-17:10 | 38.33 | 25.85 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 | 0.377311E+09 | 292.40 | 09-JUN-17:10 | 40.83 | 24.93 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 | 0.408152E+09 | 306.30 | 21-JUL-17:10 | 42.00 | 23.59 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 | 0.414149E+09 | 301.63 | 05-AUG-17:10 | 40.83 | 26.31 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 | 0.380519E+09 | 292.56 | 04-SEP-17:10 | 39.67 | 23.33 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.372265E+09 | 251.90 | 09-OCT-17:10 | 35.67 | 21.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 | 0.329808E+09 | 209.38 | 01-NOV-17:10 | 31.83 | 24.76 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 | 0.309106E+09 | 188.45 | 03-DEC-23:30 | 22.00 | 19.63 |
| Annual Sum or Average | 0.00 | 0.416028E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.269997E+09 | 186.52 | 22.00 | 18.25 | ||
| Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.414149E+09 | 306.30 | 42.00 | 26.31 |
Report: ZoneCoolingSummaryMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.283502E+09 | 164.92 | 31-JAN-21:40 | 19.30 | 15.61 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 | 0.258258E+09 | 169.85 | 27-FEB-21:10 | 20.92 | 16.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 | 0.284870E+09 | 166.02 | 07-MAR-21:10 | 19.88 | 14.10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.275437E+09 | 163.15 | 28-APR-20:10 | 32.67 | 18.30 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.56 | 0.292858E+09 | 167.96 | 31-MAY-20:10 | 39.87 | 21.29 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 | 0.286715E+09 | 168.54 | 09-JUN-20:10 | 36.83 | 25.99 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 | 0.300220E+09 | 170.75 | 21-JUL-20:10 | 40.83 | 20.42 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 | 0.301235E+09 | 171.14 | 16-AUG-20:10 | 37.67 | 28.77 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 | 0.285709E+09 | 167.79 | 04-SEP-20:10 | 35.27 | 26.62 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.289224E+09 | 162.83 | 05-OCT-20:10 | 32.83 | 25.03 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 | 0.272718E+09 | 159.89 | 01-NOV-20:10 | 30.00 | 23.04 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 | 0.283079E+09 | 164.49 | 29-DEC-21:10 | 19.98 | 13.64 |
| Annual Sum or Average | 0.00 | 0.341382E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.258258E+09 | 159.89 | 19.30 | 13.64 | ||
| Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.301235E+09 | 171.14 | 40.83 | 28.77 |
Report: ZoneHeatingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 400053.94 | 53.21 | 23-JAN-12:35 | 25.93 |
| February | 513173.26 | 75.90 | 23-FEB-11:55 | 28.00 |
| March | 1209406.95 | 70.30 | 22-MAR-09:05 | 27.67 |
| April | 1983522.25 | 104.41 | 25-APR-07:45 | 30.67 |
| May | 186195.18 | 61.88 | 02-MAY-08:05 | 26.50 |
| June | 172032.16 | 153.28 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 36938.98 | 53.08 | 30-SEP-06:55 | 25.60 |
| October | 191976.01 | 74.05 | 21-OCT-08:45 | 28.17 |
| November | 525576.88 | 67.08 | 06-NOV-08:55 | 27.00 |
| December | 492144.62 | 52.37 | 02-DEC-10:05 | 25.83 |
| Annual Sum or Average | 5711020.23 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1983522.25 | 153.28 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 623766.13 | 71.41 | 23-JAN-13:05 | 27.50 |
| February | 1095987.48 | 67.98 | 05-FEB-10:05 | 27.58 |
| March | 1728663.08 | 71.06 | 22-MAR-09:20 | 28.33 |
| April | 2302965.59 | 108.59 | 23-APR-08:55 | 31.00 |
| May | 122857.23 | 60.90 | 16-MAY-07:05 | 26.33 |
| June | 184698.91 | 152.72 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 36417.07 | 53.47 | 30-SEP-06:55 | 25.60 |
| October | 297934.92 | 76.31 | 21-OCT-08:45 | 28.17 |
| November | 831863.35 | 72.99 | 06-NOV-09:05 | 27.40 |
| December | 699661.52 | 67.82 | 10-DEC-10:05 | 27.00 |
| Annual Sum or Average | 7924815.28 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 2302965.59 | 152.72 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.270330E+09 | 536.40 | 24-JAN-07:04 | 18.17 |
| February | 0.302085E+09 | 603.88 | 10-FEB-07:04 | 19.92 |
| March | 0.470025E+09 | 799.21 | 02-MAR-07:05 | 27.67 |
| April | 0.605866E+09 | 833.59 | 27-APR-16:13 | 35.13 |
| May | 0.573829E+09 | 930.86 | 30-MAY-16:01 | 38.58 |
| June | 0.497132E+09 | 1073.22 | 09-JUN-16:01 | 41.08 |
| July | 0.256136E+09 | 1120.04 | 21-JUL-16:01 | 42.08 |
| August | 0.175362E+09 | 1069.31 | 10-AUG-16:01 | 41.33 |
| September | 0.272161E+09 | 896.61 | 05-SEP-16:01 | 38.92 |
| October | 0.357501E+09 | 808.64 | 05-OCT-16:13 | 36.20 |
| November | 0.379173E+09 | 660.89 | 01-NOV-16:13 | 32.00 |
| December | 0.331573E+09 | 574.59 | 27-DEC-07:04 | 20.92 |
| Annual Sum or Average | 0.449117E+10 | |||
| Minimum of Months | 0.175362E+09 | 536.40 | 18.17 | |
| Maximum of Months | 0.605866E+09 | 1120.04 | 42.08 |
Report: ZoneHeatingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 468737.79 | 72.20 | 23-JAN-13:05 | 27.50 |
| February | 590772.20 | 71.74 | 05-FEB-10:05 | 27.58 |
| March | 1186929.41 | 71.97 | 22-MAR-09:05 | 27.67 |
| April | 1232707.99 | 109.05 | 23-APR-08:55 | 31.00 |
| May | 89322.49 | 61.19 | 16-MAY-07:05 | 26.33 |
| June | 165580.71 | 149.35 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 36131.89 | 54.01 | 30-SEP-06:55 | 25.60 |
| October | 283016.32 | 75.94 | 21-OCT-08:45 | 28.17 |
| November | 853055.55 | 73.09 | 06-NOV-09:05 | 27.40 |
| December | 708292.47 | 68.34 | 10-DEC-10:05 | 27.00 |
| Annual Sum or Average | 5614546.83 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1232707.99 | 149.35 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 699242.86 | 73.60 | 23-JAN-13:05 | 27.50 |
| February | 1002923.98 | 71.93 | 05-FEB-10:05 | 27.58 |
| March | 1843914.33 | 71.75 | 23-MAR-08:40 | 28.33 |
| April | 2330675.70 | 111.68 | 23-APR-08:55 | 31.00 |
| May | 165373.38 | 57.83 | 16-MAY-07:05 | 26.33 |
| June | 133982.76 | 92.13 | 22-JUN-08:45 | 31.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 40594.67 | 48.80 | 30-SEP-06:55 | 25.60 |
| October | 300030.48 | 80.27 | 21-OCT-08:45 | 28.17 |
| November | 776840.72 | 72.76 | 18-NOV-10:05 | 27.42 |
| December | 778635.97 | 65.16 | 02-DEC-10:25 | 26.70 |
| Annual Sum or Average | 8072214.86 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 2330675.70 | 111.68 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 685925.27 | 73.50 | 23-JAN-13:05 | 27.50 |
| February | 995124.23 | 72.06 | 05-FEB-10:05 | 27.58 |
| March | 1839114.11 | 71.80 | 22-MAR-09:05 | 27.67 |
| April | 2313150.83 | 111.71 | 23-APR-08:55 | 31.00 |
| May | 162020.49 | 57.80 | 16-MAY-07:05 | 26.33 |
| June | 135272.20 | 92.19 | 22-JUN-08:45 | 31.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 40641.78 | 48.78 | 30-SEP-06:55 | 25.60 |
| October | 299851.88 | 80.21 | 21-OCT-08:45 | 28.17 |
| November | 756342.93 | 72.83 | 18-NOV-10:05 | 27.42 |
| December | 773354.59 | 65.17 | 02-DEC-10:25 | 26.70 |
| Annual Sum or Average | 8000798.31 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 2313150.83 | 111.71 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 485343.32 | 56.13 | 23-JAN-12:35 | 25.93 |
| February | 575349.45 | 78.63 | 23-FEB-11:55 | 28.00 |
| March | 1139474.17 | 74.01 | 22-MAR-09:05 | 27.67 |
| April | 1784011.55 | 107.33 | 25-APR-07:45 | 30.67 |
| May | 266630.53 | 62.99 | 15-MAY-07:45 | 26.50 |
| June | 118016.79 | 149.50 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 26914.11 | 51.21 | 30-SEP-06:55 | 25.60 |
| October | 191077.70 | 78.01 | 21-OCT-08:45 | 28.17 |
| November | 506746.78 | 67.79 | 06-NOV-08:55 | 27.00 |
| December | 564739.42 | 54.98 | 02-DEC-10:05 | 25.83 |
| Annual Sum or Average | 5658303.82 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1784011.55 | 149.50 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 456139.24 | 55.88 | 23-JAN-12:35 | 25.93 |
| February | 566009.03 | 78.31 | 23-FEB-11:55 | 28.00 |
| March | 886980.10 | 74.07 | 22-MAR-09:05 | 27.67 |
| April | 1221482.01 | 107.37 | 25-APR-07:45 | 30.67 |
| May | 117291.87 | 62.83 | 15-MAY-07:45 | 26.50 |
| June | 152835.53 | 149.84 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 26742.36 | 52.10 | 30-SEP-06:55 | 25.60 |
| October | 180778.06 | 76.57 | 21-OCT-08:45 | 28.17 |
| November | 490364.06 | 66.52 | 06-NOV-08:55 | 27.00 |
| December | 536747.77 | 54.12 | 02-DEC-10:05 | 25.83 |
| Annual Sum or Average | 4635370.02 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1221482.01 | 149.84 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 345019.53 | 52.07 | 23-JAN-12:35 | 25.93 |
| February | 471687.87 | 74.68 | 23-FEB-11:55 | 28.00 |
| March | 968733.51 | 67.70 | 22-MAR-09:05 | 27.67 |
| April | 1439315.93 | 101.76 | 25-APR-07:45 | 30.67 |
| May | 228130.48 | 60.88 | 02-MAY-08:05 | 26.50 |
| June | 110767.87 | 151.95 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 82529.88 | 50.47 | 30-SEP-06:55 | 25.60 |
| October | 329404.37 | 75.12 | 21-OCT-08:45 | 28.17 |
| November | 718852.28 | 65.87 | 06-NOV-08:55 | 27.00 |
| December | 550597.00 | 50.71 | 02-DEC-10:05 | 25.83 |
| Annual Sum or Average | 5245038.73 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1439315.93 | 151.95 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 735775.45 | 68.05 | 23-JAN-13:05 | 27.50 |
| February | 901880.79 | 67.37 | 04-FEB-10:33 | 27.00 |
| March | 1213274.09 | 65.90 | 22-MAR-09:05 | 27.67 |
| April | 1643698.34 | 107.04 | 23-APR-08:55 | 31.00 |
| May | 190681.39 | 60.87 | 02-MAY-08:05 | 26.50 |
| June | 114551.72 | 152.51 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 93017.85 | 49.91 | 30-SEP-06:55 | 25.60 |
| October | 593847.79 | 73.06 | 21-OCT-08:45 | 28.17 |
| November | 1787591.65 | 67.79 | 06-NOV-09:05 | 27.40 |
| December | 1423032.05 | 63.03 | 10-DEC-10:05 | 27.00 |
| Annual Sum or Average | 8697351.12 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1787591.65 | 152.51 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 336499.37 | 52.45 | 23-JAN-12:35 | 25.93 |
| February | 415243.76 | 73.78 | 23-FEB-11:55 | 28.00 |
| March | 696430.15 | 70.42 | 22-MAR-09:05 | 27.67 |
| April | 868075.42 | 103.56 | 25-APR-07:45 | 30.67 |
| May | 156754.75 | 59.55 | 15-MAY-07:45 | 26.50 |
| June | 117822.33 | 151.88 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 74707.47 | 51.38 | 30-SEP-06:55 | 25.60 |
| October | 275331.34 | 76.25 | 21-OCT-08:45 | 28.17 |
| November | 413001.02 | 66.94 | 06-NOV-08:55 | 27.00 |
| December | 510301.42 | 51.95 | 02-DEC-10:05 | 25.83 |
| Annual Sum or Average | 3864167.01 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 868075.42 | 151.88 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 578835.46 | 69.73 | 23-JAN-13:05 | 27.50 |
| February | 699578.41 | 69.32 | 05-FEB-10:05 | 27.58 |
| March | 905146.45 | 70.54 | 22-MAR-09:05 | 27.67 |
| April | 1096759.40 | 108.06 | 23-APR-08:55 | 31.00 |
| May | 116544.59 | 59.55 | 16-MAY-07:05 | 26.33 |
| June | 104014.51 | 148.14 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 86589.87 | 50.84 | 30-SEP-06:55 | 25.60 |
| October | 506311.79 | 76.43 | 21-OCT-08:45 | 28.17 |
| November | 1441396.46 | 71.53 | 06-NOV-09:05 | 27.40 |
| December | 1171671.07 | 65.55 | 10-DEC-10:05 | 27.00 |
| Annual Sum or Average | 6706848.00 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1441396.46 | 148.14 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 764819.47 | 70.70 | 23-JAN-13:05 | 27.50 |
| February | 954996.40 | 68.27 | 05-FEB-10:05 | 27.58 |
| March | 1314913.29 | 69.64 | 22-MAR-09:05 | 27.67 |
| April | 1801952.78 | 109.29 | 23-APR-08:55 | 31.00 |
| May | 217983.51 | 58.95 | 16-MAY-07:05 | 26.33 |
| June | 70465.35 | 61.75 | 22-JUN-08:40 | 29.67 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 93626.53 | 50.32 | 30-SEP-06:55 | 25.60 |
| October | 606094.22 | 75.95 | 21-OCT-08:45 | 28.17 |
| November | 1786988.15 | 70.25 | 06-NOV-09:05 | 27.40 |
| December | 1376609.88 | 66.04 | 10-DEC-10:05 | 27.00 |
| Annual Sum or Average | 8988449.58 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1801952.78 | 109.29 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 759262.69 | 70.77 | 23-JAN-13:05 | 27.50 |
| February | 949118.29 | 68.41 | 05-FEB-10:05 | 27.58 |
| March | 1308880.77 | 69.75 | 22-MAR-09:05 | 27.67 |
| April | 1795899.12 | 109.39 | 23-APR-08:55 | 31.00 |
| May | 217491.72 | 58.91 | 16-MAY-07:05 | 26.33 |
| June | 70626.63 | 61.68 | 22-JUN-08:40 | 29.67 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 93639.70 | 50.29 | 30-SEP-06:55 | 25.60 |
| October | 605393.29 | 76.04 | 21-OCT-08:45 | 28.17 |
| November | 1779854.53 | 70.34 | 06-NOV-09:05 | 27.40 |
| December | 1366794.20 | 66.10 | 10-DEC-10:05 | 27.00 |
| Annual Sum or Average | 8946960.94 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1795899.12 | 109.39 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 414367.10 | 55.40 | 23-JAN-12:35 | 25.93 |
| February | 529209.51 | 77.46 | 23-FEB-11:55 | 28.00 |
| March | 1061433.81 | 71.38 | 22-MAR-09:05 | 27.67 |
| April | 1508184.24 | 104.07 | 25-APR-07:45 | 30.67 |
| May | 271196.46 | 59.84 | 15-MAY-07:45 | 26.50 |
| June | 114684.51 | 148.94 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 81583.74 | 50.66 | 30-SEP-06:55 | 25.60 |
| October | 322662.56 | 78.33 | 21-OCT-08:45 | 28.17 |
| November | 551996.56 | 64.96 | 06-NOV-08:55 | 27.00 |
| December | 568629.64 | 53.88 | 02-DEC-10:05 | 25.83 |
| Annual Sum or Average | 5423948.14 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1508184.24 | 148.94 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 411595.96 | 55.38 | 23-JAN-12:35 | 25.93 |
| February | 528370.28 | 77.34 | 23-FEB-11:55 | 28.00 |
| March | 1053080.53 | 71.47 | 22-MAR-09:05 | 27.67 |
| April | 1504228.74 | 104.11 | 25-APR-07:45 | 30.67 |
| May | 269360.30 | 59.87 | 15-MAY-07:45 | 26.50 |
| June | 115105.99 | 148.96 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 81606.21 | 50.66 | 30-SEP-06:55 | 25.60 |
| October | 322305.66 | 78.37 | 21-OCT-08:45 | 28.17 |
| November | 537608.27 | 64.97 | 06-NOV-08:55 | 27.00 |
| December | 565974.37 | 53.90 | 02-DEC-10:05 | 25.83 |
| Annual Sum or Average | 5389236.31 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1504228.74 | 148.96 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 345380.06 | 49.49 | 23-JAN-12:35 | 25.93 |
| February | 490169.28 | 72.27 | 23-FEB-11:55 | 28.00 |
| March | 1196593.25 | 74.61 | 22-MAR-09:03 | 27.67 |
| April | 1821300.53 | 99.41 | 25-APR-07:45 | 30.67 |
| May | 281671.02 | 64.05 | 01-MAY-09:25 | 26.90 |
| June | 95120.37 | 150.64 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 111593.66 | 49.40 | 30-SEP-06:55 | 25.60 |
| October | 451271.74 | 74.27 | 21-OCT-08:45 | 28.17 |
| November | 801753.53 | 64.62 | 06-NOV-08:55 | 27.00 |
| December | 631655.55 | 50.10 | 02-DEC-10:05 | 25.83 |
| Annual Sum or Average | 6226508.99 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1821300.53 | 150.64 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1149746.55 | 68.78 | 23-JAN-13:05 | 27.50 |
| February | 1291701.52 | 76.27 | 05-FEB-10:03 | 27.58 |
| March | 1757360.24 | 75.91 | 22-MAR-09:03 | 27.67 |
| April | 2163491.28 | 106.45 | 23-APR-08:55 | 31.00 |
| May | 207882.81 | 62.03 | 02-MAY-08:05 | 26.50 |
| June | 127306.04 | 150.09 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 124859.18 | 59.48 | 30-SEP-07:07 | 27.23 |
| October | 837599.74 | 70.64 | 21-OCT-08:45 | 28.17 |
| November | 2376520.20 | 66.23 | 06-NOV-09:05 | 27.40 |
| December | 2095085.37 | 65.53 | 02-DEC-10:23 | 26.70 |
| Annual Sum or Average | 12131552.93 | |||
| Minimum of Months | 0.00 | 0.00 | 26.50 | |
| Maximum of Months | 2376520.20 | 150.09 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 323316.78 | 50.23 | 23-JAN-12:35 | 25.93 |
| February | 386234.12 | 71.79 | 23-FEB-11:55 | 28.00 |
| March | 873794.35 | 69.90 | 22-MAR-09:05 | 27.67 |
| April | 882321.83 | 102.90 | 25-APR-07:45 | 30.67 |
| May | 153855.08 | 61.89 | 02-MAY-08:05 | 26.50 |
| June | 127505.64 | 146.83 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 94150.07 | 50.88 | 30-SEP-06:55 | 25.60 |
| October | 316569.23 | 75.44 | 21-OCT-08:45 | 28.17 |
| November | 457738.31 | 67.51 | 06-NOV-08:55 | 27.00 |
| December | 561158.00 | 50.93 | 02-DEC-10:05 | 25.83 |
| Annual Sum or Average | 4176643.41 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 882321.83 | 146.83 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 621766.10 | 70.08 | 23-JAN-13:05 | 27.50 |
| February | 634962.52 | 69.07 | 05-FEB-10:05 | 27.58 |
| March | 1011074.97 | 70.07 | 22-MAR-09:05 | 27.67 |
| April | 1028277.45 | 106.87 | 23-APR-08:55 | 31.00 |
| May | 119282.99 | 61.48 | 02-MAY-08:05 | 26.50 |
| June | 120002.43 | 101.06 | 22-JUN-08:45 | 31.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 106342.62 | 50.51 | 30-SEP-06:55 | 25.60 |
| October | 505315.85 | 76.26 | 21-OCT-08:45 | 28.17 |
| November | 1146426.37 | 72.15 | 06-NOV-09:05 | 27.40 |
| December | 1166096.44 | 67.53 | 10-DEC-10:05 | 27.00 |
| Annual Sum or Average | 6459547.73 | |||
| Minimum of Months | 0.00 | 0.00 | 25.60 | |
| Maximum of Months | 1166096.44 | 106.87 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1062089.83 | 72.25 | 23-JAN-13:05 | 27.50 |
| February | 1255971.67 | 67.21 | 23-FEB-11:45 | 27.17 |
| March | 1737290.57 | 71.04 | 23-MAR-08:40 | 28.33 |
| April | 2288925.91 | 110.05 | 23-APR-08:55 | 31.00 |
| May | 199272.39 | 60.07 | 16-MAY-07:05 | 26.33 |
| June | 131864.10 | 149.12 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 121591.60 | 59.67 | 30-SEP-07:07 | 27.23 |
| October | 901347.76 | 77.66 | 21-OCT-09:00 | 29.00 |
| November | 2521213.85 | 70.03 | 06-NOV-09:05 | 27.40 |
| December | 1986987.20 | 67.96 | 10-DEC-10:05 | 27.00 |
| Annual Sum or Average | 12206554.88 | |||
| Minimum of Months | 0.00 | 0.00 | 26.33 | |
| Maximum of Months | 2521213.85 | 149.12 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1015279.35 | 72.38 | 23-JAN-13:05 | 27.50 |
| February | 1235220.35 | 67.77 | 23-FEB-11:45 | 27.17 |
| March | 1721725.65 | 70.94 | 23-MAR-08:40 | 28.33 |
| April | 2246312.72 | 110.13 | 23-APR-08:55 | 31.00 |
| May | 192936.13 | 60.14 | 16-MAY-07:05 | 26.33 |
| June | 132956.37 | 148.73 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 121604.72 | 59.66 | 30-SEP-07:07 | 27.23 |
| October | 889600.46 | 75.75 | 21-OCT-08:45 | 28.17 |
| November | 2489643.06 | 70.29 | 06-NOV-09:05 | 27.40 |
| December | 1946169.97 | 68.08 | 10-DEC-10:05 | 27.00 |
| Annual Sum or Average | 11991448.78 | |||
| Minimum of Months | 0.00 | 0.00 | 26.33 | |
| Maximum of Months | 2489643.06 | 148.73 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 388547.72 | 52.90 | 23-JAN-12:35 | 25.93 |
| February | 497925.41 | 75.25 | 23-FEB-11:55 | 28.00 |
| March | 1167583.91 | 70.39 | 23-MAR-08:40 | 28.33 |
| April | 1883826.22 | 103.52 | 25-APR-07:45 | 30.67 |
| May | 334521.53 | 61.06 | 15-MAY-07:45 | 26.50 |
| June | 109209.76 | 153.63 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 114256.20 | 59.40 | 30-SEP-07:07 | 27.23 |
| October | 387622.34 | 78.09 | 21-OCT-08:45 | 28.17 |
| November | 562652.34 | 67.90 | 06-NOV-08:55 | 27.00 |
| December | 625885.28 | 53.51 | 02-DEC-10:05 | 25.83 |
| Annual Sum or Average | 6072030.71 | |||
| Minimum of Months | 0.00 | 0.00 | 25.83 | |
| Maximum of Months | 1883826.22 | 153.63 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 384581.94 | 52.90 | 23-JAN-12:35 | 25.93 |
| February | 493859.54 | 75.16 | 23-FEB-11:55 | 28.00 |
| March | 1161377.63 | 70.29 | 23-MAR-08:40 | 28.33 |
| April | 1835146.96 | 103.65 | 25-APR-07:45 | 30.67 |
| May | 329282.41 | 61.04 | 15-MAY-07:45 | 26.50 |
| June | 108892.45 | 153.36 | 22-JUN-09:05 | 34.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 114265.96 | 59.39 | 30-SEP-07:07 | 27.23 |
| October | 382376.63 | 78.15 | 21-OCT-08:45 | 28.17 |
| November | 547133.37 | 67.84 | 06-NOV-08:55 | 27.00 |
| December | 621563.77 | 53.62 | 02-DEC-10:05 | 25.83 |
| Annual Sum or Average | 5978480.66 | |||
| Minimum of Months | 0.00 | 0.00 | 25.83 | |
| Maximum of Months | 1835146.96 | 153.36 | 34.63 |
Report: ZoneHeatingSummaryMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 15.70 | |
| Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 15.70 | |
| Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 15.70 | |
| Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.468251E+09 | 447.62 | 03-JAN-08:09 | 0.621586E+09 | 544.92 | 03-JAN-08:09 |
| February | 0.433623E+09 | 447.62 | 01-FEB-08:09 | 0.574385E+09 | 544.92 | 01-FEB-08:09 |
| March | 0.502522E+09 | 447.62 | 01-MAR-08:09 | 0.663122E+09 | 544.92 | 01-MAR-08:09 |
| April | 0.460516E+09 | 447.62 | 03-APR-07:10 | 0.610467E+09 | 544.92 | 03-APR-07:10 |
| May | 0.491098E+09 | 447.62 | 01-MAY-07:10 | 0.649277E+09 | 544.92 | 01-MAY-07:10 |
| June | 0.483363E+09 | 447.62 | 01-JUN-07:10 | 0.638158E+09 | 544.92 | 01-JUN-07:10 |
| July | 0.468251E+09 | 447.62 | 03-JUL-07:10 | 0.621586E+09 | 544.92 | 03-JUL-07:10 |
| August | 0.502522E+09 | 447.62 | 01-AUG-07:10 | 0.663122E+09 | 544.92 | 01-AUG-07:10 |
| September | 0.460516E+09 | 447.62 | 01-SEP-07:10 | 0.610467E+09 | 544.92 | 01-SEP-07:10 |
| October | 0.479675E+09 | 447.62 | 02-OCT-07:10 | 0.635432E+09 | 544.92 | 02-OCT-07:10 |
| November | 0.460516E+09 | 447.62 | 01-NOV-07:10 | 0.610467E+09 | 544.92 | 01-NOV-07:10 |
| December | 0.468251E+09 | 447.62 | 01-DEC-08:09 | 0.621586E+09 | 544.92 | 01-DEC-08:09 |
| Annual Sum or Average | 0.567911E+10 | 0.751966E+10 | ||||
| Minimum of Months | 0.433623E+09 | 447.62 | 0.574385E+09 | 544.92 | ||
| Maximum of Months | 0.502522E+09 | 447.62 | 0.663122E+09 | 544.92 |
Report: ZoneElectricSummaryMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 78005350.11 | 87.71 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 70456445.26 | 87.71 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 78005350.11 | 87.71 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 75489048.50 | 87.71 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 78005350.11 | 87.71 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 75489048.50 | 87.71 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 78005350.11 | 87.71 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 78005350.11 | 87.71 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 75489048.50 | 87.71 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 78005350.11 | 87.71 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 75489048.50 | 87.71 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 78005350.11 | 87.71 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.918450E+09 | 0.122128E+11 | ||||
| Minimum of Months | 70456445.26 | 87.71 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 78005350.11 | 87.71 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.824800E+09 | 307.95 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.744981E+09 | 307.95 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.824800E+09 | 307.95 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.798194E+09 | 307.95 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.824800E+09 | 307.95 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.798194E+09 | 307.95 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.824800E+09 | 307.95 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.824800E+09 | 307.95 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.798194E+09 | 307.95 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.824800E+09 | 307.95 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.798194E+09 | 307.95 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.824800E+09 | 307.95 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.971136E+10 | 0.00 | 0.00 | ||
| Minimum of Months | 0.744981E+09 | 307.95 | 0.00 | 0.00 | |
| Maximum of Months | 0.824800E+09 | 307.95 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.824800E+09 | 307.95 | 01-JAN-00:10 | 0.576651E+10 | 3803.87 | 01-JAN-07:10 |
| February | 0.744981E+09 | 307.95 | 01-FEB-00:10 | 0.520846E+10 | 3803.87 | 01-FEB-07:10 |
| March | 0.824800E+09 | 307.95 | 01-MAR-00:10 | 0.576651E+10 | 3803.87 | 01-MAR-07:10 |
| April | 0.798194E+09 | 307.95 | 01-APR-00:10 | 0.558049E+10 | 3803.87 | 01-APR-06:10 |
| May | 0.824800E+09 | 307.95 | 01-MAY-00:10 | 0.576651E+10 | 3803.87 | 01-MAY-06:10 |
| June | 0.798194E+09 | 307.95 | 01-JUN-00:10 | 0.558049E+10 | 3803.87 | 01-JUN-06:10 |
| July | 0.824800E+09 | 307.95 | 01-JUL-00:10 | 0.576651E+10 | 3803.87 | 01-JUL-06:10 |
| August | 0.824800E+09 | 307.95 | 01-AUG-00:10 | 0.576651E+10 | 3803.87 | 01-AUG-06:10 |
| September | 0.798194E+09 | 307.95 | 01-SEP-00:10 | 0.558049E+10 | 3803.87 | 01-SEP-06:10 |
| October | 0.824800E+09 | 307.95 | 01-OCT-00:10 | 0.576651E+10 | 3803.87 | 01-OCT-06:10 |
| November | 0.798194E+09 | 307.95 | 01-NOV-00:10 | 0.558049E+10 | 3803.87 | 01-NOV-06:10 |
| December | 0.824800E+09 | 307.95 | 01-DEC-00:10 | 0.576651E+10 | 3803.87 | 01-DEC-07:10 |
| Annual Sum or Average | 0.971136E+10 | 0.678960E+11 | ||||
| Minimum of Months | 0.744981E+09 | 307.95 | 0.520846E+10 | 3803.87 | ||
| Maximum of Months | 0.824800E+09 | 307.95 | 0.576651E+10 | 3803.87 |
Report: ZoneElectricSummaryMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.824800E+09 | 307.95 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.744981E+09 | 307.95 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.824800E+09 | 307.95 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.798194E+09 | 307.95 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.824800E+09 | 307.95 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.798194E+09 | 307.95 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.824800E+09 | 307.95 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.824800E+09 | 307.95 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.798194E+09 | 307.95 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.824800E+09 | 307.95 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.798194E+09 | 307.95 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.824800E+09 | 307.95 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.971136E+10 | 0.00 | 0.00 | ||
| Minimum of Months | 0.744981E+09 | 307.95 | 0.00 | 0.00 | |
| Maximum of Months | 0.824800E+09 | 307.95 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 665543.16 | 36995787.35 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4779845.69 | 31031747.05 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15966266.69 | 15000004.34 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34914425.18 | 4721581.38 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73934577.12 | 322865.42 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94171835.05 | 9960.17 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112667E+09 | 0.00 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116023E+09 | 0.00 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83500088.71 | 38647.38 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53137165.90 | 505944.63 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23654562.60 | 4973442.20 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3754367.80 | 23746899.12 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617169E+09 | 0.117347E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 665543.16 | 0.00 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116023E+09 | 36995787.35 |
Report: SpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 618207.30 | 37156906.65 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4759987.88 | 31232327.39 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15966334.70 | 14924364.37 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34905404.70 | 4688962.18 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73941128.69 | 323297.29 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94171581.19 | 10350.39 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112667E+09 | 0.00 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116023E+09 | 0.00 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83500050.03 | 37013.26 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53118860.40 | 492249.90 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23552296.85 | 4876771.49 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3692577.79 | 23588476.33 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616916E+09 | 0.117331E+09 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 618207.30 | 0.00 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116023E+09 | 37156906.65 |
Report: SpaceGainsMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.227408E+09 | 0.468251E+09 | 0.621586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 244078.00 | 44480478.64 |
| February | 0.216037E+09 | 0.433623E+09 | 0.574385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2986909.10 | 41351872.13 |
| March | 0.261519E+09 | 0.502522E+09 | 0.663122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11622715.74 | 26358341.25 |
| April | 0.227408E+09 | 0.460516E+09 | 0.610467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21082028.45 | 13013591.95 |
| May | 0.250148E+09 | 0.491098E+09 | 0.649277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50505189.23 | 3088037.82 |
| June | 0.250148E+09 | 0.483363E+09 | 0.638158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65328208.78 | 1550816.08 |
| July | 0.227408E+09 | 0.468251E+09 | 0.621586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78431758.85 | 21481.18 |
| August | 0.261519E+09 | 0.502522E+09 | 0.663122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85414875.68 | 10854.75 |
| September | 0.227408E+09 | 0.460516E+09 | 0.610467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54912981.24 | 1616966.63 |
| October | 0.238778E+09 | 0.479675E+09 | 0.635432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31546086.72 | 5943292.66 |
| November | 0.227408E+09 | 0.460516E+09 | 0.610467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12170904.84 | 16383946.64 |
| December | 0.227408E+09 | 0.468251E+09 | 0.621586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801066.90 | 34149052.45 |
| Annual Sum or Average | 0.284259E+10 | 0.567911E+10 | 0.751966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416047E+09 | 0.187969E+09 |
| Minimum of Months | 0.216037E+09 | 0.433623E+09 | 0.574385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 244078.00 | 10854.75 |
| Maximum of Months | 0.261519E+09 | 0.502522E+09 | 0.663122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85414875.68 | 44480478.64 |
Report: SpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 617678.26 | 37287853.51 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4754910.17 | 31273420.06 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15959475.85 | 14959135.92 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34896280.20 | 4740169.16 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73940975.38 | 330952.00 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94170962.13 | 11092.82 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112667E+09 | 0.00 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116023E+09 | 0.00 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83500025.15 | 37001.70 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53118600.09 | 499524.82 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23551591.16 | 4947773.87 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3692417.15 | 23724022.61 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616893E+09 | 0.117811E+09 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 617678.26 | 0.00 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116023E+09 | 37287853.51 |
Report: SpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 372993.92 | 22168174.56 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2869413.46 | 18765750.42 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9629702.42 | 9011015.89 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21052438.69 | 2856113.14 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44599177.06 | 195092.69 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56802068.59 | 5918.89 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67957988.28 | 0.00 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69981968.84 | 0.00 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50365021.70 | 21137.16 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32039013.37 | 286019.29 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14203808.90 | 2917715.07 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2226301.83 | 14158438.41 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372100E+09 | 70385375.52 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 372993.92 | 0.00 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69981968.84 | 22168174.56 |
Report: SpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 372932.44 | 22177325.56 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2869296.05 | 18769945.67 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9629581.39 | 9010067.88 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21052252.03 | 2856599.81 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44599171.08 | 195155.81 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56802063.13 | 5922.93 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67957988.36 | 0.00 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69981968.91 | 0.00 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50365021.50 | 21136.35 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32039012.08 | 286050.40 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14203812.99 | 2918347.76 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2226293.48 | 14162933.44 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372099E+09 | 70403485.61 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 372932.44 | 0.00 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69981968.91 | 22177325.56 |
Report: SpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401422.92 | 22366587.67 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2882543.59 | 18771231.03 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9629608.93 | 9093624.99 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21057332.99 | 2882085.05 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44595267.66 | 195374.01 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56802233.83 | 5698.30 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67957985.74 | 0.00 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69981966.96 | 0.00 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50365049.13 | 22088.83 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32050343.54 | 296730.90 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14266827.49 | 2989877.51 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2264239.45 | 14347164.99 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372255E+09 | 70970463.27 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 401422.92 | 0.00 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69981966.96 | 22366587.67 |
Report: SpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401316.91 | 22500507.09 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2882752.79 | 18922692.76 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9628981.41 | 9196219.71 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21055455.91 | 2935126.33 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44595265.30 | 207313.09 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56802103.69 | 5914.73 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67957986.70 | 0.00 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69981968.20 | 0.00 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50365065.26 | 23801.46 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32050410.77 | 310763.32 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14266657.51 | 3050178.55 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2264179.03 | 14469070.99 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372252E+09 | 71621588.02 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 401316.91 | 0.00 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69981968.20 | 22500507.09 |
Report: SpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 942467.85 | 52265949.40 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6823392.70 | 44490520.19 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22824408.90 | 21760805.09 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49991955.71 | 6767355.15 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106020E+09 | 447478.47 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135063E+09 | 13890.48 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161641E+09 | 0.00 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166460E+09 | 0.00 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119745E+09 | 45749.70 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76142323.18 | 597072.20 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33831950.31 | 6643907.61 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5339904.19 | 32624703.50 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.884827E+09 | 0.165657E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 942467.85 | 0.00 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166460E+09 | 52265949.40 |
Report: SpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 877599.16 | 51101655.01 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6800589.02 | 44457863.05 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22822517.54 | 21648719.05 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49978232.33 | 6739173.85 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106030E+09 | 450394.36 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135063E+09 | 14414.27 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161641E+09 | 0.00 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166460E+09 | 0.00 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119745E+09 | 44048.77 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76120846.26 | 573693.60 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33701807.68 | 6464217.37 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5257537.14 | 31735969.10 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.884498E+09 | 0.163230E+09 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 877599.16 | 0.00 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166460E+09 | 51101655.01 |
Report: SpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 942041.09 | 52407046.58 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6823140.06 | 44637259.53 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22817859.31 | 21833146.45 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49980929.34 | 6847809.34 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106019E+09 | 461575.18 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135063E+09 | 15030.53 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161641E+09 | 0.00 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166460E+09 | 0.00 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119745E+09 | 45896.55 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76141629.04 | 611963.00 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33830925.11 | 6741828.97 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5339622.96 | 32794362.31 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.884805E+09 | 0.166396E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 942041.09 | 0.00 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166460E+09 | 52407046.58 |
Report: SpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 876112.93 | 51156496.99 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6791349.67 | 44617230.68 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22811836.79 | 21732106.66 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49963956.81 | 6820668.37 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106029E+09 | 463283.03 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135062E+09 | 15573.94 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161641E+09 | 0.00 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166460E+09 | 0.00 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119745E+09 | 44205.52 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76116776.32 | 590569.69 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33687532.82 | 6590782.93 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5253770.49 | 31933728.61 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.884439E+09 | 0.163965E+09 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 876112.93 | 0.00 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166460E+09 | 51156496.99 |
Report: SpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 529639.34 | 30779940.29 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4100476.03 | 26393453.89 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13764944.92 | 12952716.32 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30145810.89 | 4081236.04 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63954375.54 | 269669.61 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81466886.71 | 8275.97 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97497739.43 | 0.00 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100405E+09 | 0.00 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72227385.53 | 25903.11 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45914043.24 | 345527.31 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20326915.22 | 3937084.82 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3170553.21 | 19266539.46 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533503E+09 | 98060346.82 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 529639.34 | 0.00 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100405E+09 | 30779940.29 |
Report: SpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 529581.55 | 30796540.41 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4100279.44 | 26410535.24 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13764806.95 | 12950682.72 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30145531.12 | 4081883.65 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63954359.98 | 269768.70 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81466877.82 | 8282.50 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97497739.54 | 0.00 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100405E+09 | 0.00 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72227384.97 | 25899.72 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45913998.43 | 345605.89 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20326649.24 | 3938300.77 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3170493.66 | 19275709.64 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533502E+09 | 98103209.25 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 529581.55 | 0.00 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100405E+09 | 30796540.41 |
Report: SpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 568253.80 | 31735274.34 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4115267.76 | 26889756.84 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13766202.39 | 13113233.13 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30153351.71 | 4102815.23 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63949000.32 | 267948.02 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81467175.17 | 7956.61 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97497735.67 | 0.00 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100405E+09 | 0.00 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72227373.11 | 27040.20 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45926681.50 | 361660.52 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20404895.77 | 4054425.73 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3220370.13 | 19876541.07 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533701E+09 | 0.100437E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 568253.80 | 0.00 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100405E+09 | 31735274.34 |
Report: SpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 568254.65 | 31742440.90 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4115251.57 | 26895011.92 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13766085.31 | 13112496.47 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30153179.92 | 4103443.59 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63948979.50 | 268052.05 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81467165.14 | 7962.93 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97497736.64 | 0.00 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100405E+09 | 0.00 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72227374.01 | 27036.55 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45926676.44 | 361714.84 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20404891.77 | 4055160.68 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3220373.61 | 19880195.13 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533701E+09 | 0.100454E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 568254.65 | 0.00 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100405E+09 | 31742440.90 |
Report: SpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1210089.02 | 67836857.11 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8909542.24 | 58171438.44 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29890685.01 | 28410108.15 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65645720.25 | 8649691.37 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139635E+09 | 567891.96 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177947E+09 | 19971.16 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213102E+09 | 0.00 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219469E+09 | 0.00 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157736E+09 | 57220.88 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100143E+09 | 744372.70 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44329733.85 | 8473746.15 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6920316.18 | 42349241.15 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116494E+10 | 0.215281E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1210089.02 | 0.00 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219469E+09 | 67836857.11 |
Report: SpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1129170.13 | 65034805.11 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8899402.20 | 58316273.70 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29895303.20 | 28446594.55 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65627891.11 | 8659088.36 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139647E+09 | 578575.93 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177946E+09 | 20934.16 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213102E+09 | 0.00 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219469E+09 | 0.00 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157736E+09 | 56021.76 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100117E+09 | 723725.86 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44166218.58 | 8240314.65 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6820432.83 | 40647179.31 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116456E+10 | 0.210724E+09 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1129170.13 | 0.00 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219469E+09 | 65034805.11 |
Report: SpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1209682.72 | 68235096.38 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8908117.24 | 58470050.51 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29868747.48 | 28588674.02 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65628472.43 | 8811134.96 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139634E+09 | 596281.44 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177945E+09 | 22230.41 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213102E+09 | 0.00 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219469E+09 | 0.00 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157736E+09 | 57656.01 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100142E+09 | 774134.18 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44327943.81 | 8672929.22 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6919441.94 | 42705102.78 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116489E+10 | 0.216933E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1209682.72 | 0.00 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219469E+09 | 68235096.38 |
Report: SpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1124546.60 | 65415699.14 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8871200.32 | 58613491.76 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29863252.10 | 28498955.63 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65604945.77 | 8824259.18 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139646E+09 | 604265.44 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177944E+09 | 23368.68 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213102E+09 | 0.00 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219469E+09 | 0.00 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157736E+09 | 56455.02 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100109E+09 | 760094.37 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44140761.72 | 8507552.19 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6810040.33 | 41330217.19 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116442E+10 | 0.212634E+09 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1124546.60 | 0.00 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219469E+09 | 65415699.14 |
Report: SpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 680458.23 | 39628820.45 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5360458.25 | 35271931.66 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18022097.86 | 17075858.82 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39579330.70 | 5330675.71 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84231082.89 | 357580.38 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107333E+09 | 12215.39 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128538E+09 | 0.00 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132378E+09 | 0.00 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95142215.81 | 34357.81 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60386324.02 | 454123.86 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26633697.14 | 5114400.94 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4111581.89 | 24949752.77 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702397E+09 | 0.128230E+09 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 680458.23 | 0.00 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132378E+09 | 39628820.45 |
Report: SpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 680376.37 | 39678378.07 |
| February | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5359724.18 | 35307550.32 |
| March | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18021343.22 | 17074953.14 |
| April | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39578525.20 | 5332850.15 |
| May | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84231070.23 | 358167.26 |
| June | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107333E+09 | 12237.14 |
| July | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128538E+09 | 0.00 |
| August | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132378E+09 | 0.00 |
| September | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95142214.37 | 34350.46 |
| October | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60386107.67 | 454424.45 |
| November | 0.421173E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26632660.79 | 5118738.50 |
| December | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4110994.79 | 24976836.90 |
| Annual Sum or Average | 0.512427E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702392E+09 | 0.128348E+09 |
| Minimum of Months | 0.393095E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 680376.37 | 0.00 |
| Maximum of Months | 0.435212E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132378E+09 | 39678378.07 |
Report: SpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 730106.14 | 41773773.23 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5373443.57 | 35526286.14 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18021958.26 | 17222040.50 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39590722.60 | 5332233.79 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84224024.69 | 350700.70 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107334E+09 | 11635.76 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128538E+09 | 0.00 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132378E+09 | 0.00 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95142209.54 | 35158.48 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60403042.26 | 466964.42 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26737267.11 | 5247846.80 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4173890.50 | 26051131.43 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702647E+09 | 0.132018E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 730106.14 | 0.00 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132378E+09 | 41773773.23 |
Report: SpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 730047.59 | 41786047.72 |
| February | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5373372.59 | 35539725.70 |
| March | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18021562.61 | 17222578.83 |
| April | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39590213.07 | 5334240.10 |
| May | 0.424935E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84223961.50 | 351013.38 |
| June | 0.406980E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107334E+09 | 11657.67 |
| July | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128538E+09 | 0.00 |
| August | 0.418950E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132378E+09 | 0.00 |
| September | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95142208.10 | 35151.21 |
| October | 0.430920E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60403021.03 | 467172.21 |
| November | 0.418950E+09 | 75489048.50 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26737260.71 | 5250299.60 |
| December | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4173917.79 | 26063147.51 |
| Annual Sum or Average | 0.505732E+10 | 0.918450E+09 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702646E+09 | 0.132061E+09 |
| Minimum of Months | 0.389025E+09 | 70456445.26 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 730047.59 | 0.00 |
| Maximum of Months | 0.436905E+09 | 78005350.11 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132378E+09 | 41786047.72 |
Report: SpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31216.69 | 13713014.88 |
| February | 0.657255E+09 | 0.744981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734941.13 | 12792727.58 |
| March | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2775803.34 | 7355746.50 |
| April | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6445650.44 | 2528775.40 |
| May | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16867428.73 | 242522.09 |
| June | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22051462.74 | 41385.76 |
| July | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27405978.28 | 0.00 |
| August | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28322175.94 | 0.00 |
| September | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19233398.28 | 30242.69 |
| October | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11113702.40 | 393625.52 |
| November | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3803868.88 | 2372753.09 |
| December | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287215.34 | 9343388.50 |
| Annual Sum or Average | 0.856778E+10 | 0.971136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139073E+09 | 48814182.02 |
| Minimum of Months | 0.657255E+09 | 0.744981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31216.69 | 0.00 |
| Maximum of Months | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28322175.94 | 13713014.88 |
Report: SpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 315839.49 | 0.145374E+10 |
| February | 0.657255E+09 | 0.744981E+09 | 0.260423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26125356.21 | 0.107183E+10 |
| March | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106984E+09 | 0.800885E+09 |
| April | 0.704201E+09 | 0.798194E+09 | 0.279025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315726E+09 | 0.362845E+09 |
| May | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.885688E+09 | 97912175.98 |
| June | 0.704201E+09 | 0.798194E+09 | 0.279025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104722E+10 | 32072047.25 |
| July | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137529E+10 | 88494.04 |
| August | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138196E+10 | 0.00 |
| September | 0.704201E+09 | 0.798194E+09 | 0.279025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909328E+09 | 45149185.32 |
| October | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554080E+09 | 0.172595E+09 |
| November | 0.704201E+09 | 0.798194E+09 | 0.279025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126019E+09 | 0.434659E+09 |
| December | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4562209.50 | 0.112048E+10 |
| Annual Sum or Average | 0.856778E+10 | 0.971136E+10 | 0.339480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673330E+10 | 0.559226E+10 |
| Minimum of Months | 0.657255E+09 | 0.744981E+09 | 0.260423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 315839.49 | 0.00 |
| Maximum of Months | 0.727675E+09 | 0.824800E+09 | 0.288326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138196E+10 | 0.145374E+10 |
Report: SpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20201.13 | 11204908.32 |
| February | 0.657255E+09 | 0.744981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582819.03 | 10208654.24 |
| March | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2195100.77 | 5856802.36 |
| April | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5364722.42 | 2034758.40 |
| May | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13778150.84 | 208977.67 |
| June | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17869052.32 | 35650.56 |
| July | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22218394.94 | 0.00 |
| August | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22923704.65 | 0.00 |
| September | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15623082.57 | 27453.86 |
| October | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9090417.04 | 350286.71 |
| November | 0.704201E+09 | 0.798194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3125132.72 | 1990808.26 |
| December | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234833.57 | 7610699.20 |
| Annual Sum or Average | 0.856778E+10 | 0.971136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113026E+09 | 39528999.58 |
| Minimum of Months | 0.657255E+09 | 0.744981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20201.13 | 0.00 |
| Maximum of Months | 0.727675E+09 | 0.824800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22923704.65 | 11204908.32 |
Report: PeakSpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.72 | 29-JAN-12:00 | 52.22 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.28 | 05-FEB-15:00 | 59.08 | 10-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.09 | 01-MAR-13:00 | 58.23 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.07 | 28-APR-13:20 | 24.59 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.37 | 21-MAY-13:00 | 11.05 | 01-MAY-07:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.29 | 09-JUN-16:00 | 6.48 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.58 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.85 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.97 | 14-SEP-13:00 | 5.25 | 25-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.98 | 19-OCT-15:00 | 16.99 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.78 | 19-NOV-14:00 | 24.21 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 10-DEC-13:00 | 74.00 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 20.72 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 350.37 | 74.00 |
Report: PeakSpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 | 23-JAN-13:05 | 52.22 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.28 | 05-FEB-15:00 | 59.43 | 10-FEB-19:55 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.09 | 01-MAR-13:00 | 55.42 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.07 | 28-APR-13:20 | 24.59 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.37 | 21-MAY-13:00 | 11.12 | 01-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.29 | 09-JUN-16:00 | 6.63 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.58 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.85 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.97 | 14-SEP-13:00 | 4.95 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.98 | 19-OCT-15:00 | 16.32 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.78 | 19-NOV-14:00 | 23.76 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 10-DEC-13:00 | 64.90 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 350.37 | 64.90 |
Report: PeakSpaceGainsMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 451.21 | 03-JAN-08:09 | 447.62 | 03-JAN-08:09 | 544.92 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.18 | 23-JAN-13:00 | 71.54 | 18-JAN-04:00 |
| February | 451.21 | 01-FEB-08:09 | 447.62 | 01-FEB-08:09 | 544.92 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.55 | 06-FEB-15:00 | 63.06 | 10-FEB-19:55 |
| March | 451.21 | 01-MAR-08:09 | 447.62 | 01-MAR-08:09 | 544.92 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 102.09 | 01-MAR-13:00 | 114.51 | 25-MAR-09:00 |
| April | 451.21 | 03-APR-07:10 | 447.62 | 03-APR-07:10 | 544.92 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.07 | 28-APR-13:20 | 36.48 | 05-APR-01:00 |
| May | 451.21 | 01-MAY-07:10 | 447.62 | 01-MAY-07:10 | 544.92 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.22 | 21-MAY-13:00 | 16.78 | 01-MAY-06:00 |
| June | 451.21 | 01-JUN-07:10 | 447.62 | 01-JUN-07:10 | 544.92 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.28 | 09-JUN-16:00 | 18.40 | 07-JUN-06:00 |
| July | 451.21 | 03-JUL-07:10 | 447.62 | 03-JUL-07:10 | 544.92 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.58 | 14-JUL-14:00 | 1.37 | 03-JUL-05:50 |
| August | 451.21 | 01-AUG-07:10 | 447.62 | 01-AUG-07:10 | 544.92 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.85 | 16-AUG-12:00 | 1.20 | 27-AUG-06:00 |
| September | 451.21 | 01-SEP-07:10 | 447.62 | 01-SEP-07:10 | 544.92 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.96 | 14-SEP-13:00 | 16.57 | 27-SEP-06:00 |
| October | 451.21 | 02-OCT-07:10 | 447.62 | 02-OCT-07:10 | 544.92 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.98 | 19-OCT-15:00 | 28.49 | 20-OCT-05:00 |
| November | 451.21 | 01-NOV-07:10 | 447.62 | 01-NOV-07:10 | 544.92 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.53 | 01-NOV-14:00 | 31.33 | 22-NOV-07:00 |
| December | 451.21 | 01-DEC-08:09 | 447.62 | 01-DEC-08:09 | 544.92 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 04-DEC-15:00 | 55.32 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 451.21 | 447.62 | 544.92 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 1.20 | |||||
| Maximum of Months | 451.21 | 447.62 | 544.92 | 0.00 | 0.00 | 0.00 | 0.00 | 215.22 | 114.51 |
Report: PeakSpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 23-JAN-13:05 | 52.22 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.28 | 05-FEB-15:00 | 58.66 | 10-FEB-19:55 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.09 | 01-MAR-13:00 | 59.17 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.07 | 28-APR-13:20 | 24.59 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.37 | 21-MAY-13:00 | 12.19 | 01-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.29 | 09-JUN-16:00 | 6.94 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.58 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.85 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.97 | 14-SEP-13:00 | 4.94 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.98 | 19-OCT-15:00 | 16.63 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.78 | 19-NOV-14:00 | 23.82 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 10-DEC-13:00 | 65.08 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 350.37 | 65.08 |
Report: PeakSpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 | 23-JAN-13:05 | 31.50 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 05-FEB-15:00 | 35.86 | 10-FEB-19:55 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.58 | 01-MAR-13:00 | 34.80 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.65 | 28-APR-13:20 | 14.83 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.33 | 21-MAY-13:00 | 6.78 | 01-MAY-07:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 09-JUN-16:00 | 3.87 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.65 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.96 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.54 | 14-SEP-13:00 | 2.82 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.36 | 19-OCT-15:00 | 9.68 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 19-NOV-14:00 | 14.39 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 | 10-DEC-13:00 | 39.36 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 211.33 | 39.36 |
Report: PeakSpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 23-JAN-13:05 | 31.50 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 05-FEB-15:00 | 35.85 | 10-FEB-19:55 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.58 | 01-MAR-13:00 | 34.85 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.65 | 28-APR-13:20 | 14.83 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.33 | 21-MAY-13:00 | 6.78 | 01-MAY-07:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 09-JUN-16:00 | 3.87 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.65 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.96 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.54 | 14-SEP-13:00 | 2.82 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.36 | 19-OCT-15:00 | 9.68 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 19-NOV-14:00 | 14.39 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 | 10-DEC-13:00 | 39.37 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 211.33 | 39.37 |
Report: PeakSpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 29-JAN-12:00 | 31.50 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 05-FEB-15:00 | 35.58 | 10-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.58 | 01-MAR-13:00 | 36.69 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.65 | 28-APR-13:20 | 14.83 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.33 | 21-MAY-13:00 | 6.76 | 01-MAY-07:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 09-JUN-16:00 | 3.78 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.65 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.96 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.54 | 14-SEP-13:00 | 2.95 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.36 | 19-OCT-15:00 | 10.17 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 19-NOV-14:00 | 14.70 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 | 10-DEC-13:00 | 45.36 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 211.33 | 45.36 |
Report: PeakSpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 29-JAN-12:00 | 31.50 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 05-FEB-15:00 | 35.82 | 10-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.58 | 01-MAR-13:00 | 37.75 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.65 | 28-APR-13:20 | 14.83 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.33 | 21-MAY-13:00 | 7.55 | 01-MAY-07:20 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 09-JUN-16:00 | 3.88 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.65 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.96 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.54 | 14-SEP-13:00 | 3.27 | 25-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.36 | 19-OCT-15:00 | 10.54 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 19-NOV-14:00 | 14.92 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 | 10-DEC-13:00 | 45.74 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 211.33 | 45.74 |
Report: PeakSpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | 29-JAN-12:00 | 75.20 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.81 | 05-FEB-15:00 | 84.78 | 10-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.45 | 01-MAR-13:00 | 77.32 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.31 | 28-APR-13:20 | 35.44 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 502.79 | 21-MAY-13:00 | 15.42 | 01-MAY-07:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.75 | 09-JUN-16:00 | 8.92 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.64 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.23 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.69 | 14-SEP-13:00 | 6.11 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.97 | 19-OCT-15:00 | 18.92 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.80 | 19-NOV-14:00 | 32.13 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.76 | 10-DEC-13:00 | 87.44 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 502.79 | 87.44 |
Report: PeakSpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 | 23-JAN-13:05 | 75.20 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.81 | 05-FEB-15:00 | 84.53 | 10-FEB-19:55 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.45 | 01-MAR-13:00 | 73.70 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.31 | 28-APR-13:20 | 35.44 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 502.79 | 21-MAY-13:00 | 15.55 | 01-MAY-07:20 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.75 | 09-JUN-16:00 | 9.14 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.64 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.23 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.69 | 14-SEP-13:00 | 5.89 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.97 | 19-OCT-15:00 | 18.60 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.80 | 19-NOV-14:00 | 31.67 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.76 | 10-DEC-13:00 | 86.26 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 502.79 | 86.26 |
Report: PeakSpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | 29-JAN-12:00 | 75.20 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.81 | 05-FEB-15:00 | 82.63 | 10-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.45 | 01-MAR-13:00 | 83.57 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.31 | 28-APR-13:20 | 35.44 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 502.79 | 21-MAY-13:00 | 15.85 | 01-MAY-07:20 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.75 | 09-JUN-16:00 | 9.37 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.64 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.23 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.69 | 14-SEP-13:00 | 6.09 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.97 | 19-OCT-15:00 | 19.50 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.80 | 19-NOV-14:00 | 32.27 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.76 | 10-DEC-13:00 | 87.68 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 502.79 | 87.68 |
Report: PeakSpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.19 | 23-JAN-13:05 | 75.20 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.81 | 05-FEB-15:00 | 83.38 | 10-FEB-19:55 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.45 | 01-MAR-13:00 | 79.97 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.31 | 28-APR-13:20 | 35.44 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 502.79 | 21-MAY-13:00 | 16.47 | 01-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.75 | 09-JUN-16:00 | 9.58 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.64 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.23 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.69 | 14-SEP-13:00 | 5.87 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.97 | 19-OCT-15:00 | 19.15 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.80 | 19-NOV-14:00 | 31.81 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.76 | 10-DEC-13:00 | 86.53 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 30.19 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 502.79 | 86.53 |
Report: PeakSpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.35 | 23-JAN-13:05 | 45.36 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.93 | 05-FEB-15:00 | 43.95 | 10-FEB-19:55 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.34 | 01-MAR-13:00 | 46.32 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.97 | 28-APR-13:20 | 21.38 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.27 | 21-MAY-13:00 | 9.43 | 01-MAY-07:10 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.26 | 09-JUN-16:00 | 5.34 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.30 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.98 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.92 | 14-SEP-13:00 | 3.47 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.50 | 19-OCT-15:00 | 11.43 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.94 | 19-NOV-14:00 | 19.60 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 10-DEC-13:00 | 53.33 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 18.35 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 303.27 | 53.33 |
Report: PeakSpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 | 23-JAN-13:05 | 45.36 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.93 | 05-FEB-15:00 | 43.94 | 10-FEB-19:55 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.34 | 01-MAR-13:00 | 46.40 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.97 | 28-APR-13:20 | 21.38 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.27 | 21-MAY-13:00 | 9.43 | 01-MAY-07:10 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.26 | 09-JUN-16:00 | 5.34 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.30 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.98 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.92 | 14-SEP-13:00 | 3.47 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.50 | 19-OCT-15:00 | 11.43 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.94 | 19-NOV-14:00 | 19.60 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 10-DEC-13:00 | 53.35 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 303.27 | 53.35 |
Report: PeakSpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 29-JAN-12:00 | 45.36 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.93 | 05-FEB-15:00 | 51.09 | 10-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.34 | 01-MAR-13:00 | 48.63 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.97 | 28-APR-13:20 | 21.38 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.27 | 21-MAY-13:00 | 9.34 | 01-MAY-07:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.26 | 09-JUN-16:00 | 5.20 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.30 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.98 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.92 | 14-SEP-13:00 | 3.61 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.50 | 19-OCT-15:00 | 11.71 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.94 | 19-NOV-14:00 | 19.89 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 10-DEC-13:00 | 54.10 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 303.27 | 54.10 |
Report: PeakSpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 29-JAN-12:00 | 45.36 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.93 | 05-FEB-15:00 | 51.08 | 10-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.34 | 01-MAR-13:00 | 48.71 | 25-MAR-08:50 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.97 | 28-APR-13:20 | 21.38 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.27 | 21-MAY-13:00 | 9.34 | 01-MAY-07:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.26 | 09-JUN-16:00 | 5.21 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.30 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.98 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.92 | 14-SEP-13:00 | 3.61 | 25-SEP-05:30 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.50 | 19-OCT-15:00 | 11.71 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.94 | 19-NOV-14:00 | 19.89 | 22-NOV-07:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 10-DEC-13:00 | 54.11 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 303.27 | 54.11 |
Report: PeakSpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.60 | 29-JAN-12:00 | 94.84 | 19-JAN-09:50 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.41 | 05-FEB-15:00 | 120.43 | 10-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.04 | 01-MAR-13:00 | 93.31 | 02-MAR-14:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.37 | 28-APR-13:20 | 47.19 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.20 | 21-MAY-13:00 | 19.05 | 01-MAY-07:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.38 | 09-JUN-16:00 | 11.91 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.45 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.02 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.99 | 14-SEP-13:00 | 7.46 | 25-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.49 | 19-OCT-15:00 | 22.06 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.90 | 19-NOV-14:00 | 40.23 | 22-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 10-DEC-13:00 | 105.35 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 38.60 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 663.20 | 120.43 |
Report: PeakSpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.30 | 23-JAN-13:05 | 92.71 | 18-JAN-04:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.41 | 05-FEB-15:00 | 122.26 | 10-FEB-18:12 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.04 | 01-MAR-13:00 | 90.95 | 02-MAR-14:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.37 | 28-APR-13:20 | 47.12 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.20 | 21-MAY-13:00 | 19.55 | 01-MAY-07:20 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.38 | 09-JUN-16:00 | 12.30 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.45 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.02 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.99 | 14-SEP-13:00 | 7.32 | 25-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.49 | 19-OCT-15:00 | 21.86 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.90 | 19-NOV-14:00 | 39.60 | 22-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 10-DEC-13:00 | 104.97 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 39.30 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 663.20 | 122.26 |
Report: PeakSpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.60 | 29-JAN-12:00 | 99.55 | 19-JAN-09:40 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.41 | 05-FEB-15:00 | 114.04 | 10-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.04 | 01-MAR-13:00 | 93.63 | 02-MAR-14:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.37 | 28-APR-13:20 | 47.15 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.20 | 21-MAY-13:00 | 20.19 | 01-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.38 | 09-JUN-16:00 | 12.77 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.45 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.02 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.99 | 14-SEP-13:00 | 7.44 | 25-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.49 | 19-OCT-15:00 | 23.06 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.90 | 19-NOV-14:00 | 40.10 | 22-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 10-DEC-13:00 | 105.62 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 38.60 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 663.20 | 114.04 |
Report: PeakSpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.66 | 23-JAN-13:05 | 92.71 | 18-JAN-04:00 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.41 | 05-FEB-15:00 | 116.05 | 10-FEB-19:03 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.04 | 01-MAR-13:00 | 91.27 | 02-MAR-14:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.37 | 28-APR-13:20 | 46.95 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.20 | 21-MAY-13:00 | 21.41 | 01-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.38 | 09-JUN-16:00 | 13.27 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.45 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.02 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.99 | 14-SEP-13:00 | 7.30 | 25-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.49 | 19-OCT-15:00 | 22.88 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.90 | 19-NOV-14:00 | 39.45 | 22-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 10-DEC-13:00 | 105.27 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 39.66 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 663.20 | 116.05 |
Report: PeakSpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 | 23-JAN-13:05 | 57.62 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.77 | 05-FEB-15:00 | 72.42 | 10-FEB-19:55 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.44 | 01-MAR-13:00 | 52.49 | 02-MAR-14:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.99 | 28-APR-13:20 | 28.44 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 400.02 | 21-MAY-13:00 | 12.18 | 01-MAY-07:20 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.44 | 09-JUN-16:00 | 7.26 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.06 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.87 | 14-SEP-13:00 | 4.49 | 25-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.19 | 19-OCT-15:00 | 14.05 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.69 | 19-NOV-14:00 | 25.02 | 22-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.55 | 10-DEC-13:00 | 65.69 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 400.02 | 72.42 |
Report: PeakSpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | 23-JAN-13:05 | 57.67 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.77 | 05-FEB-15:00 | 72.27 | 10-FEB-19:55 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.44 | 01-MAR-13:00 | 52.50 | 02-MAR-14:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.99 | 28-APR-13:20 | 28.44 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 400.02 | 21-MAY-13:00 | 12.19 | 01-MAY-07:20 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.44 | 09-JUN-16:00 | 7.26 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.06 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.87 | 14-SEP-13:00 | 4.49 | 25-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.19 | 19-OCT-15:00 | 14.05 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.69 | 19-NOV-14:00 | 25.02 | 22-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.55 | 10-DEC-13:00 | 65.71 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 400.02 | 72.27 |
Report: PeakSpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 | 29-JAN-12:00 | 60.24 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.77 | 05-FEB-15:00 | 70.86 | 10-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.44 | 01-MAR-13:00 | 53.96 | 02-MAR-14:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.99 | 28-APR-13:20 | 28.44 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 400.02 | 21-MAY-13:00 | 11.84 | 01-MAY-07:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.44 | 09-JUN-16:00 | 7.01 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.06 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.87 | 14-SEP-13:00 | 4.59 | 25-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.19 | 19-OCT-15:00 | 14.12 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.69 | 19-NOV-14:00 | 25.02 | 22-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.55 | 10-DEC-13:00 | 65.96 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 400.02 | 70.86 |
Report: PeakSpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 87.71 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 | 29-JAN-12:00 | 60.24 | 19-JAN-09:30 |
| February | 237.50 | 01-FEB-00:10 | 87.71 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.77 | 05-FEB-15:00 | 70.74 | 10-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 87.71 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.44 | 01-MAR-13:00 | 53.97 | 02-MAR-14:00 |
| April | 237.50 | 01-APR-00:10 | 87.71 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.99 | 28-APR-13:20 | 28.44 | 05-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 87.71 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 400.02 | 21-MAY-13:00 | 11.85 | 01-MAY-07:00 |
| June | 237.50 | 01-JUN-00:10 | 87.71 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.44 | 09-JUN-16:00 | 7.02 | 22-JUN-08:00 |
| July | 237.50 | 01-JUL-00:10 | 87.71 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 237.50 | 01-AUG-00:10 | 87.71 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.06 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 237.50 | 01-SEP-00:10 | 87.71 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.87 | 14-SEP-13:00 | 4.59 | 25-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 87.71 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.19 | 19-OCT-15:00 | 14.12 | 21-OCT-07:00 |
| November | 237.50 | 01-NOV-00:10 | 87.71 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.69 | 19-NOV-14:00 | 25.02 | 22-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 87.71 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.55 | 10-DEC-13:00 | 65.97 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 | 0.00 | |||||
| Maximum of Months | 237.50 | 87.71 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 400.02 | 70.74 |
Report: PeakSpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 23-JAN-13:02 | 19.42 | 18-JAN-04:00 |
| February | 397.10 | 01-FEB-00:10 | 307.95 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 05-FEB-15:00 | 21.08 | 10-FEB-19:55 |
| March | 397.10 | 01-MAR-00:10 | 307.95 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | 27-MAR-11:00 | 20.60 | 25-MAR-08:50 |
| April | 397.10 | 01-APR-00:10 | 307.95 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 | 28-APR-13:00 | 9.97 | 05-APR-01:00 |
| May | 397.10 | 01-MAY-00:10 | 307.95 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.56 | 21-MAY-13:00 | 3.91 | 01-MAY-07:00 |
| June | 397.10 | 01-JUN-00:10 | 307.95 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.03 | 09-JUN-15:00 | 2.45 | 22-JUN-07:53 |
| July | 397.10 | 01-JUL-00:10 | 307.95 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.96 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 397.10 | 01-AUG-00:10 | 307.95 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 397.10 | 01-SEP-00:10 | 307.95 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.88 | 14-SEP-13:00 | 1.88 | 25-SEP-05:00 |
| October | 397.10 | 01-OCT-00:10 | 307.95 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.13 | 19-OCT-15:00 | 4.59 | 21-OCT-07:00 |
| November | 397.10 | 01-NOV-00:10 | 307.95 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 19-NOV-14:00 | 7.95 | 22-NOV-06:25 |
| December | 397.10 | 01-DEC-00:10 | 307.95 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 10-DEC-12:00 | 22.48 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 0.00 | ||||
| Maximum of Months | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.56 | 22.48 |
Report: PeakSpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 | 190.19 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.36 | 28-JAN-14:00 | 7806.84 | 19-JAN-07:01 |
| February | 397.10 | 01-FEB-00:10 | 307.95 | 01-FEB-00:10 | 190.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.30 | 05-FEB-17:03 | 7179.05 | 01-FEB-07:01 |
| March | 397.10 | 01-MAR-00:10 | 307.95 | 01-MAR-00:10 | 190.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3336.37 | 27-MAR-16:02 | 6210.71 | 07-MAR-07:01 |
| April | 397.10 | 01-APR-00:10 | 307.95 | 01-APR-00:10 | 190.19 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3530.06 | 27-APR-16:02 | 5004.29 | 05-APR-06:01 |
| May | 397.10 | 01-MAY-00:10 | 307.95 | 01-MAY-00:10 | 190.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4966.34 | 30-MAY-16:01 | 3678.35 | 01-MAY-06:01 |
| June | 397.10 | 01-JUN-00:10 | 307.95 | 01-JUN-00:10 | 190.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6096.96 | 09-JUN-16:01 | 1888.90 | 07-JUN-06:01 |
| July | 397.10 | 01-JUL-00:10 | 307.95 | 01-JUL-00:10 | 190.19 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6398.74 | 03-JUL-16:01 | 86.90 | 03-JUL-06:10 |
| August | 397.10 | 01-AUG-00:10 | 307.95 | 01-AUG-00:10 | 190.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6008.08 | 10-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 397.10 | 01-SEP-00:10 | 307.95 | 01-SEP-00:10 | 190.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5586.04 | 04-SEP-16:01 | 2495.03 | 25-SEP-06:01 |
| October | 397.10 | 01-OCT-00:10 | 307.95 | 01-OCT-00:10 | 190.19 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3810.11 | 09-OCT-16:02 | 3541.89 | 29-OCT-06:02 |
| November | 397.10 | 01-NOV-00:10 | 307.95 | 01-NOV-00:10 | 190.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1852.91 | 01-NOV-16:02 | 5238.80 | 22-NOV-07:01 |
| December | 397.10 | 01-DEC-00:10 | 307.95 | 01-DEC-00:10 | 190.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.03 | 10-DEC-12:00 | 7233.10 | 31-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 397.10 | 307.95 | 190.19 | 0.00 | 0.00 | 0.00 | 0.00 | 65.36 | 0.00 | |||||
| Maximum of Months | 397.10 | 307.95 | 190.19 | 0.00 | 0.00 | 0.00 | 0.00 | 6398.74 | 7806.84 |
Report: PeakSpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 307.95 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 | 23-JAN-14:00 | 15.98 | 18-JAN-04:00 |
| February | 397.10 | 01-FEB-00:10 | 307.95 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 | 05-FEB-15:00 | 15.34 | 10-FEB-19:55 |
| March | 397.10 | 01-MAR-00:10 | 307.95 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 | 27-MAR-11:00 | 21.30 | 25-MAR-09:00 |
| April | 397.10 | 01-APR-00:10 | 307.95 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.56 | 28-APR-13:00 | 7.94 | 05-APR-01:00 |
| May | 397.10 | 01-MAY-00:10 | 307.95 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.46 | 21-MAY-13:00 | 3.22 | 01-MAY-07:10 |
| June | 397.10 | 01-JUN-00:10 | 307.95 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.37 | 09-JUN-15:10 | 1.99 | 07-JUN-06:00 |
| July | 397.10 | 01-JUL-00:10 | 307.95 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.84 | 14-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 397.10 | 01-AUG-00:10 | 307.95 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.94 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 397.10 | 01-SEP-00:10 | 307.95 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 | 14-SEP-13:00 | 1.53 | 25-SEP-05:00 |
| October | 397.10 | 01-OCT-00:10 | 307.95 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.99 | 19-OCT-15:00 | 4.02 | 21-OCT-07:00 |
| November | 397.10 | 01-NOV-00:10 | 307.95 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 | 19-NOV-14:00 | 6.73 | 22-NOV-07:00 |
| December | 397.10 | 01-DEC-00:10 | 307.95 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.92 | 10-DEC-13:00 | 18.37 | 15-DEC-12:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 | 0.00 | ||||
| Maximum of Months | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.46 | 21.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6609.70 | 26-JAN-16:42 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 |
| February | 6618.03 | 11-FEB-17:02 | 1425.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.27 |
| March | 6575.84 | 07-MAR-15:42 | 0.00 | 115.13 | 2401.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 |
| April | 6412.63 | 06-APR-08:22 | 0.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 | 0.00 |
| May | 5863.35 | 15-MAY-07:42 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 0.00 |
| June | 5146.59 | 22-JUN-09:02 | 0.00 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 0.00 |
| July | 2671.50 | 21-JUL-17:01 | 1662.50 | 518.07 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 111.94 | 0.00 |
| August | 2777.07 | 10-AUG-16:01 | 0.00 | 493.39 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 108.89 | 0.00 |
| September | 5261.52 | 30-SEP-06:52 | 1425.00 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 0.00 |
| October | 6356.22 | 20-OCT-07:32 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
| November | 6287.63 | 21-NOV-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 |
| December | 6613.23 | 16-DEC-13:52 | 712.50 | 65.78 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.44 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2671.50 | 0.00 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6618.03 | 1662.50 | 518.07 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 111.94 | 28.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6405.56 | 05-JAN-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 |
| February | 6411.68 | 12-FEB-17:12 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 |
| March | 6374.04 | 06-MAR-19:32 | 1239.75 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.95 |
| April | 6234.63 | 06-APR-08:22 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8.59 | 0.00 |
| May | 5692.06 | 15-MAY-07:32 | 555.75 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | 0.00 |
| June | 4993.78 | 22-JUN-09:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.66 | 0.00 |
| July | 2700.67 | 21-JUL-17:01 | 1446.38 | 518.07 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 111.94 | 0.00 |
| August | 2743.70 | 05-AUG-17:01 | 1446.38 | 518.07 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 77.58 | 0.00 |
| September | 5086.81 | 30-SEP-06:52 | 1211.25 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 0.00 |
| October | 6201.68 | 21-OCT-08:42 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 | 0.00 |
| November | 6100.40 | 21-NOV-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 |
| December | 6410.60 | 16-DEC-18:42 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2700.67 | 356.25 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6411.68 | 1446.38 | 526.29 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 111.94 | 27.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 7868.22 | 04-JAN-07:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.97 |
| February | 7907.74 | 13-FEB-07:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.04 |
| March | 7795.59 | 07-MAR-07:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 |
| April | 7931.41 | 24-APR-06:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 |
| May | 7899.35 | 08-MAY-06:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 |
| June | 7724.19 | 02-JUN-06:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
| July | 7719.30 | 03-JUL-06:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
| August | 6487.99 | 07-AUG-06:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 | 0.00 |
| September | 6909.15 | 26-SEP-06:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 |
| October | 8003.81 | 20-OCT-06:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 |
| November | 7690.96 | 21-NOV-07:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 |
| December | 7969.66 | 18-DEC-07:01 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 6487.99 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8003.81 | 0.00 | 895.25 | 1949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 | 32.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6179.92 | 05-JAN-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 |
| February | 6176.57 | 12-FEB-17:12 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.90 |
| March | 6141.47 | 05-MAR-14:22 | 356.25 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 |
| April | 6026.08 | 06-APR-08:22 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 7.44 | 0.00 |
| May | 5487.58 | 15-MAY-07:32 | 555.75 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 0.00 |
| June | 4861.82 | 22-JUN-09:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.59 | 0.00 |
| July | 2537.10 | 21-JUL-17:01 | 1446.38 | 518.07 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 111.94 | 0.00 |
| August | 2567.06 | 05-AUG-17:01 | 1446.38 | 518.07 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 77.58 | 0.00 |
| September | 4905.10 | 30-SEP-06:52 | 1211.25 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 0.00 |
| October | 5990.65 | 21-OCT-08:42 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 13.52 | 0.00 |
| November | 5879.63 | 21-NOV-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 |
| December | 6176.05 | 16-DEC-18:42 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.64 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2537.10 | 356.25 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6179.92 | 1446.38 | 518.07 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 111.94 | 28.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5462.41 | 15-JAN-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 |
| February | 5454.97 | 11-FEB-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 |
| March | 5427.56 | 07-MAR-20:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 |
| April | 5302.37 | 06-APR-08:22 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 | 0.00 |
| May | 4812.44 | 15-MAY-07:32 | 555.75 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 0.00 |
| June | 4166.86 | 22-JUN-09:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.68 | 0.00 |
| July | 1941.93 | 21-JUL-17:16 | 1033.12 | 370.05 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 65.09 | 0.00 |
| August | 1965.89 | 05-AUG-17:17 | 826.50 | 296.04 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 46.36 | 0.00 |
| September | 4211.33 | 30-SEP-06:52 | 1211.25 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 0.00 |
| October | 5269.16 | 21-OCT-08:42 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 7.75 | 0.00 |
| November | 5165.25 | 21-NOV-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 |
| December | 5449.16 | 16-DEC-18:42 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1941.93 | 356.25 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5462.41 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 65.09 | 17.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5457.97 | 15-JAN-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 |
| February | 5450.34 | 12-FEB-17:12 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 |
| March | 5422.11 | 07-MAR-20:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 |
| April | 5298.14 | 06-APR-08:22 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 | 0.00 |
| May | 4808.20 | 15-MAY-07:32 | 555.75 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 0.00 |
| June | 4163.97 | 22-JUN-09:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.68 | 0.00 |
| July | 1939.36 | 21-JUL-17:12 | 1033.12 | 370.05 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 65.09 | 0.00 |
| August | 1964.03 | 05-AUG-17:17 | 826.50 | 296.04 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 46.36 | 0.00 |
| September | 4207.60 | 30-SEP-06:52 | 1211.25 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 0.00 |
| October | 5265.16 | 21-OCT-08:42 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 7.75 | 0.00 |
| November | 5160.34 | 21-NOV-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 |
| December | 5444.75 | 16-DEC-18:42 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1939.36 | 356.25 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5457.97 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 65.09 | 17.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5690.34 | 15-JAN-22:32 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 |
| February | 5670.60 | 11-FEB-15:52 | 0.00 | 115.13 | 2401.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 |
| March | 5655.76 | 07-MAR-20:22 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 |
| April | 5512.19 | 06-APR-08:22 | 0.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 | 0.00 |
| May | 5010.91 | 15-MAY-07:42 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 0.00 |
| June | 4341.78 | 22-JUN-09:02 | 0.00 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 0.00 |
| July | 1917.23 | 21-JUL-17:12 | 1187.50 | 370.05 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 65.09 | 0.00 |
| August | 1996.31 | 05-AUG-17:01 | 1662.50 | 518.07 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 46.80 | 0.00 |
| September | 4460.70 | 30-SEP-06:52 | 1425.00 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 0.00 |
| October | 5445.71 | 20-OCT-07:32 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
| November | 5391.14 | 21-NOV-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 |
| December | 5676.41 | 19-DEC-19:02 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1917.23 | 0.00 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5690.34 | 1662.50 | 526.29 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 65.09 | 16.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5731.95 | 15-JAN-22:32 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 |
| February | 5714.55 | 11-FEB-15:52 | 0.00 | 115.13 | 2401.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 |
| March | 5695.79 | 07-MAR-20:22 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 |
| April | 5553.79 | 06-APR-08:22 | 0.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 0.00 |
| May | 5095.14 | 15-MAY-07:42 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 0.00 |
| June | 4427.11 | 22-JUN-09:02 | 0.00 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 | 0.00 |
| July | 2024.54 | 30-JUL-16:02 | 1425.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 60.32 | 0.00 |
| August | 2158.28 | 06-AUG-17:02 | 1425.00 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 39.11 | 0.00 |
| September | 4548.87 | 30-SEP-06:52 | 1425.00 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 0.00 |
| October | 5491.03 | 20-OCT-07:32 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
| November | 5438.45 | 21-NOV-22:52 | 1425.00 | 197.37 | 2507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 |
| December | 5720.14 | 19-DEC-19:02 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2024.54 | 0.00 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5731.95 | 1425.00 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 60.32 | 16.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6876.65 | 26-JAN-16:42 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.58 |
| February | 6899.22 | 11-FEB-17:02 | 1425.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.74 |
| March | 6857.43 | 07-MAR-15:42 | 0.00 | 115.13 | 2401.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.36 |
| April | 6661.81 | 06-APR-08:22 | 0.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 | 0.00 |
| May | 6095.75 | 15-MAY-07:42 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 | 0.00 |
| June | 5269.45 | 22-JUN-09:02 | 0.00 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 0.00 |
| July | 2740.28 | 21-JUL-16:30 | 0.00 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 161.15 | 0.00 |
| August | 2758.63 | 10-AUG-16:01 | 0.00 | 493.39 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 156.30 | 0.00 |
| September | 5176.66 | 30-SEP-06:52 | 1425.00 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 0.00 |
| October | 6644.50 | 21-OCT-08:42 | 1425.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 | 0.00 |
| November | 6486.40 | 22-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
| December | 6880.07 | 27-DEC-17:12 | 0.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2740.28 | 0.00 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6899.22 | 1425.00 | 493.39 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 161.15 | 40.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6655.20 | 05-JAN-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.19 |
| February | 6657.48 | 11-FEB-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.55 |
| March | 6632.35 | 04-MAR-21:52 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 |
| April | 6467.53 | 06-APR-08:22 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 0.00 |
| May | 5885.89 | 15-MAY-07:32 | 555.75 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 0.00 |
| June | 5106.52 | 22-JUN-09:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.19 | 0.00 |
| July | 2762.58 | 21-JUL-16:30 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 161.15 | 0.00 |
| August | 2676.52 | 10-AUG-16:01 | 1111.50 | 493.39 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 156.30 | 0.00 |
| September | 4978.81 | 30-SEP-06:52 | 1211.25 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 0.00 |
| October | 6409.38 | 21-OCT-08:42 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 20.44 | 0.00 |
| November | 6191.71 | 18-NOV-10:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 | 0.00 |
| December | 6643.16 | 18-DEC-19:22 | 1239.75 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.31 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2676.52 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6657.48 | 1425.00 | 526.29 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 161.15 | 37.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6597.95 | 26-JAN-17:52 | 0.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.99 |
| February | 6616.77 | 11-FEB-17:02 | 1425.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.94 |
| March | 6575.55 | 07-MAR-20:22 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 |
| April | 6419.05 | 06-APR-08:22 | 0.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 0.00 |
| May | 5863.51 | 15-MAY-07:42 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | 0.00 |
| June | 5127.06 | 22-JUN-09:02 | 0.00 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.15 | 0.00 |
| July | 2532.23 | 21-JUL-16:01 | 0.00 | 548.21 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 157.59 | 0.00 |
| August | 2574.31 | 16-AUG-12:00 | 0.00 | 10.96 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 202.23 | 0.00 |
| September | 4979.03 | 30-SEP-06:52 | 1425.00 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 | 0.00 |
| October | 6391.36 | 21-OCT-08:42 | 1425.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 | 0.00 |
| November | 6224.39 | 22-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 |
| December | 6598.19 | 27-DEC-17:12 | 0.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2532.23 | 0.00 | 10.96 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6616.77 | 1425.00 | 548.21 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 202.23 | 40.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6369.26 | 05-JAN-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.38 |
| February | 6381.18 | 12-FEB-17:12 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.42 |
| March | 6367.61 | 07-MAR-20:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 |
| April | 6220.88 | 06-APR-08:22 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 0.00 |
| May | 5669.08 | 15-MAY-07:32 | 555.75 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 0.00 |
| June | 4969.72 | 22-JUN-09:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.01 | 0.00 |
| July | 2546.75 | 21-JUL-16:30 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 161.15 | 0.00 |
| August | 2470.29 | 05-AUG-11:40 | 59.38 | 10.96 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 190.73 | 0.00 |
| September | 4779.95 | 30-SEP-06:52 | 1211.25 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 0.00 |
| October | 6168.90 | 21-OCT-08:42 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 18.92 | 0.00 |
| November | 6017.70 | 18-NOV-10:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 0.00 |
| December | 6354.47 | 19-DEC-16:52 | 427.50 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2470.29 | 59.38 | 10.96 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6381.18 | 1239.75 | 526.29 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 190.73 | 31.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5607.04 | 05-JAN-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.28 |
| February | 5622.54 | 12-FEB-17:12 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 |
| March | 5598.54 | 07-MAR-20:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 |
| April | 5447.55 | 06-APR-08:22 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 |
| May | 4910.88 | 15-MAY-07:32 | 555.75 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 | 0.00 |
| June | 4222.59 | 22-JUN-09:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 0.00 |
| July | 1865.32 | 21-JUL-17:01 | 1446.38 | 518.07 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 96.93 | 0.00 |
| August | 1792.90 | 05-AUG-17:17 | 826.50 | 296.04 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 66.54 | 0.00 |
| September | 4132.85 | 30-SEP-06:52 | 1211.25 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
| October | 5393.33 | 21-OCT-08:42 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 | 0.00 |
| November | 5207.21 | 18-NOV-10:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 0.00 |
| December | 5602.21 | 16-DEC-18:42 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.54 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1792.90 | 356.25 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5622.54 | 1446.38 | 526.29 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 96.93 | 24.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5601.28 | 05-JAN-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.28 |
| February | 5616.48 | 12-FEB-17:12 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 |
| March | 5593.30 | 07-MAR-20:52 | 1239.75 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 |
| April | 5442.77 | 06-APR-08:22 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 |
| May | 4906.25 | 15-MAY-07:32 | 555.75 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 |
| June | 4219.08 | 22-JUN-09:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.77 | 0.00 |
| July | 1862.82 | 21-JUL-17:01 | 1446.38 | 518.07 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 96.93 | 0.00 |
| August | 1790.59 | 05-AUG-17:17 | 826.50 | 296.04 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 66.54 | 0.00 |
| September | 4128.65 | 30-SEP-06:52 | 1211.25 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
| October | 5388.69 | 21-OCT-08:42 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 | 0.00 |
| November | 5204.32 | 18-NOV-10:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 | 0.00 |
| December | 5596.39 | 16-DEC-18:42 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1790.59 | 356.25 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5616.48 | 1446.38 | 526.29 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 96.93 | 24.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5862.41 | 26-JAN-17:52 | 0.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 |
| February | 5873.19 | 11-FEB-17:02 | 1425.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 |
| March | 5843.64 | 07-MAR-20:22 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 |
| April | 5675.92 | 06-APR-08:22 | 0.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 |
| May | 5152.56 | 15-MAY-07:42 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 0.00 |
| June | 4402.66 | 22-JUN-09:02 | 0.00 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.85 | 0.00 |
| July | 1838.01 | 21-JUL-17:12 | 1187.50 | 370.05 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 93.44 | 0.00 |
| August | 1857.76 | 05-AUG-16:01 | 1900.00 | 438.57 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 75.93 | 0.00 |
| September | 4358.58 | 30-SEP-06:52 | 1425.00 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 0.00 |
| October | 5654.98 | 21-OCT-08:42 | 1425.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.13 | 0.00 |
| November | 5527.58 | 22-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 |
| December | 5858.03 | 27-DEC-17:12 | 0.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1838.01 | 0.00 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5873.19 | 1900.00 | 526.29 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 93.44 | 25.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5857.77 | 26-JAN-17:52 | 0.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 |
| February | 5869.02 | 11-FEB-17:02 | 1425.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 |
| March | 5838.84 | 07-MAR-20:22 | 1425.00 | 526.29 | 3143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 |
| April | 5671.98 | 06-APR-08:22 | 0.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 |
| May | 5155.42 | 15-MAY-07:42 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 0.00 |
| June | 4405.68 | 22-JUN-09:02 | 0.00 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.85 | 0.00 |
| July | 1835.47 | 21-JUL-17:16 | 1187.50 | 370.05 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 93.44 | 0.00 |
| August | 1856.97 | 05-AUG-16:01 | 1900.00 | 438.57 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 75.93 | 0.00 |
| September | 4358.79 | 30-SEP-06:52 | 1425.00 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 0.00 |
| October | 5650.57 | 21-OCT-08:42 | 1425.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.13 | 0.00 |
| November | 5522.20 | 22-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
| December | 5855.66 | 19-DEC-19:02 | 1425.00 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.27 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1835.47 | 0.00 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5869.02 | 1900.00 | 526.29 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 93.44 | 25.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 7447.82 | 07-JAN-16:32 | 1425.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.20 |
| February | 7615.53 | 27-FEB-16:02 | 0.00 | 191.87 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.28 |
| March | 7466.76 | 07-MAR-15:22 | 0.00 | 115.13 | 2401.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 |
| April | 7173.60 | 06-APR-08:22 | 0.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 | 0.00 |
| May | 6525.83 | 15-MAY-07:42 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 0.00 |
| June | 5638.86 | 22-JUN-09:02 | 0.00 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.39 | 0.00 |
| July | 3545.63 | 21-JUL-16:17 | 0.00 | 219.28 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 210.35 | 0.00 |
| August | 3568.93 | 10-AUG-16:01 | 0.00 | 493.39 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 206.28 | 0.00 |
| September | 5388.36 | 30-SEP-06:52 | 1425.00 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 0.00 |
| October | 7160.54 | 21-OCT-08:42 | 1425.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 26.08 | 0.00 |
| November | 6963.28 | 22-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 |
| December | 7456.31 | 27-DEC-16:02 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.58 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3545.63 | 0.00 | 65.78 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 7615.53 | 1425.00 | 493.39 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 210.35 | 33.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 7219.13 | 05-JAN-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 |
| February | 7361.55 | 24-FEB-17:02 | 741.00 | 328.92 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.48 |
| March | 7222.51 | 07-MAR-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.68 |
| April | 7016.55 | 06-APR-08:22 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 0.00 |
| May | 6316.02 | 15-MAY-07:32 | 555.75 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 | 0.00 |
| June | 5520.84 | 22-JUN-09:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.21 | 0.00 |
| July | 3564.46 | 21-JUL-16:30 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 212.70 | 0.00 |
| August | 3460.19 | 10-AUG-16:01 | 1111.50 | 493.39 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 206.28 | 0.00 |
| September | 5246.11 | 30-SEP-06:52 | 1211.25 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | 0.00 |
| October | 6961.76 | 21-OCT-08:42 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.98 | 0.00 |
| November | 6694.53 | 18-NOV-10:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.12 | 0.00 |
| December | 7217.93 | 18-DEC-19:22 | 1239.75 | 526.29 | 3284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.92 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3460.19 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 7361.55 | 1239.75 | 526.29 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 212.70 | 65.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 7044.03 | 26-JAN-16:42 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 |
| February | 7180.83 | 27-FEB-16:02 | 0.00 | 191.87 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.74 |
| March | 7061.18 | 07-MAR-15:22 | 0.00 | 115.13 | 2401.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 |
| April | 6835.87 | 06-APR-08:22 | 0.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 | 0.00 |
| May | 6177.32 | 15-MAY-07:42 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 | 0.00 |
| June | 5470.11 | 22-JUN-09:02 | 0.00 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.99 | 0.00 |
| July | 3329.82 | 30-JUL-14:00 | 118.75 | 10.96 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 226.31 | 0.00 |
| August | 3389.72 | 16-AUG-12:00 | 0.00 | 10.96 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 267.02 | 0.00 |
| September | 5121.08 | 30-SEP-06:52 | 1425.00 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 0.00 |
| October | 6799.38 | 21-OCT-08:42 | 1425.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 | 0.00 |
| November | 6589.46 | 22-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
| December | 7061.53 | 27-DEC-16:02 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.94 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3329.82 | 0.00 | 10.96 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 7180.83 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 267.02 | 33.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6805.24 | 05-JAN-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 |
| February | 6844.03 | 11-FEB-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.72 |
| March | 6826.19 | 07-MAR-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.93 |
| April | 6678.39 | 06-APR-08:22 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 | 0.00 |
| May | 6007.18 | 15-MAY-07:32 | 555.75 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 | 0.00 |
| June | 5350.12 | 22-JUN-09:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.82 | 0.00 |
| July | 3260.70 | 21-JUL-16:17 | 494.00 | 219.28 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 210.35 | 0.00 |
| August | 3250.15 | 04-AUG-13:00 | 59.38 | 10.96 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 249.17 | 0.00 |
| September | 4977.87 | 30-SEP-06:52 | 1211.25 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 | 0.00 |
| October | 6617.42 | 21-OCT-08:42 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 0.00 |
| November | 6420.73 | 18-NOV-10:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 | 0.00 |
| December | 6815.05 | 16-DEC-18:42 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.72 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3250.15 | 59.38 | 10.96 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6844.03 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 249.17 | 51.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6166.37 | 05-JAN-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 |
| February | 6181.00 | 11-FEB-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.62 |
| March | 6156.55 | 04-MAR-21:52 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 |
| April | 6001.06 | 06-APR-08:22 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 0.00 |
| May | 5398.76 | 15-MAY-07:32 | 555.75 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 | 0.00 |
| June | 4654.43 | 22-JUN-09:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 22.19 | 0.00 |
| July | 2494.15 | 21-JUL-16:30 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 128.30 | 0.00 |
| August | 2385.76 | 10-AUG-16:01 | 1111.50 | 493.39 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 124.42 | 0.00 |
| September | 4476.47 | 30-SEP-06:52 | 1211.25 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 | 0.00 |
| October | 5947.98 | 21-OCT-08:42 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 0.00 |
| November | 5742.27 | 18-NOV-10:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 0.00 |
| December | 6148.56 | 19-DEC-16:52 | 427.50 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2385.76 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6181.00 | 1425.00 | 493.39 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 128.30 | 30.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6150.31 | 05-JAN-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 |
| February | 6167.23 | 11-FEB-18:12 | 1239.75 | 444.06 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.63 |
| March | 6143.18 | 04-MAR-21:52 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 |
| April | 5988.64 | 06-APR-08:22 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 0.00 |
| May | 5387.20 | 15-MAY-07:32 | 555.75 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1.93 | 0.00 |
| June | 4646.33 | 22-JUN-09:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 22.18 | 0.00 |
| July | 2488.83 | 21-JUL-16:30 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 128.30 | 0.00 |
| August | 2379.41 | 10-AUG-16:01 | 1111.50 | 493.39 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 124.42 | 0.00 |
| September | 4465.81 | 30-SEP-06:52 | 1211.25 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 | 0.00 |
| October | 5936.00 | 21-OCT-08:42 | 356.25 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 | 0.00 |
| November | 5736.75 | 18-NOV-10:02 | 356.25 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 0.00 |
| December | 6134.61 | 19-DEC-16:52 | 427.50 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.95 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2379.41 | 123.50 | 54.82 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6167.23 | 1425.00 | 493.39 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 128.30 | 30.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6392.93 | 26-JAN-16:42 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.49 |
| February | 6452.85 | 27-FEB-16:02 | 0.00 | 191.87 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 |
| March | 6391.84 | 07-MAR-15:22 | 0.00 | 115.13 | 2401.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 |
| April | 6174.27 | 06-APR-08:22 | 0.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 0.00 |
| May | 5604.31 | 15-MAY-07:42 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 | 0.00 |
| June | 4785.54 | 22-JUN-09:02 | 0.00 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 22.31 | 0.00 |
| July | 2482.84 | 21-JUL-16:01 | 0.00 | 548.21 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 125.46 | 0.00 |
| August | 2533.07 | 16-AUG-14:10 | 0.00 | 19.19 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 103.01 | 0.00 |
| September | 4636.09 | 30-SEP-06:52 | 1425.00 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
| October | 6155.57 | 21-OCT-08:42 | 1425.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 0.00 |
| November | 5991.24 | 22-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 |
| December | 6401.60 | 27-DEC-16:02 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2482.84 | 0.00 | 19.19 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6452.85 | 1425.00 | 548.21 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 125.46 | 21.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6379.55 | 26-JAN-16:42 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 |
| February | 6440.88 | 27-FEB-16:02 | 0.00 | 191.87 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 |
| March | 6378.87 | 07-MAR-15:22 | 0.00 | 115.13 | 2401.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.70 |
| April | 6162.07 | 06-APR-08:22 | 0.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 | 0.00 |
| May | 5589.03 | 15-MAY-07:42 | 0.00 | 98.68 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 | 0.00 |
| June | 4777.26 | 22-JUN-09:02 | 0.00 | 65.78 | 2436.90 | 0.00 | 0.00 | 0.00 | 0.00 | 22.30 | 0.00 |
| July | 2478.56 | 21-JUL-16:01 | 0.00 | 548.21 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 125.46 | 0.00 |
| August | 2536.56 | 16-AUG-14:10 | 0.00 | 19.19 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 103.01 | 0.00 |
| September | 4625.54 | 30-SEP-06:52 | 1425.00 | 213.79 | 2295.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
| October | 6142.85 | 21-OCT-08:42 | 1425.00 | 65.78 | 2366.26 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 0.00 |
| November | 5977.93 | 22-NOV-21:22 | 1425.00 | 361.83 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
| December | 6387.43 | 27-DEC-16:02 | 0.00 | 230.24 | 2825.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.07 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2478.56 | 0.00 | 19.19 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6440.88 | 1425.00 | 548.21 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 125.46 | 21.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 0.00 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 0.00 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 | 0.00 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.71 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 0.00 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 | 5.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 0.00 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 | 0.00 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 307.95 | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 | 3.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 0.00 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 0.00 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 0.00 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 0.00 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 307.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 4.17 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.646396E+11 | 53231.21 | 08-JAN-17:30 | 0.303282E+11 | 21361.32 | 13-JAN-07:00 |
| February | 0.629554E+11 | 50026.69 | 28-FEB-19:49 | 0.266514E+11 | 21260.12 | 01-FEB-07:49 |
| March | 0.768262E+11 | 52687.15 | 27-MAR-16:10 | 0.275721E+11 | 20791.99 | 01-MAR-07:40 |
| April | 0.853314E+11 | 55246.85 | 30-APR-16:19 | 0.241300E+11 | 18956.86 | 01-APR-06:49 |
| May | 0.105806E+12 | 62523.76 | 31-MAY-17:00 | 0.223357E+11 | 17167.79 | 01-MAY-06:00 |
| June | 0.112558E+12 | 65284.11 | 09-JUN-16:40 | 0.198384E+11 | 15360.76 | 01-JUN-06:19 |
| July | 0.126583E+12 | 67287.74 | 30-JUL-16:10 | 0.198991E+11 | 14317.34 | 31-JUL-06:19 |
| August | 0.129916E+12 | 71136.83 | 10-AUG-16:10 | 0.207198E+11 | 15648.79 | 31-AUG-06:49 |
| September | 0.114732E+12 | 64409.23 | 09-SEP-16:10 | 0.219942E+11 | 17259.18 | 30-SEP-06:40 |
| October | 0.104755E+12 | 60385.34 | 07-OCT-16:10 | 0.253709E+11 | 19079.08 | 31-OCT-06:49 |
| November | 0.860736E+11 | 55919.09 | 01-NOV-16:10 | 0.270476E+11 | 20900.51 | 30-NOV-07:00 |
| December | 0.715997E+11 | 52335.29 | 29-DEC-17:00 | 0.297668E+11 | 21321.72 | 31-DEC-07:30 |
| Annual Sum or Average | 0.114178E+13 | 0.295654E+12 | ||||
| Minimum of Months | 0.629554E+11 | 50026.69 | 0.198384E+11 | 14317.34 | ||
| Maximum of Months | 0.129916E+12 | 71136.83 | 0.303282E+11 | 21361.32 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 0.618562E+10 | 0.313264E+10 | 0.385428E+11 | 0.00 | 0.748533E+10 | 38818862.27 | 0.00 | 0.925438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.559770E+10 | 0.271789E+10 | 0.348258E+11 | 0.00 | 0.768527E+10 | 35062198.18 | 0.00 | 0.120936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.621989E+10 | 0.284648E+10 | 0.385844E+11 | 0.00 | 0.994375E+10 | 38818862.27 | 0.00 | 0.191929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.599345E+10 | 0.258175E+10 | 0.373085E+11 | 0.00 | 0.117637E+11 | 37566640.91 | 0.00 | 0.276465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.620847E+10 | 0.252880E+10 | 0.385705E+11 | 0.00 | 0.152854E+11 | 38818862.27 | 0.00 | 0.431742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.601630E+10 | 0.238257E+10 | 0.373361E+11 | 0.00 | 0.165062E+11 | 37566640.91 | 0.00 | 0.502794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.618562E+10 | 0.248594E+10 | 0.385428E+11 | 0.00 | 0.187352E+11 | 38818862.27 | 0.00 | 0.605948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.621989E+10 | 0.260570E+10 | 0.385844E+11 | 0.00 | 0.192261E+11 | 38818862.27 | 0.00 | 0.632407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.599345E+10 | 0.267881E+10 | 0.373085E+11 | 0.00 | 0.168457E+11 | 37566640.91 | 0.00 | 0.518675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.619704E+10 | 0.293976E+10 | 0.385567E+11 | 0.00 | 0.150735E+11 | 38818862.27 | 0.00 | 0.419493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.599345E+10 | 0.299271E+10 | 0.373085E+11 | 0.00 | 0.118199E+11 | 37566640.91 | 0.00 | 0.279215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.618562E+10 | 0.317676E+10 | 0.385428E+11 | 0.00 | 0.886884E+10 | 38818862.27 | 0.00 | 0.147868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.729965E+11 | 0.330698E+11 | 0.454012E+12 | 0.00 | 0.159239E+12 | 0.457061E+09 | 0.00 | 0.422002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.559770E+10 | 0.238257E+10 | 0.348258E+11 | 0.00 | 0.748533E+10 | 35062198.18 | 0.00 | 0.925438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.621989E+10 | 0.317676E+10 | 0.385844E+11 | 0.00 | 0.192261E+11 | 38818862.27 | 0.00 | 0.632407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.303282E+11 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.266514E+11 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.275721E+11 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.241300E+11 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.223357E+11 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.198384E+11 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.198991E+11 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.207198E+11 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.219942E+11 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.253709E+11 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.270476E+11 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.297668E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.295654E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.198384E+11 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.303282E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 4040.47 | 01-JAN-19:10 | 2101.03 | 01-JAN-00:10 | 22246.15 | 03-JAN-17:10 | 0.00 | 7410.82 | 07-JAN-16:00 | 14.49 | 01-JAN-06:10 | 0.00 | 01-JAN-00:10 |
| February | 4040.47 | 01-FEB-19:10 | 2101.03 | 01-FEB-00:10 | 22246.15 | 01-FEB-17:10 | 0.00 | 7650.17 | 28-FEB-13:09 | 14.49 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
| March | 4040.47 | 01-MAR-19:10 | 2101.03 | 01-MAR-00:10 | 22246.15 | 01-MAR-17:10 | 0.00 | 7969.42 | 29-MAR-09:50 | 14.49 | 01-MAR-06:19 | 0.00 | 01-MAR-00:10 |
| April | 4040.47 | 01-APR-18:10 | 2101.03 | 01-APR-00:10 | 22246.15 | 03-APR-16:10 | 0.00 | 8605.15 | 30-APR-08:00 | 14.49 | 01-APR-06:19 | 0.00 | 01-APR-00:10 |
| May | 4040.47 | 01-MAY-18:10 | 2101.03 | 01-MAY-00:10 | 22246.15 | 01-MAY-16:10 | 0.00 | 8539.59 | 31-MAY-17:00 | 14.49 | 01-MAY-06:10 | 0.00 | 01-MAY-00:10 |
| June | 4040.47 | 01-JUN-18:10 | 2101.03 | 01-JUN-00:10 | 22246.15 | 01-JUN-16:10 | 0.00 | 8815.98 | 09-JUN-16:30 | 14.49 | 01-JUN-06:10 | 0.00 | 01-JUN-00:10 |
| July | 4040.47 | 01-JUL-18:10 | 2101.03 | 01-JUL-00:10 | 22246.15 | 03-JUL-16:10 | 0.00 | 9212.07 | 30-JUL-16:10 | 14.49 | 01-JUL-16:19 | 0.00 | 01-JUL-00:10 |
| August | 4040.47 | 01-AUG-18:10 | 2101.03 | 01-AUG-00:10 | 22246.15 | 01-AUG-16:10 | 0.00 | 9758.92 | 10-AUG-16:10 | 14.49 | 01-AUG-06:40 | 0.00 | 01-AUG-00:10 |
| September | 4040.47 | 01-SEP-18:10 | 2101.03 | 01-SEP-00:10 | 22246.15 | 01-SEP-16:10 | 0.00 | 8753.38 | 09-SEP-16:10 | 14.49 | 01-SEP-06:10 | 0.00 | 01-SEP-00:10 |
| October | 4040.47 | 01-OCT-18:10 | 2101.03 | 01-OCT-00:10 | 22246.15 | 02-OCT-16:10 | 0.00 | 8094.83 | 07-OCT-16:10 | 14.49 | 01-OCT-17:10 | 0.00 | 01-OCT-00:10 |
| November | 4040.47 | 01-NOV-18:10 | 2101.03 | 01-NOV-00:10 | 22246.15 | 01-NOV-16:10 | 0.00 | 7508.94 | 15-NOV-09:50 | 14.49 | 01-NOV-05:19 | 0.00 | 01-NOV-00:10 |
| December | 4040.47 | 01-DEC-19:10 | 2101.03 | 01-DEC-00:10 | 22246.15 | 01-DEC-17:10 | 0.00 | 7411.51 | 06-DEC-11:50 | 14.49 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | ||||||||||||
| Minimum of Months | 4040.47 | 2101.03 | 22246.15 | 0.00 | 7410.82 | 14.49 | 0.00 | ||||||
| Maximum of Months | 4040.47 | 2101.03 | 22246.15 | 0.00 | 9758.92 | 14.49 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 21276.58 | 12-JAN-14:50 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 22573.08 | 28-FEB-13:09 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 24971.06 | 29-MAR-09:50 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 25906.07 | 30-APR-08:00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 29504.56 | 31-MAY-17:00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 31921.84 | 09-JUN-15:09 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 33623.66 | 21-JUL-15:09 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 36725.58 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 31101.38 | 08-SEP-15:09 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 27075.42 | 07-OCT-16:10 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 24863.81 | 01-NOV-14:09 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 22494.54 | 06-DEC-11:50 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 21276.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 36725.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 53231.21 | 08-JAN-17:30 | 3020.75 | 22179.86 | 0.00 | 0.00 | 7357.45 | 14.49 | 0.00 | 20658.67 | 0.00 |
| February | 50026.69 | 28-FEB-19:49 | 4040.47 | 18723.88 | 2101.03 | 0.00 | 6761.75 | 14.49 | 0.00 | 18385.07 | 0.00 |
| March | 52687.15 | 27-MAR-16:10 | 3020.75 | 22246.15 | 0.00 | 0.00 | 6879.39 | 14.49 | 0.00 | 20526.37 | 0.00 |
| April | 55246.85 | 30-APR-16:19 | 3020.75 | 22179.86 | 0.00 | 0.00 | 7322.89 | 14.49 | 0.00 | 22708.86 | 0.00 |
| May | 62523.76 | 31-MAY-17:00 | 3615.61 | 20849.51 | 0.00 | 0.00 | 8539.59 | 14.49 | 0.00 | 29504.56 | 0.00 |
| June | 65284.11 | 09-JUN-16:40 | 3020.75 | 22246.15 | 0.00 | 0.00 | 8809.00 | 14.49 | 0.00 | 31193.72 | 0.00 |
| July | 67287.74 | 30-JUL-16:10 | 3020.75 | 22179.86 | 0.00 | 0.00 | 9212.07 | 14.49 | 0.00 | 32860.58 | 0.00 |
| August | 71136.83 | 10-AUG-16:10 | 3020.75 | 22246.15 | 0.00 | 0.00 | 9758.92 | 14.49 | 0.00 | 36096.52 | 0.00 |
| September | 64409.23 | 09-SEP-16:10 | 3020.75 | 22179.86 | 0.00 | 0.00 | 8753.38 | 14.49 | 0.00 | 30440.75 | 0.00 |
| October | 60385.34 | 07-OCT-16:10 | 3020.75 | 22179.86 | 0.00 | 0.00 | 8094.83 | 14.49 | 0.00 | 27075.42 | 0.00 |
| November | 55919.09 | 01-NOV-16:10 | 3020.75 | 22246.15 | 0.00 | 0.00 | 7411.77 | 14.49 | 0.00 | 23225.93 | 0.00 |
| December | 52335.29 | 29-DEC-17:00 | 3020.75 | 22246.15 | 2101.03 | 0.00 | 6721.80 | 14.49 | 0.00 | 18231.07 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||||||||
| Minimum of Months | 50026.69 | 3020.75 | 18723.88 | 0.00 | 0.00 | 6721.80 | 14.49 | 0.00 | 18231.07 | 0.00 | |
| Maximum of Months | 71136.83 | 4040.47 | 22246.15 | 2101.03 | 0.00 | 9758.92 | 14.49 | 0.00 | 36096.52 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 21361.32 | 13-JAN-07:00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 21260.12 | 01-FEB-07:49 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 20791.99 | 01-MAR-07:40 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 18956.86 | 01-APR-06:49 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 17167.79 | 01-MAY-06:00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 15360.76 | 01-JUN-06:19 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 14317.34 | 31-JUL-06:19 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 15648.79 | 31-AUG-06:49 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 17259.18 | 30-SEP-06:40 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 19079.08 | 31-OCT-06:49 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 20900.51 | 30-NOV-07:00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 21321.72 | 31-DEC-07:30 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14317.34 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21361.32 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.64 | 0.00 | 24.64 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.65 | 0.00 | 24.65 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.66 | 0.00 | 24.66 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.71 | 0.00 | 24.71 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 25.17 | 0.00 | 25.17 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 25.56 | 0.00 | 25.56 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 25.65 | 0.00 | 25.65 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 25.63 | 0.00 | 25.63 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 25.56 | 0.00 | 25.56 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.38 | 0.00 | 25.38 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.99 | 0.00 | 24.99 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.73 | 0.00 | 24.73 |
| Annual Sum or Average | 0.00 | 0.00 | 40.50 | 25.39 | 0.00 | 25.39 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.64 | 0.00 | 24.64 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 25.65 | 0.00 | 25.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 3.33 | 23.99 | 401.50 | 24.82 | 0.00 | 24.82 |
| February | 0.83 | 25.85 | 404.83 | 24.64 | 0.83 | 24.64 |
| March | 5.00 | 25.40 | 395.17 | 24.46 | 5.00 | 24.47 |
| April | 14.00 | 25.23 | 483.17 | 24.18 | 14.00 | 24.21 |
| May | 6.67 | 24.56 | 512.00 | 24.03 | 6.67 | 24.04 |
| June | 44.33 | 24.00 | 492.00 | 24.00 | 44.33 | 24.00 |
| July | 72.33 | 24.00 | 533.00 | 24.00 | 72.33 | 24.00 |
| August | 40.33 | 24.00 | 506.00 | 24.00 | 40.33 | 24.00 |
| September | 4.50 | 24.50 | 510.00 | 24.02 | 4.50 | 24.02 |
| October | 2.33 | 25.60 | 524.00 | 24.07 | 2.33 | 24.08 |
| November | 2.50 | 26.06 | 510.00 | 24.25 | 2.50 | 24.26 |
| December | 10.83 | 26.00 | 504.50 | 24.68 | 10.83 | 24.70 |
| Annual Sum or Average | 207.00 | 24.30 | 5776.17 | 24.23 | 203.67 | 24.24 |
| Minimum of Months | 0.83 | 23.99 | 395.17 | 24.00 | 0.00 | 24.00 |
| Maximum of Months | 72.33 | 26.06 | 533.00 | 24.82 | 72.33 | 24.82 |
Report: ComfortReportSimple55Monthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 10.00 | 24.63 | 529.17 | 25.14 | 3.17 | 25.14 |
| February | 10.83 | 25.69 | 558.67 | 24.82 | 10.83 | 24.84 |
| March | 16.83 | 25.22 | 546.67 | 24.54 | 16.83 | 24.56 |
| April | 25.50 | 25.29 | 647.33 | 24.23 | 25.50 | 24.27 |
| May | 11.50 | 24.84 | 740.33 | 24.04 | 11.50 | 24.05 |
| June | 33.00 | 24.00 | 720.00 | 24.00 | 33.00 | 24.00 |
| July | 72.17 | 24.00 | 744.00 | 24.00 | 72.17 | 24.00 |
| August | 45.83 | 24.00 | 744.00 | 24.00 | 45.83 | 24.00 |
| September | 12.00 | 24.27 | 720.00 | 24.01 | 12.00 | 24.02 |
| October | 7.33 | 25.14 | 744.00 | 24.07 | 7.33 | 24.08 |
| November | 21.83 | 25.66 | 720.00 | 24.28 | 21.83 | 24.32 |
| December | 34.00 | 25.56 | 687.33 | 24.80 | 34.00 | 24.84 |
| Annual Sum or Average | 300.83 | 24.63 | 8101.50 | 24.29 | 294.00 | 24.30 |
| Minimum of Months | 7.33 | 24.00 | 529.17 | 24.00 | 3.17 | 24.00 |
| Maximum of Months | 72.17 | 25.69 | 744.00 | 25.14 | 72.17 | 25.14 |
Report: ComfortReportSimple55Monthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 133.33 | 24.00 | 0.00 | 24.00 |
| February | 0.00 | 0.00 | 132.67 | 24.00 | 0.00 | 24.00 |
| March | 0.00 | 0.00 | 155.50 | 24.00 | 0.00 | 24.00 |
| April | 0.00 | 0.00 | 140.00 | 24.00 | 0.00 | 24.00 |
| May | 0.00 | 0.00 | 154.00 | 24.00 | 0.00 | 24.00 |
| June | 0.67 | 24.00 | 154.00 | 24.00 | 0.67 | 24.00 |
| July | 2.50 | 24.00 | 140.00 | 24.00 | 2.50 | 24.00 |
| August | 2.17 | 24.00 | 161.00 | 24.00 | 2.17 | 24.00 |
| September | 0.17 | 24.00 | 140.00 | 24.00 | 0.17 | 24.00 |
| October | 0.00 | 0.00 | 147.00 | 24.00 | 0.00 | 24.00 |
| November | 0.00 | 0.00 | 140.00 | 24.00 | 0.00 | 24.00 |
| December | 0.00 | 0.00 | 140.00 | 24.00 | 0.00 | 24.00 |
| Annual Sum or Average | 5.50 | 24.00 | 1737.50 | 24.00 | 5.50 | 24.00 |
| Minimum of Months | 0.00 | 0.00 | 132.67 | 24.00 | 0.00 | 24.00 |
| Maximum of Months | 2.50 | 24.00 | 161.00 | 24.00 | 2.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 9.50 | 24.54 | 539.67 | 25.15 | 2.50 | 25.15 |
| February | 11.33 | 25.72 | 561.83 | 24.84 | 11.33 | 24.86 |
| March | 17.50 | 25.32 | 550.83 | 24.55 | 17.50 | 24.57 |
| April | 24.17 | 25.38 | 658.33 | 24.24 | 24.17 | 24.28 |
| May | 11.67 | 24.89 | 742.67 | 24.04 | 11.67 | 24.05 |
| June | 38.00 | 24.00 | 720.00 | 24.00 | 38.00 | 24.00 |
| July | 74.00 | 24.00 | 744.00 | 24.00 | 74.00 | 24.00 |
| August | 46.00 | 24.00 | 744.00 | 24.00 | 46.00 | 24.00 |
| September | 12.00 | 24.28 | 720.00 | 24.01 | 12.00 | 24.02 |
| October | 6.33 | 25.34 | 744.00 | 24.07 | 6.33 | 24.08 |
| November | 20.67 | 25.83 | 717.83 | 24.30 | 20.67 | 24.34 |
| December | 33.67 | 25.63 | 687.50 | 24.83 | 33.67 | 24.86 |
| Annual Sum or Average | 304.83 | 24.64 | 8130.67 | 24.30 | 297.83 | 24.31 |
| Minimum of Months | 6.33 | 24.00 | 539.67 | 24.00 | 2.50 | 24.00 |
| Maximum of Months | 74.00 | 25.83 | 744.00 | 25.15 | 74.00 | 25.15 |
Report: ComfortReportSimple55Monthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 6.33 | 25.07 | 563.00 | 25.06 | 3.50 | 25.06 |
| February | 10.17 | 25.72 | 578.50 | 24.81 | 10.17 | 24.82 |
| March | 17.67 | 25.23 | 539.00 | 24.57 | 17.67 | 24.59 |
| April | 24.83 | 25.35 | 603.00 | 24.26 | 24.83 | 24.30 |
| May | 14.33 | 24.68 | 714.67 | 24.04 | 14.33 | 24.05 |
| June | 80.33 | 24.00 | 720.00 | 24.00 | 80.33 | 24.00 |
| July | 147.83 | 24.00 | 744.00 | 24.00 | 147.83 | 24.00 |
| August | 105.33 | 24.00 | 744.00 | 24.00 | 105.33 | 24.00 |
| September | 50.33 | 24.07 | 720.00 | 24.01 | 50.33 | 24.02 |
| October | 30.33 | 24.33 | 731.33 | 24.07 | 30.33 | 24.08 |
| November | 23.83 | 25.59 | 713.00 | 24.28 | 23.83 | 24.32 |
| December | 34.00 | 25.56 | 690.83 | 24.79 | 34.00 | 24.83 |
| Annual Sum or Average | 545.33 | 24.35 | 8061.33 | 24.28 | 542.50 | 24.29 |
| Minimum of Months | 6.33 | 24.00 | 539.00 | 24.00 | 3.50 | 24.00 |
| Maximum of Months | 147.83 | 25.72 | 744.00 | 25.06 | 147.83 | 25.06 |
Report: ComfortReportSimple55Monthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 6.33 | 25.07 | 563.33 | 25.06 | 3.50 | 25.06 |
| February | 10.17 | 25.72 | 578.83 | 24.81 | 10.17 | 24.82 |
| March | 17.50 | 25.24 | 539.00 | 24.57 | 17.50 | 24.59 |
| April | 24.83 | 25.35 | 603.17 | 24.26 | 24.83 | 24.30 |
| May | 14.33 | 24.69 | 715.17 | 24.04 | 14.33 | 24.05 |
| June | 80.33 | 24.00 | 720.00 | 24.00 | 80.33 | 24.00 |
| July | 147.67 | 24.00 | 744.00 | 24.00 | 147.67 | 24.00 |
| August | 105.33 | 24.00 | 744.00 | 24.00 | 105.33 | 24.00 |
| September | 50.67 | 24.07 | 720.00 | 24.01 | 50.67 | 24.02 |
| October | 30.33 | 24.33 | 731.50 | 24.07 | 30.33 | 24.08 |
| November | 23.83 | 25.59 | 713.00 | 24.28 | 23.83 | 24.32 |
| December | 33.83 | 25.57 | 690.83 | 24.79 | 33.83 | 24.83 |
| Annual Sum or Average | 545.17 | 24.36 | 8062.83 | 24.28 | 542.33 | 24.29 |
| Minimum of Months | 6.33 | 24.00 | 539.00 | 24.00 | 3.50 | 24.00 |
| Maximum of Months | 147.67 | 25.72 | 744.00 | 25.06 | 147.67 | 25.06 |
Report: ComfortReportSimple55Monthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 443.83 | 24.77 | 0.00 | 24.77 |
| February | 0.67 | 25.89 | 435.50 | 24.62 | 0.67 | 24.62 |
| March | 5.50 | 25.48 | 416.67 | 24.46 | 5.50 | 24.47 |
| April | 13.33 | 25.30 | 471.17 | 24.20 | 13.33 | 24.23 |
| May | 9.83 | 24.39 | 507.00 | 24.03 | 9.83 | 24.04 |
| June | 87.17 | 24.00 | 492.00 | 24.00 | 87.17 | 24.00 |
| July | 131.17 | 24.00 | 533.00 | 24.00 | 131.17 | 24.00 |
| August | 85.50 | 24.00 | 506.00 | 24.00 | 85.50 | 24.00 |
| September | 23.50 | 24.11 | 510.00 | 24.02 | 23.50 | 24.02 |
| October | 8.17 | 24.54 | 524.00 | 24.07 | 8.17 | 24.08 |
| November | 3.50 | 26.07 | 510.00 | 24.25 | 3.50 | 24.26 |
| December | 11.00 | 26.09 | 517.67 | 24.67 | 11.00 | 24.70 |
| Annual Sum or Average | 379.33 | 24.18 | 5866.83 | 24.23 | 379.33 | 24.23 |
| Minimum of Months | 0.00 | 0.00 | 416.67 | 24.00 | 0.00 | 24.00 |
| Maximum of Months | 131.17 | 26.09 | 533.00 | 24.77 | 131.17 | 24.77 |
Report: ComfortReportSimple55Monthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 456.33 | 24.78 | 0.00 | 24.78 |
| February | 0.33 | 26.00 | 448.83 | 24.62 | 0.33 | 24.62 |
| March | 4.67 | 25.63 | 433.17 | 24.47 | 4.67 | 24.48 |
| April | 12.00 | 25.49 | 488.50 | 24.21 | 12.00 | 24.24 |
| May | 5.67 | 24.76 | 513.67 | 24.03 | 5.67 | 24.04 |
| June | 44.33 | 24.00 | 492.00 | 24.00 | 44.33 | 24.00 |
| July | 90.33 | 24.00 | 533.00 | 24.00 | 90.33 | 24.00 |
| August | 56.67 | 24.00 | 506.00 | 24.00 | 56.67 | 24.00 |
| September | 7.17 | 24.28 | 510.00 | 24.02 | 7.17 | 24.02 |
| October | 1.67 | 25.86 | 524.00 | 24.07 | 1.67 | 24.08 |
| November | 1.67 | 26.35 | 510.00 | 24.27 | 1.67 | 24.27 |
| December | 9.83 | 26.18 | 525.33 | 24.69 | 9.83 | 24.71 |
| Annual Sum or Average | 234.33 | 24.26 | 5940.83 | 24.25 | 234.33 | 24.25 |
| Minimum of Months | 0.00 | 0.00 | 433.17 | 24.00 | 0.00 | 24.00 |
| Maximum of Months | 90.33 | 26.35 | 533.00 | 24.78 | 90.33 | 24.78 |
Report: ComfortReportSimple55Monthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 7.67 | 24.06 | 324.83 | 24.91 | 0.50 | 24.92 |
| February | 1.67 | 25.39 | 367.83 | 24.68 | 1.67 | 24.69 |
| March | 6.33 | 25.30 | 369.00 | 24.50 | 6.33 | 24.52 |
| April | 14.17 | 25.17 | 463.67 | 24.18 | 14.17 | 24.20 |
| May | 8.33 | 24.41 | 494.67 | 24.03 | 8.33 | 24.03 |
| June | 69.50 | 24.00 | 492.00 | 24.00 | 69.50 | 24.00 |
| July | 116.00 | 24.00 | 533.00 | 24.00 | 116.00 | 24.00 |
| August | 97.00 | 24.00 | 506.00 | 24.00 | 97.00 | 24.00 |
| September | 52.33 | 24.06 | 510.00 | 24.01 | 52.33 | 24.02 |
| October | 45.83 | 24.16 | 519.50 | 24.05 | 45.83 | 24.06 |
| November | 8.50 | 25.23 | 476.50 | 24.19 | 8.50 | 24.21 |
| December | 12.50 | 25.39 | 438.17 | 24.63 | 12.50 | 24.65 |
| Annual Sum or Average | 439.83 | 24.16 | 5495.17 | 24.21 | 432.67 | 24.21 |
| Minimum of Months | 1.67 | 24.00 | 324.83 | 24.00 | 0.50 | 24.00 |
| Maximum of Months | 116.00 | 25.39 | 533.00 | 24.91 | 116.00 | 24.92 |
Report: ComfortReportSimple55Monthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 33.33 | 24.19 | 445.33 | 25.00 | 6.17 | 25.00 |
| February | 13.00 | 25.37 | 516.00 | 24.82 | 13.00 | 24.84 |
| March | 21.50 | 25.28 | 529.33 | 24.57 | 21.50 | 24.60 |
| April | 25.67 | 25.22 | 614.17 | 24.23 | 25.67 | 24.27 |
| May | 12.17 | 24.72 | 709.50 | 24.04 | 12.17 | 24.05 |
| June | 65.50 | 24.00 | 720.00 | 24.00 | 65.50 | 24.00 |
| July | 129.67 | 24.00 | 744.00 | 24.00 | 129.67 | 24.00 |
| August | 119.50 | 24.00 | 744.00 | 24.00 | 119.50 | 24.00 |
| September | 73.50 | 24.05 | 720.00 | 24.01 | 73.50 | 24.01 |
| October | 70.67 | 24.16 | 716.00 | 24.05 | 70.67 | 24.06 |
| November | 33.33 | 24.97 | 645.00 | 24.21 | 33.33 | 24.25 |
| December | 36.00 | 25.04 | 591.83 | 24.66 | 35.67 | 24.68 |
| Annual Sum or Average | 633.83 | 24.28 | 7695.17 | 24.24 | 606.33 | 24.25 |
| Minimum of Months | 12.17 | 24.00 | 445.33 | 24.00 | 6.17 | 24.00 |
| Maximum of Months | 129.67 | 25.37 | 744.00 | 25.00 | 129.67 | 25.00 |
Report: ComfortReportSimple55Monthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 7.33 | 23.97 | 328.50 | 24.91 | 0.17 | 24.91 |
| February | 2.17 | 25.59 | 367.50 | 24.69 | 2.17 | 24.69 |
| March | 6.67 | 25.30 | 364.67 | 24.51 | 6.67 | 24.52 |
| April | 13.83 | 25.27 | 460.00 | 24.19 | 13.83 | 24.22 |
| May | 9.67 | 24.37 | 497.83 | 24.03 | 9.67 | 24.03 |
| June | 73.00 | 24.00 | 492.00 | 24.00 | 73.00 | 24.00 |
| July | 122.67 | 24.00 | 533.00 | 24.00 | 122.67 | 24.00 |
| August | 103.00 | 24.00 | 506.00 | 24.00 | 103.00 | 24.00 |
| September | 55.17 | 24.05 | 510.00 | 24.01 | 55.17 | 24.02 |
| October | 45.17 | 24.17 | 517.67 | 24.06 | 45.17 | 24.07 |
| November | 8.50 | 25.28 | 472.67 | 24.20 | 8.50 | 24.22 |
| December | 13.50 | 25.44 | 437.67 | 24.64 | 13.50 | 24.66 |
| Annual Sum or Average | 460.67 | 24.16 | 5487.50 | 24.21 | 453.50 | 24.21 |
| Minimum of Months | 2.17 | 23.97 | 328.50 | 24.00 | 0.17 | 24.00 |
| Maximum of Months | 122.67 | 25.59 | 533.00 | 24.91 | 122.67 | 24.91 |
Report: ComfortReportSimple55Monthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 25.67 | 24.23 | 467.17 | 25.01 | 5.67 | 25.02 |
| February | 13.17 | 25.42 | 523.50 | 24.84 | 13.17 | 24.86 |
| March | 22.00 | 25.36 | 534.50 | 24.59 | 22.00 | 24.62 |
| April | 24.83 | 25.32 | 627.00 | 24.24 | 24.83 | 24.28 |
| May | 13.83 | 24.69 | 724.50 | 24.04 | 13.83 | 24.05 |
| June | 66.83 | 24.00 | 720.00 | 24.00 | 66.83 | 24.00 |
| July | 132.67 | 24.00 | 744.00 | 24.00 | 132.67 | 24.00 |
| August | 119.83 | 24.00 | 744.00 | 24.00 | 119.83 | 24.00 |
| September | 77.67 | 24.05 | 720.00 | 24.01 | 77.67 | 24.01 |
| October | 65.67 | 24.19 | 719.00 | 24.06 | 65.67 | 24.07 |
| November | 32.17 | 25.12 | 643.00 | 24.24 | 32.17 | 24.28 |
| December | 35.67 | 25.12 | 594.00 | 24.69 | 35.67 | 24.71 |
| Annual Sum or Average | 630.00 | 24.30 | 7760.67 | 24.25 | 610.00 | 24.26 |
| Minimum of Months | 13.17 | 24.00 | 467.17 | 24.00 | 5.67 | 24.00 |
| Maximum of Months | 132.67 | 25.42 | 744.00 | 25.01 | 132.67 | 25.02 |
Report: ComfortReportSimple55Monthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 14.33 | 24.80 | 475.17 | 25.01 | 7.50 | 25.02 |
| February | 16.67 | 25.47 | 522.00 | 24.81 | 16.67 | 24.82 |
| March | 22.00 | 25.22 | 491.00 | 24.62 | 22.00 | 24.64 |
| April | 25.33 | 25.23 | 557.67 | 24.26 | 25.33 | 24.30 |
| May | 20.33 | 24.43 | 669.33 | 24.04 | 20.33 | 24.05 |
| June | 113.67 | 24.00 | 715.50 | 24.00 | 113.67 | 24.00 |
| July | 207.83 | 24.00 | 735.50 | 24.00 | 207.83 | 24.00 |
| August | 208.67 | 24.00 | 744.00 | 24.00 | 208.67 | 24.00 |
| September | 150.17 | 24.03 | 718.83 | 24.01 | 150.17 | 24.01 |
| October | 91.67 | 24.13 | 691.50 | 24.05 | 91.67 | 24.06 |
| November | 32.67 | 25.00 | 612.33 | 24.24 | 32.67 | 24.27 |
| December | 36.17 | 25.15 | 596.67 | 24.70 | 36.17 | 24.72 |
| Annual Sum or Average | 939.50 | 24.21 | 7529.50 | 24.24 | 932.67 | 24.24 |
| Minimum of Months | 14.33 | 24.00 | 475.17 | 24.00 | 7.50 | 24.00 |
| Maximum of Months | 208.67 | 25.47 | 744.00 | 25.01 | 208.67 | 25.02 |
Report: ComfortReportSimple55Monthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 14.33 | 24.81 | 476.00 | 25.02 | 7.50 | 25.03 |
| February | 16.67 | 25.47 | 522.67 | 24.81 | 16.67 | 24.83 |
| March | 21.83 | 25.23 | 491.00 | 24.62 | 21.83 | 24.64 |
| April | 25.33 | 25.23 | 557.67 | 24.26 | 25.33 | 24.30 |
| May | 20.50 | 24.43 | 670.17 | 24.04 | 20.50 | 24.05 |
| June | 113.50 | 24.00 | 715.50 | 24.00 | 113.50 | 24.00 |
| July | 207.67 | 24.00 | 735.50 | 24.00 | 207.67 | 24.00 |
| August | 208.67 | 24.00 | 744.00 | 24.00 | 208.67 | 24.00 |
| September | 150.17 | 24.03 | 718.83 | 24.01 | 150.17 | 24.01 |
| October | 91.50 | 24.13 | 691.67 | 24.05 | 91.50 | 24.06 |
| November | 32.67 | 25.00 | 612.83 | 24.24 | 32.67 | 24.27 |
| December | 36.17 | 25.16 | 596.50 | 24.70 | 36.17 | 24.72 |
| Annual Sum or Average | 939.00 | 24.21 | 7532.33 | 24.25 | 932.17 | 24.24 |
| Minimum of Months | 14.33 | 24.00 | 476.00 | 24.00 | 7.50 | 24.00 |
| Maximum of Months | 208.67 | 25.47 | 744.00 | 25.02 | 208.67 | 25.03 |
Report: ComfortReportSimple55Monthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.00 | 24.18 | 358.83 | 24.89 | 0.17 | 24.89 |
| February | 1.50 | 25.71 | 393.50 | 24.67 | 1.50 | 24.67 |
| March | 6.50 | 25.31 | 377.17 | 24.50 | 6.50 | 24.52 |
| April | 14.17 | 25.18 | 436.33 | 24.19 | 14.17 | 24.22 |
| May | 17.67 | 24.20 | 478.50 | 24.03 | 17.67 | 24.03 |
| June | 109.17 | 24.00 | 491.17 | 24.00 | 109.17 | 24.00 |
| July | 179.17 | 24.00 | 525.83 | 24.00 | 179.17 | 24.00 |
| August | 155.17 | 24.00 | 506.00 | 24.00 | 155.17 | 24.00 |
| September | 98.50 | 24.03 | 510.00 | 24.01 | 98.50 | 24.02 |
| October | 58.33 | 24.12 | 512.17 | 24.05 | 58.33 | 24.06 |
| November | 8.17 | 25.30 | 478.17 | 24.20 | 8.17 | 24.22 |
| December | 12.33 | 25.55 | 460.83 | 24.64 | 12.33 | 24.66 |
| Annual Sum or Average | 662.67 | 24.11 | 5528.50 | 24.21 | 660.83 | 24.20 |
| Minimum of Months | 1.50 | 24.00 | 358.83 | 24.00 | 0.17 | 24.00 |
| Maximum of Months | 179.17 | 25.71 | 525.83 | 24.89 | 179.17 | 24.89 |
Report: ComfortReportSimple55Monthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.00 | 24.18 | 360.17 | 24.89 | 0.17 | 24.89 |
| February | 1.50 | 25.71 | 394.17 | 24.67 | 1.50 | 24.67 |
| March | 6.50 | 25.31 | 378.50 | 24.50 | 6.50 | 24.52 |
| April | 14.33 | 25.18 | 437.50 | 24.19 | 14.33 | 24.23 |
| May | 17.83 | 24.19 | 479.00 | 24.03 | 17.83 | 24.03 |
| June | 110.50 | 24.00 | 491.17 | 24.00 | 110.50 | 24.00 |
| July | 182.83 | 24.00 | 525.83 | 24.00 | 182.83 | 24.00 |
| August | 158.17 | 24.00 | 506.00 | 24.00 | 158.17 | 24.00 |
| September | 100.67 | 24.03 | 510.00 | 24.01 | 100.67 | 24.02 |
| October | 59.50 | 24.12 | 512.50 | 24.05 | 59.50 | 24.06 |
| November | 8.33 | 25.29 | 479.33 | 24.20 | 8.33 | 24.22 |
| December | 12.50 | 25.56 | 461.67 | 24.64 | 12.50 | 24.66 |
| Annual Sum or Average | 674.67 | 24.11 | 5535.83 | 24.21 | 672.83 | 24.20 |
| Minimum of Months | 1.50 | 24.00 | 360.17 | 24.00 | 0.17 | 24.00 |
| Maximum of Months | 182.83 | 25.71 | 525.83 | 24.89 | 182.83 | 24.89 |
Report: ComfortReportSimple55Monthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 151.00 | 23.53 | 260.67 | 24.49 | 3.67 | 24.51 |
| February | 75.33 | 23.77 | 284.33 | 24.56 | 8.17 | 24.59 |
| March | 58.67 | 23.80 | 308.17 | 24.40 | 7.33 | 24.41 |
| April | 29.00 | 24.54 | 425.83 | 24.13 | 26.00 | 24.16 |
| May | 19.83 | 24.17 | 495.17 | 24.02 | 19.83 | 24.03 |
| June | 82.33 | 24.00 | 492.00 | 24.00 | 82.33 | 24.00 |
| July | 132.33 | 24.00 | 532.50 | 24.00 | 132.33 | 24.00 |
| August | 113.17 | 24.00 | 506.00 | 24.00 | 113.17 | 24.00 |
| September | 85.83 | 24.04 | 510.00 | 24.01 | 85.83 | 24.02 |
| October | 72.83 | 24.11 | 517.00 | 24.05 | 72.83 | 24.05 |
| November | 26.33 | 24.38 | 435.83 | 24.14 | 21.00 | 24.16 |
| December | 87.67 | 23.87 | 346.00 | 24.50 | 21.33 | 24.51 |
| Annual Sum or Average | 934.33 | 23.92 | 5113.50 | 24.15 | 593.83 | 24.15 |
| Minimum of Months | 19.83 | 23.53 | 260.67 | 24.00 | 3.67 | 24.00 |
| Maximum of Months | 151.00 | 24.54 | 532.50 | 24.56 | 132.33 | 24.59 |
Report: ComfortReportSimple55Monthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 245.67 | 23.33 | 352.67 | 24.41 | 6.83 | 24.42 |
| February | 125.00 | 23.67 | 433.67 | 24.62 | 17.50 | 24.64 |
| March | 94.17 | 23.96 | 490.50 | 24.44 | 24.00 | 24.47 |
| April | 43.50 | 24.69 | 615.83 | 24.17 | 39.17 | 24.21 |
| May | 25.50 | 24.33 | 721.00 | 24.03 | 25.50 | 24.04 |
| June | 88.67 | 24.01 | 720.00 | 24.00 | 88.67 | 24.00 |
| July | 146.83 | 24.00 | 743.50 | 24.00 | 146.83 | 24.00 |
| August | 134.50 | 24.00 | 744.00 | 24.00 | 134.50 | 24.00 |
| September | 108.17 | 24.04 | 720.00 | 24.01 | 108.17 | 24.01 |
| October | 106.17 | 24.12 | 731.17 | 24.05 | 106.17 | 24.05 |
| November | 66.67 | 24.41 | 622.00 | 24.16 | 54.67 | 24.19 |
| December | 165.83 | 23.78 | 499.50 | 24.42 | 54.33 | 24.42 |
| Annual Sum or Average | 1350.67 | 23.88 | 7393.83 | 24.16 | 806.33 | 24.17 |
| Minimum of Months | 25.50 | 23.33 | 352.67 | 24.00 | 6.83 | 24.00 |
| Maximum of Months | 245.67 | 24.69 | 744.00 | 24.62 | 146.83 | 24.64 |
Report: ComfortReportSimple55Monthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 144.50 | 23.52 | 262.50 | 24.50 | 2.83 | 24.52 |
| February | 73.00 | 23.71 | 286.33 | 24.54 | 6.67 | 24.56 |
| March | 59.50 | 23.85 | 307.33 | 24.41 | 9.50 | 24.42 |
| April | 28.83 | 24.62 | 426.67 | 24.14 | 26.17 | 24.17 |
| May | 20.83 | 24.17 | 497.33 | 24.02 | 20.83 | 24.03 |
| June | 88.33 | 24.00 | 492.00 | 24.00 | 88.33 | 24.00 |
| July | 139.17 | 24.00 | 533.00 | 24.00 | 139.17 | 24.00 |
| August | 116.83 | 24.00 | 506.00 | 24.00 | 116.83 | 24.00 |
| September | 88.33 | 24.04 | 510.00 | 24.01 | 88.33 | 24.02 |
| October | 72.67 | 24.11 | 516.83 | 24.05 | 72.67 | 24.06 |
| November | 26.67 | 24.43 | 436.17 | 24.16 | 21.67 | 24.18 |
| December | 87.50 | 23.92 | 349.83 | 24.51 | 22.67 | 24.53 |
| Annual Sum or Average | 946.17 | 23.93 | 5124.00 | 24.16 | 615.67 | 24.16 |
| Minimum of Months | 20.83 | 23.52 | 262.50 | 24.00 | 2.83 | 24.00 |
| Maximum of Months | 144.50 | 24.62 | 533.00 | 24.54 | 139.17 | 24.56 |
Report: ComfortReportSimple55Monthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 229.17 | 23.36 | 359.00 | 24.46 | 6.17 | 24.47 |
| February | 114.83 | 23.69 | 450.67 | 24.65 | 17.17 | 24.66 |
| March | 90.33 | 24.04 | 499.00 | 24.47 | 24.50 | 24.50 |
| April | 44.33 | 24.77 | 627.50 | 24.19 | 40.17 | 24.23 |
| May | 25.67 | 24.37 | 725.83 | 24.04 | 25.67 | 24.05 |
| June | 89.33 | 24.01 | 720.00 | 24.00 | 89.33 | 24.00 |
| July | 150.17 | 24.00 | 744.00 | 24.00 | 150.17 | 24.00 |
| August | 131.83 | 24.00 | 744.00 | 24.00 | 131.83 | 24.00 |
| September | 107.17 | 24.04 | 720.00 | 24.01 | 107.17 | 24.01 |
| October | 98.00 | 24.13 | 735.83 | 24.05 | 98.00 | 24.06 |
| November | 63.17 | 24.57 | 621.83 | 24.20 | 53.33 | 24.24 |
| December | 159.83 | 23.87 | 518.83 | 24.46 | 60.50 | 24.47 |
| Annual Sum or Average | 1303.83 | 23.92 | 7466.50 | 24.18 | 804.00 | 24.18 |
| Minimum of Months | 25.67 | 23.36 | 359.00 | 24.00 | 6.17 | 24.00 |
| Maximum of Months | 229.17 | 24.77 | 744.00 | 24.65 | 150.17 | 24.66 |
Report: ComfortReportSimple55Monthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 151.33 | 23.68 | 373.67 | 24.66 | 6.83 | 24.68 |
| February | 58.00 | 24.12 | 452.67 | 24.76 | 15.50 | 24.77 |
| March | 54.67 | 24.38 | 490.67 | 24.52 | 24.00 | 24.55 |
| April | 38.50 | 24.91 | 616.50 | 24.20 | 38.50 | 24.24 |
| May | 30.17 | 24.30 | 714.67 | 24.03 | 30.17 | 24.05 |
| June | 112.17 | 24.00 | 720.00 | 24.00 | 112.17 | 24.00 |
| July | 182.50 | 24.00 | 739.17 | 24.00 | 182.50 | 24.00 |
| August | 172.33 | 24.00 | 744.00 | 24.00 | 172.33 | 24.00 |
| September | 140.17 | 24.03 | 720.00 | 24.01 | 140.17 | 24.01 |
| October | 113.00 | 24.11 | 723.50 | 24.05 | 113.00 | 24.06 |
| November | 49.50 | 24.70 | 625.17 | 24.20 | 46.17 | 24.23 |
| December | 94.17 | 24.23 | 528.33 | 24.58 | 42.50 | 24.59 |
| Annual Sum or Average | 1196.50 | 24.08 | 7448.33 | 24.20 | 923.83 | 24.20 |
| Minimum of Months | 30.17 | 23.68 | 373.67 | 24.00 | 6.83 | 24.00 |
| Maximum of Months | 182.50 | 24.91 | 744.00 | 24.76 | 182.50 | 24.77 |
Report: ComfortReportSimple55Monthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 150.00 | 23.67 | 376.50 | 24.67 | 6.83 | 24.68 |
| February | 58.33 | 24.13 | 453.50 | 24.76 | 15.67 | 24.78 |
| March | 54.67 | 24.38 | 490.33 | 24.52 | 23.83 | 24.55 |
| April | 38.50 | 24.92 | 616.50 | 24.20 | 38.50 | 24.24 |
| May | 30.17 | 24.30 | 714.83 | 24.03 | 30.17 | 24.05 |
| June | 112.33 | 24.00 | 720.00 | 24.00 | 112.33 | 24.00 |
| July | 182.50 | 24.00 | 739.17 | 24.00 | 182.50 | 24.00 |
| August | 172.17 | 24.00 | 744.00 | 24.00 | 172.17 | 24.00 |
| September | 140.33 | 24.03 | 720.00 | 24.01 | 140.33 | 24.01 |
| October | 112.50 | 24.12 | 723.33 | 24.05 | 112.50 | 24.06 |
| November | 49.33 | 24.71 | 625.33 | 24.20 | 46.00 | 24.24 |
| December | 93.67 | 24.24 | 528.33 | 24.58 | 42.67 | 24.60 |
| Annual Sum or Average | 1194.50 | 24.08 | 7451.83 | 24.20 | 923.50 | 24.20 |
| Minimum of Months | 30.17 | 23.67 | 376.50 | 24.00 | 6.83 | 24.00 |
| Maximum of Months | 182.50 | 24.92 | 744.00 | 24.76 | 182.50 | 24.78 |
Report: ComfortReportSimple55Monthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 64.17 | 23.84 | 285.00 | 24.82 | 2.33 | 24.83 |
| February | 17.33 | 24.23 | 313.50 | 24.71 | 4.50 | 24.72 |
| March | 24.50 | 24.17 | 320.50 | 24.48 | 7.50 | 24.50 |
| April | 23.67 | 24.82 | 435.17 | 24.15 | 22.50 | 24.19 |
| May | 25.00 | 24.15 | 491.83 | 24.02 | 25.00 | 24.03 |
| June | 105.67 | 24.00 | 492.00 | 24.00 | 105.67 | 24.00 |
| July | 163.33 | 24.00 | 528.50 | 24.00 | 163.33 | 24.00 |
| August | 140.00 | 24.00 | 506.00 | 24.00 | 140.00 | 24.00 |
| September | 108.50 | 24.03 | 510.00 | 24.01 | 108.50 | 24.02 |
| October | 75.00 | 24.11 | 517.00 | 24.05 | 75.00 | 24.06 |
| November | 16.17 | 24.80 | 445.83 | 24.17 | 14.83 | 24.19 |
| December | 31.33 | 24.50 | 374.00 | 24.65 | 15.50 | 24.67 |
| Annual Sum or Average | 794.67 | 24.08 | 5219.33 | 24.19 | 684.67 | 24.18 |
| Minimum of Months | 16.17 | 23.84 | 285.00 | 24.00 | 2.33 | 24.00 |
| Maximum of Months | 163.33 | 24.82 | 528.50 | 24.82 | 163.33 | 24.83 |
Report: ComfortReportSimple55Monthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 64.33 | 23.84 | 285.17 | 24.82 | 2.33 | 24.83 |
| February | 17.50 | 24.23 | 313.17 | 24.71 | 4.50 | 24.72 |
| March | 24.83 | 24.17 | 320.33 | 24.48 | 7.50 | 24.50 |
| April | 23.67 | 24.82 | 435.17 | 24.15 | 22.50 | 24.19 |
| May | 25.00 | 24.15 | 491.67 | 24.02 | 25.00 | 24.03 |
| June | 105.67 | 24.00 | 492.00 | 24.00 | 105.67 | 24.00 |
| July | 163.67 | 24.00 | 528.50 | 24.00 | 163.67 | 24.00 |
| August | 140.17 | 24.00 | 506.00 | 24.00 | 140.17 | 24.00 |
| September | 108.83 | 24.03 | 510.00 | 24.01 | 108.83 | 24.02 |
| October | 75.00 | 24.11 | 517.00 | 24.05 | 75.00 | 24.06 |
| November | 16.17 | 24.80 | 445.67 | 24.17 | 14.83 | 24.19 |
| December | 31.67 | 24.51 | 373.83 | 24.65 | 15.67 | 24.67 |
| Annual Sum or Average | 796.50 | 24.08 | 5218.50 | 24.19 | 685.67 | 24.18 |
| Minimum of Months | 16.17 | 23.84 | 285.17 | 24.00 | 2.33 | 24.00 |
| Maximum of Months | 163.67 | 24.82 | 528.50 | 24.82 | 163.67 | 24.83 |
Report: ComfortReportSimple55Monthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 25.39 | 744.00 | 25.39 | 744.00 | 25.39 |
| February | 672.00 | 25.66 | 672.00 | 25.66 | 672.00 | 25.66 |
| March | 744.00 | 25.81 | 744.00 | 25.81 | 744.00 | 25.81 |
| April | 720.00 | 26.06 | 720.00 | 26.06 | 720.00 | 26.06 |
| May | 744.00 | 26.58 | 744.00 | 26.58 | 744.00 | 26.58 |
| June | 720.00 | 26.75 | 720.00 | 26.75 | 720.00 | 26.75 |
| July | 744.00 | 26.99 | 744.00 | 26.99 | 744.00 | 26.99 |
| August | 744.00 | 27.02 | 744.00 | 27.02 | 744.00 | 27.02 |
| September | 720.00 | 26.69 | 720.00 | 26.69 | 720.00 | 26.69 |
| October | 744.00 | 26.34 | 744.00 | 26.34 | 744.00 | 26.34 |
| November | 720.00 | 25.88 | 720.00 | 25.88 | 720.00 | 25.88 |
| December | 744.00 | 25.57 | 744.00 | 25.57 | 744.00 | 25.57 |
| Annual Sum or Average | 8760.00 | 26.23 | 8760.00 | 26.23 | 8760.00 | 26.23 |
| Minimum of Months | 672.00 | 25.39 | 672.00 | 25.39 | 672.00 | 25.39 |
| Maximum of Months | 744.00 | 27.02 | 744.00 | 27.02 | 744.00 | 27.02 |
Report: ComfortReportSimple55Monthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 243.50 | 26.14 | 695.50 | 26.29 | 215.67 | 26.37 |
| February | 301.17 | 26.63 | 648.67 | 26.55 | 287.50 | 26.63 |
| March | 367.17 | 27.00 | 725.17 | 26.89 | 357.17 | 26.95 |
| April | 596.17 | 27.58 | 717.50 | 27.51 | 595.83 | 27.53 |
| May | 733.17 | 28.58 | 744.00 | 28.56 | 733.17 | 28.57 |
| June | 720.00 | 28.94 | 720.00 | 28.94 | 720.00 | 28.94 |
| July | 744.00 | 29.39 | 744.00 | 29.39 | 744.00 | 29.39 |
| August | 744.00 | 29.54 | 744.00 | 29.54 | 744.00 | 29.54 |
| September | 720.00 | 29.01 | 720.00 | 29.01 | 720.00 | 29.01 |
| October | 737.17 | 28.46 | 744.00 | 28.45 | 737.17 | 28.46 |
| November | 670.00 | 27.71 | 719.50 | 27.66 | 670.00 | 27.67 |
| December | 421.50 | 26.86 | 727.50 | 26.79 | 412.00 | 26.84 |
| Annual Sum or Average | 6997.83 | 28.31 | 8649.83 | 28.13 | 6936.50 | 28.20 |
| Minimum of Months | 243.50 | 26.14 | 648.67 | 26.29 | 215.67 | 26.37 |
| Maximum of Months | 744.00 | 29.54 | 744.00 | 29.54 | 744.00 | 29.54 |
Report: ComfortReportSimple55Monthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 26.01 | 744.00 | 26.01 | 744.00 | 26.01 |
| February | 672.00 | 26.09 | 672.00 | 26.09 | 672.00 | 26.09 |
| March | 744.00 | 26.06 | 744.00 | 26.06 | 744.00 | 26.06 |
| April | 720.00 | 26.07 | 720.00 | 26.07 | 720.00 | 26.07 |
| May | 744.00 | 26.29 | 744.00 | 26.29 | 744.00 | 26.29 |
| June | 720.00 | 26.38 | 720.00 | 26.38 | 720.00 | 26.38 |
| July | 744.00 | 26.48 | 744.00 | 26.48 | 744.00 | 26.48 |
| August | 744.00 | 26.51 | 744.00 | 26.51 | 744.00 | 26.51 |
| September | 720.00 | 26.35 | 720.00 | 26.35 | 720.00 | 26.35 |
| October | 744.00 | 26.19 | 744.00 | 26.19 | 744.00 | 26.19 |
| November | 720.00 | 26.00 | 720.00 | 26.00 | 720.00 | 26.00 |
| December | 744.00 | 26.01 | 744.00 | 26.01 | 744.00 | 26.01 |
| Annual Sum or Average | 8760.00 | 26.20 | 8760.00 | 26.20 | 8760.00 | 26.20 |
| Minimum of Months | 672.00 | 26.00 | 672.00 | 26.00 | 672.00 | 26.00 |
| Maximum of Months | 744.00 | 26.51 | 744.00 | 26.51 | 744.00 | 26.51 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 147.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 1750.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: SPLIT GSW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.160177E+10 | 0.403544E+09 | 403.34 | 0.146263E+10 | 0.139138E+09 | 0.00 | 1.00 | 01-JAN-14:32 | 0.00 | 01-JAN-09:20 | 7959.44 | 30-JAN-12:02 | 7542.75 | 26-JAN-16:42 | 1898.39 | 30-JAN-12:02 | 1743.05 | 23-JAN-12:32 | 0.00 |
| February | 0.177941E+10 | 0.455760E+09 | 400.47 | 0.158688E+10 | 0.192528E+09 | 0.00 | 1.00 | 01-FEB-11:22 | 0.00 | 01-FEB-08:45 | 8006.31 | 18-FEB-12:52 | 7543.69 | 15-FEB-17:12 | 2328.59 | 07-FEB-09:43 | 1788.06 | 23-FEB-11:52 | 0.00 |
| March | 0.242078E+10 | 0.640372E+09 | 523.36 | 0.220229E+10 | 0.218494E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 8095.09 | 24-MAR-10:12 | 7540.34 | 07-MAR-20:22 | 2843.50 | 29-MAR-09:43 | 1774.76 | 29-MAR-09:42 | 0.00 |
| April | 0.322871E+10 | 0.881720E+09 | 616.64 | 0.284763E+10 | 0.381083E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 8295.02 | 30-APR-08:52 | 7427.26 | 06-APR-08:22 | 3637.83 | 30-APR-08:53 | 1806.36 | 25-APR-07:42 | 0.00 |
| May | 0.486238E+10 | 0.139730E+10 | 730.72 | 0.422713E+10 | 0.635245E+09 | 0.00 | 1.00 | 01-MAY-09:22 | 0.00 | 01-MAY-05:15 | 8237.00 | 01-MAY-09:22 | 6819.94 | 15-MAY-07:42 | 3452.62 | 01-MAY-09:23 | 1786.57 | 01-MAY-09:23 | 0.00 |
| June | 0.571614E+10 | 0.165400E+10 | 718.86 | 0.464436E+10 | 0.107178E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 7489.90 | 22-JUN-09:02 | 6122.83 | 22-JUN-09:02 | 1403.11 | 22-JUN-09:03 | 1951.51 | 22-JUN-09:02 | 0.00 |
| July | 0.694791E+10 | 0.205336E+10 | 744.00 | 0.555552E+10 | 0.139239E+10 | 0.00 | 0.57 | 30-JUL-16:10 | 0.22 | 03-JUL-06:00 | 3808.36 | 30-JUL-17:10 | 3144.05 | 21-JUL-17:01 | 947.33 | 30-JUL-17:10 | 1129.34 | 30-JUL-16:10 | 0.00 |
| August | 0.757670E+10 | 0.223551E+10 | 744.00 | 0.607257E+10 | 0.150413E+10 | 0.00 | 0.63 | 10-AUG-16:10 | 0.29 | 15-AUG-07:00 | 4034.85 | 10-AUG-16:10 | 3279.47 | 10-AUG-16:10 | 1030.46 | 22-AUG-17:20 | 1272.26 | 10-AUG-16:10 | 0.00 |
| September | 0.672383E+10 | 0.191220E+10 | 716.56 | 0.543584E+10 | 0.128799E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 8051.49 | 25-SEP-07:22 | 6148.03 | 30-SEP-06:52 | 2559.85 | 25-SEP-07:23 | 1746.36 | 30-SEP-06:52 | 0.00 |
| October | 0.595862E+10 | 0.164014E+10 | 723.03 | 0.508048E+10 | 0.878141E+09 | 0.00 | 1.00 | 20-OCT-07:32 | 0.00 | 20-OCT-05:13 | 8082.10 | 31-OCT-07:42 | 7335.03 | 20-OCT-07:32 | 2654.38 | 31-OCT-07:43 | 1778.33 | 21-OCT-08:42 | 0.00 |
| November | 0.438731E+10 | 0.116178E+10 | 621.47 | 0.387146E+10 | 0.515842E+09 | 0.00 | 1.00 | 01-NOV-07:52 | 0.00 | 01-NOV-05:13 | 8056.44 | 01-NOV-07:52 | 7208.23 | 21-NOV-22:52 | 2597.99 | 01-NOV-07:53 | 1778.79 | 06-NOV-08:52 | 0.00 |
| December | 0.254367E+10 | 0.645934E+09 | 457.06 | 0.225122E+10 | 0.292454E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 8129.29 | 24-DEC-12:12 | 7547.27 | 30-DEC-10:42 | 2830.19 | 24-DEC-12:13 | 1741.55 | 02-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.537472E+11 | 0.150816E+11 | 7399.50 | 0.452380E+11 | 0.850922E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.160177E+10 | 0.403544E+09 | 400.47 | 0.146263E+10 | 0.139138E+09 | 0.00 | 0.57 | 0.00 | 3808.36 | 3144.05 | 947.33 | 1129.34 | 0.00 | ||||||
| Maximum of Months | 0.757670E+10 | 0.223551E+10 | 744.00 | 0.607257E+10 | 0.150413E+10 | 0.00 | 1.00 | 0.29 | 8295.02 | 7547.27 | 3637.83 | 1951.51 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.100291E+10 | 0.254385E+09 | 344.26 | 0.893161E+09 | 0.109750E+09 | 0.00 | 1.00 | 02-JAN-22:52 | 0.00 | 01-JAN-04:30 | 7783.67 | 30-JAN-11:22 | 7316.02 | 05-JAN-18:12 | 2272.07 | 30-JAN-11:23 | 1726.00 | 23-JAN-13:02 | 0.00 |
| February | 0.126769E+10 | 0.326372E+09 | 356.40 | 0.110171E+10 | 0.165976E+09 | 0.00 | 1.00 | 01-FEB-12:32 | 0.00 | 01-FEB-08:45 | 7775.93 | 07-FEB-09:42 | 7314.08 | 12-FEB-17:12 | 2268.02 | 07-FEB-09:43 | 1720.29 | 23-FEB-11:42 | 0.00 |
| March | 0.201011E+10 | 0.533523E+09 | 502.11 | 0.180649E+10 | 0.203613E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 7872.81 | 29-MAR-09:42 | 7299.67 | 10-MAR-17:52 | 2867.08 | 29-MAR-09:43 | 1721.13 | 29-MAR-09:42 | 0.00 |
| April | 0.298942E+10 | 0.816694E+09 | 614.69 | 0.261918E+10 | 0.370248E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 8020.46 | 30-APR-08:52 | 7206.60 | 06-APR-08:22 | 3424.28 | 30-APR-08:53 | 1775.69 | 23-APR-08:52 | 0.00 |
| May | 0.487446E+10 | 0.139838E+10 | 731.44 | 0.423473E+10 | 0.639728E+09 | 0.00 | 1.00 | 01-MAY-09:12 | 0.00 | 01-MAY-05:15 | 8002.31 | 01-MAY-09:12 | 6602.49 | 15-MAY-07:32 | 3406.52 | 01-MAY-09:13 | 1720.70 | 02-MAY-08:62 | 0.00 |
| June | 0.584349E+10 | 0.168664E+10 | 718.69 | 0.476208E+10 | 0.108141E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 7263.20 | 22-JUN-09:02 | 5923.47 | 22-JUN-09:02 | 1495.22 | 22-JUN-09:03 | 1892.42 | 22-JUN-09:02 | 0.00 |
| July | 0.698816E+10 | 0.206065E+10 | 744.00 | 0.559339E+10 | 0.139478E+10 | 0.00 | 0.58 | 21-JUL-16:30 | 0.23 | 03-JUL-06:00 | 3759.07 | 19-JUL-16:40 | 3175.68 | 21-JUL-17:01 | 932.16 | 19-JUL-16:01 | 1117.02 | 19-JUL-16:50 | 0.00 |
| August | 0.745271E+10 | 0.219589E+10 | 744.00 | 0.594840E+10 | 0.150431E+10 | 0.00 | 0.64 | 10-AUG-16:10 | 0.29 | 15-AUG-07:00 | 3977.93 | 10-AUG-16:10 | 3217.91 | 05-AUG-17:01 | 1048.60 | 22-AUG-17:10 | 1251.85 | 10-AUG-16:10 | 0.00 |
| September | 0.630626E+10 | 0.179391E+10 | 716.58 | 0.503387E+10 | 0.127239E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 7853.67 | 25-SEP-07:22 | 5933.85 | 30-SEP-06:52 | 2681.28 | 25-SEP-07:23 | 1693.68 | 30-SEP-06:52 | 0.00 |
| October | 0.525459E+10 | 0.144922E+10 | 721.03 | 0.439958E+10 | 0.855011E+09 | 0.00 | 1.00 | 20-OCT-08:12 | 0.00 | 20-OCT-05:13 | 7889.23 | 31-OCT-07:52 | 7170.83 | 21-OCT-08:42 | 2837.50 | 31-OCT-07:53 | 1729.96 | 22-OCT-08:62 | 0.00 |
| November | 0.357702E+10 | 0.950949E+09 | 614.18 | 0.309287E+10 | 0.484151E+09 | 0.00 | 1.00 | 01-NOV-08:12 | 0.00 | 01-NOV-05:13 | 7857.46 | 01-NOV-08:12 | 6992.28 | 21-NOV-22:52 | 2770.64 | 01-NOV-08:13 | 1737.01 | 06-NOV-09:02 | 0.00 |
| December | 0.185971E+10 | 0.474868E+09 | 422.99 | 0.160352E+10 | 0.256187E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 7914.06 | 24-DEC-13:32 | 7316.44 | 12-DEC-18:32 | 2900.50 | 06-DEC-11:43 | 1726.90 | 10-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.494265E+11 | 0.139415E+11 | 7230.38 | 0.410890E+11 | 0.833755E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.100291E+10 | 0.254385E+09 | 344.26 | 0.893161E+09 | 0.109750E+09 | 0.00 | 0.58 | 0.00 | 3759.07 | 3175.68 | 932.16 | 1117.02 | 0.00 | ||||||
| Maximum of Months | 0.745271E+10 | 0.219589E+10 | 744.00 | 0.594840E+10 | 0.150431E+10 | 0.00 | 1.00 | 0.29 | 8020.46 | 7316.44 | 3424.28 | 1892.42 | 0.00 |
Report: DXReportMonthly
For: SPLIT OFFICE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.174224E+10 | 0.439678E+09 | 204.50 | 0.160928E+10 | 0.132954E+09 | 0.00 | 1.00 | 03-JAN-07:01 | 0.00 | 01-JAN-00:10 | 9018.58 | 30-JAN-07:01 | 8343.66 | 17-JAN-07:01 | 2334.35 | 30-JAN-07:13 | 1915.39 | 30-JAN-07:02 | 0.00 |
| February | 0.183920E+10 | 0.467088E+09 | 204.78 | 0.165567E+10 | 0.183528E+09 | 0.00 | 1.00 | 01-FEB-07:01 | 0.00 | 01-FEB-00:10 | 9145.45 | 09-FEB-07:01 | 8418.26 | 10-FEB-07:01 | 2760.56 | 09-FEB-07:03 | 1915.36 | 24-FEB-07:01 | 0.00 |
| March | 0.232944E+10 | 0.609379E+09 | 254.37 | 0.214235E+10 | 0.187096E+09 | 0.00 | 1.00 | 01-MAR-07:01 | 0.00 | 01-MAR-00:10 | 9213.51 | 29-MAR-06:01 | 8492.78 | 27-MAR-06:01 | 3292.35 | 29-MAR-06:04 | 1999.42 | 02-MAR-07:01 | 0.00 |
| April | 0.259702E+10 | 0.696591E+09 | 293.65 | 0.234386E+10 | 0.253159E+09 | 0.00 | 1.00 | 03-APR-06:01 | 0.00 | 01-APR-00:10 | 9276.09 | 12-APR-06:01 | 8563.32 | 24-APR-06:01 | 3570.73 | 12-APR-06:04 | 1941.02 | 03-APR-06:01 | 0.00 |
| May | 0.430139E+10 | 0.120411E+10 | 526.79 | 0.378711E+10 | 0.514284E+09 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-01:40 | 9604.96 | 25-MAY-06:01 | 8717.48 | 08-MAY-06:01 | 5045.33 | 24-MAY-06:06 | 2114.45 | 23-MAY-06:01 | 0.00 |
| June | 0.523208E+10 | 0.146316E+10 | 630.15 | 0.420258E+10 | 0.102950E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-05:30 | 9604.63 | 08-JUN-06:11 | 8603.33 | 02-JUN-06:01 | 5608.20 | 08-JUN-06:08 | 2226.53 | 29-JUN-06:01 | 0.00 |
| July | 0.651633E+10 | 0.184137E+10 | 733.70 | 0.494901E+10 | 0.156732E+10 | 0.00 | 1.00 | 03-JUL-06:01 | 0.00 | 01-JUL-23:35 | 9535.35 | 06-JUL-06:06 | 8622.05 | 03-JUL-06:01 | 5854.92 | 27-JUL-06:07 | 2228.89 | 19-JUL-06:11 | 0.00 |
| August | 0.753560E+10 | 0.212291E+10 | 732.01 | 0.570463E+10 | 0.183097E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-16:01 | 9534.51 | 31-AUG-06:04 | 7464.70 | 07-AUG-06:01 | 5691.13 | 09-AUG-06:09 | 2248.62 | 16-AUG-06:01 | 0.00 |
| September | 0.600444E+10 | 0.164186E+10 | 688.58 | 0.466049E+10 | 0.134395E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-16:01 | 9607.25 | 25-SEP-06:01 | 7654.78 | 26-SEP-06:01 | 5594.18 | 28-SEP-06:08 | 2148.72 | 05-SEP-06:01 | 0.00 |
| October | 0.512483E+10 | 0.135501E+10 | 612.14 | 0.423743E+10 | 0.887395E+09 | 0.00 | 1.00 | 02-OCT-06:01 | 0.00 | 01-OCT-00:30 | 9606.20 | 31-OCT-06:01 | 8743.05 | 20-OCT-06:01 | 5100.54 | 18-OCT-06:07 | 2015.33 | 02-OCT-06:27 | 0.00 |
| November | 0.356445E+10 | 0.913808E+09 | 372.83 | 0.309277E+10 | 0.471686E+09 | 0.00 | 1.00 | 01-NOV-06:01 | 0.00 | 01-NOV-00:10 | 9558.53 | 03-NOV-06:01 | 8291.23 | 20-NOV-07:01 | 4245.32 | 03-NOV-06:07 | 1956.90 | 20-NOV-07:01 | 0.00 |
| December | 0.226070E+10 | 0.566032E+09 | 233.67 | 0.202276E+10 | 0.237936E+09 | 0.00 | 1.00 | 01-DEC-07:01 | 0.00 | 01-DEC-00:10 | 9142.21 | 11-DEC-07:01 | 8447.30 | 01-DEC-07:01 | 3090.87 | 06-DEC-07:04 | 1915.39 | 05-DEC-07:03 | 0.00 |
| Annual Sum or Average | 0.490477E+11 | 0.133210E+11 | 5487.17 | 0.404079E+11 | 0.863978E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.174224E+10 | 0.439678E+09 | 204.50 | 0.160928E+10 | 0.132954E+09 | 0.00 | 1.00 | 0.00 | 9018.58 | 7464.70 | 2334.35 | 1915.36 | 0.00 | ||||||
| Maximum of Months | 0.753560E+10 | 0.212291E+10 | 733.70 | 0.570463E+10 | 0.183097E+10 | 0.00 | 1.00 | 0.00 | 9607.25 | 8743.05 | 5854.92 | 2248.62 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.101006E+10 | 0.255987E+09 | 343.61 | 0.899771E+09 | 0.110287E+09 | 0.00 | 1.00 | 02-JAN-22:52 | 0.00 | 01-JAN-03:40 | 7474.95 | 30-JAN-11:22 | 7034.87 | 05-JAN-18:12 | 2150.19 | 30-JAN-11:23 | 1659.32 | 23-JAN-13:02 | 0.00 |
| February | 0.126227E+10 | 0.324732E+09 | 361.43 | 0.109598E+10 | 0.166288E+09 | 0.00 | 1.00 | 01-FEB-12:32 | 0.00 | 01-FEB-08:45 | 7480.32 | 07-FEB-09:42 | 7025.51 | 11-FEB-18:12 | 2269.32 | 07-FEB-09:43 | 1654.55 | 23-FEB-11:42 | 0.00 |
| March | 0.198375E+10 | 0.526422E+09 | 505.63 | 0.178085E+10 | 0.202901E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 7557.54 | 24-MAR-10:12 | 7014.95 | 06-MAR-12:32 | 2678.58 | 29-MAR-09:43 | 1654.36 | 29-MAR-09:42 | 0.00 |
| April | 0.302148E+10 | 0.824982E+09 | 621.65 | 0.264896E+10 | 0.372518E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 7690.20 | 30-APR-08:52 | 6938.45 | 06-APR-08:22 | 3203.53 | 30-APR-08:53 | 1707.19 | 23-APR-08:52 | 0.00 |
| May | 0.492537E+10 | 0.141090E+10 | 731.92 | 0.428407E+10 | 0.641307E+09 | 0.00 | 1.00 | 01-MAY-09:12 | 0.00 | 01-MAY-05:15 | 7655.15 | 01-MAY-09:12 | 6340.40 | 15-MAY-07:32 | 3113.79 | 01-MAY-09:13 | 1653.92 | 02-MAY-08:62 | 0.00 |
| June | 0.585762E+10 | 0.168767E+10 | 718.72 | 0.477526E+10 | 0.108236E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 6963.60 | 22-JUN-09:02 | 5731.28 | 22-JUN-09:02 | 1371.56 | 22-JUN-09:03 | 1816.58 | 22-JUN-09:02 | 0.00 |
| July | 0.700669E+10 | 0.206156E+10 | 744.00 | 0.561108E+10 | 0.139561E+10 | 0.00 | 0.57 | 30-JUL-17:10 | 0.24 | 03-JUL-05:50 | 3620.73 | 30-JUL-17:10 | 2997.83 | 21-JUL-17:01 | 913.79 | 30-JUL-17:10 | 1064.62 | 15-JUL-11:00 | 0.00 |
| August | 0.747553E+10 | 0.219740E+10 | 744.00 | 0.597013E+10 | 0.150540E+10 | 0.00 | 0.63 | 10-AUG-16:10 | 0.30 | 15-AUG-05:50 | 3752.66 | 10-AUG-16:10 | 3050.56 | 05-AUG-12:00 | 1032.06 | 22-AUG-17:20 | 1182.67 | 10-AUG-16:10 | 0.00 |
| September | 0.632266E+10 | 0.179496E+10 | 716.58 | 0.504950E+10 | 0.127316E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 7547.17 | 25-SEP-07:22 | 5700.87 | 30-SEP-06:52 | 2564.90 | 25-SEP-07:23 | 1628.04 | 30-SEP-06:52 | 0.00 |
| October | 0.528161E+10 | 0.145371E+10 | 721.03 | 0.442318E+10 | 0.858436E+09 | 0.00 | 1.00 | 20-OCT-08:12 | 0.00 | 20-OCT-05:13 | 7581.03 | 31-OCT-07:52 | 6891.27 | 21-OCT-08:42 | 2708.98 | 31-OCT-07:53 | 1662.76 | 22-OCT-08:62 | 0.00 |
| November | 0.357948E+10 | 0.950186E+09 | 612.71 | 0.309343E+10 | 0.486042E+09 | 0.00 | 1.00 | 01-NOV-08:12 | 0.00 | 01-NOV-05:13 | 7547.22 | 01-NOV-08:12 | 6715.34 | 21-NOV-22:52 | 2640.94 | 01-NOV-08:13 | 1669.13 | 06-NOV-09:02 | 0.00 |
| December | 0.184486E+10 | 0.470609E+09 | 422.52 | 0.158910E+10 | 0.255756E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 7604.11 | 24-DEC-13:32 | 7030.39 | 18-DEC-19:22 | 2729.28 | 24-DEC-13:33 | 1659.80 | 10-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.495714E+11 | 0.139591E+11 | 7243.79 | 0.412213E+11 | 0.835007E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.101006E+10 | 0.255987E+09 | 343.61 | 0.899771E+09 | 0.110287E+09 | 0.00 | 0.57 | 0.00 | 3620.73 | 2997.83 | 913.79 | 1064.62 | 0.00 | ||||||
| Maximum of Months | 0.747553E+10 | 0.219740E+10 | 744.00 | 0.597013E+10 | 0.150540E+10 | 0.00 | 1.00 | 0.30 | 7690.20 | 7034.87 | 3203.53 | 1816.58 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.106192E+10 | 0.268242E+09 | 349.35 | 0.947862E+09 | 0.114060E+09 | 0.00 | 1.00 | 01-JAN-22:52 | 0.00 | 01-JAN-09:20 | 6521.43 | 30-JAN-11:22 | 6134.71 | 05-JAN-18:12 | 1861.43 | 30-JAN-11:23 | 1448.30 | 23-JAN-13:02 | 0.00 |
| February | 0.126090E+10 | 0.322570E+09 | 357.96 | 0.109335E+10 | 0.167550E+09 | 0.00 | 1.00 | 01-FEB-12:32 | 0.00 | 01-FEB-08:45 | 6518.19 | 07-FEB-09:42 | 6135.14 | 12-FEB-17:12 | 1974.88 | 07-FEB-09:43 | 1443.17 | 23-FEB-11:42 | 0.00 |
| March | 0.185181E+10 | 0.488531E+09 | 499.78 | 0.165388E+10 | 0.197927E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 6597.38 | 29-MAR-09:42 | 6118.69 | 08-MAR-19:52 | 2382.60 | 29-MAR-09:43 | 1443.49 | 29-MAR-09:42 | 0.00 |
| April | 0.261937E+10 | 0.711936E+09 | 614.29 | 0.227079E+10 | 0.348580E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 6725.63 | 30-APR-08:52 | 6049.59 | 06-APR-08:22 | 2860.14 | 30-APR-08:53 | 1489.75 | 23-APR-08:52 | 0.00 |
| May | 0.408041E+10 | 0.116648E+10 | 731.19 | 0.348795E+10 | 0.592465E+09 | 0.00 | 1.00 | 01-MAY-09:12 | 0.00 | 01-MAY-05:15 | 6713.90 | 01-MAY-09:12 | 5510.76 | 15-MAY-07:32 | 2860.10 | 01-MAY-09:13 | 1443.15 | 02-MAY-08:62 | 0.00 |
| June | 0.484963E+10 | 0.139549E+10 | 718.92 | 0.385868E+10 | 0.990953E+09 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 6115.60 | 22-JUN-09:02 | 4906.53 | 22-JUN-09:02 | 1317.82 | 22-JUN-09:03 | 1590.43 | 22-JUN-09:02 | 0.00 |
| July | 0.575639E+10 | 0.169357E+10 | 744.00 | 0.447650E+10 | 0.127989E+10 | 0.00 | 0.54 | 19-JUL-17:00 | 0.24 | 03-JUL-05:00 | 2919.59 | 19-JUL-16:40 | 2351.93 | 21-JUL-17:12 | 820.49 | 19-JUL-16:01 | 874.47 | 19-JUL-17:00 | 0.00 |
| August | 0.607187E+10 | 0.178661E+10 | 744.00 | 0.469597E+10 | 0.137590E+10 | 0.00 | 0.57 | 10-AUG-16:10 | 0.30 | 15-AUG-05:00 | 3003.46 | 10-AUG-17:12 | 2370.79 | 05-AUG-17:12 | 903.11 | 22-AUG-17:20 | 945.23 | 10-AUG-16:10 | 0.00 |
| September | 0.517883E+10 | 0.146924E+10 | 716.67 | 0.401271E+10 | 0.116612E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 6605.78 | 25-SEP-07:22 | 4854.93 | 30-SEP-06:52 | 2318.68 | 25-SEP-07:23 | 1421.35 | 30-SEP-06:52 | 0.00 |
| October | 0.435852E+10 | 0.119804E+10 | 721.06 | 0.356820E+10 | 0.790323E+09 | 0.00 | 1.00 | 20-OCT-08:12 | 0.00 | 20-OCT-05:13 | 6622.57 | 31-OCT-07:52 | 6022.70 | 21-OCT-08:42 | 2396.19 | 31-OCT-07:53 | 1451.38 | 22-OCT-08:62 | 0.00 |
| November | 0.305152E+10 | 0.808359E+09 | 614.40 | 0.260148E+10 | 0.450046E+09 | 0.00 | 1.00 | 01-NOV-08:12 | 0.00 | 01-NOV-05:13 | 6598.37 | 01-NOV-08:12 | 5846.71 | 18-NOV-10:02 | 2326.05 | 01-NOV-08:13 | 1457.34 | 06-NOV-09:02 | 0.00 |
| December | 0.174645E+10 | 0.443600E+09 | 423.86 | 0.149846E+10 | 0.247988E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 6637.99 | 24-DEC-13:32 | 6132.21 | 18-DEC-19:22 | 2428.99 | 06-DEC-11:43 | 1448.27 | 10-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.418876E+11 | 0.117527E+11 | 7235.47 | 0.341658E+11 | 0.772180E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.106192E+10 | 0.268242E+09 | 349.35 | 0.947862E+09 | 0.114060E+09 | 0.00 | 0.54 | 0.00 | 2919.59 | 2351.93 | 820.49 | 874.47 | 0.00 | ||||||
| Maximum of Months | 0.607187E+10 | 0.178661E+10 | 744.00 | 0.469597E+10 | 0.137590E+10 | 0.00 | 1.00 | 0.30 | 6725.63 | 6135.14 | 2860.14 | 1590.43 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.106347E+10 | 0.268626E+09 | 350.11 | 0.949238E+09 | 0.114229E+09 | 0.00 | 1.00 | 01-JAN-22:52 | 0.00 | 01-JAN-09:20 | 6515.49 | 30-JAN-11:22 | 6129.26 | 05-JAN-18:12 | 1859.35 | 30-JAN-11:23 | 1447.33 | 23-JAN-13:02 | 0.00 |
| February | 0.126182E+10 | 0.322800E+09 | 357.89 | 0.109418E+10 | 0.167633E+09 | 0.00 | 1.00 | 01-FEB-12:32 | 0.00 | 01-FEB-08:45 | 6512.50 | 07-FEB-09:42 | 6129.69 | 12-FEB-17:12 | 1972.58 | 07-FEB-09:43 | 1441.90 | 23-FEB-11:42 | 0.00 |
| March | 0.185170E+10 | 0.488504E+09 | 499.82 | 0.165376E+10 | 0.197940E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 6591.74 | 29-MAR-09:42 | 6113.20 | 08-MAR-19:52 | 2379.41 | 29-MAR-09:43 | 1442.21 | 29-MAR-09:42 | 0.00 |
| April | 0.262174E+10 | 0.712571E+09 | 614.48 | 0.227298E+10 | 0.348755E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 6719.43 | 30-APR-08:52 | 6044.35 | 06-APR-08:22 | 2856.70 | 30-APR-08:53 | 1488.43 | 23-APR-08:52 | 0.00 |
| May | 0.408278E+10 | 0.116713E+10 | 731.22 | 0.349019E+10 | 0.592587E+09 | 0.00 | 1.00 | 01-MAY-09:12 | 0.00 | 01-MAY-05:15 | 6707.50 | 01-MAY-09:12 | 5505.53 | 15-MAY-07:32 | 2855.84 | 01-MAY-09:13 | 1441.86 | 02-MAY-08:62 | 0.00 |
| June | 0.485035E+10 | 0.139566E+10 | 718.92 | 0.385933E+10 | 0.991022E+09 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 6109.99 | 22-JUN-09:02 | 4902.31 | 22-JUN-09:02 | 1315.99 | 22-JUN-09:03 | 1589.00 | 22-JUN-09:02 | 0.00 |
| July | 0.575720E+10 | 0.169374E+10 | 744.00 | 0.447722E+10 | 0.127997E+10 | 0.00 | 0.54 | 19-JUL-17:00 | 0.24 | 03-JUL-05:00 | 2916.30 | 19-JUL-16:40 | 2349.14 | 21-JUL-17:12 | 819.94 | 19-JUL-16:01 | 873.42 | 19-JUL-17:00 | 0.00 |
| August | 0.607286E+10 | 0.178682E+10 | 744.00 | 0.469688E+10 | 0.137599E+10 | 0.00 | 0.57 | 10-AUG-16:10 | 0.30 | 15-AUG-05:00 | 3000.13 | 10-AUG-17:12 | 2368.73 | 05-AUG-17:12 | 902.65 | 22-AUG-17:20 | 944.42 | 10-AUG-16:10 | 0.00 |
| September | 0.517962E+10 | 0.146941E+10 | 716.67 | 0.401343E+10 | 0.116618E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 6599.89 | 25-SEP-07:22 | 4850.33 | 30-SEP-06:52 | 2316.71 | 25-SEP-07:23 | 1420.08 | 30-SEP-06:52 | 0.00 |
| October | 0.435991E+10 | 0.119838E+10 | 721.06 | 0.356944E+10 | 0.790468E+09 | 0.00 | 1.00 | 20-OCT-08:12 | 0.00 | 20-OCT-05:13 | 6616.65 | 31-OCT-07:52 | 6017.27 | 21-OCT-08:42 | 2394.06 | 31-OCT-07:53 | 1450.09 | 22-OCT-08:62 | 0.00 |
| November | 0.305299E+10 | 0.808724E+09 | 614.65 | 0.260279E+10 | 0.450203E+09 | 0.00 | 1.00 | 01-NOV-08:12 | 0.00 | 01-NOV-05:13 | 6592.43 | 01-NOV-08:12 | 5841.20 | 18-NOV-10:02 | 2323.91 | 01-NOV-08:13 | 1456.04 | 06-NOV-09:02 | 0.00 |
| December | 0.174722E+10 | 0.443787E+09 | 423.74 | 0.149914E+10 | 0.248077E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 6631.97 | 24-DEC-13:32 | 6126.75 | 18-DEC-19:22 | 2426.00 | 06-DEC-11:43 | 1446.98 | 10-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.419016E+11 | 0.117562E+11 | 7236.57 | 0.341786E+11 | 0.772306E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.106347E+10 | 0.268626E+09 | 350.11 | 0.949238E+09 | 0.114229E+09 | 0.00 | 0.54 | 0.00 | 2916.30 | 2349.14 | 819.94 | 873.42 | 0.00 | ||||||
| Maximum of Months | 0.607286E+10 | 0.178682E+10 | 744.00 | 0.469688E+10 | 0.137599E+10 | 0.00 | 1.00 | 0.30 | 6719.43 | 6129.69 | 2856.70 | 1589.00 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.168812E+10 | 0.423399E+09 | 400.90 | 0.154498E+10 | 0.143137E+09 | 0.00 | 1.00 | 01-JAN-14:32 | 0.00 | 01-JAN-09:30 | 6737.66 | 30-JAN-12:02 | 6393.17 | 26-JAN-16:42 | 1685.70 | 30-JAN-12:03 | 1477.56 | 23-JAN-12:32 | 0.00 |
| February | 0.178867E+10 | 0.455413E+09 | 400.11 | 0.159482E+10 | 0.193849E+09 | 0.00 | 1.00 | 01-FEB-11:22 | 0.00 | 01-FEB-08:45 | 6777.47 | 18-FEB-12:52 | 6391.91 | 14-FEB-14:02 | 1905.24 | 07-FEB-09:43 | 1515.83 | 23-FEB-11:52 | 0.00 |
| March | 0.228433E+10 | 0.600727E+09 | 528.86 | 0.207012E+10 | 0.214205E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 6860.50 | 29-MAR-09:42 | 6391.29 | 08-MAR-21:02 | 2393.79 | 29-MAR-09:43 | 1504.50 | 29-MAR-09:42 | 0.00 |
| April | 0.287591E+10 | 0.781578E+09 | 617.83 | 0.251462E+10 | 0.361295E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 7029.61 | 30-APR-08:52 | 6302.32 | 06-APR-08:22 | 3067.65 | 30-APR-08:53 | 1531.30 | 25-APR-07:42 | 0.00 |
| May | 0.408289E+10 | 0.116962E+10 | 730.17 | 0.349410E+10 | 0.588795E+09 | 0.00 | 1.00 | 01-MAY-09:22 | 0.00 | 01-MAY-05:15 | 6983.64 | 01-MAY-09:22 | 5756.40 | 15-MAY-07:42 | 2928.98 | 01-MAY-09:23 | 1514.51 | 01-MAY-09:23 | 0.00 |
| June | 0.473322E+10 | 0.136596E+10 | 718.93 | 0.375212E+10 | 0.981100E+09 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 6371.94 | 22-JUN-09:02 | 5122.75 | 22-JUN-09:02 | 1368.83 | 22-JUN-09:03 | 1657.42 | 22-JUN-09:02 | 0.00 |
| July | 0.572960E+10 | 0.169032E+10 | 744.00 | 0.445158E+10 | 0.127802E+10 | 0.00 | 0.53 | 30-JUL-17:10 | 0.23 | 03-JUL-06:00 | 3001.25 | 30-JUL-17:10 | 2325.11 | 21-JUL-17:12 | 812.48 | 30-JUL-17:10 | 878.44 | 30-JUL-17:10 | 0.00 |
| August | 0.621294E+10 | 0.183154E+10 | 744.00 | 0.483460E+10 | 0.137834E+10 | 0.00 | 0.56 | 10-AUG-16:10 | 0.30 | 15-AUG-07:10 | 3057.23 | 22-AUG-17:20 | 2407.62 | 05-AUG-17:01 | 885.62 | 22-AUG-17:20 | 967.01 | 10-AUG-16:10 | 0.00 |
| September | 0.562054E+10 | 0.159490E+10 | 716.67 | 0.443304E+10 | 0.118750E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 6863.50 | 25-SEP-07:22 | 5147.85 | 30-SEP-06:52 | 2323.51 | 25-SEP-07:23 | 1480.92 | 30-SEP-06:52 | 0.00 |
| October | 0.509280E+10 | 0.139754E+10 | 723.17 | 0.427235E+10 | 0.820457E+09 | 0.00 | 1.00 | 20-OCT-07:32 | 0.00 | 20-OCT-05:13 | 6851.57 | 31-OCT-07:42 | 6200.59 | 20-OCT-07:32 | 2238.86 | 31-OCT-07:43 | 1508.24 | 21-OCT-08:42 | 0.00 |
| November | 0.388880E+10 | 0.102596E+10 | 621.61 | 0.340212E+10 | 0.486678E+09 | 0.00 | 1.00 | 01-NOV-07:52 | 0.00 | 01-NOV-05:13 | 6860.41 | 01-NOV-07:52 | 6099.87 | 21-NOV-22:52 | 2320.47 | 01-NOV-07:53 | 1508.24 | 06-NOV-08:52 | 0.00 |
| December | 0.245164E+10 | 0.619079E+09 | 456.26 | 0.216591E+10 | 0.285732E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 6880.47 | 24-DEC-12:12 | 6393.26 | 30-DEC-10:42 | 2355.69 | 24-DEC-12:13 | 1476.39 | 02-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.464495E+11 | 0.129560E+11 | 7402.50 | 0.385303E+11 | 0.791911E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.168812E+10 | 0.423399E+09 | 400.11 | 0.154498E+10 | 0.143137E+09 | 0.00 | 0.53 | 0.00 | 3001.25 | 2325.11 | 812.48 | 878.44 | 0.00 | ||||||
| Maximum of Months | 0.621294E+10 | 0.183154E+10 | 744.00 | 0.483460E+10 | 0.137834E+10 | 0.00 | 1.00 | 0.30 | 7029.61 | 6393.26 | 3067.65 | 1657.42 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.176926E+10 | 0.443731E+09 | 400.10 | 0.162308E+10 | 0.146181E+09 | 0.00 | 1.00 | 01-JAN-14:32 | 0.00 | 01-JAN-09:30 | 6771.12 | 30-JAN-12:02 | 6439.58 | 02-JAN-13:32 | 1627.16 | 30-JAN-12:03 | 1488.35 | 23-JAN-12:32 | 0.00 |
| February | 0.188317E+10 | 0.479253E+09 | 399.89 | 0.168421E+10 | 0.198962E+09 | 0.00 | 1.00 | 01-FEB-11:22 | 0.00 | 01-FEB-08:45 | 6822.21 | 18-FEB-12:52 | 6440.89 | 11-FEB-13:32 | 1881.02 | 07-FEB-09:43 | 1527.00 | 23-FEB-11:52 | 0.00 |
| March | 0.242425E+10 | 0.636849E+09 | 531.28 | 0.220393E+10 | 0.220326E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 6903.59 | 24-MAR-10:12 | 6439.90 | 07-MAR-20:22 | 2348.21 | 29-MAR-09:43 | 1515.33 | 29-MAR-09:42 | 0.00 |
| April | 0.310448E+10 | 0.841764E+09 | 622.31 | 0.273123E+10 | 0.373248E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 7029.01 | 30-APR-08:52 | 6352.06 | 06-APR-08:22 | 2868.66 | 30-APR-08:53 | 1542.76 | 25-APR-07:42 | 0.00 |
| May | 0.441116E+10 | 0.125985E+10 | 731.44 | 0.380723E+10 | 0.603933E+09 | 0.00 | 1.00 | 01-MAY-09:22 | 0.00 | 01-MAY-05:15 | 6977.76 | 01-MAY-09:22 | 5849.02 | 15-MAY-07:42 | 2705.53 | 01-MAY-09:23 | 1525.56 | 01-MAY-09:22 | 0.00 |
| June | 0.506617E+10 | 0.145817E+10 | 718.89 | 0.406454E+10 | 0.100163E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 6398.61 | 22-JUN-09:02 | 5218.12 | 22-JUN-09:02 | 1304.84 | 22-JUN-09:03 | 1666.81 | 22-JUN-09:02 | 0.00 |
| July | 0.610091E+10 | 0.179517E+10 | 744.00 | 0.480191E+10 | 0.129900E+10 | 0.00 | 0.55 | 30-JUL-17:10 | 0.25 | 03-JUL-06:00 | 3195.52 | 30-JUL-17:10 | 2412.52 | 21-JUL-17:12 | 831.39 | 30-JUL-17:10 | 932.01 | 30-JUL-17:10 | 0.00 |
| August | 0.657349E+10 | 0.193284E+10 | 744.00 | 0.517579E+10 | 0.139770E+10 | 0.00 | 0.57 | 10-AUG-16:10 | 0.31 | 15-AUG-07:20 | 3165.33 | 22-AUG-17:20 | 2564.05 | 05-AUG-17:01 | 895.79 | 22-AUG-17:20 | 991.53 | 10-AUG-16:10 | 0.00 |
| September | 0.597439E+10 | 0.169088E+10 | 716.64 | 0.476754E+10 | 0.120685E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 6864.70 | 25-SEP-07:22 | 5246.00 | 30-SEP-06:52 | 2125.42 | 25-SEP-07:23 | 1491.24 | 30-SEP-06:52 | 0.00 |
| October | 0.544479E+10 | 0.148992E+10 | 723.11 | 0.460890E+10 | 0.835884E+09 | 0.00 | 1.00 | 20-OCT-07:32 | 0.00 | 20-OCT-05:13 | 6883.63 | 31-OCT-07:42 | 6257.73 | 20-OCT-07:32 | 2178.82 | 31-OCT-07:43 | 1519.00 | 21-OCT-08:42 | 0.00 |
| November | 0.416421E+10 | 0.109590E+10 | 621.58 | 0.366757E+10 | 0.496640E+09 | 0.00 | 1.00 | 01-NOV-07:52 | 0.00 | 01-NOV-05:13 | 6864.33 | 01-NOV-07:52 | 6148.13 | 21-NOV-22:52 | 2149.37 | 01-NOV-07:53 | 1518.28 | 06-NOV-08:52 | 0.00 |
| December | 0.259160E+10 | 0.653867E+09 | 456.66 | 0.229926E+10 | 0.292331E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 6918.35 | 24-DEC-12:12 | 6440.58 | 30-DEC-10:42 | 2323.53 | 24-DEC-12:13 | 1487.05 | 02-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.495079E+11 | 0.137782E+11 | 7409.90 | 0.414352E+11 | 0.807269E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.176926E+10 | 0.443731E+09 | 399.89 | 0.162308E+10 | 0.146181E+09 | 0.00 | 0.55 | 0.00 | 3165.33 | 2412.52 | 831.39 | 932.01 | 0.00 | ||||||
| Maximum of Months | 0.657349E+10 | 0.193284E+10 | 744.00 | 0.517579E+10 | 0.139770E+10 | 0.00 | 1.00 | 0.31 | 7029.01 | 6440.89 | 2868.66 | 1666.81 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.292388E+10 | 0.735690E+09 | 402.48 | 0.265478E+10 | 0.269101E+09 | 0.00 | 1.00 | 01-JAN-14:32 | 0.00 | 01-JAN-03:40 | 16700.41 | 30-JAN-12:02 | 15733.27 | 26-JAN-16:42 | 4495.51 | 30-JAN-10:12 | 3632.62 | 23-JAN-12:32 | 0.00 |
| February | 0.366421E+10 | 0.938540E+09 | 404.42 | 0.326914E+10 | 0.395070E+09 | 0.00 | 1.00 | 01-FEB-11:22 | 0.00 | 01-FEB-08:45 | 16721.33 | 18-FEB-12:52 | 15735.28 | 14-FEB-11:32 | 4869.93 | 07-FEB-09:42 | 3728.17 | 23-FEB-11:52 | 0.00 |
| March | 0.542476E+10 | 0.143230E+10 | 528.31 | 0.495375E+10 | 0.471014E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 16910.47 | 29-MAR-09:42 | 15722.25 | 07-MAR-20:22 | 6103.00 | 29-MAR-09:43 | 3702.08 | 29-MAR-09:42 | 0.00 |
| April | 0.723022E+10 | 0.197092E+10 | 619.00 | 0.640748E+10 | 0.822736E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 17364.26 | 30-APR-08:52 | 15467.71 | 06-APR-08:22 | 7868.04 | 30-APR-08:53 | 3760.80 | 25-APR-07:42 | 0.00 |
| May | 0.102111E+11 | 0.293581E+10 | 730.28 | 0.887992E+10 | 0.133121E+10 | 0.00 | 1.00 | 01-MAY-09:22 | 0.00 | 01-MAY-05:15 | 17250.45 | 01-MAY-09:22 | 14189.84 | 15-MAY-07:42 | 7508.18 | 01-MAY-09:23 | 3726.29 | 01-MAY-09:23 | 0.00 |
| June | 0.116282E+11 | 0.337005E+10 | 718.90 | 0.938500E+10 | 0.224318E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 15687.21 | 22-JUN-09:02 | 12582.69 | 22-JUN-09:02 | 3104.52 | 22-JUN-09:02 | 4079.32 | 22-JUN-09:02 | 0.00 |
| July | 0.136532E+11 | 0.404732E+10 | 744.00 | 0.107626E+11 | 0.289065E+10 | 0.00 | 0.57 | 30-JUL-16:10 | 0.19 | 03-JUL-06:00 | 7927.89 | 30-JUL-16:10 | 6448.26 | 21-JUL-16:30 | 2058.65 | 30-JUL-17:10 | 2356.76 | 30-JUL-16:10 | 0.00 |
| August | 0.142513E+11 | 0.422766E+10 | 744.00 | 0.111558E+11 | 0.309545E+10 | 0.00 | 0.61 | 10-AUG-16:10 | 0.23 | 15-AUG-07:10 | 8171.26 | 10-AUG-16:10 | 6528.94 | 10-AUG-16:10 | 2244.54 | 22-AUG-17:20 | 2581.92 | 10-AUG-16:10 | 0.00 |
| September | 0.123711E+11 | 0.354013E+10 | 716.06 | 0.975289E+10 | 0.261819E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 17032.89 | 25-SEP-07:22 | 12198.60 | 30-SEP-06:52 | 6486.94 | 25-SEP-07:23 | 3646.26 | 30-SEP-06:52 | 0.00 |
| October | 0.105473E+11 | 0.292583E+10 | 721.78 | 0.880451E+10 | 0.174282E+10 | 0.00 | 1.00 | 20-OCT-07:32 | 0.00 | 20-OCT-05:13 | 17201.33 | 31-OCT-07:42 | 15442.66 | 21-OCT-08:42 | 7155.89 | 31-OCT-07:43 | 3701.49 | 21-OCT-08:42 | 0.00 |
| November | 0.754373E+10 | 0.201212E+10 | 618.94 | 0.654139E+10 | 0.100233E+10 | 0.00 | 1.00 | 01-NOV-07:52 | 0.00 | 01-NOV-05:13 | 17179.55 | 01-NOV-07:52 | 14985.52 | 22-NOV-21:22 | 7063.17 | 01-NOV-07:53 | 3718.18 | 06-NOV-08:52 | 0.00 |
| December | 0.435399E+10 | 0.110859E+10 | 457.79 | 0.380394E+10 | 0.550053E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 17074.21 | 24-DEC-12:12 | 15743.12 | 30-DEC-10:42 | 6402.97 | 06-DEC-11:13 | 3632.99 | 10-DEC-09:32 | 0.00 |
| Annual Sum or Average | 0.103803E+12 | 0.292450E+11 | 7405.96 | 0.863712E+11 | 0.174318E+11 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.292388E+10 | 0.735690E+09 | 402.48 | 0.265478E+10 | 0.269101E+09 | 0.00 | 0.57 | 0.00 | 7927.89 | 6448.26 | 2058.65 | 2356.76 | 0.00 | ||||||
| Maximum of Months | 0.142513E+11 | 0.422766E+10 | 744.00 | 0.111558E+11 | 0.309545E+10 | 0.00 | 1.00 | 0.23 | 17364.26 | 15743.12 | 7868.04 | 4079.32 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.164251E+10 | 0.415778E+09 | 326.12 | 0.144571E+10 | 0.196796E+09 | 0.00 | 1.00 | 03-JAN-18:52 | 0.00 | 01-JAN-01:40 | 16297.77 | 30-JAN-11:22 | 15243.39 | 05-JAN-18:12 | 4990.89 | 30-JAN-11:22 | 3587.95 | 23-JAN-13:02 | 0.00 |
| February | 0.255782E+10 | 0.659148E+09 | 358.84 | 0.222102E+10 | 0.336793E+09 | 0.00 | 1.00 | 01-FEB-12:32 | 0.00 | 01-FEB-08:45 | 16273.99 | 08-FEB-22:22 | 15227.28 | 12-FEB-17:12 | 4983.01 | 07-FEB-09:42 | 3580.69 | 23-FEB-11:42 | 0.00 |
| March | 0.454750E+10 | 0.120506E+10 | 510.08 | 0.410520E+10 | 0.442300E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 16398.91 | 29-MAR-09:42 | 15218.61 | 04-MAR-21:52 | 6092.76 | 29-MAR-09:43 | 3585.30 | 29-MAR-09:42 | 0.00 |
| April | 0.671396E+10 | 0.183079E+10 | 617.67 | 0.591247E+10 | 0.801483E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 16746.46 | 30-APR-08:52 | 14983.04 | 06-APR-08:22 | 7369.78 | 30-APR-08:53 | 3692.60 | 23-APR-08:52 | 0.00 |
| May | 0.102134E+11 | 0.293144E+10 | 730.72 | 0.887415E+10 | 0.133929E+10 | 0.00 | 1.00 | 01-MAY-09:12 | 0.00 | 01-MAY-05:15 | 16727.44 | 01-MAY-09:12 | 13697.44 | 15-MAY-07:32 | 7348.29 | 01-MAY-09:13 | 3584.59 | 02-MAY-08:62 | 0.00 |
| June | 0.118639E+11 | 0.343005E+10 | 718.90 | 0.960218E+10 | 0.226173E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 15198.54 | 22-JUN-09:02 | 12163.51 | 22-JUN-09:02 | 3293.12 | 22-JUN-09:03 | 3951.42 | 22-JUN-09:02 | 0.00 |
| July | 0.137033E+11 | 0.405361E+10 | 744.00 | 0.108091E+11 | 0.289420E+10 | 0.00 | 0.58 | 21-JUL-16:30 | 0.19 | 03-JUL-06:00 | 7756.22 | 19-JUL-16:30 | 6496.23 | 21-JUL-16:30 | 2028.71 | 19-JUL-15:30 | 2296.58 | 19-JUL-16:40 | 0.00 |
| August | 0.139617E+11 | 0.413647E+10 | 744.00 | 0.108701E+11 | 0.309159E+10 | 0.00 | 0.62 | 10-AUG-16:10 | 0.24 | 15-AUG-07:00 | 8039.54 | 10-AUG-16:10 | 6352.28 | 10-AUG-16:10 | 2278.89 | 22-AUG-17:10 | 2535.46 | 10-AUG-16:10 | 0.00 |
| September | 0.114700E+11 | 0.328269E+10 | 716.06 | 0.889502E+10 | 0.257500E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 16515.29 | 25-SEP-07:22 | 11713.36 | 30-SEP-06:52 | 6465.96 | 25-SEP-07:23 | 3531.17 | 30-SEP-06:52 | 0.00 |
| October | 0.904689E+10 | 0.251375E+10 | 719.39 | 0.737059E+10 | 0.167630E+10 | 0.00 | 1.00 | 20-OCT-08:12 | 0.00 | 20-OCT-05:13 | 16656.25 | 31-OCT-07:52 | 14888.45 | 21-OCT-08:42 | 7148.01 | 31-OCT-07:53 | 3609.45 | 22-OCT-08:62 | 0.00 |
| November | 0.583716E+10 | 0.156328E+10 | 607.67 | 0.492483E+10 | 0.912338E+09 | 0.00 | 1.00 | 01-NOV-08:12 | 0.00 | 01-NOV-05:13 | 16620.78 | 01-NOV-08:12 | 14397.59 | 18-NOV-10:02 | 6972.35 | 01-NOV-08:13 | 3621.78 | 06-NOV-09:02 | 0.00 |
| December | 0.293547E+10 | 0.751426E+09 | 410.90 | 0.247764E+10 | 0.457825E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 16538.10 | 06-DEC-11:42 | 15236.63 | 18-DEC-19:22 | 6555.16 | 06-DEC-11:43 | 3599.26 | 10-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.944937E+11 | 0.267735E+11 | 7204.35 | 0.775080E+11 | 0.169856E+11 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.164251E+10 | 0.415778E+09 | 326.12 | 0.144571E+10 | 0.196796E+09 | 0.00 | 0.58 | 0.00 | 7756.22 | 6352.28 | 2028.71 | 2296.58 | 0.00 | ||||||
| Maximum of Months | 0.139617E+11 | 0.413647E+10 | 744.00 | 0.108701E+11 | 0.309159E+10 | 0.00 | 1.00 | 0.24 | 16746.46 | 15243.39 | 7369.78 | 3951.42 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.293884E+10 | 0.738405E+09 | 400.82 | 0.266985E+10 | 0.268995E+09 | 0.00 | 1.00 | 01-JAN-14:32 | 0.00 | 01-JAN-03:10 | 15957.12 | 30-JAN-12:02 | 15045.86 | 26-JAN-15:32 | 4452.32 | 30-JAN-12:03 | 3473.95 | 23-JAN-12:32 | 0.00 |
| February | 0.364972E+10 | 0.933441E+09 | 404.27 | 0.325531E+10 | 0.394411E+09 | 0.00 | 1.00 | 01-FEB-11:22 | 0.00 | 01-FEB-08:45 | 15999.32 | 07-FEB-09:42 | 15056.97 | 11-FEB-10:42 | 4855.26 | 07-FEB-09:43 | 3565.63 | 23-FEB-11:52 | 0.00 |
| March | 0.536803E+10 | 0.141629E+10 | 531.94 | 0.489957E+10 | 0.468458E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 16147.07 | 29-MAR-09:42 | 15032.49 | 07-MAR-20:22 | 5665.91 | 29-MAR-09:43 | 3540.00 | 29-MAR-09:42 | 0.00 |
| April | 0.730345E+10 | 0.198867E+10 | 624.39 | 0.647873E+10 | 0.824716E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 16555.84 | 30-APR-08:52 | 14834.57 | 06-APR-08:22 | 7293.62 | 30-APR-08:53 | 3599.28 | 25-APR-07:42 | 0.00 |
| May | 0.103202E+11 | 0.296230E+10 | 730.94 | 0.898873E+10 | 0.133149E+10 | 0.00 | 1.00 | 01-MAY-09:22 | 0.00 | 01-MAY-05:15 | 16428.95 | 01-MAY-09:22 | 13616.15 | 15-MAY-07:42 | 6831.49 | 01-MAY-09:23 | 3563.56 | 01-MAY-09:23 | 0.00 |
| June | 0.116606E+11 | 0.337296E+10 | 718.86 | 0.941793E+10 | 0.224265E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 14957.87 | 22-JUN-09:02 | 12162.69 | 22-JUN-09:02 | 3117.26 | 22-JUN-09:03 | 3895.05 | 22-JUN-09:02 | 0.00 |
| July | 0.136938E+11 | 0.405008E+10 | 744.00 | 0.108045E+11 | 0.288928E+10 | 0.00 | 0.57 | 30-JUL-16:10 | 0.20 | 03-JUL-06:00 | 7602.30 | 30-JUL-16:10 | 5998.69 | 21-JUL-16:01 | 2036.83 | 30-JUL-17:10 | 2258.46 | 30-JUL-16:10 | 0.00 |
| August | 0.143008E+11 | 0.423215E+10 | 744.00 | 0.112058E+11 | 0.309501E+10 | 0.00 | 0.60 | 10-AUG-16:10 | 0.24 | 15-AUG-05:00 | 7598.99 | 10-AUG-16:10 | 6204.63 | 16-AUG-12:00 | 2202.09 | 22-AUG-17:20 | 2405.96 | 10-AUG-16:10 | 0.00 |
| September | 0.124083E+11 | 0.354298E+10 | 716.14 | 0.979118E+10 | 0.261714E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 16299.29 | 25-SEP-07:22 | 11681.42 | 30-SEP-06:52 | 6154.70 | 25-SEP-07:23 | 3486.91 | 30-SEP-06:52 | 0.00 |
| October | 0.106079E+11 | 0.293546E+10 | 722.44 | 0.885939E+10 | 0.174853E+10 | 0.00 | 1.00 | 20-OCT-07:32 | 0.00 | 20-OCT-05:13 | 16459.56 | 31-OCT-07:42 | 14784.57 | 21-OCT-08:42 | 6793.31 | 31-OCT-07:43 | 3541.56 | 21-OCT-08:42 | 0.00 |
| November | 0.755338E+10 | 0.201061E+10 | 624.44 | 0.654776E+10 | 0.100562E+10 | 0.00 | 1.00 | 01-NOV-07:52 | 0.00 | 01-NOV-05:13 | 16435.47 | 01-NOV-07:52 | 14323.74 | 22-NOV-21:22 | 6690.06 | 01-NOV-07:53 | 3555.02 | 06-NOV-08:52 | 0.00 |
| December | 0.432134E+10 | 0.109868E+10 | 460.10 | 0.377454E+10 | 0.546800E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 16304.51 | 24-DEC-12:12 | 15054.75 | 27-DEC-17:12 | 5978.80 | 24-DEC-12:13 | 3474.41 | 10-DEC-09:32 | 0.00 |
| Annual Sum or Average | 0.104126E+12 | 0.292820E+11 | 7422.35 | 0.866933E+11 | 0.174331E+11 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.293884E+10 | 0.738405E+09 | 400.82 | 0.266985E+10 | 0.268995E+09 | 0.00 | 0.57 | 0.00 | 7598.99 | 5998.69 | 2036.83 | 2258.46 | 0.00 | ||||||
| Maximum of Months | 0.143008E+11 | 0.423215E+10 | 744.00 | 0.112058E+11 | 0.309501E+10 | 0.00 | 1.00 | 0.24 | 16555.84 | 15056.97 | 7293.62 | 3895.05 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.165519E+10 | 0.418509E+09 | 327.93 | 0.145695E+10 | 0.198247E+09 | 0.00 | 1.00 | 03-JAN-18:52 | 0.00 | 01-JAN-01:20 | 15558.85 | 30-JAN-11:22 | 14536.40 | 05-JAN-18:12 | 4929.39 | 30-JAN-11:23 | 3427.95 | 23-JAN-13:02 | 0.00 |
| February | 0.254324E+10 | 0.654653E+09 | 360.95 | 0.220736E+10 | 0.335881E+09 | 0.00 | 1.00 | 01-FEB-12:32 | 0.00 | 01-FEB-08:45 | 15540.53 | 08-FEB-22:22 | 14548.89 | 12-FEB-17:12 | 4803.63 | 08-FEB-22:23 | 3422.00 | 23-FEB-11:42 | 0.00 |
| March | 0.449214E+10 | 0.118979E+10 | 514.94 | 0.405249E+10 | 0.439653E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 15654.37 | 24-MAR-10:12 | 14526.76 | 08-MAR-19:52 | 5653.16 | 29-MAR-09:43 | 3423.10 | 29-MAR-09:42 | 0.00 |
| April | 0.678645E+10 | 0.184883E+10 | 622.04 | 0.598213E+10 | 0.804322E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 15962.38 | 30-APR-08:52 | 14344.80 | 06-APR-08:22 | 6849.44 | 30-APR-08:53 | 3530.32 | 23-APR-08:52 | 0.00 |
| May | 0.103235E+11 | 0.295771E+10 | 731.69 | 0.898348E+10 | 0.134000E+10 | 0.00 | 1.00 | 01-MAY-09:12 | 0.00 | 01-MAY-05:15 | 15898.27 | 01-MAY-09:12 | 13126.32 | 15-MAY-07:32 | 6695.32 | 01-MAY-09:13 | 3422.42 | 02-MAY-08:62 | 0.00 |
| June | 0.118968E+11 | 0.343226E+10 | 718.89 | 0.963539E+10 | 0.226144E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 14466.11 | 22-JUN-09:02 | 11745.02 | 22-JUN-09:02 | 3011.82 | 22-JUN-09:03 | 3766.60 | 22-JUN-09:02 | 0.00 |
| July | 0.137443E+11 | 0.405572E+10 | 744.00 | 0.108511E+11 | 0.289321E+10 | 0.00 | 0.57 | 30-JUL-16:10 | 0.20 | 03-JUL-05:40 | 7365.53 | 30-JUL-17:10 | 6026.51 | 21-JUL-16:30 | 1984.12 | 30-JUL-17:10 | 2183.34 | 21-JUL-14:30 | 0.00 |
| August | 0.140120E+11 | 0.414100E+10 | 744.00 | 0.109203E+11 | 0.309174E+10 | 0.00 | 0.60 | 10-AUG-16:10 | 0.25 | 15-AUG-05:50 | 7466.52 | 10-AUG-16:10 | 5920.79 | 04-AUG-13:00 | 2230.86 | 22-AUG-17:10 | 2359.46 | 10-AUG-16:10 | 0.00 |
| September | 0.115085E+11 | 0.328685E+10 | 716.08 | 0.893368E+10 | 0.257477E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 15779.60 | 25-SEP-07:22 | 11196.53 | 30-SEP-06:52 | 6128.38 | 25-SEP-07:23 | 3371.56 | 30-SEP-06:52 | 0.00 |
| October | 0.910929E+10 | 0.252557E+10 | 719.69 | 0.742515E+10 | 0.168414E+10 | 0.00 | 1.00 | 20-OCT-08:12 | 0.00 | 20-OCT-05:13 | 15914.80 | 31-OCT-07:52 | 14253.47 | 21-OCT-08:42 | 6761.28 | 31-OCT-07:53 | 3446.67 | 22-OCT-08:62 | 0.00 |
| November | 0.584455E+10 | 0.156242E+10 | 608.42 | 0.492728E+10 | 0.917277E+09 | 0.00 | 1.00 | 01-NOV-08:12 | 0.00 | 01-NOV-05:13 | 15882.67 | 01-NOV-08:12 | 13908.91 | 18-NOV-10:02 | 6563.28 | 01-NOV-08:13 | 3459.44 | 06-NOV-09:02 | 0.00 |
| December | 0.289938E+10 | 0.741225E+09 | 406.85 | 0.244320E+10 | 0.456178E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 15806.64 | 06-DEC-11:42 | 14550.12 | 19-DEC-13:02 | 6163.84 | 06-DEC-11:43 | 3437.26 | 10-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.948153E+11 | 0.268145E+11 | 7215.49 | 0.778185E+11 | 0.169969E+11 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.165519E+10 | 0.418509E+09 | 327.93 | 0.145695E+10 | 0.198247E+09 | 0.00 | 0.57 | 0.00 | 7365.53 | 5920.79 | 1984.12 | 2183.34 | 0.00 | ||||||
| Maximum of Months | 0.140120E+11 | 0.414100E+10 | 744.00 | 0.109203E+11 | 0.309174E+10 | 0.00 | 1.00 | 0.25 | 15962.38 | 14550.12 | 6849.44 | 3766.60 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.192538E+10 | 0.486531E+09 | 335.61 | 0.170796E+10 | 0.217418E+09 | 0.00 | 1.00 | 01-JAN-22:52 | 0.00 | 01-JAN-09:20 | 13515.35 | 30-JAN-11:22 | 12645.08 | 05-JAN-18:12 | 4265.95 | 30-JAN-11:23 | 2979.61 | 23-JAN-13:02 | 0.00 |
| February | 0.254173E+10 | 0.650646E+09 | 355.36 | 0.220164E+10 | 0.340091E+09 | 0.00 | 1.00 | 01-FEB-12:32 | 0.00 | 01-FEB-08:45 | 13486.67 | 08-FEB-22:22 | 12634.77 | 12-FEB-17:12 | 4283.40 | 08-FEB-22:23 | 2972.74 | 23-FEB-11:42 | 0.00 |
| March | 0.403556E+10 | 0.106344E+10 | 507.58 | 0.361759E+10 | 0.417965E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 13601.32 | 29-MAR-09:42 | 12627.46 | 04-MAR-21:52 | 5035.07 | 29-MAR-09:43 | 2975.53 | 29-MAR-09:42 | 0.00 |
| April | 0.562301E+10 | 0.152699E+10 | 616.56 | 0.489186E+10 | 0.731154E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 13890.25 | 30-APR-08:52 | 12445.68 | 06-APR-08:22 | 6134.46 | 30-APR-08:53 | 3064.38 | 23-APR-08:52 | 0.00 |
| May | 0.822671E+10 | 0.235506E+10 | 730.47 | 0.701811E+10 | 0.120859E+10 | 0.00 | 1.00 | 01-MAY-09:12 | 0.00 | 01-MAY-05:15 | 13891.13 | 01-MAY-09:12 | 11273.81 | 15-MAY-07:32 | 6140.66 | 01-MAY-09:13 | 2974.90 | 02-MAY-08:62 | 0.00 |
| June | 0.953077E+10 | 0.274894E+10 | 719.00 | 0.751191E+10 | 0.201886E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 12660.10 | 22-JUN-09:02 | 9971.99 | 22-JUN-09:02 | 2910.91 | 22-JUN-09:03 | 3285.56 | 22-JUN-09:02 | 0.00 |
| July | 0.109929E+11 | 0.324568E+10 | 744.00 | 0.840210E+10 | 0.259075E+10 | 0.00 | 0.51 | 19-JUL-16:40 | 0.20 | 03-JUL-05:00 | 5777.36 | 19-JUL-16:13 | 4541.24 | 21-JUL-17:01 | 1716.21 | 19-JUL-16:01 | 1723.08 | 19-JUL-16:50 | 0.00 |
| August | 0.111665E+11 | 0.330324E+10 | 744.00 | 0.840674E+10 | 0.275980E+10 | 0.00 | 0.54 | 10-AUG-16:10 | 0.25 | 15-AUG-05:00 | 5792.27 | 22-AUG-17:10 | 4388.50 | 10-AUG-16:10 | 1881.81 | 22-AUG-17:20 | 1842.68 | 10-AUG-16:10 | 0.00 |
| September | 0.931677E+10 | 0.265734E+10 | 716.11 | 0.700698E+10 | 0.230979E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 13713.49 | 25-SEP-07:22 | 9592.48 | 30-SEP-06:52 | 5418.81 | 25-SEP-07:23 | 2930.98 | 30-SEP-06:52 | 0.00 |
| October | 0.752816E+10 | 0.208184E+10 | 719.42 | 0.599997E+10 | 0.152819E+10 | 0.00 | 1.00 | 20-OCT-08:12 | 0.00 | 20-OCT-05:13 | 13804.07 | 31-OCT-07:52 | 12363.76 | 21-OCT-08:42 | 5848.50 | 31-OCT-07:53 | 2995.55 | 22-OCT-08:62 | 0.00 |
| November | 0.510365E+10 | 0.135986E+10 | 607.50 | 0.425640E+10 | 0.847255E+09 | 0.00 | 1.00 | 01-NOV-08:12 | 0.00 | 01-NOV-05:13 | 13777.18 | 01-NOV-08:12 | 11945.87 | 18-NOV-10:02 | 5717.43 | 01-NOV-08:13 | 3005.61 | 06-NOV-09:02 | 0.00 |
| December | 0.295139E+10 | 0.751262E+09 | 408.74 | 0.249204E+10 | 0.459350E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 13716.98 | 06-DEC-11:42 | 12631.11 | 16-DEC-18:42 | 5390.07 | 06-DEC-11:43 | 2986.82 | 10-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.789425E+11 | 0.222308E+11 | 7204.35 | 0.635133E+11 | 0.154292E+11 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.192538E+10 | 0.486531E+09 | 335.61 | 0.170796E+10 | 0.217418E+09 | 0.00 | 0.51 | 0.00 | 5777.36 | 4388.50 | 1716.21 | 1723.08 | 0.00 | ||||||
| Maximum of Months | 0.111665E+11 | 0.330324E+10 | 744.00 | 0.840674E+10 | 0.275980E+10 | 0.00 | 1.00 | 0.25 | 13891.13 | 12645.08 | 6140.66 | 3285.56 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.192901E+10 | 0.487396E+09 | 335.79 | 0.171121E+10 | 0.217799E+09 | 0.00 | 1.00 | 01-JAN-22:52 | 0.00 | 01-JAN-09:20 | 13502.32 | 30-JAN-11:22 | 12631.21 | 05-JAN-18:12 | 4260.37 | 30-JAN-11:23 | 2976.71 | 23-JAN-13:02 | 0.00 |
| February | 0.254577E+10 | 0.651642E+09 | 356.06 | 0.220528E+10 | 0.340492E+09 | 0.00 | 1.00 | 01-FEB-12:32 | 0.00 | 01-FEB-08:45 | 13473.39 | 08-FEB-22:22 | 12622.02 | 12-FEB-17:12 | 4279.81 | 08-FEB-22:23 | 2970.20 | 23-FEB-11:42 | 0.00 |
| March | 0.403603E+10 | 0.106357E+10 | 507.38 | 0.361814E+10 | 0.417890E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 13588.49 | 29-MAR-09:42 | 12614.42 | 04-MAR-21:52 | 5027.66 | 29-MAR-09:43 | 2972.61 | 29-MAR-09:42 | 0.00 |
| April | 0.562834E+10 | 0.152842E+10 | 616.56 | 0.489683E+10 | 0.731508E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 13877.02 | 30-APR-08:52 | 12433.79 | 06-APR-08:22 | 6126.55 | 30-APR-08:53 | 3061.45 | 23-APR-08:52 | 0.00 |
| May | 0.823132E+10 | 0.235633E+10 | 730.47 | 0.702250E+10 | 0.120882E+10 | 0.00 | 1.00 | 01-MAY-09:12 | 0.00 | 01-MAY-05:15 | 13878.15 | 01-MAY-09:12 | 11262.33 | 15-MAY-07:32 | 6131.16 | 01-MAY-09:13 | 2971.98 | 02-MAY-08:62 | 0.00 |
| June | 0.953237E+10 | 0.274934E+10 | 719.00 | 0.751338E+10 | 0.201900E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 12647.16 | 22-JUN-09:02 | 9962.87 | 22-JUN-09:02 | 2906.60 | 22-JUN-09:03 | 3282.27 | 22-JUN-09:02 | 0.00 |
| July | 0.109946E+11 | 0.324607E+10 | 744.00 | 0.840368E+10 | 0.259091E+10 | 0.00 | 0.51 | 19-JUL-16:40 | 0.20 | 03-JUL-05:00 | 5771.19 | 19-JUL-16:13 | 4535.77 | 21-JUL-17:01 | 1714.85 | 19-JUL-16:01 | 1720.78 | 19-JUL-16:50 | 0.00 |
| August | 0.111686E+11 | 0.330372E+10 | 744.00 | 0.840860E+10 | 0.275998E+10 | 0.00 | 0.54 | 10-AUG-16:10 | 0.25 | 15-AUG-05:00 | 5784.96 | 22-AUG-17:10 | 4383.79 | 10-AUG-16:10 | 1880.55 | 22-AUG-17:20 | 1840.86 | 10-AUG-16:10 | 0.00 |
| September | 0.931856E+10 | 0.265780E+10 | 716.11 | 0.700863E+10 | 0.230993E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 13700.12 | 25-SEP-07:22 | 9582.10 | 30-SEP-06:52 | 5413.75 | 25-SEP-07:23 | 2928.10 | 30-SEP-06:52 | 0.00 |
| October | 0.753135E+10 | 0.208267E+10 | 719.42 | 0.600281E+10 | 0.152854E+10 | 0.00 | 1.00 | 20-OCT-08:12 | 0.00 | 20-OCT-05:13 | 13790.59 | 31-OCT-07:52 | 12352.17 | 21-OCT-08:42 | 5842.56 | 31-OCT-07:53 | 2992.61 | 22-OCT-08:62 | 0.00 |
| November | 0.510798E+10 | 0.136097E+10 | 607.50 | 0.426026E+10 | 0.847720E+09 | 0.00 | 1.00 | 01-NOV-08:12 | 0.00 | 01-NOV-05:13 | 13763.84 | 01-NOV-08:12 | 11938.03 | 18-NOV-10:02 | 5711.37 | 01-NOV-08:13 | 3002.68 | 06-NOV-09:02 | 0.00 |
| December | 0.295363E+10 | 0.751802E+09 | 408.80 | 0.249405E+10 | 0.459576E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 13704.06 | 06-DEC-11:42 | 12617.93 | 16-DEC-18:42 | 5382.06 | 06-DEC-11:43 | 2983.90 | 10-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.789775E+11 | 0.222397E+11 | 7205.08 | 0.635454E+11 | 0.154322E+11 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.192901E+10 | 0.487396E+09 | 335.79 | 0.171121E+10 | 0.217799E+09 | 0.00 | 0.51 | 0.00 | 5771.19 | 4383.79 | 1714.85 | 1720.78 | 0.00 | ||||||
| Maximum of Months | 0.111686E+11 | 0.330372E+10 | 744.00 | 0.840860E+10 | 0.275998E+10 | 0.00 | 1.00 | 0.25 | 13878.15 | 12631.21 | 6131.16 | 3282.27 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.324488E+10 | 0.813544E+09 | 411.25 | 0.296119E+10 | 0.283693E+09 | 0.00 | 1.00 | 01-JAN-14:32 | 0.00 | 01-JAN-09:20 | 14000.51 | 30-JAN-12:02 | 13212.18 | 26-JAN-17:52 | 3830.07 | 30-JAN-12:03 | 3051.34 | 23-JAN-12:32 | 0.00 |
| February | 0.367240E+10 | 0.934809E+09 | 406.60 | 0.327601E+10 | 0.396389E+09 | 0.00 | 1.00 | 01-FEB-11:22 | 0.00 | 01-FEB-08:45 | 14029.36 | 18-FEB-12:52 | 13219.53 | 11-FEB-10:42 | 4227.87 | 07-FEB-09:43 | 3131.54 | 23-FEB-11:52 | 0.00 |
| March | 0.492809E+10 | 0.129425E+10 | 530.68 | 0.447950E+10 | 0.448589E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 14192.66 | 24-MAR-10:12 | 13206.25 | 07-MAR-20:22 | 5096.77 | 29-MAR-09:43 | 3108.61 | 29-MAR-09:42 | 0.00 |
| April | 0.614486E+10 | 0.166894E+10 | 618.83 | 0.539029E+10 | 0.754569E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 14572.44 | 30-APR-08:52 | 12999.14 | 06-APR-08:22 | 6622.96 | 30-APR-08:53 | 3157.73 | 25-APR-07:42 | 0.00 |
| May | 0.822438E+10 | 0.235961E+10 | 730.00 | 0.702421E+10 | 0.120017E+10 | 0.00 | 1.00 | 01-MAY-09:22 | 0.00 | 01-MAY-05:15 | 14495.92 | 01-MAY-09:22 | 11841.67 | 15-MAY-07:42 | 6358.21 | 01-MAY-09:23 | 3128.77 | 01-MAY-09:23 | 0.00 |
| June | 0.929083E+10 | 0.268742E+10 | 718.89 | 0.729326E+10 | 0.199757E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 13225.15 | 22-JUN-09:02 | 10427.26 | 22-JUN-09:02 | 3045.34 | 22-JUN-09:03 | 3432.41 | 22-JUN-09:02 | 0.00 |
| July | 0.109406E+11 | 0.323894E+10 | 744.00 | 0.835446E+10 | 0.258617E+10 | 0.00 | 0.50 | 30-JUL-16:10 | 0.19 | 03-JUL-06:00 | 5931.92 | 30-JUL-17:10 | 4481.97 | 21-JUL-17:12 | 1695.38 | 30-JUL-17:10 | 1746.55 | 30-JUL-16:10 | 0.00 |
| August | 0.114604E+11 | 0.339662E+10 | 744.00 | 0.869280E+10 | 0.276756E+10 | 0.00 | 0.53 | 10-AUG-16:10 | 0.24 | 15-AUG-07:20 | 5913.33 | 10-AUG-16:10 | 4562.06 | 10-AUG-16:10 | 1850.51 | 22-AUG-17:20 | 1889.39 | 10-AUG-16:10 | 0.00 |
| September | 0.102322E+11 | 0.292046E+10 | 716.11 | 0.786903E+10 | 0.236320E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 14306.22 | 25-SEP-07:22 | 10132.37 | 30-SEP-06:52 | 5474.01 | 25-SEP-07:23 | 3062.09 | 30-SEP-06:52 | 0.00 |
| October | 0.905032E+10 | 0.250065E+10 | 721.86 | 0.744441E+10 | 0.160591E+10 | 0.00 | 1.00 | 20-OCT-07:32 | 0.00 | 20-OCT-05:13 | 14423.36 | 31-OCT-07:42 | 12972.15 | 21-OCT-08:42 | 5904.16 | 31-OCT-07:43 | 3108.49 | 21-OCT-08:42 | 0.00 |
| November | 0.683599E+10 | 0.181458E+10 | 621.36 | 0.589272E+10 | 0.943270E+09 | 0.00 | 1.00 | 01-NOV-07:52 | 0.00 | 01-NOV-05:13 | 14409.88 | 01-NOV-07:52 | 12579.39 | 22-NOV-21:22 | 5842.56 | 01-NOV-07:53 | 3121.77 | 06-NOV-08:52 | 0.00 |
| December | 0.439469E+10 | 0.111236E+10 | 461.81 | 0.384691E+10 | 0.547780E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 14313.31 | 06-DEC-11:12 | 13221.24 | 16-DEC-11:12 | 5258.84 | 06-DEC-11:13 | 3050.47 | 10-DEC-09:32 | 0.00 |
| Annual Sum or Average | 0.884197E+11 | 0.247422E+11 | 7425.39 | 0.725248E+11 | 0.158949E+11 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.324488E+10 | 0.813544E+09 | 406.60 | 0.296119E+10 | 0.283693E+09 | 0.00 | 0.50 | 0.00 | 5913.33 | 4481.97 | 1695.38 | 1746.55 | 0.00 | ||||||
| Maximum of Months | 0.114604E+11 | 0.339662E+10 | 744.00 | 0.869280E+10 | 0.276756E+10 | 0.00 | 1.00 | 0.24 | 14572.44 | 13221.24 | 6622.96 | 3432.41 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.324598E+10 | 0.813706E+09 | 411.00 | 0.296441E+10 | 0.281572E+09 | 0.00 | 1.00 | 01-JAN-14:32 | 0.00 | 01-JAN-09:20 | 13987.87 | 30-JAN-12:02 | 13201.39 | 25-JAN-14:12 | 3815.27 | 30-JAN-12:03 | 3048.52 | 23-JAN-12:32 | 0.00 |
| February | 0.367215E+10 | 0.934639E+09 | 406.60 | 0.327813E+10 | 0.394016E+09 | 0.00 | 1.00 | 01-FEB-11:22 | 0.00 | 01-FEB-08:45 | 14016.63 | 07-FEB-09:42 | 13215.44 | 11-FEB-10:42 | 4211.85 | 07-FEB-09:43 | 3128.67 | 23-FEB-11:52 | 0.00 |
| March | 0.492591E+10 | 0.129356E+10 | 530.90 | 0.447995E+10 | 0.445958E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 14180.25 | 24-MAR-10:12 | 13201.76 | 07-MAR-12:12 | 5079.41 | 29-MAR-09:43 | 3105.70 | 29-MAR-09:42 | 0.00 |
| April | 0.614667E+10 | 0.166927E+10 | 618.83 | 0.539483E+10 | 0.751842E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:15 | 14559.70 | 30-APR-08:52 | 12988.97 | 06-APR-08:22 | 6608.52 | 30-APR-08:53 | 3155.28 | 25-APR-07:42 | 0.00 |
| May | 0.822508E+10 | 0.235960E+10 | 730.00 | 0.702827E+10 | 0.119681E+10 | 0.00 | 1.00 | 01-MAY-09:22 | 0.00 | 01-MAY-05:15 | 14482.92 | 01-MAY-09:22 | 11845.99 | 15-MAY-07:42 | 6341.36 | 01-MAY-09:23 | 3125.83 | 01-MAY-09:23 | 0.00 |
| June | 0.928847E+10 | 0.268650E+10 | 718.89 | 0.729436E+10 | 0.199411E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 13213.42 | 22-JUN-09:02 | 10431.82 | 22-JUN-09:02 | 3030.38 | 22-JUN-09:03 | 3429.28 | 22-JUN-09:02 | 0.00 |
| July | 0.109381E+11 | 0.323788E+10 | 744.00 | 0.835561E+10 | 0.258250E+10 | 0.00 | 0.50 | 30-JUL-16:10 | 0.19 | 03-JUL-06:00 | 5928.32 | 30-JUL-17:10 | 4476.73 | 21-JUL-16:12 | 1693.79 | 30-JUL-17:10 | 1745.54 | 30-JUL-16:10 | 0.00 |
| August | 0.114581E+11 | 0.339560E+10 | 744.00 | 0.869421E+10 | 0.276386E+10 | 0.00 | 0.53 | 10-AUG-16:10 | 0.24 | 15-AUG-07:20 | 5905.91 | 10-AUG-16:10 | 4557.10 | 10-AUG-16:10 | 1847.93 | 22-AUG-17:20 | 1886.95 | 10-AUG-16:10 | 0.00 |
| September | 0.102299E+11 | 0.291948E+10 | 716.11 | 0.787023E+10 | 0.235968E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 14294.11 | 25-SEP-07:22 | 10131.41 | 30-SEP-06:52 | 5463.97 | 25-SEP-07:23 | 3059.24 | 30-SEP-06:52 | 0.00 |
| October | 0.904924E+10 | 0.250004E+10 | 721.86 | 0.744666E+10 | 0.160258E+10 | 0.00 | 1.00 | 20-OCT-07:32 | 0.00 | 20-OCT-05:13 | 14410.83 | 31-OCT-07:42 | 12960.86 | 21-OCT-08:42 | 5893.13 | 31-OCT-07:43 | 3105.55 | 21-OCT-08:42 | 0.00 |
| November | 0.683568E+10 | 0.181425E+10 | 621.64 | 0.589548E+10 | 0.940202E+09 | 0.00 | 1.00 | 01-NOV-07:52 | 0.00 | 01-NOV-05:13 | 14397.29 | 01-NOV-07:52 | 12566.61 | 22-NOV-21:22 | 5830.59 | 01-NOV-07:53 | 3118.88 | 06-NOV-08:52 | 0.00 |
| December | 0.439319E+10 | 0.111184E+10 | 461.67 | 0.384812E+10 | 0.545075E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:15 | 14299.50 | 06-DEC-11:12 | 13215.23 | 16-DEC-11:12 | 5241.49 | 06-DEC-11:13 | 3047.63 | 10-DEC-09:32 | 0.00 |
| Annual Sum or Average | 0.884085E+11 | 0.247364E+11 | 7425.50 | 0.725503E+11 | 0.158582E+11 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.324598E+10 | 0.813706E+09 | 406.60 | 0.296441E+10 | 0.281572E+09 | 0.00 | 0.50 | 0.00 | 5905.91 | 4476.73 | 1693.79 | 1745.54 | 0.00 | ||||||
| Maximum of Months | 0.114581E+11 | 0.339560E+10 | 744.00 | 0.869421E+10 | 0.276386E+10 | 0.00 | 1.00 | 0.24 | 14559.70 | 13215.44 | 6608.52 | 3429.28 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.105103E+10 | 0.259876E+09 | 249.93 | 0.954572E+09 | 96462497.28 | 0.00 | 1.00 | 01-JAN-14:32 | 0.00 | 01-JAN-00:10 | 9112.60 | 30-JAN-12:02 | 8724.83 | 31-JAN-16:02 | 2784.31 | 30-JAN-10:12 | 1973.14 | 23-JAN-12:32 | 0.00 |
| February | 0.155075E+10 | 0.396725E+09 | 319.95 | 0.139204E+10 | 0.158709E+09 | 0.00 | 1.00 | 01-FEB-11:22 | 0.00 | 01-FEB-03:30 | 9115.61 | 07-FEB-09:42 | 8776.20 | 26-FEB-16:32 | 2777.08 | 07-FEB-09:42 | 2026.42 | 23-FEB-11:52 | 0.00 |
| March | 0.258831E+10 | 0.685952E+09 | 499.23 | 0.237379E+10 | 0.214515E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 9203.97 | 29-MAR-09:42 | 8687.34 | 07-MAR-15:22 | 3242.06 | 29-MAR-09:43 | 2012.16 | 29-MAR-09:42 | 0.00 |
| April | 0.376141E+10 | 0.103086E+10 | 617.11 | 0.335546E+10 | 0.405955E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:05 | 9465.71 | 30-APR-08:52 | 8403.03 | 14-APR-09:42 | 4406.29 | 30-APR-08:53 | 2042.25 | 25-APR-07:42 | 0.00 |
| May | 0.561007E+10 | 0.161895E+10 | 730.19 | 0.491880E+10 | 0.691269E+09 | 0.00 | 1.00 | 01-MAY-09:22 | 0.00 | 01-MAY-05:15 | 9390.39 | 01-MAY-09:22 | 7634.74 | 15-MAY-07:42 | 4124.61 | 01-MAY-09:23 | 2025.22 | 01-MAY-09:23 | 0.00 |
| June | 0.644570E+10 | 0.187277E+10 | 718.93 | 0.525730E+10 | 0.118840E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 8553.46 | 22-JUN-09:02 | 6760.49 | 22-JUN-09:02 | 1792.98 | 22-JUN-09:02 | 2220.78 | 22-JUN-09:02 | 0.00 |
| July | 0.767154E+10 | 0.227567E+10 | 744.00 | 0.613078E+10 | 0.154076E+10 | 0.00 | 0.65 | 30-JUL-16:10 | 0.15 | 03-JUL-06:00 | 4939.72 | 30-JUL-16:10 | 4095.96 | 21-JUL-16:12 | 1164.18 | 30-JUL-17:10 | 1451.77 | 30-JUL-16:10 | 0.00 |
| August | 0.797865E+10 | 0.236760E+10 | 744.00 | 0.632790E+10 | 0.165075E+10 | 0.00 | 0.69 | 10-AUG-16:10 | 0.20 | 15-AUG-06:00 | 5070.42 | 10-AUG-16:10 | 4142.71 | 10-AUG-16:10 | 1270.63 | 22-AUG-17:10 | 1582.92 | 10-AUG-16:10 | 0.00 |
| September | 0.676128E+10 | 0.193939E+10 | 716.06 | 0.538395E+10 | 0.137732E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 9322.57 | 25-SEP-07:22 | 6418.60 | 30-SEP-06:52 | 3743.01 | 25-SEP-07:22 | 1982.51 | 30-SEP-06:52 | 0.00 |
| October | 0.557591E+10 | 0.155331E+10 | 721.53 | 0.468291E+10 | 0.893001E+09 | 0.00 | 1.00 | 20-OCT-07:32 | 0.00 | 20-OCT-05:13 | 9435.38 | 31-OCT-07:42 | 8387.07 | 21-OCT-08:42 | 4290.83 | 31-OCT-07:43 | 2011.00 | 21-OCT-08:42 | 0.00 |
| November | 0.375449E+10 | 0.100623E+10 | 614.11 | 0.326460E+10 | 0.489886E+09 | 0.00 | 1.00 | 01-NOV-07:52 | 0.00 | 01-NOV-05:13 | 9403.54 | 01-NOV-07:52 | 8112.64 | 22-NOV-21:22 | 4171.42 | 01-NOV-07:53 | 2022.98 | 06-NOV-08:52 | 0.00 |
| December | 0.185848E+10 | 0.472238E+09 | 383.64 | 0.162616E+10 | 0.232319E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-04:50 | 9294.73 | 24-DEC-12:12 | 8727.33 | 28-DEC-15:42 | 3566.64 | 06-DEC-11:13 | 1975.25 | 10-DEC-09:32 | 0.00 |
| Annual Sum or Average | 0.546076E+11 | 0.154796E+11 | 7058.68 | 0.456683E+11 | 0.893935E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.105103E+10 | 0.259876E+09 | 249.93 | 0.954572E+09 | 96462497.28 | 0.00 | 0.65 | 0.00 | 4939.72 | 4095.96 | 1164.18 | 1451.77 | 0.00 | ||||||
| Maximum of Months | 0.797865E+10 | 0.236760E+10 | 744.00 | 0.632790E+10 | 0.165075E+10 | 0.00 | 1.00 | 0.20 | 9465.71 | 8776.20 | 4406.29 | 2220.78 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.478839E+09 | 0.119285E+09 | 164.84 | 0.418413E+09 | 60425377.35 | 0.00 | 1.00 | 03-JAN-18:52 | 0.00 | 01-JAN-00:10 | 8962.67 | 30-JAN-11:22 | 8353.93 | 05-JAN-18:12 | 2836.66 | 30-JAN-11:22 | 1965.28 | 23-JAN-13:02 | 0.00 |
| February | 0.100750E+10 | 0.260230E+09 | 269.39 | 0.878197E+09 | 0.129304E+09 | 0.00 | 1.00 | 01-FEB-12:32 | 0.00 | 01-FEB-02:30 | 8972.75 | 08-FEB-22:22 | 8491.85 | 24-FEB-17:02 | 2881.56 | 08-FEB-22:22 | 1961.70 | 23-FEB-11:42 | 0.00 |
| March | 0.213767E+10 | 0.569666E+09 | 478.73 | 0.193777E+10 | 0.199893E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 9004.06 | 29-MAR-09:42 | 8338.48 | 04-MAR-21:52 | 3360.84 | 29-MAR-09:43 | 1964.11 | 29-MAR-09:42 | 0.00 |
| April | 0.349000E+10 | 0.957477E+09 | 614.51 | 0.309418E+10 | 0.395819E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:05 | 9209.27 | 30-APR-08:52 | 8197.01 | 06-APR-08:22 | 4169.35 | 30-APR-08:53 | 2024.47 | 23-APR-08:52 | 0.00 |
| May | 0.561140E+10 | 0.161707E+10 | 730.69 | 0.491542E+10 | 0.695979E+09 | 0.00 | 1.00 | 01-MAY-09:12 | 0.00 | 01-MAY-05:15 | 9169.03 | 01-MAY-09:12 | 7415.56 | 15-MAY-07:32 | 4060.05 | 01-MAY-09:13 | 1964.03 | 02-MAY-08:62 | 0.00 |
| June | 0.656743E+10 | 0.190404E+10 | 718.89 | 0.536986E+10 | 0.119758E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 8350.62 | 22-JUN-09:02 | 6592.21 | 22-JUN-09:02 | 1819.32 | 22-JUN-09:03 | 2167.91 | 22-JUN-09:02 | 0.00 |
| July | 0.769457E+10 | 0.227863E+10 | 744.00 | 0.615206E+10 | 0.154251E+10 | 0.00 | 0.65 | 21-JUL-16:12 | 0.15 | 03-JUL-06:00 | 4758.97 | 30-JUL-16:10 | 4115.09 | 21-JUL-16:30 | 1139.74 | 30-JUL-17:10 | 1420.96 | 21-JUL-16:12 | 0.00 |
| August | 0.782248E+10 | 0.231965E+10 | 744.00 | 0.617242E+10 | 0.165006E+10 | 0.00 | 0.70 | 10-AUG-16:10 | 0.20 | 15-AUG-05:00 | 4977.41 | 10-AUG-16:10 | 4026.04 | 10-AUG-16:10 | 1289.75 | 22-AUG-17:10 | 1552.40 | 10-AUG-16:10 | 0.00 |
| September | 0.629000E+10 | 0.180594E+10 | 716.00 | 0.493139E+10 | 0.135861E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 9108.07 | 25-SEP-07:22 | 6239.25 | 30-SEP-06:52 | 3726.34 | 25-SEP-07:22 | 1935.09 | 30-SEP-06:52 | 0.00 |
| October | 0.479495E+10 | 0.133945E+10 | 718.78 | 0.393279E+10 | 0.862165E+09 | 0.00 | 1.00 | 20-OCT-08:12 | 0.00 | 20-OCT-05:13 | 9200.04 | 31-OCT-07:52 | 8151.75 | 21-OCT-08:42 | 4218.34 | 31-OCT-07:53 | 1978.09 | 22-OCT-08:62 | 0.00 |
| November | 0.287518E+10 | 0.774711E+09 | 596.72 | 0.243020E+10 | 0.444978E+09 | 0.00 | 1.00 | 01-NOV-08:12 | 0.00 | 01-NOV-05:13 | 9153.10 | 01-NOV-08:12 | 7850.55 | 18-NOV-10:02 | 4016.12 | 01-NOV-08:13 | 1986.04 | 06-NOV-09:02 | 0.00 |
| December | 0.115531E+10 | 0.296002E+09 | 322.30 | 0.971333E+09 | 0.183980E+09 | 0.00 | 1.00 | 01-DEC-21:12 | 0.00 | 01-DEC-04:00 | 9086.63 | 06-DEC-11:42 | 8351.46 | 18-DEC-19:22 | 3607.89 | 06-DEC-11:43 | 1973.21 | 10-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.499253E+11 | 0.142422E+11 | 6818.85 | 0.412040E+11 | 0.872130E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.478839E+09 | 0.119285E+09 | 164.84 | 0.418413E+09 | 60425377.35 | 0.00 | 0.65 | 0.00 | 4758.97 | 4026.04 | 1139.74 | 1420.96 | 0.00 | ||||||
| Maximum of Months | 0.782248E+10 | 0.231965E+10 | 744.00 | 0.617242E+10 | 0.165006E+10 | 0.00 | 1.00 | 0.20 | 9209.27 | 8491.85 | 4218.34 | 2167.91 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.105148E+10 | 0.259477E+09 | 250.32 | 0.954899E+09 | 96584040.20 | 0.00 | 1.00 | 01-JAN-14:32 | 0.00 | 01-JAN-00:10 | 8578.81 | 30-JAN-12:02 | 8201.71 | 31-JAN-14:52 | 2589.48 | 30-JAN-10:12 | 1859.62 | 23-JAN-12:32 | 0.00 |
| February | 0.153859E+10 | 0.392829E+09 | 319.29 | 0.138035E+10 | 0.158243E+09 | 0.00 | 1.00 | 01-FEB-11:22 | 0.00 | 01-FEB-03:20 | 8594.69 | 07-FEB-09:42 | 8253.25 | 26-FEB-15:22 | 2558.03 | 07-FEB-09:42 | 1909.41 | 23-FEB-11:52 | 0.00 |
| March | 0.255647E+10 | 0.676906E+09 | 499.26 | 0.234349E+10 | 0.212976E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 8645.53 | 29-MAR-09:42 | 8192.15 | 16-MAR-13:12 | 3033.91 | 29-MAR-09:43 | 1895.86 | 29-MAR-09:42 | 0.00 |
| April | 0.380061E+10 | 0.103989E+10 | 622.36 | 0.339295E+10 | 0.407658E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:05 | 8887.01 | 30-APR-08:52 | 7948.27 | 06-APR-08:22 | 4000.64 | 30-APR-08:53 | 1926.59 | 25-APR-07:42 | 0.00 |
| May | 0.567160E+10 | 0.163261E+10 | 731.17 | 0.497878E+10 | 0.692818E+09 | 0.00 | 1.00 | 01-MAY-09:22 | 0.00 | 01-MAY-05:15 | 8803.68 | 01-MAY-09:22 | 7220.64 | 15-MAY-07:42 | 3657.10 | 01-MAY-09:22 | 1908.50 | 01-MAY-09:23 | 0.00 |
| June | 0.646834E+10 | 0.187397E+10 | 718.89 | 0.527880E+10 | 0.118954E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 8023.30 | 22-JUN-09:02 | 6474.53 | 22-JUN-09:02 | 1712.17 | 22-JUN-09:03 | 2087.72 | 22-JUN-09:02 | 0.00 |
| July | 0.769628E+10 | 0.227535E+10 | 744.00 | 0.615534E+10 | 0.154094E+10 | 0.00 | 0.65 | 30-JUL-16:10 | 0.16 | 03-JUL-06:00 | 4688.12 | 30-JUL-16:10 | 3883.82 | 30-JUL-14:00 | 1150.61 | 30-JUL-17:10 | 1384.12 | 21-JUL-14:30 | 0.00 |
| August | 0.800823E+10 | 0.236802E+10 | 744.00 | 0.635663E+10 | 0.165160E+10 | 0.00 | 0.68 | 16-AUG-12:00 | 0.21 | 15-AUG-05:00 | 4663.82 | 10-AUG-16:10 | 3985.24 | 16-AUG-12:00 | 1243.97 | 22-AUG-17:20 | 1458.88 | 10-AUG-16:10 | 0.00 |
| September | 0.678541E+10 | 0.194017E+10 | 716.11 | 0.540733E+10 | 0.137808E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 8793.06 | 25-SEP-07:22 | 6062.49 | 30-SEP-06:52 | 3592.39 | 25-SEP-07:23 | 1868.14 | 30-SEP-06:52 | 0.00 |
| October | 0.561148E+10 | 0.155796E+10 | 722.56 | 0.471351E+10 | 0.897967E+09 | 0.00 | 1.00 | 20-OCT-07:32 | 0.00 | 20-OCT-05:13 | 8897.18 | 31-OCT-07:42 | 7904.73 | 21-OCT-08:42 | 4002.84 | 31-OCT-07:43 | 1895.14 | 21-OCT-08:42 | 0.00 |
| November | 0.375929E+10 | 0.100458E+10 | 618.81 | 0.326595E+10 | 0.493338E+09 | 0.00 | 1.00 | 01-NOV-07:52 | 0.00 | 01-NOV-05:13 | 8865.82 | 01-NOV-07:52 | 7633.86 | 22-NOV-21:22 | 3870.93 | 01-NOV-07:53 | 1906.07 | 06-NOV-08:52 | 0.00 |
| December | 0.183974E+10 | 0.466593E+09 | 386.18 | 0.160873E+10 | 0.231008E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-04:40 | 8747.75 | 24-DEC-12:12 | 8209.42 | 28-DEC-15:42 | 3278.32 | 24-DEC-12:13 | 1861.21 | 10-DEC-09:32 | 0.00 |
| Annual Sum or Average | 0.547875E+11 | 0.154884E+11 | 7072.95 | 0.458368E+11 | 0.895075E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.105148E+10 | 0.259477E+09 | 250.32 | 0.954899E+09 | 96584040.20 | 0.00 | 0.65 | 0.00 | 4663.82 | 3883.82 | 1150.61 | 1384.12 | 0.00 | ||||||
| Maximum of Months | 0.800823E+10 | 0.236802E+10 | 744.00 | 0.635663E+10 | 0.165160E+10 | 0.00 | 1.00 | 0.21 | 8897.18 | 8253.25 | 4002.84 | 2087.72 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.474255E+09 | 0.118077E+09 | 165.62 | 0.413872E+09 | 60383507.07 | 0.00 | 1.00 | 03-JAN-18:52 | 0.00 | 01-JAN-00:10 | 8423.44 | 30-JAN-11:22 | 7824.04 | 05-JAN-18:12 | 2623.13 | 30-JAN-11:23 | 1849.58 | 23-JAN-13:02 | 0.00 |
| February | 0.992342E+09 | 0.256195E+09 | 270.41 | 0.864561E+09 | 0.127782E+09 | 0.00 | 1.00 | 01-FEB-12:32 | 0.00 | 01-FEB-02:20 | 8444.34 | 08-FEB-22:22 | 7853.47 | 12-FEB-17:12 | 2896.62 | 08-FEB-22:23 | 1846.64 | 05-FEB-10:02 | 0.00 |
| March | 0.210405E+10 | 0.560579E+09 | 479.10 | 0.190615E+10 | 0.197899E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 8446.06 | 24-MAR-10:12 | 7842.85 | 08-MAR-19:52 | 3039.02 | 29-MAR-09:43 | 1847.58 | 29-MAR-09:42 | 0.00 |
| April | 0.352830E+10 | 0.966644E+09 | 620.77 | 0.313099E+10 | 0.397307E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:05 | 8632.60 | 30-APR-08:52 | 7750.51 | 06-APR-08:22 | 3778.18 | 30-APR-08:53 | 1906.56 | 23-APR-08:52 | 0.00 |
| May | 0.567269E+10 | 0.163034E+10 | 731.83 | 0.497574E+10 | 0.696947E+09 | 0.00 | 1.00 | 01-MAY-09:12 | 0.00 | 01-MAY-05:15 | 8575.93 | 01-MAY-09:12 | 7003.88 | 15-MAY-07:32 | 3593.22 | 01-MAY-09:13 | 1847.54 | 02-MAY-08:62 | 0.00 |
| June | 0.658954E+10 | 0.190444E+10 | 718.92 | 0.539143E+10 | 0.119810E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 7818.88 | 22-JUN-09:02 | 6307.50 | 22-JUN-09:02 | 1660.30 | 22-JUN-09:03 | 2034.48 | 22-JUN-09:02 | 0.00 |
| July | 0.771878E+10 | 0.227763E+10 | 744.00 | 0.617660E+10 | 0.154217E+10 | 0.00 | 0.66 | 21-JUL-14:30 | 0.16 | 03-JUL-05:50 | 4508.02 | 30-JUL-16:10 | 3785.64 | 21-JUL-12:10 | 1125.68 | 30-JUL-17:10 | 1366.69 | 21-JUL-14:30 | 0.00 |
| August | 0.785179E+10 | 0.231991E+10 | 744.00 | 0.620129E+10 | 0.165050E+10 | 0.00 | 0.68 | 10-AUG-16:10 | 0.21 | 15-AUG-05:00 | 4570.36 | 10-AUG-16:10 | 3808.02 | 04-AUG-13:00 | 1260.12 | 22-AUG-17:10 | 1428.23 | 10-AUG-16:10 | 0.00 |
| September | 0.631413E+10 | 0.180752E+10 | 716.06 | 0.495491E+10 | 0.135922E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 8577.07 | 25-SEP-07:22 | 5883.61 | 30-SEP-06:52 | 3561.78 | 25-SEP-07:23 | 1820.42 | 30-SEP-06:52 | 0.00 |
| October | 0.483044E+10 | 0.134540E+10 | 720.25 | 0.396261E+10 | 0.867833E+09 | 0.00 | 1.00 | 20-OCT-08:12 | 0.00 | 20-OCT-05:13 | 8664.22 | 31-OCT-07:52 | 7693.62 | 21-OCT-08:42 | 3912.43 | 31-OCT-07:53 | 1861.15 | 22-OCT-08:62 | 0.00 |
| November | 0.287491E+10 | 0.772848E+09 | 602.25 | 0.242656E+10 | 0.448346E+09 | 0.00 | 1.00 | 01-NOV-08:12 | 0.00 | 01-NOV-05:13 | 8617.46 | 01-NOV-08:12 | 7461.54 | 18-NOV-10:02 | 3705.21 | 01-NOV-08:13 | 1869.39 | 06-NOV-09:02 | 0.00 |
| December | 0.113416E+10 | 0.290196E+09 | 324.73 | 0.951477E+09 | 0.182688E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-04:00 | 8534.57 | 24-DEC-13:32 | 7847.21 | 19-DEC-16:52 | 3310.64 | 06-DEC-11:43 | 1856.33 | 10-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.500854E+11 | 0.142498E+11 | 6837.94 | 0.413562E+11 | 0.872918E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.474255E+09 | 0.118077E+09 | 165.62 | 0.413872E+09 | 60383507.07 | 0.00 | 0.66 | 0.00 | 4508.02 | 3785.64 | 1125.68 | 1366.69 | 0.00 | ||||||
| Maximum of Months | 0.785179E+10 | 0.231991E+10 | 744.00 | 0.620129E+10 | 0.165050E+10 | 0.00 | 1.00 | 0.21 | 8664.22 | 7853.47 | 3912.43 | 2034.48 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.524457E+09 | 0.130701E+09 | 223.04 | 0.455621E+09 | 68836350.62 | 0.00 | 1.00 | 03-JAN-18:52 | 0.00 | 01-JAN-00:10 | 7528.43 | 30-JAN-11:22 | 7015.87 | 05-JAN-18:12 | 2422.90 | 30-JAN-11:23 | 1654.63 | 23-JAN-13:02 | 0.00 |
| February | 0.964403E+09 | 0.247862E+09 | 316.40 | 0.831891E+09 | 0.132511E+09 | 0.00 | 1.00 | 01-FEB-12:32 | 0.00 | 01-FEB-04:20 | 7537.23 | 08-FEB-22:22 | 7020.08 | 12-FEB-17:12 | 2506.95 | 08-FEB-22:23 | 1650.68 | 23-FEB-11:42 | 0.00 |
| March | 0.186336E+10 | 0.494844E+09 | 506.59 | 0.167306E+10 | 0.190297E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 7570.51 | 29-MAR-09:42 | 7015.76 | 04-MAR-21:52 | 2788.29 | 29-MAR-09:43 | 1652.40 | 29-MAR-09:42 | 0.00 |
| April | 0.292408E+10 | 0.800028E+09 | 615.48 | 0.256386E+10 | 0.360219E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:05 | 7739.92 | 30-APR-08:52 | 6912.13 | 06-APR-08:22 | 3458.62 | 30-APR-08:53 | 1703.90 | 23-APR-08:52 | 0.00 |
| May | 0.458515E+10 | 0.131963E+10 | 730.92 | 0.396009E+10 | 0.625057E+09 | 0.00 | 1.00 | 01-MAY-09:12 | 0.00 | 01-MAY-05:15 | 7710.47 | 01-MAY-09:12 | 6247.32 | 15-MAY-07:32 | 3386.90 | 01-MAY-09:13 | 1652.32 | 02-MAY-08:62 | 0.00 |
| June | 0.535452E+10 | 0.155096E+10 | 718.89 | 0.429421E+10 | 0.106031E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 7038.68 | 22-JUN-09:02 | 5515.06 | 22-JUN-09:02 | 1654.15 | 22-JUN-09:03 | 1825.61 | 22-JUN-09:02 | 0.00 |
| July | 0.627443E+10 | 0.185719E+10 | 744.00 | 0.490549E+10 | 0.136894E+10 | 0.00 | 0.57 | 21-JUL-16:12 | 0.16 | 03-JUL-06:00 | 3526.92 | 30-JUL-17:10 | 2954.82 | 21-JUL-16:30 | 932.61 | 19-JUL-15:30 | 1054.98 | 21-JUL-14:40 | 0.00 |
| August | 0.635847E+10 | 0.188530E+10 | 744.00 | 0.489873E+10 | 0.145975E+10 | 0.00 | 0.61 | 10-AUG-16:10 | 0.21 | 15-AUG-05:00 | 3631.28 | 10-AUG-16:10 | 2856.90 | 10-AUG-16:10 | 1038.95 | 22-AUG-17:10 | 1147.09 | 10-AUG-16:10 | 0.00 |
| September | 0.516943E+10 | 0.148154E+10 | 715.94 | 0.396043E+10 | 0.120900E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 7662.36 | 25-SEP-07:22 | 5246.26 | 30-SEP-06:52 | 3180.92 | 25-SEP-07:23 | 1628.08 | 30-SEP-06:52 | 0.00 |
| October | 0.401315E+10 | 0.111721E+10 | 718.08 | 0.323116E+10 | 0.781997E+09 | 0.00 | 1.00 | 20-OCT-08:12 | 0.00 | 20-OCT-05:13 | 7727.57 | 31-OCT-07:52 | 6870.50 | 21-OCT-08:42 | 3455.42 | 31-OCT-07:53 | 1664.14 | 22-OCT-08:62 | 0.00 |
| November | 0.249364E+10 | 0.669106E+09 | 603.17 | 0.208125E+10 | 0.412391E+09 | 0.00 | 1.00 | 01-NOV-08:12 | 0.00 | 01-NOV-05:13 | 7691.19 | 01-NOV-08:12 | 6638.73 | 18-NOV-10:02 | 3293.34 | 01-NOV-08:13 | 1670.62 | 06-NOV-09:02 | 0.00 |
| December | 0.112561E+10 | 0.287070E+09 | 381.78 | 0.937419E+09 | 0.188187E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:03 | 7640.33 | 06-DEC-11:42 | 7014.53 | 19-DEC-16:52 | 2998.66 | 06-DEC-11:43 | 1659.88 | 10-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.416507E+11 | 0.118414E+11 | 7018.30 | 0.337932E+11 | 0.785750E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.524457E+09 | 0.130701E+09 | 223.04 | 0.455621E+09 | 68836350.62 | 0.00 | 0.57 | 0.00 | 3526.92 | 2856.90 | 932.61 | 1054.98 | 0.00 | ||||||
| Maximum of Months | 0.635847E+10 | 0.188530E+10 | 744.00 | 0.490549E+10 | 0.145975E+10 | 0.00 | 1.00 | 0.21 | 7739.92 | 7020.08 | 3458.62 | 1825.61 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.526067E+09 | 0.131093E+09 | 222.17 | 0.457099E+09 | 68967693.98 | 0.00 | 1.00 | 03-JAN-18:52 | 0.00 | 01-JAN-00:10 | 7510.37 | 30-JAN-11:22 | 6996.90 | 05-JAN-18:12 | 2416.55 | 30-JAN-11:23 | 1650.73 | 23-JAN-13:02 | 0.00 |
| February | 0.965582E+09 | 0.248140E+09 | 314.89 | 0.833037E+09 | 0.132545E+09 | 0.00 | 1.00 | 01-FEB-12:32 | 0.00 | 01-FEB-04:20 | 7519.41 | 08-FEB-22:22 | 7003.36 | 12-FEB-17:12 | 2501.75 | 08-FEB-22:23 | 1646.91 | 23-FEB-11:42 | 0.00 |
| March | 0.186398E+10 | 0.494996E+09 | 506.65 | 0.167369E+10 | 0.190285E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 7551.79 | 29-MAR-09:42 | 6998.95 | 04-MAR-21:52 | 2778.56 | 29-MAR-09:43 | 1648.47 | 29-MAR-09:42 | 0.00 |
| April | 0.292762E+10 | 0.800961E+09 | 615.59 | 0.256718E+10 | 0.360438E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:05 | 7720.72 | 30-APR-08:52 | 6896.35 | 06-APR-08:22 | 3447.32 | 30-APR-08:53 | 1699.87 | 23-APR-08:52 | 0.00 |
| May | 0.458811E+10 | 0.132038E+10 | 730.92 | 0.396293E+10 | 0.625181E+09 | 0.00 | 1.00 | 01-MAY-09:12 | 0.00 | 01-MAY-05:15 | 7686.65 | 01-MAY-09:12 | 6232.63 | 15-MAY-07:32 | 3355.73 | 01-MAY-09:13 | 1648.39 | 02-MAY-08:62 | 0.00 |
| June | 0.535575E+10 | 0.155118E+10 | 718.89 | 0.429532E+10 | 0.106043E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 7021.31 | 22-JUN-09:02 | 5503.05 | 22-JUN-09:02 | 1647.61 | 22-JUN-09:03 | 1821.18 | 22-JUN-09:02 | 0.00 |
| July | 0.627561E+10 | 0.185732E+10 | 744.00 | 0.490655E+10 | 0.136906E+10 | 0.00 | 0.57 | 21-JUL-16:12 | 0.16 | 03-JUL-06:00 | 3521.99 | 30-JUL-17:10 | 2948.98 | 21-JUL-16:30 | 931.59 | 19-JUL-15:30 | 1055.22 | 21-JUL-14:40 | 0.00 |
| August | 0.635982E+10 | 0.188548E+10 | 744.00 | 0.489993E+10 | 0.145988E+10 | 0.00 | 0.61 | 10-AUG-16:10 | 0.21 | 15-AUG-05:00 | 3623.40 | 10-AUG-16:10 | 2849.93 | 10-AUG-16:10 | 1037.70 | 22-AUG-17:10 | 1144.57 | 10-AUG-16:10 | 0.00 |
| September | 0.517072E+10 | 0.148179E+10 | 715.94 | 0.396162E+10 | 0.120911E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 7644.28 | 25-SEP-07:22 | 5232.80 | 30-SEP-06:52 | 3173.44 | 25-SEP-07:23 | 1624.21 | 30-SEP-06:52 | 0.00 |
| October | 0.401538E+10 | 0.111774E+10 | 718.25 | 0.323309E+10 | 0.782286E+09 | 0.00 | 1.00 | 20-OCT-08:12 | 0.00 | 20-OCT-05:13 | 7709.35 | 31-OCT-07:52 | 6855.18 | 21-OCT-08:42 | 3446.93 | 31-OCT-07:53 | 1660.19 | 22-OCT-08:62 | 0.00 |
| November | 0.249651E+10 | 0.669816E+09 | 603.19 | 0.208377E+10 | 0.412735E+09 | 0.00 | 1.00 | 01-NOV-08:12 | 0.00 | 01-NOV-05:13 | 7673.23 | 01-NOV-08:12 | 6630.40 | 18-NOV-10:02 | 3284.46 | 01-NOV-08:13 | 1666.69 | 06-NOV-09:02 | 0.00 |
| December | 0.112661E+10 | 0.287303E+09 | 381.27 | 0.938311E+09 | 0.188296E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:03 | 7621.45 | 06-DEC-11:42 | 6998.05 | 19-DEC-16:52 | 2988.12 | 06-DEC-11:43 | 1655.96 | 10-DEC-10:02 | 0.00 |
| Annual Sum or Average | 0.416718E+11 | 0.118462E+11 | 7015.77 | 0.338125E+11 | 0.785922E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.526067E+09 | 0.131093E+09 | 222.17 | 0.457099E+09 | 68967693.98 | 0.00 | 0.57 | 0.00 | 3521.99 | 2849.93 | 931.59 | 1055.22 | 0.00 | ||||||
| Maximum of Months | 0.635982E+10 | 0.188548E+10 | 744.00 | 0.490655E+10 | 0.145988E+10 | 0.00 | 1.00 | 0.21 | 7720.72 | 7003.36 | 3447.32 | 1821.18 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.114882E+10 | 0.284198E+09 | 343.22 | 0.104069E+10 | 0.108127E+09 | 0.00 | 1.00 | 01-JAN-14:32 | 0.00 | 01-JAN-00:30 | 7710.33 | 30-JAN-12:02 | 7361.62 | 31-JAN-14:52 | 2274.93 | 30-JAN-10:12 | 1672.34 | 23-JAN-12:32 | 0.00 |
| February | 0.153059E+10 | 0.389893E+09 | 381.78 | 0.136649E+10 | 0.164099E+09 | 0.00 | 1.00 | 01-FEB-11:22 | 0.00 | 01-FEB-05:50 | 7720.67 | 07-FEB-09:42 | 7357.14 | 26-FEB-15:22 | 2404.61 | 07-FEB-09:43 | 1716.98 | 23-FEB-11:52 | 0.00 |
| March | 0.232335E+10 | 0.613645E+09 | 525.32 | 0.211737E+10 | 0.205983E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 7793.24 | 24-MAR-10:12 | 7332.89 | 07-MAR-15:22 | 2798.91 | 29-MAR-09:43 | 1704.75 | 29-MAR-09:42 | 0.00 |
| April | 0.319864E+10 | 0.874526E+09 | 617.94 | 0.282766E+10 | 0.370983E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:05 | 8011.20 | 30-APR-08:52 | 7126.07 | 06-APR-08:22 | 3683.19 | 30-APR-08:53 | 1731.74 | 25-APR-07:42 | 0.00 |
| May | 0.458347E+10 | 0.132144E+10 | 729.81 | 0.396322E+10 | 0.620254E+09 | 0.00 | 1.00 | 01-MAY-09:22 | 0.00 | 01-MAY-05:15 | 7954.40 | 01-MAY-09:22 | 6474.83 | 15-MAY-07:42 | 3479.34 | 01-MAY-09:23 | 1715.79 | 01-MAY-09:23 | 0.00 |
| June | 0.523066E+10 | 0.151877E+10 | 718.90 | 0.418039E+10 | 0.105027E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 7261.19 | 22-JUN-09:02 | 5694.30 | 22-JUN-09:02 | 1712.12 | 22-JUN-09:03 | 1883.41 | 22-JUN-09:02 | 0.00 |
| July | 0.625050E+10 | 0.185392E+10 | 744.00 | 0.488359E+10 | 0.136690E+10 | 0.00 | 0.58 | 30-JUL-16:10 | 0.16 | 03-JUL-06:00 | 3698.86 | 30-JUL-16:10 | 2944.16 | 21-JUL-16:01 | 951.42 | 30-JUL-17:10 | 1098.61 | 30-JUL-16:10 | 0.00 |
| August | 0.651677E+10 | 0.193430E+10 | 744.00 | 0.505498E+10 | 0.146178E+10 | 0.00 | 0.61 | 10-AUG-16:10 | 0.21 | 15-AUG-05:00 | 3725.76 | 10-AUG-16:10 | 3020.70 | 16-AUG-14:00 | 1023.57 | 22-AUG-17:20 | 1178.21 | 10-AUG-16:10 | 0.00 |
| September | 0.564793E+10 | 0.161795E+10 | 715.94 | 0.441676E+10 | 0.123118E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 7897.28 | 25-SEP-07:22 | 5441.97 | 30-SEP-06:52 | 3217.41 | 25-SEP-07:23 | 1679.73 | 30-SEP-06:52 | 0.00 |
| October | 0.480612E+10 | 0.133505E+10 | 722.00 | 0.398926E+10 | 0.816857E+09 | 0.00 | 1.00 | 20-OCT-07:32 | 0.00 | 20-OCT-05:13 | 7982.92 | 31-OCT-07:42 | 7113.43 | 21-OCT-08:42 | 3539.16 | 31-OCT-07:43 | 1704.73 | 21-OCT-08:42 | 0.00 |
| November | 0.338993E+10 | 0.904964E+09 | 622.19 | 0.292946E+10 | 0.460471E+09 | 0.00 | 1.00 | 01-NOV-07:52 | 0.00 | 01-NOV-05:13 | 7960.96 | 01-NOV-07:52 | 6874.25 | 22-NOV-21:22 | 3448.04 | 01-NOV-07:53 | 1713.64 | 06-NOV-08:52 | 0.00 |
| December | 0.186116E+10 | 0.471079E+09 | 441.29 | 0.162294E+10 | 0.238227E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:03 | 7863.64 | 24-DEC-12:12 | 7375.39 | 28-DEC-15:42 | 2947.08 | 06-DEC-11:13 | 1673.36 | 10-DEC-09:32 | 0.00 |
| Annual Sum or Average | 0.464879E+11 | 0.131197E+11 | 7306.39 | 0.383928E+11 | 0.809513E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.114882E+10 | 0.284198E+09 | 343.22 | 0.104069E+10 | 0.108127E+09 | 0.00 | 0.58 | 0.00 | 3698.86 | 2944.16 | 951.42 | 1098.61 | 0.00 | ||||||
| Maximum of Months | 0.651677E+10 | 0.193430E+10 | 744.00 | 0.505498E+10 | 0.146178E+10 | 0.00 | 1.00 | 0.21 | 8011.20 | 7375.39 | 3683.19 | 1883.41 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.115029E+10 | 0.284519E+09 | 343.21 | 0.104213E+10 | 0.108155E+09 | 0.00 | 1.00 | 01-JAN-14:32 | 0.00 | 01-JAN-00:30 | 7692.48 | 30-JAN-12:02 | 7349.17 | 31-JAN-14:52 | 2269.58 | 30-JAN-10:12 | 1668.52 | 23-JAN-12:32 | 0.00 |
| February | 0.153227E+10 | 0.390262E+09 | 381.95 | 0.136810E+10 | 0.164169E+09 | 0.00 | 1.00 | 01-FEB-11:22 | 0.00 | 01-FEB-05:40 | 7703.56 | 07-FEB-09:42 | 7343.01 | 26-FEB-15:22 | 2396.81 | 07-FEB-09:43 | 1713.01 | 23-FEB-11:52 | 0.00 |
| March | 0.232386E+10 | 0.613739E+09 | 525.21 | 0.211781E+10 | 0.206046E+09 | 0.00 | 1.00 | 01-MAR-07:32 | 0.00 | 01-MAR-06:13 | 7774.59 | 24-MAR-10:12 | 7316.48 | 07-MAR-15:22 | 2788.90 | 29-MAR-09:43 | 1700.85 | 29-MAR-09:42 | 0.00 |
| April | 0.320206E+10 | 0.875405E+09 | 618.31 | 0.283088E+10 | 0.371180E+09 | 0.00 | 1.00 | 01-APR-09:42 | 0.00 | 01-APR-05:05 | 7992.11 | 30-APR-08:52 | 7110.49 | 06-APR-08:22 | 3671.41 | 30-APR-08:53 | 1727.86 | 25-APR-07:42 | 0.00 |
| May | 0.458646E+10 | 0.132221E+10 | 729.89 | 0.396605E+10 | 0.620404E+09 | 0.00 | 1.00 | 01-MAY-09:22 | 0.00 | 01-MAY-05:15 | 7934.89 | 01-MAY-09:22 | 6460.33 | 15-MAY-07:42 | 3464.63 | 01-MAY-09:23 | 1711.88 | 01-MAY-09:23 | 0.00 |
| June | 0.523191E+10 | 0.151902E+10 | 718.90 | 0.418152E+10 | 0.105039E+10 | 0.00 | 1.00 | 22-JUN-09:02 | 0.00 | 22-JUN-07:43 | 7243.97 | 22-JUN-09:02 | 5682.44 | 22-JUN-09:02 | 1705.73 | 22-JUN-09:03 | 1879.03 | 22-JUN-09:02 | 0.00 |
| July | 0.625170E+10 | 0.185408E+10 | 744.00 | 0.488467E+10 | 0.136703E+10 | 0.00 | 0.58 | 30-JUL-16:10 | 0.16 | 03-JUL-06:00 | 3694.68 | 30-JUL-16:10 | 2948.45 | 30-JUL-14:00 | 950.91 | 30-JUL-17:10 | 1097.26 | 30-JUL-16:10 | 0.00 |
| August | 0.651811E+10 | 0.193448E+10 | 744.00 | 0.505620E+10 | 0.146192E+10 | 0.00 | 0.61 | 10-AUG-16:10 | 0.21 | 15-AUG-05:00 | 3717.94 | 10-AUG-16:10 | 3025.07 | 16-AUG-14:00 | 1022.43 | 22-AUG-17:20 | 1175.71 | 10-AUG-16:10 | 0.00 |
| September | 0.564919E+10 | 0.161815E+10 | 715.94 | 0.441791E+10 | 0.123127E+10 | 0.00 | 1.00 | 25-SEP-07:22 | 0.00 | 25-SEP-05:13 | 7879.41 | 25-SEP-07:22 | 5428.58 | 30-SEP-06:52 | 3210.10 | 25-SEP-07:23 | 1675.90 | 30-SEP-06:52 | 0.00 |
| October | 0.480817E+10 | 0.133547E+10 | 722.00 | 0.399107E+10 | 0.817097E+09 | 0.00 | 1.00 | 20-OCT-07:32 | 0.00 | 20-OCT-05:13 | 7964.81 | 31-OCT-07:42 | 7097.18 | 21-OCT-08:42 | 3531.16 | 31-OCT-07:43 | 1700.84 | 21-OCT-08:42 | 0.00 |
| November | 0.339230E+10 | 0.905487E+09 | 622.47 | 0.293154E+10 | 0.460752E+09 | 0.00 | 1.00 | 01-NOV-07:52 | 0.00 | 01-NOV-05:13 | 7943.00 | 01-NOV-07:52 | 6857.65 | 22-NOV-21:22 | 3439.57 | 01-NOV-07:53 | 1709.71 | 06-NOV-08:52 | 0.00 |
| December | 0.186254E+10 | 0.471357E+09 | 441.54 | 0.162426E+10 | 0.238281E+09 | 0.00 | 1.00 | 01-DEC-09:42 | 0.00 | 01-DEC-06:03 | 7845.18 | 24-DEC-12:12 | 7358.67 | 28-DEC-15:42 | 2936.50 | 06-DEC-11:13 | 1669.51 | 10-DEC-09:32 | 0.00 |
| Annual Sum or Average | 0.465088E+11 | 0.131242E+11 | 7307.42 | 0.384121E+11 | 0.809669E+10 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.115029E+10 | 0.284519E+09 | 343.21 | 0.104213E+10 | 0.108155E+09 | 0.00 | 0.58 | 0.00 | 3694.68 | 2948.45 | 950.91 | 1097.26 | 0.00 | ||||||
| Maximum of Months | 0.651811E+10 | 0.193448E+10 | 744.00 | 0.505620E+10 | 0.146192E+10 | 0.00 | 1.00 | 0.21 | 7992.11 | 7358.67 | 3671.41 | 1879.03 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 106.93 | 50.23 | 56.71 | 168.34 | 88.06 | 0.00 | 0.00 | 0.00 |
| February | 100.84 | 41.50 | 59.35 | 171.64 | 73.13 | 0.00 | 0.00 | 0.00 |
| March | 81.19 | 20.99 | 60.20 | 157.79 | 53.33 | 0.00 | 0.00 | 0.00 |
| April | 66.35 | 8.25 | 58.10 | 157.38 | 28.91 | 0.00 | 0.00 | 0.00 |
| May | 55.13 | 0.93 | 54.20 | 182.80 | 5.01 | 0.00 | 0.00 | 0.00 |
| June | 51.86 | 0.09 | 51.77 | 195.69 | 0.56 | 0.00 | 0.00 | 0.00 |
| July | 51.85 | 0.43 | 51.42 | 233.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.06 | 4.18 | 55.88 | 255.97 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 80.10 | 18.98 | 61.12 | 251.80 | 1.85 | 0.00 | 0.00 | 0.00 |
| October | 103.37 | 40.86 | 62.51 | 252.34 | 9.98 | 0.00 | 0.00 | 0.00 |
| November | 114.95 | 55.64 | 59.31 | 230.63 | 35.70 | 0.00 | 0.00 | 0.00 |
| December | 105.98 | 52.22 | 53.76 | 180.26 | 72.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.43 | 24.43 | 57.00 | 203.37 | 30.57 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.85 | 0.09 | 51.42 | 157.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 114.95 | 55.64 | 62.51 | 255.97 | 88.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 38.76 | 11.16 | 27.60 | 51.84 | 62.01 | 0.00 | 0.00 | 0.00 |
| February | 44.20 | 12.65 | 31.55 | 68.25 | 49.60 | 0.00 | 0.00 | 0.00 |
| March | 52.30 | 15.52 | 36.78 | 96.24 | 35.09 | 0.00 | 0.00 | 0.00 |
| April | 57.02 | 15.97 | 41.05 | 125.71 | 18.98 | 0.00 | 0.00 | 0.00 |
| May | 62.04 | 18.52 | 43.52 | 172.21 | 3.40 | 0.00 | 0.00 | 0.00 |
| June | 64.22 | 20.28 | 43.94 | 190.44 | 0.42 | 0.00 | 0.00 | 0.00 |
| July | 58.93 | 16.87 | 42.06 | 204.48 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.33 | 18.29 | 42.04 | 207.39 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 57.48 | 18.07 | 39.41 | 169.14 | 1.30 | 0.00 | 0.00 | 0.00 |
| October | 51.09 | 16.50 | 34.59 | 127.56 | 7.31 | 0.00 | 0.00 | 0.00 |
| November | 43.97 | 14.40 | 29.57 | 88.97 | 25.20 | 0.00 | 0.00 | 0.00 |
| December | 36.79 | 11.14 | 25.65 | 56.36 | 50.70 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.29 | 15.79 | 36.50 | 130.24 | 21.04 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.79 | 11.14 | 25.65 | 51.84 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.22 | 20.28 | 43.94 | 207.39 | 62.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 38.76 | 11.16 | 27.60 | 53.68 | 60.52 | 0.00 | 0.00 | 0.00 |
| February | 44.20 | 12.65 | 31.55 | 69.84 | 48.46 | 0.00 | 0.00 | 0.00 |
| March | 52.30 | 15.52 | 36.78 | 97.39 | 34.36 | 0.00 | 0.00 | 0.00 |
| April | 57.02 | 15.97 | 41.05 | 126.29 | 18.69 | 0.00 | 0.00 | 0.00 |
| May | 62.04 | 18.52 | 43.52 | 172.20 | 3.39 | 0.00 | 0.00 | 0.00 |
| June | 64.22 | 20.28 | 43.94 | 190.08 | 0.43 | 0.00 | 0.00 | 0.00 |
| July | 58.93 | 16.87 | 42.06 | 204.35 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.33 | 18.29 | 42.04 | 207.76 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 57.48 | 18.07 | 39.41 | 170.32 | 1.23 | 0.00 | 0.00 | 0.00 |
| October | 51.09 | 16.50 | 34.59 | 129.24 | 6.89 | 0.00 | 0.00 | 0.00 |
| November | 43.97 | 14.40 | 29.57 | 90.65 | 24.14 | 0.00 | 0.00 | 0.00 |
| December | 36.79 | 11.14 | 25.65 | 57.97 | 49.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.29 | 15.79 | 36.50 | 131.17 | 20.48 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.79 | 11.14 | 25.65 | 53.68 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.22 | 20.28 | 43.94 | 207.76 | 60.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.09 | 0.00 | 33.09 | 32.80 | 94.62 | 0.00 | 0.00 | 0.00 |
| February | 37.93 | 0.00 | 37.93 | 49.33 | 75.63 | 0.00 | 0.00 | 0.00 |
| March | 43.57 | 0.00 | 43.57 | 76.61 | 53.01 | 0.00 | 0.00 | 0.00 |
| April | 49.17 | 0.14 | 49.02 | 116.36 | 28.17 | 0.00 | 0.00 | 0.00 |
| May | 55.39 | 1.75 | 53.64 | 183.42 | 4.90 | 0.00 | 0.00 | 0.00 |
| June | 59.05 | 3.20 | 55.85 | 211.84 | 0.67 | 0.00 | 0.00 | 0.00 |
| July | 54.28 | 1.55 | 52.73 | 240.21 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 50.68 | 0.55 | 50.13 | 233.73 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46.04 | 0.01 | 46.03 | 175.19 | 1.86 | 0.00 | 0.00 | 0.00 |
| October | 40.80 | 0.00 | 40.80 | 121.43 | 10.41 | 0.00 | 0.00 | 0.00 |
| November | 35.03 | 0.00 | 35.03 | 72.73 | 36.98 | 0.00 | 0.00 | 0.00 |
| December | 30.88 | 0.00 | 30.88 | 38.47 | 76.22 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.68 | 0.60 | 44.08 | 129.84 | 31.68 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.88 | 0.00 | 30.88 | 32.80 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 59.05 | 3.20 | 55.85 | 240.21 | 94.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 106.93 | 50.23 | 56.71 | 165.92 | 100.96 | 0.00 | 0.00 | 0.00 |
| February | 100.84 | 41.50 | 59.35 | 168.52 | 88.11 | 0.00 | 0.00 | 0.00 |
| March | 81.19 | 20.99 | 60.20 | 151.67 | 70.00 | 0.00 | 0.00 | 0.00 |
| April | 66.35 | 8.25 | 58.10 | 143.58 | 49.90 | 0.00 | 0.00 | 0.00 |
| May | 55.13 | 0.93 | 54.20 | 152.80 | 19.31 | 0.00 | 0.00 | 0.00 |
| June | 51.86 | 0.09 | 51.77 | 158.49 | 9.10 | 0.00 | 0.00 | 0.00 |
| July | 51.85 | 0.43 | 51.42 | 184.25 | 1.40 | 0.00 | 0.00 | 0.00 |
| August | 60.06 | 4.18 | 55.88 | 208.79 | 0.97 | 0.00 | 0.00 | 0.00 |
| September | 80.10 | 18.98 | 61.12 | 214.27 | 12.70 | 0.00 | 0.00 | 0.00 |
| October | 103.37 | 40.86 | 62.51 | 229.07 | 33.44 | 0.00 | 0.00 | 0.00 |
| November | 114.95 | 55.64 | 59.31 | 217.90 | 63.07 | 0.00 | 0.00 | 0.00 |
| December | 105.98 | 52.22 | 53.76 | 175.11 | 90.49 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.43 | 24.43 | 57.00 | 180.94 | 44.72 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.85 | 0.09 | 51.42 | 143.58 | 0.97 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 114.95 | 55.64 | 62.51 | 229.07 | 100.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.39 | 11.92 | 27.47 | 48.57 | 66.98 | 0.00 | 0.00 | 0.00 |
| February | 42.85 | 11.57 | 31.28 | 61.36 | 56.95 | 0.00 | 0.00 | 0.00 |
| March | 47.41 | 11.65 | 35.76 | 81.01 | 43.90 | 0.00 | 0.00 | 0.00 |
| April | 57.89 | 16.93 | 40.96 | 117.25 | 30.69 | 0.00 | 0.00 | 0.00 |
| May | 64.41 | 20.48 | 43.93 | 155.95 | 11.53 | 0.00 | 0.00 | 0.00 |
| June | 63.18 | 19.33 | 43.85 | 163.14 | 5.67 | 0.00 | 0.00 | 0.00 |
| July | 59.01 | 17.04 | 41.97 | 172.50 | 0.87 | 0.00 | 0.00 | 0.00 |
| August | 60.33 | 18.49 | 41.85 | 177.30 | 0.59 | 0.00 | 0.00 | 0.00 |
| September | 56.68 | 17.48 | 39.20 | 142.33 | 7.70 | 0.00 | 0.00 | 0.00 |
| October | 51.41 | 16.75 | 34.66 | 111.91 | 21.35 | 0.00 | 0.00 | 0.00 |
| November | 43.15 | 13.65 | 29.50 | 76.60 | 40.98 | 0.00 | 0.00 | 0.00 |
| December | 34.87 | 9.55 | 25.32 | 46.53 | 59.97 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.75 | 15.42 | 36.33 | 113.16 | 28.79 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.87 | 9.55 | 25.32 | 46.53 | 0.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.41 | 20.48 | 43.93 | 177.30 | 66.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.39 | 11.92 | 27.47 | 51.51 | 56.73 | 0.00 | 0.00 | 0.00 |
| February | 42.85 | 11.57 | 31.28 | 64.75 | 45.83 | 0.00 | 0.00 | 0.00 |
| March | 47.41 | 11.65 | 35.76 | 86.07 | 32.22 | 0.00 | 0.00 | 0.00 |
| April | 57.89 | 16.93 | 40.96 | 127.17 | 17.19 | 0.00 | 0.00 | 0.00 |
| May | 64.41 | 20.48 | 43.93 | 176.21 | 2.94 | 0.00 | 0.00 | 0.00 |
| June | 63.18 | 19.33 | 43.85 | 187.15 | 0.36 | 0.00 | 0.00 | 0.00 |
| July | 59.01 | 17.04 | 41.97 | 204.77 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.33 | 18.49 | 41.85 | 208.73 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 56.68 | 17.48 | 39.20 | 168.89 | 1.02 | 0.00 | 0.00 | 0.00 |
| October | 51.41 | 16.75 | 34.66 | 129.20 | 5.87 | 0.00 | 0.00 | 0.00 |
| November | 43.15 | 13.65 | 29.50 | 86.34 | 22.05 | 0.00 | 0.00 | 0.00 |
| December | 34.87 | 9.55 | 25.32 | 50.99 | 46.35 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.75 | 15.42 | 36.33 | 128.85 | 19.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.87 | 9.55 | 25.32 | 50.99 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.41 | 20.48 | 43.93 | 208.73 | 56.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.09 | 0.00 | 33.09 | 32.21 | 94.40 | 0.00 | 0.00 | 0.00 |
| February | 37.93 | 0.00 | 37.93 | 48.84 | 75.33 | 0.00 | 0.00 | 0.00 |
| March | 43.57 | 0.00 | 43.57 | 76.32 | 52.67 | 0.00 | 0.00 | 0.00 |
| April | 49.17 | 0.14 | 49.02 | 115.96 | 28.08 | 0.00 | 0.00 | 0.00 |
| May | 55.39 | 1.75 | 53.64 | 183.14 | 4.88 | 0.00 | 0.00 | 0.00 |
| June | 59.05 | 3.20 | 55.85 | 211.76 | 0.66 | 0.00 | 0.00 | 0.00 |
| July | 54.28 | 1.55 | 52.73 | 240.12 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 50.68 | 0.55 | 50.13 | 233.63 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46.04 | 0.01 | 46.03 | 175.10 | 1.85 | 0.00 | 0.00 | 0.00 |
| October | 40.80 | 0.00 | 40.80 | 121.26 | 10.38 | 0.00 | 0.00 | 0.00 |
| November | 35.03 | 0.00 | 35.03 | 72.45 | 36.90 | 0.00 | 0.00 | 0.00 |
| December | 30.88 | 0.00 | 30.88 | 38.08 | 76.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.68 | 0.60 | 44.08 | 129.57 | 31.57 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.88 | 0.00 | 30.88 | 32.21 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 59.05 | 3.20 | 55.85 | 240.12 | 94.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.09 | 0.00 | 33.09 | 32.92 | 94.76 | 0.00 | 0.00 | 0.00 |
| February | 37.93 | 0.00 | 37.93 | 49.57 | 75.90 | 0.00 | 0.00 | 0.00 |
| March | 43.57 | 0.00 | 43.57 | 77.18 | 53.10 | 0.00 | 0.00 | 0.00 |
| April | 49.17 | 0.14 | 49.02 | 117.68 | 27.93 | 0.00 | 0.00 | 0.00 |
| May | 55.39 | 1.75 | 53.64 | 186.66 | 4.62 | 0.00 | 0.00 | 0.00 |
| June | 59.05 | 3.20 | 55.85 | 216.06 | 0.57 | 0.00 | 0.00 | 0.00 |
| July | 54.28 | 1.55 | 52.73 | 245.28 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 50.68 | 0.55 | 50.13 | 239.40 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46.04 | 0.01 | 46.03 | 179.95 | 1.63 | 0.00 | 0.00 | 0.00 |
| October | 40.80 | 0.00 | 40.80 | 124.77 | 9.55 | 0.00 | 0.00 | 0.00 |
| November | 35.03 | 0.00 | 35.03 | 74.47 | 35.89 | 0.00 | 0.00 | 0.00 |
| December | 30.88 | 0.00 | 30.88 | 38.93 | 75.86 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.68 | 0.60 | 44.08 | 132.42 | 31.45 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.88 | 0.00 | 30.88 | 32.92 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 59.05 | 3.20 | 55.85 | 245.28 | 94.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.09 | 0.00 | 33.09 | 32.89 | 94.77 | 0.00 | 0.00 | 0.00 |
| February | 37.93 | 0.00 | 37.93 | 49.54 | 75.90 | 0.00 | 0.00 | 0.00 |
| March | 43.57 | 0.00 | 43.57 | 77.17 | 53.08 | 0.00 | 0.00 | 0.00 |
| April | 49.17 | 0.14 | 49.02 | 117.67 | 27.93 | 0.00 | 0.00 | 0.00 |
| May | 55.39 | 1.75 | 53.64 | 186.65 | 4.62 | 0.00 | 0.00 | 0.00 |
| June | 59.05 | 3.20 | 55.85 | 216.05 | 0.57 | 0.00 | 0.00 | 0.00 |
| July | 54.28 | 1.55 | 52.73 | 245.27 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 50.68 | 0.55 | 50.13 | 239.39 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46.04 | 0.01 | 46.03 | 179.95 | 1.63 | 0.00 | 0.00 | 0.00 |
| October | 40.80 | 0.00 | 40.80 | 124.76 | 9.55 | 0.00 | 0.00 | 0.00 |
| November | 35.03 | 0.00 | 35.03 | 74.46 | 35.89 | 0.00 | 0.00 | 0.00 |
| December | 30.88 | 0.00 | 30.88 | 38.91 | 75.86 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.68 | 0.60 | 44.08 | 132.40 | 31.45 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.88 | 0.00 | 30.88 | 32.89 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 59.05 | 3.20 | 55.85 | 245.27 | 94.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 106.93 | 50.23 | 56.71 | 168.15 | 88.71 | 0.00 | 0.00 | 0.00 |
| February | 100.84 | 41.50 | 59.35 | 171.63 | 73.63 | 0.00 | 0.00 | 0.00 |
| March | 81.19 | 20.99 | 60.20 | 158.18 | 53.55 | 0.00 | 0.00 | 0.00 |
| April | 66.35 | 8.25 | 58.10 | 158.56 | 28.73 | 0.00 | 0.00 | 0.00 |
| May | 55.13 | 0.93 | 54.20 | 185.96 | 4.74 | 0.00 | 0.00 | 0.00 |
| June | 51.86 | 0.09 | 51.77 | 199.92 | 0.48 | 0.00 | 0.00 | 0.00 |
| July | 51.85 | 0.43 | 51.42 | 238.47 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.06 | 4.18 | 55.88 | 261.48 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 80.10 | 18.98 | 61.12 | 256.25 | 1.64 | 0.00 | 0.00 | 0.00 |
| October | 103.37 | 40.86 | 62.51 | 255.34 | 9.22 | 0.00 | 0.00 | 0.00 |
| November | 114.95 | 55.64 | 59.31 | 232.07 | 34.78 | 0.00 | 0.00 | 0.00 |
| December | 105.98 | 52.22 | 53.76 | 180.51 | 72.60 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.43 | 24.43 | 57.00 | 205.76 | 30.48 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.85 | 0.09 | 51.42 | 158.18 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 114.95 | 55.64 | 62.51 | 261.48 | 88.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 106.93 | 50.23 | 56.71 | 167.78 | 89.21 | 0.00 | 0.00 | 0.00 |
| February | 100.84 | 41.50 | 59.35 | 171.21 | 74.26 | 0.00 | 0.00 | 0.00 |
| March | 81.19 | 20.99 | 60.20 | 157.68 | 54.23 | 0.00 | 0.00 | 0.00 |
| April | 66.35 | 8.25 | 58.10 | 157.75 | 29.51 | 0.00 | 0.00 | 0.00 |
| May | 55.13 | 0.93 | 54.20 | 184.53 | 5.09 | 0.00 | 0.00 | 0.00 |
| June | 51.86 | 0.09 | 51.77 | 198.25 | 0.54 | 0.00 | 0.00 | 0.00 |
| July | 51.85 | 0.43 | 51.42 | 236.69 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.06 | 4.18 | 55.88 | 259.77 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 80.10 | 18.98 | 61.12 | 254.65 | 1.79 | 0.00 | 0.00 | 0.00 |
| October | 103.37 | 40.86 | 62.51 | 254.13 | 9.82 | 0.00 | 0.00 | 0.00 |
| November | 114.95 | 55.64 | 59.31 | 231.23 | 35.72 | 0.00 | 0.00 | 0.00 |
| December | 105.98 | 52.22 | 53.76 | 180.01 | 73.31 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.43 | 24.43 | 57.00 | 204.68 | 30.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.85 | 0.09 | 51.42 | 157.68 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 114.95 | 55.64 | 62.51 | 259.77 | 89.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 106.93 | 50.23 | 56.71 | 168.32 | 86.73 | 0.00 | 0.00 | 0.00 |
| February | 100.84 | 41.50 | 59.35 | 170.98 | 72.66 | 0.00 | 0.00 | 0.00 |
| March | 81.19 | 20.99 | 60.20 | 157.02 | 53.45 | 0.00 | 0.00 | 0.00 |
| April | 66.35 | 8.25 | 58.10 | 157.19 | 28.46 | 0.00 | 0.00 | 0.00 |
| May | 55.13 | 0.93 | 54.20 | 185.27 | 4.50 | 0.00 | 0.00 | 0.00 |
| June | 51.86 | 0.09 | 51.77 | 200.17 | 0.39 | 0.00 | 0.00 | 0.00 |
| July | 51.85 | 0.43 | 51.42 | 239.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.06 | 4.18 | 55.88 | 263.63 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 80.10 | 18.98 | 61.12 | 258.42 | 1.29 | 0.00 | 0.00 | 0.00 |
| October | 103.37 | 40.86 | 62.51 | 257.02 | 7.57 | 0.00 | 0.00 | 0.00 |
| November | 114.95 | 55.64 | 59.31 | 233.34 | 31.75 | 0.00 | 0.00 | 0.00 |
| December | 105.98 | 52.22 | 53.76 | 181.63 | 69.42 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.43 | 24.43 | 57.00 | 206.26 | 29.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.85 | 0.09 | 51.42 | 157.02 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 114.95 | 55.64 | 62.51 | 263.63 | 86.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 38.76 | 11.16 | 27.60 | 51.97 | 61.08 | 0.00 | 0.00 | 0.00 |
| February | 44.20 | 12.65 | 31.55 | 67.99 | 49.27 | 0.00 | 0.00 | 0.00 |
| March | 52.30 | 15.52 | 36.78 | 95.72 | 35.19 | 0.00 | 0.00 | 0.00 |
| April | 57.02 | 15.97 | 41.05 | 125.49 | 18.73 | 0.00 | 0.00 | 0.00 |
| May | 62.04 | 18.52 | 43.52 | 173.58 | 3.08 | 0.00 | 0.00 | 0.00 |
| June | 64.22 | 20.28 | 43.94 | 193.06 | 0.31 | 0.00 | 0.00 | 0.00 |
| July | 58.93 | 16.87 | 42.06 | 208.23 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.33 | 18.29 | 42.04 | 212.21 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 57.48 | 18.07 | 39.41 | 173.60 | 0.92 | 0.00 | 0.00 | 0.00 |
| October | 51.09 | 16.50 | 34.59 | 130.88 | 5.67 | 0.00 | 0.00 | 0.00 |
| November | 43.97 | 14.40 | 29.57 | 90.99 | 22.47 | 0.00 | 0.00 | 0.00 |
| December | 36.79 | 11.14 | 25.65 | 57.30 | 48.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.29 | 15.79 | 36.50 | 132.12 | 20.30 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.79 | 11.14 | 25.65 | 51.97 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.22 | 20.28 | 43.94 | 212.21 | 61.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 38.76 | 11.16 | 27.60 | 54.15 | 59.36 | 0.00 | 0.00 | 0.00 |
| February | 44.20 | 12.65 | 31.55 | 69.61 | 48.30 | 0.00 | 0.00 | 0.00 |
| March | 52.30 | 15.52 | 36.78 | 96.75 | 34.64 | 0.00 | 0.00 | 0.00 |
| April | 57.02 | 15.97 | 41.05 | 126.00 | 18.52 | 0.00 | 0.00 | 0.00 |
| May | 62.04 | 18.52 | 43.52 | 173.60 | 3.08 | 0.00 | 0.00 | 0.00 |
| June | 64.22 | 20.28 | 43.94 | 192.78 | 0.31 | 0.00 | 0.00 | 0.00 |
| July | 58.93 | 16.87 | 42.06 | 208.16 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.33 | 18.29 | 42.04 | 212.57 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 57.48 | 18.07 | 39.41 | 174.68 | 0.88 | 0.00 | 0.00 | 0.00 |
| October | 51.09 | 16.50 | 34.59 | 132.50 | 5.38 | 0.00 | 0.00 | 0.00 |
| November | 43.97 | 14.40 | 29.57 | 92.69 | 21.62 | 0.00 | 0.00 | 0.00 |
| December | 36.79 | 11.14 | 25.65 | 59.09 | 46.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.29 | 15.79 | 36.50 | 133.08 | 19.78 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.79 | 11.14 | 25.65 | 54.15 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.22 | 20.28 | 43.94 | 212.57 | 59.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.09 | 0.00 | 33.09 | 33.80 | 92.52 | 0.00 | 0.00 | 0.00 |
| February | 37.93 | 0.00 | 37.93 | 49.51 | 75.28 | 0.00 | 0.00 | 0.00 |
| March | 43.57 | 0.00 | 43.57 | 76.26 | 53.40 | 0.00 | 0.00 | 0.00 |
| April | 49.17 | 0.14 | 49.02 | 116.50 | 27.87 | 0.00 | 0.00 | 0.00 |
| May | 55.39 | 1.75 | 53.64 | 185.97 | 4.44 | 0.00 | 0.00 | 0.00 |
| June | 59.05 | 3.20 | 55.85 | 216.12 | 0.50 | 0.00 | 0.00 | 0.00 |
| July | 54.28 | 1.55 | 52.73 | 246.42 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 50.68 | 0.55 | 50.13 | 241.64 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46.04 | 0.01 | 46.03 | 182.46 | 1.32 | 0.00 | 0.00 | 0.00 |
| October | 40.80 | 0.00 | 40.80 | 127.03 | 8.08 | 0.00 | 0.00 | 0.00 |
| November | 35.03 | 0.00 | 35.03 | 76.33 | 33.05 | 0.00 | 0.00 | 0.00 |
| December | 30.88 | 0.00 | 30.88 | 40.43 | 72.39 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.68 | 0.60 | 44.08 | 133.22 | 30.54 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.88 | 0.00 | 30.88 | 33.80 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 59.05 | 3.20 | 55.85 | 246.42 | 92.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 106.93 | 50.23 | 56.71 | 167.65 | 86.52 | 0.00 | 0.00 | 0.00 |
| February | 100.84 | 41.50 | 59.35 | 170.42 | 72.41 | 0.00 | 0.00 | 0.00 |
| March | 81.19 | 20.99 | 60.20 | 156.66 | 53.14 | 0.00 | 0.00 | 0.00 |
| April | 66.35 | 8.25 | 58.10 | 156.76 | 28.36 | 0.00 | 0.00 | 0.00 |
| May | 55.13 | 0.93 | 54.20 | 184.99 | 4.47 | 0.00 | 0.00 | 0.00 |
| June | 51.86 | 0.09 | 51.77 | 200.07 | 0.39 | 0.00 | 0.00 | 0.00 |
| July | 51.85 | 0.43 | 51.42 | 239.41 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.06 | 4.18 | 55.88 | 263.52 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 80.10 | 18.98 | 61.12 | 258.33 | 1.28 | 0.00 | 0.00 | 0.00 |
| October | 103.37 | 40.86 | 62.51 | 256.85 | 7.53 | 0.00 | 0.00 | 0.00 |
| November | 114.95 | 55.64 | 59.31 | 232.98 | 31.63 | 0.00 | 0.00 | 0.00 |
| December | 105.98 | 52.22 | 53.76 | 181.18 | 69.20 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.43 | 24.43 | 57.00 | 205.95 | 29.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.85 | 0.09 | 51.42 | 156.66 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 114.95 | 55.64 | 62.51 | 263.52 | 86.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.39 | 11.92 | 27.47 | 50.10 | 57.46 | 0.00 | 0.00 | 0.00 |
| February | 42.85 | 11.57 | 31.28 | 63.13 | 46.79 | 0.00 | 0.00 | 0.00 |
| March | 47.41 | 11.65 | 35.76 | 84.58 | 33.07 | 0.00 | 0.00 | 0.00 |
| April | 57.89 | 16.93 | 40.96 | 126.43 | 17.18 | 0.00 | 0.00 | 0.00 |
| May | 64.41 | 20.48 | 43.93 | 177.56 | 2.64 | 0.00 | 0.00 | 0.00 |
| June | 63.18 | 19.33 | 43.85 | 189.96 | 0.24 | 0.00 | 0.00 | 0.00 |
| July | 59.01 | 17.04 | 41.97 | 208.62 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.33 | 18.49 | 41.85 | 213.26 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 56.68 | 17.48 | 39.20 | 172.25 | 0.74 | 0.00 | 0.00 | 0.00 |
| October | 51.41 | 16.75 | 34.66 | 131.00 | 4.74 | 0.00 | 0.00 | 0.00 |
| November | 43.15 | 13.65 | 29.50 | 86.90 | 20.54 | 0.00 | 0.00 | 0.00 |
| December | 34.87 | 9.55 | 25.32 | 50.58 | 45.78 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.75 | 15.42 | 36.33 | 129.92 | 18.97 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.87 | 9.55 | 25.32 | 50.10 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.41 | 20.48 | 43.93 | 213.26 | 57.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.39 | 11.92 | 27.47 | 52.05 | 55.54 | 0.00 | 0.00 | 0.00 |
| February | 42.85 | 11.57 | 31.28 | 64.62 | 45.71 | 0.00 | 0.00 | 0.00 |
| March | 47.41 | 11.65 | 35.76 | 85.56 | 32.49 | 0.00 | 0.00 | 0.00 |
| April | 57.89 | 16.93 | 40.96 | 126.93 | 16.98 | 0.00 | 0.00 | 0.00 |
| May | 64.41 | 20.48 | 43.93 | 177.58 | 2.63 | 0.00 | 0.00 | 0.00 |
| June | 63.18 | 19.33 | 43.85 | 189.69 | 0.25 | 0.00 | 0.00 | 0.00 |
| July | 59.01 | 17.04 | 41.97 | 208.56 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.33 | 18.49 | 41.85 | 213.62 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 56.68 | 17.48 | 39.20 | 173.32 | 0.71 | 0.00 | 0.00 | 0.00 |
| October | 51.41 | 16.75 | 34.66 | 132.63 | 4.48 | 0.00 | 0.00 | 0.00 |
| November | 43.15 | 13.65 | 29.50 | 88.61 | 19.75 | 0.00 | 0.00 | 0.00 |
| December | 34.87 | 9.55 | 25.32 | 52.32 | 44.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.75 | 15.42 | 36.33 | 130.84 | 18.43 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.87 | 9.55 | 25.32 | 52.05 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.41 | 20.48 | 43.93 | 213.62 | 55.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.09 | 0.00 | 33.09 | 33.08 | 92.22 | 0.00 | 0.00 | 0.00 |
| February | 37.93 | 0.00 | 37.93 | 48.89 | 74.97 | 0.00 | 0.00 | 0.00 |
| March | 43.57 | 0.00 | 43.57 | 75.88 | 53.07 | 0.00 | 0.00 | 0.00 |
| April | 49.17 | 0.14 | 49.02 | 116.06 | 27.77 | 0.00 | 0.00 | 0.00 |
| May | 55.39 | 1.75 | 53.64 | 185.70 | 4.41 | 0.00 | 0.00 | 0.00 |
| June | 59.05 | 3.20 | 55.85 | 216.04 | 0.49 | 0.00 | 0.00 | 0.00 |
| July | 54.28 | 1.55 | 52.73 | 246.34 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 50.68 | 0.55 | 50.13 | 241.54 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46.04 | 0.01 | 46.03 | 182.37 | 1.31 | 0.00 | 0.00 | 0.00 |
| October | 40.80 | 0.00 | 40.80 | 126.84 | 8.05 | 0.00 | 0.00 | 0.00 |
| November | 35.03 | 0.00 | 35.03 | 75.97 | 32.98 | 0.00 | 0.00 | 0.00 |
| December | 30.88 | 0.00 | 30.88 | 39.96 | 72.14 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.68 | 0.60 | 44.08 | 132.91 | 30.42 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.88 | 0.00 | 30.88 | 33.08 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 59.05 | 3.20 | 55.85 | 246.34 | 92.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.09 | 0.00 | 33.09 | 33.60 | 93.31 | 0.00 | 0.00 | 0.00 |
| February | 37.93 | 0.00 | 37.93 | 49.79 | 75.34 | 0.00 | 0.00 | 0.00 |
| March | 43.57 | 0.00 | 43.57 | 77.07 | 53.15 | 0.00 | 0.00 | 0.00 |
| April | 49.17 | 0.14 | 49.02 | 118.13 | 27.42 | 0.00 | 0.00 | 0.00 |
| May | 55.39 | 1.75 | 53.64 | 189.32 | 4.18 | 0.00 | 0.00 | 0.00 |
| June | 59.05 | 3.20 | 55.85 | 220.15 | 0.43 | 0.00 | 0.00 | 0.00 |
| July | 54.28 | 1.55 | 52.73 | 250.89 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 50.68 | 0.55 | 50.13 | 246.21 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46.04 | 0.01 | 46.03 | 186.15 | 1.22 | 0.00 | 0.00 | 0.00 |
| October | 40.80 | 0.00 | 40.80 | 129.49 | 7.74 | 0.00 | 0.00 | 0.00 |
| November | 35.03 | 0.00 | 35.03 | 77.42 | 32.83 | 0.00 | 0.00 | 0.00 |
| December | 30.88 | 0.00 | 30.88 | 40.44 | 72.91 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.68 | 0.60 | 44.08 | 135.42 | 30.51 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.88 | 0.00 | 30.88 | 33.60 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 59.05 | 3.20 | 55.85 | 250.89 | 93.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.09 | 0.00 | 33.09 | 33.56 | 93.32 | 0.00 | 0.00 | 0.00 |
| February | 37.93 | 0.00 | 37.93 | 49.76 | 75.35 | 0.00 | 0.00 | 0.00 |
| March | 43.57 | 0.00 | 43.57 | 77.05 | 53.14 | 0.00 | 0.00 | 0.00 |
| April | 49.17 | 0.14 | 49.02 | 118.11 | 27.41 | 0.00 | 0.00 | 0.00 |
| May | 55.39 | 1.75 | 53.64 | 189.31 | 4.17 | 0.00 | 0.00 | 0.00 |
| June | 59.05 | 3.20 | 55.85 | 220.14 | 0.43 | 0.00 | 0.00 | 0.00 |
| July | 54.28 | 1.55 | 52.73 | 250.89 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 50.68 | 0.55 | 50.13 | 246.21 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46.04 | 0.01 | 46.03 | 186.15 | 1.21 | 0.00 | 0.00 | 0.00 |
| October | 40.80 | 0.00 | 40.80 | 129.48 | 7.74 | 0.00 | 0.00 | 0.00 |
| November | 35.03 | 0.00 | 35.03 | 77.40 | 32.83 | 0.00 | 0.00 | 0.00 |
| December | 30.88 | 0.00 | 30.88 | 40.42 | 72.91 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.68 | 0.60 | 44.08 | 135.40 | 30.51 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.88 | 0.00 | 30.88 | 33.56 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 59.05 | 3.20 | 55.85 | 250.89 | 93.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 106.93 | 50.23 | 56.71 | 167.89 | 87.70 | 0.00 | 0.00 | 0.00 |
| February | 100.84 | 41.50 | 59.35 | 171.02 | 73.10 | 0.00 | 0.00 | 0.00 |
| March | 81.19 | 20.99 | 60.20 | 157.69 | 53.32 | 0.00 | 0.00 | 0.00 |
| April | 66.35 | 8.25 | 58.10 | 158.72 | 28.03 | 0.00 | 0.00 | 0.00 |
| May | 55.13 | 0.93 | 54.20 | 188.60 | 4.24 | 0.00 | 0.00 | 0.00 |
| June | 51.86 | 0.09 | 51.77 | 204.26 | 0.33 | 0.00 | 0.00 | 0.00 |
| July | 51.85 | 0.43 | 51.42 | 243.94 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.06 | 4.18 | 55.88 | 268.11 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 80.10 | 18.98 | 61.12 | 261.90 | 1.20 | 0.00 | 0.00 | 0.00 |
| October | 103.37 | 40.86 | 62.51 | 259.26 | 7.28 | 0.00 | 0.00 | 0.00 |
| November | 114.95 | 55.64 | 59.31 | 234.18 | 31.54 | 0.00 | 0.00 | 0.00 |
| December | 105.98 | 52.22 | 53.76 | 181.42 | 70.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.43 | 24.43 | 57.00 | 208.31 | 29.53 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.85 | 0.09 | 51.42 | 157.69 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 114.95 | 55.64 | 62.51 | 268.11 | 87.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 106.93 | 50.23 | 56.71 | 167.86 | 87.70 | 0.00 | 0.00 | 0.00 |
| February | 100.84 | 41.50 | 59.35 | 171.00 | 73.10 | 0.00 | 0.00 | 0.00 |
| March | 81.19 | 20.99 | 60.20 | 157.68 | 53.31 | 0.00 | 0.00 | 0.00 |
| April | 66.35 | 8.25 | 58.10 | 158.70 | 28.03 | 0.00 | 0.00 | 0.00 |
| May | 55.13 | 0.93 | 54.20 | 188.58 | 4.24 | 0.00 | 0.00 | 0.00 |
| June | 51.86 | 0.09 | 51.77 | 204.26 | 0.33 | 0.00 | 0.00 | 0.00 |
| July | 51.85 | 0.43 | 51.42 | 243.93 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.06 | 4.18 | 55.88 | 268.10 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 80.10 | 18.98 | 61.12 | 261.89 | 1.20 | 0.00 | 0.00 | 0.00 |
| October | 103.37 | 40.86 | 62.51 | 259.25 | 7.27 | 0.00 | 0.00 | 0.00 |
| November | 114.95 | 55.64 | 59.31 | 234.16 | 31.54 | 0.00 | 0.00 | 0.00 |
| December | 105.98 | 52.22 | 53.76 | 181.40 | 70.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.43 | 24.43 | 57.00 | 208.30 | 29.53 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.85 | 0.09 | 51.42 | 157.68 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 114.95 | 55.64 | 62.51 | 268.10 | 87.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 106.93 | 50.23 | 56.71 | 167.79 | 82.77 | 0.00 | 0.00 | 0.00 |
| February | 100.84 | 41.50 | 59.35 | 169.55 | 69.79 | 0.00 | 0.00 | 0.00 |
| March | 81.19 | 20.99 | 60.20 | 155.05 | 51.50 | 0.00 | 0.00 | 0.00 |
| April | 66.35 | 8.25 | 58.10 | 154.01 | 27.12 | 0.00 | 0.00 | 0.00 |
| May | 55.13 | 0.93 | 54.20 | 180.62 | 4.17 | 0.00 | 0.00 | 0.00 |
| June | 51.86 | 0.09 | 51.77 | 195.28 | 0.34 | 0.00 | 0.00 | 0.00 |
| July | 51.85 | 0.43 | 51.42 | 233.68 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.06 | 4.18 | 55.88 | 257.75 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 80.10 | 18.98 | 61.12 | 253.45 | 1.16 | 0.00 | 0.00 | 0.00 |
| October | 103.37 | 40.86 | 62.51 | 252.82 | 6.92 | 0.00 | 0.00 | 0.00 |
| November | 114.95 | 55.64 | 59.31 | 230.66 | 30.26 | 0.00 | 0.00 | 0.00 |
| December | 105.98 | 52.22 | 53.76 | 180.67 | 66.76 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.43 | 24.43 | 57.00 | 202.82 | 28.21 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.85 | 0.09 | 51.42 | 154.01 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 114.95 | 55.64 | 62.51 | 257.75 | 82.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 38.76 | 11.16 | 27.60 | 50.84 | 57.77 | 0.00 | 0.00 | 0.00 |
| February | 44.20 | 12.65 | 31.55 | 66.55 | 46.93 | 0.00 | 0.00 | 0.00 |
| March | 52.30 | 15.52 | 36.78 | 94.06 | 33.69 | 0.00 | 0.00 | 0.00 |
| April | 57.02 | 15.97 | 41.05 | 123.16 | 17.83 | 0.00 | 0.00 | 0.00 |
| May | 62.04 | 18.52 | 43.52 | 170.27 | 2.88 | 0.00 | 0.00 | 0.00 |
| June | 64.22 | 20.28 | 43.94 | 189.59 | 0.28 | 0.00 | 0.00 | 0.00 |
| July | 58.93 | 16.87 | 42.06 | 204.17 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.33 | 18.29 | 42.04 | 208.06 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 57.48 | 18.07 | 39.41 | 170.14 | 0.84 | 0.00 | 0.00 | 0.00 |
| October | 51.09 | 16.50 | 34.59 | 128.01 | 5.23 | 0.00 | 0.00 | 0.00 |
| November | 43.97 | 14.40 | 29.57 | 89.01 | 21.26 | 0.00 | 0.00 | 0.00 |
| December | 36.79 | 11.14 | 25.65 | 56.12 | 46.16 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.29 | 15.79 | 36.50 | 129.53 | 19.28 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.79 | 11.14 | 25.65 | 50.84 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.22 | 20.28 | 43.94 | 208.06 | 57.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 38.76 | 11.16 | 27.60 | 54.48 | 55.59 | 0.00 | 0.00 | 0.00 |
| February | 44.20 | 12.65 | 31.55 | 69.03 | 46.05 | 0.00 | 0.00 | 0.00 |
| March | 52.30 | 15.52 | 36.78 | 95.53 | 33.32 | 0.00 | 0.00 | 0.00 |
| April | 57.02 | 15.97 | 41.05 | 123.86 | 17.67 | 0.00 | 0.00 | 0.00 |
| May | 62.04 | 18.52 | 43.52 | 170.28 | 2.87 | 0.00 | 0.00 | 0.00 |
| June | 64.22 | 20.28 | 43.94 | 189.25 | 0.28 | 0.00 | 0.00 | 0.00 |
| July | 58.93 | 16.87 | 42.06 | 204.10 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.33 | 18.29 | 42.04 | 208.52 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 57.48 | 18.07 | 39.41 | 171.48 | 0.82 | 0.00 | 0.00 | 0.00 |
| October | 51.09 | 16.50 | 34.59 | 130.15 | 5.05 | 0.00 | 0.00 | 0.00 |
| November | 43.97 | 14.40 | 29.57 | 91.44 | 20.57 | 0.00 | 0.00 | 0.00 |
| December | 36.79 | 11.14 | 25.65 | 58.97 | 44.48 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.29 | 15.79 | 36.50 | 130.95 | 18.77 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.79 | 11.14 | 25.65 | 54.48 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.22 | 20.28 | 43.94 | 208.52 | 55.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.09 | 0.00 | 33.09 | 34.89 | 87.25 | 0.00 | 0.00 | 0.00 |
| February | 37.93 | 0.00 | 37.93 | 49.27 | 72.31 | 0.00 | 0.00 | 0.00 |
| March | 43.57 | 0.00 | 43.57 | 74.92 | 51.64 | 0.00 | 0.00 | 0.00 |
| April | 49.17 | 0.14 | 49.02 | 113.68 | 26.68 | 0.00 | 0.00 | 0.00 |
| May | 55.39 | 1.75 | 53.64 | 181.30 | 4.18 | 0.00 | 0.00 | 0.00 |
| June | 59.05 | 3.20 | 55.85 | 211.01 | 0.45 | 0.00 | 0.00 | 0.00 |
| July | 54.28 | 1.55 | 52.73 | 240.59 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 50.68 | 0.55 | 50.13 | 235.89 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46.04 | 0.01 | 46.03 | 177.98 | 1.22 | 0.00 | 0.00 | 0.00 |
| October | 40.80 | 0.00 | 40.80 | 123.75 | 7.56 | 0.00 | 0.00 | 0.00 |
| November | 35.03 | 0.00 | 35.03 | 74.73 | 31.53 | 0.00 | 0.00 | 0.00 |
| December | 30.88 | 0.00 | 30.88 | 40.67 | 69.07 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.68 | 0.60 | 44.08 | 130.39 | 29.13 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.88 | 0.00 | 30.88 | 34.89 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 59.05 | 3.20 | 55.85 | 240.59 | 87.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 106.93 | 50.23 | 56.71 | 166.47 | 82.25 | 0.00 | 0.00 | 0.00 |
| February | 100.84 | 41.50 | 59.35 | 168.51 | 69.23 | 0.00 | 0.00 | 0.00 |
| March | 81.19 | 20.99 | 60.20 | 154.36 | 50.96 | 0.00 | 0.00 | 0.00 |
| April | 66.35 | 8.25 | 58.10 | 153.33 | 26.92 | 0.00 | 0.00 | 0.00 |
| May | 55.13 | 0.93 | 54.20 | 180.24 | 4.14 | 0.00 | 0.00 | 0.00 |
| June | 51.86 | 0.09 | 51.77 | 195.12 | 0.34 | 0.00 | 0.00 | 0.00 |
| July | 51.85 | 0.43 | 51.42 | 233.54 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.06 | 4.18 | 55.88 | 257.59 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 80.10 | 18.98 | 61.12 | 253.31 | 1.15 | 0.00 | 0.00 | 0.00 |
| October | 103.37 | 40.86 | 62.51 | 252.57 | 6.87 | 0.00 | 0.00 | 0.00 |
| November | 114.95 | 55.64 | 59.31 | 230.06 | 30.03 | 0.00 | 0.00 | 0.00 |
| December | 105.98 | 52.22 | 53.76 | 179.84 | 66.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.43 | 24.43 | 57.00 | 202.29 | 27.99 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.85 | 0.09 | 51.42 | 153.33 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 114.95 | 55.64 | 62.51 | 257.59 | 82.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.39 | 11.92 | 27.47 | 49.99 | 55.13 | 0.00 | 0.00 | 0.00 |
| February | 42.85 | 11.57 | 31.28 | 62.44 | 45.05 | 0.00 | 0.00 | 0.00 |
| March | 47.41 | 11.65 | 35.76 | 83.44 | 31.91 | 0.00 | 0.00 | 0.00 |
| April | 57.89 | 16.93 | 40.96 | 124.33 | 16.41 | 0.00 | 0.00 | 0.00 |
| May | 64.41 | 20.48 | 43.93 | 174.30 | 2.45 | 0.00 | 0.00 | 0.00 |
| June | 63.18 | 19.33 | 43.85 | 186.46 | 0.21 | 0.00 | 0.00 | 0.00 |
| July | 59.01 | 17.04 | 41.97 | 204.60 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.33 | 18.49 | 41.85 | 209.20 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 56.68 | 17.48 | 39.20 | 168.87 | 0.66 | 0.00 | 0.00 | 0.00 |
| October | 51.41 | 16.75 | 34.66 | 128.20 | 4.30 | 0.00 | 0.00 | 0.00 |
| November | 43.15 | 13.65 | 29.50 | 85.19 | 19.56 | 0.00 | 0.00 | 0.00 |
| December | 34.87 | 9.55 | 25.32 | 50.11 | 44.12 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.75 | 15.42 | 36.33 | 127.64 | 18.20 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.87 | 9.55 | 25.32 | 49.99 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.41 | 20.48 | 43.93 | 209.20 | 55.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.39 | 11.92 | 27.47 | 53.20 | 52.58 | 0.00 | 0.00 | 0.00 |
| February | 42.85 | 11.57 | 31.28 | 64.65 | 43.93 | 0.00 | 0.00 | 0.00 |
| March | 47.41 | 11.65 | 35.76 | 84.78 | 31.42 | 0.00 | 0.00 | 0.00 |
| April | 57.89 | 16.93 | 40.96 | 125.01 | 16.25 | 0.00 | 0.00 | 0.00 |
| May | 64.41 | 20.48 | 43.93 | 174.32 | 2.44 | 0.00 | 0.00 | 0.00 |
| June | 63.18 | 19.33 | 43.85 | 186.14 | 0.21 | 0.00 | 0.00 | 0.00 |
| July | 59.01 | 17.04 | 41.97 | 204.53 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.33 | 18.49 | 41.85 | 209.65 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 56.68 | 17.48 | 39.20 | 170.19 | 0.64 | 0.00 | 0.00 | 0.00 |
| October | 51.41 | 16.75 | 34.66 | 130.32 | 4.15 | 0.00 | 0.00 | 0.00 |
| November | 43.15 | 13.65 | 29.50 | 87.54 | 18.89 | 0.00 | 0.00 | 0.00 |
| December | 34.87 | 9.55 | 25.32 | 52.74 | 42.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.75 | 15.42 | 36.33 | 128.97 | 17.62 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.87 | 9.55 | 25.32 | 52.74 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.41 | 20.48 | 43.93 | 209.65 | 52.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.09 | 0.00 | 33.09 | 33.41 | 86.49 | 0.00 | 0.00 | 0.00 |
| February | 37.93 | 0.00 | 37.93 | 48.07 | 71.53 | 0.00 | 0.00 | 0.00 |
| March | 43.57 | 0.00 | 43.57 | 74.20 | 51.00 | 0.00 | 0.00 | 0.00 |
| April | 49.17 | 0.14 | 49.02 | 113.01 | 26.47 | 0.00 | 0.00 | 0.00 |
| May | 55.39 | 1.75 | 53.64 | 180.94 | 4.14 | 0.00 | 0.00 | 0.00 |
| June | 59.05 | 3.20 | 55.85 | 210.88 | 0.44 | 0.00 | 0.00 | 0.00 |
| July | 54.28 | 1.55 | 52.73 | 240.48 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 50.68 | 0.55 | 50.13 | 235.76 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46.04 | 0.01 | 46.03 | 177.85 | 1.21 | 0.00 | 0.00 | 0.00 |
| October | 40.80 | 0.00 | 40.80 | 123.50 | 7.53 | 0.00 | 0.00 | 0.00 |
| November | 35.03 | 0.00 | 35.03 | 74.15 | 31.37 | 0.00 | 0.00 | 0.00 |
| December | 30.88 | 0.00 | 30.88 | 39.71 | 68.55 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.68 | 0.60 | 44.08 | 129.84 | 28.87 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.88 | 0.00 | 30.88 | 33.41 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 59.05 | 3.20 | 55.85 | 240.48 | 86.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.09 | 0.00 | 33.09 | 34.37 | 89.51 | 0.00 | 0.00 | 0.00 |
| February | 37.93 | 0.00 | 37.93 | 49.47 | 73.47 | 0.00 | 0.00 | 0.00 |
| March | 43.57 | 0.00 | 43.57 | 76.01 | 51.86 | 0.00 | 0.00 | 0.00 |
| April | 49.17 | 0.14 | 49.02 | 115.80 | 26.59 | 0.00 | 0.00 | 0.00 |
| May | 55.39 | 1.75 | 53.64 | 185.37 | 4.04 | 0.00 | 0.00 | 0.00 |
| June | 59.05 | 3.20 | 55.85 | 215.79 | 0.41 | 0.00 | 0.00 | 0.00 |
| July | 54.28 | 1.55 | 52.73 | 245.91 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 50.68 | 0.55 | 50.13 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46.04 | 0.01 | 46.03 | 182.40 | 1.17 | 0.00 | 0.00 | 0.00 |
| October | 40.80 | 0.00 | 40.80 | 126.85 | 7.43 | 0.00 | 0.00 | 0.00 |
| November | 35.03 | 0.00 | 35.03 | 76.20 | 31.68 | 0.00 | 0.00 | 0.00 |
| December | 30.88 | 0.00 | 30.88 | 40.65 | 70.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.68 | 0.60 | 44.08 | 133.03 | 29.52 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.88 | 0.00 | 30.88 | 34.37 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 59.05 | 3.20 | 55.85 | 245.91 | 89.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.09 | 0.00 | 33.09 | 34.25 | 89.49 | 0.00 | 0.00 | 0.00 |
| February | 37.93 | 0.00 | 37.93 | 49.38 | 73.44 | 0.00 | 0.00 | 0.00 |
| March | 43.57 | 0.00 | 43.57 | 75.96 | 51.81 | 0.00 | 0.00 | 0.00 |
| April | 49.17 | 0.14 | 49.02 | 115.76 | 26.57 | 0.00 | 0.00 | 0.00 |
| May | 55.39 | 1.75 | 53.64 | 185.36 | 4.03 | 0.00 | 0.00 | 0.00 |
| June | 59.05 | 3.20 | 55.85 | 215.78 | 0.41 | 0.00 | 0.00 | 0.00 |
| July | 54.28 | 1.55 | 52.73 | 245.91 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 50.68 | 0.55 | 50.13 | 241.32 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46.04 | 0.01 | 46.03 | 182.39 | 1.17 | 0.00 | 0.00 | 0.00 |
| October | 40.80 | 0.00 | 40.80 | 126.84 | 7.43 | 0.00 | 0.00 | 0.00 |
| November | 35.03 | 0.00 | 35.03 | 76.16 | 31.67 | 0.00 | 0.00 | 0.00 |
| December | 30.88 | 0.00 | 30.88 | 40.57 | 70.38 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.68 | 0.60 | 44.08 | 132.99 | 29.50 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.88 | 0.00 | 30.88 | 34.25 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 59.05 | 3.20 | 55.85 | 245.91 | 89.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 106.93 | 50.23 | 56.71 | 166.80 | 85.04 | 0.00 | 0.00 | 0.00 |
| February | 100.84 | 41.50 | 59.35 | 169.45 | 71.14 | 0.00 | 0.00 | 0.00 |
| March | 81.19 | 20.99 | 60.20 | 155.94 | 51.87 | 0.00 | 0.00 | 0.00 |
| April | 66.35 | 8.25 | 58.10 | 155.99 | 27.06 | 0.00 | 0.00 | 0.00 |
| May | 55.13 | 0.93 | 54.20 | 184.67 | 4.05 | 0.00 | 0.00 | 0.00 |
| June | 51.86 | 0.09 | 51.77 | 200.12 | 0.31 | 0.00 | 0.00 | 0.00 |
| July | 51.85 | 0.43 | 51.42 | 238.95 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.06 | 4.18 | 55.88 | 263.07 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 80.10 | 18.98 | 61.12 | 257.60 | 1.12 | 0.00 | 0.00 | 0.00 |
| October | 103.37 | 40.86 | 62.51 | 255.60 | 6.80 | 0.00 | 0.00 | 0.00 |
| November | 114.95 | 55.64 | 59.31 | 231.71 | 30.35 | 0.00 | 0.00 | 0.00 |
| December | 105.98 | 52.22 | 53.76 | 180.31 | 68.02 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.43 | 24.43 | 57.00 | 205.24 | 28.62 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.85 | 0.09 | 51.42 | 155.94 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 114.95 | 55.64 | 62.51 | 263.07 | 85.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 106.93 | 50.23 | 56.71 | 166.71 | 85.01 | 0.00 | 0.00 | 0.00 |
| February | 100.84 | 41.50 | 59.35 | 169.38 | 71.12 | 0.00 | 0.00 | 0.00 |
| March | 81.19 | 20.99 | 60.20 | 155.90 | 51.83 | 0.00 | 0.00 | 0.00 |
| April | 66.35 | 8.25 | 58.10 | 155.95 | 27.05 | 0.00 | 0.00 | 0.00 |
| May | 55.13 | 0.93 | 54.20 | 184.65 | 4.04 | 0.00 | 0.00 | 0.00 |
| June | 51.86 | 0.09 | 51.77 | 200.11 | 0.31 | 0.00 | 0.00 | 0.00 |
| July | 51.85 | 0.43 | 51.42 | 238.94 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60.06 | 4.18 | 55.88 | 263.06 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 80.10 | 18.98 | 61.12 | 257.59 | 1.12 | 0.00 | 0.00 | 0.00 |
| October | 103.37 | 40.86 | 62.51 | 255.59 | 6.80 | 0.00 | 0.00 | 0.00 |
| November | 114.95 | 55.64 | 59.31 | 231.68 | 30.34 | 0.00 | 0.00 | 0.00 |
| December | 105.98 | 52.22 | 53.76 | 180.25 | 68.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.43 | 24.43 | 57.00 | 205.21 | 28.61 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.85 | 0.09 | 51.42 | 155.90 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 114.95 | 55.64 | 62.51 | 263.06 | 85.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW14
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 9.45 | 2.86 | 6.59 | 11.75 | 15.01 | 448.50 | 0.00 | 0.00 |
| February | 10.28 | 2.78 | 7.51 | 14.43 | 12.71 | 395.33 | 0.00 | 0.00 |
| March | 11.38 | 2.80 | 8.58 | 19.02 | 9.35 | 393.33 | 0.00 | 0.00 |
| April | 13.89 | 4.06 | 9.83 | 28.24 | 5.40 | 328.00 | 0.00 | 0.00 |
| May | 15.46 | 4.92 | 10.54 | 38.80 | 1.15 | 121.17 | 0.00 | 0.00 |
| June | 15.16 | 4.64 | 10.52 | 41.15 | 0.23 | 29.67 | 0.00 | 0.00 |
| July | 14.16 | 4.09 | 10.07 | 45.09 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 14.48 | 4.44 | 10.04 | 46.21 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 13.60 | 4.19 | 9.41 | 37.23 | 0.37 | 42.83 | 0.00 | 0.00 |
| October | 12.34 | 4.02 | 8.32 | 28.61 | 1.88 | 190.50 | 0.00 | 0.00 |
| November | 10.35 | 3.28 | 7.08 | 19.40 | 6.19 | 340.33 | 0.00 | 0.00 |
| December | 8.37 | 2.29 | 6.08 | 11.56 | 12.35 | 447.67 | 0.00 | 0.00 |
| Annual Sum or Average | 12.42 | 3.70 | 8.72 | 28.54 | 5.35 | 2737.33 | 0.00 | 0.00 |
| Minimum of Months | 8.37 | 2.29 | 6.08 | 11.56 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 15.46 | 4.92 | 10.54 | 46.21 | 15.01 | 448.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ENTRANCE DOOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 28.15 | 8.52 | 19.63 | 33.37 | 47.46 | 18.17 | 0.00 | 0.00 |
| February | 30.63 | 8.27 | 22.36 | 41.55 | 40.26 | 31.33 | 0.00 | 0.00 |
| March | 33.88 | 8.33 | 25.55 | 54.59 | 30.56 | 23.67 | 0.00 | 0.00 |
| April | 41.37 | 12.10 | 29.27 | 80.59 | 19.83 | 60.67 | 0.00 | 0.00 |
| May | 46.03 | 14.64 | 31.39 | 107.28 | 6.11 | 61.50 | 0.00 | 0.00 |
| June | 45.15 | 13.81 | 31.34 | 111.71 | 2.44 | 101.17 | 0.00 | 0.00 |
| July | 42.17 | 12.17 | 29.99 | 120.03 | 0.17 | 26.67 | 0.00 | 0.00 |
| August | 43.12 | 13.21 | 29.91 | 122.28 | 0.10 | 21.50 | 0.00 | 0.00 |
| September | 40.50 | 12.49 | 28.01 | 98.93 | 3.18 | 136.50 | 0.00 | 0.00 |
| October | 36.74 | 11.97 | 24.77 | 77.63 | 10.81 | 100.33 | 0.00 | 0.00 |
| November | 30.84 | 9.76 | 21.08 | 53.45 | 24.75 | 52.00 | 0.00 | 0.00 |
| December | 24.92 | 6.83 | 18.10 | 32.00 | 41.16 | 45.67 | 0.00 | 0.00 |
| Annual Sum or Average | 36.98 | 11.02 | 25.96 | 77.99 | 18.79 | 679.17 | 0.00 | 0.00 |
| Minimum of Months | 24.92 | 6.83 | 18.10 | 32.00 | 0.10 | 18.17 | 0.00 | 0.00 |
| Maximum of Months | 46.03 | 14.64 | 31.39 | 122.28 | 47.46 | 136.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW14
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 9.45 | 2.86 | 6.59 | 11.10 | 15.79 | 512.67 | 0.00 | 0.00 |
| February | 10.28 | 2.78 | 7.51 | 14.03 | 13.25 | 438.83 | 0.00 | 0.00 |
| March | 11.38 | 2.80 | 8.58 | 18.84 | 9.72 | 428.67 | 0.00 | 0.00 |
| April | 13.89 | 4.06 | 9.83 | 28.47 | 5.60 | 331.17 | 0.00 | 0.00 |
| May | 15.46 | 4.92 | 10.54 | 39.62 | 1.19 | 117.50 | 0.00 | 0.00 |
| June | 15.16 | 4.64 | 10.52 | 42.13 | 0.24 | 29.50 | 0.00 | 0.00 |
| July | 14.16 | 4.09 | 10.07 | 46.39 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 14.48 | 4.44 | 10.04 | 47.53 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 13.60 | 4.19 | 9.41 | 38.13 | 0.40 | 43.17 | 0.00 | 0.00 |
| October | 12.34 | 4.02 | 8.32 | 29.11 | 2.00 | 189.00 | 0.00 | 0.00 |
| November | 10.35 | 3.28 | 7.08 | 19.40 | 6.49 | 358.50 | 0.00 | 0.00 |
| December | 8.37 | 2.29 | 6.08 | 11.13 | 12.93 | 498.00 | 0.00 | 0.00 |
| Annual Sum or Average | 12.42 | 3.70 | 8.72 | 28.91 | 5.60 | 2947.00 | 0.00 | 0.00 |
| Minimum of Months | 8.37 | 2.29 | 6.08 | 11.10 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 15.46 | 4.92 | 10.54 | 47.53 | 15.79 | 512.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.450890E+09 | 0.235854E+09 |
| February | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.415237E+09 | 0.176928E+09 |
| March | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.422618E+09 | 0.142830E+09 |
| April | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.407929E+09 | 74929238.54 |
| May | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.489611E+09 | 13406257.84 |
| June | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.507220E+09 | 1444935.44 |
| July | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.625398E+09 | 0.00 |
| August | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.685601E+09 | 0.00 |
| September | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.652658E+09 | 4797164.21 |
| October | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.675855E+09 | 26735110.13 |
| November | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.597799E+09 | 92540939.94 |
| December | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.482803E+09 | 0.194535E+09 |
| Annual Sum or Average | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.641362E+10 | 0.964000E+09 |
| Minimum of Months | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.407929E+09 | 0.00 |
| Maximum of Months | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.685601E+09 | 0.235854E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.103809E+09 | 29878949.63 | 73929877.94 | 0.138843E+09 | 0.166086E+09 |
| February | 0.106921E+09 | 30593048.71 | 76327918.38 | 0.165116E+09 | 0.119988E+09 |
| March | 0.140092E+09 | 41579452.77 | 98512991.88 | 0.257774E+09 | 93975777.12 |
| April | 0.147800E+09 | 41404033.31 | 0.106396E+09 | 0.325829E+09 | 49192968.09 |
| May | 0.166174E+09 | 49614264.66 | 0.116560E+09 | 0.461241E+09 | 9107628.90 |
| June | 0.166461E+09 | 52568631.13 | 0.113892E+09 | 0.493614E+09 | 1080371.12 |
| July | 0.157832E+09 | 45185244.23 | 0.112646E+09 | 0.547675E+09 | 467.40 |
| August | 0.161596E+09 | 49000876.05 | 0.112595E+09 | 0.555467E+09 | 0.00 |
| September | 0.148987E+09 | 46838450.68 | 0.102148E+09 | 0.438423E+09 | 3357729.52 |
| October | 0.136839E+09 | 44204558.38 | 92634435.10 | 0.341648E+09 | 19584614.40 |
| November | 0.113977E+09 | 37321388.83 | 76655627.41 | 0.230612E+09 | 65309768.69 |
| December | 98539195.66 | 29848443.94 | 68690751.72 | 0.150946E+09 | 0.135793E+09 |
| Annual Sum or Average | 0.164903E+10 | 0.498037E+09 | 0.115099E+10 | 0.410719E+10 | 0.663477E+09 |
| Minimum of Months | 98539195.66 | 29848443.94 | 68690751.72 | 0.138843E+09 | 0.00 |
| Maximum of Months | 0.166461E+09 | 52568631.13 | 0.116560E+09 | 0.555467E+09 | 0.166086E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.103809E+09 | 29878949.63 | 73929877.94 | 0.143764E+09 | 0.162107E+09 |
| February | 0.106921E+09 | 30593048.71 | 76327918.38 | 0.168957E+09 | 0.117227E+09 |
| March | 0.140092E+09 | 41579452.77 | 98512991.88 | 0.260855E+09 | 92029668.54 |
| April | 0.147800E+09 | 41404033.31 | 0.106396E+09 | 0.327344E+09 | 48453474.88 |
| May | 0.166174E+09 | 49614264.66 | 0.116560E+09 | 0.461222E+09 | 9091436.02 |
| June | 0.166461E+09 | 52568631.13 | 0.113892E+09 | 0.492686E+09 | 1106032.50 |
| July | 0.157832E+09 | 45185244.23 | 0.112646E+09 | 0.547330E+09 | 474.41 |
| August | 0.161596E+09 | 49000876.05 | 0.112595E+09 | 0.556474E+09 | 0.00 |
| September | 0.148987E+09 | 46838450.68 | 0.102148E+09 | 0.441458E+09 | 3181742.20 |
| October | 0.136839E+09 | 44204558.38 | 92634435.10 | 0.346152E+09 | 18452318.59 |
| November | 0.113977E+09 | 37321388.83 | 76655627.41 | 0.234974E+09 | 62559023.04 |
| December | 98539195.66 | 29848443.94 | 68690751.72 | 0.155257E+09 | 0.131635E+09 |
| Annual Sum or Average | 0.164903E+10 | 0.498037E+09 | 0.115099E+10 | 0.413647E+10 | 0.645844E+09 |
| Minimum of Months | 98539195.66 | 29848443.94 | 68690751.72 | 0.143764E+09 | 0.00 |
| Maximum of Months | 0.166461E+09 | 52568631.13 | 0.116560E+09 | 0.556474E+09 | 0.162107E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88623175.80 | 0.00 | 88623175.80 | 87863289.97 | 0.253442E+09 |
| February | 91756479.98 | 0.00 | 91756479.98 | 0.119336E+09 | 0.182959E+09 |
| March | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.205197E+09 | 0.141989E+09 |
| April | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.301616E+09 | 73019525.51 |
| May | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.491281E+09 | 13122437.63 |
| June | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.549081E+09 | 1746466.31 |
| July | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.643375E+09 | 913.00 |
| August | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.626018E+09 | 0.00 |
| September | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.454083E+09 | 4819431.89 |
| October | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.325247E+09 | 27882485.55 |
| November | 90794144.06 | 0.00 | 90794144.06 | 0.188523E+09 | 95857191.04 |
| December | 82718268.40 | 0.00 | 82718268.40 | 0.103030E+09 | 0.204158E+09 |
| Annual Sum or Average | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.409465E+10 | 0.998996E+09 |
| Minimum of Months | 82718268.40 | 0.00 | 82718268.40 | 87863289.97 | 0.00 |
| Maximum of Months | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.643375E+09 | 0.253442E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.444409E+09 | 0.270405E+09 |
| February | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.407676E+09 | 0.213150E+09 |
| March | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.406237E+09 | 0.187478E+09 |
| April | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.372151E+09 | 0.129331E+09 |
| May | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.409264E+09 | 51707329.58 |
| June | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.410802E+09 | 23577406.36 |
| July | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.493502E+09 | 3742537.17 |
| August | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.559234E+09 | 2602531.38 |
| September | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.555377E+09 | 32905607.15 |
| October | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.613537E+09 | 89552498.96 |
| November | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.564793E+09 | 0.163466E+09 |
| December | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.469014E+09 | 0.242359E+09 |
| Annual Sum or Average | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.570600E+10 | 0.141028E+10 |
| Minimum of Months | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.372151E+09 | 2602531.38 |
| Maximum of Months | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.613537E+09 | 0.270405E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105500E+09 | 31934045.17 | 73565630.67 | 0.130100E+09 | 0.179413E+09 |
| February | 0.103672E+09 | 27988141.95 | 75684311.64 | 0.148443E+09 | 0.137780E+09 |
| March | 0.126984E+09 | 31208877.80 | 95775091.86 | 0.216988E+09 | 0.117571E+09 |
| April | 0.150052E+09 | 43886149.05 | 0.106166E+09 | 0.303922E+09 | 79554920.45 |
| May | 0.172521E+09 | 54863107.39 | 0.117658E+09 | 0.417695E+09 | 30878426.28 |
| June | 0.163769E+09 | 50105710.88 | 0.113664E+09 | 0.422862E+09 | 14702861.83 |
| July | 0.158042E+09 | 45627695.76 | 0.112414E+09 | 0.462029E+09 | 2317368.01 |
| August | 0.161601E+09 | 49510927.60 | 0.112090E+09 | 0.474887E+09 | 1570154.34 |
| September | 0.146908E+09 | 45301204.88 | 0.101606E+09 | 0.368921E+09 | 19971163.85 |
| October | 0.137691E+09 | 44866965.27 | 92824257.39 | 0.299730E+09 | 57195121.59 |
| November | 0.111852E+09 | 35388966.58 | 76462808.30 | 0.198548E+09 | 0.106220E+09 |
| December | 93401161.53 | 25580096.36 | 67821065.17 | 0.124629E+09 | 0.160618E+09 |
| Annual Sum or Average | 0.163199E+10 | 0.486262E+09 | 0.114573E+10 | 0.356875E+10 | 0.907792E+09 |
| Minimum of Months | 93401161.53 | 25580096.36 | 67821065.17 | 0.124629E+09 | 1570154.34 |
| Maximum of Months | 0.172521E+09 | 54863107.39 | 0.117658E+09 | 0.474887E+09 | 0.179413E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105500E+09 | 31934045.17 | 73565630.67 | 0.137972E+09 | 0.151945E+09 |
| February | 0.103672E+09 | 27988141.95 | 75684311.64 | 0.156646E+09 | 0.110873E+09 |
| March | 0.126984E+09 | 31208877.80 | 95775091.86 | 0.230519E+09 | 86291356.19 |
| April | 0.150052E+09 | 43886149.05 | 0.106166E+09 | 0.329636E+09 | 44556261.99 |
| May | 0.172521E+09 | 54863107.39 | 0.117658E+09 | 0.471953E+09 | 7861808.84 |
| June | 0.163769E+09 | 50105710.88 | 0.113664E+09 | 0.485086E+09 | 925796.20 |
| July | 0.158042E+09 | 45627695.76 | 0.112414E+09 | 0.548447E+09 | 0.00 |
| August | 0.161601E+09 | 49510927.60 | 0.112090E+09 | 0.559066E+09 | 0.00 |
| September | 0.146908E+09 | 45301204.88 | 0.101606E+09 | 0.437763E+09 | 2633317.74 |
| October | 0.137691E+09 | 44866965.27 | 92824257.39 | 0.346058E+09 | 15728015.32 |
| November | 0.111852E+09 | 35388966.58 | 76462808.30 | 0.223806E+09 | 57162459.67 |
| December | 93401161.53 | 25580096.36 | 67821065.17 | 0.136574E+09 | 0.124157E+09 |
| Annual Sum or Average | 0.163199E+10 | 0.486262E+09 | 0.114573E+10 | 0.406352E+10 | 0.602134E+09 |
| Minimum of Months | 93401161.53 | 25580096.36 | 67821065.17 | 0.136574E+09 | 0.00 |
| Maximum of Months | 0.172521E+09 | 54863107.39 | 0.117658E+09 | 0.559066E+09 | 0.151945E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88623175.80 | 0.00 | 88623175.80 | 86263108.89 | 0.252852E+09 |
| February | 91756479.98 | 0.00 | 91756479.98 | 0.118156E+09 | 0.182229E+09 |
| March | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.204411E+09 | 0.141078E+09 |
| April | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.300564E+09 | 72778068.96 |
| May | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.490512E+09 | 13057249.38 |
| June | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.548870E+09 | 1718462.88 |
| July | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.643147E+09 | 816.33 |
| August | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.625747E+09 | 0.00 |
| September | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.453857E+09 | 4793683.93 |
| October | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.324788E+09 | 27793041.74 |
| November | 90794144.06 | 0.00 | 90794144.06 | 0.187778E+09 | 95639849.03 |
| December | 82718268.40 | 0.00 | 82718268.40 | 0.101999E+09 | 0.203599E+09 |
| Annual Sum or Average | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.408609E+10 | 0.995538E+09 |
| Minimum of Months | 82718268.40 | 0.00 | 82718268.40 | 86263108.89 | 0.00 |
| Maximum of Months | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.643147E+09 | 0.252852E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88623175.80 | 0.00 | 88623175.80 | 88173176.91 | 0.253809E+09 |
| February | 91756479.98 | 0.00 | 91756479.98 | 0.119910E+09 | 0.183625E+09 |
| March | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.206722E+09 | 0.142219E+09 |
| April | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.305036E+09 | 72385658.44 |
| May | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.499961E+09 | 12374592.19 |
| June | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.560015E+09 | 1482109.91 |
| July | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.656952E+09 | 0.00 |
| August | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.641199E+09 | 0.00 |
| September | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.466443E+09 | 4236819.27 |
| October | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.334181E+09 | 25586752.12 |
| November | 90794144.06 | 0.00 | 90794144.06 | 0.193036E+09 | 93038031.44 |
| December | 82718268.40 | 0.00 | 82718268.40 | 0.104275E+09 | 0.203196E+09 |
| Annual Sum or Average | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.417590E+10 | 0.991953E+09 |
| Minimum of Months | 82718268.40 | 0.00 | 82718268.40 | 88173176.91 | 0.00 |
| Maximum of Months | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.656952E+09 | 0.253809E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88623175.80 | 0.00 | 88623175.80 | 88091938.90 | 0.253829E+09 |
| February | 91756479.98 | 0.00 | 91756479.98 | 0.119854E+09 | 0.183619E+09 |
| March | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.206695E+09 | 0.142181E+09 |
| April | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.304992E+09 | 72385460.71 |
| May | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.499926E+09 | 12374260.16 |
| June | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.560005E+09 | 1481311.49 |
| July | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.656942E+09 | 0.00 |
| August | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.641186E+09 | 0.00 |
| September | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.466432E+09 | 4236049.03 |
| October | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.334160E+09 | 25584443.32 |
| November | 90794144.06 | 0.00 | 90794144.06 | 0.193004E+09 | 93036688.05 |
| December | 82718268.40 | 0.00 | 82718268.40 | 0.104226E+09 | 0.203194E+09 |
| Annual Sum or Average | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.417551E+10 | 0.991920E+09 |
| Minimum of Months | 82718268.40 | 0.00 | 82718268.40 | 88091938.90 | 0.00 |
| Maximum of Months | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.656942E+09 | 0.253829E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.450386E+09 | 0.237590E+09 |
| February | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.415218E+09 | 0.178132E+09 |
| March | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.423680E+09 | 0.143417E+09 |
| April | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.410976E+09 | 74474421.24 |
| May | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.498079E+09 | 12705878.43 |
| June | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.518199E+09 | 1232606.22 |
| July | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.638729E+09 | 0.00 |
| August | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.700335E+09 | 0.00 |
| September | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.664208E+09 | 4262353.59 |
| October | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.683891E+09 | 24686332.56 |
| November | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.601520E+09 | 90146172.56 |
| December | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.483476E+09 | 0.194464E+09 |
| Annual Sum or Average | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.648870E+10 | 0.961111E+09 |
| Minimum of Months | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.410976E+09 | 0.00 |
| Maximum of Months | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.700335E+09 | 0.237590E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.449386E+09 | 0.238941E+09 |
| February | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.414186E+09 | 0.179651E+09 |
| March | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.422335E+09 | 0.145259E+09 |
| April | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.408898E+09 | 76495441.94 |
| May | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.494237E+09 | 13622150.43 |
| June | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.513860E+09 | 1409756.39 |
| July | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.633937E+09 | 0.00 |
| August | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.695779E+09 | 0.00 |
| September | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.660059E+09 | 4650200.28 |
| October | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.680672E+09 | 26293206.15 |
| November | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.599338E+09 | 92581366.11 |
| December | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.482144E+09 | 0.196366E+09 |
| Annual Sum or Average | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.645483E+10 | 0.975269E+09 |
| Minimum of Months | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.408898E+09 | 0.00 |
| Maximum of Months | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.695779E+09 | 0.238941E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.450830E+09 | 0.232300E+09 |
| February | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.413638E+09 | 0.175784E+09 |
| March | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.420558E+09 | 0.143169E+09 |
| April | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.407433E+09 | 73772508.16 |
| May | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.496217E+09 | 12045134.71 |
| June | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.518843E+09 | 1022437.86 |
| July | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.641477E+09 | 0.00 |
| August | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.706095E+09 | 0.00 |
| September | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.669817E+09 | 3344200.13 |
| October | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.688413E+09 | 20274099.62 |
| November | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.604820E+09 | 82294211.30 |
| December | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.486468E+09 | 0.185939E+09 |
| Annual Sum or Average | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.650461E+10 | 0.929945E+09 |
| Minimum of Months | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.407433E+09 | 0.00 |
| Maximum of Months | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.706095E+09 | 0.232300E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.103809E+09 | 29878949.63 | 73929877.94 | 0.139205E+09 | 0.163584E+09 |
| February | 0.106921E+09 | 30593048.71 | 76327918.38 | 0.164481E+09 | 0.119200E+09 |
| March | 0.140092E+09 | 41579452.77 | 98512991.88 | 0.256378E+09 | 94257702.08 |
| April | 0.147800E+09 | 41404033.31 | 0.106396E+09 | 0.325264E+09 | 48552215.32 |
| May | 0.166174E+09 | 49614264.66 | 0.116560E+09 | 0.464917E+09 | 8261257.86 |
| June | 0.166461E+09 | 52568631.13 | 0.113892E+09 | 0.500401E+09 | 806089.29 |
| July | 0.157832E+09 | 45185244.23 | 0.112646E+09 | 0.557711E+09 | 0.00 |
| August | 0.161596E+09 | 49000876.05 | 0.112595E+09 | 0.568384E+09 | 0.00 |
| September | 0.148987E+09 | 46838450.68 | 0.102148E+09 | 0.449978E+09 | 2397543.36 |
| October | 0.136839E+09 | 44204558.38 | 92634435.10 | 0.350542E+09 | 15197808.83 |
| November | 0.113977E+09 | 37321388.83 | 76655627.41 | 0.235838E+09 | 58241759.49 |
| December | 98539195.66 | 29848443.94 | 68690751.72 | 0.153460E+09 | 0.129640E+09 |
| Annual Sum or Average | 0.164903E+10 | 0.498037E+09 | 0.115099E+10 | 0.416656E+10 | 0.640138E+09 |
| Minimum of Months | 98539195.66 | 29848443.94 | 68690751.72 | 0.139205E+09 | 0.00 |
| Maximum of Months | 0.166461E+09 | 52568631.13 | 0.116560E+09 | 0.568384E+09 | 0.163584E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.103809E+09 | 29878949.63 | 73929877.94 | 0.145024E+09 | 0.158994E+09 |
| February | 0.106921E+09 | 30593048.71 | 76327918.38 | 0.168409E+09 | 0.116850E+09 |
| March | 0.140092E+09 | 41579452.77 | 98512991.88 | 0.259148E+09 | 92788363.60 |
| April | 0.147800E+09 | 41404033.31 | 0.106396E+09 | 0.326600E+09 | 47998114.56 |
| May | 0.166174E+09 | 49614264.66 | 0.116560E+09 | 0.464962E+09 | 8238718.73 |
| June | 0.166461E+09 | 52568631.13 | 0.113892E+09 | 0.499691E+09 | 816397.62 |
| July | 0.157832E+09 | 45185244.23 | 0.112646E+09 | 0.557525E+09 | 0.00 |
| August | 0.161596E+09 | 49000876.05 | 0.112595E+09 | 0.569349E+09 | 0.00 |
| September | 0.148987E+09 | 46838450.68 | 0.102148E+09 | 0.452770E+09 | 2283757.99 |
| October | 0.136839E+09 | 44204558.38 | 92634435.10 | 0.354885E+09 | 14421984.00 |
| November | 0.113977E+09 | 37321388.83 | 76655627.41 | 0.240247E+09 | 56044372.34 |
| December | 98539195.66 | 29848443.94 | 68690751.72 | 0.158279E+09 | 0.125435E+09 |
| Annual Sum or Average | 0.164903E+10 | 0.498037E+09 | 0.115099E+10 | 0.419689E+10 | 0.623870E+09 |
| Minimum of Months | 98539195.66 | 29848443.94 | 68690751.72 | 0.145024E+09 | 0.00 |
| Maximum of Months | 0.166461E+09 | 52568631.13 | 0.116560E+09 | 0.569349E+09 | 0.158994E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88623175.80 | 0.00 | 88623175.80 | 90516632.32 | 0.247814E+09 |
| February | 91756479.98 | 0.00 | 91756479.98 | 0.119764E+09 | 0.182129E+09 |
| March | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.204260E+09 | 0.143036E+09 |
| April | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.301964E+09 | 72240805.67 |
| May | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.498113E+09 | 11893332.81 |
| June | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.560189E+09 | 1287023.36 |
| July | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.660017E+09 | 0.00 |
| August | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.647213E+09 | 0.00 |
| September | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.472942E+09 | 3420106.70 |
| October | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.340228E+09 | 21651683.39 |
| November | 90794144.06 | 0.00 | 90794144.06 | 0.197838E+09 | 85668755.53 |
| December | 82718268.40 | 0.00 | 82718268.40 | 0.108291E+09 | 0.193894E+09 |
| Annual Sum or Average | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.420134E+10 | 0.963034E+09 |
| Minimum of Months | 82718268.40 | 0.00 | 82718268.40 | 90516632.32 | 0.00 |
| Maximum of Months | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.660017E+09 | 0.247814E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.449041E+09 | 0.231742E+09 |
| February | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.412276E+09 | 0.175169E+09 |
| March | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.419592E+09 | 0.142319E+09 |
| April | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.406315E+09 | 73500346.79 |
| May | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.495470E+09 | 11982529.64 |
| June | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.518591E+09 | 1004023.55 |
| July | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.641224E+09 | 0.00 |
| August | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.705801E+09 | 0.00 |
| September | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.669584E+09 | 3322990.49 |
| October | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.687935E+09 | 20167219.62 |
| November | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.603880E+09 | 81977966.64 |
| December | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.485279E+09 | 0.185351E+09 |
| Annual Sum or Average | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.649499E+10 | 0.926537E+09 |
| Minimum of Months | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.406315E+09 | 0.00 |
| Maximum of Months | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.705801E+09 | 0.231742E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105500E+09 | 31934045.17 | 73565630.67 | 0.134181E+09 | 0.153888E+09 |
| February | 0.103672E+09 | 27988141.95 | 75684311.64 | 0.152725E+09 | 0.113183E+09 |
| March | 0.126984E+09 | 31208877.80 | 95775091.86 | 0.226540E+09 | 88574596.58 |
| April | 0.150052E+09 | 43886149.05 | 0.106166E+09 | 0.327700E+09 | 44541520.79 |
| May | 0.172521E+09 | 54863107.39 | 0.117658E+09 | 0.475576E+09 | 7058584.16 |
| June | 0.163769E+09 | 50105710.88 | 0.113664E+09 | 0.492367E+09 | 629850.21 |
| July | 0.158042E+09 | 45627695.76 | 0.112414E+09 | 0.558780E+09 | 0.00 |
| August | 0.161601E+09 | 49510927.60 | 0.112090E+09 | 0.571184E+09 | 0.00 |
| September | 0.146908E+09 | 45301204.88 | 0.101606E+09 | 0.446467E+09 | 1926556.33 |
| October | 0.137691E+09 | 44866965.27 | 92824257.39 | 0.350862E+09 | 12690021.84 |
| November | 0.111852E+09 | 35388966.58 | 76462808.30 | 0.225244E+09 | 53237395.84 |
| December | 93401161.53 | 25580096.36 | 67821065.17 | 0.135483E+09 | 0.122606E+09 |
| Annual Sum or Average | 0.163199E+10 | 0.486262E+09 | 0.114573E+10 | 0.409711E+10 | 0.598335E+09 |
| Minimum of Months | 93401161.53 | 25580096.36 | 67821065.17 | 0.134181E+09 | 0.00 |
| Maximum of Months | 0.172521E+09 | 54863107.39 | 0.117658E+09 | 0.571184E+09 | 0.153888E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105500E+09 | 31934045.17 | 73565630.67 | 0.139407E+09 | 0.148763E+09 |
| February | 0.103672E+09 | 27988141.95 | 75684311.64 | 0.156339E+09 | 0.110584E+09 |
| March | 0.126984E+09 | 31208877.80 | 95775091.86 | 0.229162E+09 | 87025975.92 |
| April | 0.150052E+09 | 43886149.05 | 0.106166E+09 | 0.329013E+09 | 44009111.97 |
| May | 0.172521E+09 | 54863107.39 | 0.117658E+09 | 0.475634E+09 | 7033240.28 |
| June | 0.163769E+09 | 50105710.88 | 0.113664E+09 | 0.491676E+09 | 638667.40 |
| July | 0.158042E+09 | 45627695.76 | 0.112414E+09 | 0.558599E+09 | 0.00 |
| August | 0.161601E+09 | 49510927.60 | 0.112090E+09 | 0.572148E+09 | 0.00 |
| September | 0.146908E+09 | 45301204.88 | 0.101606E+09 | 0.449252E+09 | 1830398.89 |
| October | 0.137691E+09 | 44866965.27 | 92824257.39 | 0.355245E+09 | 12010772.87 |
| November | 0.111852E+09 | 35388966.58 | 76462808.30 | 0.229675E+09 | 51203577.90 |
| December | 93401161.53 | 25580096.36 | 67821065.17 | 0.140139E+09 | 0.118259E+09 |
| Annual Sum or Average | 0.163199E+10 | 0.486262E+09 | 0.114573E+10 | 0.412629E+10 | 0.581358E+09 |
| Minimum of Months | 93401161.53 | 25580096.36 | 67821065.17 | 0.139407E+09 | 0.00 |
| Maximum of Months | 0.172521E+09 | 54863107.39 | 0.117658E+09 | 0.572148E+09 | 0.148763E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88623175.80 | 0.00 | 88623175.80 | 88597903.45 | 0.246990E+09 |
| February | 91756479.98 | 0.00 | 91756479.98 | 0.118280E+09 | 0.181375E+09 |
| March | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.203248E+09 | 0.142139E+09 |
| April | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.300831E+09 | 71970382.81 |
| May | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.497385E+09 | 11816764.42 |
| June | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.559975E+09 | 1266557.38 |
| July | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.659794E+09 | 0.00 |
| August | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.646951E+09 | 0.00 |
| September | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.472708E+09 | 3398340.73 |
| October | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.339733E+09 | 21570604.21 |
| November | 90794144.06 | 0.00 | 90794144.06 | 0.196921E+09 | 85488623.83 |
| December | 82718268.40 | 0.00 | 82718268.40 | 0.107024E+09 | 0.193222E+09 |
| Annual Sum or Average | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.419145E+10 | 0.959238E+09 |
| Minimum of Months | 82718268.40 | 0.00 | 82718268.40 | 88597903.45 | 0.00 |
| Maximum of Months | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.659794E+09 | 0.246990E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88623175.80 | 0.00 | 88623175.80 | 89981383.97 | 0.249918E+09 |
| February | 91756479.98 | 0.00 | 91756479.98 | 0.120461E+09 | 0.182264E+09 |
| March | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.206421E+09 | 0.142367E+09 |
| April | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.306190E+09 | 71063368.42 |
| May | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.507068E+09 | 11184021.75 |
| June | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.570618E+09 | 1118345.73 |
| July | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.671981E+09 | 0.00 |
| August | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.659461E+09 | 0.00 |
| September | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.482503E+09 | 3149873.79 |
| October | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.346827E+09 | 20735469.58 |
| November | 90794144.06 | 0.00 | 90794144.06 | 0.200665E+09 | 85088151.03 |
| December | 82718268.40 | 0.00 | 82718268.40 | 0.108316E+09 | 0.195293E+09 |
| Annual Sum or Average | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.427049E+10 | 0.962182E+09 |
| Minimum of Months | 82718268.40 | 0.00 | 82718268.40 | 89981383.97 | 0.00 |
| Maximum of Months | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.671981E+09 | 0.249918E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88623175.80 | 0.00 | 88623175.80 | 89880250.26 | 0.249936E+09 |
| February | 91756479.98 | 0.00 | 91756479.98 | 0.120377E+09 | 0.182286E+09 |
| March | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.206382E+09 | 0.142327E+09 |
| April | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.306147E+09 | 71059419.79 |
| May | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.507039E+09 | 11182303.29 |
| June | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.570609E+09 | 1117627.31 |
| July | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.671971E+09 | 0.00 |
| August | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.659449E+09 | 0.00 |
| September | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.482493E+09 | 3148979.46 |
| October | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.346805E+09 | 20732274.99 |
| November | 90794144.06 | 0.00 | 90794144.06 | 0.200624E+09 | 85086811.28 |
| December | 82718268.40 | 0.00 | 82718268.40 | 0.108254E+09 | 0.195291E+09 |
| Annual Sum or Average | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.427003E+10 | 0.962168E+09 |
| Minimum of Months | 82718268.40 | 0.00 | 82718268.40 | 89880250.26 | 0.00 |
| Maximum of Months | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.671971E+09 | 0.249936E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.449682E+09 | 0.234899E+09 |
| February | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.413737E+09 | 0.176851E+09 |
| March | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.422350E+09 | 0.142825E+09 |
| April | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.411401E+09 | 72651094.44 |
| May | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.505135E+09 | 11356125.18 |
| June | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.529443E+09 | 867827.61 |
| July | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.653365E+09 | 0.00 |
| August | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.718100E+09 | 0.00 |
| September | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.678838E+09 | 3104180.98 |
| October | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.694390E+09 | 19486670.48 |
| November | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.606983E+09 | 81761688.25 |
| December | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.485917E+09 | 0.187516E+09 |
| Annual Sum or Average | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.656934E+10 | 0.931319E+09 |
| Minimum of Months | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.411401E+09 | 0.00 |
| Maximum of Months | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.718100E+09 | 0.234899E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.449599E+09 | 0.234901E+09 |
| February | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.413678E+09 | 0.176844E+09 |
| March | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.422317E+09 | 0.142792E+09 |
| April | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.411360E+09 | 72646568.75 |
| May | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.505105E+09 | 11354531.17 |
| June | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.529433E+09 | 867159.45 |
| July | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.653355E+09 | 0.00 |
| August | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.718089E+09 | 0.00 |
| September | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.678829E+09 | 3103335.64 |
| October | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.694372E+09 | 19483214.25 |
| November | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.606951E+09 | 81755580.19 |
| December | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.485868E+09 | 0.187506E+09 |
| Annual Sum or Average | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.656896E+10 | 0.931254E+09 |
| Minimum of Months | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.411360E+09 | 0.00 |
| Maximum of Months | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.718089E+09 | 0.234901E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.449396E+09 | 0.221702E+09 |
| February | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.410171E+09 | 0.168842E+09 |
| March | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.415284E+09 | 0.137945E+09 |
| April | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.399187E+09 | 70304494.78 |
| May | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.483771E+09 | 11167631.90 |
| June | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.506160E+09 | 888077.58 |
| July | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.625890E+09 | 0.00 |
| August | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.690358E+09 | 0.00 |
| September | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.656930E+09 | 3007362.59 |
| October | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.677159E+09 | 18524645.06 |
| November | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.597864E+09 | 78429967.71 |
| December | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.483903E+09 | 0.178810E+09 |
| Annual Sum or Average | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.639607E+10 | 0.889621E+09 |
| Minimum of Months | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.399187E+09 | 0.00 |
| Maximum of Months | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.690358E+09 | 0.221702E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.103809E+09 | 29878949.63 | 73929877.94 | 0.136178E+09 | 0.154722E+09 |
| February | 0.106921E+09 | 30593048.71 | 76327918.38 | 0.161001E+09 | 0.113523E+09 |
| March | 0.140092E+09 | 41579452.77 | 98512991.88 | 0.251926E+09 | 90246737.31 |
| April | 0.147800E+09 | 41404033.31 | 0.106396E+09 | 0.319218E+09 | 46206951.53 |
| May | 0.166174E+09 | 49614264.66 | 0.116560E+09 | 0.456052E+09 | 7710235.71 |
| June | 0.166461E+09 | 52568631.13 | 0.113892E+09 | 0.491415E+09 | 726974.75 |
| July | 0.157832E+09 | 45185244.23 | 0.112646E+09 | 0.546858E+09 | 0.00 |
| August | 0.161596E+09 | 49000876.05 | 0.112595E+09 | 0.557274E+09 | 0.00 |
| September | 0.148987E+09 | 46838450.68 | 0.102148E+09 | 0.441001E+09 | 2178897.29 |
| October | 0.136839E+09 | 44204558.38 | 92634435.10 | 0.342871E+09 | 14011918.57 |
| November | 0.113977E+09 | 37321388.83 | 76655627.41 | 0.230710E+09 | 55095831.77 |
| December | 98539195.66 | 29848443.94 | 68690751.72 | 0.150321E+09 | 0.123623E+09 |
| Annual Sum or Average | 0.164903E+10 | 0.498037E+09 | 0.115099E+10 | 0.408483E+10 | 0.608046E+09 |
| Minimum of Months | 98539195.66 | 29848443.94 | 68690751.72 | 0.136178E+09 | 0.00 |
| Maximum of Months | 0.166461E+09 | 52568631.13 | 0.116560E+09 | 0.557274E+09 | 0.154722E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.103809E+09 | 29878949.63 | 73929877.94 | 0.145926E+09 | 0.148892E+09 |
| February | 0.106921E+09 | 30593048.71 | 76327918.38 | 0.166997E+09 | 0.111410E+09 |
| March | 0.140092E+09 | 41579452.77 | 98512991.88 | 0.255875E+09 | 89253206.88 |
| April | 0.147800E+09 | 41404033.31 | 0.106396E+09 | 0.321038E+09 | 45799436.05 |
| May | 0.166174E+09 | 49614264.66 | 0.116560E+09 | 0.456083E+09 | 7699735.98 |
| June | 0.166461E+09 | 52568631.13 | 0.113892E+09 | 0.490545E+09 | 727304.22 |
| July | 0.157832E+09 | 45185244.23 | 0.112646E+09 | 0.546654E+09 | 0.00 |
| August | 0.161596E+09 | 49000876.05 | 0.112595E+09 | 0.558490E+09 | 0.00 |
| September | 0.148987E+09 | 46838450.68 | 0.102148E+09 | 0.444479E+09 | 2114632.51 |
| October | 0.136839E+09 | 44204558.38 | 92634435.10 | 0.348589E+09 | 13514809.30 |
| November | 0.113977E+09 | 37321388.83 | 76655627.41 | 0.237004E+09 | 53323650.99 |
| December | 98539195.66 | 29848443.94 | 68690751.72 | 0.157939E+09 | 0.119126E+09 |
| Annual Sum or Average | 0.164903E+10 | 0.498037E+09 | 0.115099E+10 | 0.412962E+10 | 0.591861E+09 |
| Minimum of Months | 98539195.66 | 29848443.94 | 68690751.72 | 0.145926E+09 | 0.00 |
| Maximum of Months | 0.166461E+09 | 52568631.13 | 0.116560E+09 | 0.558490E+09 | 0.148892E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88623175.80 | 0.00 | 88623175.80 | 93437960.53 | 0.233700E+09 |
| February | 91756479.98 | 0.00 | 91756479.98 | 0.119187E+09 | 0.174932E+09 |
| March | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.200659E+09 | 0.138315E+09 |
| April | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.294665E+09 | 69162735.90 |
| May | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.485601E+09 | 11196911.86 |
| June | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.546926E+09 | 1172699.40 |
| July | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.644409E+09 | 0.00 |
| August | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.631802E+09 | 0.00 |
| September | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.461327E+09 | 3159565.59 |
| October | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.331462E+09 | 20257239.89 |
| November | 90794144.06 | 0.00 | 90794144.06 | 0.193698E+09 | 81713786.35 |
| December | 82718268.40 | 0.00 | 82718268.40 | 0.108931E+09 | 0.185007E+09 |
| Annual Sum or Average | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.411210E+10 | 0.918617E+09 |
| Minimum of Months | 82718268.40 | 0.00 | 82718268.40 | 93437960.53 | 0.00 |
| Maximum of Months | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.644409E+09 | 0.233700E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.445874E+09 | 0.220305E+09 |
| February | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.407652E+09 | 0.167475E+09 |
| March | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.413432E+09 | 0.136494E+09 |
| April | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.397440E+09 | 69778183.62 |
| May | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.482744E+09 | 11087580.30 |
| June | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.505756E+09 | 870385.53 |
| July | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.625513E+09 | 0.00 |
| August | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.689925E+09 | 0.00 |
| September | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.656568E+09 | 2991047.37 |
| October | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.676481E+09 | 18403078.68 |
| November | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.596317E+09 | 77846562.71 |
| December | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.481695E+09 | 0.177589E+09 |
| Annual Sum or Average | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.637940E+10 | 0.882840E+09 |
| Minimum of Months | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.397440E+09 | 0.00 |
| Maximum of Months | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.689925E+09 | 0.220305E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105500E+09 | 31934045.17 | 73565630.67 | 0.133883E+09 | 0.147661E+09 |
| February | 0.103672E+09 | 27988141.95 | 75684311.64 | 0.151049E+09 | 0.108991E+09 |
| March | 0.126984E+09 | 31208877.80 | 95775091.86 | 0.223484E+09 | 85465235.91 |
| April | 0.150052E+09 | 43886149.05 | 0.106166E+09 | 0.322274E+09 | 42533564.85 |
| May | 0.172521E+09 | 54863107.39 | 0.117658E+09 | 0.466850E+09 | 6553849.22 |
| June | 0.163769E+09 | 50105710.88 | 0.113664E+09 | 0.483310E+09 | 551263.62 |
| July | 0.158042E+09 | 45627695.76 | 0.112414E+09 | 0.548013E+09 | 0.00 |
| August | 0.161601E+09 | 49510927.60 | 0.112090E+09 | 0.560309E+09 | 0.00 |
| September | 0.146908E+09 | 45301204.88 | 0.101606E+09 | 0.437704E+09 | 1720981.73 |
| October | 0.137691E+09 | 44866965.27 | 92824257.39 | 0.343381E+09 | 11529929.14 |
| November | 0.111852E+09 | 35388966.58 | 76462808.30 | 0.220816E+09 | 50693441.83 |
| December | 93401161.53 | 25580096.36 | 67821065.17 | 0.134226E+09 | 0.118176E+09 |
| Annual Sum or Average | 0.163199E+10 | 0.486262E+09 | 0.114573E+10 | 0.402530E+10 | 0.573876E+09 |
| Minimum of Months | 93401161.53 | 25580096.36 | 67821065.17 | 0.133883E+09 | 0.00 |
| Maximum of Months | 0.172521E+09 | 54863107.39 | 0.117658E+09 | 0.560309E+09 | 0.147661E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105500E+09 | 31934045.17 | 73565630.67 | 0.142499E+09 | 0.140841E+09 |
| February | 0.103672E+09 | 27988141.95 | 75684311.64 | 0.156396E+09 | 0.106268E+09 |
| March | 0.126984E+09 | 31208877.80 | 95775091.86 | 0.227081E+09 | 84154844.72 |
| April | 0.150052E+09 | 43886149.05 | 0.106166E+09 | 0.324016E+09 | 42121844.94 |
| May | 0.172521E+09 | 54863107.39 | 0.117658E+09 | 0.466898E+09 | 6536011.25 |
| June | 0.163769E+09 | 50105710.88 | 0.113664E+09 | 0.482472E+09 | 551283.11 |
| July | 0.158042E+09 | 45627695.76 | 0.112414E+09 | 0.547817E+09 | 0.00 |
| August | 0.161601E+09 | 49510927.60 | 0.112090E+09 | 0.561518E+09 | 0.00 |
| September | 0.146908E+09 | 45301204.88 | 0.101606E+09 | 0.441144E+09 | 1670559.27 |
| October | 0.137691E+09 | 44866965.27 | 92824257.39 | 0.349058E+09 | 11103385.14 |
| November | 0.111852E+09 | 35388966.58 | 76462808.30 | 0.226898E+09 | 48972427.37 |
| December | 93401161.53 | 25580096.36 | 67821065.17 | 0.141249E+09 | 0.113298E+09 |
| Annual Sum or Average | 0.163199E+10 | 0.486262E+09 | 0.114573E+10 | 0.406705E+10 | 0.555518E+09 |
| Minimum of Months | 93401161.53 | 25580096.36 | 67821065.17 | 0.141249E+09 | 0.00 |
| Maximum of Months | 0.172521E+09 | 54863107.39 | 0.117658E+09 | 0.561518E+09 | 0.140841E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88623175.80 | 0.00 | 88623175.80 | 89478069.81 | 0.231651E+09 |
| February | 91756479.98 | 0.00 | 91756479.98 | 0.116295E+09 | 0.173042E+09 |
| March | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.198726E+09 | 0.136596E+09 |
| April | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.292910E+09 | 68619244.56 |
| May | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.484631E+09 | 11094606.02 |
| June | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.546602E+09 | 1151462.50 |
| July | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.644100E+09 | 0.00 |
| August | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.631446E+09 | 0.00 |
| September | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.460994E+09 | 3141623.91 |
| October | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.330795E+09 | 20174490.56 |
| November | 90794144.06 | 0.00 | 90794144.06 | 0.192192E+09 | 81310308.37 |
| December | 82718268.40 | 0.00 | 82718268.40 | 0.106357E+09 | 0.183610E+09 |
| Annual Sum or Average | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.409453E+10 | 0.910391E+09 |
| Minimum of Months | 82718268.40 | 0.00 | 82718268.40 | 89478069.81 | 0.00 |
| Maximum of Months | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.644100E+09 | 0.231651E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88623175.80 | 0.00 | 88623175.80 | 92059252.21 | 0.239756E+09 |
| February | 91756479.98 | 0.00 | 91756479.98 | 0.119689E+09 | 0.177750E+09 |
| March | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.203574E+09 | 0.138892E+09 |
| April | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.300150E+09 | 68908540.62 |
| May | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.496507E+09 | 10813780.35 |
| June | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.559320E+09 | 1070432.56 |
| July | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.658657E+09 | 0.00 |
| August | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.646380E+09 | 0.00 |
| September | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.472774E+09 | 3023717.20 |
| October | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.339768E+09 | 19899929.76 |
| November | 90794144.06 | 0.00 | 90794144.06 | 0.197507E+09 | 82113394.24 |
| December | 82718268.40 | 0.00 | 82718268.40 | 0.108869E+09 | 0.188569E+09 |
| Annual Sum or Average | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.419525E+10 | 0.930797E+09 |
| Minimum of Months | 82718268.40 | 0.00 | 82718268.40 | 92059252.21 | 0.00 |
| Maximum of Months | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.658657E+09 | 0.239756E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88623175.80 | 0.00 | 88623175.80 | 91742885.27 | 0.239683E+09 |
| February | 91756479.98 | 0.00 | 91756479.98 | 0.119458E+09 | 0.177660E+09 |
| March | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.203449E+09 | 0.138776E+09 |
| April | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.300056E+09 | 68879768.72 |
| May | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.496460E+09 | 10807197.79 |
| June | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.559305E+09 | 1069020.62 |
| July | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.658644E+09 | 0.00 |
| August | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.646364E+09 | 0.00 |
| September | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.472758E+09 | 3021921.67 |
| October | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.339730E+09 | 19890846.45 |
| November | 90794144.06 | 0.00 | 90794144.06 | 0.197409E+09 | 82089572.44 |
| December | 82718268.40 | 0.00 | 82718268.40 | 0.108676E+09 | 0.188495E+09 |
| Annual Sum or Average | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.419405E+10 | 0.930372E+09 |
| Minimum of Months | 82718268.40 | 0.00 | 82718268.40 | 91742885.27 | 0.00 |
| Maximum of Months | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.658644E+09 | 0.239683E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.446756E+09 | 0.227780E+09 |
| February | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.409924E+09 | 0.172111E+09 |
| March | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.417657E+09 | 0.138918E+09 |
| April | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.404318E+09 | 70137807.78 |
| May | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.494612E+09 | 10834731.58 |
| June | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.518706E+09 | 802228.07 |
| July | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.639994E+09 | 0.00 |
| August | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.704601E+09 | 0.00 |
| September | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.667696E+09 | 2898803.85 |
| October | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.684601E+09 | 18226060.02 |
| November | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.600603E+09 | 78661899.69 |
| December | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.482934E+09 | 0.182186E+09 |
| Annual Sum or Average | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.647240E+10 | 0.902558E+09 |
| Minimum of Months | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.404318E+09 | 0.00 |
| Maximum of Months | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.704601E+09 | 0.227780E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.446521E+09 | 0.227688E+09 |
| February | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.409756E+09 | 0.172042E+09 |
| March | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.417549E+09 | 0.138822E+09 |
| April | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.404229E+09 | 70108660.34 |
| May | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.494565E+09 | 10828460.53 |
| June | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.518689E+09 | 800978.94 |
| July | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.639979E+09 | 0.00 |
| August | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.704585E+09 | 0.00 |
| September | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.667682E+09 | 2897271.32 |
| October | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.684571E+09 | 18217416.88 |
| November | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.600526E+09 | 78634185.00 |
| December | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.482793E+09 | 0.182123E+09 |
| Annual Sum or Average | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.647144E+10 | 0.902162E+09 |
| Minimum of Months | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.404229E+09 | 0.00 |
| Maximum of Months | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.704585E+09 | 0.227688E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW14
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 25315076.64 | 7662704.12 | 17652372.52 | 31467367.32 | 40190667.69 |
| February | 24876627.23 | 6715868.58 | 18160758.64 | 34915817.18 | 30754289.12 |
| March | 30470320.40 | 7488697.26 | 22981623.13 | 50941964.41 | 25051163.31 |
| April | 36005665.65 | 10530660.10 | 25475005.55 | 73201928.05 | 13995288.17 |
| May | 41397035.71 | 13164625.93 | 28232409.78 | 0.103919E+09 | 3076645.90 |
| June | 39297122.34 | 12023069.28 | 27274053.06 | 0.106651E+09 | 589749.12 |
| July | 37922842.04 | 10948551.32 | 26974290.73 | 0.120761E+09 | 3189.91 |
| August | 38776861.92 | 11880348.61 | 26896513.31 | 0.123780E+09 | 0.00 |
| September | 35251100.85 | 10870208.51 | 24380892.34 | 96491478.56 | 966425.78 |
| October | 33039569.33 | 10766010.94 | 22273558.39 | 76619141.19 | 5040170.50 |
| November | 26839288.66 | 8491726.58 | 18347562.09 | 50282569.05 | 16055771.41 |
| December | 22411988.89 | 6138048.24 | 16273940.65 | 30952705.06 | 33087436.84 |
| Annual Sum or Average | 0.391603E+09 | 0.116681E+09 | 0.274923E+09 | 0.899984E+09 | 0.168811E+09 |
| Minimum of Months | 22411988.89 | 6138048.24 | 16273940.65 | 30952705.06 | 0.00 |
| Maximum of Months | 41397035.71 | 13164625.93 | 28232409.78 | 0.123780E+09 | 40190667.69 |
Report: WindowEnergyReportMonthly
For: ENTRANCE DOOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 75394598.24 | 22821439.85 | 52573158.39 | 89377993.88 | 0.127105E+09 |
| February | 74088786.76 | 20001527.98 | 54087258.79 | 0.100518E+09 | 97390802.34 |
| March | 90748197.09 | 22303204.11 | 68444992.98 | 0.146216E+09 | 81840192.28 |
| April | 0.107234E+09 | 31362926.47 | 75870906.32 | 0.208899E+09 | 51398254.96 |
| May | 0.123291E+09 | 39207532.22 | 84083142.32 | 0.287338E+09 | 16357964.70 |
| June | 0.117037E+09 | 35807692.40 | 81228917.54 | 0.289563E+09 | 6321744.95 |
| July | 0.112944E+09 | 32607510.52 | 80336150.69 | 0.321485E+09 | 443656.68 |
| August | 0.115487E+09 | 35382634.74 | 80104510.20 | 0.327509E+09 | 257706.86 |
| September | 0.104987E+09 | 32374186.13 | 72612364.90 | 0.256419E+09 | 8252484.86 |
| October | 98400059.82 | 32063859.85 | 66336199.96 | 0.207921E+09 | 28948991.16 |
| November | 79934080.96 | 25290475.03 | 54643605.93 | 0.138540E+09 | 64147469.82 |
| December | 66748480.44 | 18280635.20 | 48467845.23 | 85712283.03 | 0.110239E+09 |
| Annual Sum or Average | 0.116629E+10 | 0.347504E+09 | 0.818789E+09 | 0.245950E+10 | 0.592703E+09 |
| Minimum of Months | 66748480.44 | 18280635.20 | 48467845.23 | 85712283.03 | 257706.86 |
| Maximum of Months | 0.123291E+09 | 39207532.22 | 84083142.32 | 0.327509E+09 | 0.127105E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW14
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 25315076.64 | 7662704.12 | 17652372.52 | 29739580.49 | 42305035.27 |
| February | 24876627.23 | 6715868.58 | 18160758.64 | 33950520.64 | 32059993.21 |
| March | 30470320.40 | 7488697.26 | 22981623.13 | 50474148.78 | 26028310.97 |
| April | 36005665.65 | 10530660.10 | 25475005.55 | 73782475.10 | 14503960.67 |
| May | 41397035.71 | 13164625.93 | 28232409.78 | 0.106118E+09 | 3196704.09 |
| June | 39297122.34 | 12023069.28 | 27274053.06 | 0.109193E+09 | 630521.00 |
| July | 37922842.04 | 10948551.32 | 26974290.73 | 0.124253E+09 | 4141.78 |
| August | 38776861.92 | 11880348.61 | 26896513.31 | 0.127296E+09 | 0.00 |
| September | 35251100.85 | 10870208.51 | 24380892.34 | 98821210.79 | 1037405.62 |
| October | 33039569.33 | 10766010.94 | 22273558.39 | 77963863.92 | 5348748.69 |
| November | 26839288.66 | 8491726.58 | 18347562.09 | 50287590.03 | 16810044.15 |
| December | 22411988.89 | 6138048.24 | 16273940.65 | 29808515.37 | 34641909.67 |
| Annual Sum or Average | 0.391603E+09 | 0.116681E+09 | 0.274923E+09 | 0.911687E+09 | 0.176567E+09 |
| Minimum of Months | 22411988.89 | 6138048.24 | 16273940.65 | 29739580.49 | 0.00 |
| Maximum of Months | 41397035.71 | 13164625.93 | 28232409.78 | 0.127296E+09 | 42305035.27 |
Report: WindowZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 217.96 | 147.84 | 145.69 | 61.38 | 84.31 | 0.00 | 0.00 |
| February | 238.70 | 121.54 | 145.04 | 54.14 | 90.90 | 0.00 | 0.00 |
| March | 253.55 | 87.93 | 133.50 | 36.51 | 96.99 | 0.00 | 0.00 |
| April | 283.04 | 47.84 | 123.37 | 24.22 | 99.15 | 0.00 | 0.00 |
| May | 355.00 | 8.40 | 117.17 | 19.45 | 97.72 | 0.00 | 0.00 |
| June | 386.12 | 0.97 | 116.08 | 20.37 | 95.71 | 0.00 | 0.00 |
| July | 437.98 | 0.00 | 110.77 | 17.30 | 93.47 | 0.00 | 0.00 |
| August | 463.36 | 0.00 | 120.39 | 22.47 | 97.92 | 0.00 | 0.00 |
| September | 420.94 | 3.14 | 137.58 | 37.05 | 100.52 | 0.00 | 0.00 |
| October | 379.71 | 17.11 | 154.46 | 57.36 | 97.10 | 0.00 | 0.00 |
| November | 318.68 | 59.97 | 158.92 | 70.03 | 88.89 | 0.00 | 0.00 |
| December | 234.88 | 121.59 | 142.77 | 63.37 | 79.40 | 0.00 | 0.00 |
| Annual Sum or Average | 333.05 | 51.04 | 133.72 | 40.22 | 93.50 | 0.00 | 0.00 |
| Minimum of Months | 217.96 | 0.00 | 110.77 | 17.30 | 79.40 | 0.00 | 0.00 |
| Maximum of Months | 463.36 | 147.84 | 158.92 | 70.03 | 100.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 84.21 | 152.88 | 71.85 | 11.16 | 60.69 | 0.00 | 0.00 |
| February | 117.65 | 122.57 | 82.13 | 12.65 | 69.48 | 0.00 | 0.00 |
| March | 173.48 | 86.85 | 95.88 | 15.53 | 80.35 | 0.00 | 0.00 |
| April | 242.61 | 46.82 | 106.19 | 16.12 | 90.07 | 0.00 | 0.00 |
| May | 355.53 | 8.20 | 117.43 | 20.27 | 97.16 | 0.00 | 0.00 |
| June | 401.89 | 1.08 | 123.27 | 23.48 | 99.79 | 0.00 | 0.00 |
| July | 444.56 | 0.00 | 113.21 | 18.42 | 94.79 | 0.00 | 0.00 |
| August | 441.49 | 0.00 | 111.01 | 18.84 | 92.17 | 0.00 | 0.00 |
| September | 345.50 | 3.08 | 103.52 | 18.08 | 85.44 | 0.00 | 0.00 |
| October | 250.67 | 17.29 | 91.89 | 16.50 | 75.39 | 0.00 | 0.00 |
| November | 163.33 | 61.07 | 79.00 | 14.40 | 64.60 | 0.00 | 0.00 |
| December | 95.44 | 124.38 | 67.67 | 11.14 | 56.53 | 0.00 | 0.00 |
| Annual Sum or Average | 260.55 | 51.70 | 96.97 | 16.39 | 80.58 | 0.00 | 0.00 |
| Minimum of Months | 84.21 | 0.00 | 67.67 | 11.14 | 56.53 | 0.00 | 0.00 |
| Maximum of Months | 444.56 | 152.88 | 123.27 | 23.48 | 99.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 212.72 | 166.16 | 146.32 | 62.15 | 84.17 | 0.00 | 0.00 |
| February | 228.57 | 143.75 | 143.70 | 53.07 | 90.63 | 0.00 | 0.00 |
| March | 231.22 | 112.43 | 128.60 | 32.64 | 95.96 | 0.00 | 0.00 |
| April | 259.34 | 79.10 | 124.24 | 25.18 | 99.06 | 0.00 | 0.00 |
| May | 307.45 | 29.53 | 119.54 | 21.41 | 98.13 | 0.00 | 0.00 |
| June | 321.06 | 14.20 | 115.04 | 19.42 | 95.62 | 0.00 | 0.00 |
| July | 356.69 | 2.20 | 110.85 | 17.47 | 93.39 | 0.00 | 0.00 |
| August | 386.06 | 1.52 | 120.39 | 22.66 | 97.73 | 0.00 | 0.00 |
| September | 356.17 | 19.97 | 136.78 | 36.46 | 100.32 | 0.00 | 0.00 |
| October | 340.33 | 54.15 | 154.78 | 57.61 | 97.17 | 0.00 | 0.00 |
| November | 293.63 | 103.18 | 158.10 | 69.29 | 88.81 | 0.00 | 0.00 |
| December | 220.42 | 149.24 | 140.85 | 61.77 | 79.08 | 0.00 | 0.00 |
| Annual Sum or Average | 293.17 | 72.58 | 133.18 | 39.85 | 93.33 | 0.00 | 0.00 |
| Minimum of Months | 212.72 | 1.52 | 110.85 | 17.47 | 79.08 | 0.00 | 0.00 |
| Maximum of Months | 386.06 | 166.16 | 158.10 | 69.29 | 100.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 78.64 | 146.06 | 72.48 | 11.92 | 60.55 | 0.00 | 0.00 |
| February | 110.49 | 118.05 | 80.78 | 11.57 | 69.21 | 0.00 | 0.00 |
| March | 160.54 | 83.04 | 90.98 | 11.65 | 79.33 | 0.00 | 0.00 |
| April | 242.24 | 44.37 | 107.06 | 17.07 | 89.98 | 0.00 | 0.00 |
| May | 359.24 | 7.70 | 119.80 | 22.23 | 97.57 | 0.00 | 0.00 |
| June | 398.89 | 1.01 | 122.23 | 22.53 | 99.70 | 0.00 | 0.00 |
| July | 444.89 | 0.00 | 113.28 | 18.58 | 94.70 | 0.00 | 0.00 |
| August | 442.36 | 0.00 | 111.01 | 19.03 | 91.98 | 0.00 | 0.00 |
| September | 343.85 | 2.73 | 102.72 | 17.49 | 85.23 | 0.00 | 0.00 |
| October | 249.70 | 15.48 | 92.21 | 16.75 | 75.46 | 0.00 | 0.00 |
| November | 156.16 | 56.32 | 78.18 | 13.65 | 64.53 | 0.00 | 0.00 |
| December | 85.45 | 118.74 | 65.76 | 9.55 | 56.20 | 0.00 | 0.00 |
| Annual Sum or Average | 256.91 | 49.15 | 96.43 | 16.02 | 80.41 | 0.00 | 0.00 |
| Minimum of Months | 78.64 | 0.00 | 65.76 | 9.55 | 56.20 | 0.00 | 0.00 |
| Maximum of Months | 444.89 | 146.06 | 122.23 | 22.53 | 99.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 32.92 | 94.76 | 33.09 | 0.00 | 33.09 | 0.00 | 0.00 |
| February | 49.57 | 75.90 | 37.93 | 0.00 | 37.93 | 0.00 | 0.00 |
| March | 77.18 | 53.10 | 43.57 | 0.00 | 43.57 | 0.00 | 0.00 |
| April | 117.68 | 27.93 | 49.17 | 0.14 | 49.02 | 0.00 | 0.00 |
| May | 186.66 | 4.62 | 55.39 | 1.75 | 53.64 | 0.00 | 0.00 |
| June | 216.06 | 0.57 | 59.05 | 3.20 | 55.85 | 0.00 | 0.00 |
| July | 245.28 | 0.00 | 54.28 | 1.55 | 52.73 | 0.00 | 0.00 |
| August | 239.40 | 0.00 | 50.68 | 0.55 | 50.13 | 0.00 | 0.00 |
| September | 179.95 | 1.63 | 46.04 | 0.01 | 46.03 | 0.00 | 0.00 |
| October | 124.77 | 9.55 | 40.80 | 0.00 | 40.80 | 0.00 | 0.00 |
| November | 74.47 | 35.89 | 35.03 | 0.00 | 35.03 | 0.00 | 0.00 |
| December | 38.93 | 75.86 | 30.88 | 0.00 | 30.88 | 0.00 | 0.00 |
| Annual Sum or Average | 132.42 | 31.45 | 44.68 | 0.60 | 44.08 | 0.00 | 0.00 |
| Minimum of Months | 32.92 | 0.00 | 30.88 | 0.00 | 30.88 | 0.00 | 0.00 |
| Maximum of Months | 245.28 | 94.76 | 59.05 | 3.20 | 55.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 32.89 | 94.77 | 33.09 | 0.00 | 33.09 | 0.00 | 0.00 |
| February | 49.54 | 75.90 | 37.93 | 0.00 | 37.93 | 0.00 | 0.00 |
| March | 77.17 | 53.08 | 43.57 | 0.00 | 43.57 | 0.00 | 0.00 |
| April | 117.67 | 27.93 | 49.17 | 0.14 | 49.02 | 0.00 | 0.00 |
| May | 186.65 | 4.62 | 55.39 | 1.75 | 53.64 | 0.00 | 0.00 |
| June | 216.05 | 0.57 | 59.05 | 3.20 | 55.85 | 0.00 | 0.00 |
| July | 245.27 | 0.00 | 54.28 | 1.55 | 52.73 | 0.00 | 0.00 |
| August | 239.39 | 0.00 | 50.68 | 0.55 | 50.13 | 0.00 | 0.00 |
| September | 179.95 | 1.63 | 46.04 | 0.01 | 46.03 | 0.00 | 0.00 |
| October | 124.76 | 9.55 | 40.80 | 0.00 | 40.80 | 0.00 | 0.00 |
| November | 74.46 | 35.89 | 35.03 | 0.00 | 35.03 | 0.00 | 0.00 |
| December | 38.91 | 75.86 | 30.88 | 0.00 | 30.88 | 0.00 | 0.00 |
| Annual Sum or Average | 132.40 | 31.45 | 44.68 | 0.60 | 44.08 | 0.00 | 0.00 |
| Minimum of Months | 32.89 | 0.00 | 30.88 | 0.00 | 30.88 | 0.00 | 0.00 |
| Maximum of Months | 245.27 | 94.77 | 59.05 | 3.20 | 55.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 168.15 | 88.71 | 106.93 | 50.23 | 56.71 | 0.00 | 0.00 |
| February | 171.63 | 73.63 | 100.84 | 41.50 | 59.35 | 0.00 | 0.00 |
| March | 158.18 | 53.55 | 81.19 | 20.99 | 60.20 | 0.00 | 0.00 |
| April | 158.56 | 28.73 | 66.35 | 8.25 | 58.10 | 0.00 | 0.00 |
| May | 185.96 | 4.74 | 55.13 | 0.93 | 54.20 | 0.00 | 0.00 |
| June | 199.92 | 0.48 | 51.86 | 0.09 | 51.77 | 0.00 | 0.00 |
| July | 238.47 | 0.00 | 51.85 | 0.43 | 51.42 | 0.00 | 0.00 |
| August | 261.48 | 0.00 | 60.06 | 4.18 | 55.88 | 0.00 | 0.00 |
| September | 256.25 | 1.64 | 80.10 | 18.98 | 61.12 | 0.00 | 0.00 |
| October | 255.34 | 9.22 | 103.37 | 40.86 | 62.51 | 0.00 | 0.00 |
| November | 232.07 | 34.78 | 114.95 | 55.64 | 59.31 | 0.00 | 0.00 |
| December | 180.51 | 72.60 | 105.98 | 52.22 | 53.76 | 0.00 | 0.00 |
| Annual Sum or Average | 205.76 | 30.48 | 81.43 | 24.43 | 57.00 | 0.00 | 0.00 |
| Minimum of Months | 158.18 | 0.00 | 51.85 | 0.09 | 51.42 | 0.00 | 0.00 |
| Maximum of Months | 261.48 | 88.71 | 114.95 | 55.64 | 62.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 167.78 | 89.21 | 106.93 | 50.23 | 56.71 | 0.00 | 0.00 |
| February | 171.21 | 74.26 | 100.84 | 41.50 | 59.35 | 0.00 | 0.00 |
| March | 157.68 | 54.23 | 81.19 | 20.99 | 60.20 | 0.00 | 0.00 |
| April | 157.75 | 29.51 | 66.35 | 8.25 | 58.10 | 0.00 | 0.00 |
| May | 184.53 | 5.09 | 55.13 | 0.93 | 54.20 | 0.00 | 0.00 |
| June | 198.25 | 0.54 | 51.86 | 0.09 | 51.77 | 0.00 | 0.00 |
| July | 236.69 | 0.00 | 51.85 | 0.43 | 51.42 | 0.00 | 0.00 |
| August | 259.77 | 0.00 | 60.06 | 4.18 | 55.88 | 0.00 | 0.00 |
| September | 254.65 | 1.79 | 80.10 | 18.98 | 61.12 | 0.00 | 0.00 |
| October | 254.13 | 9.82 | 103.37 | 40.86 | 62.51 | 0.00 | 0.00 |
| November | 231.23 | 35.72 | 114.95 | 55.64 | 59.31 | 0.00 | 0.00 |
| December | 180.01 | 73.31 | 105.98 | 52.22 | 53.76 | 0.00 | 0.00 |
| Annual Sum or Average | 204.68 | 30.93 | 81.43 | 24.43 | 57.00 | 0.00 | 0.00 |
| Minimum of Months | 157.68 | 0.00 | 51.85 | 0.09 | 51.42 | 0.00 | 0.00 |
| Maximum of Months | 259.77 | 89.21 | 114.95 | 55.64 | 62.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 218.12 | 145.63 | 145.69 | 61.38 | 84.31 | 0.00 | 0.00 |
| February | 237.77 | 120.73 | 145.04 | 54.14 | 90.90 | 0.00 | 0.00 |
| March | 252.24 | 88.14 | 133.50 | 36.51 | 96.99 | 0.00 | 0.00 |
| April | 282.63 | 47.14 | 123.37 | 24.22 | 99.15 | 0.00 | 0.00 |
| May | 358.84 | 7.58 | 117.17 | 19.45 | 97.72 | 0.00 | 0.00 |
| June | 393.23 | 0.70 | 116.08 | 20.37 | 95.71 | 0.00 | 0.00 |
| July | 447.73 | 0.00 | 110.77 | 17.30 | 93.47 | 0.00 | 0.00 |
| August | 475.84 | 0.00 | 120.39 | 22.47 | 97.92 | 0.00 | 0.00 |
| September | 432.01 | 2.21 | 137.58 | 37.05 | 100.52 | 0.00 | 0.00 |
| October | 387.74 | 13.08 | 154.46 | 57.36 | 97.10 | 0.00 | 0.00 |
| November | 323.50 | 53.39 | 158.92 | 70.03 | 88.89 | 0.00 | 0.00 |
| December | 237.30 | 116.20 | 142.77 | 63.37 | 79.40 | 0.00 | 0.00 |
| Annual Sum or Average | 337.84 | 49.24 | 133.72 | 40.22 | 93.50 | 0.00 | 0.00 |
| Minimum of Months | 218.12 | 0.00 | 110.77 | 17.30 | 79.40 | 0.00 | 0.00 |
| Maximum of Months | 475.84 | 145.63 | 158.92 | 70.03 | 100.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 85.78 | 149.73 | 71.85 | 11.16 | 60.69 | 0.00 | 0.00 |
| February | 117.59 | 122.05 | 82.13 | 12.65 | 69.48 | 0.00 | 0.00 |
| March | 172.47 | 87.50 | 95.88 | 15.53 | 80.35 | 0.00 | 0.00 |
| April | 242.45 | 46.34 | 106.19 | 16.12 | 90.07 | 0.00 | 0.00 |
| May | 359.48 | 7.43 | 117.43 | 20.27 | 97.16 | 0.00 | 0.00 |
| June | 408.89 | 0.80 | 123.27 | 23.48 | 99.79 | 0.00 | 0.00 |
| July | 454.58 | 0.00 | 113.21 | 18.42 | 94.79 | 0.00 | 0.00 |
| August | 454.21 | 0.00 | 111.01 | 18.84 | 92.17 | 0.00 | 0.00 |
| September | 357.14 | 2.20 | 103.52 | 18.08 | 85.44 | 0.00 | 0.00 |
| October | 259.52 | 13.46 | 91.89 | 16.50 | 75.39 | 0.00 | 0.00 |
| November | 168.99 | 54.65 | 79.00 | 14.40 | 64.60 | 0.00 | 0.00 |
| December | 98.68 | 118.37 | 67.67 | 11.14 | 56.53 | 0.00 | 0.00 |
| Annual Sum or Average | 265.87 | 49.89 | 96.97 | 16.39 | 80.58 | 0.00 | 0.00 |
| Minimum of Months | 85.78 | 0.00 | 67.67 | 11.14 | 56.53 | 0.00 | 0.00 |
| Maximum of Months | 454.58 | 149.73 | 123.27 | 23.48 | 99.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 216.07 | 142.29 | 146.32 | 62.15 | 84.17 | 0.00 | 0.00 |
| February | 232.28 | 117.93 | 143.70 | 53.07 | 90.63 | 0.00 | 0.00 |
| March | 239.86 | 84.83 | 128.60 | 32.64 | 95.96 | 0.00 | 0.00 |
| April | 281.99 | 44.35 | 124.24 | 25.18 | 99.06 | 0.00 | 0.00 |
| May | 362.16 | 6.72 | 119.54 | 21.41 | 98.13 | 0.00 | 0.00 |
| June | 390.01 | 0.61 | 115.04 | 19.42 | 95.62 | 0.00 | 0.00 |
| July | 448.03 | 0.00 | 110.85 | 17.47 | 93.39 | 0.00 | 0.00 |
| August | 476.77 | 0.00 | 120.39 | 22.66 | 97.73 | 0.00 | 0.00 |
| September | 430.50 | 1.95 | 136.78 | 36.46 | 100.32 | 0.00 | 0.00 |
| October | 387.73 | 12.16 | 154.78 | 57.61 | 97.17 | 0.00 | 0.00 |
| November | 319.57 | 51.86 | 158.10 | 69.29 | 88.81 | 0.00 | 0.00 |
| December | 230.91 | 114.12 | 140.85 | 61.77 | 79.08 | 0.00 | 0.00 |
| Annual Sum or Average | 335.27 | 47.75 | 133.18 | 39.85 | 93.33 | 0.00 | 0.00 |
| Minimum of Months | 216.07 | 0.00 | 110.85 | 17.47 | 79.08 | 0.00 | 0.00 |
| Maximum of Months | 476.77 | 142.29 | 158.10 | 69.29 | 100.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 80.16 | 142.79 | 72.48 | 11.92 | 60.55 | 0.00 | 0.00 |
| February | 110.45 | 117.61 | 80.78 | 11.57 | 69.21 | 0.00 | 0.00 |
| March | 159.59 | 83.70 | 90.98 | 11.65 | 79.33 | 0.00 | 0.00 |
| April | 242.10 | 43.85 | 107.06 | 17.07 | 89.98 | 0.00 | 0.00 |
| May | 363.18 | 6.93 | 119.80 | 22.23 | 97.57 | 0.00 | 0.00 |
| June | 405.72 | 0.73 | 122.23 | 22.53 | 99.70 | 0.00 | 0.00 |
| July | 454.90 | 0.00 | 113.28 | 18.58 | 94.70 | 0.00 | 0.00 |
| August | 455.16 | 0.00 | 111.01 | 19.03 | 91.98 | 0.00 | 0.00 |
| September | 355.60 | 1.92 | 102.72 | 17.49 | 85.23 | 0.00 | 0.00 |
| October | 258.88 | 11.95 | 92.21 | 16.75 | 75.46 | 0.00 | 0.00 |
| November | 162.25 | 50.40 | 78.18 | 13.65 | 64.53 | 0.00 | 0.00 |
| December | 88.87 | 112.88 | 65.76 | 9.55 | 56.20 | 0.00 | 0.00 |
| Annual Sum or Average | 262.32 | 47.41 | 96.43 | 16.02 | 80.41 | 0.00 | 0.00 |
| Minimum of Months | 80.16 | 0.00 | 65.76 | 9.55 | 56.20 | 0.00 | 0.00 |
| Maximum of Months | 455.16 | 142.79 | 122.23 | 22.53 | 99.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 33.60 | 93.31 | 33.09 | 0.00 | 33.09 | 0.00 | 0.00 |
| February | 49.79 | 75.34 | 37.93 | 0.00 | 37.93 | 0.00 | 0.00 |
| March | 77.07 | 53.15 | 43.57 | 0.00 | 43.57 | 0.00 | 0.00 |
| April | 118.13 | 27.42 | 49.17 | 0.14 | 49.02 | 0.00 | 0.00 |
| May | 189.32 | 4.18 | 55.39 | 1.75 | 53.64 | 0.00 | 0.00 |
| June | 220.15 | 0.43 | 59.05 | 3.20 | 55.85 | 0.00 | 0.00 |
| July | 250.89 | 0.00 | 54.28 | 1.55 | 52.73 | 0.00 | 0.00 |
| August | 246.21 | 0.00 | 50.68 | 0.55 | 50.13 | 0.00 | 0.00 |
| September | 186.15 | 1.22 | 46.04 | 0.01 | 46.03 | 0.00 | 0.00 |
| October | 129.49 | 7.74 | 40.80 | 0.00 | 40.80 | 0.00 | 0.00 |
| November | 77.42 | 32.83 | 35.03 | 0.00 | 35.03 | 0.00 | 0.00 |
| December | 40.44 | 72.91 | 30.88 | 0.00 | 30.88 | 0.00 | 0.00 |
| Annual Sum or Average | 135.42 | 30.51 | 44.68 | 0.60 | 44.08 | 0.00 | 0.00 |
| Minimum of Months | 33.60 | 0.00 | 30.88 | 0.00 | 30.88 | 0.00 | 0.00 |
| Maximum of Months | 250.89 | 93.31 | 59.05 | 3.20 | 55.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 33.56 | 93.32 | 33.09 | 0.00 | 33.09 | 0.00 | 0.00 |
| February | 49.76 | 75.35 | 37.93 | 0.00 | 37.93 | 0.00 | 0.00 |
| March | 77.05 | 53.14 | 43.57 | 0.00 | 43.57 | 0.00 | 0.00 |
| April | 118.11 | 27.41 | 49.17 | 0.14 | 49.02 | 0.00 | 0.00 |
| May | 189.31 | 4.17 | 55.39 | 1.75 | 53.64 | 0.00 | 0.00 |
| June | 220.14 | 0.43 | 59.05 | 3.20 | 55.85 | 0.00 | 0.00 |
| July | 250.89 | 0.00 | 54.28 | 1.55 | 52.73 | 0.00 | 0.00 |
| August | 246.21 | 0.00 | 50.68 | 0.55 | 50.13 | 0.00 | 0.00 |
| September | 186.15 | 1.21 | 46.04 | 0.01 | 46.03 | 0.00 | 0.00 |
| October | 129.48 | 7.74 | 40.80 | 0.00 | 40.80 | 0.00 | 0.00 |
| November | 77.40 | 32.83 | 35.03 | 0.00 | 35.03 | 0.00 | 0.00 |
| December | 40.42 | 72.91 | 30.88 | 0.00 | 30.88 | 0.00 | 0.00 |
| Annual Sum or Average | 135.40 | 30.51 | 44.68 | 0.60 | 44.08 | 0.00 | 0.00 |
| Minimum of Months | 33.56 | 0.00 | 30.88 | 0.00 | 30.88 | 0.00 | 0.00 |
| Maximum of Months | 250.89 | 93.32 | 59.05 | 3.20 | 55.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 167.89 | 87.70 | 106.93 | 50.23 | 56.71 | 0.00 | 0.00 |
| February | 171.02 | 73.10 | 100.84 | 41.50 | 59.35 | 0.00 | 0.00 |
| March | 157.69 | 53.32 | 81.19 | 20.99 | 60.20 | 0.00 | 0.00 |
| April | 158.72 | 28.03 | 66.35 | 8.25 | 58.10 | 0.00 | 0.00 |
| May | 188.60 | 4.24 | 55.13 | 0.93 | 54.20 | 0.00 | 0.00 |
| June | 204.26 | 0.33 | 51.86 | 0.09 | 51.77 | 0.00 | 0.00 |
| July | 243.94 | 0.00 | 51.85 | 0.43 | 51.42 | 0.00 | 0.00 |
| August | 268.11 | 0.00 | 60.06 | 4.18 | 55.88 | 0.00 | 0.00 |
| September | 261.90 | 1.20 | 80.10 | 18.98 | 61.12 | 0.00 | 0.00 |
| October | 259.26 | 7.28 | 103.37 | 40.86 | 62.51 | 0.00 | 0.00 |
| November | 234.18 | 31.54 | 114.95 | 55.64 | 59.31 | 0.00 | 0.00 |
| December | 181.42 | 70.01 | 105.98 | 52.22 | 53.76 | 0.00 | 0.00 |
| Annual Sum or Average | 208.31 | 29.53 | 81.43 | 24.43 | 57.00 | 0.00 | 0.00 |
| Minimum of Months | 157.69 | 0.00 | 51.85 | 0.09 | 51.42 | 0.00 | 0.00 |
| Maximum of Months | 268.11 | 87.70 | 114.95 | 55.64 | 62.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 167.86 | 87.70 | 106.93 | 50.23 | 56.71 | 0.00 | 0.00 |
| February | 171.00 | 73.10 | 100.84 | 41.50 | 59.35 | 0.00 | 0.00 |
| March | 157.68 | 53.31 | 81.19 | 20.99 | 60.20 | 0.00 | 0.00 |
| April | 158.70 | 28.03 | 66.35 | 8.25 | 58.10 | 0.00 | 0.00 |
| May | 188.58 | 4.24 | 55.13 | 0.93 | 54.20 | 0.00 | 0.00 |
| June | 204.26 | 0.33 | 51.86 | 0.09 | 51.77 | 0.00 | 0.00 |
| July | 243.93 | 0.00 | 51.85 | 0.43 | 51.42 | 0.00 | 0.00 |
| August | 268.10 | 0.00 | 60.06 | 4.18 | 55.88 | 0.00 | 0.00 |
| September | 261.89 | 1.20 | 80.10 | 18.98 | 61.12 | 0.00 | 0.00 |
| October | 259.25 | 7.27 | 103.37 | 40.86 | 62.51 | 0.00 | 0.00 |
| November | 234.16 | 31.54 | 114.95 | 55.64 | 59.31 | 0.00 | 0.00 |
| December | 181.40 | 70.01 | 105.98 | 52.22 | 53.76 | 0.00 | 0.00 |
| Annual Sum or Average | 208.30 | 29.53 | 81.43 | 24.43 | 57.00 | 0.00 | 0.00 |
| Minimum of Months | 157.68 | 0.00 | 51.85 | 0.09 | 51.42 | 0.00 | 0.00 |
| Maximum of Months | 268.10 | 87.70 | 114.95 | 55.64 | 62.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 216.61 | 138.52 | 145.69 | 61.38 | 84.31 | 0.00 | 0.00 |
| February | 234.89 | 115.51 | 145.04 | 54.14 | 90.90 | 0.00 | 0.00 |
| March | 248.55 | 84.64 | 133.50 | 36.51 | 96.99 | 0.00 | 0.00 |
| April | 277.10 | 44.88 | 123.37 | 24.22 | 99.15 | 0.00 | 0.00 |
| May | 350.88 | 7.04 | 117.17 | 19.45 | 97.72 | 0.00 | 0.00 |
| June | 384.87 | 0.62 | 116.08 | 20.37 | 95.71 | 0.00 | 0.00 |
| July | 437.85 | 0.00 | 110.77 | 17.30 | 93.47 | 0.00 | 0.00 |
| August | 465.81 | 0.00 | 120.39 | 22.47 | 97.92 | 0.00 | 0.00 |
| September | 423.58 | 2.00 | 137.58 | 37.05 | 100.52 | 0.00 | 0.00 |
| October | 380.68 | 11.99 | 154.46 | 57.36 | 97.10 | 0.00 | 0.00 |
| November | 318.90 | 50.75 | 158.92 | 70.03 | 88.89 | 0.00 | 0.00 |
| December | 235.37 | 111.49 | 142.77 | 63.37 | 79.40 | 0.00 | 0.00 |
| Annual Sum or Average | 331.83 | 46.97 | 133.72 | 40.22 | 93.50 | 0.00 | 0.00 |
| Minimum of Months | 216.61 | 0.00 | 110.77 | 17.30 | 79.40 | 0.00 | 0.00 |
| Maximum of Months | 465.81 | 138.52 | 158.92 | 70.03 | 100.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 86.98 | 140.46 | 71.85 | 11.16 | 60.69 | 0.00 | 0.00 |
| February | 116.55 | 116.62 | 82.13 | 12.65 | 69.48 | 0.00 | 0.00 |
| March | 169.81 | 84.32 | 95.88 | 15.53 | 80.35 | 0.00 | 0.00 |
| April | 237.48 | 44.29 | 106.19 | 16.12 | 90.07 | 0.00 | 0.00 |
| May | 351.50 | 6.97 | 117.43 | 20.27 | 97.16 | 0.00 | 0.00 |
| June | 400.25 | 0.72 | 123.27 | 23.48 | 99.79 | 0.00 | 0.00 |
| July | 444.69 | 0.00 | 113.21 | 18.42 | 94.79 | 0.00 | 0.00 |
| August | 444.40 | 0.00 | 111.01 | 18.84 | 92.17 | 0.00 | 0.00 |
| September | 349.46 | 2.03 | 103.52 | 18.08 | 85.44 | 0.00 | 0.00 |
| October | 253.90 | 12.60 | 91.89 | 16.50 | 75.39 | 0.00 | 0.00 |
| November | 166.13 | 52.06 | 79.00 | 14.40 | 64.60 | 0.00 | 0.00 |
| December | 98.65 | 112.56 | 67.67 | 11.14 | 56.53 | 0.00 | 0.00 |
| Annual Sum or Average | 260.85 | 47.40 | 96.97 | 16.39 | 80.58 | 0.00 | 0.00 |
| Minimum of Months | 86.98 | 0.00 | 67.67 | 11.14 | 56.53 | 0.00 | 0.00 |
| Maximum of Months | 444.69 | 140.46 | 123.27 | 23.48 | 99.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 214.68 | 135.61 | 146.32 | 62.15 | 84.17 | 0.00 | 0.00 |
| February | 229.69 | 113.03 | 143.70 | 53.07 | 90.63 | 0.00 | 0.00 |
| March | 236.50 | 81.57 | 128.60 | 32.64 | 95.96 | 0.00 | 0.00 |
| April | 276.57 | 42.23 | 124.24 | 25.18 | 99.06 | 0.00 | 0.00 |
| May | 354.19 | 6.23 | 119.54 | 21.41 | 98.13 | 0.00 | 0.00 |
| June | 381.56 | 0.53 | 115.04 | 19.42 | 95.62 | 0.00 | 0.00 |
| July | 438.14 | 0.00 | 110.85 | 17.47 | 93.39 | 0.00 | 0.00 |
| August | 466.78 | 0.00 | 120.39 | 22.66 | 97.73 | 0.00 | 0.00 |
| September | 422.11 | 1.76 | 136.78 | 36.46 | 100.32 | 0.00 | 0.00 |
| October | 380.69 | 11.09 | 154.78 | 57.61 | 97.17 | 0.00 | 0.00 |
| November | 314.99 | 49.33 | 158.10 | 69.29 | 88.81 | 0.00 | 0.00 |
| December | 229.04 | 109.51 | 140.85 | 61.77 | 79.08 | 0.00 | 0.00 |
| Annual Sum or Average | 329.34 | 45.60 | 133.18 | 39.85 | 93.33 | 0.00 | 0.00 |
| Minimum of Months | 214.68 | 0.00 | 110.85 | 17.47 | 79.08 | 0.00 | 0.00 |
| Maximum of Months | 466.78 | 135.61 | 158.10 | 69.29 | 100.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 82.15 | 134.61 | 72.48 | 11.92 | 60.55 | 0.00 | 0.00 |
| February | 109.96 | 112.69 | 80.78 | 11.57 | 69.21 | 0.00 | 0.00 |
| March | 157.28 | 80.72 | 90.98 | 11.65 | 79.33 | 0.00 | 0.00 |
| April | 237.20 | 41.92 | 107.06 | 17.07 | 89.98 | 0.00 | 0.00 |
| May | 355.17 | 6.49 | 119.80 | 22.23 | 97.57 | 0.00 | 0.00 |
| June | 397.01 | 0.65 | 122.23 | 22.53 | 99.70 | 0.00 | 0.00 |
| July | 445.01 | 0.00 | 113.28 | 18.58 | 94.70 | 0.00 | 0.00 |
| August | 445.40 | 0.00 | 111.01 | 19.03 | 91.98 | 0.00 | 0.00 |
| September | 347.96 | 1.77 | 102.72 | 17.49 | 85.23 | 0.00 | 0.00 |
| October | 253.29 | 11.14 | 92.21 | 16.75 | 75.46 | 0.00 | 0.00 |
| November | 159.59 | 48.16 | 78.18 | 13.65 | 64.53 | 0.00 | 0.00 |
| December | 89.41 | 107.82 | 65.76 | 9.55 | 56.20 | 0.00 | 0.00 |
| Annual Sum or Average | 257.51 | 45.19 | 96.43 | 16.02 | 80.41 | 0.00 | 0.00 |
| Minimum of Months | 82.15 | 0.00 | 65.76 | 9.55 | 56.20 | 0.00 | 0.00 |
| Maximum of Months | 445.40 | 134.61 | 122.23 | 22.53 | 99.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 34.37 | 89.51 | 33.09 | 0.00 | 33.09 | 0.00 | 0.00 |
| February | 49.47 | 73.47 | 37.93 | 0.00 | 37.93 | 0.00 | 0.00 |
| March | 76.01 | 51.86 | 43.57 | 0.00 | 43.57 | 0.00 | 0.00 |
| April | 115.80 | 26.59 | 49.17 | 0.14 | 49.02 | 0.00 | 0.00 |
| May | 185.37 | 4.04 | 55.39 | 1.75 | 53.64 | 0.00 | 0.00 |
| June | 215.79 | 0.41 | 59.05 | 3.20 | 55.85 | 0.00 | 0.00 |
| July | 245.91 | 0.00 | 54.28 | 1.55 | 52.73 | 0.00 | 0.00 |
| August | 241.33 | 0.00 | 50.68 | 0.55 | 50.13 | 0.00 | 0.00 |
| September | 182.40 | 1.17 | 46.04 | 0.01 | 46.03 | 0.00 | 0.00 |
| October | 126.85 | 7.43 | 40.80 | 0.00 | 40.80 | 0.00 | 0.00 |
| November | 76.20 | 31.68 | 35.03 | 0.00 | 35.03 | 0.00 | 0.00 |
| December | 40.65 | 70.40 | 30.88 | 0.00 | 30.88 | 0.00 | 0.00 |
| Annual Sum or Average | 133.03 | 29.52 | 44.68 | 0.60 | 44.08 | 0.00 | 0.00 |
| Minimum of Months | 34.37 | 0.00 | 30.88 | 0.00 | 30.88 | 0.00 | 0.00 |
| Maximum of Months | 245.91 | 89.51 | 59.05 | 3.20 | 55.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 34.25 | 89.49 | 33.09 | 0.00 | 33.09 | 0.00 | 0.00 |
| February | 49.38 | 73.44 | 37.93 | 0.00 | 37.93 | 0.00 | 0.00 |
| March | 75.96 | 51.81 | 43.57 | 0.00 | 43.57 | 0.00 | 0.00 |
| April | 115.76 | 26.57 | 49.17 | 0.14 | 49.02 | 0.00 | 0.00 |
| May | 185.36 | 4.03 | 55.39 | 1.75 | 53.64 | 0.00 | 0.00 |
| June | 215.78 | 0.41 | 59.05 | 3.20 | 55.85 | 0.00 | 0.00 |
| July | 245.91 | 0.00 | 54.28 | 1.55 | 52.73 | 0.00 | 0.00 |
| August | 241.32 | 0.00 | 50.68 | 0.55 | 50.13 | 0.00 | 0.00 |
| September | 182.39 | 1.17 | 46.04 | 0.01 | 46.03 | 0.00 | 0.00 |
| October | 126.84 | 7.43 | 40.80 | 0.00 | 40.80 | 0.00 | 0.00 |
| November | 76.16 | 31.67 | 35.03 | 0.00 | 35.03 | 0.00 | 0.00 |
| December | 40.57 | 70.38 | 30.88 | 0.00 | 30.88 | 0.00 | 0.00 |
| Annual Sum or Average | 132.99 | 29.50 | 44.68 | 0.60 | 44.08 | 0.00 | 0.00 |
| Minimum of Months | 34.25 | 0.00 | 30.88 | 0.00 | 30.88 | 0.00 | 0.00 |
| Maximum of Months | 245.91 | 89.49 | 59.05 | 3.20 | 55.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 166.80 | 85.04 | 106.93 | 50.23 | 56.71 | 0.00 | 0.00 |
| February | 169.45 | 71.14 | 100.84 | 41.50 | 59.35 | 0.00 | 0.00 |
| March | 155.94 | 51.87 | 81.19 | 20.99 | 60.20 | 0.00 | 0.00 |
| April | 155.99 | 27.06 | 66.35 | 8.25 | 58.10 | 0.00 | 0.00 |
| May | 184.67 | 4.05 | 55.13 | 0.93 | 54.20 | 0.00 | 0.00 |
| June | 200.12 | 0.31 | 51.86 | 0.09 | 51.77 | 0.00 | 0.00 |
| July | 238.95 | 0.00 | 51.85 | 0.43 | 51.42 | 0.00 | 0.00 |
| August | 263.07 | 0.00 | 60.06 | 4.18 | 55.88 | 0.00 | 0.00 |
| September | 257.60 | 1.12 | 80.10 | 18.98 | 61.12 | 0.00 | 0.00 |
| October | 255.60 | 6.80 | 103.37 | 40.86 | 62.51 | 0.00 | 0.00 |
| November | 231.71 | 30.35 | 114.95 | 55.64 | 59.31 | 0.00 | 0.00 |
| December | 180.31 | 68.02 | 105.98 | 52.22 | 53.76 | 0.00 | 0.00 |
| Annual Sum or Average | 205.24 | 28.62 | 81.43 | 24.43 | 57.00 | 0.00 | 0.00 |
| Minimum of Months | 155.94 | 0.00 | 51.85 | 0.09 | 51.42 | 0.00 | 0.00 |
| Maximum of Months | 263.07 | 85.04 | 114.95 | 55.64 | 62.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 166.71 | 85.01 | 106.93 | 50.23 | 56.71 | 0.00 | 0.00 |
| February | 169.38 | 71.12 | 100.84 | 41.50 | 59.35 | 0.00 | 0.00 |
| March | 155.90 | 51.83 | 81.19 | 20.99 | 60.20 | 0.00 | 0.00 |
| April | 155.95 | 27.05 | 66.35 | 8.25 | 58.10 | 0.00 | 0.00 |
| May | 184.65 | 4.04 | 55.13 | 0.93 | 54.20 | 0.00 | 0.00 |
| June | 200.11 | 0.31 | 51.86 | 0.09 | 51.77 | 0.00 | 0.00 |
| July | 238.94 | 0.00 | 51.85 | 0.43 | 51.42 | 0.00 | 0.00 |
| August | 263.06 | 0.00 | 60.06 | 4.18 | 55.88 | 0.00 | 0.00 |
| September | 257.59 | 1.12 | 80.10 | 18.98 | 61.12 | 0.00 | 0.00 |
| October | 255.59 | 6.80 | 103.37 | 40.86 | 62.51 | 0.00 | 0.00 |
| November | 231.68 | 30.34 | 114.95 | 55.64 | 59.31 | 0.00 | 0.00 |
| December | 180.25 | 68.00 | 105.98 | 52.22 | 53.76 | 0.00 | 0.00 |
| Annual Sum or Average | 205.21 | 28.61 | 81.43 | 24.43 | 57.00 | 0.00 | 0.00 |
| Minimum of Months | 155.90 | 0.00 | 51.85 | 0.09 | 51.42 | 0.00 | 0.00 |
| Maximum of Months | 263.06 | 85.01 | 114.95 | 55.64 | 62.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.75 | 15.01 | 9.45 | 2.86 | 6.59 | 0.00 | 0.00 |
| February | 14.43 | 12.71 | 10.28 | 2.78 | 7.51 | 0.00 | 0.00 |
| March | 19.02 | 9.35 | 11.38 | 2.80 | 8.58 | 0.00 | 0.00 |
| April | 28.24 | 5.40 | 13.89 | 4.06 | 9.83 | 0.00 | 0.00 |
| May | 38.80 | 1.15 | 15.46 | 4.92 | 10.54 | 0.00 | 0.00 |
| June | 41.15 | 0.23 | 15.16 | 4.64 | 10.52 | 0.00 | 0.00 |
| July | 45.09 | 0.00 | 14.16 | 4.09 | 10.07 | 0.00 | 0.00 |
| August | 46.21 | 0.00 | 14.48 | 4.44 | 10.04 | 0.00 | 0.00 |
| September | 37.23 | 0.37 | 13.60 | 4.19 | 9.41 | 0.00 | 0.00 |
| October | 28.61 | 1.88 | 12.34 | 4.02 | 8.32 | 0.00 | 0.00 |
| November | 19.40 | 6.19 | 10.35 | 3.28 | 7.08 | 0.00 | 0.00 |
| December | 11.56 | 12.35 | 8.37 | 2.29 | 6.08 | 0.00 | 0.00 |
| Annual Sum or Average | 28.54 | 5.35 | 12.42 | 3.70 | 8.72 | 0.00 | 0.00 |
| Minimum of Months | 11.56 | 0.00 | 8.37 | 2.29 | 6.08 | 0.00 | 0.00 |
| Maximum of Months | 46.21 | 15.01 | 15.46 | 4.92 | 10.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 33.37 | 47.46 | 28.15 | 8.52 | 19.63 | 0.00 | 0.00 |
| February | 41.55 | 40.26 | 30.63 | 8.27 | 22.36 | 0.00 | 0.00 |
| March | 54.59 | 30.56 | 33.88 | 8.33 | 25.55 | 0.00 | 0.00 |
| April | 80.59 | 19.83 | 41.37 | 12.10 | 29.27 | 0.00 | 0.00 |
| May | 107.28 | 6.11 | 46.03 | 14.64 | 31.39 | 0.00 | 0.00 |
| June | 111.71 | 2.44 | 45.15 | 13.81 | 31.34 | 0.00 | 0.00 |
| July | 120.03 | 0.17 | 42.17 | 12.17 | 29.99 | 0.00 | 0.00 |
| August | 122.28 | 0.10 | 43.12 | 13.21 | 29.91 | 0.00 | 0.00 |
| September | 98.93 | 3.18 | 40.50 | 12.49 | 28.01 | 0.00 | 0.00 |
| October | 77.63 | 10.81 | 36.74 | 11.97 | 24.77 | 0.00 | 0.00 |
| November | 53.45 | 24.75 | 30.84 | 9.76 | 21.08 | 0.00 | 0.00 |
| December | 32.00 | 41.16 | 24.92 | 6.83 | 18.10 | 0.00 | 0.00 |
| Annual Sum or Average | 77.99 | 18.79 | 36.98 | 11.02 | 25.96 | 0.00 | 0.00 |
| Minimum of Months | 32.00 | 0.10 | 24.92 | 6.83 | 18.10 | 0.00 | 0.00 |
| Maximum of Months | 122.28 | 47.46 | 46.03 | 14.64 | 31.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.10 | 15.79 | 9.45 | 2.86 | 6.59 | 0.00 | 0.00 |
| February | 14.03 | 13.25 | 10.28 | 2.78 | 7.51 | 0.00 | 0.00 |
| March | 18.84 | 9.72 | 11.38 | 2.80 | 8.58 | 0.00 | 0.00 |
| April | 28.47 | 5.60 | 13.89 | 4.06 | 9.83 | 0.00 | 0.00 |
| May | 39.62 | 1.19 | 15.46 | 4.92 | 10.54 | 0.00 | 0.00 |
| June | 42.13 | 0.24 | 15.16 | 4.64 | 10.52 | 0.00 | 0.00 |
| July | 46.39 | 0.00 | 14.16 | 4.09 | 10.07 | 0.00 | 0.00 |
| August | 47.53 | 0.00 | 14.48 | 4.44 | 10.04 | 0.00 | 0.00 |
| September | 38.13 | 0.40 | 13.60 | 4.19 | 9.41 | 0.00 | 0.00 |
| October | 29.11 | 2.00 | 12.34 | 4.02 | 8.32 | 0.00 | 0.00 |
| November | 19.40 | 6.49 | 10.35 | 3.28 | 7.08 | 0.00 | 0.00 |
| December | 11.13 | 12.93 | 8.37 | 2.29 | 6.08 | 0.00 | 0.00 |
| Annual Sum or Average | 28.91 | 5.60 | 12.42 | 3.70 | 8.72 | 0.00 | 0.00 |
| Minimum of Months | 11.10 | 0.00 | 8.37 | 2.29 | 6.08 | 0.00 | 0.00 |
| Maximum of Months | 47.53 | 15.79 | 15.46 | 4.92 | 10.54 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.583775E+09 | 0.395984E+09 | 0.390222E+09 | 0.164410E+09 | 0.225811E+09 | 0.00 | 0.00 |
| February | 0.577457E+09 | 0.294020E+09 | 0.350884E+09 | 0.130984E+09 | 0.219901E+09 | 0.00 | 0.00 |
| March | 0.679102E+09 | 0.235516E+09 | 0.357564E+09 | 97798364.10 | 0.259765E+09 | 0.00 | 0.00 |
| April | 0.733631E+09 | 0.123996E+09 | 0.319783E+09 | 62787607.36 | 0.256995E+09 | 0.00 | 0.00 |
| May | 0.950840E+09 | 22502921.67 | 0.313828E+09 | 52094290.29 | 0.261734E+09 | 0.00 | 0.00 |
| June | 0.100083E+10 | 2517507.43 | 0.300881E+09 | 52804856.75 | 0.248077E+09 | 0.00 | 0.00 |
| July | 0.117307E+10 | 0.00 | 0.296697E+09 | 46337321.41 | 0.250360E+09 | 0.00 | 0.00 |
| August | 0.124107E+10 | 0.00 | 0.322450E+09 | 60194229.30 | 0.262256E+09 | 0.00 | 0.00 |
| September | 0.109107E+10 | 8141944.80 | 0.356607E+09 | 96046454.82 | 0.260560E+09 | 0.00 | 0.00 |
| October | 0.101701E+10 | 45826580.91 | 0.413702E+09 | 0.153632E+09 | 0.260070E+09 | 0.00 | 0.00 |
| November | 0.826015E+09 | 0.155455E+09 | 0.411924E+09 | 0.181528E+09 | 0.230395E+09 | 0.00 | 0.00 |
| December | 0.629097E+09 | 0.325677E+09 | 0.382400E+09 | 0.169723E+09 | 0.212677E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.105030E+11 | 0.160964E+10 | 0.421694E+10 | 0.126834E+10 | 0.294860E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.577457E+09 | 0.00 | 0.296697E+09 | 46337321.41 | 0.212677E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.124107E+10 | 0.395984E+09 | 0.413702E+09 | 0.181528E+09 | 0.262256E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.225543E+09 | 0.409464E+09 | 0.192432E+09 | 29878949.63 | 0.162553E+09 | 0.00 | 0.00 |
| February | 0.284630E+09 | 0.296523E+09 | 0.198677E+09 | 30593048.71 | 0.168084E+09 | 0.00 | 0.00 |
| March | 0.464648E+09 | 0.232615E+09 | 0.256802E+09 | 41584516.91 | 0.215218E+09 | 0.00 | 0.00 |
| April | 0.628842E+09 | 0.121354E+09 | 0.275239E+09 | 41771678.73 | 0.233467E+09 | 0.00 | 0.00 |
| May | 0.952244E+09 | 21953828.15 | 0.314532E+09 | 54299418.06 | 0.260233E+09 | 0.00 | 0.00 |
| June | 0.104171E+10 | 2790849.26 | 0.319509E+09 | 60857507.46 | 0.258652E+09 | 0.00 | 0.00 |
| July | 0.119070E+10 | 1387.41 | 0.303211E+09 | 49326024.70 | 0.253885E+09 | 0.00 | 0.00 |
| August | 0.118249E+10 | 0.00 | 0.297326E+09 | 50465914.64 | 0.246860E+09 | 0.00 | 0.00 |
| September | 0.895534E+09 | 7994123.71 | 0.268318E+09 | 46868155.22 | 0.221450E+09 | 0.00 | 0.00 |
| October | 0.671381E+09 | 46317484.05 | 0.246126E+09 | 44204558.38 | 0.201921E+09 | 0.00 | 0.00 |
| November | 0.423364E+09 | 0.158283E+09 | 0.204771E+09 | 37321388.83 | 0.167450E+09 | 0.00 | 0.00 |
| December | 0.255633E+09 | 0.333138E+09 | 0.181257E+09 | 29848443.94 | 0.151409E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.821672E+10 | 0.163044E+10 | 0.305820E+10 | 0.517020E+09 | 0.254118E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.225543E+09 | 0.00 | 0.181257E+09 | 29848443.94 | 0.151409E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.119070E+10 | 0.409464E+09 | 0.319509E+09 | 60857507.46 | 0.260233E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.569736E+09 | 0.445045E+09 | 0.391913E+09 | 0.166465E+09 | 0.225447E+09 | 0.00 | 0.00 |
| February | 0.552946E+09 | 0.347757E+09 | 0.347636E+09 | 0.128379E+09 | 0.219257E+09 | 0.00 | 0.00 |
| March | 0.619296E+09 | 0.301120E+09 | 0.344455E+09 | 87427789.14 | 0.257028E+09 | 0.00 | 0.00 |
| April | 0.672210E+09 | 0.205023E+09 | 0.322035E+09 | 65269723.10 | 0.256766E+09 | 0.00 | 0.00 |
| May | 0.823470E+09 | 79097204.97 | 0.320175E+09 | 57343133.02 | 0.262832E+09 | 0.00 | 0.00 |
| June | 0.832180E+09 | 36796120.97 | 0.298190E+09 | 50341936.51 | 0.247848E+09 | 0.00 | 0.00 |
| July | 0.955359E+09 | 5887621.11 | 0.296907E+09 | 46779772.93 | 0.250128E+09 | 0.00 | 0.00 |
| August | 0.103403E+10 | 4078531.56 | 0.322455E+09 | 60704280.85 | 0.261751E+09 | 0.00 | 0.00 |
| September | 0.923186E+09 | 51764371.69 | 0.354528E+09 | 94509209.03 | 0.260018E+09 | 0.00 | 0.00 |
| October | 0.911548E+09 | 0.145029E+09 | 0.414554E+09 | 0.154294E+09 | 0.260260E+09 | 0.00 | 0.00 |
| November | 0.761085E+09 | 0.267431E+09 | 0.409799E+09 | 0.179596E+09 | 0.230203E+09 | 0.00 | 0.00 |
| December | 0.590384E+09 | 0.399717E+09 | 0.377262E+09 | 0.165454E+09 | 0.211807E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.924543E+10 | 0.228875E+10 | 0.419991E+10 | 0.125656E+10 | 0.294334E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.552946E+09 | 4078531.56 | 0.296907E+09 | 46779772.93 | 0.211807E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.103403E+10 | 0.445045E+09 | 0.414554E+09 | 0.179596E+09 | 0.262832E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.210633E+09 | 0.391195E+09 | 0.194123E+09 | 31934045.17 | 0.162189E+09 | 0.00 | 0.00 |
| February | 0.267296E+09 | 0.285595E+09 | 0.195429E+09 | 27988141.95 | 0.167441E+09 | 0.00 | 0.00 |
| March | 0.429986E+09 | 0.222425E+09 | 0.243694E+09 | 31213941.95 | 0.212480E+09 | 0.00 | 0.00 |
| April | 0.627874E+09 | 0.115009E+09 | 0.277492E+09 | 44253794.46 | 0.233238E+09 | 0.00 | 0.00 |
| May | 0.962177E+09 | 20631580.85 | 0.320879E+09 | 59548260.80 | 0.261330E+09 | 0.00 | 0.00 |
| June | 0.103394E+10 | 2623701.91 | 0.316818E+09 | 58394587.22 | 0.258423E+09 | 0.00 | 0.00 |
| July | 0.119159E+10 | 0.00 | 0.303421E+09 | 49768476.22 | 0.253653E+09 | 0.00 | 0.00 |
| August | 0.118481E+10 | 0.00 | 0.297331E+09 | 50975966.20 | 0.246355E+09 | 0.00 | 0.00 |
| September | 0.891267E+09 | 7074307.17 | 0.266239E+09 | 45330909.43 | 0.220908E+09 | 0.00 | 0.00 |
| October | 0.668796E+09 | 41471743.93 | 0.246978E+09 | 44866965.27 | 0.202111E+09 | 0.00 | 0.00 |
| November | 0.404770E+09 | 0.145989E+09 | 0.202646E+09 | 35388966.58 | 0.167257E+09 | 0.00 | 0.00 |
| December | 0.228860E+09 | 0.318042E+09 | 0.176119E+09 | 25580096.36 | 0.150539E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.810200E+10 | 0.155006E+10 | 0.304117E+10 | 0.505244E+09 | 0.253592E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.210633E+09 | 0.00 | 0.176119E+09 | 25580096.36 | 0.150539E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.119159E+10 | 0.391195E+09 | 0.320879E+09 | 59548260.80 | 0.261330E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 88173176.91 | 0.253809E+09 | 88623175.80 | 0.00 | 88623175.80 | 0.00 | 0.00 |
| February | 0.119910E+09 | 0.183625E+09 | 91756479.98 | 0.00 | 91756479.98 | 0.00 | 0.00 |
| March | 0.206722E+09 | 0.142219E+09 | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.00 | 0.00 |
| April | 0.305036E+09 | 72385658.44 | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.00 | 0.00 |
| May | 0.499961E+09 | 12374592.19 | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.00 | 0.00 |
| June | 0.560015E+09 | 1482109.91 | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.00 | 0.00 |
| July | 0.656952E+09 | 0.00 | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.00 | 0.00 |
| August | 0.641199E+09 | 0.00 | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.00 | 0.00 |
| September | 0.466443E+09 | 4236819.27 | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.00 | 0.00 |
| October | 0.334181E+09 | 25586752.12 | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.00 | 0.00 |
| November | 0.193036E+09 | 93038031.44 | 90794144.06 | 0.00 | 90794144.06 | 0.00 | 0.00 |
| December | 0.104275E+09 | 0.203196E+09 | 82718268.40 | 0.00 | 82718268.40 | 0.00 | 0.00 |
| Annual Sum or Average | 0.417590E+10 | 0.991953E+09 | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.00 | 0.00 |
| Minimum of Months | 88173176.91 | 0.00 | 82718268.40 | 0.00 | 82718268.40 | 0.00 | 0.00 |
| Maximum of Months | 0.656952E+09 | 0.253809E+09 | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 88091938.90 | 0.253829E+09 | 88623175.80 | 0.00 | 88623175.80 | 0.00 | 0.00 |
| February | 0.119854E+09 | 0.183619E+09 | 91756479.98 | 0.00 | 91756479.98 | 0.00 | 0.00 |
| March | 0.206695E+09 | 0.142181E+09 | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.00 | 0.00 |
| April | 0.304992E+09 | 72385460.71 | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.00 | 0.00 |
| May | 0.499926E+09 | 12374260.16 | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.00 | 0.00 |
| June | 0.560005E+09 | 1481311.49 | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.00 | 0.00 |
| July | 0.656942E+09 | 0.00 | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.00 | 0.00 |
| August | 0.641186E+09 | 0.00 | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.00 | 0.00 |
| September | 0.466432E+09 | 4236049.03 | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.00 | 0.00 |
| October | 0.334160E+09 | 25584443.32 | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.00 | 0.00 |
| November | 0.193004E+09 | 93036688.05 | 90794144.06 | 0.00 | 90794144.06 | 0.00 | 0.00 |
| December | 0.104226E+09 | 0.203194E+09 | 82718268.40 | 0.00 | 82718268.40 | 0.00 | 0.00 |
| Annual Sum or Average | 0.417551E+10 | 0.991920E+09 | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.00 | 0.00 |
| Minimum of Months | 88091938.90 | 0.00 | 82718268.40 | 0.00 | 82718268.40 | 0.00 | 0.00 |
| Maximum of Months | 0.656942E+09 | 0.253829E+09 | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.450386E+09 | 0.237590E+09 | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.00 | 0.00 |
| February | 0.415218E+09 | 0.178132E+09 | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.00 | 0.00 |
| March | 0.423680E+09 | 0.143417E+09 | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.00 | 0.00 |
| April | 0.410976E+09 | 74474421.24 | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.00 | 0.00 |
| May | 0.498079E+09 | 12705878.43 | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.00 | 0.00 |
| June | 0.518199E+09 | 1232606.22 | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.00 | 0.00 |
| July | 0.638729E+09 | 0.00 | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.00 | 0.00 |
| August | 0.700335E+09 | 0.00 | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.00 | 0.00 |
| September | 0.664208E+09 | 4262353.59 | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.00 | 0.00 |
| October | 0.683891E+09 | 24686332.56 | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.00 | 0.00 |
| November | 0.601520E+09 | 90146172.56 | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.00 | 0.00 |
| December | 0.483476E+09 | 0.194464E+09 | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.648870E+10 | 0.961111E+09 | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.410976E+09 | 0.00 | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.700335E+09 | 0.237590E+09 | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.449386E+09 | 0.238941E+09 | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.00 | 0.00 |
| February | 0.414186E+09 | 0.179651E+09 | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.00 | 0.00 |
| March | 0.422335E+09 | 0.145259E+09 | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.00 | 0.00 |
| April | 0.408898E+09 | 76495441.94 | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.00 | 0.00 |
| May | 0.494237E+09 | 13622150.43 | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.00 | 0.00 |
| June | 0.513860E+09 | 1409756.39 | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.00 | 0.00 |
| July | 0.633937E+09 | 0.00 | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.00 | 0.00 |
| August | 0.695779E+09 | 0.00 | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.00 | 0.00 |
| September | 0.660059E+09 | 4650200.28 | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.00 | 0.00 |
| October | 0.680672E+09 | 26293206.15 | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.00 | 0.00 |
| November | 0.599338E+09 | 92581366.11 | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.00 | 0.00 |
| December | 0.482144E+09 | 0.196366E+09 | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.645483E+10 | 0.975269E+09 | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.408898E+09 | 0.00 | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.695779E+09 | 0.238941E+09 | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.584202E+09 | 0.390051E+09 | 0.390222E+09 | 0.164410E+09 | 0.225811E+09 | 0.00 | 0.00 |
| February | 0.575201E+09 | 0.292066E+09 | 0.350884E+09 | 0.130984E+09 | 0.219901E+09 | 0.00 | 0.00 |
| March | 0.675593E+09 | 0.236085E+09 | 0.357564E+09 | 97798364.10 | 0.259765E+09 | 0.00 | 0.00 |
| April | 0.732571E+09 | 0.122199E+09 | 0.319783E+09 | 62787607.36 | 0.256995E+09 | 0.00 | 0.00 |
| May | 0.961122E+09 | 20294512.51 | 0.313828E+09 | 52094290.29 | 0.261734E+09 | 0.00 | 0.00 |
| June | 0.101924E+10 | 1823714.10 | 0.300881E+09 | 52804856.75 | 0.248077E+09 | 0.00 | 0.00 |
| July | 0.119919E+10 | 0.00 | 0.296697E+09 | 46337321.41 | 0.250360E+09 | 0.00 | 0.00 |
| August | 0.127448E+10 | 0.00 | 0.322450E+09 | 60194229.30 | 0.262256E+09 | 0.00 | 0.00 |
| September | 0.111978E+10 | 5729275.45 | 0.356607E+09 | 96046454.82 | 0.260560E+09 | 0.00 | 0.00 |
| October | 0.103852E+10 | 35033586.76 | 0.413702E+09 | 0.153632E+09 | 0.260070E+09 | 0.00 | 0.00 |
| November | 0.838521E+09 | 0.138399E+09 | 0.411924E+09 | 0.181528E+09 | 0.230395E+09 | 0.00 | 0.00 |
| December | 0.635583E+09 | 0.311233E+09 | 0.382400E+09 | 0.169723E+09 | 0.212677E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.106540E+11 | 0.155291E+10 | 0.421694E+10 | 0.126834E+10 | 0.294860E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.575201E+09 | 0.00 | 0.296697E+09 | 46337321.41 | 0.212677E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.127448E+10 | 0.390051E+09 | 0.413702E+09 | 0.181528E+09 | 0.262256E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.229762E+09 | 0.401029E+09 | 0.192432E+09 | 29878949.63 | 0.162553E+09 | 0.00 | 0.00 |
| February | 0.284465E+09 | 0.295272E+09 | 0.198677E+09 | 30593048.71 | 0.168084E+09 | 0.00 | 0.00 |
| March | 0.461942E+09 | 0.234358E+09 | 0.256802E+09 | 41584516.91 | 0.215218E+09 | 0.00 | 0.00 |
| April | 0.628439E+09 | 0.120115E+09 | 0.275239E+09 | 41771678.73 | 0.233467E+09 | 0.00 | 0.00 |
| May | 0.962837E+09 | 19893507.36 | 0.314532E+09 | 54299418.06 | 0.260233E+09 | 0.00 | 0.00 |
| June | 0.105984E+10 | 2066808.99 | 0.319509E+09 | 60857507.46 | 0.258652E+09 | 0.00 | 0.00 |
| July | 0.121754E+10 | 0.00 | 0.303211E+09 | 49326024.70 | 0.253885E+09 | 0.00 | 0.00 |
| August | 0.121656E+10 | 0.00 | 0.297326E+09 | 50465914.64 | 0.246860E+09 | 0.00 | 0.00 |
| September | 0.925701E+09 | 5693392.14 | 0.268318E+09 | 46868155.22 | 0.221450E+09 | 0.00 | 0.00 |
| October | 0.695103E+09 | 36063232.56 | 0.246126E+09 | 44204558.38 | 0.201921E+09 | 0.00 | 0.00 |
| November | 0.438012E+09 | 0.141640E+09 | 0.204771E+09 | 37321388.83 | 0.167450E+09 | 0.00 | 0.00 |
| December | 0.264292E+09 | 0.317052E+09 | 0.181257E+09 | 29848443.94 | 0.151409E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.838450E+10 | 0.157318E+10 | 0.305820E+10 | 0.517020E+09 | 0.254118E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.229762E+09 | 0.00 | 0.181257E+09 | 29848443.94 | 0.151409E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.121754E+10 | 0.401029E+09 | 0.319509E+09 | 60857507.46 | 0.260233E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.578710E+09 | 0.381120E+09 | 0.391913E+09 | 0.166465E+09 | 0.225447E+09 | 0.00 | 0.00 |
| February | 0.561941E+09 | 0.285292E+09 | 0.347636E+09 | 0.128379E+09 | 0.219257E+09 | 0.00 | 0.00 |
| March | 0.642449E+09 | 0.227211E+09 | 0.344455E+09 | 87427789.14 | 0.257028E+09 | 0.00 | 0.00 |
| April | 0.730920E+09 | 0.114946E+09 | 0.322035E+09 | 65269723.10 | 0.256766E+09 | 0.00 | 0.00 |
| May | 0.970001E+09 | 17996017.30 | 0.320175E+09 | 57343133.02 | 0.262832E+09 | 0.00 | 0.00 |
| June | 0.101090E+10 | 1572635.50 | 0.298190E+09 | 50341936.51 | 0.247848E+09 | 0.00 | 0.00 |
| July | 0.120000E+10 | 0.00 | 0.296907E+09 | 46779772.93 | 0.250128E+09 | 0.00 | 0.00 |
| August | 0.127699E+10 | 0.00 | 0.322455E+09 | 60704280.85 | 0.261751E+09 | 0.00 | 0.00 |
| September | 0.111586E+10 | 5059754.06 | 0.354528E+09 | 94509209.03 | 0.260018E+09 | 0.00 | 0.00 |
| October | 0.103851E+10 | 32566025.83 | 0.414554E+09 | 0.154294E+09 | 0.260260E+09 | 0.00 | 0.00 |
| November | 0.828338E+09 | 0.134429E+09 | 0.409799E+09 | 0.179596E+09 | 0.230203E+09 | 0.00 | 0.00 |
| December | 0.618467E+09 | 0.305661E+09 | 0.377262E+09 | 0.165454E+09 | 0.211807E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.105731E+11 | 0.150585E+10 | 0.419991E+10 | 0.125656E+10 | 0.294334E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.561941E+09 | 0.00 | 0.296907E+09 | 46779772.93 | 0.211807E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.127699E+10 | 0.381120E+09 | 0.414554E+09 | 0.179596E+09 | 0.262832E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.214702E+09 | 0.382449E+09 | 0.194123E+09 | 31934045.17 | 0.162189E+09 | 0.00 | 0.00 |
| February | 0.267191E+09 | 0.284531E+09 | 0.195429E+09 | 27988141.95 | 0.167441E+09 | 0.00 | 0.00 |
| March | 0.427438E+09 | 0.224193E+09 | 0.243694E+09 | 31213941.95 | 0.212480E+09 | 0.00 | 0.00 |
| April | 0.627513E+09 | 0.113648E+09 | 0.277492E+09 | 44253794.46 | 0.233238E+09 | 0.00 | 0.00 |
| May | 0.972743E+09 | 18573176.39 | 0.320879E+09 | 59548260.80 | 0.261330E+09 | 0.00 | 0.00 |
| June | 0.105163E+10 | 1886645.27 | 0.316818E+09 | 58394587.22 | 0.258423E+09 | 0.00 | 0.00 |
| July | 0.121839E+10 | 0.00 | 0.303421E+09 | 49768476.22 | 0.253653E+09 | 0.00 | 0.00 |
| August | 0.121910E+10 | 0.00 | 0.297331E+09 | 50975966.20 | 0.246355E+09 | 0.00 | 0.00 |
| September | 0.921708E+09 | 4977080.00 | 0.266239E+09 | 45330909.43 | 0.220908E+09 | 0.00 | 0.00 |
| October | 0.693396E+09 | 31998793.23 | 0.246978E+09 | 44866965.27 | 0.202111E+09 | 0.00 | 0.00 |
| November | 0.420550E+09 | 0.130645E+09 | 0.202646E+09 | 35388966.58 | 0.167257E+09 | 0.00 | 0.00 |
| December | 0.238021E+09 | 0.302339E+09 | 0.176119E+09 | 25580096.36 | 0.150539E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.827239E+10 | 0.149524E+10 | 0.304117E+10 | 0.505244E+09 | 0.253592E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.214702E+09 | 0.00 | 0.176119E+09 | 25580096.36 | 0.150539E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.121910E+10 | 0.382449E+09 | 0.320879E+09 | 59548260.80 | 0.261330E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 89981383.97 | 0.249918E+09 | 88623175.80 | 0.00 | 88623175.80 | 0.00 | 0.00 |
| February | 0.120461E+09 | 0.182264E+09 | 91756479.98 | 0.00 | 91756479.98 | 0.00 | 0.00 |
| March | 0.206421E+09 | 0.142367E+09 | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.00 | 0.00 |
| April | 0.306190E+09 | 71063368.42 | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.00 | 0.00 |
| May | 0.507068E+09 | 11184021.75 | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.00 | 0.00 |
| June | 0.570618E+09 | 1118345.73 | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.00 | 0.00 |
| July | 0.671981E+09 | 0.00 | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.00 | 0.00 |
| August | 0.659461E+09 | 0.00 | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.00 | 0.00 |
| September | 0.482503E+09 | 3149873.79 | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.00 | 0.00 |
| October | 0.346827E+09 | 20735469.58 | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.00 | 0.00 |
| November | 0.200665E+09 | 85088151.03 | 90794144.06 | 0.00 | 90794144.06 | 0.00 | 0.00 |
| December | 0.108316E+09 | 0.195293E+09 | 82718268.40 | 0.00 | 82718268.40 | 0.00 | 0.00 |
| Annual Sum or Average | 0.427049E+10 | 0.962182E+09 | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.00 | 0.00 |
| Minimum of Months | 89981383.97 | 0.00 | 82718268.40 | 0.00 | 82718268.40 | 0.00 | 0.00 |
| Maximum of Months | 0.671981E+09 | 0.249918E+09 | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 89880250.26 | 0.249936E+09 | 88623175.80 | 0.00 | 88623175.80 | 0.00 | 0.00 |
| February | 0.120377E+09 | 0.182286E+09 | 91756479.98 | 0.00 | 91756479.98 | 0.00 | 0.00 |
| March | 0.206382E+09 | 0.142327E+09 | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.00 | 0.00 |
| April | 0.306147E+09 | 71059419.79 | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.00 | 0.00 |
| May | 0.507039E+09 | 11182303.29 | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.00 | 0.00 |
| June | 0.570609E+09 | 1117627.31 | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.00 | 0.00 |
| July | 0.671971E+09 | 0.00 | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.00 | 0.00 |
| August | 0.659449E+09 | 0.00 | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.00 | 0.00 |
| September | 0.482493E+09 | 3148979.46 | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.00 | 0.00 |
| October | 0.346805E+09 | 20732274.99 | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.00 | 0.00 |
| November | 0.200624E+09 | 85086811.28 | 90794144.06 | 0.00 | 90794144.06 | 0.00 | 0.00 |
| December | 0.108254E+09 | 0.195291E+09 | 82718268.40 | 0.00 | 82718268.40 | 0.00 | 0.00 |
| Annual Sum or Average | 0.427003E+10 | 0.962168E+09 | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.00 | 0.00 |
| Minimum of Months | 89880250.26 | 0.00 | 82718268.40 | 0.00 | 82718268.40 | 0.00 | 0.00 |
| Maximum of Months | 0.671971E+09 | 0.249936E+09 | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.449682E+09 | 0.234899E+09 | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.00 | 0.00 |
| February | 0.413737E+09 | 0.176851E+09 | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.00 | 0.00 |
| March | 0.422350E+09 | 0.142825E+09 | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.00 | 0.00 |
| April | 0.411401E+09 | 72651094.44 | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.00 | 0.00 |
| May | 0.505135E+09 | 11356125.18 | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.00 | 0.00 |
| June | 0.529443E+09 | 867827.61 | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.00 | 0.00 |
| July | 0.653365E+09 | 0.00 | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.00 | 0.00 |
| August | 0.718100E+09 | 0.00 | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.00 | 0.00 |
| September | 0.678838E+09 | 3104180.98 | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.00 | 0.00 |
| October | 0.694390E+09 | 19486670.48 | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.00 | 0.00 |
| November | 0.606983E+09 | 81761688.25 | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.00 | 0.00 |
| December | 0.485917E+09 | 0.187516E+09 | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.656934E+10 | 0.931319E+09 | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.411401E+09 | 0.00 | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.718100E+09 | 0.234899E+09 | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.449599E+09 | 0.234901E+09 | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.00 | 0.00 |
| February | 0.413678E+09 | 0.176844E+09 | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.00 | 0.00 |
| March | 0.422317E+09 | 0.142792E+09 | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.00 | 0.00 |
| April | 0.411360E+09 | 72646568.75 | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.00 | 0.00 |
| May | 0.505105E+09 | 11354531.17 | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.00 | 0.00 |
| June | 0.529433E+09 | 867159.45 | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.00 | 0.00 |
| July | 0.653355E+09 | 0.00 | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.00 | 0.00 |
| August | 0.718089E+09 | 0.00 | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.00 | 0.00 |
| September | 0.678829E+09 | 3103335.64 | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.00 | 0.00 |
| October | 0.694372E+09 | 19483214.25 | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.00 | 0.00 |
| November | 0.606951E+09 | 81755580.19 | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.00 | 0.00 |
| December | 0.485868E+09 | 0.187506E+09 | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.656896E+10 | 0.931254E+09 | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.411360E+09 | 0.00 | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.718089E+09 | 0.234901E+09 | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.580155E+09 | 0.371005E+09 | 0.390222E+09 | 0.164410E+09 | 0.225811E+09 | 0.00 | 0.00 |
| February | 0.568252E+09 | 0.279445E+09 | 0.350884E+09 | 0.130984E+09 | 0.219901E+09 | 0.00 | 0.00 |
| March | 0.665709E+09 | 0.226691E+09 | 0.357564E+09 | 97798364.10 | 0.259765E+09 | 0.00 | 0.00 |
| April | 0.718234E+09 | 0.116340E+09 | 0.319783E+09 | 62787607.36 | 0.256995E+09 | 0.00 | 0.00 |
| May | 0.939801E+09 | 18856604.33 | 0.313828E+09 | 52094290.29 | 0.261734E+09 | 0.00 | 0.00 |
| June | 0.997570E+09 | 1609782.89 | 0.300881E+09 | 52804856.75 | 0.248077E+09 | 0.00 | 0.00 |
| July | 0.117275E+10 | 0.00 | 0.296697E+09 | 46337321.41 | 0.250360E+09 | 0.00 | 0.00 |
| August | 0.124763E+10 | 0.00 | 0.322450E+09 | 60194229.30 | 0.262256E+09 | 0.00 | 0.00 |
| September | 0.109792E+10 | 5171535.41 | 0.356607E+09 | 96046454.82 | 0.260560E+09 | 0.00 | 0.00 |
| October | 0.101960E+10 | 32110549.55 | 0.413702E+09 | 0.153632E+09 | 0.260070E+09 | 0.00 | 0.00 |
| November | 0.826588E+09 | 0.131540E+09 | 0.411924E+09 | 0.181528E+09 | 0.230395E+09 | 0.00 | 0.00 |
| December | 0.630414E+09 | 0.298623E+09 | 0.382400E+09 | 0.169723E+09 | 0.212677E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.104646E+11 | 0.148139E+10 | 0.421694E+10 | 0.126834E+10 | 0.294860E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.568252E+09 | 0.00 | 0.296697E+09 | 46337321.41 | 0.212677E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.124763E+10 | 0.371005E+09 | 0.413702E+09 | 0.181528E+09 | 0.262256E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.232980E+09 | 0.376209E+09 | 0.192432E+09 | 29878949.63 | 0.162553E+09 | 0.00 | 0.00 |
| February | 0.281963E+09 | 0.282121E+09 | 0.198677E+09 | 30593048.71 | 0.168084E+09 | 0.00 | 0.00 |
| March | 0.454813E+09 | 0.225846E+09 | 0.256802E+09 | 41584516.91 | 0.215218E+09 | 0.00 | 0.00 |
| April | 0.615545E+09 | 0.114805E+09 | 0.275239E+09 | 41771678.73 | 0.233467E+09 | 0.00 | 0.00 |
| May | 0.941454E+09 | 18666679.89 | 0.314532E+09 | 54299418.06 | 0.260233E+09 | 0.00 | 0.00 |
| June | 0.103744E+10 | 1865484.28 | 0.319509E+09 | 60857507.46 | 0.258652E+09 | 0.00 | 0.00 |
| July | 0.119106E+10 | 0.00 | 0.303211E+09 | 49326024.70 | 0.253885E+09 | 0.00 | 0.00 |
| August | 0.119029E+10 | 0.00 | 0.297326E+09 | 50465914.64 | 0.246860E+09 | 0.00 | 0.00 |
| September | 0.905793E+09 | 5261026.17 | 0.268318E+09 | 46868155.22 | 0.221450E+09 | 0.00 | 0.00 |
| October | 0.680035E+09 | 33755543.90 | 0.246126E+09 | 44204558.38 | 0.201921E+09 | 0.00 | 0.00 |
| November | 0.430601E+09 | 0.134937E+09 | 0.204771E+09 | 37321388.83 | 0.167450E+09 | 0.00 | 0.00 |
| December | 0.264229E+09 | 0.301492E+09 | 0.181257E+09 | 29848443.94 | 0.151409E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.822620E+10 | 0.149496E+10 | 0.305820E+10 | 0.517020E+09 | 0.254118E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.232980E+09 | 0.00 | 0.181257E+09 | 29848443.94 | 0.151409E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.119106E+10 | 0.376209E+09 | 0.319509E+09 | 60857507.46 | 0.260233E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.575008E+09 | 0.363216E+09 | 0.391913E+09 | 0.166465E+09 | 0.225447E+09 | 0.00 | 0.00 |
| February | 0.555668E+09 | 0.273433E+09 | 0.347636E+09 | 0.128379E+09 | 0.219257E+09 | 0.00 | 0.00 |
| March | 0.633444E+09 | 0.218487E+09 | 0.344455E+09 | 87427789.14 | 0.257028E+09 | 0.00 | 0.00 |
| April | 0.716873E+09 | 0.109470E+09 | 0.322035E+09 | 65269723.10 | 0.256766E+09 | 0.00 | 0.00 |
| May | 0.948650E+09 | 16697566.11 | 0.320175E+09 | 57343133.02 | 0.262832E+09 | 0.00 | 0.00 |
| June | 0.989013E+09 | 1368793.88 | 0.298190E+09 | 50341936.51 | 0.247848E+09 | 0.00 | 0.00 |
| July | 0.117353E+10 | 0.00 | 0.296907E+09 | 46779772.93 | 0.250128E+09 | 0.00 | 0.00 |
| August | 0.125023E+10 | 0.00 | 0.322455E+09 | 60704280.85 | 0.261751E+09 | 0.00 | 0.00 |
| September | 0.109411E+10 | 4550049.79 | 0.354528E+09 | 94509209.03 | 0.260018E+09 | 0.00 | 0.00 |
| October | 0.101963E+10 | 29702241.96 | 0.414554E+09 | 0.154294E+09 | 0.260260E+09 | 0.00 | 0.00 |
| November | 0.816459E+09 | 0.127866E+09 | 0.409799E+09 | 0.179596E+09 | 0.230203E+09 | 0.00 | 0.00 |
| December | 0.613467E+09 | 0.293310E+09 | 0.377262E+09 | 0.165454E+09 | 0.211807E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.103861E+11 | 0.143810E+10 | 0.419991E+10 | 0.125656E+10 | 0.294334E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.555668E+09 | 0.00 | 0.296907E+09 | 46779772.93 | 0.211807E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.125023E+10 | 0.363216E+09 | 0.414554E+09 | 0.179596E+09 | 0.262832E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.220020E+09 | 0.360536E+09 | 0.194123E+09 | 31934045.17 | 0.162189E+09 | 0.00 | 0.00 |
| February | 0.266006E+09 | 0.272624E+09 | 0.195429E+09 | 27988141.95 | 0.167441E+09 | 0.00 | 0.00 |
| March | 0.421252E+09 | 0.216195E+09 | 0.243694E+09 | 31213941.95 | 0.212480E+09 | 0.00 | 0.00 |
| April | 0.614832E+09 | 0.108647E+09 | 0.277492E+09 | 44253794.46 | 0.233238E+09 | 0.00 | 0.00 |
| May | 0.951279E+09 | 17380589.72 | 0.320879E+09 | 59548260.80 | 0.261330E+09 | 0.00 | 0.00 |
| June | 0.102906E+10 | 1684735.24 | 0.316818E+09 | 58394587.22 | 0.258423E+09 | 0.00 | 0.00 |
| July | 0.119192E+10 | 0.00 | 0.303421E+09 | 49768476.22 | 0.253653E+09 | 0.00 | 0.00 |
| August | 0.119296E+10 | 0.00 | 0.297331E+09 | 50975966.20 | 0.246355E+09 | 0.00 | 0.00 |
| September | 0.901906E+09 | 4580382.03 | 0.266239E+09 | 45330909.43 | 0.220908E+09 | 0.00 | 0.00 |
| October | 0.678407E+09 | 29832028.01 | 0.246978E+09 | 44866965.27 | 0.202111E+09 | 0.00 | 0.00 |
| November | 0.413648E+09 | 0.124841E+09 | 0.202646E+09 | 35388966.58 | 0.167257E+09 | 0.00 | 0.00 |
| December | 0.239487E+09 | 0.288789E+09 | 0.176119E+09 | 25580096.36 | 0.150539E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.812077E+10 | 0.142511E+10 | 0.304117E+10 | 0.505244E+09 | 0.253592E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.220020E+09 | 0.00 | 0.176119E+09 | 25580096.36 | 0.150539E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.119296E+10 | 0.360536E+09 | 0.320879E+09 | 59548260.80 | 0.261330E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 92059252.21 | 0.239756E+09 | 88623175.80 | 0.00 | 88623175.80 | 0.00 | 0.00 |
| February | 0.119689E+09 | 0.177750E+09 | 91756479.98 | 0.00 | 91756479.98 | 0.00 | 0.00 |
| March | 0.203574E+09 | 0.138892E+09 | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.00 | 0.00 |
| April | 0.300150E+09 | 68908540.62 | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.00 | 0.00 |
| May | 0.496507E+09 | 10813780.35 | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.00 | 0.00 |
| June | 0.559320E+09 | 1070432.56 | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.00 | 0.00 |
| July | 0.658657E+09 | 0.00 | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.00 | 0.00 |
| August | 0.646380E+09 | 0.00 | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.00 | 0.00 |
| September | 0.472774E+09 | 3023717.20 | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.00 | 0.00 |
| October | 0.339768E+09 | 19899929.76 | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.00 | 0.00 |
| November | 0.197507E+09 | 82113394.24 | 90794144.06 | 0.00 | 90794144.06 | 0.00 | 0.00 |
| December | 0.108869E+09 | 0.188569E+09 | 82718268.40 | 0.00 | 82718268.40 | 0.00 | 0.00 |
| Annual Sum or Average | 0.419525E+10 | 0.930797E+09 | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.00 | 0.00 |
| Minimum of Months | 92059252.21 | 0.00 | 82718268.40 | 0.00 | 82718268.40 | 0.00 | 0.00 |
| Maximum of Months | 0.658657E+09 | 0.239756E+09 | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 91742885.27 | 0.239683E+09 | 88623175.80 | 0.00 | 88623175.80 | 0.00 | 0.00 |
| February | 0.119458E+09 | 0.177660E+09 | 91756479.98 | 0.00 | 91756479.98 | 0.00 | 0.00 |
| March | 0.203449E+09 | 0.138776E+09 | 0.116710E+09 | 5064.15 | 0.116705E+09 | 0.00 | 0.00 |
| April | 0.300056E+09 | 68879768.72 | 0.127439E+09 | 367645.41 | 0.127072E+09 | 0.00 | 0.00 |
| May | 0.496460E+09 | 10807197.79 | 0.148358E+09 | 4685153.40 | 0.143673E+09 | 0.00 | 0.00 |
| June | 0.559305E+09 | 1069020.62 | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.00 | 0.00 |
| July | 0.658644E+09 | 0.00 | 0.145379E+09 | 4140780.47 | 0.141238E+09 | 0.00 | 0.00 |
| August | 0.646364E+09 | 0.00 | 0.135729E+09 | 1465038.59 | 0.134264E+09 | 0.00 | 0.00 |
| September | 0.472758E+09 | 3021921.67 | 0.119331E+09 | 29704.55 | 0.119301E+09 | 0.00 | 0.00 |
| October | 0.339730E+09 | 19890846.45 | 0.109287E+09 | 0.00 | 0.109287E+09 | 0.00 | 0.00 |
| November | 0.197409E+09 | 82089572.44 | 90794144.06 | 0.00 | 90794144.06 | 0.00 | 0.00 |
| December | 0.108676E+09 | 0.188495E+09 | 82718268.40 | 0.00 | 82718268.40 | 0.00 | 0.00 |
| Annual Sum or Average | 0.419405E+10 | 0.930372E+09 | 0.140917E+10 | 18982262.91 | 0.139019E+10 | 0.00 | 0.00 |
| Minimum of Months | 91742885.27 | 0.00 | 82718268.40 | 0.00 | 82718268.40 | 0.00 | 0.00 |
| Maximum of Months | 0.658644E+09 | 0.239683E+09 | 0.153049E+09 | 8288876.34 | 0.144760E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.446756E+09 | 0.227780E+09 | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.00 | 0.00 |
| February | 0.409924E+09 | 0.172111E+09 | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.00 | 0.00 |
| March | 0.417657E+09 | 0.138918E+09 | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.00 | 0.00 |
| April | 0.404318E+09 | 70137807.78 | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.00 | 0.00 |
| May | 0.494612E+09 | 10834731.58 | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.00 | 0.00 |
| June | 0.518706E+09 | 802228.07 | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.00 | 0.00 |
| July | 0.639994E+09 | 0.00 | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.00 | 0.00 |
| August | 0.704601E+09 | 0.00 | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.00 | 0.00 |
| September | 0.667696E+09 | 2898803.85 | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.00 | 0.00 |
| October | 0.684601E+09 | 18226060.02 | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.00 | 0.00 |
| November | 0.600603E+09 | 78661899.69 | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.00 | 0.00 |
| December | 0.482934E+09 | 0.182186E+09 | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.647240E+10 | 0.902558E+09 | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.404318E+09 | 0.00 | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.704601E+09 | 0.227780E+09 | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.446521E+09 | 0.227688E+09 | 0.286413E+09 | 0.134531E+09 | 0.151882E+09 | 0.00 | 0.00 |
| February | 0.409756E+09 | 0.172042E+09 | 0.243963E+09 | 0.100391E+09 | 0.143573E+09 | 0.00 | 0.00 |
| March | 0.417549E+09 | 0.138822E+09 | 0.217471E+09 | 56218911.34 | 0.161252E+09 | 0.00 | 0.00 |
| April | 0.404229E+09 | 70108660.34 | 0.171983E+09 | 21383574.05 | 0.150600E+09 | 0.00 | 0.00 |
| May | 0.494565E+09 | 10828460.53 | 0.147654E+09 | 2480025.63 | 0.145174E+09 | 0.00 | 0.00 |
| June | 0.518689E+09 | 800978.94 | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.00 | 0.00 |
| July | 0.639979E+09 | 0.00 | 0.138865E+09 | 1152077.17 | 0.137713E+09 | 0.00 | 0.00 |
| August | 0.704585E+09 | 0.00 | 0.160854E+09 | 11193353.25 | 0.149660E+09 | 0.00 | 0.00 |
| September | 0.667682E+09 | 2897271.32 | 0.207620E+09 | 49208004.14 | 0.158412E+09 | 0.00 | 0.00 |
| October | 0.684571E+09 | 18217416.88 | 0.276863E+09 | 0.109427E+09 | 0.167436E+09 | 0.00 | 0.00 |
| November | 0.600526E+09 | 78634185.00 | 0.297947E+09 | 0.144207E+09 | 0.153740E+09 | 0.00 | 0.00 |
| December | 0.482793E+09 | 0.182123E+09 | 0.283860E+09 | 0.139874E+09 | 0.143986E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.647144E+10 | 0.902162E+09 | 0.256791E+10 | 0.770303E+09 | 0.179761E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.404229E+09 | 0.00 | 0.134421E+09 | 236225.63 | 0.134185E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.704585E+09 | 0.227688E+09 | 0.297947E+09 | 0.144207E+09 | 0.167436E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 31467367.32 | 40190667.69 | 25315076.64 | 7662704.12 | 17652372.52 | 0.00 | 0.00 |
| February | 34915817.18 | 30754289.12 | 24876627.23 | 6715868.58 | 18160758.64 | 0.00 | 0.00 |
| March | 50941964.41 | 25051163.31 | 30470320.40 | 7488697.26 | 22981623.13 | 0.00 | 0.00 |
| April | 73201928.05 | 13995288.17 | 36005665.65 | 10530660.10 | 25475005.55 | 0.00 | 0.00 |
| May | 0.103919E+09 | 3076645.90 | 41397035.71 | 13164625.93 | 28232409.78 | 0.00 | 0.00 |
| June | 0.106651E+09 | 589749.12 | 39297122.34 | 12023069.28 | 27274053.06 | 0.00 | 0.00 |
| July | 0.120761E+09 | 3189.91 | 37922842.04 | 10948551.32 | 26974290.73 | 0.00 | 0.00 |
| August | 0.123780E+09 | 0.00 | 38776861.92 | 11880348.61 | 26896513.31 | 0.00 | 0.00 |
| September | 96491478.56 | 966425.78 | 35251100.85 | 10870208.51 | 24380892.34 | 0.00 | 0.00 |
| October | 76619141.19 | 5040170.50 | 33039569.33 | 10766010.94 | 22273558.39 | 0.00 | 0.00 |
| November | 50282569.05 | 16055771.41 | 26839288.66 | 8491726.58 | 18347562.09 | 0.00 | 0.00 |
| December | 30952705.06 | 33087436.84 | 22411988.89 | 6138048.24 | 16273940.65 | 0.00 | 0.00 |
| Annual Sum or Average | 0.899984E+09 | 0.168811E+09 | 0.391603E+09 | 0.116681E+09 | 0.274923E+09 | 0.00 | 0.00 |
| Minimum of Months | 30952705.06 | 0.00 | 22411988.89 | 6138048.24 | 16273940.65 | 0.00 | 0.00 |
| Maximum of Months | 0.123780E+09 | 40190667.69 | 41397035.71 | 13164625.93 | 28232409.78 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 89377993.88 | 0.127105E+09 | 75394598.24 | 22821439.85 | 52573158.39 | 0.00 | 0.00 |
| February | 0.100518E+09 | 97390802.34 | 74088786.76 | 20001527.98 | 54087258.79 | 0.00 | 0.00 |
| March | 0.146216E+09 | 81840192.28 | 90748197.09 | 22303204.11 | 68444992.98 | 0.00 | 0.00 |
| April | 0.208899E+09 | 51398254.96 | 0.107234E+09 | 31362926.47 | 75870906.32 | 0.00 | 0.00 |
| May | 0.287338E+09 | 16357964.70 | 0.123291E+09 | 39207532.22 | 84083142.32 | 0.00 | 0.00 |
| June | 0.289563E+09 | 6321744.95 | 0.117037E+09 | 35807692.40 | 81228917.54 | 0.00 | 0.00 |
| July | 0.321485E+09 | 443656.68 | 0.112944E+09 | 32607510.52 | 80336150.69 | 0.00 | 0.00 |
| August | 0.327509E+09 | 257706.86 | 0.115487E+09 | 35382634.74 | 80104510.20 | 0.00 | 0.00 |
| September | 0.256419E+09 | 8252484.86 | 0.104987E+09 | 32374186.13 | 72612364.90 | 0.00 | 0.00 |
| October | 0.207921E+09 | 28948991.16 | 98400059.82 | 32063859.85 | 66336199.96 | 0.00 | 0.00 |
| November | 0.138540E+09 | 64147469.82 | 79934080.96 | 25290475.03 | 54643605.93 | 0.00 | 0.00 |
| December | 85712283.03 | 0.110239E+09 | 66748480.44 | 18280635.20 | 48467845.23 | 0.00 | 0.00 |
| Annual Sum or Average | 0.245950E+10 | 0.592703E+09 | 0.116629E+10 | 0.347504E+09 | 0.818789E+09 | 0.00 | 0.00 |
| Minimum of Months | 85712283.03 | 257706.86 | 66748480.44 | 18280635.20 | 48467845.23 | 0.00 | 0.00 |
| Maximum of Months | 0.327509E+09 | 0.127105E+09 | 0.123291E+09 | 39207532.22 | 84083142.32 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 29739580.49 | 42305035.27 | 25315076.64 | 7662704.12 | 17652372.52 | 0.00 | 0.00 |
| February | 33950520.64 | 32059993.21 | 24876627.23 | 6715868.58 | 18160758.64 | 0.00 | 0.00 |
| March | 50474148.78 | 26028310.97 | 30470320.40 | 7488697.26 | 22981623.13 | 0.00 | 0.00 |
| April | 73782475.10 | 14503960.67 | 36005665.65 | 10530660.10 | 25475005.55 | 0.00 | 0.00 |
| May | 0.106118E+09 | 3196704.09 | 41397035.71 | 13164625.93 | 28232409.78 | 0.00 | 0.00 |
| June | 0.109193E+09 | 630521.00 | 39297122.34 | 12023069.28 | 27274053.06 | 0.00 | 0.00 |
| July | 0.124253E+09 | 4141.78 | 37922842.04 | 10948551.32 | 26974290.73 | 0.00 | 0.00 |
| August | 0.127296E+09 | 0.00 | 38776861.92 | 11880348.61 | 26896513.31 | 0.00 | 0.00 |
| September | 98821210.79 | 1037405.62 | 35251100.85 | 10870208.51 | 24380892.34 | 0.00 | 0.00 |
| October | 77963863.92 | 5348748.69 | 33039569.33 | 10766010.94 | 22273558.39 | 0.00 | 0.00 |
| November | 50287590.03 | 16810044.15 | 26839288.66 | 8491726.58 | 18347562.09 | 0.00 | 0.00 |
| December | 29808515.37 | 34641909.67 | 22411988.89 | 6138048.24 | 16273940.65 | 0.00 | 0.00 |
| Annual Sum or Average | 0.911687E+09 | 0.176567E+09 | 0.391603E+09 | 0.116681E+09 | 0.274923E+09 | 0.00 | 0.00 |
| Minimum of Months | 29739580.49 | 0.00 | 22411988.89 | 6138048.24 | 16273940.65 | 0.00 | 0.00 |
| Maximum of Months | 0.127296E+09 | 42305035.27 | 41397035.71 | 13164625.93 | 28232409.78 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
| February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
| March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
| April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
| May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
| June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
| July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
| August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
| September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
| October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
| November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
| December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
| Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
| Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
| Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
| February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
| March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
| April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
| May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
| June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
| July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
| August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
| September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
| October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
| November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
| December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
| Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
| February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
| March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
| April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
| May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
| June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
| July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
| August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
| September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
| October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
| November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
| December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
| Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
| February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
| March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
| April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
| May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
| June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
| July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
| August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
| September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
| October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
| November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
| December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
| Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
| February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
| March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
| April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
| May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
| June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
| July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
| August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
| September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
| October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
| November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
| December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
| Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.242625E+11 | -0.233555E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -907041409.4 | 59.95 | 0.00 | 0.00 |
| February | 0.213214E+11 | -0.205091E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -812342711.8 | 59.95 | 0.00 | 0.00 |
| March | 0.220575E+11 | -0.211678E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -889622272.6 | 59.95 | 0.00 | 0.00 |
| April | 0.193040E+11 | -0.184614E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -842603830.5 | 59.95 | 0.00 | 0.00 |
| May | 0.178686E+11 | -0.170278E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -840870081.9 | 59.95 | 0.00 | 0.00 |
| June | 0.158705E+11 | -0.150669E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -803568097.5 | 59.95 | 0.00 | 0.00 |
| July | 0.159194E+11 | -0.151012E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -818179435.3 | 59.95 | 0.00 | 0.00 |
| August | 0.165761E+11 | -0.157617E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -814324016.6 | 59.95 | 0.00 | 0.00 |
| September | 0.175953E+11 | -0.167935E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -801776606.3 | 59.95 | 0.00 | 0.00 |
| October | 0.202966E+11 | -0.194529E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -843678968.2 | 59.95 | 0.00 | 0.00 |
| November | 0.216379E+11 | -0.207997E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -838217896.1 | 59.95 | 0.00 | 0.00 |
| December | 0.238136E+11 | -0.229216E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -892023547.2 | 59.95 | 0.00 | 0.00 |
| Annual Sum or Average | 0.236523E+12 | -0.226419E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.101042E+11 | 59.95 | 0.00 | 0.00 |
| Minimum of Months | 0.158705E+11 | -0.233555E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -907041409.4 | 59.95 | 0.00 | 0.00 |
| Maximum of Months | 0.242625E+11 | -0.150669E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -801776606.3 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HEATING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.160177E+10 | 0.146263E+10 | 7959.44 | 30-JAN-12:02 | 6061.05 | 0.00 |
| February | 0.00 | 0.00 | 0.177941E+10 | 0.158688E+10 | 8006.31 | 18-FEB-12:52 | 5890.43 | 0.00 |
| March | 0.00 | 0.00 | 0.242078E+10 | 0.220229E+10 | 8095.09 | 24-MAR-10:12 | 5451.54 | 0.00 |
| April | 0.00 | 0.00 | 0.322871E+10 | 0.284763E+10 | 8295.02 | 30-APR-08:52 | 4734.91 | 0.00 |
| May | 0.00 | 0.00 | 0.486238E+10 | 0.422713E+10 | 8237.00 | 01-MAY-09:22 | 4834.76 | 0.00 |
| June | 0.00 | 0.00 | 0.571614E+10 | 0.464436E+10 | 7489.90 | 22-JUN-09:02 | 6122.83 | 0.00 |
| July | 0.00 | 0.00 | 0.694791E+10 | 0.555552E+10 | 3808.36 | 30-JUL-17:10 | 2861.03 | 0.00 |
| August | 0.00 | 0.00 | 0.757670E+10 | 0.607257E+10 | 4034.85 | 10-AUG-16:10 | 3279.47 | 0.00 |
| September | 0.00 | 0.00 | 0.672383E+10 | 0.543584E+10 | 8051.49 | 25-SEP-07:22 | 5629.85 | 0.00 |
| October | 0.00 | 0.00 | 0.595862E+10 | 0.508048E+10 | 8082.10 | 31-OCT-07:42 | 5556.31 | 0.00 |
| November | 0.00 | 0.00 | 0.438731E+10 | 0.387146E+10 | 8056.44 | 01-NOV-07:52 | 5582.64 | 0.00 |
| December | 0.00 | 0.00 | 0.254367E+10 | 0.225122E+10 | 8129.29 | 24-DEC-12:12 | 5407.82 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.537472E+11 | 0.452380E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.160177E+10 | 0.146263E+10 | 3808.36 | 2861.03 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.757670E+10 | 0.607257E+10 | 8295.02 | 6122.83 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.100291E+10 | 0.893161E+09 | 7783.67 | 30-JAN-11:22 | 5649.27 | 0.00 |
| February | 0.00 | 0.00 | 0.126769E+10 | 0.110171E+10 | 7775.93 | 07-FEB-09:42 | 5515.74 | 0.00 |
| March | 0.00 | 0.00 | 0.201011E+10 | 0.180649E+10 | 7872.81 | 29-MAR-09:42 | 5111.30 | 0.00 |
| April | 0.00 | 0.00 | 0.298942E+10 | 0.261918E+10 | 8020.46 | 30-APR-08:52 | 4674.11 | 0.00 |
| May | 0.00 | 0.00 | 0.487446E+10 | 0.423473E+10 | 8002.31 | 01-MAY-09:12 | 4671.24 | 0.00 |
| June | 0.00 | 0.00 | 0.584349E+10 | 0.476208E+10 | 7263.20 | 22-JUN-09:02 | 5923.47 | 0.00 |
| July | 0.00 | 0.00 | 0.698816E+10 | 0.559339E+10 | 3759.07 | 19-JUL-16:40 | 2857.98 | 0.00 |
| August | 0.00 | 0.00 | 0.745271E+10 | 0.594840E+10 | 3977.93 | 10-AUG-16:10 | 3200.39 | 0.00 |
| September | 0.00 | 0.00 | 0.630626E+10 | 0.503387E+10 | 7853.67 | 25-SEP-07:22 | 5292.26 | 0.00 |
| October | 0.00 | 0.00 | 0.525459E+10 | 0.439958E+10 | 7889.23 | 31-OCT-07:52 | 5191.12 | 0.00 |
| November | 0.00 | 0.00 | 0.357702E+10 | 0.309287E+10 | 7857.46 | 01-NOV-08:12 | 5194.32 | 0.00 |
| December | 0.00 | 0.00 | 0.185971E+10 | 0.160352E+10 | 7914.06 | 24-DEC-13:32 | 5161.13 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.494265E+11 | 0.410890E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.100291E+10 | 0.893161E+09 | 3759.07 | 2857.98 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.745271E+10 | 0.594840E+10 | 8020.46 | 5923.47 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.174224E+10 | 0.160928E+10 | 9018.58 | 30-JAN-07:01 | 7233.80 | 0.00 |
| February | 0.00 | 0.00 | 0.183920E+10 | 0.165567E+10 | 9145.45 | 09-FEB-07:01 | 6736.58 | 0.00 |
| March | 0.00 | 0.00 | 0.232944E+10 | 0.214235E+10 | 9213.51 | 29-MAR-06:01 | 6249.65 | 0.00 |
| April | 0.00 | 0.00 | 0.259702E+10 | 0.234386E+10 | 9276.09 | 12-APR-06:01 | 6135.48 | 0.00 |
| May | 0.00 | 0.00 | 0.430139E+10 | 0.378711E+10 | 9604.96 | 25-MAY-06:01 | 5358.90 | 0.00 |
| June | 0.00 | 0.00 | 0.523208E+10 | 0.420258E+10 | 9604.63 | 08-JUN-06:11 | 4066.76 | 0.00 |
| July | 0.00 | 0.00 | 0.651633E+10 | 0.494901E+10 | 9535.35 | 06-JUL-06:06 | 4007.16 | 0.00 |
| August | 0.00 | 0.00 | 0.753560E+10 | 0.570463E+10 | 9534.51 | 31-AUG-06:04 | 4930.38 | 0.00 |
| September | 0.00 | 0.00 | 0.600444E+10 | 0.466049E+10 | 9607.25 | 25-SEP-06:01 | 5889.16 | 0.00 |
| October | 0.00 | 0.00 | 0.512483E+10 | 0.423743E+10 | 9606.20 | 31-OCT-06:01 | 5843.88 | 0.00 |
| November | 0.00 | 0.00 | 0.356445E+10 | 0.309277E+10 | 9558.53 | 03-NOV-06:01 | 5867.85 | 0.00 |
| December | 0.00 | 0.00 | 0.226070E+10 | 0.202276E+10 | 9142.21 | 11-DEC-07:01 | 7119.40 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.490477E+11 | 0.404079E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.174224E+10 | 0.160928E+10 | 9018.58 | 4007.16 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.753560E+10 | 0.570463E+10 | 9607.25 | 7233.80 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.101006E+10 | 0.899771E+09 | 7474.95 | 30-JAN-11:22 | 5453.07 | 0.00 |
| February | 0.00 | 0.00 | 0.126227E+10 | 0.109598E+10 | 7480.32 | 07-FEB-09:42 | 5332.81 | 0.00 |
| March | 0.00 | 0.00 | 0.198375E+10 | 0.178085E+10 | 7557.54 | 24-MAR-10:12 | 5035.34 | 0.00 |
| April | 0.00 | 0.00 | 0.302148E+10 | 0.264896E+10 | 7690.20 | 30-APR-08:52 | 4560.41 | 0.00 |
| May | 0.00 | 0.00 | 0.492537E+10 | 0.428407E+10 | 7655.15 | 01-MAY-09:12 | 4616.74 | 0.00 |
| June | 0.00 | 0.00 | 0.585762E+10 | 0.477526E+10 | 6963.60 | 22-JUN-09:02 | 5731.28 | 0.00 |
| July | 0.00 | 0.00 | 0.700669E+10 | 0.561108E+10 | 3620.73 | 30-JUL-17:10 | 2706.94 | 0.00 |
| August | 0.00 | 0.00 | 0.747553E+10 | 0.597013E+10 | 3752.66 | 10-AUG-16:10 | 2992.81 | 0.00 |
| September | 0.00 | 0.00 | 0.632266E+10 | 0.504950E+10 | 7547.17 | 25-SEP-07:22 | 5092.25 | 0.00 |
| October | 0.00 | 0.00 | 0.528161E+10 | 0.442318E+10 | 7581.03 | 31-OCT-07:52 | 4996.21 | 0.00 |
| November | 0.00 | 0.00 | 0.357948E+10 | 0.309343E+10 | 7547.22 | 01-NOV-08:12 | 5003.55 | 0.00 |
| December | 0.00 | 0.00 | 0.184486E+10 | 0.158910E+10 | 7604.11 | 24-DEC-13:32 | 4970.24 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.495714E+11 | 0.412213E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.101006E+10 | 0.899771E+09 | 3620.73 | 2706.94 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.747553E+10 | 0.597013E+10 | 7690.20 | 5731.28 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.106192E+10 | 0.947862E+09 | 6521.43 | 30-JAN-11:22 | 4759.20 | 0.00 |
| February | 0.00 | 0.00 | 0.126090E+10 | 0.109335E+10 | 6518.19 | 07-FEB-09:42 | 4636.38 | 0.00 |
| March | 0.00 | 0.00 | 0.185181E+10 | 0.165388E+10 | 6597.38 | 29-MAR-09:42 | 4290.62 | 0.00 |
| April | 0.00 | 0.00 | 0.261937E+10 | 0.227079E+10 | 6725.63 | 30-APR-08:52 | 3921.94 | 0.00 |
| May | 0.00 | 0.00 | 0.408041E+10 | 0.348795E+10 | 6713.90 | 01-MAY-09:12 | 3907.27 | 0.00 |
| June | 0.00 | 0.00 | 0.484963E+10 | 0.385868E+10 | 6115.60 | 22-JUN-09:02 | 4906.53 | 0.00 |
| July | 0.00 | 0.00 | 0.575639E+10 | 0.447650E+10 | 2919.59 | 19-JUL-16:40 | 2116.29 | 0.00 |
| August | 0.00 | 0.00 | 0.607187E+10 | 0.469597E+10 | 3003.46 | 10-AUG-17:12 | 2324.60 | 0.00 |
| September | 0.00 | 0.00 | 0.517883E+10 | 0.401271E+10 | 6605.78 | 25-SEP-07:22 | 4367.85 | 0.00 |
| October | 0.00 | 0.00 | 0.435852E+10 | 0.356820E+10 | 6622.57 | 31-OCT-07:52 | 4330.05 | 0.00 |
| November | 0.00 | 0.00 | 0.305152E+10 | 0.260148E+10 | 6598.37 | 01-NOV-08:12 | 4350.48 | 0.00 |
| December | 0.00 | 0.00 | 0.174645E+10 | 0.149846E+10 | 6637.99 | 24-DEC-13:32 | 4324.15 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.418876E+11 | 0.341658E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.106192E+10 | 0.947862E+09 | 2919.59 | 2116.29 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.607187E+10 | 0.469597E+10 | 6725.63 | 4906.53 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.106347E+10 | 0.949238E+09 | 6515.49 | 30-JAN-11:22 | 4755.17 | 0.00 |
| February | 0.00 | 0.00 | 0.126182E+10 | 0.109418E+10 | 6512.50 | 07-FEB-09:42 | 4632.86 | 0.00 |
| March | 0.00 | 0.00 | 0.185170E+10 | 0.165376E+10 | 6591.74 | 29-MAR-09:42 | 4288.12 | 0.00 |
| April | 0.00 | 0.00 | 0.262174E+10 | 0.227298E+10 | 6719.43 | 30-APR-08:52 | 3919.05 | 0.00 |
| May | 0.00 | 0.00 | 0.408278E+10 | 0.349019E+10 | 6707.50 | 01-MAY-09:12 | 3905.09 | 0.00 |
| June | 0.00 | 0.00 | 0.485035E+10 | 0.385933E+10 | 6109.99 | 22-JUN-09:02 | 4902.31 | 0.00 |
| July | 0.00 | 0.00 | 0.575720E+10 | 0.447722E+10 | 2916.30 | 19-JUL-16:40 | 2113.63 | 0.00 |
| August | 0.00 | 0.00 | 0.607286E+10 | 0.469688E+10 | 3000.13 | 10-AUG-17:12 | 2321.62 | 0.00 |
| September | 0.00 | 0.00 | 0.517962E+10 | 0.401343E+10 | 6599.89 | 25-SEP-07:22 | 4363.77 | 0.00 |
| October | 0.00 | 0.00 | 0.435991E+10 | 0.356944E+10 | 6616.65 | 31-OCT-07:52 | 4326.06 | 0.00 |
| November | 0.00 | 0.00 | 0.305299E+10 | 0.260279E+10 | 6592.43 | 01-NOV-08:12 | 4346.43 | 0.00 |
| December | 0.00 | 0.00 | 0.174722E+10 | 0.149914E+10 | 6631.97 | 24-DEC-13:32 | 4320.49 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.419016E+11 | 0.341786E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.106347E+10 | 0.949238E+09 | 2916.30 | 2113.63 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.607286E+10 | 0.469688E+10 | 6719.43 | 4902.31 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.168812E+10 | 0.154498E+10 | 6737.66 | 30-JAN-12:02 | 5168.96 | 0.00 |
| February | 0.00 | 0.00 | 0.178867E+10 | 0.159482E+10 | 6777.47 | 18-FEB-12:52 | 5024.57 | 0.00 |
| March | 0.00 | 0.00 | 0.228433E+10 | 0.207012E+10 | 6860.50 | 29-MAR-09:42 | 4551.84 | 0.00 |
| April | 0.00 | 0.00 | 0.287591E+10 | 0.251462E+10 | 7029.61 | 30-APR-08:52 | 4019.44 | 0.00 |
| May | 0.00 | 0.00 | 0.408289E+10 | 0.349410E+10 | 6983.64 | 01-MAY-09:22 | 4092.55 | 0.00 |
| June | 0.00 | 0.00 | 0.473322E+10 | 0.375212E+10 | 6371.94 | 22-JUN-09:02 | 5122.75 | 0.00 |
| July | 0.00 | 0.00 | 0.572960E+10 | 0.445158E+10 | 3001.25 | 30-JUL-17:10 | 2188.77 | 0.00 |
| August | 0.00 | 0.00 | 0.621294E+10 | 0.483460E+10 | 3057.23 | 22-AUG-17:20 | 2171.61 | 0.00 |
| September | 0.00 | 0.00 | 0.562054E+10 | 0.443304E+10 | 6863.50 | 25-SEP-07:22 | 4632.48 | 0.00 |
| October | 0.00 | 0.00 | 0.509280E+10 | 0.427235E+10 | 6851.57 | 31-OCT-07:42 | 4706.54 | 0.00 |
| November | 0.00 | 0.00 | 0.388880E+10 | 0.340212E+10 | 6860.41 | 01-NOV-07:52 | 4626.11 | 0.00 |
| December | 0.00 | 0.00 | 0.245164E+10 | 0.216591E+10 | 6880.47 | 24-DEC-12:12 | 4602.66 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.464495E+11 | 0.385303E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.168812E+10 | 0.154498E+10 | 3001.25 | 2171.61 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.621294E+10 | 0.483460E+10 | 7029.61 | 5168.96 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.176926E+10 | 0.162308E+10 | 6771.12 | 30-JAN-12:02 | 5265.50 | 0.00 |
| February | 0.00 | 0.00 | 0.188317E+10 | 0.168421E+10 | 6822.21 | 18-FEB-12:52 | 5080.59 | 0.00 |
| March | 0.00 | 0.00 | 0.242425E+10 | 0.220393E+10 | 6903.59 | 24-MAR-10:12 | 4684.69 | 0.00 |
| April | 0.00 | 0.00 | 0.310448E+10 | 0.273123E+10 | 7029.01 | 30-APR-08:52 | 4227.59 | 0.00 |
| May | 0.00 | 0.00 | 0.441116E+10 | 0.380723E+10 | 6977.76 | 01-MAY-09:22 | 4318.75 | 0.00 |
| June | 0.00 | 0.00 | 0.506617E+10 | 0.406454E+10 | 6398.61 | 22-JUN-09:02 | 5218.12 | 0.00 |
| July | 0.00 | 0.00 | 0.610091E+10 | 0.480191E+10 | 3195.52 | 30-JUL-17:10 | 2364.13 | 0.00 |
| August | 0.00 | 0.00 | 0.657349E+10 | 0.517579E+10 | 3165.33 | 22-AUG-17:20 | 2269.54 | 0.00 |
| September | 0.00 | 0.00 | 0.597439E+10 | 0.476754E+10 | 6864.70 | 25-SEP-07:22 | 4843.37 | 0.00 |
| October | 0.00 | 0.00 | 0.544479E+10 | 0.460890E+10 | 6883.63 | 31-OCT-07:42 | 4802.02 | 0.00 |
| November | 0.00 | 0.00 | 0.416421E+10 | 0.366757E+10 | 6864.33 | 01-NOV-07:52 | 4807.55 | 0.00 |
| December | 0.00 | 0.00 | 0.259160E+10 | 0.229926E+10 | 6918.35 | 24-DEC-12:12 | 4672.97 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.495079E+11 | 0.414352E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.176926E+10 | 0.162308E+10 | 3165.33 | 2269.54 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.657349E+10 | 0.517579E+10 | 7029.01 | 5265.50 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.292388E+10 | 0.265478E+10 | 16700.41 | 30-JAN-12:02 | 12280.49 | 0.00 |
| February | 0.00 | 0.00 | 0.366421E+10 | 0.326914E+10 | 16721.33 | 18-FEB-12:52 | 12140.98 | 0.00 |
| March | 0.00 | 0.00 | 0.542476E+10 | 0.495375E+10 | 16910.47 | 29-MAR-09:42 | 11045.74 | 0.00 |
| April | 0.00 | 0.00 | 0.723022E+10 | 0.640748E+10 | 17364.26 | 30-APR-08:52 | 9646.33 | 0.00 |
| May | 0.00 | 0.00 | 0.102111E+11 | 0.887992E+10 | 17250.45 | 01-MAY-09:22 | 9841.42 | 0.00 |
| June | 0.00 | 0.00 | 0.116282E+11 | 0.938500E+10 | 15687.21 | 22-JUN-09:02 | 12582.69 | 0.00 |
| July | 0.00 | 0.00 | 0.136532E+11 | 0.107626E+11 | 7927.89 | 30-JUL-16:10 | 6107.57 | 0.00 |
| August | 0.00 | 0.00 | 0.142513E+11 | 0.111558E+11 | 8171.26 | 10-AUG-16:10 | 6528.94 | 0.00 |
| September | 0.00 | 0.00 | 0.123711E+11 | 0.975289E+10 | 17032.89 | 25-SEP-07:22 | 10774.07 | 0.00 |
| October | 0.00 | 0.00 | 0.105473E+11 | 0.880451E+10 | 17201.33 | 31-OCT-07:42 | 10231.70 | 0.00 |
| November | 0.00 | 0.00 | 0.754373E+10 | 0.654139E+10 | 17179.55 | 01-NOV-07:52 | 10307.17 | 0.00 |
| December | 0.00 | 0.00 | 0.435399E+10 | 0.380394E+10 | 17074.21 | 24-DEC-12:12 | 10921.56 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.103803E+12 | 0.863712E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.292388E+10 | 0.265478E+10 | 7927.89 | 6107.57 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.142513E+11 | 0.111558E+11 | 17364.26 | 12582.69 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.164251E+10 | 0.144571E+10 | 16297.77 | 30-JAN-11:22 | 11306.88 | 0.00 |
| February | 0.00 | 0.00 | 0.255782E+10 | 0.222102E+10 | 16273.99 | 08-FEB-22:22 | 11353.91 | 0.00 |
| March | 0.00 | 0.00 | 0.454750E+10 | 0.410520E+10 | 16398.91 | 29-MAR-09:42 | 10519.25 | 0.00 |
| April | 0.00 | 0.00 | 0.671396E+10 | 0.591247E+10 | 16746.46 | 30-APR-08:52 | 9528.13 | 0.00 |
| May | 0.00 | 0.00 | 0.102134E+11 | 0.887415E+10 | 16727.44 | 01-MAY-09:12 | 9525.24 | 0.00 |
| June | 0.00 | 0.00 | 0.118639E+11 | 0.960218E+10 | 15198.54 | 22-JUN-09:02 | 12163.51 | 0.00 |
| July | 0.00 | 0.00 | 0.137033E+11 | 0.108091E+11 | 7756.22 | 19-JUL-16:30 | 5794.59 | 0.00 |
| August | 0.00 | 0.00 | 0.139617E+11 | 0.108701E+11 | 8039.54 | 10-AUG-16:10 | 6352.28 | 0.00 |
| September | 0.00 | 0.00 | 0.114700E+11 | 0.889502E+10 | 16515.29 | 25-SEP-07:22 | 10251.00 | 0.00 |
| October | 0.00 | 0.00 | 0.904689E+10 | 0.737059E+10 | 16656.25 | 31-OCT-07:52 | 9739.64 | 0.00 |
| November | 0.00 | 0.00 | 0.583716E+10 | 0.492483E+10 | 16620.78 | 01-NOV-08:12 | 9818.16 | 0.00 |
| December | 0.00 | 0.00 | 0.293547E+10 | 0.247764E+10 | 16538.10 | 06-DEC-11:42 | 10170.43 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.944937E+11 | 0.775080E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.164251E+10 | 0.144571E+10 | 7756.22 | 5794.59 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.139617E+11 | 0.108701E+11 | 16746.46 | 12163.51 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.293884E+10 | 0.266985E+10 | 15957.12 | 30-JAN-12:02 | 11798.27 | 0.00 |
| February | 0.00 | 0.00 | 0.364972E+10 | 0.325531E+10 | 15999.32 | 07-FEB-09:42 | 11415.34 | 0.00 |
| March | 0.00 | 0.00 | 0.536803E+10 | 0.489957E+10 | 16147.07 | 29-MAR-09:42 | 10702.47 | 0.00 |
| April | 0.00 | 0.00 | 0.730345E+10 | 0.647873E+10 | 16555.84 | 30-APR-08:52 | 9407.65 | 0.00 |
| May | 0.00 | 0.00 | 0.103202E+11 | 0.898873E+10 | 16428.95 | 01-MAY-09:22 | 9647.04 | 0.00 |
| June | 0.00 | 0.00 | 0.116606E+11 | 0.941793E+10 | 14957.87 | 22-JUN-09:02 | 12162.69 | 0.00 |
| July | 0.00 | 0.00 | 0.136938E+11 | 0.108045E+11 | 7602.30 | 30-JUL-16:10 | 5818.92 | 0.00 |
| August | 0.00 | 0.00 | 0.143008E+11 | 0.112058E+11 | 7598.99 | 10-AUG-16:10 | 6003.84 | 0.00 |
| September | 0.00 | 0.00 | 0.124083E+11 | 0.979118E+10 | 16299.29 | 25-SEP-07:22 | 10357.51 | 0.00 |
| October | 0.00 | 0.00 | 0.106079E+11 | 0.885939E+10 | 16459.56 | 31-OCT-07:42 | 9840.62 | 0.00 |
| November | 0.00 | 0.00 | 0.755338E+10 | 0.654776E+10 | 16435.47 | 01-NOV-07:52 | 9923.46 | 0.00 |
| December | 0.00 | 0.00 | 0.432134E+10 | 0.377454E+10 | 16304.51 | 24-DEC-12:12 | 10534.81 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.104126E+12 | 0.866933E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.293884E+10 | 0.266985E+10 | 7598.99 | 5818.92 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.143008E+11 | 0.112058E+11 | 16555.84 | 12162.69 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.165519E+10 | 0.145695E+10 | 15558.85 | 30-JAN-11:22 | 10877.56 | 0.00 |
| February | 0.00 | 0.00 | 0.254324E+10 | 0.220736E+10 | 15540.53 | 08-FEB-22:22 | 10821.46 | 0.00 |
| March | 0.00 | 0.00 | 0.449214E+10 | 0.405249E+10 | 15654.37 | 24-MAR-10:12 | 10361.64 | 0.00 |
| April | 0.00 | 0.00 | 0.678645E+10 | 0.598213E+10 | 15962.38 | 30-APR-08:52 | 9257.26 | 0.00 |
| May | 0.00 | 0.00 | 0.103235E+11 | 0.898348E+10 | 15898.27 | 01-MAY-09:12 | 9350.26 | 0.00 |
| June | 0.00 | 0.00 | 0.118968E+11 | 0.963539E+10 | 14466.11 | 22-JUN-09:02 | 11745.02 | 0.00 |
| July | 0.00 | 0.00 | 0.137443E+11 | 0.108511E+11 | 7365.53 | 30-JUL-17:10 | 5381.40 | 0.00 |
| August | 0.00 | 0.00 | 0.140120E+11 | 0.109203E+11 | 7466.52 | 10-AUG-16:10 | 5828.75 | 0.00 |
| September | 0.00 | 0.00 | 0.115085E+11 | 0.893368E+10 | 15779.60 | 25-SEP-07:22 | 9838.82 | 0.00 |
| October | 0.00 | 0.00 | 0.910929E+10 | 0.742515E+10 | 15914.80 | 31-OCT-07:52 | 9363.08 | 0.00 |
| November | 0.00 | 0.00 | 0.584455E+10 | 0.492728E+10 | 15882.67 | 01-NOV-08:12 | 9481.44 | 0.00 |
| December | 0.00 | 0.00 | 0.289938E+10 | 0.244320E+10 | 15806.64 | 06-DEC-11:42 | 9822.12 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.948153E+11 | 0.778185E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.165519E+10 | 0.145695E+10 | 7365.53 | 5381.40 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.140120E+11 | 0.109203E+11 | 15962.38 | 11745.02 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.192538E+10 | 0.170796E+10 | 13515.35 | 30-JAN-11:22 | 9438.48 | 0.00 |
| February | 0.00 | 0.00 | 0.254173E+10 | 0.220164E+10 | 13486.67 | 08-FEB-22:22 | 9463.91 | 0.00 |
| March | 0.00 | 0.00 | 0.403556E+10 | 0.361759E+10 | 13601.32 | 29-MAR-09:42 | 8715.70 | 0.00 |
| April | 0.00 | 0.00 | 0.562301E+10 | 0.489186E+10 | 13890.25 | 30-APR-08:52 | 7859.69 | 0.00 |
| May | 0.00 | 0.00 | 0.822671E+10 | 0.701811E+10 | 13891.13 | 01-MAY-09:12 | 7852.18 | 0.00 |
| June | 0.00 | 0.00 | 0.953077E+10 | 0.751191E+10 | 12660.10 | 22-JUN-09:02 | 9971.99 | 0.00 |
| July | 0.00 | 0.00 | 0.109929E+11 | 0.840210E+10 | 5777.36 | 19-JUL-16:13 | 4069.28 | 0.00 |
| August | 0.00 | 0.00 | 0.111665E+11 | 0.840674E+10 | 5792.27 | 22-AUG-17:10 | 3914.22 | 0.00 |
| September | 0.00 | 0.00 | 0.931677E+10 | 0.700698E+10 | 13713.49 | 25-SEP-07:22 | 8432.27 | 0.00 |
| October | 0.00 | 0.00 | 0.752816E+10 | 0.599997E+10 | 13804.07 | 31-OCT-07:52 | 8128.19 | 0.00 |
| November | 0.00 | 0.00 | 0.510365E+10 | 0.425640E+10 | 13777.18 | 01-NOV-08:12 | 8181.30 | 0.00 |
| December | 0.00 | 0.00 | 0.295139E+10 | 0.249204E+10 | 13716.98 | 06-DEC-11:42 | 8460.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.789425E+11 | 0.635133E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.192538E+10 | 0.170796E+10 | 5777.36 | 3914.22 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.111665E+11 | 0.840674E+10 | 13891.13 | 9971.99 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.192901E+10 | 0.171121E+10 | 13502.32 | 30-JAN-11:22 | 9430.75 | 0.00 |
| February | 0.00 | 0.00 | 0.254577E+10 | 0.220528E+10 | 13473.39 | 08-FEB-22:22 | 9453.70 | 0.00 |
| March | 0.00 | 0.00 | 0.403603E+10 | 0.361814E+10 | 13588.49 | 29-MAR-09:42 | 8710.18 | 0.00 |
| April | 0.00 | 0.00 | 0.562834E+10 | 0.489683E+10 | 13877.02 | 30-APR-08:52 | 7854.32 | 0.00 |
| May | 0.00 | 0.00 | 0.823132E+10 | 0.702250E+10 | 13878.15 | 01-MAY-09:12 | 7848.80 | 0.00 |
| June | 0.00 | 0.00 | 0.953237E+10 | 0.751338E+10 | 12647.16 | 22-JUN-09:02 | 9962.87 | 0.00 |
| July | 0.00 | 0.00 | 0.109946E+11 | 0.840368E+10 | 5771.19 | 19-JUL-16:13 | 4064.59 | 0.00 |
| August | 0.00 | 0.00 | 0.111686E+11 | 0.840860E+10 | 5784.96 | 22-AUG-17:10 | 3908.23 | 0.00 |
| September | 0.00 | 0.00 | 0.931856E+10 | 0.700863E+10 | 13700.12 | 25-SEP-07:22 | 8423.64 | 0.00 |
| October | 0.00 | 0.00 | 0.753135E+10 | 0.600281E+10 | 13790.59 | 31-OCT-07:52 | 8120.23 | 0.00 |
| November | 0.00 | 0.00 | 0.510798E+10 | 0.426026E+10 | 13763.84 | 01-NOV-08:12 | 8173.79 | 0.00 |
| December | 0.00 | 0.00 | 0.295363E+10 | 0.249405E+10 | 13704.06 | 06-DEC-11:42 | 8455.05 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.789775E+11 | 0.635454E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.192901E+10 | 0.171121E+10 | 5771.19 | 3908.23 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.111686E+11 | 0.840860E+10 | 13878.15 | 9962.87 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.324488E+10 | 0.296119E+10 | 14000.51 | 30-JAN-12:02 | 10402.90 | 0.00 |
| February | 0.00 | 0.00 | 0.367240E+10 | 0.327601E+10 | 14029.36 | 18-FEB-12:52 | 10295.68 | 0.00 |
| March | 0.00 | 0.00 | 0.492809E+10 | 0.447950E+10 | 14192.66 | 24-MAR-10:12 | 9444.84 | 0.00 |
| April | 0.00 | 0.00 | 0.614486E+10 | 0.539029E+10 | 14572.44 | 30-APR-08:52 | 8055.27 | 0.00 |
| May | 0.00 | 0.00 | 0.822438E+10 | 0.702421E+10 | 14495.92 | 01-MAY-09:22 | 8215.06 | 0.00 |
| June | 0.00 | 0.00 | 0.929083E+10 | 0.729326E+10 | 13225.15 | 22-JUN-09:02 | 10427.26 | 0.00 |
| July | 0.00 | 0.00 | 0.109406E+11 | 0.835446E+10 | 5931.92 | 30-JUL-17:10 | 4236.54 | 0.00 |
| August | 0.00 | 0.00 | 0.114604E+11 | 0.869280E+10 | 5913.33 | 10-AUG-16:10 | 4562.06 | 0.00 |
| September | 0.00 | 0.00 | 0.102322E+11 | 0.786903E+10 | 14306.22 | 25-SEP-07:22 | 8993.20 | 0.00 |
| October | 0.00 | 0.00 | 0.905032E+10 | 0.744441E+10 | 14423.36 | 31-OCT-07:42 | 8656.92 | 0.00 |
| November | 0.00 | 0.00 | 0.683599E+10 | 0.589272E+10 | 14409.88 | 01-NOV-07:52 | 8707.56 | 0.00 |
| December | 0.00 | 0.00 | 0.439469E+10 | 0.384691E+10 | 14313.31 | 06-DEC-11:12 | 9215.93 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.884197E+11 | 0.725248E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.324488E+10 | 0.296119E+10 | 5913.33 | 4236.54 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.114604E+11 | 0.869280E+10 | 14572.44 | 10427.26 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.324598E+10 | 0.296441E+10 | 13987.87 | 30-JAN-12:02 | 10406.52 | 0.00 |
| February | 0.00 | 0.00 | 0.367215E+10 | 0.327813E+10 | 14016.63 | 07-FEB-09:42 | 10017.79 | 0.00 |
| March | 0.00 | 0.00 | 0.492591E+10 | 0.447995E+10 | 14180.25 | 24-MAR-10:12 | 9453.51 | 0.00 |
| April | 0.00 | 0.00 | 0.614667E+10 | 0.539483E+10 | 14559.70 | 30-APR-08:52 | 8058.14 | 0.00 |
| May | 0.00 | 0.00 | 0.822508E+10 | 0.702827E+10 | 14482.92 | 01-MAY-09:22 | 8220.21 | 0.00 |
| June | 0.00 | 0.00 | 0.928847E+10 | 0.729436E+10 | 13213.42 | 22-JUN-09:02 | 10431.82 | 0.00 |
| July | 0.00 | 0.00 | 0.109381E+11 | 0.835561E+10 | 5928.32 | 30-JUL-17:10 | 4234.53 | 0.00 |
| August | 0.00 | 0.00 | 0.114581E+11 | 0.869421E+10 | 5905.91 | 10-AUG-16:10 | 4557.10 | 0.00 |
| September | 0.00 | 0.00 | 0.102299E+11 | 0.787023E+10 | 14294.11 | 25-SEP-07:22 | 8992.15 | 0.00 |
| October | 0.00 | 0.00 | 0.904924E+10 | 0.744666E+10 | 14410.83 | 31-OCT-07:42 | 8656.42 | 0.00 |
| November | 0.00 | 0.00 | 0.683568E+10 | 0.589548E+10 | 14397.29 | 01-NOV-07:52 | 8708.02 | 0.00 |
| December | 0.00 | 0.00 | 0.439319E+10 | 0.384812E+10 | 14299.50 | 06-DEC-11:12 | 9220.83 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.884085E+11 | 0.725503E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.324598E+10 | 0.296441E+10 | 5905.91 | 4234.53 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.114581E+11 | 0.869421E+10 | 14559.70 | 10431.82 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.105103E+10 | 0.954572E+09 | 9112.60 | 30-JAN-12:02 | 6543.47 | 0.00 |
| February | 0.00 | 0.00 | 0.155075E+10 | 0.139204E+10 | 9115.61 | 07-FEB-09:42 | 6338.52 | 0.00 |
| March | 0.00 | 0.00 | 0.258831E+10 | 0.237379E+10 | 9203.97 | 29-MAR-09:42 | 5986.31 | 0.00 |
| April | 0.00 | 0.00 | 0.376141E+10 | 0.335546E+10 | 9465.71 | 30-APR-08:52 | 5140.91 | 0.00 |
| May | 0.00 | 0.00 | 0.561007E+10 | 0.491880E+10 | 9390.39 | 01-MAY-09:22 | 5297.35 | 0.00 |
| June | 0.00 | 0.00 | 0.644570E+10 | 0.525730E+10 | 8553.46 | 22-JUN-09:02 | 6760.49 | 0.00 |
| July | 0.00 | 0.00 | 0.767154E+10 | 0.613078E+10 | 4939.72 | 30-JUL-16:10 | 3871.62 | 0.00 |
| August | 0.00 | 0.00 | 0.797865E+10 | 0.632790E+10 | 5070.42 | 10-AUG-16:10 | 4142.71 | 0.00 |
| September | 0.00 | 0.00 | 0.676128E+10 | 0.538395E+10 | 9322.57 | 25-SEP-07:22 | 5579.56 | 0.00 |
| October | 0.00 | 0.00 | 0.557591E+10 | 0.468291E+10 | 9435.38 | 31-OCT-07:42 | 5231.66 | 0.00 |
| November | 0.00 | 0.00 | 0.375449E+10 | 0.326460E+10 | 9403.54 | 01-NOV-07:52 | 5325.88 | 0.00 |
| December | 0.00 | 0.00 | 0.185848E+10 | 0.162616E+10 | 9294.73 | 24-DEC-12:12 | 5880.31 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.546076E+11 | 0.456683E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.105103E+10 | 0.954572E+09 | 4939.72 | 3871.62 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.797865E+10 | 0.632790E+10 | 9465.71 | 6760.49 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.478839E+09 | 0.418413E+09 | 8962.67 | 30-JAN-11:22 | 6126.01 | 0.00 |
| February | 0.00 | 0.00 | 0.100750E+10 | 0.878197E+09 | 8972.75 | 08-FEB-22:22 | 6091.19 | 0.00 |
| March | 0.00 | 0.00 | 0.213767E+10 | 0.193777E+10 | 9004.06 | 29-MAR-09:42 | 5772.45 | 0.00 |
| April | 0.00 | 0.00 | 0.349000E+10 | 0.309418E+10 | 9209.27 | 30-APR-08:52 | 5125.77 | 0.00 |
| May | 0.00 | 0.00 | 0.561140E+10 | 0.491542E+10 | 9169.03 | 01-MAY-09:12 | 5197.39 | 0.00 |
| June | 0.00 | 0.00 | 0.656743E+10 | 0.536986E+10 | 8350.62 | 22-JUN-09:02 | 6592.21 | 0.00 |
| July | 0.00 | 0.00 | 0.769457E+10 | 0.615206E+10 | 4758.97 | 30-JUL-16:10 | 3733.42 | 0.00 |
| August | 0.00 | 0.00 | 0.782248E+10 | 0.617242E+10 | 4977.41 | 10-AUG-16:10 | 4026.04 | 0.00 |
| September | 0.00 | 0.00 | 0.629000E+10 | 0.493139E+10 | 9108.07 | 25-SEP-07:22 | 5381.73 | 0.00 |
| October | 0.00 | 0.00 | 0.479495E+10 | 0.393279E+10 | 9200.04 | 31-OCT-07:52 | 5085.53 | 0.00 |
| November | 0.00 | 0.00 | 0.287518E+10 | 0.243020E+10 | 9153.10 | 01-NOV-08:12 | 5228.43 | 0.00 |
| December | 0.00 | 0.00 | 0.115531E+10 | 0.971333E+09 | 9086.63 | 06-DEC-11:42 | 5594.85 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.499253E+11 | 0.412040E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.478839E+09 | 0.418413E+09 | 4758.97 | 3733.42 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.782248E+10 | 0.617242E+10 | 9209.27 | 6592.21 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.105148E+10 | 0.954899E+09 | 8578.81 | 30-JAN-12:02 | 6196.01 | 0.00 |
| February | 0.00 | 0.00 | 0.153859E+10 | 0.138035E+10 | 8594.69 | 07-FEB-09:42 | 6036.66 | 0.00 |
| March | 0.00 | 0.00 | 0.255647E+10 | 0.234349E+10 | 8645.53 | 29-MAR-09:42 | 5735.84 | 0.00 |
| April | 0.00 | 0.00 | 0.380061E+10 | 0.339295E+10 | 8887.01 | 30-APR-08:52 | 4961.78 | 0.00 |
| May | 0.00 | 0.00 | 0.567160E+10 | 0.497878E+10 | 8803.68 | 01-MAY-09:22 | 5146.58 | 0.00 |
| June | 0.00 | 0.00 | 0.646834E+10 | 0.527880E+10 | 8023.30 | 22-JUN-09:02 | 6474.53 | 0.00 |
| July | 0.00 | 0.00 | 0.769628E+10 | 0.615534E+10 | 4688.12 | 30-JUL-16:10 | 3643.16 | 0.00 |
| August | 0.00 | 0.00 | 0.800823E+10 | 0.635663E+10 | 4663.82 | 10-AUG-16:10 | 3762.28 | 0.00 |
| September | 0.00 | 0.00 | 0.678541E+10 | 0.540733E+10 | 8793.06 | 25-SEP-07:22 | 5307.00 | 0.00 |
| October | 0.00 | 0.00 | 0.561148E+10 | 0.471351E+10 | 8897.18 | 31-OCT-07:42 | 4974.87 | 0.00 |
| November | 0.00 | 0.00 | 0.375929E+10 | 0.326595E+10 | 8865.82 | 01-NOV-07:52 | 5082.12 | 0.00 |
| December | 0.00 | 0.00 | 0.183974E+10 | 0.160873E+10 | 8747.75 | 24-DEC-12:12 | 5581.09 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.547875E+11 | 0.458368E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.105148E+10 | 0.954899E+09 | 4663.82 | 3643.16 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.800823E+10 | 0.635663E+10 | 8897.18 | 6474.53 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.474255E+09 | 0.413872E+09 | 8423.44 | 30-JAN-11:22 | 5815.90 | 0.00 |
| February | 0.00 | 0.00 | 0.992342E+09 | 0.864561E+09 | 8444.34 | 08-FEB-22:22 | 5719.87 | 0.00 |
| March | 0.00 | 0.00 | 0.210405E+10 | 0.190615E+10 | 8446.06 | 24-MAR-10:12 | 5603.32 | 0.00 |
| April | 0.00 | 0.00 | 0.352830E+10 | 0.313099E+10 | 8632.60 | 30-APR-08:52 | 4934.23 | 0.00 |
| May | 0.00 | 0.00 | 0.567269E+10 | 0.497574E+10 | 8575.93 | 01-MAY-09:12 | 5063.40 | 0.00 |
| June | 0.00 | 0.00 | 0.658954E+10 | 0.539143E+10 | 7818.88 | 22-JUN-09:02 | 6307.50 | 0.00 |
| July | 0.00 | 0.00 | 0.771878E+10 | 0.617660E+10 | 4508.02 | 30-JUL-16:10 | 3506.17 | 0.00 |
| August | 0.00 | 0.00 | 0.785179E+10 | 0.620129E+10 | 4570.36 | 10-AUG-16:10 | 3646.71 | 0.00 |
| September | 0.00 | 0.00 | 0.631413E+10 | 0.495491E+10 | 8577.07 | 25-SEP-07:22 | 5112.27 | 0.00 |
| October | 0.00 | 0.00 | 0.483044E+10 | 0.396261E+10 | 8664.22 | 31-OCT-07:52 | 4841.32 | 0.00 |
| November | 0.00 | 0.00 | 0.287491E+10 | 0.242656E+10 | 8617.46 | 01-NOV-08:12 | 4998.01 | 0.00 |
| December | 0.00 | 0.00 | 0.113416E+10 | 0.951477E+09 | 8534.57 | 24-DEC-13:32 | 5394.32 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.500854E+11 | 0.413562E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.474255E+09 | 0.413872E+09 | 4508.02 | 3506.17 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.785179E+10 | 0.620129E+10 | 8664.22 | 6307.50 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.524457E+09 | 0.455621E+09 | 7528.43 | 30-JAN-11:22 | 5221.59 | 0.00 |
| February | 0.00 | 0.00 | 0.964403E+09 | 0.831891E+09 | 7537.23 | 08-FEB-22:22 | 5171.97 | 0.00 |
| March | 0.00 | 0.00 | 0.186336E+10 | 0.167306E+10 | 7570.51 | 29-MAR-09:42 | 4877.00 | 0.00 |
| April | 0.00 | 0.00 | 0.292408E+10 | 0.256386E+10 | 7739.92 | 30-APR-08:52 | 4344.37 | 0.00 |
| May | 0.00 | 0.00 | 0.458515E+10 | 0.396009E+10 | 7710.47 | 01-MAY-09:12 | 4388.39 | 0.00 |
| June | 0.00 | 0.00 | 0.535452E+10 | 0.429421E+10 | 7038.68 | 22-JUN-09:02 | 5515.06 | 0.00 |
| July | 0.00 | 0.00 | 0.627443E+10 | 0.490549E+10 | 3526.92 | 30-JUL-17:10 | 2601.99 | 0.00 |
| August | 0.00 | 0.00 | 0.635847E+10 | 0.489873E+10 | 3631.28 | 10-AUG-16:10 | 2856.90 | 0.00 |
| September | 0.00 | 0.00 | 0.516943E+10 | 0.396043E+10 | 7662.36 | 25-SEP-07:22 | 4559.73 | 0.00 |
| October | 0.00 | 0.00 | 0.401315E+10 | 0.323116E+10 | 7727.57 | 31-OCT-07:52 | 4355.10 | 0.00 |
| November | 0.00 | 0.00 | 0.249364E+10 | 0.208125E+10 | 7691.19 | 01-NOV-08:12 | 4468.76 | 0.00 |
| December | 0.00 | 0.00 | 0.112561E+10 | 0.937419E+09 | 7640.33 | 06-DEC-11:42 | 4726.72 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.416507E+11 | 0.337932E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.524457E+09 | 0.455621E+09 | 3526.92 | 2601.99 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.635847E+10 | 0.490549E+10 | 7739.92 | 5515.06 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.526067E+09 | 0.457099E+09 | 7510.37 | 30-JAN-11:22 | 5209.19 | 0.00 |
| February | 0.00 | 0.00 | 0.965582E+09 | 0.833037E+09 | 7519.41 | 08-FEB-22:22 | 5158.73 | 0.00 |
| March | 0.00 | 0.00 | 0.186398E+10 | 0.167369E+10 | 7551.79 | 29-MAR-09:42 | 4867.38 | 0.00 |
| April | 0.00 | 0.00 | 0.292762E+10 | 0.256718E+10 | 7720.72 | 30-APR-08:52 | 4336.52 | 0.00 |
| May | 0.00 | 0.00 | 0.458811E+10 | 0.396293E+10 | 7686.65 | 01-MAY-09:12 | 4396.67 | 0.00 |
| June | 0.00 | 0.00 | 0.535575E+10 | 0.429532E+10 | 7021.31 | 22-JUN-09:02 | 5503.05 | 0.00 |
| July | 0.00 | 0.00 | 0.627561E+10 | 0.490655E+10 | 3521.99 | 30-JUL-17:10 | 2597.59 | 0.00 |
| August | 0.00 | 0.00 | 0.635982E+10 | 0.489993E+10 | 3623.40 | 10-AUG-16:10 | 2849.93 | 0.00 |
| September | 0.00 | 0.00 | 0.517072E+10 | 0.396162E+10 | 7644.28 | 25-SEP-07:22 | 4548.73 | 0.00 |
| October | 0.00 | 0.00 | 0.401538E+10 | 0.323309E+10 | 7709.35 | 31-OCT-07:52 | 4344.79 | 0.00 |
| November | 0.00 | 0.00 | 0.249651E+10 | 0.208377E+10 | 7673.23 | 01-NOV-08:12 | 4459.40 | 0.00 |
| December | 0.00 | 0.00 | 0.112661E+10 | 0.938311E+09 | 7621.45 | 06-DEC-11:42 | 4717.75 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.416718E+11 | 0.338125E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.526067E+09 | 0.457099E+09 | 3521.99 | 2597.59 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.635982E+10 | 0.490655E+10 | 7720.72 | 5503.05 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.114882E+10 | 0.104069E+10 | 7710.33 | 30-JAN-12:02 | 5587.01 | 0.00 |
| February | 0.00 | 0.00 | 0.153059E+10 | 0.136649E+10 | 7720.67 | 07-FEB-09:42 | 5441.11 | 0.00 |
| March | 0.00 | 0.00 | 0.232335E+10 | 0.211737E+10 | 7793.24 | 24-MAR-10:12 | 5173.90 | 0.00 |
| April | 0.00 | 0.00 | 0.319864E+10 | 0.282766E+10 | 8011.20 | 30-APR-08:52 | 4390.17 | 0.00 |
| May | 0.00 | 0.00 | 0.458347E+10 | 0.396322E+10 | 7954.40 | 01-MAY-09:22 | 4497.35 | 0.00 |
| June | 0.00 | 0.00 | 0.523066E+10 | 0.418039E+10 | 7261.19 | 22-JUN-09:02 | 5694.30 | 0.00 |
| July | 0.00 | 0.00 | 0.625050E+10 | 0.488359E+10 | 3698.86 | 30-JUL-16:10 | 2864.15 | 0.00 |
| August | 0.00 | 0.00 | 0.651677E+10 | 0.505498E+10 | 3725.76 | 10-AUG-16:10 | 2973.41 | 0.00 |
| September | 0.00 | 0.00 | 0.564793E+10 | 0.441676E+10 | 7897.28 | 25-SEP-07:22 | 4767.30 | 0.00 |
| October | 0.00 | 0.00 | 0.480612E+10 | 0.398926E+10 | 7982.92 | 31-OCT-07:42 | 4513.02 | 0.00 |
| November | 0.00 | 0.00 | 0.338993E+10 | 0.292946E+10 | 7960.96 | 01-NOV-07:52 | 4586.79 | 0.00 |
| December | 0.00 | 0.00 | 0.186116E+10 | 0.162294E+10 | 7863.64 | 24-DEC-12:12 | 5028.28 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.464879E+11 | 0.383928E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.114882E+10 | 0.104069E+10 | 3698.86 | 2864.15 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.651677E+10 | 0.505498E+10 | 8011.20 | 5694.30 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HP COOLING COIL
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.115029E+10 | 0.104213E+10 | 7692.48 | 30-JAN-12:02 | 5574.54 | 0.00 |
| February | 0.00 | 0.00 | 0.153227E+10 | 0.136810E+10 | 7703.56 | 07-FEB-09:42 | 5431.42 | 0.00 |
| March | 0.00 | 0.00 | 0.232386E+10 | 0.211781E+10 | 7774.59 | 24-MAR-10:12 | 5164.64 | 0.00 |
| April | 0.00 | 0.00 | 0.320206E+10 | 0.283088E+10 | 7992.11 | 30-APR-08:52 | 4382.72 | 0.00 |
| May | 0.00 | 0.00 | 0.458646E+10 | 0.396605E+10 | 7934.89 | 01-MAY-09:22 | 4491.38 | 0.00 |
| June | 0.00 | 0.00 | 0.523191E+10 | 0.418152E+10 | 7243.97 | 22-JUN-09:02 | 5682.44 | 0.00 |
| July | 0.00 | 0.00 | 0.625170E+10 | 0.488467E+10 | 3694.68 | 30-JUL-16:10 | 2860.52 | 0.00 |
| August | 0.00 | 0.00 | 0.651811E+10 | 0.505620E+10 | 3717.94 | 10-AUG-16:10 | 2966.42 | 0.00 |
| September | 0.00 | 0.00 | 0.564919E+10 | 0.441791E+10 | 7879.41 | 25-SEP-07:22 | 4756.30 | 0.00 |
| October | 0.00 | 0.00 | 0.480817E+10 | 0.399107E+10 | 7964.81 | 31-OCT-07:42 | 4502.57 | 0.00 |
| November | 0.00 | 0.00 | 0.339230E+10 | 0.293154E+10 | 7943.00 | 01-NOV-07:52 | 4576.99 | 0.00 |
| December | 0.00 | 0.00 | 0.186254E+10 | 0.162426E+10 | 7845.18 | 24-DEC-12:12 | 5018.19 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.465088E+11 | 0.384121E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.115029E+10 | 0.104213E+10 | 3694.68 | 2860.52 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.651811E+10 | 0.505620E+10 | 7992.11 | 5682.44 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8733.20 | 16680.33 | 12-JAN-07:50 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 8491.29 | 16506.58 | 01-FEB-07:50 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7917.72 | 15724.77 | 01-MAR-07:37 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7138.08 | 14334.76 | 01-APR-06:50 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6374.07 | 12817.28 | 01-MAY-06:50 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 5830.20 | 11497.31 | 01-JUN-06:50 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 5655.74 | 10864.99 | 31-JUL-06:40 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 5902.01 | 11706.32 | 31-AUG-06:50 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 6495.45 | 13053.99 | 30-SEP-06:50 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 7278.35 | 14620.52 | 31-OCT-06:50 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 8038.96 | 15897.56 | 30-NOV-07:50 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 8571.47 | 16615.20 | 31-DEC-07:50 |
| Annual Sum or Average | 0.00 | 7195.20 | ||||
| Minimum of Months | 0.00 | 0.00 | 5655.74 | 10864.99 | ||
| Maximum of Months | 0.00 | 0.00 | 8733.20 | 16680.33 |
Report: FanReportMonthly
For: SPLIT GSW SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.106884E+09 | 0.57 | 447.69 | 01-JAN-14:32 | 0.91 |
| February | 0.119250E+09 | 0.62 | 447.69 | 01-FEB-11:22 | 0.91 |
| March | 0.165885E+09 | 0.73 | 447.69 | 01-MAR-07:32 | 0.91 |
| April | 0.222613E+09 | 0.89 | 447.69 | 01-APR-09:42 | 0.91 |
| May | 0.338967E+09 | 1.01 | 447.69 | 01-MAY-09:22 | 0.90 |
| June | 0.392578E+09 | 1.01 | 447.69 | 22-JUN-09:02 | 0.91 |
| July | 0.477638E+09 | 1.00 | 256.39 | 30-JUL-16:10 | 0.98 |
| August | 0.518830E+09 | 1.00 | 283.08 | 10-AUG-16:10 | 0.97 |
| September | 0.455137E+09 | 1.00 | 447.69 | 25-SEP-07:22 | 0.90 |
| October | 0.403865E+09 | 0.99 | 447.69 | 20-OCT-07:32 | 0.91 |
| November | 0.295967E+09 | 0.88 | 447.69 | 01-NOV-07:52 | 0.90 |
| December | 0.169438E+09 | 0.64 | 447.69 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.366705E+10 | 0.86 | |||
| Minimum of Months | 0.106884E+09 | 0.57 | 256.39 | 0.90 | |
| Maximum of Months | 0.518830E+09 | 1.01 | 447.69 | 0.98 |
Report: FanReportMonthly
For: G SW APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: G SW APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.73 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT GNW SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 67257548.30 | 0.49 | 433.76 | 02-JAN-22:52 | 0.91 |
| February | 85186129.69 | 0.56 | 433.76 | 01-FEB-12:32 | 0.91 |
| March | 0.137882E+09 | 0.70 | 433.76 | 01-MAR-07:32 | 0.91 |
| April | 0.205946E+09 | 0.89 | 433.76 | 01-APR-09:42 | 0.91 |
| May | 0.338957E+09 | 1.01 | 433.76 | 01-MAY-09:12 | 0.90 |
| June | 0.400097E+09 | 1.01 | 433.76 | 22-JUN-09:02 | 0.91 |
| July | 0.479037E+09 | 1.00 | 252.68 | 21-JUL-16:30 | 0.98 |
| August | 0.508999E+09 | 1.00 | 277.78 | 10-AUG-16:10 | 0.97 |
| September | 0.426206E+09 | 1.00 | 433.76 | 25-SEP-07:22 | 0.90 |
| October | 0.356187E+09 | 0.99 | 433.76 | 20-OCT-08:12 | 0.91 |
| November | 0.241745E+09 | 0.88 | 433.76 | 01-NOV-08:12 | 0.90 |
| December | 0.124256E+09 | 0.59 | 433.76 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.337175E+10 | 0.84 | |||
| Minimum of Months | 67257548.30 | 0.49 | 252.68 | 0.90 | |
| Maximum of Months | 0.508999E+09 | 1.01 | 433.76 | 0.98 |
Report: FanReportMonthly
For: G NW APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: G NW APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT OFFICE SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.132632E+10 | 0.92 | 513.70 | 01-JAN-00:10 | 0.91 |
| February | 0.119707E+10 | 0.92 | 513.70 | 01-FEB-00:10 | 0.91 |
| March | 0.132156E+10 | 0.92 | 513.70 | 01-MAR-00:10 | 0.91 |
| April | 0.128911E+10 | 0.91 | 513.70 | 01-APR-00:10 | 0.90 |
| May | 0.133984E+10 | 0.91 | 513.70 | 01-MAY-00:10 | 0.90 |
| June | 0.130087E+10 | 0.91 | 513.70 | 01-JUN-00:20 | 0.91 |
| July | 0.135513E+10 | 0.90 | 513.70 | 01-JUL-00:10 | 0.90 |
| August | 0.135586E+10 | 0.90 | 513.70 | 01-AUG-00:10 | 0.90 |
| September | 0.131040E+10 | 0.90 | 513.70 | 01-SEP-00:10 | 0.90 |
| October | 0.134803E+10 | 0.91 | 513.70 | 01-OCT-00:10 | 0.90 |
| November | 0.129796E+10 | 0.91 | 513.70 | 01-NOV-00:10 | 0.91 |
| December | 0.133127E+10 | 0.91 | 513.70 | 01-DEC-00:10 | 0.91 |
| Annual Sum or Average | 0.157734E+11 | 0.91 | |||
| Minimum of Months | 0.119707E+10 | 0.90 | 513.70 | 0.90 | |
| Maximum of Months | 0.135586E+10 | 0.92 | 513.70 | 0.91 |
Report: FanReportMonthly
For: SPLIT GNE SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 67362014.89 | 0.49 | 414.99 | 02-JAN-22:52 | 0.91 |
| February | 84339784.51 | 0.56 | 414.99 | 01-FEB-12:32 | 0.91 |
| March | 0.135338E+09 | 0.71 | 414.99 | 01-MAR-07:32 | 0.91 |
| April | 0.206979E+09 | 0.89 | 414.99 | 01-APR-09:42 | 0.91 |
| May | 0.340441E+09 | 1.00 | 414.99 | 01-MAY-09:12 | 0.90 |
| June | 0.398527E+09 | 1.01 | 414.99 | 22-JUN-09:02 | 0.91 |
| July | 0.477082E+09 | 1.00 | 238.49 | 30-JUL-17:10 | 0.97 |
| August | 0.507049E+09 | 1.00 | 260.80 | 10-AUG-16:10 | 0.97 |
| September | 0.424537E+09 | 1.00 | 414.99 | 25-SEP-07:22 | 0.90 |
| October | 0.355683E+09 | 0.99 | 414.99 | 20-OCT-08:12 | 0.91 |
| November | 0.240402E+09 | 0.88 | 414.99 | 01-NOV-08:12 | 0.90 |
| December | 0.122550E+09 | 0.59 | 414.99 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.336029E+10 | 0.84 | |||
| Minimum of Months | 67362014.89 | 0.49 | 238.49 | 0.90 | |
| Maximum of Months | 0.507049E+09 | 1.01 | 414.99 | 0.97 |
Report: FanReportMonthly
For: G NE APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: G NE APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT GN1 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 69564756.81 | 0.49 | 356.58 | 01-JAN-22:52 | 0.91 |
| February | 82674976.92 | 0.56 | 356.58 | 01-FEB-12:32 | 0.91 |
| March | 0.123978E+09 | 0.70 | 356.58 | 01-MAR-07:32 | 0.91 |
| April | 0.176234E+09 | 0.88 | 356.58 | 01-APR-09:42 | 0.91 |
| May | 0.277155E+09 | 1.01 | 356.58 | 01-MAY-09:12 | 0.90 |
| June | 0.324045E+09 | 1.01 | 356.58 | 22-JUN-09:02 | 0.91 |
| July | 0.384875E+09 | 1.00 | 191.82 | 19-JUL-17:00 | 0.98 |
| August | 0.404619E+09 | 1.00 | 204.22 | 10-AUG-16:10 | 0.98 |
| September | 0.341479E+09 | 1.00 | 356.58 | 25-SEP-07:22 | 0.90 |
| October | 0.288413E+09 | 0.99 | 356.58 | 20-OCT-08:12 | 0.91 |
| November | 0.201451E+09 | 0.88 | 356.58 | 01-NOV-08:12 | 0.90 |
| December | 0.113855E+09 | 0.59 | 356.58 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.278834E+10 | 0.84 | |||
| Minimum of Months | 69564756.81 | 0.49 | 191.82 | 0.90 | |
| Maximum of Months | 0.404619E+09 | 1.01 | 356.58 | 0.98 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT GN2 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 69655283.59 | 0.49 | 356.22 | 01-JAN-22:52 | 0.91 |
| February | 82723145.51 | 0.56 | 356.22 | 01-FEB-12:32 | 0.91 |
| March | 0.123953E+09 | 0.70 | 356.22 | 01-MAR-07:32 | 0.91 |
| April | 0.176368E+09 | 0.88 | 356.22 | 01-APR-09:42 | 0.91 |
| May | 0.277276E+09 | 1.01 | 356.22 | 01-MAY-09:12 | 0.90 |
| June | 0.324045E+09 | 1.01 | 356.22 | 22-JUN-09:02 | 0.91 |
| July | 0.384869E+09 | 1.00 | 191.56 | 19-JUL-17:00 | 0.98 |
| August | 0.404621E+09 | 1.00 | 204.02 | 10-AUG-16:10 | 0.98 |
| September | 0.341479E+09 | 1.00 | 356.22 | 25-SEP-07:22 | 0.90 |
| October | 0.288460E+09 | 0.99 | 356.22 | 20-OCT-08:12 | 0.91 |
| November | 0.201517E+09 | 0.88 | 356.22 | 01-NOV-08:12 | 0.90 |
| December | 0.113889E+09 | 0.59 | 356.22 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.278886E+10 | 0.84 | |||
| Minimum of Months | 69655283.59 | 0.49 | 191.56 | 0.90 | |
| Maximum of Months | 0.404621E+09 | 1.01 | 356.22 | 0.98 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT GS1 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.109943E+09 | 0.56 | 371.86 | 01-JAN-14:32 | 0.91 |
| February | 0.116920E+09 | 0.62 | 371.86 | 01-FEB-11:22 | 0.91 |
| March | 0.152726E+09 | 0.74 | 371.86 | 01-MAR-07:32 | 0.91 |
| April | 0.193629E+09 | 0.89 | 371.86 | 01-APR-09:42 | 0.91 |
| May | 0.278041E+09 | 1.01 | 371.86 | 01-MAY-09:22 | 0.90 |
| June | 0.317250E+09 | 1.01 | 371.86 | 22-JUN-09:02 | 0.91 |
| July | 0.384241E+09 | 1.01 | 195.27 | 30-JUL-17:10 | 0.98 |
| August | 0.415242E+09 | 1.00 | 209.55 | 10-AUG-16:10 | 0.98 |
| September | 0.371343E+09 | 1.00 | 371.86 | 25-SEP-07:22 | 0.90 |
| October | 0.337028E+09 | 0.99 | 371.86 | 20-OCT-07:32 | 0.91 |
| November | 0.256155E+09 | 0.88 | 371.86 | 01-NOV-07:52 | 0.90 |
| December | 0.159216E+09 | 0.63 | 371.86 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.309173E+10 | 0.86 | |||
| Minimum of Months | 0.109943E+09 | 0.56 | 195.27 | 0.90 | |
| Maximum of Months | 0.415242E+09 | 1.01 | 371.86 | 0.98 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.73 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT GS2 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.115354E+09 | 0.56 | 374.95 | 01-JAN-14:32 | 0.91 |
| February | 0.123196E+09 | 0.62 | 374.95 | 01-FEB-11:22 | 0.91 |
| March | 0.162129E+09 | 0.74 | 374.95 | 01-MAR-07:32 | 0.91 |
| April | 0.208938E+09 | 0.89 | 374.95 | 01-APR-09:42 | 0.91 |
| May | 0.300226E+09 | 1.00 | 374.95 | 01-MAY-09:22 | 0.90 |
| June | 0.339588E+09 | 1.01 | 374.95 | 22-JUN-09:02 | 0.91 |
| July | 0.409222E+09 | 1.00 | 207.78 | 30-JUL-17:10 | 0.98 |
| August | 0.439391E+09 | 1.00 | 215.28 | 10-AUG-16:10 | 0.98 |
| September | 0.394711E+09 | 1.00 | 374.95 | 25-SEP-07:22 | 0.90 |
| October | 0.360129E+09 | 0.98 | 374.95 | 20-OCT-07:32 | 0.91 |
| November | 0.274168E+09 | 0.88 | 374.95 | 01-NOV-07:52 | 0.90 |
| December | 0.168381E+09 | 0.63 | 374.95 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.329543E+10 | 0.86 | |||
| Minimum of Months | 0.115354E+09 | 0.56 | 207.78 | 0.90 | |
| Maximum of Months | 0.439391E+09 | 1.01 | 374.95 | 0.98 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.73 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT MSW SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.195188E+09 | 0.57 | 935.95 | 01-JAN-14:32 | 0.91 |
| February | 0.246015E+09 | 0.63 | 935.95 | 01-FEB-11:22 | 0.91 |
| March | 0.372093E+09 | 0.74 | 935.95 | 01-MAR-07:32 | 0.91 |
| April | 0.498845E+09 | 0.89 | 935.95 | 01-APR-09:42 | 0.91 |
| May | 0.713359E+09 | 1.01 | 935.95 | 01-MAY-09:22 | 0.90 |
| June | 0.800433E+09 | 1.01 | 935.95 | 22-JUN-09:02 | 0.91 |
| July | 0.941311E+09 | 1.01 | 535.00 | 30-JUL-16:10 | 0.98 |
| August | 0.979585E+09 | 1.01 | 573.98 | 10-AUG-16:10 | 0.97 |
| September | 0.840896E+09 | 1.01 | 935.95 | 25-SEP-07:22 | 0.90 |
| October | 0.719087E+09 | 0.99 | 935.95 | 20-OCT-07:32 | 0.91 |
| November | 0.511737E+09 | 0.89 | 935.95 | 01-NOV-07:52 | 0.90 |
| December | 0.290931E+09 | 0.64 | 935.95 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.710948E+10 | 0.87 | |||
| Minimum of Months | 0.195188E+09 | 0.57 | 535.00 | 0.90 | |
| Maximum of Months | 0.979585E+09 | 1.01 | 935.95 | 0.98 |
Report: FanReportMonthly
For: M SW APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.71 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.71 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.72 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.71 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: M SW APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.72 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.72 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.73 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.72 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: SPLIT MNW SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.110045E+09 | 0.46 | 905.31 | 03-JAN-18:52 | 0.91 |
| February | 0.172291E+09 | 0.56 | 905.31 | 01-FEB-12:32 | 0.91 |
| March | 0.312278E+09 | 0.71 | 905.31 | 01-MAR-07:32 | 0.91 |
| April | 0.462727E+09 | 0.89 | 905.31 | 01-APR-09:42 | 0.91 |
| May | 0.711461E+09 | 1.00 | 905.31 | 01-MAY-09:12 | 0.90 |
| June | 0.813893E+09 | 1.01 | 905.31 | 22-JUN-09:02 | 0.91 |
| July | 0.941802E+09 | 1.01 | 522.29 | 21-JUL-16:30 | 0.98 |
| August | 0.956815E+09 | 1.00 | 561.84 | 10-AUG-16:10 | 0.97 |
| September | 0.777887E+09 | 1.01 | 905.31 | 25-SEP-07:22 | 0.90 |
| October | 0.616275E+09 | 0.99 | 905.31 | 20-OCT-08:12 | 0.91 |
| November | 0.396475E+09 | 0.88 | 905.31 | 01-NOV-08:12 | 0.90 |
| December | 0.196538E+09 | 0.58 | 905.31 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.646849E+10 | 0.84 | |||
| Minimum of Months | 0.110045E+09 | 0.46 | 522.29 | 0.90 | |
| Maximum of Months | 0.956815E+09 | 1.01 | 905.31 | 0.98 |
Report: FanReportMonthly
For: M NW APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.71 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.71 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.72 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.71 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: M NW APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.72 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.72 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.72 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.72 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: SPLIT MSE SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.194835E+09 | 0.56 | 890.18 | 01-JAN-14:32 | 0.91 |
| February | 0.243298E+09 | 0.63 | 890.18 | 01-FEB-11:22 | 0.91 |
| March | 0.365766E+09 | 0.74 | 890.18 | 01-MAR-07:32 | 0.91 |
| April | 0.500368E+09 | 0.89 | 890.18 | 01-APR-09:42 | 0.91 |
| May | 0.715929E+09 | 1.00 | 890.18 | 01-MAY-09:22 | 0.90 |
| June | 0.796853E+09 | 1.01 | 890.18 | 22-JUN-09:02 | 0.91 |
| July | 0.936925E+09 | 1.00 | 509.37 | 30-JUL-16:10 | 0.98 |
| August | 0.975397E+09 | 1.00 | 530.77 | 10-AUG-16:10 | 0.97 |
| September | 0.837150E+09 | 1.00 | 890.18 | 25-SEP-07:22 | 0.90 |
| October | 0.717677E+09 | 0.99 | 890.18 | 20-OCT-07:32 | 0.91 |
| November | 0.508535E+09 | 0.89 | 890.18 | 01-NOV-07:52 | 0.90 |
| December | 0.286728E+09 | 0.64 | 890.18 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.707946E+10 | 0.87 | |||
| Minimum of Months | 0.194835E+09 | 0.56 | 509.37 | 0.90 | |
| Maximum of Months | 0.975397E+09 | 1.01 | 890.18 | 0.98 |
Report: FanReportMonthly
For: M SE APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.71 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.71 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.72 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.71 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: M SE APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.72 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.72 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.73 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.72 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: SPLIT MNE SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.110154E+09 | 0.46 | 859.69 | 03-JAN-18:52 | 0.91 |
| February | 0.170134E+09 | 0.56 | 859.69 | 01-FEB-12:32 | 0.91 |
| March | 0.306477E+09 | 0.72 | 859.69 | 01-MAR-07:32 | 0.91 |
| April | 0.464522E+09 | 0.89 | 859.69 | 01-APR-09:42 | 0.91 |
| May | 0.714008E+09 | 1.00 | 859.69 | 01-MAY-09:12 | 0.90 |
| June | 0.810102E+09 | 1.01 | 859.69 | 22-JUN-09:02 | 0.91 |
| July | 0.937298E+09 | 1.00 | 490.10 | 30-JUL-16:10 | 0.98 |
| August | 0.952794E+09 | 1.00 | 518.81 | 10-AUG-16:10 | 0.97 |
| September | 0.774822E+09 | 1.01 | 859.69 | 25-SEP-07:22 | 0.90 |
| October | 0.615962E+09 | 0.99 | 859.69 | 20-OCT-08:12 | 0.91 |
| November | 0.394025E+09 | 0.88 | 859.69 | 01-NOV-08:12 | 0.90 |
| December | 0.192767E+09 | 0.57 | 859.69 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.644306E+10 | 0.84 | |||
| Minimum of Months | 0.110154E+09 | 0.46 | 490.10 | 0.90 | |
| Maximum of Months | 0.952794E+09 | 1.01 | 859.69 | 0.98 |
Report: FanReportMonthly
For: M NE APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.71 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.71 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.72 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.71 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: M NE APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.72 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.72 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.72 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.72 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: SPLIT MN1 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.126332E+09 | 0.47 | 736.21 | 01-JAN-22:52 | 0.91 |
| February | 0.166997E+09 | 0.55 | 736.21 | 01-FEB-12:32 | 0.91 |
| March | 0.270476E+09 | 0.71 | 736.21 | 01-MAR-07:32 | 0.91 |
| April | 0.378639E+09 | 0.89 | 736.21 | 01-APR-09:42 | 0.91 |
| May | 0.559948E+09 | 1.01 | 736.21 | 01-MAY-09:12 | 0.90 |
| June | 0.638167E+09 | 1.01 | 736.21 | 22-JUN-09:02 | 0.91 |
| July | 0.736776E+09 | 1.01 | 378.02 | 19-JUL-16:40 | 0.98 |
| August | 0.746265E+09 | 1.01 | 397.12 | 10-AUG-16:10 | 0.98 |
| September | 0.616051E+09 | 1.01 | 736.21 | 25-SEP-07:22 | 0.90 |
| October | 0.500105E+09 | 0.99 | 736.21 | 20-OCT-08:12 | 0.91 |
| November | 0.338330E+09 | 0.87 | 736.21 | 01-NOV-08:12 | 0.90 |
| December | 0.192860E+09 | 0.57 | 736.21 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.527094E+10 | 0.84 | |||
| Minimum of Months | 0.126332E+09 | 0.47 | 378.02 | 0.90 | |
| Maximum of Months | 0.746265E+09 | 1.01 | 736.21 | 0.98 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.71 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.71 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.72 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.71 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.72 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.72 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.72 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.72 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: SPLIT MN2 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.126539E+09 | 0.47 | 735.39 | 01-JAN-22:52 | 0.91 |
| February | 0.167229E+09 | 0.55 | 735.39 | 01-FEB-12:32 | 0.91 |
| March | 0.270468E+09 | 0.71 | 735.39 | 01-MAR-07:32 | 0.91 |
| April | 0.378936E+09 | 0.89 | 735.39 | 01-APR-09:42 | 0.91 |
| May | 0.560177E+09 | 1.01 | 735.39 | 01-MAY-09:12 | 0.90 |
| June | 0.638176E+09 | 1.01 | 735.39 | 22-JUN-09:02 | 0.91 |
| July | 0.736772E+09 | 1.01 | 377.49 | 19-JUL-16:40 | 0.98 |
| August | 0.746280E+09 | 1.01 | 396.67 | 10-AUG-16:10 | 0.98 |
| September | 0.616075E+09 | 1.01 | 735.39 | 25-SEP-07:22 | 0.90 |
| October | 0.500238E+09 | 0.99 | 735.39 | 20-OCT-08:12 | 0.91 |
| November | 0.338559E+09 | 0.87 | 735.39 | 01-NOV-08:12 | 0.90 |
| December | 0.192971E+09 | 0.57 | 735.39 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.527242E+10 | 0.84 | |||
| Minimum of Months | 0.126539E+09 | 0.47 | 377.49 | 0.90 | |
| Maximum of Months | 0.746280E+09 | 1.01 | 735.39 | 0.98 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.71 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.71 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.72 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.71 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.72 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.72 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.72 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.72 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: SPLIT MS1 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.211681E+09 | 0.58 | 770.14 | 01-JAN-14:32 | 0.91 |
| February | 0.240498E+09 | 0.63 | 770.14 | 01-FEB-11:22 | 0.91 |
| March | 0.329958E+09 | 0.74 | 770.14 | 01-MAR-07:32 | 0.91 |
| April | 0.414393E+09 | 0.89 | 770.14 | 01-APR-09:42 | 0.91 |
| May | 0.561725E+09 | 1.01 | 770.14 | 01-MAY-09:22 | 0.90 |
| June | 0.624482E+09 | 1.02 | 770.14 | 22-JUN-09:02 | 0.91 |
| July | 0.736011E+09 | 1.01 | 387.28 | 30-JUL-16:10 | 0.99 |
| August | 0.768829E+09 | 1.01 | 408.82 | 10-AUG-16:10 | 0.98 |
| September | 0.678861E+09 | 1.01 | 770.14 | 25-SEP-07:22 | 0.90 |
| October | 0.602289E+09 | 0.99 | 770.14 | 20-OCT-07:32 | 0.91 |
| November | 0.452677E+09 | 0.89 | 770.14 | 01-NOV-07:52 | 0.90 |
| December | 0.286400E+09 | 0.64 | 770.14 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.590780E+10 | 0.87 | |||
| Minimum of Months | 0.211681E+09 | 0.58 | 387.28 | 0.90 | |
| Maximum of Months | 0.768829E+09 | 1.02 | 770.14 | 0.99 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.71 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.71 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.72 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.71 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.72 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.72 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.73 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.72 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: SPLIT MS2 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.211681E+09 | 0.58 | 769.31 | 01-JAN-14:32 | 0.91 |
| February | 0.240403E+09 | 0.63 | 769.31 | 01-FEB-11:22 | 0.91 |
| March | 0.329701E+09 | 0.74 | 769.31 | 01-MAR-07:32 | 0.91 |
| April | 0.414364E+09 | 0.89 | 769.31 | 01-APR-09:42 | 0.91 |
| May | 0.561560E+09 | 1.01 | 769.31 | 01-MAY-09:22 | 0.90 |
| June | 0.624090E+09 | 1.02 | 769.31 | 22-JUN-09:02 | 0.91 |
| July | 0.735552E+09 | 1.01 | 386.93 | 30-JUL-16:10 | 0.99 |
| August | 0.768370E+09 | 1.01 | 408.14 | 10-AUG-16:10 | 0.98 |
| September | 0.678447E+09 | 1.01 | 769.31 | 25-SEP-07:22 | 0.90 |
| October | 0.601982E+09 | 0.99 | 769.31 | 20-OCT-07:32 | 0.91 |
| November | 0.452482E+09 | 0.89 | 769.31 | 01-NOV-07:52 | 0.90 |
| December | 0.286207E+09 | 0.64 | 769.31 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.590484E+10 | 0.87 | |||
| Minimum of Months | 0.211681E+09 | 0.58 | 386.93 | 0.90 | |
| Maximum of Months | 0.768370E+09 | 1.02 | 769.31 | 0.99 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.71 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.71 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.72 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.71 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.124124E+09 | 0.73 | 46.34 | 01-JAN-00:10 | 0.73 |
| February | 0.112112E+09 | 0.73 | 46.34 | 01-FEB-00:10 | 0.73 |
| March | 0.124124E+09 | 0.73 | 46.34 | 01-MAR-00:10 | 0.72 |
| April | 0.120120E+09 | 0.72 | 46.34 | 01-APR-00:10 | 0.72 |
| May | 0.124124E+09 | 0.72 | 46.34 | 01-MAY-00:10 | 0.72 |
| June | 0.120120E+09 | 0.72 | 46.34 | 01-JUN-00:10 | 0.72 |
| July | 0.124124E+09 | 0.72 | 46.34 | 01-JUL-00:10 | 0.72 |
| August | 0.124124E+09 | 0.72 | 46.34 | 01-AUG-00:10 | 0.72 |
| September | 0.120120E+09 | 0.72 | 46.34 | 01-SEP-00:10 | 0.72 |
| October | 0.124124E+09 | 0.72 | 46.34 | 01-OCT-00:10 | 0.72 |
| November | 0.120120E+09 | 0.72 | 46.34 | 01-NOV-00:10 | 0.72 |
| December | 0.124124E+09 | 0.73 | 46.34 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.146145E+10 | 0.72 | |||
| Minimum of Months | 0.112112E+09 | 0.72 | 46.34 | 0.72 | |
| Maximum of Months | 0.124124E+09 | 0.73 | 46.34 | 0.73 |
Report: FanReportMonthly
For: SPLIT TSW SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 69243736.45 | 0.35 | 512.05 | 01-JAN-14:32 | 0.91 |
| February | 0.104179E+09 | 0.50 | 512.05 | 01-FEB-11:22 | 0.91 |
| March | 0.178629E+09 | 0.70 | 512.05 | 01-MAR-07:32 | 0.91 |
| April | 0.261487E+09 | 0.89 | 512.05 | 01-APR-09:42 | 0.91 |
| May | 0.394814E+09 | 1.00 | 512.05 | 01-MAY-09:22 | 0.90 |
| June | 0.447004E+09 | 1.01 | 512.05 | 22-JUN-09:02 | 0.91 |
| July | 0.532767E+09 | 1.01 | 332.67 | 30-JUL-16:10 | 0.96 |
| August | 0.552259E+09 | 1.00 | 355.80 | 10-AUG-16:10 | 0.96 |
| September | 0.462877E+09 | 1.01 | 512.05 | 25-SEP-07:22 | 0.90 |
| October | 0.382969E+09 | 0.99 | 512.05 | 20-OCT-07:32 | 0.91 |
| November | 0.256480E+09 | 0.88 | 512.05 | 01-NOV-07:52 | 0.90 |
| December | 0.124310E+09 | 0.54 | 512.05 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.376702E+10 | 0.82 | |||
| Minimum of Months | 69243736.45 | 0.35 | 332.67 | 0.90 | |
| Maximum of Months | 0.552259E+09 | 1.01 | 512.05 | 0.96 |
Report: FanReportMonthly
For: T SW APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: T SW APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT TNW SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 31690026.12 | 0.23 | 499.43 | 03-JAN-18:52 | 0.91 |
| February | 68085600.64 | 0.42 | 499.43 | 01-FEB-12:32 | 0.91 |
| March | 0.147966E+09 | 0.67 | 499.43 | 01-MAR-07:32 | 0.91 |
| April | 0.242643E+09 | 0.88 | 499.43 | 01-APR-09:42 | 0.91 |
| May | 0.394092E+09 | 1.00 | 499.43 | 01-MAY-09:12 | 0.90 |
| June | 0.454223E+09 | 1.01 | 499.43 | 22-JUN-09:02 | 0.91 |
| July | 0.533147E+09 | 1.00 | 326.66 | 21-JUL-16:12 | 0.97 |
| August | 0.540430E+09 | 1.00 | 348.04 | 10-AUG-16:10 | 0.96 |
| September | 0.430260E+09 | 1.01 | 499.43 | 25-SEP-07:22 | 0.90 |
| October | 0.329619E+09 | 0.99 | 499.43 | 20-OCT-08:12 | 0.91 |
| November | 0.196970E+09 | 0.86 | 499.43 | 01-NOV-08:12 | 0.90 |
| December | 77594639.09 | 0.45 | 499.43 | 01-DEC-21:12 | 0.91 |
| Annual Sum or Average | 0.344672E+10 | 0.80 | |||
| Minimum of Months | 31690026.12 | 0.23 | 326.66 | 0.90 | |
| Maximum of Months | 0.540430E+09 | 1.01 | 499.43 | 0.97 |
Report: FanReportMonthly
For: T NW APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: T NW APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT TSE SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 68690127.87 | 0.35 | 479.46 | 01-JAN-14:32 | 0.91 |
| February | 0.102471E+09 | 0.49 | 479.46 | 01-FEB-11:22 | 0.91 |
| March | 0.175064E+09 | 0.70 | 479.46 | 01-MAR-07:32 | 0.91 |
| April | 0.261990E+09 | 0.89 | 479.46 | 01-APR-09:42 | 0.91 |
| May | 0.395708E+09 | 1.00 | 479.46 | 01-MAY-09:22 | 0.90 |
| June | 0.444567E+09 | 1.01 | 479.46 | 22-JUN-09:02 | 0.91 |
| July | 0.529430E+09 | 1.00 | 312.94 | 30-JUL-16:10 | 0.96 |
| August | 0.548974E+09 | 1.00 | 325.84 | 16-AUG-12:00 | 0.96 |
| September | 0.460280E+09 | 1.00 | 479.46 | 25-SEP-07:22 | 0.90 |
| October | 0.381833E+09 | 0.99 | 479.46 | 20-OCT-07:32 | 0.91 |
| November | 0.254441E+09 | 0.89 | 479.46 | 01-NOV-07:52 | 0.90 |
| December | 0.122025E+09 | 0.54 | 479.46 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.374547E+10 | 0.82 | |||
| Minimum of Months | 68690127.87 | 0.35 | 312.94 | 0.90 | |
| Maximum of Months | 0.548974E+09 | 1.01 | 479.46 | 0.96 |
Report: FanReportMonthly
For: T SE APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: T SE APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT TNE SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 31156871.13 | 0.23 | 466.86 | 03-JAN-18:52 | 0.91 |
| February | 66562831.44 | 0.42 | 466.86 | 01-FEB-12:32 | 0.91 |
| March | 0.144575E+09 | 0.67 | 466.86 | 01-MAR-07:32 | 0.91 |
| April | 0.243284E+09 | 0.89 | 466.86 | 01-APR-09:42 | 0.91 |
| May | 0.394885E+09 | 1.00 | 466.86 | 01-MAY-09:12 | 0.90 |
| June | 0.451543E+09 | 1.01 | 466.86 | 22-JUN-09:02 | 0.91 |
| July | 0.529631E+09 | 1.00 | 308.07 | 21-JUL-14:30 | 0.96 |
| August | 0.537166E+09 | 1.00 | 317.32 | 10-AUG-16:10 | 0.96 |
| September | 0.428046E+09 | 1.01 | 466.86 | 25-SEP-07:22 | 0.90 |
| October | 0.329111E+09 | 0.99 | 466.86 | 20-OCT-08:12 | 0.91 |
| November | 0.195206E+09 | 0.87 | 466.86 | 01-NOV-08:12 | 0.90 |
| December | 75552937.92 | 0.46 | 466.86 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.342672E+10 | 0.80 | |||
| Minimum of Months | 31156871.13 | 0.23 | 308.07 | 0.90 | |
| Maximum of Months | 0.537166E+09 | 1.01 | 466.86 | 0.96 |
Report: FanReportMonthly
For: T NE APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: T NE APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT TN1 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 34237071.32 | 0.32 | 413.91 | 03-JAN-18:52 | 0.91 |
| February | 64031678.41 | 0.49 | 413.91 | 01-FEB-12:32 | 0.91 |
| March | 0.126832E+09 | 0.71 | 413.91 | 01-MAR-07:32 | 0.91 |
| April | 0.199996E+09 | 0.89 | 413.91 | 01-APR-09:42 | 0.91 |
| May | 0.316857E+09 | 1.01 | 413.91 | 01-MAY-09:12 | 0.90 |
| June | 0.364169E+09 | 1.01 | 413.91 | 22-JUN-09:02 | 0.91 |
| July | 0.427224E+09 | 1.01 | 236.45 | 21-JUL-16:12 | 0.98 |
| August | 0.431721E+09 | 1.01 | 251.92 | 10-AUG-16:10 | 0.97 |
| September | 0.347392E+09 | 1.01 | 413.91 | 25-SEP-07:22 | 0.90 |
| October | 0.270918E+09 | 0.99 | 413.91 | 20-OCT-08:12 | 0.91 |
| November | 0.167816E+09 | 0.87 | 413.91 | 01-NOV-08:12 | 0.90 |
| December | 74261564.63 | 0.54 | 413.91 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.282546E+10 | 0.82 | |||
| Minimum of Months | 34237071.32 | 0.32 | 236.45 | 0.90 | |
| Maximum of Months | 0.431721E+09 | 1.01 | 413.91 | 0.98 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT TN2 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 34329436.48 | 0.31 | 412.81 | 03-JAN-18:52 | 0.91 |
| February | 64083171.06 | 0.49 | 412.81 | 01-FEB-12:32 | 0.91 |
| March | 0.126830E+09 | 0.71 | 412.81 | 01-MAR-07:32 | 0.91 |
| April | 0.200167E+09 | 0.89 | 412.81 | 01-APR-09:42 | 0.91 |
| May | 0.316950E+09 | 1.01 | 412.81 | 01-MAY-09:12 | 0.90 |
| June | 0.364119E+09 | 1.01 | 412.81 | 22-JUN-09:02 | 0.91 |
| July | 0.427140E+09 | 1.01 | 235.96 | 21-JUL-16:12 | 0.98 |
| August | 0.431645E+09 | 1.00 | 251.29 | 10-AUG-16:10 | 0.97 |
| September | 0.347355E+09 | 1.01 | 412.81 | 25-SEP-07:22 | 0.90 |
| October | 0.270971E+09 | 0.99 | 412.81 | 20-OCT-08:12 | 0.91 |
| November | 0.167944E+09 | 0.87 | 412.81 | 01-NOV-08:12 | 0.90 |
| December | 74298661.97 | 0.54 | 412.81 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.282583E+10 | 0.82 | |||
| Minimum of Months | 34329436.48 | 0.31 | 235.96 | 0.90 | |
| Maximum of Months | 0.431645E+09 | 1.01 | 412.81 | 0.98 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT TS1 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 74651040.11 | 0.48 | 427.43 | 01-JAN-14:32 | 0.91 |
| February | 0.101055E+09 | 0.59 | 427.43 | 01-FEB-11:22 | 0.91 |
| March | 0.157693E+09 | 0.73 | 427.43 | 01-MAR-07:32 | 0.91 |
| April | 0.218832E+09 | 0.89 | 427.43 | 01-APR-09:42 | 0.91 |
| May | 0.317551E+09 | 1.01 | 427.43 | 01-MAY-09:22 | 0.90 |
| June | 0.356837E+09 | 1.02 | 427.43 | 22-JUN-09:02 | 0.91 |
| July | 0.426774E+09 | 1.01 | 247.49 | 30-JUL-16:10 | 0.97 |
| August | 0.443591E+09 | 1.01 | 259.65 | 10-AUG-16:10 | 0.97 |
| September | 0.380180E+09 | 1.01 | 427.43 | 25-SEP-07:22 | 0.90 |
| October | 0.324414E+09 | 0.99 | 427.43 | 20-OCT-07:32 | 0.91 |
| November | 0.227537E+09 | 0.89 | 427.43 | 01-NOV-07:52 | 0.90 |
| December | 0.122338E+09 | 0.62 | 427.43 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.315145E+10 | 0.85 | |||
| Minimum of Months | 74651040.11 | 0.48 | 247.49 | 0.90 | |
| Maximum of Months | 0.443591E+09 | 1.02 | 427.43 | 0.97 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: SPLIT TS2 SUPPLY FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 74714750.88 | 0.48 | 426.33 | 01-JAN-14:32 | 0.91 |
| February | 0.101121E+09 | 0.59 | 426.33 | 01-FEB-11:22 | 0.91 |
| March | 0.157668E+09 | 0.73 | 426.33 | 01-MAR-07:32 | 0.91 |
| April | 0.218985E+09 | 0.89 | 426.33 | 01-APR-09:42 | 0.91 |
| May | 0.317648E+09 | 1.01 | 426.33 | 01-MAY-09:22 | 0.90 |
| June | 0.356797E+09 | 1.01 | 426.33 | 22-JUN-09:02 | 0.91 |
| July | 0.426697E+09 | 1.01 | 247.12 | 30-JUL-16:10 | 0.97 |
| August | 0.443514E+09 | 1.01 | 259.02 | 10-AUG-16:10 | 0.97 |
| September | 0.380124E+09 | 1.01 | 426.33 | 25-SEP-07:22 | 0.90 |
| October | 0.324427E+09 | 0.99 | 426.33 | 20-OCT-07:32 | 0.91 |
| November | 0.227605E+09 | 0.89 | 426.33 | 01-NOV-07:52 | 0.90 |
| December | 0.122376E+09 | 0.62 | 426.33 | 01-DEC-09:42 | 0.91 |
| Annual Sum or Average | 0.315168E+10 | 0.85 | |||
| Minimum of Months | 74714750.88 | 0.48 | 247.12 | 0.90 | |
| Maximum of Months | 0.443514E+09 | 1.01 | 426.33 | 0.97 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV SUP FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.71 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.71 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.71 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV EXH FAN
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 62061755.14 | 0.73 | 23.17 | 01-JAN-00:10 | 0.73 |
| February | 56055778.84 | 0.73 | 23.17 | 01-FEB-00:10 | 0.73 |
| March | 62061755.14 | 0.73 | 23.17 | 01-MAR-00:10 | 0.72 |
| April | 60059763.04 | 0.72 | 23.17 | 01-APR-00:10 | 0.72 |
| May | 62061755.14 | 0.72 | 23.17 | 01-MAY-00:10 | 0.72 |
| June | 60059763.04 | 0.72 | 23.17 | 01-JUN-00:10 | 0.72 |
| July | 62061755.14 | 0.72 | 23.17 | 01-JUL-00:10 | 0.72 |
| August | 62061755.14 | 0.72 | 23.17 | 01-AUG-00:10 | 0.72 |
| September | 60059763.04 | 0.72 | 23.17 | 01-SEP-00:10 | 0.72 |
| October | 62061755.14 | 0.72 | 23.17 | 01-OCT-00:10 | 0.72 |
| November | 60059763.04 | 0.72 | 23.17 | 01-NOV-00:10 | 0.72 |
| December | 62061755.14 | 0.72 | 23.17 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.730727E+09 | 0.72 | |||
| Minimum of Months | 56055778.84 | 0.72 | 23.17 | 0.72 | |
| Maximum of Months | 62061755.14 | 0.73 | 23.17 | 0.73 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 38818862.27 | 11645658.68 | 14.49 | 01-JAN-00:10 | 4.35 | 4.35 | 56.42 | 0.11 |
| February | 35062198.18 | 10518659.46 | 14.49 | 01-FEB-00:10 | 4.35 | 4.35 | 56.45 | 0.11 |
| March | 38818862.27 | 11645658.68 | 14.49 | 01-MAR-00:10 | 4.35 | 4.35 | 56.61 | 0.11 |
| April | 37566640.91 | 11269992.27 | 14.49 | 01-APR-00:10 | 4.35 | 4.35 | 58.63 | 0.11 |
| May | 38818862.27 | 11645658.68 | 14.49 | 01-MAY-00:10 | 4.35 | 4.35 | 58.77 | 0.11 |
| June | 37566640.91 | 11269992.27 | 14.49 | 01-JUN-00:10 | 4.35 | 4.35 | 58.89 | 0.11 |
| July | 38818862.27 | 11645658.68 | 14.49 | 01-JUL-00:10 | 4.35 | 4.35 | 58.96 | 0.11 |
| August | 38818862.27 | 11645658.68 | 14.49 | 01-AUG-00:10 | 4.35 | 4.35 | 58.95 | 0.11 |
| September | 37566640.91 | 11269992.27 | 14.49 | 01-SEP-00:10 | 4.35 | 4.35 | 58.87 | 0.11 |
| October | 38818862.27 | 11645658.68 | 14.49 | 01-OCT-00:10 | 4.35 | 4.35 | 58.74 | 0.11 |
| November | 37566640.91 | 11269992.27 | 14.49 | 01-NOV-00:10 | 4.35 | 4.35 | 58.60 | 0.11 |
| December | 38818862.27 | 11645658.68 | 14.49 | 01-DEC-00:10 | 4.35 | 4.35 | 56.57 | 0.11 |
| Annual Sum or Average | 0.457061E+09 | 0.137118E+09 | ||||||
| Minimum of Months | 35062198.18 | 10518659.46 | 14.49 | 4.35 | 4.35 | 56.42 | 0.11 | |
| Maximum of Months | 38818862.27 | 11645658.68 | 14.49 | 4.35 | 4.35 | 58.96 | 0.11 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 56.42 | 59.95 | 8733.20 | 16680.33 | 12-JAN-07:50 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 56.45 | 59.95 | 8491.29 | 16506.58 | 01-FEB-07:50 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 56.61 | 59.95 | 7917.72 | 15724.77 | 01-MAR-07:37 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 58.63 | 59.95 | 7138.08 | 14334.76 | 01-APR-06:50 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 58.77 | 59.95 | 6374.07 | 12817.28 | 01-MAY-06:50 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 58.89 | 59.94 | 5830.20 | 11497.31 | 01-JUN-06:50 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 58.96 | 59.96 | 5655.74 | 10864.99 | 31-JUL-06:40 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 58.95 | 59.95 | 5902.01 | 11706.32 | 31-AUG-06:50 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 58.87 | 59.95 | 6495.45 | 13053.99 | 30-SEP-06:50 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 58.74 | 59.94 | 7278.35 | 14620.52 | 31-OCT-06:50 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 58.60 | 59.94 | 8038.96 | 15897.56 | 30-NOV-07:50 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 56.57 | 59.95 | 8571.47 | 16615.20 | 31-DEC-07:50 |
| Annual Sum or Average | 0.00 | 7195.20 | ||||||
| Minimum of Months | 0.00 | 0.00 | 56.42 | 59.94 | 5655.74 | 10864.99 | ||
| Maximum of Months | 0.00 | 0.00 | 58.96 | 59.96 | 8733.20 | 16680.33 |
Report: ZoneTemperatureOscillationReportMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M CORRIDOR
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.510428E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.575010E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.806256E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.110433E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.173627E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.204658E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.253100E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.275434E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.236734E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.204401E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.145775E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.815372E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.187487E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.510428E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.275434E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.321642E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.411559E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.671405E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.102264E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.173733E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.208674E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.253969E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.270489E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.222011E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.180540E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.119269E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.599124E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.173132E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.321642E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.270489E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.176600E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.166415E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.193093E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.198570E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.254395E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.276403E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.319650E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.347876E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.295226E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.270304E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.221177E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.189730E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.290944E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.166415E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.347876E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.323349E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.409072E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.661760E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.103196E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.175134E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.208620E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.253864E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.270445E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.221949E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.180939E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.119059E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.593159E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.173194E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.323349E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.270445E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.337807E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.405245E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.612509E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.888170E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.144364E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.171953E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.207844E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.219123E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.181072E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.148646E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.100981E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.557455E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.145410E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.337807E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.219123E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.338281E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.405523E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.612458E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.888939E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.144440E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.171971E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.207861E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.219144E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.181089E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.148684E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.101024E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.557676E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.145450E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.338281E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.219144E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.533342E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.572333E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.753452E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.975208E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.144766E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.168321E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.207456E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.224678E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.196624E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.173456E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.128212E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.778295E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.160478E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.533342E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.224678E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.559085E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.602449E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.798978E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.105070E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.156008E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.179776E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.220439E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.237223E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.208560E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.185005E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.137007E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.822248E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.170736E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.559085E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.237223E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.930878E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.118455E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.180439E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.246976E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.364917E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.417048E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.498863E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.520725E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.438103E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.364492E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.252386E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.139952E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.363544E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.930878E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.520725E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.525823E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.831439E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.151733E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.229352E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.364290E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.424395E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.499541E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.509329E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.406058E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.313002E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.195975E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.947963E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.332420E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.525823E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.509329E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.933240E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.117674E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.178206E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.248904E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.367822E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.416981E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.498701E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.520755E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.438013E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.365314E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.251914E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.138541E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.363615E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.933240E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.520755E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.528662E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.824787E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.149626E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.231335E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.367171E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.424236E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.499302E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.509379E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.406167E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.314153E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.195644E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.933992E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.332576E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.528662E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.509379E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.612863E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.817642E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.133391E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.190563E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.291500E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.338710E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.398245E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.404950E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.327340E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.258194E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.169819E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.944122E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.275018E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.612863E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.404950E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.613935E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.818871E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.133404E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.190735E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.291651E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.338752E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.398284E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.405000E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.327387E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.258291E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.169953E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.944773E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.275122E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.613935E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.405000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.102522E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.117531E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.162421E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.208334E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.292133E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.331190E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.397495E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.416545E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.359932E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.310294E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.226726E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.139876E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.306500E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.102522E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.416545E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.102539E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.117504E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.162326E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.208363E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.292116E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.331059E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.397343E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.416397E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.359793E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.310202E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.226673E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.139804E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.306412E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.102539E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.416397E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.329119E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.500904E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.864581E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.129235E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.201376E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.231978E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.280843E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.291986E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.240227E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.193628E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.126271E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.596548E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.192466E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.329119E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.291986E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.150975E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.328316E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.717633E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.120012E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.201116E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.235826E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.281178E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.286009E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.223620E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.166906E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.971681E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.373597E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176889E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.150975E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.286009E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.328167E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.495301E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.851970E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.130188E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.202832E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.231853E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.280478E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.291699E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.240045E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.193980E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.125902E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.588618E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.192338E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.328167E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.291699E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.149234E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.322758E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.705153E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.120993E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.202523E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.235599E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.280726E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.285707E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.223556E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.167451E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.968054E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.365749E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176765E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.149234E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.285707E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.164938E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.311893E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.621676E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.100002E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.163648E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.191513E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.228441E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.231702E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.182893E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.138813E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.836922E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.361332E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.146669E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.164938E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.231702E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.165423E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.312223E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.621826E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.100113E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.163733E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.191529E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.228446E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.231712E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.182914E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.138872E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.837760E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.361602E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.146720E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.165423E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.231712E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.358849E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.490947E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.771338E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.109336E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.163899E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.187561E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.228069E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.237789E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.199814E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.165947E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.113250E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.593418E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.162712E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.358849E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.237789E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.359234E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.491383E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.771407E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.109439E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.163986E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.187582E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.228078E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.237800E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.199827E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.165990E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.113309E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.593733E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.162759E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.359234E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.237800E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.106884E+09 | 0.160177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.119250E+09 | 0.177941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.165885E+09 | 0.242078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.222613E+09 | 0.322871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.338967E+09 | 0.486238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.392578E+09 | 0.571614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.477638E+09 | 0.694791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.518830E+09 | 0.757670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.455137E+09 | 0.672383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.403865E+09 | 0.595862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.295967E+09 | 0.438731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.169438E+09 | 0.254367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.366705E+10 | 0.537472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.106884E+09 | 0.160177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.518830E+09 | 0.757670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 67257548.30 | 0.100291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 85186129.69 | 0.126769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.137882E+09 | 0.201011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.205946E+09 | 0.298942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.338957E+09 | 0.487446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.400097E+09 | 0.584349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.479037E+09 | 0.698816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.508999E+09 | 0.745271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.426206E+09 | 0.630626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.356187E+09 | 0.525459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.241745E+09 | 0.357702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.124256E+09 | 0.185971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.337175E+10 | 0.494265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67257548.30 | 0.100291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.508999E+09 | 0.745271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.132632E+10 | 0.174224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.119707E+10 | 0.183920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.132156E+10 | 0.232944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.128911E+10 | 0.259702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.133984E+10 | 0.430139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.130087E+10 | 0.523208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.135513E+10 | 0.651633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.135586E+10 | 0.753560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.131040E+10 | 0.600444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.134803E+10 | 0.512483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.129796E+10 | 0.356445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.133127E+10 | 0.226070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.157734E+11 | 0.490477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.119707E+10 | 0.174224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.135586E+10 | 0.753560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 67362014.89 | 0.101006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 84339784.51 | 0.126227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.135338E+09 | 0.198375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.206979E+09 | 0.302148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.340441E+09 | 0.492537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.398527E+09 | 0.585762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.477082E+09 | 0.700669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.507049E+09 | 0.747553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.424537E+09 | 0.632266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.355683E+09 | 0.528161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.240402E+09 | 0.357948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.122550E+09 | 0.184486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.336029E+10 | 0.495714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67362014.89 | 0.101006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.507049E+09 | 0.747553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 69564756.81 | 0.106192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 82674976.92 | 0.126090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.123978E+09 | 0.185181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.176234E+09 | 0.261937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.277155E+09 | 0.408041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.324045E+09 | 0.484963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.384875E+09 | 0.575639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.404619E+09 | 0.607187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.341479E+09 | 0.517883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.288413E+09 | 0.435852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.201451E+09 | 0.305152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.113855E+09 | 0.174645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.278834E+10 | 0.418876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 69564756.81 | 0.106192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.404619E+09 | 0.607187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 69655283.59 | 0.106347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 82723145.51 | 0.126182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.123953E+09 | 0.185170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.176368E+09 | 0.262174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.277276E+09 | 0.408278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.324045E+09 | 0.485035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.384869E+09 | 0.575720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.404621E+09 | 0.607286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.341479E+09 | 0.517962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.288460E+09 | 0.435991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.201517E+09 | 0.305299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.113889E+09 | 0.174722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.278886E+10 | 0.419016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 69655283.59 | 0.106347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.404621E+09 | 0.607286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.109943E+09 | 0.168812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.116920E+09 | 0.178867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.152726E+09 | 0.228433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.193629E+09 | 0.287591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.278041E+09 | 0.408289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.317250E+09 | 0.473322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.384241E+09 | 0.572960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.415242E+09 | 0.621294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.371343E+09 | 0.562054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.337028E+09 | 0.509280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.256155E+09 | 0.388880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.159216E+09 | 0.245164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309173E+10 | 0.464495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.109943E+09 | 0.168812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.415242E+09 | 0.621294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.115354E+09 | 0.176926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.123196E+09 | 0.188317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.162129E+09 | 0.242425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.208938E+09 | 0.310448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.300226E+09 | 0.441116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.339588E+09 | 0.506617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.409222E+09 | 0.610091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.439391E+09 | 0.657349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.394711E+09 | 0.597439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.360129E+09 | 0.544479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.274168E+09 | 0.416421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.168381E+09 | 0.259160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.329543E+10 | 0.495079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.115354E+09 | 0.176926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.439391E+09 | 0.657349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.195188E+09 | 0.292388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.246015E+09 | 0.366421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.372093E+09 | 0.542476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.498845E+09 | 0.723022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.713359E+09 | 0.102111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.800433E+09 | 0.116282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.941311E+09 | 0.136532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.979585E+09 | 0.142513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.840896E+09 | 0.123711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.719087E+09 | 0.105473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.511737E+09 | 0.754373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.290931E+09 | 0.435399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.710948E+10 | 0.103803E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.195188E+09 | 0.292388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.979585E+09 | 0.142513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.110045E+09 | 0.164251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.172291E+09 | 0.255782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.312278E+09 | 0.454750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.462727E+09 | 0.671396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.711461E+09 | 0.102134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.813893E+09 | 0.118639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.941802E+09 | 0.137033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.956815E+09 | 0.139617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.777887E+09 | 0.114700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.616275E+09 | 0.904689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.396475E+09 | 0.583716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.196538E+09 | 0.293547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.646849E+10 | 0.944937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.110045E+09 | 0.164251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.956815E+09 | 0.139617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.194835E+09 | 0.293884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.243298E+09 | 0.364972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.365766E+09 | 0.536803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.500368E+09 | 0.730345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.715929E+09 | 0.103202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.796853E+09 | 0.116606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.936925E+09 | 0.136938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.975397E+09 | 0.143008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.837150E+09 | 0.124083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.717677E+09 | 0.106079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.508535E+09 | 0.755338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.286728E+09 | 0.432134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.707946E+10 | 0.104126E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.194835E+09 | 0.293884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.975397E+09 | 0.143008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.110154E+09 | 0.165519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.170134E+09 | 0.254324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.306477E+09 | 0.449214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.464522E+09 | 0.678645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.714008E+09 | 0.103235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.810102E+09 | 0.118968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.937298E+09 | 0.137443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.952794E+09 | 0.140120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.774822E+09 | 0.115085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.615962E+09 | 0.910929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.394025E+09 | 0.584455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.192767E+09 | 0.289938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.644306E+10 | 0.948153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.110154E+09 | 0.165519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.952794E+09 | 0.140120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.126332E+09 | 0.192538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.166997E+09 | 0.254173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.270476E+09 | 0.403556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.378639E+09 | 0.562301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.559948E+09 | 0.822671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.638167E+09 | 0.953077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.736776E+09 | 0.109929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.746265E+09 | 0.111665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.616051E+09 | 0.931677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.500105E+09 | 0.752816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.338330E+09 | 0.510365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.192860E+09 | 0.295139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.527094E+10 | 0.789425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.126332E+09 | 0.192538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.746265E+09 | 0.111665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.126539E+09 | 0.192901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.167229E+09 | 0.254577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.270468E+09 | 0.403603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.378936E+09 | 0.562834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.560177E+09 | 0.823132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.638176E+09 | 0.953237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.736772E+09 | 0.109946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.746280E+09 | 0.111686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.616075E+09 | 0.931856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.500238E+09 | 0.753135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.338559E+09 | 0.510798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.192971E+09 | 0.295363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.527242E+10 | 0.789775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.126539E+09 | 0.192901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.746280E+09 | 0.111686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.211681E+09 | 0.324488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.240498E+09 | 0.367240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.329958E+09 | 0.492809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.414393E+09 | 0.614486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.561725E+09 | 0.822438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.624482E+09 | 0.929083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.736011E+09 | 0.109406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.768829E+09 | 0.114604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.678861E+09 | 0.102322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.602289E+09 | 0.905032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.452677E+09 | 0.683599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.286400E+09 | 0.439469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.590780E+10 | 0.884197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.211681E+09 | 0.324488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.768829E+09 | 0.114604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.211681E+09 | 0.324598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.240403E+09 | 0.367215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.329701E+09 | 0.492591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.414364E+09 | 0.614667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.561560E+09 | 0.822508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.624090E+09 | 0.928847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.735552E+09 | 0.109381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.768370E+09 | 0.114581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.678447E+09 | 0.102299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.601982E+09 | 0.904924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.452482E+09 | 0.683568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.286207E+09 | 0.439319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.590484E+10 | 0.884085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.211681E+09 | 0.324598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.768370E+09 | 0.114581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 69243736.45 | 0.105103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.104179E+09 | 0.155075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.178629E+09 | 0.258831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.261487E+09 | 0.376141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.394814E+09 | 0.561007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.447004E+09 | 0.644570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.532767E+09 | 0.767154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.552259E+09 | 0.797865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.462877E+09 | 0.676128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.382969E+09 | 0.557591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.256480E+09 | 0.375449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.124310E+09 | 0.185848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.376702E+10 | 0.546076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 69243736.45 | 0.105103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.552259E+09 | 0.797865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 31690026.12 | 0.478839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 68085600.64 | 0.100750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.147966E+09 | 0.213767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.242643E+09 | 0.349000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.394092E+09 | 0.561140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.454223E+09 | 0.656743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.533147E+09 | 0.769457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.540430E+09 | 0.782248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.430260E+09 | 0.629000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.329619E+09 | 0.479495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.196970E+09 | 0.287518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 77594639.09 | 0.115531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.344672E+10 | 0.499253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31690026.12 | 0.478839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.540430E+09 | 0.782248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 68690127.87 | 0.105148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.102471E+09 | 0.153859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.175064E+09 | 0.255647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.261990E+09 | 0.380061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.395708E+09 | 0.567160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.444567E+09 | 0.646834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.529430E+09 | 0.769628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.548974E+09 | 0.800823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.460280E+09 | 0.678541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.381833E+09 | 0.561148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.254441E+09 | 0.375929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.122025E+09 | 0.183974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.374547E+10 | 0.547875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68690127.87 | 0.105148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.548974E+09 | 0.800823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 31156871.13 | 0.474255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 66562831.44 | 0.992342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.144575E+09 | 0.210405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.243284E+09 | 0.352830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.394885E+09 | 0.567269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.451543E+09 | 0.658954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.529631E+09 | 0.771878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.537166E+09 | 0.785179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.428046E+09 | 0.631413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.329111E+09 | 0.483044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.195206E+09 | 0.287491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 75552937.92 | 0.113416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.342672E+10 | 0.500854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31156871.13 | 0.474255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.537166E+09 | 0.785179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 34237071.32 | 0.524457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 64031678.41 | 0.964403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.126832E+09 | 0.186336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.199996E+09 | 0.292408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.316857E+09 | 0.458515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.364169E+09 | 0.535452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.427224E+09 | 0.627443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.431721E+09 | 0.635847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.347392E+09 | 0.516943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.270918E+09 | 0.401315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.167816E+09 | 0.249364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 74261564.63 | 0.112561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.282546E+10 | 0.416507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34237071.32 | 0.524457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.431721E+09 | 0.635847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 34329436.48 | 0.526067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 64083171.06 | 0.965582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.126830E+09 | 0.186398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.200167E+09 | 0.292762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.316950E+09 | 0.458811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.364119E+09 | 0.535575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.427140E+09 | 0.627561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.431645E+09 | 0.635982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.347355E+09 | 0.517072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.270971E+09 | 0.401538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.167944E+09 | 0.249651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 74298661.97 | 0.112661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.282583E+10 | 0.416718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34329436.48 | 0.526067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.431645E+09 | 0.635982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 74651040.11 | 0.114882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.101055E+09 | 0.153059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.157693E+09 | 0.232335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.218832E+09 | 0.319864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.317551E+09 | 0.458347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.356837E+09 | 0.523066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.426774E+09 | 0.625050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.443591E+09 | 0.651677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.380180E+09 | 0.564793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.324414E+09 | 0.480612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.227537E+09 | 0.338993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.122338E+09 | 0.186116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.315145E+10 | 0.464879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 74651040.11 | 0.114882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.443591E+09 | 0.651677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 74714750.88 | 0.115029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.101121E+09 | 0.153227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.157668E+09 | 0.232386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.218985E+09 | 0.320206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.317648E+09 | 0.458646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.356797E+09 | 0.523191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.426697E+09 | 0.625170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.443514E+09 | 0.651811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.380124E+09 | 0.564919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.324427E+09 | 0.480817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.227605E+09 | 0.339230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.122376E+09 | 0.186254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.315168E+10 | 0.465088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 74714750.88 | 0.115029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.443514E+09 | 0.651811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.106884E+09 | 0.00 | 0.00 | 0.00 | 0.403544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.119250E+09 | 0.00 | 0.00 | 0.00 | 0.455760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.165885E+09 | 0.00 | 0.00 | 0.00 | 0.640372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.222613E+09 | 0.00 | 0.00 | 0.00 | 0.881720E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.338967E+09 | 0.00 | 0.00 | 0.00 | 0.139730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.392578E+09 | 0.00 | 0.00 | 0.00 | 0.165400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.477638E+09 | 0.00 | 0.00 | 0.00 | 0.205336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.518830E+09 | 0.00 | 0.00 | 0.00 | 0.223551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.455137E+09 | 0.00 | 0.00 | 0.00 | 0.191220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.403865E+09 | 0.00 | 0.00 | 0.00 | 0.164014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.295967E+09 | 0.00 | 0.00 | 0.00 | 0.116178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.169438E+09 | 0.00 | 0.00 | 0.00 | 0.645934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.366705E+10 | 0.00 | 0.00 | 0.00 | 0.150816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.106884E+09 | 0.00 | 0.00 | 0.00 | 0.403544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.518830E+09 | 0.00 | 0.00 | 0.00 | 0.223551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 67257548.30 | 0.00 | 0.00 | 0.00 | 0.254385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 85186129.69 | 0.00 | 0.00 | 0.00 | 0.326372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.137882E+09 | 0.00 | 0.00 | 0.00 | 0.533523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.205946E+09 | 0.00 | 0.00 | 0.00 | 0.816694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.338957E+09 | 0.00 | 0.00 | 0.00 | 0.139838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.400097E+09 | 0.00 | 0.00 | 0.00 | 0.168664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.479037E+09 | 0.00 | 0.00 | 0.00 | 0.206065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.508999E+09 | 0.00 | 0.00 | 0.00 | 0.219589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.426206E+09 | 0.00 | 0.00 | 0.00 | 0.179391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.356187E+09 | 0.00 | 0.00 | 0.00 | 0.144922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.241745E+09 | 0.00 | 0.00 | 0.00 | 0.950949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.124256E+09 | 0.00 | 0.00 | 0.00 | 0.474868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.337175E+10 | 0.00 | 0.00 | 0.00 | 0.139415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67257548.30 | 0.00 | 0.00 | 0.00 | 0.254385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.508999E+09 | 0.00 | 0.00 | 0.00 | 0.219589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.132632E+10 | 0.00 | 0.00 | 0.00 | 0.439678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.119707E+10 | 0.00 | 0.00 | 0.00 | 0.467088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.132156E+10 | 0.00 | 0.00 | 0.00 | 0.609379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.128911E+10 | 0.00 | 0.00 | 0.00 | 0.696591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.133984E+10 | 0.00 | 0.00 | 0.00 | 0.120411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.130087E+10 | 0.00 | 0.00 | 0.00 | 0.146316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.135513E+10 | 0.00 | 0.00 | 0.00 | 0.184137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.135586E+10 | 0.00 | 0.00 | 0.00 | 0.212291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.131040E+10 | 0.00 | 0.00 | 0.00 | 0.164186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.134803E+10 | 0.00 | 0.00 | 0.00 | 0.135501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.129796E+10 | 0.00 | 0.00 | 0.00 | 0.913808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.133127E+10 | 0.00 | 0.00 | 0.00 | 0.566032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.157734E+11 | 0.00 | 0.00 | 0.00 | 0.133210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.119707E+10 | 0.00 | 0.00 | 0.00 | 0.439678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.135586E+10 | 0.00 | 0.00 | 0.00 | 0.212291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 67362014.89 | 0.00 | 0.00 | 0.00 | 0.255987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 84339784.51 | 0.00 | 0.00 | 0.00 | 0.324732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.135338E+09 | 0.00 | 0.00 | 0.00 | 0.526422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.206979E+09 | 0.00 | 0.00 | 0.00 | 0.824982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.340441E+09 | 0.00 | 0.00 | 0.00 | 0.141090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.398527E+09 | 0.00 | 0.00 | 0.00 | 0.168767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.477082E+09 | 0.00 | 0.00 | 0.00 | 0.206156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.507049E+09 | 0.00 | 0.00 | 0.00 | 0.219740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.424537E+09 | 0.00 | 0.00 | 0.00 | 0.179496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.355683E+09 | 0.00 | 0.00 | 0.00 | 0.145371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.240402E+09 | 0.00 | 0.00 | 0.00 | 0.950186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.122550E+09 | 0.00 | 0.00 | 0.00 | 0.470609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.336029E+10 | 0.00 | 0.00 | 0.00 | 0.139591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67362014.89 | 0.00 | 0.00 | 0.00 | 0.255987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.507049E+09 | 0.00 | 0.00 | 0.00 | 0.219740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 69564756.81 | 0.00 | 0.00 | 0.00 | 0.268242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 82674976.92 | 0.00 | 0.00 | 0.00 | 0.322570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.123978E+09 | 0.00 | 0.00 | 0.00 | 0.488531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.176234E+09 | 0.00 | 0.00 | 0.00 | 0.711936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.277155E+09 | 0.00 | 0.00 | 0.00 | 0.116648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.324045E+09 | 0.00 | 0.00 | 0.00 | 0.139549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.384875E+09 | 0.00 | 0.00 | 0.00 | 0.169357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.404619E+09 | 0.00 | 0.00 | 0.00 | 0.178661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.341479E+09 | 0.00 | 0.00 | 0.00 | 0.146924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.288413E+09 | 0.00 | 0.00 | 0.00 | 0.119804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.201451E+09 | 0.00 | 0.00 | 0.00 | 0.808359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.113855E+09 | 0.00 | 0.00 | 0.00 | 0.443600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.278834E+10 | 0.00 | 0.00 | 0.00 | 0.117527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 69564756.81 | 0.00 | 0.00 | 0.00 | 0.268242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.404619E+09 | 0.00 | 0.00 | 0.00 | 0.178661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 69655283.59 | 0.00 | 0.00 | 0.00 | 0.268626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 82723145.51 | 0.00 | 0.00 | 0.00 | 0.322800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.123953E+09 | 0.00 | 0.00 | 0.00 | 0.488504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.176368E+09 | 0.00 | 0.00 | 0.00 | 0.712571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.277276E+09 | 0.00 | 0.00 | 0.00 | 0.116713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.324045E+09 | 0.00 | 0.00 | 0.00 | 0.139566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.384869E+09 | 0.00 | 0.00 | 0.00 | 0.169374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.404621E+09 | 0.00 | 0.00 | 0.00 | 0.178682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.341479E+09 | 0.00 | 0.00 | 0.00 | 0.146941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.288460E+09 | 0.00 | 0.00 | 0.00 | 0.119838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.201517E+09 | 0.00 | 0.00 | 0.00 | 0.808724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.113889E+09 | 0.00 | 0.00 | 0.00 | 0.443787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.278886E+10 | 0.00 | 0.00 | 0.00 | 0.117562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 69655283.59 | 0.00 | 0.00 | 0.00 | 0.268626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.404621E+09 | 0.00 | 0.00 | 0.00 | 0.178682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.109943E+09 | 0.00 | 0.00 | 0.00 | 0.423399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.116920E+09 | 0.00 | 0.00 | 0.00 | 0.455413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.152726E+09 | 0.00 | 0.00 | 0.00 | 0.600727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.193629E+09 | 0.00 | 0.00 | 0.00 | 0.781578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.278041E+09 | 0.00 | 0.00 | 0.00 | 0.116962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.317250E+09 | 0.00 | 0.00 | 0.00 | 0.136596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.384241E+09 | 0.00 | 0.00 | 0.00 | 0.169032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.415242E+09 | 0.00 | 0.00 | 0.00 | 0.183154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.371343E+09 | 0.00 | 0.00 | 0.00 | 0.159490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.337028E+09 | 0.00 | 0.00 | 0.00 | 0.139754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.256155E+09 | 0.00 | 0.00 | 0.00 | 0.102596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.159216E+09 | 0.00 | 0.00 | 0.00 | 0.619079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309173E+10 | 0.00 | 0.00 | 0.00 | 0.129560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.109943E+09 | 0.00 | 0.00 | 0.00 | 0.423399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.415242E+09 | 0.00 | 0.00 | 0.00 | 0.183154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.115354E+09 | 0.00 | 0.00 | 0.00 | 0.443731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.123196E+09 | 0.00 | 0.00 | 0.00 | 0.479253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.162129E+09 | 0.00 | 0.00 | 0.00 | 0.636849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.208938E+09 | 0.00 | 0.00 | 0.00 | 0.841764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.300226E+09 | 0.00 | 0.00 | 0.00 | 0.125985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.339588E+09 | 0.00 | 0.00 | 0.00 | 0.145817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.409222E+09 | 0.00 | 0.00 | 0.00 | 0.179517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.439391E+09 | 0.00 | 0.00 | 0.00 | 0.193284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.394711E+09 | 0.00 | 0.00 | 0.00 | 0.169088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.360129E+09 | 0.00 | 0.00 | 0.00 | 0.148992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.274168E+09 | 0.00 | 0.00 | 0.00 | 0.109590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.168381E+09 | 0.00 | 0.00 | 0.00 | 0.653867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.329543E+10 | 0.00 | 0.00 | 0.00 | 0.137782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.115354E+09 | 0.00 | 0.00 | 0.00 | 0.443731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.439391E+09 | 0.00 | 0.00 | 0.00 | 0.193284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.195188E+09 | 0.00 | 0.00 | 0.00 | 0.735690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.246015E+09 | 0.00 | 0.00 | 0.00 | 0.938540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.372093E+09 | 0.00 | 0.00 | 0.00 | 0.143230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.498845E+09 | 0.00 | 0.00 | 0.00 | 0.197092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.713359E+09 | 0.00 | 0.00 | 0.00 | 0.293581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.800433E+09 | 0.00 | 0.00 | 0.00 | 0.337005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.941311E+09 | 0.00 | 0.00 | 0.00 | 0.404732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.979585E+09 | 0.00 | 0.00 | 0.00 | 0.422766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.840896E+09 | 0.00 | 0.00 | 0.00 | 0.354013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.719087E+09 | 0.00 | 0.00 | 0.00 | 0.292583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.511737E+09 | 0.00 | 0.00 | 0.00 | 0.201212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.290931E+09 | 0.00 | 0.00 | 0.00 | 0.110859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.710948E+10 | 0.00 | 0.00 | 0.00 | 0.292450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.195188E+09 | 0.00 | 0.00 | 0.00 | 0.735690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.979585E+09 | 0.00 | 0.00 | 0.00 | 0.422766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.110045E+09 | 0.00 | 0.00 | 0.00 | 0.415778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.172291E+09 | 0.00 | 0.00 | 0.00 | 0.659148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.312278E+09 | 0.00 | 0.00 | 0.00 | 0.120506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.462727E+09 | 0.00 | 0.00 | 0.00 | 0.183079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.711461E+09 | 0.00 | 0.00 | 0.00 | 0.293144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.813893E+09 | 0.00 | 0.00 | 0.00 | 0.343005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.941802E+09 | 0.00 | 0.00 | 0.00 | 0.405361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.956815E+09 | 0.00 | 0.00 | 0.00 | 0.413647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.777887E+09 | 0.00 | 0.00 | 0.00 | 0.328269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.616275E+09 | 0.00 | 0.00 | 0.00 | 0.251375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.396475E+09 | 0.00 | 0.00 | 0.00 | 0.156328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.196538E+09 | 0.00 | 0.00 | 0.00 | 0.751426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.646849E+10 | 0.00 | 0.00 | 0.00 | 0.267735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.110045E+09 | 0.00 | 0.00 | 0.00 | 0.415778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.956815E+09 | 0.00 | 0.00 | 0.00 | 0.413647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.194835E+09 | 0.00 | 0.00 | 0.00 | 0.738405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.243298E+09 | 0.00 | 0.00 | 0.00 | 0.933441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.365766E+09 | 0.00 | 0.00 | 0.00 | 0.141629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.500368E+09 | 0.00 | 0.00 | 0.00 | 0.198867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.715929E+09 | 0.00 | 0.00 | 0.00 | 0.296230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.796853E+09 | 0.00 | 0.00 | 0.00 | 0.337296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.936925E+09 | 0.00 | 0.00 | 0.00 | 0.405008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.975397E+09 | 0.00 | 0.00 | 0.00 | 0.423215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.837150E+09 | 0.00 | 0.00 | 0.00 | 0.354298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.717677E+09 | 0.00 | 0.00 | 0.00 | 0.293546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.508535E+09 | 0.00 | 0.00 | 0.00 | 0.201061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.286728E+09 | 0.00 | 0.00 | 0.00 | 0.109868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.707946E+10 | 0.00 | 0.00 | 0.00 | 0.292820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.194835E+09 | 0.00 | 0.00 | 0.00 | 0.738405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.975397E+09 | 0.00 | 0.00 | 0.00 | 0.423215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.110154E+09 | 0.00 | 0.00 | 0.00 | 0.418509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.170134E+09 | 0.00 | 0.00 | 0.00 | 0.654653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.306477E+09 | 0.00 | 0.00 | 0.00 | 0.118979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.464522E+09 | 0.00 | 0.00 | 0.00 | 0.184883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.714008E+09 | 0.00 | 0.00 | 0.00 | 0.295771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.810102E+09 | 0.00 | 0.00 | 0.00 | 0.343226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.937298E+09 | 0.00 | 0.00 | 0.00 | 0.405572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.952794E+09 | 0.00 | 0.00 | 0.00 | 0.414100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.774822E+09 | 0.00 | 0.00 | 0.00 | 0.328685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.615962E+09 | 0.00 | 0.00 | 0.00 | 0.252557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.394025E+09 | 0.00 | 0.00 | 0.00 | 0.156242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.192767E+09 | 0.00 | 0.00 | 0.00 | 0.741225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.644306E+10 | 0.00 | 0.00 | 0.00 | 0.268145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.110154E+09 | 0.00 | 0.00 | 0.00 | 0.418509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.952794E+09 | 0.00 | 0.00 | 0.00 | 0.414100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.126332E+09 | 0.00 | 0.00 | 0.00 | 0.486531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.166997E+09 | 0.00 | 0.00 | 0.00 | 0.650646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.270476E+09 | 0.00 | 0.00 | 0.00 | 0.106344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.378639E+09 | 0.00 | 0.00 | 0.00 | 0.152699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.559948E+09 | 0.00 | 0.00 | 0.00 | 0.235506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.638167E+09 | 0.00 | 0.00 | 0.00 | 0.274894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.736776E+09 | 0.00 | 0.00 | 0.00 | 0.324568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.746265E+09 | 0.00 | 0.00 | 0.00 | 0.330324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.616051E+09 | 0.00 | 0.00 | 0.00 | 0.265734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.500105E+09 | 0.00 | 0.00 | 0.00 | 0.208184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.338330E+09 | 0.00 | 0.00 | 0.00 | 0.135986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.192860E+09 | 0.00 | 0.00 | 0.00 | 0.751262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.527094E+10 | 0.00 | 0.00 | 0.00 | 0.222308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.126332E+09 | 0.00 | 0.00 | 0.00 | 0.486531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.746265E+09 | 0.00 | 0.00 | 0.00 | 0.330324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.126539E+09 | 0.00 | 0.00 | 0.00 | 0.487396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.167229E+09 | 0.00 | 0.00 | 0.00 | 0.651642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.270468E+09 | 0.00 | 0.00 | 0.00 | 0.106357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.378936E+09 | 0.00 | 0.00 | 0.00 | 0.152842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.560177E+09 | 0.00 | 0.00 | 0.00 | 0.235633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.638176E+09 | 0.00 | 0.00 | 0.00 | 0.274934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.736772E+09 | 0.00 | 0.00 | 0.00 | 0.324607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.746280E+09 | 0.00 | 0.00 | 0.00 | 0.330372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.616075E+09 | 0.00 | 0.00 | 0.00 | 0.265780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.500238E+09 | 0.00 | 0.00 | 0.00 | 0.208267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.338559E+09 | 0.00 | 0.00 | 0.00 | 0.136097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.192971E+09 | 0.00 | 0.00 | 0.00 | 0.751802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.527242E+10 | 0.00 | 0.00 | 0.00 | 0.222397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.126539E+09 | 0.00 | 0.00 | 0.00 | 0.487396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.746280E+09 | 0.00 | 0.00 | 0.00 | 0.330372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.211681E+09 | 0.00 | 0.00 | 0.00 | 0.813544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.240498E+09 | 0.00 | 0.00 | 0.00 | 0.934809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.329958E+09 | 0.00 | 0.00 | 0.00 | 0.129425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.414393E+09 | 0.00 | 0.00 | 0.00 | 0.166894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.561725E+09 | 0.00 | 0.00 | 0.00 | 0.235961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.624482E+09 | 0.00 | 0.00 | 0.00 | 0.268742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.736011E+09 | 0.00 | 0.00 | 0.00 | 0.323894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.768829E+09 | 0.00 | 0.00 | 0.00 | 0.339662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.678861E+09 | 0.00 | 0.00 | 0.00 | 0.292046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.602289E+09 | 0.00 | 0.00 | 0.00 | 0.250065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.452677E+09 | 0.00 | 0.00 | 0.00 | 0.181458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.286400E+09 | 0.00 | 0.00 | 0.00 | 0.111236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.590780E+10 | 0.00 | 0.00 | 0.00 | 0.247422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.211681E+09 | 0.00 | 0.00 | 0.00 | 0.813544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.768829E+09 | 0.00 | 0.00 | 0.00 | 0.339662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.211681E+09 | 0.00 | 0.00 | 0.00 | 0.813706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.240403E+09 | 0.00 | 0.00 | 0.00 | 0.934639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.329701E+09 | 0.00 | 0.00 | 0.00 | 0.129356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.414364E+09 | 0.00 | 0.00 | 0.00 | 0.166927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.561560E+09 | 0.00 | 0.00 | 0.00 | 0.235960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.624090E+09 | 0.00 | 0.00 | 0.00 | 0.268650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.735552E+09 | 0.00 | 0.00 | 0.00 | 0.323788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.768370E+09 | 0.00 | 0.00 | 0.00 | 0.339560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.678447E+09 | 0.00 | 0.00 | 0.00 | 0.291948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.601982E+09 | 0.00 | 0.00 | 0.00 | 0.250004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.452482E+09 | 0.00 | 0.00 | 0.00 | 0.181425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.286207E+09 | 0.00 | 0.00 | 0.00 | 0.111184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.590484E+10 | 0.00 | 0.00 | 0.00 | 0.247364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.211681E+09 | 0.00 | 0.00 | 0.00 | 0.813706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.768370E+09 | 0.00 | 0.00 | 0.00 | 0.339560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 69243736.45 | 0.00 | 0.00 | 0.00 | 0.259876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.104179E+09 | 0.00 | 0.00 | 0.00 | 0.396725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.178629E+09 | 0.00 | 0.00 | 0.00 | 0.685952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.261487E+09 | 0.00 | 0.00 | 0.00 | 0.103086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.394814E+09 | 0.00 | 0.00 | 0.00 | 0.161895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.447004E+09 | 0.00 | 0.00 | 0.00 | 0.187277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.532767E+09 | 0.00 | 0.00 | 0.00 | 0.227567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.552259E+09 | 0.00 | 0.00 | 0.00 | 0.236760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.462877E+09 | 0.00 | 0.00 | 0.00 | 0.193939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.382969E+09 | 0.00 | 0.00 | 0.00 | 0.155331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.256480E+09 | 0.00 | 0.00 | 0.00 | 0.100623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.124310E+09 | 0.00 | 0.00 | 0.00 | 0.472238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.376702E+10 | 0.00 | 0.00 | 0.00 | 0.154796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 69243736.45 | 0.00 | 0.00 | 0.00 | 0.259876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.552259E+09 | 0.00 | 0.00 | 0.00 | 0.236760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNW
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 31690026.12 | 0.00 | 0.00 | 0.00 | 0.119285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 68085600.64 | 0.00 | 0.00 | 0.00 | 0.260230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.147966E+09 | 0.00 | 0.00 | 0.00 | 0.569666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.242643E+09 | 0.00 | 0.00 | 0.00 | 0.957477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.394092E+09 | 0.00 | 0.00 | 0.00 | 0.161707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.454223E+09 | 0.00 | 0.00 | 0.00 | 0.190404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.533147E+09 | 0.00 | 0.00 | 0.00 | 0.227863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.540430E+09 | 0.00 | 0.00 | 0.00 | 0.231965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.430260E+09 | 0.00 | 0.00 | 0.00 | 0.180594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.329619E+09 | 0.00 | 0.00 | 0.00 | 0.133945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.196970E+09 | 0.00 | 0.00 | 0.00 | 0.774711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 77594639.09 | 0.00 | 0.00 | 0.00 | 0.296002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.344672E+10 | 0.00 | 0.00 | 0.00 | 0.142422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31690026.12 | 0.00 | 0.00 | 0.00 | 0.119285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.540430E+09 | 0.00 | 0.00 | 0.00 | 0.231965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 68690127.87 | 0.00 | 0.00 | 0.00 | 0.259477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.102471E+09 | 0.00 | 0.00 | 0.00 | 0.392829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.175064E+09 | 0.00 | 0.00 | 0.00 | 0.676906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.261990E+09 | 0.00 | 0.00 | 0.00 | 0.103989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.395708E+09 | 0.00 | 0.00 | 0.00 | 0.163261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.444567E+09 | 0.00 | 0.00 | 0.00 | 0.187397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.529430E+09 | 0.00 | 0.00 | 0.00 | 0.227535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.548974E+09 | 0.00 | 0.00 | 0.00 | 0.236802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.460280E+09 | 0.00 | 0.00 | 0.00 | 0.194017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.381833E+09 | 0.00 | 0.00 | 0.00 | 0.155796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.254441E+09 | 0.00 | 0.00 | 0.00 | 0.100458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.122025E+09 | 0.00 | 0.00 | 0.00 | 0.466593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.374547E+10 | 0.00 | 0.00 | 0.00 | 0.154884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68690127.87 | 0.00 | 0.00 | 0.00 | 0.259477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.548974E+09 | 0.00 | 0.00 | 0.00 | 0.236802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 31156871.13 | 0.00 | 0.00 | 0.00 | 0.118077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 66562831.44 | 0.00 | 0.00 | 0.00 | 0.256195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.144575E+09 | 0.00 | 0.00 | 0.00 | 0.560579E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.243284E+09 | 0.00 | 0.00 | 0.00 | 0.966644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.394885E+09 | 0.00 | 0.00 | 0.00 | 0.163034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.451543E+09 | 0.00 | 0.00 | 0.00 | 0.190444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.529631E+09 | 0.00 | 0.00 | 0.00 | 0.227763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.537166E+09 | 0.00 | 0.00 | 0.00 | 0.231991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.428046E+09 | 0.00 | 0.00 | 0.00 | 0.180752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.329111E+09 | 0.00 | 0.00 | 0.00 | 0.134540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.195206E+09 | 0.00 | 0.00 | 0.00 | 0.772848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 75552937.92 | 0.00 | 0.00 | 0.00 | 0.290196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.342672E+10 | 0.00 | 0.00 | 0.00 | 0.142498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31156871.13 | 0.00 | 0.00 | 0.00 | 0.118077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.537166E+09 | 0.00 | 0.00 | 0.00 | 0.231991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 34237071.32 | 0.00 | 0.00 | 0.00 | 0.130701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 64031678.41 | 0.00 | 0.00 | 0.00 | 0.247862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.126832E+09 | 0.00 | 0.00 | 0.00 | 0.494844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.199996E+09 | 0.00 | 0.00 | 0.00 | 0.800028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.316857E+09 | 0.00 | 0.00 | 0.00 | 0.131963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.364169E+09 | 0.00 | 0.00 | 0.00 | 0.155096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.427224E+09 | 0.00 | 0.00 | 0.00 | 0.185719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.431721E+09 | 0.00 | 0.00 | 0.00 | 0.188530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.347392E+09 | 0.00 | 0.00 | 0.00 | 0.148154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.270918E+09 | 0.00 | 0.00 | 0.00 | 0.111721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.167816E+09 | 0.00 | 0.00 | 0.00 | 0.669106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 74261564.63 | 0.00 | 0.00 | 0.00 | 0.287070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.282546E+10 | 0.00 | 0.00 | 0.00 | 0.118414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34237071.32 | 0.00 | 0.00 | 0.00 | 0.130701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.431721E+09 | 0.00 | 0.00 | 0.00 | 0.188530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 34329436.48 | 0.00 | 0.00 | 0.00 | 0.131093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 64083171.06 | 0.00 | 0.00 | 0.00 | 0.248140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.126830E+09 | 0.00 | 0.00 | 0.00 | 0.494996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.200167E+09 | 0.00 | 0.00 | 0.00 | 0.800961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.316950E+09 | 0.00 | 0.00 | 0.00 | 0.132038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.364119E+09 | 0.00 | 0.00 | 0.00 | 0.155118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.427140E+09 | 0.00 | 0.00 | 0.00 | 0.185732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.431645E+09 | 0.00 | 0.00 | 0.00 | 0.188548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.347355E+09 | 0.00 | 0.00 | 0.00 | 0.148179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.270971E+09 | 0.00 | 0.00 | 0.00 | 0.111774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.167944E+09 | 0.00 | 0.00 | 0.00 | 0.669816E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 74298661.97 | 0.00 | 0.00 | 0.00 | 0.287303E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.282583E+10 | 0.00 | 0.00 | 0.00 | 0.118462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34329436.48 | 0.00 | 0.00 | 0.00 | 0.131093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.431645E+09 | 0.00 | 0.00 | 0.00 | 0.188548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS1
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 74651040.11 | 0.00 | 0.00 | 0.00 | 0.284198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.101055E+09 | 0.00 | 0.00 | 0.00 | 0.389893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.157693E+09 | 0.00 | 0.00 | 0.00 | 0.613645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.218832E+09 | 0.00 | 0.00 | 0.00 | 0.874526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.317551E+09 | 0.00 | 0.00 | 0.00 | 0.132144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.356837E+09 | 0.00 | 0.00 | 0.00 | 0.151877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.426774E+09 | 0.00 | 0.00 | 0.00 | 0.185392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.443591E+09 | 0.00 | 0.00 | 0.00 | 0.193430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.380180E+09 | 0.00 | 0.00 | 0.00 | 0.161795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.324414E+09 | 0.00 | 0.00 | 0.00 | 0.133505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.227537E+09 | 0.00 | 0.00 | 0.00 | 0.904964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.122338E+09 | 0.00 | 0.00 | 0.00 | 0.471079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.315145E+10 | 0.00 | 0.00 | 0.00 | 0.131197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 74651040.11 | 0.00 | 0.00 | 0.00 | 0.284198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.443591E+09 | 0.00 | 0.00 | 0.00 | 0.193430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS2
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 74714750.88 | 0.00 | 0.00 | 0.00 | 0.284519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.101121E+09 | 0.00 | 0.00 | 0.00 | 0.390262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.157668E+09 | 0.00 | 0.00 | 0.00 | 0.613739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.218985E+09 | 0.00 | 0.00 | 0.00 | 0.875405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.317648E+09 | 0.00 | 0.00 | 0.00 | 0.132221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.356797E+09 | 0.00 | 0.00 | 0.00 | 0.151902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.426697E+09 | 0.00 | 0.00 | 0.00 | 0.185408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.443514E+09 | 0.00 | 0.00 | 0.00 | 0.193448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.380124E+09 | 0.00 | 0.00 | 0.00 | 0.161815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.324427E+09 | 0.00 | 0.00 | 0.00 | 0.133547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.227605E+09 | 0.00 | 0.00 | 0.00 | 0.905487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.122376E+09 | 0.00 | 0.00 | 0.00 | 0.471357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.315168E+10 | 0.00 | 0.00 | 0.00 | 0.131242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 74714750.88 | 0.00 | 0.00 | 0.00 | 0.284519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.443514E+09 | 0.00 | 0.00 | 0.00 | 0.193448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: G SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 37749567.72 | 21908832.85 | 0.00 | 3296978.77 | 15038303.89 | 0.00 | 86528493.65 | 0.00 | 0.36 |
| February | 26070253.27 | 70835882.91 | 0.00 | 1940813.95 | 16099718.75 | 0.00 | 42442557.39 | 0.00 | 0.36 |
| March | 21888223.55 | 0.145894E+09 | 0.00 | 1284545.79 | 11927682.93 | 0.00 | 31841937.24 | 0.00 | 0.36 |
| April | 11096501.18 | 0.349575E+09 | 0.00 | 436129.25 | 9281767.11 | 0.00 | 8406141.88 | 0.00 | 0.36 |
| May | 333369.82 | 0.718478E+09 | 0.00 | 95825.95 | 2267238.55 | 0.00 | 752566.07 | 0.00 | 0.36 |
| June | 0.00 | 0.113169E+10 | 0.00 | 3395.38 | 766107.08 | 0.00 | 73917.71 | 0.00 | 0.36 |
| July | 0.00 | 0.147987E+10 | 0.00 | 10991.55 | 0.00 | 0.00 | 75495.83 | 0.00 | 0.36 |
| August | 0.00 | 0.158297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.130892E+10 | 0.00 | 0.00 | 2474662.74 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1177397.84 | 0.878567E+09 | 0.00 | 174809.25 | 7289065.67 | 0.00 | 1808786.27 | 0.00 | 0.36 |
| November | 3065154.14 | 0.408815E+09 | 0.00 | 266042.01 | 20005955.98 | 0.00 | 1464841.37 | 0.00 | 0.36 |
| December | 26837615.29 | 0.123317E+09 | 0.00 | 2103879.54 | 24976246.45 | 0.00 | 31296171.07 | 0.00 | 0.36 |
| Annual Sum or Average | 0.128218E+09 | 0.822084E+10 | 0.00 | 9613411.44 | 0.110127E+09 | 0.00 | 0.204691E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 21908832.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 37749567.72 | 0.158297E+10 | 0.00 | 3296978.77 | 24976246.45 | 0.00 | 86528493.65 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 50240662.02 | 16376751.38 | 0.00 | 2053341.75 | 12084319.58 | 0.00 | 89310415.60 | 0.00 | 0.36 |
| February | 33237381.52 | 60735915.80 | 0.00 | 1365474.58 | 14250502.10 | 0.00 | 45281806.08 | 0.00 | 0.36 |
| March | 24034345.01 | 0.134633E+09 | 0.00 | 1062993.50 | 11835360.90 | 0.00 | 33107712.73 | 0.00 | 0.36 |
| April | 11144171.15 | 0.341658E+09 | 0.00 | 394084.93 | 8914026.56 | 0.00 | 8644010.99 | 0.00 | 0.36 |
| May | 321025.62 | 0.719504E+09 | 0.00 | 89093.19 | 2216273.52 | 0.00 | 713002.22 | 0.00 | 0.36 |
| June | 0.00 | 0.113588E+10 | 0.00 | 3467.68 | 764218.16 | 0.00 | 71117.98 | 0.00 | 0.36 |
| July | 0.00 | 0.148220E+10 | 0.00 | 11012.64 | 0.00 | 0.00 | 72477.51 | 0.00 | 0.36 |
| August | 0.00 | 0.157851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.129447E+10 | 0.00 | 0.00 | 2319022.97 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1263555.79 | 0.857317E+09 | 0.00 | 117959.04 | 7305346.32 | 0.00 | 1561969.67 | 0.00 | 0.36 |
| November | 3205614.33 | 0.383326E+09 | 0.00 | 195195.62 | 20786941.53 | 0.00 | 1695253.37 | 0.00 | 0.36 |
| December | 29907760.58 | 0.104525E+09 | 0.00 | 1537235.43 | 23303886.64 | 0.00 | 33816963.67 | 0.00 | 0.36 |
| Annual Sum or Average | 0.153355E+09 | 0.810914E+10 | 0.00 | 6829858.36 | 0.103780E+09 | 0.00 | 0.214275E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 16376751.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 50240662.02 | 0.157851E+10 | 0.00 | 2053341.75 | 23303886.64 | 0.00 | 89310415.60 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICE
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.735412E+09 | 42495102.33 | 0.00 | 3151269.90 | 3950967.41 | 0.00 | 91320595.29 | 0.00 | 0.50 |
| February | 0.544298E+09 | 79367820.04 | 0.00 | 2321244.46 | 15550128.23 | 0.00 | 46435419.65 | 0.00 | 0.51 |
| March | 0.457087E+09 | 0.154031E+09 | 0.00 | 1992074.16 | 37893806.32 | 0.00 | 38157857.29 | 0.00 | 0.51 |
| April | 0.313644E+09 | 0.287915E+09 | 0.00 | 1427963.23 | 0.116016E+09 | 0.00 | 13690877.63 | 0.00 | 0.51 |
| May | 0.127663E+09 | 0.699715E+09 | 0.00 | 1690255.37 | 0.266725E+09 | 0.00 | 2159968.71 | 0.00 | 0.52 |
| June | 61270215.21 | 0.111697E+10 | 0.00 | 480762.48 | 0.460826E+09 | 0.00 | 2270.50 | 0.00 | 0.53 |
| July | 16155884.31 | 0.168838E+10 | 0.00 | 106340.12 | 0.607924E+09 | 0.00 | 5814121.42 | 0.00 | 0.54 |
| August | 1528841.83 | 0.186059E+10 | 0.00 | 84172.37 | 0.697161E+09 | 0.00 | 123582.84 | 0.00 | 0.53 |
| September | 33688479.88 | 0.137086E+10 | 0.00 | 479732.00 | 0.399703E+09 | 0.00 | 1645075.16 | 0.00 | 0.53 |
| October | 98861043.50 | 0.867412E+09 | 0.00 | 585434.13 | 0.207788E+09 | 0.00 | 17476678.11 | 0.00 | 0.52 |
| November | 0.314336E+09 | 0.408898E+09 | 0.00 | 1668668.80 | 68151209.45 | 0.00 | 24226520.68 | 0.00 | 0.52 |
| December | 0.622408E+09 | 0.116103E+09 | 0.00 | 2737468.62 | 20524368.80 | 0.00 | 37167088.03 | 0.00 | 0.51 |
| Annual Sum or Average | 0.332635E+10 | 0.869273E+10 | 0.00 | 16725385.64 | 0.290221E+10 | 0.00 | 0.278220E+09 | 0.00 | 0.52 |
| Minimum of Months | 1528841.83 | 42495102.33 | 0.00 | 84172.37 | 3950967.41 | 0.00 | 2270.50 | 0.00 | 0.50 |
| Maximum of Months | 0.735412E+09 | 0.186059E+10 | 0.00 | 3151269.90 | 0.697161E+09 | 0.00 | 91320595.29 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: G NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 50502729.67 | 16496456.24 | 0.00 | 2092596.67 | 12167205.91 | 0.00 | 89338888.08 | 0.00 | 0.36 |
| February | 33433653.81 | 61240232.11 | 0.00 | 1377394.34 | 13570368.33 | 0.00 | 45842165.12 | 0.00 | 0.36 |
| March | 24411698.94 | 0.135117E+09 | 0.00 | 1064605.35 | 11020313.68 | 0.00 | 33432088.52 | 0.00 | 0.36 |
| April | 10879424.30 | 0.343516E+09 | 0.00 | 429693.86 | 7807398.17 | 0.00 | 9063340.28 | 0.00 | 0.36 |
| May | 330149.30 | 0.720621E+09 | 0.00 | 88875.84 | 2098014.57 | 0.00 | 699031.53 | 0.00 | 0.36 |
| June | 0.00 | 0.113653E+10 | 0.00 | 3414.20 | 755287.83 | 0.00 | 72566.82 | 0.00 | 0.36 |
| July | 0.00 | 0.148295E+10 | 0.00 | 10803.05 | 0.00 | 0.00 | 73315.08 | 0.00 | 0.36 |
| August | 0.00 | 0.157939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.129501E+10 | 0.00 | 0.00 | 2315452.76 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1281796.05 | 0.859496E+09 | 0.00 | 132269.21 | 7285830.25 | 0.00 | 1516692.25 | 0.00 | 0.36 |
| November | 3336125.18 | 0.384557E+09 | 0.00 | 201639.43 | 21001252.65 | 0.00 | 1663113.71 | 0.00 | 0.36 |
| December | 31016369.05 | 0.104499E+09 | 0.00 | 1551608.59 | 23003189.34 | 0.00 | 33550253.46 | 0.00 | 0.36 |
| Annual Sum or Average | 0.155192E+09 | 0.811942E+10 | 0.00 | 6952900.54 | 0.101024E+09 | 0.00 | 0.215251E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 16496456.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 50502729.67 | 0.157939E+10 | 0.00 | 2092596.67 | 23003189.34 | 0.00 | 89338888.08 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 48378280.57 | 16544488.17 | 0.00 | 2313202.64 | 11996954.54 | 0.00 | 87485660.63 | 0.00 | 0.36 |
| February | 32803302.39 | 60913972.58 | 0.00 | 1523980.77 | 14034239.81 | 0.00 | 42888668.04 | 0.00 | 0.36 |
| March | 24073860.40 | 0.131952E+09 | 0.00 | 1156773.55 | 12027815.35 | 0.00 | 32233575.68 | 0.00 | 0.36 |
| April | 11120793.54 | 0.335818E+09 | 0.00 | 397188.04 | 8875701.09 | 0.00 | 8780093.55 | 0.00 | 0.36 |
| May | 345232.21 | 0.701468E+09 | 0.00 | 93934.92 | 2397512.85 | 0.00 | 821800.91 | 0.00 | 0.36 |
| June | 0.00 | 0.110729E+10 | 0.00 | 3891.75 | 690690.56 | 0.00 | 90267.36 | 0.00 | 0.36 |
| July | 0.00 | 0.144520E+10 | 0.00 | 12625.56 | 0.00 | 0.00 | 109321.28 | 0.00 | 0.36 |
| August | 0.00 | 0.153647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.125701E+10 | 0.00 | 0.00 | 2173600.36 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1313694.67 | 0.831047E+09 | 0.00 | 112236.08 | 7033403.52 | 0.00 | 1753060.58 | 0.00 | 0.36 |
| November | 3206720.19 | 0.370918E+09 | 0.00 | 191502.08 | 19775314.95 | 0.00 | 2018258.72 | 0.00 | 0.36 |
| December | 30056400.99 | 0.102235E+09 | 0.00 | 1594517.37 | 22517062.85 | 0.00 | 33296532.69 | 0.00 | 0.36 |
| Annual Sum or Average | 0.151298E+09 | 0.789687E+10 | 0.00 | 7399852.76 | 0.101522E+09 | 0.00 | 0.209477E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 16544488.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 48378280.57 | 0.153647E+10 | 0.00 | 2313202.64 | 22517062.85 | 0.00 | 87485660.63 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 48380636.34 | 16558417.11 | 0.00 | 2315747.55 | 12003850.05 | 0.00 | 87544918.37 | 0.00 | 0.36 |
| February | 32823670.89 | 60955461.35 | 0.00 | 1525104.77 | 14029748.08 | 0.00 | 42851371.35 | 0.00 | 0.36 |
| March | 24100093.45 | 0.131969E+09 | 0.00 | 1155138.23 | 12048466.42 | 0.00 | 32209437.73 | 0.00 | 0.36 |
| April | 11120347.32 | 0.335948E+09 | 0.00 | 397775.28 | 8863651.84 | 0.00 | 8774746.35 | 0.00 | 0.36 |
| May | 345247.55 | 0.701571E+09 | 0.00 | 93704.81 | 2397552.24 | 0.00 | 820469.30 | 0.00 | 0.36 |
| June | 0.00 | 0.110735E+10 | 0.00 | 3891.31 | 690789.02 | 0.00 | 90305.03 | 0.00 | 0.36 |
| July | 0.00 | 0.144528E+10 | 0.00 | 12610.97 | 0.00 | 0.00 | 109251.58 | 0.00 | 0.36 |
| August | 0.00 | 0.153656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.125708E+10 | 0.00 | 0.00 | 2173627.66 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1313565.63 | 0.831164E+09 | 0.00 | 112501.57 | 7033776.62 | 0.00 | 1751447.13 | 0.00 | 0.36 |
| November | 3219791.80 | 0.371050E+09 | 0.00 | 191566.75 | 19762774.64 | 0.00 | 2003064.11 | 0.00 | 0.36 |
| December | 30064137.03 | 0.102289E+09 | 0.00 | 1595480.12 | 22499856.66 | 0.00 | 33304714.55 | 0.00 | 0.36 |
| Annual Sum or Average | 0.151367E+09 | 0.789777E+10 | 0.00 | 7403521.37 | 0.101504E+09 | 0.00 | 0.209460E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 16558417.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 48380636.34 | 0.153656E+10 | 0.00 | 2315747.55 | 22499856.66 | 0.00 | 87544918.37 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 38628660.40 | 22153715.17 | 0.00 | 3607355.05 | 15653750.61 | 0.00 | 83942823.02 | 0.00 | 0.36 |
| February | 26362794.30 | 71802008.64 | 0.00 | 2120696.10 | 16675073.85 | 0.00 | 39698317.97 | 0.00 | 0.36 |
| March | 21304652.14 | 0.145435E+09 | 0.00 | 1378009.32 | 11712544.14 | 0.00 | 31542416.74 | 0.00 | 0.36 |
| April | 11060039.48 | 0.346051E+09 | 0.00 | 443019.03 | 9036578.05 | 0.00 | 8445579.74 | 0.00 | 0.36 |
| May | 357229.81 | 0.701202E+09 | 0.00 | 99163.24 | 2479208.33 | 0.00 | 860055.19 | 0.00 | 0.36 |
| June | 0.00 | 0.110270E+10 | 0.00 | 3810.51 | 712696.02 | 0.00 | 94304.89 | 0.00 | 0.36 |
| July | 0.00 | 0.144327E+10 | 0.00 | 12770.87 | 0.00 | 0.00 | 113086.49 | 0.00 | 0.36 |
| August | 0.00 | 0.154372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.127771E+10 | 0.00 | 0.00 | 2219519.76 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1221212.58 | 0.859433E+09 | 0.00 | 161546.82 | 6897291.99 | 0.00 | 1985947.23 | 0.00 | 0.36 |
| November | 3084503.61 | 0.401653E+09 | 0.00 | 254028.74 | 19398274.72 | 0.00 | 1610553.75 | 0.00 | 0.36 |
| December | 27014341.19 | 0.122993E+09 | 0.00 | 2190830.75 | 25133889.84 | 0.00 | 30678433.56 | 0.00 | 0.36 |
| Annual Sum or Average | 0.129033E+09 | 0.803812E+10 | 0.00 | 10271230.44 | 0.109919E+09 | 0.00 | 0.198972E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 22153715.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 38628660.40 | 0.154372E+10 | 0.00 | 3607355.05 | 25133889.84 | 0.00 | 83942823.02 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 38992084.81 | 22687854.08 | 0.00 | 3720865.65 | 16024264.07 | 0.00 | 82743162.50 | 0.00 | 0.36 |
| February | 26503449.68 | 73290486.38 | 0.00 | 2208355.43 | 17045969.80 | 0.00 | 38947268.64 | 0.00 | 0.36 |
| March | 21293327.43 | 0.147953E+09 | 0.00 | 1444465.72 | 11973364.00 | 0.00 | 30832208.38 | 0.00 | 0.36 |
| April | 10286777.54 | 0.354393E+09 | 0.00 | 463373.49 | 9459784.36 | 0.00 | 8421014.43 | 0.00 | 0.36 |
| May | 315105.99 | 0.715581E+09 | 0.00 | 96741.54 | 2440439.19 | 0.00 | 724584.70 | 0.00 | 0.36 |
| June | 0.00 | 0.112142E+10 | 0.00 | 3205.01 | 745410.26 | 0.00 | 81597.75 | 0.00 | 0.36 |
| July | 0.00 | 0.146266E+10 | 0.00 | 11909.08 | 0.00 | 0.00 | 89825.49 | 0.00 | 0.36 |
| August | 0.00 | 0.156160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.129553E+10 | 0.00 | 0.00 | 2410738.88 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1198263.45 | 0.873942E+09 | 0.00 | 174616.64 | 7307959.83 | 0.00 | 1878836.25 | 0.00 | 0.36 |
| November | 3051125.15 | 0.409610E+09 | 0.00 | 262338.20 | 20710663.26 | 0.00 | 1363818.53 | 0.00 | 0.36 |
| December | 27294314.69 | 0.126364E+09 | 0.00 | 2252043.72 | 25724628.92 | 0.00 | 29914921.82 | 0.00 | 0.36 |
| Annual Sum or Average | 0.128934E+09 | 0.816503E+10 | 0.00 | 10637914.47 | 0.113843E+09 | 0.00 | 0.194997E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 22687854.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 38992084.81 | 0.156160E+10 | 0.00 | 3720865.65 | 25724628.92 | 0.00 | 82743162.50 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 76819996.93 | 43208788.25 | 0.00 | 5897471.89 | 26378588.69 | 0.00 | 0.173179E+09 | 0.00 | 0.36 |
| February | 50542879.77 | 0.139964E+09 | 0.00 | 3797692.30 | 29252257.54 | 0.00 | 85148418.79 | 0.00 | 0.36 |
| March | 41370833.29 | 0.297022E+09 | 0.00 | 2764903.42 | 22226042.96 | 0.00 | 60987806.08 | 0.00 | 0.36 |
| April | 20649551.85 | 0.713894E+09 | 0.00 | 874554.19 | 16718317.50 | 0.00 | 15752423.29 | 0.00 | 0.36 |
| May | 633766.14 | 0.143612E+10 | 0.00 | 186952.01 | 4528431.72 | 0.00 | 1475272.58 | 0.00 | 0.36 |
| June | 0.00 | 0.223999E+10 | 0.00 | 6514.08 | 1245299.83 | 0.00 | 154970.82 | 0.00 | 0.36 |
| July | 0.00 | 0.291289E+10 | 0.00 | 21394.23 | 0.00 | 0.00 | 172992.17 | 0.00 | 0.36 |
| August | 0.00 | 0.308866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.253096E+10 | 0.00 | 0.00 | 4717420.26 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 2210052.61 | 0.167393E+10 | 0.00 | 288135.14 | 12846125.42 | 0.00 | 3594392.04 | 0.00 | 0.36 |
| November | 6870518.38 | 0.762275E+09 | 0.00 | 500070.30 | 32797733.15 | 0.00 | 4548970.62 | 0.00 | 0.36 |
| December | 49053025.53 | 0.227585E+09 | 0.00 | 3482190.07 | 44994664.97 | 0.00 | 70936874.82 | 0.00 | 0.36 |
| Annual Sum or Average | 0.248151E+09 | 0.160665E+11 | 0.00 | 17819877.61 | 0.195705E+09 | 0.00 | 0.415951E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 43208788.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 76819996.93 | 0.308866E+10 | 0.00 | 5897471.89 | 44994664.97 | 0.00 | 0.173179E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.104069E+09 | 30949694.39 | 0.00 | 3250362.19 | 21628893.42 | 0.00 | 0.170831E+09 | 0.00 | 0.36 |
| February | 63823403.42 | 0.119986E+09 | 0.00 | 2610288.96 | 25981297.33 | 0.00 | 91415967.68 | 0.00 | 0.36 |
| March | 45552827.85 | 0.276769E+09 | 0.00 | 2317782.36 | 21362316.67 | 0.00 | 62209985.69 | 0.00 | 0.36 |
| April | 20700023.06 | 0.699175E+09 | 0.00 | 770863.92 | 16440335.40 | 0.00 | 16073730.37 | 0.00 | 0.36 |
| May | 633383.14 | 0.143740E+10 | 0.00 | 173858.27 | 4540036.13 | 0.00 | 1381694.16 | 0.00 | 0.36 |
| June | 0.00 | 0.224715E+10 | 0.00 | 6604.26 | 1289354.87 | 0.00 | 150882.45 | 0.00 | 0.36 |
| July | 0.00 | 0.291618E+10 | 0.00 | 20827.54 | 0.00 | 0.00 | 168524.07 | 0.00 | 0.36 |
| August | 0.00 | 0.307691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.249499E+10 | 0.00 | 0.00 | 4573921.11 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 2651759.89 | 0.161990E+10 | 0.00 | 176071.76 | 13445945.33 | 0.00 | 3025281.29 | 0.00 | 0.36 |
| November | 7703898.95 | 0.700126E+09 | 0.00 | 342833.43 | 36242429.20 | 0.00 | 5965962.04 | 0.00 | 0.36 |
| December | 58013742.69 | 0.186390E+09 | 0.00 | 2283469.95 | 42986538.91 | 0.00 | 76042941.72 | 0.00 | 0.36 |
| Annual Sum or Average | 0.303148E+09 | 0.158059E+11 | 0.00 | 11952962.62 | 0.188491E+09 | 0.00 | 0.427266E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 30949694.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 0.104069E+09 | 0.307691E+10 | 0.00 | 3250362.19 | 42986538.91 | 0.00 | 0.170831E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 78854144.57 | 43272123.01 | 0.00 | 6046551.16 | 26584286.70 | 0.00 | 0.173918E+09 | 0.00 | 0.36 |
| February | 51637398.82 | 0.139504E+09 | 0.00 | 3894791.09 | 28552161.92 | 0.00 | 86424253.08 | 0.00 | 0.36 |
| March | 41710581.59 | 0.296882E+09 | 0.00 | 2798789.04 | 20613779.32 | 0.00 | 62594571.49 | 0.00 | 0.36 |
| April | 20182406.46 | 0.714459E+09 | 0.00 | 965228.91 | 15394545.74 | 0.00 | 16745438.23 | 0.00 | 0.36 |
| May | 666301.78 | 0.143538E+10 | 0.00 | 198069.85 | 4268739.92 | 0.00 | 1434385.42 | 0.00 | 0.36 |
| June | 0.00 | 0.223879E+10 | 0.00 | 6384.10 | 1316942.57 | 0.00 | 161001.27 | 0.00 | 0.36 |
| July | 0.00 | 0.291174E+10 | 0.00 | 22921.23 | 0.00 | 0.00 | 182976.08 | 0.00 | 0.36 |
| August | 0.00 | 0.308778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.252975E+10 | 0.00 | 0.00 | 4560761.76 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 2164936.42 | 0.167691E+10 | 0.00 | 325078.74 | 12302247.43 | 0.00 | 3760776.93 | 0.00 | 0.36 |
| November | 6895374.72 | 0.765555E+09 | 0.00 | 539164.92 | 29753008.64 | 0.00 | 5054428.28 | 0.00 | 0.36 |
| December | 50396491.56 | 0.227655E+09 | 0.00 | 3560630.79 | 43425647.93 | 0.00 | 71820027.29 | 0.00 | 0.36 |
| Annual Sum or Average | 0.252508E+09 | 0.160677E+11 | 0.00 | 18357609.83 | 0.186772E+09 | 0.00 | 0.422095E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 43272123.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 78854144.57 | 0.308778E+10 | 0.00 | 6046551.16 | 43425647.93 | 0.00 | 0.173918E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.107658E+09 | 30938712.56 | 0.00 | 3393512.93 | 21071381.41 | 0.00 | 0.170105E+09 | 0.00 | 0.36 |
| February | 64623543.77 | 0.119454E+09 | 0.00 | 2673886.22 | 25367911.08 | 0.00 | 93210396.22 | 0.00 | 0.36 |
| March | 45643309.98 | 0.276284E+09 | 0.00 | 2351304.04 | 20142057.55 | 0.00 | 64097046.87 | 0.00 | 0.36 |
| April | 20682043.52 | 0.700037E+09 | 0.00 | 856701.51 | 15149652.68 | 0.00 | 16647931.43 | 0.00 | 0.36 |
| May | 627502.24 | 0.143714E+10 | 0.00 | 178934.15 | 4206659.37 | 0.00 | 1406948.06 | 0.00 | 0.36 |
| June | 0.00 | 0.224620E+10 | 0.00 | 6473.96 | 1445518.57 | 0.00 | 156474.28 | 0.00 | 0.36 |
| July | 0.00 | 0.291539E+10 | 0.00 | 21473.30 | 0.00 | 0.00 | 177379.19 | 0.00 | 0.36 |
| August | 0.00 | 0.307658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.249440E+10 | 0.00 | 0.00 | 4490815.28 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 2609033.11 | 0.162444E+10 | 0.00 | 206454.05 | 13191207.37 | 0.00 | 3054272.93 | 0.00 | 0.36 |
| November | 8002969.93 | 0.702281E+09 | 0.00 | 370702.86 | 34922582.81 | 0.00 | 6070851.93 | 0.00 | 0.36 |
| December | 60074424.23 | 0.184619E+09 | 0.00 | 2328113.61 | 41296977.25 | 0.00 | 76679866.27 | 0.00 | 0.36 |
| Annual Sum or Average | 0.309921E+09 | 0.158078E+11 | 0.00 | 12387556.63 | 0.181285E+09 | 0.00 | 0.431606E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 30938712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 0.107658E+09 | 0.307658E+10 | 0.00 | 3393512.93 | 41296977.25 | 0.00 | 0.170105E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 90907557.30 | 29782471.58 | 0.00 | 4171855.37 | 23205468.01 | 0.00 | 0.174192E+09 | 0.00 | 0.36 |
| February | 61365388.46 | 0.118589E+09 | 0.00 | 2974976.98 | 26453715.94 | 0.00 | 85173252.15 | 0.00 | 0.36 |
| March | 45711882.98 | 0.268694E+09 | 0.00 | 2464965.43 | 21641547.47 | 0.00 | 62159837.73 | 0.00 | 0.36 |
| April | 20912505.34 | 0.679825E+09 | 0.00 | 793755.67 | 16743913.97 | 0.00 | 17057903.23 | 0.00 | 0.36 |
| May | 739508.90 | 0.139254E+10 | 0.00 | 187493.15 | 4377721.31 | 0.00 | 1678110.43 | 0.00 | 0.36 |
| June | 0.00 | 0.218122E+10 | 0.00 | 9067.41 | 1060655.84 | 0.00 | 202877.98 | 0.00 | 0.36 |
| July | 0.00 | 0.283359E+10 | 0.00 | 24667.30 | 0.00 | 0.00 | 279275.33 | 0.00 | 0.36 |
| August | 0.00 | 0.298716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.242038E+10 | 0.00 | 0.00 | 4312565.32 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 2782555.51 | 0.157423E+10 | 0.00 | 184576.27 | 13316401.00 | 0.00 | 3392130.14 | 0.00 | 0.36 |
| November | 7556755.20 | 0.683729E+09 | 0.00 | 367345.47 | 36477820.85 | 0.00 | 5760741.90 | 0.00 | 0.36 |
| December | 57278143.01 | 0.184814E+09 | 0.00 | 2744587.48 | 43028966.08 | 0.00 | 70481997.94 | 0.00 | 0.36 |
| Annual Sum or Average | 0.287254E+09 | 0.153546E+11 | 0.00 | 13923290.53 | 0.190619E+09 | 0.00 | 0.420378E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 29782471.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 90907557.30 | 0.298716E+10 | 0.00 | 4171855.37 | 43028966.08 | 0.00 | 0.174192E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 90895426.52 | 29825096.61 | 0.00 | 4177905.59 | 23203386.70 | 0.00 | 0.174175E+09 | 0.00 | 0.36 |
| February | 61495559.24 | 0.118668E+09 | 0.00 | 2982321.92 | 26448395.12 | 0.00 | 85149152.70 | 0.00 | 0.36 |
| March | 45662783.49 | 0.268776E+09 | 0.00 | 2460796.60 | 21645548.68 | 0.00 | 62110791.79 | 0.00 | 0.36 |
| April | 20913700.78 | 0.680084E+09 | 0.00 | 795157.14 | 16713355.22 | 0.00 | 17048067.02 | 0.00 | 0.36 |
| May | 740250.77 | 0.139272E+10 | 0.00 | 187390.65 | 4376748.63 | 0.00 | 1675657.75 | 0.00 | 0.36 |
| June | 0.00 | 0.218129E+10 | 0.00 | 9059.67 | 1109956.33 | 0.00 | 203070.50 | 0.00 | 0.36 |
| July | 0.00 | 0.283374E+10 | 0.00 | 24617.76 | 0.00 | 0.00 | 279252.75 | 0.00 | 0.36 |
| August | 0.00 | 0.298733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.242051E+10 | 0.00 | 0.00 | 4312136.63 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 2783106.05 | 0.157450E+10 | 0.00 | 185395.18 | 13315518.14 | 0.00 | 3387369.42 | 0.00 | 0.36 |
| November | 7558577.37 | 0.684058E+09 | 0.00 | 367841.28 | 36469123.30 | 0.00 | 5754849.21 | 0.00 | 0.36 |
| December | 57356090.22 | 0.184935E+09 | 0.00 | 2747674.10 | 43023817.84 | 0.00 | 70465757.94 | 0.00 | 0.36 |
| Annual Sum or Average | 0.287405E+09 | 0.153564E+11 | 0.00 | 13938159.88 | 0.190618E+09 | 0.00 | 0.420249E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 29825096.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 90895426.52 | 0.298733E+10 | 0.00 | 4177905.59 | 43023817.84 | 0.00 | 0.174175E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 71815047.42 | 44029687.64 | 0.00 | 6917745.14 | 27630523.53 | 0.00 | 0.172715E+09 | 0.00 | 0.36 |
| February | 49358687.57 | 0.141379E+09 | 0.00 | 4244294.80 | 29947140.98 | 0.00 | 80748261.97 | 0.00 | 0.36 |
| March | 41194724.59 | 0.293085E+09 | 0.00 | 2949793.54 | 21861418.26 | 0.00 | 61532289.31 | 0.00 | 0.36 |
| April | 20882116.13 | 0.698265E+09 | 0.00 | 878191.47 | 16605840.87 | 0.00 | 16637783.13 | 0.00 | 0.36 |
| May | 738321.92 | 0.139120E+10 | 0.00 | 200587.31 | 4405263.73 | 0.00 | 1798412.69 | 0.00 | 0.36 |
| June | 0.00 | 0.217108E+10 | 0.00 | 8905.28 | 1210621.47 | 0.00 | 212563.45 | 0.00 | 0.36 |
| July | 0.00 | 0.282929E+10 | 0.00 | 24641.51 | 0.00 | 0.00 | 288251.50 | 0.00 | 0.36 |
| August | 0.00 | 0.300358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.246860E+10 | 0.00 | 0.00 | 4488017.63 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 2318845.66 | 0.164199E+10 | 0.00 | 295982.77 | 12720371.93 | 0.00 | 3980754.11 | 0.00 | 0.36 |
| November | 6568124.07 | 0.756469E+09 | 0.00 | 506857.70 | 32297448.96 | 0.00 | 4665552.85 | 0.00 | 0.36 |
| December | 48744020.43 | 0.231575E+09 | 0.00 | 3955467.30 | 45112269.84 | 0.00 | 66851456.95 | 0.00 | 0.36 |
| Annual Sum or Average | 0.241620E+09 | 0.156705E+11 | 0.00 | 19982466.83 | 0.196279E+09 | 0.00 | 0.409430E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 44029687.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 71815047.42 | 0.300358E+10 | 0.00 | 6917745.14 | 45112269.84 | 0.00 | 0.172715E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 72299485.06 | 43781372.04 | 0.00 | 6940517.92 | 27438988.53 | 0.00 | 0.173442E+09 | 0.00 | 0.36 |
| February | 49651868.23 | 0.140683E+09 | 0.00 | 4264473.24 | 29801684.86 | 0.00 | 81341972.30 | 0.00 | 0.36 |
| March | 41385243.77 | 0.292000E+09 | 0.00 | 2959876.71 | 21661020.00 | 0.00 | 62047789.90 | 0.00 | 0.36 |
| April | 20982870.16 | 0.696400E+09 | 0.00 | 885163.91 | 16527776.35 | 0.00 | 16840544.70 | 0.00 | 0.36 |
| May | 749504.78 | 0.138836E+10 | 0.00 | 209087.20 | 4384906.01 | 0.00 | 1849733.11 | 0.00 | 0.36 |
| June | 0.00 | 0.216805E+10 | 0.00 | 8897.58 | 1250348.35 | 0.00 | 216377.46 | 0.00 | 0.36 |
| July | 0.00 | 0.282612E+10 | 0.00 | 26047.52 | 0.00 | 0.00 | 297498.03 | 0.00 | 0.36 |
| August | 0.00 | 0.300037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.246554E+10 | 0.00 | 0.00 | 4476570.51 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 2336622.29 | 0.163914E+10 | 0.00 | 297283.71 | 12680483.78 | 0.00 | 4016043.30 | 0.00 | 0.36 |
| November | 6580969.74 | 0.754304E+09 | 0.00 | 515566.33 | 32020953.74 | 0.00 | 4827819.44 | 0.00 | 0.36 |
| December | 49033236.77 | 0.230716E+09 | 0.00 | 3975870.41 | 44736728.21 | 0.00 | 67388020.78 | 0.00 | 0.36 |
| Annual Sum or Average | 0.243020E+09 | 0.156455E+11 | 0.00 | 20082784.53 | 0.194979E+09 | 0.00 | 0.412268E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 43781372.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 72299485.06 | 0.300037E+10 | 0.00 | 6940517.92 | 44736728.21 | 0.00 | 0.173442E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.102184E+09 | 19396802.31 | 0.00 | 1960826.67 | 12143678.27 | 0.00 | 39162477.36 | 0.00 | 0.36 |
| February | 58766092.98 | 63606853.46 | 0.00 | 1408820.63 | 13173789.64 | 0.00 | 26100569.67 | 0.00 | 0.36 |
| March | 30573806.04 | 0.143414E+09 | 0.00 | 1049268.51 | 10391395.78 | 0.00 | 29604557.03 | 0.00 | 0.36 |
| April | 12284753.46 | 0.348356E+09 | 0.00 | 377491.45 | 6706761.22 | 0.00 | 10360673.13 | 0.00 | 0.36 |
| May | 493824.96 | 0.713037E+09 | 0.00 | 93481.34 | 1757996.55 | 0.00 | 990910.91 | 0.00 | 0.36 |
| June | 0.00 | 0.111808E+10 | 0.00 | 2852.66 | 591889.39 | 0.00 | 86434.08 | 0.00 | 0.36 |
| July | 0.00 | 0.146307E+10 | 0.00 | 9503.17 | 0.00 | 0.00 | 89927.05 | 0.00 | 0.36 |
| August | 0.00 | 0.155001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.125895E+10 | 0.00 | 0.00 | 2145126.81 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1331593.02 | 0.819850E+09 | 0.00 | 141046.89 | 5414290.31 | 0.00 | 1828189.65 | 0.00 | 0.36 |
| November | 5621585.24 | 0.366102E+09 | 0.00 | 232637.00 | 12236614.44 | 0.00 | 3719537.20 | 0.00 | 0.36 |
| December | 49982520.80 | 0.105006E+09 | 0.00 | 1255028.68 | 21159640.60 | 0.00 | 27844184.99 | 0.00 | 0.36 |
| Annual Sum or Average | 0.261239E+09 | 0.796888E+10 | 0.00 | 6530957.00 | 85721183.02 | 0.00 | 0.139787E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 19396802.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 0.102184E+09 | 0.155001E+10 | 0.00 | 1960826.67 | 21159640.60 | 0.00 | 39162477.36 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NW APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.119885E+09 | 13818313.56 | 0.00 | 866930.07 | 10026441.94 | 0.00 | 28743386.41 | 0.00 | 0.36 |
| February | 70362824.30 | 54850039.80 | 0.00 | 858045.38 | 11543721.96 | 0.00 | 23911580.69 | 0.00 | 0.36 |
| March | 34531034.17 | 0.133910E+09 | 0.00 | 864059.01 | 9844496.54 | 0.00 | 28710372.04 | 0.00 | 0.36 |
| April | 12674514.46 | 0.341898E+09 | 0.00 | 325880.90 | 6754696.99 | 0.00 | 10326294.21 | 0.00 | 0.36 |
| May | 492343.24 | 0.714138E+09 | 0.00 | 87395.98 | 1676515.81 | 0.00 | 926148.68 | 0.00 | 0.36 |
| June | 0.00 | 0.112127E+10 | 0.00 | 2863.07 | 644066.20 | 0.00 | 85343.56 | 0.00 | 0.36 |
| July | 0.00 | 0.146460E+10 | 0.00 | 9274.31 | 0.00 | 0.00 | 88834.22 | 0.00 | 0.36 |
| August | 0.00 | 0.154554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.124457E+10 | 0.00 | 0.00 | 2100665.08 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1656288.95 | 0.796798E+09 | 0.00 | 88651.89 | 5999568.85 | 0.00 | 1508786.47 | 0.00 | 0.36 |
| November | 6812968.54 | 0.336635E+09 | 0.00 | 132364.92 | 15115320.74 | 0.00 | 3951022.99 | 0.00 | 0.36 |
| December | 61654650.07 | 86266018.87 | 0.00 | 695628.74 | 19927433.38 | 0.00 | 22805567.39 | 0.00 | 0.36 |
| Annual Sum or Average | 0.308069E+09 | 0.785429E+10 | 0.00 | 3931094.26 | 83632927.49 | 0.00 | 0.121057E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 13818313.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 0.119885E+09 | 0.154554E+10 | 0.00 | 866930.07 | 19927433.38 | 0.00 | 28743386.41 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.104228E+09 | 19593426.88 | 0.00 | 2053511.45 | 12009461.79 | 0.00 | 39601812.38 | 0.00 | 0.36 |
| February | 60540977.27 | 63451450.44 | 0.00 | 1469591.36 | 12747850.21 | 0.00 | 26285871.37 | 0.00 | 0.36 |
| March | 31774763.09 | 0.143039E+09 | 0.00 | 1067413.93 | 9803999.28 | 0.00 | 29639981.69 | 0.00 | 0.36 |
| April | 12065265.52 | 0.348835E+09 | 0.00 | 437031.94 | 5704324.02 | 0.00 | 10960447.32 | 0.00 | 0.36 |
| May | 508800.37 | 0.713348E+09 | 0.00 | 103101.96 | 1484110.50 | 0.00 | 956292.52 | 0.00 | 0.36 |
| June | 0.00 | 0.111835E+10 | 0.00 | 3479.59 | 672883.50 | 0.00 | 89381.66 | 0.00 | 0.36 |
| July | 0.00 | 0.146319E+10 | 0.00 | 10374.59 | 0.00 | 0.00 | 94271.02 | 0.00 | 0.36 |
| August | 0.00 | 0.155031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.125938E+10 | 0.00 | 0.00 | 1979999.02 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1224609.93 | 0.822819E+09 | 0.00 | 167802.02 | 4870580.60 | 0.00 | 1929800.87 | 0.00 | 0.36 |
| November | 5835378.43 | 0.367827E+09 | 0.00 | 249222.13 | 10899424.31 | 0.00 | 3852814.21 | 0.00 | 0.36 |
| December | 51508638.56 | 0.105200E+09 | 0.00 | 1307613.23 | 20214823.95 | 0.00 | 28126513.36 | 0.00 | 0.36 |
| Annual Sum or Average | 0.267687E+09 | 0.797534E+10 | 0.00 | 6869142.20 | 80387457.18 | 0.00 | 0.141537E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 19593426.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 0.104228E+09 | 0.155031E+10 | 0.00 | 2053511.45 | 20214823.95 | 0.00 | 39601812.38 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NE APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.122118E+09 | 14160195.99 | 0.00 | 906446.19 | 9333086.01 | 0.00 | 28529111.56 | 0.00 | 0.36 |
| February | 72403544.49 | 54931178.08 | 0.00 | 877786.82 | 10820120.17 | 0.00 | 24119379.18 | 0.00 | 0.36 |
| March | 35621288.37 | 0.133557E+09 | 0.00 | 894169.18 | 9059751.16 | 0.00 | 29053630.08 | 0.00 | 0.36 |
| April | 12535758.84 | 0.342284E+09 | 0.00 | 380453.12 | 5705227.91 | 0.00 | 10960809.26 | 0.00 | 0.36 |
| May | 478077.57 | 0.714103E+09 | 0.00 | 93714.30 | 1459004.17 | 0.00 | 942373.39 | 0.00 | 0.36 |
| June | 0.00 | 0.112123E+10 | 0.00 | 3212.18 | 650182.52 | 0.00 | 88416.39 | 0.00 | 0.36 |
| July | 0.00 | 0.146435E+10 | 0.00 | 10000.55 | 0.00 | 0.00 | 93671.66 | 0.00 | 0.36 |
| August | 0.00 | 0.154557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.124483E+10 | 0.00 | 0.00 | 2000943.55 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1419975.72 | 0.800565E+09 | 0.00 | 107890.65 | 5330290.88 | 0.00 | 1738382.61 | 0.00 | 0.36 |
| November | 7148245.04 | 0.339740E+09 | 0.00 | 148292.03 | 12405341.49 | 0.00 | 4003402.91 | 0.00 | 0.36 |
| December | 63953369.87 | 86546762.04 | 0.00 | 712321.15 | 17661546.14 | 0.00 | 22705404.18 | 0.00 | 0.36 |
| Annual Sum or Average | 0.315678E+09 | 0.786186E+10 | 0.00 | 4134286.18 | 74425493.99 | 0.00 | 0.122235E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 14160195.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 0.122118E+09 | 0.154557E+10 | 0.00 | 906446.19 | 17661546.14 | 0.00 | 29053630.08 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 96513873.41 | 13915615.88 | 0.00 | 1105815.36 | 9733562.40 | 0.00 | 52897817.06 | 0.00 | 0.36 |
| February | 46126062.05 | 55489018.17 | 0.00 | 989652.83 | 11329100.50 | 0.00 | 45480090.75 | 0.00 | 0.36 |
| March | 25419574.00 | 0.131208E+09 | 0.00 | 968920.96 | 9780712.02 | 0.00 | 36675169.63 | 0.00 | 0.36 |
| April | 12269653.84 | 0.335878E+09 | 0.00 | 357773.93 | 6913538.26 | 0.00 | 10420611.95 | 0.00 | 0.36 |
| May | 508846.82 | 0.698590E+09 | 0.00 | 96681.00 | 1791147.45 | 0.00 | 1063626.51 | 0.00 | 0.36 |
| June | 0.00 | 0.109940E+10 | 0.00 | 4142.20 | 629022.03 | 0.00 | 107463.24 | 0.00 | 0.36 |
| July | 0.00 | 0.143637E+10 | 0.00 | 12580.15 | 0.00 | 0.00 | 135209.28 | 0.00 | 0.36 |
| August | 0.00 | 0.151462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.121944E+10 | 0.00 | 0.00 | 2058266.60 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1712130.33 | 0.782245E+09 | 0.00 | 91595.58 | 6165258.77 | 0.00 | 1667907.17 | 0.00 | 0.36 |
| November | 5096459.16 | 0.331466E+09 | 0.00 | 165912.13 | 15960017.06 | 0.00 | 4643065.53 | 0.00 | 0.36 |
| December | 41668623.48 | 85902963.45 | 0.00 | 886836.86 | 19093281.33 | 0.00 | 38527698.22 | 0.00 | 0.36 |
| Annual Sum or Average | 0.229315E+09 | 0.770452E+10 | 0.00 | 4679911.01 | 83453906.41 | 0.00 | 0.191619E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 13915615.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 96513873.41 | 0.151462E+10 | 0.00 | 1105815.36 | 19093281.33 | 0.00 | 52897817.06 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 96750731.02 | 13927964.76 | 0.00 | 1110092.18 | 9724839.84 | 0.00 | 52756078.92 | 0.00 | 0.36 |
| February | 46835260.49 | 55586005.47 | 0.00 | 991782.19 | 11237595.34 | 0.00 | 44942665.67 | 0.00 | 0.36 |
| March | 25436320.74 | 0.131298E+09 | 0.00 | 968054.88 | 9758236.13 | 0.00 | 36712115.05 | 0.00 | 0.36 |
| April | 12273950.44 | 0.336008E+09 | 0.00 | 359738.95 | 6901275.58 | 0.00 | 10424938.88 | 0.00 | 0.36 |
| May | 508778.23 | 0.698711E+09 | 0.00 | 96550.29 | 1777730.07 | 0.00 | 1059341.15 | 0.00 | 0.36 |
| June | 0.00 | 0.109948E+10 | 0.00 | 4136.28 | 629281.39 | 0.00 | 107632.74 | 0.00 | 0.36 |
| July | 0.00 | 0.143647E+10 | 0.00 | 12550.50 | 0.00 | 0.00 | 135185.24 | 0.00 | 0.36 |
| August | 0.00 | 0.151473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.121952E+10 | 0.00 | 0.00 | 2057696.98 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1713401.83 | 0.782437E+09 | 0.00 | 91666.82 | 6163277.50 | 0.00 | 1663944.92 | 0.00 | 0.36 |
| November | 5100870.57 | 0.331717E+09 | 0.00 | 166831.99 | 15924498.65 | 0.00 | 4643147.88 | 0.00 | 0.36 |
| December | 41740678.18 | 85983686.46 | 0.00 | 882958.64 | 19091604.87 | 0.00 | 38562341.91 | 0.00 | 0.36 |
| Annual Sum or Average | 0.230360E+09 | 0.770587E+10 | 0.00 | 4684362.73 | 83266036.36 | 0.00 | 0.191007E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 13927964.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 96750731.02 | 0.151473E+10 | 0.00 | 1110092.18 | 19091604.87 | 0.00 | 52756078.92 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S1 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 62521584.08 | 19900018.03 | 0.00 | 2421941.03 | 12608732.37 | 0.00 | 78015869.15 | 0.00 | 0.36 |
| February | 33739118.87 | 65203647.15 | 0.00 | 1626397.15 | 13533656.27 | 0.00 | 47211265.10 | 0.00 | 0.36 |
| March | 22794760.47 | 0.142310E+09 | 0.00 | 1187490.42 | 10435572.11 | 0.00 | 36037149.75 | 0.00 | 0.36 |
| April | 12008389.06 | 0.343800E+09 | 0.00 | 403175.12 | 7090418.54 | 0.00 | 10316265.57 | 0.00 | 0.36 |
| May | 512348.44 | 0.697494E+09 | 0.00 | 101501.19 | 1841807.33 | 0.00 | 1138769.48 | 0.00 | 0.36 |
| June | 0.00 | 0.109525E+10 | 0.00 | 4121.19 | 554699.82 | 0.00 | 109970.10 | 0.00 | 0.36 |
| July | 0.00 | 0.143450E+10 | 0.00 | 12646.40 | 0.00 | 0.00 | 137448.02 | 0.00 | 0.36 |
| August | 0.00 | 0.152081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.123841E+10 | 0.00 | 0.00 | 2110873.18 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1234608.86 | 0.810881E+09 | 0.00 | 148320.29 | 5429624.00 | 0.00 | 2150414.41 | 0.00 | 0.36 |
| November | 4292409.34 | 0.366453E+09 | 0.00 | 247668.33 | 12280008.32 | 0.00 | 4121195.93 | 0.00 | 0.36 |
| December | 30364906.05 | 0.107427E+09 | 0.00 | 1542716.84 | 21229746.47 | 0.00 | 42032104.85 | 0.00 | 0.36 |
| Annual Sum or Average | 0.167468E+09 | 0.784244E+10 | 0.00 | 7695977.94 | 87115138.41 | 0.00 | 0.221270E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 19900018.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 62521584.08 | 0.152081E+10 | 0.00 | 2421941.03 | 21229746.47 | 0.00 | 78015869.15 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S2 APARTMENT
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 62960590.40 | 19941920.32 | 0.00 | 2418896.16 | 12617253.33 | 0.00 | 77442255.89 | 0.00 | 0.36 |
| February | 33911988.92 | 65238675.55 | 0.00 | 1631717.41 | 13515981.31 | 0.00 | 47146893.24 | 0.00 | 0.36 |
| March | 22834273.81 | 0.142332E+09 | 0.00 | 1185526.21 | 10399777.16 | 0.00 | 36052069.31 | 0.00 | 0.36 |
| April | 12012423.48 | 0.343960E+09 | 0.00 | 404955.80 | 7029505.54 | 0.00 | 10318784.57 | 0.00 | 0.36 |
| May | 513569.92 | 0.697593E+09 | 0.00 | 101541.46 | 1839740.33 | 0.00 | 1135640.34 | 0.00 | 0.36 |
| June | 0.00 | 0.109533E+10 | 0.00 | 4115.27 | 554804.59 | 0.00 | 110146.70 | 0.00 | 0.36 |
| July | 0.00 | 0.143461E+10 | 0.00 | 12616.76 | 0.00 | 0.00 | 137429.82 | 0.00 | 0.36 |
| August | 0.00 | 0.152092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.123848E+10 | 0.00 | 0.00 | 2110379.78 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 1235180.10 | 0.811029E+09 | 0.00 | 149137.22 | 5428216.49 | 0.00 | 2147500.63 | 0.00 | 0.36 |
| November | 4297239.75 | 0.366659E+09 | 0.00 | 248267.57 | 12212491.51 | 0.00 | 4119755.39 | 0.00 | 0.36 |
| December | 30415988.60 | 0.107461E+09 | 0.00 | 1543847.16 | 21251716.80 | 0.00 | 42047052.87 | 0.00 | 0.36 |
| Annual Sum or Average | 0.168181E+09 | 0.784354E+10 | 0.00 | 7700621.01 | 86959866.85 | 0.00 | 0.220658E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 19941920.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 62960590.40 | 0.152092E+10 | 0.00 | 2418896.16 | 21251716.80 | 0.00 | 77442255.89 | 0.00 | 0.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:23
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.771067E+11 | 0.639829E+10 | 0.00 | 0.783115E+09 | 0.461003E+11 |
| February | 0.823214E+11 | 0.449723E+10 | 0.00 | 0.498137E+09 | 0.593660E+11 |
| March | 0.958107E+11 | 0.262712E+10 | 0.00 | 0.305313E+09 | 0.918683E+11 |
| April | 0.958467E+11 | -811653944.3 | 0.00 | -75167670.1 | 0.129114E+12 |
| May | 0.945158E+11 | -0.423769E+10 | 0.00 | -834926355.2 | 0.193680E+12 |
| June | 0.882089E+11 | -0.725415E+10 | 0.00 | -0.151604E+10 | 0.224364E+12 |
| July | 0.870597E+11 | -0.919654E+10 | 0.00 | -0.227423E+10 | 0.265892E+12 |
| August | 0.867418E+11 | -0.985210E+10 | 0.00 | -0.255601E+10 | 0.277406E+12 |
| September | 0.801606E+11 | -0.728296E+10 | 0.00 | -0.173475E+10 | 0.233822E+12 |
| October | 0.723079E+11 | -0.376389E+10 | 0.00 | -958276778.6 | 0.193751E+12 |
| November | 0.626277E+11 | -597917173.5 | 0.00 | -136818083.0 | 0.132886E+12 |
| December | 0.663573E+11 | 0.398786E+10 | 0.00 | 0.525685E+09 | 0.729995E+11 |
| Annual Sum or Average | 0.989065E+12 | -0.254864E+11 | 0.00 | -0.797397E+10 | 0.192125E+13 |
| Minimum of Months | 0.626277E+11 | -0.985210E+10 | 0.00 | -0.255601E+10 | 0.461003E+11 |
| Maximum of Months | 0.958467E+11 | 0.639829E+10 | 0.00 | 0.783115E+09 | 0.277406E+12 |