Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:38

Tabular Output Report in Format: HTML

Building: OutPatientHealthCare

Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2024-07-03 12:39:14


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 4619.80 1214.45 1214.45
Net Site Energy 4619.80 1214.45 1214.45
Total Source Energy 13631.73 3583.52 3583.52
Net Source Energy 13631.73 3583.52 3583.52


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3804.01
Net Conditioned Building Area 3804.01
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.01 197.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1415.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 626.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 237.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1341.24 188.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 517.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 93.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 478.85
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 4140.12 479.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 479.15
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 197.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1415.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 626.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 237.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 135.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 15.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 1190.14 188.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 517.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 478.85
  Water Heater 0.00 93.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.01 197.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1415.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 626.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 237.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1341.24 188.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 517.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 93.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 478.85
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 227.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 508.66 76.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.13
Other 352.59 49.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 1088.36 126.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.13


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 227.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 508.66 76.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.13
Other 352.59 49.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 1088.36 126.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.13


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 4140.119 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 4140.119 100.00
     
Total On-Site and Utility Electric Sources 4140.119 100.00
Total Electricity End Uses 4140.119 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 479.15 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 479.15 100.00
Total Water End Uses 479.15 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 339.83
Time Setpoint Not Met During Occupied Cooling 2557.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 3725.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OUTPATIENTHEALTHCARE

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

ZoneHeatingSummaryMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

ZoneElectricSummaryMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

SpaceGainsMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

PeakSpaceGainsMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

SpaceGainComponentsAtCoolingPeakMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

ComfortReportSimple55Monthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

OccupantComfortDataSummaryMonthly

| FLOOR 1 ANESTHESIA PEOPLE | FLOOR 1 CAFE PEOPLE | FLOOR 1 CLEAN PEOPLE | FLOOR 1 CLEAN WORK PEOPLE | FLOOR 1 DICTATION PEOPLE | FLOOR 1 DRESSING ROOM PEOPLE | FLOOR 1 HUMID PEOPLE | FLOOR 1 IT ROOM PEOPLE | FLOOR 1 LOBBY PEOPLE | FLOOR 1 LOCKER ROOM PEOPLE | FLOOR 1 LOUNGE PEOPLE | FLOOR 1 MRI CONTROL ROOM PEOPLE | FLOOR 1 MRI ROOM PEOPLE | FLOOR 1 NOURISHMENT PEOPLE | FLOOR 1 NURSE STATION PEOPLE | FLOOR 1 OFFICE PEOPLE | FLOOR 1 OPERATING ROOM 1 PEOPLE | FLOOR 1 OPERATING ROOM 2 PEOPLE | FLOOR 1 OPERATING ROOM 3 PEOPLE | FLOOR 1 PACU PEOPLE | FLOOR 1 PRE-OP ROOM 1 PEOPLE | FLOOR 1 PRE-OP ROOM 2 PEOPLE | FLOOR 1 PROCEDURE ROOM PEOPLE | FLOOR 1 RECEPTION PEOPLE | FLOOR 1 RECOVERY ROOM PEOPLE | FLOOR 1 SCHEDULING PEOPLE | FLOOR 1 SOIL PEOPLE | FLOOR 1 SOIL HOLD PEOPLE | FLOOR 1 SOIL WORK PEOPLE | FLOOR 1 STEP DOWN PEOPLE | FLOOR 2 CONFERENCE PEOPLE | FLOOR 2 DICTATION PEOPLE | FLOOR 2 EXAM 1 PEOPLE | FLOOR 2 EXAM 2 PEOPLE | FLOOR 2 EXAM 3 PEOPLE | FLOOR 2 EXAM 4 PEOPLE | FLOOR 2 EXAM 5 PEOPLE | FLOOR 2 EXAM 6 PEOPLE | FLOOR 2 EXAM 7 PEOPLE | FLOOR 2 EXAM 8 PEOPLE | FLOOR 2 EXAM 9 PEOPLE | FLOOR 2 LOUNGE PEOPLE | FLOOR 2 NURSE STATION 1 PEOPLE | FLOOR 2 NURSE STATION 2 PEOPLE | FLOOR 2 OFFICE PEOPLE | FLOOR 2 RECEPTION PEOPLE | FLOOR 2 SCHEDULING 1 PEOPLE | FLOOR 2 SCHEDULING 2 PEOPLE | FLOOR 2 WORK PEOPLE | FLOOR 2 X-RAY PEOPLE | FLOOR 3 DRESSING ROOM PEOPLE | FLOOR 3 HUMID PEOPLE | FLOOR 3 LOCKER PEOPLE | FLOOR 3 LOUNGE PEOPLE | FLOOR 3 OFFICE PEOPLE | FLOOR 3 PHYSICAL THERAPY 1 PEOPLE | FLOOR 3 PHYSICAL THERAPY 2 PEOPLE | FLOOR 3 TREATMENT PEOPLE | FLOOR 3 WORK PEOPLE | FLOOR 2 STORAGE 1 PEOPLE | FLOOR 2 STORAGE 2 PEOPLE | FLOOR 2 STORAGE 3 PEOPLE | FLOOR 2 UTILITY PEOPLE | FLOOR 3 ELEVATOR HALL PEOPLE | FLOOR 3 JANITOR PEOPLE | FLOOR 3 LOUNGE TOILET PEOPLE | FLOOR 3 MECHANICAL PEOPLE | FLOOR 3 MECHANICAL HALL PEOPLE | FLOOR 3 OFFICE HALL PEOPLE | FLOOR 3 OFFICE TOILET PEOPLE | FLOOR 3 PHYSICAL THERAPY TOILET PEOPLE | FLOOR 3 STORAGE 1 PEOPLE | FLOOR 3 STORAGE 2 PEOPLE | FLOOR 3 UNDEVELOPED 1 PEOPLE | FLOOR 3 UNDEVELOPED 2 PEOPLE | FLOOR 3 UTILITY PEOPLE | NE STAIR PEOPLE | NW ELEVATOR PEOPLE | NW STAIR PEOPLE | SW STAIR PEOPLE | FLOOR 1 ELECTRICAL ROOM PEOPLE | FLOOR 1 ELEVATOR PUMP ROOM PEOPLE | FLOOR 1 IT HALL PEOPLE | FLOOR 1 LOBBY HALL PEOPLE | FLOOR 1 LOBBY TOILET PEOPLE | FLOOR 1 LOCKER ROOM HALL PEOPLE | FLOOR 1 MED GAS PEOPLE | FLOOR 1 MRI HALL PEOPLE | FLOOR 1 MRI TOILET PEOPLE | FLOOR 1 NURSE HALL PEOPLE | FLOOR 1 NURSE JANITOR PEOPLE | FLOOR 1 NURSE TOILET PEOPLE | FLOOR 1 PRE-OP HALL PEOPLE | FLOOR 1 PRE-OP TOILET PEOPLE | FLOOR 1 RECEPTION HALL PEOPLE | FLOOR 1 SCRUB PEOPLE | FLOOR 1 STERILE HALL PEOPLE | FLOOR 1 STERILE STORAGE PEOPLE | FLOOR 1 STORAGE PEOPLE | FLOOR 1 SUB-STERILE PEOPLE | FLOOR 1 UTILITY HALL PEOPLE | FLOOR 1 UTILITY JANITOR PEOPLE | FLOOR 1 VESTIBULE PEOPLE | FLOOR 2 CONFERENCE TOILET PEOPLE | FLOOR 2 EXAM HALL 1 PEOPLE | FLOOR 2 EXAM HALL 2 PEOPLE | FLOOR 2 EXAM HALL 3 PEOPLE | FLOOR 2 EXAM HALL 4 PEOPLE | FLOOR 2 EXAM HALL 5 PEOPLE | FLOOR 2 EXAM HALL 6 PEOPLE | FLOOR 2 JANITOR PEOPLE | FLOOR 2 OFFICE HALL PEOPLE | FLOOR 2 RECEPTION HALL PEOPLE | FLOOR 2 WORK HALL PEOPLE | FLOOR 2 WORK TOILET PEOPLE | FLOOR 2 RECEPTION TOILET PEOPLE | FLOOR 1 BIO HAZ PEOPLE | FLOOR 1 UTILITY ROOM PEOPLE |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| AHU-1 COOLING COIL | AHU-2 COOLING COIL | AHU-3 COOLING COIL | PSZ_CAFE HP COOLING COIL | PSZ_ELEVATOR HP COOLING COIL | PSZ_MRI_CONTROL HP COOLING COIL | PSZ_MRI HP COOLING COIL | PSZ_OR_1 HP COOLING COIL | PSZ_OR_2 HP COOLING COIL | PSZ_OR_3 HP COOLING COIL | PSZ_XRAY HP COOLING COIL |

WindowReportMonthly

| 78F987 | D8037E | 4A8120 | AAE778 | 3AAD8B | 8128A9 | 9B1541 | CF850A | A6BA23 | D10D28 | 591336 | 38B811 | C044D6 | 1D94BE | 18748E | 137A56 | 8D508E | B2D381 | 1DA13A | 44E54A | 757D10 | E33BAE | 24167A | 2C0938 | 8600DD | A1ED60 | E8D997 | 88E1FC | F83F33 | B1F5EE | F52F3D | 80885D | FEEF06 | 2BE8DE | 513E2A | BA5CD9 | 1AD478 | 27F0AC | 724114 | D538C4 | 5635BC | 831C1D | 9BB95F | C0778D | 7D2D69 | 2EF63B | C417C0 | EB042B | 4C1F71 | D23C8B | B4E4BE | EEF55D | E55A57 | 93D018 | DD9F5D | 15B02B | 820282 | 9BA05A | C639E8 | A2790A | 79FCEE | EDE617 | C61F0D | 7248C5 | 29FA28 | F0B23F | EEC10E | 944FCE | C41399 | 95BA33 | F27282 | 3DB407 | 3DADE2 | DF3E2C | 5031C8 | C087D0 | D2CA75 | B0FB49 | FE9BC9 | 9DF7DE | D0BE44 | 6B5226 | 8F59F7 | 44F571 | 6BD844 | 86D536 | BAF71D | 3833A2 | 2111A1 | 9BC521 | 142781 | E74902 | 93BBC3 | C635A6 |

WindowEnergyReportMonthly

| 78F987 | D8037E | 4A8120 | AAE778 | 3AAD8B | 8128A9 | 9B1541 | CF850A | A6BA23 | D10D28 | 591336 | 38B811 | C044D6 | 1D94BE | 18748E | 137A56 | 8D508E | B2D381 | 1DA13A | 44E54A | 757D10 | E33BAE | 24167A | 2C0938 | 8600DD | A1ED60 | E8D997 | 88E1FC | F83F33 | B1F5EE | F52F3D | 80885D | FEEF06 | 2BE8DE | 513E2A | BA5CD9 | 1AD478 | 27F0AC | 724114 | D538C4 | 5635BC | 831C1D | 9BB95F | C0778D | 7D2D69 | 2EF63B | C417C0 | EB042B | 4C1F71 | D23C8B | B4E4BE | EEF55D | E55A57 | 93D018 | DD9F5D | 15B02B | 820282 | 9BA05A | C639E8 | A2790A | 79FCEE | EDE617 | C61F0D | 7248C5 | 29FA28 | F0B23F | EEC10E | 944FCE | C41399 | 95BA33 | F27282 | 3DB407 | 3DADE2 | DF3E2C | 5031C8 | C087D0 | D2CA75 | B0FB49 | FE9BC9 | 9DF7DE | D0BE44 | 6B5226 | 8F59F7 | 44F571 | 6BD844 | 86D536 | BAF71D | 3833A2 | 2111A1 | 9BC521 | 142781 | E74902 | 93BBC3 | C635A6 |

WindowZoneSummaryMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

WindowEnergyZoneSummaryMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| AHU-1 HEATING COIL | FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | FLOOR 1 CLEAN VAV BOX REHEAT COIL | FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | FLOOR 1 DICTATION VAV BOX REHEAT COIL | FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | FLOOR 1 HUMID VAV BOX REHEAT COIL | FLOOR 1 IT HALL VAV BOX REHEAT COIL | FLOOR 1 IT ROOM VAV BOX REHEAT COIL | FLOOR 1 LOBBY VAV BOX REHEAT COIL | FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | FLOOR 1 LOUNGE VAV BOX REHEAT COIL | FLOOR 1 MED GAS VAV BOX REHEAT COIL | FLOOR 1 MRI HALL VAV BOX REHEAT COIL | FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | FLOOR 1 OFFICE VAV BOX REHEAT COIL | FLOOR 1 PACU VAV BOX REHEAT COIL | FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | FLOOR 1 RECEPTION VAV BOX REHEAT COIL | FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | FLOOR 1 SCRUB VAV BOX REHEAT COIL | FLOOR 1 SOIL VAV BOX REHEAT COIL | FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | FLOOR 1 STORAGE VAV BOX REHEAT COIL | FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | AHU-2 HEATING COIL | FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | FLOOR 2 DICTATION VAV BOX REHEAT COIL | FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | FLOOR 2 JANITOR VAV BOX REHEAT COIL | FLOOR 2 LOUNGE VAV BOX REHEAT COIL | FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | FLOOR 2 OFFICE VAV BOX REHEAT COIL | FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | FLOOR 2 RECEPTION VAV BOX REHEAT COIL | FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | FLOOR 2 UTILITY VAV BOX REHEAT COIL | FLOOR 2 WORK VAV BOX REHEAT COIL | FLOOR 2 WORK HALL VAV BOX REHEAT COIL | FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | NE STAIR VAV BOX REHEAT COIL | NW ELEVATOR VAV BOX REHEAT COIL | NW STAIR VAV BOX REHEAT COIL | SW STAIR VAV BOX REHEAT COIL | AHU-3 HEATING COIL | FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | FLOOR 3 HUMID VAV BOX REHEAT COIL | FLOOR 3 JANITOR VAV BOX REHEAT COIL | FLOOR 3 LOCKER VAV BOX REHEAT COIL | FLOOR 3 LOUNGE VAV BOX REHEAT COIL | FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | FLOOR 3 OFFICE VAV BOX REHEAT COIL | FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | FLOOR 3 TREATMENT VAV BOX REHEAT COIL | FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | FLOOR 3 UTILITY VAV BOX REHEAT COIL | FLOOR 3 WORK VAV BOX REHEAT COIL | PSZ_CAFE HEATING COIL | PSZ_ELEVATOR HEATING COIL | PSZ_MRI_CONTROL HEATING COIL | PSZ_MRI HEATING COIL | PSZ_OR_1 HEATING COIL | PSZ_OR_2 HEATING COIL | PSZ_OR_3 HEATING COIL | PSZ_XRAY HEATING COIL | PSZ_CAFE_SUPPHEATCOIL | PSZ_ELEVATOR_SUPPHEATCOIL | PSZ_MRI_CONTROL_SUPPHEATCOIL | PSZ_MRI_SUPPHEATCOIL | PSZ_OR_1_SUPPHEATCOIL | PSZ_OR_2_SUPPHEATCOIL | PSZ_OR_3_SUPPHEATCOIL | PSZ_XRAY_SUPPHEATCOIL | AHU-1 COOLING COIL | AHU-2 COOLING COIL | AHU-3 COOLING COIL | PSZ_CAFE HP COOLING COIL | PSZ_ELEVATOR HP COOLING COIL | PSZ_MRI_CONTROL HP COOLING COIL | PSZ_MRI HP COOLING COIL | PSZ_OR_1 HP COOLING COIL | PSZ_OR_2 HP COOLING COIL | PSZ_OR_3 HP COOLING COIL | PSZ_XRAY HP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

FanReportMonthly

| AHU-1 FAN | AHU-2 FAN | AHU-3 FAN | FLOOR 1 ANESTHESIA EXHAUST FAN | FLOOR 1 LOBBY TOILET EXHAUST FAN | FLOOR 1 MRI TOILET EXHAUST FAN | FLOOR 1 NURSE TOILET EXHAUST FAN | FLOOR 1 PRE-OP TOILET EXHAUST FAN | FLOOR 1 SOIL EXHAUST FAN | FLOOR 1 SOIL HOLD EXHAUST FAN | FLOOR 1 SOIL WORK EXHAUST FAN | FLOOR 2 CONFERENCE TOILET EXHAUST FAN | FLOOR 2 RECEPTION TOILET EXHAUST FAN | FLOOR 2 WORK TOILET EXHAUST FAN | FLOOR 3 LOUNGE TOILET EXHAUST FAN | FLOOR 3 OFFICE TOILET EXHAUST FAN | FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN | FLOOR 1 MRI CONTROL ROOM EXHAUST FAN | FLOOR 1 MRI ROOM EXHAUST FAN | FLOOR 2 X-RAY EXHAUST FAN | PSZ_CAFE_ADDAQ FAN | PSZ_ELEVATOR_ADDAQ FAN | PSZ_MRI_CONTROL_ADDAQ FAN | PSZ_MRI_ADDAQ FAN | PSZ_OR_1_ADDAQ FAN | PSZ_OR_2_ADDAQ FAN | PSZ_OR_3_ADDAQ FAN | PSZ_XRAY_ADDAQ FAN |

PumpReportMonthly

| HEATSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

AirLoopSystemEnergyAndWaterUseMonthly

| AHU-1 | AHU-2 | AHU-3 | PSZ_CAFE | PSZ_ELEVATOR | PSZ_MRI_CONTROL | PSZ_MRI | PSZ_OR_1 | PSZ_OR_2 | PSZ_OR_3 | PSZ_XRAY |

AirLoopSystemComponentLoadsMonthly

| AHU-1 | AHU-2 | AHU-3 | PSZ_CAFE | PSZ_ELEVATOR | PSZ_MRI_CONTROL | PSZ_MRI | PSZ_OR_1 | PSZ_OR_2 | PSZ_OR_3 | PSZ_XRAY |

AirLoopSystemComponentEnergyUseMonthly

| AHU-1 | AHU-2 | AHU-3 | PSZ_CAFE | PSZ_ELEVATOR | PSZ_MRI_CONTROL | PSZ_MRI | PSZ_OR_1 | PSZ_OR_2 | PSZ_OR_3 | PSZ_XRAY |

MechanicalVentilationLoadsMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:38
RunPeriod RUNPERIOD 1
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [m] 11.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1553.34 473.81 302.86 473.81 302.86
Above Ground Wall Area [m2] 1553.34 473.81 302.86 473.81 302.86
Window Opening Area [m2] 326.23 97.22 75.91 114.08 39.02
Gross Window-Wall Ratio [%] 21.00 20.52 25.06 24.08 12.88
Above Ground Window-Wall Ratio [%] 21.00 20.52 25.06 24.08 12.88


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1553.34 473.81 302.86 473.81 302.86
Above Ground Wall Area [m2] 1553.34 473.81 302.86 473.81 302.86
Window Opening Area [m2] 326.23 97.22 75.91 114.08 39.02
Gross Window-Wall Ratio [%] 21.00 20.52 25.06 24.08 12.88
Above Ground Window-Wall Ratio [%] 21.00 20.52 25.06 24.08 12.88


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1373.29
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
FLOOR 1 ANESTHESIA 10.03 Yes Yes 30.58 1.00 8.36 0.00 2.23 2.23 16.1458 4.64 21.5300
FLOOR 1 BIO HAZ 5.20 Yes Yes 15.86 1.00 0.00 0.00 0.00 0.00 9.6875 46.45 1.0800
FLOOR 1 CAFE 39.02 Yes Yes 118.93 1.00 18.58 0.00 8.92 8.92 9.6875 0.93 10.7600
FLOOR 1 CLEAN 11.71 Yes Yes 35.68 1.00 0.00 0.00 0.00 0.00 16.1458 4.64 21.5300
FLOOR 1 CLEAN WORK 15.33 Yes Yes 46.72 1.00 0.00 0.00 0.00 0.00 16.1458 4.64 21.5300
FLOOR 1 DICTATION 11.71 Yes Yes 35.68 1.00 0.00 0.00 0.00 0.00 11.8403 18.58 11.8400
FLOOR 1 DRESSING ROOM 4.18 Yes Yes 12.74 1.00 8.36 0.00 2.32 2.32 11.8403 18.58 11.8400
FLOOR 1 ELECTRICAL ROOM 9.10 Yes Yes 27.75 1.00 6.50 0.00 0.00 0.00 16.1458 61.94 53.8200
FLOOR 1 ELEVATOR PUMP ROOM 8.45 Yes Yes 25.77 1.00 18.58 0.00 0.00 0.00 16.1458 61.94 9511.2751
FLOOR 1 HUMID 5.02 Yes Yes 15.29 1.00 0.00 0.00 0.00 0.00 11.8403 18.58 11.8400
FLOOR 1 IT HALL 13.01 Yes Yes 39.64 1.00 0.00 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 1 IT ROOM 10.41 Yes Yes 31.71 1.00 0.00 0.00 0.00 0.00 11.8403 18.58 11.8400
FLOOR 1 LOBBY 57.79 Yes Yes 176.13 1.00 20.44 0.00 8.92 8.92 13.9931 9.29 11.8400
FLOOR 1 LOBBY HALL 22.30 Yes Yes 67.96 1.00 0.00 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 1 LOBBY TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 0.00 0.00 9.6875 18.58 4.3100
FLOOR 1 LOCKER ROOM 61.32 Yes Yes 186.89 1.00 20.44 0.00 5.57 5.57 8.6111 6.19 32.2900
FLOOR 1 LOCKER ROOM HALL 46.08 Yes Yes 140.45 1.00 0.00 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 1 LOUNGE 33.45 Yes Yes 101.94 1.00 0.00 0.00 0.00 0.00 8.6111 6.19 32.2900
FLOOR 1 MED GAS 5.20 Yes Yes 15.86 1.00 13.94 0.00 0.00 0.00 9.6875 46.45 1.0800
FLOOR 1 MRI CONTROL ROOM 15.61 Yes Yes 47.57 1.00 4.65 0.00 0.00 0.00 16.1458 4.64 107.6400
FLOOR 1 MRI HALL 13.66 Yes Yes 41.63 1.00 0.00 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 1 MRI ROOM 40.88 Yes Yes 124.59 1.00 0.00 0.00 0.00 0.00 16.1458 4.64 107.6400
FLOOR 1 MRI TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 0.00 0.00 9.6875 18.58 4.3100
FLOOR 1 NOURISHMENT 16.91 Yes Yes 51.54 1.00 0.00 0.00 0.00 0.00 10.7639 6.19 21.5300
FLOOR 1 NURSE HALL 46.08 Yes Yes 140.45 1.00 0.00 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 1 NURSE JANITOR 5.02 Yes Yes 15.29 1.00 0.00 0.00 0.00 0.00 9.6875 46.45 1.0800
FLOOR 1 NURSE STATION 24.25 Yes Yes 73.91 1.00 0.00 0.00 0.00 0.00 10.7639 6.19 21.5300
FLOOR 1 NURSE TOILET 5.02 Yes Yes 15.29 1.00 0.00 0.00 0.00 0.00 9.6875 18.58 4.3100
FLOOR 1 OFFICE 44.87 Yes Yes 136.77 1.00 0.00 0.00 0.00 0.00 11.8403 18.58 11.8400
FLOOR 1 OPERATING ROOM 1 42.74 Yes Yes 130.26 1.00 39.95 0.00 10.41 10.41 23.6806 4.64 118.3600
FLOOR 1 OPERATING ROOM 2 44.59 Yes Yes 135.92 1.00 22.30 0.00 8.93 8.93 23.6806 4.64 118.3600
FLOOR 1 OPERATING ROOM 3 44.22 Yes Yes 134.79 1.00 0.00 0.00 0.00 0.00 23.6806 4.64 118.3600
FLOOR 1 PACU 10.03 Yes Yes 30.58 1.00 0.00 0.00 0.00 0.00 8.6111 4.64 32.2900
FLOOR 1 PRE-OP HALL 49.05 Yes Yes 149.51 1.00 0.00 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 1 PRE-OP ROOM 1 17.56 Yes Yes 53.52 1.00 3.72 0.00 0.00 0.00 7.5347 9.29 21.5300
FLOOR 1 PRE-OP ROOM 2 31.40 Yes Yes 95.71 1.00 0.00 0.00 0.00 0.00 7.5347 9.29 21.5300
FLOOR 1 PRE-OP TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 0.00 0.00 9.6875 18.58 4.3100
FLOOR 1 PROCEDURE ROOM 26.48 Yes Yes 80.70 1.00 17.65 0.00 5.57 5.57 16.1458 4.64 32.2900
FLOOR 1 RECEPTION 47.29 Yes Yes 144.13 1.00 12.08 0.00 3.34 3.34 13.9931 3.10 11.8400
FLOOR 1 RECEPTION HALL 11.89 Yes Yes 36.25 1.00 0.00 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 1 RECOVERY ROOM 50.17 Yes Yes 152.91 1.00 41.81 0.00 8.92 8.92 8.6111 4.64 32.2900
FLOOR 1 SCHEDULING 11.06 Yes Yes 33.70 1.00 6.50 0.00 0.74 0.74 11.8403 18.58 11.8400
FLOOR 1 SCRUB 7.80 Yes Yes 23.79 1.00 0.00 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 1 SOIL 11.71 Yes Yes 35.68 1.00 0.00 0.00 0.00 0.00 16.1458 4.64 21.5300
FLOOR 1 SOIL HOLD 5.20 Yes Yes 15.86 1.00 0.00 0.00 0.00 0.00 16.1458 4.64 21.5300
FLOOR 1 SOIL WORK 16.72 Yes Yes 50.97 1.00 0.00 0.00 0.00 0.00 16.1458 4.64 21.5300
FLOOR 1 STEP DOWN 27.87 Yes Yes 84.95 1.00 34.37 0.00 6.69 6.69 8.6111 4.64 32.2900
FLOOR 1 STERILE HALL 57.23 Yes Yes 174.43 1.00 7.43 0.00 2.23 2.23 10.3041 18.58 4.3100
FLOOR 1 STERILE STORAGE 36.79 Yes Yes 112.13 1.00 0.00 0.00 0.00 0.00 9.6875 46.45 1.0800
FLOOR 1 STORAGE 85.47 Yes Yes 260.51 1.00 58.53 0.00 8.36 8.36 9.6875 46.45 1.0800
FLOOR 1 SUB-STERILE 18.21 Yes Yes 55.50 1.00 13.01 0.00 3.97 3.97 10.3041 18.58 4.3100
FLOOR 1 UTILITY HALL 23.78 Yes Yes 72.49 1.00 14.86 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 1 UTILITY JANITOR 3.90 Yes Yes 11.89 1.00 0.00 0.00 0.00 0.00 9.6875 46.45 1.0800
FLOOR 1 UTILITY ROOM 33.45 Yes Yes 101.94 1.00 16.72 0.00 2.98 2.98 9.6875 46.45 1.0800
FLOOR 1 VESTIBULE 6.69 Yes Yes 20.39 1.00 7.43 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 2 CONFERENCE 31.22 Yes Yes 95.14 1.00 37.16 0.00 9.67 9.67 13.9931 1.86 10.7600
FLOOR 2 CONFERENCE TOILET 5.95 Yes Yes 18.12 1.00 0.00 0.00 0.00 0.00 9.6875 18.58 4.3100
FLOOR 2 DICTATION 6.50 Yes Yes 19.82 1.00 0.00 0.00 0.00 0.00 11.8403 18.58 11.8400
FLOOR 2 EXAM 1 33.45 Yes Yes 101.94 1.00 39.02 0.00 8.92 8.92 16.1458 4.64 11.8400
FLOOR 2 EXAM 2 50.17 Yes Yes 152.91 1.00 16.72 0.00 3.72 3.72 16.1458 4.64 11.8400
FLOOR 2 EXAM 3 66.89 Yes Yes 203.88 1.00 22.30 0.00 5.95 5.95 16.1458 4.64 11.8400
FLOOR 2 EXAM 4 7.80 Yes Yes 23.79 1.00 6.50 0.00 2.23 2.23 16.1458 4.64 11.8400
FLOOR 2 EXAM 5 32.52 Yes Yes 99.11 1.00 23.23 0.00 7.94 7.94 16.1458 4.64 11.8400
FLOOR 2 EXAM 6 20.90 Yes Yes 63.71 1.00 13.94 0.00 4.18 4.18 16.1458 4.64 11.8400
FLOOR 2 EXAM 7 73.58 Yes Yes 224.27 1.00 22.30 0.00 5.57 5.57 16.1458 4.64 11.8400
FLOOR 2 EXAM 8 25.08 Yes Yes 76.46 1.00 16.72 0.00 5.57 5.57 16.1458 4.64 11.8400
FLOOR 2 EXAM 9 36.79 Yes Yes 112.13 1.00 11.15 0.00 2.79 2.79 16.1458 4.64 11.8400
FLOOR 2 EXAM HALL 1 16.72 Yes Yes 50.97 1.00 5.57 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 2 EXAM HALL 2 16.72 Yes Yes 50.97 1.00 5.57 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 2 EXAM HALL 3 16.72 Yes Yes 50.97 1.00 5.57 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 2 EXAM HALL 4 18.39 Yes Yes 56.07 1.00 5.57 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 2 EXAM HALL 5 18.39 Yes Yes 56.07 1.00 5.57 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 2 EXAM HALL 6 18.39 Yes Yes 56.07 1.00 5.57 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 2 JANITOR 5.85 Yes Yes 17.84 1.00 14.86 0.00 0.00 0.00 9.6875 46.45 1.0800
FLOOR 2 LOUNGE 7.43 Yes Yes 22.65 1.00 0.00 0.00 0.00 0.00 8.6111 6.19 32.2900
FLOOR 2 NURSE STATION 1 13.94 Yes Yes 42.48 1.00 0.00 0.00 0.00 0.00 10.7639 6.19 21.5300
FLOOR 2 NURSE STATION 2 16.72 Yes Yes 50.97 1.00 0.00 0.00 0.00 0.00 10.7639 6.19 21.5300
FLOOR 2 OFFICE 52.03 Yes Yes 158.57 1.00 37.16 0.00 11.91 11.91 11.8403 18.58 11.8400
FLOOR 2 OFFICE HALL 41.25 Yes Yes 125.73 1.00 0.00 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 2 RECEPTION 91.42 Yes Yes 278.64 1.00 45.52 0.00 16.72 16.72 13.9931 3.10 11.8400
FLOOR 2 RECEPTION HALL 52.40 Yes Yes 159.71 1.00 6.50 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 2 RECEPTION TOILET 11.71 Yes Yes 35.68 1.00 0.00 0.00 0.00 0.00 9.6875 18.58 4.3100
FLOOR 2 SCHEDULING 1 30.10 Yes Yes 91.75 1.00 0.00 0.00 0.00 0.00 11.8403 18.58 11.8400
FLOOR 2 SCHEDULING 2 31.77 Yes Yes 96.84 1.00 0.00 0.00 0.00 0.00 11.8403 18.58 11.8400
FLOOR 2 STORAGE 1 5.20 Yes Yes 15.86 1.00 0.00 0.00 0.00 0.00 9.6875 46.45 1.0800
FLOOR 2 STORAGE 2 11.15 Yes Yes 33.98 1.00 0.00 0.00 0.00 0.00 9.6875 46.45 1.0800
FLOOR 2 STORAGE 3 13.38 Yes Yes 40.78 1.00 0.00 0.00 0.00 0.00 9.6875 46.45 1.0800
FLOOR 2 UTILITY 11.71 Yes Yes 35.68 1.00 8.36 0.00 2.98 2.98 9.6875 46.45 1.0800
FLOOR 2 WORK 157.01 Yes Yes 478.55 1.00 24.15 0.00 5.57 5.57 11.8403 18.58 9.7803
FLOOR 2 WORK HALL 77.48 Yes Yes 236.16 1.00 5.57 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 2 WORK TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 0.00 0.00 9.6875 18.58 4.3100
FLOOR 2 X-RAY 83.61 Yes Yes 254.85 1.00 0.00 0.00 0.00 0.00 16.1458 4.64 107.6400
FLOOR 3 DRESSING ROOM 3.90 Yes Yes 11.89 1.00 0.00 0.00 0.00 0.00 11.8403 18.58 11.8400
FLOOR 3 ELEVATOR HALL 34.37 Yes Yes 104.77 1.00 3.72 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 3 HUMID 10.03 Yes Yes 30.58 1.00 0.00 0.00 0.00 0.00 11.8403 18.58 11.8400
FLOOR 3 JANITOR 5.85 Yes Yes 17.84 1.00 14.86 0.00 0.00 0.00 9.6875 46.45 1.0800
FLOOR 3 LOCKER 11.15 Yes Yes 33.98 1.00 0.00 0.00 0.00 0.00 8.6111 6.19 32.2900
FLOOR 3 LOUNGE 70.51 Yes Yes 214.92 1.00 21.37 0.00 5.57 5.57 8.6111 6.19 32.2900
FLOOR 3 LOUNGE TOILET 17.84 Yes Yes 54.37 1.00 11.15 0.00 4.18 4.18 9.6875 18.58 4.3100
FLOOR 3 MECHANICAL 32.52 Yes Yes 99.11 1.00 23.23 0.00 7.94 7.94 16.1458 61.94 53.8200
FLOOR 3 MECHANICAL HALL 27.87 Yes Yes 84.95 1.00 0.00 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 3 OFFICE 282.05 Yes Yes 859.70 1.00 68.75 0.00 19.51 19.51 11.8403 18.58 11.8400
FLOOR 3 OFFICE HALL 77.48 Yes Yes 236.16 1.00 5.57 0.00 0.00 0.00 10.3041 18.58 4.3100
FLOOR 3 OFFICE TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 0.00 0.00 9.6875 18.58 4.3100
FLOOR 3 PHYSICAL THERAPY 1 120.77 Yes Yes 368.12 1.00 78.97 0.00 29.73 29.73 9.6875 4.64 16.1500
FLOOR 3 PHYSICAL THERAPY 2 55.00 Yes Yes 167.64 1.00 0.00 0.00 0.00 0.00 9.6875 4.64 16.1500
FLOOR 3 PHYSICAL THERAPY TOILET 7.80 Yes Yes 23.79 1.00 0.00 0.00 0.00 0.00 9.6875 18.58 4.3100
FLOOR 3 STORAGE 1 10.03 Yes Yes 30.58 1.00 0.00 0.00 0.00 0.00 9.6875 46.45 1.0800
FLOOR 3 STORAGE 2 7.80 Yes Yes 23.79 1.00 0.00 0.00 0.00 0.00 9.6875 46.45 1.0800
FLOOR 3 TREATMENT 44.22 Yes Yes 134.79 1.00 0.00 0.00 0.00 0.00 16.1458 4.64 11.8400
FLOOR 3 UNDEVELOPED 1 210.70 Yes Yes 642.23 1.00 66.89 0.00 25.64 25.64 9.6875 46.45 11.8400
FLOOR 3 UNDEVELOPED 2 107.02 Yes Yes 326.21 1.00 52.03 0.00 13.38 13.38 9.6875 46.45 11.8400
FLOOR 3 UTILITY 20.07 Yes Yes 61.16 1.00 0.00 0.00 0.00 0.00 16.1458 46.45 1.0800
FLOOR 3 WORK 53.33 Yes Yes 162.54 1.00 38.09 0.00 11.91 11.91 11.8403 18.58 11.8400
NE STAIR 15.61 Yes Yes 142.72 1.00 97.55 0.00 12.27 12.27 10.3041 18.58 4.3100
NW ELEVATOR 13.01 Yes Yes 118.93 1.00 75.25 0.00 0.00 0.00 10.3041 61.94 4.3100
NW STAIR 17.84 Yes Yes 163.10 1.00 111.48 0.00 11.15 11.15 10.3041 18.58 4.3100
SW STAIR 8.92 Yes Yes 81.55 1.00 55.74 0.00 1.11 1.11 10.3041 18.58 4.3100
Total 3804.01     11932.15   1553.34 0.00 326.23 326.23 12.0629 8.02 40.3528
Conditioned Total 3804.01     11932.15   1553.34 0.00 326.23 326.23 12.0629 8.02 40.3528
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
FLOOR 1 ANESTHESIA 10.03 Yes Yes 1.00 FLOOR 1 ANESTHESIA GENERAL FLOOR 1 ANESTHESIA 16.1458 4.64 21.5300  
FLOOR 1 BIO HAZ 5.20 Yes Yes 1.00 FLOOR 1 BIO HAZ GENERAL FLOOR 1 BIO HAZ 9.6875 46.45 1.0800  
FLOOR 1 CAFE 39.02 Yes Yes 1.00 FLOOR 1 CAFE GENERAL FLOOR 1 CAFE 9.6875 0.93 10.7600  
FLOOR 1 CLEAN 11.71 Yes Yes 1.00 FLOOR 1 CLEAN GENERAL FLOOR 1 CLEAN 16.1458 4.64 21.5300  
FLOOR 1 CLEAN WORK 15.33 Yes Yes 1.00 FLOOR 1 CLEAN WORK GENERAL FLOOR 1 CLEAN WORK 16.1458 4.64 21.5300  
FLOOR 1 DICTATION 11.71 Yes Yes 1.00 FLOOR 1 DICTATION GENERAL FLOOR 1 DICTATION 11.8403 18.58 11.8400  
FLOOR 1 DRESSING ROOM 4.18 Yes Yes 1.00 FLOOR 1 DRESSING ROOM GENERAL FLOOR 1 DRESSING ROOM 11.8403 18.58 11.8400  
FLOOR 1 ELECTRICAL ROOM 9.10 Yes Yes 1.00 FLOOR 1 ELECTRICAL ROOM GENERAL FLOOR 1 ELECTRICAL ROOM 16.1458 61.94 53.8200  
FLOOR 1 ELEVATOR PUMP ROOM 8.45 Yes Yes 1.00 FLOOR 1 ELEVATOR PUMP ROOM GENERAL FLOOR 1 ELEVATOR PUMP ROOM 16.1458 61.94 9511.2751  
FLOOR 1 HUMID 5.02 Yes Yes 1.00 FLOOR 1 HUMID GENERAL FLOOR 1 HUMID 11.8403 18.58 11.8400  
FLOOR 1 IT HALL 13.01 Yes Yes 1.00 FLOOR 1 IT HALL GENERAL FLOOR 1 IT HALL 10.3041 18.58 4.3100  
FLOOR 1 IT ROOM 10.41 Yes Yes 1.00 FLOOR 1 IT ROOM GENERAL FLOOR 1 IT ROOM 11.8403 18.58 11.8400  
FLOOR 1 LOBBY 57.79 Yes Yes 1.00 FLOOR 1 LOBBY GENERAL FLOOR 1 LOBBY 13.9931 9.29 11.8400  
FLOOR 1 LOBBY HALL 22.30 Yes Yes 1.00 FLOOR 1 LOBBY HALL GENERAL FLOOR 1 LOBBY HALL 10.3041 18.58 4.3100  
FLOOR 1 LOBBY TOILET 5.02 Yes Yes 1.00 FLOOR 1 LOBBY TOILET GENERAL FLOOR 1 LOBBY TOILET 9.6875 18.58 4.3100  
FLOOR 1 LOCKER ROOM 61.32 Yes Yes 1.00 FLOOR 1 LOCKER ROOM GENERAL FLOOR 1 LOCKER ROOM 8.6111 6.19 32.2900  
FLOOR 1 LOCKER ROOM HALL 46.08 Yes Yes 1.00 FLOOR 1 LOCKER ROOM HALL GENERAL FLOOR 1 LOCKER ROOM HALL 10.3041 18.58 4.3100  
FLOOR 1 LOUNGE 33.45 Yes Yes 1.00 FLOOR 1 LOUNGE GENERAL FLOOR 1 LOUNGE 8.6111 6.19 32.2900  
FLOOR 1 MED GAS 5.20 Yes Yes 1.00 FLOOR 1 MED GAS GENERAL FLOOR 1 MED GAS 9.6875 46.45 1.0800  
FLOOR 1 MRI CONTROL ROOM 15.61 Yes Yes 1.00 FLOOR 1 MRI CONTROL ROOM GENERAL FLOOR 1 MRI CONTROL ROOM 16.1458 4.64 107.6400  
FLOOR 1 MRI HALL 13.66 Yes Yes 1.00 FLOOR 1 MRI HALL GENERAL FLOOR 1 MRI HALL 10.3041 18.58 4.3100  
FLOOR 1 MRI ROOM 40.88 Yes Yes 1.00 FLOOR 1 MRI ROOM GENERAL FLOOR 1 MRI ROOM 16.1458 4.64 107.6400  
FLOOR 1 MRI TOILET 5.02 Yes Yes 1.00 FLOOR 1 MRI TOILET GENERAL FLOOR 1 MRI TOILET 9.6875 18.58 4.3100  
FLOOR 1 NOURISHMENT 16.91 Yes Yes 1.00 FLOOR 1 NOURISHMENT GENERAL FLOOR 1 NOURISHMENT 10.7639 6.19 21.5300  
FLOOR 1 NURSE HALL 46.08 Yes Yes 1.00 FLOOR 1 NURSE HALL GENERAL FLOOR 1 NURSE HALL 10.3041 18.58 4.3100  
FLOOR 1 NURSE JANITOR 5.02 Yes Yes 1.00 FLOOR 1 NURSE JANITOR GENERAL FLOOR 1 NURSE JANITOR 9.6875 46.45 1.0800  
FLOOR 1 NURSE STATION 24.25 Yes Yes 1.00 FLOOR 1 NURSE STATION GENERAL FLOOR 1 NURSE STATION 10.7639 6.19 21.5300  
FLOOR 1 NURSE TOILET 5.02 Yes Yes 1.00 FLOOR 1 NURSE TOILET GENERAL FLOOR 1 NURSE TOILET 9.6875 18.58 4.3100  
FLOOR 1 OFFICE 44.87 Yes Yes 1.00 FLOOR 1 OFFICE GENERAL FLOOR 1 OFFICE 11.8403 18.58 11.8400  
FLOOR 1 OPERATING ROOM 1 42.74 Yes Yes 1.00 FLOOR 1 OPERATING ROOM 1 GENERAL FLOOR 1 OPERATING ROOM 1 23.6806 4.64 118.3600  
FLOOR 1 OPERATING ROOM 2 44.59 Yes Yes 1.00 FLOOR 1 OPERATING ROOM 2 GENERAL FLOOR 1 OPERATING ROOM 2 23.6806 4.64 118.3600  
FLOOR 1 OPERATING ROOM 3 44.22 Yes Yes 1.00 FLOOR 1 OPERATING ROOM 3 GENERAL FLOOR 1 OPERATING ROOM 3 23.6806 4.64 118.3600  
FLOOR 1 PACU 10.03 Yes Yes 1.00 FLOOR 1 PACU GENERAL FLOOR 1 PACU 8.6111 4.64 32.2900  
FLOOR 1 PRE-OP HALL 49.05 Yes Yes 1.00 FLOOR 1 PRE-OP HALL GENERAL FLOOR 1 PRE-OP HALL 10.3041 18.58 4.3100  
FLOOR 1 PRE-OP ROOM 1 17.56 Yes Yes 1.00 FLOOR 1 PRE-OP ROOM 1 GENERAL FLOOR 1 PRE-OP ROOM 1 7.5347 9.29 21.5300  
FLOOR 1 PRE-OP ROOM 2 31.40 Yes Yes 1.00 FLOOR 1 PRE-OP ROOM 2 GENERAL FLOOR 1 PRE-OP ROOM 2 7.5347 9.29 21.5300  
FLOOR 1 PRE-OP TOILET 5.02 Yes Yes 1.00 FLOOR 1 PRE-OP TOILET GENERAL FLOOR 1 PRE-OP TOILET 9.6875 18.58 4.3100  
FLOOR 1 PROCEDURE ROOM 26.48 Yes Yes 1.00 FLOOR 1 PROCEDURE ROOM GENERAL FLOOR 1 PROCEDURE ROOM 16.1458 4.64 32.2900  
FLOOR 1 RECEPTION 47.29 Yes Yes 1.00 FLOOR 1 RECEPTION GENERAL FLOOR 1 RECEPTION 13.9931 3.10 11.8400  
FLOOR 1 RECEPTION HALL 11.89 Yes Yes 1.00 FLOOR 1 RECEPTION HALL GENERAL FLOOR 1 RECEPTION HALL 10.3041 18.58 4.3100  
FLOOR 1 RECOVERY ROOM 50.17 Yes Yes 1.00 FLOOR 1 RECOVERY ROOM GENERAL FLOOR 1 RECOVERY ROOM 8.6111 4.64 32.2900  
FLOOR 1 SCHEDULING 11.06 Yes Yes 1.00 FLOOR 1 SCHEDULING GENERAL FLOOR 1 SCHEDULING 11.8403 18.58 11.8400  
FLOOR 1 SCRUB 7.80 Yes Yes 1.00 FLOOR 1 SCRUB GENERAL FLOOR 1 SCRUB 10.3041 18.58 4.3100  
FLOOR 1 SOIL 11.71 Yes Yes 1.00 FLOOR 1 SOIL GENERAL FLOOR 1 SOIL 16.1458 4.64 21.5300  
FLOOR 1 SOIL HOLD 5.20 Yes Yes 1.00 FLOOR 1 SOIL HOLD GENERAL FLOOR 1 SOIL HOLD 16.1458 4.64 21.5300  
FLOOR 1 SOIL WORK 16.72 Yes Yes 1.00 FLOOR 1 SOIL WORK GENERAL FLOOR 1 SOIL WORK 16.1458 4.64 21.5300  
FLOOR 1 STEP DOWN 27.87 Yes Yes 1.00 FLOOR 1 STEP DOWN GENERAL FLOOR 1 STEP DOWN 8.6111 4.64 32.2900  
FLOOR 1 STERILE HALL 57.23 Yes Yes 1.00 FLOOR 1 STERILE HALL GENERAL FLOOR 1 STERILE HALL 10.3041 18.58 4.3100  
FLOOR 1 STERILE STORAGE 36.79 Yes Yes 1.00 FLOOR 1 STERILE STORAGE GENERAL FLOOR 1 STERILE STORAGE 9.6875 46.45 1.0800  
FLOOR 1 STORAGE 85.47 Yes Yes 1.00 FLOOR 1 STORAGE GENERAL FLOOR 1 STORAGE 9.6875 46.45 1.0800  
FLOOR 1 SUB-STERILE 18.21 Yes Yes 1.00 FLOOR 1 SUB-STERILE GENERAL FLOOR 1 SUB-STERILE 10.3041 18.58 4.3100  
FLOOR 1 UTILITY HALL 23.78 Yes Yes 1.00 FLOOR 1 UTILITY HALL GENERAL FLOOR 1 UTILITY HALL 10.3041 18.58 4.3100  
FLOOR 1 UTILITY JANITOR 3.90 Yes Yes 1.00 FLOOR 1 UTILITY JANITOR GENERAL FLOOR 1 UTILITY JANITOR 9.6875 46.45 1.0800  
FLOOR 1 UTILITY ROOM 33.45 Yes Yes 1.00 FLOOR 1 UTILITY ROOM GENERAL FLOOR 1 UTILITY ROOM 9.6875 46.45 1.0800  
FLOOR 1 VESTIBULE 6.69 Yes Yes 1.00 FLOOR 1 VESTIBULE GENERAL FLOOR 1 VESTIBULE 10.3041 18.58 4.3100  
FLOOR 2 CONFERENCE 31.22 Yes Yes 1.00 FLOOR 2 CONFERENCE GENERAL FLOOR 2 CONFERENCE 13.9931 1.86 10.7600  
FLOOR 2 CONFERENCE TOILET 5.95 Yes Yes 1.00 FLOOR 2 CONFERENCE TOILET GENERAL FLOOR 2 CONFERENCE TOILET 9.6875 18.58 4.3100  
FLOOR 2 DICTATION 6.50 Yes Yes 1.00 FLOOR 2 DICTATION GENERAL FLOOR 2 DICTATION 11.8403 18.58 11.8400  
FLOOR 2 EXAM 1 33.45 Yes Yes 1.00 FLOOR 2 EXAM 1 GENERAL FLOOR 2 EXAM 1 16.1458 4.64 11.8400  
FLOOR 2 EXAM 2 50.17 Yes Yes 1.00 FLOOR 2 EXAM 2 GENERAL FLOOR 2 EXAM 2 16.1458 4.64 11.8400  
FLOOR 2 EXAM 3 66.89 Yes Yes 1.00 FLOOR 2 EXAM 3 GENERAL FLOOR 2 EXAM 3 16.1458 4.64 11.8400  
FLOOR 2 EXAM 4 7.80 Yes Yes 1.00 FLOOR 2 EXAM 4 GENERAL FLOOR 2 EXAM 4 16.1458 4.64 11.8400  
FLOOR 2 EXAM 5 32.52 Yes Yes 1.00 FLOOR 2 EXAM 5 GENERAL FLOOR 2 EXAM 5 16.1458 4.64 11.8400  
FLOOR 2 EXAM 6 20.90 Yes Yes 1.00 FLOOR 2 EXAM 6 GENERAL FLOOR 2 EXAM 6 16.1458 4.64 11.8400  
FLOOR 2 EXAM 7 73.58 Yes Yes 1.00 FLOOR 2 EXAM 7 GENERAL FLOOR 2 EXAM 7 16.1458 4.64 11.8400  
FLOOR 2 EXAM 8 25.08 Yes Yes 1.00 FLOOR 2 EXAM 8 GENERAL FLOOR 2 EXAM 8 16.1458 4.64 11.8400  
FLOOR 2 EXAM 9 36.79 Yes Yes 1.00 FLOOR 2 EXAM 9 GENERAL FLOOR 2 EXAM 9 16.1458 4.64 11.8400  
FLOOR 2 EXAM HALL 1 16.72 Yes Yes 1.00 FLOOR 2 EXAM HALL 1 GENERAL FLOOR 2 EXAM HALL 1 10.3041 18.58 4.3100  
FLOOR 2 EXAM HALL 2 16.72 Yes Yes 1.00 FLOOR 2 EXAM HALL 2 GENERAL FLOOR 2 EXAM HALL 2 10.3041 18.58 4.3100  
FLOOR 2 EXAM HALL 3 16.72 Yes Yes 1.00 FLOOR 2 EXAM HALL 3 GENERAL FLOOR 2 EXAM HALL 3 10.3041 18.58 4.3100  
FLOOR 2 EXAM HALL 4 18.39 Yes Yes 1.00 FLOOR 2 EXAM HALL 4 GENERAL FLOOR 2 EXAM HALL 4 10.3041 18.58 4.3100  
FLOOR 2 EXAM HALL 5 18.39 Yes Yes 1.00 FLOOR 2 EXAM HALL 5 GENERAL FLOOR 2 EXAM HALL 5 10.3041 18.58 4.3100  
FLOOR 2 EXAM HALL 6 18.39 Yes Yes 1.00 FLOOR 2 EXAM HALL 6 GENERAL FLOOR 2 EXAM HALL 6 10.3041 18.58 4.3100  
FLOOR 2 JANITOR 5.85 Yes Yes 1.00 FLOOR 2 JANITOR GENERAL FLOOR 2 JANITOR 9.6875 46.45 1.0800  
FLOOR 2 LOUNGE 7.43 Yes Yes 1.00 FLOOR 2 LOUNGE GENERAL FLOOR 2 LOUNGE 8.6111 6.19 32.2900  
FLOOR 2 NURSE STATION 1 13.94 Yes Yes 1.00 FLOOR 2 NURSE STATION 1 GENERAL FLOOR 2 NURSE STATION 1 10.7639 6.19 21.5300  
FLOOR 2 NURSE STATION 2 16.72 Yes Yes 1.00 FLOOR 2 NURSE STATION 2 GENERAL FLOOR 2 NURSE STATION 2 10.7639 6.19 21.5300  
FLOOR 2 OFFICE 52.03 Yes Yes 1.00 FLOOR 2 OFFICE GENERAL FLOOR 2 OFFICE 11.8403 18.58 11.8400  
FLOOR 2 OFFICE HALL 41.25 Yes Yes 1.00 FLOOR 2 OFFICE HALL GENERAL FLOOR 2 OFFICE HALL 10.3041 18.58 4.3100  
FLOOR 2 RECEPTION 91.42 Yes Yes 1.00 FLOOR 2 RECEPTION GENERAL FLOOR 2 RECEPTION 13.9931 3.10 11.8400  
FLOOR 2 RECEPTION HALL 52.40 Yes Yes 1.00 FLOOR 2 RECEPTION HALL GENERAL FLOOR 2 RECEPTION HALL 10.3041 18.58 4.3100  
FLOOR 2 RECEPTION TOILET 11.71 Yes Yes 1.00 FLOOR 2 RECEPTION TOILET GENERAL FLOOR 2 RECEPTION TOILET 9.6875 18.58 4.3100  
FLOOR 2 SCHEDULING 1 30.10 Yes Yes 1.00 FLOOR 2 SCHEDULING 1 GENERAL FLOOR 2 SCHEDULING 1 11.8403 18.58 11.8400  
FLOOR 2 SCHEDULING 2 31.77 Yes Yes 1.00 FLOOR 2 SCHEDULING 2 GENERAL FLOOR 2 SCHEDULING 2 11.8403 18.58 11.8400  
FLOOR 2 STORAGE 1 5.20 Yes Yes 1.00 FLOOR 2 STORAGE 1 GENERAL FLOOR 2 STORAGE 1 9.6875 46.45 1.0800  
FLOOR 2 STORAGE 2 11.15 Yes Yes 1.00 FLOOR 2 STORAGE 2 GENERAL FLOOR 2 STORAGE 2 9.6875 46.45 1.0800  
FLOOR 2 STORAGE 3 13.38 Yes Yes 1.00 FLOOR 2 STORAGE 3 GENERAL FLOOR 2 STORAGE 3 9.6875 46.45 1.0800  
FLOOR 2 UTILITY 11.71 Yes Yes 1.00 FLOOR 2 UTILITY GENERAL FLOOR 2 UTILITY 9.6875 46.45 1.0800  
FLOOR 2 WORK 157.01 Yes Yes 1.00 FLOOR 2 WORK GENERAL FLOOR 2 WORK 11.8403 18.58 9.7803  
FLOOR 2 WORK HALL 77.48 Yes Yes 1.00 FLOOR 2 WORK HALL GENERAL FLOOR 2 WORK HALL 10.3041 18.58 4.3100  
FLOOR 2 WORK TOILET 5.02 Yes Yes 1.00 FLOOR 2 WORK TOILET GENERAL FLOOR 2 WORK TOILET 9.6875 18.58 4.3100  
FLOOR 2 X-RAY 83.61 Yes Yes 1.00 FLOOR 2 X-RAY GENERAL FLOOR 2 X-RAY 16.1458 4.64 107.6400  
FLOOR 3 DRESSING ROOM 3.90 Yes Yes 1.00 FLOOR 3 DRESSING ROOM GENERAL FLOOR 3 DRESSING ROOM 11.8403 18.58 11.8400  
FLOOR 3 ELEVATOR HALL 34.37 Yes Yes 1.00 FLOOR 3 ELEVATOR HALL GENERAL FLOOR 3 ELEVATOR HALL 10.3041 18.58 4.3100  
FLOOR 3 HUMID 10.03 Yes Yes 1.00 FLOOR 3 HUMID GENERAL FLOOR 3 HUMID 11.8403 18.58 11.8400  
FLOOR 3 JANITOR 5.85 Yes Yes 1.00 FLOOR 3 JANITOR GENERAL FLOOR 3 JANITOR 9.6875 46.45 1.0800  
FLOOR 3 LOCKER 11.15 Yes Yes 1.00 FLOOR 3 LOCKER GENERAL FLOOR 3 LOCKER 8.6111 6.19 32.2900  
FLOOR 3 LOUNGE 70.51 Yes Yes 1.00 FLOOR 3 LOUNGE GENERAL FLOOR 3 LOUNGE 8.6111 6.19 32.2900  
FLOOR 3 LOUNGE TOILET 17.84 Yes Yes 1.00 FLOOR 3 LOUNGE TOILET GENERAL FLOOR 3 LOUNGE TOILET 9.6875 18.58 4.3100  
FLOOR 3 MECHANICAL 32.52 Yes Yes 1.00 FLOOR 3 MECHANICAL GENERAL FLOOR 3 MECHANICAL 16.1458 61.94 53.8200  
FLOOR 3 MECHANICAL HALL 27.87 Yes Yes 1.00 FLOOR 3 MECHANICAL HALL GENERAL FLOOR 3 MECHANICAL HALL 10.3041 18.58 4.3100  
FLOOR 3 OFFICE 282.05 Yes Yes 1.00 FLOOR 3 OFFICE GENERAL FLOOR 3 OFFICE 11.8403 18.58 11.8400  
FLOOR 3 OFFICE HALL 77.48 Yes Yes 1.00 FLOOR 3 OFFICE HALL GENERAL FLOOR 3 OFFICE HALL 10.3041 18.58 4.3100  
FLOOR 3 OFFICE TOILET 5.02 Yes Yes 1.00 FLOOR 3 OFFICE TOILET GENERAL FLOOR 3 OFFICE TOILET 9.6875 18.58 4.3100  
FLOOR 3 PHYSICAL THERAPY 1 120.77 Yes Yes 1.00 FLOOR 3 PHYSICAL THERAPY 1 GENERAL FLOOR 3 PHYSICAL THERAPY 1 9.6875 4.64 16.1500  
FLOOR 3 PHYSICAL THERAPY 2 55.00 Yes Yes 1.00 FLOOR 3 PHYSICAL THERAPY 2 GENERAL FLOOR 3 PHYSICAL THERAPY 2 9.6875 4.64 16.1500  
FLOOR 3 PHYSICAL THERAPY TOILET 7.80 Yes Yes 1.00 FLOOR 3 PHYSICAL THERAPY TOILET GENERAL FLOOR 3 PHYSICAL THERAPY TOILET 9.6875 18.58 4.3100  
FLOOR 3 STORAGE 1 10.03 Yes Yes 1.00 FLOOR 3 STORAGE 1 GENERAL FLOOR 3 STORAGE 1 9.6875 46.45 1.0800  
FLOOR 3 STORAGE 2 7.80 Yes Yes 1.00 FLOOR 3 STORAGE 2 GENERAL FLOOR 3 STORAGE 2 9.6875 46.45 1.0800  
FLOOR 3 TREATMENT 44.22 Yes Yes 1.00 FLOOR 3 TREATMENT GENERAL FLOOR 3 TREATMENT 16.1458 4.64 11.8400  
FLOOR 3 UNDEVELOPED 1 210.70 Yes Yes 1.00 FLOOR 3 UNDEVELOPED 1 GENERAL FLOOR 3 UNDEVELOPED 1 9.6875 46.45 11.8400  
FLOOR 3 UNDEVELOPED 2 107.02 Yes Yes 1.00 FLOOR 3 UNDEVELOPED 2 GENERAL FLOOR 3 UNDEVELOPED 2 9.6875 46.45 11.8400  
FLOOR 3 UTILITY 20.07 Yes Yes 1.00 FLOOR 3 UTILITY GENERAL FLOOR 3 UTILITY 16.1458 46.45 1.0800  
FLOOR 3 WORK 53.33 Yes Yes 1.00 FLOOR 3 WORK GENERAL FLOOR 3 WORK 11.8403 18.58 11.8400  
NE STAIR 15.61 Yes Yes 1.00 NE STAIR GENERAL NE STAIR 10.3041 18.58 4.3100  
NW ELEVATOR 13.01 Yes Yes 1.00 NW ELEVATOR GENERAL NW ELEVATOR 10.3041 61.94 4.3100  
NW STAIR 17.84 Yes Yes 1.00 NW STAIR GENERAL NW STAIR 10.3041 18.58 4.3100  
SW STAIR 8.92 Yes Yes 1.00 SW STAIR GENERAL SW STAIR 10.3041 18.58 4.3100  
Total 3804.01             12.0629 4.01 40.3528  
Conditioned Total 3804.01             12.0629 4.01 40.3528  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 3804.01 3804.01 0.00 0.00 12.0629 8.02 40.3528
Total 3804.01 3804.01 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 28-JUL-15:09 04-FEB-07:10 - - - - - - - - - - 16-MAR-10:00
Heating 0.00 92586.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 138420.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 41298.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 69545.86 4952.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 36499.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 40.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 285805.09 97539.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 92586.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 138420.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 41298.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 6475.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 486.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 62583.90 4952.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 36499.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 40.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.02 214.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4482.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1982.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 753.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 4247.71 204.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1639.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 2.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 101.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 13111.76 519.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.01 56.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1178.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 521.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 198.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1116.64 53.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 431.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 26.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 3446.83 136.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.01 56.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1178.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 521.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 198.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1116.64 53.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 431.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 26.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 3446.83 136.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
FLOOR 1 ANESTHESIA VAV BOX COMPONENT 0.065420 0.000000 1.00 0.065420 1.00 0.500000 0.003260 0.000026 0.065420 -15.0 0.007000
FLOOR 1 BIO HAZ VAV BOX COMPONENT 0.022198 0.178590 0.200000 0.004440 1.00 0.500000 0.002133 0.000003 0.006167 -15.0 0.007000
FLOOR 1 CLEAN VAV BOX COMPONENT 0.073036 0.542760 1.00 0.073036 1.00 0.500000 0.003120 0.000028 0.073036 -15.0 0.007000
FLOOR 1 CLEAN WORK VAV BOX COMPONENT 0.091400 0.567956 1.00 0.091400 1.00 0.500000 0.002981 0.000035 0.091400 -15.0 0.007000
FLOOR 1 DICTATION VAV BOX COMPONENT 0.054946       1.00 0.500000 0.002347 0.000002 0.005495 -15.0 0.007000
FLOOR 1 DRESSING ROOM VAV BOX COMPONENT 0.030020       1.00 0.500000 0.003590 0.000005 0.009291 -15.0 0.007000
FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT 0.068438 0.101371 0.200000 0.013688 1.00 0.500000 0.003758 0.000005 0.013688 -15.0 0.007000
FLOOR 1 HUMID VAV BOX COMPONENT 0.027237       1.00 0.500000 0.002715 0.000001 0.002724 -15.0 0.007000
FLOOR 1 IT HALL VAV BOX COMPONENT 0.049664 0.199561 0.200000 0.009933 1.00 0.500000 0.001909 0.000004 0.009933 -15.0 0.007000
FLOOR 1 IT ROOM VAV BOX COMPONENT 0.047711       1.00 0.500000 0.002293 0.000002 0.004771 -15.0 0.007000
FLOOR 1 LOBBY VAV BOX COMPONENT 0.353362 0.124611 0.200000 0.070672 0.400655 0.500000 0.003058 0.000030 0.070672 -15.0 0.007000
FLOOR 1 LOBBY HALL VAV BOX COMPONENT 0.090681 0.187362 0.200000 0.018136 1.00 0.500000 0.002033 0.000007 0.018136 -15.0 0.007000
FLOOR 1 LOBBY TOILET VAV BOX COMPONENT 0.029193 0.000000 1.00 0.029193 1.00 0.500000 0.002910 0.000012 0.029193 -15.0 0.007000
FLOOR 1 LOCKER ROOM VAV BOX COMPONENT 0.339262 0.137719 0.200000 0.067852 0.417306 0.500000 0.002767 0.000026 0.067852 -15.0 0.007000
FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT 0.153065 0.229398 0.200000 0.030613 0.924941 0.500000 0.001661 0.000012 0.030613 -15.0 0.007000
FLOOR 1 LOUNGE VAV BOX COMPONENT 0.184761 0.137936 0.200000 0.036952 0.766267 0.500000 0.002762 0.000014 0.036952 -15.0 0.007000
FLOOR 1 MED GAS VAV BOX COMPONENT 0.036582 0.108369 0.200000 0.007316 1.00 0.500000 0.003516 0.000015 0.029145 -15.0 0.007000
FLOOR 1 MRI HALL VAV BOX COMPONENT 0.060667 0.171533 0.200000 0.012133 1.00 0.500000 0.002221 0.000005 0.012133 -15.0 0.007000
FLOOR 1 MRI TOILET VAV BOX COMPONENT 0.025304 0.000000 1.00 0.025304 1.00 0.500000 0.002522 0.000010 0.025304 -15.0 0.007000
FLOOR 1 NOURISHMENT VAV BOX COMPONENT 0.096209 0.133919 0.200000 0.019242 1.00 0.500000 0.002845 0.000007 0.019242 -15.0 0.007000
FLOOR 1 NURSE HALL VAV BOX COMPONENT 0.170389 0.206075 0.200000 0.034078 0.830902 0.500000 0.001849 0.000013 0.034078 -15.0 0.007000
FLOOR 1 NURSE JANITOR VAV BOX COMPONENT 0.021473 0.178030 0.200000 0.004295 1.00 0.500000 0.002140 0.000002 0.004295 -15.0 0.007000
FLOOR 1 NURSE STATION VAV BOX COMPONENT 0.127267 0.145181 0.200000 0.025453 1.00 0.500000 0.002624 0.000010 0.025453 -15.0 0.007000
FLOOR 1 NURSE TOILET VAV BOX COMPONENT 0.024325 0.000000 1.00 0.024325 1.00 0.500000 0.002424 0.000009 0.024325 -15.0 0.007000
FLOOR 1 OFFICE VAV BOX COMPONENT 0.171058       0.827652 0.500000 0.001906 0.000007 0.017106 -15.0 0.007000
FLOOR 1 PACU VAV BOX COMPONENT 0.064539 0.789707 1.00 0.064539 1.00 0.500000 0.003216 0.000025 0.064539 -15.0 0.007000
FLOOR 1 PRE-OP HALL VAV BOX COMPONENT 0.174837 0.213789 0.200000 0.034967 0.809763 0.500000 0.001782 0.000014 0.034967 -15.0 0.007000
FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT 0.089192 1.00 1.00 0.089192 1.00 0.500000 0.002540 0.000035 0.089192 -15.0 0.007000
FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT 0.159508 1.00 1.00 0.159508 1.00 0.500000 0.002540 0.000062 0.159508 -15.0 0.007000
FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT 0.024665 0.000000 1.00 0.024665 1.00 0.500000 0.002458 0.000010 0.024665 -15.0 0.007000
FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT 0.336241 1.00 1.00 0.336241 1.00 0.500000 0.006350 0.000130 0.336241 -15.0 0.007000
FLOOR 1 RECEPTION VAV BOX COMPONENT 0.270029 0.133442 0.200000 0.054006 0.524301 0.500000 0.002855 0.000021 0.054006 -15.0 0.007000
FLOOR 1 RECEPTION HALL VAV BOX COMPONENT 0.046335 0.195563 0.200000 0.009267 1.00 0.500000 0.001948 0.000004 0.009267 -15.0 0.007000
FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT 0.332852 0.765613 0.870000 0.289581 0.870000 0.500000 0.003317 0.000113 0.289581 -15.0 0.007000
FLOOR 1 SCHEDULING VAV BOX COMPONENT 0.052355       1.00 0.500000 0.002368 0.000002 0.005236 -15.0 0.007000
FLOOR 1 SCRUB VAV BOX COMPONENT 0.031484 0.188872 0.200000 0.006297 1.00 0.500000 0.002017 0.000003 0.006297 -15.0 0.007000
FLOOR 1 SOIL VAV BOX COMPONENT 0.072983 0.000000 1.00 0.072983 1.00 0.500000 0.003117 0.000028 0.072983 -15.0 0.007000
FLOOR 1 SOIL HOLD VAV BOX COMPONENT 0.034049 0.000000 1.00 0.034049 1.00 0.500000 0.003272 0.000013 0.034049 -15.0 0.007000
FLOOR 1 SOIL WORK VAV BOX COMPONENT 0.096948 0.000000 1.00 0.096948 1.00 0.500000 0.002899 0.000038 0.096948 -15.0 0.007000
FLOOR 1 STEP DOWN VAV BOX COMPONENT 0.212320 0.666801 0.690000 0.146501 0.690000 0.500000 0.003809 0.000060 0.146501 -15.0 0.007000
FLOOR 1 STERILE HALL VAV BOX COMPONENT 0.195932 0.222566 0.200000 0.039186 0.722577 0.500000 0.001712 0.000015 0.039186 -15.0 0.007000
FLOOR 1 STERILE STORAGE VAV BOX COMPONENT 0.110303 0.254151 0.200000 0.022061 1.00 0.500000 0.001499 0.000009 0.022061 -15.0 0.007000
FLOOR 1 STORAGE VAV BOX COMPONENT 0.339872 0.191627 0.200000 0.067974 0.511006 0.500000 0.001988 0.000120 0.234608 -15.0 0.007000
FLOOR 1 SUB-STERILE VAV BOX COMPONENT 0.102040 0.135979 0.200000 0.020408 1.00 0.500000 0.002802 0.000020 0.039522 -15.0 0.007000
FLOOR 1 UTILITY HALL VAV BOX COMPONENT 0.179027 0.101229 0.200000 0.035805 0.790809 0.500000 0.003764 0.000038 0.074751 -15.0 0.007000
FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT 0.016893 0.176009 0.200000 0.003379 1.00 0.500000 0.002165 0.000001 0.003379 -15.0 0.007000
FLOOR 1 UTILITY ROOM VAV BOX COMPONENT 0.144682 0.176146 0.200000 0.028936 0.978535 0.500000 0.002163 0.000035 0.067602 -15.0 0.007000
FLOOR 1 VESTIBULE VAV BOX COMPONENT 0.041608 0.122501 0.200000 0.008322 1.00 0.500000 0.003110 0.000004 0.008389 -15.0 0.007000
FLOOR 2 CONFERENCE VAV BOX COMPONENT 0.251377 0.094624 0.351000 0.088233 0.563204 0.500000 0.004026 0.000044 0.088233 -15.0 0.007800
FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT 0.027505 0.000000 1.00 0.027505 1.00 0.500000 0.002313 0.000011 0.027505 -15.0 0.007800
FLOOR 2 DICTATION VAV BOX COMPONENT 0.032968 0.150310 0.300000 0.009890 1.00 0.500000 0.002535 0.000004 0.009890 -15.0 0.007800
FLOOR 2 EXAM 1 VAV BOX COMPONENT 0.259903 0.653669 0.510000 0.132550 0.544727 0.500000 0.003886 0.000061 0.132550 -15.0 0.007800
FLOOR 2 EXAM 2 VAV BOX COMPONENT 0.254836 1.00 1.00 0.254836 1.00 0.500000 0.002540 0.000100 0.254836 -15.0 0.007800
FLOOR 2 EXAM 3 VAV BOX COMPONENT 0.339781 1.00 1.00 0.339781 1.00 0.500000 0.002540 0.000133 0.339781 -15.0 0.007800
FLOOR 2 EXAM 4 VAV BOX COMPONENT 0.050514 0.784753 0.640000 0.032329 1.00 0.500000 0.003236 0.000015 0.032329 -15.0 0.007800
FLOOR 2 EXAM 5 VAV BOX COMPONENT 0.253193 0.652352 0.690000 0.174703 0.690000 0.500000 0.003893 0.000076 0.174703 -15.0 0.007800
FLOOR 2 EXAM 6 VAV BOX COMPONENT 0.118776 0.893962 0.940000 0.111650 1.00 0.500000 0.002841 0.000047 0.111650 -15.0 0.007800
FLOOR 2 EXAM 7 VAV BOX COMPONENT 0.373759 1.00 1.00 0.373759 1.00 0.500000 0.002540 0.000145 0.373759 -15.0 0.007800
FLOOR 2 EXAM 8 VAV BOX COMPONENT 0.143740 0.886445 0.930000 0.133678 0.984945 0.500000 0.002865 0.000054 0.133678 -15.0 0.007800
FLOOR 2 EXAM 9 VAV BOX COMPONENT 0.197597 0.945762 1.00 0.197597 1.00 0.500000 0.002685 0.000077 0.197597 -15.0 0.007800
FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT 0.076366 0.166862 0.300000 0.022910 1.00 0.500000 0.002283 0.000011 0.022910 -15.0 0.007800
FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT 0.076283 0.167044 0.300000 0.022885 1.00 0.500000 0.002281 0.000009 0.022885 -15.0 0.007800
FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT 0.073680 0.172946 0.300000 0.022104 1.00 0.500000 0.002203 0.000009 0.022104 -15.0 0.007800
FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT 0.080148 0.174888 0.300000 0.024044 1.00 0.500000 0.002179 0.000009 0.024044 -15.0 0.007800
FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT 0.082763 0.169361 0.300000 0.024829 1.00 0.500000 0.002250 0.000010 0.024829 -15.0 0.007800
FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT 0.082414 0.170078 0.300000 0.024724 1.00 0.500000 0.002240 0.000010 0.024724 -15.0 0.007800
FLOOR 2 JANITOR VAV BOX COMPONENT 0.031296 0.142506 0.300000 0.009389 1.00 0.500000 0.002674 0.000011 0.021959 -15.0 0.007800
FLOOR 2 LOUNGE VAV BOX COMPONENT 0.047588 0.119009 0.300000 0.014276 1.00 0.500000 0.003201 0.000006 0.014276 -15.0 0.007800
FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT 0.074964 0.141652 0.300000 0.022489 1.00 0.500000 0.002690 0.000009 0.022489 -15.0 0.007800
FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT 0.090640 0.140585 0.300000 0.027192 1.00 0.500000 0.002710 0.000011 0.027192 -15.0 0.007800
FLOOR 2 OFFICE VAV BOX COMPONENT 0.333193 0.118981 0.300000 0.099958 0.424908 0.500000 0.003202 0.000062 0.120366 -15.0 0.007800
FLOOR 2 OFFICE HALL VAV BOX COMPONENT 0.177138 0.177442 0.300000 0.053141 0.799244 0.500000 0.002147 0.000024 0.053141 -15.0 0.007800
FLOOR 2 RECEPTION VAV BOX COMPONENT 0.543950 0.128062 0.322000 0.175152 0.341499 0.500000 0.002975 0.000078 0.175152 -15.0 0.007800
FLOOR 2 RECEPTION HALL VAV BOX COMPONENT 0.235603 0.169466 0.300000 0.070681 0.600911 0.500000 0.002248 0.000027 0.070681 -15.0 0.007800
FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT 0.050492 0.000000 1.00 0.050492 1.00 0.500000 0.002157 0.000020 0.050492 -15.0 0.007800
FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT 0.124407 0.184367 0.300000 0.037322 1.00 0.500000 0.002067 0.000014 0.037322 -15.0 0.007800
FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT 0.132363 0.182913 0.300000 0.039709 1.00 0.500000 0.002083 0.000015 0.039709 -15.0 0.007800
FLOOR 2 STORAGE 1 VAV BOX COMPONENT 0.022537 0.175901 0.300000 0.006761 1.00 0.500000 0.002166 0.000003 0.006761 -15.0 0.007800
FLOOR 2 STORAGE 2 VAV BOX COMPONENT 0.041983 0.202347 0.300000 0.012595 1.00 0.500000 0.001883 0.000005 0.012595 -15.0 0.007800
FLOOR 2 STORAGE 3 VAV BOX COMPONENT 0.051754 0.196971 0.300000 0.015526 1.00 0.500000 0.001934 0.000006 0.015526 -15.0 0.007800
FLOOR 2 UTILITY VAV BOX COMPONENT 0.075073 0.118815 0.300000 0.022522 1.00 0.500000 0.003207 0.000019 0.036902 -15.0 0.007800
FLOOR 2 WORK VAV BOX COMPONENT 0.554946 0.215586 0.300000 0.166484 0.574896 0.500000 0.001767 0.000064 0.166484 -15.0 0.007800
FLOOR 2 WORK HALL VAV BOX COMPONENT 0.335016 0.176232 0.300000 0.100505 0.469952 0.500000 0.002162 0.000039 0.100505 -15.0 0.007800
FLOOR 2 WORK TOILET VAV BOX COMPONENT 0.024667 0.000000 1.00 0.024667 1.00 0.500000 0.002458 0.000011 0.024667 -15.0 0.007800
FLOOR 3 DRESSING ROOM VAV BOX COMPONENT 0.023790 0.124982 0.300000 0.007137 1.00 0.500000 0.003048 0.000003 0.007137 -15.0 0.007800
FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT 0.127351 0.205676 0.300000 0.038205 1.00 0.500000 0.001852 0.000030 0.058948 -15.0 0.007800
FLOOR 3 HUMID VAV BOX COMPONENT 0.055210 0.138482 0.300000 0.016563 1.00 0.500000 0.002751 0.000006 0.016563 -15.0 0.007800
FLOOR 3 JANITOR VAV BOX COMPONENT 0.031160 0.143128 0.300000 0.009348 1.00 0.500000 0.002662 0.000015 0.030022 -15.0 0.007800
FLOOR 3 LOCKER VAV BOX COMPONENT 0.073749 0.115189 0.300000 0.022125 1.00 0.500000 0.003308 0.000009 0.022125 -15.0 0.007800
FLOOR 3 LOUNGE VAV BOX COMPONENT 0.420154 0.127884 0.300000 0.126046 0.341025 0.500000 0.002979 0.000050 0.126046 -15.0 0.007800
FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT 0.085908 0.000000 1.00 0.085908 1.00 0.500000 0.002408 0.000039 0.085908 -15.0 0.007800
FLOOR 3 MECHANICAL VAV BOX COMPONENT 0.365386 0.067811 0.300000 0.109616 0.387470 0.500000 0.005619 0.000043 0.109616 -15.0 0.007800
FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT 0.132105 0.160763 0.300000 0.039632 1.00 0.500000 0.002370 0.000020 0.039632 -15.0 0.007800
FLOOR 3 OFFICE VAV BOX COMPONENT 1.15 0.186940 0.300000 0.344910 0.498506 0.500000 0.002038 0.000176 0.344910 -15.0 0.007800
FLOOR 3 OFFICE HALL VAV BOX COMPONENT 0.329760 0.179041 0.300000 0.098928 0.477444 0.500000 0.002128 0.000052 0.101326 -15.0 0.007800
FLOOR 3 OFFICE TOILET VAV BOX COMPONENT 0.025040 0.000000 1.00 0.025040 1.00 0.500000 0.002496 0.000012 0.025040 -15.0 0.007800
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT 0.767752 0.799078 0.690000 0.529749 0.690000 0.500000 0.003178 0.000239 0.529749 -15.0 0.007800
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT 0.279375 1.00 0.830000 0.231882 0.830000 0.500000 0.002540 0.000091 0.231882 -15.0 0.007800
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT 0.037199 0.000000 1.00 0.037199 1.00 0.500000 0.002383 0.000014 0.037199 -15.0 0.007800
FLOOR 3 STORAGE 1 VAV BOX COMPONENT 0.041785 0.182974 1.00 0.041785 1.00 0.500000 0.002082 0.000017 0.041785 -15.0 0.007800
FLOOR 3 STORAGE 2 VAV BOX COMPONENT 0.034345 0.173140 0.300000 0.010304 1.00 0.500000 0.002201 0.000005 0.010304 -15.0 0.007800
FLOOR 3 TREATMENT VAV BOX COMPONENT 0.238364 0.942396 0.810000 0.193075 0.810000 0.500000 0.002695 0.000075 0.193075 -15.0 0.007800
FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT 0.930406 0.172566 0.300000 0.279122 0.460176 0.500000 0.002208 0.000165 0.322264 -15.0 0.007800
FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT 0.488250 0.167030 0.300000 0.146475 0.445414 0.500000 0.002281 0.000120 0.234928 -15.0 0.007800
FLOOR 3 UTILITY VAV BOX COMPONENT 0.073796 0.207208 0.307000 0.022655 1.00 0.500000 0.001839 0.000010 0.022655 -15.0 0.007800
FLOOR 3 WORK VAV BOX COMPONENT 0.377864 0.107538 0.300000 0.113359 0.374675 0.500000 0.003543 0.000077 0.151131 -15.0 0.007800
NE STAIR VAV BOX COMPONENT 0.202449 0.058746 0.300000 0.060735 0.699319 0.500000 0.006486 0.000094 0.184541 -15.0 0.007800
NW ELEVATOR VAV BOX COMPONENT 0.168083 0.058964 0.300000 0.050425 0.842300 0.500000 0.006462 0.000058 0.112570 -15.0 0.007800
NW STAIR VAV BOX COMPONENT 0.234068 0.058069 0.300000 0.070220 0.604852 0.500000 0.006561 0.000091 0.178002 -15.0 0.007800
SW STAIR VAV BOX COMPONENT 0.121628 0.055876 0.300000 0.036488 1.00 0.500000 0.006819 0.000045 0.087860 -15.0 0.007800
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL 2984.58 0.000026 49.41
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL 358.55 0.000003 6.48
FLOOR 1 CLEAN VAV BOX REHEAT COIL 3233.65 0.000028 53.10
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL 4046.69 0.000035 66.45
FLOOR 1 DICTATION VAV BOX REHEAT COIL 243.27 0.000002 3.99
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL 540.49 0.000005 9.78
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL 606.02 0.000005 9.95
FLOOR 1 HUMID VAV BOX REHEAT COIL 120.59 0.000001 1.98
FLOOR 1 IT HALL VAV BOX REHEAT COIL 439.77 0.000004 7.22
FLOOR 1 IT ROOM VAV BOX REHEAT COIL 211.24 0.000002 3.47
FLOOR 1 LOBBY VAV BOX REHEAT COIL 3473.85 0.000030 58.85
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL 802.97 0.000007 13.18
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL 1397.24 0.000012 23.47
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL 3004.15 0.000026 49.33
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL 1355.38 0.000012 22.26
FLOOR 1 LOUNGE VAV BOX REHEAT COIL 1636.05 0.000014 26.86
FLOOR 1 MED GAS VAV BOX REHEAT COIL 1696.30 0.000015 30.69
FLOOR 1 MRI HALL VAV BOX REHEAT COIL 537.20 0.000005 8.82
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL 1138.28 0.000010 18.77
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL 851.92 0.000007 13.99
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL 1508.78 0.000013 24.77
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL 190.14 0.000002 3.12
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL 1126.94 0.000010 18.50
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL 1077.00 0.000009 17.68
FLOOR 1 OFFICE VAV BOX REHEAT COIL 757.35 0.000007 12.44
FLOOR 1 PACU VAV BOX REHEAT COIL 2857.46 0.000025 46.92
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL 1548.17 0.000014 25.42
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL 3948.97 0.000035 64.84
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL 7062.18 0.000062 115.96
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL 1179.93 0.000010 19.82
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL 14887.00 0.000130 244.45
FLOOR 1 RECEPTION VAV BOX REHEAT COIL 2391.09 0.000021 39.26
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL 410.29 0.000004 6.74
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL 12957.10 0.000113 213.35
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL 231.80 0.000002 3.81
FLOOR 1 SCRUB VAV BOX REHEAT COIL 324.17 0.000003 5.58
FLOOR 1 SOIL VAV BOX REHEAT COIL 3231.28 0.000028 53.06
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL 1507.49 0.000013 24.75
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL 4292.37 0.000038 70.48
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL 6858.70 0.000060 114.42
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL 1734.97 0.000015 28.49
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL 976.73 0.000009 16.04
FLOOR 1 STORAGE VAV BOX REHEAT COIL 13705.00 0.000120 248.38
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL 2306.24 0.000020 41.78
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL 4362.06 0.000038 79.02
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL 168.08 0.000001 2.86
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL 3948.42 0.000035 71.55
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL 487.54 0.000004 8.82
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL 5025.87 0.000044 90.00
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL 1271.20 0.000011 21.12
FLOOR 2 DICTATION VAV BOX REHEAT COIL 437.90 0.000004 7.19
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL 6932.62 0.000061 119.95
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL 11401.04 0.000100 187.65
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL 15200.52 0.000133 250.18
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL 1719.54 0.000015 29.94
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL 8664.01 0.000076 147.14
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL 5345.07 0.000047 89.75
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL 16548.08 0.000145 271.61
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL 6223.75 0.000054 103.61
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL 8748.54 0.000077 143.59
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL 1225.20 0.000011 21.38
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL 1077.55 0.000009 18.00
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL 1066.72 0.000009 17.96
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL 1082.64 0.000009 17.85
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL 1099.29 0.000010 18.04
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL 1118.46 0.000010 18.47
FLOOR 2 JANITOR VAV BOX REHEAT COIL 1279.73 0.000011 23.15
FLOOR 2 LOUNGE VAV BOX REHEAT COIL 632.08 0.000006 10.37
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL 995.70 0.000009 16.34
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL 1203.92 0.000011 19.76
FLOOR 2 OFFICE VAV BOX REHEAT COIL 7038.08 0.000062 127.52
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL 2708.83 0.000024 46.44
FLOOR 2 RECEPTION VAV BOX REHEAT COIL 8937.71 0.000078 153.28
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL 3129.37 0.000027 51.36
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL 2235.50 0.000020 36.69
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL 1652.43 0.000014 27.12
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL 1758.10 0.000015 28.86
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL 340.79 0.000003 5.82
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL 584.14 0.000005 9.71
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL 687.42 0.000006 11.28
FLOOR 2 UTILITY VAV BOX REHEAT COIL 2152.67 0.000019 38.96
FLOOR 2 WORK VAV BOX REHEAT COIL 7371.03 0.000064 120.98
FLOOR 2 WORK HALL VAV BOX REHEAT COIL 4449.83 0.000039 73.04
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL 1290.81 0.000011 22.34
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL 315.98 0.000003 5.19
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL 3443.33 0.000030 62.36
FLOOR 3 HUMID VAV BOX REHEAT COIL 733.32 0.000006 12.04
FLOOR 3 JANITOR VAV BOX REHEAT COIL 1747.87 0.000015 31.61
FLOOR 3 LOCKER VAV BOX REHEAT COIL 994.39 0.000009 16.39
FLOOR 3 LOUNGE VAV BOX REHEAT COIL 5728.16 0.000050 94.69
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL 4486.17 0.000039 77.58
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL 4879.73 0.000043 80.20
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL 2308.09 0.000020 41.74
FLOOR 3 OFFICE VAV BOX REHEAT COIL 20137.16 0.000176 364.61
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL 5904.69 0.000052 106.82
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL 1396.37 0.000012 24.78
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL 27354.72 0.000239 471.11
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL 10458.98 0.000091 172.53
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL 1646.96 0.000014 27.03
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL 1938.60 0.000017 32.24
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL 588.17 0.000005 10.54
FLOOR 3 TREATMENT VAV BOX REHEAT COIL 8548.32 0.000075 140.31
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL 18890.57 0.000165 342.68
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL 13748.49 0.000120 249.21
FLOOR 3 UTILITY VAV BOX REHEAT COIL 1187.57 0.000010 20.57
FLOOR 3 WORK VAV BOX REHEAT COIL 8826.19 0.000077 159.83
NE STAIR VAV BOX REHEAT COIL 10755.93 0.000094 194.60
NW ELEVATOR VAV BOX REHEAT COIL 6572.63 0.000058 119.01
NW STAIR VAV BOX REHEAT COIL 10385.31 0.000091 187.98
SW STAIR VAV BOX REHEAT COIL 5126.39 0.000045 92.79
AHU-1 HEATING COIL 0.000000 0.000000 1.00
AHU-2 HEATING COIL 0.000000 0.000000 1.00
AHU-3 HEATING COIL 0.000000 0.000000 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
FLOOR 1 CAFE DIRECT AIR 0.359306
FLOOR 1 ELEVATOR PUMP ROOM DIRECT AIR 0.096623
FLOOR 1 MRI CONTROL ROOM DIRECT AIR 0.193873
FLOOR 1 MRI ROOM DIRECT AIR 0.464836
FLOOR 1 OPERATING ROOM 1 DIRECT AIR 0.723607
FLOOR 1 OPERATING ROOM 2 DIRECT AIR 0.755069
FLOOR 1 OPERATING ROOM 3 DIRECT AIR 0.748776
FLOOR 2 X-RAY DIRECT AIR 1.07
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
AHU-1 3.53 2.38 5.54 3.53 5.54 5.54 1.00 0.636566 5.54
AHU-2 4.03 3.18 6.45 3.18 6.05 6.05 1.00 0.526228 6.05
AHU-3 3.45 2.53 6.09 2.53 5.77 5.77 1.00 0.438308 5.77
PSZ_CAFE 0.359306 0.359306 0.359306 0.359306 0.359306 0.359306 1.00 1.00 0.359306
PSZ_ELEVATOR 0.096623 0.096623 0.096623 0.096623 0.096623 0.096623 1.00 1.00 0.096623
PSZ_MRI_CONTROL 0.193873 0.193873 0.193873 0.193873 0.193873 0.193873 1.00 1.00 0.193873
PSZ_MRI 0.464836 0.464836 0.464836 0.464836 0.464836 0.464836 1.00 1.00 0.464836
PSZ_OR_1 0.723607 0.723607 0.723607 0.723607 0.723607 0.723607 1.00 1.00 0.723607
PSZ_OR_2 0.755069 0.755069 0.755069 0.755069 0.755069 0.755069 1.00 1.00 0.755069
PSZ_OR_3 0.748776 0.748776 0.748776 0.748776 0.748776 0.748776 1.00 1.00 0.748776
PSZ_XRAY 1.07 1.07 1.07 1.07 1.07 1.07 1.00 1.00 1.07
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AHU-1_OA_CONTROLLER 5.54 1.07
AHU-2_OA_CONTROLLER 6.05  
AHU-3_OA_CONTROLLER 5.77  
PSZ_CAFE_OA_CONTROLLER 0.359306 0.184342
PSZ_ELEVATOR_OA_CONTROLLER 0.096623 0.000000
PSZ_MRI_CONTROL_OA_CONTROLLER 0.193873 0.023786
PSZ_MRI_OA_CONTROLLER 0.464836 0.062297
PSZ_OR_1_OA_CONTROLLER 0.723607 0.238805
PSZ_OR_2_OA_CONTROLLER 0.755069 0.249188
PSZ_OR_3_OA_CONTROLLER 0.748776 0.247111
PSZ_XRAY_OA_CONTROLLER 1.07 0.127426
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:TwoSpeed

Design Size High Speed Rated Air Flow Rate [m3/s] Design Size High Speed Gross Rated Total Cooling Capacity [W] Design Size High Speed Rated Sensible Heat Ratio Design Size Low Speed Rated Air Flow Rate [m3/s] Design Size Low Speed Gross Rated Total Cooling Capacity [W] Design Size Low Speed Gross Rated Sensible Heat Ratio
AHU-1 COOLING COIL 5.54 137630.08 0.701083 1.85 45872.11 0.701083
AHU-2 COOLING COIL 6.05 141596.54 0.720123 2.02 47194.13 0.720123
AHU-3 COOLING COIL 5.77 137288.61 0.714786 1.92 45758.29 0.714786
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
AHU-1 FAN 5.54
AHU-2 FAN 6.05
AHU-3 FAN 5.77
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
AHU-1 HUMIDIFIER 0.000000 0.000037 96450.70 100000.00
FLOOR 1 MRI CONTROL ROOM HUMIDIFIER 0.000000 0.000037 96450.70 100000.00
FLOOR 1 MRI ROOM HUMIDIFIER 0.000001 0.000037 96450.70 100000.00
FLOOR 1 OPERATING ROOM 1 HUMIDIFIER 0.000001 0.000037 96450.70 100000.00
FLOOR 1 OPERATING ROOM 2 HUMIDIFIER 0.000001 0.000037 96450.70 100000.00
FLOOR 1 OPERATING ROOM 3 HUMIDIFIER 0.000001 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s]
AHU-1_HEATC_CONTROLLER 0.000000
AHU-2_HEATC_CONTROLLER 0.000000
AHU-3_HEATC_CONTROLLER 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
PSZ_CAFE_ADDAQ FAN 0.359306 625.10
PSZ_ELEVATOR_ADDAQ FAN 0.096623 168.10
PSZ_MRI_CONTROL_ADDAQ FAN 0.193873 337.29
PSZ_MRI_ADDAQ FAN 0.464836 799.35
PSZ_OR_1_ADDAQ FAN 0.723607 1244.34
PSZ_OR_2_ADDAQ FAN 0.755069 1298.45
PSZ_OR_3_ADDAQ FAN 0.748776 1287.62
PSZ_XRAY_ADDAQ FAN 1.07 1773.77
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] User-Specified Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Design Size Maximum Supply Air Temperature [C] User-Specified Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ_CAFE_UNITARY_PACKAGE_DX 0.359306 0.359306 0.359306 0.359306 8922.42 5978.02 32.22 8922.42 1.00
PSZ_ELEVATOR_UNITARY_PACKAGE_DX 0.096623 0.096623 0.096623 0.096623 1682.54 1071.64 32.22 1599.46 1.00
PSZ_MRI_CONTROL_UNITARY_PACKAGE_DX 0.193873 0.193873 0.193873 0.193873 4054.94 2598.12 32.22 3877.79 1.00
PSZ_MRI_UNITARY_PACKAGE_DX 0.464836 0.464836 0.464836 0.464836 9890.23 6336.33 32.22 9457.21 1.00
PSZ_OR_1_UNITARY_PACKAGE_DX 0.723607 0.723607 0.723607 0.723607 17968.90 12039.16 29.21 17968.90 1.00
PSZ_OR_2_UNITARY_PACKAGE_DX 0.755069 0.755069 0.755069 0.755069 18750.15 12562.60 29.21 18750.15 1.00
PSZ_OR_3_UNITARY_PACKAGE_DX 0.748776 0.748776 0.748776 0.748776 18593.90 12457.91 29.21 18593.90 1.00
PSZ_XRAY_UNITARY_PACKAGE_DX 1.07 1.07 1.07 1.07 22311.11 14238.87 32.22 21252.04 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
PSZ_CAFE HP COOLING COIL 0.359310 0.179653 0.239540 8922.42 4461.21 0.701080 0.701080
PSZ_ELEVATOR HP COOLING COIL 0.096623 0.048312 0.064415 1682.54 841.27 0.800500 0.800500
PSZ_MRI_CONTROL HP COOLING COIL 0.193870 0.096936 0.129247 4054.94 2027.47 0.758980 0.758980
PSZ_MRI HP COOLING COIL 0.464840 0.232418 0.309893 9890.23 4945.11 0.753040 0.753040
PSZ_OR_1 HP COOLING COIL 0.723610 0.361804 0.482407 17968.90 8984.45 0.701080 0.701080
PSZ_OR_2 HP COOLING COIL 0.755070 0.377534 0.503380 18750.15 9375.08 0.701080 0.701080
PSZ_OR_3 HP COOLING COIL 0.748780 0.374388 0.499187 18593.90 9296.95 0.701080 0.701080
PSZ_XRAY HP COOLING COIL 1.07 0.533627 0.711500 22311.11 11155.56 0.759120 0.759120
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:MultiSpeed

Design Size Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] Design Size Speed 2 Gross Rated Heating Capacity [W] Design Size Speed 1 Gross Rated Heating Capacity [W] Design Size Resistive Defrost Heater Capacity
PSZ_CAFE HEATING COIL 0.359306 0.179653 8922.42 4461.21 0.000000
PSZ_ELEVATOR HEATING COIL 0.096623 0.048312 1599.46 799.73 0.000000
PSZ_MRI_CONTROL HEATING COIL 0.193873 0.096936 3877.79 1938.90 0.000000
PSZ_MRI HEATING COIL 0.464836 0.232418 9457.21 4728.61 0.000000
PSZ_OR_1 HEATING COIL 0.723607 0.361804 17968.90 8984.45 0.000000
PSZ_OR_2 HEATING COIL 0.755069 0.377534 18750.15 9375.08 0.000000
PSZ_OR_3 HEATING COIL 0.748776 0.374388 18593.90 9296.95 0.000000
PSZ_XRAY HEATING COIL 1.07 0.533627 21252.04 10626.02 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
PSZ_CAFE_SUPPHEATCOIL 8922.42
PSZ_ELEVATOR_SUPPHEATCOIL 1599.46
PSZ_MRI_CONTROL_SUPPHEATCOIL 3877.79
PSZ_MRI_SUPPHEATCOIL 9457.21
PSZ_OR_1_SUPPHEATCOIL 17968.90
PSZ_OR_2_SUPPHEATCOIL 18750.15
PSZ_OR_3_SUPPHEATCOIL 18593.90
PSZ_XRAY_SUPPHEATCOIL 21252.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.001169 0.140293
SWHSYS1 0.000063 0.007580
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
HEATSYS1 PUMP 0.001169 352.09 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 133636.71 133636.71 0.001169
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000063 8.07
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000063
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
5F762C 84418A | 1535AC | B40F89 | 3330D8 | 1775A6 | 38B339 |
84FB73 8E5BB9 | AF0124 |
7F5C82 E7B55F |
C732B0 8E5BB9 | 5507DC |
FE5A3C FB3814 |
F629C1 8E5BB9 | AF0124 |
577FC1 88E360 |
FLOOR 1 MED GAS ROOF 9EC269 | B316F7 | 9621FD | 42CEE1 | F209CC | 155BD6 | C5EA55 | 5E657E | 9C3A6A | C52EE0 | F7D24D | FC22D1 | 68A2D7 | CE3FEF | 5ADC59 | 88E360 | 2E2D0C | AF0124 |
C114C1 8E5BB9 | AF0124 |
ADB8D0 8E5BB9 | AF0124 |
E326E4 E7B55F |
1D96D7 E7B55F |
84418A 5F762C | A5A6A3 | EA6DC8 | 4ABC66 | 8D1BC4 | 1DEE26 | FB3814 | AF0124 | 850EA7 |
1535AC 5F762C | A5A6A3 | EA6DC8 | 4ABC66 | 8D1BC4 | 1DEE26 | FB3814 | AF0124 | 850EA7 |
6D2616 8E5BB9 | AF0124 |
A5A6A3 84418A | 1535AC | B40F89 | 3330D8 | 1775A6 | 38B339 |
EA6DC8 84418A | 1535AC | B40F89 | 3330D8 | 1775A6 | 38B339 |
B40F89 5F762C | A5A6A3 | EA6DC8 | 4ABC66 | 8D1BC4 | 1DEE26 | FB3814 | AF0124 | 850EA7 |
8E5BB9 84FB73 | C732B0 | F629C1 | C114C1 | ADB8D0 | 6D2616 | 9621FD | 42CEE1 | 155BD6 | C5EA55 | 5E657E | 9C3A6A | C52EE0 | F7D24D | FC22D1 | 5ADC59 | 2E2D0C | AF0124 |
FLOOR 1 STORGE ROOF 9EC269 | B316F7 | 9621FD | 42CEE1 | F209CC | 155BD6 | C5EA55 | 5E657E | 9C3A6A | C52EE0 | F7D24D | FC22D1 | 68A2D7 | CE3FEF | 5ADC59 | 88E360 | 2E2D0C | AF0124 |
61E610 E7B55F |
529072 88E360 |
FLOOR 1 UTILITY HALL ROOF 9EC269 | B316F7 | 9621FD | 42CEE1 | F209CC | 155BD6 | C5EA55 | 5E657E | 9C3A6A | C52EE0 | F7D24D | FC22D1 | 68A2D7 | CE3FEF | 5ADC59 | 88E360 | 2E2D0C | AF0124 |
D95F04 E7B55F |
3330D8 5F762C | A5A6A3 | EA6DC8 | 4ABC66 | 8D1BC4 | 1DEE26 | FB3814 | AF0124 | 850EA7 |
208CCF E7B55F |
1775A6 4ABC66 | 8D1BC4 | 1DEE26 | FB3814 | AF0124 | 850EA7 |
B4E619 E7B55F |
9EC269 AF0124 |
B316F7 AF0124 |
9621FD AF0124 |
42CEE1 AF0124 |
F209CC AF0124 |
155BD6 AF0124 |
C5EA55 AF0124 |
5E657E 5507DC |
4B1439 E7B55F |
4ABC66 1775A6 | 38B339 |
5B04CF FB3814 |
8D1BC4 1775A6 | 38B339 |
4B55FA E7B55F |
9C3A6A AF0124 |
C52EE0 5507DC |
1C33AD FB3814 |
F7D24D 5507DC |
FC22D1 5507DC |
68A2D7 AF0124 |
CE3FEF AF0124 |
CE618F E7B55F |
5ADC59 AF0124 |
D4F411 FB3814 |
D22917 E7B55F |
38B339 1DEE26 | FB3814 | AF0124 | 850EA7 |
BE5F2F FB3814 |
1DEE26 38B339 |
C86329 E7B55F |
88E360 577FC1 | 529072 | AF0124 |
E7B55F 7F5C82 | E326E4 | 1D96D7 | 61E610 | D95F04 | 208CCF | B4E619 | 4B1439 | 4B55FA | CE618F | D22917 | C86329 |
FB3814 FE5A3C | 84418A | 1535AC | B40F89 | 3330D8 | 1775A6 | 5B04CF | 1C33AD | D4F411 | 38B339 | BE5F2F | 270BCE |
5507DC C732B0 | 5E657E | C52EE0 | F7D24D | FC22D1 |
2E2D0C 8E5BB9 |
AF0124 84FB73 | F629C1 | C114C1 | ADB8D0 | 84418A | 1535AC | 6D2616 | B40F89 | 8E5BB9 | 3330D8 | 1775A6 | 9EC269 | B316F7 | 9621FD | 42CEE1 | F209CC | 155BD6 | C5EA55 | 9C3A6A | 68A2D7 | CE3FEF | 5ADC59 | 38B339 | 88E360 |
850EA7 84418A | 1535AC | B40F89 | 3330D8 | 1775A6 | 38B339 |
270BCE FB3814 |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
481E71 78F987 |
5F762C D8037E |
84FB73 4A8120 |
E02487 BA05F7 |
FE5A3C F67E1F | AAE778 |
F629C1 3AAD8B | 8128A9 |
E85BB5 7EB6E7 |
C114C1 D18914 |
879583 9B1541 | CF850A |
E326E4 D4B39B | A6BA23 | D10D28 |
1D96D7 591336 | 38B811 | C044D6 |
6D2616 1D94BE | 18748E |
A5A6A3 137A56 |
28B002 D2D3BC | C528DA | EFD3F9 | 8D508E | B2D381 | 1DA13A | 44E54A |
EA6DC8 757D10 |
B40F89 E33BAE |
997723 62B5AF | 24167A | 2C0938 |
CEC7BD 8600DD |
8E5BB9 71E924 |
859BC1 3C44F9 | 49526E | 865AE8 | A1ED60 | E8D997 | 88E1FC |
61E610 F83F33 |
529072 5E66D1 |
D95F04 E14DAE | B1F5EE |
3330D8 84A1D5 |
208CCF F52F3D |
AEF992 80885D |
54D065 FEEF06 |
1775A6 2BE8DE | 513E2A | BA5CD9 |
97F00A 1AD478 |
A497E9 27F0AC |
88A75F 724114 |
B4E619 D538C4 | 5635BC |
9EC269 831C1D |
B316F7 9BB95F | C0778D |
9621FD 7D2D69 | 2EF63B |
42CEE1 C417C0 |
4B1439 EB042B | 4C1F71 | D23C8B | B4E4BE |
4ABC66 EEF55D | E55A57 |
5B04CF 93D018 |
4B55FA DD9F5D |
9C3A6A 15B02B | 820282 |
68A2D7 9BA05A | C639E8 |
CE3FEF A2790A |
CE618F 79FCEE | EDE617 |
5ADC59 C61F0D | 7248C5 | 29FA28 | F0B23F | EEC10E | 944FCE | C41399 |
D22917 95BA33 | F27282 |
C1BC97 3DB407 | 3DADE2 | DF3E2C | 5031C8 |
8DA7DB C087D0 | D2CA75 | B0FB49 |
38B339 FE9BC9 | 9DF7DE | D0BE44 |
BE5F2F 6B5226 |
1DEE26 8F59F7 | 44F571 |
C86329 6BD844 | 86D536 | BAF71D | 3833A2 |
DFC6F0 2111A1 |
88E360 9CB8E5 | E4A528 | 9BC521 | 142781 |
FB3814 24BAF7 |
FCD12D 19E57D |
5507DC EDE769 |
2E2D0C 1C9872 | E74902 | 93BBC3 |
850EA7 C635A6 |
270BCE F402E9 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 26.30 23.60 20.30 19.40 20.90 21.60 24.10 26.40 27.70 28.10 28.00 27.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Miami Intl Ap FL USA TMY3 WMO#=722020 25.82 -80.30 -5.00 11.00 101193 1.2027


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 24.49 8.70 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OutPatientHealthCare 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 118 1395 117


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 FLOOR 1 ANESTHESIA 0.0 39.32 0.00 0.00 40.69 1.83 1.52 1 1 1 39.32 42.06 0.00 3.66 0.00 3.05 3.05 30.58 TARP DOE-2 10.03 8.36 6.13 2.23 7 1 0 Yes
2 FLOOR 1 BIO HAZ 0.0 39.32 25.91 0.00 41.00 27.13 1.52 1 1 1 39.93 42.06 25.91 28.35 0.00 3.05 3.05 15.86 TARP DOE-2 5.20 0.00 0.00 0.00 6 0 0 Yes
3 FLOOR 1 CAFE 0.0 0.00 19.20 0.00 8.84 12.34 1.52 1 1 1 5.79 11.89 9.14 15.54 0.00 3.05 3.05 118.93 TARP DOE-2 39.02 18.58 9.66 8.92 7 1 0 Yes
4 FLOOR 1 CLEAN 0.0 29.26 8.84 0.00 30.63 10.97 1.52 1 1 1 29.26 32.00 8.84 13.11 0.00 3.05 3.05 35.68 TARP DOE-2 11.71 0.00 0.00 0.00 9 0 0 Yes
5 FLOOR 1 CLEAN WORK 0.0 42.06 9.75 0.00 39.78 11.43 1.52 1 1 1 37.49 42.06 9.75 13.11 0.00 3.05 3.05 46.72 TARP DOE-2 15.33 0.00 0.00 0.00 8 0 0 Yes
6 FLOOR 1 DICTATION 0.0 32.00 8.84 0.00 33.38 10.97 1.52 1 1 1 32.00 34.75 8.84 13.11 0.00 3.05 3.05 35.68 TARP DOE-2 11.71 0.00 0.00 0.00 8 0 0 Yes
7 FLOOR 1 DRESSING ROOM 0.0 15.54 28.35 0.00 14.17 27.58 1.52 1 1 1 12.80 15.54 26.82 28.35 0.00 3.05 3.05 12.74 TARP DOE-2 4.18 8.36 6.04 2.32 6 1 0 Yes
8 FLOOR 1 ELECTRICAL ROOM 0.0 50.60 18.59 0.00 48.46 19.66 1.52 1 1 1 46.33 50.60 18.59 20.73 0.00 3.05 3.05 27.75 TARP DOE-2 9.10 6.50 6.50 0.00 6 0 0 Yes
9 FLOOR 1 ELEVATOR PUMP ROOM 0.0 3.96 28.35 0.00 1.98 27.28 1.52 1 1 1 0.00 3.96 26.21 28.35 0.00 3.05 3.05 25.77 TARP DOE-2 8.45 18.58 16.63 0.00 8 1 0 Yes
10 FLOOR 1 HUMID 0.0 32.00 14.94 0.00 30.63 14.02 1.52 1 1 1 29.26 32.00 13.11 14.94 0.00 3.05 3.05 15.29 TARP DOE-2 5.02 0.00 0.00 0.00 6 0 0 Yes
11 FLOOR 1 IT HALL 0.0 33.53 25.91 0.00 37.80 25.15 1.52 1 1 1 33.53 42.06 24.38 25.91 0.00 3.05 3.05 39.64 TARP DOE-2 13.01 0.00 0.00 0.00 10 0 0 Yes
12 FLOOR 1 IT ROOM 0.0 37.19 28.35 0.00 35.66 27.13 1.52 1 1 1 33.53 37.80 25.91 28.35 0.00 3.05 3.05 31.71 TARP DOE-2 10.41 0.00 0.00 0.00 6 0 0 Yes
13 FLOOR 1 LOBBY 0.0 2.13 24.38 0.00 4.17 20.93 1.52 1 1 1 2.13 6.40 11.58 28.35 0.00 3.05 3.05 176.13 TARP DOE-2 57.79 20.44 9.57 8.92 17 2 0 Yes
14 FLOOR 1 LOBBY HALL 0.0 11.89 19.20 0.00 8.84 17.37 1.52 1 1 1 5.79 11.89 15.54 19.20 0.00 3.05 3.05 67.96 TARP DOE-2 22.30 0.00 0.00 0.00 8 0 0 Yes
15 FLOOR 1 LOBBY TOILET 0.0 0.00 26.21 0.00 1.37 25.30 1.52 1 1 1 0.00 2.74 24.38 26.21 0.00 3.05 3.05 15.29 TARP DOE-2 5.02 5.57 5.57 0.00 7 0 0 Yes
16 FLOOR 1 LOCKER ROOM 0.0 29.87 28.35 0.00 26.52 23.77 1.52 1 1 1 23.16 29.87 19.20 28.35 0.00 3.05 3.05 186.89 TARP DOE-2 61.32 20.44 14.86 5.57 11 2 0 Yes
17 FLOOR 1 LOCKER ROOM HALL 0.0 23.16 19.20 0.00 32.61 17.98 1.52 1 1 1 23.16 42.06 16.76 19.20 0.00 3.05 3.05 140.45 TARP DOE-2 46.08 0.00 0.00 0.00 17 0 0 Yes
18 FLOOR 1 LOUNGE 0.0 29.87 19.20 0.00 31.70 23.77 1.52 1 1 1 29.87 33.53 19.20 28.35 0.00 3.05 3.05 101.94 TARP DOE-2 33.45 0.00 0.00 0.00 9 0 0 Yes
19 FLOOR 1 MED GAS 0.0 44.50 33.22 0.00 43.28 34.29 1.52 1 1 1 42.06 44.50 33.22 35.36 0.00 3.05 3.05 15.86 TARP DOE-2 5.20 13.94 11.98 0.00 6 1 0 Yes
20 FLOOR 1 MRI CONTROL ROOM 0.0 12.80 28.35 0.00 9.60 27.13 1.52 1 1 1 6.40 12.80 25.91 28.35 0.00 3.05 3.05 47.57 TARP DOE-2 15.61 4.65 2.69 0.00 9 1 0 Yes
21 FLOOR 1 MRI HALL 0.0 11.89 25.91 0.00 14.50 25.26 1.52 1 1 1 11.89 17.37 23.77 26.82 0.00 3.05 3.05 41.63 TARP DOE-2 13.66 0.00 0.00 0.00 11 0 0 Yes
22 FLOOR 1 MRI ROOM 0.0 6.71 25.91 0.00 8.84 22.56 1.52 1 1 1 5.79 11.89 19.20 25.91 0.00 3.05 3.05 124.59 TARP DOE-2 40.88 0.00 0.00 0.00 8 0 0 Yes
23 FLOOR 1 MRI TOILET 0.0 17.37 28.35 0.00 16.46 26.97 1.52 1 1 1 15.54 17.37 25.60 28.35 0.00 3.05 3.05 15.29 TARP DOE-2 5.02 5.57 5.57 0.00 7 0 0 Yes
24 FLOOR 1 NOURISHMENT 0.0 27.13 16.76 0.00 28.19 12.80 1.52 1 1 1 27.13 29.26 8.84 16.76 0.00 3.05 3.05 51.54 TARP DOE-2 16.91 0.00 0.00 0.00 12 0 0 Yes
25 FLOOR 1 NURSE HALL 0.0 39.32 3.66 0.00 32.61 4.88 1.52 1 1 1 23.16 42.06 3.66 6.10 0.00 3.05 3.05 140.45 TARP DOE-2 46.08 0.00 0.00 0.00 16 0 0 Yes
26 FLOOR 1 NURSE JANITOR 0.0 29.26 16.76 0.00 30.63 15.85 1.52 1 1 1 29.26 32.00 14.94 16.76 0.00 3.05 3.05 15.29 TARP DOE-2 5.02 0.00 0.00 0.00 7 0 0 Yes
27 FLOOR 1 NURSE STATION 0.0 32.00 8.84 0.00 27.58 7.47 1.52 1 1 1 23.16 32.00 6.10 8.84 0.00 3.05 3.05 73.91 TARP DOE-2 24.25 0.00 0.00 0.00 11 0 0 Yes
28 FLOOR 1 NURSE TOILET 0.0 37.49 8.84 0.00 36.58 7.47 1.52 1 1 1 35.66 37.49 6.10 8.84 0.00 3.05 3.05 15.29 TARP DOE-2 5.02 0.00 0.00 0.00 6 0 0 Yes
29 FLOOR 1 OFFICE 0.0 14.63 15.85 0.00 17.53 20.27 1.52 1 1 1 14.33 20.73 16.76 23.77 0.00 3.05 3.05 136.77 TARP DOE-2 44.87 0.00 0.00 0.00 10 0 0 Yes
30 FLOOR 1 OPERATING ROOM 1 0.0 44.81 0.00 0.00 47.55 3.51 1.52 1 1 1 44.50 50.60 0.00 7.01 0.00 3.05 3.05 130.26 TARP DOE-2 42.74 39.95 27.58 10.41 9 5 0 Yes
31 FLOOR 1 OPERATING ROOM 2 0.0 50.60 11.28 0.00 47.55 14.94 1.52 1 1 1 44.50 50.60 11.28 18.59 0.00 3.05 3.05 135.92 TARP DOE-2 44.59 22.30 13.37 8.93 10 3 0 Yes
32 FLOOR 1 OPERATING ROOM 3 0.0 33.53 19.20 0.00 37.80 21.79 1.52 1 1 1 33.53 42.06 19.20 24.38 0.00 3.05 3.05 134.79 TARP DOE-2 44.22 0.00 0.00 0.00 11 0 0 Yes
33 FLOOR 1 PACU 0.0 35.66 8.84 0.00 33.83 7.47 1.52 1 1 1 32.00 35.66 6.10 8.84 0.00 3.05 3.05 30.58 TARP DOE-2 10.03 0.00 0.00 0.00 7 0 0 Yes
34 FLOOR 1 PRE-OP HALL 0.0 20.73 23.77 0.00 21.95 13.72 1.52 1 1 1 20.73 23.16 3.66 23.77 0.00 3.05 3.05 149.51 TARP DOE-2 49.05 0.00 0.00 0.00 20 0 0 Yes
35 FLOOR 1 PRE-OP ROOM 1 0.0 17.98 13.41 0.00 19.35 11.13 1.52 1 1 1 17.98 20.73 7.92 14.33 0.00 3.05 3.05 53.52 TARP DOE-2 17.56 3.72 3.72 0.00 9 0 0 Yes
36 FLOOR 1 PRE-OP ROOM 2 0.0 24.38 8.84 0.00 25.15 12.80 1.52 1 1 1 23.16 27.13 8.84 16.76 0.00 3.05 3.05 95.71 TARP DOE-2 31.40 0.00 0.00 0.00 11 0 0 Yes
37 FLOOR 1 PRE-OP TOILET 0.0 17.98 5.49 0.00 19.35 4.57 1.52 1 1 1 17.98 20.73 3.66 5.49 0.00 3.05 3.05 15.29 TARP DOE-2 5.02 5.57 5.57 0.00 6 0 0 Yes
38 FLOOR 1 PROCEDURE ROOM 0.0 22.86 28.35 0.00 20.27 26.06 1.52 1 1 1 17.37 23.16 23.77 28.35 0.00 3.05 3.05 80.70 TARP DOE-2 26.48 17.65 12.08 5.57 10 2 0 Yes
39 FLOOR 1 RECEPTION 0.0 9.75 9.14 0.00 13.70 16.13 1.52 1 1 1 11.89 15.85 9.14 23.77 0.00 3.05 3.05 144.13 TARP DOE-2 47.29 12.08 8.73 3.34 13 1 0 Yes
40 FLOOR 1 RECEPTION HALL 0.0 20.73 14.33 0.00 18.29 15.54 1.52 1 1 1 15.85 20.73 14.33 16.76 0.00 3.05 3.05 36.25 TARP DOE-2 11.89 0.00 0.00 0.00 9 0 0 Yes
41 FLOOR 1 RECOVERY ROOM 0.0 20.42 0.00 0.00 32.46 1.83 1.52 1 1 1 25.60 39.32 0.00 3.66 0.00 3.05 3.05 152.91 TARP DOE-2 50.17 41.81 27.03 8.92 9 7 0 Yes
42 FLOOR 1 SCHEDULING 0.0 15.85 9.14 0.00 16.92 11.73 1.52 1 1 1 15.85 17.98 9.14 14.33 0.00 3.05 3.05 33.70 TARP DOE-2 11.06 6.50 5.76 0.74 7 1 0 Yes
43 FLOOR 1 SCRUB 0.0 44.50 11.28 0.00 45.42 9.14 1.52 1 1 1 44.50 46.33 7.01 11.28 0.00 3.05 3.05 23.79 TARP DOE-2 7.80 0.00 0.00 0.00 6 0 0 Yes
44 FLOOR 1 SOIL 0.0 34.75 13.11 0.00 36.12 10.97 1.52 1 1 1 34.75 37.49 8.84 13.11 0.00 3.05 3.05 35.68 TARP DOE-2 11.71 0.00 0.00 0.00 10 0 0 Yes
45 FLOOR 1 SOIL HOLD 0.0 37.19 25.91 0.00 38.86 27.13 1.52 1 1 1 37.80 39.93 25.91 28.35 0.00 3.05 3.05 15.86 TARP DOE-2 5.20 0.00 0.00 0.00 7 0 0 Yes
46 FLOOR 1 SOIL WORK 0.0 42.06 6.10 0.00 39.78 7.92 1.52 1 1 1 37.49 42.06 6.10 9.75 0.00 3.05 3.05 50.97 TARP DOE-2 16.72 0.00 0.00 0.00 10 0 0 Yes
47 FLOOR 1 STEP DOWN 0.0 20.42 0.00 0.00 21.79 1.83 1.52 1 1 1 17.98 25.60 0.00 3.66 0.00 3.05 3.05 84.95 TARP DOE-2 27.87 34.37 25.73 6.69 10 4 0 Yes
48 FLOOR 1 STERILE HALL 0.0 42.06 0.00 0.00 43.28 11.73 1.52 1 1 1 42.06 44.50 0.00 23.47 0.00 3.05 3.05 174.43 TARP DOE-2 57.23 7.43 5.20 2.23 23 1 0 Yes
49 FLOOR 1 STERILE STORAGE 0.0 32.00 13.11 0.00 37.03 14.94 1.52 1 1 1 32.00 42.06 13.11 16.76 0.00 3.05 3.05 112.13 TARP DOE-2 36.79 0.00 0.00 0.00 11 0 0 Yes
50 FLOOR 1 STORAGE 0.0 41.45 35.36 0.00 35.97 31.85 1.52 1 1 1 29.87 42.06 28.35 35.36 0.00 3.05 3.05 260.52 TARP DOE-2 85.47 58.53 41.34 8.36 10 7 0 Yes
51 FLOOR 1 SUB-STERILE 0.0 50.60 7.01 0.00 48.46 9.14 1.52 1 1 1 46.33 50.60 7.01 11.28 0.00 3.05 3.05 55.50 TARP DOE-2 18.21 13.01 9.04 3.97 6 1 0 Yes
52 FLOOR 1 UTILITY HALL 0.0 44.50 28.96 0.00 43.28 28.35 1.52 1 1 1 42.06 44.50 23.47 33.22 0.00 3.05 3.05 72.49 TARP DOE-2 23.78 14.86 7.43 0.00 13 1 0 Yes
53 FLOOR 1 UTILITY JANITOR 0.0 44.50 20.73 0.00 45.42 19.66 1.52 1 1 1 44.50 46.33 18.59 20.73 0.00 3.05 3.05 11.89 TARP DOE-2 3.90 0.00 0.00 0.00 6 0 0 Yes
54 FLOOR 1 UTILITY ROOM 0.0 50.60 20.73 0.00 47.55 23.47 1.52 1 1 1 44.50 50.60 20.73 26.21 0.00 3.05 3.05 101.94 TARP DOE-2 33.45 16.72 11.79 2.98 9 2 0 Yes
55 FLOOR 1 VESTIBULE 0.0 17.98 7.92 0.00 19.35 6.71 1.52 1 1 1 17.98 20.73 5.49 7.92 0.00 3.05 3.05 20.39 TARP DOE-2 6.69 7.43 5.48 0.00 6 1 0 Yes
56 FLOOR 2 CONFERENCE 0.0 50.60 0.00 3.05 46.33 1.83 4.57 1 1 1 42.06 50.60 0.00 3.66 3.05 6.10 3.05 95.14 TARP DOE-2 31.22 37.16 27.50 9.67 9 2 0 Yes
57 FLOOR 2 CONFERENCE TOILET 0.0 44.50 6.10 3.05 43.28 4.88 4.57 1 1 1 42.06 44.50 3.66 6.10 3.05 6.10 3.05 18.12 TARP DOE-2 5.95 0.00 0.00 0.00 6 0 0 Yes
58 FLOOR 2 DICTATION 0.0 42.06 9.14 3.05 41.00 7.62 4.57 1 1 1 39.93 42.06 6.10 9.14 3.05 6.10 3.05 19.82 TARP DOE-2 6.50 0.00 0.00 0.00 6 0 0 Yes
59 FLOOR 2 EXAM 1 0.0 17.98 0.00 3.05 19.81 4.57 4.57 1 1 1 17.98 21.64 0.00 9.14 3.05 6.10 3.05 101.94 TARP DOE-2 33.45 39.02 30.10 8.92 10 4 0 Yes
60 FLOOR 2 EXAM 2 0.0 23.47 0.00 3.05 26.21 4.57 4.57 1 1 1 23.47 28.96 0.00 9.14 3.05 6.10 3.05 152.91 TARP DOE-2 50.17 16.72 13.01 3.72 11 1 0 Yes
61 FLOOR 2 EXAM 3 0.0 30.78 0.00 3.05 34.44 4.57 4.57 1 1 1 30.78 38.10 0.00 9.14 3.05 6.10 3.05 203.88 TARP DOE-2 66.89 22.30 16.35 5.95 16 1 0 Yes
62 FLOOR 2 EXAM 4 0.0 39.93 0.00 3.05 41.00 1.83 4.57 1 1 1 39.93 42.06 0.00 3.66 3.05 6.10 3.05 23.79 TARP DOE-2 7.80 6.50 4.27 2.23 6 1 0 Yes
63 FLOOR 2 EXAM 5 0.0 50.60 18.59 3.05 48.46 22.40 4.57 1 1 1 46.33 50.60 18.59 26.21 3.05 6.10 3.05 99.11 TARP DOE-2 32.52 23.23 15.29 7.94 7 2 0 Yes
64 FLOOR 2 EXAM 6 0.0 44.50 28.35 3.05 42.21 26.06 4.57 1 1 1 39.93 44.50 23.77 28.35 3.05 6.10 3.05 63.71 TARP DOE-2 20.90 13.94 9.75 4.18 10 1 0 Yes
65 FLOOR 2 EXAM 7 0.0 38.10 28.35 3.05 34.44 23.32 4.57 1 1 1 30.78 38.10 18.29 28.35 3.05 6.10 3.05 224.27 TARP DOE-2 73.58 22.30 16.72 5.57 15 2 0 Yes
66 FLOOR 2 EXAM 8 0.0 28.96 28.35 3.05 26.21 26.06 4.57 1 1 1 23.47 28.96 23.77 28.35 3.05 6.10 3.05 76.46 TARP DOE-2 25.08 16.72 11.15 5.57 6 2 0 Yes
67 FLOOR 2 EXAM 9 0.0 21.64 28.35 3.05 19.81 23.32 4.57 1 1 1 17.98 21.64 18.29 28.35 3.05 6.10 3.05 112.13 TARP DOE-2 36.79 11.15 8.36 2.79 8 1 0 Yes
68 FLOOR 2 EXAM HALL 1 0.0 21.64 0.00 3.05 22.56 4.57 4.57 1 1 1 21.64 23.47 0.00 9.14 3.05 6.10 3.05 50.97 TARP DOE-2 16.72 5.57 5.57 0.00 10 0 0 Yes
69 FLOOR 2 EXAM HALL 2 0.0 28.96 0.00 3.05 29.87 4.57 4.57 1 1 1 28.96 30.78 0.00 9.14 3.05 6.10 3.05 50.97 TARP DOE-2 16.72 5.57 5.57 0.00 10 0 0 Yes
70 FLOOR 2 EXAM HALL 3 0.0 38.10 0.00 3.05 39.01 4.57 4.57 1 1 1 38.10 39.93 0.00 9.14 3.05 6.10 3.05 50.97 TARP DOE-2 16.72 5.57 5.57 0.00 12 0 0 Yes
71 FLOOR 2 EXAM HALL 4 0.0 39.93 28.35 3.05 39.01 23.32 4.57 1 1 1 38.10 39.93 18.29 28.35 3.05 6.10 3.05 56.07 TARP DOE-2 18.39 5.57 5.57 0.00 11 0 0 Yes
72 FLOOR 2 EXAM HALL 5 0.0 30.78 28.35 3.05 29.87 23.32 4.57 1 1 1 28.96 30.78 18.29 28.35 3.05 6.10 3.05 56.07 TARP DOE-2 18.39 5.57 5.57 0.00 10 0 0 Yes
73 FLOOR 2 EXAM HALL 6 0.0 23.47 28.35 3.05 22.56 23.32 4.57 1 1 1 21.64 23.47 18.29 28.35 3.05 6.10 3.05 56.07 TARP DOE-2 18.39 5.57 5.57 0.00 11 0 0 Yes
74 FLOOR 2 JANITOR 0.0 0.00 28.35 3.05 1.37 27.28 4.57 1 1 1 0.00 2.74 26.21 28.35 3.05 6.10 3.05 17.84 TARP DOE-2 5.85 14.86 14.86 0.00 6 0 0 Yes
75 FLOOR 2 LOUNGE 0.0 44.50 9.14 3.05 43.28 7.62 4.57 1 1 1 42.06 44.50 6.10 9.14 3.05 6.10 3.05 22.65 TARP DOE-2 7.43 0.00 0.00 0.00 6 0 0 Yes
76 FLOOR 2 NURSE STATION 1 0.0 39.01 21.34 3.05 42.21 19.81 4.57 1 1 1 39.93 44.50 18.29 21.34 3.05 6.10 3.05 42.48 TARP DOE-2 13.94 0.00 0.00 0.00 8 0 0 Yes
77 FLOOR 2 NURSE STATION 2 0.0 23.47 21.34 3.05 26.21 19.81 4.57 1 1 1 23.47 28.96 18.29 21.34 3.05 6.10 3.05 50.97 TARP DOE-2 16.72 0.00 0.00 0.00 7 0 0 Yes
78 FLOOR 2 OFFICE 0.0 50.60 3.66 3.05 48.46 9.75 4.57 1 1 1 46.33 50.60 3.66 15.85 3.05 6.10 3.05 158.57 TARP DOE-2 52.03 37.16 25.25 11.91 9 4 0 Yes
79 FLOOR 2 OFFICE HALL 0.0 46.33 3.66 3.05 45.42 14.94 4.57 1 1 1 44.50 46.33 3.66 26.21 3.05 6.10 3.05 125.73 TARP DOE-2 41.25 0.00 0.00 0.00 21 0 0 Yes
80 FLOOR 2 RECEPTION 0.0 2.13 16.46 3.05 8.91 12.84 4.57 1 1 1 2.13 15.85 9.14 16.46 3.05 6.10 3.05 278.64 TARP DOE-2 91.42 45.52 28.80 16.72 12 3 0 Yes
81 FLOOR 2 RECEPTION HALL 0.0 17.98 9.14 3.05 30.18 10.06 4.57 1 1 1 15.85 44.50 9.14 10.97 3.05 6.10 3.05 159.71 TARP DOE-2 52.40 6.50 6.50 0.00 30 0 0 Yes
82 FLOOR 2 RECEPTION TOILET 0.0 17.98 10.97 3.05 16.92 13.72 4.57 1 1 1 15.85 17.98 10.97 16.46 3.05 6.10 3.05 35.68 TARP DOE-2 11.71 0.00 0.00 0.00 7 0 0 Yes
83 FLOOR 2 SCHEDULING 1 0.0 44.50 16.46 3.05 41.76 13.72 4.57 1 1 1 39.01 44.50 10.97 16.46 3.05 6.10 3.05 91.75 TARP DOE-2 30.10 0.00 0.00 0.00 9 0 0 Yes
84 FLOOR 2 SCHEDULING 2 0.0 23.77 16.46 3.05 20.88 13.72 4.57 1 1 1 17.98 23.77 10.97 16.46 3.05 6.10 3.05 96.84 TARP DOE-2 31.77 0.00 0.00 0.00 9 0 0 Yes
85 FLOOR 2 STORAGE 1 0.0 42.06 3.66 3.05 41.00 4.88 4.57 1 1 1 39.93 42.06 3.66 6.10 3.05 6.10 3.05 15.86 TARP DOE-2 5.20 0.00 0.00 0.00 6 0 0 Yes
86 FLOOR 2 STORAGE 2 0.0 39.01 23.77 3.05 42.21 22.56 4.57 1 1 1 39.93 44.50 21.34 23.77 3.05 6.10 3.05 33.98 TARP DOE-2 11.15 0.00 0.00 0.00 8 0 0 Yes
87 FLOOR 2 STORAGE 3 0.0 23.47 21.34 3.05 26.21 22.56 4.57 1 1 1 23.47 28.96 21.34 23.77 3.05 6.10 3.05 40.78 TARP DOE-2 13.38 0.00 0.00 0.00 6 0 0 Yes
88 FLOOR 2 UTILITY 0.0 50.60 18.59 3.05 48.46 17.22 4.57 1 1 1 46.33 50.60 15.85 18.59 3.05 6.10 3.05 35.68 TARP DOE-2 11.71 8.36 5.38 2.98 6 1 0 Yes
89 FLOOR 2 WORK 0.0 17.98 28.35 3.05 10.11 23.44 4.57 1 1 1 2.13 17.98 18.29 28.35 3.05 6.10 3.05 478.55 TARP DOE-2 157.01 24.15 18.58 5.57 22 2 0 Yes
90 FLOOR 2 WORK HALL 0.0 44.50 16.46 3.05 23.33 17.37 4.57 1 1 1 2.13 44.50 16.46 18.29 3.05 6.10 3.05 236.16 TARP DOE-2 77.48 5.57 5.57 0.00 28 0 0 Yes
91 FLOOR 2 WORK TOILET 0.0 0.00 26.21 3.05 1.37 25.30 4.57 1 1 1 0.00 2.74 24.38 26.21 3.05 6.10 3.05 15.29 TARP DOE-2 5.02 5.57 5.57 0.00 7 0 0 Yes
92 FLOOR 2 X-RAY 0.0 39.01 16.46 3.05 31.39 13.72 4.57 1 1 1 23.77 39.01 10.97 16.46 3.05 6.10 3.05 254.85 TARP DOE-2 83.61 0.00 0.00 0.00 18 0 0 Yes
93 FLOOR 3 DRESSING ROOM 0.0 39.01 10.97 6.10 37.95 11.89 7.62 1 1 1 36.88 39.01 10.97 12.80 6.10 9.14 3.05 11.89 TARP DOE-2 3.90 0.00 0.00 0.00 6 0 0 Yes
94 FLOOR 3 ELEVATOR HALL 0.0 5.79 28.35 6.10 3.83 23.43 7.62 1 1 1 2.13 5.79 18.29 28.35 6.10 9.14 3.05 104.77 TARP DOE-2 34.37 3.72 3.72 0.00 10 0 0 Yes
95 FLOOR 3 HUMID 0.0 35.05 16.46 6.10 35.97 13.72 7.62 1 1 1 35.05 36.88 10.97 16.46 6.10 9.14 3.05 30.58 TARP DOE-2 10.03 0.00 0.00 0.00 7 0 0 Yes
96 FLOOR 3 JANITOR 0.0 0.00 28.35 6.10 1.37 27.28 7.62 1 1 1 0.00 2.74 26.21 28.35 6.10 9.14 3.05 17.84 TARP DOE-2 5.85 14.86 14.86 0.00 6 0 0 Yes
97 FLOOR 3 LOCKER 0.0 37.49 20.42 6.10 35.66 21.95 7.62 1 1 1 33.83 37.49 20.42 23.47 6.10 9.14 3.05 33.98 TARP DOE-2 11.15 0.00 0.00 0.00 6 0 0 Yes
98 FLOOR 3 LOUNGE 0.0 37.49 28.35 6.10 41.00 23.32 7.62 1 1 1 37.49 44.50 18.29 28.35 6.10 9.14 3.05 214.92 TARP DOE-2 70.51 21.37 15.79 5.57 13 2 0 Yes
99 FLOOR 3 LOUNGE TOILET 0.0 33.83 23.47 6.10 35.66 25.91 7.62 1 1 1 33.83 37.49 23.47 28.35 6.10 9.14 3.05 54.37 TARP DOE-2 17.84 11.15 6.97 4.18 6 1 0 Yes
100 FLOOR 3 MECHANICAL 0.0 50.60 18.59 6.10 48.46 22.40 7.62 1 1 1 46.33 50.60 18.59 26.21 6.10 9.14 3.05 99.11 TARP DOE-2 32.52 23.23 15.29 7.94 6 2 0 Yes
101 FLOOR 3 MECHANICAL HALL 0.0 46.33 3.66 6.10 45.42 18.59 7.62 1 1 1 44.50 46.33 10.97 26.21 6.10 9.14 3.05 84.95 TARP DOE-2 27.87 0.00 0.00 0.00 10 0 0 Yes
102 FLOOR 3 OFFICE 0.0 33.83 28.35 6.10 19.81 23.32 7.62 1 1 1 5.79 33.83 18.29 28.35 6.10 9.14 3.05 859.70 TARP DOE-2 282.05 68.75 49.24 19.51 16 7 0 Yes
103 FLOOR 3 OFFICE HALL 0.0 2.13 16.46 6.10 23.32 17.37 7.62 1 1 1 2.13 44.50 16.46 18.29 6.10 9.14 3.05 236.16 TARP DOE-2 77.48 5.57 5.57 0.00 14 0 0 Yes
104 FLOOR 3 OFFICE TOILET 0.0 0.00 24.38 6.10 1.37 25.30 7.62 1 1 1 0.00 2.74 24.38 26.21 6.10 9.14 3.05 15.29 TARP DOE-2 5.02 5.57 5.57 0.00 7 0 0 Yes
105 FLOOR 3 PHYSICAL THERAPY 1 0.0 50.60 0.00 6.10 40.69 3.05 7.62 1 1 1 30.78 50.60 0.00 6.10 6.10 9.14 3.05 368.12 TARP DOE-2 120.77 78.97 49.23 29.73 15 6 0 Yes
106 FLOOR 3 PHYSICAL THERAPY 2 0.0 35.05 10.97 6.10 40.69 8.53 7.62 1 1 1 35.05 46.33 6.10 10.97 6.10 9.14 3.05 167.64 TARP DOE-2 55.00 0.00 0.00 0.00 14 0 0 Yes
107 FLOOR 3 PHYSICAL THERAPY TOILET 0.0 39.01 10.97 6.10 37.95 14.63 7.62 1 1 1 36.88 39.01 12.80 16.46 6.10 9.14 3.05 23.79 TARP DOE-2 7.80 0.00 0.00 0.00 6 0 0 Yes
108 FLOOR 3 STORAGE 1 0.0 39.01 10.97 6.10 41.76 11.89 7.62 1 1 1 39.01 44.50 10.97 12.80 6.10 9.14 3.05 30.58 TARP DOE-2 10.03 0.00 0.00 0.00 6 0 0 Yes
109 FLOOR 3 STORAGE 2 0.0 37.49 18.29 6.10 35.66 19.35 7.62 1 1 1 33.83 37.49 18.29 20.42 6.10 9.14 3.05 23.79 TARP DOE-2 7.80 0.00 0.00 0.00 6 0 0 Yes
110 FLOOR 3 TREATMENT 0.0 30.78 0.00 6.10 32.92 11.28 7.62 1 1 1 30.78 35.05 6.10 16.46 6.10 9.14 3.05 134.79 TARP DOE-2 44.22 0.00 0.00 0.00 9 0 0 Yes
111 FLOOR 3 UNDEVELOPED 1 0.0 17.98 0.00 6.10 24.38 8.23 7.62 1 1 1 17.98 30.78 0.00 16.46 6.10 9.14 3.05 642.23 TARP DOE-2 210.70 66.89 41.25 25.64 14 6 0 Yes
112 FLOOR 3 UNDEVELOPED 2 0.0 2.13 11.58 6.10 9.46 12.65 7.62 1 1 1 2.13 17.98 9.14 16.46 6.10 9.14 3.05 326.21 TARP DOE-2 107.02 52.03 38.65 13.38 10 3 0 Yes
113 FLOOR 3 UTILITY 0.0 39.01 16.46 6.10 41.76 14.63 7.62 1 1 1 39.01 44.50 12.80 16.46 6.10 9.14 3.05 61.16 TARP DOE-2 20.07 0.00 0.00 0.00 6 0 0 Yes
114 FLOOR 3 WORK 0.0 50.60 18.59 6.10 48.46 12.34 7.62 1 1 1 46.33 50.60 6.10 18.59 6.10 9.14 3.05 162.54 TARP DOE-2 53.33 38.09 26.18 11.91 8 4 0 Yes
115 NE STAIR 0.0 51.82 26.21 0.00 48.16 27.28 4.57 1 1 1 44.50 51.82 26.21 28.35 0.00 9.14 9.14 142.72 TARP DOE-2 15.61 97.55 81.37 12.27 13 5 0 Yes
116 NW ELEVATOR 0.0 0.00 24.38 0.00 1.07 21.34 4.57 1 1 1 0.00 2.13 18.29 24.38 0.00 9.14 9.14 118.93 TARP DOE-2 13.01 75.25 71.35 0.00 10 2 0 Yes
117 NW STAIR 0.0 12.80 28.35 0.00 7.62 29.57 4.57 1 1 1 3.96 11.28 28.35 30.78 0.00 9.14 9.14 163.11 TARP DOE-2 17.84 111.48 96.43 11.15 10 4 0 Yes
118 SW STAIR 0.0 0.91 11.58 0.00 3.96 10.36 4.57 1 1 1 2.13 5.79 9.14 11.58 0.00 9.14 9.14 81.55 TARP DOE-2 8.92 55.74 52.68 1.11 10 2 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 FLOOR 1 ANESTHESIA 10.03 2.2 4.645 0.215 16.146 21.530 0.000 0.000 0.000 0.000 37.676 No
2 FLOOR 1 BIO HAZ 5.20 0.1 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
3 FLOOR 1 CAFE 39.02 42.0 0.929 1.076 9.688 10.760 0.000 0.000 0.000 0.000 20.448 No
4 FLOOR 1 CLEAN 11.71 2.5 4.645 0.215 16.146 21.530 0.000 0.000 0.000 0.000 37.676 No
5 FLOOR 1 CLEAN WORK 15.33 3.3 4.645 0.215 16.146 21.530 0.000 0.000 0.000 0.000 37.676 No
6 FLOOR 1 DICTATION 11.71 0.6 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
7 FLOOR 1 DRESSING ROOM 4.18 0.2 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
8 FLOOR 1 ELECTRICAL ROOM 9.10 0.1 61.935 1.615E-002 16.146 53.820 0.000 0.000 0.000 0.000 69.966 No
9 FLOOR 1 ELEVATOR PUMP ROOM 8.45 0.1 61.935 1.615E-002 16.146 9511.275 0.000 0.000 0.000 0.000 9527.421 No
10 FLOOR 1 HUMID 5.02 0.3 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
11 FLOOR 1 IT HALL 13.01 0.7 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
12 FLOOR 1 IT ROOM 10.41 0.6 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
13 FLOOR 1 LOBBY 57.79 6.2 9.289 0.108 13.993 11.840 0.000 0.000 0.000 0.000 25.833 No
14 FLOOR 1 LOBBY HALL 22.30 1.2 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
15 FLOOR 1 LOBBY TOILET 5.02 0.3 18.581 5.382E-002 9.688 4.310 0.000 0.000 0.000 0.000 13.998 No
16 FLOOR 1 LOCKER ROOM 61.32 9.9 6.193 0.161 8.611 32.290 0.000 0.000 0.000 0.000 40.901 No
17 FLOOR 1 LOCKER ROOM HALL 46.08 2.5 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
18 FLOOR 1 LOUNGE 33.45 5.4 6.193 0.161 8.611 32.290 0.000 0.000 0.000 0.000 40.901 No
19 FLOOR 1 MED GAS 5.20 0.1 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
20 FLOOR 1 MRI CONTROL ROOM 15.61 3.4 4.645 0.215 16.146 107.640 0.000 0.000 0.000 0.000 123.786 No
21 FLOOR 1 MRI HALL 13.66 0.7 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
22 FLOOR 1 MRI ROOM 40.88 8.8 4.645 0.215 16.146 107.640 0.000 0.000 0.000 0.000 123.786 No
23 FLOOR 1 MRI TOILET 5.02 0.3 18.581 5.382E-002 9.688 4.310 0.000 0.000 0.000 0.000 13.998 No
24 FLOOR 1 NOURISHMENT 16.91 2.7 6.194 0.161 10.764 21.530 0.000 0.000 0.000 0.000 32.294 No
25 FLOOR 1 NURSE HALL 46.08 2.5 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
26 FLOOR 1 NURSE JANITOR 5.02 0.1 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
27 FLOOR 1 NURSE STATION 24.25 3.9 6.194 0.161 10.764 21.530 0.000 0.000 0.000 0.000 32.294 No
28 FLOOR 1 NURSE TOILET 5.02 0.3 18.581 5.382E-002 9.688 4.310 0.000 0.000 0.000 0.000 13.998 No
29 FLOOR 1 OFFICE 44.87 2.4 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
30 FLOOR 1 OPERATING ROOM 1 42.74 9.2 4.645 0.215 23.681 43.060 75.300 0.000 0.000 0.000 142.041 No
31 FLOOR 1 OPERATING ROOM 2 44.59 9.6 4.645 0.215 23.681 43.060 75.300 0.000 0.000 0.000 142.041 No
32 FLOOR 1 OPERATING ROOM 3 44.22 9.5 4.645 0.215 23.681 43.060 75.300 0.000 0.000 0.000 142.041 No
33 FLOOR 1 PACU 10.03 2.2 4.645 0.215 8.611 32.290 0.000 0.000 0.000 0.000 40.901 No
34 FLOOR 1 PRE-OP HALL 49.05 2.6 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
35 FLOOR 1 PRE-OP ROOM 1 17.56 1.9 9.289 0.108 7.535 21.530 0.000 0.000 0.000 0.000 29.065 No
36 FLOOR 1 PRE-OP ROOM 2 31.40 3.4 9.289 0.108 7.535 21.530 0.000 0.000 0.000 0.000 29.065 No
37 FLOOR 1 PRE-OP TOILET 5.02 0.3 18.581 5.382E-002 9.688 4.310 0.000 0.000 0.000 0.000 13.998 No
38 FLOOR 1 PROCEDURE ROOM 26.48 5.7 4.645 0.215 16.146 32.290 0.000 0.000 0.000 0.000 48.436 No
39 FLOOR 1 RECEPTION 47.29 15.3 3.096 0.323 13.993 11.840 0.000 0.000 0.000 0.000 25.833 No
40 FLOOR 1 RECEPTION HALL 11.89 0.6 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
41 FLOOR 1 RECOVERY ROOM 50.17 10.8 4.645 0.215 8.611 32.290 0.000 0.000 0.000 0.000 40.901 No
42 FLOOR 1 SCHEDULING 11.06 0.6 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
43 FLOOR 1 SCRUB 7.80 0.4 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
44 FLOOR 1 SOIL 11.71 2.5 4.645 0.215 16.146 21.530 0.000 0.000 0.000 0.000 37.676 No
45 FLOOR 1 SOIL HOLD 5.20 1.1 4.645 0.215 16.146 21.530 0.000 0.000 0.000 0.000 37.676 No
46 FLOOR 1 SOIL WORK 16.72 3.6 4.645 0.215 16.146 21.530 0.000 0.000 0.000 0.000 37.676 No
47 FLOOR 1 STEP DOWN 27.87 6.0 4.645 0.215 8.611 32.290 0.000 0.000 0.000 0.000 40.901 No
48 FLOOR 1 STERILE HALL 57.23 3.1 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
49 FLOOR 1 STERILE STORAGE 36.79 0.8 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
50 FLOOR 1 STORAGE 85.47 1.8 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
51 FLOOR 1 SUB-STERILE 18.21 1.0 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
52 FLOOR 1 UTILITY HALL 23.78 1.3 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
53 FLOOR 1 UTILITY JANITOR 3.90 8.4E-002 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
54 FLOOR 1 UTILITY ROOM 33.45 0.7 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
55 FLOOR 1 VESTIBULE 6.69 0.4 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
56 FLOOR 2 CONFERENCE 31.22 16.8 1.858 0.538 13.993 10.760 0.000 0.000 0.000 0.000 24.753 No
57 FLOOR 2 CONFERENCE TOILET 5.95 0.3 18.581 5.382E-002 9.688 4.310 0.000 0.000 0.000 0.000 13.998 No
58 FLOOR 2 DICTATION 6.50 0.4 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
59 FLOOR 2 EXAM 1 33.45 7.2 4.645 0.215 16.146 11.840 0.000 0.000 0.000 0.000 27.986 No
60 FLOOR 2 EXAM 2 50.17 10.8 4.645 0.215 16.146 11.840 0.000 0.000 0.000 0.000 27.986 No
61 FLOOR 2 EXAM 3 66.89 14.4 4.645 0.215 16.146 11.840 0.000 0.000 0.000 0.000 27.986 No
62 FLOOR 2 EXAM 4 7.80 1.7 4.645 0.215 16.146 11.840 0.000 0.000 0.000 0.000 27.986 No
63 FLOOR 2 EXAM 5 32.52 7.0 4.645 0.215 16.146 11.840 0.000 0.000 0.000 0.000 27.986 No
64 FLOOR 2 EXAM 6 20.90 4.5 4.645 0.215 16.146 11.840 0.000 0.000 0.000 0.000 27.986 No
65 FLOOR 2 EXAM 7 73.58 15.8 4.645 0.215 16.146 11.840 0.000 0.000 0.000 0.000 27.986 No
66 FLOOR 2 EXAM 8 25.08 5.4 4.645 0.215 16.146 11.840 0.000 0.000 0.000 0.000 27.986 No
67 FLOOR 2 EXAM 9 36.79 7.9 4.645 0.215 16.146 11.840 0.000 0.000 0.000 0.000 27.986 No
68 FLOOR 2 EXAM HALL 1 16.72 0.9 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
69 FLOOR 2 EXAM HALL 2 16.72 0.9 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
70 FLOOR 2 EXAM HALL 3 16.72 0.9 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
71 FLOOR 2 EXAM HALL 4 18.39 1.0 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
72 FLOOR 2 EXAM HALL 5 18.39 1.0 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
73 FLOOR 2 EXAM HALL 6 18.39 1.0 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
74 FLOOR 2 JANITOR 5.85 0.1 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
75 FLOOR 2 LOUNGE 7.43 1.2 6.193 0.161 8.611 32.290 0.000 0.000 0.000 0.000 40.901 No
76 FLOOR 2 NURSE STATION 1 13.94 2.2 6.194 0.161 10.764 21.530 0.000 0.000 0.000 0.000 32.294 No
77 FLOOR 2 NURSE STATION 2 16.72 2.7 6.194 0.161 10.764 21.530 0.000 0.000 0.000 0.000 32.294 No
78 FLOOR 2 OFFICE 52.03 2.8 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
79 FLOOR 2 OFFICE HALL 41.25 2.2 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
80 FLOOR 2 RECEPTION 91.42 29.5 3.096 0.323 13.993 11.840 0.000 0.000 0.000 0.000 25.833 No
81 FLOOR 2 RECEPTION HALL 52.40 2.8 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
82 FLOOR 2 RECEPTION TOILET 11.71 0.6 18.581 5.382E-002 9.688 4.310 0.000 0.000 0.000 0.000 13.998 No
83 FLOOR 2 SCHEDULING 1 30.10 1.6 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
84 FLOOR 2 SCHEDULING 2 31.77 1.7 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
85 FLOOR 2 STORAGE 1 5.20 0.1 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
86 FLOOR 2 STORAGE 2 11.15 0.2 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
87 FLOOR 2 STORAGE 3 13.38 0.3 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
88 FLOOR 2 UTILITY 11.71 0.3 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
89 FLOOR 2 WORK 157.01 8.5 18.579 5.382E-002 11.840 9.780 0.000 0.000 0.000 0.000 21.621 No
90 FLOOR 2 WORK HALL 77.48 4.2 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
91 FLOOR 2 WORK TOILET 5.02 0.3 18.581 5.382E-002 9.688 4.310 0.000 0.000 0.000 0.000 13.998 No
92 FLOOR 2 X-RAY 83.61 18.0 4.645 0.215 16.146 107.640 0.000 0.000 0.000 0.000 123.786 No
93 FLOOR 3 DRESSING ROOM 3.90 0.2 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
94 FLOOR 3 ELEVATOR HALL 34.37 1.9 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
95 FLOOR 3 HUMID 10.03 0.5 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
96 FLOOR 3 JANITOR 5.85 0.1 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
97 FLOOR 3 LOCKER 11.15 1.8 6.193 0.161 8.611 32.290 0.000 0.000 0.000 0.000 40.901 No
98 FLOOR 3 LOUNGE 70.51 11.4 6.193 0.161 8.611 32.290 0.000 0.000 0.000 0.000 40.901 No
99 FLOOR 3 LOUNGE TOILET 17.84 1.0 18.581 5.382E-002 9.688 4.310 0.000 0.000 0.000 0.000 13.998 No
100 FLOOR 3 MECHANICAL 32.52 0.5 61.935 1.615E-002 16.146 53.820 0.000 0.000 0.000 0.000 69.966 No
101 FLOOR 3 MECHANICAL HALL 27.87 1.5 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
102 FLOOR 3 OFFICE 282.05 15.2 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
103 FLOOR 3 OFFICE HALL 77.48 4.2 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
104 FLOOR 3 OFFICE TOILET 5.02 0.3 18.581 5.382E-002 9.688 4.310 0.000 0.000 0.000 0.000 13.998 No
105 FLOOR 3 PHYSICAL THERAPY 1 120.77 26.0 4.645 0.215 9.688 16.150 0.000 0.000 0.000 0.000 25.838 No
106 FLOOR 3 PHYSICAL THERAPY 2 55.00 11.8 4.645 0.215 9.688 16.150 0.000 0.000 0.000 0.000 25.838 No
107 FLOOR 3 PHYSICAL THERAPY TOILET 7.80 0.4 18.581 5.382E-002 9.688 4.310 0.000 0.000 0.000 0.000 13.998 No
108 FLOOR 3 STORAGE 1 10.03 0.2 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
109 FLOOR 3 STORAGE 2 7.80 0.2 46.452 2.153E-002 9.688 1.080 0.000 0.000 0.000 0.000 10.768 No
110 FLOOR 3 TREATMENT 44.22 9.5 4.645 0.215 16.146 11.840 0.000 0.000 0.000 0.000 27.986 No
111 FLOOR 3 UNDEVELOPED 1 210.70 4.5 46.452 2.153E-002 9.688 11.840 0.000 0.000 0.000 0.000 21.528 No
112 FLOOR 3 UNDEVELOPED 2 107.02 2.3 46.452 2.153E-002 9.688 11.840 0.000 0.000 0.000 0.000 21.528 No
113 FLOOR 3 UTILITY 20.07 0.4 46.452 2.153E-002 16.146 1.080 0.000 0.000 0.000 0.000 17.226 No
114 FLOOR 3 WORK 53.33 2.9 18.579 5.382E-002 11.840 11.840 0.000 0.000 0.000 0.000 23.680 No
115 NE STAIR 15.61 0.8 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
116 NW ELEVATOR 13.01 0.2 61.935 1.615E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
117 NW STAIR 17.84 1.0 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No
118 SW STAIR 8.92 0.5 18.581 5.382E-002 10.304 4.310 0.000 0.000 0.000 0.000 14.614 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 FLOOR 1 ANESTHESIA PEOPLE BLDG_OCC_SCH FLOOR 1 ANESTHESIA 10.03 2.2 2.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 FLOOR 1 CAFE PEOPLE BLDG_OCC_SCH FLOOR 1 CAFE 39.02 42.0 42.0 1.076 0.929 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 38 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 FLOOR 1 CLEAN PEOPLE BLDG_OCC_SCH FLOOR 1 CLEAN 11.71 2.5 2.5 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 FLOOR 1 CLEAN WORK PEOPLE BLDG_OCC_SCH FLOOR 1 CLEAN WORK 15.33 3.3 3.3 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 FLOOR 1 DICTATION PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 1 DICTATION 11.71 0.6 0.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 FLOOR 1 DRESSING ROOM PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 1 DRESSING ROOM 4.18 0.2 0.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 FLOOR 1 HUMID PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 1 HUMID 5.02 0.3 0.3 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 FLOOR 1 IT ROOM PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 1 IT ROOM 10.41 0.6 0.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 FLOOR 1 LOBBY PEOPLE BLDG_OCC_SCH FLOOR 1 LOBBY 57.79 6.2 6.2 0.108 9.289 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 FLOOR 1 LOCKER ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 LOCKER ROOM 61.32 9.9 9.9 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 9 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 FLOOR 1 LOUNGE PEOPLE BLDG_OCC_SCH FLOOR 1 LOUNGE 33.45 5.4 5.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 FLOOR 1 MRI CONTROL ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 MRI CONTROL ROOM 15.61 3.4 3.4 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 FLOOR 1 MRI ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 MRI ROOM 40.88 8.8 8.8 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 FLOOR 1 NOURISHMENT PEOPLE BLDG_OCC_SCH FLOOR 1 NOURISHMENT 16.91 2.7 2.7 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 FLOOR 1 NURSE STATION PEOPLE BLDG_OCC_SCH FLOOR 1 NURSE STATION 24.25 3.9 3.9 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 FLOOR 1 OFFICE PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 1 OFFICE 44.87 2.4 2.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 FLOOR 1 OPERATING ROOM 1 PEOPLE BLDG_OCC_SCH FLOOR 1 OPERATING ROOM 1 42.74 9.2 9.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 FLOOR 1 OPERATING ROOM 2 PEOPLE BLDG_OCC_SCH FLOOR 1 OPERATING ROOM 2 44.59 9.6 9.6 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 9 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 FLOOR 1 OPERATING ROOM 3 PEOPLE BLDG_OCC_SCH FLOOR 1 OPERATING ROOM 3 44.22 9.5 9.5 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 9 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 FLOOR 1 PACU PEOPLE BLDG_OCC_SCH FLOOR 1 PACU 10.03 2.2 2.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 FLOOR 1 PRE-OP ROOM 1 PEOPLE BLDG_OCC_SCH FLOOR 1 PRE-OP ROOM 1 17.56 1.9 1.9 0.108 9.289 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 FLOOR 1 PRE-OP ROOM 2 PEOPLE BLDG_OCC_SCH FLOOR 1 PRE-OP ROOM 2 31.40 3.4 3.4 0.108 9.289 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
23 FLOOR 1 PROCEDURE ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 PROCEDURE ROOM 26.48 5.7 5.7 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
24 FLOOR 1 RECEPTION PEOPLE BLDG_OCC_SCH FLOOR 1 RECEPTION 47.29 15.3 15.3 0.323 3.096 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 14 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
25 FLOOR 1 RECOVERY ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 RECOVERY ROOM 50.17 10.8 10.8 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 10 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
26 FLOOR 1 SCHEDULING PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 1 SCHEDULING 11.06 0.6 0.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
27 FLOOR 1 SOIL PEOPLE BLDG_OCC_SCH FLOOR 1 SOIL 11.71 2.5 2.5 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
28 FLOOR 1 SOIL HOLD PEOPLE BLDG_OCC_SCH FLOOR 1 SOIL HOLD 5.20 1.1 1.1 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
29 FLOOR 1 SOIL WORK PEOPLE BLDG_OCC_SCH FLOOR 1 SOIL WORK 16.72 3.6 3.6 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
30 FLOOR 1 STEP DOWN PEOPLE BLDG_OCC_SCH FLOOR 1 STEP DOWN 27.87 6.0 6.0 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
31 FLOOR 2 CONFERENCE PEOPLE MEETINGROOM_OCC_W_SB_SCH FLOOR 2 CONFERENCE 31.22 16.8 16.8 0.538 1.858 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 15 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
32 FLOOR 2 DICTATION PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 2 DICTATION 6.50 0.4 0.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
33 FLOOR 2 EXAM 1 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 1 33.45 7.2 7.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
34 FLOOR 2 EXAM 2 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 2 50.17 10.8 10.8 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 10 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
35 FLOOR 2 EXAM 3 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 3 66.89 14.4 14.4 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
36 FLOOR 2 EXAM 4 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 4 7.80 1.7 1.7 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
37 FLOOR 2 EXAM 5 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 5 32.52 7.0 7.0 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
38 FLOOR 2 EXAM 6 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 6 20.90 4.5 4.5 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
39 FLOOR 2 EXAM 7 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 7 73.58 15.8 15.8 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 14 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
40 FLOOR 2 EXAM 8 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 8 25.08 5.4 5.4 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
41 FLOOR 2 EXAM 9 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 9 36.79 7.9 7.9 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
42 FLOOR 2 LOUNGE PEOPLE BLDG_OCC_SCH FLOOR 2 LOUNGE 7.43 1.2 1.2 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
43 FLOOR 2 NURSE STATION 1 PEOPLE BLDG_OCC_SCH FLOOR 2 NURSE STATION 1 13.94 2.2 2.2 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
44 FLOOR 2 NURSE STATION 2 PEOPLE BLDG_OCC_SCH FLOOR 2 NURSE STATION 2 16.72 2.7 2.7 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
45 FLOOR 2 OFFICE PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 2 OFFICE 52.03 2.8 2.8 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
46 FLOOR 2 RECEPTION PEOPLE BLDG_OCC_SCH FLOOR 2 RECEPTION 91.42 29.5 29.5 0.323 3.096 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 27 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
47 FLOOR 2 SCHEDULING 1 PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 2 SCHEDULING 1 30.10 1.6 1.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
48 FLOOR 2 SCHEDULING 2 PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 2 SCHEDULING 2 31.77 1.7 1.7 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
49 FLOOR 2 WORK PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 2 WORK 157.01 8.5 8.5 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
50 FLOOR 2 X-RAY PEOPLE BLDG_OCC_SCH FLOOR 2 X-RAY 83.61 18.0 18.0 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 16 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
51 FLOOR 3 DRESSING ROOM PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 3 DRESSING ROOM 3.90 0.2 0.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
52 FLOOR 3 HUMID PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 3 HUMID 10.03 0.5 0.5 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
53 FLOOR 3 LOCKER PEOPLE BLDG_OCC_SCH FLOOR 3 LOCKER 11.15 1.8 1.8 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
54 FLOOR 3 LOUNGE PEOPLE BLDG_OCC_SCH FLOOR 3 LOUNGE 70.51 11.4 11.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 10 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
55 FLOOR 3 OFFICE PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 3 OFFICE 282.05 15.2 15.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 14 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
56 FLOOR 3 PHYSICAL THERAPY 1 PEOPLE BLDG_OCC_SCH FLOOR 3 PHYSICAL THERAPY 1 120.77 26.0 26.0 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 23 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
57 FLOOR 3 PHYSICAL THERAPY 2 PEOPLE BLDG_OCC_SCH FLOOR 3 PHYSICAL THERAPY 2 55.00 11.8 11.8 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
58 FLOOR 3 TREATMENT PEOPLE BLDG_OCC_SCH FLOOR 3 TREATMENT 44.22 9.5 9.5 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 9 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
59 FLOOR 3 WORK PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 3 WORK 53.33 2.9 2.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
60 FLOOR 2 STORAGE 1 PEOPLE BLDG_OCC_SCH FLOOR 2 STORAGE 1 5.20 0.1 0.1 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
61 FLOOR 2 STORAGE 2 PEOPLE BLDG_OCC_SCH FLOOR 2 STORAGE 2 11.15 0.2 0.2 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
62 FLOOR 2 STORAGE 3 PEOPLE BLDG_OCC_SCH FLOOR 2 STORAGE 3 13.38 0.3 0.3 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
63 FLOOR 2 UTILITY PEOPLE BLDG_OCC_SCH FLOOR 2 UTILITY 11.71 0.3 0.3 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
64 FLOOR 3 ELEVATOR HALL PEOPLE BLDG_OCC_SCH FLOOR 3 ELEVATOR HALL 34.37 1.9 1.9 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2                      
65 FLOOR 3 JANITOR PEOPLE BLDG_OCC_SCH FLOOR 3 JANITOR 5.85 0.1 0.1 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
66 FLOOR 3 LOUNGE TOILET PEOPLE BLDG_OCC_SCH FLOOR 3 LOUNGE TOILET 17.84 1.0 1.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1                      
67 FLOOR 3 MECHANICAL PEOPLE BLDG_OCC_SCH FLOOR 3 MECHANICAL 32.52 0.5 0.5 1.615E-002 61.935 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
68 FLOOR 3 MECHANICAL HALL PEOPLE BLDG_OCC_SCH FLOOR 3 MECHANICAL HALL 27.87 1.5 1.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1                      
69 FLOOR 3 OFFICE HALL PEOPLE BLDG_OCC_SCH FLOOR 3 OFFICE HALL 77.48 4.2 4.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4                      
70 FLOOR 3 OFFICE TOILET PEOPLE BLDG_OCC_SCH FLOOR 3 OFFICE TOILET 5.02 0.3 0.3 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
71 FLOOR 3 PHYSICAL THERAPY TOILET PEOPLE BLDG_OCC_SCH FLOOR 3 PHYSICAL THERAPY TOILET 7.80 0.4 0.4 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
72 FLOOR 3 STORAGE 1 PEOPLE BLDG_OCC_SCH FLOOR 3 STORAGE 1 10.03 0.2 0.2 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
73 FLOOR 3 STORAGE 2 PEOPLE BLDG_OCC_SCH FLOOR 3 STORAGE 2 7.80 0.2 0.2 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
74 FLOOR 3 UNDEVELOPED 1 PEOPLE BLDG_OCC_SCH FLOOR 3 UNDEVELOPED 1 210.70 4.5 4.5 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4                      
75 FLOOR 3 UNDEVELOPED 2 PEOPLE BLDG_OCC_SCH FLOOR 3 UNDEVELOPED 2 107.02 2.3 2.3 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2                      
76 FLOOR 3 UTILITY PEOPLE BLDG_OCC_SCH FLOOR 3 UTILITY 20.07 0.4 0.4 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
77 NE STAIR PEOPLE BLDG_OCC_SCH NE STAIR 15.61 0.8 0.8 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1                      
78 NW ELEVATOR PEOPLE BLDG_OCC_SCH NW ELEVATOR 13.01 0.2 0.2 1.615E-002 61.935 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
79 NW STAIR PEOPLE BLDG_OCC_SCH NW STAIR 17.84 1.0 1.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1                      
80 SW STAIR PEOPLE BLDG_OCC_SCH SW STAIR 8.92 0.5 0.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0                      
81 FLOOR 1 ELECTRICAL ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 ELECTRICAL ROOM 9.10 0.1 0.1 1.615E-002 61.935 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
82 FLOOR 1 ELEVATOR PUMP ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 ELEVATOR PUMP ROOM 8.45 0.1 0.1 1.615E-002 61.935 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
83 FLOOR 1 IT HALL PEOPLE BLDG_OCC_SCH FLOOR 1 IT HALL 13.01 0.7 0.7 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
84 FLOOR 1 LOBBY HALL PEOPLE BLDG_OCC_SCH FLOOR 1 LOBBY HALL 22.30 1.2 1.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
85 FLOOR 1 LOBBY TOILET PEOPLE BLDG_OCC_SCH FLOOR 1 LOBBY TOILET 5.02 0.3 0.3 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
86 FLOOR 1 LOCKER ROOM HALL PEOPLE BLDG_OCC_SCH FLOOR 1 LOCKER ROOM HALL 46.08 2.5 2.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
87 FLOOR 1 MED GAS PEOPLE BLDG_OCC_SCH FLOOR 1 MED GAS 5.20 0.1 0.1 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
88 FLOOR 1 MRI HALL PEOPLE BLDG_OCC_SCH FLOOR 1 MRI HALL 13.66 0.7 0.7 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
89 FLOOR 1 MRI TOILET PEOPLE BLDG_OCC_SCH FLOOR 1 MRI TOILET 5.02 0.3 0.3 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
90 FLOOR 1 NURSE HALL PEOPLE BLDG_OCC_SCH FLOOR 1 NURSE HALL 46.08 2.5 2.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
91 FLOOR 1 NURSE JANITOR PEOPLE BLDG_OCC_SCH FLOOR 1 NURSE JANITOR 5.02 0.1 0.1 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1E-001 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
92 FLOOR 1 NURSE TOILET PEOPLE BLDG_OCC_SCH FLOOR 1 NURSE TOILET 5.02 0.3 0.3 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
93 FLOOR 1 PRE-OP HALL PEOPLE BLDG_OCC_SCH FLOOR 1 PRE-OP HALL 49.05 2.6 2.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
94 FLOOR 1 PRE-OP TOILET PEOPLE BLDG_OCC_SCH FLOOR 1 PRE-OP TOILET 5.02 0.3 0.3 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
95 FLOOR 1 RECEPTION HALL PEOPLE BLDG_OCC_SCH FLOOR 1 RECEPTION HALL 11.89 0.6 0.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
96 FLOOR 1 SCRUB PEOPLE BLDG_OCC_SCH FLOOR 1 SCRUB 7.80 0.4 0.4 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
97 FLOOR 1 STERILE HALL PEOPLE BLDG_OCC_SCH FLOOR 1 STERILE HALL 57.23 3.1 3.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
98 FLOOR 1 STERILE STORAGE PEOPLE BLDG_OCC_SCH FLOOR 1 STERILE STORAGE 36.79 0.8 0.8 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
99 FLOOR 1 STORAGE PEOPLE BLDG_OCC_SCH FLOOR 1 STORAGE 85.47 1.8 1.8 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
100 FLOOR 1 SUB-STERILE PEOPLE BLDG_OCC_SCH FLOOR 1 SUB-STERILE 18.21 1.0 1.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
101 FLOOR 1 UTILITY HALL PEOPLE BLDG_OCC_SCH FLOOR 1 UTILITY HALL 23.78 1.3 1.3 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
102 FLOOR 1 UTILITY JANITOR PEOPLE BLDG_OCC_SCH FLOOR 1 UTILITY JANITOR 3.90 8.4E-002 8.4E-002 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8E-002 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
103 FLOOR 1 VESTIBULE PEOPLE BLDG_OCC_SCH FLOOR 1 VESTIBULE 6.69 0.4 0.4 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
104 FLOOR 2 CONFERENCE TOILET PEOPLE BLDG_OCC_SCH FLOOR 2 CONFERENCE TOILET 5.95 0.3 0.3 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
105 FLOOR 2 EXAM HALL 1 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM HALL 1 16.72 0.9 0.9 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
106 FLOOR 2 EXAM HALL 2 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM HALL 2 16.72 0.9 0.9 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
107 FLOOR 2 EXAM HALL 3 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM HALL 3 16.72 0.9 0.9 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
108 FLOOR 2 EXAM HALL 4 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM HALL 4 18.39 1.0 1.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
109 FLOOR 2 EXAM HALL 5 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM HALL 5 18.39 1.0 1.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
110 FLOOR 2 EXAM HALL 6 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM HALL 6 18.39 1.0 1.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
111 FLOOR 2 JANITOR PEOPLE BLDG_OCC_SCH FLOOR 2 JANITOR 5.85 0.1 0.1 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
112 FLOOR 2 OFFICE HALL PEOPLE BLDG_OCC_SCH FLOOR 2 OFFICE HALL 41.25 2.2 2.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
113 FLOOR 2 RECEPTION HALL PEOPLE BLDG_OCC_SCH FLOOR 2 RECEPTION HALL 52.40 2.8 2.8 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
114 FLOOR 2 WORK HALL PEOPLE BLDG_OCC_SCH FLOOR 2 WORK HALL 77.48 4.2 4.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
115 FLOOR 2 WORK TOILET PEOPLE BLDG_OCC_SCH FLOOR 2 WORK TOILET 5.02 0.3 0.3 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
116 FLOOR 2 RECEPTION TOILET PEOPLE BLDG_OCC_SCH FLOOR 2 RECEPTION TOILET 11.71 0.6 0.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
117 FLOOR 1 BIO HAZ PEOPLE BLDG_OCC_SCH FLOOR 1 BIO HAZ 5.20 0.1 0.1 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
118 FLOOR 1 UTILITY ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 UTILITY ROOM 33.45 0.7 0.7 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 FLOOR 1 ANESTHESIA_LIGHTS LTG_SCH_ANESTHESIA FLOOR 1 ANESTHESIA 10.03 2.2 162.000 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 162.000
2 FLOOR 1 BIO HAZ_LIGHTS LTG_SCH_STORAGE FLOOR 1 BIO HAZ 5.20 0.1 50.400 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 50.400
3 FLOOR 1 CAFE_LIGHTS LTG_SCH_DINING FLOOR 1 CAFE 39.02 42.0 378.000 9.688 8.999 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 378.000
4 FLOOR 1 CLEAN_LIGHTS LTG_SCH_CLEAN FLOOR 1 CLEAN 11.71 2.5 189.000 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 189.000
5 FLOOR 1 CLEAN WORK_LIGHTS LTG_SCH_CLEAN FLOOR 1 CLEAN WORK 15.33 3.3 247.500 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 247.500
6 FLOOR 1 DICTATION_LIGHTS LTG_SCH_OFFICE FLOOR 1 DICTATION 11.71 0.6 138.600 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 138.600
7 FLOOR 1 DRESSING ROOM_LIGHTS LTG_SCH_OFFICE FLOOR 1 DRESSING ROOM 4.18 0.2 49.500 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 49.500
8 FLOOR 1 ELECTRICAL ROOM_LIGHTS LTG_SCH_EXAM FLOOR 1 ELECTRICAL ROOM 9.10 0.1 147.000 16.146 999.999 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 147.000
9 FLOOR 1 ELEVATOR PUMP ROOM_LIGHTS LTG_SCH_EXAM FLOOR 1 ELEVATOR PUMP ROOM 8.45 0.1 136.500 16.146 999.999 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 136.500
10 FLOOR 1 HUMID_LIGHTS LTG_SCH_OFFICE FLOOR 1 HUMID 5.02 0.3 59.400 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 59.400
11 FLOOR 1 IT HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 1 IT HALL 13.01 0.7 134.019 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 134.019
12 FLOOR 1 IT ROOM_LIGHTS LTG_SCH_OFFICE FLOOR 1 IT ROOM 10.41 0.6 123.200 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 123.200
13 FLOOR 1 LOBBY_LIGHTS LTG_SCH_LOBBY FLOOR 1 LOBBY 57.79 6.2 808.599 13.993 129.987 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 808.599
14 FLOOR 1 LOBBY HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 1 LOBBY HALL 22.30 1.2 229.747 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 229.747
15 FLOOR 1 LOBBY TOILET_LIGHTS LTG_SCH_TOILET FLOOR 1 LOBBY TOILET 5.02 0.3 48.600 9.688 180.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 48.600
16 FLOOR 1 LOCKER ROOM_LIGHTS LTG_SCH_LOUNGE FLOOR 1 LOCKER ROOM 61.32 9.9 527.999 8.611 53.328 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 527.999
17 FLOOR 1 LOCKER ROOM HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 1 LOCKER ROOM HALL 46.08 2.5 474.811 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 474.811
18 FLOOR 1 LOUNGE_LIGHTS LTG_SCH_LOUNGE FLOOR 1 LOUNGE 33.45 5.4 288.000 8.611 53.328 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 288.000
19 FLOOR 1 MED GAS_LIGHTS LTG_SCH_STORAGE FLOOR 1 MED GAS 5.20 0.1 50.400 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 50.400
20 FLOOR 1 MRI CONTROL ROOM_LIGHTS LTG_SCH_RADIOLOGY FLOOR 1 MRI CONTROL ROOM 15.61 3.4 252.000 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 252.000
21 FLOOR 1 MRI HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 1 MRI HALL 13.66 0.7 140.720 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 140.720
22 FLOOR 1 MRI ROOM_LIGHTS LTG_SCH_RADIOLOGY FLOOR 1 MRI ROOM 40.88 8.8 659.999 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 659.999
23 FLOOR 1 MRI TOILET_LIGHTS LTG_SCH_TOILET FLOOR 1 MRI TOILET 5.02 0.3 48.600 9.688 180.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 48.600
24 FLOOR 1 NOURISHMENT_LIGHTS LTG_SCH_NURSE FLOOR 1 NOURISHMENT 16.91 2.7 182.000 10.764 66.667 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 182.000
25 FLOOR 1 NURSE HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 1 NURSE HALL 46.08 2.5 474.811 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 474.811
26 FLOOR 1 NURSE JANITOR_LIGHTS LTG_SCH_STORAGE FLOOR 1 NURSE JANITOR 5.02 0.1 48.600 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 48.600
27 FLOOR 1 NURSE STATION_LIGHTS LTG_SCH_NURSE FLOOR 1 NURSE STATION 24.25 3.9 261.000 10.764 66.667 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 261.000
28 FLOOR 1 NURSE TOILET_LIGHTS LTG_SCH_TOILET FLOOR 1 NURSE TOILET 5.02 0.3 48.600 9.688 180.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 48.600
29 FLOOR 1 OFFICE_LIGHTS LTG_SCH_FLOOR_1_OFFICE FLOOR 1 OFFICE 44.87 2.4 531.299 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 531.299
30 FLOOR 1 OPERATING ROOM 1_LIGHTS LTG_SCH_OPERATION FLOOR 1 OPERATING ROOM 1 42.74 9.2 1011.999 23.681 109.989 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1011.999
31 FLOOR 1 OPERATING ROOM 2_LIGHTS LTG_SCH_OPERATION FLOOR 1 OPERATING ROOM 2 44.59 9.6 1055.999 23.681 109.989 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1055.999
32 FLOOR 1 OPERATING ROOM 3_LIGHTS LTG_SCH_OPERATION FLOOR 1 OPERATING ROOM 3 44.22 9.5 1047.199 23.681 109.989 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1047.199
33 FLOOR 1 PACU_LIGHTS LTG_SCH_RECOVERY FLOOR 1 PACU 10.03 2.2 86.400 8.611 39.996 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 86.400
34 FLOOR 1 PRE-OP HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 1 PRE-OP HALL 49.05 2.6 505.444 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 505.444
35 FLOOR 1 PRE-OP ROOM 1_LIGHTS LTG_SCH_PATIENT FLOOR 1 PRE-OP ROOM 1 17.56 1.9 132.300 7.535 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 132.300
36 FLOOR 1 PRE-OP ROOM 2_LIGHTS LTG_SCH_PATIENT FLOOR 1 PRE-OP ROOM 2 31.40 3.4 236.600 7.535 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 236.600
37 FLOOR 1 PRE-OP TOILET_LIGHTS LTG_SCH_TOILET FLOOR 1 PRE-OP TOILET 5.02 0.3 48.600 9.688 180.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 48.600
38 FLOOR 1 PROCEDURE ROOM_LIGHTS LTG_SCH_PROCEDURE FLOOR 1 PROCEDURE ROOM 26.48 5.7 427.500 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 427.500
39 FLOOR 1 RECEPTION_LIGHTS LTG_SCH_RECEPTION FLOOR 1 RECEPTION 47.29 15.3 661.699 13.993 43.329 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 661.699
40 FLOOR 1 RECEPTION HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 1 RECEPTION HALL 11.89 0.6 122.532 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 122.532
41 FLOOR 1 RECOVERY ROOM_LIGHTS LTG_SCH_RECOVERY FLOOR 1 RECOVERY ROOM 50.17 10.8 432.000 8.611 39.996 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 432.000
42 FLOOR 1 SCHEDULING_LIGHTS LTG_SCH_OFFICE FLOOR 1 SCHEDULING 11.06 0.6 130.900 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 130.900
43 FLOOR 1 SCRUB_LIGHTS LTG_SCH_CORRIDOR FLOOR 1 SCRUB 7.80 0.4 80.412 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 80.412
44 FLOOR 1 SOIL_LIGHTS LTG_SCH_SOILED FLOOR 1 SOIL 11.71 2.5 189.000 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 189.000
45 FLOOR 1 SOIL HOLD_LIGHTS LTG_SCH_SOILED FLOOR 1 SOIL HOLD 5.20 1.1 84.000 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 84.000
46 FLOOR 1 SOIL WORK_LIGHTS LTG_SCH_SOILED FLOOR 1 SOIL WORK 16.72 3.6 270.000 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 270.000
47 FLOOR 1 STEP DOWN_LIGHTS LTG_SCH_RECOVERY FLOOR 1 STEP DOWN 27.87 6.0 240.000 8.611 39.996 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 240.000
48 FLOOR 1 STERILE HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 1 STERILE HALL 57.23 3.1 589.685 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 589.685
49 FLOOR 1 STERILE STORAGE_LIGHTS LTG_SCH_FLOOR_1_STERILE_STORAGE FLOOR 1 STERILE STORAGE 36.79 0.8 356.400 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 356.400
50 FLOOR 1 STORAGE_LIGHTS LTG_SCH_STORAGE FLOOR 1 STORAGE 85.47 1.8 827.999 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 827.999
51 FLOOR 1 SUB-STERILE_LIGHTS LTG_SCH_CORRIDOR FLOOR 1 SUB-STERILE 18.21 1.0 187.627 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 187.627
52 FLOOR 1 UTILITY HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 1 UTILITY HALL 23.78 1.3 245.064 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 245.064
53 FLOOR 1 UTILITY JANITOR_LIGHTS LTG_SCH_STORAGE FLOOR 1 UTILITY JANITOR 3.90 8.4E-002 37.800 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 37.800
54 FLOOR 1 UTILITY ROOM_LIGHTS LTG_SCH_STORAGE FLOOR 1 UTILITY ROOM 33.45 0.7 324.000 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 324.000
55 FLOOR 1 VESTIBULE_LIGHTS LTG_SCH_CORRIDOR FLOOR 1 VESTIBULE 6.69 0.4 68.924 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 68.924
56 FLOOR 2 CONFERENCE_LIGHTS LTG_SCH_CONFERENCE FLOOR 2 CONFERENCE 31.22 16.8 436.800 13.993 25.997 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 436.800
57 FLOOR 2 CONFERENCE TOILET_LIGHTS LTG_SCH_TOILET FLOOR 2 CONFERENCE TOILET 5.95 0.3 57.600 9.688 180.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 57.600
58 FLOOR 2 DICTATION_LIGHTS LTG_SCH_OFFICE FLOOR 2 DICTATION 6.50 0.4 77.000 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 77.000
59 FLOOR 2 EXAM 1_LIGHTS LTG_SCH_EXAM FLOOR 2 EXAM 1 33.45 7.2 539.999 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 539.999
60 FLOOR 2 EXAM 2_LIGHTS LTG_SCH_EXAM FLOOR 2 EXAM 2 50.17 10.8 809.999 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 809.999
61 FLOOR 2 EXAM 3_LIGHTS LTG_SCH_EXAM FLOOR 2 EXAM 3 66.89 14.4 1079.999 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1079.999
62 FLOOR 2 EXAM 4_LIGHTS LTG_SCH_EXAM FLOOR 2 EXAM 4 7.80 1.7 126.000 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 126.000
63 FLOOR 2 EXAM 5_LIGHTS LTG_SCH_EXAM FLOOR 2 EXAM 5 32.52 7.0 524.999 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 524.999
64 FLOOR 2 EXAM 6_LIGHTS LTG_SCH_EXAM FLOOR 2 EXAM 6 20.90 4.5 337.500 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 337.500
65 FLOOR 2 EXAM 7_LIGHTS LTG_SCH_EXAM FLOOR 2 EXAM 7 73.58 15.8 1187.999 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1187.999
66 FLOOR 2 EXAM 8_LIGHTS LTG_SCH_EXAM FLOOR 2 EXAM 8 25.08 5.4 405.000 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 405.000
67 FLOOR 2 EXAM 9_LIGHTS LTG_SCH_EXAM FLOOR 2 EXAM 9 36.79 7.9 593.999 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 593.999
68 FLOOR 2 EXAM HALL 1_LIGHTS LTG_SCH_CORRIDOR FLOOR 2 EXAM HALL 1 16.72 0.9 172.310 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.310
69 FLOOR 2 EXAM HALL 2_LIGHTS LTG_SCH_CORRIDOR FLOOR 2 EXAM HALL 2 16.72 0.9 172.310 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.310
70 FLOOR 2 EXAM HALL 3_LIGHTS LTG_SCH_CORRIDOR FLOOR 2 EXAM HALL 3 16.72 0.9 172.310 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.310
71 FLOOR 2 EXAM HALL 4_LIGHTS LTG_SCH_CORRIDOR FLOOR 2 EXAM HALL 4 18.39 1.0 189.542 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 189.542
72 FLOOR 2 EXAM HALL 5_LIGHTS LTG_SCH_CORRIDOR FLOOR 2 EXAM HALL 5 18.39 1.0 189.542 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 189.542
73 FLOOR 2 EXAM HALL 6_LIGHTS LTG_SCH_CORRIDOR FLOOR 2 EXAM HALL 6 18.39 1.0 189.542 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 189.542
74 FLOOR 2 JANITOR_LIGHTS LTG_SCH_STORAGE FLOOR 2 JANITOR 5.85 0.1 56.700 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 56.700
75 FLOOR 2 LOUNGE_LIGHTS LTG_SCH_LOUNGE FLOOR 2 LOUNGE 7.43 1.2 64.000 8.611 53.328 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 64.000
76 FLOOR 2 NURSE STATION 1_LIGHTS LTG_SCH_NURSE FLOOR 2 NURSE STATION 1 13.94 2.2 150.000 10.764 66.667 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 150.000
77 FLOOR 2 NURSE STATION 2_LIGHTS LTG_SCH_NURSE FLOOR 2 NURSE STATION 2 16.72 2.7 180.000 10.764 66.667 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 180.000
78 FLOOR 2 OFFICE_LIGHTS LTG_SCH_OFFICE FLOOR 2 OFFICE 52.03 2.8 615.999 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 615.999
79 FLOOR 2 OFFICE HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 2 OFFICE HALL 41.25 2.2 425.032 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 425.032
80 FLOOR 2 RECEPTION_LIGHTS LTG_SCH_RECEPTION FLOOR 2 RECEPTION 91.42 29.5 1279.199 13.993 43.329 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1279.199
81 FLOOR 2 RECEPTION HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 2 RECEPTION HALL 52.40 2.8 539.906 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 539.906
82 FLOOR 2 RECEPTION TOILET_LIGHTS LTG_SCH_TOILET FLOOR 2 RECEPTION TOILET 11.71 0.6 113.400 9.688 180.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 113.400
83 FLOOR 2 SCHEDULING 1_LIGHTS LTG_SCH_OFFICE FLOOR 2 SCHEDULING 1 30.10 1.6 356.400 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 356.400
84 FLOOR 2 SCHEDULING 2_LIGHTS LTG_SCH_OFFICE FLOOR 2 SCHEDULING 2 31.77 1.7 376.200 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 376.200
85 FLOOR 2 STORAGE 1_LIGHTS LTG_SCH_STORAGE FLOOR 2 STORAGE 1 5.20 0.1 50.400 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 50.400
86 FLOOR 2 STORAGE 2_LIGHTS LTG_SCH_STORAGE FLOOR 2 STORAGE 2 11.15 0.2 108.000 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.000
87 FLOOR 2 STORAGE 3_LIGHTS LTG_SCH_STORAGE FLOOR 2 STORAGE 3 13.38 0.3 129.600 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 129.600
88 FLOOR 2 UTILITY_LIGHTS LTG_SCH_STORAGE FLOOR 2 UTILITY 11.71 0.3 113.400 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 113.400
89 FLOOR 2 WORK_LIGHTS LTG_SCH_OFFICE FLOOR 2 WORK 157.01 8.5 1858.998 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1858.998
90 FLOOR 2 WORK HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 2 WORK HALL 77.48 4.2 798.372 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 798.372
91 FLOOR 2 WORK TOILET_LIGHTS LTG_SCH_TOILET FLOOR 2 WORK TOILET 5.02 0.3 48.600 9.688 180.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 48.600
92 FLOOR 2 X-RAY_LIGHTS LTG_SCH_RADIOLOGY FLOOR 2 X-RAY 83.61 18.0 1349.999 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1349.999
93 FLOOR 3 DRESSING ROOM_LIGHTS LTG_SCH_OFFICE FLOOR 3 DRESSING ROOM 3.90 0.2 46.200 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 46.200
94 FLOOR 3 ELEVATOR HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 3 ELEVATOR HALL 34.37 1.9 354.194 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.194
95 FLOOR 3 HUMID_LIGHTS LTG_SCH_OFFICE FLOOR 3 HUMID 10.03 0.5 118.800 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 118.800
96 FLOOR 3 JANITOR_LIGHTS LTG_SCH_STORAGE FLOOR 3 JANITOR 5.85 0.1 56.700 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 56.700
97 FLOOR 3 LOCKER_LIGHTS LTG_SCH_LOUNGE FLOOR 3 LOCKER 11.15 1.8 96.000 8.611 53.328 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 96.000
98 FLOOR 3 LOUNGE_LIGHTS LTG_SCH_LOUNGE FLOOR 3 LOUNGE 70.51 11.4 607.199 8.611 53.328 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 607.199
99 FLOOR 3 LOUNGE TOILET_LIGHTS LTG_SCH_TOILET FLOOR 3 LOUNGE TOILET 17.84 1.0 172.800 9.688 180.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.800
100 FLOOR 3 MECHANICAL_LIGHTS LTG_SCH_EXAM FLOOR 3 MECHANICAL 32.52 0.5 524.999 16.146 999.999 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 524.999
101 FLOOR 3 MECHANICAL HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 3 MECHANICAL HALL 27.87 1.5 287.184 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 287.184
102 FLOOR 3 OFFICE_LIGHTS LTG_SCH_OFFICE FLOOR 3 OFFICE 282.05 15.2 3339.597 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3339.597
103 FLOOR 3 OFFICE HALL_LIGHTS LTG_SCH_CORRIDOR FLOOR 3 OFFICE HALL 77.48 4.2 798.372 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 798.372
104 FLOOR 3 OFFICE TOILET_LIGHTS LTG_SCH_TOILET FLOOR 3 OFFICE TOILET 5.02 0.3 48.600 9.688 180.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 48.600
105 FLOOR 3 PHYSICAL THERAPY 1_LIGHTS LTG_SCH_PHY_THERAPY FLOOR 3 PHYSICAL THERAPY 1 120.77 26.0 1169.999 9.688 44.996 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1169.999
106 FLOOR 3 PHYSICAL THERAPY 2_LIGHTS LTG_SCH_PHY_THERAPY FLOOR 3 PHYSICAL THERAPY 2 55.00 11.8 532.799 9.688 44.996 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 532.799
107 FLOOR 3 PHYSICAL THERAPY TOILET_LIGHTS LTG_SCH_TOILET FLOOR 3 PHYSICAL THERAPY TOILET 7.80 0.4 75.600 9.688 180.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 75.600
108 FLOOR 3 STORAGE 1_LIGHTS LTG_SCH_STORAGE FLOOR 3 STORAGE 1 10.03 0.2 97.200 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 97.200
109 FLOOR 3 STORAGE 2_LIGHTS LTG_SCH_STORAGE FLOOR 3 STORAGE 2 7.80 0.2 75.600 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 75.600
110 FLOOR 3 TREATMENT_LIGHTS LTG_SCH_EXAM FLOOR 3 TREATMENT 44.22 9.5 713.999 16.146 74.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 713.999
111 FLOOR 3 UNDEVELOPED 1_LIGHTS LTG_SCH_STORAGE FLOOR 3 UNDEVELOPED 1 210.70 4.5 2041.198 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2041.198
112 FLOOR 3 UNDEVELOPED 2_LIGHTS LTG_SCH_STORAGE FLOOR 3 UNDEVELOPED 2 107.02 2.3 1036.799 9.688 450.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1036.799
113 FLOOR 3 UTILITY_LIGHTS LTG_SCH_UTILITY FLOOR 3 UTILITY 20.07 0.4 324.000 16.146 749.999 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 324.000
114 FLOOR 3 WORK_LIGHTS LTG_SCH_OFFICE FLOOR 3 WORK 53.33 2.9 631.399 11.840 219.978 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 631.399
115 NE STAIR_LIGHTS LTG_SCH_CORRIDOR NE STAIR 15.61 0.8 160.823 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 160.823
116 NW ELEVATOR_LIGHTS LTG_SCH_CORRIDOR NW ELEVATOR 13.01 0.2 134.019 10.304 638.187 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 134.019
117 NW STAIR_LIGHTS LTG_SCH_CORRIDOR NW STAIR 17.84 1.0 183.798 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 183.798
118 SW STAIR_LIGHTS LTG_SCH_CORRIDOR SW STAIR 8.92 0.5 91.899 10.304 191.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 91.899


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 ELEVATOR_LIFT_RUNNING ELEVATOR_RUNNING_SCH FLOOR 1 ELEVATOR PUMP ROOM 8.45 0.1 76724.000 9075.278 562080.586 0.000 0.100 0.900 0.000 ElevatorLift 0.000 3889.140
2 ELEVATOR_LIFT_STANDBY ELEVATOR_STANDBY_SCH FLOOR 1 ELEVATOR PUMP ROOM 8.45 0.1 3200.000 378.511 23443.223 0.000 0.100 0.900 0.000 ElevatorLift 2586.816 3200.000
3 ELEVATORS_LIGHTS_FAN ELEV_LIGHT_FAN_SCH_24_7 FLOOR 1 ELEVATOR PUMP ROOM 8.45 0.1 486.000 57.486 3560.440 0.000 0.100 0.900 0.000 ElevatorLightsFan 486.000 486.000
4 FLOOR 1 ANESTHESIA_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 ANESTHESIA 10.03 2.2 216.022 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 64.188 216.022
5 FLOOR 1 BIO HAZ_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 BIO HAZ 5.20 0.1 5.619 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 1.670 5.619
6 FLOOR 1 CAFE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 CAFE 39.02 42.0 419.847 10.760 9.995 0.000 0.500 0.000 0.500 MiscPlug 124.753 419.847
7 FLOOR 1 CLEAN_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 CLEAN 11.71 2.5 252.026 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 74.886 252.026
8 FLOOR 1 CLEAN WORK_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 CLEAN WORK 15.33 3.3 330.033 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 98.066 330.033
9 FLOOR 1 DICTATION_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 DICTATION 11.71 0.6 138.597 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 41.182 138.597
10 FLOOR 1 DRESSING ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 DRESSING ROOM 4.18 0.2 49.499 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 14.708 49.499
11 FLOOR 1 ELECTRICAL ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 ELECTRICAL ROOM 9.10 0.1 490.004 53.820 3333.361 0.000 0.500 0.000 0.500 MiscPlug 145.599 490.004
12 FLOOR 1 HUMID_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 HUMID 5.02 0.3 59.399 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 17.650 59.399
13 FLOOR 1 IT HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 IT HALL 13.01 0.7 56.058 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 16.657 56.058
14 FLOOR 1 IT ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 IT ROOM 10.41 0.6 123.197 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 36.606 123.197
15 FLOOR 1 LOBBY_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 LOBBY 57.79 6.2 684.183 11.840 109.986 0.000 0.500 0.000 0.500 MiscPlug 203.297 684.183
16 FLOOR 1 LOBBY HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 LOBBY HALL 22.30 1.2 96.099 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 28.555 96.099
17 FLOOR 1 LOBBY TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 LOBBY TOILET 5.02 0.3 21.622 4.310 80.083 0.000 0.500 0.000 0.500 MiscPlug 6.425 21.622
18 FLOOR 1 LOCKER ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 LOCKER ROOM 61.32 9.9 1979.894 32.290 199.970 0.000 0.500 0.000 0.500 MiscPlug 588.302 1979.894
19 FLOOR 1 LOCKER ROOM HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 LOCKER ROOM HALL 46.08 2.5 198.604 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 59.013 198.604
20 FLOOR 1 LOUNGE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 LOUNGE 33.45 5.4 1079.942 32.290 199.970 0.000 0.500 0.000 0.500 MiscPlug 320.892 1079.942
21 FLOOR 1 MED GAS_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 MED GAS 5.20 0.1 5.619 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 1.670 5.619
22 FLOOR 1 MRI CONTROL ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 MRI CONTROL ROOM 15.61 3.4 1680.014 107.640 499.956 0.000 0.500 0.000 0.500 MiscPlug 499.196 1680.014
23 FLOOR 1 MRI HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 MRI HALL 13.66 0.7 58.861 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 17.490 58.861
24 FLOOR 1 MRI ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 MRI ROOM 40.88 8.8 4400.037 107.640 499.956 0.000 0.500 0.000 0.500 MiscPlug 1307.419 4400.037
25 FLOOR 1 MRI TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 MRI TOILET 5.02 0.3 21.622 4.310 80.083 0.000 0.500 0.000 0.500 MiscPlug 6.425 21.622
26 FLOOR 1 NOURISHMENT_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 NOURISHMENT 16.91 2.7 364.037 21.530 133.347 0.000 0.500 0.000 0.500 MiscPlug 108.169 364.037
27 FLOOR 1 NURSE HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 NURSE HALL 46.08 2.5 198.604 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 59.013 198.604
28 FLOOR 1 NURSE JANITOR_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 NURSE JANITOR 5.02 0.1 5.418 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 1.610 5.418
29 FLOOR 1 NURSE STATION_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 NURSE STATION 24.25 3.9 522.053 21.530 133.347 0.000 0.500 0.000 0.500 MiscPlug 155.122 522.053
30 FLOOR 1 NURSE TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 NURSE TOILET 5.02 0.3 21.622 4.310 80.083 0.000 0.500 0.000 0.500 MiscPlug 6.425 21.622
31 FLOOR 1 OFFICE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 OFFICE 44.87 2.4 531.287 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 157.865 531.287
32 FLOOR 1 OPERATING ROOM 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 OPERATING ROOM 1 42.74 9.2 1840.186 43.060 200.001 0.000 0.500 0.000 0.500 MiscPlug 546.790 1840.186
33 FLOOR 1 OPERATING ROOM 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 OPERATING ROOM 2 44.59 9.6 1920.194 43.060 200.001 0.000 0.500 0.000 0.500 MiscPlug 570.563 1920.194
34 FLOOR 1 OPERATING ROOM 3_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 OPERATING ROOM 3 44.22 9.5 1904.193 43.060 200.001 0.000 0.500 0.000 0.500 MiscPlug 565.808 1904.193
35 FLOOR 1 PACU_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 PACU 10.03 2.2 323.983 32.290 149.977 0.000 0.500 0.000 0.500 MiscPlug 96.268 323.983
36 FLOOR 1 PRE-OP HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 PRE-OP HALL 49.05 2.6 211.418 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 62.820 211.418
37 FLOOR 1 PRE-OP ROOM 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 PRE-OP ROOM 1 17.56 1.9 378.038 21.530 200.001 0.000 0.500 0.000 0.500 MiscPlug 112.330 378.038
38 FLOOR 1 PRE-OP ROOM 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 PRE-OP ROOM 2 31.40 3.4 676.068 21.530 200.001 0.000 0.500 0.000 0.500 MiscPlug 200.886 676.068
39 FLOOR 1 PRE-OP TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 PRE-OP TOILET 5.02 0.3 21.622 4.310 80.083 0.000 0.500 0.000 0.500 MiscPlug 6.425 21.622
40 FLOOR 1 PROCEDURE ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 PROCEDURE ROOM 26.48 5.7 854.954 32.290 149.977 0.000 0.500 0.000 0.500 MiscPlug 254.040 854.954
41 FLOOR 1 RECEPTION_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 RECEPTION 47.29 15.3 559.886 11.840 36.662 0.000 0.500 0.000 0.500 MiscPlug 166.363 559.886
42 FLOOR 1 RECEPTION HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 RECEPTION HALL 11.89 0.6 51.253 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 15.229 51.253
43 FLOOR 1 RECOVERY ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 RECOVERY ROOM 50.17 10.8 1619.913 32.290 149.977 0.000 0.500 0.000 0.500 MiscPlug 481.338 1619.913
44 FLOOR 1 SCHEDULING_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 SCHEDULING 11.06 0.6 130.897 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 38.894 130.897
45 FLOOR 1 SCRUB_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 SCRUB 7.80 0.4 33.635 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 9.994 33.635
46 FLOOR 1 SOIL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 SOIL 11.71 2.5 252.026 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 74.886 252.026
47 FLOOR 1 SOIL HOLD_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 SOIL HOLD 5.20 1.1 112.011 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 33.283 112.011
48 FLOOR 1 SOIL WORK_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 SOIL WORK 16.72 3.6 360.036 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 106.981 360.036
49 FLOOR 1 STEP DOWN_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 STEP DOWN 27.87 6.0 899.952 32.290 149.977 0.000 0.500 0.000 0.500 MiscPlug 267.410 899.952
50 FLOOR 1 STERILE HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 STERILE HALL 57.23 3.1 246.654 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 73.290 246.654
51 FLOOR 1 STERILE STORAGE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 STERILE STORAGE 36.79 0.8 39.733 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 11.806 39.733
52 FLOOR 1 STORAGE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 STORAGE 85.47 1.8 92.309 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 27.428 92.309
53 FLOOR 1 SUB-STERILE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 SUB-STERILE 18.21 1.0 78.481 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 23.320 78.481
54 FLOOR 1 UTILITY HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 UTILITY HALL 23.78 1.3 102.506 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 30.458 102.506
55 FLOOR 1 UTILITY JANITOR_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 UTILITY JANITOR 3.90 8.4E-002 4.214 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 1.252 4.214
56 FLOOR 1 UTILITY ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 UTILITY ROOM 33.45 0.7 36.121 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 10.733 36.121
57 FLOOR 1 VESTIBULE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 VESTIBULE 6.69 0.4 28.830 4.310 80.083 0.000 0.500 0.000 0.500 MiscPlug 8.566 28.830
58 FLOOR 2 CONFERENCE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 CONFERENCE 31.22 16.8 335.878 10.760 19.991 0.000 0.500 0.000 0.500 MiscPlug 99.802 335.878
59 FLOOR 2 CONFERENCE TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 CONFERENCE TOILET 5.95 0.3 25.626 4.310 80.083 0.000 0.500 0.000 0.500 MiscPlug 7.615 25.626
60 FLOOR 2 DICTATION_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 DICTATION 6.50 0.4 76.998 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 22.879 76.998
61 FLOOR 2 EXAM 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 1 33.45 7.2 395.990 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 117.664 395.990
62 FLOOR 2 EXAM 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 2 50.17 10.8 593.985 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 176.496 593.985
63 FLOOR 2 EXAM 3_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 3 66.89 14.4 791.980 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 235.327 791.980
64 FLOOR 2 EXAM 4_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 4 7.80 1.7 92.398 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 27.455 92.398
65 FLOOR 2 EXAM 5_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 5 32.52 7.0 384.990 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 114.395 384.990
66 FLOOR 2 EXAM 6_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 6 20.90 4.5 247.494 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 73.540 247.494
67 FLOOR 2 EXAM 7_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 7 73.58 15.8 871.178 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 258.860 871.178
68 FLOOR 2 EXAM 8_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 8 25.08 5.4 296.992 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 88.248 296.992
69 FLOOR 2 EXAM 9_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 9 36.79 7.9 435.589 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 129.430 435.589
70 FLOOR 2 EXAM HALL 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM HALL 1 16.72 0.9 72.074 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 21.416 72.074
71 FLOOR 2 EXAM HALL 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM HALL 2 16.72 0.9 72.074 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 21.416 72.074
72 FLOOR 2 EXAM HALL 3_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM HALL 3 16.72 0.9 72.074 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 21.416 72.074
73 FLOOR 2 EXAM HALL 4_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM HALL 4 18.39 1.0 79.282 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 23.558 79.282
74 FLOOR 2 EXAM HALL 5_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM HALL 5 18.39 1.0 79.282 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 23.558 79.282
75 FLOOR 2 EXAM HALL 6_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM HALL 6 18.39 1.0 79.282 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 23.558 79.282
76 FLOOR 2 JANITOR_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 JANITOR 5.85 0.1 6.321 1.080 50.167 0.000 0.500 0.000 0.500 MiscPlug 1.878 6.321
77 FLOOR 2 LOUNGE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 LOUNGE 7.43 1.2 239.987 32.290 199.970 0.000 0.500 0.000 0.500 MiscPlug 71.309 239.987
78 FLOOR 2 NURSE STATION 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 NURSE STATION 1 13.94 2.2 300.030 21.530 133.347 0.000 0.500 0.000 0.500 MiscPlug 89.150 300.030
79 FLOOR 2 NURSE STATION 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 NURSE STATION 2 16.72 2.7 360.036 21.530 133.347 0.000 0.500 0.000 0.500 MiscPlug 106.981 360.036
80 FLOOR 2 OFFICE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 OFFICE 52.03 2.8 615.984 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 183.032 615.984
81 FLOOR 2 OFFICE HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 OFFICE HALL 41.25 2.2 177.783 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 52.826 177.783
82 FLOOR 2 RECEPTION_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 RECEPTION 91.42 29.5 1082.372 11.840 36.662 0.000 0.500 0.000 0.500 MiscPlug 321.614 1082.372
83 FLOOR 2 RECEPTION HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 RECEPTION HALL 52.40 2.8 225.832 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 67.103 225.832
84 FLOOR 2 RECEPTION TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 RECEPTION TOILET 11.71 0.6 50.452 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 14.991 50.452
85 FLOOR 2 SCHEDULING 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 SCHEDULING 1 30.10 1.6 356.391 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 105.897 356.391
86 FLOOR 2 SCHEDULING 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 SCHEDULING 2 31.77 1.7 376.190 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 111.781 376.190
87 FLOOR 2 STORAGE 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 STORAGE 1 5.20 0.1 5.619 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 1.670 5.619
88 FLOOR 2 STORAGE 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 STORAGE 2 11.15 0.2 12.040 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 3.578 12.040
89 FLOOR 2 STORAGE 3_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 STORAGE 3 13.38 0.3 14.448 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 4.293 14.448
90 FLOOR 2 UTILITY_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 UTILITY 11.71 0.3 12.642 1.080 50.167 0.000 0.500 0.000 0.500 MiscPlug 3.756 12.642
91 FLOOR 2 WORK_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 WORK 157.01 8.5 1535.561 9.780 181.705 0.000 0.500 0.000 0.500 MiscPlug 456.274 1535.561
92 FLOOR 2 WORK HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 WORK HALL 77.48 4.2 333.944 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 99.227 333.944
93 FLOOR 2 WORK TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 WORK TOILET 5.02 0.3 21.622 4.310 80.083 0.000 0.500 0.000 0.500 MiscPlug 6.425 21.622
94 FLOOR 2 X-RAY_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 X-RAY 83.61 18.0 9000.075 107.640 499.956 0.000 0.500 0.000 0.500 MiscPlug 2674.266 9000.075
95 FLOOR 3 DRESSING ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 DRESSING ROOM 3.90 0.2 46.199 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 13.727 46.199
96 FLOOR 3 ELEVATOR HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 ELEVATOR HALL 34.37 1.9 148.153 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 44.022 148.153
97 FLOOR 3 HUMID_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 HUMID 10.03 0.5 118.797 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 35.299 118.797
98 FLOOR 3 JANITOR_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 JANITOR 5.85 0.1 6.321 1.080 50.167 0.000 0.500 0.000 0.500 MiscPlug 1.878 6.321
99 FLOOR 3 LOCKER_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 LOCKER 11.15 1.8 359.981 32.290 199.970 0.000 0.500 0.000 0.500 MiscPlug 106.964 359.981
100 FLOOR 3 LOUNGE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 LOUNGE 70.51 11.4 2276.878 32.290 199.970 0.000 0.500 0.000 0.500 MiscPlug 676.547 2276.878
101 FLOOR 3 LOUNGE TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 LOUNGE TOILET 17.84 1.0 76.879 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 22.844 76.879
102 FLOOR 3 MECHANICAL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 MECHANICAL 32.52 0.5 1750.015 53.820 3333.361 0.000 0.500 0.000 0.500 MiscPlug 519.996 1750.015
103 FLOOR 3 MECHANICAL HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 MECHANICAL HALL 27.87 1.5 120.124 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 35.693 120.124
104 FLOOR 3 OFFICE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 OFFICE 282.05 15.2 3339.515 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 992.297 3339.515
105 FLOOR 3 OFFICE HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 OFFICE HALL 77.48 4.2 333.944 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 99.227 333.944
106 FLOOR 3 OFFICE TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 OFFICE TOILET 5.02 0.3 21.622 4.310 80.083 0.000 0.500 0.000 0.500 MiscPlug 6.425 21.622
107 FLOOR 3 PHYSICAL THERAPY 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 PHYSICAL THERAPY 1 120.77 26.0 1950.499 16.150 75.012 0.000 0.500 0.000 0.500 MiscPlug 579.568 1950.499
108 FLOOR 3 PHYSICAL THERAPY 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 PHYSICAL THERAPY 2 55.00 11.8 888.227 16.150 75.012 0.000 0.500 0.000 0.500 MiscPlug 263.926 888.227
109 FLOOR 3 PHYSICAL THERAPY TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 PHYSICAL THERAPY TOILET 7.80 0.4 33.635 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 9.994 33.635
110 FLOOR 3 STORAGE 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 STORAGE 1 10.03 0.2 10.836 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 3.220 10.836
111 FLOOR 3 STORAGE 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 STORAGE 2 7.80 0.2 8.428 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 2.504 8.428
112 FLOOR 3 TREATMENT_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 TREATMENT 44.22 9.5 523.587 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 155.578 523.587
113 FLOOR 3 UNDEVELOPED 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 UNDEVELOPED 1 210.70 4.5 2494.737 11.840 549.986 0.000 0.500 0.000 0.500 MiscPlug 741.281 2494.737
114 FLOOR 3 UNDEVELOPED 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 UNDEVELOPED 2 107.02 2.3 1267.168 11.840 549.986 0.000 0.500 0.000 0.500 MiscPlug 376.524 1267.168
115 FLOOR 3 UTILITY_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 UTILITY 20.07 0.4 21.672 1.080 50.168 0.000 0.500 0.000 0.500 MiscPlug 6.440 21.672
116 FLOOR 3 WORK_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 WORK 53.33 2.9 631.384 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 187.608 631.384
117 NE STAIR_PLUGMISC_EQUIP BLDG_EQUIP_SCH NE STAIR 15.61 0.8 67.269 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 19.988 67.269
118 NW ELEVATOR_PLUGMISC_EQUIP BLDG_EQUIP_SCH NW ELEVATOR 13.01 0.2 56.058 4.310 266.941 0.000 0.500 0.000 0.500 MiscPlug 16.657 56.058
119 NW STAIR_PLUGMISC_EQUIP BLDG_EQUIP_SCH NW STAIR 17.84 1.0 76.879 4.310 80.082 0.000 0.500 0.000 0.500 MiscPlug 22.844 76.879
120 SW STAIR_PLUGMISC_EQUIP BLDG_EQUIP_SCH SW STAIR 8.92 0.5 38.440 4.310 80.083 0.000 0.500 0.000 0.500 MiscPlug 11.422 38.440


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 FLOOR 1 OPERATING ROOM 1_GASMISC_EQUIP BLDG_EQUIP_SCH_BASE FLOOR 1 OPERATING ROOM 1 42.74 9.2 3217.976 75.300 349.746 0.000 0.000 0.500 0.500 MiscPlug 965.393 3217.976
2 FLOOR 1 OPERATING ROOM 2_GASMISC_EQUIP BLDG_EQUIP_SCH_BASE FLOOR 1 OPERATING ROOM 2 44.59 9.6 3357.888 75.300 349.746 0.000 0.000 0.500 0.500 MiscPlug 1007.366 3357.888
3 FLOOR 1 OPERATING ROOM 3_GASMISC_EQUIP BLDG_EQUIP_SCH_BASE FLOOR 1 OPERATING ROOM 3 44.22 9.5 3329.905 75.300 349.746 0.000 0.000 0.500 0.500 MiscPlug 998.972 3329.905


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 9.815 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 200.0 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 INT_SLAB_FLOOR 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_CEILING 14 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
7 NONRES_ROOF 18 3 3 0.167 0.3762 0.900 0.900 0.700 0.700 Rough
8 NONRES_EXT_WALL_GRD 21 4 7 0.167 0.7871 0.900 0.900 0.700 0.700 Smooth
9 NONRES_EXT_WALL_MID 22 4 7 0.167 0.7871 0.900 0.900 0.700 0.700 Smooth
10 NONRES_EXT_WALL_TOP 23 4 7 0.167 0.7871 0.900 0.900 0.700 0.700 Smooth
11 FLOOR1ANESTHESIASLAB_FFACTOR 40 2 7 0.167 0.3650 0.000 0.900 0.000 0.700 MediumRough
12 FLOOR1BIOHAZSLAB_FFACTOR 41 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
13 FLOOR1CAFESLAB_FFACTOR 42 2 7 0.167 0.2036 0.000 0.900 0.000 0.700 MediumRough
14 FLOOR1CLEANSLAB_FFACTOR 43 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
15 FLOOR1CLEANWORKSLAB_FFACTOR 44 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
16 FLOOR1DICTATIONSLAB_FFACTOR 45 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
17 FLOOR1DRESSINGROOMSLAB_FFACTOR 46 2 7 0.167 0.9514 0.000 0.900 0.000 0.700 MediumRough
18 FLOOR1ELECTRICALROOMSLAB_FFACTOR 47 2 7 0.167 0.3104 0.000 0.900 0.000 0.700 MediumRough
19 FLOOR1ELEVATORPUMPROOMSLAB_FFACTOR 48 2 7 0.167 1.061 0.000 0.900 0.000 0.700 MediumRough
20 FLOOR1HUMIDSLAB_FFACTOR 49 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
21 FLOOR1ITHALLSLAB_FFACTOR 50 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
22 FLOOR1ITROOMSLAB_FFACTOR 51 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
23 FLOOR1LOBBYSLAB_FFACTOR 52 2 7 0.167 0.1500 0.000 0.900 0.000 0.700 MediumRough
24 FLOOR1LOBBYHALLSLAB_FFACTOR 53 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
25 FLOOR1LOBBYTOILETSLAB_FFACTOR 54 2 7 0.167 0.4961 0.000 0.900 0.000 0.700 MediumRough
26 FLOOR1LOCKERROOMSLAB_FFACTOR 55 2 7 0.167 0.1412 0.000 0.900 0.000 0.700 MediumRough
27 FLOOR1LOCKERROOMHALLSLAB_FFACTOR 56 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
28 FLOOR1LOUNGESLAB_FFACTOR 57 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
29 FLOOR1MEDGASSLAB_FFACTOR 58 2 7 0.167 1.341 0.000 0.900 0.000 0.700 MediumRough
30 FLOOR1MRICONTROLROOMSLAB_FFACTOR 59 2 7 0.167 0.1258 0.000 0.900 0.000 0.700 MediumRough
31 FLOOR1MRIHALLSLAB_FFACTOR 60 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
32 FLOOR1MRIROOMSLAB_FFACTOR 61 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
33 FLOOR1MRITOILETSLAB_FFACTOR 62 2 7 0.167 0.4961 0.000 0.900 0.000 0.700 MediumRough
34 FLOOR1NOURISHMENTSLAB_FFACTOR 63 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
35 FLOOR1NURSEHALLSLAB_FFACTOR 64 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
36 FLOOR1NURSEJANITORSLAB_FFACTOR 65 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
37 FLOOR1NURSESTATIONSLAB_FFACTOR 66 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
38 FLOOR1NURSETOILETSLAB_FFACTOR 67 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
39 FLOOR1OFFICESLAB_FFACTOR 68 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
40 FLOOR1OPERATINGROOM1SLAB_FFACTOR 69 2 7 0.167 0.4123 0.000 0.900 0.000 0.700 MediumRough
41 FLOOR1OPERATINGROOM2SLAB_FFACTOR 70 2 7 0.167 0.2142 0.000 0.900 0.000 0.700 MediumRough
42 FLOOR1OPERATINGROOM3SLAB_FFACTOR 71 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
43 FLOOR1PACUSLAB_FFACTOR 72 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
44 FLOOR1PRE-OPHALLSLAB_FFACTOR 73 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
45 FLOOR1PRE-OPROOM1SLAB_FFACTOR 74 2 7 0.167 0.8895E-01 0.000 0.900 0.000 0.700 MediumRough
46 FLOOR1PRE-OPROOM2SLAB_FFACTOR 75 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
47 FLOOR1PRE-OPTOILETSLAB_FFACTOR 76 2 7 0.167 0.4961 0.000 0.900 0.000 0.700 MediumRough
48 FLOOR1PROCEDUREROOMSLAB_FFACTOR 77 2 7 0.167 0.2888 0.000 0.900 0.000 0.700 MediumRough
49 FLOOR1RECEPTIONSLAB_FFACTOR 78 2 7 0.167 0.1077 0.000 0.900 0.000 0.700 MediumRough
50 FLOOR1RECEPTIONHALLSLAB_FFACTOR 79 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
51 FLOOR1RECOVERYROOMSLAB_FFACTOR 80 2 7 0.167 0.3650 0.000 0.900 0.000 0.700 MediumRough
52 FLOOR1SCHEDULINGSLAB_FFACTOR 81 2 7 0.167 0.2534 0.000 0.900 0.000 0.700 MediumRough
53 FLOOR1SCRUBSLAB_FFACTOR 82 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
54 FLOOR1SOILSLAB_FFACTOR 83 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
55 FLOOR1SOILHOLDSLAB_FFACTOR 84 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
56 FLOOR1SOILWORKSLAB_FFACTOR 85 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
57 FLOOR1STEPDOWNSLAB_FFACTOR 86 2 7 0.167 0.5553 0.000 0.900 0.000 0.700 MediumRough
58 FLOOR1STERILEHALLSLAB_FFACTOR 87 2 7 0.167 0.5429E-01 0.000 0.900 0.000 0.700 MediumRough
59 FLOOR1NURSESTORAGESLAB_FFACTOR 88 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
60 FLOOR1STORAGESLAB_FFACTOR 89 2 7 0.167 0.2970 0.000 0.900 0.000 0.700 MediumRough
61 FLOOR1SUB-STERILESLAB_FFACTOR 90 2 7 0.167 0.3104 0.000 0.900 0.000 0.700 MediumRough
62 FLOOR1UTILITYHALLSLAB_FFACTOR 91 2 7 0.167 0.2700 0.000 0.900 0.000 0.700 MediumRough
63 FLOOR1UTILITYJANITORSLAB_FFACTOR 92 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
64 FLOOR1UTILITYROOMSLAB_FFACTOR 93 2 7 0.167 0.2142 0.000 0.900 0.000 0.700 MediumRough
65 FLOOR1VESTIBULESLAB_FFACTOR 94 2 7 0.167 0.4961 0.000 0.900 0.000 0.700 MediumRough
66 NESTAIRSLAB_FFACTOR 95 2 7 0.167 0.9972 0.000 0.900 0.000 0.700 MediumRough
67 NWELEVATORSLAB_FFACTOR 96 2 7 0.167 0.9126 0.000 0.900 0.000 0.700 MediumRough
68 NWSTAIRSLAB_FFACTOR 97 2 7 0.167 0.9972 0.000 0.900 0.000 0.700 MediumRough
69 SWSTAIRSLAB_FFACTOR 98 2 7 0.167 0.9972 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.1019
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5000E-02
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
9 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
10 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
11 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 2.599
12 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
13 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.037
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
18 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.037
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 1.037
24 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
25 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.663
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 176.9
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 4.833
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 176.9
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 176.9
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
35 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 176.9
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_7 0.0000 0.000 0.000 0.000 0.9741
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_8 0.0000 0.000 0.000 0.000 3.145
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_9 0.0000 0.000 0.000 0.000 0.8656
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
43 ~FC_Insulation_10 0.0000 0.000 0.000 0.000 176.9
44 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
45 ~FC_Insulation_11 0.0000 0.000 0.000 0.000 176.9
46 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
47 ~FC_Insulation_12 0.0000 0.000 0.000 0.000 176.9
48 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
49 ~FC_Insulation_13 0.0000 0.000 0.000 0.000 6.588
50 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
51 ~FC_Insulation_14 0.0000 0.000 0.000 0.000 176.9
52 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
53 ~FC_Insulation_15 0.0000 0.000 0.000 0.000 1.939
54 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
55 ~FC_Insulation_16 0.0000 0.000 0.000 0.000 7.004
56 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
57 ~FC_Insulation_17 0.0000 0.000 0.000 0.000 176.9
58 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
59 ~FC_Insulation_18 0.0000 0.000 0.000 0.000 176.9
60 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
61 ~FC_Insulation_19 0.0000 0.000 0.000 0.000 0.6686
62 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
63 ~FC_Insulation_20 0.0000 0.000 0.000 0.000 7.873
64 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
65 ~FC_Insulation_21 0.0000 0.000 0.000 0.000 176.9
66 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
67 ~FC_Insulation_22 0.0000 0.000 0.000 0.000 176.9
68 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
69 ~FC_Insulation_23 0.0000 0.000 0.000 0.000 1.939
70 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
71 ~FC_Insulation_24 0.0000 0.000 0.000 0.000 176.9
72 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
73 ~FC_Insulation_25 0.0000 0.000 0.000 0.000 176.9
74 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
75 ~FC_Insulation_26 0.0000 0.000 0.000 0.000 176.9
76 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
77 ~FC_Insulation_27 0.0000 0.000 0.000 0.000 176.9
78 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
79 ~FC_Insulation_28 0.0000 0.000 0.000 0.000 176.9
80 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
81 ~FC_Insulation_29 0.0000 0.000 0.000 0.000 176.9
82 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
83 ~FC_Insulation_30 0.0000 0.000 0.000 0.000 2.348
84 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
85 ~FC_Insulation_31 0.0000 0.000 0.000 0.000 4.592
86 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
87 ~FC_Insulation_32 0.0000 0.000 0.000 0.000 176.9
88 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
89 ~FC_Insulation_33 0.0000 0.000 0.000 0.000 176.9
90 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
91 ~FC_Insulation_34 0.0000 0.000 0.000 0.000 176.9
92 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
93 ~FC_Insulation_35 0.0000 0.000 0.000 0.000 11.17
94 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
95 ~FC_Insulation_36 0.0000 0.000 0.000 0.000 176.9
96 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
97 ~FC_Insulation_37 0.0000 0.000 0.000 0.000 1.939
98 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
99 ~FC_Insulation_38 0.0000 0.000 0.000 0.000 3.386
100 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
101 ~FC_Insulation_39 0.0000 0.000 0.000 0.000 9.212
102 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
103 ~FC_Insulation_40 0.0000 0.000 0.000 0.000 176.9
104 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
105 ~FC_Insulation_41 0.0000 0.000 0.000 0.000 2.663
106 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
107 ~FC_Insulation_42 0.0000 0.000 0.000 0.000 3.869
108 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
109 ~FC_Insulation_43 0.0000 0.000 0.000 0.000 176.9
110 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
111 ~FC_Insulation_44 0.0000 0.000 0.000 0.000 176.9
112 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
113 ~FC_Insulation_45 0.0000 0.000 0.000 0.000 176.9
114 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
115 ~FC_Insulation_46 0.0000 0.000 0.000 0.000 176.9
116 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
117 ~FC_Insulation_47 0.0000 0.000 0.000 0.000 1.724
118 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
119 ~FC_Insulation_48 0.0000 0.000 0.000 0.000 18.34
120 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
121 ~FC_Insulation_49 0.0000 0.000 0.000 0.000 176.9
122 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
123 ~FC_Insulation_50 0.0000 0.000 0.000 0.000 3.291
124 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
125 ~FC_Insulation_51 0.0000 0.000 0.000 0.000 3.145
126 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
127 ~FC_Insulation_52 0.0000 0.000 0.000 0.000 3.627
128 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
129 ~FC_Insulation_53 0.0000 0.000 0.000 0.000 176.9
130 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
131 ~FC_Insulation_54 0.0000 0.000 0.000 0.000 4.592
132 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
133 ~FC_Insulation_55 0.0000 0.000 0.000 0.000 1.939
134 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
135 ~FC_Insulation_56 0.0000 0.000 0.000 0.000 0.9259
136 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
137 ~FC_Insulation_57 0.0000 0.000 0.000 0.000 1.019
138 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
139 ~FC_Insulation_58 0.0000 0.000 0.000 0.000 0.9259
140 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
141 ~FC_Insulation_59 0.0000 0.000 0.000 0.000 0.9259
142 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 9.8148919 9.8148919 9.8148919  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 200.00000 200.00000 200.00000  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
21 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
22 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
23 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
24 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
25 2 51.553741 0.22121684 1.2284947 -0.25833933
26 1 -128.86110 0.21944682 -5.1479470 1.1228340
27 0 81.526494 0.16043334E-01 4.4519351  
28 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
29 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
30 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
31 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
32 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
33 2 1.2284947 0.22121684 51.553741 -0.25833933
34 1 -5.1479470 0.21944682 -128.86110 1.1228340
35 0 4.4519351 0.16043334E-01 81.526494  
36 3 -0.61039648E-06 0.16815647E-08 -0.37447326E-05 0.10149002E-16
37 2 0.76989337 0.22941655E-02 1.0458372 -0.71793422E-06
38 1 -21.843031 0.15409339 -6.3407615 0.20050303
39 0 21.373924 0.14439780 5.5957134  
40 7 -0.29735092E-12 0.24575595E-14 -0.94456721E-13 0.15324278E-15
41 6 0.28546880E-07 0.22114619E-09 0.65405332E-08 -0.13451374E-12
42 5 -0.18947583E-03 0.18937623E-05 -0.97466953E-04 0.64660656E-08
43 4 0.29140875 0.92215111E-03 0.99417931E-01 -0.33466744E-04
44 3 -7.2517161 0.28579858E-01 -2.3345767 0.28937395E-01
45 2 40.822959 0.10163225 15.247323 -0.33280368
46 1 -80.508872 0.45869584E-01 -29.125752 1.0778326
47 0 46.824339 0.92288667E-03 16.291614  
48 7 -0.29735092E-12 0.24575595E-14 -0.94456721E-13 0.15324278E-15
49 6 0.28546880E-07 0.22114619E-09 0.65405332E-08 -0.13451374E-12
50 5 -0.18947583E-03 0.18937623E-05 -0.97466953E-04 0.64660656E-08
51 4 0.29140875 0.92215111E-03 0.99417931E-01 -0.33466744E-04
52 3 -7.2517161 0.28579858E-01 -2.3345767 0.28937395E-01
53 2 40.822959 0.10163225 15.247323 -0.33280368
54 1 -80.508872 0.45869584E-01 -29.125752 1.0778326
55 0 46.824339 0.92288667E-03 16.291614  
56 7 -0.29735092E-12 0.24575595E-14 -0.94456721E-13 0.15324278E-15
57 6 0.28546880E-07 0.22114619E-09 0.65405332E-08 -0.13451374E-12
58 5 -0.18947583E-03 0.18937623E-05 -0.97466953E-04 0.64660656E-08
59 4 0.29140875 0.92215111E-03 0.99417931E-01 -0.33466744E-04
60 3 -7.2517161 0.28579858E-01 -2.3345767 0.28937395E-01
61 2 40.822959 0.10163225 15.247323 -0.33280368
62 1 -80.508872 0.45869584E-01 -29.125752 1.0778326
63 0 46.824339 0.92288667E-03 16.291614  
64 7 -0.11367252E-08 -0.11237507E-15 0.64990219E-14 -0.76141420E-16
65 6 0.10208875E-04 0.70392633E-08 0.31767506E-02 -0.26649246E-04
66 5 -0.73996474E-03 0.41768817E-05 -0.22297880 0.19495677E-02
67 4 0.17054262E-01 0.19023662E-03 4.8171224 -0.45145562E-01
68 3 -0.14984895 0.15139241E-02 -37.951226 0.39787794
69 2 0.53218631 0.25196058E-02 116.34733 -1.4161119
70 1 -0.76818791 0.76863149E-03 -143.82688 2.0477179
71 0 0.37454105 0.18419454E-04 60.838472  
72 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
73 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
74 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
75 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
76 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
77 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
78 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
79 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
80 0 0.84795330E-02 0.69040512E-07 60.838472  
81 7 -0.20718356E-08 -0.64740328E-15 0.80410021E-14 -0.11788455E-15
82 6 0.57244538E-05 0.38994522E-08 0.31895403E-02 -0.26756537E-04
83 5 -0.41008070E-03 0.23089571E-05 -0.22370585 0.19559850E-02
84 4 0.94229551E-02 0.10508975E-03 4.8292339 -0.45261983E-01
85 3 -0.82717511E-01 0.83559143E-03 -38.019655 0.39863429
86 2 0.29367339 0.13899461E-02 116.48052 -1.4178935
87 1 -0.42384901 0.42341243E-03 -143.90529 2.0490068
88 0 0.20664115 0.10256830E-04 60.838472  
89 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
90 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
91 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
92 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
93 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
94 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
95 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
96 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
97 0 0.84795330E-02 0.69040512E-07 60.838472  
98 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
99 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
100 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
101 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
102 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
103 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
104 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
105 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
106 0 0.84795330E-02 0.69040512E-07 60.838472  
107 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
108 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
109 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
110 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
111 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
112 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
113 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
114 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
115 0 0.84795330E-02 0.69040512E-07 60.838472  
116 7 -0.40948089E-09 0.25453480E-16 0.27116584E-14 -0.62861171E-17
117 6 0.27824401E-04 0.18943663E-07 0.31278875E-02 -0.26239341E-04
118 5 -0.20194690E-02 0.11288967E-04 -0.22019980 0.19250395E-02
119 4 0.46485732E-01 0.51517467E-03 4.7708035 -0.44700348E-01
120 3 -0.40800981 0.41092948E-02 -37.689401 0.39498418
121 2 1.4481156 0.68497892E-02 115.83752 -1.4092931
122 1 -2.0895440 0.20961589E-02 -143.52669 2.0427837
123 0 1.0185749 0.49211913E-04 60.838472  
124 7 -0.13445249E-08 -0.18047694E-15 0.95417141E-14 -0.13214217E-15
125 6 0.86679006E-05 0.59706481E-08 0.31811122E-02 -0.26685835E-04
126 5 -0.62708744E-03 0.35399132E-05 -0.22322676 0.19517563E-02
127 4 0.14446922E-01 0.16120088E-03 4.8212534 -0.45185271E-01
128 3 -0.12692755 0.12824971E-02 -37.974568 0.39813593
129 2 0.45077250 0.21342266E-02 116.39276 -1.4167196
130 1 -0.65066878 0.65069199E-03 -143.85363 2.0481576
131 0 0.31724317 0.15688047E-04 60.838472  
132 7 -0.36273983E-09 0.20506702E-16 0.28355953E-14 -0.21031252E-16
133 6 0.31332729E-04 0.21263507E-07 0.31183148E-02 -0.26159038E-04
134 5 -0.22728988E-02 0.12676343E-04 -0.21965515 0.19202323E-02
135 4 0.52294670E-01 0.57874510E-03 4.7617213 -0.44613054E-01
136 3 -0.45885907 0.46181761E-02 -37.638040 0.39441656
137 2 1.6283304 0.77009453E-02 115.73748 -1.4079552
138 1 -2.3493808 0.23573210E-02 -143.46777 2.0418153
139 0 1.1451796 0.55404125E-04 60.838472  
140 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
141 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
142 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
143 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
144 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
145 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
146 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
147 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
148 0 0.84795330E-02 0.69040512E-07 60.838472  
149 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
150 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
151 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
152 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
153 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
154 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
155 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
156 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
157 0 0.84795330E-02 0.69040512E-07 60.838472  
158 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
159 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
160 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
161 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
162 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
163 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
164 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
165 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
166 0 0.84795330E-02 0.69040512E-07 60.838472  
167 7 -0.28274920E-08 -0.16345214E-14 0.46368056E-14 -0.94845746E-16
168 6 0.42953992E-05 0.28692721E-08 0.31937312E-02 -0.26791694E-04
169 5 -0.30316380E-03 0.16971370E-05 -0.22394403 0.19580873E-02
170 4 0.69364303E-02 0.77204996E-04 4.8332007 -0.45300116E-01
171 3 -0.60796750E-01 0.61357787E-03 -38.042063 0.39888197
172 2 0.21571768 0.10202415E-02 116.52413 -1.4184768
173 1 -0.31125470 0.31058960E-03 -143.93096 2.0494287
174 0 0.15172706 0.75381079E-05 60.838472  
175 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
176 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
177 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
178 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
179 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
180 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
181 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
182 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
183 0 0.84795330E-02 0.69040512E-07 60.838472  
184 7 -0.82503231E-09 -0.51351738E-16 0.12241016E-14 0.32927944E-17
185 6 0.13977446E-04 0.96327798E-08 0.31661648E-02 -0.26560444E-04
186 5 -0.10150082E-02 0.57213099E-05 -0.22237692 0.19442553E-02
187 4 0.23397668E-01 0.26069885E-03 4.8070937 -0.45049164E-01
188 3 -0.20557234 0.20757554E-02 -37.894554 0.39725155
189 2 0.73003585 0.34559367E-02 116.23700 -1.4146362
190 1 -1.0537261 0.10549988E-02 -143.76192 2.0466502
191 0 0.51374429 0.25180125E-04 60.838472  
192 7 -0.30069612E-08 -0.19542618E-14 0.19078317E-14 -0.50432920E-16
193 6 0.40654145E-05 0.27001631E-08 0.31944189E-02 -0.26797463E-04
194 5 -0.28574061E-03 0.15968343E-05 -0.22398311 0.19584323E-02
195 4 0.65297595E-02 0.72632165E-04 4.8338515 -0.45306372E-01
196 3 -0.57206693E-01 0.57717611E-03 -38.045739 0.39892260
197 2 0.20294327 0.95960489E-03 116.53129 -1.4185725
198 1 -0.29279926 0.29210452E-03 -143.93517 2.0494979
199 0 0.14272481 0.70842375E-05 60.838472  
200 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
201 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
202 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
203 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
204 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
205 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
206 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
207 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
208 0 0.84795330E-02 0.69040512E-07 60.838472  
209 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
210 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
211 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
212 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
213 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
214 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
215 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
216 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
217 0 0.84795330E-02 0.69040512E-07 60.838472  
218 7 -0.27792623E-09 0.22164045E-16 0.21259137E-14 -0.20635904E-16
219 6 0.40639744E-04 0.27287367E-07 0.30931444E-02 -0.25947888E-04
220 5 -0.29434349E-02 0.16318805E-04 -0.21822268 0.19075894E-02
221 4 0.67634767E-01 0.74565575E-03 4.7378279 -0.44383409E-01
222 3 -0.59298500 0.59576973E-02 -37.502888 0.39292297
223 2 2.1033934 0.99404830E-02 115.47420 -1.4044340
224 1 -3.0341094 0.30498981E-02 -143.31270 2.0392664
225 0 1.4787491 0.70012147E-04 60.838472  
226 7 -0.33810131E-08 -0.27652445E-14 0.26627859E-14 -0.58200283E-16
227 6 0.36689073E-05 0.24058709E-08 0.31956190E-02 -0.26807530E-04
228 5 -0.25546270E-03 0.14218557E-05 -0.22405130 0.19590342E-02
229 4 0.58214771E-02 0.64657129E-04 4.8349870 -0.45317287E-01
230 3 -0.50948863E-01 0.51367157E-03 -38.052152 0.39899349
231 2 0.18066864 0.85385983E-03 116.54377 -1.4187394
232 1 -0.26061366 0.25981409E-03 -143.94252 2.0496187
233 0 0.12702395 0.63116617E-05 60.838472  
234 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
235 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
236 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
237 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
238 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
239 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
240 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
241 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
242 0 0.84795330E-02 0.69040512E-07 60.838472  
243 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
244 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
245 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
246 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
247 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
248 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
249 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
250 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
251 0 0.84795330E-02 0.69040512E-07 60.838472  
252 7 -0.82503231E-09 -0.51351738E-16 0.12241016E-14 0.32927944E-17
253 6 0.13977446E-04 0.96327798E-08 0.31661648E-02 -0.26560444E-04
254 5 -0.10150082E-02 0.57213099E-05 -0.22237692 0.19442553E-02
255 4 0.23397668E-01 0.26069885E-03 4.8070937 -0.45049164E-01
256 3 -0.20557234 0.20757554E-02 -37.894554 0.39725155
257 2 0.73003585 0.34559367E-02 116.23700 -1.4146362
258 1 -1.0537261 0.10549988E-02 -143.76192 2.0466502
259 0 0.51374429 0.25180125E-04 60.838472  
260 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
261 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
262 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
263 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
264 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
265 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
266 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
267 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
268 0 0.84795330E-02 0.69040512E-07 60.838472  
269 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
270 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
271 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
272 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
273 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
274 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
275 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
276 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
277 0 0.84795330E-02 0.69040512E-07 60.838472  
278 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
279 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
280 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
281 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
282 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
283 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
284 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
285 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
286 0 0.84795330E-02 0.69040512E-07 60.838472  
287 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
288 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
289 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
290 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
291 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
292 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
293 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
294 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
295 0 0.84795330E-02 0.69040512E-07 60.838472  
296 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
297 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
298 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
299 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
300 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
301 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
302 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
303 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
304 0 0.84795330E-02 0.69040512E-07 60.838472  
305 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
306 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
307 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
308 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
309 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
310 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
311 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
312 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
313 0 0.84795330E-02 0.69040512E-07 60.838472  
314 7 -0.10014154E-08 -0.81239843E-16 0.11018469E-14 0.58559054E-17
315 6 0.11557021E-04 0.79727734E-08 0.31729523E-02 -0.26617383E-04
316 5 -0.83849118E-03 0.47310911E-05 -0.22276285 0.19476617E-02
317 4 0.19328005E-01 0.21552601E-03 4.8135244 -0.45110977E-01
318 3 -0.16982881 0.17154513E-02 -37.930895 0.39765322
319 2 0.60313702 0.28555610E-02 116.30775 -1.4155825
320 1 -0.87059274 0.87115248E-03 -143.80358 2.0473349
321 0 0.42446680 0.20921646E-04 60.838472  
322 7 -0.19679334E-08 -0.55830450E-15 0.73067038E-14 -0.10481378E-15
323 6 0.60098048E-05 0.41024247E-08 0.31887146E-02 -0.26749610E-04
324 5 -0.43125117E-03 0.24295581E-05 -0.22365891 0.19555707E-02
325 4 0.99140727E-02 0.11058611E-03 4.8284521 -0.45254469E-01
326 3 -0.87042882E-01 0.87935818E-03 -38.015239 0.39858547
327 2 0.30904913 0.14628239E-02 116.47193 -1.4177785
328 1 -0.44605245 0.44566177E-03 -143.90023 2.0489236
329 0 0.21746903 0.10789310E-04 60.838472  
330 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
331 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
332 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
333 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
334 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
335 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
336 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
337 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
338 0 0.84795330E-02 0.69040512E-07 60.838472  
339 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
340 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
341 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
342 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
343 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
344 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
345 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
346 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
347 0 0.84795330E-02 0.69040512E-07 60.838472  
348 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
349 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
350 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
351 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
352 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
353 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
354 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
355 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
356 0 0.84795330E-02 0.69040512E-07 60.838472  
357 7 -0.47992988E-08 -0.78589091E-14 0.68646542E-15 -0.30955872E-16
358 6 0.27652519E-05 0.17059761E-08 0.31984784E-02 -0.26831517E-04
359 5 -0.18437842E-03 0.10059259E-05 -0.22421376 0.19604681E-02
360 4 0.41452153E-02 0.45687893E-04 4.8376915 -0.45343286E-01
361 3 -0.36095256E-01 0.36259938E-03 -38.067423 0.39916230
362 2 0.12773474 0.60215454E-03 116.57348 -1.4191369
363 1 -0.18408569 0.18300024E-03 -143.96000 2.0499061
364 0 0.89681505E-01 0.44406402E-05 60.838472  
365 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
366 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
367 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
368 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
369 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
370 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
371 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
372 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
373 0 0.84795330E-02 0.69040512E-07 60.838472  
374 7 -0.82503231E-09 -0.51351740E-16 0.12241016E-14 0.32927943E-17
375 6 0.13977446E-04 0.96327798E-08 0.31661648E-02 -0.26560444E-04
376 5 -0.10150082E-02 0.57213099E-05 -0.22237692 0.19442553E-02
377 4 0.23397668E-01 0.26069885E-03 4.8070937 -0.45049164E-01
378 3 -0.20557234 0.20757554E-02 -37.894554 0.39725155
379 2 0.73003585 0.34559367E-02 116.23700 -1.4146362
380 1 -1.0537261 0.10549988E-02 -143.76192 2.0466502
381 0 0.51374429 0.25180125E-04 60.838472  
382 7 -0.14484255E-08 -0.22640921E-15 0.11860658E-13 -0.17473455E-15
383 6 0.80640390E-05 0.55493782E-08 0.31828288E-02 -0.26700235E-04
384 5 -0.58275339E-03 0.32892043E-05 -0.22332434 0.19526176E-02
385 4 0.13421983E-01 0.14977251E-03 4.8228790 -0.45200897E-01
386 3 -0.11791368 0.11914425E-02 -37.983753 0.39823745
387 2 0.41875064 0.19825898E-02 116.41064 -1.4169588
388 1 -0.60444169 0.60433957E-03 -143.86415 2.0483306
389 0 0.29470347 0.14596444E-04 60.838472  
390 7 -0.39580774E-08 -0.44227731E-14 0.11636167E-14 -0.41707686E-16
391 6 0.32141699E-05 0.20604355E-08 0.31970280E-02 -0.26819350E-04
392 5 -0.22019277E-03 0.12166791E-05 -0.22413136 0.19597408E-02
393 4 0.49928883E-02 0.55301604E-04 4.8363199 -0.45330101E-01
394 3 -0.43616617E-01 0.43917630E-03 -38.059679 0.39907669
395 2 0.15455301 0.72976032E-03 116.55841 -1.4189353
396 1 -0.22286705 0.22195160E-03 -143.95114 2.0497604
397 0 0.10860754 0.53891855E-05 60.838472  
398 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
399 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
400 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
401 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
402 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
403 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
404 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
405 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
406 0 0.84795330E-02 0.69040512E-07 60.838472  
407 7 -0.11367252E-08 -0.11237552E-15 0.64990219E-14 -0.76141421E-16
408 6 0.10208875E-04 0.70392633E-08 0.31767506E-02 -0.26649246E-04
409 5 -0.73996474E-03 0.41768817E-05 -0.22297880 0.19495677E-02
410 4 0.17054262E-01 0.19023662E-03 4.8171224 -0.45145562E-01
411 3 -0.14984895 0.15139241E-02 -37.951226 0.39787794
412 2 0.53218631 0.25196058E-02 116.34733 -1.4161119
413 1 -0.76818791 0.76863149E-03 -143.82688 2.0477179
414 0 0.37454105 0.18419454E-04 60.838472  
415 7 -0.16562279E-08 -0.33302517E-15 0.83739993E-14 -0.11718072E-15
416 6 0.70854965E-05 0.48621003E-08 0.31856219E-02 -0.26723666E-04
417 5 -0.51074476E-03 0.28813203E-05 -0.22348312 0.19540191E-02
418 4 0.11755902E-01 0.13117422E-03 4.8255239 -0.45226322E-01
419 3 -0.10325611 0.10433297E-02 -37.998697 0.39840262
420 2 0.36667104 0.17358410E-02 116.43973 -1.4173478
421 1 -0.52925309 0.52906573E-03 -143.88128 2.0486121
422 0 0.25804098 0.12766303E-04 60.838472  
423 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
424 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
425 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
426 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
427 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
428 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
429 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
430 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
431 0 0.84795330E-02 0.69040512E-07 60.838472  
432 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
433 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
434 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
435 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
436 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
437 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
438 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
439 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
440 0 0.84795330E-02 0.69040512E-07 60.838472  
441 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
442 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
443 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
444 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
445 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
446 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
447 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
448 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
449 0 0.84795330E-02 0.69040512E-07 60.838472  
450 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
451 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
452 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
453 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
454 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
455 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
456 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
457 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
458 0 0.84795330E-02 0.69040512E-07 60.838472  
459 7 -0.73236962E-09 -0.43419393E-16 0.11851766E-14 0.97251562E-18
460 6 0.15714075E-04 0.10820408E-07 0.31613160E-02 -0.26519768E-04
461 5 -0.11414297E-02 0.64279510E-05 -0.22210120 0.19418216E-02
462 4 0.26309733E-01 0.29296735E-03 4.8024989 -0.45004998E-01
463 3 -0.23113649 0.23331607E-02 -37.868585 0.39696453
464 2 0.82077326 0.38852781E-02 116.18644 -1.4139599
465 1 -1.1846568 0.11862350E-02 -143.73215 2.0461609
466 0 0.57756847 0.28335916E-04 60.838472  
467 7 -0.78904556E-08 0.24330470E-15 -0.37077476E-14 0.15816261E-16
468 6 0.20509614E-05 0.10563288E-08 0.32011659E-02 -0.26854062E-04
469 5 -0.12099283E-03 0.61836724E-06 -0.22436635 0.19618150E-02
470 4 0.26059247E-02 0.27978196E-04 4.8402300 -0.45367690E-01
471 3 -0.22313563E-01 0.22134896E-03 -38.081748 0.39932066
472 2 0.78418401E-01 0.36646799E-03 116.60134 -1.4195096
473 1 -0.11265507 0.11095342E-03 -143.97640 2.0501755
474 0 0.54793307E-01 0.26774851E-05 60.838472  
475 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
476 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
477 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
478 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
479 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
480 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
481 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
482 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
483 0 0.84795330E-02 0.69040512E-07 60.838472  
484 7 -0.14071951E-08 -0.20905665E-15 0.11061732E-13 -0.16093907E-15
485 6 0.82929144E-05 0.57091693E-08 0.31821776E-02 -0.26694772E-04
486 5 -0.59956487E-03 0.33843162E-05 -0.22328733 0.19522909E-02
487 4 0.13810706E-01 0.15410780E-03 4.8222624 -0.45194970E-01
488 3 -0.12133259 0.12259831E-02 -37.980269 0.39819894
489 2 0.43089676 0.20401076E-02 116.40386 -1.4168681
490 1 -0.62197626 0.62192370E-03 -143.86016 2.0482650
491 0 0.30325317 0.15009506E-04 60.838472  
492 7 -0.13445249E-08 -0.18047665E-15 0.95417141E-14 -0.13214217E-15
493 6 0.86679006E-05 0.59706481E-08 0.31811122E-02 -0.26685835E-04
494 5 -0.62708744E-03 0.35399132E-05 -0.22322676 0.19517563E-02
495 4 0.14446922E-01 0.16120088E-03 4.8212534 -0.45185271E-01
496 3 -0.12692755 0.12824971E-02 -37.974568 0.39813593
497 2 0.45077250 0.21342266E-02 116.39276 -1.4167196
498 1 -0.65066878 0.65069199E-03 -143.85363 2.0481576
499 0 0.31724317 0.15688047E-04 60.838472  
500 7 -0.15523266E-08 -0.27615420E-15 0.12029564E-13 -0.18067838E-15
501 6 0.75416602E-05 0.51826322E-08 0.31843179E-02 -0.26712727E-04
502 5 -0.54434189E-03 0.30717841E-05 -0.22340899 0.19533648E-02
503 4 0.12533477E-01 0.13985656E-03 4.8242891 -0.45214452E-01
504 3 -0.11009780 0.11124809E-02 -37.991720 0.39832551
505 2 0.39098153 0.18510111E-02 116.42615 -1.4171662
506 1 -0.56435173 0.56423054E-03 -143.87328 2.0484807
507 0 0.27515558 0.13608470E-04 60.838472  
508 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
509 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
510 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
511 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
512 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
513 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
514 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
515 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
516 0 0.84795330E-02 0.69040512E-07 60.838472  
517 7 -0.19679334E-08 -0.55830508E-15 0.73067036E-14 -0.10481378E-15
518 6 0.60098048E-05 0.41024247E-08 0.31887146E-02 -0.26749610E-04
519 5 -0.43125117E-03 0.24295581E-05 -0.22365891 0.19555707E-02
520 4 0.99140727E-02 0.11058611E-03 4.8284521 -0.45254469E-01
521 3 -0.87042882E-01 0.87935818E-03 -38.015239 0.39858547
522 2 0.30904913 0.14628239E-02 116.47193 -1.4177785
523 1 -0.44605245 0.44566177E-03 -143.90023 2.0489236
524 0 0.21746903 0.10789310E-04 60.838472  
525 7 -0.82503231E-09 -0.51351719E-16 0.12241016E-14 0.32927949E-17
526 6 0.13977446E-04 0.96327798E-08 0.31661648E-02 -0.26560444E-04
527 5 -0.10150082E-02 0.57213099E-05 -0.22237692 0.19442553E-02
528 4 0.23397668E-01 0.26069885E-03 4.8070937 -0.45049164E-01
529 3 -0.20557234 0.20757554E-02 -37.894554 0.39725155
530 2 0.73003585 0.34559367E-02 116.23700 -1.4146362
531 1 -1.0537261 0.10549988E-02 -143.76192 2.0466502
532 0 0.51374429 0.25180125E-04 60.838472  
533 7 -0.38870664E-09 0.19455577E-16 0.24755191E-14 -0.12808364E-16
534 6 0.29281304E-04 0.19894657E-07 0.31239065E-02 -0.26205945E-04
535 5 -0.21247570E-02 0.11867224E-04 -0.21997331 0.19230404E-02
536 4 0.48899824E-01 0.54159124E-03 4.7670268 -0.44664047E-01
537 3 -0.42914583 0.43211202E-02 -37.668044 0.39474815
538 2 1.5230312 0.72029001E-02 115.79592 -1.4087368
539 1 -2.1975643 0.22057801E-02 -143.50219 2.0423811
540 0 1.0712091 0.51290716E-04 60.838472  
541 7 -0.42871680E-09 0.20277040E-16 0.27849794E-14 -0.81971676E-17
542 6 0.26599345E-04 0.18133649E-07 0.31312414E-02 -0.26267477E-04
543 5 -0.19308842E-02 0.10802137E-04 -0.22039061 0.19267236E-02
544 4 0.44453781E-01 0.49290131E-03 4.7739850 -0.44730926E-01
545 3 -0.39021514 0.39309784E-02 -37.707390 0.39518299
546 2 1.3850351 0.65519935E-02 115.87255 -1.4097617
547 1 -1.9985821 0.20044655E-02 -143.54732 2.0431229
548 0 0.97425097 0.47183723E-04 60.838472  
549 7 -0.38870664E-09 0.19455577E-16 0.24755191E-14 -0.12808364E-16
550 6 0.29281304E-04 0.19894657E-07 0.31239065E-02 -0.26205945E-04
551 5 -0.21247570E-02 0.11867224E-04 -0.21997331 0.19230404E-02
552 4 0.48899824E-01 0.54159124E-03 4.7670268 -0.44664047E-01
553 3 -0.42914583 0.43211202E-02 -37.668044 0.39474815
554 2 1.5230312 0.72029001E-02 115.79592 -1.4087368
555 1 -2.1975643 0.22057801E-02 -143.50219 2.0423811
556 0 1.0712091 0.51290716E-04 60.838472  
557 7 -0.38870664E-09 0.19454314E-16 0.24755191E-14 -0.12808364E-16
558 6 0.29281304E-04 0.19894657E-07 0.31239065E-02 -0.26205945E-04
559 5 -0.21247570E-02 0.11867224E-04 -0.21997331 0.19230404E-02
560 4 0.48899824E-01 0.54159124E-03 4.7670268 -0.44664047E-01
561 3 -0.42914583 0.43211202E-02 -37.668044 0.39474815
562 2 1.5230312 0.72029001E-02 115.79592 -1.4087368
563 1 -2.1975643 0.22057801E-02 -143.50219 2.0423811
564 0 1.0712091 0.51290716E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 36 1 VerySmooth 6.926 5.835 1.184 0.251    
2 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 37 1 VerySmooth 6.926 5.835 1.184 0.251    
3 NONRESWINDOW_U_1.22_SHGC_EAST_0.25 38 1 VerySmooth 6.926 5.835 1.184 0.251    
4 NONRESWINDOW_U_1.22_SHGC_WEST_0.25 39 1 VerySmooth 6.926 5.835 1.184 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SOUTH SpectralAverage   2.00000E-003 0.10958 0.41397 0.41397 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.39956 1.00000 No
2 GLAZING LAYER NORTH SpectralAverage   2.00000E-003 0.10958 0.41397 0.41397 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.39956 1.00000 No
3 GLAZING LAYER EAST SpectralAverage   2.00000E-003 0.10958 0.41397 0.41397 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.39956 1.00000 No
4 GLAZING LAYER WEST SpectralAverage   2.00000E-003 0.10958 0.41397 0.41397 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.39956 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.7570 58614.2 14.749 0.4701


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 4161C8 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
2 1AD133 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
3 330DF9 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
4 481E71 0 473.81 134.43 9.14 0 3.05 2.74 3.14 0.27 3 No No
5 78F987 0 473.81 134.43 9.14 0 3.05 2.74 3.14 0.27 2 No No
6 FLOOR 1 ANESTHESIA SLAB 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
7 DDCF3E 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
8 BE1AE1 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
9 FLOOR 1 ANESTHESIA_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
10 70DAD1 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
11 32CC19 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
12 BBEE0B 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
13 F951A6 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
14 FLOOR 1 BIO HAZ SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
15 F6F6C6 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
16 FLOOR 1 BIO HAZ_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
17 5F762C 0 473.81 134.43 9.14 0 3.05 6.10 6.24 0.48 4 No No
18 D8037E 0 473.81 134.43 9.14 0 3.05 6.10 6.24 0.48 1 No No
19 4507E9 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
20 C48E94 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
21 6B31A8 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
22 368E02 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
23 FLOOR 1 CAFE SLAB 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
24 4783F2 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
25 FLOOR 1 CAFE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
26 EA8FA7 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
27 FE7511 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
28 59E0E4 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
29 7949FA 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
30 FLOOR 1 CLEAN SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
31 EC2478 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
32 1B4EDC 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
33 D1AFC9 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
34 442699 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
35 FLOOR 1 CLEAN_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
36 FD8CF2 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
37 49DA86 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
38 619EE6 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
39 B551AD 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
40 FLOOR 1 CLEAN WORK SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
41 8E9267 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
42 BB097B 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
43 2E1FB7 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
44 FLOOR 1 CLEAN WORK_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
45 94A56A 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
46 4A854B 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
47 8594D3 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
48 86244A 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
49 FLOOR 1 DICTATION SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
50 672F1E 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
51 A7115C 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
52 AF27F8 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
53 FLOOR 1 DICTATION_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
54 256F02 0 0.00 0.00 0.00 0 3.05 2.74 1.96 0.28 0 No No
55 DE027F 0 0.00 0.00 0.00 0 3.05 2.74 1.96 0.28 0 No No
56 84FB73 0 473.81 143.75 9.14 0 3.05 2.74 1.96 0.28 3 No No
57 4A8120 0 473.81 143.75 9.14 0 3.05 2.74 1.96 0.28 2 No No
58 CC17E8 0 0.00 0.00 0.00 0 3.05 2.74 1.96 0.28 0 No No
59 FLOOR 1 DRESSING ROOM SLAB 0 0.00 0.00 0.00 0 3.05 2.74 1.96 0.28 0 No No
60 5DACB5 0 0.00 0.00 0.00 0 3.05 2.74 1.96 0.28 0 No No
61 FLOOR 1 DRESSING ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.74 1.96 0.28 0 No No
62 9879B2 0 0.00 0.00 0.00 0 3.05 2.13 2.84 0.00 0 No No
63 2D53AC 0 0.00 0.00 0.00 0 3.05 2.13 2.84 0.00 0 No No
64 7F5C82 0 302.86 143.75 9.14 0 3.05 2.13 2.84 0.00 0 No No
65 E82152 0 0.00 0.00 0.00 0 3.05 2.13 2.84 0.00 0 No No
66 FLOOR 1 ELECTRICAL ROOM SLAB 0 0.00 0.00 0.00 0 3.05 2.13 2.84 0.00 0 No No
67 D7AC92 0 0.00 0.00 0.00 0 3.05 2.13 2.84 0.00 0 No No
68 FLOOR 1 ELECTRICAL ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.13 2.84 0.00 0 No No
69 F99476 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
70 C732B0 0 473.81 143.75 9.14 0 3.05 6.10 2.77 0.00 0 No No
71 9926F7 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
72 E02487 0 302.86 110.86 9.14 0 3.05 6.10 2.77 0.00 0 No No
73 BA05F7 0 302.86 110.86 9.14 0 3.05 6.10 2.77 0.00 0 No No
74 B45B50 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
75 FLOOR 1 ELEVATOR PUMP ROOM SLAB 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
76 DF9D5D 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
77 827528 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
78 FLOOR 1 ELEVATOR PUMP ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
79 758B3C 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
80 A7F46C 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
81 3F71D3 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
82 8BB36F 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
83 FLOOR 1 HUMID SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
84 D21333 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
85 FLOOR 1 HUMID_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
86 FEC1E3 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
87 5D9E95 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
88 F4D6DD 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
89 FB87D3 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
90 445A39 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
91 3A6904 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
92 FLOOR 1 IT HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
93 FB17DD 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
94 8A2F34 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
95 9A5B84 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
96 FLOOR 1 IT HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
97 2CF0AA 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
98 307901 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
99 FA769A 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
100 319A6B 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
101 FLOOR 1 IT ROOM SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
102 C732D4 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
103 FLOOR 1 IT ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
104 822161 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
105 43A2A2 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
106 6FB351 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
107 8134C2 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
108 102EC4 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
109 BAD27A 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
110 5D8FAF 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
111 46E87C 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
112 3145CA 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
113 73E892 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
114 4418C4 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
115 FE5A3C 0 302.86 110.86 9.14 0 3.05 6.71 5.50 0.44 4 No No
116 AAE778 0 302.86 110.86 9.14 0 3.05 6.71 5.50 0.44 1 No No
117 F67E1F 0 302.86 110.86 9.14 0 3.05 6.71 5.50 0.44 0 No No
118 4911A5 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
119 FLOOR 1 LOBBY SLAB 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
120 D647E0 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
121 BFB8E1 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
122 78FEE8 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
123 FLOOR 1 LOBBY_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
124 A6D45E 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
125 F7F8BA 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
126 34019D 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
127 72A819 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
128 FLOOR 1 LOBBY HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
129 D60B94 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
130 B7E9B3 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
131 690A91 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
132 FLOOR 1 LOBBY HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
133 9FF31D 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
134 9D87EC 0 302.86 110.86 9.14 0 3.05 1.83 2.19 0.00 0 No No
135 F23EB6 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
136 7F6FC2 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
137 88CB69 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
138 FLOOR 1 LOBBY TOILET SLAB 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
139 9BB388 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
140 FLOOR 1 LOBBY TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
141 E9F3F6 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
142 A9C27A 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
143 F629C1 0 473.81 143.75 9.14 0 3.05 6.71 7.74 0.27 3 No No
144 3AAD8B 0 473.81 143.75 9.14 0 3.05 6.71 7.74 0.27 2 No No
145 8128A9 0 473.81 143.75 9.14 0 3.05 6.71 7.74 0.27 2 No No
146 962DB5 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
147 92E22C 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
148 FLOOR 1 LOCKER ROOM SLAB 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
149 7B1677 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
150 21C5E8 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
151 FDCEC5 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
152 C1F15F 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
153 1E6611 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
154 FLOOR 1 LOCKER ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
155 35028C 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
156 852027 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
157 EBFE47 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
158 D9965C 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
159 71783C 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
160 D8C098 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
161 66D163 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
162 8D03E8 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
163 9A0DF2 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
164 FLOOR 1 LOCKER ROOM HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
165 1891E7 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
166 BD75DE 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
167 3137C4 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
168 C8F2F1 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
169 6B171C 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
170 86C171 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
171 C605B5 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
172 FLOOR 1 LOCKER ROOM HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
173 18AFE3 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
174 761D33 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
175 9C0202 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
176 29BD5F 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
177 897BAF 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
178 3E6044 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
179 FLOOR 1 LOUNGE SLAB 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
180 7B9EEC 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
181 B04E85 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
182 FLOOR 1 LOUNGE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
183 A4B378 0 0.00 0.00 0.00 0 3.05 4.57 2.28 0.00 0 No No
184 72BCFE 0 0.00 0.00 0.00 0 3.05 4.57 2.28 0.00 0 No No
185 E85BB5 0 473.81 143.75 9.14 0 3.05 4.57 2.28 0.00 0 No No
186 7EB6E7 0 473.81 143.75 9.14 0 3.05 4.57 2.28 0.00 0 No No
187 577FC1 0 302.86 143.75 9.14 0 3.05 4.57 2.28 0.00 0 No No
188 FLOOR 1 MED GAS SLAB 0 0.00 0.00 0.00 0 3.05 4.57 2.28 0.00 0 No No
189 FLOOR 1 MED GAS ROOF 0 1373.29 114.97 6.10 0 3.05 4.57 2.28 0.00 0 No No
190 FLOOR 1 MED GAS_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 4.57 2.28 0.00 0 No No
191 F0B690 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
192 D2C53A 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
193 BFD4BB 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
194 C114C1 0 473.81 143.75 9.14 0 3.05 1.52 3.53 0.00 0 No No
195 D18914 0 473.81 143.75 9.14 0 3.05 1.52 3.53 0.00 0 No No
196 92A2CB 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
197 1EC3A0 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
198 E66ECE 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
199 FLOOR 1 MRI CONTROL ROOM SLAB 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
200 290CAB 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
201 FLOOR 1 MRI CONTROL ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
202 824665 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
203 68F53B 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
204 27B0D7 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
205 90FDA9 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
206 91DE28 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
207 A8DB72 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
208 8A30DD 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
209 596DE0 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
210 B92155 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
211 FLOOR 1 MRI HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
212 5CB500 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
213 FLOOR 1 MRI HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
214 2FAF44 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
215 A78253 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
216 E5BC3F 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
217 867BBB 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
218 F3084E 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
219 BA91C7 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
220 FLOOR 1 MRI ROOM SLAB 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
221 803791 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
222 FLOOR 1 MRI ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
223 ADB8D0 0 473.81 143.75 9.14 0 3.05 1.83 2.19 0.00 0 No No
224 30DB21 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
225 C9D24D 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
226 4ED109 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
227 24139C 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
228 FLOOR 1 MRI TOILET SLAB 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
229 388F10 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
230 FLOOR 1 MRI TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
231 855191 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
232 C0F51F 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
233 A59907 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
234 28DE5A 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
235 58B6B6 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
236 725D3E 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
237 FLOOR 1 NOURISHMENT SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
238 4E5019 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
239 E8F02D 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
240 6ECCF3 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
241 AA1F5C 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
242 F665B1 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
243 FLOOR 1 NOURISHMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
244 6822BB 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
245 825233 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
246 86A28D 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
247 C92A6E 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
248 114EC6 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
249 9EB05A 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
250 7434CD 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
251 344D34 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
252 59CEFB 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
253 FLOOR 1 NURSE HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
254 C75191 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
255 92E327 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
256 7F6B1B 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
257 4A49C1 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
258 8F5FFC 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
259 DDBA1E 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
260 FLOOR 1 NURSE HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
261 4E3BB5 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
262 415590 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
263 D9F81F 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
264 E1B4BB 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
265 FLOOR 1 NURSE JANITOR SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
266 2CB843 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
267 E2AB17 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
268 FLOOR 1 NURSE JANITOR_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
269 464A53 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
270 FE5062 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
271 4A07CD 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
272 EE0803 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
273 DFDE4F 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
274 A452BE 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
275 FLOOR 1 NURSE STATION SLAB 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
276 BD4B70 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
277 A0117C 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
278 52F395 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
279 AA2E8F 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
280 FLOOR 1 NURSE STATION_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
281 CA6EDA 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
282 5EB34C 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
283 5CD67D 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
284 E5CB03 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
285 FLOOR 1 NURSE TOILET SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
286 156F92 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
287 FLOOR 1 NURSE TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
288 361D65 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
289 2B5816 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
290 7B67EC 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
291 7E0561 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
292 4E24F1 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
293 8259AE 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
294 FLOOR 1 OFFICE SLAB 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
295 B754EC 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
296 621A74 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
297 28F0DE 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
298 FLOOR 1 OFFICE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
299 879583 0 473.81 134.43 9.14 0 3.05 13.11 6.52 0.26 3 No No
300 9B1541 0 473.81 134.43 9.14 0 3.05 13.11 6.52 0.26 2 No No
301 CF850A 0 473.81 134.43 9.14 0 3.05 13.11 6.52 0.26 2 No No
302 83A098 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.26 0 No No
303 E326E4 0 302.86 143.75 9.14 0 3.05 13.11 6.52 0.26 3 No No
304 A6BA23 0 302.86 143.75 9.14 0 3.05 13.11 6.52 0.26 2 No No
305 D10D28 0 302.86 143.75 9.14 0 3.05 13.11 6.52 0.26 2 No No
306 D4B39B 0 302.86 143.75 9.14 0 3.05 13.11 6.52 0.26 0 No No
307 575A7B 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.26 0 No No
308 7E9E26 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.26 0 No No
309 FLOOR 1 OPERATING ROOM 1 SLAB 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.26 0 No No
310 E648BC 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.26 0 No No
311 FFE052 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.26 0 No No
312 611A3F 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.26 0 No No
313 FLOOR 1 OPERATING ROOM 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.26 0 No No
314 9C6F66 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.40 0 No No
315 1D96D7 0 302.86 143.75 9.14 0 3.05 7.32 6.65 0.40 3 No No
316 591336 0 302.86 143.75 9.14 0 3.05 7.32 6.65 0.40 2 No No
317 38B811 0 302.86 143.75 9.14 0 3.05 7.32 6.65 0.40 2 No No
318 C044D6 0 302.86 143.75 9.14 0 3.05 7.32 6.65 0.40 2 No No
319 A2AAC5 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.40 0 No No
320 1747DE 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.40 0 No No
321 F4C599 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.40 0 No No
322 964F72 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.40 0 No No
323 FLOOR 1 OPERATING ROOM 2 SLAB 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.40 0 No No
324 726F67 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.40 0 No No
325 406D70 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.40 0 No No
326 368A44 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.40 0 No No
327 FLOOR 1 OPERATING ROOM 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.40 0 No No
328 9E12D4 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
329 FD0958 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
330 AE206C 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
331 966665 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
332 52CA89 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
333 FLOOR 1 OPERATING ROOM 3 SLAB 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
334 8F1C77 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
335 18AD08 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
336 69AE66 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
337 CF6C6E 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
338 678B62 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
339 FLOOR 1 OPERATING ROOM 3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
340 2B4DBD 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
341 FCD8D2 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
342 F740DF 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
343 446771 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
344 A2F014 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
345 FLOOR 1 PACU SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
346 995832 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
347 FLOOR 1 PACU_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
348 33A280 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
349 BABBB4 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
350 F9B592 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
351 6E46A9 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
352 BA8FF7 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
353 25B45C 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
354 592524 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
355 EAACE4 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
356 3AE420 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
357 414FE2 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
358 DEAC23 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
359 22DAE3 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
360 FLOOR 1 PRE-OP HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
361 388CB3 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
362 FB3834 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
363 343C52 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
364 E63CF4 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
365 D6D2A5 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
366 83172E 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
367 8FE324 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
368 FLOOR 1 PRE-OP HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
369 4DA0F5 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
370 8F966C 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
371 FA21EE 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
372 5B255F 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
373 84418A 0 302.86 110.86 9.14 0 3.05 1.22 3.84 0.00 0 No No
374 FLOOR 1 PRE-OP ROOM 1 SLAB 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
375 3C43B2 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
376 BC6EE7 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
377 363652 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
378 FLOOR 1 PRE-OP ROOM 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
379 551E65 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
380 8C3884 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
381 9853A2 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
382 7AE5B9 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
383 FLOOR 1 PRE-OP ROOM 2 SLAB 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
384 39AFEA 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
385 CABD0E 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
386 AF38CF 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
387 C0A312 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
388 661D88 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
389 AFFD01 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
390 FLOOR 1 PRE-OP ROOM 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
391 2DEB73 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
392 7D08C0 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
393 36E420 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
394 1535AC 0 302.86 110.86 9.14 0 3.05 1.83 2.19 0.00 0 No No
395 FLOOR 1 PRE-OP TOILET SLAB 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
396 97616F 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
397 FLOOR 1 PRE-OP TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
398 95486C 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
399 EAE60F 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
400 6D2616 0 473.81 143.75 9.14 0 3.05 5.79 5.11 0.32 3 No No
401 1D94BE 0 473.81 143.75 9.14 0 3.05 5.79 5.11 0.32 2 No No
402 18748E 0 473.81 143.75 9.14 0 3.05 5.79 5.11 0.32 2 No No
403 704EC3 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
404 E20721 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
405 FA9EF2 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
406 FLOOR 1 PROCEDURE ROOM SLAB 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
407 673317 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
408 E5C1C9 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
409 79376C 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
410 FLOOR 1 PROCEDURE ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
411 6EA718 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
412 2730E5 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
413 E608B9 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
414 25AB11 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
415 5A39B1 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
416 234734 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
417 57B162 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
418 7BB928 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
419 A5A6A3 0 473.81 134.43 9.14 0 3.05 3.96 5.09 0.28 3 No No
420 137A56 0 473.81 134.43 9.14 0 3.05 3.96 5.09 0.28 2 No No
421 FLOOR 1 RECEPTION SLAB 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
422 A02892 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
423 9114B7 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
424 700E69 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
425 FLOOR 1 RECEPTION_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
426 11E9BF 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
427 839A66 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
428 FE2C3E 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
429 CD7BAD 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
430 6A1AB7 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
431 FLOOR 1 RECEPTION HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
432 68AAF3 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
433 DE014E 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
434 709E99 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
435 FLOOR 1 RECEPTION HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
436 28B002 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 3 No No
437 8D508E 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 2 No No
438 B2D381 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 2 No No
439 1DA13A 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 2 No No
440 44E54A 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 2 No No
441 D2D3BC 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 0 No No
442 C528DA 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 0 No No
443 EFD3F9 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 0 No No
444 F4FE92 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
445 66B6F7 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
446 72C4ED 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
447 FLOOR 1 RECOVERY ROOM SLAB 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
448 C5ECA6 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
449 65D500 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
450 AE5EBC 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
451 2A1A9E 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
452 FLOOR 1 RECOVERY ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
453 EA6DC8 0 473.81 134.43 9.14 0 3.05 2.13 3.02 0.11 3 No No
454 757D10 0 473.81 134.43 9.14 0 3.05 2.13 3.02 0.11 2 No No
455 612A96 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
456 BDC047 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
457 42E287 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
458 FLOOR 1 SCHEDULING SLAB 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
459 513564 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
460 58F893 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
461 FLOOR 1 SCHEDULING_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
462 7816FD 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
463 1B2EF8 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
464 24EAE3 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
465 9DB411 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
466 FLOOR 1 SCRUB SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
467 7008C0 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
468 FLOOR 1 SCRUB_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
469 762F8C 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
470 5D199F 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
471 ACADA4 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
472 4398AD 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
473 9E478E 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
474 6B967C 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
475 FLOOR 1 SOIL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
476 4B54B4 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
477 88D2F8 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
478 7274F6 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
479 FLOOR 1 SOIL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
480 A1087A 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
481 41CE25 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
482 9A776E 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
483 9ABA5B 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
484 FLOOR 1 SOIL HOLD SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
485 58A74A 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
486 D78A26 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
487 FLOOR 1 SOIL HOLD_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
488 37E2C7 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
489 23683B 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
490 CA9655 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
491 121DFF 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
492 FAE342 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
493 FLOOR 1 SOIL WORK SLAB 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
494 A44272 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
495 B9DDBA 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
496 9EBF3E 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
497 903092 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
498 FLOOR 1 SOIL WORK_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
499 5FD018 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
500 809229 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
501 B40F89 0 302.86 110.86 9.14 0 3.05 11.28 4.94 0.19 3 No No
502 E33BAE 0 302.86 110.86 9.14 0 3.05 11.28 4.94 0.19 2 No No
503 997723 0 473.81 134.43 9.14 0 3.05 11.28 4.94 0.19 3 No No
504 24167A 0 473.81 134.43 9.14 0 3.05 11.28 4.94 0.19 2 No No
505 2C0938 0 473.81 134.43 9.14 0 3.05 11.28 4.94 0.19 2 No No
506 62B5AF 0 473.81 134.43 9.14 0 3.05 11.28 4.94 0.19 0 No No
507 CA45DE 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
508 5B693D 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
509 FLOOR 1 STEP DOWN SLAB 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
510 FBDD49 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
511 4284B6 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
512 FCE842 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
513 FLOOR 1 STEP DOWN_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
514 829DCE 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
515 E77E00 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
516 CEC7BD 0 473.81 134.43 9.14 0 3.05 2.44 4.42 0.30 3 No No
517 8600DD 0 473.81 134.43 9.14 0 3.05 2.44 4.42 0.30 2 No No
518 8C4FA5 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
519 B3A518 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
520 44686F 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
521 6A2C62 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
522 A809DD 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
523 EE0E68 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
524 88AE01 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
525 2C9CF4 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
526 765EA5 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
527 2B370E 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
528 F30797 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
529 FLOOR 1 STERILE HALL SLAB 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
530 3179A6 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
531 370DB2 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
532 34B3F0 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
533 CEDA0D 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
534 4469CD 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
535 F62393 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
536 340FB5 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
537 CDA7F8 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
538 FLOOR 1 STERILE HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
539 8043B2 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
540 38F548 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
541 96662A 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
542 1003C1 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
543 863C6C 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
544 808817 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
545 EA4B61 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
546 FLOOR 1 NURSE STORAGE SLAB 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
547 C1737B 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
548 D44BF1 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
549 5C05FF 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
550 FLOOR 1 STERILE STORAGE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
551 707E04 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
552 8E5BB9 0 302.86 110.86 9.14 0 3.05 19.20 8.90 0.14 3 No No
553 71E924 0 302.86 110.86 9.14 0 3.05 19.20 8.90 0.14 0 No No
554 859BC1 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 3 No No
555 A1ED60 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 2 No No
556 E8D997 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 2 No No
557 88E1FC 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 2 No No
558 3C44F9 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 0 No No
559 49526E 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 0 No No
560 865AE8 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 0 No No
561 891195 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
562 8B4DC1 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
563 19D150 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
564 814856 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
565 5B533A 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
566 FLOOR 1 STORAGE SLAB 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
567 FLOOR 1 STORGE ROOF 0 1373.29 114.97 6.10 0 3.05 19.20 8.90 0.14 0 No No
568 FLOOR 1 STORAGE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
569 61E610 0 302.86 143.75 9.14 0 3.05 4.27 4.27 0.31 3 No No
570 F83F33 0 302.86 143.75 9.14 0 3.05 4.27 4.27 0.31 2 No No
571 76F2F2 0 0.00 0.00 0.00 0 3.05 4.27 4.27 0.31 0 No No
572 D61127 0 0.00 0.00 0.00 0 3.05 4.27 4.27 0.31 0 No No
573 196C5F 0 0.00 0.00 0.00 0 3.05 4.27 4.27 0.31 0 No No
574 FLOOR 1 SUB-STERILE SLAB 0 0.00 0.00 0.00 0 3.05 4.27 4.27 0.31 0 No No
575 1875B3 0 0.00 0.00 0.00 0 3.05 4.27 4.27 0.31 0 No No
576 FLOOR 1 SUB-STERILE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 4.27 4.27 0.31 0 No No
577 39E49D 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
578 F43F35 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
579 89BBEB 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
580 87231D 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
581 529072 0 302.86 143.75 9.14 0 3.05 4.88 3.90 0.00 0 No No
582 5E66D1 0 302.86 143.75 9.14 0 3.05 4.88 3.90 0.00 0 No No
583 C1C64E 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
584 1D9EED 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
585 20FB14 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
586 DEFACF 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
587 FLOOR 1 UTILITY HALL SLAB 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
588 FLOOR 1 UTILITY HALL ROOF 0 1373.29 114.97 6.10 0 3.05 4.88 3.90 0.00 0 No No
589 5136E3 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
590 EFCC3C 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
591 FLOOR 1 UTILITY HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
592 2E8328 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
593 E321D9 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
594 E89C6C 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
595 816F6D 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
596 FLOOR 1 UTILITY JANITOR SLAB 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
597 5F697A 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
598 FLOOR 1 UTILITY JANITOR_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
599 EC28A9 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.18 0 No No
600 204CB9 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.18 0 No No
601 62475F 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.18 0 No No
602 D95F04 0 302.86 143.75 9.14 0 3.05 5.49 5.78 0.18 3 No No
603 E14DAE 0 302.86 143.75 9.14 0 3.05 5.49 5.78 0.18 0 No No
604 B1F5EE 0 302.86 143.75 9.14 0 3.05 5.49 5.78 0.18 2 No No
605 87BFF9 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.18 0 No No
606 23CCB1 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.18 0 No No
607 FLOOR 1 UTILITY ROOM SLAB 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.18 0 No No
608 7DB101 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.18 0 No No
609 F28371 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.18 0 No No
610 FLOOR 1 UTILITY ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.18 0 No No
611 231744 0 0.00 0.00 0.00 0 3.05 2.44 2.58 0.00 0 No No
612 3330D8 0 302.86 110.86 9.14 0 3.05 2.44 2.58 0.00 0 No No
613 84A1D5 0 302.86 110.86 9.14 0 3.05 2.44 2.58 0.00 0 No No
614 2FEACD 0 0.00 0.00 0.00 0 3.05 2.44 2.58 0.00 0 No No
615 AA1709 0 0.00 0.00 0.00 0 3.05 2.44 2.58 0.00 0 No No
616 FLOOR 1 VESTIBULE SLAB 0 0.00 0.00 0.00 0 3.05 2.44 2.58 0.00 0 No No
617 C34217 0 0.00 0.00 0.00 0 3.05 2.44 2.58 0.00 0 No No
618 FLOOR 1 VESTIBULE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.44 2.58 0.00 0 No No
619 208CCF 0 302.86 143.75 9.14 0 3.05 12.19 5.12 0.26 3 No No
620 F52F3D 0 302.86 143.75 9.14 0 3.05 12.19 5.12 0.26 2 No No
621 AEF992 0 473.81 134.43 9.14 0 3.05 12.19 5.12 0.26 3 No No
622 80885D 0 473.81 134.43 9.14 0 3.05 12.19 5.12 0.26 2 No No
623 9AC2E9 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.26 0 No No
624 436189 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.26 0 No No
625 B184C1 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.26 0 No No
626 BC8EB7 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.26 0 No No
627 75353D 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.26 0 No No
628 2BD1E8 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.26 0 No No
629 240A7C 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.26 0 No No
630 FLOOR 2 CONFERENCE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.26 0 No No
631 F6D879 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
632 1701A6 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
633 772842 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
634 3C9825 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
635 C2CE5F 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
636 7149EA 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
637 FLOOR 2 CONFERENCE TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
638 296861 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
639 3D4DE8 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
640 8A5790 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
641 2DB420 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
642 56C7DA 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
643 E1B973 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
644 FLOOR 2 DICTATION_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
645 640E64 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
646 10E44F 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
647 54D065 0 473.81 134.43 9.14 0 3.05 12.80 5.23 0.23 3 No No
648 FEEF06 0 473.81 134.43 9.14 0 3.05 12.80 5.23 0.23 2 No No
649 1775A6 0 302.86 110.86 9.14 0 3.05 12.80 5.23 0.23 3 No No
650 2BE8DE 0 302.86 110.86 9.14 0 3.05 12.80 5.23 0.23 2 No No
651 513E2A 0 302.86 110.86 9.14 0 3.05 12.80 5.23 0.23 2 No No
652 BA5CD9 0 302.86 110.86 9.14 0 3.05 12.80 5.23 0.23 2 No No
653 6E3B28 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
654 14C7EF 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
655 5EBA9B 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
656 F24E0D 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
657 D023D9 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
658 A4BE81 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
659 FLOOR 2 EXAM 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
660 4EE021 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
661 6ED237 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
662 97F00A 0 473.81 134.43 9.14 0 3.05 5.49 6.86 0.22 3 No No
663 1AD478 0 473.81 134.43 9.14 0 3.05 5.49 6.86 0.22 2 No No
664 ADD799 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
665 4017DC 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
666 CCAA9D 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
667 4968A2 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
668 4579A7 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
669 FDAEB8 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
670 E3B855 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
671 906F5E 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
672 FLOOR 2 EXAM 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
673 DFA4B1 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
674 F23BF4 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
675 A497E9 0 473.81 134.43 9.14 0 3.05 7.32 8.13 0.27 3 No No
676 27F0AC 0 473.81 134.43 9.14 0 3.05 7.32 8.13 0.27 2 No No
677 26E66C 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
678 17C5CF 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
679 BA0A29 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
680 26AF41 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
681 75A3C4 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
682 BEC196 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
683 9B49F5 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
684 EB611D 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
685 C81AED 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
686 BD5B50 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
687 3AEAAB 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
688 D74115 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
689 5065F0 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
690 FLOOR 2 EXAM 3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
691 7C84B6 0 0.00 0.00 0.00 0 3.05 2.13 2.70 0.34 0 No No
692 D88779 0 0.00 0.00 0.00 0 3.05 2.13 2.70 0.34 0 No No
693 577E2E 0 0.00 0.00 0.00 0 3.05 2.13 2.70 0.34 0 No No
694 88A75F 0 473.81 134.43 9.14 0 3.05 2.13 2.70 0.34 3 No No
695 724114 0 473.81 134.43 9.14 0 3.05 2.13 2.70 0.34 2 No No
696 4E78E0 0 0.00 0.00 0.00 0 3.05 2.13 2.70 0.34 0 No No
697 C0697F 0 0.00 0.00 0.00 0 3.05 2.13 2.70 0.34 0 No No
698 FLOOR 2 EXAM 4_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.13 2.70 0.34 0 No No
699 83B6E3 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.34 0 No No
700 AC956A 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.34 0 No No
701 B4E619 0 302.86 143.75 9.14 0 3.05 7.62 5.47 0.34 3 No No
702 D538C4 0 302.86 143.75 9.14 0 3.05 7.62 5.47 0.34 2 No No
703 5635BC 0 302.86 143.75 9.14 0 3.05 7.62 5.47 0.34 2 No No
704 BFA29B 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.34 0 No No
705 65AB67 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.34 0 No No
706 C25071 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.34 0 No No
707 31B3DF 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.34 0 No No
708 FLOOR 2 EXAM 5_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.34 0 No No
709 F29458 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
710 1EB5B1 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
711 9EC269 0 473.81 143.75 9.14 0 3.05 4.57 4.57 0.30 3 No No
712 831C1D 0 473.81 143.75 9.14 0 3.05 4.57 4.57 0.30 2 No No
713 47CE83 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
714 A8FC82 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
715 C84AE1 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
716 F67EC8 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
717 10FB67 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
718 1624C5 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
719 917AB5 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
720 FLOOR 2 EXAM 6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
721 247258 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
722 B316F7 0 473.81 143.75 9.14 0 3.05 7.32 8.47 0.25 3 No No
723 9BB95F 0 473.81 143.75 9.14 0 3.05 7.32 8.47 0.25 2 No No
724 C0778D 0 473.81 143.75 9.14 0 3.05 7.32 8.47 0.25 2 No No
725 FF8B08 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
726 F976A9 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
727 8D6453 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
728 D1899C 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
729 5620F1 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
730 40E182 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
731 A6147C 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
732 37898A 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
733 F0D8EE 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
734 567037 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
735 6B3E65 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
736 245972 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
737 F17DF7 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
738 FLOOR 2 EXAM 7_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
739 D7DC8D 0 0.00 0.00 0.00 0 3.05 5.49 4.99 0.33 0 No No
740 9621FD 0 473.81 143.75 9.14 0 3.05 5.49 4.99 0.33 3 No No
741 7D2D69 0 473.81 143.75 9.14 0 3.05 5.49 4.99 0.33 2 No No
742 2EF63B 0 473.81 143.75 9.14 0 3.05 5.49 4.99 0.33 2 No No
743 6A2DCE 0 0.00 0.00 0.00 0 3.05 5.49 4.99 0.33 0 No No
744 7A03ED 0 0.00 0.00 0.00 0 3.05 5.49 4.99 0.33 0 No No
745 A9A1F6 0 0.00 0.00 0.00 0 3.05 5.49 4.99 0.33 0 No No
746 DA760E 0 0.00 0.00 0.00 0 3.05 5.49 4.99 0.33 0 No No
747 FLOOR 2 EXAM 8_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 5.49 4.99 0.33 0 No No
748 42CEE1 0 473.81 143.75 9.14 0 3.05 3.66 5.36 0.25 3 No No
749 C417C0 0 473.81 143.75 9.14 0 3.05 3.66 5.36 0.25 2 No No
750 35051E 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
751 685FFA 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
752 B51929 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
753 8E5734 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
754 4E920E 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
755 87C477 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
756 5D2769 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
757 FLOOR 2 EXAM 9_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
758 4979C8 0 473.81 134.43 9.14 0 3.05 1.83 3.05 0.00 0 No No
759 9E6B6C 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
760 DF91E0 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
761 53450D 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
762 DFCCAE 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
763 D4B714 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
764 3AE495 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
765 526C70 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
766 2C31F2 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
767 E26130 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
768 FLOOR 2 EXAM HALL 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
769 42FAB2 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
770 815D63 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
771 6713DA 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
772 8CA0BF 0 473.81 134.43 9.14 0 3.05 1.83 3.05 0.00 0 No No
773 4C8372 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
774 243E09 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
775 C94CC0 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
776 BD39AC 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
777 75EAF8 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
778 E9AEFF 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
779 FLOOR 2 EXAM HALL 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
780 479A9C 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
781 DA6040 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
782 6C95E7 0 473.81 134.43 9.14 0 3.05 1.83 3.05 0.00 0 No No
783 BC25F3 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
784 C08963 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
785 36A02A 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
786 A08A28 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
787 F87FCE 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
788 BAE3F8 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
789 D10995 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
790 D4A2A4 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
791 6C1891 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
792 FLOOR 2 EXAM HALL 3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
793 46F148 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
794 F209CC 0 473.81 143.75 9.14 0 3.05 1.83 3.09 0.00 0 No No
795 E7EC3B 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
796 55191F 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
797 3947B8 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
798 3B9E2E 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
799 C2156D 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
800 5CA4CF 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
801 4AA9BC 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
802 D1E495 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
803 4180E7 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
804 FLOOR 2 EXAM HALL 4_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
805 247FD8 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
806 2E6DF0 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
807 14F382 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
808 155BD6 0 473.81 143.75 9.14 0 3.05 1.83 3.09 0.00 0 No No
809 ED8563 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
810 A1BBBE 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
811 E0C60A 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
812 772953 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
813 15A02B 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
814 B9D6E3 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
815 FLOOR 2 EXAM HALL 5_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
816 942718 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
817 D2C12A 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
818 5556EE 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
819 C5EA55 0 473.81 143.75 9.14 0 3.05 1.83 3.09 0.00 0 No No
820 D37566 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
821 E7055D 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
822 EC3BEA 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
823 D2FA45 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
824 98E1BD 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
825 5F9E13 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
826 B4F89F 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
827 FLOOR 2 EXAM HALL 6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
828 8177BA 0 302.86 110.86 9.14 0 3.05 4.88 2.40 0.00 0 No No
829 5E657E 0 473.81 143.75 9.14 0 3.05 4.88 2.40 0.00 0 No No
830 4AD319 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
831 E0C0A7 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
832 5B736E 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
833 F6E6D8 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
834 FLOOR 2 JANITOR_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
835 97BB21 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
836 7620CF 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
837 680AA1 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
838 A524F1 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
839 4CDC86 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
840 B352F7 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
841 FLOOR 2 LOUNGE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
842 CBB2D7 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
843 D0731B 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
844 ECDEDB 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
845 ED1D7F 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
846 2805F0 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
847 5A7EAB 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
848 291561 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
849 4E1563 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
850 FLOOR 2 NURSE STATION 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
851 A49FCC 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
852 5DBD9D 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
853 491317 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
854 462370 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
855 9EADD8 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
856 DE8843 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
857 C45BF3 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
858 FLOOR 2 NURSE STATION 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
859 AAF377 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.32 0 No No
860 CE4555 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.32 0 No No
861 A8A4FA 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.32 0 No No
862 4B1439 0 302.86 143.75 9.14 0 3.05 12.19 6.32 0.32 3 No No
863 EB042B 0 302.86 143.75 9.14 0 3.05 12.19 6.32 0.32 2 No No
864 4C1F71 0 302.86 143.75 9.14 0 3.05 12.19 6.32 0.32 2 No No
865 D23C8B 0 302.86 143.75 9.14 0 3.05 12.19 6.32 0.32 2 No No
866 B4E4BE 0 302.86 143.75 9.14 0 3.05 12.19 6.32 0.32 2 No No
867 352740 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.32 0 No No
868 D3CF55 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.32 0 No No
869 64A2F7 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.32 0 No No
870 D1A180 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.32 0 No No
871 9BB582 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.32 0 No No
872 FLOOR 2 OFFICE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.32 0 No No
873 DFA16C 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
874 2884D1 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
875 CC4EB4 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
876 B2F07D 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
877 AF86E1 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
878 571934 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
879 67A7F3 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
880 24E235 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
881 AB568E 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
882 577A10 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
883 988ACA 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
884 F5AF76 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
885 4EDE0A 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
886 874DF8 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
887 8C822C 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
888 B44BE3 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
889 4F2F27 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
890 909DB9 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
891 30A09C 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
892 BFEF28 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
893 C588CC 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
894 FLOOR 2 OFFICE HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
895 23C13E 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
896 3DE7A6 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
897 4ABC66 0 473.81 134.43 9.14 0 3.05 14.94 8.69 0.37 3 No No
898 EEF55D 0 473.81 134.43 9.14 0 3.05 14.94 8.69 0.37 1 No No
899 E55A57 0 473.81 134.43 9.14 0 3.05 14.94 8.69 0.37 2 No No
900 5B04CF 0 302.86 110.86 9.14 0 3.05 14.94 8.69 0.37 4 No No
901 93D018 0 302.86 110.86 9.14 0 3.05 14.94 8.69 0.37 1 No No
902 FCDEAC 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
903 AB4E10 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
904 E7BF7F 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
905 FA00FE 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
906 14CDC6 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
907 39BFFB 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
908 167608 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
909 C39FCC 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
910 FLOOR 2 RECEPTION_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
911 CA9485 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
912 2740BD 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
913 F0AF69 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
914 8D1BC4 0 473.81 134.43 9.14 0 3.05 2.13 3.44 0.00 0 No No
915 9CE650 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
916 EEECA3 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
917 EE34A3 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
918 CFAD9D 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
919 25F524 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
920 D79C57 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
921 93F6DE 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
922 8AA0B7 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
923 1D6CD8 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
924 427B0D 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
925 A72F04 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
926 C51FD6 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
927 3110A1 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
928 F81393 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
929 4FA380 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
930 2FE383 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
931 3F961C 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
932 4B590B 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
933 20B940 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
934 21FC9D 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
935 EB4979 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
936 A5FA3B 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
937 7A3F36 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
938 4DAEA4 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
939 B52A5D 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
940 2C7827 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
941 FLOOR 2 RECEPTION HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
942 2D0A7F 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
943 E63515 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
944 B04C98 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
945 50DB3D 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
946 115AA8 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
947 CFB630 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
948 E9C76F 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
949 FLOOR 2 RECEPTION TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
950 9C568B 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
951 B76374 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
952 24DA9F 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
953 CADDAF 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
954 10830D 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
955 EF47B0 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
956 C3DB37 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
957 F631E4 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
958 93EF1F 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
959 FLOOR 2 SCHEDULING 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
960 9FBDA3 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
961 87BFF8 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
962 DB7F62 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
963 969F22 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
964 795751 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
965 6A14D8 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
966 E3963E 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
967 630683 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
968 4EB51A 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
969 FLOOR 2 SCHEDULING 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
970 390BCF 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
971 DE64CC 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
972 F6E717 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
973 58AD84 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
974 A3E3D6 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
975 ED1C1D 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
976 FLOOR 2 STORAGE 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
977 A168ED 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
978 ED650B 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
979 8E1DCD 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
980 16E41D 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
981 1C7FB1 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
982 4B217A 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
983 A3F683 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
984 430C7E 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
985 FLOOR 2 STORAGE 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
986 70C0BF 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
987 211EA4 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
988 E0D6E9 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
989 BADB96 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
990 1E3410 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
991 695D6E 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
992 FLOOR 2 STORAGE 3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
993 97B688 0 0.00 0.00 0.00 0 3.05 2.74 3.34 0.36 0 No No
994 290DF3 0 0.00 0.00 0.00 0 3.05 2.74 3.34 0.36 0 No No
995 4B55FA 0 302.86 143.75 9.14 0 3.05 2.74 3.34 0.36 3 No No
996 DD9F5D 0 302.86 143.75 9.14 0 3.05 2.74 3.34 0.36 2 No No
997 4F0CD7 0 0.00 0.00 0.00 0 3.05 2.74 3.34 0.36 0 No No
998 4D50C0 0 0.00 0.00 0.00 0 3.05 2.74 3.34 0.36 0 No No
999 703D3E 0 0.00 0.00 0.00 0 3.05 2.74 3.34 0.36 0 No No
1000 FLOOR 2 UTILITY_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.74 3.34 0.36 0 No No
1001 9C3A6A 0 473.81 143.75 9.14 0 3.05 7.92 12.12 0.23 3 No No
1002 15B02B 0 473.81 143.75 9.14 0 3.05 7.92 12.12 0.23 2 No No
1003 820282 0 473.81 143.75 9.14 0 3.05 7.92 12.12 0.23 2 No No
1004 5C7E1E 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1005 B5E37D 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1006 8D1659 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1007 E88E01 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1008 4CE123 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1009 E55935 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1010 C52EE0 0 473.81 143.75 9.14 0 3.05 7.92 12.12 0.23 3 No No
1011 9AB0BF 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1012 1A8E2A 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1013 E21951 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1014 517DFC 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1015 CEC6B4 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1016 1A95D5 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1017 5724CC 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1018 7FA5FF 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1019 E43750 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1020 E9C9E1 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1021 CE626A 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1022 541C9C 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1023 F77E4B 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1024 287E3B 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1025 FLOOR 2 WORK_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1026 830326 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1027 EAD1EA 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1028 1C33AD 0 302.86 110.86 9.14 0 3.05 1.83 3.51 0.00 0 No No
1029 52D809 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1030 450AA9 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1031 29E445 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1032 B0FF3A 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1033 9036B9 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1034 5EE606 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1035 3FBBC8 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1036 B5099E 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1037 7A8E3F 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1038 32BAA7 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1039 738F37 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1040 B94E9A 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1041 83658D 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1042 CAC621 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1043 E90253 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1044 FD4C82 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1045 F5C927 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1046 362FF8 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1047 21F419 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1048 283EC6 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1049 C5B569 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1050 D29B01 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1051 FFE9D0 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1052 7A8C4C 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1053 957242 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1054 FLOOR 2 WORK HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1055 F22E15 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1056 49DA28 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1057 8C4550 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1058 6CC177 0 302.86 110.86 9.14 0 3.05 1.83 2.19 0.00 0 No No
1059 9969B3 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1060 4C4C25 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1061 FC3B6D 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1062 FLOOR 2 WORK TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1063 34B8D8 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1064 E74038 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1065 762874 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1066 637F6F 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1067 C6DCD1 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1068 1BDF58 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1069 15A915 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1070 1CC550 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1071 55622A 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1072 5D03DA 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1073 AE5078 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1074 774CCD 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1075 F6FE66 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1076 1DCC9F 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1077 47890C 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1078 F7E82F 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1079 7FDC1A 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1080 F02E9C 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1081 FLOOR 2 X-RAY_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1082 137A14 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
1083 F2515C 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
1084 71A3C4 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
1085 46292D 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
1086 9AC2BE 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
1087 FLOOR 3 DRESSING ROOM ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 1.97 -999.00 0 No No
1088 FLOOR 3 DRESSING ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
1089 5EAFB3 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1090 E0CB0D 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1091 FB63A7 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1092 79D0A5 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1093 212961 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1094 C1AD55 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1095 B75832 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1096 F7D24D 0 473.81 143.75 9.14 0 3.05 1.22 5.01 0.00 0 No No
1097 D6F20A 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1098 FLOOR 3 ELEVATOR HALL ROOF 0 1373.29 114.97 6.10 0 3.05 1.22 5.01 0.00 0 No No
1099 FLOOR 3 ELEVATOR HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1100 C3FB92 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1101 AAD404 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1102 2272E0 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1103 E13FC4 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1104 506DC0 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1105 628387 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1106 FLOOR 3 HUMID ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 2.74 -999.00 0 No No
1107 FLOOR 3 HUMID_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1108 1D53D9 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
1109 FC22D1 0 473.81 143.75 9.14 0 3.05 4.88 2.40 0.00 0 No No
1110 DD2E2D 0 302.86 110.86 9.14 0 3.05 4.88 2.40 0.00 0 No No
1111 C4A89B 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
1112 B840A7 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
1113 FLOOR 3 JANITOR ROOF 0 1373.29 114.97 6.10 0 3.05 4.88 2.40 0.00 0 No No
1114 FLOOR 3 JANITOR_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
1115 C86932 0 0.00 0.00 0.00 0 3.05 0.00 3.33 -999.00 0 No No
1116 B1856A 0 0.00 0.00 0.00 0 3.05 0.00 3.33 -999.00 0 No No
1117 AEA170 0 0.00 0.00 0.00 0 3.05 0.00 3.33 -999.00 0 No No
1118 82303C 0 0.00 0.00 0.00 0 3.05 0.00 3.33 -999.00 0 No No
1119 D10EC7 0 0.00 0.00 0.00 0 3.05 0.00 3.33 -999.00 0 No No
1120 FLOOR 3 LOCKER ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 3.33 -999.00 0 No No
1121 FLOOR 3 LOCKER_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.33 -999.00 0 No No
1122 AA26DE 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1123 68A2D7 0 473.81 143.75 9.14 0 3.05 7.01 8.26 0.26 3 No No
1124 9BA05A 0 473.81 143.75 9.14 0 3.05 7.01 8.26 0.26 2 No No
1125 C639E8 0 473.81 143.75 9.14 0 3.05 7.01 8.26 0.26 2 No No
1126 824F52 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1127 D2E9BA 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1128 D197DA 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1129 7C7BE2 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1130 812B32 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1131 3B5B94 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1132 60F383 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1133 F7BE2F 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1134 B29215 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1135 52FA3B 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1136 FLOOR 3 LOUNGE ROOF 0 1373.29 114.97 6.10 0 3.05 7.01 8.26 0.26 0 No No
1137 FLOOR 3 LOUNGE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1138 6D960C 0 0.00 0.00 0.00 0 3.05 3.66 4.18 0.38 0 No No
1139 9AB92B 0 0.00 0.00 0.00 0 3.05 3.66 4.18 0.38 0 No No
1140 CE3FEF 0 473.81 143.75 9.14 0 3.05 3.66 4.18 0.38 3 No No
1141 A2790A 0 473.81 143.75 9.14 0 3.05 3.66 4.18 0.38 2 No No
1142 E0FD95 0 0.00 0.00 0.00 0 3.05 3.66 4.18 0.38 0 No No
1143 B46F2C 0 0.00 0.00 0.00 0 3.05 3.66 4.18 0.38 0 No No
1144 FLOOR 3 LOUNGE TOILET ROOF 0 1373.29 114.97 6.10 0 3.05 3.66 4.18 0.38 0 No No
1145 FLOOR 3 LOUNGE TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.18 0.38 0 No No
1146 6F0E5D 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.34 0 No No
1147 D67C59 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.34 0 No No
1148 6C68C2 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.34 0 No No
1149 CE618F 0 302.86 143.75 9.14 0 3.05 7.62 5.47 0.34 3 No No
1150 79FCEE 0 302.86 143.75 9.14 0 3.05 7.62 5.47 0.34 2 No No
1151 EDE617 0 302.86 143.75 9.14 0 3.05 7.62 5.47 0.34 2 No No
1152 1DC177 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.34 0 No No
1153 FLOOR 3 MECHANICAL ROOF 0 1373.29 114.97 6.10 0 3.05 7.62 5.47 0.34 0 No No
1154 FLOOR 3 MECHANICAL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.34 0 No No
1155 A11DA8 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1156 BC2C22 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1157 44775D 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1158 CDD69A 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1159 F5E7FE 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1160 4BF787 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1161 98A52C 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1162 6310E5 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1163 2E74E6 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1164 FLOOR 3 MECHANICAL HALL ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 3.27 -999.00 0 No No
1165 FLOOR 3 MECHANICAL HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1166 5FDFAE 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1167 C7B7AA 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1168 B972D4 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1169 5ADC59 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 3 No No
1170 C61F0D 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1171 7248C5 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1172 29FA28 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1173 F0B23F 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1174 EEC10E 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1175 944FCE 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1176 C41399 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1177 7DCAF1 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1178 CBFB94 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1179 A5FC87 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1180 A72B2F 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1181 538FE6 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1182 8A695C 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1183 45A523 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1184 F94215 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1185 C27BD7 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1186 AE8664 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1187 535D54 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1188 FLOOR 3 OFFICE ROOF 0 1373.29 114.97 6.10 0 3.05 22.56 14.81 0.28 0 No No
1189 FLOOR 3 OFFICE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1190 CC8990 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1191 D4F411 0 302.86 110.86 9.14 0 3.05 1.83 3.51 0.00 0 No No
1192 2F3F2A 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1193 869ED5 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1194 D75504 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1195 E80026 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1196 A03B2E 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1197 133349 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1198 7DCD8A 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1199 D7E6B2 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1200 8646EF 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1201 840387 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1202 14A82B 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1203 FLOOR 3 OFFICE HALL ROOF 0 1373.29 114.97 6.10 0 3.05 1.83 3.51 0.00 0 No No
1204 FLOOR 3 OFFICE HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1205 460DA4 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1206 8316C5 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1207 D5E94D 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1208 B35AD6 0 302.86 110.86 9.14 0 3.05 1.83 2.19 0.00 0 No No
1209 D0C6E8 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1210 F07866 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1211 FLOOR 3 OFFICE TOILET ROOF 0 1373.29 114.97 6.10 0 3.05 1.83 2.19 0.00 0 No No
1212 FLOOR 3 OFFICE TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1213 D22917 0 302.86 143.75 9.14 0 3.05 25.91 9.32 0.38 4 No No
1214 95BA33 0 302.86 143.75 9.14 0 3.05 25.91 9.32 0.38 1 No No
1215 F27282 0 302.86 143.75 9.14 0 3.05 25.91 9.32 0.38 1 No No
1216 4497EF 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1217 C1BC97 0 473.81 134.43 9.14 0 3.05 25.91 9.32 0.38 4 No No
1218 3DB407 0 473.81 134.43 9.14 0 3.05 25.91 9.32 0.38 1 No No
1219 3DADE2 0 473.81 134.43 9.14 0 3.05 25.91 9.32 0.38 1 No No
1220 DF3E2C 0 473.81 134.43 9.14 0 3.05 25.91 9.32 0.38 1 No No
1221 5031C8 0 473.81 134.43 9.14 0 3.05 25.91 9.32 0.38 1 No No
1222 F3F6EA 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1223 BCAAD1 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1224 E5720F 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1225 8E83C6 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1226 D14D65 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1227 CDCA72 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1228 339B46 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1229 7F8407 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1230 F69079 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1231 A56694 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1232 3C8351 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1233 FLOOR 3 PHYICAL THERAPY 1 ROOF 0 1373.29 114.97 6.10 0 3.05 25.91 9.32 0.38 0 No No
1234 FLOOR 3 PHYSICAL THERAPY 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.38 0 No No
1235 958E3F 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1236 27D999 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1237 55BD05 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1238 8BCB23 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1239 5C690E 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1240 E49C43 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1241 EF4AD1 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1242 8FB568 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1243 C271D9 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1244 1EE332 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1245 96623F 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1246 F17575 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1247 317B1B 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1248 FLOOR 3 PHYSICAL THERAPY 2 ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 6.81 -999.00 0 No No
1249 FLOOR 3 PHYSICAL THERAPY 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1250 44D36C 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1251 CD21EC 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1252 BF7411 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1253 EA4A9E 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1254 484FB1 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1255 FLOOR 3 PHYSICAL THERAPY TOILET ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 2.70 -999.00 0 No No
1256 FLOOR 3 PHYSICAL THERAPY TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1257 D4C22E 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1258 6EC372 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1259 301CE0 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1260 89A685 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1261 137CDB 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1262 FLOOR 3 STORAGE 1 ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 2.74 -999.00 0 No No
1263 FLOOR 3 STORAGE 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1264 FE5F03 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1265 1F37D7 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1266 AC05CF 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1267 C9F74B 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1268 63B825 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1269 FLOOR 3 STORAGE 2 ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 2.70 -999.00 0 No No
1270 FLOOR 3 STORAGE 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1271 C78153 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1272 D13E00 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1273 2451B7 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1274 624E8A 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1275 D6005B 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1276 2B4713 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1277 25A972 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1278 496A6C 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1279 FLOOR 3 TREATMENT ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 6.05 -999.00 0 No No
1280 FLOOR 3 TREATMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1281 C050FD 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1282 8DA7DB 0 473.81 134.43 9.14 0 3.05 21.95 14.40 0.38 4 No No
1283 C087D0 0 473.81 134.43 9.14 0 3.05 21.95 14.40 0.38 2 No No
1284 D2CA75 0 473.81 134.43 9.14 0 3.05 21.95 14.40 0.38 2 No No
1285 B0FB49 0 473.81 134.43 9.14 0 3.05 21.95 14.40 0.38 1 No No
1286 F8F69A 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1287 4CCA8D 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1288 2336C8 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1289 38B339 0 302.86 110.86 9.14 0 3.05 21.95 14.40 0.38 3 No No
1290 FE9BC9 0 302.86 110.86 9.14 0 3.05 21.95 14.40 0.38 1 No No
1291 9DF7DE 0 302.86 110.86 9.14 0 3.05 21.95 14.40 0.38 1 No No
1292 D0BE44 0 302.86 110.86 9.14 0 3.05 21.95 14.40 0.38 2 No No
1293 F4E5F5 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1294 AA7BE2 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1295 68EB71 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1296 66FE82 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1297 948D7B 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1298 236CCE 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1299 AE769E 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1300 FLOOR 3 UNDEVELOPED 1 ROOF 0 1373.29 114.97 6.10 0 3.05 21.95 14.40 0.38 0 No No
1301 FLOOR 3 UNDEVELOPED 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1302 BE5F2F 0 302.86 110.86 9.14 0 3.05 17.07 9.24 0.26 3 No No
1303 6B5226 0 302.86 110.86 9.14 0 3.05 17.07 9.24 0.26 2 No No
1304 D5C4E5 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1305 C1B522 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1306 1DEE26 0 473.81 134.43 9.14 0 3.05 17.07 9.24 0.26 3 No No
1307 8F59F7 0 473.81 134.43 9.14 0 3.05 17.07 9.24 0.26 2 No No
1308 44F571 0 473.81 134.43 9.14 0 3.05 17.07 9.24 0.26 2 No No
1309 192E17 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1310 855B07 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1311 9D1FA7 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1312 6F1456 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1313 CDCFEE 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1314 FLOOR 3 UNDEVELOPED 2 ROOF 0 1373.29 114.97 6.10 0 3.05 17.07 9.24 0.26 0 No No
1315 FLOOR 3 UNDEVELOPED 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1316 111907 0 0.00 0.00 0.00 0 3.05 0.00 4.39 -999.00 0 No No
1317 CF2803 0 0.00 0.00 0.00 0 3.05 0.00 4.39 -999.00 0 No No
1318 180143 0 0.00 0.00 0.00 0 3.05 0.00 4.39 -999.00 0 No No
1319 2BC70D 0 0.00 0.00 0.00 0 3.05 0.00 4.39 -999.00 0 No No
1320 DF5076 0 0.00 0.00 0.00 0 3.05 0.00 4.39 -999.00 0 No No
1321 FLOOR 3 UTILITY ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 4.39 -999.00 0 No No
1322 FLOOR 3 UTILITY_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.39 -999.00 0 No No
1323 3613B7 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.31 0 No No
1324 C86329 0 302.86 143.75 9.14 0 3.05 12.50 6.36 0.31 3 No No
1325 6BD844 0 302.86 143.75 9.14 0 3.05 12.50 6.36 0.31 2 No No
1326 86D536 0 302.86 143.75 9.14 0 3.05 12.50 6.36 0.31 2 No No
1327 BAF71D 0 302.86 143.75 9.14 0 3.05 12.50 6.36 0.31 2 No No
1328 3833A2 0 302.86 143.75 9.14 0 3.05 12.50 6.36 0.31 2 No No
1329 E7A265 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.31 0 No No
1330 4C6DBF 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.31 0 No No
1331 EFFB3B 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.31 0 No No
1332 8480E5 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.31 0 No No
1333 F6DDE6 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.31 0 No No
1334 FLOOR 3 WORK ROOF 0 1373.29 114.97 6.10 0 3.05 12.50 6.36 0.31 0 No No
1335 FLOOR 3 WORK_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.31 0 No No
1336 986A05 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.13 0 No No
1337 DFC6F0 0 302.86 143.75 9.14 0 9.14 10.67 3.30 0.13 4 No No
1338 2111A1 0 302.86 143.75 9.14 0 9.14 10.67 3.30 0.13 1 No No
1339 6EE166 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.13 0 No No
1340 A28F01 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.13 0 No No
1341 DE6295 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.13 0 No No
1342 D68874 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.13 0 No No
1343 88E360 0 473.81 143.75 9.14 0 9.14 10.67 3.30 0.13 3 No No
1344 9CB8E5 0 473.81 143.75 9.14 0 9.14 10.67 3.30 0.13 0 No No
1345 9BC521 0 473.81 143.75 9.14 0 9.14 10.67 3.30 0.13 2 No No
1346 142781 0 473.81 143.75 9.14 0 9.14 10.67 3.30 0.13 2 No No
1347 E4A528 0 473.81 143.75 9.14 0 9.14 10.67 3.30 0.13 0 No No
1348 16BE00 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.13 0 No No
1349 60F634 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.13 0 No No
1350 E7B55F 0 473.81 134.43 9.14 0 9.14 10.67 3.30 0.13 4 No No
1351 EEFDE3 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.13 0 No No
1352 NE STAIR SLAB 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.13 0 No No
1353 NE STAIR ROOF 0 1373.29 114.97 6.10 0 9.14 10.67 3.30 0.13 0 No No
1354 NE STAIR_INTERNALMASS_1 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.13 0 No No
1355 FB3814 0 473.81 134.43 9.14 0 9.14 8.23 3.16 0.00 0 No No
1356 24BAF7 0 473.81 134.43 9.14 0 9.14 8.23 3.16 0.00 0 No No
1357 976E3F 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1358 FCD12D 0 302.86 110.86 9.14 0 9.14 8.23 3.16 0.00 0 No No
1359 19E57D 0 302.86 110.86 9.14 0 9.14 8.23 3.16 0.00 0 No No
1360 D699FF 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1361 F9DFA4 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1362 BDE9D9 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1363 BEDECA 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1364 9BA592 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1365 NW ELEVATOR SLAB 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1366 NW ELEVATOR ROOF 0 1373.29 114.97 6.10 0 9.14 8.23 3.16 0.00 0 No No
1367 NW ELEVATOR_INTERNALMASS_1 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1368 5507DC 0 302.86 110.86 9.14 0 9.14 12.19 3.66 1.00E-001 3 No No
1369 EDE769 0 302.86 110.86 9.14 0 9.14 12.19 3.66 1.00E-001 0 No No
1370 2E2D0C 0 473.81 143.75 9.14 0 9.14 12.19 3.66 1.00E-001 3 No No
1371 E74902 0 473.81 143.75 9.14 0 9.14 12.19 3.66 1.00E-001 2 No No
1372 93BBC3 0 473.81 143.75 9.14 0 9.14 12.19 3.66 1.00E-001 2 No No
1373 1C9872 0 473.81 143.75 9.14 0 9.14 12.19 3.66 1.00E-001 0 No No
1374 FA9233 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1375 AF0124 0 302.86 143.75 9.14 0 9.14 12.19 3.66 1.00E-001 3 No No
1376 74AB49 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1377 DF47AC 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1378 F41621 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1379 7C0F83 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1380 NW STAIR SLAB 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1381 NW STAIR ROOF 0 1373.29 114.97 6.10 0 9.14 12.19 3.66 1.00E-001 0 No No
1382 NW STAIR_INTERNALMASS_1 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1383 8FF821 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1384 850EA7 0 473.81 134.43 9.14 0 9.14 6.10 2.93 2.00E-002 4 No No
1385 C635A6 0 473.81 134.43 9.14 0 9.14 6.10 2.93 2.00E-002 1 No No
1386 1068C8 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1387 E2AFEB 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1388 99468F 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1389 17258E 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1390 573330 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1391 270BCE 0 302.86 110.86 9.14 0 9.14 6.10 2.93 2.00E-002 4 No No
1392 F402E9 0 302.86 110.86 9.14 0 9.14 6.10 2.93 2.00E-002 0 No No
1393 SW STAIR SLAB 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1394 SW STAIR ROOF 0 1373.29 114.97 6.10 0 9.14 6.10 2.93 2.00E-002 0 No No
1395 SW STAIR_INTERNALMASS_1 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 FLOOR 1 ANESTHESIA_INFILTRATION INFIL_SCH FLOOR 1 ANESTHESIA 10.03 2.2 4.762E-003 4.746E-004 5.696E-004 0.561 0.000 0.000 0.224 0.000
2 FLOOR 1 CAFE_INFILTRATION INFIL_SCH FLOOR 1 CAFE 39.02 42.0 1.058E-002 2.712E-004 5.696E-004 0.320 0.000 0.000 0.224 0.000
3 FLOOR 1 DRESSING ROOM_INFILTRATION INFIL_SCH FLOOR 1 DRESSING ROOM 4.18 0.2 4.762E-003 1.139E-003 5.696E-004 1.345 0.000 0.000 0.224 0.000
4 FLOOR 1 ELECTRICAL ROOM_INFILTRATION INFIL_SCH FLOOR 1 ELECTRICAL ROOM 9.10 0.1 3.704E-003 4.068E-004 5.696E-004 0.481 0.000 0.000 0.224 0.000
5 FLOOR 1 ELEVATOR PUMP ROOM_INFILTRATION INFIL_SCH FLOOR 1 ELEVATOR PUMP ROOM 8.45 0.1 1.058E-002 1.252E-003 5.155E-004 1.479 0.000 0.000 0.224 0.000
6 FLOOR 1 LOBBY_INFILTRATION INFIL_SCH FLOOR 1 LOBBY 57.79 6.2 1.164E-002 2.015E-004 5.199E-004 0.238 0.000 0.000 0.224 0.000
7 FLOOR 1 LOBBY TOILET_INFILTRATION INFIL_SCH FLOOR 1 LOBBY TOILET 5.02 0.3 3.175E-003 6.329E-004 5.696E-004 0.747 0.000 0.000 0.224 0.000
8 FLOOR 1 LOCKER ROOM_INFILTRATION INFIL_SCH FLOOR 1 LOCKER ROOM 61.32 9.9 1.164E-002 1.899E-004 5.696E-004 0.224 0.000 0.000 0.224 0.000
9 FLOOR 1 MED GAS_INFILTRATION INFIL_SCH FLOOR 1 MED GAS 5.20 0.1 7.937E-003 1.526E-003 3.764E-004 1.802 0.000 0.000 0.224 0.000
10 FLOOR 1 MRI TOILET_INFILTRATION INFIL_SCH FLOOR 1 MRI TOILET 5.02 0.3 3.175E-003 6.329E-004 5.696E-004 0.747 0.000 0.000 0.224 0.000
11 FLOOR 1 OPERATING ROOM 1_INFILTRATION INFIL_SCH FLOOR 1 OPERATING ROOM 1 42.74 9.2 2.275E-002 5.324E-004 5.431E-004 0.629 0.000 0.000 0.224 0.000
12 FLOOR 1 OPERATING ROOM 2_INFILTRATION INFIL_SCH FLOOR 1 OPERATING ROOM 2 44.59 9.6 1.270E-002 2.848E-004 5.696E-004 0.336 0.000 0.000 0.224 0.000
13 FLOOR 1 PRE-OP ROOM 1_INFILTRATION INFIL_SCH FLOOR 1 PRE-OP ROOM 1 17.56 1.9 2.117E-003 1.205E-004 5.696E-004 0.142 0.000 0.000 0.224 0.000
14 FLOOR 1 PRE-OP TOILET_INFILTRATION INFIL_SCH FLOOR 1 PRE-OP TOILET 5.02 0.3 3.175E-003 6.329E-004 5.696E-004 0.747 0.000 0.000 0.224 0.000
15 FLOOR 1 PROCEDURE ROOM_INFILTRATION INFIL_SCH FLOOR 1 PROCEDURE ROOM 26.48 5.7 1.005E-002 3.797E-004 5.696E-004 0.448 0.000 0.000 0.224 0.000
16 FLOOR 1 RECEPTION_INFILTRATION INFIL_SCH FLOOR 1 RECEPTION 47.29 15.3 6.879E-003 1.455E-004 5.696E-004 0.172 0.000 0.000 0.224 0.000
17 FLOOR 1 RECOVERY ROOM_INFILTRATION INFIL_SCH FLOOR 1 RECOVERY ROOM 50.17 10.8 2.381E-002 4.746E-004 4.996E-004 0.561 0.000 0.000 0.224 0.000
18 FLOOR 1 SCHEDULING_INFILTRATION INFIL_SCH FLOOR 1 SCHEDULING 11.06 0.6 3.704E-003 3.350E-004 5.696E-004 0.396 0.000 0.000 0.224 0.000
19 FLOOR 1 STEP DOWN_INFILTRATION INFIL_SCH FLOOR 1 STEP DOWN 27.87 6.0 1.958E-002 7.025E-004 5.390E-004 0.830 0.000 0.000 0.224 0.000
20 FLOOR 1 STORAGE_INFILTRATION INFIL_SCH FLOOR 1 STORAGE 85.47 1.8 3.334E-002 3.900E-004 2.181E-004 0.461 0.000 0.000 0.224 0.000
21 FLOOR 1 SUB-STERILE_INFILTRATION INFIL_SCH FLOOR 1 SUB-STERILE 18.21 1.0 7.408E-003 4.068E-004 5.696E-004 0.481 0.000 0.000 0.224 0.000
22 FLOOR 1 UTILITY HALL_INFILTRATION INFIL_SCH FLOOR 1 UTILITY HALL 23.78 1.3 8.466E-003 3.560E-004 2.476E-004 0.420 0.000 0.000 0.224 0.000
23 FLOOR 1 UTILITY ROOM_INFILTRATION INFIL_SCH FLOOR 1 UTILITY ROOM 33.45 0.7 9.525E-003 2.848E-004 5.101E-004 0.336 0.000 0.000 0.224 0.000
24 FLOOR 1 VESTIBULE_INFILTRATION INFIL_SCH FLOOR 1 VESTIBULE 6.69 0.4 4.233E-003 6.329E-004 4.511E-004 0.747 0.000 0.000 0.224 0.000
25 FLOOR 1 VESTIBULE_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH FLOOR 1 VESTIBULE 6.69 0.4 1.186 0.177 0.126 209.417 1.000 0.000 0.000 0.000
26 FLOOR 2 CONFERENCE_INFILTRATION INFIL_SCH FLOOR 2 CONFERENCE 31.22 16.8 2.117E-002 6.781E-004 5.696E-004 0.801 0.000 0.000 0.224 0.000
27 FLOOR 2 EXAM 1_INFILTRATION INFIL_SCH FLOOR 2 EXAM 1 33.45 7.2 2.222E-002 6.645E-004 5.696E-004 0.785 0.000 0.000 0.224 0.000
28 FLOOR 2 EXAM 2_INFILTRATION INFIL_SCH FLOOR 2 EXAM 2 50.17 10.8 9.525E-003 1.899E-004 5.696E-004 0.224 0.000 0.000 0.224 0.000
29 FLOOR 2 EXAM 3_INFILTRATION INFIL_SCH FLOOR 2 EXAM 3 66.89 14.4 1.270E-002 1.899E-004 5.696E-004 0.224 0.000 0.000 0.224 0.000
30 FLOOR 2 EXAM 4_INFILTRATION INFIL_SCH FLOOR 2 EXAM 4 7.80 1.7 3.704E-003 4.746E-004 5.696E-004 0.561 0.000 0.000 0.224 0.000
31 FLOOR 2 EXAM 5_INFILTRATION INFIL_SCH FLOOR 2 EXAM 5 32.52 7.0 1.323E-002 4.068E-004 5.696E-004 0.481 0.000 0.000 0.224 0.000
32 FLOOR 2 EXAM 6_INFILTRATION INFIL_SCH FLOOR 2 EXAM 6 20.90 4.5 7.937E-003 3.797E-004 5.696E-004 0.448 0.000 0.000 0.224 0.000
33 FLOOR 2 EXAM 7_INFILTRATION INFIL_SCH FLOOR 2 EXAM 7 73.58 15.8 1.270E-002 1.726E-004 5.696E-004 0.204 0.000 0.000 0.224 0.000
34 FLOOR 2 EXAM 8_INFILTRATION INFIL_SCH FLOOR 2 EXAM 8 25.08 5.4 9.525E-003 3.797E-004 5.696E-004 0.448 0.000 0.000 0.224 0.000
35 FLOOR 2 EXAM 9_INFILTRATION INFIL_SCH FLOOR 2 EXAM 9 36.79 7.9 6.350E-003 1.726E-004 5.696E-004 0.204 0.000 0.000 0.224 0.000
36 FLOOR 2 JANITOR_INFILTRATION INFIL_SCH FLOOR 2 JANITOR 5.85 0.1 8.466E-003 1.447E-003 5.696E-004 1.709 0.000 0.000 0.224 0.000
37 FLOOR 2 OFFICE_INFILTRATION INFIL_SCH FLOOR 2 OFFICE 52.03 2.8 2.117E-002 4.068E-004 5.696E-004 0.481 0.000 0.000 0.224 0.000
38 FLOOR 2 RECEPTION_INFILTRATION INFIL_SCH FLOOR 2 RECEPTION 91.42 29.5 2.593E-002 2.836E-004 5.696E-004 0.335 0.000 0.000 0.224 0.000
39 FLOOR 2 UTILITY_INFILTRATION INFIL_SCH FLOOR 2 UTILITY 11.71 0.3 4.762E-003 4.068E-004 5.696E-004 0.481 0.000 0.000 0.224 0.000
40 FLOOR 2 WORK_INFILTRATION INFIL_SCH FLOOR 2 WORK 157.01 8.5 1.376E-002 8.763E-005 5.696E-004 0.103 0.000 0.000 0.224 0.000
41 FLOOR 2 WORK TOILET_INFILTRATION INFIL_SCH FLOOR 2 WORK TOILET 5.02 0.3 3.175E-003 6.329E-004 5.696E-004 0.747 0.000 0.000 0.224 0.000
42 FLOOR 3 ELEVATOR HALL_INFILTRATION INFIL_SCH FLOOR 3 ELEVATOR HALL 34.37 1.9 2.117E-003 6.158E-005 5.557E-005 7.273E-002 0.000 0.000 0.224 0.000
43 FLOOR 3 JANITOR_INFILTRATION INFIL_SCH FLOOR 3 JANITOR 5.85 0.1 8.466E-003 1.447E-003 4.087E-004 1.709 0.000 0.000 0.224 0.000
44 FLOOR 3 LOUNGE_INFILTRATION INFIL_SCH FLOOR 3 LOUNGE 70.51 11.4 1.217E-002 1.726E-004 1.325E-004 0.204 0.000 0.000 0.224 0.000
45 FLOOR 3 LOUNGE TOILET_INFILTRATION INFIL_SCH FLOOR 3 LOUNGE TOILET 17.84 1.0 6.350E-003 3.560E-004 2.191E-004 0.420 0.000 0.000 0.224 0.000
46 FLOOR 3 MECHANICAL_INFILTRATION INFIL_SCH FLOOR 3 MECHANICAL 32.52 0.5 1.323E-002 4.068E-004 2.373E-004 0.481 0.000 0.000 0.224 0.000
47 FLOOR 3 OFFICE_INFILTRATION INFIL_SCH FLOOR 3 OFFICE 282.05 15.2 3.916E-002 1.388E-004 1.116E-004 0.164 0.000 0.000 0.224 0.000
48 FLOOR 3 OFFICE HALL_INFILTRATION INFIL_SCH FLOOR 3 OFFICE HALL 77.48 4.2 3.175E-003 4.098E-005 3.823E-005 4.840E-002 0.000 0.000 0.224 0.000
49 FLOOR 3 OFFICE TOILET_INFILTRATION INFIL_SCH FLOOR 3 OFFICE TOILET 5.02 0.3 3.175E-003 6.329E-004 2.998E-004 0.747 0.000 0.000 0.224 0.000
50 FLOOR 3 PHYSICAL THERAPY 1_INFILTRATION INFIL_SCH FLOOR 3 PHYSICAL THERAPY 1 120.77 26.0 4.498E-002 3.724E-004 2.252E-004 0.440 0.000 0.000 0.224 0.000
51 FLOOR 3 UNDEVELOPED 1_INFILTRATION INFIL_SCH FLOOR 3 UNDEVELOPED 1 210.70 4.5 3.810E-002 1.808E-004 1.372E-004 0.214 0.000 0.000 0.224 0.000
52 FLOOR 3 UNDEVELOPED 2_INFILTRATION INFIL_SCH FLOOR 3 UNDEVELOPED 2 107.02 2.3 2.963E-002 2.769E-004 1.863E-004 0.327 0.000 0.000 0.224 0.000
53 FLOOR 3 WORK_INFILTRATION INFIL_SCH FLOOR 3 WORK 53.33 2.9 2.170E-002 4.068E-004 2.373E-004 0.481 0.000 0.000 0.224 0.000
54 NE STAIR_INFILTRATION INFIL_SCH NE STAIR 15.61 0.8 5.556E-002 3.560E-003 4.746E-004 1.402 0.000 0.000 0.224 0.000
55 NW ELEVATOR_INFILTRATION INFIL_SCH NW ELEVATOR 13.01 0.2 4.286E-002 3.295E-003 4.651E-004 1.297 0.000 0.000 0.224 0.000
56 NW STAIR_INFILTRATION INFIL_SCH NW STAIR 17.84 1.0 6.350E-002 3.560E-003 4.766E-004 1.402 0.000 0.000 0.224 0.000
57 SW STAIR_INFILTRATION INFIL_SCH SW STAIR 8.92 0.5 3.175E-002 3.560E-003 4.766E-004 1.402 0.000 0.000 0.224 0.000
58 FLOOR 3 DRESSING ROOM_INFILTRATION INFIL_SCH FLOOR 3 DRESSING ROOM 3.90 0.2 0.000 0.000 0.000 0.000 0.000 0.000 0.224 0.000
59 FLOOR 3 HUMID_INFILTRATION INFIL_SCH FLOOR 3 HUMID 10.03 0.5 0.000 0.000 0.000 0.000 0.000 0.000 0.224 0.000
60 FLOOR 3 LOCKER_INFILTRATION INFIL_SCH FLOOR 3 LOCKER 11.15 1.8 0.000 0.000 0.000 0.000 0.000 0.000 0.224 0.000
61 FLOOR 3 MECHANICAL HALL_INFILTRATION INFIL_SCH FLOOR 3 MECHANICAL HALL 27.87 1.5 0.000 0.000 0.000 0.000 0.000 0.000 0.224 0.000
62 FLOOR 3 PHYSICAL THERAPY 2_INFILTRATION INFIL_SCH FLOOR 3 PHYSICAL THERAPY 2 55.00 11.8 0.000 0.000 0.000 0.000 0.000 0.000 0.224 0.000
63 FLOOR 3 PHYSICAL THERAPY TOILET_INFILTRATION INFIL_SCH FLOOR 3 PHYSICAL THERAPY TOILET 7.80 0.4 0.000 0.000 0.000 0.000 0.000 0.000 0.224 0.000
64 FLOOR 3 STORAGE 1_INFILTRATION INFIL_SCH FLOOR 3 STORAGE 1 10.03 0.2 0.000 0.000 0.000 0.000 0.000 0.000 0.224 0.000
65 FLOOR 3 STORAGE 2_INFILTRATION INFIL_SCH FLOOR 3 STORAGE 2 7.80 0.2 0.000 0.000 0.000 0.000 0.000 0.000 0.224 0.000
66 FLOOR 3 TREATMENT_INFILTRATION INFIL_SCH FLOOR 3 TREATMENT 44.22 9.5 0.000 0.000 0.000 0.000 0.000 0.000 0.224 0.000
67 FLOOR 3 UTILITY_INFILTRATION INFIL_SCH FLOOR 3 UTILITY 20.07 0.4 0.000 0.000 0.000 0.000 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 FLOOR 1 ANESTHESIA Mixing/Well-Stirred
2 FLOOR 1 BIO HAZ Mixing/Well-Stirred
3 FLOOR 1 CAFE Mixing/Well-Stirred
4 FLOOR 1 CLEAN Mixing/Well-Stirred
5 FLOOR 1 CLEAN WORK Mixing/Well-Stirred
6 FLOOR 1 DICTATION Mixing/Well-Stirred
7 FLOOR 1 DRESSING ROOM Mixing/Well-Stirred
8 FLOOR 1 ELECTRICAL ROOM Mixing/Well-Stirred
9 FLOOR 1 ELEVATOR PUMP ROOM Mixing/Well-Stirred
10 FLOOR 1 HUMID Mixing/Well-Stirred
11 FLOOR 1 IT HALL Mixing/Well-Stirred
12 FLOOR 1 IT ROOM Mixing/Well-Stirred
13 FLOOR 1 LOBBY Mixing/Well-Stirred
14 FLOOR 1 LOBBY HALL Mixing/Well-Stirred
15 FLOOR 1 LOBBY TOILET Mixing/Well-Stirred
16 FLOOR 1 LOCKER ROOM Mixing/Well-Stirred
17 FLOOR 1 LOCKER ROOM HALL Mixing/Well-Stirred
18 FLOOR 1 LOUNGE Mixing/Well-Stirred
19 FLOOR 1 MED GAS Mixing/Well-Stirred
20 FLOOR 1 MRI CONTROL ROOM Mixing/Well-Stirred
21 FLOOR 1 MRI HALL Mixing/Well-Stirred
22 FLOOR 1 MRI ROOM Mixing/Well-Stirred
23 FLOOR 1 MRI TOILET Mixing/Well-Stirred
24 FLOOR 1 NOURISHMENT Mixing/Well-Stirred
25 FLOOR 1 NURSE HALL Mixing/Well-Stirred
26 FLOOR 1 NURSE JANITOR Mixing/Well-Stirred
27 FLOOR 1 NURSE STATION Mixing/Well-Stirred
28 FLOOR 1 NURSE TOILET Mixing/Well-Stirred
29 FLOOR 1 OFFICE Mixing/Well-Stirred
30 FLOOR 1 OPERATING ROOM 1 Mixing/Well-Stirred
31 FLOOR 1 OPERATING ROOM 2 Mixing/Well-Stirred
32 FLOOR 1 OPERATING ROOM 3 Mixing/Well-Stirred
33 FLOOR 1 PACU Mixing/Well-Stirred
34 FLOOR 1 PRE-OP HALL Mixing/Well-Stirred
35 FLOOR 1 PRE-OP ROOM 1 Mixing/Well-Stirred
36 FLOOR 1 PRE-OP ROOM 2 Mixing/Well-Stirred
37 FLOOR 1 PRE-OP TOILET Mixing/Well-Stirred
38 FLOOR 1 PROCEDURE ROOM Mixing/Well-Stirred
39 FLOOR 1 RECEPTION Mixing/Well-Stirred
40 FLOOR 1 RECEPTION HALL Mixing/Well-Stirred
41 FLOOR 1 RECOVERY ROOM Mixing/Well-Stirred
42 FLOOR 1 SCHEDULING Mixing/Well-Stirred
43 FLOOR 1 SCRUB Mixing/Well-Stirred
44 FLOOR 1 SOIL Mixing/Well-Stirred
45 FLOOR 1 SOIL HOLD Mixing/Well-Stirred
46 FLOOR 1 SOIL WORK Mixing/Well-Stirred
47 FLOOR 1 STEP DOWN Mixing/Well-Stirred
48 FLOOR 1 STERILE HALL Mixing/Well-Stirred
49 FLOOR 1 STERILE STORAGE Mixing/Well-Stirred
50 FLOOR 1 STORAGE Mixing/Well-Stirred
51 FLOOR 1 SUB-STERILE Mixing/Well-Stirred
52 FLOOR 1 UTILITY HALL Mixing/Well-Stirred
53 FLOOR 1 UTILITY JANITOR Mixing/Well-Stirred
54 FLOOR 1 UTILITY ROOM Mixing/Well-Stirred
55 FLOOR 1 VESTIBULE Mixing/Well-Stirred
56 FLOOR 2 CONFERENCE Mixing/Well-Stirred
57 FLOOR 2 CONFERENCE TOILET Mixing/Well-Stirred
58 FLOOR 2 DICTATION Mixing/Well-Stirred
59 FLOOR 2 EXAM 1 Mixing/Well-Stirred
60 FLOOR 2 EXAM 2 Mixing/Well-Stirred
61 FLOOR 2 EXAM 3 Mixing/Well-Stirred
62 FLOOR 2 EXAM 4 Mixing/Well-Stirred
63 FLOOR 2 EXAM 5 Mixing/Well-Stirred
64 FLOOR 2 EXAM 6 Mixing/Well-Stirred
65 FLOOR 2 EXAM 7 Mixing/Well-Stirred
66 FLOOR 2 EXAM 8 Mixing/Well-Stirred
67 FLOOR 2 EXAM 9 Mixing/Well-Stirred
68 FLOOR 2 EXAM HALL 1 Mixing/Well-Stirred
69 FLOOR 2 EXAM HALL 2 Mixing/Well-Stirred
70 FLOOR 2 EXAM HALL 3 Mixing/Well-Stirred
71 FLOOR 2 EXAM HALL 4 Mixing/Well-Stirred
72 FLOOR 2 EXAM HALL 5 Mixing/Well-Stirred
73 FLOOR 2 EXAM HALL 6 Mixing/Well-Stirred
74 FLOOR 2 JANITOR Mixing/Well-Stirred
75 FLOOR 2 LOUNGE Mixing/Well-Stirred
76 FLOOR 2 NURSE STATION 1 Mixing/Well-Stirred
77 FLOOR 2 NURSE STATION 2 Mixing/Well-Stirred
78 FLOOR 2 OFFICE Mixing/Well-Stirred
79 FLOOR 2 OFFICE HALL Mixing/Well-Stirred
80 FLOOR 2 RECEPTION Mixing/Well-Stirred
81 FLOOR 2 RECEPTION HALL Mixing/Well-Stirred
82 FLOOR 2 RECEPTION TOILET Mixing/Well-Stirred
83 FLOOR 2 SCHEDULING 1 Mixing/Well-Stirred
84 FLOOR 2 SCHEDULING 2 Mixing/Well-Stirred
85 FLOOR 2 STORAGE 1 Mixing/Well-Stirred
86 FLOOR 2 STORAGE 2 Mixing/Well-Stirred
87 FLOOR 2 STORAGE 3 Mixing/Well-Stirred
88 FLOOR 2 UTILITY Mixing/Well-Stirred
89 FLOOR 2 WORK Mixing/Well-Stirred
90 FLOOR 2 WORK HALL Mixing/Well-Stirred
91 FLOOR 2 WORK TOILET Mixing/Well-Stirred
92 FLOOR 2 X-RAY Mixing/Well-Stirred
93 FLOOR 3 DRESSING ROOM Mixing/Well-Stirred
94 FLOOR 3 ELEVATOR HALL Mixing/Well-Stirred
95 FLOOR 3 HUMID Mixing/Well-Stirred
96 FLOOR 3 JANITOR Mixing/Well-Stirred
97 FLOOR 3 LOCKER Mixing/Well-Stirred
98 FLOOR 3 LOUNGE Mixing/Well-Stirred
99 FLOOR 3 LOUNGE TOILET Mixing/Well-Stirred
100 FLOOR 3 MECHANICAL Mixing/Well-Stirred
101 FLOOR 3 MECHANICAL HALL Mixing/Well-Stirred
102 FLOOR 3 OFFICE Mixing/Well-Stirred
103 FLOOR 3 OFFICE HALL Mixing/Well-Stirred
104 FLOOR 3 OFFICE TOILET Mixing/Well-Stirred
105 FLOOR 3 PHYSICAL THERAPY 1 Mixing/Well-Stirred
106 FLOOR 3 PHYSICAL THERAPY 2 Mixing/Well-Stirred
107 FLOOR 3 PHYSICAL THERAPY TOILET Mixing/Well-Stirred
108 FLOOR 3 STORAGE 1 Mixing/Well-Stirred
109 FLOOR 3 STORAGE 2 Mixing/Well-Stirred
110 FLOOR 3 TREATMENT Mixing/Well-Stirred
111 FLOOR 3 UNDEVELOPED 1 Mixing/Well-Stirred
112 FLOOR 3 UNDEVELOPED 2 Mixing/Well-Stirred
113 FLOOR 3 UTILITY Mixing/Well-Stirred
114 FLOOR 3 WORK Mixing/Well-Stirred
115 NE STAIR Mixing/Well-Stirred
116 NW ELEVATOR Mixing/Well-Stirred
117 NW STAIR Mixing/Well-Stirred
118 SW STAIR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2500
2 Zone FLOOR 1 ANESTHESIA 1.2500
3 Zone FLOOR 1 BIO HAZ 1.2500
4 Zone FLOOR 1 CAFE 1.2500
5 Zone FLOOR 1 CLEAN 1.2500
6 Zone FLOOR 1 CLEAN WORK 1.2500
7 Zone FLOOR 1 DICTATION 1.2500
8 Zone FLOOR 1 DRESSING ROOM 1.2500
9 Zone FLOOR 1 ELECTRICAL ROOM 1.2500
10 Zone FLOOR 1 ELEVATOR PUMP ROOM 1.2500
11 Zone FLOOR 1 HUMID 1.2500
12 Zone FLOOR 1 IT HALL 1.2500
13 Zone FLOOR 1 IT ROOM 1.2500
14 Zone FLOOR 1 LOBBY 1.2500
15 Zone FLOOR 1 LOBBY HALL 1.2500
16 Zone FLOOR 1 LOBBY TOILET 1.2500
17 Zone FLOOR 1 LOCKER ROOM 1.2500
18 Zone FLOOR 1 LOCKER ROOM HALL 1.2500
19 Zone FLOOR 1 LOUNGE 1.2500
20 Zone FLOOR 1 MED GAS 1.2500
21 Zone FLOOR 1 MRI CONTROL ROOM 1.2500
22 Zone FLOOR 1 MRI HALL 1.2500
23 Zone FLOOR 1 MRI ROOM 1.2500
24 Zone FLOOR 1 MRI TOILET 1.2500
25 Zone FLOOR 1 NOURISHMENT 1.2500
26 Zone FLOOR 1 NURSE HALL 1.2500
27 Zone FLOOR 1 NURSE JANITOR 1.2500
28 Zone FLOOR 1 NURSE STATION 1.2500
29 Zone FLOOR 1 NURSE TOILET 1.2500
30 Zone FLOOR 1 OFFICE 1.2500
31 Zone FLOOR 1 OPERATING ROOM 1 1.2500
32 Zone FLOOR 1 OPERATING ROOM 2 1.2500
33 Zone FLOOR 1 OPERATING ROOM 3 1.2500
34 Zone FLOOR 1 PACU 1.2500
35 Zone FLOOR 1 PRE-OP HALL 1.2500
36 Zone FLOOR 1 PRE-OP ROOM 1 1.2500
37 Zone FLOOR 1 PRE-OP ROOM 2 1.2500
38 Zone FLOOR 1 PRE-OP TOILET 1.2500
39 Zone FLOOR 1 PROCEDURE ROOM 1.2500
40 Zone FLOOR 1 RECEPTION 1.2500
41 Zone FLOOR 1 RECEPTION HALL 1.2500
42 Zone FLOOR 1 RECOVERY ROOM 1.2500
43 Zone FLOOR 1 SCHEDULING 1.2500
44 Zone FLOOR 1 SCRUB 1.2500
45 Zone FLOOR 1 SOIL 1.2500
46 Zone FLOOR 1 SOIL HOLD 1.2500
47 Zone FLOOR 1 SOIL WORK 1.2500
48 Zone FLOOR 1 STEP DOWN 1.2500
49 Zone FLOOR 1 STERILE HALL 1.2500
50 Zone FLOOR 1 STERILE STORAGE 1.2500
51 Zone FLOOR 1 STORAGE 1.2500
52 Zone FLOOR 1 SUB-STERILE 1.2500
53 Zone FLOOR 1 UTILITY HALL 1.2500
54 Zone FLOOR 1 UTILITY JANITOR 1.2500
55 Zone FLOOR 1 UTILITY ROOM 1.2500
56 Zone FLOOR 1 VESTIBULE 1.2500
57 Zone FLOOR 2 CONFERENCE 1.2500
58 Zone FLOOR 2 CONFERENCE TOILET 1.2500
59 Zone FLOOR 2 DICTATION 1.2500
60 Zone FLOOR 2 EXAM 1 1.2500
61 Zone FLOOR 2 EXAM 2 1.2500
62 Zone FLOOR 2 EXAM 3 1.2500
63 Zone FLOOR 2 EXAM 4 1.2500
64 Zone FLOOR 2 EXAM 5 1.2500
65 Zone FLOOR 2 EXAM 6 1.2500
66 Zone FLOOR 2 EXAM 7 1.2500
67 Zone FLOOR 2 EXAM 8 1.2500
68 Zone FLOOR 2 EXAM 9 1.2500
69 Zone FLOOR 2 EXAM HALL 1 1.2500
70 Zone FLOOR 2 EXAM HALL 2 1.2500
71 Zone FLOOR 2 EXAM HALL 3 1.2500
72 Zone FLOOR 2 EXAM HALL 4 1.2500
73 Zone FLOOR 2 EXAM HALL 5 1.2500
74 Zone FLOOR 2 EXAM HALL 6 1.2500
75 Zone FLOOR 2 JANITOR 1.2500
76 Zone FLOOR 2 LOUNGE 1.2500
77 Zone FLOOR 2 NURSE STATION 1 1.2500
78 Zone FLOOR 2 NURSE STATION 2 1.2500
79 Zone FLOOR 2 OFFICE 1.2500
80 Zone FLOOR 2 OFFICE HALL 1.2500
81 Zone FLOOR 2 RECEPTION 1.2500
82 Zone FLOOR 2 RECEPTION HALL 1.2500
83 Zone FLOOR 2 RECEPTION TOILET 1.2500
84 Zone FLOOR 2 SCHEDULING 1 1.2500
85 Zone FLOOR 2 SCHEDULING 2 1.2500
86 Zone FLOOR 2 STORAGE 1 1.2500
87 Zone FLOOR 2 STORAGE 2 1.2500
88 Zone FLOOR 2 STORAGE 3 1.2500
89 Zone FLOOR 2 UTILITY 1.2500
90 Zone FLOOR 2 WORK 1.2500
91 Zone FLOOR 2 WORK HALL 1.2500
92 Zone FLOOR 2 WORK TOILET 1.2500
93 Zone FLOOR 2 X-RAY 1.3500
94 Zone FLOOR 3 DRESSING ROOM 1.2500
95 Zone FLOOR 3 ELEVATOR HALL 1.2500
96 Zone FLOOR 3 HUMID 1.2500
97 Zone FLOOR 3 JANITOR 1.2500
98 Zone FLOOR 3 LOCKER 1.2500
99 Zone FLOOR 3 LOUNGE 1.2500
100 Zone FLOOR 3 LOUNGE TOILET 1.2500
101 Zone FLOOR 3 MECHANICAL 1.2500
102 Zone FLOOR 3 MECHANICAL HALL 1.2500
103 Zone FLOOR 3 OFFICE 1.2500
104 Zone FLOOR 3 OFFICE HALL 1.2500
105 Zone FLOOR 3 OFFICE TOILET 1.2500
106 Zone FLOOR 3 PHYSICAL THERAPY 1 1.2500
107 Zone FLOOR 3 PHYSICAL THERAPY 2 1.2500
108 Zone FLOOR 3 PHYSICAL THERAPY TOILET 1.2500
109 Zone FLOOR 3 STORAGE 1 1.2500
110 Zone FLOOR 3 STORAGE 2 1.2500
111 Zone FLOOR 3 TREATMENT 1.2500
112 Zone FLOOR 3 UNDEVELOPED 1 1.2500
113 Zone FLOOR 3 UNDEVELOPED 2 1.2500
114 Zone FLOOR 3 UTILITY 1.2500
115 Zone FLOOR 3 WORK 1.2500
116 Zone NE STAIR 1.2500
117 Zone NW ELEVATOR 1.2500
118 Zone NW STAIR 1.2500
119 Zone SW STAIR 1.2500


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.1500
2 Zone FLOOR 1 ANESTHESIA 1.1500
3 Zone FLOOR 1 BIO HAZ 1.1500
4 Zone FLOOR 1 CAFE 1.1500
5 Zone FLOOR 1 CLEAN 1.1500
6 Zone FLOOR 1 CLEAN WORK 1.1500
7 Zone FLOOR 1 DICTATION 1.1500
8 Zone FLOOR 1 DRESSING ROOM 1.1500
9 Zone FLOOR 1 ELECTRICAL ROOM 1.1500
10 Zone FLOOR 1 ELEVATOR PUMP ROOM 1.1500
11 Zone FLOOR 1 HUMID 1.1500
12 Zone FLOOR 1 IT HALL 1.1500
13 Zone FLOOR 1 IT ROOM 1.1500
14 Zone FLOOR 1 LOBBY 1.1500
15 Zone FLOOR 1 LOBBY HALL 1.1500
16 Zone FLOOR 1 LOBBY TOILET 1.1500
17 Zone FLOOR 1 LOCKER ROOM 1.1500
18 Zone FLOOR 1 LOCKER ROOM HALL 1.1500
19 Zone FLOOR 1 LOUNGE 1.1500
20 Zone FLOOR 1 MED GAS 1.1500
21 Zone FLOOR 1 MRI CONTROL ROOM 1.1500
22 Zone FLOOR 1 MRI HALL 1.1500
23 Zone FLOOR 1 MRI ROOM 1.1500
24 Zone FLOOR 1 MRI TOILET 1.1500
25 Zone FLOOR 1 NOURISHMENT 1.1500
26 Zone FLOOR 1 NURSE HALL 1.1500
27 Zone FLOOR 1 NURSE JANITOR 1.1500
28 Zone FLOOR 1 NURSE STATION 1.1500
29 Zone FLOOR 1 NURSE TOILET 1.1500
30 Zone FLOOR 1 OFFICE 1.1500
31 Zone FLOOR 1 OPERATING ROOM 1 1.1500
32 Zone FLOOR 1 OPERATING ROOM 2 1.1500
33 Zone FLOOR 1 OPERATING ROOM 3 1.1500
34 Zone FLOOR 1 PACU 1.1500
35 Zone FLOOR 1 PRE-OP HALL 1.1500
36 Zone FLOOR 1 PRE-OP ROOM 1 1.1500
37 Zone FLOOR 1 PRE-OP ROOM 2 1.1500
38 Zone FLOOR 1 PRE-OP TOILET 1.1500
39 Zone FLOOR 1 PROCEDURE ROOM 1.1500
40 Zone FLOOR 1 RECEPTION 1.1500
41 Zone FLOOR 1 RECEPTION HALL 1.1500
42 Zone FLOOR 1 RECOVERY ROOM 1.1500
43 Zone FLOOR 1 SCHEDULING 1.1500
44 Zone FLOOR 1 SCRUB 1.1500
45 Zone FLOOR 1 SOIL 1.1500
46 Zone FLOOR 1 SOIL HOLD 1.1500
47 Zone FLOOR 1 SOIL WORK 1.1500
48 Zone FLOOR 1 STEP DOWN 1.1500
49 Zone FLOOR 1 STERILE HALL 1.1500
50 Zone FLOOR 1 STERILE STORAGE 1.1500
51 Zone FLOOR 1 STORAGE 1.1500
52 Zone FLOOR 1 SUB-STERILE 1.1500
53 Zone FLOOR 1 UTILITY HALL 1.1500
54 Zone FLOOR 1 UTILITY JANITOR 1.1500
55 Zone FLOOR 1 UTILITY ROOM 1.1500
56 Zone FLOOR 1 VESTIBULE 1.1500
57 Zone FLOOR 2 CONFERENCE 1.1500
58 Zone FLOOR 2 CONFERENCE TOILET 1.1500
59 Zone FLOOR 2 DICTATION 1.1500
60 Zone FLOOR 2 EXAM 1 1.1500
61 Zone FLOOR 2 EXAM 2 1.1500
62 Zone FLOOR 2 EXAM 3 1.1500
63 Zone FLOOR 2 EXAM 4 1.1500
64 Zone FLOOR 2 EXAM 5 1.1500
65 Zone FLOOR 2 EXAM 6 1.1500
66 Zone FLOOR 2 EXAM 7 1.1500
67 Zone FLOOR 2 EXAM 8 1.1500
68 Zone FLOOR 2 EXAM 9 1.1500
69 Zone FLOOR 2 EXAM HALL 1 1.1500
70 Zone FLOOR 2 EXAM HALL 2 1.1500
71 Zone FLOOR 2 EXAM HALL 3 1.1500
72 Zone FLOOR 2 EXAM HALL 4 1.1500
73 Zone FLOOR 2 EXAM HALL 5 1.1500
74 Zone FLOOR 2 EXAM HALL 6 1.1500
75 Zone FLOOR 2 JANITOR 1.1500
76 Zone FLOOR 2 LOUNGE 1.1500
77 Zone FLOOR 2 NURSE STATION 1 1.1500
78 Zone FLOOR 2 NURSE STATION 2 1.1500
79 Zone FLOOR 2 OFFICE 1.1500
80 Zone FLOOR 2 OFFICE HALL 1.1500
81 Zone FLOOR 2 RECEPTION 1.1500
82 Zone FLOOR 2 RECEPTION HALL 1.1500
83 Zone FLOOR 2 RECEPTION TOILET 1.1500
84 Zone FLOOR 2 SCHEDULING 1 1.1500
85 Zone FLOOR 2 SCHEDULING 2 1.1500
86 Zone FLOOR 2 STORAGE 1 1.1500
87 Zone FLOOR 2 STORAGE 2 1.1500
88 Zone FLOOR 2 STORAGE 3 1.1500
89 Zone FLOOR 2 UTILITY 1.1500
90 Zone FLOOR 2 WORK 1.1500
91 Zone FLOOR 2 WORK HALL 1.1500
92 Zone FLOOR 2 WORK TOILET 1.1500
93 Zone FLOOR 2 X-RAY 1.3500
94 Zone FLOOR 3 DRESSING ROOM 1.1500
95 Zone FLOOR 3 ELEVATOR HALL 1.1500
96 Zone FLOOR 3 HUMID 1.1500
97 Zone FLOOR 3 JANITOR 1.1500
98 Zone FLOOR 3 LOCKER 1.1500
99 Zone FLOOR 3 LOUNGE 1.1500
100 Zone FLOOR 3 LOUNGE TOILET 1.1500
101 Zone FLOOR 3 MECHANICAL 1.1500
102 Zone FLOOR 3 MECHANICAL HALL 1.1500
103 Zone FLOOR 3 OFFICE 1.1500
104 Zone FLOOR 3 OFFICE HALL 1.1500
105 Zone FLOOR 3 OFFICE TOILET 1.1500
106 Zone FLOOR 3 PHYSICAL THERAPY 1 1.1500
107 Zone FLOOR 3 PHYSICAL THERAPY 2 1.1500
108 Zone FLOOR 3 PHYSICAL THERAPY TOILET 1.1500
109 Zone FLOOR 3 STORAGE 1 1.1500
110 Zone FLOOR 3 STORAGE 2 1.1500
111 Zone FLOOR 3 TREATMENT 1.1500
112 Zone FLOOR 3 UNDEVELOPED 1 1.1500
113 Zone FLOOR 3 UNDEVELOPED 2 1.1500
114 Zone FLOOR 3 UTILITY 1.1500
115 Zone FLOOR 3 WORK 1.1500
116 Zone NE STAIR 1.1500
117 Zone NW ELEVATOR 1.1500
118 Zone NW STAIR 1.1500
119 Zone SW STAIR 1.1500


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 FLOOR 1 ANESTHESIA Cooling 788.79864 907.11844 5.68867E-002 6.54197E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 10.03353 2.16021 1.52911E-002 0.00000
2 FLOOR 1 ANESTHESIA Heating 64.37696 80.47121 4.64163E-003 1.52911E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 10.03353 2.16021 1.52911E-002 0.00000
3 FLOOR 1 BIO HAZ Cooling 269.40128 309.81147 1.93027E-002 2.21981E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 5.20257 0.11200 3.17148E-003 0.00000
4 FLOOR 1 BIO HAZ Heating 68.34306 85.42883 4.93364E-003 6.16706E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 5.20257 0.11200 3.17148E-003 0.00000
5 FLOOR 1 CAFE Cooling 4255.97101 4894.36666 0.31244 0.35931 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.20000 1.71672E-002 39.01928 42.00409 0.18434 0.00000
6 FLOOR 1 CAFE Heating 0.00000 0.00000 0.00000 0.18434   00:10:00 8.70000 6.99286E-003 39.01928 42.00409 0.18434 0.00000
7 FLOOR 1 CLEAN Cooling 881.20826 1013.38949 6.35097E-002 7.30361E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 11.70578 2.52025 1.78396E-002 0.00000
8 FLOOR 1 CLEAN Heating 0.00000 0.00000 0.00000 1.78396E-002   00:10:00 8.70000 6.99286E-003 11.70578 2.52025 1.78396E-002 0.00000
9 FLOOR 1 CLEAN WORK Cooling 1103.46285 1268.98228 7.94779E-002 9.13996E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 15.32900 3.30032 2.33614E-002 0.00000
10 FLOOR 1 CLEAN WORK Heating 0.00000 0.00000 0.00000 2.33614E-002   00:10:00 8.70000 6.99286E-003 15.32900 3.30032 2.33614E-002 0.00000
11 FLOOR 1 DICTATION Cooling 666.06418 765.97380 4.77791E-002 5.49460E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 11.70578 0.63006 5.05456E-003 0.00000
12 FLOOR 1 DICTATION Heating 0.00000 0.00000 0.00000 5.05456E-003   00:10:00 8.70000 6.99286E-003 11.70578 0.63006 5.05456E-003 0.00000
13 FLOOR 1 DRESSING ROOM Cooling 361.57801 415.81471 2.61046E-002 3.00203E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 4.18064 0.22502 1.80520E-003 0.00000
14 FLOOR 1 DRESSING ROOM Heating 103.44828 129.31035 7.43259E-003 9.29074E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 4.18064 0.22502 1.80520E-003 0.00000
15 FLOOR 1 ELECTRICAL ROOM Cooling 824.15359 947.77663 5.95116E-002 6.84383E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 9.10450 0.14700 0.00000 0.00000
16 FLOOR 1 ELEVATOR PUMP ROOM Cooling 1145.94074 1317.83185 8.40201E-002 9.66231E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.15033 1.71652E-002 8.45418 0.13650 0.00000 0.00000
17 FLOOR 1 ELEVATOR PUMP ROOM Heating 33.37821 41.72276 2.43446E-003 3.04307E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 8.45418 0.13650 0.00000 0.00000
18 FLOOR 1 HUMID Cooling 329.32945 378.72887 2.36845E-002 2.72371E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 5.01676 0.27003 2.16624E-003 0.00000
19 FLOOR 1 HUMID Heating 0.00000 0.00000 0.00000 2.16624E-003   00:10:00 8.70000 6.99286E-003 5.01676 0.27003 2.16624E-003 0.00000
20 FLOOR 1 IT HALL Cooling 588.99543 677.34474 4.31857E-002 4.96635E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 28.66633 1.71586E-002 13.00643 0.70000 3.96436E-003 0.00000
21 FLOOR 1 IT HALL Heating 0.00000 0.00000 0.00000 3.96436E-003   00:10:00 8.70000 6.99286E-003 13.00643 0.70000 3.96436E-003 0.00000
22 FLOOR 1 IT ROOM Cooling 578.49757 665.27220 4.14881E-002 4.77113E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 10.40514 0.56005 4.49294E-003 0.00000
23 FLOOR 1 IT ROOM Heating 0.00000 0.00000 0.00000 4.49294E-003   00:10:00 8.70000 6.99286E-003 10.40514 0.56005 4.49294E-003 0.00000
24 FLOOR 1 LOBBY Cooling 4190.48180 4819.05407 0.30727 0.35336 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 57.78569 6.22061 3.22906E-002 0.00000
25 FLOOR 1 LOBBY Heating 265.24741 331.55926 1.91133E-002 3.22906E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 57.78569 6.22061 3.22906E-002 0.00000
26 FLOOR 1 LOBBY HALL Cooling 1101.92830 1267.21755 7.88528E-002 9.06807E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 22.29673 1.20000 6.79604E-003 0.00000
27 FLOOR 1 LOBBY HALL Heating 0.00000 0.00000 0.00000 6.79604E-003   00:10:00 8.70000 6.99286E-003 22.29673 1.20000 6.79604E-003 0.00000
28 FLOOR 1 LOBBY TOILET Cooling 352.61248 405.50436 2.53855E-002 2.91933E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 5.01676 0.27000 0.00000 0.00000
29 FLOOR 1 LOBBY TOILET Heating 84.19827 105.24784 6.07037E-003 7.58797E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 5.01676 0.27000 0.00000 0.00000
30 FLOOR 1 LOCKER ROOM Cooling 4100.78583 4715.90371 0.29501 0.33926 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 61.31601 9.90096 4.20505E-002 0.00000
31 FLOOR 1 LOCKER ROOM Heating 0.00000 0.00000 0.00000 4.20505E-002   00:10:00 8.70000 6.99286E-003 61.31601 9.90096 4.20505E-002 0.00000
32 FLOOR 1 LOCKER ROOM HALL Cooling 1868.74362 2149.05516 0.13310 0.15307 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 46.07991 2.48000 1.40452E-002 0.00000
33 FLOOR 1 LOCKER ROOM HALL Heating 0.00000 0.00000 0.00000 1.40452E-002   00:10:00 8.70000 6.99286E-003 46.07991 2.48000 1.40452E-002 0.00000
34 FLOOR 1 LOUNGE Cooling 2233.31389 2568.31098 0.16066 0.18476 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 33.44509 5.40053 2.29366E-002 0.00000
35 FLOOR 1 LOUNGE Heating 0.00000 0.00000 0.00000 2.29366E-002   00:10:00 8.70000 6.99286E-003 33.44509 5.40053 2.29366E-002 0.00000
36 FLOOR 1 MED GAS Cooling 433.85129 498.92898 3.18106E-002 3.65822E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:10:00 32.41833 1.71657E-002 5.20257 0.11200 3.17148E-003 0.00000
37 FLOOR 1 MED GAS Heating 324.75495 405.94369 2.33160E-002 2.91449E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 5.20257 0.11200 3.17148E-003 0.00000
38 FLOOR 1 MRI CONTROL ROOM Cooling 2325.67046 2674.52103 0.16859 0.19387 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 15.60771 3.36033 2.37861E-002 0.00000
39 FLOOR 1 MRI CONTROL ROOM Heating 0.00000 0.00000 0.00000 2.37861E-002   00:10:00 8.70000 6.99286E-003 15.60771 3.36033 2.37861E-002 0.00000
40 FLOOR 1 MRI HALL Cooling 735.98363 846.38117 5.27541E-002 6.06672E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 13.65675 0.73500 4.16258E-003 0.00000
41 FLOOR 1 MRI HALL Heating 0.00000 0.00000 0.00000 4.16258E-003   00:10:00 8.70000 6.99286E-003 13.65675 0.73500 4.16258E-003 0.00000
42 FLOOR 1 MRI ROOM Cooling 5579.35468 6416.25788 0.40421 0.46484 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 40.87734 8.80086 6.22970E-002 0.00000
43 FLOOR 1 MRI ROOM Heating 0.00000 0.00000 0.00000 6.22970E-002   00:10:00 8.70000 6.99286E-003 40.87734 8.80086 6.22970E-002 0.00000
44 FLOOR 1 MRI TOILET Cooling 306.28678 352.22979 2.20037E-002 2.53042E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 5.01676 0.27000 0.00000 0.00000
45 FLOOR 1 MRI TOILET Heating 14.95018 18.68773 1.08915E-003 1.36144E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 5.01676 0.27000 0.00000 0.00000
46 FLOOR 1 NOURISHMENT Cooling 1162.35985 1336.71383 8.36598E-002 9.62088E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 16.90835 2.72999 1.37431E-002 0.00000
47 FLOOR 1 NOURISHMENT Heating 0.00000 0.00000 0.00000 1.37431E-002   00:10:00 8.70000 6.99286E-003 16.90835 2.72999 1.37431E-002 0.00000
48 FLOOR 1 NURSE HALL Cooling 2074.50005 2385.67506 0.14816 0.17039 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 46.07991 2.48000 1.40452E-002 0.00000
49 FLOOR 1 NURSE HALL Heating 0.00000 0.00000 0.00000 1.40452E-002   00:10:00 8.70000 6.99286E-003 46.07991 2.48000 1.40452E-002 0.00000
50 FLOOR 1 NURSE JANITOR Cooling 260.58436 299.67201 1.86719E-002 2.14727E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 5.01676 0.10800 3.05821E-003 0.00000
51 FLOOR 1 NURSE JANITOR Heating 0.00000 0.00000 0.00000 3.05821E-003   00:10:00 8.70000 6.99286E-003 5.01676 0.10800 3.05821E-003 0.00000
52 FLOOR 1 NURSE STATION Cooling 1539.62076 1770.56387 0.11067 0.12727 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 24.24769 3.91498 1.97085E-002 0.00000
53 FLOOR 1 NURSE STATION Heating 0.00000 0.00000 0.00000 1.97085E-002   00:10:00 8.70000 6.99286E-003 24.24769 3.91498 1.97085E-002 0.00000
54 FLOOR 1 NURSE TOILET Cooling 294.64117 338.83734 2.11526E-002 2.43255E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 5.01676 0.27000 0.00000 0.00000
55 FLOOR 1 OFFICE Cooling 2081.46521 2393.68499 0.14875 0.17106 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 44.87217 2.41524 1.93758E-002 0.00000
56 FLOOR 1 OFFICE Heating 0.00000 0.00000 0.00000 1.93758E-002   00:10:00 8.70000 6.99286E-003 44.87217 2.41524 1.93758E-002 0.00000
57 FLOOR 1 OPERATING ROOM 1 Cooling 7497.88396 8622.56656 0.54981 0.72361 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 30.82150 1.71627E-002 42.73540 9.20090 0.23881 0.00000
58 FLOOR 1 OPERATING ROOM 1 Heating 17.41651 21.77063 1.39787E-003 0.23881 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:10:00 8.70000 6.99286E-003 42.73540 9.20090 0.23881 0.00000
59 FLOOR 1 OPERATING ROOM 2 Cooling 7743.87384 8905.45491 0.56785 0.75507 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 30.46417 1.71620E-002 44.59346 9.60093 0.24919 0.00000
60 FLOOR 1 OPERATING ROOM 2 Heating 23.35427 29.19284 1.92439E-003 0.24919 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:10:00 8.70000 6.99286E-003 44.59346 9.60093 0.24919 0.00000
61 FLOOR 1 OPERATING ROOM 3 Cooling 6545.91373 7527.80079 0.47996 0.74878 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:20:00 27.48267 1.71563E-002 44.22185 9.52093 0.24711 0.00000
62 FLOOR 1 OPERATING ROOM 3 Heating 22.72758 28.40947 1.87621E-003 0.24711 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:10:00 8.70000 6.99286E-003 44.22185 9.52093 0.24711 0.00000
63 FLOOR 1 PACU Cooling 778.35390 895.10699 5.61211E-002 6.45393E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 10.03353 2.16021 3.22812E-002 0.00000
64 FLOOR 1 PACU Heating 0.00000 0.00000 0.00000 3.22812E-002   00:10:00 8.70000 6.99286E-003 10.03353 2.16021 3.22812E-002 0.00000
65 FLOOR 1 PRE-OP HALL Cooling 2130.51481 2450.09204 0.15203 0.17484 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 49.05281 2.64000 1.49513E-002 0.00000
66 FLOOR 1 PRE-OP HALL Heating 0.00000 0.00000 0.00000 1.49513E-002   00:10:00 8.70000 6.99286E-003 49.05281 2.64000 1.49513E-002 0.00000
67 FLOOR 1 PRE-OP ROOM 1 Cooling 1019.35657 1172.26006 7.31558E-002 8.91925E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 17.55867 1.89018 5.20321E-002 0.00000
68 FLOOR 1 PRE-OP ROOM 1 Heating 0.00000 0.00000 0.00000 5.20321E-002   00:10:00 8.70000 6.99286E-003 17.55867 1.89018 5.20321E-002 0.00000
69 FLOOR 1 PRE-OP ROOM 2 Cooling 1766.79033 2031.80888 0.12672 0.15951 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 31.40123 3.38033 9.30522E-002 0.00000
70 FLOOR 1 PRE-OP ROOM 2 Heating 0.00000 0.00000 0.00000 9.30522E-002   00:10:00 8.70000 6.99286E-003 31.40123 3.38033 9.30522E-002 0.00000
71 FLOOR 1 PRE-OP TOILET Cooling 298.67777 343.47944 2.14482E-002 2.46654E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 5.01676 0.27000 0.00000 0.00000
72 FLOOR 1 PRE-OP TOILET Heating 70.71311 88.39139 5.11025E-003 6.38781E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 5.01676 0.27000 0.00000 0.00000
73 FLOOR 1 PROCEDURE ROOM Cooling 2212.90563 2544.84148 0.15968 0.33624 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 26.47737 5.70055 0.10760 0.00000
74 FLOOR 1 PROCEDURE ROOM Heating 0.00000 0.00000 0.00000 0.10760   00:10:00 8.70000 6.99286E-003 26.47737 5.70055 0.10760 0.00000
75 FLOOR 1 RECEPTION Cooling 3261.54395 3750.77554 0.23481 0.27003 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 47.28765 15.27149 5.04464E-002 0.00000
76 FLOOR 1 RECEPTION Heating 0.00000 0.00000 0.00000 5.04464E-002   00:10:00 8.70000 6.99286E-003 47.28765 15.27149 5.04464E-002 0.00000
77 FLOOR 1 RECEPTION HALL Cooling 563.42118 647.93436 4.02913E-002 4.63350E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 11.89159 0.64000 3.62456E-003 0.00000
78 FLOOR 1 RECEPTION HALL Heating 0.00000 0.00000 0.00000 3.62456E-003   00:10:00 8.70000 6.99286E-003 11.89159 0.64000 3.62456E-003 0.00000
79 FLOOR 1 RECOVERY ROOM Cooling 3946.69651 4538.70099 0.28944 0.33285 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 33.14417 1.71671E-002 50.16764 10.80105 0.16141 0.00000
80 FLOOR 1 RECOVERY ROOM Heating 55.06851 68.83564 3.91664E-003 0.16141 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 8.70000 6.99286E-003 50.16764 10.80105 0.16141 0.00000
81 FLOOR 1 SCHEDULING Cooling 634.45739 729.62600 4.55263E-002 5.23552E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 11.05546 0.59506 4.77375E-003 0.00000
82 FLOOR 1 SCHEDULING Heating 0.00000 0.00000 0.00000 4.77375E-003   00:10:00 8.70000 6.99286E-003 11.05546 0.59506 4.77375E-003 0.00000
83 FLOOR 1 SCRUB Cooling 382.47888 439.85071 2.73777E-002 3.14844E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 7.80386 0.42000 2.37862E-003 0.00000
84 FLOOR 1 SCRUB Heating 35.71287 44.64109 2.59802E-003 3.24753E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 7.80386 0.42000 2.37862E-003 0.00000
85 FLOOR 1 SOIL Cooling 880.57040 1012.65596 6.34631E-002 7.29825E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 11.70578 2.52025 1.78396E-002 0.00000
86 FLOOR 1 SOIL Heating 0.00000 0.00000 0.00000 1.78396E-002   00:10:00 8.70000 6.99286E-003 11.70578 2.52025 1.78396E-002 0.00000
87 FLOOR 1 SOIL HOLD Cooling 410.51391 472.09100 2.96075E-002 3.40486E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 5.20257 1.12011 7.92871E-003 0.00000
88 FLOOR 1 SOIL HOLD Heating 0.00000 0.00000 0.00000 7.92871E-003   00:10:00 8.70000 6.99286E-003 5.20257 1.12011 7.92871E-003 0.00000
89 FLOOR 1 SOIL WORK Cooling 1170.92301 1346.56147 8.43030E-002 9.69484E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 16.72255 3.60035 2.54851E-002 0.00000
90 FLOOR 1 SOIL WORK Heating 0.00000 0.00000 0.00000 2.54851E-002   00:10:00 8.70000 6.99286E-003 16.72255 3.60035 2.54851E-002 0.00000
91 FLOOR 1 STEP DOWN Cooling 2517.53539 2895.16570 0.18463 0.21232 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 32.44067 1.71658E-002 27.87091 6.00058 8.96699E-002 0.00000
92 FLOOR 1 STEP DOWN Heating 294.48944 368.11180 2.10190E-002 8.96699E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 27.87091 6.00058 8.96699E-002 0.00000
93 FLOOR 1 STERILE HALL Cooling 2323.69610 2672.25052 0.17038 0.19593 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 28.66633 1.71586E-002 57.22827 3.08000 1.74432E-002 0.00000
94 FLOOR 1 STERILE HALL Heating 0.00000 0.00000 0.00000 1.74432E-002   00:10:00 8.70000 6.99286E-003 57.22827 3.08000 1.74432E-002 0.00000
95 FLOOR 1 STERILE STORAGE Cooling 1350.46737 1553.03748 9.59157E-002 0.11030 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 36.78960 0.79200 2.24269E-002 0.00000
96 FLOOR 1 STERILE STORAGE Heating 0.00000 0.00000 0.00000 2.24269E-002   00:10:00 8.70000 6.99286E-003 36.78960 0.79200 2.24269E-002 0.00000
97 FLOOR 1 STORAGE Cooling 4030.86557 4635.49541 0.29554 0.33987 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 32.61933 1.71661E-002 85.47080 1.84000 5.21029E-002 0.00000
98 FLOOR 1 STORAGE Heating 2654.50985 3318.13731 0.18769 0.23461 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 85.47080 1.84000 5.21029E-002 0.00000
99 FLOOR 1 SUB-STERILE Cooling 1210.14770 1391.66985 8.87302E-002 0.10204 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 30.65400 1.71624E-002 18.20900 0.98000 5.55010E-003 0.00000
100 FLOOR 1 SUB-STERILE Heating 445.39422 556.74278 3.16179E-002 3.95224E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 18.20900 0.98000 5.55010E-003 0.00000
101 FLOOR 1 UTILITY HALL Cooling 2123.19610 2441.67552 0.15568 0.17903 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 30.27433 1.71616E-002 23.78318 1.28000 7.24911E-003 0.00000
102 FLOOR 1 UTILITY HALL Heating 841.89722 1052.37153 5.98011E-002 7.47514E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 23.78318 1.28000 7.24911E-003 0.00000
103 FLOOR 1 UTILITY JANITOR Cooling 204.91780 235.65547 1.46893E-002 1.68927E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 3.90193 8.40000E-002 2.37861E-003 0.00000
104 FLOOR 1 UTILITY JANITOR Heating 14.62937 18.28672 1.06634E-003 2.37861E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 3.90193 8.40000E-002 2.37861E-003 0.00000
105 FLOOR 1 UTILITY ROOM Cooling 1715.86892 1973.24926 0.12581 0.14468 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 28.66633 1.71586E-002 33.44509 0.72000 2.03881E-002 0.00000
106 FLOOR 1 UTILITY ROOM Heating 764.87599 956.09499 5.40814E-002 6.76018E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 33.44509 0.72000 2.03881E-002 0.00000
107 FLOOR 1 VESTIBULE Cooling 493.45362 567.47166 3.61809E-002 4.16081E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 32.44067 1.71658E-002 6.68902 0.36000 2.03881E-003 0.00000
108 FLOOR 1 VESTIBULE Heating 93.05958 116.32447 6.71081E-003 8.38851E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 6.68902 0.36000 2.03881E-003 0.00000
109 FLOOR 2 CONFERENCE Cooling 2979.50405 3426.42965 0.21859 0.25138 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 31.49150 1.71640E-002 31.21542 16.80163 4.91580E-002 0.00000
110 FLOOR 2 CONFERENCE Heating 892.24840 1115.31050 6.32257E-002 7.90322E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 31.21542 16.80163 4.91580E-002 0.00000
111 FLOOR 2 CONFERENCE TOILET Cooling 333.51599 383.54339 2.39175E-002 2.75052E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 5.94579 0.32000 0.00000 0.00000
112 FLOOR 2 CONFERENCE TOILET Heating 38.99103 48.73879 2.82904E-003 3.53629E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 5.94579 0.32000 0.00000 0.00000
113 FLOOR 2 DICTATION Cooling 399.15114 459.02381 2.86679E-002 3.29681E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 6.50321 0.35003 2.80809E-003 0.00000
114 FLOOR 2 DICTATION Heating 0.00000 0.00000 0.00000 2.80809E-003   00:10:00 8.70000 6.99286E-003 6.50321 0.35003 2.80809E-003 0.00000
115 FLOOR 2 EXAM 1 Cooling 3081.69906 3543.95392 0.22600 0.25990 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 32.35133 1.71656E-002 33.44509 7.20070 5.09703E-002 0.00000
116 FLOOR 2 EXAM 1 Heating 850.17521 1062.71902 6.00436E-002 7.50545E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 33.44509 7.20070 5.09703E-002 0.00000
117 FLOOR 2 EXAM 2 Cooling 3033.69556 3488.74989 0.21786 0.25484 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 50.16764 10.80105 7.64554E-002 0.00000
118 FLOOR 2 EXAM 2 Heating 25.60245 32.00307 1.85461E-003 7.64554E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 8.70000 6.99286E-003 50.16764 10.80105 7.64554E-002 0.00000
119 FLOOR 2 EXAM 3 Cooling 3972.46025 4568.32929 0.28517 0.33978 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 66.89019 14.40140 0.10194 0.00000
120 FLOOR 2 EXAM 3 Heating 26.47343 33.09179 1.91535E-003 0.10194 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 8.70000 6.99286E-003 66.89019 14.40140 0.10194 0.00000
121 FLOOR 2 EXAM 4 Cooling 609.18505 700.56280 4.39253E-002 5.05141E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 7.80386 1.68016 1.18931E-002 0.00000
122 FLOOR 2 EXAM 4 Heating 230.33526 287.91907 1.64075E-002 2.05094E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 7.80386 1.68016 1.18931E-002 0.00000
123 FLOOR 2 EXAM 5 Cooling 3002.18834 3452.51660 0.22017 0.25319 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 30.27433 1.71616E-002 32.51606 7.00068 4.95544E-002 0.00000
124 FLOOR 2 EXAM 5 Heating 741.48192 926.85240 5.23670E-002 6.54588E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 32.51606 7.00068 4.95544E-002 0.00000
125 FLOOR 2 EXAM 6 Cooling 1435.08677 1650.34979 0.10328 0.11878 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 20.90318 4.50044 3.18564E-002 0.00000
126 FLOOR 2 EXAM 6 Heating 319.76022 399.70028 2.27867E-002 3.18564E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 20.90318 4.50044 3.18564E-002 0.00000
127 FLOOR 2 EXAM 7 Cooling 4326.23237 4975.16723 0.31051 0.37376 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 73.57921 15.84154 0.11213 0.00000
128 FLOOR 2 EXAM 7 Heating 0.00000 0.00000 0.00000 0.11213   00:10:00 8.70000 6.99286E-003 73.57921 15.84154 0.11213 0.00000
129 FLOOR 2 EXAM 8 Cooling 1736.53592 1997.01630 0.12499 0.14374 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 25.08382 5.40053 3.82277E-002 0.00000
130 FLOOR 2 EXAM 8 Heating 240.23092 300.28865 1.72371E-002 3.82277E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 25.08382 5.40053 3.82277E-002 0.00000
131 FLOOR 2 EXAM 9 Cooling 2389.69478 2748.14899 0.17182 0.19760 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 36.78960 7.92077 5.60673E-002 0.00000
132 FLOOR 2 EXAM 9 Heating 0.00000 0.00000 0.00000 5.60673E-002   00:10:00 8.70000 6.99286E-003 36.78960 7.92077 5.60673E-002 0.00000
133 FLOOR 2 EXAM HALL 1 Cooling 926.41568 1065.37803 6.64051E-002 7.63659E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 16.72255 0.90000 5.09703E-003 0.00000
134 FLOOR 2 EXAM HALL 1 Heating 167.59717 209.49647 1.20990E-002 1.51238E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 16.72255 0.90000 5.09703E-003 0.00000
135 FLOOR 2 EXAM HALL 2 Cooling 925.42519 1064.23897 6.63330E-002 7.62830E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 16.72255 0.90000 5.09703E-003 0.00000
136 FLOOR 2 EXAM HALL 2 Heating 41.72120 52.15150 3.03976E-003 5.09703E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 16.72255 0.90000 5.09703E-003 0.00000
137 FLOOR 2 EXAM HALL 3 Cooling 894.25920 1028.39809 6.40692E-002 7.36796E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 16.72255 0.90000 5.09703E-003 0.00000
138 FLOOR 2 EXAM HALL 3 Heating 63.30439 79.13048 4.60215E-003 5.75269E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 16.72255 0.90000 5.09703E-003 0.00000
139 FLOOR 2 EXAM HALL 4 Cooling 972.89231 1118.82616 6.96935E-002 8.01475E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 18.39480 0.99000 5.60674E-003 0.00000
140 FLOOR 2 EXAM HALL 4 Heating 1.99402 2.49252 1.45426E-004 5.60674E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 8.70000 6.99286E-003 18.39480 0.99000 5.60674E-003 0.00000
141 FLOOR 2 EXAM HALL 5 Cooling 1004.20032 1154.83037 7.19679E-002 8.27630E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 18.39480 0.99000 5.60674E-003 0.00000
142 FLOOR 2 EXAM HALL 5 Heating 0.00000 0.00000 0.00000 5.60674E-003   00:10:00 8.70000 6.99286E-003 18.39480 0.99000 5.60674E-003 0.00000
143 FLOOR 2 EXAM HALL 6 Cooling 1000.02175 1150.02501 7.16644E-002 8.24140E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 18.39480 0.99000 5.60674E-003 0.00000
144 FLOOR 2 EXAM HALL 6 Heating 6.91926 8.64908 5.04970E-004 5.60674E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00 8.70000 6.99286E-003 18.39480 0.99000 5.60674E-003 0.00000
145 FLOOR 2 JANITOR Cooling 371.16287 426.83730 2.72142E-002 3.12963E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59200 1.71642E-002 5.85289 0.12600 3.56792E-003 0.00000
146 FLOOR 2 JANITOR Heating 246.12032 307.65040 1.75669E-002 2.19586E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 5.85289 0.12600 3.56792E-003 0.00000
147 FLOOR 2 LOUNGE Cooling 574.06780 660.17797 4.13807E-002 4.75878E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 7.43224 1.20012 5.09702E-003 0.00000
148 FLOOR 2 LOUNGE Heating 0.00000 0.00000 0.00000 5.09702E-003   00:10:00 8.70000 6.99286E-003 7.43224 1.20012 5.09702E-003 0.00000
149 FLOOR 2 NURSE STATION 1 Cooling 906.60871 1042.60001 6.51862E-002 7.49641E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 13.93546 2.24999 1.13267E-002 0.00000
150 FLOOR 2 NURSE STATION 1 Heating 0.00000 0.00000 0.00000 1.13267E-002   00:10:00 8.70000 6.99286E-003 13.93546 2.24999 1.13267E-002 0.00000
151 FLOOR 2 NURSE STATION 2 Cooling 1096.08221 1260.49454 7.88172E-002 9.06398E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 16.72255 2.69999 1.35921E-002 0.00000
152 FLOOR 2 NURSE STATION 2 Heating 0.00000 0.00000 0.00000 1.35921E-002   00:10:00 8.70000 6.99286E-003 16.72255 2.69999 1.35921E-002 0.00000
153 FLOOR 2 OFFICE Cooling 3951.47675 4544.19826 0.28973 0.33319 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 30.46417 1.71620E-002 52.02570 2.80027 2.24647E-002 0.00000
154 FLOOR 2 OFFICE Heating 1367.68145 1709.60182 9.62926E-002 0.12037 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 52.02570 2.80027 2.24647E-002 0.00000
155 FLOOR 2 OFFICE HALL Cooling 2150.74865 2473.36095 0.15403 0.17714 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 41.24895 2.22000 1.25727E-002 0.00000
156 FLOOR 2 OFFICE HALL Heating 278.89005 348.61256 2.01680E-002 2.52100E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 41.24895 2.22000 1.25727E-002 0.00000
157 FLOOR 2 RECEPTION Cooling 6448.75402 7416.06713 0.47300 0.54395 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 32.53000 1.71659E-002 91.41659 29.52287 9.75231E-002 0.00000
158 FLOOR 2 RECEPTION Heating 927.98861 1159.98576 6.63372E-002 9.75231E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 91.41659 29.52287 9.75231E-002 0.00000
159 FLOOR 2 RECEPTION HALL Cooling 2859.07046 3287.93103 0.20487 0.23560 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 52.39731 2.82000 1.59707E-002 0.00000
160 FLOOR 2 RECEPTION HALL Heating 0.00000 0.00000 0.00000 1.59707E-002   00:10:00 8.70000 6.99286E-003 52.39731 2.82000 1.59707E-002 0.00000
161 FLOOR 2 RECEPTION TOILET Cooling 613.02721 704.98129 4.39057E-002 5.04916E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 11.70578 0.63000 0.00000 0.00000
162 FLOOR 2 SCHEDULING 1 Cooling 1511.91259 1738.69947 0.10818 0.12441 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 30.10058 1.62016 1.29974E-002 0.00000
163 FLOOR 2 SCHEDULING 1 Heating 0.00000 0.00000 0.00000 1.29974E-002   00:10:00 8.70000 6.99286E-003 30.10058 1.62016 1.29974E-002 0.00000
164 FLOOR 2 SCHEDULING 2 Cooling 1608.40841 1849.66967 0.11510 0.13236 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 31.77284 1.71017 1.37195E-002 0.00000
165 FLOOR 2 SCHEDULING 2 Heating 0.00000 0.00000 0.00000 1.37195E-002   00:10:00 8.70000 6.99286E-003 31.77284 1.71017 1.37195E-002 0.00000
166 FLOOR 2 STORAGE 1 Cooling 273.56278 314.59720 1.95978E-002 2.25375E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 5.20257 0.11200 3.17148E-003 0.00000
167 FLOOR 2 STORAGE 1 Heating 32.91155 41.13943 2.39089E-003 3.17148E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 5.20257 0.11200 3.17148E-003 0.00000
168 FLOOR 2 STORAGE 2 Cooling 511.02234 587.67569 3.65065E-002 4.19825E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 11.14836 0.24000 6.79603E-003 0.00000
169 FLOOR 2 STORAGE 2 Heating 17.10142 21.37678 1.24765E-003 6.79603E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 11.14836 0.24000 6.79603E-003 0.00000
170 FLOOR 2 STORAGE 3 Cooling 629.66004 724.10905 4.50036E-002 5.17542E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 13.37804 0.28800 8.15524E-003 0.00000
171 FLOOR 2 STORAGE 3 Heating 0.00000 0.00000 0.00000 8.15524E-003   00:10:00 8.70000 6.99286E-003 13.37804 0.28800 8.15524E-003 0.00000
172 FLOOR 2 UTILITY Cooling 890.36727 1023.92236 6.52812E-002 7.50734E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 30.27433 1.71616E-002 11.70578 0.25200 7.13583E-003 0.00000
173 FLOOR 2 UTILITY Heating 415.18158 518.97697 2.95216E-002 3.69019E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 11.70578 0.25200 7.13583E-003 0.00000
174 FLOOR 2 WORK Cooling 6766.35303 7781.30599 0.48256 0.55495 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 157.00614 8.45082 6.77953E-002 0.00000
175 FLOOR 2 WORK Heating 0.00000 0.00000 0.00000 6.77953E-002   00:10:00 8.70000 6.99286E-003 157.00614 8.45082 6.77953E-002 0.00000
176 FLOOR 2 WORK HALL Cooling 4067.75675 4677.92026 0.29132 0.33502 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 77.48114 4.17000 2.36163E-002 0.00000
177 FLOOR 2 WORK HALL Heating 0.00000 0.00000 0.00000 2.36163E-002   00:10:00 8.70000 6.99286E-003 77.48114 4.17000 2.36163E-002 0.00000
178 FLOOR 2 WORK TOILET Cooling 298.78419 343.60182 2.14499E-002 2.46674E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 5.01676 0.27000 0.00000 0.00000
179 FLOOR 2 WORK TOILET Heating 159.13222 198.91528 1.13801E-002 1.42251E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 5.01676 0.27000 0.00000 0.00000
180 FLOOR 2 X-RAY Cooling 10916.98124 14737.92468 0.79056 1.06725 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 83.61274 18.00175 0.12743 0.00000
181 FLOOR 2 X-RAY Heating 0.00000 0.00000 0.00000 0.12743   00:10:00 8.70000 6.99286E-003 83.61274 18.00175 0.12743 0.00000
182 FLOOR 3 DRESSING ROOM Cooling 287.21776 330.30043 2.06866E-002 2.37896E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 3.90193 0.21002 1.68485E-003 0.00000
183 FLOOR 3 DRESSING ROOM Heating 0.00000 0.00000 0.00000 1.68485E-003   00:10:00 8.70000 6.99286E-003 3.90193 0.21002 1.68485E-003 0.00000
184 FLOOR 3 ELEVATOR HALL Cooling 1551.11145 1783.77816 0.11074 0.12735 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 34.37412 1.85000 1.04772E-002 0.00000
185 FLOOR 3 ELEVATOR HALL Heating 666.29628 832.87036 4.71581E-002 5.89476E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 34.37412 1.85000 1.04772E-002 0.00000
186 FLOOR 3 HUMID Cooling 667.61784 767.76051 4.80083E-002 5.52095E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 10.03353 0.54005 4.33248E-003 0.00000
187 FLOOR 3 HUMID Heating 0.00000 0.00000 0.00000 4.33248E-003   00:10:00 8.70000 6.99286E-003 10.03353 0.54005 4.33248E-003 0.00000
188 FLOOR 3 JANITOR Cooling 369.54686 424.97889 2.70959E-002 3.11603E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 31.70367 1.71644E-002 5.85289 0.12600 3.56792E-003 0.00000
189 FLOOR 3 JANITOR Heating 334.99477 418.74346 2.40173E-002 3.00216E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 5.85289 0.12600 3.56792E-003 0.00000
190 FLOOR 3 LOCKER Cooling 889.47308 1022.89405 6.41292E-002 7.37485E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 11.14836 1.80018 7.64554E-003 0.00000
191 FLOOR 3 LOCKER Heating 4.44055 5.55069 3.18977E-004 7.64554E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 8.70000 6.99286E-003 11.14836 1.80018 7.64554E-003 0.00000
192 FLOOR 3 LOUNGE Cooling 4982.16333 5729.48783 0.36535 0.42015 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 33.14417 1.71671E-002 70.51341 11.38611 4.83580E-002 0.00000
193 FLOOR 3 LOUNGE Heating 99.57873 124.47341 7.03062E-003 4.83580E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 8.70000 6.99286E-003 70.51341 11.38611 4.83580E-002 0.00000
194 FLOOR 3 LOUNGE TOILET Cooling 1018.82556 1171.64940 7.47027E-002 8.59081E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 33.20000 1.71672E-002 17.83738 0.96000 0.00000 0.00000
195 FLOOR 3 LOUNGE TOILET Heating 546.22248 682.77810 3.86277E-002 4.82846E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 17.83738 0.96000 0.00000 0.00000
196 FLOOR 3 MECHANICAL Cooling 4333.46497 4983.48472 0.31773 0.36539 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 30.82150 1.71627E-002 32.51606 0.52500 0.00000 0.00000
197 FLOOR 3 MECHANICAL Heating 6.22083 7.77604 4.49856E-004 5.62320E-004 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 8.70000 6.99286E-003 32.51606 0.52500 0.00000 0.00000
198 FLOOR 3 MECHANICAL HALL Cooling 1601.57248 1841.80835 0.11487 0.13211 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 27.87091 1.50000 8.49505E-003 0.00000
199 FLOOR 3 MECHANICAL HALL Heating 441.52957 551.91196 3.15539E-002 3.94423E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 27.87091 1.50000 8.49505E-003 0.00000
200 FLOOR 3 OFFICE Cooling 13634.88378 15680.11635 0.99974 1.14970 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 33.08833 1.71670E-002 282.05363 15.18148 0.12179 0.00000
201 FLOOR 3 OFFICE Heating 3892.31048 4865.38811 0.27264 0.34080 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 282.05363 15.18148 0.12179 0.00000
202 FLOOR 3 OFFICE HALL Cooling 4005.73871 4606.59951 0.28675 0.32976 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 77.48114 4.17000 2.36163E-002 0.00000
203 FLOOR 3 OFFICE HALL Heating 1132.71605 1415.89506 8.10604E-002 0.10133 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 77.48114 4.17000 2.36163E-002 0.00000
204 FLOOR 3 OFFICE TOILET Cooling 296.97210 341.51792 2.17743E-002 2.50404E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 31.81533 1.71646E-002 5.01676 0.27000 0.00000 0.00000
205 FLOOR 3 OFFICE TOILET Heating 230.16543 287.70678 1.64533E-002 2.05666E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 5.01676 0.27000 0.00000 0.00000
206 FLOOR 3 PHYSICAL THERAPY 1 Cooling 9103.21741 10468.70002 0.66761 0.76775 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 33.14417 1.71671E-002 120.77395 26.00253 0.18406 0.00000
207 FLOOR 3 PHYSICAL THERAPY 1 Heating 3112.93233 3891.16541 0.21860 0.27325 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 120.77395 26.00253 0.18406 0.00000
208 FLOOR 3 PHYSICAL THERAPY 2 Cooling 3354.09926 3857.21415 0.24088 0.27938 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 54.99860 11.84115 8.38178E-002 0.00000
209 FLOOR 3 PHYSICAL THERAPY 2 Heating 23.90707 29.88384 1.71660E-003 8.38178E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 8.70000 6.99286E-003 54.99860 11.84115 8.38178E-002 0.00000
210 FLOOR 3 PHYSICAL THERAPY TOILET Cooling 450.92828 518.56752 3.23466E-002 3.71986E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 7.80386 0.42000 0.00000 0.00000
211 FLOOR 3 STORAGE 1 Cooling 507.71001 583.86652 3.63346E-002 4.17848E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 10.03353 0.21600 6.11643E-003 0.00000
212 FLOOR 3 STORAGE 1 Heating 69.32014 86.65018 5.02064E-003 6.27580E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 10.03353 0.21600 6.11643E-003 0.00000
213 FLOOR 3 STORAGE 2 Cooling 416.96093 479.50507 2.98655E-002 3.43453E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 7.80386 0.16800 4.75722E-003 0.00000
214 FLOOR 3 STORAGE 2 Heating 105.42769 131.78462 7.57696E-003 9.47120E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 7.80386 0.16800 4.75722E-003 0.00000
215 FLOOR 3 TREATMENT Cooling 2882.97133 3315.41703 0.20727 0.23836 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 44.22185 9.52093 6.73941E-002 0.00000
216 FLOOR 3 TREATMENT Heating 0.00000 0.00000 0.00000 6.73941E-002   00:10:00 8.70000 6.99286E-003 44.22185 9.52093 6.73941E-002 0.00000
217 FLOOR 3 UNDEVELOPED 1 Cooling 11034.59817 12689.78789 0.80905 0.93041 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 32.93200 1.71667E-002 210.70409 4.53600 0.12845 0.00000
218 FLOOR 3 UNDEVELOPED 1 Heating 3701.62294 4627.02867 0.25781 0.32226 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 210.70409 4.53600 0.12845 0.00000
219 FLOOR 3 UNDEVELOPED 2 Cooling 5790.59780 6659.18747 0.42456 0.48825 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 32.93200 1.71667E-002 107.02430 2.30400 6.52419E-002 0.00000
220 FLOOR 3 UNDEVELOPED 2 Heating 2678.80644 3348.50805 0.18794 0.23493 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 107.02430 2.30400 6.52419E-002 0.00000
221 FLOOR 3 UTILITY Cooling 899.03685 1033.89237 6.41702E-002 7.37958E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 20.06706 0.43200 1.22329E-002 0.00000
222 FLOOR 3 UTILITY Heating 147.08937 183.86171 1.06061E-002 1.32577E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 20.06706 0.43200 1.22329E-002 0.00000
223 FLOOR 3 WORK Cooling 4481.23354 5153.41858 0.32858 0.37786 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 30.82150 1.71627E-002 53.32634 2.87028 2.30263E-002 0.00000
224 FLOOR 3 WORK Heating 1707.84472 2134.80590 0.12091 0.15113 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 53.32634 2.87028 2.30263E-002 0.00000
225 NE STAIR Cooling 2400.88863 2761.02192 0.17604 0.20245 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:10:00 32.41833 1.71657E-002 15.60771 0.84000 4.75723E-003 0.00000
226 NE STAIR Heating 2068.72360 2585.90450 0.14763 0.18454 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 15.60771 0.84000 4.75723E-003 0.00000
227 NW ELEVATOR Cooling 1993.42998 2292.44447 0.14616 0.16808 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 31.81533 1.71646E-002 13.00643 0.21000 0.00000 0.00000
228 NW ELEVATOR Heating 1271.55082 1589.43853 9.00557E-002 0.11257 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 13.00643 0.21000 0.00000 0.00000
229 NW STAIR Cooling 2775.92776 3192.31692 0.20354 0.23407 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 32.03867 1.71650E-002 17.83738 0.96000 5.43683E-003 0.00000
230 NW STAIR Heating 2003.97671 2504.97089 0.14240 0.17800 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 17.83738 0.96000 5.43683E-003 0.00000
231 SW STAIR Cooling 1442.41904 1658.78189 0.10576 0.12163 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 8.91869 0.48000 2.71842E-003 0.00000
232 SW STAIR Heating 989.42890 1236.78613 7.02882E-002 8.78602E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 8.91869 0.48000 2.71842E-003 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 AHU-1 Cooling Sensible 83847.99 5.54236 5.54236 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 AHU-1 Heating Sensible 0.00 1.45579 1.45579   00:00:00
3 AHU-2 Cooling Sensible 78656.62 6.05202 6.05202 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 AHU-2 Heating Sensible 0.00 0.00000 0.00000   00:00:00
5 AHU-3 Cooling Sensible 79813.95 5.77005 5.77005 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 AHU-3 Heating Sensible 0.00 0.00000 0.00000   00:00:00
7 PSZ_CAFE Cooling Sensible 7272.65 0.35931 0.35931 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ_CAFE Heating Sensible 5240.09 0.18434 0.18434 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 PSZ_ELEVATOR Cooling Sensible 1297.45 9.66231E-002 9.66231E-002 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
10 PSZ_ELEVATOR Heating Sensible 40.99 3.04307E-003 3.04307E-003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00
11 PSZ_MRI_CONTROL Cooling Sensible 2791.46 0.19387 0.19387 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 PSZ_MRI_CONTROL Heating Sensible 676.14 2.37861E-002 2.37861E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 PSZ_MRI Cooling Sensible 6730.73 0.46484 0.46484 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 PSZ_MRI Heating Sensible 1770.85 6.22970E-002 6.22970E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 PSZ_OR_1 Cooling Sensible 13243.23 0.72361 0.72361 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 PSZ_OR_1 Heating Sensible 5919.51 0.23881 0.23881 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
17 PSZ_OR_2 Cooling Sensible 13711.47 0.75507 0.75507 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
18 PSZ_OR_2 Heating Sensible 6176.88 0.24919 0.24919 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
19 PSZ_OR_3 Cooling Sensible 12707.41 0.74878 0.74878 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
20 PSZ_OR_3 Heating Sensible 6125.41 0.24711 0.24711 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
21 PSZ_XRAY Cooling Sensible 15340.85 1.06725 1.06725 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
22 PSZ_XRAY Heating Sensible 3622.19 0.12743 0.12743 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.54197E-002
2 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
3 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
4 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.54197E-002
5 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.26005E-003
8 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.61104E-005
9 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.54197E-002
10 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
11 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
12 Coil:Heating:Water FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2984.58335
13 Coil:Heating:Water FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.61104E-005
14 Coil:Heating:Water FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 49.41418
15 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.21981E-002
16 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17859
17 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
18 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.43962E-003
19 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
20 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.13338E-003
22 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.13677E-006
23 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.16706E-003
24 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
25 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
26 Coil:Heating:Water FLOOR 1 BIO HAZ VAV BOX REHEAT COIL Design Size Rated Capacity [W] 358.55182
27 Coil:Heating:Water FLOOR 1 BIO HAZ VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.13677E-006
28 Coil:Heating:Water FLOOR 1 BIO HAZ VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6.48397
29 AirTerminal:SingleDuct:ConstantVolume:NoReheat FLOOR 1 CAFE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.35931
30 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.30361E-002
31 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.54276
32 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
33 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.30361E-002
34 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
35 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.11966E-003
37 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.82894E-005
38 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.30361E-002
39 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
40 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
41 Coil:Heating:Water FLOOR 1 CLEAN VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3233.65450
42 Coil:Heating:Water FLOOR 1 CLEAN VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.82894E-005
43 Coil:Heating:Water FLOOR 1 CLEAN VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 53.09675
44 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.13996E-002
45 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.56796
46 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
47 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.13996E-002
48 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
49 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.98126E-003
51 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.54022E-005
52 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.13996E-002
53 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
54 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
55 Coil:Heating:Water FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4046.69246
56 Coil:Heating:Water FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.54022E-005
57 Coil:Heating:Water FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 66.44687
58 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.49460E-002
59 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
60 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
61 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.34696E-003
62 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.12825E-006
63 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.49460E-003
64 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
65 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
66 Coil:Heating:Water FLOOR 1 DICTATION VAV BOX REHEAT COIL Design Size Rated Capacity [W] 243.27199
67 Coil:Heating:Water FLOOR 1 DICTATION VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.12825E-006
68 Coil:Heating:Water FLOOR 1 DICTATION VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3.99454
69 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.00203E-002
70 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
71 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
72 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.59039E-003
73 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.72847E-006
74 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.29074E-003
75 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
76 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
77 Coil:Heating:Water FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 540.49343
78 Coil:Heating:Water FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.72847E-006
79 Coil:Heating:Water FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 9.77691
80 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.84383E-002
81 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10137
82 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
83 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.36877E-002
84 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
85 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
86 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.75849E-003
87 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.30171E-006
88 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.36877E-002
89 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
90 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
91 Coil:Heating:Water FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 606.01763
92 Coil:Heating:Water FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.30171E-006
93 Coil:Heating:Water FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 9.95084
94 AirTerminal:SingleDuct:ConstantVolume:NoReheat FLOOR 1 ELEVATOR PUMP ROOM DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.66231E-002
95 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.72371E-002
96 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
97 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
98 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.71461E-003
99 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.05499E-006
100 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.72371E-003
101 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
102 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
103 Coil:Heating:Water FLOOR 1 HUMID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 120.59164
104 Coil:Heating:Water FLOOR 1 HUMID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.05499E-006
105 Coil:Heating:Water FLOOR 1 HUMID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1.98012
106 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.96635E-002
107 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19956
108 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
109 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.93271E-003
110 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
111 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
112 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.90919E-003
113 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.84728E-006
114 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.93271E-003
115 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
116 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
117 Coil:Heating:Water FLOOR 1 IT HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 439.76800
118 Coil:Heating:Water FLOOR 1 IT HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.84728E-006
119 Coil:Heating:Water FLOOR 1 IT HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7.22101
120 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.77113E-002
121 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
122 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
123 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.29268E-003
124 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.84802E-006
125 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.77113E-003
126 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
127 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
128 Coil:Heating:Water FLOOR 1 IT ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 211.24037
129 Coil:Heating:Water FLOOR 1 IT ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.84802E-006
130 Coil:Heating:Water FLOOR 1 IT ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3.46858
131 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.35336
132 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12461
133 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
134 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.06724E-002
135 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40066
136 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
137 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.05752E-003
138 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.03908E-005
139 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.06724E-002
140 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
141 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
142 Coil:Heating:Water FLOOR 1 LOBBY VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3473.85459
143 Coil:Heating:Water FLOOR 1 LOBBY VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.03908E-005
144 Coil:Heating:Water FLOOR 1 LOBBY VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 58.85243
145 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.06807E-002
146 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18736
147 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
148 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.81361E-002
149 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
150 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
151 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.03350E-003
152 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.02476E-006
153 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.81361E-002
154 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
155 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
156 Coil:Heating:Water FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 802.97278
157 Coil:Heating:Water FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.02476E-006
158 Coil:Heating:Water FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 13.18485
159 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.91933E-002
160 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
161 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
162 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.91933E-002
163 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
164 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
165 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.90958E-003
166 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.22236E-005
167 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.91933E-002
168 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
169 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
170 Coil:Heating:Water FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1397.23553
171 Coil:Heating:Water FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.22236E-005
172 Coil:Heating:Water FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 23.46883
173 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.33926
174 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13772
175 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
176 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.78524E-002
177 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.41731
178 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
179 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.76651E-003
180 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.62816E-005
181 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.78524E-002
182 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
183 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
184 Coil:Heating:Water FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3004.14768
185 Coil:Heating:Water FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.62816E-005
186 Coil:Heating:Water FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 49.32824
187 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.15307
188 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22940
189 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
190 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.06130E-002
191 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.92494
192 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
193 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.66087E-003
194 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.18575E-005
195 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.06130E-002
196 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
197 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
198 Coil:Heating:Water FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1355.38277
199 Coil:Heating:Water FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.18575E-005
200 Coil:Heating:Water FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 22.25544
201 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.18476
202 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13794
203 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
204 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.69522E-002
205 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.76627
206 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
207 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.76215E-003
208 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.43129E-005
209 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.69522E-002
210 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
211 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
212 Coil:Heating:Water FLOOR 1 LOUNGE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1636.04890
213 Coil:Heating:Water FLOOR 1 LOUNGE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.43129E-005
214 Coil:Heating:Water FLOOR 1 LOUNGE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 26.86399
215 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.65822E-002
216 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10837
217 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
218 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.31644E-003
219 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
220 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
221 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.51578E-003
222 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.48400E-005
223 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.91449E-002
224 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
225 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
226 Coil:Heating:Water FLOOR 1 MED GAS VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1696.29817
227 Coil:Heating:Water FLOOR 1 MED GAS VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.48400E-005
228 Coil:Heating:Water FLOOR 1 MED GAS VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 30.69054
229 AirTerminal:SingleDuct:ConstantVolume:NoReheat FLOOR 1 MRI CONTROL ROOM DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.19387
230 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.06672E-002
231 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17153
232 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
233 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.21334E-002
234 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
235 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
236 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.22114E-003
237 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.69970E-006
238 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.21334E-002
239 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
240 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
241 Coil:Heating:Water FLOOR 1 MRI HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 537.20457
242 Coil:Heating:Water FLOOR 1 MRI HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.69970E-006
243 Coil:Heating:Water FLOOR 1 MRI HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8.82092
244 AirTerminal:SingleDuct:ConstantVolume:NoReheat FLOOR 1 MRI ROOM DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.46484
245 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.53042E-002
246 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
247 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
248 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.53042E-002
249 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
250 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
251 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.52197E-003
252 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.95820E-006
253 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.53042E-002
254 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
255 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
256 Coil:Heating:Water FLOOR 1 MRI TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1138.28398
257 Coil:Heating:Water FLOOR 1 MRI TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.95820E-006
258 Coil:Heating:Water FLOOR 1 MRI TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 18.77084
259 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.62088E-002
260 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13392
261 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
262 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.92418E-002
263 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
264 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
265 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.84501E-003
266 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.45300E-006
267 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.92418E-002
268 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
269 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
270 Coil:Heating:Water FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 851.92393
271 Coil:Heating:Water FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.45300E-006
272 Coil:Heating:Water FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 13.98863
273 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.17039
274 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20608
275 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
276 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.40777E-002
277 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.83090
278 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
279 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.84884E-003
280 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.31995E-005
281 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.40777E-002
282 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
283 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
284 Coil:Heating:Water FLOOR 1 NURSE HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1508.78188
285 Coil:Heating:Water FLOOR 1 NURSE HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.31995E-005
286 Coil:Heating:Water FLOOR 1 NURSE HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 24.77426
287 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.14727E-002
288 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17803
289 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
290 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.29454E-003
291 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
292 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
293 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.14009E-003
294 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.66342E-006
295 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.29454E-003
296 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
297 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
298 Coil:Heating:Water FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL Design Size Rated Capacity [W] 190.13951
299 Coil:Heating:Water FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.66342E-006
300 Coil:Heating:Water FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3.12210
301 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.12727
302 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14518
303 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
304 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.54535E-002
305 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
306 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
307 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.62432E-003
308 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.85900E-006
309 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.54535E-002
310 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
311 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
312 Coil:Heating:Water FLOOR 1 NURSE STATION VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1126.94477
313 Coil:Heating:Water FLOOR 1 NURSE STATION VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.85900E-006
314 Coil:Heating:Water FLOOR 1 NURSE STATION VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 18.50448
315 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.43255E-002
316 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
317 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
318 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.43255E-002
319 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
320 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
321 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.42442E-003
322 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.42210E-006
323 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.43255E-002
324 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
325 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
326 Coil:Heating:Water FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1077.00344
327 Coil:Heating:Water FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.42210E-006
328 Coil:Heating:Water FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 17.68444
329 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.17106
330 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.82765
331 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
332 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.90606E-003
333 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.62566E-006
334 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.71058E-002
335 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
336 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
337 Coil:Heating:Water FLOOR 1 OFFICE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 757.35355
338 Coil:Heating:Water FLOOR 1 OFFICE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.62566E-006
339 Coil:Heating:Water FLOOR 1 OFFICE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 12.43578
340 AirTerminal:SingleDuct:ConstantVolume:NoReheat FLOOR 1 OPERATING ROOM 1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.72361
341 AirTerminal:SingleDuct:ConstantVolume:NoReheat FLOOR 1 OPERATING ROOM 2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.75507
342 AirTerminal:SingleDuct:ConstantVolume:NoReheat FLOOR 1 OPERATING ROOM 3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.74878
343 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.45393E-002
344 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.78971
345 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
346 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.45393E-002
347 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
348 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
349 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.21618E-003
350 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.49983E-005
351 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.45393E-002
352 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
353 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
354 Coil:Heating:Water FLOOR 1 PACU VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2857.45978
355 Coil:Heating:Water FLOOR 1 PACU VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.49983E-005
356 Coil:Heating:Water FLOOR 1 PACU VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 46.91962
357 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.17484
358 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21379
359 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
360 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.49673E-002
361 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.80976
362 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
363 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.78213E-003
364 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.35441E-005
365 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.49673E-002
366 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
367 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
368 Coil:Heating:Water FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1548.16905
369 Coil:Heating:Water FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.35441E-005
370 Coil:Heating:Water FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 25.42100
371 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.91925E-002
372 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
373 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
374 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.91925E-002
375 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
376 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
377 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
378 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.45473E-005
379 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.91925E-002
380 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
381 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
382 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3948.97296
383 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.45473E-005
384 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 64.84231
385 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.15951
386 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
387 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
388 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15951
389 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
390 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
391 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
392 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.17831E-005
393 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.15951
394 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
395 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
396 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7062.18444
397 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.17831E-005
398 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 115.96138
399 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.46654E-002
400 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
401 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
402 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.46654E-002
403 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
404 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
405 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.45830E-003
406 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.03225E-005
407 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.46654E-002
408 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
409 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
410 Coil:Heating:Water FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1179.92744
411 Coil:Heating:Water FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.03225E-005
412 Coil:Heating:Water FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 19.81564
413 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.33624
414 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
415 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
416 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.33624
417 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
418 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
419 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.34960E-003
420 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.30238E-004
421 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.33624
422 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
423 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
424 Coil:Heating:Water FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14887.00123
425 Coil:Heating:Water FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.30238E-004
426 Coil:Heating:Water FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 244.44521
427 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.27003
428 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13344
429 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
430 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.40057E-002
431 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52430
432 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
433 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.85517E-003
434 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.09183E-005
435 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.40057E-002
436 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
437 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
438 Coil:Heating:Water FLOOR 1 RECEPTION VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2391.08922
439 Coil:Heating:Water FLOOR 1 RECEPTION VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.09183E-005
440 Coil:Heating:Water FLOOR 1 RECEPTION VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 39.26179
441 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.63350E-002
442 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19556
443 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
444 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.26699E-003
445 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
446 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
447 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.94822E-003
448 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.58943E-006
449 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.26699E-003
450 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
451 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
452 Coil:Heating:Water FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 410.29360
453 Coil:Heating:Water FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.58943E-006
454 Coil:Heating:Water FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6.73704
455 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.33285
456 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.76561
457 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.87000
458 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.28958
459 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.87000
460 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
461 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.31740E-003
462 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.13354E-004
463 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.28958
464 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
465 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
466 Coil:Heating:Water FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12957.09605
467 Coil:Heating:Water FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.13354E-004
468 Coil:Heating:Water FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 213.35099
469 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.23552E-002
470 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
471 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
472 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.36784E-003
473 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.02790E-006
474 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.23552E-003
475 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
476 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
477 Coil:Heating:Water FLOOR 1 SCHEDULING VAV BOX REHEAT COIL Design Size Rated Capacity [W] 231.80133
478 Coil:Heating:Water FLOOR 1 SCHEDULING VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.02790E-006
479 Coil:Heating:Water FLOOR 1 SCHEDULING VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3.80619
480 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.14844E-002
481 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18887
482 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
483 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.29688E-003
484 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
485 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
486 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.01723E-003
487 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.83597E-006
488 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.29688E-003
489 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
490 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
491 Coil:Heating:Water FLOOR 1 SCRUB VAV BOX REHEAT COIL Design Size Rated Capacity [W] 324.16929
492 Coil:Heating:Water FLOOR 1 SCRUB VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.83597E-006
493 Coil:Heating:Water FLOOR 1 SCRUB VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5.57971
494 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.29825E-002
495 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
496 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
497 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.29825E-002
498 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
499 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
500 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.11737E-003
501 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.82687E-005
502 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.29825E-002
503 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
504 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
505 Coil:Heating:Water FLOOR 1 SOIL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3231.28229
506 Coil:Heating:Water FLOOR 1 SOIL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.82687E-005
507 Coil:Heating:Water FLOOR 1 SOIL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 53.05780
508 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.40486E-002
509 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
510 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
511 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.40486E-002
512 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
513 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
514 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.27228E-003
515 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.31882E-005
516 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.40486E-002
517 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
518 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
519 Coil:Heating:Water FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1507.49174
520 Coil:Heating:Water FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.31882E-005
521 Coil:Heating:Water FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 24.75308
522 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.69484E-002
523 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
524 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
525 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.69484E-002
526 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
527 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
528 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.89873E-003
529 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.75515E-005
530 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.69484E-002
531 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
532 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
533 Coil:Heating:Water FLOOR 1 SOIL WORK VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4292.36596
534 Coil:Heating:Water FLOOR 1 SOIL WORK VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.75515E-005
535 Coil:Heating:Water FLOOR 1 SOIL WORK VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 70.48084
536 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.21232
537 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.66680
538 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.69000
539 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.14650
540 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69000
541 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
542 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.80900E-003
543 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.00029E-005
544 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.14650
545 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
546 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
547 Coil:Heating:Water FLOOR 1 STEP DOWN VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6858.70498
548 Coil:Heating:Water FLOOR 1 STEP DOWN VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.00029E-005
549 Coil:Heating:Water FLOOR 1 STEP DOWN VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 114.42314
550 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.19593
551 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22257
552 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
553 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.91865E-002
554 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.72258
555 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
556 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.71185E-003
557 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.51783E-005
558 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.91865E-002
559 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
560 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
561 Coil:Heating:Water FLOOR 1 STERILE HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1734.97130
562 Coil:Heating:Water FLOOR 1 STERILE HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.51783E-005
563 Coil:Heating:Water FLOOR 1 STERILE HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 28.48830
564 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.11030
565 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25415
566 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
567 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.20606E-002
568 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
569 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
570 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.49911E-003
571 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.54484E-006
572 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.20606E-002
573 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
574 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
575 Coil:Heating:Water FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 976.72791
576 Coil:Heating:Water FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.54484E-006
577 Coil:Heating:Water FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 16.03792
578 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.33987
579 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19163
580 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
581 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.79744E-002
582 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51101
583 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
584 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.98823E-003
585 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.19897E-004
586 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.23461
587 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
588 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
589 Coil:Heating:Water FLOOR 1 STORAGE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13705.00480
590 Coil:Heating:Water FLOOR 1 STORAGE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.19897E-004
591 Coil:Heating:Water FLOOR 1 STORAGE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 248.38061
592 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10204
593 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13598
594 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
595 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.04079E-002
596 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
597 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
598 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.80190E-003
599 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.01760E-005
600 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.95224E-002
601 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
602 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
603 Coil:Heating:Water FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2306.24045
604 Coil:Heating:Water FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.01760E-005
605 Coil:Heating:Water FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 41.77572
606 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.17903
607 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10123
608 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
609 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.58054E-002
610 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.79081
611 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
612 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.76373E-003
613 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.81612E-005
614 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.47514E-002
615 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
616 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
617 Coil:Heating:Water FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4362.06103
618 Coil:Heating:Water FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.81612E-005
619 Coil:Heating:Water FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 79.01620
620 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.68927E-002
621 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17601
622 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
623 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.37854E-003
624 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
625 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
626 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.16466E-003
627 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.47040E-006
628 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.37854E-003
629 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
630 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
631 Coil:Heating:Water FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL Design Size Rated Capacity [W] 168.07540
632 Coil:Heating:Water FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.47040E-006
633 Coil:Heating:Water FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2.85891
634 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.14468
635 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17615
636 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
637 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.89364E-002
638 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.97853
639 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
640 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.16298E-003
641 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.45425E-005
642 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.76018E-002
643 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
644 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
645 Coil:Heating:Water FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3948.42243
646 Coil:Heating:Water FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.45425E-005
647 Coil:Heating:Water FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 71.55331
648 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.16081E-002
649 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12250
650 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
651 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.32161E-003
652 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
653 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
654 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.11018E-003
655 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.26518E-006
656 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.38851E-003
657 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
658 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
659 Coil:Heating:Water FLOOR 1 VESTIBULE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 487.53595
660 Coil:Heating:Water FLOOR 1 VESTIBULE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.26518E-006
661 Coil:Heating:Water FLOOR 1 VESTIBULE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8.81507
662 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.25138
663 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.46236E-002
664 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.35100
665 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.82332E-002
666 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.56320
667 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
668 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.02648E-003
669 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.39685E-005
670 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.82332E-002
671 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
672 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
673 Coil:Heating:Water FLOOR 2 CONFERENCE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5025.86756
674 Coil:Heating:Water FLOOR 2 CONFERENCE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.39685E-005
675 Coil:Heating:Water FLOOR 2 CONFERENCE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 89.99747
676 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.75052E-002
677 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
678 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
679 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.75052E-002
680 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
681 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
682 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.31299E-003
683 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.11210E-005
684 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.75052E-002
685 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
686 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
687 Coil:Heating:Water FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1271.20113
688 Coil:Heating:Water FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.11210E-005
689 Coil:Heating:Water FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 21.11695
690 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.29681E-002
691 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15031
692 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
693 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.89043E-003
694 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
695 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
696 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53475E-003
697 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.83091E-006
698 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.89043E-003
699 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
700 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
701 Coil:Heating:Water FLOOR 2 DICTATION VAV BOX REHEAT COIL Design Size Rated Capacity [W] 437.89598
702 Coil:Heating:Water FLOOR 2 DICTATION VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.83091E-006
703 Coil:Heating:Water FLOOR 2 DICTATION VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7.18741
704 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.25990
705 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.65367
706 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51000
707 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13255
708 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54473
709 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
710 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.88552E-003
711 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.06496E-005
712 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13255
713 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
714 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
715 Coil:Heating:Water FLOOR 2 EXAM 1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6932.62151
716 Coil:Heating:Water FLOOR 2 EXAM 1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.06496E-005
717 Coil:Heating:Water FLOOR 2 EXAM 1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 119.95422
718 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.25484
719 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
720 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
721 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.25484
722 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
723 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
724 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
725 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.97413E-005
726 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.25484
727 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
728 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
729 Coil:Heating:Water FLOOR 2 EXAM 2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11401.03775
730 Coil:Heating:Water FLOOR 2 EXAM 2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.97413E-005
731 Coil:Heating:Water FLOOR 2 EXAM 2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 187.64681
732 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.33978
733 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
734 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
735 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.33978
736 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
737 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
738 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
739 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.32981E-004
740 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.33978
741 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
742 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
743 Coil:Heating:Water FLOOR 2 EXAM 3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15200.51916
744 Coil:Heating:Water FLOOR 2 EXAM 3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.32981E-004
745 Coil:Heating:Water FLOOR 2 EXAM 3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 250.17759
746 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.05141E-002
747 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.78475
748 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.64000
749 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.23290E-002
750 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
751 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
752 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.23649E-003
753 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.50433E-005
754 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.23290E-002
755 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
756 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
757 Coil:Heating:Water FLOOR 2 EXAM 4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1719.54341
758 Coil:Heating:Water FLOOR 2 EXAM 4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.50433E-005
759 Coil:Heating:Water FLOOR 2 EXAM 4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 29.94207
760 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.25319
761 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.65235
762 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.69000
763 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.17470
764 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69000
765 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
766 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.89336E-003
767 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.57965E-005
768 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.17470
769 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
770 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
771 Coil:Heating:Water FLOOR 2 EXAM 5 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8664.00594
772 Coil:Heating:Water FLOOR 2 EXAM 5 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.57965E-005
773 Coil:Heating:Water FLOOR 2 EXAM 5 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 147.14443
774 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.11878
775 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.89396
776 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.94000
777 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11165
778 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
779 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
780 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.84111E-003
781 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.67610E-005
782 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.11165
783 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
784 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
785 Coil:Heating:Water FLOOR 2 EXAM 6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5345.06866
786 Coil:Heating:Water FLOOR 2 EXAM 6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.67610E-005
787 Coil:Heating:Water FLOOR 2 EXAM 6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 89.74503
788 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.37376
789 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
790 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
791 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.37376
792 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
793 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
794 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
795 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.44770E-004
796 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.37376
797 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
798 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
799 Coil:Heating:Water FLOOR 2 EXAM 7 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16548.07715
800 Coil:Heating:Water FLOOR 2 EXAM 7 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.44770E-004
801 Coil:Heating:Water FLOOR 2 EXAM 7 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 271.61219
802 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.14374
803 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.88645
804 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.93000
805 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13368
806 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.98495
807 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
808 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.86520E-003
809 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.44481E-005
810 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13368
811 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
812 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
813 Coil:Heating:Water FLOOR 2 EXAM 8 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6223.74991
814 Coil:Heating:Water FLOOR 2 EXAM 8 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.44481E-005
815 Coil:Heating:Water FLOOR 2 EXAM 8 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 103.61248
816 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.19760
817 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.94576
818 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
819 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.19760
820 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
821 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
822 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.68550E-003
823 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.65361E-005
824 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.19760
825 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
826 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
827 Coil:Heating:Water FLOOR 2 EXAM 9 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8748.54426
828 Coil:Heating:Water FLOOR 2 EXAM 9 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.65361E-005
829 Coil:Heating:Water FLOOR 2 EXAM 9 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 143.59441
830 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.63659E-002
831 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16686
832 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
833 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.29098E-002
834 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
835 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
836 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.28332E-003
837 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.07186E-005
838 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.29098E-002
839 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
840 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
841 Coil:Heating:Water FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1225.19724
842 Coil:Heating:Water FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.07186E-005
843 Coil:Heating:Water FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 21.37888
844 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.62830E-002
845 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16704
846 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
847 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.28849E-002
848 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
849 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
850 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.28084E-003
851 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.42689E-006
852 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.28849E-002
853 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
854 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
855 Coil:Heating:Water FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1077.55184
856 Coil:Heating:Water FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.42689E-006
857 Coil:Heating:Water FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 17.99994
858 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.36796E-002
859 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17295
860 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
861 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.21039E-002
862 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
863 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
864 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.20300E-003
865 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.33216E-006
866 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.21039E-002
867 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
868 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
869 Coil:Heating:Water FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1066.72356
870 Coil:Heating:Water FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.33216E-006
871 Coil:Heating:Water FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 17.95605
872 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.01475E-002
873 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17489
874 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
875 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.40443E-002
876 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
877 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
878 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.17854E-003
879 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.47141E-006
880 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.40443E-002
881 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
882 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
883 Coil:Heating:Water FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1082.64003
884 Coil:Heating:Water FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.47141E-006
885 Coil:Heating:Water FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 17.85073
886 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.27630E-002
887 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16936
888 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
889 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.48289E-002
890 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
891 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
892 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.24963E-003
893 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.61710E-006
894 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.48289E-002
895 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
896 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
897 Coil:Heating:Water FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1099.29331
898 Coil:Heating:Water FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.61710E-006
899 Coil:Heating:Water FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 18.04327
900 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.24140E-002
901 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17008
902 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
903 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.47242E-002
904 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
905 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
906 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.24014E-003
907 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.78480E-006
908 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.47242E-002
909 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
910 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
911 Coil:Heating:Water FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1118.46230
912 Coil:Heating:Water FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.78480E-006
913 Coil:Heating:Water FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 18.46555
914 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.12963E-002
915 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14251
916 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
917 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.38889E-003
918 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
919 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
920 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.67357E-003
921 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.11957E-005
922 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.19586E-002
923 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
924 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
925 Coil:Heating:Water FLOOR 2 JANITOR VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1279.73176
926 Coil:Heating:Water FLOOR 2 JANITOR VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.11957E-005
927 Coil:Heating:Water FLOOR 2 JANITOR VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 23.15229
928 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.75878E-002
929 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11901
930 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
931 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.42764E-002
932 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
933 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
934 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.20145E-003
935 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.52973E-006
936 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.42764E-002
937 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
938 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
939 Coil:Heating:Water FLOOR 2 LOUNGE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 632.08177
940 Coil:Heating:Water FLOOR 2 LOUNGE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.52973E-006
941 Coil:Heating:Water FLOOR 2 LOUNGE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 10.37469
942 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.49641E-002
943 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14165
944 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
945 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.24892E-002
946 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
947 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
948 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.68969E-003
949 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.71086E-006
950 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.24892E-002
951 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
952 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
953 Coil:Heating:Water FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 995.70496
954 Coil:Heating:Water FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.71086E-006
955 Coil:Heating:Water FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 16.34302
956 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.06398E-002
957 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14058
958 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
959 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.71920E-002
960 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
961 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
962 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.71011E-003
963 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.05324E-005
964 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.71920E-002
965 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
966 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
967 Coil:Heating:Water FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1203.91632
968 Coil:Heating:Water FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.05324E-005
969 Coil:Heating:Water FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 19.76050
970 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.33319
971 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11898
972 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
973 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.99578E-002
974 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.42491
975 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
976 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.20219E-003
977 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.15722E-005
978 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12037
979 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
980 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
981 Coil:Heating:Water FLOOR 2 OFFICE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7038.07949
982 Coil:Heating:Water FLOOR 2 OFFICE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.15722E-005
983 Coil:Heating:Water FLOOR 2 OFFICE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 127.52389
984 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.17714
985 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17744
986 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
987 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.31413E-002
988 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.79924
989 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
990 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.14718E-003
991 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.36980E-005
992 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.31413E-002
993 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
994 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
995 Coil:Heating:Water FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2708.82928
996 Coil:Heating:Water FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.36980E-005
997 Coil:Heating:Water FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 46.43703
998 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.54395
999 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12806
1000 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32200
1001 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.17515
1002 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34150
1003 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1004 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.97512E-003
1005 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.81910E-005
1006 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.17515
1007 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1008 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1009 Coil:Heating:Water FLOOR 2 RECEPTION VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8937.70884
1010 Coil:Heating:Water FLOOR 2 RECEPTION VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.81910E-005
1011 Coil:Heating:Water FLOOR 2 RECEPTION VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 153.27524
1012 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.23560
1013 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16947
1014 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1015 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.06808E-002
1016 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60091
1017 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1018 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.24823E-003
1019 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.73771E-005
1020 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.06808E-002
1021 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1022 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1023 Coil:Heating:Water FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3129.37409
1024 Coil:Heating:Water FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.73771E-005
1025 Coil:Heating:Water FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 51.36404
1026 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.04916E-002
1027 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
1028 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
1029 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.04916E-002
1030 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1031 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1032 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.15669E-003
1033 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.95571E-005
1034 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.04916E-002
1035 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1036 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1037 Coil:Heating:Water FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2235.50125
1038 Coil:Heating:Water FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.95571E-005
1039 Coil:Heating:Water FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 36.69244
1040 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.12441
1041 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18437
1042 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1043 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.73222E-002
1044 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1045 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1046 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.06653E-003
1047 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.44562E-005
1048 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.73222E-002
1049 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1050 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1051 Coil:Heating:Water FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1652.43228
1052 Coil:Heating:Water FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.44562E-005
1053 Coil:Heating:Water FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 27.12223
1054 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.13236
1055 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18291
1056 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1057 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.97089E-002
1058 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1059 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1060 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.08296E-003
1061 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.53806E-005
1062 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.97089E-002
1063 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1064 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1065 Coil:Heating:Water FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1758.09950
1066 Coil:Heating:Water FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.53806E-005
1067 Coil:Heating:Water FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 28.85660
1068 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.25375E-002
1069 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17590
1070 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1071 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.76125E-003
1072 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1073 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1074 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.16600E-003
1075 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.98140E-006
1076 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.76125E-003
1077 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1078 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1079 Coil:Heating:Water FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 340.79217
1080 Coil:Heating:Water FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.98140E-006
1081 Coil:Heating:Water FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5.81927
1082 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.19825E-002
1083 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20235
1084 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1085 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.25948E-002
1086 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1087 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1088 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.88290E-003
1089 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.11028E-006
1090 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.25948E-002
1091 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1092 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1093 Coil:Heating:Water FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 584.13694
1094 Coil:Heating:Water FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.11028E-006
1095 Coil:Heating:Water FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 9.71361
1096 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.17542E-002
1097 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19697
1098 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1099 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.55262E-002
1100 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1101 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1102 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.93430E-003
1103 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.01385E-006
1104 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.55262E-002
1105 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1106 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1107 Coil:Heating:Water FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 687.42043
1108 Coil:Heating:Water FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.01385E-006
1109 Coil:Heating:Water FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 11.28299
1110 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.50734E-002
1111 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11881
1112 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1113 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.25220E-002
1114 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1115 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1116 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.20668E-003
1117 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.88325E-005
1118 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.69019E-002
1119 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1120 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1121 Coil:Heating:Water FLOOR 2 UTILITY VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2152.67133
1122 Coil:Heating:Water FLOOR 2 UTILITY VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.88325E-005
1123 Coil:Heating:Water FLOOR 2 UTILITY VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 38.96220
1124 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.55495
1125 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21559
1126 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1127 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16648
1128 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.57490
1129 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1130 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.76728E-003
1131 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.44850E-005
1132 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.16648
1133 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1134 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1135 Coil:Heating:Water FLOOR 2 WORK VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7371.03009
1136 Coil:Heating:Water FLOOR 2 WORK VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.44850E-005
1137 Coil:Heating:Water FLOOR 2 WORK VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 120.98455
1138 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.33502
1139 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17623
1140 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1141 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.10050
1142 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.46995
1143 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1144 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.16192E-003
1145 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.89290E-005
1146 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.10050
1147 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1148 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1149 Coil:Heating:Water FLOOR 2 WORK HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4449.82516
1150 Coil:Heating:Water FLOOR 2 WORK HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.89290E-005
1151 Coil:Heating:Water FLOOR 2 WORK HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 73.03729
1152 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.46674E-002
1153 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
1154 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
1155 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.46674E-002
1156 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1157 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1158 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.45849E-003
1159 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.12926E-005
1160 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.46674E-002
1161 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1162 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1163 Coil:Heating:Water FLOOR 2 WORK TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1290.80991
1164 Coil:Heating:Water FLOOR 2 WORK TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.12926E-005
1165 Coil:Heating:Water FLOOR 2 WORK TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 22.33896
1166 AirTerminal:SingleDuct:ConstantVolume:NoReheat FLOOR 2 X-RAY DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.06725
1167 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.37896E-002
1168 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12498
1169 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1170 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.13687E-003
1171 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1172 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1173 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.04844E-003
1174 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.76436E-006
1175 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.13687E-003
1176 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1177 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1178 Coil:Heating:Water FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 315.98316
1179 Coil:Heating:Water FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.76436E-006
1180 Coil:Heating:Water FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5.18640
1181 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.12735
1182 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20568
1183 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1184 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.82053E-002
1185 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1186 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1187 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.85243E-003
1188 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.01237E-005
1189 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.89476E-002
1190 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1191 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1192 Coil:Heating:Water FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3443.32606
1193 Coil:Heating:Water FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.01237E-005
1194 Coil:Heating:Water FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 62.36096
1195 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.52095E-002
1196 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13848
1197 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1198 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.65629E-002
1199 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1200 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1201 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.75125E-003
1202 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.41537E-006
1203 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.65629E-002
1204 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1205 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1206 Coil:Heating:Water FLOOR 3 HUMID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 733.31592
1207 Coil:Heating:Water FLOOR 3 HUMID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.41537E-006
1208 Coil:Heating:Water FLOOR 3 HUMID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 12.03630
1209 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.11603E-002
1210 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14313
1211 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1212 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.34809E-003
1213 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1214 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1215 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.66196E-003
1216 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.52911E-005
1217 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.00216E-002
1218 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1219 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1220 Coil:Heating:Water FLOOR 3 JANITOR VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1747.86576
1221 Coil:Heating:Water FLOOR 3 JANITOR VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.52911E-005
1222 Coil:Heating:Water FLOOR 3 JANITOR VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 31.60689
1223 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.37485E-002
1224 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11519
1225 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1226 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.21246E-002
1227 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1228 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1229 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.30759E-003
1230 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.69937E-006
1231 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.21246E-002
1232 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1233 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1234 Coil:Heating:Water FLOOR 3 LOCKER VAV BOX REHEAT COIL Design Size Rated Capacity [W] 994.39163
1235 Coil:Heating:Water FLOOR 3 LOCKER VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.69937E-006
1236 Coil:Heating:Water FLOOR 3 LOCKER VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 16.38736
1237 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.42015
1238 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12788
1239 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1240 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12605
1241 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34103
1242 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1243 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.97925E-003
1244 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.01125E-005
1245 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12605
1246 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1247 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1248 Coil:Heating:Water FLOOR 3 LOUNGE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5728.16441
1249 Coil:Heating:Water FLOOR 3 LOUNGE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.01125E-005
1250 Coil:Heating:Water FLOOR 3 LOUNGE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 94.69325
1251 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.59081E-002
1252 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
1253 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
1254 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.59081E-002
1255 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1256 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1257 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.40809E-003
1258 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.92470E-005
1259 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.59081E-002
1260 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1261 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1262 Coil:Heating:Water FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4486.17234
1263 Coil:Heating:Water FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.92470E-005
1264 Coil:Heating:Water FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 77.57906
1265 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.36539
1266 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.78110E-002
1267 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1268 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.10962
1269 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.38747
1270 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1271 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.61855E-003
1272 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.26900E-005
1273 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.10962
1274 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1275 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1276 Coil:Heating:Water FLOOR 3 MECHANICAL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4879.72909
1277 Coil:Heating:Water FLOOR 3 MECHANICAL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.26900E-005
1278 Coil:Heating:Water FLOOR 3 MECHANICAL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 80.20433
1279 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.13211
1280 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16076
1281 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1282 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.96316E-002
1283 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1284 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1285 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.36995E-003
1286 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.01922E-005
1287 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.96316E-002
1288 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1289 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1290 Coil:Heating:Water FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2308.09057
1291 Coil:Heating:Water FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.01922E-005
1292 Coil:Heating:Water FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 41.74353
1293 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.14970
1294 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18694
1295 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1296 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.34491
1297 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.49851
1298 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1299 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.03809E-003
1300 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.76169E-004
1301 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.34491
1302 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1303 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1304 Coil:Heating:Water FLOOR 3 OFFICE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20137.15570
1305 Coil:Heating:Water FLOOR 3 OFFICE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.76169E-004
1306 Coil:Heating:Water FLOOR 3 OFFICE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 364.61229
1307 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.32976
1308 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17904
1309 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1310 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.89279E-002
1311 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.47744
1312 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1313 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.12800E-003
1314 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.16568E-005
1315 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.10133
1316 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1317 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1318 Coil:Heating:Water FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5904.69234
1319 Coil:Heating:Water FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.16568E-005
1320 Coil:Heating:Water FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 106.82086
1321 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.50404E-002
1322 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
1323 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
1324 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.50404E-002
1325 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1326 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1327 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.49568E-003
1328 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.22160E-005
1329 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.50404E-002
1330 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1331 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1332 Coil:Heating:Water FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1396.36552
1333 Coil:Heating:Water FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.22160E-005
1334 Coil:Heating:Water FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 24.77790
1335 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.76775
1336 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.79908
1337 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.69000
1338 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.52975
1339 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69000
1340 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1341 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.17847E-003
1342 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.39311E-004
1343 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.52975
1344 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1345 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1346 Coil:Heating:Water FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 27354.71552
1347 Coil:Heating:Water FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.39311E-004
1348 Coil:Heating:Water FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 471.10553
1349 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.27938
1350 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
1351 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.83000
1352 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23188
1353 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.83000
1354 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1355 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
1356 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.14997E-005
1357 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.23188
1358 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1359 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1360 Coil:Heating:Water FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10458.98082
1361 Coil:Heating:Water FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.14997E-005
1362 Coil:Heating:Water FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 172.53271
1363 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.71986E-002
1364 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
1365 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
1366 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.71986E-002
1367 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1368 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1369 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.38335E-003
1370 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.44083E-005
1371 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.71986E-002
1372 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1373 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1374 Coil:Heating:Water FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1646.95884
1375 Coil:Heating:Water FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.44083E-005
1376 Coil:Heating:Water FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 27.03239
1377 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.17848E-002
1378 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18297
1379 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
1380 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.17848E-002
1381 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1382 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1383 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.08226E-003
1384 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.69597E-005
1385 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.17848E-002
1386 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1387 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1388 Coil:Heating:Water FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1938.59599
1389 Coil:Heating:Water FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.69597E-005
1390 Coil:Heating:Water FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 32.24006
1391 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.43453E-002
1392 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17314
1393 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1394 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.03036E-002
1395 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1396 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1397 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.20053E-003
1398 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.14553E-006
1399 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.03036E-002
1400 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1401 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1402 Coil:Heating:Water FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 588.16573
1403 Coil:Heating:Water FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.14553E-006
1404 Coil:Heating:Water FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 10.54213
1405 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.23836
1406 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.94240
1407 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.81000
1408 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.19307
1409 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.81000
1410 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1411 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.69509E-003
1412 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.47845E-005
1413 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.19307
1414 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1415 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1416 Coil:Heating:Water FLOOR 3 TREATMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8548.32410
1417 Coil:Heating:Water FLOOR 3 TREATMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.47845E-005
1418 Coil:Heating:Water FLOOR 3 TREATMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 140.30809
1419 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.93041
1420 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17257
1421 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1422 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.27912
1423 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.46018
1424 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1425 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.20785E-003
1426 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.65263E-004
1427 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.32226
1428 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1429 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1430 Coil:Heating:Water FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18890.57440
1431 Coil:Heating:Water FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.65263E-004
1432 Coil:Heating:Water FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 342.67639
1433 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.48825
1434 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16703
1435 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1436 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.14647
1437 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44541
1438 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1439 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.28102E-003
1440 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.20278E-004
1441 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.23493
1442 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1443 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1444 Coil:Heating:Water FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13748.49234
1445 Coil:Heating:Water FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.20278E-004
1446 Coil:Heating:Water FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 249.20889
1447 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.37958E-002
1448 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20721
1449 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30700
1450 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.26553E-002
1451 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1452 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1453 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.83873E-003
1454 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.03894E-005
1455 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.26553E-002
1456 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1457 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1458 Coil:Heating:Water FLOOR 3 UTILITY VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1187.57055
1459 Coil:Heating:Water FLOOR 3 UTILITY VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.03894E-005
1460 Coil:Heating:Water FLOOR 3 UTILITY VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 20.56548
1461 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.37786
1462 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10754
1463 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1464 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11336
1465 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37468
1466 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1467 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.54293E-003
1468 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.72153E-005
1469 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.15113
1470 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1471 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1472 Coil:Heating:Water FLOOR 3 WORK VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8826.18555
1473 Coil:Heating:Water FLOOR 3 WORK VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.72153E-005
1474 Coil:Heating:Water FLOOR 3 WORK VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 159.83221
1475 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.20245
1476 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 5.87461E-002
1477 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1478 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.07346E-002
1479 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69932
1480 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1481 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.48553E-003
1482 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.40975E-005
1483 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.18454
1484 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1485 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1486 Coil:Heating:Water NE STAIR VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10755.92804
1487 Coil:Heating:Water NE STAIR VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.40975E-005
1488 Coil:Heating:Water NE STAIR VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 194.59979
1489 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.16808
1490 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 5.89643E-002
1491 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1492 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.04249E-002
1493 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.84230
1494 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1495 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.46153E-003
1496 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.75002E-005
1497 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.11257
1498 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1499 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1500 Coil:Heating:Water NW ELEVATOR VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6572.62747
1501 Coil:Heating:Water NW ELEVATOR VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.75002E-005
1502 Coil:Heating:Water NW ELEVATOR VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 119.01016
1503 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.23407
1504 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 5.80690E-002
1505 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1506 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.02203E-002
1507 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60485
1508 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1509 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.56115E-003
1510 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.08552E-005
1511 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.17800
1512 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1513 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1514 Coil:Heating:Water NW STAIR VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10385.30751
1515 Coil:Heating:Water NW STAIR VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.08552E-005
1516 Coil:Heating:Water NW STAIR VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 187.98141
1517 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.12163
1518 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 5.58758E-002
1519 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
1520 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.64883E-002
1521 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1522 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1523 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.81870E-003
1524 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.48479E-005
1525 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.78602E-002
1526 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] -15.00000
1527 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.80000E-003
1528 Coil:Heating:Water SW STAIR VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5126.38594
1529 Coil:Heating:Water SW STAIR VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.48479E-005
1530 Coil:Heating:Water SW STAIR VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 92.79375
1531 AirLoopHVAC AHU-1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 3.52808
1532 AirLoopHVAC AHU-1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.38496
1533 AirLoopHVAC AHU-1 Sum of Air Terminal Maximum Flow Rates [m3/s] 5.54236
1534 AirLoopHVAC AHU-1 Adjusted Heating Design Air Flow Rate [m3/s] 3.52808
1535 AirLoopHVAC AHU-1 Adjusted Cooling Design Air Flow Rate [m3/s] 5.54236
1536 AirLoopHVAC AHU-1 Adjusted Main Design Air Flow Rate [m3/s] 5.54236
1537 AirLoopHVAC AHU-1 User Heating Air Flow Ratio [] 1.00000
1538 AirLoopHVAC AHU-1 Calculated Heating Air Flow Ratio [] 0.63657
1539 AirLoopHVAC AHU-2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.03089
1540 AirLoopHVAC AHU-2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.18474
1541 AirLoopHVAC AHU-2 Sum of Air Terminal Maximum Flow Rates [m3/s] 6.44944
1542 AirLoopHVAC AHU-2 Adjusted Heating Design Air Flow Rate [m3/s] 3.18474
1543 AirLoopHVAC AHU-2 Adjusted Cooling Design Air Flow Rate [m3/s] 6.05202
1544 AirLoopHVAC AHU-2 Adjusted Main Design Air Flow Rate [m3/s] 6.05202
1545 AirLoopHVAC AHU-2 User Heating Air Flow Ratio [] 1.00000
1546 AirLoopHVAC AHU-2 Calculated Heating Air Flow Ratio [] 0.52623
1547 AirLoopHVAC AHU-3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 3.45115
1548 AirLoopHVAC AHU-3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.52906
1549 AirLoopHVAC AHU-3 Sum of Air Terminal Maximum Flow Rates [m3/s] 6.08845
1550 AirLoopHVAC AHU-3 Adjusted Heating Design Air Flow Rate [m3/s] 2.52906
1551 AirLoopHVAC AHU-3 Adjusted Cooling Design Air Flow Rate [m3/s] 5.77005
1552 AirLoopHVAC AHU-3 Adjusted Main Design Air Flow Rate [m3/s] 5.77005
1553 AirLoopHVAC AHU-3 User Heating Air Flow Ratio [] 1.00000
1554 AirLoopHVAC AHU-3 Calculated Heating Air Flow Ratio [] 0.43831
1555 AirLoopHVAC PSZ_CAFE Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.35931
1556 AirLoopHVAC PSZ_CAFE Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.35931
1557 AirLoopHVAC PSZ_CAFE Sum of Air Terminal Maximum Flow Rates [m3/s] 0.35931
1558 AirLoopHVAC PSZ_CAFE Adjusted Heating Design Air Flow Rate [m3/s] 0.35931
1559 AirLoopHVAC PSZ_CAFE Adjusted Cooling Design Air Flow Rate [m3/s] 0.35931
1560 AirLoopHVAC PSZ_CAFE Adjusted Main Design Air Flow Rate [m3/s] 0.35931
1561 AirLoopHVAC PSZ_CAFE User Heating Air Flow Ratio [] 1.00000
1562 AirLoopHVAC PSZ_CAFE Calculated Heating Air Flow Ratio [] 1.00000
1563 AirLoopHVAC PSZ_ELEVATOR Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 9.66231E-002
1564 AirLoopHVAC PSZ_ELEVATOR Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 9.66231E-002
1565 AirLoopHVAC PSZ_ELEVATOR Sum of Air Terminal Maximum Flow Rates [m3/s] 9.66231E-002
1566 AirLoopHVAC PSZ_ELEVATOR Adjusted Heating Design Air Flow Rate [m3/s] 9.66231E-002
1567 AirLoopHVAC PSZ_ELEVATOR Adjusted Cooling Design Air Flow Rate [m3/s] 9.66231E-002
1568 AirLoopHVAC PSZ_ELEVATOR Adjusted Main Design Air Flow Rate [m3/s] 9.66231E-002
1569 AirLoopHVAC PSZ_ELEVATOR User Heating Air Flow Ratio [] 1.00000
1570 AirLoopHVAC PSZ_ELEVATOR Calculated Heating Air Flow Ratio [] 1.00000
1571 AirLoopHVAC PSZ_MRI_CONTROL Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.19387
1572 AirLoopHVAC PSZ_MRI_CONTROL Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.19387
1573 AirLoopHVAC PSZ_MRI_CONTROL Sum of Air Terminal Maximum Flow Rates [m3/s] 0.19387
1574 AirLoopHVAC PSZ_MRI_CONTROL Adjusted Heating Design Air Flow Rate [m3/s] 0.19387
1575 AirLoopHVAC PSZ_MRI_CONTROL Adjusted Cooling Design Air Flow Rate [m3/s] 0.19387
1576 AirLoopHVAC PSZ_MRI_CONTROL Adjusted Main Design Air Flow Rate [m3/s] 0.19387
1577 AirLoopHVAC PSZ_MRI_CONTROL User Heating Air Flow Ratio [] 1.00000
1578 AirLoopHVAC PSZ_MRI_CONTROL Calculated Heating Air Flow Ratio [] 1.00000
1579 AirLoopHVAC PSZ_MRI Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.46484
1580 AirLoopHVAC PSZ_MRI Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.46484
1581 AirLoopHVAC PSZ_MRI Sum of Air Terminal Maximum Flow Rates [m3/s] 0.46484
1582 AirLoopHVAC PSZ_MRI Adjusted Heating Design Air Flow Rate [m3/s] 0.46484
1583 AirLoopHVAC PSZ_MRI Adjusted Cooling Design Air Flow Rate [m3/s] 0.46484
1584 AirLoopHVAC PSZ_MRI Adjusted Main Design Air Flow Rate [m3/s] 0.46484
1585 AirLoopHVAC PSZ_MRI User Heating Air Flow Ratio [] 1.00000
1586 AirLoopHVAC PSZ_MRI Calculated Heating Air Flow Ratio [] 1.00000
1587 AirLoopHVAC PSZ_OR_1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.72361
1588 AirLoopHVAC PSZ_OR_1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.72361
1589 AirLoopHVAC PSZ_OR_1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.72361
1590 AirLoopHVAC PSZ_OR_1 Adjusted Heating Design Air Flow Rate [m3/s] 0.72361
1591 AirLoopHVAC PSZ_OR_1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.72361
1592 AirLoopHVAC PSZ_OR_1 Adjusted Main Design Air Flow Rate [m3/s] 0.72361
1593 AirLoopHVAC PSZ_OR_1 User Heating Air Flow Ratio [] 1.00000
1594 AirLoopHVAC PSZ_OR_1 Calculated Heating Air Flow Ratio [] 1.00000
1595 AirLoopHVAC PSZ_OR_2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.75507
1596 AirLoopHVAC PSZ_OR_2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.75507
1597 AirLoopHVAC PSZ_OR_2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.75507
1598 AirLoopHVAC PSZ_OR_2 Adjusted Heating Design Air Flow Rate [m3/s] 0.75507
1599 AirLoopHVAC PSZ_OR_2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.75507
1600 AirLoopHVAC PSZ_OR_2 Adjusted Main Design Air Flow Rate [m3/s] 0.75507
1601 AirLoopHVAC PSZ_OR_2 User Heating Air Flow Ratio [] 1.00000
1602 AirLoopHVAC PSZ_OR_2 Calculated Heating Air Flow Ratio [] 1.00000
1603 AirLoopHVAC PSZ_OR_3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.74878
1604 AirLoopHVAC PSZ_OR_3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.74878
1605 AirLoopHVAC PSZ_OR_3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.74878
1606 AirLoopHVAC PSZ_OR_3 Adjusted Heating Design Air Flow Rate [m3/s] 0.74878
1607 AirLoopHVAC PSZ_OR_3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.74878
1608 AirLoopHVAC PSZ_OR_3 Adjusted Main Design Air Flow Rate [m3/s] 0.74878
1609 AirLoopHVAC PSZ_OR_3 User Heating Air Flow Ratio [] 1.00000
1610 AirLoopHVAC PSZ_OR_3 Calculated Heating Air Flow Ratio [] 1.00000
1611 AirLoopHVAC PSZ_XRAY Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.06725
1612 AirLoopHVAC PSZ_XRAY Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.06725
1613 AirLoopHVAC PSZ_XRAY Sum of Air Terminal Maximum Flow Rates [m3/s] 1.06725
1614 AirLoopHVAC PSZ_XRAY Adjusted Heating Design Air Flow Rate [m3/s] 1.06725
1615 AirLoopHVAC PSZ_XRAY Adjusted Cooling Design Air Flow Rate [m3/s] 1.06725
1616 AirLoopHVAC PSZ_XRAY Adjusted Main Design Air Flow Rate [m3/s] 1.06725
1617 AirLoopHVAC PSZ_XRAY User Heating Air Flow Ratio [] 1.00000
1618 AirLoopHVAC PSZ_XRAY Calculated Heating Air Flow Ratio [] 1.00000
1619 AirLoopHVAC AHU-1 Design Supply Air Flow Rate [m3/s] 5.54236
1620 AirLoopHVAC AHU-2 Design Supply Air Flow Rate [m3/s] 6.05202
1621 AirLoopHVAC AHU-3 Design Supply Air Flow Rate [m3/s] 5.77005
1622 AirLoopHVAC PSZ_CAFE Design Supply Air Flow Rate [m3/s] 0.35931
1623 AirLoopHVAC PSZ_ELEVATOR Design Supply Air Flow Rate [m3/s] 9.66231E-002
1624 AirLoopHVAC PSZ_MRI_CONTROL Design Supply Air Flow Rate [m3/s] 0.19387
1625 AirLoopHVAC PSZ_MRI Design Supply Air Flow Rate [m3/s] 0.46484
1626 AirLoopHVAC PSZ_OR_1 Design Supply Air Flow Rate [m3/s] 0.72361
1627 AirLoopHVAC PSZ_OR_2 Design Supply Air Flow Rate [m3/s] 0.75507
1628 AirLoopHVAC PSZ_OR_3 Design Supply Air Flow Rate [m3/s] 0.74878
1629 AirLoopHVAC PSZ_XRAY Design Supply Air Flow Rate [m3/s] 1.06725
1630 Controller:OutdoorAir AHU-1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.54236
1631 Controller:OutdoorAir AHU-1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.06558
1632 Coil:Cooling:DX:TwoSpeed AHU-1 COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 5.54236
1633 Coil:Cooling:DX:TwoSpeed AHU-1 COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 137630.08455
1634 Coil:Cooling:DX:TwoSpeed AHU-1 COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.70108
1635 Coil:Cooling:DX:TwoSpeed AHU-1 COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.84727
1636 Coil:Cooling:DX:TwoSpeed AHU-1 COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 45872.10718
1637 Coil:Cooling:DX:TwoSpeed AHU-1 COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.70108
1638 Coil:Heating:Water AHU-1 HEATING COIL Design Size Rated Capacity [W] 0.00000
1639 Coil:Heating:Water AHU-1 HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 0.00000
1640 Coil:Heating:Water AHU-1 HEATING COIL Design Size U-Factor Times Area Value [W/K] 1.00000
1641 Fan:VariableVolume AHU-1 FAN Design Size Maximum Flow Rate [m3/s] 5.54236
1642 Humidifier:Steam:Electric AHU-1 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 0.00000
1643 Humidifier:Steam:Electric AHU-1 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
1644 Humidifier:Steam:Electric AHU-1 HUMIDIFIER Design Size Rated Power [W] 96450.69782
1645 Humidifier:Steam:Electric AHU-1 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
1646 Controller:WaterCoil AHU-1_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 0.00000
1647 Controller:OutdoorAir AHU-2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 6.05202
1648 Coil:Cooling:DX:TwoSpeed AHU-2 COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 6.05202
1649 Coil:Cooling:DX:TwoSpeed AHU-2 COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 141596.54129
1650 Coil:Cooling:DX:TwoSpeed AHU-2 COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.72012
1651 Coil:Cooling:DX:TwoSpeed AHU-2 COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 2.01714
1652 Coil:Cooling:DX:TwoSpeed AHU-2 COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 47194.12721
1653 Coil:Cooling:DX:TwoSpeed AHU-2 COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.72012
1654 Coil:Heating:Water AHU-2 HEATING COIL Design Size Rated Capacity [W] 0.00000
1655 Coil:Heating:Water AHU-2 HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 0.00000
1656 Coil:Heating:Water AHU-2 HEATING COIL Design Size U-Factor Times Area Value [W/K] 1.00000
1657 Fan:VariableVolume AHU-2 FAN Design Size Maximum Flow Rate [m3/s] 6.05202
1658 Controller:WaterCoil AHU-2_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 0.00000
1659 Controller:OutdoorAir AHU-3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.77005
1660 Coil:Cooling:DX:TwoSpeed AHU-3 COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 5.77005
1661 Coil:Cooling:DX:TwoSpeed AHU-3 COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 137288.61197
1662 Coil:Cooling:DX:TwoSpeed AHU-3 COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.71479
1663 Coil:Cooling:DX:TwoSpeed AHU-3 COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.92316
1664 Coil:Cooling:DX:TwoSpeed AHU-3 COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 45758.29437
1665 Coil:Cooling:DX:TwoSpeed AHU-3 COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.71479
1666 Coil:Heating:Water AHU-3 HEATING COIL Design Size Rated Capacity [W] 0.00000
1667 Coil:Heating:Water AHU-3 HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 0.00000
1668 Coil:Heating:Water AHU-3 HEATING COIL Design Size U-Factor Times Area Value [W/K] 1.00000
1669 Fan:VariableVolume AHU-3 FAN Design Size Maximum Flow Rate [m3/s] 5.77005
1670 Controller:WaterCoil AHU-3_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 0.00000
1671 Controller:OutdoorAir PSZ_CAFE_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.35931
1672 Controller:OutdoorAir PSZ_CAFE_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.18434
1673 Fan:SystemModel PSZ_CAFE_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.35931
1674 Fan:SystemModel PSZ_CAFE_ADDAQ FAN Design Electric Power Consumption [W] 625.10279
1675 AirLoopHVAC:UnitarySystem PSZ_CAFE_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.35931
1676 AirLoopHVAC:UnitarySystem PSZ_CAFE_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.35931
1677 AirLoopHVAC:UnitarySystem PSZ_CAFE_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.35931
1678 AirLoopHVAC:UnitarySystem PSZ_CAFE_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.35931
1679 Coil:Cooling:DX:MultiSpeed PSZ_CAFE HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.35931
1680 Coil:Cooling:DX:MultiSpeed PSZ_CAFE HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.17965
1681 Coil:Cooling:DX:MultiSpeed PSZ_CAFE HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.23954
1682 Coil:Cooling:DX:MultiSpeed PSZ_CAFE HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 8922.42000
1683 Coil:Cooling:DX:MultiSpeed PSZ_CAFE HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 4461.21000
1684 Coil:Cooling:DX:MultiSpeed PSZ_CAFE HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.70108
1685 Coil:Cooling:DX:MultiSpeed PSZ_CAFE HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.70108
1686 AirLoopHVAC:UnitarySystem PSZ_CAFE_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 8922.42000
1687 AirLoopHVAC:UnitarySystem PSZ_CAFE_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 5978.01977
1688 AirLoopHVAC:UnitarySystem PSZ_CAFE_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 32.22000
1689 AirLoopHVAC:UnitarySystem PSZ_CAFE_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 8922.41757
1690 AirLoopHVAC:UnitarySystem PSZ_CAFE_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
1691 Coil:Heating:DX:MultiSpeed PSZ_CAFE HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 0.35931
1692 Coil:Heating:DX:MultiSpeed PSZ_CAFE HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.17965
1693 Coil:Heating:DX:MultiSpeed PSZ_CAFE HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 8922.41757
1694 Coil:Heating:DX:MultiSpeed PSZ_CAFE HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 4461.20878
1695 Coil:Heating:DX:MultiSpeed PSZ_CAFE HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
1696 Coil:Heating:Electric PSZ_CAFE_SUPPHEATCOIL Design Size Nominal Capacity [W] 8922.41757
1697 Controller:OutdoorAir PSZ_ELEVATOR_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.66231E-002
1698 Controller:OutdoorAir PSZ_ELEVATOR_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.00000
1699 Fan:SystemModel PSZ_ELEVATOR_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 9.66231E-002
1700 Fan:SystemModel PSZ_ELEVATOR_ADDAQ FAN Design Electric Power Consumption [W] 168.10027
1701 AirLoopHVAC:UnitarySystem PSZ_ELEVATOR_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 9.66231E-002
1702 AirLoopHVAC:UnitarySystem PSZ_ELEVATOR_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 9.66231E-002
1703 AirLoopHVAC:UnitarySystem PSZ_ELEVATOR_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 9.66231E-002
1704 AirLoopHVAC:UnitarySystem PSZ_ELEVATOR_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 9.66231E-002
1705 Coil:Cooling:DX:MultiSpeed PSZ_ELEVATOR HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 9.66231E-002
1706 Coil:Cooling:DX:MultiSpeed PSZ_ELEVATOR HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 4.83116E-002
1707 Coil:Cooling:DX:MultiSpeed PSZ_ELEVATOR HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 6.44154E-002
1708 Coil:Cooling:DX:MultiSpeed PSZ_ELEVATOR HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 1682.54000
1709 Coil:Cooling:DX:MultiSpeed PSZ_ELEVATOR HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 841.27000
1710 Coil:Cooling:DX:MultiSpeed PSZ_ELEVATOR HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80050
1711 Coil:Cooling:DX:MultiSpeed PSZ_ELEVATOR HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80050
1712 AirLoopHVAC:UnitarySystem PSZ_ELEVATOR_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 1682.54000
1713 AirLoopHVAC:UnitarySystem PSZ_ELEVATOR_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 1071.63554
1714 AirLoopHVAC:UnitarySystem PSZ_ELEVATOR_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 32.22000
1715 AirLoopHVAC:UnitarySystem PSZ_ELEVATOR_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 1599.45603
1716 AirLoopHVAC:UnitarySystem PSZ_ELEVATOR_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
1717 Coil:Heating:DX:MultiSpeed PSZ_ELEVATOR HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 9.66231E-002
1718 Coil:Heating:DX:MultiSpeed PSZ_ELEVATOR HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 4.83116E-002
1719 Coil:Heating:DX:MultiSpeed PSZ_ELEVATOR HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 1599.45603
1720 Coil:Heating:DX:MultiSpeed PSZ_ELEVATOR HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 799.72802
1721 Coil:Heating:DX:MultiSpeed PSZ_ELEVATOR HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
1722 Coil:Heating:Electric PSZ_ELEVATOR_SUPPHEATCOIL Design Size Nominal Capacity [W] 1599.45603
1723 Controller:OutdoorAir PSZ_MRI_CONTROL_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.19387
1724 Controller:OutdoorAir PSZ_MRI_CONTROL_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.37861E-002
1725 Fan:SystemModel PSZ_MRI_CONTROL_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.19387
1726 Fan:SystemModel PSZ_MRI_CONTROL_ADDAQ FAN Design Electric Power Consumption [W] 337.29077
1727 AirLoopHVAC:UnitarySystem PSZ_MRI_CONTROL_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.19387
1728 AirLoopHVAC:UnitarySystem PSZ_MRI_CONTROL_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.19387
1729 AirLoopHVAC:UnitarySystem PSZ_MRI_CONTROL_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.19387
1730 AirLoopHVAC:UnitarySystem PSZ_MRI_CONTROL_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.19387
1731 Coil:Cooling:DX:MultiSpeed PSZ_MRI_CONTROL HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.19387
1732 Coil:Cooling:DX:MultiSpeed PSZ_MRI_CONTROL HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 9.69365E-002
1733 Coil:Cooling:DX:MultiSpeed PSZ_MRI_CONTROL HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.12925
1734 Coil:Cooling:DX:MultiSpeed PSZ_MRI_CONTROL HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 4054.94000
1735 Coil:Cooling:DX:MultiSpeed PSZ_MRI_CONTROL HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 2027.47000
1736 Coil:Cooling:DX:MultiSpeed PSZ_MRI_CONTROL HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.75898
1737 Coil:Cooling:DX:MultiSpeed PSZ_MRI_CONTROL HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.75898
1738 AirLoopHVAC:UnitarySystem PSZ_MRI_CONTROL_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 4054.94000
1739 AirLoopHVAC:UnitarySystem PSZ_MRI_CONTROL_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 2598.12131
1740 AirLoopHVAC:UnitarySystem PSZ_MRI_CONTROL_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 32.22000
1741 AirLoopHVAC:UnitarySystem PSZ_MRI_CONTROL_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 3877.79300
1742 AirLoopHVAC:UnitarySystem PSZ_MRI_CONTROL_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
1743 Coil:Heating:DX:MultiSpeed PSZ_MRI_CONTROL HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 0.19387
1744 Coil:Heating:DX:MultiSpeed PSZ_MRI_CONTROL HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 9.69365E-002
1745 Coil:Heating:DX:MultiSpeed PSZ_MRI_CONTROL HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 3877.79300
1746 Coil:Heating:DX:MultiSpeed PSZ_MRI_CONTROL HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 1938.89650
1747 Coil:Heating:DX:MultiSpeed PSZ_MRI_CONTROL HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
1748 Coil:Heating:Electric PSZ_MRI_CONTROL_SUPPHEATCOIL Design Size Nominal Capacity [W] 3877.79300
1749 Humidifier:Steam:Electric FLOOR 1 MRI CONTROL ROOM HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 3.42492E-007
1750 Humidifier:Steam:Electric FLOOR 1 MRI CONTROL ROOM HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
1751 Humidifier:Steam:Electric FLOOR 1 MRI CONTROL ROOM HUMIDIFIER Design Size Rated Power [W] 96450.69782
1752 Humidifier:Steam:Electric FLOOR 1 MRI CONTROL ROOM HUMIDIFIER User-Specified Rated Power [W] 100000.00000
1753 Controller:OutdoorAir PSZ_MRI_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.46484
1754 Controller:OutdoorAir PSZ_MRI_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.22970E-002
1755 Fan:SystemModel PSZ_MRI_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.46484
1756 Fan:SystemModel PSZ_MRI_ADDAQ FAN Design Electric Power Consumption [W] 799.34992
1757 AirLoopHVAC:UnitarySystem PSZ_MRI_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.46484
1758 AirLoopHVAC:UnitarySystem PSZ_MRI_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.46484
1759 AirLoopHVAC:UnitarySystem PSZ_MRI_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.46484
1760 AirLoopHVAC:UnitarySystem PSZ_MRI_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.46484
1761 Coil:Cooling:DX:MultiSpeed PSZ_MRI HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.46484
1762 Coil:Cooling:DX:MultiSpeed PSZ_MRI HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.23242
1763 Coil:Cooling:DX:MultiSpeed PSZ_MRI HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.30989
1764 Coil:Cooling:DX:MultiSpeed PSZ_MRI HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 9890.23000
1765 Coil:Cooling:DX:MultiSpeed PSZ_MRI HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 4945.11500
1766 Coil:Cooling:DX:MultiSpeed PSZ_MRI HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.75304
1767 Coil:Cooling:DX:MultiSpeed PSZ_MRI HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.75304
1768 AirLoopHVAC:UnitarySystem PSZ_MRI_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 9890.23000
1769 AirLoopHVAC:UnitarySystem PSZ_MRI_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 6336.33300
1770 AirLoopHVAC:UnitarySystem PSZ_MRI_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 32.22000
1771 AirLoopHVAC:UnitarySystem PSZ_MRI_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 9457.21343
1772 AirLoopHVAC:UnitarySystem PSZ_MRI_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
1773 Coil:Heating:DX:MultiSpeed PSZ_MRI HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 0.46484
1774 Coil:Heating:DX:MultiSpeed PSZ_MRI HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.23242
1775 Coil:Heating:DX:MultiSpeed PSZ_MRI HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 9457.21343
1776 Coil:Heating:DX:MultiSpeed PSZ_MRI HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 4728.60672
1777 Coil:Heating:DX:MultiSpeed PSZ_MRI HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
1778 Coil:Heating:Electric PSZ_MRI_SUPPHEATCOIL Design Size Nominal Capacity [W] 9457.21343
1779 Humidifier:Steam:Electric FLOOR 1 MRI ROOM HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 8.20835E-007
1780 Humidifier:Steam:Electric FLOOR 1 MRI ROOM HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
1781 Humidifier:Steam:Electric FLOOR 1 MRI ROOM HUMIDIFIER Design Size Rated Power [W] 96450.69782
1782 Humidifier:Steam:Electric FLOOR 1 MRI ROOM HUMIDIFIER User-Specified Rated Power [W] 100000.00000
1783 Controller:OutdoorAir PSZ_OR_1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.72361
1784 Controller:OutdoorAir PSZ_OR_1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.23881
1785 Fan:SystemModel PSZ_OR_1_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.72361
1786 Fan:SystemModel PSZ_OR_1_ADDAQ FAN Design Electric Power Consumption [W] 1244.34347
1787 AirLoopHVAC:UnitarySystem PSZ_OR_1_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.72361
1788 AirLoopHVAC:UnitarySystem PSZ_OR_1_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.72361
1789 AirLoopHVAC:UnitarySystem PSZ_OR_1_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.72361
1790 AirLoopHVAC:UnitarySystem PSZ_OR_1_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.72361
1791 Coil:Cooling:DX:MultiSpeed PSZ_OR_1 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.72361
1792 Coil:Cooling:DX:MultiSpeed PSZ_OR_1 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.36180
1793 Coil:Cooling:DX:MultiSpeed PSZ_OR_1 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.48241
1794 Coil:Cooling:DX:MultiSpeed PSZ_OR_1 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 17968.90000
1795 Coil:Cooling:DX:MultiSpeed PSZ_OR_1 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 8984.45000
1796 Coil:Cooling:DX:MultiSpeed PSZ_OR_1 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.70108
1797 Coil:Cooling:DX:MultiSpeed PSZ_OR_1 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.70108
1798 AirLoopHVAC:UnitarySystem PSZ_OR_1_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 17968.90000
1799 AirLoopHVAC:UnitarySystem PSZ_OR_1_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 12039.15965
1800 AirLoopHVAC:UnitarySystem PSZ_OR_1_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 29.21000
1801 AirLoopHVAC:UnitarySystem PSZ_OR_1_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 17968.89500
1802 AirLoopHVAC:UnitarySystem PSZ_OR_1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
1803 Coil:Heating:DX:MultiSpeed PSZ_OR_1 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 0.72361
1804 Coil:Heating:DX:MultiSpeed PSZ_OR_1 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.36180
1805 Coil:Heating:DX:MultiSpeed PSZ_OR_1 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 17968.89500
1806 Coil:Heating:DX:MultiSpeed PSZ_OR_1 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 8984.44750
1807 Coil:Heating:DX:MultiSpeed PSZ_OR_1 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
1808 Coil:Heating:Electric PSZ_OR_1_SUPPHEATCOIL Design Size Nominal Capacity [W] 17968.89500
1809 Humidifier:Steam:Electric FLOOR 1 OPERATING ROOM 1 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.27650E-006
1810 Humidifier:Steam:Electric FLOOR 1 OPERATING ROOM 1 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
1811 Humidifier:Steam:Electric FLOOR 1 OPERATING ROOM 1 HUMIDIFIER Design Size Rated Power [W] 96450.69782
1812 Humidifier:Steam:Electric FLOOR 1 OPERATING ROOM 1 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
1813 Controller:OutdoorAir PSZ_OR_2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.75507
1814 Controller:OutdoorAir PSZ_OR_2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.24919
1815 Fan:SystemModel PSZ_OR_2_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.75507
1816 Fan:SystemModel PSZ_OR_2_ADDAQ FAN Design Electric Power Consumption [W] 1298.44536
1817 AirLoopHVAC:UnitarySystem PSZ_OR_2_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.75507
1818 AirLoopHVAC:UnitarySystem PSZ_OR_2_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.75507
1819 AirLoopHVAC:UnitarySystem PSZ_OR_2_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.75507
1820 AirLoopHVAC:UnitarySystem PSZ_OR_2_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.75507
1821 Coil:Cooling:DX:MultiSpeed PSZ_OR_2 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.75507
1822 Coil:Cooling:DX:MultiSpeed PSZ_OR_2 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.37753
1823 Coil:Cooling:DX:MultiSpeed PSZ_OR_2 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.50338
1824 Coil:Cooling:DX:MultiSpeed PSZ_OR_2 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 18750.15000
1825 Coil:Cooling:DX:MultiSpeed PSZ_OR_2 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 9375.07500
1826 Coil:Cooling:DX:MultiSpeed PSZ_OR_2 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.70108
1827 Coil:Cooling:DX:MultiSpeed PSZ_OR_2 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.70108
1828 AirLoopHVAC:UnitarySystem PSZ_OR_2_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 18750.15000
1829 AirLoopHVAC:UnitarySystem PSZ_OR_2_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 12562.60138
1830 AirLoopHVAC:UnitarySystem PSZ_OR_2_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 29.21000
1831 AirLoopHVAC:UnitarySystem PSZ_OR_2_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 18750.15131
1832 AirLoopHVAC:UnitarySystem PSZ_OR_2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
1833 Coil:Heating:DX:MultiSpeed PSZ_OR_2 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 0.75507
1834 Coil:Heating:DX:MultiSpeed PSZ_OR_2 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.37753
1835 Coil:Heating:DX:MultiSpeed PSZ_OR_2 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 18750.15131
1836 Coil:Heating:DX:MultiSpeed PSZ_OR_2 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 9375.07565
1837 Coil:Heating:DX:MultiSpeed PSZ_OR_2 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
1838 Coil:Heating:Electric PSZ_OR_2_SUPPHEATCOIL Design Size Nominal Capacity [W] 18750.15131
1839 Humidifier:Steam:Electric FLOOR 1 OPERATING ROOM 2 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.33254E-006
1840 Humidifier:Steam:Electric FLOOR 1 OPERATING ROOM 2 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
1841 Humidifier:Steam:Electric FLOOR 1 OPERATING ROOM 2 HUMIDIFIER Design Size Rated Power [W] 96450.69782
1842 Humidifier:Steam:Electric FLOOR 1 OPERATING ROOM 2 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
1843 Controller:OutdoorAir PSZ_OR_3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.74878
1844 Controller:OutdoorAir PSZ_OR_3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.24711
1845 Fan:SystemModel PSZ_OR_3_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.74878
1846 Fan:SystemModel PSZ_OR_3_ADDAQ FAN Design Electric Power Consumption [W] 1287.62499
1847 AirLoopHVAC:UnitarySystem PSZ_OR_3_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.74878
1848 AirLoopHVAC:UnitarySystem PSZ_OR_3_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.74878
1849 AirLoopHVAC:UnitarySystem PSZ_OR_3_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.74878
1850 AirLoopHVAC:UnitarySystem PSZ_OR_3_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.74878
1851 Coil:Cooling:DX:MultiSpeed PSZ_OR_3 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.74878
1852 Coil:Cooling:DX:MultiSpeed PSZ_OR_3 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.37439
1853 Coil:Cooling:DX:MultiSpeed PSZ_OR_3 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.49919
1854 Coil:Cooling:DX:MultiSpeed PSZ_OR_3 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 18593.90000
1855 Coil:Cooling:DX:MultiSpeed PSZ_OR_3 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 9296.95000
1856 Coil:Cooling:DX:MultiSpeed PSZ_OR_3 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.70108
1857 Coil:Cooling:DX:MultiSpeed PSZ_OR_3 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.70108
1858 AirLoopHVAC:UnitarySystem PSZ_OR_3_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 18593.90000
1859 AirLoopHVAC:UnitarySystem PSZ_OR_3_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 12457.91303
1860 AirLoopHVAC:UnitarySystem PSZ_OR_3_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 29.21000
1861 AirLoopHVAC:UnitarySystem PSZ_OR_3_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 18593.90005
1862 AirLoopHVAC:UnitarySystem PSZ_OR_3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
1863 Coil:Heating:DX:MultiSpeed PSZ_OR_3 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 0.74878
1864 Coil:Heating:DX:MultiSpeed PSZ_OR_3 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.37439
1865 Coil:Heating:DX:MultiSpeed PSZ_OR_3 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 18593.90005
1866 Coil:Heating:DX:MultiSpeed PSZ_OR_3 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 9296.95002
1867 Coil:Heating:DX:MultiSpeed PSZ_OR_3 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
1868 Coil:Heating:Electric PSZ_OR_3_SUPPHEATCOIL Design Size Nominal Capacity [W] 18593.90005
1869 Humidifier:Steam:Electric FLOOR 1 OPERATING ROOM 3 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.32585E-006
1870 Humidifier:Steam:Electric FLOOR 1 OPERATING ROOM 3 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
1871 Humidifier:Steam:Electric FLOOR 1 OPERATING ROOM 3 HUMIDIFIER Design Size Rated Power [W] 96450.69782
1872 Humidifier:Steam:Electric FLOOR 1 OPERATING ROOM 3 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
1873 Controller:OutdoorAir PSZ_XRAY_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.06725
1874 Controller:OutdoorAir PSZ_XRAY_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.12743
1875 Fan:SystemModel PSZ_XRAY_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.06725
1876 Fan:SystemModel PSZ_XRAY_ADDAQ FAN Design Electric Power Consumption [W] 1773.77195
1877 AirLoopHVAC:UnitarySystem PSZ_XRAY_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.06725
1878 AirLoopHVAC:UnitarySystem PSZ_XRAY_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.06725
1879 AirLoopHVAC:UnitarySystem PSZ_XRAY_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.06725
1880 AirLoopHVAC:UnitarySystem PSZ_XRAY_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.06725
1881 Coil:Cooling:DX:MultiSpeed PSZ_XRAY HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.06725
1882 Coil:Cooling:DX:MultiSpeed PSZ_XRAY HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.53363
1883 Coil:Cooling:DX:MultiSpeed PSZ_XRAY HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.71150
1884 Coil:Cooling:DX:MultiSpeed PSZ_XRAY HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 22311.11000
1885 Coil:Cooling:DX:MultiSpeed PSZ_XRAY HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 11155.55500
1886 Coil:Cooling:DX:MultiSpeed PSZ_XRAY HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.75912
1887 Coil:Cooling:DX:MultiSpeed PSZ_XRAY HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.75912
1888 AirLoopHVAC:UnitarySystem PSZ_XRAY_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 22311.11000
1889 AirLoopHVAC:UnitarySystem PSZ_XRAY_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 14238.86607
1890 AirLoopHVAC:UnitarySystem PSZ_XRAY_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 32.22000
1891 AirLoopHVAC:UnitarySystem PSZ_XRAY_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 21252.03892
1892 AirLoopHVAC:UnitarySystem PSZ_XRAY_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
1893 Coil:Heating:DX:MultiSpeed PSZ_XRAY HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 1.06725
1894 Coil:Heating:DX:MultiSpeed PSZ_XRAY HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.53363
1895 Coil:Heating:DX:MultiSpeed PSZ_XRAY HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 21252.03892
1896 Coil:Heating:DX:MultiSpeed PSZ_XRAY HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 10626.01946
1897 Coil:Heating:DX:MultiSpeed PSZ_XRAY HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
1898 Coil:Heating:Electric PSZ_XRAY_SUPPHEATCOIL Design Size Nominal Capacity [W] 21252.03892
1899 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.16911E-003
1900 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.14029
1901 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.16911E-003
1902 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 352.08527
1903 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
1904 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 133636.71043
1905 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 133636.71000
1906 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.16911E-003
1907 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 6.31667E-005
1908 PlantLoop SWHSYS1 Plant Loop Volume [m3] 7.58000E-003
1909 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 6.31667E-005
1910 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 8.06887
1911 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 6.31667E-005


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL 2019.29
2 Coil:Heating:Water FLOOR 1 BIO HAZ VAV BOX REHEAT COIL 242.49
3 Coil:Heating:Water FLOOR 1 CLEAN VAV BOX REHEAT COIL 2188.04
4 Coil:Heating:Water FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL 2738.17
5 Coil:Heating:Water FLOOR 1 DICTATION VAV BOX REHEAT COIL 164.61
6 Coil:Heating:Water FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL 365.54
7 Coil:Heating:Water FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL 410.06
8 Coil:Heating:Water FLOOR 1 HUMID VAV BOX REHEAT COIL 81.60
9 Coil:Heating:Water FLOOR 1 IT HALL VAV BOX REHEAT COIL 297.57
10 Coil:Heating:Water FLOOR 1 IT ROOM VAV BOX REHEAT COIL 142.93
11 Coil:Heating:Water FLOOR 1 LOBBY VAV BOX REHEAT COIL 2350.13
12 Coil:Heating:Water FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL 543.33
13 Coil:Heating:Water FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL 945.28
14 Coil:Heating:Water FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL 2032.74
15 Coil:Heating:Water FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL 917.11
16 Coil:Heating:Water FLOOR 1 LOUNGE VAV BOX REHEAT COIL 1107.02
17 Coil:Heating:Water FLOOR 1 MED GAS VAV BOX REHEAT COIL 1147.22
18 Coil:Heating:Water FLOOR 1 MRI HALL VAV BOX REHEAT COIL 363.50
19 Coil:Heating:Water FLOOR 1 MRI TOILET VAV BOX REHEAT COIL 770.15
20 Coil:Heating:Water FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL 576.45
21 Coil:Heating:Water FLOOR 1 NURSE HALL VAV BOX REHEAT COIL 1020.91
22 Coil:Heating:Water FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL 128.66
23 Coil:Heating:Water FLOOR 1 NURSE STATION VAV BOX REHEAT COIL 762.54
24 Coil:Heating:Water FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL 728.75
25 Coil:Heating:Water FLOOR 1 OFFICE VAV BOX REHEAT COIL 512.46
26 Coil:Heating:Water FLOOR 1 PACU VAV BOX REHEAT COIL 1933.49
27 Coil:Heating:Water FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL 1047.56
28 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL 2672.05
29 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL 4778.59
30 Coil:Heating:Water FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL 798.27
31 Coil:Heating:Water FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL 10073.21
32 Coil:Heating:Water FLOOR 1 RECEPTION VAV BOX REHEAT COIL 1617.92
33 Coil:Heating:Water FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL 277.62
34 Coil:Heating:Water FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL 8766.66
35 Coil:Heating:Water FLOOR 1 SCHEDULING VAV BOX REHEAT COIL 156.85
36 Coil:Heating:Water FLOOR 1 SCRUB VAV BOX REHEAT COIL 219.28
37 Coil:Heating:Water FLOOR 1 SOIL VAV BOX REHEAT COIL 2186.43
38 Coil:Heating:Water FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL 1020.04
39 Coil:Heating:Water FLOOR 1 SOIL WORK VAV BOX REHEAT COIL 2904.41
40 Coil:Heating:Water FLOOR 1 STEP DOWN VAV BOX REHEAT COIL 4640.28
41 Coil:Heating:Water FLOOR 1 STERILE HALL VAV BOX REHEAT COIL 1173.96
42 Coil:Heating:Water FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL 660.90
43 Coil:Heating:Water FLOOR 1 STORAGE VAV BOX REHEAT COIL 9268.74
44 Coil:Heating:Water FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL 1559.72
45 Coil:Heating:Water FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL 2950.08
46 Coil:Heating:Water FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL 113.70
47 Coil:Heating:Water FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL 2670.33
48 Coil:Heating:Water FLOOR 1 VESTIBULE VAV BOX REHEAT COIL 329.72
49 Coil:Heating:Water FLOOR 2 CONFERENCE VAV BOX REHEAT COIL 3397.85
50 Coil:Heating:Water FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL 859.81
51 Coil:Heating:Water FLOOR 2 DICTATION VAV BOX REHEAT COIL 296.22
52 Coil:Heating:Water FLOOR 2 EXAM 1 VAV BOX REHEAT COIL 4687.89
53 Coil:Heating:Water FLOOR 2 EXAM 2 VAV BOX REHEAT COIL 7711.84
54 Coil:Heating:Water FLOOR 2 EXAM 3 VAV BOX REHEAT COIL 10281.87
55 Coil:Heating:Water FLOOR 2 EXAM 4 VAV BOX REHEAT COIL 1162.74
56 Coil:Heating:Water FLOOR 2 EXAM 5 VAV BOX REHEAT COIL 5859.54
57 Coil:Heating:Water FLOOR 2 EXAM 6 VAV BOX REHEAT COIL 3615.10
58 Coil:Heating:Water FLOOR 2 EXAM 7 VAV BOX REHEAT COIL 11194.31
59 Coil:Heating:Water FLOOR 2 EXAM 8 VAV BOX REHEAT COIL 4209.57
60 Coil:Heating:Water FLOOR 2 EXAM 9 VAV BOX REHEAT COIL 5918.14
61 Coil:Heating:Water FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL 828.46
62 Coil:Heating:Water FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL 728.81
63 Coil:Heating:Water FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL 721.46
64 Coil:Heating:Water FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL 732.31
65 Coil:Heating:Water FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL 743.64
66 Coil:Heating:Water FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL 756.53
67 Coil:Heating:Water FLOOR 2 JANITOR VAV BOX REHEAT COIL 865.16
68 Coil:Heating:Water FLOOR 2 LOUNGE VAV BOX REHEAT COIL 427.59
69 Coil:Heating:Water FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL 673.57
70 Coil:Heating:Water FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL 814.42
71 Coil:Heating:Water FLOOR 2 OFFICE VAV BOX REHEAT COIL 4758.03
72 Coil:Heating:Water FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL 1831.81
73 Coil:Heating:Water FLOOR 2 RECEPTION VAV BOX REHEAT COIL 6044.00
74 Coil:Heating:Water FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL 2116.93
75 Coil:Heating:Water FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL 1512.25
76 Coil:Heating:Water FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL 1117.82
77 Coil:Heating:Water FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL 1189.30
78 Coil:Heating:Water FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL 230.46
79 Coil:Heating:Water FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL 395.10
80 Coil:Heating:Water FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL 465.02
81 Coil:Heating:Water FLOOR 2 UTILITY VAV BOX REHEAT COIL 1455.30
82 Coil:Heating:Water FLOOR 2 WORK VAV BOX REHEAT COIL 4986.29
83 Coil:Heating:Water FLOOR 2 WORK HALL VAV BOX REHEAT COIL 3010.18
84 Coil:Heating:Water FLOOR 2 WORK TOILET VAV BOX REHEAT COIL 872.85
85 Coil:Heating:Water FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL 213.75
86 Coil:Heating:Water FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL 2327.83
87 Coil:Heating:Water FLOOR 3 HUMID VAV BOX REHEAT COIL 496.07
88 Coil:Heating:Water FLOOR 3 JANITOR VAV BOX REHEAT COIL 1181.64
89 Coil:Heating:Water FLOOR 3 LOCKER VAV BOX REHEAT COIL 672.62
90 Coil:Heating:Water FLOOR 3 LOUNGE VAV BOX REHEAT COIL 3874.52
91 Coil:Heating:Water FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL 3033.59
92 Coil:Heating:Water FLOOR 3 MECHANICAL VAV BOX REHEAT COIL 3300.75
93 Coil:Heating:Water FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL 1560.37
94 Coil:Heating:Water FLOOR 3 OFFICE VAV BOX REHEAT COIL 13613.58
95 Coil:Heating:Water FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL 3991.84
96 Coil:Heating:Water FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL 944.08
97 Coil:Heating:Water FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL 18497.86
98 Coil:Heating:Water FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL 7074.52
99 Coil:Heating:Water FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL 1114.12
100 Coil:Heating:Water FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL 1311.22
101 Coil:Heating:Water FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL 397.64
102 Coil:Heating:Water FLOOR 3 TREATMENT VAV BOX REHEAT COIL 5782.70
103 Coil:Heating:Water FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL 12770.76
104 Coil:Heating:Water FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL 9294.53
105 Coil:Heating:Water FLOOR 3 UTILITY VAV BOX REHEAT COIL 803.04
106 Coil:Heating:Water FLOOR 3 WORK VAV BOX REHEAT COIL 5966.88
107 Coil:Heating:Water NE STAIR VAV BOX REHEAT COIL 7271.49
108 Coil:Heating:Water NW ELEVATOR VAV BOX REHEAT COIL 4443.38
109 Coil:Heating:Water NW STAIR VAV BOX REHEAT COIL 7020.92
110 Coil:Heating:Water SW STAIR VAV BOX REHEAT COIL 3465.66
111 Coil:Heating:Water AHU-1 HEATING COIL 0.00
112 Coil:Heating:Water AHU-2 HEATING COIL 0.00
113 Coil:Heating:Water AHU-3 HEATING COIL 0.00


VAV DX Cooling Coil Standard Rating Information

DX Coil Type DX Coil Name Fan Type Fan Name Standard Net Cooling Capacity {W} Standard Net Cooling Capacity {Btu/h} IEER {Btu/W-h} COP 100% Capacity {W/W} COP 75% Capacity {W/W} COP 50% Capacity {W/W} COP 25% Capacity {W/W} EER 100% Capacity {Btu/W-h} EER 75% Capacity {Btu/W-h} EER 50% Capacity {Btu/W-h} EER 25% Capacity {Btu/W-h} Supply Air Flow 100% {kg/s} Supply Air Flow 75% {kg/s} Supply Air Flow 50% {kg/s} Supply Air Flow 25% {kg/s}
1 Coil:Cooling:DX:TwoSpeed AHU-1 COOLING COIL N/A N/A 133577.25 455784.50 11.69 3.09 3.34 3.54 3.70 10.53 11.39 12.09 12.61 6.4028 5.0670 3.3894 1.4371
2 Coil:Cooling:DX:TwoSpeed AHU-2 COOLING COIL N/A N/A 137156.31 467996.75 11.57 3.06 3.30 3.50 3.67 10.44 11.27 11.95 12.53 6.9915 5.5363 3.7180 1.5398
3 Coil:Cooling:DX:TwoSpeed AHU-3 COOLING COIL N/A N/A 133059.13 454016.60 11.61 3.07 3.31 3.52 3.68 10.47 11.30 11.99 12.55 6.6658 5.2856 3.5377 1.4756


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed PSZ_CAFE HP COOLING COIL 8639.0     9.73 9.73  
2 Coil:Cooling:DX:MultiSpeed PSZ_ELEVATOR HP COOLING COIL 1606.8     9.25 9.25  
3 Coil:Cooling:DX:MultiSpeed PSZ_MRI_CONTROL HP COOLING COIL 3902.5     9.51 9.51  
4 Coil:Cooling:DX:MultiSpeed PSZ_MRI HP COOLING COIL 9524.6     9.54 9.54  
5 Coil:Cooling:DX:MultiSpeed PSZ_OR_1 HP COOLING COIL 17398.0     9.73 9.73  
6 Coil:Cooling:DX:MultiSpeed PSZ_OR_2 HP COOLING COIL 18154.5     9.73 9.73  
7 Coil:Cooling:DX:MultiSpeed PSZ_OR_3 HP COOLING COIL 18003.2     9.73 9.73  
8 Coil:Cooling:DX:MultiSpeed PSZ_XRAY HP COOLING COIL 21471.8     10.59 10.59  


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:MultiSpeed PSZ_CAFE HEATING COIL 9211.1 5068.5 7.91 2
2 Coil:Heating:DX:MultiSpeed PSZ_ELEVATOR HEATING COIL 1676.1 933.5 7.83 2
3 Coil:Heating:DX:MultiSpeed PSZ_MRI_CONTROL HEATING COIL 4032.4 2232.0 7.87 2
4 Coil:Heating:DX:MultiSpeed PSZ_MRI HEATING COIL 9828.1 5437.2 7.74 2
5 Coil:Heating:DX:MultiSpeed PSZ_OR_1 HEATING COIL 18550.2 10207.4 7.90 2
6 Coil:Heating:DX:MultiSpeed PSZ_OR_2 HEATING COIL 19356.8 10651.2 7.87 2
7 Coil:Heating:DX:MultiSpeed PSZ_OR_3 HEATING COIL 19195.5 10562.4 7.88 2
8 Coil:Heating:DX:MultiSpeed PSZ_XRAY HEATING COIL 22103.1 12235.9 7.80 2


Zone Surfaces

Zone Name # Surfaces
1 FLOOR 1 ANESTHESIA 9
2 FLOOR 1 BIO HAZ 7
3 FLOOR 1 CAFE 9
4 FLOOR 1 CLEAN 10
5 FLOOR 1 CLEAN WORK 9
6 FLOOR 1 DICTATION 9
7 FLOOR 1 DRESSING ROOM 8
8 FLOOR 1 ELECTRICAL ROOM 7
9 FLOOR 1 ELEVATOR PUMP ROOM 10
10 FLOOR 1 HUMID 7
11 FLOOR 1 IT HALL 11
12 FLOOR 1 IT ROOM 7
13 FLOOR 1 LOBBY 20
14 FLOOR 1 LOBBY HALL 9
15 FLOOR 1 LOBBY TOILET 8
16 FLOOR 1 LOCKER ROOM 14
17 FLOOR 1 LOCKER ROOM HALL 18
18 FLOOR 1 LOUNGE 10
19 FLOOR 1 MED GAS 8
20 FLOOR 1 MRI CONTROL ROOM 11
21 FLOOR 1 MRI HALL 12
22 FLOOR 1 MRI ROOM 9
23 FLOOR 1 MRI TOILET 8
24 FLOOR 1 NOURISHMENT 13
25 FLOOR 1 NURSE HALL 17
26 FLOOR 1 NURSE JANITOR 8
27 FLOOR 1 NURSE STATION 12
28 FLOOR 1 NURSE TOILET 7
29 FLOOR 1 OFFICE 11
30 FLOOR 1 OPERATING ROOM 1 15
31 FLOOR 1 OPERATING ROOM 2 14
32 FLOOR 1 OPERATING ROOM 3 12
33 FLOOR 1 PACU 8
34 FLOOR 1 PRE-OP HALL 21
35 FLOOR 1 PRE-OP ROOM 1 10
36 FLOOR 1 PRE-OP ROOM 2 12
37 FLOOR 1 PRE-OP TOILET 7
38 FLOOR 1 PROCEDURE ROOM 13
39 FLOOR 1 RECEPTION 15
40 FLOOR 1 RECEPTION HALL 10
41 FLOOR 1 RECOVERY ROOM 17
42 FLOOR 1 SCHEDULING 9
43 FLOOR 1 SCRUB 7
44 FLOOR 1 SOIL 11
45 FLOOR 1 SOIL HOLD 8
46 FLOOR 1 SOIL WORK 11
47 FLOOR 1 STEP DOWN 15
48 FLOOR 1 STERILE HALL 25
49 FLOOR 1 STERILE STORAGE 12
50 FLOOR 1 STORAGE 18
51 FLOOR 1 SUB-STERILE 8
52 FLOOR 1 UTILITY HALL 15
53 FLOOR 1 UTILITY JANITOR 7
54 FLOOR 1 UTILITY ROOM 12
55 FLOOR 1 VESTIBULE 8
56 FLOOR 2 CONFERENCE 12
57 FLOOR 2 CONFERENCE TOILET 7
58 FLOOR 2 DICTATION 7
59 FLOOR 2 EXAM 1 15
60 FLOOR 2 EXAM 2 13
61 FLOOR 2 EXAM 3 18
62 FLOOR 2 EXAM 4 8
63 FLOOR 2 EXAM 5 10
64 FLOOR 2 EXAM 6 12
65 FLOOR 2 EXAM 7 18
66 FLOOR 2 EXAM 8 9
67 FLOOR 2 EXAM 9 10
68 FLOOR 2 EXAM HALL 1 11
69 FLOOR 2 EXAM HALL 2 11
70 FLOOR 2 EXAM HALL 3 13
71 FLOOR 2 EXAM HALL 4 12
72 FLOOR 2 EXAM HALL 5 11
73 FLOOR 2 EXAM HALL 6 12
74 FLOOR 2 JANITOR 7
75 FLOOR 2 LOUNGE 7
76 FLOOR 2 NURSE STATION 1 9
77 FLOOR 2 NURSE STATION 2 8
78 FLOOR 2 OFFICE 14
79 FLOOR 2 OFFICE HALL 22
80 FLOOR 2 RECEPTION 16
81 FLOOR 2 RECEPTION HALL 31
82 FLOOR 2 RECEPTION TOILET 8
83 FLOOR 2 SCHEDULING 1 10
84 FLOOR 2 SCHEDULING 2 10
85 FLOOR 2 STORAGE 1 7
86 FLOOR 2 STORAGE 2 9
87 FLOOR 2 STORAGE 3 7
88 FLOOR 2 UTILITY 8
89 FLOOR 2 WORK 25
90 FLOOR 2 WORK HALL 29
91 FLOOR 2 WORK TOILET 8
92 FLOOR 2 X-RAY 19
93 FLOOR 3 DRESSING ROOM 7
94 FLOOR 3 ELEVATOR HALL 11
95 FLOOR 3 HUMID 8
96 FLOOR 3 JANITOR 7
97 FLOOR 3 LOCKER 7
98 FLOOR 3 LOUNGE 16
99 FLOOR 3 LOUNGE TOILET 8
100 FLOOR 3 MECHANICAL 9
101 FLOOR 3 MECHANICAL HALL 11
102 FLOOR 3 OFFICE 24
103 FLOOR 3 OFFICE HALL 15
104 FLOOR 3 OFFICE TOILET 8
105 FLOOR 3 PHYSICAL THERAPY 1 22
106 FLOOR 3 PHYSICAL THERAPY 2 15
107 FLOOR 3 PHYSICAL THERAPY TOILET 7
108 FLOOR 3 STORAGE 1 7
109 FLOOR 3 STORAGE 2 7
110 FLOOR 3 TREATMENT 10
111 FLOOR 3 UNDEVELOPED 1 21
112 FLOOR 3 UNDEVELOPED 2 14
113 FLOOR 3 UTILITY 7
114 FLOOR 3 WORK 13
115 NE STAIR 19
116 NW ELEVATOR 13
117 NW STAIR 15
118 SW STAIR 13


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 4161C8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 B3A518 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 1AD133 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 114EC6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 330DF9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 66B6F7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 481E71 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   6.13 8.36 6.13 180.00 90.00 2.74 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
5 78F987 Window 481E71 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
6 FLOOR 1 ANESTHESIA SLAB Floor   CTF - ConductionTransferFunction FLOOR1ANESTHESIASLAB_FFACTOR 0.365 0.335   10.03 10.03 10.03 0.00 180.00 2.74 3.66 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
7 DDCF3E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2.23 2.23 2.23 90.00 0.00 3.66 0.61 0.00 A08A28 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BE1AE1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 270.00 0.00 3.66 2.13 0.00 4E78E0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 FLOOR 1 ANESTHESIA_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   20.07 20.07 20.07 0.00 90.00 20.07 1.00 0.00 FLOOR 1 ANESTHESIA_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
10 70DAD1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 A1087A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
11 32CC19 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 DEFACF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
12 BBEE0B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 19D150 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
13 F951A6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 5D9E95 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 FLOOR 1 BIO HAZ SLAB Floor   CTF - ConductionTransferFunction FLOOR1BIOHAZSLAB_FFACTOR 5.650E-003 5.642E-003   5.20 5.20 5.20 0.00 180.00 2.13 2.44 0.00 FLOOR 1 BIO HAZ SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
15 F6F6C6 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.20 5.20 5.20 0.00 0.00 2.13 2.44 0.00 F67EC8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
16 FLOOR 1 BIO HAZ_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.41 10.41 10.41 0.00 90.00 10.41 1.00 0.00 FLOOR 1 BIO HAZ_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
17 5F762C Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   9.66 18.58 9.66 180.00 90.00 6.10 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
18 D8037E Window 5F762C Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 8.92 8.92 8.92 180.00 90.00 3.66 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
19 4507E9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 0.00 90.00 6.10 3.05 0.00 A6D45E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 C48E94 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.08 12.08 12.08 270.00 90.00 3.96 3.05 0.00 3145CA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
21 6B31A8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   19.51 19.51 19.51 90.00 90.00 6.40 3.05 0.00 7BB928 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 368E02 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 8FF821 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 FLOOR 1 CAFE SLAB Floor   CTF - ConductionTransferFunction FLOOR1CAFESLAB_FFACTOR 0.204 0.194   39.02 39.02 39.02 90.00 180.00 6.40 6.10 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 4783F2 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   39.02 39.02 39.02 90.00 0.00 6.40 6.10 0.00 39BFFB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 FLOOR 1 CAFE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 FLOOR 1 CAFE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 EA8FA7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 EE0803 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 FE7511 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 8BB36F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 59E0E4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 270.00 90.00 4.27 3.05 0.00 855191 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 7949FA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 90.00 90.00 4.27 3.05 0.00 86244A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 FLOOR 1 CLEAN SLAB Floor   CTF - ConductionTransferFunction FLOOR1CLEANSLAB_FFACTOR 5.650E-003 5.642E-003   11.71 11.71 11.71 90.00 180.00 4.27 2.74 0.00 FLOOR 1 CLEAN SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 EC2478 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.46 0.46 0.46 90.00 0.00 0.30 1.52 0.00 75EAF8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 1B4EDC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.37 0.37 0.37 0.00 0.00 1.22 0.30 0.00 EB611D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
33 D1AFC9 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.85 5.85 5.85 180.00 0.00 2.74 2.13 0.00 1CC550 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
34 442699 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 0.00 0.00 2.74 1.83 0.00 2FE383 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
35 FLOOR 1 CLEAN_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   23.41 23.41 23.41 0.00 90.00 23.41 1.00 0.00 FLOOR 1 CLEAN_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
36 FD8CF2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 808817 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
37 49DA86 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.22 10.22 10.22 270.00 90.00 3.35 3.05 0.00 6B967C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
38 619EE6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.22 10.22 10.22 90.00 90.00 3.35 3.05 0.00 A809DD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
39 B551AD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 121DFF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
40 FLOOR 1 CLEAN WORK SLAB Floor   CTF - ConductionTransferFunction FLOOR1CLEANWORKSLAB_FFACTOR 5.650E-003 5.642E-003   15.33 15.33 15.33 180.00 180.00 4.57 3.35 0.00 FLOOR 1 CLEAN WORK SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
41 8E9267 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.50 6.50 6.50 270.00 0.00 2.13 3.05 0.00 EF47B0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
42 BB097B Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.25 3.25 3.25 180.00 0.00 1.52 2.13 0.00 774CCD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
43 2E1FB7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.57 5.57 5.57 270.00 0.00 1.22 4.57 0.00 A5FA3B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
44 FLOOR 1 CLEAN WORK_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   30.66 30.66 30.66 0.00 90.00 30.66 1.00 0.00 FLOOR 1 CLEAN WORK_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
45 94A56A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 8043B2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 4A854B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 90.00 90.00 4.27 3.05 0.00 ACADA4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
47 8594D3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 A2F014 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
48 86244A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 270.00 90.00 4.27 3.05 0.00 7949FA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
49 FLOOR 1 DICTATION SLAB Floor   CTF - ConductionTransferFunction FLOOR1DICTATIONSLAB_FFACTOR 5.650E-003 5.642E-003   11.71 11.71 11.71 0.00 180.00 2.74 4.27 0.00 FLOOR 1 DICTATION SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
50 672F1E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.84 0.84 0.84 0.00 0.00 2.74 0.30 0.00 9B49F5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
51 A7115C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.85 5.85 5.85 180.00 0.00 2.74 2.13 0.00 5D03DA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
52 AF27F8 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 0.00 0.00 2.74 1.83 0.00 3F961C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 FLOOR 1 DICTATION_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   23.41 23.41 23.41 0.00 90.00 23.41 1.00 0.00 FLOOR 1 DICTATION_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 256F02 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 90.00 90.00 1.52 3.05 0.00 4ED109 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
55 DE027F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 270.00 90.00 1.52 3.05 0.00 1EC3A0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
56 84FB73 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   6.04 8.36 6.04 0.00 90.00 2.74 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
57 4A8120 Window 84FB73 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.32 2.32 2.32 0.00 90.00 1.52 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.56 0.44 4
58 CC17E8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 A8DB72 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 FLOOR 1 DRESSING ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1DRESSINGROOMSLAB_FFACTOR 0.951 0.773   4.18 4.18 4.18 0.00 180.00 2.74 1.52 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
60 5DACB5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.18 4.18 4.18 0.00 0.00 2.74 1.52 0.00 541C9C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
61 FLOOR 1 DRESSING ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   8.36 8.36 8.36 0.00 90.00 8.36 1.00 0.00 FLOOR 1 DRESSING ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
62 9879B2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 2E8328 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 2D53AC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 964F72 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
64 7F5C82 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 E82152 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 EC28A9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
66 FLOOR 1 ELECTRICAL ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1ELECTRICALROOMSLAB_FFACTOR 0.310 0.289   9.10 9.10 9.10 0.00 180.00 4.27 2.13 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
67 D7AC92 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.10 9.10 9.10 0.00 0.00 4.27 2.13 0.00 65AB67 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
68 FLOOR 1 ELECTRICAL ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   18.21 18.21 18.21 0.00 90.00 18.21 1.00 0.00 FLOOR 1 ELECTRICAL ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
69 F99476 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 F23EB6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
70 C732B0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   12.08 12.08 12.08 0.00 90.00 3.96 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.61 0.39 4
71 9926F7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 6FB351 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 E02487 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   4.55 6.50 4.55 270.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 BA05F7 Door E02487 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
74 B45B50 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   3.72 3.72 3.72 180.00 90.00 1.22 3.05 0.00 5D8FAF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 FLOOR 1 ELEVATOR PUMP ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1ELEVATORPUMPROOMSLAB_FFACTOR 1.061 0.843   8.45 8.45 8.45 180.00 180.00 3.96 2.13 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
76 DF9D5D Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.85 5.85 5.85 90.00 0.00 2.13 2.74 0.00 5B736E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
77 827528 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2.60 2.60 2.60 270.00 0.00 2.13 1.22 0.00 1A8E2A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
78 FLOOR 1 ELEVATOR PUMP ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   16.91 16.91 16.91 0.00 90.00 16.91 1.00 0.00 FLOOR 1 ELEVATOR PUMP ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
79 758B3C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 863C6C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 A7F46C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 725D3E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 3F71D3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 E1B4BB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
82 8BB36F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 FE7511 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
83 FLOOR 1 HUMID SLAB Floor   CTF - ConductionTransferFunction FLOOR1HUMIDSLAB_FFACTOR 5.650E-003 5.642E-003   5.02 5.02 5.02 0.00 180.00 2.74 1.83 0.00 FLOOR 1 HUMID SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
84 D21333 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 0.00 0.00 2.74 1.83 0.00 55622A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
85 FLOOR 1 HUMID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 1 HUMID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 FEC1E3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 180.00 90.00 8.53 3.05 0.00 AE206C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
87 5D9E95 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 F951A6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 F4D6DD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 90.00 90.00 1.52 3.05 0.00 20FB14 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
89 FB87D3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 270.00 90.00 1.52 3.05 0.00 3E6044 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 445A39 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 9A776E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 3A6904 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 2CF0AA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 FLOOR 1 IT HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1ITHALLSLAB_FFACTOR 5.650E-003 5.642E-003   13.01 13.01 13.01 180.00 180.00 8.53 1.52 0.00 FLOOR 1 IT HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 FB17DD Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.25 3.25 3.25 270.00 0.00 1.52 2.13 0.00 1624C5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 8A2F34 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2.79 2.79 2.79 270.00 0.00 1.52 1.83 0.00 4AA9BC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
95 9A5B84 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.97 6.97 6.97 90.00 0.00 1.52 4.57 0.00 40E182 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
96 FLOOR 1 IT HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   26.01 26.01 26.01 0.00 90.00 26.01 1.00 0.00 FLOOR 1 IT HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
97 2CF0AA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 3A6904 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 307901 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 897BAF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
99 FA769A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 41CE25 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 319A6B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 5B533A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 FLOOR 1 IT ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1ITROOMSLAB_FFACTOR 5.650E-003 5.642E-003   10.41 10.41 10.41 90.00 180.00 2.44 4.27 0.00 FLOOR 1 IT ROOM SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 C732D4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.41 10.41 10.41 90.00 0.00 2.44 4.27 0.00 8D6453 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 FLOOR 1 IT ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   20.81 20.81 20.81 0.00 90.00 20.81 1.00 0.00 FLOOR 1 IT ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 822161 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 FA9233 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 43A2A2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 270.00 90.00 6.10 3.05 0.00 976E3F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 6FB351 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 9926F7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 8134C2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 0.00 90.00 0.61 3.05 0.00 88CB69 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 102EC4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 9FF31D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 BAD27A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 1068C8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 5D8FAF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   3.72 3.72 3.72 0.00 90.00 1.22 3.05 0.00 B45B50 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 46E87C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 BFD4BB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
112 3145CA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.08 12.08 12.08 90.00 90.00 3.96 3.05 0.00 C48E94 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
113 73E892 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 180.00 90.00 0.61 3.05 0.00 F3084E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
114 4418C4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 E5BC3F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 FE5A3C Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   9.57 20.44 9.57 270.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.58 0.42 4
116 AAE778 Window FE5A3C Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_WEST_0.25 N/A 6.926 No 8.92 8.92 8.92 270.00 90.00 3.66 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
117 F67E1F Door FE5A3C CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
118 4911A5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 72A819 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
119 FLOOR 1 LOBBY SLAB Floor   CTF - ConductionTransferFunction FLOOR1LOBBYSLAB_FFACTOR 0.150 0.145   57.79 57.79 57.79 90.00 180.00 7.60 7.60 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 10
120 D647E0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.69 6.69 6.69 180.00 0.00 3.66 1.83 0.00 CAC621 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
121 BFB8E1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   33.26 33.26 33.26 180.00 0.00 5.77 5.77 0.00 517DFC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
122 78FEE8 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   17.84 17.84 17.84 270.00 0.00 4.88 3.66 0.00 167608 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
123 FLOOR 1 LOBBY_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   115.57 115.57 115.57 0.00 90.00 115.57 1.00 0.00 FLOOR 1 LOBBY_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
124 A6D45E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 180.00 90.00 6.10 3.05 0.00 4507E9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 F7F8BA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 234734 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 34019D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 0.00 90.00 6.10 3.05 0.00 867BBB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
127 72A819 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 4911A5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
128 FLOOR 1 LOBBY HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1LOBBYHALLSLAB_FFACTOR 5.650E-003 5.642E-003   22.30 22.30 22.30 0.00 180.00 6.10 3.66 0.00 FLOOR 1 LOBBY HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
129 D60B94 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.15 11.15 11.15 180.00 0.00 6.10 1.83 0.00 E90253 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
130 B7E9B3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.57 5.57 5.57 180.00 0.00 6.10 0.91 0.00 5724CC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
131 690A91 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.57 5.57 5.57 0.00 0.00 6.10 0.91 0.00 FA00FE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
132 FLOOR 1 LOBBY HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   44.59 44.59 44.59 0.00 90.00 44.59 1.00 0.00 FLOOR 1 LOBBY HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
133 9FF31D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 102EC4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 9D87EC Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
135 F23EB6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 F99476 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
136 7F6FC2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 D699FF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
137 88CB69 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 180.00 90.00 0.61 3.05 0.00 8134C2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
138 FLOOR 1 LOBBY TOILET SLAB Floor   CTF - ConductionTransferFunction FLOOR1LOBBYTOILETSLAB_FFACTOR 0.496 0.443   5.02 5.02 5.02 0.00 180.00 2.74 1.83 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
139 9BB388 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 0.00 0.00 2.74 1.83 0.00 4C4C25 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
140 FLOOR 1 LOBBY TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 1 LOBBY TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
141 E9F3F6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 270.00 90.00 4.57 3.05 0.00 704EC3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
142 A9C27A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 180.00 90.00 6.71 3.05 0.00 8D03E8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
143 F629C1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   14.86 20.44 14.86 0.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
144 3AAD8B Window F629C1 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.59 0.41 4
145 8128A9 Window F629C1 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
146 962DB5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 90.00 90.00 9.14 3.05 0.00 761D33 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 92E22C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 270.00 90.00 4.57 3.05 0.00 EAACE4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 FLOOR 1 LOCKER ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1LOCKERROOMSLAB_FFACTOR 0.141 0.137   61.32 61.32 61.32 270.00 180.00 9.14 6.71 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
149 7B1677 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   8.36 8.36 8.36 270.00 0.00 9.14 0.91 0.00 772953 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
150 21C5E8 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   25.08 25.08 25.08 180.00 0.00 5.49 4.57 0.00 A9A1F6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
151 FDCEC5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2.79 2.79 2.79 90.00 0.00 9.14 0.30 0.00 EC3BEA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 C1F15F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 180.00 0.00 5.49 2.44 0.00 1E3410 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
153 1E6611 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.71 11.71 11.71 0.00 0.00 5.49 2.13 0.00 9EADD8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
154 FLOOR 1 LOCKER ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   122.63 122.63 122.63 0.00 90.00 122.63 1.00 0.00 FLOOR 1 LOCKER ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
155 35028C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 88AE01 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 852027 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 592524 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
157 EBFE47 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 0.00 90.00 8.53 3.05 0.00 FD0958 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 D9965C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.08 12.08 12.08 180.00 90.00 3.96 3.05 0.00 7AE5B9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
159 71783C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 C0F51F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
160 D8C098 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 4E3BB5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
161 66D163 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 180.00 90.00 10.06 3.05 0.00 1003C1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
162 8D03E8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 A9C27A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
163 9A0DF2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 18AFE3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
164 FLOOR 1 LOCKER ROOM HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1LOCKERROOMHALLSLAB_FFACTOR 5.650E-003 5.642E-003   46.08 46.08 46.08 180.00 180.00 18.90 2.44 0.00 FLOOR 1 LOCKER ROOM HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
165 1891E7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.95 1.95 1.95 270.00 0.00 0.91 2.13 0.00 5A7EAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
166 BD75DE Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   28.80 28.80 28.80 270.00 0.00 1.52 18.90 0.00 FFE9D0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
167 3137C4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.67 1.67 1.67 270.00 0.00 0.91 1.83 0.00 C2156D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
168 C8F2F1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.69 6.69 6.69 180.00 0.00 7.32 0.91 0.00 37898A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
169 6B171C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.67 1.67 1.67 180.00 0.00 1.83 0.91 0.00 E0C60A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
170 86C171 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 270.00 0.00 0.91 5.49 0.00 DE8843 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
171 C605B5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.28 0.28 0.28 90.00 0.00 0.91 0.30 0.00 5F9E13 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 FLOOR 1 LOCKER ROOM HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   92.16 92.16 92.16 0.00 90.00 92.16 1.00 0.00 FLOOR 1 LOCKER ROOM HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
173 18AFE3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 9A0DF2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
174 761D33 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 270.00 90.00 9.14 3.05 0.00 962DB5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
175 9C0202 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 891195 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
176 29BD5F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   15.79 15.79 15.79 90.00 90.00 5.18 3.05 0.00 9E12D4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 897BAF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 307901 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 3E6044 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 90.00 90.00 1.52 3.05 0.00 FB87D3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
179 FLOOR 1 LOUNGE SLAB Floor   CTF - ConductionTransferFunction FLOOR1LOUNGESLAB_FFACTOR 5.650E-003 5.642E-003   33.45 33.45 33.45 180.00 180.00 3.66 9.14 0.00 FLOOR 1 LOUNGE SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 7B9EEC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   25.08 25.08 25.08 270.00 0.00 9.14 2.74 0.00 A6147C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
181 B04E85 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   8.36 8.36 8.36 90.00 0.00 9.14 0.91 0.00 15A02B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
182 FLOOR 1 LOUNGE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   66.89 66.89 66.89 0.00 90.00 66.89 1.00 0.00 FLOOR 1 LOUNGE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
183 A4B378 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 89BBEB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 72BCFE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 8B4DC1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 E85BB5 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   5.48 7.43 5.48 0.00 90.00 2.44 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 7EB6E7 Door E85BB5 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 577FC1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.58 0.42 4
188 FLOOR 1 MED GAS SLAB Floor   CTF - ConductionTransferFunction FLOOR1MEDGASSLAB_FFACTOR 1.341 1.012   5.20 5.20 5.20 180.00 180.00 2.44 2.13 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 FLOOR 1 MED GAS ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   5.20 5.20 5.20 180.00 0.00 2.44 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.15 0.85 4
190 FLOOR 1 MED GAS_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.41 10.41 10.41 0.00 90.00 10.41 1.00 0.00 FLOOR 1 MED GAS_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
191 F0B690 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 A78253 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 D2C53A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 90.00 90.00 0.91 3.05 0.00 27B0D7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BFD4BB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 46E87C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 C114C1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   2.69 4.65 2.69 0.00 90.00 1.52 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.67 0.33 4
195 D18914 Door C114C1 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.68 0.32 4
196 92A2CB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 0.00 90.00 4.88 3.05 0.00 74AB49 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
197 1EC3A0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 90.00 90.00 1.52 3.05 0.00 DE027F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
198 E66ECE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 180.00 90.00 0.91 3.05 0.00 90FDA9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
199 FLOOR 1 MRI CONTROL ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1MRICONTROLROOMSLAB_FFACTOR 0.126 0.122   15.61 15.61 15.61 180.00 180.00 6.40 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
200 290CAB Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   15.61 15.61 15.61 90.00 0.00 2.44 6.40 0.00 CEC6B4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
201 FLOOR 1 MRI CONTROL ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   31.22 31.22 31.22 0.00 90.00 31.22 1.00 0.00 FLOOR 1 MRI CONTROL ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
202 824665 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 E20721 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
203 68F53B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 E608B9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
204 27B0D7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 270.00 90.00 0.91 3.05 0.00 D2C53A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
205 90FDA9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 0.00 90.00 0.91 3.05 0.00 E66ECE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
206 91DE28 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 BA91C7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
207 A8DB72 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 CC17E8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
208 8A30DD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   3.72 3.72 3.72 90.00 90.00 1.22 3.05 0.00 24139C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
209 596DE0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 C9D24D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
210 B92155 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 180.00 90.00 3.05 3.05 0.00 4E24F1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
211 FLOOR 1 MRI HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1MRIHALLSLAB_FFACTOR 5.650E-003 5.642E-003   13.66 13.66 13.66 180.00 180.00 3.70 3.70 0.00 FLOOR 1 MRI HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 8
212 5CB500 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.66 13.66 13.66 180.00 0.00 3.70 3.70 0.00 1A95D5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 8
213 FLOOR 1 MRI HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   27.31 27.31 27.31 0.00 90.00 27.31 1.00 0.00 FLOOR 1 MRI HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
214 2FAF44 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 90.00 90.00 4.57 3.05 0.00 6EA718 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
215 A78253 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 F0B690 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
216 E5BC3F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 4418C4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
217 867BBB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 180.00 90.00 6.10 3.05 0.00 34019D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
218 F3084E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 0.00 90.00 0.61 3.05 0.00 73E892 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
219 BA91C7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 91DE28 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
220 FLOOR 1 MRI ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1MRIROOMSLAB_FFACTOR 5.650E-003 5.642E-003   40.88 40.88 40.88 90.00 180.00 6.71 6.10 0.00 FLOOR 1 MRI ROOM SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
221 803791 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   40.88 40.88 40.88 90.00 0.00 6.71 6.10 0.00 E43750 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
222 FLOOR 1 MRI ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   81.75 81.75 81.75 0.00 90.00 81.75 1.00 0.00 FLOOR 1 MRI ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
223 ADB8D0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
224 30DB21 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 95486C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 C9D24D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 596DE0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 4ED109 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 270.00 90.00 1.52 3.05 0.00 256F02 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 24139C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   3.72 3.72 3.72 270.00 90.00 1.22 3.05 0.00 8A30DD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 FLOOR 1 MRI TOILET SLAB Floor   CTF - ConductionTransferFunction FLOOR1MRITOILETSLAB_FFACTOR 0.496 0.443   5.02 5.02 5.02 90.00 180.00 2.74 1.83 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
229 388F10 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 90.00 0.00 2.74 1.83 0.00 E21951 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
230 FLOOR 1 MRI TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 1 MRI TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
231 855191 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 90.00 90.00 4.27 3.05 0.00 59E0E4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 C0F51F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 71783C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
233 A59907 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 A452BE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
234 28DE5A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.15 24.15 24.15 270.00 90.00 7.92 3.05 0.00 551E65 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
235 58B6B6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 D9F81F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
236 725D3E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 A7F46C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
237 FLOOR 1 NOURISHMENT SLAB Floor   CTF - ConductionTransferFunction FLOOR1NOURISHMENTSLAB_FFACTOR 5.650E-003 5.642E-003   16.91 16.91 16.91 270.00 180.00 7.92 2.13 0.00 FLOOR 1 NOURISHMENT SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
238 4E5019 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.65 0.65 0.65 180.00 0.00 2.13 0.30 0.00 21F419 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
239 E8F02D Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.56 0.56 0.56 90.00 0.00 0.30 1.83 0.00 E3B855 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
240 6ECCF3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.29E-002 9.29E-002 9.29E-002 0.00 0.00 0.30 0.30 0.00 BD39AC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
241 AA1F5C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.90 3.90 3.90 0.00 0.00 2.13 1.83 0.00 4FA380 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
242 F665B1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.71 11.71 11.71 270.00 0.00 5.49 2.13 0.00 C6DCD1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
243 FLOOR 1 NOURISHMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   33.82 33.82 33.82 0.00 90.00 33.82 1.00 0.00 FLOOR 1 NOURISHMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
244 6822BB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 5FD018 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
245 825233 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 23683B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
246 86A28D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 BABBB4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
247 C92A6E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 44686F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
248 114EC6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 1AD133 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
249 9EB05A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 E5CB03 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
250 7434CD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 F740DF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
251 344D34 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.94 26.94 26.94 0.00 90.00 8.84 3.05 0.00 4A07CD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
252 59CEFB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.81 41.81 41.81 180.00 90.00 13.72 3.05 0.00 72C4ED Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
253 FLOOR 1 NURSE HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1NURSEHALLSLAB_FFACTOR 5.650E-003 5.642E-003   46.08 46.08 46.08 270.00 180.00 2.44 18.90 0.00 FLOOR 1 NURSE HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
254 C75191 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.74 0.74 0.74 90.00 0.00 2.44 0.30 0.00 526C70 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
255 92E327 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 0.00 0.00 5.49 2.44 0.00 CCAA9D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
256 7F6B1B Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   17.84 17.84 17.84 90.00 0.00 2.44 7.32 0.00 BA0A29 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
257 4A49C1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 90.00 0.00 2.44 1.83 0.00 243E09 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
258 8F5FFC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 0.00 0.00 1.83 2.44 0.00 BAE3F8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
259 DDBA1E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.20 5.20 5.20 270.00 0.00 2.44 2.13 0.00 A3E3D6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
260 FLOOR 1 NURSE HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   92.16 92.16 92.16 0.00 90.00 92.16 1.00 0.00 FLOOR 1 NURSE HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
261 4E3BB5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 D8C098 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
262 415590 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 96662A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
263 D9F81F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 58B6B6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
264 E1B4BB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 3F71D3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
265 FLOOR 1 NURSE JANITOR SLAB Floor   CTF - ConductionTransferFunction FLOOR1NURSEJANITORSLAB_FFACTOR 5.650E-003 5.642E-003   5.02 5.02 5.02 180.00 180.00 2.74 1.83 0.00 FLOOR 1 NURSE JANITOR SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
266 2CB843 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.84 0.84 0.84 180.00 0.00 2.74 0.30 0.00 C5B569 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
267 E2AB17 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.18 4.18 4.18 0.00 0.00 2.74 1.52 0.00 AE5078 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
268 FLOOR 1 NURSE JANITOR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 1 NURSE JANITOR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
269 464A53 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 BA8FF7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
270 FE5062 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 FCD8D2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
271 4A07CD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.94 26.94 26.94 180.00 90.00 8.84 3.05 0.00 344D34 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
272 EE0803 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 EA8FA7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
273 DFDE4F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.08 12.08 12.08 0.00 90.00 3.96 3.05 0.00 8C3884 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
274 A452BE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 A59907 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
275 FLOOR 1 NURSE STATION SLAB Floor   CTF - ConductionTransferFunction FLOOR1NURSESTATIONSLAB_FFACTOR 5.650E-003 5.642E-003   24.25 24.25 24.25 180.00 180.00 8.84 2.74 0.00 FLOOR 1 NURSE STATION SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
276 BD4B70 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.84 0.84 0.84 90.00 0.00 2.74 0.30 0.00 3AE495 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
277 A0117C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   15.05 15.05 15.05 90.00 0.00 2.74 5.49 0.00 4579A7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
278 52F395 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.34 3.34 3.34 270.00 0.00 2.74 1.22 0.00 BD5B50 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
279 AA2E8F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 90.00 0.00 2.74 1.83 0.00 C94CC0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
280 FLOOR 1 NURSE STATION_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   48.50 48.50 48.50 0.00 90.00 48.50 1.00 0.00 FLOOR 1 NURSE STATION_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
281 CA6EDA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 446771 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
282 5EB34C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 9E478E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
283 5CD67D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 FAE342 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
284 E5CB03 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 9EB05A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
285 FLOOR 1 NURSE TOILET SLAB Floor   CTF - ConductionTransferFunction FLOOR1NURSETOILETSLAB_FFACTOR 5.650E-003 5.642E-003   5.02 5.02 5.02 180.00 180.00 1.83 2.74 0.00 FLOOR 1 NURSE TOILET SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
286 156F92 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 180.00 0.00 1.83 2.74 0.00 75A3C4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
287 FLOOR 1 NURSE TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 1 NURSE TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
288 361D65 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.22 10.22 10.22 0.00 90.00 3.35 3.05 0.00 EAE60F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
289 2B5816 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 90.00 90.00 7.01 3.05 0.00 33A280 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
290 7B67EC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 180.00 90.00 1.52 3.05 0.00 25AB11 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
291 7E0561 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 270.00 90.00 7.01 3.05 0.00 2730E5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
292 4E24F1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 0.00 90.00 3.05 3.05 0.00 B92155 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
293 8259AE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 180.00 90.00 4.88 3.05 0.00 CD7BAD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
294 FLOOR 1 OFFICE SLAB Floor   CTF - ConductionTransferFunction FLOOR1OFFICESLAB_FFACTOR 5.650E-003 5.642E-003   44.87 44.87 44.87 0.00 180.00 6.40 7.01 0.00 FLOOR 1 OFFICE SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
295 B754EC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.75 9.75 9.75 0.00 0.00 6.40 1.52 0.00 F5C927 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
296 621A74 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   15.05 15.05 15.05 270.00 0.00 5.49 2.74 0.00 87C477 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
297 28F0DE Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 90.00 0.00 5.49 3.66 0.00 CE626A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
298 FLOOR 1 OFFICE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   89.74 89.74 89.74 0.00 90.00 89.74 1.00 0.00 FLOOR 1 OFFICE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
299 879583 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   14.12 18.58 14.12 180.00 90.00 6.10 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
300 9B1541 Window 879583 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
301 CF850A Window 879583 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
302 83A098 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 270.00 90.00 7.01 3.05 0.00 E77E00 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
303 E326E4 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   13.46 21.37 13.46 90.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
304 A6BA23 Window E326E4 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
305 D10D28 Window E326E4 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
306 D4B39B Door E326E4 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
307 575A7B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 196C5F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
308 7E9E26 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 9DB411 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
309 FLOOR 1 OPERATING ROOM 1 SLAB Floor   CTF - ConductionTransferFunction FLOOR1OPERATINGROOM1SLAB_FFACTOR 0.412 0.375   42.74 42.74 42.74 0.00 180.00 6.10 7.01 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
310 E648BC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   22.30 22.30 22.30 0.00 0.00 6.10 3.66 0.00 2BD1E8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
311 FFE052 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   14.31 14.31 14.31 270.00 0.00 3.35 4.27 0.00 64A2F7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
312 611A3F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.13 6.13 6.13 90.00 0.00 3.35 1.83 0.00 874DF8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
313 FLOOR 1 OPERATING ROOM 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   85.47 85.47 85.47 0.00 90.00 85.47 1.00 0.00 FLOOR 1 OPERATING ROOM 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
314 9C6F66 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 816F6D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
315 1D96D7 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   13.37 22.30 13.37 90.00 90.00 7.32 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
316 591336 Window 1D96D7 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
317 38B811 Window 1D96D7 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
318 C044D6 Window 1D96D7 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
319 A2AAC5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 24EAE3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
320 1747DE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 270.00 90.00 7.32 3.05 0.00 765EA5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
321 F4C599 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 76F2F2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
322 964F72 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 2D53AC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
323 FLOOR 1 OPERATING ROOM 2 SLAB Floor   CTF - ConductionTransferFunction FLOOR1OPERATINGROOM2SLAB_FFACTOR 0.214 0.204   44.59 44.59 44.59 0.00 180.00 6.10 7.32 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
324 726F67 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 180.00 0.00 1.83 7.32 0.00 B44BE3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
325 406D70 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   19.51 19.51 19.51 180.00 0.00 4.27 4.57 0.00 352740 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
326 368A44 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.71 11.71 11.71 180.00 0.00 4.27 2.74 0.00 4D50C0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
327 FLOOR 1 OPERATING ROOM 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   89.19 89.19 89.19 0.00 90.00 89.19 1.00 0.00 FLOOR 1 OPERATING ROOM 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
328 9E12D4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   15.79 15.79 15.79 270.00 90.00 5.18 3.05 0.00 29BD5F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
329 FD0958 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 180.00 90.00 8.53 3.05 0.00 EBFE47 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
330 AE206C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 0.00 90.00 8.53 3.05 0.00 FEC1E3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
331 966665 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 90.00 90.00 0.91 3.05 0.00 1D9EED Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
332 52CA89 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 90.00 90.00 4.27 3.05 0.00 829DCE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
333 FLOOR 1 OPERATING ROOM 3 SLAB Floor   CTF - ConductionTransferFunction FLOOR1OPERATINGROOM3SLAB_FFACTOR 5.650E-003 5.642E-003   44.22 44.22 44.22 0.00 180.00 8.53 5.18 0.00 FLOOR 1 OPERATING ROOM 3 SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
334 8F1C77 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.30 1.30 1.30 180.00 0.00 2.13 0.61 0.00 10FB67 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
335 18AD08 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.48 9.48 9.48 270.00 0.00 5.18 1.83 0.00 D1E495 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
336 69AE66 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.20 5.20 5.20 180.00 0.00 2.13 2.44 0.00 A3F683 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
337 CF6C6E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.55 4.55 4.55 0.00 0.00 2.13 2.13 0.00 291561 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
338 678B62 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   23.69 23.69 23.69 90.00 0.00 5.18 4.57 0.00 5620F1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
339 FLOOR 1 OPERATING ROOM 3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   88.44 88.44 88.44 0.00 90.00 88.44 1.00 0.00 FLOOR 1 OPERATING ROOM 3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
340 2B4DBD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 0.00 90.00 0.91 3.05 0.00 762F8C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
341 FCD8D2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 FE5062 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
342 F740DF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 7434CD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
343 446771 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 CA6EDA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
344 A2F014 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 8594D3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
345 FLOOR 1 PACU SLAB Floor   CTF - ConductionTransferFunction FLOOR1PACUSLAB_FFACTOR 5.650E-003 5.642E-003   10.03 10.03 10.03 180.00 180.00 3.66 2.74 0.00 FLOOR 1 PACU SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
346 995832 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.03 10.03 10.03 180.00 0.00 3.66 2.74 0.00 BEC196 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
347 FLOOR 1 PACU_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   20.07 20.07 20.07 0.00 90.00 20.07 1.00 0.00 FLOOR 1 PACU_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
348 33A280 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 270.00 90.00 7.01 3.05 0.00 2B5816 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
349 BABBB4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 86A28D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
350 F9B592 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 FA9EF2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
351 6E46A9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 5B693D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
352 BA8FF7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 464A53 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
353 25B45C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.15 24.15 24.15 90.00 90.00 7.92 3.05 0.00 9853A2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
354 592524 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 852027 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
355 EAACE4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 90.00 90.00 4.57 3.05 0.00 92E22C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
356 3AE420 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 FE2C3E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
357 414FE2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   19.51 19.51 19.51 270.00 90.00 6.40 3.05 0.00 5B255F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
358 DEAC23 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 AA1709 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
359 22DAE3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 7D08C0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
360 FLOOR 1 PRE-OP HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1PRE-OPHALLSLAB_FFACTOR 5.650E-003 5.642E-003   49.05 49.05 49.05 180.00 180.00 2.44 20.12 0.00 FLOOR 1 PRE-OP HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
361 388CB3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 90.00 0.00 5.49 0.91 0.00 D023D9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
362 FB3834 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   8.36 8.36 8.36 270.00 0.00 5.49 1.52 0.00 DFCCAE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
363 343C52 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 0.00 0.00 2.44 5.49 0.00 630683 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
364 E63CF4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 0.00 0.00 2.44 1.83 0.00 3110A1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
365 D6D2A5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 270.00 0.00 1.83 2.44 0.00 362FF8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
366 83172E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   8.36 8.36 8.36 270.00 0.00 5.49 1.52 0.00 98E1BD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
367 8FE324 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 90.00 0.00 5.49 0.91 0.00 8E5734 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
368 FLOOR 1 PRE-OP HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   98.11 98.11 98.11 0.00 90.00 98.11 1.00 0.00 FLOOR 1 PRE-OP HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
369 4DA0F5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 231744 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
370 8F966C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   15.79 15.79 15.79 270.00 90.00 5.18 3.05 0.00 42E287 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
371 FA21EE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 6A1AB7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
372 5B255F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   19.51 19.51 19.51 90.00 90.00 6.40 3.05 0.00 414FE2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
373 84418A Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   3.72 3.72 3.72 270.00 90.00 1.22 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.72 0.28 4
374 FLOOR 1 PRE-OP ROOM 1 SLAB Floor   CTF - ConductionTransferFunction FLOOR1PRE-OPROOM1SLAB_FFACTOR 8.895E-002 8.707E-002   17.56 17.56 17.56 90.00 180.00 6.40 2.74 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
375 3C43B2 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.20 9.20 9.20 270.00 0.00 3.35 2.74 0.00 6A14D8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
376 BC6EE7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.34 3.34 3.34 0.00 0.00 2.74 1.22 0.00 F24E0D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
377 363652 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 180.00 0.00 2.74 1.83 0.00 21FC9D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
378 FLOOR 1 PRE-OP ROOM 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   35.12 35.12 35.12 0.00 90.00 35.12 1.00 0.00 FLOOR 1 PRE-OP ROOM 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
379 551E65 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.15 24.15 24.15 90.00 90.00 7.92 3.05 0.00 28DE5A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
380 8C3884 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.08 12.08 12.08 180.00 90.00 3.96 3.05 0.00 DFDE4F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
381 9853A2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.15 24.15 24.15 270.00 90.00 7.92 3.05 0.00 25B45C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
382 7AE5B9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.08 12.08 12.08 0.00 90.00 3.96 3.05 0.00 D9965C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
383 FLOOR 1 PRE-OP ROOM 2 SLAB Floor   CTF - ConductionTransferFunction FLOOR1PRE-OPROOM2SLAB_FFACTOR 5.650E-003 5.642E-003   31.40 31.40 31.40 0.00 180.00 3.96 7.92 0.00 FLOOR 1 PRE-OP ROOM 2 SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
384 39AFEA Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.29E-002 9.29E-002 9.29E-002 90.00 0.00 0.30 0.30 0.00 D4B714 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
385 CABD0E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.21 1.21 1.21 180.00 0.00 3.96 0.30 0.00 FD4C82 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
386 AF38CF Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.11 1.11 1.11 0.00 0.00 3.66 0.30 0.00 FDAEB8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
387 C0A312 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.25 7.25 7.25 0.00 0.00 3.96 1.83 0.00 F81393 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
388 661D88 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   18.39 18.39 18.39 0.00 0.00 3.35 5.49 0.00 1BDF58 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
389 AFFD01 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.34 3.34 3.34 0.00 0.00 0.61 5.49 0.00 795751 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
390 FLOOR 1 PRE-OP ROOM 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   62.80 62.80 62.80 0.00 90.00 62.80 1.00 0.00 FLOOR 1 PRE-OP ROOM 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
391 2DEB73 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 2FEACD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
392 7D08C0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 22DAE3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
393 36E420 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 CA45DE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
394 1535AC Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.64 0.36 4
395 FLOOR 1 PRE-OP TOILET SLAB Floor   CTF - ConductionTransferFunction FLOOR1PRE-OPTOILETSLAB_FFACTOR 0.496 0.443   5.02 5.02 5.02 270.00 180.00 1.83 2.74 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
396 97616F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 270.00 0.00 1.83 2.74 0.00 14C7EF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
397 FLOOR 1 PRE-OP TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 1 PRE-OP TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
398 95486C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 30DB21 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
399 EAE60F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.22 10.22 10.22 180.00 90.00 3.35 3.05 0.00 361D65 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
400 6D2616 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   12.08 17.65 12.08 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
401 1D94BE Window 6D2616 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
402 18748E Window 6D2616 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
403 704EC3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 90.00 90.00 4.57 3.05 0.00 E9F3F6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
404 E20721 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 824665 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
405 FA9EF2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 F9B592 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
406 FLOOR 1 PROCEDURE ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1PROCEDUREROOMSLAB_FFACTOR 0.289 0.270   26.48 26.48 26.48 270.00 180.00 4.57 5.79 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
407 673317 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.97 6.97 6.97 270.00 0.00 4.57 1.52 0.00 D2FA45 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
408 E5C1C9 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   16.72 16.72 16.72 270.00 0.00 4.57 3.66 0.00 4E920E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
409 79376C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2.79 2.79 2.79 90.00 0.00 4.57 0.61 0.00 E9C9E1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
410 FLOOR 1 PROCEDURE ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   52.95 52.95 52.95 0.00 90.00 52.95 1.00 0.00 FLOOR 1 PROCEDURE ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
411 6EA718 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 270.00 90.00 4.57 3.05 0.00 2FAF44 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
412 2730E5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 90.00 90.00 7.01 3.05 0.00 7E0561 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
413 E608B9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 68F53B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
414 25AB11 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 0.00 90.00 1.52 3.05 0.00 7B67EC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
415 5A39B1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   15.79 15.79 15.79 90.00 90.00 5.18 3.05 0.00 612A96 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
416 234734 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 F7F8BA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
417 57B162 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 11E9BF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
418 7BB928 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   19.51 19.51 19.51 270.00 90.00 6.40 3.05 0.00 6B31A8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
419 A5A6A3 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   8.73 12.08 8.73 180.00 90.00 3.96 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
420 137A56 Window A5A6A3 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 3.34 3.34 3.34 180.00 90.00 2.74 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
421 FLOOR 1 RECEPTION SLAB Floor   CTF - ConductionTransferFunction FLOOR1RECEPTIONSLAB_FFACTOR 0.108 0.105   47.29 47.29 47.29 270.00 180.00 6.88 6.88 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
422 A02892 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.92 4.92 4.92 180.00 0.00 2.22 2.22 0.00 83658D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
423 9114B7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 90.00 0.00 5.49 2.44 0.00 7FA5FF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
424 700E69 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   28.99 28.99 28.99 270.00 0.00 7.32 3.96 0.00 14CDC6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
425 FLOOR 1 RECEPTION_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   94.58 94.58 94.58 0.00 90.00 94.58 1.00 0.00 FLOOR 1 RECEPTION_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
426 11E9BF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 57B162 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
427 839A66 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 BDC047 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
428 FE2C3E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 3AE420 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
429 CD7BAD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 0.00 90.00 4.88 3.05 0.00 8259AE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
430 6A1AB7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 FA21EE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
431 FLOOR 1 RECEPTION HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1RECEPTIONHALLSLAB_FFACTOR 5.650E-003 5.642E-003   11.89 11.89 11.89 0.00 180.00 4.88 2.44 0.00 FLOOR 1 RECEPTION HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
432 68AAF3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.55 4.55 4.55 0.00 0.00 2.13 2.13 0.00 115AA8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
433 DE014E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.85 5.85 5.85 0.00 0.00 2.74 2.13 0.00 E3963E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
434 709E99 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.49 1.49 1.49 180.00 0.00 4.88 0.30 0.00 7A8C4C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
435 FLOOR 1 RECEPTION HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   23.78 23.78 23.78 0.00 90.00 23.78 1.00 0.00 FLOOR 1 RECEPTION HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
436 28B002 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   27.03 41.81 27.03 180.00 90.00 13.72 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
437 8D508E Window 28B002 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
438 B2D381 Window 28B002 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
439 1DA13A Window 28B002 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
440 44E54A Window 28B002 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
441 D2D3BC Door 28B002 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
442 C528DA Door 28B002 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
443 EFD3F9 Door 28B002 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
444 F4FE92 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 809229 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
445 66B6F7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 330DF9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
446 72C4ED Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.81 41.81 41.81 0.00 90.00 13.72 3.05 0.00 59CEFB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
447 FLOOR 1 RECOVERY ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1RECOVERYROOMSLAB_FFACTOR 0.365 0.335   50.17 50.17 50.17 90.00 180.00 3.66 13.72 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
448 C5ECA6 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   12.26 12.26 12.26 90.00 0.00 3.66 3.35 0.00 4017DC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
449 65D500 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   26.76 26.76 26.76 90.00 0.00 3.66 7.32 0.00 17C5CF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
450 AE5EBC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.69 6.69 6.69 90.00 0.00 3.66 1.83 0.00 4C8372 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
451 2A1A9E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 270.00 0.00 3.66 1.22 0.00 F87FCE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
452 FLOOR 1 RECOVERY ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   100.34 100.34 100.34 0.00 90.00 100.34 1.00 0.00 FLOOR 1 RECOVERY ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
453 EA6DC8 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   5.76 6.50 5.76 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.71 0.29 4
454 757D10 Window EA6DC8 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 0.74 0.74 0.74 180.00 90.00 0.61 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.71 0.29 4
455 612A96 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   15.79 15.79 15.79 270.00 90.00 5.18 3.05 0.00 5A39B1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
456 BDC047 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 839A66 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
457 42E287 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   15.79 15.79 15.79 90.00 90.00 5.18 3.05 0.00 8F966C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
458 FLOOR 1 SCHEDULING SLAB Floor   CTF - ConductionTransferFunction FLOOR1SCHEDULINGSLAB_FFACTOR 0.253 0.239   11.06 11.06 11.06 90.00 180.00 5.18 2.13 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
459 513564 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.90 3.90 3.90 0.00 0.00 2.13 1.83 0.00 C51FD6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
460 58F893 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.15 7.15 7.15 180.00 0.00 2.13 3.35 0.00 CFB630 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
461 FLOOR 1 SCHEDULING_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   22.11 22.11 22.11 0.00 90.00 22.11 1.00 0.00 FLOOR 1 SCHEDULING_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
462 7816FD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 90.00 90.00 4.27 3.05 0.00 D61127 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
463 1B2EF8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 270.00 90.00 4.27 3.05 0.00 2C9CF4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
464 24EAE3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 A2AAC5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
465 9DB411 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 7E9E26 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
466 FLOOR 1 SCRUB SLAB Floor   CTF - ConductionTransferFunction FLOOR1SCRUBSLAB_FFACTOR 5.650E-003 5.642E-003   7.80 7.80 7.80 90.00 180.00 4.27 1.83 0.00 FLOOR 1 SCRUB SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
467 7008C0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 90.00 0.00 4.27 1.83 0.00 8C822C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
468 FLOOR 1 SCRUB_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   15.61 15.61 15.61 0.00 90.00 15.61 1.00 0.00 FLOOR 1 SCRUB_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
469 762F8C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 180.00 90.00 0.91 3.05 0.00 2B4DBD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
470 5D199F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 90.00 90.00 0.91 3.05 0.00 CA9655 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
471 ACADA4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 270.00 90.00 4.27 3.05 0.00 4A854B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
472 4398AD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 EA4B61 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
473 9E478E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 5EB34C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
474 6B967C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.22 10.22 10.22 90.00 90.00 3.35 3.05 0.00 49DA86 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
475 FLOOR 1 SOIL SLAB Floor   CTF - ConductionTransferFunction FLOOR1SOILSLAB_FFACTOR 5.650E-003 5.642E-003   11.71 11.71 11.71 90.00 180.00 4.27 2.74 0.00 FLOOR 1 SOIL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
476 4B54B4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.84 0.84 0.84 0.00 0.00 2.74 0.30 0.00 C81AED Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
477 88D2F8 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.85 5.85 5.85 180.00 0.00 2.74 2.13 0.00 15A915 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
478 7274F6 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 0.00 0.00 2.74 1.83 0.00 4B590B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
479 FLOOR 1 SOIL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   23.41 23.41 23.41 0.00 90.00 23.41 1.00 0.00 FLOOR 1 SOIL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
480 A1087A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 70DAD1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
481 41CE25 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 FA769A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
482 9A776E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 445A39 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
483 9ABA5B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 814856 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
484 FLOOR 1 SOIL HOLD SLAB Floor   CTF - ConductionTransferFunction FLOOR1SOILHOLDSLAB_FFACTOR 5.650E-003 5.642E-003   5.20 5.20 5.20 0.00 180.00 2.13 2.44 0.00 FLOOR 1 SOIL HOLD SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
485 58A74A Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 270.00 0.00 2.44 1.83 0.00 5CA4CF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
486 D78A26 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.74 0.74 0.74 90.00 0.00 2.44 0.30 0.00 D1899C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
487 FLOOR 1 SOIL HOLD_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.41 10.41 10.41 0.00 90.00 10.41 1.00 0.00 FLOOR 1 SOIL HOLD_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
488 37E2C7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 6A2C62 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
489 23683B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 825233 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
490 CA9655 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 270.00 90.00 0.91 3.05 0.00 5D199F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
491 121DFF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 B551AD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
492 FAE342 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 5CD67D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
493 FLOOR 1 SOIL WORK SLAB Floor   CTF - ConductionTransferFunction FLOOR1SOILWORKSLAB_FFACTOR 5.650E-003 5.642E-003   16.72 16.72 16.72 0.00 180.00 4.57 3.66 0.00 FLOOR 1 SOIL WORK SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
494 A44272 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.86 1.86 1.86 90.00 0.00 3.05 0.61 0.00 26AF41 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
495 B9DDBA Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.57 5.57 5.57 90.00 0.00 3.05 1.83 0.00 D10995 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
496 9EBF3E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2.79 2.79 2.79 0.00 0.00 4.57 0.61 0.00 EB4979 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
497 903092 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.50 6.50 6.50 0.00 0.00 2.13 3.05 0.00 56C7DA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
498 FLOOR 1 SOIL WORK_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   33.45 33.45 33.45 0.00 90.00 33.45 1.00 0.00 FLOOR 1 SOIL WORK_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
499 5FD018 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 6822BB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
500 809229 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 F4FE92 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
501 B40F89 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   8.92 11.15 8.92 270.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.61 0.39 4
502 E33BAE Window B40F89 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_WEST_0.25 N/A 6.926 No 2.23 2.23 2.23 270.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.61 0.39 4
503 997723 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   16.82 23.23 16.82 180.00 90.00 7.62 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
504 24167A Window 997723 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
505 2C0938 Window 997723 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
506 62B5AF Door 997723 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
507 CA45DE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 36E420 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
508 5B693D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 6E46A9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
509 FLOOR 1 STEP DOWN SLAB Floor   CTF - ConductionTransferFunction FLOOR1STEPDOWNSLAB_FFACTOR 0.555 0.489   27.87 27.87 27.87 270.00 180.00 3.66 7.62 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
510 FBDD49 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 0.00 0.00 3.66 3.66 0.00 5EBA9B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
511 4284B6 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.69 6.69 6.69 90.00 0.00 3.66 1.83 0.00 2C31F2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
512 FCE842 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 270.00 0.00 3.66 2.13 0.00 4968A2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
513 FLOOR 1 STEP DOWN_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   55.74 55.74 55.74 0.00 90.00 55.74 1.00 0.00 FLOOR 1 STEP DOWN_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
514 829DCE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 270.00 90.00 4.27 3.05 0.00 52CA89 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
515 E77E00 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 90.00 90.00 7.01 3.05 0.00 83A098 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
516 CEC7BD Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   5.20 7.43 5.20 180.00 90.00 2.44 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
517 8600DD Window CEC7BD Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
518 8C4FA5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 F43F35 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
519 B3A518 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 4161C8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
520 44686F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 C92A6E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
521 6A2C62 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 37E2C7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
522 A809DD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.22 10.22 10.22 270.00 90.00 3.35 3.05 0.00 619EE6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
523 EE0E68 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 38F548 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
524 88AE01 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 35028C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
525 2C9CF4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 90.00 90.00 4.27 3.05 0.00 1B2EF8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
526 765EA5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 90.00 90.00 7.32 3.05 0.00 1747DE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
527 2B370E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 E321D9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
528 F30797 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 87BFF9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
529 FLOOR 1 STERILE HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1STERILEHALLSLAB_FFACTOR 5.429E-002 5.359E-002   57.23 57.23 57.23 270.00 180.00 23.47 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
530 3179A6 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   8.92 8.92 8.92 0.00 0.00 2.44 3.66 0.00 75353D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
531 370DB2 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.20 5.20 5.20 180.00 0.00 2.44 2.13 0.00 4B217A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
532 34B3F0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.43 7.43 7.43 90.00 0.00 3.05 2.44 0.00 4CDC86 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
533 CEDA0D Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.95 5.95 5.95 0.00 0.00 2.44 2.44 0.00 C2CE5F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
534 4469CD Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 90.00 0.00 5.49 2.44 0.00 10830D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
535 F62393 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 90.00 0.00 1.83 2.44 0.00 283EC6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
536 340FB5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 0.00 0.00 2.44 1.83 0.00 20B940 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
537 CDA7F8 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.43 7.43 7.43 270.00 0.00 3.05 2.44 0.00 2805F0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
538 FLOOR 1 STERILE HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   114.46 114.46 114.46 0.00 90.00 114.46 1.00 0.00 FLOOR 1 STERILE HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
539 8043B2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 94A56A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
540 38F548 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 EE0E68 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
541 96662A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 415590 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
542 1003C1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 0.00 90.00 10.06 3.05 0.00 66D163 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
543 863C6C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 758B3C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
544 808817 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 FD8CF2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
545 EA4B61 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 4398AD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
546 FLOOR 1 NURSE STORAGE SLAB Floor   CTF - ConductionTransferFunction FLOOR1NURSESTORAGESLAB_FFACTOR 5.650E-003 5.642E-003   36.79 36.79 36.79 0.00 180.00 10.06 3.66 0.00 FLOOR 1 NURSE STORAGE SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
547 C1737B Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.22 10.22 10.22 0.00 0.00 3.05 3.35 0.00 C3DB37 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
548 D44BF1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.07 3.07 3.07 180.00 0.00 10.06 0.30 0.00 D29B01 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
549 5C05FF Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   23.50 23.50 23.50 0.00 0.00 7.01 3.35 0.00 F6FE66 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
550 FLOOR 1 STERILE STORAGE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   73.58 73.58 73.58 0.00 90.00 73.58 1.00 0.00 FLOOR 1 STERILE STORAGE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
551 707E04 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 90.00 90.00 4.88 3.05 0.00 87231D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
552 8E5BB9 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   18.39 21.37 18.39 270.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.69 0.31 4
553 71E924 Door 8E5BB9 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   2.97 2.97 2.97 270.00 90.00 1.22 2.44 4.00E-004 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
554 859BC1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   22.95 37.16 22.95 0.00 90.00 12.19 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
555 A1ED60 Window 859BC1 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
556 E8D997 Window 859BC1 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
557 88E1FC Window 859BC1 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
558 3C44F9 Door 859BC1 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
559 49526E Door 859BC1 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
560 865AE8 Door 859BC1 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
561 891195 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 9C0202 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
562 8B4DC1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 72BCFE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
563 19D150 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 BBEE0B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
564 814856 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 9ABA5B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
565 5B533A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 319A6B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
566 FLOOR 1 STORAGE SLAB Floor   CTF - ConductionTransferFunction FLOOR1STORAGESLAB_FFACTOR 0.297 0.277   85.47 85.47 85.47 270.00 180.00 7.01 12.19 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
567 FLOOR 1 STORGE ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   85.47 85.47 85.47 270.00 0.00 7.01 12.19 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.27 0.73 4
568 FLOOR 1 STORAGE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   170.94 170.94 170.94 0.00 90.00 170.94 1.00 0.00 FLOOR 1 STORAGE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
569 61E610 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   9.04 13.01 9.04 90.00 90.00 4.27 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
570 F83F33 Window 61E610 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 3.97 3.97 3.97 90.00 90.00 2.44 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
571 76F2F2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 F4C599 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
572 D61127 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 270.00 90.00 4.27 3.05 0.00 7816FD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
573 196C5F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 575A7B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
574 FLOOR 1 SUB-STERILE SLAB Floor   CTF - ConductionTransferFunction FLOOR1SUB-STERILESLAB_FFACTOR 0.310 0.289   18.21 18.21 18.21 180.00 180.00 4.27 4.27 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
575 1875B3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   18.21 18.21 18.21 180.00 0.00 4.27 4.27 0.00 D3CF55 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
576 FLOOR 1 SUB-STERILE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   36.42 36.42 36.42 0.00 90.00 36.42 1.00 0.00 FLOOR 1 SUB-STERILE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
577 39E49D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 62475F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
578 F43F35 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 8C4FA5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
579 89BBEB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 A4B378 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
580 87231D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 270.00 90.00 4.88 3.05 0.00 707E04 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
581 529072 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   7.43 14.86 7.43 90.00 90.00 4.88 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.67 0.33 4
582 5E66D1 Door 529072 CTF - ConductionTransferFunction OVERHEAD DOOR_CON 200.000 200.000   7.43 7.43 7.43 90.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.66 0.34 4
583 C1C64E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 986A05 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
584 1D9EED Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 270.00 90.00 0.91 3.05 0.00 966665 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
585 20FB14 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 270.00 90.00 1.52 3.05 0.00 F4D6DD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
586 DEFACF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 32CC19 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
587 FLOOR 1 UTILITY HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1UTILITYHALLSLAB_FFACTOR 0.270 0.253   23.78 23.78 23.78 90.00 180.00 9.75 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
588 FLOOR 1 UTILITY HALL ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   11.89 11.89 11.89 180.00 0.00 2.44 4.88 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.32 0.68 4
589 5136E3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.74 0.74 0.74 0.00 0.00 2.44 0.30 0.00 1C7FB1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
590 EFCC3C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.15 11.15 11.15 270.00 0.00 4.57 2.44 0.00 C84AE1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
591 FLOOR 1 UTILITY HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   47.57 47.57 47.57 0.00 90.00 47.57 1.00 0.00 FLOOR 1 UTILITY HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
592 2E8328 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 9879B2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
593 E321D9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 2B370E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
594 E89C6C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 23CCB1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
595 816F6D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 9C6F66 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
596 FLOOR 1 UTILITY JANITOR SLAB Floor   CTF - ConductionTransferFunction FLOOR1UTILITYJANITORSLAB_FFACTOR 5.650E-003 5.642E-003   3.90 3.90 3.90 90.00 180.00 2.13 1.83 0.00 FLOOR 1 UTILITY JANITOR SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
597 5F697A Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.90 3.90 3.90 90.00 0.00 2.13 1.83 0.00 4F2F27 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
598 FLOOR 1 UTILITY JANITOR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7.80 7.80 7.80 0.00 90.00 7.80 1.00 0.00 FLOOR 1 UTILITY JANITOR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
599 EC28A9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 E82152 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
600 204CB9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 0.00 90.00 6.10 3.05 0.00 A28F01 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
601 62475F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 39E49D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
602 D95F04 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   11.79 16.72 11.79 90.00 90.00 5.49 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
603 E14DAE Door D95F04 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.59 0.41 4
604 B1F5EE Window D95F04 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
605 87BFF9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 F30797 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
606 23CCB1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 E89C6C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
607 FLOOR 1 UTILITY ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1UTILITYROOMSLAB_FFACTOR 0.214 0.204   33.45 33.45 33.45 180.00 180.00 6.10 5.49 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
608 7DB101 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.03 10.03 10.03 270.00 0.00 5.49 1.83 0.00 909DB9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
609 F28371 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   23.41 23.41 23.41 180.00 0.00 4.27 5.49 0.00 C25071 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
610 FLOOR 1 UTILITY ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   66.89 66.89 66.89 0.00 90.00 66.89 1.00 0.00 FLOOR 1 UTILITY ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
611 231744 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 4DA0F5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
612 3330D8 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   5.48 7.43 5.48 270.00 90.00 2.44 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.69 0.31 4
613 84A1D5 Door 3330D8 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.69 0.31 4
614 2FEACD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 2DEB73 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
615 AA1709 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 DEAC23 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
616 FLOOR 1 VESTIBULE SLAB Floor   CTF - ConductionTransferFunction FLOOR1VESTIBULESLAB_FFACTOR 0.496 0.443   6.69 6.69 6.69 90.00 180.00 2.44 2.74 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
617 C34217 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.69 6.69 6.69 90.00 0.00 2.44 2.74 0.00 6E3B28 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
618 FLOOR 1 VESTIBULE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   13.38 13.38 13.38 0.00 90.00 13.38 1.00 0.00 FLOOR 1 VESTIBULE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
619 208CCF Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   8.17 11.15 8.17 90.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
620 F52F3D Window 208CCF Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
621 AEF992 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   19.32 26.01 19.32 180.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
622 80885D Window AEF992 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 6.69 6.69 6.69 180.00 90.00 5.49 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
623 9AC2E9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 CE4555 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
624 436189 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 7C84B6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
625 B184C1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 CC4EB4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
626 BC8EB7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 3C9825 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
627 75353D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   8.92 8.92 8.92 270.00 180.00 3.66 2.44 0.00 3179A6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
628 2BD1E8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   22.30 22.30 22.30 180.00 180.00 6.10 3.66 0.00 E648BC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
629 240A7C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   31.22 31.22 31.22 180.00 0.00 8.53 3.66 0.00 D14D65 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
630 FLOOR 2 CONFERENCE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   62.43 62.43 62.43 0.00 90.00 62.43 1.00 0.00 FLOOR 2 CONFERENCE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
631 F6D879 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 58AD84 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
632 1701A6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 680AA1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
633 772842 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 577A10 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
634 3C9825 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 BC8EB7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
635 C2CE5F Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.95 5.95 5.95 0.00 180.00 2.44 2.44 0.00 CEDA0D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
636 7149EA Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.95 5.95 5.95 0.00 0.00 2.44 2.44 0.00 CDCA72 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
637 FLOOR 2 CONFERENCE TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   11.89 11.89 11.89 0.00 90.00 11.89 1.00 0.00 FLOOR 2 CONFERENCE TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
638 296861 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 7620CF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
639 3D4DE8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 36A02A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
640 8A5790 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 D79C57 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
641 2DB420 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 DE64CC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
642 56C7DA Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.50 6.50 6.50 90.00 180.00 3.05 2.13 0.00 903092 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
643 E1B973 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.50 6.50 6.50 90.00 0.00 3.05 2.13 0.00 1EE332 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
644 FLOOR 2 DICTATION_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   13.01 13.01 13.01 0.00 90.00 13.01 1.00 0.00 FLOOR 2 DICTATION_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
645 640E64 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 90.00 90.00 9.14 3.05 0.00 9E6B6C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
646 10E44F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 A72F04 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
647 54D065 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   8.92 11.15 8.92 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
648 FEEF06 Window 54D065 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
649 1775A6 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   21.18 27.87 21.18 270.00 90.00 9.14 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
650 2BE8DE Window 1775A6 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_WEST_0.25 N/A 6.926 No 2.23 2.23 2.23 270.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
651 513E2A Window 1775A6 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_WEST_0.25 N/A 6.926 No 2.23 2.23 2.23 270.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.68 0.32 4
652 BA5CD9 Window 1775A6 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_WEST_0.25 N/A 6.926 No 2.23 2.23 2.23 270.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.61 0.39 4
653 6E3B28 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.69 6.69 6.69 270.00 180.00 2.44 2.74 0.00 C34217 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
654 14C7EF Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 270.00 180.00 1.83 2.74 0.00 97616F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
655 5EBA9B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 270.00 180.00 3.66 3.66 0.00 FBDD49 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
656 F24E0D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.34 3.34 3.34 270.00 180.00 1.22 2.74 0.00 BC6EE7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
657 D023D9 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 0.00 180.00 0.91 5.49 0.00 388CB3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
658 A4BE81 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   33.45 33.45 33.45 0.00 0.00 3.66 9.14 0.00 F4E5F5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
659 FLOOR 2 EXAM 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   66.89 66.89 66.89 0.00 90.00 66.89 1.00 0.00 FLOOR 2 EXAM 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
660 4EE021 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 90.00 90.00 9.14 3.05 0.00 42FAB2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
661 6ED237 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 270.00 90.00 9.14 3.05 0.00 53450D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
662 97F00A Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   13.01 16.72 13.01 180.00 90.00 5.49 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
663 1AD478 Window 97F00A Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 3.72 3.72 3.72 180.00 90.00 3.05 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
664 ADD799 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 EEECA3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
665 4017DC Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   12.26 12.26 12.26 90.00 180.00 3.66 3.35 0.00 C5ECA6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
666 CCAA9D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 180.00 180.00 5.49 2.44 0.00 92E327 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
667 4968A2 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 270.00 180.00 3.66 2.13 0.00 FCE842 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
668 4579A7 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   15.05 15.05 15.05 180.00 180.00 5.49 2.74 0.00 A0117C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
669 FDAEB8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.11 1.11 1.11 270.00 180.00 0.30 3.66 0.00 AF38CF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
670 E3B855 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.56 0.56 0.56 90.00 180.00 0.30 1.83 0.00 E8F02D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
671 906F5E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   50.17 50.17 50.17 0.00 0.00 5.49 9.14 0.00 68EB71 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
672 FLOOR 2 EXAM 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   100.34 100.34 100.34 0.00 90.00 100.34 1.00 0.00 FLOOR 2 EXAM 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
673 DFA4B1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 0.00 90.00 7.32 3.05 0.00 CFAD9D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
674 F23BF4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 270.00 90.00 9.14 3.05 0.00 6713DA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
675 A497E9 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   16.35 22.30 16.35 180.00 90.00 7.32 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
676 27F0AC Window A497E9 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 5.95 5.95 5.95 180.00 90.00 4.88 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
677 26E66C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 90.00 90.00 9.14 3.05 0.00 479A9C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
678 17C5CF Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   26.76 26.76 26.76 180.00 180.00 7.32 3.66 0.00 65D500 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
679 BA0A29 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   17.84 17.84 17.84 180.00 180.00 7.32 2.44 0.00 7F6B1B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
680 26AF41 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.86 1.86 1.86 180.00 180.00 0.61 3.05 0.00 A44272 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
681 75A3C4 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 90.00 180.00 2.74 1.83 0.00 156F92 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
682 BEC196 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.03 10.03 10.03 90.00 180.00 2.74 3.66 0.00 995832 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
683 9B49F5 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.84 0.84 0.84 90.00 180.00 0.30 2.74 0.00 672F1E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
684 EB611D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.37 0.37 0.37 0.00 180.00 1.22 0.30 0.00 1B4EDC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
685 C81AED Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.84 0.84 0.84 270.00 180.00 0.30 2.74 0.00 4B54B4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
686 BD5B50 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.34 3.34 3.34 180.00 180.00 1.22 2.74 0.00 52F395 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
687 3AEAAB Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.01 13.01 13.01 90.00 0.00 3.05 4.27 0.00 2B4713 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
688 D74115 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   44.59 44.59 44.59 0.00 0.00 7.32 6.10 0.00 7F8407 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
689 5065F0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.29 9.29 9.29 270.00 0.00 3.05 3.05 0.00 8FB568 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
690 FLOOR 2 EXAM 3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   133.78 133.78 133.78 0.00 90.00 133.78 1.00 0.00 FLOOR 2 EXAM 3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
691 7C84B6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 436189 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
692 D88779 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 F6E717 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
693 577E2E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 DA6040 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
694 88A75F Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   4.27 6.50 4.27 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
695 724114 Window 88A75F Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
696 4E78E0 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 90.00 180.00 3.66 2.13 0.00 BE1AE1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
697 C0697F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 90.00 0.00 3.66 2.13 0.00 F69079 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
698 FLOOR 2 EXAM 4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   15.61 15.61 15.61 0.00 90.00 15.61 1.00 0.00 FLOOR 2 EXAM 4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
699 83B6E3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 290DF3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
700 AC956A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   23.23 23.23 23.23 270.00 90.00 7.62 3.05 0.00 571934 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
701 B4E619 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   15.29 23.23 15.29 90.00 90.00 7.62 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.54 0.46 4
702 D538C4 Window B4E619 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 3.97 3.97 3.97 90.00 90.00 2.44 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
703 5635BC Window B4E619 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 3.97 3.97 3.97 90.00 90.00 2.44 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.54 0.46 4
704 BFA29B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 DE6295 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
705 65AB67 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.10 9.10 9.10 180.00 180.00 4.27 2.13 0.00 D7AC92 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
706 C25071 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   23.41 23.41 23.41 0.00 180.00 4.27 5.49 0.00 F28371 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
707 31B3DF Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.52 32.52 32.52 270.00 0.00 7.62 4.27 0.00 1DC177 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
708 FLOOR 2 EXAM 5_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   65.03 65.03 65.03 0.00 90.00 65.03 1.00 0.00 FLOOR 2 EXAM 5_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
709 F29458 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ED650B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
710 1EB5B1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 2884D1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
711 9EC269 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   9.75 13.94 9.75 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
712 831C1D Window 9EC269 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 4.18 4.18 4.18 0.00 90.00 2.74 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
713 47CE83 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 270.00 90.00 4.57 3.05 0.00 3947B8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
714 A8FC82 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 16BE00 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
715 C84AE1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.15 11.15 11.15 90.00 180.00 4.57 2.44 0.00 EFCC3C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
716 F67EC8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.20 5.20 5.20 90.00 180.00 2.44 2.13 0.00 F6F6C6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
717 10FB67 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.30 1.30 1.30 180.00 180.00 2.13 0.61 0.00 8F1C77 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
718 1624C5 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.25 3.25 3.25 180.00 180.00 2.13 1.52 0.00 FB17DD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
719 917AB5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.90 20.90 20.90 90.00 0.00 4.57 4.57 0.00 F7BE2F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
720 FLOOR 2 EXAM 6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   41.81 41.81 41.81 0.00 90.00 41.81 1.00 0.00 FLOOR 2 EXAM 6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
721 247258 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 270.00 90.00 10.06 3.05 0.00 14F382 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
722 B316F7 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   16.72 22.30 16.72 0.00 90.00 7.32 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
723 9BB95F Window B316F7 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
724 C0778D Window B316F7 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
725 FF8B08 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 90.00 90.00 10.06 3.05 0.00 55191F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
726 F976A9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 180.00 90.00 7.32 3.05 0.00 3FBBC8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
727 8D6453 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.41 10.41 10.41 0.00 180.00 4.27 2.44 0.00 C732D4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
728 D1899C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.74 0.74 0.74 0.00 180.00 0.30 2.44 0.00 D78A26 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
729 5620F1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   23.69 23.69 23.69 90.00 180.00 5.18 4.57 0.00 678B62 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
730 40E182 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.97 6.97 6.97 270.00 180.00 1.52 4.57 0.00 9A5B84 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
731 A6147C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   25.08 25.08 25.08 0.00 180.00 2.74 9.14 0.00 7B9EEC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
732 37898A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.69 6.69 6.69 180.00 180.00 7.32 0.91 0.00 C8F2F1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
733 F0D8EE Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   30.66 30.66 30.66 90.00 0.00 10.06 3.05 0.00 A72B2F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
734 567037 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.13 6.13 6.13 180.00 0.00 0.61 10.06 0.00 60F383 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
735 6B3E65 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   17.84 17.84 17.84 90.00 0.00 4.88 3.66 0.00 B46F2C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
736 245972 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.15 11.15 11.15 90.00 0.00 3.05 3.66 0.00 D10EC7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
737 F17DF7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 0.00 0.00 3.66 2.13 0.00 63B825 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
738 FLOOR 2 EXAM 7_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   147.16 147.16 147.16 0.00 90.00 147.16 1.00 0.00 FLOOR 2 EXAM 7_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
739 D7DC8D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 90.00 90.00 4.57 3.05 0.00 2E6DF0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
740 9621FD Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   11.15 16.72 11.15 0.00 90.00 5.49 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
741 7D2D69 Window 9621FD Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
742 2EF63B Window 9621FD Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
743 6A2DCE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 270.00 90.00 4.57 3.05 0.00 D37566 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
744 7A03ED Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 BADB96 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
745 A9A1F6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   25.08 25.08 25.08 0.00 180.00 5.49 4.57 0.00 21C5E8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
746 DA760E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   25.08 25.08 25.08 0.00 0.00 5.49 4.57 0.00 8A695C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
747 FLOOR 2 EXAM 8_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   50.17 50.17 50.17 0.00 90.00 50.17 1.00 0.00 FLOOR 2 EXAM 8_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
748 42CEE1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   8.36 11.15 8.36 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
749 C417C0 Window 42CEE1 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
750 35051E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 270.00 90.00 10.06 3.05 0.00 5C7E1E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
751 685FFA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 90.00 90.00 10.06 3.05 0.00 5556EE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
752 B51929 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 32BAA7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
753 8E5734 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 90.00 180.00 5.49 0.91 0.00 8FE324 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
754 4E920E Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   16.72 16.72 16.72 0.00 180.00 3.66 4.57 0.00 E5C1C9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
755 87C477 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   15.05 15.05 15.05 270.00 180.00 5.49 2.74 0.00 621A74 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
756 5D2769 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.79 36.79 36.79 180.00 0.00 3.66 10.06 0.00 AE8664 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
757 FLOOR 2 EXAM 9_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   73.58 73.58 73.58 0.00 90.00 73.58 1.00 0.00 FLOOR 2 EXAM 9_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
758 4979C8 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
759 9E6B6C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 270.00 90.00 9.14 3.05 0.00 640E64 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
760 DF91E0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 9CE650 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
761 53450D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 90.00 90.00 9.14 3.05 0.00 6ED237 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
762 DFCCAE Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   8.36 8.36 8.36 90.00 180.00 5.49 1.52 0.00 FB3834 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
763 D4B714 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.29E-002 9.29E-002 9.29E-002 0.00 180.00 0.30 0.30 0.00 39AFEA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
764 3AE495 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.84 0.84 0.84 0.00 180.00 0.30 2.74 0.00 BD4B70 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
765 526C70 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.74 0.74 0.74 0.00 180.00 0.30 2.44 0.00 C75191 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
766 2C31F2 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.69 6.69 6.69 180.00 180.00 1.83 3.66 0.00 4284B6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
767 E26130 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   16.72 16.72 16.72 270.00 0.00 9.14 1.83 0.00 AA7BE2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
768 FLOOR 2 EXAM HALL 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   33.45 33.45 33.45 0.00 90.00 33.45 1.00 0.00 FLOOR 2 EXAM HALL 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
769 42FAB2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 270.00 90.00 9.14 3.05 0.00 4EE021 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
770 815D63 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 EE34A3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
771 6713DA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 90.00 90.00 9.14 3.05 0.00 F23BF4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
772 8CA0BF Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
773 4C8372 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.69 6.69 6.69 180.00 180.00 1.83 3.66 0.00 AE5EBC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
774 243E09 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 180.00 180.00 1.83 2.44 0.00 4A49C1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
775 C94CC0 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 180.00 180.00 1.83 2.74 0.00 AA2E8F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
776 BD39AC Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.29E-002 9.29E-002 9.29E-002 270.00 180.00 0.30 0.30 0.00 6ECCF3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
777 75EAF8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.46 0.46 0.46 90.00 180.00 0.30 1.52 0.00 EC2478 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
778 E9AEFF Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   16.72 16.72 16.72 270.00 0.00 9.14 1.83 0.00 948D7B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
779 FLOOR 2 EXAM HALL 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   33.45 33.45 33.45 0.00 90.00 33.45 1.00 0.00 FLOOR 2 EXAM HALL 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
780 479A9C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 270.00 90.00 9.14 3.05 0.00 26E66C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
781 DA6040 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 577E2E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
782 6C95E7 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
783 BC25F3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 25F524 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
784 C08963 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 390BCF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
785 36A02A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 3D4DE8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
786 A08A28 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2.23 2.23 2.23 180.00 180.00 0.61 3.66 0.00 DDCF3E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
787 F87FCE Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 180.00 180.00 1.22 3.66 0.00 2A1A9E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
788 BAE3F8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 180.00 180.00 1.83 2.44 0.00 8F5FFC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
789 D10995 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.57 5.57 5.57 0.00 180.00 1.83 3.05 0.00 B9DDBA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
790 D4A2A4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.57 5.57 5.57 180.00 0.00 1.83 3.05 0.00 C271D9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
791 6C1891 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.15 11.15 11.15 270.00 0.00 6.10 1.83 0.00 3C8351 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
792 FLOOR 2 EXAM HALL 3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   33.45 33.45 33.45 0.00 90.00 33.45 1.00 0.00 FLOOR 2 EXAM HALL 3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
793 46F148 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 CBB2D7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
794 F209CC Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
795 E7EC3B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 B5099E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
796 55191F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 270.00 90.00 10.06 3.05 0.00 FF8B08 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
797 3947B8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 90.00 90.00 4.57 3.05 0.00 47CE83 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
798 3B9E2E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 A168ED Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
799 C2156D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.67 1.67 1.67 180.00 180.00 1.83 0.91 0.00 3137C4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
800 5CA4CF Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 0.00 180.00 1.83 2.44 0.00 58A74A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
801 4AA9BC Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2.79 2.79 2.79 0.00 180.00 1.83 1.52 0.00 8A2F34 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
802 D1E495 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.48 9.48 9.48 90.00 180.00 5.18 1.83 0.00 18AD08 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
803 4180E7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   18.39 18.39 18.39 90.00 0.00 10.06 1.83 0.00 52FA3B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
804 FLOOR 2 EXAM HALL 4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   36.79 36.79 36.79 0.00 90.00 36.79 1.00 0.00 FLOOR 2 EXAM HALL 4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
805 247FD8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 5EE606 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
806 2E6DF0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 270.00 90.00 4.57 3.05 0.00 D7DC8D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
807 14F382 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 90.00 90.00 10.06 3.05 0.00 247258 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
808 155BD6 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
809 ED8563 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 E0D6E9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
810 A1BBBE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 462370 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
811 E0C60A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.67 1.67 1.67 270.00 180.00 0.91 1.83 0.00 6B171C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
812 772953 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   8.36 8.36 8.36 270.00 180.00 9.14 0.91 0.00 7B1677 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
813 15A02B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   8.36 8.36 8.36 0.00 180.00 0.91 9.14 0.00 B04E85 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
814 B9D6E3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   18.39 18.39 18.39 90.00 0.00 10.06 1.83 0.00 538FE6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
815 FLOOR 2 EXAM HALL 5_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   36.79 36.79 36.79 0.00 90.00 36.79 1.00 0.00 FLOOR 2 EXAM HALL 5_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
816 942718 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 7A8E3F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
817 D2C12A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 A49FCC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
818 5556EE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 270.00 90.00 10.06 3.05 0.00 685FFA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
819 C5EA55 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
820 D37566 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 90.00 90.00 4.57 3.05 0.00 6A2DCE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
821 E7055D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 70C0BF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
822 EC3BEA Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2.79 2.79 2.79 90.00 180.00 9.14 0.30 0.00 FDCEC5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
823 D2FA45 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.97 6.97 6.97 270.00 180.00 4.57 1.52 0.00 673317 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
824 98E1BD Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   8.36 8.36 8.36 270.00 180.00 5.49 1.52 0.00 83172E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
825 5F9E13 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.28 0.28 0.28 180.00 180.00 0.30 0.91 0.00 C605B5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
826 B4F89F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   18.39 18.39 18.39 270.00 0.00 10.06 1.83 0.00 F94215 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
827 FLOOR 2 EXAM HALL 6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   36.79 36.79 36.79 0.00 90.00 36.79 1.00 0.00 FLOOR 2 EXAM HALL 6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
828 8177BA Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
829 5E657E Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
830 4AD319 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 4CE123 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
831 E0C0A7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 8C4550 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
832 5B736E Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.85 5.85 5.85 180.00 180.00 2.74 2.13 0.00 DF9D5D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
833 F6E6D8 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.85 5.85 5.85 180.00 0.00 2.74 2.13 0.00 B840A7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
834 FLOOR 2 JANITOR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   11.71 11.71 11.71 0.00 90.00 11.71 1.00 0.00 FLOOR 2 JANITOR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
835 97BB21 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 93F6DE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
836 7620CF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 296861 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
837 680AA1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 1701A6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
838 A524F1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 988ACA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
839 4CDC86 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.43 7.43 7.43 0.00 180.00 2.44 3.05 0.00 34B3F0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
840 B352F7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.43 7.43 7.43 0.00 0.00 2.44 3.05 0.00 96623F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
841 FLOOR 2 LOUNGE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   14.86 14.86 14.86 0.00 90.00 14.86 1.00 0.00 FLOOR 2 LOUNGE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
842 CBB2D7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 46F148 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
843 D0731B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 16E41D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
844 ECDEDB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 52D809 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
845 ED1D7F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 24E235 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
846 2805F0 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.43 7.43 7.43 90.00 180.00 3.05 2.44 0.00 CDA7F8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
847 5A7EAB Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.95 1.95 1.95 180.00 180.00 2.13 0.91 0.00 1891E7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
848 291561 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.55 4.55 4.55 0.00 180.00 2.13 2.13 0.00 CF6C6E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
849 4E1563 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.94 13.94 13.94 180.00 0.00 4.57 3.05 0.00 3B5B94 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
850 FLOOR 2 NURSE STATION 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   27.87 27.87 27.87 0.00 90.00 27.87 1.00 0.00 FLOOR 2 NURSE STATION 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
851 A49FCC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 D2C12A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
852 5DBD9D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 B94E9A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
853 491317 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 211EA4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
854 462370 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 A1BBBE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
855 9EADD8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.71 11.71 11.71 0.00 180.00 5.49 2.13 0.00 1E6611 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
856 DE8843 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 180.00 180.00 5.49 0.91 0.00 86C171 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
857 C45BF3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   16.72 16.72 16.72 270.00 0.00 3.05 5.49 0.00 C27BD7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
858 FLOOR 2 NURSE STATION 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   33.45 33.45 33.45 0.00 90.00 33.45 1.00 0.00 FLOOR 2 NURSE STATION 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
859 AAF377 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   37.16 37.16 37.16 270.00 90.00 12.19 3.05 0.00 DFA16C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
860 CE4555 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 9AC2E9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
861 A8A4FA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 97B688 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
862 4B1439 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   25.25 37.16 25.25 90.00 90.00 12.19 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
863 EB042B Window 4B1439 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
864 4C1F71 Window 4B1439 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
865 D23C8B Window 4B1439 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
866 B4E4BE Window 4B1439 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
867 352740 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   19.51 19.51 19.51 0.00 180.00 4.27 4.57 0.00 406D70 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
868 D3CF55 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   18.21 18.21 18.21 0.00 180.00 4.27 4.27 0.00 1875B3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
869 64A2F7 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   14.31 14.31 14.31 180.00 180.00 4.27 3.35 0.00 FFE052 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
870 D1A180 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.41 10.41 10.41 0.00 0.00 4.27 2.44 0.00 8E83C6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
871 9BB582 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   41.62 41.62 41.62 180.00 0.00 4.27 9.75 0.00 8480E5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
872 FLOOR 2 OFFICE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   104.05 104.05 104.05 0.00 90.00 104.05 1.00 0.00 FLOOR 2 OFFICE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
873 DFA16C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   37.16 37.16 37.16 90.00 90.00 12.19 3.05 0.00 AAF377 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
874 2884D1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 1EB5B1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
875 CC4EB4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 B184C1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
876 B2F07D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 6EE166 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
877 AF86E1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 4F0CD7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
878 571934 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   23.23 23.23 23.23 90.00 90.00 7.62 3.05 0.00 AC956A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
879 67A7F3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 8E1DCD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
880 24E235 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 ED1D7F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
881 AB568E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 830326 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
882 577A10 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 772842 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
883 988ACA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 A524F1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
884 F5AF76 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 270.00 90.00 5.49 3.05 0.00 24DA9F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
885 4EDE0A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 2740BD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
886 874DF8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.13 6.13 6.13 270.00 180.00 3.35 1.83 0.00 611A3F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
887 8C822C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 270.00 180.00 4.27 1.83 0.00 7008C0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
888 B44BE3 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 270.00 180.00 7.32 1.83 0.00 726F67 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
889 4F2F27 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.90 3.90 3.90 180.00 180.00 1.83 2.13 0.00 5F697A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
890 909DB9 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.03 10.03 10.03 0.00 180.00 1.83 5.49 0.00 7DB101 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
891 30A09C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   8.92 8.92 8.92 90.00 0.00 4.88 1.83 0.00 F17575 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
892 BFEF28 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   27.87 27.87 27.87 90.00 0.00 15.24 1.83 0.00 2E74E6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
893 C588CC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 0.00 0.00 1.83 2.44 0.00 339B46 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
894 FLOOR 2 OFFICE HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   82.50 82.50 82.50 0.00 90.00 82.50 1.00 0.00 FLOOR 2 OFFICE HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
895 23C13E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.81 41.81 41.81 0.00 90.00 13.72 3.05 0.00 EAD1EA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
896 3DE7A6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 17258E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
897 4ABC66 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   20.62 30.66 20.62 180.00 90.00 10.06 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
898 EEF55D Window 4ABC66 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 6.69 6.69 6.69 180.00 90.00 3.66 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.54 0.46 4
899 E55A57 Window 4ABC66 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 3.34 3.34 3.34 180.00 90.00 2.74 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.60 0.40 4
900 5B04CF Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   8.18 14.86 8.18 270.00 90.00 4.88 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
901 93D018 Window 5B04CF Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_WEST_0.25 N/A 6.926 No 6.69 6.69 6.69 270.00 90.00 3.66 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
902 FCDEAC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 99468F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
903 AB4E10 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 CA9485 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
904 E7BF7F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 90.00 90.00 5.49 3.05 0.00 B04C98 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
905 FA00FE Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.57 5.57 5.57 90.00 180.00 0.91 6.10 0.00 690A91 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
906 14CDC6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   28.99 28.99 28.99 270.00 180.00 7.32 3.96 0.00 700E69 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
907 39BFFB Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   39.02 39.02 39.02 180.00 180.00 6.10 6.40 0.00 4783F2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
908 167608 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   17.84 17.84 17.84 270.00 180.00 4.88 3.66 0.00 78FEE8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
909 C39FCC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   91.42 91.42 91.42 180.00 0.00 9.56 9.56 0.00 9D1FA7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
910 FLOOR 2 RECEPTION_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   182.83 182.83 182.83 0.00 90.00 182.83 1.00 0.00 FLOOR 2 RECEPTION_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
911 CA9485 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 AB4E10 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
912 2740BD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 4EDE0A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
913 F0AF69 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 B76374 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
914 8D1BC4 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.70 0.30 4
915 9CE650 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 DF91E0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
916 EEECA3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 ADD799 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
917 EE34A3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 815D63 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
918 CFAD9D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 180.00 90.00 7.32 3.05 0.00 DFA4B1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
919 25F524 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 BC25F3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
920 D79C57 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 8A5790 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
921 93F6DE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 97BB21 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
922 8AA0B7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   46.45 46.45 46.45 0.00 90.00 15.24 3.05 0.00 E74038 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
923 1D6CD8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.65 17.65 17.65 0.00 90.00 5.79 3.05 0.00 9FBDA3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
924 427B0D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 E63515 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
925 A72F04 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 10E44F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
926 C51FD6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.90 3.90 3.90 270.00 180.00 1.83 2.13 0.00 513564 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
927 3110A1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 270.00 180.00 1.83 2.44 0.00 E63CF4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
928 F81393 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.25 7.25 7.25 0.00 180.00 3.96 1.83 0.00 C0A312 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
929 4FA380 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.90 3.90 3.90 270.00 180.00 1.83 2.13 0.00 AA1F5C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
930 2FE383 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 270.00 180.00 1.83 2.74 0.00 442699 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
931 3F961C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 270.00 180.00 1.83 2.74 0.00 AF27F8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
932 4B590B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 270.00 180.00 1.83 2.74 0.00 7274F6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
933 20B940 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 90.00 180.00 1.83 2.44 0.00 340FB5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
934 21FC9D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 90.00 180.00 1.83 2.74 0.00 363652 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
935 EB4979 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2.79 2.79 2.79 270.00 180.00 0.61 4.57 0.00 9EBF3E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
936 A5FA3B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.57 5.57 5.57 90.00 180.00 1.22 4.57 0.00 2E1FB7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
937 7A3F36 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.90 3.90 3.90 90.00 0.00 1.83 2.13 0.00 6F1456 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
938 4DAEA4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   23.41 23.41 23.41 180.00 0.00 12.80 1.83 0.00 236CCE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
939 B52A5D Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   17.28 17.28 17.28 0.00 0.00 9.45 1.83 0.00 317B1B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
940 2C7827 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 180.00 0.00 4.27 1.83 0.00 496A6C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
941 FLOOR 2 RECEPTION HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   104.79 104.79 104.79 0.00 90.00 104.79 1.00 0.00 FLOOR 2 RECEPTION HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
942 2D0A7F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 90.00 90.00 5.49 3.05 0.00 87BFF8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
943 E63515 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 427B0D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
944 B04C98 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 270.00 90.00 5.49 3.05 0.00 E7BF7F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
945 50DB3D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 450AA9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
946 115AA8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.55 4.55 4.55 0.00 180.00 2.13 2.13 0.00 68AAF3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
947 CFB630 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.15 7.15 7.15 180.00 180.00 2.13 3.35 0.00 58F893 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
948 E9C76F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.71 11.71 11.71 180.00 0.00 2.13 5.49 0.00 CDCFEE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
949 FLOOR 2 RECEPTION TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   23.41 23.41 23.41 0.00 90.00 23.41 1.00 0.00 FLOOR 2 RECEPTION TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
950 9C568B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 9036B9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
951 B76374 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 F0AF69 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
952 24DA9F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 90.00 90.00 5.49 3.05 0.00 F5AF76 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
953 CADDAF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 270.00 90.00 5.49 3.05 0.00 762874 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
954 10830D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 90.00 180.00 5.49 2.44 0.00 4469CD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
955 EF47B0 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.50 6.50 6.50 180.00 180.00 3.05 2.13 0.00 8E9267 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
956 C3DB37 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.22 10.22 10.22 0.00 180.00 3.05 3.35 0.00 C1737B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
957 F631E4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.03 10.03 10.03 0.00 0.00 5.49 1.83 0.00 137CDB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
958 93EF1F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 180.00 0.00 5.49 3.66 0.00 DF5076 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
959 FLOOR 2 SCHEDULING 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   60.20 60.20 60.20 0.00 90.00 60.20 1.00 0.00 FLOOR 2 SCHEDULING 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
960 9FBDA3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.65 17.65 17.65 180.00 90.00 5.79 3.05 0.00 1D6CD8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
961 87BFF8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 270.00 90.00 5.49 3.05 0.00 2D0A7F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
962 DB7F62 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 90.00 90.00 5.49 3.05 0.00 637F6F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
963 969F22 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.65 17.65 17.65 0.00 90.00 5.79 3.05 0.00 29E445 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
964 795751 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.34 3.34 3.34 90.00 180.00 5.49 0.61 0.00 AFFD01 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
965 6A14D8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.20 9.20 9.20 180.00 180.00 2.74 3.35 0.00 3C43B2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
966 E3963E Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.85 5.85 5.85 270.00 180.00 2.13 2.74 0.00 DE014E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
967 630683 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 270.00 180.00 5.49 2.44 0.00 343C52 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
968 4EB51A Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   31.77 31.77 31.77 90.00 0.00 5.49 5.79 0.00 66FE82 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
969 FLOOR 2 SCHEDULING 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   63.55 63.55 63.55 0.00 90.00 63.55 1.00 0.00 FLOOR 2 SCHEDULING 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
970 390BCF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 C08963 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
971 DE64CC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 2DB420 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
972 F6E717 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 D88779 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
973 58AD84 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 F6D879 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
974 A3E3D6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.20 5.20 5.20 270.00 180.00 2.44 2.13 0.00 DDBA1E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
975 ED1C1D Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.20 5.20 5.20 270.00 0.00 2.44 2.13 0.00 A56694 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
976 FLOOR 2 STORAGE 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.41 10.41 10.41 0.00 90.00 10.41 1.00 0.00 FLOOR 2 STORAGE 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
977 A168ED Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 3B9E2E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
978 ED650B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 F29458 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
979 8E1DCD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 67A7F3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
980 16E41D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 D0731B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
981 1C7FB1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.74 0.74 0.74 0.00 180.00 2.44 0.30 0.00 5136E3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
982 4B217A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.20 5.20 5.20 90.00 180.00 2.13 2.44 0.00 370DB2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
983 A3F683 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.20 5.20 5.20 0.00 180.00 2.13 2.44 0.00 69AE66 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
984 430C7E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.15 11.15 11.15 270.00 0.00 2.44 4.57 0.00 B29215 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
985 FLOOR 2 STORAGE 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   22.30 22.30 22.30 0.00 90.00 22.30 1.00 0.00 FLOOR 2 STORAGE 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
986 70C0BF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 E7055D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
987 211EA4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 491317 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
988 E0D6E9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 ED8563 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
989 BADB96 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 7A03ED Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
990 1E3410 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 90.00 180.00 2.44 5.49 0.00 C1F15F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
991 695D6E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 90.00 0.00 2.44 5.49 0.00 45A523 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
992 FLOOR 2 STORAGE 3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   26.76 26.76 26.76 0.00 90.00 26.76 1.00 0.00 FLOOR 2 STORAGE 3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
993 97B688 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 A8A4FA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
994 290DF3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 83B6E3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
995 4B55FA Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   5.38 8.36 5.38 90.00 90.00 2.74 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
996 DD9F5D Window 4B55FA Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
997 4F0CD7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 AF86E1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
998 4D50C0 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.71 11.71 11.71 270.00 180.00 2.74 4.27 0.00 368A44 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
999 703D3E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.71 11.71 11.71 270.00 0.00 2.74 4.27 0.00 F6DDE6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1000 FLOOR 2 UTILITY_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   23.41 23.41 23.41 0.00 90.00 23.41 1.00 0.00 FLOOR 2 UTILITY_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1001 9C3A6A Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   14.86 20.44 14.86 0.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
1002 15B02B Window 9C3A6A Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
1003 820282 Window 9C3A6A Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.59 0.41 4
1004 5C7E1E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 90.00 90.00 10.06 3.05 0.00 35051E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1005 B5E37D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 0.00 90.00 0.61 3.05 0.00 9969B3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1006 8D1659 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 270.00 90.00 6.10 3.05 0.00 BEDECA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1007 E88E01 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   48.31 48.31 48.31 180.00 90.00 15.85 3.05 0.00 738F37 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1008 4CE123 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 4AD319 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1009 E55935 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 0.00 90.00 7.32 3.05 0.00 F41621 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1010 C52EE0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   3.72 3.72 3.72 0.00 90.00 1.22 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.69 0.31 4
1011 9AB0BF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 F22E15 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1012 1A8E2A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2.60 2.60 2.60 270.00 180.00 2.13 1.22 0.00 827528 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1013 E21951 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 180.00 180.00 1.83 2.74 0.00 388F10 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1014 517DFC Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   33.26 33.26 33.26 270.00 180.00 5.77 5.77 0.00 BFB8E1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 10
1015 CEC6B4 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   15.61 15.61 15.61 0.00 180.00 6.40 2.44 0.00 290CAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1016 1A95D5 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.66 13.66 13.66 270.00 180.00 3.70 3.70 0.00 5CB500 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 8
1017 5724CC Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.57 5.57 5.57 180.00 180.00 6.10 0.91 0.00 B7E9B3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1018 7FA5FF Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 270.00 180.00 5.49 2.44 0.00 9114B7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1019 E43750 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   40.88 40.88 40.88 0.00 180.00 6.10 6.71 0.00 803791 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1020 E9C9E1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2.79 2.79 2.79 0.00 180.00 0.61 4.57 0.00 79376C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1021 CE626A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 270.00 180.00 5.49 3.66 0.00 28F0DE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1022 541C9C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.18 4.18 4.18 270.00 180.00 1.52 2.74 0.00 5DACB5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1023 F77E4B Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   34.37 34.37 34.37 90.00 0.00 5.86 5.86 0.00 D6F20A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
1024 287E3B Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   122.63 122.63 122.63 270.00 0.00 10.06 12.19 0.00 535D54 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1025 FLOOR 2 WORK_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   259.39 259.39 259.39 0.00 90.00 259.39 1.00 0.00 FLOOR 2 WORK_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1026 830326 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 AB568E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1027 EAD1EA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.81 41.81 41.81 180.00 90.00 13.72 3.05 0.00 23C13E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1028 1C33AD Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
1029 52D809 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ECDEDB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1030 450AA9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 50DB3D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1031 29E445 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.65 17.65 17.65 180.00 90.00 5.79 3.05 0.00 969F22 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1032 B0FF3A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   46.45 46.45 46.45 180.00 90.00 15.24 3.05 0.00 34B8D8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1033 9036B9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 9C568B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1034 5EE606 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 247FD8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1035 3FBBC8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 0.00 90.00 7.32 3.05 0.00 F976A9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1036 B5099E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 E7EC3B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1037 7A8E3F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 942718 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1038 32BAA7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 B51929 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1039 738F37 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   48.31 48.31 48.31 0.00 90.00 15.85 3.05 0.00 E88E01 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1040 B94E9A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 5DBD9D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1041 83658D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.92 4.92 4.92 270.00 180.00 2.22 2.22 0.00 A02892 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
1042 CAC621 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.69 6.69 6.69 270.00 180.00 1.83 3.66 0.00 D647E0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1043 E90253 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.15 11.15 11.15 270.00 180.00 1.83 6.10 0.00 D60B94 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1044 FD4C82 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.21 1.21 1.21 180.00 180.00 3.96 0.30 0.00 CABD0E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1045 F5C927 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.75 9.75 9.75 0.00 180.00 6.40 1.52 0.00 B754EC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1046 362FF8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 270.00 180.00 1.83 2.44 0.00 D6D2A5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1047 21F419 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.65 0.65 0.65 180.00 180.00 2.13 0.30 0.00 4E5019 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1048 283EC6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 180.00 180.00 2.44 1.83 0.00 F62393 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1049 C5B569 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.84 0.84 0.84 180.00 180.00 2.74 0.30 0.00 2CB843 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1050 D29B01 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.07 3.07 3.07 180.00 180.00 10.06 0.30 0.00 D44BF1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1051 FFE9D0 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   28.80 28.80 28.80 270.00 180.00 1.52 18.90 0.00 BD75DE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1052 7A8C4C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.49 1.49 1.49 180.00 180.00 4.88 0.30 0.00 709E99 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1053 957242 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   77.48 77.48 77.48 0.00 0.00 42.37 1.83 0.00 14A82B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1054 FLOOR 2 WORK HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   154.96 154.96 154.96 0.00 90.00 154.96 1.00 0.00 FLOOR 2 WORK HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1055 F22E15 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 9AB0BF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1056 49DA28 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 BDE9D9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1057 8C4550 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 E0C0A7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1058 6CC177 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1059 9969B3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 180.00 90.00 0.61 3.05 0.00 B5E37D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1060 4C4C25 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 180.00 180.00 2.74 1.83 0.00 9BB388 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1061 FC3B6D Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 90.00 0.00 1.83 2.74 0.00 F07866 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1062 FLOOR 2 WORK TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 2 WORK TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1063 34B8D8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   46.45 46.45 46.45 0.00 90.00 15.24 3.05 0.00 B0FF3A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1064 E74038 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   46.45 46.45 46.45 180.00 90.00 15.24 3.05 0.00 8AA0B7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1065 762874 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 90.00 90.00 5.49 3.05 0.00 CADDAF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1066 637F6F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 270.00 90.00 5.49 3.05 0.00 DB7F62 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1067 C6DCD1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.71 11.71 11.71 270.00 180.00 5.49 2.13 0.00 F665B1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1068 1BDF58 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   18.39 18.39 18.39 270.00 180.00 5.49 3.35 0.00 661D88 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1069 15A915 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.85 5.85 5.85 180.00 180.00 2.74 2.13 0.00 88D2F8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1070 1CC550 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.85 5.85 5.85 180.00 180.00 2.74 2.13 0.00 D1AFC9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1071 55622A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 180.00 180.00 2.74 1.83 0.00 D21333 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1072 5D03DA Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.85 5.85 5.85 180.00 180.00 2.74 2.13 0.00 A7115C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1073 AE5078 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.18 4.18 4.18 270.00 180.00 1.52 2.74 0.00 E2AB17 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1074 774CCD Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.25 3.25 3.25 180.00 180.00 1.52 2.13 0.00 BB097B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1075 F6FE66 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   23.50 23.50 23.50 0.00 180.00 7.01 3.35 0.00 5C05FF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1076 1DCC9F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   38.46 38.46 38.46 90.00 0.00 5.49 7.01 0.00 AE769E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1077 47890C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.90 3.90 3.90 0.00 0.00 2.13 1.83 0.00 9AC2BE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1078 F7E82F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 180.00 0.00 2.13 3.66 0.00 484FB1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1079 7FDC1A Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   23.41 23.41 23.41 90.00 0.00 5.49 4.27 0.00 25A972 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1080 F02E9C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.03 10.03 10.03 270.00 0.00 5.49 1.83 0.00 628387 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1081 FLOOR 2 X-RAY_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   167.23 167.23 167.23 0.00 90.00 167.23 1.00 0.00 FLOOR 2 X-RAY_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1082 137A14 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 CD21EC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1083 F2515C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 AAD404 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1084 71A3C4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 EF4AD1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1085 46292D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 301CE0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1086 9AC2BE Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.90 3.90 3.90 270.00 180.00 1.83 2.13 0.00 47890C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1087 FLOOR 3 DRESSING ROOM ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   3.90 3.90 3.90 270.00 0.00 1.83 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1088 FLOOR 3 DRESSING ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7.80 7.80 7.80 0.00 90.00 7.80 1.00 0.00 FLOOR 3 DRESSING ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1089 5EAFB3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 DF47AC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1090 E0CB0D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 270.00 90.00 6.10 3.05 0.00 F9DFA4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1091 FB63A7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 0.00 90.00 0.61 3.05 0.00 D0C6E8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1092 79D0A5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 8646EF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1093 212961 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 90.00 90.00 10.06 3.05 0.00 B972D4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1094 C1AD55 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 C4A89B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1095 B75832 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 8316C5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1096 F7D24D Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   3.72 3.72 3.72 0.00 90.00 1.22 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
1097 D6F20A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   34.37 34.37 34.37 270.00 180.00 5.86 5.86 0.00 F77E4B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
1098 FLOOR 3 ELEVATOR HALL ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   34.37 34.37 34.37 0.00 0.00 5.86 5.86 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
1099 FLOOR 3 ELEVATOR HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   68.75 68.75 68.75 0.00 90.00 68.75 1.00 0.00 FLOOR 3 ELEVATOR HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1100 C3FB92 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 55BD05 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1101 AAD404 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 F2515C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1102 2272E0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 270.00 90.00 5.49 3.05 0.00 D6005B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1103 E13FC4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 D75504 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1104 506DC0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 EA4A9E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1105 628387 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.03 10.03 10.03 270.00 180.00 5.49 1.83 0.00 F02E9C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1106 FLOOR 3 HUMID ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   10.03 10.03 10.03 270.00 0.00 5.49 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1107 FLOOR 3 HUMID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   20.07 20.07 20.07 0.00 90.00 20.07 1.00 0.00 FLOOR 3 HUMID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1108 1D53D9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 460DA4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1109 FC22D1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.54 0.46 4
1110 DD2E2D Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1111 C4A89B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 C1AD55 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1112 B840A7 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.85 5.85 5.85 0.00 180.00 2.74 2.13 0.00 F6E6D8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1113 FLOOR 3 JANITOR ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   5.85 5.85 5.85 0.00 0.00 2.74 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1114 FLOOR 3 JANITOR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   11.71 11.71 11.71 0.00 90.00 11.71 1.00 0.00 FLOOR 3 JANITOR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1115 C86932 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 812B32 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1116 B1856A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 9AB92B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1117 AEA170 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 1F37D7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1118 82303C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 A5FC87 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1119 D10EC7 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.15 11.15 11.15 0.00 180.00 3.66 3.05 0.00 245972 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1120 FLOOR 3 LOCKER ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   11.15 11.15 11.15 0.00 0.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1121 FLOOR 3 LOCKER_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   22.30 22.30 22.30 0.00 90.00 22.30 1.00 0.00 FLOOR 3 LOCKER_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1122 AA26DE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 180.00 90.00 7.01 3.05 0.00 CC8990 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1123 68A2D7 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   15.79 21.37 15.79 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1124 9BA05A Window 68A2D7 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1125 C639E8 Window 68A2D7 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1126 824F52 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.15 24.15 24.15 90.00 90.00 7.92 3.05 0.00 44775D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1127 D2E9BA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 EEFDE3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1128 D197DA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 AC05CF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1129 7C7BE2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 270.00 90.00 4.88 3.05 0.00 E0FD95 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1130 812B32 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 C86932 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1131 3B5B94 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.94 13.94 13.94 180.00 180.00 4.57 3.05 0.00 4E1563 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1132 60F383 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.13 6.13 6.13 90.00 180.00 10.06 0.61 0.00 567037 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1133 F7BE2F Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.90 20.90 20.90 90.00 180.00 4.57 4.57 0.00 917AB5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1134 B29215 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.15 11.15 11.15 0.00 180.00 4.57 2.44 0.00 430C7E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1135 52FA3B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   18.39 18.39 18.39 90.00 180.00 10.06 1.83 0.00 4180E7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1136 FLOOR 3 LOUNGE ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   70.51 70.51 70.51 270.00 0.00 10.06 7.01 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1137 FLOOR 3 LOUNGE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   141.03 141.03 141.03 0.00 90.00 141.03 1.00 0.00 FLOOR 3 LOUNGE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1138 6D960C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 270.00 90.00 4.88 3.05 0.00 CBFB94 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1139 9AB92B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 B1856A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1140 CE3FEF Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   6.97 11.15 6.97 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1141 A2790A Window CE3FEF Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 4.18 4.18 4.18 0.00 90.00 2.74 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1142 E0FD95 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 90.00 90.00 4.88 3.05 0.00 7C7BE2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1143 B46F2C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   17.84 17.84 17.84 0.00 180.00 3.66 4.88 0.00 6B3E65 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1144 FLOOR 3 LOUNGE TOILET ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   17.84 17.84 17.84 0.00 0.00 3.66 4.88 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1145 FLOOR 3 LOUNGE TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   35.67 35.67 35.67 0.00 90.00 35.67 1.00 0.00 FLOOR 3 LOUNGE TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1146 6F0E5D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 60F634 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1147 D67C59 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   23.23 23.23 23.23 270.00 90.00 7.62 3.05 0.00 98A52C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1148 6C68C2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 3613B7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1149 CE618F Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   15.29 23.23 15.29 90.00 90.00 7.62 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
1150 79FCEE Window CE618F Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 3.97 3.97 3.97 90.00 90.00 2.44 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1151 EDE617 Window CE618F Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 3.97 3.97 3.97 90.00 90.00 2.44 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
1152 1DC177 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.52 32.52 32.52 0.00 180.00 4.27 7.62 0.00 31B3DF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1153 FLOOR 3 MECHANICAL ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   32.52 32.52 32.52 0.00 0.00 4.27 7.62 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1154 FLOOR 3 MECHANICAL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   65.03 65.03 65.03 0.00 90.00 65.03 1.00 0.00 FLOOR 3 MECHANICAL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1155 A11DA8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   23.23 23.23 23.23 90.00 90.00 7.62 3.05 0.00 4C6DBF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1156 BC2C22 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 D68874 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1157 44775D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.15 24.15 24.15 270.00 90.00 7.92 3.05 0.00 824F52 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1158 CDD69A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 5C690E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1159 F5E7FE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CF2803 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1160 4BF787 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 869ED5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1161 98A52C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   23.23 23.23 23.23 90.00 90.00 7.62 3.05 0.00 D67C59 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1162 6310E5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 6EC372 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1163 2E74E6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   27.87 27.87 27.87 90.00 180.00 15.24 1.83 0.00 BFEF28 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1164 FLOOR 3 MECHANICAL HALL ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   27.87 27.87 27.87 0.00 0.00 1.83 15.24 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1165 FLOOR 3 MECHANICAL HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   55.74 55.74 55.74 0.00 90.00 55.74 1.00 0.00 FLOOR 3 MECHANICAL HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1166 5FDFAE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   85.47 85.47 85.47 180.00 90.00 28.04 3.05 0.00 D7E6B2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1167 C7B7AA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 FE5F03 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1168 B972D4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 270.00 90.00 10.06 3.05 0.00 212961 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1169 5ADC59 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   49.24 68.75 49.24 0.00 90.00 22.56 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
1170 C61F0D Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1171 7248C5 Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.56 0.44 4
1172 29FA28 Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1173 F0B23F Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1174 EEC10E Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1175 944FCE Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
1176 C41399 Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1177 7DCAF1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 7C0F83 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1178 CBFB94 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 90.00 90.00 4.88 3.05 0.00 6D960C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1179 A5FC87 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 82303C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1180 A72B2F Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   30.66 30.66 30.66 90.00 180.00 10.06 3.05 0.00 F0D8EE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1181 538FE6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   18.39 18.39 18.39 90.00 180.00 10.06 1.83 0.00 B9D6E3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1182 8A695C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   25.08 25.08 25.08 0.00 180.00 5.49 4.57 0.00 DA760E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1183 45A523 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 0.00 180.00 5.49 2.44 0.00 695D6E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1184 F94215 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   18.39 18.39 18.39 0.00 180.00 1.83 10.06 0.00 B4F89F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1185 C27BD7 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   16.72 16.72 16.72 90.00 180.00 3.05 5.49 0.00 C45BF3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1186 AE8664 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.79 36.79 36.79 90.00 180.00 10.06 3.66 0.00 5D2769 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1187 535D54 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   122.63 122.63 122.63 0.00 180.00 12.19 10.06 0.00 287E3B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1188 FLOOR 3 OFFICE ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   282.05 282.05 282.05 180.00 0.00 28.04 10.06 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1189 FLOOR 3 OFFICE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   564.11 564.11 564.11 0.00 90.00 564.11 1.00 0.00 FLOOR 3 OFFICE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1190 CC8990 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 0.00 90.00 7.01 3.05 0.00 AA26DE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1191 D4F411 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.62 0.38 4
1192 2F3F2A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   48.31 48.31 48.31 180.00 90.00 15.85 3.05 0.00 855B07 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1193 869ED5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 4BF787 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1194 D75504 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 E13FC4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1195 E80026 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 D13E00 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1196 A03B2E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 BF7411 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1197 133349 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 111907 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1198 7DCD8A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 C9F74B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1199 D7E6B2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   85.47 85.47 85.47 0.00 90.00 28.04 3.05 0.00 5FDFAE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1200 8646EF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 79D0A5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1201 840387 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   39.02 39.02 39.02 180.00 90.00 12.80 3.05 0.00 4CCA8D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1202 14A82B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   77.48 77.48 77.48 270.00 180.00 1.83 42.37 0.00 957242 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1203 FLOOR 3 OFFICE HALL ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   77.48 77.48 77.48 270.00 0.00 1.83 42.37 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1204 FLOOR 3 OFFICE HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   154.96 154.96 154.96 0.00 90.00 154.96 1.00 0.00 FLOOR 3 OFFICE HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1205 460DA4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 1D53D9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1206 8316C5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 B75832 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1207 D5E94D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 9BA592 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1208 B35AD6 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1209 D0C6E8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 180.00 90.00 0.61 3.05 0.00 FB63A7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1210 F07866 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 270.00 180.00 1.83 2.74 0.00 FC3B6D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1211 FLOOR 3 OFFICE TOILET ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   5.02 5.02 5.02 270.00 0.00 1.83 2.74 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1212 FLOOR 3 OFFICE TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 3 OFFICE TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1213 D22917 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   11.14 18.58 11.14 90.00 90.00 6.10 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1214 95BA33 Window D22917 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 3.72 3.72 3.72 90.00 90.00 1.83 2.03 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1215 F27282 Window D22917 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 3.72 3.72 3.72 90.00 90.00 1.83 2.03 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1216 4497EF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 270.00 90.00 6.10 3.05 0.00 C050FD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1217 C1BC97 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   38.09 60.39 38.09 180.00 90.00 19.81 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1218 3DB407 Window C1BC97 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 5.57 5.57 5.57 180.00 90.00 3.05 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1219 3DADE2 Window C1BC97 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 5.57 5.57 5.57 180.00 90.00 3.05 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1220 DF3E2C Window C1BC97 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 5.57 5.57 5.57 180.00 90.00 3.05 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1221 5031C8 Window C1BC97 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 5.57 5.57 5.57 180.00 90.00 3.05 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1222 F3F6EA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 E7A265 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1223 BCAAD1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   34.37 34.37 34.37 0.00 90.00 11.28 3.05 0.00 958E3F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1224 E5720F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 C78153 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1225 8E83C6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.41 10.41 10.41 90.00 180.00 2.44 4.27 0.00 D1A180 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1226 D14D65 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   31.22 31.22 31.22 90.00 180.00 3.66 8.53 0.00 240A7C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1227 CDCA72 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.95 5.95 5.95 90.00 180.00 2.44 2.44 0.00 7149EA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1228 339B46 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 90.00 180.00 2.44 1.83 0.00 C588CC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1229 7F8407 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   44.59 44.59 44.59 270.00 180.00 6.10 7.32 0.00 D74115 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1230 F69079 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 90.00 180.00 3.66 2.13 0.00 C0697F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1231 A56694 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.20 5.20 5.20 90.00 180.00 2.44 2.13 0.00 ED1C1D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1232 3C8351 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.15 11.15 11.15 90.00 180.00 6.10 1.83 0.00 6C1891 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1233 FLOOR 3 PHYICAL THERAPY 1 ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   120.77 120.77 120.77 180.00 0.00 19.81 6.10 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1234 FLOOR 3 PHYSICAL THERAPY 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   241.55 241.55 241.55 0.00 90.00 241.55 1.00 0.00 FLOOR 3 PHYSICAL THERAPY 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1235 958E3F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   34.37 34.37 34.37 180.00 90.00 11.28 3.05 0.00 BCAAD1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1236 27D999 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 270.00 90.00 4.88 3.05 0.00 2451B7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1237 55BD05 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 C3FB92 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1238 8BCB23 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 90.00 90.00 4.88 3.05 0.00 EFFB3B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1239 5C690E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 CDD69A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1240 E49C43 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 D4C22E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1241 EF4AD1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 71A3C4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1242 8FB568 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.29 9.29 9.29 180.00 180.00 3.05 3.05 0.00 5065F0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1243 C271D9 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.57 5.57 5.57 180.00 180.00 1.83 3.05 0.00 D4A2A4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1244 1EE332 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.50 6.50 6.50 180.00 180.00 2.13 3.05 0.00 E1B973 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1245 96623F Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.43 7.43 7.43 180.00 180.00 2.44 3.05 0.00 B352F7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1246 F17575 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   8.92 8.92 8.92 180.00 180.00 1.83 4.88 0.00 30A09C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1247 317B1B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   17.28 17.28 17.28 0.00 180.00 9.45 1.83 0.00 B52A5D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1248 FLOOR 3 PHYSICAL THERAPY 2 ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   55.00 55.00 55.00 90.00 0.00 4.88 11.28 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1249 FLOOR 3 PHYSICAL THERAPY 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   110.00 110.00 110.00 0.00 90.00 110.00 1.00 0.00 FLOOR 3 PHYSICAL THERAPY 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1250 44D36C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 2BC70D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1251 CD21EC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 137A14 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1252 BF7411 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 A03B2E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1253 EA4A9E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 506DC0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1254 484FB1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 90.00 180.00 3.66 2.13 0.00 F7E82F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1255 FLOOR 3 PHYSICAL THERAPY TOILET ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   7.80 7.80 7.80 90.00 0.00 3.66 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1256 FLOOR 3 PHYSICAL THERAPY TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   15.61 15.61 15.61 0.00 90.00 15.61 1.00 0.00 FLOOR 3 PHYSICAL THERAPY TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1257 D4C22E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 E49C43 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1258 6EC372 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 6310E5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1259 301CE0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 46292D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1260 89A685 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 180143 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1261 137CDB Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.03 10.03 10.03 180.00 180.00 5.49 1.83 0.00 F631E4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1262 FLOOR 3 STORAGE 1 ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   10.03 10.03 10.03 180.00 0.00 5.49 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1263 FLOOR 3 STORAGE 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   20.07 20.07 20.07 0.00 90.00 20.07 1.00 0.00 FLOOR 3 STORAGE 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1264 FE5F03 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 C7B7AA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1265 1F37D7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 AEA170 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1266 AC05CF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 D197DA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1267 C9F74B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 7DCD8A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1268 63B825 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 180.00 180.00 3.66 2.13 0.00 F17DF7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1269 FLOOR 3 STORAGE 2 ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   7.80 7.80 7.80 180.00 0.00 3.66 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1270 FLOOR 3 STORAGE 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   15.61 15.61 15.61 0.00 90.00 15.61 1.00 0.00 FLOOR 3 STORAGE 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1271 C78153 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 E5720F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1272 D13E00 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 E80026 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1273 2451B7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 90.00 90.00 4.88 3.05 0.00 27D999 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1274 624E8A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 2336C8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1275 D6005B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 90.00 90.00 5.49 3.05 0.00 2272E0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1276 2B4713 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.01 13.01 13.01 180.00 180.00 4.27 3.05 0.00 3AEAAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1277 25A972 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   23.41 23.41 23.41 0.00 180.00 4.27 5.49 0.00 7FDC1A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1278 496A6C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 270.00 180.00 1.83 4.27 0.00 2C7827 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1279 FLOOR 3 TREATMENT ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   44.22 44.22 44.22 90.00 0.00 10.36 4.27 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1280 FLOOR 3 TREATMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   88.44 88.44 88.44 0.00 90.00 88.44 1.00 0.00 FLOOR 3 TREATMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1281 C050FD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 90.00 90.00 6.10 3.05 0.00 4497EF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1282 8DA7DB Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   23.41 39.02 23.41 180.00 90.00 12.80 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1283 C087D0 Window 8DA7DB Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 5.57 5.57 5.57 180.00 90.00 3.05 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1284 D2CA75 Window 8DA7DB Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 5.57 5.57 5.57 180.00 90.00 3.05 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1285 B0FB49 Window 8DA7DB Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 4.46 4.46 4.46 180.00 90.00 2.44 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1286 F8F69A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 270.00 90.00 7.32 3.05 0.00 192E17 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1287 4CCA8D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   39.02 39.02 39.02 0.00 90.00 12.80 3.05 0.00 840387 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1288 2336C8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 624E8A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1289 38B339 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   17.84 27.87 17.84 270.00 90.00 9.14 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.56 0.44 4
1290 FE9BC9 Window 38B339 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_WEST_0.25 N/A 6.926 No 3.34 3.34 3.34 270.00 90.00 1.83 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
1291 9DF7DE Window 38B339 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_WEST_0.25 N/A 6.926 No 3.34 3.34 3.34 270.00 90.00 1.83 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
1292 D0BE44 Window 38B339 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_WEST_0.25 N/A 6.926 No 3.34 3.34 3.34 270.00 90.00 1.83 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.61 0.39 4
1293 F4E5F5 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   33.45 33.45 33.45 180.00 180.00 3.66 9.14 0.00 A4BE81 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1294 AA7BE2 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   16.72 16.72 16.72 180.00 180.00 1.83 9.14 0.00 E26130 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1295 68EB71 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   50.17 50.17 50.17 180.00 180.00 5.49 9.14 0.00 906F5E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1296 66FE82 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   31.77 31.77 31.77 270.00 180.00 5.49 5.79 0.00 4EB51A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1297 948D7B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   16.72 16.72 16.72 180.00 180.00 1.83 9.14 0.00 E9AEFF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1298 236CCE Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   23.41 23.41 23.41 0.00 180.00 12.80 1.83 0.00 4DAEA4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1299 AE769E Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   38.46 38.46 38.46 90.00 180.00 5.49 7.01 0.00 1DCC9F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1300 FLOOR 3 UNDEVELOPED 1 ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   210.70 210.70 210.70 0.00 0.00 12.80 16.46 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1301 FLOOR 3 UNDEVELOPED 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   421.41 421.41 421.41 0.00 90.00 421.41 1.00 0.00 FLOOR 3 UNDEVELOPED 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1302 BE5F2F Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   10.41 14.86 10.41 270.00 90.00 4.88 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
1303 6B5226 Window BE5F2F Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_WEST_0.25 N/A 6.926 No 4.46 4.46 4.46 270.00 90.00 3.66 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
1304 D5C4E5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 E2AFEB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1305 C1B522 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 573330 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1306 1DEE26 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   28.24 37.16 28.24 180.00 90.00 12.19 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
1307 8F59F7 Window 1DEE26 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 4.46 4.46 4.46 180.00 90.00 3.66 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
1308 44F571 Window 1DEE26 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 4.46 4.46 4.46 180.00 90.00 3.66 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.56 0.44 4
1309 192E17 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 90.00 90.00 7.32 3.05 0.00 F8F69A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1310 855B07 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   48.31 48.31 48.31 0.00 90.00 15.85 3.05 0.00 2F3F2A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1311 9D1FA7 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   91.42 91.42 91.42 270.00 180.00 9.56 9.56 0.00 C39FCC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
1312 6F1456 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.90 3.90 3.90 180.00 180.00 2.13 1.83 0.00 7A3F36 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1313 CDCFEE Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.71 11.71 11.71 0.00 180.00 2.13 5.49 0.00 E9C76F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1314 FLOOR 3 UNDEVELOPED 2 ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   107.02 107.02 107.02 180.00 0.00 10.35 10.35 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
1315 FLOOR 3 UNDEVELOPED 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   214.05 214.05 214.05 0.00 90.00 214.05 1.00 0.00 FLOOR 3 UNDEVELOPED 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1316 111907 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 133349 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1317 CF2803 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 F5E7FE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1318 180143 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 89A685 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1319 2BC70D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 44D36C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1320 DF5076 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 0.00 180.00 5.49 3.66 0.00 93EF1F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1321 FLOOR 3 UTILITY ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   20.07 20.07 20.07 0.00 0.00 5.49 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1322 FLOOR 3 UTILITY_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   40.13 40.13 40.13 0.00 90.00 40.13 1.00 0.00 FLOOR 3 UTILITY_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1323 3613B7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 6C68C2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1324 C86329 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   26.18 38.09 26.18 90.00 90.00 12.50 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1325 6BD844 Window C86329 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1326 86D536 Window C86329 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1327 BAF71D Window C86329 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1328 3833A2 Window C86329 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 2.98 2.98 2.98 90.00 90.00 1.83 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1329 E7A265 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 F3F6EA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1330 4C6DBF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   23.23 23.23 23.23 270.00 90.00 7.62 3.05 0.00 A11DA8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1331 EFFB3B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 270.00 90.00 4.88 3.05 0.00 8BCB23 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1332 8480E5 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   41.62 41.62 41.62 180.00 180.00 4.27 9.75 0.00 9BB582 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1333 F6DDE6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.71 11.71 11.71 0.00 180.00 4.27 2.74 0.00 703D3E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1334 FLOOR 3 WORK ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   53.33 53.33 53.33 90.00 0.00 12.50 4.27 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1335 FLOOR 3 WORK_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   106.65 106.65 106.65 0.00 90.00 106.65 1.00 0.00 FLOOR 3 WORK_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1336 986A05 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 C1C64E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1337 DFC6F0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   18.52 19.51 18.52 90.00 90.00 2.13 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1338 2111A1 Window DFC6F0 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_EAST_0.25 N/A 6.926 No 0.99 0.99 0.99 90.00 90.00 0.61 1.63 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1339 6EE166 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 B2F07D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1340 A28F01 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 180.00 90.00 6.10 3.05 0.00 204CB9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1341 DE6295 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 BFA29B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1342 D68874 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 BC2C22 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1343 88E360 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   51.71 66.89 51.71 0.00 90.00 7.32 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
1344 9CB8E5 Door 88E360 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
1345 9BC521 Window 88E360 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 5.71 5.71 5.71 0.00 90.00 3.75 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1346 142781 Window 88E360 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 5.57 5.57 5.57 0.00 90.00 3.66 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1347 E4A528 Door 88E360 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
1348 16BE00 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 A8FC82 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1349 60F634 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 6F0E5D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1350 E7B55F Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   11.15 11.15 11.15 180.00 90.00 1.22 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.70 0.30 4
1351 EEFDE3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 D2E9BA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1352 NE STAIR SLAB Floor   CTF - ConductionTransferFunction NESTAIRSLAB_FFACTOR 0.997 0.803   15.61 15.61 15.61 0.00 180.00 7.32 2.13 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1353 NE STAIR ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   15.61 15.61 15.61 0.00 0.00 7.32 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1354 NE STAIR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   31.22 31.22 31.22 0.00 90.00 31.22 1.00 0.00 NE STAIR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1355 FB3814 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   17.56 19.51 17.56 180.00 90.00 2.13 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.68 0.32 4
1356 24BAF7 Door FB3814 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.71 0.29 4
1357 976E3F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 90.00 90.00 6.10 3.05 0.00 43A2A2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1358 FCD12D Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   53.79 55.74 53.79 270.00 90.00 6.10 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1359 19E57D Door FCD12D CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1360 D699FF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 7F6FC2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1361 F9DFA4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 90.00 90.00 6.10 3.05 0.00 E0CB0D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1362 BDE9D9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 49DA28 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1363 BEDECA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 90.00 90.00 6.10 3.05 0.00 8D1659 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1364 9BA592 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 D5E94D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1365 NW ELEVATOR SLAB Floor   CTF - ConductionTransferFunction NWELEVATORSLAB_FFACTOR 0.913 0.747   13.01 13.01 13.01 90.00 180.00 6.10 2.13 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1366 NW ELEVATOR ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   13.01 13.01 13.01 90.00 0.00 6.10 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1367 NW ELEVATOR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   26.01 26.01 26.01 0.00 90.00 26.01 1.00 0.00 NW ELEVATOR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1368 5507DC Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   20.35 22.30 20.35 270.00 90.00 2.44 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
1369 EDE769 Door 5507DC CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.68 0.32 4
1370 2E2D0C Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   53.79 66.89 53.79 0.00 90.00 7.32 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1371 E74902 Window 2E2D0C Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 5.57 5.57 5.57 0.00 90.00 3.66 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1372 93BBC3 Window 2E2D0C Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 N/A 6.926 No 5.57 5.57 5.57 0.00 90.00 3.66 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1373 1C9872 Door 2E2D0C CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1374 FA9233 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 822161 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1375 AF0124 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   22.30 22.30 22.30 90.00 90.00 2.44 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.68 0.32 4
1376 74AB49 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 180.00 90.00 4.88 3.05 0.00 92A2CB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1377 DF47AC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 5EAFB3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1378 F41621 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 180.00 90.00 7.32 3.05 0.00 E55935 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1379 7C0F83 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 7DCAF1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1380 NW STAIR SLAB Floor   CTF - ConductionTransferFunction NWSTAIRSLAB_FFACTOR 0.997 0.803   17.84 17.84 17.84 270.00 180.00 2.44 7.32 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1381 NW STAIR ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   17.84 17.84 17.84 270.00 0.00 2.44 7.32 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1382 NW STAIR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   35.67 35.67 35.67 0.00 90.00 35.67 1.00 0.00 NW STAIR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1383 8FF821 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 368E02 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1384 850EA7 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   32.33 33.45 32.33 180.00 90.00 3.66 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
1385 C635A6 Window 850EA7 Window5 Detailed Fenestration NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 N/A 6.926 No 1.11 1.11 1.11 180.00 90.00 0.91 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
1386 1068C8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 BAD27A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1387 E2AFEB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 D5C4E5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1388 99468F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 FCDEAC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1389 17258E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 3DE7A6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1390 573330 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 C1B522 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1391 270BCE Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   20.35 22.30 20.35 270.00 90.00 2.44 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1392 F402E9 Door 270BCE CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
1393 SW STAIR SLAB Floor   CTF - ConductionTransferFunction SWSTAIRSLAB_FFACTOR 0.997 0.803   8.92 8.92 8.92 270.00 180.00 2.44 3.66 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1394 SW STAIR ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   8.92 8.92 8.92 180.00 0.00 3.66 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1395 SW STAIR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   17.84 17.84 17.84 0.00 90.00 17.84 1.00 0.00 SW STAIR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 FLOOR 1 ANESTHESIA RunPeriod: RUNPERIOD 1 0.7292940725 1.1475640256 Pass Pass 0.2178415438 0.4013900320 Pass Pass
2 FLOOR 1 BIO HAZ RunPeriod: RUNPERIOD 1 0.1296170686 0.1909472872 Pass Pass 0.2043681096 0.3991223726 Pass Pass
3 FLOOR 1 CAFE RunPeriod: RUNPERIOD 1 7.9614314668E-006 7.8543358620E-006 Pass Pass 5.1519202559E-002 8.6588109578E-002 Pass Pass
4 FLOOR 1 CLEAN RunPeriod: RUNPERIOD 1 0.6282858117 0.9797986423 Pass Pass 0.2989616129 0.5913857726 Pass Pass
5 FLOOR 1 CLEAN WORK RunPeriod: RUNPERIOD 1 0.5611716292 0.8502981771 Pass Pass 0.2906537337 0.5577714351 Pass Pass
6 FLOOR 1 DICTATION RunPeriod: RUNPERIOD 1 0.1655243716 0.2200010657 Pass Pass 0.2043072020 0.4013550618 Pass Pass
7 FLOOR 1 DRESSING ROOM RunPeriod: RUNPERIOD 1 0.2234547207 0.3376315086 Pass Pass 0.2032015174 0.3982706304 Pass Pass
8 FLOOR 1 ELECTRICAL ROOM RunPeriod: RUNPERIOD 1 0.2952343467 0.4138162410 Pass Pass 0.2032316659 0.4016099656 Pass Pass
9 FLOOR 1 ELEVATOR PUMP ROOM RunPeriod: RUNPERIOD 1 2.0153128429E-005 1.8507401776E-005 Pass Pass 1.5332122906E-002 1.0925534844E-002 Pass Pass
10 FLOOR 1 HUMID RunPeriod: RUNPERIOD 1 0.1794671619 0.2576631861 Pass Pass 0.2046240814 0.4003660999 Pass Pass
11 FLOOR 1 IT HALL RunPeriod: RUNPERIOD 1 0.1237080424 0.1704299072 Pass Pass 0.2036560621 0.4004940834 Pass Pass
12 FLOOR 1 IT ROOM RunPeriod: RUNPERIOD 1 0.1536141169 0.2146426532 Pass Pass 0.2041434081 0.4008789566 Pass Pass
13 FLOOR 1 LOBBY RunPeriod: RUNPERIOD 1 0.2453670547 0.3543274049 Pass Pass 0.2039132875 0.3989899360 Pass Pass
14 FLOOR 1 LOBBY HALL RunPeriod: RUNPERIOD 1 0.1693276096 0.2538440846 Pass Pass 0.2041319701 0.3996406457 Pass Pass
15 FLOOR 1 LOBBY TOILET RunPeriod: RUNPERIOD 1 0.6834042552 1.0330713358 Pass Pass 0.2347724806 0.4293428979 Pass Pass
16 FLOOR 1 LOCKER ROOM RunPeriod: RUNPERIOD 1 0.2379686541 0.3112810100 Pass Pass 0.2036440975 0.4019016856 Pass Pass
17 FLOOR 1 LOCKER ROOM HALL RunPeriod: RUNPERIOD 1 0.1266174897 0.1711503059 Pass Pass 0.2033994096 0.4008367431 Pass Pass
18 FLOOR 1 LOUNGE RunPeriod: RUNPERIOD 1 0.2225566648 0.2853093198 Pass Pass 0.2036645870 0.4022111733 Pass Pass
19 FLOOR 1 MED GAS RunPeriod: RUNPERIOD 1 0.2092409721 0.3126887682 Pass Pass 0.2031822926 0.3973666268 Pass Pass
20 FLOOR 1 MRI CONTROL ROOM RunPeriod: RUNPERIOD 1 1.5552319980E-005 1.4991971632E-005 Pass Pass 1.0104194162E-002 4.5341369318E-002 Pass Pass
21 FLOOR 1 MRI HALL RunPeriod: RUNPERIOD 1 0.1650618740 0.2395135238 Pass Pass 0.2045099278 0.3999077569 Pass Pass
22 FLOOR 1 MRI ROOM RunPeriod: RUNPERIOD 1 5.6193981615E-005 1.3528575813E-004 Pass Pass 6.8107405911E-003 4.2946695144E-002 Pass Pass
23 FLOOR 1 MRI TOILET RunPeriod: RUNPERIOD 1 0.5526001918 0.8417523825 Pass Pass 0.2395619048 0.4325476980 Pass Pass
24 FLOOR 1 NOURISHMENT RunPeriod: RUNPERIOD 1 0.2074877748 0.2722778060 Pass Pass 0.2041446978 0.4018388787 Pass Pass
25 FLOOR 1 NURSE HALL RunPeriod: RUNPERIOD 1 0.1366839761 0.1882949984 Pass Pass 0.2037322821 0.4005217956 Pass Pass
26 FLOOR 1 NURSE JANITOR RunPeriod: RUNPERIOD 1 0.1541833219 0.2202624441 Pass Pass 0.2052820478 0.3989866447 Pass Pass
27 FLOOR 1 NURSE STATION RunPeriod: RUNPERIOD 1 0.1976872870 0.2568411481 Pass Pass 0.2042138449 0.4020077718 Pass Pass
28 FLOOR 1 NURSE TOILET RunPeriod: RUNPERIOD 1 0.4364476324 0.6858423227 Pass Pass 0.3104881020 0.6290755184 Pass Pass
29 FLOOR 1 OFFICE RunPeriod: RUNPERIOD 1 0.1601221106 0.2153890746 Pass Pass 0.2043159150 0.4011358407 Pass Pass
30 FLOOR 1 OPERATING ROOM 1 RunPeriod: RUNPERIOD 1 5.0131258714E-002 0.3802348679 Pass Pass 3.1893241844E-002 0.2083444747 Pass Pass
31 FLOOR 1 OPERATING ROOM 2 RunPeriod: RUNPERIOD 1 5.0163703752E-002 0.3746864956 Pass Pass 3.1578111687E-002 0.2237054317 Pass Pass
32 FLOOR 1 OPERATING ROOM 3 RunPeriod: RUNPERIOD 1 5.0366907114E-002 0.3644228086 Pass Pass 4.6365769106E-002 0.3752500779 Pass Pass
33 FLOOR 1 PACU RunPeriod: RUNPERIOD 1 0.6051819236 0.9293837401 Pass Pass 0.2860323394 0.5484337171 Pass Pass
34 FLOOR 1 PRE-OP HALL RunPeriod: RUNPERIOD 1 0.1343456926 0.1799679952 Pass Pass 0.2035030074 0.4008859735 Pass Pass
35 FLOOR 1 PRE-OP ROOM 1 RunPeriod: RUNPERIOD 1 0.5917252442 0.8971910025 Pass Pass 0.2788071901 0.5380181179 Pass Pass
36 FLOOR 1 PRE-OP ROOM 2 RunPeriod: RUNPERIOD 1 0.5914057108 0.8986333320 Pass Pass 0.3229868201 0.7288438890 Pass Pass
37 FLOOR 1 PRE-OP TOILET RunPeriod: RUNPERIOD 1 0.5744232791 0.8646210706 Pass Pass 0.2400100187 0.4389935620 Pass Pass
38 FLOOR 1 PROCEDURE ROOM RunPeriod: RUNPERIOD 1 0.7120442113 1.1431314402 Pass Pass 0.2972673942 0.5667657841 Pass Pass
39 FLOOR 1 RECEPTION RunPeriod: RUNPERIOD 1 0.2300576047 0.3248304553 Pass Pass 0.2037859759 0.4003213637 Pass Pass
40 FLOOR 1 RECEPTION HALL RunPeriod: RUNPERIOD 1 0.1432593514 0.2043903739 Pass Pass 0.2040386512 0.4002077661 Pass Pass
41 FLOOR 1 RECOVERY ROOM RunPeriod: RUNPERIOD 1 0.7593775239 1.1463899634 Pass Pass 0.2126494803 0.4009239093 Pass Pass
42 FLOOR 1 SCHEDULING RunPeriod: RUNPERIOD 1 0.1726168498 0.2473538185 Pass Pass 0.2031249276 0.4003205262 Pass Pass
43 FLOOR 1 SCRUB RunPeriod: RUNPERIOD 1 0.1428925644 0.2060918909 Pass Pass 0.2046261014 0.3995052996 Pass Pass
44 FLOOR 1 SOIL RunPeriod: RUNPERIOD 1 0.5670684005 0.8676521281 Pass Pass 0.2961826652 0.5739294969 Pass Pass
45 FLOOR 1 SOIL HOLD RunPeriod: RUNPERIOD 1 0.5483144849 0.8583042648 Pass Pass 0.3036513182 0.6002953039 Pass Pass
46 FLOOR 1 SOIL WORK RunPeriod: RUNPERIOD 1 0.5386530843 0.8135002878 Pass Pass 0.2910449713 0.5583827257 Pass Pass
47 FLOOR 1 STEP DOWN RunPeriod: RUNPERIOD 1 0.7122678603 1.0779707487 Pass Pass 0.2109267253 0.3990643601 Pass Pass
48 FLOOR 1 STERILE HALL RunPeriod: RUNPERIOD 1 0.1303744651 0.1769851228 Pass Pass 0.2031349968 0.4007326187 Pass Pass
49 FLOOR 1 STERILE STORAGE RunPeriod: RUNPERIOD 1 0.1163719127 0.1543045249 Pass Pass 0.2029797590 0.4008457321 Pass Pass
50 FLOOR 1 STORAGE RunPeriod: RUNPERIOD 1 0.1459820213 0.2010722436 Pass Pass 0.2031816802 0.3994206984 Pass Pass
51 FLOOR 1 SUB-STERILE RunPeriod: RUNPERIOD 1 0.2195012356 0.2854645790 Pass Pass 0.2040622424 0.4009732052 Pass Pass
52 FLOOR 1 UTILITY HALL RunPeriod: RUNPERIOD 1 0.2370931497 0.3441684444 Pass Pass 0.2051983076 0.3987125715 Pass Pass
53 FLOOR 1 UTILITY JANITOR RunPeriod: RUNPERIOD 1 0.1467913850 0.2153950563 Pass Pass 0.2045095788 0.3989749019 Pass Pass
54 FLOOR 1 UTILITY ROOM RunPeriod: RUNPERIOD 1 0.1789955058 0.2353158195 Pass Pass 0.2035568356 0.4005655219 Pass Pass
55 FLOOR 1 VESTIBULE RunPeriod: RUNPERIOD 1 0.1924016551 0.2863599832 Pass Pass 0.2036264669 0.3988935939 Pass Pass
56 FLOOR 2 CONFERENCE RunPeriod: RUNPERIOD 1 0.3786741046 0.5625415853 Pass Pass 0.2335619990 0.4185061088 Pass Pass
57 FLOOR 2 CONFERENCE TOILET RunPeriod: RUNPERIOD 1 0.3922503354 0.5663959472 Pass Pass 0.2554799285 0.4294641834 Pass Pass
58 FLOOR 2 DICTATION RunPeriod: RUNPERIOD 1 0.1546401397 0.2281192771 Pass Pass 0.2348879822 0.4182985128 Pass Pass
59 FLOOR 2 EXAM 1 RunPeriod: RUNPERIOD 1 0.3799714459 0.5780648965 Pass Pass 0.2387597508 0.4176512900 Pass Pass
60 FLOOR 2 EXAM 2 RunPeriod: RUNPERIOD 1 0.4399985853 0.6648562496 Pass Pass 0.2519278264 0.4261962737 Pass Pass
61 FLOOR 2 EXAM 3 RunPeriod: RUNPERIOD 1 0.4122949461 0.6291532529 Pass Pass 0.2478857215 0.4232113874 Pass Pass
62 FLOOR 2 EXAM 4 RunPeriod: RUNPERIOD 1 0.4039999814 0.6112802980 Pass Pass 0.2359057406 0.4182483880 Pass Pass
63 FLOOR 2 EXAM 5 RunPeriod: RUNPERIOD 1 0.5117862475 0.7482992175 Pass Pass 0.2498943757 0.4261360990 Pass Pass
64 FLOOR 2 EXAM 6 RunPeriod: RUNPERIOD 1 0.4017892534 0.6012916878 Pass Pass 0.2532128552 0.4273749630 Pass Pass
65 FLOOR 2 EXAM 7 RunPeriod: RUNPERIOD 1 0.3717920059 0.5570388734 Pass Pass 0.2530246910 0.4275311711 Pass Pass
66 FLOOR 2 EXAM 8 RunPeriod: RUNPERIOD 1 0.4152056303 0.6247613847 Pass Pass 0.2518833158 0.4256897302 Pass Pass
67 FLOOR 2 EXAM 9 RunPeriod: RUNPERIOD 1 0.4186719614 0.6184642973 Pass Pass 0.2580226188 0.4331063184 Pass Pass
68 FLOOR 2 EXAM HALL 1 RunPeriod: RUNPERIOD 1 0.1573463436 0.2305408150 Pass Pass 0.2341948249 0.4176166280 Pass Pass
69 FLOOR 2 EXAM HALL 2 RunPeriod: RUNPERIOD 1 0.1501762219 0.2208514553 Pass Pass 0.2340772091 0.4180289860 Pass Pass
70 FLOOR 2 EXAM HALL 3 RunPeriod: RUNPERIOD 1 0.1364675746 0.2037568671 Pass Pass 0.2323617364 0.4181427898 Pass Pass
71 FLOOR 2 EXAM HALL 4 RunPeriod: RUNPERIOD 1 0.1297661913 0.1873386721 Pass Pass 0.2339759351 0.4186183473 Pass Pass
72 FLOOR 2 EXAM HALL 5 RunPeriod: RUNPERIOD 1 0.1375321994 0.1993643121 Pass Pass 0.2334683551 0.4186056079 Pass Pass
73 FLOOR 2 EXAM HALL 6 RunPeriod: RUNPERIOD 1 0.1388596539 0.2006070572 Pass Pass 0.2342220517 0.4184413990 Pass Pass
74 FLOOR 2 JANITOR RunPeriod: RUNPERIOD 1 0.1638328429 0.2427767885 Pass Pass 0.2314028866 0.4166293709 Pass Pass
75 FLOOR 2 LOUNGE RunPeriod: RUNPERIOD 1 0.1988343059 0.2717168082 Pass Pass 0.2315001948 0.4205701619 Pass Pass
76 FLOOR 2 NURSE STATION 1 RunPeriod: RUNPERIOD 1 0.1775637028 0.2481123079 Pass Pass 0.2323658216 0.4199512094 Pass Pass
77 FLOOR 2 NURSE STATION 2 RunPeriod: RUNPERIOD 1 0.1844764257 0.2569003261 Pass Pass 0.2321924978 0.4198761221 Pass Pass
78 FLOOR 2 OFFICE RunPeriod: RUNPERIOD 1 0.2540980223 0.3412233514 Pass Pass 0.2330180777 0.4198411526 Pass Pass
79 FLOOR 2 OFFICE HALL RunPeriod: RUNPERIOD 1 0.1448768834 0.2128975330 Pass Pass 0.2340818078 0.4180724026 Pass Pass
80 FLOOR 2 RECEPTION RunPeriod: RUNPERIOD 1 0.2566823066 0.3685619540 Pass Pass 0.2319905499 0.4180213089 Pass Pass
81 FLOOR 2 RECEPTION HALL RunPeriod: RUNPERIOD 1 0.1503672432 0.2240322378 Pass Pass 0.2339040505 0.4181071566 Pass Pass
82 FLOOR 2 RECEPTION TOILET RunPeriod: RUNPERIOD 1 0.3979714761 0.5753089716 Pass Pass 0.2536568384 0.4274320032 Pass Pass
83 FLOOR 2 SCHEDULING 1 RunPeriod: RUNPERIOD 1 0.1452226287 0.2083109443 Pass Pass 0.2326390023 0.4192873780 Pass Pass
84 FLOOR 2 SCHEDULING 2 RunPeriod: RUNPERIOD 1 0.1545530212 0.2252465045 Pass Pass 0.2334966374 0.4190324716 Pass Pass
85 FLOOR 2 STORAGE 1 RunPeriod: RUNPERIOD 1 0.1364567366 0.1978054081 Pass Pass 0.2343308236 0.4171879439 Pass Pass
86 FLOOR 2 STORAGE 2 RunPeriod: RUNPERIOD 1 0.1177699817 0.1700974300 Pass Pass 0.2334401600 0.4185168499 Pass Pass
87 FLOOR 2 STORAGE 3 RunPeriod: RUNPERIOD 1 0.1255533691 0.1819882122 Pass Pass 0.2332739998 0.4186042192 Pass Pass
88 FLOOR 2 UTILITY RunPeriod: RUNPERIOD 1 0.2312856410 0.3235602287 Pass Pass 0.2348092874 0.4191968101 Pass Pass
89 FLOOR 2 WORK RunPeriod: RUNPERIOD 1 0.1407211133 0.1921821956 Pass Pass 0.2312473160 0.4193542762 Pass Pass
90 FLOOR 2 WORK HALL RunPeriod: RUNPERIOD 1 0.1488625653 0.2207823030 Pass Pass 0.2337751189 0.4182270057 Pass Pass
91 FLOOR 2 WORK TOILET RunPeriod: RUNPERIOD 1 0.3946209153 0.5743932315 Pass Pass 0.2513378170 0.4243823586 Pass Pass
92 FLOOR 2 X-RAY RunPeriod: RUNPERIOD 1 1.7252445026E-005 1.6732548550E-005 Pass Pass 8.7695876767E-003 5.9434282169E-002 Pass Pass
93 FLOOR 3 DRESSING ROOM RunPeriod: RUNPERIOD 1 0.2858274126 0.2335751691 Pass Pass 0.4063011534 0.4858124581 Pass Pass
94 FLOOR 3 ELEVATOR HALL RunPeriod: RUNPERIOD 1 0.2461722493 0.1879231502 Pass Pass 0.4066864387 0.4856301198 Pass Pass
95 FLOOR 3 HUMID RunPeriod: RUNPERIOD 1 0.2939166942 0.2275083365 Pass Pass 0.4059123325 0.4867957142 Pass Pass
96 FLOOR 3 JANITOR RunPeriod: RUNPERIOD 1 0.2745910799 0.2329275486 Pass Pass 0.4065110435 0.4838505196 Pass Pass
97 FLOOR 3 LOCKER RunPeriod: RUNPERIOD 1 0.3956763516 0.2938573856 Pass Pass 0.4062249984 0.4884317610 Pass Pass
98 FLOOR 3 LOUNGE RunPeriod: RUNPERIOD 1 0.4271771332 0.2993155937 Pass Pass 0.4062979090 0.4890109493 Pass Pass
99 FLOOR 3 LOUNGE TOILET RunPeriod: RUNPERIOD 1 0.6047774131 0.5225628064 Pass Pass 0.4254770504 0.4762454004 Pass Pass
100 FLOOR 3 MECHANICAL RunPeriod: RUNPERIOD 1 0.9623800941 0.8670775835 Pass Pass 0.4257485686 0.4905462193 Pass Pass
101 FLOOR 3 MECHANICAL HALL RunPeriod: RUNPERIOD 1 0.2925408502 0.2360208830 Pass Pass 0.4066804258 0.4847657845 Pass Pass
102 FLOOR 3 OFFICE RunPeriod: RUNPERIOD 1 0.2900226012 0.2086170526 Pass Pass 0.4070787500 0.4863670317 Pass Pass
103 FLOOR 3 OFFICE HALL RunPeriod: RUNPERIOD 1 0.2680127048 0.2109579467 Pass Pass 0.4067177130 0.4849679061 Pass Pass
104 FLOOR 3 OFFICE TOILET RunPeriod: RUNPERIOD 1 0.6320585458 0.5641442812 Pass Pass 0.4298948142 0.4723135336 Pass Pass
105 FLOOR 3 PHYSICAL THERAPY 1 RunPeriod: RUNPERIOD 1 0.7335519594 0.6389246963 Pass Pass 0.4175372655 0.4814471461 Pass Pass
106 FLOOR 3 PHYSICAL THERAPY 2 RunPeriod: RUNPERIOD 1 0.5896188558 0.4827476715 Pass Pass 0.4221874722 0.4808659637 Pass Pass
107 FLOOR 3 PHYSICAL THERAPY TOILET RunPeriod: RUNPERIOD 1 0.6203578775 0.5285208593 Pass Pass 0.4322195465 0.4753661520 Pass Pass
108 FLOOR 3 STORAGE 1 RunPeriod: RUNPERIOD 1 0.5159348114 0.4360104563 Pass Pass 0.4261328814 0.4744485985 Pass Pass
109 FLOOR 3 STORAGE 2 RunPeriod: RUNPERIOD 1 0.2509606542 0.2029771090 Pass Pass 0.4080458551 0.4831112766 Pass Pass
110 FLOOR 3 TREATMENT RunPeriod: RUNPERIOD 1 0.6326505001 0.5195675885 Pass Pass 0.4238129473 0.4790673249 Pass Pass
111 FLOOR 3 UNDEVELOPED 1 RunPeriod: RUNPERIOD 1 0.3576287192 0.2769583682 Pass Pass 0.4072482217 0.4864399415 Pass Pass
112 FLOOR 3 UNDEVELOPED 2 RunPeriod: RUNPERIOD 1 0.3992540383 0.3373410518 Pass Pass 0.4119482807 0.4826085529 Pass Pass
113 FLOOR 3 UTILITY RunPeriod: RUNPERIOD 1 0.2153412316 0.1639400613 Pass Pass 0.4064489738 0.4857549859 Pass Pass
114 FLOOR 3 WORK RunPeriod: RUNPERIOD 1 0.4637915255 0.3772219681 Pass Pass 0.4074986977 0.4851698939 Pass Pass
115 NE STAIR RunPeriod: RUNPERIOD 1 0.1972302139 0.2789717768 Pass Pass 0.2301791850 0.4163059974 Pass Pass
116 NW ELEVATOR RunPeriod: RUNPERIOD 1 0.1695345183 0.2374084709 Pass Pass 0.2302717710 0.4157391087 Pass Pass
117 NW STAIR RunPeriod: RUNPERIOD 1 0.1740348486 0.2396704512 Pass Pass 0.2303393336 0.4157320291 Pass Pass
118 SW STAIR RunPeriod: RUNPERIOD 1 0.2700731896 0.4392087467 Pass Pass 0.2514185769 0.4361226031 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3690.29 -90.1 -970.9 -1920.5 6946.07 7654.82



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 8.70 0.00 8.70 Wetbulb [C] 3.80 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 33.20 6.70 25.30 Wetbulb [C] 4.50 140.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 65.00 29      
Feb 0.00 0      
Mar 0.00 0      
Apr 38.00 14      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 391.00 83      
Sep 0.00 0      
Oct 225.00 40      
Nov 0.00 0      
Dec 5.00 10      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
481E71 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 8.36 6.13 180.00 90.00 S
FLOOR 1 ANESTHESIA SLAB FLOOR1ANESTHESIASLAB_FFACTOR 1.00 0.345 0.365 10.03 10.03 0.00 180.00  
5F762C NONRES_EXT_WALL_GRD 0.30 0.704 0.787 18.58 9.66 180.00 90.00 S
FLOOR 1 CAFE SLAB FLOOR1CAFESLAB_FFACTOR 1.00 0.197 0.204 39.02 39.02 90.00 180.00  
84FB73 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 8.36 6.04 0.00 90.00 N
FLOOR 1 DRESSING ROOM SLAB FLOOR1DRESSINGROOMSLAB_FFACTOR 1.00 0.824 0.951 4.18 4.18 0.00 180.00  
7F5C82 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 6.50 6.50 90.00 90.00 E
FLOOR 1 ELECTRICAL ROOM SLAB FLOOR1ELECTRICALROOMSLAB_FFACTOR 1.00 0.296 0.310 9.10 9.10 0.00 180.00  
C732B0 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 12.08 12.08 0.00 90.00 N
E02487 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 6.50 4.55 270.00 90.00 W
FLOOR 1 ELEVATOR PUMP ROOM SLAB FLOOR1ELEVATORPUMPROOMSLAB_FFACTOR 1.00 0.905 1.061 8.45 8.45 180.00 180.00  
FE5A3C NONRES_EXT_WALL_GRD 0.30 0.704 0.787 20.44 9.57 270.00 90.00 W
FLOOR 1 LOBBY SLAB FLOOR1LOBBYSLAB_FFACTOR 1.00 0.146 0.150 57.79 57.79 90.00 180.00  
9D87EC NONRES_EXT_WALL_GRD 0.30 0.704 0.787 5.57 5.57 270.00 90.00 W
FLOOR 1 LOBBY TOILET SLAB FLOOR1LOBBYTOILETSLAB_FFACTOR 1.00 0.459 0.496 5.02 5.02 0.00 180.00  
F629C1 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 20.44 14.86 0.00 90.00 N
FLOOR 1 LOCKER ROOM SLAB FLOOR1LOCKERROOMSLAB_FFACTOR 1.00 0.138 0.141 61.32 61.32 270.00 180.00  
E85BB5 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 7.43 5.48 0.00 90.00 N
577FC1 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 6.50 6.50 90.00 90.00 E
FLOOR 1 MED GAS SLAB FLOOR1MEDGASSLAB_FFACTOR 1.00 1.102 1.341 5.20 5.20 180.00 180.00  
FLOOR 1 MED GAS ROOF NONRES_ROOF 0.30 0.358 0.376 5.20 5.20 180.00 0.00  
C114C1 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 4.65 2.69 0.00 90.00 N
FLOOR 1 MRI CONTROL ROOM SLAB FLOOR1MRICONTROLROOMSLAB_FFACTOR 1.00 0.123 0.126 15.61 15.61 180.00 180.00  
ADB8D0 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 5.57 5.57 0.00 90.00 N
FLOOR 1 MRI TOILET SLAB FLOOR1MRITOILETSLAB_FFACTOR 1.00 0.459 0.496 5.02 5.02 90.00 180.00  
879583 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 18.58 14.12 180.00 90.00 S
E326E4 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 21.37 13.46 90.00 90.00 E
FLOOR 1 OPERATING ROOM 1 SLAB FLOOR1OPERATINGROOM1SLAB_FFACTOR 1.00 0.386 0.412 42.74 42.74 0.00 180.00  
1D96D7 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 22.30 13.37 90.00 90.00 E
FLOOR 1 OPERATING ROOM 2 SLAB FLOOR1OPERATINGROOM2SLAB_FFACTOR 1.00 0.207 0.214 44.59 44.59 0.00 180.00  
84418A NONRES_EXT_WALL_GRD 0.30 0.704 0.787 3.72 3.72 270.00 90.00 W
FLOOR 1 PRE-OP ROOM 1 SLAB FLOOR1PRE-OPROOM1SLAB_FFACTOR 1.00 0.088 0.089 17.56 17.56 90.00 180.00  
1535AC NONRES_EXT_WALL_GRD 0.30 0.704 0.787 5.57 5.57 270.00 90.00 W
FLOOR 1 PRE-OP TOILET SLAB FLOOR1PRE-OPTOILETSLAB_FFACTOR 1.00 0.459 0.496 5.02 5.02 270.00 180.00  
6D2616 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 17.65 12.08 0.00 90.00 N
FLOOR 1 PROCEDURE ROOM SLAB FLOOR1PROCEDUREROOMSLAB_FFACTOR 1.00 0.276 0.289 26.48 26.48 270.00 180.00  
A5A6A3 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 12.08 8.73 180.00 90.00 S
FLOOR 1 RECEPTION SLAB FLOOR1RECEPTIONSLAB_FFACTOR 1.00 0.106 0.108 47.29 47.29 270.00 180.00  
28B002 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 41.81 27.03 180.00 90.00 S
FLOOR 1 RECOVERY ROOM SLAB FLOOR1RECOVERYROOMSLAB_FFACTOR 1.00 0.345 0.365 50.17 50.17 90.00 180.00  
EA6DC8 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 6.50 5.76 180.00 90.00 S
FLOOR 1 SCHEDULING SLAB FLOOR1SCHEDULINGSLAB_FFACTOR 1.00 0.243 0.253 11.06 11.06 90.00 180.00  
B40F89 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 11.15 8.92 270.00 90.00 W
997723 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 23.23 16.82 180.00 90.00 S
FLOOR 1 STEP DOWN SLAB FLOOR1STEPDOWNSLAB_FFACTOR 1.00 0.509 0.555 27.87 27.87 270.00 180.00  
CEC7BD NONRES_EXT_WALL_GRD 0.30 0.704 0.787 7.43 5.20 180.00 90.00 S
FLOOR 1 STERILE HALL SLAB FLOOR1STERILEHALLSLAB_FFACTOR 1.00 0.054 0.054 57.23 57.23 270.00 180.00  
8E5BB9 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 21.37 18.39 270.00 90.00 W
859BC1 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 37.16 22.95 0.00 90.00 N
FLOOR 1 STORAGE SLAB FLOOR1STORAGESLAB_FFACTOR 1.00 0.283 0.297 85.47 85.47 270.00 180.00  
FLOOR 1 STORGE ROOF NONRES_ROOF 0.30 0.358 0.376 85.47 85.47 270.00 0.00  
61E610 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 13.01 9.04 90.00 90.00 E
FLOOR 1 SUB-STERILE SLAB FLOOR1SUB-STERILESLAB_FFACTOR 1.00 0.296 0.310 18.21 18.21 180.00 180.00  
529072 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 14.86 7.43 90.00 90.00 E
FLOOR 1 UTILITY HALL SLAB FLOOR1UTILITYHALLSLAB_FFACTOR 1.00 0.259 0.270 23.78 23.78 90.00 180.00  
FLOOR 1 UTILITY HALL ROOF NONRES_ROOF 0.30 0.358 0.376 11.89 11.89 180.00 0.00  
D95F04 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 16.72 11.79 90.00 90.00 E
FLOOR 1 UTILITY ROOM SLAB FLOOR1UTILITYROOMSLAB_FFACTOR 1.00 0.207 0.214 33.45 33.45 180.00 180.00  
3330D8 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 7.43 5.48 270.00 90.00 W
FLOOR 1 VESTIBULE SLAB FLOOR1VESTIBULESLAB_FFACTOR 1.00 0.459 0.496 6.69 6.69 90.00 180.00  
208CCF NONRES_EXT_WALL_MID 0.30 0.704 0.787 11.15 8.17 90.00 90.00 E
AEF992 NONRES_EXT_WALL_MID 0.30 0.704 0.787 26.01 19.32 180.00 90.00 S
54D065 NONRES_EXT_WALL_MID 0.30 0.704 0.787 11.15 8.92 180.00 90.00 S
1775A6 NONRES_EXT_WALL_MID 0.30 0.704 0.787 27.87 21.18 270.00 90.00 W
97F00A NONRES_EXT_WALL_MID 0.30 0.704 0.787 16.72 13.01 180.00 90.00 S
A497E9 NONRES_EXT_WALL_MID 0.30 0.704 0.787 22.30 16.35 180.00 90.00 S
88A75F NONRES_EXT_WALL_MID 0.30 0.704 0.787 6.50 4.27 180.00 90.00 S
B4E619 NONRES_EXT_WALL_MID 0.30 0.704 0.787 23.23 15.29 90.00 90.00 E
9EC269 NONRES_EXT_WALL_MID 0.30 0.704 0.787 13.94 9.75 0.00 90.00 N
B316F7 NONRES_EXT_WALL_MID 0.30 0.704 0.787 22.30 16.72 0.00 90.00 N
9621FD NONRES_EXT_WALL_MID 0.30 0.704 0.787 16.72 11.15 0.00 90.00 N
42CEE1 NONRES_EXT_WALL_MID 0.30 0.704 0.787 11.15 8.36 0.00 90.00 N
4979C8 NONRES_EXT_WALL_MID 0.30 0.704 0.787 5.57 5.57 180.00 90.00 S
8CA0BF NONRES_EXT_WALL_MID 0.30 0.704 0.787 5.57 5.57 180.00 90.00 S
6C95E7 NONRES_EXT_WALL_MID 0.30 0.704 0.787 5.57 5.57 180.00 90.00 S
F209CC NONRES_EXT_WALL_MID 0.30 0.704 0.787 5.57 5.57 0.00 90.00 N
155BD6 NONRES_EXT_WALL_MID 0.30 0.704 0.787 5.57 5.57 0.00 90.00 N
C5EA55 NONRES_EXT_WALL_MID 0.30 0.704 0.787 5.57 5.57 0.00 90.00 N
8177BA NONRES_EXT_WALL_MID 0.30 0.704 0.787 6.50 6.50 270.00 90.00 W
5E657E NONRES_EXT_WALL_MID 0.30 0.704 0.787 8.36 8.36 0.00 90.00 N
4B1439 NONRES_EXT_WALL_MID 0.30 0.704 0.787 37.16 25.25 90.00 90.00 E
4ABC66 NONRES_EXT_WALL_MID 0.30 0.704 0.787 30.66 20.62 180.00 90.00 S
5B04CF NONRES_EXT_WALL_MID 0.30 0.704 0.787 14.86 8.18 270.00 90.00 W
8D1BC4 NONRES_EXT_WALL_MID 0.30 0.704 0.787 6.50 6.50 180.00 90.00 S
4B55FA NONRES_EXT_WALL_MID 0.30 0.704 0.787 8.36 5.38 90.00 90.00 E
9C3A6A NONRES_EXT_WALL_MID 0.30 0.704 0.787 20.44 14.86 0.00 90.00 N
C52EE0 NONRES_EXT_WALL_MID 0.30 0.704 0.787 3.72 3.72 0.00 90.00 N
1C33AD NONRES_EXT_WALL_MID 0.30 0.704 0.787 5.57 5.57 270.00 90.00 W
6CC177 NONRES_EXT_WALL_MID 0.30 0.704 0.787 5.57 5.57 270.00 90.00 W
FLOOR 3 DRESSING ROOM ROOF NONRES_ROOF 0.30 0.358 0.376 3.90 3.90 270.00 0.00  
F7D24D NONRES_EXT_WALL_TOP 0.30 0.704 0.787 3.72 3.72 0.00 90.00 N
FLOOR 3 ELEVATOR HALL ROOF NONRES_ROOF 0.30 0.358 0.376 34.37 34.37 0.00 0.00  
FLOOR 3 HUMID ROOF NONRES_ROOF 0.30 0.358 0.376 10.03 10.03 270.00 0.00  
FC22D1 NONRES_EXT_WALL_TOP 0.30 0.704 0.787 8.36 8.36 0.00 90.00 N
DD2E2D NONRES_EXT_WALL_TOP 0.30 0.704 0.787 6.50 6.50 270.00 90.00 W
FLOOR 3 JANITOR ROOF NONRES_ROOF 0.30 0.358 0.376 5.85 5.85 0.00 0.00  
FLOOR 3 LOCKER ROOF NONRES_ROOF 0.30 0.358 0.376 11.15 11.15 0.00 0.00  
68A2D7 NONRES_EXT_WALL_TOP 0.30 0.704 0.787 21.37 15.79 0.00 90.00 N
FLOOR 3 LOUNGE ROOF NONRES_ROOF 0.30 0.358 0.376 70.51 70.51 270.00 0.00  
CE3FEF NONRES_EXT_WALL_TOP 0.30 0.704 0.787 11.15 6.97 0.00 90.00 N
FLOOR 3 LOUNGE TOILET ROOF NONRES_ROOF 0.30 0.358 0.376 17.84 17.84 0.00 0.00  
CE618F NONRES_EXT_WALL_TOP 0.30 0.704 0.787 23.23 15.29 90.00 90.00 E
FLOOR 3 MECHANICAL ROOF NONRES_ROOF 0.30 0.358 0.376 32.52 32.52 0.00 0.00  
FLOOR 3 MECHANICAL HALL ROOF NONRES_ROOF 0.30 0.358 0.376 27.87 27.87 0.00 0.00  
5ADC59 NONRES_EXT_WALL_TOP 0.30 0.704 0.787 68.75 49.24 0.00 90.00 N
FLOOR 3 OFFICE ROOF NONRES_ROOF 0.30 0.358 0.376 282.05 282.05 180.00 0.00  
D4F411 NONRES_EXT_WALL_TOP 0.30 0.704 0.787 5.57 5.57 270.00 90.00 W
FLOOR 3 OFFICE HALL ROOF NONRES_ROOF 0.30 0.358 0.376 77.48 77.48 270.00 0.00  
B35AD6 NONRES_EXT_WALL_TOP 0.30 0.704 0.787 5.57 5.57 270.00 90.00 W
FLOOR 3 OFFICE TOILET ROOF NONRES_ROOF 0.30 0.358 0.376 5.02 5.02 270.00 0.00  
D22917 NONRES_EXT_WALL_TOP 0.30 0.704 0.787 18.58 11.14 90.00 90.00 E
C1BC97 NONRES_EXT_WALL_TOP 0.30 0.704 0.787 60.39 38.09 180.00 90.00 S
FLOOR 3 PHYICAL THERAPY 1 ROOF NONRES_ROOF 0.30 0.358 0.376 120.77 120.77 180.00 0.00  
FLOOR 3 PHYSICAL THERAPY 2 ROOF NONRES_ROOF 0.30 0.358 0.376 55.00 55.00 90.00 0.00  
FLOOR 3 PHYSICAL THERAPY TOILET ROOF NONRES_ROOF 0.30 0.358 0.376 7.80 7.80 90.00 0.00  
FLOOR 3 STORAGE 1 ROOF NONRES_ROOF 0.30 0.358 0.376 10.03 10.03 180.00 0.00  
FLOOR 3 STORAGE 2 ROOF NONRES_ROOF 0.30 0.358 0.376 7.80 7.80 180.00 0.00  
FLOOR 3 TREATMENT ROOF NONRES_ROOF 0.30 0.358 0.376 44.22 44.22 90.00 0.00  
8DA7DB NONRES_EXT_WALL_TOP 0.30 0.704 0.787 39.02 23.41 180.00 90.00 S
38B339 NONRES_EXT_WALL_TOP 0.30 0.704 0.787 27.87 17.84 270.00 90.00 W
FLOOR 3 UNDEVELOPED 1 ROOF NONRES_ROOF 0.30 0.358 0.376 210.70 210.70 0.00 0.00  
BE5F2F NONRES_EXT_WALL_TOP 0.30 0.704 0.787 14.86 10.41 270.00 90.00 W
1DEE26 NONRES_EXT_WALL_TOP 0.30 0.704 0.787 37.16 28.24 180.00 90.00 S
FLOOR 3 UNDEVELOPED 2 ROOF NONRES_ROOF 0.30 0.358 0.376 107.02 107.02 180.00 0.00  
FLOOR 3 UTILITY ROOF NONRES_ROOF 0.30 0.358 0.376 20.07 20.07 0.00 0.00  
C86329 NONRES_EXT_WALL_TOP 0.30 0.704 0.787 38.09 26.18 90.00 90.00 E
FLOOR 3 WORK ROOF NONRES_ROOF 0.30 0.358 0.376 53.33 53.33 90.00 0.00  
DFC6F0 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 19.51 18.52 90.00 90.00 E
88E360 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 66.89 51.71 0.00 90.00 N
E7B55F NONRES_EXT_WALL_GRD 0.30 0.704 0.787 11.15 11.15 180.00 90.00 S
NE STAIR SLAB NESTAIRSLAB_FFACTOR 1.00 0.858 0.997 15.61 15.61 0.00 180.00  
NE STAIR ROOF NONRES_ROOF 0.30 0.358 0.376 15.61 15.61 0.00 0.00  
FB3814 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 19.51 17.56 180.00 90.00 S
FCD12D NONRES_EXT_WALL_GRD 0.30 0.704 0.787 55.74 53.79 270.00 90.00 W
NW ELEVATOR SLAB NWELEVATORSLAB_FFACTOR 1.00 0.795 0.913 13.01 13.01 90.00 180.00  
NW ELEVATOR ROOF NONRES_ROOF 0.30 0.358 0.376 13.01 13.01 90.00 0.00  
5507DC NONRES_EXT_WALL_GRD 0.30 0.704 0.787 22.30 20.35 270.00 90.00 W
2E2D0C NONRES_EXT_WALL_GRD 0.30 0.704 0.787 66.89 53.79 0.00 90.00 N
AF0124 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 22.30 22.30 90.00 90.00 E
NW STAIR SLAB NWSTAIRSLAB_FFACTOR 1.00 0.858 0.997 17.84 17.84 270.00 180.00  
NW STAIR ROOF NONRES_ROOF 0.30 0.358 0.376 17.84 17.84 270.00 0.00  
850EA7 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 33.45 32.33 180.00 90.00 S
270BCE NONRES_EXT_WALL_GRD 0.30 0.704 0.787 22.30 20.35 270.00 90.00 W
SW STAIR SLAB SWSTAIRSLAB_FFACTOR 1.00 0.858 0.997 8.92 8.92 270.00 180.00  
SW STAIR ROOF NONRES_ROOF 0.30 0.358 0.376 8.92 8.92 180.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
4161C8 INT_WALL 0.30 2.511 6.299 11.15 11.15 90.00 90.00 E
1AD133 INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
330DF9 INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
DDCF3E INT_SLAB_CEILING 0.30 1.887 3.839 2.23 2.23 90.00 0.00  
BE1AE1 INT_SLAB_CEILING 0.30 1.887 3.839 7.80 7.80 270.00 0.00  
70DAD1 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
32CC19 INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
BBEE0B INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
F951A6 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
FLOOR 1 BIO HAZ SLAB FLOOR1BIOHAZSLAB_FFACTOR 1.00 0.006 0.006 5.20 5.20 0.00 180.00  
F6F6C6 INT_SLAB_CEILING 0.30 1.887 3.839 5.20 5.20 0.00 0.00  
4507E9 INT_WALL 0.30 2.511 6.299 18.58 18.58 0.00 90.00 N
C48E94 INT_WALL 0.30 2.511 6.299 12.08 12.08 270.00 90.00 W
6B31A8 INT_WALL 0.30 2.511 6.299 19.51 19.51 90.00 90.00 E
368E02 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
4783F2 INT_SLAB_CEILING 0.30 1.887 3.839 39.02 39.02 90.00 0.00  
EA8FA7 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
FE7511 INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
59E0E4 INT_WALL 0.30 2.511 6.299 13.01 13.01 270.00 90.00 W
7949FA INT_WALL 0.30 2.511 6.299 13.01 13.01 90.00 90.00 E
FLOOR 1 CLEAN SLAB FLOOR1CLEANSLAB_FFACTOR 1.00 0.006 0.006 11.71 11.71 90.00 180.00  
EC2478 INT_SLAB_CEILING 0.30 1.887 3.839 0.46 0.46 90.00 0.00  
1B4EDC INT_SLAB_CEILING 0.30 1.887 3.839 0.37 0.37 0.00 0.00  
D1AFC9 INT_SLAB_CEILING 0.30 1.887 3.839 5.85 5.85 180.00 0.00  
442699 INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 0.00 0.00  
FD8CF2 INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
49DA86 INT_WALL 0.30 2.511 6.299 10.22 10.22 270.00 90.00 W
619EE6 INT_WALL 0.30 2.511 6.299 10.22 10.22 90.00 90.00 E
B551AD INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
FLOOR 1 CLEAN WORK SLAB FLOOR1CLEANWORKSLAB_FFACTOR 1.00 0.006 0.006 15.33 15.33 180.00 180.00  
8E9267 INT_SLAB_CEILING 0.30 1.887 3.839 6.50 6.50 270.00 0.00  
BB097B INT_SLAB_CEILING 0.30 1.887 3.839 3.25 3.25 180.00 0.00  
2E1FB7 INT_SLAB_CEILING 0.30 1.887 3.839 5.57 5.57 270.00 0.00  
94A56A INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
4A854B INT_WALL 0.30 2.511 6.299 13.01 13.01 90.00 90.00 E
8594D3 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
86244A INT_WALL 0.30 2.511 6.299 13.01 13.01 270.00 90.00 W
FLOOR 1 DICTATION SLAB FLOOR1DICTATIONSLAB_FFACTOR 1.00 0.006 0.006 11.71 11.71 0.00 180.00  
672F1E INT_SLAB_CEILING 0.30 1.887 3.839 0.84 0.84 0.00 0.00  
A7115C INT_SLAB_CEILING 0.30 1.887 3.839 5.85 5.85 180.00 0.00  
AF27F8 INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 0.00 0.00  
256F02 INT_WALL 0.30 2.511 6.299 4.65 4.65 90.00 90.00 E
DE027F INT_WALL 0.30 2.511 6.299 4.65 4.65 270.00 90.00 W
CC17E8 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
5DACB5 INT_SLAB_CEILING 0.30 1.887 3.839 4.18 4.18 0.00 0.00  
9879B2 INT_WALL 0.30 2.511 6.299 6.50 6.50 270.00 90.00 W
2D53AC INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
E82152 INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
D7AC92 INT_SLAB_CEILING 0.30 1.887 3.839 9.10 9.10 0.00 0.00  
F99476 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
9926F7 INT_WALL 0.30 2.511 6.299 6.50 6.50 90.00 90.00 E
B45B50 INT_WALL 0.30 2.511 6.299 3.72 3.72 180.00 90.00 S
DF9D5D INT_SLAB_CEILING 0.30 1.887 3.839 5.85 5.85 90.00 0.00  
827528 INT_SLAB_CEILING 0.30 1.887 3.839 2.60 2.60 270.00 0.00  
758B3C INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
A7F46C INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
3F71D3 INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
8BB36F INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
FLOOR 1 HUMID SLAB FLOOR1HUMIDSLAB_FFACTOR 1.00 0.006 0.006 5.02 5.02 0.00 180.00  
D21333 INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 0.00 0.00  
FEC1E3 INT_WALL 0.30 2.511 6.299 26.01 26.01 180.00 90.00 S
5D9E95 INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
F4D6DD INT_WALL 0.30 2.511 6.299 4.65 4.65 90.00 90.00 E
FB87D3 INT_WALL 0.30 2.511 6.299 4.65 4.65 270.00 90.00 W
445A39 INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
3A6904 INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
FLOOR 1 IT HALL SLAB FLOOR1ITHALLSLAB_FFACTOR 1.00 0.006 0.006 13.01 13.01 180.00 180.00  
FB17DD INT_SLAB_CEILING 0.30 1.887 3.839 3.25 3.25 270.00 0.00  
8A2F34 INT_SLAB_CEILING 0.30 1.887 3.839 2.79 2.79 270.00 0.00  
9A5B84 INT_SLAB_CEILING 0.30 1.887 3.839 6.97 6.97 90.00 0.00  
2CF0AA INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
307901 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
FA769A INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
319A6B INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
FLOOR 1 IT ROOM SLAB FLOOR1ITROOMSLAB_FFACTOR 1.00 0.006 0.006 10.41 10.41 90.00 180.00  
C732D4 INT_SLAB_CEILING 0.30 1.887 3.839 10.41 10.41 90.00 0.00  
822161 INT_WALL 0.30 2.511 6.299 7.43 7.43 0.00 90.00 N
43A2A2 INT_WALL 0.30 2.511 6.299 18.58 18.58 270.00 90.00 W
6FB351 INT_WALL 0.30 2.511 6.299 6.50 6.50 270.00 90.00 W
8134C2 INT_WALL 0.30 2.511 6.299 1.86 1.86 0.00 90.00 N
102EC4 INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
BAD27A INT_WALL 0.30 2.511 6.299 11.15 11.15 180.00 90.00 S
5D8FAF INT_WALL 0.30 2.511 6.299 3.72 3.72 0.00 90.00 N
46E87C INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
3145CA INT_WALL 0.30 2.511 6.299 12.08 12.08 90.00 90.00 E
73E892 INT_WALL 0.30 2.511 6.299 1.86 1.86 180.00 90.00 S
4418C4 INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
4911A5 INT_WALL 0.30 2.511 6.299 11.15 11.15 90.00 90.00 E
D647E0 INT_SLAB_CEILING 0.30 1.887 3.839 6.69 6.69 180.00 0.00  
BFB8E1 INT_SLAB_CEILING 0.30 1.887 3.839 33.26 33.26 180.00 0.00  
78FEE8 INT_SLAB_CEILING 0.30 1.887 3.839 17.84 17.84 270.00 0.00  
A6D45E INT_WALL 0.30 2.511 6.299 18.58 18.58 180.00 90.00 S
F7F8BA INT_WALL 0.30 2.511 6.299 11.15 11.15 90.00 90.00 E
34019D INT_WALL 0.30 2.511 6.299 18.58 18.58 0.00 90.00 N
72A819 INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
FLOOR 1 LOBBY HALL SLAB FLOOR1LOBBYHALLSLAB_FFACTOR 1.00 0.006 0.006 22.30 22.30 0.00 180.00  
D60B94 INT_SLAB_CEILING 0.30 1.887 3.839 11.15 11.15 180.00 0.00  
B7E9B3 INT_SLAB_CEILING 0.30 1.887 3.839 5.57 5.57 180.00 0.00  
690A91 INT_SLAB_CEILING 0.30 1.887 3.839 5.57 5.57 0.00 0.00  
9FF31D INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
F23EB6 INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
7F6FC2 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
88CB69 INT_WALL 0.30 2.511 6.299 1.86 1.86 180.00 90.00 S
9BB388 INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 0.00 0.00  
E9F3F6 INT_WALL 0.30 2.511 6.299 13.94 13.94 270.00 90.00 W
A9C27A INT_WALL 0.30 2.511 6.299 20.44 20.44 180.00 90.00 S
962DB5 INT_WALL 0.30 2.511 6.299 27.87 27.87 90.00 90.00 E
92E22C INT_WALL 0.30 2.511 6.299 13.94 13.94 270.00 90.00 W
7B1677 INT_SLAB_CEILING 0.30 1.887 3.839 8.36 8.36 270.00 0.00  
21C5E8 INT_SLAB_CEILING 0.30 1.887 3.839 25.08 25.08 180.00 0.00  
FDCEC5 INT_SLAB_CEILING 0.30 1.887 3.839 2.79 2.79 90.00 0.00  
C1F15F INT_SLAB_CEILING 0.30 1.887 3.839 13.38 13.38 180.00 0.00  
1E6611 INT_SLAB_CEILING 0.30 1.887 3.839 11.71 11.71 0.00 0.00  
35028C INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
852027 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
EBFE47 INT_WALL 0.30 2.511 6.299 26.01 26.01 0.00 90.00 N
D9965C INT_WALL 0.30 2.511 6.299 12.08 12.08 180.00 90.00 S
71783C INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
D8C098 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
66D163 INT_WALL 0.30 2.511 6.299 30.66 30.66 180.00 90.00 S
8D03E8 INT_WALL 0.30 2.511 6.299 20.44 20.44 0.00 90.00 N
9A0DF2 INT_WALL 0.30 2.511 6.299 11.15 11.15 0.00 90.00 N
FLOOR 1 LOCKER ROOM HALL SLAB FLOOR1LOCKERROOMHALLSLAB_FFACTOR 1.00 0.006 0.006 46.08 46.08 180.00 180.00  
1891E7 INT_SLAB_CEILING 0.30 1.887 3.839 1.95 1.95 270.00 0.00  
BD75DE INT_SLAB_CEILING 0.30 1.887 3.839 28.80 28.80 270.00 0.00  
3137C4 INT_SLAB_CEILING 0.30 1.887 3.839 1.67 1.67 270.00 0.00  
C8F2F1 INT_SLAB_CEILING 0.30 1.887 3.839 6.69 6.69 180.00 0.00  
6B171C INT_SLAB_CEILING 0.30 1.887 3.839 1.67 1.67 180.00 0.00  
86C171 INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 270.00 0.00  
C605B5 INT_SLAB_CEILING 0.30 1.887 3.839 0.28 0.28 90.00 0.00  
18AFE3 INT_WALL 0.30 2.511 6.299 11.15 11.15 180.00 90.00 S
761D33 INT_WALL 0.30 2.511 6.299 27.87 27.87 270.00 90.00 W
9C0202 INT_WALL 0.30 2.511 6.299 11.15 11.15 0.00 90.00 N
29BD5F INT_WALL 0.30 2.511 6.299 15.79 15.79 90.00 90.00 E
897BAF INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
3E6044 INT_WALL 0.30 2.511 6.299 4.65 4.65 90.00 90.00 E
FLOOR 1 LOUNGE SLAB FLOOR1LOUNGESLAB_FFACTOR 1.00 0.006 0.006 33.45 33.45 180.00 180.00  
7B9EEC INT_SLAB_CEILING 0.30 1.887 3.839 25.08 25.08 270.00 0.00  
B04E85 INT_SLAB_CEILING 0.30 1.887 3.839 8.36 8.36 90.00 0.00  
A4B378 INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
72BCFE INT_WALL 0.30 2.511 6.299 6.50 6.50 270.00 90.00 W
F0B690 INT_WALL 0.30 2.511 6.299 16.72 16.72 180.00 90.00 S
D2C53A INT_WALL 0.30 2.511 6.299 2.79 2.79 90.00 90.00 E
BFD4BB INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
92A2CB INT_WALL 0.30 2.511 6.299 14.86 14.86 0.00 90.00 N
1EC3A0 INT_WALL 0.30 2.511 6.299 4.65 4.65 90.00 90.00 E
E66ECE INT_WALL 0.30 2.511 6.299 2.79 2.79 180.00 90.00 S
290CAB INT_SLAB_CEILING 0.30 1.887 3.839 15.61 15.61 90.00 0.00  
824665 INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
68F53B INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
27B0D7 INT_WALL 0.30 2.511 6.299 2.79 2.79 270.00 90.00 W
90FDA9 INT_WALL 0.30 2.511 6.299 2.79 2.79 0.00 90.00 N
91DE28 INT_WALL 0.30 2.511 6.299 6.50 6.50 270.00 90.00 W
A8DB72 INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
8A30DD INT_WALL 0.30 2.511 6.299 3.72 3.72 90.00 90.00 E
596DE0 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
B92155 INT_WALL 0.30 2.511 6.299 9.29 9.29 180.00 90.00 S
FLOOR 1 MRI HALL SLAB FLOOR1MRIHALLSLAB_FFACTOR 1.00 0.006 0.006 13.66 13.66 180.00 180.00  
5CB500 INT_SLAB_CEILING 0.30 1.887 3.839 13.66 13.66 180.00 0.00  
2FAF44 INT_WALL 0.30 2.511 6.299 13.94 13.94 90.00 90.00 E
A78253 INT_WALL 0.30 2.511 6.299 16.72 16.72 0.00 90.00 N
E5BC3F INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
867BBB INT_WALL 0.30 2.511 6.299 18.58 18.58 180.00 90.00 S
F3084E INT_WALL 0.30 2.511 6.299 1.86 1.86 0.00 90.00 N
BA91C7 INT_WALL 0.30 2.511 6.299 6.50 6.50 90.00 90.00 E
FLOOR 1 MRI ROOM SLAB FLOOR1MRIROOMSLAB_FFACTOR 1.00 0.006 0.006 40.88 40.88 90.00 180.00  
803791 INT_SLAB_CEILING 0.30 1.887 3.839 40.88 40.88 90.00 0.00  
30DB21 INT_WALL 0.30 2.511 6.299 8.36 8.36 90.00 90.00 E
C9D24D INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
4ED109 INT_WALL 0.30 2.511 6.299 4.65 4.65 270.00 90.00 W
24139C INT_WALL 0.30 2.511 6.299 3.72 3.72 270.00 90.00 W
388F10 INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 90.00 0.00  
855191 INT_WALL 0.30 2.511 6.299 13.01 13.01 90.00 90.00 E
C0F51F INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
A59907 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
28DE5A INT_WALL 0.30 2.511 6.299 24.15 24.15 270.00 90.00 W
58B6B6 INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
725D3E INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
FLOOR 1 NOURISHMENT SLAB FLOOR1NOURISHMENTSLAB_FFACTOR 1.00 0.006 0.006 16.91 16.91 270.00 180.00  
4E5019 INT_SLAB_CEILING 0.30 1.887 3.839 0.65 0.65 180.00 0.00  
E8F02D INT_SLAB_CEILING 0.30 1.887 3.839 0.56 0.56 90.00 0.00  
6ECCF3 INT_SLAB_CEILING 0.30 1.887 3.839 0.09 0.09 0.00 0.00  
AA1F5C INT_SLAB_CEILING 0.30 1.887 3.839 3.90 3.90 0.00 0.00  
F665B1 INT_SLAB_CEILING 0.30 1.887 3.839 11.71 11.71 270.00 0.00  
6822BB INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
825233 INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
86A28D INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
C92A6E INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
114EC6 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
9EB05A INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
7434CD INT_WALL 0.30 2.511 6.299 11.15 11.15 0.00 90.00 N
344D34 INT_WALL 0.30 2.511 6.299 26.94 26.94 0.00 90.00 N
59CEFB INT_WALL 0.30 2.511 6.299 41.81 41.81 180.00 90.00 S
FLOOR 1 NURSE HALL SLAB FLOOR1NURSEHALLSLAB_FFACTOR 1.00 0.006 0.006 46.08 46.08 270.00 180.00  
C75191 INT_SLAB_CEILING 0.30 1.887 3.839 0.74 0.74 90.00 0.00  
92E327 INT_SLAB_CEILING 0.30 1.887 3.839 13.38 13.38 0.00 0.00  
7F6B1B INT_SLAB_CEILING 0.30 1.887 3.839 17.84 17.84 90.00 0.00  
4A49C1 INT_SLAB_CEILING 0.30 1.887 3.839 4.46 4.46 90.00 0.00  
8F5FFC INT_SLAB_CEILING 0.30 1.887 3.839 4.46 4.46 0.00 0.00  
DDBA1E INT_SLAB_CEILING 0.30 1.887 3.839 5.20 5.20 270.00 0.00  
4E3BB5 INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
415590 INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
D9F81F INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
E1B4BB INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
FLOOR 1 NURSE JANITOR SLAB FLOOR1NURSEJANITORSLAB_FFACTOR 1.00 0.006 0.006 5.02 5.02 180.00 180.00  
2CB843 INT_SLAB_CEILING 0.30 1.887 3.839 0.84 0.84 180.00 0.00  
E2AB17 INT_SLAB_CEILING 0.30 1.887 3.839 4.18 4.18 0.00 0.00  
464A53 INT_WALL 0.30 2.511 6.299 8.36 8.36 270.00 90.00 W
FE5062 INT_WALL 0.30 2.511 6.299 8.36 8.36 90.00 90.00 E
4A07CD INT_WALL 0.30 2.511 6.299 26.94 26.94 180.00 90.00 S
EE0803 INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
DFDE4F INT_WALL 0.30 2.511 6.299 12.08 12.08 0.00 90.00 N
A452BE INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
FLOOR 1 NURSE STATION SLAB FLOOR1NURSESTATIONSLAB_FFACTOR 1.00 0.006 0.006 24.25 24.25 180.00 180.00  
BD4B70 INT_SLAB_CEILING 0.30 1.887 3.839 0.84 0.84 90.00 0.00  
A0117C INT_SLAB_CEILING 0.30 1.887 3.839 15.05 15.05 90.00 0.00  
52F395 INT_SLAB_CEILING 0.30 1.887 3.839 3.34 3.34 270.00 0.00  
AA2E8F INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 90.00 0.00  
CA6EDA INT_WALL 0.30 2.511 6.299 8.36 8.36 270.00 90.00 W
5EB34C INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
5CD67D INT_WALL 0.30 2.511 6.299 8.36 8.36 90.00 90.00 E
E5CB03 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
FLOOR 1 NURSE TOILET SLAB FLOOR1NURSETOILETSLAB_FFACTOR 1.00 0.006 0.006 5.02 5.02 180.00 180.00  
156F92 INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 180.00 0.00  
361D65 INT_WALL 0.30 2.511 6.299 10.22 10.22 0.00 90.00 N
2B5816 INT_WALL 0.30 2.511 6.299 21.37 21.37 90.00 90.00 E
7B67EC INT_WALL 0.30 2.511 6.299 4.65 4.65 180.00 90.00 S
7E0561 INT_WALL 0.30 2.511 6.299 21.37 21.37 270.00 90.00 W
4E24F1 INT_WALL 0.30 2.511 6.299 9.29 9.29 0.00 90.00 N
8259AE INT_WALL 0.30 2.511 6.299 14.86 14.86 180.00 90.00 S
FLOOR 1 OFFICE SLAB FLOOR1OFFICESLAB_FFACTOR 1.00 0.006 0.006 44.87 44.87 0.00 180.00  
B754EC INT_SLAB_CEILING 0.30 1.887 3.839 9.75 9.75 0.00 0.00  
621A74 INT_SLAB_CEILING 0.30 1.887 3.839 15.05 15.05 270.00 0.00  
28F0DE INT_SLAB_CEILING 0.30 1.887 3.839 20.07 20.07 90.00 0.00  
83A098 INT_WALL 0.30 2.511 6.299 21.37 21.37 270.00 90.00 W
575A7B INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
7E9E26 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
E648BC INT_SLAB_CEILING 0.30 1.887 3.839 22.30 22.30 0.00 0.00  
FFE052 INT_SLAB_CEILING 0.30 1.887 3.839 14.31 14.31 270.00 0.00  
611A3F INT_SLAB_CEILING 0.30 1.887 3.839 6.13 6.13 90.00 0.00  
9C6F66 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
A2AAC5 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
1747DE INT_WALL 0.30 2.511 6.299 22.30 22.30 270.00 90.00 W
F4C599 INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
964F72 INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
726F67 INT_SLAB_CEILING 0.30 1.887 3.839 13.38 13.38 180.00 0.00  
406D70 INT_SLAB_CEILING 0.30 1.887 3.839 19.51 19.51 180.00 0.00  
368A44 INT_SLAB_CEILING 0.30 1.887 3.839 11.71 11.71 180.00 0.00  
9E12D4 INT_WALL 0.30 2.511 6.299 15.79 15.79 270.00 90.00 W
FD0958 INT_WALL 0.30 2.511 6.299 26.01 26.01 180.00 90.00 S
AE206C INT_WALL 0.30 2.511 6.299 26.01 26.01 0.00 90.00 N
966665 INT_WALL 0.30 2.511 6.299 2.79 2.79 90.00 90.00 E
52CA89 INT_WALL 0.30 2.511 6.299 13.01 13.01 90.00 90.00 E
FLOOR 1 OPERATING ROOM 3 SLAB FLOOR1OPERATINGROOM3SLAB_FFACTOR 1.00 0.006 0.006 44.22 44.22 0.00 180.00  
8F1C77 INT_SLAB_CEILING 0.30 1.887 3.839 1.30 1.30 180.00 0.00  
18AD08 INT_SLAB_CEILING 0.30 1.887 3.839 9.48 9.48 270.00 0.00  
69AE66 INT_SLAB_CEILING 0.30 1.887 3.839 5.20 5.20 180.00 0.00  
CF6C6E INT_SLAB_CEILING 0.30 1.887 3.839 4.55 4.55 0.00 0.00  
678B62 INT_SLAB_CEILING 0.30 1.887 3.839 23.69 23.69 90.00 0.00  
2B4DBD INT_WALL 0.30 2.511 6.299 2.79 2.79 0.00 90.00 N
FCD8D2 INT_WALL 0.30 2.511 6.299 8.36 8.36 270.00 90.00 W
F740DF INT_WALL 0.30 2.511 6.299 11.15 11.15 180.00 90.00 S
446771 INT_WALL 0.30 2.511 6.299 8.36 8.36 90.00 90.00 E
A2F014 INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
FLOOR 1 PACU SLAB FLOOR1PACUSLAB_FFACTOR 1.00 0.006 0.006 10.03 10.03 180.00 180.00  
995832 INT_SLAB_CEILING 0.30 1.887 3.839 10.03 10.03 180.00 0.00  
33A280 INT_WALL 0.30 2.511 6.299 21.37 21.37 270.00 90.00 W
BABBB4 INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
F9B592 INT_WALL 0.30 2.511 6.299 7.43 7.43 0.00 90.00 N
6E46A9 INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
BA8FF7 INT_WALL 0.30 2.511 6.299 8.36 8.36 90.00 90.00 E
25B45C INT_WALL 0.30 2.511 6.299 24.15 24.15 90.00 90.00 E
592524 INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
EAACE4 INT_WALL 0.30 2.511 6.299 13.94 13.94 90.00 90.00 E
3AE420 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
414FE2 INT_WALL 0.30 2.511 6.299 19.51 19.51 270.00 90.00 W
DEAC23 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
22DAE3 INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
FLOOR 1 PRE-OP HALL SLAB FLOOR1PRE-OPHALLSLAB_FFACTOR 1.00 0.006 0.006 49.05 49.05 180.00 180.00  
388CB3 INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 90.00 0.00  
FB3834 INT_SLAB_CEILING 0.30 1.887 3.839 8.36 8.36 270.00 0.00  
343C52 INT_SLAB_CEILING 0.30 1.887 3.839 13.38 13.38 0.00 0.00  
E63CF4 INT_SLAB_CEILING 0.30 1.887 3.839 4.46 4.46 0.00 0.00  
D6D2A5 INT_SLAB_CEILING 0.30 1.887 3.839 4.46 4.46 270.00 0.00  
83172E INT_SLAB_CEILING 0.30 1.887 3.839 8.36 8.36 270.00 0.00  
8FE324 INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 90.00 0.00  
4DA0F5 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
8F966C INT_WALL 0.30 2.511 6.299 15.79 15.79 270.00 90.00 W
FA21EE INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
5B255F INT_WALL 0.30 2.511 6.299 19.51 19.51 90.00 90.00 E
3C43B2 INT_SLAB_CEILING 0.30 1.887 3.839 9.20 9.20 270.00 0.00  
BC6EE7 INT_SLAB_CEILING 0.30 1.887 3.839 3.34 3.34 0.00 0.00  
363652 INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 180.00 0.00  
551E65 INT_WALL 0.30 2.511 6.299 24.15 24.15 90.00 90.00 E
8C3884 INT_WALL 0.30 2.511 6.299 12.08 12.08 180.00 90.00 S
9853A2 INT_WALL 0.30 2.511 6.299 24.15 24.15 270.00 90.00 W
7AE5B9 INT_WALL 0.30 2.511 6.299 12.08 12.08 0.00 90.00 N
FLOOR 1 PRE-OP ROOM 2 SLAB FLOOR1PRE-OPROOM2SLAB_FFACTOR 1.00 0.006 0.006 31.40 31.40 0.00 180.00  
39AFEA INT_SLAB_CEILING 0.30 1.887 3.839 0.09 0.09 90.00 0.00  
CABD0E INT_SLAB_CEILING 0.30 1.887 3.839 1.21 1.21 180.00 0.00  
AF38CF INT_SLAB_CEILING 0.30 1.887 3.839 1.11 1.11 0.00 0.00  
C0A312 INT_SLAB_CEILING 0.30 1.887 3.839 7.25 7.25 0.00 0.00  
661D88 INT_SLAB_CEILING 0.30 1.887 3.839 18.39 18.39 0.00 0.00  
AFFD01 INT_SLAB_CEILING 0.30 1.887 3.839 3.34 3.34 0.00 0.00  
2DEB73 INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
7D08C0 INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
36E420 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
97616F INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 270.00 0.00  
95486C INT_WALL 0.30 2.511 6.299 8.36 8.36 270.00 90.00 W
EAE60F INT_WALL 0.30 2.511 6.299 10.22 10.22 180.00 90.00 S
704EC3 INT_WALL 0.30 2.511 6.299 13.94 13.94 90.00 90.00 E
E20721 INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
FA9EF2 INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
673317 INT_SLAB_CEILING 0.30 1.887 3.839 6.97 6.97 270.00 0.00  
E5C1C9 INT_SLAB_CEILING 0.30 1.887 3.839 16.72 16.72 270.00 0.00  
79376C INT_SLAB_CEILING 0.30 1.887 3.839 2.79 2.79 90.00 0.00  
6EA718 INT_WALL 0.30 2.511 6.299 13.94 13.94 270.00 90.00 W
2730E5 INT_WALL 0.30 2.511 6.299 21.37 21.37 90.00 90.00 E
E608B9 INT_WALL 0.30 2.511 6.299 7.43 7.43 0.00 90.00 N
25AB11 INT_WALL 0.30 2.511 6.299 4.65 4.65 0.00 90.00 N
5A39B1 INT_WALL 0.30 2.511 6.299 15.79 15.79 90.00 90.00 E
234734 INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
57B162 INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
7BB928 INT_WALL 0.30 2.511 6.299 19.51 19.51 270.00 90.00 W
A02892 INT_SLAB_CEILING 0.30 1.887 3.839 4.92 4.92 180.00 0.00  
9114B7 INT_SLAB_CEILING 0.30 1.887 3.839 13.38 13.38 90.00 0.00  
700E69 INT_SLAB_CEILING 0.30 1.887 3.839 28.99 28.99 270.00 0.00  
11E9BF INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
839A66 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
FE2C3E INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
CD7BAD INT_WALL 0.30 2.511 6.299 14.86 14.86 0.00 90.00 N
6A1AB7 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
FLOOR 1 RECEPTION HALL SLAB FLOOR1RECEPTIONHALLSLAB_FFACTOR 1.00 0.006 0.006 11.89 11.89 0.00 180.00  
68AAF3 INT_SLAB_CEILING 0.30 1.887 3.839 4.55 4.55 0.00 0.00  
DE014E INT_SLAB_CEILING 0.30 1.887 3.839 5.85 5.85 0.00 0.00  
709E99 INT_SLAB_CEILING 0.30 1.887 3.839 1.49 1.49 180.00 0.00  
F4FE92 INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
66B6F7 INT_WALL 0.30 2.511 6.299 11.15 11.15 90.00 90.00 E
72C4ED INT_WALL 0.30 2.511 6.299 41.81 41.81 0.00 90.00 N
C5ECA6 INT_SLAB_CEILING 0.30 1.887 3.839 12.26 12.26 90.00 0.00  
65D500 INT_SLAB_CEILING 0.30 1.887 3.839 26.76 26.76 90.00 0.00  
AE5EBC INT_SLAB_CEILING 0.30 1.887 3.839 6.69 6.69 90.00 0.00  
2A1A9E INT_SLAB_CEILING 0.30 1.887 3.839 4.46 4.46 270.00 0.00  
612A96 INT_WALL 0.30 2.511 6.299 15.79 15.79 270.00 90.00 W
BDC047 INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
42E287 INT_WALL 0.30 2.511 6.299 15.79 15.79 90.00 90.00 E
513564 INT_SLAB_CEILING 0.30 1.887 3.839 3.90 3.90 0.00 0.00  
58F893 INT_SLAB_CEILING 0.30 1.887 3.839 7.15 7.15 180.00 0.00  
7816FD INT_WALL 0.30 2.511 6.299 13.01 13.01 90.00 90.00 E
1B2EF8 INT_WALL 0.30 2.511 6.299 13.01 13.01 270.00 90.00 W
24EAE3 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
9DB411 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
FLOOR 1 SCRUB SLAB FLOOR1SCRUBSLAB_FFACTOR 1.00 0.006 0.006 7.80 7.80 90.00 180.00  
7008C0 INT_SLAB_CEILING 0.30 1.887 3.839 7.80 7.80 90.00 0.00  
762F8C INT_WALL 0.30 2.511 6.299 2.79 2.79 180.00 90.00 S
5D199F INT_WALL 0.30 2.511 6.299 2.79 2.79 90.00 90.00 E
ACADA4 INT_WALL 0.30 2.511 6.299 13.01 13.01 270.00 90.00 W
4398AD INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
9E478E INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
6B967C INT_WALL 0.30 2.511 6.299 10.22 10.22 90.00 90.00 E
FLOOR 1 SOIL SLAB FLOOR1SOILSLAB_FFACTOR 1.00 0.006 0.006 11.71 11.71 90.00 180.00  
4B54B4 INT_SLAB_CEILING 0.30 1.887 3.839 0.84 0.84 0.00 0.00  
88D2F8 INT_SLAB_CEILING 0.30 1.887 3.839 5.85 5.85 180.00 0.00  
7274F6 INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 0.00 0.00  
A1087A INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
41CE25 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
9A776E INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
9ABA5B INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
FLOOR 1 SOIL HOLD SLAB FLOOR1SOILHOLDSLAB_FFACTOR 1.00 0.006 0.006 5.20 5.20 0.00 180.00  
58A74A INT_SLAB_CEILING 0.30 1.887 3.839 4.46 4.46 270.00 0.00  
D78A26 INT_SLAB_CEILING 0.30 1.887 3.839 0.74 0.74 90.00 0.00  
37E2C7 INT_WALL 0.30 2.511 6.299 11.15 11.15 90.00 90.00 E
23683B INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
CA9655 INT_WALL 0.30 2.511 6.299 2.79 2.79 270.00 90.00 W
121DFF INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
FAE342 INT_WALL 0.30 2.511 6.299 8.36 8.36 270.00 90.00 W
FLOOR 1 SOIL WORK SLAB FLOOR1SOILWORKSLAB_FFACTOR 1.00 0.006 0.006 16.72 16.72 0.00 180.00  
A44272 INT_SLAB_CEILING 0.30 1.887 3.839 1.86 1.86 90.00 0.00  
B9DDBA INT_SLAB_CEILING 0.30 1.887 3.839 5.57 5.57 90.00 0.00  
9EBF3E INT_SLAB_CEILING 0.30 1.887 3.839 2.79 2.79 0.00 0.00  
903092 INT_SLAB_CEILING 0.30 1.887 3.839 6.50 6.50 0.00 0.00  
5FD018 INT_WALL 0.30 2.511 6.299 7.43 7.43 0.00 90.00 N
809229 INT_WALL 0.30 2.511 6.299 11.15 11.15 90.00 90.00 E
CA45DE INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
5B693D INT_WALL 0.30 2.511 6.299 7.43 7.43 0.00 90.00 N
FBDD49 INT_SLAB_CEILING 0.30 1.887 3.839 13.38 13.38 0.00 0.00  
4284B6 INT_SLAB_CEILING 0.30 1.887 3.839 6.69 6.69 90.00 0.00  
FCE842 INT_SLAB_CEILING 0.30 1.887 3.839 7.80 7.80 270.00 0.00  
829DCE INT_WALL 0.30 2.511 6.299 13.01 13.01 270.00 90.00 W
E77E00 INT_WALL 0.30 2.511 6.299 21.37 21.37 90.00 90.00 E
8C4FA5 INT_WALL 0.30 2.511 6.299 7.43 7.43 0.00 90.00 N
B3A518 INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
44686F INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
6A2C62 INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
A809DD INT_WALL 0.30 2.511 6.299 10.22 10.22 270.00 90.00 W
EE0E68 INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
88AE01 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
2C9CF4 INT_WALL 0.30 2.511 6.299 13.01 13.01 90.00 90.00 E
765EA5 INT_WALL 0.30 2.511 6.299 22.30 22.30 90.00 90.00 E
2B370E INT_WALL 0.30 2.511 6.299 6.50 6.50 90.00 90.00 E
F30797 INT_WALL 0.30 2.511 6.299 8.36 8.36 90.00 90.00 E
3179A6 INT_SLAB_CEILING 0.30 1.887 3.839 8.92 8.92 0.00 0.00  
370DB2 INT_SLAB_CEILING 0.30 1.887 3.839 5.20 5.20 180.00 0.00  
34B3F0 INT_SLAB_CEILING 0.30 1.887 3.839 7.43 7.43 90.00 0.00  
CEDA0D INT_SLAB_CEILING 0.30 1.887 3.839 5.95 5.95 0.00 0.00  
4469CD INT_SLAB_CEILING 0.30 1.887 3.839 13.38 13.38 90.00 0.00  
F62393 INT_SLAB_CEILING 0.30 1.887 3.839 4.46 4.46 90.00 0.00  
340FB5 INT_SLAB_CEILING 0.30 1.887 3.839 4.46 4.46 0.00 0.00  
CDA7F8 INT_SLAB_CEILING 0.30 1.887 3.839 7.43 7.43 270.00 0.00  
8043B2 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
38F548 INT_WALL 0.30 2.511 6.299 11.15 11.15 90.00 90.00 E
96662A INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
1003C1 INT_WALL 0.30 2.511 6.299 30.66 30.66 0.00 90.00 N
863C6C INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
808817 INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
EA4B61 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
FLOOR 1 NURSE STORAGE SLAB FLOOR1NURSESTORAGESLAB_FFACTOR 1.00 0.006 0.006 36.79 36.79 0.00 180.00  
C1737B INT_SLAB_CEILING 0.30 1.887 3.839 10.22 10.22 0.00 0.00  
D44BF1 INT_SLAB_CEILING 0.30 1.887 3.839 3.07 3.07 180.00 0.00  
5C05FF INT_SLAB_CEILING 0.30 1.887 3.839 23.50 23.50 0.00 0.00  
707E04 INT_WALL 0.30 2.511 6.299 14.86 14.86 90.00 90.00 E
891195 INT_WALL 0.30 2.511 6.299 11.15 11.15 180.00 90.00 S
8B4DC1 INT_WALL 0.30 2.511 6.299 6.50 6.50 90.00 90.00 E
19D150 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
814856 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
5B533A INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
76F2F2 INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
D61127 INT_WALL 0.30 2.511 6.299 13.01 13.01 270.00 90.00 W
196C5F INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
1875B3 INT_SLAB_CEILING 0.30 1.887 3.839 18.21 18.21 180.00 0.00  
39E49D INT_WALL 0.30 2.511 6.299 8.36 8.36 90.00 90.00 E
F43F35 INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
89BBEB INT_WALL 0.30 2.511 6.299 7.43 7.43 0.00 90.00 N
87231D INT_WALL 0.30 2.511 6.299 14.86 14.86 270.00 90.00 W
C1C64E INT_WALL 0.30 2.511 6.299 6.50 6.50 90.00 90.00 E
1D9EED INT_WALL 0.30 2.511 6.299 2.79 2.79 270.00 90.00 W
20FB14 INT_WALL 0.30 2.511 6.299 4.65 4.65 270.00 90.00 W
DEFACF INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
5136E3 INT_SLAB_CEILING 0.30 1.887 3.839 0.74 0.74 0.00 0.00  
EFCC3C INT_SLAB_CEILING 0.30 1.887 3.839 11.15 11.15 270.00 0.00  
2E8328 INT_WALL 0.30 2.511 6.299 6.50 6.50 90.00 90.00 E
E321D9 INT_WALL 0.30 2.511 6.299 6.50 6.50 270.00 90.00 W
E89C6C INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
816F6D INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
FLOOR 1 UTILITY JANITOR SLAB FLOOR1UTILITYJANITORSLAB_FFACTOR 1.00 0.006 0.006 3.90 3.90 90.00 180.00  
5F697A INT_SLAB_CEILING 0.30 1.887 3.839 3.90 3.90 90.00 0.00  
EC28A9 INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
204CB9 INT_WALL 0.30 2.511 6.299 18.58 18.58 0.00 90.00 N
62475F INT_WALL 0.30 2.511 6.299 8.36 8.36 270.00 90.00 W
87BFF9 INT_WALL 0.30 2.511 6.299 8.36 8.36 270.00 90.00 W
23CCB1 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
7DB101 INT_SLAB_CEILING 0.30 1.887 3.839 10.03 10.03 270.00 0.00  
F28371 INT_SLAB_CEILING 0.30 1.887 3.839 23.41 23.41 180.00 0.00  
231744 INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
2FEACD INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
AA1709 INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
C34217 INT_SLAB_CEILING 0.30 1.887 3.839 6.69 6.69 90.00 0.00  
9AC2E9 INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
436189 INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
B184C1 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
BC8EB7 INT_WALL 0.30 2.511 6.299 7.43 7.43 0.00 90.00 N
75353D INT_SLAB_FLOOR 0.30 1.887 3.839 8.92 8.92 270.00 180.00  
2BD1E8 INT_SLAB_FLOOR 0.30 1.887 3.839 22.30 22.30 180.00 180.00  
240A7C INT_SLAB_CEILING 0.30 1.887 3.839 31.22 31.22 180.00 0.00  
F6D879 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
1701A6 INT_WALL 0.30 2.511 6.299 7.43 7.43 0.00 90.00 N
772842 INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
3C9825 INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
C2CE5F INT_SLAB_FLOOR 0.30 1.887 3.839 5.95 5.95 0.00 180.00  
7149EA INT_SLAB_CEILING 0.30 1.887 3.839 5.95 5.95 0.00 0.00  
296861 INT_WALL 0.30 2.511 6.299 9.29 9.29 90.00 90.00 E
3D4DE8 INT_WALL 0.30 2.511 6.299 9.29 9.29 270.00 90.00 W
8A5790 INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
2DB420 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
56C7DA INT_SLAB_FLOOR 0.30 1.887 3.839 6.50 6.50 90.00 180.00  
E1B973 INT_SLAB_CEILING 0.30 1.887 3.839 6.50 6.50 90.00 0.00  
640E64 INT_WALL 0.30 2.511 6.299 27.87 27.87 90.00 90.00 E
10E44F INT_WALL 0.30 2.511 6.299 11.15 11.15 0.00 90.00 N
6E3B28 INT_SLAB_FLOOR 0.30 1.887 3.839 6.69 6.69 270.00 180.00  
14C7EF INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 270.00 180.00  
5EBA9B INT_SLAB_FLOOR 0.30 1.887 3.839 13.38 13.38 270.00 180.00  
F24E0D INT_SLAB_FLOOR 0.30 1.887 3.839 3.34 3.34 270.00 180.00  
D023D9 INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 0.00 180.00  
A4BE81 INT_SLAB_CEILING 0.30 1.887 3.839 33.45 33.45 0.00 0.00  
4EE021 INT_WALL 0.30 2.511 6.299 27.87 27.87 90.00 90.00 E
6ED237 INT_WALL 0.30 2.511 6.299 27.87 27.87 270.00 90.00 W
ADD799 INT_WALL 0.30 2.511 6.299 16.72 16.72 0.00 90.00 N
4017DC INT_SLAB_FLOOR 0.30 1.887 3.839 12.26 12.26 90.00 180.00  
CCAA9D INT_SLAB_FLOOR 0.30 1.887 3.839 13.38 13.38 180.00 180.00  
4968A2 INT_SLAB_FLOOR 0.30 1.887 3.839 7.80 7.80 270.00 180.00  
4579A7 INT_SLAB_FLOOR 0.30 1.887 3.839 15.05 15.05 180.00 180.00  
FDAEB8 INT_SLAB_FLOOR 0.30 1.887 3.839 1.11 1.11 270.00 180.00  
E3B855 INT_SLAB_FLOOR 0.30 1.887 3.839 0.56 0.56 90.00 180.00  
906F5E INT_SLAB_CEILING 0.30 1.887 3.839 50.17 50.17 0.00 0.00  
DFA4B1 INT_WALL 0.30 2.511 6.299 22.30 22.30 0.00 90.00 N
F23BF4 INT_WALL 0.30 2.511 6.299 27.87 27.87 270.00 90.00 W
26E66C INT_WALL 0.30 2.511 6.299 27.87 27.87 90.00 90.00 E
17C5CF INT_SLAB_FLOOR 0.30 1.887 3.839 26.76 26.76 180.00 180.00  
BA0A29 INT_SLAB_FLOOR 0.30 1.887 3.839 17.84 17.84 180.00 180.00  
26AF41 INT_SLAB_FLOOR 0.30 1.887 3.839 1.86 1.86 180.00 180.00  
75A3C4 INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 90.00 180.00  
BEC196 INT_SLAB_FLOOR 0.30 1.887 3.839 10.03 10.03 90.00 180.00  
9B49F5 INT_SLAB_FLOOR 0.30 1.887 3.839 0.84 0.84 90.00 180.00  
EB611D INT_SLAB_FLOOR 0.30 1.887 3.839 0.37 0.37 0.00 180.00  
C81AED INT_SLAB_FLOOR 0.30 1.887 3.839 0.84 0.84 270.00 180.00  
BD5B50 INT_SLAB_FLOOR 0.30 1.887 3.839 3.34 3.34 180.00 180.00  
3AEAAB INT_SLAB_CEILING 0.30 1.887 3.839 13.01 13.01 90.00 0.00  
D74115 INT_SLAB_CEILING 0.30 1.887 3.839 44.59 44.59 0.00 0.00  
5065F0 INT_SLAB_CEILING 0.30 1.887 3.839 9.29 9.29 270.00 0.00  
7C84B6 INT_WALL 0.30 2.511 6.299 11.15 11.15 90.00 90.00 E
D88779 INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
577E2E INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
4E78E0 INT_SLAB_FLOOR 0.30 1.887 3.839 7.80 7.80 90.00 180.00  
C0697F INT_SLAB_CEILING 0.30 1.887 3.839 7.80 7.80 90.00 0.00  
83B6E3 INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
AC956A INT_WALL 0.30 2.511 6.299 23.23 23.23 270.00 90.00 W
BFA29B INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
65AB67 INT_SLAB_FLOOR 0.30 1.887 3.839 9.10 9.10 180.00 180.00  
C25071 INT_SLAB_FLOOR 0.30 1.887 3.839 23.41 23.41 0.00 180.00  
31B3DF INT_SLAB_CEILING 0.30 1.887 3.839 32.52 32.52 270.00 0.00  
F29458 INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
1EB5B1 INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
47CE83 INT_WALL 0.30 2.511 6.299 13.94 13.94 270.00 90.00 W
A8FC82 INT_WALL 0.30 2.511 6.299 6.50 6.50 90.00 90.00 E
C84AE1 INT_SLAB_FLOOR 0.30 1.887 3.839 11.15 11.15 90.00 180.00  
F67EC8 INT_SLAB_FLOOR 0.30 1.887 3.839 5.20 5.20 90.00 180.00  
10FB67 INT_SLAB_FLOOR 0.30 1.887 3.839 1.30 1.30 180.00 180.00  
1624C5 INT_SLAB_FLOOR 0.30 1.887 3.839 3.25 3.25 180.00 180.00  
917AB5 INT_SLAB_CEILING 0.30 1.887 3.839 20.90 20.90 90.00 0.00  
247258 INT_WALL 0.30 2.511 6.299 30.66 30.66 270.00 90.00 W
FF8B08 INT_WALL 0.30 2.511 6.299 30.66 30.66 90.00 90.00 E
F976A9 INT_WALL 0.30 2.511 6.299 22.30 22.30 180.00 90.00 S
8D6453 INT_SLAB_FLOOR 0.30 1.887 3.839 10.41 10.41 0.00 180.00  
D1899C INT_SLAB_FLOOR 0.30 1.887 3.839 0.74 0.74 0.00 180.00  
5620F1 INT_SLAB_FLOOR 0.30 1.887 3.839 23.69 23.69 90.00 180.00  
40E182 INT_SLAB_FLOOR 0.30 1.887 3.839 6.97 6.97 270.00 180.00  
A6147C INT_SLAB_FLOOR 0.30 1.887 3.839 25.08 25.08 0.00 180.00  
37898A INT_SLAB_FLOOR 0.30 1.887 3.839 6.69 6.69 180.00 180.00  
F0D8EE INT_SLAB_CEILING 0.30 1.887 3.839 30.66 30.66 90.00 0.00  
567037 INT_SLAB_CEILING 0.30 1.887 3.839 6.13 6.13 180.00 0.00  
6B3E65 INT_SLAB_CEILING 0.30 1.887 3.839 17.84 17.84 90.00 0.00  
245972 INT_SLAB_CEILING 0.30 1.887 3.839 11.15 11.15 90.00 0.00  
F17DF7 INT_SLAB_CEILING 0.30 1.887 3.839 7.80 7.80 0.00 0.00  
D7DC8D INT_WALL 0.30 2.511 6.299 13.94 13.94 90.00 90.00 E
6A2DCE INT_WALL 0.30 2.511 6.299 13.94 13.94 270.00 90.00 W
7A03ED INT_WALL 0.30 2.511 6.299 16.72 16.72 180.00 90.00 S
A9A1F6 INT_SLAB_FLOOR 0.30 1.887 3.839 25.08 25.08 0.00 180.00  
DA760E INT_SLAB_CEILING 0.30 1.887 3.839 25.08 25.08 0.00 0.00  
35051E INT_WALL 0.30 2.511 6.299 30.66 30.66 270.00 90.00 W
685FFA INT_WALL 0.30 2.511 6.299 30.66 30.66 90.00 90.00 E
B51929 INT_WALL 0.30 2.511 6.299 11.15 11.15 180.00 90.00 S
8E5734 INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 90.00 180.00  
4E920E INT_SLAB_FLOOR 0.30 1.887 3.839 16.72 16.72 0.00 180.00  
87C477 INT_SLAB_FLOOR 0.30 1.887 3.839 15.05 15.05 270.00 180.00  
5D2769 INT_SLAB_CEILING 0.30 1.887 3.839 36.79 36.79 180.00 0.00  
9E6B6C INT_WALL 0.30 2.511 6.299 27.87 27.87 270.00 90.00 W
DF91E0 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
53450D INT_WALL 0.30 2.511 6.299 27.87 27.87 90.00 90.00 E
DFCCAE INT_SLAB_FLOOR 0.30 1.887 3.839 8.36 8.36 90.00 180.00  
D4B714 INT_SLAB_FLOOR 0.30 1.887 3.839 0.09 0.09 0.00 180.00  
3AE495 INT_SLAB_FLOOR 0.30 1.887 3.839 0.84 0.84 0.00 180.00  
526C70 INT_SLAB_FLOOR 0.30 1.887 3.839 0.74 0.74 0.00 180.00  
2C31F2 INT_SLAB_FLOOR 0.30 1.887 3.839 6.69 6.69 180.00 180.00  
E26130 INT_SLAB_CEILING 0.30 1.887 3.839 16.72 16.72 270.00 0.00  
42FAB2 INT_WALL 0.30 2.511 6.299 27.87 27.87 270.00 90.00 W
815D63 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
6713DA INT_WALL 0.30 2.511 6.299 27.87 27.87 90.00 90.00 E
4C8372 INT_SLAB_FLOOR 0.30 1.887 3.839 6.69 6.69 180.00 180.00  
243E09 INT_SLAB_FLOOR 0.30 1.887 3.839 4.46 4.46 180.00 180.00  
C94CC0 INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 180.00 180.00  
BD39AC INT_SLAB_FLOOR 0.30 1.887 3.839 0.09 0.09 270.00 180.00  
75EAF8 INT_SLAB_FLOOR 0.30 1.887 3.839 0.46 0.46 90.00 180.00  
E9AEFF INT_SLAB_CEILING 0.30 1.887 3.839 16.72 16.72 270.00 0.00  
479A9C INT_WALL 0.30 2.511 6.299 27.87 27.87 270.00 90.00 W
DA6040 INT_WALL 0.30 2.511 6.299 11.15 11.15 90.00 90.00 E
BC25F3 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
C08963 INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
36A02A INT_WALL 0.30 2.511 6.299 9.29 9.29 90.00 90.00 E
A08A28 INT_SLAB_FLOOR 0.30 1.887 3.839 2.23 2.23 180.00 180.00  
F87FCE INT_SLAB_FLOOR 0.30 1.887 3.839 4.46 4.46 180.00 180.00  
BAE3F8 INT_SLAB_FLOOR 0.30 1.887 3.839 4.46 4.46 180.00 180.00  
D10995 INT_SLAB_FLOOR 0.30 1.887 3.839 5.57 5.57 0.00 180.00  
D4A2A4 INT_SLAB_CEILING 0.30 1.887 3.839 5.57 5.57 180.00 0.00  
6C1891 INT_SLAB_CEILING 0.30 1.887 3.839 11.15 11.15 270.00 0.00  
46F148 INT_WALL 0.30 2.511 6.299 9.29 9.29 90.00 90.00 E
E7EC3B INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
55191F INT_WALL 0.30 2.511 6.299 30.66 30.66 270.00 90.00 W
3947B8 INT_WALL 0.30 2.511 6.299 13.94 13.94 90.00 90.00 E
3B9E2E INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
C2156D INT_SLAB_FLOOR 0.30 1.887 3.839 1.67 1.67 180.00 180.00  
5CA4CF INT_SLAB_FLOOR 0.30 1.887 3.839 4.46 4.46 0.00 180.00  
4AA9BC INT_SLAB_FLOOR 0.30 1.887 3.839 2.79 2.79 0.00 180.00  
D1E495 INT_SLAB_FLOOR 0.30 1.887 3.839 9.48 9.48 90.00 180.00  
4180E7 INT_SLAB_CEILING 0.30 1.887 3.839 18.39 18.39 90.00 0.00  
247FD8 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
2E6DF0 INT_WALL 0.30 2.511 6.299 13.94 13.94 270.00 90.00 W
14F382 INT_WALL 0.30 2.511 6.299 30.66 30.66 90.00 90.00 E
ED8563 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
A1BBBE INT_WALL 0.30 2.511 6.299 9.29 9.29 270.00 90.00 W
E0C60A INT_SLAB_FLOOR 0.30 1.887 3.839 1.67 1.67 270.00 180.00  
772953 INT_SLAB_FLOOR 0.30 1.887 3.839 8.36 8.36 270.00 180.00  
15A02B INT_SLAB_FLOOR 0.30 1.887 3.839 8.36 8.36 0.00 180.00  
B9D6E3 INT_SLAB_CEILING 0.30 1.887 3.839 18.39 18.39 90.00 0.00  
942718 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
D2C12A INT_WALL 0.30 2.511 6.299 9.29 9.29 90.00 90.00 E
5556EE INT_WALL 0.30 2.511 6.299 30.66 30.66 270.00 90.00 W
D37566 INT_WALL 0.30 2.511 6.299 13.94 13.94 90.00 90.00 E
E7055D INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
EC3BEA INT_SLAB_FLOOR 0.30 1.887 3.839 2.79 2.79 90.00 180.00  
D2FA45 INT_SLAB_FLOOR 0.30 1.887 3.839 6.97 6.97 270.00 180.00  
98E1BD INT_SLAB_FLOOR 0.30 1.887 3.839 8.36 8.36 270.00 180.00  
5F9E13 INT_SLAB_FLOOR 0.30 1.887 3.839 0.28 0.28 180.00 180.00  
B4F89F INT_SLAB_CEILING 0.30 1.887 3.839 18.39 18.39 270.00 0.00  
4AD319 INT_WALL 0.30 2.511 6.299 6.50 6.50 90.00 90.00 E
E0C0A7 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
5B736E INT_SLAB_FLOOR 0.30 1.887 3.839 5.85 5.85 180.00 180.00  
F6E6D8 INT_SLAB_CEILING 0.30 1.887 3.839 5.85 5.85 180.00 0.00  
97BB21 INT_WALL 0.30 2.511 6.299 7.43 7.43 0.00 90.00 N
7620CF INT_WALL 0.30 2.511 6.299 9.29 9.29 270.00 90.00 W
680AA1 INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
A524F1 INT_WALL 0.30 2.511 6.299 9.29 9.29 90.00 90.00 E
4CDC86 INT_SLAB_FLOOR 0.30 1.887 3.839 7.43 7.43 0.00 180.00  
B352F7 INT_SLAB_CEILING 0.30 1.887 3.839 7.43 7.43 0.00 0.00  
CBB2D7 INT_WALL 0.30 2.511 6.299 9.29 9.29 270.00 90.00 W
D0731B INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ECDEDB INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ED1D7F INT_WALL 0.30 2.511 6.299 9.29 9.29 90.00 90.00 E
2805F0 INT_SLAB_FLOOR 0.30 1.887 3.839 7.43 7.43 90.00 180.00  
5A7EAB INT_SLAB_FLOOR 0.30 1.887 3.839 1.95 1.95 180.00 180.00  
291561 INT_SLAB_FLOOR 0.30 1.887 3.839 4.55 4.55 0.00 180.00  
4E1563 INT_SLAB_CEILING 0.30 1.887 3.839 13.94 13.94 180.00 0.00  
A49FCC INT_WALL 0.30 2.511 6.299 9.29 9.29 270.00 90.00 W
5DBD9D INT_WALL 0.30 2.511 6.299 16.72 16.72 180.00 90.00 S
491317 INT_WALL 0.30 2.511 6.299 16.72 16.72 0.00 90.00 N
462370 INT_WALL 0.30 2.511 6.299 9.29 9.29 90.00 90.00 E
9EADD8 INT_SLAB_FLOOR 0.30 1.887 3.839 11.71 11.71 0.00 180.00  
DE8843 INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 180.00 180.00  
C45BF3 INT_SLAB_CEILING 0.30 1.887 3.839 16.72 16.72 270.00 0.00  
AAF377 INT_WALL 0.30 2.511 6.299 37.16 37.16 270.00 90.00 W
CE4555 INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
A8A4FA INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
352740 INT_SLAB_FLOOR 0.30 1.887 3.839 19.51 19.51 0.00 180.00  
D3CF55 INT_SLAB_FLOOR 0.30 1.887 3.839 18.21 18.21 0.00 180.00  
64A2F7 INT_SLAB_FLOOR 0.30 1.887 3.839 14.31 14.31 180.00 180.00  
D1A180 INT_SLAB_CEILING 0.30 1.887 3.839 10.41 10.41 0.00 0.00  
9BB582 INT_SLAB_CEILING 0.30 1.887 3.839 41.62 41.62 180.00 0.00  
DFA16C INT_WALL 0.30 2.511 6.299 37.16 37.16 90.00 90.00 E
2884D1 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
CC4EB4 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
B2F07D INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
AF86E1 INT_WALL 0.30 2.511 6.299 8.36 8.36 90.00 90.00 E
571934 INT_WALL 0.30 2.511 6.299 23.23 23.23 90.00 90.00 E
67A7F3 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
24E235 INT_WALL 0.30 2.511 6.299 9.29 9.29 270.00 90.00 W
AB568E INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
577A10 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
988ACA INT_WALL 0.30 2.511 6.299 9.29 9.29 270.00 90.00 W
F5AF76 INT_WALL 0.30 2.511 6.299 16.72 16.72 270.00 90.00 W
4EDE0A INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
874DF8 INT_SLAB_FLOOR 0.30 1.887 3.839 6.13 6.13 270.00 180.00  
8C822C INT_SLAB_FLOOR 0.30 1.887 3.839 7.80 7.80 270.00 180.00  
B44BE3 INT_SLAB_FLOOR 0.30 1.887 3.839 13.38 13.38 270.00 180.00  
4F2F27 INT_SLAB_FLOOR 0.30 1.887 3.839 3.90 3.90 180.00 180.00  
909DB9 INT_SLAB_FLOOR 0.30 1.887 3.839 10.03 10.03 0.00 180.00  
30A09C INT_SLAB_CEILING 0.30 1.887 3.839 8.92 8.92 90.00 0.00  
BFEF28 INT_SLAB_CEILING 0.30 1.887 3.839 27.87 27.87 90.00 0.00  
C588CC INT_SLAB_CEILING 0.30 1.887 3.839 4.46 4.46 0.00 0.00  
23C13E INT_WALL 0.30 2.511 6.299 41.81 41.81 0.00 90.00 N
3DE7A6 INT_WALL 0.30 2.511 6.299 11.15 11.15 180.00 90.00 S
FCDEAC INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
AB4E10 INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
E7BF7F INT_WALL 0.30 2.511 6.299 16.72 16.72 90.00 90.00 E
FA00FE INT_SLAB_FLOOR 0.30 1.887 3.839 5.57 5.57 90.00 180.00  
14CDC6 INT_SLAB_FLOOR 0.30 1.887 3.839 28.99 28.99 270.00 180.00  
39BFFB INT_SLAB_FLOOR 0.30 1.887 3.839 39.02 39.02 180.00 180.00  
167608 INT_SLAB_FLOOR 0.30 1.887 3.839 17.84 17.84 270.00 180.00  
C39FCC INT_SLAB_CEILING 0.30 1.887 3.839 91.42 91.42 180.00 0.00  
CA9485 INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
2740BD INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
F0AF69 INT_WALL 0.30 2.511 6.299 16.72 16.72 0.00 90.00 N
9CE650 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
EEECA3 INT_WALL 0.30 2.511 6.299 16.72 16.72 180.00 90.00 S
EE34A3 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
CFAD9D INT_WALL 0.30 2.511 6.299 22.30 22.30 180.00 90.00 S
25F524 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
D79C57 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
93F6DE INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
8AA0B7 INT_WALL 0.30 2.511 6.299 46.45 46.45 0.00 90.00 N
1D6CD8 INT_WALL 0.30 2.511 6.299 17.65 17.65 0.00 90.00 N
427B0D INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
A72F04 INT_WALL 0.30 2.511 6.299 11.15 11.15 180.00 90.00 S
C51FD6 INT_SLAB_FLOOR 0.30 1.887 3.839 3.90 3.90 270.00 180.00  
3110A1 INT_SLAB_FLOOR 0.30 1.887 3.839 4.46 4.46 270.00 180.00  
F81393 INT_SLAB_FLOOR 0.30 1.887 3.839 7.25 7.25 0.00 180.00  
4FA380 INT_SLAB_FLOOR 0.30 1.887 3.839 3.90 3.90 270.00 180.00  
2FE383 INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 270.00 180.00  
3F961C INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 270.00 180.00  
4B590B INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 270.00 180.00  
20B940 INT_SLAB_FLOOR 0.30 1.887 3.839 4.46 4.46 90.00 180.00  
21FC9D INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 90.00 180.00  
EB4979 INT_SLAB_FLOOR 0.30 1.887 3.839 2.79 2.79 270.00 180.00  
A5FA3B INT_SLAB_FLOOR 0.30 1.887 3.839 5.57 5.57 90.00 180.00  
7A3F36 INT_SLAB_CEILING 0.30 1.887 3.839 3.90 3.90 90.00 0.00  
4DAEA4 INT_SLAB_CEILING 0.30 1.887 3.839 23.41 23.41 180.00 0.00  
B52A5D INT_SLAB_CEILING 0.30 1.887 3.839 17.28 17.28 0.00 0.00  
2C7827 INT_SLAB_CEILING 0.30 1.887 3.839 7.80 7.80 180.00 0.00  
2D0A7F INT_WALL 0.30 2.511 6.299 16.72 16.72 90.00 90.00 E
E63515 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
B04C98 INT_WALL 0.30 2.511 6.299 16.72 16.72 270.00 90.00 W
50DB3D INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
115AA8 INT_SLAB_FLOOR 0.30 1.887 3.839 4.55 4.55 0.00 180.00  
CFB630 INT_SLAB_FLOOR 0.30 1.887 3.839 7.15 7.15 180.00 180.00  
E9C76F INT_SLAB_CEILING 0.30 1.887 3.839 11.71 11.71 180.00 0.00  
9C568B INT_WALL 0.30 2.511 6.299 16.72 16.72 0.00 90.00 N
B76374 INT_WALL 0.30 2.511 6.299 16.72 16.72 180.00 90.00 S
24DA9F INT_WALL 0.30 2.511 6.299 16.72 16.72 90.00 90.00 E
CADDAF INT_WALL 0.30 2.511 6.299 16.72 16.72 270.00 90.00 W
10830D INT_SLAB_FLOOR 0.30 1.887 3.839 13.38 13.38 90.00 180.00  
EF47B0 INT_SLAB_FLOOR 0.30 1.887 3.839 6.50 6.50 180.00 180.00  
C3DB37 INT_SLAB_FLOOR 0.30 1.887 3.839 10.22 10.22 0.00 180.00  
F631E4 INT_SLAB_CEILING 0.30 1.887 3.839 10.03 10.03 0.00 0.00  
93EF1F INT_SLAB_CEILING 0.30 1.887 3.839 20.07 20.07 180.00 0.00  
9FBDA3 INT_WALL 0.30 2.511 6.299 17.65 17.65 180.00 90.00 S
87BFF8 INT_WALL 0.30 2.511 6.299 16.72 16.72 270.00 90.00 W
DB7F62 INT_WALL 0.30 2.511 6.299 16.72 16.72 90.00 90.00 E
969F22 INT_WALL 0.30 2.511 6.299 17.65 17.65 0.00 90.00 N
795751 INT_SLAB_FLOOR 0.30 1.887 3.839 3.34 3.34 90.00 180.00  
6A14D8 INT_SLAB_FLOOR 0.30 1.887 3.839 9.20 9.20 180.00 180.00  
E3963E INT_SLAB_FLOOR 0.30 1.887 3.839 5.85 5.85 270.00 180.00  
630683 INT_SLAB_FLOOR 0.30 1.887 3.839 13.38 13.38 270.00 180.00  
4EB51A INT_SLAB_CEILING 0.30 1.887 3.839 31.77 31.77 90.00 0.00  
390BCF INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
DE64CC INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
F6E717 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
58AD84 INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
A3E3D6 INT_SLAB_FLOOR 0.30 1.887 3.839 5.20 5.20 270.00 180.00  
ED1C1D INT_SLAB_CEILING 0.30 1.887 3.839 5.20 5.20 270.00 0.00  
A168ED INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
ED650B INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
8E1DCD INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
16E41D INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
1C7FB1 INT_SLAB_FLOOR 0.30 1.887 3.839 0.74 0.74 0.00 180.00  
4B217A INT_SLAB_FLOOR 0.30 1.887 3.839 5.20 5.20 90.00 180.00  
A3F683 INT_SLAB_FLOOR 0.30 1.887 3.839 5.20 5.20 0.00 180.00  
430C7E INT_SLAB_CEILING 0.30 1.887 3.839 11.15 11.15 270.00 0.00  
70C0BF INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
211EA4 INT_WALL 0.30 2.511 6.299 16.72 16.72 180.00 90.00 S
E0D6E9 INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
BADB96 INT_WALL 0.30 2.511 6.299 16.72 16.72 0.00 90.00 N
1E3410 INT_SLAB_FLOOR 0.30 1.887 3.839 13.38 13.38 90.00 180.00  
695D6E INT_SLAB_CEILING 0.30 1.887 3.839 13.38 13.38 90.00 0.00  
97B688 INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
290DF3 INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
4F0CD7 INT_WALL 0.30 2.511 6.299 8.36 8.36 270.00 90.00 W
4D50C0 INT_SLAB_FLOOR 0.30 1.887 3.839 11.71 11.71 270.00 180.00  
703D3E INT_SLAB_CEILING 0.30 1.887 3.839 11.71 11.71 270.00 0.00  
5C7E1E INT_WALL 0.30 2.511 6.299 30.66 30.66 90.00 90.00 E
B5E37D INT_WALL 0.30 2.511 6.299 1.86 1.86 0.00 90.00 N
8D1659 INT_WALL 0.30 2.511 6.299 18.58 18.58 270.00 90.00 W
E88E01 INT_WALL 0.30 2.511 6.299 48.31 48.31 180.00 90.00 S
4CE123 INT_WALL 0.30 2.511 6.299 6.50 6.50 270.00 90.00 W
E55935 INT_WALL 0.30 2.511 6.299 22.30 22.30 0.00 90.00 N
9AB0BF INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
1A8E2A INT_SLAB_FLOOR 0.30 1.887 3.839 2.60 2.60 270.00 180.00  
E21951 INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 180.00 180.00  
517DFC INT_SLAB_FLOOR 0.30 1.887 3.839 33.26 33.26 270.00 180.00  
CEC6B4 INT_SLAB_FLOOR 0.30 1.887 3.839 15.61 15.61 0.00 180.00  
1A95D5 INT_SLAB_FLOOR 0.30 1.887 3.839 13.66 13.66 270.00 180.00  
5724CC INT_SLAB_FLOOR 0.30 1.887 3.839 5.57 5.57 180.00 180.00  
7FA5FF INT_SLAB_FLOOR 0.30 1.887 3.839 13.38 13.38 270.00 180.00  
E43750 INT_SLAB_FLOOR 0.30 1.887 3.839 40.88 40.88 0.00 180.00  
E9C9E1 INT_SLAB_FLOOR 0.30 1.887 3.839 2.79 2.79 0.00 180.00  
CE626A INT_SLAB_FLOOR 0.30 1.887 3.839 20.07 20.07 270.00 180.00  
541C9C INT_SLAB_FLOOR 0.30 1.887 3.839 4.18 4.18 270.00 180.00  
F77E4B INT_SLAB_CEILING 0.30 1.887 3.839 34.37 34.37 90.00 0.00  
287E3B INT_SLAB_CEILING 0.30 1.887 3.839 122.63 122.63 270.00 0.00  
830326 INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
EAD1EA INT_WALL 0.30 2.511 6.299 41.81 41.81 180.00 90.00 S
52D809 INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
450AA9 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
29E445 INT_WALL 0.30 2.511 6.299 17.65 17.65 180.00 90.00 S
B0FF3A INT_WALL 0.30 2.511 6.299 46.45 46.45 180.00 90.00 S
9036B9 INT_WALL 0.30 2.511 6.299 16.72 16.72 180.00 90.00 S
5EE606 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
3FBBC8 INT_WALL 0.30 2.511 6.299 22.30 22.30 0.00 90.00 N
B5099E INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
7A8E3F INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
32BAA7 INT_WALL 0.30 2.511 6.299 11.15 11.15 0.00 90.00 N
738F37 INT_WALL 0.30 2.511 6.299 48.31 48.31 0.00 90.00 N
B94E9A INT_WALL 0.30 2.511 6.299 16.72 16.72 0.00 90.00 N
83658D INT_SLAB_FLOOR 0.30 1.887 3.839 4.92 4.92 270.00 180.00  
CAC621 INT_SLAB_FLOOR 0.30 1.887 3.839 6.69 6.69 270.00 180.00  
E90253 INT_SLAB_FLOOR 0.30 1.887 3.839 11.15 11.15 270.00 180.00  
FD4C82 INT_SLAB_FLOOR 0.30 1.887 3.839 1.21 1.21 180.00 180.00  
F5C927 INT_SLAB_FLOOR 0.30 1.887 3.839 9.75 9.75 0.00 180.00  
362FF8 INT_SLAB_FLOOR 0.30 1.887 3.839 4.46 4.46 270.00 180.00  
21F419 INT_SLAB_FLOOR 0.30 1.887 3.839 0.65 0.65 180.00 180.00  
283EC6 INT_SLAB_FLOOR 0.30 1.887 3.839 4.46 4.46 180.00 180.00  
C5B569 INT_SLAB_FLOOR 0.30 1.887 3.839 0.84 0.84 180.00 180.00  
D29B01 INT_SLAB_FLOOR 0.30 1.887 3.839 3.07 3.07 180.00 180.00  
FFE9D0 INT_SLAB_FLOOR 0.30 1.887 3.839 28.80 28.80 270.00 180.00  
7A8C4C INT_SLAB_FLOOR 0.30 1.887 3.839 1.49 1.49 180.00 180.00  
957242 INT_SLAB_CEILING 0.30 1.887 3.839 77.48 77.48 0.00 0.00  
F22E15 INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
49DA28 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
8C4550 INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
9969B3 INT_WALL 0.30 2.511 6.299 1.86 1.86 180.00 90.00 S
4C4C25 INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 180.00 180.00  
FC3B6D INT_SLAB_CEILING 0.30 1.887 3.839 5.02 5.02 90.00 0.00  
34B8D8 INT_WALL 0.30 2.511 6.299 46.45 46.45 0.00 90.00 N
E74038 INT_WALL 0.30 2.511 6.299 46.45 46.45 180.00 90.00 S
762874 INT_WALL 0.30 2.511 6.299 16.72 16.72 90.00 90.00 E
637F6F INT_WALL 0.30 2.511 6.299 16.72 16.72 270.00 90.00 W
C6DCD1 INT_SLAB_FLOOR 0.30 1.887 3.839 11.71 11.71 270.00 180.00  
1BDF58 INT_SLAB_FLOOR 0.30 1.887 3.839 18.39 18.39 270.00 180.00  
15A915 INT_SLAB_FLOOR 0.30 1.887 3.839 5.85 5.85 180.00 180.00  
1CC550 INT_SLAB_FLOOR 0.30 1.887 3.839 5.85 5.85 180.00 180.00  
55622A INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 180.00 180.00  
5D03DA INT_SLAB_FLOOR 0.30 1.887 3.839 5.85 5.85 180.00 180.00  
AE5078 INT_SLAB_FLOOR 0.30 1.887 3.839 4.18 4.18 270.00 180.00  
774CCD INT_SLAB_FLOOR 0.30 1.887 3.839 3.25 3.25 180.00 180.00  
F6FE66 INT_SLAB_FLOOR 0.30 1.887 3.839 23.50 23.50 0.00 180.00  
1DCC9F INT_SLAB_CEILING 0.30 1.887 3.839 38.46 38.46 90.00 0.00  
47890C INT_SLAB_CEILING 0.30 1.887 3.839 3.90 3.90 0.00 0.00  
F7E82F INT_SLAB_CEILING 0.30 1.887 3.839 7.80 7.80 180.00 0.00  
7FDC1A INT_SLAB_CEILING 0.30 1.887 3.839 23.41 23.41 90.00 0.00  
F02E9C INT_SLAB_CEILING 0.30 1.887 3.839 10.03 10.03 270.00 0.00  
137A14 INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
F2515C INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
71A3C4 INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
46292D INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
9AC2BE INT_SLAB_FLOOR 0.30 1.887 3.839 3.90 3.90 270.00 180.00  
5EAFB3 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
E0CB0D INT_WALL 0.30 2.511 6.299 18.58 18.58 270.00 90.00 W
FB63A7 INT_WALL 0.30 2.511 6.299 1.86 1.86 0.00 90.00 N
79D0A5 INT_WALL 0.30 2.511 6.299 11.15 11.15 180.00 90.00 S
212961 INT_WALL 0.30 2.511 6.299 30.66 30.66 90.00 90.00 E
C1AD55 INT_WALL 0.30 2.511 6.299 6.50 6.50 270.00 90.00 W
B75832 INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
D6F20A INT_SLAB_FLOOR 0.30 1.887 3.839 34.37 34.37 270.00 180.00  
C3FB92 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
AAD404 INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
2272E0 INT_WALL 0.30 2.511 6.299 16.72 16.72 270.00 90.00 W
E13FC4 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
506DC0 INT_WALL 0.30 2.511 6.299 11.15 11.15 90.00 90.00 E
628387 INT_SLAB_FLOOR 0.30 1.887 3.839 10.03 10.03 270.00 180.00  
1D53D9 INT_WALL 0.30 2.511 6.299 8.36 8.36 180.00 90.00 S
C4A89B INT_WALL 0.30 2.511 6.299 6.50 6.50 90.00 90.00 E
B840A7 INT_SLAB_FLOOR 0.30 1.887 3.839 5.85 5.85 0.00 180.00  
C86932 INT_WALL 0.30 2.511 6.299 9.29 9.29 90.00 90.00 E
B1856A INT_WALL 0.30 2.511 6.299 11.15 11.15 0.00 90.00 N
AEA170 INT_WALL 0.30 2.511 6.299 11.15 11.15 180.00 90.00 S
82303C INT_WALL 0.30 2.511 6.299 9.29 9.29 270.00 90.00 W
D10EC7 INT_SLAB_FLOOR 0.30 1.887 3.839 11.15 11.15 0.00 180.00  
AA26DE INT_WALL 0.30 2.511 6.299 21.37 21.37 180.00 90.00 S
824F52 INT_WALL 0.30 2.511 6.299 24.15 24.15 90.00 90.00 E
D2E9BA INT_WALL 0.30 2.511 6.299 6.50 6.50 90.00 90.00 E
D197DA INT_WALL 0.30 2.511 6.299 6.50 6.50 270.00 90.00 W
7C7BE2 INT_WALL 0.30 2.511 6.299 14.86 14.86 270.00 90.00 W
812B32 INT_WALL 0.30 2.511 6.299 9.29 9.29 270.00 90.00 W
3B5B94 INT_SLAB_FLOOR 0.30 1.887 3.839 13.94 13.94 180.00 180.00  
60F383 INT_SLAB_FLOOR 0.30 1.887 3.839 6.13 6.13 90.00 180.00  
F7BE2F INT_SLAB_FLOOR 0.30 1.887 3.839 20.90 20.90 90.00 180.00  
B29215 INT_SLAB_FLOOR 0.30 1.887 3.839 11.15 11.15 0.00 180.00  
52FA3B INT_SLAB_FLOOR 0.30 1.887 3.839 18.39 18.39 90.00 180.00  
6D960C INT_WALL 0.30 2.511 6.299 14.86 14.86 270.00 90.00 W
9AB92B INT_WALL 0.30 2.511 6.299 11.15 11.15 180.00 90.00 S
E0FD95 INT_WALL 0.30 2.511 6.299 14.86 14.86 90.00 90.00 E
B46F2C INT_SLAB_FLOOR 0.30 1.887 3.839 17.84 17.84 0.00 180.00  
6F0E5D INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
D67C59 INT_WALL 0.30 2.511 6.299 23.23 23.23 270.00 90.00 W
6C68C2 INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
1DC177 INT_SLAB_FLOOR 0.30 1.887 3.839 32.52 32.52 0.00 180.00  
A11DA8 INT_WALL 0.30 2.511 6.299 23.23 23.23 90.00 90.00 E
BC2C22 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
44775D INT_WALL 0.30 2.511 6.299 24.15 24.15 270.00 90.00 W
CDD69A INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
F5E7FE INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
4BF787 INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
98A52C INT_WALL 0.30 2.511 6.299 23.23 23.23 90.00 90.00 E
6310E5 INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
2E74E6 INT_SLAB_FLOOR 0.30 1.887 3.839 27.87 27.87 90.00 180.00  
5FDFAE INT_WALL 0.30 2.511 6.299 85.47 85.47 180.00 90.00 S
C7B7AA INT_WALL 0.30 2.511 6.299 6.50 6.50 90.00 90.00 E
B972D4 INT_WALL 0.30 2.511 6.299 30.66 30.66 270.00 90.00 W
7DCAF1 INT_WALL 0.30 2.511 6.299 16.72 16.72 0.00 90.00 N
CBFB94 INT_WALL 0.30 2.511 6.299 14.86 14.86 90.00 90.00 E
A5FC87 INT_WALL 0.30 2.511 6.299 9.29 9.29 90.00 90.00 E
A72B2F INT_SLAB_FLOOR 0.30 1.887 3.839 30.66 30.66 90.00 180.00  
538FE6 INT_SLAB_FLOOR 0.30 1.887 3.839 18.39 18.39 90.00 180.00  
8A695C INT_SLAB_FLOOR 0.30 1.887 3.839 25.08 25.08 0.00 180.00  
45A523 INT_SLAB_FLOOR 0.30 1.887 3.839 13.38 13.38 0.00 180.00  
F94215 INT_SLAB_FLOOR 0.30 1.887 3.839 18.39 18.39 0.00 180.00  
C27BD7 INT_SLAB_FLOOR 0.30 1.887 3.839 16.72 16.72 90.00 180.00  
AE8664 INT_SLAB_FLOOR 0.30 1.887 3.839 36.79 36.79 90.00 180.00  
535D54 INT_SLAB_FLOOR 0.30 1.887 3.839 122.63 122.63 0.00 180.00  
CC8990 INT_WALL 0.30 2.511 6.299 21.37 21.37 0.00 90.00 N
2F3F2A INT_WALL 0.30 2.511 6.299 48.31 48.31 180.00 90.00 S
869ED5 INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
D75504 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
E80026 INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
A03B2E INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
133349 INT_WALL 0.30 2.511 6.299 16.72 16.72 180.00 90.00 S
7DCD8A INT_WALL 0.30 2.511 6.299 11.15 11.15 0.00 90.00 N
D7E6B2 INT_WALL 0.30 2.511 6.299 85.47 85.47 0.00 90.00 N
8646EF INT_WALL 0.30 2.511 6.299 11.15 11.15 0.00 90.00 N
840387 INT_WALL 0.30 2.511 6.299 39.02 39.02 180.00 90.00 S
14A82B INT_SLAB_FLOOR 0.30 1.887 3.839 77.48 77.48 270.00 180.00  
460DA4 INT_WALL 0.30 2.511 6.299 8.36 8.36 0.00 90.00 N
8316C5 INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
D5E94D INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
D0C6E8 INT_WALL 0.30 2.511 6.299 1.86 1.86 180.00 90.00 S
F07866 INT_SLAB_FLOOR 0.30 1.887 3.839 5.02 5.02 270.00 180.00  
4497EF INT_WALL 0.30 2.511 6.299 18.58 18.58 270.00 90.00 W
F3F6EA INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
BCAAD1 INT_WALL 0.30 2.511 6.299 34.37 34.37 0.00 90.00 N
E5720F INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
8E83C6 INT_SLAB_FLOOR 0.30 1.887 3.839 10.41 10.41 90.00 180.00  
D14D65 INT_SLAB_FLOOR 0.30 1.887 3.839 31.22 31.22 90.00 180.00  
CDCA72 INT_SLAB_FLOOR 0.30 1.887 3.839 5.95 5.95 90.00 180.00  
339B46 INT_SLAB_FLOOR 0.30 1.887 3.839 4.46 4.46 90.00 180.00  
7F8407 INT_SLAB_FLOOR 0.30 1.887 3.839 44.59 44.59 270.00 180.00  
F69079 INT_SLAB_FLOOR 0.30 1.887 3.839 7.80 7.80 90.00 180.00  
A56694 INT_SLAB_FLOOR 0.30 1.887 3.839 5.20 5.20 90.00 180.00  
3C8351 INT_SLAB_FLOOR 0.30 1.887 3.839 11.15 11.15 90.00 180.00  
958E3F INT_WALL 0.30 2.511 6.299 34.37 34.37 180.00 90.00 S
27D999 INT_WALL 0.30 2.511 6.299 14.86 14.86 270.00 90.00 W
55BD05 INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
8BCB23 INT_WALL 0.30 2.511 6.299 14.86 14.86 90.00 90.00 E
5C690E INT_WALL 0.30 2.511 6.299 5.57 5.57 0.00 90.00 N
E49C43 INT_WALL 0.30 2.511 6.299 16.72 16.72 0.00 90.00 N
EF4AD1 INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
8FB568 INT_SLAB_FLOOR 0.30 1.887 3.839 9.29 9.29 180.00 180.00  
C271D9 INT_SLAB_FLOOR 0.30 1.887 3.839 5.57 5.57 180.00 180.00  
1EE332 INT_SLAB_FLOOR 0.30 1.887 3.839 6.50 6.50 180.00 180.00  
96623F INT_SLAB_FLOOR 0.30 1.887 3.839 7.43 7.43 180.00 180.00  
F17575 INT_SLAB_FLOOR 0.30 1.887 3.839 8.92 8.92 180.00 180.00  
317B1B INT_SLAB_FLOOR 0.30 1.887 3.839 17.28 17.28 0.00 180.00  
44D36C INT_WALL 0.30 2.511 6.299 11.15 11.15 90.00 90.00 E
CD21EC INT_WALL 0.30 2.511 6.299 6.50 6.50 180.00 90.00 S
BF7411 INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
EA4A9E INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
484FB1 INT_SLAB_FLOOR 0.30 1.887 3.839 7.80 7.80 90.00 180.00  
D4C22E INT_WALL 0.30 2.511 6.299 16.72 16.72 180.00 90.00 S
6EC372 INT_WALL 0.30 2.511 6.299 5.57 5.57 90.00 90.00 E
301CE0 INT_WALL 0.30 2.511 6.299 5.57 5.57 270.00 90.00 W
89A685 INT_WALL 0.30 2.511 6.299 16.72 16.72 0.00 90.00 N
137CDB INT_SLAB_FLOOR 0.30 1.887 3.839 10.03 10.03 180.00 180.00  
FE5F03 INT_WALL 0.30 2.511 6.299 6.50 6.50 270.00 90.00 W
1F37D7 INT_WALL 0.30 2.511 6.299 11.15 11.15 0.00 90.00 N
AC05CF INT_WALL 0.30 2.511 6.299 6.50 6.50 90.00 90.00 E
C9F74B INT_WALL 0.30 2.511 6.299 11.15 11.15 180.00 90.00 S
63B825 INT_SLAB_FLOOR 0.30 1.887 3.839 7.80 7.80 180.00 180.00  
C78153 INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
D13E00 INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
2451B7 INT_WALL 0.30 2.511 6.299 14.86 14.86 90.00 90.00 E
624E8A INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
D6005B INT_WALL 0.30 2.511 6.299 16.72 16.72 90.00 90.00 E
2B4713 INT_SLAB_FLOOR 0.30 1.887 3.839 13.01 13.01 180.00 180.00  
25A972 INT_SLAB_FLOOR 0.30 1.887 3.839 23.41 23.41 0.00 180.00  
496A6C INT_SLAB_FLOOR 0.30 1.887 3.839 7.80 7.80 270.00 180.00  
C050FD INT_WALL 0.30 2.511 6.299 18.58 18.58 90.00 90.00 E
F8F69A INT_WALL 0.30 2.511 6.299 22.30 22.30 270.00 90.00 W
4CCA8D INT_WALL 0.30 2.511 6.299 39.02 39.02 0.00 90.00 N
2336C8 INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
F4E5F5 INT_SLAB_FLOOR 0.30 1.887 3.839 33.45 33.45 180.00 180.00  
AA7BE2 INT_SLAB_FLOOR 0.30 1.887 3.839 16.72 16.72 180.00 180.00  
68EB71 INT_SLAB_FLOOR 0.30 1.887 3.839 50.17 50.17 180.00 180.00  
66FE82 INT_SLAB_FLOOR 0.30 1.887 3.839 31.77 31.77 270.00 180.00  
948D7B INT_SLAB_FLOOR 0.30 1.887 3.839 16.72 16.72 180.00 180.00  
236CCE INT_SLAB_FLOOR 0.30 1.887 3.839 23.41 23.41 0.00 180.00  
AE769E INT_SLAB_FLOOR 0.30 1.887 3.839 38.46 38.46 90.00 180.00  
D5C4E5 INT_WALL 0.30 2.511 6.299 11.15 11.15 180.00 90.00 S
C1B522 INT_WALL 0.30 2.511 6.299 7.43 7.43 270.00 90.00 W
192E17 INT_WALL 0.30 2.511 6.299 22.30 22.30 90.00 90.00 E
855B07 INT_WALL 0.30 2.511 6.299 48.31 48.31 0.00 90.00 N
9D1FA7 INT_SLAB_FLOOR 0.30 1.887 3.839 91.42 91.42 270.00 180.00  
6F1456 INT_SLAB_FLOOR 0.30 1.887 3.839 3.90 3.90 180.00 180.00  
CDCFEE INT_SLAB_FLOOR 0.30 1.887 3.839 11.71 11.71 0.00 180.00  
111907 INT_WALL 0.30 2.511 6.299 16.72 16.72 0.00 90.00 N
CF2803 INT_WALL 0.30 2.511 6.299 11.15 11.15 90.00 90.00 E
180143 INT_WALL 0.30 2.511 6.299 16.72 16.72 180.00 90.00 S
2BC70D INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
DF5076 INT_SLAB_FLOOR 0.30 1.887 3.839 20.07 20.07 0.00 180.00  
3613B7 INT_WALL 0.30 2.511 6.299 13.01 13.01 0.00 90.00 N
E7A265 INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
4C6DBF INT_WALL 0.30 2.511 6.299 23.23 23.23 270.00 90.00 W
EFFB3B INT_WALL 0.30 2.511 6.299 14.86 14.86 270.00 90.00 W
8480E5 INT_SLAB_FLOOR 0.30 1.887 3.839 41.62 41.62 180.00 180.00  
F6DDE6 INT_SLAB_FLOOR 0.30 1.887 3.839 11.71 11.71 0.00 180.00  
986A05 INT_WALL 0.30 2.511 6.299 6.50 6.50 270.00 90.00 W
6EE166 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
A28F01 INT_WALL 0.30 2.511 6.299 18.58 18.58 180.00 90.00 S
DE6295 INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
D68874 INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
16BE00 INT_WALL 0.30 2.511 6.299 6.50 6.50 270.00 90.00 W
60F634 INT_WALL 0.30 2.511 6.299 13.01 13.01 180.00 90.00 S
EEFDE3 INT_WALL 0.30 2.511 6.299 6.50 6.50 270.00 90.00 W
976E3F INT_WALL 0.30 2.511 6.299 18.58 18.58 90.00 90.00 E
D699FF INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
F9DFA4 INT_WALL 0.30 2.511 6.299 18.58 18.58 90.00 90.00 E
BDE9D9 INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
BEDECA INT_WALL 0.30 2.511 6.299 18.58 18.58 90.00 90.00 E
9BA592 INT_WALL 0.30 2.511 6.299 6.50 6.50 0.00 90.00 N
FA9233 INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
74AB49 INT_WALL 0.30 2.511 6.299 14.86 14.86 180.00 90.00 S
DF47AC INT_WALL 0.30 2.511 6.299 5.57 5.57 180.00 90.00 S
F41621 INT_WALL 0.30 2.511 6.299 22.30 22.30 180.00 90.00 S
7C0F83 INT_WALL 0.30 2.511 6.299 16.72 16.72 180.00 90.00 S
8FF821 INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
1068C8 INT_WALL 0.30 2.511 6.299 11.15 11.15 0.00 90.00 N
E2AFEB INT_WALL 0.30 2.511 6.299 11.15 11.15 0.00 90.00 N
99468F INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
17258E INT_WALL 0.30 2.511 6.299 11.15 11.15 0.00 90.00 N
573330 INT_WALL 0.30 2.511 6.299 7.43 7.43 90.00 90.00 E
FLOOR 1 ANESTHESIA_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 20.07   0.00 90.00 N
FLOOR 1 BIO HAZ_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 10.41   0.00 90.00 N
FLOOR 1 CAFE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
FLOOR 1 CLEAN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 23.41   0.00 90.00 N
FLOOR 1 CLEAN WORK_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 30.66   0.00 90.00 N
FLOOR 1 DICTATION_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 23.41   0.00 90.00 N
FLOOR 1 DRESSING ROOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 8.36   0.00 90.00 N
FLOOR 1 ELECTRICAL ROOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 18.21   0.00 90.00 N
FLOOR 1 ELEVATOR PUMP ROOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 16.91   0.00 90.00 N
FLOOR 1 HUMID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 10.03   0.00 90.00 N
FLOOR 1 IT HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 26.01   0.00 90.00 N
FLOOR 1 IT ROOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 20.81   0.00 90.00 N
FLOOR 1 LOBBY_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 115.57   0.00 90.00 N
FLOOR 1 LOBBY HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 44.59   0.00 90.00 N
FLOOR 1 LOBBY TOILET_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 10.03   0.00 90.00 N
FLOOR 1 LOCKER ROOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 122.63   0.00 90.00 N
FLOOR 1 LOCKER ROOM HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 92.16   0.00 90.00 N
FLOOR 1 LOUNGE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 66.89   0.00 90.00 N
FLOOR 1 MED GAS_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 10.41   0.00 90.00 N
FLOOR 1 MRI CONTROL ROOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 31.22   0.00 90.00 N
FLOOR 1 MRI HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 27.31   0.00 90.00 N
FLOOR 1 MRI ROOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 81.75   0.00 90.00 N
FLOOR 1 MRI TOILET_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 10.03   0.00 90.00 N
FLOOR 1 NOURISHMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 33.82   0.00 90.00 N
FLOOR 1 NURSE HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 92.16   0.00 90.00 N
FLOOR 1 NURSE JANITOR_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 10.03   0.00 90.00 N
FLOOR 1 NURSE STATION_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 48.50   0.00 90.00 N
FLOOR 1 NURSE TOILET_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 10.03   0.00 90.00 N
FLOOR 1 OFFICE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 89.74   0.00 90.00 N
FLOOR 1 OPERATING ROOM 1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 85.47   0.00 90.00 N
FLOOR 1 OPERATING ROOM 2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 89.19   0.00 90.00 N
FLOOR 1 OPERATING ROOM 3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 88.44   0.00 90.00 N
FLOOR 1 PACU_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 20.07   0.00 90.00 N
FLOOR 1 PRE-OP HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 98.11   0.00 90.00 N
FLOOR 1 PRE-OP ROOM 1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 35.12   0.00 90.00 N
FLOOR 1 PRE-OP ROOM 2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 62.80   0.00 90.00 N
FLOOR 1 PRE-OP TOILET_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 10.03   0.00 90.00 N
FLOOR 1 PROCEDURE ROOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 52.95   0.00 90.00 N
FLOOR 1 RECEPTION_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 94.58   0.00 90.00 N
FLOOR 1 RECEPTION HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 23.78   0.00 90.00 N
FLOOR 1 RECOVERY ROOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 100.34   0.00 90.00 N
FLOOR 1 SCHEDULING_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 22.11   0.00 90.00 N
FLOOR 1 SCRUB_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 15.61   0.00 90.00 N
FLOOR 1 SOIL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 23.41   0.00 90.00 N
FLOOR 1 SOIL HOLD_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 10.41   0.00 90.00 N
FLOOR 1 SOIL WORK_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 33.45   0.00 90.00 N
FLOOR 1 STEP DOWN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 55.74   0.00 90.00 N
FLOOR 1 STERILE HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 114.46   0.00 90.00 N
FLOOR 1 STERILE STORAGE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 73.58   0.00 90.00 N
FLOOR 1 STORAGE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 170.94   0.00 90.00 N
FLOOR 1 SUB-STERILE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 36.42   0.00 90.00 N
FLOOR 1 UTILITY HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 47.57   0.00 90.00 N
FLOOR 1 UTILITY JANITOR_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7.80   0.00 90.00 N
FLOOR 1 UTILITY ROOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 66.89   0.00 90.00 N
FLOOR 1 VESTIBULE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 13.38   0.00 90.00 N
FLOOR 2 CONFERENCE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 62.43   0.00 90.00 N
FLOOR 2 CONFERENCE TOILET_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 11.89   0.00 90.00 N
FLOOR 2 DICTATION_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 13.01   0.00 90.00 N
FLOOR 2 EXAM 1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 66.89   0.00 90.00 N
FLOOR 2 EXAM 2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 100.34   0.00 90.00 N
FLOOR 2 EXAM 3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 133.78   0.00 90.00 N
FLOOR 2 EXAM 4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 15.61   0.00 90.00 N
FLOOR 2 EXAM 5_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 65.03   0.00 90.00 N
FLOOR 2 EXAM 6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 41.81   0.00 90.00 N
FLOOR 2 EXAM 7_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 147.16   0.00 90.00 N
FLOOR 2 EXAM 8_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50.17   0.00 90.00 N
FLOOR 2 EXAM 9_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 73.58   0.00 90.00 N
FLOOR 2 EXAM HALL 1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 33.45   0.00 90.00 N
FLOOR 2 EXAM HALL 2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 33.45   0.00 90.00 N
FLOOR 2 EXAM HALL 3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 33.45   0.00 90.00 N
FLOOR 2 EXAM HALL 4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 36.79   0.00 90.00 N
FLOOR 2 EXAM HALL 5_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 36.79   0.00 90.00 N
FLOOR 2 EXAM HALL 6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 36.79   0.00 90.00 N
FLOOR 2 JANITOR_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 11.71   0.00 90.00 N
FLOOR 2 LOUNGE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 14.86   0.00 90.00 N
FLOOR 2 NURSE STATION 1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 27.87   0.00 90.00 N
FLOOR 2 NURSE STATION 2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 33.45   0.00 90.00 N
FLOOR 2 OFFICE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 104.05   0.00 90.00 N
FLOOR 2 OFFICE HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 82.50   0.00 90.00 N
FLOOR 2 RECEPTION_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 182.83   0.00 90.00 N
FLOOR 2 RECEPTION HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 104.79   0.00 90.00 N
FLOOR 2 RECEPTION TOILET_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 23.41   0.00 90.00 N
FLOOR 2 SCHEDULING 1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 60.20   0.00 90.00 N
FLOOR 2 SCHEDULING 2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 63.55   0.00 90.00 N
FLOOR 2 STORAGE 1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 10.41   0.00 90.00 N
FLOOR 2 STORAGE 2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 22.30   0.00 90.00 N
FLOOR 2 STORAGE 3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 26.76   0.00 90.00 N
FLOOR 2 UTILITY_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 23.41   0.00 90.00 N
FLOOR 2 WORK_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 259.39   0.00 90.00 N
FLOOR 2 WORK HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 154.96   0.00 90.00 N
FLOOR 2 WORK TOILET_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 10.03   0.00 90.00 N
FLOOR 2 X-RAY_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 167.23   0.00 90.00 N
FLOOR 3 DRESSING ROOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7.80   0.00 90.00 N
FLOOR 3 ELEVATOR HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 68.75   0.00 90.00 N
FLOOR 3 HUMID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 20.07   0.00 90.00 N
FLOOR 3 JANITOR_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 11.71   0.00 90.00 N
FLOOR 3 LOCKER_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 22.30   0.00 90.00 N
FLOOR 3 LOUNGE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 141.03   0.00 90.00 N
FLOOR 3 LOUNGE TOILET_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 35.67   0.00 90.00 N
FLOOR 3 MECHANICAL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 65.03   0.00 90.00 N
FLOOR 3 MECHANICAL HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 55.74   0.00 90.00 N
FLOOR 3 OFFICE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 564.11   0.00 90.00 N
FLOOR 3 OFFICE HALL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 154.96   0.00 90.00 N
FLOOR 3 OFFICE TOILET_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 10.03   0.00 90.00 N
FLOOR 3 PHYSICAL THERAPY 1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 241.55   0.00 90.00 N
FLOOR 3 PHYSICAL THERAPY 2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 110.00   0.00 90.00 N
FLOOR 3 PHYSICAL THERAPY TOILET_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 15.61   0.00 90.00 N
FLOOR 3 STORAGE 1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 20.07   0.00 90.00 N
FLOOR 3 STORAGE 2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 15.61   0.00 90.00 N
FLOOR 3 TREATMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 88.44   0.00 90.00 N
FLOOR 3 UNDEVELOPED 1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 421.41   0.00 90.00 N
FLOOR 3 UNDEVELOPED 2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 214.05   0.00 90.00 N
FLOOR 3 UTILITY_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 40.13   0.00 90.00 N
FLOOR 3 WORK_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 106.65   0.00 90.00 N
NE STAIR_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 31.22   0.00 90.00 N
NW ELEVATOR_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 26.01   0.00 90.00 N
NW STAIR_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 35.67   0.00 90.00 N
SW STAIR_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 17.84   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
78F987 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 481E71 180.00 90.00 S
D8037E NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   8.92 0.00 0.00 8.92 8.92 6.926 0.251 0.277             No 5F762C 180.00 90.00 S
4A8120 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.32 0.00 0.00 2.32 2.32 6.926 0.251 0.277             No 84FB73 0.00 90.00 N
AAE778 NONRESWINDOW_U_1.22_SHGC_WEST_0.25   8.92 0.00 0.00 8.92 8.92 6.926 0.251 0.277             No FE5A3C 270.00 90.00 W
3AAD8B NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No F629C1 0.00 90.00 N
8128A9 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No F629C1 0.00 90.00 N
9B1541 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 879583 180.00 90.00 S
CF850A NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 879583 180.00 90.00 S
A6BA23 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No E326E4 90.00 90.00 E
D10D28 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No E326E4 90.00 90.00 E
591336 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No 1D96D7 90.00 90.00 E
38B811 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No 1D96D7 90.00 90.00 E
C044D6 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No 1D96D7 90.00 90.00 E
1D94BE NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 6D2616 0.00 90.00 N
18748E NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 6D2616 0.00 90.00 N
137A56 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   3.34 0.00 0.00 3.34 3.34 6.926 0.251 0.277             No A5A6A3 180.00 90.00 S
8D508E NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 28B002 180.00 90.00 S
B2D381 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 28B002 180.00 90.00 S
1DA13A NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 28B002 180.00 90.00 S
44E54A NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 28B002 180.00 90.00 S
757D10 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   0.74 0.00 0.00 0.74 0.74 6.926 0.251 0.277             No EA6DC8 180.00 90.00 S
E33BAE NONRESWINDOW_U_1.22_SHGC_WEST_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No B40F89 270.00 90.00 W
24167A NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 997723 180.00 90.00 S
2C0938 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 997723 180.00 90.00 S
8600DD NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No CEC7BD 180.00 90.00 S
A1ED60 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 859BC1 0.00 90.00 N
E8D997 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 859BC1 0.00 90.00 N
88E1FC NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 859BC1 0.00 90.00 N
F83F33 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   3.97 0.00 0.00 3.97 3.97 6.926 0.251 0.277             No 61E610 90.00 90.00 E
B1F5EE NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No D95F04 90.00 90.00 E
F52F3D NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No 208CCF 90.00 90.00 E
80885D NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   6.69 0.00 0.00 6.69 6.69 6.926 0.251 0.277             No AEF992 180.00 90.00 S
FEEF06 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 54D065 180.00 90.00 S
2BE8DE NONRESWINDOW_U_1.22_SHGC_WEST_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 1775A6 270.00 90.00 W
513E2A NONRESWINDOW_U_1.22_SHGC_WEST_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 1775A6 270.00 90.00 W
BA5CD9 NONRESWINDOW_U_1.22_SHGC_WEST_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 1775A6 270.00 90.00 W
1AD478 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   3.72 0.00 0.00 3.72 3.72 6.926 0.251 0.277             No 97F00A 180.00 90.00 S
27F0AC NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   5.95 0.00 0.00 5.95 5.95 6.926 0.251 0.277             No A497E9 180.00 90.00 S
724114 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   2.23 0.00 0.00 2.23 2.23 6.926 0.251 0.277             No 88A75F 180.00 90.00 S
D538C4 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   3.97 0.00 0.00 3.97 3.97 6.926 0.251 0.277             No B4E619 90.00 90.00 E
5635BC NONRESWINDOW_U_1.22_SHGC_EAST_0.25   3.97 0.00 0.00 3.97 3.97 6.926 0.251 0.277             No B4E619 90.00 90.00 E
831C1D NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   4.18 0.00 0.00 4.18 4.18 6.926 0.251 0.277             No 9EC269 0.00 90.00 N
9BB95F NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No B316F7 0.00 90.00 N
C0778D NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No B316F7 0.00 90.00 N
7D2D69 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 9621FD 0.00 90.00 N
2EF63B NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 9621FD 0.00 90.00 N
C417C0 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 42CEE1 0.00 90.00 N
EB042B NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No 4B1439 90.00 90.00 E
4C1F71 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No 4B1439 90.00 90.00 E
D23C8B NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No 4B1439 90.00 90.00 E
B4E4BE NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No 4B1439 90.00 90.00 E
EEF55D NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   6.69 0.00 0.00 6.69 6.69 6.926 0.251 0.277             No 4ABC66 180.00 90.00 S
E55A57 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   3.34 0.00 0.00 3.34 3.34 6.926 0.251 0.277             No 4ABC66 180.00 90.00 S
93D018 NONRESWINDOW_U_1.22_SHGC_WEST_0.25   6.69 0.00 0.00 6.69 6.69 6.926 0.251 0.277             No 5B04CF 270.00 90.00 W
DD9F5D NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No 4B55FA 90.00 90.00 E
15B02B NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 9C3A6A 0.00 90.00 N
820282 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 9C3A6A 0.00 90.00 N
9BA05A NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 68A2D7 0.00 90.00 N
C639E8 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 68A2D7 0.00 90.00 N
A2790A NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   4.18 0.00 0.00 4.18 4.18 6.926 0.251 0.277             No CE3FEF 0.00 90.00 N
79FCEE NONRESWINDOW_U_1.22_SHGC_EAST_0.25   3.97 0.00 0.00 3.97 3.97 6.926 0.251 0.277             No CE618F 90.00 90.00 E
EDE617 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   3.97 0.00 0.00 3.97 3.97 6.926 0.251 0.277             No CE618F 90.00 90.00 E
C61F0D NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 5ADC59 0.00 90.00 N
7248C5 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 5ADC59 0.00 90.00 N
29FA28 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 5ADC59 0.00 90.00 N
F0B23F NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 5ADC59 0.00 90.00 N
EEC10E NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 5ADC59 0.00 90.00 N
944FCE NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 5ADC59 0.00 90.00 N
C41399 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 6.926 0.251 0.277             No 5ADC59 0.00 90.00 N
95BA33 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   3.72 0.00 0.00 3.72 3.72 6.926 0.251 0.277             No D22917 90.00 90.00 E
F27282 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   3.72 0.00 0.00 3.72 3.72 6.926 0.251 0.277             No D22917 90.00 90.00 E
3DB407 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   5.57 0.00 0.00 5.57 5.57 6.926 0.251 0.277             No C1BC97 180.00 90.00 S
3DADE2 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   5.57 0.00 0.00 5.57 5.57 6.926 0.251 0.277             No C1BC97 180.00 90.00 S
DF3E2C NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   5.57 0.00 0.00 5.57 5.57 6.926 0.251 0.277             No C1BC97 180.00 90.00 S
5031C8 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   5.57 0.00 0.00 5.57 5.57 6.926 0.251 0.277             No C1BC97 180.00 90.00 S
C087D0 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   5.57 0.00 0.00 5.57 5.57 6.926 0.251 0.277             No 8DA7DB 180.00 90.00 S
D2CA75 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   5.57 0.00 0.00 5.57 5.57 6.926 0.251 0.277             No 8DA7DB 180.00 90.00 S
B0FB49 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   4.46 0.00 0.00 4.46 4.46 6.926 0.251 0.277             No 8DA7DB 180.00 90.00 S
FE9BC9 NONRESWINDOW_U_1.22_SHGC_WEST_0.25   3.34 0.00 0.00 3.34 3.34 6.926 0.251 0.277             No 38B339 270.00 90.00 W
9DF7DE NONRESWINDOW_U_1.22_SHGC_WEST_0.25   3.34 0.00 0.00 3.34 3.34 6.926 0.251 0.277             No 38B339 270.00 90.00 W
D0BE44 NONRESWINDOW_U_1.22_SHGC_WEST_0.25   3.34 0.00 0.00 3.34 3.34 6.926 0.251 0.277             No 38B339 270.00 90.00 W
6B5226 NONRESWINDOW_U_1.22_SHGC_WEST_0.25   4.46 0.00 0.00 4.46 4.46 6.926 0.251 0.277             No BE5F2F 270.00 90.00 W
8F59F7 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   4.46 0.00 0.00 4.46 4.46 6.926 0.251 0.277             No 1DEE26 180.00 90.00 S
44F571 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   4.46 0.00 0.00 4.46 4.46 6.926 0.251 0.277             No 1DEE26 180.00 90.00 S
6BD844 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No C86329 90.00 90.00 E
86D536 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No C86329 90.00 90.00 E
BAF71D NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No C86329 90.00 90.00 E
3833A2 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   2.98 0.00 0.00 2.98 2.98 6.926 0.251 0.277             No C86329 90.00 90.00 E
2111A1 NONRESWINDOW_U_1.22_SHGC_EAST_0.25   0.99 0.00 0.00 0.99 0.99 6.926 0.251 0.277             No DFC6F0 90.00 90.00 E
9BC521 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   5.71 0.00 0.00 5.71 5.71 6.926 0.251 0.277             No 88E360 0.00 90.00 N
142781 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   5.57 0.00 0.00 5.57 5.57 6.926 0.251 0.277             No 88E360 0.00 90.00 N
E74902 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   5.57 0.00 0.00 5.57 5.57 6.926 0.251 0.277             No 2E2D0C 0.00 90.00 N
93BBC3 NONRESWINDOW_U_1.22_SHGC_NORTH_0.25   5.57 0.00 0.00 5.57 5.57 6.926 0.251 0.277             No 2E2D0C 0.00 90.00 N
C635A6 NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25   1.11 0.00 0.00 1.11 1.11 6.926 0.251 0.277             No 850EA7 180.00 90.00 S
Total or Average             326.23 6.926 0.251 0.277                      
North Total or Average             97.22 6.926 0.251 0.277                      
Non-North Total or Average             229.01 6.926 0.251 0.277                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
BA05F7 SWINGING DOOR_CON 3.975 9.815 1.95 E02487
F67E1F SWINGING DOOR_CON 3.975 9.815 1.95 FE5A3C
7EB6E7 SWINGING DOOR_CON 3.975 9.815 1.95 E85BB5
D18914 SWINGING DOOR_CON 3.975 9.815 1.95 C114C1
D4B39B SWINGING DOOR_CON 3.975 9.815 1.95 E326E4
D2D3BC SWINGING DOOR_CON 3.975 9.815 1.95 28B002
C528DA SWINGING DOOR_CON 3.975 9.815 1.95 28B002
EFD3F9 SWINGING DOOR_CON 3.975 9.815 1.95 28B002
62B5AF SWINGING DOOR_CON 3.975 9.815 1.95 997723
71E924 SWINGING DOOR_CON 3.975 9.815 2.97 8E5BB9
3C44F9 SWINGING DOOR_CON 3.975 9.815 1.95 859BC1
49526E SWINGING DOOR_CON 3.975 9.815 1.95 859BC1
865AE8 SWINGING DOOR_CON 3.975 9.815 1.95 859BC1
5E66D1 OVERHEAD DOOR_CON 6.464 200.000 7.43 529072
E14DAE SWINGING DOOR_CON 3.975 9.815 1.95 D95F04
84A1D5 SWINGING DOOR_CON 3.975 9.815 1.95 3330D8
9CB8E5 SWINGING DOOR_CON 3.975 9.815 1.95 88E360
E4A528 SWINGING DOOR_CON 3.975 9.815 1.95 88E360
24BAF7 SWINGING DOOR_CON 3.975 9.815 1.95 FB3814
19E57D SWINGING DOOR_CON 3.975 9.815 1.95 FCD12D
EDE769 SWINGING DOOR_CON 3.975 9.815 1.95 5507DC
1C9872 SWINGING DOOR_CON 3.975 9.815 1.95 2E2D0C
F402E9 SWINGING DOOR_CON 3.975 9.815 1.95 270BCE


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
78F987 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
D8037E 0.00 1.00 1.00 0.00 1.00 0.00 0.00 1.00 1.00
4A8120 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
AAE778 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
3AAD8B 0.00 0.00 0.00 0.68 0.00 1.00 0.00 0.00 0.00
8128A9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
9B1541 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CF850A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
A6BA23 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
D10D28 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
591336 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
38B811 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
C044D6 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
1D94BE 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
18748E 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
137A56 0.00 1.00 1.00 0.00 1.00 0.00 0.00 1.00 1.00
8D508E 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
B2D381 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
1DA13A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
44E54A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
757D10 0.00 0.00 1.00 0.00 0.24 0.00 0.00 0.00 1.00
E33BAE 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
24167A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
2C0938 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
8600DD 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
A1ED60 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
E8D997 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
88E1FC 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F83F33 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
B1F5EE 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F52F3D 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
80885D 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
FEEF06 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
2BE8DE 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
513E2A 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
BA5CD9 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
1AD478 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
27F0AC 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
724114 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
D538C4 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
5635BC 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
831C1D 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
9BB95F 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
C0778D 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
7D2D69 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
2EF63B 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
C417C0 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
EB042B 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
4C1F71 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
D23C8B 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
B4E4BE 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
EEF55D 0.74 1.00 1.00 0.00 1.00 0.00 0.22 1.00 1.00
E55A57 0.00 1.00 1.00 0.00 1.00 0.00 0.00 1.00 1.00
93D018 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
DD9F5D 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
15B02B 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
820282 0.00 0.00 0.00 1.00 0.00 0.12 0.00 0.00 0.00
9BA05A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
C639E8 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
A2790A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
79FCEE 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
EDE617 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
C61F0D 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
7248C5 0.00 0.00 0.00 1.00 0.00 0.98 0.00 0.00 0.00
29FA28 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F0B23F 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
EEC10E 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
944FCE 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
C41399 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
95BA33 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F27282 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
3DB407 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
3DADE2 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
DF3E2C 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
5031C8 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
C087D0 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
D2CA75 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
B0FB49 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
FE9BC9 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
9DF7DE 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
D0BE44 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
6B5226 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
8F59F7 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
44F571 0.73 1.00 1.00 0.00 1.00 0.00 0.57 1.00 1.00
6BD844 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
86D536 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
BAF71D 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
3833A2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
2111A1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
9BC521 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
142781 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
E74902 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
93BBC3 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
C635A6 0.90 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
FLOOR 1 ANESTHESIA_LIGHTS FLOOR 1 ANESTHESIA FLOOR 1 ANESTHESIA GENERAL 16.1458 10.03 162.00 LightsWired LTG_SCH_ANESTHESIA 74.58 168.00 72.68 0.0000 Y 2.21
FLOOR 1 BIO HAZ_LIGHTS FLOOR 1 BIO HAZ FLOOR 1 BIO HAZ GENERAL 9.6875 5.20 50.40 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 0.69
FLOOR 1 CAFE_LIGHTS FLOOR 1 CAFE FLOOR 1 CAFE GENERAL 9.6875 39.02 378.00 LightsWired LTG_SCH_DINING 74.58 168.00 72.68 0.0000 Y 5.16
FLOOR 1 CLEAN_LIGHTS FLOOR 1 CLEAN FLOOR 1 CLEAN GENERAL 16.1458 11.71 189.00 LightsWired LTG_SCH_CLEAN 74.58 168.00 72.68 0.0000 Y 2.58
FLOOR 1 CLEAN WORK_LIGHTS FLOOR 1 CLEAN WORK FLOOR 1 CLEAN WORK GENERAL 16.1458 15.33 247.50 LightsWired LTG_SCH_CLEAN 74.58 168.00 72.68 0.0000 Y 3.38
FLOOR 1 DICTATION_LIGHTS FLOOR 1 DICTATION FLOOR 1 DICTATION GENERAL 11.8403 11.71 138.60 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 1.89
FLOOR 1 DRESSING ROOM_LIGHTS FLOOR 1 DRESSING ROOM FLOOR 1 DRESSING ROOM GENERAL 11.8403 4.18 49.50 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 0.68
FLOOR 1 ELECTRICAL ROOM_LIGHTS FLOOR 1 ELECTRICAL ROOM FLOOR 1 ELECTRICAL ROOM GENERAL 16.1458 9.10 147.00 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 2.01
FLOOR 1 ELEVATOR PUMP ROOM_LIGHTS FLOOR 1 ELEVATOR PUMP ROOM FLOOR 1 ELEVATOR PUMP ROOM GENERAL 16.1458 8.45 136.50 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 1.86
FLOOR 1 HUMID_LIGHTS FLOOR 1 HUMID FLOOR 1 HUMID GENERAL 11.8403 5.02 59.40 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 0.81
FLOOR 1 IT HALL_LIGHTS FLOOR 1 IT HALL FLOOR 1 IT HALL GENERAL 10.3041 13.01 134.02 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 1.83
FLOOR 1 IT ROOM_LIGHTS FLOOR 1 IT ROOM FLOOR 1 IT ROOM GENERAL 11.8403 10.41 123.20 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 1.68
FLOOR 1 LOBBY_LIGHTS FLOOR 1 LOBBY FLOOR 1 LOBBY GENERAL 13.9931 57.79 808.60 LightsWired LTG_SCH_LOBBY 74.58 168.00 72.68 0.0000 Y 11.03
FLOOR 1 LOBBY HALL_LIGHTS FLOOR 1 LOBBY HALL FLOOR 1 LOBBY HALL GENERAL 10.3041 22.30 229.75 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 3.13
FLOOR 1 LOBBY TOILET_LIGHTS FLOOR 1 LOBBY TOILET FLOOR 1 LOBBY TOILET GENERAL 9.6875 5.02 48.60 LightsWired LTG_SCH_TOILET 74.58 168.00 72.68 0.0000 Y 0.66
FLOOR 1 LOCKER ROOM_LIGHTS FLOOR 1 LOCKER ROOM FLOOR 1 LOCKER ROOM GENERAL 8.6111 61.32 528.00 LightsWired LTG_SCH_LOUNGE 74.58 168.00 72.68 0.0000 Y 7.20
FLOOR 1 LOCKER ROOM HALL_LIGHTS FLOOR 1 LOCKER ROOM HALL FLOOR 1 LOCKER ROOM HALL GENERAL 10.3041 46.08 474.81 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 6.48
FLOOR 1 LOUNGE_LIGHTS FLOOR 1 LOUNGE FLOOR 1 LOUNGE GENERAL 8.6111 33.45 288.00 LightsWired LTG_SCH_LOUNGE 74.58 168.00 72.68 0.0000 Y 3.93
FLOOR 1 MED GAS_LIGHTS FLOOR 1 MED GAS FLOOR 1 MED GAS GENERAL 9.6875 5.20 50.40 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 0.69
FLOOR 1 MRI CONTROL ROOM_LIGHTS FLOOR 1 MRI CONTROL ROOM FLOOR 1 MRI CONTROL ROOM GENERAL 16.1458 15.61 252.00 LightsWired LTG_SCH_RADIOLOGY 74.58 168.00 72.68 0.0000 Y 3.44
FLOOR 1 MRI HALL_LIGHTS FLOOR 1 MRI HALL FLOOR 1 MRI HALL GENERAL 10.3041 13.66 140.72 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 1.92
FLOOR 1 MRI ROOM_LIGHTS FLOOR 1 MRI ROOM FLOOR 1 MRI ROOM GENERAL 16.1458 40.88 660.00 LightsWired LTG_SCH_RADIOLOGY 74.58 168.00 72.68 0.0000 Y 9.00
FLOOR 1 MRI TOILET_LIGHTS FLOOR 1 MRI TOILET FLOOR 1 MRI TOILET GENERAL 9.6875 5.02 48.60 LightsWired LTG_SCH_TOILET 74.58 168.00 72.68 0.0000 Y 0.66
FLOOR 1 NOURISHMENT_LIGHTS FLOOR 1 NOURISHMENT FLOOR 1 NOURISHMENT GENERAL 10.7639 16.91 182.00 LightsWired LTG_SCH_NURSE 74.58 168.00 72.68 0.0000 Y 2.48
FLOOR 1 NURSE HALL_LIGHTS FLOOR 1 NURSE HALL FLOOR 1 NURSE HALL GENERAL 10.3041 46.08 474.81 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 6.48
FLOOR 1 NURSE JANITOR_LIGHTS FLOOR 1 NURSE JANITOR FLOOR 1 NURSE JANITOR GENERAL 9.6875 5.02 48.60 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 0.66
FLOOR 1 NURSE STATION_LIGHTS FLOOR 1 NURSE STATION FLOOR 1 NURSE STATION GENERAL 10.7639 24.25 261.00 LightsWired LTG_SCH_NURSE 74.58 168.00 72.68 0.0000 Y 3.56
FLOOR 1 NURSE TOILET_LIGHTS FLOOR 1 NURSE TOILET FLOOR 1 NURSE TOILET GENERAL 9.6875 5.02 48.60 LightsWired LTG_SCH_TOILET 74.58 168.00 72.68 0.0000 Y 0.66
FLOOR 1 OFFICE_LIGHTS FLOOR 1 OFFICE FLOOR 1 OFFICE GENERAL 11.8403 44.87 531.30 LightsWired LTG_SCH_FLOOR_1_OFFICE 74.58 168.00 72.68 0.0000 Y 7.25
FLOOR 1 OPERATING ROOM 1_LIGHTS FLOOR 1 OPERATING ROOM 1 FLOOR 1 OPERATING ROOM 1 GENERAL 23.6806 42.74 1012.00 LightsWired LTG_SCH_OPERATION 74.58 168.00 72.68 0.0000 Y 13.81
FLOOR 1 OPERATING ROOM 2_LIGHTS FLOOR 1 OPERATING ROOM 2 FLOOR 1 OPERATING ROOM 2 GENERAL 23.6806 44.59 1056.00 LightsWired LTG_SCH_OPERATION 74.58 168.00 72.68 0.0000 Y 14.41
FLOOR 1 OPERATING ROOM 3_LIGHTS FLOOR 1 OPERATING ROOM 3 FLOOR 1 OPERATING ROOM 3 GENERAL 23.6806 44.22 1047.20 LightsWired LTG_SCH_OPERATION 74.58 168.00 72.68 0.0000 Y 14.29
FLOOR 1 PACU_LIGHTS FLOOR 1 PACU FLOOR 1 PACU GENERAL 8.6111 10.03 86.40 LightsWired LTG_SCH_RECOVERY 74.58 168.00 72.68 0.0000 Y 1.18
FLOOR 1 PRE-OP HALL_LIGHTS FLOOR 1 PRE-OP HALL FLOOR 1 PRE-OP HALL GENERAL 10.3041 49.05 505.44 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 6.90
FLOOR 1 PRE-OP ROOM 1_LIGHTS FLOOR 1 PRE-OP ROOM 1 FLOOR 1 PRE-OP ROOM 1 GENERAL 7.5347 17.56 132.30 LightsWired LTG_SCH_PATIENT 74.58 168.00 72.68 0.0000 Y 1.81
FLOOR 1 PRE-OP ROOM 2_LIGHTS FLOOR 1 PRE-OP ROOM 2 FLOOR 1 PRE-OP ROOM 2 GENERAL 7.5347 31.40 236.60 LightsWired LTG_SCH_PATIENT 74.58 168.00 72.68 0.0000 Y 3.23
FLOOR 1 PRE-OP TOILET_LIGHTS FLOOR 1 PRE-OP TOILET FLOOR 1 PRE-OP TOILET GENERAL 9.6875 5.02 48.60 LightsWired LTG_SCH_TOILET 74.58 168.00 72.68 0.0000 Y 0.66
FLOOR 1 PROCEDURE ROOM_LIGHTS FLOOR 1 PROCEDURE ROOM FLOOR 1 PROCEDURE ROOM GENERAL 16.1458 26.48 427.50 LightsWired LTG_SCH_PROCEDURE 74.58 168.00 72.68 0.0000 Y 5.83
FLOOR 1 RECEPTION_LIGHTS FLOOR 1 RECEPTION FLOOR 1 RECEPTION GENERAL 13.9931 47.29 661.70 LightsWired LTG_SCH_RECEPTION 74.58 168.00 72.68 0.0000 Y 9.03
FLOOR 1 RECEPTION HALL_LIGHTS FLOOR 1 RECEPTION HALL FLOOR 1 RECEPTION HALL GENERAL 10.3041 11.89 122.53 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 1.67
FLOOR 1 RECOVERY ROOM_LIGHTS FLOOR 1 RECOVERY ROOM FLOOR 1 RECOVERY ROOM GENERAL 8.6111 50.17 432.00 LightsWired LTG_SCH_RECOVERY 74.58 168.00 72.68 0.0000 Y 5.89
FLOOR 1 SCHEDULING_LIGHTS FLOOR 1 SCHEDULING FLOOR 1 SCHEDULING GENERAL 11.8403 11.06 130.90 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 1.79
FLOOR 1 SCRUB_LIGHTS FLOOR 1 SCRUB FLOOR 1 SCRUB GENERAL 10.3041 7.80 80.41 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 1.10
FLOOR 1 SOIL_LIGHTS FLOOR 1 SOIL FLOOR 1 SOIL GENERAL 16.1458 11.71 189.00 LightsWired LTG_SCH_SOILED 74.58 168.00 72.68 0.0000 Y 2.58
FLOOR 1 SOIL HOLD_LIGHTS FLOOR 1 SOIL HOLD FLOOR 1 SOIL HOLD GENERAL 16.1458 5.20 84.00 LightsWired LTG_SCH_SOILED 74.58 168.00 72.68 0.0000 Y 1.15
FLOOR 1 SOIL WORK_LIGHTS FLOOR 1 SOIL WORK FLOOR 1 SOIL WORK GENERAL 16.1458 16.72 270.00 LightsWired LTG_SCH_SOILED 74.58 168.00 72.68 0.0000 Y 3.68
FLOOR 1 STEP DOWN_LIGHTS FLOOR 1 STEP DOWN FLOOR 1 STEP DOWN GENERAL 8.6111 27.87 240.00 LightsWired LTG_SCH_RECOVERY 74.58 168.00 72.68 0.0000 Y 3.27
FLOOR 1 STERILE HALL_LIGHTS FLOOR 1 STERILE HALL FLOOR 1 STERILE HALL GENERAL 10.3041 57.23 589.68 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 8.05
FLOOR 1 STERILE STORAGE_LIGHTS FLOOR 1 STERILE STORAGE FLOOR 1 STERILE STORAGE GENERAL 9.6875 36.79 356.40 LightsWired LTG_SCH_FLOOR_1_STERILE_STORAGE 74.58 168.00 72.68 0.0000 Y 4.86
FLOOR 1 STORAGE_LIGHTS FLOOR 1 STORAGE FLOOR 1 STORAGE GENERAL 9.6875 85.47 828.00 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 11.30
FLOOR 1 SUB-STERILE_LIGHTS FLOOR 1 SUB-STERILE FLOOR 1 SUB-STERILE GENERAL 10.3041 18.21 187.63 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 2.56
FLOOR 1 UTILITY HALL_LIGHTS FLOOR 1 UTILITY HALL FLOOR 1 UTILITY HALL GENERAL 10.3041 23.78 245.06 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 3.34
FLOOR 1 UTILITY JANITOR_LIGHTS FLOOR 1 UTILITY JANITOR FLOOR 1 UTILITY JANITOR GENERAL 9.6875 3.90 37.80 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 0.52
FLOOR 1 UTILITY ROOM_LIGHTS FLOOR 1 UTILITY ROOM FLOOR 1 UTILITY ROOM GENERAL 9.6875 33.45 324.00 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 4.42
FLOOR 1 VESTIBULE_LIGHTS FLOOR 1 VESTIBULE FLOOR 1 VESTIBULE GENERAL 10.3041 6.69 68.92 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 0.94
FLOOR 2 CONFERENCE_LIGHTS FLOOR 2 CONFERENCE FLOOR 2 CONFERENCE GENERAL 13.9931 31.22 436.80 LightsWired LTG_SCH_CONFERENCE 74.58 168.00 72.68 0.0000 Y 5.96
FLOOR 2 CONFERENCE TOILET_LIGHTS FLOOR 2 CONFERENCE TOILET FLOOR 2 CONFERENCE TOILET GENERAL 9.6875 5.95 57.60 LightsWired LTG_SCH_TOILET 74.58 168.00 72.68 0.0000 Y 0.79
FLOOR 2 DICTATION_LIGHTS FLOOR 2 DICTATION FLOOR 2 DICTATION GENERAL 11.8403 6.50 77.00 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 1.05
FLOOR 2 EXAM 1_LIGHTS FLOOR 2 EXAM 1 FLOOR 2 EXAM 1 GENERAL 16.1458 33.45 540.00 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 7.37
FLOOR 2 EXAM 2_LIGHTS FLOOR 2 EXAM 2 FLOOR 2 EXAM 2 GENERAL 16.1458 50.17 810.00 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 11.05
FLOOR 2 EXAM 3_LIGHTS FLOOR 2 EXAM 3 FLOOR 2 EXAM 3 GENERAL 16.1458 66.89 1080.00 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 14.74
FLOOR 2 EXAM 4_LIGHTS FLOOR 2 EXAM 4 FLOOR 2 EXAM 4 GENERAL 16.1458 7.80 126.00 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 1.72
FLOOR 2 EXAM 5_LIGHTS FLOOR 2 EXAM 5 FLOOR 2 EXAM 5 GENERAL 16.1458 32.52 525.00 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 7.16
FLOOR 2 EXAM 6_LIGHTS FLOOR 2 EXAM 6 FLOOR 2 EXAM 6 GENERAL 16.1458 20.90 337.50 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 4.60
FLOOR 2 EXAM 7_LIGHTS FLOOR 2 EXAM 7 FLOOR 2 EXAM 7 GENERAL 16.1458 73.58 1188.00 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 16.21
FLOOR 2 EXAM 8_LIGHTS FLOOR 2 EXAM 8 FLOOR 2 EXAM 8 GENERAL 16.1458 25.08 405.00 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 5.53
FLOOR 2 EXAM 9_LIGHTS FLOOR 2 EXAM 9 FLOOR 2 EXAM 9 GENERAL 16.1458 36.79 594.00 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 8.10
FLOOR 2 EXAM HALL 1_LIGHTS FLOOR 2 EXAM HALL 1 FLOOR 2 EXAM HALL 1 GENERAL 10.3041 16.72 172.31 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 2.35
FLOOR 2 EXAM HALL 2_LIGHTS FLOOR 2 EXAM HALL 2 FLOOR 2 EXAM HALL 2 GENERAL 10.3041 16.72 172.31 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 2.35
FLOOR 2 EXAM HALL 3_LIGHTS FLOOR 2 EXAM HALL 3 FLOOR 2 EXAM HALL 3 GENERAL 10.3041 16.72 172.31 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 2.35
FLOOR 2 EXAM HALL 4_LIGHTS FLOOR 2 EXAM HALL 4 FLOOR 2 EXAM HALL 4 GENERAL 10.3041 18.39 189.54 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 2.59
FLOOR 2 EXAM HALL 5_LIGHTS FLOOR 2 EXAM HALL 5 FLOOR 2 EXAM HALL 5 GENERAL 10.3041 18.39 189.54 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 2.59
FLOOR 2 EXAM HALL 6_LIGHTS FLOOR 2 EXAM HALL 6 FLOOR 2 EXAM HALL 6 GENERAL 10.3041 18.39 189.54 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 2.59
FLOOR 2 JANITOR_LIGHTS FLOOR 2 JANITOR FLOOR 2 JANITOR GENERAL 9.6875 5.85 56.70 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 0.77
FLOOR 2 LOUNGE_LIGHTS FLOOR 2 LOUNGE FLOOR 2 LOUNGE GENERAL 8.6111 7.43 64.00 LightsWired LTG_SCH_LOUNGE 74.58 168.00 72.68 0.0000 Y 0.87
FLOOR 2 NURSE STATION 1_LIGHTS FLOOR 2 NURSE STATION 1 FLOOR 2 NURSE STATION 1 GENERAL 10.7639 13.94 150.00 LightsWired LTG_SCH_NURSE 74.58 168.00 72.68 0.0000 Y 2.05
FLOOR 2 NURSE STATION 2_LIGHTS FLOOR 2 NURSE STATION 2 FLOOR 2 NURSE STATION 2 GENERAL 10.7639 16.72 180.00 LightsWired LTG_SCH_NURSE 74.58 168.00 72.68 0.0000 Y 2.46
FLOOR 2 OFFICE_LIGHTS FLOOR 2 OFFICE FLOOR 2 OFFICE GENERAL 11.8403 52.03 616.00 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 8.40
FLOOR 2 OFFICE HALL_LIGHTS FLOOR 2 OFFICE HALL FLOOR 2 OFFICE HALL GENERAL 10.3041 41.25 425.03 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 5.80
FLOOR 2 RECEPTION_LIGHTS FLOOR 2 RECEPTION FLOOR 2 RECEPTION GENERAL 13.9931 91.42 1279.20 LightsWired LTG_SCH_RECEPTION 74.58 168.00 72.68 0.0000 Y 17.45
FLOOR 2 RECEPTION HALL_LIGHTS FLOOR 2 RECEPTION HALL FLOOR 2 RECEPTION HALL GENERAL 10.3041 52.40 539.91 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 7.37
FLOOR 2 RECEPTION TOILET_LIGHTS FLOOR 2 RECEPTION TOILET FLOOR 2 RECEPTION TOILET GENERAL 9.6875 11.71 113.40 LightsWired LTG_SCH_TOILET 74.58 168.00 72.68 0.0000 Y 1.55
FLOOR 2 SCHEDULING 1_LIGHTS FLOOR 2 SCHEDULING 1 FLOOR 2 SCHEDULING 1 GENERAL 11.8403 30.10 356.40 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 4.86
FLOOR 2 SCHEDULING 2_LIGHTS FLOOR 2 SCHEDULING 2 FLOOR 2 SCHEDULING 2 GENERAL 11.8403 31.77 376.20 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 5.13
FLOOR 2 STORAGE 1_LIGHTS FLOOR 2 STORAGE 1 FLOOR 2 STORAGE 1 GENERAL 9.6875 5.20 50.40 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 0.69
FLOOR 2 STORAGE 2_LIGHTS FLOOR 2 STORAGE 2 FLOOR 2 STORAGE 2 GENERAL 9.6875 11.15 108.00 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 1.47
FLOOR 2 STORAGE 3_LIGHTS FLOOR 2 STORAGE 3 FLOOR 2 STORAGE 3 GENERAL 9.6875 13.38 129.60 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 1.77
FLOOR 2 UTILITY_LIGHTS FLOOR 2 UTILITY FLOOR 2 UTILITY GENERAL 9.6875 11.71 113.40 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 1.55
FLOOR 2 WORK_LIGHTS FLOOR 2 WORK FLOOR 2 WORK GENERAL 11.8403 157.01 1859.00 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 25.36
FLOOR 2 WORK HALL_LIGHTS FLOOR 2 WORK HALL FLOOR 2 WORK HALL GENERAL 10.3041 77.48 798.37 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 10.89
FLOOR 2 WORK TOILET_LIGHTS FLOOR 2 WORK TOILET FLOOR 2 WORK TOILET GENERAL 9.6875 5.02 48.60 LightsWired LTG_SCH_TOILET 74.58 168.00 72.68 0.0000 Y 0.66
FLOOR 2 X-RAY_LIGHTS FLOOR 2 X-RAY FLOOR 2 X-RAY GENERAL 16.1458 83.61 1350.00 LightsWired LTG_SCH_RADIOLOGY 74.58 168.00 72.68 0.0000 Y 18.42
FLOOR 3 DRESSING ROOM_LIGHTS FLOOR 3 DRESSING ROOM FLOOR 3 DRESSING ROOM GENERAL 11.8403 3.90 46.20 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 0.63
FLOOR 3 ELEVATOR HALL_LIGHTS FLOOR 3 ELEVATOR HALL FLOOR 3 ELEVATOR HALL GENERAL 10.3041 34.37 354.19 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 4.83
FLOOR 3 HUMID_LIGHTS FLOOR 3 HUMID FLOOR 3 HUMID GENERAL 11.8403 10.03 118.80 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 1.62
FLOOR 3 JANITOR_LIGHTS FLOOR 3 JANITOR FLOOR 3 JANITOR GENERAL 9.6875 5.85 56.70 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 0.77
FLOOR 3 LOCKER_LIGHTS FLOOR 3 LOCKER FLOOR 3 LOCKER GENERAL 8.6111 11.15 96.00 LightsWired LTG_SCH_LOUNGE 74.58 168.00 72.68 0.0000 Y 1.31
FLOOR 3 LOUNGE_LIGHTS FLOOR 3 LOUNGE FLOOR 3 LOUNGE GENERAL 8.6111 70.51 607.20 LightsWired LTG_SCH_LOUNGE 74.58 168.00 72.68 0.0000 Y 8.28
FLOOR 3 LOUNGE TOILET_LIGHTS FLOOR 3 LOUNGE TOILET FLOOR 3 LOUNGE TOILET GENERAL 9.6875 17.84 172.80 LightsWired LTG_SCH_TOILET 74.58 168.00 72.68 0.0000 Y 2.36
FLOOR 3 MECHANICAL_LIGHTS FLOOR 3 MECHANICAL FLOOR 3 MECHANICAL GENERAL 16.1458 32.52 525.00 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 7.16
FLOOR 3 MECHANICAL HALL_LIGHTS FLOOR 3 MECHANICAL HALL FLOOR 3 MECHANICAL HALL GENERAL 10.3041 27.87 287.18 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 3.92
FLOOR 3 OFFICE_LIGHTS FLOOR 3 OFFICE FLOOR 3 OFFICE GENERAL 11.8403 282.05 3339.60 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 45.56
FLOOR 3 OFFICE HALL_LIGHTS FLOOR 3 OFFICE HALL FLOOR 3 OFFICE HALL GENERAL 10.3041 77.48 798.37 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 10.89
FLOOR 3 OFFICE TOILET_LIGHTS FLOOR 3 OFFICE TOILET FLOOR 3 OFFICE TOILET GENERAL 9.6875 5.02 48.60 LightsWired LTG_SCH_TOILET 74.58 168.00 72.68 0.0000 Y 0.66
FLOOR 3 PHYSICAL THERAPY 1_LIGHTS FLOOR 3 PHYSICAL THERAPY 1 FLOOR 3 PHYSICAL THERAPY 1 GENERAL 9.6875 120.77 1170.00 LightsWired LTG_SCH_PHY_THERAPY 74.58 168.00 72.68 0.0000 Y 15.96
FLOOR 3 PHYSICAL THERAPY 2_LIGHTS FLOOR 3 PHYSICAL THERAPY 2 FLOOR 3 PHYSICAL THERAPY 2 GENERAL 9.6875 55.00 532.80 LightsWired LTG_SCH_PHY_THERAPY 74.58 168.00 72.68 0.0000 Y 7.27
FLOOR 3 PHYSICAL THERAPY TOILET_LIGHTS FLOOR 3 PHYSICAL THERAPY TOILET FLOOR 3 PHYSICAL THERAPY TOILET GENERAL 9.6875 7.80 75.60 LightsWired LTG_SCH_TOILET 74.58 168.00 72.68 0.0000 Y 1.03
FLOOR 3 STORAGE 1_LIGHTS FLOOR 3 STORAGE 1 FLOOR 3 STORAGE 1 GENERAL 9.6875 10.03 97.20 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 1.33
FLOOR 3 STORAGE 2_LIGHTS FLOOR 3 STORAGE 2 FLOOR 3 STORAGE 2 GENERAL 9.6875 7.80 75.60 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 1.03
FLOOR 3 TREATMENT_LIGHTS FLOOR 3 TREATMENT FLOOR 3 TREATMENT GENERAL 16.1458 44.22 714.00 LightsWired LTG_SCH_EXAM 74.58 168.00 72.68 0.0000 Y 9.74
FLOOR 3 UNDEVELOPED 1_LIGHTS FLOOR 3 UNDEVELOPED 1 FLOOR 3 UNDEVELOPED 1 GENERAL 9.6875 210.70 2041.20 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 27.85
FLOOR 3 UNDEVELOPED 2_LIGHTS FLOOR 3 UNDEVELOPED 2 FLOOR 3 UNDEVELOPED 2 GENERAL 9.6875 107.02 1036.80 LightsWired LTG_SCH_STORAGE 74.58 168.00 72.68 0.0000 Y 14.15
FLOOR 3 UTILITY_LIGHTS FLOOR 3 UTILITY FLOOR 3 UTILITY GENERAL 16.1458 20.07 324.00 LightsWired LTG_SCH_UTILITY 74.58 168.00 72.68 0.0000 Y 4.42
FLOOR 3 WORK_LIGHTS FLOOR 3 WORK FLOOR 3 WORK GENERAL 11.8403 53.33 631.40 LightsWired LTG_SCH_OFFICE 74.58 168.00 72.68 0.0000 Y 8.61
NE STAIR_LIGHTS NE STAIR NE STAIR GENERAL 10.3041 15.61 160.82 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 2.19
NW ELEVATOR_LIGHTS NW ELEVATOR NW ELEVATOR GENERAL 10.3041 13.01 134.02 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 1.83
NW STAIR_LIGHTS NW STAIR NW STAIR GENERAL 10.3041 17.84 183.80 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 2.51
SW STAIR_LIGHTS SW STAIR SW STAIR GENERAL 10.3041 8.92 91.90 LightsWired LTG_SCH_CORRIDOR 74.58 168.00 72.68 0.0000 Y 1.25
Interior Lighting Total       12.0629 3804.01 45887.41               626.08


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS 15116.60 AstronomicalClock -   83.82 83.82 237.86
Exterior Lighting Total 15116.60           237.86



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 133636.71 0.75        


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
AHU-1 COOLING COIL Coil:Cooling:DX:TwoSpeed   137630.08 96490.14 41139.94 0.70 3.50    
AHU-2 COOLING COIL Coil:Cooling:DX:TwoSpeed   141596.54 101966.98 39629.56 0.72 3.50    
AHU-3 COOLING COIL Coil:Cooling:DX:TwoSpeed   137288.61 98131.99 39156.62 0.71 3.50    
PSZ_CAFE HP COOLING COIL Coil:Cooling:DX:MultiSpeed   8922.42 6255.33 2667.09 0.70 3.00    
PSZ_ELEVATOR HP COOLING COIL Coil:Cooling:DX:MultiSpeed   1682.54 1346.87 335.67 0.80 3.00    
PSZ_MRI_CONTROL HP COOLING COIL Coil:Cooling:DX:MultiSpeed   4054.94 3077.62 977.32 0.76 3.00    
PSZ_MRI HP COOLING COIL Coil:Cooling:DX:MultiSpeed   9890.23 7447.74 2442.49 0.75 3.00    
PSZ_OR_1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   17968.90 12597.64 5371.26 0.70 3.00    
PSZ_OR_2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   18750.15 13145.36 5604.79 0.70 3.00    
PSZ_OR_3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   18593.90 13035.81 5558.09 0.70 3.00    
PSZ_XRAY HP COOLING COIL Coil:Cooling:DX:MultiSpeed   22311.11 16936.81 5374.30 0.76 3.40    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
AHU-1 COOLING COIL   133577.2 3.09 10.53 N/A N/A 11.69
AHU-2 COOLING COIL   137156.3 3.06 10.44 N/A N/A 11.57
AHU-3 COOLING COIL   133059.1 3.07 10.47 N/A N/A 11.61
PSZ_CAFE HP COOLING COIL   8639.0     9.73 9.73  
PSZ_ELEVATOR HP COOLING COIL   1606.8     9.25 9.25  
PSZ_MRI_CONTROL HP COOLING COIL   3902.5     9.51 9.51  
PSZ_MRI HP COOLING COIL   9524.6     9.54 9.54  
PSZ_OR_1 HP COOLING COIL   17398.0     9.73 9.73  
PSZ_OR_2 HP COOLING COIL   18154.5     9.73 9.73  
PSZ_OR_3 HP COOLING COIL   18003.2     9.73 9.73  
PSZ_XRAY HP COOLING COIL   21471.8     10.59 10.59  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
AHU-1 COOLING COIL Coil:Cooling:DX:TwoSpeed                
AHU-2 COOLING COIL Coil:Cooling:DX:TwoSpeed                
AHU-3 COOLING COIL Coil:Cooling:DX:TwoSpeed                
PSZ_CAFE HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ_ELEVATOR HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ_MRI_CONTROL HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ_MRI HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ_OR_1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ_OR_2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ_OR_3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ_XRAY HP COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ_CAFE HEATING COIL Coil:Heating:DX:MultiSpeed 9211.1 5068.5 7.91 2
PSZ_ELEVATOR HEATING COIL Coil:Heating:DX:MultiSpeed 1676.1 933.5 7.83 2
PSZ_MRI_CONTROL HEATING COIL Coil:Heating:DX:MultiSpeed 4032.4 2232.0 7.87 2
PSZ_MRI HEATING COIL Coil:Heating:DX:MultiSpeed 9828.1 5437.2 7.74 2
PSZ_OR_1 HEATING COIL Coil:Heating:DX:MultiSpeed 18550.2 10207.4 7.90 2
PSZ_OR_2 HEATING COIL Coil:Heating:DX:MultiSpeed 19356.8 10651.2 7.87 2
PSZ_OR_3 HEATING COIL Coil:Heating:DX:MultiSpeed 19195.5 10562.4 7.88 2
PSZ_XRAY HEATING COIL Coil:Heating:DX:MultiSpeed 22103.1 12235.9 7.80 2
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL Coil:Heating:Water 2984.58 2019.29 -
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL Coil:Heating:Water 358.55 242.49 -
FLOOR 1 CLEAN VAV BOX REHEAT COIL Coil:Heating:Water 3233.65 2188.04 -
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL Coil:Heating:Water 4046.69 2738.17 -
FLOOR 1 DICTATION VAV BOX REHEAT COIL Coil:Heating:Water 243.27 164.61 -
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL Coil:Heating:Water 540.49 365.54 -
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL Coil:Heating:Water 606.02 410.06 -
FLOOR 1 HUMID VAV BOX REHEAT COIL Coil:Heating:Water 120.59 81.60 -
FLOOR 1 IT HALL VAV BOX REHEAT COIL Coil:Heating:Water 439.77 297.57 -
FLOOR 1 IT ROOM VAV BOX REHEAT COIL Coil:Heating:Water 211.24 142.93 -
FLOOR 1 LOBBY VAV BOX REHEAT COIL Coil:Heating:Water 3473.85 2350.13 -
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL Coil:Heating:Water 802.97 543.33 -
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1397.24 945.28 -
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL Coil:Heating:Water 3004.15 2032.74 -
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL Coil:Heating:Water 1355.38 917.11 -
FLOOR 1 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Water 1636.05 1107.02 -
FLOOR 1 MED GAS VAV BOX REHEAT COIL Coil:Heating:Water 1696.30 1147.22 -
FLOOR 1 MRI HALL VAV BOX REHEAT COIL Coil:Heating:Water 537.20 363.50 -
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1138.28 770.15 -
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL Coil:Heating:Water 851.92 576.45 -
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL Coil:Heating:Water 1508.78 1020.91 -
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL Coil:Heating:Water 190.14 128.66 -
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL Coil:Heating:Water 1126.94 762.54 -
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1077.00 728.75 -
FLOOR 1 OFFICE VAV BOX REHEAT COIL Coil:Heating:Water 757.35 512.46 -
FLOOR 1 PACU VAV BOX REHEAT COIL Coil:Heating:Water 2857.46 1933.49 -
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL Coil:Heating:Water 1548.17 1047.56 -
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL Coil:Heating:Water 3948.97 2672.05 -
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL Coil:Heating:Water 7062.18 4778.59 -
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1179.93 798.27 -
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL Coil:Heating:Water 14887.00 10073.21 -
FLOOR 1 RECEPTION VAV BOX REHEAT COIL Coil:Heating:Water 2391.09 1617.92 -
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL Coil:Heating:Water 410.29 277.62 -
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL Coil:Heating:Water 12957.10 8766.66 -
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL Coil:Heating:Water 231.80 156.85 -
FLOOR 1 SCRUB VAV BOX REHEAT COIL Coil:Heating:Water 324.17 219.28 -
FLOOR 1 SOIL VAV BOX REHEAT COIL Coil:Heating:Water 3231.28 2186.43 -
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL Coil:Heating:Water 1507.49 1020.04 -
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL Coil:Heating:Water 4292.37 2904.41 -
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL Coil:Heating:Water 6858.70 4640.28 -
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL Coil:Heating:Water 1734.97 1173.96 -
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL Coil:Heating:Water 976.73 660.90 -
FLOOR 1 STORAGE VAV BOX REHEAT COIL Coil:Heating:Water 13705.00 9268.74 -
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL Coil:Heating:Water 2306.24 1559.72 -
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL Coil:Heating:Water 4362.06 2950.08 -
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL Coil:Heating:Water 168.08 113.70 -
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL Coil:Heating:Water 3948.42 2670.33 -
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL Coil:Heating:Water 487.54 329.72 -
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL Coil:Heating:Water 5025.87 3397.85 -
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1271.20 859.81 -
FLOOR 2 DICTATION VAV BOX REHEAT COIL Coil:Heating:Water 437.90 296.22 -
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL Coil:Heating:Water 6932.62 4687.89 -
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL Coil:Heating:Water 11401.04 7711.84 -
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL Coil:Heating:Water 15200.52 10281.87 -
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL Coil:Heating:Water 1719.54 1162.74 -
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL Coil:Heating:Water 8664.01 5859.54 -
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL Coil:Heating:Water 5345.07 3615.10 -
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL Coil:Heating:Water 16548.08 11194.31 -
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL Coil:Heating:Water 6223.75 4209.57 -
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL Coil:Heating:Water 8748.54 5918.14 -
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL Coil:Heating:Water 1225.20 828.46 -
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL Coil:Heating:Water 1077.55 728.81 -
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL Coil:Heating:Water 1066.72 721.46 -
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL Coil:Heating:Water 1082.64 732.31 -
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL Coil:Heating:Water 1099.29 743.64 -
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL Coil:Heating:Water 1118.46 756.53 -
FLOOR 2 JANITOR VAV BOX REHEAT COIL Coil:Heating:Water 1279.73 865.16 -
FLOOR 2 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Water 632.08 427.59 -
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL Coil:Heating:Water 995.70 673.57 -
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL Coil:Heating:Water 1203.92 814.42 -
FLOOR 2 OFFICE VAV BOX REHEAT COIL Coil:Heating:Water 7038.08 4758.03 -
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL Coil:Heating:Water 2708.83 1831.81 -
FLOOR 2 RECEPTION VAV BOX REHEAT COIL Coil:Heating:Water 8937.71 6044.00 -
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL Coil:Heating:Water 3129.37 2116.93 -
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL Coil:Heating:Water 2235.50 1512.25 -
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL Coil:Heating:Water 1652.43 1117.82 -
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL Coil:Heating:Water 1758.10 1189.30 -
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL Coil:Heating:Water 340.79 230.46 -
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL Coil:Heating:Water 584.14 395.10 -
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL Coil:Heating:Water 687.42 465.02 -
FLOOR 2 UTILITY VAV BOX REHEAT COIL Coil:Heating:Water 2152.67 1455.30 -
FLOOR 2 WORK VAV BOX REHEAT COIL Coil:Heating:Water 7371.03 4986.29 -
FLOOR 2 WORK HALL VAV BOX REHEAT COIL Coil:Heating:Water 4449.83 3010.18 -
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1290.81 872.85 -
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL Coil:Heating:Water 315.98 213.75 -
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL Coil:Heating:Water 3443.33 2327.83 -
FLOOR 3 HUMID VAV BOX REHEAT COIL Coil:Heating:Water 733.32 496.07 -
FLOOR 3 JANITOR VAV BOX REHEAT COIL Coil:Heating:Water 1747.87 1181.64 -
FLOOR 3 LOCKER VAV BOX REHEAT COIL Coil:Heating:Water 994.39 672.62 -
FLOOR 3 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Water 5728.16 3874.52 -
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL Coil:Heating:Water 4486.17 3033.59 -
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL Coil:Heating:Water 4879.73 3300.75 -
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL Coil:Heating:Water 2308.09 1560.37 -
FLOOR 3 OFFICE VAV BOX REHEAT COIL Coil:Heating:Water 20137.16 13613.58 -
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL Coil:Heating:Water 5904.69 3991.84 -
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1396.37 944.08 -
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL Coil:Heating:Water 27354.72 18497.86 -
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL Coil:Heating:Water 10458.98 7074.52 -
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1646.96 1114.12 -
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL Coil:Heating:Water 1938.60 1311.22 -
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL Coil:Heating:Water 588.17 397.64 -
FLOOR 3 TREATMENT VAV BOX REHEAT COIL Coil:Heating:Water 8548.32 5782.70 -
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL Coil:Heating:Water 18890.57 12770.76 -
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL Coil:Heating:Water 13748.49 9294.53 -
FLOOR 3 UTILITY VAV BOX REHEAT COIL Coil:Heating:Water 1187.57 803.04 -
FLOOR 3 WORK VAV BOX REHEAT COIL Coil:Heating:Water 8826.19 5966.88 -
NE STAIR VAV BOX REHEAT COIL Coil:Heating:Water 10755.93 7271.49 -
NW ELEVATOR VAV BOX REHEAT COIL Coil:Heating:Water 6572.63 4443.38 -
NW STAIR VAV BOX REHEAT COIL Coil:Heating:Water 10385.31 7020.92 -
SW STAIR VAV BOX REHEAT COIL Coil:Heating:Water 5126.39 3465.66 -
AHU-1 HEATING COIL Coil:Heating:Water 0.00 0.00 -
AHU-2 HEATING COIL Coil:Heating:Water 0.00 0.00 -
AHU-3 HEATING COIL Coil:Heating:Water 0.00 0.00 -
PSZ_CAFE HEATING COIL Coil:Heating:DX:MultiSpeed   8922.42 3.40
PSZ_CAFE_SUPPHEATCOIL Coil:Heating:Electric   8922.42 1.00
PSZ_ELEVATOR HEATING COIL Coil:Heating:DX:MultiSpeed   1599.46 3.40
PSZ_ELEVATOR_SUPPHEATCOIL Coil:Heating:Electric   1599.46 1.00
PSZ_MRI_CONTROL HEATING COIL Coil:Heating:DX:MultiSpeed   3877.79 3.40
PSZ_MRI_CONTROL_SUPPHEATCOIL Coil:Heating:Electric   3877.79 1.00
PSZ_MRI HEATING COIL Coil:Heating:DX:MultiSpeed   9457.21 3.40
PSZ_MRI_SUPPHEATCOIL Coil:Heating:Electric   9457.21 1.00
PSZ_OR_1 HEATING COIL Coil:Heating:DX:MultiSpeed   17968.90 3.40
PSZ_OR_1_SUPPHEATCOIL Coil:Heating:Electric   17968.90 1.00
PSZ_OR_2 HEATING COIL Coil:Heating:DX:MultiSpeed   18750.15 3.40
PSZ_OR_2_SUPPHEATCOIL Coil:Heating:Electric   18750.15 1.00
PSZ_OR_3 HEATING COIL Coil:Heating:DX:MultiSpeed   18593.90 3.40
PSZ_OR_3_SUPPHEATCOIL Coil:Heating:Electric   18593.90 1.00
PSZ_XRAY HEATING COIL Coil:Heating:DX:MultiSpeed   21252.04 3.40
PSZ_XRAY_SUPPHEATCOIL Coil:Heating:Electric   21252.04 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
FLOOR 1 ANESTHESIA EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.07 0.00 0.00 1.00 0.00 General    
FLOOR 1 LOBBY TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.04 0.00 0.00 1.00 0.00 General    
FLOOR 1 MRI CONTROL ROOM EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.16 0.00 0.00 1.00 0.00 General    
FLOOR 1 MRI ROOM EXHAUST FAN Fan:ZoneExhaust 0.39 0.00 0.42 0.00 0.00 1.00 0.00 General    
FLOOR 1 MRI TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.04 0.00 0.00 1.00 0.00 General    
FLOOR 1 NURSE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.04 0.00 0.00 1.00 0.00 General    
FLOOR 1 PRE-OP TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.04 0.00 0.00 1.00 0.00 General    
FLOOR 1 SOIL EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.10 0.00 0.00 1.00 0.00 General    
FLOOR 1 SOIL HOLD EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.04 0.00 0.00 1.00 0.00 General    
FLOOR 1 SOIL WORK EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.14 0.00 0.00 1.00 0.00 General    
FLOOR 2 CONFERENCE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.05 0.00 0.00 1.00 0.00 General    
FLOOR 2 RECEPTION TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.10 0.00 0.00 1.00 0.00 General    
FLOOR 2 WORK TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.04 0.00 0.00 1.00 0.00 General    
FLOOR 2 X-RAY EXHAUST FAN Fan:ZoneExhaust 0.39 0.00 0.85 0.00 0.00 1.00 0.00 General    
FLOOR 3 LOUNGE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.15 0.00 0.00 1.00 0.00 General    
FLOOR 3 OFFICE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.04 0.00 0.00 1.00 0.00 General    
FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 0.00 0.07 0.00 0.00 1.00 0.00 General    
AHU-1 FAN Fan:VariableVolume 0.60 1337.13 5.54 12259.49 2211.96 1.00 1.13 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00
AHU-2 FAN Fan:VariableVolume 0.60 1337.13 6.05 13386.82 2211.96 1.00 1.13 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00
AHU-3 FAN Fan:VariableVolume 0.60 1337.13 5.77 12763.12 2211.96 1.00 1.13 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00
PSZ_CAFE_ADDAQ FAN Fan:SystemModel 0.56 966.87 0.36 625.10 1739.75 1.00 1.63 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ_ELEVATOR_ADDAQ FAN Fan:SystemModel 0.56 966.87 0.10 168.10 1739.75 1.00 3.00 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00
PSZ_MRI_CONTROL_ADDAQ FAN Fan:SystemModel 0.56 966.87 0.19 337.29 1739.75 1.00 2.07 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ_MRI_ADDAQ FAN Fan:SystemModel 0.56 966.87 0.46 799.35 1719.64 1.00 1.52 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ_OR_1_ADDAQ FAN Fan:SystemModel 0.56 966.87 0.72 1244.34 1719.64 1.00 1.37 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ_OR_2_ADDAQ FAN Fan:SystemModel 0.56 966.87 0.76 1298.45 1719.64 1.00 1.36 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ_OR_3_ADDAQ FAN Fan:SystemModel 0.56 966.87 0.75 1287.62 1719.64 1.00 1.36 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ_XRAY_ADDAQ FAN Fan:SystemModel 0.58 966.87 1.07 1773.77 1662.00 1.00 1.32 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.001169 352.09 301156.09 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000063 8.07 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.76 58614.20 0.81 14.75 0.47


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
AHU-1 COOLING COIL Coil:Cooling:DX:TwoSpeed None 133577.25 3.09 10.53 11.69 6.4028 3.34 11.39 5.0670 3.54 12.09 3.3894 3.70 12.61 1.4371
AHU-2 COOLING COIL Coil:Cooling:DX:TwoSpeed None 137156.31 3.06 10.44 11.57 6.9915 3.30 11.27 5.5363 3.50 11.95 3.7180 3.67 12.53 1.5398
AHU-3 COOLING COIL Coil:Cooling:DX:TwoSpeed None 133059.13 3.07 10.47 11.61 6.6658 3.31 11.30 5.2856 3.52 11.99 3.5377 3.68 12.55 1.4756
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {{W/1000cfm}} (773.3 {{W/(m3/s)}})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
FLOOR 1 ANESTHESIA 788.80 907.12 90.41 0.057 0.065 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00900 28.24 0.01716 0.015 0.00
FLOOR 1 BIO HAZ 269.40 309.81 59.55 0.019 0.022 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00857 28.24 0.01716 0.003 0.00
FLOOR 1 CAFE 4255.97 4894.37 125.43 0.312 0.359 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 22.20 22.19 0.01019 33.20 0.01717 0.184 0.00
FLOOR 1 CLEAN 881.21 1013.39 86.57 0.064 0.073 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00898 28.24 0.01716 0.018 0.00
FLOOR 1 CLEAN WORK 1103.46 1268.98 82.78 0.079 0.091 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00901 28.24 0.01716 0.023 0.00
FLOOR 1 DICTATION 666.06 765.97 65.44 0.048 0.055 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00866 28.24 0.01716 0.005 0.00
FLOOR 1 DRESSING ROOM 361.58 415.81 99.46 0.026 0.030 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00869 28.24 0.01716 0.002 0.00
FLOOR 1 ELECTRICAL ROOM 824.15 947.78 104.10 0.060 0.068 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00856 28.24 0.01716 0.000 0.00
FLOOR 1 ELEVATOR PUMP ROOM 1145.94 1317.83 155.88 0.084 0.097 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 22.20 22.20 0.00858 32.15 0.01717 0.000 0.00
FLOOR 1 HUMID 329.33 378.73 75.49 0.024 0.027 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00864 28.24 0.01716 0.002 0.00
FLOOR 1 IT HALL 589.00 677.34 52.08 0.043 0.050 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 22.20 22.20 0.00871 28.67 0.01716 0.004 0.00
FLOOR 1 IT ROOM 578.50 665.27 63.94 0.041 0.048 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00867 28.24 0.01716 0.004 0.00
FLOOR 1 LOBBY 4190.48 4819.05 83.40 0.307 0.353 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 22.20 22.20 0.00877 32.26 0.01717 0.032 0.00
FLOOR 1 LOBBY HALL 1101.93 1267.22 56.83 0.079 0.091 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00869 28.24 0.01716 0.007 0.00
FLOOR 1 LOBBY TOILET 352.61 405.50 80.83 0.025 0.029 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00869 28.24 0.01716 0.000 0.00
FLOOR 1 LOCKER ROOM 4100.79 4715.90 76.91 0.295 0.339 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00893 28.24 0.01716 0.042 0.00
FLOOR 1 LOCKER ROOM HALL 1868.74 2149.06 46.64 0.133 0.153 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00873 28.24 0.01716 0.014 0.00
FLOOR 1 LOUNGE 2233.31 2568.31 76.79 0.161 0.185 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00891 28.24 0.01716 0.023 0.00
FLOOR 1 MED GAS 433.85 498.93 95.90 0.032 0.037 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:10:00 22.20 22.20 0.00866 32.42 0.01717 0.003 0.00
FLOOR 1 MRI CONTROL ROOM 2325.67 2674.52 171.36 0.169 0.194 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00875 28.24 0.01716 0.024 0.00
FLOOR 1 MRI HALL 735.98 846.38 61.98 0.053 0.061 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00867 28.24 0.01716 0.004 0.00
FLOOR 1 MRI ROOM 5579.35 6416.26 156.96 0.404 0.465 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00877 28.24 0.01716 0.062 0.00
FLOOR 1 MRI TOILET 306.29 352.23 70.21 0.022 0.025 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00872 28.24 0.01716 0.000 0.00
FLOOR 1 NOURISHMENT 1162.36 1336.71 79.06 0.084 0.096 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00890 28.24 0.01716 0.014 0.00
FLOOR 1 NURSE HALL 2074.50 2385.68 51.77 0.148 0.170 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00871 28.24 0.01716 0.014 0.00
FLOOR 1 NURSE JANITOR 260.58 299.67 59.73 0.019 0.021 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00857 28.24 0.01716 0.003 0.00
FLOOR 1 NURSE STATION 1539.62 1770.56 73.02 0.111 0.127 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00893 28.24 0.01716 0.020 0.00
FLOOR 1 NURSE TOILET 294.64 338.84 67.54 0.021 0.024 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00865 28.24 0.01716 0.000 0.00
FLOOR 1 OFFICE 2081.47 2393.68 53.34 0.149 0.171 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00870 28.24 0.01716 0.019 0.00
FLOOR 1 OPERATING ROOM 1 7497.88 8622.57 201.77 0.550 0.724 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 18.60 18.60 0.00866 30.82 0.01716 0.239 0.00
FLOOR 1 OPERATING ROOM 2 7743.87 8905.45 199.70 0.568 0.755 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 18.60 18.60 0.00865 30.46 0.01716 0.249 0.00
FLOOR 1 OPERATING ROOM 3 6545.91 7527.80 170.23 0.480 0.749 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:20:00 18.60 18.60 0.00865 27.48 0.01716 0.247 0.00
FLOOR 1 PACU 778.35 895.11 89.21 0.056 0.065 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00897 28.24 0.01716 0.032 0.00
FLOOR 1 PRE-OP HALL 2130.51 2450.09 49.95 0.152 0.175 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00871 28.24 0.01716 0.015 0.00
FLOOR 1 PRE-OP ROOM 1 1019.36 1172.26 66.76 0.073 0.089 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00883 28.24 0.01716 0.052 0.00
FLOOR 1 PRE-OP ROOM 2 1766.79 2031.81 64.70 0.127 0.160 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00883 28.24 0.01716 0.093 0.00
FLOOR 1 PRE-OP TOILET 298.68 343.48 68.47 0.021 0.025 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00873 28.24 0.01716 0.000 0.00
FLOOR 1 PROCEDURE ROOM 2212.91 2544.84 96.11 0.160 0.336 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00897 28.24 0.01716 0.108 0.00
FLOOR 1 RECEPTION 3261.54 3750.78 79.32 0.235 0.270 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00931 28.24 0.01716 0.050 0.00
FLOOR 1 RECEPTION HALL 563.42 647.93 54.49 0.040 0.046 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00869 28.24 0.01716 0.004 0.00
FLOOR 1 RECOVERY ROOM 3946.70 4538.70 90.47 0.289 0.333 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 22.20 22.20 0.00900 33.14 0.01717 0.161 0.00
FLOOR 1 SCHEDULING 634.46 729.63 66.00 0.046 0.052 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00870 28.24 0.01716 0.005 0.00
FLOOR 1 SCRUB 382.48 439.85 56.36 0.027 0.031 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00869 28.24 0.01716 0.002 0.00
FLOOR 1 SOIL 880.57 1012.66 86.51 0.063 0.073 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00898 28.24 0.01716 0.018 0.00
FLOOR 1 SOIL HOLD 410.51 472.09 90.74 0.030 0.034 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00896 28.24 0.01716 0.008 0.00
FLOOR 1 SOIL WORK 1170.92 1346.56 80.52 0.084 0.097 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00902 28.24 0.01716 0.025 0.00
FLOOR 1 STEP DOWN 2517.54 2895.17 103.88 0.185 0.212 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 22.20 22.20 0.00895 32.44 0.01717 0.090 0.00
FLOOR 1 STERILE HALL 2323.70 2672.25 46.69 0.170 0.196 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 22.20 22.20 0.00874 28.67 0.01716 0.017 0.00
FLOOR 1 STERILE STORAGE 1350.47 1553.04 42.21 0.096 0.110 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00860 28.24 0.01716 0.022 0.00
FLOOR 1 STORAGE 4030.87 4635.50 54.23 0.296 0.340 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 22.20 22.20 0.00863 32.62 0.01717 0.052 0.00
FLOOR 1 SUB-STERILE 1210.15 1391.67 76.43 0.089 0.102 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 22.20 22.20 0.00868 30.65 0.01716 0.006 0.00
FLOOR 1 UTILITY HALL 2123.20 2441.68 102.66 0.156 0.179 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 22.20 22.20 0.00863 30.27 0.01716 0.007 0.00
FLOOR 1 UTILITY JANITOR 204.92 235.66 60.39 0.015 0.017 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00857 28.24 0.01716 0.002 0.00
FLOOR 1 UTILITY ROOM 1715.87 1973.25 59.00 0.126 0.145 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 22.20 22.20 0.00862 28.67 0.01716 0.020 0.00
FLOOR 1 VESTIBULE 493.45 567.47 84.84 0.036 0.042 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 22.20 22.20 0.00868 32.44 0.01717 0.002 0.00
FLOOR 2 CONFERENCE 2979.50 3426.43 109.77 0.219 0.251 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 22.20 22.19 0.00952 31.49 0.01716 0.049 0.00
FLOOR 2 CONFERENCE TOILET 333.52 383.54 64.51 0.024 0.028 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00866 28.24 0.01716 0.000 0.00
FLOOR 2 DICTATION 399.15 459.02 70.58 0.029 0.033 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00865 28.24 0.01716 0.003 0.00
FLOOR 2 EXAM 1 3081.70 3543.95 105.96 0.226 0.260 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 22.20 22.20 0.00896 32.35 0.01717 0.051 0.00
FLOOR 2 EXAM 2 3033.70 3488.75 69.54 0.218 0.255 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00914 28.24 0.01716 0.076 0.00
FLOOR 2 EXAM 3 3972.46 4568.33 68.30 0.285 0.340 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00916 28.24 0.01716 0.102 0.00
FLOOR 2 EXAM 4 609.19 700.56 89.77 0.044 0.051 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00902 28.24 0.01716 0.012 0.00
FLOOR 2 EXAM 5 3002.19 3452.52 106.18 0.220 0.253 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 22.20 22.20 0.00894 30.27 0.01716 0.050 0.00
FLOOR 2 EXAM 6 1435.09 1650.35 78.95 0.103 0.119 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00909 28.24 0.01716 0.032 0.00
FLOOR 2 EXAM 7 4326.23 4975.17 67.62 0.311 0.374 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00916 28.24 0.01716 0.112 0.00
FLOOR 2 EXAM 8 1736.54 1997.02 79.61 0.125 0.144 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00908 28.24 0.01716 0.038 0.00
FLOOR 2 EXAM 9 2389.69 2748.15 74.70 0.172 0.198 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00909 28.24 0.01716 0.056 0.00
FLOOR 2 EXAM HALL 1 926.42 1065.38 63.71 0.066 0.076 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00867 28.24 0.01716 0.005 0.00
FLOOR 2 EXAM HALL 2 925.43 1064.24 63.64 0.066 0.076 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00867 28.24 0.01716 0.005 0.00
FLOOR 2 EXAM HALL 3 894.26 1028.40 61.50 0.064 0.074 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00867 28.24 0.01716 0.005 0.00
FLOOR 2 EXAM HALL 4 972.89 1118.83 60.82 0.070 0.080 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00868 28.24 0.01716 0.006 0.00
FLOOR 2 EXAM HALL 5 1004.20 1154.83 62.78 0.072 0.083 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00867 28.24 0.01716 0.006 0.00
FLOOR 2 EXAM HALL 6 1000.02 1150.03 62.52 0.072 0.082 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00867 28.24 0.01716 0.006 0.00
FLOOR 2 JANITOR 371.16 426.84 72.93 0.027 0.031 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 22.20 22.20 0.00877 31.59 0.01716 0.004 0.00
FLOOR 2 LOUNGE 574.07 660.18 88.83 0.041 0.048 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00886 28.24 0.01716 0.005 0.00
FLOOR 2 NURSE STATION 1 906.61 1042.60 74.82 0.065 0.075 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00893 28.24 0.01716 0.011 0.00
FLOOR 2 NURSE STATION 2 1096.08 1260.49 75.38 0.079 0.091 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00892 28.24 0.01716 0.014 0.00
FLOOR 2 OFFICE 3951.48 4544.20 87.35 0.290 0.333 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 22.20 22.20 0.00867 30.46 0.01716 0.022 0.00
FLOOR 2 OFFICE HALL 2150.75 2473.36 59.96 0.154 0.177 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00868 28.24 0.01716 0.013 0.00
FLOOR 2 RECEPTION 6448.75 7416.07 81.12 0.473 0.544 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 22.20 22.20 0.00931 32.53 0.01717 0.098 0.00
FLOOR 2 RECEPTION HALL 2859.07 3287.93 62.75 0.205 0.236 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00867 28.24 0.01716 0.016 0.00
FLOOR 2 RECEPTION TOILET 613.03 704.98 60.23 0.044 0.050 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00868 28.24 0.01716 0.000 0.00
FLOOR 2 SCHEDULING 1 1511.91 1738.70 57.76 0.108 0.124 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00869 28.24 0.01716 0.013 0.00
FLOOR 2 SCHEDULING 2 1608.41 1849.67 58.22 0.115 0.132 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00869 28.24 0.01716 0.014 0.00
FLOOR 2 STORAGE 1 273.56 314.60 60.47 0.020 0.023 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00857 28.24 0.01716 0.003 0.00
FLOOR 2 STORAGE 2 511.02 587.68 52.71 0.037 0.042 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00858 28.24 0.01716 0.007 0.00
FLOOR 2 STORAGE 3 629.66 724.11 54.13 0.045 0.052 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00858 28.24 0.01716 0.008 0.00
FLOOR 2 UTILITY 890.37 1023.92 87.47 0.065 0.075 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 22.20 22.20 0.00860 30.27 0.01716 0.007 0.00
FLOOR 2 WORK 6766.35 7781.31 49.56 0.483 0.555 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00874 28.24 0.01716 0.068 0.00
FLOOR 2 WORK HALL 4067.76 4677.92 60.37 0.291 0.335 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00868 28.24 0.01716 0.024 0.00
FLOOR 2 WORK TOILET 298.78 343.60 68.49 0.021 0.025 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00876 28.24 0.01716 0.000 0.00
FLOOR 2 X-RAY 10916.98 14737.92 176.26 0.791 1.067 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00878 28.24 0.01716 0.127 0.00
FLOOR 3 DRESSING ROOM 287.22 330.30 84.65 0.021 0.024 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00863 28.24 0.01716 0.002 0.00
FLOOR 3 ELEVATOR HALL 1551.11 1783.78 51.89 0.111 0.127 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00873 28.24 0.01716 0.010 0.00
FLOOR 3 HUMID 667.62 767.76 76.52 0.048 0.055 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00864 28.24 0.01716 0.004 0.00
FLOOR 3 JANITOR 369.55 424.98 72.61 0.027 0.031 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 22.20 22.20 0.00881 31.70 0.01716 0.004 0.00
FLOOR 3 LOCKER 889.47 1022.89 91.75 0.064 0.074 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00885 28.24 0.01716 0.008 0.00
FLOOR 3 LOUNGE 4982.16 5729.49 81.25 0.365 0.420 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 22.20 22.20 0.00891 33.14 0.01717 0.048 0.00
FLOOR 3 LOUNGE TOILET 1018.83 1171.65 65.69 0.075 0.086 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 22.20 22.20 0.00873 33.20 0.01717 0.000 0.00
FLOOR 3 MECHANICAL 4333.46 4983.48 153.26 0.318 0.365 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 22.20 22.20 0.00856 30.82 0.01716 0.000 0.00
FLOOR 3 MECHANICAL HALL 1601.57 1841.81 66.08 0.115 0.132 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00866 28.24 0.01716 0.008 0.00
FLOOR 3 OFFICE 13634.88 15680.12 55.59 1.000 1.150 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 22.20 22.20 0.00872 33.09 0.01717 0.122 0.00
FLOOR 3 OFFICE HALL 4005.74 4606.60 59.45 0.287 0.330 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00869 28.24 0.01716 0.024 0.00
FLOOR 3 OFFICE TOILET 296.97 341.52 68.08 0.022 0.025 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 22.20 22.20 0.00877 31.82 0.01716 0.000 0.00
FLOOR 3 PHYSICAL THERAPY 1 9103.22 10468.70 86.68 0.668 0.768 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 22.20 22.20 0.00904 33.14 0.01717 0.184 0.00
FLOOR 3 PHYSICAL THERAPY 2 3354.10 3857.21 70.13 0.241 0.279 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00911 28.24 0.01716 0.084 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 450.93 518.57 66.45 0.032 0.037 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00866 28.24 0.01716 0.000 0.00
FLOOR 3 STORAGE 1 507.71 583.87 58.19 0.036 0.042 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00857 28.24 0.01716 0.006 0.00
FLOOR 3 STORAGE 2 416.96 479.51 61.44 0.030 0.034 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00857 28.24 0.01716 0.005 0.00
FLOOR 3 TREATMENT 2882.97 3315.42 74.97 0.207 0.238 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00907 28.24 0.01716 0.067 0.00
FLOOR 3 UNDEVELOPED 1 11034.60 12689.79 60.23 0.809 0.930 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 22.20 22.20 0.00861 32.93 0.01717 0.128 0.00
FLOOR 3 UNDEVELOPED 2 5790.60 6659.19 62.22 0.425 0.488 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 22.20 22.20 0.00862 32.93 0.01717 0.065 0.00
FLOOR 3 UTILITY 899.04 1033.89 51.52 0.064 0.074 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00858 28.24 0.01716 0.012 0.00
FLOOR 3 WORK 4481.23 5153.42 96.64 0.329 0.378 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 22.20 22.20 0.00866 30.82 0.01716 0.023 0.00
NE STAIR 2400.89 2761.02 176.90 0.176 0.202 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:10:00 22.20 22.20 0.00878 32.42 0.01717 0.005 0.00
NW ELEVATOR 1993.43 2292.44 176.25 0.146 0.168 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 22.20 22.20 0.00872 31.82 0.01716 0.000 0.00
NW STAIR 2775.93 3192.32 178.97 0.204 0.234 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 22.20 22.20 0.00877 32.04 0.01717 0.005 0.00
SW STAIR 1442.42 1658.78 185.99 0.106 0.122 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 22.20 22.20 0.00876 32.26 0.01717 0.003 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
FLOOR 1 ANESTHESIA 64.38 80.47 8.02 0.005 0.015 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00944 8.70 0.00699 0.015 0.00
FLOOR 1 BIO HAZ 68.34 85.43 16.42 0.005 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00815 8.70 0.00699 0.003 0.00
FLOOR 1 CAFE 0.00 0.00 0.00 0.000 0.184   00:10:00 18.30 20.09 0.01335 8.70 0.00699 0.184 0.00
FLOOR 1 CLEAN 0.00 0.00 0.00 0.000 0.018   00:10:00 18.30 24.60 0.01179 8.70 0.00699 0.018 0.00
FLOOR 1 CLEAN WORK 0.00 0.00 0.00 0.000 0.023   00:10:00 18.30 23.94 0.01180 8.70 0.00699 0.023 0.00
FLOOR 1 DICTATION 0.00 0.00 0.00 0.000 0.005   00:10:00 18.30 24.12 0.00935 8.70 0.00699 0.005 0.00
FLOOR 1 DRESSING ROOM 103.45 129.31 30.93 0.007 0.009 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00779 8.70 0.00699 0.002 0.00
FLOOR 1 ELECTRICAL ROOM 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
FLOOR 1 ELEVATOR PUMP ROOM 33.38 41.72 4.94 0.002 0.003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00725 8.70 0.00699 0.000 0.00
FLOOR 1 HUMID 0.00 0.00 0.00 0.000 0.002   00:10:00 18.30 24.22 0.00932 8.70 0.00699 0.002 0.00
FLOOR 1 IT HALL 0.00 0.00 0.00 0.000 0.004   00:10:00 18.30 21.59 0.01627 8.70 0.00699 0.004 0.00
FLOOR 1 IT ROOM 0.00 0.00 0.00 0.000 0.004   00:10:00 18.30 21.56 0.01624 8.70 0.00699 0.004 0.00
FLOOR 1 LOBBY 265.25 331.56 5.74 0.019 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.01032 8.70 0.00699 0.032 0.00
FLOOR 1 LOBBY HALL 0.00 0.00 0.00 0.000 0.007   00:10:00 18.30 22.41 0.01004 8.70 0.00699 0.007 0.00
FLOOR 1 LOBBY TOILET 84.20 105.25 20.98 0.006 0.008 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00778 8.70 0.00699 0.000 0.00
FLOOR 1 LOCKER ROOM 0.00 0.00 0.00 0.000 0.042   00:10:00 18.30 23.01 0.01012 8.70 0.00699 0.042 0.00
FLOOR 1 LOCKER ROOM HALL 0.00 0.00 0.00 0.000 0.014   00:10:00 18.30 22.86 0.00973 8.70 0.00699 0.014 0.00
FLOOR 1 LOUNGE 0.00 0.00 0.00 0.000 0.023   00:10:00 18.30 23.64 0.01096 8.70 0.00699 0.023 0.00
FLOOR 1 MED GAS 324.75 405.94 78.03 0.023 0.029 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00799 8.70 0.00699 0.003 0.00
FLOOR 1 MRI CONTROL ROOM 0.00 0.00 0.00 0.000 0.024   00:10:00 18.30 24.91 0.00893 8.70 0.00699 0.024 0.00
FLOOR 1 MRI HALL 0.00 0.00 0.00 0.000 0.004   00:10:00 18.30 22.28 0.01041 8.70 0.00699 0.004 0.00
FLOOR 1 MRI ROOM 0.00 0.00 0.00 0.000 0.062   00:10:00 18.30 25.00 0.00850 8.70 0.00699 0.062 0.00
FLOOR 1 MRI TOILET 14.95 18.69 3.73 0.001 0.001 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00764 8.70 0.00699 0.000 0.00
FLOOR 1 NOURISHMENT 0.00 0.00 0.00 0.000 0.014   00:10:00 18.30 24.64 0.01097 8.70 0.00699 0.014 0.00
FLOOR 1 NURSE HALL 0.00 0.00 0.00 0.000 0.014   00:10:00 18.30 22.04 0.01240 8.70 0.00699 0.014 0.00
FLOOR 1 NURSE JANITOR 0.00 0.00 0.00 0.000 0.003   00:10:00 18.30 23.54 0.00887 8.70 0.00699 0.003 0.00
FLOOR 1 NURSE STATION 0.00 0.00 0.00 0.000 0.020   00:10:00 18.30 23.67 0.01100 8.70 0.00699 0.020 0.00
FLOOR 1 NURSE TOILET 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
FLOOR 1 OFFICE 0.00 0.00 0.00 0.000 0.019   00:10:00 18.30 22.90 0.00953 8.70 0.00699 0.019 0.00
FLOOR 1 OPERATING ROOM 1 17.42 21.77 0.51 0.001 0.239 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:10:00 18.10 18.83 0.00786 8.70 0.00699 0.239 0.00
FLOOR 1 OPERATING ROOM 2 23.35 29.19 0.65 0.002 0.249 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:10:00 18.10 18.95 0.00823 8.70 0.00699 0.249 0.00
FLOOR 1 OPERATING ROOM 3 22.73 28.41 0.64 0.002 0.247 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:10:00 18.10 18.95 0.00852 8.70 0.00699 0.247 0.00
FLOOR 1 PACU 0.00 0.00 0.00 0.000 0.032   00:10:00 18.30 23.99 0.01172 8.70 0.00699 0.032 0.00
FLOOR 1 PRE-OP HALL 0.00 0.00 0.00 0.000 0.015   00:10:00 18.30 22.51 0.01004 8.70 0.00699 0.015 0.00
FLOOR 1 PRE-OP ROOM 1 0.00 0.00 0.00 0.000 0.052   00:10:00 18.30 22.81 0.00977 8.70 0.00699 0.052 0.00
FLOOR 1 PRE-OP ROOM 2 0.00 0.00 0.00 0.000 0.093   00:10:00 18.30 24.47 0.01018 8.70 0.00699 0.093 0.00
FLOOR 1 PRE-OP TOILET 70.71 88.39 17.62 0.005 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00774 8.70 0.00699 0.000 0.00
FLOOR 1 PROCEDURE ROOM 0.00 0.00 0.00 0.000 0.108   00:10:00 18.30 21.40 0.01011 8.70 0.00699 0.108 0.00
FLOOR 1 RECEPTION 0.00 0.00 0.00 0.000 0.050   00:10:00 18.30 21.90 0.01318 8.70 0.00699 0.050 0.00
FLOOR 1 RECEPTION HALL 0.00 0.00 0.00 0.000 0.004   00:10:00 18.30 22.60 0.00989 8.70 0.00699 0.004 0.00
FLOOR 1 RECOVERY ROOM 55.07 68.84 1.37 0.004 0.161 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 21.10 21.19 0.00954 8.70 0.00699 0.161 0.00
FLOOR 1 SCHEDULING 0.00 0.00 0.00 0.000 0.005   00:10:00 18.30 21.73 0.00883 8.70 0.00699 0.005 0.00
FLOOR 1 SCRUB 35.71 44.64 5.72 0.003 0.003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00944 8.70 0.00699 0.002 0.00
FLOOR 1 SOIL 0.00 0.00 0.00 0.000 0.018   00:10:00 18.30 24.33 0.01178 8.70 0.00699 0.018 0.00
FLOOR 1 SOIL HOLD 0.00 0.00 0.00 0.000 0.008   00:10:00 18.30 21.47 0.01371 8.70 0.00699 0.008 0.00
FLOOR 1 SOIL WORK 0.00 0.00 0.00 0.000 0.025   00:10:00 18.30 23.47 0.01183 8.70 0.00699 0.025 0.00
FLOOR 1 STEP DOWN 294.49 368.11 13.21 0.021 0.090 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00836 8.70 0.00699 0.090 0.00
FLOOR 1 STERILE HALL 0.00 0.00 0.00 0.000 0.017   00:10:00 18.30 21.20 0.01587 8.70 0.00699 0.017 0.00
FLOOR 1 STERILE STORAGE 0.00 0.00 0.00 0.000 0.022   00:10:00 18.30 23.22 0.00895 8.70 0.00699 0.022 0.00
FLOOR 1 STORAGE 2654.51 3318.14 38.82 0.188 0.235 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00798 8.70 0.00699 0.052 0.00
FLOOR 1 SUB-STERILE 445.39 556.74 30.58 0.032 0.040 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00790 8.70 0.00699 0.006 0.00
FLOOR 1 UTILITY HALL 841.90 1052.37 44.25 0.060 0.075 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00802 8.70 0.00699 0.007 0.00
FLOOR 1 UTILITY JANITOR 14.63 18.29 4.69 0.001 0.002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00875 8.70 0.00699 0.002 0.00
FLOOR 1 UTILITY ROOM 764.88 956.09 28.59 0.054 0.068 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00787 8.70 0.00699 0.020 0.00
FLOOR 1 VESTIBULE 93.06 116.32 17.39 0.007 0.008 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00773 8.70 0.00699 0.002 0.00
FLOOR 2 CONFERENCE 892.25 1115.31 35.73 0.063 0.079 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00856 8.70 0.00699 0.049 0.00
FLOOR 2 CONFERENCE TOILET 38.99 48.74 8.20 0.003 0.004 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.01009 8.70 0.00699 0.000 0.00
FLOOR 2 DICTATION 0.00 0.00 0.00 0.000 0.003   00:10:00 18.30 22.22 0.00996 8.70 0.00699 0.003 0.00
FLOOR 2 EXAM 1 850.18 1062.72 31.78 0.060 0.075 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00812 8.70 0.00699 0.051 0.00
FLOOR 2 EXAM 2 25.60 32.00 0.64 0.002 0.076 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 21.10 21.13 0.01176 8.70 0.00699 0.076 0.00
FLOOR 2 EXAM 3 26.47 33.09 0.49 0.002 0.102 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 21.10 21.15 0.01175 8.70 0.00699 0.102 0.00
FLOOR 2 EXAM 4 230.34 287.92 36.89 0.016 0.021 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00810 8.70 0.00699 0.012 0.00
FLOOR 2 EXAM 5 741.48 926.85 28.50 0.052 0.065 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00815 8.70 0.00699 0.050 0.00
FLOOR 2 EXAM 6 319.76 399.70 19.12 0.023 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00823 8.70 0.00699 0.032 0.00
FLOOR 2 EXAM 7 0.00 0.00 0.00 0.000 0.112   00:10:00 18.30 21.02 0.01411 8.70 0.00699 0.112 0.00
FLOOR 2 EXAM 8 240.23 300.29 11.97 0.017 0.038 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00845 8.70 0.00699 0.038 0.00
FLOOR 2 EXAM 9 0.00 0.00 0.00 0.000 0.056   00:10:00 18.30 20.97 0.01408 8.70 0.00699 0.056 0.00
FLOOR 2 EXAM HALL 1 167.60 209.50 12.53 0.012 0.015 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00874 8.70 0.00699 0.005 0.00
FLOOR 2 EXAM HALL 2 41.72 52.15 3.12 0.003 0.005 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.01457 8.70 0.00699 0.005 0.00
FLOOR 2 EXAM HALL 3 63.30 79.13 4.73 0.005 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.01299 8.70 0.00699 0.005 0.00
FLOOR 2 EXAM HALL 4 1.99 2.49 0.14 0.000 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 21.10 21.12 0.01567 8.70 0.00699 0.006 0.00
FLOOR 2 EXAM HALL 5 0.00 0.00 0.00 0.000 0.006   00:10:00 18.30 21.30 0.01597 8.70 0.00699 0.006 0.00
FLOOR 2 EXAM HALL 6 6.92 8.65 0.47 0.001 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00 21.10 21.10 0.01559 8.70 0.00699 0.006 0.00
FLOOR 2 JANITOR 246.12 307.65 52.56 0.018 0.022 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00793 8.70 0.00699 0.004 0.00
FLOOR 2 LOUNGE 0.00 0.00 0.00 0.000 0.005   00:10:00 18.30 22.59 0.01095 8.70 0.00699 0.005 0.00
FLOOR 2 NURSE STATION 1 0.00 0.00 0.00 0.000 0.011   00:10:00 18.30 22.37 0.01122 8.70 0.00699 0.011 0.00
FLOOR 2 NURSE STATION 2 0.00 0.00 0.00 0.000 0.014   00:10:00 18.30 22.53 0.01117 8.70 0.00699 0.014 0.00
FLOOR 2 OFFICE 1367.68 1709.60 32.86 0.096 0.120 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00793 8.70 0.00699 0.022 0.00
FLOOR 2 OFFICE HALL 278.89 348.61 8.45 0.020 0.025 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00971 8.70 0.00699 0.013 0.00
FLOOR 2 RECEPTION 927.99 1159.99 12.69 0.066 0.098 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00960 8.70 0.00699 0.098 0.00
FLOOR 2 RECEPTION HALL 0.00 0.00 0.00 0.000 0.016   00:10:00 18.30 22.27 0.01070 8.70 0.00699 0.016 0.00
FLOOR 2 RECEPTION TOILET 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
FLOOR 2 SCHEDULING 1 0.00 0.00 0.00 0.000 0.013   00:10:00 18.30 22.76 0.00954 8.70 0.00699 0.013 0.00
FLOOR 2 SCHEDULING 2 0.00 0.00 0.00 0.000 0.014   00:10:00 18.30 22.70 0.00958 8.70 0.00699 0.014 0.00
FLOOR 2 STORAGE 1 32.91 41.14 7.91 0.002 0.003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00855 8.70 0.00699 0.003 0.00
FLOOR 2 STORAGE 2 17.10 21.38 1.92 0.001 0.007 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.01304 8.70 0.00699 0.007 0.00
FLOOR 2 STORAGE 3 0.00 0.00 0.00 0.000 0.008   00:10:00 18.30 21.37 0.01604 8.70 0.00699 0.008 0.00
FLOOR 2 UTILITY 415.18 518.98 44.34 0.030 0.037 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00796 8.70 0.00699 0.007 0.00
FLOOR 2 WORK 0.00 0.00 0.00 0.000 0.068   00:10:00 18.30 21.22 0.01273 8.70 0.00699 0.068 0.00
FLOOR 2 WORK HALL 0.00 0.00 0.00 0.000 0.024   00:10:00 18.30 22.00 0.01525 8.70 0.00699 0.024 0.00
FLOOR 2 WORK TOILET 159.13 198.92 39.65 0.011 0.014 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00788 8.70 0.00699 0.000 0.00
FLOOR 2 X-RAY 0.00 0.00 0.00 0.000 0.127   00:10:00 18.30 25.00 0.00850 8.70 0.00699 0.127 0.00
FLOOR 3 DRESSING ROOM 0.00 0.00 0.00 0.000 0.002   00:10:00 18.30 21.80 0.01168 8.70 0.00699 0.002 0.00
FLOOR 3 ELEVATOR HALL 666.30 832.87 24.23 0.047 0.059 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00812 8.70 0.00699 0.010 0.00
FLOOR 3 HUMID 0.00 0.00 0.00 0.000 0.004   00:10:00 18.30 21.89 0.01035 8.70 0.00699 0.004 0.00
FLOOR 3 JANITOR 334.99 418.74 71.54 0.024 0.030 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00797 8.70 0.00699 0.004 0.00
FLOOR 3 LOCKER 4.44 5.55 0.50 0.000 0.008 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 21.10 21.21 0.01150 8.70 0.00699 0.008 0.00
FLOOR 3 LOUNGE 99.58 124.47 1.77 0.007 0.048 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 21.10 21.17 0.00918 8.70 0.00699 0.048 0.00
FLOOR 3 LOUNGE TOILET 546.22 682.78 38.28 0.039 0.048 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00798 8.70 0.00699 0.000 0.00
FLOOR 3 MECHANICAL 6.22 7.78 0.24 0.000 0.001 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 21.10 21.29 0.00727 8.70 0.00699 0.000 0.00
FLOOR 3 MECHANICAL HALL 441.53 551.91 19.80 0.032 0.039 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00846 8.70 0.00699 0.008 0.00
FLOOR 3 OFFICE 3892.31 4865.39 17.25 0.273 0.341 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00803 8.70 0.00699 0.122 0.00
FLOOR 3 OFFICE HALL 1132.72 1415.90 18.27 0.081 0.101 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00832 8.70 0.00699 0.024 0.00
FLOOR 3 OFFICE TOILET 230.17 287.71 57.35 0.016 0.021 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 8.70 0.00699 0.000 0.00
FLOOR 3 PHYSICAL THERAPY 1 3112.93 3891.17 32.22 0.219 0.273 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00821 8.70 0.00699 0.184 0.00
FLOOR 3 PHYSICAL THERAPY 2 23.91 29.88 0.54 0.002 0.084 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 21.10 21.19 0.01535 8.70 0.00699 0.084 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
FLOOR 3 STORAGE 1 69.32 86.65 8.64 0.005 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00857 8.70 0.00699 0.006 0.00
FLOOR 3 STORAGE 2 105.43 131.78 16.89 0.008 0.009 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00823 8.70 0.00699 0.005 0.00
FLOOR 3 TREATMENT 0.00 0.00 0.00 0.000 0.067   00:10:00 18.30 21.22 0.01524 8.70 0.00699 0.067 0.00
FLOOR 3 UNDEVELOPED 1 3701.62 4627.03 21.96 0.258 0.322 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00783 8.70 0.00699 0.128 0.00
FLOOR 3 UNDEVELOPED 2 2678.81 3348.51 31.29 0.188 0.235 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00793 8.70 0.00699 0.065 0.00
FLOOR 3 UTILITY 147.09 183.86 9.16 0.011 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00835 8.70 0.00699 0.012 0.00
FLOOR 3 WORK 1707.84 2134.81 40.03 0.121 0.151 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00801 8.70 0.00699 0.023 0.00
NE STAIR 2068.72 2585.90 165.68 0.148 0.185 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00797 8.70 0.00699 0.005 0.00
NW ELEVATOR 1271.55 1589.44 122.20 0.090 0.113 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00792 8.70 0.00699 0.000 0.00
NW STAIR 2003.98 2504.97 140.43 0.142 0.178 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00796 8.70 0.00699 0.005 0.00
SW STAIR 989.43 1236.79 138.67 0.070 0.088 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00795 8.70 0.00699 0.003 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
AHU-1 5.54 5.54 1.46 1.46 5.5424 3.5281 5.5424 0.6366 1.0000
AHU-2 6.05 6.05 0.00 0.00 6.0520 3.1847 6.0520 0.5262 1.0000
AHU-3 5.77 5.77 0.00 0.00 5.7700 2.5291 5.7700 0.4383 1.0000
PSZ_CAFE 0.36 0.36 0.18 0.18 0.3593 0.3593 0.3593 1.0000 1.0000
PSZ_ELEVATOR 0.10 0.10 0.00 0.00 0.0966 0.0966 0.0966 1.0000 1.0000
PSZ_MRI_CONTROL 0.19 0.19 0.02 0.02 0.1939 0.1939 0.1939 1.0000 1.0000
PSZ_MRI 0.46 0.46 0.06 0.06 0.4648 0.4648 0.4648 1.0000 1.0000
PSZ_OR_1 0.72 0.72 0.24 0.24 0.7236 0.7236 0.7236 1.0000 1.0000
PSZ_OR_2 0.76 0.76 0.25 0.25 0.7551 0.7551 0.7551 1.0000 1.0000
PSZ_OR_3 0.75 0.75 0.25 0.25 0.7488 0.7488 0.7488 1.0000 1.0000
PSZ_XRAY 1.07 1.07 0.13 0.13 1.0673 1.0673 1.0673 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 2984.583 2984.583 0.065420 0.00002611 49.414 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2984.58 2984.58 0.065420 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00944370 60.4636 80.47 0.00 3147.73 3147.73
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 BIO HAZ VAV BOX 358.552 358.552 0.006167 0.00000314 6.484 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 358.55 358.55 0.006167 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00815494 52.3206 85.43 0.00 378.06 378.06
FLOOR 1 CLEAN VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 CLEAN VAV BOX 3233.655 3233.655 0.073036 0.00002829 53.097   1/21 00:10:00   1/21 00:10:00 3233.65 3233.65 0.073036 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 3410.72 3410.72
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 CLEAN WORK VAV BOX 4046.692 4046.692 0.091400 0.00003540 66.447   1/21 00:10:00   1/21 00:10:00 4046.69 4046.69 0.091400 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 4268.28 4268.28
FLOOR 1 DICTATION VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 DICTATION VAV BOX 243.272 243.272 0.005495 0.00000213 3.995   1/21 00:10:00   1/21 00:10:00 243.27 243.27 0.005495 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 256.59 256.59
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 DRESSING ROOM VAV BOX 540.493 540.493 0.009291 0.00000473 9.777 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 540.49 540.49 0.009291 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00779158 50.0202 129.31 0.00 569.91 569.91
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 ELECTRICAL ROOM VAV BOX 606.018 606.018 0.013688 0.00000530 9.951   1/21 00:10:00   1/21 00:10:00 606.02 606.02 0.013688 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 639.20 639.20
FLOOR 1 HUMID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 HUMID VAV BOX 120.592 120.592 0.002724 0.00000105 1.980   1/21 00:10:00   1/21 00:10:00 120.59 120.59 0.002724 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 127.19 127.19
FLOOR 1 IT HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 IT HALL VAV BOX 439.768 439.768 0.009933 0.00000385 7.221   1/21 00:10:00   1/21 00:10:00 439.77 439.77 0.009933 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 463.85 463.85
FLOOR 1 IT ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 IT ROOM VAV BOX 211.240 211.240 0.004771 0.00000185 3.469   1/21 00:10:00   1/21 00:10:00 211.24 211.24 0.004771 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 222.81 222.81
FLOOR 1 LOBBY VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOBBY VAV BOX 3473.855 3473.855 0.070672 0.00003039 58.852 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3473.85 3473.85 0.070672 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.01031892 65.9752 331.56 0.00 3663.62 3663.62
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOBBY HALL VAV BOX 802.973 802.973 0.018136 0.00000702 13.185   1/21 00:10:00   1/21 00:10:00 802.97 802.97 0.018136 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 846.94 846.94
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 1397.236 1397.236 0.029193 0.00001222 23.469 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1397.24 1397.24 0.029193 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00777643 49.9236 105.25 0.00 1473.58 1473.58
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOCKER ROOM VAV BOX 3004.148 3004.148 0.067852 0.00002628 49.328   1/21 00:10:00   1/21 00:10:00 3004.15 3004.15 0.067852 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 3168.64 3168.64
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOCKER ROOM HALL VAV BOX 1355.383 1355.383 0.030613 0.00001186 22.255   1/21 00:10:00   1/21 00:10:00 1355.38 1355.38 0.030613 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1429.60 1429.60
FLOOR 1 LOUNGE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOUNGE VAV BOX 1636.049 1636.049 0.036952 0.00001431 26.864   1/21 00:10:00   1/21 00:10:00 1636.05 1636.05 0.036952 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1725.63 1725.63
FLOOR 1 MED GAS VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 MED GAS VAV BOX 1696.298 1696.298 0.029145 0.00001484 30.691 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1696.30 1696.30 0.029145 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00798848 51.2669 405.94 0.00 1788.61 1788.61
FLOOR 1 MRI HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 MRI HALL VAV BOX 537.205 537.205 0.012133 0.00000470 8.821   1/21 00:10:00   1/21 00:10:00 537.20 537.20 0.012133 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 566.62 566.62
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 1138.284 1138.284 0.025304 0.00000996 18.771 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1138.28 1138.28 0.025304 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00763784 49.0439 18.69 0.00 1200.52 1200.52
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NOURISHMENT VAV BOX 851.924 851.924 0.019242 0.00000745 13.989   1/21 00:10:00   1/21 00:10:00 851.92 851.92 0.019242 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 898.57 898.57
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NURSE HALL VAV BOX 1508.782 1508.782 0.034078 0.00001320 24.774   1/21 00:10:00   1/21 00:10:00 1508.78 1508.78 0.034078 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1591.40 1591.40
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NURSE JANITOR VAV BOX 190.140 190.140 0.004295 0.00000166 3.122   1/21 00:10:00   1/21 00:10:00 190.14 190.14 0.004295 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 200.55 200.55
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NURSE STATION VAV BOX 1126.945 1126.945 0.025453 0.00000986 18.504   1/21 00:10:00   1/21 00:10:00 1126.94 1126.94 0.025453 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1188.65 1188.65
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 1077.003 1077.003 0.024325 0.00000942 17.684   1/21 00:10:00   1/21 00:10:00 1077.00 1077.00 0.024325 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1135.98 1135.98
FLOOR 1 OFFICE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 OFFICE VAV BOX 757.354 757.354 0.017106 0.00000663 12.436   1/21 00:10:00   1/21 00:10:00 757.35 757.35 0.017106 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 798.82 798.82
FLOOR 1 PACU VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PACU VAV BOX 2857.460 2857.460 0.064539 0.00002500 46.920   1/21 00:10:00   1/21 00:10:00 2857.46 2857.46 0.064539 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 3013.92 3013.92
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PRE-OP HALL VAV BOX 1548.169 1548.169 0.034967 0.00001354 25.421   1/21 00:10:00   1/21 00:10:00 1548.17 1548.17 0.034967 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1632.94 1632.94
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PRE-OP ROOM 1 VAV BOX 3948.973 3948.973 0.089192 0.00003455 64.842   1/21 00:10:00   1/21 00:10:00 3948.97 3948.97 0.089192 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 4165.21 4165.21
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PRE-OP ROOM 2 VAV BOX 7062.184 7062.184 0.159508 0.00006178 115.961   1/21 00:10:00   1/21 00:10:00 7062.18 7062.18 0.159508 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 7448.89 7448.89
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 1179.927 1179.927 0.024665 0.00001032 19.816 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1179.93 1179.93 0.024665 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00774375 49.7163 88.39 0.00 1244.39 1244.39
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PROCEDURE ROOM VAV BOX 14887.001 14887.001 0.336241 0.00013024 244.445   1/21 00:10:00   1/21 00:10:00 14887.00 14887.00 0.336241 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 15702.16 15702.16
FLOOR 1 RECEPTION VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 RECEPTION VAV BOX 2391.089 2391.089 0.054006 0.00002092 39.262   1/21 00:10:00   1/21 00:10:00 2391.09 2391.09 0.054006 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 2522.02 2522.02
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 RECEPTION HALL VAV BOX 410.294 410.294 0.009267 0.00000359 6.737   1/21 00:10:00   1/21 00:10:00 410.29 410.29 0.009267 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 432.76 432.76
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 RECOVERY ROOM VAV BOX 12957.096 12957.096 0.289581 0.00011335 213.351 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 12957.10 12957.10 0.289581 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.19 0.00954189 60.7586 68.84 0.00 13665.57 13665.57
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 SCHEDULING VAV BOX 231.801 231.801 0.005236 0.00000203 3.806   1/21 00:10:00   1/21 00:10:00 231.80 231.80 0.005236 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 244.49 244.49
FLOOR 1 SCRUB VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 SCRUB VAV BOX 324.169 324.169 0.006297 0.00000284 5.580 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 324.17 324.17 0.006297 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00943938 60.4368 44.64 0.00 341.85 341.85
FLOOR 1 SOIL VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 3231.282 3231.282 0.072983 0.00002827 53.058   1/21 00:10:00   1/21 00:10:00 3231.28 3231.28 0.072983 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 3408.22 3408.22
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 1507.492 1507.492 0.034049 0.00001319 24.753   1/21 00:10:00   1/21 00:10:00 1507.49 1507.49 0.034049 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1590.04 1590.04
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 4292.366 4292.366 0.096948 0.00003755 70.481   1/21 00:10:00   1/21 00:10:00 4292.37 4292.37 0.096948 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 4527.40 4527.40
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STEP DOWN VAV BOX 6858.705 6858.705 0.146501 0.00006000 114.423 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6858.70 6858.70 0.146501 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00836020 53.6198 368.11 0.00 7233.52 7233.52
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STERILE HALL VAV BOX 1734.971 1734.971 0.039186 0.00001518 28.488   1/21 00:10:00   1/21 00:10:00 1734.97 1734.97 0.039186 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1829.97 1829.97
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STERILE STORAGE VAV BOX 976.728 976.728 0.022061 0.00000854 16.038   1/21 00:10:00   1/21 00:10:00 976.73 976.73 0.022061 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1030.21 1030.21
FLOOR 1 STORAGE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STORAGE VAV BOX 13705.005 13705.005 0.234608 0.00011990 248.381 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13705.00 13705.00 0.234608 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00798233 51.2279 3318.14 0.00 14450.83 14450.83
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 SUB-STERILE VAV BOX 2306.240 2306.240 0.039522 0.00002018 41.776 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2306.24 2306.24 0.039522 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00789641 50.6841 556.74 0.00 2431.75 2431.75
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 UTILITY HALL VAV BOX 4362.061 4362.061 0.074751 0.00003816 79.016 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4362.06 4362.06 0.074751 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00801554 51.4381 1052.37 0.00 4599.44 4599.44
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 UTILITY JANITOR VAV BOX 168.075 168.075 0.003379 0.00000147 2.859 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 168.08 168.08 0.003379 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00874735 56.0684 18.29 0.00 177.26 177.26
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 UTILITY ROOM VAV BOX 3948.422 3948.422 0.067602 0.00003454 71.553 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3948.42 3948.42 0.067602 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00787230 50.5313 956.09 0.00 4163.30 4163.30
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 VESTIBULE VAV BOX 487.536 487.536 0.008389 0.00000427 8.815 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 487.54 487.54 0.008389 -15.00 -15.00 0.00700000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00772817 49.6176 116.32 0.00 514.07 514.07
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 CONFERENCE VAV BOX 5025.868 5025.868 0.088233 0.00004397 89.997 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5025.87 5025.87 0.088233 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00855514 54.8506 1115.31 0.00 5299.43 5299.43
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 1271.201 1271.201 0.027505 0.00001112 21.117 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1271.20 1271.20 0.027505 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.01009146 64.5431 48.74 0.00 1340.68 1340.68
FLOOR 2 DICTATION VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 DICTATION VAV BOX 437.896 437.896 0.009890 0.00000383 7.187   1/21 00:10:00   1/21 00:10:00 437.90 437.90 0.009890 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 461.87 461.87
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 1 VAV BOX 6932.622 6932.622 0.132550 0.00006065 119.954 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6932.62 6932.62 0.132550 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00811736 52.0828 1062.72 0.00 7310.65 7310.65
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 2 VAV BOX 11401.038 11401.038 0.254836 0.00009974 187.647 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 11401.04 11401.04 0.254836 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.13 0.01175940 74.8871 32.00 0.00 12024.45 12024.45
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 3 VAV BOX 15200.519 15200.519 0.339781 0.00013298 250.178 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 15200.52 15200.52 0.339781 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.15 0.01174740 74.7131 33.09 0.00 16031.68 16031.68
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 4 VAV BOX 1719.543 1719.543 0.032329 0.00001504 29.942 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1719.54 1719.54 0.032329 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00810092 51.9789 287.92 0.00 1813.29 1813.29
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 5 VAV BOX 8664.006 8664.006 0.174703 0.00007580 147.144 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8664.01 8664.01 0.174703 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00815458 52.3184 926.85 0.00 9137.26 9137.26
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 6 VAV BOX 5345.069 5345.069 0.111650 0.00004676 89.745 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5345.07 5345.07 0.111650 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00823071 52.8003 399.70 0.00 5637.11 5637.11
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 7 VAV BOX 16548.077 16548.077 0.373759 0.00014477 271.612   1/21 00:10:00   1/21 00:10:00 16548.08 16548.08 0.373759 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 17454.20 17454.20
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 8 VAV BOX 6223.750 6223.750 0.133678 0.00005445 103.612 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6223.75 6223.75 0.133678 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00844861 54.1791 300.29 0.00 6563.89 6563.89
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 9 VAV BOX 8748.544 8748.544 0.197597 0.00007654 143.594   1/21 00:10:00   1/21 00:10:00 8748.54 8748.54 0.197597 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 9227.59 9227.59
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 1 VAV BOX 1225.197 1225.197 0.022910 0.00001072 21.379 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1225.20 1225.20 0.022910 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00873585 55.9945 209.50 0.00 1291.99 1291.99
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 2 VAV BOX 1077.552 1077.552 0.022885 0.00000943 18.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1077.55 1077.55 0.022885 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.01457397 92.5548 52.15 0.00 1136.44 1136.44
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 3 VAV BOX 1066.724 1066.724 0.022104 0.00000933 17.956 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1066.72 1066.72 0.022104 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.01299434 82.7273 79.13 0.00 1125.00 1125.00
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 4 VAV BOX 1082.640 1082.640 0.024044 0.00000947 17.851 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 1082.64 1082.64 0.024044 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.12 0.01566637 99.1834 2.49 0.00 1141.83 1141.83
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 5 VAV BOX 1099.293 1099.293 0.024829 0.00000962 18.043   1/21 00:10:00   1/21 00:10:00 1099.29 1099.29 0.024829 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1159.49 1159.49
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 6 VAV BOX 1118.462 1118.462 0.024724 0.00000978 18.466 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00 1118.46 1118.46 0.024724 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.01559387 98.8807 8.65 0.00 1179.61 1179.61
FLOOR 2 JANITOR VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 JANITOR VAV BOX 1279.732 1279.732 0.021959 0.00001120 23.152 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1279.73 1279.73 0.021959 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00793061 50.9009 307.65 0.00 1349.38 1349.38
FLOOR 2 LOUNGE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 LOUNGE VAV BOX 632.082 632.082 0.014276 0.00000553 10.375   1/21 00:10:00   1/21 00:10:00 632.08 632.08 0.014276 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 666.69 666.69
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 NURSE STATION 1 VAV BOX 995.705 995.705 0.022489 0.00000871 16.343   1/21 00:10:00   1/21 00:10:00 995.70 995.70 0.022489 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1050.23 1050.23
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 NURSE STATION 2 VAV BOX 1203.916 1203.916 0.027192 0.00001053 19.761   1/21 00:10:00   1/21 00:10:00 1203.92 1203.92 0.027192 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1269.84 1269.84
FLOOR 2 OFFICE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 OFFICE VAV BOX 7038.079 7038.079 0.120366 0.00006157 127.524 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 7038.08 7038.08 0.120366 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00793304 50.9160 1709.60 0.00 7421.09 7421.09
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 OFFICE HALL VAV BOX 2708.829 2708.829 0.053141 0.00002370 46.437 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2708.83 2708.83 0.053141 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00971169 62.1521 348.61 0.00 2856.58 2856.58
FLOOR 2 RECEPTION VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 RECEPTION VAV BOX 8937.709 8937.709 0.175152 0.00007819 153.275 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8937.71 8937.71 0.175152 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00960215 61.4603 1159.99 0.00 9425.20 9425.20
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 RECEPTION HALL VAV BOX 3129.374 3129.374 0.070681 0.00002738 51.364   1/21 00:10:00   1/21 00:10:00 3129.37 3129.37 0.070681 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 3300.73 3300.73
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 2235.501 2235.501 0.050492 0.00001956 36.692   1/21 00:10:00   1/21 00:10:00 2235.50 2235.50 0.050492 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 2357.91 2357.91
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 SCHEDULING 1 VAV BOX 1652.432 1652.432 0.037322 0.00001446 27.122   1/21 00:10:00   1/21 00:10:00 1652.43 1652.43 0.037322 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1742.91 1742.91
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 SCHEDULING 2 VAV BOX 1758.099 1758.099 0.039709 0.00001538 28.857   1/21 00:10:00   1/21 00:10:00 1758.10 1758.10 0.039709 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1854.37 1854.37
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 STORAGE 1 VAV BOX 340.792 340.792 0.006761 0.00000298 5.819 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 340.79 340.79 0.006761 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00854614 54.7960 41.14 0.00 359.38 359.38
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 STORAGE 2 VAV BOX 584.137 584.137 0.012595 0.00000511 9.714 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 584.14 584.14 0.012595 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.01303855 83.0074 21.38 0.00 616.06 616.06
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 STORAGE 3 VAV BOX 687.420 687.420 0.015526 0.00000601 11.283   1/21 00:10:00   1/21 00:10:00 687.42 687.42 0.015526 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 725.06 725.06
FLOOR 2 UTILITY VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 UTILITY VAV BOX 2152.671 2152.671 0.036902 0.00001883 38.962 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2152.67 2152.67 0.036902 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00795936 51.0827 518.98 0.00 2269.82 2269.82
FLOOR 2 WORK VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 WORK VAV BOX 7371.030 7371.030 0.166484 0.00006448 120.985   1/21 00:10:00   1/21 00:10:00 7371.03 7371.03 0.166484 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 7774.65 7774.65
FLOOR 2 WORK HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 WORK HALL VAV BOX 4449.825 4449.825 0.100505 0.00003893 73.037   1/21 00:10:00   1/21 00:10:00 4449.83 4449.83 0.100505 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 4693.48 4693.48
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 1290.810 1290.810 0.024667 0.00001129 22.339 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1290.81 1290.81 0.024667 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00788230 50.5950 198.92 0.00 1361.20 1361.20
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 DRESSING ROOM VAV BOX 315.983 315.983 0.007137 0.00000276 5.186   1/21 00:10:00   1/21 00:10:00 315.98 315.98 0.007137 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 333.29 333.29
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 ELEVATOR HALL VAV BOX 3443.326 3443.326 0.058948 0.00003012 62.361 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3443.33 3443.33 0.058948 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00811683 52.0792 832.87 0.00 3630.71 3630.71
FLOOR 3 HUMID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 HUMID VAV BOX 733.316 733.316 0.016563 0.00000642 12.036   1/21 00:10:00   1/21 00:10:00 733.32 733.32 0.016563 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 773.47 773.47
FLOOR 3 JANITOR VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 JANITOR VAV BOX 1747.866 1747.866 0.030022 0.00001529 31.607 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1747.87 1747.87 0.030022 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00797146 51.1592 418.74 0.00 1842.99 1842.99
FLOOR 3 LOCKER VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 LOCKER VAV BOX 994.392 994.392 0.022125 0.00000870 16.387 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 994.39 994.39 0.022125 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.21 0.01150121 72.9022 5.55 0.00 1048.76 1048.76
FLOOR 3 LOUNGE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 LOUNGE VAV BOX 5728.164 5728.164 0.126046 0.00005011 94.693 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 5728.16 5728.16 0.126046 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.17 0.00918200 58.5588 124.47 0.00 6041.31 6041.31
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 4486.172 4486.172 0.085908 0.00003925 77.579 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4486.17 4486.17 0.085908 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00797813 51.2015 682.78 0.00 4730.80 4730.80
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 MECHANICAL VAV BOX 4879.729 4879.729 0.109616 0.00004269 80.204 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 4879.73 4879.73 0.109616 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.29 0.00726615 46.1492 7.78 0.00 5146.57 5146.57
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 MECHANICAL HALL VAV BOX 2308.091 2308.091 0.039632 0.00002019 41.744 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2308.09 2308.09 0.039632 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00846098 54.2564 551.91 0.00 2433.70 2433.70
FLOOR 3 OFFICE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 OFFICE VAV BOX 20137.156 20137.156 0.344910 0.00017617 364.612 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20137.16 20137.16 0.344910 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00803435 51.5572 4865.39 0.00 21233.03 21233.03
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 OFFICE HALL VAV BOX 5904.692 5904.692 0.101326 0.00005166 106.821 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5904.69 5904.69 0.101326 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00831721 53.3473 1415.90 0.00 6226.03 6226.03
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 1396.366 1396.366 0.025040 0.00001222 24.778 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1396.37 1396.37 0.025040 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800123 51.3476 287.71 0.00 1472.39 1472.39
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 PHYSICAL THERAPY 1 VAV BOX 27354.716 27354.716 0.529749 0.00023931 471.106 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 27354.72 27354.72 0.529749 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00820779 52.6548 3891.17 0.00 28846.54 28846.54
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 PHYSICAL THERAPY 2 VAV BOX 10458.981 10458.981 0.231882 0.00009150 172.533 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 10458.98 10458.98 0.231882 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.19 0.01535043 96.8566 29.88 0.00 11030.81 11030.81
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 1646.959 1646.959 0.037199 0.00001441 27.032   1/21 00:10:00   1/21 00:10:00 1646.96 1646.96 0.037199 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 1737.14 1737.14
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 STORAGE 1 VAV BOX 1938.596 1938.596 0.041785 0.00001696 32.240 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1938.60 1938.60 0.041785 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00856922 54.9419 86.65 0.00 2044.55 2044.55
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 STORAGE 2 VAV BOX 588.166 588.166 0.010304 0.00000515 10.542 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 588.17 588.17 0.010304 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00822839 52.7854 131.78 0.00 620.18 620.18
FLOOR 3 TREATMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 TREATMENT VAV BOX 8548.324 8548.324 0.193075 0.00007478 140.308   1/21 00:10:00   1/21 00:10:00 8548.32 8548.32 0.193075 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800000 51.3396 0.00 0.00 9016.41 9016.41
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 UNDEVELOPED 1 VAV BOX 18890.574 18890.574 0.322264 0.00016526 342.676 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 18890.57 18890.57 0.322264 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00782671 50.2422 4627.03 0.00 19918.59 19918.59
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 UNDEVELOPED 2 VAV BOX 13748.492 13748.492 0.234928 0.00012028 249.209 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13748.49 13748.49 0.234928 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00792997 50.8964 3348.51 0.00 14496.68 14496.68
FLOOR 3 UTILITY VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 UTILITY VAV BOX 1187.571 1187.571 0.022655 0.00001039 20.565 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1187.57 1187.57 0.022655 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00835332 53.5763 183.86 0.00 1252.33 1252.33
FLOOR 3 WORK VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 WORK VAV BOX 8826.186 8826.186 0.151131 0.00007722 159.832 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8826.19 8826.19 0.151131 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00800659 51.3815 2134.81 0.00 9306.51 9306.51
NE STAIR VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT NE STAIR VAV BOX 10755.928 10755.928 0.184541 0.00009410 194.600 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10755.93 10755.93 0.184541 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00797109 51.1569 2585.90 0.00 11341.27 11341.27
NW ELEVATOR VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT NW ELEVATOR VAV BOX 6572.627 6572.627 0.112570 0.00005750 119.010 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6572.63 6572.63 0.112570 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00791599 50.8081 1589.44 0.00 6930.31 6930.31
NW STAIR VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT NW STAIR VAV BOX 10385.308 10385.308 0.178002 0.00009086 187.981 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10385.31 10385.31 0.178002 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00795572 51.0596 2504.97 0.00 10950.48 10950.48
SW STAIR VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT SW STAIR VAV BOX 5126.386 5126.386 0.087860 0.00004485 92.794 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5126.39 5126.39 0.087860 -15.00 -15.00 0.00780000 32.22 18.76 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00794845 51.0136 1236.79 0.00 5405.37 5405.37
AHU-1 COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC AHU-1 137630.085 96490.143 5.542364 -999.0 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 137480.44 87273.08 5.542364 23.62 17.85 0.01042907 9.30 8.99 0.00700000 29.42 0.01716002 24.35 19.2261 22.20 0.00884749 53.0181 61899.27 0.00 138028.14 96561.36
AHU-1 HEATING COIL Coil:Heating:Water AirLoopHVAC AHU-1 0.000 0.000 5.542364 0.00000000 1.000   unknown unknown unknown 0.00 0.00 5.542364 18.64 13.95 0.00800691 -15.00 -15.00 0.00700000 8.70 0.00699286 8.70 19.2261 -999.00 -999.0 -999.0000 0.00 0.00 0.00 0.00
AHU-2 COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC AHU-2 141596.541 101966.980 6.052016 -999.0 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 142555.30 92506.63 6.052016 23.55 18.03 0.01067129 11.01 10.61 0.00780000 28.67 0.01715859 24.15 20.9649 22.20 0.00895047 53.6281 71764.19 0.00 142006.07 102033.68
AHU-2 HEATING COIL Coil:Heating:Water AirLoopHVAC AHU-2 0.000 0.000 6.052016 0.00000000 1.000   unknown unknown unknown 0.00 0.00 6.052016 0.00 -6.26 0.00000000 -15.00 -15.00 0.00780000 0.00 0.00000000 -6.26 20.9649 -999.00 -999.0 -999.0000 0.00 0.00 0.00 0.00
AHU-3 COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC AHU-3 137288.612 98131.993 5.770049 -999.0 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 134739.06 92628.16 5.770049 24.25 17.99 0.01033737 11.00 10.61 0.00780000 33.20 0.01716721 25.32 18.6030 22.20 0.00877644 52.5974 68427.17 0.00 137685.68 98198.23
AHU-3 HEATING COIL Coil:Heating:Water AirLoopHVAC AHU-3 0.000 0.000 5.770049 0.00000000 1.000   unknown unknown unknown 0.00 0.00 5.770049 0.00 -6.26 0.00000000 -15.00 -15.00 0.00780000 0.00 0.00000000 -6.26 18.6030 -999.00 -999.0 -999.0000 0.00 0.00 0.00 0.00
PSZ_CAFE HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ_CAFE 8922.420 6255.330 0.359310 -999.0 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 4461.21 2464.02 0.239540 27.84 21.68 0.01376824 9.69 9.69 0.00850000 33.20 0.01716721 25.32 76.9569 22.19 0.01018705 60.9638 4255.97 0.00 -999.00 -999.00
PSZ_CAFE HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ_CAFE 8922.418 8922.418 0.359306 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 4461.21 3851.86 0.179653 14.74 11.87 0.00748328 32.22 18.75 0.00800000 8.70 0.00699286 8.70 102.6104 20.09 0.01335370 90.4596 0.00 0.00 -999.00 -999.00
PSZ_CAFE_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ_CAFE 8922.418 8922.418 -999.0 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 8922.42 7703.71 0.359306 14.74 11.87 0.00748328 32.22 18.75 0.00800000 8.70 0.00699286 8.70 51.3052 20.09 0.01335370 90.4596 0.00 0.00 -999.00 -999.00
PSZ_ELEVATOR HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ_ELEVATOR 1682.540 1346.873 0.096623 -999.0 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 841.27 825.45 0.064415 22.20 15.80 0.00858169 9.67 9.67 0.00850000 32.15 0.01716522 25.06 0.0000 22.20 0.00858169 51.4424 1145.94 0.00 -999.00 -999.00
PSZ_ELEVATOR HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ_ELEVATOR 1599.456 1599.456 0.096623 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 799.73 660.31 0.048312 21.08 14.18 0.00725124 32.22 18.75 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00725124 46.5905 33.38 0.00 -999.00 -999.00
PSZ_ELEVATOR_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ_ELEVATOR 1599.456 1599.456 -999.0 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1599.46 1320.62 0.096623 21.08 14.18 0.00725124 32.22 18.75 0.00800000 8.70 0.00699286 8.70 0.0000 21.10 0.00725124 46.5905 33.38 0.00 -999.00 -999.00
PSZ_MRI_CONTROL HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ_MRI_CONTROL 4054.940 3077.618 0.193870 -999.0 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 2027.47 1585.34 0.129247 23.00 17.11 0.00977813 9.67 9.67 0.00850000 28.24 0.01715778 24.03 18.4037 22.20 0.00874610 52.4214 2325.67 0.00 -999.00 -999.00
PSZ_MRI_CONTROL HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ_MRI_CONTROL 3877.793 3877.793 0.193873 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1938.90 1502.90 0.096936 19.58 14.19 0.00787643 32.22 18.75 0.00800000 8.70 0.00699286 8.70 24.5379 24.91 0.00893323 45.4608 0.00 0.00 -999.00 -999.00
PSZ_MRI_CONTROL_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ_MRI_CONTROL 3877.793 3877.793 -999.0 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 3877.79 3005.79 0.193873 19.58 14.19 0.00787643 32.22 18.75 0.00800000 8.70 0.00699286 8.70 12.2689 24.91 0.00893323 45.4608 0.00 0.00 -999.00 -999.00
PSZ_MRI HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ_MRI 9890.230 7447.739 0.464840 -999.0 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 4945.11 3797.94 0.309893 23.07 17.23 0.00989238 9.69 9.69 0.00850000 28.24 0.01715778 24.03 20.1027 22.20 0.00878555 52.6558 5240.26 0.00 -999.00 -999.00
PSZ_MRI HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ_MRI 9457.213 9457.213 0.464836 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 4728.61 3643.44 0.232418 19.44 14.12 0.00786502 32.22 18.75 0.00800000 8.70 0.00699286 8.70 26.8039 25.00 0.00850371 43.0658 0.00 0.00 -999.00 -999.00
PSZ_MRI_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ_MRI 9457.213 9457.213 -999.0 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9457.21 7286.88 0.464836 19.44 14.12 0.00786502 32.22 18.75 0.00800000 8.70 0.00699286 8.70 13.4019 25.00 0.00850371 43.0658 0.00 0.00 -999.00 -999.00
PSZ_OR_1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ_OR_1 17968.900 12597.636 0.723610 -999.0 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 8984.45 5384.36 0.482407 22.63 18.36 0.01146568 6.10 6.10 0.00850000 30.82 0.01716268 24.71 49.5029 18.60 0.00866220 64.8521 7395.12 0.00 -999.00 -999.00
PSZ_OR_1 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ_OR_1 17968.895 17968.895 0.723607 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 8984.45 6023.16 0.361804 15.64 12.33 0.00757714 29.21 17.76 0.00800000 8.70 0.00699286 8.70 66.0041 21.34 0.00816519 51.6129 21.77 0.00 -999.00 -999.00
PSZ_OR_1_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ_OR_1 17968.895 17968.895 -999.0 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 17968.90 12046.31 0.723607 15.64 12.33 0.00757714 29.21 17.76 0.00800000 8.70 0.00699286 8.70 33.0020 21.34 0.00816519 51.6129 21.77 0.00 -999.00 -999.00
PSZ_OR_2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ_OR_2 18750.150 13145.355 0.755070 -999.0 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 9375.08 5598.61 0.503380 22.51 18.31 0.01146027 6.10 6.10 0.00850000 30.46 0.01716200 24.62 49.5030 18.60 0.00865491 64.7978 7616.26 0.00 -999.00 -999.00
PSZ_OR_2 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ_OR_2 18750.151 18750.151 0.755069 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9375.08 6203.41 0.377534 15.81 12.65 0.00782337 29.21 17.76 0.00800000 8.70 0.00699286 8.70 66.0041 22.20 0.00833849 50.0032 29.19 0.00 -999.00 -999.00
PSZ_OR_2_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ_OR_2 18750.151 18750.151 -999.0 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 18750.15 12406.82 0.755069 15.81 12.65 0.00782337 29.21 17.76 0.00800000 8.70 0.00699286 8.70 33.0020 22.20 0.00833849 50.0032 29.19 0.00 -999.00 -999.00
PSZ_OR_3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ_OR_3 18593.900 13035.811 0.748780 -999.0 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:20:00 9296.95 5341.02 0.499187 21.53 17.99 0.01146031 6.10 6.10 0.00850000 27.48 0.01715635 23.83 49.5028 18.60 0.00867635 64.9559 6139.54 0.00 -999.00 -999.00
PSZ_OR_3 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ_OR_3 18593.900 18593.900 0.748776 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9296.95 6146.09 0.374388 15.82 12.85 0.00801887 29.21 17.76 0.00800000 8.70 0.00699286 8.70 66.0041 22.20 0.00850194 50.9702 28.41 0.00 -999.00 -999.00
PSZ_OR_3_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ_OR_3 18593.900 18593.900 -999.0 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 18593.90 12292.19 0.748776 15.82 12.85 0.00801887 29.21 17.76 0.00800000 8.70 0.00699286 8.70 33.0020 22.20 0.00850194 50.9702 28.41 0.00 -999.00 -999.00
PSZ_XRAY HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ_XRAY 22311.110 16936.810 1.067250 -999.0 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 11155.56 8714.04 0.711500 22.98 17.11 0.00978182 9.74 9.74 0.00850000 28.24 0.01715778 24.03 17.9094 22.20 0.00878175 52.6336 10916.98 0.00 -999.00 -999.00
PSZ_XRAY HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ_XRAY 21252.039 21252.039 1.067253 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10626.02 8246.59 0.533627 19.62 14.20 0.00787975 32.22 18.75 0.00800000 8.70 0.00699286 8.70 23.8792 25.00 0.00850375 43.0660 0.00 0.00 -999.00 -999.00
PSZ_XRAY_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ_XRAY 21252.039 21252.039 -999.0 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 21252.04 16493.18 1.067253 19.62 14.20 0.00787975 32.22 18.75 0.00800000 8.70 0.00699286 8.70 11.9396 25.00 0.00850375 43.0660 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 ANESTHESIA N/A N/A N/A Yes Yes Yes No 2984.583 2984.583 0.065420 0.00002611 49.414 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.6568 2.233356 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 2984.58 2984.58 1.0000 0.07868280 0.065420 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.02610777 60.00 32.22 27.78 0.000 2984.58 8.70 0.00699286 8.70 0.00000000 0.0000 21.01 0.00944370 21.10 0.00944370 60.4636 80.47 0.00 3147.73 3147.73 0.07868280 -20.00 -20.00 0.00700000 -2850.5 19.30 13.26 0.00700000 37154.9
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 BIO HAZ VAV BOX FLOOR 1 BIO HAZ N/A N/A N/A Yes Yes Yes No 358.552 358.552 0.006167 0.00000314 6.484 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0789 0.268303 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 358.55 358.55 1.0000 0.00741736 0.006167 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00313645 60.00 32.22 27.78 0.000 358.55 8.70 0.00699286 8.70 0.00000000 0.0000 21.02 0.00815494 21.10 0.00815494 52.3206 85.43 0.00 378.06 378.06 0.00741736 -20.00 -20.00 0.00700000 -2850.5 30.08 17.24 0.00700000 48119.8
FLOOR 1 CLEAN VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 CLEAN VAV BOX FLOOR 1 CLEAN N/A N/A N/A Yes Yes Yes No 3233.655 3233.655 0.073036 0.00002829 53.097 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.7116 2.419735   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 3233.65 3233.65 1.0000 0.08784338 0.073036 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.02828653 60.00 32.22 27.78 0.000 3233.65 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 3410.72 3410.72 0.08784338 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 CLEAN WORK VAV BOX FLOOR 1 CLEAN WORK N/A N/A N/A Yes Yes Yes No 4046.692 4046.692 0.091400 0.00003540 66.447 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.8905 3.028129   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 4046.69 4046.69 1.0000 0.10992985 0.091400 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.03539862 60.00 32.22 27.78 0.000 4046.69 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 4268.28 4268.28 0.10992985 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 DICTATION VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 DICTATION VAV BOX FLOOR 1 DICTATION N/A N/A N/A Yes Yes Yes No 243.272 243.272 0.005495 0.00000213 3.995 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0535 0.182040   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 243.27 243.27 1.0000 0.00660857 0.005495 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00212803 60.00 32.22 27.78 0.000 243.27 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 256.59 256.59 0.00660857 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 DRESSING ROOM VAV BOX FLOOR 1 DRESSING ROOM N/A N/A N/A Yes Yes Yes No 540.493 540.493 0.009291 0.00000473 9.777 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.1189 0.404450 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 540.49 540.49 1.0000 0.01117434 0.009291 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00472799 60.00 32.22 27.78 0.000 540.49 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00779158 21.10 0.00779158 50.0202 129.31 0.00 569.91 569.91 0.01117434 -20.00 -20.00 0.00700000 -2850.5 30.11 17.25 0.00700000 48151.0
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 ELECTRICAL ROOM VAV BOX FLOOR 1 ELECTRICAL ROOM N/A N/A N/A Yes Yes Yes No 606.018 606.018 0.013688 0.00000530 9.951 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.1334 0.453481   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 606.02 606.02 1.0000 0.01646269 0.013688 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00530117 60.00 32.22 27.78 0.000 606.02 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 639.20 639.20 0.01646269 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 HUMID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 HUMID VAV BOX FLOOR 1 HUMID N/A N/A N/A Yes Yes Yes No 120.592 120.592 0.002724 0.00000105 1.980 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0265 0.090238   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 120.59 120.59 1.0000 0.00327592 0.002724 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00105488 60.00 32.22 27.78 0.000 120.59 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 127.19 127.19 0.00327592 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 IT HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 IT HALL VAV BOX FLOOR 1 IT HALL N/A N/A N/A Yes Yes Yes No 439.768 439.768 0.009933 0.00000385 7.221 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0968 0.329077   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 439.77 439.77 1.0000 0.01194646 0.009933 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00384689 60.00 32.22 27.78 0.000 439.77 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 463.85 463.85 0.01194646 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 IT ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 IT ROOM VAV BOX FLOOR 1 IT ROOM N/A N/A N/A Yes Yes Yes No 211.240 211.240 0.004771 0.00000185 3.469 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0465 0.158071   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 211.24 211.24 1.0000 0.00573842 0.004771 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00184783 60.00 32.22 27.78 0.000 211.24 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 222.81 222.81 0.00573842 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 LOBBY VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOBBY VAV BOX FLOOR 1 LOBBY N/A N/A N/A Yes Yes Yes No 3473.855 3473.855 0.070672 0.00003039 58.852 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.7645 2.599476 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 3473.85 3473.85 1.0000 0.08500040 0.070672 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.03038770 60.00 32.22 27.78 0.000 3473.85 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.01031892 21.10 0.01031892 65.9752 331.56 0.00 3663.62 3663.62 0.08500040 -20.00 -20.00 0.00700000 -2850.5 22.35 14.44 0.00700000 40250.7
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOBBY HALL VAV BOX FLOOR 1 LOBBY HALL N/A N/A N/A Yes Yes Yes No 802.973 802.973 0.018136 0.00000702 13.185 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.1767 0.600862   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 802.97 802.97 1.0000 0.02181304 0.018136 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00702404 60.00 32.22 27.78 0.000 802.97 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 846.94 846.94 0.02181304 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 LOBBY TOILET N/A N/A N/A Yes Yes Yes No 1397.236 1397.236 0.029193 0.00001222 23.469 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3075 1.045548 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1397.24 1397.24 1.0000 0.03511194 0.029193 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.01222238 60.00 32.22 27.78 0.000 1397.24 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00777643 21.10 0.00777643 49.9236 105.25 0.00 1473.58 1473.58 0.03511194 -20.00 -20.00 0.00700000 -2850.5 21.23 14.01 0.00700000 39117.4
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOCKER ROOM VAV BOX FLOOR 1 LOCKER ROOM N/A N/A N/A Yes Yes Yes No 3004.148 3004.148 0.067852 0.00002628 49.328 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.6611 2.247996   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 3004.15 3004.15 1.0000 0.08160875 0.067852 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.02627891 60.00 32.22 27.78 0.000 3004.15 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 3168.64 3168.64 0.08160875 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOCKER ROOM HALL VAV BOX FLOOR 1 LOCKER ROOM HALL N/A N/A N/A Yes Yes Yes No 1355.383 1355.383 0.030613 0.00001186 22.255 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2983 1.014229   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1355.38 1355.38 1.0000 0.03681946 0.030613 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.01185627 60.00 32.22 27.78 0.000 1355.38 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1429.60 1429.60 0.03681946 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 LOUNGE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOUNGE VAV BOX FLOOR 1 LOUNGE N/A N/A N/A Yes Yes Yes No 1636.049 1636.049 0.036952 0.00001431 26.864 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3600 1.224251   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1636.05 1636.05 1.0000 0.04444385 0.036952 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.01431141 60.00 32.22 27.78 0.000 1636.05 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1725.63 1725.63 0.04444385 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 MED GAS VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 MED GAS VAV BOX FLOOR 1 MED GAS N/A N/A N/A Yes Yes Yes No 1696.298 1696.298 0.029145 0.00001484 30.691 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3733 1.269335 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1696.30 1696.30 1.0000 0.03505375 0.029145 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.01483844 60.00 32.22 27.78 0.000 1696.30 8.70 0.00699286 8.70 0.00000000 0.0000 20.99 0.00798848 21.10 0.00798848 51.2669 405.94 0.00 1788.61 1788.61 0.03505375 -20.00 -20.00 0.00700000 -2850.5 30.13 17.26 0.00700000 48174.4
FLOOR 1 MRI HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 MRI HALL VAV BOX FLOOR 1 MRI HALL N/A N/A N/A Yes Yes Yes No 537.205 537.205 0.012133 0.00000470 8.821 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.1182 0.401989   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 537.20 537.20 1.0000 0.01459335 0.012133 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00469922 60.00 32.22 27.78 0.000 537.20 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 566.62 566.62 0.01459335 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 MRI TOILET N/A N/A N/A Yes Yes Yes No 1138.284 1138.284 0.025304 0.00000996 18.771 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2505 0.851775 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1138.28 1138.28 1.0000 0.03043440 0.025304 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00995719 60.00 32.22 27.78 0.000 1138.28 8.70 0.00699286 8.70 0.00000000 0.0000 21.07 0.00763784 21.10 0.00763784 49.0439 18.69 0.00 1200.52 1200.52 0.03043440 -20.00 -20.00 0.00700000 -2850.5 18.75 13.04 0.00700000 36595.7
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NOURISHMENT VAV BOX FLOOR 1 NOURISHMENT N/A N/A N/A Yes Yes Yes No 851.924 851.924 0.019242 0.00000745 13.989 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.1875 0.637492   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 851.92 851.92 1.0000 0.02314282 0.019242 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00745224 60.00 32.22 27.78 0.000 851.92 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 898.57 898.57 0.02314282 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NURSE HALL VAV BOX FLOOR 1 NURSE HALL N/A N/A N/A Yes Yes Yes No 1508.782 1508.782 0.034078 0.00001320 24.774 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3320 1.129018   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1508.78 1508.78 1.0000 0.04098660 0.034078 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.01319814 60.00 32.22 27.78 0.000 1508.78 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1591.40 1591.40 0.04098660 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NURSE JANITOR VAV BOX FLOOR 1 NURSE JANITOR N/A N/A N/A Yes Yes Yes No 190.140 190.140 0.004295 0.00000166 3.122 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0418 0.142281   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 190.14 190.14 1.0000 0.00516521 0.004295 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00166325 60.00 32.22 27.78 0.000 190.14 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 200.55 200.55 0.00516521 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NURSE STATION VAV BOX FLOOR 1 NURSE STATION N/A N/A N/A Yes Yes Yes No 1126.945 1126.945 0.025453 0.00000986 18.504 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2480 0.843290   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1126.94 1126.94 1.0000 0.03061386 0.025453 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00985800 60.00 32.22 27.78 0.000 1126.94 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1188.65 1188.65 0.03061386 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 NURSE TOILET N/A N/A N/A Yes Yes Yes No 1077.003 1077.003 0.024325 0.00000942 17.684 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2370 0.805919   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1077.00 1077.00 1.0000 0.02925718 0.024325 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00942113 60.00 32.22 27.78 0.000 1077.00 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1135.98 1135.98 0.02925718 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 OFFICE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 OFFICE VAV BOX FLOOR 1 OFFICE N/A N/A N/A Yes Yes Yes No 757.354 757.354 0.017106 0.00000663 12.436 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.1667 0.566726   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 757.35 757.35 1.0000 0.02057378 0.017106 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00662498 60.00 32.22 27.78 0.000 757.35 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 798.82 798.82 0.02057378 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 PACU VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PACU VAV BOX FLOOR 1 PACU N/A N/A N/A Yes Yes Yes No 2857.460 2857.460 0.064539 0.00002500 46.920 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.6288 2.138230   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 2857.46 2857.46 1.0000 0.07762392 0.064539 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.02499575 60.00 32.22 27.78 0.000 2857.46 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 3013.92 3013.92 0.07762392 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PRE-OP HALL VAV BOX FLOOR 1 PRE-OP HALL N/A N/A N/A Yes Yes Yes No 1548.169 1548.169 0.034967 0.00001354 25.421 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3407 1.158491   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1548.17 1548.17 1.0000 0.04205657 0.034967 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.01354268 60.00 32.22 27.78 0.000 1548.17 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1632.94 1632.94 0.04205657 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PRE-OP ROOM 1 VAV BOX FLOOR 1 PRE-OP ROOM 1 N/A N/A N/A Yes Yes Yes No 3948.973 3948.973 0.089192 0.00003455 64.842 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.8690 2.955006   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 3948.97 3948.97 1.0000 0.10727527 0.089192 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.03454381 60.00 32.22 27.78 0.000 3948.97 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 4165.21 4165.21 0.10727527 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PRE-OP ROOM 2 VAV BOX FLOOR 1 PRE-OP ROOM 2 N/A N/A N/A Yes Yes Yes No 7062.184 7062.184 0.159508 0.00006178 115.961 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.5541 5.284614   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 7062.18 7062.18 1.0000 0.19184677 0.159508 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.06177677 60.00 32.22 27.78 0.000 7062.18 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 7448.89 7448.89 0.19184677 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 PRE-OP TOILET N/A N/A N/A Yes Yes Yes No 1179.927 1179.927 0.024665 0.00001032 19.816 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2597 0.882937 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1179.93 1179.93 1.0000 0.02966609 0.024665 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.01032147 60.00 32.22 27.78 0.000 1179.93 8.70 0.00699286 8.70 0.00000000 0.0000 20.99 0.00774375 21.10 0.00774375 49.7163 88.39 0.00 1244.39 1244.39 0.02966609 -20.00 -20.00 0.00700000 -2850.5 21.21 14.01 0.00700000 39096.2
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PROCEDURE ROOM VAV BOX FLOOR 1 PROCEDURE ROOM N/A N/A N/A Yes Yes Yes No 14887.001 14887.001 0.336241 0.00013024 244.445 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 3.2760 11.139904   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 14887.00 14887.00 1.0000 0.40441072 0.336241 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.13022470 60.00 32.22 27.78 0.000 14887.00 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 15702.16 15702.16 0.40441072 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 RECEPTION VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 RECEPTION VAV BOX FLOOR 1 RECEPTION N/A N/A N/A Yes Yes Yes No 2391.089 2391.089 0.054006 0.00002092 39.262 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.5262 1.789246   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 2391.09 2391.09 1.0000 0.06495480 0.054006 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.02091616 60.00 32.22 27.78 0.000 2391.09 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 2522.02 2522.02 0.06495480 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 RECEPTION HALL VAV BOX FLOOR 1 RECEPTION HALL N/A N/A N/A Yes Yes Yes No 410.294 410.294 0.009267 0.00000359 6.737 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0903 0.307022   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 410.29 410.29 1.0000 0.01114577 0.009267 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00358906 60.00 32.22 27.78 0.000 410.29 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 432.76 432.76 0.01114577 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 RECOVERY ROOM VAV BOX FLOOR 1 RECOVERY ROOM N/A N/A N/A Yes Yes Yes No 12957.096 12957.096 0.289581 0.00011335 213.351 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 2.8513 9.695761 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 Sensible 12957.10 12957.10 1.0000 0.34829054 0.289581 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.11334277 60.00 32.22 27.78 0.000 12957.10 8.70 0.00699286 8.70 0.00000000 0.0000 21.01 0.00954189 21.19 0.00954189 60.7586 68.84 0.00 13665.57 13665.57 0.34829054 -20.00 -20.00 0.00700000 -2850.5 18.55 12.96 0.00700000 36385.7
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 SCHEDULING VAV BOX FLOOR 1 SCHEDULING N/A N/A N/A Yes Yes Yes No 231.801 231.801 0.005236 0.00000203 3.806 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0510 0.173456   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 231.80 231.80 1.0000 0.00629697 0.005236 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00202769 60.00 32.22 27.78 0.000 231.80 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 244.49 244.49 0.00629697 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 SCRUB VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 SCRUB VAV BOX FLOOR 1 SCRUB N/A N/A N/A Yes Yes Yes No 324.169 324.169 0.006297 0.00000284 5.580 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0713 0.242575 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 324.17 324.17 1.0000 0.00757350 0.006297 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00283569 60.00 32.22 27.78 0.000 324.17 8.70 0.00699286 8.70 0.00000000 0.0000 21.05 0.00943938 21.10 0.00943938 60.4368 44.64 0.00 341.85 341.85 0.00757350 -20.00 -20.00 0.00700000 -2850.5 24.35 15.19 0.00700000 42287.0
FLOOR 1 SOIL VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 SOIL N/A N/A N/A Yes Yes Yes No 3231.282 3231.282 0.072983 0.00002827 53.058 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.7111 2.417960   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 3231.28 3231.28 1.0000 0.08777894 0.072983 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.02826578 60.00 32.22 27.78 0.000 3231.28 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 3408.22 3408.22 0.08777894 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 SOIL HOLD N/A N/A N/A Yes Yes Yes No 1507.492 1507.492 0.034049 0.00001319 24.753 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3317 1.128052   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1507.49 1507.49 1.0000 0.04095155 0.034049 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.01318685 60.00 32.22 27.78 0.000 1507.49 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1590.04 1590.04 0.04095155 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 SOIL WORK N/A N/A N/A Yes Yes Yes No 4292.366 4292.366 0.096948 0.00003755 70.481 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.9446 3.211966   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 4292.37 4292.37 1.0000 0.11660366 0.096948 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.03754766 60.00 32.22 27.78 0.000 4292.37 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 4527.40 4527.40 0.11660366 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STEP DOWN VAV BOX FLOOR 1 STEP DOWN N/A N/A N/A Yes Yes Yes No 6858.705 6858.705 0.146501 0.00006000 114.423 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.5093 5.132351 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 6858.70 6858.70 1.0000 0.17620254 0.146501 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.05999682 60.00 32.22 27.78 0.000 6858.70 8.70 0.00699286 8.70 0.00000000 0.0000 20.95 0.00836020 21.10 0.00836020 53.6198 368.11 0.00 7233.52 7233.52 0.17620254 -20.00 -20.00 0.00700000 -2850.5 20.33 13.66 0.00700000 38201.8
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STERILE HALL VAV BOX FLOOR 1 STERILE HALL N/A N/A N/A Yes Yes Yes No 1734.971 1734.971 0.039186 0.00001518 28.488 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3818 1.298274   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1734.97 1734.97 1.0000 0.04713112 0.039186 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.01517674 60.00 32.22 27.78 0.000 1734.97 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1829.97 1829.97 0.04713112 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STERILE STORAGE VAV BOX FLOOR 1 STERILE STORAGE N/A N/A N/A Yes Yes Yes No 976.728 976.728 0.022061 0.00000854 16.038 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2149 0.730883   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 976.73 976.73 1.0000 0.02653316 0.022061 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00854397 60.00 32.22 27.78 0.000 976.73 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1030.21 1030.21 0.02653316 -20.00 -20.00 0.00700000 -2850.5 18.15 12.80 0.00700000 35976.8
FLOOR 1 STORAGE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STORAGE VAV BOX FLOOR 1 STORAGE N/A N/A N/A Yes Yes Yes No 13705.005 13705.005 0.234608 0.00011990 248.381 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 3.0159 10.255419 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13705.00 13705.00 1.0000 0.28217271 0.234608 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.11988513 60.00 32.22 27.78 0.000 13705.00 8.70 0.00699286 8.70 0.00000000 0.0000 20.88 0.00798233 21.10 0.00798233 51.2279 3318.14 0.00 14450.83 14450.83 0.28217271 -20.00 -20.00 0.00700000 -2850.5 30.31 17.32 0.00700000 48362.2
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 SUB-STERILE VAV BOX FLOOR 1 SUB-STERILE N/A N/A N/A Yes Yes Yes No 2306.240 2306.240 0.039522 0.00002018 41.776 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.5075 1.725754 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 2306.24 2306.24 1.0000 0.04753511 0.039522 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.02017394 60.00 32.22 27.78 0.000 2306.24 8.70 0.00699286 8.70 0.00000000 0.0000 20.93 0.00789641 21.10 0.00789641 50.6841 556.74 0.00 2431.75 2431.75 0.04753511 -20.00 -20.00 0.00700000 -2850.5 30.26 17.30 0.00700000 48306.4
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 UTILITY HALL VAV BOX FLOOR 1 UTILITY HALL N/A N/A N/A Yes Yes Yes No 4362.061 4362.061 0.074751 0.00003816 79.016 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.9599 3.264119 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 4362.06 4362.06 1.0000 0.08990640 0.074751 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.03815732 60.00 32.22 27.78 0.000 4362.06 8.70 0.00699286 8.70 0.00000000 0.0000 20.88 0.00801554 21.10 0.00801554 51.4381 1052.37 0.00 4599.44 4599.44 0.08990640 -20.00 -20.00 0.00700000 -2850.5 30.26 17.30 0.00700000 48307.7
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 UTILITY JANITOR VAV BOX FLOOR 1 UTILITY JANITOR N/A N/A N/A Yes Yes Yes No 168.075 168.075 0.003379 0.00000147 2.859 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0370 0.125770 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 168.08 168.08 1.0000 0.00406350 0.003379 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00147025 60.00 32.22 27.78 0.000 168.08 8.70 0.00699286 8.70 0.00000000 0.0000 21.07 0.00874735 21.10 0.00874735 56.0684 18.29 0.00 177.26 177.26 0.00406350 -20.00 -20.00 0.00700000 -2850.5 22.86 14.63 0.00700000 40771.0
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 UTILITY ROOM VAV BOX FLOOR 1 UTILITY ROOM N/A N/A N/A Yes Yes Yes No 3948.422 3948.422 0.067602 0.00003454 71.553 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.8689 2.954594 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 3948.42 3948.42 1.0000 0.08130726 0.067602 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.03453900 60.00 32.22 27.78 0.000 3948.42 8.70 0.00699286 8.70 0.00000000 0.0000 20.87 0.00787230 21.10 0.00787230 50.5313 956.09 0.00 4163.30 4163.30 0.08130726 -20.00 -20.00 0.00700000 -2850.5 30.31 17.32 0.00700000 48354.0
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 VESTIBULE VAV BOX FLOOR 1 VESTIBULE N/A N/A N/A Yes Yes Yes No 487.536 487.536 0.008389 0.00000427 8.815 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.1073 0.364822 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 487.54 487.54 1.0000 0.01008919 0.008389 -15.00 -15.00 0.00700000 2238.8 32.22 18.76 0.00800000 52863.7 0.00426474 60.00 32.22 27.78 0.000 487.54 8.70 0.00699286 8.70 0.00000000 0.0000 21.01 0.00772817 21.10 0.00772817 49.6176 116.32 0.00 514.07 514.07 0.01008919 -20.00 -20.00 0.00700000 -2850.5 30.06 17.23 0.00700000 48101.9
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 CONFERENCE VAV BOX FLOOR 2 CONFERENCE N/A N/A N/A Yes Yes Yes No 5025.868 5025.868 0.088233 0.00004397 89.997 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.1060 3.760844 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 5025.87 5025.87 1.0000 0.10612147 0.088233 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.04396400 60.00 32.22 27.78 0.000 5025.87 8.70 0.00699286 8.70 0.00000000 0.0000 20.91 0.00855514 21.10 0.00855514 54.8506 1115.31 0.00 5299.43 5299.43 0.10612147 -20.00 -20.00 0.00780000 -879.5 28.99 17.53 0.00780000 49057.9
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 2 CONFERENCE TOILET N/A N/A N/A Yes Yes Yes No 1271.201 1271.201 0.027505 0.00001112 21.117 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2797 0.951236 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1271.20 1271.20 1.0000 0.03308154 0.027505 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01111989 60.00 32.22 27.78 0.000 1271.20 8.70 0.00699286 8.70 0.00000000 0.0000 21.04 0.01009146 21.10 0.01009146 64.5431 48.74 0.00 1340.68 1340.68 0.03308154 -20.00 -20.00 0.00780000 -879.5 19.76 14.20 0.00780000 39647.1
FLOOR 2 DICTATION VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 DICTATION VAV BOX FLOOR 2 DICTATION N/A N/A N/A Yes Yes Yes No 437.896 437.896 0.009890 0.00000383 7.187 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0964 0.327676   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 437.90 437.90 1.0000 0.01189560 0.009890 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00383051 60.00 32.22 27.78 0.000 437.90 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 461.87 461.87 0.01189560 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 1 VAV BOX FLOOR 2 EXAM 1 N/A N/A N/A Yes Yes Yes No 6932.622 6932.622 0.132550 0.00006065 119.954 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.5256 5.187662 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 6932.62 6932.62 1.0000 0.15942358 0.132550 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.06064341 60.00 32.22 27.78 0.000 6932.62 8.70 0.00699286 8.70 0.00000000 0.0000 20.86 0.00811736 21.10 0.00811736 52.0828 1062.72 0.00 7310.65 7310.65 0.15942358 -20.00 -20.00 0.00780000 -879.5 24.99 16.14 0.00780000 44977.3
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 2 VAV BOX FLOOR 2 EXAM 2 N/A N/A N/A Yes Yes Yes No 11401.038 11401.038 0.254836 0.00009974 187.647 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 2.5089 8.531367 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 Sensible 11401.04 11401.04 1.0000 0.30650076 0.254836 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.09973108 60.00 32.22 27.78 0.000 11401.04 8.70 0.00699286 8.70 0.00000000 0.0000 21.05 0.01175940 21.13 0.01175940 74.8871 32.00 0.00 12024.45 12024.45 0.30650076 -20.00 -20.00 0.00780000 -879.5 18.49 13.70 0.00780000 38351.9
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 3 VAV BOX FLOOR 2 EXAM 3 N/A N/A N/A Yes Yes Yes No 15200.519 15200.519 0.339781 0.00013298 250.178 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 3.3450 11.374509 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 Sensible 15200.52 15200.52 1.0000 0.40866768 0.339781 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.13296721 60.00 32.22 27.78 0.000 15200.52 8.70 0.00699286 8.70 0.00000000 0.0000 21.07 0.01174740 21.15 0.01174740 74.7131 33.09 0.00 16031.68 16031.68 0.40866768 -20.00 -20.00 0.00780000 -879.5 18.48 13.70 0.00780000 38349.7
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 4 VAV BOX FLOOR 2 EXAM 4 N/A N/A N/A Yes Yes Yes No 1719.543 1719.543 0.032329 0.00001504 29.942 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3784 1.286730 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1719.54 1719.54 1.0000 0.03888340 0.032329 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01504178 60.00 32.22 27.78 0.000 1719.54 8.70 0.00699286 8.70 0.00000000 0.0000 20.92 0.00810092 21.10 0.00810092 51.9789 287.92 0.00 1813.29 1813.29 0.03888340 -20.00 -20.00 0.00780000 -879.5 25.75 16.41 0.00780000 45754.7
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 5 VAV BOX FLOOR 2 EXAM 5 N/A N/A N/A Yes Yes Yes No 8664.006 8664.006 0.174703 0.00007580 147.144 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.9066 6.483253 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8664.01 8664.01 1.0000 0.21012256 0.174703 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.07578877 60.00 32.22 27.78 0.000 8664.01 8.70 0.00699286 8.70 0.00000000 0.0000 20.82 0.00815458 21.10 0.00815458 52.3184 926.85 0.00 9137.26 9137.26 0.21012256 -20.00 -20.00 0.00780000 -879.5 22.66 15.29 0.00780000 42605.9
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 6 VAV BOX FLOOR 2 EXAM 6 N/A N/A N/A Yes Yes Yes No 5345.069 5345.069 0.111650 0.00004676 89.745 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.1762 3.999701 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 5345.07 5345.07 1.0000 0.13428557 0.111650 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.04675622 60.00 32.22 27.78 0.000 5345.07 8.70 0.00699286 8.70 0.00000000 0.0000 20.91 0.00823071 21.10 0.00823071 52.8003 399.70 0.00 5637.11 5637.11 0.13428557 -20.00 -20.00 0.00780000 -879.5 21.18 14.74 0.00780000 41099.0
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 7 VAV BOX FLOOR 2 EXAM 7 N/A N/A N/A Yes Yes Yes No 16548.077 16548.077 0.373759 0.00014477 271.612 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 3.6416 12.382883   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 16548.08 16548.08 1.0000 0.44953445 0.373759 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.14475503 60.00 32.22 27.78 0.000 16548.08 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 17454.20 17454.20 0.44953445 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 8 VAV BOX FLOOR 2 EXAM 8 N/A N/A N/A Yes Yes Yes No 6223.750 6223.750 0.133678 0.00005445 103.612 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.3696 4.657216 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 6223.75 6223.75 1.0000 0.16078020 0.133678 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.05444252 60.00 32.22 27.78 0.000 6223.75 8.70 0.00699286 8.70 0.00000000 0.0000 20.97 0.00844861 21.10 0.00844861 54.1791 300.29 0.00 6563.89 6563.89 0.16078020 -20.00 -20.00 0.00780000 -879.5 20.05 14.31 0.00780000 39945.8
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 9 VAV BOX FLOOR 2 EXAM 9 N/A N/A N/A Yes Yes Yes No 8748.544 8748.544 0.197597 0.00007654 143.594 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.9252 6.546513   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 8748.54 8748.54 1.0000 0.23765734 0.197597 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.07652827 60.00 32.22 27.78 0.000 8748.54 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 9227.59 9227.59 0.23765734 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 1 VAV BOX FLOOR 2 EXAM HALL 1 N/A N/A N/A Yes Yes Yes No 1225.197 1225.197 0.022910 0.00001072 21.379 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2696 0.916812 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1225.20 1225.20 1.0000 0.02755448 0.022910 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01071747 60.00 32.22 27.78 0.000 1225.20 8.70 0.00699286 8.70 0.00000000 0.0000 21.01 0.00873585 21.10 0.00873585 55.9945 209.50 0.00 1291.99 1291.99 0.02755448 -20.00 -20.00 0.00780000 -879.5 26.00 16.50 0.00780000 46009.2
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 2 VAV BOX FLOOR 2 EXAM HALL 2 N/A N/A N/A Yes Yes Yes No 1077.552 1077.552 0.022885 0.00000943 18.000 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2371 0.806329 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1077.55 1077.55 1.0000 0.02752454 0.022885 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00942593 60.00 32.22 27.78 0.000 1077.55 8.70 0.00699286 8.70 0.00000000 0.0000 21.06 0.01457397 21.10 0.01457397 92.5548 52.15 0.00 1136.44 1136.44 0.02752454 -20.00 -20.00 0.00780000 -879.5 20.50 14.48 0.00780000 40408.6
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 3 VAV BOX FLOOR 2 EXAM HALL 3 N/A N/A N/A Yes Yes Yes No 1066.724 1066.724 0.022104 0.00000933 17.956 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2347 0.798226 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1066.72 1066.72 1.0000 0.02658519 0.022104 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00933121 60.00 32.22 27.78 0.000 1066.72 8.70 0.00699286 8.70 0.00000000 0.0000 21.05 0.01299434 21.10 0.01299434 82.7273 79.13 0.00 1125.00 1125.00 0.02658519 -20.00 -20.00 0.00780000 -879.5 21.51 14.86 0.00780000 41437.4
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 4 VAV BOX FLOOR 2 EXAM HALL 4 N/A N/A N/A Yes Yes Yes No 1082.640 1082.640 0.024044 0.00000947 17.851 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2382 0.810137 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 Sensible 1082.64 1082.64 1.0000 0.02891896 0.024044 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00947044 60.00 32.22 27.78 0.000 1082.64 8.70 0.00699286 8.70 0.00000000 0.0000 21.04 0.01566637 21.12 0.01566637 99.1834 2.49 0.00 1141.83 1141.83 0.02891896 -20.00 -20.00 0.00780000 -879.5 18.73 13.80 0.00780000 38604.4
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 5 VAV BOX FLOOR 2 EXAM HALL 5 N/A N/A N/A Yes Yes Yes No 1099.293 1099.293 0.024829 0.00000962 18.043 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2419 0.822598   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1099.29 1099.29 1.0000 0.02986270 0.024829 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00961612 60.00 32.22 27.78 0.000 1099.29 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1159.49 1159.49 0.02986270 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 6 VAV BOX FLOOR 2 EXAM HALL 6 N/A N/A N/A Yes Yes Yes No 1118.462 1118.462 0.024724 0.00000978 18.466 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2461 0.836942 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00 Sensible 1118.46 1118.46 1.0000 0.02973677 0.024724 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00978380 60.00 32.22 27.78 0.000 1118.46 8.70 0.00699286 8.70 0.00000000 0.0000 21.07 0.01559387 21.10 0.01559387 98.8807 8.65 0.00 1179.61 1179.61 0.02973677 -20.00 -20.00 0.00780000 -879.5 18.92 13.87 0.00780000 38789.0
FLOOR 2 JANITOR VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 JANITOR VAV BOX FLOOR 2 JANITOR N/A N/A N/A Yes Yes Yes No 1279.732 1279.732 0.021959 0.00001120 23.152 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2816 0.957620 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1279.73 1279.73 1.0000 0.02641051 0.021959 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01119451 60.00 32.22 27.78 0.000 1279.73 8.70 0.00699286 8.70 0.00000000 0.0000 20.88 0.00793061 21.10 0.00793061 50.9009 307.65 0.00 1349.38 1349.38 0.02641051 -20.00 -20.00 0.00780000 -879.5 30.12 17.92 0.00780000 50212.9
FLOOR 2 LOUNGE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 LOUNGE VAV BOX FLOOR 2 LOUNGE N/A N/A N/A Yes Yes Yes No 632.082 632.082 0.014276 0.00000553 10.375 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.1391 0.472985   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 632.08 632.08 1.0000 0.01717073 0.014276 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00552916 60.00 32.22 27.78 0.000 632.08 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 666.69 666.69 0.01717073 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 NURSE STATION 1 VAV BOX FLOOR 2 NURSE STATION 1 N/A N/A N/A Yes Yes Yes No 995.705 995.705 0.022489 0.00000871 16.343 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2191 0.745083   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 995.70 995.70 1.0000 0.02704868 0.022489 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00870997 60.00 32.22 27.78 0.000 995.70 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1050.23 1050.23 0.02704868 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 NURSE STATION 2 VAV BOX FLOOR 2 NURSE STATION 2 N/A N/A N/A Yes Yes Yes No 1203.916 1203.916 0.027192 0.00001053 19.761 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2649 0.900887   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1203.92 1203.92 1.0000 0.03270482 0.027192 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01053131 60.00 32.22 27.78 0.000 1203.92 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1269.84 1269.84 0.03270482 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 OFFICE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 OFFICE VAV BOX FLOOR 2 OFFICE N/A N/A N/A Yes Yes Yes No 7038.079 7038.079 0.120366 0.00006157 127.524 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.5488 5.266576 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 7038.08 7038.08 1.0000 0.14476863 0.120366 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.06156591 60.00 32.22 27.78 0.000 7038.08 8.70 0.00699286 8.70 0.00000000 0.0000 20.84 0.00793304 21.10 0.00793304 50.9160 1709.60 0.00 7421.09 7421.09 0.14476863 -20.00 -20.00 0.00780000 -879.5 30.29 17.97 0.00780000 50382.3
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 OFFICE HALL VAV BOX FLOOR 2 OFFICE HALL N/A N/A N/A Yes Yes Yes No 2708.829 2708.829 0.053141 0.00002370 46.437 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.5961 2.027010 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 2708.83 2708.83 1.0000 0.06391513 0.053141 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.02369560 60.00 32.22 27.78 0.000 2708.83 8.70 0.00699286 8.70 0.00000000 0.0000 21.02 0.00971169 21.10 0.00971169 62.1521 348.61 0.00 2856.58 2856.58 0.06391513 -20.00 -20.00 0.00780000 -879.5 23.85 15.72 0.00780000 43813.9
FLOOR 2 RECEPTION VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 RECEPTION VAV BOX FLOOR 2 RECEPTION N/A N/A N/A Yes Yes Yes No 8937.709 8937.709 0.175152 0.00007819 153.275 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.9668 6.688064 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8937.71 8937.71 1.0000 0.21066208 0.175152 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.07818300 60.00 32.22 27.78 0.000 8937.71 8.70 0.00699286 8.70 0.00000000 0.0000 20.96 0.00960215 21.10 0.00960215 61.4603 1159.99 0.00 9425.20 9425.20 0.21066208 -20.00 -20.00 0.00780000 -879.5 23.89 15.74 0.00780000 43861.4
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 RECEPTION HALL VAV BOX FLOOR 2 RECEPTION HALL N/A N/A N/A Yes Yes Yes No 3129.374 3129.374 0.070681 0.00002738 51.364 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.6887 2.341702   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 3129.37 3129.37 1.0000 0.08501057 0.070681 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.02737434 60.00 32.22 27.78 0.000 3129.37 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 3300.73 3300.73 0.08501057 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 2 RECEPTION TOILET N/A N/A N/A Yes Yes Yes No 2235.501 2235.501 0.050492 0.00001956 36.692 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.4919 1.672820   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 2235.50 2235.50 1.0000 0.06072819 0.050492 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01955515 60.00 32.22 27.78 0.000 2235.50 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 2357.91 2357.91 0.06072819 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 SCHEDULING 1 VAV BOX FLOOR 2 SCHEDULING 1 N/A N/A N/A Yes Yes Yes No 1652.432 1652.432 0.037322 0.00001446 27.122 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3636 1.236511   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1652.43 1652.43 1.0000 0.04488892 0.037322 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01445472 60.00 32.22 27.78 0.000 1652.43 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1742.91 1742.91 0.04488892 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 SCHEDULING 2 VAV BOX FLOOR 2 SCHEDULING 2 N/A N/A N/A Yes Yes Yes No 1758.099 1758.099 0.039709 0.00001538 28.857 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3869 1.315581   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1758.10 1758.10 1.0000 0.04775940 0.039709 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01537905 60.00 32.22 27.78 0.000 1758.10 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1854.37 1854.37 0.04775940 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 STORAGE 1 VAV BOX FLOOR 2 STORAGE 1 N/A N/A N/A Yes Yes Yes No 340.792 340.792 0.006761 0.00000298 5.819 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0750 0.255014 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 340.79 340.79 1.0000 0.00813202 0.006761 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00298109 60.00 32.22 27.78 0.000 340.79 8.70 0.00699286 8.70 0.00000000 0.0000 21.05 0.00854614 21.10 0.00854614 54.7960 41.14 0.00 359.38 359.38 0.00813202 -20.00 -20.00 0.00780000 -879.5 23.36 15.54 0.00780000 43314.1
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 STORAGE 2 VAV BOX FLOOR 2 STORAGE 2 N/A N/A N/A Yes Yes Yes No 584.137 584.137 0.012595 0.00000511 9.714 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.1285 0.437108 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 584.14 584.14 1.0000 0.01514820 0.012595 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00510976 60.00 32.22 27.78 0.000 584.14 8.70 0.00699286 8.70 0.00000000 0.0000 21.07 0.01303855 21.10 0.01303855 83.0074 21.38 0.00 616.06 616.06 0.01514820 -20.00 -20.00 0.00780000 -879.5 19.90 14.25 0.00780000 39789.6
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 STORAGE 3 VAV BOX FLOOR 2 STORAGE 3 N/A N/A N/A Yes Yes Yes No 687.420 687.420 0.015526 0.00000601 11.283 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.1513 0.514395   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 687.42 687.42 1.0000 0.01867402 0.015526 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00601324 60.00 32.22 27.78 0.000 687.42 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 725.06 725.06 0.01867402 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 UTILITY VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 UTILITY VAV BOX FLOOR 2 UTILITY N/A N/A N/A Yes Yes Yes No 2152.671 2152.671 0.036902 0.00001883 38.962 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.4737 1.610838 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 2152.67 2152.67 1.0000 0.04438341 0.036902 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01883059 60.00 32.22 27.78 0.000 2152.67 8.70 0.00699286 8.70 0.00000000 0.0000 20.89 0.00795936 21.10 0.00795936 51.0827 518.98 0.00 2269.82 2269.82 0.04438341 -20.00 -20.00 0.00780000 -879.5 30.17 17.93 0.00780000 50261.7
FLOOR 2 WORK VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 WORK VAV BOX FLOOR 2 WORK N/A N/A N/A Yes Yes Yes No 7371.030 7371.030 0.166484 0.00006448 120.985 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.6221 5.515722   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 7371.03 7371.03 1.0000 0.20023667 0.166484 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.06447841 60.00 32.22 27.78 0.000 7371.03 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 7774.65 7774.65 0.20023667 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 WORK HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 WORK HALL VAV BOX FLOOR 2 WORK HALL N/A N/A N/A Yes Yes Yes No 4449.825 4449.825 0.100505 0.00003893 73.037 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.9792 3.329792   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 4449.83 4449.83 1.0000 0.12088110 0.100505 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.03892504 60.00 32.22 27.78 0.000 4449.83 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 4693.48 4693.48 0.12088110 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 2 WORK TOILET N/A N/A N/A Yes Yes Yes No 1290.810 1290.810 0.024667 0.00001129 22.339 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2841 0.965910 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1290.81 1290.81 1.0000 0.02966841 0.024667 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01129142 60.00 32.22 27.78 0.000 1290.81 8.70 0.00699286 8.70 0.00000000 0.0000 20.92 0.00788230 21.10 0.00788230 50.5950 198.92 0.00 1361.20 1361.20 0.02966841 -20.00 -20.00 0.00780000 -879.5 25.01 16.14 0.00780000 45000.8
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 DRESSING ROOM VAV BOX FLOOR 3 DRESSING ROOM N/A N/A N/A Yes Yes Yes No 315.983 315.983 0.007137 0.00000276 5.186 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0695 0.236449   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 315.98 315.98 1.0000 0.00858380 0.007137 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00276408 60.00 32.22 27.78 0.000 315.98 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 333.29 333.29 0.00858380 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 ELEVATOR HALL VAV BOX FLOOR 3 ELEVATOR HALL N/A N/A N/A Yes Yes Yes No 3443.326 3443.326 0.058948 0.00003012 62.361 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.7577 2.576632 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 3443.33 3443.33 1.0000 0.07089857 0.058948 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.03012065 60.00 32.22 27.78 0.000 3443.33 8.70 0.00699286 8.70 0.00000000 0.0000 20.90 0.00811683 21.10 0.00811683 52.0792 832.87 0.00 3630.71 3630.71 0.07089857 -20.00 -20.00 0.00780000 -879.5 30.24 17.95 0.00780000 50330.5
FLOOR 3 HUMID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 HUMID VAV BOX FLOOR 3 HUMID N/A N/A N/A Yes Yes Yes No 733.316 733.316 0.016563 0.00000642 12.036 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.1614 0.548738   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 733.32 733.32 1.0000 0.01992079 0.016563 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00641471 60.00 32.22 27.78 0.000 733.32 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 773.47 773.47 0.01992079 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 3 JANITOR VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 JANITOR VAV BOX FLOOR 3 JANITOR N/A N/A N/A Yes Yes Yes No 1747.866 1747.866 0.030022 0.00001529 31.607 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3846 1.307923 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1747.87 1747.87 1.0000 0.03610810 0.030022 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01528953 60.00 32.22 27.78 0.000 1747.87 8.70 0.00699286 8.70 0.00000000 0.0000 20.92 0.00797146 21.10 0.00797146 51.1592 418.74 0.00 1842.99 1842.99 0.03610810 -20.00 -20.00 0.00780000 -879.5 30.07 17.90 0.00780000 50161.3
FLOOR 3 LOCKER VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 LOCKER VAV BOX FLOOR 3 LOCKER N/A N/A N/A Yes Yes Yes No 994.392 994.392 0.022125 0.00000870 16.387 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2188 0.744101 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 Sensible 994.39 994.39 1.0000 0.02661007 0.022125 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00869848 60.00 32.22 27.78 0.000 994.39 8.70 0.00699286 8.70 0.00000000 0.0000 20.87 0.01150121 21.21 0.01150121 72.9022 5.55 0.00 1048.76 1048.76 0.02661007 -20.00 -20.00 0.00780000 -879.5 18.66 13.77 0.00780000 38532.7
FLOOR 3 LOUNGE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 LOUNGE VAV BOX FLOOR 3 LOUNGE N/A N/A N/A Yes Yes Yes No 5728.164 5728.164 0.126046 0.00005011 94.693 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.2605 4.286370 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 Sensible 5728.16 5728.16 1.0000 0.15160081 0.126046 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.05010737 60.00 32.22 27.78 0.000 5728.16 8.70 0.00699286 8.70 0.00000000 0.0000 20.95 0.00918200 21.17 0.00918200 58.5588 124.47 0.00 6041.31 6041.31 0.15160081 -20.00 -20.00 0.00780000 -879.5 19.09 13.94 0.00780000 38970.7
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 3 LOUNGE TOILET N/A N/A N/A Yes Yes Yes No 4486.172 4486.172 0.085908 0.00003925 77.579 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.9872 3.356991 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 4486.17 4486.17 1.0000 0.10332504 0.085908 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.03924299 60.00 32.22 27.78 0.000 4486.17 8.70 0.00699286 8.70 0.00000000 0.0000 20.89 0.00797813 21.10 0.00797813 51.2015 682.78 0.00 4730.80 4730.80 0.10332504 -20.00 -20.00 0.00780000 -879.5 24.92 16.11 0.00780000 44906.2
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 MECHANICAL VAV BOX FLOOR 3 MECHANICAL N/A N/A N/A Yes Yes Yes No 4879.729 4879.729 0.109616 0.00004269 80.204 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.0738 3.651488 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 Sensible 4879.73 4879.73 1.0000 0.13183936 0.109616 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.04268564 60.00 32.22 27.78 0.000 4879.73 8.70 0.00699286 8.70 0.00000000 0.0000 20.95 0.00726615 21.29 0.00726615 46.1492 7.78 0.00 5146.57 5146.57 0.13183936 -20.00 -20.00 0.00780000 -879.5 18.30 13.63 0.00780000 38157.2
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 MECHANICAL HALL VAV BOX FLOOR 3 MECHANICAL HALL N/A N/A N/A Yes Yes Yes No 2308.091 2308.091 0.039632 0.00002019 41.744 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.5079 1.727138 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 2308.09 2308.09 1.0000 0.04766645 0.039632 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.02019012 60.00 32.22 27.78 0.000 2308.09 8.70 0.00699286 8.70 0.00000000 0.0000 20.95 0.00846098 21.10 0.00846098 54.2564 551.91 0.00 2433.70 2433.70 0.04766645 -20.00 -20.00 0.00780000 -879.5 30.09 17.90 0.00780000 50177.4
FLOOR 3 OFFICE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 OFFICE VAV BOX FLOOR 3 OFFICE N/A N/A N/A Yes Yes Yes No 20137.156 20137.156 0.344910 0.00017617 364.612 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 4.4314 15.068581 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20137.16 20137.16 1.0000 0.41483692 0.344910 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.17615065 60.00 32.22 27.78 0.000 20137.16 8.70 0.00699286 8.70 0.00000000 0.0000 20.87 0.00803435 21.10 0.00803435 51.5572 4865.39 0.00 21233.03 21233.03 0.41483692 -20.00 -20.00 0.00780000 -879.5 30.21 17.95 0.00780000 50304.6
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 OFFICE HALL VAV BOX FLOOR 3 OFFICE HALL N/A N/A N/A Yes Yes Yes No 5904.692 5904.692 0.101326 0.00005166 106.821 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.2994 4.418466 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 5904.69 5904.69 1.0000 0.12186819 0.101326 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.05165155 60.00 32.22 27.78 0.000 5904.69 8.70 0.00699286 8.70 0.00000000 0.0000 20.96 0.00831721 21.10 0.00831721 53.3473 1415.90 0.00 6226.03 6226.03 0.12186819 -20.00 -20.00 0.00780000 -879.5 30.12 17.91 0.00780000 50208.8
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 3 OFFICE TOILET N/A N/A N/A Yes Yes Yes No 1396.366 1396.366 0.025040 0.00001222 24.778 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3073 1.044897 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1396.37 1396.37 1.0000 0.03011710 0.025040 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01221477 60.00 32.22 27.78 0.000 1396.37 8.70 0.00699286 8.70 0.00000000 0.0000 20.94 0.00800123 21.10 0.00800123 51.3476 287.71 0.00 1472.39 1472.39 0.03011710 -20.00 -20.00 0.00780000 -879.5 27.96 17.18 0.00780000 48009.3
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 PHYSICAL THERAPY 1 VAV BOX FLOOR 3 PHYSICAL THERAPY 1 N/A N/A N/A Yes Yes Yes No 27354.716 27354.716 0.529749 0.00023931 471.106 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 6.0197 20.469462 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 27354.72 27354.72 1.0000 0.63714945 0.529749 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.23928657 60.00 32.22 27.78 0.000 27354.72 8.70 0.00699286 8.70 0.00000000 0.0000 20.89 0.00820779 21.10 0.00820779 52.6548 3891.17 0.00 28846.54 28846.54 0.63714945 -20.00 -20.00 0.00780000 -879.5 24.42 15.93 0.00780000 44394.9
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 PHYSICAL THERAPY 2 VAV BOX FLOOR 3 PHYSICAL THERAPY 2 N/A N/A N/A Yes Yes Yes No 10458.981 10458.981 0.231882 0.00009150 172.533 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 2.3016 7.826428 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 Sensible 10458.98 10458.98 1.0000 0.27889299 0.231882 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.09149039 60.00 32.22 27.78 0.000 10458.98 8.70 0.00699286 8.70 0.00000000 0.0000 20.87 0.01535043 21.19 0.01535043 96.8566 29.88 0.00 11030.81 11030.81 0.27889299 -20.00 -20.00 0.00780000 -879.5 18.80 13.83 0.00780000 38672.7
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 3 PHYSICAL THERAPY TOILET N/A N/A N/A Yes Yes Yes No 1646.959 1646.959 0.037199 0.00001441 27.032 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.3624 1.232415   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 1646.96 1646.96 1.0000 0.04474023 0.037199 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01440684 60.00 32.22 27.78 0.000 1646.96 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 1737.14 1737.14 0.04474023 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 STORAGE 1 VAV BOX FLOOR 3 STORAGE 1 N/A N/A N/A Yes Yes Yes No 1938.596 1938.596 0.041785 0.00001696 32.240 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.4266 1.450646 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1938.60 1938.60 1.0000 0.05025620 0.041785 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01695795 60.00 32.22 27.78 0.000 1938.60 8.70 0.00699286 8.70 0.00000000 0.0000 21.02 0.00856922 21.10 0.00856922 54.9419 86.65 0.00 2044.55 2044.55 0.05025620 -20.00 -20.00 0.00780000 -879.5 19.91 14.25 0.00780000 39803.1
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 STORAGE 2 VAV BOX FLOOR 3 STORAGE 2 N/A N/A N/A Yes Yes Yes No 588.166 588.166 0.010304 0.00000515 10.542 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.1294 0.440123 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 588.17 588.17 1.0000 0.01239252 0.010304 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.00514501 60.00 32.22 27.78 0.000 588.17 8.70 0.00699286 8.70 0.00000000 0.0000 20.98 0.00822839 21.10 0.00822839 52.7854 131.78 0.00 620.18 620.18 0.01239252 -20.00 -20.00 0.00780000 -879.5 29.10 17.57 0.00780000 49165.2
FLOOR 3 TREATMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 TREATMENT VAV BOX FLOOR 3 TREATMENT N/A N/A N/A Yes Yes Yes No 8548.324 8548.324 0.193075 0.00007478 140.308 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.8811 6.396689   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 8548.32 8548.32 1.0000 0.23221829 0.193075 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.07477684 60.00 32.22 27.78 0.000 8548.32 8.70 0.00699286 8.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 51.3396 0.00 0.00 9016.41 9016.41 0.23221829 -20.00 -20.00 0.00780000 -879.5 18.09 13.55 0.00780000 37947.8
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 UNDEVELOPED 1 VAV BOX FLOOR 3 UNDEVELOPED 1 N/A N/A N/A Yes Yes Yes No 18890.574 18890.574 0.322264 0.00016526 342.676 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 4.1571 14.135767 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 18890.57 18890.57 1.0000 0.38759964 0.322264 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.16524613 60.00 32.22 27.78 0.000 18890.57 8.70 0.00699286 8.70 0.00000000 0.0000 20.82 0.00782671 21.10 0.00782671 50.2422 4627.03 0.00 19918.59 19918.59 0.38759964 -20.00 -20.00 0.00780000 -879.5 30.41 18.01 0.00780000 50510.1
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 UNDEVELOPED 2 VAV BOX FLOOR 3 UNDEVELOPED 2 N/A N/A N/A Yes Yes Yes No 13748.492 13748.492 0.234928 0.00012028 249.209 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 3.0255 10.287961 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13748.49 13748.49 1.0000 0.28255678 0.234928 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.12026554 60.00 32.22 27.78 0.000 13748.49 8.70 0.00699286 8.70 0.00000000 0.0000 20.83 0.00792997 21.10 0.00792997 50.8964 3348.51 0.00 14496.68 14496.68 0.28255678 -20.00 -20.00 0.00780000 -879.5 30.33 17.99 0.00780000 50425.9
FLOOR 3 UTILITY VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 UTILITY VAV BOX FLOOR 3 UTILITY N/A N/A N/A Yes Yes Yes No 1187.571 1187.571 0.022655 0.00001039 20.565 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.2613 0.888656 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1187.57 1187.57 1.0000 0.02724841 0.022655 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.01038833 60.00 32.22 27.78 0.000 1187.57 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00835332 21.10 0.00835332 53.5763 183.86 0.00 1252.33 1252.33 0.02724841 -20.00 -20.00 0.00780000 -879.5 25.09 16.17 0.00780000 45080.1
FLOOR 3 WORK VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 WORK VAV BOX FLOOR 3 WORK N/A N/A N/A Yes Yes Yes No 8826.186 8826.186 0.151131 0.00007722 159.832 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.9423 6.604612 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8826.19 8826.19 1.0000 0.18177173 0.151131 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.07720744 60.00 32.22 27.78 0.000 8826.19 8.70 0.00699286 8.70 0.00000000 0.0000 20.88 0.00800659 21.10 0.00800659 51.3815 2134.81 0.00 9306.51 9306.51 0.18177173 -20.00 -20.00 0.00780000 -879.5 30.23 17.95 0.00780000 50319.4
NE STAIR VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT NE STAIR VAV BOX NE STAIR N/A N/A N/A Yes Yes Yes No 10755.928 10755.928 0.184541 0.00009410 194.600 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 2.3670 8.048633 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10755.93 10755.93 1.0000 0.22195416 0.184541 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.09408795 60.00 32.22 27.78 0.000 10755.93 8.70 0.00699286 8.70 0.00000000 0.0000 20.94 0.00797109 21.10 0.00797109 51.1569 2585.90 0.00 11341.27 11341.27 0.22195416 -20.00 -20.00 0.00780000 -879.5 30.13 17.92 0.00780000 50217.9
NW ELEVATOR VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT NW ELEVATOR VAV BOX NW ELEVATOR N/A N/A N/A Yes Yes Yes No 6572.627 6572.627 0.112570 0.00005750 119.010 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.4464 4.918280 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 6572.63 6572.63 1.0000 0.13539187 0.112570 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.05749435 60.00 32.22 27.78 0.000 6572.63 8.70 0.00699286 8.70 0.00000000 0.0000 20.88 0.00791599 21.10 0.00791599 50.8081 1589.44 0.00 6930.31 6930.31 0.13539187 -20.00 -20.00 0.00780000 -879.5 30.22 17.95 0.00780000 50307.6
NW STAIR VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT NW STAIR VAV BOX NW STAIR N/A N/A N/A Yes Yes Yes No 10385.308 10385.308 0.178002 0.00009086 187.981 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 2.2854 7.771298 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10385.31 10385.31 1.0000 0.21409053 0.178002 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.09084593 60.00 32.22 27.78 0.000 10385.31 8.70 0.00699286 8.70 0.00000000 0.0000 20.94 0.00795572 21.10 0.00795572 51.0596 2504.97 0.00 10950.48 10950.48 0.21409053 -20.00 -20.00 0.00780000 -879.5 30.18 17.93 0.00780000 50269.4
SW STAIR VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT SW STAIR VAV BOX SW STAIR N/A N/A N/A Yes Yes Yes No 5126.386 5126.386 0.087860 0.00004485 92.794 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 1.1281 3.836061 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 5126.39 5126.39 1.0000 0.10567289 0.087860 -15.00 -15.00 0.00780000 4217.2 32.22 18.76 0.00800000 52863.7 0.04484329 60.00 32.22 27.78 0.000 5126.39 8.70 0.00699286 8.70 0.00000000 0.0000 20.94 0.00794845 21.10 0.00794845 51.0136 1236.79 0.00 5405.37 5405.37 0.10567289 -20.00 -20.00 0.00780000 -879.5 30.18 17.94 0.00780000 50272.4
AHU-1 COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC AHU-1 FLOOR 1 ANESTHESIA; FLOOR 1 BIO HAZ; FLOOR 1 CLEAN; FLOOR 1 CLEAN WORK; FLOOR 1 DICTATION; FLOOR 1 DRESSING ROOM; FLOOR 1 ELECTRICAL ROOM; FLOOR 1 HUMID; FLOOR 1 IT HALL; FLOOR 1 IT ROOM; FLOOR 1 LOBBY; FLOOR 1 LOBBY HALL; FLOOR 1 LOBBY TOILET; FLOOR 1 LOCKER ROOM; FLOOR 1 LOCKER ROOM HALL; FLOOR 1 LOUNGE; FLOOR 1 MED GAS; FLOOR 1 MRI HALL; FLOOR 1 MRI TOILET; FLOOR 1 NOURISHMENT; FLOOR 1 NURSE HALL; FLOOR 1 NURSE JANITOR; FLOOR 1 NURSE STATION; FLOOR 1 NURSE TOILET; FLOOR 1 OFFICE; FLOOR 1 PACU; FLOOR 1 PRE-OP HALL; FLOOR 1 PRE-OP ROOM 1; FLOOR 1 PRE-OP ROOM 2; FLOOR 1 PRE-OP TOILET; FLOOR 1 PROCEDURE ROOM; FLOOR 1 RECEPTION; FLOOR 1 RECEPTION HALL; FLOOR 1 RECOVERY ROOM; FLOOR 1 SCHEDULING; FLOOR 1 SCRUB; FLOOR 1 SOIL; FLOOR 1 SOIL HOLD; FLOOR 1 SOIL WORK; FLOOR 1 STEP DOWN; FLOOR 1 STERILE HALL; FLOOR 1 STERILE STORAGE; FLOOR 1 STORAGE; FLOOR 1 SUB-STERILE; FLOOR 1 UTILITY HALL; FLOOR 1 UTILITY JANITOR; FLOOR 1 UTILITY ROOM; FLOOR 1 VESTIBULE; Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 137630.085 96490.143 5.542364 -999.0 -999.000 -999.0000 1.00000 0.90873 1024.2271 1004.8586 1.2027 AHU-1 FAN Fan:VariableVolume 5.542364 6.66601638   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 Sensible 137480.44 87273.08 0.9989 6.66601638 5.542364 23.62 17.85 0.01042907 50272.3 9.30 8.99 0.00700000 26977.1 -999.0 -999.00 -999.00 -999.00 12259.488 125220.95 29.42 0.01716002 24.35 1.06558155 19.2261 22.24 0.00882694 22.20 0.00884749 53.0181 61899.27 0.00 138028.14 96561.36 6.40275912 26.67 19.44 0.01118466 55322.4 11.89 11.87 0.00864541 33764.8
AHU-1 HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC AHU-1 FLOOR 1 ANESTHESIA; FLOOR 1 BIO HAZ; FLOOR 1 CLEAN; FLOOR 1 CLEAN WORK; FLOOR 1 DICTATION; FLOOR 1 DRESSING ROOM; FLOOR 1 ELECTRICAL ROOM; FLOOR 1 HUMID; FLOOR 1 IT HALL; FLOOR 1 IT ROOM; FLOOR 1 LOBBY; FLOOR 1 LOBBY HALL; FLOOR 1 LOBBY TOILET; FLOOR 1 LOCKER ROOM; FLOOR 1 LOCKER ROOM HALL; FLOOR 1 LOUNGE; FLOOR 1 MED GAS; FLOOR 1 MRI HALL; FLOOR 1 MRI TOILET; FLOOR 1 NOURISHMENT; FLOOR 1 NURSE HALL; FLOOR 1 NURSE JANITOR; FLOOR 1 NURSE STATION; FLOOR 1 NURSE TOILET; FLOOR 1 OFFICE; FLOOR 1 PACU; FLOOR 1 PRE-OP HALL; FLOOR 1 PRE-OP ROOM 1; FLOOR 1 PRE-OP ROOM 2; FLOOR 1 PRE-OP TOILET; FLOOR 1 PROCEDURE ROOM; FLOOR 1 RECEPTION; FLOOR 1 RECEPTION HALL; FLOOR 1 RECOVERY ROOM; FLOOR 1 SCHEDULING; FLOOR 1 SCRUB; FLOOR 1 SOIL; FLOOR 1 SOIL HOLD; FLOOR 1 SOIL WORK; FLOOR 1 STEP DOWN; FLOOR 1 STERILE HALL; FLOOR 1 STERILE STORAGE; FLOOR 1 STORAGE; FLOOR 1 SUB-STERILE; FLOOR 1 UTILITY HALL; FLOOR 1 UTILITY JANITOR; FLOOR 1 UTILITY ROOM; FLOOR 1 VESTIBULE; Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 0.000 0.000 5.542364 0.00000000 1.000 -999.0000 1.00000 1.00000 1017.8527 1004.8586 1.2027 AHU-1 FAN Fan:VariableVolume 5.542364 6.66601638   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0000 -999.0   unknown unknown unknown unknown unknown Sensible 0.00 0.00 1.0000 6.66601638 5.542364 18.64 13.95 0.00800691 39036.6 -15.00 -15.00 0.00700000 2238.8 0.00000000 60.00 32.22 27.78 0.000 0.00 8.70 0.00699286 8.70 1.06558155 19.2261 21.01 0.00824828 -999.00 -999.0 -999.0000 0.00 0.00 0.00 0.00 6.66601638 -20.00 -20.00 0.00800691 -369.7 -20.00 -20.00 0.00800691 -369.7
AHU-2 COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC AHU-2 FLOOR 2 CONFERENCE; FLOOR 2 CONFERENCE TOILET; FLOOR 2 DICTATION; FLOOR 2 EXAM 1; FLOOR 2 EXAM 2; FLOOR 2 EXAM 3; FLOOR 2 EXAM 4; FLOOR 2 EXAM 5; FLOOR 2 EXAM 6; FLOOR 2 EXAM 7; FLOOR 2 EXAM 8; FLOOR 2 EXAM 9; FLOOR 2 EXAM HALL 1; FLOOR 2 EXAM HALL 2; FLOOR 2 EXAM HALL 3; FLOOR 2 EXAM HALL 4; FLOOR 2 EXAM HALL 5; FLOOR 2 EXAM HALL 6; FLOOR 2 JANITOR; FLOOR 2 LOUNGE; FLOOR 2 NURSE STATION 1; FLOOR 2 NURSE STATION 2; FLOOR 2 OFFICE; FLOOR 2 OFFICE HALL; FLOOR 2 RECEPTION; FLOOR 2 RECEPTION HALL; FLOOR 2 RECEPTION TOILET; FLOOR 2 SCHEDULING 1; FLOOR 2 SCHEDULING 2; FLOOR 2 STORAGE 1; FLOOR 2 STORAGE 2; FLOOR 2 STORAGE 3; FLOOR 2 UTILITY; FLOOR 2 WORK; FLOOR 2 WORK HALL; FLOOR 2 WORK TOILET; NE STAIR; NW ELEVATOR; NW STAIR; SW STAIR; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 141596.541 101966.980 6.052016 -999.0 -999.000 -999.0000 1.00000 1.00000 1024.6774 1004.8586 1.2027 AHU-2 FAN Fan:VariableVolume 6.052016 7.27899556   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 Sensible 142555.30 92506.63 1.0068 7.27899556 6.052016 23.55 18.03 0.01067129 50823.2 11.01 10.61 0.00780000 30725.4 -999.0 -999.00 -999.00 -999.00 13386.820 129168.48 28.67 0.01715859 24.15 1.26880000 20.9649 22.20 0.00895047 22.20 0.00895047 53.6281 71764.19 0.00 142006.07 102033.68 6.99153026 26.67 19.44 0.01118466 55322.4 12.38 12.37 0.00894305 35011.2
AHU-2 HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC AHU-2 FLOOR 2 CONFERENCE; FLOOR 2 CONFERENCE TOILET; FLOOR 2 DICTATION; FLOOR 2 EXAM 1; FLOOR 2 EXAM 2; FLOOR 2 EXAM 3; FLOOR 2 EXAM 4; FLOOR 2 EXAM 5; FLOOR 2 EXAM 6; FLOOR 2 EXAM 7; FLOOR 2 EXAM 8; FLOOR 2 EXAM 9; FLOOR 2 EXAM HALL 1; FLOOR 2 EXAM HALL 2; FLOOR 2 EXAM HALL 3; FLOOR 2 EXAM HALL 4; FLOOR 2 EXAM HALL 5; FLOOR 2 EXAM HALL 6; FLOOR 2 JANITOR; FLOOR 2 LOUNGE; FLOOR 2 NURSE STATION 1; FLOOR 2 NURSE STATION 2; FLOOR 2 OFFICE; FLOOR 2 OFFICE HALL; FLOOR 2 RECEPTION; FLOOR 2 RECEPTION HALL; FLOOR 2 RECEPTION TOILET; FLOOR 2 SCHEDULING 1; FLOOR 2 SCHEDULING 2; FLOOR 2 STORAGE 1; FLOOR 2 STORAGE 2; FLOOR 2 STORAGE 3; FLOOR 2 UTILITY; FLOOR 2 WORK; FLOOR 2 WORK HALL; FLOOR 2 WORK TOILET; NE STAIR; NW ELEVATOR; NW STAIR; SW STAIR; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 0.000 0.000 6.052016 0.00000000 1.000 -999.0000 1.00000 1.00000 1019.3398 1004.8586 1.2027 AHU-2 FAN Fan:VariableVolume 6.052016 7.27899556   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0000 -999.0   unknown unknown unknown unknown unknown Sensible 0.00 0.00 1.0000 7.27899556 6.052016 0.00 -6.26 0.00000000 25.0 -15.00 -15.00 0.00780000 4217.2 0.00000000 60.00 32.22 27.78 0.000 0.00 0.00 0.00000000 -6.26 1.26880000 20.9649 0.00 0.00000000 -999.00 -999.0 -999.0000 0.00 0.00 0.00 0.00 7.27899556 -20.00 -21.54 0.00000000 -20072.2 -20.00 -21.54 0.00000000 -20072.2
AHU-3 COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC AHU-3 FLOOR 3 DRESSING ROOM; FLOOR 3 ELEVATOR HALL; FLOOR 3 HUMID; FLOOR 3 JANITOR; FLOOR 3 LOCKER; FLOOR 3 LOUNGE; FLOOR 3 LOUNGE TOILET; FLOOR 3 MECHANICAL; FLOOR 3 MECHANICAL HALL; FLOOR 3 OFFICE; FLOOR 3 OFFICE HALL; FLOOR 3 OFFICE TOILET; FLOOR 3 PHYSICAL THERAPY 1; FLOOR 3 PHYSICAL THERAPY 2; FLOOR 3 PHYSICAL THERAPY TOILET; FLOOR 3 STORAGE 1; FLOOR 3 STORAGE 2; FLOOR 3 TREATMENT; FLOOR 3 UNDEVELOPED 1; FLOOR 3 UNDEVELOPED 2; FLOOR 3 UTILITY; FLOOR 3 WORK; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 137288.612 98131.993 5.770049 -999.0 -999.000 -999.0000 1.00000 1.00000 1024.0567 1004.8586 1.2027 AHU-3 FAN Fan:VariableVolume 5.770049 6.93986305   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 Sensible 134739.06 92628.16 0.9814 6.93986305 5.770049 24.25 17.99 0.01033737 50681.6 11.00 10.61 0.00780000 30724.2 -999.0 -999.00 -999.00 -999.00 12763.120 121975.94 33.20 0.01716721 25.32 1.07340000 18.6030 22.20 0.00877644 22.20 0.00877644 52.5974 68427.17 0.00 137685.68 98198.23 6.66579093 26.67 19.44 0.01118466 55322.4 12.24 12.23 0.00886203 34666.8
AHU-3 HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC AHU-3 FLOOR 3 DRESSING ROOM; FLOOR 3 ELEVATOR HALL; FLOOR 3 HUMID; FLOOR 3 JANITOR; FLOOR 3 LOCKER; FLOOR 3 LOUNGE; FLOOR 3 LOUNGE TOILET; FLOOR 3 MECHANICAL; FLOOR 3 MECHANICAL HALL; FLOOR 3 OFFICE; FLOOR 3 OFFICE HALL; FLOOR 3 OFFICE TOILET; FLOOR 3 PHYSICAL THERAPY 1; FLOOR 3 PHYSICAL THERAPY 2; FLOOR 3 PHYSICAL THERAPY TOILET; FLOOR 3 STORAGE 1; FLOOR 3 STORAGE 2; FLOOR 3 TREATMENT; FLOOR 3 UNDEVELOPED 1; FLOOR 3 UNDEVELOPED 2; FLOOR 3 UTILITY; FLOOR 3 WORK; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 0.000 0.000 5.770049 0.00000000 1.000 -999.0000 1.00000 1.00000 1019.3398 1004.8586 1.2027 AHU-3 FAN Fan:VariableVolume 5.770049 6.93986305   4197.9300 999.8980 1.16899298 54.44 82.22 27.78 454420.67 0.0000 -999.0   unknown unknown unknown unknown unknown Sensible 0.00 0.00 1.0000 6.93986305 5.770049 0.00 -6.26 0.00000000 25.0 -15.00 -15.00 0.00780000 4217.2 0.00000000 60.00 32.22 27.78 0.000 0.00 0.00 0.00000000 -6.26 1.07340000 18.6030 0.00 0.00000000 -999.00 -999.0 -999.0000 0.00 0.00 0.00 0.00 6.93986305 -20.00 -21.54 0.00000000 -20072.2 -20.00 -21.54 0.00000000 -20072.2
PSZ_CAFE HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_CAFE FLOOR 1 CAFE Non-Coincident CoolingDesignCapacity N/A No No unknown No 8922.420 6255.330 0.359310 -999.0 -999.000 -999.0000 1.00000 1.00000 1030.4345 1004.8586 1.2027 PSZ_CAFE_ADDAQ FAN Fan:SystemModel 0.359306 0.43215102   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 Sensible 4461.21 2464.02 1.0000 0.28810408 0.239540 27.84 21.68 0.01376824 63117.2 9.69 9.69 0.00850000 31143.0 -999.0 -999.00 -999.00 -999.00 0.000 4461.21 33.20 0.01716721 25.32 0.18434248 76.9569 22.19 0.01018705 22.19 0.01018705 60.9638 4255.97 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_CAFE HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_CAFE FLOOR 1 CAFE Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 8922.418 8922.418 0.359306 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_CAFE_ADDAQ FAN Fan:SystemModel 0.359306 0.43215102   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 4461.21 3851.86 1.0000 0.21607551 0.179653 14.74 11.87 0.00748328 33729.8 32.22 18.75 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 4461.21 8.70 0.00699286 8.70 0.18434248 102.6104 21.10 0.00800000 20.09 0.01335370 90.4596 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_CAFE_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ_CAFE FLOOR 1 CAFE Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 8922.418 8922.418 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_CAFE_ADDAQ FAN Fan:SystemModel 0.359306 0.43215102   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 8922.42 7703.71 1.0000 0.43215102 0.359306 14.74 11.87 0.00748328 33729.8 32.22 18.75 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 8922.42 8.70 0.00699286 8.70 0.18434248 51.3052 21.10 0.00800000 20.09 0.01335370 90.4596 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_ELEVATOR HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_ELEVATOR FLOOR 1 ELEVATOR PUMP ROOM Non-Coincident CoolingDesignCapacity N/A No No unknown No 1682.540 1346.873 0.096623 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.7929 1004.8586 1.2027 PSZ_ELEVATOR_ADDAQ FAN Fan:SystemModel 0.096623 0.11621241   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 Sensible 841.27 825.45 1.0000 0.07747491 0.064415 22.20 15.80 0.00858169 44123.3 9.67 9.67 0.00850000 31129.5 -999.0 -999.00 -999.00 -999.00 0.000 841.27 32.15 0.01716522 25.06 0.00000000 0.0000 22.20 0.00858169 22.20 0.00858169 51.4424 1145.94 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_ELEVATOR HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_ELEVATOR FLOOR 1 ELEVATOR PUMP ROOM Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 1599.456 1599.456 0.096623 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_ELEVATOR_ADDAQ FAN Fan:SystemModel 0.096623 0.11621241   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 799.73 660.31 1.0000 0.05810621 0.048312 21.08 14.18 0.00725124 39596.9 32.22 18.75 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 799.73 8.70 0.00699286 8.70 0.00000000 0.0000 21.08 0.00725124 21.10 0.00725124 46.5905 33.38 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_ELEVATOR_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ_ELEVATOR FLOOR 1 ELEVATOR PUMP ROOM Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 1599.456 1599.456 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_ELEVATOR_ADDAQ FAN Fan:SystemModel 0.096623 0.11621241   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1599.46 1320.62 1.0000 0.11621241 0.096623 21.08 14.18 0.00725124 39596.9 32.22 18.75 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 1599.46 8.70 0.00699286 8.70 0.00000000 0.0000 21.08 0.00725124 21.10 0.00725124 46.5905 33.38 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_MRI_CONTROL HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_MRI_CONTROL FLOOR 1 MRI CONTROL ROOM Non-Coincident CoolingDesignCapacity N/A No No unknown No 4054.940 3077.618 0.193870 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.0170 1004.8586 1.2027 PSZ_MRI_CONTROL_ADDAQ FAN Fan:SystemModel 0.193873 0.23317853   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 2027.47 1585.34 1.0000 0.15545000 0.129247 23.00 17.11 0.00977813 47986.3 9.67 9.67 0.00850000 31132.6 -999.0 -999.00 -999.00 -999.00 0.000 2027.47 28.24 0.01715778 24.03 0.02378614 18.4037 22.27 0.00874610 22.20 0.00874610 52.4214 2325.67 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_MRI_CONTROL HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_MRI_CONTROL FLOOR 1 MRI CONTROL ROOM Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 3877.793 3877.793 0.193873 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_MRI_CONTROL_ADDAQ FAN Fan:SystemModel 0.193873 0.23317853   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1938.90 1502.90 1.0000 0.11658926 0.096936 19.58 14.19 0.00787643 39658.6 32.22 18.75 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 1938.90 8.70 0.00699286 8.70 0.02378614 24.5379 21.10 0.00800000 24.91 0.00893323 45.4608 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_MRI_CONTROL_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ_MRI_CONTROL FLOOR 1 MRI CONTROL ROOM Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3877.793 3877.793 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_MRI_CONTROL_ADDAQ FAN Fan:SystemModel 0.193873 0.23317853   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 3877.79 3005.79 1.0000 0.23317853 0.193873 19.58 14.19 0.00787643 39658.6 32.22 18.75 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 3877.79 8.70 0.00699286 8.70 0.02378614 12.2689 21.10 0.00800000 24.91 0.00893323 45.4608 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_MRI HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_MRI FLOOR 1 MRI ROOM Non-Coincident CoolingDesignCapacity N/A No No unknown No 9890.230 7447.739 0.464840 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.2294 1004.8586 1.2027 PSZ_MRI_ADDAQ FAN Fan:SystemModel 0.464836 0.55907624   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 Sensible 4945.11 3797.94 1.0000 0.37272078 0.309893 23.07 17.23 0.00989238 48345.8 9.69 9.69 0.00850000 31149.6 -999.0 -999.00 -999.00 -999.00 0.000 4945.11 28.24 0.01715778 24.03 0.06229702 20.1027 22.27 0.00876798 22.20 0.00878555 52.6558 5240.26 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_MRI HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_MRI FLOOR 1 MRI ROOM Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 9457.213 9457.213 0.464836 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_MRI_ADDAQ FAN Fan:SystemModel 0.464836 0.55907624   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 4728.61 3643.44 1.0000 0.27953812 0.232418 19.44 14.12 0.00786502 39486.4 32.22 18.75 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 4728.61 8.70 0.00699286 8.70 0.06229702 26.8039 21.10 0.00800000 25.00 0.00850371 43.0658 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_MRI_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ_MRI FLOOR 1 MRI ROOM Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 9457.213 9457.213 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_MRI_ADDAQ FAN Fan:SystemModel 0.464836 0.55907624   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9457.21 7286.88 1.0000 0.55907624 0.464836 19.44 14.12 0.00786502 39486.4 32.22 18.75 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 9457.21 8.70 0.00699286 8.70 0.06229702 13.4019 21.10 0.00800000 25.00 0.00850371 43.0658 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_OR_1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_OR_1 FLOOR 1 OPERATING ROOM 1 Non-Coincident CoolingDesignCapacity N/A No No unknown No 17968.900 12597.636 0.723610 -999.0 -999.000 -999.0000 1.00000 1.00000 1026.1541 1004.8586 1.2027 PSZ_OR_1_ADDAQ FAN Fan:SystemModel 0.723607 0.87031080   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 Sensible 8984.45 5384.36 1.0000 0.58020928 0.482407 22.63 18.36 0.01146568 51898.9 6.10 6.10 0.00850000 27479.4 -999.0 -999.00 -999.00 -999.00 0.000 8984.45 30.82 0.01716268 24.71 0.23880519 49.5029 18.60 0.00865944 18.60 0.00866220 64.8521 7395.12 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_OR_1 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_OR_1 FLOOR 1 OPERATING ROOM 1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 17968.895 17968.895 0.723607 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_OR_1_ADDAQ FAN Fan:SystemModel 0.723607 0.87031080   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 8984.45 6023.16 1.0000 0.43515540 0.361804 15.64 12.33 0.00757714 34882.1 29.21 17.76 0.00800000 49793.3 -999.0 -999.00 -999.00 -999.00 0.000 8984.45 8.70 0.00699286 8.70 0.23880519 66.0041 19.05 0.00786494 21.34 0.00816519 51.6129 21.77 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_OR_1_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ_OR_1 FLOOR 1 OPERATING ROOM 1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 17968.895 17968.895 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_OR_1_ADDAQ FAN Fan:SystemModel 0.723607 0.87031080   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 17968.90 12046.31 1.0000 0.87031080 0.723607 15.64 12.33 0.00757714 34882.1 29.21 17.76 0.00800000 49793.3 -999.0 -999.00 -999.00 -999.00 0.000 17968.90 8.70 0.00699286 8.70 0.23880519 33.0020 19.05 0.00786494 21.34 0.00816519 51.6129 21.77 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_OR_2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_OR_2 FLOOR 1 OPERATING ROOM 2 Non-Coincident CoolingDesignCapacity N/A No No unknown No 18750.150 13145.355 0.755070 -999.0 -999.000 -999.0000 1.00000 1.00000 1026.1441 1004.8586 1.2027 PSZ_OR_2_ADDAQ FAN Fan:SystemModel 0.755069 0.90815040   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 Sensible 9375.08 5598.61 1.0000 0.60543473 0.503380 22.51 18.31 0.01146027 51764.2 6.10 6.10 0.00850000 27479.4 -999.0 -999.00 -999.00 -999.00 0.000 9375.08 30.46 0.01716200 24.62 0.24918803 49.5030 18.60 0.00865169 18.60 0.00865491 64.7978 7616.26 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_OR_2 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_OR_2 FLOOR 1 OPERATING ROOM 2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 18750.151 18750.151 0.755069 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_OR_2_ADDAQ FAN Fan:SystemModel 0.755069 0.90815040   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9375.08 6203.41 1.0000 0.45407520 0.377534 15.81 12.65 0.00782337 35684.7 29.21 17.76 0.00800000 49793.3 -999.0 -999.00 -999.00 -999.00 0.000 9375.08 8.70 0.00699286 8.70 0.24918803 66.0041 19.32 0.00823247 22.20 0.00833849 50.0032 29.19 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_OR_2_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ_OR_2 FLOOR 1 OPERATING ROOM 2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 18750.151 18750.151 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_OR_2_ADDAQ FAN Fan:SystemModel 0.755069 0.90815040   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 18750.15 12406.82 1.0000 0.90815040 0.755069 15.81 12.65 0.00782337 35684.7 29.21 17.76 0.00800000 49793.3 -999.0 -999.00 -999.00 -999.00 0.000 18750.15 8.70 0.00699286 8.70 0.24918803 33.0020 19.32 0.00823247 22.20 0.00833849 50.0032 29.19 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_OR_3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_OR_3 FLOOR 1 OPERATING ROOM 3 Non-Coincident CoolingDesignCapacity N/A No No unknown No 18593.900 13035.811 0.748780 -999.0 -999.000 -999.0000 1.00000 1.00000 1026.1441 1004.8586 1.2027 PSZ_OR_3_ADDAQ FAN Fan:SystemModel 0.748776 0.90058248   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:20:00 Sensible 9296.95 5341.02 1.0000 0.60039124 0.499187 21.53 17.99 0.01146031 50755.3 6.10 6.10 0.00850000 27479.4 -999.0 -999.00 -999.00 -999.00 0.000 9296.95 27.48 0.01715635 23.83 0.24711146 49.5028 18.60 0.00865454 18.60 0.00867635 64.9559 6139.54 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_OR_3 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_OR_3 FLOOR 1 OPERATING ROOM 3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 18593.900 18593.900 0.748776 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_OR_3_ADDAQ FAN Fan:SystemModel 0.748776 0.90058248   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9296.95 6146.09 1.0000 0.45029124 0.374388 15.82 12.85 0.00801887 36191.9 29.21 17.76 0.00800000 49793.3 -999.0 -999.00 -999.00 -999.00 0.000 9296.95 8.70 0.00699286 8.70 0.24711146 66.0041 19.33 0.00852427 22.20 0.00850194 50.9702 28.41 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_OR_3_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ_OR_3 FLOOR 1 OPERATING ROOM 3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 18593.900 18593.900 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_OR_3_ADDAQ FAN Fan:SystemModel 0.748776 0.90058248   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 18593.90 12292.19 1.0000 0.90058248 0.748776 15.82 12.85 0.00801887 36191.9 29.21 17.76 0.00800000 49793.3 -999.0 -999.00 -999.00 -999.00 0.000 18593.90 8.70 0.00699286 8.70 0.24711146 33.0020 19.33 0.00852427 22.20 0.00850194 50.9702 28.41 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_XRAY HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_XRAY FLOOR 2 X-RAY Non-Coincident CoolingDesignCapacity N/A No No unknown No 22311.110 16936.810 1.067250 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.0239 1004.8586 1.2027 PSZ_XRAY_ADDAQ FAN Fan:SystemModel 1.067253 1.28362690   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 11155.56 8714.04 1.0000 0.85574875 0.711500 22.98 17.11 0.00978182 47975.2 9.74 9.74 0.00850000 31197.2 -999.0 -999.00 -999.00 -999.00 0.000 11155.56 28.24 0.01715778 24.03 0.12742573 17.9094 22.27 0.00878175 22.20 0.00878175 52.6336 10916.98 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_XRAY HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ_XRAY FLOOR 2 X-RAY Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 21252.039 21252.039 1.067253 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_XRAY_ADDAQ FAN Fan:SystemModel 1.067253 1.28362690   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 10626.02 8246.59 1.0000 0.64181345 0.533627 19.62 14.20 0.00787975 39708.6 32.22 18.75 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 10626.02 8.70 0.00699286 8.70 0.12742573 23.8792 21.10 0.00800000 25.00 0.00850375 43.0660 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ_XRAY_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ_XRAY FLOOR 2 X-RAY Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 21252.039 21252.039 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 PSZ_XRAY_ADDAQ FAN Fan:SystemModel 1.067253 1.28362690   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 21252.04 16493.18 1.0000 1.28362690 1.067253 19.62 14.20 0.00787975 39708.6 32.22 18.75 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 21252.04 8.70 0.00699286 8.70 0.12742573 11.9396 21.10 0.00800000 25.00 0.00850375 43.0660 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
FLOOR 1 ANESTHESIA AHU-1_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 BIO HAZ AHU-1_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 CLEAN AHU-1_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 CLEAN WORK AHU-1_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 DICTATION AHU-1_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 DRESSING ROOM AHU-1_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 ELECTRICAL ROOM AHU-1_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 HUMID AHU-1_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 IT HALL AHU-1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 IT ROOM AHU-1_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 LOBBY AHU-1_DCV 0.000000 0.000559 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 LOBBY HALL AHU-1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 LOBBY TOILET AHU-1_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 LOCKER ROOM AHU-1_DCV 0.000000 0.000686 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 LOCKER ROOM HALL AHU-1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 LOUNGE AHU-1_DCV 0.000000 0.000686 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 MED GAS AHU-1_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 MRI HALL AHU-1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 MRI TOILET AHU-1_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 NOURISHMENT AHU-1_DCV 0.000000 0.000813 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 NURSE HALL AHU-1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 NURSE JANITOR AHU-1_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 NURSE STATION AHU-1_DCV 0.000000 0.000813 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 NURSE TOILET AHU-1_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 OFFICE AHU-1_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 PACU AHU-1_DCV 0.000000 0.003217 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 PRE-OP HALL AHU-1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 PRE-OP ROOM 1 AHU-1_DCV 0.000000 0.002963 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 PRE-OP ROOM 2 AHU-1_DCV 0.000000 0.002963 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 PRE-OP TOILET AHU-1_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 PROCEDURE ROOM AHU-1_DCV 0.000000 0.004064 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 RECEPTION AHU-1_DCV 0.000000 0.001067 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 RECEPTION HALL AHU-1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 RECOVERY ROOM AHU-1_DCV 0.000000 0.003217 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 SCHEDULING AHU-1_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 SCRUB AHU-1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 SOIL AHU-1_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 SOIL HOLD AHU-1_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 SOIL WORK AHU-1_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 STEP DOWN AHU-1_DCV 0.000000 0.003217 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 STERILE HALL AHU-1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 STERILE STORAGE AHU-1_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 STORAGE AHU-1_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 SUB-STERILE AHU-1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 UTILITY HALL AHU-1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 UTILITY JANITOR AHU-1_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 UTILITY ROOM AHU-1_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 1 VESTIBULE AHU-1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 CONFERENCE AHU-2_DCV 0.000000 0.001575 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 CONFERENCE TOILET AHU-2_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 DICTATION AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM 1 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM 2 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM 3 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM 4 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM 5 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM 6 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM 7 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM 8 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM 9 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM HALL 1 AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM HALL 2 AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM HALL 3 AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM HALL 4 AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM HALL 5 AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 EXAM HALL 6 AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 JANITOR AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 LOUNGE AHU-2_DCV 0.000000 0.000686 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 NURSE STATION 1 AHU-2_DCV 0.000000 0.000813 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 NURSE STATION 2 AHU-2_DCV 0.000000 0.000813 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 OFFICE AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 OFFICE HALL AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 RECEPTION AHU-2_DCV 0.000000 0.001067 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 RECEPTION HALL AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 RECEPTION TOILET AHU-2_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 SCHEDULING 1 AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 SCHEDULING 2 AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 STORAGE 1 AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 STORAGE 2 AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 STORAGE 3 AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 UTILITY AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 WORK AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 WORK HALL AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 2 WORK TOILET AHU-2_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 DRESSING ROOM AHU-3_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 ELEVATOR HALL AHU-3_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 HUMID AHU-3_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 JANITOR AHU-3_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 LOCKER AHU-3_DCV 0.000000 0.000686 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 LOUNGE AHU-3_DCV 0.000000 0.000686 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 LOUNGE TOILET AHU-3_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 MECHANICAL AHU-3_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 MECHANICAL HALL AHU-3_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 OFFICE AHU-3_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 OFFICE HALL AHU-3_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 OFFICE TOILET AHU-3_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 PHYSICAL THERAPY 1 AHU-3_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 PHYSICAL THERAPY 2 AHU-3_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 PHYSICAL THERAPY TOILET AHU-3_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 STORAGE 1 AHU-3_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 STORAGE 2 AHU-3_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 TREATMENT AHU-3_DCV 0.000000 0.001524 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 UNDEVELOPED 1 AHU-3_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 UNDEVELOPED 2 AHU-3_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 UTILITY AHU-3_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
FLOOR 3 WORK AHU-3_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
NE STAIR AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
NW ELEVATOR AHU-2_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
NW STAIR AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
SW STAIR AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FLOOR 1 ANESTHESIA 53.83 4739.33 53.67
FLOOR 1 BIO HAZ 5.00 4745.00 5.00
FLOOR 1 CAFE 2907.50 2191.50 1264.00
FLOOR 1 CLEAN 288.83 4721.83 288.83
FLOOR 1 CLEAN WORK 509.50 4745.00 509.50
FLOOR 1 DICTATION 0.00 4132.67 0.00
FLOOR 1 DRESSING ROOM 485.50 3441.17 50.33
FLOOR 1 ELECTRICAL ROOM 372.50 3806.50 2.17
FLOOR 1 ELEVATOR PUMP ROOM 1585.50 820.67 0.00
FLOOR 1 HUMID 0.00 4088.33 0.00
FLOOR 1 IT HALL 0.00 4745.00 0.00
FLOOR 1 IT ROOM 0.00 4139.00 0.00
FLOOR 1 LOBBY 660.50 3566.67 0.00
FLOOR 1 LOBBY HALL 77.33 4034.67 0.00
FLOOR 1 LOBBY TOILET 27.83 4690.17 13.17
FLOOR 1 LOCKER ROOM 327.50 3708.67 0.00
FLOOR 1 LOCKER ROOM HALL 0.00 4745.00 0.00
FLOOR 1 LOUNGE 48.33 4329.17 0.00
FLOOR 1 MED GAS 654.50 4114.50 181.67
FLOOR 1 MRI CONTROL ROOM 1465.50 1085.00 0.33
FLOOR 1 MRI HALL 0.00 4699.67 0.00
FLOOR 1 MRI ROOM 1549.67 290.33 0.00
FLOOR 1 MRI TOILET 48.33 4745.00 48.33
FLOOR 1 NOURISHMENT 4.00 4649.50 0.00
FLOOR 1 NURSE HALL 0.00 4745.00 0.00
FLOOR 1 NURSE JANITOR 0.00 4742.83 0.00
FLOOR 1 NURSE STATION 0.00 4693.50 0.00
FLOOR 1 NURSE TOILET 675.00 4745.00 675.00
FLOOR 1 OFFICE 0.00 4052.83 0.00
FLOOR 1 OPERATING ROOM 1 463.50 4709.83 463.50
FLOOR 1 OPERATING ROOM 2 662.83 4745.00 662.83
FLOOR 1 OPERATING ROOM 3 814.83 4745.00 814.83
FLOOR 1 PACU 476.67 4742.33 476.67
FLOOR 1 PRE-OP HALL 0.00 4745.00 0.00
FLOOR 1 PRE-OP ROOM 1 107.83 4745.00 107.83
FLOOR 1 PRE-OP ROOM 2 235.33 4729.67 235.33
FLOOR 1 PRE-OP TOILET 40.50 4744.83 40.50
FLOOR 1 PROCEDURE ROOM 185.83 4735.00 185.83
FLOOR 1 RECEPTION 247.83 3800.50 0.00
FLOOR 1 RECEPTION HALL 0.00 4744.67 0.00
FLOOR 1 RECOVERY ROOM 29.33 4592.17 18.33
FLOOR 1 SCHEDULING 6.17 4054.33 2.33
FLOOR 1 SCRUB 0.00 4745.00 0.00
FLOOR 1 SOIL 510.17 4743.67 510.17
FLOOR 1 SOIL HOLD 244.33 4745.00 244.33
FLOOR 1 SOIL WORK 561.67 4745.00 561.67
FLOOR 1 STEP DOWN 42.67 4473.33 20.00
FLOOR 1 STERILE HALL 0.00 4745.00 0.00
FLOOR 1 STERILE STORAGE 0.00 4745.00 0.00
FLOOR 1 STORAGE 404.83 4201.83 70.33
FLOOR 1 SUB-STERILE 116.00 4444.00 5.50
FLOOR 1 UTILITY HALL 267.33 4410.17 51.50
FLOOR 1 UTILITY JANITOR 0.00 4745.00 0.00
FLOOR 1 UTILITY ROOM 151.50 4392.33 4.50
FLOOR 1 VESTIBULE 2888.00 4351.17 2645.83
FLOOR 2 CONFERENCE 799.83 1975.50 170.67
FLOOR 2 CONFERENCE TOILET 3.67 4744.00 3.67
FLOOR 2 DICTATION 0.00 4115.83 0.00
FLOOR 2 EXAM 1 492.00 3729.00 132.67
FLOOR 2 EXAM 2 81.00 4650.00 43.00
FLOOR 2 EXAM 3 49.67 4717.33 42.50
FLOOR 2 EXAM 4 222.17 4373.33 102.50
FLOOR 2 EXAM 5 257.17 3836.50 86.17
FLOOR 2 EXAM 6 97.17 4707.67 87.17
FLOOR 2 EXAM 7 49.00 4688.00 38.33
FLOOR 2 EXAM 8 112.83 4677.00 82.00
FLOOR 2 EXAM 9 71.00 4647.67 38.33
FLOOR 2 EXAM HALL 1 2.17 4602.83 0.17
FLOOR 2 EXAM HALL 2 0.50 4697.17 0.00
FLOOR 2 EXAM HALL 3 0.00 4743.83 0.00
FLOOR 2 EXAM HALL 4 0.00 4710.50 0.00
FLOOR 2 EXAM HALL 5 9.00 4634.50 0.00
FLOOR 2 EXAM HALL 6 3.33 4666.50 0.00
FLOOR 2 JANITOR 748.83 4068.00 337.83
FLOOR 2 LOUNGE 68.67 4526.17 0.00
FLOOR 2 NURSE STATION 1 122.67 4345.50 0.00
FLOOR 2 NURSE STATION 2 207.83 4166.33 0.00
FLOOR 2 OFFICE 617.83 3096.17 109.67
FLOOR 2 OFFICE HALL 0.00 4704.83 0.00
FLOOR 2 RECEPTION 1050.50 2900.67 108.50
FLOOR 2 RECEPTION HALL 14.50 4579.50 0.00
FLOOR 2 RECEPTION TOILET 16.33 4589.33 1.00
FLOOR 2 SCHEDULING 1 48.00 3898.50 0.00
FLOOR 2 SCHEDULING 2 146.33 3766.50 0.00
FLOOR 2 STORAGE 1 0.00 4745.00 0.00
FLOOR 2 STORAGE 2 0.00 4731.17 0.00
FLOOR 2 STORAGE 3 6.67 4612.33 0.00
FLOOR 2 UTILITY 435.50 4199.33 112.50
FLOOR 2 WORK 342.50 3064.00 12.33
FLOOR 2 WORK HALL 63.83 4460.00 0.00
FLOOR 2 WORK TOILET 128.33 4700.83 113.67
FLOOR 2 X-RAY 1502.50 842.50 187.67
FLOOR 3 DRESSING ROOM 0.00 4139.00 0.00
FLOOR 3 ELEVATOR HALL 217.67 4308.00 5.83
FLOOR 3 HUMID 0.00 4082.83 0.00
FLOOR 3 JANITOR 537.50 4263.83 177.83
FLOOR 3 LOCKER 208.50 4255.17 0.33
FLOOR 3 LOUNGE 603.67 3535.67 1.17
FLOOR 3 LOUNGE TOILET 64.67 4706.00 52.50
FLOOR 3 MECHANICAL 2039.50 1148.83 90.83
FLOOR 3 MECHANICAL HALL 187.67 4339.17 1.67
FLOOR 3 OFFICE 445.17 3436.17 3.33
FLOOR 3 OFFICE HALL 143.67 4377.67 0.83
FLOOR 3 OFFICE TOILET 98.50 4689.17 80.83
FLOOR 3 PHYSICAL THERAPY 1 417.67 2686.00 34.33
FLOOR 3 PHYSICAL THERAPY 2 6.83 4745.00 6.83
FLOOR 3 PHYSICAL THERAPY TOILET 1.00 4745.00 1.00
FLOOR 3 STORAGE 1 8.00 4745.00 8.00
FLOOR 3 STORAGE 2 45.33 4575.50 0.33
FLOOR 3 TREATMENT 1.00 4745.00 1.00
FLOOR 3 UNDEVELOPED 1 647.50 3332.17 3.67
FLOOR 3 UNDEVELOPED 2 707.17 3375.67 6.17
FLOOR 3 UTILITY 0.00 4736.33 0.00
FLOOR 3 WORK 622.00 2600.67 30.33
NE STAIR 983.67 3266.17 422.67
NW ELEVATOR 946.17 3943.83 361.00
NW STAIR 991.67 3260.50 414.17
SW STAIR 1115.50 3346.00 358.33
Facility 4179.17 4745.00 3725.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FLOOR 1 ANESTHESIA 0.00 0.00 0.00 0.00
FLOOR 1 BIO HAZ 0.00 0.00 0.00 0.00
FLOOR 1 CAFE 0.00 1247.33 0.00 1247.33
FLOOR 1 CLEAN 0.00 0.00 0.00 0.00
FLOOR 1 CLEAN WORK 0.00 0.00 0.00 0.00
FLOOR 1 DICTATION 0.00 0.00 0.00 0.00
FLOOR 1 DRESSING ROOM 0.00 29.17 0.00 29.00
FLOOR 1 ELECTRICAL ROOM 0.00 59.50 0.00 19.50
FLOOR 1 ELEVATOR PUMP ROOM 0.00 0.00 0.00 0.00
FLOOR 1 HUMID 0.00 0.00 0.00 0.00
FLOOR 1 IT HALL 0.00 0.00 0.00 0.00
FLOOR 1 IT ROOM 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY 0.00 30.83 0.00 24.00
FLOOR 1 LOBBY HALL 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 0.00 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM 0.00 16.50 0.00 0.67
FLOOR 1 LOCKER ROOM HALL 0.00 0.00 0.00 0.00
FLOOR 1 LOUNGE 0.00 1.67 0.00 0.00
FLOOR 1 MED GAS 0.50 60.33 0.00 52.33
FLOOR 1 MRI CONTROL ROOM 0.00 0.00 0.00 0.00
FLOOR 1 MRI HALL 0.00 0.00 0.00 0.00
FLOOR 1 MRI ROOM 0.00 0.00 0.00 0.00
FLOOR 1 MRI TOILET 0.00 0.00 0.00 0.00
FLOOR 1 NOURISHMENT 0.00 0.00 0.00 0.00
FLOOR 1 NURSE HALL 0.00 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR 0.00 0.00 0.00 0.00
FLOOR 1 NURSE STATION 0.00 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 0.00 0.00 0.00 0.00
FLOOR 1 OFFICE 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 1 0.00 502.17 0.00 502.17
FLOOR 1 OPERATING ROOM 2 0.00 353.17 0.00 353.17
FLOOR 1 OPERATING ROOM 3 0.00 7.33 0.00 7.33
FLOOR 1 PACU 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 1 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 2 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 0.00 0.00 0.00 0.00
FLOOR 1 PROCEDURE ROOM 0.00 0.00 0.00 0.00
FLOOR 1 RECEPTION 0.00 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL 0.00 0.00 0.00 0.00
FLOOR 1 RECOVERY ROOM 0.00 0.00 0.00 0.00
FLOOR 1 SCHEDULING 0.00 0.00 0.00 0.00
FLOOR 1 SCRUB 0.00 0.00 0.00 0.00
FLOOR 1 SOIL 0.00 0.00 0.00 0.00
FLOOR 1 SOIL HOLD 0.00 0.00 0.00 0.00
FLOOR 1 SOIL WORK 0.00 0.00 0.00 0.00
FLOOR 1 STEP DOWN 0.00 0.00 0.00 0.00
FLOOR 1 STERILE HALL 0.00 0.00 0.00 0.00
FLOOR 1 STERILE STORAGE 0.00 0.00 0.00 0.00
FLOOR 1 STORAGE 0.00 17.50 0.00 17.33
FLOOR 1 SUB-STERILE 0.00 3.17 0.00 3.17
FLOOR 1 UTILITY HALL 0.00 23.50 0.00 23.50
FLOOR 1 UTILITY JANITOR 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 0.00 0.83 0.00 0.83
FLOOR 1 VESTIBULE 339.50 2290.67 339.50 2282.17
FLOOR 2 CONFERENCE 0.00 28.00 0.00 28.00
FLOOR 2 CONFERENCE TOILET 0.00 0.00 0.00 0.00
FLOOR 2 DICTATION 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 1 0.00 5.33 0.00 5.33
FLOOR 2 EXAM 2 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 3 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 4 0.00 23.50 0.00 23.50
FLOOR 2 EXAM 5 0.00 1.17 0.00 1.17
FLOOR 2 EXAM 6 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 7 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 8 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 9 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 1 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 2 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 3 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 4 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 5 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 6 0.00 0.00 0.00 0.00
FLOOR 2 JANITOR 0.00 35.33 0.00 14.00
FLOOR 2 LOUNGE 0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 1 0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 2 0.00 0.00 0.00 0.00
FLOOR 2 OFFICE 0.00 25.50 0.00 25.50
FLOOR 2 OFFICE HALL 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION 0.00 18.17 0.00 17.17
FLOOR 2 RECEPTION HALL 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 1 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 2 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 1 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 2 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 3 0.00 0.00 0.00 0.00
FLOOR 2 UTILITY 0.00 15.17 0.00 15.17
FLOOR 2 WORK 0.00 1.33 0.00 0.00
FLOOR 2 WORK HALL 0.00 0.00 0.00 0.00
FLOOR 2 WORK TOILET 0.00 0.00 0.00 0.00
FLOOR 2 X-RAY 0.00 0.00 0.00 0.00
FLOOR 3 DRESSING ROOM 0.00 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 0.00 0.00 0.00 0.00
FLOOR 3 HUMID 0.00 0.00 0.00 0.00
FLOOR 3 JANITOR 0.33 45.17 0.00 23.83
FLOOR 3 LOCKER 0.00 0.50 0.00 0.50
FLOOR 3 LOUNGE 0.00 32.83 0.00 29.33
FLOOR 3 LOUNGE TOILET 0.00 0.00 0.00 0.00
FLOOR 3 MECHANICAL 0.00 461.67 0.00 151.33
FLOOR 3 MECHANICAL HALL 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE 0.00 9.00 0.00 9.00
FLOOR 3 OFFICE HALL 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE TOILET 0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY 1 0.00 3.33 0.00 3.33
FLOOR 3 PHYSICAL THERAPY 2 0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 1 0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 2 0.00 0.00 0.00 0.00
FLOOR 3 TREATMENT 0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 1 0.00 39.83 0.00 39.33
FLOOR 3 UNDEVELOPED 2 0.00 62.17 0.00 58.67
FLOOR 3 UTILITY 0.00 0.00 0.00 0.00
FLOOR 3 WORK 0.00 52.17 0.00 51.83
NE STAIR 3.50 85.83 0.33 67.83
NW ELEVATOR 0.00 81.67 0.00 39.67
NW STAIR 1.17 102.67 0.00 63.33
SW STAIR 0.00 129.17 0.00 76.83
Facility 343.83 2919.00 339.83 2557.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
FLOOR 1 ANESTHESIA 1.31 2.16 30.58 2.541 0.051 0.000 0.000
FLOOR 1 BIO HAZ 0.07 0.11 15.86 0.389 0.000 0.000 0.000
FLOOR 1 CAFE 25.44 42.00 118.93 4.731 0.030 0.000 0.000
FLOOR 1 CLEAN 1.53 2.52 35.68 2.430 0.000 0.000 0.000
FLOOR 1 CLEAN WORK 2.00 3.30 46.72 2.321 0.000 0.000 0.000
FLOOR 1 DICTATION 0.36 0.63 35.68 0.537 0.000 0.000 0.000
FLOOR 1 DRESSING ROOM 0.13 0.23 12.74 1.044 0.128 0.000 0.000
FLOOR 1 ELECTRICAL ROOM 0.09 0.15 27.75 1.453 0.044 0.000 0.000
FLOOR 1 ELEVATOR PUMP ROOM 0.08 0.14 25.77 0.000 0.136 0.000 0.000
FLOOR 1 HUMID 0.16 0.27 15.29 0.682 0.000 0.000 0.000
FLOOR 1 IT HALL 0.42 0.70 39.64 0.415 0.000 0.000 0.000
FLOOR 1 IT ROOM 0.32 0.56 31.71 0.565 0.000 0.000 0.000
FLOOR 1 LOBBY 3.77 6.22 176.13 0.993 0.022 0.000 0.000
FLOOR 1 LOBBY HALL 0.73 1.20 67.96 0.713 0.000 0.000 0.000
FLOOR 1 LOBBY TOILET 0.16 0.27 15.29 2.267 0.068 0.000 0.000
FLOOR 1 LOCKER ROOM 6.00 9.90 186.89 1.094 0.021 0.000 0.000
FLOOR 1 LOCKER ROOM HALL 1.50 2.48 140.45 0.437 0.000 0.000 0.000
FLOOR 1 LOUNGE 3.27 5.40 101.94 1.043 0.000 0.000 0.000
FLOOR 1 MED GAS 0.07 0.11 15.86 0.928 0.165 0.000 0.000
FLOOR 1 MRI CONTROL ROOM 2.04 3.36 47.57 1.518 0.000 0.000 0.000
FLOOR 1 MRI HALL 0.45 0.73 41.63 0.610 0.000 0.000 0.000
FLOOR 1 MRI ROOM 5.33 8.80 124.59 1.518 0.000 0.000 0.000
FLOOR 1 MRI TOILET 0.16 0.27 15.29 1.964 0.068 0.000 0.000
FLOOR 1 NOURISHMENT 1.65 2.73 51.54 0.869 0.000 0.000 0.000
FLOOR 1 NURSE HALL 1.50 2.48 140.45 0.400 0.000 0.000 0.000
FLOOR 1 NURSE JANITOR 0.07 0.11 15.29 0.496 0.000 0.000 0.000
FLOOR 1 NURSE STATION 2.37 3.91 73.91 0.795 0.000 0.000 0.000
FLOOR 1 NURSE TOILET 0.16 0.27 15.29 1.887 0.000 0.000 0.000
FLOOR 1 OFFICE 1.40 2.42 136.77 0.573 0.000 0.000 0.000
FLOOR 1 OPERATING ROOM 1 5.57 9.20 130.26 5.499 0.057 0.000 0.000
FLOOR 1 OPERATING ROOM 2 5.82 9.60 135.92 5.498 0.030 0.000 0.000
FLOOR 1 OPERATING ROOM 3 5.77 9.52 134.79 5.497 0.000 0.000 0.000
FLOOR 1 PACU 1.31 2.16 30.58 2.505 0.000 0.000 0.000
FLOOR 1 PRE-OP HALL 1.60 2.64 149.51 0.427 0.000 0.000 0.000
FLOOR 1 PRE-OP ROOM 1 1.14 1.89 53.52 1.979 0.013 0.000 0.000
FLOOR 1 PRE-OP ROOM 2 2.05 3.38 95.71 1.978 0.000 0.000 0.000
FLOOR 1 PRE-OP TOILET 0.16 0.27 15.29 1.915 0.068 0.000 0.000
FLOOR 1 PROCEDURE ROOM 3.45 5.70 80.70 4.942 0.041 0.000 0.000
FLOOR 1 RECEPTION 9.25 15.27 144.13 1.124 0.016 0.000 0.000
FLOOR 1 RECEPTION HALL 0.39 0.64 36.25 0.489 0.000 0.000 0.000
FLOOR 1 RECOVERY ROOM 6.54 10.80 152.91 2.253 0.051 0.000 0.000
FLOOR 1 SCHEDULING 0.34 0.60 33.70 0.668 0.038 0.000 0.000
FLOOR 1 SCRUB 0.25 0.42 23.79 0.502 0.000 0.000 0.000
FLOOR 1 SOIL 1.53 2.52 35.68 2.427 0.000 0.000 0.000
FLOOR 1 SOIL HOLD 0.68 1.12 15.86 2.548 0.000 0.000 0.000
FLOOR 1 SOIL WORK 2.18 3.60 50.97 2.257 0.000 0.000 0.000
FLOOR 1 STEP DOWN 3.63 6.00 84.95 2.077 0.076 0.000 0.000
FLOOR 1 STERILE HALL 1.87 3.08 174.43 0.448 0.000 0.000 0.000
FLOOR 1 STERILE STORAGE 0.48 0.79 112.13 0.348 0.000 0.000 0.000
FLOOR 1 STORAGE 1.11 1.84 260.51 0.505 0.042 0.000 0.000
FLOOR 1 SUB-STERILE 0.59 0.98 55.50 0.735 0.044 0.000 0.000
FLOOR 1 UTILITY HALL 0.78 1.28 72.49 0.830 0.038 0.000 0.000
FLOOR 1 UTILITY JANITOR 0.05 0.08 11.89 0.510 0.000 0.000 0.000
FLOOR 1 UTILITY ROOM 0.44 0.72 101.94 0.543 0.031 0.000 0.000
FLOOR 1 VESTIBULE 0.22 0.36 20.39 1.649 125.200 0.000 0.000
FLOOR 2 CONFERENCE 9.75 16.80 95.14 1.595 0.115 0.000 0.000
FLOOR 2 CONFERENCE TOILET 0.19 0.32 18.12 1.350 0.000 0.000 0.000
FLOOR 2 DICTATION 0.20 0.35 19.82 0.656 0.000 0.000 0.000
FLOOR 2 EXAM 1 4.36 7.20 101.94 1.398 0.104 0.000 0.000
FLOOR 2 EXAM 2 6.54 10.80 152.91 1.485 0.029 0.000 0.000
FLOOR 2 EXAM 3 8.72 14.40 203.88 1.484 0.029 0.000 0.000
FLOOR 2 EXAM 4 1.02 1.68 23.79 1.488 0.074 0.000 0.000
FLOOR 2 EXAM 5 4.24 7.00 99.11 1.654 0.063 0.000 0.000
FLOOR 2 EXAM 6 2.73 4.50 63.71 1.561 0.059 0.000 0.000
FLOOR 2 EXAM 7 9.60 15.84 224.27 1.484 0.027 0.000 0.000
FLOOR 2 EXAM 8 3.27 5.40 76.46 1.559 0.059 0.000 0.000
FLOOR 2 EXAM 9 4.80 7.92 112.13 1.569 0.027 0.000 0.000
FLOOR 2 EXAM HALL 1 0.55 0.90 50.97 0.670 0.000 0.000 0.000
FLOOR 2 EXAM HALL 2 0.55 0.90 50.97 0.614 0.000 0.000 0.000
FLOOR 2 EXAM HALL 3 0.55 0.90 50.97 0.560 0.000 0.000 0.000
FLOOR 2 EXAM HALL 4 0.60 0.99 56.07 0.578 0.000 0.000 0.000
FLOOR 2 EXAM HALL 5 0.60 0.99 56.07 0.631 0.000 0.000 0.000
FLOOR 2 EXAM HALL 6 0.60 0.99 56.07 0.598 0.000 0.000 0.000
FLOOR 2 JANITOR 0.08 0.13 17.84 0.758 0.226 0.000 0.000
FLOOR 2 LOUNGE 0.73 1.20 22.65 1.141 0.000 0.000 0.000
FLOOR 2 NURSE STATION 1 1.36 2.25 42.48 1.009 0.000 0.000 0.000
FLOOR 2 NURSE STATION 2 1.64 2.70 50.97 1.045 0.000 0.000 0.000
FLOOR 2 OFFICE 1.62 2.80 158.57 0.959 0.066 0.000 0.000
FLOOR 2 OFFICE HALL 1.34 2.22 125.73 0.600 0.000 0.000 0.000
FLOOR 2 RECEPTION 17.88 29.52 278.64 1.292 0.044 0.000 0.000
FLOOR 2 RECEPTION HALL 1.71 2.82 159.71 0.662 0.000 0.000 0.000
FLOOR 2 RECEPTION TOILET 0.38 0.63 35.68 1.260 0.000 0.000 0.000
FLOOR 2 SCHEDULING 1 0.94 1.62 91.75 0.670 0.000 0.000 0.000
FLOOR 2 SCHEDULING 2 0.99 1.71 96.84 0.699 0.000 0.000 0.000
FLOOR 2 STORAGE 1 0.07 0.11 15.86 0.451 0.000 0.000 0.000
FLOOR 2 STORAGE 2 0.15 0.24 33.98 0.472 0.000 0.000 0.000
FLOOR 2 STORAGE 3 0.17 0.29 40.78 0.526 0.000 0.000 0.000
FLOOR 2 UTILITY 0.15 0.25 35.68 0.874 0.063 0.000 0.000
FLOOR 2 WORK 4.88 8.45 478.55 0.644 0.014 0.000 0.000
FLOOR 2 WORK HALL 2.53 4.17 236.16 0.687 0.000 0.000 0.000
FLOOR 2 WORK TOILET 0.16 0.27 15.29 1.436 0.098 0.000 0.000
FLOOR 2 X-RAY 10.90 18.00 254.85 2.188 0.000 0.000 0.000
FLOOR 3 DRESSING ROOM 0.12 0.21 11.89 0.804 0.000 0.000 0.000
FLOOR 3 ELEVATOR HALL 1.12 1.85 104.77 0.609 0.011 0.000 0.000
FLOOR 3 HUMID 0.31 0.54 30.58 0.823 0.000 0.000 0.000
FLOOR 3 JANITOR 0.08 0.13 17.84 0.703 0.267 0.000 0.000
FLOOR 3 LOCKER 1.09 1.80 33.98 1.281 0.000 0.000 0.000
FLOOR 3 LOUNGE 6.90 11.39 214.92 1.282 0.032 0.000 0.000
FLOOR 3 LOUNGE TOILET 0.58 0.96 54.37 1.438 0.065 0.000 0.000
FLOOR 3 MECHANICAL 0.32 0.53 99.11 2.361 0.075 0.000 0.000
FLOOR 3 MECHANICAL HALL 0.91 1.50 84.95 0.742 0.000 0.000 0.000
FLOOR 3 OFFICE 8.77 15.18 859.70 0.723 0.027 0.000 0.000
FLOOR 3 OFFICE HALL 2.53 4.17 236.16 0.686 0.008 0.000 0.000
FLOOR 3 OFFICE TOILET 0.16 0.27 15.29 1.491 0.116 0.000 0.000
FLOOR 3 PHYSICAL THERAPY 1 15.75 26.00 368.12 1.550 0.069 0.000 0.000
FLOOR 3 PHYSICAL THERAPY 2 7.17 11.84 167.64 1.287 0.000 0.000 0.000
FLOOR 3 PHYSICAL THERAPY TOILET 0.25 0.42 23.79 1.423 0.000 0.000 0.000
FLOOR 3 STORAGE 1 0.13 0.22 30.58 1.242 0.000 0.000 0.000
FLOOR 3 STORAGE 2 0.10 0.17 23.79 0.614 0.000 0.000 0.000
FLOOR 3 TREATMENT 5.77 9.52 134.79 1.349 0.000 0.000 0.000
FLOOR 3 UNDEVELOPED 1 2.75 4.54 642.23 0.811 0.033 0.000 0.000
FLOOR 3 UNDEVELOPED 2 1.40 2.30 326.21 0.863 0.051 0.000 0.000
FLOOR 3 UTILITY 0.26 0.43 61.16 0.487 0.000 0.000 0.000
FLOOR 3 WORK 1.66 2.87 162.54 1.079 0.078 0.000 0.000
NE STAIR 0.51 0.84 142.72 0.698 0.185 0.000 0.000
NW ELEVATOR 0.13 0.21 118.93 0.563 0.171 0.000 0.000
NW STAIR 0.58 0.96 163.10 0.659 0.185 0.000 0.000
SW STAIR 0.29 0.48 81.55 0.744 0.185 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
FLOOR 1 ANESTHESIA 1.31 2.16 30.58 0.000 0.000 0.000 0.000
FLOOR 1 BIO HAZ 0.07 0.11 15.86 0.000 0.000 0.000 0.000
FLOOR 1 CAFE 25.44 42.00 118.93 0.000 0.000 0.000 0.000
FLOOR 1 CLEAN 1.53 2.52 35.68 0.000 0.000 0.000 0.000
FLOOR 1 CLEAN WORK 2.00 3.30 46.72 0.000 0.000 0.000 0.000
FLOOR 1 DICTATION 0.36 0.63 35.68 0.000 0.000 0.000 0.000
FLOOR 1 DRESSING ROOM 0.13 0.23 12.74 0.000 0.000 0.000 0.000
FLOOR 1 ELECTRICAL ROOM 0.09 0.15 27.75 0.000 0.000 0.000 0.000
FLOOR 1 ELEVATOR PUMP ROOM 0.08 0.14 25.77 0.000 0.000 0.000 0.000
FLOOR 1 HUMID 0.16 0.27 15.29 0.000 0.000 0.000 0.000
FLOOR 1 IT HALL 0.42 0.70 39.64 0.000 0.000 0.000 0.000
FLOOR 1 IT ROOM 0.32 0.56 31.71 0.000 0.000 0.000 0.000
FLOOR 1 LOBBY 3.77 6.22 176.13 0.000 0.000 0.000 0.000
FLOOR 1 LOBBY HALL 0.73 1.20 67.96 0.000 0.000 0.000 0.000
FLOOR 1 LOBBY TOILET 0.16 0.27 15.29 0.000 0.000 0.000 0.000
FLOOR 1 LOCKER ROOM 6.00 9.90 186.89 0.000 0.000 0.000 0.000
FLOOR 1 LOCKER ROOM HALL 1.50 2.48 140.45 0.000 0.000 0.000 0.000
FLOOR 1 LOUNGE 3.27 5.40 101.94 0.000 0.000 0.000 0.000
FLOOR 1 MED GAS 0.07 0.11 15.86 0.000 0.000 0.000 0.000
FLOOR 1 MRI CONTROL ROOM 2.04 3.36 47.57 0.000 0.000 0.000 0.000
FLOOR 1 MRI HALL 0.45 0.73 41.63 0.000 0.000 0.000 0.000
FLOOR 1 MRI ROOM 5.33 8.80 124.59 0.000 0.000 0.000 0.000
FLOOR 1 MRI TOILET 0.16 0.27 15.29 0.000 0.000 0.000 0.000
FLOOR 1 NOURISHMENT 1.65 2.73 51.54 0.000 0.000 0.000 0.000
FLOOR 1 NURSE HALL 1.50 2.48 140.45 0.000 0.000 0.000 0.000
FLOOR 1 NURSE JANITOR 0.07 0.11 15.29 0.000 0.000 0.000 0.000
FLOOR 1 NURSE STATION 2.37 3.91 73.91 0.000 0.000 0.000 0.000
FLOOR 1 NURSE TOILET 0.16 0.27 15.29 0.000 0.000 0.000 0.000
FLOOR 1 OFFICE 1.40 2.42 136.77 0.000 0.000 0.000 0.000
FLOOR 1 OPERATING ROOM 1 5.57 9.20 130.26 0.000 0.000 0.000 0.000
FLOOR 1 OPERATING ROOM 2 5.82 9.60 135.92 0.000 0.000 0.000 0.000
FLOOR 1 OPERATING ROOM 3 5.77 9.52 134.79 0.000 0.000 0.000 0.000
FLOOR 1 PACU 1.31 2.16 30.58 0.000 0.000 0.000 0.000
FLOOR 1 PRE-OP HALL 1.60 2.64 149.51 0.000 0.000 0.000 0.000
FLOOR 1 PRE-OP ROOM 1 1.14 1.89 53.52 0.000 0.000 0.000 0.000
FLOOR 1 PRE-OP ROOM 2 2.05 3.38 95.71 0.000 0.000 0.000 0.000
FLOOR 1 PRE-OP TOILET 0.16 0.27 15.29 0.000 0.000 0.000 0.000
FLOOR 1 PROCEDURE ROOM 3.45 5.70 80.70 0.000 0.000 0.000 0.000
FLOOR 1 RECEPTION 9.25 15.27 144.13 0.000 0.000 0.000 0.000
FLOOR 1 RECEPTION HALL 0.39 0.64 36.25 0.000 0.000 0.000 0.000
FLOOR 1 RECOVERY ROOM 6.54 10.80 152.91 0.000 0.000 0.000 0.000
FLOOR 1 SCHEDULING 0.34 0.60 33.70 0.000 0.000 0.000 0.000
FLOOR 1 SCRUB 0.25 0.42 23.79 0.000 0.000 0.000 0.000
FLOOR 1 SOIL 1.53 2.52 35.68 0.000 0.000 0.000 0.000
FLOOR 1 SOIL HOLD 0.68 1.12 15.86 0.000 0.000 0.000 0.000
FLOOR 1 SOIL WORK 2.18 3.60 50.97 0.000 0.000 0.000 0.000
FLOOR 1 STEP DOWN 3.63 6.00 84.95 0.000 0.000 0.000 0.000
FLOOR 1 STERILE HALL 1.87 3.08 174.43 0.000 0.000 0.000 0.000
FLOOR 1 STERILE STORAGE 0.48 0.79 112.13 0.000 0.000 0.000 0.000
FLOOR 1 STORAGE 1.11 1.84 260.51 0.000 0.000 0.000 0.000
FLOOR 1 SUB-STERILE 0.59 0.98 55.50 0.000 0.000 0.000 0.000
FLOOR 1 UTILITY HALL 0.78 1.28 72.49 0.000 0.000 0.000 0.000
FLOOR 1 UTILITY JANITOR 0.05 0.08 11.89 0.000 0.000 0.000 0.000
FLOOR 1 UTILITY ROOM 0.44 0.72 101.94 0.000 0.000 0.000 0.000
FLOOR 1 VESTIBULE 0.22 0.36 20.39 0.000 0.000 0.000 0.000
FLOOR 2 CONFERENCE 9.75 16.80 95.14 0.000 0.000 0.000 0.000
FLOOR 2 CONFERENCE TOILET 0.19 0.32 18.12 0.000 0.000 0.000 0.000
FLOOR 2 DICTATION 0.20 0.35 19.82 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 1 4.36 7.20 101.94 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 2 6.54 10.80 152.91 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 3 8.72 14.40 203.88 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 4 1.02 1.68 23.79 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 5 4.24 7.00 99.11 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 6 2.73 4.50 63.71 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 7 9.60 15.84 224.27 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 8 3.27 5.40 76.46 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 9 4.80 7.92 112.13 0.000 0.000 0.000 0.000
FLOOR 2 EXAM HALL 1 0.55 0.90 50.97 0.000 0.000 0.000 0.000
FLOOR 2 EXAM HALL 2 0.55 0.90 50.97 0.000 0.000 0.000 0.000
FLOOR 2 EXAM HALL 3 0.55 0.90 50.97 0.000 0.000 0.000 0.000
FLOOR 2 EXAM HALL 4 0.60 0.99 56.07 0.000 0.000 0.000 0.000
FLOOR 2 EXAM HALL 5 0.60 0.99 56.07 0.000 0.000 0.000 0.000
FLOOR 2 EXAM HALL 6 0.60 0.99 56.07 0.000 0.000 0.000 0.000
FLOOR 2 JANITOR 0.08 0.13 17.84 0.000 0.000 0.000 0.000
FLOOR 2 LOUNGE 0.73 1.20 22.65 0.000 0.000 0.000 0.000
FLOOR 2 NURSE STATION 1 1.36 2.25 42.48 0.000 0.000 0.000 0.000
FLOOR 2 NURSE STATION 2 1.64 2.70 50.97 0.000 0.000 0.000 0.000
FLOOR 2 OFFICE 1.62 2.80 158.57 0.000 0.000 0.000 0.000
FLOOR 2 OFFICE HALL 1.34 2.22 125.73 0.000 0.000 0.000 0.000
FLOOR 2 RECEPTION 17.88 29.52 278.64 0.000 0.000 0.000 0.000
FLOOR 2 RECEPTION HALL 1.71 2.82 159.71 0.000 0.000 0.000 0.000
FLOOR 2 RECEPTION TOILET 0.38 0.63 35.68 0.000 0.000 0.000 0.000
FLOOR 2 SCHEDULING 1 0.94 1.62 91.75 0.000 0.000 0.000 0.000
FLOOR 2 SCHEDULING 2 0.99 1.71 96.84 0.000 0.000 0.000 0.000
FLOOR 2 STORAGE 1 0.07 0.11 15.86 0.000 0.000 0.000 0.000
FLOOR 2 STORAGE 2 0.15 0.24 33.98 0.000 0.000 0.000 0.000
FLOOR 2 STORAGE 3 0.17 0.29 40.78 0.000 0.000 0.000 0.000
FLOOR 2 UTILITY 0.15 0.25 35.68 0.000 0.000 0.000 0.000
FLOOR 2 WORK 4.88 8.45 478.55 0.000 0.000 0.000 0.000
FLOOR 2 WORK HALL 2.53 4.17 236.16 0.000 0.000 0.000 0.000
FLOOR 2 WORK TOILET 0.16 0.27 15.29 0.000 0.000 0.000 0.000
FLOOR 2 X-RAY 10.90 18.00 254.85 0.000 0.000 0.000 0.000
FLOOR 3 DRESSING ROOM 0.12 0.21 11.89 0.000 0.000 0.000 0.000
FLOOR 3 ELEVATOR HALL 1.12 1.85 104.77 0.000 0.000 0.000 0.000
FLOOR 3 HUMID 0.31 0.54 30.58 0.000 0.000 0.000 0.000
FLOOR 3 JANITOR 0.08 0.13 17.84 0.000 0.000 0.000 0.000
FLOOR 3 LOCKER 1.09 1.80 33.98 0.000 0.000 0.000 0.000
FLOOR 3 LOUNGE 6.90 11.39 214.92 0.000 0.000 0.000 0.000
FLOOR 3 LOUNGE TOILET 0.58 0.96 54.37 0.000 0.000 0.000 0.000
FLOOR 3 MECHANICAL 0.32 0.53 99.11 0.000 0.000 0.000 0.000
FLOOR 3 MECHANICAL HALL 0.91 1.50 84.95 0.000 0.000 0.000 0.000
FLOOR 3 OFFICE 8.77 15.18 859.70 0.000 0.000 0.000 0.000
FLOOR 3 OFFICE HALL 2.53 4.17 236.16 0.000 0.000 0.000 0.000
FLOOR 3 OFFICE TOILET 0.16 0.27 15.29 0.000 0.000 0.000 0.000
FLOOR 3 PHYSICAL THERAPY 1 15.75 26.00 368.12 0.000 0.000 0.000 0.000
FLOOR 3 PHYSICAL THERAPY 2 7.17 11.84 167.64 0.000 0.000 0.000 0.000
FLOOR 3 PHYSICAL THERAPY TOILET 0.25 0.42 23.79 0.000 0.000 0.000 0.000
FLOOR 3 STORAGE 1 0.13 0.22 30.58 0.000 0.000 0.000 0.000
FLOOR 3 STORAGE 2 0.10 0.17 23.79 0.000 0.000 0.000 0.000
FLOOR 3 TREATMENT 5.77 9.52 134.79 0.000 0.000 0.000 0.000
FLOOR 3 UNDEVELOPED 1 2.75 4.54 642.23 0.000 0.000 0.000 0.000
FLOOR 3 UNDEVELOPED 2 1.40 2.30 326.21 0.000 0.000 0.000 0.000
FLOOR 3 UTILITY 0.26 0.43 61.16 0.000 0.000 0.000 0.000
FLOOR 3 WORK 1.66 2.87 162.54 0.000 0.000 0.000 0.000
NE STAIR 0.51 0.84 142.72 0.000 0.000 0.000 0.000
NW ELEVATOR 0.13 0.21 118.93 0.000 0.000 0.000 0.000
NW STAIR 0.58 0.96 163.10 0.000 0.000 0.000 0.000
SW STAIR 0.29 0.48 81.55 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
FLOOR 1 ANESTHESIA AHU-1 1.31 2.16 30.58 10.03 0.0153 0.015
FLOOR 1 BIO HAZ AHU-1 0.07 0.11 15.86 5.20 0.0032 0.003
FLOOR 1 CAFE PSZ_CAFE 25.44 42.00 118.93 39.02 0.1843 0.184
FLOOR 1 CLEAN AHU-1 1.53 2.52 35.68 11.71 0.0178 0.018
FLOOR 1 CLEAN WORK AHU-1 2.00 3.30 46.72 15.33 0.0234 0.023
FLOOR 1 DICTATION AHU-1 0.36 0.63 35.68 11.71 0.0051 0.005
FLOOR 1 DRESSING ROOM AHU-1 0.13 0.23 12.74 4.18 0.0018 0.002
FLOOR 1 ELECTRICAL ROOM AHU-1 0.09 0.15 27.75 9.10 0.0000 0.000
FLOOR 1 ELEVATOR PUMP ROOM PSZ_ELEVATOR 0.08 0.14 25.77 8.45 0.0000 0.000
FLOOR 1 HUMID AHU-1 0.16 0.27 15.29 5.02 0.0022 0.002
FLOOR 1 IT HALL AHU-1 0.42 0.70 39.64 13.01 0.0040 0.004
FLOOR 1 IT ROOM AHU-1 0.32 0.56 31.71 10.41 0.0045 0.004
FLOOR 1 LOBBY AHU-1 3.77 6.22 176.13 57.79 0.0323 0.032
FLOOR 1 LOBBY HALL AHU-1 0.73 1.20 67.96 22.30 0.0068 0.007
FLOOR 1 LOBBY TOILET AHU-1 0.16 0.27 15.29 5.02 0.0000 0.000
FLOOR 1 LOCKER ROOM AHU-1 6.00 9.90 186.89 61.32 0.0421 0.042
FLOOR 1 LOCKER ROOM HALL AHU-1 1.50 2.48 140.45 46.08 0.0140 0.014
FLOOR 1 LOUNGE AHU-1 3.27 5.40 101.94 33.45 0.0229 0.023
FLOOR 1 MED GAS AHU-1 0.07 0.11 15.86 5.20 0.0032 0.003
FLOOR 1 MRI CONTROL ROOM PSZ_MRI_CONTROL 2.04 3.36 47.57 15.61 0.0238 0.024
FLOOR 1 MRI HALL AHU-1 0.45 0.73 41.63 13.66 0.0042 0.004
FLOOR 1 MRI ROOM PSZ_MRI 5.33 8.80 124.59 40.88 0.0623 0.062
FLOOR 1 MRI TOILET AHU-1 0.16 0.27 15.29 5.02 0.0000 0.000
FLOOR 1 NOURISHMENT AHU-1 1.65 2.73 51.54 16.91 0.0137 0.014
FLOOR 1 NURSE HALL AHU-1 1.50 2.48 140.45 46.08 0.0140 0.014
FLOOR 1 NURSE JANITOR AHU-1 0.07 0.11 15.29 5.02 0.0031 0.003
FLOOR 1 NURSE STATION AHU-1 2.37 3.91 73.91 24.25 0.0197 0.020
FLOOR 1 NURSE TOILET AHU-1 0.16 0.27 15.29 5.02 0.0000 0.000
FLOOR 1 OFFICE AHU-1 1.40 2.42 136.77 44.87 0.0194 0.019
FLOOR 1 OPERATING ROOM 1 PSZ_OR_1 5.57 9.20 130.26 42.74 0.2388 0.239
FLOOR 1 OPERATING ROOM 2 PSZ_OR_2 5.82 9.60 135.92 44.59 0.2492 0.249
FLOOR 1 OPERATING ROOM 3 PSZ_OR_3 5.77 9.52 134.79 44.22 0.2471 0.247
FLOOR 1 PACU AHU-1 1.31 2.16 30.58 10.03 0.0323 0.032
FLOOR 1 PRE-OP HALL AHU-1 1.60 2.64 149.51 49.05 0.0150 0.015
FLOOR 1 PRE-OP ROOM 1 AHU-1 1.14 1.89 53.52 17.56 0.0520 0.052
FLOOR 1 PRE-OP ROOM 2 AHU-1 2.05 3.38 95.71 31.40 0.0931 0.093
FLOOR 1 PRE-OP TOILET AHU-1 0.16 0.27 15.29 5.02 0.0000 0.000
FLOOR 1 PROCEDURE ROOM AHU-1 3.45 5.70 80.70 26.48 0.1076 0.108
FLOOR 1 RECEPTION AHU-1 9.25 15.27 144.13 47.29 0.0504 0.050
FLOOR 1 RECEPTION HALL AHU-1 0.39 0.64 36.25 11.89 0.0036 0.004
FLOOR 1 RECOVERY ROOM AHU-1 6.54 10.80 152.91 50.17 0.1614 0.161
FLOOR 1 SCHEDULING AHU-1 0.34 0.60 33.70 11.06 0.0048 0.005
FLOOR 1 SCRUB AHU-1 0.25 0.42 23.79 7.80 0.0024 0.002
FLOOR 1 SOIL AHU-1 1.53 2.52 35.68 11.71 0.0178 0.018
FLOOR 1 SOIL HOLD AHU-1 0.68 1.12 15.86 5.20 0.0079 0.008
FLOOR 1 SOIL WORK AHU-1 2.18 3.60 50.97 16.72 0.0255 0.025
FLOOR 1 STEP DOWN AHU-1 3.63 6.00 84.95 27.87 0.0897 0.090
FLOOR 1 STERILE HALL AHU-1 1.87 3.08 174.43 57.23 0.0174 0.017
FLOOR 1 STERILE STORAGE AHU-1 0.48 0.79 112.13 36.79 0.0224 0.022
FLOOR 1 STORAGE AHU-1 1.11 1.84 260.51 85.47 0.0521 0.052
FLOOR 1 SUB-STERILE AHU-1 0.59 0.98 55.50 18.21 0.0056 0.006
FLOOR 1 UTILITY HALL AHU-1 0.78 1.28 72.49 23.78 0.0072 0.007
FLOOR 1 UTILITY JANITOR AHU-1 0.05 0.08 11.89 3.90 0.0024 0.002
FLOOR 1 UTILITY ROOM AHU-1 0.44 0.72 101.94 33.45 0.0204 0.020
FLOOR 1 VESTIBULE AHU-1 0.22 0.36 20.39 6.69 0.0020 0.002
FLOOR 2 CONFERENCE AHU-2 9.75 16.80 95.14 31.22 0.0000 0.049
FLOOR 2 CONFERENCE TOILET AHU-2 0.19 0.32 18.12 5.95 0.0000 0.000
FLOOR 2 DICTATION AHU-2 0.20 0.35 19.82 6.50 0.0000 0.003
FLOOR 2 EXAM 1 AHU-2 4.36 7.20 101.94 33.45 0.0000 0.051
FLOOR 2 EXAM 2 AHU-2 6.54 10.80 152.91 50.17 0.0000 0.076
FLOOR 2 EXAM 3 AHU-2 8.72 14.40 203.88 66.89 0.0000 0.102
FLOOR 2 EXAM 4 AHU-2 1.02 1.68 23.79 7.80 0.0000 0.012
FLOOR 2 EXAM 5 AHU-2 4.24 7.00 99.11 32.52 0.0000 0.050
FLOOR 2 EXAM 6 AHU-2 2.73 4.50 63.71 20.90 0.0000 0.032
FLOOR 2 EXAM 7 AHU-2 9.60 15.84 224.27 73.58 0.0000 0.112
FLOOR 2 EXAM 8 AHU-2 3.27 5.40 76.46 25.08 0.0000 0.038
FLOOR 2 EXAM 9 AHU-2 4.80 7.92 112.13 36.79 0.0000 0.056
FLOOR 2 EXAM HALL 1 AHU-2 0.55 0.90 50.97 16.72 0.0000 0.005
FLOOR 2 EXAM HALL 2 AHU-2 0.55 0.90 50.97 16.72 0.0000 0.005
FLOOR 2 EXAM HALL 3 AHU-2 0.55 0.90 50.97 16.72 0.0000 0.005
FLOOR 2 EXAM HALL 4 AHU-2 0.60 0.99 56.07 18.39 0.0000 0.006
FLOOR 2 EXAM HALL 5 AHU-2 0.60 0.99 56.07 18.39 0.0000 0.006
FLOOR 2 EXAM HALL 6 AHU-2 0.60 0.99 56.07 18.39 0.0000 0.006
FLOOR 2 JANITOR AHU-2 0.08 0.13 17.84 5.85 0.0000 0.004
FLOOR 2 LOUNGE AHU-2 0.73 1.20 22.65 7.43 0.0000 0.005
FLOOR 2 NURSE STATION 1 AHU-2 1.36 2.25 42.48 13.94 0.0000 0.011
FLOOR 2 NURSE STATION 2 AHU-2 1.64 2.70 50.97 16.72 0.0000 0.014
FLOOR 2 OFFICE AHU-2 1.62 2.80 158.57 52.03 0.0000 0.022
FLOOR 2 OFFICE HALL AHU-2 1.34 2.22 125.73 41.25 0.0000 0.013
FLOOR 2 RECEPTION AHU-2 17.88 29.52 278.64 91.42 0.0000 0.098
FLOOR 2 RECEPTION HALL AHU-2 1.71 2.82 159.71 52.40 0.0000 0.016
FLOOR 2 RECEPTION TOILET AHU-2 0.38 0.63 35.68 11.71 0.0000 0.000
FLOOR 2 SCHEDULING 1 AHU-2 0.94 1.62 91.75 30.10 0.0000 0.013
FLOOR 2 SCHEDULING 2 AHU-2 0.99 1.71 96.84 31.77 0.0000 0.014
FLOOR 2 STORAGE 1 AHU-2 0.07 0.11 15.86 5.20 0.0000 0.003
FLOOR 2 STORAGE 2 AHU-2 0.15 0.24 33.98 11.15 0.0000 0.007
FLOOR 2 STORAGE 3 AHU-2 0.17 0.29 40.78 13.38 0.0000 0.008
FLOOR 2 UTILITY AHU-2 0.15 0.25 35.68 11.71 0.0000 0.007
FLOOR 2 WORK AHU-2 4.88 8.45 478.55 157.01 0.0000 0.068
FLOOR 2 WORK HALL AHU-2 2.53 4.17 236.16 77.48 0.0000 0.024
FLOOR 2 WORK TOILET AHU-2 0.16 0.27 15.29 5.02 0.0000 0.000
FLOOR 2 X-RAY PSZ_XRAY 10.90 18.00 254.85 83.61 0.1274 0.127
FLOOR 3 DRESSING ROOM AHU-3 0.12 0.21 11.89 3.90 0.0000 0.002
FLOOR 3 ELEVATOR HALL AHU-3 1.12 1.85 104.77 34.37 0.0000 0.010
FLOOR 3 HUMID AHU-3 0.31 0.54 30.58 10.03 0.0000 0.004
FLOOR 3 JANITOR AHU-3 0.08 0.13 17.84 5.85 0.0000 0.004
FLOOR 3 LOCKER AHU-3 1.09 1.80 33.98 11.15 0.0000 0.008
FLOOR 3 LOUNGE AHU-3 6.90 11.39 214.92 70.51 0.0000 0.048
FLOOR 3 LOUNGE TOILET AHU-3 0.58 0.96 54.37 17.84 0.0000 0.000
FLOOR 3 MECHANICAL AHU-3 0.32 0.53 99.11 32.52 0.0000 0.000
FLOOR 3 MECHANICAL HALL AHU-3 0.91 1.50 84.95 27.87 0.0000 0.008
FLOOR 3 OFFICE AHU-3 8.77 15.18 859.70 282.05 0.0000 0.122
FLOOR 3 OFFICE HALL AHU-3 2.53 4.17 236.16 77.48 0.0000 0.024
FLOOR 3 OFFICE TOILET AHU-3 0.16 0.27 15.29 5.02 0.0000 0.000
FLOOR 3 PHYSICAL THERAPY 1 AHU-3 15.75 26.00 368.12 120.77 0.0000 0.184
FLOOR 3 PHYSICAL THERAPY 2 AHU-3 7.17 11.84 167.64 55.00 0.0000 0.084
FLOOR 3 PHYSICAL THERAPY TOILET AHU-3 0.25 0.42 23.79 7.80 0.0000 0.000
FLOOR 3 STORAGE 1 AHU-3 0.13 0.22 30.58 10.03 0.0000 0.006
FLOOR 3 STORAGE 2 AHU-3 0.10 0.17 23.79 7.80 0.0000 0.005
FLOOR 3 TREATMENT AHU-3 5.77 9.52 134.79 44.22 0.0000 0.067
FLOOR 3 UNDEVELOPED 1 AHU-3 2.75 4.54 642.23 210.70 0.0000 0.128
FLOOR 3 UNDEVELOPED 2 AHU-3 1.40 2.30 326.21 107.02 0.0000 0.065
FLOOR 3 UTILITY AHU-3 0.26 0.43 61.16 20.07 0.0000 0.012
FLOOR 3 WORK AHU-3 1.66 2.87 162.54 53.33 0.0000 0.023
NE STAIR AHU-2 0.51 0.84 142.72 15.61 0.0000 0.005
NW ELEVATOR AHU-2 0.13 0.21 118.93 13.01 0.0000 0.000
NW STAIR AHU-2 0.58 0.96 163.10 17.84 0.0000 0.005
SW STAIR AHU-2 0.29 0.48 81.55 8.92 0.0000 0.003
Total Facility   285.91 474.50 11932.15 3804.01 2.1985 3.955


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
FLOOR 1 ANESTHESIA 479389.17 0.00 479389.17 20050.97 499440.14 482219.72 2893.69 0.00 5866.31 1462.86
FLOOR 1 BIO HAZ 36599.30 0.00 36599.30 0.00 36599.30 100015.84 8759.80 0.00 0.20 1462.86
FLOOR 1 CAFE 2614050.05 0.00 2614050.05 44557.72 2658607.77 5813424.33 4821.00 3939.00 0.00 0.00
FLOOR 1 CLEAN 535201.68 0.00 535201.68 0.00 535201.68 562589.68 2893.69 0.00 5866.31 1462.86
FLOOR 1 CLEAN WORK 669767.47 0.00 669767.47 0.00 669767.47 736724.58 2893.69 0.00 5866.31 1462.86
FLOOR 1 DICTATION 105658.97 0.00 105658.97 0.00 105658.97 159400.51 6498.28 48.39 2213.32 2053.57
FLOOR 1 DRESSING ROOM 73262.37 0.00 73262.37 20050.97 93313.34 56928.75 2937.85 1.67 5820.49 2065.52
FLOOR 1 ELECTRICAL ROOM 213412.95 0.00 213412.95 15595.20 229008.15 0.00 0.00 0.00 5866.31 1462.86
FLOOR 1 ELEVATOR PUMP ROOM 0.00 0.00 0.00 44557.72 44557.72 0.00 0.00 0.00 0.00 0.00
FLOOR 1 HUMID 56704.98 0.00 56704.98 0.00 56704.98 68314.51 5157.08 31.35 3571.57 2064.26
FLOOR 1 IT HALL 94371.72 0.00 94371.72 0.00 94371.72 125020.01 5216.06 63.95 3479.99 1462.86
FLOOR 1 IT ROOM 97744.25 0.00 97744.25 0.00 97744.25 141689.35 6219.74 29.04 2511.21 2057.23
FLOOR 1 LOBBY 942012.27 0.00 942012.27 49013.49 991025.76 1018315.93 5403.31 10.14 3346.54 1462.86
FLOOR 1 LOBBY HALL 258390.01 0.00 258390.01 0.00 258390.01 214320.02 4815.67 0.03 3944.31 1462.86
FLOOR 1 LOBBY TOILET 213925.86 0.00 213925.86 13367.32 227293.18 0.00 0.00 0.00 5866.31 1462.86
FLOOR 1 LOCKER ROOM 1076719.95 0.00 1076719.95 49013.49 1125733.44 1326103.18 5375.72 6.21 3378.07 1462.86
FLOOR 1 LOCKER ROOM HALL 340486.54 0.00 340486.54 0.00 340486.54 442928.04 5648.63 29.72 3081.65 1462.86
FLOOR 1 LOUNGE 562052.23 0.00 562052.23 0.00 562052.23 723329.01 5379.55 5.85 3374.59 1462.86
FLOOR 1 MED GAS 81657.77 0.00 81657.77 33418.29 115076.06 100015.84 6024.10 45.85 2690.05 1462.86
FLOOR 1 MRI CONTROL ROOM 337296.92 0.00 337296.92 0.00 337296.92 750119.57 4821.00 3939.00 0.00 0.00
FLOOR 1 MRI HALL 139900.66 0.00 139900.66 0.00 139900.66 131271.01 4824.37 0.74 3934.89 1462.86
FLOOR 1 MRI ROOM 883396.69 0.00 883396.69 0.00 883396.69 1964598.87 4821.00 3939.00 0.00 0.00
FLOOR 1 MRI TOILET 185427.06 0.00 185427.06 13367.32 198794.38 0.00 0.00 0.00 5866.31 1462.86
FLOOR 1 NOURISHMENT 242956.10 0.00 242956.10 0.00 242956.10 433402.17 6125.79 64.59 2569.62 1462.86
FLOOR 1 NURSE HALL 322599.69 0.00 322599.69 0.00 322599.69 442928.04 5480.88 174.67 3104.45 1462.86
FLOOR 1 NURSE JANITOR 42982.17 0.00 42982.17 0.00 42982.17 96443.85 8584.89 37.93 137.17 1462.86
FLOOR 1 NURSE STATION 319173.71 0.00 319173.71 0.00 319173.71 621527.29 6648.54 193.57 1917.89 1462.86
FLOOR 1 NURSE TOILET 178254.68 0.00 178254.68 0.00 178254.68 0.00 0.00 0.00 5866.31 1462.86
FLOOR 1 OFFICE 418953.63 0.00 418953.63 0.00 418953.63 611035.30 5939.21 45.46 2775.33 2065.70
FLOOR 1 OPERATING ROOM 1 3386353.15 0.00 3386353.15 95799.09 3482152.25 7530960.55 4821.00 3939.00 0.00 0.00
FLOOR 1 OPERATING ROOM 2 3533585.90 0.00 3533585.90 53469.26 3587055.16 7858393.62 4821.00 3939.00 0.00 0.00
FLOOR 1 OPERATING ROOM 3 3504139.35 0.00 3504139.35 0.00 3504139.35 7792907.01 4821.00 3939.00 0.00 0.00
FLOOR 1 PACU 472937.75 0.00 472937.75 0.00 472937.75 1018019.03 8760.00 0.00 0.00 1462.86
FLOOR 1 PRE-OP HALL 359350.47 0.00 359350.47 0.00 359350.47 471504.04 5218.69 46.78 3494.53 1462.86
FLOOR 1 PRE-OP ROOM 1 653593.93 0.00 653593.93 8911.54 662505.48 1640885.79 8760.00 0.00 0.00 1462.86
FLOOR 1 PRE-OP ROOM 2 1168861.11 0.00 1168861.11 0.00 1168861.11 2934494.16 8760.00 0.00 0.00 1462.86
FLOOR 1 PRE-OP TOILET 180746.02 0.00 180746.02 13367.32 194113.33 0.00 0.00 0.00 5866.31 1462.86
FLOOR 1 PROCEDURE ROOM 2463945.38 0.00 2463945.38 42329.83 2506275.21 3393396.94 2893.69 0.00 5866.31 1462.86
FLOOR 1 RECEPTION 851055.68 0.00 851055.68 28962.52 880018.19 1590878.14 5988.03 8.19 2763.78 1462.86
FLOOR 1 RECEPTION HALL 99011.73 0.00 99011.73 0.00 99011.73 114304.01 4830.37 2.66 3926.97 1462.86
FLOOR 1 RECOVERY ROOM 2124054.85 0.00 2124054.85 100254.87 2224309.71 5090095.15 8760.00 0.00 0.00 1462.86
FLOOR 1 SCHEDULING 122265.55 0.00 122265.55 15595.20 137860.75 150544.93 5733.43 15.62 3010.95 2067.65
FLOOR 1 SCRUB 66835.75 0.00 66835.75 0.00 66835.75 75012.01 4839.98 8.07 3911.96 1462.86
FLOOR 1 SOIL 534809.06 0.00 534809.06 0.00 534809.06 562589.68 2893.69 0.00 5866.31 1462.86
FLOOR 1 SOIL HOLD 249504.74 0.00 249504.74 0.00 249504.74 250039.86 2893.69 0.00 5866.31 1462.86
FLOOR 1 SOIL WORK 710428.86 0.00 710428.86 0.00 710428.86 803699.54 2893.69 0.00 5866.31 1462.86
FLOOR 1 STEP DOWN 1083272.30 0.00 1083272.30 82431.78 1165704.08 2827830.64 8760.00 0.00 0.00 1462.86
FLOOR 1 STERILE HALL 433568.44 0.00 433568.44 0.00 433568.44 550088.05 5204.75 483.42 3071.82 1462.86
FLOOR 1 STERILE STORAGE 221261.36 0.00 221261.36 0.00 221261.36 707254.90 8751.47 0.25 8.28 1462.86
FLOOR 1 STORAGE 733534.09 0.00 733534.09 140356.81 873890.90 1643117.44 7683.31 42.30 1034.39 1462.86
FLOOR 1 SUB-STERILE 226309.21 0.00 226309.21 31190.40 257499.61 175028.01 2893.69 0.00 5866.31 1462.86
FLOOR 1 UTILITY HALL 344088.92 0.00 344088.92 35646.17 379735.10 228608.02 2893.69 0.00 5866.31 1462.86
FLOOR 1 UTILITY JANITOR 34260.49 0.00 34260.49 0.00 34260.49 75011.88 8656.66 58.19 45.16 1462.86
FLOOR 1 UTILITY ROOM 309368.55 0.00 309368.55 40101.95 349470.49 642959.00 7499.30 89.32 1171.38 1462.86
FLOOR 1 VESTIBULE 168837.14 0.00 168837.14 11736720.66 11905557.79 64296.01 2893.69 0.00 5866.31 1462.86
FLOOR 2 CONFERENCE 717267.75 0.00 717267.75 128065.43 845333.18 1550246.16 6758.70 35.98 1965.31 2035.74
FLOOR 2 CONFERENCE TOILET 120234.99 0.00 120234.99 0.00 120234.99 0.00 0.00 0.00 5289.08 922.74
FLOOR 2 DICTATION 63011.02 0.00 63011.02 0.00 63011.02 88555.84 4862.32 9.03 3888.65 1528.74
FLOOR 2 EXAM 1 691708.35 0.00 691708.35 134468.70 826177.05 1607399.08 7499.62 163.60 1096.78 922.74
FLOOR 2 EXAM 2 1113978.09 0.00 1113978.09 57629.44 1171607.54 2411098.62 7686.73 44.31 1028.96 922.74
FLOOR 2 EXAM 3 1485304.13 0.00 1485304.13 76839.26 1562143.38 3214798.16 7686.73 44.31 1028.96 922.74
FLOOR 2 EXAM 4 171727.24 0.00 171727.24 22411.45 194138.69 375059.79 6937.66 168.25 1654.08 922.74
FLOOR 2 EXAM 5 801524.62 0.00 801524.62 80040.89 881565.51 1562749.10 6782.45 125.19 1852.36 922.74
FLOOR 2 EXAM 6 488061.84 0.00 488061.84 48024.54 536086.37 1004624.42 7548.47 55.84 1155.69 922.74
FLOOR 2 EXAM 7 1633834.54 0.00 1633834.54 76839.26 1710673.80 3536277.97 7686.73 44.31 1028.96 922.74
FLOOR 2 EXAM 8 584474.04 0.00 584474.04 57629.44 642103.49 1205549.31 7553.41 55.39 1151.20 922.74
FLOOR 2 EXAM 9 863766.45 0.00 863766.45 38419.63 902186.07 1768138.99 7533.23 54.57 1172.20 922.74
FLOOR 2 EXAM HALL 1 163959.39 0.00 163959.39 0.00 163959.39 160740.01 4829.48 0.50 3930.02 922.74
FLOOR 2 EXAM HALL 2 150794.32 0.00 150794.32 0.00 150794.32 160740.01 4831.25 0.64 3928.11 922.74
FLOOR 2 EXAM HALL 3 137747.52 0.00 137747.52 0.00 137747.52 160740.01 4833.64 2.67 3923.69 922.74
FLOOR 2 EXAM HALL 4 155999.98 0.00 155999.98 0.00 155999.98 176814.01 4831.23 1.31 3927.46 922.74
FLOOR 2 EXAM HALL 5 170103.44 0.00 170103.44 0.00 170103.44 176814.01 4829.09 0.32 3930.58 922.74
FLOOR 2 EXAM HALL 6 161458.16 0.00 161458.16 0.00 161458.16 176814.01 4830.48 0.36 3929.15 922.74
FLOOR 2 JANITOR 64999.03 0.00 64999.03 51226.17 116225.20 112517.82 5579.56 82.99 3097.45 922.74
FLOOR 2 LOUNGE 123513.61 0.00 123513.61 0.00 123513.61 160739.78 4833.71 0.72 3925.57 922.74
FLOOR 2 NURSE STATION 1 204609.61 0.00 204609.61 0.00 204609.61 357199.59 5465.57 59.82 3234.62 922.74
FLOOR 2 NURSE STATION 2 254046.83 0.00 254046.83 0.00 254046.83 428639.51 5395.91 15.31 3348.78 922.74
FLOOR 2 OFFICE 746677.30 0.00 746677.30 128065.43 874742.73 708446.73 4830.84 0.41 3928.75 1528.74
FLOOR 2 OFFICE HALL 362575.48 0.00 362575.48 0.00 362575.48 396492.03 4831.34 0.64 3928.02 922.74
FLOOR 2 RECEPTION 1714773.27 0.00 1714773.27 156880.15 1871653.42 3075489.37 5624.38 60.69 3074.94 922.74
FLOOR 2 RECEPTION HALL 508056.38 0.00 508056.38 0.00 508056.38 503652.04 4828.48 0.32 3931.20 922.74
FLOOR 2 RECEPTION TOILET 220716.83 0.00 220716.83 0.00 220716.83 0.00 0.00 0.00 5289.08 922.74
FLOOR 2 SCHEDULING 1 297323.78 0.00 297323.78 0.00 297323.78 409887.03 4832.63 0.53 3926.85 1528.74
FLOOR 2 SCHEDULING 2 327182.73 0.00 327182.73 0.00 327182.73 432658.54 4831.48 0.40 3928.12 1528.74
FLOOR 2 STORAGE 1 34767.89 0.00 34767.89 0.00 34767.89 100015.84 8745.85 2.31 11.84 922.74
FLOOR 2 STORAGE 2 77420.74 0.00 77420.74 0.00 77420.74 214319.67 8664.71 30.38 64.91 922.74
FLOOR 2 STORAGE 3 103205.97 0.00 103205.97 0.00 103205.97 257183.60 8150.02 108.20 501.78 922.74
FLOOR 2 UTILITY 150195.63 0.00 150195.63 28814.72 179010.35 225035.65 5349.36 44.59 3366.04 922.74
FLOOR 2 WORK 1494438.22 0.00 1494438.22 83242.53 1577680.74 2137991.01 5045.28 347.91 3366.82 1528.74
FLOOR 2 WORK HALL 777365.74 0.00 777365.74 0.00 777365.74 744762.06 4826.93 0.38 3932.69 922.74
FLOOR 2 WORK TOILET 107829.96 0.00 107829.96 19209.81 127039.77 0.00 0.00 0.00 5289.08 922.74
FLOOR 2 X-RAY 2797474.12 0.00 2797474.12 0.00 2797474.12 4018497.70 4753.28 3636.02 370.69 67.74
FLOOR 3 DRESSING ROOM 52690.65 0.00 52690.65 0.00 52690.65 53133.50 4834.28 1.49 3924.23 3214.96
FLOOR 3 ELEVATOR HALL 334638.29 0.00 334638.29 15159.01 349797.30 330410.03 4834.65 1.08 3924.27 2608.96
FLOOR 3 HUMID 136963.36 0.00 136963.36 0.00 136963.36 136629.01 4835.26 0.88 3923.85 3214.96
FLOOR 3 JANITOR 67577.37 0.00 67577.37 60636.06 128213.42 112517.82 6310.69 83.58 2365.73 2608.96
FLOOR 3 LOCKER 224574.61 0.00 224574.61 0.00 224574.61 241109.67 4834.50 0.50 3925.00 2608.96
FLOOR 3 LOUNGE 1407288.23 0.00 1407288.23 87164.33 1494452.56 1525018.65 4831.36 0.87 3927.77 2608.96
FLOOR 3 LOUNGE TOILET 449317.49 0.00 449317.49 45477.04 494794.53 0.00 0.00 0.00 7122.39 2608.96
FLOOR 3 MECHANICAL 1201636.59 0.00 1201636.59 94743.84 1296380.43 0.00 0.00 0.00 7122.39 2608.96
FLOOR 3 MECHANICAL HALL 332538.03 0.00 332538.03 0.00 332538.03 267900.02 4828.05 1.42 3930.53 2608.96
FLOOR 3 OFFICE 3329394.68 0.00 3329394.68 280441.76 3609836.43 3840793.32 4833.13 0.82 3926.05 3214.96
FLOOR 3 OFFICE HALL 851444.37 0.00 851444.37 22738.52 874182.89 744762.06 4831.89 0.67 3927.44 2608.96
FLOOR 3 OFFICE TOILET 130966.69 0.00 130966.69 22738.52 153705.21 0.00 0.00 0.00 7122.39 2608.96
FLOOR 3 PHYSICAL THERAPY 1 3176299.73 0.00 3176299.73 322129.05 3498428.78 5804496.67 6633.34 240.81 1885.85 2608.96
FLOOR 3 PHYSICAL THERAPY 2 1232547.79 0.00 1232547.79 0.00 1232547.79 2643278.48 7924.62 26.83 808.55 2608.96
FLOOR 3 PHYSICAL THERAPY TOILET 194556.57 0.00 194556.57 0.00 194556.57 0.00 0.00 0.00 7122.39 2608.96
FLOOR 3 STORAGE 1 218543.25 0.00 218543.25 0.00 218543.25 192887.70 4821.00 0.00 3939.00 2608.96
FLOOR 3 STORAGE 2 78181.31 0.00 78181.31 0.00 78181.31 150023.77 6942.05 127.98 1689.97 2608.96
FLOOR 3 TREATMENT 1036386.90 0.00 1036386.90 0.00 1036386.90 2125338.78 7888.71 19.89 851.39 2608.96
FLOOR 3 UNDEVELOPED 1 2701351.52 0.00 2701351.52 272862.25 2974213.77 4050641.69 5779.50 27.89 2952.61 2608.96
FLOOR 3 UNDEVELOPED 2 1455735.14 0.00 1455735.14 212226.20 1667961.33 2057468.80 5699.34 25.49 3035.17 2608.96
FLOOR 3 UTILITY 161036.67 0.00 161036.67 0.00 161036.67 385775.40 8672.15 53.00 34.85 2608.96
FLOOR 3 WORK 953147.54 0.00 953147.54 155379.89 1108527.43 726157.89 4819.22 2.20 3938.58 3214.96
NE STAIR 476979.35 0.00 476979.35 336171.75 813151.10 150024.01 4688.24 3.64 4068.12 922.74
NW ELEVATOR 323131.92 0.00 323131.92 259332.49 582464.42 0.00 0.00 0.00 5289.08 922.74
NW STAIR 516067.12 0.00 516067.12 384196.29 900263.41 171456.01 4672.52 5.68 4081.80 922.74
SW STAIR 290795.32 0.00 290795.32 192098.14 482893.46 85728.01 4616.03 6.33 4137.65 922.74
Total Facility 76934248.08 0.00 76934248.08 16679431.87 93613679.95 0.12E+09 8760.00 3958.92 7705.29 4445.28


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
FLOOR 1 ANESTHESIA 0.0214 0.0000 0.0214 0.0004 0.0218 0.0153 341.55 0.00 4403.45
FLOOR 1 BIO HAZ 0.0017 0.0000 0.0017 0.0000 0.0017 0.0032 4744.80 0.00 0.20
FLOOR 1 CAFE 0.1530 0.0000 0.1530 0.0010 0.1540 0.1843 806.00 3939.00 0.00
FLOOR 1 CLEAN 0.0239 0.0000 0.0239 0.0000 0.0239 0.0178 341.55 0.00 4403.45
FLOOR 1 CLEAN WORK 0.0299 0.0000 0.0299 0.0000 0.0299 0.0234 341.55 0.00 4403.45
FLOOR 1 DICTATION 0.0053 0.0000 0.0053 0.0000 0.0053 0.0051 1986.12 32.97 2119.91
FLOOR 1 DRESSING ROOM 0.0036 0.0000 0.0036 0.0004 0.0041 0.0018 341.55 0.00 3797.45
FLOOR 1 ELECTRICAL ROOM 0.0110 0.0000 0.0110 0.0003 0.0114 0.0000 0.00 0.00 4403.45
FLOOR 1 ELEVATOR PUMP ROOM 0.0000 0.0000 0.0000 0.0010 0.0010 0.0000 0.00 0.00 0.00
FLOOR 1 HUMID 0.0029 0.0000 0.0029 0.0000 0.0029 0.0022 846.58 11.56 3280.86
FLOOR 1 IT HALL 0.0045 0.0000 0.0045 0.0000 0.0045 0.0040 1201.06 63.95 3479.99
FLOOR 1 IT ROOM 0.0049 0.0000 0.0049 0.0000 0.0049 0.0045 1703.42 21.24 2414.34
FLOOR 1 LOBBY 0.0479 0.0000 0.0479 0.0011 0.0489 0.0323 1402.96 9.61 3332.43
FLOOR 1 LOBBY HALL 0.0133 0.0000 0.0133 0.0000 0.0133 0.0068 805.97 0.00 3939.03
FLOOR 1 LOBBY TOILET 0.0096 0.0000 0.0096 0.0003 0.0098 0.0000 0.00 0.00 4403.45
FLOOR 1 LOCKER ROOM 0.0560 0.0000 0.0560 0.0011 0.0571 0.0421 1372.95 5.80 3366.25
FLOOR 1 LOCKER ROOM HALL 0.0168 0.0000 0.0168 0.0000 0.0168 0.0140 1633.63 29.72 3081.65
FLOOR 1 LOUNGE 0.0291 0.0000 0.0291 0.0000 0.0291 0.0229 1369.71 5.63 3369.66
FLOOR 1 MED GAS 0.0040 0.0000 0.0040 0.0007 0.0048 0.0032 2013.86 45.48 2685.66
FLOOR 1 MRI CONTROL ROOM 0.0197 0.0000 0.0197 0.0000 0.0197 0.0238 806.00 3939.00 0.00
FLOOR 1 MRI HALL 0.0070 0.0000 0.0070 0.0000 0.0070 0.0042 809.39 0.74 3934.87
FLOOR 1 MRI ROOM 0.0517 0.0000 0.0517 0.0000 0.0517 0.0623 806.00 3939.00 0.00
FLOOR 1 MRI TOILET 0.0083 0.0000 0.0083 0.0003 0.0086 0.0000 0.00 0.00 4403.45
FLOOR 1 NOURISHMENT 0.0123 0.0000 0.0123 0.0000 0.0123 0.0137 2110.99 64.58 2569.44
FLOOR 1 NURSE HALL 0.0154 0.0000 0.0154 0.0000 0.0154 0.0140 1465.88 174.67 3104.45
FLOOR 1 NURSE JANITOR 0.0021 0.0000 0.0021 0.0000 0.0021 0.0031 4569.89 37.93 137.17
FLOOR 1 NURSE STATION 0.0161 0.0000 0.0161 0.0000 0.0161 0.0197 2633.56 193.56 1917.89
FLOOR 1 NURSE TOILET 0.0080 0.0000 0.0080 0.0000 0.0080 0.0000 0.00 0.00 4403.45
FLOOR 1 OFFICE 0.0215 0.0000 0.0215 0.0000 0.0215 0.0194 1551.48 16.80 2570.73
FLOOR 1 OPERATING ROOM 1 0.1982 0.0000 0.1982 0.0021 0.2003 0.2388 806.00 3939.00 0.00
FLOOR 1 OPERATING ROOM 2 0.2069 0.0000 0.2069 0.0011 0.2080 0.2492 806.00 3939.00 0.00
FLOOR 1 OPERATING ROOM 3 0.2051 0.0000 0.2051 0.0000 0.2051 0.2471 806.00 3939.00 0.00
FLOOR 1 PACU 0.0211 0.0000 0.0211 0.0000 0.0211 0.0323 4745.00 0.00 0.00
FLOOR 1 PRE-OP HALL 0.0175 0.0000 0.0175 0.0000 0.0175 0.0150 1203.69 46.78 3494.53
FLOOR 1 PRE-OP ROOM 1 0.0292 0.0000 0.0292 0.0002 0.0294 0.0520 4745.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 2 0.0522 0.0000 0.0522 0.0000 0.0522 0.0931 4745.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 0.0081 0.0000 0.0081 0.0003 0.0084 0.0000 0.00 0.00 4403.45
FLOOR 1 PROCEDURE ROOM 0.1100 0.0000 0.1100 0.0009 0.1109 0.1076 341.55 0.00 4403.45
FLOOR 1 RECEPTION 0.0443 0.0000 0.0443 0.0006 0.0449 0.0504 1973.32 8.19 2763.49
FLOOR 1 RECEPTION HALL 0.0049 0.0000 0.0049 0.0000 0.0049 0.0036 815.37 2.66 3926.97
FLOOR 1 RECOVERY ROOM 0.0949 0.0000 0.0949 0.0022 0.0970 0.1614 4745.00 0.00 0.00
FLOOR 1 SCHEDULING 0.0062 0.0000 0.0062 0.0003 0.0065 0.0048 1586.16 1.87 2550.96
FLOOR 1 SCRUB 0.0033 0.0000 0.0033 0.0000 0.0033 0.0024 824.98 8.07 3911.96
FLOOR 1 SOIL 0.0239 0.0000 0.0239 0.0000 0.0239 0.0178 341.55 0.00 4403.45
FLOOR 1 SOIL HOLD 0.0111 0.0000 0.0111 0.0000 0.0111 0.0079 341.55 0.00 4403.45
FLOOR 1 SOIL WORK 0.0317 0.0000 0.0317 0.0000 0.0317 0.0255 341.55 0.00 4403.45
FLOOR 1 STEP DOWN 0.0485 0.0000 0.0485 0.0018 0.0503 0.0897 4745.00 0.00 0.00
FLOOR 1 STERILE HALL 0.0214 0.0000 0.0214 0.0000 0.0214 0.0174 1189.75 483.42 3071.82
FLOOR 1 STERILE STORAGE 0.0107 0.0000 0.0107 0.0000 0.0107 0.0224 4736.47 0.25 8.28
FLOOR 1 STORAGE 0.0360 0.0000 0.0360 0.0030 0.0390 0.0521 3668.59 42.24 1034.16
FLOOR 1 SUB-STERILE 0.0112 0.0000 0.0112 0.0007 0.0118 0.0056 341.55 0.00 4403.45
FLOOR 1 UTILITY HALL 0.0165 0.0000 0.0165 0.0008 0.0173 0.0072 341.55 0.00 4403.45
FLOOR 1 UTILITY JANITOR 0.0017 0.0000 0.0017 0.0000 0.0017 0.0024 4641.66 58.19 45.16
FLOOR 1 UTILITY ROOM 0.0152 0.0000 0.0152 0.0009 0.0160 0.0204 3484.30 89.32 1171.38
FLOOR 1 VESTIBULE 0.0090 0.0000 0.0090 0.6864 0.6954 0.0020 341.55 0.00 4403.45
FLOOR 2 CONFERENCE 0.0414 0.0000 0.0414 0.0030 0.0444 0.0492 1693.37 25.82 1912.81
FLOOR 2 CONFERENCE TOILET 0.0067 0.0000 0.0067 0.0000 0.0067 0.0000 0.00 0.00 4366.34
FLOOR 2 DICTATION 0.0036 0.0000 0.0036 0.0000 0.0036 0.0028 841.32 6.78 3290.90
FLOOR 2 EXAM 1 0.0389 0.0000 0.0389 0.0029 0.0418 0.0510 3484.62 163.60 1096.78
FLOOR 2 EXAM 2 0.0622 0.0000 0.0622 0.0012 0.0635 0.0765 3671.73 44.31 1028.96
FLOOR 2 EXAM 3 0.0830 0.0000 0.0830 0.0016 0.0846 0.1019 3671.73 44.31 1028.96
FLOOR 2 EXAM 4 0.0097 0.0000 0.0097 0.0005 0.0102 0.0119 2922.66 168.25 1654.08
FLOOR 2 EXAM 5 0.0449 0.0000 0.0449 0.0017 0.0466 0.0496 2767.45 125.19 1852.36
FLOOR 2 EXAM 6 0.0273 0.0000 0.0273 0.0010 0.0283 0.0319 3533.47 55.84 1155.69
FLOOR 2 EXAM 7 0.0913 0.0000 0.0913 0.0016 0.0929 0.1121 3671.73 44.31 1028.96
FLOOR 2 EXAM 8 0.0327 0.0000 0.0327 0.0012 0.0339 0.0382 3538.41 55.39 1151.20
FLOOR 2 EXAM 9 0.0483 0.0000 0.0483 0.0008 0.0491 0.0561 3518.23 54.57 1172.20
FLOOR 2 EXAM HALL 1 0.0093 0.0000 0.0093 0.0000 0.0093 0.0051 814.48 0.50 3930.02
FLOOR 2 EXAM HALL 2 0.0086 0.0000 0.0086 0.0000 0.0086 0.0051 816.25 0.64 3928.11
FLOOR 2 EXAM HALL 3 0.0078 0.0000 0.0078 0.0000 0.0078 0.0051 818.64 2.67 3923.69
FLOOR 2 EXAM HALL 4 0.0089 0.0000 0.0089 0.0000 0.0089 0.0056 816.23 1.31 3927.46
FLOOR 2 EXAM HALL 5 0.0097 0.0000 0.0097 0.0000 0.0097 0.0056 814.09 0.32 3930.58
FLOOR 2 EXAM HALL 6 0.0092 0.0000 0.0092 0.0000 0.0092 0.0056 815.48 0.36 3929.15
FLOOR 2 JANITOR 0.0037 0.0000 0.0037 0.0011 0.0048 0.0036 1564.56 82.99 3097.45
FLOOR 2 LOUNGE 0.0071 0.0000 0.0071 0.0000 0.0071 0.0051 818.71 0.72 3925.57
FLOOR 2 NURSE STATION 1 0.0117 0.0000 0.0117 0.0000 0.0117 0.0113 1450.57 59.82 3234.62
FLOOR 2 NURSE STATION 2 0.0146 0.0000 0.0146 0.0000 0.0146 0.0136 1380.91 15.31 3348.78
FLOOR 2 OFFICE 0.0416 0.0000 0.0416 0.0028 0.0444 0.0225 815.84 0.41 3322.75
FLOOR 2 OFFICE HALL 0.0206 0.0000 0.0206 0.0000 0.0206 0.0126 816.34 0.64 3928.02
FLOOR 2 RECEPTION 0.0983 0.0000 0.0983 0.0034 0.1017 0.0975 1609.38 60.69 3074.94
FLOOR 2 RECEPTION HALL 0.0289 0.0000 0.0289 0.0000 0.0289 0.0160 813.48 0.32 3931.20
FLOOR 2 RECEPTION TOILET 0.0123 0.0000 0.0123 0.0000 0.0123 0.0000 0.00 0.00 4366.34
FLOOR 2 SCHEDULING 1 0.0168 0.0000 0.0168 0.0000 0.0168 0.0130 816.79 0.36 3321.85
FLOOR 2 SCHEDULING 2 0.0185 0.0000 0.0185 0.0000 0.0185 0.0137 815.98 0.23 3322.79
FLOOR 2 STORAGE 1 0.0020 0.0000 0.0020 0.0000 0.0020 0.0032 4730.85 2.31 11.84
FLOOR 2 STORAGE 2 0.0044 0.0000 0.0044 0.0000 0.0044 0.0068 4649.71 30.38 64.91
FLOOR 2 STORAGE 3 0.0059 0.0000 0.0059 0.0000 0.0059 0.0082 4135.02 108.20 501.78
FLOOR 2 UTILITY 0.0085 0.0000 0.0085 0.0006 0.0091 0.0071 1334.36 44.59 3366.04
FLOOR 2 WORK 0.0842 0.0000 0.0842 0.0019 0.0860 0.0678 1028.28 345.91 2764.82
FLOOR 2 WORK HALL 0.0443 0.0000 0.0443 0.0000 0.0443 0.0236 811.93 0.38 3932.69
FLOOR 2 WORK TOILET 0.0060 0.0000 0.0060 0.0004 0.0064 0.0000 0.00 0.00 4366.34
FLOOR 2 X-RAY 0.1519 0.0000 0.1519 0.0000 0.1519 0.1274 806.00 3636.00 303.00
FLOOR 3 DRESSING ROOM 0.0026 0.0000 0.0026 0.0000 0.0026 0.0017 819.28 1.49 3318.23
FLOOR 3 ELEVATOR HALL 0.0174 0.0000 0.0174 0.0003 0.0178 0.0105 819.65 1.08 3924.27
FLOOR 3 HUMID 0.0069 0.0000 0.0069 0.0000 0.0069 0.0043 820.26 0.88 3317.85
FLOOR 3 JANITOR 0.0034 0.0000 0.0034 0.0013 0.0047 0.0036 2295.69 83.58 2365.73
FLOOR 3 LOCKER 0.0119 0.0000 0.0119 0.0000 0.0119 0.0076 819.50 0.50 3925.00
FLOOR 3 LOUNGE 0.0753 0.0000 0.0753 0.0019 0.0771 0.0484 816.36 0.87 3927.77
FLOOR 3 LOUNGE TOILET 0.0215 0.0000 0.0215 0.0010 0.0224 0.0000 0.00 0.00 4513.43
FLOOR 3 MECHANICAL 0.0639 0.0000 0.0639 0.0020 0.0660 0.0000 0.00 0.00 4513.43
FLOOR 3 MECHANICAL HALL 0.0172 0.0000 0.0172 0.0000 0.0172 0.0085 813.05 1.42 3930.53
FLOOR 3 OFFICE 0.1698 0.0000 0.1698 0.0062 0.1760 0.1218 818.13 0.82 3320.05
FLOOR 3 OFFICE HALL 0.0443 0.0000 0.0443 0.0005 0.0448 0.0236 816.89 0.67 3927.44
FLOOR 3 OFFICE TOILET 0.0063 0.0000 0.0063 0.0005 0.0067 0.0000 0.00 0.00 4513.43
FLOOR 3 PHYSICAL THERAPY 1 0.1561 0.0000 0.1561 0.0069 0.1630 0.1841 2618.34 240.81 1885.85
FLOOR 3 PHYSICAL THERAPY 2 0.0591 0.0000 0.0591 0.0000 0.0591 0.0838 3909.62 26.83 808.55
FLOOR 3 PHYSICAL THERAPY TOILET 0.0093 0.0000 0.0093 0.0000 0.0093 0.0000 0.00 0.00 4513.43
FLOOR 3 STORAGE 1 0.0104 0.0000 0.0104 0.0000 0.0104 0.0061 806.00 0.00 3939.00
FLOOR 3 STORAGE 2 0.0040 0.0000 0.0040 0.0000 0.0040 0.0048 2927.05 127.98 1689.97
FLOOR 3 TREATMENT 0.0498 0.0000 0.0498 0.0000 0.0498 0.0674 3873.71 19.89 851.39
FLOOR 3 UNDEVELOPED 1 0.1424 0.0000 0.1424 0.0059 0.1483 0.1284 1764.50 27.89 2952.61
FLOOR 3 UNDEVELOPED 2 0.0770 0.0000 0.0770 0.0046 0.0815 0.0652 1684.34 25.49 3035.17
FLOOR 3 UTILITY 0.0082 0.0000 0.0082 0.0000 0.0082 0.0122 4657.15 53.00 34.85
FLOOR 3 WORK 0.0479 0.0000 0.0479 0.0035 0.0514 0.0230 804.22 2.20 3332.58
NE STAIR 0.0272 0.0000 0.0272 0.0072 0.0344 0.0048 688.77 2.71 4053.51
NW ELEVATOR 0.0183 0.0000 0.0183 0.0056 0.0239 0.0000 0.00 0.00 4366.34
NW STAIR 0.0293 0.0000 0.0293 0.0082 0.0376 0.0054 703.12 2.99 4038.89
SW STAIR 0.0166 0.0000 0.0166 0.0041 0.0207 0.0027 664.90 2.72 4077.38
Total Facility 4.0602 0.0000 4.0602 0.7933 4.8535 3.9552 4745.00 3950.16 4676.02


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
AHU-1 30811460.34 0.00 30811460.34 33604179.83 2893.69 0.00 5866.31 1462.86
AHU-2 27270406.71 0.00 27270406.71 30009397.83 4823.55 0.77 3935.69 922.74
AHU-3 28536437.25 0.00 28536437.25 25388343.28 4825.61 0.45 3933.94 2608.96
PSZ_CAFE 3781434.99 0.00 3781434.99 5813424.33 4821.00 0.00 3939.00 0.00
PSZ_ELEVATOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ_MRI_CONTROL 487927.29 0.00 487927.29 750119.57 4821.00 0.00 3939.00 0.00
PSZ_MRI 1277904.81 0.00 1277904.81 1964598.87 4821.00 0.00 3939.00 0.00
PSZ_OR_1 4898633.95 0.00 4898633.95 7530960.55 4821.00 0.00 3939.00 0.00
PSZ_OR_2 5111618.03 0.00 5111618.03 7858393.62 4821.00 0.00 3939.00 0.00
PSZ_OR_3 5069021.21 0.00 5069021.21 7792907.01 4821.00 0.00 3939.00 0.00
PSZ_XRAY 4046701.88 0.00 4046701.88 4018497.70 4753.26 0.00 4006.74 67.74


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
AHU-1 1.4523 0.0000 1.4523 1.0656 341.55 0.00 4403.45
AHU-2 1.5425 0.0000 1.5425 0.9516 808.55 0.77 3935.69
AHU-3 1.4641 0.0000 1.4641 0.8051 810.61 0.45 3933.94
PSZ_CAFE 0.2214 0.0000 0.2214 0.1843 806.00 0.00 3939.00
PSZ_ELEVATOR 0.0000 0.0000 0.0000 0.0000 0.00 0.00 0.00
PSZ_MRI_CONTROL 0.0286 0.0000 0.0286 0.0238 806.00 0.00 3939.00
PSZ_MRI 0.0748 0.0000 0.0748 0.0623 806.00 0.00 3939.00
PSZ_OR_1 0.2868 0.0000 0.2868 0.2388 806.00 0.00 3939.00
PSZ_OR_2 0.2992 0.0000 0.2992 0.2492 806.00 0.00 3939.00
PSZ_OR_3 0.2967 0.0000 0.2967 0.2471 806.00 0.00 3939.00
PSZ_XRAY 0.2197 0.0000 0.2197 0.1274 806.00 0.00 3939.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
AHU-1 0.00 5866.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AHU-2 0.00 2165.75 0.00 1350.08 0.00 0.00 1773.25 0.00 0.00 0.00
AHU-3 0.00 3053.59 0.00 3183.39 0.00 0.00 885.41 0.00 0.00 0.00
PSZ_CAFE 0.00 3939.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ_ELEVATOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ_MRI_CONTROL 0.00 3939.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ_MRI 0.00 3939.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ_OR_1 0.00 3939.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ_OR_2 0.00 3939.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ_OR_3 0.00 3939.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ_XRAY 0.00 3636.00 0.00 370.74 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
AHU-1 0.0000 1.5651 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AHU-2 0.0000 1.8125 0.0000 0.2778 0.0000 0.0000 1.8479 0.0000 0.0000 0.0000
AHU-3 0.0000 1.7634 0.0000 0.3758 0.0000 0.0000 1.5230 0.0000 0.0000 0.0000
PSZ_CAFE 0.0000 0.2667 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ_ELEVATOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ_MRI_CONTROL 0.0000 0.0344 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ_MRI 0.0000 0.0901 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ_OR_1 0.0000 0.3455 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ_OR_2 0.0000 0.3606 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ_OR_3 0.0000 0.3576 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ_XRAY 0.0000 0.1844 0.0000 1.2329 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Surfaces by Class

Total Outdoors
Wall 672 86
Floor 259 30
Roof 229 29
Internal Mass 118 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 94 94
Door 23 23
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 11
Conditioned Zones 118
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4112
Defaulted Fields 3174
Fields with Defaults 15661
Autosized Fields 1232
Autosizable Fields 1755
Autocalculated Fields 1515
Autocalculatable Fields 3028



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 4140.12 27885.06 05-FEB-18:00 285805.09 28-JUL-15:10
Electricity:Building 1967.32 24755.54 01-JAN-00:10 110844.53 02-JAN-07:10
Electricity:Zone:FLOOR 1 ANESTHESIA 6.28 72.29 01-JAN-00:10 359.76 02-JAN-07:10
Electricity:SpaceType:GENERAL 1967.32 24755.54 01-JAN-00:10 110844.53 02-JAN-07:10
InteriorLights:Electricity 626.08 2294.37 01-JAN-00:10 41298.67 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 ANESTHESIA 2.21 8.10 01-JAN-00:10 145.80 02-JAN-07:10
InteriorLights:Electricity:SpaceType:GENERAL 626.08 2294.37 01-JAN-00:10 41298.67 02-JAN-07:10
LightsWired:InteriorLights:Electricity 626.08 2294.37 01-JAN-00:10 41298.67 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 ANESTHESIA 2.21 8.10 01-JAN-00:10 145.80 02-JAN-07:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 626.08 2294.37 01-JAN-00:10 41298.67 02-JAN-07:10
Electricity:Zone:FLOOR 1 BIO HAZ 0.79 4.19 01-JAN-00:10 50.93 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 BIO HAZ 0.69 2.52 01-JAN-00:10 45.36 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 BIO HAZ 0.69 2.52 01-JAN-00:10 45.36 02-JAN-07:10
Electricity:Zone:FLOOR 1 CAFE 13.07 143.65 01-JAN-00:10 756.04 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 CAFE 5.16 18.90 01-JAN-00:10 340.20 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 CAFE 5.16 18.90 01-JAN-00:10 340.20 02-JAN-07:10
Electricity:Zone:FLOOR 1 CLEAN 7.33 84.34 01-JAN-00:10 419.72 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 CLEAN 2.58 9.45 01-JAN-00:10 170.10 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 CLEAN 2.58 9.45 01-JAN-00:10 170.10 02-JAN-07:10
Electricity:Zone:FLOOR 1 CLEAN WORK 9.59 110.44 01-JAN-00:10 549.63 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 CLEAN WORK 3.38 12.37 01-JAN-00:10 222.75 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 CLEAN WORK 3.38 12.37 01-JAN-00:10 222.75 02-JAN-07:10
Electricity:Zone:FLOOR 1 DICTATION 4.50 48.11 01-JAN-00:10 262.01 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 DICTATION 1.89 6.93 01-JAN-00:10 124.74 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 DICTATION 1.89 6.93 01-JAN-00:10 124.74 02-JAN-07:10
Electricity:Zone:FLOOR 1 DRESSING ROOM 1.61 17.18 01-JAN-00:10 93.58 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 DRESSING ROOM 0.68 2.47 01-JAN-00:10 44.55 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 DRESSING ROOM 0.68 2.47 01-JAN-00:10 44.55 02-JAN-07:10
Electricity:Zone:FLOOR 1 ELECTRICAL ROOM 11.23 152.95 01-JAN-00:10 617.63 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 ELECTRICAL ROOM 2.01 7.35 01-JAN-00:10 132.30 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 ELECTRICAL ROOM 2.01 7.35 01-JAN-00:10 132.30 02-JAN-07:10
Electricity:Zone:FLOOR 1 ELEVATOR PUMP ROOM 152.97 3692.82 01-JAN-00:10 7084.81 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 ELEVATOR PUMP ROOM 1.86 6.82 01-JAN-00:10 122.85 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 ELEVATOR PUMP ROOM 1.86 6.82 01-JAN-00:10 122.85 02-JAN-07:10
Electricity:Zone:FLOOR 1 HUMID 1.93 20.62 01-JAN-00:10 112.29 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 HUMID 0.81 2.97 01-JAN-00:10 53.46 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 HUMID 0.81 2.97 01-JAN-00:10 53.46 02-JAN-07:10
Electricity:Zone:FLOOR 1 IT HALL 2.88 23.36 01-JAN-00:10 176.14 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 IT HALL 1.83 6.70 01-JAN-00:10 120.62 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 IT HALL 1.83 6.70 01-JAN-00:10 120.62 02-JAN-07:10
Electricity:Zone:FLOOR 1 IT ROOM 4.00 42.77 01-JAN-00:10 232.90 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 IT ROOM 1.68 6.16 01-JAN-00:10 110.88 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 IT ROOM 1.68 6.16 01-JAN-00:10 110.88 02-JAN-07:10
Electricity:Zone:FLOOR 1 LOBBY 23.92 243.73 01-JAN-00:10 1405.40 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 LOBBY 11.03 40.43 01-JAN-00:10 727.74 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 LOBBY 11.03 40.43 01-JAN-00:10 727.74 02-JAN-07:10
Electricity:Zone:FLOOR 1 LOBBY HALL 4.94 40.04 01-JAN-00:10 301.95 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 LOBBY HALL 3.13 11.49 01-JAN-00:10 206.77 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 LOBBY HALL 3.13 11.49 01-JAN-00:10 206.77 02-JAN-07:10
Electricity:Zone:FLOOR 1 LOBBY TOILET 1.07 8.85 01-JAN-00:10 65.16 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 LOBBY TOILET 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 LOBBY TOILET 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
Electricity:Zone:FLOOR 1 LOCKER ROOM 44.50 614.70 01-JAN-00:10 2436.21 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 LOCKER ROOM 7.20 26.40 01-JAN-00:10 475.20 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 LOCKER ROOM 7.20 26.40 01-JAN-00:10 475.20 02-JAN-07:10
Electricity:Zone:FLOOR 1 LOCKER ROOM HALL 10.22 82.75 01-JAN-00:10 624.04 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 LOCKER ROOM HALL 6.48 23.74 01-JAN-00:10 427.33 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 LOCKER ROOM HALL 6.48 23.74 01-JAN-00:10 427.33 02-JAN-07:10
Electricity:Zone:FLOOR 1 LOUNGE 24.27 335.29 01-JAN-00:10 1328.84 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 LOUNGE 3.93 14.40 01-JAN-00:10 259.20 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 LOUNGE 3.93 14.40 01-JAN-00:10 259.20 02-JAN-07:10
Electricity:Zone:FLOOR 1 MED GAS 0.79 4.19 01-JAN-00:10 50.93 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 MED GAS 0.69 2.52 01-JAN-00:10 45.36 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 MED GAS 0.69 2.52 01-JAN-00:10 45.36 02-JAN-07:10
Electricity:Zone:FLOOR 1 MRI CONTROL ROOM 35.08 511.80 01-JAN-00:10 1890.79 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 MRI CONTROL ROOM 3.44 12.60 01-JAN-00:10 226.80 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 MRI CONTROL ROOM 3.44 12.60 01-JAN-00:10 226.80 02-JAN-07:10
Electricity:Zone:FLOOR 1 MRI HALL 3.03 24.53 01-JAN-00:10 184.95 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 MRI HALL 1.92 7.04 01-JAN-00:10 126.65 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 MRI HALL 1.92 7.04 01-JAN-00:10 126.65 02-JAN-07:10
Electricity:Zone:FLOOR 1 MRI ROOM 91.88 1340.42 01-JAN-00:10 4952.06 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 MRI ROOM 9.00 33.00 01-JAN-00:10 594.00 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 MRI ROOM 9.00 33.00 01-JAN-00:10 594.00 02-JAN-07:10
Electricity:Zone:FLOOR 1 MRI TOILET 1.07 8.85 01-JAN-00:10 65.16 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 MRI TOILET 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 MRI TOILET 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
Electricity:Zone:FLOOR 1 NOURISHMENT 9.34 117.27 01-JAN-00:10 524.36 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 NOURISHMENT 2.48 9.10 01-JAN-00:10 163.80 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 NOURISHMENT 2.48 9.10 01-JAN-00:10 163.80 02-JAN-07:10
Electricity:Zone:FLOOR 1 NURSE HALL 10.22 82.75 01-JAN-00:10 624.04 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 NURSE HALL 6.48 23.74 01-JAN-00:10 427.33 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 NURSE HALL 6.48 23.74 01-JAN-00:10 427.33 02-JAN-07:10
Electricity:Zone:FLOOR 1 NURSE JANITOR 0.77 4.04 01-JAN-00:10 49.11 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 NURSE JANITOR 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 NURSE JANITOR 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
Electricity:Zone:FLOOR 1 NURSE STATION 13.39 168.17 01-JAN-00:10 751.97 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 NURSE STATION 3.56 13.05 01-JAN-00:10 234.90 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 NURSE STATION 3.56 13.05 01-JAN-00:10 234.90 02-JAN-07:10
Electricity:Zone:FLOOR 1 NURSE TOILET 1.07 8.85 01-JAN-00:10 65.16 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 NURSE TOILET 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 NURSE TOILET 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
Electricity:Zone:FLOOR 1 OFFICE 17.26 184.43 01-JAN-00:10 1004.39 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 OFFICE 7.25 26.56 01-JAN-00:10 478.17 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 OFFICE 7.25 26.56 01-JAN-00:10 478.17 02-JAN-07:10
Electricity:Zone:FLOOR 1 OPERATING ROOM 1 48.47 597.39 01-JAN-00:10 2733.43 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 OPERATING ROOM 1 13.81 50.60 01-JAN-00:10 910.80 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 OPERATING ROOM 1 13.81 50.60 01-JAN-00:10 910.80 02-JAN-07:10
Electricity:Zone:FLOOR 1 OPERATING ROOM 2 50.58 623.36 01-JAN-00:10 2852.28 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 OPERATING ROOM 2 14.41 52.80 01-JAN-00:10 950.40 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 OPERATING ROOM 2 14.41 52.80 01-JAN-00:10 950.40 02-JAN-07:10
Electricity:Zone:FLOOR 1 OPERATING ROOM 3 50.15 618.17 01-JAN-00:10 2828.51 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 OPERATING ROOM 3 14.29 52.36 01-JAN-00:10 942.48 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 OPERATING ROOM 3 14.29 52.36 01-JAN-00:10 942.48 02-JAN-07:10
Electricity:Zone:FLOOR 1 PACU 7.28 100.59 01-JAN-00:10 398.65 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 PACU 1.18 4.32 01-JAN-00:10 77.76 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 PACU 1.18 4.32 01-JAN-00:10 77.76 02-JAN-07:10
Electricity:Zone:FLOOR 1 PRE-OP HALL 10.88 88.09 01-JAN-00:10 664.30 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 PRE-OP HALL 6.90 25.27 01-JAN-00:10 454.90 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 PRE-OP HALL 6.90 25.27 01-JAN-00:10 454.90 02-JAN-07:10
Electricity:Zone:FLOOR 1 PRE-OP ROOM 1 8.93 118.94 01-JAN-00:10 493.50 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 PRE-OP ROOM 1 1.81 6.61 01-JAN-00:10 119.07 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 PRE-OP ROOM 1 1.81 6.61 01-JAN-00:10 119.07 02-JAN-07:10
Electricity:Zone:FLOOR 1 PRE-OP ROOM 2 15.96 212.72 01-JAN-00:10 882.56 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 PRE-OP ROOM 2 3.23 11.83 01-JAN-00:10 212.94 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 PRE-OP ROOM 2 3.23 11.83 01-JAN-00:10 212.94 02-JAN-07:10
Electricity:Zone:FLOOR 1 PRE-OP TOILET 1.07 8.85 01-JAN-00:10 65.16 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 PRE-OP TOILET 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 PRE-OP TOILET 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
Electricity:Zone:FLOOR 1 PROCEDURE ROOM 21.94 275.41 01-JAN-00:10 1231.55 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 PROCEDURE ROOM 5.83 21.37 01-JAN-00:10 384.75 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 PROCEDURE ROOM 5.83 21.37 01-JAN-00:10 384.75 02-JAN-07:10
Electricity:Zone:FLOOR 1 RECEPTION 19.57 199.45 01-JAN-00:10 1150.07 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 RECEPTION 9.03 33.08 01-JAN-00:10 595.53 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 RECEPTION 9.03 33.08 01-JAN-00:10 595.53 02-JAN-07:10
Electricity:Zone:FLOOR 1 RECEPTION HALL 2.64 21.36 01-JAN-00:10 161.04 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 RECEPTION HALL 1.67 6.13 01-JAN-00:10 110.28 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 RECEPTION HALL 1.67 6.13 01-JAN-00:10 110.28 02-JAN-07:10
Electricity:Zone:FLOOR 1 RECOVERY ROOM 36.41 502.94 01-JAN-00:10 1993.26 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 RECOVERY ROOM 5.89 21.60 01-JAN-00:10 388.80 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 RECOVERY ROOM 5.89 21.60 01-JAN-00:10 388.80 02-JAN-07:10
Electricity:Zone:FLOOR 1 SCHEDULING 4.25 45.44 01-JAN-00:10 247.46 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 SCHEDULING 1.79 6.54 01-JAN-00:10 117.81 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 SCHEDULING 1.79 6.54 01-JAN-00:10 117.81 02-JAN-07:10
Electricity:Zone:FLOOR 1 SCRUB 1.73 14.01 01-JAN-00:10 105.68 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 SCRUB 1.10 4.02 01-JAN-00:10 72.37 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 SCRUB 1.10 4.02 01-JAN-00:10 72.37 02-JAN-07:10
Electricity:Zone:FLOOR 1 SOIL 7.33 84.34 01-JAN-00:10 419.72 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 SOIL 2.58 9.45 01-JAN-00:10 170.10 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 SOIL 2.58 9.45 01-JAN-00:10 170.10 02-JAN-07:10
Electricity:Zone:FLOOR 1 SOIL HOLD 3.26 37.48 01-JAN-00:10 186.54 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 SOIL HOLD 1.15 4.20 01-JAN-00:10 75.60 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 SOIL HOLD 1.15 4.20 01-JAN-00:10 75.60 02-JAN-07:10
Electricity:Zone:FLOOR 1 SOIL WORK 10.47 120.48 01-JAN-00:10 599.60 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 SOIL WORK 3.68 13.50 01-JAN-00:10 243.00 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 SOIL WORK 3.68 13.50 01-JAN-00:10 243.00 02-JAN-07:10
Electricity:Zone:FLOOR 1 STEP DOWN 20.23 279.41 01-JAN-00:10 1107.37 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 STEP DOWN 3.27 12.00 01-JAN-00:10 216.00 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 STEP DOWN 3.27 12.00 01-JAN-00:10 216.00 02-JAN-07:10
Electricity:Zone:FLOOR 1 STERILE HALL 12.69 102.77 01-JAN-00:10 775.02 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 STERILE HALL 8.05 29.48 01-JAN-00:10 530.72 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 STERILE HALL 8.05 29.48 01-JAN-00:10 530.72 02-JAN-07:10
Electricity:Zone:FLOOR 1 STERILE STORAGE 5.61 29.63 01-JAN-00:10 360.11 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 STERILE STORAGE 4.86 17.82 01-JAN-00:10 320.76 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 STERILE STORAGE 4.86 17.82 01-JAN-00:10 320.76 02-JAN-07:10
Electricity:Zone:FLOOR 1 STORAGE 13.04 68.83 01-JAN-00:10 836.63 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 STORAGE 11.30 41.40 01-JAN-00:10 745.20 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 STORAGE 11.30 41.40 01-JAN-00:10 745.20 02-JAN-07:10
Electricity:Zone:FLOOR 1 SUB-STERILE 4.04 32.70 01-JAN-00:10 246.60 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 SUB-STERILE 2.56 9.38 01-JAN-00:10 168.86 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 SUB-STERILE 2.56 9.38 01-JAN-00:10 168.86 02-JAN-07:10
Electricity:Zone:FLOOR 1 UTILITY HALL 5.27 42.71 01-JAN-00:10 322.09 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 UTILITY HALL 3.34 12.25 01-JAN-00:10 220.56 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 UTILITY HALL 3.34 12.25 01-JAN-00:10 220.56 02-JAN-07:10
Electricity:Zone:FLOOR 1 UTILITY JANITOR 0.60 3.14 01-JAN-00:10 38.19 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 UTILITY JANITOR 0.52 1.89 01-JAN-00:10 34.02 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 UTILITY JANITOR 0.52 1.89 01-JAN-00:10 34.02 02-JAN-07:10
Electricity:Zone:FLOOR 1 UTILITY ROOM 5.10 26.93 01-JAN-00:10 327.38 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 UTILITY ROOM 4.42 16.20 01-JAN-00:10 291.60 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 UTILITY ROOM 4.42 16.20 01-JAN-00:10 291.60 02-JAN-07:10
Electricity:Zone:FLOOR 1 VESTIBULE 1.48 12.01 01-JAN-00:10 90.59 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 VESTIBULE 0.94 3.45 01-JAN-00:10 62.03 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 1 VESTIBULE 0.94 3.45 01-JAN-00:10 62.03 02-JAN-07:10
Electricity:Zone:FLOOR 2 CONFERENCE 12.29 121.64 01-JAN-00:10 725.79 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 CONFERENCE 5.96 21.84 01-JAN-00:10 393.12 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 CONFERENCE 5.96 21.84 01-JAN-00:10 393.12 02-JAN-07:10
Electricity:Zone:FLOOR 2 CONFERENCE TOILET 1.27 10.49 01-JAN-00:10 77.22 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 CONFERENCE TOILET 0.79 2.88 01-JAN-00:10 51.84 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 CONFERENCE TOILET 0.79 2.88 01-JAN-00:10 51.84 02-JAN-07:10
Electricity:Zone:FLOOR 2 DICTATION 2.50 26.73 01-JAN-00:10 145.56 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 DICTATION 1.05 3.85 01-JAN-00:10 69.30 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 DICTATION 1.05 3.85 01-JAN-00:10 69.30 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 1 14.83 144.66 01-JAN-00:10 878.21 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 1 7.37 27.00 01-JAN-00:10 486.00 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM 1 7.37 27.00 01-JAN-00:10 486.00 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 2 22.24 217.00 01-JAN-00:10 1317.32 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 2 11.05 40.50 01-JAN-00:10 729.00 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM 2 11.05 40.50 01-JAN-00:10 729.00 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 3 29.65 289.33 01-JAN-00:10 1756.42 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 3 14.74 54.00 01-JAN-00:10 972.00 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM 3 14.74 54.00 01-JAN-00:10 972.00 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 4 3.46 33.75 01-JAN-00:10 204.92 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 4 1.72 6.30 01-JAN-00:10 113.40 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM 4 1.72 6.30 01-JAN-00:10 113.40 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 5 14.41 140.65 01-JAN-00:10 853.82 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 5 7.16 26.25 01-JAN-00:10 472.50 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM 5 7.16 26.25 01-JAN-00:10 472.50 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 6 9.27 90.41 01-JAN-00:10 548.88 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 6 4.60 16.87 01-JAN-00:10 303.75 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM 6 4.60 16.87 01-JAN-00:10 303.75 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 7 32.62 318.26 01-JAN-00:10 1932.07 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 7 16.21 59.40 01-JAN-00:10 1069.20 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM 7 16.21 59.40 01-JAN-00:10 1069.20 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 8 11.12 108.50 01-JAN-00:10 658.66 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 8 5.53 20.25 01-JAN-00:10 364.50 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM 8 5.53 20.25 01-JAN-00:10 364.50 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 9 16.31 159.13 01-JAN-00:10 966.03 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 9 8.10 29.70 01-JAN-00:10 534.60 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM 9 8.10 29.70 01-JAN-00:10 534.60 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM HALL 1 3.71 30.03 01-JAN-00:10 226.47 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 1 2.35 8.62 01-JAN-00:10 155.08 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 1 2.35 8.62 01-JAN-00:10 155.08 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM HALL 2 3.71 30.03 01-JAN-00:10 226.47 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 2 2.35 8.62 01-JAN-00:10 155.08 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 2 2.35 8.62 01-JAN-00:10 155.08 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM HALL 3 3.71 30.03 01-JAN-00:10 226.47 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 3 2.35 8.62 01-JAN-00:10 155.08 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 3 2.35 8.62 01-JAN-00:10 155.08 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM HALL 4 4.08 33.03 01-JAN-00:10 249.11 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 4 2.59 9.48 01-JAN-00:10 170.59 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 4 2.59 9.48 01-JAN-00:10 170.59 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM HALL 5 4.08 33.03 01-JAN-00:10 249.11 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 5 2.59 9.48 01-JAN-00:10 170.59 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 5 2.59 9.48 01-JAN-00:10 170.59 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM HALL 6 4.08 33.03 01-JAN-00:10 249.11 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 6 2.59 9.48 01-JAN-00:10 170.59 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 6 2.59 9.48 01-JAN-00:10 170.59 02-JAN-07:10
Electricity:Zone:FLOOR 2 JANITOR 0.89 4.71 01-JAN-00:10 57.29 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 JANITOR 0.77 2.83 01-JAN-00:10 51.03 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 JANITOR 0.77 2.83 01-JAN-00:10 51.03 02-JAN-07:10
Electricity:Zone:FLOOR 2 LOUNGE 5.39 74.51 01-JAN-00:10 295.30 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 LOUNGE 0.87 3.20 01-JAN-00:10 57.60 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 LOUNGE 0.87 3.20 01-JAN-00:10 57.60 02-JAN-07:10
Electricity:Zone:FLOOR 2 NURSE STATION 1 7.70 96.65 01-JAN-00:10 432.17 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 NURSE STATION 1 2.05 7.50 01-JAN-00:10 135.00 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 NURSE STATION 1 2.05 7.50 01-JAN-00:10 135.00 02-JAN-07:10
Electricity:Zone:FLOOR 2 NURSE STATION 2 9.24 115.98 01-JAN-00:10 518.60 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 NURSE STATION 2 2.46 9.00 01-JAN-00:10 162.00 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 NURSE STATION 2 2.46 9.00 01-JAN-00:10 162.00 02-JAN-07:10
Electricity:Zone:FLOOR 2 OFFICE 20.01 213.83 01-JAN-00:10 1164.51 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 OFFICE 8.40 30.80 01-JAN-00:10 554.40 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 OFFICE 8.40 30.80 01-JAN-00:10 554.40 02-JAN-07:10
Electricity:Zone:FLOOR 2 OFFICE HALL 9.15 74.08 01-JAN-00:10 558.62 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 OFFICE HALL 5.80 21.25 01-JAN-00:10 382.53 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 OFFICE HALL 5.80 21.25 01-JAN-00:10 382.53 02-JAN-07:10
Electricity:Zone:FLOOR 2 RECEPTION 37.84 385.57 01-JAN-00:10 2223.33 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 RECEPTION 17.45 63.96 01-JAN-00:10 1151.28 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 RECEPTION 17.45 63.96 01-JAN-00:10 1151.28 02-JAN-07:10
Electricity:Zone:FLOOR 2 RECEPTION HALL 11.62 94.10 01-JAN-00:10 709.59 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 RECEPTION HALL 7.37 27.00 01-JAN-00:10 485.92 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 RECEPTION HALL 7.37 27.00 01-JAN-00:10 485.92 02-JAN-07:10
Electricity:Zone:FLOOR 2 RECEPTION TOILET 2.50 20.66 01-JAN-00:10 152.03 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 RECEPTION TOILET 1.55 5.67 01-JAN-00:10 102.06 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 RECEPTION TOILET 1.55 5.67 01-JAN-00:10 102.06 02-JAN-07:10
Electricity:Zone:FLOOR 2 SCHEDULING 1 11.58 123.72 01-JAN-00:10 673.75 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 SCHEDULING 1 4.86 17.82 01-JAN-00:10 320.76 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 SCHEDULING 1 4.86 17.82 01-JAN-00:10 320.76 02-JAN-07:10
Electricity:Zone:FLOOR 2 SCHEDULING 2 12.22 130.59 01-JAN-00:10 711.18 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 SCHEDULING 2 5.13 18.81 01-JAN-00:10 338.58 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 SCHEDULING 2 5.13 18.81 01-JAN-00:10 338.58 02-JAN-07:10
Electricity:Zone:FLOOR 2 STORAGE 1 0.79 4.19 01-JAN-00:10 50.93 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 STORAGE 1 0.69 2.52 01-JAN-00:10 45.36 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 STORAGE 1 0.69 2.52 01-JAN-00:10 45.36 02-JAN-07:10
Electricity:Zone:FLOOR 2 STORAGE 2 1.70 8.98 01-JAN-00:10 109.13 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 STORAGE 2 1.47 5.40 01-JAN-00:10 97.20 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 STORAGE 2 1.47 5.40 01-JAN-00:10 97.20 02-JAN-07:10
Electricity:Zone:FLOOR 2 STORAGE 3 2.04 10.77 01-JAN-00:10 130.95 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 STORAGE 3 1.77 6.48 01-JAN-00:10 116.64 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 STORAGE 3 1.77 6.48 01-JAN-00:10 116.64 02-JAN-07:10
Electricity:Zone:FLOOR 2 UTILITY 1.79 9.43 01-JAN-00:10 114.58 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 UTILITY 1.55 5.67 01-JAN-00:10 102.06 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 UTILITY 1.55 5.67 01-JAN-00:10 102.06 02-JAN-07:10
Electricity:Zone:FLOOR 2 WORK 54.29 549.22 01-JAN-00:10 3194.01 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 WORK 25.36 92.95 01-JAN-00:10 1673.10 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 WORK 25.36 92.95 01-JAN-00:10 1673.10 02-JAN-07:10
Electricity:Zone:FLOOR 2 WORK HALL 17.18 139.15 01-JAN-00:10 1049.29 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 WORK HALL 10.89 39.92 01-JAN-00:10 718.53 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 WORK HALL 10.89 39.92 01-JAN-00:10 718.53 02-JAN-07:10
Electricity:Zone:FLOOR 2 WORK TOILET 1.07 8.85 01-JAN-00:10 65.16 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 WORK TOILET 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 WORK TOILET 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
Electricity:Zone:FLOOR 2 X-RAY 187.94 2741.77 01-JAN-00:10 10129.22 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 X-RAY 18.42 67.50 01-JAN-00:10 1215.00 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 2 X-RAY 18.42 67.50 01-JAN-00:10 1215.00 02-JAN-07:10
Electricity:Zone:FLOOR 3 DRESSING ROOM 1.50 16.04 01-JAN-00:10 87.34 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 DRESSING ROOM 0.63 2.31 01-JAN-00:10 41.58 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 DRESSING ROOM 0.63 2.31 01-JAN-00:10 41.58 02-JAN-07:10
Electricity:Zone:FLOOR 3 ELEVATOR HALL 7.62 61.73 01-JAN-00:10 465.51 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 ELEVATOR HALL 4.83 17.71 01-JAN-00:10 318.77 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 ELEVATOR HALL 4.83 17.71 01-JAN-00:10 318.77 02-JAN-07:10
Electricity:Zone:FLOOR 3 HUMID 3.86 41.24 01-JAN-00:10 224.58 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 HUMID 1.62 5.94 01-JAN-00:10 106.92 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 HUMID 1.62 5.94 01-JAN-00:10 106.92 02-JAN-07:10
Electricity:Zone:FLOOR 3 JANITOR 0.89 4.71 01-JAN-00:10 57.29 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 JANITOR 0.77 2.83 01-JAN-00:10 51.03 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 JANITOR 0.77 2.83 01-JAN-00:10 51.03 02-JAN-07:10
Electricity:Zone:FLOOR 3 LOCKER 8.09 111.76 01-JAN-00:10 442.95 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 LOCKER 1.31 4.80 01-JAN-00:10 86.40 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 LOCKER 1.31 4.80 01-JAN-00:10 86.40 02-JAN-07:10
Electricity:Zone:FLOOR 3 LOUNGE 51.17 706.91 01-JAN-00:10 2801.64 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 LOUNGE 8.28 30.36 01-JAN-00:10 546.48 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 LOUNGE 8.28 30.36 01-JAN-00:10 546.48 02-JAN-07:10
Electricity:Zone:FLOOR 3 LOUNGE TOILET 3.81 31.48 01-JAN-00:10 231.67 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 LOUNGE TOILET 2.36 8.64 01-JAN-00:10 155.52 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 LOUNGE TOILET 2.36 8.64 01-JAN-00:10 155.52 02-JAN-07:10
Electricity:Zone:FLOOR 3 MECHANICAL 40.12 546.25 01-JAN-00:10 2205.82 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 MECHANICAL 7.16 26.25 01-JAN-00:10 472.50 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 MECHANICAL 7.16 26.25 01-JAN-00:10 472.50 02-JAN-07:10
Electricity:Zone:FLOOR 3 MECHANICAL HALL 6.18 50.05 01-JAN-00:10 377.44 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 MECHANICAL HALL 3.92 14.36 01-JAN-00:10 258.47 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 MECHANICAL HALL 3.92 14.36 01-JAN-00:10 258.47 02-JAN-07:10
Electricity:Zone:FLOOR 3 OFFICE 108.47 1159.28 01-JAN-00:10 6313.29 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 OFFICE 45.56 166.98 01-JAN-00:10 3005.64 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 OFFICE 45.56 166.98 01-JAN-00:10 3005.64 02-JAN-07:10
Electricity:Zone:FLOOR 3 OFFICE HALL 17.18 139.15 01-JAN-00:10 1049.29 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 OFFICE HALL 10.89 39.92 01-JAN-00:10 718.53 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 OFFICE HALL 10.89 39.92 01-JAN-00:10 718.53 02-JAN-07:10
Electricity:Zone:FLOOR 3 OFFICE TOILET 1.07 8.85 01-JAN-00:10 65.16 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 OFFICE TOILET 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 OFFICE TOILET 0.66 2.43 01-JAN-00:10 43.74 02-JAN-07:10
Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 1 52.70 638.07 01-JAN-00:10 2984.89 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 1 15.96 58.50 01-JAN-00:10 1053.00 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 1 15.96 58.50 01-JAN-00:10 1053.00 02-JAN-07:10
Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 2 24.00 290.57 01-JAN-00:10 1359.27 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 2 7.27 26.64 01-JAN-00:10 479.52 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 2 7.27 26.64 01-JAN-00:10 479.52 02-JAN-07:10
Electricity:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 1.66 13.77 01-JAN-00:10 101.35 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 1.03 3.78 01-JAN-00:10 68.04 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 1.03 3.78 01-JAN-00:10 68.04 02-JAN-07:10
Electricity:Zone:FLOOR 3 STORAGE 1 1.53 8.08 01-JAN-00:10 98.21 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 STORAGE 1 1.33 4.86 01-JAN-00:10 87.48 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 STORAGE 1 1.33 4.86 01-JAN-00:10 87.48 02-JAN-07:10
Electricity:Zone:FLOOR 3 STORAGE 2 1.19 6.28 01-JAN-00:10 76.39 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 STORAGE 2 1.03 3.78 01-JAN-00:10 68.04 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 STORAGE 2 1.03 3.78 01-JAN-00:10 68.04 02-JAN-07:10
Electricity:Zone:FLOOR 3 TREATMENT 19.60 191.28 01-JAN-00:10 1161.19 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 TREATMENT 9.74 35.70 01-JAN-00:10 642.60 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 TREATMENT 9.74 35.70 01-JAN-00:10 642.60 02-JAN-07:10
Electricity:Zone:FLOOR 3 UNDEVELOPED 1 74.84 843.34 01-JAN-00:10 4308.02 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 UNDEVELOPED 1 27.85 102.06 01-JAN-00:10 1837.08 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 UNDEVELOPED 1 27.85 102.06 01-JAN-00:10 1837.08 02-JAN-07:10
Electricity:Zone:FLOOR 3 UNDEVELOPED 2 38.01 428.36 01-JAN-00:10 2188.20 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 UNDEVELOPED 2 14.15 51.84 01-JAN-00:10 933.12 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 UNDEVELOPED 2 14.15 51.84 01-JAN-00:10 933.12 02-JAN-07:10
Electricity:Zone:FLOOR 3 UTILITY 4.83 22.64 01-JAN-00:10 313.07 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 UTILITY 4.42 16.20 01-JAN-00:10 291.60 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 UTILITY 4.42 16.20 01-JAN-00:10 291.60 02-JAN-07:10
Electricity:Zone:FLOOR 3 WORK 20.51 219.18 01-JAN-00:10 1193.62 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 WORK 8.61 31.57 01-JAN-00:10 568.26 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:FLOOR 3 WORK 8.61 31.57 01-JAN-00:10 568.26 02-JAN-07:10
Electricity:Zone:NE STAIR 3.46 28.03 01-JAN-00:10 211.37 02-JAN-07:10
InteriorLights:Electricity:Zone:NE STAIR 2.19 8.04 01-JAN-00:10 144.74 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:NE STAIR 2.19 8.04 01-JAN-00:10 144.74 02-JAN-07:10
Electricity:Zone:NW ELEVATOR 2.88 23.36 01-JAN-00:10 176.14 02-JAN-07:10
InteriorLights:Electricity:Zone:NW ELEVATOR 1.83 6.70 01-JAN-00:10 120.62 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:NW ELEVATOR 1.83 6.70 01-JAN-00:10 120.62 02-JAN-07:10
Electricity:Zone:NW STAIR 3.96 32.03 01-JAN-00:10 241.56 02-JAN-07:10
InteriorLights:Electricity:Zone:NW STAIR 2.51 9.19 01-JAN-00:10 165.42 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:NW STAIR 2.51 9.19 01-JAN-00:10 165.42 02-JAN-07:10
Electricity:Zone:SW STAIR 1.98 16.02 01-JAN-00:10 120.78 02-JAN-07:10
InteriorLights:Electricity:Zone:SW STAIR 1.25 4.59 01-JAN-00:10 82.71 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:SW STAIR 1.25 4.59 01-JAN-00:10 82.71 02-JAN-07:10
InteriorEquipment:Electricity 1341.24 22461.17 01-JAN-00:10 69545.86 02-JAN-07:10
InteriorEquipment:Electricity:Zone:FLOOR 1 ELEVATOR PUMP ROOM 151.11 3686.00 01-JAN-00:10 6961.96 02-JAN-07:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1341.24 22461.17 01-JAN-00:10 69545.86 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity 135.78 3200.00 01-JAN-00:10 6475.96 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:Zone:FLOOR 1 ELEVATOR PUMP ROOM 135.78 3200.00 01-JAN-00:10 6475.96 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL 135.78 3200.00 01-JAN-00:10 6475.96 02-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity 15.33 486.00 01-JAN-00:10 486.00 01-JAN-00:10
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:FLOOR 1 ELEVATOR PUMP ROOM 15.33 486.00 01-JAN-00:10 486.00 01-JAN-00:10
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL 15.33 486.00 01-JAN-00:10 486.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:FLOOR 1 ANESTHESIA 4.07 64.19 01-JAN-00:10 213.96 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity 1190.14 18775.17 01-JAN-00:10 62583.90 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 ANESTHESIA 4.07 64.19 01-JAN-00:10 213.96 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 1190.14 18775.17 01-JAN-00:10 62583.90 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 BIO HAZ 0.11 1.67 01-JAN-00:10 5.57 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 BIO HAZ 0.11 1.67 01-JAN-00:10 5.57 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 CAFE 7.91 124.75 01-JAN-00:10 415.84 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 CAFE 7.91 124.75 01-JAN-00:10 415.84 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 CLEAN 4.75 74.89 01-JAN-00:10 249.62 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 CLEAN 4.75 74.89 01-JAN-00:10 249.62 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 CLEAN WORK 6.22 98.07 01-JAN-00:10 326.89 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 CLEAN WORK 6.22 98.07 01-JAN-00:10 326.89 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 DICTATION 2.61 41.18 01-JAN-00:10 137.27 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 DICTATION 2.61 41.18 01-JAN-00:10 137.27 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 DRESSING ROOM 0.93 14.71 01-JAN-00:10 49.03 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 DRESSING ROOM 0.93 14.71 01-JAN-00:10 49.03 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 ELECTRICAL ROOM 9.23 145.60 01-JAN-00:10 485.33 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 ELECTRICAL ROOM 9.23 145.60 01-JAN-00:10 485.33 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 HUMID 1.12 17.65 01-JAN-00:10 58.83 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 HUMID 1.12 17.65 01-JAN-00:10 58.83 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 IT HALL 1.06 16.66 01-JAN-00:10 55.52 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 IT HALL 1.06 16.66 01-JAN-00:10 55.52 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 IT ROOM 2.32 36.61 01-JAN-00:10 122.02 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 IT ROOM 2.32 36.61 01-JAN-00:10 122.02 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 LOBBY 12.89 203.30 01-JAN-00:10 677.66 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 LOBBY 12.89 203.30 01-JAN-00:10 677.66 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 LOBBY HALL 1.81 28.55 01-JAN-00:10 95.18 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 LOBBY HALL 1.81 28.55 01-JAN-00:10 95.18 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 LOBBY TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 LOBBY TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 LOCKER ROOM 37.29 588.30 01-JAN-00:10 1961.01 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 LOCKER ROOM 37.29 588.30 01-JAN-00:10 1961.01 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 LOCKER ROOM HALL 3.74 59.01 01-JAN-00:10 196.71 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 LOCKER ROOM HALL 3.74 59.01 01-JAN-00:10 196.71 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 LOUNGE 20.34 320.89 01-JAN-00:10 1069.64 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 LOUNGE 20.34 320.89 01-JAN-00:10 1069.64 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 MED GAS 0.11 1.67 01-JAN-00:10 5.57 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 MED GAS 0.11 1.67 01-JAN-00:10 5.57 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 MRI CONTROL ROOM 31.64 499.20 01-JAN-00:10 1663.99 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 MRI CONTROL ROOM 31.64 499.20 01-JAN-00:10 1663.99 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 MRI HALL 1.11 17.49 01-JAN-00:10 58.30 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 MRI HALL 1.11 17.49 01-JAN-00:10 58.30 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 MRI ROOM 82.88 1307.42 01-JAN-00:10 4358.06 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 MRI ROOM 82.88 1307.42 01-JAN-00:10 4358.06 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 MRI TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 MRI TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 NOURISHMENT 6.86 108.17 01-JAN-00:10 360.56 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 NOURISHMENT 6.86 108.17 01-JAN-00:10 360.56 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 NURSE HALL 3.74 59.01 01-JAN-00:10 196.71 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 NURSE HALL 3.74 59.01 01-JAN-00:10 196.71 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 NURSE JANITOR 0.10 1.61 01-JAN-00:10 5.37 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 NURSE JANITOR 0.10 1.61 01-JAN-00:10 5.37 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 NURSE STATION 9.83 155.12 01-JAN-00:10 517.07 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 NURSE STATION 9.83 155.12 01-JAN-00:10 517.07 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 NURSE TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 NURSE TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 OFFICE 10.01 157.87 01-JAN-00:10 526.22 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 OFFICE 10.01 157.87 01-JAN-00:10 526.22 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 OPERATING ROOM 1 34.66 546.79 01-JAN-00:10 1822.63 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 OPERATING ROOM 1 34.66 546.79 01-JAN-00:10 1822.63 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 OPERATING ROOM 2 36.17 570.56 01-JAN-00:10 1901.88 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 OPERATING ROOM 2 36.17 570.56 01-JAN-00:10 1901.88 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 OPERATING ROOM 3 35.87 565.81 01-JAN-00:10 1886.03 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 OPERATING ROOM 3 35.87 565.81 01-JAN-00:10 1886.03 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 PACU 6.10 96.27 01-JAN-00:10 320.89 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 PACU 6.10 96.27 01-JAN-00:10 320.89 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 PRE-OP HALL 3.98 62.82 01-JAN-00:10 209.40 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 PRE-OP HALL 3.98 62.82 01-JAN-00:10 209.40 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 PRE-OP ROOM 1 7.12 112.33 01-JAN-00:10 374.43 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 PRE-OP ROOM 1 7.12 112.33 01-JAN-00:10 374.43 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 PRE-OP ROOM 2 12.73 200.89 01-JAN-00:10 669.62 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 PRE-OP ROOM 2 12.73 200.89 01-JAN-00:10 669.62 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 PRE-OP TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 PRE-OP TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 PROCEDURE ROOM 16.10 254.04 01-JAN-00:10 846.80 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 PROCEDURE ROOM 16.10 254.04 01-JAN-00:10 846.80 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 RECEPTION 10.55 166.36 01-JAN-00:10 554.54 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 RECEPTION 10.55 166.36 01-JAN-00:10 554.54 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 RECEPTION HALL 0.97 15.23 01-JAN-00:10 50.76 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 RECEPTION HALL 0.97 15.23 01-JAN-00:10 50.76 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 RECOVERY ROOM 30.51 481.34 01-JAN-00:10 1604.46 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 RECOVERY ROOM 30.51 481.34 01-JAN-00:10 1604.46 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 SCHEDULING 2.47 38.89 01-JAN-00:10 129.65 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 SCHEDULING 2.47 38.89 01-JAN-00:10 129.65 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 SCRUB 0.63 9.99 01-JAN-00:10 33.31 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 SCRUB 0.63 9.99 01-JAN-00:10 33.31 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 SOIL 4.75 74.89 01-JAN-00:10 249.62 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 SOIL 4.75 74.89 01-JAN-00:10 249.62 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 SOIL HOLD 2.11 33.28 01-JAN-00:10 110.94 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 SOIL HOLD 2.11 33.28 01-JAN-00:10 110.94 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 SOIL WORK 6.78 106.98 01-JAN-00:10 356.60 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 SOIL WORK 6.78 106.98 01-JAN-00:10 356.60 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 STEP DOWN 16.95 267.41 01-JAN-00:10 891.37 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 STEP DOWN 16.95 267.41 01-JAN-00:10 891.37 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 STERILE HALL 4.65 73.29 01-JAN-00:10 244.30 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 STERILE HALL 4.65 73.29 01-JAN-00:10 244.30 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 STERILE STORAGE 0.75 11.81 01-JAN-00:10 39.35 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 STERILE STORAGE 0.75 11.81 01-JAN-00:10 39.35 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 STORAGE 1.74 27.43 01-JAN-00:10 91.43 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 STORAGE 1.74 27.43 01-JAN-00:10 91.43 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 SUB-STERILE 1.48 23.32 01-JAN-00:10 77.73 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 SUB-STERILE 1.48 23.32 01-JAN-00:10 77.73 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 UTILITY HALL 1.93 30.46 01-JAN-00:10 101.53 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 UTILITY HALL 1.93 30.46 01-JAN-00:10 101.53 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 UTILITY JANITOR 0.08 1.25 01-JAN-00:10 4.17 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 UTILITY JANITOR 0.08 1.25 01-JAN-00:10 4.17 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 UTILITY ROOM 0.68 10.73 01-JAN-00:10 35.78 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 UTILITY ROOM 0.68 10.73 01-JAN-00:10 35.78 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 VESTIBULE 0.54 8.57 01-JAN-00:10 28.55 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 1 VESTIBULE 0.54 8.57 01-JAN-00:10 28.55 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 CONFERENCE 6.33 99.80 01-JAN-00:10 332.67 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 CONFERENCE 6.33 99.80 01-JAN-00:10 332.67 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 CONFERENCE TOILET 0.48 7.61 01-JAN-00:10 25.38 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 CONFERENCE TOILET 0.48 7.61 01-JAN-00:10 25.38 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 DICTATION 1.45 22.88 01-JAN-00:10 76.26 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 DICTATION 1.45 22.88 01-JAN-00:10 76.26 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 1 7.46 117.66 01-JAN-00:10 392.21 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 1 7.46 117.66 01-JAN-00:10 392.21 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 2 11.19 176.50 01-JAN-00:10 588.32 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 2 11.19 176.50 01-JAN-00:10 588.32 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 3 14.92 235.33 01-JAN-00:10 784.42 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 3 14.92 235.33 01-JAN-00:10 784.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 4 1.74 27.45 01-JAN-00:10 91.52 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 4 1.74 27.45 01-JAN-00:10 91.52 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 5 7.25 114.40 01-JAN-00:10 381.32 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 5 7.25 114.40 01-JAN-00:10 381.32 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 6 4.66 73.54 01-JAN-00:10 245.13 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 6 4.66 73.54 01-JAN-00:10 245.13 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 7 16.41 258.86 01-JAN-00:10 862.87 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 7 16.41 258.86 01-JAN-00:10 862.87 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 8 5.59 88.25 01-JAN-00:10 294.16 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 8 5.59 88.25 01-JAN-00:10 294.16 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 9 8.20 129.43 01-JAN-00:10 431.43 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 9 8.20 129.43 01-JAN-00:10 431.43 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 1 1.36 21.42 01-JAN-00:10 71.39 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 1 1.36 21.42 01-JAN-00:10 71.39 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 2 1.36 21.42 01-JAN-00:10 71.39 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 2 1.36 21.42 01-JAN-00:10 71.39 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 3 1.36 21.42 01-JAN-00:10 71.39 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 3 1.36 21.42 01-JAN-00:10 71.39 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 4 1.49 23.56 01-JAN-00:10 78.53 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 4 1.49 23.56 01-JAN-00:10 78.53 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 5 1.49 23.56 01-JAN-00:10 78.53 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 5 1.49 23.56 01-JAN-00:10 78.53 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 6 1.49 23.56 01-JAN-00:10 78.53 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 6 1.49 23.56 01-JAN-00:10 78.53 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 JANITOR 0.12 1.88 01-JAN-00:10 6.26 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 JANITOR 0.12 1.88 01-JAN-00:10 6.26 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 LOUNGE 4.52 71.31 01-JAN-00:10 237.70 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 LOUNGE 4.52 71.31 01-JAN-00:10 237.70 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 NURSE STATION 1 5.65 89.15 01-JAN-00:10 297.17 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 NURSE STATION 1 5.65 89.15 01-JAN-00:10 297.17 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 NURSE STATION 2 6.78 106.98 01-JAN-00:10 356.60 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 NURSE STATION 2 6.78 106.98 01-JAN-00:10 356.60 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 OFFICE 11.60 183.03 01-JAN-00:10 610.11 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 OFFICE 11.60 183.03 01-JAN-00:10 610.11 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 OFFICE HALL 3.35 52.83 01-JAN-00:10 176.09 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 OFFICE HALL 3.35 52.83 01-JAN-00:10 176.09 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 RECEPTION 20.39 321.61 01-JAN-00:10 1072.05 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 RECEPTION 20.39 321.61 01-JAN-00:10 1072.05 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 RECEPTION HALL 4.25 67.10 01-JAN-00:10 223.68 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 RECEPTION HALL 4.25 67.10 01-JAN-00:10 223.68 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 RECEPTION TOILET 0.95 14.99 01-JAN-00:10 49.97 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 RECEPTION TOILET 0.95 14.99 01-JAN-00:10 49.97 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 SCHEDULING 1 6.71 105.90 01-JAN-00:10 352.99 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 SCHEDULING 1 6.71 105.90 01-JAN-00:10 352.99 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 SCHEDULING 2 7.09 111.78 01-JAN-00:10 372.60 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 SCHEDULING 2 7.09 111.78 01-JAN-00:10 372.60 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 STORAGE 1 0.11 1.67 01-JAN-00:10 5.57 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 STORAGE 1 0.11 1.67 01-JAN-00:10 5.57 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 STORAGE 2 0.23 3.58 01-JAN-00:10 11.93 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 STORAGE 2 0.23 3.58 01-JAN-00:10 11.93 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 STORAGE 3 0.27 4.29 01-JAN-00:10 14.31 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 STORAGE 3 0.27 4.29 01-JAN-00:10 14.31 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 UTILITY 0.24 3.76 01-JAN-00:10 12.52 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 UTILITY 0.24 3.76 01-JAN-00:10 12.52 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 WORK 28.92 456.27 01-JAN-00:10 1520.91 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 WORK 28.92 456.27 01-JAN-00:10 1520.91 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 WORK HALL 6.29 99.23 01-JAN-00:10 330.76 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 WORK HALL 6.29 99.23 01-JAN-00:10 330.76 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 WORK TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 WORK TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 X-RAY 169.52 2674.27 01-JAN-00:10 8914.22 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 2 X-RAY 169.52 2674.27 01-JAN-00:10 8914.22 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 DRESSING ROOM 0.87 13.73 01-JAN-00:10 45.76 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 DRESSING ROOM 0.87 13.73 01-JAN-00:10 45.76 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 ELEVATOR HALL 2.79 44.02 01-JAN-00:10 146.74 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 ELEVATOR HALL 2.79 44.02 01-JAN-00:10 146.74 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 HUMID 2.24 35.30 01-JAN-00:10 117.66 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 HUMID 2.24 35.30 01-JAN-00:10 117.66 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 JANITOR 0.12 1.88 01-JAN-00:10 6.26 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 JANITOR 0.12 1.88 01-JAN-00:10 6.26 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 LOCKER 6.78 106.96 01-JAN-00:10 356.55 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 LOCKER 6.78 106.96 01-JAN-00:10 356.55 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 LOUNGE 42.89 676.55 01-JAN-00:10 2255.16 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 LOUNGE 42.89 676.55 01-JAN-00:10 2255.16 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 LOUNGE TOILET 1.45 22.84 01-JAN-00:10 76.15 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 LOUNGE TOILET 1.45 22.84 01-JAN-00:10 76.15 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 MECHANICAL 32.96 520.00 01-JAN-00:10 1733.32 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 MECHANICAL 32.96 520.00 01-JAN-00:10 1733.32 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 MECHANICAL HALL 2.26 35.69 01-JAN-00:10 118.98 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 MECHANICAL HALL 2.26 35.69 01-JAN-00:10 118.98 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 OFFICE 62.90 992.30 01-JAN-00:10 3307.66 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 OFFICE 62.90 992.30 01-JAN-00:10 3307.66 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 OFFICE HALL 6.29 99.23 01-JAN-00:10 330.76 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 OFFICE HALL 6.29 99.23 01-JAN-00:10 330.76 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 OFFICE TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 OFFICE TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 1 36.74 579.57 01-JAN-00:10 1931.89 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 1 36.74 579.57 01-JAN-00:10 1931.89 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 2 16.73 263.93 01-JAN-00:10 879.75 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 2 16.73 263.93 01-JAN-00:10 879.75 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 0.63 9.99 01-JAN-00:10 33.31 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 0.63 9.99 01-JAN-00:10 33.31 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 STORAGE 1 0.20 3.22 01-JAN-00:10 10.73 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 STORAGE 1 0.20 3.22 01-JAN-00:10 10.73 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 STORAGE 2 0.16 2.50 01-JAN-00:10 8.35 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 STORAGE 2 0.16 2.50 01-JAN-00:10 8.35 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 TREATMENT 9.86 155.58 01-JAN-00:10 518.59 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 TREATMENT 9.86 155.58 01-JAN-00:10 518.59 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 UNDEVELOPED 1 46.99 741.28 01-JAN-00:10 2470.94 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 UNDEVELOPED 1 46.99 741.28 01-JAN-00:10 2470.94 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 UNDEVELOPED 2 23.87 376.52 01-JAN-00:10 1255.08 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 UNDEVELOPED 2 23.87 376.52 01-JAN-00:10 1255.08 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 UTILITY 0.41 6.44 01-JAN-00:10 21.47 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 UTILITY 0.41 6.44 01-JAN-00:10 21.47 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 WORK 11.89 187.61 01-JAN-00:10 625.36 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FLOOR 3 WORK 11.89 187.61 01-JAN-00:10 625.36 02-JAN-06:10
InteriorEquipment:Electricity:Zone:NE STAIR 1.27 19.99 01-JAN-00:10 66.63 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:NE STAIR 1.27 19.99 01-JAN-00:10 66.63 02-JAN-06:10
InteriorEquipment:Electricity:Zone:NW ELEVATOR 1.06 16.66 01-JAN-00:10 55.52 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:NW ELEVATOR 1.06 16.66 01-JAN-00:10 55.52 02-JAN-06:10
InteriorEquipment:Electricity:Zone:NW STAIR 1.45 22.84 01-JAN-00:10 76.15 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:NW STAIR 1.45 22.84 01-JAN-00:10 76.15 02-JAN-06:10
InteriorEquipment:Electricity:Zone:SW STAIR 0.72 11.42 01-JAN-00:10 38.07 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:SW STAIR 0.72 11.42 01-JAN-00:10 38.07 02-JAN-06:10
ElectricityPurchased:Facility 4140.12 27885.06 05-FEB-18:00 285805.09 28-JUL-15:10
ElectricityPurchased:Plant 4140.12 27885.06 05-FEB-18:00 285805.09 28-JUL-15:10
Cogeneration:ElectricityPurchased 4140.12 27885.06 05-FEB-18:00 285805.09 28-JUL-15:10
General:Cogeneration:ElectricityPurchased 4140.12 27885.06 05-FEB-18:00 285805.09 28-JUL-15:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 4140.12 27885.06 05-FEB-18:00 285805.09 28-JUL-15:10
ElectricityNet:Plant 4140.12 27885.06 05-FEB-18:00 285805.09 28-JUL-15:10
Cogeneration:ElectricityNet 4140.12 27885.06 05-FEB-18:00 285805.09 28-JUL-15:10
General:Cogeneration:ElectricityNet 4140.12 27885.06 05-FEB-18:00 285805.09 28-JUL-15:10
Electricity:HVAC 1934.06 2543.47 05-FEB-04:40 174919.78 28-JUL-15:10
Fans:Electricity 517.72 933.25 05-FEB-04:40 36543.99 28-JUL-15:20
General:Fans:Electricity 517.72 933.25 05-FEB-04:40 36543.99 28-JUL-15:20
Cooling:Electricity 1415.52 1610.22 05-FEB-04:40 138442.35 28-JUL-15:00
General:Cooling:Electricity 1415.52 1610.22 05-FEB-04:40 138442.35 28-JUL-15:00
Heating:Electricity 0.01 0.00 01-JAN-00:10 958.92 04-FEB-06:10
General:Heating:Electricity 0.01 0.00 01-JAN-00:10 958.92 04-FEB-06:10
ExteriorLights:Electricity 237.86 0.00 01-JAN-07:20 15116.60 01-JAN-00:10
General:ExteriorLights:Electricity 237.86 0.00 01-JAN-07:20 15116.60 01-JAN-00:10
Humidifier:Electricity 0.81 0.00 01-JAN-00:10 9892.01 04-FEB-06:50
General:Humidifier:Electricity 0.81 0.00 01-JAN-00:10 9892.01 04-FEB-06:50
Electricity:Plant 0.87 0.00 01-JAN-00:10 252.12 04-FEB-07:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 0.87 0.00 01-JAN-00:10 252.12 04-FEB-07:10
General:Pumps:Electricity 0.87 0.00 01-JAN-00:10 252.12 04-FEB-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 479.68 2971.73 01-JAN-00:10 97539.18 04-FEB-07:10
NaturalGas:Building 188.37 2971.73 01-JAN-00:10 9905.77 02-JAN-06:10
NaturalGas:Zone:FLOOR 1 OPERATING ROOM 1 61.20 965.39 01-JAN-00:10 3217.98 02-JAN-06:10
NaturalGas:SpaceType:GENERAL 188.37 2971.73 01-JAN-00:10 9905.77 02-JAN-06:10
InteriorEquipment:NaturalGas 188.37 2971.73 01-JAN-00:10 9905.77 02-JAN-06:10
InteriorEquipment:NaturalGas:Zone:FLOOR 1 OPERATING ROOM 1 61.20 965.39 01-JAN-00:10 3217.98 02-JAN-06:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 188.37 2971.73 01-JAN-00:10 9905.77 02-JAN-06:10
MiscPlug:InteriorEquipment:NaturalGas 188.37 2971.73 01-JAN-00:10 9905.77 02-JAN-06:10
MiscPlug:InteriorEquipment:NaturalGas:Zone:FLOOR 1 OPERATING ROOM 1 61.20 965.39 01-JAN-00:10 3217.98 02-JAN-06:10
MiscPlug:InteriorEquipment:NaturalGas:SpaceType:GENERAL 188.37 2971.73 01-JAN-00:10 9905.77 02-JAN-06:10
NaturalGas:Zone:FLOOR 1 OPERATING ROOM 2 63.86 1007.37 01-JAN-00:10 3357.89 02-JAN-06:10
InteriorEquipment:NaturalGas:Zone:FLOOR 1 OPERATING ROOM 2 63.86 1007.37 01-JAN-00:10 3357.89 02-JAN-06:10
MiscPlug:InteriorEquipment:NaturalGas:Zone:FLOOR 1 OPERATING ROOM 2 63.86 1007.37 01-JAN-00:10 3357.89 02-JAN-06:10
NaturalGas:Zone:FLOOR 1 OPERATING ROOM 3 63.32 998.97 01-JAN-00:10 3329.91 02-JAN-06:10
InteriorEquipment:NaturalGas:Zone:FLOOR 1 OPERATING ROOM 3 63.32 998.97 01-JAN-00:10 3329.91 02-JAN-06:10
MiscPlug:InteriorEquipment:NaturalGas:Zone:FLOOR 1 OPERATING ROOM 3 63.32 998.97 01-JAN-00:10 3329.91 02-JAN-06:10
NaturalGas:Plant 291.30 0.00 01-JAN-00:10 92586.30 04-FEB-07:10
Heating:NaturalGas 197.59 0.00 01-JAN-00:10 92586.30 04-FEB-07:10
Boiler:Heating:NaturalGas 197.59 0.00 01-JAN-00:10 92586.30 04-FEB-07:10
WaterSystems:NaturalGas 93.72 0.00 01-JAN-00:10 10458.43 17-JAN-13:40
Water Heater:WaterSystems:NaturalGas 93.72 0.00 01-JAN-00:10 10458.43 17-JAN-13:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 479.15 0.00 01-JAN-00:10 0.00 16-MAR-11:00
Water:HVAC 0.30 0.00 01-JAN-00:10 0.00 04-FEB-06:50
Humidifier:Water 0.30 0.00 01-JAN-00:10 0.00 04-FEB-06:50
General:Humidifier:Water 0.30 0.00 01-JAN-00:10 0.00 04-FEB-06:50
MainsWater:Facility 479.15 0.00 01-JAN-00:10 0.00 16-MAR-11:00
MainsWater:HVAC 0.30 0.00 01-JAN-00:10 0.00 04-FEB-06:50
Humidifier:MainsWater 0.30 0.00 01-JAN-00:10 0.00 04-FEB-06:50
General:Humidifier:MainsWater 0.30 0.00 01-JAN-00:10 0.00 04-FEB-06:50
Water:Plant 478.85 0.00 01-JAN-00:10 0.00 02-JAN-11:30
WaterSystems:Water 478.85 0.00 01-JAN-00:10 0.00 02-JAN-11:30
WaterUse:WaterSystems:Water 478.85 0.00 01-JAN-00:10 0.00 02-JAN-11:30
MainsWater:Plant 478.85 0.00 01-JAN-00:10 0.00 02-JAN-11:30
WaterSystems:MainsWater 478.85 0.00 01-JAN-00:10 0.00 02-JAN-11:30
WaterUse:WaterSystems:MainsWater 478.85 0.00 01-JAN-00:10 0.00 02-JAN-11:30
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 8528.64 9317.70 05-FEB-04:40 692602.36 28-JUL-15:00
EnergyTransfer:Building 2776.81 4181.64 05-FEB-04:40 205506.29 28-JUL-15:40
EnergyTransfer:Zone:FLOOR 1 ANESTHESIA 13.26 0.00 01-JAN-00:10 897.08 04-DEC-14:30
Heating:EnergyTransfer 1.76 0.00 01-JAN-00:10 35808.05 04-FEB-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 ANESTHESIA 0.01 0.00 01-JAN-00:10 154.44 04-FEB-06:20
General:Heating:EnergyTransfer 1.76 0.00 01-JAN-00:10 35808.05 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 ANESTHESIA 0.01 0.00 01-JAN-00:10 154.44 04-FEB-06:20
Cooling:EnergyTransfer 2775.05 4181.64 05-FEB-04:40 205506.29 28-JUL-15:40
Cooling:EnergyTransfer:Zone:FLOOR 1 ANESTHESIA 13.25 0.00 01-JAN-00:10 897.08 04-DEC-14:30
General:Cooling:EnergyTransfer 2775.05 4181.64 05-FEB-04:40 205506.29 28-JUL-15:40
General:Cooling:EnergyTransfer:Zone:FLOOR 1 ANESTHESIA 13.25 0.00 01-JAN-00:10 897.08 04-DEC-14:30
EnergyTransfer:Zone:FLOOR 1 BIO HAZ 1.43 0.00 01-JAN-00:10 106.63 28-JUL-16:20
Heating:EnergyTransfer:Zone:FLOOR 1 BIO HAZ 0.00 0.00 01-JAN-00:10 31.80 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 BIO HAZ 0.00 0.00 01-JAN-00:10 31.80 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 BIO HAZ 1.43 0.00 01-JAN-00:10 106.63 28-JUL-16:20
General:Cooling:EnergyTransfer:Zone:FLOOR 1 BIO HAZ 1.43 0.00 01-JAN-00:10 106.63 28-JUL-16:20
EnergyTransfer:Zone:FLOOR 1 CAFE 46.39 0.00 04-JAN-20:10 4837.02 04-DEC-14:30
Heating:EnergyTransfer:Zone:FLOOR 1 CAFE 0.03 0.00 01-JAN-00:10 531.62 10-JUN-14:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 CAFE 0.03 0.00 01-JAN-00:10 531.62 10-JUN-14:10
Cooling:EnergyTransfer:Zone:FLOOR 1 CAFE 46.36 0.00 04-JAN-20:10 4837.02 04-DEC-14:30
General:Cooling:EnergyTransfer:Zone:FLOOR 1 CAFE 46.36 0.00 04-JAN-20:10 4837.02 04-DEC-14:30
EnergyTransfer:Zone:FLOOR 1 CLEAN 12.99 0.00 01-JAN-00:10 900.01 06-FEB-06:10
Heating:EnergyTransfer:Zone:FLOOR 1 CLEAN 0.01 0.00 01-JAN-00:10 112.41 06-JUN-05:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 CLEAN 0.01 0.00 01-JAN-00:10 112.41 06-JUN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 CLEAN 12.98 0.00 01-JAN-00:10 900.01 06-FEB-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 CLEAN 12.98 0.00 01-JAN-00:10 900.01 06-FEB-06:10
EnergyTransfer:Zone:FLOOR 1 CLEAN WORK 15.16 0.00 01-JAN-00:10 1086.07 06-FEB-06:10
Heating:EnergyTransfer:Zone:FLOOR 1 CLEAN WORK 0.01 0.00 01-JAN-00:10 168.07 06-JUN-05:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 CLEAN WORK 0.01 0.00 01-JAN-00:10 168.07 06-JUN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 CLEAN WORK 15.14 0.00 01-JAN-00:10 1086.07 06-FEB-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 CLEAN WORK 15.14 0.00 01-JAN-00:10 1086.07 06-FEB-06:10
EnergyTransfer:Zone:FLOOR 1 DICTATION 4.20 0.00 01-JAN-00:10 400.70 25-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 DICTATION 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 DICTATION 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 DICTATION 4.20 0.00 01-JAN-00:10 400.70 25-JAN-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 DICTATION 4.20 0.00 01-JAN-00:10 400.70 25-JAN-07:10
EnergyTransfer:Zone:FLOOR 1 DRESSING ROOM 3.01 0.00 01-JAN-00:10 328.52 31-JUL-14:20
Heating:EnergyTransfer:Zone:FLOOR 1 DRESSING ROOM 0.00 0.00 01-JAN-00:10 104.47 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 DRESSING ROOM 0.00 0.00 01-JAN-00:10 104.47 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 DRESSING ROOM 3.01 0.00 01-JAN-00:10 328.52 31-JUL-14:20
General:Cooling:EnergyTransfer:Zone:FLOOR 1 DRESSING ROOM 3.01 0.00 01-JAN-00:10 328.52 31-JUL-14:20
EnergyTransfer:Zone:FLOOR 1 ELECTRICAL ROOM 8.80 0.00 01-JAN-00:10 714.54 25-JUL-11:20
Heating:EnergyTransfer:Zone:FLOOR 1 ELECTRICAL ROOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 ELECTRICAL ROOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 ELECTRICAL ROOM 8.80 0.00 01-JAN-00:10 714.54 25-JUL-11:20
General:Cooling:EnergyTransfer:Zone:FLOOR 1 ELECTRICAL ROOM 8.80 0.00 01-JAN-00:10 714.54 25-JUL-11:20
EnergyTransfer:Zone:FLOOR 1 ELEVATOR PUMP ROOM 11.63 0.00 22-JAN-02:40 996.98 28-JUL-15:30
Heating:EnergyTransfer:Zone:FLOOR 1 ELEVATOR PUMP ROOM 0.01 0.00 01-JAN-00:10 140.14 04-FEB-06:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 ELEVATOR PUMP ROOM 0.01 0.00 01-JAN-00:10 140.14 04-FEB-06:10
Cooling:EnergyTransfer:Zone:FLOOR 1 ELEVATOR PUMP ROOM 11.63 0.00 22-JAN-02:40 996.98 28-JUL-15:30
General:Cooling:EnergyTransfer:Zone:FLOOR 1 ELEVATOR PUMP ROOM 11.63 0.00 22-JAN-02:40 996.98 28-JUL-15:30
EnergyTransfer:Zone:FLOOR 1 HUMID 2.28 0.00 01-JAN-00:10 224.63 25-JAN-07:20
Heating:EnergyTransfer:Zone:FLOOR 1 HUMID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 HUMID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 HUMID 2.28 0.00 01-JAN-00:10 224.63 25-JAN-07:20
General:Cooling:EnergyTransfer:Zone:FLOOR 1 HUMID 2.28 0.00 01-JAN-00:10 224.63 25-JAN-07:20
EnergyTransfer:Zone:FLOOR 1 IT HALL 3.76 0.00 01-JAN-00:10 293.01 21-APR-06:10
Heating:EnergyTransfer:Zone:FLOOR 1 IT HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 IT HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 IT HALL 3.76 0.00 01-JAN-00:10 293.01 21-APR-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 IT HALL 3.76 0.00 01-JAN-00:10 293.01 21-APR-06:10
EnergyTransfer:Zone:FLOOR 1 IT ROOM 3.95 0.00 01-JAN-00:10 313.67 10-MAY-14:10
Heating:EnergyTransfer:Zone:FLOOR 1 IT ROOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 IT ROOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 IT ROOM 3.95 0.00 01-JAN-00:10 313.67 10-MAY-14:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 IT ROOM 3.95 0.00 01-JAN-00:10 313.67 10-MAY-14:10
EnergyTransfer:Zone:FLOOR 1 LOBBY 38.90 0.00 01-JAN-00:10 3796.44 28-JUL-15:30
Heating:EnergyTransfer:Zone:FLOOR 1 LOBBY 0.00 0.00 01-JAN-00:10 25.08 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 LOBBY 0.00 0.00 01-JAN-00:10 25.08 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 LOBBY 38.90 0.00 01-JAN-00:10 3796.44 28-JUL-15:30
General:Cooling:EnergyTransfer:Zone:FLOOR 1 LOBBY 38.90 0.00 01-JAN-00:10 3796.44 28-JUL-15:30
EnergyTransfer:Zone:FLOOR 1 LOBBY HALL 10.61 0.00 01-JAN-00:10 891.30 21-FEB-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 LOBBY HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 LOBBY HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 LOBBY HALL 10.61 0.00 01-JAN-00:10 891.30 21-FEB-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 LOBBY HALL 10.61 0.00 01-JAN-00:10 891.30 21-FEB-07:10
EnergyTransfer:Zone:FLOOR 1 LOBBY TOILET 5.63 0.00 01-JAN-00:10 362.64 02-MAY-19:40
Heating:EnergyTransfer:Zone:FLOOR 1 LOBBY TOILET 0.00 0.00 01-JAN-00:10 76.34 04-FEB-06:20
General:Heating:EnergyTransfer:Zone:FLOOR 1 LOBBY TOILET 0.00 0.00 01-JAN-00:10 76.34 04-FEB-06:20
Cooling:EnergyTransfer:Zone:FLOOR 1 LOBBY TOILET 5.63 0.00 01-JAN-00:10 362.64 02-MAY-19:40
General:Cooling:EnergyTransfer:Zone:FLOOR 1 LOBBY TOILET 5.63 0.00 01-JAN-00:10 362.64 02-MAY-19:40
EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM 44.35 0.00 01-JAN-00:10 3323.73 27-JUL-16:20
Heating:EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM 44.35 0.00 01-JAN-00:10 3323.73 27-JUL-16:20
General:Cooling:EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM 44.35 0.00 01-JAN-00:10 3323.73 27-JUL-16:20
EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM HALL 13.71 0.00 01-JAN-00:10 1210.05 22-DEC-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM HALL 13.71 0.00 01-JAN-00:10 1210.05 22-DEC-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM HALL 13.71 0.00 01-JAN-00:10 1210.05 22-DEC-07:10
EnergyTransfer:Zone:FLOOR 1 LOUNGE 23.04 0.00 01-JAN-00:10 1787.89 21-APR-06:10
Heating:EnergyTransfer:Zone:FLOOR 1 LOUNGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 LOUNGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 LOUNGE 23.04 0.00 01-JAN-00:10 1787.89 21-APR-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 LOUNGE 23.04 0.00 01-JAN-00:10 1787.89 21-APR-06:10
EnergyTransfer:Zone:FLOOR 1 MED GAS 3.23 0.00 01-JAN-00:10 413.81 25-JUL-11:30
Heating:EnergyTransfer:Zone:FLOOR 1 MED GAS 0.03 0.00 01-JAN-00:10 296.47 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 MED GAS 0.03 0.00 01-JAN-00:10 296.47 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 MED GAS 3.20 0.00 01-JAN-00:10 413.81 25-JUL-11:30
General:Cooling:EnergyTransfer:Zone:FLOOR 1 MED GAS 3.20 0.00 01-JAN-00:10 413.81 25-JUL-11:30
EnergyTransfer:Zone:FLOOR 1 MRI CONTROL ROOM 32.34 108.06 05-FEB-07:00 2124.77 28-JUL-15:10
Heating:EnergyTransfer:Zone:FLOOR 1 MRI CONTROL ROOM 0.01 0.00 01-JAN-00:10 84.16 08-JUL-14:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 MRI CONTROL ROOM 0.01 0.00 01-JAN-00:10 84.16 08-JUL-14:10
Cooling:EnergyTransfer:Zone:FLOOR 1 MRI CONTROL ROOM 32.33 108.06 05-FEB-07:00 2124.77 28-JUL-15:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 MRI CONTROL ROOM 32.33 108.06 05-FEB-07:00 2124.77 28-JUL-15:10
EnergyTransfer:Zone:FLOOR 1 MRI HALL 5.68 0.00 01-JAN-00:10 425.59 15-NOV-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 MRI HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 MRI HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 MRI HALL 5.68 0.00 01-JAN-00:10 425.59 15-NOV-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 MRI HALL 5.68 0.00 01-JAN-00:10 425.59 15-NOV-07:10
EnergyTransfer:Zone:FLOOR 1 MRI ROOM 82.79 793.91 05-FEB-08:00 5076.13 29-MAR-06:10
Heating:EnergyTransfer:Zone:FLOOR 1 MRI ROOM 0.02 0.00 01-JAN-00:10 288.51 29-JUL-14:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 MRI ROOM 0.02 0.00 01-JAN-00:10 288.51 29-JUL-14:10
Cooling:EnergyTransfer:Zone:FLOOR 1 MRI ROOM 82.77 793.91 05-FEB-08:00 5076.13 29-MAR-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 MRI ROOM 82.77 793.91 05-FEB-08:00 5076.13 29-MAR-06:10
EnergyTransfer:Zone:FLOOR 1 MRI TOILET 4.28 0.00 01-JAN-00:10 298.20 19-NOV-06:20
Heating:EnergyTransfer:Zone:FLOOR 1 MRI TOILET 0.01 0.00 01-JAN-00:10 75.38 04-FEB-06:20
General:Heating:EnergyTransfer:Zone:FLOOR 1 MRI TOILET 0.01 0.00 01-JAN-00:10 75.38 04-FEB-06:20
Cooling:EnergyTransfer:Zone:FLOOR 1 MRI TOILET 4.27 0.00 01-JAN-00:10 298.20 19-NOV-06:20
General:Cooling:EnergyTransfer:Zone:FLOOR 1 MRI TOILET 4.27 0.00 01-JAN-00:10 298.20 19-NOV-06:20
EnergyTransfer:Zone:FLOOR 1 NOURISHMENT 9.80 0.00 01-JAN-00:10 856.27 25-JAN-07:20
Heating:EnergyTransfer:Zone:FLOOR 1 NOURISHMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 NOURISHMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 NOURISHMENT 9.80 0.00 01-JAN-00:10 856.27 25-JAN-07:20
General:Cooling:EnergyTransfer:Zone:FLOOR 1 NOURISHMENT 9.80 0.00 01-JAN-00:10 856.27 25-JAN-07:20
EnergyTransfer:Zone:FLOOR 1 NURSE HALL 12.74 0.00 01-JAN-00:10 1101.45 14-DEC-14:50
Heating:EnergyTransfer:Zone:FLOOR 1 NURSE HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 NURSE HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 NURSE HALL 12.74 0.00 01-JAN-00:10 1101.45 14-DEC-14:50
General:Cooling:EnergyTransfer:Zone:FLOOR 1 NURSE HALL 12.74 0.00 01-JAN-00:10 1101.45 14-DEC-14:50
EnergyTransfer:Zone:FLOOR 1 NURSE JANITOR 1.72 0.00 01-JAN-00:10 172.28 25-JAN-07:20
Heating:EnergyTransfer:Zone:FLOOR 1 NURSE JANITOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 NURSE JANITOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 NURSE JANITOR 1.72 0.00 01-JAN-00:10 172.28 25-JAN-07:20
General:Cooling:EnergyTransfer:Zone:FLOOR 1 NURSE JANITOR 1.72 0.00 01-JAN-00:10 172.28 25-JAN-07:20
EnergyTransfer:Zone:FLOOR 1 NURSE STATION 12.86 0.00 01-JAN-00:10 1111.14 27-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 NURSE STATION 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 NURSE STATION 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 NURSE STATION 12.86 0.00 01-JAN-00:10 1111.14 27-JAN-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 NURSE STATION 12.86 0.00 01-JAN-00:10 1111.14 27-JAN-07:10
EnergyTransfer:Zone:FLOOR 1 NURSE TOILET 3.21 0.00 01-JAN-00:10 291.05 22-DEC-04:20
Heating:EnergyTransfer:Zone:FLOOR 1 NURSE TOILET 0.01 0.00 01-JAN-00:10 67.00 05-SEP-05:20
General:Heating:EnergyTransfer:Zone:FLOOR 1 NURSE TOILET 0.01 0.00 01-JAN-00:10 67.00 05-SEP-05:20
Cooling:EnergyTransfer:Zone:FLOOR 1 NURSE TOILET 3.20 0.00 01-JAN-00:10 291.05 22-DEC-04:20
General:Cooling:EnergyTransfer:Zone:FLOOR 1 NURSE TOILET 3.20 0.00 01-JAN-00:10 291.05 22-DEC-04:20
EnergyTransfer:Zone:FLOOR 1 OFFICE 17.12 0.00 01-JAN-00:10 1479.77 03-MAR-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 OFFICE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 OFFICE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 OFFICE 17.12 0.00 01-JAN-00:10 1479.77 03-MAR-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 OFFICE 17.12 0.00 01-JAN-00:10 1479.77 03-MAR-07:10
EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 1 109.72 92.59 17-DEC-17:10 7564.26 20-OCT-10:30
Heating:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 1 0.05 0.00 01-JAN-00:10 603.38 29-JUL-16:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 1 0.05 0.00 01-JAN-00:10 603.38 29-JUL-16:10
Cooling:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 1 109.68 92.59 17-DEC-17:10 7564.26 20-OCT-10:30
General:Cooling:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 1 109.68 92.59 17-DEC-17:10 7564.26 20-OCT-10:30
EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 2 109.68 40.14 05-FEB-17:10 7484.85 18-MAY-09:20
Heating:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 2 0.05 0.00 01-JAN-00:10 638.95 29-JUL-16:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 2 0.05 0.00 01-JAN-00:10 638.95 29-JUL-16:10
Cooling:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 2 109.63 40.14 05-FEB-17:10 7484.85 18-MAY-09:20
General:Cooling:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 2 109.63 40.14 05-FEB-17:10 7484.85 18-MAY-09:20
EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 3 98.65 18.60 01-JAN-17:10 6105.18 14-JUL-13:00
Heating:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 3 0.06 0.00 01-JAN-00:10 657.71 29-JUL-16:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 3 0.06 0.00 01-JAN-00:10 657.71 29-JUL-16:10
Cooling:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 3 98.59 18.60 01-JAN-17:10 6105.18 14-JUL-13:00
General:Cooling:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 3 98.59 18.60 01-JAN-17:10 6105.18 14-JUL-13:00
EnergyTransfer:Zone:FLOOR 1 PACU 11.37 0.00 01-JAN-00:10 780.15 06-FEB-06:10
Heating:EnergyTransfer:Zone:FLOOR 1 PACU 0.01 0.00 01-JAN-00:10 100.88 06-JUN-05:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 PACU 0.01 0.00 01-JAN-00:10 100.88 06-JUN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 PACU 11.36 0.00 01-JAN-00:10 780.15 06-FEB-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 PACU 11.36 0.00 01-JAN-00:10 780.15 06-FEB-06:10
EnergyTransfer:Zone:FLOOR 1 PRE-OP HALL 14.37 0.00 01-JAN-00:10 1178.34 03-MAR-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 PRE-OP HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 PRE-OP HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 PRE-OP HALL 14.37 0.00 01-JAN-00:10 1178.34 03-MAR-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 PRE-OP HALL 14.37 0.00 01-JAN-00:10 1178.34 03-MAR-07:10
EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 1 16.39 0.00 01-JAN-00:10 1092.81 27-NOV-06:10
Heating:EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 1 0.02 0.00 01-JAN-00:10 196.93 06-JUN-05:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 1 0.02 0.00 01-JAN-00:10 196.93 06-JUN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 1 16.38 0.00 01-JAN-00:10 1092.81 27-NOV-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 1 16.38 0.00 01-JAN-00:10 1092.81 27-NOV-06:10
EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 2 27.86 0.00 01-JAN-00:10 2015.73 06-FEB-06:10
Heating:EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 2 0.03 0.00 01-JAN-00:10 361.10 06-JUN-05:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 2 0.03 0.00 01-JAN-00:10 361.10 06-JUN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 2 27.82 0.00 01-JAN-00:10 2015.73 06-FEB-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 2 27.82 0.00 01-JAN-00:10 2015.73 06-FEB-06:10
EnergyTransfer:Zone:FLOOR 1 PRE-OP TOILET 4.51 0.00 01-JAN-00:10 317.42 28-JUL-17:00
Heating:EnergyTransfer:Zone:FLOOR 1 PRE-OP TOILET 0.01 0.00 01-JAN-00:10 83.50 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 PRE-OP TOILET 0.01 0.00 01-JAN-00:10 83.50 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 PRE-OP TOILET 4.50 0.00 01-JAN-00:10 317.42 28-JUL-17:00
General:Cooling:EnergyTransfer:Zone:FLOOR 1 PRE-OP TOILET 4.50 0.00 01-JAN-00:10 317.42 28-JUL-17:00
EnergyTransfer:Zone:FLOOR 1 PROCEDURE ROOM 34.64 0.00 01-JAN-00:10 2735.55 27-JUL-17:10
Heating:EnergyTransfer:Zone:FLOOR 1 PROCEDURE ROOM 0.04 0.00 01-JAN-00:10 342.94 04-FEB-06:20
General:Heating:EnergyTransfer:Zone:FLOOR 1 PROCEDURE ROOM 0.04 0.00 01-JAN-00:10 342.94 04-FEB-06:20
Cooling:EnergyTransfer:Zone:FLOOR 1 PROCEDURE ROOM 34.60 0.00 01-JAN-00:10 2735.55 27-JUL-17:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 PROCEDURE ROOM 34.60 0.00 01-JAN-00:10 2735.55 27-JUL-17:10
EnergyTransfer:Zone:FLOOR 1 RECEPTION 34.92 0.00 01-JAN-00:10 2943.84 04-DEC-14:30
Heating:EnergyTransfer:Zone:FLOOR 1 RECEPTION 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 RECEPTION 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 RECEPTION 34.92 0.00 01-JAN-00:10 2943.84 04-DEC-14:30
General:Cooling:EnergyTransfer:Zone:FLOOR 1 RECEPTION 34.92 0.00 01-JAN-00:10 2943.84 04-DEC-14:30
EnergyTransfer:Zone:FLOOR 1 RECEPTION HALL 3.98 0.00 01-JAN-00:10 338.72 24-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 RECEPTION HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 RECEPTION HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 RECEPTION HALL 3.98 0.00 01-JAN-00:10 338.72 24-JAN-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 RECEPTION HALL 3.98 0.00 01-JAN-00:10 338.72 24-JAN-07:10
EnergyTransfer:Zone:FLOOR 1 RECOVERY ROOM 63.19 0.00 01-JAN-00:10 4568.40 04-DEC-14:20
Heating:EnergyTransfer:Zone:FLOOR 1 RECOVERY ROOM 0.03 0.00 01-JAN-00:10 787.09 04-FEB-06:20
General:Heating:EnergyTransfer:Zone:FLOOR 1 RECOVERY ROOM 0.03 0.00 01-JAN-00:10 787.09 04-FEB-06:20
Cooling:EnergyTransfer:Zone:FLOOR 1 RECOVERY ROOM 63.16 0.00 01-JAN-00:10 4568.40 04-DEC-14:20
General:Cooling:EnergyTransfer:Zone:FLOOR 1 RECOVERY ROOM 63.16 0.00 01-JAN-00:10 4568.40 04-DEC-14:20
EnergyTransfer:Zone:FLOOR 1 SCHEDULING 4.99 0.00 01-JAN-00:10 520.16 04-DEC-15:30
Heating:EnergyTransfer:Zone:FLOOR 1 SCHEDULING 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 SCHEDULING 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 SCHEDULING 4.99 0.00 01-JAN-00:10 520.16 04-DEC-15:30
General:Cooling:EnergyTransfer:Zone:FLOOR 1 SCHEDULING 4.99 0.00 01-JAN-00:10 520.16 04-DEC-15:30
EnergyTransfer:Zone:FLOOR 1 SCRUB 2.69 0.00 01-JAN-00:10 208.88 23-AUG-11:20
Heating:EnergyTransfer:Zone:FLOOR 1 SCRUB 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 SCRUB 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 SCRUB 2.69 0.00 01-JAN-00:10 208.88 23-AUG-11:20
General:Cooling:EnergyTransfer:Zone:FLOOR 1 SCRUB 2.69 0.00 01-JAN-00:10 208.88 23-AUG-11:20
EnergyTransfer:Zone:FLOOR 1 SOIL 11.95 0.00 01-JAN-00:10 869.33 06-FEB-06:10
Heating:EnergyTransfer:Zone:FLOOR 1 SOIL 0.01 0.00 01-JAN-00:10 126.45 06-JUN-05:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 SOIL 0.01 0.00 01-JAN-00:10 126.45 06-JUN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 SOIL 11.94 0.00 01-JAN-00:10 869.33 06-FEB-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 SOIL 11.94 0.00 01-JAN-00:10 869.33 06-FEB-06:10
EnergyTransfer:Zone:FLOOR 1 SOIL HOLD 5.93 0.00 01-JAN-00:10 377.18 07-MAY-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 SOIL HOLD 0.00 0.00 01-JAN-00:10 65.42 04-FEB-06:20
General:Heating:EnergyTransfer:Zone:FLOOR 1 SOIL HOLD 0.00 0.00 01-JAN-00:10 65.42 04-FEB-06:20
Cooling:EnergyTransfer:Zone:FLOOR 1 SOIL HOLD 5.92 0.00 01-JAN-00:10 377.18 07-MAY-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 SOIL HOLD 5.92 0.00 01-JAN-00:10 377.18 07-MAY-07:10
EnergyTransfer:Zone:FLOOR 1 SOIL WORK 15.59 0.00 01-JAN-00:10 1139.35 27-JAN-04:30
Heating:EnergyTransfer:Zone:FLOOR 1 SOIL WORK 0.02 0.00 01-JAN-00:10 193.11 06-JUN-05:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 SOIL WORK 0.02 0.00 01-JAN-00:10 193.11 06-JUN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 SOIL WORK 15.58 0.00 01-JAN-00:10 1139.35 27-JAN-04:30
General:Cooling:EnergyTransfer:Zone:FLOOR 1 SOIL WORK 15.58 0.00 01-JAN-00:10 1139.35 27-JAN-04:30
EnergyTransfer:Zone:FLOOR 1 STEP DOWN 35.93 0.00 01-JAN-00:10 2755.84 07-NOV-15:00
Heating:EnergyTransfer:Zone:FLOOR 1 STEP DOWN 0.01 0.00 01-JAN-00:10 465.19 04-FEB-06:20
General:Heating:EnergyTransfer:Zone:FLOOR 1 STEP DOWN 0.01 0.00 01-JAN-00:10 465.19 04-FEB-06:20
Cooling:EnergyTransfer:Zone:FLOOR 1 STEP DOWN 35.92 0.00 01-JAN-00:10 2755.84 07-NOV-15:00
General:Cooling:EnergyTransfer:Zone:FLOOR 1 STEP DOWN 35.92 0.00 01-JAN-00:10 2755.84 07-NOV-15:00
EnergyTransfer:Zone:FLOOR 1 STERILE HALL 17.43 0.00 01-JAN-00:10 1420.63 10-NOV-13:40
Heating:EnergyTransfer:Zone:FLOOR 1 STERILE HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 STERILE HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 STERILE HALL 17.43 0.00 01-JAN-00:10 1420.63 10-NOV-13:40
General:Cooling:EnergyTransfer:Zone:FLOOR 1 STERILE HALL 17.43 0.00 01-JAN-00:10 1420.63 10-NOV-13:40
EnergyTransfer:Zone:FLOOR 1 STERILE STORAGE 8.86 0.00 01-JAN-00:10 826.50 27-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 STERILE STORAGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 STERILE STORAGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 STERILE STORAGE 8.86 0.00 01-JAN-00:10 826.50 27-JAN-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 STERILE STORAGE 8.86 0.00 01-JAN-00:10 826.50 27-JAN-07:10
EnergyTransfer:Zone:FLOOR 1 STORAGE 29.12 0.00 01-JAN-00:10 3791.70 28-JUL-15:30
Heating:EnergyTransfer:Zone:FLOOR 1 STORAGE 0.07 0.00 01-JAN-00:10 1958.50 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 STORAGE 0.07 0.00 01-JAN-00:10 1958.50 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 STORAGE 29.05 0.00 01-JAN-00:10 3791.70 28-JUL-15:30
General:Cooling:EnergyTransfer:Zone:FLOOR 1 STORAGE 29.05 0.00 01-JAN-00:10 3791.70 28-JUL-15:30
EnergyTransfer:Zone:FLOOR 1 SUB-STERILE 9.12 0.00 01-JAN-00:10 1028.01 25-JUL-09:40
Heating:EnergyTransfer:Zone:FLOOR 1 SUB-STERILE 0.00 0.00 01-JAN-00:10 267.61 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 SUB-STERILE 0.00 0.00 01-JAN-00:10 267.61 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 SUB-STERILE 9.12 0.00 01-JAN-00:10 1028.01 25-JUL-09:40
General:Cooling:EnergyTransfer:Zone:FLOOR 1 SUB-STERILE 9.12 0.00 01-JAN-00:10 1028.01 25-JUL-09:40
EnergyTransfer:Zone:FLOOR 1 UTILITY HALL 13.37 0.00 01-JAN-00:10 1851.90 25-JUL-09:30
Heating:EnergyTransfer:Zone:FLOOR 1 UTILITY HALL 0.01 0.00 01-JAN-00:10 556.29 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 UTILITY HALL 0.01 0.00 01-JAN-00:10 556.29 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 UTILITY HALL 13.36 0.00 01-JAN-00:10 1851.90 25-JUL-09:30
General:Cooling:EnergyTransfer:Zone:FLOOR 1 UTILITY HALL 13.36 0.00 01-JAN-00:10 1851.90 25-JUL-09:30
EnergyTransfer:Zone:FLOOR 1 UTILITY JANITOR 1.38 0.00 01-JAN-00:10 104.05 28-JUL-06:10
Heating:EnergyTransfer:Zone:FLOOR 1 UTILITY JANITOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 UTILITY JANITOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 UTILITY JANITOR 1.38 0.00 01-JAN-00:10 104.05 28-JUL-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 1 UTILITY JANITOR 1.38 0.00 01-JAN-00:10 104.05 28-JUL-06:10
EnergyTransfer:Zone:FLOOR 1 UTILITY ROOM 12.49 0.00 01-JAN-00:10 1310.84 25-JUL-09:40
Heating:EnergyTransfer:Zone:FLOOR 1 UTILITY ROOM 0.00 0.00 01-JAN-00:10 492.43 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 1 UTILITY ROOM 0.00 0.00 01-JAN-00:10 492.43 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 UTILITY ROOM 12.49 0.00 01-JAN-00:10 1310.84 25-JUL-09:40
General:Cooling:EnergyTransfer:Zone:FLOOR 1 UTILITY ROOM 12.49 0.00 01-JAN-00:10 1310.84 25-JUL-09:40
EnergyTransfer:Zone:FLOOR 1 VESTIBULE 8.86 0.00 01-JAN-00:10 1174.40 28-JUL-15:40
Heating:EnergyTransfer:Zone:FLOOR 1 VESTIBULE 0.37 0.00 01-JAN-00:10 534.11 16-MAR-07:00
General:Heating:EnergyTransfer:Zone:FLOOR 1 VESTIBULE 0.37 0.00 01-JAN-00:10 534.11 16-MAR-07:00
Cooling:EnergyTransfer:Zone:FLOOR 1 VESTIBULE 8.49 0.00 01-JAN-00:10 1174.40 28-JUL-15:40
General:Cooling:EnergyTransfer:Zone:FLOOR 1 VESTIBULE 8.49 0.00 01-JAN-00:10 1174.40 28-JUL-15:40
EnergyTransfer:Zone:FLOOR 2 CONFERENCE 28.05 0.00 01-JAN-00:10 3058.80 07-NOV-13:40
Heating:EnergyTransfer:Zone:FLOOR 2 CONFERENCE 0.00 0.00 01-JAN-00:10 638.41 04-FEB-06:20
General:Heating:EnergyTransfer:Zone:FLOOR 2 CONFERENCE 0.00 0.00 01-JAN-00:10 638.41 04-FEB-06:20
Cooling:EnergyTransfer:Zone:FLOOR 2 CONFERENCE 28.05 0.00 01-JAN-00:10 3058.80 07-NOV-13:40
General:Cooling:EnergyTransfer:Zone:FLOOR 2 CONFERENCE 28.05 0.00 01-JAN-00:10 3058.80 07-NOV-13:40
EnergyTransfer:Zone:FLOOR 2 CONFERENCE TOILET 3.64 0.00 01-JAN-00:10 235.69 07-NOV-14:10
Heating:EnergyTransfer:Zone:FLOOR 2 CONFERENCE TOILET 0.00 0.00 01-JAN-00:10 57.14 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 CONFERENCE TOILET 0.00 0.00 01-JAN-00:10 57.14 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 CONFERENCE TOILET 3.64 0.00 01-JAN-00:10 235.69 07-NOV-14:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 CONFERENCE TOILET 3.64 0.00 01-JAN-00:10 235.69 07-NOV-14:10
EnergyTransfer:Zone:FLOOR 2 DICTATION 2.41 0.00 01-JAN-00:10 248.63 27-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 2 DICTATION 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 DICTATION 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 DICTATION 2.41 0.00 01-JAN-00:10 248.63 27-JAN-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 DICTATION 2.41 0.00 01-JAN-00:10 248.63 27-JAN-07:10
EnergyTransfer:Zone:FLOOR 2 EXAM 1 26.87 0.00 01-JAN-00:10 2832.01 06-OCT-16:30
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 1 0.00 0.00 01-JAN-00:10 661.02 04-FEB-06:20
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 1 0.00 0.00 01-JAN-00:10 661.02 04-FEB-06:20
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 1 26.87 0.00 01-JAN-00:10 2832.01 06-OCT-16:30
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 1 26.87 0.00 01-JAN-00:10 2832.01 06-OCT-16:30
EnergyTransfer:Zone:FLOOR 2 EXAM 2 37.19 0.00 01-JAN-00:10 2801.96 07-NOV-14:10
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 2 0.00 0.00 01-JAN-00:10 446.73 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 2 0.00 0.00 01-JAN-00:10 446.73 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 2 37.19 0.00 01-JAN-00:10 2801.96 07-NOV-14:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 2 37.19 0.00 01-JAN-00:10 2801.96 07-NOV-14:10
EnergyTransfer:Zone:FLOOR 2 EXAM 3 47.85 0.00 01-JAN-00:10 3739.61 14-DEC-14:10
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 3 0.01 0.00 01-JAN-00:10 623.29 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 3 0.01 0.00 01-JAN-00:10 623.29 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 3 47.84 0.00 01-JAN-00:10 3739.61 14-DEC-14:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 3 47.84 0.00 01-JAN-00:10 3739.61 14-DEC-14:10
EnergyTransfer:Zone:FLOOR 2 EXAM 4 6.58 0.00 01-JAN-00:10 638.19 07-NOV-13:40
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 4 0.00 0.00 01-JAN-00:10 147.96 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 4 0.00 0.00 01-JAN-00:10 147.96 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 4 6.58 0.00 01-JAN-00:10 638.19 07-NOV-13:40
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 4 6.58 0.00 01-JAN-00:10 638.19 07-NOV-13:40
EnergyTransfer:Zone:FLOOR 2 EXAM 5 28.95 0.00 01-JAN-00:10 2633.55 25-JUL-09:30
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 5 0.01 0.00 01-JAN-00:10 657.50 04-FEB-06:20
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 5 0.01 0.00 01-JAN-00:10 657.50 04-FEB-06:20
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 5 28.94 0.00 01-JAN-00:10 2633.55 25-JUL-09:30
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 5 28.94 0.00 01-JAN-00:10 2633.55 25-JUL-09:30
EnergyTransfer:Zone:FLOOR 2 EXAM 6 16.29 0.00 01-JAN-00:10 1229.71 27-JUL-16:40
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 6 0.00 0.00 01-JAN-00:10 360.04 04-FEB-06:20
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 6 0.00 0.00 01-JAN-00:10 360.04 04-FEB-06:20
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 6 16.29 0.00 01-JAN-00:10 1229.71 27-JUL-16:40
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 6 16.29 0.00 01-JAN-00:10 1229.71 27-JUL-16:40
EnergyTransfer:Zone:FLOOR 2 EXAM 7 51.70 0.00 01-JAN-00:10 3701.13 27-JUL-16:30
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 7 0.01 0.00 01-JAN-00:10 653.30 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 7 0.01 0.00 01-JAN-00:10 653.30 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 7 51.70 0.00 01-JAN-00:10 3701.13 27-JUL-16:30
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 7 51.70 0.00 01-JAN-00:10 3701.13 27-JUL-16:30
EnergyTransfer:Zone:FLOOR 2 EXAM 8 20.03 0.00 01-JAN-00:10 1485.31 27-JUL-16:30
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 8 0.00 0.00 01-JAN-00:10 332.70 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 8 0.00 0.00 01-JAN-00:10 332.70 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 8 20.03 0.00 01-JAN-00:10 1485.31 27-JUL-16:30
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 8 20.03 0.00 01-JAN-00:10 1485.31 27-JUL-16:30
EnergyTransfer:Zone:FLOOR 2 EXAM 9 27.92 0.00 01-JAN-00:10 1990.41 27-JUL-16:20
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 9 0.00 0.00 01-JAN-00:10 316.58 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 9 0.00 0.00 01-JAN-00:10 316.58 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 9 27.92 0.00 01-JAN-00:10 1990.41 27-JUL-16:20
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 9 27.92 0.00 01-JAN-00:10 1990.41 27-JUL-16:20
EnergyTransfer:Zone:FLOOR 2 EXAM HALL 1 6.40 0.00 01-JAN-00:10 640.10 07-NOV-16:30
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 1 0.00 0.00 01-JAN-00:10 37.92 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 1 0.00 0.00 01-JAN-00:10 37.92 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 1 6.40 0.00 01-JAN-00:10 640.10 07-NOV-16:30
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 1 6.40 0.00 01-JAN-00:10 640.10 07-NOV-16:30
EnergyTransfer:Zone:FLOOR 2 EXAM HALL 2 5.83 0.00 01-JAN-00:10 568.67 14-DEC-15:20
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 2 5.83 0.00 01-JAN-00:10 568.67 14-DEC-15:20
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 2 5.83 0.00 01-JAN-00:10 568.67 14-DEC-15:20
EnergyTransfer:Zone:FLOOR 2 EXAM HALL 3 5.33 0.00 01-JAN-00:10 547.28 14-DEC-15:20
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 3 5.33 0.00 01-JAN-00:10 547.28 14-DEC-15:20
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 3 5.33 0.00 01-JAN-00:10 547.28 14-DEC-15:20
EnergyTransfer:Zone:FLOOR 2 EXAM HALL 4 6.03 0.00 01-JAN-00:10 527.36 07-APR-06:10
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 4 6.03 0.00 01-JAN-00:10 527.36 07-APR-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 4 6.03 0.00 01-JAN-00:10 527.36 07-APR-06:10
EnergyTransfer:Zone:FLOOR 2 EXAM HALL 5 6.57 0.00 01-JAN-00:10 580.14 07-APR-06:10
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 5 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 5 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 5 6.57 0.00 01-JAN-00:10 580.14 07-APR-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 5 6.57 0.00 01-JAN-00:10 580.14 07-APR-06:10
EnergyTransfer:Zone:FLOOR 2 EXAM HALL 6 6.24 0.00 01-JAN-00:10 547.40 02-FEB-07:10
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 6 6.24 0.00 01-JAN-00:10 547.40 02-FEB-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 6 6.24 0.00 01-JAN-00:10 547.40 02-FEB-07:10
EnergyTransfer:Zone:FLOOR 2 JANITOR 2.60 0.00 01-JAN-00:10 324.76 28-JUL-17:00
Heating:EnergyTransfer:Zone:FLOOR 2 JANITOR 0.00 0.00 01-JAN-00:10 146.76 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 JANITOR 0.00 0.00 01-JAN-00:10 146.76 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 JANITOR 2.60 0.00 01-JAN-00:10 324.76 28-JUL-17:00
General:Cooling:EnergyTransfer:Zone:FLOOR 2 JANITOR 2.60 0.00 01-JAN-00:10 324.76 28-JUL-17:00
EnergyTransfer:Zone:FLOOR 2 LOUNGE 4.70 0.00 01-JAN-00:10 413.62 02-MAR-07:10
Heating:EnergyTransfer:Zone:FLOOR 2 LOUNGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 LOUNGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 LOUNGE 4.70 0.00 01-JAN-00:10 413.62 02-MAR-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 LOUNGE 4.70 0.00 01-JAN-00:10 413.62 02-MAR-07:10
EnergyTransfer:Zone:FLOOR 2 NURSE STATION 1 7.79 0.00 01-JAN-00:10 672.42 27-APR-06:10
Heating:EnergyTransfer:Zone:FLOOR 2 NURSE STATION 1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 NURSE STATION 1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 NURSE STATION 1 7.79 0.00 01-JAN-00:10 672.42 27-APR-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 NURSE STATION 1 7.79 0.00 01-JAN-00:10 672.42 27-APR-06:10
EnergyTransfer:Zone:FLOOR 2 NURSE STATION 2 9.67 0.00 01-JAN-00:10 834.17 09-MAR-07:10
Heating:EnergyTransfer:Zone:FLOOR 2 NURSE STATION 2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 NURSE STATION 2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 NURSE STATION 2 9.67 0.00 01-JAN-00:10 834.17 09-MAR-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 NURSE STATION 2 9.67 0.00 01-JAN-00:10 834.17 09-MAR-07:10
EnergyTransfer:Zone:FLOOR 2 OFFICE 29.21 0.00 01-JAN-00:10 3467.87 25-JUL-09:30
Heating:EnergyTransfer:Zone:FLOOR 2 OFFICE 0.00 0.00 01-JAN-00:10 817.58 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 OFFICE 0.00 0.00 01-JAN-00:10 817.58 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 OFFICE 29.21 0.00 01-JAN-00:10 3467.87 25-JUL-09:30
General:Cooling:EnergyTransfer:Zone:FLOOR 2 OFFICE 29.21 0.00 01-JAN-00:10 3467.87 25-JUL-09:30
EnergyTransfer:Zone:FLOOR 2 OFFICE HALL 14.07 0.00 01-JAN-00:10 1206.35 07-JUL-06:10
Heating:EnergyTransfer:Zone:FLOOR 2 OFFICE HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 OFFICE HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 OFFICE HALL 14.07 0.00 01-JAN-00:10 1206.35 07-JUL-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 OFFICE HALL 14.07 0.00 01-JAN-00:10 1206.35 07-JUL-06:10
EnergyTransfer:Zone:FLOOR 2 RECEPTION 67.03 0.00 01-JAN-00:10 6433.14 07-NOV-15:00
Heating:EnergyTransfer:Zone:FLOOR 2 RECEPTION 0.00 0.00 01-JAN-00:10 849.32 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 RECEPTION 0.00 0.00 01-JAN-00:10 849.32 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 RECEPTION 67.03 0.00 01-JAN-00:10 6433.14 07-NOV-15:00
General:Cooling:EnergyTransfer:Zone:FLOOR 2 RECEPTION 67.03 0.00 01-JAN-00:10 6433.14 07-NOV-15:00
EnergyTransfer:Zone:FLOOR 2 RECEPTION HALL 19.62 0.00 01-JAN-00:10 1797.18 23-FEB-07:10
Heating:EnergyTransfer:Zone:FLOOR 2 RECEPTION HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 RECEPTION HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 RECEPTION HALL 19.62 0.00 01-JAN-00:10 1797.18 23-FEB-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 RECEPTION HALL 19.62 0.00 01-JAN-00:10 1797.18 23-FEB-07:10
EnergyTransfer:Zone:FLOOR 2 RECEPTION TOILET 7.15 0.00 01-JAN-00:10 457.89 07-NOV-09:00
Heating:EnergyTransfer:Zone:FLOOR 2 RECEPTION TOILET 0.00 0.00 01-JAN-00:10 86.27 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 RECEPTION TOILET 0.00 0.00 01-JAN-00:10 86.27 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 RECEPTION TOILET 7.15 0.00 01-JAN-00:10 457.89 07-NOV-09:00
General:Cooling:EnergyTransfer:Zone:FLOOR 2 RECEPTION TOILET 7.15 0.00 01-JAN-00:10 457.89 07-NOV-09:00
EnergyTransfer:Zone:FLOOR 2 SCHEDULING 1 11.38 0.00 01-JAN-00:10 1068.97 02-MAR-07:10
Heating:EnergyTransfer:Zone:FLOOR 2 SCHEDULING 1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 SCHEDULING 1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 SCHEDULING 1 11.38 0.00 01-JAN-00:10 1068.97 02-MAR-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 SCHEDULING 1 11.38 0.00 01-JAN-00:10 1068.97 02-MAR-07:10
EnergyTransfer:Zone:FLOOR 2 SCHEDULING 2 12.53 0.00 01-JAN-00:10 1177.90 23-FEB-07:10
Heating:EnergyTransfer:Zone:FLOOR 2 SCHEDULING 2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 SCHEDULING 2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 SCHEDULING 2 12.53 0.00 01-JAN-00:10 1177.90 23-FEB-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 SCHEDULING 2 12.53 0.00 01-JAN-00:10 1177.90 23-FEB-07:10
EnergyTransfer:Zone:FLOOR 2 STORAGE 1 1.34 0.00 01-JAN-00:10 126.78 13-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 2 STORAGE 1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 STORAGE 1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 STORAGE 1 1.34 0.00 01-JAN-00:10 126.78 13-JAN-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 STORAGE 1 1.34 0.00 01-JAN-00:10 126.78 13-JAN-07:10
EnergyTransfer:Zone:FLOOR 2 STORAGE 2 3.00 0.00 01-JAN-00:10 280.15 11-MAY-06:10
Heating:EnergyTransfer:Zone:FLOOR 2 STORAGE 2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 STORAGE 2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 STORAGE 2 3.00 0.00 01-JAN-00:10 280.15 11-MAY-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 STORAGE 2 3.00 0.00 01-JAN-00:10 280.15 11-MAY-06:10
EnergyTransfer:Zone:FLOOR 2 STORAGE 3 3.99 0.00 01-JAN-00:10 376.38 07-APR-06:10
Heating:EnergyTransfer:Zone:FLOOR 2 STORAGE 3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 STORAGE 3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 STORAGE 3 3.99 0.00 01-JAN-00:10 376.38 07-APR-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 STORAGE 3 3.99 0.00 01-JAN-00:10 376.38 07-APR-06:10
EnergyTransfer:Zone:FLOOR 2 UTILITY 5.84 0.00 01-JAN-00:10 763.81 25-JUL-09:30
Heating:EnergyTransfer:Zone:FLOOR 2 UTILITY 0.00 0.00 01-JAN-00:10 240.30 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 UTILITY 0.00 0.00 01-JAN-00:10 240.30 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 UTILITY 5.83 0.00 01-JAN-00:10 763.81 25-JUL-09:30
General:Cooling:EnergyTransfer:Zone:FLOOR 2 UTILITY 5.83 0.00 01-JAN-00:10 763.81 25-JUL-09:30
EnergyTransfer:Zone:FLOOR 2 WORK 57.86 0.00 01-JAN-00:10 5044.11 21-JUL-06:10
Heating:EnergyTransfer:Zone:FLOOR 2 WORK 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 WORK 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 WORK 57.86 0.00 01-JAN-00:10 5044.11 21-JUL-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 WORK 57.86 0.00 01-JAN-00:10 5044.11 21-JUL-06:10
EnergyTransfer:Zone:FLOOR 2 WORK HALL 29.97 0.00 01-JAN-00:10 2710.19 31-MAR-06:10
Heating:EnergyTransfer:Zone:FLOOR 2 WORK HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 WORK HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 WORK HALL 29.97 0.00 01-JAN-00:10 2710.19 31-MAR-06:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 WORK HALL 29.97 0.00 01-JAN-00:10 2710.19 31-MAR-06:10
EnergyTransfer:Zone:FLOOR 2 WORK TOILET 3.40 0.00 01-JAN-00:10 262.38 28-JUL-17:00
Heating:EnergyTransfer:Zone:FLOOR 2 WORK TOILET 0.00 0.00 01-JAN-00:10 97.65 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 WORK TOILET 0.00 0.00 01-JAN-00:10 97.65 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 WORK TOILET 3.40 0.00 01-JAN-00:10 262.38 28-JUL-17:00
General:Cooling:EnergyTransfer:Zone:FLOOR 2 WORK TOILET 3.40 0.00 01-JAN-00:10 262.38 28-JUL-17:00
EnergyTransfer:Zone:FLOOR 2 X-RAY 149.07 1298.81 04-FEB-19:10 9767.52 27-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 2 X-RAY 0.10 0.00 01-JAN-00:10 1191.72 28-JUL-17:10
General:Heating:EnergyTransfer:Zone:FLOOR 2 X-RAY 0.10 0.00 01-JAN-00:10 1191.72 28-JUL-17:10
Cooling:EnergyTransfer:Zone:FLOOR 2 X-RAY 148.97 1298.81 04-FEB-19:10 9767.52 27-JAN-07:10
General:Cooling:EnergyTransfer:Zone:FLOOR 2 X-RAY 148.97 1298.81 04-FEB-19:10 9767.52 27-JAN-07:10
EnergyTransfer:Zone:FLOOR 3 DRESSING ROOM 2.12 0.00 01-JAN-00:10 174.42 28-JUL-15:30
Heating:EnergyTransfer:Zone:FLOOR 3 DRESSING ROOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 DRESSING ROOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 3 DRESSING ROOM 2.12 0.00 01-JAN-00:10 174.42 28-JUL-15:30
General:Cooling:EnergyTransfer:Zone:FLOOR 3 DRESSING ROOM 2.12 0.00 01-JAN-00:10 174.42 28-JUL-15:30
EnergyTransfer:Zone:FLOOR 3 ELEVATOR HALL 13.94 0.00 01-JAN-00:10 1241.32 28-JUL-15:40
Heating:EnergyTransfer:Zone:FLOOR 3 ELEVATOR HALL 0.00 0.00 01-JAN-00:10 451.20 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 ELEVATOR HALL 0.00 0.00 01-JAN-00:10 451.20 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 ELEVATOR HALL 13.94 0.00 01-JAN-00:10 1241.32 28-JUL-15:40
General:Cooling:EnergyTransfer:Zone:FLOOR 3 ELEVATOR HALL 13.94 0.00 01-JAN-00:10 1241.32 28-JUL-15:40
EnergyTransfer:Zone:FLOOR 3 HUMID 5.55 0.00 01-JAN-00:10 458.27 28-JUL-15:30
Heating:EnergyTransfer:Zone:FLOOR 3 HUMID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 HUMID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 3 HUMID 5.55 0.00 01-JAN-00:10 458.27 28-JUL-15:30
General:Cooling:EnergyTransfer:Zone:FLOOR 3 HUMID 5.55 0.00 01-JAN-00:10 458.27 28-JUL-15:30
EnergyTransfer:Zone:FLOOR 3 JANITOR 2.82 0.00 01-JAN-00:10 356.82 28-JUL-16:40
Heating:EnergyTransfer:Zone:FLOOR 3 JANITOR 0.02 0.00 01-JAN-00:10 266.34 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 JANITOR 0.02 0.00 01-JAN-00:10 266.34 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 JANITOR 2.80 0.00 01-JAN-00:10 356.82 28-JUL-16:40
General:Cooling:EnergyTransfer:Zone:FLOOR 3 JANITOR 2.80 0.00 01-JAN-00:10 356.82 28-JUL-16:40
EnergyTransfer:Zone:FLOOR 3 LOCKER 9.06 0.00 01-JAN-00:10 712.10 28-JUL-15:30
Heating:EnergyTransfer:Zone:FLOOR 3 LOCKER 0.00 0.00 01-JAN-00:10 23.64 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 LOCKER 0.00 0.00 01-JAN-00:10 23.64 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 LOCKER 9.06 0.00 01-JAN-00:10 712.10 28-JUL-15:30
General:Cooling:EnergyTransfer:Zone:FLOOR 3 LOCKER 9.06 0.00 01-JAN-00:10 712.10 28-JUL-15:30
EnergyTransfer:Zone:FLOOR 3 LOUNGE 57.09 0.00 01-JAN-00:10 4696.17 28-JUL-15:30
Heating:EnergyTransfer:Zone:FLOOR 3 LOUNGE 0.00 0.00 01-JAN-00:10 712.32 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 LOUNGE 0.00 0.00 01-JAN-00:10 712.32 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 LOUNGE 57.09 0.00 01-JAN-00:10 4696.17 28-JUL-15:30
General:Cooling:EnergyTransfer:Zone:FLOOR 3 LOUNGE 57.09 0.00 01-JAN-00:10 4696.17 28-JUL-15:30
EnergyTransfer:Zone:FLOOR 3 LOUNGE TOILET 14.33 0.00 01-JAN-00:10 963.41 28-JUL-15:50
Heating:EnergyTransfer:Zone:FLOOR 3 LOUNGE TOILET 0.02 0.00 01-JAN-00:10 485.45 04-FEB-06:20
General:Heating:EnergyTransfer:Zone:FLOOR 3 LOUNGE TOILET 0.02 0.00 01-JAN-00:10 485.45 04-FEB-06:20
Cooling:EnergyTransfer:Zone:FLOOR 3 LOUNGE TOILET 14.31 0.00 01-JAN-00:10 963.41 28-JUL-15:50
General:Cooling:EnergyTransfer:Zone:FLOOR 3 LOUNGE TOILET 14.31 0.00 01-JAN-00:10 963.41 28-JUL-15:50
EnergyTransfer:Zone:FLOOR 3 MECHANICAL 50.94 0.00 01-JAN-00:10 4193.80 25-JUL-09:50
Heating:EnergyTransfer:Zone:FLOOR 3 MECHANICAL 0.00 0.00 01-JAN-00:10 267.54 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 MECHANICAL 0.00 0.00 01-JAN-00:10 267.54 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 MECHANICAL 50.94 0.00 01-JAN-00:10 4193.80 25-JUL-09:50
General:Cooling:EnergyTransfer:Zone:FLOOR 3 MECHANICAL 50.94 0.00 01-JAN-00:10 4193.80 25-JUL-09:50
EnergyTransfer:Zone:FLOOR 3 MECHANICAL HALL 13.76 0.00 01-JAN-00:10 1171.36 07-JUL-12:20
Heating:EnergyTransfer:Zone:FLOOR 3 MECHANICAL HALL 0.00 0.00 01-JAN-00:10 388.88 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 MECHANICAL HALL 0.00 0.00 01-JAN-00:10 388.88 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 MECHANICAL HALL 13.76 0.00 01-JAN-00:10 1171.36 07-JUL-12:20
General:Cooling:EnergyTransfer:Zone:FLOOR 3 MECHANICAL HALL 13.76 0.00 01-JAN-00:10 1171.36 07-JUL-12:20
EnergyTransfer:Zone:FLOOR 3 OFFICE 137.37 0.00 01-JAN-00:10 12349.85 28-JUL-15:10
Heating:EnergyTransfer:Zone:FLOOR 3 OFFICE 0.00 0.00 01-JAN-00:10 3412.96 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 OFFICE 0.00 0.00 01-JAN-00:10 3412.96 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 OFFICE 137.37 0.00 01-JAN-00:10 12349.85 28-JUL-15:10
General:Cooling:EnergyTransfer:Zone:FLOOR 3 OFFICE 137.37 0.00 01-JAN-00:10 12349.85 28-JUL-15:10
EnergyTransfer:Zone:FLOOR 3 OFFICE HALL 35.23 0.00 01-JAN-00:10 3006.66 28-JUL-15:40
Heating:EnergyTransfer:Zone:FLOOR 3 OFFICE HALL 0.00 0.00 01-JAN-00:10 567.29 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 OFFICE HALL 0.00 0.00 01-JAN-00:10 567.29 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 OFFICE HALL 35.23 0.00 01-JAN-00:10 3006.66 28-JUL-15:40
General:Cooling:EnergyTransfer:Zone:FLOOR 3 OFFICE HALL 35.23 0.00 01-JAN-00:10 3006.66 28-JUL-15:40
EnergyTransfer:Zone:FLOOR 3 OFFICE TOILET 4.24 0.00 01-JAN-00:10 279.09 28-JUL-16:50
Heating:EnergyTransfer:Zone:FLOOR 3 OFFICE TOILET 0.01 0.00 01-JAN-00:10 157.54 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 OFFICE TOILET 0.01 0.00 01-JAN-00:10 157.54 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 OFFICE TOILET 4.23 0.00 01-JAN-00:10 279.09 28-JUL-16:50
General:Cooling:EnergyTransfer:Zone:FLOOR 3 OFFICE TOILET 4.23 0.00 01-JAN-00:10 279.09 28-JUL-16:50
EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 1 118.37 0.00 01-JAN-00:10 9503.43 06-OCT-12:30
Heating:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 1 0.06 0.00 01-JAN-00:10 2925.90 04-FEB-06:20
General:Heating:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 1 0.06 0.00 01-JAN-00:10 2925.90 04-FEB-06:20
Cooling:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 1 118.31 0.00 01-JAN-00:10 9503.43 06-OCT-12:30
General:Cooling:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 1 118.31 0.00 01-JAN-00:10 9503.43 06-OCT-12:30
EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 2 43.44 0.00 01-JAN-00:10 2772.83 28-JUL-15:10
Heating:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 2 0.01 0.00 01-JAN-00:10 523.08 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 2 0.01 0.00 01-JAN-00:10 523.08 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 2 43.43 0.00 01-JAN-00:10 2772.83 28-JUL-15:10
General:Cooling:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 2 43.43 0.00 01-JAN-00:10 2772.83 28-JUL-15:10
EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 6.29 0.00 01-JAN-00:10 375.80 28-JUL-15:40
Heating:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 0.00 0.00 01-JAN-00:10 68.00 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 0.00 0.00 01-JAN-00:10 68.00 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 6.29 0.00 01-JAN-00:10 375.80 28-JUL-15:40
General:Cooling:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 6.29 0.00 01-JAN-00:10 375.80 28-JUL-15:40
EnergyTransfer:Zone:FLOOR 3 STORAGE 1 6.50 0.00 01-JAN-00:10 403.79 28-JUL-15:20
Heating:EnergyTransfer:Zone:FLOOR 3 STORAGE 1 0.01 0.00 01-JAN-00:10 119.85 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 STORAGE 1 0.01 0.00 01-JAN-00:10 119.85 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 STORAGE 1 6.48 0.00 01-JAN-00:10 403.79 28-JUL-15:20
General:Cooling:EnergyTransfer:Zone:FLOOR 3 STORAGE 1 6.48 0.00 01-JAN-00:10 403.79 28-JUL-15:20
EnergyTransfer:Zone:FLOOR 3 STORAGE 2 3.25 0.00 01-JAN-00:10 270.18 28-JUL-15:20
Heating:EnergyTransfer:Zone:FLOOR 3 STORAGE 2 0.00 0.00 01-JAN-00:10 46.57 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 STORAGE 2 0.00 0.00 01-JAN-00:10 46.57 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 STORAGE 2 3.25 0.00 01-JAN-00:10 270.18 28-JUL-15:20
General:Cooling:EnergyTransfer:Zone:FLOOR 3 STORAGE 2 3.25 0.00 01-JAN-00:10 270.18 28-JUL-15:20
EnergyTransfer:Zone:FLOOR 3 TREATMENT 37.74 0.00 01-JAN-00:10 2369.84 28-JUL-15:40
Heating:EnergyTransfer:Zone:FLOOR 3 TREATMENT 0.01 0.00 01-JAN-00:10 388.35 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 TREATMENT 0.01 0.00 01-JAN-00:10 388.35 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 TREATMENT 37.73 0.00 01-JAN-00:10 2369.84 28-JUL-15:40
General:Cooling:EnergyTransfer:Zone:FLOOR 3 TREATMENT 37.73 0.00 01-JAN-00:10 2369.84 28-JUL-15:40
EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 1 112.71 0.00 01-JAN-00:10 10643.02 28-JUL-15:40
Heating:EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 1 0.00 0.00 01-JAN-00:10 3235.09 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 1 0.00 0.00 01-JAN-00:10 3235.09 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 1 112.71 0.00 01-JAN-00:10 10643.02 28-JUL-15:40
General:Cooling:EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 1 112.71 0.00 01-JAN-00:10 10643.02 28-JUL-15:40
EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 2 61.16 0.00 01-JAN-00:10 5742.02 07-NOV-15:00
Heating:EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 2 0.01 0.00 01-JAN-00:10 1868.15 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 2 0.01 0.00 01-JAN-00:10 1868.15 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 2 61.16 0.00 01-JAN-00:10 5742.02 07-NOV-15:00
General:Cooling:EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 2 61.16 0.00 01-JAN-00:10 5742.02 07-NOV-15:00
EnergyTransfer:Zone:FLOOR 3 UTILITY 6.59 0.00 01-JAN-00:10 559.90 28-JUL-15:10
Heating:EnergyTransfer:Zone:FLOOR 3 UTILITY 0.00 0.00 01-JAN-00:10 49.81 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 UTILITY 0.00 0.00 01-JAN-00:10 49.81 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 UTILITY 6.59 0.00 01-JAN-00:10 559.90 28-JUL-15:10
General:Cooling:EnergyTransfer:Zone:FLOOR 3 UTILITY 6.59 0.00 01-JAN-00:10 559.90 28-JUL-15:10
EnergyTransfer:Zone:FLOOR 3 WORK 38.99 0.00 01-JAN-00:10 4152.46 25-JUL-09:50
Heating:EnergyTransfer:Zone:FLOOR 3 WORK 0.01 0.00 01-JAN-00:10 1312.09 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:FLOOR 3 WORK 0.01 0.00 01-JAN-00:10 1312.09 04-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 WORK 38.97 0.00 01-JAN-00:10 4152.46 25-JUL-09:50
General:Cooling:EnergyTransfer:Zone:FLOOR 3 WORK 38.97 0.00 01-JAN-00:10 4152.46 25-JUL-09:50
EnergyTransfer:Zone:NE STAIR 19.24 0.00 01-JAN-00:10 2393.92 31-JUL-14:10
Heating:EnergyTransfer:Zone:NE STAIR 0.23 0.00 01-JAN-00:10 2095.42 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:NE STAIR 0.23 0.00 01-JAN-00:10 2095.42 04-FEB-07:10
Cooling:EnergyTransfer:Zone:NE STAIR 19.00 0.00 01-JAN-00:10 2393.92 31-JUL-14:10
General:Cooling:EnergyTransfer:Zone:NE STAIR 19.00 0.00 01-JAN-00:10 2393.92 31-JUL-14:10
EnergyTransfer:Zone:NW ELEVATOR 13.17 0.00 01-JAN-00:10 1902.69 08-SEP-16:30
Heating:EnergyTransfer:Zone:NW ELEVATOR 0.05 0.00 01-JAN-00:10 1083.04 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:NW ELEVATOR 0.05 0.00 01-JAN-00:10 1083.04 04-FEB-07:10
Cooling:EnergyTransfer:Zone:NW ELEVATOR 13.13 0.00 01-JAN-00:10 1902.69 08-SEP-16:30
General:Cooling:EnergyTransfer:Zone:NW ELEVATOR 13.13 0.00 01-JAN-00:10 1902.69 08-SEP-16:30
EnergyTransfer:Zone:NW STAIR 20.88 0.00 01-JAN-00:10 2772.90 28-JUL-16:00
Heating:EnergyTransfer:Zone:NW STAIR 0.20 0.00 01-JAN-00:10 2068.85 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:NW STAIR 0.20 0.00 01-JAN-00:10 2068.85 04-FEB-07:10
Cooling:EnergyTransfer:Zone:NW STAIR 20.67 0.00 01-JAN-00:10 2772.90 28-JUL-16:00
General:Cooling:EnergyTransfer:Zone:NW STAIR 20.67 0.00 01-JAN-00:10 2772.90 28-JUL-16:00
EnergyTransfer:Zone:SW STAIR 12.01 0.00 01-JAN-00:10 1523.85 07-NOV-16:00
Heating:EnergyTransfer:Zone:SW STAIR 0.03 0.00 01-JAN-00:10 822.12 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:SW STAIR 0.03 0.00 01-JAN-00:10 822.12 04-FEB-07:10
Cooling:EnergyTransfer:Zone:SW STAIR 11.99 0.00 01-JAN-00:10 1523.85 07-NOV-16:00
General:Cooling:EnergyTransfer:Zone:SW STAIR 11.99 0.00 01-JAN-00:10 1523.85 07-NOV-16:00
PlantLoopHeatingDemand:Facility 183.11 0.00 01-JAN-00:10 78512.16 04-FEB-07:10
PlantLoopHeatingDemand:Plant 64.36 0.00 01-JAN-00:10 7645.12 18-JAN-11:20
WaterSystems:PlantLoopHeatingDemand 64.36 0.00 01-JAN-00:10 7645.12 18-JAN-11:20
General:WaterSystems:PlantLoopHeatingDemand 64.36 0.00 01-JAN-00:10 7645.12 18-JAN-11:20
EnergyTransfer:HVAC 5569.60 5136.06 05-FEB-04:40 487406.33 21-AUG-16:00
HeatingCoils:EnergyTransfer 118.76 0.00 01-JAN-00:10 80598.25 04-FEB-07:10
PlantLoopHeatingDemand:HVAC 118.75 0.00 01-JAN-00:10 78419.28 04-FEB-07:10
HeatingCoils:PlantLoopHeatingDemand 118.75 0.00 01-JAN-00:10 78419.28 04-FEB-07:10
CoolingCoils:EnergyTransfer 5450.84 5136.06 05-FEB-04:40 480016.67 21-AUG-16:00
EnergyTransfer:Plant 182.22 0.00 01-JAN-00:10 68825.72 04-FEB-07:10
WaterSystems:EnergyTransfer 64.36 0.00 01-JAN-00:10 7645.12 18-JAN-11:20
WaterUse:WaterSystems:EnergyTransfer 64.36 0.00 01-JAN-00:10 7645.12 18-JAN-11:20
Boilers:EnergyTransfer 117.86 0.00 01-JAN-00:10 68732.84 04-FEB-07:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
FLOOR 1 ANESTHESIA 0.000 0.000 0.007 -13.254 0.000 0.000 1.894 2.210 4.069 3.021 0.000 0.100 2.311 0.000 -0.331 0.000 -0.027 -0.000
FLOOR 1 BIO HAZ 0.000 0.000 0.000 -1.431 0.000 0.000 0.093 0.688 0.106 0.000 0.000 0.000 0.545 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 CAFE 0.000 0.000 0.033 -46.359 0.000 0.000 32.981 5.157 7.908 9.004 0.000 0.083 0.000 0.000 -2.282 0.000 -0.107 -6.419
FLOOR 1 CLEAN 0.000 0.000 0.007 -12.983 0.000 0.000 2.217 2.579 4.747 0.000 0.000 0.000 3.432 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 CLEAN WORK 0.000 0.000 0.014 -15.143 0.000 0.000 2.906 3.377 6.216 0.000 0.000 0.000 2.629 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 DICTATION 0.000 0.000 0.000 -4.202 0.000 0.000 0.432 1.891 2.610 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.731
FLOOR 1 DRESSING ROOM 0.000 0.000 0.001 -3.009 0.000 0.000 0.154 0.675 0.932 1.370 0.000 0.050 0.286 0.000 -0.427 0.000 -0.031 -0.000
FLOOR 1 ELECTRICAL ROOM 0.000 0.000 0.000 -8.801 0.000 0.000 0.120 2.006 9.229 0.000 0.000 0.035 0.000 0.000 0.000 0.000 -0.036 -2.553
FLOOR 1 ELEVATOR PUMP ROOM 0.000 0.000 0.005 -11.626 0.000 0.000 0.111 1.862 15.111 0.000 0.000 0.089 0.000 0.000 0.000 0.000 -0.110 -5.442
FLOOR 1 HUMID 0.000 0.000 0.000 -2.284 0.000 0.000 0.184 0.810 1.119 0.000 0.000 0.000 0.170 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 IT HALL 0.000 0.000 0.000 -3.758 0.000 0.000 0.576 1.829 1.056 0.000 0.000 0.000 0.297 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 IT ROOM 0.000 0.000 0.000 -3.949 0.000 0.000 0.383 1.681 2.320 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.435
FLOOR 1 LOBBY 0.000 0.000 0.000 -38.904 0.000 0.000 5.078 11.032 12.887 9.379 0.000 0.113 2.592 0.000 -2.075 0.000 -0.103 -0.000
FLOOR 1 LOBBY HALL 0.000 0.000 0.000 -10.611 0.000 0.000 0.981 3.135 1.810 0.000 0.000 0.000 4.686 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 LOBBY TOILET 0.000 0.000 0.003 -5.629 0.000 0.000 0.237 0.663 0.407 0.000 0.000 0.058 4.281 0.000 0.000 0.000 -0.020 -0.000
FLOOR 1 LOCKER ROOM 0.000 0.000 0.000 -44.346 0.000 0.000 8.077 7.204 37.292 3.245 0.000 0.117 0.000 0.000 -1.299 0.000 -0.114 -10.175
FLOOR 1 LOCKER ROOM HALL 0.000 0.000 0.000 -13.710 0.000 0.000 2.037 6.478 3.741 0.000 0.000 0.000 1.454 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 LOUNGE 0.000 0.000 0.000 -23.039 0.000 0.000 4.411 3.929 20.341 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -5.643
FLOOR 1 MED GAS 0.000 0.000 0.028 -3.204 0.000 0.000 0.093 0.688 0.106 0.000 0.000 0.090 2.234 0.000 0.000 0.000 -0.034 -0.000
FLOOR 1 MRI CONTROL ROOM 0.000 0.000 0.007 -32.331 0.000 0.000 2.729 3.438 31.643 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -5.487
FLOOR 1 MRI HALL 0.000 0.000 0.000 -5.676 0.000 0.000 0.603 1.920 1.109 0.000 0.000 0.000 2.044 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 MRI ROOM 0.000 0.000 0.020 -82.771 0.000 0.000 7.147 9.005 82.876 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -16.277
FLOOR 1 MRI TOILET 0.000 0.000 0.006 -4.272 0.000 0.000 0.237 0.663 0.407 0.000 0.000 0.066 2.908 0.000 0.000 0.000 -0.016 -0.000
FLOOR 1 NOURISHMENT 0.000 0.000 0.000 -9.804 0.000 0.000 2.238 2.483 6.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.773
FLOOR 1 NURSE HALL 0.000 0.000 0.000 -12.737 0.000 0.000 2.045 6.478 3.741 0.000 0.000 0.000 0.473 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 NURSE JANITOR 0.000 0.000 0.000 -1.721 0.000 0.000 0.089 0.663 0.102 0.000 0.000 0.000 0.867 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 NURSE STATION 0.000 0.000 0.000 -12.861 0.000 0.000 3.210 3.561 9.833 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -3.743
FLOOR 1 NURSE TOILET 0.000 0.000 0.012 -3.198 0.000 0.000 0.238 0.663 0.407 0.000 0.000 0.000 1.878 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 OFFICE 0.000 0.000 0.000 -17.121 0.000 0.000 1.645 7.249 10.007 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.779
FLOOR 1 OPERATING ROOM 1 0.000 0.000 0.045 -109.676 0.000 0.000 8.730 13.808 65.258 13.851 0.000 0.458 9.174 0.000 -1.544 0.000 -0.104 0.000
FLOOR 1 OPERATING ROOM 2 0.000 0.000 0.052 -109.631 0.000 0.000 9.135 14.408 68.095 11.848 0.000 0.256 7.216 0.000 -1.322 0.000 -0.058 -0.000
FLOOR 1 OPERATING ROOM 3 0.000 0.000 0.056 -98.591 0.000 0.000 9.100 14.288 67.528 0.000 0.000 0.000 7.620 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 PACU 0.000 0.000 0.008 -11.363 0.000 0.000 1.902 1.179 6.102 0.000 0.000 0.000 2.173 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 PRE-OP HALL 0.000 0.000 0.000 -14.372 0.000 0.000 2.171 6.896 3.982 0.000 0.000 0.000 1.323 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 PRE-OP ROOM 1 0.000 0.000 0.016 -16.375 0.000 0.000 1.662 1.805 7.120 0.000 0.000 0.045 5.738 0.000 0.000 0.000 -0.013 -0.000
FLOOR 1 PRE-OP ROOM 2 0.000 0.000 0.031 -27.825 0.000 0.000 2.975 3.228 12.734 0.000 0.000 0.000 8.857 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 PRE-OP TOILET 0.000 0.000 0.006 -4.500 0.000 0.000 0.237 0.663 0.407 0.000 0.000 0.063 3.140 0.000 0.000 0.000 -0.017 -0.000
FLOOR 1 PROCEDURE ROOM 0.000 0.000 0.036 -34.599 0.000 0.000 5.028 5.833 16.103 4.333 0.000 0.229 3.959 0.000 -0.863 0.000 -0.059 -0.000
FLOOR 1 RECEPTION 0.000 0.000 0.000 -34.924 0.000 0.000 12.471 9.028 10.546 3.292 0.000 0.074 0.317 0.000 -0.742 0.000 -0.062 -0.000
FLOOR 1 RECEPTION HALL 0.000 0.000 0.000 -3.977 0.000 0.000 0.526 1.672 0.965 0.000 0.000 0.000 0.814 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 RECOVERY ROOM 0.000 0.000 0.032 -63.158 0.000 0.000 9.420 5.894 30.511 11.895 0.000 0.483 6.485 0.000 -1.410 0.000 -0.151 -0.000
FLOOR 1 SCHEDULING 0.000 0.000 0.000 -4.987 0.000 0.000 0.406 1.786 2.465 0.674 0.000 0.045 0.000 0.000 -0.131 0.000 -0.028 -0.231
FLOOR 1 SCRUB 0.000 0.000 0.000 -2.687 0.000 0.000 0.345 1.097 0.634 0.000 0.000 0.000 0.611 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 SOIL 0.000 0.000 0.011 -11.940 0.000 0.000 2.219 2.579 4.747 0.000 0.000 0.000 2.385 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 SOIL HOLD 0.000 0.000 0.003 -5.924 0.000 0.000 0.986 1.146 2.110 0.000 0.000 0.000 1.680 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 SOIL WORK 0.000 0.000 0.019 -15.575 0.000 0.000 3.172 3.684 6.781 0.000 0.000 0.000 1.919 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 STEP DOWN 0.000 0.000 0.013 -35.919 0.000 0.000 5.150 3.275 16.951 8.315 0.000 0.354 3.055 0.000 -1.067 0.000 -0.126 -0.000
FLOOR 1 STERILE HALL 0.000 0.000 0.000 -17.428 0.000 0.000 2.532 8.046 4.646 2.806 0.000 0.000 0.000 0.000 -0.388 0.000 0.000 -0.214
FLOOR 1 STERILE STORAGE 0.000 0.000 0.000 -8.857 0.000 0.000 0.651 4.863 0.748 0.000 0.000 0.000 2.595 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 STORAGE 0.000 0.000 0.074 -29.047 0.000 0.000 1.528 11.297 1.739 5.313 0.000 0.389 10.145 0.000 -1.279 0.000 -0.160 -0.000
FLOOR 1 SUB-STERILE 0.000 0.000 0.001 -9.124 0.000 0.000 0.807 2.560 1.478 4.630 0.000 0.090 0.274 0.000 -0.670 0.000 -0.045 -0.000
FLOOR 1 UTILITY HALL 0.000 0.000 0.012 -13.359 0.000 0.000 1.067 3.344 1.931 0.000 0.000 0.111 6.935 0.000 0.000 0.000 -0.041 -0.000
FLOOR 1 UTILITY JANITOR 0.000 0.000 0.000 -1.380 0.000 0.000 0.069 0.516 0.079 0.000 0.000 0.000 0.715 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 UTILITY ROOM 0.000 0.000 0.001 -12.490 0.000 0.000 0.593 4.421 0.680 3.455 0.000 0.113 3.781 0.000 -0.497 0.000 -0.058 -0.000
FLOOR 1 VESTIBULE 0.000 0.000 0.373 -8.487 0.000 0.000 0.243 0.940 0.543 0.000 0.000 8.095 0.000 0.000 0.000 0.000 -1.116 -0.592
FLOOR 2 CONFERENCE 0.000 0.000 0.002 -28.047 0.000 0.000 10.121 5.960 6.326 10.936 0.000 0.329 0.000 0.000 -1.849 0.000 -0.226 -3.552
FLOOR 2 CONFERENCE TOILET 0.000 0.000 0.000 -3.641 0.000 0.000 0.279 0.786 0.483 0.000 0.000 0.000 2.094 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 DICTATION 0.000 0.000 0.000 -2.412 0.000 0.000 0.239 1.051 1.450 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.328
FLOOR 2 EXAM 1 0.000 0.000 0.004 -26.865 0.000 0.000 5.943 7.368 7.459 9.473 0.000 0.382 0.000 0.000 -1.705 0.000 -0.245 -1.813
FLOOR 2 EXAM 2 0.000 0.000 0.002 -37.192 0.000 0.000 9.235 11.051 11.188 4.697 0.000 0.219 1.629 0.000 -0.721 0.000 -0.109 -0.000
FLOOR 2 EXAM 3 0.000 0.000 0.012 -47.839 0.000 0.000 12.409 14.735 14.917 7.653 0.000 0.307 0.000 0.000 -1.074 0.000 -0.135 -0.985
FLOOR 2 EXAM 4 0.000 0.000 0.001 -6.579 0.000 0.000 1.387 1.719 1.740 2.685 0.000 0.069 0.000 0.000 -0.407 0.000 -0.038 -0.577
FLOOR 2 EXAM 5 0.000 0.000 0.006 -28.943 0.000 0.000 5.864 7.163 7.251 9.005 0.000 0.260 0.980 0.000 -1.448 0.000 -0.138 -0.000
FLOOR 2 EXAM 6 0.000 0.000 0.004 -16.290 0.000 0.000 3.847 4.605 4.662 2.928 0.000 0.175 0.898 0.000 -0.753 0.000 -0.075 -0.000
FLOOR 2 EXAM 7 0.000 0.000 0.006 -51.697 0.000 0.000 13.684 16.209 16.409 4.060 0.000 0.304 2.233 0.000 -1.072 0.000 -0.135 -0.000
FLOOR 2 EXAM 8 0.000 0.000 0.002 -20.030 0.000 0.000 4.589 5.526 5.594 3.822 0.000 0.205 1.481 0.000 -1.090 0.000 -0.099 -0.000
FLOOR 2 EXAM 9 0.000 0.000 0.001 -27.923 0.000 0.000 6.821 8.104 8.204 1.979 0.000 0.148 3.289 0.000 -0.554 0.000 -0.070 -0.000
FLOOR 2 EXAM HALL 1 0.000 0.000 0.000 -6.396 0.000 0.000 0.738 2.351 1.358 0.000 0.000 0.000 1.949 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 EXAM HALL 2 0.000 0.000 0.000 -5.828 0.000 0.000 0.739 2.351 1.358 0.000 0.000 0.000 1.380 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 EXAM HALL 3 0.000 0.000 0.000 -5.332 0.000 0.000 0.740 2.351 1.358 0.000 0.000 0.000 0.883 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 EXAM HALL 4 0.000 0.000 0.000 -6.026 0.000 0.000 0.813 2.586 1.493 0.000 0.000 0.000 1.133 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 EXAM HALL 5 0.000 0.000 0.000 -6.574 0.000 0.000 0.812 2.586 1.493 0.000 0.000 0.000 1.682 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 EXAM HALL 6 0.000 0.000 0.000 -6.242 0.000 0.000 0.813 2.586 1.493 0.000 0.000 0.000 1.350 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 JANITOR 0.000 0.000 0.001 -2.602 0.000 0.000 0.104 0.774 0.119 0.000 0.000 0.116 1.576 0.000 0.000 0.000 -0.088 -0.000
FLOOR 2 LOUNGE 0.000 0.000 0.000 -4.696 0.000 0.000 0.982 0.873 4.520 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.679
FLOOR 2 NURSE STATION 1 0.000 0.000 0.000 -7.790 0.000 0.000 1.841 2.047 5.651 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.748
FLOOR 2 NURSE STATION 2 0.000 0.000 0.000 -9.670 0.000 0.000 2.207 2.456 6.781 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.775
FLOOR 2 OFFICE 0.000 0.000 0.003 -29.209 0.000 0.000 1.913 8.405 11.602 13.246 0.000 0.319 0.000 0.000 -2.260 0.000 -0.226 -3.792
FLOOR 2 OFFICE HALL 0.000 0.000 0.000 -14.074 0.000 0.000 1.822 5.799 3.349 0.000 0.000 0.000 3.105 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 RECEPTION 0.000 0.000 0.001 -67.031 0.000 0.000 24.084 17.453 20.387 17.396 0.000 0.362 0.000 0.000 -3.944 0.000 -0.356 -8.352
FLOOR 2 RECEPTION HALL 0.000 0.000 0.000 -19.624 0.000 0.000 2.311 7.366 4.254 0.000 0.000 0.000 5.693 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 RECEPTION TOILET 0.000 0.000 0.000 -7.154 0.000 0.000 0.545 1.547 0.950 0.000 0.000 0.000 4.111 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 SCHEDULING 1 0.000 0.000 0.000 -11.384 0.000 0.000 1.104 4.863 6.713 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.295
FLOOR 2 SCHEDULING 2 0.000 0.000 0.000 -12.531 0.000 0.000 1.164 5.133 7.086 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.852
FLOOR 2 STORAGE 1 0.000 0.000 0.000 -1.343 0.000 0.000 0.092 0.688 0.106 0.000 0.000 0.000 0.458 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 STORAGE 2 0.000 0.000 0.000 -2.998 0.000 0.000 0.197 1.474 0.227 0.000 0.000 0.000 1.101 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 STORAGE 3 0.000 0.000 0.000 -3.994 0.000 0.000 0.236 1.768 0.272 0.000 0.000 0.000 1.717 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 UTILITY 0.000 0.000 0.002 -5.833 0.000 0.000 0.208 1.547 0.238 3.369 0.000 0.078 0.949 0.000 -0.515 0.000 -0.043 -0.000
FLOOR 2 WORK 0.000 0.000 0.000 -57.858 0.000 0.000 5.746 25.364 28.923 3.276 0.000 0.201 0.000 0.000 -1.323 0.000 -0.187 -4.141
FLOOR 2 WORK HALL 0.000 0.000 0.000 -29.973 0.000 0.000 3.414 10.893 6.290 0.000 0.000 0.000 9.376 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 WORK TOILET 0.000 0.000 0.001 -3.401 0.000 0.000 0.235 0.663 0.407 0.000 0.000 0.066 2.058 0.000 0.000 0.000 -0.030 -0.000
FLOOR 2 X-RAY 0.000 0.000 0.097 -148.970 0.000 0.000 14.624 18.419 169.518 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -53.688
FLOOR 3 DRESSING ROOM 0.000 0.000 0.000 -2.125 0.000 0.000 0.144 0.630 0.870 0.000 0.000 0.000 0.480 0.000 0.000 0.000 0.000 -0.000
FLOOR 3 ELEVATOR HALL 0.000 0.000 0.000 -13.935 0.000 0.000 1.518 4.833 2.790 0.000 0.000 0.044 4.771 0.000 0.000 0.000 -0.021 -0.000
FLOOR 3 HUMID 0.000 0.000 0.000 -5.554 0.000 0.000 0.370 1.621 2.238 0.000 0.000 0.000 1.326 0.000 0.000 0.000 0.000 -0.000
FLOOR 3 JANITOR 0.000 0.000 0.019 -2.805 0.000 0.000 0.105 0.774 0.119 0.000 0.000 0.175 1.674 0.000 0.000 0.000 -0.060 -0.000
FLOOR 3 LOCKER 0.000 0.000 0.000 -9.063 0.000 0.000 1.473 1.310 6.780 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.501
FLOOR 3 LOUNGE 0.000 0.000 0.000 -57.094 0.000 0.000 9.298 8.285 42.886 3.365 0.000 0.234 0.000 0.000 -1.101 0.000 -0.139 -5.734
FLOOR 3 LOUNGE TOILET 0.000 0.000 0.022 -14.311 0.000 0.000 0.834 2.358 1.448 3.082 0.000 0.219 6.910 0.000 -0.521 0.000 -0.041 0.000
FLOOR 3 MECHANICAL 0.000 0.000 0.000 -50.942 0.000 0.000 0.427 7.163 32.962 8.075 0.000 0.197 4.071 0.000 -1.751 0.000 -0.202 -0.000
FLOOR 3 MECHANICAL HALL 0.000 0.000 0.000 -13.764 0.000 0.000 1.232 3.918 2.263 0.000 0.000 0.000 6.351 0.000 0.000 0.000 0.000 -0.000
FLOOR 3 OFFICE 0.000 0.000 0.003 -137.370 0.000 0.000 10.344 45.565 62.901 11.809 0.000 0.782 10.008 0.000 -3.639 0.000 -0.401 -0.000
FLOOR 3 OFFICE HALL 0.000 0.000 0.000 -35.231 0.000 0.000 3.423 10.893 6.290 0.000 0.000 0.068 14.589 0.000 0.000 0.000 -0.033 -0.000
FLOOR 3 OFFICE TOILET 0.000 0.000 0.006 -4.232 0.000 0.000 0.235 0.663 0.407 0.000 0.000 0.101 2.842 0.000 0.000 0.000 -0.021 -0.000
FLOOR 3 PHYSICAL THERAPY 1 0.000 0.000 0.061 -118.305 0.000 0.000 21.656 15.963 36.738 34.803 0.000 1.409 11.475 0.000 -3.485 0.000 -0.316 -0.000
FLOOR 3 PHYSICAL THERAPY 2 0.000 0.000 0.014 -43.426 0.000 0.000 9.938 7.269 16.730 0.000 0.000 0.000 9.474 0.000 0.000 0.000 0.000 -0.000
FLOOR 3 PHYSICAL THERAPY TOILET 0.000 0.000 0.003 -6.288 0.000 0.000 0.367 1.031 0.634 0.000 0.000 0.000 4.252 0.000 0.000 0.000 0.000 -0.000
FLOOR 3 STORAGE 1 0.000 0.000 0.014 -6.482 0.000 0.000 0.189 1.326 0.204 0.000 0.000 0.000 4.749 0.000 0.000 0.000 0.000 -0.000
FLOOR 3 STORAGE 2 0.000 0.000 0.000 -3.248 0.000 0.000 0.138 1.031 0.159 0.000 0.000 0.000 1.920 0.000 0.000 0.000 0.000 -0.000
FLOOR 3 TREATMENT 0.000 0.000 0.007 -37.732 0.000 0.000 7.956 9.742 9.862 0.000 0.000 0.000 10.164 0.000 0.000 0.000 0.000 -0.000
FLOOR 3 UNDEVELOPED 1 0.000 0.000 0.005 -112.709 0.000 0.000 3.713 27.850 46.989 27.315 0.000 0.735 10.919 0.000 -4.418 0.000 -0.399 -0.000
FLOOR 3 UNDEVELOPED 2 0.000 0.000 0.006 -61.155 0.000 0.000 1.886 14.146 23.867 14.298 0.000 0.541 9.142 0.000 -2.420 0.000 -0.311 -0.000
FLOOR 3 UTILITY 0.000 0.000 0.000 -6.586 0.000 0.000 0.356 4.421 0.408 0.000 0.000 0.000 1.401 0.000 0.000 0.000 0.000 -0.000
FLOOR 3 WORK 0.000 0.000 0.013 -38.975 0.000 0.000 1.969 8.615 11.892 13.038 0.000 0.479 4.815 0.000 -1.673 0.000 -0.174 -0.000
NE STAIR 0.000 0.000 0.232 -19.002 0.000 0.000 0.695 2.194 1.267 7.642 0.000 0.763 8.458 0.000 -1.871 0.000 -0.378 0.000
NW ELEVATOR 0.000 0.000 0.045 -13.127 0.000 0.000 0.173 1.829 1.056 0.000 0.000 0.588 9.834 0.000 0.000 0.000 -0.398 -0.000
NW STAIR 0.000 0.000 0.205 -20.670 0.000 0.000 0.794 2.508 1.448 6.406 0.000 0.839 10.953 0.000 -1.997 0.000 -0.486 0.000
SW STAIR 0.000 0.000 0.026 -11.985 0.000 0.000 0.394 1.254 0.724 1.239 0.000 0.406 8.498 0.000 -0.226 0.000 -0.328 0.000
Total Facility 0.000 0.000 1.761 -2775.042 0.000 0.000 387.805 626.080 1299.433 322.028 0.000 22.728 334.198 0.000 -58.142 0.000 -8.545 -152.307


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
FLOOR 1 ANESTHESIA 01-JAN-08:11 0.00 0.00 0.00 -1002.45 0.00 0.00 7.23 16.20 106.98 203.09 0.00 0.00 672.30 0.00 -0.00 0.00 -3.35 0.00
FLOOR 1 BIO HAZ 15-JUN-06:01 0.00 0.00 0.00 -143.98 0.00 0.00 7.77 45.36 5.57 0.00 0.00 0.00 85.28 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 CAFE 20-JAN-07:01 0.00 0.00 0.00 -6809.48 0.00 0.00 2750.71 340.20 415.84 0.00 0.00 0.00 3690.76 0.00 -380.13 0.00 -7.91 0.00
FLOOR 1 CLEAN 26-JAN-04:21 0.00 0.00 0.00 -1189.44 0.00 0.00 0.00 56.70 124.81 0.00 0.00 0.00 1007.93 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 CLEAN WORK 26-JAN-04:21 0.00 0.00 0.00 -1446.82 0.00 0.00 0.00 74.25 163.44 0.00 0.00 0.00 1209.13 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 DICTATION 24-JAN-07:01 0.00 0.00 0.00 -769.30 0.00 0.00 41.27 124.74 137.27 0.00 0.00 0.00 466.02 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 DRESSING ROOM 06-AUG-14:31 0.00 0.00 0.00 -537.52 0.00 0.00 0.62 4.95 24.51 156.27 0.00 10.72 340.45 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 04-JUL-11:51 0.00 0.00 0.00 -1216.95 0.00 0.00 0.40 14.70 242.66 0.00 0.00 5.63 953.55 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 27-NOV-07:01 0.00 0.00 0.00 -1340.77 0.00 0.00 8.94 122.85 696.20 0.00 0.00 0.00 518.02 0.00 -0.00 0.00 -5.24 0.00
FLOOR 1 HUMID 24-JAN-07:01 0.00 0.00 0.00 -380.54 0.00 0.00 17.69 53.46 58.83 0.00 0.00 0.00 250.56 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 IT HALL 03-FEB-07:01 0.00 0.00 0.00 -665.08 0.00 0.00 47.45 120.62 55.52 0.00 0.00 0.00 441.49 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 IT ROOM 16-JUN-06:01 0.00 0.00 0.00 -650.04 0.00 0.00 37.16 110.88 122.02 0.00 0.00 0.00 379.99 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 LOBBY 04-JUL-15:51 0.00 0.00 0.00 -6457.66 0.00 0.00 16.77 80.86 338.83 1760.60 0.00 20.87 4239.73 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 LOBBY HALL 13-MAY-04:01 0.00 0.00 0.00 -1429.74 0.00 0.00 0.00 22.97 28.55 0.00 0.00 0.00 1378.21 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 22-OCT-07:01 0.00 0.00 0.00 -456.94 0.00 0.00 0.90 4.86 10.71 0.00 0.00 0.00 440.83 0.00 -0.00 0.00 -0.35 0.00
FLOOR 1 LOCKER ROOM 06-AUG-14:31 0.00 0.00 0.00 -5697.04 0.00 0.00 30.19 52.80 980.50 392.01 0.00 30.07 4211.47 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 22-MAR-06:02 0.00 0.00 0.00 -2182.62 0.00 0.00 162.51 427.33 196.71 0.00 0.00 0.00 1396.07 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 LOUNGE 13-MAY-04:01 0.00 0.00 0.00 -2928.35 0.00 0.00 0.00 28.80 320.89 0.00 0.00 0.00 2578.66 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 MED GAS 04-JUL-12:31 0.00 0.00 0.00 -696.03 0.00 0.00 0.28 5.04 2.78 0.00 0.00 10.00 677.93 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 MRI CONTROL ROOM 15-MAR-06:01 0.00 0.00 0.00 -3391.58 0.00 0.00 220.07 226.80 1663.99 0.00 0.00 0.00 1280.73 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 MRI HALL 12-DEC-07:02 0.00 0.00 0.00 -844.18 0.00 0.00 48.37 126.65 58.30 0.00 0.00 0.00 610.87 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 MRI ROOM 25-JAN-07:01 0.00 0.00 0.00 -9017.22 0.00 0.00 576.39 594.00 4358.06 0.00 0.00 0.00 3488.77 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 MRI TOILET 13-AUG-03:41 0.00 0.00 0.00 -369.61 0.00 0.00 0.00 2.43 6.42 0.00 0.00 0.22 360.53 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 NOURISHMENT 27-NOV-06:12 0.00 0.00 0.00 -1445.52 0.00 0.00 92.43 109.20 360.56 0.00 0.00 0.00 883.33 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 NURSE HALL 27-JAN-07:01 0.00 0.00 0.00 -2332.85 0.00 0.00 165.57 427.33 196.71 0.00 0.00 0.00 1543.24 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR 24-JAN-07:01 0.00 0.00 0.00 -301.38 0.00 0.00 7.07 43.74 5.37 0.00 0.00 0.00 245.20 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 NURSE STATION 03-FEB-06:12 0.00 0.00 0.00 -1899.45 0.00 0.00 133.61 156.60 517.07 0.00 0.00 0.00 1092.17 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 28-JAN-06:01 0.00 0.00 0.00 -360.95 0.00 0.00 3.79 4.86 6.42 0.00 0.00 0.00 345.88 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 OFFICE 27-NOV-06:12 0.00 0.00 0.00 -2583.17 0.00 0.00 83.36 318.78 526.22 0.00 0.00 0.00 1654.81 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 1 16-MAR-05:01 0.00 0.00 0.00 -15798.87 0.00 0.00 357.18 607.20 3431.62 0.00 0.00 0.00 12170.94 0.00 -743.41 0.00 -24.66 0.00
FLOOR 1 OPERATING ROOM 2 16-MAR-05:01 0.00 0.00 0.00 -16422.63 0.00 0.00 372.71 633.60 3580.82 0.00 0.00 0.00 12495.39 0.00 -646.05 0.00 -13.84 0.00
FLOOR 1 OPERATING ROOM 3 16-MAR-05:01 0.00 0.00 0.00 -16340.24 0.00 0.00 369.60 628.32 3550.98 0.00 0.00 0.00 11791.34 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 PACU 27-JAN-04:21 0.00 0.00 0.00 -1037.58 0.00 0.00 0.00 25.92 160.45 0.00 0.00 0.00 851.22 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 24-JAN-07:02 0.00 0.00 0.00 -2434.23 0.00 0.00 175.28 454.90 209.40 0.00 0.00 0.00 1594.65 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 1 24-JAN-04:11 0.00 0.00 0.00 -1387.02 0.00 0.00 0.00 39.69 187.22 0.00 0.00 0.00 1166.36 0.00 -0.00 0.00 -6.24 0.00
FLOOR 1 PRE-OP ROOM 2 26-JAN-04:21 0.00 0.00 0.00 -2597.34 0.00 0.00 0.00 70.98 334.81 0.00 0.00 0.00 2191.55 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 22-OCT-07:01 0.00 0.00 0.00 -363.13 0.00 0.00 0.95 4.86 10.71 0.00 0.00 0.00 346.72 0.00 -0.00 0.00 -0.12 0.00
FLOOR 1 PROCEDURE ROOM 03-MAR-04:11 0.00 0.00 0.00 -4866.79 0.00 0.00 0.00 128.25 423.40 0.00 0.00 0.00 4433.45 0.00 -108.18 0.00 -10.12 0.00
FLOOR 1 RECEPTION 13-MAY-04:01 0.00 0.00 0.00 -4182.38 0.00 0.00 0.00 66.17 166.36 0.00 0.00 2.22 3959.74 0.00 -12.12 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL 24-JAN-07:02 0.00 0.00 0.00 -651.45 0.00 0.00 42.01 110.28 50.76 0.00 0.00 0.00 448.40 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 RECOVERY ROOM 31-DEC-13:28 0.00 0.00 0.00 -4874.38 0.00 0.00 33.83 43.20 802.23 1724.29 0.00 0.00 2288.08 0.00 -0.00 0.00 -17.25 0.00
FLOOR 1 SCHEDULING 21-FEB-07:01 0.00 0.00 0.00 -726.90 0.00 0.00 39.06 117.81 129.65 0.00 0.00 0.00 465.74 0.00 -23.54 0.00 -1.81 0.00
FLOOR 1 SCRUB 02-AUG-06:01 0.00 0.00 0.00 -423.76 0.00 0.00 28.24 72.37 33.31 0.00 0.00 0.00 289.83 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 SOIL 26-JAN-04:21 0.00 0.00 0.00 -1161.38 0.00 0.00 0.00 56.70 124.81 0.00 0.00 0.00 979.87 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 SOIL HOLD 15-MAR-03:11 0.00 0.00 0.00 -493.68 0.00 0.00 0.00 25.20 55.47 0.00 0.00 0.00 413.01 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 SOIL WORK 27-JAN-04:21 0.00 0.00 0.00 -1516.80 0.00 0.00 0.00 81.00 178.30 0.00 0.00 0.00 1257.50 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 STEP DOWN 07-NOV-15:00 0.00 0.00 0.00 -2755.82 0.00 0.00 419.36 216.00 891.37 1295.70 0.00 2.85 0.00 0.00 -0.00 0.00 0.00 -69.45
FLOOR 1 STERILE HALL 02-MAR-07:01 0.00 0.00 0.00 -2644.11 0.00 0.00 207.86 530.72 244.30 0.00 0.00 0.00 1712.66 0.00 -51.43 0.00 0.00 0.00
FLOOR 1 STERILE STORAGE 22-MAR-06:02 0.00 0.00 0.00 -1557.06 0.00 0.00 52.49 320.76 39.35 0.00 0.00 0.00 1144.46 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 STORAGE 04-JUL-15:51 0.00 0.00 0.00 -6196.93 0.00 0.00 5.14 82.80 45.71 543.92 0.00 60.28 5459.07 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 SUB-STERILE 04-JUL-11:11 0.00 0.00 0.00 -1783.95 0.00 0.00 2.84 18.76 38.87 492.12 0.00 9.86 1221.51 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 UTILITY HALL 02-JUL-10:31 0.00 0.00 0.00 -3397.86 0.00 0.00 3.17 24.51 50.76 0.00 0.00 5.87 3313.56 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 UTILITY JANITOR 02-AUG-06:01 0.00 0.00 0.00 -226.61 0.00 0.00 5.65 34.02 4.17 0.00 0.00 0.00 182.77 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 04-JUL-11:11 0.00 0.00 0.00 -2508.67 0.00 0.00 2.14 32.40 17.89 368.68 0.00 12.91 2074.65 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 VESTIBULE 28-JUL-15:40 0.00 0.00 0.00 -1174.16 0.00 0.00 4.30 62.03 28.55 0.00 0.00 1647.63 0.00 0.00 -0.00 0.00 0.00 -568.36
FLOOR 2 CONFERENCE 03-DEC-15:01 0.00 0.00 0.00 -4097.79 0.00 0.00 43.17 43.68 166.34 1121.36 0.00 0.00 2732.59 0.00 -0.00 0.00 -9.35 0.00
FLOOR 2 CONFERENCE TOILET 27-MAY-04:02 0.00 0.00 0.00 -355.78 0.00 0.00 0.00 5.76 7.61 0.00 0.00 0.00 342.40 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 DICTATION 27-JAN-06:12 0.00 0.00 0.00 -417.51 0.00 0.00 12.32 46.20 76.26 0.00 0.00 0.00 282.73 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM 1 03-DEC-15:01 0.00 0.00 0.00 -3923.08 0.00 0.00 20.77 54.00 196.11 1548.89 0.00 0.00 2107.86 0.00 -0.00 0.00 -4.56 0.00
FLOOR 2 EXAM 2 27-MAY-04:02 0.00 0.00 0.00 -3467.41 0.00 0.00 0.00 81.00 176.50 0.00 0.00 4.31 3208.15 0.00 -2.55 0.00 0.00 0.00
FLOOR 2 EXAM 3 27-MAY-04:02 0.00 0.00 0.00 -4503.10 0.00 0.00 0.00 108.00 235.33 3.85 0.00 7.30 4148.63 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM 4 03-DEC-15:01 0.00 0.00 0.00 -815.25 0.00 0.00 4.52 12.60 45.76 376.65 0.00 0.00 377.25 0.00 -0.00 0.00 -1.52 0.00
FLOOR 2 EXAM 5 10-SEP-11:11 0.00 0.00 0.00 -3816.69 0.00 0.00 20.64 52.50 190.66 869.23 0.00 32.86 2650.79 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM 6 27-MAY-04:02 0.00 0.00 0.00 -1518.80 0.00 0.00 0.00 33.75 73.54 0.00 0.00 3.68 1412.69 0.00 -4.86 0.00 0.00 0.00
FLOOR 2 EXAM 7 27-MAY-04:02 0.00 0.00 0.00 -5124.76 0.00 0.00 0.00 118.80 258.86 0.00 0.00 5.27 4748.05 0.00 -6.23 0.00 0.00 0.00
FLOOR 2 EXAM 8 15-JUL-04:01 0.00 0.00 0.00 -1908.16 0.00 0.00 0.00 40.50 88.25 0.00 0.00 1.94 1791.17 0.00 -13.70 0.00 0.00 0.00
FLOOR 2 EXAM 9 27-MAY-04:02 0.00 0.00 0.00 -2706.19 0.00 0.00 0.00 59.40 129.43 0.00 0.00 2.67 2518.73 0.00 -4.04 0.00 0.00 0.00
FLOOR 2 EXAM HALL 1 11-FEB-05:01 0.00 0.00 0.00 -1003.75 0.00 0.00 0.00 17.23 21.42 0.00 0.00 0.00 965.10 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 2 14-JAN-05:01 0.00 0.00 0.00 -991.41 0.00 0.00 0.00 17.23 21.42 0.00 0.00 0.00 952.76 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 3 23-FEB-07:01 0.00 0.00 0.00 -882.23 0.00 0.00 59.88 155.08 71.39 0.00 0.00 0.00 595.88 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 4 08-MAY-05:01 0.00 0.00 0.00 -975.33 0.00 0.00 34.33 113.72 78.53 0.00 0.00 0.00 748.75 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 5 15-JUL-04:01 0.00 0.00 0.00 -1086.05 0.00 0.00 0.00 18.95 23.56 0.00 0.00 0.00 1043.53 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 6 08-MAY-05:01 0.00 0.00 0.00 -1015.51 0.00 0.00 33.97 113.72 78.53 0.00 0.00 0.00 789.29 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 JANITOR 29-MAY-17:32 0.00 0.00 0.00 -481.10 0.00 0.00 0.35 2.83 1.88 0.00 0.00 39.44 436.60 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 LOUNGE 12-MAY-04:01 0.00 0.00 0.00 -637.06 0.00 0.00 0.00 19.20 118.85 0.00 0.00 0.00 499.01 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 1 12-MAY-04:01 0.00 0.00 0.00 -1026.28 0.00 0.00 0.00 45.00 148.58 0.00 0.00 0.00 832.69 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 2 09-MAY-04:01 0.00 0.00 0.00 -1259.15 0.00 0.00 0.00 54.00 178.30 0.00 0.00 0.00 1026.85 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 OFFICE 10-SEP-11:11 0.00 0.00 0.00 -5367.72 0.00 0.00 7.69 61.60 305.05 1277.03 0.00 44.52 3671.83 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 OFFICE HALL 08-MAY-05:01 0.00 0.00 0.00 -2206.80 0.00 0.00 75.68 255.02 176.09 0.00 0.00 0.00 1700.02 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION 03-DEC-15:01 0.00 0.00 0.00 -8751.78 0.00 0.00 80.31 127.92 536.02 2808.61 0.00 0.00 5209.29 0.00 -0.00 0.00 -10.38 0.00
FLOOR 2 RECEPTION HALL 11-FEB-05:01 0.00 0.00 0.00 -3115.02 0.00 0.00 0.00 53.99 67.10 0.00 0.00 0.00 2993.92 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 27-MAY-04:02 0.00 0.00 0.00 -682.37 0.00 0.00 0.00 11.34 14.99 0.00 0.00 0.00 656.04 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 1 11-FEB-05:01 0.00 0.00 0.00 -1672.29 0.00 0.00 0.00 35.64 105.90 0.00 0.00 0.00 1530.75 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 2 11-FEB-05:01 0.00 0.00 0.00 -1818.72 0.00 0.00 0.00 37.62 111.78 0.00 0.00 0.00 1669.32 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 1 23-FEB-07:01 0.00 0.00 0.00 -264.86 0.00 0.00 7.54 45.36 5.57 0.00 0.00 0.00 206.40 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 2 08-MAY-05:01 0.00 0.00 0.00 -512.49 0.00 0.00 8.34 64.80 11.93 0.00 0.00 0.00 427.42 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 3 15-JUL-04:01 0.00 0.00 0.00 -682.36 0.00 0.00 0.00 12.96 4.29 0.00 0.00 0.00 665.11 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 UTILITY 23-JUL-10:11 0.00 0.00 0.00 -1183.75 0.00 0.00 0.67 11.34 6.26 529.61 0.00 6.50 629.37 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 WORK 27-MAY-04:02 0.00 0.00 0.00 -8192.99 0.00 0.00 0.00 185.90 456.27 0.00 0.00 0.70 7568.19 0.00 -18.07 0.00 0.00 0.00
FLOOR 2 WORK HALL 11-FEB-05:01 0.00 0.00 0.00 -4490.26 0.00 0.00 0.00 79.84 99.23 0.00 0.00 0.00 4311.19 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 WORK TOILET 09-APR-19:11 0.00 0.00 0.00 -326.06 0.00 0.00 0.00 2.43 6.42 0.00 0.00 0.08 317.12 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 X-RAY 03-FEB-07:01 0.00 0.00 0.00 -18280.38 0.00 0.00 1178.95 1215.00 8914.22 0.00 0.00 0.00 6972.21 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 DRESSING ROOM 15-DEC-07:01 0.00 0.00 0.00 -280.64 0.00 0.00 14.02 41.58 45.76 0.00 0.00 0.00 179.29 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 04-JUL-16:01 0.00 0.00 0.00 -1864.27 0.00 0.00 5.60 17.71 44.02 0.00 0.00 6.84 1790.10 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 HUMID 15-DEC-07:01 0.00 0.00 0.00 -669.44 0.00 0.00 35.51 106.92 117.66 0.00 0.00 0.00 409.34 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 JANITOR 29-MAY-16:01 0.00 0.00 0.00 -506.41 0.00 0.00 0.34 2.83 1.88 0.00 0.00 49.41 451.95 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 LOCKER 04-JUL-16:01 0.00 0.00 0.00 -1077.98 0.00 0.00 5.30 4.80 106.96 0.00 0.00 0.00 960.91 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 LOUNGE 30-JUL-12:41 0.00 0.00 0.00 -6773.97 0.00 0.00 30.79 60.72 1127.58 420.88 0.00 45.75 5088.25 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 LOUNGE TOILET 30-JUL-13:21 0.00 0.00 0.00 -1213.63 0.00 0.00 3.05 17.28 38.07 337.67 0.00 28.84 788.71 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 MECHANICAL 30-JUL-11:21 0.00 0.00 0.00 -6883.48 0.00 0.00 0.96 52.50 866.66 830.06 0.00 19.31 5113.98 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 MECHANICAL HALL 30-JUL-13:21 0.00 0.00 0.00 -1933.64 0.00 0.00 4.58 28.72 59.49 0.00 0.00 0.00 1840.85 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 OFFICE 30-JUL-13:21 0.00 0.00 0.00 -17879.22 0.00 0.00 43.81 333.96 1653.83 1451.76 0.00 152.72 14243.14 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 OFFICE HALL 04-JUL-16:01 0.00 0.00 0.00 -4720.60 0.00 0.00 12.85 39.92 99.23 0.00 0.00 10.72 4557.89 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 OFFICE TOILET 04-JUL-16:02 0.00 0.00 0.00 -354.48 0.00 0.00 0.84 2.43 6.42 0.00 0.00 12.44 332.34 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY 1 30-JUL-12:41 0.00 0.00 0.00 -11760.11 0.00 0.00 75.09 117.00 965.95 2704.60 0.00 186.11 7711.35 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY 2 16-JUL-13:22 0.00 0.00 0.00 -2839.91 0.00 0.00 42.54 53.28 439.88 0.00 0.00 0.00 2304.21 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 04-JUL-16:02 0.00 0.00 0.00 -445.57 0.00 0.00 1.51 3.78 9.99 0.00 0.00 0.00 430.28 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 1 04-JUL-16:02 0.00 0.00 0.00 -482.79 0.00 0.00 0.80 4.86 3.22 0.00 0.00 0.00 473.91 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 2 01-SEP-06:01 0.00 0.00 0.00 -395.00 0.00 0.00 11.39 68.04 8.35 0.00 0.00 0.00 307.21 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 TREATMENT 04-JUL-16:02 0.00 0.00 0.00 -2406.42 0.00 0.00 33.59 35.70 155.58 0.00 0.00 0.00 2181.54 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 1 16-APR-14:51 0.00 0.00 0.00 -15128.70 0.00 0.00 12.34 204.12 1235.47 3347.54 0.00 75.44 10253.79 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 2 16-APR-14:51 0.00 0.00 0.00 -8075.13 0.00 0.00 6.11 103.68 627.54 1656.96 0.00 56.11 5624.73 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 UTILITY 03-FEB-07:01 0.00 0.00 0.00 -750.69 0.00 0.00 29.80 291.60 21.47 0.00 0.00 0.00 407.82 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 WORK 30-JUL-11:21 0.00 0.00 0.00 -6433.08 0.00 0.00 7.03 63.14 312.68 1322.87 0.00 42.32 4685.04 0.00 -0.00 0.00 0.00 0.00
NE STAIR 10-SEP-12:31 0.00 0.00 0.00 -3526.11 0.00 0.00 2.14 16.08 33.31 687.19 0.00 126.25 2661.14 0.00 -0.00 0.00 0.00 0.00
NW ELEVATOR 15-OCT-16:32 0.00 0.00 0.00 -2745.92 0.00 0.00 0.57 6.70 16.66 0.00 0.00 40.03 2681.96 0.00 -0.00 0.00 0.00 0.00
NW STAIR 10-SEP-12:31 0.00 0.00 0.00 -3971.95 0.00 0.00 2.54 18.38 38.07 640.66 0.00 157.82 3114.48 0.00 -0.00 0.00 0.00 0.00
SW STAIR 03-DEC-15:01 0.00 0.00 0.00 -2146.84 0.00 0.00 1.17 9.19 19.04 183.66 0.00 0.00 1956.26 0.00 -0.00 0.00 -22.47 0.00
Total Facility 01-SEP-06:01 -9873.15 9873.15 9873.15 -219013.04 0.00 0.00 33225.53 41298.67 68232.98 5363.90 0.00 1698.71 59320.10 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
FLOOR 1 ANESTHESIA 04-FEB-06:12 0.00 0.00 926.66 0.00 0.00 0.00 40.10 16.20 64.19 0.00 0.00 0.00 0.00 0.00 -156.86 0.00 -7.24 -883.05
FLOOR 1 BIO HAZ 23-JAN-07:01 0.00 0.00 128.21 0.00 0.00 0.00 8.42 45.36 5.57 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -187.55
FLOOR 1 CAFE 29-JUL-14:01 0.00 0.00 2913.14 0.00 0.00 0.00 652.20 113.40 207.92 862.06 0.00 6.75 0.00 0.00 -0.00 0.00 0.00 -4755.48
FLOOR 1 CLEAN 21-AUG-06:01 0.00 0.00 845.96 0.00 0.00 0.00 196.43 170.10 249.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1462.11
FLOOR 1 CLEAN WORK 10-JUL-06:01 0.00 0.00 1170.90 0.00 0.00 0.00 257.22 222.75 326.89 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1977.76
FLOOR 1 DICTATION - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 DRESSING ROOM 04-FEB-06:12 0.00 0.00 270.05 0.00 0.00 0.00 1.02 4.95 14.71 0.00 0.00 0.00 0.00 0.00 -161.37 0.00 -7.26 -122.10
FLOOR 1 ELECTRICAL ROOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 21-MAR-05:13 0.00 0.00 201.55 0.00 0.00 0.00 4.42 81.90 573.72 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -4.88 -856.71
FLOOR 1 HUMID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 IT HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 IT ROOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY 04-FEB-07:03 0.00 0.00 100.30 0.00 0.00 0.00 104.01 242.58 338.83 0.00 0.00 0.00 0.00 0.00 -644.60 0.00 -18.84 -122.28
FLOOR 1 LOBBY HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 16-MAR-06:01 0.00 0.00 496.78 0.00 0.00 0.00 21.04 43.74 21.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -4.47 -578.51
FLOOR 1 LOCKER ROOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 LOUNGE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 MED GAS 04-FEB-06:12 0.00 0.00 462.71 0.00 0.00 0.00 2.08 5.04 1.67 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -11.55 -459.95
FLOOR 1 MRI CONTROL ROOM 28-JUL-17:01 0.00 0.00 450.77 0.00 0.00 0.00 130.44 151.20 831.99 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1564.40
FLOOR 1 MRI HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI ROOM 28-JUL-17:01 0.00 0.00 1191.71 0.00 0.00 0.00 341.63 396.00 2179.03 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -4108.38
FLOOR 1 MRI TOILET 04-FEB-06:12 0.00 0.00 452.26 0.00 0.00 0.00 5.01 4.86 6.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -4.82 -463.74
FLOOR 1 NOURISHMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE STATION - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 16-MAR-06:01 0.00 0.00 381.12 0.00 0.00 0.00 21.05 43.74 21.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -467.33
FLOOR 1 OFFICE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 1 29-JUL-16:01 0.00 0.00 4227.18 0.00 0.00 0.00 168.85 303.60 1715.81 1013.35 0.00 18.55 0.00 0.00 -0.00 0.00 0.00 -7447.34
FLOOR 1 OPERATING ROOM 2 29-JUL-16:01 0.00 0.00 4476.32 0.00 0.00 0.00 176.19 316.80 1790.41 873.83 0.00 10.40 0.00 0.00 -0.00 0.00 0.00 -7643.96
FLOOR 1 OPERATING ROOM 3 29-JUL-16:01 0.00 0.00 4607.51 0.00 0.00 0.00 174.72 314.16 1775.49 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -6871.88
FLOOR 1 PACU 10-JUL-06:01 0.00 0.00 738.16 0.00 0.00 0.00 168.37 77.76 320.89 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1305.18
FLOOR 1 PRE-OP HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 1 16-MAR-06:01 0.00 0.00 1385.40 0.00 0.00 0.00 147.33 119.07 374.43 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -2.97 -2023.26
FLOOR 1 PRE-OP ROOM 2 16-MAR-06:01 0.00 0.00 2373.07 0.00 0.00 0.00 263.47 212.94 669.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -3519.09
FLOOR 1 PRE-OP TOILET 04-FEB-06:12 0.00 0.00 485.16 0.00 0.00 0.00 5.01 4.86 6.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -4.81 -496.64
FLOOR 1 PROCEDURE ROOM 04-FEB-06:12 0.00 0.00 2057.64 0.00 0.00 0.00 105.82 42.75 254.04 0.00 0.00 0.00 0.00 0.00 -392.48 0.00 -15.15 -2052.61
FLOOR 1 RECEPTION - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 RECOVERY ROOM 04-FEB-06:12 0.00 0.00 4722.56 0.00 0.00 0.00 200.51 43.20 481.34 0.00 0.00 0.00 0.00 0.00 -629.54 0.00 -36.23 -4781.83
FLOOR 1 SCHEDULING - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 SCRUB - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL 21-AUG-06:01 0.00 0.00 898.58 0.00 0.00 0.00 196.45 170.10 249.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1514.75
FLOOR 1 SOIL HOLD 17-JAN-07:01 0.00 0.00 409.91 0.00 0.00 0.00 87.31 75.60 110.94 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -683.76
FLOOR 1 SOIL WORK 10-JUL-06:01 0.00 0.00 1323.49 0.00 0.00 0.00 280.64 243.00 356.60 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2203.73
FLOOR 1 STEP DOWN 04-FEB-06:12 0.00 0.00 2780.48 0.00 0.00 0.00 111.39 24.00 267.41 0.00 0.00 0.00 0.00 0.00 -457.24 0.00 -29.79 -2696.25
FLOOR 1 STERILE HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 STERILE STORAGE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 STORAGE 04-FEB-06:12 0.00 0.00 4339.91 0.00 0.00 0.00 34.16 82.80 27.43 0.00 0.00 0.00 0.00 0.00 -540.25 0.00 -47.72 -3896.33
FLOOR 1 SUB-STERILE 16-MAR-06:01 0.00 0.00 1010.83 0.00 0.00 0.00 74.74 168.86 77.73 0.00 0.00 0.00 0.00 0.00 -274.60 0.00 -10.43 -1047.15
FLOOR 1 UTILITY HALL 04-FEB-06:12 0.00 0.00 2106.55 0.00 0.00 0.00 23.76 24.51 30.46 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -12.56 -2172.71
FLOOR 1 UTILITY JANITOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 16-MAR-06:01 0.00 0.00 1665.82 0.00 0.00 0.00 55.03 291.60 35.78 0.00 0.00 0.00 0.00 0.00 -203.61 0.00 -13.30 -1831.31
FLOOR 1 VESTIBULE 16-MAR-07:00 0.00 0.00 534.08 0.00 0.00 0.00 37.98 62.03 28.55 0.00 0.00 0.00 1289.55 0.00 -0.00 0.00 -1952.19 0.00
FLOOR 2 CONFERENCE 04-FEB-06:12 0.00 0.00 2854.12 0.00 0.00 0.00 77.97 43.68 99.80 0.00 0.00 0.00 0.00 0.00 -661.88 0.00 -45.48 -2368.22
FLOOR 2 CONFERENCE TOILET 16-MAR-06:01 0.00 0.00 278.28 0.00 0.00 0.00 24.41 51.84 25.38 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -379.91
FLOOR 2 DICTATION - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 1 04-FEB-06:12 0.00 0.00 3255.64 0.00 0.00 0.00 133.67 54.00 117.66 0.00 0.00 0.00 0.00 0.00 -619.43 0.00 -48.50 -2893.04
FLOOR 2 EXAM 2 04-FEB-07:03 0.00 0.00 1786.94 0.00 0.00 0.00 187.08 243.00 294.16 0.00 0.00 0.00 0.00 0.00 -241.78 0.00 -22.03 -2247.37
FLOOR 2 EXAM 3 16-MAR-06:01 0.00 0.00 4088.75 0.00 0.00 0.00 1108.85 972.00 784.42 0.00 0.00 0.00 0.00 0.00 -430.27 0.00 -25.75 -6498.00
FLOOR 2 EXAM 4 16-MAR-06:01 0.00 0.00 710.31 0.00 0.00 0.00 130.94 113.40 91.52 0.00 0.00 0.00 0.00 0.00 -155.12 0.00 -7.45 -883.60
FLOOR 2 EXAM 5 16-MAR-06:01 0.00 0.00 3337.91 0.00 0.00 0.00 545.70 472.50 381.32 0.00 0.00 0.00 0.00 0.00 -538.29 0.00 -26.79 -4172.35
FLOOR 2 EXAM 6 16-MAR-06:01 0.00 0.00 2091.90 0.00 0.00 0.00 350.81 303.75 245.13 0.00 0.00 0.00 0.00 0.00 -291.62 0.00 -16.07 -2683.91
FLOOR 2 EXAM 7 16-MAR-06:01 0.00 0.00 3531.36 0.00 0.00 0.00 1213.91 1069.20 862.87 0.00 0.00 0.00 0.00 0.00 -408.62 0.00 -25.75 -6242.97
FLOOR 2 EXAM 8 16-MAR-06:01 0.00 0.00 2401.00 0.00 0.00 0.00 420.88 364.50 294.16 0.00 0.00 0.00 0.00 0.00 -395.46 0.00 -19.28 -3065.81
FLOOR 2 EXAM 9 16-MAR-06:01 0.00 0.00 1322.32 0.00 0.00 0.00 604.46 534.60 431.43 0.00 0.00 0.00 0.00 0.00 -205.45 0.00 -12.88 -2674.48
FLOOR 2 EXAM HALL 1 04-FEB-07:03 0.00 0.00 151.67 0.00 0.00 0.00 15.06 51.69 35.69 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -254.12
FLOOR 2 EXAM HALL 2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 5 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 JANITOR 04-FEB-06:12 0.00 0.00 384.94 0.00 0.00 0.00 2.28 5.67 1.88 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -18.47 -376.30
FLOOR 2 LOUNGE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 OFFICE 04-FEB-06:12 0.00 0.00 3744.54 0.00 0.00 0.00 12.76 61.60 183.03 0.00 0.00 0.00 0.00 0.00 -842.38 0.00 -46.63 -3112.92
FLOOR 2 OFFICE HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION 04-FEB-07:03 0.00 0.00 3397.29 0.00 0.00 0.00 508.75 383.76 536.02 0.00 0.00 0.00 0.00 0.00 -1219.09 0.00 -60.25 -3546.49
FLOOR 2 RECEPTION HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 04-FEB-07:03 0.00 0.00 345.07 0.00 0.00 0.00 10.88 34.02 24.99 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -414.96
FLOOR 2 SCHEDULING 1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 UTILITY 04-FEB-06:12 0.00 0.00 924.53 0.00 0.00 0.00 4.63 11.34 3.76 0.00 0.00 0.00 0.00 0.00 -206.43 0.00 -10.36 -727.47
FLOOR 2 WORK - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 WORK HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 2 WORK TOILET 16-MAR-06:01 0.00 0.00 528.12 0.00 0.00 0.00 21.04 43.74 21.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -6.40 -607.91
FLOOR 2 X-RAY 28-JUL-17:01 0.00 0.00 11931.52 0.00 0.00 0.00 698.78 810.00 4457.11 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -17897.40
FLOOR 3 DRESSING ROOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 04-FEB-07:03 0.00 0.00 1479.85 0.00 0.00 0.00 32.04 106.26 73.37 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -5.78 -1685.74
FLOOR 3 HUMID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 3 JANITOR 04-FEB-06:12 0.00 0.00 397.09 0.00 0.00 0.00 2.34 5.67 1.88 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -20.76 -386.22
FLOOR 3 LOCKER 04-FEB-07:03 0.00 0.00 94.56 0.00 0.00 0.00 30.34 28.80 178.27 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -331.97
FLOOR 3 LOUNGE 04-FEB-07:03 0.00 0.00 2849.25 0.00 0.00 0.00 197.21 182.16 1127.58 0.00 0.00 0.00 0.00 0.00 -415.87 0.00 -33.47 -3906.86
FLOOR 3 LOUNGE TOILET 04-FEB-06:12 0.00 0.00 2103.88 0.00 0.00 0.00 17.82 17.28 22.84 0.00 0.00 0.00 0.00 0.00 -292.30 0.00 -16.48 -1853.05
FLOOR 3 MECHANICAL 04-FEB-07:03 0.00 0.00 1070.16 0.00 0.00 0.00 9.09 157.50 866.66 0.00 0.00 0.00 0.00 0.00 -244.62 0.00 -36.34 -1822.45
FLOOR 3 MECHANICAL HALL 04-FEB-07:03 0.00 0.00 1308.02 0.00 0.00 0.00 25.98 86.16 59.49 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1479.64
FLOOR 3 OFFICE 04-FEB-07:03 0.00 0.00 11504.54 0.00 0.00 0.00 262.95 1001.88 1653.83 0.00 0.00 0.00 0.00 0.00 -1446.72 0.00 -106.75 -12869.73
FLOOR 3 OFFICE HALL 04-FEB-07:03 0.00 0.00 2269.18 0.00 0.00 0.00 71.01 239.51 165.38 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -8.75 -2736.32
FLOOR 3 OFFICE TOILET 04-FEB-06:12 0.00 0.00 612.70 0.00 0.00 0.00 5.01 4.86 6.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -8.25 -620.75
FLOOR 3 PHYSICAL THERAPY 1 04-FEB-06:12 0.00 0.00 13057.31 0.00 0.00 0.00 482.70 117.00 579.57 0.00 0.00 0.00 0.00 0.00 -1952.41 0.00 -115.88 -12168.29
FLOOR 3 PHYSICAL THERAPY 2 04-FEB-07:03 0.00 0.00 2092.35 0.00 0.00 0.00 205.08 159.84 439.88 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2897.15
FLOOR 3 PHYSICAL THERAPY TOILET 02-OCT-06:01 0.00 0.00 462.77 0.00 0.00 0.00 32.45 68.04 33.31 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -596.58
FLOOR 3 STORAGE 1 30-OCT-06:01 0.00 0.00 717.07 0.00 0.00 0.00 16.84 87.48 10.73 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -832.12
FLOOR 3 STORAGE 2 04-FEB-07:03 0.00 0.00 174.73 0.00 0.00 0.00 2.84 22.68 4.17 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -204.42
FLOOR 3 TREATMENT 04-FEB-07:03 0.00 0.00 1553.41 0.00 0.00 0.00 164.92 214.20 259.30 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2191.82
FLOOR 3 UNDEVELOPED 1 04-FEB-07:03 0.00 0.00 10346.14 0.00 0.00 0.00 78.56 612.36 1235.47 0.00 0.00 0.00 0.00 0.00 -1674.81 0.00 -104.52 -10493.20
FLOOR 3 UNDEVELOPED 2 04-FEB-06:12 0.00 0.00 6046.58 0.00 0.00 0.00 41.99 103.68 376.52 0.00 0.00 0.00 0.00 0.00 -954.58 0.00 -75.80 -5538.39
FLOOR 3 UTILITY 04-FEB-07:03 0.00 0.00 199.24 0.00 0.00 0.00 7.23 97.20 10.73 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -314.40
FLOOR 3 WORK 04-FEB-06:12 0.00 0.00 4729.78 0.00 0.00 0.00 13.32 63.14 187.61 0.00 0.00 0.00 0.00 0.00 -792.08 0.00 -54.70 -4147.07
NE STAIR 04-FEB-05:21 0.00 0.00 2764.90 0.00 0.00 0.00 0.00 16.08 19.99 0.00 0.00 0.00 0.00 0.00 -705.63 0.00 -420.84 -1674.50
NW ELEVATOR 04-FEB-06:12 0.00 0.00 2145.57 0.00 0.00 0.00 3.90 13.40 16.66 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -88.23 -2091.30
NW STAIR 04-FEB-06:01 0.00 0.00 3156.40 0.00 0.00 0.00 18.92 18.38 22.84 0.00 0.00 0.00 0.00 0.00 -679.25 0.00 -120.37 -2416.92
SW STAIR 04-FEB-06:12 0.00 0.00 1552.11 0.00 0.00 0.00 8.91 9.19 11.42 0.00 0.00 0.00 0.00 0.00 -70.39 0.00 -65.43 -1445.81
Total Facility 04-FEB-07:03 -39349.80 39349.80 102675.39 -39349.80 0.00 0.00 8011.90 13766.22 34464.59 0.00 0.00 0.00 0.00 0.00 -19247.35 0.00 -1878.06 -98442.89



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
AHU-1 5.5424 0.0000 115.2784 1.0000 Calculated from schedules 1.0656 5.5424 0.1984 1.0000 Not calculated 1.0656 0.1923    
AHU-2 6.4494 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 6.0520 0.0000 1.0000 Not calculated 0.0000 0.0000    
AHU-3 6.0884 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 5.7700 0.0000 1.0000 Not calculated 0.0000 0.0000    
PSZ_CAFE 0.3593 0.0000 42.0041 1.0000 Calculated from schedules 0.1843 0.3593 0.5131 1.0000 Not calculated 0.1843 0.5131    
PSZ_ELEVATOR 0.0966 0.0000 0.1365 1.0000 Calculated from schedules 0.0000 0.0966 0.0000 1.0000 Not calculated 0.0000 0.0000    
PSZ_MRI_CONTROL 0.1939 0.0000 3.3603 1.0000 Calculated from schedules 0.0238 0.1939 0.1227 1.0000 Not calculated 0.0238 0.1227    
PSZ_MRI 0.4648 0.0000 8.8009 1.0000 Calculated from schedules 0.0623 0.4648 0.1340 1.0000 Not calculated 0.0623 0.1340    
PSZ_OR_1 0.7236 0.0000 9.2009 1.0000 Calculated from schedules 0.2388 0.7236 0.3777 1.0000 Not calculated 0.2388 0.3300    
PSZ_OR_2 0.7551 0.0000 9.6009 1.0000 Calculated from schedules 0.2492 0.7551 0.3816 1.0000 Not calculated 0.2492 0.3300    
PSZ_OR_3 0.7488 0.0000 9.5209 1.0000 Calculated from schedules 0.2471 0.7488 0.4477 1.0000 Not calculated 0.2471 0.3300    
PSZ_XRAY 1.0673 0.0000 18.0018 1.0000 Calculated from schedules 0.1274 1.0673 0.1194 1.0000 Not calculated 0.1274 0.1194    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
AHU-1 3.5281 0.0000 115.2784 1.0000 Calculated from schedules 1.0656 2.3850 1.0000 1.0000 Not calculated 1.0656 0.4468    
AHU-2 4.0309 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.1847 0.0000 1.0000 Not calculated 0.0000 0.0000    
AHU-3 3.4511 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.5291 0.0000 1.0000 Not calculated 0.0000 0.0000    
PSZ_CAFE 0.3593 0.0000 42.0041 1.0000 Calculated from schedules 0.1843 0.3593 1.0000 1.0000 Not calculated 0.1843 0.5131    
PSZ_ELEVATOR 0.0966 0.0000 0.1365 1.0000 Calculated from schedules 0.0000 0.0966 0.0000 1.0000 Not calculated 0.0000 0.0000    
PSZ_MRI_CONTROL 0.1939 0.0000 3.3603 1.0000 Calculated from schedules 0.0238 0.1939 1.0000 1.0000 Not calculated 0.0238 0.1227    
PSZ_MRI 0.4648 0.0000 8.8009 1.0000 Calculated from schedules 0.0623 0.4648 1.0000 1.0000 Not calculated 0.0623 0.1340    
PSZ_OR_1 0.7236 0.0000 9.2009 1.0000 Calculated from schedules 0.2388 0.7236 1.0000 1.0000 Not calculated 0.2388 0.3300    
PSZ_OR_2 0.7551 0.0000 9.6009 1.0000 Calculated from schedules 0.2492 0.7551 1.0000 1.0000 Not calculated 0.2492 0.3300    
PSZ_OR_3 0.7488 0.0000 9.5209 1.0000 Calculated from schedules 0.2471 0.7488 1.0000 1.0000 Not calculated 0.2471 0.3300    
PSZ_XRAY 1.0673 0.0000 18.0018 1.0000 Calculated from schedules 0.1274 1.0673 1.0000 1.0000 Not calculated 0.1274 0.1194    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
FLOOR 1 ANESTHESIA AHU-1 0.000000 2.1602 0.001524 10.03 0.0153 1.0000 0.0153 1.000 0.0153
FLOOR 1 BIO HAZ AHU-1 0.000000 0.1120 0.000610 5.20 0.0032 1.0000 0.0032 1.000 0.0032
FLOOR 1 CAFE PSZ_CAFE 0.000000 42.0041 0.004724 39.02 0.1843 1.0000 0.1843 1.000 0.1843
FLOOR 1 CLEAN AHU-1 0.000000 2.5202 0.001524 11.71 0.0178 1.0000 0.0178 1.000 0.0178
FLOOR 1 CLEAN WORK AHU-1 0.000000 3.3003 0.001524 15.33 0.0234 1.0000 0.0234 1.000 0.0234
FLOOR 1 DICTATION AHU-1 0.000000 0.6301 0.000432 11.71 0.0051 1.0000 0.0051 1.000 0.0051
FLOOR 1 DRESSING ROOM AHU-1 0.000000 0.2250 0.000432 4.18 0.0018 1.0000 0.0018 1.000 0.0018
FLOOR 1 ELECTRICAL ROOM AHU-1 0.000000 0.1470 0.000000 9.10 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 ELEVATOR PUMP ROOM PSZ_ELEVATOR 0.000000 0.1365 0.000000 8.45 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 HUMID AHU-1 0.000000 0.2700 0.000432 5.02 0.0022 1.0000 0.0022 1.000 0.0022
FLOOR 1 IT HALL AHU-1 0.000000 0.7000 0.000305 13.01 0.0040 1.0000 0.0040 1.000 0.0040
FLOOR 1 IT ROOM AHU-1 0.000000 0.5601 0.000432 10.41 0.0045 1.0000 0.0045 1.000 0.0045
FLOOR 1 LOBBY AHU-1 0.000000 6.2206 0.000559 57.79 0.0323 1.0000 0.0323 1.000 0.0323
FLOOR 1 LOBBY HALL AHU-1 0.000000 1.2000 0.000305 22.30 0.0068 1.0000 0.0068 1.000 0.0068
FLOOR 1 LOBBY TOILET AHU-1 0.000000 0.2700 0.000000 5.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 LOCKER ROOM AHU-1 0.000000 9.9010 0.000686 61.32 0.0421 1.0000 0.0421 1.000 0.0421
FLOOR 1 LOCKER ROOM HALL AHU-1 0.000000 2.4800 0.000305 46.08 0.0140 1.0000 0.0140 1.000 0.0140
FLOOR 1 LOUNGE AHU-1 0.000000 5.4005 0.000686 33.45 0.0229 1.0000 0.0229 1.000 0.0229
FLOOR 1 MED GAS AHU-1 0.000000 0.1120 0.000610 5.20 0.0032 1.0000 0.0032 1.000 0.0032
FLOOR 1 MRI CONTROL ROOM PSZ_MRI_CONTROL 0.000000 3.3603 0.001524 15.61 0.0238 1.0000 0.0238 1.000 0.0238
FLOOR 1 MRI HALL AHU-1 0.000000 0.7350 0.000305 13.66 0.0042 1.0000 0.0042 1.000 0.0042
FLOOR 1 MRI ROOM PSZ_MRI 0.000000 8.8009 0.001524 40.88 0.0623 1.0000 0.0623 1.000 0.0623
FLOOR 1 MRI TOILET AHU-1 0.000000 0.2700 0.000000 5.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 NOURISHMENT AHU-1 0.000000 2.7300 0.000813 16.91 0.0137 1.0000 0.0137 1.000 0.0137
FLOOR 1 NURSE HALL AHU-1 0.000000 2.4800 0.000305 46.08 0.0140 1.0000 0.0140 1.000 0.0140
FLOOR 1 NURSE JANITOR AHU-1 0.000000 0.1080 0.000610 5.02 0.0031 1.0000 0.0031 1.000 0.0031
FLOOR 1 NURSE STATION AHU-1 0.000000 3.9150 0.000813 24.25 0.0197 1.0000 0.0197 1.000 0.0197
FLOOR 1 NURSE TOILET AHU-1 0.000000 0.2700 0.000000 5.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 OFFICE AHU-1 0.000000 2.4152 0.000432 44.87 0.0194 1.0000 0.0194 1.000 0.0194
FLOOR 1 OPERATING ROOM 1 PSZ_OR_1 0.000000 9.2009 0.005588 42.74 0.2388 1.0000 0.2388 1.000 0.2388
FLOOR 1 OPERATING ROOM 2 PSZ_OR_2 0.000000 9.6009 0.005588 44.59 0.2492 1.0000 0.2492 1.000 0.2492
FLOOR 1 OPERATING ROOM 3 PSZ_OR_3 0.000000 9.5209 0.005588 44.22 0.2471 1.0000 0.2471 1.000 0.2471
FLOOR 1 PACU AHU-1 0.000000 2.1602 0.003217 10.03 0.0323 1.0000 0.0323 1.000 0.0323
FLOOR 1 PRE-OP HALL AHU-1 0.000000 2.6400 0.000305 49.05 0.0150 1.0000 0.0150 1.000 0.0150
FLOOR 1 PRE-OP ROOM 1 AHU-1 0.000000 1.8902 0.002963 17.56 0.0520 1.0000 0.0520 1.000 0.0520
FLOOR 1 PRE-OP ROOM 2 AHU-1 0.000000 3.3803 0.002963 31.40 0.0931 1.0000 0.0931 1.000 0.0931
FLOOR 1 PRE-OP TOILET AHU-1 0.000000 0.2700 0.000000 5.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 PROCEDURE ROOM AHU-1 0.000000 5.7006 0.004064 26.48 0.1076 1.0000 0.1076 1.000 0.1076
FLOOR 1 RECEPTION AHU-1 0.000000 15.2715 0.001067 47.29 0.0504 1.0000 0.0504 1.000 0.0504
FLOOR 1 RECEPTION HALL AHU-1 0.000000 0.6400 0.000305 11.89 0.0036 1.0000 0.0036 1.000 0.0036
FLOOR 1 RECOVERY ROOM AHU-1 0.000000 10.8011 0.003217 50.17 0.1614 1.0000 0.1614 1.000 0.1614
FLOOR 1 SCHEDULING AHU-1 0.000000 0.5951 0.000432 11.06 0.0048 1.0000 0.0048 1.000 0.0048
FLOOR 1 SCRUB AHU-1 0.000000 0.4200 0.000305 7.80 0.0024 1.0000 0.0024 1.000 0.0024
FLOOR 1 SOIL AHU-1 0.000000 2.5202 0.001524 11.71 0.0178 1.0000 0.0178 1.000 0.0178
FLOOR 1 SOIL HOLD AHU-1 0.000000 1.1201 0.001524 5.20 0.0079 1.0000 0.0079 1.000 0.0079
FLOOR 1 SOIL WORK AHU-1 0.000000 3.6004 0.001524 16.72 0.0255 1.0000 0.0255 1.000 0.0255
FLOOR 1 STEP DOWN AHU-1 0.000000 6.0006 0.003217 27.87 0.0897 1.0000 0.0897 1.000 0.0897
FLOOR 1 STERILE HALL AHU-1 0.000000 3.0800 0.000305 57.23 0.0174 1.0000 0.0174 1.000 0.0174
FLOOR 1 STERILE STORAGE AHU-1 0.000000 0.7920 0.000610 36.79 0.0224 1.0000 0.0224 1.000 0.0224
FLOOR 1 STORAGE AHU-1 0.000000 1.8400 0.000610 85.47 0.0521 1.0000 0.0521 1.000 0.0521
FLOOR 1 SUB-STERILE AHU-1 0.000000 0.9800 0.000305 18.21 0.0056 1.0000 0.0056 1.000 0.0056
FLOOR 1 UTILITY HALL AHU-1 0.000000 1.2800 0.000305 23.78 0.0072 1.0000 0.0072 1.000 0.0072
FLOOR 1 UTILITY JANITOR AHU-1 0.000000 0.0840 0.000610 3.90 0.0024 1.0000 0.0024 1.000 0.0024
FLOOR 1 UTILITY ROOM AHU-1 0.000000 0.7200 0.000610 33.45 0.0204 1.0000 0.0204 1.000 0.0204
FLOOR 1 VESTIBULE AHU-1 0.000000 0.3600 0.000305 6.69 0.0020 1.0000 0.0020 1.000 0.0020
FLOOR 2 CONFERENCE AHU-2 0.000000 16.8016 0.001575 31.22 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 CONFERENCE TOILET AHU-2 0.000000 0.3200 0.000000 5.95 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 DICTATION AHU-2 0.000000 0.3500 0.000432 6.50 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 1 AHU-2 0.000000 7.2007 0.001524 33.45 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 2 AHU-2 0.000000 10.8011 0.001524 50.17 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 3 AHU-2 0.000000 14.4014 0.001524 66.89 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 4 AHU-2 0.000000 1.6802 0.001524 7.80 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 5 AHU-2 0.000000 7.0007 0.001524 32.52 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 6 AHU-2 0.000000 4.5004 0.001524 20.90 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 7 AHU-2 0.000000 15.8415 0.001524 73.58 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 8 AHU-2 0.000000 5.4005 0.001524 25.08 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 9 AHU-2 0.000000 7.9208 0.001524 36.79 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM HALL 1 AHU-2 0.000000 0.9000 0.000305 16.72 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM HALL 2 AHU-2 0.000000 0.9000 0.000305 16.72 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM HALL 3 AHU-2 0.000000 0.9000 0.000305 16.72 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM HALL 4 AHU-2 0.000000 0.9900 0.000305 18.39 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM HALL 5 AHU-2 0.000000 0.9900 0.000305 18.39 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM HALL 6 AHU-2 0.000000 0.9900 0.000305 18.39 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 JANITOR AHU-2 0.000000 0.1260 0.000610 5.85 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 LOUNGE AHU-2 0.000000 1.2001 0.000686 7.43 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 NURSE STATION 1 AHU-2 0.000000 2.2500 0.000813 13.94 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 NURSE STATION 2 AHU-2 0.000000 2.7000 0.000813 16.72 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 OFFICE AHU-2 0.000000 2.8003 0.000432 52.03 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 OFFICE HALL AHU-2 0.000000 2.2200 0.000305 41.25 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 RECEPTION AHU-2 0.000000 29.5229 0.001067 91.42 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 RECEPTION HALL AHU-2 0.000000 2.8200 0.000305 52.40 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 RECEPTION TOILET AHU-2 0.000000 0.6300 0.000000 11.71 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 SCHEDULING 1 AHU-2 0.000000 1.6202 0.000432 30.10 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 SCHEDULING 2 AHU-2 0.000000 1.7102 0.000432 31.77 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 STORAGE 1 AHU-2 0.000000 0.1120 0.000610 5.20 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 STORAGE 2 AHU-2 0.000000 0.2400 0.000610 11.15 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 STORAGE 3 AHU-2 0.000000 0.2880 0.000610 13.38 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 UTILITY AHU-2 0.000000 0.2520 0.000610 11.71 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 WORK AHU-2 0.000000 8.4508 0.000432 157.01 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 WORK HALL AHU-2 0.000000 4.1700 0.000305 77.48 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 WORK TOILET AHU-2 0.000000 0.2700 0.000000 5.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 X-RAY PSZ_XRAY 0.000000 18.0018 0.001524 83.61 0.1274 1.0000 0.1274 1.000 0.1274
FLOOR 3 DRESSING ROOM AHU-3 0.000000 0.2100 0.000432 3.90 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 ELEVATOR HALL AHU-3 0.000000 1.8500 0.000305 34.37 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 HUMID AHU-3 0.000000 0.5401 0.000432 10.03 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 JANITOR AHU-3 0.000000 0.1260 0.000610 5.85 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 LOCKER AHU-3 0.000000 1.8002 0.000686 11.15 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 LOUNGE AHU-3 0.000000 11.3861 0.000686 70.51 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 LOUNGE TOILET AHU-3 0.000000 0.9600 0.000000 17.84 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 MECHANICAL AHU-3 0.000000 0.5250 0.000000 32.52 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 MECHANICAL HALL AHU-3 0.000000 1.5000 0.000305 27.87 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 OFFICE AHU-3 0.000000 15.1815 0.000432 282.05 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 OFFICE HALL AHU-3 0.000000 4.1700 0.000305 77.48 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 OFFICE TOILET AHU-3 0.000000 0.2700 0.000000 5.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 PHYSICAL THERAPY 1 AHU-3 0.000000 26.0025 0.001524 120.77 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 PHYSICAL THERAPY 2 AHU-3 0.000000 11.8412 0.001524 55.00 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 PHYSICAL THERAPY TOILET AHU-3 0.000000 0.4200 0.000000 7.80 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 STORAGE 1 AHU-3 0.000000 0.2160 0.000610 10.03 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 STORAGE 2 AHU-3 0.000000 0.1680 0.000610 7.80 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 TREATMENT AHU-3 0.000000 9.5209 0.001524 44.22 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 UNDEVELOPED 1 AHU-3 0.000000 4.5360 0.000610 210.70 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 UNDEVELOPED 2 AHU-3 0.000000 2.3040 0.000610 107.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 UTILITY AHU-3 0.000000 0.4320 0.000610 20.07 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 WORK AHU-3 0.000000 2.8703 0.000432 53.33 0.0000 1.0000 0.0000 1.000 0.0000
NE STAIR AHU-2 0.000000 0.8400 0.000305 15.61 0.0000 1.0000 0.0000 1.000 0.0000
NW ELEVATOR AHU-2 0.000000 0.2100 0.000000 13.01 0.0000 1.0000 0.0000 1.000 0.0000
NW STAIR AHU-2 0.000000 0.9600 0.000305 17.84 0.0000 1.0000 0.0000 1.000 0.0000
SW STAIR AHU-2 0.000000 0.4800 0.000305 8.92 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
AHU-1 0.000000 115.28 0.000984 1082.4133 1.0656 1.0656 1.0656
AHU-2   0.00 0.000802 1187.1150 0.0000 0.0000 0.0000
AHU-3   0.00 0.000662 1215.3576 0.0000 0.0000 0.0000
PSZ_CAFE 0.000000 42.00 0.004724 39.0193 0.1843 0.1843 0.1843
PSZ_ELEVATOR 0.000000 0.14 0.000000 8.4542 0.0000 0.0000 0.0000
PSZ_MRI_CONTROL 0.000000 3.36 0.001524 15.6077 0.0238 0.0238 0.0238
PSZ_MRI 0.000000 8.80 0.001524 40.8773 0.0623 0.0623 0.0623
PSZ_OR_1 0.000000 9.20 0.005588 42.7354 0.2388 0.2388 0.2388
PSZ_OR_2 0.000000 9.60 0.005588 44.5935 0.2492 0.2492 0.2492
PSZ_OR_3 0.000000 9.52 0.005588 44.2218 0.2471 0.2471 0.2471
PSZ_XRAY 0.000000 18.00 0.001524 83.6127 0.1274 0.1274 0.1274


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
FLOOR 1 ANESTHESIA AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0654 0.0654 0.0654 No 0.0153 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 BIO HAZ AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0222 0.0222 0.0044 No 0.0032 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 CAFE PSZ_CAFE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3593 0.3593 0.3593 No 0.1843 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 CLEAN AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0730 0.0730 0.0730 No 0.0178 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 CLEAN WORK AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0914 0.0914 0.0914 No 0.0234 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 DICTATION AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0549 0.0549 0.0110 No 0.0051 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 DRESSING ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0300 0.0300 0.0060 No 0.0018 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 ELECTRICAL ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0684 0.0684 0.0137 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 ELEVATOR PUMP ROOM PSZ_ELEVATOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0966 0.0966 0.0966 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 HUMID AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0272 0.0272 0.0054 No 0.0022 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 IT HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0497 0.0497 0.0099 No 0.0040 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 IT ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0477 0.0477 0.0095 No 0.0045 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOBBY AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3534 0.3534 0.0707 No 0.0323 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOBBY HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0907 0.0907 0.0181 No 0.0068 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOBBY TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0292 0.0292 0.0292 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOCKER ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3393 0.3393 0.0679 No 0.0421 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOCKER ROOM HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1531 0.1531 0.0306 No 0.0140 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOUNGE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1848 0.1848 0.0370 No 0.0229 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MED GAS AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0366 0.0366 0.0073 No 0.0032 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI CONTROL ROOM PSZ_MRI_CONTROL AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.1939 0.1939 0.1939 No 0.0238 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0607 0.0607 0.0121 No 0.0042 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI ROOM PSZ_MRI AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4648 0.4648 0.4648 No 0.0623 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0253 0.0253 0.0253 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NOURISHMENT AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0962 0.0962 0.0192 No 0.0137 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1704 0.1704 0.0341 No 0.0140 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE JANITOR AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0215 0.0215 0.0043 No 0.0031 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE STATION AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1273 0.1273 0.0255 No 0.0197 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0243 0.0243 0.0243 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OFFICE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1711 0.1711 0.0342 No 0.0194 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OPERATING ROOM 1 PSZ_OR_1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.7236 0.7236 0.7236 No 0.2388 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OPERATING ROOM 2 PSZ_OR_2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.7551 0.7551 0.7551 No 0.2492 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OPERATING ROOM 3 PSZ_OR_3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.7488 0.7488 0.7488 No 0.2471 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PACU AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0645 0.0645 0.0645 No 0.0323 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1748 0.1748 0.0350 No 0.0150 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP ROOM 1 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0892 0.0892 0.0892 No 0.0520 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP ROOM 2 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1595 0.1595 0.1595 No 0.0931 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0247 0.0247 0.0247 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PROCEDURE ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3362 0.3362 0.3362 No 0.1076 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 RECEPTION AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2700 0.2700 0.0540 No 0.0504 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 RECEPTION HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0463 0.0463 0.0093 No 0.0036 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 RECOVERY ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3329 0.3329 0.2896 No 0.1614 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SCHEDULING AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0524 0.0524 0.0105 No 0.0048 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SCRUB AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0315 0.0315 0.0063 No 0.0024 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SOIL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0730 0.0730 0.0730 No 0.0178 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SOIL HOLD AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0340 0.0340 0.0340 No 0.0079 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SOIL WORK AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0969 0.0969 0.0969 No 0.0255 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STEP DOWN AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2123 0.2123 0.1465 No 0.0897 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STERILE HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1959 0.1959 0.0392 No 0.0174 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STERILE STORAGE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1103 0.1103 0.0221 No 0.0224 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STORAGE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3399 0.3399 0.0680 No 0.0521 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SUB-STERILE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1020 0.1020 0.0204 No 0.0056 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 UTILITY HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1790 0.1790 0.0358 No 0.0072 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 UTILITY JANITOR AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0169 0.0169 0.0034 No 0.0024 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 UTILITY ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1447 0.1447 0.0289 No 0.0204 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 VESTIBULE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0416 0.0416 0.0083 No 0.0020 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 CONFERENCE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2514 0.2514 0.0882 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 CONFERENCE TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0275 0.0275 0.0275 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 DICTATION AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0330 0.0330 0.0099 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2599 0.2599 0.1326 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2548 0.2548 0.2548 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 3 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3398 0.3398 0.3398 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 4 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0505 0.0505 0.0323 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 5 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2532 0.2532 0.1747 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 6 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1188 0.1188 0.1116 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 7 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3738 0.3738 0.3738 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 8 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1437 0.1437 0.1337 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 9 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1976 0.1976 0.1976 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0764 0.0764 0.0229 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0763 0.0763 0.0229 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 3 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0737 0.0737 0.0221 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 4 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0801 0.0801 0.0240 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 5 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0828 0.0828 0.0248 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 6 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0824 0.0824 0.0247 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 JANITOR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0313 0.0313 0.0094 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 LOUNGE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0476 0.0476 0.0143 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 NURSE STATION 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0750 0.0750 0.0225 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 NURSE STATION 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0906 0.0906 0.0272 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 OFFICE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3332 0.3332 0.1000 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 OFFICE HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1771 0.1771 0.0531 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 RECEPTION AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5440 0.5440 0.1752 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 RECEPTION HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2356 0.2356 0.0707 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 RECEPTION TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0505 0.0505 0.0505 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 SCHEDULING 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1244 0.1244 0.0373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 SCHEDULING 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1324 0.1324 0.0397 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 STORAGE 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0225 0.0225 0.0068 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 STORAGE 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0420 0.0420 0.0126 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 STORAGE 3 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0518 0.0518 0.0155 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 UTILITY AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0751 0.0751 0.0225 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 WORK AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5549 0.5549 0.1665 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 WORK HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3350 0.3350 0.1005 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 WORK TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0247 0.0247 0.0247 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 X-RAY PSZ_XRAY AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.0673 1.0673 1.0673 No 0.1274 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 DRESSING ROOM AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0238 0.0238 0.0071 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 ELEVATOR HALL AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1274 0.1274 0.0382 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 HUMID AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0552 0.0552 0.0166 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 JANITOR AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0312 0.0312 0.0093 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 LOCKER AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0737 0.0737 0.0221 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 LOUNGE AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4202 0.4202 0.1260 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 LOUNGE TOILET AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0859 0.0859 0.0859 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 MECHANICAL AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3654 0.3654 0.1096 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 MECHANICAL HALL AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1321 0.1321 0.0396 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 OFFICE AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1497 1.1497 0.3449 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 OFFICE HALL AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3298 0.3298 0.0989 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 OFFICE TOILET AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0250 0.0250 0.0250 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 PHYSICAL THERAPY 1 AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7678 0.7678 0.5297 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 PHYSICAL THERAPY 2 AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2794 0.2794 0.2319 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 PHYSICAL THERAPY TOILET AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0372 0.0372 0.0372 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 STORAGE 1 AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0418 0.0418 0.0418 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 STORAGE 2 AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0343 0.0343 0.0103 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 TREATMENT AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2384 0.2384 0.1931 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 UNDEVELOPED 1 AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9304 0.9304 0.2791 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 UNDEVELOPED 2 AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4882 0.4882 0.1465 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 UTILITY AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0738 0.0738 0.0227 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 WORK AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3779 0.3779 0.1134 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NE STAIR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2024 0.2024 0.0607 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NW ELEVATOR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1681 0.1681 0.0504 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NW STAIR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2341 0.2341 0.0702 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
SW STAIR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1216 0.1216 0.0365 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
AHU-1 5.5424 5.5424 5.5424 2.3850 1.0656 1.0000
AHU-2 6.4494 6.0520 6.4494 3.1847 0.0000 1.0000
AHU-3 6.0884 5.7700 6.0884 2.5291 0.0000 1.0000
PSZ_CAFE 0.3593 0.3593 0.3593 0.3593 0.1843 1.0000
PSZ_ELEVATOR 0.0966 0.0966 0.0966 0.0966 0.0000 1.0000
PSZ_MRI_CONTROL 0.1939 0.1939 0.1939 0.1939 0.0238 1.0000
PSZ_MRI 0.4648 0.4648 0.4648 0.4648 0.0623 1.0000
PSZ_OR_1 0.7236 0.7236 0.7236 0.7236 0.2388 1.0000
PSZ_OR_2 0.7551 0.7551 0.7551 0.7551 0.2492 1.0000
PSZ_OR_3 0.7488 0.7488 0.7488 0.7488 0.2471 1.0000
PSZ_XRAY 1.0673 1.0673 1.0673 1.0673 0.1274 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
FLOOR 1 ANESTHESIA AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0654 0.0654 0.0654 No 0.0153 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 BIO HAZ AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0111 0.0111 0.0044 No 0.0032 0.5143 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 CAFE PSZ_CAFE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3593 0.3593 0.3593 No 0.1843 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 CLEAN AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0730 0.0730 0.0730 No 0.0178 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 CLEAN WORK AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0914 0.0914 0.0914 No 0.0234 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 DICTATION AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0275 0.0275 0.0110 No 0.0051 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 DRESSING ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0150 0.0150 0.0060 No 0.0018 0.1943 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 ELECTRICAL ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0342 0.0342 0.0137 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 ELEVATOR PUMP ROOM PSZ_ELEVATOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0966 0.0966 0.0966 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 HUMID AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0136 0.0136 0.0054 No 0.0022 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 IT HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0248 0.0248 0.0099 No 0.0040 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 IT ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0239 0.0239 0.0095 No 0.0045 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOBBY AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1767 0.1767 0.0707 No 0.0323 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOBBY HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0453 0.0453 0.0181 No 0.0068 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOBBY TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0292 0.0292 0.0292 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOCKER ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1696 0.1696 0.0679 No 0.0421 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOCKER ROOM HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0765 0.0765 0.0306 No 0.0140 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOUNGE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0924 0.0924 0.0370 No 0.0229 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MED GAS AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0183 0.0183 0.0073 No 0.0032 0.1088 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI CONTROL ROOM PSZ_MRI_CONTROL AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.1939 0.1939 0.1939 No 0.0238 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0303 0.0303 0.0121 No 0.0042 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI ROOM PSZ_MRI AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4648 0.4648 0.4648 No 0.0623 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0253 0.0253 0.0253 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NOURISHMENT AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0481 0.0481 0.0192 No 0.0137 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0852 0.0852 0.0341 No 0.0140 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE JANITOR AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0107 0.0107 0.0043 No 0.0031 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE STATION AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0636 0.0636 0.0255 No 0.0197 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0243 0.0243 0.0243 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OFFICE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0855 0.0855 0.0342 No 0.0194 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OPERATING ROOM 1 PSZ_OR_1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.7236 0.7236 0.7236 No 0.2388 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OPERATING ROOM 2 PSZ_OR_2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.7551 0.7551 0.7551 No 0.2492 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OPERATING ROOM 3 PSZ_OR_3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.7488 0.7488 0.7488 No 0.2471 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PACU AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0645 0.0645 0.0645 No 0.0323 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0874 0.0874 0.0350 No 0.0150 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP ROOM 1 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0892 0.0892 0.0892 No 0.0520 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP ROOM 2 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1595 0.1595 0.1595 No 0.0931 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0247 0.0247 0.0247 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PROCEDURE ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3362 0.3362 0.3362 No 0.1076 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 RECEPTION AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1350 0.1350 0.0540 No 0.0504 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 RECEPTION HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0232 0.0232 0.0093 No 0.0036 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 RECOVERY ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2896 0.2896 0.2896 No 0.1614 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SCHEDULING AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0262 0.0262 0.0105 No 0.0048 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SCRUB AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0157 0.0157 0.0063 No 0.0024 0.7324 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SOIL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0730 0.0730 0.0730 No 0.0178 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SOIL HOLD AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0340 0.0340 0.0340 No 0.0079 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SOIL WORK AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0969 0.0969 0.0969 No 0.0255 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STEP DOWN AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1465 0.1465 0.1465 No 0.0897 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STERILE HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0980 0.0980 0.0392 No 0.0174 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STERILE STORAGE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0552 0.0552 0.0221 No 0.0224 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STORAGE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1699 0.1699 0.0680 No 0.0521 0.2221 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SUB-STERILE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0510 0.0510 0.0204 No 0.0056 0.1404 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 UTILITY HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0895 0.0895 0.0358 No 0.0072 0.0970 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 UTILITY JANITOR AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0084 0.0084 0.0034 No 0.0024 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 UTILITY ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0723 0.0723 0.0289 No 0.0204 0.3016 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 VESTIBULE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0208 0.0208 0.0083 No 0.0020 0.2430 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 CONFERENCE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1257 0.1257 0.0882 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 CONFERENCE TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0275 0.0275 0.0275 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 DICTATION AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0165 0.0165 0.0099 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1326 0.1326 0.1326 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2548 0.2548 0.2548 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 3 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3398 0.3398 0.3398 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 4 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0323 0.0323 0.0323 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 5 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1747 0.1747 0.1747 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 6 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1116 0.1116 0.1116 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 7 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3738 0.3738 0.3738 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 8 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1337 0.1337 0.1337 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 9 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1976 0.1976 0.1976 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0382 0.0382 0.0229 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0381 0.0381 0.0229 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 3 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0368 0.0368 0.0221 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 4 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0401 0.0401 0.0240 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 5 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0414 0.0414 0.0248 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 6 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0412 0.0412 0.0247 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 JANITOR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0156 0.0156 0.0094 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 LOUNGE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0238 0.0238 0.0143 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 NURSE STATION 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0375 0.0375 0.0225 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 NURSE STATION 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0453 0.0453 0.0272 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 OFFICE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1666 0.1666 0.1000 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 OFFICE HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0886 0.0886 0.0531 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 RECEPTION AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2720 0.2720 0.1752 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 RECEPTION HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1178 0.1178 0.0707 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 RECEPTION TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0505 0.0505 0.0505 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 SCHEDULING 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0622 0.0622 0.0373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 SCHEDULING 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0662 0.0662 0.0397 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 STORAGE 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0113 0.0113 0.0068 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 STORAGE 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0210 0.0210 0.0126 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 STORAGE 3 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0259 0.0259 0.0155 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 UTILITY AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0375 0.0375 0.0225 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 WORK AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2775 0.2775 0.1665 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 WORK HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1675 0.1675 0.1005 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 WORK TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0247 0.0247 0.0247 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 X-RAY PSZ_XRAY AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.0673 1.0673 1.0673 No 0.1274 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 DRESSING ROOM AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0119 0.0119 0.0071 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 ELEVATOR HALL AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0637 0.0637 0.0382 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 HUMID AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0276 0.0276 0.0166 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 JANITOR AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0156 0.0156 0.0093 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 LOCKER AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0369 0.0369 0.0221 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 LOUNGE AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2101 0.2101 0.1260 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 LOUNGE TOILET AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0859 0.0859 0.0859 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 MECHANICAL AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1827 0.1827 0.1096 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 MECHANICAL HALL AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0661 0.0661 0.0396 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 OFFICE AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5749 0.5749 0.3449 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 OFFICE HALL AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1649 0.1649 0.0989 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 OFFICE TOILET AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0250 0.0250 0.0250 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 PHYSICAL THERAPY 1 AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5297 0.5297 0.5297 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 PHYSICAL THERAPY 2 AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2319 0.2319 0.2319 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 PHYSICAL THERAPY TOILET AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0372 0.0372 0.0372 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 STORAGE 1 AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0418 0.0418 0.0418 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 STORAGE 2 AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0172 0.0172 0.0103 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 TREATMENT AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1931 0.1931 0.1931 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 UNDEVELOPED 1 AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4652 0.4652 0.2791 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 UNDEVELOPED 2 AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2441 0.2441 0.1465 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 UTILITY AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0369 0.0369 0.0227 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 WORK AHU-3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1889 0.1889 0.1134 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NE STAIR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1012 0.1012 0.0607 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NW ELEVATOR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0840 0.0840 0.0504 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NW STAIR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1170 0.1170 0.0702 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
SW STAIR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0608 0.0608 0.0365 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
AHU-1 3.5281 2.3850 2.3850 2.3850 1.0656 1.0000
AHU-2 4.0309 3.1847 3.1847 3.1847 0.0000 1.0000
AHU-3 3.4511 2.5291 2.5291 2.5291 0.0000 1.0000
PSZ_CAFE 0.3593 0.3593 0.3593 0.3593 0.1843 1.0000
PSZ_ELEVATOR 0.0966 0.0966 0.0966 0.0966 0.0000 1.0000
PSZ_MRI_CONTROL 0.1939 0.1939 0.1939 0.1939 0.0238 1.0000
PSZ_MRI 0.4648 0.4648 0.4648 0.4648 0.0623 1.0000
PSZ_OR_1 0.7236 0.7236 0.7236 0.7236 0.2388 1.0000
PSZ_OR_2 0.7551 0.7551 0.7551 0.7551 0.2492 1.0000
PSZ_OR_3 0.7488 0.7488 0.7488 0.7488 0.2471 1.0000
PSZ_XRAY 1.0673 1.0673 1.0673 1.0673 0.1274 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Total gross floor area [m2] 3804.01
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
FLOOR 1 ANESTHESIA 10.03 10.03 0.00 91.00
FLOOR 1 BIO HAZ 5.20 5.20 0.00 91.00
FLOOR 1 CAFE 39.02 39.02 0.00 91.00
FLOOR 1 CLEAN 11.71 11.71 0.00 91.00
FLOOR 1 CLEAN WORK 15.33 15.33 0.00 91.00
FLOOR 1 DICTATION 11.71 11.71 0.00 79.38
FLOOR 1 DRESSING ROOM 4.18 4.18 0.00 79.38
FLOOR 1 ELECTRICAL ROOM 9.10 9.10 0.00 91.00
FLOOR 1 ELEVATOR PUMP ROOM 8.45 8.45 0.00 91.00
FLOOR 1 HUMID 5.02 5.02 0.00 79.38
FLOOR 1 IT HALL 13.01 13.01 0.00 91.00
FLOOR 1 IT ROOM 10.41 10.41 0.00 79.38
FLOOR 1 LOBBY 57.79 57.79 0.00 91.00
FLOOR 1 LOBBY HALL 22.30 22.30 0.00 91.00
FLOOR 1 LOBBY TOILET 5.02 5.02 0.00 91.00
FLOOR 1 LOCKER ROOM 61.32 61.32 0.00 91.00
FLOOR 1 LOCKER ROOM HALL 46.08 46.08 0.00 91.00
FLOOR 1 LOUNGE 33.45 33.45 0.00 91.00
FLOOR 1 MED GAS 5.20 5.20 0.00 91.00
FLOOR 1 MRI CONTROL ROOM 15.61 15.61 0.00 91.00
FLOOR 1 MRI HALL 13.66 13.66 0.00 91.00
FLOOR 1 MRI ROOM 40.88 40.88 0.00 91.00
FLOOR 1 MRI TOILET 5.02 5.02 0.00 91.00
FLOOR 1 NOURISHMENT 16.91 16.91 0.00 91.00
FLOOR 1 NURSE HALL 46.08 46.08 0.00 91.00
FLOOR 1 NURSE JANITOR 5.02 5.02 0.00 91.00
FLOOR 1 NURSE STATION 24.25 24.25 0.00 91.00
FLOOR 1 NURSE TOILET 5.02 5.02 0.00 91.00
FLOOR 1 OFFICE 44.87 44.87 0.00 79.38
FLOOR 1 OPERATING ROOM 1 42.74 42.74 0.00 91.00
FLOOR 1 OPERATING ROOM 2 44.59 44.59 0.00 91.00
FLOOR 1 OPERATING ROOM 3 44.22 44.22 0.00 91.00
FLOOR 1 PACU 10.03 10.03 0.00 91.00
FLOOR 1 PRE-OP HALL 49.05 49.05 0.00 91.00
FLOOR 1 PRE-OP ROOM 1 17.56 17.56 0.00 91.00
FLOOR 1 PRE-OP ROOM 2 31.40 31.40 0.00 91.00
FLOOR 1 PRE-OP TOILET 5.02 5.02 0.00 91.00
FLOOR 1 PROCEDURE ROOM 26.48 26.48 0.00 91.00
FLOOR 1 RECEPTION 47.29 47.29 0.00 91.00
FLOOR 1 RECEPTION HALL 11.89 11.89 0.00 91.00
FLOOR 1 RECOVERY ROOM 50.17 50.17 0.00 91.00
FLOOR 1 SCHEDULING 11.06 11.06 0.00 79.38
FLOOR 1 SCRUB 7.80 7.80 0.00 91.00
FLOOR 1 SOIL 11.71 11.71 0.00 91.00
FLOOR 1 SOIL HOLD 5.20 5.20 0.00 91.00
FLOOR 1 SOIL WORK 16.72 16.72 0.00 91.00
FLOOR 1 STEP DOWN 27.87 27.87 0.00 91.00
FLOOR 1 STERILE HALL 57.23 57.23 0.00 91.00
FLOOR 1 STERILE STORAGE 36.79 36.79 0.00 91.00
FLOOR 1 STORAGE 85.47 85.47 0.00 91.00
FLOOR 1 SUB-STERILE 18.21 18.21 0.00 91.00
FLOOR 1 UTILITY HALL 23.78 23.78 0.00 91.00
FLOOR 1 UTILITY JANITOR 3.90 3.90 0.00 91.00
FLOOR 1 UTILITY ROOM 33.45 33.45 0.00 91.00
FLOOR 1 VESTIBULE 6.69 6.69 0.00 91.00
FLOOR 2 CONFERENCE 31.22 31.22 0.00 69.65
FLOOR 2 CONFERENCE TOILET 5.95 5.95 0.00 91.00
FLOOR 2 DICTATION 6.50 6.50 0.00 79.38
FLOOR 2 EXAM 1 33.45 33.45 0.00 91.00
FLOOR 2 EXAM 2 50.17 50.17 0.00 91.00
FLOOR 2 EXAM 3 66.89 66.89 0.00 91.00
FLOOR 2 EXAM 4 7.80 7.80 0.00 91.00
FLOOR 2 EXAM 5 32.52 32.52 0.00 91.00
FLOOR 2 EXAM 6 20.90 20.90 0.00 91.00
FLOOR 2 EXAM 7 73.58 73.58 0.00 91.00
FLOOR 2 EXAM 8 25.08 25.08 0.00 91.00
FLOOR 2 EXAM 9 36.79 36.79 0.00 91.00
FLOOR 2 EXAM HALL 1 16.72 16.72 0.00 91.00
FLOOR 2 EXAM HALL 2 16.72 16.72 0.00 91.00
FLOOR 2 EXAM HALL 3 16.72 16.72 0.00 91.00
FLOOR 2 EXAM HALL 4 18.39 18.39 0.00 91.00
FLOOR 2 EXAM HALL 5 18.39 18.39 0.00 91.00
FLOOR 2 EXAM HALL 6 18.39 18.39 0.00 91.00
FLOOR 2 JANITOR 5.85 5.85 0.00 91.00
FLOOR 2 LOUNGE 7.43 7.43 0.00 91.00
FLOOR 2 NURSE STATION 1 13.94 13.94 0.00 91.00
FLOOR 2 NURSE STATION 2 16.72 16.72 0.00 91.00
FLOOR 2 OFFICE 52.03 52.03 0.00 79.38
FLOOR 2 OFFICE HALL 41.25 41.25 0.00 91.00
FLOOR 2 RECEPTION 91.42 91.42 0.00 91.00
FLOOR 2 RECEPTION HALL 52.40 52.40 0.00 91.00
FLOOR 2 RECEPTION TOILET 11.71 11.71 0.00 91.00
FLOOR 2 SCHEDULING 1 30.10 30.10 0.00 79.38
FLOOR 2 SCHEDULING 2 31.77 31.77 0.00 79.38
FLOOR 2 STORAGE 1 5.20 5.20 0.00 91.00
FLOOR 2 STORAGE 2 11.15 11.15 0.00 91.00
FLOOR 2 STORAGE 3 13.38 13.38 0.00 91.00
FLOOR 2 UTILITY 11.71 11.71 0.00 91.00
FLOOR 2 WORK 157.01 157.01 0.00 79.38
FLOOR 2 WORK HALL 77.48 77.48 0.00 91.00
FLOOR 2 WORK TOILET 5.02 5.02 0.00 91.00
FLOOR 2 X-RAY 83.61 83.61 0.00 91.00
FLOOR 3 DRESSING ROOM 3.90 3.90 0.00 79.38
FLOOR 3 ELEVATOR HALL 34.37 34.37 0.00 91.00
FLOOR 3 HUMID 10.03 10.03 0.00 79.38
FLOOR 3 JANITOR 5.85 5.85 0.00 91.00
FLOOR 3 LOCKER 11.15 11.15 0.00 91.00
FLOOR 3 LOUNGE 70.51 70.51 0.00 91.00
FLOOR 3 LOUNGE TOILET 17.84 17.84 0.00 91.00
FLOOR 3 MECHANICAL 32.52 32.52 0.00 91.00
FLOOR 3 MECHANICAL HALL 27.87 27.87 0.00 91.00
FLOOR 3 OFFICE 282.05 282.05 0.00 79.38
FLOOR 3 OFFICE HALL 77.48 77.48 0.00 91.00
FLOOR 3 OFFICE TOILET 5.02 5.02 0.00 91.00
FLOOR 3 PHYSICAL THERAPY 1 120.77 120.77 0.00 91.00
FLOOR 3 PHYSICAL THERAPY 2 55.00 55.00 0.00 91.00
FLOOR 3 PHYSICAL THERAPY TOILET 7.80 7.80 0.00 91.00
FLOOR 3 STORAGE 1 10.03 10.03 0.00 91.00
FLOOR 3 STORAGE 2 7.80 7.80 0.00 91.00
FLOOR 3 TREATMENT 44.22 44.22 0.00 91.00
FLOOR 3 UNDEVELOPED 1 210.70 210.70 0.00 91.00
FLOOR 3 UNDEVELOPED 2 107.02 107.02 0.00 91.00
FLOOR 3 UTILITY 20.07 20.07 0.00 91.00
FLOOR 3 WORK 53.33 53.33 0.00 79.38
NE STAIR 15.61 15.61 0.00 91.00
NW ELEVATOR 13.01 13.01 0.00 91.00
NW STAIR 17.84 17.84 0.00 91.00
SW STAIR 8.92 8.92 0.00 91.00
Totals 3804.01 3804.01 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 339.83
Number of hours cooling loads not met 2557.33
Number of hours not met 2897.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.01 958.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 197.59 92586.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1415.52 138442.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 626.08 41298.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 237.86 15116.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLift 135.78 6475.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLightsFan 15.33 486.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 1190.14 62583.90 188.37 9905.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 517.72 36543.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.87 252.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 0.81 9892.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 93.72 10458.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1341.24 4140.12
Natural Gas 188.37 479.68
Additional 0.00 0.00
Total 1529.62 4619.80


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 164.58
Space Heating 0.00
Space Cooling 372.11
Fans (All) 136.10
Service Water Heating 0.00
Receptacle Equipment 352.59
Miscellaneous (All) 1088.36
Subtotal 1088.36


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 51.94
Service Water Heating 24.64
Miscellaneous (All) 126.10
Subtotal 126.10


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 13.55
Space Heating 4.28
Space Cooling 30.64
Fans (All) 11.21
Service Water Heating 2.03
Receptacle Equipment 33.11
Miscellaneous 5.19


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 154. 3744.
ELEVATOR_STANDBY_SCH 8177. 8760.
FLOOR 1 ANESTHESIA WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 ANESTHESIA WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 MRI CONTROL ROOM WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 MRI CONTROL ROOM WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 MRI ROOM WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 MRI ROOM WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 OPERATING ROOM 1 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 OPERATING ROOM 1 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 OPERATING ROOM 2 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 OPERATING ROOM 2 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 OPERATING ROOM 3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 OPERATING ROOM 3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 PACU WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 PACU WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 PRE-OP ROOM 1 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 PRE-OP ROOM 1 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 PRE-OP ROOM 2 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 PRE-OP ROOM 2 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 PROCEDURE ROOM WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 PROCEDURE ROOM WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 RECOVERY ROOM WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 RECOVERY ROOM WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 STEP DOWN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 STEP DOWN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 2 X-RAY WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 2 X-RAY WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 3 PHYSICAL THERAPY 1 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 3 PHYSICAL THERAPY 1 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 3 PHYSICAL THERAPY 2 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 3 PHYSICAL THERAPY 2 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
AHU-1_OAMINOAFRACSCHEDULE 2891. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
EXTERIOR_LGT_189_1 6932. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 3871. 8760.
BLDG_SWH_SCH 2170. 7965.
WORK_EFF_SCH 0. 0.
INFIL_SCH 5718. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_DOOR_OPENING_SCH 2935. 3380.
FAN_SCH 4056. 4056.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4056. 4056.
MINOA_SCHED 8760. 8760.
OR_MINSA_SCHED 4747. 8760.
LTG_SCH_OFFICE 3889. 8760.
LTG_SCH_OPERATION 3889. 8760.
LTG_SCH_FLOOR_1_OFFICE 3889. 8760.
LTG_SCH_LOUNGE 3889. 8760.
LTG_SCH_FLOOR_1_STERILE_STORAGE 3889. 8760.
LTG_SCH_PATIENT 3889. 8760.
LTG_SCH_NURSE 3889. 8760.
LTG_SCH_EXAM 3889. 8760.
LTG_SCH_ANESTHESIA 3889. 8760.
LTG_SCH_RADIOLOGY 3889. 8760.
LTG_SCH_PHY_THERAPY 3889. 8760.
LTG_SCH_UTILITY 3889. 8760.
LTG_SCH_SOILED 3889. 8760.
LTG_SCH_CLEAN 3889. 8760.
LTG_SCH_DINING 3889. 8760.
LTG_SCH_LOBBY 3889. 8760.
LTG_SCH_STORAGE 3889. 8760.
LTG_SCH_RECOVERY 3889. 8760.
LTG_SCH_CORRIDOR 3889. 8760.
LTG_SCH_TOILET 3889. 8760.
LTG_SCH_PROCEDURE 3889. 8760.
LTG_SCH_CONFERENCE 3889. 8760.
LTG_SCH_RECEPTION 3889. 8760.
BLDG_EQUIP_SCH 5293. 8760.
BLDG_EQUIP_SCH_BASE 5344. 8760.
BLDG_OCC_SCH 3035. 4745.
MEETINGROOM_OCC_W_SB_SCH 2237. 3601.
OFFICE_OCC_W_SB_SCH 2528. 4121.
BLDG_OA_SCH 4056. 4056.
BLDG_CAV_SCH 5950. 8760.
BLDG_CAV_SCH_HUMID 6752. 8760.
BLDG_OA_FRAC_SCH 1014. 4056.
FLOOR 2 CONFERENCE_MDP_SCH 0. 0.
FLOOR 1 DICTATION_MDP_SCH 1627. 8136.
FLOOR 1 DRESSING ROOM_MDP_SCH 1627. 8136.
FLOOR 1 HUMID_MDP_SCH 1627. 8136.
FLOOR 1 IT ROOM_MDP_SCH 1627. 8136.
FLOOR 1 OFFICE_MDP_SCH 1627. 8136.
FLOOR 1 SCHEDULING_MDP_SCH 1627. 8136.
FLOOR 2 DICTATION_MDP_SCH 0. 0.
FLOOR 2 OFFICE_MDP_SCH 0. 0.
FLOOR 2 SCHEDULING 1_MDP_SCH 0. 0.
FLOOR 2 SCHEDULING 2_MDP_SCH 0. 0.
FLOOR 2 WORK_MDP_SCH 0. 0.
FLOOR 3 DRESSING ROOM_MDP_SCH 0. 0.
FLOOR 3 HUMID_MDP_SCH 0. 0.
FLOOR 3 OFFICE_MDP_SCH 0. 0.
FLOOR 3 WORK_MDP_SCH 0. 0.
AHU_1 BALANCED EXHAUST FRACTION SCHEDULE 8760. 8760.
AHU_2 BALANCED EXHAUST FRACTION SCHEDULE 3744. 3744.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM FLOOR 1 ANESTHESIA DUAL SP CONTROL January 21.10 365 18.30 365
CLGSETP_SCH_YES_OPTIMUM FLOOR 1 ANESTHESIA DUAL SP CONTROL July 22.20 365 25.00 365
HTGSETP_SCH_YES_OPTIMUM_OFF_W_SB FLOOR 1 DICTATION DUAL SP CONTROL January 21.10 365 18.30 365
CLGSETP_SCH_YES_OPTIMUM_OFF_W_SB FLOOR 1 DICTATION DUAL SP CONTROL July 22.20 365 25.00 365
OR_HTGSETP_SCH FLOOR 1 OPERATING ROOM 1 DUAL SP CONTROL January 18.10 365 18.10 365
OR_CLGSETP_SCH FLOOR 1 OPERATING ROOM 1 DUAL SP CONTROL July 18.60 365 22.20 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
FLOOR 1 ANESTHESIA 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 BIO HAZ 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 CAFE 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 CLEAN 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 CLEAN WORK 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 DICTATION 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 DRESSING ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 HUMID 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 IT HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 IT ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 LOUNGE 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 MED GAS 8747.00 13.00 0.00 0.00 0.00
FLOOR 1 MRI CONTROL ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 NOURISHMENT 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE STATION 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 OFFICE 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 3 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 PACU 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 PROCEDURE ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 RECEPTION 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 RECOVERY ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 SCHEDULING 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 SCRUB 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL HOLD 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL WORK 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 STEP DOWN 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 STERILE HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 STERILE STORAGE 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 STORAGE 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 SUB-STERILE 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY HALL 8758.83 1.17 0.00 0.00 0.00
FLOOR 1 UTILITY JANITOR 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 VESTIBULE 7442.00 866.83 451.17 0.00 0.00
FLOOR 2 CONFERENCE 8758.83 1.17 0.00 0.00 0.00
FLOOR 2 CONFERENCE TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 DICTATION 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 3 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 4 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 5 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 6 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 7 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 8 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 9 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 3 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 4 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 5 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 6 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 JANITOR 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 LOUNGE 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 OFFICE 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 OFFICE HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 3 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 UTILITY 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 WORK 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 WORK HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 WORK TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 X-RAY 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 DRESSING ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 HUMID 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 JANITOR 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 LOCKER 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 LOUNGE 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 LOUNGE TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 MECHANICAL 8616.83 143.17 0.00 0.00 0.00
FLOOR 3 MECHANICAL HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 TREATMENT 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 UTILITY 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 WORK 8751.83 8.17 0.00 0.00 0.00
NE STAIR 8747.83 12.17 0.00 0.00 0.00
NW ELEVATOR 8758.67 1.33 0.00 0.00 0.00
NW STAIR 8749.33 10.67 0.00 0.00 0.00
SW STAIR 8744.50 15.50 0.00 0.00 0.00
Min 7442.00 0.00 0.00 0.00 0.00
Max 8760.00 866.83 451.17 0.00 0.00
Average 8747.08 9.09 3.82 0.00 0.00
Sum 1032155.67 1073.17 451.17 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
FLOOR 1 ANESTHESIA 3276.00 0.00 0.00 0.00 0.00
FLOOR 1 BIO HAZ 0.00 0.00 0.00 0.00 0.00
FLOOR 1 CAFE 121288.00 0.00 0.00 0.00 0.00
FLOOR 1 CLEAN 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 CLEAN WORK 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 DICTATION 0.00 0.00 0.00 0.00 0.00
FLOOR 1 DRESSING ROOM 0.00 0.00 0.00 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 0.00 0.00 0.00 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 0.00 0.00 0.00 0.00 0.00
FLOOR 1 HUMID 0.00 0.00 0.00 0.00 0.00
FLOOR 1 IT HALL 0.00 0.00 0.00 0.00 0.00
FLOOR 1 IT ROOM 0.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY 16035.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY HALL 2772.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM 25161.00 0.00 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 LOUNGE 12759.00 0.00 0.00 0.00 0.00
FLOOR 1 MED GAS 0.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI CONTROL ROOM 9126.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI HALL 0.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI ROOM 22389.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 1 NOURISHMENT 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE HALL 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR 0.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE STATION 9126.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 1 OFFICE 5040.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 1 25161.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 2 25161.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 3 25161.00 0.00 0.00 0.00 0.00
FLOOR 1 PACU 3276.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 1 2772.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 2 9126.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 1 PROCEDURE ROOM 15531.00 0.00 0.00 0.00 0.00
FLOOR 1 RECEPTION 41859.00 0.00 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL 0.00 0.00 0.00 0.00 0.00
FLOOR 1 RECOVERY ROOM 29100.00 0.00 0.00 0.00 0.00
FLOOR 1 SCHEDULING 0.00 0.00 0.00 0.00 0.00
FLOOR 1 SCRUB 0.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL HOLD 2772.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL WORK 9126.00 0.00 0.00 0.00 0.00
FLOOR 1 STEP DOWN 16035.00 0.00 0.00 0.00 0.00
FLOOR 1 STERILE HALL 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 STERILE STORAGE 0.00 0.00 0.00 0.00 0.00
FLOOR 1 STORAGE 2772.00 0.00 0.00 0.00 0.00
FLOOR 1 SUB-STERILE 0.00 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY HALL 2772.00 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY JANITOR 0.00 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 0.00 0.00 0.00 0.00 0.00
FLOOR 1 VESTIBULE 0.00 0.00 0.00 0.00 0.00
FLOOR 2 CONFERENCE 35343.00 0.00 0.00 0.00 0.00
FLOOR 2 CONFERENCE TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 2 DICTATION 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 1 19113.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 2 29100.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 3 38730.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 4 2772.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 5 19113.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 6 12402.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 7 44631.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 8 12759.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 9 21885.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 1 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 2 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 3 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 4 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 5 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 6 0.00 0.00 0.00 0.00 0.00
FLOOR 2 JANITOR 0.00 0.00 0.00 0.00 0.00
FLOOR 2 LOUNGE 2772.00 0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 1 6048.00 0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 2 6048.00 0.00 0.00 0.00 0.00
FLOOR 2 OFFICE 5040.00 0.00 0.00 0.00 0.00
FLOOR 2 OFFICE HALL 3276.00 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION 84167.00 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION HALL 6048.00 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 1 2268.00 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 2 2268.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 1 0.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 2 0.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 3 0.00 0.00 0.00 0.00 0.00
FLOOR 2 UTILITY 0.00 0.00 0.00 0.00 0.00
FLOOR 2 WORK 18606.00 0.00 0.00 0.00 0.00
FLOOR 2 WORK HALL 9630.00 0.00 0.00 0.00 0.00
FLOOR 2 WORK TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 2 X-RAY 51489.00 0.00 0.00 0.00 0.00
FLOOR 3 DRESSING ROOM 0.00 0.00 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 2772.00 0.00 0.00 0.00 0.00
FLOOR 3 HUMID 0.00 0.00 0.00 0.00 0.00
FLOOR 3 JANITOR 0.00 0.00 0.00 0.00 0.00
FLOOR 3 LOCKER 2772.00 0.00 0.00 0.00 0.00
FLOOR 3 LOUNGE 31872.00 0.00 0.00 0.00 0.00
FLOOR 3 LOUNGE TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 3 MECHANICAL 0.00 0.00 0.00 0.00 0.00
FLOOR 3 MECHANICAL HALL 2772.00 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE 34746.00 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE HALL 9630.00 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY 1 75041.00 0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY 2 31872.00 0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 1 0.00 0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 2 0.00 0.00 0.00 0.00 0.00
FLOOR 3 TREATMENT 25161.00 0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 1 12402.00 0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 2 6048.00 0.00 0.00 0.00 0.00
FLOOR 3 UTILITY 0.00 0.00 0.00 0.00 0.00
FLOOR 3 WORK 5040.00 0.00 0.00 0.00 0.00
NE STAIR 0.00 0.00 0.00 0.00 0.00
NW ELEVATOR 0.00 0.00 0.00 0.00 0.00
NW STAIR 0.00 0.00 0.00 0.00 0.00
SW STAIR 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 121288.00 0.00 0.00 0.00 0.00
Average 9827.25 0.00 0.00 0.00 0.00
Sum 1159616.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
FLOOR 1 ANESTHESIA 8749.17 10.83 0.00 0.00 0.00
FLOOR 1 BIO HAZ 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 CAFE 6464.50 2295.50 0.00 0.00 0.00
FLOOR 1 CLEAN 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 CLEAN WORK 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 DICTATION 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 DRESSING ROOM 8458.83 301.17 0.00 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 8681.17 78.83 0.00 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 8664.67 95.33 0.00 0.00 0.00
FLOOR 1 HUMID 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 IT HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 IT ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY 8754.33 5.67 0.00 0.00 0.00
FLOOR 1 LOBBY HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 8719.33 40.67 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM 8744.00 16.00 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 LOUNGE 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 MED GAS 8393.83 366.17 0.00 0.00 0.00
FLOOR 1 MRI CONTROL ROOM 8610.33 149.67 0.00 0.00 0.00
FLOOR 1 MRI HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI ROOM 8636.50 123.50 0.00 0.00 0.00
FLOOR 1 MRI TOILET 8747.50 12.50 0.00 0.00 0.00
FLOOR 1 NOURISHMENT 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE STATION 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 OFFICE 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 3 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 PACU 8759.83 0.17 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 8747.67 12.33 0.00 0.00 0.00
FLOOR 1 PROCEDURE ROOM 8750.83 9.17 0.00 0.00 0.00
FLOOR 1 RECEPTION 8758.83 1.17 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 RECOVERY ROOM 8739.50 20.50 0.00 0.00 0.00
FLOOR 1 SCHEDULING 8753.00 7.00 0.00 0.00 0.00
FLOOR 1 SCRUB 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL HOLD 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL WORK 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 STEP DOWN 8698.83 61.17 0.00 0.00 0.00
FLOOR 1 STERILE HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 STERILE STORAGE 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 STORAGE 8747.83 12.17 0.00 0.00 0.00
FLOOR 1 SUB-STERILE 8752.67 7.33 0.00 0.00 0.00
FLOOR 1 UTILITY HALL 8757.17 2.83 0.00 0.00 0.00
FLOOR 1 UTILITY JANITOR 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 1 VESTIBULE 6156.33 2423.50 180.17 0.00 0.00
FLOOR 2 CONFERENCE 7478.00 1282.00 0.00 0.00 0.00
FLOOR 2 CONFERENCE TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 DICTATION 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 1 7773.83 986.17 0.00 0.00 0.00
FLOOR 2 EXAM 2 8571.50 188.50 0.00 0.00 0.00
FLOOR 2 EXAM 3 8643.00 117.00 0.00 0.00 0.00
FLOOR 2 EXAM 4 8348.83 411.17 0.00 0.00 0.00
FLOOR 2 EXAM 5 8196.17 563.83 0.00 0.00 0.00
FLOOR 2 EXAM 6 8431.00 329.00 0.00 0.00 0.00
FLOOR 2 EXAM 7 8627.00 133.00 0.00 0.00 0.00
FLOOR 2 EXAM 8 8332.17 427.83 0.00 0.00 0.00
FLOOR 2 EXAM 9 8601.00 159.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 3 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 4 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 5 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 6 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 JANITOR 6169.00 2591.00 0.00 0.00 0.00
FLOOR 2 LOUNGE 8749.17 10.83 0.00 0.00 0.00
FLOOR 2 NURSE STATION 1 8719.00 41.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 2 8600.00 160.00 0.00 0.00 0.00
FLOOR 2 OFFICE 7924.00 836.00 0.00 0.00 0.00
FLOOR 2 OFFICE HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION 7256.17 1503.83 0.00 0.00 0.00
FLOOR 2 RECEPTION HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 2 8757.50 2.50 0.00 0.00 0.00
FLOOR 2 STORAGE 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 3 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 UTILITY 8329.33 430.67 0.00 0.00 0.00
FLOOR 2 WORK 8385.83 374.17 0.00 0.00 0.00
FLOOR 2 WORK HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 2 WORK TOILET 8257.33 502.67 0.00 0.00 0.00
FLOOR 2 X-RAY 8241.50 518.50 0.00 0.00 0.00
FLOOR 3 DRESSING ROOM 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 HUMID 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 JANITOR 8228.33 531.67 0.00 0.00 0.00
FLOOR 3 LOCKER 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 LOUNGE 8722.67 37.33 0.00 0.00 0.00
FLOOR 3 LOUNGE TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 MECHANICAL 8496.17 263.83 0.00 0.00 0.00
FLOOR 3 MECHANICAL HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE 8755.50 4.50 0.00 0.00 0.00
FLOOR 3 OFFICE HALL 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY 1 8758.83 1.17 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 1 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 2 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 TREATMENT 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 1 8740.83 19.17 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 2 8712.67 47.33 0.00 0.00 0.00
FLOOR 3 UTILITY 8760.00 0.00 0.00 0.00 0.00
FLOOR 3 WORK 8715.00 45.00 0.00 0.00 0.00
NE STAIR 6604.17 2155.83 0.00 0.00 0.00
NW ELEVATOR 6516.33 2243.67 0.00 0.00 0.00
NW STAIR 6400.33 2359.67 0.00 0.00 0.00
SW STAIR 6218.33 2541.67 0.00 0.00 0.00
Min 6156.33 0.00 0.00 0.00 0.00
Max 8760.00 2591.00 180.17 0.00 0.00
Average 8522.26 236.21 1.53 0.00 0.00
Sum 1005627.17 27872.67 180.17 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
FLOOR 1 ANESTHESIA 3276.00 0.00 0.00 0.00 0.00
FLOOR 1 BIO HAZ 0.00 0.00 0.00 0.00 0.00
FLOOR 1 CAFE 90798.67 30489.33 0.00 0.00 0.00
FLOOR 1 CLEAN 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 CLEAN WORK 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 DICTATION 0.00 0.00 0.00 0.00 0.00
FLOOR 1 DRESSING ROOM 0.00 0.00 0.00 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 0.00 0.00 0.00 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 0.00 0.00 0.00 0.00 0.00
FLOOR 1 HUMID 0.00 0.00 0.00 0.00 0.00
FLOOR 1 IT HALL 0.00 0.00 0.00 0.00 0.00
FLOOR 1 IT ROOM 0.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY 16035.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY HALL 2772.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM 25161.00 0.00 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 LOUNGE 12759.00 0.00 0.00 0.00 0.00
FLOOR 1 MED GAS 0.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI CONTROL ROOM 9085.50 40.50 0.00 0.00 0.00
FLOOR 1 MRI HALL 0.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI ROOM 22183.67 205.33 0.00 0.00 0.00
FLOOR 1 MRI TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 1 NOURISHMENT 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE HALL 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR 0.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE STATION 9126.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 1 OFFICE 5040.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 1 25161.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 2 25161.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 3 25161.00 0.00 0.00 0.00 0.00
FLOOR 1 PACU 3276.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 1 2772.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 2 9126.00 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 1 PROCEDURE ROOM 15531.00 0.00 0.00 0.00 0.00
FLOOR 1 RECEPTION 41859.00 0.00 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL 0.00 0.00 0.00 0.00 0.00
FLOOR 1 RECOVERY ROOM 29100.00 0.00 0.00 0.00 0.00
FLOOR 1 SCHEDULING 0.00 0.00 0.00 0.00 0.00
FLOOR 1 SCRUB 0.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL HOLD 2772.00 0.00 0.00 0.00 0.00
FLOOR 1 SOIL WORK 9126.00 0.00 0.00 0.00 0.00
FLOOR 1 STEP DOWN 16035.00 0.00 0.00 0.00 0.00
FLOOR 1 STERILE HALL 6048.00 0.00 0.00 0.00 0.00
FLOOR 1 STERILE STORAGE 0.00 0.00 0.00 0.00 0.00
FLOOR 1 STORAGE 2772.00 0.00 0.00 0.00 0.00
FLOOR 1 SUB-STERILE 0.00 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY HALL 2772.00 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY JANITOR 0.00 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 0.00 0.00 0.00 0.00 0.00
FLOOR 1 VESTIBULE 0.00 0.00 0.00 0.00 0.00
FLOOR 2 CONFERENCE 34993.67 349.33 0.00 0.00 0.00
FLOOR 2 CONFERENCE TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 2 DICTATION 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 1 19112.50 0.50 0.00 0.00 0.00
FLOOR 2 EXAM 2 29100.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 3 38730.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 4 2772.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 5 19113.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 6 12402.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 7 44631.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 8 12759.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 9 21885.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 1 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 2 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 3 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 4 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 5 0.00 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 6 0.00 0.00 0.00 0.00 0.00
FLOOR 2 JANITOR 0.00 0.00 0.00 0.00 0.00
FLOOR 2 LOUNGE 2772.00 0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 1 6048.00 0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 2 6048.00 0.00 0.00 0.00 0.00
FLOOR 2 OFFICE 5039.17 0.83 0.00 0.00 0.00
FLOOR 2 OFFICE HALL 3276.00 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION 83498.67 668.33 0.00 0.00 0.00
FLOOR 2 RECEPTION HALL 6048.00 0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 1 2268.00 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 2 2268.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 1 0.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 2 0.00 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 3 0.00 0.00 0.00 0.00 0.00
FLOOR 2 UTILITY 0.00 0.00 0.00 0.00 0.00
FLOOR 2 WORK 18605.33 0.67 0.00 0.00 0.00
FLOOR 2 WORK HALL 9630.00 0.00 0.00 0.00 0.00
FLOOR 2 WORK TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 2 X-RAY 49467.50 2021.50 0.00 0.00 0.00
FLOOR 3 DRESSING ROOM 0.00 0.00 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 2772.00 0.00 0.00 0.00 0.00
FLOOR 3 HUMID 0.00 0.00 0.00 0.00 0.00
FLOOR 3 JANITOR 0.00 0.00 0.00 0.00 0.00
FLOOR 3 LOCKER 2772.00 0.00 0.00 0.00 0.00
FLOOR 3 LOUNGE 31853.67 18.33 0.00 0.00 0.00
FLOOR 3 LOUNGE TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 3 MECHANICAL 0.00 0.00 0.00 0.00 0.00
FLOOR 3 MECHANICAL HALL 2772.00 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE 34746.00 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE HALL 9630.00 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY 1 75039.83 1.17 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY 2 31872.00 0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 0.00 0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 1 0.00 0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 2 0.00 0.00 0.00 0.00 0.00
FLOOR 3 TREATMENT 25161.00 0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 1 12402.00 0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 2 6048.00 0.00 0.00 0.00 0.00
FLOOR 3 UTILITY 0.00 0.00 0.00 0.00 0.00
FLOOR 3 WORK 5040.00 0.00 0.00 0.00 0.00
NE STAIR 0.00 0.00 0.00 0.00 0.00
NW ELEVATOR 0.00 0.00 0.00 0.00 0.00
NW STAIR 0.00 0.00 0.00 0.00 0.00
SW STAIR 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 90798.67 30489.33 0.00 0.00 0.00
Average 9540.85 286.41 0.00 0.00 0.00
Sum 1125820.17 33795.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:39:14

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OUTPATIENTHEALTHCARE

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101059E+10 1002.58 01-JAN-08:11 20.53 19.27 72432939.14 81.17 12-JAN-14:09 25.50 19.66
February 0.927187E+09 990.99 05-FEB-16:21 20.55 13.91 65429879.43 81.33 22-FEB-14:00 27.80 14.29
March 0.103807E+10 974.61 03-MAR-04:11 20.77 16.18 77222811.48 78.92 01-MAR-14:20 20.77 16.18
April 0.100305E+10 947.21 23-APR-05:31 23.30 19.98 68567533.09 73.44 10-APR-08:30 23.30 19.98
May 0.111251E+10 931.61 28-MAY-04:21 23.60 22.61 73963543.99 73.44 15-MAY-07:10 23.60 22.61
June 0.112883E+10 933.00 18-JUN-07:11 25.60 22.81 73798302.13 73.45 12-JUN-08:20 25.60 22.81
July 0.117366E+10 899.12 15-JUL-23:51 26.70 24.27 68712820.37 73.44 31-JUL-06:40 26.50 24.22
August 0.123369E+10 949.03 13-AUG-03:41 25.40 23.10 77034634.38 75.43 31-AUG-14:39 32.03 24.60
September 0.122292E+10 931.35 10-SEP-12:31 31.10 24.59 68828563.44 76.99 29-SEP-12:39 30.93 24.21
October 0.124834E+10 973.59 22-OCT-07:01 22.77 20.26 71958957.56 79.01 06-OCT-12:39 22.77 20.26
November 0.112501E+10 1000.13 26-NOV-08:11 19.07 18.48 71449870.02 82.21 07-NOV-14:20 19.07 18.48
December 0.103077E+10 985.75 22-DEC-21:31 22.80 20.70 69963800.85 82.93 04-DEC-14:50 22.80 20.70
                     
Annual Sum or Average 0.132546E+11         0.859364E+09        
Minimum of Months 0.927187E+09 899.12   19.07 13.91 65429879.43 73.44   19.07 14.29
Maximum of Months 0.124834E+10 1002.58   31.10 24.59 77222811.48 82.93   32.03 24.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 85365387.24 73.82 06-JAN-16:40 25.37 22.26 3985620.11 4.27 04-JAN-17:19 25.37 22.26
February 82558258.78 79.91 17-FEB-16:00 26.70 21.75 3695080.16 4.27 14-FEB-17:19 26.70 21.75
March 0.103413E+09 84.84 30-MAR-16:03 25.92 19.59 4466411.73 4.27 08-MAR-17:19 25.92 19.59
April 0.116845E+09 95.16 14-APR-16:00 29.40 24.14 4047951.86 4.27 18-APR-16:19 22.93 14.20
May 0.139922E+09 100.88 18-MAY-15:40 30.37 22.32 4373971.56 4.29 18-MAY-06:10 30.37 22.32
June 0.146260E+09 143.98 15-JUN-06:01 27.20 23.94 4367405.82 4.33 15-JUN-06:10 27.20 23.94
July 0.150474E+09 128.99 21-JUL-06:01 26.78 24.28 4073418.12 4.32 19-JUL-06:10 26.78 24.28
August 0.150269E+09 142.25 01-AUG-06:01 28.30 24.71 4550594.95 4.33 01-AUG-06:10 28.30 24.71
September 0.137081E+09 110.53 22-SEP-06:01 27.80 25.38 4053855.71 4.30 22-SEP-06:10 27.80 25.38
October 0.124935E+09 89.86 03-OCT-16:00 31.10 24.94 4183420.36 4.27 03-OCT-06:19 31.10 24.94
November 0.104023E+09 81.54 30-NOV-15:50 27.70 24.85 4090296.37 4.27 17-NOV-17:19 27.70 24.85
December 90211117.63 81.95 01-DEC-15:20 26.30 19.85 3908758.39 4.27 08-DEC-17:19 25.40 22.62
                     
Annual Sum or Average 0.143136E+10         49796785.14        
Minimum of Months 82558258.78 73.82   25.37 19.59 3695080.16 4.27   22.93 14.20
Maximum of Months 0.150474E+09 143.98   31.10 25.38 4550594.95 4.33   31.10 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.387930E+10 6811.47 20-JAN-07:01 14.90 11.74 0.161842E+10 1960.56 02-JAN-14:30 14.90 11.74
February 0.353677E+10 6405.98 23-FEB-07:01 14.68 12.86 0.146956E+10 1785.89 16-FEB-07:10 14.68 12.86
March 0.408129E+10 6594.04 01-MAR-07:01 13.07 12.09 0.175648E+10 1801.32 13-MAR-13:20 27.80 23.66
April 0.369984E+10 6389.75 19-APR-06:01 15.68 12.27 0.158432E+10 1889.55 14-APR-15:09 15.68 12.27
May 0.394831E+10 5242.31 08-MAY-05:01 23.90 19.12 0.174917E+10 1944.39 31-MAY-13:20 31.50 25.43
June 0.379752E+10 4794.42 10-JUN-04:01 26.02 24.10 0.184643E+10 1981.40 08-JUN-15:00 26.02 24.10
July 0.360508E+10 4441.24 13-JUL-04:01 25.40 23.51 0.178481E+10 2041.81 25-JUL-14:20 31.50 26.30
August 0.399677E+10 4528.95 18-AUG-04:01 27.70 24.78 0.198793E+10 2068.87 22-AUG-13:09 32.52 26.10
September 0.384166E+10 4967.36 23-SEP-04:01 27.80 25.31 0.175744E+10 2073.33 20-SEP-13:39 27.80 25.31
October 0.412394E+10 4914.69 17-OCT-06:03 23.80 18.16 0.175074E+10 2060.41 03-OCT-14:09 23.80 18.16
November 0.395625E+10 5121.72 14-NOV-07:02 18.17 15.21 0.167066E+10 1983.92 10-NOV-14:50 18.17 15.21
December 0.389151E+10 5819.33 13-DEC-07:01 12.48 11.76 0.157893E+10 1854.21 08-DEC-16:10 12.48 11.76
                     
Annual Sum or Average 0.463582E+11         0.205549E+11        
Minimum of Months 0.353677E+10 4441.24   12.48 11.74 0.146956E+10 1785.89   12.48 11.74
Maximum of Months 0.412394E+10 6811.47   27.80 25.31 0.198793E+10 2073.33   32.52 26.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 CLEAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100555E+10 1189.38 26-JAN-04:21 11.10 8.31 83099100.33 85.67 30-JAN-08:09 21.20 20.03
February 0.933502E+09 1172.46 06-FEB-06:01 18.30 14.67 75414751.49 85.66 15-FEB-10:30 24.40 19.86
March 0.108898E+10 1170.54 22-MAR-03:11 14.23 12.78 89916884.09 85.67 07-MAR-08:20 14.23 12.78
April 0.105512E+10 1116.01 19-APR-03:11 15.00 11.82 79950691.17 85.67 17-APR-07:10 15.00 11.82
May 0.114445E+10 1080.65 28-MAY-04:21 23.60 22.61 86165079.49 85.67 22-MAY-07:00 23.60 22.61
June 0.113293E+10 1045.80 25-JUN-06:41 24.82 23.80 85924421.83 85.67 12-JUN-08:20 24.82 23.80
July 0.114010E+10 999.08 16-JUL-01:51 26.70 23.84 79902949.72 85.68 10-JUL-07:40 26.70 23.84
August 0.117915E+10 1066.26 13-AUG-03:41 25.40 23.10 89589003.07 85.67 22-AUG-08:30 29.40 25.36
September 0.111464E+10 1028.20 17-SEP-07:01 24.37 22.87 79765657.85 85.68 25-SEP-06:49 24.40 23.65
October 0.112465E+10 1086.77 22-OCT-07:01 22.77 20.26 82699479.04 85.68 10-OCT-07:10 22.77 20.26
November 0.105066E+10 1156.45 27-NOV-06:01 10.00 8.82 81848620.99 85.67 10-NOV-13:00 10.00 8.82
December 0.101317E+10 1180.16 15-DEC-04:11 8.13 5.63 80363406.62 85.67 11-DEC-08:30 8.13 5.63
                     
Annual Sum or Average 0.129829E+11         0.994640E+09        
Minimum of Months 0.933502E+09 999.08   8.13 5.63 75414751.49 85.66   8.13 5.63
Maximum of Months 0.117915E+10 1189.38   26.70 23.84 89916884.09 85.68   29.40 25.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116993E+10 1446.75 26-JAN-04:21 11.10 8.31 0.108483E+09 112.18 09-JAN-13:00 11.10 8.31
February 0.108632E+10 1417.53 25-FEB-06:01 10.18 7.59 98476899.35 112.18 13-FEB-08:39 10.18 7.59
March 0.127015E+10 1421.86 18-MAR-05:01 19.40 15.66 0.117475E+09 112.18 01-MAR-15:39 19.40 15.66
April 0.122901E+10 1356.28 19-APR-03:11 15.00 11.82 0.104464E+09 112.19 17-APR-08:09 15.00 11.82
May 0.133140E+10 1307.62 28-MAY-04:21 23.60 22.61 0.112651E+09 112.20 15-MAY-08:39 23.60 22.61
June 0.132375E+10 1266.21 25-JUN-06:41 24.82 23.80 0.112373E+09 112.20 26-JUN-08:09 27.98 25.36
July 0.133002E+10 1209.20 16-JUL-01:51 26.70 23.84 0.104486E+09 112.20 31-JUL-09:39 31.13 25.51
August 0.137988E+10 1292.64 13-AUG-03:41 25.40 23.10 0.117171E+09 112.20 07-AUG-08:09 25.40 23.10
September 0.130235E+10 1244.39 17-SEP-07:01 24.37 22.87 0.104304E+09 112.20 19-SEP-06:49 27.20 24.31
October 0.131285E+10 1316.48 22-OCT-07:01 22.77 20.26 0.108110E+09 112.20 11-OCT-07:10 22.77 20.26
November 0.122700E+10 1387.50 27-NOV-06:01 10.00 8.82 0.106944E+09 112.19 24-NOV-08:09 10.00 8.82
December 0.118074E+10 1436.45 15-DEC-04:11 8.13 5.63 0.104923E+09 112.19 11-DEC-08:09 8.13 5.63
                     
Annual Sum or Average 0.151434E+11         0.129986E+10        
Minimum of Months 0.108632E+10 1209.20   8.13 5.63 98476899.35 112.18   8.13 5.63
Maximum of Months 0.137988E+10 1446.75   26.70 23.84 0.117475E+09 112.20   31.13 25.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.357143E+09 769.29 24-JAN-07:01 11.78 9.92 19933251.84 26.78 23-JAN-07:10 11.78 9.92
February 0.326368E+09 767.25 03-FEB-07:01 10.60 7.66 18083268.09 26.78 01-FEB-07:10 10.60 7.66
March 0.379929E+09 768.51 22-MAR-06:01 13.30 12.49 21537679.91 26.78 21-MAR-06:10 13.30 12.49
April 0.341005E+09 738.44 19-APR-06:01 15.68 12.27 19114436.44 26.08 20-APR-06:10 21.10 14.86
May 0.357110E+09 530.01 10-MAY-14:02 27.20 23.54 20554577.30 25.40 24-MAY-12:09 25.60 23.70
June 0.351270E+09 516.51 23-JUN-06:01 26.70 24.69 20452913.09 25.40 23-JUN-14:09 25.10 23.82
July 0.343525E+09 454.41 14-JUL-14:03 27.97 25.30 19006091.75 25.40 31-JUL-14:09 32.85 25.64
August 0.364303E+09 414.26 11-AUG-06:01 28.30 23.57 21319744.18 25.40 09-AUG-12:09 28.30 23.57
September 0.339619E+09 389.79 28-SEP-14:05 28.48 24.26 18967134.44 25.40 07-SEP-14:09 28.48 24.26
October 0.345629E+09 400.17 20-OCT-14:05 27.70 21.85 19726838.98 25.40 26-OCT-14:09 22.07 21.01
November 0.344266E+09 757.64 13-NOV-07:01 12.30 7.88 19602780.22 26.59 15-NOV-07:10 18.48 17.34
December 0.351764E+09 768.60 15-DEC-07:01 7.88 5.99 19264047.53 26.78 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.420193E+10         0.237563E+09        
Minimum of Months 0.326368E+09 389.79   7.88 5.99 18083268.09 25.40   10.60 7.66
Maximum of Months 0.379929E+09 769.29   28.48 25.30 21537679.91 26.78   32.85 25.64



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.160281E+09 257.29 02-JAN-15:05 28.35 22.91 6979278.76 9.10 06-JAN-07:10 22.88 20.20
February 0.165343E+09 264.47 17-FEB-13:05 26.70 20.00 6378042.72 9.11 17-FEB-07:10 26.70 20.00
March 0.193841E+09 264.44 13-MAR-14:05 27.98 23.35 7576189.69 9.16 06-MAR-07:10 27.98 23.35
April 0.222070E+09 303.64 17-APR-14:05 31.78 20.21 6863199.74 9.18 13-APR-06:10 31.78 20.21
May 0.291644E+09 507.80 14-MAY-13:51 27.80 23.35 7454341.39 9.46 31-MAY-06:10 25.28 24.33
June 0.316124E+09 516.12 11-JUN-15:51 31.10 24.23 7450653.02 9.56 23-JUN-06:10 26.70 24.69
July 0.331107E+09 531.08 04-JUL-15:11 32.43 24.62 6978933.57 9.56 14-JUL-06:10 27.30 25.19
August 0.333908E+09 537.47 06-AUG-14:31 31.87 25.20 7778270.47 9.56 28-AUG-06:10 25.68 24.72
September 0.310193E+09 524.13 04-SEP-14:31 30.40 24.34 6941887.61 9.56 11-SEP-06:10 26.70 24.27
October 0.280725E+09 411.67 02-OCT-06:01 26.70 24.92 7174211.54 9.56 04-OCT-06:10 26.20 25.75
November 0.229775E+09 404.66 30-NOV-07:02 25.60 24.11 7027594.09 9.56 30-NOV-07:10 25.60 24.11
December 0.174288E+09 293.24 11-DEC-07:03 22.12 20.55 6796836.69 9.39 11-DEC-07:10 22.12 20.55
                     
Annual Sum or Average 0.300930E+10         85399439.29        
Minimum of Months 0.160281E+09 257.29   22.12 20.00 6378042.72 9.10   22.12 20.00
Maximum of Months 0.333908E+09 537.47   32.43 25.20 7778270.47 9.56   31.78 25.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.617105E+09 1030.62 03-JAN-06:12 20.00 19.21 5606985.30 6.25 26-JAN-07:10 10.68 8.58
February 0.581062E+09 1030.90 02-FEB-06:12 22.80 20.83 5092568.62 6.25 28-FEB-07:10 18.07 14.12
March 0.699650E+09 1033.32 31-MAR-05:12 22.20 18.84 6074298.05 6.25 16-MAR-06:10 22.20 18.84
April 0.702920E+09 1186.34 09-APR-11:51 27.20 18.29 5430371.51 6.25 10-APR-06:10 20.87 18.76
May 0.796175E+09 1155.73 14-MAY-12:31 28.50 23.56 5847507.91 6.25 02-MAY-06:10 28.50 23.56
June 0.820415E+09 1157.83 11-JUN-15:51 31.10 24.23 5830681.78 6.25 06-JUN-06:10 31.10 24.23
July 0.827429E+09 1217.09 04-JUL-11:51 31.70 25.49 5451572.76 6.25 07-JUL-06:10 23.68 21.85
August 0.864636E+09 1178.70 06-AUG-14:31 31.87 25.20 6079868.62 6.25 09-AUG-06:10 26.28 23.75
September 0.804373E+09 1198.21 10-SEP-12:31 31.10 24.59 5433296.35 6.25 08-SEP-06:10 31.10 24.59
October 0.780926E+09 1094.42 07-OCT-04:01 25.00 23.72 5622454.86 6.25 20-OCT-06:10 21.78 20.17
November 0.692022E+09 1050.71 30-NOV-06:02 25.60 24.37 5542520.95 6.25 07-NOV-07:10 25.60 24.37
December 0.614245E+09 1033.18 01-DEC-06:12 23.30 18.40 5433986.64 6.25 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.880096E+10         67446113.35        
Minimum of Months 0.581062E+09 1030.62   20.00 18.29 5092568.62 6.25   10.68 8.58
Maximum of Months 0.864636E+09 1217.09   31.87 25.49 6079868.62 6.25   31.10 24.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.737889E+09 1340.74 27-JAN-07:01 12.38 8.00 5261487.73 5.80 02-JAN-07:10 12.38 8.00
February 0.699465E+09 1319.93 24-FEB-07:01 11.88 8.65 4779127.31 5.80 13-FEB-07:10 11.88 8.65
March 0.832067E+09 1298.02 15-MAR-06:01 11.60 8.27 5689385.48 5.80 10-MAR-07:10 11.60 8.27
April 0.900840E+09 1153.87 19-APR-06:01 15.68 12.27 5083670.73 5.80 27-APR-06:10 21.78 18.41
May 0.106147E+10 1152.74 08-MAY-05:01 23.90 19.12 5466491.47 5.80 25-MAY-06:10 22.98 21.70
June 0.108532E+10 1256.87 23-JUN-06:01 26.70 24.69 5445658.10 5.80 19-JUN-06:10 26.70 24.69
July 0.116617E+10 1247.02 14-JUL-06:01 27.30 25.19 5091520.42 5.80 18-JUL-06:10 24.45 22.95
August 0.119543E+10 1267.13 09-AUG-06:01 26.28 23.75 5677753.87 5.80 14-AUG-06:10 23.48 23.00
September 0.113481E+10 1257.77 11-SEP-06:01 26.70 24.27 5074964.91 5.80 26-SEP-06:10 23.30 21.69
October 0.108931E+10 1294.56 14-OCT-05:01 23.98 22.48 5254317.78 5.80 31-OCT-06:10 21.88 21.24
November 0.917762E+09 1340.76 27-NOV-07:01 10.37 9.01 5186498.88 5.80 22-NOV-07:10 10.37 9.01
December 0.805772E+09 1327.41 13-DEC-07:01 12.48 11.76 5101752.09 5.80 28-DEC-07:10 18.98 13.79
                     
Annual Sum or Average 0.116263E+11         63112628.78        
Minimum of Months 0.699465E+09 1152.74   10.37 8.00 4779127.31 5.80   10.37 8.00
Maximum of Months 0.119543E+10 1340.76   27.30 25.19 5689385.48 5.80   26.70 24.69



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.190095E+09 380.53 24-JAN-07:01 11.78 9.92 8569576.77 11.48 19-JAN-07:10 11.78 9.92
February 0.174100E+09 379.44 03-FEB-07:01 10.60 7.66 7776339.25 11.48 06-FEB-07:10 18.48 14.80
March 0.203490E+09 380.18 22-MAR-06:01 13.30 12.49 9261570.35 11.48 03-MAR-07:10 13.30 12.49
April 0.185748E+09 375.06 19-APR-06:01 15.68 12.27 8232356.87 11.48 20-APR-06:10 21.10 14.86
May 0.196419E+09 314.94 12-MAY-06:02 25.10 22.68 8857936.59 11.20 02-MAY-06:10 25.10 22.68
June 0.193366E+09 359.57 16-JUN-06:01 26.20 23.01 8816347.30 11.03 22-JUN-06:10 24.32 23.63
July 0.189401E+09 340.65 21-JUL-06:01 26.78 24.28 8204419.36 10.90 14-JUL-06:10 26.78 24.28
August 0.200605E+09 352.62 11-AUG-06:01 28.30 23.57 9189596.06 10.93 10-AUG-06:10 28.30 23.57
September 0.186481E+09 324.38 22-SEP-06:01 27.80 25.38 8183622.28 10.97 28-SEP-06:10 23.90 23.16
October 0.189737E+09 333.54 03-OCT-06:01 26.10 25.23 8502707.95 11.08 20-OCT-06:10 21.78 20.17
November 0.186365E+09 380.26 13-NOV-07:01 12.30 7.88 8439280.62 11.48 15-NOV-07:10 18.48 17.34
December 0.187778E+09 380.10 15-DEC-07:01 7.88 5.99 8285062.13 11.48 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.228359E+10         0.102319E+09        
Minimum of Months 0.174100E+09 314.94   7.88 5.99 7776339.25 10.90   11.78 9.92
Maximum of Months 0.203490E+09 380.53   28.30 25.38 9261570.35 11.48   28.30 24.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 IT HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.256961E+09 663.27 05-JAN-07:01 16.70 15.72 26267689.43 28.18 05-JAN-07:10 16.70 15.72
February 0.250968E+09 665.10 03-FEB-07:01 10.60 7.66 23869904.90 28.19 17-FEB-07:10 22.88 20.65
March 0.307920E+09 660.91 15-MAR-06:01 11.60 8.27 28526449.13 28.24 09-MAR-07:10 11.60 8.27
April 0.310385E+09 662.02 19-APR-06:01 15.68 12.27 25440602.39 28.35 21-APR-06:10 22.30 16.14
May 0.347247E+09 575.44 12-MAY-06:02 25.10 22.68 27417326.88 28.25 26-MAY-06:10 24.50 22.18
June 0.351154E+09 656.76 16-JUN-06:01 26.20 23.01 27338684.19 28.09 22-JUN-06:10 24.32 23.63
July 0.349156E+09 635.03 19-JUL-06:01 25.87 24.05 25468534.60 27.96 14-JUL-06:10 25.87 24.05
August 0.363322E+09 654.37 09-AUG-06:01 26.28 23.75 28494028.29 27.93 10-AUG-06:10 24.90 23.71
September 0.334255E+09 606.95 21-SEP-06:01 27.12 24.30 25384094.31 27.89 28-SEP-06:10 23.90 23.16
October 0.323628E+09 585.71 04-OCT-06:01 26.20 25.75 26280675.21 27.86 27-OCT-06:10 22.98 21.95
November 0.295036E+09 602.15 30-NOV-07:02 25.60 24.11 25966756.88 28.03 15-NOV-07:10 25.60 24.11
December 0.267762E+09 658.32 20-DEC-07:01 11.60 9.47 25461478.81 28.01 29-DEC-07:10 19.50 16.01
                     
Annual Sum or Average 0.375779E+10         0.315916E+09        
Minimum of Months 0.250968E+09 575.44   10.60 7.66 23869904.90 27.86   11.60 8.27
Maximum of Months 0.363322E+09 665.10   27.12 25.75 28526449.13 28.35   25.87 24.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.260372E+09 647.83 05-JAN-07:01 16.70 15.72 17614490.66 23.19 05-JAN-07:10 16.70 15.72
February 0.255961E+09 647.28 03-FEB-07:01 10.60 7.66 16010164.02 23.28 17-FEB-07:10 22.88 20.65
March 0.315507E+09 645.37 15-MAR-06:01 11.60 8.27 19127948.07 23.35 09-MAR-07:10 11.60 8.27
April 0.325812E+09 647.54 19-APR-06:01 15.68 12.27 17069691.56 23.42 21-APR-06:10 22.30 16.14
May 0.369773E+09 640.95 12-MAY-06:02 25.10 22.68 18425185.62 23.44 26-MAY-06:10 24.50 22.18
June 0.375153E+09 650.06 16-JUN-06:01 26.20 23.01 18363364.39 23.39 23-JUN-06:10 26.70 24.69
July 0.375464E+09 643.47 13-JUL-06:02 25.68 24.05 17118995.13 23.33 14-JUL-06:10 27.30 25.19
August 0.388207E+09 647.31 02-AUG-06:01 27.20 23.52 19139413.44 23.31 04-AUG-06:10 26.02 24.56
September 0.356424E+09 642.53 01-SEP-06:01 26.10 22.39 17043253.64 23.19 22-SEP-06:10 27.80 25.38
October 0.343697E+09 638.58 02-OCT-06:01 26.70 24.92 17662929.46 23.08 19-OCT-06:10 23.30 19.29
November 0.308676E+09 642.01 30-NOV-07:02 25.60 24.11 17458966.07 23.19 30-NOV-07:10 25.60 24.11
December 0.273639E+09 645.15 12-DEC-07:01 11.20 8.46 17067427.11 23.15 01-DEC-07:10 11.20 8.46
                     
Annual Sum or Average 0.394869E+10         0.212102E+09        
Minimum of Months 0.255961E+09 638.58   10.60 7.66 16010164.02 23.08   11.20 8.27
Maximum of Months 0.388207E+09 650.06   27.20 24.92 19139413.44 23.44   27.80 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 LOBBY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.252481E+10 4819.84 20-JAN-07:01 14.90 11.74 0.235870E+09 264.42 02-JAN-07:10 14.90 11.74
February 0.246726E+10 5144.88 20-FEB-16:42 26.70 17.88 0.214617E+09 264.41 28-FEB-07:10 18.07 14.12
March 0.301335E+10 5131.94 28-MAR-18:06 24.90 20.79 0.256648E+09 264.42 08-MAR-07:10 24.90 20.79
April 0.315424E+10 6096.77 09-APR-15:51 27.20 18.64 0.230024E+09 264.42 10-APR-06:10 20.87 18.76
May 0.362174E+10 6088.66 14-MAY-14:31 28.13 23.23 0.247700E+09 264.42 02-MAY-06:10 28.13 23.23
June 0.364832E+10 6226.22 11-JUN-15:51 31.10 24.23 0.246697E+09 264.41 06-JUN-06:10 31.10 24.23
July 0.378018E+10 6458.35 04-JUL-15:51 31.70 25.12 0.230913E+09 264.41 07-JUL-06:10 23.68 21.85
August 0.392363E+10 6327.45 06-AUG-14:31 31.87 25.20 0.257410E+09 264.41 09-AUG-06:10 26.28 23.75
September 0.361322E+10 6222.30 04-SEP-14:31 30.40 24.34 0.229829E+09 264.41 06-SEP-06:10 23.40 22.67
October 0.350528E+10 5572.85 07-OCT-04:01 25.00 23.72 0.237767E+09 264.41 20-OCT-06:10 21.78 20.17
November 0.302072E+10 4820.55 30-NOV-07:02 25.60 24.11 0.233711E+09 264.42 07-NOV-07:10 25.60 24.11
December 0.263107E+10 4813.97 04-DEC-07:02 17.48 15.66 0.228983E+09 264.42 01-DEC-07:10 17.48 15.66
                     
Annual Sum or Average 0.389038E+11         0.285017E+10        
Minimum of Months 0.246726E+10 4813.97   14.90 11.74 0.214617E+09 264.41   14.90 11.74
Maximum of Months 0.392363E+10 6458.35   31.87 25.20 0.257410E+09 264.42   31.10 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.796751E+09 1358.79 17-JAN-06:12 12.97 11.88 45701563.80 51.01 23-JAN-07:10 13.58 12.59
February 0.736041E+09 1370.99 21-FEB-06:12 15.60 15.30 41508308.61 51.01 06-FEB-07:10 15.60 15.30
March 0.876130E+09 1353.26 13-MAR-05:12 21.87 20.06 49464842.10 51.01 03-MAR-07:10 21.87 20.06
April 0.847334E+09 1350.00 03-APR-05:12 20.40 17.15 44144223.34 51.01 03-APR-06:10 20.18 17.61
May 0.931658E+09 1429.75 13-MAY-04:01 25.00 22.24 47536369.12 51.01 15-MAY-06:10 25.28 22.81
June 0.943992E+09 1415.55 17-JUN-04:01 25.60 21.66 47381050.17 51.01 05-JUN-06:10 25.60 21.66
July 0.950062E+09 1333.51 19-JUL-05:02 26.93 24.03 44242105.42 51.01 24-JUL-06:10 24.18 23.69
August 0.100165E+10 1344.64 04-AUG-05:02 27.02 24.71 49415205.48 51.01 21-AUG-06:10 27.38 24.48
September 0.935548E+09 1404.37 16-SEP-04:01 23.90 23.08 44119945.36 51.01 25-SEP-06:10 24.40 23.65
October 0.932147E+09 1426.57 07-OCT-04:01 25.00 23.72 45695079.56 51.01 18-OCT-06:10 25.00 18.59
November 0.855136E+09 1374.08 27-NOV-06:12 10.00 8.82 45106398.97 51.01 15-NOV-07:10 10.00 8.82
December 0.804542E+09 1362.00 04-DEC-06:12 17.20 15.50 44294674.18 51.01 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.106110E+11         0.548610E+09        
Minimum of Months 0.736041E+09 1333.51   10.00 8.82 41508308.61 51.01   10.00 8.82
Maximum of Months 0.100165E+10 1429.75   27.02 24.71 49464842.10 51.01   27.38 24.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.349237E+09 443.17 02-JAN-04:11 18.70 18.41 8911730.69 9.18 27-JAN-12:00 22.20 16.34
February 0.337380E+09 445.74 19-FEB-20:31 22.97 19.17 8097523.65 9.18 03-FEB-11:50 22.97 19.17
March 0.399263E+09 449.22 13-MAR-03:11 21.70 19.53 9667560.62 9.18 16-MAR-06:00 6.70 4.26
April 0.441813E+09 451.23 23-APR-05:31 23.30 19.98 8623246.03 9.18 21-APR-07:49 23.30 19.98
May 0.521158E+09 447.13 28-MAY-04:21 23.60 22.61 9301292.08 9.18 12-MAY-09:09 23.60 22.61
June 0.531816E+09 449.22 18-JUN-07:11 25.60 22.81 9271640.82 9.18 06-JUN-08:30 25.60 22.81
July 0.576010E+09 446.05 16-JUL-01:51 26.70 23.84 8647365.27 9.18 13-JUL-06:00 26.70 23.84
August 0.574339E+09 454.01 13-AUG-03:41 25.40 23.10 9672716.88 9.18 28-AUG-10:39 22.80 22.32
September 0.553309E+09 453.06 17-SEP-07:01 24.37 22.87 8627646.15 9.18 27-SEP-10:20 28.87 23.67
October 0.528491E+09 457.03 22-OCT-07:01 22.77 20.26 8938514.09 9.18 27-OCT-07:40 25.03 21.81
November 0.440548E+09 451.52 05-NOV-00:01 26.10 24.59 8812395.59 9.18 09-NOV-10:50 26.70 23.11
December 0.375550E+09 451.64 26-DEC-02:21 23.90 22.78 8638845.55 9.18 27-DEC-13:09 19.50 14.86
                     
Annual Sum or Average 0.562892E+10         0.107210E+09        
Minimum of Months 0.337380E+09 443.17   18.70 18.41 8097523.65 9.18   6.70 4.26
Maximum of Months 0.576010E+09 457.03   26.70 24.59 9672716.88 9.18   28.87 23.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.325892E+10 5215.83 19-JAN-06:12 18.30 16.31 0.377993E+09 420.84 19-JAN-07:10 18.58 16.60
February 0.305842E+10 5237.56 02-FEB-06:12 22.80 20.83 0.343370E+09 420.84 01-FEB-07:10 22.80 20.83
March 0.362833E+10 5214.12 13-MAR-05:12 21.87 20.06 0.409372E+09 420.85 16-MAR-06:10 6.70 4.45
April 0.352983E+10 5183.50 07-APR-05:12 23.30 20.25 0.365558E+09 420.84 10-APR-06:10 20.87 18.76
May 0.399993E+10 5478.49 13-MAY-04:01 25.00 22.24 0.393779E+09 420.85 02-MAY-06:10 25.00 22.24
June 0.405723E+10 5432.08 17-JUN-04:01 25.60 21.66 0.392434E+09 420.84 06-JUN-06:10 25.60 21.66
July 0.400945E+10 5677.41 04-JUL-15:51 31.70 25.12 0.366631E+09 420.84 06-JUL-06:10 24.08 22.05
August 0.422678E+10 5697.71 06-AUG-14:31 31.87 25.20 0.409084E+09 420.84 09-AUG-06:10 26.28 23.75
September 0.389372E+10 5337.03 16-SEP-04:01 23.90 23.08 0.365309E+09 420.84 08-SEP-06:10 23.90 23.08
October 0.383452E+10 5373.99 07-OCT-04:01 25.00 23.72 0.378180E+09 420.84 20-OCT-06:10 21.78 20.17
November 0.355130E+10 5185.93 15-NOV-06:12 18.70 17.38 0.373343E+09 420.85 07-NOV-07:10 18.70 17.38
December 0.329758E+10 5204.00 18-DEC-06:12 17.40 17.26 0.366522E+09 420.84 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.443460E+11         0.454158E+10        
Minimum of Months 0.305842E+10 5183.50   17.40 16.31 0.343370E+09 420.84   6.70 4.45
Maximum of Months 0.422678E+10 5697.71   31.87 25.20 0.409372E+09 420.85   26.28 23.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.108483E+10 2178.33 24-JAN-07:02 11.78 9.92 93822148.72 105.42 27-JAN-07:10 12.38 8.00
February 0.100602E+10 2180.47 03-FEB-07:02 10.60 7.66 85219251.97 105.41 03-FEB-07:10 10.60 7.66
March 0.119428E+10 2182.58 22-MAR-06:02 13.30 12.49 0.101608E+09 105.42 03-MAR-07:10 13.30 12.49
April 0.111612E+10 2135.36 19-APR-06:02 15.68 12.27 90491432.76 104.52 20-APR-06:10 21.10 14.86
May 0.120324E+10 2078.06 26-MAY-06:03 24.50 22.18 97408436.01 103.21 26-MAY-06:10 24.50 22.18
June 0.119163E+10 2076.76 16-JUN-06:01 26.20 23.01 97060371.56 102.22 22-JUN-06:10 24.32 23.63
July 0.117211E+10 2058.41 13-JUL-06:02 25.68 24.05 90420683.20 101.39 14-JUL-06:10 27.30 25.19
August 0.123827E+10 2071.84 31-AUG-06:01 25.78 23.68 0.101180E+09 101.48 10-AUG-06:10 25.78 23.68
September 0.114788E+10 2065.26 01-SEP-06:01 26.10 22.39 90192319.76 101.74 28-SEP-06:10 23.90 23.16
October 0.115445E+10 2063.36 27-OCT-06:03 22.98 21.95 93467811.00 102.37 27-OCT-06:10 22.98 21.95
November 0.111342E+10 2155.31 13-NOV-07:02 12.30 7.88 92482574.45 105.36 15-NOV-07:10 18.48 17.34
December 0.108727E+10 2180.04 20-DEC-07:02 11.60 9.47 90874030.05 105.42 14-DEC-07:10 11.60 9.47
                     
Annual Sum or Average 0.137095E+11         0.112423E+10        
Minimum of Months 0.100602E+10 2058.41   10.60 7.66 85219251.97 101.39   10.60 7.66
Maximum of Months 0.123827E+10 2182.58   26.20 24.05 0.101608E+09 105.42   27.30 25.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.175471E+10 2839.87 19-JAN-06:12 18.30 16.31 0.206025E+09 229.55 02-JAN-07:10 18.30 16.31
February 0.163842E+10 2860.33 03-FEB-06:12 10.93 7.57 0.187159E+09 229.56 06-FEB-07:10 18.48 14.80
March 0.196042E+10 2865.46 21-MAR-05:12 11.33 9.18 0.223116E+09 229.55 08-MAR-07:10 11.33 9.18
April 0.186880E+10 2842.15 19-APR-05:12 15.20 11.93 0.199074E+09 229.55 03-APR-06:10 15.20 11.93
May 0.205846E+10 2928.37 13-MAY-04:01 25.00 22.24 0.214239E+09 229.56 15-MAY-06:10 25.28 22.81
June 0.206055E+10 2885.32 17-JUN-04:01 25.60 21.66 0.213441E+09 229.55 05-JUN-06:10 25.60 21.66
July 0.201661E+10 2760.91 07-JUL-05:12 23.30 21.52 0.199197E+09 229.55 05-JUL-06:10 23.30 21.52
August 0.213837E+10 2766.66 29-AUG-05:12 23.13 22.73 0.222516E+09 229.55 07-AUG-06:10 23.13 22.73
September 0.196603E+10 2859.37 16-SEP-04:01 23.90 23.08 0.198573E+09 229.55 25-SEP-06:10 24.40 23.65
October 0.196220E+10 2862.29 07-OCT-04:01 25.00 23.72 0.205699E+09 229.55 18-OCT-06:10 25.00 18.59
November 0.184946E+10 2866.01 13-NOV-06:12 12.20 7.55 0.203291E+09 229.56 16-NOV-07:10 21.20 18.94
December 0.176447E+10 2842.64 20-DEC-06:12 12.77 10.60 0.199685E+09 229.55 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.230385E+11         0.247201E+10        
Minimum of Months 0.163842E+10 2760.91   10.93 7.55 0.187159E+09 229.55   11.33 9.18
Maximum of Months 0.213837E+10 2928.37   25.60 23.72 0.223116E+09 229.56   25.60 23.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 MED GAS

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116041E+09 178.14 03-JAN-14:10 26.70 20.96 3859272.25 4.27 03-JAN-17:19 24.63 19.86
February 0.134794E+09 206.49 11-FEB-14:00 29.40 24.15 3629399.92 4.27 22-FEB-16:10 27.43 14.84
March 0.178215E+09 254.12 27-MAR-13:00 27.80 22.40 4351160.15 4.27 21-MAR-13:39 27.80 22.40
April 0.240598E+09 629.62 09-APR-12:31 27.93 19.11 3984465.32 4.27 18-APR-16:10 23.12 14.31
May 0.330459E+09 657.12 14-MAY-12:31 28.50 23.56 4392464.29 4.37 15-MAY-06:10 25.28 22.81
June 0.370597E+09 671.78 11-JUN-15:51 31.10 24.23 4410920.86 4.63 12-JUN-06:10 25.68 24.45
July 0.413009E+09 695.88 04-JUL-12:31 31.70 25.73 4138026.39 4.70 10-JUL-06:10 27.12 24.30
August 0.392505E+09 688.71 06-AUG-14:31 31.87 25.20 4603226.83 4.76 21-AUG-06:10 27.38 24.48
September 0.369747E+09 681.52 10-SEP-12:31 31.10 24.59 4112484.46 4.76 11-SEP-06:10 26.70 24.27
October 0.309486E+09 599.30 08-OCT-14:31 29.40 24.03 4225467.17 4.55 30-OCT-06:10 26.70 25.38
November 0.214052E+09 259.64 03-NOV-13:50 29.40 24.41 4072154.61 4.36 30-NOV-07:10 25.60 24.11
December 0.134819E+09 216.80 01-DEC-14:10 26.10 19.79 3784239.29 4.27 04-DEC-17:19 24.43 18.38
                     
Annual Sum or Average 0.320432E+10         49563281.54        
Minimum of Months 0.116041E+09 178.14   26.10 19.11 3629399.92 4.27   23.12 14.31
Maximum of Months 0.413009E+09 695.88   31.87 25.73 4603226.83 4.76   27.80 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.247291E+10 3374.11 27-JAN-07:01 12.38 8.00 0.129536E+09 142.85 02-JAN-07:10 12.38 8.00
February 0.228611E+10 3387.37 24-FEB-07:01 11.88 8.65 0.117691E+09 142.86 06-FEB-07:10 11.88 8.65
March 0.269811E+10 3391.80 15-MAR-06:01 11.60 8.27 0.140085E+09 142.85 22-MAR-06:10 13.30 12.49
April 0.261138E+10 3063.80 19-APR-06:01 15.68 12.27 0.125158E+09 142.85 14-APR-06:10 15.68 12.27
May 0.287319E+10 3054.76 08-MAY-05:01 23.90 19.12 0.134585E+09 142.86 31-MAY-06:10 25.28 24.33
June 0.288384E+10 2849.75 06-JUN-05:02 23.98 23.24 0.134072E+09 142.86 08-JUN-06:10 28.30 25.49
July 0.286138E+10 2622.70 18-JUL-05:12 23.50 22.60 0.125352E+09 142.86 14-JUL-06:10 23.50 22.60
August 0.299260E+10 2627.98 14-AUG-05:12 23.30 22.69 0.139785E+09 142.86 15-AUG-06:10 27.38 24.80
September 0.277215E+10 2611.91 27-SEP-05:12 23.30 21.82 0.124945E+09 142.86 22-SEP-06:10 23.30 21.82
October 0.278253E+10 2839.93 26-OCT-05:02 23.80 22.28 0.129361E+09 142.86 04-OCT-06:10 23.80 22.28
November 0.260408E+10 3348.24 13-NOV-07:01 12.30 7.88 0.127694E+09 142.85 30-NOV-07:10 25.60 24.11
December 0.249221E+10 3388.63 12-DEC-07:01 11.20 8.46 0.125611E+09 142.85 14-DEC-07:10 15.78 15.78
                     
Annual Sum or Average 0.323305E+11         0.155388E+10        
Minimum of Months 0.228611E+10 2611.91   11.20 7.88 0.117691E+09 142.85   11.88 8.00
Maximum of Months 0.299260E+10 3391.80   23.98 23.24 0.140085E+09 142.86   28.30 25.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.418629E+09 843.87 24-JAN-07:01 11.78 9.92 27829103.97 31.12 05-JAN-07:10 11.78 9.92
February 0.390997E+09 841.80 23-FEB-07:01 14.68 12.86 25277154.66 31.04 13-FEB-07:10 14.68 12.86
March 0.464329E+09 842.28 01-MAR-07:01 13.07 12.09 30141216.63 31.12 03-MAR-07:10 21.28 17.30
April 0.453971E+09 830.75 19-APR-06:01 15.68 12.27 26878754.99 30.97 20-APR-06:10 21.10 14.86
May 0.507298E+09 818.23 12-MAY-06:02 25.10 22.68 28958757.69 30.84 02-MAY-06:10 25.10 22.68
June 0.512927E+09 829.61 16-JUN-06:01 26.20 23.01 28868258.72 30.75 19-JUN-06:10 24.50 22.74
July 0.513208E+09 822.89 05-JUL-06:01 26.28 24.22 26922977.21 30.70 14-JUL-06:10 27.30 25.19
August 0.536927E+09 828.34 02-AUG-06:01 27.20 23.52 30101268.67 30.73 04-AUG-06:10 26.02 24.56
September 0.500498E+09 825.83 01-SEP-06:01 26.10 22.39 26851043.86 30.72 22-SEP-06:10 27.80 25.38
October 0.495089E+09 834.63 02-OCT-06:01 26.70 24.92 27813737.74 30.82 19-OCT-06:10 23.30 19.29
November 0.455905E+09 837.29 27-NOV-07:01 10.37 9.01 27474921.81 31.19 15-NOV-07:10 10.37 9.01
December 0.425931E+09 844.21 12-DEC-07:02 11.20 8.46 26970515.54 31.18 05-DEC-07:10 11.20 8.46
                     
Annual Sum or Average 0.567571E+10         0.334088E+09        
Minimum of Months 0.390997E+09 818.23   10.37 8.46 25277154.66 30.70   10.37 8.46
Maximum of Months 0.536927E+09 844.21   27.20 24.92 30141216.63 31.19   27.80 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.683206E+10 9017.17 25-JAN-07:01 9.50 4.87 0.339264E+09 374.13 02-JAN-07:10 9.50 4.87
February 0.621684E+10 8556.94 03-FEB-07:01 10.60 7.66 0.308244E+09 374.13 06-FEB-07:10 18.48 14.80
March 0.723003E+10 8932.78 16-MAR-06:01 6.70 4.45 0.366892E+09 374.14 14-MAR-06:10 6.70 4.45
April 0.675195E+10 7917.75 19-APR-06:01 15.68 12.27 0.327798E+09 374.14 14-APR-06:10 15.68 12.27
May 0.714711E+10 7529.40 08-MAY-05:01 23.90 19.12 0.352488E+09 374.15 31-MAY-06:10 25.28 24.33
June 0.704272E+10 7078.00 06-JUN-05:02 23.98 23.24 0.351145E+09 374.16 08-JUN-06:10 28.30 25.49
July 0.691248E+10 6864.46 07-JUL-05:12 23.30 21.52 0.328307E+09 374.16 14-JUL-06:10 27.30 25.19
August 0.732169E+10 6704.05 14-AUG-05:12 23.30 22.69 0.366108E+09 374.16 15-AUG-06:10 27.38 24.80
September 0.678931E+10 6817.67 27-SEP-05:12 23.30 21.82 0.327240E+09 374.16 22-SEP-06:10 23.30 21.82
October 0.697482E+10 7193.05 23-OCT-05:02 23.72 21.83 0.338804E+09 374.16 04-OCT-06:10 23.72 21.83
November 0.677246E+10 8608.30 13-NOV-07:01 12.30 7.88 0.334439E+09 374.15 30-NOV-07:10 25.60 24.11
December 0.677884E+10 8704.33 15-DEC-07:01 7.88 5.99 0.328985E+09 374.14 07-DEC-07:10 7.88 5.99
                     
Annual Sum or Average 0.827703E+11         0.406971E+10        
Minimum of Months 0.621684E+10 6704.05   6.70 4.45 0.308244E+09 374.13   6.70 4.45
Maximum of Months 0.732169E+10 9017.17   23.98 23.24 0.366892E+09 374.16   28.30 25.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.274587E+09 357.91 28-JAN-06:01 16.38 14.91 8879664.70 9.18 18-JAN-10:39 16.38 14.91
February 0.262223E+09 356.67 09-FEB-03:01 18.90 18.21 8063391.86 9.18 09-FEB-12:09 24.27 19.49
March 0.302378E+09 357.59 23-MAR-02:11 20.77 16.71 9623451.41 9.18 16-MAR-07:49 20.77 16.71
April 0.326425E+09 362.87 23-APR-05:31 23.30 19.98 8573018.06 9.18 12-APR-07:10 23.30 19.98
May 0.391647E+09 361.58 28-MAY-04:21 23.60 22.61 9256213.00 9.18 16-MAY-06:49 23.60 22.61
June 0.406085E+09 357.91 18-JUN-07:11 25.60 22.81 9236439.43 9.18 21-JUN-07:30 24.40 22.75
July 0.431433E+09 346.98 16-JUL-06:01 27.38 23.64 8601416.51 9.18 05-JUL-06:00 27.38 23.64
August 0.431378E+09 369.85 13-AUG-03:41 25.40 23.10 9632415.67 9.18 15-AUG-06:49 28.12 25.00
September 0.416427E+09 355.69 17-SEP-07:01 24.37 22.87 8583710.75 9.18 11-SEP-06:00 24.37 22.87
October 0.397035E+09 364.83 22-OCT-07:01 22.77 20.26 8889500.12 9.18 13-OCT-06:49 22.77 20.26
November 0.339142E+09 363.29 05-NOV-00:01 26.10 24.59 8776347.54 9.18 20-NOV-09:39 25.73 20.69
December 0.292851E+09 366.68 24-DEC-06:31 21.87 21.87 8599912.28 9.18 26-DEC-07:00 18.30 15.62
                     
Annual Sum or Average 0.427161E+10         0.106715E+09        
Minimum of Months 0.262223E+09 346.98   16.38 14.91 8063391.86 9.18   16.38 14.91
Maximum of Months 0.431433E+09 369.85   27.38 24.59 9632415.67 9.18   28.12 25.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.816092E+09 1435.87 23-JAN-06:12 13.30 12.17 0.103763E+09 116.04 02-JAN-07:10 13.30 12.17
February 0.746795E+09 1437.81 06-FEB-06:12 18.30 14.67 94209455.00 116.04 06-FEB-07:10 18.48 14.80
March 0.875592E+09 1431.90 21-MAR-05:12 11.33 9.18 0.112273E+09 116.04 08-MAR-07:10 11.33 9.18
April 0.796225E+09 1335.41 19-APR-06:01 15.68 12.27 99970644.51 116.04 03-APR-06:10 15.68 12.27
May 0.844185E+09 1303.37 12-MAY-06:02 25.10 22.68 0.107536E+09 116.04 18-MAY-06:10 24.78 20.53
June 0.832862E+09 1323.76 16-JUN-06:01 26.20 23.01 0.107129E+09 116.04 23-JUN-06:10 26.70 24.69
July 0.808646E+09 1307.40 13-JUL-06:02 25.68 24.05 99740674.29 116.04 13-JUL-06:10 25.68 24.05
August 0.864983E+09 1323.48 09-AUG-06:01 26.28 23.75 0.111671E+09 116.04 29-AUG-06:10 22.98 22.46
September 0.799347E+09 1316.50 01-SEP-06:01 26.10 22.39 99535083.90 116.04 28-SEP-06:10 23.90 23.16
October 0.814903E+09 1307.91 02-OCT-06:01 26.70 24.92 0.103226E+09 116.04 18-OCT-06:10 25.00 18.59
November 0.800951E+09 1445.47 27-NOV-06:12 10.00 8.82 0.102184E+09 116.04 16-NOV-07:10 10.00 8.82
December 0.803696E+09 1434.34 22-DEC-06:12 17.80 16.07 0.100469E+09 116.04 01-DEC-07:10 17.80 16.07
                     
Annual Sum or Average 0.980428E+10         0.124171E+10        
Minimum of Months 0.746795E+09 1303.37   10.00 8.82 94209455.00 116.04   10.00 8.82
Maximum of Months 0.875592E+09 1445.47   26.70 24.92 0.112273E+09 116.04   26.70 24.69



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109592E+10 2332.88 27-JAN-07:01 12.38 8.00 93490884.47 102.27 27-JAN-07:10 12.38 8.00
February 0.989482E+09 2315.94 23-FEB-07:01 14.68 12.86 84844990.74 101.45 23-FEB-07:10 14.68 12.86
March 0.112152E+10 2323.13 02-MAR-07:01 15.18 13.78 0.101101E+09 101.96 02-MAR-07:10 15.18 13.78
April 0.997220E+09 1355.33 20-APR-06:03 21.10 14.86 89824220.79 97.86 20-APR-06:10 21.10 14.86
May 0.104537E+10 940.93 26-MAY-06:03 24.50 22.18 96442449.93 96.14 26-MAY-06:10 24.50 22.18
June 0.103461E+10 793.53 22-JUN-17:00 29.40 24.47 95971349.82 94.74 22-JUN-06:10 29.40 24.47
July 0.102576E+10 777.95 27-JUL-17:00 34.40 24.79 89128528.19 94.55 14-JUL-06:19 34.40 24.79
August 0.109783E+10 848.47 31-AUG-16:03 31.52 24.72 0.100187E+09 94.55 17-AUG-06:19 31.52 24.72
September 0.105355E+10 850.24 28-SEP-16:03 30.50 24.71 89301202.36 94.69 28-SEP-06:10 30.50 24.71
October 0.109934E+10 1028.93 20-OCT-06:03 21.78 20.17 92872743.10 96.49 20-OCT-06:10 21.78 20.17
November 0.109269E+10 2257.45 27-NOV-07:01 10.37 9.01 92027801.93 100.60 15-NOV-07:10 10.37 9.01
December 0.108363E+10 2312.65 14-DEC-07:01 15.78 15.78 90516526.58 101.96 14-DEC-07:10 15.78 15.78
                     
Annual Sum or Average 0.127369E+11         0.111571E+10        
Minimum of Months 0.989482E+09 777.95   10.37 8.00 84844990.74 94.55   10.37 8.00
Maximum of Months 0.112152E+10 2332.88   34.40 24.79 0.101101E+09 102.27   34.40 24.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.142056E+09 301.38 24-JAN-07:01 11.78 9.92 4085644.67 4.59 26-JAN-07:10 10.68 8.58
February 0.130612E+09 299.72 03-FEB-07:02 10.60 7.66 3709951.72 4.57 01-FEB-07:10 10.60 7.66
March 0.153087E+09 300.79 22-MAR-06:02 13.30 12.49 4421087.86 4.58 17-MAR-06:10 13.30 12.49
April 0.140746E+09 291.73 19-APR-06:01 15.68 12.27 3934684.41 4.49 20-APR-06:10 21.10 14.86
May 0.148485E+09 238.36 12-MAY-06:02 25.10 22.68 4232427.24 4.39 02-MAY-06:10 25.10 22.68
June 0.145793E+09 274.10 15-JUN-06:01 27.20 23.94 4215860.72 4.33 22-JUN-06:10 24.32 23.63
July 0.143386E+09 255.73 14-JUL-06:01 27.30 25.19 3925935.49 4.28 14-JUL-06:10 27.30 25.19
August 0.151096E+09 274.72 11-AUG-06:01 28.30 23.57 4394459.46 4.29 10-AUG-06:10 28.30 23.57
September 0.140988E+09 247.40 22-SEP-06:01 27.80 25.38 3916884.69 4.30 28-SEP-06:10 23.90 23.16
October 0.143128E+09 233.87 04-OCT-06:01 26.20 25.75 4060867.79 4.35 20-OCT-06:10 21.78 20.17
November 0.140506E+09 300.33 13-NOV-07:01 12.30 7.88 4021769.39 4.57 13-NOV-07:10 12.30 7.88
December 0.141135E+09 301.08 15-DEC-07:01 7.88 5.99 3955715.71 4.59 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.172102E+10         48875289.15        
Minimum of Months 0.130612E+09 233.87   7.88 5.99 3709951.72 4.28   10.60 7.66
Maximum of Months 0.153087E+09 301.38   28.30 25.75 4421087.86 4.59   28.30 25.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.107488E+10 1891.34 23-JAN-06:12 13.30 12.17 0.148729E+09 166.41 02-JAN-07:10 13.30 12.17
February 0.982931E+09 1899.70 03-FEB-06:12 10.93 7.57 0.135023E+09 166.41 06-FEB-07:10 18.48 14.80
March 0.115107E+10 1879.36 21-MAR-05:12 11.33 9.18 0.160940E+09 166.41 08-MAR-07:10 11.33 9.18
April 0.104195E+10 1770.90 19-APR-06:01 15.68 12.27 0.143269E+09 166.41 03-APR-06:10 15.68 12.27
May 0.110034E+10 1731.95 12-MAY-06:02 25.10 22.68 0.154086E+09 166.41 18-MAY-06:10 24.78 20.53
June 0.108188E+10 1757.90 16-JUN-06:01 26.20 23.01 0.153486E+09 166.41 23-JUN-06:10 26.70 24.69
July 0.104865E+10 1737.13 13-JUL-06:02 25.68 24.05 0.142876E+09 166.41 14-JUL-06:10 27.30 25.19
August 0.112885E+10 1757.41 09-AUG-06:01 26.28 23.75 0.160025E+09 166.41 31-AUG-06:10 25.78 23.68
September 0.104880E+10 1749.62 01-SEP-06:01 26.10 22.39 0.142658E+09 166.41 15-SEP-06:10 24.40 22.71
October 0.107811E+10 1733.39 02-OCT-06:01 26.70 24.92 0.147996E+09 166.41 18-OCT-06:10 25.00 18.59
November 0.106318E+10 1898.00 27-NOV-06:12 10.00 8.82 0.146502E+09 166.41 09-NOV-07:10 10.00 8.82
December 0.106070E+10 1893.54 22-DEC-06:12 17.80 16.07 0.144018E+09 166.41 01-DEC-07:10 17.80 16.07
                     
Annual Sum or Average 0.128613E+11         0.177961E+10        
Minimum of Months 0.982931E+09 1731.95   10.00 7.57 0.135023E+09 166.41   10.00 8.82
Maximum of Months 0.115107E+10 1899.70   26.70 24.92 0.160940E+09 166.41   27.30 25.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.255477E+09 360.93 28-JAN-06:01 16.38 14.91 8872080.65 9.18 02-JAN-08:09 16.38 14.91
February 0.236660E+09 356.29 25-FEB-06:01 10.18 7.59 8052817.44 9.18 15-FEB-08:39 10.18 7.59
March 0.271790E+09 356.35 18-MAR-05:01 19.40 15.66 9608560.73 9.18 07-MAR-08:00 19.40 15.66
April 0.260573E+09 332.37 19-APR-03:11 15.00 11.82 8541728.50 9.18 14-APR-08:50 15.00 11.82
May 0.275652E+09 324.51 28-MAY-04:21 23.60 22.61 9211617.51 9.18 23-MAY-09:09 23.60 22.61
June 0.269945E+09 309.42 25-JUN-06:41 24.82 23.80 9189241.70 9.18 07-JUN-06:40 24.82 23.80
July 0.273902E+09 294.39 16-JUL-06:01 27.38 23.64 8543190.93 9.18 28-JUL-07:10 25.28 24.00
August 0.281858E+09 319.29 13-AUG-03:41 25.40 23.10 9582296.51 9.18 21-AUG-08:30 30.00 25.67
September 0.271305E+09 303.36 17-SEP-07:01 24.37 22.87 8528344.70 9.18 05-SEP-08:30 24.37 22.87
October 0.277815E+09 326.52 22-OCT-07:01 22.77 20.26 8839419.29 9.18 16-OCT-06:00 22.77 20.26
November 0.264153E+09 339.76 13-NOV-04:11 12.80 8.27 8744630.10 9.18 24-NOV-07:30 21.10 21.10
December 0.258767E+09 358.53 15-DEC-04:11 8.13 5.63 8581423.71 9.18 11-DEC-08:30 8.13 5.63
                     
Annual Sum or Average 0.319790E+10         0.106295E+09        
Minimum of Months 0.236660E+09 294.39   8.13 5.63 8052817.44 9.18   8.13 5.63
Maximum of Months 0.281858E+09 360.93   27.38 23.80 9608560.73 9.18   30.00 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.134613E+10 2545.65 23-JAN-06:12 13.30 12.17 76849213.14 102.67 02-JAN-07:10 13.30 12.17
February 0.124432E+10 2559.78 03-FEB-06:12 10.93 7.57 69739764.92 102.67 06-FEB-07:10 18.48 14.80
March 0.147647E+10 2532.92 21-MAR-05:12 11.33 9.18 83102159.64 102.67 03-MAR-07:10 11.33 9.18
April 0.138830E+10 2410.82 19-APR-06:02 15.68 12.27 74015451.75 102.67 03-APR-06:10 15.68 12.27
May 0.150329E+10 2370.01 12-MAY-06:02 25.10 22.68 79781108.30 102.67 16-MAY-06:10 25.28 21.69
June 0.149112E+10 2432.72 23-JUN-06:02 26.70 24.69 79451211.06 102.66 28-JUN-06:10 26.70 24.27
July 0.146987E+10 2432.39 14-JUL-06:02 27.30 25.19 74049566.15 102.67 26-JUL-06:10 26.20 24.96
August 0.155546E+10 2432.44 17-AUG-06:02 26.97 23.97 82845788.16 102.66 23-AUG-06:10 26.88 24.72
September 0.144574E+10 2424.99 22-SEP-06:02 27.80 25.38 73830532.93 102.66 21-SEP-06:10 27.80 25.38
October 0.145777E+10 2431.33 04-OCT-06:02 26.20 25.75 76648214.35 102.67 18-OCT-06:10 25.00 18.59
November 0.139291E+10 2583.11 27-NOV-06:12 10.00 8.82 75866555.73 102.67 15-NOV-07:10 10.00 8.82
December 0.134984E+10 2543.33 22-DEC-06:12 17.80 16.07 74362603.44 102.67 21-DEC-07:10 17.80 16.07
                     
Annual Sum or Average 0.171212E+11         0.920542E+09        
Minimum of Months 0.124432E+10 2370.01   10.00 7.57 69739764.92 102.66   10.00 8.82
Maximum of Months 0.155546E+10 2583.11   27.80 25.75 83102159.64 102.67   27.80 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.855916E+10 15770.21 25-JAN-06:01 9.40 4.63 0.243867E+09 351.37 25-JAN-17:00 16.70 8.38
February 0.787694E+10 14876.27 03-FEB-06:01 11.02 7.56 0.221515E+09 351.03 03-FEB-17:19 14.80 7.84
March 0.906189E+10 15803.88 16-MAR-05:01 6.70 4.49 0.264162E+09 350.98 15-MAR-16:19 6.70 4.49
April 0.882738E+10 13391.14 19-APR-05:01 15.10 11.88 0.235740E+09 350.89 14-APR-16:00 15.10 11.88
May 0.952687E+10 12038.56 14-MAY-05:01 25.60 23.64 0.255162E+09 350.91 31-MAY-16:00 28.90 25.29
June 0.950250E+10 12127.35 25-JUN-05:01 24.32 23.63 0.262642E+09 350.91 07-JUN-16:00 24.32 23.63
July 0.957505E+10 12417.89 04-JUL-05:01 22.88 20.93 0.254489E+09 350.92 13-JUL-16:00 28.30 25.79
August 0.992708E+10 12229.82 06-AUG-05:01 24.40 23.27 0.282805E+09 350.92 03-AUG-16:00 24.40 23.27
September 0.953781E+10 12389.30 10-SEP-05:01 24.40 23.57 0.248217E+09 350.91 18-SEP-16:00 31.10 25.66
October 0.972237E+10 12382.69 22-OCT-05:01 22.20 20.00 0.249879E+09 350.91 02-OCT-16:00 22.20 20.00
November 0.900465E+10 14792.63 13-NOV-06:01 12.20 7.52 0.241932E+09 350.91 30-NOV-17:00 27.20 24.74
December 0.855382E+10 15431.86 15-DEC-06:01 7.80 5.70 0.236171E+09 351.77 20-DEC-17:00 13.90 6.47
                     
Annual Sum or Average 0.109676E+12         0.299658E+10        
Minimum of Months 0.787694E+10 12038.56   6.70 4.49 0.221515E+09 350.89   6.70 4.49
Maximum of Months 0.992708E+10 15803.88   25.60 23.64 0.282805E+09 351.77   31.10 25.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.848394E+10 16406.83 25-JAN-06:01 9.40 4.63 0.254411E+09 366.63 25-JAN-17:00 16.70 8.38
February 0.785492E+10 15525.21 03-FEB-06:01 11.02 7.56 0.231149E+09 366.29 03-FEB-17:19 14.80 7.84
March 0.921153E+10 16428.33 16-MAR-05:01 6.70 4.49 0.275646E+09 366.24 15-MAR-16:19 6.70 4.49
April 0.903589E+10 14073.71 19-APR-05:01 15.10 11.88 0.245823E+09 366.14 14-APR-16:00 15.10 11.88
May 0.970264E+10 12817.41 07-MAY-05:01 20.60 19.45 0.265622E+09 366.17 31-MAY-16:00 28.90 25.29
June 0.964196E+10 12803.20 25-JUN-05:01 24.32 23.63 0.271210E+09 366.17 08-JUN-16:00 24.32 23.63
July 0.964987E+10 13169.87 04-JUL-05:01 22.88 20.93 0.260988E+09 366.18 13-JUL-16:00 28.30 25.79
August 0.994755E+10 12851.68 06-AUG-05:01 24.40 23.27 0.289218E+09 366.18 09-AUG-16:00 30.60 25.72
September 0.940461E+10 12936.57 10-SEP-05:01 24.40 23.57 0.252815E+09 366.18 22-SEP-16:00 30.00 26.31
October 0.947727E+10 12991.08 22-OCT-05:01 22.20 20.00 0.257159E+09 366.17 03-OCT-16:00 22.20 20.00
November 0.880799E+10 15457.50 13-NOV-06:01 12.20 7.52 0.251172E+09 366.16 30-NOV-17:00 27.20 24.74
December 0.841216E+10 16079.00 15-DEC-06:01 7.80 5.70 0.246436E+09 367.04 20-DEC-17:00 13.90 6.47
                     
Annual Sum or Average 0.109630E+12         0.310165E+10        
Minimum of Months 0.785492E+10 12803.20   6.70 4.49 0.231149E+09 366.14   6.70 4.49
Maximum of Months 0.994755E+10 16428.33   24.40 23.63 0.289218E+09 367.04   30.60 26.31



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.825380E+10 16315.29 25-JAN-06:01 9.40 4.63 0.252290E+09 363.58 25-JAN-17:00 16.70 8.38
February 0.751760E+10 15445.65 03-FEB-06:01 11.02 7.56 0.229229E+09 363.23 03-FEB-17:19 14.80 7.84
March 0.867164E+10 16346.09 16-MAR-05:01 6.70 4.49 0.273347E+09 363.18 15-MAR-16:19 6.70 4.49
April 0.809466E+10 14054.38 19-APR-05:01 15.10 11.88 0.243740E+09 363.07 14-APR-16:00 15.10 11.88
May 0.846529E+10 13044.27 07-MAY-05:01 20.60 19.45 0.262890E+09 363.11 31-MAY-16:00 28.90 25.29
June 0.829292E+10 12827.34 25-JUN-05:01 24.32 23.63 0.262411E+09 363.13 08-JUN-16:00 24.32 23.63
July 0.814771E+10 13301.14 04-JUL-05:01 22.88 20.93 0.246080E+09 363.12 25-JUL-16:00 30.60 24.86
August 0.857827E+10 12809.72 06-AUG-05:01 24.40 23.27 0.274709E+09 363.12 09-AUG-16:00 30.60 25.72
September 0.799302E+10 12883.76 04-SEP-05:01 24.32 22.73 0.244030E+09 363.13 20-SEP-16:00 30.60 25.72
October 0.824772E+10 12971.75 22-OCT-05:01 22.20 20.00 0.252606E+09 363.12 03-OCT-16:00 22.20 20.00
November 0.811631E+10 15408.51 13-NOV-06:01 12.20 7.52 0.249045E+09 363.10 30-NOV-17:00 27.20 24.74
December 0.821112E+10 16012.87 15-DEC-06:01 7.80 5.70 0.244382E+09 364.00 20-DEC-17:00 13.90 6.47
                     
Annual Sum or Average 0.985900E+11         0.303476E+10        
Minimum of Months 0.751760E+10 12809.72   6.70 4.49 0.229229E+09 363.07   6.70 4.49
Maximum of Months 0.867164E+10 16346.09   24.40 23.63 0.274709E+09 364.00   30.60 25.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 PACU

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.894991E+09 1037.85 27-JAN-04:21 14.15 8.48 71108031.26 73.43 20-JAN-17:00 14.15 8.48
February 0.828784E+09 1015.47 24-FEB-04:11 12.60 7.66 64542261.08 73.43 22-FEB-14:50 12.60 7.66
March 0.964997E+09 1016.38 03-MAR-04:11 20.77 16.18 76967854.00 73.44 28-MAR-08:09 23.07 20.59
April 0.922702E+09 959.75 19-APR-03:11 15.00 11.82 68424503.00 73.44 10-APR-14:50 15.00 11.82
May 0.992669E+09 925.81 28-MAY-04:21 23.60 22.61 73767153.09 73.44 31-MAY-08:09 28.07 24.52
June 0.979067E+09 891.20 25-JUN-06:41 24.82 23.80 73573160.36 73.45 26-JUN-08:09 27.98 25.36
July 0.976507E+09 850.75 16-JUL-01:51 26.70 23.84 68410001.01 73.45 31-JUL-07:10 26.97 24.40
August 0.102152E+10 912.10 13-AUG-03:41 25.40 23.10 76716384.25 73.45 14-AUG-06:00 24.40 23.27
September 0.965707E+09 878.67 17-SEP-07:01 24.37 22.87 68299439.69 73.45 05-SEP-08:20 24.37 22.87
October 0.984854E+09 936.58 22-OCT-07:01 22.77 20.26 70809084.44 73.44 10-OCT-07:10 22.77 20.26
November 0.931007E+09 993.70 27-NOV-06:01 10.00 8.82 70066704.83 73.44 06-NOV-08:09 10.00 8.82
December 0.900755E+09 1031.55 15-DEC-04:11 8.13 5.63 68776061.35 73.44 26-DEC-08:09 18.30 15.50
                     
Annual Sum or Average 0.113636E+11         0.851461E+09        
Minimum of Months 0.828784E+09 850.75   8.13 5.63 64542261.08 73.43   10.00 7.66
Maximum of Months 0.102152E+10 1037.85   26.70 23.84 76967854.00 73.45   28.07 25.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.112805E+10 2434.29 24-JAN-07:02 11.78 9.92 99647042.21 109.84 24-JAN-07:10 11.78 9.92
February 0.105184E+10 2422.10 24-FEB-07:02 11.88 8.65 90501901.07 109.51 23-FEB-07:10 11.88 8.65
March 0.123431E+10 2419.66 01-MAR-07:02 13.07 12.09 0.107897E+09 109.79 02-MAR-07:10 15.18 13.78
April 0.116547E+10 2347.95 19-APR-06:01 15.68 12.27 96064185.72 107.77 20-APR-06:10 21.10 14.86
May 0.125575E+10 1976.48 12-MAY-06:02 25.10 22.68 0.103378E+09 106.14 26-MAY-06:10 24.50 22.18
June 0.124085E+10 2283.51 16-JUN-06:01 26.20 23.01 0.102991E+09 105.13 22-JUN-06:10 24.32 23.63
July 0.123085E+10 2183.84 21-JUL-06:01 26.78 24.28 95931924.28 104.39 21-JUL-06:10 26.78 24.28
August 0.130812E+10 2257.13 11-AUG-06:01 28.30 23.57 0.107406E+09 104.78 31-AUG-06:10 25.78 23.68
September 0.121562E+10 2201.73 01-SEP-06:01 26.10 22.39 95733936.57 104.83 28-SEP-06:10 23.90 23.16
October 0.123140E+10 2124.97 03-OCT-06:01 26.10 25.23 99254438.47 105.84 20-OCT-06:10 21.78 20.17
November 0.117963E+10 2387.73 13-NOV-07:01 12.30 7.88 98216185.61 109.30 15-NOV-07:10 18.48 17.34
December 0.113011E+10 2422.49 20-DEC-07:02 11.60 9.47 96503581.12 109.30 14-DEC-07:10 11.60 9.47
                     
Annual Sum or Average 0.143720E+11         0.119353E+10        
Minimum of Months 0.105184E+10 1976.48   11.60 7.88 90501901.07 104.39   11.60 8.65
Maximum of Months 0.130812E+10 2434.29   28.30 25.23 0.107897E+09 109.84   26.78 24.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.117585E+10 1387.36 24-JAN-04:11 13.13 11.24 62260507.32 64.25 26-JAN-15:00 20.60 11.94
February 0.111049E+10 1376.28 23-FEB-04:11 15.20 13.49 56536961.20 64.25 03-FEB-11:20 15.20 13.49
March 0.129342E+10 1374.99 03-MAR-04:11 20.77 16.18 67430907.20 64.26 16-MAR-10:30 13.60 5.96
April 0.131073E+10 1339.05 09-APR-07:11 22.77 18.40 60022229.75 64.25 14-APR-07:19 24.47 22.73
May 0.146410E+10 1308.05 28-MAY-04:21 23.60 22.61 64710913.27 64.25 30-MAY-06:00 23.90 22.65
June 0.146534E+10 1277.40 18-JUN-07:11 25.60 22.81 64530732.15 64.26 06-JUN-07:00 25.60 22.81
July 0.151740E+10 1242.72 16-JUL-01:51 26.70 23.84 60053325.63 64.26 31-JUL-08:50 29.72 25.44
August 0.155978E+10 1308.38 13-AUG-03:41 25.40 23.10 67313827.68 64.26 21-AUG-07:19 28.67 25.33
September 0.148373E+10 1279.46 17-SEP-07:01 24.37 22.87 59954843.75 64.25 18-SEP-08:30 27.50 25.03
October 0.147169E+10 1335.07 22-OCT-07:01 22.77 20.26 62146837.00 64.25 05-OCT-08:30 22.77 20.26
November 0.131700E+10 1368.70 27-NOV-06:01 10.00 8.82 61436741.59 64.25 08-NOV-10:30 10.00 8.82
December 0.120551E+10 1372.28 14-DEC-04:11 15.20 15.20 60248124.45 64.25 27-DEC-10:39 14.43 11.91
                     
Annual Sum or Average 0.163750E+11         0.746646E+09        
Minimum of Months 0.111049E+10 1242.72   10.00 8.82 56536961.20 64.25   10.00 5.96
Maximum of Months 0.155978E+10 1387.36   26.70 23.84 67430907.20 64.26   29.72 25.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.213220E+10 2597.50 26-JAN-04:21 11.10 8.31 0.111379E+09 114.90 02-JAN-11:00 11.10 8.31
February 0.198175E+10 2556.88 06-FEB-06:01 18.30 14.67 0.101089E+09 114.90 14-FEB-12:09 24.60 19.65
March 0.231103E+10 2561.04 22-MAR-03:11 14.23 12.78 0.120533E+09 114.90 24-MAR-10:39 25.03 19.82
April 0.225704E+10 2448.43 19-APR-03:11 15.00 11.82 0.107185E+09 114.90 28-APR-14:50 24.60 19.59
May 0.245882E+10 2385.58 28-MAY-04:21 23.60 22.61 0.115521E+09 114.91 31-MAY-08:09 28.07 24.52
June 0.243644E+10 2311.03 25-JUN-06:41 24.82 23.80 0.115197E+09 114.91 12-JUN-06:00 24.82 23.80
July 0.247427E+10 2220.50 16-JUL-01:51 26.70 23.84 0.107125E+09 114.92 10-JUL-09:09 26.70 23.84
August 0.253797E+10 2356.40 13-AUG-03:41 25.40 23.10 0.120109E+09 114.91 21-AUG-12:09 28.53 26.08
September 0.241212E+10 2277.30 17-SEP-07:01 24.37 22.87 0.106939E+09 114.92 18-SEP-07:49 27.30 24.72
October 0.242180E+10 2395.74 22-OCT-07:01 22.77 20.26 0.110873E+09 114.91 11-OCT-12:30 22.77 20.26
November 0.224667E+10 2542.96 27-NOV-06:01 10.00 8.82 0.109728E+09 114.90 24-NOV-09:20 10.00 8.82
December 0.215484E+10 2579.71 15-DEC-04:11 8.13 5.63 0.107716E+09 114.90 12-DEC-10:00 8.13 5.63
                     
Annual Sum or Average 0.278250E+11         0.133339E+10        
Minimum of Months 0.198175E+10 2220.50   8.13 5.63 0.101089E+09 114.90   8.13 5.63
Maximum of Months 0.253797E+10 2597.50   26.70 23.84 0.120533E+09 114.92   28.53 26.08



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.271771E+09 354.14 13-JAN-00:11 22.20 19.49 8894197.75 9.18 26-JAN-12:30 19.45 11.82
February 0.270097E+09 355.60 28-FEB-04:11 16.70 13.47 8084327.24 9.18 03-FEB-12:50 16.70 13.47
March 0.306467E+09 356.69 14-MAR-01:11 23.90 22.65 9649390.55 9.18 17-MAR-07:49 14.22 7.37
April 0.346149E+09 356.42 12-APR-20:21 25.60 23.02 8603213.34 9.18 28-APR-06:00 23.30 18.87
May 0.412635E+09 349.27 01-MAY-23:11 23.70 21.16 9285383.02 9.25 18-MAY-16:00 28.90 22.35
June 0.420853E+09 346.77 18-JUN-02:11 24.27 22.54 9258804.51 9.30 09-JUN-16:00 24.27 22.54
July 0.458869E+09 342.68 28-JUL-18:42 29.55 24.55 8636702.84 9.66 28-JUL-16:00 29.55 24.55
August 0.472655E+09 355.28 13-AUG-03:41 25.40 23.10 9671615.51 9.53 31-AUG-16:00 30.60 24.52
September 0.450250E+09 350.69 17-SEP-07:01 24.37 22.87 8618777.35 9.49 08-SEP-16:00 24.37 22.87
October 0.435540E+09 363.19 22-OCT-07:01 22.77 20.26 8927518.02 9.37 06-OCT-16:00 22.77 20.26
November 0.362554E+09 356.79 07-NOV-02:31 20.60 19.80 8801088.58 9.32 07-NOV-17:10 27.52 22.38
December 0.292492E+09 360.08 04-DEC-04:11 17.03 15.34 8617931.85 9.18 20-DEC-13:30 14.15 7.37
                     
Annual Sum or Average 0.450033E+10         0.107049E+09        
Minimum of Months 0.270097E+09 342.68   16.70 13.47 8084327.24 9.18   14.15 7.37
Maximum of Months 0.472655E+09 363.19   29.55 24.55 9671615.51 9.66   30.60 24.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234684E+10 4767.13 05-JAN-21:31 21.87 18.05 0.186361E+09 193.97 24-JAN-14:09 15.28 8.36
February 0.224011E+10 4780.28 01-FEB-23:51 22.80 19.79 0.169174E+09 193.94 15-FEB-08:09 22.38 19.62
March 0.264736E+10 4868.09 03-MAR-04:11 20.77 16.18 0.201962E+09 193.98 20-MAR-15:20 19.40 10.17
April 0.273243E+10 4821.44 23-APR-05:31 23.30 19.98 0.179803E+09 193.95 03-APR-15:20 23.30 19.98
May 0.318181E+10 4797.27 28-MAY-04:21 23.60 22.61 0.194060E+09 193.96 10-MAY-08:20 23.60 22.61
June 0.325255E+10 4805.75 18-JUN-07:11 25.60 22.81 0.193604E+09 193.94 12-JUN-15:00 25.60 22.81
July 0.332945E+10 4569.04 16-JUL-01:51 26.70 23.84 0.180097E+09 193.92 18-JUL-16:10 30.60 24.64
August 0.338744E+10 4861.13 13-AUG-03:41 25.40 23.10 0.201869E+09 193.96 14-AUG-07:40 25.53 23.84
September 0.319454E+10 4703.08 10-SEP-07:11 25.73 24.30 0.179775E+09 193.98 11-SEP-07:49 27.12 24.66
October 0.310079E+10 4798.25 22-OCT-07:01 22.77 20.26 0.186308E+09 193.95 27-OCT-09:09 27.38 22.45
November 0.274415E+10 4840.56 26-NOV-08:11 19.07 18.48 0.184030E+09 193.93 21-NOV-11:00 19.07 18.48
December 0.244180E+10 4839.47 24-DEC-06:31 21.87 21.87 0.180352E+09 193.96 20-DEC-14:09 21.87 21.87
                     
Annual Sum or Average 0.345993E+11         0.223739E+10        
Minimum of Months 0.224011E+10 4569.04   19.07 16.18 0.169174E+09 193.92   15.28 8.36
Maximum of Months 0.338744E+10 4868.09   26.70 24.30 0.201962E+09 193.98   30.60 24.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.268747E+10 3797.52 17-JAN-07:01 13.22 11.98 0.582546E+09 649.09 02-JAN-07:10 13.22 11.98
February 0.247464E+10 4035.27 21-FEB-06:12 15.60 15.30 0.529136E+09 649.08 06-FEB-07:10 15.60 15.30
March 0.289712E+10 3796.40 01-MAR-07:01 13.07 12.09 0.630492E+09 649.10 08-MAR-07:10 21.88 18.24
April 0.274271E+10 3770.28 19-APR-06:01 15.68 12.27 0.562515E+09 649.09 10-APR-06:10 15.68 12.27
May 0.302135E+10 4182.80 13-MAY-04:01 25.00 22.24 0.605689E+09 649.10 02-MAY-06:10 25.00 22.24
June 0.305671E+10 3823.55 08-JUN-06:02 28.30 25.49 0.603752E+09 649.08 12-JUN-06:10 25.68 24.45
July 0.304020E+10 3821.60 14-JUL-06:02 27.30 25.19 0.563735E+09 649.08 06-JUL-06:10 27.30 25.19
August 0.326667E+10 3820.66 15-AUG-06:02 27.38 24.80 0.629842E+09 649.08 09-AUG-06:10 27.38 24.80
September 0.306023E+10 3820.37 22-SEP-06:02 27.80 25.38 0.562670E+09 649.08 05-SEP-06:10 27.80 25.38
October 0.309068E+10 4178.32 07-OCT-04:01 25.00 23.72 0.582926E+09 649.08 10-OCT-06:10 23.98 22.48
November 0.287762E+10 4026.33 27-NOV-06:12 10.00 8.82 0.575208E+09 649.10 16-NOV-07:10 10.00 8.82
December 0.270853E+10 4017.47 05-DEC-06:12 18.70 17.38 0.564907E+09 649.08 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.349239E+11         0.699342E+10        
Minimum of Months 0.247464E+10 3770.28   10.00 8.82 0.529136E+09 649.08   10.00 8.82
Maximum of Months 0.326667E+10 4182.80   28.30 25.49 0.630492E+09 649.10   27.80 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.318693E+09 651.46 24-JAN-07:02 11.78 9.92 24209006.24 27.11 24-JAN-07:10 11.78 9.92
February 0.292989E+09 648.00 24-FEB-07:02 11.88 8.65 21981264.19 27.05 23-FEB-07:10 11.88 8.65
March 0.344471E+09 647.82 01-MAR-07:01 13.07 12.09 26200348.03 27.03 02-MAR-07:10 15.18 13.78
April 0.321786E+09 631.94 19-APR-06:01 15.68 12.27 23328389.21 26.60 20-APR-06:10 21.10 14.86
May 0.344321E+09 602.05 12-MAY-06:02 25.10 22.68 25102350.98 26.20 02-MAY-06:10 25.10 22.68
June 0.339679E+09 615.59 16-JUN-06:01 26.20 23.01 25008293.62 25.91 22-JUN-06:10 24.32 23.63
July 0.336968E+09 605.18 19-JUL-06:01 25.87 24.05 23300399.92 25.71 14-JUL-06:10 25.87 24.05
August 0.357203E+09 616.25 31-AUG-06:01 25.78 23.68 26079030.76 25.80 31-AUG-06:10 25.78 23.68
September 0.334433E+09 614.82 01-SEP-06:01 26.10 22.39 23254288.04 25.86 28-SEP-06:10 23.90 23.16
October 0.340337E+09 612.20 02-OCT-06:01 26.70 24.92 24110846.59 26.13 20-OCT-06:10 21.78 20.17
November 0.327366E+09 649.52 13-NOV-07:01 12.30 7.88 23857213.66 27.06 13-NOV-07:10 12.30 7.88
December 0.319000E+09 649.29 20-DEC-07:02 11.60 9.47 23446996.29 27.05 14-DEC-07:10 11.60 9.47
                     
Annual Sum or Average 0.397725E+10         0.289878E+09        
Minimum of Months 0.292989E+09 602.05   11.60 7.88 21981264.19 25.71   11.60 7.88
Maximum of Months 0.357203E+09 651.46   26.70 24.92 26200348.03 27.11   25.87 24.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.483651E+10 4766.75 01-JAN-08:11 20.53 19.27 0.370376E+09 411.72 27-JAN-13:20 22.20 16.05
February 0.443189E+10 4711.48 05-FEB-16:21 20.55 13.91 0.333206E+09 411.73 22-FEB-16:19 27.07 14.73
March 0.496903E+10 4639.30 12-MAR-11:01 23.40 17.45 0.390493E+09 411.72 01-MAR-14:20 23.40 17.45
April 0.480291E+10 4375.56 23-APR-05:31 23.30 19.98 0.343797E+09 378.63 13-APR-13:20 23.30 19.98
May 0.530015E+10 4309.98 28-MAY-04:21 23.60 22.61 0.370144E+09 367.18 15-MAY-08:09 23.60 22.61
June 0.535527E+10 4351.09 18-JUN-07:11 25.60 22.81 0.369259E+09 367.16 05-JUN-08:09 25.60 22.81
July 0.557127E+10 4179.58 15-JUL-23:51 26.70 24.27 0.343957E+09 368.77 27-JUL-16:10 34.90 25.19
August 0.586069E+10 4393.63 13-AUG-03:41 25.40 23.10 0.386928E+09 396.24 31-AUG-14:39 32.03 24.60
September 0.581111E+10 4453.48 10-SEP-12:31 31.10 24.59 0.348493E+09 406.48 29-SEP-12:39 30.93 24.21
October 0.593081E+10 4543.52 22-OCT-07:01 22.77 20.26 0.367421E+09 411.71 19-OCT-14:20 22.77 20.26
November 0.535626E+10 4752.13 26-NOV-09:51 20.00 15.93 0.365693E+09 411.72 08-NOV-12:20 20.00 15.93
December 0.493342E+10 4874.22 31-DEC-13:28 23.85 20.84 0.356941E+09 415.38 04-DEC-14:20 23.85 20.84
                     
Annual Sum or Average 0.631593E+11         0.434671E+10        
Minimum of Months 0.443189E+10 4179.58   20.00 13.91 0.333206E+09 367.16   20.00 14.73
Maximum of Months 0.593081E+10 4874.22   31.10 24.59 0.390493E+09 415.38   34.90 25.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.383593E+09 726.77 17-JAN-07:01 13.22 11.98 18881709.76 25.29 13-JAN-07:10 13.22 11.98
February 0.353175E+09 726.92 21-FEB-07:01 15.60 15.30 17133137.79 25.28 28-FEB-07:10 18.07 14.12
March 0.400594E+09 722.17 01-MAR-07:01 13.07 12.09 20405408.69 25.23 03-MAR-07:10 21.28 17.30
April 0.382352E+09 701.95 12-APR-06:02 25.10 22.69 18166914.31 24.80 21-APR-06:10 22.30 16.14
May 0.423786E+09 698.12 12-MAY-06:02 25.10 22.68 19584972.31 24.74 26-MAY-06:10 24.50 22.18
June 0.427155E+09 709.51 16-JUN-06:01 26.20 23.01 19514299.44 24.74 08-JUN-06:10 26.20 23.01
July 0.435563E+09 702.22 13-JUL-06:02 25.68 24.05 18206103.17 24.78 14-JUL-06:10 27.30 25.19
August 0.467371E+09 712.48 31-AUG-06:01 25.78 23.68 20381640.72 24.93 18-AUG-06:10 25.78 23.68
September 0.444926E+09 714.73 01-SEP-06:01 26.10 22.39 18189491.04 25.10 22-SEP-06:10 27.80 25.38
October 0.451953E+09 716.81 02-OCT-06:01 26.70 24.92 18894436.07 25.16 18-OCT-06:10 25.00 18.59
November 0.422644E+09 723.06 27-NOV-07:01 10.37 9.01 18671940.27 25.29 15-NOV-07:10 10.37 9.01
December 0.393945E+09 722.96 14-DEC-07:01 15.78 15.78 18295112.04 25.29 04-DEC-07:10 15.78 15.78
                     
Annual Sum or Average 0.498706E+10         0.226325E+09        
Minimum of Months 0.353175E+09 698.12   10.37 9.01 17133137.79 24.74   10.37 9.01
Maximum of Months 0.467371E+09 726.92   26.70 24.92 20405408.69 25.29   27.80 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 SCRUB

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.180950E+09 418.33 05-JAN-07:01 16.70 15.72 15790025.36 16.97 13-JAN-07:10 21.88 19.26
February 0.174210E+09 417.57 23-FEB-07:01 14.68 12.86 14344991.26 16.98 17-FEB-07:10 14.68 12.86
March 0.212296E+09 419.26 01-MAR-07:01 13.07 12.09 17131124.59 17.05 31-MAR-06:10 22.30 18.89
April 0.215420E+09 416.18 19-APR-06:01 15.68 12.27 15288611.86 16.99 14-APR-06:10 15.68 12.27
May 0.241849E+09 409.55 19-MAY-06:02 25.28 22.70 16479457.09 17.06 19-MAY-06:10 25.28 22.70
June 0.252495E+09 421.24 16-JUN-06:01 26.20 23.01 16448508.79 17.22 09-JUN-06:10 26.20 23.01
July 0.258814E+09 420.80 13-JUL-06:02 25.68 24.05 15344087.86 17.20 28-JUL-06:10 25.00 23.85
August 0.268876E+09 423.77 02-AUG-06:01 27.20 23.52 17156260.34 17.22 18-AUG-06:10 27.38 24.43
September 0.250379E+09 423.54 01-SEP-06:01 26.10 22.39 15300128.06 17.29 22-SEP-06:10 27.80 25.38
October 0.240849E+09 404.15 30-OCT-06:01 26.70 25.38 15832586.20 17.11 04-OCT-06:10 26.70 25.38
November 0.208915E+09 417.97 30-NOV-07:02 25.60 24.11 15611862.03 17.02 03-NOV-06:10 25.60 24.11
December 0.182025E+09 414.82 12-DEC-07:01 11.20 8.46 15294509.61 16.95 07-DEC-07:10 11.20 8.46
                     
Annual Sum or Average 0.268708E+10         0.190022E+09        
Minimum of Months 0.174210E+09 404.15   11.20 8.46 14344991.26 16.95   11.20 8.46
Maximum of Months 0.268876E+09 423.77   27.20 25.38 17156260.34 17.29   27.80 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 SOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.932436E+09 1161.32 26-JAN-04:21 11.10 8.31 82868011.21 85.67 13-JAN-16:10 11.10 8.31
February 0.865213E+09 1136.43 25-FEB-06:01 10.18 7.59 75219830.41 85.67 06-FEB-16:19 10.18 7.59
March 0.100902E+10 1140.06 18-MAR-05:01 19.40 15.66 89725520.77 85.68 06-MAR-08:09 19.40 15.66
April 0.971851E+09 1081.13 19-APR-03:11 15.00 11.82 79779259.59 85.67 11-APR-12:50 15.00 11.82
May 0.104799E+10 1042.99 28-MAY-04:21 23.60 22.61 86025867.45 85.68 15-MAY-08:09 23.60 22.61
June 0.103775E+10 1005.17 25-JUN-06:41 24.82 23.80 85808812.17 85.68 12-JUN-08:00 24.82 23.80
July 0.103898E+10 956.54 16-JUL-01:51 26.70 23.84 79784776.61 85.69 10-JUL-06:40 26.70 23.84
August 0.108004E+10 1028.94 13-AUG-03:41 25.40 23.10 89471301.68 85.68 21-AUG-08:00 30.60 26.05
September 0.101781E+10 986.13 17-SEP-07:01 24.37 22.87 79644459.07 85.68 05-SEP-08:50 24.37 22.87
October 0.103008E+10 1048.64 22-OCT-07:01 22.77 20.26 82553562.47 85.69 30-OCT-06:00 26.70 25.38
November 0.969826E+09 1112.27 27-NOV-06:01 10.00 8.82 81672880.06 85.67 24-NOV-15:50 10.00 8.82
December 0.939407E+09 1152.06 15-DEC-04:11 8.13 5.63 80143845.64 85.67 20-DEC-11:30 13.30 8.67
                     
Annual Sum or Average 0.119404E+11         0.992698E+09        
Minimum of Months 0.865213E+09 956.54   8.13 5.63 75219830.41 85.67   10.00 7.59
Maximum of Months 0.108004E+10 1161.32   26.70 23.84 89725520.77 85.69   30.60 26.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.392967E+09 487.12 08-JAN-08:21 16.15 14.61 36763784.92 38.08 26-JAN-07:00 11.10 8.50
February 0.379355E+09 487.46 24-FEB-04:11 12.60 7.66 33403646.71 38.08 06-FEB-15:50 12.60 7.66
March 0.458642E+09 493.70 15-MAR-03:11 12.20 8.80 39888955.77 38.08 27-MAR-06:49 20.50 18.60
April 0.481558E+09 493.38 19-APR-03:11 15.00 11.82 35537647.07 38.07 10-APR-14:50 15.00 11.82
May 0.549059E+09 488.26 28-MAY-04:21 23.60 22.61 38342435.11 38.07 24-MAY-06:40 23.60 22.61
June 0.557598E+09 484.37 25-JUN-06:41 24.82 23.80 38248545.74 38.07 05-JUN-07:10 24.82 23.80
July 0.575988E+09 470.94 23-JUL-03:51 24.40 22.49 35592519.41 38.08 17-JUL-06:49 24.40 22.49
August 0.579470E+09 486.31 13-AUG-03:41 25.40 23.10 39873041.69 38.07 08-AUG-07:30 25.40 23.10
September 0.547024E+09 477.04 17-SEP-07:01 24.37 22.87 35508774.19 38.08 18-SEP-08:30 27.50 25.03
October 0.528586E+09 486.49 22-OCT-07:01 22.77 20.26 36781496.54 38.08 25-OCT-07:49 24.72 21.54
November 0.462139E+09 487.61 26-NOV-08:11 19.07 18.48 36337005.07 38.08 21-NOV-07:00 19.07 18.48
December 0.411865E+09 491.59 12-DEC-04:11 12.93 11.21 35592352.07 38.08 11-DEC-08:09 12.93 11.21
                     
Annual Sum or Average 0.592425E+10         0.441870E+09        
Minimum of Months 0.379355E+09 470.94   12.20 7.66 33403646.71 38.07   11.10 7.66
Maximum of Months 0.579470E+09 493.70   25.40 23.80 39888955.77 38.08   27.50 25.03



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.121634E+10 1516.77 27-JAN-04:21 14.15 8.48 0.118266E+09 122.38 09-JAN-08:39 14.15 8.48
February 0.112665E+10 1486.94 24-FEB-04:11 12.60 7.66 0.107354E+09 122.39 21-FEB-08:39 12.60 7.66
March 0.131534E+10 1488.68 03-MAR-04:11 20.77 16.18 0.128077E+09 122.38 29-MAR-06:00 22.80 19.52
April 0.126388E+10 1413.93 19-APR-03:11 15.00 11.82 0.113880E+09 122.39 24-APR-06:40 22.93 19.87
May 0.136055E+10 1361.38 28-MAY-04:21 23.60 22.61 0.122825E+09 122.42 15-MAY-07:10 23.60 22.61
June 0.134922E+10 1316.03 25-JUN-06:41 24.82 23.80 0.122532E+09 122.42 05-JUN-07:10 24.82 23.80
July 0.134875E+10 1259.41 16-JUL-01:51 26.70 23.84 0.113926E+09 122.42 17-JUL-06:49 25.18 23.84
August 0.140950E+10 1344.22 13-AUG-03:41 25.40 23.10 0.127765E+09 122.41 14-AUG-07:10 24.68 23.42
September 0.133192E+10 1296.53 17-SEP-07:01 24.37 22.87 0.113732E+09 122.40 05-SEP-06:00 24.37 22.87
October 0.135355E+10 1376.57 22-OCT-07:01 22.77 20.26 0.117883E+09 122.40 16-OCT-07:19 22.77 20.26
November 0.127299E+10 1444.50 27-NOV-06:01 10.00 8.82 0.116601E+09 122.40 06-NOV-09:09 10.00 8.82
December 0.122668E+10 1507.82 15-DEC-04:11 8.13 5.63 0.114385E+09 122.40 26-DEC-09:20 18.50 14.88
                     
Annual Sum or Average 0.155754E+11         0.141723E+10        
Minimum of Months 0.112665E+10 1259.41   8.13 5.63 0.107354E+09 122.38   10.00 7.66
Maximum of Months 0.140950E+10 1516.77   26.70 23.84 0.128077E+09 122.42   25.18 23.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.261124E+10 2617.75 02-JAN-14:30 28.90 24.11 0.209661E+09 228.75 26-JAN-17:19 19.63 11.66
February 0.242085E+10 2647.57 22-FEB-15:40 27.80 14.73 0.189897E+09 228.75 22-FEB-17:19 25.03 14.06
March 0.274405E+10 2369.12 01-MAR-16:00 25.00 15.70 0.224039E+09 228.75 01-MAR-17:19 24.03 15.54
April 0.275068E+10 2288.11 09-APR-13:51 27.20 19.18 0.197974E+09 228.75 11-APR-16:19 27.93 22.30
May 0.310449E+10 2228.59 28-MAY-04:21 23.60 22.61 0.212451E+09 227.07 19-MAY-16:19 23.60 22.61
June 0.314939E+10 2288.78 18-JUN-07:11 25.60 22.81 0.211335E+09 226.83 29-JUN-16:19 30.60 24.86
July 0.330207E+10 2279.50 04-JUL-15:51 31.70 25.12 0.199172E+09 228.75 28-JUL-16:19 34.80 24.67
August 0.343116E+10 2387.71 31-AUG-15:00 32.20 24.99 0.225518E+09 228.75 29-AUG-16:19 32.20 24.99
September 0.335830E+10 2369.36 10-SEP-12:31 31.10 24.59 0.202894E+09 228.75 08-SEP-16:19 31.10 24.59
October 0.337988E+10 2529.90 25-OCT-14:30 30.00 22.37 0.211732E+09 228.75 19-OCT-16:19 30.00 22.37
November 0.298225E+10 2755.84 07-NOV-15:00 28.30 20.78 0.209735E+09 228.75 06-NOV-17:19 28.30 20.78
December 0.268578E+10 2753.03 04-DEC-14:40 25.93 17.99 0.203138E+09 228.75 04-DEC-17:19 24.43 18.38
                     
Annual Sum or Average 0.359201E+11         0.249755E+10        
Minimum of Months 0.242085E+10 2228.59   23.60 14.73 0.189897E+09 226.83   19.63 11.66
Maximum of Months 0.343116E+10 2755.84   32.20 25.12 0.225518E+09 228.75   34.80 24.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.131650E+10 2632.86 05-JAN-07:01 16.70 15.72 0.116021E+09 125.58 13-JAN-07:10 21.88 19.26
February 0.122405E+10 2633.64 23-FEB-07:01 14.68 12.86 0.105414E+09 125.33 10-FEB-07:10 14.68 12.86
March 0.142297E+10 2644.03 02-MAR-07:01 15.18 13.78 0.125734E+09 125.73 03-MAR-07:10 21.28 17.30
April 0.135787E+10 2589.24 19-APR-06:01 15.68 12.27 0.112073E+09 124.27 21-APR-06:10 22.30 16.14
May 0.148841E+10 2460.42 12-MAY-06:02 25.10 22.68 0.120740E+09 124.01 26-MAY-06:10 24.50 22.18
June 0.152641E+10 2612.66 16-JUN-06:01 26.20 23.01 0.120453E+09 124.40 09-JUN-06:10 26.20 23.01
July 0.155048E+10 2603.28 13-JUL-06:02 25.68 24.05 0.112305E+09 124.48 14-JUL-06:10 27.30 25.19
August 0.164558E+10 2615.44 31-AUG-06:01 25.78 23.68 0.125659E+09 124.58 18-AUG-06:10 25.78 23.68
September 0.156338E+10 2623.17 01-SEP-06:01 26.10 22.39 0.112086E+09 125.20 22-SEP-06:10 27.80 25.38
October 0.156715E+10 2601.01 13-OCT-06:02 25.10 23.53 0.116096E+09 124.55 18-OCT-06:10 25.00 18.59
November 0.144148E+10 2621.56 30-NOV-07:02 25.60 24.11 0.114602E+09 125.39 16-NOV-07:10 25.60 24.11
December 0.132409E+10 2619.19 14-DEC-07:01 15.78 15.78 0.112433E+09 125.08 07-DEC-07:10 15.78 15.78
                     
Annual Sum or Average 0.174284E+11         0.139362E+10        
Minimum of Months 0.122405E+10 2460.42   14.68 12.27 0.105414E+09 124.01   14.68 12.86
Maximum of Months 0.164558E+10 2644.03   26.20 24.11 0.125734E+09 125.73   27.80 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.727810E+09 1557.03 24-JAN-07:02 11.78 9.92 29923847.28 33.29 27-JAN-07:10 12.38 8.00
February 0.670317E+09 1554.61 03-FEB-07:02 10.60 7.66 27174950.65 33.06 03-FEB-07:10 10.60 7.66
March 0.787502E+09 1557.02 22-MAR-06:02 13.30 12.49 32390922.20 33.12 17-MAR-06:10 13.30 12.49
April 0.722414E+09 1495.77 19-APR-06:01 15.68 12.27 28828933.76 32.51 20-APR-06:10 21.10 14.86
May 0.762395E+09 1393.02 12-MAY-06:02 25.10 22.68 31017338.84 31.89 26-MAY-06:10 24.50 22.18
June 0.752038E+09 1454.76 16-JUN-06:01 26.20 23.01 30904272.42 31.54 22-JUN-06:10 24.32 23.63
July 0.740006E+09 1379.58 21-JUL-06:01 26.78 24.28 28780487.06 31.27 14-JUL-06:10 26.78 24.28
August 0.781055E+09 1437.86 31-AUG-06:01 25.78 23.68 32216428.25 31.31 10-AUG-06:10 25.78 23.68
September 0.728975E+09 1389.52 01-SEP-06:01 26.10 22.39 28713445.42 31.39 28-SEP-06:10 23.90 23.16
October 0.737428E+09 1301.66 04-OCT-06:01 26.20 25.75 29764382.00 31.67 20-OCT-06:10 21.78 20.17
November 0.722736E+09 1530.77 13-NOV-07:02 12.30 7.88 29467477.84 32.89 15-NOV-07:10 18.48 17.34
December 0.724785E+09 1556.52 21-DEC-07:02 11.88 10.85 28975815.82 33.28 22-DEC-07:10 18.07 16.23
                     
Annual Sum or Average 0.885746E+10         0.358158E+09        
Minimum of Months 0.670317E+09 1301.66   10.60 7.66 27174950.65 31.27   10.60 7.66
Maximum of Months 0.787502E+09 1557.03   26.78 25.75 32390922.20 33.29   26.78 24.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.112906E+10 1455.32 06-JAN-14:00 26.70 22.36 63526059.22 70.15 03-JAN-17:19 26.70 22.36
February 0.124012E+10 1724.85 17-FEB-13:50 26.70 21.41 59644363.91 70.15 22-FEB-16:49 25.97 14.39
March 0.168305E+10 2170.41 27-MAR-15:10 27.70 22.36 72094395.82 70.15 21-MAR-16:19 27.70 22.36
April 0.228543E+10 4573.03 16-APR-15:41 30.78 20.97 66631760.38 70.95 13-APR-06:10 30.78 20.97
May 0.310642E+10 5859.67 14-MAY-14:31 28.13 23.23 72582549.86 75.40 15-MAY-06:10 25.28 22.81
June 0.341055E+10 6099.97 11-JUN-15:51 31.10 24.23 72638187.98 78.21 12-JUN-06:10 25.68 24.45
July 0.368161E+10 6196.94 04-JUL-15:51 31.70 25.12 68074251.29 78.21 10-JUL-06:10 27.12 24.30
August 0.352387E+10 6133.80 06-AUG-14:31 31.87 25.20 75733407.27 78.21 21-AUG-06:10 27.38 24.48
September 0.315989E+10 5923.19 04-SEP-14:31 30.40 24.34 67489270.34 78.21 11-SEP-06:10 26.70 24.27
October 0.261792E+10 4588.73 02-OCT-06:01 26.70 24.92 69385643.30 74.95 02-OCT-06:10 26.70 24.92
November 0.188690E+10 2465.37 30-NOV-07:02 25.60 24.11 67081981.54 71.79 30-NOV-07:10 25.60 24.11
December 0.132268E+10 1911.77 01-DEC-13:40 26.10 19.68 62467487.03 70.15 01-DEC-17:19 24.63 19.36
                     
Annual Sum or Average 0.290475E+11         0.817349E+09        
Minimum of Months 0.112906E+10 1455.32   25.60 19.68 59644363.91 70.15   24.63 14.39
Maximum of Months 0.368161E+10 6196.94   31.87 25.20 75733407.27 78.21   30.78 24.92



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.508491E+09 688.14 13-JAN-10:30 25.85 21.29 36380473.01 37.36 27-JAN-10:50 21.13 14.49
February 0.519044E+09 735.00 28-FEB-10:00 24.40 16.28 33159469.74 37.49 17-FEB-07:10 24.40 16.28
March 0.650405E+09 812.23 31-MAR-09:30 24.15 19.41 39675017.44 38.18 09-MAR-07:10 24.15 19.41
April 0.740990E+09 1073.68 09-APR-08:31 23.90 18.82 35621622.69 38.06 12-APR-06:10 25.10 22.69
May 0.876697E+09 1060.57 19-MAY-06:02 25.28 22.70 38505348.25 40.11 18-MAY-06:10 25.28 22.70
June 0.929886E+09 1591.90 11-JUN-09:51 30.60 23.81 38498606.30 41.38 09-JUN-06:10 30.60 23.81
July 0.978764E+09 1784.11 04-JUL-11:11 31.70 25.25 36007867.42 40.63 21-JUL-06:10 26.78 24.28
August 0.981076E+09 1449.56 06-AUG-10:31 30.53 24.87 40153447.94 40.73 01-AUG-06:10 30.53 24.87
September 0.921080E+09 1736.40 10-SEP-11:11 30.77 24.31 35839602.32 40.45 22-SEP-06:10 27.80 25.38
October 0.846645E+09 1209.14 04-OCT-06:01 26.20 25.75 36998545.66 39.50 04-OCT-06:10 26.20 25.75
November 0.664412E+09 932.71 21-NOV-07:02 25.18 21.19 36300144.59 39.69 09-NOV-07:10 25.18 21.19
December 0.506843E+09 712.91 08-DEC-10:20 26.47 22.65 35175086.45 38.07 01-DEC-07:10 26.47 22.65
                     
Annual Sum or Average 0.912433E+10         0.442315E+09        
Minimum of Months 0.506843E+09 688.14   23.90 16.28 33159469.74 37.36   21.13 14.49
Maximum of Months 0.981076E+09 1784.11   31.70 25.75 40153447.94 41.38   30.60 25.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.587309E+09 577.87 03-JAN-14:00 26.70 20.96 43806758.89 48.80 04-JAN-14:20 25.40 21.19
February 0.613702E+09 656.54 17-FEB-13:30 26.70 20.72 41132395.55 48.80 16-FEB-17:19 26.70 20.72
March 0.843190E+09 1153.08 29-MAR-07:30 23.35 19.48 50243506.58 48.80 21-MAR-08:20 23.35 19.48
April 0.115498E+10 3353.01 09-APR-08:31 23.90 18.82 46108651.04 48.80 18-APR-16:19 22.93 14.20
May 0.145194E+10 3186.12 14-MAY-08:31 28.33 23.89 50084475.27 51.34 15-MAY-06:10 25.28 22.81
June 0.153600E+10 3319.21 11-JUN-07:51 28.30 24.59 50129291.77 53.26 12-JUN-06:10 25.68 24.45
July 0.163582E+10 3398.42 02-JUL-10:31 32.23 24.18 46914748.78 51.82 10-JUL-06:10 27.12 24.30
August 0.155636E+10 3261.59 06-AUG-10:31 30.53 24.87 52183866.81 51.43 01-AUG-06:10 30.53 24.87
September 0.137406E+10 3200.44 10-SEP-08:31 27.93 25.10 46546391.72 50.24 11-SEP-06:10 26.70 24.27
October 0.112819E+10 1058.04 06-OCT-07:30 25.85 23.67 47861581.63 48.80 19-OCT-16:19 27.03 20.36
November 0.836109E+09 782.79 03-NOV-13:30 29.40 24.30 46181166.65 48.80 06-NOV-17:19 27.43 20.23
December 0.641209E+09 696.12 01-DEC-13:40 26.10 19.68 42900884.35 48.80 01-DEC-17:19 24.63 19.36
                     
Annual Sum or Average 0.133589E+11         0.564094E+09        
Minimum of Months 0.587309E+09 577.87   23.35 18.82 41132395.55 48.80   22.93 14.20
Maximum of Months 0.163582E+10 3398.42   32.23 25.10 52183866.81 53.26   30.53 24.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 91176512.77 224.31 05-JAN-07:01 16.70 15.72 3159284.72 3.39 04-JAN-07:10 16.70 15.72
February 88008095.12 223.51 23-FEB-07:01 14.68 12.86 2869024.19 3.40 17-FEB-07:10 14.68 12.86
March 0.107230E+09 224.50 01-MAR-07:01 13.07 12.09 3427307.62 3.41 31-MAR-06:10 22.30 18.89
April 0.111062E+09 223.58 19-APR-06:01 15.68 12.27 3059659.68 3.40 27-APR-06:10 21.78 18.41
May 0.125655E+09 210.20 19-MAY-06:02 25.28 22.70 3298361.55 3.41 19-MAY-06:10 25.28 22.70
June 0.130843E+09 225.34 16-JUN-06:01 26.20 23.01 3291400.29 3.44 09-JUN-06:10 26.20 23.01
July 0.134686E+09 226.12 05-JUL-06:01 26.28 24.22 3070902.10 3.43 26-JUL-06:10 26.20 24.96
August 0.138440E+09 226.62 02-AUG-06:01 27.20 23.52 3432483.68 3.44 18-AUG-06:10 27.38 24.43
September 0.129189E+09 226.10 01-SEP-06:01 26.10 22.39 3061496.64 3.45 22-SEP-06:10 27.80 25.38
October 0.123880E+09 223.32 02-OCT-06:01 26.70 24.92 3168138.21 3.42 04-OCT-06:10 26.20 25.75
November 0.107108E+09 223.70 30-NOV-07:02 25.60 24.11 3124226.86 3.40 10-NOV-07:10 25.60 24.11
December 92225153.41 223.29 12-DEC-07:01 11.20 8.46 3060048.04 3.39 01-DEC-07:10 11.20 8.46
                     
Annual Sum or Average 0.137950E+10         38022333.57        
Minimum of Months 88008095.12 210.20   11.20 8.46 2869024.19 3.39   11.20 8.46
Maximum of Months 0.138440E+09 226.62   27.20 24.92 3432483.68 3.45   27.80 25.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.659294E+09 868.23 02-JAN-10:40 25.53 21.01 26548359.24 27.45 27-JAN-10:50 21.13 14.49
February 0.680450E+09 842.23 28-FEB-10:10 24.40 16.25 24253143.65 27.54 17-FEB-07:10 24.40 16.25
March 0.863398E+09 1049.44 27-MAR-10:30 25.85 21.67 29106775.50 27.88 09-MAR-07:10 25.85 21.67
April 0.101738E+10 1092.02 14-APR-10:10 28.40 23.20 26184860.61 28.29 17-APR-06:10 18.98 16.80
May 0.122620E+10 1826.77 15-MAY-06:02 25.28 22.81 28312968.41 29.47 15-MAY-06:10 25.28 22.81
June 0.129584E+10 1981.01 12-JUN-06:02 25.68 24.45 28293490.48 30.17 12-JUN-06:10 25.68 24.45
July 0.136127E+10 2508.86 04-JUL-11:11 31.70 25.25 26460637.27 29.98 05-JUL-06:10 26.28 24.22
August 0.135244E+10 1991.07 21-AUG-06:01 27.38 24.48 29500544.49 29.98 01-AUG-06:10 27.38 24.48
September 0.127687E+10 2442.24 10-SEP-11:11 30.77 24.31 26334362.28 29.91 11-SEP-06:10 26.70 24.27
October 0.116922E+10 1922.59 02-OCT-06:01 26.70 24.92 27191637.67 29.15 30-OCT-06:10 26.70 25.38
November 0.907258E+09 1452.99 21-NOV-07:02 25.18 21.19 26666898.75 28.84 22-NOV-07:10 23.40 20.81
December 0.680331E+09 900.07 08-DEC-10:30 26.65 22.70 25613750.37 28.04 01-DEC-07:10 26.65 22.70
                     
Annual Sum or Average 0.124899E+11         0.324467E+09        
Minimum of Months 0.659294E+09 842.23   24.40 16.25 24253143.65 27.45   18.98 14.49
Maximum of Months 0.136127E+10 2508.86   31.70 25.25 29500544.49 30.17   27.38 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.306153E+09 883.29 02-JAN-14:20 28.90 24.35 11970091.80 23.25 02-JAN-15:09 28.35 22.91
February 0.453078E+09 848.87 02-FEB-14:00 28.30 22.51 13223972.39 22.18 02-FEB-14:09 28.03 22.49
March 0.513220E+09 904.68 13-MAR-16:00 29.40 22.41 15024496.40 24.14 13-MAR-16:10 29.32 22.34
April 0.647078E+09 1023.76 17-APR-15:00 32.20 19.76 16592705.04 28.93 17-APR-15:09 32.12 19.85
May 0.895863E+09 1130.94 22-MAY-13:00 34.40 23.24 21306677.36 32.98 22-MAY-13:09 34.32 23.33
June 0.952539E+09 993.34 09-JUN-15:20 31.10 24.72 21934914.57 27.29 09-JUN-16:30 31.10 24.60
July 0.962716E+09 1174.40 28-JUL-15:40 35.00 24.98 22043820.03 34.60 28-JUL-16:10 34.90 24.75
August 0.104804E+10 1118.05 23-AUG-13:00 33.90 25.44 24197409.03 32.19 23-AUG-13:09 33.62 25.44
September 0.896581E+09 1044.28 20-SEP-16:00 32.20 25.55 20514228.14 29.23 08-SEP-16:10 32.20 25.55
October 0.850386E+09 1019.37 03-OCT-15:00 31.70 25.11 19962519.71 28.19 03-OCT-15:09 31.60 25.08
November 0.651843E+09 931.65 17-NOV-15:00 30.00 22.20 16870797.33 25.16 17-NOV-15:09 29.90 22.11
December 0.309183E+09 829.68 08-DEC-14:00 27.80 22.72 11929010.81 21.50 08-DEC-14:09 27.70 22.74
                     
Annual Sum or Average 0.848668E+10         0.215571E+09        
Minimum of Months 0.306153E+09 829.68   27.80 19.76 11929010.81 21.50   27.70 19.85
Maximum of Months 0.104804E+10 1174.40   35.00 25.55 24197409.03 34.60   34.90 25.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.201033E+10 3788.00 01-JAN-13:31 26.47 21.74 0.469102E+09 705.46 13-JAN-07:10 21.88 19.26
February 0.188508E+10 3809.25 26-FEB-13:01 25.10 16.13 0.426425E+09 713.40 17-FEB-07:10 25.10 16.13
March 0.216635E+10 3168.58 12-MAR-13:41 24.90 18.25 0.510193E+09 714.06 31-MAR-06:10 22.30 18.89
April 0.213533E+10 3700.00 09-APR-13:11 27.93 19.41 0.453555E+09 714.07 14-APR-06:10 23.40 22.27
May 0.243442E+10 2951.09 12-MAY-06:02 25.10 22.68 0.493350E+09 714.12 19-MAY-06:10 25.28 22.70
June 0.257705E+10 3304.52 03-JUN-04:01 26.60 23.89 0.491990E+09 714.09 06-JUN-06:10 24.68 23.80
July 0.259726E+10 2868.84 07-JUL-06:03 23.68 21.85 0.457348E+09 714.09 19-JUL-06:10 25.87 24.05
August 0.273001E+10 2922.32 31-AUG-12:50 31.70 24.66 0.513785E+09 714.10 23-AUG-06:10 31.70 24.66
September 0.264077E+10 4071.40 10-SEP-12:31 31.10 24.59 0.455570E+09 714.10 11-SEP-06:10 26.70 24.27
October 0.261456E+10 3854.61 22-OCT-11:31 28.50 22.79 0.475847E+09 714.10 26-OCT-06:10 23.30 21.84
November 0.227286E+10 3828.19 19-NOV-13:41 26.70 21.27 0.470148E+09 714.12 09-NOV-07:10 26.70 21.27
December 0.198300E+10 4098.11 03-DEC-15:01 24.40 18.45 0.452041E+09 714.04 01-DEC-07:10 24.40 18.45
                     
Annual Sum or Average 0.280470E+11         0.566936E+10        
Minimum of Months 0.188508E+10 2868.84   23.68 16.13 0.426425E+09 705.46   21.88 16.13
Maximum of Months 0.273001E+10 4098.11   31.70 24.66 0.513785E+09 714.12   31.70 24.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.255902E+09 350.81 14-JAN-05:02 23.90 21.32 10755910.26 11.25 13-JAN-07:10 23.90 21.32
February 0.240162E+09 343.22 11-FEB-05:01 23.90 22.27 9784788.57 11.25 02-FEB-07:10 23.90 22.27
March 0.282923E+09 314.66 12-MAR-13:41 24.90 18.25 11669328.34 11.26 31-MAR-06:10 22.30 18.89
April 0.284763E+09 320.40 13-APR-04:01 24.40 22.09 10394850.82 11.19 07-APR-06:10 24.40 22.09
May 0.323684E+09 355.85 27-MAY-04:02 24.40 23.65 11157488.99 11.15 11-MAY-06:10 24.40 23.65
June 0.343367E+09 340.81 03-JUN-04:02 26.60 23.89 11104501.34 11.09 06-JUN-07:10 26.38 24.66
July 0.347380E+09 345.04 15-JUL-04:02 25.18 24.23 10346349.44 11.12 07-JUL-06:10 25.18 24.23
August 0.356571E+09 335.45 12-AUG-04:01 23.90 23.16 11574596.81 11.08 09-AUG-13:20 23.90 23.16
September 0.340405E+09 349.95 16-SEP-04:02 23.90 23.08 10331445.95 11.08 28-SEP-07:49 24.32 23.88
October 0.326438E+09 341.54 14-OCT-05:02 23.98 22.48 10724948.80 11.18 20-OCT-06:10 21.78 20.17
November 0.279736E+09 330.75 03-NOV-04:01 24.40 22.49 10612668.89 11.27 16-NOV-07:10 21.20 18.94
December 0.260015E+09 337.11 09-DEC-05:01 25.00 22.66 10413862.43 11.26 07-DEC-07:10 25.00 22.66
                     
Annual Sum or Average 0.364135E+10         0.128871E+09        
Minimum of Months 0.240162E+09 314.66   23.90 18.25 9784788.57 11.08   21.20 18.89
Maximum of Months 0.356571E+09 355.85   26.60 24.23 11669328.34 11.27   26.38 24.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.194035E+09 417.54 27-JAN-06:12 12.20 7.69 11068108.28 14.88 26-JAN-07:10 12.20 7.69
February 0.178366E+09 404.19 23-FEB-07:01 14.68 12.86 10046464.61 14.88 01-FEB-07:10 14.68 12.86
March 0.209037E+09 405.44 01-MAR-07:01 13.07 12.09 11977056.13 14.88 09-MAR-07:10 22.80 20.25
April 0.192281E+09 399.57 19-APR-06:01 15.68 12.27 10650141.39 14.88 20-APR-06:10 21.10 14.86
May 0.206894E+09 385.88 11-MAY-06:03 21.88 20.94 11462228.48 14.77 11-MAY-06:10 21.88 20.94
June 0.212120E+09 354.56 06-JUN-06:03 24.68 23.80 11411142.15 14.50 22-JUN-06:10 24.32 23.63
July 0.206524E+09 379.64 07-JUL-06:03 23.68 21.85 10626073.97 14.57 07-JUL-06:10 23.68 21.85
August 0.219808E+09 360.12 29-AUG-06:03 22.98 22.46 11897711.61 14.47 29-AUG-06:10 22.98 22.46
September 0.205315E+09 372.66 28-SEP-06:03 23.90 23.16 10603672.21 14.53 06-SEP-06:10 23.90 23.16
October 0.203724E+09 387.81 20-OCT-06:03 21.78 20.17 11016338.81 14.83 20-OCT-06:10 21.78 20.17
November 0.191917E+09 394.39 14-NOV-07:02 18.17 15.21 10924854.38 14.88 15-NOV-07:10 18.48 17.34
December 0.192398E+09 404.35 20-DEC-07:01 11.60 9.47 10707808.00 14.88 06-DEC-07:10 11.60 9.47
                     
Annual Sum or Average 0.241242E+10         0.132392E+09        
Minimum of Months 0.178366E+09 354.56   11.60 7.69 10046464.61 14.47   11.60 7.69
Maximum of Months 0.219808E+09 417.54   24.68 23.80 11977056.13 14.88   24.32 23.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.174019E+10 3300.27 14-JAN-05:01 23.90 21.32 0.264755E+09 274.52 02-JAN-17:49 23.90 21.32
February 0.169890E+10 3328.11 20-FEB-16:31 26.70 17.88 0.243120E+09 274.51 03-FEB-17:19 26.70 17.88
March 0.203360E+10 2661.10 27-MAR-16:30 26.95 22.12 0.290253E+09 275.96 14-MAR-06:10 26.95 22.12
April 0.212884E+10 3753.64 02-APR-16:32 25.97 18.13 0.261862E+09 276.68 14-APR-06:10 23.40 22.27
May 0.246632E+10 3190.20 08-MAY-05:01 23.90 19.12 0.282029E+09 274.51 08-MAY-16:19 26.33 20.21
June 0.255572E+10 3408.61 10-JUN-04:01 26.02 24.10 0.280967E+09 278.73 08-JUN-06:10 26.02 24.10
July 0.264007E+10 2822.31 28-JUL-15:30 35.00 25.05 0.262604E+09 277.07 21-JUL-06:10 35.00 25.05
August 0.273394E+10 2814.02 31-AUG-15:30 31.95 24.87 0.293321E+09 280.04 18-AUG-06:10 31.95 24.87
September 0.255899E+10 3904.25 10-SEP-15:51 31.10 24.95 0.261737E+09 279.35 22-SEP-06:10 27.80 25.38
October 0.245899E+10 3390.97 15-OCT-16:32 28.50 20.76 0.271100E+09 274.95 04-OCT-06:10 28.50 20.76
November 0.205785E+10 2800.45 07-NOV-15:30 28.30 21.48 0.265729E+09 274.51 06-NOV-17:49 28.30 21.48
December 0.179196E+10 3923.62 03-DEC-15:01 24.40 18.45 0.257501E+09 275.46 07-DEC-07:10 23.40 21.72
                     
Annual Sum or Average 0.268654E+11         0.323498E+10        
Minimum of Months 0.169890E+10 2661.10   23.90 17.88 0.243120E+09 274.51   23.40 17.88
Maximum of Months 0.273394E+10 3923.62   35.00 25.05 0.293321E+09 280.04   35.00 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.275397E+10 3447.97 14-JAN-05:02 23.90 21.32 0.383287E+09 408.14 11-JAN-17:49 23.90 21.32
February 0.253870E+10 3421.20 11-FEB-05:01 23.90 22.27 0.349296E+09 407.02 08-FEB-17:30 23.90 22.27
March 0.291966E+10 3163.31 12-MAR-13:41 24.90 18.25 0.416201E+09 405.82 23-MAR-09:00 23.90 17.94
April 0.285977E+10 3039.77 13-APR-04:01 24.40 22.09 0.367295E+09 401.51 25-APR-15:00 20.60 20.15
May 0.322437E+10 3469.14 27-MAY-04:02 24.40 23.65 0.390256E+09 400.37 25-MAY-16:00 24.40 23.65
June 0.338195E+10 3239.27 03-JUN-04:02 26.60 23.89 0.385532E+09 396.47 22-JUN-11:50 23.90 22.27
July 0.343102E+10 3313.51 15-JUL-04:01 25.18 24.23 0.354693E+09 395.09 14-JUL-16:00 25.18 24.23
August 0.357116E+10 3252.81 12-AUG-04:01 23.90 23.16 0.400952E+09 395.44 09-AUG-13:30 23.90 23.16
September 0.341257E+10 3372.59 16-SEP-04:02 23.90 23.08 0.359586E+09 396.26 27-SEP-16:00 26.70 23.55
October 0.337038E+10 3299.96 14-OCT-05:02 23.98 22.48 0.375565E+09 400.99 27-OCT-15:50 25.60 23.90
November 0.295286E+10 3204.60 26-NOV-13:11 21.70 13.93 0.376907E+09 407.20 28-NOV-17:49 25.68 21.10
December 0.277599E+10 3341.30 09-DEC-05:01 25.00 22.66 0.371427E+09 409.20 14-DEC-17:00 19.40 15.66
                     
Annual Sum or Average 0.371924E+11         0.453100E+10        
Minimum of Months 0.253870E+10 3039.77   21.70 13.93 0.349296E+09 395.09   19.40 15.66
Maximum of Months 0.357116E+10 3469.14   26.60 24.23 0.416201E+09 409.20   26.70 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.359149E+10 4486.80 14-JAN-05:02 23.90 21.32 0.505064E+09 540.87 11-JAN-17:49 23.90 21.32
February 0.330216E+10 4427.14 11-FEB-05:01 23.90 22.27 0.459494E+09 538.22 03-FEB-13:00 23.90 22.27
March 0.377588E+10 4122.97 12-MAR-13:41 24.90 18.25 0.545924E+09 535.74 17-MAR-10:00 21.10 14.57
April 0.365749E+10 3901.17 13-APR-04:01 24.40 22.09 0.479889E+09 529.07 26-APR-16:49 25.00 21.61
May 0.411377E+10 4505.35 27-MAY-04:02 24.40 23.65 0.510680E+09 527.60 25-MAY-16:00 24.40 23.65
June 0.432377E+10 4198.27 03-JUN-04:02 26.60 23.89 0.505591E+09 521.99 21-JUN-16:00 23.90 22.27
July 0.434799E+10 4276.88 15-JUL-04:01 25.18 24.23 0.466601E+09 520.59 14-JUL-16:00 25.18 24.23
August 0.456696E+10 4195.41 12-AUG-04:01 23.90 23.16 0.525758E+09 518.83 09-AUG-13:30 23.90 23.16
September 0.437468E+10 4362.96 16-SEP-04:02 23.90 23.08 0.471582E+09 522.14 27-SEP-16:00 26.70 23.55
October 0.434432E+10 4269.66 14-OCT-05:02 23.98 22.48 0.492079E+09 528.39 27-OCT-15:00 25.60 23.90
November 0.383108E+10 4210.24 26-NOV-13:11 21.70 13.93 0.494939E+09 537.61 28-NOV-17:49 25.68 21.10
December 0.360942E+10 4345.01 03-DEC-15:01 24.40 18.45 0.488905E+09 542.26 14-DEC-17:00 19.40 15.66
                     
Annual Sum or Average 0.478390E+11         0.594651E+10        
Minimum of Months 0.330216E+10 3901.17   21.70 13.93 0.459494E+09 518.83   19.40 14.57
Maximum of Months 0.456696E+10 4505.35   26.60 24.23 0.545924E+09 542.26   26.70 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.503271E+09 702.93 08-JAN-15:11 21.10 14.12 62684072.12 68.63 02-JAN-14:39 21.10 14.12
February 0.460408E+09 623.73 22-FEB-14:10 27.30 14.16 57071242.27 68.64 22-FEB-14:39 27.60 14.24
March 0.510157E+09 602.99 01-MAR-14:10 23.48 15.79 67714913.29 66.18 01-MAR-14:09 23.48 15.79
April 0.485909E+09 521.73 13-APR-13:10 29.32 23.85 60523185.76 64.05 26-APR-13:20 25.93 22.64
May 0.544565E+09 474.03 22-MAY-13:10 34.32 23.33 65288808.39 64.05 24-MAY-16:19 23.90 23.16
June 0.576436E+09 486.08 01-JUN-14:40 30.20 23.46 65149767.45 64.05 08-JUN-06:19 28.30 25.49
July 0.587494E+09 496.69 27-JUL-16:00 35.00 25.28 60730807.50 64.05 14-JUL-16:19 35.00 25.28
August 0.620161E+09 584.37 31-AUG-13:10 31.70 24.44 67967839.98 64.18 31-AUG-13:09 31.70 24.44
September 0.616369E+09 637.93 10-SEP-12:31 31.10 24.59 60756230.40 66.01 29-SEP-12:39 30.93 24.21
October 0.622160E+09 618.91 06-OCT-12:30 30.30 23.72 63238648.35 67.90 06-OCT-12:39 30.20 23.69
November 0.548825E+09 752.36 26-NOV-13:11 21.70 13.93 62474621.28 69.97 07-NOV-13:50 21.70 13.93
December 0.503710E+09 815.37 03-DEC-15:01 24.40 18.45 60766088.18 69.30 04-DEC-14:30 25.85 18.01
                     
Annual Sum or Average 0.657947E+10         0.754366E+09        
Minimum of Months 0.460408E+09 474.03   21.10 13.93 57071242.27 64.05   21.10 13.93
Maximum of Months 0.622160E+09 815.37   35.00 25.28 67967839.98 69.97   35.00 25.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.180035E+10 2716.34 14-JAN-05:01 23.90 21.32 0.243603E+09 266.88 27-JAN-09:50 17.93 11.43
February 0.174456E+10 2390.79 11-FEB-05:01 23.90 22.27 0.226152E+09 266.89 08-FEB-17:19 23.90 22.27
March 0.214272E+10 2279.84 27-MAR-10:20 25.57 21.63 0.274773E+09 267.26 30-MAR-09:20 24.60 19.93
April 0.233147E+10 3700.40 09-APR-08:31 23.90 18.82 0.249805E+09 267.03 26-APR-10:00 27.80 22.40
May 0.273994E+10 3322.20 08-MAY-05:01 23.90 19.12 0.271017E+09 267.01 01-MAY-10:00 23.90 19.12
June 0.291676E+10 3363.42 03-JUN-04:01 26.60 23.89 0.270810E+09 267.00 14-JUN-09:20 28.17 23.37
July 0.299846E+10 3340.08 15-JUL-04:01 25.18 24.23 0.252510E+09 267.05 21-JUL-09:20 29.80 25.06
August 0.297574E+10 2934.79 07-AUG-04:01 25.68 24.34 0.280962E+09 267.19 23-AUG-09:20 30.97 25.77
September 0.280464E+10 3818.49 10-SEP-11:11 30.77 24.31 0.250217E+09 267.32 08-SEP-09:20 30.77 24.31
October 0.259990E+10 3055.56 14-OCT-05:01 23.98 22.48 0.256026E+09 267.54 23-OCT-09:20 28.50 23.45
November 0.209897E+10 2205.81 07-NOV-09:30 24.75 21.38 0.248268E+09 266.88 01-NOV-09:20 24.75 21.38
December 0.179008E+10 2364.88 03-DEC-10:21 21.65 17.67 0.234582E+09 266.88 06-DEC-09:39 25.73 21.39
                     
Annual Sum or Average 0.289436E+11         0.305872E+10        
Minimum of Months 0.174456E+10 2205.81   21.65 17.67 0.226152E+09 266.88   17.93 11.43
Maximum of Months 0.299846E+10 3818.49   30.77 24.34 0.280962E+09 267.54   30.97 25.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101755E+10 1430.00 14-JAN-05:02 23.90 21.32 0.151624E+09 165.88 06-JAN-10:50 23.90 21.32
February 0.990871E+09 1442.48 11-FEB-05:01 23.90 22.27 0.139689E+09 167.67 02-FEB-15:30 23.90 22.27
March 0.120026E+10 1302.23 12-MAR-13:41 24.90 18.25 0.168300E+09 168.54 07-MAR-13:39 24.90 18.25
April 0.126948E+10 1344.98 09-APR-13:11 27.93 19.41 0.153809E+09 168.96 28-APR-14:39 24.80 19.61
May 0.151768E+10 1519.93 27-MAY-04:02 24.40 23.65 0.168946E+09 171.03 26-MAY-12:50 24.40 23.65
June 0.163039E+10 1460.60 03-JUN-04:02 26.60 23.89 0.169109E+09 171.05 22-JUN-13:39 27.57 23.40
July 0.167455E+10 1457.83 15-JUL-04:01 25.18 24.23 0.155867E+09 170.27 18-JUL-09:30 29.40 24.72
August 0.167572E+10 1435.07 12-AUG-04:01 23.90 23.16 0.173344E+09 169.01 01-AUG-15:39 23.90 23.16
September 0.156742E+10 1502.51 16-SEP-04:01 23.90 23.08 0.153303E+09 169.29 15-SEP-15:00 23.90 23.08
October 0.146494E+10 1402.65 14-OCT-05:01 23.98 22.48 0.155509E+09 168.38 27-OCT-15:39 25.60 23.90
November 0.122261E+10 1355.56 29-NOV-05:01 25.00 19.79 0.151993E+09 166.95 29-NOV-17:00 26.70 24.69
December 0.105831E+10 1401.99 09-DEC-05:01 25.00 22.66 0.147214E+09 166.20 01-DEC-11:20 25.00 22.66
                     
Annual Sum or Average 0.162898E+11         0.188871E+10        
Minimum of Months 0.990871E+09 1302.23   23.90 18.25 0.139689E+09 165.88   23.90 18.25
Maximum of Months 0.167572E+10 1519.93   27.93 24.23 0.173344E+09 171.05   29.40 24.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.355079E+10 4884.29 14-JAN-05:02 23.90 21.32 0.538850E+09 582.67 06-JAN-10:30 23.90 21.32
February 0.336076E+10 4938.88 11-FEB-05:01 23.90 22.27 0.493729E+09 581.18 02-FEB-15:39 23.90 22.27
March 0.402064E+10 4221.30 12-MAR-13:41 24.90 18.25 0.591087E+09 584.15 07-MAR-11:00 24.90 18.25
April 0.405332E+10 4398.54 12-APR-04:01 24.40 22.16 0.529806E+09 584.71 27-APR-09:39 24.63 19.57
May 0.470770E+10 5127.20 27-MAY-04:02 24.40 23.65 0.571262E+09 586.02 25-MAY-16:00 24.40 23.65
June 0.497673E+10 4781.83 03-JUN-04:02 26.60 23.89 0.566675E+09 582.63 22-JUN-11:39 23.90 22.27
July 0.502226E+10 4917.52 15-JUL-04:01 25.18 24.23 0.520982E+09 578.89 07-JUL-07:30 25.18 24.23
August 0.512980E+10 4779.94 12-AUG-04:01 23.90 23.16 0.584056E+09 577.81 09-AUG-13:30 23.90 23.16
September 0.476993E+10 4951.20 16-SEP-04:02 23.90 23.08 0.519247E+09 576.29 06-SEP-08:30 23.90 23.08
October 0.453839E+10 4768.91 14-OCT-05:02 23.98 22.48 0.536272E+09 577.87 27-OCT-15:50 25.60 23.90
November 0.394152E+10 4551.57 29-NOV-05:01 25.00 19.79 0.532251E+09 579.36 28-NOV-17:00 25.00 19.79
December 0.362579E+10 4737.53 09-DEC-05:01 25.00 22.66 0.522601E+09 578.35 29-DEC-14:50 21.70 17.90
                     
Annual Sum or Average 0.516976E+11         0.650682E+10        
Minimum of Months 0.336076E+10 4221.30   23.90 18.25 0.493729E+09 576.29   21.70 17.90
Maximum of Months 0.512980E+10 5127.20   26.60 24.23 0.591087E+09 586.02   25.60 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.130576E+10 1782.32 14-JAN-05:01 23.90 21.32 0.184420E+09 203.74 06-JAN-10:50 23.90 21.32
February 0.125202E+10 1906.13 11-FEB-05:01 23.90 22.27 0.170412E+09 205.11 02-FEB-15:09 23.90 22.27
March 0.149596E+10 1607.39 12-MAR-13:41 24.90 18.25 0.205348E+09 205.87 07-MAR-13:20 24.90 18.25
April 0.155306E+10 1630.44 13-APR-04:01 24.40 22.09 0.187107E+09 205.79 20-APR-11:00 26.10 19.16
May 0.184885E+10 1857.24 27-MAY-04:02 24.40 23.65 0.205003E+09 205.88 24-MAY-16:19 24.40 23.65
June 0.197527E+10 1870.27 03-JUN-04:01 26.60 23.89 0.204706E+09 205.88 21-JUN-16:19 23.90 22.10
July 0.202189E+10 1908.61 15-JUL-04:01 25.18 24.23 0.188446E+09 205.85 18-JUL-09:39 29.40 24.80
August 0.202967E+10 1746.05 12-AUG-04:01 23.90 23.16 0.209808E+09 204.87 10-AUG-10:50 23.90 23.16
September 0.189886E+10 1905.46 16-SEP-04:01 23.90 23.08 0.185612E+09 205.39 15-SEP-15:00 23.90 23.08
October 0.178783E+10 1740.50 14-OCT-05:01 23.98 22.48 0.188816E+09 204.62 27-OCT-15:39 25.60 23.90
November 0.151517E+10 1676.15 29-NOV-05:01 25.00 19.79 0.185180E+09 204.20 29-NOV-11:50 26.60 25.08
December 0.134603E+10 1722.54 09-DEC-05:01 25.00 22.66 0.179397E+09 202.93 01-DEC-11:20 25.00 22.66
                     
Annual Sum or Average 0.200304E+11         0.229426E+10        
Minimum of Months 0.125202E+10 1607.39   23.90 18.25 0.170412E+09 202.93   23.90 18.25
Maximum of Months 0.202967E+10 1908.61   26.60 24.23 0.209808E+09 205.88   29.40 25.08



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.192498E+10 2588.74 14-JAN-05:02 23.90 21.32 0.271029E+09 292.24 06-JAN-10:30 23.90 21.32
February 0.181600E+10 2626.05 11-FEB-05:01 23.90 22.27 0.248324E+09 292.08 08-FEB-17:30 23.90 22.27
March 0.216504E+10 2284.58 12-MAR-13:41 24.90 18.25 0.297575E+09 293.22 07-MAR-11:00 24.90 18.25
April 0.218319E+10 2362.22 13-APR-04:01 24.40 22.09 0.266813E+09 293.01 27-APR-09:39 24.63 19.57
May 0.253083E+10 2707.54 27-MAY-04:02 24.40 23.65 0.287487E+09 293.55 25-MAY-16:00 24.40 23.65
June 0.267716E+10 2535.50 03-JUN-04:02 26.60 23.89 0.285100E+09 292.12 22-JUN-11:39 23.90 22.27
July 0.271479E+10 2609.24 15-JUL-04:01 25.18 24.23 0.262088E+09 290.75 07-JUL-07:30 25.18 24.23
August 0.276751E+10 2541.14 12-AUG-04:01 23.90 23.16 0.293856E+09 290.35 29-AUG-08:20 27.57 23.71
September 0.258269E+10 2617.18 16-SEP-04:02 23.90 23.08 0.261245E+09 289.77 06-SEP-08:30 23.90 23.08
October 0.246342E+10 2526.17 14-OCT-05:02 23.98 22.48 0.269752E+09 289.89 27-OCT-15:50 25.60 23.90
November 0.213247E+10 2439.76 29-NOV-05:01 25.00 19.79 0.267700E+09 291.33 28-NOV-17:49 25.00 19.79
December 0.196502E+10 2523.36 09-DEC-05:01 25.00 22.66 0.262883E+09 290.23 29-DEC-14:50 21.70 17.90
                     
Annual Sum or Average 0.279231E+11         0.327385E+10        
Minimum of Months 0.181600E+10 2284.58   23.90 18.25 0.248324E+09 289.77   21.70 17.90
Maximum of Months 0.276751E+10 2707.54   26.60 24.23 0.297575E+09 293.55   27.57 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.478269E+09 1001.82 14-JAN-05:01 23.90 21.32 34046988.40 38.20 13-JAN-07:10 23.90 21.32
February 0.452587E+09 1003.91 11-FEB-05:01 23.90 22.27 30949083.60 38.20 10-FEB-07:10 23.90 22.27
March 0.525921E+09 920.43 01-MAR-07:01 13.07 12.09 36955298.53 38.26 31-MAR-06:10 22.30 18.89
April 0.509657E+09 906.14 04-APR-06:03 21.70 19.64 32962405.41 38.11 04-APR-06:10 21.70 19.64
May 0.554281E+09 926.07 08-MAY-05:01 23.90 19.12 35444593.79 37.64 02-MAY-06:10 23.90 19.12
June 0.565005E+09 869.72 06-JUN-05:02 23.98 23.24 35302385.69 37.00 06-JUN-06:10 24.68 23.80
July 0.560949E+09 886.52 07-JUL-06:03 23.68 21.85 32939175.38 37.48 07-JUL-06:10 23.68 21.85
August 0.600203E+09 868.05 29-AUG-06:03 22.98 22.46 36831657.04 37.13 18-AUG-06:10 22.98 22.46
September 0.570533E+09 884.38 16-SEP-04:01 23.90 23.08 32885387.75 37.20 27-SEP-06:10 23.30 22.07
October 0.573232E+09 924.03 14-OCT-05:01 23.98 22.48 34101245.86 38.02 20-OCT-06:10 21.78 20.17
November 0.523696E+09 907.27 16-NOV-07:03 21.20 18.94 33659490.44 38.10 22-NOV-07:10 23.40 20.81
December 0.481313E+09 968.28 09-DEC-05:01 25.00 22.66 33013244.08 38.26 07-DEC-07:10 25.00 22.66
                     
Annual Sum or Average 0.639565E+10         0.409091E+09        
Minimum of Months 0.452587E+09 868.05   13.07 12.09 30949083.60 37.00   21.70 18.89
Maximum of Months 0.600203E+09 1003.91   25.00 23.24 36955298.53 38.26   25.00 23.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.476416E+09 991.54 14-JAN-05:01 23.90 21.32 34049644.78 38.13 13-JAN-07:10 23.90 21.32
February 0.439101E+09 930.44 23-FEB-07:01 14.68 12.86 30925972.12 38.07 02-FEB-07:10 14.68 12.86
March 0.499297E+09 926.41 01-MAR-07:01 13.07 12.09 36887270.29 37.89 02-MAR-07:10 15.18 13.78
April 0.457107E+09 886.02 06-APR-06:03 22.30 19.91 32833317.96 37.34 07-APR-06:10 23.40 20.30
May 0.485685E+09 824.10 11-MAY-06:03 21.88 20.94 35287245.12 36.84 11-MAY-06:10 21.88 20.94
June 0.493162E+09 748.68 15-JUN-06:01 27.20 23.94 35138780.58 36.12 22-JUN-06:10 24.32 23.63
July 0.481478E+09 742.77 20-JUL-06:01 26.28 24.57 32739859.35 36.32 07-JUL-06:10 26.28 24.57
August 0.519102E+09 783.47 09-AUG-06:01 26.28 23.75 36653412.21 36.15 29-AUG-06:10 22.98 22.46
September 0.500695E+09 765.95 01-SEP-06:01 26.10 22.39 32722854.86 36.38 06-SEP-06:10 23.40 22.67
October 0.512953E+09 908.86 14-OCT-05:01 23.98 22.48 33958555.56 37.31 20-OCT-06:10 21.78 20.17
November 0.490870E+09 903.40 28-NOV-07:03 20.68 18.41 33599513.19 38.00 28-NOV-07:10 20.68 18.41
December 0.472149E+09 922.55 14-DEC-07:01 15.78 15.78 32997611.27 38.17 05-DEC-07:10 15.78 15.78
                     
Annual Sum or Average 0.582801E+10         0.407794E+09        
Minimum of Months 0.439101E+09 742.77   13.07 12.09 30925972.12 36.12   14.68 12.86
Maximum of Months 0.519102E+09 991.54   27.20 24.57 36887270.29 38.17   26.28 24.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.435355E+09 878.77 27-JAN-07:01 12.38 8.00 33976794.61 37.39 13-JAN-07:10 12.38 8.00
February 0.399426E+09 882.19 23-FEB-07:01 14.68 12.86 30858790.64 37.32 23-FEB-07:10 14.68 12.86
March 0.449190E+09 877.31 02-MAR-07:01 15.18 13.78 36804384.02 37.21 02-MAR-07:10 15.18 13.78
April 0.409433E+09 742.30 07-APR-06:03 23.40 20.30 32753615.38 36.50 07-APR-06:10 23.40 20.30
May 0.440803E+09 660.30 25-MAY-06:03 22.98 21.70 35206511.80 36.16 25-MAY-06:10 22.98 21.70
June 0.456164E+09 658.22 08-JUN-06:01 28.30 25.49 35065932.96 35.62 22-JUN-06:10 24.32 23.63
July 0.446948E+09 664.82 14-JUL-06:01 27.30 25.19 32659213.92 35.67 07-JUL-06:10 27.30 25.19
August 0.480373E+09 638.50 11-AUG-06:01 28.30 23.57 36585532.96 35.35 29-AUG-06:10 22.98 22.46
September 0.463778E+09 671.43 22-SEP-06:01 27.80 25.38 32663801.08 35.60 27-SEP-06:10 23.30 22.07
October 0.471892E+09 806.54 14-OCT-05:01 23.98 22.48 33896605.53 36.54 20-OCT-06:10 21.78 20.17
November 0.448187E+09 855.31 16-NOV-07:03 21.20 18.94 33525202.36 37.16 16-NOV-07:10 21.20 18.94
December 0.430446E+09 876.55 14-DEC-07:01 15.78 15.78 32923879.74 37.41 05-DEC-07:10 15.78 15.78
                     
Annual Sum or Average 0.533200E+10         0.406920E+09        
Minimum of Months 0.399426E+09 638.50   12.38 8.00 30858790.64 35.35   12.38 8.00
Maximum of Months 0.480373E+09 882.19   28.30 25.49 36804384.02 37.41   27.30 25.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.407432E+09 958.02 20-JAN-07:01 14.90 11.74 37305748.48 41.61 06-JAN-07:10 14.90 11.74
February 0.400081E+09 951.71 23-FEB-07:01 14.68 12.86 33906443.01 41.67 02-FEB-07:10 14.68 12.86
March 0.485712E+09 952.21 01-MAR-07:01 13.07 12.09 40518284.73 41.71 10-MAR-07:10 23.40 22.10
April 0.491430E+09 949.50 07-APR-06:03 23.40 20.30 36142413.40 41.78 07-APR-06:10 23.40 20.30
May 0.565884E+09 975.39 08-MAY-05:01 23.90 19.12 38933331.53 41.65 11-MAY-06:10 21.88 20.94
June 0.587862E+09 925.74 14-JUN-06:03 23.48 22.19 38801780.75 41.33 06-JUN-06:10 23.48 22.19
July 0.572586E+09 937.67 07-JUL-06:03 23.68 21.85 36175413.35 41.42 07-JUL-06:10 23.68 21.85
August 0.590141E+09 933.35 29-AUG-06:03 22.98 22.46 40425339.70 41.11 29-AUG-06:10 22.98 22.46
September 0.539806E+09 936.83 06-SEP-06:03 23.40 22.67 36042528.99 41.28 06-SEP-06:10 23.40 22.67
October 0.510420E+09 953.71 14-OCT-05:01 23.98 22.48 37317654.43 41.12 27-OCT-06:10 22.98 21.95
November 0.456495E+09 942.41 22-NOV-07:03 23.40 20.81 36887037.37 41.48 22-NOV-07:10 23.40 20.81
December 0.417883E+09 949.72 20-DEC-07:01 11.60 9.47 36162095.00 41.50 01-DEC-07:10 11.60 9.47
                     
Annual Sum or Average 0.602573E+10         0.448618E+09        
Minimum of Months 0.400081E+09 925.74   11.60 9.47 33906443.01 41.11   11.60 9.47
Maximum of Months 0.590141E+09 975.39   23.98 22.67 40518284.73 41.78   23.68 22.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.450935E+09 1006.00 20-JAN-07:01 14.90 11.74 37386789.43 42.08 06-JAN-07:10 14.90 11.74
February 0.439673E+09 1078.44 11-FEB-05:01 23.90 22.27 33981751.65 42.08 02-FEB-07:10 23.90 22.27
March 0.532972E+09 998.10 01-MAR-07:01 13.07 12.09 40590651.68 42.08 09-MAR-07:10 22.80 20.25
April 0.535669E+09 987.41 19-APR-06:01 15.68 12.27 36209233.92 42.08 07-APR-06:10 15.68 12.27
May 0.615427E+09 1031.11 08-MAY-05:01 23.90 19.12 39007222.80 42.08 11-MAY-06:10 21.88 20.94
June 0.635757E+09 970.70 06-JUN-05:02 23.98 23.24 38867378.72 41.94 06-JUN-06:10 24.68 23.80
July 0.619582E+09 1086.20 15-JUL-04:01 25.18 24.23 36243557.04 41.95 07-JUL-06:10 25.18 24.23
August 0.638779E+09 978.06 29-AUG-06:03 22.98 22.46 40492938.92 41.80 29-AUG-06:10 22.98 22.46
September 0.585172E+09 1078.94 16-SEP-04:01 23.90 23.08 36108741.31 41.93 06-SEP-06:10 23.90 23.08
October 0.556814E+09 1000.84 14-OCT-05:01 23.98 22.48 37391016.11 41.71 27-OCT-06:10 22.98 21.95
November 0.501585E+09 984.92 16-NOV-07:03 21.20 18.94 36964168.55 42.01 22-NOV-07:10 23.40 20.81
December 0.461478E+09 997.34 20-DEC-07:01 11.60 9.47 36245492.43 42.02 08-DEC-07:10 11.60 9.47
                     
Annual Sum or Average 0.657384E+10         0.449489E+09        
Minimum of Months 0.439673E+09 970.70   11.60 9.47 33981751.65 41.71   11.60 9.47
Maximum of Months 0.638779E+09 1086.20   25.18 24.23 40590651.68 42.08   25.18 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.428141E+09 991.86 20-JAN-07:01 14.90 11.74 37350902.61 41.84 06-JAN-07:10 14.90 11.74
February 0.418249E+09 985.72 23-FEB-07:01 14.68 12.86 33943238.21 41.93 02-FEB-07:10 14.68 12.86
March 0.505603E+09 985.44 01-MAR-07:01 13.07 12.09 40552877.82 41.90 09-MAR-07:10 22.80 20.25
April 0.508116E+09 977.97 07-APR-06:03 23.40 20.30 36168521.32 41.92 07-APR-06:10 23.40 20.30
May 0.583694E+09 1015.58 08-MAY-05:01 23.90 19.12 38957556.26 41.75 11-MAY-06:10 21.88 20.94
June 0.603729E+09 954.75 06-JUN-05:02 23.98 23.24 38817737.72 41.39 06-JUN-06:10 24.68 23.80
July 0.588479E+09 963.80 07-JUL-06:03 23.68 21.85 36193000.42 41.48 07-JUL-06:10 23.68 21.85
August 0.606484E+09 962.39 29-AUG-06:03 22.98 22.46 40442576.94 41.30 29-AUG-06:10 22.98 22.46
September 0.555917E+09 965.53 06-SEP-06:03 23.40 22.67 36061911.64 41.45 06-SEP-06:10 23.40 22.67
October 0.529083E+09 986.37 14-OCT-05:01 23.98 22.48 37346562.09 41.23 27-OCT-06:10 22.98 21.95
November 0.476157E+09 972.57 16-NOV-07:03 21.20 18.94 36923831.92 41.69 22-NOV-07:10 23.40 20.81
December 0.438154E+09 984.28 20-DEC-07:01 11.60 9.47 36206648.11 41.71 08-DEC-07:10 11.60 9.47
                     
Annual Sum or Average 0.624180E+10         0.448965E+09        
Minimum of Months 0.418249E+09 954.75   11.60 9.47 33943238.21 41.23   11.60 9.47
Maximum of Months 0.606484E+09 1015.58   23.98 23.24 40552877.82 41.93   24.68 23.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.127746E+09 261.94 14-JAN-05:01 23.90 21.32 4577544.22 5.08 30-JAN-07:10 21.10 20.23
February 0.134950E+09 294.90 18-FEB-07:03 23.80 20.78 4246216.37 5.13 17-FEB-07:10 23.80 20.78
March 0.171175E+09 365.02 14-MAR-06:03 23.30 22.57 5074969.45 5.30 14-MAR-06:10 23.30 22.57
April 0.204273E+09 392.83 16-APR-19:51 26.10 22.26 4627171.73 5.35 14-APR-06:10 26.10 22.26
May 0.264512E+09 481.35 29-MAY-17:32 31.30 24.51 5003354.01 5.36 15-MAY-06:10 31.30 24.51
June 0.285362E+09 458.11 25-JUN-17:51 29.40 24.47 4989894.82 5.36 23-JUN-06:10 29.40 24.47
July 0.296379E+09 474.81 30-JUL-16:12 29.80 25.10 4669168.16 5.36 14-JUL-06:10 29.80 25.10
August 0.292603E+09 478.35 06-AUG-16:01 28.22 23.94 5199606.22 5.36 23-AUG-06:10 26.88 24.72
September 0.268881E+09 478.59 10-SEP-16:31 31.10 24.47 4643346.70 5.36 11-SEP-06:10 26.70 24.27
October 0.235052E+09 418.93 04-OCT-04:01 26.10 25.71 4797078.14 5.36 30-OCT-06:10 26.70 25.38
November 0.182661E+09 362.60 24-NOV-07:03 21.10 21.10 4680814.75 5.29 30-NOV-07:10 25.60 24.11
December 0.138609E+09 343.39 01-DEC-07:03 23.30 18.59 4479157.17 5.22 01-DEC-07:10 23.30 18.59
                     
Annual Sum or Average 0.260220E+10         56988321.74        
Minimum of Months 0.127746E+09 261.94   21.10 18.59 4246216.37 5.08   21.10 18.59
Maximum of Months 0.296379E+09 481.35   31.30 25.71 5199606.22 5.36   31.30 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.365324E+09 626.59 26-JAN-06:12 10.60 8.23 45640211.63 51.01 30-JAN-07:10 21.10 20.23
February 0.337292E+09 632.95 11-FEB-05:01 23.90 22.27 41461550.28 51.01 06-FEB-07:10 23.90 22.27
March 0.400924E+09 628.21 21-MAR-05:12 11.33 9.18 49433079.54 51.02 13-MAR-06:10 11.33 9.18
April 0.376169E+09 621.52 26-APR-05:12 20.60 19.80 44061400.67 51.01 10-APR-06:10 20.60 19.80
May 0.411422E+09 637.16 12-MAY-04:01 23.98 22.02 47402632.39 51.01 02-MAY-06:10 23.98 22.02
June 0.421688E+09 635.98 22-JUN-04:01 25.50 23.68 47241704.05 51.01 12-JUN-06:10 25.50 23.68
July 0.409637E+09 629.97 15-JUL-04:01 25.18 24.23 44067295.64 51.01 07-JUL-06:10 25.18 24.23
August 0.437075E+09 568.68 29-AUG-05:12 23.13 22.73 49256605.67 51.01 29-AUG-06:10 22.98 22.46
September 0.403939E+09 636.15 15-SEP-04:01 24.40 22.75 43947164.89 51.01 05-SEP-06:10 24.40 22.75
October 0.399635E+09 619.48 20-OCT-05:12 21.70 19.91 45543417.13 51.01 20-OCT-06:10 21.78 20.17
November 0.370910E+09 628.36 29-NOV-05:01 25.00 19.79 45031651.40 51.01 09-NOV-07:10 25.00 19.79
December 0.362373E+09 625.46 20-DEC-06:12 12.77 10.60 44217016.23 51.01 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.469639E+10         0.547304E+09        
Minimum of Months 0.337292E+09 568.68   10.60 8.23 41461550.28 51.01   11.33 9.18
Maximum of Months 0.437075E+09 637.16   25.50 24.23 49433079.54 51.02   25.50 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.586565E+09 1003.37 14-JAN-05:01 23.90 21.32 85575374.34 95.64 30-JAN-07:10 21.10 20.23
February 0.546111E+09 1019.96 11-FEB-05:01 23.90 22.27 77759699.57 95.64 06-FEB-07:10 23.90 22.27
March 0.656376E+09 997.71 21-MAR-05:12 11.33 9.18 92736635.89 95.64 13-MAR-06:10 11.33 9.18
April 0.626482E+09 994.85 26-APR-05:12 20.60 19.80 82704078.76 95.64 10-APR-06:10 20.60 19.80
May 0.695209E+09 1026.42 12-MAY-04:01 23.98 22.02 89002032.19 95.64 22-MAY-06:10 23.17 20.96
June 0.713911E+09 1024.22 22-JUN-04:01 25.50 23.68 88692890.49 95.64 12-JUN-06:10 25.50 23.68
July 0.694779E+09 1022.72 15-JUL-04:01 25.18 24.23 82760724.39 95.64 07-JUL-06:10 25.18 24.23
August 0.736200E+09 1014.10 30-AUG-04:01 25.50 23.18 92463261.28 95.64 29-AUG-06:10 25.50 23.18
September 0.676215E+09 1022.19 15-SEP-04:01 24.40 22.75 82505749.71 95.64 11-SEP-06:10 24.40 22.75
October 0.663087E+09 1007.98 17-OCT-04:01 24.32 19.13 85473647.22 95.64 20-OCT-06:10 21.78 20.17
November 0.609360E+09 1015.48 29-NOV-05:01 25.00 19.79 84484336.61 95.64 09-NOV-07:10 25.00 19.79
December 0.586159E+09 998.16 09-DEC-05:01 25.00 22.66 82932919.38 95.64 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.779045E+10         0.102709E+10        
Minimum of Months 0.546111E+09 994.85   11.33 9.18 77759699.57 95.64   11.33 9.18
Maximum of Months 0.736200E+09 1026.42   25.50 24.23 92736635.89 95.64   25.50 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.730254E+09 1231.33 14-JAN-05:01 23.90 21.32 0.102812E+09 114.77 30-JAN-07:10 21.10 20.23
February 0.679852E+09 1254.16 11-FEB-05:01 23.90 22.27 93418060.05 114.77 06-FEB-07:10 23.90 22.27
March 0.816179E+09 1211.11 03-MAR-06:12 21.10 17.01 0.111392E+09 114.77 13-MAR-06:10 22.12 20.68
April 0.777837E+09 1229.74 12-APR-04:01 24.40 22.16 99351301.08 114.77 10-APR-06:10 24.40 22.16
May 0.865012E+09 1259.36 09-MAY-04:01 24.32 19.60 0.106910E+09 114.77 22-MAY-06:10 23.17 20.96
June 0.884527E+09 1255.59 22-JUN-04:01 25.50 23.68 0.106515E+09 114.77 12-JUN-06:10 25.50 23.68
July 0.860157E+09 1253.33 15-JUL-04:01 25.18 24.23 99401882.78 114.77 07-JUL-06:10 25.18 24.23
August 0.910217E+09 1242.37 30-AUG-04:01 25.50 23.18 0.111038E+09 114.77 14-AUG-06:10 25.50 23.18
September 0.835232E+09 1250.39 15-SEP-04:01 24.40 22.75 99093259.45 114.77 05-SEP-06:10 24.40 22.75
October 0.820934E+09 1235.99 17-OCT-04:01 24.32 19.13 0.102660E+09 114.77 16-OCT-06:10 24.32 19.13
November 0.758448E+09 1246.64 29-NOV-05:01 25.00 19.79 0.101496E+09 114.77 09-NOV-07:10 25.00 19.79
December 0.731344E+09 1224.29 09-DEC-05:01 25.00 22.66 99650966.53 114.77 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.966999E+10         0.123374E+10        
Minimum of Months 0.679852E+09 1211.11   21.10 17.01 93418060.05 114.77   11.88 10.85
Maximum of Months 0.910217E+09 1259.36   25.50 24.23 0.111392E+09 114.77   25.50 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.162810E+10 3693.16 14-JAN-05:01 23.90 21.32 87153868.24 112.05 06-JAN-07:10 23.90 21.32
February 0.167847E+10 2864.77 26-FEB-09:09 19.87 15.54 79576854.92 113.72 17-FEB-07:10 19.87 15.54
March 0.214967E+10 3398.48 26-MAR-09:09 24.60 21.30 95180455.39 116.90 09-MAR-07:10 24.60 21.30
April 0.243033E+10 5227.30 09-APR-08:31 23.90 18.82 85535987.05 115.74 14-APR-06:10 23.40 22.27
May 0.286613E+10 4450.17 23-MAY-04:01 24.90 21.94 92523687.63 119.03 16-MAY-06:10 24.90 21.94
June 0.306830E+10 5191.38 04-JUN-10:31 30.93 25.16 92385434.86 119.03 30-JUN-06:10 26.10 24.46
July 0.313208E+10 5307.00 23-JUL-10:11 31.10 24.78 86475017.07 119.03 05-JUL-06:10 31.10 24.78
August 0.310209E+10 4460.72 18-AUG-04:01 27.70 24.78 96243519.97 119.03 03-AUG-06:10 27.70 24.78
September 0.289495E+10 5369.32 10-SEP-11:11 30.77 24.31 85875287.12 119.03 22-SEP-06:10 27.80 25.38
October 0.263080E+10 5042.05 09-OCT-10:51 32.20 23.83 88765702.74 117.74 04-OCT-06:10 32.20 23.83
November 0.204288E+10 3844.08 21-NOV-07:02 25.18 21.19 87111163.82 118.89 09-NOV-07:10 25.18 21.19
December 0.158590E+10 3605.58 09-DEC-05:01 25.00 22.66 84327721.92 115.45 01-DEC-07:10 25.00 22.66
                     
Annual Sum or Average 0.292097E+11         0.106115E+10        
Minimum of Months 0.158590E+10 2864.77   19.87 15.54 79576854.92 112.05   19.87 15.54
Maximum of Months 0.313208E+10 5369.32   32.20 25.16 96243519.97 119.03   32.20 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.920240E+09 2091.79 20-JAN-07:01 14.90 11.74 83649691.03 92.41 06-JAN-07:10 14.90 11.74
February 0.901421E+09 2092.23 23-FEB-07:01 14.68 12.86 76038577.97 92.89 17-FEB-07:10 14.68 12.86
March 0.111336E+10 2100.08 31-MAR-06:03 22.30 18.89 90864996.53 93.74 31-MAR-06:10 22.30 18.89
April 0.114514E+10 2100.70 18-APR-06:02 18.22 13.63 81153731.97 93.55 27-APR-06:10 21.78 18.41
May 0.130761E+10 2206.94 08-MAY-05:01 23.90 19.12 87437060.93 93.78 11-MAY-06:10 21.88 20.94
June 0.137727E+10 2077.43 07-JUN-06:02 26.20 24.62 87207409.63 93.81 06-JUN-06:10 26.20 24.62
July 0.137184E+10 2103.27 07-JUL-06:03 23.68 21.85 81394685.48 94.15 07-JUL-06:10 23.68 21.85
August 0.141419E+10 2100.44 09-AUG-06:02 26.28 23.75 90896996.45 92.79 18-AUG-06:10 27.38 24.43
September 0.131159E+10 2086.88 06-SEP-06:03 23.40 22.67 81097207.28 93.23 06-SEP-06:10 23.40 22.67
October 0.123872E+10 2124.67 14-OCT-05:01 23.98 22.48 83921804.25 93.05 27-OCT-06:10 22.98 21.95
November 0.105364E+10 2102.63 22-NOV-07:03 23.40 20.81 82779375.70 93.79 22-NOV-07:10 23.40 20.81
December 0.919405E+09 2090.62 01-DEC-07:03 23.30 18.59 81042032.45 93.42 01-DEC-07:10 23.30 18.59
                     
Annual Sum or Average 0.140744E+11         0.100748E+10        
Minimum of Months 0.901421E+09 2077.43   14.68 11.74 76038577.97 92.41   14.68 11.74
Maximum of Months 0.141419E+10 2206.94   26.28 24.62 90896996.45 94.15   27.38 24.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.477856E+10 8081.98 08-JAN-15:11 21.10 14.12 0.112315E+10 1254.88 02-JAN-07:10 21.10 14.12
February 0.451356E+10 8330.40 20-FEB-15:51 26.70 17.88 0.102206E+10 1254.85 10-FEB-07:10 26.70 17.88
March 0.532542E+10 7182.22 12-MAR-13:41 24.90 18.25 0.122038E+10 1254.87 08-MAR-07:10 24.90 18.25
April 0.524553E+10 8028.09 09-APR-13:51 27.20 19.18 0.109167E+10 1254.89 10-APR-06:10 20.87 18.76
May 0.593673E+10 7568.43 23-MAY-04:01 24.90 21.94 0.117487E+10 1254.90 02-MAY-06:10 24.90 21.94
June 0.615345E+10 7601.50 10-JUN-04:01 26.02 24.10 0.117069E+10 1254.86 12-JUN-06:10 25.68 24.45
July 0.615640E+10 7555.57 12-JUL-04:01 26.93 25.40 0.109502E+10 1254.87 07-JUL-06:10 26.93 25.40
August 0.654086E+10 7606.15 07-AUG-04:01 25.68 24.34 0.122120E+10 1254.86 30-AUG-06:10 24.68 23.02
September 0.613515E+10 8325.82 10-SEP-12:31 31.10 24.59 0.109159E+10 1254.88 05-SEP-06:10 31.10 24.59
October 0.605566E+10 8190.43 15-OCT-15:11 29.23 21.00 0.113031E+10 1254.89 20-OCT-06:10 21.78 20.17
November 0.534281E+10 8068.71 26-NOV-13:51 21.70 12.56 0.111253E+10 1254.90 09-NOV-07:10 21.70 12.56
December 0.484774E+10 8752.44 03-DEC-15:01 24.40 18.45 0.109047E+10 1254.85 05-DEC-07:10 18.58 17.38
                     
Annual Sum or Average 0.670319E+11         0.135439E+11        
Minimum of Months 0.451356E+10 7182.22   21.10 12.56 0.102206E+10 1254.85   18.58 12.56
Maximum of Months 0.654086E+10 8752.44   31.10 25.40 0.122120E+10 1254.90   31.10 25.40



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.153097E+10 3083.76 14-JAN-05:01 23.90 21.32 0.106983E+09 119.87 26-JAN-07:10 10.68 8.58
February 0.142132E+10 3115.51 11-FEB-05:01 23.90 22.27 97205347.10 119.87 01-FEB-07:10 23.90 22.27
March 0.167193E+10 3012.09 02-MAR-06:12 15.00 13.91 0.115907E+09 119.87 30-MAR-06:10 22.88 19.49
April 0.157119E+10 2880.10 19-APR-06:01 15.68 12.27 0.103290E+09 119.87 11-APR-06:10 15.68 12.27
May 0.170403E+10 2877.81 08-MAY-05:01 23.90 19.12 0.111109E+09 119.87 02-MAY-06:10 23.90 19.12
June 0.174406E+10 2756.16 14-JUN-06:03 23.48 22.19 0.110690E+09 118.79 06-JUN-06:10 23.48 22.19
July 0.170515E+10 2789.64 07-JUL-06:03 23.68 21.85 0.103212E+09 119.66 07-JUL-06:10 23.68 21.85
August 0.181317E+10 2782.71 29-AUG-06:03 22.98 22.46 0.115418E+09 119.08 29-AUG-06:10 22.98 22.46
September 0.169316E+10 2946.54 16-SEP-04:01 23.90 23.08 0.102988E+09 119.45 06-SEP-06:10 23.90 23.08
October 0.167821E+10 2874.08 14-OCT-05:01 23.98 22.48 0.106754E+09 119.87 20-OCT-06:10 21.78 20.17
November 0.156277E+10 2924.79 16-NOV-06:12 21.10 18.68 0.105564E+09 119.87 09-NOV-07:10 21.10 18.68
December 0.152825E+10 2997.60 05-DEC-06:12 18.70 17.38 0.103673E+09 119.87 06-DEC-07:10 22.48 20.49
                     
Annual Sum or Average 0.196242E+11         0.128279E+10        
Minimum of Months 0.142132E+10 2756.16   15.00 12.27 97205347.10 118.79   10.68 8.58
Maximum of Months 0.181317E+10 3115.51   23.98 23.08 0.115907E+09 119.87   23.90 23.08



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.506865E+09 673.79 14-JAN-05:02 23.90 21.32 21550305.63 22.94 03-JAN-07:10 23.90 21.32
February 0.472583E+09 663.67 11-FEB-05:01 23.90 22.27 19614436.29 23.02 23-FEB-07:10 14.68 12.86
March 0.555493E+09 606.08 12-MAR-13:41 24.90 18.25 23434699.65 22.99 02-MAR-07:10 24.90 18.25
April 0.560327E+09 618.61 13-APR-04:01 24.40 22.09 20860200.44 22.99 04-APR-06:10 24.40 22.09
May 0.637772E+09 682.50 27-MAY-04:02 24.40 23.65 22293253.86 22.76 02-MAY-06:10 24.40 23.65
June 0.670548E+09 651.09 03-JUN-04:02 26.60 23.89 22109988.77 22.53 06-JUN-06:10 24.68 23.80
July 0.682314E+09 661.94 15-JUL-04:02 25.18 24.23 20568425.14 22.64 07-JUL-06:10 25.18 24.23
August 0.698708E+09 644.15 12-AUG-04:01 23.90 23.16 23043089.28 22.52 29-AUG-06:10 22.98 22.46
September 0.664119E+09 671.77 16-SEP-04:02 23.90 23.08 20555889.54 22.65 06-SEP-06:10 23.90 23.08
October 0.638156E+09 657.79 14-OCT-05:02 23.98 22.48 21378731.28 22.78 20-OCT-06:10 21.78 20.17
November 0.549573E+09 633.60 03-NOV-04:01 24.40 22.49 21214097.09 22.97 07-NOV-07:10 20.68 20.34
December 0.517989E+09 649.46 09-DEC-05:01 25.00 22.66 20892819.65 23.12 05-DEC-07:10 25.00 22.66
                     
Annual Sum or Average 0.715445E+10         0.257516E+09        
Minimum of Months 0.472583E+09 606.08   23.90 18.25 19614436.29 22.52   14.68 12.86
Maximum of Months 0.698708E+09 682.50   26.60 24.23 23434699.65 23.12   25.18 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.882133E+09 1658.84 11-JAN-06:12 14.40 13.13 51464075.33 68.87 26-JAN-07:10 10.68 8.58
February 0.816642E+09 1672.53 11-FEB-05:01 23.90 22.27 46727070.50 68.87 06-FEB-07:10 23.90 22.27
March 0.971425E+09 1662.93 21-MAR-05:12 11.33 9.18 55694814.58 68.87 13-MAR-06:10 11.33 9.18
April 0.914827E+09 1632.30 20-APR-05:12 21.10 15.61 49598778.29 68.87 11-APR-06:10 21.10 15.61
May 0.998901E+09 1666.25 26-MAY-04:01 23.90 22.01 53433008.41 68.87 02-MAY-06:10 23.90 22.01
June 0.102533E+10 1657.27 22-JUN-04:01 25.50 23.68 53222784.21 68.87 02-JUN-06:10 25.50 23.68
July 0.100029E+10 1662.28 15-JUL-04:01 25.18 24.23 49639322.72 68.87 07-JUL-06:10 25.18 24.23
August 0.105976E+10 1638.68 12-AUG-04:01 23.90 23.16 55494577.16 68.87 08-AUG-06:10 23.90 23.16
September 0.980508E+09 1660.24 08-SEP-04:01 24.40 22.81 49464974.29 68.87 27-SEP-06:10 23.30 22.07
October 0.963038E+09 1625.54 20-OCT-05:12 21.70 19.91 51342175.28 68.87 20-OCT-06:10 21.78 20.17
November 0.892598E+09 1660.85 29-NOV-05:01 25.00 19.79 50832721.39 68.87 08-NOV-07:10 25.00 19.79
December 0.878938E+09 1657.10 20-DEC-06:12 12.77 10.60 49805077.13 68.87 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.113844E+11         0.616719E+09        
Minimum of Months 0.816642E+09 1625.54   11.33 9.18 46727070.50 68.87   10.68 8.58
Maximum of Months 0.105976E+10 1672.53   25.50 24.23 55694814.58 68.87   25.50 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.967990E+09 1797.52 14-JAN-05:01 23.90 21.32 54396370.68 72.70 26-JAN-07:10 10.68 8.58
February 0.897132E+09 1818.99 11-FEB-05:01 23.90 22.27 49388313.03 72.70 06-FEB-07:10 23.90 22.27
March 0.106620E+10 1770.41 24-MAR-05:12 21.87 18.71 58857976.88 72.70 13-MAR-06:10 21.87 18.71
April 0.100983E+10 1782.25 12-APR-04:01 24.40 22.16 52427662.67 72.70 10-APR-06:10 24.40 22.16
May 0.110119E+10 1801.70 12-MAY-04:01 23.98 22.02 56467243.53 72.70 22-MAY-06:10 23.17 20.96
June 0.112364E+10 1789.29 22-JUN-04:01 25.50 23.68 56227851.14 72.70 26-JUN-06:10 25.78 24.55
July 0.109771E+10 1798.33 15-JUL-04:01 25.18 24.23 52455869.93 72.70 07-JUL-06:10 25.18 24.23
August 0.116559E+10 1788.29 31-AUG-04:01 26.02 23.27 58631989.54 72.70 08-AUG-06:10 26.02 23.27
September 0.107967E+10 1796.93 08-SEP-04:01 24.40 22.81 52279650.33 72.70 11-SEP-06:10 26.70 24.27
October 0.106834E+10 1795.82 14-OCT-05:02 23.98 22.48 54278070.86 72.70 20-OCT-06:10 21.78 20.17
November 0.988406E+09 1802.37 03-NOV-04:01 24.40 22.49 53734251.05 72.70 20-NOV-07:10 24.40 20.33
December 0.965644E+09 1789.94 09-DEC-05:01 25.00 22.66 52652508.03 72.70 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.125314E+11         0.651798E+09        
Minimum of Months 0.897132E+09 1770.41   21.87 18.71 49388313.03 72.70   10.68 8.58
Maximum of Months 0.116559E+10 1818.99   26.02 24.23 58857976.88 72.70   26.70 24.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.103283E+09 263.44 27-JAN-07:01 12.38 8.00 4214021.51 4.56 13-JAN-07:10 12.38 8.00
February 96608598.26 264.85 23-FEB-07:01 14.68 12.86 3826175.05 4.56 23-FEB-07:10 14.68 12.86
March 0.110209E+09 264.28 02-MAR-07:01 15.18 13.78 4565319.16 4.56 02-MAR-07:10 15.18 13.78
April 0.104083E+09 189.99 07-APR-06:03 23.40 20.30 4063629.45 4.47 07-APR-06:10 23.40 20.30
May 0.114537E+09 167.57 11-MAY-06:03 21.88 20.94 4364135.46 4.44 11-MAY-06:10 21.88 20.94
June 0.119768E+09 123.80 22-JUN-06:03 24.32 23.63 4345772.67 4.37 22-JUN-06:10 24.32 23.63
July 0.119200E+09 140.69 07-JUL-06:03 23.68 21.85 4040121.41 4.39 07-JUL-06:10 23.68 21.85
August 0.124845E+09 117.97 09-AUG-06:01 26.28 23.75 4534821.65 4.34 29-AUG-06:10 22.98 22.46
September 0.119948E+09 129.75 27-SEP-06:03 23.30 22.07 4045889.48 4.38 27-SEP-06:10 23.30 22.07
October 0.118652E+09 194.28 20-OCT-06:03 21.78 20.17 4203213.94 4.48 20-OCT-06:10 21.78 20.17
November 0.108909E+09 233.02 16-NOV-07:03 21.20 18.94 4158563.43 4.54 16-NOV-07:10 21.20 18.94
December 0.103351E+09 262.59 14-DEC-07:01 15.78 15.78 4081897.64 4.56 05-DEC-07:10 15.78 15.78
                     
Annual Sum or Average 0.134339E+10         50443560.84        
Minimum of Months 96608598.26 117.97   12.38 8.00 3826175.05 4.34   12.38 8.00
Maximum of Months 0.124845E+09 264.85   26.28 23.75 4565319.16 4.56   24.32 23.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.200251E+09 500.44 20-JAN-07:01 14.90 11.74 9039600.85 9.98 06-JAN-07:10 14.90 11.74
February 0.195815E+09 498.22 23-FEB-07:01 14.68 12.86 8214121.70 10.00 16-FEB-07:10 14.68 12.86
March 0.239087E+09 499.66 01-MAR-07:01 13.07 12.09 9816058.21 10.02 10-MAR-07:10 23.40 22.10
April 0.244041E+09 497.31 27-APR-06:03 21.78 18.41 8757842.63 10.04 27-APR-06:10 21.78 18.41
May 0.280245E+09 512.52 08-MAY-05:01 23.90 19.12 9435206.30 10.05 11-MAY-06:10 21.88 20.94
June 0.292773E+09 488.26 14-JUN-06:03 23.48 22.19 9405040.75 9.98 06-JUN-06:10 23.48 22.19
July 0.288241E+09 494.44 07-JUL-06:03 23.68 21.85 8770630.76 10.03 07-JUL-06:10 23.68 21.85
August 0.296878E+09 489.80 29-AUG-06:03 22.98 22.46 9800894.27 9.91 29-AUG-06:10 22.98 22.46
September 0.273045E+09 492.45 06-SEP-06:03 23.40 22.67 8739237.01 9.96 06-SEP-06:10 23.40 22.67
October 0.256930E+09 500.90 14-OCT-05:01 23.98 22.48 9047591.77 9.94 27-OCT-06:10 22.98 21.95
November 0.225389E+09 495.01 22-NOV-07:03 23.40 20.81 8938689.59 10.00 22-NOV-07:10 23.40 20.81
December 0.205647E+09 497.59 12-DEC-07:01 11.20 8.46 8761912.21 10.01 01-DEC-07:10 11.20 8.46
                     
Annual Sum or Average 0.299834E+10         0.108727E+09        
Minimum of Months 0.195815E+09 488.26   11.20 8.46 8214121.70 9.91   11.20 8.46
Maximum of Months 0.296878E+09 512.52   23.98 22.67 9816058.21 10.05   23.68 22.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.275292E+09 639.47 14-JAN-05:01 23.90 21.32 10881205.55 12.22 06-JAN-07:10 23.90 21.32
February 0.266187E+09 681.14 11-FEB-05:01 23.90 22.27 9888024.30 12.23 16-FEB-07:10 22.30 18.55
March 0.323455E+09 628.81 01-MAR-07:01 13.07 12.09 11807869.84 12.24 09-MAR-07:10 22.80 20.25
April 0.324551E+09 622.46 19-APR-06:01 15.68 12.27 10533397.85 12.24 07-APR-06:10 15.68 12.27
May 0.371906E+09 649.64 08-MAY-05:01 23.90 19.12 11348584.45 12.24 25-MAY-06:10 22.98 21.70
June 0.383934E+09 610.32 14-JUN-06:03 23.48 22.19 11307744.60 12.18 06-JUN-06:10 23.48 22.19
July 0.376465E+09 682.44 15-JUL-04:01 25.18 24.23 10546234.07 12.21 07-JUL-06:10 25.18 24.23
August 0.388342E+09 616.28 29-AUG-06:03 22.98 22.46 11782769.95 12.15 29-AUG-06:10 22.98 22.46
September 0.356771E+09 676.99 16-SEP-04:01 23.90 23.08 10507535.79 12.20 06-SEP-06:10 23.90 23.08
October 0.339672E+09 630.08 14-OCT-05:01 23.98 22.48 10880879.21 12.13 27-OCT-06:10 22.98 21.95
November 0.304634E+09 620.59 16-NOV-07:03 21.20 18.94 10755437.68 12.21 22-NOV-07:10 23.40 20.81
December 0.282314E+09 628.70 12-DEC-07:01 11.20 8.46 10548380.04 12.21 01-DEC-07:10 11.20 8.46
                     
Annual Sum or Average 0.399352E+10         0.130788E+09        
Minimum of Months 0.266187E+09 610.32   11.20 8.46 9888024.30 12.13   11.20 8.46
Maximum of Months 0.388342E+09 682.44   25.18 24.23 11807869.84 12.24   25.18 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.300585E+09 489.66 13-JAN-10:30 25.85 21.29 9216221.48 9.61 27-JAN-11:20 22.07 15.40
February 0.316035E+09 537.34 28-FEB-10:00 24.40 16.28 8488522.40 9.62 17-FEB-07:10 24.40 16.28
March 0.413730E+09 615.19 31-MAR-09:30 24.15 19.41 10194378.52 9.91 09-MAR-07:10 24.15 19.41
April 0.492512E+09 1141.45 09-APR-09:51 26.10 18.81 9171817.85 9.79 17-APR-06:10 18.98 16.80
May 0.588872E+09 910.74 08-MAY-05:01 23.90 19.12 9912939.61 10.23 16-MAY-06:10 25.28 21.69
June 0.632708E+09 1148.36 04-JUN-10:31 30.93 25.16 9902392.04 10.51 09-JUN-06:10 27.88 24.73
July 0.651261E+09 1183.93 23-JUL-10:11 31.10 24.78 9261137.63 10.30 21-JUL-06:10 31.10 24.78
August 0.635171E+09 764.95 02-AUG-06:01 27.20 23.52 10311434.09 10.30 01-AUG-06:10 27.20 23.52
September 0.591375E+09 1177.28 10-SEP-11:11 30.77 24.31 9203779.24 10.14 22-SEP-06:10 27.80 25.38
October 0.526382E+09 1000.09 09-OCT-10:51 32.20 23.83 9498651.06 9.90 04-OCT-06:10 32.20 23.83
November 0.390490E+09 594.11 07-NOV-09:30 24.75 21.38 9305878.30 10.14 22-NOV-07:10 23.40 20.81
December 0.293846E+09 508.27 08-DEC-10:20 26.47 22.65 8875768.48 9.77 01-DEC-07:10 26.47 22.65
                     
Annual Sum or Average 0.583297E+10         0.113343E+09        
Minimum of Months 0.293846E+09 489.66   23.90 16.28 8488522.40 9.61   18.98 15.40
Maximum of Months 0.651261E+09 1183.93   32.20 25.16 10311434.09 10.51   32.20 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.389162E+10 7691.17 14-JAN-05:01 23.90 21.32 0.268400E+09 359.23 02-JAN-07:10 23.90 21.32
February 0.374174E+10 7804.08 11-FEB-05:01 23.90 22.27 0.243916E+09 359.23 01-FEB-07:10 23.90 22.27
March 0.455736E+10 7520.99 07-MAR-06:12 20.00 18.87 0.291068E+09 359.23 13-MAR-06:10 22.12 20.68
April 0.463648E+10 7737.11 13-APR-04:01 24.40 22.09 0.259800E+09 359.24 10-APR-06:10 24.40 22.09
May 0.537149E+10 8195.56 27-MAY-04:02 24.40 23.65 0.280172E+09 359.23 22-MAY-06:10 24.40 23.65
June 0.561824E+10 8051.23 03-JUN-04:02 26.60 23.89 0.279084E+09 359.23 12-JUN-06:10 25.68 24.45
July 0.555536E+10 7941.47 15-JUL-04:02 25.18 24.23 0.260735E+09 359.23 07-JUL-06:10 25.18 24.23
August 0.576758E+10 7902.51 07-AUG-04:02 25.68 24.34 0.290916E+09 359.23 08-AUG-06:10 26.38 23.78
September 0.529537E+10 8057.66 16-SEP-04:02 23.90 23.08 0.259586E+09 359.23 05-SEP-06:10 23.90 23.08
October 0.503819E+10 7787.32 14-OCT-05:02 23.98 22.48 0.269149E+09 359.24 20-OCT-06:10 21.78 20.17
November 0.440208E+10 7732.07 03-NOV-04:01 24.40 22.49 0.265856E+09 359.23 20-NOV-07:10 24.40 20.33
December 0.398323E+10 7727.26 09-DEC-05:01 25.00 22.66 0.260101E+09 359.23 06-DEC-07:10 25.00 22.66
                     
Annual Sum or Average 0.578588E+11         0.322878E+10        
Minimum of Months 0.374174E+10 7520.99   20.00 18.87 0.243916E+09 359.23   21.78 20.17
Maximum of Months 0.576758E+10 8195.56   26.60 24.34 0.291068E+09 359.24   26.38 24.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.221547E+10 4423.83 14-JAN-05:01 23.90 21.32 0.158242E+09 177.26 30-JAN-07:10 21.10 20.23
February 0.207880E+10 4490.94 11-FEB-05:01 23.90 22.27 0.143806E+09 177.26 01-FEB-07:10 23.90 22.27
March 0.249722E+10 4299.89 02-MAR-06:12 15.00 13.91 0.171520E+09 177.26 13-MAR-06:10 22.12 20.68
April 0.242138E+10 4303.51 04-APR-05:12 21.70 19.78 0.152996E+09 177.26 11-APR-06:10 23.40 20.34
May 0.268230E+10 4405.92 10-MAY-04:01 25.00 22.65 0.164740E+09 177.26 22-MAY-06:10 23.17 20.96
June 0.275219E+10 4404.76 21-JUN-04:01 25.40 23.98 0.164176E+09 177.26 02-JUN-06:10 25.40 23.98
July 0.271007E+10 4473.00 15-JUL-04:01 25.18 24.23 0.153194E+09 177.26 07-JUL-06:10 25.18 24.23
August 0.284200E+10 4415.28 12-AUG-04:01 23.90 23.16 0.171170E+09 177.26 31-AUG-06:10 25.78 23.68
September 0.263310E+10 4442.15 16-SEP-04:01 23.90 23.08 0.152712E+09 177.26 05-SEP-06:10 23.90 23.08
October 0.256897E+10 4261.52 20-OCT-05:12 21.70 19.91 0.158195E+09 177.26 20-OCT-06:10 21.78 20.17
November 0.233624E+10 4287.89 07-NOV-06:12 20.20 19.86 0.156270E+09 177.26 08-NOV-07:10 21.10 20.43
December 0.223517E+10 4415.93 09-DEC-05:01 25.00 22.66 0.153382E+09 177.26 07-DEC-07:10 25.00 22.66
                     
Annual Sum or Average 0.299729E+11         0.190040E+10        
Minimum of Months 0.207880E+10 4261.52   15.00 13.91 0.143806E+09 177.26   21.10 20.17
Maximum of Months 0.284200E+10 4490.94   25.40 24.23 0.171520E+09 177.26   25.78 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.192230E+09 310.74 14-JAN-05:02 23.90 21.32 9014958.80 9.56 03-JAN-17:00 23.90 21.32
February 0.194067E+09 308.15 11-FEB-05:01 23.90 22.27 8218221.12 9.52 10-FEB-17:00 23.90 22.27
March 0.238885E+09 313.05 12-MAR-19:01 22.20 18.30 9844740.23 9.67 10-MAR-17:00 22.20 18.30
April 0.271387E+09 326.08 09-APR-19:11 23.70 19.18 8830635.45 9.65 25-APR-15:39 22.80 21.33
May 0.324939E+09 323.47 27-MAY-04:02 24.40 23.65 9580206.67 9.69 18-MAY-16:00 24.40 23.65
June 0.346405E+09 319.78 10-JUN-04:02 26.02 24.10 9536068.99 9.80 13-JUN-16:00 23.30 21.31
July 0.362164E+09 318.77 09-JUL-21:31 28.30 24.59 8898005.84 9.80 05-JUL-16:00 28.30 24.59
August 0.361099E+09 318.91 20-AUG-17:42 30.10 24.42 9912927.56 9.79 23-AUG-16:00 23.90 21.61
September 0.340913E+09 320.00 10-SEP-17:11 30.93 24.45 8824309.73 9.60 05-SEP-16:00 30.93 24.45
October 0.313043E+09 321.28 15-OCT-17:12 27.93 20.65 9111297.26 9.53 02-OCT-06:40 27.93 20.65
November 0.248478E+09 302.06 05-NOV-17:11 27.43 23.78 8966841.63 9.60 14-NOV-17:00 22.20 15.01
December 0.207140E+09 303.81 09-DEC-05:01 25.00 22.66 8761287.00 9.70 01-DEC-17:00 25.00 22.66
                     
Annual Sum or Average 0.340075E+10         0.109500E+09        
Minimum of Months 0.192230E+09 302.06   22.20 18.30 8218221.12 9.52   22.20 15.01
Maximum of Months 0.362164E+09 326.08   30.93 24.59 9912927.56 9.80   30.93 24.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 X-RAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.125772E+11 18278.12 27-JAN-07:01 12.38 8.00 0.692041E+09 765.36 02-JAN-07:10 12.38 8.00
February 0.114074E+11 18281.30 03-FEB-07:01 10.60 7.66 0.629805E+09 765.32 06-FEB-07:10 18.48 14.80
March 0.132415E+11 18275.33 21-MAR-06:01 10.60 8.77 0.750157E+09 765.29 22-MAR-06:10 13.30 12.49
April 0.121428E+11 16125.49 19-APR-06:01 15.68 12.27 0.670485E+09 765.28 17-APR-06:10 15.68 12.27
May 0.127647E+11 15719.39 08-MAY-05:01 23.90 19.12 0.720998E+09 765.28 31-MAY-06:10 25.28 24.33
June 0.125745E+11 14473.88 06-JUN-05:02 23.98 23.24 0.718264E+09 765.31 08-JUN-06:10 28.30 25.49
July 0.121974E+11 13325.37 07-JUL-05:12 23.30 21.52 0.671554E+09 765.30 14-JUL-06:10 27.30 25.19
August 0.130499E+11 13248.18 11-AUG-06:01 28.30 23.57 0.748876E+09 765.29 16-AUG-06:10 26.88 24.79
September 0.120226E+11 13605.84 01-SEP-06:01 26.10 22.39 0.669367E+09 765.30 22-SEP-06:10 27.80 25.38
October 0.123892E+11 14491.77 26-OCT-05:02 23.80 22.28 0.693011E+09 765.31 04-OCT-06:10 23.80 22.28
November 0.122158E+11 17988.87 13-NOV-07:01 12.30 7.88 0.684073E+09 765.30 27-NOV-07:10 10.37 9.01
December 0.123873E+11 18272.24 20-DEC-07:01 11.60 9.47 0.671307E+09 765.30 28-DEC-07:10 18.98 13.79
                     
Annual Sum or Average 0.148970E+12         0.831994E+10        
Minimum of Months 0.114074E+11 13248.18   10.60 7.66 0.629805E+09 765.28   10.37 8.00
Maximum of Months 0.132415E+11 18281.30   28.30 23.57 0.750157E+09 765.36   28.30 25.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.154332E+09 277.68 26-JAN-07:01 10.68 8.58 6569791.91 8.59 26-JAN-07:10 10.68 8.58
February 0.147576E+09 279.16 03-FEB-07:01 10.60 7.66 5964954.17 8.75 03-FEB-07:10 10.60 7.66
March 0.179026E+09 278.07 16-MAR-06:01 6.70 4.45 7119685.15 8.68 15-MAR-06:10 6.70 4.45
April 0.178521E+09 161.83 14-APR-12:50 30.50 22.74 6329730.36 8.07 19-APR-06:10 15.68 12.27
May 0.192727E+09 168.10 18-MAY-13:00 31.70 22.83 6837232.36 8.07 23-MAY-06:10 24.08 21.72
June 0.193477E+09 171.26 09-JUN-14:20 31.10 24.95 6825435.74 8.17 08-JUN-06:10 31.10 24.95
July 0.194423E+09 174.42 28-JUL-15:30 35.00 25.05 6365459.22 8.13 13-JUL-06:10 35.00 25.05
August 0.198131E+09 166.01 31-AUG-14:40 32.03 24.60 7114460.89 8.16 18-AUG-06:10 32.03 24.60
September 0.183618E+09 163.14 08-SEP-15:30 32.20 23.32 6334756.70 8.15 22-SEP-06:10 27.80 25.38
October 0.180854E+09 163.51 06-OCT-13:00 30.00 23.64 6555358.03 8.06 04-OCT-06:10 30.00 23.64
November 0.165973E+09 222.84 13-NOV-07:01 12.30 7.88 6480605.49 8.28 13-NOV-07:10 12.30 7.88
December 0.156230E+09 280.66 15-DEC-07:01 7.88 5.99 6355147.30 8.67 15-DEC-07:10 7.88 5.99
                     
Annual Sum or Average 0.212489E+10         78852617.35        
Minimum of Months 0.147576E+09 161.83   6.70 4.45 5964954.17 8.06   6.70 4.45
Maximum of Months 0.198131E+09 280.66   35.00 25.05 7119685.15 8.75   35.00 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.846454E+09 1146.69 06-JAN-07:03 22.88 20.20 69218431.30 73.75 06-JAN-07:10 22.88 20.20
February 0.857815E+09 1431.46 17-FEB-07:03 22.88 20.65 63070580.27 75.02 17-FEB-07:10 22.88 20.65
March 0.107687E+10 1490.30 14-MAR-06:03 23.30 22.57 75472225.85 76.31 14-MAR-06:10 23.30 22.57
April 0.117943E+10 1548.21 16-APR-14:51 31.70 21.16 67594510.71 77.44 13-APR-06:10 31.70 21.16
May 0.134325E+10 1829.83 29-MAY-16:01 33.03 24.50 73067762.47 78.63 30-MAY-06:10 23.40 22.58
June 0.136656E+10 1540.12 16-JUN-06:02 26.20 23.01 72965721.30 78.64 12-JUN-06:10 26.20 23.01
July 0.139706E+10 1864.91 04-JUL-16:01 31.42 25.15 68222936.39 78.64 05-JUL-06:10 26.28 24.22
August 0.139558E+10 1547.08 11-AUG-06:02 28.30 23.57 76036857.30 78.64 02-AUG-06:10 28.30 23.57
September 0.128913E+10 1562.41 01-SEP-06:01 26.10 22.39 67835318.89 78.64 11-SEP-06:10 26.70 24.27
October 0.123226E+10 1507.23 12-OCT-06:02 25.18 22.99 70028069.34 78.02 04-OCT-06:10 25.18 22.99
November 0.105879E+10 1504.11 21-NOV-07:02 25.18 21.19 68771890.75 77.56 30-NOV-07:10 25.60 24.11
December 0.892028E+09 1476.95 01-DEC-07:03 23.30 18.59 67216710.92 75.79 01-DEC-07:10 23.30 18.59
                     
Annual Sum or Average 0.139352E+11         0.839501E+09        
Minimum of Months 0.846454E+09 1146.69   22.88 18.59 63070580.27 73.75   22.88 18.59
Maximum of Months 0.139706E+10 1864.91   33.03 25.15 76036857.30 78.64   31.70 24.27



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.404430E+09 662.93 26-JAN-07:01 10.68 8.58 16975048.24 22.62 26-JAN-07:10 10.68 8.58
February 0.386375E+09 665.55 03-FEB-07:02 10.60 7.66 15412121.70 22.95 03-FEB-07:10 10.60 7.66
March 0.468804E+09 663.56 15-MAR-06:02 11.60 8.27 18394931.58 22.90 15-MAR-06:10 11.60 8.27
April 0.465437E+09 541.46 19-APR-06:01 15.68 12.27 16370081.02 21.60 13-APR-06:10 15.68 12.27
May 0.503247E+09 467.59 17-MAY-06:02 25.18 21.24 17680242.12 21.64 23-MAY-06:10 24.08 21.72
June 0.505361E+09 609.81 16-JUN-06:01 26.20 23.01 17645283.30 21.92 08-JUN-06:10 26.20 23.01
July 0.505830E+09 585.27 19-JUL-06:01 25.87 24.05 16464455.52 21.79 13-JUL-06:10 25.87 24.05
August 0.518259E+09 595.96 02-AUG-06:01 27.20 23.52 18391879.77 21.87 18-AUG-06:10 27.38 24.43
September 0.479375E+09 619.51 01-SEP-06:01 26.10 22.39 16382072.40 21.85 22-SEP-06:10 27.80 25.38
October 0.472923E+09 540.95 04-OCT-06:01 26.20 25.75 16954961.35 21.61 04-OCT-06:10 26.20 25.75
November 0.435015E+09 639.89 13-NOV-07:01 12.30 7.88 16750994.99 21.82 13-NOV-07:10 12.30 7.88
December 0.409141E+09 669.47 15-DEC-07:01 7.88 5.99 16424750.85 22.81 15-DEC-07:10 7.88 5.99
                     
Annual Sum or Average 0.555420E+10         0.203847E+09        
Minimum of Months 0.386375E+09 467.59   7.88 5.99 15412121.70 21.60   7.88 5.99
Maximum of Months 0.518259E+09 669.47   27.20 25.75 18394931.58 22.95   27.80 25.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.129293E+09 191.29 02-JAN-16:20 25.40 20.54 4421747.56 4.80 19-JAN-16:30 25.00 18.21
February 0.145443E+09 216.95 22-FEB-17:03 25.32 14.17 4105630.26 4.80 27-FEB-16:10 26.10 17.26
March 0.187582E+09 257.72 27-MAR-17:00 26.70 22.05 4949083.80 4.80 21-MAR-16:49 26.70 22.05
April 0.233965E+09 473.21 16-APR-16:51 31.10 22.32 4521275.81 4.86 13-APR-06:10 31.10 22.32
May 0.291493E+09 506.25 29-MAY-16:01 33.03 24.50 4952531.66 5.03 30-MAY-06:10 23.40 22.58
June 0.305559E+09 480.83 11-JUN-18:42 29.50 24.51 4959746.77 5.16 08-JUN-06:10 29.50 24.51
July 0.324621E+09 496.05 30-JUL-15:21 31.95 25.24 4641162.06 5.18 10-JUL-06:10 31.95 25.24
August 0.307349E+09 481.62 20-AUG-16:01 30.60 24.86 5162773.31 5.24 21-AUG-06:10 27.38 24.48
September 0.282698E+09 479.52 17-SEP-16:01 31.10 24.89 4600216.31 5.23 18-SEP-06:10 27.30 24.35
October 0.251770E+09 465.76 29-OCT-16:01 29.22 25.30 4724807.67 4.97 30-OCT-06:10 26.70 25.38
November 0.199031E+09 237.16 07-NOV-16:40 27.97 22.32 4558152.55 4.84 30-NOV-07:10 25.60 24.11
December 0.146031E+09 218.50 08-DEC-16:30 26.40 23.05 4323288.99 4.80 13-DEC-16:40 20.77 15.41
                     
Annual Sum or Average 0.280484E+10         55920416.74        
Minimum of Months 0.129293E+09 191.29   25.32 14.17 4105630.26 4.80   20.77 15.41
Maximum of Months 0.324621E+09 506.25   33.03 25.30 5162773.31 5.24   31.95 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 LOCKER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.644692E+09 897.90 27-JAN-07:01 12.38 8.00 68203459.18 76.52 06-JAN-07:10 12.38 8.00
February 0.621166E+09 956.26 03-FEB-06:12 10.93 7.57 61996388.39 76.52 08-FEB-07:10 20.18 19.04
March 0.756394E+09 895.28 20-MAR-06:01 10.50 8.55 74025121.81 76.52 13-MAR-06:10 10.50 8.55
April 0.759011E+09 1063.04 16-APR-14:51 31.70 21.16 66091191.38 76.52 06-APR-06:10 31.70 21.16
May 0.834490E+09 940.58 29-MAY-16:01 33.03 24.50 71294735.15 76.52 22-MAY-06:10 33.03 24.50
June 0.837145E+09 873.94 21-JUN-06:03 24.40 22.75 71130171.75 76.52 14-JUN-06:10 24.40 22.75
July 0.831502E+09 1078.52 04-JUL-16:01 31.42 25.15 66458687.81 76.52 07-JUL-06:10 23.68 21.85
August 0.853913E+09 886.49 31-AUG-06:01 25.78 23.68 74121413.22 76.52 30-AUG-06:10 25.78 23.68
September 0.784736E+09 891.38 01-SEP-06:01 26.10 22.39 66129339.01 76.52 06-SEP-06:10 23.40 22.67
October 0.773541E+09 878.72 12-OCT-06:02 25.18 22.99 68353707.70 76.52 20-OCT-06:10 21.78 20.17
November 0.710197E+09 896.00 13-NOV-07:01 12.30 7.88 67387948.81 76.52 28-NOV-07:10 20.68 18.41
December 0.655851E+09 899.27 13-DEC-07:01 12.48 11.76 66116236.24 76.52 21-DEC-07:10 11.88 10.85
                     
Annual Sum or Average 0.906264E+10         0.821308E+09        
Minimum of Months 0.621166E+09 873.94   10.50 7.57 61996388.39 76.52   10.50 8.00
Maximum of Months 0.853913E+09 1078.52   33.03 25.15 74121413.22 76.52   33.03 24.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.389597E+10 5139.74 27-JAN-07:01 12.38 8.00 0.432107E+09 484.01 02-JAN-07:10 12.38 8.00
February 0.380004E+10 5129.43 27-FEB-07:01 15.28 13.52 0.392919E+09 483.99 08-FEB-07:10 15.28 13.52
March 0.463194E+10 5118.31 21-MAR-06:01 10.60 8.77 0.469353E+09 484.00 13-MAR-06:10 10.60 8.77
April 0.475061E+10 6678.92 16-APR-14:51 31.70 21.16 0.419674E+09 484.01 10-APR-06:10 31.70 21.16
May 0.533010E+10 6711.92 29-MAY-15:21 33.05 24.42 0.452937E+09 484.00 22-MAY-06:10 33.05 24.42
June 0.540771E+10 6329.34 04-JUN-12:41 28.77 25.50 0.451957E+09 484.00 14-JUN-06:10 23.48 22.19
July 0.540170E+10 6777.20 30-JUL-12:41 32.98 25.43 0.422769E+09 484.00 07-JUL-06:10 32.98 25.43
August 0.549718E+10 6304.23 20-AUG-16:01 30.60 24.86 0.470837E+09 484.00 30-AUG-06:10 24.68 23.02
September 0.504903E+10 6269.72 10-SEP-16:01 31.10 24.83 0.420328E+09 484.00 05-SEP-06:10 31.10 24.83
October 0.491948E+10 5079.54 12-OCT-06:02 25.18 22.99 0.434150E+09 484.00 20-OCT-06:10 21.78 20.17
November 0.442979E+10 5124.82 13-NOV-07:01 12.30 7.88 0.427446E+09 484.00 28-NOV-07:10 20.68 18.41
December 0.397987E+10 5145.90 13-DEC-07:01 12.48 11.76 0.419088E+09 484.00 01-DEC-07:10 12.48 11.76
                     
Annual Sum or Average 0.570934E+11         0.521357E+10        
Minimum of Months 0.380004E+10 5079.54   10.60 7.88 0.392919E+09 483.99   10.60 8.00
Maximum of Months 0.549718E+10 6777.20   33.05 25.50 0.470837E+09 484.01   33.05 25.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.844306E+09 938.55 15-JAN-15:22 25.30 16.86 31684625.99 33.44 04-JAN-14:09 25.30 16.86
February 0.879376E+09 987.39 20-FEB-15:41 26.70 17.88 28928076.79 34.14 02-FEB-14:09 26.70 17.88
March 0.108304E+10 983.95 26-MAR-16:01 25.50 21.40 34653811.74 34.00 13-MAR-16:00 25.50 21.40
April 0.120810E+10 1164.58 16-APR-14:51 31.70 21.16 31314126.05 35.05 17-APR-15:00 31.70 20.29
May 0.138766E+10 1201.36 29-MAY-16:01 33.03 24.50 34334076.07 35.53 22-MAY-13:39 33.03 24.50
June 0.141041E+10 1127.11 04-JUN-12:42 28.77 25.50 34527903.37 35.76 01-JUN-14:00 28.77 25.50
July 0.145628E+10 1214.08 30-JUL-13:21 33.05 25.13 32344122.76 35.92 28-JUL-15:30 33.05 25.13
August 0.141987E+10 1097.86 06-AUG-14:42 31.78 25.16 35714744.01 35.36 15-AUG-15:39 31.10 25.31
September 0.133843E+10 1093.95 10-SEP-16:02 31.10 24.83 31546018.81 34.80 22-SEP-15:00 31.10 25.66
October 0.128432E+10 1021.98 22-OCT-16:42 27.38 22.61 32059783.37 34.24 02-OCT-16:30 27.38 22.61
November 0.109297E+10 988.43 05-NOV-10:41 26.02 24.85 31461979.31 33.73 29-NOV-13:20 26.70 24.55
December 0.906686E+09 987.39 10-DEC-14:31 28.90 22.80 30718011.62 33.63 01-DEC-12:50 28.90 22.80
                     
Annual Sum or Average 0.143115E+11         0.389287E+09        
Minimum of Months 0.844306E+09 938.55   25.30 16.86 28928076.79 33.44   25.30 16.86
Maximum of Months 0.145628E+10 1214.08   33.05 25.50 35714744.01 35.92   33.05 25.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.332847E+10 5994.66 16-JAN-10:11 19.47 15.50 20035562.58 22.32 02-JAN-07:10 19.47 15.50
February 0.328203E+10 5934.81 20-FEB-15:41 26.70 17.88 18229562.88 22.32 08-FEB-07:10 26.70 17.88
March 0.404674E+10 5814.89 12-MAR-10:41 23.22 17.37 21754928.02 22.32 03-MAR-07:10 23.22 17.37
April 0.431555E+10 6659.43 02-APR-10:01 24.68 20.54 19486668.16 22.32 10-APR-06:10 20.87 18.76
May 0.480616E+10 6825.06 07-MAY-10:01 28.40 21.86 21007036.68 22.32 09-MAY-06:10 24.18 19.97
June 0.487873E+10 6484.17 04-JUN-07:21 26.95 24.72 20946398.77 22.32 14-JUN-06:10 23.48 22.19
July 0.499432E+10 6887.80 30-JUL-11:21 33.05 24.63 19604052.40 22.32 07-JUL-06:10 33.05 24.63
August 0.495651E+10 5901.73 20-AUG-16:01 30.60 24.86 21826119.70 22.32 30-AUG-06:10 24.68 23.02
September 0.464427E+10 6013.56 24-SEP-10:01 29.68 24.62 19515396.01 22.32 06-SEP-06:10 29.68 24.62
October 0.448978E+10 5933.16 09-OCT-10:41 31.73 23.86 20160926.92 22.32 20-OCT-06:10 21.78 20.17
November 0.385907E+10 6101.09 26-NOV-09:51 20.00 15.93 19835102.27 22.32 28-NOV-07:10 20.68 18.41
December 0.334116E+10 6029.52 03-DEC-09:11 21.10 17.61 19432672.39 22.32 01-DEC-07:10 21.10 17.61
                     
Annual Sum or Average 0.509428E+11         0.241834E+09        
Minimum of Months 0.328203E+10 5814.89   19.47 15.50 18229562.88 22.32   19.47 15.50
Maximum of Months 0.499432E+10 6887.80   33.05 24.86 21826119.70 22.32   33.05 24.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.882579E+09 881.99 02-JAN-14:40 28.90 23.86 56195143.61 59.01 06-JAN-07:10 22.88 20.20
February 0.879158E+09 978.59 17-FEB-07:03 22.88 20.65 51147622.29 59.58 17-FEB-07:10 22.88 20.65
March 0.109952E+10 1130.13 14-MAR-06:03 23.30 22.57 61149682.31 60.26 14-MAR-06:10 23.30 22.57
April 0.116872E+10 1908.75 16-APR-14:51 31.70 21.16 54685575.75 60.80 13-APR-06:10 31.70 21.16
May 0.130707E+10 1534.40 17-MAY-06:02 25.18 21.24 59085457.15 61.88 23-MAY-06:10 24.08 21.72
June 0.132941E+10 1525.08 15-JUN-06:02 27.20 23.94 59026236.15 63.22 08-JUN-06:10 27.20 23.94
July 0.135069E+10 1934.33 30-JUL-13:21 33.05 25.13 55161301.15 62.28 14-JUL-06:10 33.05 25.13
August 0.134910E+10 1536.29 25-AUG-06:03 24.90 22.92 61497004.82 63.08 01-AUG-06:10 24.90 22.92
September 0.125224E+10 1559.81 01-SEP-06:01 26.10 22.39 54859307.59 62.80 19-SEP-06:10 27.20 24.31
October 0.120455E+10 1404.31 02-OCT-06:01 26.70 24.92 56621814.92 61.54 04-OCT-06:10 26.20 25.75
November 0.104378E+10 1453.78 30-NOV-07:02 25.60 24.11 55674462.62 61.34 30-NOV-07:10 25.60 24.11
December 0.897266E+09 1065.41 01-DEC-07:03 23.30 18.59 54474593.63 59.95 01-DEC-07:10 23.30 18.59
                     
Annual Sum or Average 0.137641E+11         0.679578E+09        
Minimum of Months 0.879158E+09 881.99   22.88 18.59 51147622.29 59.01   22.88 18.59
Maximum of Months 0.135069E+10 1934.33   33.05 25.13 61497004.82 63.22   33.05 25.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.864132E+10 13696.90 06-JAN-07:03 22.88 20.20 0.476635E+09 645.32 06-JAN-07:10 22.88 20.20
February 0.869045E+10 13764.04 02-FEB-07:03 22.88 20.91 0.434016E+09 645.34 02-FEB-07:10 22.88 20.91
March 0.107664E+11 13816.28 14-MAR-06:03 23.30 22.57 0.519332E+09 645.34 14-MAR-06:10 23.30 22.57
April 0.115447E+11 17480.16 16-APR-14:51 31.70 21.16 0.465005E+09 645.36 14-APR-06:10 31.70 21.16
May 0.131869E+11 17589.66 29-MAY-15:21 33.05 24.42 0.503363E+09 645.35 24-MAY-06:10 33.05 24.42
June 0.134724E+11 16932.51 11-JUN-14:41 31.20 24.47 0.502283E+09 645.36 14-JUN-06:10 23.48 22.19
July 0.136220E+11 17885.75 30-JUL-13:21 33.05 25.13 0.470026E+09 645.36 07-JUL-06:10 33.05 25.13
August 0.136015E+11 16874.85 06-AUG-14:42 31.78 25.16 0.523221E+09 645.36 30-AUG-06:10 24.68 23.02
September 0.125012E+11 15737.91 10-SEP-16:01 31.10 24.83 0.466563E+09 645.36 14-SEP-06:10 24.40 22.82
October 0.119295E+11 13973.55 12-OCT-06:02 25.18 22.99 0.482254E+09 645.35 13-OCT-06:10 25.10 23.53
November 0.104387E+11 13972.33 21-NOV-07:02 25.18 21.19 0.474013E+09 645.35 29-NOV-07:10 25.00 20.34
December 0.897540E+10 13784.95 01-DEC-07:03 23.30 18.59 0.462351E+09 645.35 01-DEC-07:10 23.30 18.59
                     
Annual Sum or Average 0.137370E+12         0.577906E+10        
Minimum of Months 0.864132E+10 13696.90   22.88 18.59 0.434016E+09 645.32   22.88 18.59
Maximum of Months 0.136220E+11 17885.75   33.05 25.16 0.523221E+09 645.36   33.05 25.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.233470E+10 2884.25 20-JAN-07:01 14.90 11.74 0.156614E+09 166.61 06-JAN-07:10 14.90 11.74
February 0.230238E+10 3625.41 03-FEB-07:01 10.60 7.66 0.142471E+09 168.34 02-FEB-07:10 10.60 7.66
March 0.283716E+10 3736.98 15-MAR-06:01 11.60 8.27 0.170315E+09 169.89 14-MAR-06:10 11.60 8.27
April 0.297354E+10 3855.40 12-APR-06:02 25.10 22.69 0.152196E+09 171.90 13-APR-06:10 24.50 22.18
May 0.329974E+10 3894.43 17-MAY-06:02 25.18 21.24 0.164345E+09 173.56 23-MAY-06:10 24.08 21.72
June 0.333138E+10 3881.20 16-JUN-06:02 26.20 23.01 0.164091E+09 176.28 08-JUN-06:10 26.20 23.01
July 0.338454E+10 4722.16 04-JUL-16:01 31.42 25.15 0.153325E+09 174.39 28-JUL-06:10 25.00 23.85
August 0.340659E+10 3905.20 11-AUG-06:02 28.30 23.57 0.171008E+09 176.00 01-AUG-06:10 28.30 23.57
September 0.316112E+10 3950.22 01-SEP-06:01 26.10 22.39 0.152546E+09 175.60 19-SEP-06:10 27.20 24.31
October 0.307191E+10 3825.19 12-OCT-06:02 25.18 22.99 0.157555E+09 172.61 04-OCT-06:10 25.18 22.99
November 0.271992E+10 3816.11 21-NOV-07:02 25.18 21.19 0.155027E+09 172.38 30-NOV-07:10 25.60 24.11
December 0.240793E+10 3328.85 01-DEC-07:03 23.30 18.59 0.151913E+09 168.73 01-DEC-07:10 23.30 18.59
                     
Annual Sum or Average 0.352309E+11         0.189141E+10        
Minimum of Months 0.230238E+10 2884.25   10.60 7.66 0.142471E+09 166.61   10.60 7.66
Maximum of Months 0.340659E+10 4722.16   31.42 25.15 0.171008E+09 176.28   28.30 24.31



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235849E+09 284.34 01-JAN-17:01 24.82 21.57 8951811.47 9.72 03-JAN-17:40 24.27 20.21
February 0.249066E+09 312.74 20-FEB-17:42 25.28 17.48 8168629.87 9.96 22-FEB-17:00 23.90 13.63
March 0.314803E+09 303.63 26-MAR-16:01 25.50 21.40 9785276.09 9.85 27-MAR-16:00 26.70 22.05
April 0.363886E+09 330.81 16-APR-14:51 31.70 21.16 8791891.99 10.09 24-APR-16:00 26.10 20.43
May 0.413551E+09 353.89 29-MAY-16:01 33.03 24.50 9565136.79 10.16 17-MAY-16:00 33.03 24.50
June 0.415644E+09 342.77 11-JUN-18:42 29.50 24.51 9546498.66 10.10 09-JUN-16:00 29.50 24.51
July 0.435629E+09 354.57 04-JUL-16:02 31.42 25.15 8963897.26 10.06 07-JUL-16:00 31.10 23.86
August 0.425985E+09 337.51 20-AUG-16:01 30.60 24.86 9951001.45 10.10 17-AUG-16:00 30.60 24.86
September 0.405328E+09 339.28 10-SEP-16:02 31.10 24.83 8829243.03 10.04 08-SEP-16:00 31.10 24.83
October 0.390042E+09 330.51 09-OCT-17:22 28.35 23.53 9071204.33 9.95 19-OCT-16:00 26.70 20.63
November 0.321348E+09 299.68 05-NOV-16:01 27.80 24.12 8916009.65 10.07 07-NOV-17:00 26.10 22.26
December 0.260991E+09 302.60 10-DEC-16:31 27.57 22.50 8695831.17 9.91 06-DEC-17:49 27.57 22.50
                     
Annual Sum or Average 0.423212E+10         0.109236E+09        
Minimum of Months 0.235849E+09 284.34   24.82 17.48 8168629.87 9.72   23.90 13.63
Maximum of Months 0.435629E+09 354.57   33.03 25.15 9951001.45 10.16   33.03 24.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.841448E+10 9173.38 02-JAN-14:30 28.90 24.11 0.944078E+09 1025.15 02-JAN-14:39 28.90 23.86
February 0.807894E+10 11558.76 20-FEB-15:41 26.70 17.88 0.862574E+09 1040.81 22-FEB-14:39 27.60 14.24
March 0.940501E+10 8774.38 01-MAR-14:00 23.30 15.73 0.102858E+10 991.75 21-MAR-11:09 19.27 12.62
April 0.956773E+10 11664.78 16-APR-14:51 31.70 21.16 0.920340E+09 991.41 24-APR-11:39 26.87 20.45
May 0.104636E+11 11091.78 29-MAY-15:21 33.05 24.42 0.999733E+09 991.29 08-MAY-16:19 33.05 24.42
June 0.105770E+11 8155.16 01-JUN-14:10 30.50 23.72 0.100115E+10 991.29 21-JUN-16:19 23.90 22.10
July 0.108876E+11 11765.17 30-JUL-12:41 32.98 25.43 0.933996E+09 992.23 28-JUL-15:20 32.98 25.43
August 0.110819E+11 9009.21 31-AUG-13:10 31.70 24.44 0.104221E+10 1006.93 31-AUG-13:20 31.70 24.32
September 0.107734E+11 9194.53 29-SEP-12:40 30.93 24.21 0.929409E+09 1027.29 29-SEP-12:50 31.02 24.22
October 0.108763E+11 9503.43 06-OCT-12:30 30.30 23.72 0.961659E+09 1061.63 06-OCT-12:39 30.20 23.69
November 0.964039E+10 9392.61 07-NOV-13:40 28.13 20.93 0.945202E+09 1048.86 07-NOV-13:50 28.22 20.86
December 0.853917E+10 9186.83 04-DEC-14:10 25.68 18.04 0.916071E+09 1026.15 04-DEC-14:09 25.68 18.04
                     
Annual Sum or Average 0.118306E+12         0.114850E+11        
Minimum of Months 0.807894E+10 8155.16   23.30 15.73 0.862574E+09 991.29   19.27 12.62
Maximum of Months 0.110819E+11 11765.17   33.05 25.43 0.104221E+10 1061.63   33.05 25.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.314521E+10 2593.87 27-JAN-14:30 22.50 16.00 0.427778E+09 451.42 02-JAN-17:19 22.50 16.00
February 0.301339E+10 2655.00 22-FEB-15:05 27.80 14.40 0.389811E+09 451.42 09-FEB-17:19 27.80 14.40
March 0.360412E+10 2588.41 01-MAR-14:10 23.48 15.79 0.467233E+09 451.42 21-MAR-16:19 22.60 15.59
April 0.364437E+10 2828.92 16-APR-14:52 31.70 21.16 0.414246E+09 451.42 25-APR-16:19 21.13 20.12
May 0.391050E+10 2731.20 07-MAY-11:22 28.60 22.09 0.447666E+09 451.42 24-MAY-16:19 23.90 23.16
June 0.389899E+10 2748.04 04-JUN-12:42 28.77 25.50 0.447866E+09 451.42 12-JUN-16:19 24.80 23.18
July 0.395314E+10 2840.26 16-JUL-13:22 31.10 24.24 0.416341E+09 451.42 05-JUL-16:19 31.10 24.24
August 0.401075E+10 2686.51 31-AUG-14:40 32.03 24.60 0.466439E+09 451.42 11-AUG-16:19 32.03 24.60
September 0.378373E+10 2667.64 08-SEP-15:10 32.20 23.39 0.414129E+09 451.42 05-SEP-16:19 32.20 23.39
October 0.379456E+10 2678.46 06-OCT-13:00 30.00 23.64 0.426064E+09 451.42 13-OCT-16:19 24.07 22.86
November 0.345932E+10 2693.32 20-NOV-20:21 25.60 20.62 0.421858E+09 451.42 06-NOV-17:19 25.60 20.62
December 0.320758E+10 2599.90 14-DEC-14:10 24.63 19.49 0.414451E+09 451.42 13-DEC-17:19 24.63 19.49
                     
Annual Sum or Average 0.434257E+11         0.515388E+10        
Minimum of Months 0.301339E+10 2588.41   22.50 14.40 0.389811E+09 451.42   21.13 14.40
Maximum of Months 0.401075E+10 2840.26   32.20 25.50 0.467233E+09 451.42   32.20 24.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.443178E+09 395.78 16-JAN-12:51 21.70 15.33 14043794.55 14.78 25-JAN-15:00 17.80 8.74
February 0.429674E+09 409.60 26-FEB-17:51 24.40 16.10 12754878.82 14.80 03-FEB-15:20 24.40 16.10
March 0.516139E+09 394.29 12-MAR-16:01 24.40 18.40 15260654.95 14.94 16-MAR-14:39 18.30 8.84
April 0.532147E+09 435.48 16-APR-14:52 31.70 21.16 13565333.77 14.77 19-APR-15:09 23.12 16.08
May 0.571727E+09 420.70 07-MAY-11:22 28.60 22.09 14596394.75 14.53 02-MAY-16:19 28.60 22.09
June 0.570256E+09 429.10 04-JUN-12:42 28.77 25.50 14552892.61 14.53 13-JUN-16:00 23.30 21.31
July 0.585350E+09 445.66 04-JUL-16:02 31.42 25.15 13565531.53 14.50 14-JUL-16:00 22.80 21.21
August 0.584592E+09 430.55 11-AUG-21:21 25.25 23.30 15161251.60 14.55 23-AUG-16:00 23.90 21.61
September 0.552873E+09 414.49 10-SEP-16:02 31.10 24.83 13501202.61 14.47 14-SEP-16:00 27.20 22.18
October 0.547916E+09 404.67 22-OCT-16:42 27.38 22.61 13966538.98 14.61 13-OCT-16:19 27.38 22.61
November 0.494420E+09 431.14 20-NOV-20:21 25.60 20.62 13809741.90 14.68 13-NOV-14:39 25.60 20.62
December 0.459286E+09 391.54 12-DEC-07:02 11.20 8.46 13594626.77 14.75 15-DEC-15:09 19.90 14.72
                     
Annual Sum or Average 0.628756E+10         0.168373E+09        
Minimum of Months 0.429674E+09 391.54   11.20 8.46 12754878.82 14.47   17.80 8.74
Maximum of Months 0.585350E+09 445.66   31.70 25.50 15260654.95 14.94   28.60 22.61



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.450358E+09 445.03 20-JAN-07:02 14.90 11.74 7157387.42 7.43 31-JAN-15:50 17.20 11.74
February 0.439391E+09 449.25 23-FEB-07:02 14.68 12.86 6501359.50 7.42 03-FEB-15:20 14.68 12.86
March 0.531691E+09 448.55 22-MAR-06:02 13.30 12.49 7772119.56 7.51 16-MAR-14:39 13.30 12.49
April 0.551986E+09 473.37 16-APR-14:52 31.70 21.16 6912945.73 7.44 19-APR-14:00 23.30 16.21
May 0.593325E+09 458.46 07-MAY-11:22 28.60 22.09 7455278.07 7.35 11-MAY-13:20 29.40 23.01
June 0.592617E+09 467.13 04-JUN-12:42 28.77 25.50 7442200.54 7.36 09-JUN-14:39 31.10 24.95
July 0.610367E+09 482.88 04-JUL-16:02 31.42 25.15 6938478.76 7.34 28-JUL-07:40 26.13 24.42
August 0.605122E+09 461.22 11-AUG-21:21 25.25 23.30 7756909.81 7.35 23-AUG-16:00 23.90 21.61
September 0.571836E+09 451.77 10-SEP-16:02 31.10 24.83 6911519.20 7.34 05-SEP-07:49 31.10 24.83
October 0.562386E+09 434.85 22-OCT-16:42 27.38 22.61 7147498.99 7.35 13-OCT-15:30 27.38 22.61
November 0.506312E+09 463.13 20-NOV-20:21 25.60 20.62 7055612.22 7.39 13-NOV-13:50 25.60 20.62
December 0.466578E+09 445.27 12-DEC-07:02 11.20 8.46 6927868.21 7.41 27-DEC-14:00 20.60 15.54
                     
Annual Sum or Average 0.648197E+10         85979178.00        
Minimum of Months 0.439391E+09 434.85   11.20 8.46 6501359.50 7.34   13.30 11.74
Maximum of Months 0.610367E+09 482.88   31.70 25.50 7772119.56 7.51   31.10 24.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.212047E+09 214.50 06-JAN-07:03 22.88 20.20 6288372.32 6.59 06-JAN-07:10 22.88 20.20
February 0.211201E+09 385.15 03-FEB-07:01 10.60 7.66 5721580.38 6.64 02-FEB-07:10 10.60 7.66
March 0.261902E+09 386.49 15-MAR-06:01 11.60 8.27 6843521.43 6.67 09-MAR-07:10 11.60 8.27
April 0.277172E+09 294.50 12-APR-06:02 25.10 22.69 6111483.44 6.69 13-APR-06:10 24.50 22.18
May 0.308089E+09 357.85 10-MAY-06:02 25.18 23.10 6599965.22 6.77 23-MAY-06:10 24.08 21.72
June 0.310404E+09 384.61 16-JUN-06:01 26.20 23.01 6589267.10 6.87 08-JUN-06:10 26.20 23.01
July 0.315182E+09 374.35 13-JUL-06:02 25.68 24.05 6153164.35 6.81 14-JUL-06:10 27.30 25.19
August 0.313874E+09 375.53 02-AUG-06:01 27.20 23.52 6864901.32 6.83 01-AUG-06:10 27.20 23.52
September 0.290469E+09 395.08 01-SEP-06:01 26.10 22.39 6121138.22 6.80 22-SEP-06:10 27.80 25.38
October 0.279880E+09 349.88 03-OCT-06:01 26.10 25.23 6321291.47 6.70 04-OCT-06:10 26.20 25.75
November 0.248221E+09 371.87 30-NOV-07:02 25.60 24.11 6225601.96 6.75 30-NOV-07:10 25.60 24.11
December 0.219699E+09 235.61 01-DEC-07:03 23.30 18.59 6101723.76 6.62 01-DEC-07:10 23.30 18.59
                     
Annual Sum or Average 0.324814E+10         75942010.97        
Minimum of Months 0.211201E+09 214.50   10.60 7.66 5721580.38 6.59   10.60 7.66
Maximum of Months 0.315182E+09 395.08   27.20 25.23 6864901.32 6.87   27.80 25.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.273385E+10 2186.10 26-JAN-14:50 21.10 11.99 0.347314E+09 362.98 25-JAN-15:50 21.10 11.99
February 0.262170E+10 2277.54 20-FEB-15:41 26.70 17.88 0.316121E+09 362.97 09-FEB-17:19 26.70 17.88
March 0.313541E+10 2198.47 21-MAR-14:20 22.80 14.82 0.378469E+09 363.03 16-MAR-12:00 22.80 14.82
April 0.317237E+10 2396.58 16-APR-14:52 31.70 21.16 0.335479E+09 362.97 25-APR-16:19 21.13 20.12
May 0.339779E+10 2296.54 07-MAY-11:22 28.60 22.09 0.362469E+09 362.97 24-MAY-16:19 23.90 23.16
June 0.337938E+10 2322.38 04-JUN-12:42 28.77 25.50 0.362603E+09 362.97 12-JUN-16:19 24.80 23.18
July 0.342648E+10 2406.89 04-JUL-16:02 31.42 25.15 0.337233E+09 362.97 05-JUL-16:19 26.83 24.02
August 0.348062E+10 2296.83 31-AUG-14:40 32.03 24.60 0.377961E+09 362.97 11-AUG-16:19 32.03 24.60
September 0.328074E+10 2275.97 08-SEP-15:30 32.20 23.32 0.335895E+09 362.97 12-SEP-16:19 27.20 22.08
October 0.329477E+10 2274.71 06-OCT-13:00 30.00 23.64 0.345964E+09 362.97 13-OCT-14:20 28.67 24.02
November 0.300792E+10 2352.78 20-NOV-20:21 25.60 20.62 0.342346E+09 362.97 06-NOV-17:19 25.60 20.62
December 0.280075E+10 2190.71 14-DEC-14:10 24.63 19.49 0.336463E+09 363.00 27-DEC-14:50 20.50 15.50
                     
Annual Sum or Average 0.377318E+11         0.417832E+10        
Minimum of Months 0.262170E+10 2186.10   21.10 11.99 0.316121E+09 362.97   20.50 11.99
Maximum of Months 0.348062E+10 2406.89   32.20 25.50 0.378469E+09 363.03   32.03 24.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.770088E+10 13954.69 15-JAN-15:22 25.30 16.86 0.170587E+09 186.67 06-JAN-07:10 25.30 16.86
February 0.754193E+10 14845.00 20-FEB-15:41 26.70 17.88 0.155502E+09 189.62 02-FEB-07:10 26.70 17.88
March 0.898155E+10 13997.24 12-MAR-16:01 24.40 18.40 0.185785E+09 192.36 14-MAR-06:10 23.30 22.57
April 0.928883E+10 15130.98 16-APR-14:51 31.70 21.16 0.166595E+09 192.82 12-APR-06:10 31.70 21.16
May 0.102176E+11 14895.19 29-MAY-16:01 33.03 24.50 0.179901E+09 192.82 24-MAY-06:10 33.03 24.50
June 0.102866E+11 13958.26 11-JUN-14:41 31.20 24.47 0.179521E+09 192.82 02-JUN-06:10 31.20 24.47
July 0.105955E+11 14852.63 30-JUL-14:01 33.40 24.78 0.168018E+09 192.82 05-JUL-06:10 33.40 24.78
August 0.107769E+11 14126.04 20-AUG-16:01 30.60 24.86 0.187213E+09 192.82 22-AUG-06:10 26.70 24.27
September 0.102250E+11 14242.91 17-SEP-16:01 31.10 24.89 0.167128E+09 192.82 01-SEP-06:10 31.10 24.89
October 0.101748E+11 14208.14 09-OCT-16:01 29.32 23.78 0.172664E+09 192.82 30-OCT-06:10 26.70 25.38
November 0.900170E+10 14036.84 19-NOV-14:21 26.70 20.96 0.169343E+09 192.82 30-NOV-07:10 25.60 24.11
December 0.791833E+10 14315.25 10-DEC-15:11 28.70 22.62 0.165609E+09 190.42 01-DEC-07:10 28.70 22.62
                     
Annual Sum or Average 0.112710E+12         0.206787E+10        
Minimum of Months 0.754193E+10 13954.69   24.40 16.86 0.155502E+09 186.67   23.30 16.86
Maximum of Months 0.107769E+11 15130.98   33.40 24.89 0.187213E+09 192.82   33.40 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.406994E+10 7513.23 15-JAN-15:22 25.30 16.86 86484345.71 94.24 06-JAN-07:10 25.30 16.86
February 0.400212E+10 7955.35 20-FEB-15:41 26.70 17.88 78929687.61 96.33 17-FEB-07:10 26.70 17.88
March 0.475701E+10 7433.08 12-MAR-16:01 24.40 18.40 94256734.57 97.94 14-MAR-06:10 23.30 22.57
April 0.499574E+10 8076.23 16-APR-14:51 31.70 21.16 84697583.32 97.94 14-APR-06:10 31.70 21.16
May 0.554600E+10 7984.27 29-MAY-16:01 33.03 24.50 91505297.31 97.94 24-MAY-06:10 33.03 24.50
June 0.561699E+10 7425.58 11-JUN-16:01 31.02 24.22 91305636.35 97.94 02-JUN-06:10 31.02 24.22
July 0.584373E+10 7970.76 30-JUL-14:01 33.40 24.78 85477579.03 97.94 05-JUL-06:10 33.40 24.78
August 0.591752E+10 7538.62 20-AUG-16:01 30.60 24.86 95214593.98 97.94 31-AUG-06:10 25.78 23.68
September 0.567000E+10 7635.58 10-SEP-16:02 31.10 24.83 85051009.59 97.94 14-SEP-06:10 24.40 22.82
October 0.562122E+10 7593.43 09-OCT-16:01 29.32 23.78 87897739.17 97.94 06-OCT-06:10 29.32 23.78
November 0.488538E+10 7528.14 19-NOV-13:41 26.70 21.27 86090314.15 97.94 21-NOV-07:10 25.18 21.19
December 0.422987E+10 7643.45 10-DEC-15:11 28.70 22.62 84024710.61 97.76 11-DEC-07:10 22.12 20.55
                     
Annual Sum or Average 0.611555E+11         0.105094E+10        
Minimum of Months 0.400212E+10 7425.58   24.40 16.86 78929687.61 94.24   22.12 16.86
Maximum of Months 0.591752E+10 8076.23   33.40 24.86 95214593.98 97.94   33.40 24.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.448697E+09 432.41 26-JAN-14:40 21.10 11.99 16119822.74 16.47 27-JAN-11:30 22.25 15.57
February 0.438713E+09 750.71 03-FEB-07:01 10.60 7.66 14662345.10 16.85 03-FEB-07:10 10.60 7.66
March 0.540407E+09 702.13 15-MAR-06:01 11.60 8.27 17531798.51 16.82 15-MAR-06:10 11.60 8.27
April 0.561110E+09 515.18 14-APR-12:40 30.40 22.78 15628899.08 16.48 13-APR-06:10 30.40 22.78
May 0.612625E+09 543.46 18-MAY-13:10 31.52 22.88 16873015.54 16.57 23-MAY-06:10 24.08 21.72
June 0.617087E+09 646.74 08-JUN-06:01 28.30 25.49 16851346.30 16.81 08-JUN-06:10 28.30 25.49
July 0.628287E+09 559.90 28-JUL-15:10 35.00 25.20 15726235.38 16.70 13-JUL-06:10 35.00 25.20
August 0.628467E+09 574.03 18-AUG-06:01 27.38 24.43 17559967.13 16.75 18-AUG-06:10 27.38 24.43
September 0.582407E+09 544.06 22-SEP-06:01 27.80 25.38 15651214.94 16.72 22-SEP-06:10 27.80 25.38
October 0.565148E+09 526.17 06-OCT-12:50 30.10 23.67 16162923.90 16.50 04-OCT-06:10 30.10 23.67
November 0.505508E+09 468.70 08-NOV-13:50 28.40 22.20 15933956.65 16.54 30-NOV-07:10 25.60 24.11
December 0.457908E+09 439.33 08-DEC-14:20 27.60 22.76 15628829.81 16.47 18-DEC-14:39 25.00 19.68
                     
Annual Sum or Average 0.658636E+10         0.194330E+09        
Minimum of Months 0.438713E+09 432.41   10.60 7.66 14662345.10 16.47   10.60 7.66
Maximum of Months 0.628467E+09 750.71   35.00 25.49 17559967.13 16.85   35.00 25.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.222708E+10 2726.63 13-JAN-10:30 25.85 21.29 88053768.36 109.43 27-JAN-11:30 22.25 15.57
February 0.231605E+10 2855.09 28-FEB-10:10 24.40 16.25 80610138.52 109.43 28-FEB-08:09 24.40 16.25
March 0.296329E+10 3471.58 27-MAR-10:30 25.85 21.67 96577332.47 111.62 09-MAR-07:10 25.85 21.67
April 0.337147E+10 6148.91 16-APR-12:11 30.97 20.95 86928753.36 111.98 13-APR-06:10 30.97 20.95
May 0.383847E+10 6304.37 07-MAY-10:01 28.40 21.86 94439166.71 118.62 16-MAY-06:10 25.28 21.69
June 0.395456E+10 5984.48 11-JUN-10:01 30.68 23.76 94483837.17 121.98 08-JUN-06:10 30.68 23.76
July 0.410166E+10 6435.88 30-JUL-11:21 33.05 24.63 88472417.45 119.83 14-JUL-06:10 33.05 24.63
August 0.397484E+10 5759.87 20-AUG-11:22 31.95 26.15 98346926.43 121.56 01-AUG-06:10 31.95 26.15
September 0.371797E+10 5853.20 24-SEP-10:01 29.68 24.62 87698924.83 119.12 19-SEP-06:10 29.68 24.62
October 0.348280E+10 5764.53 09-OCT-10:41 31.73 23.86 90389223.77 115.17 04-OCT-06:10 31.73 23.86
November 0.281662E+10 3169.49 07-NOV-10:00 25.60 21.07 88365293.80 114.70 21-NOV-07:10 25.18 21.19
December 0.221005E+10 2835.30 08-DEC-10:30 26.65 22.70 85211888.87 109.43 01-DEC-07:40 26.65 22.70
                     
Annual Sum or Average 0.389749E+11         0.107958E+10        
Minimum of Months 0.221005E+10 2726.63   24.40 16.25 80610138.52 109.43   22.25 15.57
Maximum of Months 0.410166E+10 6435.88   33.05 26.15 98346926.43 121.98   33.05 26.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: NE STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.746685E+09 2658.83 01-JAN-14:51 26.10 21.82 29766532.77 32.03 02-JAN-17:49 24.08 20.17
February 0.844679E+09 1579.82 11-FEB-14:00 29.40 24.15 27702227.02 32.02 23-FEB-16:40 24.80 18.47
March 0.105686E+10 3077.08 05-MAR-14:02 28.22 23.47 33210327.01 32.03 17-MAR-12:09 21.10 14.86
April 0.141375E+10 3234.67 09-APR-13:11 27.93 19.41 30316991.78 32.03 14-APR-13:00 30.60 24.51
May 0.198909E+10 3271.56 29-MAY-16:12 32.77 24.48 33214289.11 33.82 15-MAY-06:10 32.77 24.48
June 0.227156E+10 3326.50 25-JUN-13:51 31.10 25.30 33270447.71 35.70 08-JUN-06:10 31.10 25.30
July 0.245163E+10 3361.68 23-JUL-12:51 32.20 24.61 31184793.91 35.47 10-JUL-06:10 32.20 24.61
August 0.227400E+10 3296.25 06-AUG-14:02 32.12 25.32 34652453.76 35.70 01-AUG-06:10 32.12 25.32
September 0.212537E+10 3526.11 10-SEP-12:31 31.10 24.59 30941505.51 35.69 18-SEP-06:10 27.30 24.35
October 0.175911E+10 3238.05 22-OCT-12:51 28.90 23.36 31825408.22 34.75 30-OCT-06:10 26.70 25.38
November 0.125560E+10 3062.35 05-NOV-14:31 27.60 23.88 30826136.42 34.04 30-NOV-07:10 25.60 24.11
December 0.814718E+09 3112.65 10-DEC-14:31 28.90 22.80 29017629.55 32.10 01-DEC-07:10 28.90 22.80
                     
Annual Sum or Average 0.190030E+11         0.375929E+09        
Minimum of Months 0.746685E+09 1579.82   26.10 19.41 27702227.02 32.02   21.10 14.86
Maximum of Months 0.245163E+10 3526.11   32.77 25.32 34652453.76 35.70   32.77 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: NW ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.679182E+09 1433.63 17-JAN-16:40 21.87 15.52 7515934.12 8.01 02-JAN-17:49 21.87 15.52
February 0.707208E+09 2640.06 20-FEB-17:51 25.00 17.39 6934700.79 8.01 23-FEB-16:40 24.80 18.47
March 0.832955E+09 2557.51 12-MAR-17:02 24.13 18.70 8344805.26 8.12 14-MAR-06:10 23.30 22.57
April 0.997379E+09 2702.22 02-APR-17:12 25.03 17.93 7609892.39 8.17 13-APR-06:10 24.50 22.18
May 0.125524E+10 2692.59 29-MAY-16:52 31.70 24.36 8296069.88 8.38 30-MAY-06:10 23.40 22.58
June 0.134053E+10 2628.46 25-JUN-16:31 29.23 24.32 8287422.10 8.62 08-JUN-06:10 29.23 24.32
July 0.148613E+10 2657.87 09-JUL-16:52 30.00 25.18 7765669.49 8.64 10-JUL-06:10 27.12 24.30
August 0.147013E+10 2684.60 06-AUG-16:01 28.22 23.94 8649828.02 8.78 21-AUG-06:10 27.38 24.48
September 0.139112E+10 2722.51 10-SEP-16:31 31.10 24.47 7729722.17 8.82 18-SEP-06:10 27.30 24.35
October 0.123842E+10 2746.06 15-OCT-16:32 28.50 20.76 7981724.45 8.59 30-OCT-06:10 26.70 25.38
November 0.970731E+09 2592.98 05-NOV-16:31 27.80 24.12 7722014.98 8.37 30-NOV-07:10 25.60 24.11
December 0.758822E+09 2620.93 10-DEC-15:11 28.70 22.62 7377773.86 8.14 11-DEC-07:10 22.12 20.55
                     
Annual Sum or Average 0.131278E+11         94215557.51        
Minimum of Months 0.679182E+09 1433.63   21.87 15.52 6934700.79 8.01   21.87 15.52
Maximum of Months 0.148613E+10 2746.06   31.70 25.18 8649828.02 8.82   29.23 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: NW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.772519E+09 1478.89 02-JAN-15:00 28.90 23.37 33744738.89 36.60 02-JAN-17:49 24.08 20.17
February 0.877865E+09 1579.00 02-FEB-14:00 28.30 22.51 31531183.08 36.60 23-FEB-16:40 24.80 18.47
March 0.110267E+10 3529.24 05-MAR-14:42 27.88 23.38 37881350.92 37.09 14-MAR-06:10 23.30 22.57
April 0.154133E+10 3631.95 09-APR-13:51 27.20 19.18 34791401.64 37.48 13-APR-06:10 24.50 22.18
May 0.223114E+10 3830.50 29-MAY-16:12 32.77 24.48 38064770.33 39.31 30-MAY-06:10 23.40 22.58
June 0.253312E+10 3839.38 25-JUN-13:51 31.10 25.30 38083404.96 40.81 28-JUN-06:10 26.70 24.27
July 0.274882E+10 3851.27 23-JUL-12:51 32.20 24.61 35671370.57 40.81 10-JUL-06:10 32.20 24.61
August 0.252912E+10 3802.60 06-AUG-14:42 31.78 25.16 39678813.27 40.81 02-AUG-06:10 31.78 25.16
September 0.228575E+10 3971.72 10-SEP-12:31 31.10 24.59 35416281.03 40.81 11-SEP-06:10 26.70 24.27
October 0.184423E+10 3660.78 22-OCT-13:31 28.90 23.36 36461698.13 40.53 30-OCT-06:10 26.70 25.38
November 0.132361E+10 3522.02 05-NOV-15:11 27.80 23.92 35242480.00 39.68 30-NOV-07:10 25.60 24.11
December 0.880604E+09 3561.52 10-DEC-15:11 28.70 22.62 33117328.21 37.61 01-DEC-07:10 28.70 22.62
                     
Annual Sum or Average 0.206708E+11         0.429685E+09        
Minimum of Months 0.772519E+09 1478.89   27.20 19.18 31531183.08 36.60   23.30 18.47
Maximum of Months 0.274882E+10 3971.72   32.77 25.30 39678813.27 40.81   32.20 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: SW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.747182E+09 2005.74 08-JAN-15:51 21.10 14.12 17665861.22 18.82 02-JAN-15:20 21.10 14.12
February 0.722258E+09 2002.87 20-FEB-16:31 26.70 17.88 16196742.45 19.38 22-FEB-16:30 26.70 14.62
March 0.798409E+09 1905.87 26-MAR-15:02 27.43 21.70 19354515.00 19.25 14-MAR-06:10 27.43 21.70
April 0.871677E+09 2001.29 02-APR-16:32 25.97 18.13 17549873.81 19.22 13-APR-06:10 24.50 22.18
May 0.104094E+10 1970.38 29-MAY-16:12 32.77 24.48 19032319.79 19.71 30-MAY-06:10 23.40 22.58
June 0.111356E+10 1943.37 25-JUN-14:31 30.37 24.89 19007531.56 20.40 08-JUN-06:10 30.37 24.89
July 0.123131E+10 1949.23 30-JUL-15:32 31.30 25.24 17806813.29 20.32 10-JUL-06:10 31.30 25.24
August 0.125460E+10 1978.12 06-AUG-16:01 28.22 23.94 19852236.49 20.40 21-AUG-06:10 27.38 24.48
September 0.125732E+10 2062.90 10-SEP-12:31 31.10 24.59 17755131.27 20.40 11-SEP-06:10 26.70 24.27
October 0.118565E+10 2083.46 15-OCT-16:32 28.50 20.76 18379389.57 20.40 30-OCT-06:10 26.70 25.38
November 0.962716E+09 1962.54 19-NOV-15:01 26.70 20.63 17923638.12 19.91 30-NOV-07:10 25.60 24.11
December 0.799871E+09 2146.99 03-DEC-15:01 24.40 18.45 17269301.66 19.55 11-DEC-07:10 22.12 20.55
                     
Annual Sum or Average 0.119855E+11         0.217793E+09        
Minimum of Months 0.722258E+09 1905.87   21.10 14.12 16196742.45 18.82   21.10 14.12
Maximum of Months 0.125732E+10 2146.99   32.77 25.24 19852236.49 20.40   31.30 25.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 674920.75 808.35 31-JAN-07:01 12.20
February 505362.73 926.65 04-FEB-06:12 5.40
March 539782.28 894.03 16-MAR-06:01 6.70
April 376771.33 565.84 19-APR-06:01 15.68
May 549739.20 500.37 08-MAY-05:01 23.90
June 860174.35 617.33 06-JUN-05:02 23.98
July 914683.45 694.94 10-JUL-06:01 27.12
August 872227.09 677.60 21-AUG-06:01 27.38
September 525647.91 646.56 18-SEP-06:01 27.30
October 319304.12 487.69 02-OCT-06:01 26.70
November 242634.72 820.40 13-NOV-07:01 12.30
December 545865.85 841.24 27-DEC-07:01 8.98
         
Annual Sum or Average 6927113.79      
Minimum of Months 242634.72 487.69   5.40
Maximum of Months 914683.45 926.65   27.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 16237.49 128.20 23-JAN-07:01 13.58
February 35540.12 127.18 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 51777.60      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 35540.12 128.20   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1096598.91 1242.44 07-JAN-15:01 26.50
February 1660718.66 1510.66 11-FEB-15:01 28.22
March 2315975.58 1546.26 13-MAR-17:01 28.80
April 3642752.81 2120.00 17-APR-17:01 31.02
May 4139359.95 2062.16 22-MAY-17:01 31.52
June 3582681.11 2171.65 10-JUN-14:01 31.20
July 3281303.72 2911.51 29-JUL-14:01 35.00
August 3249966.14 2328.13 19-AUG-14:01 32.12
September 2802330.45 2103.45 09-SEP-14:01 31.02
October 2973126.23 2159.57 14-OCT-14:01 31.52
November 2622356.54 1424.56 04-NOV-14:01 27.52
December 1270135.11 1174.96 09-DEC-15:01 26.60
         
Annual Sum or Average 32637305.22      
Minimum of Months 1096598.91 1174.96   26.50
Maximum of Months 4139359.95 2911.51   35.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 CLEAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 408210.56 701.23 09-JAN-07:01 12.38
February 306139.09 690.27 22-FEB-07:01 11.88
March 307939.56 704.23 20-MAR-06:01 10.50
April 193933.09 456.91 19-APR-06:01 15.68
May 570895.59 454.76 08-MAY-05:01 23.90
June 1085881.90 722.41 08-JUN-06:01 28.30
July 1268721.25 842.54 10-JUL-06:01 27.12
August 1178571.17 845.96 21-AUG-06:01 27.38
September 949665.47 824.94 18-SEP-06:01 27.30
October 532942.68 627.50 30-OCT-06:01 26.70
November 267096.93 689.13 13-NOV-07:01 12.30
December 332658.17 718.21 12-DEC-07:01 11.20
         
Annual Sum or Average 7402655.45      
Minimum of Months 193933.09 454.76   10.50
Maximum of Months 1268721.25 845.96   28.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 950622.66 1105.89 09-JAN-07:01 12.38
February 668984.90 1066.66 22-FEB-07:01 11.88
March 661492.37 1105.18 20-MAR-06:01 10.50
April 595322.76 735.91 19-APR-06:01 15.68
May 1208167.24 861.71 08-MAY-05:01 23.90
June 1869795.13 1045.86 09-JUN-06:01 27.88
July 1962267.24 1170.90 10-JUL-06:01 27.12
August 2030732.24 1166.64 21-AUG-06:01 27.38
September 1711630.17 1148.06 18-SEP-06:01 27.30
October 1297048.40 911.35 30-OCT-06:01 26.70
November 626753.33 1110.44 13-NOV-07:01 12.30
December 791566.91 1090.51 12-DEC-07:01 11.20
         
Annual Sum or Average 14374383.34      
Minimum of Months 595322.76 735.91   10.50
Maximum of Months 2030732.24 1170.90   27.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 14581.74 202.85 25-JAN-07:01 9.50
February 454306.34 270.04 04-FEB-06:12 5.40
March 45443.35 249.77 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 29044.57 231.26 15-DEC-07:01 7.88
         
Annual Sum or Average 543376.00      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 454306.34 270.04   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 967457.13 201.52 26-JAN-06:13 10.60
February 808801.22 200.31 25-FEB-06:13 10.37
March 719240.95 201.55 21-MAR-05:13 11.33
April 352011.17 168.67 26-APR-05:14 20.60
May 210859.95 73.35 30-MAY-17:01 30.92
June 194105.50 78.92 06-JUN-05:03 23.98
July 162173.67 101.49 10-JUL-17:12 28.90
August 217989.57 112.30 12-AUG-14:13 24.23
September 186282.58 100.66 07-SEP-17:12 29.47
October 218436.85 95.51 10-OCT-17:13 27.93
November 379790.72 197.71 13-NOV-06:13 12.20
December 945354.13 201.50 16-DEC-06:13 11.70
         
Annual Sum or Average 5362503.44      
Minimum of Months 162173.67 73.35   10.37
Maximum of Months 967457.13 201.55   30.92



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 IT HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 LOBBY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 15045.70 100.30 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 15045.70      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 15045.70 100.30   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 407040.75 471.72 25-JAN-07:01 9.50
February 339284.92 461.36 03-FEB-07:01 10.60
March 310946.15 496.78 16-MAR-06:01 6.70
April 136422.88 309.10 19-APR-06:01 15.68
May 150150.32 87.59 10-MAY-06:02 25.18
June 335944.66 326.92 08-JUN-06:01 28.30
July 326186.16 326.28 11-JUL-06:01 26.88
August 361429.93 317.92 23-AUG-06:01 26.88
September 169462.34 305.11 22-SEP-06:01 27.80
October 129553.02 250.23 04-OCT-06:01 26.20
November 145780.22 460.86 13-NOV-07:01 12.30
December 331127.36 485.83 15-DEC-07:01 7.88
         
Annual Sum or Average 3143328.71      
Minimum of Months 129553.02 87.59   6.70
Maximum of Months 407040.75 496.78   28.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 MED GAS

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 7193525.03 458.36 25-JAN-06:12 9.40
February 6619594.63 462.69 04-FEB-06:12 5.40
March 6471043.22 461.73 16-MAR-05:12 6.70
April 131348.80 426.51 19-APR-06:01 15.68
May 14034.64 93.56 01-MAY-06:03 20.78
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 1062535.42 447.35 13-NOV-06:12 12.20
December 6104227.36 459.16 15-DEC-06:12 7.80
         
Annual Sum or Average 27596309.10      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 7193525.03 462.69   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 230715.04 236.97 07-JAN-15:01 26.50
February 348307.41 275.36 11-FEB-15:01 28.22
March 436414.43 287.53 04-MAR-15:01 27.80
April 536000.82 354.24 17-APR-17:01 31.02
May 732749.69 386.34 22-MAY-17:01 31.52
June 842494.31 352.56 09-JUN-17:01 30.92
July 898901.13 450.66 28-JUL-17:01 34.13
August 850356.35 399.84 07-AUG-17:01 31.93
September 828475.56 369.84 08-SEP-17:01 31.60
October 723907.77 392.12 14-OCT-05:02 23.98
November 540033.26 256.14 04-NOV-14:01 27.52
December 284876.54 234.14 09-DEC-15:01 26.60
         
Annual Sum or Average 7253232.31      
Minimum of Months 230715.04 234.14   23.98
Maximum of Months 898901.13 450.66   34.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 505753.48 600.69 07-JAN-15:01 26.50
February 730964.20 716.39 11-FEB-15:01 28.22
March 1056152.41 739.28 04-MAR-15:01 27.80
April 1454204.44 930.88 17-APR-17:01 31.02
May 2083331.43 1014.02 22-MAY-17:01 31.52
June 2328721.78 928.19 09-JUN-17:01 30.92
July 2539088.55 1191.44 28-JUL-17:01 34.13
August 2428454.61 1046.34 07-AUG-17:01 31.93
September 2312649.57 974.83 08-SEP-17:01 31.60
October 2024150.73 952.83 14-OCT-05:02 23.98
November 1422938.55 669.54 04-NOV-14:01 27.52
December 643745.48 605.44 09-DEC-15:01 26.60
         
Annual Sum or Average 19530155.22      
Minimum of Months 505753.48 600.69   23.98
Maximum of Months 2539088.55 1191.44   34.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 501186.69 373.02 25-JAN-07:01 9.50
February 489689.34 452.26 04-FEB-06:12 5.40
March 512794.62 408.62 16-MAR-06:01 6.70
April 473138.41 358.46 19-APR-06:01 15.68
May 516595.76 182.67 15-MAY-06:02 25.28
June 600248.51 385.98 08-JUN-06:01 28.30
July 579665.85 380.16 14-JUL-06:01 27.30
August 594124.82 372.62 15-AUG-06:01 27.38
September 466816.95 380.79 22-SEP-06:01 27.80
October 435660.30 340.59 30-OCT-06:01 26.70
November 389286.81 364.02 13-NOV-07:01 12.30
December 474997.62 392.24 15-DEC-07:01 7.88
         
Annual Sum or Average 6034205.67      
Minimum of Months 389286.81 182.67   5.40
Maximum of Months 600248.51 452.26   28.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 568000.50 347.04 25-JAN-07:01 9.50
February 494512.80 340.56 22-FEB-07:01 11.88
March 676072.33 381.12 16-MAR-06:01 6.70
April 881170.02 336.02 19-APR-06:01 15.68
May 1210136.94 368.53 08-MAY-05:01 23.90
June 1285267.28 367.58 06-JUN-05:02 23.98
July 1389624.94 360.84 14-JUL-06:01 27.30
August 1351523.78 380.49 07-AUG-04:01 25.68
September 1364250.32 361.84 22-SEP-06:01 27.80
October 1115389.29 359.50 04-OCT-06:01 26.20
November 782446.76 340.85 13-NOV-07:01 12.30
December 615338.83 365.64 15-DEC-07:01 7.88
         
Annual Sum or Average 11733733.79      
Minimum of Months 494512.80 336.02   6.70
Maximum of Months 1389624.94 381.12   27.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1674229.81 1730.89 23-JAN-17:01 26.32
February 2686221.78 2394.20 04-FEB-06:02 5.50
March 3194113.68 2400.57 13-MAR-16:01 29.32
April 3946882.41 3386.33 15-APR-16:01 31.70
May 5043022.16 3138.69 22-MAY-16:01 32.62
June 4950141.42 3377.83 10-JUN-16:01 31.52
July 4546499.46 4223.67 29-JUL-16:01 35.40
August 4673421.47 3348.28 19-AUG-16:01 31.60
September 4569818.95 3181.71 30-SEP-16:01 31.02
October 4406052.18 3255.77 14-OCT-16:01 31.23
November 3745845.74 2481.42 04-NOV-16:01 27.70
December 1935757.85 1945.76 09-DEC-17:01 25.50
         
Annual Sum or Average 45372006.92      
Minimum of Months 1674229.81 1730.89   5.50
Maximum of Months 5043022.16 4223.67   35.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1851031.44 1889.95 23-JAN-17:01 26.32
February 2942152.49 2491.65 11-FEB-17:01 27.02
March 3563889.77 2577.56 13-MAR-16:01 29.32
April 4269951.23 3587.98 15-APR-16:01 31.70
May 5380002.46 3366.58 22-MAY-16:01 32.62
June 5425513.02 3562.28 10-JUN-16:01 31.52
July 5344110.46 4472.67 29-JUL-16:01 35.40
August 5999869.70 3554.87 19-AUG-16:01 31.60
September 5677052.70 3431.88 30-SEP-16:01 31.02
October 4958500.33 3485.53 14-OCT-16:01 31.23
November 4143008.09 2644.01 04-NOV-16:01 27.70
December 2269615.00 2106.69 09-DEC-17:01 25.50
         
Annual Sum or Average 51824696.68      
Minimum of Months 1851031.44 1889.95   25.50
Maximum of Months 5999869.70 4472.67   35.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1890919.78 1902.24 23-JAN-17:01 26.32
February 2979395.30 2533.54 11-FEB-17:01 27.02
March 3732165.58 2643.19 13-MAR-16:01 29.32
April 4602847.58 3681.56 15-APR-16:01 31.70
May 5738116.61 3467.95 22-MAY-16:01 32.62
June 5917626.77 3652.83 10-JUN-16:01 31.52
July 6424394.33 4603.96 29-JUL-16:01 35.40
August 6701633.67 3669.61 19-AUG-16:01 31.60
September 6029370.51 3527.10 30-SEP-16:01 31.02
October 5331213.93 3570.96 14-OCT-16:01 31.23
November 4339434.87 2705.16 04-NOV-16:01 27.70
December 2312980.28 2149.59 09-DEC-17:01 25.50
         
Annual Sum or Average 56000099.21      
Minimum of Months 1890919.78 1902.24   25.50
Maximum of Months 6701633.67 4603.96   35.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 PACU

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 458556.02 639.96 09-JAN-07:01 12.38
February 340536.45 617.12 22-FEB-07:01 11.88
March 326384.98 642.63 20-MAR-06:01 10.50
April 256353.37 424.07 19-APR-06:01 15.68
May 569822.06 504.93 08-MAY-05:01 23.90
June 1099730.01 640.31 09-JUN-06:01 27.88
July 1188858.73 738.16 10-JUL-06:01 27.12
August 1208981.04 734.42 21-AUG-06:01 27.38
September 918194.29 715.60 18-SEP-06:01 27.30
October 590075.58 550.82 30-OCT-06:01 26.70
November 246987.21 643.01 13-NOV-07:01 12.30
December 363571.06 639.46 27-DEC-07:01 8.98
         
Annual Sum or Average 7568050.79      
Minimum of Months 246987.21 424.07   8.98
Maximum of Months 1208981.04 738.16   27.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1273243.26 1263.46 25-JAN-07:01 9.50
February 993930.53 1235.78 03-FEB-07:01 10.60
March 1032731.78 1385.38 16-MAR-06:01 6.70
April 807316.87 1005.71 19-APR-06:01 15.68
May 1318865.33 729.32 31-MAY-04:01 25.00
June 2133313.28 1268.39 09-JUN-06:01 27.88
July 2110977.56 1265.51 14-JUL-06:01 27.30
August 2088242.73 1273.53 15-AUG-06:01 27.38
September 1489786.46 1254.21 22-SEP-06:01 27.80
October 1107352.03 1092.26 30-OCT-06:01 26.70
November 815292.09 1233.90 13-NOV-07:01 12.30
December 1094697.43 1330.09 15-DEC-07:01 7.88
         
Annual Sum or Average 16265749.34      
Minimum of Months 807316.87 729.32   6.70
Maximum of Months 2133313.28 1385.38   27.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2015339.34 2202.55 31-JAN-07:01 12.20
February 1448619.02 2201.05 03-FEB-07:01 10.60
March 1679304.32 2373.05 16-MAR-06:01 6.70
April 1396694.68 1700.16 19-APR-06:01 15.68
May 2654357.64 1442.43 31-MAY-04:01 25.00
June 4171564.66 2318.62 09-JUN-06:01 27.88
July 4178626.00 2314.13 14-JUL-06:01 27.30
August 4260998.97 2280.85 15-AUG-06:01 27.38
September 3488469.95 2332.87 22-SEP-06:01 27.80
October 2600755.93 2028.31 30-OCT-06:01 26.70
November 1565124.72 2198.56 13-NOV-07:01 12.30
December 1803099.96 2284.66 27-DEC-07:01 8.98
         
Annual Sum or Average 31262955.17      
Minimum of Months 1396694.68 1442.43   6.70
Maximum of Months 4260998.97 2373.05   27.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 564923.89 404.19 25-JAN-07:01 9.50
February 638550.13 485.16 04-FEB-06:12 5.40
March 567965.58 440.90 16-MAR-06:01 6.70
April 461534.32 388.37 19-APR-06:01 15.68
May 553596.24 247.80 08-MAY-05:01 23.90
June 630808.34 401.97 08-JUN-06:01 28.30
July 596095.55 402.55 14-JUL-06:01 27.30
August 612145.57 397.92 23-AUG-06:01 26.88
September 478397.56 390.12 18-SEP-06:01 27.30
October 408472.04 346.14 02-OCT-06:01 26.70
November 396171.02 395.24 13-NOV-07:01 12.30
December 533932.69 423.84 15-DEC-07:01 7.88
         
Annual Sum or Average 6442592.92      
Minimum of Months 396171.02 247.80   5.40
Maximum of Months 638550.13 485.16   28.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2573467.56 1792.33 25-JAN-07:01 9.50
February 1967682.09 2057.63 04-FEB-06:12 5.40
March 2079702.62 1939.44 16-MAR-06:01 6.70
April 1929223.65 1053.35 19-APR-06:01 15.68
May 3582356.66 1418.70 20-MAY-04:03 25.68
June 4120273.38 1233.10 15-JUN-06:01 27.20
July 5026973.21 1388.62 10-JUL-06:01 27.12
August 4107066.30 1486.77 07-AUG-04:01 25.68
September 3428318.63 1378.64 18-SEP-06:01 27.30
October 3064910.86 1478.42 07-OCT-04:03 25.00
November 2063625.31 1762.23 13-NOV-07:01 12.30
December 2176683.43 1817.98 15-DEC-07:01 7.88
         
Annual Sum or Average 36120283.70      
Minimum of Months 1929223.65 1053.35   5.40
Maximum of Months 5026973.21 2057.63   27.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3075960.39 3872.88 31-JAN-07:01 12.20
February 2440612.54 4722.54 04-FEB-06:12 5.40
March 2434488.97 4339.56 16-MAR-06:01 6.70
April 1432855.38 2709.13 19-APR-06:01 15.68
May 2528844.65 2201.92 31-MAY-04:01 25.00
June 4261956.10 3084.81 06-JUN-05:02 23.98
July 4404231.17 3306.01 10-JUL-06:01 27.12
August 4159596.75 3242.53 21-AUG-06:01 27.38
September 2341867.52 3088.43 18-SEP-06:01 27.30
October 1439518.43 2298.87 02-OCT-06:01 26.70
November 1006868.18 3866.80 13-NOV-07:01 12.30
December 2390746.37 4049.20 27-DEC-07:01 8.98
         
Annual Sum or Average 31917546.45      
Minimum of Months 1006868.18 2201.92   5.40
Maximum of Months 4404231.17 4722.54   27.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 SCRUB

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 SOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 660475.51 809.63 09-JAN-07:01 12.38
February 459544.80 784.10 22-FEB-07:01 11.88
March 451610.37 808.99 20-MAR-06:01 10.50
April 414421.74 548.64 19-APR-06:01 15.68
May 870137.07 659.82 08-MAY-05:01 23.90
June 1467272.22 793.53 09-JUN-06:01 27.88
July 1571727.04 895.38 10-JUL-06:01 27.12
August 1609484.39 898.58 21-AUG-06:01 27.38
September 1339312.69 882.73 18-SEP-06:01 27.30
October 1009322.12 696.19 30-OCT-06:01 26.70
November 441017.58 809.67 13-NOV-07:01 12.30
December 545995.82 811.18 12-DEC-07:01 11.20
         
Annual Sum or Average 10840321.36      
Minimum of Months 414421.74 548.64   10.50
Maximum of Months 1609484.39 898.58   27.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 351254.52 409.86 17-JAN-07:01 13.22
February 254227.58 392.51 04-FEB-06:12 5.40
March 217707.59 396.83 20-MAR-06:01 10.50
April 85444.33 231.39 19-APR-06:01 15.68
May 139572.24 135.08 31-MAY-04:01 25.00
June 316173.88 300.55 09-JUN-06:01 27.88
July 344706.41 329.65 10-JUL-06:01 27.12
August 379215.72 333.10 21-AUG-06:01 27.38
September 209720.79 333.79 18-SEP-06:01 27.30
October 164841.66 268.07 30-OCT-06:01 26.70
November 125407.11 402.33 13-NOV-07:01 12.30
December 270582.22 393.69 21-DEC-07:01 11.88
         
Annual Sum or Average 2858854.05      
Minimum of Months 85444.33 135.08   5.40
Maximum of Months 379215.72 409.86   27.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1173604.79 1269.25 09-JAN-07:01 12.38
February 856978.21 1210.11 22-FEB-07:01 11.88
March 903549.47 1276.51 20-MAR-06:01 10.50
April 1034940.07 858.48 19-APR-06:01 15.68
May 1749159.67 1080.12 08-MAY-05:01 23.90
June 2477348.85 1181.85 15-JUN-06:01 27.20
July 2565918.70 1323.48 10-JUL-06:01 27.12
August 2618260.84 1314.95 21-AUG-06:01 27.38
September 2238056.64 1293.42 18-SEP-06:01 27.30
October 1835175.21 1034.23 30-OCT-06:01 26.70
November 941953.54 1269.32 13-NOV-07:01 12.30
December 1020034.94 1241.79 27-DEC-07:01 8.98
         
Annual Sum or Average 19414980.92      
Minimum of Months 856978.21 858.48   8.98
Maximum of Months 2618260.84 1323.48   27.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1774540.59 2265.94 25-JAN-07:01 9.50
February 1394052.74 2780.46 04-FEB-06:12 5.40
March 1390504.40 2495.28 16-MAR-06:01 6.70
April 517172.16 1507.66 19-APR-06:01 15.68
May 691677.47 1043.18 31-MAY-04:01 25.00
June 1571025.58 1644.00 06-JUN-05:02 23.98
July 1686282.06 1666.32 10-JUL-06:01 27.12
August 1484258.23 1604.28 21-AUG-06:01 27.38
September 579140.97 1446.23 18-SEP-06:01 27.30
October 378939.67 920.07 02-OCT-06:01 26.70
November 455931.17 2227.11 13-NOV-07:01 12.30
December 1359749.42 2311.53 27-DEC-07:01 8.98
         
Annual Sum or Average 13283274.46      
Minimum of Months 378939.67 920.07   5.40
Maximum of Months 1774540.59 2780.46   27.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 22151152.50 4259.21 25-JAN-06:12 9.40
February 22042630.53 4339.84 04-FEB-06:12 5.40
March 12527303.88 4195.20 16-MAR-05:12 6.70
April 117179.75 1562.40 19-APR-06:01 15.68
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 1953791.35 4057.35 27-NOV-07:01 10.37
December 15336851.90 4231.23 15-DEC-06:12 7.80
         
Annual Sum or Average 74128909.91      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 22151152.50 4339.84   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 142871.70 905.18 23-JAN-07:01 13.58
February 214689.05 888.45 04-FEB-07:03 5.28
March 127216.77 1010.82 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 26876.39 241.59 27-NOV-07:01 10.37
December 151115.64 631.82 15-DEC-07:01 7.88
         
Annual Sum or Average 662769.54      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 214689.05 1010.82   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2757687.91 1806.01 25-JAN-06:12 9.40
February 4079455.28 2106.51 04-FEB-06:12 5.40
March 1570382.85 1922.79 16-MAR-06:01 6.70
April 56839.84 757.86 19-APR-06:01 15.68
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 308738.15 1735.04 27-NOV-07:01 10.37
December 3089293.75 1858.00 15-DEC-07:01 7.88
         
Annual Sum or Average 11862397.79      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 4079455.28 2106.51   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 367043.12 1542.32 25-JAN-07:01 9.50
February 514084.94 1644.25 04-FEB-07:03 5.28
March 206692.92 1665.81 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 27136.02 292.59 27-NOV-07:01 10.37
December 382688.17 1601.13 15-DEC-07:01 7.88
         
Annual Sum or Average 1497645.18      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 514084.94 1665.81   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116374E+09 444.45 25-JAN-07:02 9.50
February 44996050.53 412.80 03-FEB-08:00 10.60
March 71975948.82 534.11 16-MAR-07:00 6.70
April 9246408.68 297.39 19-APR-06:05 15.68
May 139979.39 180.97 01-MAY-06:03 20.78
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 17786759.49 418.44 27-NOV-07:04 10.37
December 0.112280E+09 495.30 15-DEC-07:02 7.88
         
Annual Sum or Average 0.372800E+09      
Minimum of Months 0.00 0.00   6.70
Maximum of Months 0.116374E+09 534.11   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 123361.41 822.41 21-JAN-07:03 13.98
February 1741647.24 2854.18 04-FEB-06:12 5.40
March 121219.25 993.86 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 180866.80 1205.78 16-DEC-07:03 11.88
         
Annual Sum or Average 2167094.70      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 1741647.24 2854.18   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 19565.80 233.90 25-JAN-07:01 9.50
February 34282.87 228.55 04-FEB-07:03 5.28
March 17299.98 278.28 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 3519.53 35.20 12-JUN-06:02 25.68
July 9856.18 141.42 10-JUL-06:01 27.12
August 7211.02 108.17 21-AUG-06:01 27.38
September 7475.33 76.94 18-SEP-06:01 27.30
October 0.00 0.00 01-OCT-00:03 27.93
November 7539.70 74.01 13-NOV-07:01 12.30
December 20366.82 150.22 27-DEC-07:01 8.98
         
Annual Sum or Average 127117.24      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 34282.87 278.28   27.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 445908.79 2627.14 25-JAN-07:01 9.50
February 2245824.79 3255.69 04-FEB-06:12 5.40
March 404029.74 2849.64 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 175899.05 1879.04 13-NOV-07:01 12.30
December 625545.58 2756.39 15-DEC-07:01 7.88
         
Annual Sum or Average 3897207.96      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 2245824.79 3255.69   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 77749.13 696.80 25-JAN-07:01 9.50
February 371230.11 1786.94 04-FEB-07:03 5.28
March 116359.97 1696.16 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 127128.77 473.73 20-MAY-06:03 25.78
June 360445.45 734.31 10-JUN-06:03 25.68
July 474185.35 762.90 22-JUL-06:03 25.78
August 301805.82 664.71 05-AUG-06:03 26.28
September 347242.80 592.74 23-SEP-06:03 25.60
October 66989.23 446.59 07-OCT-06:03 24.50
November 22020.96 146.81 04-NOV-06:03 25.60
December 148600.95 656.34 16-DEC-07:03 11.88
         
Annual Sum or Average 2413758.55      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 474185.35 1786.94   26.28



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 480387.46 2287.97 25-JAN-07:01 9.50
February 836639.93 2493.15 04-FEB-07:03 5.28
March 582225.48 4088.66 16-MAR-06:01 6.70
April 385451.81 1151.37 15-APR-06:03 22.30
May 899265.09 1700.32 20-MAY-06:03 25.78
June 1484121.64 1956.95 12-JUN-06:02 25.68
July 2184672.63 3735.40 10-JUL-06:01 27.12
August 1352809.37 3523.95 21-AUG-06:01 27.38
September 1544088.77 2684.34 18-SEP-06:01 27.30
October 626009.68 1664.47 07-OCT-06:03 24.50
November 546490.78 1824.57 27-NOV-07:01 10.37
December 757678.00 2541.31 27-DEC-07:01 8.98
         
Annual Sum or Average 11679840.64      
Minimum of Months 385451.81 1151.37   5.28
Maximum of Months 2184672.63 4088.66   27.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 51828.83 500.02 25-JAN-07:01 9.50
February 319977.38 660.17 04-FEB-06:12 5.40
March 80136.54 710.30 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 28196.53 301.06 13-NOV-07:01 12.30
December 108176.24 552.68 27-DEC-07:01 8.98
         
Annual Sum or Average 588315.52      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 319977.38 710.30   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1895024.05 3186.44 25-JAN-07:01 9.50
February 1528211.61 3329.23 04-FEB-06:12 5.40
March 1103381.08 3337.84 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 312719.62 2952.38 27-NOV-07:01 10.37
December 1421823.02 3275.36 15-DEC-07:01 7.88
         
Annual Sum or Average 6261159.38      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 1895024.05 3337.84   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1051993.32 1932.99 25-JAN-07:01 9.50
February 1057740.53 1892.60 04-FEB-06:12 5.40
March 629775.53 2091.85 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 29007.99 193.39 07-OCT-06:03 24.50
November 231836.44 1893.54 27-NOV-07:01 10.37
December 697173.69 2023.94 15-DEC-07:01 7.88
         
Annual Sum or Average 3697527.50      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 1057740.53 2091.85   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 762639.52 3363.27 25-JAN-07:01 9.50
February 853967.85 2613.19 04-FEB-07:03 5.28
March 368025.85 3531.28 16-MAR-06:01 6.70
April 57011.26 380.08 15-APR-06:03 22.30
May 200762.33 733.51 20-MAY-06:03 25.78
June 474752.40 1071.51 10-JUN-06:03 25.68
July 613775.01 1090.40 22-JUL-06:03 25.78
August 566172.99 1099.11 19-AUG-06:03 27.88
September 954096.70 1389.40 02-SEP-06:03 26.70
October 294806.13 1610.40 07-OCT-06:03 24.50
November 366340.94 2653.20 27-NOV-07:01 10.37
December 695485.13 2508.44 15-DEC-07:01 7.88
         
Annual Sum or Average 6207836.11      
Minimum of Months 57011.26 380.08   5.28
Maximum of Months 954096.70 3531.28   27.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 472827.64 2215.67 25-JAN-07:01 9.50
February 556162.17 1731.53 04-FEB-06:12 5.40
March 254348.44 2400.95 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 13671.85 91.15 07-OCT-06:03 24.50
November 130010.16 1669.79 27-NOV-07:01 10.37
December 471137.77 2320.70 15-DEC-07:01 7.88
         
Annual Sum or Average 1898158.04      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 556162.17 2400.95   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 78179.65 1149.72 25-JAN-07:01 9.50
February 271925.35 1266.34 04-FEB-07:03 5.28
March 79337.34 1322.29 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 29573.69 120.62 10-JUN-06:03 25.68
July 55227.06 153.81 22-JUL-06:03 25.78
August 42610.98 144.52 19-AUG-06:03 27.88
September 154660.08 285.25 09-SEP-06:03 27.80
October 54379.65 362.53 07-OCT-06:03 24.50
November 29865.72 268.53 27-NOV-07:01 10.37
December 138787.56 730.88 15-DEC-07:01 7.88
         
Annual Sum or Average 934547.08      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 271925.35 1322.29   27.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 22750.47 151.67 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 22750.47      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 22750.47 151.67   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 67573.42 367.07 25-JAN-07:01 9.50
February 1178364.41 384.94 04-FEB-06:12 5.40
March 85700.73 368.89 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 19454.82 236.65 13-NOV-07:01 12.30
December 148554.93 368.94 15-DEC-07:01 7.88
         
Annual Sum or Average 1499648.30      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 1178364.41 384.94   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 373634.99 3041.93 25-JAN-07:01 9.50
February 1567196.75 3744.63 04-FEB-06:12 5.40
March 236029.80 3317.52 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 84182.03 1340.92 27-NOV-07:01 10.37
December 738100.37 3181.41 15-DEC-07:01 7.88
         
Annual Sum or Average 2999143.94      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 1567196.75 3744.63   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 509592.13 3397.28 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 509592.13      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 509592.13 3397.28   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 51760.86 345.07 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 51760.86      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 51760.86 345.07   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 488828.63 873.18 25-JAN-07:01 9.50
February 801605.38 924.55 04-FEB-06:12 5.40
March 309496.09 886.07 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 103488.49 854.56 27-NOV-07:01 10.37
December 571538.71 886.53 15-DEC-07:01 7.88
         
Annual Sum or Average 2274957.31      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 801605.38 924.55   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 260514.18 489.98 25-JAN-07:01 9.50
February 536204.67 455.85 03-FEB-07:01 10.60
March 139638.82 528.11 16-MAR-06:01 6.70
April 1219.56 16.26 19-APR-06:01 15.68
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 57192.72 480.86 13-NOV-07:01 12.30
December 188414.32 512.38 15-DEC-07:01 7.88
         
Annual Sum or Average 1183184.27      
Minimum of Months 0.00 0.00   6.70
Maximum of Months 536204.67 528.11   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 X-RAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2021310.54 2527.10 06-JAN-18:01 24.40
February 3195279.86 3338.69 10-FEB-18:01 25.32
March 4816681.08 6651.90 13-MAR-17:01 28.80
April 7004490.09 8855.12 17-APR-17:01 31.02
May 11137457.07 9505.90 22-MAY-17:01 31.52
June 11879732.28 8776.42 09-JUN-17:01 30.92
July 12121524.14 11917.21 28-JUL-17:01 34.13
August 13326289.23 9901.40 07-AUG-17:01 31.93
September 11678884.11 9399.81 08-SEP-17:01 31.60
October 9982868.70 8297.40 03-OCT-17:01 30.40
November 7273322.72 5548.40 03-NOV-17:01 27.80
December 2272139.87 3058.30 08-DEC-18:01 25.00
         
Annual Sum or Average 96709979.71      
Minimum of Months 2021310.54 2527.10   24.40
Maximum of Months 13326289.23 11917.21   34.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 395397.40 1479.86 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 395397.40      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 395397.40 1479.86   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4511795.92 387.91 25-JAN-06:12 9.40
February 5269256.04 397.10 04-FEB-06:12 5.40
March 3024510.57 389.83 16-MAR-05:12 6.70
April 30385.29 361.33 19-APR-06:01 15.68
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 1318491.43 382.21 13-NOV-06:12 12.20
December 5135669.85 392.52 15-DEC-06:12 7.80
         
Annual Sum or Average 19290109.10      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 5269256.04 397.10   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 LOCKER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 14183.48 94.56 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 14183.48      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 14183.48 94.56   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 427390.66 2849.27 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 427390.66      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 427390.66 2849.27   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2768878.90 1707.76 25-JAN-07:01 9.50
February 4773562.06 2103.92 04-FEB-06:12 5.40
March 2345066.34 1844.30 16-MAR-06:01 6.70
April 1737728.86 1488.11 19-APR-06:01 15.68
May 693571.98 568.61 06-MAY-06:03 22.57
June 538937.73 499.94 10-JUN-06:03 25.68
July 880614.71 721.82 31-JUL-06:01 26.20
August 980773.34 787.89 09-AUG-06:01 26.28
September 1082383.01 675.10 18-SEP-06:01 27.30
October 1546165.36 799.13 02-OCT-06:01 26.70
November 1782431.90 1678.04 27-NOV-07:01 10.37
December 2570759.43 1785.92 15-DEC-07:01 7.88
         
Annual Sum or Average 21700873.62      
Minimum of Months 538937.73 499.94   5.40
Maximum of Months 4773562.06 2103.92   27.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 229929.98 1070.15 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 229929.98      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 229929.98 1070.15   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 287808.39 1308.03 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 287808.39      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 287808.39 1308.03   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 2595865.77 11504.56 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 31083.10 207.22 16-DEC-07:03 11.88
         
Annual Sum or Average 2626948.87      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 2595865.77 11504.56   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 340375.29 2269.17 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 340375.29      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 340375.29 2269.17   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1000441.82 545.03 25-JAN-07:01 9.50
February 1905441.75 612.71 04-FEB-06:12 5.40
March 693418.09 579.95 16-MAR-06:01 6.70
April 296429.32 431.60 19-APR-06:01 15.68
May 75297.89 155.57 01-MAY-06:03 20.78
June 32677.13 98.19 07-JUN-06:01 26.20
July 41470.58 159.70 15-JUL-06:03 26.20
August 52865.16 130.36 09-AUG-06:01 26.28
September 58862.63 106.11 16-SEP-06:03 23.90
October 149237.70 173.44 14-OCT-06:03 24.40
November 448628.86 535.27 27-NOV-07:01 10.37
December 1171914.34 569.27 15-DEC-07:01 7.88
         
Annual Sum or Average 5926685.28      
Minimum of Months 32677.13 98.19   5.40
Maximum of Months 1905441.75 612.71   26.28



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 10874421.86 10336.37 25-JAN-07:01 9.50
February 15083952.94 13057.48 04-FEB-06:12 5.40
March 7493292.97 11176.45 16-MAR-06:01 6.70
April 3903596.93 8387.35 19-APR-06:01 15.68
May 1858342.29 3610.94 06-MAY-06:03 22.57
June 1661832.33 3233.44 24-JUN-06:03 24.60
July 2207810.30 3395.08 15-JUL-06:03 26.20
August 1594197.80 3412.94 12-AUG-06:03 23.62
September 1673288.76 3562.99 16-SEP-06:03 23.90
October 2282964.88 4012.07 28-OCT-06:03 21.70
November 2963225.92 10136.42 27-NOV-07:01 10.37
December 9049386.58 10814.31 15-DEC-07:01 7.88
         
Annual Sum or Average 60646313.56      
Minimum of Months 1594197.80 3233.44   5.40
Maximum of Months 15083952.94 13057.48   26.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1075421.04 1760.03 07-JAN-07:03 22.80
February 1412591.38 2092.33 04-FEB-07:03 5.28
March 948992.92 1783.21 25-MAR-06:03 21.78
April 1342715.89 1817.80 15-APR-06:03 22.30
May 1069453.98 1807.73 06-MAY-06:03 22.57
June 1057175.66 1751.24 03-JUN-06:03 26.20
July 1349647.47 1770.33 22-JUL-06:03 25.78
August 1047928.27 1749.33 26-AUG-06:03 25.18
September 1285008.30 1737.97 16-SEP-06:03 23.90
October 1172080.51 1804.36 14-OCT-06:03 24.40
November 839107.51 1817.61 25-NOV-07:03 19.50
December 1313395.06 1805.64 02-DEC-07:03 20.78
         
Annual Sum or Average 13913517.99      
Minimum of Months 839107.51 1737.97   5.28
Maximum of Months 1412591.38 2092.33   26.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 247826.90 304.09 17-JAN-07:01 13.22
February 225985.27 375.51 27-FEB-07:01 15.28
March 161428.85 193.10 25-MAR-06:03 21.78
April 286111.50 225.51 15-APR-06:03 22.30
May 240888.32 226.22 01-MAY-06:03 20.78
June 262080.79 280.18 26-JUN-06:01 25.78
July 346375.47 354.87 31-JUL-06:01 26.20
August 338236.84 332.10 21-AUG-06:01 27.38
September 251910.49 343.24 18-SEP-06:01 27.30
October 338336.53 462.86 02-OCT-06:01 26.70
November 253592.41 252.25 27-NOV-07:01 10.37
December 234794.43 318.57 04-DEC-07:02 17.48
         
Annual Sum or Average 3187567.79      
Minimum of Months 161428.85 193.10   10.37
Maximum of Months 346375.47 462.86   27.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1075460.71 682.26 17-JAN-07:01 13.22
February 972208.13 681.82 21-FEB-07:01 15.60
March 1042357.42 673.39 01-MAR-07:01 13.07
April 1194824.84 655.03 19-APR-06:01 15.68
May 1143248.68 484.84 15-MAY-06:02 25.28
June 1161637.88 699.96 26-JUN-06:01 25.78
July 1190615.08 709.53 10-JUL-06:01 27.12
August 1265201.10 712.59 21-AUG-06:01 27.38
September 1142020.20 710.85 18-SEP-06:01 27.30
October 1248562.64 717.17 30-OCT-06:01 26.70
November 1138089.99 681.00 27-NOV-07:01 10.37
December 1044030.67 675.70 12-DEC-07:01 11.20
         
Annual Sum or Average 13618257.35      
Minimum of Months 972208.13 484.84   10.37
Maximum of Months 1265201.10 717.17   27.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 27941.36 174.73 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 27941.36      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 27941.36 174.73   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 491072.28 1036.91 07-JAN-07:03 22.80
February 674472.96 1553.39 04-FEB-07:03 5.28
March 420900.94 1093.17 25-MAR-06:03 21.78
April 822067.03 1295.45 15-APR-06:03 22.30
May 596870.76 1287.21 06-MAY-06:03 22.57
June 597035.13 1115.10 24-JUN-06:03 24.60
July 763852.07 1209.60 15-JUL-06:03 26.20
August 557469.13 1065.32 05-AUG-06:03 26.28
September 607967.31 1093.33 16-SEP-06:03 23.90
October 720076.11 1284.77 14-OCT-06:03 24.40
November 511932.65 1275.79 25-NOV-07:03 19.50
December 656176.04 1169.18 02-DEC-07:03 20.78
         
Annual Sum or Average 7419892.42      
Minimum of Months 420900.94 1036.91   5.28
Maximum of Months 822067.03 1553.39   26.28



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 4445587.58 10346.19 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 428661.26 2857.74 16-DEC-07:03 11.88
         
Annual Sum or Average 4874248.84      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 4445587.58 10346.19   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 216229.13 1082.94 25-JAN-07:01 9.50
February 5443432.37 6046.70 04-FEB-06:12 5.40
March 212291.19 3538.19 16-MAR-06:01 6.70
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 597538.14 3263.61 16-DEC-07:03 11.88
         
Annual Sum or Average 6469490.83      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 5443432.37 6046.70   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 29885.79 199.24 04-FEB-07:03 5.28
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:03 22.57
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:03 22.40
December 0.00 0.00 01-DEC-00:01 24.10
         
Annual Sum or Average 29885.79      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 29885.79 199.24   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2881850.00 3811.45 25-JAN-07:01 9.50
February 5767666.95 4729.90 04-FEB-06:12 5.40
March 1724903.28 4116.38 16-MAR-06:01 6.70
April 1877.92 25.04 19-APR-06:01 15.68
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 511174.47 3733.84 27-NOV-07:01 10.37
December 2551543.92 3985.55 15-DEC-07:01 7.88
         
Annual Sum or Average 13439016.54      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 5767666.95 4729.90   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: NE STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 50357325.74 2680.85 25-JAN-05:51 9.40
February 63599977.67 2764.90 04-FEB-05:21 5.85
March 50578892.24 2706.41 16-MAR-03:21 7.80
April 716559.15 2412.12 19-APR-06:01 15.68
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 10589693.64 2595.83 27-NOV-06:12 10.00
December 56632017.53 2604.38 16-DEC-06:12 11.70
         
Annual Sum or Average 0.232474E+09      
Minimum of Months 0.00 0.00   5.85
Maximum of Months 63599977.67 2764.90   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: NW ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 7513988.35 2087.05 25-JAN-06:12 9.40
February 15160986.84 2145.60 04-FEB-06:12 5.40
March 9929467.30 2122.75 16-MAR-05:12 6.70
April 131644.92 1755.27 19-APR-06:01 15.68
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 1826500.25 2008.94 27-NOV-07:01 10.37
December 10576332.21 2123.27 15-DEC-06:12 7.80
         
Annual Sum or Average 45138919.89      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 15160986.84 2145.60   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: NW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 42722244.62 2989.67 25-JAN-06:12 9.40
February 57496811.09 3156.42 04-FEB-06:01 5.50
March 48076129.10 3102.71 16-MAR-03:21 7.80
April 374194.43 2776.74 19-APR-06:01 15.68
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 9618453.39 2982.93 27-NOV-06:12 10.00
December 46658193.76 2997.31 15-DEC-06:12 7.80
         
Annual Sum or Average 0.204946E+09      
Minimum of Months 0.00 0.00   5.50
Maximum of Months 57496811.09 3156.42   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: SW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3428635.10 1504.76 25-JAN-06:12 9.40
February 9781247.59 1552.12 04-FEB-06:12 5.40
March 6067017.46 1535.79 16-MAR-05:12 6.70
April 77547.96 1033.97 19-APR-06:01 15.68
May 0.00 0.00 01-MAY-00:02 22.05
June 0.00 0.00 01-JUN-00:01 26.68
July 0.00 0.00 01-JUL-00:01 26.83
August 0.00 0.00 01-AUG-00:01 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 847165.86 1448.49 27-NOV-07:01 10.37
December 5656091.88 1528.46 15-DEC-06:12 7.80
         
Annual Sum or Average 25857705.86      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 9781247.59 1552.12   28.60



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.184174E+09 145.80 02-JAN-07:10 0.342612E+09 213.96 02-JAN-06:10
February 0.167466E+09 145.80 01-FEB-07:10 0.310415E+09 213.96 01-FEB-06:10
March 0.198025E+09 145.80 01-MAR-07:10 0.354012E+09 213.96 01-MAR-06:10
April 0.178605E+09 145.80 03-APR-06:10 0.331982E+09 213.96 03-APR-05:10
May 0.191085E+09 145.80 01-MAY-06:10 0.348312E+09 213.96 01-MAY-05:10
June 0.190123E+09 145.80 01-JUN-06:10 0.341379E+09 213.96 01-JUN-05:10
July 0.179567E+09 145.80 03-JUL-06:10 0.338914E+09 213.96 03-JUL-05:10
August 0.197996E+09 145.80 01-AUG-06:10 0.354012E+09 213.96 01-AUG-05:10
September 0.178576E+09 145.80 01-SEP-06:10 0.331982E+09 213.96 01-SEP-05:10
October 0.184204E+09 145.80 02-OCT-06:10 0.342612E+09 213.96 02-OCT-05:10
November 0.180908E+09 145.80 01-NOV-06:10 0.333677E+09 213.96 01-NOV-05:10
December 0.179567E+09 145.80 01-DEC-07:10 0.338914E+09 213.96 01-DEC-06:10
             
Annual Sum or Average 0.221030E+10     0.406882E+10    
Minimum of Months 0.167466E+09 145.80   0.310415E+09 213.96  
Maximum of Months 0.198025E+09 145.80   0.354012E+09 213.96  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 57298696.55 45.36 02-JAN-07:10 8911442.72 5.57 02-JAN-06:10
February 52100445.58 45.36 01-FEB-07:10 8073991.50 5.57 01-FEB-06:10
March 61607892.38 45.36 01-MAR-07:10 9207956.55 5.57 01-MAR-06:10
April 55565946.23 45.36 03-APR-06:10 8634963.61 5.57 03-APR-05:10
May 59448758.47 45.36 01-MAY-06:10 9059699.64 5.57 01-MAY-05:10
June 59149382.76 45.36 01-JUN-06:10 8879387.17 5.57 01-JUN-05:10
July 55865321.94 45.36 03-JUL-06:10 8815276.07 5.57 03-JUL-05:10
August 61598820.39 45.36 01-AUG-06:10 9207956.55 5.57 01-AUG-05:10
September 55556874.24 45.36 01-SEP-06:10 8634963.61 5.57 01-SEP-05:10
October 57307768.54 45.36 02-OCT-06:10 8911442.72 5.57 02-OCT-05:10
November 56282633.53 45.36 01-NOV-06:10 8679039.99 5.57 01-NOV-05:10
December 55865321.94 45.36 01-DEC-07:10 8815276.07 5.57 01-DEC-06:10
             
Annual Sum or Average 0.687648E+09     0.105831E+09    
Minimum of Months 52100445.58 45.36   8073991.50 5.57  
Maximum of Months 61607892.38 45.36   9207956.55 5.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.429740E+09 340.20 02-JAN-07:10 0.665880E+09 415.84 02-JAN-06:10
February 0.390753E+09 340.20 01-FEB-07:10 0.603304E+09 415.84 01-FEB-06:10
March 0.462059E+09 340.20 01-MAR-07:10 0.688036E+09 415.84 01-MAR-06:10
April 0.416745E+09 340.20 03-APR-06:10 0.645221E+09 415.84 03-APR-05:10
May 0.445866E+09 340.20 01-MAY-06:10 0.676958E+09 415.84 01-MAY-05:10
June 0.443620E+09 340.20 01-JUN-06:10 0.663485E+09 415.84 01-JUN-05:10
July 0.418990E+09 340.20 03-JUL-06:10 0.658694E+09 415.84 03-JUL-05:10
August 0.461991E+09 340.20 01-AUG-06:10 0.688036E+09 415.84 01-AUG-05:10
September 0.416677E+09 340.20 01-SEP-06:10 0.645221E+09 415.84 01-SEP-05:10
October 0.429808E+09 340.20 02-OCT-06:10 0.665880E+09 415.84 02-OCT-05:10
November 0.422120E+09 340.20 01-NOV-06:10 0.648514E+09 415.84 01-NOV-05:10
December 0.418990E+09 340.20 01-DEC-07:10 0.658694E+09 415.84 01-DEC-06:10
             
Annual Sum or Average 0.515736E+10     0.790792E+10    
Minimum of Months 0.390753E+09 340.20   0.603304E+09 415.84  
Maximum of Months 0.462059E+09 340.20   0.688036E+09 415.84  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 CLEAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.214870E+09 170.10 02-JAN-07:10 0.399714E+09 249.62 02-JAN-06:10
February 0.195377E+09 170.10 01-FEB-07:10 0.362151E+09 249.62 01-FEB-06:10
March 0.231030E+09 170.10 01-MAR-07:10 0.413013E+09 249.62 01-MAR-06:10
April 0.208372E+09 170.10 03-APR-06:10 0.387312E+09 249.62 03-APR-05:10
May 0.222933E+09 170.10 01-MAY-06:10 0.406364E+09 249.62 01-MAY-05:10
June 0.221810E+09 170.10 01-JUN-06:10 0.398276E+09 249.62 01-JUN-05:10
July 0.209495E+09 170.10 03-JUL-06:10 0.395400E+09 249.62 03-JUL-05:10
August 0.230996E+09 170.10 01-AUG-06:10 0.413013E+09 249.62 01-AUG-05:10
September 0.208338E+09 170.10 01-SEP-06:10 0.387312E+09 249.62 01-SEP-05:10
October 0.214904E+09 170.10 02-OCT-06:10 0.399714E+09 249.62 02-OCT-05:10
November 0.211060E+09 170.10 01-NOV-06:10 0.389289E+09 249.62 01-NOV-05:10
December 0.209495E+09 170.10 01-DEC-07:10 0.395400E+09 249.62 01-DEC-06:10
             
Annual Sum or Average 0.257868E+10     0.474696E+10    
Minimum of Months 0.195377E+09 170.10   0.362151E+09 249.62  
Maximum of Months 0.231030E+09 170.10   0.413013E+09 249.62  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.281378E+09 222.75 02-JAN-07:10 0.523434E+09 326.89 02-JAN-06:10
February 0.255850E+09 222.75 01-FEB-07:10 0.474245E+09 326.89 01-FEB-06:10
March 0.302539E+09 222.75 01-MAR-07:10 0.540851E+09 326.89 01-MAR-06:10
April 0.272868E+09 222.75 03-APR-06:10 0.507195E+09 326.89 03-APR-05:10
May 0.291936E+09 222.75 01-MAY-06:10 0.532143E+09 326.89 01-MAY-05:10
June 0.290466E+09 222.75 01-JUN-06:10 0.521552E+09 326.89 01-JUN-05:10
July 0.274339E+09 222.75 03-JUL-06:10 0.517786E+09 326.89 03-JUL-05:10
August 0.302494E+09 222.75 01-AUG-06:10 0.540851E+09 326.89 01-AUG-05:10
September 0.272824E+09 222.75 01-SEP-06:10 0.507195E+09 326.89 01-SEP-05:10
October 0.281422E+09 222.75 02-OCT-06:10 0.523434E+09 326.89 02-OCT-05:10
November 0.276388E+09 222.75 01-NOV-06:10 0.509784E+09 326.89 01-NOV-05:10
December 0.274339E+09 222.75 01-DEC-07:10 0.517786E+09 326.89 01-DEC-06:10
             
Annual Sum or Average 0.337684E+10     0.621626E+10    
Minimum of Months 0.255850E+09 222.75   0.474245E+09 326.89  
Maximum of Months 0.302539E+09 222.75   0.540851E+09 326.89  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.157571E+09 124.74 02-JAN-07:10 0.219815E+09 137.27 02-JAN-06:10
February 0.143276E+09 124.74 01-FEB-07:10 0.199158E+09 137.27 01-FEB-06:10
March 0.169422E+09 124.74 01-MAR-07:10 0.227129E+09 137.27 01-MAR-06:10
April 0.152806E+09 124.74 03-APR-06:10 0.212995E+09 137.27 03-APR-05:10
May 0.163484E+09 124.74 01-MAY-06:10 0.223472E+09 137.27 01-MAY-05:10
June 0.162661E+09 124.74 01-JUN-06:10 0.219024E+09 137.27 01-JUN-05:10
July 0.153630E+09 124.74 03-JUL-06:10 0.217443E+09 137.27 03-JUL-05:10
August 0.169397E+09 124.74 01-AUG-06:10 0.227129E+09 137.27 01-AUG-05:10
September 0.152781E+09 124.74 01-SEP-06:10 0.212995E+09 137.27 01-SEP-05:10
October 0.157596E+09 124.74 02-OCT-06:10 0.219815E+09 137.27 02-OCT-05:10
November 0.154777E+09 124.74 01-NOV-06:10 0.214082E+09 137.27 01-NOV-05:10
December 0.153630E+09 124.74 01-DEC-07:10 0.217443E+09 137.27 01-DEC-06:10
             
Annual Sum or Average 0.189103E+10     0.261050E+10    
Minimum of Months 0.143276E+09 124.74   0.199158E+09 137.27  
Maximum of Months 0.169422E+09 124.74   0.227129E+09 137.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 56275505.54 44.55 02-JAN-07:10 78505166.56 49.03 02-JAN-06:10
February 51170080.48 44.55 01-FEB-07:10 71127657.65 49.03 01-FEB-06:10
March 60507751.44 44.55 01-MAR-07:10 81117298.90 49.03 01-MAR-06:10
April 54573697.19 44.55 03-APR-06:10 76069529.65 49.03 03-APR-05:10
May 58387173.50 44.55 01-MAY-06:10 79811232.73 49.03 01-MAY-05:10
June 58093143.78 44.55 01-JUN-06:10 78222773.87 49.03 01-JUN-05:10
July 54867726.90 44.55 03-JUL-06:10 77657988.50 49.03 03-JUL-05:10
August 60498841.45 44.55 01-AUG-06:10 81117298.90 49.03 01-AUG-05:10
September 54564787.20 44.55 01-SEP-06:10 76069529.65 49.03 01-SEP-05:10
October 56284415.53 44.55 02-OCT-06:10 78505166.56 49.03 02-OCT-05:10
November 55277586.51 44.55 01-NOV-06:10 76457819.59 49.03 01-NOV-05:10
December 54867726.90 44.55 01-DEC-07:10 77657988.50 49.03 01-DEC-06:10
             
Annual Sum or Average 0.675368E+09     0.932319E+09    
Minimum of Months 51170080.48 44.55   71127657.65 49.03  
Maximum of Months 60507751.44 44.55   81117298.90 49.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.167121E+09 132.30 02-JAN-07:10 0.777149E+09 485.33 02-JAN-06:10
February 0.151960E+09 132.30 01-FEB-07:10 0.704116E+09 485.33 01-FEB-06:10
March 0.179690E+09 132.30 01-MAR-07:10 0.803007E+09 485.33 01-MAR-06:10
April 0.162067E+09 132.30 03-APR-06:10 0.753038E+09 485.33 03-APR-05:10
May 0.173392E+09 132.30 01-MAY-06:10 0.790078E+09 485.33 01-MAY-05:10
June 0.172519E+09 132.30 01-JUN-06:10 0.774353E+09 485.33 01-JUN-05:10
July 0.162941E+09 132.30 03-JUL-06:10 0.768762E+09 485.33 03-JUL-05:10
August 0.179663E+09 132.30 01-AUG-06:10 0.803007E+09 485.33 01-AUG-05:10
September 0.162041E+09 132.30 01-SEP-06:10 0.753038E+09 485.33 01-SEP-05:10
October 0.167148E+09 132.30 02-OCT-06:10 0.777149E+09 485.33 02-OCT-05:10
November 0.164158E+09 132.30 01-NOV-06:10 0.756881E+09 485.33 01-NOV-05:10
December 0.162941E+09 132.30 01-DEC-07:10 0.768762E+09 485.33 01-DEC-06:10
             
Annual Sum or Average 0.200564E+10     0.922934E+10    
Minimum of Months 0.151960E+09 132.30   0.704116E+09 485.33  
Maximum of Months 0.179690E+09 132.30   0.803007E+09 485.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.155184E+09 122.85 02-JAN-07:10 0.127493E+11 6961.96 02-JAN-07:10
February 0.141105E+09 122.85 01-FEB-07:10 0.115637E+11 6961.96 01-FEB-07:10
March 0.166855E+09 122.85 01-MAR-07:10 0.129794E+11 6961.96 01-MAR-07:10
April 0.150491E+09 122.85 03-APR-06:10 0.124308E+11 6961.96 01-APR-06:10
May 0.161007E+09 122.85 01-MAY-06:10 0.128643E+11 6961.96 01-MAY-06:10
June 0.160196E+09 122.85 01-JUN-06:10 0.125459E+11 6961.96 01-JUN-06:10
July 0.151302E+09 122.85 03-JUL-06:10 0.127493E+11 6961.96 01-JUL-06:10
August 0.166830E+09 122.85 01-AUG-06:10 0.129794E+11 6961.96 01-AUG-06:10
September 0.150467E+09 122.85 01-SEP-06:10 0.124308E+11 6961.96 01-SEP-06:10
October 0.155209E+09 122.85 02-OCT-06:10 0.127493E+11 6961.96 02-OCT-06:10
November 0.152432E+09 122.85 01-NOV-06:10 0.123157E+11 6961.96 01-NOV-06:10
December 0.151302E+09 122.85 01-DEC-07:10 0.127493E+11 6961.96 01-DEC-07:10
             
Annual Sum or Average 0.186238E+10     0.151107E+12    
Minimum of Months 0.141105E+09 122.85   0.115637E+11 6961.96  
Maximum of Months 0.166855E+09 122.85   0.129794E+11 6961.96  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 67530606.65 53.46 02-JAN-07:10 94206295.03 58.83 02-JAN-06:10
February 61404096.58 53.46 01-FEB-07:10 85353275.40 58.83 01-FEB-06:10
March 72609301.73 53.46 01-MAR-07:10 97340857.01 58.83 01-MAR-06:10
April 65488436.62 53.46 03-APR-06:10 91283527.79 58.83 03-APR-05:10
May 70064608.20 53.46 01-MAY-06:10 95773576.02 58.83 01-MAY-05:10
June 69711772.54 53.46 01-JUN-06:10 93867423.47 58.83 01-JUN-05:10
July 65841272.28 53.46 03-JUL-06:10 93189680.34 58.83 03-JUL-05:10
August 72598609.74 53.46 01-AUG-06:10 97340857.01 58.83 01-AUG-05:10
September 65477744.63 53.46 01-SEP-06:10 91283527.79 58.83 01-SEP-05:10
October 67541298.64 53.46 02-OCT-06:10 94206295.03 58.83 02-OCT-05:10
November 66333103.81 53.46 01-NOV-06:10 91749476.19 58.83 01-NOV-05:10
December 65841272.28 53.46 01-DEC-07:10 93189680.34 58.83 01-DEC-06:10
             
Annual Sum or Average 0.810442E+09     0.111878E+10    
Minimum of Months 61404096.58 53.46   85353275.40 58.83  
Maximum of Months 72609301.73 53.46   97340857.01 58.83  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 IT HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.152364E+09 120.62 02-JAN-07:10 88907770.82 55.52 02-JAN-06:10
February 0.138541E+09 120.62 01-FEB-07:10 80552679.05 55.52 01-FEB-06:10
March 0.163822E+09 120.62 01-MAR-07:10 91866032.98 55.52 01-MAR-06:10
April 0.147756E+09 120.62 03-APR-06:10 86149391.24 55.52 03-APR-05:10
May 0.158081E+09 120.62 01-MAY-06:10 90386901.90 55.52 01-MAY-05:10
June 0.157285E+09 120.62 01-JUN-06:10 88587958.69 55.52 01-JUN-05:10
July 0.148552E+09 120.62 03-JUL-06:10 87948334.44 55.52 03-JUL-05:10
August 0.163798E+09 120.62 01-AUG-06:10 91866032.98 55.52 01-AUG-05:10
September 0.147732E+09 120.62 01-SEP-06:10 86149391.24 55.52 01-SEP-05:10
October 0.152388E+09 120.62 02-OCT-06:10 88907770.82 55.52 02-OCT-05:10
November 0.149662E+09 120.62 01-NOV-06:10 86589132.91 55.52 01-NOV-05:10
December 0.148552E+09 120.62 01-DEC-07:10 87948334.44 55.52 01-DEC-06:10
             
Annual Sum or Average 0.182853E+10     0.105586E+10    
Minimum of Months 0.138541E+09 120.62   80552679.05 55.52  
Maximum of Months 0.163822E+09 120.62   91866032.98 55.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.140063E+09 110.88 02-JAN-07:10 0.195391E+09 122.02 02-JAN-06:10
February 0.127357E+09 110.88 01-FEB-07:10 0.177029E+09 122.02 01-FEB-06:10
March 0.150597E+09 110.88 01-MAR-07:10 0.201892E+09 122.02 01-MAR-06:10
April 0.135828E+09 110.88 03-APR-06:10 0.189329E+09 122.02 03-APR-05:10
May 0.145319E+09 110.88 01-MAY-06:10 0.198642E+09 122.02 01-MAY-05:10
June 0.144587E+09 110.88 01-JUN-06:10 0.194688E+09 122.02 01-JUN-05:10
July 0.136560E+09 110.88 03-JUL-06:10 0.193282E+09 122.02 03-JUL-05:10
August 0.150575E+09 110.88 01-AUG-06:10 0.201892E+09 122.02 01-AUG-05:10
September 0.135806E+09 110.88 01-SEP-06:10 0.189329E+09 122.02 01-SEP-05:10
October 0.140086E+09 110.88 02-OCT-06:10 0.195391E+09 122.02 02-OCT-05:10
November 0.137580E+09 110.88 01-NOV-06:10 0.190295E+09 122.02 01-NOV-05:10
December 0.136560E+09 110.88 01-DEC-07:10 0.193282E+09 122.02 01-DEC-06:10
             
Annual Sum or Average 0.168092E+10     0.232044E+10    
Minimum of Months 0.127357E+09 110.88   0.177029E+09 122.02  
Maximum of Months 0.150597E+09 110.88   0.201892E+09 122.02  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 LOBBY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.919280E+09 727.74 02-JAN-07:10 0.108512E+10 677.66 02-JAN-06:10
February 0.835881E+09 727.74 01-FEB-07:10 0.983143E+09 677.66 01-FEB-06:10
March 0.988416E+09 727.74 01-MAR-07:10 0.112122E+10 677.66 01-MAR-06:10
April 0.891481E+09 727.74 03-APR-06:10 0.105145E+10 677.66 03-APR-05:10
May 0.953775E+09 727.74 01-MAY-06:10 0.110317E+10 677.66 01-MAY-05:10
June 0.948972E+09 727.74 01-JUN-06:10 0.108121E+10 677.66 01-JUN-05:10
July 0.896284E+09 727.74 03-JUL-06:10 0.107341E+10 677.66 03-JUL-05:10
August 0.988270E+09 727.74 01-AUG-06:10 0.112122E+10 677.66 01-AUG-05:10
September 0.891335E+09 727.74 01-SEP-06:10 0.105145E+10 677.66 01-SEP-05:10
October 0.919426E+09 727.74 02-OCT-06:10 0.108512E+10 677.66 02-OCT-05:10
November 0.902979E+09 727.74 01-NOV-06:10 0.105682E+10 677.66 01-NOV-05:10
December 0.896284E+09 727.74 01-DEC-07:10 0.107341E+10 677.66 01-DEC-06:10
             
Annual Sum or Average 0.110324E+11     0.128867E+11    
Minimum of Months 0.835881E+09 727.74   0.983143E+09 677.66  
Maximum of Months 0.988416E+09 727.74   0.112122E+10 677.66  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.261195E+09 206.77 02-JAN-07:10 0.152413E+09 95.18 02-JAN-06:10
February 0.237499E+09 206.77 01-FEB-07:10 0.138090E+09 95.18 01-FEB-06:10
March 0.280838E+09 206.77 01-MAR-07:10 0.157485E+09 95.18 01-MAR-06:10
April 0.253296E+09 206.77 03-APR-06:10 0.147685E+09 95.18 03-APR-05:10
May 0.270996E+09 206.77 01-MAY-06:10 0.154949E+09 95.18 01-MAY-05:10
June 0.269631E+09 206.77 01-JUN-06:10 0.151865E+09 95.18 01-JUN-05:10
July 0.254661E+09 206.77 03-JUL-06:10 0.150769E+09 95.18 03-JUL-05:10
August 0.280797E+09 206.77 01-AUG-06:10 0.157485E+09 95.18 01-AUG-05:10
September 0.253255E+09 206.77 01-SEP-06:10 0.147685E+09 95.18 01-SEP-05:10
October 0.261236E+09 206.77 02-OCT-06:10 0.152413E+09 95.18 02-OCT-05:10
November 0.256563E+09 206.77 01-NOV-06:10 0.148438E+09 95.18 01-NOV-05:10
December 0.254661E+09 206.77 01-DEC-07:10 0.150769E+09 95.18 01-DEC-06:10
             
Annual Sum or Average 0.313463E+10     0.181004E+10    
Minimum of Months 0.237499E+09 206.77   0.138090E+09 95.18  
Maximum of Months 0.280838E+09 206.77   0.157485E+09 95.18  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 55252314.53 43.74 02-JAN-07:10 34293067.55 21.42 02-JAN-06:10
February 50239715.38 43.74 01-FEB-07:10 31070382.70 21.42 01-FEB-06:10
March 59407610.51 43.74 01-MAR-07:10 35434113.87 21.42 01-MAR-06:10
April 53581448.15 43.74 03-APR-06:10 33229118.96 21.42 03-APR-05:10
May 57325588.52 43.74 01-MAY-06:10 34863590.71 21.42 01-MAY-05:10
June 57036904.80 43.74 01-JUN-06:10 34169711.20 21.42 01-JUN-05:10
July 53870131.87 43.74 03-JUL-06:10 33922998.48 21.42 03-JUL-05:10
August 59398862.52 43.74 01-AUG-06:10 35434113.87 21.42 01-AUG-05:10
September 53572700.16 43.74 01-SEP-06:10 33229118.96 21.42 01-SEP-05:10
October 55261062.52 43.74 02-OCT-06:10 34293067.55 21.42 02-OCT-05:10
November 54272539.48 43.74 01-NOV-06:10 33398733.96 21.42 01-NOV-05:10
December 53870131.87 43.74 01-DEC-07:10 33922998.48 21.42 01-DEC-06:10
             
Annual Sum or Average 0.663089E+09     0.407261E+09    
Minimum of Months 50239715.38 43.74   31070382.70 21.42  
Maximum of Months 59407610.51 43.74   35434113.87 21.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.600272E+09 475.20 02-JAN-07:10 0.314012E+10 1961.01 02-JAN-06:10
February 0.545814E+09 475.20 01-FEB-07:10 0.284503E+10 1961.01 01-FEB-06:10
March 0.645416E+09 475.20 01-MAR-07:10 0.324460E+10 1961.01 01-MAR-06:10
April 0.582119E+09 475.20 03-APR-06:10 0.304270E+10 1961.01 03-APR-05:10
May 0.622797E+09 475.20 01-MAY-06:10 0.319236E+10 1961.01 01-MAY-05:10
June 0.619660E+09 475.20 01-JUN-06:10 0.312883E+10 1961.01 01-JUN-05:10
July 0.585256E+09 475.20 03-JUL-06:10 0.310623E+10 1961.01 03-JUL-05:10
August 0.645321E+09 475.20 01-AUG-06:10 0.324460E+10 1961.01 01-AUG-05:10
September 0.582024E+09 475.20 01-SEP-06:10 0.304270E+10 1961.01 01-SEP-05:10
October 0.600367E+09 475.20 02-OCT-06:10 0.314012E+10 1961.01 02-OCT-05:10
November 0.589628E+09 475.20 01-NOV-06:10 0.305823E+10 1961.01 01-NOV-05:10
December 0.585256E+09 475.20 01-DEC-07:10 0.310623E+10 1961.01 01-DEC-06:10
             
Annual Sum or Average 0.720393E+10     0.372918E+11    
Minimum of Months 0.545814E+09 475.20   0.284503E+10 1961.01  
Maximum of Months 0.645416E+09 475.20   0.324460E+10 1961.01  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.539803E+09 427.33 02-JAN-07:10 0.314987E+09 196.71 02-JAN-06:10
February 0.490831E+09 427.33 01-FEB-07:10 0.285387E+09 196.71 01-FEB-06:10
March 0.580400E+09 427.33 01-MAR-07:10 0.325468E+09 196.71 01-MAR-06:10
April 0.523479E+09 427.33 03-APR-06:10 0.305215E+09 196.71 03-APR-05:10
May 0.560059E+09 427.33 01-MAY-06:10 0.320228E+09 196.71 01-MAY-05:10
June 0.557238E+09 427.33 01-JUN-06:10 0.313854E+09 196.71 01-JUN-05:10
July 0.526300E+09 427.33 03-JUL-06:10 0.311588E+09 196.71 03-JUL-05:10
August 0.580314E+09 427.33 01-AUG-06:10 0.325468E+09 196.71 01-AUG-05:10
September 0.523394E+09 427.33 01-SEP-06:10 0.305215E+09 196.71 01-SEP-05:10
October 0.539889E+09 427.33 02-OCT-06:10 0.314987E+09 196.71 02-OCT-05:10
November 0.530231E+09 427.33 01-NOV-06:10 0.306773E+09 196.71 01-NOV-05:10
December 0.526300E+09 427.33 01-DEC-07:10 0.311588E+09 196.71 01-DEC-06:10
             
Annual Sum or Average 0.647824E+10     0.374076E+10    
Minimum of Months 0.490831E+09 427.33   0.285387E+09 196.71  
Maximum of Months 0.580400E+09 427.33   0.325468E+09 196.71  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.327421E+09 259.20 02-JAN-07:10 0.171279E+10 1069.64 02-JAN-06:10
February 0.297717E+09 259.20 01-FEB-07:10 0.155183E+10 1069.64 01-FEB-06:10
March 0.352045E+09 259.20 01-MAR-07:10 0.176978E+10 1069.64 01-MAR-06:10
April 0.317520E+09 259.20 03-APR-06:10 0.165965E+10 1069.64 03-APR-05:10
May 0.339707E+09 259.20 01-MAY-06:10 0.174129E+10 1069.64 01-MAY-05:10
June 0.337996E+09 259.20 01-JUN-06:10 0.170663E+10 1069.64 01-JUN-05:10
July 0.319230E+09 259.20 03-JUL-06:10 0.169431E+10 1069.64 03-JUL-05:10
August 0.351993E+09 259.20 01-AUG-06:10 0.176978E+10 1069.64 01-AUG-05:10
September 0.317468E+09 259.20 01-SEP-06:10 0.165965E+10 1069.64 01-SEP-05:10
October 0.327473E+09 259.20 02-OCT-06:10 0.171279E+10 1069.64 02-OCT-05:10
November 0.321615E+09 259.20 01-NOV-06:10 0.166812E+10 1069.64 01-NOV-05:10
December 0.319230E+09 259.20 01-DEC-07:10 0.169431E+10 1069.64 01-DEC-06:10
             
Annual Sum or Average 0.392942E+10     0.203410E+11    
Minimum of Months 0.297717E+09 259.20   0.155183E+10 1069.64  
Maximum of Months 0.352045E+09 259.20   0.176978E+10 1069.64  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 MED GAS

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 57298696.55 45.36 02-JAN-07:10 8911442.72 5.57 02-JAN-06:10
February 52100445.58 45.36 01-FEB-07:10 8073991.50 5.57 01-FEB-06:10
March 61607892.38 45.36 01-MAR-07:10 9207956.55 5.57 01-MAR-06:10
April 55565946.23 45.36 03-APR-06:10 8634963.61 5.57 03-APR-05:10
May 59448758.47 45.36 01-MAY-06:10 9059699.64 5.57 01-MAY-05:10
June 59149382.76 45.36 01-JUN-06:10 8879387.17 5.57 01-JUN-05:10
July 55865321.94 45.36 03-JUL-06:10 8815276.07 5.57 03-JUL-05:10
August 61598820.39 45.36 01-AUG-06:10 9207956.55 5.57 01-AUG-05:10
September 55556874.24 45.36 01-SEP-06:10 8634963.61 5.57 01-SEP-05:10
October 57307768.54 45.36 02-OCT-06:10 8911442.72 5.57 02-OCT-05:10
November 56282633.53 45.36 01-NOV-06:10 8679039.99 5.57 01-NOV-05:10
December 55865321.94 45.36 01-DEC-07:10 8815276.07 5.57 01-DEC-06:10
             
Annual Sum or Average 0.687648E+09     0.105831E+09    
Minimum of Months 52100445.58 45.36   8073991.50 5.57  
Maximum of Months 61607892.38 45.36   9207956.55 5.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.286493E+09 226.80 02-JAN-07:10 0.266451E+10 1663.99 02-JAN-06:10
February 0.260502E+09 226.80 01-FEB-07:10 0.241411E+10 1663.99 01-FEB-06:10
March 0.308039E+09 226.80 01-MAR-07:10 0.275317E+10 1663.99 01-MAR-06:10
April 0.277830E+09 226.80 03-APR-06:10 0.258184E+10 1663.99 03-APR-05:10
May 0.297244E+09 226.80 01-MAY-06:10 0.270884E+10 1663.99 01-MAY-05:10
June 0.295747E+09 226.80 01-JUN-06:10 0.265493E+10 1663.99 01-JUN-05:10
July 0.279327E+09 226.80 03-JUL-06:10 0.263576E+10 1663.99 03-JUL-05:10
August 0.307994E+09 226.80 01-AUG-06:10 0.275317E+10 1663.99 01-AUG-05:10
September 0.277784E+09 226.80 01-SEP-06:10 0.258184E+10 1663.99 01-SEP-05:10
October 0.286539E+09 226.80 02-OCT-06:10 0.266451E+10 1663.99 02-OCT-05:10
November 0.281413E+09 226.80 01-NOV-06:10 0.259502E+10 1663.99 01-NOV-05:10
December 0.279327E+09 226.80 01-DEC-07:10 0.263576E+10 1663.99 01-DEC-06:10
             
Annual Sum or Average 0.343824E+10     0.316435E+11    
Minimum of Months 0.260502E+09 226.80   0.241411E+10 1663.99  
Maximum of Months 0.308039E+09 226.80   0.275317E+10 1663.99  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.159982E+09 126.65 02-JAN-07:10 93353183.15 58.30 02-JAN-06:10
February 0.145468E+09 126.65 01-FEB-07:10 84580334.55 58.30 01-FEB-06:10
March 0.172014E+09 126.65 01-MAR-07:10 96459359.21 58.30 01-MAR-06:10
April 0.155144E+09 126.65 03-APR-06:10 90456883.85 58.30 03-APR-05:10
May 0.165985E+09 126.65 01-MAY-06:10 94906271.18 58.30 01-MAY-05:10
June 0.165149E+09 126.65 01-JUN-06:10 93017380.33 58.30 01-JUN-05:10
July 0.155980E+09 126.65 03-JUL-06:10 92345774.70 58.30 03-JUL-05:10
August 0.171988E+09 126.65 01-AUG-06:10 96459359.21 58.30 01-AUG-05:10
September 0.155119E+09 126.65 01-SEP-06:10 90456883.85 58.30 01-SEP-05:10
October 0.160007E+09 126.65 02-OCT-06:10 93353183.15 58.30 02-OCT-05:10
November 0.157145E+09 126.65 01-NOV-06:10 90918612.73 58.30 01-NOV-05:10
December 0.155980E+09 126.65 01-DEC-07:10 92345774.70 58.30 01-DEC-06:10
             
Annual Sum or Average 0.191996E+10     0.110865E+10    
Minimum of Months 0.145468E+09 126.65   84580334.55 58.30  
Maximum of Months 0.172014E+09 126.65   96459359.21 58.30  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.750340E+09 594.00 02-JAN-07:10 0.697848E+10 4358.06 02-JAN-06:10
February 0.682268E+09 594.00 01-FEB-07:10 0.632268E+10 4358.06 01-FEB-06:10
March 0.806770E+09 594.00 01-MAR-07:10 0.721068E+10 4358.06 01-MAR-06:10
April 0.727649E+09 594.00 03-APR-06:10 0.676197E+10 4358.06 03-APR-05:10
May 0.778496E+09 594.00 01-MAY-06:10 0.709458E+10 4358.06 01-MAY-05:10
June 0.774575E+09 594.00 01-JUN-06:10 0.695338E+10 4358.06 01-JUN-05:10
July 0.731570E+09 594.00 03-JUL-06:10 0.690317E+10 4358.06 03-JUL-05:10
August 0.806651E+09 594.00 01-AUG-06:10 0.721068E+10 4358.06 01-AUG-05:10
September 0.727530E+09 594.00 01-SEP-06:10 0.676197E+10 4358.06 01-SEP-05:10
October 0.750459E+09 594.00 02-OCT-06:10 0.697848E+10 4358.06 02-OCT-05:10
November 0.737034E+09 594.00 01-NOV-06:10 0.679649E+10 4358.06 01-NOV-05:10
December 0.731570E+09 594.00 01-DEC-07:10 0.690317E+10 4358.06 01-DEC-06:10
             
Annual Sum or Average 0.900491E+10     0.828757E+11    
Minimum of Months 0.682268E+09 594.00   0.632268E+10 4358.06  
Maximum of Months 0.806770E+09 594.00   0.721068E+10 4358.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 55252314.53 43.74 02-JAN-07:10 34293067.55 21.42 02-JAN-06:10
February 50239715.38 43.74 01-FEB-07:10 31070382.70 21.42 01-FEB-06:10
March 59407610.51 43.74 01-MAR-07:10 35434113.87 21.42 01-MAR-06:10
April 53581448.15 43.74 03-APR-06:10 33229118.96 21.42 03-APR-05:10
May 57325588.52 43.74 01-MAY-06:10 34863590.71 21.42 01-MAY-05:10
June 57036904.80 43.74 01-JUN-06:10 34169711.20 21.42 01-JUN-05:10
July 53870131.87 43.74 03-JUL-06:10 33922998.48 21.42 03-JUL-05:10
August 59398862.52 43.74 01-AUG-06:10 35434113.87 21.42 01-AUG-05:10
September 53572700.16 43.74 01-SEP-06:10 33229118.96 21.42 01-SEP-05:10
October 55261062.52 43.74 02-OCT-06:10 34293067.55 21.42 02-OCT-05:10
November 54272539.48 43.74 01-NOV-06:10 33398733.96 21.42 01-NOV-05:10
December 53870131.87 43.74 01-DEC-07:10 33922998.48 21.42 01-DEC-06:10
             
Annual Sum or Average 0.663089E+09     0.407261E+09    
Minimum of Months 50239715.38 43.74   31070382.70 21.42  
Maximum of Months 59407610.51 43.74   35434113.87 21.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.206912E+09 163.80 02-JAN-07:10 0.577364E+09 360.56 02-JAN-06:10
February 0.188140E+09 163.80 01-FEB-07:10 0.523106E+09 360.56 01-FEB-06:10
March 0.222473E+09 163.80 01-MAR-07:10 0.596575E+09 360.56 01-MAR-06:10
April 0.200655E+09 163.80 03-APR-06:10 0.559451E+09 360.56 03-APR-05:10
May 0.214676E+09 163.80 01-MAY-06:10 0.586969E+09 360.56 01-MAY-05:10
June 0.213595E+09 163.80 01-JUN-06:10 0.575287E+09 360.56 01-JUN-05:10
July 0.201736E+09 163.80 03-JUL-06:10 0.571133E+09 360.56 03-JUL-05:10
August 0.222440E+09 163.80 01-AUG-06:10 0.596575E+09 360.56 01-AUG-05:10
September 0.200622E+09 163.80 01-SEP-06:10 0.559451E+09 360.56 01-SEP-05:10
October 0.206945E+09 163.80 02-OCT-06:10 0.577364E+09 360.56 02-OCT-05:10
November 0.203243E+09 163.80 01-NOV-06:10 0.562307E+09 360.56 01-NOV-05:10
December 0.201736E+09 163.80 01-DEC-07:10 0.571133E+09 360.56 01-DEC-06:10
             
Annual Sum or Average 0.248317E+10     0.685672E+10    
Minimum of Months 0.188140E+09 163.80   0.523106E+09 360.56  
Maximum of Months 0.222473E+09 163.80   0.596575E+09 360.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.539803E+09 427.33 02-JAN-07:10 0.314987E+09 196.71 02-JAN-06:10
February 0.490831E+09 427.33 01-FEB-07:10 0.285387E+09 196.71 01-FEB-06:10
March 0.580400E+09 427.33 01-MAR-07:10 0.325468E+09 196.71 01-MAR-06:10
April 0.523479E+09 427.33 03-APR-06:10 0.305215E+09 196.71 03-APR-05:10
May 0.560059E+09 427.33 01-MAY-06:10 0.320228E+09 196.71 01-MAY-05:10
June 0.557238E+09 427.33 01-JUN-06:10 0.313854E+09 196.71 01-JUN-05:10
July 0.526300E+09 427.33 03-JUL-06:10 0.311588E+09 196.71 03-JUL-05:10
August 0.580314E+09 427.33 01-AUG-06:10 0.325468E+09 196.71 01-AUG-05:10
September 0.523394E+09 427.33 01-SEP-06:10 0.305215E+09 196.71 01-SEP-05:10
October 0.539889E+09 427.33 02-OCT-06:10 0.314987E+09 196.71 02-OCT-05:10
November 0.530231E+09 427.33 01-NOV-06:10 0.306773E+09 196.71 01-NOV-05:10
December 0.526300E+09 427.33 01-DEC-07:10 0.311588E+09 196.71 01-DEC-06:10
             
Annual Sum or Average 0.647824E+10     0.374076E+10    
Minimum of Months 0.490831E+09 427.33   0.285387E+09 196.71  
Maximum of Months 0.580400E+09 427.33   0.325468E+09 196.71  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 55252314.53 43.74 02-JAN-07:10 8593131.60 5.37 02-JAN-06:10
February 50239715.38 43.74 01-FEB-07:10 7785593.60 5.37 01-FEB-06:10
March 59407610.51 43.74 01-MAR-07:10 8879054.14 5.37 01-MAR-06:10
April 53581448.15 43.74 03-APR-06:10 8326528.14 5.37 03-APR-05:10
May 57325588.52 43.74 01-MAY-06:10 8736092.87 5.37 01-MAY-05:10
June 57036904.80 43.74 01-JUN-06:10 8562221.05 5.37 01-JUN-05:10
July 53870131.87 43.74 03-JUL-06:10 8500399.96 5.37 03-JUL-05:10
August 59398862.52 43.74 01-AUG-06:10 8879054.14 5.37 01-AUG-05:10
September 53572700.16 43.74 01-SEP-06:10 8326528.14 5.37 01-SEP-05:10
October 55261062.52 43.74 02-OCT-06:10 8593131.60 5.37 02-OCT-05:10
November 54272539.48 43.74 01-NOV-06:10 8369030.14 5.37 01-NOV-05:10
December 53870131.87 43.74 01-DEC-07:10 8500399.96 5.37 01-DEC-06:10
             
Annual Sum or Average 0.663089E+09     0.102051E+09    
Minimum of Months 50239715.38 43.74   7785593.60 5.37  
Maximum of Months 59407610.51 43.74   8879054.14 5.37  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.296725E+09 234.90 02-JAN-07:10 0.827978E+09 517.07 02-JAN-06:10
February 0.269806E+09 234.90 01-FEB-07:10 0.750169E+09 517.07 01-FEB-06:10
March 0.319041E+09 234.90 01-MAR-07:10 0.855528E+09 517.07 01-MAR-06:10
April 0.287752E+09 234.90 03-APR-06:10 0.802290E+09 517.07 03-APR-05:10
May 0.307860E+09 234.90 01-MAY-06:10 0.841753E+09 517.07 01-MAY-05:10
June 0.306309E+09 234.90 01-JUN-06:10 0.825000E+09 517.07 01-JUN-05:10
July 0.289303E+09 234.90 03-JUL-06:10 0.819043E+09 517.07 03-JUL-05:10
August 0.318994E+09 234.90 01-AUG-06:10 0.855528E+09 517.07 01-AUG-05:10
September 0.287705E+09 234.90 01-SEP-06:10 0.802290E+09 517.07 01-SEP-05:10
October 0.296772E+09 234.90 02-OCT-06:10 0.827978E+09 517.07 02-OCT-05:10
November 0.291464E+09 234.90 01-NOV-06:10 0.806385E+09 517.07 01-NOV-05:10
December 0.289303E+09 234.90 01-DEC-07:10 0.819043E+09 517.07 01-DEC-06:10
             
Annual Sum or Average 0.356103E+10     0.983299E+10    
Minimum of Months 0.269806E+09 234.90   0.750169E+09 517.07  
Maximum of Months 0.319041E+09 234.90   0.855528E+09 517.07  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 55252314.53 43.74 02-JAN-07:10 34293067.55 21.42 02-JAN-06:10
February 50239715.38 43.74 01-FEB-07:10 31070382.70 21.42 01-FEB-06:10
March 59407610.51 43.74 01-MAR-07:10 35434113.87 21.42 01-MAR-06:10
April 53581448.15 43.74 03-APR-06:10 33229118.96 21.42 03-APR-05:10
May 57325588.52 43.74 01-MAY-06:10 34863590.71 21.42 01-MAY-05:10
June 57036904.80 43.74 01-JUN-06:10 34169711.20 21.42 01-JUN-05:10
July 53870131.87 43.74 03-JUL-06:10 33922998.48 21.42 03-JUL-05:10
August 59398862.52 43.74 01-AUG-06:10 35434113.87 21.42 01-AUG-05:10
September 53572700.16 43.74 01-SEP-06:10 33229118.96 21.42 01-SEP-05:10
October 55261062.52 43.74 02-OCT-06:10 34293067.55 21.42 02-OCT-05:10
November 54272539.48 43.74 01-NOV-06:10 33398733.96 21.42 01-NOV-05:10
December 53870131.87 43.74 01-DEC-07:10 33922998.48 21.42 01-DEC-06:10
             
Annual Sum or Average 0.663089E+09     0.407261E+09    
Minimum of Months 50239715.38 43.74   31070382.70 21.42  
Maximum of Months 59407610.51 43.74   35434113.87 21.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.604024E+09 478.17 02-JAN-07:10 0.842623E+09 526.22 02-JAN-06:10
February 0.549226E+09 478.17 01-FEB-07:10 0.763438E+09 526.22 01-FEB-06:10
March 0.649450E+09 478.17 01-MAR-07:10 0.870660E+09 526.22 01-MAR-06:10
April 0.585758E+09 478.17 03-APR-06:10 0.816480E+09 526.22 03-APR-05:10
May 0.626689E+09 478.17 01-MAY-06:10 0.856641E+09 526.22 01-MAY-05:10
June 0.623533E+09 478.17 01-JUN-06:10 0.839592E+09 526.22 01-JUN-05:10
July 0.588914E+09 478.17 03-JUL-06:10 0.833530E+09 526.22 03-JUL-05:10
August 0.649354E+09 478.17 01-AUG-06:10 0.870660E+09 526.22 01-AUG-05:10
September 0.585662E+09 478.17 01-SEP-06:10 0.816480E+09 526.22 01-SEP-05:10
October 0.604119E+09 478.17 02-OCT-06:10 0.842623E+09 526.22 02-OCT-05:10
November 0.593313E+09 478.17 01-NOV-06:10 0.820648E+09 526.22 01-NOV-05:10
December 0.588914E+09 478.17 01-DEC-07:10 0.833530E+09 526.22 01-DEC-06:10
             
Annual Sum or Average 0.724895E+10     0.100069E+11    
Minimum of Months 0.549226E+09 478.17   0.763438E+09 526.22  
Maximum of Months 0.649450E+09 478.17   0.870660E+09 526.22  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.115052E+10 910.80 02-JAN-07:10 0.291854E+10 1822.63 02-JAN-06:10
February 0.104614E+10 910.80 01-FEB-07:10 0.264427E+10 1822.63 01-FEB-06:10
March 0.123705E+10 910.80 01-MAR-07:10 0.301565E+10 1822.63 01-MAR-06:10
April 0.111573E+10 910.80 03-APR-06:10 0.282800E+10 1822.63 03-APR-05:10
May 0.119369E+10 910.80 01-MAY-06:10 0.296710E+10 1822.63 01-MAY-05:10
June 0.118768E+10 910.80 01-JUN-06:10 0.290805E+10 1822.63 01-JUN-05:10
July 0.112174E+10 910.80 03-JUL-06:10 0.288705E+10 1822.63 03-JUL-05:10
August 0.123687E+10 910.80 01-AUG-06:10 0.301565E+10 1822.63 01-AUG-05:10
September 0.111555E+10 910.80 01-SEP-06:10 0.282800E+10 1822.63 01-SEP-05:10
October 0.115070E+10 910.80 02-OCT-06:10 0.291854E+10 1822.63 02-OCT-05:10
November 0.113012E+10 910.80 01-NOV-06:10 0.284243E+10 1822.63 01-NOV-05:10
December 0.112174E+10 910.80 01-DEC-07:10 0.288705E+10 1822.63 01-DEC-06:10
             
Annual Sum or Average 0.138075E+11     0.346603E+11    
Minimum of Months 0.104614E+10 910.80   0.264427E+10 1822.63  
Maximum of Months 0.123705E+10 910.80   0.301565E+10 1822.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.120054E+10 950.40 02-JAN-07:10 0.304544E+10 1901.88 02-JAN-06:10
February 0.109163E+10 950.40 01-FEB-07:10 0.275924E+10 1901.88 01-FEB-06:10
March 0.129083E+10 950.40 01-MAR-07:10 0.314677E+10 1901.88 01-MAR-06:10
April 0.116424E+10 950.40 03-APR-06:10 0.295095E+10 1901.88 03-APR-05:10
May 0.124559E+10 950.40 01-MAY-06:10 0.309610E+10 1901.88 01-MAY-05:10
June 0.123932E+10 950.40 01-JUN-06:10 0.303448E+10 1901.88 01-JUN-05:10
July 0.117051E+10 950.40 03-JUL-06:10 0.301257E+10 1901.88 03-JUL-05:10
August 0.129064E+10 950.40 01-AUG-06:10 0.314677E+10 1901.88 01-AUG-05:10
September 0.116405E+10 950.40 01-SEP-06:10 0.295095E+10 1901.88 01-SEP-05:10
October 0.120073E+10 950.40 02-OCT-06:10 0.304544E+10 1901.88 02-OCT-05:10
November 0.117926E+10 950.40 01-NOV-06:10 0.296601E+10 1901.88 01-NOV-05:10
December 0.117051E+10 950.40 01-DEC-07:10 0.301257E+10 1901.88 01-DEC-06:10
             
Annual Sum or Average 0.144079E+11     0.361673E+11    
Minimum of Months 0.109163E+10 950.40   0.275924E+10 1901.88  
Maximum of Months 0.129083E+10 950.40   0.314677E+10 1901.88  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.119054E+10 942.48 02-JAN-07:10 0.302006E+10 1886.03 02-JAN-06:10
February 0.108253E+10 942.48 01-FEB-07:10 0.273625E+10 1886.03 01-FEB-06:10
March 0.128008E+10 942.48 01-MAR-07:10 0.312055E+10 1886.03 01-MAR-06:10
April 0.115454E+10 942.48 03-APR-06:10 0.292636E+10 1886.03 03-APR-05:10
May 0.123521E+10 942.48 01-MAY-06:10 0.307030E+10 1886.03 01-MAY-05:10
June 0.122899E+10 942.48 01-JUN-06:10 0.300919E+10 1886.03 01-JUN-05:10
July 0.116076E+10 942.48 03-JUL-06:10 0.298747E+10 1886.03 03-JUL-05:10
August 0.127989E+10 942.48 01-AUG-06:10 0.312055E+10 1886.03 01-AUG-05:10
September 0.115435E+10 942.48 01-SEP-06:10 0.292636E+10 1886.03 01-SEP-05:10
October 0.119073E+10 942.48 02-OCT-06:10 0.302006E+10 1886.03 02-OCT-05:10
November 0.116943E+10 942.48 01-NOV-06:10 0.294130E+10 1886.03 01-NOV-05:10
December 0.116076E+10 942.48 01-DEC-07:10 0.298747E+10 1886.03 01-DEC-06:10
             
Annual Sum or Average 0.142878E+11     0.358659E+11    
Minimum of Months 0.108253E+10 942.48   0.273625E+10 1886.03  
Maximum of Months 0.128008E+10 942.48   0.312055E+10 1886.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 PACU

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 98226336.94 77.76 02-JAN-07:10 0.513838E+09 320.89 02-JAN-06:10
February 89315049.57 77.76 01-FEB-07:10 0.465550E+09 320.89 01-FEB-06:10
March 0.105614E+09 77.76 01-MAR-07:10 0.530935E+09 320.89 01-MAR-06:10
April 95255907.82 77.76 03-APR-06:10 0.497896E+09 320.89 03-APR-05:10
May 0.101912E+09 77.76 01-MAY-06:10 0.522386E+09 320.89 01-MAY-05:10
June 0.101399E+09 77.76 01-JUN-06:10 0.511990E+09 320.89 01-JUN-05:10
July 95769123.32 77.76 03-JUL-06:10 0.508293E+09 320.89 03-JUL-05:10
August 0.105598E+09 77.76 01-AUG-06:10 0.530935E+09 320.89 01-AUG-05:10
September 95240355.83 77.76 01-SEP-06:10 0.497896E+09 320.89 01-SEP-05:10
October 98241888.93 77.76 02-OCT-06:10 0.513838E+09 320.89 02-OCT-05:10
November 96484514.63 77.76 01-NOV-06:10 0.500437E+09 320.89 01-NOV-05:10
December 95769123.32 77.76 01-DEC-07:10 0.508293E+09 320.89 01-DEC-06:10
             
Annual Sum or Average 0.117882E+10     0.610229E+10    
Minimum of Months 89315049.57 77.76   0.465550E+09 320.89  
Maximum of Months 0.105614E+09 77.76   0.530935E+09 320.89  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.574629E+09 454.90 02-JAN-07:10 0.335309E+09 209.40 02-JAN-06:10
February 0.522498E+09 454.90 01-FEB-07:10 0.303799E+09 209.40 01-FEB-06:10
March 0.617845E+09 454.90 01-MAR-07:10 0.346466E+09 209.40 01-MAR-06:10
April 0.557252E+09 454.90 03-APR-06:10 0.324906E+09 209.40 03-APR-05:10
May 0.596191E+09 454.90 01-MAY-06:10 0.340888E+09 209.40 01-MAY-05:10
June 0.593189E+09 454.90 01-JUN-06:10 0.334103E+09 209.40 01-JUN-05:10
July 0.560254E+09 454.90 03-JUL-06:10 0.331691E+09 209.40 03-JUL-05:10
August 0.617754E+09 454.90 01-AUG-06:10 0.346466E+09 209.40 01-AUG-05:10
September 0.557161E+09 454.90 01-SEP-06:10 0.324906E+09 209.40 01-SEP-05:10
October 0.574720E+09 454.90 02-OCT-06:10 0.335309E+09 209.40 02-OCT-05:10
November 0.564439E+09 454.90 01-NOV-06:10 0.326565E+09 209.40 01-NOV-05:10
December 0.560254E+09 454.90 01-DEC-07:10 0.331691E+09 209.40 01-DEC-06:10
             
Annual Sum or Average 0.689619E+10     0.398210E+10    
Minimum of Months 0.522498E+09 454.90   0.303799E+09 209.40  
Maximum of Months 0.617845E+09 454.90   0.346466E+09 209.40  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.150409E+09 119.07 02-JAN-07:10 0.599570E+09 374.43 02-JAN-06:10
February 0.136764E+09 119.07 01-FEB-07:10 0.543226E+09 374.43 01-FEB-06:10
March 0.161721E+09 119.07 01-MAR-07:10 0.619520E+09 374.43 01-MAR-06:10
April 0.145861E+09 119.07 03-APR-06:10 0.580969E+09 374.43 03-APR-05:10
May 0.156053E+09 119.07 01-MAY-06:10 0.609545E+09 374.43 01-MAY-05:10
June 0.155267E+09 119.07 01-JUN-06:10 0.597414E+09 374.43 01-JUN-05:10
July 0.146646E+09 119.07 03-JUL-06:10 0.593100E+09 374.43 03-JUL-05:10
August 0.161697E+09 119.07 01-AUG-06:10 0.619520E+09 374.43 01-AUG-05:10
September 0.145837E+09 119.07 01-SEP-06:10 0.580969E+09 374.43 01-SEP-05:10
October 0.150433E+09 119.07 02-OCT-06:10 0.599570E+09 374.43 02-OCT-05:10
November 0.147742E+09 119.07 01-NOV-06:10 0.583934E+09 374.43 01-NOV-05:10
December 0.146646E+09 119.07 01-DEC-07:10 0.593100E+09 374.43 01-DEC-06:10
             
Annual Sum or Average 0.180508E+10     0.712044E+10    
Minimum of Months 0.136764E+09 119.07   0.543226E+09 374.43  
Maximum of Months 0.161721E+09 119.07   0.619520E+09 374.43  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.268986E+09 212.94 02-JAN-07:10 0.107225E+10 669.62 02-JAN-06:10
February 0.244583E+09 212.94 01-FEB-07:10 0.971483E+09 669.62 01-FEB-06:10
March 0.289215E+09 212.94 01-MAR-07:10 0.110792E+10 669.62 01-MAR-06:10
April 0.260851E+09 212.94 03-APR-06:10 0.103898E+10 669.62 03-APR-05:10
May 0.279079E+09 212.94 01-MAY-06:10 0.109009E+10 669.62 01-MAY-05:10
June 0.277673E+09 212.94 01-JUN-06:10 0.106839E+10 669.62 01-JUN-05:10
July 0.262257E+09 212.94 03-JUL-06:10 0.106068E+10 669.62 03-JUL-05:10
August 0.289172E+09 212.94 01-AUG-06:10 0.110792E+10 669.62 01-AUG-05:10
September 0.260809E+09 212.94 01-SEP-06:10 0.103898E+10 669.62 01-SEP-05:10
October 0.269028E+09 212.94 02-OCT-06:10 0.107225E+10 669.62 02-OCT-05:10
November 0.264216E+09 212.94 01-NOV-06:10 0.104428E+10 669.62 01-NOV-05:10
December 0.262257E+09 212.94 01-DEC-07:10 0.106068E+10 669.62 01-DEC-06:10
             
Annual Sum or Average 0.322812E+10     0.127339E+11    
Minimum of Months 0.244583E+09 212.94   0.971483E+09 669.62  
Maximum of Months 0.289215E+09 212.94   0.110792E+10 669.62  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 55252314.53 43.74 02-JAN-07:10 34293067.55 21.42 02-JAN-06:10
February 50239715.38 43.74 01-FEB-07:10 31070382.70 21.42 01-FEB-06:10
March 59407610.51 43.74 01-MAR-07:10 35434113.87 21.42 01-MAR-06:10
April 53581448.15 43.74 03-APR-06:10 33229118.96 21.42 03-APR-05:10
May 57325588.52 43.74 01-MAY-06:10 34863590.71 21.42 01-MAY-05:10
June 57036904.80 43.74 01-JUN-06:10 34169711.20 21.42 01-JUN-05:10
July 53870131.87 43.74 03-JUL-06:10 33922998.48 21.42 03-JUL-05:10
August 59398862.52 43.74 01-AUG-06:10 35434113.87 21.42 01-AUG-05:10
September 53572700.16 43.74 01-SEP-06:10 33229118.96 21.42 01-SEP-05:10
October 55261062.52 43.74 02-OCT-06:10 34293067.55 21.42 02-OCT-05:10
November 54272539.48 43.74 01-NOV-06:10 33398733.96 21.42 01-NOV-05:10
December 53870131.87 43.74 01-DEC-07:10 33922998.48 21.42 01-DEC-06:10
             
Annual Sum or Average 0.663089E+09     0.407261E+09    
Minimum of Months 50239715.38 43.74   31070382.70 21.42  
Maximum of Months 59407610.51 43.74   35434113.87 21.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.486016E+09 384.75 02-JAN-07:10 0.135596E+10 846.80 02-JAN-06:10
February 0.441923E+09 384.75 01-FEB-07:10 0.122854E+10 846.80 01-FEB-06:10
March 0.522567E+09 384.75 01-MAR-07:10 0.140108E+10 846.80 01-MAR-06:10
April 0.471318E+09 384.75 03-APR-06:10 0.131389E+10 846.80 03-APR-05:10
May 0.504253E+09 384.75 01-MAY-06:10 0.137852E+10 846.80 01-MAY-05:10
June 0.501714E+09 384.75 01-JUN-06:10 0.135108E+10 846.80 01-JUN-05:10
July 0.473858E+09 384.75 03-JUL-06:10 0.134133E+10 846.80 03-JUL-05:10
August 0.522490E+09 384.75 01-AUG-06:10 0.140108E+10 846.80 01-AUG-05:10
September 0.471241E+09 384.75 01-SEP-06:10 0.131389E+10 846.80 01-SEP-05:10
October 0.486093E+09 384.75 02-OCT-06:10 0.135596E+10 846.80 02-OCT-05:10
November 0.477397E+09 384.75 01-NOV-06:10 0.132060E+10 846.80 01-NOV-05:10
December 0.473858E+09 384.75 01-DEC-07:10 0.134133E+10 846.80 01-DEC-06:10
             
Annual Sum or Average 0.583273E+10     0.161033E+11    
Minimum of Months 0.441923E+09 384.75   0.122854E+10 846.80  
Maximum of Months 0.522567E+09 384.75   0.140108E+10 846.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.752273E+09 595.53 02-JAN-07:10 0.887981E+09 554.54 02-JAN-06:10
February 0.684025E+09 595.53 01-FEB-07:10 0.804533E+09 554.54 01-FEB-06:10
March 0.808848E+09 595.53 01-MAR-07:10 0.917527E+09 554.54 01-MAR-06:10
April 0.729524E+09 595.53 03-APR-06:10 0.860432E+09 554.54 03-APR-05:10
May 0.780501E+09 595.53 01-MAY-06:10 0.902754E+09 554.54 01-MAY-05:10
June 0.776570E+09 595.53 01-JUN-06:10 0.884787E+09 554.54 01-JUN-05:10
July 0.733454E+09 595.53 03-JUL-06:10 0.878399E+09 554.54 03-JUL-05:10
August 0.808729E+09 595.53 01-AUG-06:10 0.917527E+09 554.54 01-AUG-05:10
September 0.729404E+09 595.53 01-SEP-06:10 0.860432E+09 554.54 01-SEP-05:10
October 0.752392E+09 595.53 02-OCT-06:10 0.887981E+09 554.54 02-OCT-05:10
November 0.738933E+09 595.53 01-NOV-06:10 0.864824E+09 554.54 01-NOV-05:10
December 0.733454E+09 595.53 01-DEC-07:10 0.878399E+09 554.54 01-DEC-06:10
             
Annual Sum or Average 0.902811E+10     0.105456E+11    
Minimum of Months 0.684025E+09 595.53   0.804533E+09 554.54  
Maximum of Months 0.808848E+09 595.53   0.917527E+09 554.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.139304E+09 110.28 02-JAN-07:10 81287018.65 50.76 02-JAN-06:10
February 0.126666E+09 110.28 01-FEB-07:10 73648085.69 50.76 01-FEB-06:10
March 0.149781E+09 110.28 01-MAR-07:10 83991712.62 50.76 01-MAR-06:10
April 0.135091E+09 110.28 03-APR-06:10 78765074.28 50.76 03-APR-05:10
May 0.144531E+09 110.28 01-MAY-06:10 82639365.64 50.76 01-MAY-05:10
June 0.143803E+09 110.28 01-JUN-06:10 80994619.30 50.76 01-JUN-05:10
July 0.135819E+09 110.28 03-JUL-06:10 80409820.61 50.76 03-JUL-05:10
August 0.149758E+09 110.28 01-AUG-06:10 83991712.62 50.76 01-AUG-05:10
September 0.135069E+09 110.28 01-SEP-06:10 78765074.28 50.76 01-SEP-05:10
October 0.139326E+09 110.28 02-OCT-06:10 81287018.65 50.76 02-OCT-05:10
November 0.136834E+09 110.28 01-NOV-06:10 79167123.38 50.76 01-NOV-05:10
December 0.135819E+09 110.28 01-DEC-07:10 80409820.61 50.76 01-DEC-06:10
             
Annual Sum or Average 0.167180E+10     0.965356E+09    
Minimum of Months 0.126666E+09 110.28   73648085.69 50.76  
Maximum of Months 0.149781E+09 110.28   83991712.62 50.76  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.491132E+09 388.80 02-JAN-07:10 0.256919E+10 1604.46 02-JAN-06:10
February 0.446575E+09 388.80 01-FEB-07:10 0.232775E+10 1604.46 01-FEB-06:10
March 0.528068E+09 388.80 01-MAR-07:10 0.265468E+10 1604.46 01-MAR-06:10
April 0.476280E+09 388.80 03-APR-06:10 0.248948E+10 1604.46 03-APR-05:10
May 0.509561E+09 388.80 01-MAY-06:10 0.261193E+10 1604.46 01-MAY-05:10
June 0.506995E+09 388.80 01-JUN-06:10 0.255995E+10 1604.46 01-JUN-05:10
July 0.478846E+09 388.80 03-JUL-06:10 0.254146E+10 1604.46 03-JUL-05:10
August 0.527990E+09 388.80 01-AUG-06:10 0.265468E+10 1604.46 01-AUG-05:10
September 0.476202E+09 388.80 01-SEP-06:10 0.248948E+10 1604.46 01-SEP-05:10
October 0.491209E+09 388.80 02-OCT-06:10 0.256919E+10 1604.46 02-OCT-05:10
November 0.482423E+09 388.80 01-NOV-06:10 0.250219E+10 1604.46 01-NOV-05:10
December 0.478846E+09 388.80 01-DEC-07:10 0.254146E+10 1604.46 01-DEC-06:10
             
Annual Sum or Average 0.589412E+10     0.305114E+11    
Minimum of Months 0.446575E+09 388.80   0.232775E+10 1604.46  
Maximum of Months 0.528068E+09 388.80   0.265468E+10 1604.46  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.148817E+09 117.81 02-JAN-07:10 0.207603E+09 129.65 02-JAN-06:10
February 0.135316E+09 117.81 01-FEB-07:10 0.188093E+09 129.65 01-FEB-06:10
March 0.160009E+09 117.81 01-MAR-07:10 0.214510E+09 129.65 01-MAR-06:10
April 0.144317E+09 117.81 03-APR-06:10 0.201162E+09 129.65 03-APR-05:10
May 0.154402E+09 117.81 01-MAY-06:10 0.211057E+09 129.65 01-MAY-05:10
June 0.153624E+09 117.81 01-JUN-06:10 0.206856E+09 129.65 01-JUN-05:10
July 0.145095E+09 117.81 03-JUL-06:10 0.205362E+09 129.65 03-JUL-05:10
August 0.159986E+09 117.81 01-AUG-06:10 0.214510E+09 129.65 01-AUG-05:10
September 0.144294E+09 117.81 01-SEP-06:10 0.201162E+09 129.65 01-SEP-05:10
October 0.148841E+09 117.81 02-OCT-06:10 0.207603E+09 129.65 02-OCT-05:10
November 0.146179E+09 117.81 01-NOV-06:10 0.202189E+09 129.65 01-NOV-05:10
December 0.145095E+09 117.81 01-DEC-07:10 0.205362E+09 129.65 01-DEC-06:10
             
Annual Sum or Average 0.178597E+10     0.246547E+10    
Minimum of Months 0.135316E+09 117.81   0.188093E+09 129.65  
Maximum of Months 0.160009E+09 117.81   0.214510E+09 129.65  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 SCRUB

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 91418282.89 72.37 02-JAN-07:10 53344630.77 33.31 02-JAN-06:10
February 83124635.63 72.37 01-FEB-07:10 48331578.69 33.31 01-FEB-06:10
March 98293470.41 72.37 01-MAR-07:10 55119587.01 33.31 01-MAR-06:10
April 88653733.81 72.37 03-APR-06:10 51689604.01 33.31 03-APR-05:10
May 94848639.61 72.37 01-MAY-06:10 54232108.89 33.31 01-MAY-05:10
June 94370995.01 72.37 01-JUN-06:10 53152743.61 33.31 01-JUN-05:10
July 89131378.41 72.37 03-JUL-06:10 52768969.29 33.31 03-JUL-05:10
August 98278996.33 72.37 01-AUG-06:10 55119587.01 33.31 01-AUG-05:10
September 88639259.73 72.37 01-SEP-06:10 51689604.01 33.31 01-SEP-05:10
October 91432756.97 72.37 02-OCT-06:10 53344630.77 33.31 02-OCT-05:10
November 89797186.05 72.37 01-NOV-06:10 51953448.85 33.31 01-NOV-05:10
December 89131378.41 72.37 01-DEC-07:10 52768969.29 33.31 01-DEC-06:10
             
Annual Sum or Average 0.109712E+10     0.633515E+09    
Minimum of Months 83124635.63 72.37   48331578.69 33.31  
Maximum of Months 98293470.41 72.37   55119587.01 33.31  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 SOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.214870E+09 170.10 02-JAN-07:10 0.399714E+09 249.62 02-JAN-06:10
February 0.195377E+09 170.10 01-FEB-07:10 0.362151E+09 249.62 01-FEB-06:10
March 0.231030E+09 170.10 01-MAR-07:10 0.413013E+09 249.62 01-MAR-06:10
April 0.208372E+09 170.10 03-APR-06:10 0.387312E+09 249.62 03-APR-05:10
May 0.222933E+09 170.10 01-MAY-06:10 0.406364E+09 249.62 01-MAY-05:10
June 0.221810E+09 170.10 01-JUN-06:10 0.398276E+09 249.62 01-JUN-05:10
July 0.209495E+09 170.10 03-JUL-06:10 0.395400E+09 249.62 03-JUL-05:10
August 0.230996E+09 170.10 01-AUG-06:10 0.413013E+09 249.62 01-AUG-05:10
September 0.208338E+09 170.10 01-SEP-06:10 0.387312E+09 249.62 01-SEP-05:10
October 0.214904E+09 170.10 02-OCT-06:10 0.399714E+09 249.62 02-OCT-05:10
November 0.211060E+09 170.10 01-NOV-06:10 0.389289E+09 249.62 01-NOV-05:10
December 0.209495E+09 170.10 01-DEC-07:10 0.395400E+09 249.62 01-DEC-06:10
             
Annual Sum or Average 0.257868E+10     0.474696E+10    
Minimum of Months 0.195377E+09 170.10   0.362151E+09 249.62  
Maximum of Months 0.231030E+09 170.10   0.413013E+09 249.62  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 95497827.58 75.60 02-JAN-07:10 0.177650E+09 110.94 02-JAN-06:10
February 86834075.97 75.60 01-FEB-07:10 0.160956E+09 110.94 01-FEB-06:10
March 0.102680E+09 75.60 01-MAR-07:10 0.183561E+09 110.94 01-MAR-06:10
April 92609910.38 75.60 03-APR-06:10 0.172139E+09 110.94 03-APR-05:10
May 99081264.11 75.60 01-MAY-06:10 0.180606E+09 110.94 01-MAY-05:10
June 98582304.60 75.60 01-JUN-06:10 0.177011E+09 110.94 01-JUN-05:10
July 93108869.89 75.60 03-JUL-06:10 0.175733E+09 110.94 03-JUL-05:10
August 0.102665E+09 75.60 01-AUG-06:10 0.183561E+09 110.94 01-AUG-05:10
September 92594790.39 75.60 01-SEP-06:10 0.172139E+09 110.94 01-SEP-05:10
October 95512947.57 75.60 02-OCT-06:10 0.177650E+09 110.94 02-OCT-05:10
November 93804389.22 75.60 01-NOV-06:10 0.173017E+09 110.94 01-NOV-05:10
December 93108869.89 75.60 01-DEC-07:10 0.175733E+09 110.94 01-DEC-06:10
             
Annual Sum or Average 0.114608E+10     0.210976E+10    
Minimum of Months 86834075.97 75.60   0.160956E+09 110.94  
Maximum of Months 0.102680E+09 75.60   0.183561E+09 110.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.306957E+09 243.00 02-JAN-07:10 0.571019E+09 356.60 02-JAN-06:10
February 0.279110E+09 243.00 01-FEB-07:10 0.517358E+09 356.60 01-FEB-06:10
March 0.330042E+09 243.00 01-MAR-07:10 0.590019E+09 356.60 01-MAR-06:10
April 0.297675E+09 243.00 03-APR-06:10 0.553303E+09 356.60 03-APR-05:10
May 0.318475E+09 243.00 01-MAY-06:10 0.580519E+09 356.60 01-MAY-05:10
June 0.316872E+09 243.00 01-JUN-06:10 0.568965E+09 356.60 01-JUN-05:10
July 0.299279E+09 243.00 03-JUL-06:10 0.564857E+09 356.60 03-JUL-05:10
August 0.329994E+09 243.00 01-AUG-06:10 0.590019E+09 356.60 01-AUG-05:10
September 0.297626E+09 243.00 01-SEP-06:10 0.553303E+09 356.60 01-SEP-05:10
October 0.307006E+09 243.00 02-OCT-06:10 0.571019E+09 356.60 02-OCT-05:10
November 0.301514E+09 243.00 01-NOV-06:10 0.556128E+09 356.60 01-NOV-05:10
December 0.299279E+09 243.00 01-DEC-07:10 0.564857E+09 356.60 01-DEC-06:10
             
Annual Sum or Average 0.368383E+10     0.678137E+10    
Minimum of Months 0.279110E+09 243.00   0.517358E+09 356.60  
Maximum of Months 0.330042E+09 243.00   0.590019E+09 356.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272851E+09 216.00 02-JAN-07:10 0.142733E+10 891.37 02-JAN-06:10
February 0.248097E+09 216.00 01-FEB-07:10 0.129319E+10 891.37 01-FEB-06:10
March 0.293371E+09 216.00 01-MAR-07:10 0.147482E+10 891.37 01-MAR-06:10
April 0.264600E+09 216.00 03-APR-06:10 0.138304E+10 891.37 03-APR-05:10
May 0.283089E+09 216.00 01-MAY-06:10 0.145107E+10 891.37 01-MAY-05:10
June 0.281664E+09 216.00 01-JUN-06:10 0.142219E+10 891.37 01-JUN-05:10
July 0.266025E+09 216.00 03-JUL-06:10 0.141192E+10 891.37 03-JUL-05:10
August 0.293328E+09 216.00 01-AUG-06:10 0.147482E+10 891.37 01-AUG-05:10
September 0.264557E+09 216.00 01-SEP-06:10 0.138304E+10 891.37 01-SEP-05:10
October 0.272894E+09 216.00 02-OCT-06:10 0.142733E+10 891.37 02-OCT-05:10
November 0.268013E+09 216.00 01-NOV-06:10 0.139010E+10 891.37 01-NOV-05:10
December 0.266025E+09 216.00 01-DEC-07:10 0.141192E+10 891.37 01-DEC-06:10
             
Annual Sum or Average 0.327451E+10     0.169508E+11    
Minimum of Months 0.248097E+09 216.00   0.129319E+10 891.37  
Maximum of Months 0.293371E+09 216.00   0.147482E+10 891.37  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.670401E+09 530.72 02-JAN-07:10 0.391194E+09 244.30 02-JAN-06:10
February 0.609581E+09 530.72 01-FEB-07:10 0.354432E+09 244.30 01-FEB-06:10
March 0.720819E+09 530.72 01-MAR-07:10 0.404211E+09 244.30 01-MAR-06:10
April 0.650127E+09 530.72 03-APR-06:10 0.379057E+09 244.30 03-APR-05:10
May 0.695557E+09 530.72 01-MAY-06:10 0.397702E+09 244.30 01-MAY-05:10
June 0.692054E+09 530.72 01-JUN-06:10 0.389787E+09 244.30 01-JUN-05:10
July 0.653630E+09 530.72 03-JUL-06:10 0.386973E+09 244.30 03-JUL-05:10
August 0.720713E+09 530.72 01-AUG-06:10 0.404211E+09 244.30 01-AUG-05:10
September 0.650021E+09 530.72 01-SEP-06:10 0.379057E+09 244.30 01-SEP-05:10
October 0.670507E+09 530.72 02-OCT-06:10 0.391194E+09 244.30 02-OCT-05:10
November 0.658513E+09 530.72 01-NOV-06:10 0.380992E+09 244.30 01-NOV-05:10
December 0.653630E+09 530.72 01-DEC-07:10 0.386973E+09 244.30 01-DEC-06:10
             
Annual Sum or Average 0.804555E+10     0.464578E+10    
Minimum of Months 0.609581E+09 530.72   0.354432E+09 244.30  
Maximum of Months 0.720819E+09 530.72   0.404211E+09 244.30  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.405184E+09 320.76 02-JAN-07:10 63016404.11 39.35 02-JAN-06:10
February 0.368425E+09 320.76 01-FEB-07:10 57094448.86 39.35 01-FEB-06:10
March 0.435656E+09 320.76 01-MAR-07:10 65113172.95 39.35 01-MAR-06:10
April 0.392931E+09 320.76 03-APR-06:10 61061308.83 39.35 03-APR-05:10
May 0.420388E+09 320.76 01-MAY-06:10 64064788.53 39.35 01-MAY-05:10
June 0.418271E+09 320.76 01-JUN-06:10 62789726.39 39.35 01-JUN-05:10
July 0.395048E+09 320.76 03-JUL-06:10 62336370.97 39.35 03-JUL-05:10
August 0.435592E+09 320.76 01-AUG-06:10 65113172.95 39.35 01-AUG-05:10
September 0.392866E+09 320.76 01-SEP-06:10 61061308.83 39.35 01-SEP-05:10
October 0.405248E+09 320.76 02-OCT-06:10 63016404.11 39.35 02-OCT-05:10
November 0.397999E+09 320.76 01-NOV-06:10 61372990.69 39.35 01-NOV-05:10
December 0.395048E+09 320.76 01-DEC-07:10 62336370.97 39.35 01-DEC-06:10
             
Annual Sum or Average 0.486265E+10     0.748376E+09    
Minimum of Months 0.368425E+09 320.76   57094448.86 39.35  
Maximum of Months 0.435656E+09 320.76   65113172.95 39.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.941336E+09 745.20 02-JAN-07:10 0.146402E+09 91.43 02-JAN-06:10
February 0.855936E+09 745.20 01-FEB-07:10 0.132644E+09 91.43 01-FEB-06:10
March 0.101213E+10 745.20 01-MAR-07:10 0.151273E+09 91.43 01-MAR-06:10
April 0.912869E+09 745.20 03-APR-06:10 0.141860E+09 91.43 03-APR-05:10
May 0.976658E+09 745.20 01-MAY-06:10 0.148837E+09 91.43 01-MAY-05:10
June 0.971740E+09 745.20 01-JUN-06:10 0.145875E+09 91.43 01-JUN-05:10
July 0.917787E+09 745.20 03-JUL-06:10 0.144822E+09 91.43 03-JUL-05:10
August 0.101198E+10 745.20 01-AUG-06:10 0.151273E+09 91.43 01-AUG-05:10
September 0.912720E+09 745.20 01-SEP-06:10 0.141860E+09 91.43 01-SEP-05:10
October 0.941485E+09 745.20 02-OCT-06:10 0.146402E+09 91.43 02-OCT-05:10
November 0.924643E+09 745.20 01-NOV-06:10 0.142584E+09 91.43 01-NOV-05:10
December 0.917787E+09 745.20 01-DEC-07:10 0.144822E+09 91.43 01-DEC-06:10
             
Annual Sum or Average 0.112971E+11     0.173865E+10    
Minimum of Months 0.855936E+09 745.20   0.132644E+09 91.43  
Maximum of Months 0.101213E+10 745.20   0.151273E+09 91.43  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.213309E+09 168.86 02-JAN-07:10 0.124471E+09 77.73 02-JAN-06:10
February 0.193957E+09 168.86 01-FEB-07:10 0.112774E+09 77.73 01-FEB-06:10
March 0.229351E+09 168.86 01-MAR-07:10 0.128612E+09 77.73 01-MAR-06:10
April 0.206859E+09 168.86 03-APR-06:10 0.120609E+09 77.73 03-APR-05:10
May 0.221313E+09 168.86 01-MAY-06:10 0.126542E+09 77.73 01-MAY-05:10
June 0.220199E+09 168.86 01-JUN-06:10 0.124023E+09 77.73 01-JUN-05:10
July 0.207973E+09 168.86 03-JUL-06:10 0.123128E+09 77.73 03-JUL-05:10
August 0.229318E+09 168.86 01-AUG-06:10 0.128612E+09 77.73 01-AUG-05:10
September 0.206825E+09 168.86 01-SEP-06:10 0.120609E+09 77.73 01-SEP-05:10
October 0.213343E+09 168.86 02-OCT-06:10 0.124471E+09 77.73 02-OCT-05:10
November 0.209527E+09 168.86 01-NOV-06:10 0.121225E+09 77.73 01-NOV-05:10
December 0.207973E+09 168.86 01-DEC-07:10 0.123128E+09 77.73 01-DEC-06:10
             
Annual Sum or Average 0.255995E+10     0.147820E+10    
Minimum of Months 0.193957E+09 168.86   0.112774E+09 77.73  
Maximum of Months 0.229351E+09 168.86   0.128612E+09 77.73  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.278608E+09 220.56 02-JAN-07:10 0.162574E+09 101.53 02-JAN-06:10
February 0.253332E+09 220.56 01-FEB-07:10 0.147296E+09 101.53 01-FEB-06:10
March 0.299561E+09 220.56 01-MAR-07:10 0.167984E+09 101.53 01-MAR-06:10
April 0.270183E+09 220.56 03-APR-06:10 0.157530E+09 101.53 03-APR-05:10
May 0.289063E+09 220.56 01-MAY-06:10 0.165279E+09 101.53 01-MAY-05:10
June 0.287607E+09 220.56 01-JUN-06:10 0.161989E+09 101.53 01-JUN-05:10
July 0.271638E+09 220.56 03-JUL-06:10 0.160820E+09 101.53 03-JUL-05:10
August 0.299517E+09 220.56 01-AUG-06:10 0.167984E+09 101.53 01-AUG-05:10
September 0.270139E+09 220.56 01-SEP-06:10 0.157530E+09 101.53 01-SEP-05:10
October 0.278652E+09 220.56 02-OCT-06:10 0.162574E+09 101.53 02-OCT-05:10
November 0.273668E+09 220.56 01-NOV-06:10 0.158334E+09 101.53 01-NOV-05:10
December 0.271638E+09 220.56 01-DEC-07:10 0.160820E+09 101.53 01-DEC-06:10
             
Annual Sum or Average 0.334361E+10     0.193071E+10    
Minimum of Months 0.253332E+09 220.56   0.147296E+09 101.53  
Maximum of Months 0.299561E+09 220.56   0.167984E+09 101.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 42974022.41 34.02 02-JAN-07:10 6683582.04 4.17 02-JAN-06:10
February 39075334.19 34.02 01-FEB-07:10 6055493.62 4.17 01-FEB-06:10
March 46205919.28 34.02 01-MAR-07:10 6905967.42 4.17 01-MAR-06:10
April 41674459.67 34.02 03-APR-06:10 6476222.71 4.17 03-APR-05:10
May 44586568.85 34.02 01-MAY-06:10 6794774.73 4.17 01-MAY-05:10
June 44362037.07 34.02 01-JUN-06:10 6659540.38 4.17 01-JUN-05:10
July 41898991.45 34.02 03-JUL-06:10 6611457.06 4.17 03-JUL-05:10
August 46199115.29 34.02 01-AUG-06:10 6905967.42 4.17 01-AUG-05:10
September 41667655.68 34.02 01-SEP-06:10 6476222.71 4.17 01-SEP-05:10
October 42980826.41 34.02 02-OCT-06:10 6683582.04 4.17 02-OCT-05:10
November 42211975.15 34.02 01-NOV-06:10 6509279.99 4.17 01-NOV-05:10
December 41898991.45 34.02 01-DEC-07:10 6611457.06 4.17 01-DEC-06:10
             
Annual Sum or Average 0.515736E+09     79373547.16    
Minimum of Months 39075334.19 34.02   6055493.62 4.17  
Maximum of Months 46205919.28 34.02   6905967.42 4.17  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.368349E+09 291.60 02-JAN-07:10 57287596.84 35.78 02-JAN-06:10
February 0.334931E+09 291.60 01-FEB-07:10 51904005.23 35.78 01-FEB-06:10
March 0.396051E+09 291.60 01-MAR-07:10 59193748.89 35.78 01-MAR-06:10
April 0.357210E+09 291.60 03-APR-06:10 55510238.85 35.78 03-APR-05:10
May 0.382171E+09 291.60 01-MAY-06:10 58240672.87 35.78 01-MAY-05:10
June 0.380246E+09 291.60 01-JUN-06:10 57081526.35 35.78 01-JUN-05:10
July 0.359134E+09 291.60 03-JUL-06:10 56669385.36 35.78 03-JUL-05:10
August 0.395992E+09 291.60 01-AUG-06:10 59193748.89 35.78 01-AUG-05:10
September 0.357151E+09 291.60 01-SEP-06:10 55510238.85 35.78 01-SEP-05:10
October 0.368407E+09 291.60 02-OCT-06:10 57287596.84 35.78 02-OCT-05:10
November 0.361817E+09 291.60 01-NOV-06:10 55793585.77 35.78 01-NOV-05:10
December 0.359134E+09 291.60 01-DEC-07:10 56669385.36 35.78 01-DEC-06:10
             
Annual Sum or Average 0.442059E+10     0.680342E+09    
Minimum of Months 0.334931E+09 291.60   51904005.23 35.78  
Maximum of Months 0.396051E+09 291.60   59193748.89 35.78  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 78358528.19 62.03 02-JAN-07:10 45724037.20 28.55 02-JAN-06:10
February 71249687.69 62.03 01-FEB-07:10 41427129.03 28.55 01-FEB-06:10
March 84251546.07 62.03 01-MAR-07:10 47245430.53 28.55 01-MAR-06:10
April 75988914.69 62.03 03-APR-06:10 44305440.73 28.55 03-APR-05:10
May 81298833.95 62.03 01-MAY-06:10 46484733.87 28.55 01-MAY-05:10
June 80889424.29 62.03 01-JUN-06:10 45559562.25 28.55 01-JUN-05:10
July 76398324.35 62.03 03-JUL-06:10 45230612.34 28.55 03-JUL-05:10
August 84239139.71 62.03 01-AUG-06:10 47245430.53 28.55 01-AUG-05:10
September 75976508.34 62.03 01-SEP-06:10 44305440.73 28.55 01-SEP-05:10
October 78370934.55 62.03 02-OCT-06:10 45724037.20 28.55 02-OCT-05:10
November 76969016.61 62.03 01-NOV-06:10 44531593.79 28.55 01-NOV-05:10
December 76398324.35 62.03 01-DEC-07:10 45230612.34 28.55 01-DEC-06:10
             
Annual Sum or Average 0.940389E+09     0.543014E+09    
Minimum of Months 71249687.69 62.03   41427129.03 28.55  
Maximum of Months 84251546.07 62.03   47245430.53 28.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.496589E+09 393.12 02-JAN-07:10 0.532704E+09 332.67 02-JAN-06:10
February 0.451537E+09 393.12 01-FEB-07:10 0.482643E+09 332.67 01-FEB-06:10
March 0.533935E+09 393.12 01-MAR-07:10 0.550429E+09 332.67 01-MAR-06:10
April 0.481572E+09 393.12 03-APR-06:10 0.516177E+09 332.67 03-APR-05:10
May 0.515223E+09 393.12 01-MAY-06:10 0.541566E+09 332.67 01-MAY-05:10
June 0.512628E+09 393.12 01-JUN-06:10 0.530788E+09 332.67 01-JUN-05:10
July 0.484166E+09 393.12 03-JUL-06:10 0.526955E+09 332.67 03-JUL-05:10
August 0.533856E+09 393.12 01-AUG-06:10 0.550429E+09 332.67 01-AUG-05:10
September 0.481493E+09 393.12 01-SEP-06:10 0.516177E+09 332.67 01-SEP-05:10
October 0.496667E+09 393.12 02-OCT-06:10 0.532704E+09 332.67 02-OCT-05:10
November 0.487783E+09 393.12 01-NOV-06:10 0.518811E+09 332.67 01-NOV-05:10
December 0.484166E+09 393.12 01-DEC-07:10 0.526955E+09 332.67 01-DEC-06:10
             
Annual Sum or Average 0.595961E+10     0.632634E+10    
Minimum of Months 0.451537E+09 393.12   0.482643E+09 332.67  
Maximum of Months 0.533935E+09 393.12   0.550429E+09 332.67  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65484224.63 51.84 02-JAN-07:10 40643588.63 25.38 02-JAN-06:10
February 59543366.38 51.84 01-FEB-07:10 36824114.70 25.38 01-FEB-06:10
March 70409019.86 51.84 01-MAR-07:10 41995938.25 25.38 01-MAR-06:10
April 63503938.54 51.84 03-APR-06:10 39382613.98 25.38 03-APR-05:10
May 67941438.25 51.84 01-MAY-06:10 41319763.44 25.38 01-MAY-05:10
June 67599294.58 51.84 01-JUN-06:10 40497388.67 25.38 01-JUN-05:10
July 63846082.21 51.84 03-JUL-06:10 40204988.75 25.38 03-JUL-05:10
August 70398651.87 51.84 01-AUG-06:10 41995938.25 25.38 01-AUG-05:10
September 63493570.55 51.84 01-SEP-06:10 39382613.98 25.38 01-SEP-05:10
October 65494592.62 51.84 02-OCT-06:10 40643588.63 25.38 02-OCT-05:10
November 64323009.75 51.84 01-NOV-06:10 39583638.92 25.38 01-NOV-05:10
December 63846082.21 51.84 01-DEC-07:10 40204988.75 25.38 01-DEC-06:10
             
Annual Sum or Average 0.785883E+09     0.482679E+09    
Minimum of Months 59543366.38 51.84   36824114.70 25.38  
Maximum of Months 70409019.86 51.84   41995938.25 25.38  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 87539675.28 69.30 02-JAN-07:10 0.122119E+09 76.26 02-JAN-06:10
February 79597902.97 69.30 01-FEB-07:10 0.110643E+09 76.26 01-FEB-06:10
March 94123168.91 69.30 01-MAR-07:10 0.126183E+09 76.26 01-MAR-06:10
April 84892417.85 69.30 03-APR-06:10 0.118330E+09 76.26 03-APR-05:10
May 90824492.11 69.30 01-MAY-06:10 0.124151E+09 76.26 01-MAY-05:10
June 90367112.55 69.30 01-JUN-06:10 0.121680E+09 76.26 01-JUN-05:10
July 85349797.40 69.30 03-JUL-06:10 0.120801E+09 76.26 03-JUL-05:10
August 94109308.93 69.30 01-AUG-06:10 0.126183E+09 76.26 01-AUG-05:10
September 84878557.86 69.30 01-SEP-06:10 0.118330E+09 76.26 01-SEP-05:10
October 87553535.27 69.30 02-OCT-06:10 0.122119E+09 76.26 02-OCT-05:10
November 85987356.79 69.30 01-NOV-06:10 0.118934E+09 76.26 01-NOV-05:10
December 85349797.40 69.30 01-DEC-07:10 0.120801E+09 76.26 01-DEC-06:10
             
Annual Sum or Average 0.105057E+10     0.145028E+10    
Minimum of Months 79597902.97 69.30   0.110643E+09 76.26  
Maximum of Months 94123168.91 69.30   0.126183E+09 76.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.613915E+09 486.00 02-JAN-07:10 0.628042E+09 392.21 02-JAN-06:10
February 0.558219E+09 486.00 01-FEB-07:10 0.569022E+09 392.21 01-FEB-06:10
March 0.660085E+09 486.00 01-MAR-07:10 0.648939E+09 392.21 01-MAR-06:10
April 0.595349E+09 486.00 03-APR-06:10 0.608557E+09 392.21 03-APR-05:10
May 0.636951E+09 486.00 01-MAY-06:10 0.638490E+09 392.21 01-MAY-05:10
June 0.633743E+09 486.00 01-JUN-06:10 0.625783E+09 392.21 01-JUN-05:10
July 0.598557E+09 486.00 03-JUL-06:10 0.621264E+09 392.21 03-JUL-05:10
August 0.659987E+09 486.00 01-AUG-06:10 0.648939E+09 392.21 01-AUG-05:10
September 0.595252E+09 486.00 01-SEP-06:10 0.608557E+09 392.21 01-SEP-05:10
October 0.614012E+09 486.00 02-OCT-06:10 0.628042E+09 392.21 02-OCT-05:10
November 0.603028E+09 486.00 01-NOV-06:10 0.611663E+09 392.21 01-NOV-05:10
December 0.598557E+09 486.00 01-DEC-07:10 0.621264E+09 392.21 01-DEC-06:10
             
Annual Sum or Average 0.736766E+10     0.745856E+10    
Minimum of Months 0.558219E+09 486.00   0.569022E+09 392.21  
Maximum of Months 0.660085E+09 486.00   0.648939E+09 392.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.920872E+09 729.00 02-JAN-07:10 0.942063E+09 588.32 02-JAN-06:10
February 0.837329E+09 729.00 01-FEB-07:10 0.853533E+09 588.32 01-FEB-06:10
March 0.990127E+09 729.00 01-MAR-07:10 0.973408E+09 588.32 01-MAR-06:10
April 0.893024E+09 729.00 03-APR-06:10 0.912835E+09 588.32 03-APR-05:10
May 0.955426E+09 729.00 01-MAY-06:10 0.957736E+09 588.32 01-MAY-05:10
June 0.950615E+09 729.00 01-JUN-06:10 0.938674E+09 588.32 01-JUN-05:10
July 0.897836E+09 729.00 03-JUL-06:10 0.931897E+09 588.32 03-JUL-05:10
August 0.989981E+09 729.00 01-AUG-06:10 0.973408E+09 588.32 01-AUG-05:10
September 0.892878E+09 729.00 01-SEP-06:10 0.912835E+09 588.32 01-SEP-05:10
October 0.921018E+09 729.00 02-OCT-06:10 0.942063E+09 588.32 02-OCT-05:10
November 0.904542E+09 729.00 01-NOV-06:10 0.917495E+09 588.32 01-NOV-05:10
December 0.897836E+09 729.00 01-DEC-07:10 0.931897E+09 588.32 01-DEC-06:10
             
Annual Sum or Average 0.110515E+11     0.111878E+11    
Minimum of Months 0.837329E+09 729.00   0.853533E+09 588.32  
Maximum of Months 0.990127E+09 729.00   0.973408E+09 588.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.122783E+10 972.00 02-JAN-07:10 0.125608E+10 784.42 02-JAN-06:10
February 0.111644E+10 972.00 01-FEB-07:10 0.113804E+10 784.42 01-FEB-06:10
March 0.132017E+10 972.00 01-MAR-07:10 0.129788E+10 784.42 01-MAR-06:10
April 0.119070E+10 972.00 03-APR-06:10 0.121711E+10 784.42 03-APR-05:10
May 0.127390E+10 972.00 01-MAY-06:10 0.127698E+10 784.42 01-MAY-05:10
June 0.126749E+10 972.00 01-JUN-06:10 0.125157E+10 784.42 01-JUN-05:10
July 0.119711E+10 972.00 03-JUL-06:10 0.124253E+10 784.42 03-JUL-05:10
August 0.131997E+10 972.00 01-AUG-06:10 0.129788E+10 784.42 01-AUG-05:10
September 0.119050E+10 972.00 01-SEP-06:10 0.121711E+10 784.42 01-SEP-05:10
October 0.122802E+10 972.00 02-OCT-06:10 0.125608E+10 784.42 02-OCT-05:10
November 0.120606E+10 972.00 01-NOV-06:10 0.122333E+10 784.42 01-NOV-05:10
December 0.119711E+10 972.00 01-DEC-07:10 0.124253E+10 784.42 01-DEC-06:10
             
Annual Sum or Average 0.147353E+11     0.149171E+11    
Minimum of Months 0.111644E+10 972.00   0.113804E+10 784.42  
Maximum of Months 0.132017E+10 972.00   0.129788E+10 784.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.143247E+09 113.40 02-JAN-07:10 0.146543E+09 91.52 02-JAN-06:10
February 0.130251E+09 113.40 01-FEB-07:10 0.132772E+09 91.52 01-FEB-06:10
March 0.154020E+09 113.40 01-MAR-07:10 0.151419E+09 91.52 01-MAR-06:10
April 0.138915E+09 113.40 03-APR-06:10 0.141996E+09 91.52 03-APR-05:10
May 0.148622E+09 113.40 01-MAY-06:10 0.148981E+09 91.52 01-MAY-05:10
June 0.147873E+09 113.40 01-JUN-06:10 0.146016E+09 91.52 01-JUN-05:10
July 0.139663E+09 113.40 03-JUL-06:10 0.144962E+09 91.52 03-JUL-05:10
August 0.153997E+09 113.40 01-AUG-06:10 0.151419E+09 91.52 01-AUG-05:10
September 0.138892E+09 113.40 01-SEP-06:10 0.141996E+09 91.52 01-SEP-05:10
October 0.143269E+09 113.40 02-OCT-06:10 0.146543E+09 91.52 02-OCT-05:10
November 0.140707E+09 113.40 01-NOV-06:10 0.142721E+09 91.52 01-NOV-05:10
December 0.139663E+09 113.40 01-DEC-07:10 0.144962E+09 91.52 01-DEC-06:10
             
Annual Sum or Average 0.171912E+10     0.174033E+10    
Minimum of Months 0.130251E+09 113.40   0.132772E+09 91.52  
Maximum of Months 0.154020E+09 113.40   0.151419E+09 91.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.596861E+09 472.50 02-JAN-07:10 0.610596E+09 381.32 02-JAN-06:10
February 0.542713E+09 472.50 01-FEB-07:10 0.553216E+09 381.32 01-FEB-06:10
March 0.641749E+09 472.50 01-MAR-07:10 0.630913E+09 381.32 01-MAR-06:10
April 0.578812E+09 472.50 03-APR-06:10 0.591652E+09 381.32 03-APR-05:10
May 0.619258E+09 472.50 01-MAY-06:10 0.620755E+09 381.32 01-MAY-05:10
June 0.616139E+09 472.50 01-JUN-06:10 0.608400E+09 381.32 01-JUN-05:10
July 0.581930E+09 472.50 03-JUL-06:10 0.604007E+09 381.32 03-JUL-05:10
August 0.641654E+09 472.50 01-AUG-06:10 0.630913E+09 381.32 01-AUG-05:10
September 0.578717E+09 472.50 01-SEP-06:10 0.591652E+09 381.32 01-SEP-05:10
October 0.596956E+09 472.50 02-OCT-06:10 0.610596E+09 381.32 02-OCT-05:10
November 0.586277E+09 472.50 01-NOV-06:10 0.594672E+09 381.32 01-NOV-05:10
December 0.581930E+09 472.50 01-DEC-07:10 0.604007E+09 381.32 01-DEC-06:10
             
Annual Sum or Average 0.716300E+10     0.725138E+10    
Minimum of Months 0.542713E+09 472.50   0.553216E+09 381.32  
Maximum of Months 0.641749E+09 472.50   0.630913E+09 381.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.383697E+09 303.75 02-JAN-07:10 0.392526E+09 245.13 02-JAN-06:10
February 0.348887E+09 303.75 01-FEB-07:10 0.355639E+09 245.13 01-FEB-06:10
March 0.412553E+09 303.75 01-MAR-07:10 0.405587E+09 245.13 01-MAR-06:10
April 0.372093E+09 303.75 03-APR-06:10 0.380348E+09 245.13 03-APR-05:10
May 0.398094E+09 303.75 01-MAY-06:10 0.399056E+09 245.13 01-MAY-05:10
June 0.396090E+09 303.75 01-JUN-06:10 0.391114E+09 245.13 01-JUN-05:10
July 0.374098E+09 303.75 03-JUL-06:10 0.388290E+09 245.13 03-JUL-05:10
August 0.412492E+09 303.75 01-AUG-06:10 0.405587E+09 245.13 01-AUG-05:10
September 0.372033E+09 303.75 01-SEP-06:10 0.380348E+09 245.13 01-SEP-05:10
October 0.383757E+09 303.75 02-OCT-06:10 0.392526E+09 245.13 02-OCT-05:10
November 0.376893E+09 303.75 01-NOV-06:10 0.382289E+09 245.13 01-NOV-05:10
December 0.374098E+09 303.75 01-DEC-07:10 0.388290E+09 245.13 01-DEC-06:10
             
Annual Sum or Average 0.460478E+10     0.466160E+10    
Minimum of Months 0.348887E+09 303.75   0.355639E+09 245.13  
Maximum of Months 0.412553E+09 303.75   0.405587E+09 245.13  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135061E+10 1069.20 02-JAN-07:10 0.138169E+10 862.87 02-JAN-06:10
February 0.122808E+10 1069.20 01-FEB-07:10 0.125185E+10 862.87 01-FEB-06:10
March 0.145219E+10 1069.20 01-MAR-07:10 0.142767E+10 862.87 01-MAR-06:10
April 0.130977E+10 1069.20 03-APR-06:10 0.133882E+10 862.87 03-APR-05:10
May 0.140129E+10 1069.20 01-MAY-06:10 0.140468E+10 862.87 01-MAY-05:10
June 0.139424E+10 1069.20 01-JUN-06:10 0.137672E+10 862.87 01-JUN-05:10
July 0.131683E+10 1069.20 03-JUL-06:10 0.136678E+10 862.87 03-JUL-05:10
August 0.145197E+10 1069.20 01-AUG-06:10 0.142767E+10 862.87 01-AUG-05:10
September 0.130955E+10 1069.20 01-SEP-06:10 0.133882E+10 862.87 01-SEP-05:10
October 0.135083E+10 1069.20 02-OCT-06:10 0.138169E+10 862.87 02-OCT-05:10
November 0.132666E+10 1069.20 01-NOV-06:10 0.134566E+10 862.87 01-NOV-05:10
December 0.131683E+10 1069.20 01-DEC-07:10 0.136678E+10 862.87 01-DEC-06:10
             
Annual Sum or Average 0.162088E+11     0.164088E+11    
Minimum of Months 0.122808E+10 1069.20   0.125185E+10 862.87  
Maximum of Months 0.145219E+10 1069.20   0.142767E+10 862.87  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.460436E+09 364.50 02-JAN-07:10 0.471031E+09 294.16 02-JAN-06:10
February 0.418664E+09 364.50 01-FEB-07:10 0.426766E+09 294.16 01-FEB-06:10
March 0.495063E+09 364.50 01-MAR-07:10 0.486704E+09 294.16 01-MAR-06:10
April 0.446512E+09 364.50 03-APR-06:10 0.456417E+09 294.16 03-APR-05:10
May 0.477713E+09 364.50 01-MAY-06:10 0.478868E+09 294.16 01-MAY-05:10
June 0.475308E+09 364.50 01-JUN-06:10 0.469337E+09 294.16 01-JUN-05:10
July 0.448918E+09 364.50 03-JUL-06:10 0.465948E+09 294.16 03-JUL-05:10
August 0.494991E+09 364.50 01-AUG-06:10 0.486704E+09 294.16 01-AUG-05:10
September 0.446439E+09 364.50 01-SEP-06:10 0.456417E+09 294.16 01-SEP-05:10
October 0.460509E+09 364.50 02-OCT-06:10 0.471031E+09 294.16 02-OCT-05:10
November 0.452271E+09 364.50 01-NOV-06:10 0.458747E+09 294.16 01-NOV-05:10
December 0.448918E+09 364.50 01-DEC-07:10 0.465948E+09 294.16 01-DEC-06:10
             
Annual Sum or Average 0.552574E+10     0.559392E+10    
Minimum of Months 0.418664E+09 364.50   0.426766E+09 294.16  
Maximum of Months 0.495063E+09 364.50   0.486704E+09 294.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.675306E+09 534.60 02-JAN-07:10 0.690846E+09 431.43 02-JAN-06:10
February 0.614041E+09 534.60 01-FEB-07:10 0.625924E+09 431.43 01-FEB-06:10
March 0.726093E+09 534.60 01-MAR-07:10 0.713833E+09 431.43 01-MAR-06:10
April 0.654884E+09 534.60 03-APR-06:10 0.669412E+09 431.43 03-APR-05:10
May 0.700646E+09 534.60 01-MAY-06:10 0.702339E+09 431.43 01-MAY-05:10
June 0.697118E+09 534.60 01-JUN-06:10 0.688361E+09 431.43 01-JUN-05:10
July 0.658413E+09 534.60 03-JUL-06:10 0.683391E+09 431.43 03-JUL-05:10
August 0.725986E+09 534.60 01-AUG-06:10 0.713833E+09 431.43 01-AUG-05:10
September 0.654777E+09 534.60 01-SEP-06:10 0.669412E+09 431.43 01-SEP-05:10
October 0.675413E+09 534.60 02-OCT-06:10 0.690846E+09 431.43 02-OCT-05:10
November 0.663331E+09 534.60 01-NOV-06:10 0.672829E+09 431.43 01-NOV-05:10
December 0.658413E+09 534.60 01-DEC-07:10 0.683391E+09 431.43 01-DEC-06:10
             
Annual Sum or Average 0.810442E+10     0.820442E+10    
Minimum of Months 0.614041E+09 534.60   0.625924E+09 431.43  
Maximum of Months 0.726093E+09 534.60   0.713833E+09 431.43  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.195896E+09 155.08 02-JAN-07:10 0.114310E+09 71.39 02-JAN-06:10
February 0.178124E+09 155.08 01-FEB-07:10 0.103568E+09 71.39 01-FEB-06:10
March 0.210629E+09 155.08 01-MAR-07:10 0.118113E+09 71.39 01-MAR-06:10
April 0.189972E+09 155.08 03-APR-06:10 0.110764E+09 71.39 03-APR-05:10
May 0.203247E+09 155.08 01-MAY-06:10 0.116212E+09 71.39 01-MAY-05:10
June 0.202224E+09 155.08 01-JUN-06:10 0.113899E+09 71.39 01-JUN-05:10
July 0.190996E+09 155.08 03-JUL-06:10 0.113076E+09 71.39 03-JUL-05:10
August 0.210598E+09 155.08 01-AUG-06:10 0.118113E+09 71.39 01-AUG-05:10
September 0.189941E+09 155.08 01-SEP-06:10 0.110764E+09 71.39 01-SEP-05:10
October 0.195927E+09 155.08 02-OCT-06:10 0.114310E+09 71.39 02-OCT-05:10
November 0.192423E+09 155.08 01-NOV-06:10 0.111329E+09 71.39 01-NOV-05:10
December 0.190996E+09 155.08 01-DEC-07:10 0.113076E+09 71.39 01-DEC-06:10
             
Annual Sum or Average 0.235097E+10     0.135753E+10    
Minimum of Months 0.178124E+09 155.08   0.103568E+09 71.39  
Maximum of Months 0.210629E+09 155.08   0.118113E+09 71.39  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.195896E+09 155.08 02-JAN-07:10 0.114310E+09 71.39 02-JAN-06:10
February 0.178124E+09 155.08 01-FEB-07:10 0.103568E+09 71.39 01-FEB-06:10
March 0.210629E+09 155.08 01-MAR-07:10 0.118113E+09 71.39 01-MAR-06:10
April 0.189972E+09 155.08 03-APR-06:10 0.110764E+09 71.39 03-APR-05:10
May 0.203247E+09 155.08 01-MAY-06:10 0.116212E+09 71.39 01-MAY-05:10
June 0.202224E+09 155.08 01-JUN-06:10 0.113899E+09 71.39 01-JUN-05:10
July 0.190996E+09 155.08 03-JUL-06:10 0.113076E+09 71.39 03-JUL-05:10
August 0.210598E+09 155.08 01-AUG-06:10 0.118113E+09 71.39 01-AUG-05:10
September 0.189941E+09 155.08 01-SEP-06:10 0.110764E+09 71.39 01-SEP-05:10
October 0.195927E+09 155.08 02-OCT-06:10 0.114310E+09 71.39 02-OCT-05:10
November 0.192423E+09 155.08 01-NOV-06:10 0.111329E+09 71.39 01-NOV-05:10
December 0.190996E+09 155.08 01-DEC-07:10 0.113076E+09 71.39 01-DEC-06:10
             
Annual Sum or Average 0.235097E+10     0.135753E+10    
Minimum of Months 0.178124E+09 155.08   0.103568E+09 71.39  
Maximum of Months 0.210629E+09 155.08   0.118113E+09 71.39  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.195896E+09 155.08 02-JAN-07:10 0.114310E+09 71.39 02-JAN-06:10
February 0.178124E+09 155.08 01-FEB-07:10 0.103568E+09 71.39 01-FEB-06:10
March 0.210629E+09 155.08 01-MAR-07:10 0.118113E+09 71.39 01-MAR-06:10
April 0.189972E+09 155.08 03-APR-06:10 0.110764E+09 71.39 03-APR-05:10
May 0.203247E+09 155.08 01-MAY-06:10 0.116212E+09 71.39 01-MAY-05:10
June 0.202224E+09 155.08 01-JUN-06:10 0.113899E+09 71.39 01-JUN-05:10
July 0.190996E+09 155.08 03-JUL-06:10 0.113076E+09 71.39 03-JUL-05:10
August 0.210598E+09 155.08 01-AUG-06:10 0.118113E+09 71.39 01-AUG-05:10
September 0.189941E+09 155.08 01-SEP-06:10 0.110764E+09 71.39 01-SEP-05:10
October 0.195927E+09 155.08 02-OCT-06:10 0.114310E+09 71.39 02-OCT-05:10
November 0.192423E+09 155.08 01-NOV-06:10 0.111329E+09 71.39 01-NOV-05:10
December 0.190996E+09 155.08 01-DEC-07:10 0.113076E+09 71.39 01-DEC-06:10
             
Annual Sum or Average 0.235097E+10     0.135753E+10    
Minimum of Months 0.178124E+09 155.08   0.103568E+09 71.39  
Maximum of Months 0.210629E+09 155.08   0.118113E+09 71.39  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.215486E+09 170.59 02-JAN-07:10 0.125741E+09 78.53 02-JAN-06:10
February 0.195937E+09 170.59 01-FEB-07:10 0.113924E+09 78.53 01-FEB-06:10
March 0.231692E+09 170.59 01-MAR-07:10 0.129925E+09 78.53 01-MAR-06:10
April 0.208970E+09 170.59 03-APR-06:10 0.121840E+09 78.53 03-APR-05:10
May 0.223572E+09 170.59 01-MAY-06:10 0.127833E+09 78.53 01-MAY-05:10
June 0.222446E+09 170.59 01-JUN-06:10 0.125289E+09 78.53 01-JUN-05:10
July 0.210095E+09 170.59 03-JUL-06:10 0.124384E+09 78.53 03-JUL-05:10
August 0.231658E+09 170.59 01-AUG-06:10 0.129925E+09 78.53 01-AUG-05:10
September 0.208935E+09 170.59 01-SEP-06:10 0.121840E+09 78.53 01-SEP-05:10
October 0.215520E+09 170.59 02-OCT-06:10 0.125741E+09 78.53 02-OCT-05:10
November 0.211665E+09 170.59 01-NOV-06:10 0.122462E+09 78.53 01-NOV-05:10
December 0.210095E+09 170.59 01-DEC-07:10 0.124384E+09 78.53 01-DEC-06:10
             
Annual Sum or Average 0.258607E+10     0.149329E+10    
Minimum of Months 0.195937E+09 170.59   0.113924E+09 78.53  
Maximum of Months 0.231692E+09 170.59   0.129925E+09 78.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.215486E+09 170.59 02-JAN-07:10 0.125741E+09 78.53 02-JAN-06:10
February 0.195937E+09 170.59 01-FEB-07:10 0.113924E+09 78.53 01-FEB-06:10
March 0.231692E+09 170.59 01-MAR-07:10 0.129925E+09 78.53 01-MAR-06:10
April 0.208970E+09 170.59 03-APR-06:10 0.121840E+09 78.53 03-APR-05:10
May 0.223572E+09 170.59 01-MAY-06:10 0.127833E+09 78.53 01-MAY-05:10
June 0.222446E+09 170.59 01-JUN-06:10 0.125289E+09 78.53 01-JUN-05:10
July 0.210095E+09 170.59 03-JUL-06:10 0.124384E+09 78.53 03-JUL-05:10
August 0.231658E+09 170.59 01-AUG-06:10 0.129925E+09 78.53 01-AUG-05:10
September 0.208935E+09 170.59 01-SEP-06:10 0.121840E+09 78.53 01-SEP-05:10
October 0.215520E+09 170.59 02-OCT-06:10 0.125741E+09 78.53 02-OCT-05:10
November 0.211665E+09 170.59 01-NOV-06:10 0.122462E+09 78.53 01-NOV-05:10
December 0.210095E+09 170.59 01-DEC-07:10 0.124384E+09 78.53 01-DEC-06:10
             
Annual Sum or Average 0.258607E+10     0.149329E+10    
Minimum of Months 0.195937E+09 170.59   0.113924E+09 78.53  
Maximum of Months 0.231692E+09 170.59   0.129925E+09 78.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.215486E+09 170.59 02-JAN-07:10 0.125741E+09 78.53 02-JAN-06:10
February 0.195937E+09 170.59 01-FEB-07:10 0.113924E+09 78.53 01-FEB-06:10
March 0.231692E+09 170.59 01-MAR-07:10 0.129925E+09 78.53 01-MAR-06:10
April 0.208970E+09 170.59 03-APR-06:10 0.121840E+09 78.53 03-APR-05:10
May 0.223572E+09 170.59 01-MAY-06:10 0.127833E+09 78.53 01-MAY-05:10
June 0.222446E+09 170.59 01-JUN-06:10 0.125289E+09 78.53 01-JUN-05:10
July 0.210095E+09 170.59 03-JUL-06:10 0.124384E+09 78.53 03-JUL-05:10
August 0.231658E+09 170.59 01-AUG-06:10 0.129925E+09 78.53 01-AUG-05:10
September 0.208935E+09 170.59 01-SEP-06:10 0.121840E+09 78.53 01-SEP-05:10
October 0.215520E+09 170.59 02-OCT-06:10 0.125741E+09 78.53 02-OCT-05:10
November 0.211665E+09 170.59 01-NOV-06:10 0.122462E+09 78.53 01-NOV-05:10
December 0.210095E+09 170.59 01-DEC-07:10 0.124384E+09 78.53 01-DEC-06:10
             
Annual Sum or Average 0.258607E+10     0.149329E+10    
Minimum of Months 0.195937E+09 170.59   0.113924E+09 78.53  
Maximum of Months 0.231692E+09 170.59   0.129925E+09 78.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 64461033.62 51.03 02-JAN-07:10 10025293.76 6.26 02-JAN-06:10
February 58613001.28 51.03 01-FEB-07:10 9083168.58 6.26 01-FEB-06:10
March 69308878.93 51.03 01-MAR-07:10 10358869.18 6.26 01-MAR-06:10
April 62511689.50 51.03 03-APR-06:10 9714257.22 6.26 03-APR-05:10
May 66879853.28 51.03 01-MAY-06:10 10192081.47 6.26 01-MAY-05:10
June 66543055.60 51.03 01-JUN-06:10 9989231.55 6.26 01-JUN-05:10
July 62848487.18 51.03 03-JUL-06:10 9917107.14 6.26 03-JUL-05:10
August 69298672.94 51.03 01-AUG-06:10 10358869.18 6.26 01-AUG-05:10
September 62501483.51 51.03 01-SEP-06:10 9714257.22 6.26 01-SEP-05:10
October 64471239.61 51.03 02-OCT-06:10 10025293.76 6.26 02-OCT-05:10
November 63317962.72 51.03 01-NOV-06:10 9763842.76 6.26 01-NOV-05:10
December 62848487.18 51.03 01-DEC-07:10 9917107.14 6.26 01-DEC-06:10
             
Annual Sum or Average 0.773604E+09     0.119059E+09    
Minimum of Months 58613001.28 51.03   9083168.58 6.26  
Maximum of Months 69308878.93 51.03   10358869.18 6.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 72760249.59 57.60 02-JAN-07:10 0.380621E+09 237.70 02-JAN-06:10
February 66159295.97 57.60 01-FEB-07:10 0.344852E+09 237.70 01-FEB-06:10
March 78232244.29 57.60 01-MAR-07:10 0.393285E+09 237.70 01-MAR-06:10
April 70559931.72 57.60 03-APR-06:10 0.368812E+09 237.70 03-APR-05:10
May 75490486.94 57.60 01-MAY-06:10 0.386953E+09 237.70 01-MAY-05:10
June 75110327.31 57.60 01-JUN-06:10 0.379252E+09 237.70 01-JUN-05:10
July 70940091.35 57.60 03-JUL-06:10 0.376513E+09 237.70 03-JUL-05:10
August 78220724.30 57.60 01-AUG-06:10 0.393285E+09 237.70 01-AUG-05:10
September 70548411.73 57.60 01-SEP-06:10 0.368812E+09 237.70 01-SEP-05:10
October 72771769.58 57.60 02-OCT-06:10 0.380621E+09 237.70 02-OCT-05:10
November 71470010.84 57.60 01-NOV-06:10 0.370694E+09 237.70 01-NOV-05:10
December 70940091.35 57.60 01-DEC-07:10 0.376513E+09 237.70 01-DEC-06:10
             
Annual Sum or Average 0.873204E+09     0.452021E+10    
Minimum of Months 66159295.97 57.60   0.344852E+09 237.70  
Maximum of Months 78232244.29 57.60   0.393285E+09 237.70  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.170532E+09 135.00 02-JAN-07:10 0.475850E+09 297.17 02-JAN-06:10
February 0.155061E+09 135.00 01-FEB-07:10 0.431132E+09 297.17 01-FEB-06:10
March 0.183357E+09 135.00 01-MAR-07:10 0.491683E+09 297.17 01-MAR-06:10
April 0.165375E+09 135.00 03-APR-06:10 0.461086E+09 297.17 03-APR-05:10
May 0.176931E+09 135.00 01-MAY-06:10 0.483766E+09 297.17 01-MAY-05:10
June 0.176040E+09 135.00 01-JUN-06:10 0.474138E+09 297.17 01-JUN-05:10
July 0.166266E+09 135.00 03-JUL-06:10 0.470715E+09 297.17 03-JUL-05:10
August 0.183330E+09 135.00 01-AUG-06:10 0.491683E+09 297.17 01-AUG-05:10
September 0.165348E+09 135.00 01-SEP-06:10 0.461086E+09 297.17 01-SEP-05:10
October 0.170559E+09 135.00 02-OCT-06:10 0.475850E+09 297.17 02-OCT-05:10
November 0.167508E+09 135.00 01-NOV-06:10 0.463440E+09 297.17 01-NOV-05:10
December 0.166266E+09 135.00 01-DEC-07:10 0.470715E+09 297.17 01-DEC-06:10
             
Annual Sum or Average 0.204657E+10     0.565114E+10    
Minimum of Months 0.155061E+09 135.00   0.431132E+09 297.17  
Maximum of Months 0.183357E+09 135.00   0.491683E+09 297.17  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.204638E+09 162.00 02-JAN-07:10 0.571019E+09 356.60 02-JAN-06:10
February 0.186073E+09 162.00 01-FEB-07:10 0.517358E+09 356.60 01-FEB-06:10
March 0.220028E+09 162.00 01-MAR-07:10 0.590019E+09 356.60 01-MAR-06:10
April 0.198450E+09 162.00 03-APR-06:10 0.553303E+09 356.60 03-APR-05:10
May 0.212317E+09 162.00 01-MAY-06:10 0.580519E+09 356.60 01-MAY-05:10
June 0.211248E+09 162.00 01-JUN-06:10 0.568965E+09 356.60 01-JUN-05:10
July 0.199519E+09 162.00 03-JUL-06:10 0.564857E+09 356.60 03-JUL-05:10
August 0.219996E+09 162.00 01-AUG-06:10 0.590019E+09 356.60 01-AUG-05:10
September 0.198417E+09 162.00 01-SEP-06:10 0.553303E+09 356.60 01-SEP-05:10
October 0.204671E+09 162.00 02-OCT-06:10 0.571019E+09 356.60 02-OCT-05:10
November 0.201009E+09 162.00 01-NOV-06:10 0.556128E+09 356.60 01-NOV-05:10
December 0.199519E+09 162.00 01-DEC-07:10 0.564857E+09 356.60 01-DEC-06:10
             
Annual Sum or Average 0.245589E+10     0.678137E+10    
Minimum of Months 0.186073E+09 162.00   0.517358E+09 356.60  
Maximum of Months 0.220028E+09 162.00   0.590019E+09 356.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.700317E+09 554.40 02-JAN-07:10 0.976954E+09 610.11 02-JAN-06:10
February 0.636783E+09 554.40 01-FEB-07:10 0.885145E+09 610.11 01-FEB-06:10
March 0.752985E+09 554.40 01-MAR-07:10 0.100946E+10 610.11 01-MAR-06:10
April 0.679139E+09 554.40 03-APR-06:10 0.946644E+09 610.11 03-APR-05:10
May 0.726596E+09 554.40 01-MAY-06:10 0.993207E+09 610.11 01-MAY-05:10
June 0.722937E+09 554.40 01-JUN-06:10 0.973440E+09 610.11 01-JUN-05:10
July 0.682798E+09 554.40 03-JUL-06:10 0.966411E+09 610.11 03-JUL-05:10
August 0.752874E+09 554.40 01-AUG-06:10 0.100946E+10 610.11 01-AUG-05:10
September 0.679028E+09 554.40 01-SEP-06:10 0.946644E+09 610.11 01-SEP-05:10
October 0.700428E+09 554.40 02-OCT-06:10 0.976954E+09 610.11 02-OCT-05:10
November 0.687899E+09 554.40 01-NOV-06:10 0.951476E+09 610.11 01-NOV-05:10
December 0.682798E+09 554.40 01-DEC-07:10 0.966411E+09 610.11 01-DEC-06:10
             
Annual Sum or Average 0.840458E+10     0.116022E+11    
Minimum of Months 0.636783E+09 554.40   0.885145E+09 610.11  
Maximum of Months 0.752985E+09 554.40   0.100946E+10 610.11  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.483211E+09 382.53 02-JAN-07:10 0.281965E+09 176.09 02-JAN-06:10
February 0.439373E+09 382.53 01-FEB-07:10 0.255467E+09 176.09 01-FEB-06:10
March 0.519551E+09 382.53 01-MAR-07:10 0.291347E+09 176.09 01-MAR-06:10
April 0.468598E+09 382.53 03-APR-06:10 0.273217E+09 176.09 03-APR-05:10
May 0.501343E+09 382.53 01-MAY-06:10 0.286656E+09 176.09 01-MAY-05:10
June 0.498818E+09 382.53 01-JUN-06:10 0.280950E+09 176.09 01-JUN-05:10
July 0.471123E+09 382.53 03-JUL-06:10 0.278922E+09 176.09 03-JUL-05:10
August 0.519475E+09 382.53 01-AUG-06:10 0.291347E+09 176.09 01-AUG-05:10
September 0.468522E+09 382.53 01-SEP-06:10 0.273217E+09 176.09 01-SEP-05:10
October 0.483287E+09 382.53 02-OCT-06:10 0.281965E+09 176.09 02-OCT-05:10
November 0.474642E+09 382.53 01-NOV-06:10 0.274611E+09 176.09 01-NOV-05:10
December 0.471123E+09 382.53 01-DEC-07:10 0.278922E+09 176.09 01-DEC-06:10
             
Annual Sum or Average 0.579907E+10     0.334858E+10    
Minimum of Months 0.439373E+09 382.53   0.255467E+09 176.09  
Maximum of Months 0.519551E+09 382.53   0.291347E+09 176.09  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.145430E+10 1151.28 02-JAN-07:10 0.171665E+10 1072.05 02-JAN-06:10
February 0.132236E+10 1151.28 01-FEB-07:10 0.155533E+10 1072.05 01-FEB-06:10
March 0.156367E+10 1151.28 01-MAR-07:10 0.177377E+10 1072.05 01-MAR-06:10
April 0.141032E+10 1151.28 03-APR-06:10 0.166339E+10 1072.05 03-APR-05:10
May 0.150887E+10 1151.28 01-MAY-06:10 0.174521E+10 1072.05 01-MAY-05:10
June 0.150127E+10 1151.28 01-JUN-06:10 0.171047E+10 1072.05 01-JUN-05:10
July 0.141792E+10 1151.28 03-JUL-06:10 0.169812E+10 1072.05 03-JUL-05:10
August 0.156344E+10 1151.28 01-AUG-06:10 0.177377E+10 1072.05 01-AUG-05:10
September 0.141009E+10 1151.28 01-SEP-06:10 0.166339E+10 1072.05 01-SEP-05:10
October 0.145453E+10 1151.28 02-OCT-06:10 0.171665E+10 1072.05 02-OCT-05:10
November 0.142851E+10 1151.28 01-NOV-06:10 0.167188E+10 1072.05 01-NOV-05:10
December 0.141792E+10 1151.28 01-DEC-07:10 0.169812E+10 1072.05 01-DEC-06:10
             
Annual Sum or Average 0.174532E+11     0.203867E+11    
Minimum of Months 0.132236E+10 1151.28   0.155533E+10 1072.05  
Maximum of Months 0.156367E+10 1151.28   0.177377E+10 1072.05  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.613808E+09 485.92 02-JAN-07:10 0.358171E+09 223.68 02-JAN-06:10
February 0.558123E+09 485.92 01-FEB-07:10 0.324512E+09 223.68 01-FEB-06:10
March 0.659970E+09 485.92 01-MAR-07:10 0.370089E+09 223.68 01-MAR-06:10
April 0.595246E+09 485.92 03-APR-06:10 0.347059E+09 223.68 03-APR-05:10
May 0.636841E+09 485.92 01-MAY-06:10 0.364130E+09 223.68 01-MAY-05:10
June 0.633634E+09 485.92 01-JUN-06:10 0.356883E+09 223.68 01-JUN-05:10
July 0.598454E+09 485.92 03-JUL-06:10 0.354306E+09 223.68 03-JUL-05:10
August 0.659873E+09 485.92 01-AUG-06:10 0.370089E+09 223.68 01-AUG-05:10
September 0.595149E+09 485.92 01-SEP-06:10 0.347059E+09 223.68 01-SEP-05:10
October 0.613906E+09 485.92 02-OCT-06:10 0.358171E+09 223.68 02-OCT-05:10
November 0.602924E+09 485.92 01-NOV-06:10 0.348830E+09 223.68 01-NOV-05:10
December 0.598454E+09 485.92 01-DEC-07:10 0.354306E+09 223.68 01-DEC-06:10
             
Annual Sum or Average 0.736638E+10     0.425361E+10    
Minimum of Months 0.558123E+09 485.92   0.324512E+09 223.68  
Maximum of Months 0.659970E+09 485.92   0.370089E+09 223.68  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.128922E+09 102.06 02-JAN-07:10 80016946.16 49.97 02-JAN-06:10
February 0.117226E+09 102.06 01-FEB-07:10 72497368.03 49.97 01-FEB-06:10
March 0.138618E+09 102.06 01-MAR-07:10 82679380.52 49.97 01-MAR-06:10
April 0.125023E+09 102.06 03-APR-06:10 77534406.01 49.97 03-APR-05:10
May 0.133760E+09 102.06 01-MAY-06:10 81348163.34 49.97 01-MAY-05:10
June 0.133086E+09 102.06 01-JUN-06:10 79729115.42 49.97 01-JUN-05:10
July 0.125697E+09 102.06 03-JUL-06:10 79153453.93 49.97 03-JUL-05:10
August 0.138597E+09 102.06 01-AUG-06:10 82679380.52 49.97 01-AUG-05:10
September 0.125003E+09 102.06 01-SEP-06:10 77534406.01 49.97 01-SEP-05:10
October 0.128942E+09 102.06 02-OCT-06:10 80016946.16 49.97 02-OCT-05:10
November 0.126636E+09 102.06 01-NOV-06:10 77930173.28 49.97 01-NOV-05:10
December 0.125697E+09 102.06 01-DEC-07:10 79153453.93 49.97 01-DEC-06:10
             
Annual Sum or Average 0.154721E+10     0.950273E+09    
Minimum of Months 0.117226E+09 102.06   72497368.03 49.97  
Maximum of Months 0.138618E+09 102.06   82679380.52 49.97  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.405184E+09 320.76 02-JAN-07:10 0.565238E+09 352.99 02-JAN-06:10
February 0.368425E+09 320.76 01-FEB-07:10 0.512120E+09 352.99 01-FEB-06:10
March 0.435656E+09 320.76 01-MAR-07:10 0.584045E+09 352.99 01-MAR-06:10
April 0.392931E+09 320.76 03-APR-06:10 0.547701E+09 352.99 03-APR-05:10
May 0.420388E+09 320.76 01-MAY-06:10 0.574641E+09 352.99 01-MAY-05:10
June 0.418271E+09 320.76 01-JUN-06:10 0.563204E+09 352.99 01-JUN-05:10
July 0.395048E+09 320.76 03-JUL-06:10 0.559138E+09 352.99 03-JUL-05:10
August 0.435592E+09 320.76 01-AUG-06:10 0.584045E+09 352.99 01-AUG-05:10
September 0.392866E+09 320.76 01-SEP-06:10 0.547701E+09 352.99 01-SEP-05:10
October 0.405248E+09 320.76 02-OCT-06:10 0.565238E+09 352.99 02-OCT-05:10
November 0.397999E+09 320.76 01-NOV-06:10 0.550497E+09 352.99 01-NOV-05:10
December 0.395048E+09 320.76 01-DEC-07:10 0.559138E+09 352.99 01-DEC-06:10
             
Annual Sum or Average 0.486265E+10     0.671270E+10    
Minimum of Months 0.368425E+09 320.76   0.512120E+09 352.99  
Maximum of Months 0.435656E+09 320.76   0.584045E+09 352.99  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.427694E+09 338.58 02-JAN-07:10 0.596640E+09 372.60 02-JAN-06:10
February 0.388893E+09 338.58 01-FEB-07:10 0.540571E+09 372.60 01-FEB-06:10
March 0.459859E+09 338.58 01-MAR-07:10 0.616492E+09 372.60 01-MAR-06:10
April 0.414760E+09 338.58 03-APR-06:10 0.578129E+09 372.60 03-APR-05:10
May 0.443743E+09 338.58 01-MAY-06:10 0.606566E+09 372.60 01-MAY-05:10
June 0.441508E+09 338.58 01-JUN-06:10 0.594494E+09 372.60 01-JUN-05:10
July 0.416995E+09 338.58 03-JUL-06:10 0.590201E+09 372.60 03-JUL-05:10
August 0.459791E+09 338.58 01-AUG-06:10 0.616492E+09 372.60 01-AUG-05:10
September 0.414692E+09 338.58 01-SEP-06:10 0.578129E+09 372.60 01-SEP-05:10
October 0.427762E+09 338.58 02-OCT-06:10 0.596640E+09 372.60 02-OCT-05:10
November 0.420110E+09 338.58 01-NOV-06:10 0.581080E+09 372.60 01-NOV-05:10
December 0.416995E+09 338.58 01-DEC-07:10 0.590201E+09 372.60 01-DEC-06:10
             
Annual Sum or Average 0.513280E+10     0.708563E+10    
Minimum of Months 0.388893E+09 338.58   0.540571E+09 372.60  
Maximum of Months 0.459859E+09 338.58   0.616492E+09 372.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 57298696.55 45.36 02-JAN-07:10 8911442.72 5.57 02-JAN-06:10
February 52100445.58 45.36 01-FEB-07:10 8073991.50 5.57 01-FEB-06:10
March 61607892.38 45.36 01-MAR-07:10 9207956.55 5.57 01-MAR-06:10
April 55565946.23 45.36 03-APR-06:10 8634963.61 5.57 03-APR-05:10
May 59448758.47 45.36 01-MAY-06:10 9059699.64 5.57 01-MAY-05:10
June 59149382.76 45.36 01-JUN-06:10 8879387.17 5.57 01-JUN-05:10
July 55865321.94 45.36 03-JUL-06:10 8815276.07 5.57 03-JUL-05:10
August 61598820.39 45.36 01-AUG-06:10 9207956.55 5.57 01-AUG-05:10
September 55556874.24 45.36 01-SEP-06:10 8634963.61 5.57 01-SEP-05:10
October 57307768.54 45.36 02-OCT-06:10 8911442.72 5.57 02-OCT-05:10
November 56282633.53 45.36 01-NOV-06:10 8679039.99 5.57 01-NOV-05:10
December 55865321.94 45.36 01-DEC-07:10 8815276.07 5.57 01-DEC-06:10
             
Annual Sum or Average 0.687648E+09     0.105831E+09    
Minimum of Months 52100445.58 45.36   8073991.50 5.57  
Maximum of Months 61607892.38 45.36   9207956.55 5.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.122783E+09 97.20 02-JAN-07:10 19095812.75 11.93 02-JAN-06:10
February 0.111644E+09 97.20 01-FEB-07:10 17301287.18 11.93 01-FEB-06:10
March 0.132017E+09 97.20 01-MAR-07:10 19731195.01 11.93 01-MAR-06:10
April 0.119070E+09 97.20 03-APR-06:10 18503361.72 11.93 03-APR-05:10
May 0.127390E+09 97.20 01-MAY-06:10 19413503.88 11.93 01-MAY-05:10
June 0.126749E+09 97.20 01-JUN-06:10 19027122.77 11.93 01-JUN-05:10
July 0.119711E+09 97.20 03-JUL-06:10 18889742.83 11.93 03-JUL-05:10
August 0.131997E+09 97.20 01-AUG-06:10 19731195.01 11.93 01-AUG-05:10
September 0.119050E+09 97.20 01-SEP-06:10 18503361.72 11.93 01-SEP-05:10
October 0.122802E+09 97.20 02-OCT-06:10 19095812.75 11.93 02-OCT-05:10
November 0.120606E+09 97.20 01-NOV-06:10 18597810.44 11.93 01-NOV-05:10
December 0.119711E+09 97.20 01-DEC-07:10 18889742.83 11.93 01-DEC-06:10
             
Annual Sum or Average 0.147353E+10     0.226780E+09    
Minimum of Months 0.111644E+09 97.20   17301287.18 11.93  
Maximum of Months 0.132017E+09 97.20   19731195.01 11.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147340E+09 116.64 02-JAN-07:10 22915070.46 14.31 02-JAN-06:10
February 0.133973E+09 116.64 01-FEB-07:10 20761630.83 14.31 01-FEB-06:10
March 0.158420E+09 116.64 01-MAR-07:10 23677532.33 14.31 01-MAR-06:10
April 0.142884E+09 116.64 03-APR-06:10 22204126.27 14.31 03-APR-05:10
May 0.152868E+09 116.64 01-MAY-06:10 23296301.39 14.31 01-MAY-05:10
June 0.152098E+09 116.64 01-JUN-06:10 22832642.15 14.31 01-JUN-05:10
July 0.143654E+09 116.64 03-JUL-06:10 22667785.52 14.31 03-JUL-05:10
August 0.158397E+09 116.64 01-AUG-06:10 23677532.33 14.31 01-AUG-05:10
September 0.142861E+09 116.64 01-SEP-06:10 22204126.27 14.31 01-SEP-05:10
October 0.147363E+09 116.64 02-OCT-06:10 22915070.46 14.31 02-OCT-05:10
November 0.144727E+09 116.64 01-NOV-06:10 22317465.20 14.31 01-NOV-05:10
December 0.143654E+09 116.64 01-DEC-07:10 22667785.52 14.31 01-DEC-06:10
             
Annual Sum or Average 0.176824E+10     0.272137E+09    
Minimum of Months 0.133973E+09 116.64   20761630.83 14.31  
Maximum of Months 0.158420E+09 116.64   23677532.33 14.31  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.128922E+09 102.06 02-JAN-07:10 20050587.52 12.52 02-JAN-06:10
February 0.117226E+09 102.06 01-FEB-07:10 18166337.17 12.52 01-FEB-06:10
March 0.138618E+09 102.06 01-MAR-07:10 20717738.37 12.52 01-MAR-06:10
April 0.125023E+09 102.06 03-APR-06:10 19428514.44 12.52 03-APR-05:10
May 0.133760E+09 102.06 01-MAY-06:10 20384162.95 12.52 01-MAY-05:10
June 0.133086E+09 102.06 01-JUN-06:10 19978463.11 12.52 01-JUN-05:10
July 0.125697E+09 102.06 03-JUL-06:10 19834214.28 12.52 03-JUL-05:10
August 0.138597E+09 102.06 01-AUG-06:10 20717738.37 12.52 01-AUG-05:10
September 0.125003E+09 102.06 01-SEP-06:10 19428514.44 12.52 01-SEP-05:10
October 0.128942E+09 102.06 02-OCT-06:10 20050587.52 12.52 02-OCT-05:10
November 0.126636E+09 102.06 01-NOV-06:10 19527685.51 12.52 01-NOV-05:10
December 0.125697E+09 102.06 01-DEC-07:10 19834214.28 12.52 01-DEC-06:10
             
Annual Sum or Average 0.154721E+10     0.238119E+09    
Minimum of Months 0.117226E+09 102.06   18166337.17 12.52  
Maximum of Months 0.138618E+09 102.06   20717738.37 12.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.211346E+10 1673.10 02-JAN-07:10 0.243541E+10 1520.91 02-JAN-06:10
February 0.192172E+10 1673.10 01-FEB-07:10 0.220654E+10 1520.91 01-FEB-06:10
March 0.227240E+10 1673.10 01-MAR-07:10 0.251644E+10 1520.91 01-MAR-06:10
April 0.204955E+10 1673.10 03-APR-06:10 0.235985E+10 1520.91 03-APR-05:10
May 0.219276E+10 1673.10 01-MAY-06:10 0.247592E+10 1520.91 01-MAY-05:10
June 0.218172E+10 1673.10 01-JUN-06:10 0.242665E+10 1520.91 01-JUN-05:10
July 0.206059E+10 1673.10 03-JUL-06:10 0.240913E+10 1520.91 03-JUL-05:10
August 0.227207E+10 1673.10 01-AUG-06:10 0.251644E+10 1520.91 01-AUG-05:10
September 0.204921E+10 1673.10 01-SEP-06:10 0.235985E+10 1520.91 01-SEP-05:10
October 0.211379E+10 1673.10 02-OCT-06:10 0.243541E+10 1520.91 02-OCT-05:10
November 0.207598E+10 1673.10 01-NOV-06:10 0.237189E+10 1520.91 01-NOV-05:10
December 0.206059E+10 1673.10 01-DEC-07:10 0.240913E+10 1520.91 01-DEC-06:10
             
Annual Sum or Average 0.253638E+11     0.289226E+11    
Minimum of Months 0.192172E+10 1673.10   0.220654E+10 1520.91  
Maximum of Months 0.227240E+10 1673.10   0.251644E+10 1520.91  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.907653E+09 718.53 02-JAN-07:10 0.529636E+09 330.76 02-JAN-06:10
February 0.825309E+09 718.53 01-FEB-07:10 0.479864E+09 330.76 01-FEB-06:10
March 0.975914E+09 718.53 01-MAR-07:10 0.547259E+09 330.76 01-MAR-06:10
April 0.880205E+09 718.53 03-APR-06:10 0.513204E+09 330.76 03-APR-05:10
May 0.941711E+09 718.53 01-MAY-06:10 0.538448E+09 330.76 01-MAY-05:10
June 0.936969E+09 718.53 01-JUN-06:10 0.527731E+09 330.76 01-JUN-05:10
July 0.884947E+09 718.53 03-JUL-06:10 0.523921E+09 330.76 03-JUL-05:10
August 0.975770E+09 718.53 01-AUG-06:10 0.547259E+09 330.76 01-AUG-05:10
September 0.880061E+09 718.53 01-SEP-06:10 0.513204E+09 330.76 01-SEP-05:10
October 0.907797E+09 718.53 02-OCT-06:10 0.529636E+09 330.76 02-OCT-05:10
November 0.891558E+09 718.53 01-NOV-06:10 0.515824E+09 330.76 01-NOV-05:10
December 0.884947E+09 718.53 01-DEC-07:10 0.523921E+09 330.76 01-DEC-06:10
             
Annual Sum or Average 0.108928E+11     0.628991E+10    
Minimum of Months 0.825309E+09 718.53   0.479864E+09 330.76  
Maximum of Months 0.975914E+09 718.53   0.547259E+09 330.76  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 55252314.53 43.74 02-JAN-07:10 34293067.55 21.42 02-JAN-06:10
February 50239715.38 43.74 01-FEB-07:10 31070382.70 21.42 01-FEB-06:10
March 59407610.51 43.74 01-MAR-07:10 35434113.87 21.42 01-MAR-06:10
April 53581448.15 43.74 03-APR-06:10 33229118.96 21.42 03-APR-05:10
May 57325588.52 43.74 01-MAY-06:10 34863590.71 21.42 01-MAY-05:10
June 57036904.80 43.74 01-JUN-06:10 34169711.20 21.42 01-JUN-05:10
July 53870131.87 43.74 03-JUL-06:10 33922998.48 21.42 03-JUL-05:10
August 59398862.52 43.74 01-AUG-06:10 35434113.87 21.42 01-AUG-05:10
September 53572700.16 43.74 01-SEP-06:10 33229118.96 21.42 01-SEP-05:10
October 55261062.52 43.74 02-OCT-06:10 34293067.55 21.42 02-OCT-05:10
November 54272539.48 43.74 01-NOV-06:10 33398733.96 21.42 01-NOV-05:10
December 53870131.87 43.74 01-DEC-07:10 33922998.48 21.42 01-DEC-06:10
             
Annual Sum or Average 0.663089E+09     0.407261E+09    
Minimum of Months 50239715.38 43.74   31070382.70 21.42  
Maximum of Months 59407610.51 43.74   35434113.87 21.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 X-RAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.153479E+10 1215.00 02-JAN-07:10 0.142742E+11 8914.22 02-JAN-06:10
February 0.139555E+10 1215.00 01-FEB-07:10 0.129327E+11 8914.22 01-FEB-06:10
March 0.165021E+10 1215.00 01-MAR-07:10 0.147491E+11 8914.22 01-MAR-06:10
April 0.148837E+10 1215.00 03-APR-06:10 0.138313E+11 8914.22 03-APR-05:10
May 0.159238E+10 1215.00 01-MAY-06:10 0.145116E+11 8914.22 01-MAY-05:10
June 0.158436E+10 1215.00 01-JUN-06:10 0.142228E+11 8914.22 01-JUN-05:10
July 0.149639E+10 1215.00 03-JUL-06:10 0.141201E+11 8914.22 03-JUL-05:10
August 0.164997E+10 1215.00 01-AUG-06:10 0.147491E+11 8914.22 01-AUG-05:10
September 0.148813E+10 1215.00 01-SEP-06:10 0.138313E+11 8914.22 01-SEP-05:10
October 0.153503E+10 1215.00 02-OCT-06:10 0.142742E+11 8914.22 02-OCT-05:10
November 0.150757E+10 1215.00 01-NOV-06:10 0.139019E+11 8914.22 01-NOV-05:10
December 0.149639E+10 1215.00 01-DEC-07:10 0.141201E+11 8914.22 01-DEC-06:10
             
Annual Sum or Average 0.184191E+11     0.169518E+12    
Minimum of Months 0.139555E+10 1215.00   0.129327E+11 8914.22  
Maximum of Months 0.165021E+10 1215.00   0.147491E+11 8914.22  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 52523805.17 41.58 02-JAN-07:10 73271509.94 45.76 02-JAN-06:10
February 47758741.78 41.58 01-FEB-07:10 66385832.97 45.76 01-FEB-06:10
March 56473901.35 41.58 01-MAR-07:10 75709500.82 45.76 01-MAR-06:10
April 50935450.71 41.58 03-APR-06:10 70998248.16 45.76 03-APR-05:10
May 54494695.26 41.58 01-MAY-06:10 74490505.38 45.76 01-MAY-05:10
June 54220267.53 41.58 01-JUN-06:10 73007943.35 45.76 01-JUN-05:10
July 51209878.44 41.58 03-JUL-06:10 72480810.19 45.76 03-JUL-05:10
August 56465585.36 41.58 01-AUG-06:10 75709500.82 45.76 01-AUG-05:10
September 50927134.72 41.58 01-SEP-06:10 70998248.16 45.76 01-SEP-05:10
October 52532121.16 41.58 02-OCT-06:10 73271509.94 45.76 02-OCT-05:10
November 51592414.07 41.58 01-NOV-06:10 71360652.21 45.76 01-NOV-05:10
December 51209878.44 41.58 01-DEC-07:10 72480810.19 45.76 01-DEC-06:10
             
Annual Sum or Average 0.630344E+09     0.870165E+09    
Minimum of Months 47758741.78 41.58   66385832.97 45.76  
Maximum of Months 56473901.35 41.58   75709500.82 45.76  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.402676E+09 318.77 02-JAN-07:10 0.234971E+09 146.74 02-JAN-06:10
February 0.366144E+09 318.77 01-FEB-07:10 0.212889E+09 146.74 01-FEB-06:10
March 0.432959E+09 318.77 01-MAR-07:10 0.242789E+09 146.74 01-MAR-06:10
April 0.390499E+09 318.77 03-APR-06:10 0.227681E+09 146.74 03-APR-05:10
May 0.417786E+09 318.77 01-MAY-06:10 0.238880E+09 146.74 01-MAY-05:10
June 0.415682E+09 318.77 01-JUN-06:10 0.234125E+09 146.74 01-JUN-05:10
July 0.392603E+09 318.77 03-JUL-06:10 0.232435E+09 146.74 03-JUL-05:10
August 0.432896E+09 318.77 01-AUG-06:10 0.242789E+09 146.74 01-AUG-05:10
September 0.390435E+09 318.77 01-SEP-06:10 0.227681E+09 146.74 01-SEP-05:10
October 0.402740E+09 318.77 02-OCT-06:10 0.234971E+09 146.74 02-OCT-05:10
November 0.395535E+09 318.77 01-NOV-06:10 0.228843E+09 146.74 01-NOV-05:10
December 0.392603E+09 318.77 01-DEC-07:10 0.232435E+09 146.74 01-DEC-06:10
             
Annual Sum or Average 0.483256E+10     0.279049E+10    
Minimum of Months 0.366144E+09 318.77   0.212889E+09 146.74  
Maximum of Months 0.432959E+09 318.77   0.242789E+09 146.74  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135061E+09 106.92 02-JAN-07:10 0.188413E+09 117.66 02-JAN-06:10
February 0.122808E+09 106.92 01-FEB-07:10 0.170707E+09 117.66 01-FEB-06:10
March 0.145219E+09 106.92 01-MAR-07:10 0.194682E+09 117.66 01-MAR-06:10
April 0.130977E+09 106.92 03-APR-06:10 0.182567E+09 117.66 03-APR-05:10
May 0.140129E+09 106.92 01-MAY-06:10 0.191547E+09 117.66 01-MAY-05:10
June 0.139424E+09 106.92 01-JUN-06:10 0.187735E+09 117.66 01-JUN-05:10
July 0.131683E+09 106.92 03-JUL-06:10 0.186379E+09 117.66 03-JUL-05:10
August 0.145197E+09 106.92 01-AUG-06:10 0.194682E+09 117.66 01-AUG-05:10
September 0.130955E+09 106.92 01-SEP-06:10 0.182567E+09 117.66 01-SEP-05:10
October 0.135083E+09 106.92 02-OCT-06:10 0.188413E+09 117.66 02-OCT-05:10
November 0.132666E+09 106.92 01-NOV-06:10 0.183499E+09 117.66 01-NOV-05:10
December 0.131683E+09 106.92 01-DEC-07:10 0.186379E+09 117.66 01-DEC-06:10
             
Annual Sum or Average 0.162088E+10     0.223757E+10    
Minimum of Months 0.122808E+09 106.92   0.170707E+09 117.66  
Maximum of Months 0.145219E+09 106.92   0.194682E+09 117.66  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 64461033.62 51.03 02-JAN-07:10 10025293.76 6.26 02-JAN-06:10
February 58613001.28 51.03 01-FEB-07:10 9083168.58 6.26 01-FEB-06:10
March 69308878.93 51.03 01-MAR-07:10 10358869.18 6.26 01-MAR-06:10
April 62511689.50 51.03 03-APR-06:10 9714257.22 6.26 03-APR-05:10
May 66879853.28 51.03 01-MAY-06:10 10192081.47 6.26 01-MAY-05:10
June 66543055.60 51.03 01-JUN-06:10 9989231.55 6.26 01-JUN-05:10
July 62848487.18 51.03 03-JUL-06:10 9917107.14 6.26 03-JUL-05:10
August 69298672.94 51.03 01-AUG-06:10 10358869.18 6.26 01-AUG-05:10
September 62501483.51 51.03 01-SEP-06:10 9714257.22 6.26 01-SEP-05:10
October 64471239.61 51.03 02-OCT-06:10 10025293.76 6.26 02-OCT-05:10
November 63317962.72 51.03 01-NOV-06:10 9763842.76 6.26 01-NOV-05:10
December 62848487.18 51.03 01-DEC-07:10 9917107.14 6.26 01-DEC-06:10
             
Annual Sum or Average 0.773604E+09     0.119059E+09    
Minimum of Months 58613001.28 51.03   9083168.58 6.26  
Maximum of Months 69308878.93 51.03   10358869.18 6.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 LOCKER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.109140E+09 86.40 02-JAN-07:10 0.570931E+09 356.55 02-JAN-06:10
February 99238943.96 86.40 01-FEB-07:10 0.517278E+09 356.55 01-FEB-06:10
March 0.117348E+09 86.40 01-MAR-07:10 0.589928E+09 356.55 01-MAR-06:10
April 0.105840E+09 86.40 03-APR-06:10 0.553218E+09 356.55 03-APR-05:10
May 0.113236E+09 86.40 01-MAY-06:10 0.580429E+09 356.55 01-MAY-05:10
June 0.112665E+09 86.40 01-JUN-06:10 0.568877E+09 356.55 01-JUN-05:10
July 0.106410E+09 86.40 03-JUL-06:10 0.564770E+09 356.55 03-JUL-05:10
August 0.117331E+09 86.40 01-AUG-06:10 0.589928E+09 356.55 01-AUG-05:10
September 0.105823E+09 86.40 01-SEP-06:10 0.553218E+09 356.55 01-SEP-05:10
October 0.109158E+09 86.40 02-OCT-06:10 0.570931E+09 356.55 02-OCT-05:10
November 0.107205E+09 86.40 01-NOV-06:10 0.556042E+09 356.55 01-NOV-05:10
December 0.106410E+09 86.40 01-DEC-07:10 0.564770E+09 356.55 01-DEC-06:10
             
Annual Sum or Average 0.130981E+10     0.678032E+10    
Minimum of Months 99238943.96 86.40   0.517278E+09 356.55  
Maximum of Months 0.117348E+09 86.40   0.589928E+09 356.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.690313E+09 546.48 02-JAN-07:10 0.361114E+10 2255.16 02-JAN-06:10
February 0.627686E+09 546.48 01-FEB-07:10 0.327178E+10 2255.16 01-FEB-06:10
March 0.742228E+09 546.48 01-MAR-07:10 0.373129E+10 2255.16 01-MAR-06:10
April 0.669437E+09 546.48 03-APR-06:10 0.349910E+10 2255.16 03-APR-05:10
May 0.716216E+09 546.48 01-MAY-06:10 0.367122E+10 2255.16 01-MAY-05:10
June 0.712609E+09 546.48 01-JUN-06:10 0.359815E+10 2255.16 01-JUN-05:10
July 0.673044E+09 546.48 03-JUL-06:10 0.357217E+10 2255.16 03-JUL-05:10
August 0.742119E+09 546.48 01-AUG-06:10 0.373129E+10 2255.16 01-AUG-05:10
September 0.669328E+09 546.48 01-SEP-06:10 0.349910E+10 2255.16 01-SEP-05:10
October 0.690422E+09 546.48 02-OCT-06:10 0.361114E+10 2255.16 02-OCT-05:10
November 0.678072E+09 546.48 01-NOV-06:10 0.351696E+10 2255.16 01-NOV-05:10
December 0.673044E+09 546.48 01-DEC-07:10 0.357217E+10 2255.16 01-DEC-06:10
             
Annual Sum or Average 0.828452E+10     0.428855E+11    
Minimum of Months 0.627686E+09 546.48   0.327178E+10 2255.16  
Maximum of Months 0.742228E+09 546.48   0.373129E+10 2255.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196453E+09 155.52 02-JAN-07:10 0.121931E+09 76.15 02-JAN-06:10
February 0.178630E+09 155.52 01-FEB-07:10 0.110472E+09 76.15 01-FEB-06:10
March 0.211227E+09 155.52 01-MAR-07:10 0.125988E+09 76.15 01-MAR-06:10
April 0.190512E+09 155.52 03-APR-06:10 0.118148E+09 76.15 03-APR-05:10
May 0.203824E+09 155.52 01-MAY-06:10 0.123959E+09 76.15 01-MAY-05:10
June 0.202798E+09 155.52 01-JUN-06:10 0.121492E+09 76.15 01-JUN-05:10
July 0.191538E+09 155.52 03-JUL-06:10 0.120615E+09 76.15 03-JUL-05:10
August 0.211196E+09 155.52 01-AUG-06:10 0.125988E+09 76.15 01-AUG-05:10
September 0.190481E+09 155.52 01-SEP-06:10 0.118148E+09 76.15 01-SEP-05:10
October 0.196484E+09 155.52 02-OCT-06:10 0.121931E+09 76.15 02-OCT-05:10
November 0.192969E+09 155.52 01-NOV-06:10 0.118751E+09 76.15 01-NOV-05:10
December 0.191538E+09 155.52 01-DEC-07:10 0.120615E+09 76.15 01-DEC-06:10
             
Annual Sum or Average 0.235765E+10     0.144804E+10    
Minimum of Months 0.178630E+09 155.52   0.110472E+09 76.15  
Maximum of Months 0.211227E+09 155.52   0.125988E+09 76.15  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.596861E+09 472.50 02-JAN-07:10 0.277553E+10 1733.32 02-JAN-06:10
February 0.542713E+09 472.50 01-FEB-07:10 0.251470E+10 1733.32 01-FEB-06:10
March 0.641749E+09 472.50 01-MAR-07:10 0.286788E+10 1733.32 01-MAR-06:10
April 0.578812E+09 472.50 03-APR-06:10 0.268942E+10 1733.32 03-APR-05:10
May 0.619258E+09 472.50 01-MAY-06:10 0.282171E+10 1733.32 01-MAY-05:10
June 0.616139E+09 472.50 01-JUN-06:10 0.276555E+10 1733.32 01-JUN-05:10
July 0.581930E+09 472.50 03-JUL-06:10 0.274558E+10 1733.32 03-JUL-05:10
August 0.641654E+09 472.50 01-AUG-06:10 0.286788E+10 1733.32 01-AUG-05:10
September 0.578717E+09 472.50 01-SEP-06:10 0.268942E+10 1733.32 01-SEP-05:10
October 0.596956E+09 472.50 02-OCT-06:10 0.277553E+10 1733.32 02-OCT-05:10
November 0.586277E+09 472.50 01-NOV-06:10 0.270315E+10 1733.32 01-NOV-05:10
December 0.581930E+09 472.50 01-DEC-07:10 0.274558E+10 1733.32 01-DEC-06:10
             
Annual Sum or Average 0.716300E+10     0.329619E+11    
Minimum of Months 0.542713E+09 472.50   0.251470E+10 1733.32  
Maximum of Months 0.641749E+09 472.50   0.286788E+10 1733.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.326494E+09 258.47 02-JAN-07:10 0.190517E+09 118.98 02-JAN-06:10
February 0.296874E+09 258.47 01-FEB-07:10 0.172613E+09 118.98 01-FEB-06:10
March 0.351048E+09 258.47 01-MAR-07:10 0.196856E+09 118.98 01-MAR-06:10
April 0.316620E+09 258.47 03-APR-06:10 0.184606E+09 118.98 03-APR-05:10
May 0.338745E+09 258.47 01-MAY-06:10 0.193686E+09 118.98 01-MAY-05:10
June 0.337039E+09 258.47 01-JUN-06:10 0.189831E+09 118.98 01-JUN-05:10
July 0.318326E+09 258.47 03-JUL-06:10 0.188461E+09 118.98 03-JUL-05:10
August 0.350996E+09 258.47 01-AUG-06:10 0.196856E+09 118.98 01-AUG-05:10
September 0.316569E+09 258.47 01-SEP-06:10 0.184606E+09 118.98 01-SEP-05:10
October 0.326546E+09 258.47 02-OCT-06:10 0.190517E+09 118.98 02-OCT-05:10
November 0.320704E+09 258.47 01-NOV-06:10 0.185548E+09 118.98 01-NOV-05:10
December 0.318326E+09 258.47 01-DEC-07:10 0.188461E+09 118.98 01-DEC-06:10
             
Annual Sum or Average 0.391829E+10     0.226256E+10    
Minimum of Months 0.296874E+09 258.47   0.172613E+09 118.98  
Maximum of Months 0.351048E+09 258.47   0.196856E+09 118.98  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.379672E+10 3005.64 02-JAN-07:10 0.529649E+10 3307.66 02-JAN-06:10
February 0.345227E+10 3005.64 01-FEB-07:10 0.479875E+10 3307.66 01-FEB-06:10
March 0.408226E+10 3005.64 01-MAR-07:10 0.547272E+10 3307.66 01-MAR-06:10
April 0.368191E+10 3005.64 03-APR-06:10 0.513216E+10 3307.66 03-APR-05:10
May 0.393919E+10 3005.64 01-MAY-06:10 0.538460E+10 3307.66 01-MAY-05:10
June 0.391935E+10 3005.64 01-JUN-06:10 0.527743E+10 3307.66 01-JUN-05:10
July 0.370174E+10 3005.64 03-JUL-06:10 0.523933E+10 3307.66 03-JUL-05:10
August 0.408166E+10 3005.64 01-AUG-06:10 0.547272E+10 3307.66 01-AUG-05:10
September 0.368130E+10 3005.64 01-SEP-06:10 0.513216E+10 3307.66 01-SEP-05:10
October 0.379732E+10 3005.64 02-OCT-06:10 0.529649E+10 3307.66 02-OCT-05:10
November 0.372939E+10 3005.64 01-NOV-06:10 0.515836E+10 3307.66 01-NOV-05:10
December 0.370174E+10 3005.64 01-DEC-07:10 0.523933E+10 3307.66 01-DEC-06:10
             
Annual Sum or Average 0.455649E+11     0.629005E+11    
Minimum of Months 0.345227E+10 3005.64   0.479875E+10 3307.66  
Maximum of Months 0.408226E+10 3005.64   0.547272E+10 3307.66  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.907653E+09 718.53 02-JAN-07:10 0.529636E+09 330.76 02-JAN-06:10
February 0.825309E+09 718.53 01-FEB-07:10 0.479864E+09 330.76 01-FEB-06:10
March 0.975914E+09 718.53 01-MAR-07:10 0.547259E+09 330.76 01-MAR-06:10
April 0.880205E+09 718.53 03-APR-06:10 0.513204E+09 330.76 03-APR-05:10
May 0.941711E+09 718.53 01-MAY-06:10 0.538448E+09 330.76 01-MAY-05:10
June 0.936969E+09 718.53 01-JUN-06:10 0.527731E+09 330.76 01-JUN-05:10
July 0.884947E+09 718.53 03-JUL-06:10 0.523921E+09 330.76 03-JUL-05:10
August 0.975770E+09 718.53 01-AUG-06:10 0.547259E+09 330.76 01-AUG-05:10
September 0.880061E+09 718.53 01-SEP-06:10 0.513204E+09 330.76 01-SEP-05:10
October 0.907797E+09 718.53 02-OCT-06:10 0.529636E+09 330.76 02-OCT-05:10
November 0.891558E+09 718.53 01-NOV-06:10 0.515824E+09 330.76 01-NOV-05:10
December 0.884947E+09 718.53 01-DEC-07:10 0.523921E+09 330.76 01-DEC-06:10
             
Annual Sum or Average 0.108928E+11     0.628991E+10    
Minimum of Months 0.825309E+09 718.53   0.479864E+09 330.76  
Maximum of Months 0.975914E+09 718.53   0.547259E+09 330.76  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 55252314.53 43.74 02-JAN-07:10 34293067.55 21.42 02-JAN-06:10
February 50239715.38 43.74 01-FEB-07:10 31070382.70 21.42 01-FEB-06:10
March 59407610.51 43.74 01-MAR-07:10 35434113.87 21.42 01-MAR-06:10
April 53581448.15 43.74 03-APR-06:10 33229118.96 21.42 03-APR-05:10
May 57325588.52 43.74 01-MAY-06:10 34863590.71 21.42 01-MAY-05:10
June 57036904.80 43.74 01-JUN-06:10 34169711.20 21.42 01-JUN-05:10
July 53870131.87 43.74 03-JUL-06:10 33922998.48 21.42 03-JUL-05:10
August 59398862.52 43.74 01-AUG-06:10 35434113.87 21.42 01-AUG-05:10
September 53572700.16 43.74 01-SEP-06:10 33229118.96 21.42 01-SEP-05:10
October 55261062.52 43.74 02-OCT-06:10 34293067.55 21.42 02-OCT-05:10
November 54272539.48 43.74 01-NOV-06:10 33398733.96 21.42 01-NOV-05:10
December 53870131.87 43.74 01-DEC-07:10 33922998.48 21.42 01-DEC-06:10
             
Annual Sum or Average 0.663089E+09     0.407261E+09    
Minimum of Months 50239715.38 43.74   31070382.70 21.42  
Maximum of Months 59407610.51 43.74   35434113.87 21.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133015E+10 1053.00 02-JAN-07:10 0.309350E+10 1931.89 02-JAN-06:10
February 0.120947E+10 1053.00 01-FEB-07:10 0.280279E+10 1931.89 01-FEB-06:10
March 0.143018E+10 1053.00 01-MAR-07:10 0.319643E+10 1931.89 01-MAR-06:10
April 0.128992E+10 1053.00 03-APR-06:10 0.299752E+10 1931.89 03-APR-05:10
May 0.138006E+10 1053.00 01-MAY-06:10 0.314497E+10 1931.89 01-MAY-05:10
June 0.137311E+10 1053.00 01-JUN-06:10 0.308237E+10 1931.89 01-JUN-05:10
July 0.129687E+10 1053.00 03-JUL-06:10 0.306012E+10 1931.89 03-JUL-05:10
August 0.142997E+10 1053.00 01-AUG-06:10 0.319643E+10 1931.89 01-AUG-05:10
September 0.128971E+10 1053.00 01-SEP-06:10 0.299752E+10 1931.89 01-SEP-05:10
October 0.133036E+10 1053.00 02-OCT-06:10 0.309350E+10 1931.89 02-OCT-05:10
November 0.130656E+10 1053.00 01-NOV-06:10 0.301283E+10 1931.89 01-NOV-05:10
December 0.129687E+10 1053.00 01-DEC-07:10 0.306012E+10 1931.89 01-DEC-06:10
             
Annual Sum or Average 0.159633E+11     0.367381E+11    
Minimum of Months 0.120947E+10 1053.00   0.280279E+10 1931.89  
Maximum of Months 0.143018E+10 1053.00   0.319643E+10 1931.89  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.605729E+09 479.52 02-JAN-07:10 0.140873E+10 879.75 02-JAN-06:10
February 0.550776E+09 479.52 01-FEB-07:10 0.127635E+10 879.75 01-FEB-06:10
March 0.651283E+09 479.52 01-MAR-07:10 0.145561E+10 879.75 01-MAR-06:10
April 0.587411E+09 479.52 03-APR-06:10 0.136503E+10 879.75 03-APR-05:10
May 0.628458E+09 479.52 01-MAY-06:10 0.143217E+10 879.75 01-MAY-05:10
June 0.625293E+09 479.52 01-JUN-06:10 0.140367E+10 879.75 01-JUN-05:10
July 0.590576E+09 479.52 03-JUL-06:10 0.139353E+10 879.75 03-JUL-05:10
August 0.651188E+09 479.52 01-AUG-06:10 0.145561E+10 879.75 01-AUG-05:10
September 0.587316E+09 479.52 01-SEP-06:10 0.136503E+10 879.75 01-SEP-05:10
October 0.605825E+09 479.52 02-OCT-06:10 0.140873E+10 879.75 02-OCT-05:10
November 0.594988E+09 479.52 01-NOV-06:10 0.137199E+10 879.75 01-NOV-05:10
December 0.590576E+09 479.52 01-DEC-07:10 0.139353E+10 879.75 01-DEC-06:10
             
Annual Sum or Average 0.726942E+10     0.167300E+11    
Minimum of Months 0.550776E+09 479.52   0.127635E+10 879.75  
Maximum of Months 0.651283E+09 479.52   0.145561E+10 879.75  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85948044.82 68.04 02-JAN-07:10 53344630.77 33.31 02-JAN-06:10
February 78150668.37 68.04 01-FEB-07:10 48331578.69 33.31 01-FEB-06:10
March 92411838.57 68.04 01-MAR-07:10 55119587.01 33.31 01-MAR-06:10
April 83348919.34 68.04 03-APR-06:10 51689604.01 33.31 03-APR-05:10
May 89173137.70 68.04 01-MAY-06:10 54232108.89 33.31 01-MAY-05:10
June 88724074.14 68.04 01-JUN-06:10 53152743.61 33.31 01-JUN-05:10
July 83797982.90 68.04 03-JUL-06:10 52768969.29 33.31 03-JUL-05:10
August 92398230.58 68.04 01-AUG-06:10 55119587.01 33.31 01-AUG-05:10
September 83335311.35 68.04 01-SEP-06:10 51689604.01 33.31 01-SEP-05:10
October 85961652.81 68.04 02-OCT-06:10 53344630.77 33.31 02-OCT-05:10
November 84423950.30 68.04 01-NOV-06:10 51953448.85 33.31 01-NOV-05:10
December 83797982.90 68.04 01-DEC-07:10 52768969.29 33.31 01-DEC-06:10
             
Annual Sum or Average 0.103147E+10     0.633515E+09    
Minimum of Months 78150668.37 68.04   48331578.69 33.31  
Maximum of Months 92411838.57 68.04   55119587.01 33.31  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110505E+09 87.48 02-JAN-07:10 17186263.19 10.73 02-JAN-06:10
February 0.100479E+09 87.48 01-FEB-07:10 15571187.20 10.73 01-FEB-06:10
March 0.118815E+09 87.48 01-MAR-07:10 17758108.28 10.73 01-MAR-06:10
April 0.107163E+09 87.48 03-APR-06:10 16653056.29 10.73 03-APR-05:10
May 0.114651E+09 87.48 01-MAY-06:10 17472185.74 10.73 01-MAY-05:10
June 0.114074E+09 87.48 01-JUN-06:10 17124442.10 10.73 01-JUN-05:10
July 0.107740E+09 87.48 03-JUL-06:10 17000799.92 10.73 03-JUL-05:10
August 0.118798E+09 87.48 01-AUG-06:10 17758108.28 10.73 01-AUG-05:10
September 0.107145E+09 87.48 01-SEP-06:10 16653056.29 10.73 01-SEP-05:10
October 0.110522E+09 87.48 02-OCT-06:10 17186263.19 10.73 02-OCT-05:10
November 0.108545E+09 87.48 01-NOV-06:10 16738060.29 10.73 01-NOV-05:10
December 0.107740E+09 87.48 01-DEC-07:10 17000799.92 10.73 01-DEC-06:10
             
Annual Sum or Average 0.132618E+10     0.204102E+09    
Minimum of Months 0.100479E+09 87.48   15571187.20 10.73  
Maximum of Months 0.118815E+09 87.48   17758108.28 10.73  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85948044.82 68.04 02-JAN-07:10 13367164.08 8.35 02-JAN-06:10
February 78150668.37 68.04 01-FEB-07:10 12110987.24 8.35 01-FEB-06:10
March 92411838.57 68.04 01-MAR-07:10 13811934.83 8.35 01-MAR-06:10
April 83348919.34 68.04 03-APR-06:10 12952445.41 8.35 03-APR-05:10
May 89173137.70 68.04 01-MAY-06:10 13589549.46 8.35 01-MAY-05:10
June 88724074.14 68.04 01-JUN-06:10 13319080.76 8.35 01-JUN-05:10
July 83797982.90 68.04 03-JUL-06:10 13222914.11 8.35 03-JUL-05:10
August 92398230.58 68.04 01-AUG-06:10 13811934.83 8.35 01-AUG-05:10
September 83335311.35 68.04 01-SEP-06:10 12952445.41 8.35 01-SEP-05:10
October 85961652.81 68.04 02-OCT-06:10 13367164.08 8.35 02-OCT-05:10
November 84423950.30 68.04 01-NOV-06:10 13018559.98 8.35 01-NOV-05:10
December 83797982.90 68.04 01-DEC-07:10 13222914.11 8.35 01-DEC-06:10
             
Annual Sum or Average 0.103147E+10     0.158747E+09    
Minimum of Months 78150668.37 68.04   12110987.24 8.35  
Maximum of Months 92411838.57 68.04   13811934.83 8.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.811732E+09 642.60 02-JAN-07:10 0.830411E+09 518.59 02-JAN-06:10
February 0.738090E+09 642.60 01-FEB-07:10 0.752373E+09 518.59 01-FEB-06:10
March 0.872778E+09 642.60 01-MAR-07:10 0.858042E+09 518.59 01-MAR-06:10
April 0.787184E+09 642.60 03-APR-06:10 0.804647E+09 518.59 03-APR-05:10
May 0.842191E+09 642.60 01-MAY-06:10 0.844226E+09 518.59 01-MAY-05:10
June 0.837950E+09 642.60 01-JUN-06:10 0.827424E+09 518.59 01-JUN-05:10
July 0.791425E+09 642.60 03-JUL-06:10 0.821450E+09 518.59 03-JUL-05:10
August 0.872650E+09 642.60 01-AUG-06:10 0.858042E+09 518.59 01-AUG-05:10
September 0.787056E+09 642.60 01-SEP-06:10 0.804647E+09 518.59 01-SEP-05:10
October 0.811860E+09 642.60 02-OCT-06:10 0.830411E+09 518.59 02-OCT-05:10
November 0.797337E+09 642.60 01-NOV-06:10 0.808755E+09 518.59 01-NOV-05:10
December 0.791425E+09 642.60 01-DEC-07:10 0.821450E+09 518.59 01-DEC-06:10
             
Annual Sum or Average 0.974168E+10     0.986188E+10    
Minimum of Months 0.738090E+09 642.60   0.752373E+09 518.59  
Maximum of Months 0.872778E+09 642.60   0.858042E+09 518.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232060E+10 1837.08 02-JAN-07:10 0.395666E+10 2470.94 02-JAN-06:10
February 0.211007E+10 1837.08 01-FEB-07:10 0.358484E+10 2470.94 01-FEB-06:10
March 0.249512E+10 1837.08 01-MAR-07:10 0.408832E+10 2470.94 01-MAR-06:10
April 0.225042E+10 1837.08 03-APR-06:10 0.383391E+10 2470.94 03-APR-05:10
May 0.240767E+10 1837.08 01-MAY-06:10 0.402249E+10 2470.94 01-MAY-05:10
June 0.239555E+10 1837.08 01-JUN-06:10 0.394243E+10 2470.94 01-JUN-05:10
July 0.226255E+10 1837.08 03-JUL-06:10 0.391397E+10 2470.94 03-JUL-05:10
August 0.249475E+10 1837.08 01-AUG-06:10 0.408832E+10 2470.94 01-AUG-05:10
September 0.225005E+10 1837.08 01-SEP-06:10 0.383391E+10 2470.94 01-SEP-05:10
October 0.232096E+10 1837.08 02-OCT-06:10 0.395666E+10 2470.94 02-OCT-05:10
November 0.227945E+10 1837.08 01-NOV-06:10 0.385348E+10 2470.94 01-NOV-05:10
December 0.226255E+10 1837.08 01-DEC-07:10 0.391397E+10 2470.94 01-DEC-06:10
             
Annual Sum or Average 0.278497E+11     0.469889E+11    
Minimum of Months 0.211007E+10 1837.08   0.358484E+10 2470.94  
Maximum of Months 0.249512E+10 1837.08   0.408832E+10 2470.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.117872E+10 933.12 02-JAN-07:10 0.200973E+10 1255.08 02-JAN-06:10
February 0.107178E+10 933.12 01-FEB-07:10 0.182087E+10 1255.08 01-FEB-06:10
March 0.126736E+10 933.12 01-MAR-07:10 0.207660E+10 1255.08 01-MAR-06:10
April 0.114307E+10 933.12 03-APR-06:10 0.194738E+10 1255.08 03-APR-05:10
May 0.122295E+10 933.12 01-MAY-06:10 0.204317E+10 1255.08 01-MAY-05:10
June 0.121679E+10 933.12 01-JUN-06:10 0.200250E+10 1255.08 01-JUN-05:10
July 0.114923E+10 933.12 03-JUL-06:10 0.198805E+10 1255.08 03-JUL-05:10
August 0.126718E+10 933.12 01-AUG-06:10 0.207660E+10 1255.08 01-AUG-05:10
September 0.114288E+10 933.12 01-SEP-06:10 0.194738E+10 1255.08 01-SEP-05:10
October 0.117890E+10 933.12 02-OCT-06:10 0.200973E+10 1255.08 02-OCT-05:10
November 0.115781E+10 933.12 01-NOV-06:10 0.195732E+10 1255.08 01-NOV-05:10
December 0.114923E+10 933.12 01-DEC-07:10 0.198805E+10 1255.08 01-DEC-06:10
             
Annual Sum or Average 0.141459E+11     0.238674E+11    
Minimum of Months 0.107178E+10 933.12   0.182087E+10 1255.08  
Maximum of Months 0.126736E+10 933.12   0.207660E+10 1255.08  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.368349E+09 291.60 02-JAN-07:10 34372526.38 21.47 02-JAN-06:10
February 0.334931E+09 291.60 01-FEB-07:10 31142374.40 21.47 01-FEB-06:10
March 0.396051E+09 291.60 01-MAR-07:10 35516216.56 21.47 01-MAR-06:10
April 0.357210E+09 291.60 03-APR-06:10 33306112.57 21.47 03-APR-05:10
May 0.382171E+09 291.60 01-MAY-06:10 34944371.47 21.47 01-MAY-05:10
June 0.380246E+09 291.60 01-JUN-06:10 34248884.20 21.47 01-JUN-05:10
July 0.359134E+09 291.60 03-JUL-06:10 34001599.84 21.47 03-JUL-05:10
August 0.395992E+09 291.60 01-AUG-06:10 35516216.56 21.47 01-AUG-05:10
September 0.357151E+09 291.60 01-SEP-06:10 33306112.57 21.47 01-SEP-05:10
October 0.368407E+09 291.60 02-OCT-06:10 34372526.38 21.47 02-OCT-05:10
November 0.361817E+09 291.60 01-NOV-06:10 33476120.57 21.47 01-NOV-05:10
December 0.359134E+09 291.60 01-DEC-07:10 34001599.84 21.47 01-DEC-06:10
             
Annual Sum or Average 0.442059E+10     0.408205E+09    
Minimum of Months 0.334931E+09 291.60   31142374.40 21.47  
Maximum of Months 0.396051E+09 291.60   35516216.56 21.47  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.717825E+09 568.26 02-JAN-07:10 0.100138E+10 625.36 02-JAN-06:10
February 0.652703E+09 568.26 01-FEB-07:10 0.907273E+09 625.36 01-FEB-06:10
March 0.771810E+09 568.26 01-MAR-07:10 0.103470E+10 625.36 01-MAR-06:10
April 0.696118E+09 568.26 03-APR-06:10 0.970310E+09 625.36 03-APR-05:10
May 0.744761E+09 568.26 01-MAY-06:10 0.101804E+10 625.36 01-MAY-05:10
June 0.741010E+09 568.26 01-JUN-06:10 0.997776E+09 625.36 01-JUN-05:10
July 0.699868E+09 568.26 03-JUL-06:10 0.990572E+09 625.36 03-JUL-05:10
August 0.771696E+09 568.26 01-AUG-06:10 0.103470E+10 625.36 01-AUG-05:10
September 0.696004E+09 568.26 01-SEP-06:10 0.970310E+09 625.36 01-SEP-05:10
October 0.717939E+09 568.26 02-OCT-06:10 0.100138E+10 625.36 02-OCT-05:10
November 0.705096E+09 568.26 01-NOV-06:10 0.975263E+09 625.36 01-NOV-05:10
December 0.699868E+09 568.26 01-DEC-07:10 0.990572E+09 625.36 01-DEC-06:10
             
Annual Sum or Average 0.861470E+10     0.118923E+11    
Minimum of Months 0.652703E+09 568.26   0.907273E+09 625.36  
Maximum of Months 0.771810E+09 568.26   0.103470E+10 625.36  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: NE STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.182837E+09 144.74 02-JAN-07:10 0.106689E+09 66.63 02-JAN-06:10
February 0.166249E+09 144.74 01-FEB-07:10 96663157.38 66.63 01-FEB-06:10
March 0.196587E+09 144.74 01-MAR-07:10 0.110239E+09 66.63 01-MAR-06:10
April 0.177307E+09 144.74 03-APR-06:10 0.103379E+09 66.63 03-APR-05:10
May 0.189697E+09 144.74 01-MAY-06:10 0.108464E+09 66.63 01-MAY-05:10
June 0.188742E+09 144.74 01-JUN-06:10 0.106305E+09 66.63 01-JUN-05:10
July 0.178263E+09 144.74 03-JUL-06:10 0.105538E+09 66.63 03-JUL-05:10
August 0.196558E+09 144.74 01-AUG-06:10 0.110239E+09 66.63 01-AUG-05:10
September 0.177279E+09 144.74 01-SEP-06:10 0.103379E+09 66.63 01-SEP-05:10
October 0.182866E+09 144.74 02-OCT-06:10 0.106689E+09 66.63 02-OCT-05:10
November 0.179594E+09 144.74 01-NOV-06:10 0.103907E+09 66.63 01-NOV-05:10
December 0.178263E+09 144.74 01-DEC-07:10 0.105538E+09 66.63 01-DEC-06:10
             
Annual Sum or Average 0.219424E+10     0.126703E+10    
Minimum of Months 0.166249E+09 144.74   96663157.38 66.63  
Maximum of Months 0.196587E+09 144.74   0.110239E+09 66.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: NW ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.152364E+09 120.62 02-JAN-07:10 88907770.82 55.52 02-JAN-06:10
February 0.138541E+09 120.62 01-FEB-07:10 80552679.05 55.52 01-FEB-06:10
March 0.163822E+09 120.62 01-MAR-07:10 91866032.98 55.52 01-MAR-06:10
April 0.147756E+09 120.62 03-APR-06:10 86149391.24 55.52 03-APR-05:10
May 0.158081E+09 120.62 01-MAY-06:10 90386901.90 55.52 01-MAY-05:10
June 0.157285E+09 120.62 01-JUN-06:10 88587958.69 55.52 01-JUN-05:10
July 0.148552E+09 120.62 03-JUL-06:10 87948334.44 55.52 03-JUL-05:10
August 0.163798E+09 120.62 01-AUG-06:10 91866032.98 55.52 01-AUG-05:10
September 0.147732E+09 120.62 01-SEP-06:10 86149391.24 55.52 01-SEP-05:10
October 0.152388E+09 120.62 02-OCT-06:10 88907770.82 55.52 02-OCT-05:10
November 0.149662E+09 120.62 01-NOV-06:10 86589132.91 55.52 01-NOV-05:10
December 0.148552E+09 120.62 01-DEC-07:10 87948334.44 55.52 01-DEC-06:10
             
Annual Sum or Average 0.182853E+10     0.105586E+10    
Minimum of Months 0.138541E+09 120.62   80552679.05 55.52  
Maximum of Months 0.163822E+09 120.62   91866032.98 55.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: NW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.208956E+09 165.42 02-JAN-07:10 0.121931E+09 76.15 02-JAN-06:10
February 0.189999E+09 165.42 01-FEB-07:10 0.110472E+09 76.15 01-FEB-06:10
March 0.224671E+09 165.42 01-MAR-07:10 0.125988E+09 76.15 01-MAR-06:10
April 0.202637E+09 165.42 03-APR-06:10 0.118148E+09 76.15 03-APR-05:10
May 0.216797E+09 165.42 01-MAY-06:10 0.123959E+09 76.15 01-MAY-05:10
June 0.215705E+09 165.42 01-JUN-06:10 0.121492E+09 76.15 01-JUN-05:10
July 0.203729E+09 165.42 03-JUL-06:10 0.120615E+09 76.15 03-JUL-05:10
August 0.224638E+09 165.42 01-AUG-06:10 0.125988E+09 76.15 01-AUG-05:10
September 0.202604E+09 165.42 01-SEP-06:10 0.118148E+09 76.15 01-SEP-05:10
October 0.208989E+09 165.42 02-OCT-06:10 0.121931E+09 76.15 02-OCT-05:10
November 0.205251E+09 165.42 01-NOV-06:10 0.118751E+09 76.15 01-NOV-05:10
December 0.203729E+09 165.42 01-DEC-07:10 0.120615E+09 76.15 01-DEC-06:10
             
Annual Sum or Average 0.250770E+10     0.144804E+10    
Minimum of Months 0.189999E+09 165.42   0.110472E+09 76.15  
Maximum of Months 0.224671E+09 165.42   0.125988E+09 76.15  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: SW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104478E+09 82.71 02-JAN-07:10 60965382.94 38.07 02-JAN-06:10
February 94999583.58 82.71 01-FEB-07:10 55236172.04 38.07 01-FEB-06:10
March 0.112335E+09 82.71 01-MAR-07:10 62993907.37 38.07 01-MAR-06:10
April 0.101319E+09 82.71 03-APR-06:10 59073920.97 38.07 03-APR-05:10
May 0.108398E+09 82.71 01-MAY-06:10 61979645.16 38.07 01-MAY-05:10
June 0.107853E+09 82.71 01-JUN-06:10 60746083.00 38.07 01-JUN-05:10
July 0.101864E+09 82.71 03-JUL-06:10 60307483.12 38.07 03-JUL-05:10
August 0.112319E+09 82.71 01-AUG-06:10 62993907.37 38.07 01-AUG-05:10
September 0.101302E+09 82.71 01-SEP-06:10 59073920.97 38.07 01-SEP-05:10
October 0.104495E+09 82.71 02-OCT-06:10 60965382.94 38.07 02-OCT-05:10
November 0.102625E+09 82.71 01-NOV-06:10 59375458.38 38.07 01-NOV-05:10
December 0.101864E+09 82.71 01-DEC-07:10 60307483.12 38.07 01-DEC-06:10
             
Annual Sum or Average 0.125385E+10     0.724019E+09    
Minimum of Months 94999583.58 82.71   55236172.04 38.07  
Maximum of Months 0.112335E+09 82.71   62993907.37 38.07  



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.229197E+09 0.184174E+09 0.342612E+09 0.00 0.00 0.00 0.00 1812586.00 5704687.52
February 0.208246E+09 0.167466E+09 0.310415E+09 0.00 0.00 0.00 0.00 3305205.83 6666121.59
March 0.248327E+09 0.198025E+09 0.354012E+09 0.00 0.00 0.00 0.00 4728478.53 5079416.89
April 0.221404E+09 0.178605E+09 0.331982E+09 0.00 0.00 0.00 0.00 7346134.51 749489.79
May 0.238762E+09 0.191085E+09 0.348312E+09 0.00 0.00 0.00 0.00 14469871.65 57190.89
June 0.238155E+09 0.190123E+09 0.341379E+09 0.00 0.00 0.00 0.00 13454563.55 0.00
July 0.222011E+09 0.179567E+09 0.338914E+09 0.00 0.00 0.00 0.00 11323613.48 0.19
August 0.248327E+09 0.197996E+09 0.354012E+09 0.00 0.00 0.00 0.00 12735592.59 0.29
September 0.221404E+09 0.178576E+09 0.331982E+09 0.00 0.00 0.00 0.00 12215575.09 0.00
October 0.229197E+09 0.184204E+09 0.342612E+09 0.00 0.00 0.00 0.00 10266245.30 38128.18
November 0.226210E+09 0.180908E+09 0.333677E+09 0.00 0.00 0.00 0.00 6284024.17 3395672.67
December 0.222011E+09 0.179567E+09 0.338914E+09 0.00 0.00 0.00 0.00 2404347.86 5657640.43
                   
Annual Sum or Average 0.275325E+10 0.221030E+10 0.406882E+10 0.00 0.00 0.00 0.00 0.100346E+09 27348348.45
Minimum of Months 0.208246E+09 0.167466E+09 0.310415E+09 0.00 0.00 0.00 0.00 1812586.00 0.00
Maximum of Months 0.248327E+09 0.198025E+09 0.354012E+09 0.00 0.00 0.00 0.00 14469871.65 6666121.59



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11883110.40 57298696.55 8911442.72 0.00 0.00 0.00 0.00 0.00 0.00
February 10796889.60 52100445.58 8073991.50 0.00 0.00 0.00 0.00 0.00 0.00
March 12874982.40 61607892.38 9207956.55 0.00 0.00 0.00 0.00 0.00 0.00
April 11479104.00 55565946.23 8634963.61 0.00 0.00 0.00 0.00 0.00 0.00
May 12379046.40 59448758.47 9059699.64 0.00 0.00 0.00 0.00 0.00 0.00
June 12347596.80 59149382.76 8879387.17 0.00 0.00 0.00 0.00 0.00 0.00
July 11510553.60 55865321.94 8815276.07 0.00 0.00 0.00 0.00 0.00 0.00
August 12874982.40 61598820.39 9207956.55 0.00 0.00 0.00 0.00 0.00 0.00
September 11479104.00 55556874.24 8634963.61 0.00 0.00 0.00 0.00 0.00 0.00
October 11883110.40 57307768.54 8911442.72 0.00 0.00 0.00 0.00 0.00 0.00
November 11728281.60 56282633.53 8679039.99 0.00 0.00 0.00 0.00 0.00 0.00
December 11510553.60 55865321.94 8815276.07 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.142747E+09 0.687648E+09 0.105831E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 10796889.60 52100445.58 8073991.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12874982.40 61607892.38 9207956.55 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.445660E+10 0.429740E+09 0.665880E+09 0.00 0.00 0.00 0.00 1043769.39 18443471.07
February 0.404923E+10 0.390753E+09 0.603304E+09 0.00 0.00 0.00 0.00 2315516.23 24300898.45
March 0.482859E+10 0.462059E+09 0.688036E+09 0.00 0.00 0.00 0.00 2610437.01 20665483.28
April 0.430508E+10 0.416745E+09 0.645221E+09 0.00 0.00 0.00 0.00 4374020.77 7729590.94
May 0.464259E+10 0.445866E+09 0.676958E+09 0.00 0.00 0.00 0.00 10786033.32 1620472.09
June 0.463080E+10 0.443620E+09 0.663485E+09 0.00 0.00 0.00 0.00 12840134.91 267372.69
July 0.431688E+10 0.418990E+09 0.658694E+09 0.00 0.00 0.00 0.00 10933662.06 337150.76
August 0.482859E+10 0.461991E+09 0.688036E+09 0.00 0.00 0.00 0.00 12828395.09 184992.49
September 0.430508E+10 0.416677E+09 0.645221E+09 0.00 0.00 0.00 0.00 11965191.36 421467.87
October 0.445660E+10 0.429808E+09 0.665880E+09 0.00 0.00 0.00 0.00 8131729.61 1134010.02
November 0.439853E+10 0.422120E+09 0.648514E+09 0.00 0.00 0.00 0.00 4156768.71 13381512.72
December 0.431688E+10 0.418990E+09 0.658694E+09 0.00 0.00 0.00 0.00 1466767.74 18608719.35
                   
Annual Sum or Average 0.535355E+11 0.515736E+10 0.790792E+10 0.00 0.00 0.00 0.00 83452426.21 0.107095E+09
Minimum of Months 0.404923E+10 0.390753E+09 0.603304E+09 0.00 0.00 0.00 0.00 1043769.39 184992.49
Maximum of Months 0.482859E+10 0.462059E+09 0.688036E+09 0.00 0.00 0.00 0.00 12840134.91 24300898.45



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 CLEAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.267396E+09 0.214870E+09 0.399714E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.242954E+09 0.195377E+09 0.362151E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.289715E+09 0.231030E+09 0.413013E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.258305E+09 0.208372E+09 0.387312E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.278556E+09 0.222933E+09 0.406364E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.277848E+09 0.221810E+09 0.398276E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.259013E+09 0.209495E+09 0.395400E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.289715E+09 0.230996E+09 0.413013E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.258305E+09 0.208338E+09 0.387312E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.267396E+09 0.214904E+09 0.399714E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.263912E+09 0.211060E+09 0.389289E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.259013E+09 0.209495E+09 0.395400E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.321213E+10 0.257868E+10 0.474696E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.242954E+09 0.195377E+09 0.362151E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.289715E+09 0.231030E+09 0.413013E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.350161E+09 0.281378E+09 0.523434E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.318154E+09 0.255850E+09 0.474245E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.379389E+09 0.302539E+09 0.540851E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.338257E+09 0.272868E+09 0.507195E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.364775E+09 0.291936E+09 0.532143E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.363849E+09 0.290466E+09 0.521552E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.339183E+09 0.274339E+09 0.517786E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.379389E+09 0.302494E+09 0.540851E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.338257E+09 0.272824E+09 0.507195E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.350161E+09 0.281422E+09 0.523434E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.345599E+09 0.276388E+09 0.509784E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.339183E+09 0.274339E+09 0.517786E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.420636E+10 0.337684E+10 0.621626E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.318154E+09 0.255850E+09 0.474245E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.379389E+09 0.302539E+09 0.540851E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 55743792.66 0.157571E+09 0.219815E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 50613077.37 0.143276E+09 0.199158E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 60343744.30 0.169422E+09 0.227129E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 53756831.30 0.152806E+09 0.212995E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 58043768.48 0.163484E+09 0.223472E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 57866847.27 0.162661E+09 0.219024E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 53933752.52 0.153630E+09 0.217443E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 60343744.30 0.169397E+09 0.227129E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 53756831.30 0.152781E+09 0.212995E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 55743792.66 0.157596E+09 0.219815E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 55076935.77 0.154777E+09 0.214082E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 53933752.52 0.153630E+09 0.217443E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.669157E+09 0.189103E+10 0.261050E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 50613077.37 0.143276E+09 0.199158E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 60343744.30 0.169422E+09 0.227129E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 19908497.38 56275505.54 78505166.56 0.00 0.00 0.00 0.00 733586.74 5978142.60
February 18076099.06 51170080.48 71127657.65 0.00 0.00 0.00 0.00 1313007.79 7158634.49
March 21551337.25 60507751.44 81117298.90 0.00 0.00 0.00 0.00 1666609.73 5736919.75
April 19198868.32 54573697.19 76069529.65 0.00 0.00 0.00 0.00 2921501.10 1435552.92
May 20729917.32 58387173.50 79811232.73 0.00 0.00 0.00 0.00 6916943.52 186680.39
June 20666731.17 58093143.78 78222773.87 0.00 0.00 0.00 0.00 7389174.85 31700.68
July 19262054.47 54867726.90 77657988.50 0.00 0.00 0.00 0.00 6122615.74 35657.71
August 21551337.25 60498841.45 81117298.90 0.00 0.00 0.00 0.00 7217515.43 16740.32
September 19198868.32 54564787.20 76069529.65 0.00 0.00 0.00 0.00 6687382.44 22031.73
October 19908497.38 56284415.53 78505166.56 0.00 0.00 0.00 0.00 5147102.39 152205.93
November 19670334.20 55277586.51 76457819.59 0.00 0.00 0.00 0.00 2899011.16 4010169.85
December 19262054.47 54867726.90 77657988.50 0.00 0.00 0.00 0.00 929943.39 6105027.09
                   
Annual Sum or Average 0.238985E+09 0.675368E+09 0.932319E+09 0.00 0.00 0.00 0.00 49944394.27 30869463.46
Minimum of Months 18076099.06 51170080.48 71127657.65 0.00 0.00 0.00 0.00 733586.74 16740.32
Maximum of Months 21551337.25 60507751.44 81117298.90 0.00 0.00 0.00 0.00 7389174.85 7158634.49



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 15596582.40 0.167121E+09 0.777149E+09 0.00 0.00 0.00 0.00 460573.72 6339489.23
February 14170917.60 0.151960E+09 0.704116E+09 0.00 0.00 0.00 0.00 921531.40 8184741.36
March 16898414.40 0.179690E+09 0.803007E+09 0.00 0.00 0.00 0.00 1106411.67 7026678.97
April 15066324.00 0.162067E+09 0.753038E+09 0.00 0.00 0.00 0.00 1887325.93 2485166.13
May 16247498.40 0.173392E+09 0.790078E+09 0.00 0.00 0.00 0.00 4600893.71 508145.97
June 16206220.80 0.172519E+09 0.774353E+09 0.00 0.00 0.00 0.00 5311627.03 90385.96
July 15107601.60 0.162941E+09 0.768762E+09 0.00 0.00 0.00 0.00 4509208.76 94262.84
August 16898414.40 0.179663E+09 0.803007E+09 0.00 0.00 0.00 0.00 5349057.12 54707.37
September 15066324.00 0.162041E+09 0.753038E+09 0.00 0.00 0.00 0.00 4981744.19 110437.35
October 15596582.40 0.167148E+09 0.777149E+09 0.00 0.00 0.00 0.00 3552855.50 354536.47
November 15393369.60 0.164158E+09 0.756881E+09 0.00 0.00 0.00 0.00 1902815.82 4489737.26
December 15107601.60 0.162941E+09 0.768762E+09 0.00 0.00 0.00 0.00 657721.89 6309836.27
                   
Annual Sum or Average 0.187356E+09 0.200564E+10 0.922934E+10 0.00 0.00 0.00 0.00 35241766.76 36048125.21
Minimum of Months 14170917.60 0.151960E+09 0.704116E+09 0.00 0.00 0.00 0.00 460573.72 54707.37
Maximum of Months 16898414.40 0.179690E+09 0.803007E+09 0.00 0.00 0.00 0.00 5349057.12 8184741.36



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 14482540.80 0.155184E+09 0.127493E+10 0.00 0.00 0.00 0.00 1069291.51 19042635.01
February 13158709.20 0.141105E+09 0.115637E+10 0.00 0.00 0.00 0.00 2338850.96 25019258.81
March 15691384.80 0.166855E+09 0.129794E+10 0.00 0.00 0.00 0.00 2680824.55 21165780.09
April 13990158.00 0.150491E+09 0.124308E+10 0.00 0.00 0.00 0.00 4476847.48 7805962.98
May 15086962.80 0.161007E+09 0.128643E+10 0.00 0.00 0.00 0.00 11184415.94 1621912.92
June 15048633.60 0.160196E+09 0.125459E+10 0.00 0.00 0.00 0.00 13617025.35 267384.76
July 14028487.20 0.151302E+09 0.127493E+10 0.00 0.00 0.00 0.00 11733708.04 337115.13
August 15691384.80 0.166830E+09 0.129794E+10 0.00 0.00 0.00 0.00 13912034.67 184911.43
September 13990158.00 0.150467E+09 0.124308E+10 0.00 0.00 0.00 0.00 12833404.90 421432.97
October 14482540.80 0.155209E+09 0.127493E+10 0.00 0.00 0.00 0.00 8771721.04 1133820.96
November 14293843.20 0.152432E+09 0.123157E+10 0.00 0.00 0.00 0.00 4542405.72 13603062.23
December 14028487.20 0.151302E+09 0.127493E+10 0.00 0.00 0.00 0.00 1533346.19 19035512.20
                   
Annual Sum or Average 0.173973E+09 0.186238E+10 0.151107E+11 0.00 0.00 0.00 0.00 88693876.34 0.109639E+09
Minimum of Months 13158709.20 0.141105E+09 0.115637E+10 0.00 0.00 0.00 0.00 1069291.51 184911.43
Maximum of Months 15691384.80 0.166855E+09 0.129794E+10 0.00 0.00 0.00 0.00 13912034.67 25019258.81



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 23890196.86 67530606.65 94206295.03 0.00 0.00 0.00 0.00 0.00 0.00
February 21691318.87 61404096.58 85353275.40 0.00 0.00 0.00 0.00 0.00 0.00
March 25861604.70 72609301.73 97340857.01 0.00 0.00 0.00 0.00 0.00 0.00
April 23038641.99 65488436.62 91283527.79 0.00 0.00 0.00 0.00 0.00 0.00
May 24875900.78 70064608.20 95773576.02 0.00 0.00 0.00 0.00 0.00 0.00
June 24800077.40 69711772.54 93867423.47 0.00 0.00 0.00 0.00 0.00 0.00
July 23114465.37 65841272.28 93189680.34 0.00 0.00 0.00 0.00 0.00 0.00
August 25861604.70 72598609.74 97340857.01 0.00 0.00 0.00 0.00 0.00 0.00
September 23038641.99 65477744.63 91283527.79 0.00 0.00 0.00 0.00 0.00 0.00
October 23890196.86 67541298.64 94206295.03 0.00 0.00 0.00 0.00 0.00 0.00
November 23604401.04 66333103.81 91749476.19 0.00 0.00 0.00 0.00 0.00 0.00
December 23114465.37 65841272.28 93189680.34 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.286782E+09 0.810442E+09 0.111878E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 21691318.87 61404096.58 85353275.40 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25861604.70 72609301.73 97340857.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 IT HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 74269440.00 0.152364E+09 88907770.82 0.00 0.00 0.00 0.00 0.00 0.00
February 67480560.00 0.138541E+09 80552679.05 0.00 0.00 0.00 0.00 0.00 0.00
March 80468640.00 0.163822E+09 91866032.98 0.00 0.00 0.00 0.00 0.00 0.00
April 71744400.00 0.147756E+09 86149391.24 0.00 0.00 0.00 0.00 0.00 0.00
May 77369040.00 0.158081E+09 90386901.90 0.00 0.00 0.00 0.00 0.00 0.00
June 77172480.00 0.157285E+09 88587958.69 0.00 0.00 0.00 0.00 0.00 0.00
July 71940960.00 0.148552E+09 87948334.44 0.00 0.00 0.00 0.00 0.00 0.00
August 80468640.00 0.163798E+09 91866032.98 0.00 0.00 0.00 0.00 0.00 0.00
September 71744400.00 0.147732E+09 86149391.24 0.00 0.00 0.00 0.00 0.00 0.00
October 74269440.00 0.152388E+09 88907770.82 0.00 0.00 0.00 0.00 0.00 0.00
November 73301760.00 0.149662E+09 86589132.91 0.00 0.00 0.00 0.00 0.00 0.00
December 71940960.00 0.148552E+09 87948334.44 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.892171E+09 0.182853E+10 0.105586E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 67480560.00 0.138541E+09 80552679.05 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 80468640.00 0.163822E+09 91866032.98 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 49550037.92 0.140063E+09 0.195391E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 44989402.11 0.127357E+09 0.177029E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 53638883.83 0.150597E+09 0.201892E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 47783850.05 0.135828E+09 0.189329E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 51594460.87 0.145319E+09 0.198642E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 51437197.57 0.144587E+09 0.194688E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 47941113.35 0.136560E+09 0.193282E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 53638883.83 0.150575E+09 0.201892E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 47783850.05 0.135806E+09 0.189329E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 49550037.92 0.140086E+09 0.195391E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 48957276.24 0.137580E+09 0.190295E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 47941113.35 0.136560E+09 0.193282E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.594806E+09 0.168092E+10 0.232044E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 44989402.11 0.127357E+09 0.177029E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 53638883.83 0.150597E+09 0.201892E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 LOBBY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.660001E+09 0.919280E+09 0.108512E+10 0.00 0.00 0.00 0.00 1629303.67 18178281.32
February 0.599671E+09 0.835881E+09 0.983143E+09 0.00 0.00 0.00 0.00 2825434.48 23382973.86
March 0.715091E+09 0.988416E+09 0.112122E+10 0.00 0.00 0.00 0.00 3458278.73 20454118.85
April 0.637562E+09 0.891481E+09 0.105145E+10 0.00 0.00 0.00 0.00 5843850.19 7070732.86
May 0.687546E+09 0.953775E+09 0.110317E+10 0.00 0.00 0.00 0.00 14740081.75 1172392.30
June 0.685799E+09 0.948972E+09 0.108121E+10 0.00 0.00 0.00 0.00 17302317.15 227389.86
July 0.639309E+09 0.896284E+09 0.107341E+10 0.00 0.00 0.00 0.00 14415067.22 205226.55
August 0.715091E+09 0.988270E+09 0.112122E+10 0.00 0.00 0.00 0.00 17127006.70 117428.25
September 0.637562E+09 0.891335E+09 0.105145E+10 0.00 0.00 0.00 0.00 16019873.38 199013.96
October 0.660001E+09 0.919426E+09 0.108512E+10 0.00 0.00 0.00 0.00 11535800.57 840085.47
November 0.651402E+09 0.902979E+09 0.105682E+10 0.00 0.00 0.00 0.00 6526250.65 12763133.30
December 0.639309E+09 0.896284E+09 0.107341E+10 0.00 0.00 0.00 0.00 2062213.40 18478295.28
                   
Annual Sum or Average 0.792835E+10 0.110324E+11 0.128867E+11 0.00 0.00 0.00 0.00 0.113485E+09 0.103089E+09
Minimum of Months 0.599671E+09 0.835881E+09 0.983143E+09 0.00 0.00 0.00 0.00 1629303.67 117428.25
Maximum of Months 0.715091E+09 0.988416E+09 0.112122E+10 0.00 0.00 0.00 0.00 17302317.15 23382973.86



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.127319E+09 0.261195E+09 0.152413E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.115681E+09 0.237499E+09 0.138090E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137946E+09 0.280838E+09 0.157485E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.122990E+09 0.253296E+09 0.147685E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132633E+09 0.270996E+09 0.154949E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.132296E+09 0.269631E+09 0.151865E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.123327E+09 0.254661E+09 0.150769E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.137946E+09 0.280797E+09 0.157485E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.122990E+09 0.253255E+09 0.147685E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.127319E+09 0.261236E+09 0.152413E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.125660E+09 0.256563E+09 0.148438E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.123327E+09 0.254661E+09 0.150769E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.152944E+10 0.313463E+10 0.181004E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.115681E+09 0.237499E+09 0.138090E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137946E+09 0.280838E+09 0.157485E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 28646784.00 55252314.53 34293067.55 0.00 0.00 0.00 0.00 1215356.83 3883847.08
February 26028216.00 50239715.38 31070382.70 0.00 0.00 0.00 0.00 2030132.52 4722227.04
March 31037904.00 59407610.51 35434113.87 0.00 0.00 0.00 0.00 2640758.46 3912317.05
April 27672840.00 53581448.15 33229118.96 0.00 0.00 0.00 0.00 3896109.37 901046.25
May 29842344.00 57325588.52 34863590.71 0.00 0.00 0.00 0.00 7930945.94 94645.03
June 29766528.00 57036904.80 34169711.20 0.00 0.00 0.00 0.00 7760904.58 6989.50
July 27748656.00 53870131.87 33922998.48 0.00 0.00 0.00 0.00 6451550.02 3294.16
August 31037904.00 59398862.52 35434113.87 0.00 0.00 0.00 0.00 7439608.19 3233.94
September 27672840.00 53572700.16 33229118.96 0.00 0.00 0.00 0.00 7187195.67 3058.18
October 28646784.00 55261062.52 34293067.55 0.00 0.00 0.00 0.00 5981353.14 60683.83
November 28273536.00 54272539.48 33398733.96 0.00 0.00 0.00 0.00 3813755.04 2467532.85
December 27748656.00 53870131.87 33922998.48 0.00 0.00 0.00 0.00 1504325.64 3926135.99
                   
Annual Sum or Average 0.344123E+09 0.663089E+09 0.407261E+09 0.00 0.00 0.00 0.00 57851995.40 19985010.89
Minimum of Months 26028216.00 50239715.38 31070382.70 0.00 0.00 0.00 0.00 1215356.83 3058.18
Maximum of Months 31037904.00 59407610.51 35434113.87 0.00 0.00 0.00 0.00 7930945.94 4722227.04



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.105048E+10 0.600272E+09 0.314012E+10 0.00 0.00 0.00 0.00 1488023.45 20255977.27
February 0.954461E+09 0.545814E+09 0.284503E+10 0.00 0.00 0.00 0.00 2878849.67 26276224.40
March 0.113817E+10 0.645416E+09 0.324460E+10 0.00 0.00 0.00 0.00 3473700.98 22304477.25
April 0.101477E+10 0.582119E+09 0.304270E+10 0.00 0.00 0.00 0.00 6241172.90 7519322.03
May 0.109433E+10 0.622797E+09 0.319236E+10 0.00 0.00 0.00 0.00 15094642.44 1396699.06
June 0.109155E+10 0.619660E+09 0.312883E+10 0.00 0.00 0.00 0.00 17511806.66 236825.32
July 0.101755E+10 0.585256E+09 0.310623E+10 0.00 0.00 0.00 0.00 15169286.45 201345.79
August 0.113817E+10 0.645321E+09 0.324460E+10 0.00 0.00 0.00 0.00 17751278.74 121318.71
September 0.101477E+10 0.582024E+09 0.304270E+10 0.00 0.00 0.00 0.00 16752362.54 197169.33
October 0.105048E+10 0.600367E+09 0.314012E+10 0.00 0.00 0.00 0.00 11944917.48 879835.44
November 0.103680E+10 0.589628E+09 0.305823E+10 0.00 0.00 0.00 0.00 6206706.89 14323097.47
December 0.101755E+10 0.585256E+09 0.310623E+10 0.00 0.00 0.00 0.00 2036532.78 20444857.97
                   
Annual Sum or Average 0.126191E+11 0.720393E+10 0.372918E+11 0.00 0.00 0.00 0.00 0.116549E+09 0.114157E+09
Minimum of Months 0.954461E+09 0.545814E+09 0.284503E+10 0.00 0.00 0.00 0.00 1488023.45 121318.71
Maximum of Months 0.113817E+10 0.645416E+09 0.324460E+10 0.00 0.00 0.00 0.00 17751278.74 26276224.40



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.263126E+09 0.539803E+09 0.314987E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.239074E+09 0.490831E+09 0.285387E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.285089E+09 0.580400E+09 0.325468E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.254180E+09 0.523479E+09 0.305215E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.274107E+09 0.560059E+09 0.320228E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.273411E+09 0.557238E+09 0.313854E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.254877E+09 0.526300E+09 0.311588E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.285089E+09 0.580314E+09 0.325468E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.254180E+09 0.523394E+09 0.305215E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.263126E+09 0.539889E+09 0.314987E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.259698E+09 0.530231E+09 0.306773E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.254877E+09 0.526300E+09 0.311588E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.316083E+10 0.647824E+10 0.374076E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.239074E+09 0.490831E+09 0.285387E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.285089E+09 0.580400E+09 0.325468E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.572991E+09 0.327421E+09 0.171279E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.520615E+09 0.297717E+09 0.155183E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.620818E+09 0.352045E+09 0.176978E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.553511E+09 0.317520E+09 0.165965E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.596905E+09 0.339707E+09 0.174129E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.595388E+09 0.337996E+09 0.170663E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.555027E+09 0.319230E+09 0.169431E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.620818E+09 0.351993E+09 0.176978E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.553511E+09 0.317468E+09 0.165965E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.572991E+09 0.327473E+09 0.171279E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.565526E+09 0.321615E+09 0.166812E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.555027E+09 0.319230E+09 0.169431E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.688313E+10 0.392942E+10 0.203410E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.520615E+09 0.297717E+09 0.155183E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.620818E+09 0.352045E+09 0.176978E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 MED GAS

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 11883110.40 57298696.55 8911442.72 0.00 0.00 0.00 0.00 1949761.77 6776924.92
February 10796889.60 52100445.58 8073991.50 0.00 0.00 0.00 0.00 3209759.15 7861460.95
March 12874982.40 61607892.38 9207956.55 0.00 0.00 0.00 0.00 4198359.51 6123895.98
April 11479104.00 55565946.23 8634963.61 0.00 0.00 0.00 0.00 5741933.18 1104536.15
May 12379046.40 59448758.47 9059699.64 0.00 0.00 0.00 0.00 12368626.72 150906.68
June 12347596.80 59149382.76 8879387.17 0.00 0.00 0.00 0.00 12492411.99 35433.46
July 11510553.60 55865321.94 8815276.07 0.00 0.00 0.00 0.00 9907410.12 63421.75
August 12874982.40 61598820.39 9207956.55 0.00 0.00 0.00 0.00 12054880.48 29310.53
September 11479104.00 55556874.24 8634963.61 0.00 0.00 0.00 0.00 11106961.50 34245.24
October 11883110.40 57307768.54 8911442.72 0.00 0.00 0.00 0.00 9175889.71 147300.85
November 11728281.60 56282633.53 8679039.99 0.00 0.00 0.00 0.00 5847734.22 4633402.08
December 11510553.60 55865321.94 8815276.07 0.00 0.00 0.00 0.00 2303499.65 6999243.12
                   
Annual Sum or Average 0.142747E+09 0.687648E+09 0.105831E+09 0.00 0.00 0.00 0.00 90357227.99 33960081.71
Minimum of Months 10796889.60 52100445.58 8073991.50 0.00 0.00 0.00 0.00 1949761.77 29310.53
Maximum of Months 12874982.40 61607892.38 9207956.55 0.00 0.00 0.00 0.00 12492411.99 7861460.95



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.356528E+09 0.286493E+09 0.266451E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.323938E+09 0.260502E+09 0.241411E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.386287E+09 0.308039E+09 0.275317E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.344407E+09 0.277830E+09 0.258184E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.371408E+09 0.297244E+09 0.270884E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.370464E+09 0.295747E+09 0.265493E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.345350E+09 0.279327E+09 0.263576E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.386287E+09 0.307994E+09 0.275317E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.344407E+09 0.277784E+09 0.258184E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.356528E+09 0.286539E+09 0.266451E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.351883E+09 0.281413E+09 0.259502E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.345350E+09 0.279327E+09 0.263576E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.428284E+10 0.343824E+10 0.316435E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.323938E+09 0.260502E+09 0.241411E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.386287E+09 0.308039E+09 0.275317E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 77982912.00 0.159982E+09 93353183.15 0.00 0.00 0.00 0.00 0.00 0.00
February 70854588.00 0.145468E+09 84580334.55 0.00 0.00 0.00 0.00 0.00 0.00
March 84492072.00 0.172014E+09 96459359.21 0.00 0.00 0.00 0.00 0.00 0.00
April 75331620.00 0.155144E+09 90456883.85 0.00 0.00 0.00 0.00 0.00 0.00
May 81237492.00 0.165985E+09 94906271.18 0.00 0.00 0.00 0.00 0.00 0.00
June 81031104.00 0.165149E+09 93017380.33 0.00 0.00 0.00 0.00 0.00 0.00
July 75538008.00 0.155980E+09 92345774.70 0.00 0.00 0.00 0.00 0.00 0.00
August 84492072.00 0.171988E+09 96459359.21 0.00 0.00 0.00 0.00 0.00 0.00
September 75331620.00 0.155119E+09 90456883.85 0.00 0.00 0.00 0.00 0.00 0.00
October 77982912.00 0.160007E+09 93353183.15 0.00 0.00 0.00 0.00 0.00 0.00
November 76966848.00 0.157145E+09 90918612.73 0.00 0.00 0.00 0.00 0.00 0.00
December 75538008.00 0.155980E+09 92345774.70 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.936779E+09 0.191996E+10 0.110865E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 70854588.00 0.145468E+09 84580334.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 84492072.00 0.172014E+09 96459359.21 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.933764E+09 0.750340E+09 0.697848E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.848410E+09 0.682268E+09 0.632268E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.101170E+10 0.806770E+09 0.721068E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.902017E+09 0.727649E+09 0.676197E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.972734E+09 0.778496E+09 0.709458E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.970263E+09 0.774575E+09 0.695338E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.904489E+09 0.731570E+09 0.690317E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.101170E+10 0.806651E+09 0.721068E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.902017E+09 0.727530E+09 0.676197E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.933764E+09 0.750459E+09 0.697848E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.921598E+09 0.737034E+09 0.679649E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.904489E+09 0.731570E+09 0.690317E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.112170E+11 0.900491E+10 0.828757E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.848410E+09 0.682268E+09 0.632268E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.101170E+10 0.806770E+09 0.721068E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 28646784.00 55252314.53 34293067.55 0.00 0.00 0.00 0.00 1387951.77 3416054.77
February 26028216.00 50239715.38 31070382.70 0.00 0.00 0.00 0.00 2350877.50 3955090.52
March 31037904.00 59407610.51 35434113.87 0.00 0.00 0.00 0.00 3250975.14 3078966.64
April 27672840.00 53581448.15 33229118.96 0.00 0.00 0.00 0.00 4804937.99 417134.23
May 29842344.00 57325588.52 34863590.71 0.00 0.00 0.00 0.00 9262658.17 35460.30
June 29766528.00 57036904.80 34169711.20 0.00 0.00 0.00 0.00 8650650.01 0.00
July 27748656.00 53870131.87 33922998.48 0.00 0.00 0.00 0.00 7237621.10 0.00
August 31037904.00 59398862.52 35434113.87 0.00 0.00 0.00 0.00 8251916.20 9.52
September 27672840.00 53572700.16 33229118.96 0.00 0.00 0.00 0.00 8014154.33 0.00
October 28646784.00 55261062.52 34293067.55 0.00 0.00 0.00 0.00 6956814.66 18129.62
November 28273536.00 54272539.48 33398733.96 0.00 0.00 0.00 0.00 4376133.44 2042190.05
December 27748656.00 53870131.87 33922998.48 0.00 0.00 0.00 0.00 1799196.22 3441782.59
                   
Annual Sum or Average 0.344123E+09 0.663089E+09 0.407261E+09 0.00 0.00 0.00 0.00 66343886.53 16404818.26
Minimum of Months 26028216.00 50239715.38 31070382.70 0.00 0.00 0.00 0.00 1387951.77 0.00
Maximum of Months 31037904.00 59407610.51 35434113.87 0.00 0.00 0.00 0.00 9262658.17 3955090.52



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.289650E+09 0.206912E+09 0.577364E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.263173E+09 0.188140E+09 0.523106E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.313826E+09 0.222473E+09 0.596575E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.279802E+09 0.200655E+09 0.559451E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.301738E+09 0.214676E+09 0.586969E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.300971E+09 0.213595E+09 0.575287E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.280569E+09 0.201736E+09 0.571133E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.313826E+09 0.222440E+09 0.596575E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.279802E+09 0.200622E+09 0.559451E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.289650E+09 0.206945E+09 0.577364E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.285876E+09 0.203243E+09 0.562307E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.280569E+09 0.201736E+09 0.571133E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.347945E+10 0.248317E+10 0.685672E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.263173E+09 0.188140E+09 0.523106E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.313826E+09 0.222473E+09 0.596575E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.263126E+09 0.539803E+09 0.314987E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.239074E+09 0.490831E+09 0.285387E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.285089E+09 0.580400E+09 0.325468E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.254180E+09 0.523479E+09 0.305215E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.274107E+09 0.560059E+09 0.320228E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.273411E+09 0.557238E+09 0.313854E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.254877E+09 0.526300E+09 0.311588E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.285089E+09 0.580314E+09 0.325468E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.254180E+09 0.523394E+09 0.305215E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.263126E+09 0.539889E+09 0.314987E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.259698E+09 0.530231E+09 0.306773E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.254877E+09 0.526300E+09 0.311588E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.316083E+10 0.647824E+10 0.374076E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.239074E+09 0.490831E+09 0.285387E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.285089E+09 0.580400E+09 0.325468E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11458713.60 55252314.53 8593131.60 0.00 0.00 0.00 0.00 0.00 0.00
February 10411286.40 50239715.38 7785593.60 0.00 0.00 0.00 0.00 0.00 0.00
March 12415161.60 59407610.51 8879054.14 0.00 0.00 0.00 0.00 0.00 0.00
April 11069136.00 53581448.15 8326528.14 0.00 0.00 0.00 0.00 0.00 0.00
May 11936937.60 57325588.52 8736092.87 0.00 0.00 0.00 0.00 0.00 0.00
June 11906611.20 57036904.80 8562221.05 0.00 0.00 0.00 0.00 0.00 0.00
July 11099462.40 53870131.87 8500399.96 0.00 0.00 0.00 0.00 0.00 0.00
August 12415161.60 59398862.52 8879054.14 0.00 0.00 0.00 0.00 0.00 0.00
September 11069136.00 53572700.16 8326528.14 0.00 0.00 0.00 0.00 0.00 0.00
October 11458713.60 55261062.52 8593131.60 0.00 0.00 0.00 0.00 0.00 0.00
November 11309414.40 54272539.48 8369030.14 0.00 0.00 0.00 0.00 0.00 0.00
December 11099462.40 53870131.87 8500399.96 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.137649E+09 0.663089E+09 0.102051E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 10411286.40 50239715.38 7785593.60 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12415161.60 59407610.51 8879054.14 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.415377E+09 0.296725E+09 0.827978E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.377408E+09 0.269806E+09 0.750169E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.450048E+09 0.319041E+09 0.855528E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.401255E+09 0.287752E+09 0.802290E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.432712E+09 0.307860E+09 0.841753E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.431613E+09 0.306309E+09 0.825000E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.402354E+09 0.289303E+09 0.819043E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.450048E+09 0.318994E+09 0.855528E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.401255E+09 0.287705E+09 0.802290E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.415377E+09 0.296772E+09 0.827978E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.409965E+09 0.291464E+09 0.806385E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.402354E+09 0.289303E+09 0.819043E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.498976E+10 0.356103E+10 0.983299E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.377408E+09 0.269806E+09 0.750169E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.450048E+09 0.319041E+09 0.855528E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 28646784.00 55252314.53 34293067.55 0.00 0.00 0.00 0.00 0.00 0.00
February 26028216.00 50239715.38 31070382.70 0.00 0.00 0.00 0.00 0.00 0.00
March 31037904.00 59407610.51 35434113.87 0.00 0.00 0.00 0.00 0.00 0.00
April 27672840.00 53581448.15 33229118.96 0.00 0.00 0.00 0.00 0.00 0.00
May 29842344.00 57325588.52 34863590.71 0.00 0.00 0.00 0.00 0.00 0.00
June 29766528.00 57036904.80 34169711.20 0.00 0.00 0.00 0.00 0.00 0.00
July 27748656.00 53870131.87 33922998.48 0.00 0.00 0.00 0.00 0.00 0.00
August 31037904.00 59398862.52 35434113.87 0.00 0.00 0.00 0.00 0.00 0.00
September 27672840.00 53572700.16 33229118.96 0.00 0.00 0.00 0.00 0.00 0.00
October 28646784.00 55261062.52 34293067.55 0.00 0.00 0.00 0.00 0.00 0.00
November 28273536.00 54272539.48 33398733.96 0.00 0.00 0.00 0.00 0.00 0.00
December 27748656.00 53870131.87 33922998.48 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.344123E+09 0.663089E+09 0.407261E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 26028216.00 50239715.38 31070382.70 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31037904.00 59407610.51 35434113.87 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.213685E+09 0.604024E+09 0.842623E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.194017E+09 0.549226E+09 0.763438E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.231318E+09 0.649450E+09 0.870660E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.206068E+09 0.585758E+09 0.816480E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.222501E+09 0.626689E+09 0.856641E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.221823E+09 0.623533E+09 0.839592E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.206746E+09 0.588914E+09 0.833530E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.231318E+09 0.649354E+09 0.870660E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.206068E+09 0.585662E+09 0.816480E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.213685E+09 0.604119E+09 0.842623E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.211128E+09 0.593313E+09 0.820648E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.206746E+09 0.588914E+09 0.833530E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.256510E+10 0.724895E+10 0.100069E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.194017E+09 0.549226E+09 0.763438E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.231318E+09 0.649450E+09 0.870660E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.976208E+09 0.115052E+10 0.291854E+10 0.257644E+10 0.00 0.00 0.00 11668327.38 21408241.58
February 0.886974E+09 0.104614E+10 0.264427E+10 0.233432E+10 0.00 0.00 0.00 19132399.83 26201910.07
March 0.105769E+10 0.123705E+10 0.301565E+10 0.266217E+10 0.00 0.00 0.00 25117664.63 20073804.79
April 0.943018E+09 0.111573E+10 0.282800E+10 0.249651E+10 0.00 0.00 0.00 33941825.56 2518341.89
May 0.101695E+10 0.119369E+10 0.296710E+10 0.261930E+10 0.00 0.00 0.00 60995855.04 107154.31
June 0.101437E+10 0.118768E+10 0.290805E+10 0.256717E+10 0.00 0.00 0.00 57471953.27 0.00
July 0.945602E+09 0.112174E+10 0.288705E+10 0.254864E+10 0.00 0.00 0.00 47613236.08 0.00
August 0.105769E+10 0.123687E+10 0.301565E+10 0.266217E+10 0.00 0.00 0.00 54589187.47 0.00
September 0.943018E+09 0.111555E+10 0.282800E+10 0.249651E+10 0.00 0.00 0.00 52051468.02 0.00
October 0.976208E+09 0.115070E+10 0.291854E+10 0.257644E+10 0.00 0.00 0.00 47336638.74 92196.67
November 0.963488E+09 0.113012E+10 0.284243E+10 0.250925E+10 0.00 0.00 0.00 31992090.32 11800285.80
December 0.945602E+09 0.112174E+10 0.288705E+10 0.254864E+10 0.00 0.00 0.00 16010384.70 21883120.37
                   
Annual Sum or Average 0.117268E+11 0.138075E+11 0.346603E+11 0.305975E+11 0.00 0.00 0.00 0.457921E+09 0.104085E+09
Minimum of Months 0.886974E+09 0.104614E+10 0.264427E+10 0.233432E+10 0.00 0.00 0.00 11668327.38 0.00
Maximum of Months 0.105769E+10 0.123705E+10 0.301565E+10 0.266217E+10 0.00 0.00 0.00 60995855.04 26201910.07



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.101865E+10 0.120054E+10 0.304544E+10 0.268846E+10 0.00 0.00 0.00 6514881.70 11947135.87
February 0.925538E+09 0.109163E+10 0.275924E+10 0.243581E+10 0.00 0.00 0.00 10680891.81 14624105.06
March 0.110368E+10 0.129083E+10 0.314677E+10 0.277791E+10 0.00 0.00 0.00 14020997.52 11203999.32
April 0.984019E+09 0.116424E+10 0.295095E+10 0.260505E+10 0.00 0.00 0.00 18951205.19 1405608.15
May 0.106116E+10 0.124559E+10 0.309610E+10 0.273319E+10 0.00 0.00 0.00 34073289.05 59806.89
June 0.105847E+10 0.123932E+10 0.303448E+10 0.267879E+10 0.00 0.00 0.00 32165099.09 0.00
July 0.986715E+09 0.117051E+10 0.301257E+10 0.265945E+10 0.00 0.00 0.00 26689869.81 0.00
August 0.110368E+10 0.129064E+10 0.314677E+10 0.277791E+10 0.00 0.00 0.00 30647765.12 0.00
September 0.984019E+09 0.116405E+10 0.295095E+10 0.260505E+10 0.00 0.00 0.00 29237411.34 0.00
October 0.101865E+10 0.120073E+10 0.304544E+10 0.268846E+10 0.00 0.00 0.00 26533732.20 51458.48
November 0.100538E+10 0.117926E+10 0.296601E+10 0.261835E+10 0.00 0.00 0.00 17900154.33 6585417.98
December 0.986715E+09 0.117051E+10 0.301257E+10 0.265945E+10 0.00 0.00 0.00 8938067.07 12212938.30
                   
Annual Sum or Average 0.122367E+11 0.144079E+11 0.361673E+11 0.319279E+11 0.00 0.00 0.00 0.256353E+09 58090470.06
Minimum of Months 0.925538E+09 0.109163E+10 0.275924E+10 0.243581E+10 0.00 0.00 0.00 6514881.70 0.00
Maximum of Months 0.110368E+10 0.129083E+10 0.314677E+10 0.277791E+10 0.00 0.00 0.00 34073289.05 14624105.06



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.101016E+10 0.119054E+10 0.302006E+10 0.266606E+10 0.00 0.00 0.00 0.00 0.00
February 0.917825E+09 0.108253E+10 0.273625E+10 0.241551E+10 0.00 0.00 0.00 0.00 0.00
March 0.109448E+10 0.128008E+10 0.312055E+10 0.275476E+10 0.00 0.00 0.00 0.00 0.00
April 0.975819E+09 0.115454E+10 0.292636E+10 0.258334E+10 0.00 0.00 0.00 0.00 0.00
May 0.105232E+10 0.123521E+10 0.307030E+10 0.271041E+10 0.00 0.00 0.00 0.00 0.00
June 0.104965E+10 0.122899E+10 0.300919E+10 0.265647E+10 0.00 0.00 0.00 0.00 0.00
July 0.978492E+09 0.116076E+10 0.298747E+10 0.263728E+10 0.00 0.00 0.00 0.00 0.00
August 0.109448E+10 0.127989E+10 0.312055E+10 0.275476E+10 0.00 0.00 0.00 0.00 0.00
September 0.975819E+09 0.115435E+10 0.292636E+10 0.258334E+10 0.00 0.00 0.00 0.00 0.00
October 0.101016E+10 0.119073E+10 0.302006E+10 0.266606E+10 0.00 0.00 0.00 0.00 0.00
November 0.997001E+09 0.116943E+10 0.294130E+10 0.259653E+10 0.00 0.00 0.00 0.00 0.00
December 0.978492E+09 0.116076E+10 0.298747E+10 0.263728E+10 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.121347E+11 0.142878E+11 0.358659E+11 0.316618E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.917825E+09 0.108253E+10 0.273625E+10 0.241551E+10 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.109448E+10 0.128008E+10 0.312055E+10 0.275476E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 PACU

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.229197E+09 98226336.94 0.513838E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.208246E+09 89315049.57 0.465550E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.248327E+09 0.105614E+09 0.530935E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.221404E+09 95255907.82 0.497896E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.238762E+09 0.101912E+09 0.522386E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.238155E+09 0.101399E+09 0.511990E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.222011E+09 95769123.32 0.508293E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.248327E+09 0.105598E+09 0.530935E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.221404E+09 95240355.83 0.497896E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.229197E+09 98241888.93 0.513838E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.226210E+09 96484514.63 0.500437E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.222011E+09 95769123.32 0.508293E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.275325E+10 0.117882E+10 0.610229E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.208246E+09 89315049.57 0.465550E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.248327E+09 0.105614E+09 0.530935E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.280102E+09 0.574629E+09 0.335309E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.254498E+09 0.522498E+09 0.303799E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.303482E+09 0.617845E+09 0.346466E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.270579E+09 0.557252E+09 0.324906E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.291792E+09 0.596191E+09 0.340888E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.291050E+09 0.593189E+09 0.334103E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.271320E+09 0.560254E+09 0.331691E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.303482E+09 0.617754E+09 0.346466E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.270579E+09 0.557161E+09 0.324906E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.280102E+09 0.574720E+09 0.335309E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.276452E+09 0.564439E+09 0.326565E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.271320E+09 0.560254E+09 0.331691E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.336476E+10 0.689619E+10 0.398210E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.254498E+09 0.522498E+09 0.303799E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.303482E+09 0.617845E+09 0.346466E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.200547E+09 0.150409E+09 0.599570E+09 0.00 0.00 0.00 0.00 913736.18 2610265.29
February 0.182215E+09 0.136764E+09 0.543226E+09 0.00 0.00 0.00 0.00 1527959.83 3128926.05
March 0.217286E+09 0.161721E+09 0.619520E+09 0.00 0.00 0.00 0.00 2081249.10 2485168.63
April 0.193729E+09 0.145861E+09 0.580969E+09 0.00 0.00 0.00 0.00 3163432.82 421252.64
May 0.208917E+09 0.156053E+09 0.609545E+09 0.00 0.00 0.00 0.00 6323459.64 34755.26
June 0.208386E+09 0.155267E+09 0.597414E+09 0.00 0.00 0.00 0.00 5968763.40 0.00
July 0.194259E+09 0.146646E+09 0.593100E+09 0.00 0.00 0.00 0.00 5031149.96 2.31
August 0.217286E+09 0.161697E+09 0.619520E+09 0.00 0.00 0.00 0.00 5692594.43 15.58
September 0.193729E+09 0.145837E+09 0.580969E+09 0.00 0.00 0.00 0.00 5551864.00 0.00
October 0.200547E+09 0.150433E+09 0.599570E+09 0.00 0.00 0.00 0.00 4771890.18 16977.21
November 0.197934E+09 0.147742E+09 0.583934E+09 0.00 0.00 0.00 0.00 2963649.46 1592674.05
December 0.194259E+09 0.146646E+09 0.593100E+09 0.00 0.00 0.00 0.00 1203343.05 2600725.38
                   
Annual Sum or Average 0.240910E+10 0.180508E+10 0.712044E+10 0.00 0.00 0.00 0.00 45193092.05 12890762.41
Minimum of Months 0.182215E+09 0.136764E+09 0.543226E+09 0.00 0.00 0.00 0.00 913736.18 0.00
Maximum of Months 0.217286E+09 0.161721E+09 0.619520E+09 0.00 0.00 0.00 0.00 6323459.64 3128926.05



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.358650E+09 0.268986E+09 0.107225E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.325866E+09 0.244583E+09 0.971483E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.388586E+09 0.289215E+09 0.110792E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.346457E+09 0.260851E+09 0.103898E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.373618E+09 0.279079E+09 0.109009E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.372669E+09 0.277673E+09 0.106839E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.347406E+09 0.262257E+09 0.106068E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.388586E+09 0.289172E+09 0.110792E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.346457E+09 0.260809E+09 0.103898E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.358650E+09 0.269028E+09 0.107225E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.353977E+09 0.264216E+09 0.104428E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.347406E+09 0.262257E+09 0.106068E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.430833E+10 0.322812E+10 0.127339E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.325866E+09 0.244583E+09 0.971483E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.388586E+09 0.289215E+09 0.110792E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 28646784.00 55252314.53 34293067.55 0.00 0.00 0.00 0.00 1314905.41 3422643.87
February 26028216.00 50239715.38 31070382.70 0.00 0.00 0.00 0.00 2234484.88 4011491.18
March 31037904.00 59407610.51 35434113.87 0.00 0.00 0.00 0.00 3000914.88 3165507.42
April 27672840.00 53581448.15 33229118.96 0.00 0.00 0.00 0.00 4452648.05 455996.64
May 29842344.00 57325588.52 34863590.71 0.00 0.00 0.00 0.00 8920014.54 35173.27
June 29766528.00 57036904.80 34169711.20 0.00 0.00 0.00 0.00 8465222.18 0.00
July 27748656.00 53870131.87 33922998.48 0.00 0.00 0.00 0.00 7037828.85 0.00
August 31037904.00 59398862.52 35434113.87 0.00 0.00 0.00 0.00 7921597.95 0.00
September 27672840.00 53572700.16 33229118.96 0.00 0.00 0.00 0.00 7665994.76 2.55
October 28646784.00 55261062.52 34293067.55 0.00 0.00 0.00 0.00 6571462.43 21860.26
November 28273536.00 54272539.48 33398733.96 0.00 0.00 0.00 0.00 4152886.65 2083599.29
December 27748656.00 53870131.87 33922998.48 0.00 0.00 0.00 0.00 1680482.97 3407666.92
                   
Annual Sum or Average 0.344123E+09 0.663089E+09 0.407261E+09 0.00 0.00 0.00 0.00 63418443.55 16603941.41
Minimum of Months 26028216.00 50239715.38 31070382.70 0.00 0.00 0.00 0.00 1314905.41 0.00
Maximum of Months 31037904.00 59407610.51 35434113.87 0.00 0.00 0.00 0.00 8920014.54 4011491.18



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.604824E+09 0.486016E+09 0.135596E+10 0.00 0.00 0.00 0.00 5070884.84 11877642.66
February 0.549538E+09 0.441923E+09 0.122854E+10 0.00 0.00 0.00 0.00 8541532.28 14279183.30
March 0.655308E+09 0.522567E+09 0.140108E+10 0.00 0.00 0.00 0.00 11522603.95 11475308.22
April 0.584261E+09 0.471318E+09 0.131389E+10 0.00 0.00 0.00 0.00 16638144.72 2189980.78
May 0.630066E+09 0.504253E+09 0.137852E+10 0.00 0.00 0.00 0.00 31588124.22 208320.91
June 0.628466E+09 0.501714E+09 0.135108E+10 0.00 0.00 0.00 0.00 29295734.02 122.96
July 0.585862E+09 0.473858E+09 0.134133E+10 0.00 0.00 0.00 0.00 24632882.37 358.48
August 0.655308E+09 0.522490E+09 0.140108E+10 0.00 0.00 0.00 0.00 28050723.18 2619.58
September 0.584261E+09 0.471241E+09 0.131389E+10 0.00 0.00 0.00 0.00 27484026.91 118.37
October 0.604824E+09 0.486093E+09 0.135596E+10 0.00 0.00 0.00 0.00 23989431.94 92883.50
November 0.596944E+09 0.477397E+09 0.132060E+10 0.00 0.00 0.00 0.00 15520501.18 7135130.91
December 0.585862E+09 0.473858E+09 0.134133E+10 0.00 0.00 0.00 0.00 6592540.07 11982717.67
                   
Annual Sum or Average 0.726553E+10 0.583273E+10 0.161033E+11 0.00 0.00 0.00 0.00 0.228927E+09 59244387.32
Minimum of Months 0.549538E+09 0.441923E+09 0.122854E+10 0.00 0.00 0.00 0.00 5070884.84 118.37
Maximum of Months 0.655308E+09 0.522567E+09 0.140108E+10 0.00 0.00 0.00 0.00 31588124.22 14279183.30



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.162029E+10 0.752273E+09 0.887981E+09 0.00 0.00 0.00 0.00 910166.69 11446959.39
February 0.147218E+10 0.684025E+09 0.804533E+09 0.00 0.00 0.00 0.00 1695119.64 14603290.66
March 0.175554E+10 0.808848E+09 0.917527E+09 0.00 0.00 0.00 0.00 2194378.66 12109521.55
April 0.156521E+10 0.729524E+09 0.860432E+09 0.00 0.00 0.00 0.00 4073715.11 3637751.05
May 0.168791E+10 0.780501E+09 0.902754E+09 0.00 0.00 0.00 0.00 10161042.88 500725.33
June 0.168363E+10 0.776570E+09 0.884787E+09 0.00 0.00 0.00 0.00 11378883.23 61995.48
July 0.156949E+10 0.733454E+09 0.878399E+09 0.00 0.00 0.00 0.00 9729007.92 64561.13
August 0.175554E+10 0.808729E+09 0.917527E+09 0.00 0.00 0.00 0.00 11220513.36 31978.69
September 0.156521E+10 0.729404E+09 0.860432E+09 0.00 0.00 0.00 0.00 10401459.25 56849.26
October 0.162029E+10 0.752392E+09 0.887981E+09 0.00 0.00 0.00 0.00 7463393.36 383234.52
November 0.159918E+10 0.738933E+09 0.864824E+09 0.00 0.00 0.00 0.00 3966710.78 7961755.89
December 0.156949E+10 0.733454E+09 0.878399E+09 0.00 0.00 0.00 0.00 1238370.16 11521286.03
                   
Annual Sum or Average 0.194640E+11 0.902811E+10 0.105456E+11 0.00 0.00 0.00 0.00 74432761.04 62379908.96
Minimum of Months 0.147218E+10 0.684025E+09 0.804533E+09 0.00 0.00 0.00 0.00 910166.69 31978.69
Maximum of Months 0.175554E+10 0.808848E+09 0.917527E+09 0.00 0.00 0.00 0.00 11378883.23 14603290.66



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 67903488.00 0.139304E+09 81287018.65 0.00 0.00 0.00 0.00 0.00 0.00
February 61696512.00 0.126666E+09 73648085.69 0.00 0.00 0.00 0.00 0.00 0.00
March 73571328.00 0.149781E+09 83991712.62 0.00 0.00 0.00 0.00 0.00 0.00
April 65594880.00 0.135091E+09 78765074.28 0.00 0.00 0.00 0.00 0.00 0.00
May 70737408.00 0.144531E+09 82639365.64 0.00 0.00 0.00 0.00 0.00 0.00
June 70557696.00 0.143803E+09 80994619.30 0.00 0.00 0.00 0.00 0.00 0.00
July 65774592.00 0.135819E+09 80409820.61 0.00 0.00 0.00 0.00 0.00 0.00
August 73571328.00 0.149758E+09 83991712.62 0.00 0.00 0.00 0.00 0.00 0.00
September 65594880.00 0.135069E+09 78765074.28 0.00 0.00 0.00 0.00 0.00 0.00
October 67903488.00 0.139326E+09 81287018.65 0.00 0.00 0.00 0.00 0.00 0.00
November 67018752.00 0.136834E+09 79167123.38 0.00 0.00 0.00 0.00 0.00 0.00
December 65774592.00 0.135819E+09 80409820.61 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.815699E+09 0.167180E+10 0.965356E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 61696512.00 0.126666E+09 73648085.69 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 73571328.00 0.149781E+09 83991712.62 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.114598E+10 0.491132E+09 0.256919E+10 0.00 0.00 0.00 0.00 8064298.18 31029604.18
February 0.104123E+10 0.446575E+09 0.232775E+10 0.00 0.00 0.00 0.00 15135661.49 36442410.78
March 0.124164E+10 0.528068E+09 0.265468E+10 0.00 0.00 0.00 0.00 22112048.20 28060667.79
April 0.110702E+10 0.476280E+09 0.248948E+10 0.00 0.00 0.00 0.00 35204885.80 4864053.63
May 0.119381E+10 0.509561E+09 0.261193E+10 0.00 0.00 0.00 0.00 70550577.82 410674.14
June 0.119078E+10 0.506995E+09 0.255995E+10 0.00 0.00 0.00 0.00 66104989.75 0.00
July 0.111005E+10 0.478846E+09 0.254146E+10 0.00 0.00 0.00 0.00 55722540.81 271.61
August 0.124164E+10 0.527990E+09 0.265468E+10 0.00 0.00 0.00 0.00 62409886.73 4450.67
September 0.110702E+10 0.476202E+09 0.248948E+10 0.00 0.00 0.00 0.00 59399335.99 590.85
October 0.114598E+10 0.491209E+09 0.256919E+10 0.00 0.00 0.00 0.00 48671088.11 300312.79
November 0.113105E+10 0.482423E+09 0.250219E+10 0.00 0.00 0.00 0.00 29092713.50 18936893.94
December 0.111005E+10 0.478846E+09 0.254146E+10 0.00 0.00 0.00 0.00 10736816.41 30700469.43
                   
Annual Sum or Average 0.137663E+11 0.589412E+10 0.305114E+11 0.00 0.00 0.00 0.00 0.483205E+09 0.150750E+09
Minimum of Months 0.104123E+10 0.446575E+09 0.232775E+10 0.00 0.00 0.00 0.00 8064298.18 0.00
Maximum of Months 0.124164E+10 0.528068E+09 0.265468E+10 0.00 0.00 0.00 0.00 70550577.82 36442410.78



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 52646915.29 0.148817E+09 0.207603E+09 0.00 0.00 0.00 0.00 565442.73 5467485.18
February 47801239.74 0.135316E+09 0.188093E+09 0.00 0.00 0.00 0.00 971504.43 6700593.56
March 56991314.06 0.160009E+09 0.214510E+09 0.00 0.00 0.00 0.00 1351097.09 5354858.60
April 50770340.68 0.144317E+09 0.201162E+09 0.00 0.00 0.00 0.00 2577386.04 1225311.44
May 54819114.68 0.154402E+09 0.211057E+09 0.00 0.00 0.00 0.00 6444677.06 111003.67
June 54652022.42 0.153624E+09 0.206856E+09 0.00 0.00 0.00 0.00 6859770.07 73.40
July 50937432.94 0.145095E+09 0.205362E+09 0.00 0.00 0.00 0.00 5801196.28 6554.87
August 56991314.06 0.159986E+09 0.214510E+09 0.00 0.00 0.00 0.00 6624135.69 3389.93
September 50770340.68 0.144294E+09 0.201162E+09 0.00 0.00 0.00 0.00 6175394.64 1817.81
October 52646915.29 0.148841E+09 0.207603E+09 0.00 0.00 0.00 0.00 4661265.25 95114.92
November 52017106.00 0.146179E+09 0.202189E+09 0.00 0.00 0.00 0.00 2517074.46 3639144.37
December 50937432.94 0.145095E+09 0.205362E+09 0.00 0.00 0.00 0.00 758906.92 5476598.55
                   
Annual Sum or Average 0.631981E+09 0.178597E+10 0.246547E+10 0.00 0.00 0.00 0.00 45307850.66 28081946.30
Minimum of Months 47801239.74 0.135316E+09 0.188093E+09 0.00 0.00 0.00 0.00 565442.73 73.40
Maximum of Months 56991314.06 0.160009E+09 0.214510E+09 0.00 0.00 0.00 0.00 6859770.07 6700593.56



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 SCRUB

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 44561664.00 91418282.89 53344630.77 0.00 0.00 0.00 0.00 0.00 0.00
February 40488336.00 83124635.63 48331578.69 0.00 0.00 0.00 0.00 0.00 0.00
March 48281184.00 98293470.41 55119587.01 0.00 0.00 0.00 0.00 0.00 0.00
April 43046640.00 88653733.81 51689604.01 0.00 0.00 0.00 0.00 0.00 0.00
May 46421424.00 94848639.61 54232108.89 0.00 0.00 0.00 0.00 0.00 0.00
June 46303488.00 94370995.01 53152743.61 0.00 0.00 0.00 0.00 0.00 0.00
July 43164576.00 89131378.41 52768969.29 0.00 0.00 0.00 0.00 0.00 0.00
August 48281184.00 98278996.33 55119587.01 0.00 0.00 0.00 0.00 0.00 0.00
September 43046640.00 88639259.73 51689604.01 0.00 0.00 0.00 0.00 0.00 0.00
October 44561664.00 91432756.97 53344630.77 0.00 0.00 0.00 0.00 0.00 0.00
November 43981056.00 89797186.05 51953448.85 0.00 0.00 0.00 0.00 0.00 0.00
December 43164576.00 89131378.41 52768969.29 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.535302E+09 0.109712E+10 0.633515E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 40488336.00 83124635.63 48331578.69 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 48281184.00 98293470.41 55119587.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 SOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.267396E+09 0.214870E+09 0.399714E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.242954E+09 0.195377E+09 0.362151E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.289715E+09 0.231030E+09 0.413013E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.258305E+09 0.208372E+09 0.387312E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.278556E+09 0.222933E+09 0.406364E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.277848E+09 0.221810E+09 0.398276E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.259013E+09 0.209495E+09 0.395400E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.289715E+09 0.230996E+09 0.413013E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.258305E+09 0.208338E+09 0.387312E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.267396E+09 0.214904E+09 0.399714E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.263912E+09 0.211060E+09 0.389289E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.259013E+09 0.209495E+09 0.395400E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.321213E+10 0.257868E+10 0.474696E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.242954E+09 0.195377E+09 0.362151E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.289715E+09 0.231030E+09 0.413013E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.118843E+09 95497827.58 0.177650E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.107979E+09 86834075.97 0.160956E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.128762E+09 0.102680E+09 0.183561E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.114802E+09 92609910.38 0.172139E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.123803E+09 99081264.11 0.180606E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.123488E+09 98582304.60 0.177011E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.115117E+09 93108869.89 0.175733E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.128762E+09 0.102665E+09 0.183561E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.114802E+09 92594790.39 0.172139E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.118843E+09 95512947.57 0.177650E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.117294E+09 93804389.22 0.173017E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.115117E+09 93108869.89 0.175733E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.142761E+10 0.114608E+10 0.210976E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.107979E+09 86834075.97 0.160956E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.128762E+09 0.102680E+09 0.183561E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.381994E+09 0.306957E+09 0.571019E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.347077E+09 0.279110E+09 0.517358E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.413879E+09 0.330042E+09 0.590019E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.369007E+09 0.297675E+09 0.553303E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.397937E+09 0.318475E+09 0.580519E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.396926E+09 0.316872E+09 0.568965E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.370018E+09 0.299279E+09 0.564857E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.413879E+09 0.329994E+09 0.590019E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.369007E+09 0.297626E+09 0.553303E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.381994E+09 0.307006E+09 0.571019E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.377017E+09 0.301514E+09 0.556128E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.370018E+09 0.299279E+09 0.564857E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.458875E+10 0.368383E+10 0.678137E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.347077E+09 0.279110E+09 0.517358E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.413879E+09 0.330042E+09 0.590019E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.636657E+09 0.272851E+09 0.142733E+10 0.00 0.00 0.00 0.00 5833727.01 25381612.82
February 0.578461E+09 0.248097E+09 0.129319E+10 0.00 0.00 0.00 0.00 10704434.41 30033090.76
March 0.689798E+09 0.293371E+09 0.147482E+10 0.00 0.00 0.00 0.00 15387574.46 23837072.62
April 0.615012E+09 0.264600E+09 0.138304E+10 0.00 0.00 0.00 0.00 24857431.88 4756785.06
May 0.663228E+09 0.283089E+09 0.145107E+10 0.00 0.00 0.00 0.00 51769305.16 434993.88
June 0.661543E+09 0.281664E+09 0.142219E+10 0.00 0.00 0.00 0.00 49720502.97 5250.40
July 0.616697E+09 0.266025E+09 0.141192E+10 0.00 0.00 0.00 0.00 41553154.16 2798.50
August 0.689798E+09 0.293328E+09 0.147482E+10 0.00 0.00 0.00 0.00 46347402.88 10425.97
September 0.615012E+09 0.264557E+09 0.138304E+10 0.00 0.00 0.00 0.00 43919421.91 5960.39
October 0.636657E+09 0.272894E+09 0.142733E+10 0.00 0.00 0.00 0.00 35281832.62 364797.78
November 0.628362E+09 0.268013E+09 0.139010E+10 0.00 0.00 0.00 0.00 21000783.42 15799947.32
December 0.616697E+09 0.266025E+09 0.141192E+10 0.00 0.00 0.00 0.00 7558955.23 25357548.14
                   
Annual Sum or Average 0.764792E+10 0.327451E+10 0.169508E+11 0.00 0.00 0.00 0.00 0.353935E+09 0.125990E+09
Minimum of Months 0.578461E+09 0.248097E+09 0.129319E+10 0.00 0.00 0.00 0.00 5833727.01 2798.50
Maximum of Months 0.689798E+09 0.293371E+09 0.147482E+10 0.00 0.00 0.00 0.00 51769305.16 30033090.76



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.326786E+09 0.670401E+09 0.391194E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.296914E+09 0.609581E+09 0.354432E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.354062E+09 0.720819E+09 0.404211E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.315675E+09 0.650127E+09 0.379057E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.340424E+09 0.695557E+09 0.397702E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.339559E+09 0.692054E+09 0.389787E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.316540E+09 0.653630E+09 0.386973E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.354062E+09 0.720713E+09 0.404211E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.315675E+09 0.650021E+09 0.379057E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.326786E+09 0.670507E+09 0.391194E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.322528E+09 0.658513E+09 0.380992E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.316540E+09 0.653630E+09 0.386973E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.392555E+10 0.804555E+10 0.464578E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.296914E+09 0.609581E+09 0.354432E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.354062E+09 0.720819E+09 0.404211E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 84030566.40 0.405184E+09 63016404.11 0.00 0.00 0.00 0.00 0.00 0.00
February 76349433.60 0.368425E+09 57094448.86 0.00 0.00 0.00 0.00 0.00 0.00
March 91044518.40 0.435656E+09 65113172.95 0.00 0.00 0.00 0.00 0.00 0.00
April 81173664.00 0.392931E+09 61061308.83 0.00 0.00 0.00 0.00 0.00 0.00
May 87537542.40 0.420388E+09 64064788.53 0.00 0.00 0.00 0.00 0.00 0.00
June 87315148.80 0.418271E+09 62789726.39 0.00 0.00 0.00 0.00 0.00 0.00
July 81396057.60 0.395048E+09 62336370.97 0.00 0.00 0.00 0.00 0.00 0.00
August 91044518.40 0.435592E+09 65113172.95 0.00 0.00 0.00 0.00 0.00 0.00
September 81173664.00 0.392866E+09 61061308.83 0.00 0.00 0.00 0.00 0.00 0.00
October 84030566.40 0.405248E+09 63016404.11 0.00 0.00 0.00 0.00 0.00 0.00
November 82935705.60 0.397999E+09 61372990.69 0.00 0.00 0.00 0.00 0.00 0.00
December 81396057.60 0.395048E+09 62336370.97 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.100943E+10 0.486265E+10 0.748376E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 76349433.60 0.368425E+09 57094448.86 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 91044518.40 0.435656E+09 65113172.95 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.195223E+09 0.941336E+09 0.146402E+09 0.00 0.00 0.00 0.00 8883142.82 30829338.53
February 0.177377E+09 0.855936E+09 0.132644E+09 0.00 0.00 0.00 0.00 13524583.25 36858670.18
March 0.211518E+09 0.101213E+10 0.151273E+09 0.00 0.00 0.00 0.00 16660129.43 30426763.10
April 0.188585E+09 0.912869E+09 0.141860E+09 0.00 0.00 0.00 0.00 22501543.76 7173793.36
May 0.203370E+09 0.976658E+09 0.148837E+09 0.00 0.00 0.00 0.00 50592153.59 843833.58
June 0.202853E+09 0.971740E+09 0.145875E+09 0.00 0.00 0.00 0.00 53026343.76 139409.11
July 0.189102E+09 0.917787E+09 0.144822E+09 0.00 0.00 0.00 0.00 42559091.28 226580.34
August 0.211518E+09 0.101198E+10 0.151273E+09 0.00 0.00 0.00 0.00 52322024.61 90432.86
September 0.188585E+09 0.912720E+09 0.141860E+09 0.00 0.00 0.00 0.00 49688681.29 71907.18
October 0.195223E+09 0.941485E+09 0.146402E+09 0.00 0.00 0.00 0.00 42485621.37 520217.74
November 0.192679E+09 0.924643E+09 0.142584E+09 0.00 0.00 0.00 0.00 26515708.31 21007394.59
December 0.189102E+09 0.917787E+09 0.144822E+09 0.00 0.00 0.00 0.00 10667859.89 31344394.72
                   
Annual Sum or Average 0.234513E+10 0.112971E+11 0.173865E+10 0.00 0.00 0.00 0.00 0.389427E+09 0.159533E+09
Minimum of Months 0.177377E+09 0.855936E+09 0.132644E+09 0.00 0.00 0.00 0.00 8883142.82 71907.18
Maximum of Months 0.211518E+09 0.101213E+10 0.151273E+09 0.00 0.00 0.00 0.00 53026343.76 36858670.18



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.103977E+09 0.213309E+09 0.124471E+09 0.00 0.00 0.00 0.00 1404160.28 8924237.95
February 94472784.00 0.193957E+09 0.112774E+09 0.00 0.00 0.00 0.00 2436574.27 10620203.39
March 0.112656E+09 0.229351E+09 0.128612E+09 0.00 0.00 0.00 0.00 3197658.36 8625939.76
April 0.100442E+09 0.206859E+09 0.120609E+09 0.00 0.00 0.00 0.00 5231420.39 1977173.09
May 0.108317E+09 0.221313E+09 0.126542E+09 0.00 0.00 0.00 0.00 12536625.83 181136.13
June 0.108041E+09 0.220199E+09 0.124023E+09 0.00 0.00 0.00 0.00 12993223.22 2449.87
July 0.100717E+09 0.207973E+09 0.123128E+09 0.00 0.00 0.00 0.00 10543093.57 26837.20
August 0.112656E+09 0.229318E+09 0.128612E+09 0.00 0.00 0.00 0.00 12623088.31 8476.06
September 0.100442E+09 0.206825E+09 0.120609E+09 0.00 0.00 0.00 0.00 11753258.45 7429.30
October 0.103977E+09 0.213343E+09 0.124471E+09 0.00 0.00 0.00 0.00 9544895.50 139511.59
November 0.102622E+09 0.209527E+09 0.121225E+09 0.00 0.00 0.00 0.00 5596173.87 5691571.33
December 0.100717E+09 0.207973E+09 0.123128E+09 0.00 0.00 0.00 0.00 2050425.30 8711386.36
                   
Annual Sum or Average 0.124904E+10 0.255995E+10 0.147820E+10 0.00 0.00 0.00 0.00 89910597.34 44916352.04
Minimum of Months 94472784.00 0.193957E+09 0.112774E+09 0.00 0.00 0.00 0.00 1404160.28 2449.87
Maximum of Months 0.112656E+09 0.229351E+09 0.128612E+09 0.00 0.00 0.00 0.00 12993223.22 10620203.39



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.135807E+09 0.278608E+09 0.162574E+09 0.00 0.00 0.00 0.00 2424423.56 8007842.17
February 0.123393E+09 0.253332E+09 0.147296E+09 0.00 0.00 0.00 0.00 3816437.43 9558881.81
March 0.147143E+09 0.299561E+09 0.167984E+09 0.00 0.00 0.00 0.00 4680537.04 7942218.02
April 0.131190E+09 0.270183E+09 0.157530E+09 0.00 0.00 0.00 0.00 6547744.17 1770956.99
May 0.141475E+09 0.289063E+09 0.165279E+09 0.00 0.00 0.00 0.00 14853279.94 184692.45
June 0.141115E+09 0.287607E+09 0.161989E+09 0.00 0.00 0.00 0.00 15120825.97 9859.92
July 0.131549E+09 0.271638E+09 0.160820E+09 0.00 0.00 0.00 0.00 12081406.98 26932.60
August 0.147143E+09 0.299517E+09 0.167984E+09 0.00 0.00 0.00 0.00 14788651.32 9525.45
September 0.131190E+09 0.270139E+09 0.157530E+09 0.00 0.00 0.00 0.00 14059383.78 9151.47
October 0.135807E+09 0.278652E+09 0.162574E+09 0.00 0.00 0.00 0.00 12159654.32 99967.92
November 0.134038E+09 0.273668E+09 0.158334E+09 0.00 0.00 0.00 0.00 7540429.72 5177210.34
December 0.131549E+09 0.271638E+09 0.160820E+09 0.00 0.00 0.00 0.00 3051957.37 8023556.27
                   
Annual Sum or Average 0.163140E+10 0.334361E+10 0.193071E+10 0.00 0.00 0.00 0.00 0.111125E+09 40820795.41
Minimum of Months 0.123393E+09 0.253332E+09 0.147296E+09 0.00 0.00 0.00 0.00 2424423.56 9151.47
Maximum of Months 0.147143E+09 0.299561E+09 0.167984E+09 0.00 0.00 0.00 0.00 15120825.97 9558881.81



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 8912332.80 42974022.41 6683582.04 0.00 0.00 0.00 0.00 0.00 0.00
February 8097667.20 39075334.19 6055493.62 0.00 0.00 0.00 0.00 0.00 0.00
March 9656236.80 46205919.28 6905967.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8609328.00 41674459.67 6476222.71 0.00 0.00 0.00 0.00 0.00 0.00
May 9284284.80 44586568.85 6794774.73 0.00 0.00 0.00 0.00 0.00 0.00
June 9260697.60 44362037.07 6659540.38 0.00 0.00 0.00 0.00 0.00 0.00
July 8632915.20 41898991.45 6611457.06 0.00 0.00 0.00 0.00 0.00 0.00
August 9656236.80 46199115.29 6905967.42 0.00 0.00 0.00 0.00 0.00 0.00
September 8609328.00 41667655.68 6476222.71 0.00 0.00 0.00 0.00 0.00 0.00
October 8912332.80 42980826.41 6683582.04 0.00 0.00 0.00 0.00 0.00 0.00
November 8796211.20 42211975.15 6509279.99 0.00 0.00 0.00 0.00 0.00 0.00
December 8632915.20 41898991.45 6611457.06 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.107060E+09 0.515736E+09 79373547.16 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 8097667.20 39075334.19 6055493.62 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9656236.80 46205919.28 6905967.42 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 76391424.00 0.368349E+09 57287596.84 0.00 0.00 0.00 0.00 1815802.88 11372132.06
February 69408576.00 0.334931E+09 51904005.23 0.00 0.00 0.00 0.00 3080867.93 13545866.83
March 82767744.00 0.396051E+09 59193748.89 0.00 0.00 0.00 0.00 4007144.75 11088779.65
April 73794240.00 0.357210E+09 55510238.85 0.00 0.00 0.00 0.00 6493345.28 2639168.23
May 79579584.00 0.382171E+09 58240672.87 0.00 0.00 0.00 0.00 15558377.66 281380.65
June 79377408.00 0.380246E+09 57081526.35 0.00 0.00 0.00 0.00 16372586.36 14239.17
July 73996416.00 0.359134E+09 56669385.36 0.00 0.00 0.00 0.00 13266597.23 47246.55
August 82767744.00 0.395992E+09 59193748.89 0.00 0.00 0.00 0.00 16057646.22 16255.46
September 73794240.00 0.357151E+09 55510238.85 0.00 0.00 0.00 0.00 14924292.50 16482.74
October 76391424.00 0.368407E+09 57287596.84 0.00 0.00 0.00 0.00 11998784.33 206172.30
November 75396096.00 0.361817E+09 55793585.77 0.00 0.00 0.00 0.00 7069334.98 7549844.07
December 73996416.00 0.359134E+09 56669385.36 0.00 0.00 0.00 0.00 2536840.64 11011091.96
                   
Annual Sum or Average 0.917661E+09 0.442059E+10 0.680342E+09 0.00 0.00 0.00 0.00 0.113182E+09 57788659.68
Minimum of Months 69408576.00 0.334931E+09 51904005.23 0.00 0.00 0.00 0.00 1815802.88 14239.17
Maximum of Months 82767744.00 0.396051E+09 59193748.89 0.00 0.00 0.00 0.00 16372586.36 13545866.83



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 38195712.00 78358528.19 45724037.20 0.00 0.00 0.00 0.00 0.222424E+09 0.344178E+09
February 34704288.00 71249687.69 41427129.03 0.00 0.00 0.00 0.00 0.370589E+09 0.139486E+09
March 41383872.00 84251546.07 47245430.53 0.00 0.00 0.00 0.00 0.403800E+09 0.216494E+09
April 36897120.00 75988914.69 44305440.73 0.00 0.00 0.00 0.00 0.557983E+09 31246126.38
May 39789792.00 81298833.95 46484733.87 0.00 0.00 0.00 0.00 0.908547E+09 1176223.79
June 39688704.00 80889424.29 45559562.25 0.00 0.00 0.00 0.00 0.990356E+09 45458.46
July 36998208.00 76398324.35 45230612.34 0.00 0.00 0.00 0.00 0.102058E+10 192171.96
August 41383872.00 84239139.71 47245430.53 0.00 0.00 0.00 0.00 0.110786E+10 47097.00
September 36897120.00 75976508.34 44305440.73 0.00 0.00 0.00 0.00 0.897119E+09 9565.48
October 38195712.00 78370934.55 45724037.20 0.00 0.00 0.00 0.00 0.819226E+09 909897.08
November 37698048.00 76969016.61 44531593.79 0.00 0.00 0.00 0.00 0.582489E+09 60915262.08
December 36998208.00 76398324.35 45230612.34 0.00 0.00 0.00 0.00 0.213545E+09 0.320962E+09
                   
Annual Sum or Average 0.458831E+09 0.940389E+09 0.543014E+09 0.00 0.00 0.00 0.00 0.809451E+10 0.111566E+10
Minimum of Months 34704288.00 71249687.69 41427129.03 0.00 0.00 0.00 0.00 0.213545E+09 9565.48
Maximum of Months 41383872.00 84251546.07 47245430.53 0.00 0.00 0.00 0.00 0.110786E+10 0.344178E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.131738E+10 0.496589E+09 0.532704E+09 0.00 0.00 0.00 0.00 3800896.05 41434309.60
February 0.119363E+10 0.451537E+09 0.482643E+09 0.00 0.00 0.00 0.00 7428324.94 52277604.09
March 0.142698E+10 0.533935E+09 0.550429E+09 0.00 0.00 0.00 0.00 10297697.86 43991939.38
April 0.126295E+10 0.481572E+09 0.516177E+09 0.00 0.00 0.00 0.00 18763335.00 13587563.69
May 0.137218E+10 0.515223E+09 0.541566E+09 0.00 0.00 0.00 0.00 44947852.13 2414414.93
June 0.136746E+10 0.512628E+09 0.530788E+09 0.00 0.00 0.00 0.00 50324856.14 262180.91
July 0.126766E+10 0.484166E+09 0.526955E+09 0.00 0.00 0.00 0.00 41889530.83 501408.22
August 0.142698E+10 0.533856E+09 0.550429E+09 0.00 0.00 0.00 0.00 49847125.33 206333.84
September 0.126295E+10 0.481493E+09 0.516177E+09 0.00 0.00 0.00 0.00 45359022.75 542467.09
October 0.131738E+10 0.496667E+09 0.532704E+09 0.00 0.00 0.00 0.00 32946968.39 1800525.30
November 0.130758E+10 0.487783E+09 0.518811E+09 0.00 0.00 0.00 0.00 17333119.69 28394681.80
December 0.126766E+10 0.484166E+09 0.526955E+09 0.00 0.00 0.00 0.00 5622839.92 40972592.68
                   
Annual Sum or Average 0.157908E+11 0.595961E+10 0.632634E+10 0.00 0.00 0.00 0.00 0.328562E+09 0.226386E+09
Minimum of Months 0.119363E+10 0.451537E+09 0.482643E+09 0.00 0.00 0.00 0.00 3800896.05 206333.84
Maximum of Months 0.142698E+10 0.533935E+09 0.550429E+09 0.00 0.00 0.00 0.00 50324856.14 52277604.09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 33951744.00 65484224.63 40643588.63 0.00 0.00 0.00 0.00 0.00 0.00
February 30848256.00 59543366.38 36824114.70 0.00 0.00 0.00 0.00 0.00 0.00
March 36785664.00 70409019.86 41995938.25 0.00 0.00 0.00 0.00 0.00 0.00
April 32797440.00 63503938.54 39382613.98 0.00 0.00 0.00 0.00 0.00 0.00
May 35368704.00 67941438.25 41319763.44 0.00 0.00 0.00 0.00 0.00 0.00
June 35278848.00 67599294.58 40497388.67 0.00 0.00 0.00 0.00 0.00 0.00
July 32887296.00 63846082.21 40204988.75 0.00 0.00 0.00 0.00 0.00 0.00
August 36785664.00 70398651.87 41995938.25 0.00 0.00 0.00 0.00 0.00 0.00
September 32797440.00 63493570.55 39382613.98 0.00 0.00 0.00 0.00 0.00 0.00
October 33951744.00 65494592.62 40643588.63 0.00 0.00 0.00 0.00 0.00 0.00
November 33509376.00 64323009.75 39583638.92 0.00 0.00 0.00 0.00 0.00 0.00
December 32887296.00 63846082.21 40204988.75 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.407849E+09 0.785883E+09 0.482679E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 30848256.00 59543366.38 36824114.70 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 36785664.00 70409019.86 41995938.25 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 30968773.70 87539675.28 0.122119E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 28118376.32 79597902.97 0.110643E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 33524302.39 94123168.91 0.126183E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 29864906.28 84892417.85 0.118330E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 32246538.05 90824492.11 0.124151E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 32148248.48 90367112.55 0.121680E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 29963195.84 85349797.40 0.120801E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 33524302.39 94109308.93 0.126183E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 29864906.28 84878557.86 0.118330E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 30968773.70 87553535.27 0.122119E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 30598297.65 85987356.79 0.118934E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 29963195.84 85349797.40 0.120801E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.371754E+09 0.105057E+10 0.145028E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 28118376.32 79597902.97 0.110643E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 33524302.39 94123168.91 0.126183E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.763989E+09 0.613915E+09 0.628042E+09 0.00 0.00 0.00 0.00 5715560.22 42815509.93
February 0.694153E+09 0.558219E+09 0.569022E+09 0.00 0.00 0.00 0.00 9068558.40 55751975.80
March 0.827758E+09 0.660085E+09 0.648939E+09 0.00 0.00 0.00 0.00 12434707.97 49868978.46
April 0.738014E+09 0.595349E+09 0.608557E+09 0.00 0.00 0.00 0.00 21309584.68 16910983.03
May 0.795873E+09 0.636951E+09 0.638490E+09 0.00 0.00 0.00 0.00 50348714.75 2922780.93
June 0.793851E+09 0.633743E+09 0.625783E+09 0.00 0.00 0.00 0.00 57530660.92 291849.78
July 0.740036E+09 0.598557E+09 0.621264E+09 0.00 0.00 0.00 0.00 47920413.59 502774.87
August 0.827758E+09 0.659987E+09 0.648939E+09 0.00 0.00 0.00 0.00 56106223.54 255301.58
September 0.738014E+09 0.595252E+09 0.608557E+09 0.00 0.00 0.00 0.00 52827357.72 590781.93
October 0.763989E+09 0.614012E+09 0.628042E+09 0.00 0.00 0.00 0.00 39428688.61 2016516.46
November 0.754034E+09 0.603028E+09 0.611663E+09 0.00 0.00 0.00 0.00 21411463.23 29399516.54
December 0.740036E+09 0.598557E+09 0.621264E+09 0.00 0.00 0.00 0.00 7763253.23 43486626.89
                   
Annual Sum or Average 0.917751E+10 0.736766E+10 0.745856E+10 0.00 0.00 0.00 0.00 0.381865E+09 0.244814E+09
Minimum of Months 0.694153E+09 0.558219E+09 0.569022E+09 0.00 0.00 0.00 0.00 5715560.22 255301.58
Maximum of Months 0.827758E+09 0.660085E+09 0.648939E+09 0.00 0.00 0.00 0.00 57530660.92 55751975.80



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.114598E+10 0.920872E+09 0.942063E+09 0.00 0.00 0.00 0.00 3362459.54 19957979.04
February 0.104123E+10 0.837329E+09 0.853533E+09 0.00 0.00 0.00 0.00 5436177.30 25859279.49
March 0.124164E+10 0.990127E+09 0.973408E+09 0.00 0.00 0.00 0.00 7931918.82 21697525.45
April 0.110702E+10 0.893024E+09 0.912835E+09 0.00 0.00 0.00 0.00 13754537.75 6073784.51
May 0.119381E+10 0.955426E+09 0.957736E+09 0.00 0.00 0.00 0.00 29791739.65 810218.37
June 0.119078E+10 0.950615E+09 0.938674E+09 0.00 0.00 0.00 0.00 31697370.25 9295.89
July 0.111005E+10 0.897836E+09 0.931897E+09 0.00 0.00 0.00 0.00 26856392.72 105322.52
August 0.124164E+10 0.989981E+09 0.973408E+09 0.00 0.00 0.00 0.00 30955083.29 47185.37
September 0.110702E+10 0.892878E+09 0.912835E+09 0.00 0.00 0.00 0.00 29336046.16 101492.75
October 0.114598E+10 0.921018E+09 0.942063E+09 0.00 0.00 0.00 0.00 22797900.35 597395.94
November 0.113105E+10 0.904542E+09 0.917495E+09 0.00 0.00 0.00 0.00 12213625.30 13786571.53
December 0.111005E+10 0.897836E+09 0.931897E+09 0.00 0.00 0.00 0.00 4838791.62 20149637.40
                   
Annual Sum or Average 0.137663E+11 0.110515E+11 0.111878E+11 0.00 0.00 0.00 0.00 0.218972E+09 0.109196E+09
Minimum of Months 0.104123E+10 0.837329E+09 0.853533E+09 0.00 0.00 0.00 0.00 3362459.54 9295.89
Maximum of Months 0.124164E+10 0.990127E+09 0.973408E+09 0.00 0.00 0.00 0.00 31697370.25 25859279.49



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.152798E+10 0.122783E+10 0.125608E+10 0.00 0.00 0.00 0.00 4696724.13 25398171.42
February 0.138831E+10 0.111644E+10 0.113804E+10 0.00 0.00 0.00 0.00 7627114.74 32357938.04
March 0.165552E+10 0.132017E+10 0.129788E+10 0.00 0.00 0.00 0.00 11351145.75 26627471.00
April 0.147603E+10 0.119070E+10 0.121711E+10 0.00 0.00 0.00 0.00 19640131.05 6552507.47
May 0.159175E+10 0.127390E+10 0.127698E+10 0.00 0.00 0.00 0.00 42270408.98 711173.49
June 0.158770E+10 0.126749E+10 0.125157E+10 0.00 0.00 0.00 0.00 44079070.26 4487.65
July 0.148007E+10 0.119711E+10 0.124253E+10 0.00 0.00 0.00 0.00 37282805.09 87679.30
August 0.165552E+10 0.131997E+10 0.129788E+10 0.00 0.00 0.00 0.00 42822450.06 21963.56
September 0.147603E+10 0.119050E+10 0.121711E+10 0.00 0.00 0.00 0.00 40582901.70 63120.05
October 0.152798E+10 0.122802E+10 0.125608E+10 0.00 0.00 0.00 0.00 32198381.91 577180.45
November 0.150807E+10 0.120606E+10 0.122333E+10 0.00 0.00 0.00 0.00 17302038.79 17032145.26
December 0.148007E+10 0.119711E+10 0.124253E+10 0.00 0.00 0.00 0.00 6871579.63 25515975.22
                   
Annual Sum or Average 0.183550E+11 0.147353E+11 0.149171E+11 0.00 0.00 0.00 0.00 0.306725E+09 0.134950E+09
Minimum of Months 0.138831E+10 0.111644E+10 0.113804E+10 0.00 0.00 0.00 0.00 4696724.13 4487.65
Maximum of Months 0.165552E+10 0.132017E+10 0.129788E+10 0.00 0.00 0.00 0.00 44079070.26 32357938.04



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.178264E+09 0.143247E+09 0.146543E+09 0.00 0.00 0.00 0.00 807224.16 7225282.70
February 0.161969E+09 0.130251E+09 0.132772E+09 0.00 0.00 0.00 0.00 1452580.52 9008282.31
March 0.193144E+09 0.154020E+09 0.151419E+09 0.00 0.00 0.00 0.00 2236233.86 7365813.86
April 0.172203E+09 0.138915E+09 0.141996E+09 0.00 0.00 0.00 0.00 4171115.34 1884362.91
May 0.185704E+09 0.148622E+09 0.148981E+09 0.00 0.00 0.00 0.00 9700332.16 221990.17
June 0.185232E+09 0.147873E+09 0.146016E+09 0.00 0.00 0.00 0.00 10444506.38 4935.64
July 0.172675E+09 0.139663E+09 0.144962E+09 0.00 0.00 0.00 0.00 8802366.01 37210.25
August 0.193144E+09 0.153997E+09 0.151419E+09 0.00 0.00 0.00 0.00 10194803.17 13505.79
September 0.172203E+09 0.138892E+09 0.141996E+09 0.00 0.00 0.00 0.00 9383908.19 26243.07
October 0.178264E+09 0.143269E+09 0.146543E+09 0.00 0.00 0.00 0.00 6993923.23 195496.57
November 0.175941E+09 0.140707E+09 0.142721E+09 0.00 0.00 0.00 0.00 3652548.20 4883895.50
December 0.172675E+09 0.139663E+09 0.144962E+09 0.00 0.00 0.00 0.00 1186100.43 7164602.11
                   
Annual Sum or Average 0.214142E+10 0.171912E+10 0.174033E+10 0.00 0.00 0.00 0.00 69025641.65 38031620.89
Minimum of Months 0.161969E+09 0.130251E+09 0.132772E+09 0.00 0.00 0.00 0.00 807224.16 4935.64
Maximum of Months 0.193144E+09 0.154020E+09 0.151419E+09 0.00 0.00 0.00 0.00 10444506.38 9008282.31



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.742767E+09 0.596861E+09 0.610596E+09 0.00 0.00 0.00 0.00 4605555.12 24058344.69
February 0.674871E+09 0.542713E+09 0.553216E+09 0.00 0.00 0.00 0.00 7441956.12 31596121.17
March 0.804765E+09 0.641749E+09 0.630913E+09 0.00 0.00 0.00 0.00 9746376.42 27657610.08
April 0.717514E+09 0.578812E+09 0.591652E+09 0.00 0.00 0.00 0.00 15542541.09 9572274.62
May 0.773766E+09 0.619258E+09 0.620755E+09 0.00 0.00 0.00 0.00 33602696.98 2080673.78
June 0.771800E+09 0.616139E+09 0.608400E+09 0.00 0.00 0.00 0.00 36792303.02 337853.85
July 0.719480E+09 0.581930E+09 0.604007E+09 0.00 0.00 0.00 0.00 30404678.76 411548.27
August 0.804765E+09 0.641654E+09 0.630913E+09 0.00 0.00 0.00 0.00 36784374.05 198994.71
September 0.717514E+09 0.578717E+09 0.591652E+09 0.00 0.00 0.00 0.00 35118863.53 408547.79
October 0.742767E+09 0.596956E+09 0.610596E+09 0.00 0.00 0.00 0.00 27716641.04 1096958.61
November 0.733089E+09 0.586277E+09 0.594672E+09 0.00 0.00 0.00 0.00 15675379.83 17041811.48
December 0.719480E+09 0.581930E+09 0.604007E+09 0.00 0.00 0.00 0.00 6687364.71 23795774.34
                   
Annual Sum or Average 0.892258E+10 0.716300E+10 0.725138E+10 0.00 0.00 0.00 0.00 0.260119E+09 0.138257E+09
Minimum of Months 0.674871E+09 0.542713E+09 0.553216E+09 0.00 0.00 0.00 0.00 4605555.12 198994.71
Maximum of Months 0.804765E+09 0.641749E+09 0.630913E+09 0.00 0.00 0.00 0.00 36792303.02 31596121.17



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.477493E+09 0.383697E+09 0.392526E+09 0.00 0.00 0.00 0.00 3348878.43 13498663.21
February 0.433846E+09 0.348887E+09 0.355639E+09 0.00 0.00 0.00 0.00 5183696.43 17497204.70
March 0.517349E+09 0.412553E+09 0.405587E+09 0.00 0.00 0.00 0.00 6945995.97 14962789.80
April 0.461259E+09 0.372093E+09 0.380348E+09 0.00 0.00 0.00 0.00 11025032.33 4474728.48
May 0.497421E+09 0.398094E+09 0.399056E+09 0.00 0.00 0.00 0.00 22487035.62 762910.86
June 0.496157E+09 0.396090E+09 0.391114E+09 0.00 0.00 0.00 0.00 23937883.70 51958.24
July 0.462523E+09 0.374098E+09 0.388290E+09 0.00 0.00 0.00 0.00 20214771.64 124603.95
August 0.517349E+09 0.412492E+09 0.405587E+09 0.00 0.00 0.00 0.00 24007738.60 54006.12
September 0.461259E+09 0.372033E+09 0.380348E+09 0.00 0.00 0.00 0.00 23232991.69 96082.92
October 0.477493E+09 0.383757E+09 0.392526E+09 0.00 0.00 0.00 0.00 19010938.99 389009.97
November 0.471271E+09 0.376893E+09 0.382289E+09 0.00 0.00 0.00 0.00 10889721.41 9227460.56
December 0.462523E+09 0.374098E+09 0.388290E+09 0.00 0.00 0.00 0.00 4602590.61 13717828.86
                   
Annual Sum or Average 0.573594E+10 0.460478E+10 0.466160E+10 0.00 0.00 0.00 0.00 0.174887E+09 74857247.68
Minimum of Months 0.433846E+09 0.348887E+09 0.355639E+09 0.00 0.00 0.00 0.00 3348878.43 51958.24
Maximum of Months 0.517349E+09 0.412553E+09 0.405587E+09 0.00 0.00 0.00 0.00 24007738.60 17497204.70



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.168077E+10 0.135061E+10 0.138169E+10 0.00 0.00 0.00 0.00 5507930.39 24482882.96
February 0.152714E+10 0.122808E+10 0.125185E+10 0.00 0.00 0.00 0.00 8519795.63 31880787.43
March 0.182107E+10 0.145219E+10 0.142767E+10 0.00 0.00 0.00 0.00 11870696.89 26956798.68
April 0.162363E+10 0.130977E+10 0.133882E+10 0.00 0.00 0.00 0.00 19292578.89 7745373.31
May 0.175092E+10 0.140129E+10 0.140468E+10 0.00 0.00 0.00 0.00 39870554.37 1162022.19
June 0.174647E+10 0.139424E+10 0.137672E+10 0.00 0.00 0.00 0.00 42140641.13 19919.28
July 0.162808E+10 0.131683E+10 0.136678E+10 0.00 0.00 0.00 0.00 35806959.33 159415.76
August 0.182107E+10 0.145197E+10 0.142767E+10 0.00 0.00 0.00 0.00 41828664.06 65479.66
September 0.162363E+10 0.130955E+10 0.133882E+10 0.00 0.00 0.00 0.00 40439380.37 127289.79
October 0.168077E+10 0.135083E+10 0.138169E+10 0.00 0.00 0.00 0.00 32844506.22 636078.50
November 0.165888E+10 0.132666E+10 0.134566E+10 0.00 0.00 0.00 0.00 18358458.67 16787180.92
December 0.162808E+10 0.131683E+10 0.136678E+10 0.00 0.00 0.00 0.00 7752676.85 24822107.83
                   
Annual Sum or Average 0.201905E+11 0.162088E+11 0.164088E+11 0.00 0.00 0.00 0.00 0.304233E+09 0.134845E+09
Minimum of Months 0.152714E+10 0.122808E+10 0.125185E+10 0.00 0.00 0.00 0.00 5507930.39 19919.28
Maximum of Months 0.182107E+10 0.145219E+10 0.142767E+10 0.00 0.00 0.00 0.00 42140641.13 31880787.43



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.572991E+09 0.460436E+09 0.471031E+09 0.00 0.00 0.00 0.00 3756769.63 17528201.80
February 0.520615E+09 0.418664E+09 0.426766E+09 0.00 0.00 0.00 0.00 5852451.01 22964638.15
March 0.620818E+09 0.495063E+09 0.486704E+09 0.00 0.00 0.00 0.00 7860799.65 19669329.22
April 0.553511E+09 0.446512E+09 0.456417E+09 0.00 0.00 0.00 0.00 12828472.58 6107704.74
May 0.596905E+09 0.477713E+09 0.478868E+09 0.00 0.00 0.00 0.00 26310384.98 1140305.65
June 0.595388E+09 0.475308E+09 0.469337E+09 0.00 0.00 0.00 0.00 28364896.06 101121.62
July 0.555027E+09 0.448918E+09 0.465948E+09 0.00 0.00 0.00 0.00 24141574.11 172710.19
August 0.620818E+09 0.494991E+09 0.486704E+09 0.00 0.00 0.00 0.00 28520203.01 78788.88
September 0.553511E+09 0.446439E+09 0.456417E+09 0.00 0.00 0.00 0.00 27640858.50 155200.78
October 0.572991E+09 0.460509E+09 0.471031E+09 0.00 0.00 0.00 0.00 22214447.59 561383.74
November 0.565526E+09 0.452271E+09 0.458747E+09 0.00 0.00 0.00 0.00 12390336.49 12162916.47
December 0.555027E+09 0.448918E+09 0.465948E+09 0.00 0.00 0.00 0.00 5191575.72 17868359.06
                   
Annual Sum or Average 0.688313E+10 0.552574E+10 0.559392E+10 0.00 0.00 0.00 0.00 0.205073E+09 98510660.30
Minimum of Months 0.520615E+09 0.418664E+09 0.426766E+09 0.00 0.00 0.00 0.00 3756769.63 78788.88
Maximum of Months 0.620818E+09 0.495063E+09 0.486704E+09 0.00 0.00 0.00 0.00 28520203.01 22964638.15



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.840387E+09 0.675306E+09 0.690846E+09 0.00 0.00 0.00 0.00 2639589.07 12576006.21
February 0.763569E+09 0.614041E+09 0.625924E+09 0.00 0.00 0.00 0.00 4123267.21 16446636.81
March 0.910534E+09 0.726093E+09 0.713833E+09 0.00 0.00 0.00 0.00 5699178.94 13965384.95
April 0.811816E+09 0.654884E+09 0.669412E+09 0.00 0.00 0.00 0.00 9311890.00 4134987.86
May 0.875461E+09 0.700646E+09 0.702339E+09 0.00 0.00 0.00 0.00 19347962.58 657777.18
June 0.873236E+09 0.697118E+09 0.688361E+09 0.00 0.00 0.00 0.00 20585437.98 25319.48
July 0.814040E+09 0.658413E+09 0.683391E+09 0.00 0.00 0.00 0.00 17472233.89 89813.19
August 0.910534E+09 0.725986E+09 0.713833E+09 0.00 0.00 0.00 0.00 20458309.35 41983.63
September 0.811816E+09 0.654777E+09 0.669412E+09 0.00 0.00 0.00 0.00 19741262.96 81418.73
October 0.840387E+09 0.675413E+09 0.690846E+09 0.00 0.00 0.00 0.00 15846627.82 363110.13
November 0.829438E+09 0.663331E+09 0.672829E+09 0.00 0.00 0.00 0.00 8836128.43 8735031.97
December 0.814040E+09 0.658413E+09 0.683391E+09 0.00 0.00 0.00 0.00 3689122.36 12758746.87
                   
Annual Sum or Average 0.100953E+11 0.810442E+10 0.820442E+10 0.00 0.00 0.00 0.00 0.147751E+09 69876217.02
Minimum of Months 0.763569E+09 0.614041E+09 0.625924E+09 0.00 0.00 0.00 0.00 2639589.07 25319.48
Maximum of Months 0.910534E+09 0.726093E+09 0.713833E+09 0.00 0.00 0.00 0.00 20585437.98 16446636.81



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 95489280.00 0.195896E+09 0.114310E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 86760720.00 0.178124E+09 0.103568E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.103460E+09 0.210629E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 92242800.00 0.189972E+09 0.110764E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 99474480.00 0.203247E+09 0.116212E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 99221760.00 0.202224E+09 0.113899E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 92495520.00 0.190996E+09 0.113076E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.103460E+09 0.210598E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 92242800.00 0.189941E+09 0.110764E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 95489280.00 0.195927E+09 0.114310E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 94245120.00 0.192423E+09 0.111329E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 92495520.00 0.190996E+09 0.113076E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.114708E+10 0.235097E+10 0.135753E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 86760720.00 0.178124E+09 0.103568E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.103460E+09 0.210629E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 95489280.00 0.195896E+09 0.114310E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 86760720.00 0.178124E+09 0.103568E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.103460E+09 0.210629E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 92242800.00 0.189972E+09 0.110764E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 99474480.00 0.203247E+09 0.116212E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 99221760.00 0.202224E+09 0.113899E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 92495520.00 0.190996E+09 0.113076E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.103460E+09 0.210598E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 92242800.00 0.189941E+09 0.110764E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 95489280.00 0.195927E+09 0.114310E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 94245120.00 0.192423E+09 0.111329E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 92495520.00 0.190996E+09 0.113076E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.114708E+10 0.235097E+10 0.135753E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 86760720.00 0.178124E+09 0.103568E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.103460E+09 0.210629E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 95489280.00 0.195896E+09 0.114310E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 86760720.00 0.178124E+09 0.103568E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.103460E+09 0.210629E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 92242800.00 0.189972E+09 0.110764E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 99474480.00 0.203247E+09 0.116212E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 99221760.00 0.202224E+09 0.113899E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 92495520.00 0.190996E+09 0.113076E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.103460E+09 0.210598E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 92242800.00 0.189941E+09 0.110764E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 95489280.00 0.195927E+09 0.114310E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 94245120.00 0.192423E+09 0.111329E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 92495520.00 0.190996E+09 0.113076E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.114708E+10 0.235097E+10 0.135753E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 86760720.00 0.178124E+09 0.103568E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.103460E+09 0.210629E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.105038E+09 0.215486E+09 0.125741E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 95436792.00 0.195937E+09 0.113924E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.113806E+09 0.231692E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.101467E+09 0.208970E+09 0.121840E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.109422E+09 0.223572E+09 0.127833E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.109144E+09 0.222446E+09 0.125289E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.101745E+09 0.210095E+09 0.124384E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.113806E+09 0.231658E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.101467E+09 0.208935E+09 0.121840E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.105038E+09 0.215520E+09 0.125741E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.103670E+09 0.211665E+09 0.122462E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.101745E+09 0.210095E+09 0.124384E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.126178E+10 0.258607E+10 0.149329E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 95436792.00 0.195937E+09 0.113924E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113806E+09 0.231692E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.105038E+09 0.215486E+09 0.125741E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 95436792.00 0.195937E+09 0.113924E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.113806E+09 0.231692E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.101467E+09 0.208970E+09 0.121840E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.109422E+09 0.223572E+09 0.127833E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.109144E+09 0.222446E+09 0.125289E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.101745E+09 0.210095E+09 0.124384E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.113806E+09 0.231658E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.101467E+09 0.208935E+09 0.121840E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.105038E+09 0.215520E+09 0.125741E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.103670E+09 0.211665E+09 0.122462E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.101745E+09 0.210095E+09 0.124384E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.126178E+10 0.258607E+10 0.149329E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 95436792.00 0.195937E+09 0.113924E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113806E+09 0.231692E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.105038E+09 0.215486E+09 0.125741E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 95436792.00 0.195937E+09 0.113924E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.113806E+09 0.231692E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.101467E+09 0.208970E+09 0.121840E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.109422E+09 0.223572E+09 0.127833E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.109144E+09 0.222446E+09 0.125289E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.101745E+09 0.210095E+09 0.124384E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.113806E+09 0.231658E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.101467E+09 0.208935E+09 0.121840E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.105038E+09 0.215520E+09 0.125741E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.103670E+09 0.211665E+09 0.122462E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.101745E+09 0.210095E+09 0.124384E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.126178E+10 0.258607E+10 0.149329E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 95436792.00 0.195937E+09 0.113924E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113806E+09 0.231692E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 13368499.20 64461033.62 10025293.76 0.00 0.00 0.00 0.00 1993701.73 15233883.41
February 12146500.80 58613001.28 9083168.58 0.00 0.00 0.00 0.00 3313686.34 19569797.66
March 14484355.20 69308878.93 10358869.18 0.00 0.00 0.00 0.00 3821740.52 17791811.82
April 12913992.00 62511689.50 9714257.22 0.00 0.00 0.00 0.00 6321902.41 6487665.97
May 13926427.20 66879853.28 10192081.47 0.00 0.00 0.00 0.00 14264412.14 1290706.80
June 13891046.40 66543055.60 9989231.55 0.00 0.00 0.00 0.00 16987956.13 240282.03
July 12949372.80 62848487.18 9917107.14 0.00 0.00 0.00 0.00 14166743.37 346592.69
August 14484355.20 69298672.94 10358869.18 0.00 0.00 0.00 0.00 17280277.65 145200.46
September 12913992.00 62501483.51 9714257.22 0.00 0.00 0.00 0.00 16170351.57 293065.71
October 13368499.20 64471239.61 10025293.76 0.00 0.00 0.00 0.00 12143049.72 786077.00
November 13194316.80 63317962.72 9763842.76 0.00 0.00 0.00 0.00 6999948.37 10354834.82
December 12949372.80 62848487.18 9917107.14 0.00 0.00 0.00 0.00 2495135.34 15521638.83
                   
Annual Sum or Average 0.160591E+09 0.773604E+09 0.119059E+09 0.00 0.00 0.00 0.00 0.115959E+09 88061557.19
Minimum of Months 12146500.80 58613001.28 9083168.58 0.00 0.00 0.00 0.00 1993701.73 145200.46
Maximum of Months 14484355.20 69308878.93 10358869.18 0.00 0.00 0.00 0.00 17280277.65 19569797.66



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.127331E+09 72760249.59 0.380621E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.115692E+09 66159295.97 0.344852E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137960E+09 78232244.29 0.393285E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.123002E+09 70559931.72 0.368812E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132646E+09 75490486.94 0.386953E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.132309E+09 75110327.31 0.379252E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.123339E+09 70940091.35 0.376513E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.137960E+09 78220724.30 0.393285E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.123002E+09 70548411.73 0.368812E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.127331E+09 72771769.58 0.380621E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.125672E+09 71470010.84 0.370694E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.123339E+09 70940091.35 0.376513E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.152958E+10 0.873204E+09 0.452021E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.115692E+09 66159295.97 0.344852E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137960E+09 78232244.29 0.393285E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.238722E+09 0.170532E+09 0.475850E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.216901E+09 0.155061E+09 0.431132E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.258648E+09 0.183357E+09 0.491683E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.230606E+09 0.165375E+09 0.461086E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.248685E+09 0.176931E+09 0.483766E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.248053E+09 0.176040E+09 0.474138E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.231238E+09 0.166266E+09 0.470715E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.258648E+09 0.183330E+09 0.491683E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.230606E+09 0.165348E+09 0.461086E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.238722E+09 0.170559E+09 0.475850E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.235612E+09 0.167508E+09 0.463440E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.231238E+09 0.166266E+09 0.470715E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.286768E+10 0.204657E+10 0.565114E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.216901E+09 0.155061E+09 0.431132E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.258648E+09 0.183357E+09 0.491683E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.286467E+09 0.204638E+09 0.571019E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.260281E+09 0.186073E+09 0.517358E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.310378E+09 0.220028E+09 0.590019E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.276727E+09 0.198450E+09 0.553303E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.298422E+09 0.212317E+09 0.580519E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.297664E+09 0.211248E+09 0.568965E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.277485E+09 0.199519E+09 0.564857E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.310378E+09 0.219996E+09 0.590019E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.276727E+09 0.198417E+09 0.553303E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.286467E+09 0.204671E+09 0.571019E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.282734E+09 0.201009E+09 0.556128E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.277485E+09 0.199519E+09 0.564857E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.344122E+10 0.245589E+10 0.678137E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.260281E+09 0.186073E+09 0.517358E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.310378E+09 0.220028E+09 0.590019E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.247750E+09 0.700317E+09 0.976954E+09 0.00 0.00 0.00 0.00 4572743.52 40154072.01
February 0.224947E+09 0.636783E+09 0.885145E+09 0.00 0.00 0.00 0.00 8442641.93 51625590.63
March 0.268194E+09 0.752985E+09 0.100946E+10 0.00 0.00 0.00 0.00 10508368.34 45031778.38
April 0.238919E+09 0.679139E+09 0.946644E+09 0.00 0.00 0.00 0.00 17446171.71 15502217.06
May 0.257972E+09 0.726596E+09 0.993207E+09 0.00 0.00 0.00 0.00 41384364.91 3127452.27
June 0.257186E+09 0.722937E+09 0.973440E+09 0.00 0.00 0.00 0.00 47197452.59 449273.09
July 0.239706E+09 0.682798E+09 0.966411E+09 0.00 0.00 0.00 0.00 38664683.04 729935.53
August 0.268194E+09 0.752874E+09 0.100946E+10 0.00 0.00 0.00 0.00 47576304.59 322307.94
September 0.238919E+09 0.679028E+09 0.946644E+09 0.00 0.00 0.00 0.00 44237520.29 665075.06
October 0.247750E+09 0.700428E+09 0.976954E+09 0.00 0.00 0.00 0.00 33800944.12 1814870.54
November 0.244786E+09 0.687899E+09 0.951476E+09 0.00 0.00 0.00 0.00 18690617.93 27562243.22
December 0.239706E+09 0.682798E+09 0.966411E+09 0.00 0.00 0.00 0.00 6917535.27 39500296.19
                   
Annual Sum or Average 0.297403E+10 0.840458E+10 0.116022E+11 0.00 0.00 0.00 0.00 0.319439E+09 0.226485E+09
Minimum of Months 0.224947E+09 0.636783E+09 0.885145E+09 0.00 0.00 0.00 0.00 4572743.52 322307.94
Maximum of Months 0.268194E+09 0.752985E+09 0.100946E+10 0.00 0.00 0.00 0.00 47576304.59 51625590.63



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.235540E+09 0.483211E+09 0.281965E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.214010E+09 0.439373E+09 0.255467E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.255201E+09 0.519551E+09 0.291347E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.227532E+09 0.468598E+09 0.273217E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.245370E+09 0.501343E+09 0.286656E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.244747E+09 0.498818E+09 0.280950E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.228156E+09 0.471123E+09 0.278922E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.255201E+09 0.519475E+09 0.291347E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.227532E+09 0.468522E+09 0.273217E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.235540E+09 0.483287E+09 0.281965E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.232471E+09 0.474642E+09 0.274611E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.228156E+09 0.471123E+09 0.278922E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.282946E+10 0.579907E+10 0.334858E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.214010E+09 0.439373E+09 0.255467E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.255201E+09 0.519551E+09 0.291347E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.313235E+10 0.145430E+10 0.171665E+10 0.00 0.00 0.00 0.00 4567612.32 60057652.96
February 0.284603E+10 0.132236E+10 0.155533E+10 0.00 0.00 0.00 0.00 8584266.24 79240499.67
March 0.339381E+10 0.156367E+10 0.177377E+10 0.00 0.00 0.00 0.00 11082004.31 69742534.30
April 0.302586E+10 0.141032E+10 0.166339E+10 0.00 0.00 0.00 0.00 19562859.45 26038970.19
May 0.326308E+10 0.150887E+10 0.174521E+10 0.00 0.00 0.00 0.00 47047640.48 6206964.51
June 0.325479E+10 0.150127E+10 0.171047E+10 0.00 0.00 0.00 0.00 55941028.05 1106811.96
July 0.303415E+10 0.141792E+10 0.169812E+10 0.00 0.00 0.00 0.00 46956151.82 1270547.53
August 0.339381E+10 0.156344E+10 0.177377E+10 0.00 0.00 0.00 0.00 55801665.88 698192.79
September 0.302586E+10 0.141009E+10 0.166339E+10 0.00 0.00 0.00 0.00 51623472.68 1606075.61
October 0.313235E+10 0.145453E+10 0.171665E+10 0.00 0.00 0.00 0.00 35899125.49 4473527.45
November 0.309154E+10 0.142851E+10 0.167188E+10 0.00 0.00 0.00 0.00 18722696.85 44107188.24
December 0.303415E+10 0.141792E+10 0.169812E+10 0.00 0.00 0.00 0.00 6276369.59 61192877.72
                   
Annual Sum or Average 0.376278E+11 0.174532E+11 0.203867E+11 0.00 0.00 0.00 0.00 0.362065E+09 0.355742E+09
Minimum of Months 0.284603E+10 0.132236E+10 0.155533E+10 0.00 0.00 0.00 0.00 4567612.32 698192.79
Maximum of Months 0.339381E+10 0.156367E+10 0.177377E+10 0.00 0.00 0.00 0.00 55941028.05 79240499.67



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.299200E+09 0.613808E+09 0.358171E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.271850E+09 0.558123E+09 0.324512E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.324174E+09 0.659970E+09 0.370089E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.289027E+09 0.595246E+09 0.347059E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.311687E+09 0.636841E+09 0.364130E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.310895E+09 0.633634E+09 0.356883E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.289819E+09 0.598454E+09 0.354306E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.324174E+09 0.659873E+09 0.370089E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.289027E+09 0.595149E+09 0.347059E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.299200E+09 0.613906E+09 0.358171E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.295301E+09 0.602924E+09 0.348830E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.289819E+09 0.598454E+09 0.354306E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.359417E+10 0.736638E+10 0.425361E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.271850E+09 0.558123E+09 0.324512E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.324174E+09 0.659970E+09 0.370089E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 66842496.00 0.128922E+09 80016946.16 0.00 0.00 0.00 0.00 0.00 0.00
February 60732504.00 0.117226E+09 72497368.03 0.00 0.00 0.00 0.00 0.00 0.00
March 72421776.00 0.138618E+09 82679380.52 0.00 0.00 0.00 0.00 0.00 0.00
April 64569960.00 0.125023E+09 77534406.01 0.00 0.00 0.00 0.00 0.00 0.00
May 69632136.00 0.133760E+09 81348163.34 0.00 0.00 0.00 0.00 0.00 0.00
June 69455232.00 0.133086E+09 79729115.42 0.00 0.00 0.00 0.00 0.00 0.00
July 64746864.00 0.125697E+09 79153453.93 0.00 0.00 0.00 0.00 0.00 0.00
August 72421776.00 0.138597E+09 82679380.52 0.00 0.00 0.00 0.00 0.00 0.00
September 64569960.00 0.125003E+09 77534406.01 0.00 0.00 0.00 0.00 0.00 0.00
October 66842496.00 0.128942E+09 80016946.16 0.00 0.00 0.00 0.00 0.00 0.00
November 65971584.00 0.126636E+09 77930173.28 0.00 0.00 0.00 0.00 0.00 0.00
December 64746864.00 0.125697E+09 79153453.93 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.802954E+09 0.154721E+10 0.950273E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 60732504.00 0.117226E+09 72497368.03 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 72421776.00 0.138618E+09 82679380.52 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.143341E+09 0.405184E+09 0.565238E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130148E+09 0.368425E+09 0.512120E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.155170E+09 0.435656E+09 0.584045E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138232E+09 0.392931E+09 0.547701E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.149255E+09 0.420388E+09 0.574641E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.148800E+09 0.418271E+09 0.563204E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138687E+09 0.395048E+09 0.559138E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.155170E+09 0.435592E+09 0.584045E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.138232E+09 0.392866E+09 0.547701E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143341E+09 0.405248E+09 0.565238E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.141626E+09 0.397999E+09 0.550497E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138687E+09 0.395048E+09 0.559138E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.172069E+10 0.486265E+10 0.671270E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130148E+09 0.368425E+09 0.512120E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.155170E+09 0.435656E+09 0.584045E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.151305E+09 0.427694E+09 0.596640E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.137378E+09 0.388893E+09 0.540571E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.163790E+09 0.459859E+09 0.616492E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.145911E+09 0.414760E+09 0.578129E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.157547E+09 0.443743E+09 0.606566E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.157067E+09 0.441508E+09 0.594494E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.146392E+09 0.416995E+09 0.590201E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.163790E+09 0.459791E+09 0.616492E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.145911E+09 0.414692E+09 0.578129E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.151305E+09 0.427762E+09 0.596640E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.149495E+09 0.420110E+09 0.581080E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.146392E+09 0.416995E+09 0.590201E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.181628E+10 0.513280E+10 0.708563E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.137378E+09 0.388893E+09 0.540571E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.163790E+09 0.459859E+09 0.616492E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11883110.40 57298696.55 8911442.72 0.00 0.00 0.00 0.00 0.00 0.00
February 10796889.60 52100445.58 8073991.50 0.00 0.00 0.00 0.00 0.00 0.00
March 12874982.40 61607892.38 9207956.55 0.00 0.00 0.00 0.00 0.00 0.00
April 11479104.00 55565946.23 8634963.61 0.00 0.00 0.00 0.00 0.00 0.00
May 12379046.40 59448758.47 9059699.64 0.00 0.00 0.00 0.00 0.00 0.00
June 12347596.80 59149382.76 8879387.17 0.00 0.00 0.00 0.00 0.00 0.00
July 11510553.60 55865321.94 8815276.07 0.00 0.00 0.00 0.00 0.00 0.00
August 12874982.40 61598820.39 9207956.55 0.00 0.00 0.00 0.00 0.00 0.00
September 11479104.00 55556874.24 8634963.61 0.00 0.00 0.00 0.00 0.00 0.00
October 11883110.40 57307768.54 8911442.72 0.00 0.00 0.00 0.00 0.00 0.00
November 11728281.60 56282633.53 8679039.99 0.00 0.00 0.00 0.00 0.00 0.00
December 11510553.60 55865321.94 8815276.07 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.142747E+09 0.687648E+09 0.105831E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 10796889.60 52100445.58 8073991.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12874982.40 61607892.38 9207956.55 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 25463808.00 0.122783E+09 19095812.75 0.00 0.00 0.00 0.00 0.00 0.00
February 23136192.00 0.111644E+09 17301287.18 0.00 0.00 0.00 0.00 0.00 0.00
March 27589248.00 0.132017E+09 19731195.01 0.00 0.00 0.00 0.00 0.00 0.00
April 24598080.00 0.119070E+09 18503361.72 0.00 0.00 0.00 0.00 0.00 0.00
May 26526528.00 0.127390E+09 19413503.88 0.00 0.00 0.00 0.00 0.00 0.00
June 26459136.00 0.126749E+09 19027122.77 0.00 0.00 0.00 0.00 0.00 0.00
July 24665472.00 0.119711E+09 18889742.83 0.00 0.00 0.00 0.00 0.00 0.00
August 27589248.00 0.131997E+09 19731195.01 0.00 0.00 0.00 0.00 0.00 0.00
September 24598080.00 0.119050E+09 18503361.72 0.00 0.00 0.00 0.00 0.00 0.00
October 25463808.00 0.122802E+09 19095812.75 0.00 0.00 0.00 0.00 0.00 0.00
November 25132032.00 0.120606E+09 18597810.44 0.00 0.00 0.00 0.00 0.00 0.00
December 24665472.00 0.119711E+09 18889742.83 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.305887E+09 0.147353E+10 0.226780E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 23136192.00 0.111644E+09 17301287.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27589248.00 0.132017E+09 19731195.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 30556569.60 0.147340E+09 22915070.46 0.00 0.00 0.00 0.00 0.00 0.00
February 27763430.40 0.133973E+09 20761630.83 0.00 0.00 0.00 0.00 0.00 0.00
March 33107097.60 0.158420E+09 23677532.33 0.00 0.00 0.00 0.00 0.00 0.00
April 29517696.00 0.142884E+09 22204126.27 0.00 0.00 0.00 0.00 0.00 0.00
May 31831833.60 0.152868E+09 23296301.39 0.00 0.00 0.00 0.00 0.00 0.00
June 31750963.20 0.152098E+09 22832642.15 0.00 0.00 0.00 0.00 0.00 0.00
July 29598566.40 0.143654E+09 22667785.52 0.00 0.00 0.00 0.00 0.00 0.00
August 33107097.60 0.158397E+09 23677532.33 0.00 0.00 0.00 0.00 0.00 0.00
September 29517696.00 0.142861E+09 22204126.27 0.00 0.00 0.00 0.00 0.00 0.00
October 30556569.60 0.147363E+09 22915070.46 0.00 0.00 0.00 0.00 0.00 0.00
November 30158438.40 0.144727E+09 22317465.20 0.00 0.00 0.00 0.00 0.00 0.00
December 29598566.40 0.143654E+09 22667785.52 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.367065E+09 0.176824E+10 0.272137E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 27763430.40 0.133973E+09 20761630.83 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 33107097.60 0.158420E+09 23677532.33 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 26736998.40 0.128922E+09 20050587.52 0.00 0.00 0.00 0.00 1164413.15 8066324.73
February 24293001.60 0.117226E+09 18166337.17 0.00 0.00 0.00 0.00 2026172.71 10138053.27
March 28968710.40 0.138618E+09 20717738.37 0.00 0.00 0.00 0.00 2613979.61 8710908.45
April 25827984.00 0.125023E+09 19428514.44 0.00 0.00 0.00 0.00 4282369.80 2544366.75
May 27852854.40 0.133760E+09 20384162.95 0.00 0.00 0.00 0.00 10252633.72 379414.28
June 27782092.80 0.133086E+09 19978463.11 0.00 0.00 0.00 0.00 11360683.83 24298.17
July 25898745.60 0.125697E+09 19834214.28 0.00 0.00 0.00 0.00 9210959.43 87401.57
August 28968710.40 0.138597E+09 20717738.37 0.00 0.00 0.00 0.00 11356611.08 30931.99
September 25827984.00 0.125003E+09 19428514.44 0.00 0.00 0.00 0.00 10587374.11 48117.72
October 26736998.40 0.128942E+09 20050587.52 0.00 0.00 0.00 0.00 8460602.44 216701.10
November 26388633.60 0.126636E+09 19527685.51 0.00 0.00 0.00 0.00 4798452.98 5399699.84
December 25898745.60 0.125697E+09 19834214.28 0.00 0.00 0.00 0.00 1804074.32 7837024.21
                   
Annual Sum or Average 0.321181E+09 0.154721E+10 0.238119E+09 0.00 0.00 0.00 0.00 77918327.17 43483242.08
Minimum of Months 24293001.60 0.117226E+09 18166337.17 0.00 0.00 0.00 0.00 1164413.15 24298.17
Maximum of Months 28968710.40 0.138618E+09 20717738.37 0.00 0.00 0.00 0.00 11360683.83 10138053.27



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.747675E+09 0.211346E+10 0.243541E+10 0.00 0.00 0.00 0.00 2898816.21 32009153.92
February 0.678858E+09 0.192172E+10 0.220654E+10 0.00 0.00 0.00 0.00 5225440.45 42552051.75
March 0.809372E+09 0.227240E+10 0.251644E+10 0.00 0.00 0.00 0.00 6391689.56 37065322.46
April 0.721024E+09 0.204955E+10 0.235985E+10 0.00 0.00 0.00 0.00 11085732.12 13323520.00
May 0.778524E+09 0.219276E+10 0.247592E+10 0.00 0.00 0.00 0.00 25382237.09 3043324.01
June 0.776151E+09 0.218172E+10 0.242665E+10 0.00 0.00 0.00 0.00 29914198.99 483181.30
July 0.723397E+09 0.206059E+10 0.240913E+10 0.00 0.00 0.00 0.00 25452499.55 601695.84
August 0.809372E+09 0.227207E+10 0.251644E+10 0.00 0.00 0.00 0.00 30397453.89 316015.97
September 0.721024E+09 0.204921E+10 0.235985E+10 0.00 0.00 0.00 0.00 28648739.37 690121.25
October 0.747675E+09 0.211379E+10 0.243541E+10 0.00 0.00 0.00 0.00 20748611.97 1878704.15
November 0.738730E+09 0.207598E+10 0.237189E+10 0.00 0.00 0.00 0.00 10821652.73 23085219.39
December 0.723397E+09 0.206059E+10 0.240913E+10 0.00 0.00 0.00 0.00 3967063.05 32441785.88
                   
Annual Sum or Average 0.897520E+10 0.253638E+11 0.289226E+11 0.00 0.00 0.00 0.00 0.200934E+09 0.187490E+09
Minimum of Months 0.678858E+09 0.192172E+10 0.220654E+10 0.00 0.00 0.00 0.00 2898816.21 316015.97
Maximum of Months 0.809372E+09 0.227240E+10 0.251644E+10 0.00 0.00 0.00 0.00 30397453.89 42552051.75



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.442434E+09 0.907653E+09 0.529636E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.401991E+09 0.825309E+09 0.479864E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.479363E+09 0.975914E+09 0.547259E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.427392E+09 0.880205E+09 0.513204E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.460898E+09 0.941711E+09 0.538448E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.459727E+09 0.936969E+09 0.527731E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.428563E+09 0.884947E+09 0.523921E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.479363E+09 0.975770E+09 0.547259E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.427392E+09 0.880061E+09 0.513204E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.442434E+09 0.907797E+09 0.529636E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.436669E+09 0.891558E+09 0.515824E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.428563E+09 0.884947E+09 0.523921E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.531479E+10 0.108928E+11 0.628991E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.401991E+09 0.825309E+09 0.479864E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.479363E+09 0.975914E+09 0.547259E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 28646784.00 55252314.53 34293067.55 0.00 0.00 0.00 0.00 1288708.97 5372332.57
February 26028216.00 50239715.38 31070382.70 0.00 0.00 0.00 0.00 2028803.12 6856376.24
March 31037904.00 59407610.51 35434113.87 0.00 0.00 0.00 0.00 2620694.72 6021781.83
April 27672840.00 53581448.15 33229118.96 0.00 0.00 0.00 0.00 4076782.77 1742882.32
May 29842344.00 57325588.52 34863590.71 0.00 0.00 0.00 0.00 8617945.60 229765.44
June 29766528.00 57036904.80 34169711.20 0.00 0.00 0.00 0.00 9333965.59 17693.81
July 27748656.00 53870131.87 33922998.48 0.00 0.00 0.00 0.00 7679757.85 42107.43
August 31037904.00 59398862.52 35434113.87 0.00 0.00 0.00 0.00 9185836.67 21950.46
September 27672840.00 53572700.16 33229118.96 0.00 0.00 0.00 0.00 8750860.76 25292.40
October 28646784.00 55261062.52 34293067.55 0.00 0.00 0.00 0.00 7025323.79 151683.03
November 28273536.00 54272539.48 33398733.96 0.00 0.00 0.00 0.00 4207626.03 3630017.69
December 27748656.00 53870131.87 33922998.48 0.00 0.00 0.00 0.00 1654289.52 5449607.79
                   
Annual Sum or Average 0.344123E+09 0.663089E+09 0.407261E+09 0.00 0.00 0.00 0.00 66470595.39 29561491.01
Minimum of Months 26028216.00 50239715.38 31070382.70 0.00 0.00 0.00 0.00 1288708.97 17693.81
Maximum of Months 31037904.00 59407610.51 35434113.87 0.00 0.00 0.00 0.00 9333965.59 6856376.24



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 X-RAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.190997E+10 0.153479E+10 0.142742E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.173538E+10 0.139555E+10 0.129327E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.206939E+10 0.165021E+10 0.147491E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.184504E+10 0.148837E+10 0.138313E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.198968E+10 0.159238E+10 0.145116E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.198463E+10 0.158436E+10 0.142228E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.185009E+10 0.149639E+10 0.141201E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.206939E+10 0.164997E+10 0.147491E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.184504E+10 0.148813E+10 0.138313E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.190997E+10 0.153503E+10 0.142742E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.188509E+10 0.150757E+10 0.139019E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.185009E+10 0.149639E+10 0.141201E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.229438E+11 0.184191E+11 0.169518E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.173538E+10 0.139555E+10 0.129327E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.206939E+10 0.165021E+10 0.147491E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 18581264.22 52523805.17 73271509.94 0.00 0.00 0.00 0.00 0.00 0.00
February 16871025.79 47758741.78 66385832.97 0.00 0.00 0.00 0.00 0.00 0.00
March 20114581.43 56473901.35 75709500.82 0.00 0.00 0.00 0.00 0.00 0.00
April 17918943.77 50935450.71 70998248.16 0.00 0.00 0.00 0.00 0.00 0.00
May 19347922.83 54494695.26 74490505.38 0.00 0.00 0.00 0.00 0.00 0.00
June 19288949.09 54220267.53 73007943.35 0.00 0.00 0.00 0.00 0.00 0.00
July 17977917.51 51209878.44 72480810.19 0.00 0.00 0.00 0.00 0.00 0.00
August 20114581.43 56465585.36 75709500.82 0.00 0.00 0.00 0.00 0.00 0.00
September 17918943.77 50927134.72 70998248.16 0.00 0.00 0.00 0.00 0.00 0.00
October 18581264.22 52532121.16 73271509.94 0.00 0.00 0.00 0.00 0.00 0.00
November 18358978.59 51592414.07 71360652.21 0.00 0.00 0.00 0.00 0.00 0.00
December 17977917.51 51209878.44 72480810.19 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.223052E+09 0.630344E+09 0.870165E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16871025.79 47758741.78 66385832.97 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20114581.43 56473901.35 75709500.82 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.196284E+09 0.402676E+09 0.234971E+09 0.00 0.00 0.00 0.00 740608.03 4228728.52
February 0.178341E+09 0.366144E+09 0.212889E+09 0.00 0.00 0.00 0.00 1150300.17 5055361.42
March 0.212667E+09 0.432959E+09 0.242789E+09 0.00 0.00 0.00 0.00 1578538.18 4147510.88
April 0.189610E+09 0.390499E+09 0.227681E+09 0.00 0.00 0.00 0.00 2487381.74 719585.43
May 0.204475E+09 0.417786E+09 0.238880E+09 0.00 0.00 0.00 0.00 5962471.42 47549.60
June 0.203956E+09 0.415682E+09 0.234125E+09 0.00 0.00 0.00 0.00 6242418.44 302.07
July 0.190130E+09 0.392603E+09 0.232435E+09 0.00 0.00 0.00 0.00 4991429.00 11442.78
August 0.212667E+09 0.432896E+09 0.242789E+09 0.00 0.00 0.00 0.00 6097951.77 2187.94
September 0.189610E+09 0.390435E+09 0.227681E+09 0.00 0.00 0.00 0.00 5692632.18 1315.04
October 0.196284E+09 0.402740E+09 0.234971E+09 0.00 0.00 0.00 0.00 4794707.44 39677.45
November 0.193726E+09 0.395535E+09 0.228843E+09 0.00 0.00 0.00 0.00 2839869.04 2618741.58
December 0.190130E+09 0.392603E+09 0.232435E+09 0.00 0.00 0.00 0.00 1000224.72 4241178.81
                   
Annual Sum or Average 0.235788E+10 0.483256E+10 0.279049E+10 0.00 0.00 0.00 0.00 43578532.13 21113581.52
Minimum of Months 0.178341E+09 0.366144E+09 0.212889E+09 0.00 0.00 0.00 0.00 740608.03 302.07
Maximum of Months 0.212667E+09 0.432959E+09 0.242789E+09 0.00 0.00 0.00 0.00 6242418.44 5055361.42



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 47780393.71 0.135061E+09 0.188413E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 43382637.75 0.122808E+09 0.170707E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 51723209.40 0.145219E+09 0.194682E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 46077283.97 0.130977E+09 0.182567E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 49751801.56 0.140129E+09 0.191547E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 49600154.80 0.139424E+09 0.187735E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 46228930.73 0.131683E+09 0.186379E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 51723209.40 0.145197E+09 0.194682E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 46077283.97 0.130955E+09 0.182567E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 47780393.71 0.135083E+09 0.188413E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 47208802.09 0.132666E+09 0.183499E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 46228930.73 0.131683E+09 0.186379E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.573563E+09 0.162088E+10 0.223757E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 43382637.75 0.122808E+09 0.170707E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 51723209.40 0.145219E+09 0.194682E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 13368499.20 64461033.62 10025293.76 0.00 0.00 0.00 0.00 3761730.61 12345607.96
February 12146500.80 58613001.28 9083168.58 0.00 0.00 0.00 0.00 6138770.38 14420887.56
March 14484355.20 69308878.93 10358869.18 0.00 0.00 0.00 0.00 7566944.96 12408166.92
April 12913992.00 62511689.50 9714257.22 0.00 0.00 0.00 0.00 10431490.53 1973680.78
May 13926427.20 66879853.28 10192081.47 0.00 0.00 0.00 0.00 23033203.22 86889.63
June 13891046.40 66543055.60 9989231.55 0.00 0.00 0.00 0.00 23600056.90 3397.57
July 12949372.80 62848487.18 9917107.14 0.00 0.00 0.00 0.00 18953918.15 50429.03
August 14484355.20 69298672.94 10358869.18 0.00 0.00 0.00 0.00 23167735.69 7692.31
September 12913992.00 62501483.51 9714257.22 0.00 0.00 0.00 0.00 21709023.24 11004.78
October 13368499.20 64471239.61 10025293.76 0.00 0.00 0.00 0.00 19190387.80 47094.11
November 13194316.80 63317962.72 9763842.76 0.00 0.00 0.00 0.00 12361422.17 6670022.67
December 12949372.80 62848487.18 9917107.14 0.00 0.00 0.00 0.00 4845290.29 12411633.29
                   
Annual Sum or Average 0.160591E+09 0.773604E+09 0.119059E+09 0.00 0.00 0.00 0.00 0.174760E+09 60436506.61
Minimum of Months 12146500.80 58613001.28 9083168.58 0.00 0.00 0.00 0.00 3761730.61 3397.57
Maximum of Months 14484355.20 69308878.93 10358869.18 0.00 0.00 0.00 0.00 23600056.90 14420887.56



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 LOCKER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.190997E+09 0.109140E+09 0.570931E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.173538E+09 99238943.96 0.517278E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.206939E+09 0.117348E+09 0.589928E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.184504E+09 0.105840E+09 0.553218E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.198968E+09 0.113236E+09 0.580429E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.198463E+09 0.112665E+09 0.568877E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.185009E+09 0.106410E+09 0.564770E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.206939E+09 0.117331E+09 0.589928E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.184504E+09 0.105823E+09 0.553218E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.190997E+09 0.109158E+09 0.570931E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.188509E+09 0.107205E+09 0.556042E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.185009E+09 0.106410E+09 0.564770E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.229438E+10 0.130981E+10 0.678032E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.173538E+09 99238943.96 0.517278E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.206939E+09 0.117348E+09 0.589928E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.120806E+10 0.690313E+09 0.361114E+10 0.00 0.00 0.00 0.00 3475092.77 27818876.97
February 0.109763E+10 0.627686E+09 0.327178E+10 0.00 0.00 0.00 0.00 5761780.59 33558708.53
March 0.130889E+10 0.742228E+09 0.373129E+10 0.00 0.00 0.00 0.00 7792219.74 26824670.86
April 0.116698E+10 0.669437E+09 0.349910E+10 0.00 0.00 0.00 0.00 12702406.41 5090018.19
May 0.125847E+10 0.716216E+09 0.367122E+10 0.00 0.00 0.00 0.00 32006179.62 423632.79
June 0.125528E+10 0.712609E+09 0.359815E+10 0.00 0.00 0.00 0.00 33959448.12 19933.66
July 0.117018E+10 0.673044E+09 0.357217E+10 0.00 0.00 0.00 0.00 27571843.79 112855.85
August 0.130889E+10 0.742119E+09 0.373129E+10 0.00 0.00 0.00 0.00 33476221.16 27946.71
September 0.116698E+10 0.669328E+09 0.349910E+10 0.00 0.00 0.00 0.00 31266402.45 28562.26
October 0.120806E+10 0.690422E+09 0.361114E+10 0.00 0.00 0.00 0.00 25963727.31 307692.70
November 0.119232E+10 0.678072E+09 0.351696E+10 0.00 0.00 0.00 0.00 14937126.72 17692853.87
December 0.117018E+10 0.673044E+09 0.357217E+10 0.00 0.00 0.00 0.00 4854188.28 27489886.29
                   
Annual Sum or Average 0.145119E+11 0.828452E+10 0.428855E+11 0.00 0.00 0.00 0.00 0.233767E+09 0.139396E+09
Minimum of Months 0.109763E+10 0.627686E+09 0.327178E+10 0.00 0.00 0.00 0.00 3475092.77 19933.66
Maximum of Months 0.130889E+10 0.742228E+09 0.373129E+10 0.00 0.00 0.00 0.00 33959448.12 33558708.53



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.101855E+09 0.196453E+09 0.121931E+09 0.00 0.00 0.00 0.00 5096927.88 8718037.82
February 92544768.00 0.178630E+09 0.110472E+09 0.00 0.00 0.00 0.00 8977398.16 9835708.62
March 0.110357E+09 0.211227E+09 0.125988E+09 0.00 0.00 0.00 0.00 13162474.44 8201054.89
April 98392320.00 0.190512E+09 0.118148E+09 0.00 0.00 0.00 0.00 16998960.55 622159.12
May 0.106106E+09 0.203824E+09 0.123959E+09 0.00 0.00 0.00 0.00 29641404.65 3304.53
June 0.105837E+09 0.202798E+09 0.121492E+09 0.00 0.00 0.00 0.00 26927976.10 0.00
July 98661888.00 0.191538E+09 0.120615E+09 0.00 0.00 0.00 0.00 21486099.44 567.88
August 0.110357E+09 0.211196E+09 0.125988E+09 0.00 0.00 0.00 0.00 25600728.86 0.00
September 98392320.00 0.190481E+09 0.118148E+09 0.00 0.00 0.00 0.00 24719171.34 0.00
October 0.101855E+09 0.196484E+09 0.121931E+09 0.00 0.00 0.00 0.00 23467202.40 945.54
November 0.100528E+09 0.192969E+09 0.118751E+09 0.00 0.00 0.00 0.00 15709662.08 4702761.05
December 98661888.00 0.191538E+09 0.120615E+09 0.00 0.00 0.00 0.00 6908187.33 8743526.43
                   
Annual Sum or Average 0.122355E+10 0.235765E+10 0.144804E+10 0.00 0.00 0.00 0.00 0.218696E+09 40828065.88
Minimum of Months 92544768.00 0.178630E+09 0.110472E+09 0.00 0.00 0.00 0.00 5096927.88 0.00
Maximum of Months 0.110357E+09 0.211227E+09 0.125988E+09 0.00 0.00 0.00 0.00 29641404.65 9835708.62



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 55702080.00 0.596861E+09 0.277553E+10 0.00 0.00 0.00 0.00 2466763.87 37167775.85
February 50610420.00 0.542713E+09 0.251470E+10 0.00 0.00 0.00 0.00 5044729.16 46729713.99
March 60351480.00 0.641749E+09 0.286788E+10 0.00 0.00 0.00 0.00 5861842.13 38446752.48
April 53808300.00 0.578812E+09 0.268942E+10 0.00 0.00 0.00 0.00 9777973.96 11730483.91
May 58026780.00 0.619258E+09 0.282171E+10 0.00 0.00 0.00 0.00 25910166.68 2535544.85
June 57879360.00 0.616139E+09 0.276555E+10 0.00 0.00 0.00 0.00 29630791.90 448969.95
July 53955720.00 0.581930E+09 0.274558E+10 0.00 0.00 0.00 0.00 24794965.46 636577.46
August 60351480.00 0.641654E+09 0.286788E+10 0.00 0.00 0.00 0.00 29980391.58 314665.84
September 53808300.00 0.578717E+09 0.268942E+10 0.00 0.00 0.00 0.00 27385032.33 565785.37
October 55702080.00 0.596956E+09 0.277553E+10 0.00 0.00 0.00 0.00 20683404.55 1591077.08
November 54976320.00 0.586277E+09 0.270315E+10 0.00 0.00 0.00 0.00 11562932.09 25692653.87
December 53955720.00 0.581930E+09 0.274558E+10 0.00 0.00 0.00 0.00 3462804.96 36285443.80
                   
Annual Sum or Average 0.669128E+09 0.716300E+10 0.329619E+11 0.00 0.00 0.00 0.00 0.196562E+09 0.202145E+09
Minimum of Months 50610420.00 0.542713E+09 0.251470E+10 0.00 0.00 0.00 0.00 2466763.87 314665.84
Maximum of Months 60351480.00 0.641749E+09 0.286788E+10 0.00 0.00 0.00 0.00 29980391.58 46729713.99



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.159149E+09 0.326494E+09 0.190517E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.144601E+09 0.296874E+09 0.172613E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.172433E+09 0.351048E+09 0.196856E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.153738E+09 0.316620E+09 0.184606E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.165791E+09 0.338745E+09 0.193686E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.165370E+09 0.337039E+09 0.189831E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.154159E+09 0.318326E+09 0.188461E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.172433E+09 0.350996E+09 0.196856E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.153738E+09 0.316569E+09 0.184606E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.159149E+09 0.326546E+09 0.190517E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.157075E+09 0.320704E+09 0.185548E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.154159E+09 0.318326E+09 0.188461E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.191179E+10 0.391829E+10 0.226256E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.144601E+09 0.296874E+09 0.172613E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.172433E+09 0.351048E+09 0.196856E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.134316E+10 0.379672E+10 0.529649E+10 0.00 0.00 0.00 0.00 12599482.77 80687804.31
February 0.121953E+10 0.345227E+10 0.479875E+10 0.00 0.00 0.00 0.00 19924069.47 96388774.28
March 0.145400E+10 0.408226E+10 0.547272E+10 0.00 0.00 0.00 0.00 27473750.52 78199514.03
April 0.129528E+10 0.368191E+10 0.513216E+10 0.00 0.00 0.00 0.00 44049330.67 13693151.52
May 0.139858E+10 0.393919E+10 0.538460E+10 0.00 0.00 0.00 0.00 0.106630E+09 938115.98
June 0.139432E+10 0.391935E+10 0.527743E+10 0.00 0.00 0.00 0.00 0.111863E+09 18948.48
July 0.129955E+10 0.370174E+10 0.523933E+10 0.00 0.00 0.00 0.00 90421310.63 248860.91
August 0.145400E+10 0.408166E+10 0.547272E+10 0.00 0.00 0.00 0.00 0.110204E+09 36460.00
September 0.129528E+10 0.368130E+10 0.513216E+10 0.00 0.00 0.00 0.00 0.103131E+09 26705.32
October 0.134316E+10 0.379732E+10 0.529649E+10 0.00 0.00 0.00 0.00 87314872.95 699513.44
November 0.132709E+10 0.372939E+10 0.515836E+10 0.00 0.00 0.00 0.00 50713251.67 49984625.64
December 0.129955E+10 0.370174E+10 0.523933E+10 0.00 0.00 0.00 0.00 17515320.24 80435307.58
                   
Annual Sum or Average 0.161235E+11 0.455649E+11 0.629005E+11 0.00 0.00 0.00 0.00 0.781839E+09 0.401358E+09
Minimum of Months 0.121953E+10 0.345227E+10 0.479875E+10 0.00 0.00 0.00 0.00 12599482.77 18948.48
Maximum of Months 0.145400E+10 0.408226E+10 0.547272E+10 0.00 0.00 0.00 0.00 0.111863E+09 96388774.28



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.442434E+09 0.907653E+09 0.529636E+09 0.00 0.00 0.00 0.00 1090083.99 6596331.07
February 0.401991E+09 0.825309E+09 0.479864E+09 0.00 0.00 0.00 0.00 1716242.37 7863522.90
March 0.479363E+09 0.975914E+09 0.547259E+09 0.00 0.00 0.00 0.00 2483840.40 6304476.50
April 0.427392E+09 0.880205E+09 0.513204E+09 0.00 0.00 0.00 0.00 3948922.62 994727.82
May 0.460898E+09 0.941711E+09 0.538448E+09 0.00 0.00 0.00 0.00 9504605.84 52871.32
June 0.459727E+09 0.936969E+09 0.527731E+09 0.00 0.00 0.00 0.00 9807479.71 278.18
July 0.428563E+09 0.884947E+09 0.523921E+09 0.00 0.00 0.00 0.00 7874817.45 11204.55
August 0.479363E+09 0.975770E+09 0.547259E+09 0.00 0.00 0.00 0.00 9525402.51 1095.01
September 0.427392E+09 0.880061E+09 0.513204E+09 0.00 0.00 0.00 0.00 8904533.05 692.83
October 0.442434E+09 0.907797E+09 0.529636E+09 0.00 0.00 0.00 0.00 7523284.24 42956.64
November 0.436669E+09 0.891558E+09 0.515824E+09 0.00 0.00 0.00 0.00 4406123.83 4072640.37
December 0.428563E+09 0.884947E+09 0.523921E+09 0.00 0.00 0.00 0.00 1532613.05 6565314.20
                   
Annual Sum or Average 0.531479E+10 0.108928E+11 0.628991E+10 0.00 0.00 0.00 0.00 68317949.06 32506111.40
Minimum of Months 0.401991E+09 0.825309E+09 0.479864E+09 0.00 0.00 0.00 0.00 1090083.99 278.18
Maximum of Months 0.479363E+09 0.975914E+09 0.547259E+09 0.00 0.00 0.00 0.00 9807479.71 7863522.90



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 28646784.00 55252314.53 34293067.55 0.00 0.00 0.00 0.00 2412860.64 4513604.76
February 26028216.00 50239715.38 31070382.70 0.00 0.00 0.00 0.00 4146087.44 5189997.26
March 31037904.00 59407610.51 35434113.87 0.00 0.00 0.00 0.00 5692404.60 4394161.76
April 27672840.00 53581448.15 33229118.96 0.00 0.00 0.00 0.00 7367721.48 417635.59
May 29842344.00 57325588.52 34863590.71 0.00 0.00 0.00 0.00 13616682.09 6677.97
June 29766528.00 57036904.80 34169711.20 0.00 0.00 0.00 0.00 12757707.79 0.00
July 27748656.00 53870131.87 33922998.48 0.00 0.00 0.00 0.00 10083939.35 1257.39
August 31037904.00 59398862.52 35434113.87 0.00 0.00 0.00 0.00 12033317.50 0.00
September 27672840.00 53572700.16 33229118.96 0.00 0.00 0.00 0.00 11508005.03 112.13
October 28646784.00 55261062.52 34293067.55 0.00 0.00 0.00 0.00 10668366.11 2995.76
November 28273536.00 54272539.48 33398733.96 0.00 0.00 0.00 0.00 7262405.38 2423087.90
December 27748656.00 53870131.87 33922998.48 0.00 0.00 0.00 0.00 3093851.78 4478877.06
                   
Annual Sum or Average 0.344123E+09 0.663089E+09 0.407261E+09 0.00 0.00 0.00 0.00 0.100643E+09 21428407.59
Minimum of Months 26028216.00 50239715.38 31070382.70 0.00 0.00 0.00 0.00 2412860.64 0.00
Maximum of Months 31037904.00 59407610.51 35434113.87 0.00 0.00 0.00 0.00 13616682.09 5189997.26



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.275885E+10 0.133015E+10 0.309350E+10 0.00 0.00 0.00 0.00 26030411.50 69467680.71
February 0.250666E+10 0.120947E+10 0.280279E+10 0.00 0.00 0.00 0.00 48953941.29 75760444.02
March 0.298913E+10 0.143018E+10 0.319643E+10 0.00 0.00 0.00 0.00 79404315.89 60754015.28
April 0.266505E+10 0.128992E+10 0.299752E+10 0.00 0.00 0.00 0.00 0.109457E+09 4700808.74
May 0.287399E+10 0.138006E+10 0.314497E+10 0.00 0.00 0.00 0.00 0.201554E+09 17278.51
June 0.286669E+10 0.137311E+10 0.308237E+10 0.00 0.00 0.00 0.00 0.183944E+09 0.00
July 0.267235E+10 0.129687E+10 0.306012E+10 0.00 0.00 0.00 0.00 0.146659E+09 7124.27
August 0.298913E+10 0.142997E+10 0.319643E+10 0.00 0.00 0.00 0.00 0.172066E+09 0.00
September 0.266505E+10 0.128971E+10 0.299752E+10 0.00 0.00 0.00 0.00 0.161359E+09 1032.93
October 0.275885E+10 0.133036E+10 0.309350E+10 0.00 0.00 0.00 0.00 0.147599E+09 6092.55
November 0.272290E+10 0.130656E+10 0.301283E+10 0.00 0.00 0.00 0.00 94877260.77 37527521.28
December 0.267235E+10 0.129687E+10 0.306012E+10 0.00 0.00 0.00 0.00 37351369.83 67566881.28
                   
Annual Sum or Average 0.331410E+11 0.159633E+11 0.367381E+11 0.00 0.00 0.00 0.00 0.140926E+10 0.315809E+09
Minimum of Months 0.250666E+10 0.120947E+10 0.280279E+10 0.00 0.00 0.00 0.00 26030411.50 0.00
Maximum of Months 0.298913E+10 0.143018E+10 0.319643E+10 0.00 0.00 0.00 0.00 0.201554E+09 75760444.02



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.125634E+10 0.605729E+09 0.140873E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.114150E+10 0.550776E+09 0.127635E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.136120E+10 0.651283E+09 0.145561E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.121362E+10 0.587411E+09 0.136503E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.130877E+10 0.628458E+09 0.143217E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.130544E+10 0.625293E+09 0.140367E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.121695E+10 0.590576E+09 0.139353E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.136120E+10 0.651188E+09 0.145561E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.121362E+10 0.587316E+09 0.136503E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.125634E+10 0.605825E+09 0.140873E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.123997E+10 0.594988E+09 0.137199E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.121695E+10 0.590576E+09 0.139353E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.150919E+11 0.726942E+10 0.167300E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.114150E+10 0.550776E+09 0.127635E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.136120E+10 0.651283E+09 0.145561E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 44561664.00 85948044.82 53344630.77 0.00 0.00 0.00 0.00 0.00 0.00
February 40488336.00 78150668.37 48331578.69 0.00 0.00 0.00 0.00 0.00 0.00
March 48281184.00 92411838.57 55119587.01 0.00 0.00 0.00 0.00 0.00 0.00
April 43046640.00 83348919.34 51689604.01 0.00 0.00 0.00 0.00 0.00 0.00
May 46421424.00 89173137.70 54232108.89 0.00 0.00 0.00 0.00 0.00 0.00
June 46303488.00 88724074.14 53152743.61 0.00 0.00 0.00 0.00 0.00 0.00
July 43164576.00 83797982.90 52768969.29 0.00 0.00 0.00 0.00 0.00 0.00
August 48281184.00 92398230.58 55119587.01 0.00 0.00 0.00 0.00 0.00 0.00
September 43046640.00 83335311.35 51689604.01 0.00 0.00 0.00 0.00 0.00 0.00
October 44561664.00 85961652.81 53344630.77 0.00 0.00 0.00 0.00 0.00 0.00
November 43981056.00 84423950.30 51953448.85 0.00 0.00 0.00 0.00 0.00 0.00
December 43164576.00 83797982.90 52768969.29 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.535302E+09 0.103147E+10 0.633515E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 40488336.00 78150668.37 48331578.69 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 48281184.00 92411838.57 55119587.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 22917427.20 0.110505E+09 17186263.19 0.00 0.00 0.00 0.00 0.00 0.00
February 20822572.80 0.100479E+09 15571187.20 0.00 0.00 0.00 0.00 0.00 0.00
March 24830323.20 0.118815E+09 17758108.28 0.00 0.00 0.00 0.00 0.00 0.00
April 22138272.00 0.107163E+09 16653056.29 0.00 0.00 0.00 0.00 0.00 0.00
May 23873875.20 0.114651E+09 17472185.74 0.00 0.00 0.00 0.00 0.00 0.00
June 23813222.40 0.114074E+09 17124442.10 0.00 0.00 0.00 0.00 0.00 0.00
July 22198924.80 0.107740E+09 17000799.92 0.00 0.00 0.00 0.00 0.00 0.00
August 24830323.20 0.118798E+09 17758108.28 0.00 0.00 0.00 0.00 0.00 0.00
September 22138272.00 0.107145E+09 16653056.29 0.00 0.00 0.00 0.00 0.00 0.00
October 22917427.20 0.110522E+09 17186263.19 0.00 0.00 0.00 0.00 0.00 0.00
November 22618828.80 0.108545E+09 16738060.29 0.00 0.00 0.00 0.00 0.00 0.00
December 22198924.80 0.107740E+09 17000799.92 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.275298E+09 0.132618E+10 0.204102E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 20822572.80 0.100479E+09 15571187.20 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24830323.20 0.118815E+09 17758108.28 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 17824665.60 85948044.82 13367164.08 0.00 0.00 0.00 0.00 0.00 0.00
February 16195334.40 78150668.37 12110987.24 0.00 0.00 0.00 0.00 0.00 0.00
March 19312473.60 92411838.57 13811934.83 0.00 0.00 0.00 0.00 0.00 0.00
April 17218656.00 83348919.34 12952445.41 0.00 0.00 0.00 0.00 0.00 0.00
May 18568569.60 89173137.70 13589549.46 0.00 0.00 0.00 0.00 0.00 0.00
June 18521395.20 88724074.14 13319080.76 0.00 0.00 0.00 0.00 0.00 0.00
July 17265830.40 83797982.90 13222914.11 0.00 0.00 0.00 0.00 0.00 0.00
August 19312473.60 92398230.58 13811934.83 0.00 0.00 0.00 0.00 0.00 0.00
September 17218656.00 83335311.35 12952445.41 0.00 0.00 0.00 0.00 0.00 0.00
October 17824665.60 85961652.81 13367164.08 0.00 0.00 0.00 0.00 0.00 0.00
November 17592422.40 84423950.30 13018559.98 0.00 0.00 0.00 0.00 0.00 0.00
December 17265830.40 83797982.90 13222914.11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.214121E+09 0.103147E+10 0.158747E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16195334.40 78150668.37 12110987.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19312473.60 92411838.57 13811934.83 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.101016E+10 0.811732E+09 0.830411E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.917825E+09 0.738090E+09 0.752373E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.109448E+10 0.872778E+09 0.858042E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.975819E+09 0.787184E+09 0.804647E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.105232E+10 0.842191E+09 0.844226E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.104965E+10 0.837950E+09 0.827424E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.978492E+09 0.791425E+09 0.821450E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.109448E+10 0.872650E+09 0.858042E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.975819E+09 0.787056E+09 0.804647E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.101016E+10 0.811860E+09 0.830411E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.997001E+09 0.797337E+09 0.808755E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.978492E+09 0.791425E+09 0.821450E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.121347E+11 0.974168E+10 0.986188E+10 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.917825E+09 0.738090E+09 0.752373E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.109448E+10 0.872778E+09 0.858042E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.481266E+09 0.232060E+10 0.395666E+10 0.00 0.00 0.00 0.00 9993040.64 80928154.35
February 0.437274E+09 0.211007E+10 0.358484E+10 0.00 0.00 0.00 0.00 17184173.44 96161605.41
March 0.521437E+09 0.249512E+10 0.408832E+10 0.00 0.00 0.00 0.00 24376685.12 76633278.45
April 0.464904E+09 0.225042E+10 0.383391E+10 0.00 0.00 0.00 0.00 39935573.45 13151882.61
May 0.501351E+09 0.240767E+10 0.402249E+10 0.00 0.00 0.00 0.00 0.103809E+09 722040.01
June 0.500078E+09 0.239555E+10 0.394243E+10 0.00 0.00 0.00 0.00 0.109272E+09 13680.78
July 0.466177E+09 0.226255E+10 0.391397E+10 0.00 0.00 0.00 0.00 87979408.79 206192.06
August 0.521437E+09 0.249475E+10 0.408832E+10 0.00 0.00 0.00 0.00 0.105553E+09 26985.28
September 0.464904E+09 0.225005E+10 0.383391E+10 0.00 0.00 0.00 0.00 97154847.98 30727.87
October 0.481266E+09 0.232096E+10 0.395666E+10 0.00 0.00 0.00 0.00 79751353.24 655966.03
November 0.474995E+09 0.227945E+10 0.385348E+10 0.00 0.00 0.00 0.00 46351307.71 50850016.31
December 0.466177E+09 0.226255E+10 0.391397E+10 0.00 0.00 0.00 0.00 14004250.27 79507315.36
                   
Annual Sum or Average 0.578127E+10 0.278497E+11 0.469889E+11 0.00 0.00 0.00 0.00 0.735364E+09 0.398888E+09
Minimum of Months 0.437274E+09 0.211007E+10 0.358484E+10 0.00 0.00 0.00 0.00 9993040.64 13680.78
Maximum of Months 0.521437E+09 0.249512E+10 0.408832E+10 0.00 0.00 0.00 0.00 0.109272E+09 96161605.41



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.244453E+09 0.117872E+10 0.200973E+10 0.00 0.00 0.00 0.00 7368843.99 62642045.77
February 0.222107E+09 0.107178E+10 0.182087E+10 0.00 0.00 0.00 0.00 12986972.90 74397715.39
March 0.264857E+09 0.126736E+10 0.207660E+10 0.00 0.00 0.00 0.00 17483770.73 59678859.32
April 0.236142E+09 0.114307E+10 0.194738E+10 0.00 0.00 0.00 0.00 28888626.76 11271776.62
May 0.254655E+09 0.122295E+10 0.204317E+10 0.00 0.00 0.00 0.00 75950700.94 748048.84
June 0.254008E+09 0.121679E+10 0.200250E+10 0.00 0.00 0.00 0.00 81026579.89 23412.55
July 0.236789E+09 0.114923E+10 0.198805E+10 0.00 0.00 0.00 0.00 65280033.57 243444.19
August 0.264857E+09 0.126718E+10 0.207660E+10 0.00 0.00 0.00 0.00 78684184.85 61424.74
September 0.236142E+09 0.114288E+10 0.194738E+10 0.00 0.00 0.00 0.00 71884990.80 66316.64
October 0.244453E+09 0.117890E+10 0.200973E+10 0.00 0.00 0.00 0.00 57742792.67 751880.12
November 0.241268E+09 0.115781E+10 0.195732E+10 0.00 0.00 0.00 0.00 33930343.46 39996749.81
December 0.236789E+09 0.114923E+10 0.198805E+10 0.00 0.00 0.00 0.00 9884360.98 61583912.48
                   
Annual Sum or Average 0.293652E+10 0.141459E+11 0.238674E+11 0.00 0.00 0.00 0.00 0.541112E+09 0.311466E+09
Minimum of Months 0.222107E+09 0.107178E+10 0.182087E+10 0.00 0.00 0.00 0.00 7368843.99 23412.55
Maximum of Months 0.264857E+09 0.126736E+10 0.207660E+10 0.00 0.00 0.00 0.00 81026579.89 74397715.39



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 45834854.40 0.368349E+09 34372526.38 0.00 0.00 0.00 0.00 0.00 0.00
February 41645145.60 0.334931E+09 31142374.40 0.00 0.00 0.00 0.00 0.00 0.00
March 49660646.40 0.396051E+09 35516216.56 0.00 0.00 0.00 0.00 0.00 0.00
April 44276544.00 0.357210E+09 33306112.57 0.00 0.00 0.00 0.00 0.00 0.00
May 47747750.40 0.382171E+09 34944371.47 0.00 0.00 0.00 0.00 0.00 0.00
June 47626444.80 0.380246E+09 34248884.20 0.00 0.00 0.00 0.00 0.00 0.00
July 44397849.60 0.359134E+09 34001599.84 0.00 0.00 0.00 0.00 0.00 0.00
August 49660646.40 0.395992E+09 35516216.56 0.00 0.00 0.00 0.00 0.00 0.00
September 44276544.00 0.357151E+09 33306112.57 0.00 0.00 0.00 0.00 0.00 0.00
October 45834854.40 0.368407E+09 34372526.38 0.00 0.00 0.00 0.00 0.00 0.00
November 45237657.60 0.361817E+09 33476120.57 0.00 0.00 0.00 0.00 0.00 0.00
December 44397849.60 0.359134E+09 34001599.84 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.550597E+09 0.442059E+10 0.408205E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 41645145.60 0.334931E+09 31142374.40 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 49660646.40 0.396051E+09 35516216.56 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.253944E+09 0.717825E+09 0.100138E+10 0.00 0.00 0.00 0.00 7974722.11 36744911.29
February 0.230571E+09 0.652703E+09 0.907273E+09 0.00 0.00 0.00 0.00 14579926.10 41923767.02
March 0.274899E+09 0.771810E+09 0.103470E+10 0.00 0.00 0.00 0.00 20992564.08 33847431.50
April 0.244892E+09 0.696118E+09 0.970310E+09 0.00 0.00 0.00 0.00 29476489.03 4386195.81
May 0.264422E+09 0.744761E+09 0.101804E+10 0.00 0.00 0.00 0.00 66727174.01 163836.13
June 0.263616E+09 0.741010E+09 0.997776E+09 0.00 0.00 0.00 0.00 66226711.91 12045.35
July 0.245698E+09 0.699868E+09 0.990572E+09 0.00 0.00 0.00 0.00 52167457.63 102230.59
August 0.274899E+09 0.771696E+09 0.103470E+10 0.00 0.00 0.00 0.00 63967176.82 5617.64
September 0.244892E+09 0.696004E+09 0.970310E+09 0.00 0.00 0.00 0.00 59440270.02 11600.58
October 0.253944E+09 0.717939E+09 0.100138E+10 0.00 0.00 0.00 0.00 52873894.38 82185.54
November 0.250906E+09 0.705096E+09 0.975263E+09 0.00 0.00 0.00 0.00 32819576.97 21207268.25
December 0.245698E+09 0.699868E+09 0.990572E+09 0.00 0.00 0.00 0.00 12227906.02 35566661.70
                   
Annual Sum or Average 0.304838E+10 0.861470E+10 0.118923E+11 0.00 0.00 0.00 0.00 0.479474E+09 0.174054E+09
Minimum of Months 0.230571E+09 0.652703E+09 0.907273E+09 0.00 0.00 0.00 0.00 7974722.11 5617.64
Maximum of Months 0.274899E+09 0.771810E+09 0.103470E+10 0.00 0.00 0.00 0.00 66727174.01 41923767.02



Table of Contents

Report: SpaceGainsMonthly

For: NE STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 89123328.00 0.182837E+09 0.106689E+09 0.00 0.00 0.00 0.00 11760584.61 71164331.29
February 80976672.00 0.166249E+09 96663157.38 0.00 0.00 0.00 0.00 21537892.36 86406354.44
March 96562368.00 0.196587E+09 0.110239E+09 0.00 0.00 0.00 0.00 26547276.79 70883611.96
April 86093280.00 0.177307E+09 0.103379E+09 0.00 0.00 0.00 0.00 42897862.84 19091257.26
May 92842848.00 0.189697E+09 0.108464E+09 0.00 0.00 0.00 0.00 99712390.01 3821107.95
June 92606976.00 0.188742E+09 0.106305E+09 0.00 0.00 0.00 0.00 0.110079E+09 1001708.18
July 86329152.00 0.178263E+09 0.105538E+09 0.00 0.00 0.00 0.00 91992377.20 1446525.83
August 96562368.00 0.196558E+09 0.110239E+09 0.00 0.00 0.00 0.00 0.112118E+09 571888.06
September 86093280.00 0.177279E+09 0.103379E+09 0.00 0.00 0.00 0.00 0.103233E+09 801352.59
October 89123328.00 0.182866E+09 0.106689E+09 0.00 0.00 0.00 0.00 81377290.21 2462905.74
November 87962112.00 0.179594E+09 0.103907E+09 0.00 0.00 0.00 0.00 46377362.37 47841091.17
December 86329152.00 0.178263E+09 0.105538E+09 0.00 0.00 0.00 0.00 15588631.76 72225632.65
                   
Annual Sum or Average 0.107060E+10 0.219424E+10 0.126703E+10 0.00 0.00 0.00 0.00 0.763222E+09 0.377718E+09
Minimum of Months 80976672.00 0.166249E+09 96663157.38 0.00 0.00 0.00 0.00 11760584.61 571888.06
Maximum of Months 96562368.00 0.196587E+09 0.110239E+09 0.00 0.00 0.00 0.00 0.112118E+09 86406354.44



Table of Contents

Report: SpaceGainsMonthly

For: NW ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 22280832.00 0.152364E+09 88907770.82 0.00 0.00 0.00 0.00 9637335.32 71214858.25
February 20244168.00 0.138541E+09 80552679.05 0.00 0.00 0.00 0.00 16034284.49 88282708.54
March 24140592.00 0.163822E+09 91866032.98 0.00 0.00 0.00 0.00 19246377.25 80018766.10
April 21523320.00 0.147756E+09 86149391.24 0.00 0.00 0.00 0.00 31408940.60 26923316.31
May 23210712.00 0.158081E+09 90386901.90 0.00 0.00 0.00 0.00 75495877.34 3972951.61
June 23151744.00 0.157285E+09 88587958.69 0.00 0.00 0.00 0.00 88939633.15 659262.77
July 21582288.00 0.148552E+09 87948334.44 0.00 0.00 0.00 0.00 72905933.73 1155403.99
August 24140592.00 0.163798E+09 91866032.98 0.00 0.00 0.00 0.00 87486114.20 523034.48
September 21523320.00 0.147732E+09 86149391.24 0.00 0.00 0.00 0.00 80778227.14 898246.78
October 22280832.00 0.152388E+09 88907770.82 0.00 0.00 0.00 0.00 59512556.22 3004331.59
November 21990528.00 0.149662E+09 86589132.91 0.00 0.00 0.00 0.00 35127214.70 48053864.33
December 21582288.00 0.148552E+09 87948334.44 0.00 0.00 0.00 0.00 11428012.22 72920190.12
                   
Annual Sum or Average 0.267651E+09 0.182853E+10 0.105586E+10 0.00 0.00 0.00 0.00 0.588001E+09 0.397627E+09
Minimum of Months 20244168.00 0.138541E+09 80552679.05 0.00 0.00 0.00 0.00 9637335.32 523034.48
Maximum of Months 24140592.00 0.163822E+09 91866032.98 0.00 0.00 0.00 0.00 88939633.15 88282708.54



Table of Contents

Report: SpaceGainsMonthly

For: NW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.101855E+09 0.208956E+09 0.121931E+09 0.00 0.00 0.00 0.00 14666868.67 86548435.02
February 92544768.00 0.189999E+09 0.110472E+09 0.00 0.00 0.00 0.00 25399928.64 0.107938E+09
March 0.110357E+09 0.224671E+09 0.125988E+09 0.00 0.00 0.00 0.00 29023815.76 93006614.15
April 98392320.00 0.202637E+09 0.118148E+09 0.00 0.00 0.00 0.00 45523453.92 31156713.68
May 0.106106E+09 0.216797E+09 0.123959E+09 0.00 0.00 0.00 0.00 0.105078E+09 6963678.36
June 0.105837E+09 0.215705E+09 0.121492E+09 0.00 0.00 0.00 0.00 0.121487E+09 1728954.23
July 98661888.00 0.203729E+09 0.120615E+09 0.00 0.00 0.00 0.00 0.102122E+09 2358976.77
August 0.110357E+09 0.224638E+09 0.125988E+09 0.00 0.00 0.00 0.00 0.123811E+09 1014146.90
September 98392320.00 0.202604E+09 0.118148E+09 0.00 0.00 0.00 0.00 0.115133E+09 1831811.57
October 0.101855E+09 0.208989E+09 0.121931E+09 0.00 0.00 0.00 0.00 88448939.70 4328690.86
November 0.100528E+09 0.205251E+09 0.118751E+09 0.00 0.00 0.00 0.00 50565840.34 59036380.52
December 98661888.00 0.203729E+09 0.120615E+09 0.00 0.00 0.00 0.00 17849428.24 90064335.67
                   
Annual Sum or Average 0.122355E+10 0.250770E+10 0.144804E+10 0.00 0.00 0.00 0.00 0.839109E+09 0.485976E+09
Minimum of Months 92544768.00 0.189999E+09 0.110472E+09 0.00 0.00 0.00 0.00 14666868.67 1014146.90
Maximum of Months 0.110357E+09 0.224671E+09 0.125988E+09 0.00 0.00 0.00 0.00 0.123811E+09 0.107938E+09



Table of Contents

Report: SpaceGainsMonthly

For: SW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 50927616.00 0.104478E+09 60965382.94 0.00 0.00 0.00 0.00 5132559.49 58859514.14
February 46272384.00 94999583.58 55236172.04 0.00 0.00 0.00 0.00 10199180.16 72254699.84
March 55178496.00 0.112335E+09 62993907.37 0.00 0.00 0.00 0.00 12526521.20 63328115.05
April 49196160.00 0.101319E+09 59073920.97 0.00 0.00 0.00 0.00 21446306.70 21600834.75
May 53053056.00 0.108398E+09 61979645.16 0.00 0.00 0.00 0.00 53292799.11 3873852.56
June 52918272.00 0.107853E+09 60746083.00 0.00 0.00 0.00 0.00 62888364.15 786599.01
July 49330944.00 0.101864E+09 60307483.12 0.00 0.00 0.00 0.00 52343621.42 1166067.43
August 55178496.00 0.112319E+09 62993907.37 0.00 0.00 0.00 0.00 62307650.50 559371.07
September 49196160.00 0.101302E+09 59073920.97 0.00 0.00 0.00 0.00 56775626.22 1227534.95
October 50927616.00 0.104495E+09 60965382.94 0.00 0.00 0.00 0.00 39699477.05 3440901.25
November 50264064.00 0.102625E+09 59375458.38 0.00 0.00 0.00 0.00 22058934.59 41229563.13
December 49330944.00 0.101864E+09 60307483.12 0.00 0.00 0.00 0.00 6873416.98 59825783.18
                   
Annual Sum or Average 0.611774E+09 0.125385E+10 0.724019E+09 0.00 0.00 0.00 0.00 0.405544E+09 0.328153E+09
Minimum of Months 46272384.00 94999583.58 55236172.04 0.00 0.00 0.00 0.00 5132559.49 559371.07
Maximum of Months 55178496.00 0.112335E+09 62993907.37 0.00 0.00 0.00 0.00 62888364.15 72254699.84



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 233.30 02-JAN-07:10 145.80 02-JAN-07:10 213.96 02-JAN-06:10 0.00 0.00 0.00 0.00 16.80 13-JAN-19:20 19.48 24-JAN-03:00
February 233.30 01-FEB-07:10 145.80 01-FEB-07:10 213.96 01-FEB-06:10 0.00 0.00 0.00 0.00 13.96 20-FEB-15:30 31.68 04-FEB-04:50
March 233.30 01-MAR-07:10 145.80 01-MAR-07:10 213.96 01-MAR-06:10 0.00 0.00 0.00 0.00 20.55 05-MAR-16:10 32.20 16-MAR-01:53
April 233.30 03-APR-06:10 145.80 03-APR-06:10 213.96 03-APR-05:10 0.00 0.00 0.00 0.00 23.91 23-APR-09:50 8.71 19-APR-03:00
May 233.30 01-MAY-06:10 145.80 01-MAY-06:10 213.96 01-MAY-05:10 0.00 0.00 0.00 0.00 37.31 29-MAY-17:00 2.57 07-MAY-06:00
June 233.30 01-JUN-06:10 145.80 01-JUN-06:10 213.96 01-JUN-05:10 0.00 0.00 0.00 0.00 30.72 18-JUN-13:00 0.00 01-JUN-00:01
July 233.30 03-JUL-06:10 145.80 03-JUL-06:10 213.96 03-JUL-05:10 0.00 0.00 0.00 0.00 37.85 30-JUL-16:00 0.00 14-JUL-18:40
August 233.30 01-AUG-06:10 145.80 01-AUG-06:10 213.96 01-AUG-05:10 0.00 0.00 0.00 0.00 30.76 13-AUG-12:30 0.00 14-AUG-03:05
September 233.30 01-SEP-06:10 145.80 01-SEP-06:10 213.96 01-SEP-05:10 0.00 0.00 0.00 0.00 29.67 17-SEP-16:30 0.00 01-SEP-00:03
October 233.30 02-OCT-06:10 145.80 02-OCT-06:10 213.96 02-OCT-05:10 0.00 0.00 0.00 0.00 24.21 01-OCT-13:20 2.26 16-OCT-03:03
November 233.30 01-NOV-06:10 145.80 01-NOV-06:10 213.96 01-NOV-05:10 0.00 0.00 0.00 0.00 19.20 22-NOV-19:50 29.65 11-NOV-09:00
December 233.30 01-DEC-07:10 145.80 01-DEC-07:10 213.96 01-DEC-06:10 0.00 0.00 0.00 0.00 22.01 10-DEC-14:50 31.69 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 233.30   145.80   213.96   0.00 0.00 0.00 0.00 13.96   0.00  
Maximum of Months 233.30   145.80   213.96   0.00 0.00 0.00 0.00 37.85   32.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 12.10 02-JAN-07:10 45.36 02-JAN-07:10 5.57 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 12.10 01-FEB-07:10 45.36 01-FEB-07:10 5.57 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 12.10 01-MAR-07:10 45.36 01-MAR-07:10 5.57 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 12.10 03-APR-06:10 45.36 03-APR-06:10 5.57 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 12.10 01-MAY-06:10 45.36 01-MAY-06:10 5.57 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 12.10 01-JUN-06:10 45.36 01-JUN-06:10 5.57 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 12.10 03-JUL-06:10 45.36 03-JUL-06:10 5.57 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 12.10 01-AUG-06:10 45.36 01-AUG-06:10 5.57 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 12.10 01-SEP-06:10 45.36 01-SEP-06:10 5.57 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 12.10 02-OCT-06:10 45.36 02-OCT-06:10 5.57 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 12.10 01-NOV-06:10 45.36 01-NOV-06:10 5.57 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 12.10 01-DEC-07:10 45.36 01-DEC-07:10 5.57 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 12.10   45.36   5.57   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12.10   45.36   5.57   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 4536.44 02-JAN-07:10 340.20 02-JAN-07:10 415.84 02-JAN-06:10 0.00 0.00 0.00 0.00 7.95 07-JAN-13:00 47.95 24-JAN-03:00
February 4536.44 01-FEB-07:10 340.20 01-FEB-07:10 415.84 01-FEB-06:10 0.00 0.00 0.00 0.00 8.93 02-FEB-14:00 81.43 04-FEB-04:52
March 4536.44 01-MAR-07:10 340.20 01-MAR-07:10 415.84 01-MAR-06:10 0.00 0.00 0.00 0.00 14.99 05-MAR-14:00 79.48 16-MAR-01:53
April 4536.44 03-APR-06:10 340.20 03-APR-06:10 415.84 03-APR-05:10 0.00 0.00 0.00 0.00 23.24 16-APR-13:00 24.83 18-APR-23:52
May 4536.44 01-MAY-06:10 340.20 01-MAY-06:10 415.84 01-MAY-05:10 0.00 0.00 0.00 0.00 45.04 29-MAY-16:00 12.41 25-MAY-04:51
June 4536.44 01-JUN-06:10 340.20 01-JUN-06:10 415.84 01-JUN-05:10 0.00 0.00 0.00 0.00 29.41 25-JUN-14:00 6.20 18-JUN-20:00
July 4536.44 03-JUL-06:10 340.20 03-JUL-06:10 415.84 03-JUL-05:10 0.00 0.00 0.00 0.00 37.97 30-JUL-15:52 6.98 02-JUL-16:00
August 4536.44 01-AUG-06:10 340.20 01-AUG-06:10 415.84 01-AUG-05:10 0.00 0.00 0.00 0.00 33.22 13-AUG-13:00 11.72 14-AUG-03:00
September 4536.44 01-SEP-06:10 340.20 01-SEP-06:10 415.84 01-SEP-05:10 0.00 0.00 0.00 0.00 33.51 17-SEP-14:00 4.71 02-SEP-21:52
October 4536.44 02-OCT-06:10 340.20 02-OCT-06:10 415.84 02-OCT-05:10 0.00 0.00 0.00 0.00 25.88 29-OCT-13:51 11.95 16-OCT-05:00
November 4536.44 01-NOV-06:10 340.20 01-NOV-06:10 415.84 01-NOV-05:10 0.00 0.00 0.00 0.00 11.53 23-NOV-11:53 77.68 11-NOV-09:00
December 4536.44 01-DEC-07:10 340.20 01-DEC-07:10 415.84 01-DEC-06:10 0.00 0.00 0.00 0.00 21.49 10-DEC-14:53 77.53 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 4536.44   340.20   415.84   0.00 0.00 0.00 0.00 7.95   4.71  
Maximum of Months 4536.44   340.20   415.84   0.00 0.00 0.00 0.00 45.04   81.43  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 CLEAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 272.19 02-JAN-07:10 170.10 02-JAN-07:10 249.62 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 272.19 01-FEB-07:10 170.10 01-FEB-07:10 249.62 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 272.19 01-MAR-07:10 170.10 01-MAR-07:10 249.62 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 272.19 03-APR-06:10 170.10 03-APR-06:10 249.62 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 272.19 01-MAY-06:10 170.10 01-MAY-06:10 249.62 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 272.19 01-JUN-06:10 170.10 01-JUN-06:10 249.62 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 272.19 03-JUL-06:10 170.10 03-JUL-06:10 249.62 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 272.19 01-AUG-06:10 170.10 01-AUG-06:10 249.62 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 272.19 01-SEP-06:10 170.10 01-SEP-06:10 249.62 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 272.19 02-OCT-06:10 170.10 02-OCT-06:10 249.62 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 272.19 01-NOV-06:10 170.10 01-NOV-06:10 249.62 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 272.19 01-DEC-07:10 170.10 01-DEC-07:10 249.62 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 272.19   170.10   249.62   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 272.19   170.10   249.62   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 356.43 02-JAN-07:10 222.75 02-JAN-07:10 326.89 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 356.43 01-FEB-07:10 222.75 01-FEB-07:10 326.89 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 356.43 01-MAR-07:10 222.75 01-MAR-07:10 326.89 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 356.43 03-APR-06:10 222.75 03-APR-06:10 326.89 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 356.43 01-MAY-06:10 222.75 01-MAY-06:10 326.89 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 356.43 01-JUN-06:10 222.75 01-JUN-06:10 326.89 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 356.43 03-JUL-06:10 222.75 03-JUL-06:10 326.89 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 356.43 01-AUG-06:10 222.75 01-AUG-06:10 326.89 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 356.43 01-SEP-06:10 222.75 01-SEP-06:10 326.89 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 356.43 02-OCT-06:10 222.75 02-OCT-06:10 326.89 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 356.43 01-NOV-06:10 222.75 01-NOV-06:10 326.89 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 356.43 01-DEC-07:10 222.75 01-DEC-07:10 326.89 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 356.43   222.75   326.89   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 356.43   222.75   326.89   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 68.05 02-JAN-07:10 124.74 02-JAN-07:10 137.27 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 68.05 01-FEB-07:10 124.74 01-FEB-07:10 137.27 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 68.05 01-MAR-07:10 124.74 01-MAR-07:10 137.27 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 68.05 03-APR-06:10 124.74 03-APR-06:10 137.27 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 68.05 01-MAY-06:10 124.74 01-MAY-06:10 137.27 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 68.05 01-JUN-06:10 124.74 01-JUN-06:10 137.27 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 68.05 03-JUL-06:10 124.74 03-JUL-06:10 137.27 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 68.05 01-AUG-06:10 124.74 01-AUG-06:10 137.27 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 68.05 01-SEP-06:10 124.74 01-SEP-06:10 137.27 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 68.05 02-OCT-06:10 124.74 02-OCT-06:10 137.27 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 68.05 01-NOV-06:10 124.74 01-NOV-06:10 137.27 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 68.05 01-DEC-07:10 124.74 01-DEC-07:10 137.27 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 68.05   124.74   137.27   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 68.05   124.74   137.27   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 24.30 02-JAN-07:10 44.55 02-JAN-07:10 49.03 02-JAN-06:10 0.00 0.00 0.00 0.00 7.73 15-JAN-14:00 17.44 24-JAN-03:00
February 24.30 01-FEB-07:10 44.55 01-FEB-07:10 49.03 01-FEB-06:10 0.00 0.00 0.00 0.00 7.24 20-FEB-15:30 29.97 04-FEB-04:50
March 24.30 01-MAR-07:10 44.55 01-MAR-07:10 49.03 01-MAR-06:10 0.00 0.00 0.00 0.00 8.55 13-MAR-18:01 28.99 16-MAR-01:53
April 24.30 03-APR-06:10 44.55 03-APR-06:10 49.03 03-APR-05:10 0.00 0.00 0.00 0.00 11.20 16-APR-12:51 8.48 18-APR-23:52
May 24.30 01-MAY-06:10 44.55 01-MAY-06:10 49.03 01-MAY-05:10 0.00 0.00 0.00 0.00 21.13 29-MAY-16:15 3.08 07-MAY-06:00
June 24.30 01-JUN-06:10 44.55 01-JUN-06:10 49.03 01-JUN-05:10 0.00 0.00 0.00 0.00 14.29 17-JUN-18:20 1.59 18-JUN-19:10
July 24.30 03-JUL-06:10 44.55 03-JUL-06:10 49.03 03-JUL-05:10 0.00 0.00 0.00 0.00 17.12 30-JUL-15:35 2.91 02-JUL-15:50
August 24.30 01-AUG-06:10 44.55 01-AUG-06:10 49.03 01-AUG-05:10 0.00 0.00 0.00 0.00 15.33 13-AUG-12:27 4.13 14-AUG-02:53
September 24.30 01-SEP-06:10 44.55 01-SEP-06:10 49.03 01-SEP-05:10 0.00 0.00 0.00 0.00 16.00 17-SEP-13:45 1.68 02-SEP-22:00
October 24.30 02-OCT-06:10 44.55 02-OCT-06:10 49.03 02-OCT-05:10 0.00 0.00 0.00 0.00 12.92 29-OCT-13:53 3.40 16-OCT-02:53
November 24.30 01-NOV-06:10 44.55 01-NOV-06:10 49.03 01-NOV-05:10 0.00 0.00 0.00 0.00 8.65 22-NOV-21:20 27.45 11-NOV-09:00
December 24.30 01-DEC-07:10 44.55 01-DEC-07:10 49.03 01-DEC-06:10 0.00 0.00 0.00 0.00 11.86 10-DEC-14:50 28.07 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 24.30   44.55   49.03   0.00 0.00 0.00 0.00 7.24   1.59  
Maximum of Months 24.30   44.55   49.03   0.00 0.00 0.00 0.00 21.13   29.97  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15.88 02-JAN-07:10 132.30 02-JAN-07:10 485.33 02-JAN-06:10 0.00 0.00 0.00 0.00 4.47 15-JAN-14:20 17.37 24-JAN-03:00
February 15.88 01-FEB-07:10 132.30 01-FEB-07:10 485.33 01-FEB-06:10 0.00 0.00 0.00 0.00 5.00 20-FEB-15:10 29.05 04-FEB-04:50
March 15.88 01-MAR-07:10 132.30 01-MAR-07:10 485.33 01-MAR-06:10 0.00 0.00 0.00 0.00 6.98 05-MAR-13:50 29.40 16-MAR-01:53
April 15.88 03-APR-06:10 132.30 03-APR-06:10 485.33 03-APR-05:10 0.00 0.00 0.00 0.00 8.94 16-APR-18:00 9.31 18-APR-23:52
May 15.88 01-MAY-06:10 132.30 01-MAY-06:10 485.33 01-MAY-05:10 0.00 0.00 0.00 0.00 17.88 29-MAY-16:20 5.29 25-MAY-05:00
June 15.88 01-JUN-06:10 132.30 01-JUN-06:10 485.33 01-JUN-05:10 0.00 0.00 0.00 0.00 11.72 18-JUN-15:00 2.46 18-JUN-20:20
July 15.88 03-JUL-06:10 132.30 03-JUL-06:10 485.33 03-JUL-05:10 0.00 0.00 0.00 0.00 14.67 30-JUL-16:00 3.25 02-JUL-15:50
August 15.88 01-AUG-06:10 132.30 01-AUG-06:10 485.33 01-AUG-05:10 0.00 0.00 0.00 0.00 12.92 13-AUG-12:50 5.10 14-AUG-03:05
September 15.88 01-SEP-06:10 132.30 01-SEP-06:10 485.33 01-SEP-05:10 0.00 0.00 0.00 0.00 13.18 17-SEP-16:50 1.92 26-SEP-03:40
October 15.88 02-OCT-06:10 132.30 02-OCT-06:10 485.33 02-OCT-05:10 0.00 0.00 0.00 0.00 10.36 29-OCT-14:00 4.92 16-OCT-05:00
November 15.88 01-NOV-06:10 132.30 01-NOV-06:10 485.33 01-NOV-05:10 0.00 0.00 0.00 0.00 6.02 23-NOV-12:00 28.16 11-NOV-09:00
December 15.88 01-DEC-07:10 132.30 01-DEC-07:10 485.33 01-DEC-06:10 0.00 0.00 0.00 0.00 9.58 10-DEC-15:00 27.58 15-DEC-04:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15.88   132.30   485.33   0.00 0.00 0.00 0.00 4.47   1.92  
Maximum of Months 15.88   132.30   485.33   0.00 0.00 0.00 0.00 17.88   29.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 14.74 02-JAN-07:10 122.85 02-JAN-07:10 696.20 02-JAN-07:10 0.00 0.00 0.00 0.00 7.95 07-JAN-13:00 50.39 24-JAN-03:00
February 14.74 01-FEB-07:10 122.85 01-FEB-07:10 696.20 01-FEB-07:10 0.00 0.00 0.00 0.00 9.60 02-FEB-14:00 82.85 04-FEB-04:52
March 14.74 01-MAR-07:10 122.85 01-MAR-07:10 696.20 01-MAR-07:10 0.00 0.00 0.00 0.00 14.99 05-MAR-14:00 81.42 16-MAR-01:53
April 14.74 03-APR-06:10 122.85 03-APR-06:10 696.20 01-APR-06:10 0.00 0.00 0.00 0.00 23.24 16-APR-12:55 25.84 18-APR-23:52
May 14.74 01-MAY-06:10 122.85 01-MAY-06:10 696.20 01-MAY-06:10 0.00 0.00 0.00 0.00 45.04 29-MAY-15:53 12.41 25-MAY-04:51
June 14.74 01-JUN-06:10 122.85 01-JUN-06:10 696.20 01-JUN-06:10 0.00 0.00 0.00 0.00 29.40 25-JUN-14:00 6.20 18-JUN-20:00
July 14.74 03-JUL-06:10 122.85 03-JUL-06:10 696.20 01-JUL-06:10 0.00 0.00 0.00 0.00 37.97 30-JUL-16:00 6.98 02-JUL-15:54
August 14.74 01-AUG-06:10 122.85 01-AUG-06:10 696.20 01-AUG-06:10 0.00 0.00 0.00 0.00 33.22 13-AUG-13:00 11.72 14-AUG-03:00
September 14.74 01-SEP-06:10 122.85 01-SEP-06:10 696.20 01-SEP-06:10 0.00 0.00 0.00 0.00 33.51 17-SEP-14:00 4.71 02-SEP-21:52
October 14.74 02-OCT-06:10 122.85 02-OCT-06:10 696.20 02-OCT-06:10 0.00 0.00 0.00 0.00 25.88 29-OCT-14:00 11.95 16-OCT-04:51
November 14.74 01-NOV-06:10 122.85 01-NOV-06:10 696.20 01-NOV-06:10 0.00 0.00 0.00 0.00 11.53 23-NOV-11:53 77.68 11-NOV-09:00
December 14.74 01-DEC-07:10 122.85 01-DEC-07:10 696.20 01-DEC-07:10 0.00 0.00 0.00 0.00 21.49 10-DEC-14:53 78.68 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 14.74   122.85   696.20   0.00 0.00 0.00 0.00 7.95   4.71  
Maximum of Months 14.74   122.85   696.20   0.00 0.00 0.00 0.00 45.04   82.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 29.16 02-JAN-07:10 53.46 02-JAN-07:10 58.83 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 29.16 01-FEB-07:10 53.46 01-FEB-07:10 58.83 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 29.16 01-MAR-07:10 53.46 01-MAR-07:10 58.83 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 29.16 03-APR-06:10 53.46 03-APR-06:10 58.83 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 29.16 01-MAY-06:10 53.46 01-MAY-06:10 58.83 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 29.16 01-JUN-06:10 53.46 01-JUN-06:10 58.83 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 29.16 03-JUL-06:10 53.46 03-JUL-06:10 58.83 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 29.16 01-AUG-06:10 53.46 01-AUG-06:10 58.83 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 29.16 01-SEP-06:10 53.46 01-SEP-06:10 58.83 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 29.16 02-OCT-06:10 53.46 02-OCT-06:10 58.83 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 29.16 01-NOV-06:10 53.46 01-NOV-06:10 58.83 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 29.16 01-DEC-07:10 53.46 01-DEC-07:10 58.83 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 29.16   53.46   58.83   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 29.16   53.46   58.83   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 IT HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 75.60 02-JAN-07:10 120.62 02-JAN-07:10 55.52 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 75.60 01-FEB-07:10 120.62 01-FEB-07:10 55.52 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 75.60 01-MAR-07:10 120.62 01-MAR-07:10 55.52 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 75.60 03-APR-06:10 120.62 03-APR-06:10 55.52 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 75.60 01-MAY-06:10 120.62 01-MAY-06:10 55.52 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 75.60 01-JUN-06:10 120.62 01-JUN-06:10 55.52 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 75.60 03-JUL-06:10 120.62 03-JUL-06:10 55.52 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 75.60 01-AUG-06:10 120.62 01-AUG-06:10 55.52 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 75.60 01-SEP-06:10 120.62 01-SEP-06:10 55.52 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 75.60 02-OCT-06:10 120.62 02-OCT-06:10 55.52 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 75.60 01-NOV-06:10 120.62 01-NOV-06:10 55.52 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 75.60 01-DEC-07:10 120.62 01-DEC-07:10 55.52 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 75.60   120.62   55.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 75.60   120.62   55.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 60.49 02-JAN-07:10 110.88 02-JAN-07:10 122.02 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 60.49 01-FEB-07:10 110.88 01-FEB-07:10 122.02 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 60.49 01-MAR-07:10 110.88 01-MAR-07:10 122.02 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 60.49 03-APR-06:10 110.88 03-APR-06:10 122.02 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 60.49 01-MAY-06:10 110.88 01-MAY-06:10 122.02 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 60.49 01-JUN-06:10 110.88 01-JUN-06:10 122.02 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 60.49 03-JUL-06:10 110.88 03-JUL-06:10 122.02 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 60.49 01-AUG-06:10 110.88 01-AUG-06:10 122.02 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 60.49 01-SEP-06:10 110.88 01-SEP-06:10 122.02 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 60.49 02-OCT-06:10 110.88 02-OCT-06:10 122.02 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 60.49 01-NOV-06:10 110.88 01-NOV-06:10 122.02 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 60.49 01-DEC-07:10 110.88 01-DEC-07:10 122.02 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 60.49   110.88   122.02   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 60.49   110.88   122.02   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 LOBBY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 671.83 02-JAN-07:10 727.74 02-JAN-07:10 677.66 02-JAN-06:10 0.00 0.00 0.00 0.00 18.18 15-JAN-12:00 51.29 24-JAN-03:00
February 671.83 01-FEB-07:10 727.74 01-FEB-07:10 677.66 01-FEB-06:10 0.00 0.00 0.00 0.00 11.29 19-FEB-14:00 85.74 04-FEB-04:50
March 671.83 01-MAR-07:10 727.74 01-MAR-07:10 677.66 01-MAR-06:10 0.00 0.00 0.00 0.00 22.79 05-MAR-14:10 87.35 16-MAR-01:53
April 671.83 03-APR-06:10 727.74 03-APR-06:10 677.66 03-APR-05:10 0.00 0.00 0.00 0.00 28.74 16-APR-12:51 27.48 18-APR-23:52
May 671.83 01-MAY-06:10 727.74 01-MAY-06:10 677.66 01-MAY-05:10 0.00 0.00 0.00 0.00 52.08 29-MAY-16:15 11.21 07-MAY-01:52
June 671.83 01-JUN-06:10 727.74 01-JUN-06:10 677.66 01-JUN-05:10 0.00 0.00 0.00 0.00 35.83 17-JUN-18:20 7.68 18-JUN-20:20
July 671.83 03-JUL-06:10 727.74 03-JUL-06:10 677.66 03-JUL-05:10 0.00 0.00 0.00 0.00 45.72 30-JUL-16:00 7.87 02-JUL-15:50
August 671.83 01-AUG-06:10 727.74 01-AUG-06:10 677.66 01-AUG-05:10 0.00 0.00 0.00 0.00 42.80 13-AUG-12:50 15.58 14-AUG-03:00
September 671.83 01-SEP-06:10 727.74 01-SEP-06:10 677.66 01-SEP-05:10 0.00 0.00 0.00 0.00 39.31 17-SEP-13:50 5.62 02-SEP-22:00
October 671.83 02-OCT-06:10 727.74 02-OCT-06:10 677.66 02-OCT-05:10 0.00 0.00 0.00 0.00 32.29 29-OCT-14:00 12.92 16-OCT-02:53
November 671.83 01-NOV-06:10 727.74 01-NOV-06:10 677.66 01-NOV-05:10 0.00 0.00 0.00 0.00 20.69 23-NOV-12:00 79.76 11-NOV-09:00
December 671.83 01-DEC-07:10 727.74 01-DEC-07:10 677.66 01-DEC-06:10 0.00 0.00 0.00 0.00 27.03 10-DEC-14:50 80.64 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 671.83   727.74   677.66   0.00 0.00 0.00 0.00 11.29   5.62  
Maximum of Months 671.83   727.74   677.66   0.00 0.00 0.00 0.00 52.08   87.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 129.60 02-JAN-07:10 206.77 02-JAN-07:10 95.18 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 129.60 01-FEB-07:10 206.77 01-FEB-07:10 95.18 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 129.60 01-MAR-07:10 206.77 01-MAR-07:10 95.18 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 129.60 03-APR-06:10 206.77 03-APR-06:10 95.18 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 129.60 01-MAY-06:10 206.77 01-MAY-06:10 95.18 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 129.60 01-JUN-06:10 206.77 01-JUN-06:10 95.18 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 129.60 03-JUL-06:10 206.77 03-JUL-06:10 95.18 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 129.60 01-AUG-06:10 206.77 01-AUG-06:10 95.18 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 129.60 01-SEP-06:10 206.77 01-SEP-06:10 95.18 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 129.60 02-OCT-06:10 206.77 02-OCT-06:10 95.18 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 129.60 01-NOV-06:10 206.77 01-NOV-06:10 95.18 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 129.60 01-DEC-07:10 206.77 01-DEC-07:10 95.18 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 129.60   206.77   95.18   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 129.60   206.77   95.18   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 29.16 02-JAN-07:10 43.74 02-JAN-07:10 21.42 02-JAN-06:10 0.00 0.00 0.00 0.00 13.80 15-JAN-14:00 13.36 24-JAN-03:00
February 29.16 01-FEB-07:10 43.74 01-FEB-07:10 21.42 01-FEB-06:10 0.00 0.00 0.00 0.00 11.14 20-FEB-14:50 21.43 04-FEB-04:50
March 29.16 01-MAR-07:10 43.74 01-MAR-07:10 21.42 01-MAR-06:10 0.00 0.00 0.00 0.00 13.51 05-MAR-14:10 22.62 16-MAR-01:53
April 29.16 03-APR-06:10 43.74 03-APR-06:10 21.42 03-APR-05:10 0.00 0.00 0.00 0.00 15.93 23-APR-09:50 6.75 18-APR-23:52
May 29.16 01-MAY-06:10 43.74 01-MAY-06:10 21.42 01-MAY-05:10 0.00 0.00 0.00 0.00 22.69 29-MAY-16:20 2.44 07-MAY-05:10
June 29.16 01-JUN-06:10 43.74 01-JUN-06:10 21.42 01-JUN-05:10 0.00 0.00 0.00 0.00 20.25 18-JUN-12:40 0.58 18-JUN-02:00
July 29.16 03-JUL-06:10 43.74 03-JUL-06:10 21.42 03-JUL-05:10 0.00 0.00 0.00 0.00 21.38 30-JUL-16:00 0.68 04-JUL-03:30
August 29.16 01-AUG-06:10 43.74 01-AUG-06:10 21.42 01-AUG-05:10 0.00 0.00 0.00 0.00 20.10 13-AUG-12:30 2.39 14-AUG-03:00
September 29.16 01-SEP-06:10 43.74 01-SEP-06:10 21.42 01-SEP-05:10 0.00 0.00 0.00 0.00 19.70 17-SEP-13:50 0.80 02-SEP-22:00
October 29.16 02-OCT-06:10 43.74 02-OCT-06:10 21.42 02-OCT-05:10 0.00 0.00 0.00 0.00 17.22 29-OCT-14:00 2.60 16-OCT-03:00
November 29.16 01-NOV-06:10 43.74 01-NOV-06:10 21.42 01-NOV-05:10 0.00 0.00 0.00 0.00 13.21 19-NOV-14:00 19.08 11-NOV-09:00
December 29.16 01-DEC-07:10 43.74 01-DEC-07:10 21.42 01-DEC-06:10 0.00 0.00 0.00 0.00 16.58 10-DEC-14:50 21.07 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 29.16   43.74   21.42   0.00 0.00 0.00 0.00 11.14   0.58  
Maximum of Months 29.16   43.74   21.42   0.00 0.00 0.00 0.00 22.69   22.62  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1069.30 02-JAN-07:10 475.20 02-JAN-07:10 1961.01 02-JAN-06:10 0.00 0.00 0.00 0.00 14.21 15-JAN-14:20 56.41 24-JAN-03:00
February 1069.30 01-FEB-07:10 475.20 01-FEB-07:10 1961.01 01-FEB-06:10 0.00 0.00 0.00 0.00 15.13 20-FEB-15:10 92.49 04-FEB-04:50
March 1069.30 01-MAR-07:10 475.20 01-MAR-07:10 1961.01 01-MAR-06:10 0.00 0.00 0.00 0.00 20.82 05-MAR-13:50 92.79 16-MAR-01:53
April 1069.30 03-APR-06:10 475.20 03-APR-06:10 1961.01 03-APR-05:10 0.00 0.00 0.00 0.00 29.74 16-APR-18:10 28.69 18-APR-23:52
May 1069.30 01-MAY-06:10 475.20 01-MAY-06:10 1961.01 01-MAY-05:10 0.00 0.00 0.00 0.00 55.12 29-MAY-16:40 14.30 25-MAY-05:00
June 1069.30 01-JUN-06:10 475.20 01-JUN-06:10 1961.01 01-JUN-05:10 0.00 0.00 0.00 0.00 36.37 18-JUN-15:00 7.56 18-JUN-20:20
July 1069.30 03-JUL-06:10 475.20 03-JUL-06:10 1961.01 03-JUL-05:10 0.00 0.00 0.00 0.00 50.53 30-JUL-16:00 7.53 02-JUL-15:50
August 1069.30 01-AUG-06:10 475.20 01-AUG-06:10 1961.01 01-AUG-05:10 0.00 0.00 0.00 0.00 41.96 13-AUG-12:50 14.42 14-AUG-03:05
September 1069.30 01-SEP-06:10 475.20 01-SEP-06:10 1961.01 01-SEP-05:10 0.00 0.00 0.00 0.00 43.07 17-SEP-16:50 5.09 02-SEP-22:00
October 1069.30 02-OCT-06:10 475.20 02-OCT-06:10 1961.01 02-OCT-05:10 0.00 0.00 0.00 0.00 33.16 29-OCT-14:00 12.93 16-OCT-05:00
November 1069.30 01-NOV-06:10 475.20 01-NOV-06:10 1961.01 01-NOV-05:10 0.00 0.00 0.00 0.00 19.34 23-NOV-12:00 88.33 11-NOV-09:00
December 1069.30 01-DEC-07:10 475.20 01-DEC-07:10 1961.01 01-DEC-06:10 0.00 0.00 0.00 0.00 29.91 10-DEC-15:00 87.61 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1069.30   475.20   1961.01   0.00 0.00 0.00 0.00 14.21   5.09  
Maximum of Months 1069.30   475.20   1961.01   0.00 0.00 0.00 0.00 55.12   92.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 267.84 02-JAN-07:10 427.33 02-JAN-07:10 196.71 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 267.84 01-FEB-07:10 427.33 01-FEB-07:10 196.71 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 267.84 01-MAR-07:10 427.33 01-MAR-07:10 196.71 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 267.84 03-APR-06:10 427.33 03-APR-06:10 196.71 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 267.84 01-MAY-06:10 427.33 01-MAY-06:10 196.71 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 267.84 01-JUN-06:10 427.33 01-JUN-06:10 196.71 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 267.84 03-JUL-06:10 427.33 03-JUL-06:10 196.71 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 267.84 01-AUG-06:10 427.33 01-AUG-06:10 196.71 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 267.84 01-SEP-06:10 427.33 01-SEP-06:10 196.71 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 267.84 02-OCT-06:10 427.33 02-OCT-06:10 196.71 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 267.84 01-NOV-06:10 427.33 01-NOV-06:10 196.71 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 267.84 01-DEC-07:10 427.33 01-DEC-07:10 196.71 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 267.84   427.33   196.71   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 267.84   427.33   196.71   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 583.26 02-JAN-07:10 259.20 02-JAN-07:10 1069.64 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 583.26 01-FEB-07:10 259.20 01-FEB-07:10 1069.64 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 583.26 01-MAR-07:10 259.20 01-MAR-07:10 1069.64 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 583.26 03-APR-06:10 259.20 03-APR-06:10 1069.64 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 583.26 01-MAY-06:10 259.20 01-MAY-06:10 1069.64 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 583.26 01-JUN-06:10 259.20 01-JUN-06:10 1069.64 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 583.26 03-JUL-06:10 259.20 03-JUL-06:10 1069.64 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 583.26 01-AUG-06:10 259.20 01-AUG-06:10 1069.64 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 583.26 01-SEP-06:10 259.20 01-SEP-06:10 1069.64 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 583.26 02-OCT-06:10 259.20 02-OCT-06:10 1069.64 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 583.26 01-NOV-06:10 259.20 01-NOV-06:10 1069.64 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 583.26 01-DEC-07:10 259.20 01-DEC-07:10 1069.64 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 583.26   259.20   1069.64   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 583.26   259.20   1069.64   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 MED GAS

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 12.10 02-JAN-07:10 45.36 02-JAN-07:10 5.57 02-JAN-06:10 0.00 0.00 0.00 0.00 18.45 15-JAN-14:00 22.58 24-JAN-03:00
February 12.10 01-FEB-07:10 45.36 01-FEB-07:10 5.57 01-FEB-06:10 0.00 0.00 0.00 0.00 13.91 20-FEB-15:30 45.22 04-FEB-04:53
March 12.10 01-MAR-07:10 45.36 01-MAR-07:10 5.57 01-MAR-06:10 0.00 0.00 0.00 0.00 15.97 13-MAR-18:01 39.06 16-MAR-01:53
April 12.10 03-APR-06:10 45.36 03-APR-06:10 5.57 03-APR-05:10 0.00 0.00 0.00 0.00 17.83 16-APR-13:04 11.66 18-APR-23:52
May 12.10 01-MAY-06:10 45.36 01-MAY-06:10 5.57 01-MAY-05:10 0.00 0.00 0.00 0.00 35.03 29-MAY-16:13 4.67 07-MAY-13:30
June 12.10 01-JUN-06:10 45.36 01-JUN-06:10 5.57 01-JUN-05:10 0.00 0.00 0.00 0.00 24.59 16-JUN-23:40 2.94 18-JUN-19:10
July 12.10 03-JUL-06:10 45.36 03-JUL-06:10 5.57 03-JUL-05:10 0.00 0.00 0.00 0.00 28.48 30-JUL-16:00 6.89 02-JUL-15:50
August 12.10 01-AUG-06:10 45.36 01-AUG-06:10 5.57 01-AUG-05:10 0.00 0.00 0.00 0.00 25.33 13-AUG-12:25 7.51 14-AUG-02:53
September 12.10 01-SEP-06:10 45.36 01-SEP-06:10 5.57 01-SEP-05:10 0.00 0.00 0.00 0.00 26.30 17-SEP-13:43 4.40 03-SEP-14:00
October 12.10 02-OCT-06:10 45.36 02-OCT-06:10 5.57 02-OCT-05:10 0.00 0.00 0.00 0.00 21.73 29-OCT-13:53 4.66 16-OCT-02:53
November 12.10 01-NOV-06:10 45.36 01-NOV-06:10 5.57 01-NOV-05:10 0.00 0.00 0.00 0.00 16.19 22-NOV-21:20 38.32 11-NOV-09:00
December 12.10 01-DEC-07:10 45.36 01-DEC-07:10 5.57 01-DEC-06:10 0.00 0.00 0.00 0.00 21.48 10-DEC-14:50 38.48 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 12.10   45.36   5.57   0.00 0.00 0.00 0.00 13.91   2.94  
Maximum of Months 12.10   45.36   5.57   0.00 0.00 0.00 0.00 35.03   45.22  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 362.92 02-JAN-07:10 226.80 02-JAN-07:10 1663.99 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 362.92 01-FEB-07:10 226.80 01-FEB-07:10 1663.99 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 362.92 01-MAR-07:10 226.80 01-MAR-07:10 1663.99 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 362.92 03-APR-06:10 226.80 03-APR-06:10 1663.99 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 362.92 01-MAY-06:10 226.80 01-MAY-06:10 1663.99 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 362.92 01-JUN-06:10 226.80 01-JUN-06:10 1663.99 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 362.92 03-JUL-06:10 226.80 03-JUL-06:10 1663.99 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 362.92 01-AUG-06:10 226.80 01-AUG-06:10 1663.99 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 362.92 01-SEP-06:10 226.80 01-SEP-06:10 1663.99 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 362.92 02-OCT-06:10 226.80 02-OCT-06:10 1663.99 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 362.92 01-NOV-06:10 226.80 01-NOV-06:10 1663.99 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 362.92 01-DEC-07:10 226.80 01-DEC-07:10 1663.99 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 362.92   226.80   1663.99   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 362.92   226.80   1663.99   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 79.38 02-JAN-07:10 126.65 02-JAN-07:10 58.30 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 79.38 01-FEB-07:10 126.65 01-FEB-07:10 58.30 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 79.38 01-MAR-07:10 126.65 01-MAR-07:10 58.30 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 79.38 03-APR-06:10 126.65 03-APR-06:10 58.30 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 79.38 01-MAY-06:10 126.65 01-MAY-06:10 58.30 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 79.38 01-JUN-06:10 126.65 01-JUN-06:10 58.30 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 79.38 03-JUL-06:10 126.65 03-JUL-06:10 58.30 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 79.38 01-AUG-06:10 126.65 01-AUG-06:10 58.30 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 79.38 01-SEP-06:10 126.65 01-SEP-06:10 58.30 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 79.38 02-OCT-06:10 126.65 02-OCT-06:10 58.30 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 79.38 01-NOV-06:10 126.65 01-NOV-06:10 58.30 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 79.38 01-DEC-07:10 126.65 01-DEC-07:10 58.30 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 79.38   126.65   58.30   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 79.38   126.65   58.30   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 950.49 02-JAN-07:10 594.00 02-JAN-07:10 4358.06 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 950.49 01-FEB-07:10 594.00 01-FEB-07:10 4358.06 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 950.49 01-MAR-07:10 594.00 01-MAR-07:10 4358.06 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 950.49 03-APR-06:10 594.00 03-APR-06:10 4358.06 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 950.49 01-MAY-06:10 594.00 01-MAY-06:10 4358.06 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 950.49 01-JUN-06:10 594.00 01-JUN-06:10 4358.06 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 950.49 03-JUL-06:10 594.00 03-JUL-06:10 4358.06 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 950.49 01-AUG-06:10 594.00 01-AUG-06:10 4358.06 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 950.49 01-SEP-06:10 594.00 01-SEP-06:10 4358.06 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 950.49 02-OCT-06:10 594.00 02-OCT-06:10 4358.06 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 950.49 01-NOV-06:10 594.00 01-NOV-06:10 4358.06 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 950.49 01-DEC-07:10 594.00 01-DEC-07:10 4358.06 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 950.49   594.00   4358.06   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 950.49   594.00   4358.06   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 29.16 02-JAN-07:10 43.74 02-JAN-07:10 21.42 02-JAN-06:10 0.00 0.00 0.00 0.00 13.80 15-JAN-14:00 12.38 24-JAN-03:00
February 29.16 01-FEB-07:10 43.74 01-FEB-07:10 21.42 01-FEB-06:10 0.00 0.00 0.00 0.00 11.16 20-FEB-14:50 21.33 04-FEB-04:50
March 29.16 01-MAR-07:10 43.74 01-MAR-07:10 21.42 01-MAR-06:10 0.00 0.00 0.00 0.00 13.70 05-MAR-16:10 21.35 16-MAR-01:53
April 29.16 03-APR-06:10 43.74 03-APR-06:10 21.42 03-APR-05:10 0.00 0.00 0.00 0.00 15.94 23-APR-09:50 5.83 19-APR-03:00
May 29.16 01-MAY-06:10 43.74 01-MAY-06:10 21.42 01-MAY-05:10 0.00 0.00 0.00 0.00 24.67 29-MAY-17:00 1.65 07-MAY-06:00
June 29.16 01-JUN-06:10 43.74 01-JUN-06:10 21.42 01-JUN-05:10 0.00 0.00 0.00 0.00 20.27 18-JUN-12:40 0.00 01-JUN-00:01
July 29.16 03-JUL-06:10 43.74 03-JUL-06:10 21.42 03-JUL-05:10 0.00 0.00 0.00 0.00 23.79 30-JUL-16:00 0.00 01-JUL-00:01
August 29.16 01-AUG-06:10 43.74 01-AUG-06:10 21.42 01-AUG-05:10 0.00 0.00 0.00 0.00 20.43 13-AUG-13:10 0.02 14-AUG-03:05
September 29.16 01-SEP-06:10 43.74 01-SEP-06:10 21.42 01-SEP-05:10 0.00 0.00 0.00 0.00 20.57 17-SEP-13:50 0.00 01-SEP-00:03
October 29.16 02-OCT-06:10 43.74 02-OCT-06:10 21.42 02-OCT-05:10 0.00 0.00 0.00 0.00 18.05 29-OCT-14:00 1.16 16-OCT-03:00
November 29.16 01-NOV-06:10 43.74 01-NOV-06:10 21.42 01-NOV-05:10 0.00 0.00 0.00 0.00 13.22 19-NOV-14:00 17.60 11-NOV-09:00
December 29.16 01-DEC-07:10 43.74 01-DEC-07:10 21.42 01-DEC-06:10 0.00 0.00 0.00 0.00 17.33 10-DEC-14:50 20.56 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 29.16   43.74   21.42   0.00 0.00 0.00 0.00 11.16   0.00  
Maximum of Months 29.16   43.74   21.42   0.00 0.00 0.00 0.00 24.67   21.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 294.84 02-JAN-07:10 163.80 02-JAN-07:10 360.56 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 294.84 01-FEB-07:10 163.80 01-FEB-07:10 360.56 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 294.84 01-MAR-07:10 163.80 01-MAR-07:10 360.56 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 294.84 03-APR-06:10 163.80 03-APR-06:10 360.56 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 294.84 01-MAY-06:10 163.80 01-MAY-06:10 360.56 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 294.84 01-JUN-06:10 163.80 01-JUN-06:10 360.56 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 294.84 03-JUL-06:10 163.80 03-JUL-06:10 360.56 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 294.84 01-AUG-06:10 163.80 01-AUG-06:10 360.56 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 294.84 01-SEP-06:10 163.80 01-SEP-06:10 360.56 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 294.84 02-OCT-06:10 163.80 02-OCT-06:10 360.56 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 294.84 01-NOV-06:10 163.80 01-NOV-06:10 360.56 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 294.84 01-DEC-07:10 163.80 01-DEC-07:10 360.56 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 294.84   163.80   360.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 294.84   163.80   360.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 267.84 02-JAN-07:10 427.33 02-JAN-07:10 196.71 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 267.84 01-FEB-07:10 427.33 01-FEB-07:10 196.71 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 267.84 01-MAR-07:10 427.33 01-MAR-07:10 196.71 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 267.84 03-APR-06:10 427.33 03-APR-06:10 196.71 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 267.84 01-MAY-06:10 427.33 01-MAY-06:10 196.71 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 267.84 01-JUN-06:10 427.33 01-JUN-06:10 196.71 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 267.84 03-JUL-06:10 427.33 03-JUL-06:10 196.71 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 267.84 01-AUG-06:10 427.33 01-AUG-06:10 196.71 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 267.84 01-SEP-06:10 427.33 01-SEP-06:10 196.71 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 267.84 02-OCT-06:10 427.33 02-OCT-06:10 196.71 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 267.84 01-NOV-06:10 427.33 01-NOV-06:10 196.71 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 267.84 01-DEC-07:10 427.33 01-DEC-07:10 196.71 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 267.84   427.33   196.71   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 267.84   427.33   196.71   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11.66 02-JAN-07:10 43.74 02-JAN-07:10 5.37 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11.66 01-FEB-07:10 43.74 01-FEB-07:10 5.37 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11.66 01-MAR-07:10 43.74 01-MAR-07:10 5.37 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11.66 03-APR-06:10 43.74 03-APR-06:10 5.37 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11.66 01-MAY-06:10 43.74 01-MAY-06:10 5.37 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11.66 01-JUN-06:10 43.74 01-JUN-06:10 5.37 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11.66 03-JUL-06:10 43.74 03-JUL-06:10 5.37 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11.66 01-AUG-06:10 43.74 01-AUG-06:10 5.37 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11.66 01-SEP-06:10 43.74 01-SEP-06:10 5.37 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11.66 02-OCT-06:10 43.74 02-OCT-06:10 5.37 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11.66 01-NOV-06:10 43.74 01-NOV-06:10 5.37 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11.66 01-DEC-07:10 43.74 01-DEC-07:10 5.37 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11.66   43.74   5.37   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11.66   43.74   5.37   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 422.82 02-JAN-07:10 234.90 02-JAN-07:10 517.07 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 422.82 01-FEB-07:10 234.90 01-FEB-07:10 517.07 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 422.82 01-MAR-07:10 234.90 01-MAR-07:10 517.07 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 422.82 03-APR-06:10 234.90 03-APR-06:10 517.07 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 422.82 01-MAY-06:10 234.90 01-MAY-06:10 517.07 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 422.82 01-JUN-06:10 234.90 01-JUN-06:10 517.07 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 422.82 03-JUL-06:10 234.90 03-JUL-06:10 517.07 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 422.82 01-AUG-06:10 234.90 01-AUG-06:10 517.07 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 422.82 01-SEP-06:10 234.90 01-SEP-06:10 517.07 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 422.82 02-OCT-06:10 234.90 02-OCT-06:10 517.07 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 422.82 01-NOV-06:10 234.90 01-NOV-06:10 517.07 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 422.82 01-DEC-07:10 234.90 01-DEC-07:10 517.07 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 422.82   234.90   517.07   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 422.82   234.90   517.07   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 29.16 02-JAN-07:10 43.74 02-JAN-07:10 21.42 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 29.16 01-FEB-07:10 43.74 01-FEB-07:10 21.42 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 29.16 01-MAR-07:10 43.74 01-MAR-07:10 21.42 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 29.16 03-APR-06:10 43.74 03-APR-06:10 21.42 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 29.16 01-MAY-06:10 43.74 01-MAY-06:10 21.42 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 29.16 01-JUN-06:10 43.74 01-JUN-06:10 21.42 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 29.16 03-JUL-06:10 43.74 03-JUL-06:10 21.42 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 29.16 01-AUG-06:10 43.74 01-AUG-06:10 21.42 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 29.16 01-SEP-06:10 43.74 01-SEP-06:10 21.42 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 29.16 02-OCT-06:10 43.74 02-OCT-06:10 21.42 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 29.16 01-NOV-06:10 43.74 01-NOV-06:10 21.42 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 29.16 01-DEC-07:10 43.74 01-DEC-07:10 21.42 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 29.16   43.74   21.42   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 29.16   43.74   21.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 260.85 02-JAN-07:10 478.17 02-JAN-07:10 526.22 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 260.85 01-FEB-07:10 478.17 01-FEB-07:10 526.22 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 260.85 01-MAR-07:10 478.17 01-MAR-07:10 526.22 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 260.85 03-APR-06:10 478.17 03-APR-06:10 526.22 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 260.85 01-MAY-06:10 478.17 01-MAY-06:10 526.22 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 260.85 01-JUN-06:10 478.17 01-JUN-06:10 526.22 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 260.85 03-JUL-06:10 478.17 03-JUL-06:10 526.22 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 260.85 01-AUG-06:10 478.17 01-AUG-06:10 526.22 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 260.85 01-SEP-06:10 478.17 01-SEP-06:10 526.22 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 260.85 02-OCT-06:10 478.17 02-OCT-06:10 526.22 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 260.85 01-NOV-06:10 478.17 01-NOV-06:10 526.22 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 260.85 01-DEC-07:10 478.17 01-DEC-07:10 526.22 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 260.85   478.17   526.22   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 260.85   478.17   526.22   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 993.70 02-JAN-07:10 910.80 02-JAN-07:10 1822.63 02-JAN-06:10 1608.99 02-JAN-06:10 0.00 0.00 0.00 94.83 15-JAN-13:51 80.08 24-JAN-05:53
February 993.70 01-FEB-07:10 910.80 01-FEB-07:10 1822.63 01-FEB-06:10 1608.99 01-FEB-06:10 0.00 0.00 0.00 79.02 20-FEB-15:00 170.76 04-FEB-05:00
March 993.70 01-MAR-07:10 910.80 01-MAR-07:10 1822.63 01-MAR-06:10 1608.99 01-MAR-06:10 0.00 0.00 0.00 96.82 05-MAR-16:00 156.31 16-MAR-01:53
April 993.70 03-APR-06:10 910.80 03-APR-06:10 1822.63 03-APR-05:10 1608.99 03-APR-05:10 0.00 0.00 0.00 113.72 23-APR-10:00 39.53 19-APR-03:00
May 993.70 01-MAY-06:10 910.80 01-MAY-06:10 1822.63 01-MAY-05:10 1608.99 01-MAY-05:10 0.00 0.00 0.00 171.51 29-MAY-16:00 7.39 07-MAY-05:00
June 993.70 01-JUN-06:10 910.80 01-JUN-06:10 1822.63 01-JUN-05:10 1608.99 01-JUN-05:10 0.00 0.00 0.00 152.60 18-JUN-12:55 0.00 01-JUN-00:01
July 993.70 03-JUL-06:10 910.80 03-JUL-06:10 1822.63 03-JUL-05:10 1608.99 03-JUL-05:10 0.00 0.00 0.00 186.12 30-JUL-16:00 0.00 01-JUL-00:01
August 993.70 01-AUG-06:10 910.80 01-AUG-06:10 1822.63 01-AUG-05:10 1608.99 01-AUG-05:10 0.00 0.00 0.00 153.06 13-AUG-13:00 0.00 01-AUG-00:01
September 993.70 01-SEP-06:10 910.80 01-SEP-06:10 1822.63 01-SEP-05:10 1608.99 01-SEP-05:10 0.00 0.00 0.00 147.65 17-SEP-14:00 0.00 01-SEP-00:03
October 993.70 02-OCT-06:10 910.80 02-OCT-06:10 1822.63 02-OCT-05:10 1608.99 02-OCT-05:10 0.00 0.00 0.00 126.85 29-OCT-13:51 4.25 28-OCT-03:47
November 993.70 01-NOV-06:10 910.80 01-NOV-06:10 1822.63 01-NOV-05:10 1608.99 01-NOV-05:10 0.00 0.00 0.00 96.92 23-NOV-11:53 95.61 13-NOV-05:53
December 993.70 01-DEC-07:10 910.80 01-DEC-07:10 1822.63 01-DEC-06:10 1608.99 01-DEC-06:10 0.00 0.00 0.00 122.01 10-DEC-14:53 151.27 15-DEC-06:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 993.70   910.80   1822.63   1608.99   0.00 0.00 0.00 79.02   0.00  
Maximum of Months 993.70   910.80   1822.63   1608.99   0.00 0.00 0.00 186.12   170.76  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1036.90 02-JAN-07:10 950.40 02-JAN-07:10 1901.88 02-JAN-06:10 1678.94 02-JAN-06:10 0.00 0.00 0.00 52.93 15-JAN-13:51 44.69 24-JAN-05:54
February 1036.90 01-FEB-07:10 950.40 01-FEB-07:10 1901.88 01-FEB-06:10 1678.94 01-FEB-06:10 0.00 0.00 0.00 44.11 20-FEB-14:56 95.31 04-FEB-04:53
March 1036.90 01-MAR-07:10 950.40 01-MAR-07:10 1901.88 01-MAR-06:10 1678.94 01-MAR-06:10 0.00 0.00 0.00 54.04 05-MAR-16:00 87.24 16-MAR-01:53
April 1036.90 03-APR-06:10 950.40 03-APR-06:10 1901.88 03-APR-05:10 1678.94 03-APR-05:10 0.00 0.00 0.00 63.47 23-APR-10:00 22.07 19-APR-03:00
May 1036.90 01-MAY-06:10 950.40 01-MAY-06:10 1901.88 01-MAY-05:10 1678.94 01-MAY-05:10 0.00 0.00 0.00 95.72 29-MAY-16:00 4.12 07-MAY-05:00
June 1036.90 01-JUN-06:10 950.40 01-JUN-06:10 1901.88 01-JUN-05:10 1678.94 01-JUN-05:10 0.00 0.00 0.00 85.17 18-JUN-12:55 0.00 01-JUN-00:01
July 1036.90 03-JUL-06:10 950.40 03-JUL-06:10 1901.88 03-JUL-05:10 1678.94 03-JUL-05:10 0.00 0.00 0.00 103.88 30-JUL-16:00 0.00 01-JUL-00:01
August 1036.90 01-AUG-06:10 950.40 01-AUG-06:10 1901.88 01-AUG-05:10 1678.94 01-AUG-05:10 0.00 0.00 0.00 85.43 13-AUG-13:00 0.00 01-AUG-00:01
September 1036.90 01-SEP-06:10 950.40 01-SEP-06:10 1901.88 01-SEP-05:10 1678.94 01-SEP-05:10 0.00 0.00 0.00 82.41 17-SEP-14:00 0.00 01-SEP-00:03
October 1036.90 02-OCT-06:10 950.40 02-OCT-06:10 1901.88 02-OCT-05:10 1678.94 02-OCT-05:10 0.00 0.00 0.00 70.80 29-OCT-13:51 2.37 28-OCT-03:47
November 1036.90 01-NOV-06:10 950.40 01-NOV-06:10 1901.88 01-NOV-05:10 1678.94 01-NOV-05:10 0.00 0.00 0.00 54.10 23-NOV-11:53 53.36 13-NOV-05:53
December 1036.90 01-DEC-07:10 950.40 01-DEC-07:10 1901.88 01-DEC-06:10 1678.94 01-DEC-06:10 0.00 0.00 0.00 68.10 10-DEC-14:53 84.43 15-DEC-06:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 1036.90   950.40   1901.88   1678.94   0.00 0.00 0.00 44.11   0.00  
Maximum of Months 1036.90   950.40   1901.88   1678.94   0.00 0.00 0.00 103.88   95.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1028.26 02-JAN-07:10 942.48 02-JAN-07:10 1886.03 02-JAN-06:10 1664.95 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00
February 1028.26 01-FEB-07:10 942.48 01-FEB-07:10 1886.03 01-FEB-06:10 1664.95 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00
March 1028.26 01-MAR-07:10 942.48 01-MAR-07:10 1886.03 01-MAR-06:10 1664.95 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 1028.26 03-APR-06:10 942.48 03-APR-06:10 1886.03 03-APR-05:10 1664.95 03-APR-05:10 0.00 0.00 0.00 0.00 0.00
May 1028.26 01-MAY-06:10 942.48 01-MAY-06:10 1886.03 01-MAY-05:10 1664.95 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00
June 1028.26 01-JUN-06:10 942.48 01-JUN-06:10 1886.03 01-JUN-05:10 1664.95 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00
July 1028.26 03-JUL-06:10 942.48 03-JUL-06:10 1886.03 03-JUL-05:10 1664.95 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00
August 1028.26 01-AUG-06:10 942.48 01-AUG-06:10 1886.03 01-AUG-05:10 1664.95 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00
September 1028.26 01-SEP-06:10 942.48 01-SEP-06:10 1886.03 01-SEP-05:10 1664.95 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00
October 1028.26 02-OCT-06:10 942.48 02-OCT-06:10 1886.03 02-OCT-05:10 1664.95 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00
November 1028.26 01-NOV-06:10 942.48 01-NOV-06:10 1886.03 01-NOV-05:10 1664.95 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00
December 1028.26 01-DEC-07:10 942.48 01-DEC-07:10 1886.03 01-DEC-06:10 1664.95 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00
                           
Annual Sum or Average                 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1028.26   942.48   1886.03   1664.95   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1028.26   942.48   1886.03   1664.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 PACU

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 233.30 02-JAN-07:10 77.76 02-JAN-07:10 320.89 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 233.30 01-FEB-07:10 77.76 01-FEB-07:10 320.89 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 233.30 01-MAR-07:10 77.76 01-MAR-07:10 320.89 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 233.30 03-APR-06:10 77.76 03-APR-06:10 320.89 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 233.30 01-MAY-06:10 77.76 01-MAY-06:10 320.89 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 233.30 01-JUN-06:10 77.76 01-JUN-06:10 320.89 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 233.30 03-JUL-06:10 77.76 03-JUL-06:10 320.89 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 233.30 01-AUG-06:10 77.76 01-AUG-06:10 320.89 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 233.30 01-SEP-06:10 77.76 01-SEP-06:10 320.89 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 233.30 02-OCT-06:10 77.76 02-OCT-06:10 320.89 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 233.30 01-NOV-06:10 77.76 01-NOV-06:10 320.89 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 233.30 01-DEC-07:10 77.76 01-DEC-07:10 320.89 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 233.30   77.76   320.89   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 233.30   77.76   320.89   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 285.12 02-JAN-07:10 454.90 02-JAN-07:10 209.40 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 285.12 01-FEB-07:10 454.90 01-FEB-07:10 209.40 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 285.12 01-MAR-07:10 454.90 01-MAR-07:10 209.40 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 285.12 03-APR-06:10 454.90 03-APR-06:10 209.40 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 285.12 01-MAY-06:10 454.90 01-MAY-06:10 209.40 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 285.12 01-JUN-06:10 454.90 01-JUN-06:10 209.40 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 285.12 03-JUL-06:10 454.90 03-JUL-06:10 209.40 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 285.12 01-AUG-06:10 454.90 01-AUG-06:10 209.40 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 285.12 01-SEP-06:10 454.90 01-SEP-06:10 209.40 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 285.12 02-OCT-06:10 454.90 02-OCT-06:10 209.40 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 285.12 01-NOV-06:10 454.90 01-NOV-06:10 209.40 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 285.12 01-DEC-07:10 454.90 01-DEC-07:10 209.40 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 285.12   454.90   209.40   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 285.12   454.90   209.40   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 204.14 02-JAN-07:10 119.07 02-JAN-07:10 374.43 02-JAN-06:10 0.00 0.00 0.00 0.00 9.20 15-JAN-14:00 9.40 24-JAN-03:00
February 204.14 01-FEB-07:10 119.07 01-FEB-07:10 374.43 01-FEB-06:10 0.00 0.00 0.00 0.00 7.44 20-FEB-14:50 15.27 04-FEB-04:50
March 204.14 01-MAR-07:10 119.07 01-MAR-07:10 374.43 01-MAR-06:10 0.00 0.00 0.00 0.00 9.14 05-MAR-16:10 16.09 16-MAR-01:53
April 204.14 03-APR-06:10 119.07 03-APR-06:10 374.43 03-APR-05:10 0.00 0.00 0.00 0.00 10.63 23-APR-09:50 4.47 19-APR-03:00
May 204.14 01-MAY-06:10 119.07 01-MAY-06:10 374.43 01-MAY-05:10 0.00 0.00 0.00 0.00 16.58 29-MAY-17:00 1.35 07-MAY-06:00
June 204.14 01-JUN-06:10 119.07 01-JUN-06:10 374.43 01-JUN-05:10 0.00 0.00 0.00 0.00 13.81 18-JUN-13:00 0.00 01-JUN-00:01
July 204.14 03-JUL-06:10 119.07 03-JUL-06:10 374.43 03-JUL-05:10 0.00 0.00 0.00 0.00 17.28 30-JUL-16:00 0.01 04-JUL-04:57
August 204.14 01-AUG-06:10 119.07 01-AUG-06:10 374.43 01-AUG-05:10 0.00 0.00 0.00 0.00 13.79 13-AUG-13:10 0.05 14-AUG-03:05
September 204.14 01-SEP-06:10 119.07 01-SEP-06:10 374.43 01-SEP-05:10 0.00 0.00 0.00 0.00 13.78 17-SEP-13:50 0.00 01-SEP-00:03
October 204.14 02-OCT-06:10 119.07 02-OCT-06:10 374.43 02-OCT-05:10 0.00 0.00 0.00 0.00 12.11 29-OCT-14:00 0.99 16-OCT-03:03
November 204.14 01-NOV-06:10 119.07 01-NOV-06:10 374.43 01-NOV-05:10 0.00 0.00 0.00 0.00 8.82 19-NOV-14:00 13.18 11-NOV-09:00
December 204.14 01-DEC-07:10 119.07 01-DEC-07:10 374.43 01-DEC-06:10 0.00 0.00 0.00 0.00 11.56 10-DEC-14:50 15.33 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 204.14   119.07   374.43   0.00 0.00 0.00 0.00 7.44   0.00  
Maximum of Months 204.14   119.07   374.43   0.00 0.00 0.00 0.00 17.28   16.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 365.08 02-JAN-07:10 212.94 02-JAN-07:10 669.62 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 365.08 01-FEB-07:10 212.94 01-FEB-07:10 669.62 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 365.08 01-MAR-07:10 212.94 01-MAR-07:10 669.62 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 365.08 03-APR-06:10 212.94 03-APR-06:10 669.62 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 365.08 01-MAY-06:10 212.94 01-MAY-06:10 669.62 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 365.08 01-JUN-06:10 212.94 01-JUN-06:10 669.62 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 365.08 03-JUL-06:10 212.94 03-JUL-06:10 669.62 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 365.08 01-AUG-06:10 212.94 01-AUG-06:10 669.62 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 365.08 01-SEP-06:10 212.94 01-SEP-06:10 669.62 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 365.08 02-OCT-06:10 212.94 02-OCT-06:10 669.62 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 365.08 01-NOV-06:10 212.94 01-NOV-06:10 669.62 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 365.08 01-DEC-07:10 212.94 01-DEC-07:10 669.62 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 365.08   212.94   669.62   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 365.08   212.94   669.62   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 29.16 02-JAN-07:10 43.74 02-JAN-07:10 21.42 02-JAN-06:10 0.00 0.00 0.00 0.00 13.80 15-JAN-14:00 12.57 24-JAN-03:00
February 29.16 01-FEB-07:10 43.74 01-FEB-07:10 21.42 01-FEB-06:10 0.00 0.00 0.00 0.00 11.15 20-FEB-14:50 20.53 04-FEB-04:50
March 29.16 01-MAR-07:10 43.74 01-MAR-07:10 21.42 01-MAR-06:10 0.00 0.00 0.00 0.00 13.70 05-MAR-16:10 21.16 16-MAR-01:53
April 29.16 03-APR-06:10 43.74 03-APR-06:10 21.42 03-APR-05:10 0.00 0.00 0.00 0.00 15.94 23-APR-09:50 5.87 19-APR-03:00
May 29.16 01-MAY-06:10 43.74 01-MAY-06:10 21.42 01-MAY-05:10 0.00 0.00 0.00 0.00 23.95 29-MAY-16:20 1.66 07-MAY-06:00
June 29.16 01-JUN-06:10 43.74 01-JUN-06:10 21.42 01-JUN-05:10 0.00 0.00 0.00 0.00 20.27 18-JUN-12:40 0.00 01-JUN-00:01
July 29.16 03-JUL-06:10 43.74 03-JUL-06:10 21.42 03-JUL-05:10 0.00 0.00 0.00 0.00 23.35 30-JUL-16:00 0.00 01-JUL-00:01
August 29.16 01-AUG-06:10 43.74 01-AUG-06:10 21.42 01-AUG-05:10 0.00 0.00 0.00 0.00 20.68 13-AUG-13:10 0.00 01-AUG-00:01
September 29.16 01-SEP-06:10 43.74 01-SEP-06:10 21.42 01-SEP-05:10 0.00 0.00 0.00 0.00 20.50 17-SEP-13:50 0.02 02-SEP-22:00
October 29.16 02-OCT-06:10 43.74 02-OCT-06:10 21.42 02-OCT-05:10 0.00 0.00 0.00 0.00 17.60 29-OCT-14:00 1.30 16-OCT-03:00
November 29.16 01-NOV-06:10 43.74 01-NOV-06:10 21.42 01-NOV-05:10 0.00 0.00 0.00 0.00 13.15 23-NOV-11:40 17.93 11-NOV-09:00
December 29.16 01-DEC-07:10 43.74 01-DEC-07:10 21.42 01-DEC-06:10 0.00 0.00 0.00 0.00 16.54 10-DEC-14:50 20.44 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 29.16   43.74   21.42   0.00 0.00 0.00 0.00 11.15   0.00  
Maximum of Months 29.16   43.74   21.42   0.00 0.00 0.00 0.00 23.95   21.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 615.66 02-JAN-07:10 384.75 02-JAN-07:10 846.80 02-JAN-06:10 0.00 0.00 0.00 0.00 43.70 15-JAN-14:00 42.41 24-JAN-03:00
February 615.66 01-FEB-07:10 384.75 01-FEB-07:10 846.80 01-FEB-06:10 0.00 0.00 0.00 0.00 36.21 20-FEB-14:56 68.40 04-FEB-04:50
March 615.66 01-MAR-07:10 384.75 01-MAR-07:10 846.80 01-MAR-06:10 0.00 0.00 0.00 0.00 43.80 05-MAR-15:44 70.00 16-MAR-01:53
April 615.66 03-APR-06:10 384.75 03-APR-06:10 846.80 03-APR-05:10 0.00 0.00 0.00 0.00 52.26 23-APR-09:56 20.32 19-APR-03:00
May 615.66 01-MAY-06:10 384.75 01-MAY-06:10 846.80 01-MAY-05:10 0.00 0.00 0.00 0.00 78.76 29-MAY-17:00 6.93 07-MAY-06:00
June 615.66 01-JUN-06:10 384.75 01-JUN-06:10 846.80 01-JUN-05:10 0.00 0.00 0.00 0.00 69.51 18-JUN-13:00 0.18 18-JUN-05:00
July 615.66 03-JUL-06:10 384.75 03-JUL-06:10 846.80 03-JUL-05:10 0.00 0.00 0.00 0.00 84.41 30-JUL-15:59 0.46 04-JUL-04:57
August 615.66 01-AUG-06:10 384.75 01-AUG-06:10 846.80 01-AUG-05:10 0.00 0.00 0.00 0.00 67.87 13-AUG-12:46 3.16 14-AUG-03:05
September 615.66 01-SEP-06:10 384.75 01-SEP-06:10 846.80 01-SEP-05:10 0.00 0.00 0.00 0.00 66.81 17-SEP-13:57 0.20 06-SEP-02:20
October 615.66 02-OCT-06:10 384.75 02-OCT-06:10 846.80 02-OCT-05:10 0.00 0.00 0.00 0.00 57.53 29-OCT-13:58 5.27 16-OCT-03:03
November 615.66 01-NOV-06:10 384.75 01-NOV-06:10 846.80 01-NOV-05:10 0.00 0.00 0.00 0.00 44.32 23-NOV-11:57 60.25 11-NOV-09:00
December 615.66 01-DEC-07:10 384.75 01-DEC-07:10 846.80 01-DEC-06:10 0.00 0.00 0.00 0.00 55.48 10-DEC-15:00 67.13 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 615.66   384.75   846.80   0.00 0.00 0.00 0.00 36.21   0.18  
Maximum of Months 615.66   384.75   846.80   0.00 0.00 0.00 0.00 84.41   70.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1649.32 02-JAN-07:10 595.53 02-JAN-07:10 554.54 02-JAN-06:10 0.00 0.00 0.00 0.00 9.22 29-JAN-12:40 32.32 24-JAN-03:00
February 1649.32 01-FEB-07:10 595.53 01-FEB-07:10 554.54 01-FEB-06:10 0.00 0.00 0.00 0.00 7.77 20-FEB-15:10 54.49 04-FEB-04:50
March 1649.32 01-MAR-07:10 595.53 01-MAR-07:10 554.54 01-MAR-06:10 0.00 0.00 0.00 0.00 14.64 05-MAR-14:10 54.13 16-MAR-01:53
April 1649.32 03-APR-06:10 595.53 03-APR-06:10 554.54 03-APR-05:10 0.00 0.00 0.00 0.00 18.36 16-APR-18:30 16.26 18-APR-23:52
May 1649.32 01-MAY-06:10 595.53 01-MAY-06:10 554.54 01-MAY-05:10 0.00 0.00 0.00 0.00 35.76 29-MAY-16:20 6.02 07-MAY-06:00
June 1649.32 01-JUN-06:10 595.53 01-JUN-06:10 554.54 01-JUN-05:10 0.00 0.00 0.00 0.00 24.58 18-JUN-15:00 2.46 18-JUN-02:00
July 1649.32 03-JUL-06:10 595.53 03-JUL-06:10 554.54 03-JUL-05:10 0.00 0.00 0.00 0.00 32.88 30-JUL-16:00 2.89 04-JUL-03:20
August 1649.32 01-AUG-06:10 595.53 01-AUG-06:10 554.54 01-AUG-05:10 0.00 0.00 0.00 0.00 27.42 13-AUG-12:50 6.69 14-AUG-03:00
September 1649.32 01-SEP-06:10 595.53 01-SEP-06:10 554.54 01-SEP-05:10 0.00 0.00 0.00 0.00 26.12 17-SEP-16:30 2.45 02-SEP-22:00
October 1649.32 02-OCT-06:10 595.53 02-OCT-06:10 554.54 02-OCT-05:10 0.00 0.00 0.00 0.00 19.98 29-OCT-14:00 6.90 16-OCT-03:00
November 1649.32 01-NOV-06:10 595.53 01-NOV-06:10 554.54 01-NOV-05:10 0.00 0.00 0.00 0.00 12.05 23-NOV-12:00 49.48 11-NOV-09:00
December 1649.32 01-DEC-07:10 595.53 01-DEC-07:10 554.54 01-DEC-06:10 0.00 0.00 0.00 0.00 16.79 10-DEC-14:50 51.18 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1649.32   595.53   554.54   0.00 0.00 0.00 0.00 7.77   2.45  
Maximum of Months 1649.32   595.53   554.54   0.00 0.00 0.00 0.00 35.76   54.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 69.12 02-JAN-07:10 110.28 02-JAN-07:10 50.76 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 69.12 01-FEB-07:10 110.28 01-FEB-07:10 50.76 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 69.12 01-MAR-07:10 110.28 01-MAR-07:10 50.76 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 69.12 03-APR-06:10 110.28 03-APR-06:10 50.76 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 69.12 01-MAY-06:10 110.28 01-MAY-06:10 50.76 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 69.12 01-JUN-06:10 110.28 01-JUN-06:10 50.76 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 69.12 03-JUL-06:10 110.28 03-JUL-06:10 50.76 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 69.12 01-AUG-06:10 110.28 01-AUG-06:10 50.76 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 69.12 01-SEP-06:10 110.28 01-SEP-06:10 50.76 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 69.12 02-OCT-06:10 110.28 02-OCT-06:10 50.76 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 69.12 01-NOV-06:10 110.28 01-NOV-06:10 50.76 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 69.12 01-DEC-07:10 110.28 01-DEC-07:10 50.76 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 69.12   110.28   50.76   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 69.12   110.28   50.76   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1166.51 02-JAN-07:10 388.80 02-JAN-07:10 1604.46 02-JAN-06:10 0.00 0.00 0.00 0.00 82.54 13-JAN-19:50 102.29 24-JAN-03:00
February 1166.51 01-FEB-07:10 388.80 01-FEB-07:10 1604.46 01-FEB-06:10 0.00 0.00 0.00 0.00 68.49 17-FEB-19:20 157.73 04-FEB-04:50
March 1166.51 01-MAR-07:10 388.80 01-MAR-07:10 1604.46 01-MAR-06:10 0.00 0.00 0.00 0.00 102.56 05-MAR-16:10 162.09 16-MAR-01:53
April 1166.51 03-APR-06:10 388.80 03-APR-06:10 1604.46 03-APR-05:10 0.00 0.00 0.00 0.00 118.41 23-APR-09:50 45.18 18-APR-23:52
May 1166.51 01-MAY-06:10 388.80 01-MAY-06:10 1604.46 01-MAY-05:10 0.00 0.00 0.00 0.00 186.51 29-MAY-17:00 14.83 07-MAY-06:00
June 1166.51 01-JUN-06:10 388.80 01-JUN-06:10 1604.46 01-JUN-05:10 0.00 0.00 0.00 0.00 148.95 18-JUN-13:00 0.00 01-JUN-00:01
July 1166.51 03-JUL-06:10 388.80 03-JUL-06:10 1604.46 03-JUL-05:10 0.00 0.00 0.00 0.00 184.81 30-JUL-16:00 0.54 14-JUL-18:40
August 1166.51 01-AUG-06:10 388.80 01-AUG-06:10 1604.46 01-AUG-05:10 0.00 0.00 0.00 0.00 147.30 13-AUG-12:30 5.67 14-AUG-03:05
September 1166.51 01-SEP-06:10 388.80 01-SEP-06:10 1604.46 01-SEP-05:10 0.00 0.00 0.00 0.00 144.58 17-SEP-17:10 1.55 02-SEP-22:00
October 1166.51 02-OCT-06:10 388.80 02-OCT-06:10 1604.46 02-OCT-05:10 0.00 0.00 0.00 0.00 119.95 01-OCT-13:20 14.99 16-OCT-03:03
November 1166.51 01-NOV-06:10 388.80 01-NOV-06:10 1604.46 01-NOV-05:10 0.00 0.00 0.00 0.00 95.20 22-NOV-19:50 158.40 11-NOV-09:00
December 1166.51 01-DEC-07:10 388.80 01-DEC-07:10 1604.46 01-DEC-06:10 0.00 0.00 0.00 0.00 100.28 10-DEC-14:50 161.39 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1166.51   388.80   1604.46   0.00 0.00 0.00 0.00 68.49   0.00  
Maximum of Months 1166.51   388.80   1604.46   0.00 0.00 0.00 0.00 186.51   162.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 64.27 02-JAN-07:10 117.81 02-JAN-07:10 129.65 02-JAN-06:10 0.00 0.00 0.00 0.00 5.76 15-JAN-12:00 16.08 24-JAN-03:00
February 64.27 01-FEB-07:10 117.81 01-FEB-07:10 129.65 01-FEB-06:10 0.00 0.00 0.00 0.00 4.74 20-FEB-15:10 27.92 04-FEB-04:50
March 64.27 01-MAR-07:10 117.81 01-MAR-07:10 129.65 01-MAR-06:10 0.00 0.00 0.00 0.00 8.52 05-MAR-14:10 27.35 16-MAR-01:53
April 64.27 03-APR-06:10 117.81 03-APR-06:10 129.65 03-APR-05:10 0.00 0.00 0.00 0.00 10.60 16-APR-12:51 7.77 19-APR-03:00
May 64.27 01-MAY-06:10 117.81 01-MAY-06:10 129.65 01-MAY-05:10 0.00 0.00 0.00 0.00 19.87 29-MAY-16:20 2.51 07-MAY-06:00
June 64.27 01-JUN-06:10 117.81 01-JUN-06:10 129.65 01-JUN-05:10 0.00 0.00 0.00 0.00 14.42 18-JUN-15:00 0.15 06-JUN-02:57
July 64.27 03-JUL-06:10 117.81 03-JUL-06:10 129.65 03-JUL-05:10 0.00 0.00 0.00 0.00 18.93 30-JUL-16:00 0.55 14-JUL-18:07
August 64.27 01-AUG-06:10 117.81 01-AUG-06:10 129.65 01-AUG-05:10 0.00 0.00 0.00 0.00 15.58 13-AUG-12:51 1.64 14-AUG-03:05
September 64.27 01-SEP-06:10 117.81 01-SEP-06:10 129.65 01-SEP-05:10 0.00 0.00 0.00 0.00 14.79 17-SEP-14:00 0.68 02-SEP-22:00
October 64.27 02-OCT-06:10 117.81 02-OCT-06:10 129.65 02-OCT-05:10 0.00 0.00 0.00 0.00 11.37 29-OCT-14:00 2.56 16-OCT-03:00
November 64.27 01-NOV-06:10 117.81 01-NOV-06:10 129.65 01-NOV-05:10 0.00 0.00 0.00 0.00 7.64 23-NOV-12:00 24.11 11-NOV-09:00
December 64.27 01-DEC-07:10 117.81 01-DEC-07:10 129.65 01-DEC-06:10 0.00 0.00 0.00 0.00 9.52 10-DEC-15:00 26.07 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 64.27   117.81   129.65   0.00 0.00 0.00 0.00 4.74   0.15  
Maximum of Months 64.27   117.81   129.65   0.00 0.00 0.00 0.00 19.87   27.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 SCRUB

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 45.36 02-JAN-07:10 72.37 02-JAN-07:10 33.31 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 45.36 01-FEB-07:10 72.37 01-FEB-07:10 33.31 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 45.36 01-MAR-07:10 72.37 01-MAR-07:10 33.31 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 45.36 03-APR-06:10 72.37 03-APR-06:10 33.31 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 45.36 01-MAY-06:10 72.37 01-MAY-06:10 33.31 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 45.36 01-JUN-06:10 72.37 01-JUN-06:10 33.31 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 45.36 03-JUL-06:10 72.37 03-JUL-06:10 33.31 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 45.36 01-AUG-06:10 72.37 01-AUG-06:10 33.31 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 45.36 01-SEP-06:10 72.37 01-SEP-06:10 33.31 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 45.36 02-OCT-06:10 72.37 02-OCT-06:10 33.31 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 45.36 01-NOV-06:10 72.37 01-NOV-06:10 33.31 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 45.36 01-DEC-07:10 72.37 01-DEC-07:10 33.31 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 45.36   72.37   33.31   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 45.36   72.37   33.31   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 SOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 272.19 02-JAN-07:10 170.10 02-JAN-07:10 249.62 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 272.19 01-FEB-07:10 170.10 01-FEB-07:10 249.62 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 272.19 01-MAR-07:10 170.10 01-MAR-07:10 249.62 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 272.19 03-APR-06:10 170.10 03-APR-06:10 249.62 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 272.19 01-MAY-06:10 170.10 01-MAY-06:10 249.62 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 272.19 01-JUN-06:10 170.10 01-JUN-06:10 249.62 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 272.19 03-JUL-06:10 170.10 03-JUL-06:10 249.62 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 272.19 01-AUG-06:10 170.10 01-AUG-06:10 249.62 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 272.19 01-SEP-06:10 170.10 01-SEP-06:10 249.62 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 272.19 02-OCT-06:10 170.10 02-OCT-06:10 249.62 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 272.19 01-NOV-06:10 170.10 01-NOV-06:10 249.62 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 272.19 01-DEC-07:10 170.10 01-DEC-07:10 249.62 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 272.19   170.10   249.62   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 272.19   170.10   249.62   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 120.97 02-JAN-07:10 75.60 02-JAN-07:10 110.94 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 120.97 01-FEB-07:10 75.60 01-FEB-07:10 110.94 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 120.97 01-MAR-07:10 75.60 01-MAR-07:10 110.94 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 120.97 03-APR-06:10 75.60 03-APR-06:10 110.94 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 120.97 01-MAY-06:10 75.60 01-MAY-06:10 110.94 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 120.97 01-JUN-06:10 75.60 01-JUN-06:10 110.94 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 120.97 03-JUL-06:10 75.60 03-JUL-06:10 110.94 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 120.97 01-AUG-06:10 75.60 01-AUG-06:10 110.94 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 120.97 01-SEP-06:10 75.60 01-SEP-06:10 110.94 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 120.97 02-OCT-06:10 75.60 02-OCT-06:10 110.94 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 120.97 01-NOV-06:10 75.60 01-NOV-06:10 110.94 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 120.97 01-DEC-07:10 75.60 01-DEC-07:10 110.94 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 120.97   75.60   110.94   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 120.97   75.60   110.94   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 388.84 02-JAN-07:10 243.00 02-JAN-07:10 356.60 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 388.84 01-FEB-07:10 243.00 01-FEB-07:10 356.60 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 388.84 01-MAR-07:10 243.00 01-MAR-07:10 356.60 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 388.84 03-APR-06:10 243.00 03-APR-06:10 356.60 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 388.84 01-MAY-06:10 243.00 01-MAY-06:10 356.60 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 388.84 01-JUN-06:10 243.00 01-JUN-06:10 356.60 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 388.84 03-JUL-06:10 243.00 03-JUL-06:10 356.60 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 388.84 01-AUG-06:10 243.00 01-AUG-06:10 356.60 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 388.84 01-SEP-06:10 243.00 01-SEP-06:10 356.60 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 388.84 02-OCT-06:10 243.00 02-OCT-06:10 356.60 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 388.84 01-NOV-06:10 243.00 01-NOV-06:10 356.60 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 388.84 01-DEC-07:10 243.00 01-DEC-07:10 356.60 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 388.84   243.00   356.60   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 388.84   243.00   356.60   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 648.06 02-JAN-07:10 216.00 02-JAN-07:10 891.37 02-JAN-06:10 0.00 0.00 0.00 0.00 60.95 13-JAN-19:50 81.91 24-JAN-03:00
February 648.06 01-FEB-07:10 216.00 01-FEB-07:10 891.37 01-FEB-06:10 0.00 0.00 0.00 0.00 50.91 17-FEB-19:20 125.30 04-FEB-04:50
March 648.06 01-MAR-07:10 216.00 01-MAR-07:10 891.37 01-MAR-06:10 0.00 0.00 0.00 0.00 75.23 05-MAR-16:10 130.05 16-MAR-01:53
April 648.06 03-APR-06:10 216.00 03-APR-06:10 891.37 03-APR-05:10 0.00 0.00 0.00 0.00 89.11 23-APR-09:50 37.75 18-APR-23:52
May 648.06 01-MAY-06:10 216.00 01-MAY-06:10 891.37 01-MAY-05:10 0.00 0.00 0.00 0.00 135.74 29-MAY-17:00 13.44 07-MAY-06:00
June 648.06 01-JUN-06:10 216.00 01-JUN-06:10 891.37 01-JUN-05:10 0.00 0.00 0.00 0.00 118.92 17-JUN-18:20 2.69 18-JUN-01:52
July 648.06 03-JUL-06:10 216.00 03-JUL-06:10 891.37 03-JUL-05:10 0.00 0.00 0.00 0.00 135.48 30-JUL-16:00 1.77 04-JUL-03:30
August 648.06 01-AUG-06:10 216.00 01-AUG-06:10 891.37 01-AUG-05:10 0.00 0.00 0.00 0.00 112.03 13-AUG-12:30 10.41 14-AUG-03:05
September 648.06 01-SEP-06:10 216.00 01-SEP-06:10 891.37 01-SEP-05:10 0.00 0.00 0.00 0.00 101.62 17-SEP-17:10 3.85 02-SEP-22:00
October 648.06 02-OCT-06:10 216.00 02-OCT-06:10 891.37 02-OCT-05:10 0.00 0.00 0.00 0.00 90.59 01-OCT-13:20 14.82 16-OCT-03:03
November 648.06 01-NOV-06:10 216.00 01-NOV-06:10 891.37 01-NOV-05:10 0.00 0.00 0.00 0.00 71.48 22-NOV-19:50 126.89 11-NOV-09:00
December 648.06 01-DEC-07:10 216.00 01-DEC-07:10 891.37 01-DEC-06:10 0.00 0.00 0.00 0.00 73.79 10-DEC-14:50 127.52 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 648.06   216.00   891.37   0.00 0.00 0.00 0.00 50.91   1.77  
Maximum of Months 648.06   216.00   891.37   0.00 0.00 0.00 0.00 135.74   130.05  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 332.64 02-JAN-07:10 530.72 02-JAN-07:10 244.30 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 332.64 01-FEB-07:10 530.72 01-FEB-07:10 244.30 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 332.64 01-MAR-07:10 530.72 01-MAR-07:10 244.30 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 332.64 03-APR-06:10 530.72 03-APR-06:10 244.30 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 332.64 01-MAY-06:10 530.72 01-MAY-06:10 244.30 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 332.64 01-JUN-06:10 530.72 01-JUN-06:10 244.30 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 332.64 03-JUL-06:10 530.72 03-JUL-06:10 244.30 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 332.64 01-AUG-06:10 530.72 01-AUG-06:10 244.30 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 332.64 01-SEP-06:10 530.72 01-SEP-06:10 244.30 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 332.64 02-OCT-06:10 530.72 02-OCT-06:10 244.30 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 332.64 01-NOV-06:10 530.72 01-NOV-06:10 244.30 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 332.64 01-DEC-07:10 530.72 01-DEC-07:10 244.30 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 332.64   530.72   244.30   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 332.64   530.72   244.30   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 85.54 02-JAN-07:10 320.76 02-JAN-07:10 39.35 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 85.54 01-FEB-07:10 320.76 01-FEB-07:10 39.35 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 85.54 01-MAR-07:10 320.76 01-MAR-07:10 39.35 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 85.54 03-APR-06:10 320.76 03-APR-06:10 39.35 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 85.54 01-MAY-06:10 320.76 01-MAY-06:10 39.35 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 85.54 01-JUN-06:10 320.76 01-JUN-06:10 39.35 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 85.54 03-JUL-06:10 320.76 03-JUL-06:10 39.35 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 85.54 01-AUG-06:10 320.76 01-AUG-06:10 39.35 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 85.54 01-SEP-06:10 320.76 01-SEP-06:10 39.35 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 85.54 02-OCT-06:10 320.76 02-OCT-06:10 39.35 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 85.54 01-NOV-06:10 320.76 01-NOV-06:10 39.35 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 85.54 01-DEC-07:10 320.76 01-DEC-07:10 39.35 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 85.54   320.76   39.35   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 85.54   320.76   39.35   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 198.72 02-JAN-07:10 745.20 02-JAN-07:10 91.43 02-JAN-06:10 0.00 0.00 0.00 0.00 85.47 15-JAN-14:00 99.59 24-JAN-03:00
February 198.72 01-FEB-07:10 745.20 01-FEB-07:10 91.43 01-FEB-06:10 0.00 0.00 0.00 0.00 67.35 20-FEB-14:50 192.45 04-FEB-04:50
March 198.72 01-MAR-07:10 745.20 01-MAR-07:10 91.43 01-MAR-06:10 0.00 0.00 0.00 0.00 70.52 05-MAR-14:10 193.14 16-MAR-01:53
April 198.72 03-APR-06:10 745.20 03-APR-06:10 91.43 03-APR-05:10 0.00 0.00 0.00 0.00 80.10 16-APR-12:51 58.71 18-APR-23:52
May 198.72 01-MAY-06:10 745.20 01-MAY-06:10 91.43 01-MAY-05:10 0.00 0.00 0.00 0.00 147.52 29-MAY-16:15 20.07 07-MAY-06:00
June 198.72 01-JUN-06:10 745.20 01-JUN-06:10 91.43 01-JUN-05:10 0.00 0.00 0.00 0.00 102.67 16-JUN-23:40 9.83 18-JUN-19:10
July 198.72 03-JUL-06:10 745.20 03-JUL-06:10 91.43 03-JUL-05:10 0.00 0.00 0.00 0.00 121.72 30-JUL-15:35 19.15 02-JUL-15:50
August 198.72 01-AUG-06:10 745.20 01-AUG-06:10 91.43 01-AUG-05:10 0.00 0.00 0.00 0.00 116.41 13-AUG-12:50 27.93 14-AUG-02:53
September 198.72 01-SEP-06:10 745.20 01-SEP-06:10 91.43 01-SEP-05:10 0.00 0.00 0.00 0.00 110.82 17-SEP-13:50 10.48 02-SEP-22:00
October 198.72 02-OCT-06:10 745.20 02-OCT-06:10 91.43 02-OCT-05:10 0.00 0.00 0.00 0.00 101.84 29-OCT-14:00 18.75 16-OCT-02:53
November 198.72 01-NOV-06:10 745.20 01-NOV-06:10 91.43 01-NOV-05:10 0.00 0.00 0.00 0.00 67.87 23-NOV-12:00 175.83 11-NOV-09:00
December 198.72 01-DEC-07:10 745.20 01-DEC-07:10 91.43 01-DEC-06:10 0.00 0.00 0.00 0.00 103.09 10-DEC-14:50 176.72 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 198.72   745.20   91.43   0.00 0.00 0.00 0.00 67.35   9.83  
Maximum of Months 198.72   745.20   91.43   0.00 0.00 0.00 0.00 147.52   193.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 105.84 02-JAN-07:10 168.86 02-JAN-07:10 77.73 02-JAN-06:10 0.00 0.00 0.00 0.00 16.25 15-JAN-14:00 26.60 24-JAN-03:00
February 105.84 01-FEB-07:10 168.86 01-FEB-07:10 77.73 01-FEB-06:10 0.00 0.00 0.00 0.00 14.79 20-FEB-14:50 49.43 04-FEB-04:50
March 105.84 01-MAR-07:10 168.86 01-MAR-07:10 77.73 01-MAR-06:10 0.00 0.00 0.00 0.00 17.94 05-MAR-16:10 48.91 16-MAR-01:53
April 105.84 03-APR-06:10 168.86 03-APR-06:10 77.73 03-APR-05:10 0.00 0.00 0.00 0.00 19.18 16-APR-18:30 14.23 18-APR-23:52
May 105.84 01-MAY-06:10 168.86 01-MAY-06:10 77.73 01-MAY-05:10 0.00 0.00 0.00 0.00 38.24 29-MAY-16:20 4.70 07-MAY-06:00
June 105.84 01-JUN-06:10 168.86 01-JUN-06:10 77.73 01-JUN-05:10 0.00 0.00 0.00 0.00 28.38 18-JUN-15:00 0.82 18-JUN-01:52
July 105.84 03-JUL-06:10 168.86 03-JUL-06:10 77.73 03-JUL-05:10 0.00 0.00 0.00 0.00 32.98 30-JUL-16:00 2.18 02-JUL-15:50
August 105.84 01-AUG-06:10 168.86 01-AUG-06:10 77.73 01-AUG-05:10 0.00 0.00 0.00 0.00 29.32 13-AUG-12:50 4.29 14-AUG-02:53
September 105.84 01-SEP-06:10 168.86 01-SEP-06:10 77.73 01-SEP-05:10 0.00 0.00 0.00 0.00 28.45 17-SEP-16:30 1.69 02-SEP-22:00
October 105.84 02-OCT-06:10 168.86 02-OCT-06:10 77.73 02-OCT-05:10 0.00 0.00 0.00 0.00 24.37 29-OCT-14:00 4.21 16-OCT-02:53
November 105.84 01-NOV-06:10 168.86 01-NOV-06:10 77.73 01-NOV-05:10 0.00 0.00 0.00 0.00 15.71 19-NOV-14:40 46.39 11-NOV-09:00
December 105.84 01-DEC-07:10 168.86 01-DEC-07:10 77.73 01-DEC-06:10 0.00 0.00 0.00 0.00 24.17 10-DEC-14:50 45.72 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 105.84   168.86   77.73   0.00 0.00 0.00 0.00 14.79   0.82  
Maximum of Months 105.84   168.86   77.73   0.00 0.00 0.00 0.00 38.24   49.43  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 138.24 02-JAN-07:10 220.56 02-JAN-07:10 101.53 02-JAN-06:10 0.00 0.00 0.00 0.00 23.70 15-JAN-14:00 26.46 24-JAN-03:00
February 138.24 01-FEB-07:10 220.56 01-FEB-07:10 101.53 01-FEB-06:10 0.00 0.00 0.00 0.00 19.32 20-FEB-14:50 49.83 04-FEB-04:50
March 138.24 01-MAR-07:10 220.56 01-MAR-07:10 101.53 01-MAR-06:10 0.00 0.00 0.00 0.00 21.35 05-MAR-16:10 49.74 16-MAR-01:53
April 138.24 03-APR-06:10 220.56 03-APR-06:10 101.53 03-APR-05:10 0.00 0.00 0.00 0.00 22.71 16-APR-18:30 14.82 18-APR-23:52
May 138.24 01-MAY-06:10 220.56 01-MAY-06:10 101.53 01-MAY-05:10 0.00 0.00 0.00 0.00 41.22 29-MAY-16:20 5.67 07-MAY-06:10
June 138.24 01-JUN-06:10 220.56 01-JUN-06:10 101.53 01-JUN-05:10 0.00 0.00 0.00 0.00 32.41 17-JUN-18:20 2.53 25-JUN-10:00
July 138.24 03-JUL-06:10 220.56 03-JUL-06:10 101.53 03-JUL-05:10 0.00 0.00 0.00 0.00 35.74 30-JUL-16:00 3.82 02-JUL-15:50
August 138.24 01-AUG-06:10 220.56 01-AUG-06:10 101.53 01-AUG-05:10 0.00 0.00 0.00 0.00 32.35 13-AUG-12:50 5.46 14-AUG-02:53
September 138.24 01-SEP-06:10 220.56 01-SEP-06:10 101.53 01-SEP-05:10 0.00 0.00 0.00 0.00 32.04 17-SEP-16:30 1.90 02-SEP-22:00
October 138.24 02-OCT-06:10 220.56 02-OCT-06:10 101.53 02-OCT-05:10 0.00 0.00 0.00 0.00 29.26 29-OCT-14:00 4.20 16-OCT-03:00
November 138.24 01-NOV-06:10 220.56 01-NOV-06:10 101.53 01-NOV-05:10 0.00 0.00 0.00 0.00 21.57 22-NOV-19:50 45.44 11-NOV-09:00
December 138.24 01-DEC-07:10 220.56 01-DEC-07:10 101.53 01-DEC-06:10 0.00 0.00 0.00 0.00 29.19 10-DEC-14:50 46.05 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 138.24   220.56   101.53   0.00 0.00 0.00 0.00 19.32   1.90  
Maximum of Months 138.24   220.56   101.53   0.00 0.00 0.00 0.00 41.22   49.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 9.07 02-JAN-07:10 34.02 02-JAN-07:10 4.17 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 9.07 01-FEB-07:10 34.02 01-FEB-07:10 4.17 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 9.07 01-MAR-07:10 34.02 01-MAR-07:10 4.17 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 9.07 03-APR-06:10 34.02 03-APR-06:10 4.17 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 9.07 01-MAY-06:10 34.02 01-MAY-06:10 4.17 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 9.07 01-JUN-06:10 34.02 01-JUN-06:10 4.17 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 9.07 03-JUL-06:10 34.02 03-JUL-06:10 4.17 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 9.07 01-AUG-06:10 34.02 01-AUG-06:10 4.17 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 9.07 01-SEP-06:10 34.02 01-SEP-06:10 4.17 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 9.07 02-OCT-06:10 34.02 02-OCT-06:10 4.17 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 9.07 01-NOV-06:10 34.02 01-NOV-06:10 4.17 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 9.07 01-DEC-07:10 34.02 01-DEC-07:10 4.17 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 9.07   34.02   4.17   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9.07   34.02   4.17   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 77.76 02-JAN-07:10 291.60 02-JAN-07:10 35.78 02-JAN-06:10 0.00 0.00 0.00 0.00 19.62 15-JAN-14:00 34.07 24-JAN-03:00
February 77.76 01-FEB-07:10 291.60 01-FEB-07:10 35.78 01-FEB-06:10 0.00 0.00 0.00 0.00 17.48 20-FEB-14:50 63.30 04-FEB-04:50
March 77.76 01-MAR-07:10 291.60 01-MAR-07:10 35.78 01-MAR-06:10 0.00 0.00 0.00 0.00 21.64 05-MAR-14:10 63.04 16-MAR-01:53
April 77.76 03-APR-06:10 291.60 03-APR-06:10 35.78 03-APR-05:10 0.00 0.00 0.00 0.00 23.78 16-APR-12:51 18.57 18-APR-23:52
May 77.76 01-MAY-06:10 291.60 01-MAY-06:10 35.78 01-MAY-05:10 0.00 0.00 0.00 0.00 46.77 29-MAY-16:00 6.35 07-MAY-06:00
June 77.76 01-JUN-06:10 291.60 01-JUN-06:10 35.78 01-JUN-05:10 0.00 0.00 0.00 0.00 33.85 18-JUN-15:00 1.22 18-JUN-01:52
July 77.76 03-JUL-06:10 291.60 03-JUL-06:10 35.78 03-JUL-05:10 0.00 0.00 0.00 0.00 39.98 30-JUL-16:00 3.82 02-JUL-15:50
August 77.76 01-AUG-06:10 291.60 01-AUG-06:10 35.78 01-AUG-05:10 0.00 0.00 0.00 0.00 36.28 13-AUG-12:50 6.48 14-AUG-02:57
September 77.76 01-SEP-06:10 291.60 01-SEP-06:10 35.78 01-SEP-05:10 0.00 0.00 0.00 0.00 35.11 17-SEP-16:30 2.22 02-SEP-22:00
October 77.76 02-OCT-06:10 291.60 02-OCT-06:10 35.78 02-OCT-05:10 0.00 0.00 0.00 0.00 30.15 29-OCT-14:00 6.11 16-OCT-02:53
November 77.76 01-NOV-06:10 291.60 01-NOV-06:10 35.78 01-NOV-05:10 0.00 0.00 0.00 0.00 19.19 23-NOV-12:00 59.13 11-NOV-09:00
December 77.76 01-DEC-07:10 291.60 01-DEC-07:10 35.78 01-DEC-06:10 0.00 0.00 0.00 0.00 29.56 10-DEC-14:50 58.56 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 77.76   291.60   35.78   0.00 0.00 0.00 0.00 17.48   1.22  
Maximum of Months 77.76   291.60   35.78   0.00 0.00 0.00 0.00 46.77   63.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 38.88 02-JAN-07:10 62.03 02-JAN-07:10 28.55 02-JAN-06:10 0.00 0.00 0.00 0.00 1161.54 02-JAN-13:55 3432.83 25-JAN-07:01
February 38.88 01-FEB-07:10 62.03 01-FEB-07:10 28.55 01-FEB-06:10 0.00 0.00 0.00 0.00 1065.91 02-FEB-14:00 3383.22 03-FEB-07:01
March 38.88 01-MAR-07:10 62.03 01-MAR-07:10 28.55 01-MAR-06:10 0.00 0.00 0.00 0.00 1072.99 13-MAR-15:00 4251.29 16-MAR-06:01
April 38.88 03-APR-06:10 62.03 03-APR-06:10 28.55 03-APR-05:10 0.00 0.00 0.00 0.00 1503.71 17-APR-14:05 1818.49 19-APR-06:01
May 38.88 01-MAY-06:10 62.03 01-MAY-06:10 28.55 01-MAY-05:10 0.00 0.00 0.00 0.00 1842.39 22-MAY-13:00 432.14 10-MAY-14:53
June 38.88 01-JUN-06:10 62.03 01-JUN-06:10 28.55 01-JUN-05:10 0.00 0.00 0.00 0.00 2176.67 08-JUN-06:01 71.18 13-JUN-17:06
July 38.88 03-JUL-06:10 62.03 03-JUL-06:10 28.55 03-JUL-05:10 0.00 0.00 0.00 0.00 2080.22 10-JUL-06:01 61.45 14-JUL-17:06
August 38.88 01-AUG-06:10 62.03 01-AUG-06:10 28.55 01-AUG-05:10 0.00 0.00 0.00 0.00 2212.92 11-AUG-06:01 74.18 23-AUG-17:06
September 38.88 01-SEP-06:10 62.03 01-SEP-06:10 28.55 01-SEP-05:10 0.00 0.00 0.00 0.00 2094.51 18-SEP-06:01 18.48 27-SEP-17:55
October 38.88 02-OCT-06:10 62.03 02-OCT-06:10 28.55 02-OCT-05:10 0.00 0.00 0.00 0.00 1863.60 02-OCT-06:01 438.56 26-OCT-13:53
November 38.88 01-NOV-06:10 62.03 01-NOV-06:10 28.55 01-NOV-05:10 0.00 0.00 0.00 0.00 1314.21 30-NOV-07:02 3407.77 27-NOV-07:01
December 38.88 01-DEC-07:10 62.03 01-DEC-07:10 28.55 01-DEC-06:10 0.00 0.00 0.00 0.00 933.50 08-DEC-11:00 4088.92 15-DEC-07:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 38.88   62.03   28.55   0.00 0.00 0.00 0.00 933.50   18.48  
Maximum of Months 38.88   62.03   28.55   0.00 0.00 0.00 0.00 2212.92   4251.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1814.58 02-JAN-07:10 393.12 02-JAN-07:10 332.67 02-JAN-06:10 0.00 0.00 0.00 0.00 40.71 29-JAN-12:50 110.09 24-JAN-03:00
February 1814.58 01-FEB-07:10 393.12 01-FEB-07:10 332.67 01-FEB-06:10 0.00 0.00 0.00 0.00 31.63 19-FEB-16:00 176.31 04-FEB-05:20
March 1814.58 01-MAR-07:10 393.12 01-MAR-07:10 332.67 01-MAR-06:10 0.00 0.00 0.00 0.00 63.46 05-MAR-14:10 179.40 16-MAR-02:00
April 1814.58 03-APR-06:10 393.12 03-APR-06:10 332.67 03-APR-05:10 0.00 0.00 0.00 0.00 81.18 16-APR-18:40 58.29 18-APR-23:52
May 1814.58 01-MAY-06:10 393.12 01-MAY-06:10 332.67 01-MAY-05:10 0.00 0.00 0.00 0.00 147.26 29-MAY-16:20 25.27 25-MAY-04:40
June 1814.58 01-JUN-06:10 393.12 01-JUN-06:10 332.67 01-JUN-05:10 0.00 0.00 0.00 0.00 112.66 16-JUN-23:50 10.81 21-JUN-18:30
July 1814.58 03-JUL-06:10 393.12 03-JUL-06:10 332.67 03-JUL-05:10 0.00 0.00 0.00 0.00 127.15 30-JUL-16:00 16.31 04-JUL-02:51
August 1814.58 01-AUG-06:10 393.12 01-AUG-06:10 332.67 01-AUG-05:10 0.00 0.00 0.00 0.00 115.19 13-AUG-12:50 18.59 14-AUG-03:20
September 1814.58 01-SEP-06:10 393.12 01-SEP-06:10 332.67 01-SEP-05:10 0.00 0.00 0.00 0.00 106.47 17-SEP-16:30 8.85 26-SEP-04:00
October 1814.58 02-OCT-06:10 393.12 02-OCT-06:10 332.67 02-OCT-05:10 0.00 0.00 0.00 0.00 87.27 01-OCT-13:10 20.29 16-OCT-03:20
November 1814.58 01-NOV-06:10 393.12 01-NOV-06:10 332.67 01-NOV-05:10 0.00 0.00 0.00 0.00 62.72 22-NOV-21:20 193.99 11-NOV-09:00
December 1814.58 01-DEC-07:10 393.12 01-DEC-07:10 332.67 01-DEC-06:10 0.00 0.00 0.00 0.00 66.51 10-DEC-14:34 167.28 15-DEC-03:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1814.58   393.12   332.67   0.00 0.00 0.00 0.00 31.63   8.85  
Maximum of Months 1814.58   393.12   332.67   0.00 0.00 0.00 0.00 147.26   193.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 34.56 02-JAN-07:10 51.84 02-JAN-07:10 25.38 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 34.56 01-FEB-07:10 51.84 01-FEB-07:10 25.38 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 34.56 01-MAR-07:10 51.84 01-MAR-07:10 25.38 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 34.56 03-APR-06:10 51.84 03-APR-06:10 25.38 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 34.56 01-MAY-06:10 51.84 01-MAY-06:10 25.38 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 34.56 01-JUN-06:10 51.84 01-JUN-06:10 25.38 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 34.56 03-JUL-06:10 51.84 03-JUL-06:10 25.38 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 34.56 01-AUG-06:10 51.84 01-AUG-06:10 25.38 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 34.56 01-SEP-06:10 51.84 01-SEP-06:10 25.38 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 34.56 02-OCT-06:10 51.84 02-OCT-06:10 25.38 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 34.56 01-NOV-06:10 51.84 01-NOV-06:10 25.38 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 34.56 01-DEC-07:10 51.84 01-DEC-07:10 25.38 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 34.56   51.84   25.38   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 34.56   51.84   25.38   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 37.80 02-JAN-07:10 69.30 02-JAN-07:10 76.26 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 37.80 01-FEB-07:10 69.30 01-FEB-07:10 76.26 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 37.80 01-MAR-07:10 69.30 01-MAR-07:10 76.26 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 37.80 03-APR-06:10 69.30 03-APR-06:10 76.26 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 37.80 01-MAY-06:10 69.30 01-MAY-06:10 76.26 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 37.80 01-JUN-06:10 69.30 01-JUN-06:10 76.26 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 37.80 03-JUL-06:10 69.30 03-JUL-06:10 76.26 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 37.80 01-AUG-06:10 69.30 01-AUG-06:10 76.26 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 37.80 01-SEP-06:10 69.30 01-SEP-06:10 76.26 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 37.80 02-OCT-06:10 69.30 02-OCT-06:10 76.26 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 37.80 01-NOV-06:10 69.30 01-NOV-06:10 76.26 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 37.80 01-DEC-07:10 69.30 01-DEC-07:10 76.26 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 37.80   69.30   76.26   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37.80   69.30   76.26   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 777.68 02-JAN-07:10 486.00 02-JAN-07:10 392.21 02-JAN-06:10 0.00 0.00 0.00 0.00 64.67 15-JAN-12:00 121.75 24-JAN-03:00
February 777.68 01-FEB-07:10 486.00 01-FEB-07:10 392.21 01-FEB-06:10 0.00 0.00 0.00 0.00 47.31 20-FEB-14:40 190.14 04-FEB-05:20
March 777.68 01-MAR-07:10 486.00 01-MAR-07:10 392.21 01-MAR-06:10 0.00 0.00 0.00 0.00 84.62 05-MAR-14:10 196.74 16-MAR-02:00
April 777.68 03-APR-06:10 486.00 03-APR-06:10 392.21 03-APR-05:10 0.00 0.00 0.00 0.00 98.66 23-APR-09:50 66.44 18-APR-23:52
May 777.68 01-MAY-06:10 486.00 01-MAY-06:10 392.21 01-MAY-05:10 0.00 0.00 0.00 0.00 153.86 29-MAY-16:18 27.96 25-MAY-04:40
June 777.68 01-JUN-06:10 486.00 01-JUN-06:10 392.21 01-JUN-05:10 0.00 0.00 0.00 0.00 133.69 18-JUN-12:50 8.58 18-JUN-01:52
July 777.68 03-JUL-06:10 486.00 03-JUL-06:10 392.21 03-JUL-05:10 0.00 0.00 0.00 0.00 157.81 30-JUL-16:00 17.95 04-JUL-02:51
August 777.68 01-AUG-06:10 486.00 01-AUG-06:10 392.21 01-AUG-05:10 0.00 0.00 0.00 0.00 143.39 13-AUG-12:50 22.42 14-AUG-03:20
September 777.68 01-SEP-06:10 486.00 01-SEP-06:10 392.21 01-SEP-05:10 0.00 0.00 0.00 0.00 127.36 17-SEP-13:50 10.79 26-SEP-04:00
October 777.68 02-OCT-06:10 486.00 02-OCT-06:10 392.21 02-OCT-05:10 0.00 0.00 0.00 0.00 110.32 01-OCT-13:10 24.55 16-OCT-03:20
November 777.68 01-NOV-06:10 486.00 01-NOV-06:10 392.21 01-NOV-05:10 0.00 0.00 0.00 0.00 81.83 23-NOV-12:00 188.59 11-NOV-09:00
December 777.68 01-DEC-07:10 486.00 01-DEC-07:10 392.21 01-DEC-06:10 0.00 0.00 0.00 0.00 93.48 10-DEC-14:00 180.39 15-DEC-03:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 777.68   486.00   392.21   0.00 0.00 0.00 0.00 47.31   8.58  
Maximum of Months 777.68   486.00   392.21   0.00 0.00 0.00 0.00 157.81   196.74  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1166.51 02-JAN-07:10 729.00 02-JAN-07:10 588.32 02-JAN-06:10 0.00 0.00 0.00 0.00 41.54 15-JAN-15:00 59.80 24-JAN-03:00
February 1166.51 01-FEB-07:10 729.00 01-FEB-07:10 588.32 01-FEB-06:10 0.00 0.00 0.00 0.00 36.18 20-FEB-15:20 93.80 04-FEB-05:20
March 1166.51 01-MAR-07:10 729.00 01-MAR-07:10 588.32 01-MAR-06:10 0.00 0.00 0.00 0.00 51.01 05-MAR-14:10 93.54 16-MAR-02:00
April 1166.51 03-APR-06:10 729.00 03-APR-06:10 588.32 03-APR-05:10 0.00 0.00 0.00 0.00 57.38 23-APR-10:30 30.38 18-APR-23:52
May 1166.51 01-MAY-06:10 729.00 01-MAY-06:10 588.32 01-MAY-05:10 0.00 0.00 0.00 0.00 99.16 29-MAY-17:00 11.43 25-MAY-04:40
June 1166.51 01-JUN-06:10 729.00 01-JUN-06:10 588.32 01-JUN-05:10 0.00 0.00 0.00 0.00 79.71 18-JUN-12:50 1.72 06-JUN-03:10
July 1166.51 03-JUL-06:10 729.00 03-JUL-06:10 588.32 03-JUL-05:10 0.00 0.00 0.00 0.00 93.67 30-JUL-16:00 3.50 04-JUL-03:10
August 1166.51 01-AUG-06:10 729.00 01-AUG-06:10 588.32 01-AUG-05:10 0.00 0.00 0.00 0.00 78.68 13-AUG-12:30 4.91 14-AUG-03:50
September 1166.51 01-SEP-06:10 729.00 01-SEP-06:10 588.32 01-SEP-05:10 0.00 0.00 0.00 0.00 77.27 17-SEP-16:30 4.20 26-SEP-04:00
October 1166.51 02-OCT-06:10 729.00 02-OCT-06:10 588.32 02-OCT-05:10 0.00 0.00 0.00 0.00 63.05 01-OCT-13:10 9.69 16-OCT-03:20
November 1166.51 01-NOV-06:10 729.00 01-NOV-06:10 588.32 01-NOV-05:10 0.00 0.00 0.00 0.00 47.35 23-NOV-12:00 95.89 11-NOV-09:00
December 1166.51 01-DEC-07:10 729.00 01-DEC-07:10 588.32 01-DEC-06:10 0.00 0.00 0.00 0.00 58.53 10-DEC-14:40 87.95 15-DEC-05:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1166.51   729.00   588.32   0.00 0.00 0.00 0.00 36.18   1.72  
Maximum of Months 1166.51   729.00   588.32   0.00 0.00 0.00 0.00 99.16   95.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1555.35 02-JAN-07:10 972.00 02-JAN-07:10 784.42 02-JAN-06:10 0.00 0.00 0.00 0.00 55.47 15-JAN-15:00 77.47 24-JAN-03:00
February 1555.35 01-FEB-07:10 972.00 01-FEB-07:10 784.42 01-FEB-06:10 0.00 0.00 0.00 0.00 48.97 20-FEB-15:20 123.04 04-FEB-05:20
March 1555.35 01-MAR-07:10 972.00 01-MAR-07:10 784.42 01-MAR-06:10 0.00 0.00 0.00 0.00 69.68 05-MAR-14:10 121.56 16-MAR-02:00
April 1555.35 03-APR-06:10 972.00 03-APR-06:10 784.42 03-APR-05:10 0.00 0.00 0.00 0.00 78.94 23-APR-10:30 38.61 18-APR-23:52
May 1555.35 01-MAY-06:10 972.00 01-MAY-06:10 784.42 01-MAY-05:10 0.00 0.00 0.00 0.00 135.84 29-MAY-17:00 11.82 25-MAY-04:40
June 1555.35 01-JUN-06:10 972.00 01-JUN-06:10 784.42 01-JUN-05:10 0.00 0.00 0.00 0.00 109.22 18-JUN-12:50 1.47 06-JUN-03:10
July 1555.35 03-JUL-06:10 972.00 03-JUL-06:10 784.42 03-JUL-05:10 0.00 0.00 0.00 0.00 129.11 30-JUL-16:00 2.65 14-JUL-18:30
August 1555.35 01-AUG-06:10 972.00 01-AUG-06:10 784.42 01-AUG-05:10 0.00 0.00 0.00 0.00 107.19 13-AUG-12:30 3.21 11-AUG-24:00
September 1555.35 01-SEP-06:10 972.00 01-SEP-06:10 784.42 01-SEP-05:10 0.00 0.00 0.00 0.00 105.98 17-SEP-16:30 3.85 26-SEP-04:00
October 1555.35 02-OCT-06:10 972.00 02-OCT-06:10 784.42 02-OCT-05:10 0.00 0.00 0.00 0.00 87.21 01-OCT-13:10 9.91 28-OCT-02:32
November 1555.35 01-NOV-06:10 972.00 01-NOV-06:10 784.42 01-NOV-05:10 0.00 0.00 0.00 0.00 64.39 23-NOV-12:00 123.80 11-NOV-09:00
December 1555.35 01-DEC-07:10 972.00 01-DEC-07:10 784.42 01-DEC-06:10 0.00 0.00 0.00 0.00 78.36 10-DEC-14:40 115.35 15-DEC-05:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1555.35   972.00   784.42   0.00 0.00 0.00 0.00 48.97   1.47  
Maximum of Months 1555.35   972.00   784.42   0.00 0.00 0.00 0.00 135.84   123.80  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 181.46 02-JAN-07:10 113.40 02-JAN-07:10 91.52 02-JAN-06:10 0.00 0.00 0.00 0.00 9.18 13-JAN-19:40 20.47 24-JAN-03:00
February 181.46 01-FEB-07:10 113.40 01-FEB-07:10 91.52 01-FEB-06:10 0.00 0.00 0.00 0.00 7.41 19-FEB-16:00 33.04 04-FEB-05:20
March 181.46 01-MAR-07:10 113.40 01-MAR-07:10 91.52 01-MAR-06:10 0.00 0.00 0.00 0.00 14.28 05-MAR-16:10 33.46 16-MAR-02:00
April 181.46 03-APR-06:10 113.40 03-APR-06:10 91.52 03-APR-05:10 0.00 0.00 0.00 0.00 16.82 16-APR-18:00 10.20 18-APR-23:52
May 181.46 01-MAY-06:10 113.40 01-MAY-06:10 91.52 01-MAY-05:10 0.00 0.00 0.00 0.00 30.93 29-MAY-17:00 3.52 25-MAY-04:40
June 181.46 01-JUN-06:10 113.40 01-JUN-06:10 91.52 01-JUN-05:10 0.00 0.00 0.00 0.00 23.19 18-JUN-14:50 0.76 05-JUN-22:00
July 181.46 03-JUL-06:10 113.40 03-JUL-06:10 91.52 03-JUL-05:10 0.00 0.00 0.00 0.00 28.63 30-JUL-16:00 1.36 04-JUL-02:51
August 181.46 01-AUG-06:10 113.40 01-AUG-06:10 91.52 01-AUG-05:10 0.00 0.00 0.00 0.00 24.28 13-AUG-12:50 1.54 14-AUG-03:20
September 181.46 01-SEP-06:10 113.40 01-SEP-06:10 91.52 01-SEP-05:10 0.00 0.00 0.00 0.00 22.75 17-SEP-17:10 1.03 26-SEP-04:00
October 181.46 02-OCT-06:10 113.40 02-OCT-06:10 91.52 02-OCT-05:10 0.00 0.00 0.00 0.00 18.69 01-OCT-13:10 3.08 16-OCT-03:20
November 181.46 01-NOV-06:10 113.40 01-NOV-06:10 91.52 01-NOV-05:10 0.00 0.00 0.00 0.00 14.02 22-NOV-20:10 34.03 11-NOV-09:00
December 181.46 01-DEC-07:10 113.40 01-DEC-07:10 91.52 01-DEC-06:10 0.00 0.00 0.00 0.00 13.87 10-DEC-14:40 31.60 15-DEC-03:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 181.46   113.40   91.52   0.00 0.00 0.00 0.00 7.41   0.76  
Maximum of Months 181.46   113.40   91.52   0.00 0.00 0.00 0.00 30.93   34.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 756.07 02-JAN-07:10 472.50 02-JAN-07:10 381.32 02-JAN-06:10 0.00 0.00 0.00 0.00 61.18 15-JAN-15:00 70.11 24-JAN-03:00
February 756.07 01-FEB-07:10 472.50 01-FEB-07:10 381.32 01-FEB-06:10 0.00 0.00 0.00 0.00 52.94 20-FEB-15:20 114.39 04-FEB-05:20
March 756.07 01-MAR-07:10 472.50 01-MAR-07:10 381.32 01-MAR-06:10 0.00 0.00 0.00 0.00 61.45 05-MAR-16:10 115.03 16-MAR-02:00
April 756.07 03-APR-06:10 472.50 03-APR-06:10 381.32 03-APR-05:10 0.00 0.00 0.00 0.00 66.43 16-APR-18:40 39.32 18-APR-23:52
May 756.07 01-MAY-06:10 472.50 01-MAY-06:10 381.32 01-MAY-05:10 0.00 0.00 0.00 0.00 118.60 29-MAY-17:00 18.80 25-MAY-04:40
June 756.07 01-JUN-06:10 472.50 01-JUN-06:10 381.32 01-JUN-05:10 0.00 0.00 0.00 0.00 93.50 18-JUN-12:50 8.33 18-JUN-20:00
July 756.07 03-JUL-06:10 472.50 03-JUL-06:10 381.32 03-JUL-05:10 0.00 0.00 0.00 0.00 104.53 30-JUL-16:00 11.87 04-JUL-02:51
August 756.07 01-AUG-06:10 472.50 01-AUG-06:10 381.32 01-AUG-05:10 0.00 0.00 0.00 0.00 93.01 13-AUG-12:30 15.32 14-AUG-03:20
September 756.07 01-SEP-06:10 472.50 01-SEP-06:10 381.32 01-SEP-05:10 0.00 0.00 0.00 0.00 94.99 17-SEP-16:30 7.96 26-SEP-04:00
October 756.07 02-OCT-06:10 472.50 02-OCT-06:10 381.32 02-OCT-05:10 0.00 0.00 0.00 0.00 81.43 29-OCT-14:10 14.32 16-OCT-03:20
November 756.07 01-NOV-06:10 472.50 01-NOV-06:10 381.32 01-NOV-05:10 0.00 0.00 0.00 0.00 60.22 23-NOV-12:00 129.58 11-NOV-09:00
December 756.07 01-DEC-07:10 472.50 01-DEC-07:10 381.32 01-DEC-06:10 0.00 0.00 0.00 0.00 80.55 10-DEC-14:40 105.57 15-DEC-05:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 756.07   472.50   381.32   0.00 0.00 0.00 0.00 52.94   7.96  
Maximum of Months 756.07   472.50   381.32   0.00 0.00 0.00 0.00 118.60   129.58  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 486.05 02-JAN-07:10 303.75 02-JAN-07:10 245.13 02-JAN-06:10 0.00 0.00 0.00 0.00 39.56 15-JAN-15:00 41.82 24-JAN-03:00
February 486.05 01-FEB-07:10 303.75 01-FEB-07:10 245.13 01-FEB-06:10 0.00 0.00 0.00 0.00 33.97 20-FEB-15:20 70.75 04-FEB-05:20
March 486.05 01-MAR-07:10 303.75 01-MAR-07:10 245.13 01-MAR-06:10 0.00 0.00 0.00 0.00 38.23 05-MAR-16:10 69.81 16-MAR-02:00
April 486.05 03-APR-06:10 303.75 03-APR-06:10 245.13 03-APR-05:10 0.00 0.00 0.00 0.00 44.13 23-APR-11:50 22.63 18-APR-23:52
May 486.05 01-MAY-06:10 303.75 01-MAY-06:10 245.13 01-MAY-05:10 0.00 0.00 0.00 0.00 73.62 29-MAY-16:20 9.68 25-MAY-04:40
June 486.05 01-JUN-06:10 303.75 01-JUN-06:10 245.13 01-JUN-05:10 0.00 0.00 0.00 0.00 58.43 18-JUN-12:50 2.13 05-JUN-22:00
July 486.05 03-JUL-06:10 303.75 03-JUL-06:10 245.13 03-JUL-05:10 0.00 0.00 0.00 0.00 69.52 30-JUL-16:00 4.67 04-JUL-02:51
August 486.05 01-AUG-06:10 303.75 01-AUG-06:10 245.13 01-AUG-05:10 0.00 0.00 0.00 0.00 59.36 13-AUG-12:30 5.81 14-AUG-03:20
September 486.05 01-SEP-06:10 303.75 01-SEP-06:10 245.13 01-SEP-05:10 0.00 0.00 0.00 0.00 60.64 17-SEP-13:50 3.45 26-SEP-04:00
October 486.05 02-OCT-06:10 303.75 02-OCT-06:10 245.13 02-OCT-05:10 0.00 0.00 0.00 0.00 51.86 29-OCT-14:10 6.67 16-OCT-03:20
November 486.05 01-NOV-06:10 303.75 01-NOV-06:10 245.13 01-NOV-05:10 0.00 0.00 0.00 0.00 38.64 23-NOV-12:00 67.80 11-NOV-09:00
December 486.05 01-DEC-07:10 303.75 01-DEC-07:10 245.13 01-DEC-06:10 0.00 0.00 0.00 0.00 50.58 10-DEC-14:40 65.09 15-DEC-05:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 486.05   303.75   245.13   0.00 0.00 0.00 0.00 33.97   2.13  
Maximum of Months 486.05   303.75   245.13   0.00 0.00 0.00 0.00 73.62   70.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1710.89 02-JAN-07:10 1069.20 02-JAN-07:10 862.87 02-JAN-06:10 0.00 0.00 0.00 0.00 66.62 15-JAN-15:00 75.95 24-JAN-05:51
February 1710.89 01-FEB-07:10 1069.20 01-FEB-07:10 862.87 01-FEB-06:10 0.00 0.00 0.00 0.00 57.34 20-FEB-15:20 124.63 04-FEB-05:20
March 1710.89 01-MAR-07:10 1069.20 01-MAR-07:10 862.87 01-MAR-06:10 0.00 0.00 0.00 0.00 68.33 05-MAR-14:10 121.72 16-MAR-02:00
April 1710.89 03-APR-06:10 1069.20 03-APR-06:10 862.87 03-APR-05:10 0.00 0.00 0.00 0.00 78.76 23-APR-11:50 40.04 18-APR-23:52
May 1710.89 01-MAY-06:10 1069.20 01-MAY-06:10 862.87 01-MAY-05:10 0.00 0.00 0.00 0.00 134.20 29-MAY-17:00 16.32 25-MAY-04:40
June 1710.89 01-JUN-06:10 1069.20 01-JUN-06:10 862.87 01-JUN-05:10 0.00 0.00 0.00 0.00 105.99 18-JUN-14:50 2.75 06-JUN-02:53
July 1710.89 03-JUL-06:10 1069.20 03-JUL-06:10 862.87 03-JUL-05:10 0.00 0.00 0.00 0.00 127.01 30-JUL-15:51 5.48 04-JUL-03:00
August 1710.89 01-AUG-06:10 1069.20 01-AUG-06:10 862.87 01-AUG-05:10 0.00 0.00 0.00 0.00 108.05 13-AUG-12:30 6.62 14-AUG-03:50
September 1710.89 01-SEP-06:10 1069.20 01-SEP-06:10 862.87 01-SEP-05:10 0.00 0.00 0.00 0.00 109.44 17-SEP-13:50 5.79 26-SEP-04:00
October 1710.89 02-OCT-06:10 1069.20 02-OCT-06:10 862.87 02-OCT-05:10 0.00 0.00 0.00 0.00 93.53 29-OCT-14:10 10.87 28-OCT-02:32
November 1710.89 01-NOV-06:10 1069.20 01-NOV-06:10 862.87 01-NOV-05:10 0.00 0.00 0.00 0.00 67.11 23-NOV-12:00 121.71 11-NOV-09:00
December 1710.89 01-DEC-07:10 1069.20 01-DEC-07:10 862.87 01-DEC-06:10 0.00 0.00 0.00 0.00 89.62 10-DEC-14:40 114.30 15-DEC-05:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1710.89   1069.20   862.87   0.00 0.00 0.00 0.00 57.34   2.75  
Maximum of Months 1710.89   1069.20   862.87   0.00 0.00 0.00 0.00 134.20   124.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 583.26 02-JAN-07:10 364.50 02-JAN-07:10 294.16 02-JAN-06:10 0.00 0.00 0.00 0.00 46.13 15-JAN-15:00 53.11 24-JAN-03:00
February 583.26 01-FEB-07:10 364.50 01-FEB-07:10 294.16 01-FEB-06:10 0.00 0.00 0.00 0.00 39.68 20-FEB-15:20 87.62 04-FEB-05:20
March 583.26 01-MAR-07:10 364.50 01-MAR-07:10 294.16 01-MAR-06:10 0.00 0.00 0.00 0.00 46.16 05-MAR-16:10 86.25 16-MAR-02:00
April 583.26 03-APR-06:10 364.50 03-APR-06:10 294.16 03-APR-05:10 0.00 0.00 0.00 0.00 53.24 23-APR-11:50 27.99 18-APR-23:52
May 583.26 01-MAY-06:10 364.50 01-MAY-06:10 294.16 01-MAY-05:10 0.00 0.00 0.00 0.00 88.14 29-MAY-17:00 13.62 25-MAY-04:40
June 583.26 01-JUN-06:10 364.50 01-JUN-06:10 294.16 01-JUN-05:10 0.00 0.00 0.00 0.00 69.71 18-JUN-12:50 2.81 05-JUN-22:00
July 583.26 03-JUL-06:10 364.50 03-JUL-06:10 294.16 03-JUL-05:10 0.00 0.00 0.00 0.00 84.27 30-JUL-16:00 6.27 04-JUL-02:51
August 583.26 01-AUG-06:10 364.50 01-AUG-06:10 294.16 01-AUG-05:10 0.00 0.00 0.00 0.00 70.98 13-AUG-12:30 7.81 14-AUG-03:20
September 583.26 01-SEP-06:10 364.50 01-SEP-06:10 294.16 01-SEP-05:10 0.00 0.00 0.00 0.00 72.92 17-SEP-13:50 4.76 26-SEP-04:00
October 583.26 02-OCT-06:10 364.50 02-OCT-06:10 294.16 02-OCT-05:10 0.00 0.00 0.00 0.00 61.92 29-OCT-14:10 8.86 16-OCT-03:20
November 583.26 01-NOV-06:10 364.50 01-NOV-06:10 294.16 01-NOV-05:10 0.00 0.00 0.00 0.00 46.50 23-NOV-12:00 84.85 11-NOV-09:00
December 583.26 01-DEC-07:10 364.50 01-DEC-07:10 294.16 01-DEC-06:10 0.00 0.00 0.00 0.00 61.07 10-DEC-14:40 80.82 15-DEC-05:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 583.26   364.50   294.16   0.00 0.00 0.00 0.00 39.68   2.81  
Maximum of Months 583.26   364.50   294.16   0.00 0.00 0.00 0.00 88.14   87.62  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 855.44 02-JAN-07:10 534.60 02-JAN-07:10 431.43 02-JAN-06:10 0.00 0.00 0.00 0.00 33.58 15-JAN-15:00 38.74 24-JAN-03:00
February 855.44 01-FEB-07:10 534.60 01-FEB-07:10 431.43 01-FEB-06:10 0.00 0.00 0.00 0.00 28.63 20-FEB-15:20 63.09 04-FEB-05:20
March 855.44 01-MAR-07:10 534.60 01-MAR-07:10 431.43 01-MAR-06:10 0.00 0.00 0.00 0.00 33.89 05-MAR-14:10 62.03 16-MAR-02:00
April 855.44 03-APR-06:10 534.60 03-APR-06:10 431.43 03-APR-05:10 0.00 0.00 0.00 0.00 39.16 23-APR-11:50 20.28 18-APR-23:52
May 855.44 01-MAY-06:10 534.60 01-MAY-06:10 431.43 01-MAY-05:10 0.00 0.00 0.00 0.00 65.11 29-MAY-17:00 8.70 25-MAY-04:40
June 855.44 01-JUN-06:10 534.60 01-JUN-06:10 431.43 01-JUN-05:10 0.00 0.00 0.00 0.00 51.93 18-JUN-12:50 1.52 06-JUN-02:53
July 855.44 03-JUL-06:10 534.60 03-JUL-06:10 431.43 03-JUL-05:10 0.00 0.00 0.00 0.00 61.72 30-JUL-16:00 3.16 04-JUL-03:00
August 855.44 01-AUG-06:10 534.60 01-AUG-06:10 431.43 01-AUG-05:10 0.00 0.00 0.00 0.00 52.37 13-AUG-13:10 4.25 14-AUG-03:40
September 855.44 01-SEP-06:10 534.60 01-SEP-06:10 431.43 01-SEP-05:10 0.00 0.00 0.00 0.00 53.51 17-SEP-13:50 3.17 26-SEP-04:00
October 855.44 02-OCT-06:10 534.60 02-OCT-06:10 431.43 02-OCT-05:10 0.00 0.00 0.00 0.00 45.49 29-OCT-14:10 6.04 16-OCT-03:20
November 855.44 01-NOV-06:10 534.60 01-NOV-06:10 431.43 01-NOV-05:10 0.00 0.00 0.00 0.00 34.15 23-NOV-12:00 61.81 11-NOV-09:00
December 855.44 01-DEC-07:10 534.60 01-DEC-07:10 431.43 01-DEC-06:10 0.00 0.00 0.00 0.00 43.84 10-DEC-14:40 58.12 15-DEC-05:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 855.44   534.60   431.43   0.00 0.00 0.00 0.00 28.63   1.52  
Maximum of Months 855.44   534.60   431.43   0.00 0.00 0.00 0.00 65.11   63.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 97.20 02-JAN-07:10 155.08 02-JAN-07:10 71.39 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 97.20 01-FEB-07:10 155.08 01-FEB-07:10 71.39 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 97.20 01-MAR-07:10 155.08 01-MAR-07:10 71.39 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 97.20 03-APR-06:10 155.08 03-APR-06:10 71.39 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 97.20 01-MAY-06:10 155.08 01-MAY-06:10 71.39 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 97.20 01-JUN-06:10 155.08 01-JUN-06:10 71.39 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 97.20 03-JUL-06:10 155.08 03-JUL-06:10 71.39 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 97.20 01-AUG-06:10 155.08 01-AUG-06:10 71.39 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 97.20 01-SEP-06:10 155.08 01-SEP-06:10 71.39 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 97.20 02-OCT-06:10 155.08 02-OCT-06:10 71.39 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 97.20 01-NOV-06:10 155.08 01-NOV-06:10 71.39 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 97.20 01-DEC-07:10 155.08 01-DEC-07:10 71.39 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 97.20   155.08   71.39   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 97.20   155.08   71.39   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 97.20 02-JAN-07:10 155.08 02-JAN-07:10 71.39 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 97.20 01-FEB-07:10 155.08 01-FEB-07:10 71.39 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 97.20 01-MAR-07:10 155.08 01-MAR-07:10 71.39 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 97.20 03-APR-06:10 155.08 03-APR-06:10 71.39 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 97.20 01-MAY-06:10 155.08 01-MAY-06:10 71.39 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 97.20 01-JUN-06:10 155.08 01-JUN-06:10 71.39 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 97.20 03-JUL-06:10 155.08 03-JUL-06:10 71.39 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 97.20 01-AUG-06:10 155.08 01-AUG-06:10 71.39 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 97.20 01-SEP-06:10 155.08 01-SEP-06:10 71.39 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 97.20 02-OCT-06:10 155.08 02-OCT-06:10 71.39 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 97.20 01-NOV-06:10 155.08 01-NOV-06:10 71.39 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 97.20 01-DEC-07:10 155.08 01-DEC-07:10 71.39 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 97.20   155.08   71.39   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 97.20   155.08   71.39   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 97.20 02-JAN-07:10 155.08 02-JAN-07:10 71.39 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 97.20 01-FEB-07:10 155.08 01-FEB-07:10 71.39 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 97.20 01-MAR-07:10 155.08 01-MAR-07:10 71.39 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 97.20 03-APR-06:10 155.08 03-APR-06:10 71.39 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 97.20 01-MAY-06:10 155.08 01-MAY-06:10 71.39 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 97.20 01-JUN-06:10 155.08 01-JUN-06:10 71.39 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 97.20 03-JUL-06:10 155.08 03-JUL-06:10 71.39 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 97.20 01-AUG-06:10 155.08 01-AUG-06:10 71.39 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 97.20 01-SEP-06:10 155.08 01-SEP-06:10 71.39 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 97.20 02-OCT-06:10 155.08 02-OCT-06:10 71.39 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 97.20 01-NOV-06:10 155.08 01-NOV-06:10 71.39 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 97.20 01-DEC-07:10 155.08 01-DEC-07:10 71.39 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 97.20   155.08   71.39   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 97.20   155.08   71.39   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 106.92 02-JAN-07:10 170.59 02-JAN-07:10 78.53 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 106.92 01-FEB-07:10 170.59 01-FEB-07:10 78.53 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 106.92 01-MAR-07:10 170.59 01-MAR-07:10 78.53 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 106.92 03-APR-06:10 170.59 03-APR-06:10 78.53 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 106.92 01-MAY-06:10 170.59 01-MAY-06:10 78.53 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 106.92 01-JUN-06:10 170.59 01-JUN-06:10 78.53 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 106.92 03-JUL-06:10 170.59 03-JUL-06:10 78.53 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 106.92 01-AUG-06:10 170.59 01-AUG-06:10 78.53 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 106.92 01-SEP-06:10 170.59 01-SEP-06:10 78.53 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 106.92 02-OCT-06:10 170.59 02-OCT-06:10 78.53 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 106.92 01-NOV-06:10 170.59 01-NOV-06:10 78.53 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 106.92 01-DEC-07:10 170.59 01-DEC-07:10 78.53 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 106.92   170.59   78.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 106.92   170.59   78.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 106.92 02-JAN-07:10 170.59 02-JAN-07:10 78.53 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 106.92 01-FEB-07:10 170.59 01-FEB-07:10 78.53 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 106.92 01-MAR-07:10 170.59 01-MAR-07:10 78.53 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 106.92 03-APR-06:10 170.59 03-APR-06:10 78.53 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 106.92 01-MAY-06:10 170.59 01-MAY-06:10 78.53 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 106.92 01-JUN-06:10 170.59 01-JUN-06:10 78.53 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 106.92 03-JUL-06:10 170.59 03-JUL-06:10 78.53 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 106.92 01-AUG-06:10 170.59 01-AUG-06:10 78.53 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 106.92 01-SEP-06:10 170.59 01-SEP-06:10 78.53 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 106.92 02-OCT-06:10 170.59 02-OCT-06:10 78.53 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 106.92 01-NOV-06:10 170.59 01-NOV-06:10 78.53 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 106.92 01-DEC-07:10 170.59 01-DEC-07:10 78.53 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 106.92   170.59   78.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 106.92   170.59   78.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 106.92 02-JAN-07:10 170.59 02-JAN-07:10 78.53 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 106.92 01-FEB-07:10 170.59 01-FEB-07:10 78.53 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 106.92 01-MAR-07:10 170.59 01-MAR-07:10 78.53 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 106.92 03-APR-06:10 170.59 03-APR-06:10 78.53 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 106.92 01-MAY-06:10 170.59 01-MAY-06:10 78.53 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 106.92 01-JUN-06:10 170.59 01-JUN-06:10 78.53 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 106.92 03-JUL-06:10 170.59 03-JUL-06:10 78.53 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 106.92 01-AUG-06:10 170.59 01-AUG-06:10 78.53 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 106.92 01-SEP-06:10 170.59 01-SEP-06:10 78.53 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 106.92 02-OCT-06:10 170.59 02-OCT-06:10 78.53 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 106.92 01-NOV-06:10 170.59 01-NOV-06:10 78.53 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 106.92 01-DEC-07:10 170.59 01-DEC-07:10 78.53 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 106.92   170.59   78.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 106.92   170.59   78.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 13.61 02-JAN-07:10 51.03 02-JAN-07:10 6.26 02-JAN-06:10 0.00 0.00 0.00 0.00 23.13 15-JAN-14:00 44.41 24-JAN-03:00
February 13.61 01-FEB-07:10 51.03 01-FEB-07:10 6.26 01-FEB-06:10 0.00 0.00 0.00 0.00 19.51 20-FEB-14:51 72.68 04-FEB-05:20
March 13.61 01-MAR-07:10 51.03 01-MAR-07:10 6.26 01-MAR-06:10 0.00 0.00 0.00 0.00 22.88 05-MAR-14:10 74.98 16-MAR-02:00
April 13.61 03-APR-06:10 51.03 03-APR-06:10 6.26 03-APR-05:10 0.00 0.00 0.00 0.00 31.02 16-APR-12:51 25.35 18-APR-23:52
May 13.61 01-MAY-06:10 51.03 01-MAY-06:10 6.26 01-MAY-05:10 0.00 0.00 0.00 0.00 52.53 29-MAY-16:15 9.74 07-MAY-01:52
June 13.61 01-JUN-06:10 51.03 01-JUN-06:10 6.26 01-JUN-05:10 0.00 0.00 0.00 0.00 36.74 25-JUN-14:00 7.44 18-JUN-19:51
July 13.61 03-JUL-06:10 51.03 03-JUL-06:10 6.26 03-JUL-05:10 0.00 0.00 0.00 0.00 43.48 30-JUL-16:00 8.06 04-JUL-02:51
August 13.61 01-AUG-06:10 51.03 01-AUG-06:10 6.26 01-AUG-05:10 0.00 0.00 0.00 0.00 42.07 13-AUG-12:50 12.80 14-AUG-02:53
September 13.61 01-SEP-06:10 51.03 01-SEP-06:10 6.26 01-SEP-05:10 0.00 0.00 0.00 0.00 41.07 17-SEP-13:50 5.24 02-SEP-22:00
October 13.61 02-OCT-06:10 51.03 02-OCT-06:10 6.26 02-OCT-05:10 0.00 0.00 0.00 0.00 32.96 29-OCT-14:10 9.97 16-OCT-02:53
November 13.61 01-NOV-06:10 51.03 01-NOV-06:10 6.26 01-NOV-05:10 0.00 0.00 0.00 0.00 22.21 23-NOV-12:00 64.96 11-NOV-08:53
December 13.61 01-DEC-07:10 51.03 01-DEC-07:10 6.26 01-DEC-06:10 0.00 0.00 0.00 0.00 31.24 10-DEC-14:40 68.28 15-DEC-03:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 13.61   51.03   6.26   0.00 0.00 0.00 0.00 19.51   5.24  
Maximum of Months 13.61   51.03   6.26   0.00 0.00 0.00 0.00 52.53   74.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 129.61 02-JAN-07:10 57.60 02-JAN-07:10 237.70 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 129.61 01-FEB-07:10 57.60 01-FEB-07:10 237.70 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 129.61 01-MAR-07:10 57.60 01-MAR-07:10 237.70 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 129.61 03-APR-06:10 57.60 03-APR-06:10 237.70 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 129.61 01-MAY-06:10 57.60 01-MAY-06:10 237.70 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 129.61 01-JUN-06:10 57.60 01-JUN-06:10 237.70 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 129.61 03-JUL-06:10 57.60 03-JUL-06:10 237.70 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 129.61 01-AUG-06:10 57.60 01-AUG-06:10 237.70 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 129.61 01-SEP-06:10 57.60 01-SEP-06:10 237.70 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 129.61 02-OCT-06:10 57.60 02-OCT-06:10 237.70 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 129.61 01-NOV-06:10 57.60 01-NOV-06:10 237.70 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 129.61 01-DEC-07:10 57.60 01-DEC-07:10 237.70 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 129.61   57.60   237.70   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 129.61   57.60   237.70   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 243.00 02-JAN-07:10 135.00 02-JAN-07:10 297.17 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 243.00 01-FEB-07:10 135.00 01-FEB-07:10 297.17 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 243.00 01-MAR-07:10 135.00 01-MAR-07:10 297.17 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 243.00 03-APR-06:10 135.00 03-APR-06:10 297.17 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 243.00 01-MAY-06:10 135.00 01-MAY-06:10 297.17 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 243.00 01-JUN-06:10 135.00 01-JUN-06:10 297.17 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 243.00 03-JUL-06:10 135.00 03-JUL-06:10 297.17 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 243.00 01-AUG-06:10 135.00 01-AUG-06:10 297.17 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 243.00 01-SEP-06:10 135.00 01-SEP-06:10 297.17 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 243.00 02-OCT-06:10 135.00 02-OCT-06:10 297.17 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 243.00 01-NOV-06:10 135.00 01-NOV-06:10 297.17 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 243.00 01-DEC-07:10 135.00 01-DEC-07:10 297.17 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 243.00   135.00   297.17   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 243.00   135.00   297.17   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 291.60 02-JAN-07:10 162.00 02-JAN-07:10 356.60 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 291.60 01-FEB-07:10 162.00 01-FEB-07:10 356.60 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 291.60 01-MAR-07:10 162.00 01-MAR-07:10 356.60 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 291.60 03-APR-06:10 162.00 03-APR-06:10 356.60 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 291.60 01-MAY-06:10 162.00 01-MAY-06:10 356.60 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 291.60 01-JUN-06:10 162.00 01-JUN-06:10 356.60 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 291.60 03-JUL-06:10 162.00 03-JUL-06:10 356.60 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 291.60 01-AUG-06:10 162.00 01-AUG-06:10 356.60 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 291.60 01-SEP-06:10 162.00 01-SEP-06:10 356.60 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 291.60 02-OCT-06:10 162.00 02-OCT-06:10 356.60 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 291.60 01-NOV-06:10 162.00 01-NOV-06:10 356.60 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 291.60 01-DEC-07:10 162.00 01-DEC-07:10 356.60 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 291.60   162.00   356.60   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 291.60   162.00   356.60   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 302.43 02-JAN-07:10 554.40 02-JAN-07:10 610.11 02-JAN-06:10 0.00 0.00 0.00 0.00 54.98 15-JAN-15:00 111.32 24-JAN-03:00
February 302.43 01-FEB-07:10 554.40 01-FEB-07:10 610.11 01-FEB-06:10 0.00 0.00 0.00 0.00 52.86 20-FEB-15:20 187.54 04-FEB-05:20
March 302.43 01-MAR-07:10 554.40 01-MAR-07:10 610.11 01-MAR-06:10 0.00 0.00 0.00 0.00 63.15 05-MAR-14:10 189.40 16-MAR-02:00
April 302.43 03-APR-06:10 554.40 03-APR-06:10 610.11 03-APR-05:10 0.00 0.00 0.00 0.00 76.13 16-APR-18:00 61.88 18-APR-23:52
May 302.43 01-MAY-06:10 554.40 01-MAY-06:10 610.11 01-MAY-05:10 0.00 0.00 0.00 0.00 142.35 29-MAY-16:20 28.91 25-MAY-04:40
June 302.43 01-JUN-06:10 554.40 01-JUN-06:10 610.11 01-JUN-05:10 0.00 0.00 0.00 0.00 101.91 18-JUN-15:00 11.83 18-JUN-20:00
July 302.43 03-JUL-06:10 554.40 03-JUL-06:10 610.11 03-JUL-05:10 0.00 0.00 0.00 0.00 118.09 30-JUL-16:00 18.82 04-JUL-02:51
August 302.43 01-AUG-06:10 554.40 01-AUG-06:10 610.11 01-AUG-05:10 0.00 0.00 0.00 0.00 108.85 13-AUG-12:50 25.58 14-AUG-03:20
September 302.43 01-SEP-06:10 554.40 01-SEP-06:10 610.11 01-SEP-05:10 0.00 0.00 0.00 0.00 110.01 17-SEP-16:30 10.72 26-SEP-04:00
October 302.43 02-OCT-06:10 554.40 02-OCT-06:10 610.11 02-OCT-05:10 0.00 0.00 0.00 0.00 88.50 29-OCT-14:10 22.08 16-OCT-03:20
November 302.43 01-NOV-06:10 554.40 01-NOV-06:10 610.11 01-NOV-05:10 0.00 0.00 0.00 0.00 58.31 22-NOV-20:10 202.70 11-NOV-09:00
December 302.43 01-DEC-07:10 554.40 01-DEC-07:10 610.11 01-DEC-06:10 0.00 0.00 0.00 0.00 88.71 10-DEC-15:00 175.01 15-DEC-05:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 302.43   554.40   610.11   0.00 0.00 0.00 0.00 52.86   10.72  
Maximum of Months 302.43   554.40   610.11   0.00 0.00 0.00 0.00 142.35   202.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 239.76 02-JAN-07:10 382.53 02-JAN-07:10 176.09 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 239.76 01-FEB-07:10 382.53 01-FEB-07:10 176.09 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 239.76 01-MAR-07:10 382.53 01-MAR-07:10 176.09 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 239.76 03-APR-06:10 382.53 03-APR-06:10 176.09 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 239.76 01-MAY-06:10 382.53 01-MAY-06:10 176.09 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 239.76 01-JUN-06:10 382.53 01-JUN-06:10 176.09 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 239.76 03-JUL-06:10 382.53 03-JUL-06:10 176.09 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 239.76 01-AUG-06:10 382.53 01-AUG-06:10 176.09 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 239.76 01-SEP-06:10 382.53 01-SEP-06:10 176.09 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 239.76 02-OCT-06:10 382.53 02-OCT-06:10 176.09 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 239.76 01-NOV-06:10 382.53 01-NOV-06:10 176.09 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 239.76 01-DEC-07:10 382.53 01-DEC-07:10 176.09 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 239.76   382.53   176.09   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 239.76   382.53   176.09   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 3188.47 02-JAN-07:10 1151.28 02-JAN-07:10 1072.05 02-JAN-06:10 0.00 0.00 0.00 0.00 49.23 29-JAN-12:50 158.88 24-JAN-03:00
February 3188.47 01-FEB-07:10 1151.28 01-FEB-07:10 1072.05 01-FEB-06:10 0.00 0.00 0.00 0.00 34.27 19-FEB-15:55 252.15 04-FEB-05:20
March 3188.47 01-MAR-07:10 1151.28 01-MAR-07:10 1072.05 01-MAR-06:10 0.00 0.00 0.00 0.00 73.02 05-MAR-14:10 255.46 16-MAR-02:00
April 3188.47 03-APR-06:10 1151.28 03-APR-06:10 1072.05 03-APR-05:10 0.00 0.00 0.00 0.00 93.12 16-APR-13:00 85.32 18-APR-23:52
May 3188.47 01-MAY-06:10 1151.28 01-MAY-06:10 1072.05 01-MAY-05:10 0.00 0.00 0.00 0.00 169.87 29-MAY-16:17 47.57 25-MAY-04:40
June 3188.47 01-JUN-06:10 1151.28 01-JUN-06:10 1072.05 01-JUN-05:10 0.00 0.00 0.00 0.00 120.26 17-JUN-18:50 26.92 18-JUN-20:00
July 3188.47 03-JUL-06:10 1151.28 03-JUL-06:10 1072.05 03-JUL-05:10 0.00 0.00 0.00 0.00 152.46 30-JUL-16:00 29.70 04-JUL-02:51
August 3188.47 01-AUG-06:10 1151.28 01-AUG-06:10 1072.05 01-AUG-05:10 0.00 0.00 0.00 0.00 139.52 13-AUG-12:50 41.41 14-AUG-03:20
September 3188.47 01-SEP-06:10 1151.28 01-SEP-06:10 1072.05 01-SEP-05:10 0.00 0.00 0.00 0.00 126.63 17-SEP-13:47 19.28 26-SEP-04:00
October 3188.47 02-OCT-06:10 1151.28 02-OCT-06:10 1072.05 02-OCT-05:10 0.00 0.00 0.00 0.00 99.03 29-OCT-14:06 40.86 16-OCT-05:00
November 3188.47 01-NOV-06:10 1151.28 01-NOV-06:10 1072.05 01-NOV-05:10 0.00 0.00 0.00 0.00 61.79 22-NOV-21:20 256.00 11-NOV-09:00
December 3188.47 01-DEC-07:10 1151.28 01-DEC-07:10 1072.05 01-DEC-06:10 0.00 0.00 0.00 0.00 81.43 10-DEC-13:54 237.50 15-DEC-05:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 3188.47   1151.28   1072.05   0.00 0.00 0.00 0.00 34.27   19.28  
Maximum of Months 3188.47   1151.28   1072.05   0.00 0.00 0.00 0.00 169.87   256.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 304.56 02-JAN-07:10 485.92 02-JAN-07:10 223.68 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 304.56 01-FEB-07:10 485.92 01-FEB-07:10 223.68 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 304.56 01-MAR-07:10 485.92 01-MAR-07:10 223.68 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 304.56 03-APR-06:10 485.92 03-APR-06:10 223.68 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 304.56 01-MAY-06:10 485.92 01-MAY-06:10 223.68 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 304.56 01-JUN-06:10 485.92 01-JUN-06:10 223.68 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 304.56 03-JUL-06:10 485.92 03-JUL-06:10 223.68 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 304.56 01-AUG-06:10 485.92 01-AUG-06:10 223.68 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 304.56 01-SEP-06:10 485.92 01-SEP-06:10 223.68 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 304.56 02-OCT-06:10 485.92 02-OCT-06:10 223.68 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 304.56 01-NOV-06:10 485.92 01-NOV-06:10 223.68 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 304.56 01-DEC-07:10 485.92 01-DEC-07:10 223.68 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 304.56   485.92   223.68   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 304.56   485.92   223.68   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 68.04 02-JAN-07:10 102.06 02-JAN-07:10 49.97 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 68.04 01-FEB-07:10 102.06 01-FEB-07:10 49.97 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 68.04 01-MAR-07:10 102.06 01-MAR-07:10 49.97 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 68.04 03-APR-06:10 102.06 03-APR-06:10 49.97 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 68.04 01-MAY-06:10 102.06 01-MAY-06:10 49.97 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 68.04 01-JUN-06:10 102.06 01-JUN-06:10 49.97 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 68.04 03-JUL-06:10 102.06 03-JUL-06:10 49.97 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 68.04 01-AUG-06:10 102.06 01-AUG-06:10 49.97 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 68.04 01-SEP-06:10 102.06 01-SEP-06:10 49.97 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 68.04 02-OCT-06:10 102.06 02-OCT-06:10 49.97 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 68.04 01-NOV-06:10 102.06 01-NOV-06:10 49.97 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 68.04 01-DEC-07:10 102.06 01-DEC-07:10 49.97 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 68.04   102.06   49.97   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 68.04   102.06   49.97   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 174.98 02-JAN-07:10 320.76 02-JAN-07:10 352.99 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 174.98 01-FEB-07:10 320.76 01-FEB-07:10 352.99 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 174.98 01-MAR-07:10 320.76 01-MAR-07:10 352.99 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 174.98 03-APR-06:10 320.76 03-APR-06:10 352.99 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 174.98 01-MAY-06:10 320.76 01-MAY-06:10 352.99 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 174.98 01-JUN-06:10 320.76 01-JUN-06:10 352.99 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 174.98 03-JUL-06:10 320.76 03-JUL-06:10 352.99 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 174.98 01-AUG-06:10 320.76 01-AUG-06:10 352.99 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 174.98 01-SEP-06:10 320.76 01-SEP-06:10 352.99 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 174.98 02-OCT-06:10 320.76 02-OCT-06:10 352.99 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 174.98 01-NOV-06:10 320.76 01-NOV-06:10 352.99 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 174.98 01-DEC-07:10 320.76 01-DEC-07:10 352.99 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 174.98   320.76   352.99   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 174.98   320.76   352.99   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 184.70 02-JAN-07:10 338.58 02-JAN-07:10 372.60 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 184.70 01-FEB-07:10 338.58 01-FEB-07:10 372.60 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 184.70 01-MAR-07:10 338.58 01-MAR-07:10 372.60 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 184.70 03-APR-06:10 338.58 03-APR-06:10 372.60 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 184.70 01-MAY-06:10 338.58 01-MAY-06:10 372.60 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 184.70 01-JUN-06:10 338.58 01-JUN-06:10 372.60 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 184.70 03-JUL-06:10 338.58 03-JUL-06:10 372.60 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 184.70 01-AUG-06:10 338.58 01-AUG-06:10 372.60 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 184.70 01-SEP-06:10 338.58 01-SEP-06:10 372.60 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 184.70 02-OCT-06:10 338.58 02-OCT-06:10 372.60 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 184.70 01-NOV-06:10 338.58 01-NOV-06:10 372.60 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 184.70 01-DEC-07:10 338.58 01-DEC-07:10 372.60 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 184.70   338.58   372.60   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 184.70   338.58   372.60   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 12.10 02-JAN-07:10 45.36 02-JAN-07:10 5.57 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 12.10 01-FEB-07:10 45.36 01-FEB-07:10 5.57 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 12.10 01-MAR-07:10 45.36 01-MAR-07:10 5.57 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 12.10 03-APR-06:10 45.36 03-APR-06:10 5.57 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 12.10 01-MAY-06:10 45.36 01-MAY-06:10 5.57 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 12.10 01-JUN-06:10 45.36 01-JUN-06:10 5.57 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 12.10 03-JUL-06:10 45.36 03-JUL-06:10 5.57 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 12.10 01-AUG-06:10 45.36 01-AUG-06:10 5.57 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 12.10 01-SEP-06:10 45.36 01-SEP-06:10 5.57 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 12.10 02-OCT-06:10 45.36 02-OCT-06:10 5.57 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 12.10 01-NOV-06:10 45.36 01-NOV-06:10 5.57 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 12.10 01-DEC-07:10 45.36 01-DEC-07:10 5.57 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 12.10   45.36   5.57   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12.10   45.36   5.57   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 25.92 02-JAN-07:10 97.20 02-JAN-07:10 11.93 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 25.92 01-FEB-07:10 97.20 01-FEB-07:10 11.93 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 25.92 01-MAR-07:10 97.20 01-MAR-07:10 11.93 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 25.92 03-APR-06:10 97.20 03-APR-06:10 11.93 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 25.92 01-MAY-06:10 97.20 01-MAY-06:10 11.93 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 25.92 01-JUN-06:10 97.20 01-JUN-06:10 11.93 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 25.92 03-JUL-06:10 97.20 03-JUL-06:10 11.93 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 25.92 01-AUG-06:10 97.20 01-AUG-06:10 11.93 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 25.92 01-SEP-06:10 97.20 01-SEP-06:10 11.93 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 25.92 02-OCT-06:10 97.20 02-OCT-06:10 11.93 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 25.92 01-NOV-06:10 97.20 01-NOV-06:10 11.93 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 25.92 01-DEC-07:10 97.20 01-DEC-07:10 11.93 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 25.92   97.20   11.93   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25.92   97.20   11.93   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 31.10 02-JAN-07:10 116.64 02-JAN-07:10 14.31 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 31.10 01-FEB-07:10 116.64 01-FEB-07:10 14.31 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 31.10 01-MAR-07:10 116.64 01-MAR-07:10 14.31 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 31.10 03-APR-06:10 116.64 03-APR-06:10 14.31 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 31.10 01-MAY-06:10 116.64 01-MAY-06:10 14.31 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 31.10 01-JUN-06:10 116.64 01-JUN-06:10 14.31 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 31.10 03-JUL-06:10 116.64 03-JUL-06:10 14.31 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 31.10 01-AUG-06:10 116.64 01-AUG-06:10 14.31 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 31.10 01-SEP-06:10 116.64 01-SEP-06:10 14.31 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 31.10 02-OCT-06:10 116.64 02-OCT-06:10 14.31 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 31.10 01-NOV-06:10 116.64 01-NOV-06:10 14.31 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 31.10 01-DEC-07:10 116.64 01-DEC-07:10 14.31 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 31.10   116.64   14.31   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31.10   116.64   14.31   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 27.22 02-JAN-07:10 102.06 02-JAN-07:10 12.52 02-JAN-06:10 0.00 0.00 0.00 0.00 14.41 15-JAN-15:00 23.89 24-JAN-03:00
February 27.22 01-FEB-07:10 102.06 01-FEB-07:10 12.52 01-FEB-06:10 0.00 0.00 0.00 0.00 13.45 20-FEB-15:20 41.31 04-FEB-05:20
March 27.22 01-MAR-07:10 102.06 01-MAR-07:10 12.52 01-MAR-06:10 0.00 0.00 0.00 0.00 15.64 05-MAR-16:10 41.92 16-MAR-02:00
April 27.22 03-APR-06:10 102.06 03-APR-06:10 12.52 03-APR-05:10 0.00 0.00 0.00 0.00 17.60 16-APR-18:00 13.19 18-APR-23:52
May 27.22 01-MAY-06:10 102.06 01-MAY-06:10 12.52 01-MAY-05:10 0.00 0.00 0.00 0.00 32.86 29-MAY-16:20 4.43 07-MAY-06:00
June 27.22 01-JUN-06:10 102.06 01-JUN-06:10 12.52 01-JUN-05:10 0.00 0.00 0.00 0.00 24.47 18-JUN-14:50 1.38 05-JUN-22:00
July 27.22 03-JUL-06:10 102.06 03-JUL-06:10 12.52 03-JUL-05:10 0.00 0.00 0.00 0.00 27.76 30-JUL-16:00 3.22 02-JUL-16:10
August 27.22 01-AUG-06:10 102.06 01-AUG-06:10 12.52 01-AUG-05:10 0.00 0.00 0.00 0.00 25.26 13-AUG-12:50 3.78 14-AUG-03:00
September 27.22 01-SEP-06:10 102.06 01-SEP-06:10 12.52 01-SEP-05:10 0.00 0.00 0.00 0.00 25.69 17-SEP-16:30 1.28 26-SEP-04:00
October 27.22 02-OCT-06:10 102.06 02-OCT-06:10 12.52 02-OCT-05:10 0.00 0.00 0.00 0.00 21.67 29-OCT-14:10 3.57 16-OCT-02:53
November 27.22 01-NOV-06:10 102.06 01-NOV-06:10 12.52 01-NOV-05:10 0.00 0.00 0.00 0.00 14.83 19-NOV-14:30 43.07 11-NOV-09:00
December 27.22 01-DEC-07:10 102.06 01-DEC-07:10 12.52 01-DEC-06:10 0.00 0.00 0.00 0.00 21.72 10-DEC-14:40 38.31 15-DEC-03:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 27.22   102.06   12.52   0.00 0.00 0.00 0.00 13.45   1.28  
Maximum of Months 27.22   102.06   12.52   0.00 0.00 0.00 0.00 32.86   43.07  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 912.69 02-JAN-07:10 1673.10 02-JAN-07:10 1520.91 02-JAN-06:10 0.00 0.00 0.00 0.00 33.04 15-JAN-14:00 89.44 24-JAN-03:00
February 912.69 01-FEB-07:10 1673.10 01-FEB-07:10 1520.91 01-FEB-06:10 0.00 0.00 0.00 0.00 30.78 20-FEB-15:20 148.27 04-FEB-05:20
March 912.69 01-MAR-07:10 1673.10 01-MAR-07:10 1520.91 01-MAR-06:10 0.00 0.00 0.00 0.00 40.70 05-MAR-14:10 145.79 16-MAR-02:00
April 912.69 03-APR-06:10 1673.10 03-APR-06:10 1520.91 03-APR-05:10 0.00 0.00 0.00 0.00 53.20 16-APR-13:00 47.84 18-APR-23:52
May 912.69 01-MAY-06:10 1673.10 01-MAY-06:10 1520.91 01-MAY-05:10 0.00 0.00 0.00 0.00 97.21 29-MAY-16:20 25.80 25-MAY-04:40
June 912.69 01-JUN-06:10 1673.10 01-JUN-06:10 1520.91 01-JUN-05:10 0.00 0.00 0.00 0.00 68.02 25-JUN-14:00 12.24 18-JUN-20:00
July 912.69 03-JUL-06:10 1673.10 03-JUL-06:10 1520.91 03-JUL-05:10 0.00 0.00 0.00 0.00 86.51 30-JUL-16:00 14.24 04-JUL-02:51
August 912.69 01-AUG-06:10 1673.10 01-AUG-06:10 1520.91 01-AUG-05:10 0.00 0.00 0.00 0.00 76.87 13-AUG-12:51 21.05 14-AUG-03:20
September 912.69 01-SEP-06:10 1673.10 01-SEP-06:10 1520.91 01-SEP-05:10 0.00 0.00 0.00 0.00 76.24 17-SEP-13:50 9.89 26-SEP-04:00
October 912.69 02-OCT-06:10 1673.10 02-OCT-06:10 1520.91 02-OCT-05:10 0.00 0.00 0.00 0.00 61.81 29-OCT-14:10 20.56 16-OCT-05:00
November 912.69 01-NOV-06:10 1673.10 01-NOV-06:10 1520.91 01-NOV-05:10 0.00 0.00 0.00 0.00 36.31 23-NOV-12:00 141.60 11-NOV-09:00
December 912.69 01-DEC-07:10 1673.10 01-DEC-07:10 1520.91 01-DEC-06:10 0.00 0.00 0.00 0.00 56.46 10-DEC-15:00 137.12 15-DEC-05:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 912.69   1673.10   1520.91   0.00 0.00 0.00 0.00 30.78   9.89  
Maximum of Months 912.69   1673.10   1520.91   0.00 0.00 0.00 0.00 97.21   148.27  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 450.36 02-JAN-07:10 718.53 02-JAN-07:10 330.76 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 450.36 01-FEB-07:10 718.53 01-FEB-07:10 330.76 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 450.36 01-MAR-07:10 718.53 01-MAR-07:10 330.76 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 450.36 03-APR-06:10 718.53 03-APR-06:10 330.76 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 450.36 01-MAY-06:10 718.53 01-MAY-06:10 330.76 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 450.36 01-JUN-06:10 718.53 01-JUN-06:10 330.76 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 450.36 03-JUL-06:10 718.53 03-JUL-06:10 330.76 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 450.36 01-AUG-06:10 718.53 01-AUG-06:10 330.76 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 450.36 01-SEP-06:10 718.53 01-SEP-06:10 330.76 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 450.36 02-OCT-06:10 718.53 02-OCT-06:10 330.76 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 450.36 01-NOV-06:10 718.53 01-NOV-06:10 330.76 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 450.36 01-DEC-07:10 718.53 01-DEC-07:10 330.76 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 450.36   718.53   330.76   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 450.36   718.53   330.76   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 29.16 02-JAN-07:10 43.74 02-JAN-07:10 21.42 02-JAN-06:10 0.00 0.00 0.00 0.00 14.92 15-JAN-14:20 17.30 24-JAN-03:00
February 29.16 01-FEB-07:10 43.74 01-FEB-07:10 21.42 01-FEB-06:10 0.00 0.00 0.00 0.00 12.19 20-FEB-14:40 28.59 04-FEB-05:20
March 29.16 01-MAR-07:10 43.74 01-MAR-07:10 21.42 01-MAR-06:10 0.00 0.00 0.00 0.00 15.07 05-MAR-14:10 29.38 16-MAR-02:00
April 29.16 03-APR-06:10 43.74 03-APR-06:10 21.42 03-APR-05:10 0.00 0.00 0.00 0.00 17.55 23-APR-11:50 9.54 18-APR-23:52
May 29.16 01-MAY-06:10 43.74 01-MAY-06:10 21.42 01-MAY-05:10 0.00 0.00 0.00 0.00 26.97 29-MAY-16:18 3.11 07-MAY-04:52
June 29.16 01-JUN-06:10 43.74 01-JUN-06:10 21.42 01-JUN-05:10 0.00 0.00 0.00 0.00 23.40 18-JUN-12:50 0.75 18-JUN-20:00
July 29.16 03-JUL-06:10 43.74 03-JUL-06:10 21.42 03-JUL-05:10 0.00 0.00 0.00 0.00 25.03 30-JUL-16:00 1.66 04-JUL-02:51
August 29.16 01-AUG-06:10 43.74 01-AUG-06:10 21.42 01-AUG-05:10 0.00 0.00 0.00 0.00 23.46 13-AUG-12:30 2.92 14-AUG-03:00
September 29.16 01-SEP-06:10 43.74 01-SEP-06:10 21.42 01-SEP-05:10 0.00 0.00 0.00 0.00 23.30 17-SEP-13:50 0.95 04-SEP-23:52
October 29.16 02-OCT-06:10 43.74 02-OCT-06:10 21.42 02-OCT-05:10 0.00 0.00 0.00 0.00 19.56 29-OCT-14:10 3.19 16-OCT-03:10
November 29.16 01-NOV-06:10 43.74 01-NOV-06:10 21.42 01-NOV-05:10 0.00 0.00 0.00 0.00 15.10 23-NOV-12:00 25.95 11-NOV-08:53
December 29.16 01-DEC-07:10 43.74 01-DEC-07:10 21.42 01-DEC-06:10 0.00 0.00 0.00 0.00 18.76 10-DEC-14:40 26.59 15-DEC-03:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 29.16   43.74   21.42   0.00 0.00 0.00 0.00 12.19   0.75  
Maximum of Months 29.16   43.74   21.42   0.00 0.00 0.00 0.00 26.97   29.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 X-RAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1944.19 02-JAN-07:10 1215.00 02-JAN-07:10 8914.22 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 1944.19 01-FEB-07:10 1215.00 01-FEB-07:10 8914.22 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 1944.19 01-MAR-07:10 1215.00 01-MAR-07:10 8914.22 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 1944.19 03-APR-06:10 1215.00 03-APR-06:10 8914.22 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 1944.19 01-MAY-06:10 1215.00 01-MAY-06:10 8914.22 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 1944.19 01-JUN-06:10 1215.00 01-JUN-06:10 8914.22 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 1944.19 03-JUL-06:10 1215.00 03-JUL-06:10 8914.22 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 1944.19 01-AUG-06:10 1215.00 01-AUG-06:10 8914.22 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 1944.19 01-SEP-06:10 1215.00 01-SEP-06:10 8914.22 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 1944.19 02-OCT-06:10 1215.00 02-OCT-06:10 8914.22 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 1944.19 01-NOV-06:10 1215.00 01-NOV-06:10 8914.22 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 1944.19 01-DEC-07:10 1215.00 01-DEC-07:10 8914.22 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1944.19   1215.00   8914.22   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1944.19   1215.00   8914.22   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 22.68 02-JAN-07:10 41.58 02-JAN-07:10 45.76 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05
February 22.68 01-FEB-07:10 41.58 01-FEB-07:10 45.76 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 22.68 01-MAR-07:10 41.58 01-MAR-07:10 45.76 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 22.68 03-APR-06:10 41.58 03-APR-06:10 45.76 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 01-APR-00:03
May 22.68 01-MAY-06:10 41.58 01-MAY-06:10 45.76 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 01-MAY-00:02
June 22.68 01-JUN-06:10 41.58 01-JUN-06:10 45.76 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:01 0.00 01-JUN-00:01
July 22.68 03-JUL-06:10 41.58 03-JUL-06:10 45.76 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:01 0.00 01-JUL-00:01
August 22.68 01-AUG-06:10 41.58 01-AUG-06:10 45.76 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:01 0.00 01-AUG-00:01
September 22.68 01-SEP-06:10 41.58 01-SEP-06:10 45.76 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 01-SEP-00:03
October 22.68 02-OCT-06:10 41.58 02-OCT-06:10 45.76 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 01-OCT-00:03
November 22.68 01-NOV-06:10 41.58 01-NOV-06:10 45.76 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 0.00 01-NOV-00:03
December 22.68 01-DEC-07:10 41.58 01-DEC-07:10 45.76 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 22.68   41.58   45.76   0.00 0.00 0.00 0.00 0.00   0.00  
Maximum of Months 22.68   41.58   45.76   0.00 0.00 0.00 0.00 0.00   0.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 199.80 02-JAN-07:10 318.77 02-JAN-07:10 146.74 02-JAN-06:10 0.00 0.00 0.00 0.00 6.83 15-JAN-14:10 13.84 24-JAN-03:00
February 199.80 01-FEB-07:10 318.77 01-FEB-07:10 146.74 01-FEB-06:10 0.00 0.00 0.00 0.00 5.78 20-FEB-15:10 24.93 04-FEB-05:00
March 199.80 01-MAR-07:10 318.77 01-MAR-07:10 146.74 01-MAR-06:10 0.00 0.00 0.00 0.00 7.58 05-MAR-14:00 25.20 16-MAR-01:53
April 199.80 03-APR-06:10 318.77 03-APR-06:10 146.74 03-APR-05:10 0.00 0.00 0.00 0.00 9.18 16-APR-13:00 7.01 19-APR-03:00
May 199.80 01-MAY-06:10 318.77 01-MAY-06:10 146.74 01-MAY-05:10 0.00 0.00 0.00 0.00 16.78 29-MAY-16:10 1.85 07-MAY-05:26
June 199.80 01-JUN-06:10 318.77 01-JUN-06:10 146.74 01-JUN-05:10 0.00 0.00 0.00 0.00 12.53 18-JUN-13:00 0.49 05-JUN-22:00
July 199.80 03-JUL-06:10 318.77 03-JUL-06:10 146.74 03-JUL-05:10 0.00 0.00 0.00 0.00 13.50 30-JUL-15:50 2.10 02-JUL-16:00
August 199.80 01-AUG-06:10 318.77 01-AUG-06:10 146.74 01-AUG-05:10 0.00 0.00 0.00 0.00 14.16 13-AUG-12:50 1.47 14-AUG-03:20
September 199.80 01-SEP-06:10 318.77 01-SEP-06:10 146.74 01-SEP-05:10 0.00 0.00 0.00 0.00 12.61 17-SEP-14:10 0.80 02-SEP-22:00
October 199.80 02-OCT-06:10 318.77 02-OCT-06:10 146.74 02-OCT-05:10 0.00 0.00 0.00 0.00 10.86 29-OCT-14:10 1.72 16-OCT-02:44
November 199.80 01-NOV-06:10 318.77 01-NOV-06:10 146.74 01-NOV-05:10 0.00 0.00 0.00 0.00 7.26 23-NOV-11:50 19.33 11-NOV-08:40
December 199.80 01-DEC-07:10 318.77 01-DEC-07:10 146.74 01-DEC-06:10 0.00 0.00 0.00 0.00 10.49 10-DEC-14:40 23.69 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 199.80   318.77   146.74   0.00 0.00 0.00 0.00 5.78   0.49  
Maximum of Months 199.80   318.77   146.74   0.00 0.00 0.00 0.00 16.78   25.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 58.33 02-JAN-07:10 106.92 02-JAN-07:10 117.66 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05
February 58.33 01-FEB-07:10 106.92 01-FEB-07:10 117.66 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 58.33 01-MAR-07:10 106.92 01-MAR-07:10 117.66 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 58.33 03-APR-06:10 106.92 03-APR-06:10 117.66 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 01-APR-00:03
May 58.33 01-MAY-06:10 106.92 01-MAY-06:10 117.66 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 01-MAY-00:02
June 58.33 01-JUN-06:10 106.92 01-JUN-06:10 117.66 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:01 0.00 01-JUN-00:01
July 58.33 03-JUL-06:10 106.92 03-JUL-06:10 117.66 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:01 0.00 01-JUL-00:01
August 58.33 01-AUG-06:10 106.92 01-AUG-06:10 117.66 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:01 0.00 01-AUG-00:01
September 58.33 01-SEP-06:10 106.92 01-SEP-06:10 117.66 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 01-SEP-00:03
October 58.33 02-OCT-06:10 106.92 02-OCT-06:10 117.66 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 01-OCT-00:03
November 58.33 01-NOV-06:10 106.92 01-NOV-06:10 117.66 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 0.00 01-NOV-00:03
December 58.33 01-DEC-07:10 106.92 01-DEC-07:10 117.66 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 58.33   106.92   117.66   0.00 0.00 0.00 0.00 0.00   0.00  
Maximum of Months 58.33   106.92   117.66   0.00 0.00 0.00 0.00 0.00   0.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 13.61 02-JAN-07:10 51.03 02-JAN-07:10 6.26 02-JAN-06:10 0.00 0.00 0.00 0.00 30.99 15-JAN-11:51 42.14 24-JAN-03:00
February 13.61 01-FEB-07:10 51.03 01-FEB-07:10 6.26 01-FEB-06:10 0.00 0.00 0.00 0.00 24.30 20-FEB-14:42 81.71 04-FEB-05:10
March 13.61 01-MAR-07:10 51.03 01-MAR-07:10 6.26 01-MAR-06:10 0.00 0.00 0.00 0.00 28.20 05-MAR-14:00 78.14 16-MAR-01:53
April 13.61 03-APR-06:10 51.03 03-APR-06:10 6.26 03-APR-05:10 0.00 0.00 0.00 0.00 35.74 16-APR-13:00 22.88 18-APR-24:00
May 13.61 01-MAY-06:10 51.03 01-MAY-06:10 6.26 01-MAY-05:10 0.00 0.00 0.00 0.00 60.51 29-MAY-16:04 7.24 28-MAY-18:00
June 13.61 01-JUN-06:10 51.03 01-JUN-06:10 6.26 01-JUN-05:10 0.00 0.00 0.00 0.00 45.65 18-JUN-13:00 2.33 18-JUN-18:00
July 13.61 03-JUL-06:10 51.03 03-JUL-06:10 6.26 03-JUL-05:10 0.00 0.00 0.00 0.00 50.44 30-JUL-15:50 10.23 02-JUL-16:00
August 13.61 01-AUG-06:10 51.03 01-AUG-06:10 6.26 01-AUG-05:10 0.00 0.00 0.00 0.00 50.05 13-AUG-12:50 5.09 14-AUG-03:20
September 13.61 01-SEP-06:10 51.03 01-SEP-06:10 6.26 01-SEP-05:10 0.00 0.00 0.00 0.00 47.03 17-SEP-14:05 4.35 02-SEP-22:00
October 13.61 02-OCT-06:10 51.03 02-OCT-06:10 6.26 02-OCT-05:10 0.00 0.00 0.00 0.00 38.38 29-OCT-12:10 4.23 16-OCT-01:22
November 13.61 01-NOV-06:10 51.03 01-NOV-06:10 6.26 01-NOV-05:10 0.00 0.00 0.00 0.00 30.78 19-NOV-10:30 55.07 11-NOV-08:40
December 13.61 01-DEC-07:10 51.03 01-DEC-07:10 6.26 01-DEC-06:10 0.00 0.00 0.00 0.00 37.72 10-DEC-14:00 69.82 15-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 13.61   51.03   6.26   0.00 0.00 0.00 0.00 24.30   2.33  
Maximum of Months 13.61   51.03   6.26   0.00 0.00 0.00 0.00 60.51   81.71  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 LOCKER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 194.42 02-JAN-07:10 86.40 02-JAN-07:10 356.55 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05
February 194.42 01-FEB-07:10 86.40 01-FEB-07:10 356.55 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 194.42 01-MAR-07:10 86.40 01-MAR-07:10 356.55 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 194.42 03-APR-06:10 86.40 03-APR-06:10 356.55 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 01-APR-00:03
May 194.42 01-MAY-06:10 86.40 01-MAY-06:10 356.55 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 01-MAY-00:02
June 194.42 01-JUN-06:10 86.40 01-JUN-06:10 356.55 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:01 0.00 01-JUN-00:01
July 194.42 03-JUL-06:10 86.40 03-JUL-06:10 356.55 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:01 0.00 01-JUL-00:01
August 194.42 01-AUG-06:10 86.40 01-AUG-06:10 356.55 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:01 0.00 01-AUG-00:01
September 194.42 01-SEP-06:10 86.40 01-SEP-06:10 356.55 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 01-SEP-00:03
October 194.42 02-OCT-06:10 86.40 02-OCT-06:10 356.55 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 01-OCT-00:03
November 194.42 01-NOV-06:10 86.40 01-NOV-06:10 356.55 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 0.00 01-NOV-00:03
December 194.42 01-DEC-07:10 86.40 01-DEC-07:10 356.55 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 194.42   86.40   356.55   0.00 0.00 0.00 0.00 0.00   0.00  
Maximum of Months 194.42   86.40   356.55   0.00 0.00 0.00 0.00 0.00   0.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1229.70 02-JAN-07:10 546.48 02-JAN-07:10 2255.16 02-JAN-06:10 0.00 0.00 0.00 0.00 27.38 13-JAN-21:53 86.10 24-JAN-03:00
February 1229.70 01-FEB-07:10 546.48 01-FEB-07:10 2255.16 01-FEB-06:10 0.00 0.00 0.00 0.00 24.65 20-FEB-15:10 146.77 04-FEB-05:00
March 1229.70 01-MAR-07:10 546.48 01-MAR-07:10 2255.16 01-MAR-06:10 0.00 0.00 0.00 0.00 35.11 05-MAR-14:00 149.62 16-MAR-01:53
April 1229.70 03-APR-06:10 546.48 03-APR-06:10 2255.16 03-APR-05:10 0.00 0.00 0.00 0.00 48.63 16-APR-12:54 44.04 19-APR-03:00
May 1229.70 01-MAY-06:10 546.48 01-MAY-06:10 2255.16 01-MAY-05:10 0.00 0.00 0.00 0.00 94.60 29-MAY-16:04 17.83 25-MAY-04:40
June 1229.70 01-JUN-06:10 546.48 01-JUN-06:10 2255.16 01-JUN-05:10 0.00 0.00 0.00 0.00 66.01 16-JUN-23:30 8.34 21-JUN-18:40
July 1229.70 03-JUL-06:10 546.48 03-JUL-06:10 2255.16 03-JUL-05:10 0.00 0.00 0.00 0.00 72.49 30-JUL-15:43 19.05 02-JUL-16:00
August 1229.70 01-AUG-06:10 546.48 01-AUG-06:10 2255.16 01-AUG-05:10 0.00 0.00 0.00 0.00 70.15 13-AUG-13:00 13.14 14-AUG-03:20
September 1229.70 01-SEP-06:10 546.48 01-SEP-06:10 2255.16 01-SEP-05:10 0.00 0.00 0.00 0.00 69.92 17-SEP-16:50 9.45 03-SEP-14:00
October 1229.70 02-OCT-06:10 546.48 02-OCT-06:10 2255.16 02-OCT-05:10 0.00 0.00 0.00 0.00 54.88 29-OCT-14:10 13.64 16-OCT-04:40
November 1229.70 01-NOV-06:10 546.48 01-NOV-06:10 2255.16 01-NOV-05:10 0.00 0.00 0.00 0.00 39.11 22-NOV-23:53 123.30 11-NOV-08:40
December 1229.70 01-DEC-07:10 546.48 01-DEC-07:10 2255.16 01-DEC-06:10 0.00 0.00 0.00 0.00 51.52 10-DEC-15:00 149.67 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1229.70   546.48   2255.16   0.00 0.00 0.00 0.00 24.65   8.34  
Maximum of Months 1229.70   546.48   2255.16   0.00 0.00 0.00 0.00 94.60   149.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 103.68 02-JAN-07:10 155.52 02-JAN-07:10 76.15 02-JAN-06:10 0.00 0.00 0.00 0.00 35.82 13-JAN-21:50 33.58 24-JAN-03:00
February 103.68 01-FEB-07:10 155.52 01-FEB-07:10 76.15 01-FEB-06:10 0.00 0.00 0.00 0.00 29.72 20-FEB-15:10 64.27 04-FEB-05:00
March 103.68 01-MAR-07:10 155.52 01-MAR-07:10 76.15 01-MAR-06:10 0.00 0.00 0.00 0.00 34.73 05-MAR-15:50 64.23 16-MAR-01:53
April 103.68 03-APR-06:10 155.52 03-APR-06:10 76.15 03-APR-05:10 0.00 0.00 0.00 0.00 42.55 23-APR-10:10 16.82 19-APR-03:00
May 103.68 01-MAY-06:10 155.52 01-MAY-06:10 76.15 01-MAY-05:10 0.00 0.00 0.00 0.00 64.58 29-MAY-16:50 1.92 07-MAY-05:26
June 103.68 01-JUN-06:10 155.52 01-JUN-06:10 76.15 01-JUN-05:10 0.00 0.00 0.00 0.00 54.60 18-JUN-12:50 0.00 01-JUN-00:01
July 103.68 03-JUL-06:10 155.52 03-JUL-06:10 76.15 03-JUL-05:10 0.00 0.00 0.00 0.00 57.86 30-JUL-16:10 1.79 02-JUL-16:00
August 103.68 01-AUG-06:10 155.52 01-AUG-06:10 76.15 01-AUG-05:10 0.00 0.00 0.00 0.00 56.29 13-AUG-12:50 0.00 01-AUG-00:01
September 103.68 01-SEP-06:10 155.52 01-SEP-06:10 76.15 01-SEP-05:10 0.00 0.00 0.00 0.00 53.34 17-SEP-16:50 0.00 01-SEP-00:03
October 103.68 02-OCT-06:10 155.52 02-OCT-06:10 76.15 02-OCT-05:10 0.00 0.00 0.00 0.00 46.33 29-OCT-14:10 0.96 28-OCT-04:04
November 103.68 01-NOV-06:10 155.52 01-NOV-06:10 76.15 01-NOV-05:10 0.00 0.00 0.00 0.00 36.09 22-NOV-20:30 46.12 11-NOV-08:40
December 103.68 01-DEC-07:10 155.52 01-DEC-07:10 76.15 01-DEC-06:10 0.00 0.00 0.00 0.00 45.84 10-DEC-14:40 61.43 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 103.68   155.52   76.15   0.00 0.00 0.00 0.00 29.72   0.00  
Maximum of Months 103.68   155.52   76.15   0.00 0.00 0.00 0.00 64.58   64.27  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 56.70 02-JAN-07:10 472.50 02-JAN-07:10 1733.32 02-JAN-06:10 0.00 0.00 0.00 0.00 19.83 29-JAN-12:16 107.29 24-JAN-03:00
February 56.70 01-FEB-07:10 472.50 01-FEB-07:10 1733.32 01-FEB-06:10 0.00 0.00 0.00 0.00 22.32 20-FEB-15:05 168.53 03-FEB-05:53
March 56.70 01-MAR-07:10 472.50 01-MAR-07:10 1733.32 01-MAR-06:10 0.00 0.00 0.00 0.00 33.37 05-MAR-13:44 170.08 16-MAR-01:53
April 56.70 03-APR-06:10 472.50 03-APR-06:10 1733.32 03-APR-05:10 0.00 0.00 0.00 0.00 50.63 16-APR-12:54 55.68 19-APR-03:00
May 56.70 01-MAY-06:10 472.50 01-MAY-06:10 1733.32 01-MAY-05:10 0.00 0.00 0.00 0.00 99.39 29-MAY-16:04 46.18 25-MAY-04:40
June 56.70 01-JUN-06:10 472.50 01-JUN-06:10 1733.32 01-JUN-05:10 0.00 0.00 0.00 0.00 57.07 25-JUN-14:05 28.06 18-JUN-20:00
July 56.70 03-JUL-06:10 472.50 03-JUL-06:10 1733.32 03-JUL-05:10 0.00 0.00 0.00 0.00 78.79 30-JUL-15:50 37.20 02-JUL-16:00
August 56.70 01-AUG-06:10 472.50 01-AUG-06:10 1733.32 01-AUG-05:10 0.00 0.00 0.00 0.00 72.86 13-AUG-12:44 39.39 14-AUG-03:20
September 56.70 01-SEP-06:10 472.50 01-SEP-06:10 1733.32 01-SEP-05:10 0.00 0.00 0.00 0.00 73.03 17-SEP-16:46 25.58 03-SEP-14:00
October 56.70 02-OCT-06:10 472.50 02-OCT-06:10 1733.32 02-OCT-05:10 0.00 0.00 0.00 0.00 58.11 29-OCT-14:04 33.19 16-OCT-04:40
November 56.70 01-NOV-06:10 472.50 01-NOV-06:10 1733.32 01-NOV-05:10 0.00 0.00 0.00 0.00 29.87 22-NOV-20:50 166.84 11-NOV-08:40
December 56.70 01-DEC-07:10 472.50 01-DEC-07:10 1733.32 01-DEC-06:10 0.00 0.00 0.00 0.00 46.43 10-DEC-14:33 168.58 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 56.70   472.50   1733.32   0.00 0.00 0.00 0.00 19.83   25.58  
Maximum of Months 56.70   472.50   1733.32   0.00 0.00 0.00 0.00 99.39   170.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 162.00 02-JAN-07:10 258.47 02-JAN-07:10 118.98 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05
February 162.00 01-FEB-07:10 258.47 01-FEB-07:10 118.98 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 162.00 01-MAR-07:10 258.47 01-MAR-07:10 118.98 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 162.00 03-APR-06:10 258.47 03-APR-06:10 118.98 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 01-APR-00:03
May 162.00 01-MAY-06:10 258.47 01-MAY-06:10 118.98 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 01-MAY-00:02
June 162.00 01-JUN-06:10 258.47 01-JUN-06:10 118.98 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:01 0.00 01-JUN-00:01
July 162.00 03-JUL-06:10 258.47 03-JUL-06:10 118.98 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:01 0.00 01-JUL-00:01
August 162.00 01-AUG-06:10 258.47 01-AUG-06:10 118.98 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:01 0.00 01-AUG-00:01
September 162.00 01-SEP-06:10 258.47 01-SEP-06:10 118.98 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 01-SEP-00:03
October 162.00 02-OCT-06:10 258.47 02-OCT-06:10 118.98 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 01-OCT-00:03
November 162.00 01-NOV-06:10 258.47 01-NOV-06:10 118.98 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 0.00 01-NOV-00:03
December 162.00 01-DEC-07:10 258.47 01-DEC-07:10 118.98 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 162.00   258.47   118.98   0.00 0.00 0.00 0.00 0.00   0.00  
Maximum of Months 162.00   258.47   118.98   0.00 0.00 0.00 0.00 0.00   0.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1639.60 02-JAN-07:10 3005.64 02-JAN-07:10 3307.66 02-JAN-06:10 0.00 0.00 0.00 0.00 105.29 15-JAN-14:10 257.14 24-JAN-03:00
February 1639.60 01-FEB-07:10 3005.64 01-FEB-07:10 3307.66 01-FEB-06:10 0.00 0.00 0.00 0.00 95.53 20-FEB-15:10 454.97 04-FEB-05:00
March 1639.60 01-MAR-07:10 3005.64 01-MAR-07:10 3307.66 01-MAR-06:10 0.00 0.00 0.00 0.00 123.84 05-MAR-14:00 458.41 16-MAR-01:53
April 1639.60 03-APR-06:10 3005.64 03-APR-06:10 3307.66 03-APR-05:10 0.00 0.00 0.00 0.00 157.58 16-APR-13:00 130.62 19-APR-03:00
May 1639.60 01-MAY-06:10 3005.64 01-MAY-06:10 3307.66 01-MAY-05:10 0.00 0.00 0.00 0.00 300.87 29-MAY-16:10 34.09 07-MAY-05:26
June 1639.60 01-JUN-06:10 3005.64 01-JUN-06:10 3307.66 01-JUN-05:10 0.00 0.00 0.00 0.00 207.86 18-JUN-13:00 15.11 21-JUN-18:40
July 1639.60 03-JUL-06:10 3005.64 03-JUL-06:10 3307.66 03-JUL-05:10 0.00 0.00 0.00 0.00 239.41 30-JUL-15:50 44.62 02-JUL-16:00
August 1639.60 01-AUG-06:10 3005.64 01-AUG-06:10 3307.66 01-AUG-05:10 0.00 0.00 0.00 0.00 238.16 13-AUG-13:00 27.15 14-AUG-03:20
September 1639.60 01-SEP-06:10 3005.64 01-SEP-06:10 3307.66 01-SEP-05:10 0.00 0.00 0.00 0.00 228.53 17-SEP-16:50 14.77 03-SEP-14:00
October 1639.60 02-OCT-06:10 3005.64 02-OCT-06:10 3307.66 02-OCT-05:10 0.00 0.00 0.00 0.00 183.27 29-OCT-14:10 30.08 16-OCT-03:20
November 1639.60 01-NOV-06:10 3005.64 01-NOV-06:10 3307.66 01-NOV-05:10 0.00 0.00 0.00 0.00 119.62 22-NOV-23:53 361.91 11-NOV-08:40
December 1639.60 01-DEC-07:10 3005.64 01-DEC-07:10 3307.66 01-DEC-06:10 0.00 0.00 0.00 0.00 179.60 10-DEC-15:00 444.71 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1639.60   3005.64   3307.66   0.00 0.00 0.00 0.00 95.53   14.77  
Maximum of Months 1639.60   3005.64   3307.66   0.00 0.00 0.00 0.00 300.87   458.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 450.36 02-JAN-07:10 718.53 02-JAN-07:10 330.76 02-JAN-06:10 0.00 0.00 0.00 0.00 9.33 15-JAN-14:10 21.24 24-JAN-03:00
February 450.36 01-FEB-07:10 718.53 01-FEB-07:10 330.76 01-FEB-06:10 0.00 0.00 0.00 0.00 8.04 20-FEB-15:10 39.29 04-FEB-05:00
March 450.36 01-MAR-07:10 718.53 01-MAR-07:10 330.76 01-MAR-06:10 0.00 0.00 0.00 0.00 11.58 05-MAR-13:50 39.27 16-MAR-01:53
April 450.36 03-APR-06:10 718.53 03-APR-06:10 330.76 03-APR-05:10 0.00 0.00 0.00 0.00 13.93 16-APR-13:00 10.65 19-APR-03:00
May 450.36 01-MAY-06:10 718.53 01-MAY-06:10 330.76 01-MAY-05:10 0.00 0.00 0.00 0.00 25.57 29-MAY-16:10 2.51 07-MAY-05:26
June 450.36 01-JUN-06:10 718.53 01-JUN-06:10 330.76 01-JUN-05:10 0.00 0.00 0.00 0.00 19.88 18-JUN-13:00 0.56 05-JUN-22:00
July 450.36 03-JUL-06:10 718.53 03-JUL-06:10 330.76 03-JUL-05:10 0.00 0.00 0.00 0.00 21.45 30-JUL-15:51 2.73 02-JUL-16:00
August 450.36 01-AUG-06:10 718.53 01-AUG-06:10 330.76 01-AUG-05:10 0.00 0.00 0.00 0.00 21.91 13-AUG-12:50 1.24 14-AUG-03:20
September 450.36 01-SEP-06:10 718.53 01-SEP-06:10 330.76 01-SEP-05:10 0.00 0.00 0.00 0.00 19.45 17-SEP-14:10 0.92 02-SEP-22:00
October 450.36 02-OCT-06:10 718.53 02-OCT-06:10 330.76 02-OCT-05:10 0.00 0.00 0.00 0.00 16.57 29-OCT-14:10 2.12 16-OCT-02:44
November 450.36 01-NOV-06:10 718.53 01-NOV-06:10 330.76 01-NOV-05:10 0.00 0.00 0.00 0.00 11.28 23-NOV-11:50 29.65 11-NOV-08:40
December 450.36 01-DEC-07:10 718.53 01-DEC-07:10 330.76 01-DEC-06:10 0.00 0.00 0.00 0.00 15.65 10-DEC-14:40 37.59 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 450.36   718.53   330.76   0.00 0.00 0.00 0.00 8.04   0.56  
Maximum of Months 450.36   718.53   330.76   0.00 0.00 0.00 0.00 25.57   39.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 29.16 02-JAN-07:10 43.74 02-JAN-07:10 21.42 02-JAN-06:10 0.00 0.00 0.00 0.00 18.35 15-JAN-14:10 17.33 24-JAN-03:00
February 29.16 01-FEB-07:10 43.74 01-FEB-07:10 21.42 01-FEB-06:10 0.00 0.00 0.00 0.00 14.31 20-FEB-15:10 31.66 04-FEB-05:00
March 29.16 01-MAR-07:10 43.74 01-MAR-07:10 21.42 01-MAR-06:10 0.00 0.00 0.00 0.00 17.31 05-MAR-13:50 33.09 16-MAR-01:53
April 29.16 03-APR-06:10 43.74 03-APR-06:10 21.42 03-APR-05:10 0.00 0.00 0.00 0.00 21.69 23-APR-10:10 8.91 19-APR-03:00
May 29.16 01-MAY-06:10 43.74 01-MAY-06:10 21.42 01-MAY-05:10 0.00 0.00 0.00 0.00 30.70 29-MAY-16:10 1.62 07-MAY-05:26
June 29.16 01-JUN-06:10 43.74 01-JUN-06:10 21.42 01-JUN-05:10 0.00 0.00 0.00 0.00 27.53 18-JUN-12:50 0.00 01-JUN-00:01
July 29.16 03-JUL-06:10 43.74 03-JUL-06:10 21.42 03-JUL-05:10 0.00 0.00 0.00 0.00 26.88 30-JUL-16:10 1.81 02-JUL-16:00
August 29.16 01-AUG-06:10 43.74 01-AUG-06:10 21.42 01-AUG-05:10 0.00 0.00 0.00 0.00 28.43 13-AUG-12:50 0.00 01-AUG-00:01
September 29.16 01-SEP-06:10 43.74 01-SEP-06:10 21.42 01-SEP-05:10 0.00 0.00 0.00 0.00 25.80 17-SEP-14:10 0.45 02-SEP-22:00
October 29.16 02-OCT-06:10 43.74 02-OCT-06:10 21.42 02-OCT-05:10 0.00 0.00 0.00 0.00 22.53 29-OCT-14:10 0.94 16-OCT-02:04
November 29.16 01-NOV-06:10 43.74 01-NOV-06:10 21.42 01-NOV-05:10 0.00 0.00 0.00 0.00 18.12 23-NOV-11:50 22.89 11-NOV-08:40
December 29.16 01-DEC-07:10 43.74 01-DEC-07:10 21.42 01-DEC-06:10 0.00 0.00 0.00 0.00 21.94 10-DEC-14:40 29.80 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 29.16   43.74   21.42   0.00 0.00 0.00 0.00 14.31   0.00  
Maximum of Months 29.16   43.74   21.42   0.00 0.00 0.00 0.00 30.70   33.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2808.27 02-JAN-07:10 1053.00 02-JAN-07:10 1931.89 02-JAN-06:10 0.00 0.00 0.00 0.00 221.96 13-JAN-21:53 244.86 24-JAN-03:00
February 2808.27 01-FEB-07:10 1053.00 01-FEB-07:10 1931.89 01-FEB-06:10 0.00 0.00 0.00 0.00 150.36 17-FEB-23:50 440.06 04-FEB-05:00
March 2808.27 01-MAR-07:10 1053.00 01-MAR-07:10 1931.89 01-MAR-06:10 0.00 0.00 0.00 0.00 228.20 05-MAR-15:50 450.79 16-MAR-01:53
April 2808.27 03-APR-06:10 1053.00 03-APR-06:10 1931.89 03-APR-05:10 0.00 0.00 0.00 0.00 252.93 16-APR-18:20 117.59 19-APR-03:00
May 2808.27 01-MAY-06:10 1053.00 01-MAY-06:10 1931.89 01-MAY-05:10 0.00 0.00 0.00 0.00 445.90 29-MAY-16:50 11.66 07-MAY-05:26
June 2808.27 01-JUN-06:10 1053.00 01-JUN-06:10 1931.89 01-JUN-05:10 0.00 0.00 0.00 0.00 363.97 16-JUN-23:30 0.00 01-JUN-00:01
July 2808.27 03-JUL-06:10 1053.00 03-JUL-06:10 1931.89 03-JUL-05:10 0.00 0.00 0.00 0.00 386.17 30-JUL-16:10 17.30 02-JUL-16:00
August 2808.27 01-AUG-06:10 1053.00 01-AUG-06:10 1931.89 01-AUG-05:10 0.00 0.00 0.00 0.00 367.93 13-AUG-12:50 0.00 01-AUG-00:01
September 2808.27 01-SEP-06:10 1053.00 01-SEP-06:10 1931.89 01-SEP-05:10 0.00 0.00 0.00 0.00 351.40 17-SEP-16:50 8.52 03-SEP-14:00
October 2808.27 02-OCT-06:10 1053.00 02-OCT-06:10 1931.89 02-OCT-05:10 0.00 0.00 0.00 0.00 285.54 01-OCT-12:50 5.33 28-OCT-04:04
November 2808.27 01-NOV-06:10 1053.00 01-NOV-06:10 1931.89 01-NOV-05:10 0.00 0.00 0.00 0.00 234.19 22-NOV-23:53 362.79 11-NOV-08:40
December 2808.27 01-DEC-07:10 1053.00 01-DEC-07:10 1931.89 01-DEC-06:10 0.00 0.00 0.00 0.00 234.85 10-DEC-14:40 434.03 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2808.27   1053.00   1931.89   0.00 0.00 0.00 0.00 150.36   0.00  
Maximum of Months 2808.27   1053.00   1931.89   0.00 0.00 0.00 0.00 445.90   450.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1278.84 02-JAN-07:10 479.52 02-JAN-07:10 879.75 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05
February 1278.84 01-FEB-07:10 479.52 01-FEB-07:10 879.75 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 1278.84 01-MAR-07:10 479.52 01-MAR-07:10 879.75 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 1278.84 03-APR-06:10 479.52 03-APR-06:10 879.75 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 01-APR-00:03
May 1278.84 01-MAY-06:10 479.52 01-MAY-06:10 879.75 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 01-MAY-00:02
June 1278.84 01-JUN-06:10 479.52 01-JUN-06:10 879.75 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:01 0.00 01-JUN-00:01
July 1278.84 03-JUL-06:10 479.52 03-JUL-06:10 879.75 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:01 0.00 01-JUL-00:01
August 1278.84 01-AUG-06:10 479.52 01-AUG-06:10 879.75 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:01 0.00 01-AUG-00:01
September 1278.84 01-SEP-06:10 479.52 01-SEP-06:10 879.75 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 01-SEP-00:03
October 1278.84 02-OCT-06:10 479.52 02-OCT-06:10 879.75 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 01-OCT-00:03
November 1278.84 01-NOV-06:10 479.52 01-NOV-06:10 879.75 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 0.00 01-NOV-00:03
December 1278.84 01-DEC-07:10 479.52 01-DEC-07:10 879.75 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1278.84   479.52   879.75   0.00 0.00 0.00 0.00 0.00   0.00  
Maximum of Months 1278.84   479.52   879.75   0.00 0.00 0.00 0.00 0.00   0.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45.36 02-JAN-07:10 68.04 02-JAN-07:10 33.31 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05
February 45.36 01-FEB-07:10 68.04 01-FEB-07:10 33.31 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 45.36 01-MAR-07:10 68.04 01-MAR-07:10 33.31 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 45.36 03-APR-06:10 68.04 03-APR-06:10 33.31 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 01-APR-00:03
May 45.36 01-MAY-06:10 68.04 01-MAY-06:10 33.31 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 01-MAY-00:02
June 45.36 01-JUN-06:10 68.04 01-JUN-06:10 33.31 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:01 0.00 01-JUN-00:01
July 45.36 03-JUL-06:10 68.04 03-JUL-06:10 33.31 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:01 0.00 01-JUL-00:01
August 45.36 01-AUG-06:10 68.04 01-AUG-06:10 33.31 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:01 0.00 01-AUG-00:01
September 45.36 01-SEP-06:10 68.04 01-SEP-06:10 33.31 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 01-SEP-00:03
October 45.36 02-OCT-06:10 68.04 02-OCT-06:10 33.31 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 01-OCT-00:03
November 45.36 01-NOV-06:10 68.04 01-NOV-06:10 33.31 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 0.00 01-NOV-00:03
December 45.36 01-DEC-07:10 68.04 01-DEC-07:10 33.31 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45.36   68.04   33.31   0.00 0.00 0.00 0.00 0.00   0.00  
Maximum of Months 45.36   68.04   33.31   0.00 0.00 0.00 0.00 0.00   0.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 23.33 02-JAN-07:10 87.48 02-JAN-07:10 10.73 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05
February 23.33 01-FEB-07:10 87.48 01-FEB-07:10 10.73 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 23.33 01-MAR-07:10 87.48 01-MAR-07:10 10.73 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 23.33 03-APR-06:10 87.48 03-APR-06:10 10.73 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 01-APR-00:03
May 23.33 01-MAY-06:10 87.48 01-MAY-06:10 10.73 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 01-MAY-00:02
June 23.33 01-JUN-06:10 87.48 01-JUN-06:10 10.73 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:01 0.00 01-JUN-00:01
July 23.33 03-JUL-06:10 87.48 03-JUL-06:10 10.73 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:01 0.00 01-JUL-00:01
August 23.33 01-AUG-06:10 87.48 01-AUG-06:10 10.73 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:01 0.00 01-AUG-00:01
September 23.33 01-SEP-06:10 87.48 01-SEP-06:10 10.73 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 01-SEP-00:03
October 23.33 02-OCT-06:10 87.48 02-OCT-06:10 10.73 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 01-OCT-00:03
November 23.33 01-NOV-06:10 87.48 01-NOV-06:10 10.73 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 0.00 01-NOV-00:03
December 23.33 01-DEC-07:10 87.48 01-DEC-07:10 10.73 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 23.33   87.48   10.73   0.00 0.00 0.00 0.00 0.00   0.00  
Maximum of Months 23.33   87.48   10.73   0.00 0.00 0.00 0.00 0.00   0.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 18.14 02-JAN-07:10 68.04 02-JAN-07:10 8.35 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05
February 18.14 01-FEB-07:10 68.04 01-FEB-07:10 8.35 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 18.14 01-MAR-07:10 68.04 01-MAR-07:10 8.35 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 18.14 03-APR-06:10 68.04 03-APR-06:10 8.35 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 01-APR-00:03
May 18.14 01-MAY-06:10 68.04 01-MAY-06:10 8.35 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 01-MAY-00:02
June 18.14 01-JUN-06:10 68.04 01-JUN-06:10 8.35 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:01 0.00 01-JUN-00:01
July 18.14 03-JUL-06:10 68.04 03-JUL-06:10 8.35 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:01 0.00 01-JUL-00:01
August 18.14 01-AUG-06:10 68.04 01-AUG-06:10 8.35 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:01 0.00 01-AUG-00:01
September 18.14 01-SEP-06:10 68.04 01-SEP-06:10 8.35 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 01-SEP-00:03
October 18.14 02-OCT-06:10 68.04 02-OCT-06:10 8.35 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 01-OCT-00:03
November 18.14 01-NOV-06:10 68.04 01-NOV-06:10 8.35 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 0.00 01-NOV-00:03
December 18.14 01-DEC-07:10 68.04 01-DEC-07:10 8.35 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 18.14   68.04   8.35   0.00 0.00 0.00 0.00 0.00   0.00  
Maximum of Months 18.14   68.04   8.35   0.00 0.00 0.00 0.00 0.00   0.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1028.26 02-JAN-07:10 642.60 02-JAN-07:10 518.59 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05
February 1028.26 01-FEB-07:10 642.60 01-FEB-07:10 518.59 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 1028.26 01-MAR-07:10 642.60 01-MAR-07:10 518.59 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 1028.26 03-APR-06:10 642.60 03-APR-06:10 518.59 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 01-APR-00:03
May 1028.26 01-MAY-06:10 642.60 01-MAY-06:10 518.59 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 01-MAY-00:02
June 1028.26 01-JUN-06:10 642.60 01-JUN-06:10 518.59 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:01 0.00 01-JUN-00:01
July 1028.26 03-JUL-06:10 642.60 03-JUL-06:10 518.59 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:01 0.00 01-JUL-00:01
August 1028.26 01-AUG-06:10 642.60 01-AUG-06:10 518.59 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:01 0.00 01-AUG-00:01
September 1028.26 01-SEP-06:10 642.60 01-SEP-06:10 518.59 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 01-SEP-00:03
October 1028.26 02-OCT-06:10 642.60 02-OCT-06:10 518.59 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 01-OCT-00:03
November 1028.26 01-NOV-06:10 642.60 01-NOV-06:10 518.59 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 0.00 01-NOV-00:03
December 1028.26 01-DEC-07:10 642.60 01-DEC-07:10 518.59 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1028.26   642.60   518.59   0.00 0.00 0.00 0.00 0.00   0.00  
Maximum of Months 1028.26   642.60   518.59   0.00 0.00 0.00 0.00 0.00   0.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 489.89 02-JAN-07:10 1837.08 02-JAN-07:10 2470.94 02-JAN-06:10 0.00 0.00 0.00 0.00 75.79 29-JAN-12:40 248.64 24-JAN-03:00
February 489.89 01-FEB-07:10 1837.08 01-FEB-07:10 2470.94 01-FEB-06:10 0.00 0.00 0.00 0.00 58.38 02-FEB-14:00 426.81 04-FEB-05:00
March 489.89 01-MAR-07:10 1837.08 01-MAR-07:10 2470.94 01-MAR-06:10 0.00 0.00 0.00 0.00 110.69 05-MAR-14:00 439.51 16-MAR-01:53
April 489.89 03-APR-06:10 1837.08 03-APR-06:10 2470.94 03-APR-05:10 0.00 0.00 0.00 0.00 150.73 16-APR-12:54 123.58 19-APR-03:00
May 489.89 01-MAY-06:10 1837.08 01-MAY-06:10 2470.94 01-MAY-05:10 0.00 0.00 0.00 0.00 277.46 29-MAY-16:04 31.06 07-MAY-05:26
June 489.89 01-JUN-06:10 1837.08 01-JUN-06:10 2470.94 01-JUN-05:10 0.00 0.00 0.00 0.00 199.05 16-JUN-23:30 13.60 21-JUN-18:40
July 489.89 03-JUL-06:10 1837.08 03-JUL-06:10 2470.94 03-JUL-05:10 0.00 0.00 0.00 0.00 226.93 30-JUL-15:43 43.04 02-JUL-16:00
August 489.89 01-AUG-06:10 1837.08 01-AUG-06:10 2470.94 01-AUG-05:10 0.00 0.00 0.00 0.00 223.11 13-AUG-13:00 24.04 14-AUG-03:20
September 489.89 01-SEP-06:10 1837.08 01-SEP-06:10 2470.94 01-SEP-05:10 0.00 0.00 0.00 0.00 214.97 17-SEP-16:50 26.83 03-SEP-14:00
October 489.89 02-OCT-06:10 1837.08 02-OCT-06:10 2470.94 02-OCT-05:10 0.00 0.00 0.00 0.00 168.40 29-OCT-14:06 30.94 16-OCT-03:20
November 489.89 01-NOV-06:10 1837.08 01-NOV-06:10 2470.94 01-NOV-05:10 0.00 0.00 0.00 0.00 112.99 22-NOV-23:53 351.83 11-NOV-08:40
December 489.89 01-DEC-07:10 1837.08 01-DEC-07:10 2470.94 01-DEC-06:10 0.00 0.00 0.00 0.00 134.83 10-DEC-14:34 420.91 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 489.89   1837.08   2470.94   0.00 0.00 0.00 0.00 58.38   13.60  
Maximum of Months 489.89   1837.08   2470.94   0.00 0.00 0.00 0.00 277.46   439.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 248.83 02-JAN-07:10 933.12 02-JAN-07:10 1255.08 02-JAN-06:10 0.00 0.00 0.00 0.00 55.50 29-JAN-12:40 189.59 24-JAN-03:00
February 248.83 01-FEB-07:10 933.12 01-FEB-07:10 1255.08 01-FEB-06:10 0.00 0.00 0.00 0.00 45.41 02-FEB-14:00 318.67 04-FEB-05:00
March 248.83 01-MAR-07:10 933.12 01-MAR-07:10 1255.08 01-MAR-06:10 0.00 0.00 0.00 0.00 79.27 05-MAR-14:00 330.80 16-MAR-01:53
April 248.83 03-APR-06:10 933.12 03-APR-06:10 1255.08 03-APR-05:10 0.00 0.00 0.00 0.00 113.03 16-APR-12:54 94.43 19-APR-03:00
May 248.83 01-MAY-06:10 933.12 01-MAY-06:10 1255.08 01-MAY-05:10 0.00 0.00 0.00 0.00 216.74 29-MAY-16:04 26.76 28-MAY-18:00
June 248.83 01-JUN-06:10 933.12 01-JUN-06:10 1255.08 01-JUN-05:10 0.00 0.00 0.00 0.00 149.09 16-JUN-23:30 11.19 21-JUN-18:40
July 248.83 03-JUL-06:10 933.12 03-JUL-06:10 1255.08 03-JUL-05:10 0.00 0.00 0.00 0.00 176.50 30-JUL-15:43 40.26 02-JUL-16:00
August 248.83 01-AUG-06:10 933.12 01-AUG-06:10 1255.08 01-AUG-05:10 0.00 0.00 0.00 0.00 167.10 13-AUG-12:50 29.50 14-AUG-03:20
September 248.83 01-SEP-06:10 933.12 01-SEP-06:10 1255.08 01-SEP-05:10 0.00 0.00 0.00 0.00 162.90 17-SEP-16:46 26.92 03-SEP-14:00
October 248.83 02-OCT-06:10 933.12 02-OCT-06:10 1255.08 02-OCT-05:10 0.00 0.00 0.00 0.00 122.78 29-OCT-14:06 30.56 16-OCT-02:44
November 248.83 01-NOV-06:10 933.12 01-NOV-06:10 1255.08 01-NOV-05:10 0.00 0.00 0.00 0.00 84.11 22-NOV-23:53 267.65 11-NOV-08:40
December 248.83 01-DEC-07:10 933.12 01-DEC-07:10 1255.08 01-DEC-06:10 0.00 0.00 0.00 0.00 106.16 10-DEC-14:34 312.84 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 248.83   933.12   1255.08   0.00 0.00 0.00 0.00 45.41   11.19  
Maximum of Months 248.83   933.12   1255.08   0.00 0.00 0.00 0.00 216.74   330.80  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 46.66 02-JAN-07:10 291.60 02-JAN-07:10 21.47 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05
February 46.66 01-FEB-07:10 291.60 01-FEB-07:10 21.47 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 46.66 01-MAR-07:10 291.60 01-MAR-07:10 21.47 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 46.66 03-APR-06:10 291.60 03-APR-06:10 21.47 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 01-APR-00:03
May 46.66 01-MAY-06:10 291.60 01-MAY-06:10 21.47 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 01-MAY-00:02
June 46.66 01-JUN-06:10 291.60 01-JUN-06:10 21.47 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:01 0.00 01-JUN-00:01
July 46.66 03-JUL-06:10 291.60 03-JUL-06:10 21.47 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:01 0.00 01-JUL-00:01
August 46.66 01-AUG-06:10 291.60 01-AUG-06:10 21.47 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:01 0.00 01-AUG-00:01
September 46.66 01-SEP-06:10 291.60 01-SEP-06:10 21.47 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 01-SEP-00:03
October 46.66 02-OCT-06:10 291.60 02-OCT-06:10 21.47 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 01-OCT-00:03
November 46.66 01-NOV-06:10 291.60 01-NOV-06:10 21.47 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 0.00 01-NOV-00:03
December 46.66 01-DEC-07:10 291.60 01-DEC-07:10 21.47 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 46.66   291.60   21.47   0.00 0.00 0.00 0.00 0.00   0.00  
Maximum of Months 46.66   291.60   21.47   0.00 0.00 0.00 0.00 0.00   0.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 309.99 02-JAN-07:10 568.26 02-JAN-07:10 625.36 02-JAN-06:10 0.00 0.00 0.00 0.00 67.02 13-JAN-21:53 118.94 24-JAN-03:00
February 309.99 01-FEB-07:10 568.26 01-FEB-07:10 625.36 01-FEB-06:10 0.00 0.00 0.00 0.00 55.33 20-FEB-15:10 211.43 04-FEB-05:00
March 309.99 01-MAR-07:10 568.26 01-MAR-07:10 625.36 01-MAR-06:10 0.00 0.00 0.00 0.00 70.49 05-MAR-15:50 217.26 16-MAR-01:53
April 309.99 03-APR-06:10 568.26 03-APR-06:10 625.36 03-APR-05:10 0.00 0.00 0.00 0.00 88.25 16-APR-12:54 60.27 19-APR-03:00
May 309.99 01-MAY-06:10 568.26 01-MAY-06:10 625.36 01-MAY-05:10 0.00 0.00 0.00 0.00 168.44 29-MAY-16:04 20.05 07-MAY-14:00
June 309.99 01-JUN-06:10 568.26 01-JUN-06:10 625.36 01-JUN-05:10 0.00 0.00 0.00 0.00 128.93 16-JUN-23:30 13.81 25-JUN-10:00
July 309.99 03-JUL-06:10 568.26 03-JUL-06:10 625.36 03-JUL-05:10 0.00 0.00 0.00 0.00 129.52 30-JUL-16:10 29.58 02-JUL-16:00
August 309.99 01-AUG-06:10 568.26 01-AUG-06:10 625.36 01-AUG-05:10 0.00 0.00 0.00 0.00 127.05 13-AUG-12:50 9.18 14-AUG-03:20
September 309.99 01-SEP-06:10 568.26 01-SEP-06:10 625.36 01-SEP-05:10 0.00 0.00 0.00 0.00 128.36 17-SEP-16:50 14.68 03-SEP-14:00
October 309.99 02-OCT-06:10 568.26 02-OCT-06:10 625.36 02-OCT-05:10 0.00 0.00 0.00 0.00 102.33 29-OCT-14:10 9.04 16-OCT-02:44
November 309.99 01-NOV-06:10 568.26 01-NOV-06:10 625.36 01-NOV-05:10 0.00 0.00 0.00 0.00 80.70 22-NOV-23:53 191.39 11-NOV-08:40
December 309.99 01-DEC-07:10 568.26 01-DEC-07:10 625.36 01-DEC-06:10 0.00 0.00 0.00 0.00 100.01 10-DEC-14:40 205.13 15-DEC-05:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 309.99   568.26   625.36   0.00 0.00 0.00 0.00 55.33   9.04  
Maximum of Months 309.99   568.26   625.36   0.00 0.00 0.00 0.00 168.44   217.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: NE STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 90.72 02-JAN-07:10 144.74 02-JAN-07:10 66.63 02-JAN-06:10 0.00 0.00 0.00 0.00 95.11 13-JAN-21:20 209.53 24-JAN-03:00
February 90.72 01-FEB-07:10 144.74 01-FEB-07:10 66.63 01-FEB-06:10 0.00 0.00 0.00 0.00 98.65 20-FEB-15:00 454.84 04-FEB-04:55
March 90.72 01-MAR-07:10 144.74 01-MAR-07:10 66.63 01-MAR-06:10 0.00 0.00 0.00 0.00 135.33 13-MAR-18:01 387.80 16-MAR-01:50
April 90.72 03-APR-06:10 144.74 03-APR-06:10 66.63 03-APR-05:10 0.00 0.00 0.00 0.00 174.82 16-APR-12:52 110.03 18-APR-23:52
May 90.72 01-MAY-06:10 144.74 01-MAY-06:10 66.63 01-MAY-05:10 0.00 0.00 0.00 0.00 340.02 29-MAY-16:15 56.26 28-MAY-18:00
June 90.72 01-JUN-06:10 144.74 01-JUN-06:10 66.63 01-JUN-05:10 0.00 0.00 0.00 0.00 222.91 25-JUN-13:54 42.95 18-JUN-19:51
July 90.72 03-JUL-06:10 144.74 03-JUL-06:10 66.63 03-JUL-05:10 0.00 0.00 0.00 0.00 285.34 30-JUL-16:00 63.74 02-JUL-16:10
August 90.72 01-AUG-06:10 144.74 01-AUG-06:10 66.63 01-AUG-05:10 0.00 0.00 0.00 0.00 244.58 13-AUG-12:50 65.72 14-AUG-02:53
September 90.72 01-SEP-06:10 144.74 01-SEP-06:10 66.63 01-SEP-05:10 0.00 0.00 0.00 0.00 253.01 17-SEP-13:45 32.70 02-SEP-21:52
October 90.72 02-OCT-06:10 144.74 02-OCT-06:10 66.63 02-OCT-05:10 0.00 0.00 0.00 0.00 190.31 29-OCT-14:06 52.85 01-OCT-06:51
November 90.72 01-NOV-06:10 144.74 01-NOV-06:10 66.63 01-NOV-05:10 0.00 0.00 0.00 0.00 133.99 22-NOV-20:10 333.38 11-NOV-09:00
December 90.72 01-DEC-07:10 144.74 01-DEC-07:10 66.63 01-DEC-06:10 0.00 0.00 0.00 0.00 165.51 10-DEC-14:34 387.80 15-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 90.72   144.74   66.63   0.00 0.00 0.00 0.00 95.11   32.70  
Maximum of Months 90.72   144.74   66.63   0.00 0.00 0.00 0.00 340.02   454.84  



Table of Contents

Report: PeakSpaceGainsMonthly

For: NW ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 22.68 02-JAN-07:10 120.62 02-JAN-07:10 55.52 02-JAN-06:10 0.00 0.00 0.00 0.00 114.98 15-JAN-11:51 202.56 24-JAN-03:00
February 22.68 01-FEB-07:10 120.62 01-FEB-07:10 55.52 01-FEB-06:10 0.00 0.00 0.00 0.00 63.98 20-FEB-14:11 350.87 04-FEB-04:58
March 22.68 01-MAR-07:10 120.62 01-MAR-07:10 55.52 01-MAR-06:10 0.00 0.00 0.00 0.00 108.54 05-MAR-14:10 335.23 16-MAR-02:00
April 22.68 03-APR-06:10 120.62 03-APR-06:10 55.52 03-APR-05:10 0.00 0.00 0.00 0.00 147.20 16-APR-12:51 114.84 18-APR-18:20
May 22.68 01-MAY-06:10 120.62 01-MAY-06:10 55.52 01-MAY-05:10 0.00 0.00 0.00 0.00 261.53 29-MAY-15:53 41.63 28-MAY-18:00
June 22.68 01-JUN-06:10 120.62 01-JUN-06:10 55.52 01-JUN-05:10 0.00 0.00 0.00 0.00 178.70 18-JUN-13:00 31.58 18-JUN-19:51
July 22.68 03-JUL-06:10 120.62 03-JUL-06:10 55.52 03-JUL-05:10 0.00 0.00 0.00 0.00 220.12 30-JUL-16:00 40.98 02-JUL-16:10
August 22.68 01-AUG-06:10 120.62 01-AUG-06:10 55.52 01-AUG-05:10 0.00 0.00 0.00 0.00 197.72 13-AUG-12:42 54.32 14-AUG-02:53
September 22.68 01-SEP-06:10 120.62 01-SEP-06:10 55.52 01-SEP-05:10 0.00 0.00 0.00 0.00 194.43 17-SEP-13:53 28.23 02-SEP-22:00
October 22.68 02-OCT-06:10 120.62 02-OCT-06:10 55.52 02-OCT-05:10 0.00 0.00 0.00 0.00 152.32 29-OCT-14:06 42.02 16-OCT-02:53
November 22.68 01-NOV-06:10 120.62 01-NOV-06:10 55.52 01-NOV-05:10 0.00 0.00 0.00 0.00 109.85 19-NOV-10:30 288.84 11-NOV-08:53
December 22.68 01-DEC-07:10 120.62 01-DEC-07:10 55.52 01-DEC-06:10 0.00 0.00 0.00 0.00 129.66 10-DEC-13:54 304.11 15-DEC-03:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 22.68   120.62   55.52   0.00 0.00 0.00 0.00 63.98   28.23  
Maximum of Months 22.68   120.62   55.52   0.00 0.00 0.00 0.00 261.53   350.87  



Table of Contents

Report: PeakSpaceGainsMonthly

For: NW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 103.68 02-JAN-07:10 165.42 02-JAN-07:10 76.15 02-JAN-06:10 0.00 0.00 0.00 0.00 149.94 15-JAN-11:51 256.04 24-JAN-03:00
February 103.68 01-FEB-07:10 165.42 01-FEB-07:10 76.15 01-FEB-06:10 0.00 0.00 0.00 0.00 129.54 20-FEB-15:00 519.81 04-FEB-04:55
March 103.68 01-MAR-07:10 165.42 01-MAR-07:10 76.15 01-MAR-06:10 0.00 0.00 0.00 0.00 146.32 13-MAR-18:01 444.97 16-MAR-01:53
April 103.68 03-APR-06:10 165.42 03-APR-06:10 76.15 03-APR-05:10 0.00 0.00 0.00 0.00 199.80 16-APR-12:51 138.37 18-APR-23:52
May 103.68 01-MAY-06:10 165.42 01-MAY-06:10 76.15 01-MAY-05:10 0.00 0.00 0.00 0.00 388.08 29-MAY-16:15 74.17 28-MAY-18:00
June 103.68 01-JUN-06:10 165.42 01-JUN-06:10 76.15 01-JUN-05:10 0.00 0.00 0.00 0.00 254.31 25-JUN-13:54 63.50 18-JUN-19:51
July 103.68 03-JUL-06:10 165.42 03-JUL-06:10 76.15 03-JUL-05:10 0.00 0.00 0.00 0.00 326.10 30-JUL-16:00 75.79 02-JUL-16:10
August 103.68 01-AUG-06:10 165.42 01-AUG-06:10 76.15 01-AUG-05:10 0.00 0.00 0.00 0.00 279.52 13-AUG-12:50 88.78 14-AUG-02:53
September 103.68 01-SEP-06:10 165.42 01-SEP-06:10 76.15 01-SEP-05:10 0.00 0.00 0.00 0.00 288.05 17-SEP-13:53 44.11 02-SEP-22:00
October 103.68 02-OCT-06:10 165.42 02-OCT-06:10 76.15 02-OCT-05:10 0.00 0.00 0.00 0.00 227.03 29-OCT-14:06 69.52 01-OCT-06:51
November 103.68 01-NOV-06:10 165.42 01-NOV-06:10 76.15 01-NOV-05:10 0.00 0.00 0.00 0.00 150.52 22-NOV-20:10 379.70 11-NOV-08:53
December 103.68 01-DEC-07:10 165.42 01-DEC-07:10 76.15 01-DEC-06:10 0.00 0.00 0.00 0.00 195.77 10-DEC-14:40 443.20 15-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 103.68   165.42   76.15   0.00 0.00 0.00 0.00 129.54   44.11  
Maximum of Months 103.68   165.42   76.15   0.00 0.00 0.00 0.00 388.08   519.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: SW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 51.84 02-JAN-07:10 82.71 02-JAN-07:10 38.07 02-JAN-06:10 0.00 0.00 0.00 0.00 45.91 29-JAN-12:10 154.72 24-JAN-03:00
February 51.84 01-FEB-07:10 82.71 01-FEB-07:10 38.07 01-FEB-06:10 0.00 0.00 0.00 0.00 41.24 02-FEB-14:00 259.90 04-FEB-05:00
March 51.84 01-MAR-07:10 82.71 01-MAR-07:10 38.07 01-MAR-06:10 0.00 0.00 0.00 0.00 72.48 05-MAR-14:05 245.75 16-MAR-02:00
April 51.84 03-APR-06:10 82.71 03-APR-06:10 38.07 03-APR-05:10 0.00 0.00 0.00 0.00 99.90 16-APR-12:51 83.61 18-APR-23:52
May 51.84 01-MAY-06:10 82.71 01-MAY-06:10 38.07 01-MAY-05:10 0.00 0.00 0.00 0.00 193.76 29-MAY-16:15 36.84 28-MAY-18:00
June 51.84 01-JUN-06:10 82.71 01-JUN-06:10 38.07 01-JUN-05:10 0.00 0.00 0.00 0.00 132.05 25-JUN-13:53 31.35 18-JUN-19:51
July 51.84 03-JUL-06:10 82.71 03-JUL-06:10 38.07 03-JUL-05:10 0.00 0.00 0.00 0.00 163.05 30-JUL-16:00 35.89 02-JUL-16:10
August 51.84 01-AUG-06:10 82.71 01-AUG-06:10 38.07 01-AUG-05:10 0.00 0.00 0.00 0.00 143.04 13-AUG-12:25 45.54 14-AUG-02:53
September 51.84 01-SEP-06:10 82.71 01-SEP-06:10 38.07 01-SEP-05:10 0.00 0.00 0.00 0.00 144.53 17-SEP-13:45 23.76 02-SEP-22:00
October 51.84 02-OCT-06:10 82.71 02-OCT-06:10 38.07 02-OCT-05:10 0.00 0.00 0.00 0.00 109.63 29-OCT-14:06 36.21 01-OCT-06:51
November 51.84 01-NOV-06:10 82.71 01-NOV-06:10 38.07 01-NOV-05:10 0.00 0.00 0.00 0.00 65.95 22-NOV-20:10 222.86 11-NOV-09:00
December 51.84 01-DEC-07:10 82.71 01-DEC-07:10 38.07 01-DEC-06:10 0.00 0.00 0.00 0.00 92.18 10-DEC-14:58 226.41 15-DEC-03:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 51.84   82.71   38.07   0.00 0.00 0.00 0.00 41.24   23.76  
Maximum of Months 51.84   82.71   38.07   0.00 0.00 0.00 0.00 193.76   259.90  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1002.58 01-JAN-08:11 129.61 162.00 1069.81 0.00 0.00 0.00 0.00 0.00 3.35
February 990.99 05-FEB-16:21 129.61 162.00 1069.81 0.00 0.00 0.00 0.00 0.00 6.44
March 974.61 03-MAR-04:11 0.00 486.00 1069.81 0.00 0.00 0.00 0.00 0.00 5.49
April 947.21 23-APR-05:31 129.61 81.00 641.88 0.00 0.00 0.00 0.00 0.85 0.00
May 931.61 28-MAY-04:21 0.00 81.00 641.88 0.00 0.00 0.00 0.00 0.43 0.00
June 933.00 18-JUN-07:11 129.61 162.00 1069.81 0.00 0.00 0.00 0.00 6.20 0.00
July 899.12 15-JUL-23:51 0.00 81.00 641.88 0.00 0.00 0.00 0.00 2.00 0.00
August 949.03 13-AUG-03:41 0.00 81.00 641.88 0.00 0.00 0.00 0.00 0.34 0.00
September 931.35 10-SEP-12:31 129.61 162.00 1069.81 0.00 0.00 0.00 0.00 15.53 0.00
October 973.59 22-OCT-07:01 129.61 162.00 1069.81 0.00 0.00 0.00 0.00 0.00 0.23
November 1000.13 26-NOV-08:11 129.61 162.00 1069.81 0.00 0.00 0.00 0.00 0.00 6.26
December 985.75 22-DEC-21:31 0.00 486.00 641.88 0.00 0.00 0.00 0.00 0.00 1.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 899.12   0.00 81.00 641.88 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1002.58   129.61 486.00 1069.81 0.00 0.00 0.00 0.00 15.53 6.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 73.82 06-JAN-16:40 12.10 45.36 5.57 0.00 0.00 0.00 0.00 0.00 0.00
February 79.91 17-FEB-16:00 12.10 45.36 5.57 0.00 0.00 0.00 0.00 0.00 0.00
March 84.84 30-MAR-16:03 84.67 317.52 38.96 0.00 0.00 0.00 0.00 0.00 0.00
April 95.16 14-APR-16:00 12.10 45.36 5.57 0.00 0.00 0.00 0.00 0.00 0.00
May 100.88 18-MAY-15:40 12.10 45.36 5.57 0.00 0.00 0.00 0.00 0.00 0.00
June 143.98 15-JUN-06:01 108.86 408.24 50.09 0.00 0.00 0.00 0.00 0.00 0.00
July 128.99 21-JUL-06:01 96.77 362.88 44.52 0.00 0.00 0.00 0.00 0.00 0.00
August 142.25 01-AUG-06:01 108.86 408.24 50.09 0.00 0.00 0.00 0.00 0.00 0.00
September 110.53 22-SEP-06:01 108.86 408.24 50.09 0.00 0.00 0.00 0.00 0.00 0.00
October 89.86 03-OCT-16:00 12.10 45.36 5.57 0.00 0.00 0.00 0.00 0.00 0.00
November 81.54 30-NOV-15:50 12.10 45.36 5.57 0.00 0.00 0.00 0.00 0.00 0.00
December 81.95 01-DEC-15:20 12.10 45.36 5.57 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 73.82   12.10 45.36 5.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 143.98   108.86 408.24 50.09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6811.47 20-JAN-07:01 40827.97 3061.80 3742.58 0.00 0.00 0.00 0.00 0.00 7.91
February 6405.98 23-FEB-07:01 40827.97 3061.80 3742.58 0.00 0.00 0.00 0.00 0.00 5.16
March 6594.04 01-MAR-07:01 45364.41 3402.00 4158.42 0.00 0.00 0.00 0.00 0.00 3.80
April 6389.75 19-APR-06:01 36291.53 2721.60 3326.74 0.00 0.00 0.00 0.00 0.00 3.45
May 5242.31 08-MAY-05:01 17641.72 1587.60 2910.90 0.00 0.00 0.00 0.00 0.17 0.00
June 4794.42 10-JUN-04:01 0.00 378.00 1247.53 0.00 0.00 0.00 0.00 3.33 0.00
July 4441.24 13-JUL-04:01 0.00 1020.60 1871.29 0.00 0.00 0.00 0.00 3.60 0.00
August 4528.95 18-AUG-04:01 0.00 1020.60 1871.29 0.00 0.00 0.00 0.00 11.14 0.00
September 4967.36 23-SEP-04:01 0.00 378.00 1247.53 0.00 0.00 0.00 0.00 7.15 0.00
October 4914.69 17-OCT-06:03 18145.77 1360.80 1663.37 0.00 0.00 0.00 0.00 1.18 0.00
November 5121.72 14-NOV-07:02 22682.21 1701.00 2079.21 0.00 0.00 0.00 0.00 0.00 2.60
December 5819.33 13-DEC-07:01 45364.41 3402.00 4158.42 0.00 0.00 0.00 0.00 0.00 2.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4441.24   0.00 378.00 1247.53 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6811.47   45364.41 3402.00 4158.42 0.00 0.00 0.00 0.00 11.14 7.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 CLEAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1189.38 26-JAN-04:21 0.00 567.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
February 1172.46 06-FEB-06:01 1512.15 1134.00 2496.21 0.00 0.00 0.00 0.00 0.00 0.00
March 1170.54 22-MAR-03:11 0.00 567.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
April 1116.01 19-APR-03:11 0.00 567.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
May 1080.65 28-MAY-04:21 0.00 94.50 748.86 0.00 0.00 0.00 0.00 0.00 0.00
June 1045.80 25-JUN-06:41 151.21 94.50 748.86 0.00 0.00 0.00 0.00 0.00 0.00
July 999.08 16-JUL-01:51 0.00 94.50 748.86 0.00 0.00 0.00 0.00 0.00 0.00
August 1066.26 13-AUG-03:41 0.00 94.50 748.86 0.00 0.00 0.00 0.00 0.00 0.00
September 1028.20 17-SEP-07:01 151.21 189.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
October 1086.77 22-OCT-07:01 151.21 189.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
November 1156.45 27-NOV-06:01 1512.15 1134.00 2496.21 0.00 0.00 0.00 0.00 0.00 0.00
December 1180.16 15-DEC-04:11 0.00 567.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 999.08   0.00 94.50 748.86 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1189.38   1512.15 1134.00 2496.21 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1446.75 26-JAN-04:21 0.00 742.50 1634.43 0.00 0.00 0.00 0.00 0.00 0.00
February 1417.53 25-FEB-06:01 792.08 247.50 980.66 0.00 0.00 0.00 0.00 0.00 0.00
March 1421.86 18-MAR-05:01 792.08 247.50 980.66 0.00 0.00 0.00 0.00 0.00 0.00
April 1356.28 19-APR-03:11 0.00 742.50 1634.43 0.00 0.00 0.00 0.00 0.00 0.00
May 1307.62 28-MAY-04:21 0.00 123.75 980.66 0.00 0.00 0.00 0.00 0.00 0.00
June 1266.21 25-JUN-06:41 198.02 123.75 980.66 0.00 0.00 0.00 0.00 0.00 0.00
July 1209.20 16-JUL-01:51 0.00 123.75 980.66 0.00 0.00 0.00 0.00 0.00 0.00
August 1292.64 13-AUG-03:41 0.00 123.75 980.66 0.00 0.00 0.00 0.00 0.00 0.00
September 1244.39 17-SEP-07:01 198.02 247.50 1634.43 0.00 0.00 0.00 0.00 0.00 0.00
October 1316.48 22-OCT-07:01 198.02 247.50 1634.43 0.00 0.00 0.00 0.00 0.00 0.00
November 1387.50 27-NOV-06:01 1980.19 1485.00 3268.85 0.00 0.00 0.00 0.00 0.00 0.00
December 1436.45 15-DEC-04:11 0.00 742.50 1634.43 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1209.20   0.00 123.75 980.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1446.75   1980.19 1485.00 3268.85 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 769.29 24-JAN-07:01 680.47 1247.40 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
February 767.25 03-FEB-07:01 680.47 1247.40 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
March 768.51 22-MAR-06:01 680.47 1247.40 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
April 738.44 19-APR-06:01 544.37 997.92 1098.19 0.00 0.00 0.00 0.00 0.00 0.00
May 530.01 10-MAY-14:02 272.19 498.96 549.10 0.00 0.00 0.00 0.00 0.00 0.00
June 516.51 23-JUN-06:01 544.37 997.92 1098.19 0.00 0.00 0.00 0.00 0.00 0.00
July 454.41 14-JUL-14:03 204.14 374.22 411.82 0.00 0.00 0.00 0.00 0.00 0.00
August 414.26 11-AUG-06:01 612.42 1122.66 1235.47 0.00 0.00 0.00 0.00 0.00 0.00
September 389.79 28-SEP-14:05 136.09 249.48 274.55 0.00 0.00 0.00 0.00 0.00 0.00
October 400.17 20-OCT-14:05 136.09 249.48 274.55 0.00 0.00 0.00 0.00 0.00 0.00
November 757.64 13-NOV-07:01 680.47 1247.40 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
December 768.60 15-DEC-07:01 680.47 1247.40 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 389.79   136.09 249.48 274.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 769.29   680.47 1247.40 1372.74 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 257.29 02-JAN-15:05 48.60 89.10 98.05 0.00 0.00 0.00 0.00 1.86 0.00
February 264.47 17-FEB-13:05 48.60 89.10 98.05 0.00 0.00 0.00 0.00 3.42 0.00
March 264.44 13-MAR-14:05 48.60 89.10 98.05 0.00 0.00 0.00 0.00 3.23 0.00
April 303.64 17-APR-14:05 48.60 89.10 98.05 0.00 0.00 0.00 0.00 2.75 0.00
May 507.80 14-MAY-13:51 12.15 44.55 220.62 0.00 0.00 0.00 0.00 4.75 0.00
June 516.12 11-JUN-15:51 12.15 44.55 220.62 0.00 0.00 0.00 0.00 10.86 0.00
July 531.08 04-JUL-15:11 13.50 49.50 245.13 0.00 0.00 0.00 0.00 10.46 0.00
August 537.47 06-AUG-14:31 13.50 49.50 245.13 0.00 0.00 0.00 0.00 10.72 0.00
September 524.13 04-SEP-14:31 12.15 44.55 220.62 0.00 0.00 0.00 0.00 5.59 0.00
October 411.67 02-OCT-06:01 194.42 356.40 392.21 0.00 0.00 0.00 0.00 1.54 0.00
November 404.66 30-NOV-07:02 145.81 267.30 294.16 0.00 0.00 0.00 0.00 1.48 0.00
December 293.24 11-DEC-07:03 97.21 178.20 196.11 0.00 0.00 0.00 0.00 0.00 0.05
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 257.29   12.15 44.55 98.05 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 537.47   194.42 356.40 392.21 0.00 0.00 0.00 0.00 10.86 0.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1030.62 03-JAN-06:12 44.10 441.00 2426.65 0.00 0.00 0.00 0.00 0.00 0.38
February 1030.90 02-FEB-06:12 44.10 441.00 2426.65 0.00 0.00 0.00 0.00 0.00 0.27
March 1033.32 31-MAR-05:12 44.10 441.00 2426.65 0.00 0.00 0.00 0.00 0.00 0.49
April 1186.34 09-APR-11:51 7.94 132.30 2183.98 0.00 0.00 0.00 0.00 1.86 0.00
May 1155.73 14-MAY-12:31 7.94 132.30 2183.98 0.00 0.00 0.00 0.00 5.07 0.00
June 1157.83 11-JUN-15:51 7.94 132.30 2183.98 0.00 0.00 0.00 0.00 8.74 0.00
July 1217.09 04-JUL-11:51 8.82 147.00 2426.65 0.00 0.00 0.00 0.00 5.63 0.00
August 1178.70 06-AUG-14:31 8.82 147.00 2426.65 0.00 0.00 0.00 0.00 9.08 0.00
September 1198.21 10-SEP-12:31 8.82 147.00 2426.65 0.00 0.00 0.00 0.00 8.13 0.00
October 1094.42 07-OCT-04:01 0.00 147.00 1455.99 0.00 0.00 0.00 0.00 0.25 0.00
November 1050.71 30-NOV-06:02 52.92 529.20 2911.98 0.00 0.00 0.00 0.00 0.59 0.00
December 1033.18 01-DEC-06:12 44.10 441.00 2426.65 0.00 0.00 0.00 0.00 0.00 0.01
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1030.62   0.00 132.30 1455.99 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1217.09   52.92 529.20 2911.98 0.00 0.00 0.00 0.00 9.08 0.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1340.74 27-JAN-07:01 147.42 1228.50 6961.96 0.00 0.00 0.00 0.00 0.00 0.00
February 1319.93 24-FEB-07:01 147.42 1228.50 6961.96 0.00 0.00 0.00 0.00 0.00 0.65
March 1298.02 15-MAR-06:01 147.42 1228.50 6961.96 0.00 0.00 0.00 0.00 0.00 13.62
April 1153.87 19-APR-06:01 117.94 982.80 5569.56 0.00 0.00 0.00 0.00 0.00 3.45
May 1152.74 08-MAY-05:01 57.33 573.30 4016.05 0.00 0.00 0.00 0.00 0.21 0.00
June 1256.87 23-JUN-06:01 117.94 982.80 5569.56 0.00 0.00 0.00 0.00 0.73 0.00
July 1247.02 14-JUL-06:01 132.68 1105.65 6265.76 0.00 0.00 0.00 0.00 1.37 0.00
August 1267.13 09-AUG-06:01 117.94 982.80 5569.56 0.00 0.00 0.00 0.00 0.00 0.00
September 1257.77 11-SEP-06:01 117.94 982.80 5569.56 0.00 0.00 0.00 0.00 1.26 0.00
October 1294.56 14-OCT-05:01 26.21 109.20 4589.78 0.00 0.00 0.00 0.00 0.00 0.00
November 1340.76 27-NOV-07:01 147.42 1228.50 6961.96 0.00 0.00 0.00 0.00 0.00 5.24
December 1327.41 13-DEC-07:01 147.42 1228.50 6961.96 0.00 0.00 0.00 0.00 0.00 2.20
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1152.74   26.21 109.20 4016.05 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1340.76   147.42 1228.50 6961.96 0.00 0.00 0.00 0.00 1.37 13.62



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 380.53 24-JAN-07:01 291.63 534.60 588.32 0.00 0.00 0.00 0.00 0.00 0.00
February 379.44 03-FEB-07:01 291.63 534.60 588.32 0.00 0.00 0.00 0.00 0.00 0.00
March 380.18 22-MAR-06:01 291.63 534.60 588.32 0.00 0.00 0.00 0.00 0.00 0.00
April 375.06 19-APR-06:01 233.30 427.68 470.65 0.00 0.00 0.00 0.00 0.00 0.00
May 314.94 12-MAY-06:02 145.81 267.30 294.16 0.00 0.00 0.00 0.00 0.00 0.00
June 359.57 16-JUN-06:01 233.30 427.68 470.65 0.00 0.00 0.00 0.00 0.00 0.00
July 340.65 21-JUL-06:01 233.30 427.68 470.65 0.00 0.00 0.00 0.00 0.00 0.00
August 352.62 11-AUG-06:01 262.47 481.14 529.49 0.00 0.00 0.00 0.00 0.00 0.00
September 324.38 22-SEP-06:01 262.47 481.14 529.49 0.00 0.00 0.00 0.00 0.00 0.00
October 333.54 03-OCT-06:01 233.30 427.68 470.65 0.00 0.00 0.00 0.00 0.00 0.00
November 380.26 13-NOV-07:01 291.63 534.60 588.32 0.00 0.00 0.00 0.00 0.00 0.00
December 380.10 15-DEC-07:01 291.63 534.60 588.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 314.94   145.81 267.30 294.16 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 380.53   291.63 534.60 588.32 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 IT HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 663.27 05-JAN-07:01 529.20 844.32 388.66 0.00 0.00 0.00 0.00 0.00 0.00
February 665.10 03-FEB-07:01 756.00 1206.17 555.23 0.00 0.00 0.00 0.00 0.00 0.00
March 660.91 15-MAR-06:01 756.00 1206.17 555.23 0.00 0.00 0.00 0.00 0.00 0.00
April 662.02 19-APR-06:01 604.80 964.94 444.18 0.00 0.00 0.00 0.00 0.00 0.00
May 575.44 12-MAY-06:02 378.00 603.09 277.61 0.00 0.00 0.00 0.00 0.00 0.00
June 656.76 16-JUN-06:01 604.80 964.94 444.18 0.00 0.00 0.00 0.00 0.00 0.00
July 635.03 19-JUL-06:01 529.20 844.32 388.66 0.00 0.00 0.00 0.00 0.00 0.00
August 654.37 09-AUG-06:01 604.80 964.94 444.18 0.00 0.00 0.00 0.00 0.00 0.00
September 606.95 21-SEP-06:01 604.80 964.94 444.18 0.00 0.00 0.00 0.00 0.00 0.00
October 585.71 04-OCT-06:01 604.80 964.94 444.18 0.00 0.00 0.00 0.00 0.00 0.00
November 602.15 30-NOV-07:02 453.60 723.70 333.14 0.00 0.00 0.00 0.00 0.00 0.00
December 658.32 20-DEC-07:01 756.00 1206.17 555.23 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 575.44   378.00 603.09 277.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 665.10   756.00 1206.17 555.23 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 647.83 05-JAN-07:01 423.40 776.16 854.15 0.00 0.00 0.00 0.00 0.00 0.00
February 647.28 03-FEB-07:01 604.86 1108.80 1220.22 0.00 0.00 0.00 0.00 0.00 0.00
March 645.37 15-MAR-06:01 604.86 1108.80 1220.22 0.00 0.00 0.00 0.00 0.00 0.00
April 647.54 19-APR-06:01 483.89 887.04 976.17 0.00 0.00 0.00 0.00 0.00 0.00
May 640.95 12-MAY-06:02 302.43 554.40 610.11 0.00 0.00 0.00 0.00 0.00 0.00
June 650.06 16-JUN-06:01 483.89 887.04 976.17 0.00 0.00 0.00 0.00 0.00 0.00
July 643.47 13-JUL-06:02 362.92 665.28 732.13 0.00 0.00 0.00 0.00 0.00 0.00
August 647.31 02-AUG-06:01 483.89 887.04 976.17 0.00 0.00 0.00 0.00 0.00 0.00
September 642.53 01-SEP-06:01 423.40 776.16 854.15 0.00 0.00 0.00 0.00 0.00 0.00
October 638.58 02-OCT-06:01 483.89 887.04 976.17 0.00 0.00 0.00 0.00 0.00 0.00
November 642.01 30-NOV-07:02 362.92 665.28 732.13 0.00 0.00 0.00 0.00 0.00 0.00
December 645.15 12-DEC-07:01 604.86 1108.80 1220.22 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 638.58   302.43 554.40 610.11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 650.06   604.86 1108.80 1220.22 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 LOBBY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4819.84 20-JAN-07:01 6046.43 6549.65 6098.90 0.00 0.00 0.00 0.00 0.00 9.00
February 5144.88 20-FEB-16:42 223.94 485.16 2032.97 0.00 0.00 0.00 0.00 5.80 0.00
March 5131.94 28-MAR-18:06 0.00 4851.60 3388.28 0.00 0.00 0.00 0.00 0.00 0.90
April 6096.77 09-APR-15:51 298.59 646.88 2710.62 0.00 0.00 0.00 0.00 6.01 0.00
May 6088.66 14-MAY-14:31 335.91 727.74 3049.45 0.00 0.00 0.00 0.00 12.51 0.00
June 6226.22 11-JUN-15:51 335.91 727.74 3049.45 0.00 0.00 0.00 0.00 24.81 0.00
July 6458.35 04-JUL-15:51 373.24 808.60 3388.28 0.00 0.00 0.00 0.00 20.87 0.00
August 6327.45 06-AUG-14:31 373.24 808.60 3388.28 0.00 0.00 0.00 0.00 26.06 0.00
September 6222.30 04-SEP-14:31 335.91 727.74 3049.45 0.00 0.00 0.00 0.00 13.24 0.00
October 5572.85 07-OCT-04:01 0.00 808.60 2032.97 0.00 0.00 0.00 0.00 1.00 0.00
November 4820.55 30-NOV-07:02 4030.95 4366.44 4065.94 0.00 0.00 0.00 0.00 3.45 0.00
December 4813.97 04-DEC-07:02 4030.95 4366.44 4065.94 0.00 0.00 0.00 0.00 0.00 0.50
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4813.97   0.00 485.16 2032.97 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6458.35   6046.43 6549.65 6098.90 0.00 0.00 0.00 0.00 26.06 9.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1358.79 17-JAN-06:12 360.00 689.24 475.91 0.00 0.00 0.00 0.00 0.00 0.00
February 1370.99 21-FEB-06:12 360.00 689.24 475.91 0.00 0.00 0.00 0.00 0.00 0.00
March 1353.26 13-MAR-05:12 360.00 689.24 475.91 0.00 0.00 0.00 0.00 0.00 0.00
April 1350.00 03-APR-05:12 360.00 689.24 475.91 0.00 0.00 0.00 0.00 0.00 0.00
May 1429.75 13-MAY-04:01 0.00 229.75 285.55 0.00 0.00 0.00 0.00 0.00 0.00
June 1415.55 17-JUN-04:01 0.00 229.75 285.55 0.00 0.00 0.00 0.00 0.00 0.00
July 1333.51 19-JUL-05:02 432.00 827.09 571.09 0.00 0.00 0.00 0.00 0.00 0.00
August 1344.64 04-AUG-05:02 432.00 827.09 571.09 0.00 0.00 0.00 0.00 0.00 0.00
September 1404.37 16-SEP-04:01 0.00 206.77 256.99 0.00 0.00 0.00 0.00 0.00 0.00
October 1426.57 07-OCT-04:01 0.00 229.75 285.55 0.00 0.00 0.00 0.00 0.00 0.00
November 1374.08 27-NOV-06:12 432.00 827.09 571.09 0.00 0.00 0.00 0.00 0.00 0.00
December 1362.00 04-DEC-06:12 360.00 689.24 475.91 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1333.51   0.00 206.77 256.99 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1429.75   432.00 827.09 571.09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 443.17 02-JAN-04:11 0.00 145.80 107.08 0.00 0.00 0.00 0.00 0.00 0.00
February 445.74 19-FEB-20:31 0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.00 0.28
March 449.22 13-MAR-03:11 0.00 145.80 107.08 0.00 0.00 0.00 0.00 0.00 2.09
April 451.23 23-APR-05:31 16.20 24.30 64.25 0.00 0.00 0.00 0.00 0.00 0.46
May 447.13 28-MAY-04:21 0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.02 0.00
June 449.22 18-JUN-07:11 16.20 48.60 107.08 0.00 0.00 0.00 0.00 2.80 0.00
July 446.05 16-JUL-01:51 0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.32 0.00
August 454.01 13-AUG-03:41 0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.15 0.00
September 453.06 17-SEP-07:01 16.20 48.60 107.08 0.00 0.00 0.00 0.00 0.27 0.00
October 457.03 22-OCT-07:01 16.20 48.60 107.08 0.00 0.00 0.00 0.00 0.00 0.35
November 451.52 05-NOV-00:01 0.00 24.30 64.25 0.00 0.00 0.00 0.00 1.19 0.00
December 451.64 26-DEC-02:21 0.00 48.60 64.25 0.00 0.00 0.00 0.00 0.19 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 443.17   0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 457.03   16.20 145.80 107.08 0.00 0.00 0.00 0.00 2.80 2.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5215.83 19-JAN-06:12 2970.29 1584.00 9805.03 0.00 0.00 0.00 0.00 0.00 0.00
February 5237.56 02-FEB-06:12 2970.29 1584.00 9805.03 0.00 0.00 0.00 0.00 0.00 1.16
March 5214.12 13-MAR-05:12 2970.29 1584.00 9805.03 0.00 0.00 0.00 0.00 0.00 1.67
April 5183.50 07-APR-05:12 2970.29 1584.00 9805.03 0.00 0.00 0.00 0.00 0.00 0.37
May 5478.49 13-MAY-04:01 0.00 528.00 5883.02 0.00 0.00 0.00 0.00 1.76 0.00
June 5432.08 17-JUN-04:01 0.00 528.00 5883.02 0.00 0.00 0.00 0.00 6.10 0.00
July 5677.41 04-JUL-15:51 594.06 528.00 9805.03 0.00 0.00 0.00 0.00 25.72 0.00
August 5697.71 06-AUG-14:31 594.06 528.00 9805.03 0.00 0.00 0.00 0.00 30.07 0.00
September 5337.03 16-SEP-04:01 0.00 475.20 5294.72 0.00 0.00 0.00 0.00 0.00 0.76
October 5373.99 07-OCT-04:01 0.00 528.00 5883.02 0.00 0.00 0.00 0.00 0.92 0.00
November 5185.93 15-NOV-06:12 2970.29 1584.00 9805.03 0.00 0.00 0.00 0.00 0.00 2.19
December 5204.00 18-DEC-06:12 2970.29 1584.00 9805.03 0.00 0.00 0.00 0.00 0.00 3.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5183.50   0.00 475.20 5294.72 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5697.71   2970.29 1584.00 9805.03 0.00 0.00 0.00 0.00 30.07 3.02



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2178.33 24-JAN-07:02 2678.40 4273.30 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
February 2180.47 03-FEB-07:02 2678.40 4273.30 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
March 2182.58 22-MAR-06:02 2678.40 4273.30 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
April 2135.36 19-APR-06:02 2142.72 3418.64 1573.68 0.00 0.00 0.00 0.00 0.00 0.00
May 2078.06 26-MAY-06:03 1071.36 1709.32 786.84 0.00 0.00 0.00 0.00 0.00 0.00
June 2076.76 16-JUN-06:01 2142.72 3418.64 1573.68 0.00 0.00 0.00 0.00 0.00 0.00
July 2058.41 13-JUL-06:02 1607.04 2563.98 1180.26 0.00 0.00 0.00 0.00 0.00 0.00
August 2071.84 31-AUG-06:01 1874.88 2991.31 1376.97 0.00 0.00 0.00 0.00 0.00 0.00
September 2065.26 01-SEP-06:01 1874.88 2991.31 1376.97 0.00 0.00 0.00 0.00 0.00 0.00
October 2063.36 27-OCT-06:03 1071.36 1709.32 786.84 0.00 0.00 0.00 0.00 0.00 0.00
November 2155.31 13-NOV-07:02 2678.40 4273.30 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
December 2180.04 20-DEC-07:02 2678.40 4273.30 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2058.41   1071.36 1709.32 786.84 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2182.58   2678.40 4273.30 1967.10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2839.87 19-JAN-06:12 1620.16 864.00 5348.20 0.00 0.00 0.00 0.00 0.00 0.00
February 2860.33 03-FEB-06:12 1944.19 1036.80 6417.84 0.00 0.00 0.00 0.00 0.00 0.00
March 2865.46 21-MAR-05:12 1944.19 1036.80 6417.84 0.00 0.00 0.00 0.00 0.00 0.00
April 2842.15 19-APR-05:12 1620.16 864.00 5348.20 0.00 0.00 0.00 0.00 0.00 0.00
May 2928.37 13-MAY-04:01 0.00 288.00 3208.92 0.00 0.00 0.00 0.00 0.00 0.00
June 2885.32 17-JUN-04:01 0.00 288.00 3208.92 0.00 0.00 0.00 0.00 0.00 0.00
July 2760.91 07-JUL-05:12 1620.16 864.00 5348.20 0.00 0.00 0.00 0.00 0.00 0.00
August 2766.66 29-AUG-05:12 1620.16 864.00 5348.20 0.00 0.00 0.00 0.00 0.00 0.00
September 2859.37 16-SEP-04:01 0.00 259.20 2888.03 0.00 0.00 0.00 0.00 0.00 0.00
October 2862.29 07-OCT-04:01 0.00 288.00 3208.92 0.00 0.00 0.00 0.00 0.00 0.00
November 2866.01 13-NOV-06:12 1944.19 1036.80 6417.84 0.00 0.00 0.00 0.00 0.00 0.00
December 2842.64 20-DEC-06:12 1620.16 864.00 5348.20 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2760.91   0.00 259.20 2888.03 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2928.37   1944.19 1036.80 6417.84 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 MED GAS

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 178.14 03-JAN-14:10 24.19 90.72 11.13 0.00 0.00 0.00 0.00 2.23 0.00
February 206.49 11-FEB-14:00 4.03 20.16 4.45 0.00 0.00 0.00 0.00 4.20 0.00
March 254.12 27-MAR-13:00 12.10 45.36 5.57 0.00 0.00 0.00 0.00 4.07 0.00
April 629.62 09-APR-12:31 6.05 45.36 25.04 0.00 0.00 0.00 0.00 7.23 0.00
May 657.12 14-MAY-12:31 6.05 45.36 25.04 0.00 0.00 0.00 0.00 8.22 0.00
June 671.78 11-JUN-15:51 6.05 45.36 25.04 0.00 0.00 0.00 0.00 15.12 0.00
July 695.88 04-JUL-12:31 6.72 50.40 27.83 0.00 0.00 0.00 0.00 10.00 0.00
August 688.71 06-AUG-14:31 6.72 50.40 27.83 0.00 0.00 0.00 0.00 15.61 0.00
September 681.52 10-SEP-12:31 6.72 50.40 27.83 0.00 0.00 0.00 0.00 14.60 0.00
October 599.30 08-OCT-14:31 5.38 40.32 22.26 0.00 0.00 0.00 0.00 9.64 0.00
November 259.64 03-NOV-13:50 12.10 45.36 5.57 0.00 0.00 0.00 0.00 4.80 0.00
December 216.80 01-DEC-14:10 24.19 90.72 11.13 0.00 0.00 0.00 0.00 1.20 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 178.14   4.03 20.16 4.45 0.00 0.00 0.00 0.00 1.20 0.00
Maximum of Months 695.88   24.19 90.72 27.83 0.00 0.00 0.00 0.00 15.61 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 3374.11 27-JAN-07:01 3629.15 2268.00 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
February 3387.37 24-FEB-07:01 3629.15 2268.00 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
March 3391.80 15-MAR-06:01 3629.15 2268.00 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
April 3063.80 19-APR-06:01 2903.32 1814.40 13311.90 0.00 0.00 0.00 0.00 0.00 0.00
May 3054.76 08-MAY-05:01 1411.34 1058.40 11647.91 0.00 0.00 0.00 0.00 0.00 0.00
June 2849.75 06-JUN-05:02 1209.72 907.20 9983.93 0.00 0.00 0.00 0.00 0.00 0.00
July 2622.70 18-JUL-05:12 1008.10 756.00 8319.94 0.00 0.00 0.00 0.00 0.00 0.00
August 2627.98 14-AUG-05:12 1008.10 756.00 8319.94 0.00 0.00 0.00 0.00 0.00 0.00
September 2611.91 27-SEP-05:12 1008.10 756.00 8319.94 0.00 0.00 0.00 0.00 0.00 0.00
October 2839.93 26-OCT-05:02 1209.72 907.20 9983.93 0.00 0.00 0.00 0.00 0.00 0.00
November 3348.24 13-NOV-07:01 3629.15 2268.00 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
December 3388.63 12-DEC-07:01 3629.15 2268.00 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2611.91   1008.10 756.00 8319.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3391.80   3629.15 2268.00 16639.88 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 843.87 24-JAN-07:01 793.80 1266.48 582.99 0.00 0.00 0.00 0.00 0.00 0.00
February 841.80 23-FEB-07:01 714.42 1139.83 524.69 0.00 0.00 0.00 0.00 0.00 0.00
March 842.28 01-MAR-07:01 793.80 1266.48 582.99 0.00 0.00 0.00 0.00 0.00 0.00
April 830.75 19-APR-06:01 635.04 1013.19 466.39 0.00 0.00 0.00 0.00 0.00 0.00
May 818.23 12-MAY-06:02 396.90 633.24 291.50 0.00 0.00 0.00 0.00 0.00 0.00
June 829.61 16-JUN-06:01 635.04 1013.19 466.39 0.00 0.00 0.00 0.00 0.00 0.00
July 822.89 05-JUL-06:01 635.04 1013.19 466.39 0.00 0.00 0.00 0.00 0.00 0.00
August 828.34 02-AUG-06:01 635.04 1013.19 466.39 0.00 0.00 0.00 0.00 0.00 0.00
September 825.83 01-SEP-06:01 555.66 886.54 408.09 0.00 0.00 0.00 0.00 0.00 0.00
October 834.63 02-OCT-06:01 635.04 1013.19 466.39 0.00 0.00 0.00 0.00 0.00 0.00
November 837.29 27-NOV-07:01 793.80 1266.48 582.99 0.00 0.00 0.00 0.00 0.00 0.00
December 844.21 12-DEC-07:02 793.80 1266.48 582.99 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 818.23   396.90 633.24 291.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 844.21   793.80 1266.48 582.99 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 9017.17 25-JAN-07:01 9504.92 5939.99 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
February 8556.94 03-FEB-07:01 9504.92 5939.99 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
March 8932.78 16-MAR-06:01 9504.92 5939.99 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
April 7917.75 19-APR-06:01 7603.94 4752.00 34864.50 0.00 0.00 0.00 0.00 0.00 0.00
May 7529.40 08-MAY-05:01 3696.36 2772.00 30506.44 0.00 0.00 0.00 0.00 0.00 0.00
June 7078.00 06-JUN-05:02 3168.31 2376.00 26148.38 0.00 0.00 0.00 0.00 0.00 0.00
July 6864.46 07-JUL-05:12 2640.26 1980.00 21790.31 0.00 0.00 0.00 0.00 0.00 0.00
August 6704.05 14-AUG-05:12 2640.26 1980.00 21790.31 0.00 0.00 0.00 0.00 0.00 0.00
September 6817.67 27-SEP-05:12 2640.26 1980.00 21790.31 0.00 0.00 0.00 0.00 0.00 0.00
October 7193.05 23-OCT-05:02 3168.31 2376.00 26148.38 0.00 0.00 0.00 0.00 0.00 0.00
November 8608.30 13-NOV-07:01 9504.92 5939.99 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
December 8704.33 15-DEC-07:01 9504.92 5939.99 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6704.05   2640.26 1980.00 21790.31 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9017.17   9504.92 5939.99 43580.63 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 357.91 28-JAN-06:01 64.80 48.60 64.25 0.00 0.00 0.00 0.00 0.00 0.73
February 356.67 09-FEB-03:01 0.00 48.60 64.25 0.00 0.00 0.00 0.00 0.00 4.03
March 357.59 23-MAR-02:11 0.00 48.60 64.25 0.00 0.00 0.00 0.00 0.00 1.92
April 362.87 23-APR-05:31 16.20 24.30 64.25 0.00 0.00 0.00 0.00 0.73 0.00
May 361.58 28-MAY-04:21 0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.28 0.00
June 357.91 18-JUN-07:11 16.20 48.60 107.08 0.00 0.00 0.00 0.00 4.29 0.00
July 346.98 16-JUL-06:01 16.20 24.30 64.25 0.00 0.00 0.00 0.00 1.65 0.00
August 369.85 13-AUG-03:41 0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.22 0.00
September 355.69 17-SEP-07:01 16.20 48.60 107.08 0.00 0.00 0.00 0.00 0.84 0.00
October 364.83 22-OCT-07:01 16.20 48.60 107.08 0.00 0.00 0.00 0.00 0.00 0.04
November 363.29 05-NOV-00:01 0.00 24.30 64.25 0.00 0.00 0.00 0.00 1.63 0.00
December 366.68 24-DEC-06:31 16.20 24.30 64.25 0.00 0.00 0.00 0.00 0.00 0.15
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 346.98   0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 369.85   64.80 48.60 107.08 0.00 0.00 0.00 0.00 4.29 4.03



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1435.87 23-JAN-06:12 819.00 546.00 1802.82 0.00 0.00 0.00 0.00 0.00 0.00
February 1437.81 06-FEB-06:12 819.00 546.00 1802.82 0.00 0.00 0.00 0.00 0.00 0.00
March 1431.90 21-MAR-05:12 982.80 655.20 2163.38 0.00 0.00 0.00 0.00 0.00 0.00
April 1335.41 19-APR-06:01 2358.71 1310.40 2884.51 0.00 0.00 0.00 0.00 0.00 0.00
May 1303.37 12-MAY-06:02 1474.19 819.00 1802.82 0.00 0.00 0.00 0.00 0.00 0.00
June 1323.76 16-JUN-06:01 2358.71 1310.40 2884.51 0.00 0.00 0.00 0.00 0.00 0.00
July 1307.40 13-JUL-06:02 1769.03 982.80 2163.38 0.00 0.00 0.00 0.00 0.00 0.00
August 1323.48 09-AUG-06:01 2358.71 1310.40 2884.51 0.00 0.00 0.00 0.00 0.00 0.00
September 1316.50 01-SEP-06:01 2063.87 1146.60 2523.95 0.00 0.00 0.00 0.00 0.00 0.00
October 1307.91 02-OCT-06:01 2358.71 1310.40 2884.51 0.00 0.00 0.00 0.00 0.00 0.00
November 1445.47 27-NOV-06:12 982.80 655.20 2163.38 0.00 0.00 0.00 0.00 0.00 0.00
December 1434.34 22-DEC-06:12 819.00 546.00 1802.82 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1303.37   819.00 546.00 1802.82 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1445.47   2358.71 1310.40 2884.51 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2332.88 27-JAN-07:01 2678.40 4273.30 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
February 2315.94 23-FEB-07:01 2410.56 3845.97 1770.39 0.00 0.00 0.00 0.00 0.00 0.00
March 2323.13 02-MAR-07:01 2142.72 3418.64 1573.68 0.00 0.00 0.00 0.00 0.00 0.00
April 1355.33 20-APR-06:03 1071.36 1709.32 786.84 0.00 0.00 0.00 0.00 0.00 0.00
May 940.93 26-MAY-06:03 1071.36 1709.32 786.84 0.00 0.00 0.00 0.00 0.00 0.00
June 793.53 22-JUN-17:00 267.84 427.33 196.71 0.00 0.00 0.00 0.00 0.00 0.00
July 777.95 27-JUL-17:00 267.84 427.33 196.71 0.00 0.00 0.00 0.00 0.00 0.00
August 848.47 31-AUG-16:03 1874.88 2991.31 1376.97 0.00 0.00 0.00 0.00 0.00 0.00
September 850.24 28-SEP-16:03 1874.88 2991.31 1376.97 0.00 0.00 0.00 0.00 0.00 0.00
October 1028.93 20-OCT-06:03 1071.36 1709.32 786.84 0.00 0.00 0.00 0.00 0.00 0.00
November 2257.45 27-NOV-07:01 2678.40 4273.30 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
December 2312.65 14-DEC-07:01 1874.88 2991.31 1376.97 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 777.95   267.84 427.33 196.71 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2332.88   2678.40 4273.30 1967.10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 301.38 24-JAN-07:01 116.64 437.40 53.66 0.00 0.00 0.00 0.00 0.00 0.00
February 299.72 03-FEB-07:02 116.64 437.40 53.66 0.00 0.00 0.00 0.00 0.00 0.00
March 300.79 22-MAR-06:02 116.64 437.40 53.66 0.00 0.00 0.00 0.00 0.00 0.00
April 291.73 19-APR-06:01 93.31 349.92 42.93 0.00 0.00 0.00 0.00 0.00 0.00
May 238.36 12-MAY-06:02 58.32 218.70 26.83 0.00 0.00 0.00 0.00 0.00 0.00
June 274.10 15-JUN-06:01 104.98 393.66 48.30 0.00 0.00 0.00 0.00 0.00 0.00
July 255.73 14-JUL-06:01 104.98 393.66 48.30 0.00 0.00 0.00 0.00 0.00 0.00
August 274.72 11-AUG-06:01 104.98 393.66 48.30 0.00 0.00 0.00 0.00 0.00 0.00
September 247.40 22-SEP-06:01 104.98 393.66 48.30 0.00 0.00 0.00 0.00 0.00 0.00
October 233.87 04-OCT-06:01 93.31 349.92 42.93 0.00 0.00 0.00 0.00 0.00 0.00
November 300.33 13-NOV-07:01 116.64 437.40 53.66 0.00 0.00 0.00 0.00 0.00 0.00
December 301.08 15-DEC-07:01 116.64 437.40 53.66 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 233.87   58.32 218.70 26.83 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 301.38   116.64 437.40 53.66 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1891.34 23-JAN-06:12 1174.50 783.00 2585.36 0.00 0.00 0.00 0.00 0.00 0.00
February 1899.70 03-FEB-06:12 1409.39 939.60 3102.44 0.00 0.00 0.00 0.00 0.00 0.00
March 1879.36 21-MAR-05:12 1409.39 939.60 3102.44 0.00 0.00 0.00 0.00 0.00 0.00
April 1770.90 19-APR-06:01 3382.55 1879.20 4136.58 0.00 0.00 0.00 0.00 0.00 0.00
May 1731.95 12-MAY-06:02 2114.09 1174.50 2585.36 0.00 0.00 0.00 0.00 0.00 0.00
June 1757.90 16-JUN-06:01 3382.55 1879.20 4136.58 0.00 0.00 0.00 0.00 0.00 0.00
July 1737.13 13-JUL-06:02 2536.91 1409.40 3102.44 0.00 0.00 0.00 0.00 0.00 0.00
August 1757.41 09-AUG-06:01 3382.55 1879.20 4136.58 0.00 0.00 0.00 0.00 0.00 0.00
September 1749.62 01-SEP-06:01 2959.73 1644.30 3619.51 0.00 0.00 0.00 0.00 0.00 0.00
October 1733.39 02-OCT-06:01 3382.55 1879.20 4136.58 0.00 0.00 0.00 0.00 0.00 0.00
November 1898.00 27-NOV-06:12 1409.39 939.60 3102.44 0.00 0.00 0.00 0.00 0.00 0.00
December 1893.54 22-DEC-06:12 1174.50 783.00 2585.36 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1731.95   1174.50 783.00 2585.36 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1899.70   3382.55 1879.20 4136.58 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 360.93 28-JAN-06:01 64.80 48.60 64.25 0.00 0.00 0.00 0.00 0.00 0.00
February 356.29 25-FEB-06:01 64.80 48.60 64.25 0.00 0.00 0.00 0.00 0.00 0.00
March 356.35 18-MAR-05:01 64.80 48.60 64.25 0.00 0.00 0.00 0.00 0.00 0.00
April 332.37 19-APR-03:11 0.00 145.80 107.08 0.00 0.00 0.00 0.00 0.00 0.00
May 324.51 28-MAY-04:21 0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.00 0.00
June 309.42 25-JUN-06:41 16.20 24.30 64.25 0.00 0.00 0.00 0.00 0.00 0.00
July 294.39 16-JUL-06:01 16.20 24.30 64.25 0.00 0.00 0.00 0.00 0.00 0.00
August 319.29 13-AUG-03:41 0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.00 0.00
September 303.36 17-SEP-07:01 16.20 48.60 107.08 0.00 0.00 0.00 0.00 0.00 0.00
October 326.52 22-OCT-07:01 16.20 48.60 107.08 0.00 0.00 0.00 0.00 0.00 0.00
November 339.76 13-NOV-04:11 0.00 145.80 107.08 0.00 0.00 0.00 0.00 0.00 0.00
December 358.53 15-DEC-04:11 0.00 145.80 107.08 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 294.39   0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 360.93   64.80 145.80 107.08 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2545.65 23-JAN-06:12 724.57 1593.90 2631.09 0.00 0.00 0.00 0.00 0.00 0.00
February 2559.78 03-FEB-06:12 869.48 1912.68 3157.31 0.00 0.00 0.00 0.00 0.00 0.00
March 2532.92 21-MAR-05:12 869.48 1912.68 3157.31 0.00 0.00 0.00 0.00 0.00 0.00
April 2410.82 19-APR-06:02 2086.76 3825.36 4209.75 0.00 0.00 0.00 0.00 0.00 0.00
May 2370.01 12-MAY-06:02 1304.23 2390.85 2631.09 0.00 0.00 0.00 0.00 0.00 0.00
June 2432.72 23-JUN-06:02 2086.76 3825.36 4209.75 0.00 0.00 0.00 0.00 0.00 0.00
July 2432.39 14-JUL-06:02 2347.61 4303.53 4735.96 0.00 0.00 0.00 0.00 0.00 0.00
August 2432.44 17-AUG-06:02 2347.61 4303.53 4735.96 0.00 0.00 0.00 0.00 0.00 0.00
September 2424.99 22-SEP-06:02 2347.61 4303.53 4735.96 0.00 0.00 0.00 0.00 0.00 0.00
October 2431.33 04-OCT-06:02 2086.76 3825.36 4209.75 0.00 0.00 0.00 0.00 0.00 0.00
November 2583.11 27-NOV-06:12 869.48 1912.68 3157.31 0.00 0.00 0.00 0.00 0.00 0.00
December 2543.33 22-DEC-06:12 724.57 1593.90 2631.09 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2370.01   724.57 1593.90 2631.09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2583.11   2347.61 4303.53 4735.96 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15770.21 25-JAN-06:01 5520.54 6071.99 18226.32 16089.88 0.00 0.00 0.00 0.00 15.10
February 14876.27 03-FEB-06:01 5520.54 6071.99 18226.32 16089.88 0.00 0.00 0.00 0.00 25.87
March 15803.88 16-MAR-05:01 5520.54 6071.99 18226.32 16089.88 0.00 0.00 0.00 0.00 24.66
April 13391.14 19-APR-05:01 5520.54 6071.99 18226.32 16089.88 0.00 0.00 0.00 0.00 4.40
May 12038.56 14-MAY-05:01 496.85 455.40 4921.11 4344.27 0.00 0.00 0.00 18.36 0.00
June 12127.35 25-JUN-05:01 441.64 404.80 4374.32 3861.57 0.00 0.00 0.00 16.31 0.00
July 12417.89 04-JUL-05:01 552.05 506.00 5467.90 4826.96 0.00 0.00 0.00 7.10 0.00
August 12229.82 06-AUG-05:01 441.64 404.80 4374.32 3861.57 0.00 0.00 0.00 8.42 0.00
September 12389.30 10-SEP-05:01 441.64 404.80 4374.32 3861.57 0.00 0.00 0.00 0.00 0.00
October 12382.69 22-OCT-05:01 441.64 404.80 4374.32 3861.57 0.00 0.00 0.00 8.36 0.00
November 14792.63 13-NOV-06:01 5520.54 6071.99 18226.32 16089.88 0.00 0.00 0.00 0.00 17.64
December 15431.86 15-DEC-06:01 5520.54 6071.99 18226.32 16089.88 0.00 0.00 0.00 0.00 30.17
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 12038.56   441.64 404.80 4374.32 3861.57 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15803.88   5520.54 6071.99 18226.32 16089.88 0.00 0.00 0.00 18.36 30.17



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16406.83 25-JAN-06:01 5760.56 6335.99 19018.77 16789.44 0.00 0.00 0.00 0.00 8.46
February 15525.21 03-FEB-06:01 5760.56 6335.99 19018.77 16789.44 0.00 0.00 0.00 0.00 14.51
March 16428.33 16-MAR-05:01 5760.56 6335.99 19018.77 16789.44 0.00 0.00 0.00 0.00 13.84
April 14073.71 19-APR-05:01 5760.56 6335.99 19018.77 16789.44 0.00 0.00 0.00 0.00 2.47
May 12817.41 07-MAY-05:01 460.84 422.40 4564.50 4029.47 0.00 0.00 0.00 2.79 0.00
June 12803.20 25-JUN-05:01 460.84 422.40 4564.50 4029.47 0.00 0.00 0.00 9.16 0.00
July 13169.87 04-JUL-05:01 576.06 528.00 5705.63 5036.83 0.00 0.00 0.00 4.02 0.00
August 12851.68 06-AUG-05:01 460.84 422.40 4564.50 4029.47 0.00 0.00 0.00 4.73 0.00
September 12936.57 10-SEP-05:01 460.84 422.40 4564.50 4029.47 0.00 0.00 0.00 0.00 0.00
October 12991.08 22-OCT-05:01 460.84 422.40 4564.50 4029.47 0.00 0.00 0.00 4.71 0.00
November 15457.50 13-NOV-06:01 5760.56 6335.99 19018.77 16789.44 0.00 0.00 0.00 0.00 9.90
December 16079.00 15-DEC-06:01 5760.56 6335.99 19018.77 16789.44 0.00 0.00 0.00 0.00 16.90
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 12803.20   460.84 422.40 4564.50 4029.47 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16428.33   5760.56 6335.99 19018.77 16789.44 0.00 0.00 0.00 9.16 16.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16315.29 25-JAN-06:01 5712.56 6283.19 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00
February 15445.65 03-FEB-06:01 5712.56 6283.19 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00
March 16346.09 16-MAR-05:01 5712.56 6283.19 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00
April 14054.38 19-APR-05:01 5712.56 6283.19 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00
May 13044.27 07-MAY-05:01 457.00 418.88 4526.47 3995.89 0.00 0.00 0.00 0.00 0.00
June 12827.34 25-JUN-05:01 457.00 418.88 4526.47 3995.89 0.00 0.00 0.00 0.00 0.00
July 13301.14 04-JUL-05:01 571.26 523.60 5658.08 4994.86 0.00 0.00 0.00 0.00 0.00
August 12809.72 06-AUG-05:01 457.00 418.88 4526.47 3995.89 0.00 0.00 0.00 0.00 0.00
September 12883.76 04-SEP-05:01 457.00 418.88 4526.47 3995.89 0.00 0.00 0.00 0.00 0.00
October 12971.75 22-OCT-05:01 457.00 418.88 4526.47 3995.89 0.00 0.00 0.00 0.00 0.00
November 15408.51 13-NOV-06:01 5712.56 6283.19 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00
December 16012.87 15-DEC-06:01 5712.56 6283.19 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00
Minimum of Months 12809.72   457.00 418.88 4526.47 3995.89 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16346.09   5712.56 6283.19 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 PACU

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1037.85 27-JAN-04:21 0.00 259.20 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
February 1015.47 24-FEB-04:11 0.00 259.20 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
March 1016.38 03-MAR-04:11 0.00 259.20 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
April 959.75 19-APR-03:11 0.00 259.20 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
May 925.81 28-MAY-04:21 0.00 43.20 962.68 0.00 0.00 0.00 0.00 0.00 0.00
June 891.20 25-JUN-06:41 129.61 43.20 962.68 0.00 0.00 0.00 0.00 0.00 0.00
July 850.75 16-JUL-01:51 0.00 43.20 962.68 0.00 0.00 0.00 0.00 0.00 0.00
August 912.10 13-AUG-03:41 0.00 43.20 962.68 0.00 0.00 0.00 0.00 0.00 0.00
September 878.67 17-SEP-07:01 129.61 86.40 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
October 936.58 22-OCT-07:01 129.61 86.40 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
November 993.70 27-NOV-06:01 1296.13 518.40 3208.92 0.00 0.00 0.00 0.00 0.00 0.00
December 1031.55 15-DEC-04:11 0.00 259.20 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 850.75   0.00 43.20 962.68 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1037.85   1296.13 518.40 3208.92 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2434.29 24-JAN-07:02 2851.20 4549.00 2094.01 0.00 0.00 0.00 0.00 0.00 0.00
February 2422.10 24-FEB-07:02 2851.20 4549.00 2094.01 0.00 0.00 0.00 0.00 0.00 0.00
March 2419.66 01-MAR-07:02 2851.20 4549.00 2094.01 0.00 0.00 0.00 0.00 0.00 0.00
April 2347.95 19-APR-06:01 2280.96 3639.20 1675.21 0.00 0.00 0.00 0.00 0.00 0.00
May 1976.48 12-MAY-06:02 1425.60 2274.50 1047.00 0.00 0.00 0.00 0.00 0.00 0.00
June 2283.51 16-JUN-06:01 2280.96 3639.20 1675.21 0.00 0.00 0.00 0.00 0.00 0.00
July 2183.84 21-JUL-06:01 2280.96 3639.20 1675.21 0.00 0.00 0.00 0.00 0.00 0.00
August 2257.13 11-AUG-06:01 2566.08 4094.10 1884.61 0.00 0.00 0.00 0.00 0.00 0.00
September 2201.73 01-SEP-06:01 1995.84 3184.30 1465.81 0.00 0.00 0.00 0.00 0.00 0.00
October 2124.97 03-OCT-06:01 2280.96 3639.20 1675.21 0.00 0.00 0.00 0.00 0.00 0.00
November 2387.73 13-NOV-07:01 2851.20 4549.00 2094.01 0.00 0.00 0.00 0.00 0.00 0.00
December 2422.49 20-DEC-07:02 2851.20 4549.00 2094.01 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1976.48   1425.60 2274.50 1047.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2434.29   2851.20 4549.00 2094.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1387.36 24-JAN-04:11 0.00 396.90 1872.16 0.00 0.00 0.00 0.00 0.00 6.24
February 1376.28 23-FEB-04:11 0.00 396.90 1872.16 0.00 0.00 0.00 0.00 0.00 4.97
March 1374.99 03-MAR-04:11 0.00 396.90 1872.16 0.00 0.00 0.00 0.00 0.00 2.86
April 1339.05 09-APR-07:11 113.41 132.30 1872.16 0.00 0.00 0.00 0.00 0.00 0.17
May 1308.05 28-MAY-04:21 0.00 66.15 1123.30 0.00 0.00 0.00 0.00 0.11 0.00
June 1277.40 18-JUN-07:11 113.41 132.30 1872.16 0.00 0.00 0.00 0.00 2.68 0.00
July 1242.72 16-JUL-01:51 0.00 66.15 1123.30 0.00 0.00 0.00 0.00 0.29 0.00
August 1308.38 13-AUG-03:41 0.00 66.15 1123.30 0.00 0.00 0.00 0.00 0.14 0.00
September 1279.46 17-SEP-07:01 113.41 132.30 1872.16 0.00 0.00 0.00 0.00 0.48 0.00
October 1335.07 22-OCT-07:01 113.41 132.30 1872.16 0.00 0.00 0.00 0.00 0.00 0.12
November 1368.70 27-NOV-06:01 1134.11 793.80 3744.32 0.00 0.00 0.00 0.00 0.00 1.25
December 1372.28 14-DEC-04:11 0.00 396.90 1872.16 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1242.72   0.00 66.15 1123.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1387.36   1134.11 793.80 3744.32 0.00 0.00 0.00 0.00 2.68 6.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2597.50 26-JAN-04:21 0.00 709.80 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
February 2556.88 06-FEB-06:01 2028.20 1419.60 6696.19 0.00 0.00 0.00 0.00 0.00 0.00
March 2561.04 22-MAR-03:11 0.00 709.80 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
April 2448.43 19-APR-03:11 0.00 709.80 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
May 2385.58 28-MAY-04:21 0.00 118.30 2008.86 0.00 0.00 0.00 0.00 0.00 0.00
June 2311.03 25-JUN-06:41 202.82 118.30 2008.86 0.00 0.00 0.00 0.00 0.00 0.00
July 2220.50 16-JUL-01:51 0.00 118.30 2008.86 0.00 0.00 0.00 0.00 0.00 0.00
August 2356.40 13-AUG-03:41 0.00 118.30 2008.86 0.00 0.00 0.00 0.00 0.00 0.00
September 2277.30 17-SEP-07:01 202.82 236.60 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
October 2395.74 22-OCT-07:01 202.82 236.60 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
November 2542.96 27-NOV-06:01 2028.20 1419.60 6696.19 0.00 0.00 0.00 0.00 0.00 0.00
December 2579.71 15-DEC-04:11 0.00 709.80 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2220.50   0.00 118.30 2008.86 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2597.50   2028.20 1419.60 6696.19 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 354.14 13-JAN-00:11 0.00 48.60 64.25 0.00 0.00 0.00 0.00 0.00 0.30
February 355.60 28-FEB-04:11 0.00 145.80 107.08 0.00 0.00 0.00 0.00 0.00 0.44
March 356.69 14-MAR-01:11 0.00 48.60 64.25 0.00 0.00 0.00 0.00 1.30 0.00
April 356.42 12-APR-20:21 0.00 145.80 64.25 0.00 0.00 0.00 0.00 2.88 0.00
May 349.27 01-MAY-23:11 0.00 48.60 64.25 0.00 0.00 0.00 0.00 0.43 0.00
June 346.77 18-JUN-02:11 0.00 24.30 64.25 0.00 0.00 0.00 0.00 2.31 0.00
July 342.68 28-JUL-18:42 0.00 174.96 64.25 0.00 0.00 0.00 0.00 5.14 0.00
August 355.28 13-AUG-03:41 0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.24 0.00
September 350.69 17-SEP-07:01 16.20 48.60 107.08 0.00 0.00 0.00 0.00 0.78 0.00
October 363.19 22-OCT-07:01 16.20 48.60 107.08 0.00 0.00 0.00 0.00 0.00 0.12
November 356.79 07-NOV-02:31 0.00 48.60 64.25 0.00 0.00 0.00 0.00 0.00 0.24
December 360.08 04-DEC-04:11 0.00 145.80 107.08 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 342.68   0.00 24.30 64.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 363.19   16.20 174.96 107.08 0.00 0.00 0.00 0.00 5.14 0.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4767.13 05-JAN-21:31 0.00 1282.50 2540.40 0.00 0.00 0.00 0.00 0.00 3.00
February 4780.28 01-FEB-23:51 0.00 427.50 2540.40 0.00 0.00 0.00 0.00 0.36 0.00
March 4868.09 03-MAR-04:11 0.00 1282.50 4233.99 0.00 0.00 0.00 0.00 0.00 10.12
April 4821.44 23-APR-05:31 342.03 213.75 2540.40 0.00 0.00 0.00 0.00 2.23 0.00
May 4797.27 28-MAY-04:21 0.00 213.75 2540.40 0.00 0.00 0.00 0.00 0.88 0.00
June 4805.75 18-JUN-07:11 342.03 427.50 4233.99 0.00 0.00 0.00 0.00 12.91 0.00
July 4569.04 16-JUL-01:51 0.00 213.75 2540.40 0.00 0.00 0.00 0.00 1.45 0.00
August 4861.13 13-AUG-03:41 0.00 213.75 2540.40 0.00 0.00 0.00 0.00 0.72 0.00
September 4703.08 10-SEP-07:11 342.03 427.50 4233.99 0.00 0.00 0.00 0.00 5.63 0.00
October 4798.25 22-OCT-07:01 342.03 427.50 4233.99 0.00 0.00 0.00 0.00 0.00 0.02
November 4840.56 26-NOV-08:11 342.03 427.50 4233.99 0.00 0.00 0.00 0.00 0.00 11.12
December 4839.47 24-DEC-06:31 342.03 213.75 2540.40 0.00 0.00 0.00 0.00 0.00 0.44
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4569.04   0.00 213.75 2540.40 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4868.09   342.03 1282.50 4233.99 0.00 0.00 0.00 0.00 12.91 11.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3797.52 17-JAN-07:01 16493.20 5955.29 5545.45 0.00 0.00 0.00 0.00 0.00 3.20
February 4035.27 21-FEB-06:12 4581.45 1985.10 2772.72 0.00 0.00 0.00 0.00 0.00 3.43
March 3796.40 01-MAR-07:01 16493.20 5955.29 5545.45 0.00 0.00 0.00 0.00 0.00 2.59
April 3770.28 19-APR-06:01 13194.56 4764.24 4436.36 0.00 0.00 0.00 0.00 0.00 2.41
May 4182.80 13-MAY-04:01 0.00 661.70 1663.63 0.00 0.00 0.00 0.00 2.22 0.00
June 3823.55 08-JUN-06:02 14843.88 5359.76 4990.90 0.00 0.00 0.00 0.00 2.08 0.00
July 3821.60 14-JUL-06:02 14843.88 5359.76 4990.90 0.00 0.00 0.00 0.00 0.91 0.00
August 3820.66 15-AUG-06:02 14843.88 5359.76 4990.90 0.00 0.00 0.00 0.00 2.62 0.00
September 3820.37 22-SEP-06:02 14843.88 5359.76 4990.90 0.00 0.00 0.00 0.00 1.55 0.00
October 4178.32 07-OCT-04:01 0.00 661.70 1663.63 0.00 0.00 0.00 0.00 0.78 0.00
November 4026.33 27-NOV-06:12 5497.73 2382.12 3327.27 0.00 0.00 0.00 0.00 0.00 3.88
December 4017.47 05-DEC-06:12 4581.45 1985.10 2772.72 0.00 0.00 0.00 0.00 0.00 0.54
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3770.28   0.00 661.70 1663.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4182.80   16493.20 5955.29 5545.45 0.00 0.00 0.00 0.00 2.62 3.88



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 651.46 24-JAN-07:02 691.20 1102.79 507.64 0.00 0.00 0.00 0.00 0.00 0.00
February 648.00 24-FEB-07:02 691.20 1102.79 507.64 0.00 0.00 0.00 0.00 0.00 0.00
March 647.82 01-MAR-07:01 691.20 1102.79 507.64 0.00 0.00 0.00 0.00 0.00 0.00
April 631.94 19-APR-06:01 552.96 882.23 406.11 0.00 0.00 0.00 0.00 0.00 0.00
May 602.05 12-MAY-06:02 345.60 551.39 253.82 0.00 0.00 0.00 0.00 0.00 0.00
June 615.59 16-JUN-06:01 552.96 882.23 406.11 0.00 0.00 0.00 0.00 0.00 0.00
July 605.18 19-JUL-06:01 483.84 771.95 355.35 0.00 0.00 0.00 0.00 0.00 0.00
August 616.25 31-AUG-06:01 483.84 771.95 355.35 0.00 0.00 0.00 0.00 0.00 0.00
September 614.82 01-SEP-06:01 483.84 771.95 355.35 0.00 0.00 0.00 0.00 0.00 0.00
October 612.20 02-OCT-06:01 552.96 882.23 406.11 0.00 0.00 0.00 0.00 0.00 0.00
November 649.52 13-NOV-07:01 691.20 1102.79 507.64 0.00 0.00 0.00 0.00 0.00 0.00
December 649.29 20-DEC-07:02 691.20 1102.79 507.64 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 602.05   345.60 551.39 253.82 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 651.46   691.20 1102.79 507.64 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4766.75 01-JAN-08:11 648.06 432.00 8022.30 0.00 0.00 0.00 0.00 0.00 21.70
February 4711.48 05-FEB-16:21 648.06 432.00 8022.30 0.00 0.00 0.00 0.00 0.00 42.22
March 4639.30 12-MAR-11:01 583.26 388.80 7220.07 0.00 0.00 0.00 0.00 0.00 9.63
April 4375.56 23-APR-05:31 648.06 216.00 4813.38 0.00 0.00 0.00 0.00 0.00 0.79
May 4309.98 28-MAY-04:21 0.00 216.00 4813.38 0.00 0.00 0.00 0.00 0.91 0.00
June 4351.09 18-JUN-07:11 648.06 432.00 8022.30 0.00 0.00 0.00 0.00 24.15 0.00
July 4179.58 15-JUL-23:51 0.00 216.00 4813.38 0.00 0.00 0.00 0.00 8.70 0.00
August 4393.63 13-AUG-03:41 0.00 216.00 4813.38 0.00 0.00 0.00 0.00 1.34 0.00
September 4453.48 10-SEP-12:31 648.06 432.00 8022.30 0.00 0.00 0.00 0.00 68.75 0.00
October 4543.52 22-OCT-07:01 648.06 432.00 8022.30 0.00 0.00 0.00 0.00 0.00 2.70
November 4752.13 26-NOV-09:51 583.26 388.80 7220.07 0.00 0.00 0.00 0.00 0.00 62.12
December 4874.22 31-DEC-13:28 583.26 388.80 7220.07 0.00 0.00 0.00 0.00 0.00 17.25
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4179.58   0.00 216.00 4813.38 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4874.22   648.06 432.00 8022.30 0.00 0.00 0.00 0.00 68.75 62.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 726.77 17-JAN-07:01 642.66 1178.10 1296.48 0.00 0.00 0.00 0.00 0.00 1.70
February 726.92 21-FEB-07:01 514.13 942.48 1037.18 0.00 0.00 0.00 0.00 0.00 1.81
March 722.17 01-MAR-07:01 642.66 1178.10 1296.48 0.00 0.00 0.00 0.00 0.00 1.37
April 701.95 12-APR-06:02 321.33 589.05 648.24 0.00 0.00 0.00 0.00 0.67 0.00
May 698.12 12-MAY-06:02 321.33 589.05 648.24 0.00 0.00 0.00 0.00 0.67 0.00
June 709.51 16-JUN-06:01 514.13 942.48 1037.18 0.00 0.00 0.00 0.00 1.10 0.00
July 702.22 13-JUL-06:02 385.60 706.86 777.89 0.00 0.00 0.00 0.00 0.43 0.00
August 712.48 31-AUG-06:01 449.86 824.67 907.54 0.00 0.00 0.00 0.00 0.31 0.00
September 714.73 01-SEP-06:01 449.86 824.67 907.54 0.00 0.00 0.00 0.00 0.50 0.00
October 716.81 02-OCT-06:01 514.13 942.48 1037.18 0.00 0.00 0.00 0.00 1.20 0.00
November 723.06 27-NOV-07:01 642.66 1178.10 1296.48 0.00 0.00 0.00 0.00 0.00 1.90
December 722.96 14-DEC-07:01 449.86 824.67 907.54 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 698.12   321.33 589.05 648.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 726.92   642.66 1178.10 1296.48 0.00 0.00 0.00 0.00 1.20 1.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 SCRUB

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 418.33 05-JAN-07:01 317.52 506.59 233.20 0.00 0.00 0.00 0.00 0.00 0.00
February 417.57 23-FEB-07:01 408.24 651.33 299.82 0.00 0.00 0.00 0.00 0.00 0.00
March 419.26 01-MAR-07:01 453.60 723.70 333.14 0.00 0.00 0.00 0.00 0.00 0.00
April 416.18 19-APR-06:01 362.88 578.96 266.51 0.00 0.00 0.00 0.00 0.00 0.00
May 409.55 19-MAY-06:02 226.80 361.85 166.57 0.00 0.00 0.00 0.00 0.00 0.00
June 421.24 16-JUN-06:01 362.88 578.96 266.51 0.00 0.00 0.00 0.00 0.00 0.00
July 420.80 13-JUL-06:02 272.16 434.22 199.88 0.00 0.00 0.00 0.00 0.00 0.00
August 423.77 02-AUG-06:01 362.88 578.96 266.51 0.00 0.00 0.00 0.00 0.00 0.00
September 423.54 01-SEP-06:01 317.52 506.59 233.20 0.00 0.00 0.00 0.00 0.00 0.00
October 404.15 30-OCT-06:01 362.88 578.96 266.51 0.00 0.00 0.00 0.00 0.00 0.00
November 417.97 30-NOV-07:02 272.16 434.22 199.88 0.00 0.00 0.00 0.00 0.00 0.00
December 414.82 12-DEC-07:01 453.60 723.70 333.14 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 404.15   226.80 361.85 166.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 423.77   453.60 723.70 333.14 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 SOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1161.32 26-JAN-04:21 0.00 567.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
February 1136.43 25-FEB-06:01 604.86 189.00 748.86 0.00 0.00 0.00 0.00 0.00 0.00
March 1140.06 18-MAR-05:01 604.86 189.00 748.86 0.00 0.00 0.00 0.00 0.00 0.00
April 1081.13 19-APR-03:11 0.00 567.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
May 1042.99 28-MAY-04:21 0.00 94.50 748.86 0.00 0.00 0.00 0.00 0.00 0.00
June 1005.17 25-JUN-06:41 151.21 94.50 748.86 0.00 0.00 0.00 0.00 0.00 0.00
July 956.54 16-JUL-01:51 0.00 94.50 748.86 0.00 0.00 0.00 0.00 0.00 0.00
August 1028.94 13-AUG-03:41 0.00 94.50 748.86 0.00 0.00 0.00 0.00 0.00 0.00
September 986.13 17-SEP-07:01 151.21 189.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
October 1048.64 22-OCT-07:01 151.21 189.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
November 1112.27 27-NOV-06:01 1512.15 1134.00 2496.21 0.00 0.00 0.00 0.00 0.00 0.00
December 1152.06 15-DEC-04:11 0.00 567.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 956.54   0.00 94.50 748.86 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1161.32   1512.15 1134.00 2496.21 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 487.12 08-JAN-08:21 67.21 84.00 554.71 0.00 0.00 0.00 0.00 0.00 0.00
February 487.46 24-FEB-04:11 0.00 252.00 554.71 0.00 0.00 0.00 0.00 0.00 0.00
March 493.70 15-MAR-03:11 0.00 252.00 554.71 0.00 0.00 0.00 0.00 0.00 0.00
April 493.38 19-APR-03:11 0.00 252.00 554.71 0.00 0.00 0.00 0.00 0.00 0.00
May 488.26 28-MAY-04:21 0.00 42.00 332.83 0.00 0.00 0.00 0.00 0.00 0.00
June 484.37 25-JUN-06:41 67.21 42.00 332.83 0.00 0.00 0.00 0.00 0.00 0.00
July 470.94 23-JUL-03:51 0.00 42.00 332.83 0.00 0.00 0.00 0.00 0.00 0.00
August 486.31 13-AUG-03:41 0.00 42.00 332.83 0.00 0.00 0.00 0.00 0.00 0.00
September 477.04 17-SEP-07:01 67.21 84.00 554.71 0.00 0.00 0.00 0.00 0.00 0.00
October 486.49 22-OCT-07:01 67.21 84.00 554.71 0.00 0.00 0.00 0.00 0.00 0.00
November 487.61 26-NOV-08:11 67.21 84.00 554.71 0.00 0.00 0.00 0.00 0.00 0.00
December 491.59 12-DEC-04:11 0.00 252.00 554.71 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 470.94   0.00 42.00 332.83 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 493.70   67.21 252.00 554.71 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1516.77 27-JAN-04:21 0.00 810.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
February 1486.94 24-FEB-04:11 0.00 810.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
March 1488.68 03-MAR-04:11 0.00 810.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
April 1413.93 19-APR-03:11 0.00 810.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
May 1361.38 28-MAY-04:21 0.00 135.00 1069.81 0.00 0.00 0.00 0.00 0.00 0.00
June 1316.03 25-JUN-06:41 216.02 135.00 1069.81 0.00 0.00 0.00 0.00 0.00 0.00
July 1259.41 16-JUL-01:51 0.00 135.00 1069.81 0.00 0.00 0.00 0.00 0.00 0.00
August 1344.22 13-AUG-03:41 0.00 135.00 1069.81 0.00 0.00 0.00 0.00 0.00 0.00
September 1296.53 17-SEP-07:01 216.02 270.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
October 1376.57 22-OCT-07:01 216.02 270.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
November 1444.50 27-NOV-06:01 2160.21 1620.00 3566.02 0.00 0.00 0.00 0.00 0.00 0.00
December 1507.82 15-DEC-04:11 0.00 810.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1259.41   0.00 135.00 1069.81 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1516.77   2160.21 1620.00 3566.02 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2617.75 02-JAN-14:30 648.06 216.00 891.37 0.00 0.00 0.00 0.00 5.88 0.00
February 2647.57 22-FEB-15:40 648.06 216.00 891.37 0.00 0.00 0.00 0.00 6.57 0.00
March 2369.12 01-MAR-16:00 648.06 216.00 891.37 0.00 0.00 0.00 0.00 3.64 0.00
April 2288.11 09-APR-13:51 324.03 216.00 4011.15 0.00 0.00 0.00 0.00 23.19 0.00
May 2228.59 28-MAY-04:21 0.00 120.00 2674.10 0.00 0.00 0.00 0.00 0.28 0.00
June 2288.78 18-JUN-07:11 360.04 240.00 4456.83 0.00 0.00 0.00 0.00 15.62 0.00
July 2279.50 04-JUL-15:51 360.04 240.00 4456.83 0.00 0.00 0.00 0.00 49.45 0.00
August 2387.71 31-AUG-15:00 648.06 216.00 891.37 0.00 0.00 0.00 0.00 12.71 0.00
September 2369.36 10-SEP-12:31 360.04 240.00 4456.83 0.00 0.00 0.00 0.00 51.48 0.00
October 2529.90 25-OCT-14:30 648.06 216.00 891.37 0.00 0.00 0.00 0.00 11.25 0.00
November 2755.84 07-NOV-15:00 648.06 216.00 891.37 0.00 0.00 0.00 0.00 2.85 0.00
December 2753.03 04-DEC-14:40 648.06 216.00 891.37 0.00 0.00 0.00 0.00 4.05 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2228.59   0.00 120.00 891.37 0.00 0.00 0.00 0.00 0.28 0.00
Maximum of Months 2755.84   648.06 240.00 4456.83 0.00 0.00 0.00 0.00 51.48 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2632.86 05-JAN-07:01 2328.48 3715.01 1710.11 0.00 0.00 0.00 0.00 0.00 0.00
February 2633.64 23-FEB-07:01 2993.76 4776.45 2198.71 0.00 0.00 0.00 0.00 0.00 0.00
March 2644.03 02-MAR-07:01 2661.12 4245.73 1954.41 0.00 0.00 0.00 0.00 0.00 0.00
April 2589.24 19-APR-06:01 2661.12 4245.73 1954.41 0.00 0.00 0.00 0.00 0.00 0.00
May 2460.42 12-MAY-06:02 1663.20 2653.58 1221.50 0.00 0.00 0.00 0.00 0.00 0.00
June 2612.66 16-JUN-06:01 2661.12 4245.73 1954.41 0.00 0.00 0.00 0.00 0.00 0.00
July 2603.28 13-JUL-06:02 1995.84 3184.30 1465.81 0.00 0.00 0.00 0.00 0.00 0.00
August 2615.44 31-AUG-06:01 2328.48 3715.01 1710.11 0.00 0.00 0.00 0.00 0.00 0.00
September 2623.17 01-SEP-06:01 2328.48 3715.01 1710.11 0.00 0.00 0.00 0.00 0.00 0.00
October 2601.01 13-OCT-06:02 1663.20 2653.58 1221.50 0.00 0.00 0.00 0.00 0.00 0.00
November 2621.56 30-NOV-07:02 1995.84 3184.30 1465.81 0.00 0.00 0.00 0.00 0.00 0.00
December 2619.19 14-DEC-07:01 2328.48 3715.01 1710.11 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2460.42   1663.20 2653.58 1221.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2644.03   2993.76 4776.45 2198.71 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1557.03 24-JAN-07:02 855.36 3207.60 393.54 0.00 0.00 0.00 0.00 0.00 0.00
February 1554.61 03-FEB-07:02 855.36 3207.60 393.54 0.00 0.00 0.00 0.00 0.00 0.00
March 1557.02 22-MAR-06:02 855.36 3207.60 393.54 0.00 0.00 0.00 0.00 0.00 0.00
April 1495.77 19-APR-06:01 684.29 2566.08 314.83 0.00 0.00 0.00 0.00 0.00 0.00
May 1393.02 12-MAY-06:02 427.68 1603.80 196.77 0.00 0.00 0.00 0.00 0.00 0.00
June 1454.76 16-JUN-06:01 684.29 2566.08 314.83 0.00 0.00 0.00 0.00 0.00 0.00
July 1379.58 21-JUL-06:01 684.29 2566.08 314.83 0.00 0.00 0.00 0.00 0.00 0.00
August 1437.86 31-AUG-06:01 598.75 2245.32 275.48 0.00 0.00 0.00 0.00 0.00 0.00
September 1389.52 01-SEP-06:01 598.75 2245.32 275.48 0.00 0.00 0.00 0.00 0.00 0.00
October 1301.66 04-OCT-06:01 684.29 2566.08 314.83 0.00 0.00 0.00 0.00 0.00 0.00
November 1530.77 13-NOV-07:02 855.36 3207.60 393.54 0.00 0.00 0.00 0.00 0.00 0.00
December 1556.52 21-DEC-07:02 855.36 3207.60 393.54 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1301.66   427.68 1603.80 196.77 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1557.03   855.36 3207.60 393.54 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1455.32 06-JAN-14:00 198.72 745.20 91.43 0.00 0.00 0.00 0.00 22.49 0.00
February 1724.85 17-FEB-13:50 198.72 745.20 91.43 0.00 0.00 0.00 0.00 21.90 0.00
March 2170.41 27-MAR-15:10 198.72 745.20 91.43 0.00 0.00 0.00 0.00 14.07 0.00
April 4573.03 16-APR-15:41 77.28 579.60 320.00 0.00 0.00 0.00 0.00 33.50 0.00
May 5859.67 14-MAY-14:31 99.36 745.20 411.43 0.00 0.00 0.00 0.00 35.96 0.00
June 6099.97 11-JUN-15:51 99.36 745.20 411.43 0.00 0.00 0.00 0.00 67.68 0.00
July 6196.94 04-JUL-15:51 110.40 828.00 457.14 0.00 0.00 0.00 0.00 60.28 0.00
August 6133.80 06-AUG-14:31 110.40 828.00 457.14 0.00 0.00 0.00 0.00 73.30 0.00
September 5923.19 04-SEP-14:31 99.36 745.20 411.43 0.00 0.00 0.00 0.00 39.17 0.00
October 4588.73 02-OCT-06:01 1589.76 5961.59 731.42 0.00 0.00 0.00 0.00 11.22 0.00
November 2465.37 30-NOV-07:02 1192.32 4471.20 548.57 0.00 0.00 0.00 0.00 11.03 0.00
December 1911.77 01-DEC-13:40 198.72 745.20 91.43 0.00 0.00 0.00 0.00 4.68 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1455.32   77.28 579.60 91.43 0.00 0.00 0.00 0.00 4.68 0.00
Maximum of Months 6196.94   1589.76 5961.59 731.42 0.00 0.00 0.00 0.00 73.30 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 688.14 13-JAN-10:30 105.84 168.86 77.73 0.00 0.00 0.00 0.00 1.79 0.00
February 735.00 28-FEB-10:00 105.84 168.86 77.73 0.00 0.00 0.00 0.00 1.38 0.00
March 812.23 31-MAR-09:30 105.84 168.86 77.73 0.00 0.00 0.00 0.00 1.46 0.00
April 1073.68 09-APR-08:31 52.92 168.86 349.79 0.00 0.00 0.00 0.00 0.00 1.19
May 1060.57 19-MAY-06:02 529.20 844.32 388.66 0.00 0.00 0.00 0.00 1.46 0.00
June 1591.90 11-JUN-09:51 58.80 187.63 388.66 0.00 0.00 0.00 0.00 8.12 0.00
July 1784.11 04-JUL-11:11 58.80 187.63 388.66 0.00 0.00 0.00 0.00 9.86 0.00
August 1449.56 06-AUG-10:31 58.80 187.63 388.66 0.00 0.00 0.00 0.00 4.00 0.00
September 1736.40 10-SEP-11:11 58.80 187.63 388.66 0.00 0.00 0.00 0.00 13.01 0.00
October 1209.14 04-OCT-06:01 846.72 1350.91 621.86 0.00 0.00 0.00 0.00 1.41 0.00
November 932.71 21-NOV-07:02 529.20 844.32 388.66 0.00 0.00 0.00 0.00 1.96 0.00
December 712.91 08-DEC-10:20 105.84 168.86 77.73 0.00 0.00 0.00 0.00 2.27 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 688.14   52.92 168.86 77.73 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1784.11   846.72 1350.91 621.86 0.00 0.00 0.00 0.00 13.01 1.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 577.87 03-JAN-14:00 138.24 220.56 101.53 0.00 0.00 0.00 0.00 2.21 0.00
February 656.54 17-FEB-13:30 138.24 220.56 101.53 0.00 0.00 0.00 0.00 5.87 0.00
March 1153.08 29-MAR-07:30 138.24 220.56 101.53 0.00 0.00 0.00 0.00 0.95 0.00
April 3353.01 09-APR-08:31 69.12 220.56 456.87 0.00 0.00 0.00 0.00 0.00 3.13
May 3186.12 14-MAY-08:31 69.12 220.56 456.87 0.00 0.00 0.00 0.00 7.01 0.00
June 3319.21 11-JUN-07:51 69.12 220.56 456.87 0.00 0.00 0.00 0.00 1.66 0.00
July 3398.42 02-JUL-10:31 76.80 245.06 507.64 0.00 0.00 0.00 0.00 5.87 0.00
August 3261.59 06-AUG-10:31 76.80 245.06 507.64 0.00 0.00 0.00 0.00 3.62 0.00
September 3200.44 10-SEP-08:31 69.12 220.56 456.87 0.00 0.00 0.00 0.00 4.92 0.00
October 1058.04 06-OCT-07:30 138.24 220.56 101.53 0.00 0.00 0.00 0.00 1.42 0.00
November 782.79 03-NOV-13:30 138.24 220.56 101.53 0.00 0.00 0.00 0.00 5.28 0.00
December 696.12 01-DEC-13:40 138.24 220.56 101.53 0.00 0.00 0.00 0.00 1.19 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 577.87   69.12 220.56 101.53 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3398.42   138.24 245.06 507.64 0.00 0.00 0.00 0.00 7.01 3.13



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 224.31 05-JAN-07:01 63.50 238.14 29.22 0.00 0.00 0.00 0.00 0.00 0.00
February 223.51 23-FEB-07:01 81.65 306.18 37.57 0.00 0.00 0.00 0.00 0.00 0.00
March 224.50 01-MAR-07:01 90.72 340.20 41.74 0.00 0.00 0.00 0.00 0.00 0.00
April 223.58 19-APR-06:01 72.58 272.16 33.39 0.00 0.00 0.00 0.00 0.00 0.00
May 210.20 19-MAY-06:02 45.36 170.10 20.87 0.00 0.00 0.00 0.00 0.00 0.00
June 225.34 16-JUN-06:01 72.58 272.16 33.39 0.00 0.00 0.00 0.00 0.00 0.00
July 226.12 05-JUL-06:01 72.58 272.16 33.39 0.00 0.00 0.00 0.00 0.00 0.00
August 226.62 02-AUG-06:01 72.58 272.16 33.39 0.00 0.00 0.00 0.00 0.00 0.00
September 226.10 01-SEP-06:01 63.50 238.14 29.22 0.00 0.00 0.00 0.00 0.00 0.00
October 223.32 02-OCT-06:01 72.58 272.16 33.39 0.00 0.00 0.00 0.00 0.00 0.00
November 223.70 30-NOV-07:02 54.43 204.12 25.04 0.00 0.00 0.00 0.00 0.00 0.00
December 223.29 12-DEC-07:01 90.72 340.20 41.74 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 210.20   45.36 170.10 20.87 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 226.62   90.72 340.20 41.74 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 868.23 02-JAN-10:40 77.76 291.60 35.78 0.00 0.00 0.00 0.00 1.17 0.00
February 842.23 28-FEB-10:10 77.76 291.60 35.78 0.00 0.00 0.00 0.00 1.83 0.00
March 1049.44 27-MAR-10:30 77.76 291.60 35.78 0.00 0.00 0.00 0.00 1.01 0.00
April 1092.02 14-APR-10:10 77.76 291.60 35.78 0.00 0.00 0.00 0.00 3.25 0.00
May 1826.77 15-MAY-06:02 388.80 1458.00 178.88 0.00 0.00 0.00 0.00 1.96 0.00
June 1981.01 12-JUN-06:02 466.56 1749.60 214.66 0.00 0.00 0.00 0.00 0.96 0.00
July 2508.86 04-JUL-11:11 43.20 324.00 178.88 0.00 0.00 0.00 0.00 12.91 0.00
August 1991.07 21-AUG-06:01 699.84 2624.40 321.99 0.00 0.00 0.00 0.00 2.25 0.00
September 2442.24 10-SEP-11:11 43.20 324.00 178.88 0.00 0.00 0.00 0.00 17.06 0.00
October 1922.59 02-OCT-06:01 622.08 2332.80 286.21 0.00 0.00 0.00 0.00 3.33 0.00
November 1452.99 21-NOV-07:02 388.80 1458.00 178.88 0.00 0.00 0.00 0.00 2.53 0.00
December 900.07 08-DEC-10:30 77.76 291.60 35.78 0.00 0.00 0.00 0.00 2.98 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 842.23   43.20 291.60 35.78 0.00 0.00 0.00 0.00 0.96 0.00
Maximum of Months 2508.86   699.84 2624.40 321.99 0.00 0.00 0.00 0.00 17.06 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 883.29 02-JAN-14:20 38.88 62.03 28.55 0.00 0.00 0.00 0.00 1102.81 0.00
February 848.87 02-FEB-14:00 38.88 62.03 28.55 0.00 0.00 0.00 0.00 1065.91 0.00
March 904.68 13-MAR-16:00 38.88 62.03 28.55 0.00 0.00 0.00 0.00 1072.90 0.00
April 1023.76 17-APR-15:00 38.88 62.03 28.55 0.00 0.00 0.00 0.00 1502.66 0.00
May 1130.94 22-MAY-13:00 38.88 62.03 28.55 0.00 0.00 0.00 0.00 1842.39 0.00
June 993.34 09-JUN-15:20 38.88 62.03 28.55 0.00 0.00 0.00 0.00 1171.63 0.00
July 1174.40 28-JUL-15:40 38.88 62.03 28.55 0.00 0.00 0.00 0.00 1647.63 0.00
August 1118.05 23-AUG-13:00 38.88 62.03 28.55 0.00 0.00 0.00 0.00 1674.92 0.00
September 1044.28 20-SEP-16:00 38.88 62.03 28.55 0.00 0.00 0.00 0.00 1352.81 0.00
October 1019.37 03-OCT-15:00 38.88 62.03 28.55 0.00 0.00 0.00 0.00 1321.30 0.00
November 931.65 17-NOV-15:00 38.88 62.03 28.55 0.00 0.00 0.00 0.00 1145.90 0.00
December 829.68 08-DEC-14:00 38.88 62.03 28.55 0.00 0.00 0.00 0.00 904.94 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 829.68   38.88 62.03 28.55 0.00 0.00 0.00 0.00 904.94 0.00
Maximum of Months 1174.40   38.88 62.03 28.55 0.00 0.00 0.00 0.00 1842.39 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3788.00 01-JAN-13:31 806.48 349.44 1330.70 0.00 0.00 0.00 0.00 8.86 0.00
February 3809.25 26-FEB-13:01 1008.10 436.80 1663.37 0.00 0.00 0.00 0.00 0.00 1.00
March 3168.58 12-MAR-13:41 907.29 393.12 1497.03 0.00 0.00 0.00 0.00 0.00 1.35
April 3700.00 09-APR-13:11 907.29 393.12 1497.03 0.00 0.00 0.00 0.00 32.14 0.00
May 2951.09 12-MAY-06:02 9072.88 1965.60 1663.37 0.00 0.00 0.00 0.00 5.08 0.00
June 3304.52 03-JUN-04:01 0.00 436.80 998.02 0.00 0.00 0.00 0.00 6.24 0.00
July 2868.84 07-JUL-06:03 7258.31 1572.48 1330.70 0.00 0.00 0.00 0.00 0.00 0.00
August 2922.32 31-AUG-12:50 1814.58 393.12 332.67 0.00 0.00 0.00 0.00 17.57 0.00
September 4071.40 10-SEP-12:31 1008.10 436.80 1663.37 0.00 0.00 0.00 0.00 60.06 0.00
October 3854.61 22-OCT-11:31 1008.10 436.80 1663.37 0.00 0.00 0.00 0.00 22.66 0.00
November 3828.19 19-NOV-13:41 1008.10 436.80 1663.37 0.00 0.00 0.00 0.00 20.67 0.00
December 4098.11 03-DEC-15:01 705.67 305.76 1164.36 0.00 0.00 0.00 0.00 0.00 9.35
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2868.84   0.00 305.76 332.67 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4098.11   9072.88 1965.60 1663.37 0.00 0.00 0.00 0.00 60.06 9.35



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 350.81 14-JAN-05:02 0.00 51.84 68.53 0.00 0.00 0.00 0.00 0.00 0.00
February 343.22 11-FEB-05:01 0.00 51.84 68.53 0.00 0.00 0.00 0.00 0.00 0.00
March 314.66 12-MAR-13:41 17.28 51.84 114.22 0.00 0.00 0.00 0.00 0.00 0.00
April 320.40 13-APR-04:01 0.00 120.96 88.84 0.00 0.00 0.00 0.00 0.00 0.00
May 355.85 27-MAY-04:02 0.00 57.60 76.15 0.00 0.00 0.00 0.00 0.00 0.00
June 340.81 03-JUN-04:02 0.00 57.60 76.15 0.00 0.00 0.00 0.00 0.00 0.00
July 345.04 15-JUL-04:02 0.00 51.84 68.53 0.00 0.00 0.00 0.00 0.00 0.00
August 335.45 12-AUG-04:01 0.00 46.08 60.92 0.00 0.00 0.00 0.00 0.00 0.00
September 349.95 16-SEP-04:02 0.00 51.84 68.53 0.00 0.00 0.00 0.00 0.00 0.00
October 341.54 14-OCT-05:02 61.44 46.08 60.92 0.00 0.00 0.00 0.00 0.00 0.00
November 330.75 03-NOV-04:01 0.00 120.96 88.84 0.00 0.00 0.00 0.00 0.00 0.00
December 337.11 09-DEC-05:01 0.00 51.84 68.53 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 314.66   0.00 46.08 60.92 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 355.85   61.44 120.96 114.22 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 417.54 27-JAN-06:12 105.01 231.00 381.32 0.00 0.00 0.00 0.00 0.00 0.00
February 404.19 23-FEB-07:01 340.23 623.70 686.37 0.00 0.00 0.00 0.00 0.00 0.00
March 405.44 01-MAR-07:01 378.04 693.00 762.63 0.00 0.00 0.00 0.00 0.00 0.00
April 399.57 19-APR-06:01 302.43 554.40 610.11 0.00 0.00 0.00 0.00 0.00 0.00
May 385.88 11-MAY-06:03 151.21 277.20 305.05 0.00 0.00 0.00 0.00 0.00 0.00
June 354.56 06-JUN-06:03 151.21 277.20 305.05 0.00 0.00 0.00 0.00 0.00 0.00
July 379.64 07-JUL-06:03 151.21 277.20 305.05 0.00 0.00 0.00 0.00 0.00 0.00
August 360.12 29-AUG-06:03 151.21 277.20 305.05 0.00 0.00 0.00 0.00 0.00 0.00
September 372.66 28-SEP-06:03 151.21 277.20 305.05 0.00 0.00 0.00 0.00 0.00 0.00
October 387.81 20-OCT-06:03 151.21 277.20 305.05 0.00 0.00 0.00 0.00 0.00 0.00
November 394.39 14-NOV-07:02 189.02 346.50 381.32 0.00 0.00 0.00 0.00 0.00 0.00
December 404.35 20-DEC-07:01 378.04 693.00 762.63 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 354.56   105.01 231.00 305.05 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 417.54   378.04 693.00 762.63 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3300.27 14-JAN-05:01 0.00 486.00 1058.97 0.00 0.00 0.00 0.00 0.00 1.47
February 3328.11 20-FEB-16:31 388.84 486.00 1764.96 0.00 0.00 0.00 0.00 16.94 0.00
March 2661.10 27-MAR-16:30 777.68 486.00 392.21 0.00 0.00 0.00 0.00 13.86 0.00
April 3753.64 02-APR-16:32 259.23 162.00 705.98 0.00 0.00 0.00 0.00 10.05 0.00
May 3190.20 08-MAY-05:01 3024.29 2268.00 2745.49 0.00 0.00 0.00 0.00 1.23 0.00
June 3408.61 10-JUN-04:01 0.00 540.00 1176.64 0.00 0.00 0.00 0.00 10.00 0.00
July 2822.31 28-JUL-15:30 777.68 486.00 392.21 0.00 0.00 0.00 0.00 16.50 0.00
August 2814.02 31-AUG-15:30 777.68 486.00 392.21 0.00 0.00 0.00 0.00 20.18 0.00
September 3904.25 10-SEP-15:51 388.84 486.00 1764.96 0.00 0.00 0.00 0.00 74.29 0.00
October 3390.97 15-OCT-16:32 259.23 162.00 705.98 0.00 0.00 0.00 0.00 32.44 0.00
November 2800.45 07-NOV-15:30 777.68 486.00 392.21 0.00 0.00 0.00 0.00 7.87 0.00
December 3923.62 03-DEC-15:01 302.43 378.00 1372.74 0.00 0.00 0.00 0.00 0.00 4.56
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2661.10   0.00 162.00 392.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3923.62   3024.29 2268.00 2745.49 0.00 0.00 0.00 0.00 74.29 4.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3447.97 14-JAN-05:02 0.00 729.00 1588.46 0.00 0.00 0.00 0.00 3.90 0.00
February 3421.20 11-FEB-05:01 0.00 729.00 1588.46 0.00 0.00 0.00 0.00 0.00 1.31
March 3163.31 12-MAR-13:41 583.26 729.00 2647.43 0.00 0.00 0.00 0.00 9.06 0.00
April 3039.77 13-APR-04:01 0.00 1701.00 2059.12 0.00 0.00 0.00 0.00 5.70 0.00
May 3469.14 27-MAY-04:02 0.00 810.00 1764.96 0.00 0.00 0.00 0.00 4.31 0.00
June 3239.27 03-JUN-04:02 0.00 810.00 1764.96 0.00 0.00 0.00 0.00 4.34 0.00
July 3313.51 15-JUL-04:01 0.00 729.00 1588.46 0.00 0.00 0.00 0.00 2.32 0.00
August 3252.81 12-AUG-04:01 0.00 648.00 1411.96 0.00 0.00 0.00 0.00 0.39 0.00
September 3372.59 16-SEP-04:02 0.00 729.00 1588.46 0.00 0.00 0.00 0.00 3.02 0.00
October 3299.96 14-OCT-05:02 2073.80 648.00 1411.96 0.00 0.00 0.00 0.00 0.00 0.00
November 3204.60 26-NOV-13:11 583.26 729.00 2647.43 0.00 0.00 0.00 0.00 0.00 10.51
December 3341.30 09-DEC-05:01 0.00 729.00 1588.46 0.00 0.00 0.00 0.00 3.98 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3039.77   0.00 648.00 1411.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3469.14   2073.80 1701.00 2647.43 0.00 0.00 0.00 0.00 9.06 10.51



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4486.80 14-JAN-05:02 0.00 972.00 2117.95 0.00 0.00 0.00 0.00 7.46 0.00
February 4427.14 11-FEB-05:01 0.00 972.00 2117.95 0.00 0.00 0.00 0.00 0.51 0.00
March 4122.97 12-MAR-13:41 777.68 972.00 3529.91 0.00 0.00 0.00 0.00 13.56 0.00
April 3901.17 13-APR-04:01 0.00 2268.00 2745.49 0.00 0.00 0.00 0.00 9.29 0.00
May 4505.35 27-MAY-04:02 0.00 1080.00 2353.27 0.00 0.00 0.00 0.00 7.30 0.00
June 4198.27 03-JUN-04:02 0.00 1080.00 2353.27 0.00 0.00 0.00 0.00 6.21 0.00
July 4276.88 15-JUL-04:01 0.00 972.00 2117.95 0.00 0.00 0.00 0.00 3.90 0.00
August 4195.41 12-AUG-04:01 0.00 864.00 1882.62 0.00 0.00 0.00 0.00 1.27 0.00
September 4362.96 16-SEP-04:02 0.00 972.00 2117.95 0.00 0.00 0.00 0.00 5.49 0.00
October 4269.66 14-OCT-05:02 2765.07 864.00 1882.62 0.00 0.00 0.00 0.00 0.00 0.00
November 4210.24 26-NOV-13:11 777.68 972.00 3529.91 0.00 0.00 0.00 0.00 0.00 12.61
December 4345.01 03-DEC-15:01 604.86 756.00 2745.49 0.00 0.00 0.00 0.00 3.16 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3901.17   0.00 756.00 1882.62 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4505.35   2765.07 2268.00 3529.91 0.00 0.00 0.00 0.00 13.56 12.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 702.93 08-JAN-15:11 90.73 113.40 411.82 0.00 0.00 0.00 0.00 0.00 3.33
February 623.73 22-FEB-14:10 362.92 226.80 183.03 0.00 0.00 0.00 0.00 0.78 0.00
March 602.99 01-MAR-14:10 362.92 226.80 183.03 0.00 0.00 0.00 0.00 0.37 0.00
April 521.73 13-APR-13:10 362.92 226.80 183.03 0.00 0.00 0.00 0.00 2.69 0.00
May 474.03 22-MAY-13:10 362.92 226.80 183.03 0.00 0.00 0.00 0.00 5.73 0.00
June 486.08 01-JUN-14:40 181.46 113.40 91.52 0.00 0.00 0.00 0.00 3.37 0.00
July 496.69 27-JUL-16:00 181.46 113.40 91.52 0.00 0.00 0.00 0.00 6.04 0.00
August 584.37 31-AUG-13:10 362.92 226.80 183.03 0.00 0.00 0.00 0.00 2.81 0.00
September 637.93 10-SEP-12:31 100.81 126.00 457.58 0.00 0.00 0.00 0.00 13.01 0.00
October 618.91 06-OCT-12:30 181.46 113.40 91.52 0.00 0.00 0.00 0.00 1.14 0.00
November 752.36 26-NOV-13:11 90.73 113.40 411.82 0.00 0.00 0.00 0.00 0.00 9.25
December 815.37 03-DEC-15:01 70.57 88.20 320.31 0.00 0.00 0.00 0.00 0.00 1.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 474.03   70.57 88.20 91.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 815.37   362.92 226.80 457.58 0.00 0.00 0.00 0.00 13.01 9.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2716.34 14-JAN-05:01 0.00 472.50 1029.56 0.00 0.00 0.00 0.00 0.00 0.68
February 2390.79 11-FEB-05:01 0.00 472.50 1029.56 0.00 0.00 0.00 0.00 0.00 0.45
March 2279.84 27-MAR-10:20 756.07 472.50 381.32 0.00 0.00 0.00 0.00 1.75 0.00
April 3700.40 09-APR-08:31 378.04 472.50 1715.93 0.00 0.00 0.00 0.00 0.00 3.07
May 3322.20 08-MAY-05:01 2940.29 2205.00 2669.22 0.00 0.00 0.00 0.00 0.00 0.57
June 3363.42 03-JUN-04:01 0.00 525.00 1143.95 0.00 0.00 0.00 0.00 3.70 0.00
July 3340.08 15-JUL-04:01 0.00 472.50 1029.56 0.00 0.00 0.00 0.00 2.88 0.00
August 2934.79 07-AUG-04:01 0.00 1417.50 1715.93 0.00 0.00 0.00 0.00 0.00 0.00
September 3818.49 10-SEP-11:11 420.04 525.00 1906.59 0.00 0.00 0.00 0.00 32.86 0.00
October 3055.56 14-OCT-05:01 1344.13 420.00 915.16 0.00 0.00 0.00 0.00 0.00 0.00
November 2205.81 07-NOV-09:30 756.07 472.50 381.32 0.00 0.00 0.00 0.00 0.82 0.00
December 2364.88 03-DEC-10:21 294.03 367.50 1334.61 0.00 0.00 0.00 0.00 0.00 9.97
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2205.81   0.00 367.50 381.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3818.49   2940.29 2205.00 2669.22 0.00 0.00 0.00 0.00 32.86 9.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1430.00 14-JAN-05:02 0.00 303.75 661.86 0.00 0.00 0.00 0.00 6.50 0.00
February 1442.48 11-FEB-05:01 0.00 303.75 661.86 0.00 0.00 0.00 0.00 0.81 0.00
March 1302.23 12-MAR-13:41 243.02 303.75 1103.10 0.00 0.00 0.00 0.00 10.05 0.00
April 1344.98 09-APR-13:11 243.02 303.75 1103.10 0.00 0.00 0.00 0.00 21.15 0.00
May 1519.93 27-MAY-04:02 0.00 337.50 735.40 0.00 0.00 0.00 0.00 3.68 0.00
June 1460.60 03-JUN-04:02 0.00 337.50 735.40 0.00 0.00 0.00 0.00 3.34 0.00
July 1457.83 15-JUL-04:01 0.00 303.75 661.86 0.00 0.00 0.00 0.00 1.88 0.00
August 1435.07 12-AUG-04:01 0.00 270.00 588.32 0.00 0.00 0.00 0.00 0.25 0.00
September 1502.51 16-SEP-04:01 0.00 303.75 661.86 0.00 0.00 0.00 0.00 0.00 0.18
October 1402.65 14-OCT-05:01 864.08 270.00 588.32 0.00 0.00 0.00 0.00 0.00 0.00
November 1355.56 29-NOV-05:01 0.00 708.75 857.96 0.00 0.00 0.00 0.00 7.13 0.00
December 1401.99 09-DEC-05:01 0.00 303.75 661.86 0.00 0.00 0.00 0.00 4.85 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1302.23   0.00 270.00 588.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1519.93   864.08 708.75 1103.10 0.00 0.00 0.00 0.00 21.15 0.18



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4884.29 14-JAN-05:02 0.00 1069.20 2329.74 0.00 0.00 0.00 0.00 8.38 0.00
February 4938.88 11-FEB-05:01 0.00 1069.20 2329.74 0.00 0.00 0.00 0.00 0.00 0.56
March 4221.30 12-MAR-13:41 855.44 1069.20 3882.90 0.00 0.00 0.00 0.00 18.03 0.00
April 4398.54 12-APR-04:01 0.00 2494.80 3020.04 0.00 0.00 0.00 0.00 8.90 0.00
May 5127.20 27-MAY-04:02 0.00 1188.00 2588.60 0.00 0.00 0.00 0.00 5.27 0.00
June 4781.83 03-JUN-04:02 0.00 1188.00 2588.60 0.00 0.00 0.00 0.00 5.68 0.00
July 4917.52 15-JUL-04:01 0.00 1069.20 2329.74 0.00 0.00 0.00 0.00 2.80 0.00
August 4779.94 12-AUG-04:01 0.00 950.40 2070.88 0.00 0.00 0.00 0.00 0.48 0.00
September 4951.20 16-SEP-04:02 0.00 1069.20 2329.74 0.00 0.00 0.00 0.00 3.98 0.00
October 4768.91 14-OCT-05:02 3041.58 950.40 2070.88 0.00 0.00 0.00 0.00 0.00 0.00
November 4551.57 29-NOV-05:01 0.00 2494.80 3020.04 0.00 0.00 0.00 0.00 11.20 0.00
December 4737.53 09-DEC-05:01 0.00 1069.20 2329.74 0.00 0.00 0.00 0.00 7.15 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4221.30   0.00 950.40 2070.88 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5127.20   3041.58 2494.80 3882.90 0.00 0.00 0.00 0.00 18.03 0.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1782.32 14-JAN-05:01 0.00 364.50 794.23 0.00 0.00 0.00 0.00 0.00 0.39
February 1906.13 11-FEB-05:01 0.00 364.50 794.23 0.00 0.00 0.00 0.00 0.00 0.48
March 1607.39 12-MAR-13:41 291.63 364.50 1323.72 0.00 0.00 0.00 0.00 10.62 0.00
April 1630.44 13-APR-04:01 0.00 850.50 1029.56 0.00 0.00 0.00 0.00 4.96 0.00
May 1857.24 27-MAY-04:02 0.00 405.00 882.48 0.00 0.00 0.00 0.00 3.50 0.00
June 1870.27 03-JUN-04:01 0.00 405.00 882.48 0.00 0.00 0.00 0.00 2.91 0.00
July 1908.61 15-JUL-04:01 0.00 364.50 794.23 0.00 0.00 0.00 0.00 1.94 0.00
August 1746.05 12-AUG-04:01 0.00 324.00 705.98 0.00 0.00 0.00 0.00 0.02 0.00
September 1905.46 16-SEP-04:01 0.00 364.50 794.23 0.00 0.00 0.00 0.00 0.00 0.86
October 1740.50 14-OCT-05:01 1036.90 324.00 705.98 0.00 0.00 0.00 0.00 0.00 0.00
November 1676.15 29-NOV-05:01 0.00 850.50 1029.56 0.00 0.00 0.00 0.00 7.19 0.00
December 1722.54 09-DEC-05:01 0.00 364.50 794.23 0.00 0.00 0.00 0.00 4.77 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1607.39   0.00 324.00 705.98 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1908.61   1036.90 850.50 1323.72 0.00 0.00 0.00 0.00 10.62 0.86



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2588.74 14-JAN-05:02 0.00 534.60 1164.87 0.00 0.00 0.00 0.00 4.08 0.00
February 2626.05 11-FEB-05:01 0.00 534.60 1164.87 0.00 0.00 0.00 0.00 0.00 0.50
March 2284.58 12-MAR-13:41 427.72 534.60 1941.45 0.00 0.00 0.00 0.00 8.30 0.00
April 2362.22 13-APR-04:01 0.00 1247.40 1510.02 0.00 0.00 0.00 0.00 3.75 0.00
May 2707.54 27-MAY-04:02 0.00 594.00 1294.30 0.00 0.00 0.00 0.00 2.67 0.00
June 2535.50 03-JUN-04:02 0.00 594.00 1294.30 0.00 0.00 0.00 0.00 2.82 0.00
July 2609.24 15-JUL-04:01 0.00 534.60 1164.87 0.00 0.00 0.00 0.00 1.35 0.00
August 2541.14 12-AUG-04:01 0.00 475.20 1035.44 0.00 0.00 0.00 0.00 0.18 0.00
September 2617.18 16-SEP-04:02 0.00 534.60 1164.87 0.00 0.00 0.00 0.00 1.99 0.00
October 2526.17 14-OCT-05:02 1520.79 475.20 1035.44 0.00 0.00 0.00 0.00 0.00 0.00
November 2439.76 29-NOV-05:01 0.00 1247.40 1510.02 0.00 0.00 0.00 0.00 5.21 0.00
December 2523.36 09-DEC-05:01 0.00 534.60 1164.87 0.00 0.00 0.00 0.00 3.37 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2284.58   0.00 475.20 1035.44 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2707.54   1520.79 1247.40 1941.45 0.00 0.00 0.00 0.00 8.30 0.50



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1001.82 14-JAN-05:01 0.00 155.08 192.74 0.00 0.00 0.00 0.00 0.00 0.00
February 1003.91 11-FEB-05:01 0.00 155.08 192.74 0.00 0.00 0.00 0.00 0.00 0.00
March 920.43 01-MAR-07:01 972.00 1550.79 713.87 0.00 0.00 0.00 0.00 0.00 0.00
April 906.14 04-APR-06:03 388.80 620.32 285.55 0.00 0.00 0.00 0.00 0.00 0.00
May 926.07 08-MAY-05:01 378.00 723.70 499.71 0.00 0.00 0.00 0.00 0.00 0.00
June 869.72 06-JUN-05:02 324.00 620.32 428.32 0.00 0.00 0.00 0.00 0.00 0.00
July 886.52 07-JUL-06:03 388.80 620.32 285.55 0.00 0.00 0.00 0.00 0.00 0.00
August 868.05 29-AUG-06:03 388.80 620.32 285.55 0.00 0.00 0.00 0.00 0.00 0.00
September 884.38 16-SEP-04:01 0.00 155.08 192.74 0.00 0.00 0.00 0.00 0.00 0.00
October 924.03 14-OCT-05:01 172.80 137.85 171.33 0.00 0.00 0.00 0.00 0.00 0.00
November 907.27 16-NOV-07:03 388.80 620.32 285.55 0.00 0.00 0.00 0.00 0.00 0.00
December 968.28 09-DEC-05:01 0.00 155.08 192.74 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 868.05   0.00 137.85 171.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1003.91   972.00 1550.79 713.87 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 991.54 14-JAN-05:01 0.00 155.08 192.74 0.00 0.00 0.00 0.00 0.00 0.00
February 930.44 23-FEB-07:01 874.80 1395.71 642.48 0.00 0.00 0.00 0.00 0.00 0.00
March 926.41 01-MAR-07:01 972.00 1550.79 713.87 0.00 0.00 0.00 0.00 0.00 0.00
April 886.02 06-APR-06:03 388.80 620.32 285.55 0.00 0.00 0.00 0.00 0.00 0.00
May 824.10 11-MAY-06:03 388.80 620.32 285.55 0.00 0.00 0.00 0.00 0.00 0.00
June 748.68 15-JUN-06:01 874.80 1395.71 642.48 0.00 0.00 0.00 0.00 0.00 0.00
July 742.77 20-JUL-06:01 777.60 1240.64 571.09 0.00 0.00 0.00 0.00 0.00 0.00
August 783.47 09-AUG-06:01 777.60 1240.64 571.09 0.00 0.00 0.00 0.00 0.00 0.00
September 765.95 01-SEP-06:01 680.40 1085.56 499.71 0.00 0.00 0.00 0.00 0.00 0.00
October 908.86 14-OCT-05:01 172.80 137.85 171.33 0.00 0.00 0.00 0.00 0.00 0.00
November 903.40 28-NOV-07:03 388.80 620.32 285.55 0.00 0.00 0.00 0.00 0.00 0.00
December 922.55 14-DEC-07:01 680.40 1085.56 499.71 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 742.77   0.00 137.85 171.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 991.54   972.00 1550.79 713.87 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 878.77 27-JAN-07:01 972.00 1550.79 713.87 0.00 0.00 0.00 0.00 0.00 0.00
February 882.19 23-FEB-07:01 874.80 1395.71 642.48 0.00 0.00 0.00 0.00 0.00 0.00
March 877.31 02-MAR-07:01 777.60 1240.64 571.09 0.00 0.00 0.00 0.00 0.00 0.00
April 742.30 07-APR-06:03 388.80 620.32 285.55 0.00 0.00 0.00 0.00 0.00 0.00
May 660.30 25-MAY-06:03 388.80 620.32 285.55 0.00 0.00 0.00 0.00 0.00 0.00
June 658.22 08-JUN-06:01 874.80 1395.71 642.48 0.00 0.00 0.00 0.00 0.00 0.00
July 664.82 14-JUL-06:01 874.80 1395.71 642.48 0.00 0.00 0.00 0.00 0.00 0.00
August 638.50 11-AUG-06:01 874.80 1395.71 642.48 0.00 0.00 0.00 0.00 0.00 0.00
September 671.43 22-SEP-06:01 874.80 1395.71 642.48 0.00 0.00 0.00 0.00 0.00 0.00
October 806.54 14-OCT-05:01 172.80 137.85 171.33 0.00 0.00 0.00 0.00 0.00 0.00
November 855.31 16-NOV-07:03 388.80 620.32 285.55 0.00 0.00 0.00 0.00 0.00 0.00
December 876.55 14-DEC-07:01 680.40 1085.56 499.71 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 638.50   172.80 137.85 171.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 882.19   972.00 1550.79 713.87 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 958.02 20-JAN-07:01 962.28 1535.29 706.73 0.00 0.00 0.00 0.00 0.00 0.00
February 951.71 23-FEB-07:01 962.28 1535.29 706.73 0.00 0.00 0.00 0.00 0.00 0.00
March 952.21 01-MAR-07:01 1069.20 1705.87 785.25 0.00 0.00 0.00 0.00 0.00 0.00
April 949.50 07-APR-06:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
May 975.39 08-MAY-05:01 415.80 796.07 549.68 0.00 0.00 0.00 0.00 0.00 0.00
June 925.74 14-JUN-06:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
July 937.67 07-JUL-06:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
August 933.35 29-AUG-06:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
September 936.83 06-SEP-06:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
October 953.71 14-OCT-05:01 190.08 151.63 188.46 0.00 0.00 0.00 0.00 0.00 0.00
November 942.41 22-NOV-07:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
December 949.72 20-DEC-07:01 1069.20 1705.87 785.25 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 925.74   190.08 151.63 188.46 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 975.39   1069.20 1705.87 785.25 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1006.00 20-JAN-07:01 962.28 1535.29 706.73 0.00 0.00 0.00 0.00 0.00 0.00
February 1078.44 11-FEB-05:01 0.00 170.59 212.02 0.00 0.00 0.00 0.00 0.00 0.00
March 998.10 01-MAR-07:01 1069.20 1705.87 785.25 0.00 0.00 0.00 0.00 0.00 0.00
April 987.41 19-APR-06:01 855.36 1364.70 628.20 0.00 0.00 0.00 0.00 0.00 0.00
May 1031.11 08-MAY-05:01 415.80 796.07 549.68 0.00 0.00 0.00 0.00 0.00 0.00
June 970.70 06-JUN-05:02 356.40 682.35 471.15 0.00 0.00 0.00 0.00 0.00 0.00
July 1086.20 15-JUL-04:01 0.00 170.59 212.02 0.00 0.00 0.00 0.00 0.00 0.00
August 978.06 29-AUG-06:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
September 1078.94 16-SEP-04:01 0.00 170.59 212.02 0.00 0.00 0.00 0.00 0.00 0.00
October 1000.84 14-OCT-05:01 190.08 151.63 188.46 0.00 0.00 0.00 0.00 0.00 0.00
November 984.92 16-NOV-07:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
December 997.34 20-DEC-07:01 1069.20 1705.87 785.25 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 970.70   0.00 151.63 188.46 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1086.20   1069.20 1705.87 785.25 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 991.86 20-JAN-07:01 962.28 1535.29 706.73 0.00 0.00 0.00 0.00 0.00 0.00
February 985.72 23-FEB-07:01 962.28 1535.29 706.73 0.00 0.00 0.00 0.00 0.00 0.00
March 985.44 01-MAR-07:01 1069.20 1705.87 785.25 0.00 0.00 0.00 0.00 0.00 0.00
April 977.97 07-APR-06:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
May 1015.58 08-MAY-05:01 415.80 796.07 549.68 0.00 0.00 0.00 0.00 0.00 0.00
June 954.75 06-JUN-05:02 356.40 682.35 471.15 0.00 0.00 0.00 0.00 0.00 0.00
July 963.80 07-JUL-06:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
August 962.39 29-AUG-06:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
September 965.53 06-SEP-06:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
October 986.37 14-OCT-05:01 190.08 151.63 188.46 0.00 0.00 0.00 0.00 0.00 0.00
November 972.57 16-NOV-07:03 427.68 682.35 314.10 0.00 0.00 0.00 0.00 0.00 0.00
December 984.28 20-DEC-07:01 1069.20 1705.87 785.25 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 954.75   190.08 151.63 188.46 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1015.58   1069.20 1705.87 785.25 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 261.94 14-JAN-05:01 0.00 51.03 16.90 0.00 0.00 0.00 0.00 0.00 0.19
February 294.90 18-FEB-07:03 12.10 68.04 12.52 0.00 0.00 0.00 0.00 2.05 0.00
March 365.02 14-MAR-06:03 54.43 204.12 25.04 0.00 0.00 0.00 0.00 1.12 0.00
April 392.83 16-APR-19:51 0.00 19.84 13.15 0.00 0.00 0.00 0.00 4.30 0.00
May 481.35 29-MAY-17:32 4.54 17.01 11.27 0.00 0.00 0.00 0.00 39.44 0.00
June 458.11 25-JUN-17:51 6.05 22.68 15.03 0.00 0.00 0.00 0.00 15.44 0.00
July 474.81 30-JUL-16:12 4.54 17.01 11.27 0.00 0.00 0.00 0.00 30.95 0.00
August 478.35 06-AUG-16:01 7.56 28.35 18.78 0.00 0.00 0.00 0.00 14.30 0.00
September 478.59 10-SEP-16:31 6.05 22.68 15.03 0.00 0.00 0.00 0.00 27.73 0.00
October 418.93 04-OCT-04:01 0.00 153.09 28.17 0.00 0.00 0.00 0.00 5.22 0.00
November 362.60 24-NOV-07:03 54.43 204.12 25.04 0.00 0.00 0.00 0.00 0.00 1.15
December 343.39 01-DEC-07:03 54.43 204.12 25.04 0.00 0.00 0.00 0.00 0.40 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 261.94   0.00 17.01 11.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 481.35   54.43 204.12 28.17 0.00 0.00 0.00 0.00 39.44 1.15



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 626.59 26-JAN-06:12 432.04 230.40 1426.19 0.00 0.00 0.00 0.00 0.00 0.00
February 632.95 11-FEB-05:01 0.00 57.60 641.78 0.00 0.00 0.00 0.00 0.00 0.00
March 628.21 21-MAR-05:12 432.04 230.40 1426.19 0.00 0.00 0.00 0.00 0.00 0.00
April 621.52 26-APR-05:12 360.04 192.00 1188.49 0.00 0.00 0.00 0.00 0.00 0.00
May 637.16 12-MAY-04:01 0.00 172.80 1069.64 0.00 0.00 0.00 0.00 0.00 0.00
June 635.98 22-JUN-04:01 0.00 172.80 1069.64 0.00 0.00 0.00 0.00 0.00 0.00
July 629.97 15-JUL-04:01 0.00 57.60 641.78 0.00 0.00 0.00 0.00 0.00 0.00
August 568.68 29-AUG-05:12 360.04 192.00 1188.49 0.00 0.00 0.00 0.00 0.00 0.00
September 636.15 15-SEP-04:01 0.00 172.80 1069.64 0.00 0.00 0.00 0.00 0.00 0.00
October 619.48 20-OCT-05:12 360.04 192.00 1188.49 0.00 0.00 0.00 0.00 0.00 0.00
November 628.36 29-NOV-05:01 0.00 134.40 831.94 0.00 0.00 0.00 0.00 0.00 0.00
December 625.46 20-DEC-06:12 360.04 192.00 1188.49 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 568.68   0.00 57.60 641.78 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 637.16   432.04 230.40 1426.19 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1003.37 14-JAN-05:01 0.00 135.00 802.35 0.00 0.00 0.00 0.00 0.00 0.00
February 1019.96 11-FEB-05:01 0.00 135.00 802.35 0.00 0.00 0.00 0.00 0.00 0.00
March 997.71 21-MAR-05:12 810.00 540.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
April 994.85 26-APR-05:12 675.00 450.00 1485.84 0.00 0.00 0.00 0.00 0.00 0.00
May 1026.42 12-MAY-04:01 0.00 405.00 1337.26 0.00 0.00 0.00 0.00 0.00 0.00
June 1024.22 22-JUN-04:01 0.00 405.00 1337.26 0.00 0.00 0.00 0.00 0.00 0.00
July 1022.72 15-JUL-04:01 0.00 135.00 802.35 0.00 0.00 0.00 0.00 0.00 0.00
August 1014.10 30-AUG-04:01 0.00 405.00 1337.26 0.00 0.00 0.00 0.00 0.00 0.00
September 1022.19 15-SEP-04:01 0.00 405.00 1337.26 0.00 0.00 0.00 0.00 0.00 0.00
October 1007.98 17-OCT-04:01 0.00 405.00 1337.26 0.00 0.00 0.00 0.00 0.00 0.00
November 1015.48 29-NOV-05:01 0.00 315.00 1040.09 0.00 0.00 0.00 0.00 0.00 0.00
December 998.16 09-DEC-05:01 0.00 135.00 802.35 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 994.85   0.00 135.00 802.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1026.42   810.00 540.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1231.33 14-JAN-05:01 0.00 162.00 962.82 0.00 0.00 0.00 0.00 0.00 0.00
February 1254.16 11-FEB-05:01 0.00 162.00 962.82 0.00 0.00 0.00 0.00 0.00 0.00
March 1211.11 03-MAR-06:12 810.00 540.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
April 1229.74 12-APR-04:01 0.00 378.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
May 1259.36 09-MAY-04:01 0.00 378.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
June 1255.59 22-JUN-04:01 0.00 486.00 1604.71 0.00 0.00 0.00 0.00 0.00 0.00
July 1253.33 15-JUL-04:01 0.00 162.00 962.82 0.00 0.00 0.00 0.00 0.00 0.00
August 1242.37 30-AUG-04:01 0.00 486.00 1604.71 0.00 0.00 0.00 0.00 0.00 0.00
September 1250.39 15-SEP-04:01 0.00 486.00 1604.71 0.00 0.00 0.00 0.00 0.00 0.00
October 1235.99 17-OCT-04:01 0.00 486.00 1604.71 0.00 0.00 0.00 0.00 0.00 0.00
November 1246.64 29-NOV-05:01 0.00 378.00 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
December 1224.29 09-DEC-05:01 0.00 162.00 962.82 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1211.11   0.00 162.00 962.82 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1259.36   810.00 540.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3693.16 14-JAN-05:01 0.00 554.40 1647.29 0.00 0.00 0.00 0.00 0.00 0.86
February 2864.77 26-FEB-09:09 134.41 492.80 2440.43 0.00 0.00 0.00 0.00 0.00 28.79
March 3398.48 26-MAR-09:09 151.21 554.40 2745.49 0.00 0.00 0.00 0.00 0.00 6.23
April 5227.30 09-APR-08:31 151.21 554.40 2745.49 0.00 0.00 0.00 0.00 0.00 7.85
May 4450.17 23-MAY-04:01 0.00 1663.20 2745.49 0.00 0.00 0.00 0.00 6.01 0.00
June 5191.38 04-JUN-10:31 168.02 616.00 3050.54 0.00 0.00 0.00 0.00 30.48 0.00
July 5307.00 23-JUL-10:11 168.02 616.00 3050.54 0.00 0.00 0.00 0.00 28.22 0.00
August 4460.72 18-AUG-04:01 0.00 1663.20 2745.49 0.00 0.00 0.00 0.00 31.21 0.00
September 5369.32 10-SEP-11:11 168.02 616.00 3050.54 0.00 0.00 0.00 0.00 44.52 0.00
October 5042.05 09-OCT-10:51 168.02 616.00 3050.54 0.00 0.00 0.00 0.00 41.30 0.00
November 3844.08 21-NOV-07:02 1512.15 2772.00 3050.54 0.00 0.00 0.00 0.00 7.72 0.00
December 3605.58 09-DEC-05:01 0.00 554.40 1647.29 0.00 0.00 0.00 0.00 9.09 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2864.77   0.00 492.80 1647.29 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5369.32   1512.15 2772.00 3050.54 0.00 0.00 0.00 0.00 44.52 28.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2091.79 20-JAN-07:01 2157.84 3442.76 1584.78 0.00 0.00 0.00 0.00 0.00 0.00
February 2092.23 23-FEB-07:01 2157.84 3442.76 1584.78 0.00 0.00 0.00 0.00 0.00 0.00
March 2100.08 31-MAR-06:03 959.04 1530.12 704.35 0.00 0.00 0.00 0.00 0.00 0.00
April 2100.70 18-APR-06:02 1198.80 1912.65 880.44 0.00 0.00 0.00 0.00 0.00 0.00
May 2206.94 08-MAY-05:01 932.40 1785.14 1232.61 0.00 0.00 0.00 0.00 0.00 0.00
June 2077.43 07-JUN-06:02 1918.08 3060.23 1408.70 0.00 0.00 0.00 0.00 0.00 0.00
July 2103.27 07-JUL-06:03 959.04 1530.12 704.35 0.00 0.00 0.00 0.00 0.00 0.00
August 2100.44 09-AUG-06:02 1918.08 3060.23 1408.70 0.00 0.00 0.00 0.00 0.00 0.00
September 2086.88 06-SEP-06:03 959.04 1530.12 704.35 0.00 0.00 0.00 0.00 0.00 0.00
October 2124.67 14-OCT-05:01 426.24 340.03 422.61 0.00 0.00 0.00 0.00 0.00 0.00
November 2102.63 22-NOV-07:03 959.04 1530.12 704.35 0.00 0.00 0.00 0.00 0.00 0.00
December 2090.62 01-DEC-07:03 959.04 1530.12 704.35 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2077.43   426.24 340.03 422.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2206.94   2157.84 3442.76 1584.78 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8081.98 08-JAN-15:11 1594.24 1151.28 4824.21 0.00 0.00 0.00 0.00 0.00 23.67
February 8330.40 20-FEB-15:51 1771.37 1279.20 5360.24 0.00 0.00 0.00 0.00 19.04 0.00
March 7182.22 12-MAR-13:41 1594.24 1151.28 4824.21 0.00 0.00 0.00 0.00 0.00 1.58
April 8028.09 09-APR-13:51 1594.24 1151.28 4824.21 0.00 0.00 0.00 0.00 28.99 0.00
May 7568.43 23-MAY-04:01 0.00 3453.84 4824.21 0.00 0.00 0.00 0.00 2.83 0.00
June 7601.50 10-JUN-04:01 0.00 1279.20 3216.14 0.00 0.00 0.00 0.00 7.60 0.00
July 7555.57 12-JUL-04:01 0.00 3453.84 4824.21 0.00 0.00 0.00 0.00 9.16 0.00
August 7606.15 07-AUG-04:01 0.00 3453.84 4824.21 0.00 0.00 0.00 0.00 0.00 0.00
September 8325.82 10-SEP-12:31 1771.37 1279.20 5360.24 0.00 0.00 0.00 0.00 84.24 0.00
October 8190.43 15-OCT-15:11 1417.10 1023.36 4288.19 0.00 0.00 0.00 0.00 60.69 0.00
November 8068.71 26-NOV-13:51 1594.24 1151.28 4824.21 0.00 0.00 0.00 0.00 0.00 58.66
December 8752.44 03-DEC-15:01 1239.96 895.44 3752.16 0.00 0.00 0.00 0.00 0.00 10.38
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7182.22   0.00 895.44 3216.14 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8752.44   1771.37 3453.84 5360.24 0.00 0.00 0.00 0.00 84.24 58.66



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 3083.76 14-JAN-05:01 0.00 485.92 603.93 0.00 0.00 0.00 0.00 0.00 0.00
February 3115.51 11-FEB-05:01 0.00 485.92 603.93 0.00 0.00 0.00 0.00 0.00 0.00
March 3012.09 02-MAR-06:12 846.00 1619.72 1118.39 0.00 0.00 0.00 0.00 0.00 0.00
April 2880.10 19-APR-06:01 2436.48 3887.32 1789.42 0.00 0.00 0.00 0.00 0.00 0.00
May 2877.81 08-MAY-05:01 1184.40 2267.61 1565.75 0.00 0.00 0.00 0.00 0.00 0.00
June 2756.16 14-JUN-06:03 1218.24 1943.66 894.71 0.00 0.00 0.00 0.00 0.00 0.00
July 2789.64 07-JUL-06:03 1218.24 1943.66 894.71 0.00 0.00 0.00 0.00 0.00 0.00
August 2782.71 29-AUG-06:03 1218.24 1943.66 894.71 0.00 0.00 0.00 0.00 0.00 0.00
September 2946.54 16-SEP-04:01 0.00 485.92 603.93 0.00 0.00 0.00 0.00 0.00 0.00
October 2874.08 14-OCT-05:01 541.44 431.92 536.83 0.00 0.00 0.00 0.00 0.00 0.00
November 2924.79 16-NOV-06:12 846.00 1619.72 1118.39 0.00 0.00 0.00 0.00 0.00 0.00
December 2997.60 05-DEC-06:12 846.00 1619.72 1118.39 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2756.16   0.00 431.92 536.83 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3115.51   2436.48 3887.32 1789.42 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 673.79 14-JAN-05:02 0.00 102.06 134.92 0.00 0.00 0.00 0.00 0.00 0.00
February 663.67 11-FEB-05:01 0.00 102.06 134.92 0.00 0.00 0.00 0.00 0.00 0.00
March 606.08 12-MAR-13:41 34.02 102.06 224.87 0.00 0.00 0.00 0.00 0.00 0.00
April 618.61 13-APR-04:01 0.00 238.14 174.90 0.00 0.00 0.00 0.00 0.00 0.00
May 682.50 27-MAY-04:02 0.00 113.40 149.91 0.00 0.00 0.00 0.00 0.00 0.00
June 651.09 03-JUN-04:02 0.00 113.40 149.91 0.00 0.00 0.00 0.00 0.00 0.00
July 661.94 15-JUL-04:02 0.00 102.06 134.92 0.00 0.00 0.00 0.00 0.00 0.00
August 644.15 12-AUG-04:01 0.00 90.72 119.93 0.00 0.00 0.00 0.00 0.00 0.00
September 671.77 16-SEP-04:02 0.00 102.06 134.92 0.00 0.00 0.00 0.00 0.00 0.00
October 657.79 14-OCT-05:02 120.96 90.72 119.93 0.00 0.00 0.00 0.00 0.00 0.00
November 633.60 03-NOV-04:01 0.00 238.14 174.90 0.00 0.00 0.00 0.00 0.00 0.00
December 649.46 09-DEC-05:01 0.00 102.06 134.92 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 606.08   0.00 90.72 119.93 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 682.50   120.96 238.14 224.87 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1658.84 11-JAN-06:12 486.05 1069.20 1764.96 0.00 0.00 0.00 0.00 0.00 0.00
February 1672.53 11-FEB-05:01 0.00 320.76 953.08 0.00 0.00 0.00 0.00 0.00 0.00
March 1662.93 21-MAR-05:12 583.26 1283.04 2117.95 0.00 0.00 0.00 0.00 0.00 0.00
April 1632.30 20-APR-05:12 486.05 1069.20 1764.96 0.00 0.00 0.00 0.00 0.00 0.00
May 1666.25 26-MAY-04:01 0.00 748.44 1235.47 0.00 0.00 0.00 0.00 0.00 0.00
June 1657.27 22-JUN-04:01 0.00 962.28 1588.46 0.00 0.00 0.00 0.00 0.00 0.00
July 1662.28 15-JUL-04:01 0.00 320.76 953.08 0.00 0.00 0.00 0.00 0.00 0.00
August 1638.68 12-AUG-04:01 0.00 285.12 847.18 0.00 0.00 0.00 0.00 0.00 0.00
September 1660.24 08-SEP-04:01 0.00 748.44 1235.47 0.00 0.00 0.00 0.00 0.00 0.00
October 1625.54 20-OCT-05:12 486.05 1069.20 1764.96 0.00 0.00 0.00 0.00 0.00 0.00
November 1660.85 29-NOV-05:01 0.00 748.44 1235.47 0.00 0.00 0.00 0.00 0.00 0.00
December 1657.10 20-DEC-06:12 486.05 1069.20 1764.96 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1625.54   0.00 285.12 847.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1672.53   583.26 1283.04 2117.95 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1797.52 14-JAN-05:01 0.00 338.58 1006.02 0.00 0.00 0.00 0.00 0.00 0.00
February 1818.99 11-FEB-05:01 0.00 338.58 1006.02 0.00 0.00 0.00 0.00 0.00 0.00
March 1770.41 24-MAR-05:12 513.05 1128.60 1863.01 0.00 0.00 0.00 0.00 0.00 0.00
April 1782.25 12-APR-04:01 0.00 790.02 1304.11 0.00 0.00 0.00 0.00 0.00 0.00
May 1801.70 12-MAY-04:01 0.00 1015.74 1676.71 0.00 0.00 0.00 0.00 0.00 0.00
June 1789.29 22-JUN-04:01 0.00 1015.74 1676.71 0.00 0.00 0.00 0.00 0.00 0.00
July 1798.33 15-JUL-04:01 0.00 338.58 1006.02 0.00 0.00 0.00 0.00 0.00 0.00
August 1788.29 31-AUG-04:01 0.00 790.02 1304.11 0.00 0.00 0.00 0.00 0.00 0.00
September 1796.93 08-SEP-04:01 0.00 790.02 1304.11 0.00 0.00 0.00 0.00 0.00 0.00
October 1795.82 14-OCT-05:02 82.09 300.96 894.24 0.00 0.00 0.00 0.00 0.00 0.00
November 1802.37 03-NOV-04:01 0.00 790.02 1304.11 0.00 0.00 0.00 0.00 0.00 0.00
December 1789.94 09-DEC-05:01 0.00 338.58 1006.02 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1770.41   0.00 300.96 894.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1818.99   513.05 1128.60 1863.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 263.44 27-JAN-07:01 120.96 453.60 55.65 0.00 0.00 0.00 0.00 0.00 0.00
February 264.85 23-FEB-07:01 108.86 408.24 50.09 0.00 0.00 0.00 0.00 0.00 0.00
March 264.28 02-MAR-07:01 96.77 362.88 44.52 0.00 0.00 0.00 0.00 0.00 0.00
April 189.99 07-APR-06:03 48.38 181.44 22.26 0.00 0.00 0.00 0.00 0.00 0.00
May 167.57 11-MAY-06:03 48.38 181.44 22.26 0.00 0.00 0.00 0.00 0.00 0.00
June 123.80 22-JUN-06:03 48.38 181.44 22.26 0.00 0.00 0.00 0.00 0.00 0.00
July 140.69 07-JUL-06:03 48.38 181.44 22.26 0.00 0.00 0.00 0.00 0.00 0.00
August 117.97 09-AUG-06:01 96.77 362.88 44.52 0.00 0.00 0.00 0.00 0.00 0.00
September 129.75 27-SEP-06:03 48.38 181.44 22.26 0.00 0.00 0.00 0.00 0.00 0.00
October 194.28 20-OCT-06:03 48.38 181.44 22.26 0.00 0.00 0.00 0.00 0.00 0.00
November 233.02 16-NOV-07:03 48.38 181.44 22.26 0.00 0.00 0.00 0.00 0.00 0.00
December 262.59 14-DEC-07:01 84.67 317.52 38.96 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 117.97   48.38 181.44 22.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 264.85   120.96 453.60 55.65 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 500.44 20-JAN-07:01 233.28 874.80 107.33 0.00 0.00 0.00 0.00 0.00 0.00
February 498.22 23-FEB-07:01 233.28 874.80 107.33 0.00 0.00 0.00 0.00 0.00 0.00
March 499.66 01-MAR-07:01 259.20 972.00 119.25 0.00 0.00 0.00 0.00 0.00 0.00
April 497.31 27-APR-06:03 103.68 388.80 47.70 0.00 0.00 0.00 0.00 0.00 0.00
May 512.52 08-MAY-05:01 100.80 453.60 83.48 0.00 0.00 0.00 0.00 0.00 0.00
June 488.26 14-JUN-06:03 103.68 388.80 47.70 0.00 0.00 0.00 0.00 0.00 0.00
July 494.44 07-JUL-06:03 103.68 388.80 47.70 0.00 0.00 0.00 0.00 0.00 0.00
August 489.80 29-AUG-06:03 103.68 388.80 47.70 0.00 0.00 0.00 0.00 0.00 0.00
September 492.45 06-SEP-06:03 103.68 388.80 47.70 0.00 0.00 0.00 0.00 0.00 0.00
October 500.90 14-OCT-05:01 46.08 86.40 28.62 0.00 0.00 0.00 0.00 0.00 0.00
November 495.01 22-NOV-07:03 103.68 388.80 47.70 0.00 0.00 0.00 0.00 0.00 0.00
December 497.59 12-DEC-07:01 259.20 972.00 119.25 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 488.26   46.08 86.40 28.62 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 512.52   259.20 972.00 119.25 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 639.47 14-JAN-05:01 0.00 116.64 38.64 0.00 0.00 0.00 0.00 0.00 0.00
February 681.14 11-FEB-05:01 0.00 116.64 38.64 0.00 0.00 0.00 0.00 0.00 0.00
March 628.81 01-MAR-07:01 311.04 1166.40 143.10 0.00 0.00 0.00 0.00 0.00 0.00
April 622.46 19-APR-06:01 248.83 933.12 114.48 0.00 0.00 0.00 0.00 0.00 0.00
May 649.64 08-MAY-05:01 120.96 544.32 100.17 0.00 0.00 0.00 0.00 0.00 0.00
June 610.32 14-JUN-06:03 124.42 466.56 57.24 0.00 0.00 0.00 0.00 0.00 0.00
July 682.44 15-JUL-04:01 0.00 116.64 38.64 0.00 0.00 0.00 0.00 0.00 0.00
August 616.28 29-AUG-06:03 124.42 466.56 57.24 0.00 0.00 0.00 0.00 0.00 0.00
September 676.99 16-SEP-04:01 0.00 116.64 38.64 0.00 0.00 0.00 0.00 0.00 0.00
October 630.08 14-OCT-05:01 55.30 103.68 34.35 0.00 0.00 0.00 0.00 0.00 0.00
November 620.59 16-NOV-07:03 124.42 466.56 57.24 0.00 0.00 0.00 0.00 0.00 0.00
December 628.70 12-DEC-07:01 311.04 1166.40 143.10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 610.32   0.00 103.68 34.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 682.44   311.04 1166.40 143.10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 489.66 13-JAN-10:30 27.22 102.06 12.52 0.00 0.00 0.00 0.00 1.64 0.00
February 537.34 28-FEB-10:00 27.22 102.06 12.52 0.00 0.00 0.00 0.00 1.26 0.00
March 615.19 31-MAR-09:30 27.22 102.06 12.52 0.00 0.00 0.00 0.00 1.33 0.00
April 1141.45 09-APR-09:51 15.12 113.40 62.61 0.00 0.00 0.00 0.00 1.37 0.00
May 910.74 08-MAY-05:01 105.84 476.28 87.65 0.00 0.00 0.00 0.00 0.30 0.00
June 1148.36 04-JUN-10:31 15.12 113.40 62.61 0.00 0.00 0.00 0.00 7.15 0.00
July 1183.93 23-JUL-10:11 15.12 113.40 62.61 0.00 0.00 0.00 0.00 6.50 0.00
August 764.95 02-AUG-06:01 217.73 816.48 100.17 0.00 0.00 0.00 0.00 1.75 0.00
September 1177.28 10-SEP-11:11 15.12 113.40 62.61 0.00 0.00 0.00 0.00 10.78 0.00
October 1000.09 09-OCT-10:51 15.12 113.40 62.61 0.00 0.00 0.00 0.00 9.55 0.00
November 594.11 07-NOV-09:30 27.22 102.06 12.52 0.00 0.00 0.00 0.00 0.29 0.00
December 508.27 08-DEC-10:20 27.22 102.06 12.52 0.00 0.00 0.00 0.00 2.08 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 489.66   15.12 102.06 12.52 0.00 0.00 0.00 0.00 0.29 0.00
Maximum of Months 1183.93   217.73 816.48 100.17 0.00 0.00 0.00 0.00 10.78 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7691.17 14-JAN-05:01 0.00 1673.10 4106.46 0.00 0.00 0.00 0.00 0.00 7.27
February 7804.08 11-FEB-05:01 0.00 1673.10 4106.46 0.00 0.00 0.00 0.00 0.00 5.92
March 7520.99 07-MAR-06:12 2535.25 5576.99 7604.56 0.00 0.00 0.00 0.00 0.00 5.93
April 7737.11 13-APR-04:01 0.00 3903.90 5323.19 0.00 0.00 0.00 0.00 0.00 0.02
May 8195.56 27-MAY-04:02 0.00 1859.00 4562.74 0.00 0.00 0.00 0.00 0.70 0.00
June 8051.23 03-JUN-04:02 0.00 1859.00 4562.74 0.00 0.00 0.00 0.00 3.95 0.00
July 7941.47 15-JUL-04:02 0.00 1673.10 4106.46 0.00 0.00 0.00 0.00 3.01 0.00
August 7902.51 07-AUG-04:02 0.00 5019.30 6844.11 0.00 0.00 0.00 0.00 0.00 0.00
September 8057.66 16-SEP-04:02 0.00 1673.10 4106.46 0.00 0.00 0.00 0.00 0.00 0.80
October 7787.32 14-OCT-05:02 405.64 1487.20 3650.19 0.00 0.00 0.00 0.00 0.00 0.00
November 7732.07 03-NOV-04:01 0.00 3903.90 5323.19 0.00 0.00 0.00 0.00 0.00 0.17
December 7727.26 09-DEC-05:01 0.00 1673.10 4106.46 0.00 0.00 0.00 0.00 2.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7520.99   0.00 1487.20 3650.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8195.56   2535.25 5576.99 7604.56 0.00 0.00 0.00 0.00 3.95 7.27



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 4423.83 14-JAN-05:01 0.00 718.53 893.05 0.00 0.00 0.00 0.00 0.00 0.00
February 4490.94 11-FEB-05:01 0.00 718.53 893.05 0.00 0.00 0.00 0.00 0.00 0.00
March 4299.89 02-MAR-06:12 1251.00 2395.12 1653.79 0.00 0.00 0.00 0.00 0.00 0.00
April 4303.51 04-APR-05:12 1251.00 2395.12 1653.79 0.00 0.00 0.00 0.00 0.00 0.00
May 4405.92 10-MAY-04:01 0.00 1916.09 1323.03 0.00 0.00 0.00 0.00 0.00 0.00
June 4404.76 21-JUN-04:01 0.00 2155.60 1488.41 0.00 0.00 0.00 0.00 0.00 0.00
July 4473.00 15-JUL-04:01 0.00 718.53 893.05 0.00 0.00 0.00 0.00 0.00 0.00
August 4415.28 12-AUG-04:01 0.00 638.70 793.82 0.00 0.00 0.00 0.00 0.00 0.00
September 4442.15 16-SEP-04:01 0.00 718.53 893.05 0.00 0.00 0.00 0.00 0.00 0.00
October 4261.52 20-OCT-05:12 1251.00 2395.12 1653.79 0.00 0.00 0.00 0.00 0.00 0.00
November 4287.89 07-NOV-06:12 1251.00 2395.12 1653.79 0.00 0.00 0.00 0.00 0.00 0.00
December 4415.93 09-DEC-05:01 0.00 718.53 893.05 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 4261.52   0.00 638.70 793.82 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4490.94   1251.00 2395.12 1653.79 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 310.74 14-JAN-05:02 0.00 43.74 57.82 0.00 0.00 0.00 0.00 3.00 0.00
February 308.15 11-FEB-05:01 0.00 43.74 57.82 0.00 0.00 0.00 0.00 0.97 0.00
March 313.05 12-MAR-19:01 0.00 17.01 44.97 0.00 0.00 0.00 0.00 0.00 1.82
April 326.08 09-APR-19:11 0.00 17.01 44.97 0.00 0.00 0.00 0.00 0.08 0.00
May 323.47 27-MAY-04:02 0.00 48.60 64.25 0.00 0.00 0.00 0.00 2.05 0.00
June 319.78 10-JUN-04:02 0.00 48.60 64.25 0.00 0.00 0.00 0.00 2.22 0.00
July 318.77 09-JUL-21:31 0.00 17.01 44.97 0.00 0.00 0.00 0.00 4.90 0.00
August 318.91 20-AUG-17:42 9.72 14.58 38.55 0.00 0.00 0.00 0.00 8.17 0.00
September 320.00 10-SEP-17:11 11.34 17.01 44.97 0.00 0.00 0.00 0.00 12.32 0.00
October 321.28 15-OCT-17:12 9.72 14.58 38.55 0.00 0.00 0.00 0.00 5.21 0.00
November 302.06 05-NOV-17:11 12.96 19.44 51.40 0.00 0.00 0.00 0.00 5.83 0.00
December 303.81 09-DEC-05:01 0.00 43.74 57.82 0.00 0.00 0.00 0.00 2.22 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 302.06   0.00 14.58 38.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 326.08   12.96 48.60 64.25 0.00 0.00 0.00 0.00 12.32 1.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 X-RAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 18278.12 27-JAN-07:01 19441.89 12149.99 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
February 18281.30 03-FEB-07:01 19441.89 12149.99 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
March 18275.33 21-MAR-06:01 19441.89 12149.99 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
April 16125.49 19-APR-06:01 15553.51 9719.99 71313.75 0.00 0.00 0.00 0.00 0.00 0.00
May 15719.39 08-MAY-05:01 7560.74 5669.99 62399.53 0.00 0.00 0.00 0.00 0.00 0.00
June 14473.88 06-JUN-05:02 6480.63 4860.00 53485.31 0.00 0.00 0.00 0.00 0.00 0.00
July 13325.37 07-JUL-05:12 5400.53 4050.00 44571.09 0.00 0.00 0.00 0.00 0.00 0.00
August 13248.18 11-AUG-06:01 17497.70 10934.99 80227.97 0.00 0.00 0.00 0.00 0.00 0.00
September 13605.84 01-SEP-06:01 13609.32 8504.99 62399.53 0.00 0.00 0.00 0.00 0.00 0.00
October 14491.77 26-OCT-05:02 6480.63 4860.00 53485.31 0.00 0.00 0.00 0.00 0.00 0.00
November 17988.87 13-NOV-07:01 19441.89 12149.99 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
December 18272.24 20-DEC-07:01 19441.89 12149.99 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 13248.18   5400.53 4050.00 44571.09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18281.30   19441.89 12149.99 89142.19 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 277.68 26-JAN-07:01 226.82 415.80 457.58 0.00 0.00 0.00 0.00 0.00 0.00
February 279.16 03-FEB-07:01 226.82 415.80 457.58 0.00 0.00 0.00 0.00 0.00 0.00
March 278.07 16-MAR-06:01 226.82 415.80 457.58 0.00 0.00 0.00 0.00 0.00 0.00
April 161.83 14-APR-12:50 22.68 41.58 45.76 0.00 0.00 0.00 0.00 0.00 0.00
May 168.10 18-MAY-13:00 22.68 41.58 45.76 0.00 0.00 0.00 0.00 0.00 0.00
June 171.26 09-JUN-14:20 22.68 41.58 45.76 0.00 0.00 0.00 0.00 0.00 0.00
July 174.42 28-JUL-15:30 22.68 41.58 45.76 0.00 0.00 0.00 0.00 0.00 0.00
August 166.01 31-AUG-14:40 22.68 41.58 45.76 0.00 0.00 0.00 0.00 0.00 0.00
September 163.14 08-SEP-15:30 22.68 41.58 45.76 0.00 0.00 0.00 0.00 0.00 0.00
October 163.51 06-OCT-13:00 22.68 41.58 45.76 0.00 0.00 0.00 0.00 0.00 0.00
November 222.84 13-NOV-07:01 226.82 415.80 457.58 0.00 0.00 0.00 0.00 0.00 0.00
December 280.66 15-DEC-07:01 226.82 415.80 457.58 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 161.83   22.68 41.58 45.76 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 280.66   226.82 415.80 457.58 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1146.69 06-JAN-07:03 799.20 1275.10 586.96 0.00 0.00 0.00 0.00 0.20 0.00
February 1431.46 17-FEB-07:03 799.20 1275.10 586.96 0.00 0.00 0.00 0.00 0.22 0.00
March 1490.30 14-MAR-06:03 799.20 1275.10 586.96 0.00 0.00 0.00 0.00 0.31 0.00
April 1548.21 16-APR-14:51 111.00 354.19 733.70 0.00 0.00 0.00 0.00 5.43 0.00
May 1829.83 29-MAY-16:01 111.00 177.10 440.22 0.00 0.00 0.00 0.00 15.10 0.00
June 1540.12 16-JUN-06:02 1598.40 2550.19 1173.91 0.00 0.00 0.00 0.00 1.07 0.00
July 1864.91 04-JUL-16:01 111.00 177.10 440.22 0.00 0.00 0.00 0.00 6.84 0.00
August 1547.08 11-AUG-06:02 1798.20 2868.97 1320.65 0.00 0.00 0.00 0.00 1.07 0.00
September 1562.41 01-SEP-06:01 1398.60 2231.42 1027.17 0.00 0.00 0.00 0.00 0.44 0.00
October 1507.23 12-OCT-06:02 999.00 1593.87 733.70 0.00 0.00 0.00 0.00 0.42 0.00
November 1504.11 21-NOV-07:02 999.00 1593.87 733.70 0.00 0.00 0.00 0.00 0.86 0.00
December 1476.95 01-DEC-07:03 799.20 1275.10 586.96 0.00 0.00 0.00 0.00 0.11 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1146.69   111.00 177.10 440.22 0.00 0.00 0.00 0.00 0.11 0.00
Maximum of Months 1864.91   1798.20 2868.97 1320.65 0.00 0.00 0.00 0.00 15.10 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 662.93 26-JAN-07:01 583.26 1069.20 1176.64 0.00 0.00 0.00 0.00 0.00 0.00
February 665.55 03-FEB-07:02 583.26 1069.20 1176.64 0.00 0.00 0.00 0.00 0.00 0.00
March 663.56 15-MAR-06:02 583.26 1069.20 1176.64 0.00 0.00 0.00 0.00 0.00 0.00
April 541.46 19-APR-06:01 466.61 855.36 941.31 0.00 0.00 0.00 0.00 0.00 0.00
May 467.59 17-MAY-06:02 291.63 534.60 588.32 0.00 0.00 0.00 0.00 0.00 0.00
June 609.81 16-JUN-06:01 466.61 855.36 941.31 0.00 0.00 0.00 0.00 0.00 0.00
July 585.27 19-JUL-06:01 408.28 748.44 823.65 0.00 0.00 0.00 0.00 0.00 0.00
August 595.96 02-AUG-06:01 466.61 855.36 941.31 0.00 0.00 0.00 0.00 0.00 0.00
September 619.51 01-SEP-06:01 408.28 748.44 823.65 0.00 0.00 0.00 0.00 0.00 0.00
October 540.95 04-OCT-06:01 466.61 855.36 941.31 0.00 0.00 0.00 0.00 0.00 0.00
November 639.89 13-NOV-07:01 583.26 1069.20 1176.64 0.00 0.00 0.00 0.00 0.00 0.00
December 669.47 15-DEC-07:01 583.26 1069.20 1176.64 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 467.59   291.63 534.60 588.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 669.47   583.26 1069.20 1176.64 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 191.29 02-JAN-16:20 13.61 51.03 6.26 0.00 0.00 0.00 0.00 2.77 0.00
February 216.95 22-FEB-17:03 95.26 357.21 43.83 0.00 0.00 0.00 0.00 3.21 0.00
March 257.72 27-MAR-17:00 13.61 51.03 6.26 0.00 0.00 0.00 0.00 5.89 0.00
April 473.21 16-APR-16:51 6.80 25.51 16.90 0.00 0.00 0.00 0.00 15.76 0.00
May 506.25 29-MAY-16:01 7.56 28.35 18.78 0.00 0.00 0.00 0.00 49.41 0.00
June 480.83 11-JUN-18:42 0.00 17.01 11.27 0.00 0.00 0.00 0.00 17.93 0.00
July 496.05 30-JUL-15:21 7.56 56.70 31.30 0.00 0.00 0.00 0.00 34.79 0.00
August 481.62 20-AUG-16:01 7.56 28.35 18.78 0.00 0.00 0.00 0.00 22.34 0.00
September 479.52 17-SEP-16:01 7.56 28.35 18.78 0.00 0.00 0.00 0.00 38.22 0.00
October 465.76 29-OCT-16:01 7.56 28.35 18.78 0.00 0.00 0.00 0.00 24.54 0.00
November 237.16 07-NOV-16:40 13.61 51.03 6.26 0.00 0.00 0.00 0.00 5.17 0.00
December 218.50 08-DEC-16:30 13.61 51.03 6.26 0.00 0.00 0.00 0.00 5.27 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 191.29   0.00 17.01 6.26 0.00 0.00 0.00 0.00 2.77 0.00
Maximum of Months 506.25   95.26 357.21 43.83 0.00 0.00 0.00 0.00 49.41 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 LOCKER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 897.90 27-JAN-07:01 1944.19 864.00 3565.47 0.00 0.00 0.00 0.00 0.00 0.00
February 956.26 03-FEB-06:12 648.06 345.60 2139.28 0.00 0.00 0.00 0.00 0.00 0.00
March 895.28 20-MAR-06:01 1944.19 864.00 3565.47 0.00 0.00 0.00 0.00 0.00 0.00
April 1063.04 16-APR-14:51 108.01 96.00 1782.73 0.00 0.00 0.00 0.00 0.00 0.00
May 940.58 29-MAY-16:01 108.01 48.00 1069.64 0.00 0.00 0.00 0.00 0.00 0.00
June 873.94 21-JUN-06:03 777.68 345.60 1426.19 0.00 0.00 0.00 0.00 0.00 0.00
July 1078.52 04-JUL-16:01 108.01 48.00 1069.64 0.00 0.00 0.00 0.00 0.00 0.00
August 886.49 31-AUG-06:01 1360.93 604.80 2495.83 0.00 0.00 0.00 0.00 0.00 0.00
September 891.38 01-SEP-06:01 1360.93 604.80 2495.83 0.00 0.00 0.00 0.00 0.00 0.00
October 878.72 12-OCT-06:02 972.09 432.00 1782.73 0.00 0.00 0.00 0.00 0.00 0.00
November 896.00 13-NOV-07:01 1944.19 864.00 3565.47 0.00 0.00 0.00 0.00 0.00 0.00
December 899.27 13-DEC-07:01 1944.19 864.00 3565.47 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 873.94   108.01 48.00 1069.64 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1078.52   1944.19 864.00 3565.47 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5139.74 27-JAN-07:01 12297.00 5464.79 22551.58 0.00 0.00 0.00 0.00 0.00 0.00
February 5129.43 27-FEB-07:01 9837.60 4371.84 18041.26 0.00 0.00 0.00 0.00 0.00 7.20
March 5118.31 21-MAR-06:01 12297.00 5464.79 22551.58 0.00 0.00 0.00 0.00 0.00 12.45
April 6678.92 16-APR-14:51 683.17 607.20 11275.79 0.00 0.00 0.00 0.00 25.50 0.00
May 6711.92 29-MAY-15:21 683.17 607.20 11275.79 0.00 0.00 0.00 0.00 69.68 0.00
June 6329.34 04-JUN-12:41 614.85 546.48 10148.21 0.00 0.00 0.00 0.00 13.31 0.00
July 6777.20 30-JUL-12:41 683.17 607.20 11275.79 0.00 0.00 0.00 0.00 45.75 0.00
August 6304.23 20-AUG-16:01 683.17 303.60 6765.47 0.00 0.00 0.00 0.00 34.32 0.00
September 6269.72 10-SEP-16:01 683.17 303.60 6765.47 0.00 0.00 0.00 0.00 46.48 0.00
October 5079.54 12-OCT-06:02 6148.50 2732.40 11275.79 0.00 0.00 0.00 0.00 2.25 0.00
November 5124.82 13-NOV-07:01 12297.00 5464.79 22551.58 0.00 0.00 0.00 0.00 0.00 20.33
December 5145.90 13-DEC-07:01 12297.00 5464.79 22551.58 0.00 0.00 0.00 0.00 0.00 4.57
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5079.54   614.85 303.60 6765.47 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6777.20   12297.00 5464.79 22551.58 0.00 0.00 0.00 0.00 69.68 20.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 938.55 15-JAN-15:22 34.56 103.68 228.44 0.00 0.00 0.00 0.00 19.34 0.00
February 987.39 20-FEB-15:41 40.32 120.96 266.51 0.00 0.00 0.00 0.00 18.40 0.00
March 983.95 26-MAR-16:01 57.60 86.40 228.44 0.00 0.00 0.00 0.00 14.32 0.00
April 1164.58 16-APR-14:51 57.60 172.80 380.73 0.00 0.00 0.00 0.00 17.97 0.00
May 1201.36 29-MAY-16:01 57.60 86.40 228.44 0.00 0.00 0.00 0.00 47.25 0.00
June 1127.11 04-JUN-12:42 51.84 155.52 342.66 0.00 0.00 0.00 0.00 13.20 0.00
July 1214.08 30-JUL-13:21 57.60 172.80 380.73 0.00 0.00 0.00 0.00 28.84 0.00
August 1097.86 06-AUG-14:42 34.56 103.68 228.44 0.00 0.00 0.00 0.00 35.69 0.00
September 1093.95 10-SEP-16:02 57.60 86.40 228.44 0.00 0.00 0.00 0.00 35.39 0.00
October 1021.98 22-OCT-16:42 34.56 51.84 137.06 0.00 0.00 0.00 0.00 13.20 0.00
November 988.43 05-NOV-10:41 51.84 155.52 342.66 0.00 0.00 0.00 0.00 11.40 0.00
December 987.39 10-DEC-14:31 57.60 172.80 380.73 0.00 0.00 0.00 0.00 36.06 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 938.55   34.56 51.84 137.06 0.00 0.00 0.00 0.00 11.40 0.00
Maximum of Months 1214.08   57.60 172.80 380.73 0.00 0.00 0.00 0.00 47.25 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5994.66 16-JAN-10:11 28.35 472.50 7799.94 0.00 0.00 0.00 0.00 0.00 46.71
February 5934.81 20-FEB-15:41 22.05 367.50 6066.62 0.00 0.00 0.00 0.00 3.33 0.00
March 5814.89 12-MAR-10:41 31.50 525.00 8666.60 0.00 0.00 0.00 0.00 0.00 30.33
April 6659.43 02-APR-10:01 28.35 472.50 7799.94 0.00 0.00 0.00 0.00 0.00 16.39
May 6825.06 07-MAY-10:01 31.50 525.00 8666.60 0.00 0.00 0.00 0.00 1.46 0.00
June 6484.17 04-JUN-07:21 28.35 472.50 7799.94 0.00 0.00 0.00 0.00 0.00 0.96
July 6887.80 30-JUL-11:21 31.50 525.00 8666.60 0.00 0.00 0.00 0.00 19.31 0.00
August 5901.73 20-AUG-16:01 31.50 262.50 5199.96 0.00 0.00 0.00 0.00 30.54 0.00
September 6013.56 24-SEP-10:01 22.05 367.50 6066.62 0.00 0.00 0.00 0.00 16.29 0.00
October 5933.16 09-OCT-10:41 22.05 367.50 6066.62 0.00 0.00 0.00 0.00 23.15 0.00
November 6101.09 26-NOV-09:51 28.35 472.50 7799.94 0.00 0.00 0.00 0.00 0.00 84.49
December 6029.52 03-DEC-09:11 22.05 367.50 6066.62 0.00 0.00 0.00 0.00 0.00 29.13
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5814.89   22.05 262.50 5199.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6887.80   31.50 525.00 8666.60 0.00 0.00 0.00 0.00 30.54 84.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 881.99 02-JAN-14:40 162.00 258.47 118.98 0.00 0.00 0.00 0.00 0.00 0.00
February 978.59 17-FEB-07:03 648.00 1033.86 475.91 0.00 0.00 0.00 0.00 0.00 0.00
March 1130.13 14-MAR-06:03 648.00 1033.86 475.91 0.00 0.00 0.00 0.00 0.00 0.00
April 1908.75 16-APR-14:51 90.00 287.18 594.89 0.00 0.00 0.00 0.00 0.00 0.00
May 1534.40 17-MAY-06:02 810.00 1292.33 594.89 0.00 0.00 0.00 0.00 0.00 0.00
June 1525.08 15-JUN-06:02 1458.00 2326.19 1070.80 0.00 0.00 0.00 0.00 0.00 0.00
July 1934.33 30-JUL-13:21 90.00 287.18 594.89 0.00 0.00 0.00 0.00 0.00 0.00
August 1536.29 25-AUG-06:03 648.00 1033.86 475.91 0.00 0.00 0.00 0.00 0.00 0.00
September 1559.81 01-SEP-06:01 1134.00 1809.26 832.84 0.00 0.00 0.00 0.00 0.00 0.00
October 1404.31 02-OCT-06:01 1296.00 2067.73 951.82 0.00 0.00 0.00 0.00 0.00 0.00
November 1453.78 30-NOV-07:02 972.00 1550.79 713.87 0.00 0.00 0.00 0.00 0.00 0.00
December 1065.41 01-DEC-07:03 648.00 1033.86 475.91 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 881.99   90.00 258.47 118.98 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1934.33   1458.00 2326.19 1070.80 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13696.90 06-JAN-07:03 6558.40 12022.55 13230.63 0.00 0.00 0.00 0.00 1.32 0.00
February 13764.04 02-FEB-07:03 6558.40 12022.55 13230.63 0.00 0.00 0.00 0.00 1.15 0.00
March 13816.28 14-MAR-06:03 6558.40 12022.55 13230.63 0.00 0.00 0.00 0.00 4.13 0.00
April 17480.16 16-APR-14:51 910.89 3339.60 16538.29 0.00 0.00 0.00 0.00 90.54 0.00
May 17589.66 29-MAY-15:21 910.89 3339.60 16538.29 0.00 0.00 0.00 0.00 242.36 0.00
June 16932.51 11-JUN-14:41 637.62 2337.72 11576.80 0.00 0.00 0.00 0.00 87.72 0.00
July 17885.75 30-JUL-13:21 910.89 3339.60 16538.29 0.00 0.00 0.00 0.00 152.72 0.00
August 16874.85 06-AUG-14:42 546.53 2003.76 9922.97 0.00 0.00 0.00 0.00 178.74 0.00
September 15737.91 10-SEP-16:01 910.89 1669.80 9922.97 0.00 0.00 0.00 0.00 157.81 0.00
October 13973.55 12-OCT-06:02 8198.00 15028.19 16538.29 0.00 0.00 0.00 0.00 7.06 0.00
November 13972.33 21-NOV-07:02 8198.00 15028.19 16538.29 0.00 0.00 0.00 0.00 14.24 0.00
December 13784.95 01-DEC-07:03 6558.40 12022.55 13230.63 0.00 0.00 0.00 0.00 1.33 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13696.90   546.53 1669.80 9922.97 0.00 0.00 0.00 0.00 1.15 0.00
Maximum of Months 17885.75   8198.00 15028.19 16538.29 0.00 0.00 0.00 0.00 242.36 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2884.25 20-JAN-07:01 4053.24 6466.81 2976.82 0.00 0.00 0.00 0.00 0.00 3.99
February 3625.41 03-FEB-07:01 4503.60 7185.35 3307.58 0.00 0.00 0.00 0.00 0.00 7.39
March 3736.98 15-MAR-06:01 4503.60 7185.35 3307.58 0.00 0.00 0.00 0.00 0.00 6.98
April 3855.40 12-APR-06:02 2251.80 3592.67 1653.79 0.00 0.00 0.00 0.00 0.94 0.00
May 3894.43 17-MAY-06:02 2251.80 3592.67 1653.79 0.00 0.00 0.00 0.00 1.27 0.00
June 3881.20 16-JUN-06:02 3602.88 5748.28 2646.06 0.00 0.00 0.00 0.00 1.72 0.00
July 4722.16 04-JUL-16:01 250.20 399.19 992.27 0.00 0.00 0.00 0.00 10.72 0.00
August 3905.20 11-AUG-06:02 4053.24 6466.81 2976.82 0.00 0.00 0.00 0.00 1.67 0.00
September 3950.22 01-SEP-06:01 3152.52 5029.74 2315.31 0.00 0.00 0.00 0.00 0.71 0.00
October 3825.19 12-OCT-06:02 2251.80 3592.67 1653.79 0.00 0.00 0.00 0.00 0.68 0.00
November 3816.11 21-NOV-07:02 2251.80 3592.67 1653.79 0.00 0.00 0.00 0.00 1.38 0.00
December 3328.85 01-DEC-07:03 1801.44 2874.14 1323.03 0.00 0.00 0.00 0.00 0.18 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2884.25   250.20 399.19 992.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4722.16   4503.60 7185.35 3307.58 0.00 0.00 0.00 0.00 10.72 7.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 284.34 01-JAN-17:01 16.20 24.30 64.25 0.00 0.00 0.00 0.00 3.93 0.00
February 312.74 20-FEB-17:42 9.72 14.58 38.55 0.00 0.00 0.00 0.00 2.88 0.00
March 303.63 26-MAR-16:01 16.20 24.30 64.25 0.00 0.00 0.00 0.00 5.90 0.00
April 330.81 16-APR-14:51 16.20 48.60 107.08 0.00 0.00 0.00 0.00 9.33 0.00
May 353.89 29-MAY-16:01 16.20 24.30 64.25 0.00 0.00 0.00 0.00 23.30 0.00
June 342.77 11-JUN-18:42 0.00 14.58 38.55 0.00 0.00 0.00 0.00 9.12 0.00
July 354.57 04-JUL-16:02 16.20 24.30 64.25 0.00 0.00 0.00 0.00 12.44 0.00
August 337.51 20-AUG-16:01 16.20 24.30 64.25 0.00 0.00 0.00 0.00 11.13 0.00
September 339.28 10-SEP-16:02 16.20 24.30 64.25 0.00 0.00 0.00 0.00 16.30 0.00
October 330.51 09-OCT-17:22 9.72 14.58 38.55 0.00 0.00 0.00 0.00 6.75 0.00
November 299.68 05-NOV-16:01 16.20 24.30 64.25 0.00 0.00 0.00 0.00 2.92 0.00
December 302.60 10-DEC-16:31 14.58 43.74 96.37 0.00 0.00 0.00 0.00 9.68 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 284.34   0.00 14.58 38.55 0.00 0.00 0.00 0.00 2.88 0.00
Maximum of Months 354.57   16.20 48.60 107.08 0.00 0.00 0.00 0.00 23.30 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9173.38 02-JAN-14:30 2808.27 1053.00 1931.89 0.00 0.00 0.00 0.00 21.70 0.00
February 11558.76 20-FEB-15:41 1092.11 819.00 6761.62 0.00 0.00 0.00 0.00 41.09 0.00
March 8774.38 01-MAR-14:00 2808.27 1053.00 1931.89 0.00 0.00 0.00 0.00 5.43 0.00
April 11664.78 16-APR-14:51 1560.15 1170.00 9659.46 0.00 0.00 0.00 0.00 104.20 0.00
May 11091.78 29-MAY-15:21 1560.15 1170.00 9659.46 0.00 0.00 0.00 0.00 304.94 0.00
June 8155.16 01-JUN-14:10 5616.55 2106.00 3863.79 0.00 0.00 0.00 0.00 47.10 0.00
July 11765.17 30-JUL-12:41 1560.15 1170.00 9659.46 0.00 0.00 0.00 0.00 186.11 0.00
August 9009.21 31-AUG-13:10 5616.55 2106.00 3863.79 0.00 0.00 0.00 0.00 39.70 0.00
September 9194.53 29-SEP-12:40 2808.27 1053.00 1931.89 0.00 0.00 0.00 0.00 36.35 0.00
October 9503.43 06-OCT-12:30 2808.27 1053.00 1931.89 0.00 0.00 0.00 0.00 16.10 0.00
November 9392.61 07-NOV-13:40 2808.27 1053.00 1931.89 0.00 0.00 0.00 0.00 21.22 0.00
December 9186.83 04-DEC-14:10 5616.55 2106.00 3863.79 0.00 0.00 0.00 0.00 12.19 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8155.16   1092.11 819.00 1931.89 0.00 0.00 0.00 0.00 5.43 0.00
Maximum of Months 11765.17   5616.55 2106.00 9659.46 0.00 0.00 0.00 0.00 304.94 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2593.87 27-JAN-14:30 1278.84 479.52 879.75 0.00 0.00 0.00 0.00 0.00 0.00
February 2655.00 22-FEB-15:05 2557.69 959.04 1759.51 0.00 0.00 0.00 0.00 0.00 0.00
March 2588.41 01-MAR-14:10 2557.69 959.04 1759.51 0.00 0.00 0.00 0.00 0.00 0.00
April 2828.92 16-APR-14:52 710.47 532.80 4398.77 0.00 0.00 0.00 0.00 0.00 0.00
May 2731.20 07-MAY-11:22 710.47 532.80 4398.77 0.00 0.00 0.00 0.00 0.00 0.00
June 2748.04 04-JUN-12:42 639.42 479.52 3958.89 0.00 0.00 0.00 0.00 0.00 0.00
July 2840.26 16-JUL-13:22 710.47 532.80 4398.77 0.00 0.00 0.00 0.00 0.00 0.00
August 2686.51 31-AUG-14:40 1278.84 479.52 879.75 0.00 0.00 0.00 0.00 0.00 0.00
September 2667.64 08-SEP-15:10 1278.84 479.52 879.75 0.00 0.00 0.00 0.00 0.00 0.00
October 2678.46 06-OCT-13:00 1278.84 479.52 879.75 0.00 0.00 0.00 0.00 0.00 0.00
November 2693.32 20-NOV-20:21 0.00 1438.56 2375.34 0.00 0.00 0.00 0.00 0.00 0.00
December 2599.90 14-DEC-14:10 2557.69 959.04 1759.51 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2588.41   0.00 479.52 879.75 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2840.26   2557.69 1438.56 4398.77 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 395.78 16-JAN-12:51 22.68 68.04 149.91 0.00 0.00 0.00 0.00 0.00 0.00
February 409.60 26-FEB-17:51 20.16 30.24 79.95 0.00 0.00 0.00 0.00 0.00 0.00
March 394.29 12-MAR-16:01 25.20 37.80 99.94 0.00 0.00 0.00 0.00 0.00 0.00
April 435.48 16-APR-14:52 25.20 75.60 166.57 0.00 0.00 0.00 0.00 0.00 0.00
May 420.70 07-MAY-11:22 25.20 75.60 166.57 0.00 0.00 0.00 0.00 0.00 0.00
June 429.10 04-JUN-12:42 22.68 68.04 149.91 0.00 0.00 0.00 0.00 0.00 0.00
July 445.66 04-JUL-16:02 25.20 37.80 99.94 0.00 0.00 0.00 0.00 0.00 0.00
August 430.55 11-AUG-21:21 0.00 68.04 89.95 0.00 0.00 0.00 0.00 0.00 0.00
September 414.49 10-SEP-16:02 25.20 37.80 99.94 0.00 0.00 0.00 0.00 0.00 0.00
October 404.67 22-OCT-16:42 15.12 22.68 59.96 0.00 0.00 0.00 0.00 0.00 0.00
November 431.14 20-NOV-20:21 0.00 204.12 89.95 0.00 0.00 0.00 0.00 0.00 0.00
December 391.54 12-DEC-07:02 453.60 680.40 333.14 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 391.54   0.00 22.68 59.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 445.66   453.60 680.40 333.14 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 445.03 20-JAN-07:02 209.95 787.32 96.60 0.00 0.00 0.00 0.00 0.00 0.00
February 449.25 23-FEB-07:02 209.95 787.32 96.60 0.00 0.00 0.00 0.00 0.00 0.00
March 448.55 22-MAR-06:02 233.28 874.80 107.33 0.00 0.00 0.00 0.00 0.00 0.00
April 473.37 16-APR-14:52 12.96 97.20 53.66 0.00 0.00 0.00 0.00 0.00 0.00
May 458.46 07-MAY-11:22 12.96 97.20 53.66 0.00 0.00 0.00 0.00 0.00 0.00
June 467.13 04-JUN-12:42 11.66 87.48 48.30 0.00 0.00 0.00 0.00 0.00 0.00
July 482.88 04-JUL-16:02 12.96 48.60 32.20 0.00 0.00 0.00 0.00 0.00 0.00
August 461.22 11-AUG-21:21 0.00 87.48 28.98 0.00 0.00 0.00 0.00 0.00 0.00
September 451.77 10-SEP-16:02 12.96 48.60 32.20 0.00 0.00 0.00 0.00 0.00 0.00
October 434.85 22-OCT-16:42 7.78 29.16 19.32 0.00 0.00 0.00 0.00 0.00 0.00
November 463.13 20-NOV-20:21 0.00 262.44 28.98 0.00 0.00 0.00 0.00 0.00 0.00
December 445.27 12-DEC-07:02 233.28 874.80 107.33 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 434.85   0.00 29.16 19.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 482.88   233.28 874.80 107.33 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 214.50 06-JAN-07:03 72.58 272.16 33.39 0.00 0.00 0.00 0.00 0.00 0.00
February 385.15 03-FEB-07:01 181.44 680.40 83.48 0.00 0.00 0.00 0.00 0.00 0.00
March 386.49 15-MAR-06:01 181.44 680.40 83.48 0.00 0.00 0.00 0.00 0.00 0.00
April 294.50 12-APR-06:02 90.72 340.20 41.74 0.00 0.00 0.00 0.00 0.00 0.00
May 357.85 10-MAY-06:02 90.72 340.20 41.74 0.00 0.00 0.00 0.00 0.00 0.00
June 384.61 16-JUN-06:01 145.15 544.32 66.78 0.00 0.00 0.00 0.00 0.00 0.00
July 374.35 13-JUL-06:02 108.86 408.24 50.09 0.00 0.00 0.00 0.00 0.00 0.00
August 375.53 02-AUG-06:01 145.15 544.32 66.78 0.00 0.00 0.00 0.00 0.00 0.00
September 395.08 01-SEP-06:01 127.01 476.28 58.43 0.00 0.00 0.00 0.00 0.00 0.00
October 349.88 03-OCT-06:01 145.15 544.32 66.78 0.00 0.00 0.00 0.00 0.00 0.00
November 371.87 30-NOV-07:02 108.86 408.24 50.09 0.00 0.00 0.00 0.00 0.00 0.00
December 235.61 01-DEC-07:03 72.58 272.16 33.39 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 214.50   72.58 272.16 33.39 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 395.08   181.44 680.40 83.48 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2186.10 26-JAN-14:50 1028.26 642.60 518.59 0.00 0.00 0.00 0.00 0.00 0.00
February 2277.54 20-FEB-15:41 399.88 499.80 1815.07 0.00 0.00 0.00 0.00 0.00 0.00
March 2198.47 21-MAR-14:20 1028.26 642.60 518.59 0.00 0.00 0.00 0.00 0.00 0.00
April 2396.58 16-APR-14:52 571.26 714.00 2592.96 0.00 0.00 0.00 0.00 0.00 0.00
May 2296.54 07-MAY-11:22 571.26 714.00 2592.96 0.00 0.00 0.00 0.00 0.00 0.00
June 2322.38 04-JUN-12:42 514.13 642.60 2333.66 0.00 0.00 0.00 0.00 0.00 0.00
July 2406.89 04-JUL-16:02 571.26 357.00 1555.78 0.00 0.00 0.00 0.00 0.00 0.00
August 2296.83 31-AUG-14:40 1028.26 642.60 518.59 0.00 0.00 0.00 0.00 0.00 0.00
September 2275.97 08-SEP-15:30 1028.26 642.60 518.59 0.00 0.00 0.00 0.00 0.00 0.00
October 2274.71 06-OCT-13:00 1028.26 642.60 518.59 0.00 0.00 0.00 0.00 0.00 0.00
November 2352.78 20-NOV-20:21 0.00 1927.80 1400.20 0.00 0.00 0.00 0.00 0.00 0.00
December 2190.71 14-DEC-14:10 2056.52 1285.20 1037.18 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2186.10   0.00 357.00 518.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2406.89   2056.52 1927.80 2592.96 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13954.69 15-JAN-15:22 163.30 1224.72 7412.81 0.00 0.00 0.00 0.00 0.00 1.22
February 14845.00 20-FEB-15:41 190.51 1428.84 8648.28 0.00 0.00 0.00 0.00 15.65 0.00
March 13997.24 12-MAR-16:01 272.16 1020.60 7412.81 0.00 0.00 0.00 0.00 0.00 20.95
April 15130.98 16-APR-14:51 272.16 2041.20 12354.69 0.00 0.00 0.00 0.00 75.44 0.00
May 14895.19 29-MAY-16:01 272.16 1020.60 7412.81 0.00 0.00 0.00 0.00 227.49 0.00
June 13958.26 11-JUN-14:41 190.51 1428.84 8648.28 0.00 0.00 0.00 0.00 82.20 0.00
July 14852.63 30-JUL-14:01 272.16 2041.20 12354.69 0.00 0.00 0.00 0.00 122.47 0.00
August 14126.04 20-AUG-16:01 272.16 1020.60 7412.81 0.00 0.00 0.00 0.00 104.43 0.00
September 14242.91 17-SEP-16:01 272.16 1020.60 7412.81 0.00 0.00 0.00 0.00 172.35 0.00
October 14208.14 09-OCT-16:01 272.16 1020.60 7412.81 0.00 0.00 0.00 0.00 46.12 0.00
November 14036.84 19-NOV-14:21 244.94 1837.08 11119.22 0.00 0.00 0.00 0.00 44.57 0.00
December 14315.25 10-DEC-15:11 272.16 2041.20 12354.69 0.00 0.00 0.00 0.00 96.52 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13954.69   163.30 1020.60 7412.81 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15130.98   272.16 2041.20 12354.69 0.00 0.00 0.00 0.00 227.49 20.95



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7513.23 15-JAN-15:22 82.94 622.08 3765.24 0.00 0.00 0.00 0.00 0.00 9.65
February 7955.35 20-FEB-15:41 96.77 725.76 4392.78 0.00 0.00 0.00 0.00 6.61 0.00
March 7433.08 12-MAR-16:01 138.24 518.40 3765.24 0.00 0.00 0.00 0.00 0.00 18.83
April 8076.23 16-APR-14:51 138.24 1036.80 6275.40 0.00 0.00 0.00 0.00 56.11 0.00
May 7984.27 29-MAY-16:01 138.24 518.40 3765.24 0.00 0.00 0.00 0.00 169.69 0.00
June 7425.58 11-JUN-16:01 138.24 518.40 3765.24 0.00 0.00 0.00 0.00 103.38 0.00
July 7970.76 30-JUL-14:01 138.24 1036.80 6275.40 0.00 0.00 0.00 0.00 91.34 0.00
August 7538.62 20-AUG-16:01 138.24 518.40 3765.24 0.00 0.00 0.00 0.00 77.87 0.00
September 7635.58 10-SEP-16:02 138.24 518.40 3765.24 0.00 0.00 0.00 0.00 118.52 0.00
October 7593.43 09-OCT-16:01 138.24 518.40 3765.24 0.00 0.00 0.00 0.00 33.74 0.00
November 7528.14 19-NOV-13:41 138.24 1036.80 6275.40 0.00 0.00 0.00 0.00 27.75 0.00
December 7643.45 10-DEC-15:11 138.24 1036.80 6275.40 0.00 0.00 0.00 0.00 70.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7425.58   82.94 518.40 3765.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8076.23   138.24 1036.80 6275.40 0.00 0.00 0.00 0.00 169.69 18.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 432.41 26-JAN-14:40 46.66 291.60 21.47 0.00 0.00 0.00 0.00 0.00 0.00
February 750.71 03-FEB-07:01 466.56 2916.00 214.66 0.00 0.00 0.00 0.00 0.00 0.00
March 702.13 15-MAR-06:01 466.56 2916.00 214.66 0.00 0.00 0.00 0.00 0.00 0.00
April 515.18 14-APR-12:40 46.66 291.60 21.47 0.00 0.00 0.00 0.00 0.00 0.00
May 543.46 18-MAY-13:10 93.31 583.20 42.93 0.00 0.00 0.00 0.00 0.00 0.00
June 646.74 08-JUN-06:01 419.90 2624.40 193.19 0.00 0.00 0.00 0.00 0.00 0.00
July 559.90 28-JUL-15:10 46.66 291.60 21.47 0.00 0.00 0.00 0.00 0.00 0.00
August 574.03 18-AUG-06:01 419.90 2624.40 193.19 0.00 0.00 0.00 0.00 0.00 0.00
September 544.06 22-SEP-06:01 419.90 2624.40 193.19 0.00 0.00 0.00 0.00 0.00 0.00
October 526.17 06-OCT-12:50 46.66 291.60 21.47 0.00 0.00 0.00 0.00 0.00 0.00
November 468.70 08-NOV-13:50 46.66 291.60 21.47 0.00 0.00 0.00 0.00 0.00 0.00
December 439.33 08-DEC-14:20 46.66 291.60 21.47 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 432.41   46.66 291.60 21.47 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 750.71   466.56 2916.00 214.66 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2726.63 13-JAN-10:30 309.99 568.26 625.36 0.00 0.00 0.00 0.00 8.81 0.00
February 2855.09 28-FEB-10:10 309.99 568.26 625.36 0.00 0.00 0.00 0.00 6.96 0.00
March 3471.58 27-MAR-10:30 309.99 568.26 625.36 0.00 0.00 0.00 0.00 3.88 0.00
April 6148.91 16-APR-12:11 172.22 631.40 3126.80 0.00 0.00 0.00 0.00 41.85 0.00
May 6304.37 07-MAY-10:01 172.22 631.40 3126.80 0.00 0.00 0.00 0.00 20.42 0.00
June 5984.48 11-JUN-10:01 120.55 441.98 2188.76 0.00 0.00 0.00 0.00 35.66 0.00
July 6435.88 30-JUL-11:21 172.22 631.40 3126.80 0.00 0.00 0.00 0.00 42.32 0.00
August 5759.87 20-AUG-11:22 103.33 378.84 1876.08 0.00 0.00 0.00 0.00 91.38 0.00
September 5853.20 24-SEP-10:01 120.55 441.98 2188.76 0.00 0.00 0.00 0.00 32.97 0.00
October 5764.53 09-OCT-10:41 120.55 441.98 2188.76 0.00 0.00 0.00 0.00 43.46 0.00
November 3169.49 07-NOV-10:00 309.99 568.26 625.36 0.00 0.00 0.00 0.00 4.20 0.00
December 2835.30 08-DEC-10:30 309.99 568.26 625.36 0.00 0.00 0.00 0.00 11.44 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2726.63   103.33 378.84 625.36 0.00 0.00 0.00 0.00 3.88 0.00
Maximum of Months 6435.88   309.99 631.40 3126.80 0.00 0.00 0.00 0.00 91.38 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: NE STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2658.83 01-JAN-14:51 40.32 128.66 266.51 0.00 0.00 0.00 0.00 19.53 0.00
February 1579.82 11-FEB-14:00 30.24 64.33 53.30 0.00 0.00 0.00 0.00 42.18 0.00
March 3077.08 05-MAR-14:02 30.24 96.49 199.88 0.00 0.00 0.00 0.00 103.98 0.00
April 3234.67 09-APR-13:11 45.36 144.74 299.82 0.00 0.00 0.00 0.00 55.03 0.00
May 3271.56 29-MAY-16:12 30.24 48.25 119.93 0.00 0.00 0.00 0.00 291.78 0.00
June 3326.50 25-JUN-13:51 50.40 160.82 333.14 0.00 0.00 0.00 0.00 178.75 0.00
July 3361.68 23-JUL-12:51 50.40 160.82 333.14 0.00 0.00 0.00 0.00 134.71 0.00
August 3296.25 06-AUG-14:02 30.24 96.49 199.88 0.00 0.00 0.00 0.00 151.02 0.00
September 3526.11 10-SEP-12:31 50.40 160.82 333.14 0.00 0.00 0.00 0.00 126.25 0.00
October 3238.05 22-OCT-12:51 50.40 160.82 333.14 0.00 0.00 0.00 0.00 47.23 0.00
November 3062.35 05-NOV-14:31 45.36 144.74 299.82 0.00 0.00 0.00 0.00 44.58 0.00
December 3112.65 10-DEC-14:31 50.40 160.82 333.14 0.00 0.00 0.00 0.00 141.46 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1579.82   30.24 48.25 53.30 0.00 0.00 0.00 0.00 19.53 0.00
Maximum of Months 3526.11   50.40 160.82 333.14 0.00 0.00 0.00 0.00 291.78 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: NW ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1433.63 17-JAN-16:40 22.68 120.62 55.52 0.00 0.00 0.00 0.00 0.00 0.50
February 2640.06 20-FEB-17:51 11.34 60.31 149.91 0.00 0.00 0.00 0.00 0.00 10.55
March 2557.51 12-MAR-17:02 7.56 40.21 99.94 0.00 0.00 0.00 0.00 0.00 26.57
April 2702.22 02-APR-17:12 7.56 40.21 99.94 0.00 0.00 0.00 0.00 0.00 20.85
May 2692.59 29-MAY-16:52 7.56 40.21 99.94 0.00 0.00 0.00 0.00 211.50 0.00
June 2628.46 25-JUN-16:31 11.34 60.31 149.91 0.00 0.00 0.00 0.00 24.98 0.00
July 2657.87 09-JUL-16:52 7.56 40.21 99.94 0.00 0.00 0.00 0.00 97.20 0.00
August 2684.60 06-AUG-16:01 12.60 67.01 166.57 0.00 0.00 0.00 0.00 58.38 0.00
September 2722.51 10-SEP-16:31 10.08 53.61 133.26 0.00 0.00 0.00 0.00 122.12 0.00
October 2746.06 15-OCT-16:32 7.56 40.21 99.94 0.00 0.00 0.00 0.00 40.03 0.00
November 2592.98 05-NOV-16:31 10.08 53.61 133.26 0.00 0.00 0.00 0.00 35.98 0.00
December 2620.93 10-DEC-15:11 12.60 134.02 277.61 0.00 0.00 0.00 0.00 89.12 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1433.63   7.56 40.21 55.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2746.06   22.68 134.02 277.61 0.00 0.00 0.00 0.00 211.50 26.57



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: NW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1478.89 02-JAN-15:00 103.68 165.42 76.15 0.00 0.00 0.00 0.00 39.99 0.00
February 1579.00 02-FEB-14:00 103.68 165.42 76.15 0.00 0.00 0.00 0.00 82.47 0.00
March 3529.24 05-MAR-14:42 34.56 110.28 228.44 0.00 0.00 0.00 0.00 109.68 0.00
April 3631.95 09-APR-13:51 51.84 165.42 342.66 0.00 0.00 0.00 0.00 50.63 0.00
May 3830.50 29-MAY-16:12 34.56 55.14 137.06 0.00 0.00 0.00 0.00 325.26 0.00
June 3839.38 25-JUN-13:51 57.60 183.80 380.73 0.00 0.00 0.00 0.00 205.31 0.00
July 3851.27 23-JUL-12:51 57.60 183.80 380.73 0.00 0.00 0.00 0.00 157.26 0.00
August 3802.60 06-AUG-14:42 34.56 110.28 228.44 0.00 0.00 0.00 0.00 210.47 0.00
September 3971.72 10-SEP-12:31 57.60 183.80 380.73 0.00 0.00 0.00 0.00 157.82 0.00
October 3660.78 22-OCT-13:31 57.60 183.80 380.73 0.00 0.00 0.00 0.00 77.58 0.00
November 3522.02 05-NOV-15:11 51.84 165.42 342.66 0.00 0.00 0.00 0.00 37.28 0.00
December 3561.52 10-DEC-15:11 57.60 183.80 380.73 0.00 0.00 0.00 0.00 145.27 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1478.89   34.56 55.14 76.15 0.00 0.00 0.00 0.00 37.28 0.00
Maximum of Months 3971.72   103.68 183.80 380.73 0.00 0.00 0.00 0.00 325.26 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: SW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2005.74 08-JAN-15:51 25.92 82.71 171.33 0.00 0.00 0.00 0.00 0.00 49.03
February 2002.87 20-FEB-16:31 25.92 82.71 171.33 0.00 0.00 0.00 0.00 5.33 0.00
March 1905.87 26-MAR-15:02 17.28 55.14 114.22 0.00 0.00 0.00 0.00 35.80 0.00
April 2001.29 02-APR-16:32 17.28 27.57 68.53 0.00 0.00 0.00 0.00 0.00 6.20
May 1970.38 29-MAY-16:12 17.28 27.57 68.53 0.00 0.00 0.00 0.00 165.92 0.00
June 1943.37 25-JUN-14:31 28.80 91.90 190.36 0.00 0.00 0.00 0.00 63.29 0.00
July 1949.23 30-JUL-15:32 17.28 55.14 114.22 0.00 0.00 0.00 0.00 131.77 0.00
August 1978.12 06-AUG-16:01 28.80 45.95 114.22 0.00 0.00 0.00 0.00 38.92 0.00
September 2062.90 10-SEP-12:31 28.80 91.90 190.36 0.00 0.00 0.00 0.00 79.01 0.00
October 2083.46 15-OCT-16:32 17.28 27.57 68.53 0.00 0.00 0.00 0.00 20.95 0.00
November 1962.54 19-NOV-15:01 25.92 82.71 171.33 0.00 0.00 0.00 0.00 14.19 0.00
December 2146.99 03-DEC-15:01 20.16 64.33 133.26 0.00 0.00 0.00 0.00 0.00 22.47
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1905.87   17.28 27.57 68.53 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2146.99   28.80 91.90 190.36 0.00 0.00 0.00 0.00 165.92 49.03



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.301027E+12 251407.90 02-JAN-13:00 0.398236E+11 64551.94 21-JAN-07:10
February 0.282227E+12 238398.01 02-FEB-13:00 0.362004E+11 97539.18 04-FEB-07:10
March 0.328548E+12 247393.20 13-MAR-14:00 0.410172E+11 60910.18 16-MAR-06:10
April 0.325288E+12 264477.74 14-APR-14:00 0.383086E+11 46705.94 15-APR-06:10
May 0.368670E+12 269728.20 31-MAY-12:00 0.412633E+11 45912.70 13-MAY-06:10
June 0.380536E+12 271516.00 08-JUN-14:00 0.413588E+11 47722.86 10-JUN-06:10
July 0.384259E+12 285805.09 28-JUL-15:09 0.415531E+11 47924.01 22-JUL-06:10
August 0.400427E+12 277053.59 21-AUG-15:00 0.428095E+11 47304.43 05-AUG-06:10
September 0.371156E+12 271849.81 20-SEP-15:00 0.402057E+11 47587.12 30-SEP-06:10
October 0.363275E+12 267097.57 03-OCT-14:30 0.400927E+11 48783.06 07-OCT-06:10
November 0.330130E+12 255390.14 03-NOV-14:09 0.375971E+11 51662.07 13-NOV-07:10
December 0.304577E+12 243960.62 08-DEC-15:30 0.394456E+11 74097.31 16-DEC-07:10
             
Annual Sum or Average 0.414012E+13     0.479676E+12    
Minimum of Months 0.282227E+12 238398.01   0.362004E+11 45912.70  
Maximum of Months 0.400427E+12 285805.09   0.428095E+11 97539.18  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.521685E+11 0.226930E+11 0.112964E+12 0.00 0.371871E+11 70461846.19 45959.29 0.757528E+11 0.00 0.191440E+09 0.00 0.00 0.00
February 0.474357E+11 0.195820E+11 0.102360E+12 0.00 0.355471E+11 63629424.44 5971678.58 0.769960E+11 0.00 0.236027E+09 0.00 0.00 0.00
March 0.560919E+11 0.204437E+11 0.116528E+12 0.00 0.425149E+11 71978475.47 25569.14 0.926734E+11 0.00 0.224359E+09 0.00 0.00 0.00
April 0.505909E+11 0.185753E+11 0.109536E+12 0.00 0.425300E+11 68886045.17 365.39 0.103980E+12 0.00 6599911.18 0.00 0.00 0.00
May 0.541260E+11 0.181036E+11 0.114746E+12 0.00 0.470001E+11 75865752.78 0.00 0.134612E+12 0.00 5694408.88 0.00 0.00 0.00
June 0.538535E+11 0.170243E+11 0.112400E+12 0.00 0.477138E+11 78152132.99 0.00 0.149463E+12 0.00 3862572.93 0.00 0.00 0.00
July 0.508634E+11 0.177499E+11 0.111882E+12 0.00 0.474836E+11 81052200.17 0.00 0.156193E+12 0.00 5878673.79 0.00 0.00 0.00
August 0.560836E+11 0.187113E+11 0.116528E+12 0.00 0.491611E+11 80790178.54 0.00 0.159858E+12 0.00 3640840.92 0.00 0.00 0.00
September 0.505826E+11 0.192737E+11 0.109536E+12 0.00 0.458879E+11 76457241.13 0.00 0.145794E+12 0.00 4956242.62 0.00 0.00 0.00
October 0.521767E+11 0.211693E+11 0.112964E+12 0.00 0.445983E+11 72427515.21 3143.82 0.132288E+12 0.00 6340172.54 0.00 0.00 0.00
November 0.512434E+11 0.216046E+11 0.109917E+12 0.00 0.402831E+11 64149461.19 25874.16 0.106997E+12 0.00 21164146.09 0.00 0.00 0.00
December 0.508634E+11 0.229289E+11 0.111882E+12 0.00 0.378167E+11 70873127.39 141.82 0.809112E+11 0.00 0.104171E+09 0.00 0.00 0.00
                           
Annual Sum or Average 0.626080E+12 0.237860E+12 0.134124E+13 0.00 0.517724E+12 0.874723E+09 6072732.19 0.141552E+13 0.00 0.814135E+09 0.00 0.00 0.00
Minimum of Months 0.474357E+11 0.170243E+11 0.102360E+12 0.00 0.355471E+11 63629424.44 0.00 0.757528E+11 0.00 3640840.92 0.00 0.00 0.00
Maximum of Months 0.560919E+11 0.229289E+11 0.116528E+12 0.00 0.491611E+11 81052200.17 5971678.58 0.159858E+12 0.00 0.236027E+09 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.158619E+11 0.00 0.155048E+11 0.00 0.845688E+10 0.00 0.00
February 0.143713E+11 0.00 0.142000E+11 0.00 0.762908E+10 0.00 0.00
March 0.163897E+11 0.00 0.158355E+11 0.00 0.879200E+10 0.00 0.00
April 0.153698E+11 0.00 0.153265E+11 0.00 0.761230E+10 0.00 0.00
May 0.161258E+11 0.00 0.173182E+11 0.00 0.781927E+10 0.00 0.00
June 0.158049E+11 0.00 0.180490E+11 0.00 0.750490E+10 0.00 0.00
July 0.156907E+11 0.00 0.188788E+11 0.00 0.698355E+10 0.00 0.00
August 0.163897E+11 0.00 0.186383E+11 0.00 0.778159E+10 0.00 0.00
September 0.153698E+11 0.00 0.175984E+11 0.00 0.723748E+10 0.00 0.00
October 0.158619E+11 0.00 0.164424E+11 0.00 0.778847E+10 0.00 0.00
November 0.154482E+11 0.00 0.141746E+11 0.00 0.797423E+10 0.00 0.00
December 0.156907E+11 0.00 0.156194E+11 0.00 0.813544E+10 0.00 0.00
               
Annual Sum or Average 0.188374E+12 0.00 0.197586E+12 0.00 0.937152E+11 0.00 0.00
Minimum of Months 0.143713E+11 0.00 0.141746E+11 0.00 0.698355E+10 0.00 0.00
Maximum of Months 0.163897E+11 0.00 0.188788E+11 0.00 0.879200E+10 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 41298.67 02-JAN-07:10 15116.60 01-JAN-00:10 69545.86 02-JAN-07:10 0.00 33633.31 04-JAN-13:00 163.83 21-JAN-07:10 41.88 22-JAN-06:10
February 41298.67 01-FEB-07:10 15116.60 01-FEB-00:10 69545.86 01-FEB-07:10 0.00 34207.12 17-FEB-15:50 252.12 04-FEB-07:10 958.92 04-FEB-06:10
March 41298.67 01-MAR-07:10 15116.60 01-MAR-00:10 69545.86 01-MAR-07:10 0.00 34662.16 31-MAR-16:19 171.69 16-MAR-06:10 42.62 16-MAR-06:10
April 41298.67 03-APR-06:10 15116.60 01-APR-00:10 69545.86 03-APR-06:10 0.00 35524.46 14-APR-15:20 138.98 15-APR-06:10 0.61 02-APR-05:10
May 41298.67 01-MAY-06:10 15116.60 01-MAY-00:10 69545.86 01-MAY-06:10 0.00 36126.78 18-MAY-14:30 138.10 13-MAY-06:10 0.00 01-MAY-00:10
June 41298.67 01-JUN-06:10 15116.60 01-JUN-00:10 69545.86 01-JUN-06:10 0.00 36168.03 09-JUN-14:30 143.25 10-JUN-06:10 0.00 01-JUN-00:10
July 41298.67 03-JUL-06:10 15116.60 01-JUL-00:10 69545.86 03-JUL-06:10 0.00 36543.99 28-JUL-15:20 143.58 22-JUL-06:10 0.00 01-JUL-00:10
August 41298.67 01-AUG-06:10 15116.60 01-AUG-00:10 69545.86 01-AUG-06:10 0.00 35994.54 02-AUG-15:20 141.96 05-AUG-06:10 0.00 01-AUG-00:10
September 41298.67 01-SEP-06:10 15116.60 01-SEP-00:10 69545.86 01-SEP-06:10 0.00 35249.01 07-SEP-14:09 143.63 30-SEP-06:10 0.00 01-SEP-00:10
October 41298.67 02-OCT-06:10 15116.60 01-OCT-00:10 69545.86 02-OCT-06:10 0.00 34816.94 03-OCT-16:00 143.74 07-OCT-06:10 5.24 09-OCT-05:10
November 41298.67 01-NOV-06:10 15116.60 01-NOV-00:10 69545.86 01-NOV-06:10 0.00 34378.40 03-NOV-16:19 139.84 25-NOV-07:10 43.12 12-NOV-06:10
December 41298.67 01-DEC-07:10 15116.60 01-DEC-00:10 69545.86 01-DEC-07:10 0.00 34172.65 07-DEC-15:30 191.85 16-DEC-07:10 0.24 16-DEC-07:10
                           
Annual Sum or Average             0.00            
Minimum of Months 41298.67   15116.60   69545.86   0.00 33633.31   138.10   0.00  
Maximum of Months 41298.67   15116.60   69545.86   0.00 36543.99   252.12   958.92  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 111285.84 02-JAN-13:00 0.00 7717.36 25-JAN-06:30 0.00 0.00 0.00
February 94933.08 02-FEB-13:00 0.00 9892.01 04-FEB-06:49 0.00 0.00 0.00
March 103009.98 13-MAR-14:00 0.00 6134.23 16-MAR-10:00 0.00 0.00 0.00
April 118202.08 14-APR-14:00 0.00 1737.12 09-APR-16:19 0.00 0.00 0.00
May 125821.66 31-MAY-12:00 0.00 1301.76 21-MAY-16:19 0.00 0.00 0.00
June 124664.57 08-JUN-14:00 0.00 1110.43 04-JUN-16:19 0.00 0.00 0.00
July 138442.35 28-JUL-14:00 0.00 1223.12 02-JUL-16:19 0.00 0.00 0.00
August 132544.18 22-AUG-12:00 0.00 1772.90 27-AUG-16:19 0.00 0.00 0.00
September 127135.20 22-SEP-12:00 0.00 1287.33 03-SEP-16:19 0.00 0.00 0.00
October 123061.94 03-OCT-14:30 0.00 1073.34 08-OCT-16:19 0.00 0.00 0.00
November 112226.66 03-NOV-14:09 0.00 2778.01 13-NOV-06:10 0.00 0.00 0.00
December 101273.37 08-DEC-13:00 0.00 9117.36 20-DEC-18:19 0.00 0.00 0.00
                 
Annual Sum or Average     0.00     0.00 0.00 0.00
Minimum of Months 94933.08   0.00 1073.34   0.00 0.00 0.00
Maximum of Months 138442.35   0.00 9892.01   0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 251407.90 02-JAN-13:00 41298.67 68321.12 0.00 0.00 30451.83 50.43 0.00 111285.84 0.00
February 238398.01 02-FEB-13:00 41298.67 68321.12 0.00 0.00 33807.81 37.32 0.00 94933.08 0.00
March 247393.20 13-MAR-14:00 41298.67 69545.86 0.00 0.00 33499.90 38.79 0.00 103009.98 0.00
April 264477.74 14-APR-14:00 41298.67 69545.86 0.00 0.00 35392.82 38.31 0.00 118202.08 0.00
May 269728.20 31-MAY-12:00 41298.67 68321.12 0.00 0.00 34241.79 44.96 0.00 125821.66 0.00
June 271516.00 08-JUN-14:00 41298.67 69545.86 0.00 0.00 35966.31 40.58 0.00 124664.57 0.00
July 285805.09 28-JUL-15:09 41298.67 69545.86 0.00 0.00 36499.41 40.78 0.00 138420.37 0.00
August 277053.59 21-AUG-15:00 41298.67 69545.86 0.00 0.00 34576.33 48.03 0.00 131584.70 0.00
September 271849.81 20-SEP-15:00 41298.67 69545.86 0.00 0.00 34550.77 41.31 0.00 126413.20 0.00
October 267097.57 03-OCT-14:30 41298.67 69545.86 0.00 0.00 33148.99 42.11 0.00 123061.94 0.00
November 255390.14 03-NOV-14:09 41298.67 69545.86 0.00 0.00 32276.88 42.07 0.00 112226.66 0.00
December 243960.62 08-DEC-15:30 41298.67 69545.86 0.00 0.00 31857.54 42.44 0.00 101216.11 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 238398.01   41298.67 68321.12 0.00 0.00 30451.83 37.32 0.00 94933.08 0.00
Maximum of Months 285805.09   41298.67 69545.86 0.00 0.00 36499.41 50.43 0.00 138420.37 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 9905.77 02-JAN-06:10 0.00 58949.08 21-JAN-07:10 0.00 10458.43 17-JAN-13:39 0.00
February 9905.77 01-FEB-06:10 0.00 92586.30 04-FEB-07:10 0.00 10454.34 01-FEB-11:30 0.00
March 9905.77 01-MAR-06:10 0.00 52869.63 11-MAR-07:10 0.00 10176.73 01-MAR-13:00 0.00
April 9905.77 03-APR-05:10 0.00 41103.19 15-APR-06:10 0.00 9617.71 03-APR-10:39 0.00
May 9905.77 01-MAY-05:10 0.00 40309.97 13-MAY-06:10 0.00 9504.90 03-MAY-12:20 0.00
June 9905.77 01-JUN-05:10 0.00 42120.19 10-JUN-06:10 0.00 8767.45 01-JUN-12:50 0.00
July 9905.77 03-JUL-05:10 0.00 42321.33 22-JUL-06:10 0.00 8734.34 03-JUL-10:50 0.00
August 9905.77 01-AUG-05:10 0.00 41701.77 05-AUG-06:10 0.00 8759.12 31-AUG-12:30 0.00
September 9905.77 01-SEP-05:10 0.00 42634.24 30-SEP-06:10 0.00 8915.77 28-SEP-12:20 0.00
October 9905.77 02-OCT-05:10 0.00 43180.33 07-OCT-06:10 0.00 9609.29 31-OCT-12:00 0.00
November 9905.77 01-NOV-05:10 0.00 42876.91 25-NOV-07:10 0.00 9667.76 30-NOV-13:00 0.00
December 9905.77 01-DEC-06:10 0.00 68494.41 16-DEC-07:10 0.00 10450.19 29-DEC-11:20 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 9905.77   0.00 40309.97   0.00 8734.34   0.00
Maximum of Months 9905.77   0.00 92586.30   0.00 10458.43   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 3.00 23.53 3.00 23.53
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 14.00 23.02 14.00 23.02
April 0.00 0.00 0.00 0.00 27.00 23.24 27.00 23.24
May 0.00 0.00 0.00 0.00 89.33 23.16 89.33 23.16
June 0.00 0.00 0.00 0.00 208.33 23.52 208.33 23.52
July 0.00 0.00 0.00 0.00 212.33 23.88 212.33 23.88
August 0.00 0.00 0.00 0.00 235.33 23.86 235.33 23.86
September 0.00 0.00 0.00 0.00 200.83 23.78 200.83 23.78
October 0.00 0.00 0.00 0.00 145.50 23.64 145.50 23.64
November 0.00 0.00 0.00 0.00 92.33 23.46 92.33 23.46
December 0.00 0.00 0.00 0.00 19.33 23.20 19.33 23.20
                 
Annual Sum or Average 0.00   0.00   1247.33 23.66 1247.33 23.66
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 235.33 23.88 235.33 23.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 CLEAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 25.61 0.67 25.61
May 0.00 0.00 0.00 0.00 2.33 25.95 2.33 25.95
June 0.00 0.00 0.00 0.00 3.33 25.76 3.33 25.76
July 0.00 0.00 0.00 0.00 9.17 25.92 9.00 25.92
August 0.00 0.00 0.00 0.00 5.33 25.97 5.33 25.97
September 0.00 0.00 0.00 0.00 5.67 25.88 5.67 25.88
October 0.00 0.00 0.00 0.00 2.67 25.67 2.67 25.67
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   29.17 25.88 29.00 25.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.17 25.97 9.00 25.97



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 25.71 0.00 25.71
February 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
March 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
April 0.00 0.00 0.00 0.00 2.17 25.42 1.50 25.53
May 0.00 0.00 0.00 0.00 5.00 25.00 0.67 25.08
June 0.00 0.00 0.00 0.00 8.83 25.11 2.00 25.22
July 0.00 0.00 0.00 0.00 14.83 25.46 7.17 25.58
August 0.00 0.00 0.00 0.00 10.50 25.27 2.83 25.35
September 0.00 0.00 0.00 0.00 11.00 25.31 4.33 25.42
October 0.00 0.00 0.00 0.00 5.17 25.08 1.00 25.17
November 0.00 0.00 0.00 0.00 1.50 24.93 0.00 24.93
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   59.50 25.26 19.50 25.38
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 14.83 25.71 7.17 25.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 IT HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 LOBBY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.67 25.91 1.67 25.91
March 0.00 0.00 0.00 0.00 0.83 25.77 0.83 25.77
April 0.00 0.00 0.00 0.00 3.17 25.91 3.00 25.92
May 0.00 0.00 0.00 0.00 2.00 25.80 1.33 25.88
June 0.00 0.00 0.00 0.00 2.50 25.48 1.83 25.59
July 0.00 0.00 0.00 0.00 5.83 25.67 4.33 25.79
August 0.00 0.00 0.00 0.00 4.67 25.40 2.67 25.61
September 0.00 0.00 0.00 0.00 5.33 25.53 3.83 25.69
October 0.00 0.00 0.00 0.00 3.50 25.72 3.17 25.78
November 0.00 0.00 0.00 0.00 0.33 25.66 0.33 25.66
December 0.00 0.00 0.00 0.00 1.00 25.73 1.00 25.73
                 
Annual Sum or Average 0.00   0.00   30.83 25.65 24.00 25.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.83 25.91 4.33 25.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.33 25.56 0.00 25.56
March 0.00 0.00 0.00 0.00 0.33 25.63 0.00 25.63
April 0.00 0.00 0.00 0.00 0.50 24.87 0.17 25.05
May 0.00 0.00 0.00 0.00 2.33 24.59 0.00 24.59
June 0.00 0.00 0.00 0.00 3.83 24.58 0.17 24.63
July 0.00 0.00 0.00 0.00 1.50 24.53 0.00 24.53
August 0.00 0.00 0.00 0.00 2.83 24.53 0.00 24.53
September 0.00 0.00 0.00 0.00 2.00 24.59 0.17 24.67
October 0.00 0.00 0.00 0.00 1.50 24.53 0.00 24.53
November 0.00 0.00 0.00 0.00 1.33 24.69 0.17 24.79
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   16.50 24.63 0.67 24.66
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.83 25.63 0.17 25.63



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 25.58 0.00 25.58
February 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
March 0.00 0.00 0.00 0.00 0.17 25.63 0.00 25.63
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.67 24.50 0.00 24.50
June 0.00 0.00 0.00 0.00 0.17 24.47 0.00 24.47
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.33 24.46 0.00 24.46
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.67 24.82 0.00 24.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.67 25.63 0.00 25.63



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 MED GAS

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.50 17.52 0.00 17.52 0.00 17.52 0.00 17.52
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.67 26.08 2.50 26.09
May 0.00 0.00 0.00 0.00 6.83 26.09 6.50 26.09
June 0.00 0.00 0.00 0.00 8.00 26.28 7.00 26.32
July 0.00 0.00 0.00 0.00 17.00 26.46 12.83 26.55
August 0.00 0.00 0.00 0.00 8.17 26.36 7.17 26.41
September 0.00 0.00 0.00 0.00 11.50 26.28 10.17 26.32
October 0.00 0.00 0.00 0.00 6.17 25.92 6.17 25.92
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.50 17.52 0.00 17.52 60.33 26.20 52.33 26.27
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 17.52 0.00 17.52 17.00 26.46 12.83 26.55



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 19.17 0.17 19.17
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 19.19 0.67 19.19
May 0.00 0.00 0.00 0.00 5.33 19.38 5.33 19.38
June 0.00 0.00 0.00 0.00 73.67 19.53 73.67 19.53
July 0.00 0.00 0.00 0.00 137.67 19.75 137.67 19.75
August 0.00 0.00 0.00 0.00 130.83 19.80 130.83 19.80
September 0.00 0.00 0.00 0.00 97.00 19.64 97.00 19.64
October 0.00 0.00 0.00 0.00 49.17 19.55 49.17 19.55
November 0.00 0.00 0.00 0.00 7.67 19.23 7.67 19.23
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   502.17 19.68 502.17 19.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 137.67 19.80 137.67 19.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 2.00 19.32 2.00 19.32
June 0.00 0.00 0.00 0.00 54.67 19.40 54.67 19.40
July 0.00 0.00 0.00 0.00 112.67 19.60 112.67 19.60
August 0.00 0.00 0.00 0.00 110.33 19.57 110.33 19.57
September 0.00 0.00 0.00 0.00 52.33 19.41 52.33 19.41
October 0.00 0.00 0.00 0.00 21.17 19.39 21.17 19.39
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   353.17 19.52 353.17 19.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 112.67 19.60 112.67 19.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 6.33 19.22 6.33 19.22
August 0.00 0.00 0.00 0.00 0.33 19.19 0.33 19.19
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.67 19.22 0.67 19.22
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   7.33 19.22 7.33 19.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.33 19.22 6.33 19.22



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 PACU

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 SCRUB

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 SOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 25.62 0.33 25.62
May 0.00 0.00 0.00 0.00 1.00 25.82 1.00 25.82
June 0.00 0.00 0.00 0.00 2.67 25.81 2.67 25.81
July 0.00 0.00 0.00 0.00 8.33 25.87 8.17 25.87
August 0.00 0.00 0.00 0.00 3.00 25.84 3.00 25.84
September 0.00 0.00 0.00 0.00 2.17 25.64 2.17 25.64
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   17.50 25.82 17.33 25.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.33 25.87 8.17 25.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.33 25.69 0.33 25.69
July 0.00 0.00 0.00 0.00 2.50 25.80 2.50 25.80
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.33 25.56 0.33 25.56
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.17 25.76 3.17 25.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.50 25.80 2.50 25.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.50 26.12 2.50 26.12
May 0.00 0.00 0.00 0.00 1.83 26.06 1.83 26.06
June 0.00 0.00 0.00 0.00 3.67 26.24 3.67 26.24
July 0.00 0.00 0.00 0.00 9.83 26.35 9.83 26.35
August 0.00 0.00 0.00 0.00 3.83 26.06 3.83 26.06
September 0.00 0.00 0.00 0.00 1.83 25.80 1.83 25.80
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   23.50 26.19 23.50 26.19
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.83 26.35 9.83 26.35



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.83 25.61 0.83 25.61
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.83 25.61 0.83 25.61
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 25.61 0.83 25.61



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 108.33 16.89 108.33 16.89 75.83 18.90 75.83 20.08
February 39.50 16.92 39.50 16.92 136.67 21.89 136.67 23.00
March 62.17 15.91 62.17 15.91 150.83 20.69 150.83 22.08
April 8.83 18.84 8.83 18.84 183.50 25.17 183.33 25.46
May 0.00 0.00 0.00 0.00 242.67 27.33 242.50 27.33
June 0.00 0.00 0.00 0.00 257.33 27.56 256.83 27.57
July 0.00 0.00 0.00 0.00 238.33 28.67 235.83 28.68
August 0.00 0.00 0.00 0.00 271.67 28.31 268.83 28.32
September 0.00 0.00 0.00 0.00 238.00 27.68 236.17 27.68
October 0.00 0.00 0.00 0.00 228.17 27.06 227.67 27.06
November 15.00 17.47 15.00 17.47 187.17 24.72 187.17 25.26
December 105.67 17.38 105.67 17.38 80.50 19.43 80.50 20.60
                 
Annual Sum or Average 339.50 16.94 339.50 16.94 2290.67 24.60 2282.17 25.59
Minimum of Months 0.00 0.00 0.00 0.00 75.83 18.90 75.83 20.08
Maximum of Months 108.33 18.84 108.33 18.84 271.67 28.67 268.83 28.68



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.50 25.92 2.50 25.92
February 0.00 0.00 0.00 0.00 3.33 25.89 3.33 25.89
March 0.00 0.00 0.00 0.00 0.33 25.71 0.33 25.71
April 0.00 0.00 0.00 0.00 1.17 25.77 1.17 25.77
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.67 25.86 1.67 25.86
August 0.00 0.00 0.00 0.00 2.00 25.76 2.00 25.76
September 0.00 0.00 0.00 0.00 5.17 26.12 5.17 26.12
October 0.00 0.00 0.00 0.00 6.50 26.14 6.50 26.14
November 0.00 0.00 0.00 0.00 2.00 25.90 2.00 25.90
December 0.00 0.00 0.00 0.00 3.33 26.25 3.33 26.25
                 
Annual Sum or Average 0.00   0.00   28.00 26.02 28.00 26.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.50 26.25 6.50 26.25



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.00 25.79 1.00 25.79
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 25.72 0.83 25.72
May 0.00 0.00 0.00 0.00 0.50 25.81 0.50 25.81
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 25.68 0.33 25.68
August 0.00 0.00 0.00 0.00 0.33 25.66 0.33 25.66
September 0.00 0.00 0.00 0.00 1.17 25.96 1.17 25.96
October 0.00 0.00 0.00 0.00 0.67 25.60 0.67 25.60
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.50 25.61 0.50 25.61
                 
Annual Sum or Average 0.00   0.00   5.33 25.76 5.33 25.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.17 25.96 1.17 25.96



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.17 22.81 2.17 22.81
February 0.00 0.00 0.00 0.00 2.67 23.18 2.67 23.18
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 1.33 24.69 1.33 24.69
November 0.00 0.00 0.00 0.00 9.17 22.94 9.17 22.94
December 0.00 0.00 0.00 0.00 8.17 23.63 8.17 23.63
                 
Annual Sum or Average 0.00   0.00   23.50 23.29 23.50 23.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.17 24.69 9.17 24.69



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.17 25.71 1.17 25.71
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.17 25.71 1.17 25.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.17 25.71 1.17 25.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.17 25.79 0.50 25.81
May 0.00 0.00 0.00 0.00 3.33 25.84 1.33 25.88
June 0.00 0.00 0.00 0.00 5.50 25.55 1.17 25.60
July 0.00 0.00 0.00 0.00 13.17 25.74 4.67 25.78
August 0.00 0.00 0.00 0.00 6.50 25.57 2.83 25.65
September 0.00 0.00 0.00 0.00 5.33 25.61 3.17 25.69
October 0.00 0.00 0.00 0.00 0.33 25.58 0.33 25.58
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   35.33 25.67 14.00 25.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 13.17 25.84 4.67 25.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.50 25.99 2.50 25.99
May 0.00 0.00 0.00 0.00 1.17 25.85 1.17 25.85
June 0.00 0.00 0.00 0.00 3.17 26.02 3.17 26.02
July 0.00 0.00 0.00 0.00 10.00 26.10 10.00 26.10
August 0.00 0.00 0.00 0.00 3.83 25.76 3.83 25.76
September 0.00 0.00 0.00 0.00 3.50 25.95 3.50 25.95
October 0.00 0.00 0.00 0.00 1.33 25.80 1.33 25.80
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   25.50 25.98 25.50 25.98
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 10.00 26.10 10.00 26.10



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.67 25.93 1.67 25.93
March 0.00 0.00 0.00 0.00 0.50 25.58 0.33 25.59
April 0.00 0.00 0.00 0.00 0.67 25.74 0.67 25.74
May 0.00 0.00 0.00 0.00 0.67 25.71 0.67 25.71
June 0.00 0.00 0.00 0.00 0.17 24.47 0.00 24.47
July 0.00 0.00 0.00 0.00 0.83 25.65 0.83 25.65
August 0.00 0.00 0.00 0.00 1.33 25.54 1.17 25.60
September 0.00 0.00 0.00 0.00 3.67 25.65 3.17 25.73
October 0.00 0.00 0.00 0.00 4.67 25.83 4.67 25.83
November 0.00 0.00 0.00 0.00 1.17 25.65 1.17 25.65
December 0.00 0.00 0.00 0.00 2.83 25.88 2.83 25.88
                 
Annual Sum or Average 0.00   0.00   18.17 25.74 17.17 25.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.67 25.93 4.67 25.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.67 25.92 1.67 25.92
May 0.00 0.00 0.00 0.00 0.67 25.74 0.67 25.74
June 0.00 0.00 0.00 0.00 2.17 25.96 2.17 25.96
July 0.00 0.00 0.00 0.00 6.67 26.07 6.67 26.07
August 0.00 0.00 0.00 0.00 1.17 25.71 1.17 25.71
September 0.00 0.00 0.00 0.00 2.17 25.84 2.17 25.84
October 0.00 0.00 0.00 0.00 0.67 25.67 0.67 25.67
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   15.17 25.94 15.17 25.94
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.67 26.07 6.67 26.07



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.33 24.54 0.00 24.54
July 0.00 0.00 0.00 0.00 0.17 24.59 0.00 24.59
August 0.00 0.00 0.00 0.00 0.67 24.54 0.00 24.54
September 0.00 0.00 0.00 0.00 0.17 24.52 0.00 24.52
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.33 24.54 0.00 24.54
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.67 24.59 0.00 24.59



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 X-RAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.33 17.61 0.00 17.61 0.00 17.61 0.00 17.61
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.17 25.89 1.33 25.89
May 0.00 0.00 0.00 0.00 4.50 25.92 2.33 25.96
June 0.00 0.00 0.00 0.00 8.00 25.88 2.83 25.92
July 0.00 0.00 0.00 0.00 15.83 25.97 7.50 26.02
August 0.00 0.00 0.00 0.00 7.17 25.93 4.00 25.97
September 0.00 0.00 0.00 0.00 6.33 25.93 4.67 25.96
October 0.00 0.00 0.00 0.00 1.17 25.66 1.17 25.66
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 17.61 0.00 17.61 45.17 25.86 23.83 25.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 17.61 0.00 17.61 15.83 25.97 7.50 26.02



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 LOCKER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 25.59 0.50 25.59
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.50 25.59 0.50 25.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.50 25.59 0.50 25.59



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.00 25.85 2.00 25.85
May 0.00 0.00 0.00 0.00 3.33 25.81 3.33 25.81
June 0.00 0.00 0.00 0.00 5.17 25.90 4.17 25.93
July 0.00 0.00 0.00 0.00 12.17 25.98 9.83 26.01
August 0.00 0.00 0.00 0.00 3.83 25.99 3.67 26.00
September 0.00 0.00 0.00 0.00 4.67 25.90 4.67 25.90
October 0.00 0.00 0.00 0.00 1.67 25.63 1.67 25.63
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   32.83 25.92 29.33 25.93
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 12.17 25.99 9.83 26.01



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 15.33 26.38 12.00 26.47
February 0.00 0.00 0.00 0.00 12.50 26.36 8.50 26.48
March 0.00 0.00 0.00 0.00 16.17 26.37 8.50 26.51
April 0.00 0.00 0.00 0.00 27.33 26.65 13.00 26.84
May 0.00 0.00 0.00 0.00 49.50 26.38 14.17 26.58
June 0.00 0.00 0.00 0.00 66.50 26.34 11.67 26.50
July 0.00 0.00 0.00 0.00 70.50 26.55 17.67 26.79
August 0.00 0.00 0.00 0.00 62.50 26.33 11.17 26.50
September 0.00 0.00 0.00 0.00 62.67 26.41 14.17 26.61
October 0.00 0.00 0.00 0.00 39.33 26.44 16.00 26.64
November 0.00 0.00 0.00 0.00 23.50 26.24 12.33 26.35
December 0.00 0.00 0.00 0.00 15.83 26.42 12.17 26.51
                 
Annual Sum or Average 0.00   0.00   461.67 26.41 151.33 26.59
Minimum of Months 0.00 0.00 0.00 0.00 12.50 26.24 8.50 26.35
Maximum of Months 0.00 0.00 0.00 0.00 70.50 26.65 17.67 26.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 25.59 0.33 25.59
May 0.00 0.00 0.00 0.00 0.33 25.63 0.33 25.63
June 0.00 0.00 0.00 0.00 1.50 25.71 1.50 25.71
July 0.00 0.00 0.00 0.00 5.33 25.77 5.33 25.77
August 0.00 0.00 0.00 0.00 1.50 25.73 1.50 25.73
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   9.00 25.74 9.00 25.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.33 25.77 5.33 25.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.33 25.58 0.33 25.58
October 0.00 0.00 0.00 0.00 1.83 23.91 1.83 23.91
November 0.00 0.00 0.00 0.00 0.50 22.76 0.50 22.76
December 0.00 0.00 0.00 0.00 0.67 25.80 0.67 25.80
                 
Annual Sum or Average 0.00   0.00   3.33 24.28 3.33 24.28
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.83 25.80 1.83 25.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.33 25.69 0.33 25.69
February 0.00 0.00 0.00 0.00 2.83 25.93 2.83 25.93
March 0.00 0.00 0.00 0.00 1.17 25.81 1.17 25.81
April 0.00 0.00 0.00 0.00 3.50 25.88 3.50 25.88
May 0.00 0.00 0.00 0.00 1.83 25.82 1.83 25.82
June 0.00 0.00 0.00 0.00 2.50 25.86 2.50 25.86
July 0.00 0.00 0.00 0.00 7.67 25.93 7.17 25.94
August 0.00 0.00 0.00 0.00 3.50 25.97 3.50 25.97
September 0.00 0.00 0.00 0.00 5.83 25.96 5.83 25.96
October 0.00 0.00 0.00 0.00 5.83 25.94 5.83 25.94
November 0.00 0.00 0.00 0.00 1.83 25.70 1.83 25.70
December 0.00 0.00 0.00 0.00 3.00 25.88 3.00 25.88
                 
Annual Sum or Average 0.00   0.00   39.83 25.91 39.33 25.91
Minimum of Months 0.00 0.00 0.00 0.00 0.33 25.69 0.33 25.69
Maximum of Months 0.00 0.00 0.00 0.00 7.67 25.97 7.17 25.97



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.17 25.82 2.17 25.82
February 0.00 0.00 0.00 0.00 3.83 26.03 3.83 26.03
March 0.00 0.00 0.00 0.00 1.83 25.92 1.83 25.92
April 0.00 0.00 0.00 0.00 5.17 25.96 4.83 25.97
May 0.00 0.00 0.00 0.00 4.00 25.88 3.83 25.89
June 0.00 0.00 0.00 0.00 4.00 25.94 3.67 25.95
July 0.00 0.00 0.00 0.00 12.00 26.00 10.00 26.03
August 0.00 0.00 0.00 0.00 5.33 26.03 4.67 26.06
September 0.00 0.00 0.00 0.00 8.33 26.09 8.33 26.09
October 0.00 0.00 0.00 0.00 7.83 26.10 7.83 26.10
November 0.00 0.00 0.00 0.00 3.83 25.87 3.83 25.87
December 0.00 0.00 0.00 0.00 3.83 26.07 3.83 26.07
                 
Annual Sum or Average 0.00   0.00   62.17 26.00 58.67 26.01
Minimum of Months 0.00 0.00 0.00 0.00 1.83 25.82 1.83 25.82
Maximum of Months 0.00 0.00 0.00 0.00 12.00 26.10 10.00 26.10



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 25.58 0.17 25.58
February 0.00 0.00 0.00 0.00 0.17 25.56 0.17 25.56
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 5.83 26.17 5.83 26.17
May 0.00 0.00 0.00 0.00 5.50 26.03 5.50 26.03
June 0.00 0.00 0.00 0.00 6.50 26.34 6.50 26.34
July 0.00 0.00 0.00 0.00 13.83 26.51 13.50 26.52
August 0.00 0.00 0.00 0.00 7.00 26.20 7.00 26.20
September 0.00 0.00 0.00 0.00 8.50 26.24 8.50 26.24
October 0.00 0.00 0.00 0.00 4.67 25.91 4.67 25.91
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   52.17 26.26 51.83 26.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 13.83 26.51 13.50 26.52



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: NE STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.50 25.59 0.50 25.59
February 1.83 17.42 0.33 17.46 0.00 17.46 0.00 17.46
March 1.00 17.60 0.00 17.60 1.83 22.94 1.83 24.08
April 0.00 0.00 0.00 0.00 4.83 26.03 4.33 26.05
May 0.00 0.00 0.00 0.00 10.17 26.15 9.00 26.17
June 0.00 0.00 0.00 0.00 12.17 26.11 8.00 26.19
July 0.00 0.00 0.00 0.00 21.17 26.28 13.67 26.37
August 0.00 0.00 0.00 0.00 10.00 26.25 7.83 26.33
September 0.00 0.00 0.00 0.00 12.67 26.20 10.17 26.27
October 0.00 0.00 0.00 0.00 9.67 26.04 9.67 26.04
November 0.00 0.00 0.00 0.00 1.83 25.71 1.83 25.71
December 0.67 17.65 0.00 17.65 1.00 22.56 1.00 23.79
                 
Annual Sum or Average 3.50 17.52 0.33 17.53 85.83 25.78 67.83 25.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.46 0.00 17.46
Maximum of Months 1.83 17.65 0.33 17.65 21.17 26.28 13.67 26.37



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: NW ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 2.67 26.02 2.33 26.04
March 0.00 0.00 0.00 0.00 1.67 25.82 1.00 25.85
April 0.00 0.00 0.00 0.00 7.83 25.95 3.17 26.00
May 0.00 0.00 0.00 0.00 8.33 25.93 2.67 25.97
June 0.00 0.00 0.00 0.00 8.17 25.93 2.50 25.97
July 0.00 0.00 0.00 0.00 17.67 26.00 6.83 26.05
August 0.00 0.00 0.00 0.00 11.50 25.97 4.50 26.03
September 0.00 0.00 0.00 0.00 11.83 26.02 6.50 26.08
October 0.00 0.00 0.00 0.00 7.67 26.03 5.83 26.06
November 0.00 0.00 0.00 0.00 1.67 25.88 1.67 25.88
December 0.00 0.00 0.00 0.00 2.67 25.91 2.67 25.91
                 
Annual Sum or Average 0.00   0.00   81.67 25.97 39.67 26.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 17.67 26.03 6.83 26.08



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: NW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 1.00 17.44 0.00 17.44 0.00 17.44 0.00 17.44
March 0.17 17.72 0.00 17.72 1.50 24.96 1.50 25.34
April 0.00 0.00 0.00 0.00 5.33 25.95 4.50 25.96
May 0.00 0.00 0.00 0.00 13.33 26.07 9.00 26.12
June 0.00 0.00 0.00 0.00 16.00 26.06 7.83 26.14
July 0.00 0.00 0.00 0.00 25.67 26.22 13.00 26.32
August 0.00 0.00 0.00 0.00 15.50 26.05 7.50 26.17
September 0.00 0.00 0.00 0.00 15.33 26.06 10.00 26.14
October 0.00 0.00 0.00 0.00 8.00 25.99 8.00 25.99
November 0.00 0.00 0.00 0.00 1.33 25.66 1.33 25.66
December 0.00 0.00 0.00 0.00 0.67 25.75 0.67 25.75
                 
Annual Sum or Average 1.17 17.48 0.00 17.48 102.67 25.98 63.33 26.08
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 17.72 0.00 17.72 25.67 26.22 13.00 26.32



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: SW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 4.33 26.08 4.33 26.08
February 0.00 0.00 0.00 0.00 5.00 26.17 4.67 26.18
March 0.00 0.00 0.00 0.00 4.33 26.01 3.33 26.05
April 0.00 0.00 0.00 0.00 9.50 26.09 5.33 26.16
May 0.00 0.00 0.00 0.00 11.50 25.95 6.00 25.99
June 0.00 0.00 0.00 0.00 10.83 25.95 4.67 25.99
July 0.00 0.00 0.00 0.00 21.17 26.09 9.33 26.16
August 0.00 0.00 0.00 0.00 15.33 26.02 6.00 26.12
September 0.00 0.00 0.00 0.00 18.17 26.15 9.00 26.26
October 0.00 0.00 0.00 0.00 13.50 26.27 9.00 26.36
November 0.00 0.00 0.00 0.00 8.50 25.28 8.17 25.27
December 0.00 0.00 0.00 0.00 7.00 26.26 7.00 26.26
                 
Annual Sum or Average 0.00   0.00   129.17 26.04 76.83 26.09
Minimum of Months 0.00 0.00 0.00 0.00 4.33 25.28 3.33 25.27
Maximum of Months 0.00 0.00 0.00 0.00 21.17 26.27 9.33 26.36



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 402.33 21.14 5.83 21.10 5.83 21.06
February 364.00 21.03 6.83 20.99 6.83 20.95
March 402.83 20.86 4.83 20.87 4.83 20.87
April 390.00 20.73 5.33 20.71 5.33 20.69
May 403.00 20.69 5.67 20.66 5.67 20.63
June 390.00 20.70 11.00 20.64 11.00 20.59
July 403.00 20.62 6.83 20.59 6.83 20.56
August 403.00 20.75 3.83 20.73 3.83 20.71
September 390.00 20.77 1.83 20.76 1.83 20.75
October 403.00 20.91 0.33 20.91 0.33 20.91
November 389.33 21.02 1.00 21.02 0.83 21.02
December 398.83 21.05 0.50 21.04 0.50 21.04
             
Annual Sum or Average 4739.33 20.86 53.83 20.83 53.67 20.81
Minimum of Months 364.00 20.62 0.33 20.59 0.33 20.56
Maximum of Months 403.00 21.14 11.00 21.10 11.00 21.06



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 BIO HAZ

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 21.67 0.00 21.67 0.00 21.67
February 364.00 21.81 5.00 21.79 5.00 21.77
March 403.00 22.01 0.00 22.01 0.00 22.01
April 390.00 22.21 0.00 22.21 0.00 22.21
May 403.00 22.25 0.00 22.25 0.00 22.25
June 390.00 22.28 0.00 22.28 0.00 22.28
July 403.00 22.32 0.00 22.32 0.00 22.32
August 403.00 22.25 0.00 22.25 0.00 22.25
September 390.00 22.24 0.00 22.24 0.00 22.24
October 403.00 22.17 0.00 22.17 0.00 22.17
November 390.00 22.07 0.00 22.07 0.00 22.07
December 403.00 21.80 0.00 21.80 0.00 21.80
             
Annual Sum or Average 4745.00 22.09 5.00 22.09 5.00 22.09
Minimum of Months 364.00 21.67 0.00 21.67 0.00 21.67
Maximum of Months 403.00 22.32 5.00 22.32 5.00 22.32



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 191.83 22.65 138.00 23.40 32.00 23.51
February 152.00 22.63 110.17 23.47 23.67 23.58
March 195.67 22.70 123.83 23.40 36.50 23.54
April 174.17 22.78 159.00 23.56 39.00 23.68
May 123.17 23.26 255.00 23.65 63.33 23.74
June 205.17 23.76 335.00 23.83 180.83 23.86
July 248.67 24.04 360.00 24.13 242.83 24.12
August 256.50 24.02 360.00 24.06 239.83 24.08
September 202.17 24.05 339.67 24.08 189.83 24.10
October 134.00 23.82 314.33 23.95 105.00 24.01
November 131.50 23.31 247.67 23.79 68.67 23.87
December 176.67 22.82 164.83 23.58 42.50 23.71
             
Annual Sum or Average 2191.50 23.37 2907.50 23.81 1264.00 23.89
Minimum of Months 123.17 22.63 110.17 23.40 23.67 23.51
Maximum of Months 256.50 24.05 360.00 24.13 242.83 24.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 CLEAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 394.50 20.87 4.17 20.85 4.17 20.83
February 361.50 20.86 7.67 20.81 7.67 20.77
March 399.67 20.80 1.67 20.79 1.67 20.78
April 389.67 20.70 12.83 20.63 12.83 20.57
May 403.00 20.63 30.17 20.48 30.17 20.35
June 390.00 20.63 35.33 20.45 35.33 20.30
July 403.00 20.49 57.00 20.24 57.00 20.05
August 403.00 20.64 34.67 20.47 34.67 20.32
September 390.00 20.55 49.00 20.32 49.00 20.13
October 403.00 20.59 38.33 20.41 38.33 20.25
November 386.67 20.76 13.83 20.68 13.83 20.61
December 397.83 20.80 4.17 20.78 4.17 20.76
             
Annual Sum or Average 4721.83 20.69 288.83 20.57 288.83 20.45
Minimum of Months 361.50 20.49 1.67 20.24 1.67 20.05
Maximum of Months 403.00 20.87 57.00 20.85 57.00 20.83



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 20.83 25.50 20.69 25.50 20.57
February 364.00 20.77 28.33 20.61 28.33 20.47
March 403.00 20.75 21.83 20.63 21.83 20.53
April 390.00 20.62 41.67 20.41 41.67 20.23
May 403.00 20.57 49.50 20.33 49.50 20.14
June 390.00 20.59 45.67 20.36 45.67 20.17
July 403.00 20.44 68.17 20.15 68.17 19.93
August 403.00 20.59 45.00 20.37 45.00 20.19
September 390.00 20.50 58.67 20.23 58.67 20.02
October 403.00 20.53 57.00 20.27 57.00 20.06
November 390.00 20.69 37.00 20.50 37.00 20.34
December 403.00 20.73 31.17 20.57 31.17 20.43
             
Annual Sum or Average 4745.00 20.63 509.50 20.42 509.50 20.24
Minimum of Months 364.00 20.44 21.83 20.15 21.83 19.93
Maximum of Months 403.00 20.83 68.17 20.69 68.17 20.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 349.33 22.46 0.00 22.46 0.00 22.46
February 317.17 22.42 0.00 22.42 0.00 22.42
March 348.83 22.39 0.00 22.39 0.00 22.39
April 340.00 22.29 0.00 22.29 0.00 22.29
May 351.00 22.17 0.00 22.17 0.00 22.17
June 338.00 22.12 0.00 22.12 0.00 22.12
July 353.00 22.04 0.00 22.04 0.00 22.04
August 349.00 22.12 0.00 22.12 0.00 22.12
September 340.00 22.06 0.00 22.06 0.00 22.06
October 353.00 22.14 0.00 22.14 0.00 22.14
November 341.83 22.35 0.00 22.35 0.00 22.35
December 351.50 22.43 0.00 22.43 0.00 22.43
             
Annual Sum or Average 4132.67 22.25 0.00 22.25 0.00 22.25
Minimum of Months 317.17 22.04 0.00 22.04 0.00 22.04
Maximum of Months 353.00 22.46 0.00 22.46 0.00 22.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 339.17 22.24 5.33 22.27 2.33 22.28
February 310.17 22.25 9.50 22.24 7.33 22.22
March 329.50 22.25 22.00 22.35 9.50 22.38
April 301.83 22.41 22.67 22.55 5.17 22.56
May 271.83 22.36 52.83 22.71 4.33 22.73
June 258.00 22.34 50.50 22.70 3.50 22.72
July 238.50 22.31 85.50 22.95 0.00 22.95
August 268.67 22.34 55.50 22.74 1.33 22.74
September 241.00 22.32 63.50 22.81 0.00 22.81
October 261.50 22.38 60.50 22.78 2.83 22.80
November 304.67 22.42 30.00 22.58 6.33 22.60
December 316.33 22.31 27.67 22.45 7.67 22.48
             
Annual Sum or Average 3441.17 22.33 485.50 22.59 50.33 22.60
Minimum of Months 238.50 22.24 5.33 22.24 0.00 22.22
Maximum of Months 339.17 22.42 85.50 22.95 9.50 22.95



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 346.50 22.50 17.17 22.61 0.00 22.61
February 321.33 22.48 10.00 22.56 0.00 22.56
March 352.00 22.43 18.00 22.54 2.17 22.55
April 314.17 22.40 29.83 22.62 0.00 22.62
May 315.83 22.35 32.50 22.58 0.00 22.58
June 308.83 22.33 32.67 22.57 0.00 22.57
July 288.17 22.31 62.50 22.76 0.00 22.76
August 317.50 22.31 36.67 22.57 0.00 22.57
September 287.50 22.31 42.67 22.64 0.00 22.64
October 297.17 22.33 44.00 22.67 0.00 22.67
November 316.17 22.46 24.83 22.64 0.00 22.64
December 341.33 22.48 21.67 22.63 0.00 22.63
             
Annual Sum or Average 3806.50 22.39 372.50 22.62 2.17 22.62
Minimum of Months 287.50 22.31 10.00 22.54 0.00 22.55
Maximum of Months 352.00 22.50 62.50 22.76 2.17 22.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 172.00 22.21 124.67 23.34 0.00 23.34
February 135.00 22.29 104.83 23.40 0.00 23.40
March 155.00 22.23 108.50 23.28 0.00 23.28
April 108.00 22.20 125.50 23.58 0.00 23.58
May 26.33 22.20 136.00 24.15 0.00 24.15
June 10.50 22.20 123.00 24.29 0.00 24.29
July 1.50 22.20 167.00 24.32 0.00 24.32
August 17.33 22.20 141.33 23.99 0.00 23.99
September 1.00 22.20 147.00 24.37 0.00 24.37
October 9.67 22.20 147.50 24.43 0.00 24.43
November 44.83 22.22 129.00 24.10 0.00 24.10
December 139.50 22.22 131.17 23.50 0.00 23.50
             
Annual Sum or Average 820.67 22.23 1585.50 23.79 0.00 23.79
Minimum of Months 1.00 22.20 104.83 23.28 0.00 23.28
Maximum of Months 172.00 22.29 167.00 24.43 0.00 24.43



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 338.00 22.53 0.00 22.53 0.00 22.53
February 312.17 22.52 0.00 22.52 0.00 22.52
March 343.17 22.46 0.00 22.46 0.00 22.46
April 336.67 22.42 0.00 22.42 0.00 22.42
May 351.00 22.33 0.00 22.33 0.00 22.33
June 338.00 22.28 0.00 22.28 0.00 22.28
July 353.00 22.25 0.00 22.25 0.00 22.25
August 349.00 22.28 0.00 22.28 0.00 22.28
September 340.00 22.25 0.00 22.25 0.00 22.25
October 353.00 22.32 0.00 22.32 0.00 22.32
November 334.67 22.46 0.00 22.46 0.00 22.46
December 339.67 22.50 0.00 22.50 0.00 22.50
             
Annual Sum or Average 4088.33 22.38 0.00 22.38 0.00 22.38
Minimum of Months 312.17 22.25 0.00 22.25 0.00 22.25
Maximum of Months 353.00 22.53 0.00 22.53 0.00 22.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 IT HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.20 0.00 22.20 0.00 22.20
February 364.00 22.19 0.00 22.19 0.00 22.19
March 403.00 22.26 0.00 22.26 0.00 22.26
April 390.00 22.26 0.00 22.26 0.00 22.26
May 403.00 22.24 0.00 22.24 0.00 22.24
June 390.00 22.23 0.00 22.23 0.00 22.23
July 403.00 22.22 0.00 22.22 0.00 22.22
August 403.00 22.22 0.00 22.22 0.00 22.22
September 390.00 22.19 0.00 22.19 0.00 22.19
October 403.00 22.19 0.00 22.19 0.00 22.19
November 390.00 22.25 0.00 22.25 0.00 22.25
December 403.00 22.21 0.00 22.21 0.00 22.21
             
Annual Sum or Average 4745.00 22.22 0.00 22.22 0.00 22.22
Minimum of Months 364.00 22.19 0.00 22.19 0.00 22.19
Maximum of Months 403.00 22.26 0.00 22.26 0.00 22.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 IT ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 353.00 22.32 0.00 22.32 0.00 22.32
February 318.00 22.32 0.00 22.32 0.00 22.32
March 349.00 22.38 0.00 22.38 0.00 22.38
April 340.00 22.43 0.00 22.43 0.00 22.43
May 351.00 22.42 0.00 22.42 0.00 22.42
June 338.00 22.40 0.00 22.40 0.00 22.40
July 353.00 22.44 0.00 22.44 0.00 22.44
August 349.00 22.39 0.00 22.39 0.00 22.39
September 340.00 22.38 0.00 22.38 0.00 22.38
October 353.00 22.37 0.00 22.37 0.00 22.37
November 342.00 22.42 0.00 22.42 0.00 22.42
December 353.00 22.36 0.00 22.36 0.00 22.36
             
Annual Sum or Average 4139.00 22.39 0.00 22.39 0.00 22.39
Minimum of Months 318.00 22.32 0.00 22.32 0.00 22.32
Maximum of Months 353.00 22.44 0.00 22.44 0.00 22.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 LOBBY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 348.83 22.41 12.00 22.49 0.00 22.49
February 311.00 22.37 27.00 22.56 0.00 22.56
March 322.67 22.31 36.17 22.53 0.00 22.53
April 286.83 22.29 61.00 22.72 0.00 22.72
May 284.33 22.25 73.67 22.73 0.00 22.73
June 286.83 22.25 57.83 22.63 0.00 22.63
July 264.50 22.23 93.83 22.86 0.00 22.86
August 292.17 22.23 67.83 22.67 0.00 22.67
September 269.50 22.24 76.00 22.76 0.00 22.76
October 273.00 22.24 79.17 22.77 0.00 22.77
November 306.50 22.38 35.50 22.62 0.00 22.62
December 320.50 22.36 40.50 22.62 0.00 22.62
             
Annual Sum or Average 3566.67 22.30 660.50 22.66 0.00 22.66
Minimum of Months 264.50 22.23 12.00 22.49 0.00 22.49
Maximum of Months 348.83 22.41 93.83 22.86 0.00 22.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 334.83 22.44 10.00 22.51 0.00 22.51
February 315.17 22.47 8.33 22.53 0.00 22.53
March 348.33 22.40 4.00 22.43 0.00 22.43
April 332.83 22.44 8.67 22.50 0.00 22.50
May 352.33 22.45 3.33 22.47 0.00 22.47
June 360.17 22.46 1.33 22.47 0.00 22.47
July 347.83 22.49 1.83 22.50 0.00 22.50
August 360.83 22.43 1.67 22.44 0.00 22.44
September 333.17 22.44 4.33 22.47 0.00 22.47
October 320.00 22.39 8.17 22.46 0.00 22.46
November 307.83 22.39 12.33 22.49 0.00 22.49
December 321.33 22.40 13.33 22.50 0.00 22.50
             
Annual Sum or Average 4034.67 22.43 77.33 22.48 0.00 22.48
Minimum of Months 307.83 22.39 1.33 22.43 0.00 22.43
Maximum of Months 360.83 22.49 13.33 22.53 0.00 22.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 398.83 20.99 0.33 20.99 0.33 20.99
February 359.17 20.94 6.17 20.93 6.17 20.92
March 402.00 20.97 3.17 21.00 3.17 21.02
April 384.50 20.92 3.67 20.95 1.50 20.97
May 399.33 20.94 1.83 20.96 0.00 20.96
June 386.33 20.92 0.17 20.92 0.00 20.92
July 400.00 20.95 0.00 20.95 0.00 20.95
August 400.33 20.95 0.00 20.95 0.00 20.95
September 384.83 20.94 0.00 20.94 0.00 20.94
October 395.50 20.95 3.00 20.98 0.00 20.98
November 384.83 20.97 2.17 20.99 0.00 20.99
December 394.50 20.98 7.33 21.04 2.00 21.05
             
Annual Sum or Average 4690.17 20.95 27.83 20.97 13.17 20.97
Minimum of Months 359.17 20.92 0.00 20.92 0.00 20.92
Maximum of Months 402.00 20.99 7.33 21.04 6.17 21.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 322.50 22.41 21.33 22.58 0.00 22.58
February 302.83 22.45 20.83 22.61 0.00 22.61
March 330.67 22.36 27.00 22.55 0.00 22.55
April 310.83 22.39 23.33 22.57 0.00 22.57
May 308.67 22.32 35.17 22.57 0.00 22.57
June 307.83 22.32 23.83 22.49 0.00 22.49
July 290.50 22.31 31.17 22.55 0.00 22.55
August 324.67 22.33 28.50 22.52 0.00 22.52
September 297.50 22.34 20.17 22.50 0.00 22.50
October 304.50 22.35 26.83 22.56 0.00 22.56
November 295.00 22.36 26.33 22.58 0.00 22.58
December 313.17 22.39 43.00 22.70 0.00 22.70
             
Annual Sum or Average 3708.67 22.36 327.50 22.57 0.00 22.57
Minimum of Months 290.50 22.31 20.17 22.49 0.00 22.49
Maximum of Months 330.67 22.45 43.00 22.70 0.00 22.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.46 0.00 22.46 0.00 22.46
February 364.00 22.44 0.00 22.44 0.00 22.44
March 403.00 22.41 0.00 22.41 0.00 22.41
April 390.00 22.39 0.00 22.39 0.00 22.39
May 403.00 22.34 0.00 22.34 0.00 22.34
June 390.00 22.30 0.00 22.30 0.00 22.30
July 403.00 22.29 0.00 22.29 0.00 22.29
August 403.00 22.30 0.00 22.30 0.00 22.30
September 390.00 22.29 0.00 22.29 0.00 22.29
October 403.00 22.33 0.00 22.33 0.00 22.33
November 390.00 22.44 0.00 22.44 0.00 22.44
December 403.00 22.46 0.00 22.46 0.00 22.46
             
Annual Sum or Average 4745.00 22.37 0.00 22.37 0.00 22.37
Minimum of Months 364.00 22.29 0.00 22.29 0.00 22.29
Maximum of Months 403.00 22.46 0.00 22.46 0.00 22.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 359.17 22.53 4.00 22.56 0.00 22.56
February 328.17 22.52 8.50 22.59 0.00 22.59
March 360.67 22.44 6.17 22.49 0.00 22.49
April 348.17 22.49 7.50 22.54 0.00 22.54
May 369.33 22.50 3.00 22.52 0.00 22.52
June 367.33 22.48 0.17 22.49 0.00 22.49
July 378.17 22.56 0.00 22.56 0.00 22.56
August 380.17 22.48 0.67 22.49 0.00 22.49
September 373.33 22.54 0.00 22.54 0.00 22.54
October 375.00 22.54 2.00 22.56 0.00 22.56
November 338.50 22.50 8.00 22.56 0.00 22.56
December 351.17 22.50 8.33 22.56 0.00 22.56
             
Annual Sum or Average 4329.17 22.51 48.33 22.54 0.00 22.54
Minimum of Months 328.17 22.44 0.00 22.49 0.00 22.49
Maximum of Months 380.17 22.56 8.50 22.59 0.00 22.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 MED GAS

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 402.17 21.38 35.83 21.28 35.83 21.21
February 360.50 21.65 32.50 21.54 31.83 21.44
March 387.50 21.77 41.00 21.79 29.00 21.75
April 348.67 22.03 35.83 22.23 6.83 22.23
May 325.83 22.20 66.17 22.59 8.00 22.60
June 313.67 22.26 66.17 22.69 5.83 22.71
July 286.67 22.30 98.83 22.99 4.17 23.03
August 326.33 22.28 62.17 22.68 6.83 22.72
September 290.67 22.24 76.17 22.79 0.33 22.79
October 322.67 22.26 68.67 22.67 5.33 22.68
November 361.00 22.02 35.00 22.10 17.33 22.08
December 388.83 21.58 36.17 21.58 30.33 21.55
             
Annual Sum or Average 4114.50 21.97 654.50 22.22 181.67 22.19
Minimum of Months 286.67 21.38 32.50 21.28 0.33 21.21
Maximum of Months 402.17 22.30 98.83 22.99 35.83 23.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 209.83 22.21 123.17 23.21 0.00 23.21
February 162.50 22.21 104.50 23.26 0.00 23.26
March 157.83 22.21 106.50 23.26 0.00 23.26
April 88.50 22.20 121.33 23.71 0.00 23.71
May 33.17 22.20 122.83 24.19 0.00 24.19
June 31.50 22.20 112.83 24.11 0.00 24.11
July 33.67 22.20 140.33 24.24 0.00 24.24
August 31.17 22.20 115.67 24.12 0.00 24.12
September 38.83 22.20 127.50 24.12 0.00 24.12
October 32.83 22.20 136.17 24.25 0.00 24.25
November 71.00 22.21 127.83 23.88 0.33 23.88
December 194.17 22.21 126.83 23.28 0.00 23.28
             
Annual Sum or Average 1085.00 22.21 1465.50 23.68 0.33 23.69
Minimum of Months 31.17 22.20 104.50 23.21 0.00 23.21
Maximum of Months 209.83 22.21 140.33 24.25 0.33 24.25



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 MRI HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 398.50 22.52 0.00 22.52 0.00 22.52
February 358.00 22.46 0.00 22.46 0.00 22.46
March 399.33 22.45 0.00 22.45 0.00 22.45
April 382.83 22.45 0.00 22.45 0.00 22.45
May 400.83 22.45 0.00 22.45 0.00 22.45
June 389.33 22.42 0.00 22.42 0.00 22.42
July 403.00 22.47 0.00 22.47 0.00 22.47
August 402.00 22.42 0.00 22.42 0.00 22.42
September 389.67 22.45 0.00 22.45 0.00 22.45
October 399.33 22.47 0.00 22.47 0.00 22.47
November 382.33 22.51 0.00 22.51 0.00 22.51
December 394.50 22.51 0.00 22.51 0.00 22.51
             
Annual Sum or Average 4699.67 22.47 0.00 22.47 0.00 22.47
Minimum of Months 358.00 22.42 0.00 22.42 0.00 22.42
Maximum of Months 403.00 22.52 0.00 22.52 0.00 22.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 MRI ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 34.83 22.20 135.50 24.26 0.00 24.26
February 32.67 22.21 119.83 24.21 0.00 24.21
March 40.50 22.20 114.17 24.05 0.00 24.05
April 38.33 22.20 130.00 24.14 0.00 24.14
May 29.00 22.20 128.67 24.21 0.00 24.21
June 11.67 22.20 116.33 24.38 0.00 24.38
July 2.33 22.20 143.33 24.65 0.00 24.65
August 10.67 22.20 118.33 24.39 0.00 24.39
September 15.50 22.20 129.50 24.41 0.00 24.41
October 19.17 22.20 140.17 24.40 0.00 24.40
November 16.67 22.20 133.67 24.46 0.00 24.46
December 39.00 22.20 140.17 24.21 0.00 24.21
             
Annual Sum or Average 290.33 22.20 1549.67 24.31 0.00 24.31
Minimum of Months 2.33 22.20 114.17 24.05 0.00 24.05
Maximum of Months 40.50 22.21 143.33 24.65 0.00 24.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 MRI TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 20.85 9.50 20.81 9.50 20.77
February 364.00 20.79 17.17 20.73 17.17 20.67
March 403.00 20.82 8.50 20.81 8.50 20.81
April 390.00 20.75 5.00 20.75 5.00 20.74
May 403.00 20.77 0.00 20.77 0.00 20.77
June 390.00 20.78 0.00 20.78 0.00 20.78
July 403.00 20.72 0.00 20.72 0.00 20.72
August 403.00 20.80 0.17 20.80 0.17 20.80
September 390.00 20.76 0.00 20.76 0.00 20.76
October 403.00 20.77 0.00 20.77 0.00 20.77
November 390.00 20.83 2.67 20.82 2.67 20.81
December 403.00 20.85 5.33 20.84 5.33 20.83
             
Annual Sum or Average 4745.00 20.79 48.33 20.78 48.33 20.77
Minimum of Months 364.00 20.72 0.00 20.72 0.00 20.67
Maximum of Months 403.00 20.85 17.17 20.84 17.17 20.83



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 378.17 22.50 2.67 22.52 0.00 22.52
February 350.83 22.50 0.17 22.50 0.00 22.50
March 391.00 22.45 0.00 22.45 0.00 22.45
April 381.50 22.42 0.00 22.42 0.00 22.42
May 401.33 22.37 0.00 22.37 0.00 22.37
June 390.00 22.32 0.00 22.32 0.00 22.32
July 403.00 22.29 0.00 22.29 0.00 22.29
August 403.00 22.32 0.00 22.32 0.00 22.32
September 390.00 22.30 0.00 22.30 0.00 22.30
October 401.00 22.36 0.00 22.36 0.00 22.36
November 379.00 22.47 0.50 22.48 0.00 22.48
December 380.67 22.47 0.67 22.48 0.00 22.48
             
Annual Sum or Average 4649.50 22.40 4.00 22.40 0.00 22.40
Minimum of Months 350.83 22.29 0.00 22.29 0.00 22.29
Maximum of Months 403.00 22.50 2.67 22.52 0.00 22.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 NURSE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.39 0.00 22.39 0.00 22.39
February 364.00 22.32 0.00 22.32 0.00 22.32
March 403.00 22.30 0.00 22.30 0.00 22.30
April 390.00 22.21 0.00 22.21 0.00 22.21
May 403.00 22.10 0.00 22.10 0.00 22.10
June 390.00 22.05 0.00 22.05 0.00 22.05
July 403.00 21.98 0.00 21.98 0.00 21.98
August 403.00 22.08 0.00 22.08 0.00 22.08
September 390.00 22.07 0.00 22.07 0.00 22.07
October 403.00 22.18 0.00 22.18 0.00 22.18
November 390.00 22.31 0.00 22.31 0.00 22.31
December 403.00 22.37 0.00 22.37 0.00 22.37
             
Annual Sum or Average 4745.00 22.20 0.00 22.20 0.00 22.20
Minimum of Months 364.00 21.98 0.00 21.98 0.00 21.98
Maximum of Months 403.00 22.39 0.00 22.39 0.00 22.39



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 402.17 22.50 0.00 22.50 0.00 22.50
February 364.00 22.46 0.00 22.46 0.00 22.46
March 403.00 22.42 0.00 22.42 0.00 22.42
April 390.00 22.38 0.00 22.38 0.00 22.38
May 403.00 22.31 0.00 22.31 0.00 22.31
June 390.00 22.26 0.00 22.26 0.00 22.26
July 403.00 22.24 0.00 22.24 0.00 22.24
August 403.00 22.26 0.00 22.26 0.00 22.26
September 390.00 22.24 0.00 22.24 0.00 22.24
October 403.00 22.30 0.00 22.30 0.00 22.30
November 388.67 22.42 0.00 22.42 0.00 22.42
December 403.00 22.48 0.00 22.48 0.00 22.48
             
Annual Sum or Average 4742.83 22.35 0.00 22.35 0.00 22.35
Minimum of Months 364.00 22.24 0.00 22.24 0.00 22.24
Maximum of Months 403.00 22.50 0.00 22.50 0.00 22.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 NURSE STATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 388.17 22.52 0.00 22.52 0.00 22.52
February 357.67 22.50 0.00 22.50 0.00 22.50
March 396.00 22.46 0.00 22.46 0.00 22.46
April 389.00 22.43 0.00 22.43 0.00 22.43
May 403.00 22.34 0.00 22.34 0.00 22.34
June 390.00 22.29 0.00 22.29 0.00 22.29
July 403.00 22.25 0.00 22.25 0.00 22.25
August 403.00 22.30 0.00 22.30 0.00 22.30
September 390.00 22.27 0.00 22.27 0.00 22.27
October 403.00 22.36 0.00 22.36 0.00 22.36
November 382.67 22.48 0.00 22.48 0.00 22.48
December 388.00 22.49 0.00 22.49 0.00 22.49
             
Annual Sum or Average 4693.50 22.39 0.00 22.39 0.00 22.39
Minimum of Months 357.67 22.25 0.00 22.25 0.00 22.25
Maximum of Months 403.00 22.52 0.00 22.52 0.00 22.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 20.78 34.33 20.62 34.33 20.48
February 364.00 20.72 37.00 20.54 37.00 20.40
March 403.00 20.73 30.17 20.59 30.17 20.47
April 390.00 20.59 55.83 20.35 55.83 20.16
May 403.00 20.53 65.00 20.28 65.00 20.08
June 390.00 20.56 59.67 20.31 59.67 20.12
July 403.00 20.40 92.33 20.09 92.33 19.87
August 403.00 20.57 59.67 20.32 59.67 20.14
September 390.00 20.47 77.33 20.17 77.33 19.96
October 403.00 20.49 73.50 20.21 73.50 20.01
November 390.00 20.65 49.83 20.43 49.83 20.26
December 403.00 20.70 40.33 20.52 40.33 20.37
             
Annual Sum or Average 4745.00 20.60 675.00 20.36 675.00 20.18
Minimum of Months 364.00 20.40 30.17 20.09 30.17 19.87
Maximum of Months 403.00 20.78 92.33 20.62 92.33 20.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 336.50 22.61 0.00 22.61 0.00 22.61
February 305.50 22.57 0.00 22.57 0.00 22.57
March 339.00 22.53 0.00 22.53 0.00 22.53
April 329.83 22.53 0.00 22.53 0.00 22.53
May 348.33 22.51 0.00 22.51 0.00 22.51
June 337.83 22.46 0.00 22.46 0.00 22.46
July 353.00 22.49 0.00 22.49 0.00 22.49
August 348.33 22.46 0.00 22.46 0.00 22.46
September 340.00 22.48 0.00 22.48 0.00 22.48
October 349.50 22.53 0.00 22.53 0.00 22.53
November 329.17 22.59 0.00 22.59 0.00 22.59
December 335.83 22.59 0.00 22.59 0.00 22.59
             
Annual Sum or Average 4052.83 22.53 0.00 22.53 0.00 22.53
Minimum of Months 305.50 22.46 0.00 22.46 0.00 22.46
Maximum of Months 353.00 22.61 0.00 22.61 0.00 22.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 19.15 74.00 19.07 74.00 19.00
February 364.00 19.15 70.67 19.06 70.67 18.99
March 403.00 19.15 56.83 19.08 56.83 19.03
April 390.00 19.16 33.67 19.11 33.67 19.08
May 403.00 19.18 31.17 19.14 31.17 19.10
June 389.00 19.37 16.50 19.34 16.50 19.31
July 393.50 19.51 11.17 19.49 11.17 19.46
August 389.50 19.49 14.00 19.47 14.00 19.46
September 380.67 19.39 14.50 19.36 14.50 19.33
October 401.17 19.28 22.83 19.24 22.83 19.21
November 390.00 19.18 49.17 19.13 49.17 19.09
December 403.00 19.15 69.00 19.08 69.00 19.03
             
Annual Sum or Average 4709.83 19.26 463.50 19.21 463.50 19.16
Minimum of Months 364.00 19.15 11.17 19.06 11.17 18.99
Maximum of Months 403.00 19.51 74.00 19.49 74.00 19.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 19.15 98.50 19.04 98.50 18.97
February 364.00 19.15 83.50 19.05 83.50 18.98
March 403.00 19.15 67.00 19.07 67.00 19.01
April 390.00 19.15 40.67 19.10 40.67 19.06
May 403.00 19.17 45.00 19.11 45.00 19.06
June 390.00 19.31 25.83 19.27 25.83 19.23
July 403.00 19.47 23.00 19.43 23.00 19.39
August 403.00 19.45 25.33 19.42 25.33 19.38
September 390.00 19.32 34.33 19.26 34.33 19.21
October 403.00 19.21 53.83 19.14 53.83 19.08
November 390.00 19.15 70.50 19.08 70.50 19.03
December 403.00 19.15 95.33 19.06 95.33 18.99
             
Annual Sum or Average 4745.00 19.24 662.83 19.16 662.83 19.10
Minimum of Months 364.00 19.15 23.00 19.04 23.00 18.97
Maximum of Months 403.00 19.47 98.50 19.43 98.50 19.39



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 19.15 96.83 19.04 96.83 18.97
February 364.00 19.15 91.33 19.04 91.33 18.97
March 403.00 19.15 84.83 19.06 84.83 18.99
April 390.00 19.15 55.00 19.09 55.00 19.04
May 403.00 19.15 54.33 19.09 54.33 19.04
June 390.00 19.16 44.67 19.11 44.67 19.08
July 403.00 19.19 65.67 19.11 65.67 19.05
August 403.00 19.19 45.00 19.14 45.00 19.10
September 390.00 19.16 55.67 19.10 55.67 19.05
October 403.00 19.16 65.17 19.08 65.17 19.02
November 390.00 19.15 73.50 19.09 73.50 19.04
December 403.00 19.15 82.83 19.07 82.83 19.01
             
Annual Sum or Average 4745.00 19.16 814.83 19.08 814.83 19.03
Minimum of Months 364.00 19.15 44.67 19.04 44.67 18.97
Maximum of Months 403.00 19.19 96.83 19.14 96.83 19.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 PACU

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 401.17 20.87 19.50 20.76 19.50 20.67
February 363.67 20.81 24.00 20.67 24.00 20.55
March 403.00 20.78 17.33 20.69 17.33 20.61
April 390.00 20.64 38.33 20.45 38.33 20.29
May 403.00 20.58 48.33 20.35 48.33 20.17
June 390.00 20.59 45.83 20.37 45.83 20.18
July 403.00 20.45 68.17 20.16 68.17 19.94
August 403.00 20.60 45.00 20.38 45.00 20.21
September 390.00 20.51 58.17 20.24 58.17 20.03
October 403.00 20.55 54.50 20.30 54.50 20.10
November 390.00 20.73 32.83 20.56 32.83 20.42
December 402.50 20.78 24.67 20.65 24.67 20.54
             
Annual Sum or Average 4742.33 20.66 476.67 20.46 476.67 20.29
Minimum of Months 363.67 20.45 17.33 20.16 17.33 19.94
Maximum of Months 403.00 20.87 68.17 20.76 68.17 20.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.42 0.00 22.42 0.00 22.42
February 364.00 22.38 0.00 22.38 0.00 22.38
March 403.00 22.37 0.00 22.37 0.00 22.37
April 390.00 22.33 0.00 22.33 0.00 22.33
May 403.00 22.27 0.00 22.27 0.00 22.27
June 390.00 22.23 0.00 22.23 0.00 22.23
July 403.00 22.21 0.00 22.21 0.00 22.21
August 403.00 22.24 0.00 22.24 0.00 22.24
September 390.00 22.22 0.00 22.22 0.00 22.22
October 403.00 22.27 0.00 22.27 0.00 22.27
November 390.00 22.38 0.00 22.38 0.00 22.38
December 403.00 22.41 0.00 22.41 0.00 22.41
             
Annual Sum or Average 4745.00 22.31 0.00 22.31 0.00 22.31
Minimum of Months 364.00 22.21 0.00 22.21 0.00 22.21
Maximum of Months 403.00 22.42 0.00 22.42 0.00 22.42



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 20.93 2.67 20.92 2.67 20.90
February 364.00 20.87 6.33 20.83 6.33 20.80
March 403.00 20.84 0.00 20.84 0.00 20.84
April 390.00 20.74 1.67 20.74 1.67 20.73
May 403.00 20.69 11.67 20.63 11.67 20.58
June 390.00 20.69 19.17 20.59 19.17 20.50
July 403.00 20.58 27.33 20.46 27.33 20.36
August 403.00 20.71 11.83 20.65 11.83 20.60
September 390.00 20.64 17.33 20.56 17.33 20.48
October 403.00 20.68 9.33 20.64 9.33 20.59
November 390.00 20.83 0.50 20.83 0.50 20.82
December 403.00 20.86 0.00 20.86 0.00 20.86
             
Annual Sum or Average 4745.00 20.75 107.83 20.71 107.83 20.67
Minimum of Months 364.00 20.58 0.00 20.46 0.00 20.36
Maximum of Months 403.00 20.93 27.33 20.92 27.33 20.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 398.67 20.91 2.00 20.90 2.00 20.89
February 361.83 20.86 5.33 20.83 5.33 20.80
March 401.00 20.81 0.50 20.81 0.50 20.80
April 390.00 20.71 7.67 20.67 7.67 20.63
May 403.00 20.63 23.00 20.52 23.00 20.42
June 390.00 20.63 31.00 20.47 31.00 20.34
July 403.00 20.50 51.33 20.27 51.33 20.09
August 403.00 20.64 29.67 20.49 29.67 20.36
September 390.00 20.55 44.00 20.34 44.00 20.17
October 403.00 20.60 30.67 20.45 30.67 20.32
November 387.67 20.77 8.83 20.72 8.83 20.68
December 398.50 20.81 1.33 20.80 1.33 20.79
             
Annual Sum or Average 4729.67 20.70 235.33 20.60 235.33 20.50
Minimum of Months 361.83 20.50 0.50 20.27 0.50 20.09
Maximum of Months 403.00 20.91 51.33 20.90 51.33 20.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 20.90 9.00 20.87 9.00 20.83
February 364.00 20.87 13.83 20.82 13.83 20.78
March 403.00 20.87 7.67 20.88 7.67 20.88
April 390.00 20.83 3.17 20.83 3.17 20.83
May 403.00 20.81 0.33 20.81 0.33 20.81
June 390.00 20.81 0.00 20.81 0.00 20.81
July 403.00 20.79 0.00 20.79 0.00 20.79
August 403.00 20.86 0.00 20.86 0.00 20.86
September 390.00 20.84 0.17 20.84 0.17 20.84
October 403.00 20.88 0.00 20.88 0.00 20.88
November 390.00 20.90 2.17 20.90 2.17 20.89
December 402.83 20.92 4.17 20.92 4.17 20.92
             
Annual Sum or Average 4744.83 20.86 40.50 20.85 40.50 20.84
Minimum of Months 364.00 20.79 0.00 20.79 0.00 20.78
Maximum of Months 403.00 20.92 13.83 20.92 13.83 20.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 402.83 20.70 32.83 20.52 32.83 20.37
February 363.00 20.64 29.33 20.47 29.33 20.33
March 401.33 20.63 16.00 20.55 16.00 20.48
April 387.50 20.52 16.83 20.43 16.83 20.35
May 402.67 20.54 5.50 20.51 5.50 20.48
June 390.00 20.56 8.83 20.51 8.83 20.47
July 403.00 20.44 5.83 20.41 5.83 20.38
August 403.00 20.57 9.17 20.52 9.17 20.47
September 390.00 20.50 8.50 20.45 8.50 20.40
October 403.00 20.52 13.83 20.44 13.83 20.37
November 389.50 20.61 18.83 20.50 18.83 20.40
December 399.17 20.60 20.33 20.49 20.33 20.39
             
Annual Sum or Average 4735.00 20.57 185.83 20.48 185.83 20.41
Minimum of Months 363.00 20.44 5.50 20.41 5.50 20.33
Maximum of Months 403.00 20.70 32.83 20.55 32.83 20.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 308.67 22.35 28.17 22.56 0.00 22.56
February 285.33 22.36 21.00 22.52 0.00 22.52
March 323.83 22.33 17.33 22.44 0.00 22.44
April 323.00 22.40 13.33 22.49 0.00 22.49
May 349.50 22.42 10.17 22.48 0.00 22.48
June 348.17 22.42 10.17 22.47 0.00 22.47
July 343.67 22.46 9.83 22.51 0.00 22.51
August 340.67 22.37 13.67 22.45 0.00 22.45
September 307.33 22.36 17.50 22.48 0.00 22.48
October 292.17 22.31 31.83 22.53 0.00 22.53
November 282.50 22.31 31.00 22.54 0.00 22.54
December 295.67 22.33 43.83 22.63 0.00 22.63
             
Annual Sum or Average 3800.50 22.37 247.83 22.51 0.00 22.51
Minimum of Months 282.50 22.31 9.83 22.44 0.00 22.44
Maximum of Months 349.50 22.46 43.83 22.63 0.00 22.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.49 0.00 22.49 0.00 22.49
February 364.00 22.45 0.00 22.45 0.00 22.45
March 403.00 22.41 0.00 22.41 0.00 22.41
April 390.00 22.38 0.00 22.38 0.00 22.38
May 403.00 22.32 0.00 22.32 0.00 22.32
June 390.00 22.28 0.00 22.28 0.00 22.28
July 403.00 22.27 0.00 22.27 0.00 22.27
August 403.00 22.28 0.00 22.28 0.00 22.28
September 390.00 22.28 0.00 22.28 0.00 22.28
October 403.00 22.34 0.00 22.34 0.00 22.34
November 389.67 22.45 0.00 22.45 0.00 22.45
December 403.00 22.48 0.00 22.48 0.00 22.48
             
Annual Sum or Average 4744.67 22.37 0.00 22.37 0.00 22.37
Minimum of Months 364.00 22.27 0.00 22.27 0.00 22.27
Maximum of Months 403.00 22.49 0.00 22.49 0.00 22.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 354.67 21.19 6.33 21.19 3.67 21.16
February 339.17 21.12 5.17 21.09 4.83 21.06
March 399.17 20.99 3.50 21.01 2.67 21.02
April 389.67 20.82 1.17 20.81 1.17 20.81
May 403.00 20.75 1.00 20.75 1.00 20.74
June 390.00 20.75 3.00 20.73 3.00 20.71
July 403.00 20.69 1.00 20.69 1.00 20.68
August 403.00 20.83 0.00 20.83 0.00 20.83
September 390.00 20.93 0.33 20.92 0.33 20.92
October 392.50 21.09 0.50 21.09 0.00 21.09
November 360.50 21.18 1.17 21.19 0.33 21.18
December 367.50 21.14 6.17 21.19 0.33 21.19
             
Annual Sum or Average 4592.17 20.95 29.33 20.95 18.33 20.94
Minimum of Months 339.17 20.69 0.00 20.69 0.00 20.68
Maximum of Months 403.00 21.19 6.33 21.19 4.83 21.19



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 SCHEDULING

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 343.33 22.60 0.00 22.60 0.00 22.60
February 309.33 22.53 0.00 22.53 0.00 22.53
March 345.17 22.50 3.83 22.51 2.33 22.52
April 335.83 22.49 0.00 22.49 0.00 22.49
May 350.00 22.46 0.00 22.46 0.00 22.46
June 337.50 22.41 0.00 22.41 0.00 22.41
July 353.00 22.48 0.00 22.48 0.00 22.48
August 348.17 22.46 0.00 22.46 0.00 22.46
September 338.67 22.53 0.00 22.53 0.00 22.53
October 340.83 22.56 0.33 22.57 0.00 22.57
November 330.00 22.59 0.00 22.59 0.00 22.59
December 322.50 22.56 2.00 22.57 0.00 22.57
             
Annual Sum or Average 4054.33 22.51 6.17 22.52 2.33 22.52
Minimum of Months 309.33 22.41 0.00 22.41 0.00 22.41
Maximum of Months 353.00 22.60 3.83 22.60 2.33 22.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 SCRUB

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.30 0.00 22.30 0.00 22.30
February 364.00 22.27 0.00 22.27 0.00 22.27
March 403.00 22.30 0.00 22.30 0.00 22.30
April 390.00 22.33 0.00 22.33 0.00 22.33
May 403.00 22.31 0.00 22.31 0.00 22.31
June 390.00 22.33 0.00 22.33 0.00 22.33
July 403.00 22.37 0.00 22.37 0.00 22.37
August 403.00 22.33 0.00 22.33 0.00 22.33
September 390.00 22.35 0.00 22.35 0.00 22.35
October 403.00 22.35 0.00 22.35 0.00 22.35
November 390.00 22.34 0.00 22.34 0.00 22.34
December 403.00 22.29 0.00 22.29 0.00 22.29
             
Annual Sum or Average 4745.00 22.32 0.00 22.32 0.00 22.32
Minimum of Months 364.00 22.27 0.00 22.27 0.00 22.27
Maximum of Months 403.00 22.37 0.00 22.37 0.00 22.37



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 SOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 402.17 20.83 25.00 20.70 25.00 20.58
February 363.83 20.78 27.50 20.62 27.50 20.48
March 403.00 20.75 21.17 20.64 21.17 20.54
April 390.00 20.62 41.67 20.41 41.67 20.24
May 403.00 20.57 49.67 20.33 49.67 20.14
June 390.00 20.58 46.00 20.35 46.00 20.17
July 403.00 20.44 68.67 20.14 68.67 19.92
August 403.00 20.59 45.50 20.37 45.50 20.19
September 390.00 20.50 59.50 20.22 59.50 20.01
October 403.00 20.52 57.67 20.26 57.67 20.06
November 390.00 20.69 37.50 20.50 37.50 20.34
December 402.67 20.74 30.33 20.58 30.33 20.44
             
Annual Sum or Average 4743.67 20.63 510.17 20.42 510.17 20.25
Minimum of Months 363.83 20.44 21.17 20.14 21.17 19.92
Maximum of Months 403.00 20.83 68.67 20.70 68.67 20.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 20.75 39.50 20.57 39.50 20.41
February 364.00 20.74 31.00 20.58 31.00 20.44
March 403.00 20.76 16.00 20.69 16.00 20.61
April 390.00 20.70 11.00 20.65 11.00 20.60
May 403.00 20.69 9.67 20.64 9.67 20.60
June 390.00 20.71 8.00 20.67 8.00 20.63
July 403.00 20.61 6.50 20.58 6.50 20.55
August 403.00 20.70 11.17 20.65 11.17 20.60
September 390.00 20.63 21.50 20.53 21.50 20.44
October 403.00 20.63 31.83 20.49 31.83 20.36
November 390.00 20.74 27.00 20.61 27.00 20.50
December 403.00 20.71 31.17 20.57 31.17 20.44
             
Annual Sum or Average 4745.00 20.70 244.33 20.60 244.33 20.51
Minimum of Months 364.00 20.61 6.50 20.49 6.50 20.36
Maximum of Months 403.00 20.76 39.50 20.69 39.50 20.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 SOIL WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 20.79 31.83 20.63 31.83 20.49
February 364.00 20.74 32.83 20.55 32.83 20.39
March 403.00 20.72 26.33 20.59 26.33 20.47
April 390.00 20.59 48.00 20.35 48.00 20.16
May 403.00 20.54 53.33 20.30 53.33 20.10
June 390.00 20.57 48.33 20.33 48.33 20.14
July 403.00 20.42 72.17 20.12 72.17 19.90
August 403.00 20.58 48.00 20.35 48.00 20.16
September 390.00 20.48 62.67 20.20 62.67 19.99
October 403.00 20.51 60.33 20.24 60.33 20.03
November 390.00 20.66 41.50 20.45 41.50 20.28
December 403.00 20.70 36.33 20.52 36.33 20.36
             
Annual Sum or Average 4745.00 20.61 561.67 20.38 561.67 20.20
Minimum of Months 364.00 20.42 26.33 20.12 26.33 19.90
Maximum of Months 403.00 20.79 72.17 20.63 72.17 20.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 STEP DOWN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 353.83 21.38 5.67 21.39 2.50 21.37
February 333.00 21.39 7.67 21.38 5.83 21.36
March 397.67 21.31 4.67 21.33 4.67 21.34
April 387.17 21.19 2.50 21.21 2.50 21.22
May 402.17 21.13 0.00 21.13 0.00 21.13
June 389.50 21.10 0.00 21.10 0.00 21.10
July 403.00 21.18 0.00 21.18 0.00 21.18
August 398.83 21.32 0.00 21.32 0.00 21.32
September 374.50 21.38 1.00 21.38 0.00 21.38
October 345.67 21.40 5.83 21.45 0.00 21.45
November 332.50 21.43 2.50 21.45 1.67 21.46
December 355.50 21.39 12.83 21.50 2.83 21.51
             
Annual Sum or Average 4473.33 21.29 42.67 21.31 20.00 21.31
Minimum of Months 332.50 21.10 0.00 21.10 0.00 21.10
Maximum of Months 403.00 21.43 12.83 21.50 5.83 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 STERILE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.38 0.00 22.38 0.00 22.38
February 364.00 22.34 0.00 22.34 0.00 22.34
March 403.00 22.33 0.00 22.33 0.00 22.33
April 390.00 22.32 0.00 22.32 0.00 22.32
May 403.00 22.29 0.00 22.29 0.00 22.29
June 390.00 22.28 0.00 22.28 0.00 22.28
July 403.00 22.31 0.00 22.31 0.00 22.31
August 403.00 22.30 0.00 22.30 0.00 22.30
September 390.00 22.32 0.00 22.32 0.00 22.32
October 403.00 22.36 0.00 22.36 0.00 22.36
November 390.00 22.39 0.00 22.39 0.00 22.39
December 403.00 22.38 0.00 22.38 0.00 22.38
             
Annual Sum or Average 4745.00 22.33 0.00 22.33 0.00 22.33
Minimum of Months 364.00 22.28 0.00 22.28 0.00 22.28
Maximum of Months 403.00 22.39 0.00 22.39 0.00 22.39



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.45 0.00 22.45 0.00 22.45
February 364.00 22.42 0.00 22.42 0.00 22.42
March 403.00 22.39 0.00 22.39 0.00 22.39
April 390.00 22.35 0.00 22.35 0.00 22.35
May 403.00 22.28 0.00 22.28 0.00 22.28
June 390.00 22.24 0.00 22.24 0.00 22.24
July 403.00 22.23 0.00 22.23 0.00 22.23
August 403.00 22.25 0.00 22.25 0.00 22.25
September 390.00 22.23 0.00 22.23 0.00 22.23
October 403.00 22.28 0.00 22.28 0.00 22.28
November 390.00 22.40 0.00 22.40 0.00 22.40
December 403.00 22.43 0.00 22.43 0.00 22.43
             
Annual Sum or Average 4745.00 22.33 0.00 22.33 0.00 22.33
Minimum of Months 364.00 22.23 0.00 22.23 0.00 22.23
Maximum of Months 403.00 22.45 0.00 22.45 0.00 22.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 21.38 21.67 21.32 21.67 21.27
February 364.00 21.65 25.67 21.54 25.67 21.44
March 396.50 21.89 11.50 21.86 11.50 21.83
April 353.00 22.25 16.00 22.35 0.00 22.35
May 323.50 22.27 52.00 22.57 0.00 22.57
June 310.17 22.28 54.33 22.62 0.33 22.62
July 287.67 22.27 90.83 22.86 0.00 22.86
August 325.00 22.28 51.67 22.60 0.00 22.60
September 304.83 22.30 50.50 22.62 0.00 22.62
October 351.50 22.35 19.50 22.44 0.00 22.44
November 380.17 22.10 2.00 22.09 2.00 22.08
December 402.50 21.65 9.17 21.61 9.17 21.58
             
Annual Sum or Average 4201.83 22.03 404.83 22.19 70.33 22.16
Minimum of Months 287.67 21.38 2.00 21.32 0.00 21.27
Maximum of Months 403.00 22.35 90.83 22.86 25.67 22.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 397.67 22.16 1.00 22.16 0.00 22.16
February 361.00 22.16 3.00 22.14 3.00 22.12
March 399.17 22.23 3.00 22.24 2.50 22.25
April 365.33 22.32 9.33 22.38 0.00 22.38
May 378.67 22.38 6.83 22.41 0.00 22.41
June 354.67 22.37 14.00 22.45 0.00 22.45
July 325.50 22.36 38.17 22.60 0.00 22.60
August 364.00 22.36 15.33 22.44 0.00 22.44
September 341.00 22.39 18.67 22.50 0.00 22.50
October 371.50 22.41 6.50 22.44 0.00 22.44
November 384.83 22.31 0.00 22.31 0.00 22.31
December 400.67 22.14 0.17 22.14 0.00 22.14
             
Annual Sum or Average 4444.00 22.30 116.00 22.35 5.50 22.35
Minimum of Months 325.50 22.14 0.00 22.14 0.00 22.12
Maximum of Months 400.67 22.41 38.17 22.60 3.00 22.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 21.30 13.67 21.26 13.67 21.22
February 364.00 21.55 21.17 21.46 21.17 21.38
March 401.67 21.88 7.33 21.86 7.00 21.84
April 358.00 22.17 19.67 22.31 0.00 22.31
May 360.00 22.27 27.00 22.43 0.00 22.43
June 336.17 22.29 32.50 22.51 0.00 22.51
July 310.33 22.28 65.83 22.74 0.00 22.74
August 356.17 22.25 32.33 22.45 0.00 22.45
September 337.00 22.29 37.33 22.51 0.00 22.51
October 390.83 22.30 0.83 22.30 0.00 22.30
November 390.00 21.96 2.00 21.95 2.00 21.94
December 403.00 21.49 7.67 21.46 7.67 21.43
             
Annual Sum or Average 4410.17 21.98 267.33 22.09 51.50 22.07
Minimum of Months 310.33 21.30 0.83 21.26 0.00 21.22
Maximum of Months 403.00 22.30 65.83 22.74 21.17 22.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.33 0.00 22.33 0.00 22.33
February 364.00 22.29 0.00 22.29 0.00 22.29
March 403.00 22.33 0.00 22.33 0.00 22.33
April 390.00 22.37 0.00 22.37 0.00 22.37
May 403.00 22.36 0.00 22.36 0.00 22.36
June 390.00 22.36 0.00 22.36 0.00 22.36
July 403.00 22.42 0.00 22.42 0.00 22.42
August 403.00 22.36 0.00 22.36 0.00 22.36
September 390.00 22.38 0.00 22.38 0.00 22.38
October 403.00 22.39 0.00 22.39 0.00 22.39
November 390.00 22.38 0.00 22.38 0.00 22.38
December 403.00 22.32 0.00 22.32 0.00 22.32
             
Annual Sum or Average 4745.00 22.36 0.00 22.36 0.00 22.36
Minimum of Months 364.00 22.29 0.00 22.29 0.00 22.29
Maximum of Months 403.00 22.42 0.00 22.42 0.00 22.42



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 398.17 22.12 0.00 22.12 0.00 22.12
February 363.83 22.14 3.17 22.12 3.17 22.10
March 398.17 22.24 1.33 22.24 1.33 22.25
April 362.17 22.35 8.00 22.39 0.00 22.39
May 362.83 22.36 11.83 22.43 0.00 22.43
June 345.67 22.35 19.67 22.47 0.00 22.47
July 327.67 22.37 51.33 22.67 0.00 22.67
August 361.50 22.36 21.50 22.47 0.00 22.47
September 336.17 22.38 27.83 22.54 0.00 22.54
October 351.67 22.38 6.83 22.42 0.00 22.42
November 383.50 22.35 0.00 22.35 0.00 22.35
December 401.00 22.11 0.00 22.11 0.00 22.11
             
Annual Sum or Average 4392.33 22.29 151.50 22.36 4.50 22.36
Minimum of Months 327.67 22.11 0.00 22.11 0.00 22.10
Maximum of Months 401.00 22.38 51.33 22.67 3.17 22.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 VESTIBULE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 389.00 20.98 186.67 20.70 175.33 20.49
February 301.00 22.09 172.00 22.33 132.83 22.28
March 359.83 21.90 229.33 21.95 201.00 21.88
April 308.00 23.80 218.33 24.40 156.83 24.60
May 389.17 25.62 286.67 26.11 280.83 26.31
June 383.50 26.00 288.67 26.50 287.33 26.70
July 377.83 26.49 266.50 27.17 260.00 27.47
August 384.83 26.68 307.83 27.16 300.00 27.37
September 367.50 25.96 270.33 26.49 260.00 26.73
October 351.83 25.34 270.83 25.86 240.00 26.05
November 370.17 23.90 235.00 24.28 219.00 24.42
December 368.50 21.12 155.83 21.05 132.67 20.88
             
Annual Sum or Average 4351.17 24.21 2888.00 24.69 2645.83 24.90
Minimum of Months 301.00 20.98 155.83 20.70 132.67 20.49
Maximum of Months 389.17 26.68 307.83 27.17 300.00 27.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 CONFERENCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 211.00 22.29 46.33 22.62 5.17 22.63
February 186.67 22.34 49.50 22.64 19.33 22.66
March 204.83 22.40 53.83 22.71 21.50 22.78
April 184.50 22.43 56.67 22.82 13.83 22.88
May 180.00 22.42 64.50 22.82 15.67 22.89
June 147.33 22.39 59.50 22.86 10.17 22.92
July 123.33 22.35 84.00 23.11 4.83 23.14
August 137.00 22.41 65.83 22.98 10.83 23.04
September 109.33 22.40 74.00 23.19 4.83 23.22
October 123.67 22.59 99.67 23.29 18.17 23.37
November 154.50 22.52 76.67 22.98 16.67 23.04
December 213.33 22.43 69.33 22.83 29.67 22.93
             
Annual Sum or Average 1975.50 22.41 799.83 22.89 170.67 22.94
Minimum of Months 109.33 22.29 46.33 22.62 4.83 22.63
Maximum of Months 213.33 22.59 99.67 23.29 29.67 23.37



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 21.27 0.00 21.27 0.00 21.27
February 364.00 21.28 3.67 21.27 3.67 21.25
March 403.00 21.28 0.00 21.28 0.00 21.28
April 390.00 21.23 0.00 21.23 0.00 21.23
May 403.00 21.14 0.00 21.14 0.00 21.14
June 390.00 21.11 0.00 21.11 0.00 21.11
July 403.00 21.11 0.00 21.11 0.00 21.11
August 403.00 21.11 0.00 21.11 0.00 21.11
September 390.00 21.14 0.00 21.14 0.00 21.14
October 403.00 21.21 0.00 21.21 0.00 21.21
November 389.00 21.32 0.00 21.32 0.00 21.32
December 403.00 21.29 0.00 21.29 0.00 21.29
             
Annual Sum or Average 4744.00 21.21 3.67 21.21 3.67 21.20
Minimum of Months 364.00 21.11 0.00 21.11 0.00 21.11
Maximum of Months 403.00 21.32 3.67 21.32 3.67 21.32



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 350.83 22.46 0.00 22.46 0.00 22.46
February 312.83 22.43 0.00 22.43 0.00 22.43
March 344.00 22.43 0.00 22.43 0.00 22.43
April 340.00 22.39 0.00 22.39 0.00 22.39
May 351.00 22.29 0.00 22.29 0.00 22.29
June 338.00 22.26 0.00 22.26 0.00 22.26
July 353.00 22.23 0.00 22.23 0.00 22.23
August 349.00 22.26 0.00 22.26 0.00 22.26
September 340.00 22.25 0.00 22.25 0.00 22.25
October 353.00 22.33 0.00 22.33 0.00 22.33
November 333.00 22.45 0.00 22.45 0.00 22.45
December 351.17 22.48 0.00 22.48 0.00 22.48
             
Annual Sum or Average 4115.83 22.35 0.00 22.35 0.00 22.35
Minimum of Months 312.83 22.23 0.00 22.23 0.00 22.23
Maximum of Months 353.00 22.48 0.00 22.48 0.00 22.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 376.67 22.03 6.00 22.04 4.17 22.05
February 316.00 22.10 32.17 22.21 17.33 22.22
March 325.17 22.16 39.00 22.33 18.67 22.40
April 294.67 22.20 50.50 22.46 11.33 22.52
May 303.33 22.22 46.50 22.42 12.17 22.48
June 311.67 22.19 33.17 22.34 7.83 22.38
July 286.50 22.16 56.33 22.43 3.00 22.45
August 289.83 22.18 50.00 22.41 8.33 22.45
September 274.67 22.17 52.83 22.44 2.33 22.45
October 280.00 22.24 63.33 22.54 10.83 22.59
November 316.83 22.25 24.00 22.36 13.00 22.42
December 353.67 22.13 38.17 22.29 23.67 22.38
             
Annual Sum or Average 3729.00 22.17 492.00 22.35 132.67 22.40
Minimum of Months 274.67 22.03 6.00 22.04 2.33 22.05
Maximum of Months 376.67 22.25 63.33 22.54 23.67 22.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 392.50 21.64 3.67 21.67 0.00 21.67
February 351.00 21.65 17.50 21.73 9.50 21.75
March 395.00 21.67 17.17 21.79 12.50 21.86
April 382.17 21.50 5.83 21.54 4.17 21.57
May 398.83 21.34 3.83 21.37 3.33 21.39
June 389.00 21.27 2.00 21.28 2.00 21.30
July 401.50 21.14 0.00 21.14 0.00 21.14
August 400.83 21.26 3.33 21.29 2.83 21.30
September 389.00 21.32 0.00 21.32 0.00 21.32
October 394.50 21.42 4.33 21.45 0.00 21.45
November 374.67 21.62 8.00 21.68 4.50 21.71
December 381.00 21.60 15.33 21.71 4.17 21.75
             
Annual Sum or Average 4650.00 21.45 81.00 21.50 43.00 21.52
Minimum of Months 351.00 21.14 0.00 21.14 0.00 21.14
Maximum of Months 401.50 21.67 17.50 21.79 12.50 21.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 397.17 21.53 1.33 21.54 0.00 21.54
February 358.00 21.55 11.83 21.58 9.17 21.59
March 402.50 21.55 12.50 21.62 12.50 21.69
April 390.00 21.34 4.00 21.37 4.00 21.39
May 403.00 21.17 3.33 21.19 3.33 21.21
June 390.00 21.10 2.00 21.11 2.00 21.13
July 403.00 20.99 0.00 20.99 0.00 20.99
August 403.00 21.11 2.83 21.12 2.83 21.14
September 390.00 21.15 0.00 21.15 0.00 21.15
October 402.33 21.29 0.00 21.29 0.00 21.29
November 385.67 21.53 5.33 21.57 4.50 21.59
December 392.67 21.53 6.50 21.58 4.17 21.61
             
Annual Sum or Average 4717.33 21.32 49.67 21.34 42.50 21.36
Minimum of Months 358.00 20.99 0.00 20.99 0.00 20.99
Maximum of Months 403.00 21.55 12.50 21.62 12.50 21.69



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 342.17 22.11 21.00 22.22 4.00 22.22
February 320.17 22.16 28.50 22.25 14.50 22.25
March 390.67 22.19 19.50 22.26 17.50 22.31
April 383.33 22.17 12.00 22.22 10.50 22.25
May 401.50 22.16 9.17 22.19 9.17 22.22
June 389.00 22.15 4.67 22.17 4.67 22.19
July 396.50 22.16 1.17 22.17 0.33 22.17
August 395.00 22.17 8.67 22.20 7.17 22.22
September 356.17 22.20 11.33 22.26 0.00 22.26
October 328.33 22.25 31.00 22.40 6.33 22.43
November 320.33 22.28 31.17 22.42 11.67 22.46
December 350.17 22.19 44.00 22.39 16.67 22.45
             
Annual Sum or Average 4373.33 22.18 222.17 22.26 102.50 22.28
Minimum of Months 320.17 22.11 1.17 22.17 0.00 22.17
Maximum of Months 401.50 22.28 44.00 22.42 17.50 22.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 391.83 21.45 9.83 21.52 2.17 21.52
February 352.50 21.65 19.50 21.72 13.67 21.74
March 371.83 21.84 21.50 21.97 16.50 22.06
April 291.50 21.97 24.83 22.15 9.17 22.22
May 273.67 22.02 20.50 22.18 7.17 22.24
June 257.33 22.04 21.50 22.21 3.00 22.23
July 231.67 21.97 40.00 22.27 0.00 22.27
August 284.83 21.99 19.50 22.13 5.83 22.18
September 286.83 21.92 26.33 22.12 0.00 22.12
October 325.33 21.86 21.00 22.02 4.83 22.05
November 373.00 21.80 14.33 21.90 8.50 21.95
December 396.17 21.49 18.33 21.60 15.33 21.68
             
Annual Sum or Average 3836.50 21.81 257.17 21.95 86.17 21.99
Minimum of Months 231.67 21.45 9.83 21.52 0.00 21.52
Maximum of Months 396.17 22.04 40.00 22.27 16.50 22.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 21.16 1.17 21.16 1.17 21.16
February 360.67 21.28 19.17 21.30 18.17 21.32
March 402.33 21.46 16.83 21.55 16.50 21.63
April 386.00 21.59 9.83 21.65 8.67 21.70
May 399.67 21.75 7.67 21.80 7.00 21.84
June 385.00 21.76 5.33 21.80 2.83 21.82
July 396.00 21.66 2.67 21.68 0.00 21.68
August 401.33 21.65 6.67 21.69 5.83 21.72
September 383.50 21.54 0.00 21.54 0.00 21.54
October 399.83 21.44 4.67 21.47 4.67 21.49
November 387.50 21.38 9.00 21.44 8.17 21.48
December 402.83 21.27 14.17 21.34 14.17 21.41
             
Annual Sum or Average 4707.67 21.50 97.17 21.53 87.17 21.57
Minimum of Months 360.67 21.16 0.00 21.16 0.00 21.16
Maximum of Months 403.00 21.76 19.17 21.80 18.17 21.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 401.83 21.26 0.00 21.26 0.00 21.26
February 354.67 21.29 14.00 21.34 9.33 21.36
March 397.83 21.39 12.50 21.48 12.50 21.56
April 383.00 21.34 5.00 21.38 2.67 21.40
May 398.00 21.31 4.00 21.34 2.50 21.36
June 387.33 21.27 1.33 21.28 1.33 21.29
July 400.17 21.14 0.00 21.14 0.00 21.14
August 400.67 21.19 3.67 21.22 2.83 21.24
September 390.00 21.16 0.00 21.16 0.00 21.16
October 398.50 21.15 0.00 21.15 0.00 21.15
November 386.33 21.33 4.17 21.36 4.17 21.39
December 389.67 21.24 4.33 21.27 3.00 21.29
             
Annual Sum or Average 4688.00 21.26 49.00 21.28 38.33 21.30
Minimum of Months 354.67 21.14 0.00 21.14 0.00 21.14
Maximum of Months 401.83 21.39 14.00 21.48 12.50 21.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 402.00 21.33 1.17 21.32 1.17 21.32
February 356.83 21.43 18.00 21.50 13.17 21.53
March 398.17 21.60 19.33 21.71 16.50 21.80
April 383.50 21.70 12.00 21.78 8.67 21.84
May 397.50 21.84 9.17 21.90 7.00 21.94
June 384.33 21.83 6.67 21.87 2.83 21.89
July 395.83 21.72 5.17 21.75 0.00 21.75
August 401.17 21.72 7.00 21.76 5.83 21.80
September 381.50 21.59 1.17 21.60 0.00 21.60
October 394.33 21.50 5.67 21.54 4.67 21.57
November 387.00 21.54 9.83 21.60 8.33 21.65
December 394.83 21.39 17.67 21.50 13.83 21.58
             
Annual Sum or Average 4677.00 21.60 112.83 21.66 82.00 21.69
Minimum of Months 356.83 21.33 1.17 21.32 0.00 21.32
Maximum of Months 402.00 21.84 19.33 21.90 16.50 21.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 398.67 21.33 0.00 21.33 0.00 21.33
February 352.83 21.35 17.00 21.44 9.00 21.46
March 395.33 21.46 15.67 21.57 12.50 21.66
April 378.50 21.40 8.33 21.46 2.83 21.48
May 396.17 21.39 5.17 21.43 2.50 21.45
June 385.17 21.34 2.17 21.36 1.33 21.37
July 397.83 21.21 0.33 21.21 0.00 21.21
August 400.00 21.27 5.00 21.31 2.83 21.33
September 386.50 21.23 0.00 21.23 0.00 21.23
October 395.17 21.22 2.00 21.24 0.00 21.24
November 377.83 21.35 5.00 21.39 4.17 21.42
December 383.67 21.28 10.33 21.36 3.17 21.39
             
Annual Sum or Average 4647.67 21.32 71.00 21.36 38.33 21.38
Minimum of Months 352.83 21.21 0.00 21.21 0.00 21.21
Maximum of Months 400.00 21.46 17.00 21.57 12.50 21.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 400.83 22.47 0.00 22.47 0.00 22.47
February 345.67 22.39 2.17 22.41 0.17 22.40
March 379.67 22.41 0.00 22.41 0.00 22.41
April 375.67 22.45 0.00 22.45 0.00 22.45
May 395.17 22.40 0.00 22.40 0.00 22.40
June 389.50 22.37 0.00 22.37 0.00 22.37
July 397.50 22.41 0.00 22.41 0.00 22.41
August 397.17 22.38 0.00 22.38 0.00 22.38
September 382.17 22.43 0.00 22.43 0.00 22.43
October 385.00 22.47 0.00 22.47 0.00 22.47
November 370.00 22.48 0.00 22.48 0.00 22.48
December 384.50 22.48 0.00 22.48 0.00 22.48
             
Annual Sum or Average 4602.83 22.43 2.17 22.43 0.17 22.43
Minimum of Months 345.67 22.37 0.00 22.37 0.00 22.37
Maximum of Months 400.83 22.48 2.17 22.48 0.17 22.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 400.00 22.45 0.00 22.45 0.00 22.45
February 353.83 22.39 0.00 22.39 0.00 22.39
March 389.67 22.39 0.00 22.39 0.00 22.39
April 390.00 22.38 0.00 22.38 0.00 22.38
May 403.00 22.29 0.00 22.29 0.00 22.29
June 390.00 22.24 0.00 22.24 0.00 22.24
July 403.00 22.23 0.00 22.23 0.00 22.23
August 403.00 22.26 0.00 22.26 0.00 22.26
September 390.00 22.29 0.00 22.29 0.00 22.29
October 403.00 22.39 0.00 22.39 0.00 22.39
November 378.33 22.45 0.50 22.45 0.00 22.45
December 393.33 22.47 0.00 22.47 0.00 22.47
             
Annual Sum or Average 4697.17 22.35 0.50 22.35 0.00 22.35
Minimum of Months 353.83 22.23 0.00 22.23 0.00 22.23
Maximum of Months 403.00 22.47 0.50 22.47 0.00 22.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.40 0.00 22.40 0.00 22.40
February 364.00 22.38 0.00 22.38 0.00 22.38
March 403.00 22.38 0.00 22.38 0.00 22.38
April 390.00 22.31 0.00 22.31 0.00 22.31
May 403.00 22.22 0.00 22.22 0.00 22.22
June 390.00 22.19 0.00 22.19 0.00 22.19
July 403.00 22.18 0.00 22.18 0.00 22.18
August 403.00 22.21 0.00 22.21 0.00 22.21
September 390.00 22.25 0.00 22.25 0.00 22.25
October 403.00 22.34 0.00 22.34 0.00 22.34
November 388.83 22.43 0.00 22.43 0.00 22.43
December 403.00 22.44 0.00 22.44 0.00 22.44
             
Annual Sum or Average 4743.83 22.31 0.00 22.31 0.00 22.31
Minimum of Months 364.00 22.18 0.00 22.18 0.00 22.18
Maximum of Months 403.00 22.44 0.00 22.44 0.00 22.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 402.67 22.32 0.00 22.32 0.00 22.32
February 357.67 22.29 0.00 22.29 0.00 22.29
March 390.67 22.35 0.00 22.35 0.00 22.35
April 386.67 22.38 0.00 22.38 0.00 22.38
May 399.83 22.36 0.00 22.36 0.00 22.36
June 390.00 22.34 0.00 22.34 0.00 22.34
July 401.83 22.36 0.00 22.36 0.00 22.36
August 400.83 22.32 0.00 22.32 0.00 22.32
September 390.00 22.32 0.00 22.32 0.00 22.32
October 402.83 22.34 0.00 22.34 0.00 22.34
November 384.67 22.39 0.00 22.39 0.00 22.39
December 402.83 22.37 0.00 22.37 0.00 22.37
             
Annual Sum or Average 4710.50 22.35 0.00 22.35 0.00 22.35
Minimum of Months 357.67 22.29 0.00 22.29 0.00 22.29
Maximum of Months 402.83 22.39 0.00 22.39 0.00 22.39



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 401.67 22.39 0.00 22.39 0.00 22.39
February 346.83 22.31 2.00 22.32 0.00 22.32
March 382.33 22.37 6.67 22.40 0.00 22.40
April 375.83 22.39 0.00 22.39 0.00 22.39
May 392.50 22.39 0.33 22.39 0.00 22.39
June 386.33 22.38 0.00 22.38 0.00 22.38
July 397.67 22.40 0.00 22.40 0.00 22.40
August 397.17 22.35 0.00 22.35 0.00 22.35
September 389.83 22.38 0.00 22.38 0.00 22.38
October 398.83 22.39 0.00 22.39 0.00 22.39
November 373.00 22.42 0.00 22.42 0.00 22.42
December 392.50 22.41 0.00 22.41 0.00 22.41
             
Annual Sum or Average 4634.50 22.38 9.00 22.39 0.00 22.39
Minimum of Months 346.83 22.31 0.00 22.32 0.00 22.32
Maximum of Months 401.67 22.42 6.67 22.42 0.00 22.42



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 402.67 22.36 0.00 22.36 0.00 22.36
February 348.67 22.29 0.00 22.29 0.00 22.29
March 385.67 22.36 3.33 22.38 0.00 22.38
April 379.00 22.38 0.00 22.38 0.00 22.38
May 397.17 22.38 0.00 22.38 0.00 22.38
June 388.33 22.35 0.00 22.35 0.00 22.35
July 401.00 22.38 0.00 22.38 0.00 22.38
August 398.00 22.32 0.00 22.32 0.00 22.32
September 389.83 22.35 0.00 22.35 0.00 22.35
October 402.67 22.37 0.00 22.37 0.00 22.37
November 376.33 22.40 0.00 22.40 0.00 22.40
December 397.17 22.40 0.00 22.40 0.00 22.40
             
Annual Sum or Average 4666.50 22.36 3.33 22.36 0.00 22.36
Minimum of Months 348.67 22.29 0.00 22.29 0.00 22.29
Maximum of Months 402.67 22.40 3.33 22.40 0.00 22.40



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 398.17 22.03 10.50 22.05 10.17 22.06
February 350.50 22.14 33.67 22.18 26.33 22.18
March 374.83 22.27 41.00 22.42 28.33 22.49
April 331.00 22.42 57.00 22.67 23.00 22.74
May 326.17 22.48 86.17 22.85 37.50 22.97
June 304.83 22.39 74.17 22.77 23.67 22.86
July 281.67 22.35 106.33 22.93 17.17 23.00
August 336.00 22.46 73.17 22.80 36.17 22.93
September 294.00 22.40 86.83 22.85 21.50 22.93
October 335.83 22.54 90.00 22.89 46.00 23.01
November 359.33 22.38 42.00 22.54 30.00 22.62
December 375.67 22.18 48.00 22.33 38.00 22.42
             
Annual Sum or Average 4068.00 22.33 748.83 22.60 337.83 22.69
Minimum of Months 281.67 22.03 10.50 22.05 10.17 22.06
Maximum of Months 398.17 22.54 106.33 22.93 46.00 23.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 378.33 22.48 6.00 22.51 0.00 22.51
February 336.17 22.43 14.50 22.53 0.00 22.53
March 371.33 22.40 15.17 22.49 0.00 22.49
April 365.83 22.43 4.83 22.46 0.00 22.46
May 394.00 22.43 1.17 22.44 0.00 22.44
June 386.50 22.42 0.00 22.42 0.00 22.42
July 398.00 22.45 0.33 22.45 0.00 22.45
August 397.17 22.41 0.17 22.41 0.00 22.41
September 388.67 22.45 0.17 22.45 0.00 22.45
October 390.00 22.47 0.83 22.47 0.00 22.47
November 352.17 22.44 15.50 22.54 0.00 22.54
December 368.00 22.44 10.00 22.50 0.00 22.50
             
Annual Sum or Average 4526.17 22.44 68.67 22.47 0.00 22.47
Minimum of Months 336.17 22.40 0.00 22.41 0.00 22.41
Maximum of Months 398.00 22.48 15.50 22.54 0.00 22.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 372.50 22.46 7.00 22.50 0.00 22.50
February 327.17 22.40 19.00 22.53 0.00 22.53
March 359.17 22.38 21.67 22.52 0.00 22.52
April 350.00 22.42 14.83 22.51 0.00 22.51
May 371.33 22.43 6.50 22.47 0.00 22.47
June 365.67 22.41 3.00 22.43 0.00 22.43
July 381.17 22.48 1.50 22.49 0.00 22.49
August 381.83 22.41 5.83 22.45 0.00 22.45
September 366.17 22.43 0.50 22.44 0.00 22.44
October 373.17 22.45 3.50 22.47 0.00 22.47
November 335.50 22.41 23.83 22.57 0.00 22.57
December 361.83 22.44 15.50 22.53 0.00 22.53
             
Annual Sum or Average 4345.50 22.43 122.67 22.49 0.00 22.49
Minimum of Months 327.17 22.38 0.50 22.43 0.00 22.43
Maximum of Months 381.83 22.48 23.83 22.57 0.00 22.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 355.67 22.44 14.17 22.53 0.00 22.53
February 317.50 22.40 24.33 22.59 0.00 22.59
March 346.50 22.37 26.33 22.55 0.00 22.55
April 338.17 22.41 25.00 22.58 0.00 22.58
May 350.50 22.40 12.67 22.49 0.00 22.49
June 350.50 22.40 6.83 22.44 0.00 22.44
July 365.67 22.47 6.67 22.51 0.00 22.51
August 364.67 22.39 7.17 22.44 0.00 22.44
September 354.33 22.43 5.83 22.47 0.00 22.47
October 357.17 22.44 12.33 22.52 0.00 22.52
November 319.50 22.39 33.83 22.64 0.00 22.64
December 346.17 22.43 32.67 22.64 0.00 22.64
             
Annual Sum or Average 4166.33 22.42 207.83 22.53 0.00 22.53
Minimum of Months 317.50 22.37 5.83 22.44 0.00 22.44
Maximum of Months 365.67 22.47 33.83 22.64 0.00 22.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 329.00 22.19 15.33 22.28 1.50 22.27
February 301.50 22.29 20.17 22.35 13.00 22.35
March 314.33 22.37 33.83 22.53 20.17 22.61
April 245.67 22.43 53.17 22.79 11.00 22.84
May 214.33 22.40 67.50 22.84 11.00 22.89
June 198.33 22.33 66.50 22.84 6.67 22.88
July 181.83 22.26 103.50 23.09 0.33 23.09
August 218.67 22.35 63.50 22.80 8.17 22.85
September 199.67 22.28 76.33 22.86 0.00 22.86
October 243.17 22.37 65.83 22.79 7.67 22.82
November 314.33 22.43 28.33 22.57 14.33 22.63
December 335.33 22.29 23.83 22.40 15.83 22.46
             
Annual Sum or Average 3096.17 22.33 617.83 22.66 109.67 22.69
Minimum of Months 181.83 22.19 15.33 22.28 0.00 22.27
Maximum of Months 335.33 22.43 103.50 23.09 20.17 23.09



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.36 0.00 22.36 0.00 22.36
February 362.83 22.35 0.00 22.35 0.00 22.35
March 395.50 22.39 0.00 22.39 0.00 22.39
April 388.67 22.46 0.00 22.46 0.00 22.46
May 400.00 22.43 0.00 22.43 0.00 22.43
June 385.67 22.42 0.00 22.42 0.00 22.42
July 395.17 22.48 0.00 22.48 0.00 22.48
August 400.67 22.41 0.00 22.41 0.00 22.41
September 388.83 22.45 0.00 22.45 0.00 22.45
October 400.83 22.46 0.00 22.46 0.00 22.46
November 381.00 22.42 0.00 22.42 0.00 22.42
December 402.67 22.38 0.00 22.38 0.00 22.38
             
Annual Sum or Average 4704.83 22.42 0.00 22.42 0.00 22.42
Minimum of Months 362.83 22.35 0.00 22.35 0.00 22.35
Maximum of Months 403.00 22.48 0.00 22.48 0.00 22.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 292.00 22.36 49.00 22.64 0.50 22.64
February 269.67 22.41 62.00 22.77 16.33 22.83
March 284.00 22.44 77.67 22.84 21.67 22.95
April 241.50 22.36 88.00 22.89 10.83 22.96
May 241.33 22.30 93.83 22.84 8.50 22.89
June 255.00 22.28 82.33 22.73 6.00 22.77
July 220.67 22.21 112.00 22.90 0.00 22.90
August 229.67 22.30 90.17 22.84 7.50 22.89
September 187.83 22.21 106.00 22.99 0.00 22.99
October 187.33 22.29 117.00 23.12 5.67 23.16
November 213.67 22.43 82.67 22.94 13.50 23.02
December 278.00 22.45 89.83 22.93 18.00 23.02
             
Annual Sum or Average 2900.67 22.34 1050.50 22.87 108.50 22.92
Minimum of Months 187.33 22.21 49.00 22.64 0.00 22.64
Maximum of Months 292.00 22.45 117.00 23.12 21.67 23.16



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 390.33 22.49 0.00 22.49 0.00 22.49
February 341.83 22.43 4.00 22.45 0.00 22.45
March 375.33 22.39 5.50 22.42 0.00 22.42
April 371.17 22.42 0.00 22.42 0.00 22.42
May 396.50 22.39 0.00 22.39 0.00 22.39
June 390.00 22.38 0.00 22.38 0.00 22.38
July 401.50 22.40 0.00 22.40 0.00 22.40
August 398.00 22.36 0.00 22.36 0.00 22.36
September 389.83 22.41 0.00 22.41 0.00 22.41
October 393.00 22.44 0.00 22.44 0.00 22.44
November 358.17 22.43 4.67 22.46 0.00 22.46
December 373.83 22.45 0.33 22.45 0.00 22.45
             
Annual Sum or Average 4579.50 22.41 14.50 22.42 0.00 22.42
Minimum of Months 341.83 22.36 0.00 22.36 0.00 22.36
Maximum of Months 401.50 22.49 5.50 22.49 0.00 22.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 395.50 21.45 0.00 21.45 0.00 21.45
February 343.67 21.35 6.17 21.39 1.00 21.39
March 381.17 21.35 8.00 21.41 0.00 21.41
April 374.33 21.34 0.00 21.34 0.00 21.34
May 394.17 21.26 0.00 21.26 0.00 21.26
June 386.67 21.22 0.00 21.22 0.00 21.22
July 398.33 21.21 0.00 21.21 0.00 21.21
August 398.00 21.21 0.00 21.21 0.00 21.21
September 383.33 21.23 0.00 21.23 0.00 21.23
October 392.50 21.30 0.00 21.30 0.00 21.30
November 364.17 21.34 1.83 21.35 0.00 21.35
December 377.50 21.36 0.33 21.36 0.00 21.36
             
Annual Sum or Average 4589.33 21.30 16.33 21.31 1.00 21.31
Minimum of Months 343.67 21.21 0.00 21.21 0.00 21.21
Maximum of Months 398.33 21.45 8.00 21.45 1.00 21.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 328.00 22.52 4.17 22.54 0.00 22.54
February 287.17 22.46 12.67 22.55 0.00 22.55
March 315.33 22.43 13.17 22.51 0.00 22.51
April 312.17 22.46 2.67 22.47 0.00 22.47
May 337.67 22.46 0.67 22.46 0.00 22.46
June 332.67 22.45 0.00 22.45 0.00 22.45
July 347.50 22.49 0.00 22.49 0.00 22.49
August 343.17 22.44 0.00 22.44 0.00 22.44
September 335.00 22.47 0.17 22.47 0.00 22.47
October 340.33 22.50 0.17 22.50 0.00 22.50
November 303.00 22.47 9.83 22.54 0.00 22.54
December 316.50 22.47 4.50 22.50 0.00 22.50
             
Annual Sum or Average 3898.50 22.47 48.00 22.49 0.00 22.49
Minimum of Months 287.17 22.43 0.00 22.44 0.00 22.44
Maximum of Months 347.50 22.52 13.17 22.55 0.00 22.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 311.50 22.49 9.17 22.55 0.00 22.55
February 278.83 22.46 21.17 22.63 0.00 22.63
March 301.33 22.41 24.83 22.59 0.00 22.59
April 301.50 22.46 17.17 22.58 0.00 22.58
May 328.50 22.47 4.33 22.50 0.00 22.50
June 325.83 22.45 0.17 22.46 0.00 22.46
July 341.50 22.51 1.50 22.52 0.00 22.52
August 338.00 22.46 5.17 22.49 0.00 22.49
September 324.67 22.48 0.17 22.48 0.00 22.48
October 324.17 22.50 8.33 22.55 0.00 22.55
November 286.83 22.45 27.33 22.66 0.00 22.66
December 303.83 22.47 27.00 22.66 0.00 22.66
             
Annual Sum or Average 3766.50 22.47 146.33 22.55 0.00 22.55
Minimum of Months 278.83 22.41 0.17 22.46 0.00 22.46
Maximum of Months 341.50 22.51 27.33 22.66 0.00 22.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.32 0.00 22.32 0.00 22.32
February 364.00 22.28 0.00 22.28 0.00 22.28
March 403.00 22.32 0.00 22.32 0.00 22.32
April 390.00 22.25 0.00 22.25 0.00 22.25
May 403.00 22.17 0.00 22.17 0.00 22.17
June 390.00 22.14 0.00 22.14 0.00 22.14
July 403.00 22.11 0.00 22.11 0.00 22.11
August 403.00 22.15 0.00 22.15 0.00 22.15
September 390.00 22.17 0.00 22.17 0.00 22.17
October 403.00 22.27 0.00 22.27 0.00 22.27
November 390.00 22.35 0.00 22.35 0.00 22.35
December 403.00 22.34 0.00 22.34 0.00 22.34
             
Annual Sum or Average 4745.00 22.24 0.00 22.24 0.00 22.24
Minimum of Months 364.00 22.11 0.00 22.11 0.00 22.11
Maximum of Months 403.00 22.35 0.00 22.35 0.00 22.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.32 0.00 22.32 0.00 22.32
February 363.50 22.32 0.00 22.32 0.00 22.32
March 398.83 22.38 0.00 22.38 0.00 22.38
April 389.83 22.40 0.00 22.40 0.00 22.40
May 402.33 22.37 0.00 22.37 0.00 22.37
June 390.00 22.35 0.00 22.35 0.00 22.35
July 401.83 22.38 0.00 22.38 0.00 22.38
August 401.17 22.33 0.00 22.33 0.00 22.33
September 390.00 22.34 0.00 22.34 0.00 22.34
October 402.83 22.36 0.00 22.36 0.00 22.36
November 384.83 22.40 0.00 22.40 0.00 22.40
December 403.00 22.37 0.00 22.37 0.00 22.37
             
Annual Sum or Average 4731.17 22.36 0.00 22.36 0.00 22.36
Minimum of Months 363.50 22.32 0.00 22.32 0.00 22.32
Maximum of Months 403.00 22.40 0.00 22.40 0.00 22.40



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 STORAGE 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 400.50 22.42 0.00 22.42 0.00 22.42
February 343.67 22.32 0.50 22.32 0.00 22.32
March 381.17 22.37 6.00 22.40 0.00 22.40
April 370.83 22.39 0.00 22.39 0.00 22.39
May 391.83 22.40 0.17 22.41 0.00 22.41
June 384.33 22.38 0.00 22.38 0.00 22.38
July 397.00 22.42 0.00 22.42 0.00 22.42
August 397.17 22.37 0.00 22.37 0.00 22.37
September 388.00 22.40 0.00 22.40 0.00 22.40
October 396.50 22.41 0.00 22.41 0.00 22.41
November 370.00 22.43 0.00 22.43 0.00 22.43
December 391.33 22.43 0.00 22.43 0.00 22.43
             
Annual Sum or Average 4612.33 22.40 6.67 22.40 0.00 22.40
Minimum of Months 343.67 22.32 0.00 22.32 0.00 22.32
Maximum of Months 400.50 22.43 6.00 22.43 0.00 22.43



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 387.33 21.97 7.50 22.00 1.67 22.00
February 356.83 22.13 14.67 22.14 12.67 22.13
March 386.17 22.25 26.83 22.33 20.17 22.38
April 343.50 22.32 39.17 22.53 10.67 22.56
May 337.50 22.33 45.67 22.55 10.83 22.59
June 323.17 22.31 46.17 22.57 6.50 22.60
July 293.33 22.26 79.00 22.75 0.33 22.75
August 343.00 22.30 44.67 22.54 8.17 22.57
September 311.50 22.29 49.17 22.57 0.00 22.57
October 346.83 22.34 40.00 22.53 7.50 22.55
November 375.67 22.28 21.67 22.35 15.50 22.39
December 394.50 22.00 21.00 22.05 18.50 22.08
             
Annual Sum or Average 4199.33 22.22 435.50 22.40 112.50 22.43
Minimum of Months 293.33 21.97 7.50 22.00 0.00 22.00
Maximum of Months 394.50 22.34 79.00 22.75 20.17 22.75



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 320.67 22.53 4.67 22.55 0.00 22.55
February 271.00 22.41 22.83 22.59 0.00 22.59
March 288.67 22.45 27.00 22.64 9.67 22.70
April 252.33 22.37 26.17 22.58 0.00 22.58
May 234.17 22.25 40.17 22.54 0.00 22.54
June 232.00 22.24 28.50 22.46 0.00 22.46
July 219.33 22.24 50.83 22.61 0.00 22.61
August 248.50 22.28 32.50 22.50 2.67 22.53
September 221.50 22.25 26.00 22.48 0.00 22.48
October 230.83 22.27 29.83 22.53 0.00 22.53
November 257.17 22.41 28.33 22.61 0.00 22.61
December 287.83 22.45 25.67 22.62 0.00 22.62
             
Annual Sum or Average 3064.00 22.36 342.50 22.56 12.33 22.57
Minimum of Months 219.33 22.24 4.67 22.46 0.00 22.46
Maximum of Months 320.67 22.53 50.83 22.64 9.67 22.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 WORK HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 383.83 22.49 0.33 22.49 0.00 22.49
February 333.67 22.41 14.00 22.50 0.00 22.50
March 365.50 22.39 15.83 22.48 0.00 22.48
April 358.00 22.43 6.17 22.46 0.00 22.46
May 384.00 22.45 4.00 22.47 0.00 22.47
June 379.00 22.43 0.00 22.43 0.00 22.43
July 392.67 22.49 1.17 22.49 0.00 22.49
August 393.50 22.43 3.00 22.44 0.00 22.44
September 376.83 22.45 0.00 22.45 0.00 22.45
October 381.67 22.47 0.00 22.47 0.00 22.47
November 346.50 22.43 13.67 22.51 0.00 22.51
December 364.83 22.44 5.67 22.47 0.00 22.47
             
Annual Sum or Average 4460.00 22.44 63.83 22.47 0.00 22.47
Minimum of Months 333.67 22.39 0.00 22.43 0.00 22.43
Maximum of Months 393.50 22.49 15.83 22.51 0.00 22.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 WORK TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 21.17 4.00 21.18 4.00 21.19
February 363.17 21.23 18.67 21.25 18.67 21.26
March 402.83 21.34 16.83 21.41 16.83 21.49
April 386.17 21.38 10.50 21.44 10.50 21.50
May 400.67 21.44 11.67 21.51 10.67 21.57
June 386.83 21.38 8.00 21.43 6.50 21.47
July 392.83 21.41 6.83 21.46 1.17 21.46
August 399.83 21.36 7.67 21.40 7.17 21.44
September 377.67 21.33 5.50 21.37 0.67 21.38
October 395.50 21.38 9.67 21.44 8.50 21.49
November 389.33 21.35 11.17 21.40 11.17 21.46
December 403.00 21.32 17.83 21.39 17.83 21.46
             
Annual Sum or Average 4700.83 21.34 128.33 21.39 113.67 21.43
Minimum of Months 363.17 21.17 4.00 21.18 0.67 21.19
Maximum of Months 403.00 21.44 18.67 21.51 18.67 21.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 X-RAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 104.83 22.35 122.33 23.68 5.50 23.71
February 81.67 22.40 114.17 23.79 5.33 23.82
March 83.83 22.45 108.67 23.74 7.33 23.79
April 65.50 22.56 123.83 24.02 8.50 24.06
May 57.33 23.14 126.33 24.21 19.33 24.28
June 57.00 23.42 115.17 24.22 25.00 24.32
July 63.67 23.25 143.00 24.25 24.00 24.33
August 58.83 23.44 118.00 24.22 26.17 24.32
September 65.33 23.22 130.00 24.19 23.83 24.27
October 51.83 23.17 137.17 24.31 18.00 24.37
November 55.83 23.07 131.67 24.26 17.50 24.32
December 96.83 22.40 132.17 23.77 7.17 23.81
             
Annual Sum or Average 842.50 22.82 1502.50 24.04 187.67 24.11
Minimum of Months 51.83 22.35 108.67 23.68 5.33 23.71
Maximum of Months 104.83 23.44 143.00 24.31 26.17 24.37



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 353.00 22.16 0.00 22.16 0.00 22.16
February 318.00 22.17 0.00 22.17 0.00 22.17
March 349.00 22.18 0.00 22.18 0.00 22.18
April 340.00 22.19 0.00 22.19 0.00 22.19
May 351.00 22.17 0.00 22.17 0.00 22.17
June 338.00 22.21 0.00 22.21 0.00 22.21
July 353.00 22.26 0.00 22.26 0.00 22.26
August 349.00 22.20 0.00 22.20 0.00 22.20
September 340.00 22.18 0.00 22.18 0.00 22.18
October 353.00 22.12 0.00 22.12 0.00 22.12
November 342.00 22.15 0.00 22.15 0.00 22.15
December 353.00 22.14 0.00 22.14 0.00 22.14
             
Annual Sum or Average 4139.00 22.18 0.00 22.18 0.00 22.18
Minimum of Months 318.00 22.12 0.00 22.12 0.00 22.12
Maximum of Months 353.00 22.26 0.00 22.26 0.00 22.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.20 0.00 22.20 0.00 22.20
February 359.50 22.22 5.83 22.19 5.83 22.16
March 390.67 22.31 0.50 22.32 0.00 22.32
April 350.00 22.34 12.83 22.40 0.00 22.40
May 345.00 22.34 24.83 22.46 0.00 22.46
June 333.17 22.34 28.83 22.49 0.00 22.49
July 317.50 22.34 64.17 22.68 0.00 22.68
August 350.67 22.34 26.17 22.47 0.00 22.47
September 325.00 22.34 39.17 22.53 0.00 22.53
October 354.50 22.37 15.17 22.44 0.00 22.44
November 379.50 22.33 0.17 22.34 0.00 22.34
December 399.50 22.29 0.00 22.29 0.00 22.29
             
Annual Sum or Average 4308.00 22.31 217.67 22.40 5.83 22.40
Minimum of Months 317.50 22.20 0.00 22.19 0.00 22.16
Maximum of Months 403.00 22.37 64.17 22.68 5.83 22.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 353.00 22.28 0.00 22.28 0.00 22.28
February 318.00 22.29 0.00 22.29 0.00 22.29
March 349.00 22.29 0.00 22.29 0.00 22.29
April 337.00 22.31 0.00 22.31 0.00 22.31
May 343.67 22.28 0.00 22.28 0.00 22.28
June 328.50 22.30 0.00 22.30 0.00 22.30
July 333.17 22.34 0.00 22.34 0.00 22.34
August 338.33 22.28 0.00 22.28 0.00 22.28
September 334.83 22.30 0.00 22.30 0.00 22.30
October 352.33 22.26 0.00 22.26 0.00 22.26
November 342.00 22.28 0.00 22.28 0.00 22.28
December 353.00 22.27 0.00 22.27 0.00 22.27
             
Annual Sum or Average 4082.83 22.29 0.00 22.29 0.00 22.29
Minimum of Months 318.00 22.26 0.00 22.26 0.00 22.26
Maximum of Months 353.00 22.34 0.00 22.34 0.00 22.34



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 402.33 21.50 27.00 21.41 27.00 21.33
February 353.83 21.65 29.33 21.59 22.67 21.49
March 380.50 21.86 28.00 21.89 18.83 21.88
April 342.00 22.04 34.67 22.26 0.00 22.26
May 345.17 22.27 61.67 22.59 15.17 22.65
June 333.17 22.30 58.33 22.61 12.50 22.65
July 314.17 22.26 81.33 22.77 2.00 22.78
August 358.17 22.33 53.67 22.60 20.83 22.69
September 322.33 22.26 60.67 22.63 6.17 22.67
October 349.83 22.21 51.17 22.47 14.33 22.52
November 374.33 21.92 30.17 21.94 22.33 21.91
December 388.00 21.67 21.50 21.67 16.00 21.64
             
Annual Sum or Average 4263.83 22.01 537.50 22.20 177.83 22.19
Minimum of Months 314.17 21.50 21.50 21.41 0.00 21.33
Maximum of Months 402.33 22.33 81.33 22.77 27.00 22.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 LOCKER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 402.33 22.44 0.00 22.44 0.00 22.44
February 356.67 22.42 0.33 22.42 0.33 22.41
March 381.33 22.41 0.67 22.41 0.00 22.41
April 341.33 22.39 14.17 22.46 0.00 22.46
May 339.17 22.34 27.83 22.47 0.00 22.47
June 328.00 22.32 32.50 22.49 0.00 22.49
July 315.50 22.32 65.00 22.65 0.00 22.65
August 346.33 22.33 30.67 22.48 0.00 22.48
September 322.50 22.33 30.83 22.48 0.00 22.48
October 351.33 22.38 6.33 22.41 0.00 22.41
November 373.33 22.46 0.17 22.46 0.00 22.46
December 397.33 22.46 0.00 22.46 0.00 22.46
             
Annual Sum or Average 4255.17 22.39 208.50 22.47 0.33 22.47
Minimum of Months 315.50 22.32 0.00 22.41 0.00 22.41
Maximum of Months 402.33 22.46 65.00 22.65 0.33 22.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 378.17 22.44 4.50 22.47 0.00 22.47
February 331.17 22.39 11.83 22.44 1.17 22.44
March 348.67 22.37 29.33 22.51 0.00 22.51
April 300.00 22.34 57.50 22.68 0.00 22.68
May 251.17 22.29 75.00 22.79 0.00 22.79
June 222.17 22.26 69.67 22.81 0.00 22.81
July 186.33 22.29 95.17 23.13 0.00 23.13
August 242.67 22.26 66.50 22.75 0.00 22.75
September 278.50 22.27 77.67 22.76 0.00 22.76
October 308.33 22.31 71.17 22.69 0.00 22.69
November 331.50 22.41 29.50 22.55 0.00 22.55
December 357.00 22.43 15.83 22.51 0.00 22.51
             
Annual Sum or Average 3535.67 22.35 603.67 22.66 1.17 22.66
Minimum of Months 186.33 22.26 4.50 22.44 0.00 22.44
Maximum of Months 378.17 22.44 95.17 23.13 1.17 23.13



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 20.82 15.17 20.78 15.17 20.74
February 364.00 20.87 20.50 20.81 20.50 20.75
March 403.00 21.01 4.17 21.00 4.17 20.99
April 388.83 21.16 0.83 21.15 0.83 21.15
May 399.83 21.33 1.17 21.34 0.00 21.34
June 386.17 21.42 1.83 21.43 0.00 21.43
July 382.83 21.47 6.67 21.51 0.00 21.51
August 397.17 21.33 2.00 21.34 0.00 21.34
September 385.67 21.25 0.50 21.26 0.00 21.26
October 402.50 21.08 0.00 21.08 0.00 21.08
November 390.00 20.94 5.00 20.92 5.00 20.91
December 403.00 20.88 6.83 20.86 6.83 20.85
             
Annual Sum or Average 4706.00 21.13 64.67 21.12 52.50 21.11
Minimum of Months 364.00 20.82 0.00 20.78 0.00 20.74
Maximum of Months 403.00 21.47 20.50 21.51 20.50 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 MECHANICAL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 238.17 22.51 56.83 22.96 1.50 22.99
February 152.50 22.42 60.67 23.01 2.33 22.99
March 131.17 22.48 96.83 23.13 2.33 23.17
April 69.00 23.11 185.67 23.50 8.83 23.63
May 35.50 23.84 246.67 23.45 9.83 23.59
June 18.33 25.02 260.00 23.39 9.83 23.52
July 37.33 25.41 302.50 23.66 24.33 23.88
August 47.50 23.33 257.83 23.26 9.67 23.38
September 41.00 23.91 223.17 23.63 12.33 23.81
October 54.17 23.25 179.83 23.76 9.17 23.90
November 97.67 22.55 98.00 23.43 0.50 23.44
December 226.50 22.42 71.50 23.00 0.17 23.01
             
Annual Sum or Average 1148.83 22.81 2039.50 23.35 90.83 23.46
Minimum of Months 18.33 22.42 56.83 22.96 0.17 22.99
Maximum of Months 238.17 25.41 302.50 23.76 24.33 23.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 401.67 22.25 0.00 22.25 0.00 22.25
February 362.33 22.26 1.67 22.25 1.67 22.24
March 395.83 22.31 0.67 22.31 0.00 22.31
April 348.17 22.30 15.17 22.39 0.00 22.39
May 349.83 22.31 17.83 22.40 0.00 22.40
June 336.83 22.31 28.00 22.46 0.00 22.46
July 318.33 22.29 62.67 22.64 0.00 22.64
August 353.67 22.30 23.00 22.42 0.00 22.42
September 326.33 22.30 29.33 22.46 0.00 22.46
October 360.50 22.33 9.33 22.37 0.00 22.37
November 384.33 22.33 0.00 22.33 0.00 22.33
December 401.33 22.27 0.00 22.27 0.00 22.27
             
Annual Sum or Average 4339.17 22.30 187.67 22.38 1.67 22.38
Minimum of Months 318.33 22.25 0.00 22.25 0.00 22.24
Maximum of Months 401.67 22.33 62.67 22.64 1.67 22.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 350.17 22.31 0.00 22.31 0.00 22.31
February 306.33 22.30 6.33 22.30 3.33 22.28
March 314.67 22.35 11.67 22.41 0.00 22.41
April 276.83 22.35 38.33 22.58 0.00 22.58
May 265.00 22.32 62.00 22.68 0.00 22.68
June 250.83 22.29 60.83 22.69 0.00 22.69
July 236.50 22.31 86.50 22.92 0.00 22.92
August 267.50 22.29 56.17 22.64 0.00 22.64
September 252.33 22.31 67.00 22.72 0.00 22.72
October 274.83 22.34 44.67 22.59 0.00 22.59
November 308.00 22.37 8.83 22.42 0.00 22.42
December 333.17 22.35 2.83 22.37 0.00 22.37
             
Annual Sum or Average 3436.17 22.33 445.17 22.55 3.33 22.55
Minimum of Months 236.50 22.29 0.00 22.30 0.00 22.28
Maximum of Months 350.17 22.37 86.50 22.92 3.33 22.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 402.83 22.28 0.00 22.28 0.00 22.28
February 358.17 22.28 0.83 22.28 0.83 22.27
March 392.83 22.33 0.33 22.33 0.00 22.33
April 352.67 22.32 10.50 22.38 0.00 22.38
May 357.33 22.33 12.17 22.39 0.00 22.39
June 345.00 22.33 19.83 22.43 0.00 22.43
July 326.67 22.31 52.50 22.58 0.00 22.58
August 363.17 22.33 18.83 22.42 0.00 22.42
September 334.00 22.31 23.33 22.43 0.00 22.43
October 362.67 22.34 5.33 22.37 0.00 22.37
November 383.33 22.35 0.00 22.35 0.00 22.35
December 399.00 22.33 0.00 22.33 0.00 22.33
             
Annual Sum or Average 4377.67 22.32 143.67 22.38 0.83 22.38
Minimum of Months 326.67 22.28 0.00 22.28 0.00 22.27
Maximum of Months 402.83 22.35 52.50 22.58 0.83 22.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 20.88 28.33 20.81 28.33 20.75
February 364.00 20.95 21.50 20.88 21.50 20.81
March 403.00 21.09 6.83 21.07 6.83 21.06
April 387.83 21.20 0.67 21.20 0.17 21.20
May 398.50 21.31 1.17 21.32 0.00 21.32
June 384.00 21.32 2.17 21.33 0.00 21.33
July 383.00 21.39 7.17 21.44 0.00 21.44
August 393.50 21.29 3.17 21.31 0.00 21.31
September 380.33 21.28 3.17 21.30 0.00 21.30
October 399.00 21.20 0.33 21.20 0.00 21.20
November 390.00 21.05 13.83 21.00 13.83 20.96
December 403.00 21.00 10.17 20.97 10.17 20.94
             
Annual Sum or Average 4689.17 21.16 98.50 21.15 80.83 21.13
Minimum of Months 364.00 20.88 0.33 20.81 0.00 20.75
Maximum of Months 403.00 21.39 28.33 21.44 28.33 21.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 287.00 21.50 29.00 21.55 8.33 21.51
February 244.33 21.50 32.17 21.58 8.83 21.52
March 274.67 21.59 11.83 21.58 6.33 21.55
April 247.67 21.61 12.00 21.68 1.17 21.67
May 227.67 21.67 4.33 21.71 0.00 21.71
June 189.00 21.72 9.83 21.79 0.00 21.79
July 165.33 21.61 46.83 21.96 0.00 21.96
August 186.83 21.63 32.83 21.81 0.00 21.81
September 160.00 21.55 70.33 21.94 0.00 21.94
October 186.17 21.58 84.83 21.96 0.00 21.96
November 227.67 21.57 46.67 21.71 3.67 21.69
December 289.67 21.53 37.00 21.64 6.00 21.61
             
Annual Sum or Average 2686.00 21.58 417.67 21.73 34.33 21.71
Minimum of Months 160.00 21.50 4.33 21.55 0.00 21.51
Maximum of Months 289.67 21.72 84.83 21.96 8.83 21.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 21.53 0.33 21.52 0.33 21.52
February 364.00 21.55 3.00 21.53 3.00 21.52
March 403.00 21.64 0.17 21.64 0.17 21.64
April 390.00 21.57 0.00 21.57 0.00 21.57
May 403.00 21.59 0.50 21.58 0.50 21.58
June 390.00 21.66 0.17 21.66 0.17 21.66
July 403.00 21.61 0.00 21.61 0.00 21.61
August 403.00 21.65 0.33 21.64 0.33 21.64
September 390.00 21.56 1.67 21.55 1.67 21.54
October 403.00 21.48 0.50 21.48 0.50 21.48
November 390.00 21.53 0.17 21.53 0.17 21.53
December 403.00 21.48 0.00 21.48 0.00 21.48
             
Annual Sum or Average 4745.00 21.57 6.83 21.57 6.83 21.56
Minimum of Months 364.00 21.48 0.00 21.48 0.00 21.48
Maximum of Months 403.00 21.66 3.00 21.66 3.00 21.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 21.03 0.00 21.03 0.00 21.03
February 364.00 21.03 1.00 21.03 1.00 21.02
March 403.00 21.06 0.00 21.06 0.00 21.06
April 390.00 21.05 0.00 21.05 0.00 21.05
May 403.00 21.01 0.00 21.01 0.00 21.01
June 390.00 21.04 0.00 21.04 0.00 21.04
July 403.00 21.06 0.00 21.06 0.00 21.06
August 403.00 21.02 0.00 21.02 0.00 21.02
September 390.00 21.00 0.00 21.00 0.00 21.00
October 403.00 20.96 0.00 20.96 0.00 20.96
November 390.00 21.00 0.00 21.00 0.00 21.00
December 403.00 21.00 0.00 21.00 0.00 21.00
             
Annual Sum or Average 4745.00 21.02 1.00 21.02 1.00 21.02
Minimum of Months 364.00 20.96 0.00 20.96 0.00 20.96
Maximum of Months 403.00 21.06 1.00 21.06 1.00 21.06



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 20.89 1.83 20.89 1.83 20.88
February 364.00 20.90 4.00 20.88 4.00 20.87
March 403.00 20.93 0.00 20.93 0.00 20.93
April 390.00 20.93 0.00 20.93 0.00 20.93
May 403.00 20.91 0.00 20.91 0.00 20.91
June 390.00 20.95 0.00 20.95 0.00 20.95
July 403.00 20.96 0.00 20.96 0.00 20.96
August 403.00 20.94 0.17 20.93 0.17 20.93
September 390.00 20.91 1.67 20.90 1.67 20.90
October 403.00 20.86 0.33 20.86 0.33 20.86
November 390.00 20.89 0.00 20.89 0.00 20.89
December 403.00 20.87 0.00 20.87 0.00 20.87
             
Annual Sum or Average 4745.00 20.91 8.00 20.91 8.00 20.91
Minimum of Months 364.00 20.86 0.00 20.86 0.00 20.86
Maximum of Months 403.00 20.96 4.00 20.96 4.00 20.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.20 0.00 22.20 0.00 22.20
February 364.00 22.22 0.33 22.22 0.33 22.21
March 402.50 22.30 0.00 22.30 0.00 22.30
April 374.83 22.33 0.83 22.33 0.00 22.33
May 384.67 22.35 1.33 22.36 0.00 22.36
June 363.83 22.33 5.83 22.36 0.00 22.36
July 343.83 22.31 27.83 22.45 0.00 22.45
August 381.50 22.32 6.67 22.35 0.00 22.35
September 365.67 22.33 2.50 22.35 0.00 22.35
October 398.67 22.34 0.00 22.34 0.00 22.34
November 390.00 22.29 0.00 22.29 0.00 22.29
December 403.00 22.25 0.00 22.25 0.00 22.25
             
Annual Sum or Average 4575.50 22.30 45.33 22.32 0.33 22.32
Minimum of Months 343.83 22.20 0.00 22.20 0.00 22.20
Maximum of Months 403.00 22.35 27.83 22.45 0.33 22.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 TREATMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 21.66 0.00 21.66 0.00 21.66
February 364.00 21.67 1.00 21.66 1.00 21.66
March 403.00 21.74 0.00 21.74 0.00 21.74
April 390.00 21.67 0.00 21.67 0.00 21.67
May 403.00 21.69 0.00 21.69 0.00 21.69
June 390.00 21.75 0.00 21.75 0.00 21.75
July 403.00 21.71 0.00 21.71 0.00 21.71
August 403.00 21.75 0.00 21.75 0.00 21.75
September 390.00 21.67 0.00 21.67 0.00 21.67
October 403.00 21.61 0.00 21.61 0.00 21.61
November 390.00 21.66 0.00 21.66 0.00 21.66
December 403.00 21.62 0.00 21.62 0.00 21.62
             
Annual Sum or Average 4745.00 21.68 1.00 21.68 1.00 21.68
Minimum of Months 364.00 21.61 0.00 21.61 0.00 21.61
Maximum of Months 403.00 21.75 1.00 21.75 1.00 21.75



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 350.83 22.26 21.00 22.39 0.00 22.39
February 315.33 22.27 29.17 22.43 3.67 22.41
March 328.83 22.27 35.67 22.47 0.00 22.47
April 266.67 22.31 56.67 22.71 0.00 22.71
May 265.00 22.30 68.17 22.73 0.00 22.73
June 264.50 22.28 62.83 22.69 0.00 22.69
July 214.50 22.32 88.33 23.02 0.00 23.02
August 236.17 22.30 62.17 22.76 0.00 22.76
September 225.17 22.29 76.00 22.88 0.00 22.88
October 246.83 22.31 74.00 22.83 0.00 22.83
November 291.17 22.30 35.83 22.53 0.00 22.53
December 327.17 22.26 37.67 22.50 0.00 22.50
             
Annual Sum or Average 3332.17 22.29 647.50 22.65 3.67 22.65
Minimum of Months 214.50 22.26 21.00 22.39 0.00 22.39
Maximum of Months 350.83 22.32 88.33 23.02 3.67 23.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 346.83 22.22 28.33 22.40 0.00 22.40
February 313.67 22.24 33.83 22.42 6.00 22.39
March 335.67 22.25 38.00 22.48 0.00 22.48
April 275.67 22.31 57.17 22.72 0.00 22.72
May 282.00 22.30 73.50 22.77 0.00 22.77
June 272.50 22.28 67.17 22.72 0.00 22.72
July 220.33 22.30 92.67 23.05 0.00 23.05
August 246.83 22.28 66.67 22.78 0.00 22.78
September 225.83 22.31 79.17 22.95 0.17 22.95
October 244.83 22.34 78.67 22.92 0.00 22.92
November 285.83 22.29 44.83 22.59 0.00 22.59
December 325.67 22.24 47.17 22.54 0.00 22.54
             
Annual Sum or Average 3375.67 22.28 707.17 22.68 6.17 22.68
Minimum of Months 220.33 22.22 28.33 22.40 0.00 22.39
Maximum of Months 346.83 22.34 92.67 23.05 6.00 23.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.00 22.09 0.00 22.09 0.00 22.09
February 364.00 22.11 0.00 22.11 0.00 22.11
March 403.00 22.18 0.00 22.18 0.00 22.18
April 390.00 22.22 0.00 22.22 0.00 22.22
May 403.00 22.22 0.00 22.22 0.00 22.22
June 389.50 22.25 0.00 22.25 0.00 22.25
July 395.17 22.30 0.00 22.30 0.00 22.30
August 402.67 22.23 0.00 22.23 0.00 22.23
September 390.00 22.23 0.00 22.23 0.00 22.23
October 403.00 22.17 0.00 22.17 0.00 22.17
November 390.00 22.14 0.00 22.14 0.00 22.14
December 403.00 22.11 0.00 22.11 0.00 22.11
             
Annual Sum or Average 4736.33 22.19 0.00 22.19 0.00 22.19
Minimum of Months 364.00 22.09 0.00 22.09 0.00 22.09
Maximum of Months 403.00 22.30 0.00 22.30 0.00 22.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 331.50 21.94 14.00 21.98 4.50 21.96
February 288.50 21.99 15.17 22.02 6.00 21.98
March 292.17 22.08 19.00 22.18 2.33 22.17
April 193.50 22.13 54.50 22.64 0.50 22.65
May 146.50 22.20 76.33 22.86 0.00 22.86
June 126.67 22.32 76.83 23.03 1.67 23.06
July 113.50 22.52 113.67 23.50 6.83 23.60
August 144.33 22.27 76.33 22.91 1.50 22.94
September 141.00 22.22 82.50 23.04 0.83 23.05
October 203.83 22.17 62.83 22.68 0.00 22.68
November 294.17 22.13 16.83 22.20 2.00 22.19
December 325.00 21.94 14.00 21.98 4.17 21.96
             
Annual Sum or Average 2600.67 22.11 622.00 22.51 30.33 22.51
Minimum of Months 113.50 21.94 14.00 21.98 0.00 21.96
Maximum of Months 331.50 22.52 113.67 23.50 6.83 23.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: NE STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 381.83 21.61 48.67 21.63 32.50 21.55
February 345.50 21.85 51.33 21.86 40.33 21.80
March 373.33 22.00 68.83 22.13 45.67 22.13
April 301.67 22.18 76.17 22.59 25.50 22.64
May 215.67 22.55 100.00 23.18 35.33 23.29
June 152.83 22.72 89.33 23.46 27.00 23.59
July 138.67 22.87 120.17 23.80 27.00 23.93
August 182.50 22.66 87.67 23.31 29.00 23.46
September 164.50 22.58 101.50 23.41 23.00 23.52
October 278.67 22.50 103.50 23.05 44.50 23.16
November 360.50 22.20 60.17 22.37 38.83 22.42
December 370.50 21.82 76.33 21.99 54.00 22.01
             
Annual Sum or Average 3266.17 22.17 983.67 22.60 422.67 22.65
Minimum of Months 138.67 21.61 48.67 21.63 23.00 21.55
Maximum of Months 381.83 22.87 120.17 23.80 54.00 23.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: NW ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 366.00 21.76 31.33 21.83 16.00 21.80
February 332.67 21.88 51.33 22.02 30.00 21.99
March 358.33 22.02 69.67 22.25 36.83 22.28
April 321.67 22.20 74.67 22.59 23.33 22.64
May 329.67 22.40 94.50 22.82 37.50 22.91
June 317.83 22.36 78.17 22.75 23.33 22.82
July 287.17 22.35 109.00 22.96 17.17 23.01
August 329.33 22.45 83.33 22.84 35.83 22.96
September 288.17 22.35 96.33 22.90 19.17 22.96
October 321.83 22.45 109.00 22.93 44.00 23.02
November 338.50 22.20 66.00 22.45 34.83 22.51
December 352.67 21.98 82.83 22.28 43.00 22.32
             
Annual Sum or Average 3943.83 22.19 946.17 22.55 361.00 22.60
Minimum of Months 287.17 21.76 31.33 21.83 16.00 21.80
Maximum of Months 366.00 22.45 109.00 22.96 44.00 23.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: NW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 388.33 21.58 41.67 21.59 29.33 21.52
February 347.67 21.83 47.00 21.83 38.50 21.79
March 368.67 21.99 67.67 22.13 45.00 22.14
April 301.83 22.22 80.33 22.65 24.50 22.70
May 198.67 22.62 101.83 23.30 34.17 23.42
June 145.33 22.73 93.00 23.50 26.17 23.63
July 127.17 22.89 121.50 23.85 26.33 23.99
August 174.33 22.72 92.67 23.39 30.33 23.55
September 172.83 22.58 107.00 23.39 22.67 23.50
October 304.83 22.52 105.83 23.03 46.00 23.15
November 358.33 22.20 61.33 22.38 39.33 22.44
December 372.50 21.85 71.83 22.02 51.83 22.06
             
Annual Sum or Average 3260.50 22.18 991.67 22.62 414.17 22.68
Minimum of Months 127.17 21.58 41.67 21.59 22.67 21.52
Maximum of Months 388.33 22.89 121.50 23.85 51.83 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: SW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 307.33 21.94 64.50 22.32 12.17 22.30
February 289.33 22.08 66.17 22.38 29.50 22.37
March 324.33 22.14 78.67 22.47 34.33 22.50
April 290.17 22.32 83.00 22.80 24.17 22.87
May 299.50 22.47 98.67 22.97 35.50 23.07
June 295.50 22.41 85.67 22.87 23.83 22.96
July 247.17 22.43 114.83 23.16 19.83 23.23
August 263.17 22.55 91.17 23.06 33.33 23.20
September 213.17 22.52 108.67 23.25 23.00 23.36
October 246.50 22.69 124.00 23.32 46.17 23.46
November 265.50 22.39 97.67 22.85 32.33 22.93
December 304.33 22.22 102.50 22.69 44.17 22.77
             
Annual Sum or Average 3346.00 22.33 1115.50 22.84 358.33 22.91
Minimum of Months 213.17 21.94 64.50 22.32 12.17 22.30
Maximum of Months 324.33 22.69 124.00 23.32 46.17 23.46



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 ANESTHESIA PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.14031 49.32306 -0.1080 6.01786
February 364.00000 21.03041 49.83280 -0.1348 6.11320
March 403.00000 20.86574 51.20788 -0.1742 6.15004
April 390.00000 20.73451 53.50197 -0.2085 6.45597
May 403.00000 20.69090 53.91587 -1.3807 44.69681
June 390.00000 20.70183 53.92868 -1.3760 44.43511
July 403.00000 20.62345 53.93328 -1.3963 45.51690
August 403.00000 20.75067 53.78454 -1.3405 42.63064
September 390.00000 20.76816 53.43678 -1.3185 41.56820
October 403.00000 20.90931 53.10198 -0.1339 5.91437
November 390.00000 21.02976 51.74675 -0.1103 5.90989
December 403.00000 21.07488 51.20431 -0.1089 5.95111
           
Annual Sum or Average 4745.00000 20.85916 52.42286 -0.6523 21.87796
Minimum of Months 364.00000 20.62345 49.32306 -1.3963 5.90989
Maximum of Months 403.00000 21.14031 53.93328 -0.1080 45.51690



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 CAFE PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 23.03923 53.80553 0.36801 8.63922
February 364.00000 22.98825 54.03713 0.35919 8.66214
March 403.00000 22.93693 55.66297 0.35984 8.61063
April 390.00000 23.12337 59.06181 0.41576 9.39217
May 403.00000 23.27029 62.41401 -0.4407 10.22545
June 390.00000 23.64640 65.23270 -0.3093 7.96824
July 403.00000 23.97874 64.41196 -0.2177 7.02857
August 403.00000 23.88901 65.78873 -0.2159 7.16306
September 390.00000 23.85468 63.13314 -0.2272 7.32068
October 403.00000 23.62159 60.23045 0.56913 12.55801
November 390.00000 23.39097 58.60377 0.49945 11.06292
December 403.00000 23.11917 55.29003 0.40485 9.41468
           
Annual Sum or Average 4745.00000 23.40722 59.83479 0.12897 9.00737
Minimum of Months 364.00000 22.93693 53.80553 -0.4407 7.02857
Maximum of Months 403.00000 23.97874 65.78873 0.56913 12.55801



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 CLEAN PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 20.95356 47.84505 -0.1825 6.33035
February 364.00000 20.88330 48.14866 -0.1980 6.41438
March 403.00000 20.83108 49.09607 -0.1993 6.27185
April 390.00000 20.70401 51.55414 -0.2314 6.74106
May 403.00000 20.62977 52.11805 -1.4274 47.06960
June 390.00000 20.63220 52.20427 -1.4367 47.51018
July 403.00000 20.49438 52.56548 -1.4883 50.18818
August 403.00000 20.63709 52.20730 -1.4378 47.56831
September 390.00000 20.54954 52.31537 -1.4696 49.21885
October 403.00000 20.59320 52.11630 -0.2717 7.21335
November 390.00000 20.79042 50.59921 -0.2187 6.62098
December 403.00000 20.85179 49.66901 -0.1962 6.43451
           
Annual Sum or Average 4745.00000 20.71160 50.88353 -0.7330 24.07040
Minimum of Months 364.00000 20.49438 47.84505 -1.4883 6.27185
Maximum of Months 403.00000 20.95356 52.56548 -0.1825 50.18818



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 CLEAN WORK PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 20.82814 48.26633 -0.2337 6.82550
February 364.00000 20.76988 48.54087 -0.2467 6.94031
March 403.00000 20.74668 49.43478 -0.2421 6.74499
April 390.00000 20.61676 51.91014 -0.2745 7.29929
May 403.00000 20.56555 52.40820 -1.4817 49.81793
June 390.00000 20.58585 52.43949 -1.4835 49.89072
July 403.00000 20.44274 52.81097 -1.5355 52.57581
August 403.00000 20.59129 52.44221 -1.4837 49.90564
September 390.00000 20.50101 52.55116 -1.5162 51.57424
October 403.00000 20.52653 52.40942 -0.3095 7.76324
November 390.00000 20.69028 50.96810 -0.2643 7.16392
December 403.00000 20.73219 50.10540 -0.2457 6.95886
           
Annual Sum or Average 4745.00000 20.63233 51.20386 -0.7796 25.39870
Minimum of Months 364.00000 20.44274 48.26633 -1.5355 6.74499
Maximum of Months 403.00000 20.82814 52.81097 -0.2337 52.57581



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 DICTATION PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.48048 43.47185 0.03716 5.16499
February 318.00000 22.42645 43.60399 0.02447 5.13322
March 349.00000 22.39239 44.49794 0.02728 5.10459
April 340.00000 22.29488 46.71660 0.00170 5.09695
May 351.00000 22.16821 47.49436 -1.1065 30.97456
June 338.00000 22.11795 47.79565 -1.1256 31.86962
July 353.00000 22.03885 48.00749 -1.1628 33.66070
August 349.00000 22.12068 47.83718 -1.1264 31.89622
September 340.00000 22.05994 47.84663 -1.1520 33.15359
October 353.00000 22.14389 47.46954 -0.0423 5.17297
November 342.00000 22.34865 45.95991 0.00941 5.11241
December 353.00000 22.43445 44.96802 0.03353 5.15667
           
Annual Sum or Average 4139.00000 22.25149 46.31769 -0.4670 16.50039
Minimum of Months 318.00000 22.03885 43.47185 -1.1628 5.09695
Maximum of Months 353.00000 22.48048 48.00749 0.03716 33.66070



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 DRESSING ROOM PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.31183 45.57517 0.00732 5.49416
February 318.00000 22.29594 46.00949 0.01948 5.69252
March 349.00000 22.35759 47.34019 0.04900 5.81582
April 340.00000 22.60491 48.30319 0.13051 5.75116
May 351.00000 22.78600 48.62381 -0.7762 18.82252
June 338.00000 22.79205 47.86808 -0.7532 18.01235
July 353.00000 23.02184 47.03889 -0.6849 16.46800
August 349.00000 22.81002 47.82251 -0.7430 17.91550
September 340.00000 22.91526 47.21808 -0.7261 17.45573
October 353.00000 22.86115 48.20917 0.21681 6.62915
November 342.00000 22.59825 47.45573 0.13115 5.85842
December 353.00000 22.49241 48.02692 0.07626 5.87303
           
Annual Sum or Average 4139.00000 22.65602 47.46566 -0.2552 10.83526
Minimum of Months 318.00000 22.29594 45.57517 -0.7762 5.49416
Maximum of Months 353.00000 23.02184 48.62381 0.21681 18.82252



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 HUMID PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.60778 42.87335 0.07464 5.28955
February 318.00000 22.55474 43.02736 0.06288 5.22798
March 349.00000 22.49463 43.92850 0.06042 5.20029
April 340.00000 22.44140 45.99878 0.04719 5.14152
May 351.00000 22.33389 46.64634 -1.0323 27.59624
June 338.00000 22.27834 46.92667 -1.0521 28.44973
July 353.00000 22.24575 47.01410 -1.0748 29.46633
August 349.00000 22.27701 46.96809 -1.0538 28.52140
September 340.00000 22.25143 46.90806 -1.0697 29.24128
October 353.00000 22.32269 46.59625 0.01181 5.06966
November 342.00000 22.50157 45.23061 0.05531 5.17784
December 353.00000 22.56771 44.34860 0.07263 5.27318
           
Annual Sum or Average 4139.00000 22.40582 45.54982 -0.4099 15.00712
Minimum of Months 318.00000 22.24575 42.87335 -1.0748 5.06966
Maximum of Months 353.00000 22.60778 47.01410 0.07464 29.46633



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 IT ROOM PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.32195 44.10382 -0.0271 5.08998
February 318.00000 22.32022 43.97721 -0.0201 5.18798
March 349.00000 22.37977 44.60036 0.01048 5.07141
April 340.00000 22.42553 46.24743 0.03656 5.08428
May 351.00000 22.42182 46.51137 -1.0009 26.23845
June 338.00000 22.40127 46.64349 -1.0035 26.34039
July 353.00000 22.44053 46.48622 -1.0003 26.21117
August 349.00000 22.38996 46.71635 -1.0092 26.57900
September 340.00000 22.38219 46.61701 -1.0223 27.13353
October 353.00000 22.37484 46.61285 0.02056 5.05058
November 342.00000 22.41576 45.73707 0.02148 5.06767
December 353.00000 22.36489 45.29442 -0.0029 5.06115
           
Annual Sum or Average 4139.00000 22.38687 45.80401 -0.4179 14.04070
Minimum of Months 318.00000 22.32022 43.97721 -1.0223 5.05058
Maximum of Months 353.00000 22.44053 46.71635 0.03656 27.13353



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 LOBBY PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.66020 44.56415 0.15142 5.79266
February 364.00000 22.65270 44.58704 0.16308 6.09482
March 403.00000 22.66782 45.42248 0.18999 6.22257
April 390.00000 22.81941 46.56628 0.24650 6.83531
May 403.00000 22.80384 46.81389 -0.6990 16.30622
June 390.00000 22.73319 46.90388 -0.7154 16.63643
July 403.00000 22.92454 46.15083 -0.6567 15.32022
August 403.00000 22.74774 46.82647 -0.6993 16.26855
September 390.00000 22.84802 46.32400 -0.6844 15.97932
October 403.00000 22.86458 46.47424 0.26447 6.99299
November 390.00000 22.74866 46.20005 0.21668 6.31602
December 403.00000 22.74055 45.88588 0.18811 6.23068
           
Annual Sum or Average 4745.00000 22.76833 46.06723 -0.1716 10.44060
Minimum of Months 364.00000 22.65270 44.56415 -0.7154 5.79266
Maximum of Months 403.00000 22.92454 46.90388 0.26447 16.63643



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 LOCKER ROOM PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.83097 44.70658 0.18330 6.07204
February 364.00000 22.76761 44.89138 0.17644 6.03561
March 403.00000 22.70768 45.93346 0.18269 6.08186
April 390.00000 22.77254 47.38844 0.20533 6.20653
May 403.00000 22.76590 47.63217 -0.7599 17.81689
June 390.00000 22.70147 47.70826 -0.7719 18.10027
July 403.00000 22.83149 47.15909 -0.7486 17.45536
August 403.00000 22.69585 47.77169 -0.7736 18.17788
September 390.00000 22.76632 47.30302 -0.7685 18.01525
October 403.00000 22.80997 47.37095 0.21481 6.28742
November 390.00000 22.84435 46.62711 0.21631 6.31538
December 403.00000 22.85364 46.14965 0.20266 6.31083
           
Annual Sum or Average 4745.00000 22.77916 46.72930 -0.2057 11.10244
Minimum of Months 364.00000 22.69585 44.70658 -0.7736 6.03561
Maximum of Months 403.00000 22.85364 47.77169 0.21631 18.17788



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 LOUNGE PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.76386 44.40746 0.14509 5.70086
February 364.00000 22.72059 44.41924 0.14005 5.68359
March 403.00000 22.65612 45.26686 0.14514 5.69118
April 390.00000 22.69588 46.89509 0.15844 5.74898
May 403.00000 22.65057 47.24131 -0.8490 20.57749
June 390.00000 22.58527 47.51898 -0.8669 21.15604
July 403.00000 22.66507 47.18462 -0.8598 20.92538
August 403.00000 22.58024 47.58679 -0.8705 21.29023
September 390.00000 22.61697 47.29141 -0.8737 21.40083
October 403.00000 22.66721 47.10540 0.14420 5.60129
November 390.00000 22.76201 46.27016 0.16388 5.80603
December 403.00000 22.76792 45.56924 0.15630 5.78988
           
Annual Sum or Average 4745.00000 22.67743 46.40608 -0.2747 12.15168
Minimum of Months 364.00000 22.58024 44.40746 -0.8737 5.60129
Maximum of Months 403.00000 22.76792 47.58679 0.16388 21.40083



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 MRI CONTROL ROOM PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 23.08166 44.12510 0.33194 7.92735
February 364.00000 23.05377 44.52108 0.33704 7.99865
March 403.00000 22.92299 45.20226 0.33309 7.94325
April 390.00000 23.03979 46.56871 0.37469 8.56949
May 403.00000 22.98965 48.27620 -0.5089 11.61545
June 390.00000 22.91838 49.82804 -0.5050 11.46797
July 403.00000 23.08861 49.62873 -0.4648 10.82865
August 403.00000 22.90622 50.35401 -0.5051 11.46868
September 390.00000 23.02619 49.57480 -0.4891 11.27441
October 403.00000 23.07247 48.12166 0.40268 9.01823
November 390.00000 23.07637 46.99510 0.38107 8.64213
December 403.00000 23.10263 44.77309 0.34812 8.23220
           
Annual Sum or Average 4745.00000 23.02306 47.34384 0.00091 9.59077
Minimum of Months 364.00000 22.90622 44.12510 -0.5089 7.92735
Maximum of Months 403.00000 23.10263 50.35401 0.40268 11.61545



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 MRI ROOM PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 23.08186 42.83059 0.39314 8.80933
February 364.00000 23.05396 43.36866 0.39293 8.80526
March 403.00000 22.92306 44.02992 0.38581 8.65919
April 390.00000 23.03971 45.73668 0.41293 9.13757
May 403.00000 22.98962 47.76804 -0.4719 10.69770
June 390.00000 22.91836 49.52731 -0.4757 10.71708
July 403.00000 23.08854 49.40016 -0.4450 10.25137
August 403.00000 22.90627 50.01948 -0.4732 10.66103
September 390.00000 23.02618 49.20788 -0.4591 10.49756
October 403.00000 23.07249 47.50389 0.43013 9.41802
November 390.00000 23.07641 46.18581 0.42325 9.31140
December 403.00000 23.10282 43.59191 0.40236 9.00113
           
Annual Sum or Average 4745.00000 23.02311 46.61237 0.04084 9.66818
Minimum of Months 364.00000 22.90627 42.83059 -0.4757 8.65919
Maximum of Months 403.00000 23.10282 50.01948 0.43013 10.71708



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 NOURISHMENT PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.63134 44.92968 0.10903 5.45114
February 364.00000 22.57434 45.04170 0.09577 5.36286
March 403.00000 22.51150 45.98192 0.09380 5.32402
April 390.00000 22.47098 47.95435 0.07954 5.24640
May 403.00000 22.37480 48.62436 -0.9912 25.89240
June 390.00000 22.32308 48.97215 -1.0107 26.70440
July 403.00000 22.29444 48.92720 -1.0358 27.78746
August 403.00000 22.32463 49.03802 -1.0117 26.73996
September 390.00000 22.30066 48.85245 -1.0290 27.50127
October 403.00000 22.37197 48.49622 0.04555 5.13367
November 390.00000 22.53536 47.27233 0.08967 5.30516
December 403.00000 22.59204 46.27434 0.10557 5.42180
           
Annual Sum or Average 4745.00000 22.44139 47.54282 -0.3744 14.37573
Minimum of Months 364.00000 22.29444 44.92968 -1.0358 5.13367
Maximum of Months 403.00000 22.63134 49.03802 0.10903 27.78746



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 NURSE STATION PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.59750 45.28715 0.09435 5.34084
February 364.00000 22.53635 45.39552 0.07976 5.27864
March 403.00000 22.49094 46.32550 0.08111 5.25534
April 390.00000 22.43692 48.34510 0.06262 5.17774
May 403.00000 22.33965 49.05477 -1.0183 27.03773
June 390.00000 22.28826 49.43401 -1.0395 27.95768
July 403.00000 22.25253 49.39889 -1.0669 29.16989
August 403.00000 22.29733 49.46484 -1.0368 27.82565
September 390.00000 22.27363 49.23566 -1.0516 28.50254
October 403.00000 22.35781 48.80249 0.03495 5.11645
November 390.00000 22.51764 47.57368 0.07955 5.24911
December 403.00000 22.56521 46.60067 0.09284 5.32726
           
Annual Sum or Average 4745.00000 22.41217 47.92244 -0.3935 14.82653
Minimum of Months 364.00000 22.25253 45.28715 -1.0669 5.11645
Maximum of Months 403.00000 22.59750 49.46484 0.09435 29.16989



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 OFFICE PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.69315 43.04215 0.10999 5.42392
February 318.00000 22.64007 43.12980 0.09972 5.37659
March 349.00000 22.58365 44.00189 0.10254 5.36881
April 340.00000 22.58369 45.85796 0.10423 5.34277
May 351.00000 22.52112 46.30734 -0.9335 23.55881
June 338.00000 22.46341 46.56489 -0.9520 24.26644
July 353.00000 22.49381 46.44056 -0.9559 24.41035
August 349.00000 22.46781 46.58273 -0.9510 24.22633
September 340.00000 22.48274 46.39352 -0.9555 24.40045
October 353.00000 22.54707 46.14214 0.09020 5.25296
November 342.00000 22.66050 45.10848 0.11589 5.42311
December 353.00000 22.68130 44.35867 0.11669 5.45533
           
Annual Sum or Average 4139.00000 22.56804 45.33677 -0.3356 13.23715
Minimum of Months 318.00000 22.46341 43.04215 -0.9559 5.25296
Maximum of Months 353.00000 22.69315 46.58273 0.11669 24.41035



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 OPERATING ROOM 1 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 19.15089 46.17391 -0.4571 10.39455
February 364.00000 19.14918 47.25334 -0.4423 10.17536
March 403.00000 19.15223 48.53309 -0.4275 9.91628
April 390.00000 19.15749 51.26295 -0.3996 9.40660
May 403.00000 19.18171 54.31691 -1.5670 55.10255
June 390.00000 19.37709 56.57985 -1.4801 50.59963
July 403.00000 19.57411 55.68791 -1.4198 47.52185
August 403.00000 19.58111 57.15701 -1.4073 46.90378
September 390.00000 19.45529 55.51337 -1.4422 48.67452
October 403.00000 19.29329 53.25880 -0.3255 8.42592
November 390.00000 19.18334 51.43353 -0.3845 9.27995
December 403.00000 19.15015 47.90732 -0.4478 10.24749
           
Annual Sum or Average 4745.00000 19.28483 52.11197 -0.8526 26.48662
Minimum of Months 364.00000 19.14918 46.17391 -1.5670 8.42592
Maximum of Months 403.00000 19.58111 57.15701 -0.3255 55.10255



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 OPERATING ROOM 2 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 19.14883 46.45519 -0.4910 11.04668
February 364.00000 19.14892 47.40953 -0.4727 10.72484
March 403.00000 19.15184 48.56463 -0.4456 10.18208
April 390.00000 19.15329 51.18677 -0.4126 9.58202
May 403.00000 19.16723 54.23916 -1.5898 56.23703
June 390.00000 19.31239 56.65151 -1.5192 52.58134
July 403.00000 19.47495 55.81119 -1.4759 50.29998
August 403.00000 19.45374 57.39550 -1.4769 50.36649
September 390.00000 19.31603 55.93590 -1.5292 53.08026
October 403.00000 19.21418 53.68180 -0.3818 9.16559
November 390.00000 19.15325 51.89732 -0.4295 10.00910
December 403.00000 19.14926 48.18904 -0.4849 10.95669
           
Annual Sum or Average 4745.00000 19.23775 52.30697 -0.8950 27.95553
Minimum of Months 364.00000 19.14883 46.45519 -1.5898 9.16559
Maximum of Months 403.00000 19.47495 57.39550 -0.3818 56.23703



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 OPERATING ROOM 3 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 19.14844 46.56302 -0.5174 11.66243
February 364.00000 19.14935 47.54902 -0.5091 11.50285
March 403.00000 19.15118 48.86571 -0.4909 11.08812
April 390.00000 19.15133 51.86663 -0.4823 10.94277
May 403.00000 19.15410 55.20163 -1.7108 62.34169
June 390.00000 19.16009 58.02126 -1.6917 61.41636
July 403.00000 19.19084 57.18302 -1.7027 61.90550
August 403.00000 19.18507 58.73736 -1.6816 60.90336
September 390.00000 19.16005 57.32271 -1.7081 62.20253
October 403.00000 19.15876 54.56623 -0.4739 10.87042
November 390.00000 19.15172 52.38747 -0.4801 11.00184
December 403.00000 19.14877 48.09225 -0.5079 11.47435
           
Annual Sum or Average 4745.00000 19.15926 53.05425 -0.9993 32.40166
Minimum of Months 364.00000 19.14844 46.56302 -1.7108 10.87042
Maximum of Months 403.00000 19.19084 58.73736 -0.4739 62.34169



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 PACU PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 20.88514 49.62676 -0.2217 6.69321
February 364.00000 20.81580 49.91336 -0.2382 6.83387
March 403.00000 20.78333 50.88640 -0.2367 6.66821
April 390.00000 20.64288 53.21827 -0.2746 7.27999
May 403.00000 20.58075 53.74134 -1.4917 50.34004
June 390.00000 20.59392 53.85538 -1.4986 50.66843
July 403.00000 20.45131 54.13246 -1.5520 53.41963
August 403.00000 20.60067 53.87654 -1.4976 50.63041
September 390.00000 20.51252 53.91620 -1.5278 52.17116
October 403.00000 20.55014 53.75318 -0.3093 7.74647
November 390.00000 20.73332 52.20634 -0.2577 7.07061
December 403.00000 20.78741 51.37532 -0.2351 6.82896
           
Annual Sum or Average 4745.00000 20.66061 52.55510 -0.7816 25.64161
Minimum of Months 364.00000 20.45131 49.62676 -1.5520 6.66821
Maximum of Months 403.00000 20.88514 54.13246 -0.2217 53.41963



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 1 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 20.93020 49.14765 -0.2223 6.54397
February 364.00000 20.86971 49.44129 -0.2311 6.61018
March 403.00000 20.83807 50.45333 -0.2294 6.46597
April 390.00000 20.74432 52.65357 -0.2414 6.69968
May 403.00000 20.68776 53.15313 -1.4274 47.08660
June 390.00000 20.68670 53.26232 -1.4337 47.38383
July 403.00000 20.58360 53.41517 -1.4651 49.04771
August 403.00000 20.70688 53.24382 -1.4211 46.73419
September 390.00000 20.64108 53.19218 -1.4453 48.01992
October 403.00000 20.68402 53.05472 -0.2555 6.85040
November 390.00000 20.83037 51.63269 -0.2261 6.53801
December 403.00000 20.86353 50.90805 -0.2239 6.52794
           
Annual Sum or Average 4745.00000 20.75491 51.97597 -0.7382 23.81175
Minimum of Months 364.00000 20.58360 49.14765 -1.4651 6.46597
Maximum of Months 403.00000 20.93020 53.41517 -0.2223 49.04771



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 2 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 20.95008 48.51989 -0.1890 6.33825
February 364.00000 20.87925 48.82415 -0.2047 6.43295
March 403.00000 20.82895 49.84244 -0.2058 6.29787
April 390.00000 20.70787 52.20154 -0.2357 6.73529
May 403.00000 20.63313 52.79093 -1.4351 47.48206
June 390.00000 20.63186 52.91950 -1.4464 48.03080
July 403.00000 20.49710 53.20012 -1.4950 50.56725
August 403.00000 20.63755 52.92958 -1.4473 48.08102
September 390.00000 20.55103 52.97072 -1.4776 49.65579
October 403.00000 20.59684 52.76104 -0.2756 7.20249
November 390.00000 20.79264 51.24432 -0.2235 6.61517
December 403.00000 20.85031 50.32429 -0.2019 6.43517
           
Annual Sum or Average 4745.00000 20.71215 51.55774 -0.7397 24.26236
Minimum of Months 364.00000 20.49710 48.51989 -1.4950 6.29787
Maximum of Months 403.00000 20.95008 53.20012 -0.1890 50.56725



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 PROCEDURE ROOM PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 20.70250 48.66751 -0.2346 7.06213
February 364.00000 20.64972 48.97079 -0.2365 7.10719
March 403.00000 20.64314 49.83113 -0.2242 6.82611
April 390.00000 20.54824 52.23899 -0.2261 6.95653
May 403.00000 20.54053 52.46926 -1.3640 43.93548
June 390.00000 20.56310 52.42103 -1.3510 43.25610
July 403.00000 20.44440 52.71974 -1.3855 45.05449
August 403.00000 20.56596 52.40644 -1.3519 43.29144
September 390.00000 20.49566 52.47139 -1.3807 44.79775
October 403.00000 20.51506 52.43144 -0.2293 6.93858
November 390.00000 20.61088 51.14365 -0.2187 6.85879
December 403.00000 20.63347 50.62809 -0.2288 7.01360
           
Annual Sum or Average 4745.00000 20.57569 51.37862 -0.7054 22.51740
Minimum of Months 364.00000 20.44440 48.66751 -1.3855 6.82611
Maximum of Months 403.00000 20.70250 52.71974 -0.2187 45.05449



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 RECEPTION PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.78725 47.26568 0.20996 6.22818
February 364.00000 22.73229 47.40461 0.19931 6.15608
March 403.00000 22.64256 48.62353 0.19422 6.05293
April 390.00000 22.67271 50.07908 0.20325 6.06990
May 403.00000 22.63136 50.49325 -0.7926 18.59162
June 390.00000 22.58092 50.61427 -0.8025 18.88204
July 403.00000 22.67780 49.91560 -0.7840 18.30672
August 403.00000 22.60433 50.49684 -0.7861 18.38256
September 390.00000 22.69243 49.76630 -0.7668 17.82620
October 403.00000 22.76035 49.64129 0.23242 6.39517
November 390.00000 22.79038 49.02645 0.23423 6.42037
December 403.00000 22.81161 48.53178 0.22761 6.44980
           
Annual Sum or Average 4745.00000 22.69855 49.33129 -0.2050 11.34505
Minimum of Months 364.00000 22.58092 47.26568 -0.8025 6.05293
Maximum of Months 403.00000 22.81161 50.61427 0.23423 18.88204



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 RECOVERY ROOM PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.40299 48.00075 -0.0208 6.06452
February 364.00000 21.24950 48.64605 -0.0575 6.04550
March 403.00000 21.00639 50.24300 -0.1145 5.90234
April 390.00000 20.82176 52.75578 -0.1626 6.07703
May 403.00000 20.75120 53.29754 -1.3253 41.89225
June 390.00000 20.74680 53.31910 -1.3269 41.95990
July 403.00000 20.69405 53.23442 -1.3379 42.55128
August 403.00000 20.83393 53.04887 -1.2750 39.39834
September 390.00000 20.92605 52.45485 -1.2270 37.17880
October 403.00000 21.14236 51.88867 -0.0524 5.75226
November 390.00000 21.28435 50.56089 -0.0228 5.84449
December 403.00000 21.31599 49.95760 -0.0251 5.95694
           
Annual Sum or Average 4745.00000 21.01345 51.46467 -0.5821 20.47709
Minimum of Months 364.00000 20.69405 48.00075 -1.3379 5.75226
Maximum of Months 403.00000 21.40299 53.31910 -0.0208 42.55128



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 SCHEDULING PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.64243 44.11767 0.08800 5.36984
February 318.00000 22.57611 44.61942 0.07624 5.39004
March 349.00000 22.51537 46.02656 0.07408 5.31449
April 340.00000 22.50750 47.76667 0.07531 5.23557
May 351.00000 22.46036 48.56849 -0.9682 24.93709
June 338.00000 22.41706 48.35771 -0.9814 25.45558
July 353.00000 22.48389 47.87950 -0.9688 24.94694
August 349.00000 22.46803 48.17031 -0.9561 24.47269
September 340.00000 22.53815 47.56138 -0.9409 23.90359
October 353.00000 22.61627 47.67437 0.10992 5.42623
November 342.00000 22.64395 46.54925 0.11247 5.43742
December 353.00000 22.68955 46.08757 0.11509 5.57762
           
Annual Sum or Average 4139.00000 22.54681 46.95832 -0.3485 13.48629
Minimum of Months 318.00000 22.41706 44.11767 -0.9814 5.23557
Maximum of Months 353.00000 22.68955 48.56849 0.11509 25.45558



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 SOIL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 20.84080 48.15596 -0.2308 6.80700
February 364.00000 20.78013 48.43816 -0.2446 6.92189
March 403.00000 20.75349 49.33393 -0.2413 6.73877
April 390.00000 20.62022 51.82511 -0.2757 7.31855
May 403.00000 20.56544 52.33139 -1.4857 50.02200
June 390.00000 20.58386 52.36609 -1.4893 50.18179
July 403.00000 20.43914 52.75107 -1.5429 52.94566
August 403.00000 20.58909 52.36898 -1.4900 50.22686
September 390.00000 20.49744 52.48866 -1.5234 51.93435
October 403.00000 20.52374 52.34433 -0.3138 7.83104
November 390.00000 20.69370 50.88203 -0.2655 7.18666
December 403.00000 20.74266 50.00202 -0.2439 6.95238
           
Annual Sum or Average 4745.00000 20.63503 51.12067 -0.7821 25.53339
Minimum of Months 364.00000 20.43914 48.15596 -1.5429 6.73877
Maximum of Months 403.00000 20.84080 52.75107 -0.2308 52.94566



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 SOIL HOLD PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 20.75473 48.28368 -0.2991 7.45445
February 364.00000 20.73588 48.43775 -0.2944 7.42392
March 403.00000 20.76393 49.19856 -0.2698 6.94599
April 390.00000 20.70414 51.46087 -0.2630 6.95935
May 403.00000 20.68992 51.83325 -1.4329 47.37193
June 390.00000 20.70636 51.87023 -1.4277 47.08457
July 403.00000 20.61140 52.09397 -1.4576 48.66589
August 403.00000 20.70234 51.90211 -1.4324 47.32025
September 390.00000 20.62997 51.96552 -1.4607 48.81645
October 403.00000 20.63315 51.90062 -0.2857 7.24869
November 390.00000 20.73642 50.64197 -0.2727 7.08792
December 403.00000 20.71477 49.98169 -0.2895 7.29426
           
Annual Sum or Average 4745.00000 20.69833 50.80938 -0.7683 24.24017
Minimum of Months 364.00000 20.61140 48.28368 -1.4607 6.94599
Maximum of Months 403.00000 20.76393 52.09397 -0.2630 48.81645



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 SOIL WORK PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 20.79491 48.40481 -0.2518 7.00361
February 364.00000 20.73636 48.67976 -0.2657 7.15129
March 403.00000 20.72321 49.55788 -0.2598 6.94224
April 390.00000 20.58972 52.04326 -0.2946 7.55094
May 403.00000 20.54477 52.52591 -1.5103 51.27897
June 390.00000 20.56948 52.54491 -1.5115 51.32112
July 403.00000 20.42328 52.92187 -1.5648 54.06189
August 403.00000 20.57572 52.54574 -1.5104 51.27937
September 390.00000 20.48440 52.65306 -1.5421 52.89083
October 403.00000 20.50837 52.51562 -0.3264 8.00012
November 390.00000 20.66362 51.09406 -0.2817 7.37090
December 403.00000 20.70173 50.24357 -0.2634 7.14479
           
Annual Sum or Average 4745.00000 20.60895 51.32402 -0.8017 26.11312
Minimum of Months 364.00000 20.42328 48.40481 -1.5648 6.94224
Maximum of Months 403.00000 20.79491 52.92187 -0.2518 54.06189



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 STEP DOWN PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.58936 48.36464 0.00371 6.06767
February 364.00000 21.50400 48.83065 -0.0131 6.06829
March 403.00000 21.32997 50.38752 -0.0502 5.85436
April 390.00000 21.20901 52.58432 -0.0705 5.72524
May 403.00000 21.13845 53.20055 -1.1850 35.15718
June 390.00000 21.10125 53.30328 -1.1939 35.54999
July 403.00000 21.17788 52.72877 -1.1630 34.19254
August 403.00000 21.32858 52.63388 -1.1007 31.50703
September 390.00000 21.43249 51.89468 -1.0562 29.62987
October 403.00000 21.58038 51.54433 0.05070 5.80688
November 390.00000 21.60988 50.50083 0.04528 5.90376
December 403.00000 21.58593 50.18450 0.02179 6.04980
           
Annual Sum or Average 4745.00000 21.38175 51.35924 -0.4787 17.36405
Minimum of Months 364.00000 21.10125 48.36464 -1.1939 5.72524
Maximum of Months 403.00000 21.60988 53.30328 0.05070 35.54999



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 CONFERENCE PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 312.00000 22.60339 55.16214 0.21510 6.86731
February 279.00000 22.62411 55.91917 0.23266 7.30799
March 306.00000 22.58657 58.40545 0.24761 7.02194
April 295.00000 22.69057 60.29910 0.28905 7.12486
May 309.00000 22.68648 61.92567 -0.6585 14.70532
June 296.00000 22.67522 61.37584 -0.6453 14.36063
July 308.00000 22.84828 59.61373 -0.6010 13.57794
August 306.00000 22.71141 61.19707 -0.6256 14.07542
September 295.00000 22.84582 59.64362 -0.5887 13.43820
October 312.00000 22.91592 59.99287 0.37522 8.59210
November 306.00000 22.76245 58.74671 0.31014 7.74182
December 308.00000 22.67682 59.28807 0.25476 7.40494
           
Annual Sum or Average 3632.00000 22.71960 59.30942 -0.0995 10.19014
Minimum of Months 279.00000 22.58657 55.16214 -0.6585 6.86731
Maximum of Months 312.00000 22.91592 61.92567 0.37522 14.70532



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 DICTATION PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.46979 51.55487 0.07224 5.26915
February 318.00000 22.45218 51.78781 0.06870 5.36866
March 349.00000 22.45603 53.39781 0.08576 5.33900
April 340.00000 22.38975 56.75620 0.08158 5.24088
May 351.00000 22.29221 58.02888 -1.0001 26.27236
June 338.00000 22.25602 58.07112 -1.0129 26.79991
July 353.00000 22.23359 57.42020 -1.0321 27.62547
August 349.00000 22.26007 57.91485 -1.0121 26.75730
September 340.00000 22.25408 57.49474 -1.0211 27.16007
October 353.00000 22.33473 56.86487 0.06419 5.16991
November 342.00000 22.49243 55.75873 0.09958 5.36663
December 353.00000 22.48320 53.89866 0.08829 5.31760
           
Annual Sum or Average 4139.00000 22.36413 55.76114 -0.3782 14.34028
Minimum of Months 318.00000 22.23359 51.55487 -1.0321 5.16991
Maximum of Months 353.00000 22.49243 58.07112 0.09958 27.62547



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 1 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.07841 54.51161 0.08821 5.74113
February 364.00000 22.22872 54.64324 0.13798 6.46550
March 403.00000 22.28512 56.54418 0.17672 6.49426
April 390.00000 22.42029 58.97132 0.23734 6.67620
May 403.00000 22.37005 60.36578 -0.7474 17.45441
June 390.00000 22.31947 60.08640 -0.7646 17.87000
July 403.00000 22.42139 58.59667 -0.7323 17.08848
August 403.00000 22.36028 59.76517 -0.7399 17.29712
September 390.00000 22.43451 58.78849 -0.7292 16.97870
October 403.00000 22.47384 58.86707 0.26321 6.83007
November 390.00000 22.32700 57.87430 0.20307 6.27714
December 403.00000 22.24051 57.62257 0.15140 6.24206
           
Annual Sum or Average 4745.00000 22.33030 58.07148 -0.2068 10.97717
Minimum of Months 364.00000 22.07841 54.51161 -0.7646 5.74113
Maximum of Months 403.00000 22.47384 60.36578 0.26321 17.87000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 2 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.71068 55.18946 0.03197 5.41201
February 364.00000 21.74569 55.57051 0.04021 5.70395
March 403.00000 21.72562 57.67555 0.05176 5.54861
April 390.00000 21.54753 61.34594 0.02696 5.34313
May 403.00000 21.36983 62.95136 -1.1007 30.97637
June 390.00000 21.27568 62.99072 -1.1318 32.33724
July 403.00000 21.15297 62.26338 -1.1730 34.23073
August 403.00000 21.27934 62.74345 -1.1240 31.94179
September 390.00000 21.33069 61.92019 -1.1094 31.27438
October 403.00000 21.48314 61.18650 0.02442 5.23363
November 390.00000 21.73256 59.35811 0.06855 5.41946
December 403.00000 21.74824 58.00585 0.05674 5.54747
           
Annual Sum or Average 4745.00000 21.50695 60.12303 -0.4478 16.64807
Minimum of Months 364.00000 21.15297 55.18946 -1.1730 5.23363
Maximum of Months 403.00000 21.74824 62.99072 0.06855 34.23073



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 3 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.57479 55.62550 0.00077 5.39091
February 364.00000 21.59605 56.06721 0.00525 5.60309
March 403.00000 21.54944 58.28037 0.00886 5.44292
April 390.00000 21.33935 62.08176 -0.0265 5.34489
May 403.00000 21.16926 63.69476 -1.1749 34.42061
June 390.00000 21.10182 63.63677 -1.1965 35.40278
July 403.00000 20.98950 62.87785 -1.2379 37.39911
August 403.00000 21.10663 63.38787 -1.1882 34.97283
September 390.00000 21.15249 62.56778 -1.1742 34.30852
October 403.00000 21.29392 61.86756 -0.0226 5.23715
November 390.00000 21.56229 59.93486 0.02780 5.33173
December 403.00000 21.59882 58.51343 0.02151 5.44692
           
Annual Sum or Average 4745.00000 21.33458 60.73475 -0.4994 17.93465
Minimum of Months 364.00000 20.98950 55.62550 -1.2379 5.23715
Maximum of Months 403.00000 21.59882 63.69476 0.02780 37.39911



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 4 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.29463 53.37447 0.13316 6.02525
February 364.00000 22.31504 54.02662 0.14031 6.24337
March 403.00000 22.22974 56.40263 0.13146 5.90056
April 390.00000 22.20569 59.47944 0.13567 5.60705
May 403.00000 22.17023 60.80713 -0.9018 22.46729
June 390.00000 22.15724 60.42205 -0.9020 22.46643
July 403.00000 22.18612 59.19175 -0.8985 22.36756
August 403.00000 22.19393 60.07804 -0.8798 21.70605
September 390.00000 22.30667 58.82705 -0.8369 20.25392
October 403.00000 22.44416 58.38555 0.21869 6.31583
November 390.00000 22.43221 57.05415 0.20279 6.27411
December 403.00000 22.36275 56.56638 0.16768 6.31351
           
Annual Sum or Average 4745.00000 22.27453 57.90469 -0.2767 12.70366
Minimum of Months 364.00000 22.15724 53.37447 -0.9020 5.60705
Maximum of Months 403.00000 22.44416 60.80713 0.21869 22.46729



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 5 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.53539 55.61674 -0.0174 5.78806
February 364.00000 21.72298 55.68500 0.04050 6.09853
March 403.00000 21.92668 57.09087 0.12020 6.09502
April 390.00000 22.13432 59.29866 0.21137 6.36624
May 403.00000 22.16235 60.21400 -0.7506 17.48738
June 390.00000 22.19827 59.69656 -0.7293 16.71826
July 403.00000 22.26705 58.37677 -0.7074 16.27207
August 403.00000 22.12483 59.83317 -0.7620 17.90843
September 390.00000 22.14877 59.08393 -0.7643 17.94013
October 403.00000 22.05348 59.43569 0.19373 6.12441
November 390.00000 21.86557 58.83883 0.11299 5.77144
December 403.00000 21.53472 59.05037 -0.0022 5.79331
           
Annual Sum or Average 4745.00000 21.97367 58.53388 -0.2565 10.72375
Minimum of Months 364.00000 21.53472 55.61674 -0.7643 5.77144
Maximum of Months 403.00000 22.26705 60.21400 0.21137 17.94013



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 6 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.16440 56.86464 -0.1429 5.85860
February 364.00000 21.30472 57.04771 -0.0971 6.10302
March 403.00000 21.46764 58.66914 -0.0332 5.67728
April 390.00000 21.61316 61.27718 0.03415 5.34730
May 403.00000 21.76920 61.81441 -0.9631 25.02887
June 390.00000 21.79446 61.34345 -0.9463 24.30709
July 403.00000 21.70936 60.45573 -0.9733 25.35605
August 403.00000 21.65895 61.61816 -0.9939 26.23022
September 390.00000 21.58181 61.19084 -1.0297 27.71081
October 403.00000 21.45602 61.57325 0.00513 5.22257
November 390.00000 21.39984 60.44613 -0.0325 5.36955
December 403.00000 21.27440 59.93942 -0.0921 5.70312
           
Annual Sum or Average 4745.00000 21.51701 60.20285 -0.4409 14.03919
Minimum of Months 364.00000 21.16440 56.86464 -1.0297 5.22257
Maximum of Months 403.00000 21.79446 61.81441 0.03415 27.71081



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 7 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.26919 56.56602 -0.0920 5.64805
February 364.00000 21.36184 56.74404 -0.0643 5.86966
March 403.00000 21.42887 58.59426 -0.0236 5.54507
April 390.00000 21.38827 61.86841 -0.0087 5.39229
May 403.00000 21.34935 62.98014 -1.0947 30.71940
June 390.00000 21.29364 62.89163 -1.1098 31.33502
July 403.00000 21.15813 62.21854 -1.1568 33.48429
August 403.00000 21.21004 62.95592 -1.1396 32.68436
September 390.00000 21.16168 62.50651 -1.1674 34.01519
October 403.00000 21.18520 62.21036 -0.0565 5.34670
November 390.00000 21.35429 60.62308 -0.0329 5.39636
December 403.00000 21.33204 59.34713 -0.0581 5.61250
           
Annual Sum or Average 4745.00000 21.29037 60.81251 -0.5031 16.81854
Minimum of Months 364.00000 21.15813 56.56602 -1.1674 5.34670
Maximum of Months 403.00000 21.42887 62.98014 -0.0087 34.01519



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 8 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.33373 56.31049 -0.0844 5.61855
February 364.00000 21.48193 56.46082 -0.0395 5.98670
March 403.00000 21.63270 58.10588 0.01954 5.72797
April 390.00000 21.73805 60.84485 0.07332 5.48137
May 403.00000 21.87037 61.45605 -0.9161 23.22399
June 390.00000 21.86427 61.10369 -0.9114 22.99098
July 403.00000 21.76218 60.28128 -0.9448 24.24556
August 403.00000 21.73128 61.36972 -0.9584 24.82409
September 390.00000 21.65046 60.95962 -0.9955 26.30773
October 403.00000 21.55691 61.22312 0.03824 5.27656
November 390.00000 21.56219 59.90843 0.01810 5.37751
December 403.00000 21.44606 59.33608 -0.0344 5.64863
           
Annual Sum or Average 4745.00000 21.63637 59.79716 -0.3969 13.43529
Minimum of Months 364.00000 21.33373 56.31049 -0.9955 5.27656
Maximum of Months 403.00000 21.87037 61.45605 0.07332 26.30773



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 9 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.35752 56.15488 -0.0730 5.57080
February 364.00000 21.44224 56.35271 -0.0482 5.84797
March 403.00000 21.51257 58.17071 -0.0080 5.56846
April 390.00000 21.47837 61.42681 0.00782 5.37547
May 403.00000 21.43484 62.53657 -1.0742 29.78162
June 390.00000 21.37520 62.46082 -1.0909 30.44592
July 403.00000 21.24881 61.76597 -1.1340 32.38941
August 403.00000 21.29254 62.51603 -1.1192 31.72185
September 390.00000 21.25310 62.04833 -1.1426 32.82495
October 403.00000 21.27875 61.73941 -0.0372 5.29756
November 390.00000 21.43972 60.20010 -0.0157 5.39071
December 403.00000 21.42003 58.91779 -0.0394 5.59696
           
Annual Sum or Average 4745.00000 21.37718 60.37753 -0.4839 16.37968
Minimum of Months 364.00000 21.24881 56.15488 -1.1426 5.29756
Maximum of Months 403.00000 21.51257 62.53657 0.00782 32.82495



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 LOUNGE PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.59972 52.19350 0.12143 5.54730
February 364.00000 22.58713 52.34793 0.11987 5.65632
March 403.00000 22.56335 53.93907 0.13426 5.67516
April 390.00000 22.54935 57.15599 0.14369 5.59098
May 403.00000 22.47520 58.17785 -0.9050 22.50769
June 390.00000 22.43896 58.13426 -0.9161 22.90068
July 403.00000 22.47232 57.10534 -0.9212 23.09995
August 403.00000 22.43684 57.94731 -0.9174 22.96575
September 390.00000 22.45998 57.39978 -0.9207 23.08515
October 403.00000 22.52624 56.84872 0.13118 5.49111
November 390.00000 22.64309 56.15612 0.15652 5.78806
December 403.00000 22.61642 54.36092 0.13725 5.64942
           
Annual Sum or Average 4745.00000 22.53034 55.99693 -0.3056 12.87219
Minimum of Months 364.00000 22.43684 52.19350 -0.9212 5.49111
Maximum of Months 403.00000 22.64309 58.17785 0.15652 23.09995



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 NURSE STATION 1 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.60260 52.54785 0.13668 5.62981
February 364.00000 22.60158 52.63483 0.13916 5.80345
March 403.00000 22.59070 54.16145 0.15906 5.86379
April 390.00000 22.59746 57.26238 0.17716 5.84988
May 403.00000 22.54217 58.16303 -0.8468 20.41361
June 390.00000 22.49884 58.12709 -0.8587 20.79662
July 403.00000 22.55197 57.02203 -0.8574 20.76782
August 403.00000 22.48999 57.98244 -0.8638 20.99234
September 390.00000 22.52155 57.40586 -0.8668 21.09483
October 403.00000 22.57321 56.94033 0.16447 5.71978
November 390.00000 22.67034 56.38545 0.18245 5.98070
December 403.00000 22.63817 54.62610 0.15841 5.79292
           
Annual Sum or Average 4745.00000 22.57300 56.12038 -0.2672 12.09518
Minimum of Months 364.00000 22.48999 52.54785 -0.8668 5.62981
Maximum of Months 403.00000 22.67034 58.16303 0.18245 21.09483



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 NURSE STATION 2 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.65830 52.31677 0.15869 5.81580
February 364.00000 22.65302 52.41957 0.16028 6.00444
March 403.00000 22.63252 53.96388 0.17854 6.07232
April 390.00000 22.64352 57.06501 0.19711 6.05534
May 403.00000 22.58907 57.94722 -0.8169 19.44239
June 390.00000 22.53165 57.95815 -0.8344 19.97446
July 403.00000 22.59342 56.83008 -0.8313 19.88998
August 403.00000 22.52251 57.81404 -0.8403 20.19609
September 390.00000 22.55998 57.22823 -0.8423 20.25718
October 403.00000 22.61652 56.74470 0.18310 5.88784
November 390.00000 22.72558 56.14544 0.20471 6.23119
December 403.00000 22.70166 54.36218 0.18254 6.04312
           
Annual Sum or Average 4745.00000 22.61874 55.91506 -0.2442 11.85601
Minimum of Months 364.00000 22.52251 52.31677 -0.8423 5.81580
Maximum of Months 403.00000 22.72558 57.95815 0.20471 20.25718



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 OFFICE PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.32686 52.39068 0.08194 5.75860
February 318.00000 22.38241 53.00944 0.11715 6.05286
March 349.00000 22.48893 54.81229 0.18013 6.28470
April 340.00000 22.72701 56.71496 0.27485 7.03578
May 351.00000 22.74268 57.94254 -0.6600 14.92818
June 338.00000 22.75980 57.29487 -0.6370 14.44081
July 353.00000 22.98868 55.62456 -0.5745 13.47355
August 349.00000 22.72089 57.33449 -0.6600 15.09177
September 340.00000 22.83825 56.32354 -0.6395 14.62414
October 353.00000 22.77516 56.88826 0.28654 7.13822
November 342.00000 22.53427 56.07211 0.19148 6.19613
December 353.00000 22.36381 56.13422 0.10773 5.85700
           
Annual Sum or Average 4139.00000 22.63848 55.89171 -0.1620 9.75252
Minimum of Months 318.00000 22.32686 52.39068 -0.6600 5.75860
Maximum of Months 353.00000 22.98868 57.94254 0.28654 15.09177



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 RECEPTION PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.70440 54.07785 0.24374 6.63026
February 364.00000 22.72891 54.39080 0.26029 7.26186
March 403.00000 22.71894 56.37932 0.28246 7.32356
April 390.00000 22.80468 58.71583 0.32380 7.63336
May 403.00000 22.76045 59.80207 -0.6281 14.08331
June 390.00000 22.70005 59.58488 -0.6402 14.29975
July 403.00000 22.85812 57.91680 -0.5998 13.50842
August 403.00000 22.72129 59.31125 -0.6236 14.00657
September 390.00000 22.85521 58.11158 -0.5909 13.35957
October 403.00000 22.91168 58.01822 0.36590 8.37965
November 390.00000 22.83064 57.43197 0.32596 7.65431
December 403.00000 22.82408 56.68272 0.29439 7.47546
           
Annual Sum or Average 4745.00000 22.78519 57.55097 -0.0843 10.15169
Minimum of Months 364.00000 22.70005 54.07785 -0.6402 6.63026
Maximum of Months 403.00000 22.91168 59.80207 0.36590 14.29975



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 SCHEDULING 1 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.63925 51.12271 0.13944 5.62317
February 318.00000 22.63420 51.32571 0.14006 5.72005
March 349.00000 22.60429 52.93491 0.15383 5.76918
April 340.00000 22.59409 56.09024 0.16397 5.71262
May 351.00000 22.51550 57.18380 -0.8741 21.33435
June 338.00000 22.47426 57.19511 -0.8863 21.75647
July 353.00000 22.51235 56.32033 -0.8889 21.85580
August 349.00000 22.47099 57.05313 -0.8884 21.84493
September 340.00000 22.49376 56.56326 -0.8925 21.99400
October 353.00000 22.55431 56.05115 0.14799 5.57570
November 342.00000 22.67847 55.19466 0.17370 5.87144
December 353.00000 22.65965 53.39688 0.15729 5.74602
           
Annual Sum or Average 4139.00000 22.56901 55.05005 -0.2811 12.42408
Minimum of Months 318.00000 22.47099 51.12271 -0.8925 5.57570
Maximum of Months 353.00000 22.67847 57.19511 0.17370 21.99400



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 SCHEDULING 2 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.70496 50.90235 0.16331 5.83192
February 318.00000 22.69579 51.11305 0.16310 5.96168
March 349.00000 22.65770 52.74036 0.17550 6.00494
April 340.00000 22.65405 55.87673 0.18823 5.94215
May 351.00000 22.57078 56.96842 -0.8407 20.18872
June 338.00000 22.51305 57.03447 -0.8592 20.79725
July 353.00000 22.56403 56.11889 -0.8578 20.75567
August 349.00000 22.51312 56.87569 -0.8592 20.80989
September 340.00000 22.55289 56.33422 -0.8580 20.76753
October 353.00000 22.63009 55.76899 0.17720 5.82174
November 342.00000 22.74754 54.94406 0.20028 6.14854
December 353.00000 22.73816 53.12583 0.18419 6.02384
           
Annual Sum or Average 4139.00000 22.62831 54.83075 -0.2535 12.10942
Minimum of Months 318.00000 22.51305 50.90235 -0.8592 5.82174
Maximum of Months 353.00000 22.74754 57.03447 0.20028 20.80989



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 WORK PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.65631 51.48520 0.15702 5.75518
February 318.00000 22.66578 51.81368 0.16902 6.14126
March 349.00000 22.69542 53.52502 0.20391 6.33886
April 340.00000 22.75954 56.19114 0.24273 6.50487
May 351.00000 22.74864 57.13446 -0.7238 16.58966
June 338.00000 22.69755 56.98734 -0.7319 16.77306
July 353.00000 22.82468 55.73102 -0.7077 16.15087
August 349.00000 22.68030 56.89136 -0.7406 17.04797
September 340.00000 22.76031 56.13412 -0.7332 16.83900
October 353.00000 22.79071 55.98771 0.24902 6.58674
November 342.00000 22.78667 55.22150 0.23195 6.43360
December 353.00000 22.75074 53.95330 0.19908 6.18283
           
Annual Sum or Average 4139.00000 22.73523 55.10047 -0.1833 10.62694
Minimum of Months 318.00000 22.65631 51.48520 -0.7406 5.75518
Maximum of Months 353.00000 22.82468 57.13446 0.24902 17.04797



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 X-RAY PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 23.03987 43.93680 0.35780 8.23131
February 364.00000 23.03517 44.42556 0.36031 8.30606
March 403.00000 22.91660 45.20077 0.35556 8.21186
April 390.00000 23.03989 47.41170 0.37870 8.59387
May 403.00000 22.99027 50.18583 -0.5261 11.87979
June 390.00000 22.91900 52.47687 -0.5259 11.87388
July 403.00000 23.08911 52.22369 -0.5032 11.45308
August 403.00000 22.90705 53.01744 -0.5244 11.83649
September 390.00000 23.02685 52.05950 -0.5154 11.70365
October 403.00000 23.07294 49.85085 0.39408 8.83415
November 390.00000 23.07671 48.26272 0.39319 8.84914
December 403.00000 23.06807 44.99499 0.36729 8.42393
           
Annual Sum or Average 4745.00000 23.01496 48.69030 -0.0012 9.85801
Minimum of Months 364.00000 22.90705 43.93680 -0.5261 8.21186
Maximum of Months 403.00000 23.08911 53.01744 0.39408 11.87979



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 DRESSING ROOM PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.16368 50.10264 -0.0139 5.22558
February 318.00000 22.16954 50.85851 -0.0042 5.27301
March 349.00000 22.18321 52.19855 0.01562 5.23138
April 340.00000 22.18751 55.01221 0.03324 5.28878
May 351.00000 22.16971 56.90441 -1.0212 27.40886
June 338.00000 22.21012 57.17267 -0.9985 26.41639
July 353.00000 22.25844 56.58161 -0.9899 26.14234
August 349.00000 22.19510 57.43523 -1.0041 26.63604
September 340.00000 22.18252 57.08479 -1.0184 27.29173
October 353.00000 22.12333 56.83203 0.02439 5.27209
November 342.00000 22.15257 55.12490 0.01710 5.23232
December 353.00000 22.14428 52.98288 -0.0012 5.18894
           
Annual Sum or Average 4139.00000 22.17830 54.87386 -0.4150 14.24988
Minimum of Months 318.00000 22.12333 50.10264 -1.0212 5.18894
Maximum of Months 353.00000 22.25844 57.43523 0.03324 27.40886



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 HUMID PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.28253 49.75040 0.03390 5.21121
February 318.00000 22.28763 50.50058 0.04432 5.28613
March 349.00000 22.29202 51.82940 0.06389 5.28571
April 340.00000 22.32203 54.54004 0.08686 5.39132
May 351.00000 22.30159 56.37174 -0.9446 24.20992
June 338.00000 22.33277 56.65366 -0.9233 23.36590
July 353.00000 22.40780 55.98160 -0.9084 22.91082
August 349.00000 22.31689 56.91405 -0.9291 23.57305
September 340.00000 22.32142 56.51560 -0.9402 24.05618
October 353.00000 22.26658 56.26505 0.07974 5.34642
November 342.00000 22.28137 54.68389 0.06877 5.27911
December 353.00000 22.27336 52.55749 0.04892 5.20348
           
Annual Sum or Average 4139.00000 22.30722 54.39590 -0.3531 12.95406
Minimum of Months 318.00000 22.26658 49.75040 -0.9446 5.20348
Maximum of Months 353.00000 22.40780 56.91405 0.08686 24.20992



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 LOCKER PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.44213 50.57109 0.09098 5.33660
February 364.00000 22.44348 51.18874 0.10434 5.54334
March 403.00000 22.47954 52.34018 0.13617 5.59318
April 390.00000 22.57029 54.91588 0.18051 5.90403
May 403.00000 22.57929 56.34761 -0.7979 18.89106
June 390.00000 22.57395 56.63141 -0.7863 18.57313
July 403.00000 22.70854 55.68590 -0.7532 17.84890
August 403.00000 22.55011 56.88612 -0.7990 18.96240
September 390.00000 22.58764 56.30163 -0.8035 19.17745
October 403.00000 22.54627 56.09898 0.17673 5.85699
November 390.00000 22.50762 55.06131 0.15042 5.60995
December 403.00000 22.48033 52.98332 0.11767 5.43706
           
Annual Sum or Average 4745.00000 22.53966 54.59973 -0.2508 11.09277
Minimum of Months 364.00000 22.44213 50.57109 -0.8035 5.33660
Maximum of Months 403.00000 22.70854 56.88612 0.18051 19.17745



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 LOUNGE PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.53050 50.62127 0.14362 5.68568
February 364.00000 22.52836 51.28181 0.16322 6.03962
March 403.00000 22.57963 52.45207 0.20292 6.23188
April 390.00000 22.71848 54.82981 0.26768 6.91495
May 403.00000 22.75252 56.25319 -0.6523 14.88577
June 390.00000 22.73576 56.47083 -0.6358 14.49888
July 403.00000 22.91644 55.35967 -0.5866 13.80922
August 403.00000 22.70523 56.74988 -0.6545 14.97673
September 390.00000 22.77777 56.04411 -0.6523 15.04145
October 403.00000 22.73454 55.96338 0.27611 7.00538
November 390.00000 22.62458 55.01196 0.22420 6.31297
December 403.00000 22.59468 53.11221 0.17890 5.96251
           
Annual Sum or Average 4745.00000 22.68414 54.52727 -0.1456 9.80118
Minimum of Months 364.00000 22.52836 50.62127 -0.6545 5.68568
Maximum of Months 403.00000 22.91644 56.74988 0.27611 15.04145



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 OFFICE PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.31943 50.11558 0.06449 5.40989
February 318.00000 22.35375 50.77801 0.09368 5.79079
March 349.00000 22.48314 51.85584 0.15001 5.85089
April 340.00000 22.65362 54.02966 0.22351 6.43985
May 351.00000 22.73241 55.60757 -0.6979 16.07789
June 338.00000 22.73040 55.84343 -0.6772 15.55355
July 353.00000 22.93181 54.71411 -0.6205 14.61952
August 349.00000 22.69497 56.16582 -0.6967 16.09804
September 340.00000 22.76090 55.55776 -0.6959 16.19217
October 353.00000 22.67745 55.54069 0.23605 6.50893
November 342.00000 22.49439 54.48344 0.16600 5.87041
December 353.00000 22.42671 52.75777 0.11258 5.57839
           
Annual Sum or Average 4139.00000 22.60620 53.96656 -0.1962 10.01253
Minimum of Months 318.00000 22.31943 50.11558 -0.6979 5.40989
Maximum of Months 353.00000 22.93181 56.16582 0.23605 16.19217



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 1 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.75412 53.25350 0.05912 6.76783
February 364.00000 21.79627 53.95013 0.08328 6.94762
March 403.00000 21.80680 55.46351 0.09636 6.58030
April 390.00000 21.88049 58.25147 0.14095 6.61950
May 403.00000 21.94555 59.97414 -0.8359 21.18980
June 390.00000 22.02033 60.01443 -0.7937 19.53475
July 403.00000 22.10503 59.09062 -0.7587 18.80131
August 403.00000 22.01517 60.17474 -0.7877 19.64304
September 390.00000 22.07532 59.28985 -0.7603 19.12749
October 403.00000 22.05703 58.95425 0.21918 7.20789
November 390.00000 21.89608 57.80153 0.15128 6.89498
December 403.00000 21.79219 56.07503 0.08346 6.78311
           
Annual Sum or Average 4745.00000 21.92935 57.70927 -0.2608 12.20824
Minimum of Months 364.00000 21.75412 53.25350 -0.8359 6.58030
Maximum of Months 403.00000 22.10503 60.17474 0.21918 21.18980



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 2 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.52640 54.80001 -0.0630 5.96485
February 364.00000 21.54534 55.44060 -0.0490 6.05652
March 403.00000 21.63791 56.76661 -0.0109 5.84565
April 390.00000 21.57237 59.86807 -0.0016 5.87970
May 403.00000 21.58559 61.68677 -1.0658 30.12938
June 390.00000 21.65976 61.85848 -1.0320 28.53723
July 403.00000 21.61031 61.33560 -1.0473 29.21314
August 403.00000 21.64653 62.11647 -1.0383 28.80994
September 390.00000 21.55877 61.75194 -1.0723 30.29283
October 403.00000 21.48387 61.53096 -0.0141 5.80604
November 390.00000 21.52838 59.88790 -0.0233 5.89744
December 403.00000 21.48394 57.69588 -0.0561 5.88488
           
Annual Sum or Average 4745.00000 21.57003 59.58145 -0.4587 15.75087
Minimum of Months 364.00000 21.48387 54.80001 -1.0723 5.80604
Maximum of Months 403.00000 21.65976 62.11647 -0.0016 30.29283



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 TREATMENT PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.65523 53.42989 -0.0132 5.76124
February 364.00000 21.66701 54.08632 -0.0010 5.86405
March 403.00000 21.74081 55.38727 0.03305 5.72675
April 390.00000 21.67422 58.56512 0.04097 5.77944
May 403.00000 21.68615 60.31663 -1.0040 27.38195
June 390.00000 21.75168 60.48141 -0.9734 26.00392
July 403.00000 21.71038 60.03560 -0.9875 26.60810
August 403.00000 21.74620 60.69765 -0.9765 26.13232
September 390.00000 21.66994 60.38133 -1.0082 27.47110
October 403.00000 21.60831 60.12367 0.03291 5.71153
November 390.00000 21.65624 58.47521 0.02555 5.76312
December 403.00000 21.61831 56.29510 -0.0043 5.68260
           
Annual Sum or Average 4745.00000 21.68210 58.20923 -0.4054 14.54208
Minimum of Months 364.00000 21.60831 53.42989 -1.0082 5.68260
Maximum of Months 403.00000 21.75168 60.69765 0.04097 27.47110



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 WORK PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 353.00000 22.05103 50.78766 0.02763 6.15244
February 318.00000 22.12373 51.54452 0.07276 6.27763
March 349.00000 22.25488 52.60436 0.13774 6.31614
April 340.00000 22.56497 54.48233 0.25791 7.49359
May 351.00000 22.66151 56.17018 -0.6406 15.16832
June 338.00000 22.70942 56.17546 -0.5983 14.10533
July 353.00000 22.96316 54.92064 -0.5149 13.36070
August 349.00000 22.65440 56.57990 -0.6285 15.01268
September 340.00000 22.76901 55.81339 -0.6077 14.78122
October 353.00000 22.61836 56.11113 0.27586 7.43404
November 342.00000 22.25440 55.27531 0.14566 6.22059
December 353.00000 22.07247 54.05415 0.04672 6.06520
           
Annual Sum or Average 4139.00000 22.47622 54.55607 -0.1697 9.87823
Minimum of Months 318.00000 22.05103 50.78766 -0.6406 6.06520
Maximum of Months 353.00000 22.96316 56.57990 0.27586 15.16832



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 STORAGE 1 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 STORAGE 2 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 STORAGE 3 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 UTILITY PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 ELEVATOR HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 JANITOR PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 LOUNGE TOILET PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 MECHANICAL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 MECHANICAL HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 OFFICE HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 OFFICE TOILET PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 STORAGE 1 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 STORAGE 2 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 UNDEVELOPED 1 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 UNDEVELOPED 2 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 UTILITY PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: NE STAIR PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: NW ELEVATOR PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: NW STAIR PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: SW STAIR PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 403.00000 0.00000 0.00000 0.00000 0.00000
February 364.00000 0.00000 0.00000 0.00000 0.00000
March 403.00000 0.00000 0.00000 0.00000 0.00000
April 390.00000 0.00000 0.00000 0.00000 0.00000
May 403.00000 0.00000 0.00000 0.00000 0.00000
June 390.00000 0.00000 0.00000 0.00000 0.00000
July 403.00000 0.00000 0.00000 0.00000 0.00000
August 403.00000 0.00000 0.00000 0.00000 0.00000
September 390.00000 0.00000 0.00000 0.00000 0.00000
October 403.00000 0.00000 0.00000 0.00000 0.00000
November 390.00000 0.00000 0.00000 0.00000 0.00000
December 403.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4745.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 364.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 403.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 ELECTRICAL ROOM PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.78893 42.37142 0.13974 5.78312
February 364.00000 22.71706 42.76921 0.13254 5.74783
March 403.00000 22.67107 43.77616 0.14608 5.80398
April 390.00000 22.78987 45.27014 0.18924 6.13093
May 403.00000 22.76801 45.62774 -0.7820 18.59976
June 390.00000 22.73766 45.47542 -0.7765 18.43085
July 403.00000 22.91162 44.96976 -0.7315 17.29534
August 403.00000 22.72813 45.52156 -0.7749 18.38640
September 390.00000 22.83494 45.04446 -0.7553 17.87300
October 403.00000 22.86076 45.24628 0.21264 6.38088
November 390.00000 22.82269 44.50174 0.18454 6.06490
December 403.00000 22.78209 44.29896 0.14944 5.87437
           
Annual Sum or Average 4745.00000 22.78483 44.58208 -0.2243 11.06238
Minimum of Months 364.00000 22.67107 42.37142 -0.7820 5.74783
Maximum of Months 403.00000 22.91162 45.62774 0.21264 18.59976



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 23.07990 40.52867 0.35210 8.47156
February 364.00000 23.02966 40.68187 0.35305 8.55457
March 403.00000 22.92162 42.11344 0.35286 8.59945
April 390.00000 23.03855 43.04036 0.40324 9.38804
May 403.00000 22.98805 44.04354 -0.4567 11.13494
June 390.00000 22.91628 43.79574 -0.4662 11.16418
July 403.00000 23.08688 43.62274 -0.4003 10.27721
August 403.00000 22.90435 43.59735 -0.4489 10.83406
September 390.00000 23.02462 43.23580 -0.4203 10.51870
October 403.00000 23.07099 43.42551 0.44398 10.14025
November 390.00000 23.07415 42.16858 0.40843 9.33841
December 403.00000 23.10128 42.18950 0.38562 9.19689
           
Annual Sum or Average 4745.00000 23.01968 42.71630 0.04035 9.80847
Minimum of Months 364.00000 22.90435 40.52867 -0.4662 8.47156
Maximum of Months 403.00000 23.10128 44.04354 0.44398 11.16418



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 IT HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.19547 45.37671 -0.0606 5.17213
February 364.00000 22.19330 45.17541 -0.0569 5.22233
March 403.00000 22.25578 45.73741 -0.0300 5.07600
April 390.00000 22.25750 47.45926 -0.0179 5.05881
May 403.00000 22.24025 47.78861 -1.0892 30.09895
June 390.00000 22.23240 47.91799 -1.0899 30.12019
July 403.00000 22.22142 47.86915 -1.1009 30.62311
August 403.00000 22.22470 48.00671 -1.0939 30.30312
September 390.00000 22.19019 47.95835 -1.1125 31.17930
October 403.00000 22.19292 47.93131 -0.0370 5.09757
November 390.00000 22.24794 47.08440 -0.0290 5.08457
December 403.00000 22.21489 46.50448 -0.0452 5.10761
           
Annual Sum or Average 4745.00000 22.22236 47.07714 -0.4828 15.74067
Minimum of Months 364.00000 22.19019 45.17541 -1.1125 5.05881
Maximum of Months 403.00000 22.25750 48.00671 -0.0179 31.17930



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 LOBBY HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.75853 42.90588 0.15999 5.85332
February 364.00000 22.70613 42.98164 0.14944 5.76596
March 403.00000 22.62675 43.83580 0.14689 5.70743
April 390.00000 22.67767 45.52425 0.16509 5.80512
May 403.00000 22.64098 45.84611 -0.8340 20.09618
June 390.00000 22.58561 46.04766 -0.8458 20.43645
July 403.00000 22.68830 45.71570 -0.8221 19.68438
August 403.00000 22.59022 46.03376 -0.8396 20.22769
September 390.00000 22.66464 45.70230 -0.8249 19.79425
October 403.00000 22.72012 45.50223 0.17798 5.91933
November 390.00000 22.76148 44.82035 0.18068 5.97346
December 403.00000 22.76243 44.10574 0.17032 5.93648
           
Annual Sum or Average 4745.00000 22.68181 44.92774 -0.2538 11.80245
Minimum of Months 364.00000 22.58561 42.90588 -0.8458 5.70743
Maximum of Months 403.00000 22.76243 46.04766 0.18068 20.43645



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 LOBBY TOILET PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.02397 46.99129 -0.2030 6.34498
February 364.00000 20.98371 47.30716 -0.2043 6.38333
March 403.00000 20.98045 48.18677 -0.1925 6.12554
April 390.00000 20.96939 50.33351 -0.1686 5.94013
May 403.00000 20.96947 50.60099 -1.2844 39.77641
June 390.00000 20.94754 50.57877 -1.2907 40.04399
July 403.00000 20.97038 50.45806 -1.2710 39.08077
August 403.00000 20.97013 50.49174 -1.2723 39.10430
September 390.00000 20.98782 50.29713 -1.2675 38.93862
October 403.00000 21.01609 50.32778 -0.1444 5.73505
November 390.00000 21.01698 49.31343 -0.1633 5.91519
December 403.00000 21.05210 48.84574 -0.1737 6.13651
           
Annual Sum or Average 4745.00000 20.99084 49.48838 -0.6389 20.04187
Minimum of Months 364.00000 20.94754 46.99129 -1.2907 5.73505
Maximum of Months 403.00000 21.05210 50.60099 -0.1444 40.04399



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 LOCKER ROOM HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.46476 44.33925 0.03624 5.10809
February 364.00000 22.43513 44.31827 0.03023 5.10792
March 403.00000 22.41244 45.11373 0.03655 5.10308
April 390.00000 22.38986 47.03285 0.03488 5.08023
May 403.00000 22.33665 47.50647 -1.0305 27.48501
June 390.00000 22.29849 47.76143 -1.0438 28.05628
July 403.00000 22.29472 47.70644 -1.0552 28.55147
August 403.00000 22.29854 47.81205 -1.0449 28.09723
September 390.00000 22.28589 47.66931 -1.0562 28.60385
October 403.00000 22.32883 47.44033 0.01523 5.04465
November 390.00000 22.43550 46.43980 0.04072 5.09638
December 403.00000 22.45539 45.57364 0.04203 5.11475
           
Annual Sum or Average 4745.00000 22.36933 46.57058 -0.4189 14.76098
Minimum of Months 364.00000 22.28589 44.31827 -1.0562 5.04465
Maximum of Months 403.00000 22.46476 47.81205 0.04203 28.60385



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 MED GAS PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.38117 48.17527 -0.2376 7.21656
February 364.00000 21.66748 48.06323 -0.1428 6.79340
March 403.00000 21.86060 48.87844 -0.0738 6.39903
April 390.00000 22.27447 49.34836 0.07610 6.19389
May 403.00000 22.62542 49.41722 -0.7830 19.80364
June 390.00000 22.70392 48.21018 -0.7265 17.93385
July 403.00000 22.96205 47.03158 -0.6243 16.00590
August 403.00000 22.68894 48.20184 -0.7270 18.10187
September 390.00000 22.83289 47.44243 -0.6908 17.26982
October 403.00000 22.68932 49.02022 0.20398 6.82262
November 390.00000 22.15507 49.17554 0.02739 5.98562
December 403.00000 21.66031 50.61034 -0.1414 6.68467
           
Annual Sum or Average 4745.00000 22.29474 48.63684 -0.3213 11.29801
Minimum of Months 364.00000 21.38117 47.03158 -0.7830 5.98562
Maximum of Months 403.00000 22.96205 50.61034 0.20398 19.80364



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 MRI HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.53779 43.60515 0.06814 5.22171
February 364.00000 22.49150 43.65221 0.05961 5.21883
March 403.00000 22.46678 44.44094 0.06660 5.20929
April 390.00000 22.48144 46.21530 0.07850 5.21624
May 403.00000 22.45915 46.51573 -0.9506 24.21966
June 390.00000 22.42371 46.68832 -0.9583 24.50373
July 403.00000 22.47031 46.50012 -0.9523 24.27205
August 403.00000 22.42611 46.70351 -0.9569 24.45340
September 390.00000 22.45327 46.48395 -0.9562 24.42946
October 403.00000 22.49129 46.32018 0.08147 5.21649
November 390.00000 22.54214 45.53599 0.08827 5.26520
December 403.00000 22.54726 44.81797 0.08037 5.27283
           
Annual Sum or Average 4745.00000 22.48257 45.63282 -0.3568 13.25588
Minimum of Months 364.00000 22.42371 43.60515 -0.9583 5.20929
Maximum of Months 403.00000 22.54726 46.70351 0.08827 24.50373



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 MRI TOILET PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 20.85327 47.59839 -0.2793 7.06118
February 364.00000 20.79484 48.01097 -0.2880 7.22226
March 403.00000 20.81861 48.87530 -0.2764 6.95342
April 390.00000 20.75136 51.19520 -0.2733 6.95916
May 403.00000 20.76763 51.44815 -1.4276 47.09783
June 390.00000 20.78296 51.29042 -1.4177 46.56319
July 403.00000 20.72483 51.40601 -1.4317 47.31429
August 403.00000 20.79935 51.22538 -1.4098 46.14255
September 390.00000 20.75529 51.20021 -1.4245 46.93862
October 403.00000 20.76948 51.29718 -0.2571 6.69988
November 390.00000 20.82898 50.04057 -0.2542 6.69887
December 403.00000 20.84546 49.65460 -0.2616 6.85499
           
Annual Sum or Average 4745.00000 20.79110 50.28152 -0.7529 23.64073
Minimum of Months 364.00000 20.72483 47.59839 -1.4317 6.69887
Maximum of Months 403.00000 20.85327 51.44815 -0.2542 47.31429



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 NURSE HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.38832 44.45905 0.01857 5.06607
February 364.00000 22.32300 44.60284 0.00130 5.09083
March 403.00000 22.30374 45.54932 0.00287 5.04900
April 390.00000 22.21084 47.83466 -0.0203 5.06755
May 403.00000 22.10088 48.67343 -1.1337 32.21208
June 390.00000 22.05274 49.01791 -1.1514 33.07534
July 403.00000 21.98370 49.13079 -1.1813 34.52499
August 403.00000 22.08379 48.91884 -1.1391 32.46881
September 390.00000 22.06577 48.66016 -1.1458 32.80251
October 403.00000 22.17917 48.07441 -0.0268 5.09105
November 390.00000 22.31417 46.80483 0.00890 5.05534
December 403.00000 22.36701 45.79224 0.02012 5.05958
           
Annual Sum or Average 4745.00000 22.19714 47.30670 -0.4818 16.78407
Minimum of Months 364.00000 21.98370 44.45905 -1.1813 5.04900
Maximum of Months 403.00000 22.38832 49.13079 0.02012 34.52499



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 NURSE JANITOR PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.50067 42.78299 0.04264 5.15669
February 364.00000 22.46127 42.85370 0.03370 5.12579
March 403.00000 22.41717 43.64881 0.03321 5.11646
April 390.00000 22.38082 45.68260 0.02736 5.07831
May 403.00000 22.30530 46.19979 -1.0480 28.24065
June 390.00000 22.25987 46.42906 -1.0652 28.99069
July 403.00000 22.24422 46.50450 -1.0795 29.63075
August 403.00000 22.25900 46.45867 -1.0668 29.05829
September 390.00000 22.24251 46.41029 -1.0778 29.55736
October 403.00000 22.29608 46.15592 0.00126 5.03853
November 390.00000 22.43015 45.03165 0.03411 5.10168
December 403.00000 22.47661 44.13584 0.04434 5.15559
           
Annual Sum or Average 4745.00000 22.35558 45.20272 -0.4295 15.16348
Minimum of Months 364.00000 22.24251 42.78299 -1.0795 5.03853
Maximum of Months 403.00000 22.50067 46.50450 0.04434 29.63075



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 NURSE TOILET PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 20.77550 47.11854 -0.3114 7.55144
February 364.00000 20.71939 47.39953 -0.3255 7.75348
March 403.00000 20.72977 48.15511 -0.3186 7.54686
April 390.00000 20.58780 50.76979 -0.3539 8.24262
May 403.00000 20.53451 51.25165 -1.5947 55.65203
June 390.00000 20.55751 51.24144 -1.5986 55.83798
July 403.00000 20.40317 51.77547 -1.6522 58.53989
August 403.00000 20.56639 51.22346 -1.5975 55.80363
September 390.00000 20.46600 51.46244 -1.6288 57.35315
October 403.00000 20.49023 51.31291 -0.3888 8.86235
November 390.00000 20.64856 49.81559 -0.3423 8.04630
December 403.00000 20.69845 48.98147 -0.3205 7.69712
           
Annual Sum or Average 4745.00000 20.59747 50.05546 -0.8726 28.36370
Minimum of Months 364.00000 20.40317 47.11854 -1.6522 7.54686
Maximum of Months 403.00000 20.77550 51.77547 -0.3114 58.53989



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 PRE-OP HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.42242 44.45954 0.02333 5.08363
February 364.00000 22.38200 44.46503 0.01541 5.09656
March 403.00000 22.36657 45.29432 0.02187 5.07205
April 390.00000 22.33151 47.24327 0.01854 5.05222
May 403.00000 22.26533 47.79069 -1.0589 28.72217
June 390.00000 22.22527 48.07969 -1.0737 29.38875
July 403.00000 22.20944 48.04053 -1.0873 30.00871
August 403.00000 22.23625 48.05617 -1.0686 29.15588
September 390.00000 22.21900 47.92344 -1.0809 29.71891
October 403.00000 22.27446 47.62171 0.00188 5.04231
November 390.00000 22.38451 46.58094 0.02765 5.06847
December 403.00000 22.41097 45.72211 0.02864 5.08476
           
Annual Sum or Average 4745.00000 22.31028 46.78460 -0.4387 15.26797
Minimum of Months 364.00000 22.20944 44.45954 -1.0873 5.04231
Maximum of Months 403.00000 22.42242 48.07969 0.02864 30.00871



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 PRE-OP TOILET PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 20.90480 47.47587 -0.2718 6.97295
February 364.00000 20.87029 47.81263 -0.2669 6.96059
March 403.00000 20.87292 48.73537 -0.2645 6.81859
April 390.00000 20.82670 50.98311 -0.2450 6.60844
May 403.00000 20.81087 51.34604 -1.3965 45.47908
June 390.00000 20.81218 51.23113 -1.3952 45.38673
July 403.00000 20.78639 51.23787 -1.3904 45.17367
August 403.00000 20.86485 51.04805 -1.3565 43.39038
September 390.00000 20.83903 50.95589 -1.3692 44.06186
October 403.00000 20.87511 50.98449 -0.2103 6.22391
November 390.00000 20.90391 49.83981 -0.2227 6.38646
December 403.00000 20.91765 49.45437 -0.2478 6.69303
           
Annual Sum or Average 4745.00000 20.85708 50.10355 -0.7225 22.60685
Minimum of Months 364.00000 20.78639 47.47587 -1.3965 6.22391
Maximum of Months 403.00000 20.91765 51.34604 -0.2103 45.47908



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 RECEPTION HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.49211 43.98085 0.04423 5.13988
February 364.00000 22.44524 44.04277 0.03338 5.12624
March 403.00000 22.41110 44.88293 0.03594 5.10576
April 390.00000 22.38357 46.83614 0.03304 5.07604
May 403.00000 22.31924 47.36703 -1.0377 27.78844
June 390.00000 22.27517 47.64978 -1.0541 28.49850
July 403.00000 22.27441 47.58145 -1.0629 28.88207
August 403.00000 22.28493 47.63743 -1.0498 28.30413
September 390.00000 22.28495 47.44893 -1.0553 28.54895
October 403.00000 22.34475 47.14333 0.02085 5.04437
November 390.00000 22.45153 46.12532 0.04610 5.11581
December 403.00000 22.47931 45.25307 0.04916 5.14601
           
Annual Sum or Average 4745.00000 22.37015 46.34036 -0.4191 14.87245
Minimum of Months 364.00000 22.27441 43.98085 -1.0629 5.04437
Maximum of Months 403.00000 22.49211 47.64978 0.04916 28.88207



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 SCRUB PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.29974 44.69149 -0.0240 5.06795
February 364.00000 22.26816 44.64143 -0.0275 5.13000
March 403.00000 22.30469 45.27703 -0.0063 5.05113
April 390.00000 22.33163 46.92801 0.01272 5.03400
May 403.00000 22.31388 47.23429 -1.0434 28.03321
June 390.00000 22.33101 47.20505 -1.0298 27.43853
July 403.00000 22.37350 46.95648 -1.0192 26.99270
August 403.00000 22.33273 47.19035 -1.0258 27.27262
September 390.00000 22.34790 46.98429 -1.0275 27.34538
October 403.00000 22.35041 46.97041 0.02004 5.03791
November 390.00000 22.33942 46.44465 0.00679 5.04937
December 403.00000 22.28635 46.01511 -0.0188 5.05653
           
Annual Sum or Average 4745.00000 22.32358 46.38688 -0.4344 14.43159
Minimum of Months 364.00000 22.26816 44.64143 -1.0434 5.03400
Maximum of Months 403.00000 22.37350 47.23429 0.02004 28.03321



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 STERILE HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.37529 44.56482 0.01052 5.04777
February 364.00000 22.34453 44.55457 0.00450 5.08353
March 403.00000 22.33370 45.40119 0.01204 5.05126
April 390.00000 22.32345 47.24585 0.01583 5.03323
May 403.00000 22.28812 47.65475 -1.0492 28.28610
June 390.00000 22.28463 47.72690 -1.0452 28.10944
July 403.00000 22.30559 47.52135 -1.0439 28.05438
August 403.00000 22.30189 47.63411 -1.0345 27.64606
September 390.00000 22.32117 47.34597 -1.0326 27.56674
October 403.00000 22.35656 47.15689 0.02869 5.04735
November 390.00000 22.38654 46.45234 0.03150 5.05988
December 403.00000 22.37853 45.79809 0.01940 5.05003
           
Annual Sum or Average 4745.00000 22.33329 46.59816 -0.4262 14.64408
Minimum of Months 364.00000 22.28463 44.55457 -1.0492 5.03323
Maximum of Months 403.00000 22.38654 47.72690 0.03150 28.28610



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 STERILE STORAGE PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.45345 43.25769 0.03679 5.10552
February 364.00000 22.42010 43.26865 0.02900 5.08867
March 403.00000 22.38821 44.04737 0.03172 5.08433
April 390.00000 22.35128 46.07804 0.02453 5.05561
May 403.00000 22.28072 46.60946 -1.0514 28.37989
June 390.00000 22.24433 46.82912 -1.0650 28.97887
July 403.00000 22.22847 46.88794 -1.0801 29.65825
August 403.00000 22.24529 46.85839 -1.0658 29.01101
September 390.00000 22.22737 46.79165 -1.0776 29.55068
October 403.00000 22.27543 46.54432 0.00029 5.03365
November 390.00000 22.39672 45.48137 0.03107 5.07294
December 403.00000 22.43497 44.54756 0.03952 5.10586
           
Annual Sum or Average 4745.00000 22.32837 45.61168 -0.4317 15.15331
Minimum of Months 364.00000 22.22737 43.25769 -1.0801 5.03365
Maximum of Months 403.00000 22.45345 46.88794 0.03952 29.65825



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 STORAGE PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.38233 47.82378 -0.2377 6.82330
February 364.00000 21.64751 47.53794 -0.1552 6.55972
March 403.00000 21.91686 47.91343 -0.0648 5.89799
April 390.00000 22.41733 47.95805 0.10415 5.67527
May 403.00000 22.64342 47.79654 -0.7855 19.03195
June 390.00000 22.68553 47.08049 -0.7444 17.77931
July 403.00000 22.91261 46.09813 -0.6622 15.95813
August 403.00000 22.66337 47.16029 -0.7562 18.18947
September 390.00000 22.72298 46.73706 -0.7619 18.37457
October 403.00000 22.54223 47.95768 0.14014 5.73859
November 390.00000 22.14264 48.31513 0.00703 5.50543
December 403.00000 21.64835 49.38058 -0.1473 6.23271
           
Annual Sum or Average 4745.00000 22.27991 47.64884 -0.3400 11.00752
Minimum of Months 364.00000 21.38233 46.09813 -0.7855 5.50543
Maximum of Months 403.00000 22.91261 49.38058 0.14014 19.03195



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 SUB-STERILE PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.18364 45.81238 -0.0104 5.35328
February 364.00000 22.17268 46.05968 0.00211 5.37000
March 403.00000 22.25024 46.89128 0.04184 5.28942
April 390.00000 22.43840 47.82075 0.11287 5.49403
May 403.00000 22.47417 48.20917 -0.8698 21.30673
June 390.00000 22.52504 47.64582 -0.8362 20.16562
July 403.00000 22.71309 46.81502 -0.7779 18.55046
August 403.00000 22.51805 47.70090 -0.8355 20.18535
September 390.00000 22.59918 47.10826 -0.8202 19.69752
October 403.00000 22.52963 47.80364 0.14397 5.61566
November 390.00000 22.33275 47.60002 0.06933 5.30682
December 403.00000 22.15448 48.08530 -0.0048 5.32486
           
Annual Sum or Average 4745.00000 22.40882 47.30347 -0.3174 11.50871
Minimum of Months 364.00000 22.15448 45.81238 -0.8698 5.28942
Maximum of Months 403.00000 22.71309 48.20917 0.14397 21.30673



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 UTILITY HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.29749 47.78551 -0.2386 6.71148
February 364.00000 21.54771 47.40029 -0.1648 6.35645
March 403.00000 21.88909 47.35472 -0.0565 5.67145
April 390.00000 22.35516 47.43297 0.10644 5.75848
May 403.00000 22.48114 47.32523 -0.8278 20.26006
June 390.00000 22.54514 46.86643 -0.7870 18.95452
July 403.00000 22.77646 45.99017 -0.7097 17.24096
August 403.00000 22.49595 47.08573 -0.8127 19.91769
September 390.00000 22.56317 46.70035 -0.8199 20.02967
October 403.00000 22.34646 47.85562 0.08988 5.35538
November 390.00000 21.95807 48.31347 -0.0341 5.45226
December 403.00000 21.48501 49.27005 -0.1742 6.23968
           
Annual Sum or Average 4745.00000 22.14768 47.45009 -0.3706 11.52637
Minimum of Months 364.00000 21.29749 45.99017 -0.8278 5.35538
Maximum of Months 403.00000 22.77646 49.27005 0.10644 20.26006



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 UTILITY JANITOR PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.33341 43.27476 -0.0209 5.07069
February 364.00000 22.28887 43.32696 -0.0273 5.13647
March 403.00000 22.32727 43.93736 -0.0063 5.05712
April 390.00000 22.36724 45.69701 0.01717 5.04493
May 403.00000 22.35677 45.97197 -1.0310 27.50388
June 390.00000 22.36282 45.99239 -1.0219 27.11467
July 403.00000 22.41682 45.83107 -1.0076 26.52880
August 403.00000 22.36070 46.00255 -1.0205 27.05718
September 390.00000 22.38462 45.84546 -1.0191 27.00413
October 403.00000 22.39037 45.78953 0.02491 5.05339
November 390.00000 22.37858 45.14123 0.01184 5.05266
December 403.00000 22.31947 44.63989 -0.0154 5.06071
           
Annual Sum or Average 4745.00000 22.35763 45.12959 -0.4288 14.27835
Minimum of Months 364.00000 22.28887 43.27476 -1.0310 5.04493
Maximum of Months 403.00000 22.41682 46.00255 0.02491 27.50388



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 VESTIBULE PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.11613 57.54758 -0.1765 13.22990
February 364.00000 22.55473 55.79342 0.09517 10.90923
March 403.00000 22.18261 59.41847 0.05973 14.18568
April 390.00000 24.03869 58.62596 0.43093 13.34073
May 403.00000 25.57754 62.97154 -0.0536 16.58212
June 390.00000 25.97182 68.22061 0.10015 17.90426
July 403.00000 26.34155 63.93943 0.19146 23.52106
August 403.00000 26.57069 67.33542 0.28614 22.32440
September 390.00000 25.85613 65.70051 0.07420 19.32873
October 403.00000 25.33671 64.02013 0.74439 21.98343
November 390.00000 23.98230 63.93602 0.45633 15.15717
December 403.00000 21.40958 60.19754 -0.0915 13.08451
           
Annual Sum or Average 4745.00000 24.25090 62.34258 0.17611 16.84830
Minimum of Months 364.00000 21.11613 55.79342 -0.1765 10.90923
Maximum of Months 403.00000 26.57069 68.22061 0.74439 23.52106



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 CONFERENCE TOILET PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.27051 54.75608 -0.1371 5.60805
February 364.00000 21.28317 54.86733 -0.1334 5.75272
March 403.00000 21.27972 56.66326 -0.1161 5.55829
April 390.00000 21.22928 60.41688 -0.1064 5.38057
May 403.00000 21.13977 61.67380 -1.2564 38.18527
June 390.00000 21.11162 61.56828 -1.2646 38.56731
July 403.00000 21.10887 60.64813 -1.2726 38.97793
August 403.00000 21.11166 61.28203 -1.2651 38.59348
September 390.00000 21.13585 60.80319 -1.2610 38.39792
October 403.00000 21.21281 60.11139 -0.1088 5.37055
November 390.00000 21.32463 59.02854 -0.0934 5.40785
December 403.00000 21.29156 57.14923 -0.1188 5.53065
           
Annual Sum or Average 4745.00000 21.20776 59.10026 -0.5973 19.35955
Minimum of Months 364.00000 21.10887 54.75608 -1.2726 5.37055
Maximum of Months 403.00000 21.32463 61.67380 -0.0934 38.97793



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM HALL 1 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.47878 51.59463 0.10031 5.36181
February 364.00000 22.47901 51.64715 0.10420 5.67003
March 403.00000 22.50580 53.16505 0.12569 5.59308
April 390.00000 22.49752 56.43426 0.14197 5.53118
May 403.00000 22.42525 57.43887 -0.9044 22.42437
June 390.00000 22.37491 57.42867 -0.9223 23.08740
July 403.00000 22.42593 56.36269 -0.9172 22.91139
August 403.00000 22.39495 57.09768 -0.9123 22.72229
September 390.00000 22.45523 56.45398 -0.8983 22.21540
October 403.00000 22.53638 55.82694 0.15199 5.61004
November 390.00000 22.55971 55.36727 0.15374 5.63495
December 403.00000 22.54943 53.59688 0.12996 5.56413
           
Annual Sum or Average 4745.00000 22.47355 55.21702 -0.3064 12.73597
Minimum of Months 364.00000 22.37491 51.59463 -0.9223 5.36181
Maximum of Months 403.00000 22.55971 57.43887 0.15374 23.08740



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM HALL 2 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.46244 51.64836 0.09607 5.32466
February 364.00000 22.43735 51.81280 0.09119 5.51520
March 403.00000 22.44244 53.42069 0.10470 5.42668
April 390.00000 22.37758 56.94768 0.10141 5.29413
May 403.00000 22.28669 58.10498 -0.9722 25.08482
June 390.00000 22.23933 58.11796 -0.9905 25.84667
July 403.00000 22.23453 57.26951 -1.0049 26.44174
August 403.00000 22.25939 57.80742 -0.9825 25.49294
September 390.00000 22.29448 57.19597 -0.9736 25.12809
October 403.00000 22.39344 56.45261 0.10545 5.30051
November 390.00000 22.49840 55.64646 0.13174 5.48331
December 403.00000 22.50294 53.76646 0.11721 5.43672
           
Annual Sum or Average 4745.00000 22.36870 55.70020 -0.3507 13.86504
Minimum of Months 364.00000 22.23453 51.64836 -1.0049 5.29413
Maximum of Months 403.00000 22.50294 58.11796 0.13174 26.44174



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM HALL 3 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.40373 51.93747 0.07153 5.21246
February 364.00000 22.37613 52.11784 0.06551 5.37535
March 403.00000 22.38110 53.76774 0.07748 5.27051
April 390.00000 22.31072 57.31909 0.07288 5.17463
May 403.00000 22.22297 58.48747 -1.0098 26.66054
June 390.00000 22.19040 58.42675 -1.0206 27.13458
July 403.00000 22.17508 57.61407 -1.0372 27.84896
August 403.00000 22.21139 58.12206 -1.0124 26.75917
September 390.00000 22.24676 57.48945 -1.0034 26.38625
October 403.00000 22.34084 56.76516 0.08249 5.20281
November 390.00000 22.43243 55.99055 0.10500 5.31370
December 403.00000 22.43530 54.09773 0.09054 5.27657
           
Annual Sum or Average 4745.00000 22.31020 56.02909 -0.3792 14.35602
Minimum of Months 364.00000 22.17508 51.93747 -1.0372 5.17463
Maximum of Months 403.00000 22.43530 58.48747 0.10500 27.84896



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM HALL 4 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.31611 52.40313 0.03785 5.18537
February 364.00000 22.32144 52.37359 0.04556 5.44228
March 403.00000 22.40247 53.69353 0.08271 5.34407
April 390.00000 22.39183 56.93057 0.10366 5.32264
May 403.00000 22.37175 57.70154 -0.9324 23.47896
June 390.00000 22.34296 57.58934 -0.9400 23.75732
July 403.00000 22.36283 56.65175 -0.9478 24.06770
August 403.00000 22.32500 57.48263 -0.9525 24.25984
September 390.00000 22.32047 57.10672 -0.9654 24.78320
October 403.00000 22.34126 56.76195 0.08380 5.21158
November 390.00000 22.41601 56.11408 0.09548 5.31420
December 403.00000 22.37270 54.43899 0.06621 5.23202
           
Annual Sum or Average 4745.00000 22.35724 55.78581 -0.3543 13.16129
Minimum of Months 364.00000 22.31611 52.37359 -0.9654 5.18537
Maximum of Months 403.00000 22.41601 57.70154 0.10366 24.78320



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM HALL 5 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.39279 52.03152 0.06430 5.24582
February 364.00000 22.39413 52.03579 0.07130 5.52003
March 403.00000 22.45774 53.39395 0.10542 5.47984
April 390.00000 22.45313 56.62857 0.12720 5.45604
May 403.00000 22.43393 57.38725 -0.8987 22.21515
June 390.00000 22.39253 57.31864 -0.9110 22.64483
July 403.00000 22.42489 56.33663 -0.9153 22.81817
August 403.00000 22.37477 57.19608 -0.9236 23.14027
September 390.00000 22.37978 56.79312 -0.9339 23.52939
October 403.00000 22.40898 56.40657 0.10813 5.31991
November 390.00000 22.49019 55.74496 0.12192 5.46555
December 403.00000 22.45286 54.05241 0.09357 5.35491
           
Annual Sum or Average 4745.00000 22.42145 55.45890 -0.3266 12.72392
Minimum of Months 364.00000 22.37477 52.03152 -0.9339 5.24582
Maximum of Months 403.00000 22.49019 57.38725 0.12720 23.52939



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM HALL 6 PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.36548 52.18052 0.05334 5.21545
February 364.00000 22.36142 52.19060 0.05870 5.49511
March 403.00000 22.43480 53.53428 0.09409 5.42178
April 390.00000 22.42236 56.79083 0.11406 5.38114
May 403.00000 22.39974 57.57198 -0.9187 22.96221
June 390.00000 22.36129 57.49996 -0.9302 23.37884
July 403.00000 22.38595 56.54665 -0.9365 23.62681
August 403.00000 22.34460 57.38360 -0.9423 23.86168
September 390.00000 22.34583 56.98900 -0.9532 24.28936
October 403.00000 22.37536 56.59996 0.09497 5.25712
November 390.00000 22.45735 55.92203 0.10889 5.39012
December 403.00000 22.42330 54.21124 0.08189 5.30576
           
Annual Sum or Average 4745.00000 22.38995 55.63361 -0.3420 13.00883
Minimum of Months 364.00000 22.34460 52.18052 -0.9532 5.21545
Maximum of Months 403.00000 22.45735 57.57198 0.11406 24.28936



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 JANITOR PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.05065 53.44933 -0.0227 5.68931
February 364.00000 22.20916 53.78243 0.03068 6.18485
March 403.00000 22.36903 55.50309 0.09492 6.25961
April 390.00000 22.65732 57.82001 0.19876 6.31720
May 403.00000 22.75877 59.77768 -0.7324 17.69239
June 390.00000 22.71953 59.07796 -0.7361 17.67387
July 403.00000 22.89948 57.60686 -0.6838 16.59575
August 403.00000 22.69664 59.09849 -0.7465 18.08437
September 390.00000 22.80280 58.23027 -0.7270 17.59817
October 403.00000 22.77390 58.97904 0.24162 6.99839
November 390.00000 22.48024 57.45553 0.14250 6.15785
December 403.00000 22.28703 57.37557 0.06625 6.08622
           
Annual Sum or Average 4745.00000 22.56042 57.36688 -0.2412 10.97309
Minimum of Months 364.00000 22.05065 53.44933 -0.7465 5.68931
Maximum of Months 403.00000 22.89948 59.77768 0.24162 18.08437



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 OFFICE HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.35957 52.23961 0.05091 5.18576
February 364.00000 22.35436 52.26893 0.05625 5.40842
March 403.00000 22.42243 53.59691 0.09269 5.36683
April 390.00000 22.46475 56.64946 0.12789 5.41769
May 403.00000 22.43960 57.43126 -0.9009 22.26579
June 390.00000 22.43383 57.21453 -0.8981 22.16540
July 403.00000 22.50617 56.06504 -0.8857 21.75903
August 403.00000 22.41542 57.05680 -0.9069 22.49913
September 390.00000 22.45418 56.52242 -0.9041 22.39915
October 403.00000 22.46345 56.21589 0.12378 5.39603
November 390.00000 22.46084 55.91874 0.11145 5.37689
December 403.00000 22.38175 54.41714 0.06875 5.22464
           
Annual Sum or Average 4745.00000 22.43005 55.48051 -0.3243 12.41321
Minimum of Months 364.00000 22.35436 52.23961 -0.9069 5.18576
Maximum of Months 403.00000 22.50617 57.43126 0.12789 22.49913



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 RECEPTION HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.53897 51.41065 0.12276 5.48210
February 364.00000 22.53277 51.54539 0.12282 5.59955
March 403.00000 22.51447 53.11917 0.13568 5.61886
April 390.00000 22.49381 56.47061 0.14452 5.54523
May 403.00000 22.42006 57.47585 -0.9030 22.36296
June 390.00000 22.37718 57.43024 -0.9178 22.90783
July 403.00000 22.40314 56.46922 -0.9237 23.13687
August 403.00000 22.38113 57.18635 -0.9168 22.87153
September 390.00000 22.40844 56.67774 -0.9166 22.86611
October 403.00000 22.47480 56.11097 0.13448 5.46890
November 390.00000 22.57413 55.38485 0.15659 5.68811
December 403.00000 22.57060 53.53618 0.14255 5.61216
           
Annual Sum or Average 4745.00000 22.47376 55.25133 -0.3041 12.80592
Minimum of Months 364.00000 22.37718 51.41065 -0.9237 5.46890
Maximum of Months 403.00000 22.57413 57.47585 0.15659 23.13687



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 WORK HALL PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.55944 51.38114 0.12599 5.52469
February 364.00000 22.55972 51.48077 0.12889 5.68809
March 403.00000 22.54929 53.00233 0.14642 5.73713
April 390.00000 22.56155 56.22702 0.16728 5.74317
May 403.00000 22.51732 57.07134 -0.8566 20.73967
June 390.00000 22.47184 57.00987 -0.8712 21.22260
July 403.00000 22.52915 55.92993 -0.8661 21.06860
August 403.00000 22.46746 56.79414 -0.8743 21.34935
September 390.00000 22.50463 56.27603 -0.8727 21.29510
October 403.00000 22.55379 55.80139 0.15894 5.67058
November 390.00000 22.62332 55.22064 0.17082 5.83800
December 403.00000 22.60261 53.45247 0.14984 5.69910
           
Annual Sum or Average 4745.00000 22.54154 54.98598 -0.2769 12.16903
Minimum of Months 364.00000 22.46746 51.38114 -0.8743 5.52469
Maximum of Months 403.00000 22.62332 57.07134 0.17082 21.34935



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 WORK TOILET PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.17411 55.47359 -0.1839 5.98511
February 364.00000 21.24016 56.02661 -0.1547 6.22903
March 403.00000 21.33669 57.86785 -0.1068 5.82145
April 390.00000 21.40289 60.87785 -0.0551 5.37091
May 403.00000 21.45117 61.95972 -1.1280 32.30820
June 390.00000 21.40196 61.60971 -1.1422 32.86531
July 403.00000 21.47237 60.27229 -1.1200 31.93046
August 403.00000 21.37760 61.50684 -1.1493 33.22630
September 390.00000 21.41785 60.71755 -1.1452 33.08449
October 403.00000 21.42092 60.80372 -0.0464 5.40867
November 390.00000 21.34951 59.41903 -0.0887 5.48594
December 403.00000 21.31557 58.81724 -0.1221 5.81810
           
Annual Sum or Average 4745.00000 21.36409 59.63071 -0.5392 17.02482
Minimum of Months 364.00000 21.17411 55.47359 -1.1493 5.37091
Maximum of Months 403.00000 21.47237 61.95972 -0.0464 33.22630



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 RECEPTION TOILET PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.49500 54.08237 -0.0674 5.43754
February 364.00000 21.51127 54.17472 -0.0639 5.62381
March 403.00000 21.50468 55.94817 -0.0467 5.46964
April 390.00000 21.44918 59.67859 -0.0375 5.27643
May 403.00000 21.32385 61.02767 -1.1689 34.01420
June 390.00000 21.24623 61.10022 -1.1947 35.17683
July 403.00000 21.23987 60.19143 -1.2020 35.54747
August 403.00000 21.24860 60.80022 -1.1934 35.11957
September 390.00000 21.27694 60.31869 -1.1895 34.97474
October 403.00000 21.37901 59.54211 -0.0527 5.27416
November 390.00000 21.53192 58.36520 -0.0280 5.39257
December 403.00000 21.53743 56.36832 -0.0434 5.44986
           
Annual Sum or Average 4745.00000 21.39459 58.48642 -0.5268 17.80211
Minimum of Months 364.00000 21.23987 54.08237 -1.2020 5.27416
Maximum of Months 403.00000 21.53743 61.10022 -0.0280 35.54747



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 BIO HAZ PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 21.66923 45.30548 -0.1925 5.95881
February 364.00000 21.81422 44.88083 -0.1565 5.85842
March 403.00000 22.01282 45.07695 -0.0989 5.34895
April 390.00000 22.20962 46.35447 -0.0338 5.05793
May 403.00000 22.25477 46.44899 -1.0803 29.65719
June 390.00000 22.27746 46.41892 -1.0669 29.05139
July 403.00000 22.32416 46.26468 -1.0555 28.56857
August 403.00000 22.25412 46.52678 -1.0772 29.51713
September 390.00000 22.24093 46.49538 -1.0904 30.10992
October 403.00000 22.16642 46.73330 -0.0460 5.07539
November 390.00000 22.06910 46.30891 -0.0793 5.24091
December 403.00000 21.80437 46.30473 -0.1502 5.62046
           
Annual Sum or Average 4745.00000 22.09253 46.09995 -0.5129 15.47940
Minimum of Months 364.00000 21.66923 44.88083 -1.0904 5.05793
Maximum of Months 403.00000 22.32416 46.73330 -0.0338 30.10992



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 UTILITY ROOM PEOPLE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 403.00000 22.14258 45.05524 -0.0357 5.40427
February 364.00000 22.14156 45.33023 -0.0213 5.44277
March 403.00000 22.25772 46.03328 0.02668 5.29721
April 390.00000 22.47006 47.02834 0.10601 5.46096
May 403.00000 22.52393 47.36210 -0.8696 21.38835
June 390.00000 22.55388 46.91259 -0.8462 20.61705
July 403.00000 22.73980 46.15375 -0.7896 19.06861
August 403.00000 22.53992 46.97501 -0.8510 20.80886
September 390.00000 22.62829 46.42417 -0.8311 20.19672
October 403.00000 22.56862 46.98778 0.13844 5.63529
November 390.00000 22.37446 46.76198 0.06578 5.29037
December 403.00000 22.11755 47.15590 -0.0257 5.41646
           
Annual Sum or Average 4745.00000 22.42290 46.52185 -0.3298 11.70669
Minimum of Months 364.00000 22.11755 45.05524 -0.8696 5.29037
Maximum of Months 403.00000 22.73980 47.36210 0.13844 21.38835



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.937795E+10 0.00 400.88 153822.85 17-JAN-07:01 0.00 25.09 46.66 0.02 0.00 0.03 1.15 17-JAN-07:01
February 0.857396E+10 0.00 384.27 152531.91 22-FEB-07:01 0.00 24.89 47.95 0.02 0.00 0.03 1.14 22-FEB-07:01
March 0.946169E+10 0.00 440.57 155683.52 16-MAR-06:01 0.00 24.90 48.73 0.02 0.00 0.03 1.16 16-MAR-06:01
April 0.912257E+10 0.00 447.39 123465.48 19-APR-06:01 0.00 24.68 49.87 0.02 0.00 0.03 0.92 19-APR-06:01
May 0.102719E+11 0.00 505.22 67571.56 13-MAY-06:03 0.00 24.65 52.24 0.02 0.00 0.03 0.51 13-MAY-06:03
June 0.107359E+11 0.00 517.94 71053.85 15-JUN-06:01 0.00 24.73 53.92 0.02 0.00 0.03 0.53 15-JUN-06:01
July 0.113197E+11 0.00 540.46 96984.74 10-JUL-06:01 0.00 24.73 54.23 0.03 0.00 0.03 0.73 10-JUL-06:01
August 0.110760E+11 0.00 544.35 96420.48 21-AUG-06:01 0.00 24.77 54.43 0.02 0.00 0.03 0.72 21-AUG-06:01
September 0.104700E+11 0.00 521.88 92857.57 18-SEP-06:01 0.00 24.83 54.17 0.02 0.00 0.03 0.69 18-SEP-06:01
October 0.967886E+10 0.00 500.99 75689.86 02-OCT-06:01 0.00 24.76 52.05 0.02 0.00 0.03 0.57 02-OCT-06:01
November 0.831796E+10 0.00 435.88 153753.64 13-NOV-07:01 0.00 24.68 49.23 0.02 0.00 0.02 1.15 13-NOV-07:01
December 0.945408E+10 0.00 413.17 154988.85 12-DEC-07:01 0.00 25.12 47.34 0.02 0.00 0.03 1.16 12-DEC-07:01
                           
Annual Sum or Average 0.117860E+12 0.00 5652.99     0.00 24.82 50.91 0.02 0.00 0.03    
Minimum of Months 0.831796E+10 0.00 384.27 67571.56   0.00 24.65 46.66 0.02 0.00 0.02 0.51  
Maximum of Months 0.113197E+11 0.00 544.35 155683.52   0.00 25.12 54.43 0.03 0.00 0.03 1.16  



Table of Contents

Report: DXReportMonthly

For: AHU-1 COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.788082E+11 0.191246E+11 411.26 0.596961E+11 0.191121E+11 0.00 1.00 01-JAN-08:11 0.00 01-JAN-00:05 104395.80 06-JAN-07:03 70468.29 06-JAN-07:03 41732.33 02-JAN-14:00 26102.23 02-JAN-14:00 0.00
February 0.790498E+11 0.193210E+11 388.06 0.593655E+11 0.196843E+11 0.00 1.00 01-FEB-06:12 0.00 01-FEB-00:10 110329.19 02-FEB-07:03 70957.31 02-FEB-07:03 39371.88 02-FEB-07:03 26321.43 02-FEB-07:03 0.00
March 0.960909E+11 0.234376E+11 454.17 0.701939E+11 0.258970E+11 0.00 1.00 01-MAR-07:01 0.00 01-MAR-00:05 119817.72 14-MAR-06:03 71556.49 10-MAR-07:03 49815.46 14-MAR-06:03 28413.91 14-MAR-06:03 0.00
April 0.107733E+12 0.266276E+11 466.34 0.763986E+11 0.313339E+11 0.00 1.00 01-APR-00:21 0.00 01-APR-00:03 121869.64 12-APR-06:02 75200.08 12-APR-06:02 46669.56 12-APR-06:02 29441.81 12-APR-06:02 0.00
May 0.141800E+12 0.355665E+11 528.81 0.915818E+11 0.502185E+11 0.00 1.00 01-MAY-01:26 0.00 01-MAY-00:02 137682.24 31-MAY-06:02 79853.26 19-MAY-06:02 60268.83 31-MAY-06:02 32973.53 31-MAY-06:02 0.00
June 0.158950E+12 0.399474E+11 540.10 0.956793E+11 0.632708E+11 0.00 1.00 01-JUN-00:29 0.00 01-JUN-00:01 143582.94 07-JUN-06:01 86529.64 15-JUN-06:01 61905.02 07-JUN-06:01 35564.43 08-JUN-06:01 0.00
July 0.166176E+12 0.423110E+11 563.27 0.999218E+11 0.662545E+11 0.00 1.00 01-JUL-00:01 0.00 01-JUL-00:31 144051.17 26-JUL-06:01 85359.66 21-JUL-06:01 62630.68 26-JUL-06:01 35152.33 14-JUL-06:01 0.00
August 0.170495E+12 0.431135E+11 566.55 0.101619E+12 0.688754E+11 0.00 1.00 01-AUG-00:28 0.00 01-AUG-00:01 143680.61 04-AUG-06:01 90006.39 11-AUG-06:01 63061.22 24-AUG-06:02 35485.77 01-AUG-06:01 0.00
September 0.156833E+12 0.394806E+11 544.20 0.945372E+11 0.622962E+11 0.00 1.00 01-SEP-00:11 0.00 01-SEP-00:03 143614.25 22-SEP-06:01 84857.15 21-SEP-06:01 61255.59 22-SEP-06:02 35361.33 22-SEP-06:01 0.00
October 0.141179E+12 0.352243E+11 524.11 0.891972E+11 0.519821E+11 0.00 1.00 01-OCT-00:21 0.00 01-OCT-00:03 145162.72 04-OCT-06:01 80066.99 02-OCT-06:01 66710.90 04-OCT-06:01 34978.35 30-OCT-06:01 0.00
November 0.113665E+12 0.278818E+11 455.89 0.746941E+11 0.389706E+11 0.00 1.00 01-NOV-00:31 0.00 01-NOV-00:03 141745.57 30-NOV-07:02 81229.86 30-NOV-07:02 60515.72 30-NOV-07:02 34108.00 30-NOV-07:02 0.00
December 0.859434E+11 0.208045E+11 423.55 0.622099E+11 0.237335E+11 0.00 1.00 01-DEC-00:01 0.00 01-DEC-00:31 115924.66 07-DEC-07:03 72224.10 07-DEC-07:03 43787.31 08-DEC-07:03 27649.27 07-DEC-07:03 0.00
                                       
Annual Sum or Average 0.149672E+13 0.372841E+12 5866.31 0.975095E+12 0.521629E+12 0.00                         0.00
Minimum of Months 0.788082E+11 0.191246E+11 388.06 0.593655E+11 0.191121E+11 0.00 1.00   0.00   104395.80   70468.29   39371.88   26102.23   0.00
Maximum of Months 0.170495E+12 0.431135E+11 566.55 0.101619E+12 0.688754E+11 0.00 1.00   0.00   145162.72   90006.39   66710.90   35564.43   0.00



Table of Contents

Report: DXReportMonthly

For: AHU-2 COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.668292E+11 0.163338E+11 371.92 0.545641E+11 0.122652E+11 0.00 1.00 01-JAN-10:51 0.00 01-JAN-00:05 151751.18 14-JAN-05:01 89213.06 14-JAN-05:01 62538.12 14-JAN-05:01 35327.27 14-JAN-05:01 0.00
February 0.684467E+11 0.167897E+11 347.68 0.554487E+11 0.129980E+11 0.00 1.00 01-FEB-06:12 0.00 01-FEB-00:10 142715.32 11-FEB-05:01 83923.03 11-FEB-05:01 58792.29 11-FEB-05:01 33227.12 11-FEB-05:01 0.00
March 0.824539E+11 0.201547E+11 403.85 0.653460E+11 0.171079E+11 0.00 1.00 01-MAR-07:01 0.00 01-MAR-00:05 147278.46 14-MAR-06:03 79693.46 10-MAR-07:03 67787.44 14-MAR-06:03 34393.24 14-MAR-06:03 0.00
April 0.931693E+11 0.230857E+11 412.47 0.721028E+11 0.210665E+11 0.00 1.00 01-APR-05:01 0.00 01-APR-00:03 145957.45 12-APR-06:02 82427.52 12-APR-06:02 63529.94 12-APR-06:02 34725.35 12-APR-06:02 0.00
May 0.123714E+12 0.311352E+11 473.04 0.877551E+11 0.359585E+11 0.00 1.00 01-MAY-04:11 0.00 01-MAY-00:02 153205.28 27-MAY-04:01 96631.75 08-MAY-05:01 69567.39 31-MAY-06:02 35635.38 31-MAY-06:02 0.00
June 0.141005E+12 0.356401E+11 504.49 0.935806E+11 0.474248E+11 0.00 1.00 01-JUN-00:21 0.00 01-JUN-00:01 151287.01 06-JUN-05:02 93679.55 03-JUN-04:01 74114.12 26-JUN-06:03 36740.75 08-JUN-06:01 0.00
July 0.145270E+12 0.374143E+11 514.47 0.964765E+11 0.487930E+11 0.00 1.00 01-JUL-04:01 0.00 01-JUL-00:01 150493.92 26-JUL-06:01 88624.45 28-JUL-15:30 72038.56 14-JUL-06:03 36328.21 14-JUL-06:01 0.00
August 0.149729E+12 0.381780E+11 520.58 0.980999E+11 0.516289E+11 0.00 1.00 01-AUG-04:12 0.00 01-AUG-00:01 150589.95 24-AUG-06:02 88508.92 11-AUG-06:01 70827.25 04-AUG-06:03 36679.10 01-AUG-06:01 0.00
September 0.136615E+12 0.347023E+11 498.44 0.908561E+11 0.457591E+11 0.00 1.00 01-SEP-04:11 0.00 01-SEP-00:11 151576.31 22-SEP-05:01 94516.05 16-SEP-04:01 74043.56 22-SEP-06:03 36668.35 22-SEP-05:01 0.00
October 0.121733E+12 0.306060E+11 467.62 0.845012E+11 0.372316E+11 0.00 1.00 01-OCT-05:01 0.00 01-OCT-00:03 151440.75 30-OCT-06:02 92658.64 14-OCT-05:01 75651.78 30-OCT-06:02 36209.53 30-OCT-06:02 0.00
November 0.969734E+11 0.238650E+11 392.32 0.691341E+11 0.278393E+11 0.00 1.00 01-NOV-04:11 0.00 01-NOV-00:03 150446.54 30-NOV-07:02 87716.02 21-NOV-07:02 68585.95 30-NOV-07:02 35732.11 30-NOV-07:02 0.00
December 0.713335E+11 0.174300E+11 381.25 0.564732E+11 0.148603E+11 0.00 1.00 01-DEC-04:31 0.00 01-DEC-00:01 140889.79 07-DEC-07:03 87085.21 09-DEC-05:01 61558.00 23-DEC-06:12 33027.85 07-DEC-07:03 0.00
                                       
Annual Sum or Average 0.129727E+13 0.325335E+12 5288.11 0.924338E+12 0.372933E+12 0.00                         0.00
Minimum of Months 0.668292E+11 0.163338E+11 347.68 0.545641E+11 0.122652E+11 0.00 1.00   0.00   140889.79   79693.46   58792.29   33027.85   0.00
Maximum of Months 0.149729E+12 0.381780E+11 520.58 0.980999E+11 0.516289E+11 0.00 1.00   0.00   153205.28   96631.75   75651.78   36740.75   0.00



Table of Contents

Report: DXReportMonthly

For: AHU-3 COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.739216E+11 0.184190E+11 513.22 0.608576E+11 0.130640E+11 0.00 1.00 01-JAN-13:02 0.00 01-JAN-00:05 112198.93 02-JAN-14:00 73553.87 02-JAN-14:00 38652.42 02-JAN-13:55 28495.94 02-JAN-14:00 0.00
February 0.773034E+11 0.193083E+11 493.22 0.632426E+11 0.140608E+11 0.00 1.00 01-FEB-07:03 0.00 01-FEB-00:10 117357.44 02-FEB-07:03 76210.43 22-FEB-15:05 44190.29 02-FEB-07:03 27661.26 02-FEB-07:03 0.00
March 0.952590E+11 0.237267E+11 585.34 0.762521E+11 0.190069E+11 0.00 1.00 01-MAR-10:10 0.00 01-MAR-00:05 135530.52 14-MAR-06:03 75882.99 27-MAR-15:00 60564.81 14-MAR-06:03 31707.60 14-MAR-06:03 0.00
April 0.107673E+12 0.271976E+11 606.34 0.846196E+11 0.230531E+11 0.00 1.00 01-APR-10:20 0.00 01-APR-00:32 137829.19 12-APR-06:02 101319.20 16-APR-14:51 57631.50 12-APR-06:02 32848.33 12-APR-06:02 0.00
May 0.135758E+12 0.346542E+11 641.64 0.982106E+11 0.375479E+11 0.00 1.00 01-MAY-06:03 0.00 01-MAY-00:02 145699.89 31-MAY-06:02 98055.65 29-MAY-16:01 65932.96 31-MAY-06:02 35722.82 29-MAY-16:01 0.00
June 0.149077E+12 0.380534E+11 625.63 0.100861E+12 0.482160E+11 0.00 1.00 01-JUN-04:01 0.00 01-JUN-00:31 145698.23 22-JUN-06:03 93036.36 11-JUN-14:41 67257.68 08-JUN-06:03 35612.24 08-JUN-06:01 0.00
July 0.154013E+12 0.399723E+11 640.16 0.104525E+12 0.494878E+11 0.00 1.00 01-JUL-06:00 0.00 01-JUL-00:31 145739.61 26-JUL-06:01 103571.25 30-JUL-14:41 67728.00 26-JUL-06:02 38783.16 28-JUL-15:00 0.00
August 0.157166E+12 0.404410E+11 646.51 0.105114E+12 0.520522E+11 0.00 1.00 01-AUG-04:01 0.00 01-AUG-00:31 145763.15 24-AUG-06:02 92710.06 06-AUG-14:42 66871.66 24-AUG-06:02 36367.73 23-AUG-13:00 0.00
September 0.143650E+12 0.368137E+11 621.57 0.973883E+11 0.462616E+11 0.00 1.00 01-SEP-04:02 0.00 01-SEP-00:32 145955.62 20-SEP-06:03 89766.56 10-SEP-16:01 67847.85 20-SEP-06:03 35419.58 22-SEP-06:01 0.00
October 0.131979E+12 0.336271E+11 635.89 0.935859E+11 0.383928E+11 0.00 1.00 01-OCT-10:41 0.00 01-OCT-00:32 146564.25 04-OCT-06:01 86625.09 06-OCT-12:40 71252.67 04-OCT-06:02 35037.51 30-OCT-06:01 0.00
November 0.108130E+12 0.270806E+11 573.43 0.790413E+11 0.290888E+11 0.00 1.00 01-NOV-06:03 0.00 01-NOV-00:31 145523.96 30-NOV-07:02 81653.32 21-NOV-07:02 65443.91 30-NOV-07:02 34617.35 30-NOV-07:02 0.00
December 0.800836E+11 0.199660E+11 538.20 0.636429E+11 0.164407E+11 0.00 1.00 01-DEC-07:03 0.00 01-DEC-00:12 123965.19 07-DEC-07:03 74459.76 01-DEC-07:03 49799.34 07-DEC-07:03 29206.66 07-DEC-07:03 0.00
                                       
Annual Sum or Average 0.141401E+13 0.359260E+12 7121.14 0.102734E+13 0.386673E+12 0.00                         0.00
Minimum of Months 0.739216E+11 0.184190E+11 493.22 0.608576E+11 0.130640E+11 0.00 1.00   0.00   112198.93   73553.87   38652.42   27661.26   0.00
Maximum of Months 0.157166E+12 0.404410E+11 646.51 0.105114E+12 0.520522E+11 0.00 1.00   0.00   146564.25   103571.25   71252.67   38783.16   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ_CAFE HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.628952E+10 0.173170E+10 533.18 0.409426E+10 0.219526E+10 0.00 1.00 02-JAN-06:12 0.00 02-JAN-18:01 9909.20 02-JAN-14:10 6438.46 02-JAN-12:40 5140.07 07-JAN-06:12 2778.27 02-JAN-14:40 0.00
February 0.648578E+10 0.180997E+10 522.79 0.424443E+10 0.224135E+10 0.00 1.00 01-FEB-06:12 0.00 01-FEB-00:10 9657.39 02-FEB-06:12 6528.13 22-FEB-15:00 5055.73 11-FEB-07:03 2749.51 02-FEB-14:00 0.00
March 0.764072E+10 0.212623E+10 630.74 0.480881E+10 0.283191E+10 0.00 1.00 01-MAR-07:01 0.00 01-MAR-01:05 9809.06 14-MAR-10:10 6045.82 28-MAR-14:00 5579.90 14-MAR-06:03 2788.05 13-MAR-16:00 0.00
April 0.827811E+10 0.233931E+10 684.52 0.512660E+10 0.315151E+10 0.00 1.00 01-APR-05:12 0.00 01-APR-05:14 9839.30 14-APR-15:10 6983.20 17-APR-15:00 5354.24 14-APR-06:03 2835.97 14-APR-13:50 0.00
May 0.105355E+11 0.302731E+10 735.44 0.605684E+10 0.447871E+10 0.00 1.00 01-MAY-05:12 0.00 01-MAY-00:12 10006.97 31-MAY-17:00 6637.14 22-MAY-13:00 5930.94 27-MAY-06:03 2977.34 22-MAY-13:00 0.00
June 0.114276E+11 0.324418E+10 717.95 0.599643E+10 0.543117E+10 0.00 1.00 01-JUN-04:01 0.00 01-JUN-04:02 10155.72 28-JUN-12:00 5959.44 16-JUN-16:00 5808.75 26-JUN-06:01 2853.65 13-JUN-13:00 0.00
July 0.112753E+11 0.323546E+10 742.33 0.599940E+10 0.527594E+10 0.00 1.00 01-JUL-04:01 0.00 01-JUL-04:02 10186.81 25-JUL-14:55 6584.89 07-JUL-12:00 5968.12 29-JUL-06:03 2997.05 28-JUL-16:00 0.00
August 0.121429E+11 0.346079E+10 742.27 0.638169E+10 0.576122E+10 0.00 1.00 01-AUG-04:01 0.00 01-AUG-04:02 10212.13 21-AUG-12:00 6233.37 14-AUG-14:00 5938.70 05-AUG-06:03 2950.55 23-AUG-13:00 0.00
September 0.111707E+11 0.318567E+10 718.53 0.596234E+10 0.520841E+10 0.00 1.00 01-SEP-05:02 0.00 01-SEP-04:03 10184.02 22-SEP-17:00 6211.70 08-SEP-16:00 5887.09 20-SEP-06:03 2893.80 08-SEP-15:00 0.00
October 0.106770E+11 0.305513E+10 742.83 0.605647E+10 0.462051E+10 0.00 1.00 02-OCT-04:02 0.00 02-OCT-04:03 10188.03 02-OCT-12:00 6501.00 19-OCT-14:05 6186.59 04-OCT-06:01 2869.41 03-OCT-12:50 0.00
November 0.914389E+10 0.257068E+10 670.55 0.525877E+10 0.388512E+10 0.00 1.00 01-NOV-05:12 0.00 01-NOV-05:14 10044.52 30-NOV-12:00 6455.38 06-NOV-13:30 5967.39 04-NOV-06:03 2807.14 17-NOV-15:00 0.00
December 0.671285E+10 0.185120E+10 578.32 0.425071E+10 0.246214E+10 0.00 1.00 01-DEC-06:12 0.00 01-DEC-18:01 9814.40 23-DEC-06:12 6275.46 04-DEC-14:50 5531.02 23-DEC-07:03 2737.42 08-DEC-14:00 0.00
                                       
Annual Sum or Average 0.111780E+12 0.316376E+11 8019.44 0.642367E+11 0.475432E+11 0.00                         0.00
Minimum of Months 0.628952E+10 0.173170E+10 522.79 0.409426E+10 0.219526E+10 0.00 1.00   0.00   9657.39   5959.44   5055.73   2737.42   0.00
Maximum of Months 0.121429E+11 0.346079E+10 742.83 0.638169E+10 0.576122E+10 0.00 1.00   0.00   10212.13   6983.20   6186.59   2997.05   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ_ELEVATOR HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.101084E+10 0.288134E+09 724.95 0.980532E+09 30307414.36 0.00 1.00 02-JAN-06:12 0.00 02-JAN-18:01 1759.46 14-JAN-05:01 1625.77 27-JAN-07:01 420.01 14-JAN-05:01 486.27 14-JAN-05:01 0.00
February 0.967407E+09 0.278387E+09 632.04 0.923668E+09 43738840.56 0.00 1.00 01-FEB-06:12 0.00 01-FEB-18:01 1764.24 11-FEB-05:01 1604.73 24-FEB-07:01 431.49 11-FEB-05:01 486.98 11-FEB-05:01 0.00
March 0.115599E+10 0.332874E+09 715.06 0.109829E+10 57703806.42 0.00 1.00 01-MAR-06:12 0.00 01-MAR-18:01 1713.02 10-MAR-06:12 1582.97 15-MAR-06:01 426.88 10-MAR-06:12 468.92 14-MAR-05:12 0.00
April 0.122489E+10 0.362220E+09 718.54 0.116894E+10 55957069.61 0.00 1.00 01-APR-05:12 0.00 01-APR-14:01 1578.07 22-APR-05:12 1436.27 19-APR-06:01 321.07 13-APR-04:01 431.19 22-APR-05:12 0.00
May 0.145824E+10 0.443657E+09 742.50 0.136246E+10 95774049.57 0.00 1.00 01-MAY-05:12 0.00 01-MAY-17:01 1768.38 27-MAY-04:01 1474.78 08-MAY-05:01 469.60 27-MAY-04:01 494.24 20-MAY-04:01 0.00
June 0.147608E+10 0.455119E+09 718.62 0.138818E+10 87894948.58 0.00 1.00 01-JUN-04:01 0.00 01-JUN-04:02 1735.42 17-JUN-04:01 1529.68 23-JUN-06:01 335.70 17-JUN-04:01 497.94 08-JUN-06:01 0.00
July 0.155102E+10 0.487736E+09 742.59 0.147750E+10 73518056.30 0.00 1.00 01-JUL-04:01 0.00 01-JUL-04:02 1659.02 13-JUL-04:01 1513.32 17-JUL-06:01 261.29 13-JUL-04:01 487.68 14-JUL-06:01 0.00
August 0.160268E+10 0.498776E+09 742.45 0.151615E+10 86532001.90 0.00 1.00 01-AUG-04:01 0.00 01-AUG-04:02 1721.14 18-AUG-04:01 1541.54 09-AUG-06:01 332.37 18-AUG-04:01 509.28 01-AUG-04:01 0.00
September 0.152165E+10 0.469703E+09 718.58 0.144104E+10 80619617.50 0.00 1.00 01-SEP-04:02 0.00 01-SEP-17:01 1718.77 20-SEP-04:01 1522.90 11-SEP-06:01 313.23 20-SEP-04:01 506.52 23-SEP-04:01 0.00
October 0.147015E+10 0.446356E+09 742.58 0.139092E+10 79234051.40 0.00 1.00 02-OCT-04:02 0.00 02-OCT-17:01 1729.60 04-OCT-04:01 1619.98 14-OCT-05:01 334.05 04-OCT-04:01 496.26 04-OCT-04:01 0.00
November 0.124671E+10 0.366744E+09 710.78 0.118286E+10 63848264.40 0.00 1.00 01-NOV-05:12 0.00 01-NOV-17:01 1713.09 22-NOV-06:12 1625.92 27-NOV-07:01 375.05 22-NOV-06:12 469.50 22-NOV-06:12 0.00
December 0.110840E+10 0.317535E+09 713.60 0.106258E+10 45820412.59 0.00 1.00 01-DEC-06:12 0.00 01-DEC-18:01 1720.13 09-DEC-05:01 1612.50 13-DEC-07:01 350.69 23-DEC-06:12 484.60 09-DEC-05:01 0.00
                                       
Annual Sum or Average 0.157941E+11 0.474724E+10 8622.29 0.149931E+11 0.800949E+09 0.00                         0.00
Minimum of Months 0.967407E+09 0.278387E+09 632.04 0.923668E+09 30307414.36 0.00 1.00   0.00   1578.07   1436.27   261.29   431.19   0.00
Maximum of Months 0.160268E+10 0.498776E+09 742.59 0.151615E+10 95774049.57 0.00 1.00   0.00   1768.38   1625.92   469.60   509.28   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ_MRI_CONTROL HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.337930E+10 0.948497E+09 742.72 0.293173E+10 0.447569E+09 0.00 1.00 02-JAN-06:12 0.00 02-JAN-18:01 3999.13 05-JAN-07:01 3624.52 27-JAN-07:01 944.19 02-JAN-14:10 1077.65 05-JAN-07:01 0.00
February 0.321111E+10 0.915294E+09 670.56 0.277048E+10 0.440630E+09 0.00 1.00 01-FEB-06:12 0.00 01-FEB-18:01 4029.80 21-FEB-07:01 3622.10 24-FEB-07:01 940.73 11-FEB-07:03 1086.65 21-FEB-07:01 0.00
March 0.380135E+10 0.107999E+10 742.74 0.325252E+10 0.548837E+09 0.00 1.00 01-MAR-06:12 0.00 01-MAR-18:01 4100.02 14-MAR-06:03 3618.42 15-MAR-06:01 1119.12 14-MAR-06:03 1133.42 14-MAR-06:03 0.00
April 0.385709E+10 0.112672E+10 718.97 0.324551E+10 0.611572E+09 0.00 1.00 01-APR-05:12 0.00 01-APR-14:01 4123.98 12-APR-06:02 3403.22 19-APR-06:01 1064.66 14-APR-06:03 1171.93 12-APR-06:02 0.00
May 0.445859E+10 0.134884E+10 742.98 0.363316E+10 0.825435E+09 0.00 1.00 01-MAY-05:12 0.00 01-MAY-17:01 4160.38 31-MAY-06:02 3692.77 08-MAY-05:01 1209.25 31-MAY-06:02 1181.10 31-MAY-06:02 0.00
June 0.465985E+10 0.142535E+10 718.92 0.366892E+10 0.990934E+09 0.00 1.00 01-JUN-04:01 0.00 01-JUN-17:01 4159.44 22-JUN-06:03 3493.11 06-JUN-05:02 1208.61 08-JUN-06:02 1229.68 08-JUN-06:01 0.00
July 0.466292E+10 0.145664E+10 742.99 0.368393E+10 0.978991E+09 0.00 1.00 01-JUL-04:01 0.00 01-JUL-04:02 4161.19 24-JUL-06:03 3243.56 18-JUL-05:12 1255.58 26-JUL-06:02 1240.51 28-JUL-15:10 0.00
August 0.489144E+10 0.151113E+10 742.99 0.382867E+10 0.106278E+10 0.00 1.00 01-AUG-04:01 0.00 01-AUG-17:01 4165.79 24-AUG-06:02 3242.98 14-AUG-05:12 1235.67 24-AUG-06:02 1226.37 01-AUG-06:01 0.00
September 0.448758E+10 0.137596E+10 718.97 0.354012E+10 0.947458E+09 0.00 1.00 01-SEP-04:02 0.00 01-SEP-17:01 4164.92 20-SEP-06:03 3226.60 27-SEP-05:12 1232.77 22-SEP-06:02 1222.04 22-SEP-06:01 0.00
October 0.435602E+10 0.131536E+10 743.08 0.351679E+10 0.839230E+09 0.00 1.00 02-OCT-04:02 0.00 02-OCT-17:01 4179.09 04-OCT-06:01 3479.79 26-OCT-05:02 1346.95 04-OCT-06:02 1205.51 30-OCT-06:01 0.00
November 0.392944E+10 0.114736E+10 718.98 0.322007E+10 0.709370E+09 0.00 1.00 01-NOV-05:12 0.00 01-NOV-17:01 4149.84 30-NOV-07:02 3596.39 13-NOV-07:01 1173.73 04-NOV-06:03 1184.71 30-NOV-07:02 0.00
December 0.346820E+10 0.978834E+09 742.74 0.297699E+10 0.491209E+09 0.00 1.00 01-DEC-06:12 0.00 01-DEC-18:01 4025.43 19-DEC-07:01 3598.13 12-DEC-07:01 1008.86 08-DEC-07:03 1102.62 07-DEC-07:03 0.00
                                       
Annual Sum or Average 0.491629E+11 0.146300E+11 8746.66 0.402689E+11 0.889401E+10 0.00                         0.00
Minimum of Months 0.321111E+10 0.915294E+09 670.56 0.277048E+10 0.440630E+09 0.00 1.00   0.00   3999.13   3226.60   940.73   1077.65   0.00
Maximum of Months 0.489144E+10 0.151113E+10 743.08 0.382867E+10 0.106278E+10 0.00 1.00   0.00   4179.09   3692.77   1346.95   1240.51   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ_MRI HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.907536E+10 0.254927E+10 742.78 0.799149E+10 0.108387E+10 0.00 1.00 02-JAN-06:12 0.00 02-JAN-18:01 9825.84 05-JAN-07:01 9307.31 25-JAN-07:01 2372.20 07-JAN-07:03 2670.61 06-JAN-07:03 0.00
February 0.850843E+10 0.242593E+10 670.82 0.743962E+10 0.106881E+10 0.00 1.00 01-FEB-06:12 0.00 01-FEB-18:01 9946.55 02-FEB-07:03 8866.61 03-FEB-07:01 2517.49 11-FEB-07:03 2740.29 02-FEB-07:03 0.00
March 0.994873E+10 0.282490E+10 742.74 0.860970E+10 0.133902E+10 0.00 1.00 01-MAR-06:12 0.00 01-MAR-18:01 10109.62 06-MAR-06:12 9034.45 17-MAR-06:01 2803.24 14-MAR-06:03 2796.26 14-MAR-06:03 0.00
April 0.982933E+10 0.287011E+10 718.88 0.832308E+10 0.150626E+10 0.00 1.00 01-APR-05:12 0.00 01-APR-14:01 10109.30 14-APR-05:12 8626.75 19-APR-06:01 2688.60 14-APR-06:03 2858.36 12-APR-06:02 0.00
May 0.110642E+11 0.334419E+10 742.89 0.901450E+10 0.204966E+10 0.00 1.00 01-MAY-05:12 0.00 01-MAY-17:01 10158.27 31-MAY-06:02 8969.90 08-MAY-05:01 3026.00 31-MAY-06:02 2882.50 31-MAY-06:02 0.00
June 0.114386E+11 0.349532E+10 718.87 0.896330E+10 0.247534E+10 0.00 1.00 01-JUN-04:01 0.00 01-JUN-17:01 10157.43 12-JUN-06:02 8534.00 06-JUN-05:02 3061.21 07-JUN-06:02 3002.21 08-JUN-06:01 0.00
July 0.113668E+11 0.354533E+10 742.95 0.892310E+10 0.244371E+10 0.00 1.00 01-JUL-04:01 0.00 01-JUL-04:02 10161.14 24-JUL-06:03 8321.79 07-JUL-05:12 3170.38 29-JUL-06:03 2977.43 28-JUL-15:10 0.00
August 0.120283E+11 0.371113E+10 742.93 0.937019E+10 0.265808E+10 0.00 1.00 01-AUG-04:01 0.00 01-AUG-17:01 10175.16 28-AUG-06:02 8144.64 14-AUG-05:12 3225.39 05-AUG-06:03 2994.07 01-AUG-06:01 0.00
September 0.110324E+11 0.337870E+10 718.88 0.866703E+10 0.236541E+10 0.00 1.00 01-SEP-04:02 0.00 01-SEP-17:01 10167.78 20-SEP-06:03 8268.48 27-SEP-05:12 3096.69 22-SEP-06:02 2983.46 22-SEP-06:01 0.00
October 0.108633E+11 0.327813E+10 742.89 0.878076E+10 0.208256E+10 0.00 1.00 02-OCT-04:02 0.00 02-OCT-17:01 10210.25 04-OCT-06:01 8667.78 23-OCT-05:02 3367.70 04-OCT-06:02 2943.23 30-OCT-06:01 0.00
November 0.100682E+11 0.293854E+10 718.91 0.830541E+10 0.176278E+10 0.00 1.00 01-NOV-05:12 0.00 01-NOV-17:01 10138.33 10-NOV-06:12 9066.83 13-NOV-07:01 3121.98 04-NOV-06:03 2891.25 30-NOV-07:02 0.00
December 0.919071E+10 0.259373E+10 742.76 0.799196E+10 0.119876E+10 0.00 1.00 01-DEC-06:12 0.00 01-DEC-18:01 10094.08 08-DEC-06:12 8829.29 15-DEC-07:01 2606.12 23-DEC-07:03 2791.27 07-DEC-07:03 0.00
                                       
Annual Sum or Average 0.124414E+12 0.369553E+11 8746.29 0.102380E+12 0.220342E+11 0.00                         0.00
Minimum of Months 0.850843E+10 0.242593E+10 670.82 0.743962E+10 0.106881E+10 0.00 1.00   0.00   9825.84   8144.64   2372.20   2670.61   0.00
Maximum of Months 0.120283E+11 0.371113E+10 742.95 0.937019E+10 0.265808E+10 0.00 1.00   0.00   10210.25   9307.31   3367.70   3002.21   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ_OR_1 HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.145064E+11 0.409218E+10 741.94 0.109454E+11 0.356097E+10 0.00 1.00 01-JAN-06:01 0.00 01-JAN-06:02 18286.31 02-JAN-14:10 16207.34 01-JAN-06:01 7586.02 02-JAN-14:00 5496.36 02-JAN-14:10 0.00
February 0.143195E+11 0.408856E+10 669.03 0.107113E+11 0.360819E+10 0.00 1.00 01-FEB-06:01 0.00 01-FEB-17:01 18295.56 11-FEB-06:02 16076.51 05-FEB-06:01 6774.89 11-FEB-11:30 5109.19 11-FEB-06:02 0.00
March 0.168083E+11 0.479520E+10 742.63 0.122568E+11 0.455144E+10 0.00 1.00 01-MAR-06:01 0.00 01-MAR-17:01 18259.77 06-MAR-06:01 15721.47 12-MAR-05:01 7936.23 14-MAR-09:30 5304.55 14-MAR-10:00 0.00
April 0.180153E+11 0.525440E+10 718.71 0.128651E+11 0.515015E+10 0.00 1.00 01-APR-05:01 0.00 01-APR-16:01 18168.13 12-APR-05:02 16047.96 02-APR-05:01 7634.47 25-APR-14:00 5617.36 14-APR-14:40 0.00
May 0.217552E+11 0.656151E+10 742.77 0.146054E+11 0.714976E+10 0.00 1.00 01-MAY-05:02 0.00 01-MAY-16:01 18473.06 27-MAY-05:02 15552.37 07-MAY-05:01 8508.74 31-MAY-06:50 5849.68 22-MAY-13:00 0.00
June 0.234461E+11 0.711343E+10 718.97 0.147732E+11 0.867288E+10 0.00 1.00 01-JUN-05:02 0.00 01-JUN-16:01 18750.14 28-JUN-11:40 15684.67 25-JUN-05:01 8818.31 28-JUN-11:30 5695.71 06-JUN-13:00 0.00
July 0.236129E+11 0.728974E+10 742.96 0.150865E+11 0.852648E+10 0.00 1.00 01-JUL-05:02 0.00 01-JUL-16:01 18946.67 26-JUL-16:03 15756.66 02-JUL-05:01 9221.81 29-JUL-08:70 5993.77 28-JUL-16:03 0.00
August 0.247646E+11 0.756370E+10 743.15 0.155398E+11 0.922480E+10 0.00 1.00 01-AUG-05:02 0.00 01-AUG-16:01 18877.56 21-AUG-12:00 15784.09 06-AUG-05:01 9061.14 26-AUG-08:70 5904.58 23-AUG-13:00 0.00
September 0.230017E+11 0.699147E+10 719.00 0.146649E+11 0.833675E+10 0.00 1.00 01-SEP-05:02 0.00 02-SEP-16:01 18792.99 22-SEP-16:03 16009.69 04-SEP-05:01 8955.86 09-SEP-08:65 5785.09 20-SEP-14:00 0.00
October 0.218564E+11 0.657134E+10 742.78 0.145715E+11 0.728490E+10 0.00 1.00 01-OCT-05:01 0.00 01-OCT-16:01 18827.52 04-OCT-08:00 15990.35 22-OCT-05:01 9505.20 04-OCT-06:40 5739.68 02-OCT-14:00 0.00
November 0.189403E+11 0.551767E+10 718.38 0.128770E+11 0.606327E+10 0.00 1.00 01-NOV-05:01 0.00 01-NOV-16:01 18562.35 29-NOV-12:00 16506.28 12-NOV-06:01 8746.17 29-NOV-11:20 5529.08 03-NOV-14:00 0.00
December 0.151781E+11 0.429473E+10 742.24 0.111584E+11 0.401971E+10 0.00 1.00 01-DEC-06:02 0.00 01-DEC-17:01 18292.86 23-DEC-06:01 15742.19 17-DEC-06:01 7289.66 23-DEC-09:10 5178.18 08-DEC-14:00 0.00
                                       
Annual Sum or Average 0.236205E+12 0.701339E+11 8742.56 0.160055E+12 0.761493E+11 0.00                         0.00
Minimum of Months 0.143195E+11 0.408856E+10 669.03 0.107113E+11 0.356097E+10 0.00 1.00   0.00   18168.13   15552.37   6774.89   5109.19   0.00
Maximum of Months 0.247646E+11 0.756370E+10 743.15 0.155398E+11 0.922480E+10 0.00 1.00   0.00   18946.67   16506.28   9505.20   5993.77   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ_OR_2 HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.145619E+11 0.411018E+10 741.68 0.109578E+11 0.360413E+10 0.00 1.00 01-JAN-06:01 0.00 01-JAN-06:02 19018.16 02-JAN-14:00 16974.33 01-JAN-06:01 8129.95 02-JAN-14:00 5719.27 02-JAN-14:00 0.00
February 0.144427E+11 0.411992E+10 669.02 0.107967E+11 0.364601E+10 0.00 1.00 01-FEB-06:01 0.00 01-FEB-17:01 18975.26 11-FEB-06:02 16890.99 05-FEB-06:01 6946.96 11-FEB-09:10 5308.87 11-FEB-06:02 0.00
March 0.171573E+11 0.489034E+10 742.55 0.125358E+11 0.462145E+10 0.00 1.00 01-MAR-06:01 0.00 01-MAR-17:01 18950.81 06-MAR-06:01 16654.92 12-MAR-05:01 8180.06 14-MAR-09:20 5424.79 14-MAR-10:00 0.00
April 0.185045E+11 0.539151E+10 718.59 0.132398E+11 0.526471E+10 0.00 1.00 01-APR-05:01 0.00 01-APR-16:01 18889.19 12-APR-05:02 16868.28 02-APR-05:01 7852.71 25-APR-14:00 5855.03 14-APR-14:40 0.00
May 0.222900E+11 0.671807E+10 742.63 0.149829E+11 0.730712E+10 0.00 1.00 01-MAY-05:02 0.00 01-MAY-16:01 19216.11 31-MAY-07:00 16574.96 07-MAY-05:01 8866.25 31-MAY-06:50 6072.97 22-MAY-14:00 0.00
June 0.240653E+11 0.729862E+10 718.87 0.151394E+11 0.892589E+10 0.00 1.00 01-JUN-05:02 0.00 01-JUN-16:01 19533.86 28-JUN-11:40 16543.89 25-JUN-05:01 9225.69 28-JUN-11:30 5939.61 06-JUN-13:00 0.00
July 0.242082E+11 0.747383E+10 742.74 0.154096E+11 0.879864E+10 0.00 1.00 01-JUL-05:02 0.00 01-JUL-16:01 19657.60 25-JUL-14:55 16553.85 02-JUL-05:01 9651.08 29-JUL-08:70 6253.28 28-JUL-16:03 0.00
August 0.253311E+11 0.773652E+10 742.90 0.158189E+11 0.951223E+10 0.00 1.00 01-AUG-05:02 0.00 01-AUG-16:01 19644.13 21-AUG-12:00 16586.99 06-AUG-05:01 9480.79 26-AUG-08:70 6154.59 23-AUG-13:00 0.00
September 0.233290E+11 0.708849E+10 718.75 0.147620E+11 0.856700E+10 0.00 1.00 01-SEP-05:02 0.00 01-SEP-16:01 19602.95 22-SEP-16:03 16727.51 04-SEP-05:01 9300.04 22-SEP-07:00 6030.73 20-SEP-16:03 0.00
October 0.219443E+11 0.659074E+10 742.55 0.145158E+11 0.742855E+10 0.00 1.00 01-OCT-05:01 0.00 01-OCT-16:01 19618.77 04-OCT-08:00 16782.35 22-OCT-05:01 9950.55 04-OCT-06:01 5981.42 02-OCT-14:00 0.00
November 0.189692E+11 0.551649E+10 718.23 0.128231E+11 0.614609E+10 0.00 1.00 01-NOV-05:01 0.00 01-NOV-16:01 19325.45 29-NOV-12:00 17133.49 12-NOV-06:01 9149.26 29-NOV-11:20 5755.71 03-NOV-14:00 0.00
December 0.151484E+11 0.428548E+10 741.86 0.111032E+11 0.404515E+10 0.00 1.00 01-DEC-06:02 0.00 01-DEC-17:01 18984.95 23-DEC-06:01 16682.99 17-DEC-06:01 7565.93 23-DEC-09:10 5375.92 09-DEC-06:02 0.00
                                       
Annual Sum or Average 0.239952E+12 0.712202E+11 8740.36 0.162085E+12 0.778670E+11 0.00                         0.00
Minimum of Months 0.144427E+11 0.411018E+10 669.02 0.107967E+11 0.360413E+10 0.00 1.00   0.00   18889.19   16543.89   6946.96   5308.87   0.00
Maximum of Months 0.253311E+11 0.773652E+10 742.90 0.158189E+11 0.951223E+10 0.00 1.00   0.00   19657.60   17133.49   9950.55   6253.28   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ_OR_3 HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.141936E+11 0.400654E+10 741.58 0.107145E+11 0.347910E+10 0.00 1.00 01-JAN-06:01 0.00 01-JAN-06:02 18661.09 07-JAN-06:01 17019.52 01-JAN-06:01 7839.96 02-JAN-14:00 5391.03 02-JAN-14:00 0.00
February 0.139118E+11 0.396576E+10 669.83 0.104343E+11 0.347753E+10 0.00 1.00 01-FEB-06:01 0.00 01-FEB-17:01 18645.73 11-FEB-06:02 16932.65 20-FEB-06:01 6625.21 11-FEB-09:10 5229.57 11-FEB-06:02 0.00
March 0.163426E+11 0.465148E+10 742.28 0.119562E+11 0.438641E+10 0.00 1.00 01-MAR-06:01 0.00 01-MAR-17:01 18652.43 06-MAR-06:01 16871.70 12-MAR-05:01 7760.08 14-MAR-09:20 5182.73 14-MAR-05:01 0.00
April 0.171892E+11 0.499040E+10 718.16 0.122123E+11 0.497693E+10 0.00 1.00 01-APR-05:01 0.00 01-APR-16:01 18665.55 14-APR-05:02 16881.60 02-APR-05:01 7587.54 25-APR-14:00 5601.06 14-APR-14:30 0.00
May 0.205230E+11 0.615711E+10 742.25 0.136250E+11 0.689801E+10 0.00 1.00 01-MAY-05:02 0.00 01-MAY-16:01 18896.48 31-MAY-05:02 16866.87 07-MAY-05:01 8518.20 24-MAY-10:00 5923.29 31-MAY-13:00 0.00
June 0.222528E+11 0.672420E+10 718.34 0.137093E+11 0.854356E+10 0.00 1.00 01-JUN-05:02 0.00 01-JUN-16:01 19259.78 28-JUN-11:40 16612.10 25-JUN-05:01 9238.74 28-JUN-11:30 5877.78 06-JUN-13:00 0.00
July 0.223601E+11 0.689113E+10 742.08 0.138555E+11 0.850462E+10 0.00 1.00 01-JUL-05:02 0.00 01-JUL-16:01 19360.29 25-JUL-14:55 16669.53 04-JUL-05:01 9363.57 25-JUL-14:55 6178.66 27-JUL-16:00 0.00
August 0.236061E+11 0.719334E+10 742.35 0.144111E+11 0.919493E+10 0.00 1.00 01-AUG-05:02 0.00 01-AUG-16:01 19320.53 21-AUG-12:05 16584.72 06-AUG-05:01 9437.10 21-AUG-12:00 6088.93 23-AUG-13:00 0.00
September 0.214629E+11 0.649725E+10 718.12 0.132585E+11 0.820434E+10 0.00 1.00 01-SEP-05:02 0.00 01-SEP-16:01 19214.83 22-SEP-07:20 16740.42 04-SEP-05:01 9299.12 22-SEP-07:00 5965.55 20-SEP-14:00 0.00
October 0.202515E+11 0.605876E+10 741.88 0.131746E+11 0.707686E+10 0.00 1.00 01-OCT-05:01 0.00 01-OCT-16:01 19383.57 04-OCT-08:00 16811.33 09-OCT-05:01 9937.91 04-OCT-06:01 5922.24 02-OCT-14:00 0.00
November 0.179276E+11 0.519886E+10 717.98 0.120604E+11 0.586729E+10 0.00 1.00 01-NOV-05:01 0.00 01-NOV-16:01 18881.50 30-NOV-06:02 17008.71 12-NOV-06:01 8932.18 29-NOV-12:00 5486.80 30-NOV-12:00 0.00
December 0.147783E+11 0.417509E+10 741.71 0.108809E+11 0.389739E+10 0.00 1.00 01-DEC-06:02 0.00 01-DEC-17:01 18677.01 23-DEC-06:01 16909.89 25-DEC-06:01 7469.99 23-DEC-09:10 5306.93 09-DEC-06:02 0.00
                                       
Annual Sum or Average 0.224800E+12 0.665099E+11 8736.55 0.150293E+12 0.745070E+11 0.00                         0.00
Minimum of Months 0.139118E+11 0.396576E+10 669.83 0.104343E+11 0.347753E+10 0.00 1.00   0.00   18645.73   16584.72   6625.21   5182.73   0.00
Maximum of Months 0.236061E+11 0.719334E+10 742.35 0.144111E+11 0.919493E+10 0.00 1.00   0.00   19383.57   17019.52   9937.91   6178.66   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ_XRAY HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.167659E+11 0.414890E+10 731.59 0.146760E+11 0.208993E+10 0.00 1.00 02-JAN-06:12 0.00 02-JAN-18:01 22306.77 14-JAN-05:01 19624.06 27-JAN-07:01 10120.92 14-JAN-05:01 5308.81 14-JAN-05:01 0.00
February 0.158539E+11 0.397308E+10 667.58 0.137547E+11 0.209923E+10 0.00 1.00 01-FEB-06:12 0.00 01-FEB-18:01 24501.65 11-FEB-05:01 19485.47 24-FEB-07:01 12420.61 11-FEB-05:01 5800.49 11-FEB-05:01 0.00
March 0.186412E+11 0.465342E+10 739.60 0.159707E+11 0.267050E+10 0.00 1.00 01-MAR-06:12 0.00 01-MAR-18:01 21889.04 22-MAR-06:01 19396.70 15-MAR-06:01 7142.38 09-MAR-18:04 5207.23 22-MAR-06:01 0.00
April 0.185137E+11 0.473458E+10 719.09 0.154100E+11 0.310367E+10 0.00 1.00 01-APR-05:12 0.00 01-APR-14:01 22787.43 12-APR-04:01 17938.12 19-APR-06:01 10866.89 12-APR-04:01 5599.09 12-APR-06:02 0.00
May 0.215804E+11 0.565581E+10 743.21 0.168644E+11 0.471592E+10 0.00 1.00 01-MAY-05:12 0.00 01-MAY-17:01 25222.30 31-MAY-04:01 19195.21 08-MAY-05:01 14535.58 31-MAY-04:01 5903.49 20-MAY-04:01 0.00
June 0.230358E+11 0.606541E+10 719.21 0.169699E+11 0.606591E+10 0.00 1.00 01-JUN-04:01 0.00 01-JUN-17:01 25480.32 23-JUN-04:01 17918.15 06-JUN-05:02 14478.65 07-JUN-04:02 6098.86 08-JUN-04:01 0.00
July 0.227365E+11 0.611568E+10 743.29 0.167966E+11 0.593992E+10 0.00 1.00 01-JUL-04:01 0.00 01-JUL-04:02 25618.20 12-JUL-04:01 17036.20 28-JUL-17:02 14538.02 03-JUL-04:01 6277.30 26-JUL-17:03 0.00
August 0.242702E+11 0.645002E+10 743.26 0.177694E+11 0.650085E+10 0.00 1.00 01-AUG-04:01 0.00 01-AUG-17:01 25510.38 15-AUG-04:01 16531.97 11-AUG-06:01 14362.36 10-AUG-04:01 6070.64 01-AUG-04:01 0.00
September 0.219777E+11 0.581016E+10 719.26 0.162879E+11 0.568987E+10 0.00 1.00 01-SEP-04:02 0.00 01-SEP-17:01 25572.22 22-SEP-04:02 16792.45 01-SEP-06:01 14232.97 13-SEP-04:01 6090.50 21-SEP-17:03 0.00
October 0.210626E+11 0.551496E+10 743.29 0.162897E+11 0.477291E+10 0.00 1.00 02-OCT-04:02 0.00 02-OCT-17:01 25717.65 04-OCT-04:01 17917.41 26-OCT-05:02 16960.52 04-OCT-04:12 5969.34 02-OCT-04:02 0.00
November 0.193104E+11 0.491334E+10 719.26 0.154295E+11 0.388099E+10 0.00 1.00 01-NOV-05:12 0.00 01-NOV-17:01 25295.92 30-NOV-05:02 19314.03 13-NOV-07:01 14470.77 04-NOV-04:01 5935.43 30-NOV-05:02 0.00
December 0.169758E+11 0.421417E+10 730.77 0.146111E+11 0.236471E+10 0.00 1.00 01-DEC-06:12 0.00 01-DEC-18:01 24607.42 09-DEC-05:01 19475.78 20-DEC-07:01 11865.23 09-DEC-05:01 5870.32 09-DEC-05:01 0.00
                                       
Annual Sum or Average 0.240724E+12 0.622495E+11 8719.42 0.190830E+12 0.498944E+11 0.00                         0.00
Minimum of Months 0.158539E+11 0.397308E+10 667.58 0.137547E+11 0.208993E+10 0.00 1.00   0.00   21889.04   16531.97   7142.38   5207.23   0.00
Maximum of Months 0.242702E+11 0.645002E+10 743.29 0.177694E+11 0.650085E+10 0.00 1.00   0.00   25717.65   19624.06   16960.52   6277.30   0.00



Table of Contents

Report: WindowReportMonthly

For: 78F987

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.98 24.52 13.47 102.69 33.08 0.00 0.00 0.00
February 35.10 20.44 14.66 100.71 25.57 0.00 0.00 0.00
March 27.98 12.57 15.41 82.50 18.62 0.00 0.00 0.00
April 19.26 4.29 14.97 72.54 6.74 0.00 0.00 0.00
May 14.78 0.55 14.24 76.74 0.99 0.00 0.00 0.00
June 13.90 0.05 13.85 84.95 0.03 0.00 0.00 0.00
July 14.96 0.25 14.72 92.34 0.14 0.00 0.00 0.00
August 17.41 1.98 15.44 95.11 0.01 0.00 0.00 0.00
September 22.50 6.21 16.29 111.71 0.21 0.00 0.00 0.00
October 30.38 14.62 15.75 117.99 1.49 0.00 0.00 0.00
November 33.60 18.68 14.92 109.87 12.20 0.00 0.00 0.00
December 36.45 22.77 13.68 102.67 27.45 0.00 0.00 0.00
                 
Annual Sum or Average 25.31 10.53 14.78 95.79 10.48 0.00 0.00 0.00
Minimum of Months 13.90 0.05 13.47 72.54 0.01 0.00 0.00 0.00
Maximum of Months 37.98 24.52 16.29 117.99 33.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: D8037E

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 131.07 82.89 48.18 333.15 178.04 10.17 0.00 0.00
February 122.59 69.80 52.79 325.95 146.64 0.00 0.00 0.00
March 101.72 44.89 56.83 267.08 118.36 0.00 0.00 0.00
April 72.81 16.70 56.12 226.95 69.66 0.00 0.00 0.00
May 55.50 2.19 53.31 209.43 26.89 0.00 0.00 0.00
June 51.82 0.22 51.61 217.86 9.45 0.00 0.00 0.00
July 55.93 0.98 54.95 245.36 15.13 0.00 0.00 0.00
August 65.47 7.69 57.78 250.59 11.97 0.00 0.00 0.00
September 83.21 22.89 60.32 320.74 21.11 0.00 0.00 0.00
October 107.92 50.53 57.39 349.57 38.28 0.00 0.00 0.00
November 116.85 63.31 53.54 336.84 86.48 0.00 0.00 0.00
December 132.68 83.07 49.61 345.40 150.02 0.17 0.00 0.00
                 
Annual Sum or Average 91.32 36.95 54.37 285.52 72.35 10.33 0.00 0.00
Minimum of Months 51.82 0.22 48.18 209.43 9.45 0.00 0.00 0.00
Maximum of Months 132.68 83.07 60.32 349.57 178.04 10.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 4A8120

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.91 0.00 7.91 14.64 38.19 0.00 0.00 0.00
February 9.38 0.00 9.38 22.88 29.64 0.00 0.00 0.00
March 11.19 0.00 11.19 27.32 22.89 0.00 0.00 0.00
April 12.44 0.03 12.41 41.09 11.16 0.00 0.00 0.00
May 13.82 0.50 13.32 58.17 2.84 0.00 0.00 0.00
June 14.72 1.00 13.72 70.01 0.69 0.00 0.00 0.00
July 14.85 0.62 14.23 73.29 1.43 0.00 0.00 0.00
August 13.43 0.10 13.33 63.27 0.90 0.00 0.00 0.00
September 12.06 0.00 12.06 60.72 2.85 0.00 0.00 0.00
October 10.14 0.00 10.14 43.20 4.92 0.00 0.00 0.00
November 8.80 0.00 8.80 28.99 16.05 0.00 0.00 0.00
December 7.80 0.00 7.80 16.70 31.86 0.00 0.00 0.00
                 
Annual Sum or Average 11.39 0.19 11.20 43.45 13.55 0.00 0.00 0.00
Minimum of Months 7.80 0.00 7.80 14.64 0.69 0.00 0.00 0.00
Maximum of Months 14.85 1.00 14.23 73.29 38.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: AAE778

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 69.90 30.74 39.16 163.91 166.71 0.00 0.00 0.00
February 87.14 39.97 47.17 226.50 136.51 0.00 0.00 0.00
March 108.19 49.82 58.37 280.47 112.08 0.00 0.00 0.00
April 118.89 55.37 63.52 352.31 64.95 0.00 0.00 0.00
May 108.47 42.25 66.23 369.72 23.33 0.00 0.00 0.00
June 91.80 26.27 65.54 354.94 6.96 0.00 0.00 0.00
July 102.83 32.42 70.41 404.69 11.77 0.00 0.00 0.00
August 102.45 33.92 68.53 373.89 7.49 0.00 0.00 0.00
September 87.32 26.24 61.08 344.15 16.98 0.00 0.00 0.00
October 87.16 34.50 52.66 295.71 30.10 0.00 0.00 0.00
November 72.08 27.06 45.02 217.19 76.27 0.00 0.00 0.00
December 72.44 33.06 39.38 181.01 139.95 0.00 0.00 0.00
                 
Annual Sum or Average 92.43 35.96 56.47 297.40 65.78 0.00 0.00 0.00
Minimum of Months 69.90 26.24 39.16 163.91 6.96 0.00 0.00 0.00
Maximum of Months 118.89 55.37 70.41 404.69 166.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 3AAD8B

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 8.87 0.00 8.87 15.39 55.49 0.00 0.00 0.00
February 10.52 0.00 10.52 24.54 44.59 0.00 0.00 0.00
March 12.57 0.00 12.57 29.50 35.72 0.00 0.00 0.00
April 13.89 0.03 13.87 45.73 17.99 0.00 0.00 0.00
May 15.69 0.58 15.11 67.21 5.18 0.00 0.00 0.00
June 16.50 0.90 15.60 81.25 1.22 0.00 0.00 0.00
July 16.80 0.68 16.12 87.18 2.01 0.00 0.00 0.00
August 15.06 0.09 14.97 74.69 1.50 0.00 0.00 0.00
September 13.54 0.00 13.54 72.67 3.71 0.00 0.00 0.00
October 11.34 0.00 11.34 50.70 6.89 0.00 0.00 0.00
November 9.88 0.00 9.88 32.61 23.47 0.00 0.00 0.00
December 8.76 0.00 8.76 18.01 46.25 0.00 0.00 0.00
                 
Annual Sum or Average 12.80 0.19 12.61 50.08 20.23 0.00 0.00 0.00
Minimum of Months 8.76 0.00 8.76 15.39 1.22 0.00 0.00 0.00
Maximum of Months 16.80 0.90 16.12 87.18 55.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 8128A9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.69 0.00 9.69 16.70 56.63 0.00 0.00 0.00
February 11.48 0.00 11.48 26.23 45.64 0.00 0.00 0.00
March 13.70 0.00 13.70 31.70 36.69 0.00 0.00 0.00
April 15.11 0.02 15.09 48.31 19.02 0.00 0.00 0.00
May 17.34 0.79 16.55 71.17 5.81 0.00 0.00 0.00
June 18.67 1.44 17.24 86.86 1.51 0.00 0.00 0.00
July 18.82 1.02 17.80 92.33 2.43 0.00 0.00 0.00
August 16.50 0.11 16.39 77.26 1.71 0.00 0.00 0.00
September 14.83 0.00 14.83 75.41 4.24 0.00 0.00 0.00
October 12.42 0.00 12.42 52.62 7.73 0.00 0.00 0.00
November 10.82 0.00 10.82 34.38 24.45 0.00 0.00 0.00
December 9.59 0.00 9.59 19.52 47.14 0.00 0.00 0.00
                 
Annual Sum or Average 14.09 0.28 13.81 52.83 20.98 0.00 0.00 0.00
Minimum of Months 9.59 0.00 9.59 16.70 1.51 0.00 0.00 0.00
Maximum of Months 18.82 1.44 17.80 92.33 56.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 9B1541

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.98 24.52 13.47 109.58 30.94 0.00 0.00 0.00
February 35.10 20.44 14.66 106.96 24.81 0.00 0.00 0.00
March 27.98 12.57 15.41 86.88 18.72 0.00 0.00 0.00
April 19.26 4.29 14.97 74.12 8.50 0.00 0.00 0.00
May 14.78 0.55 14.24 73.95 1.64 0.00 0.00 0.00
June 13.90 0.05 13.85 79.50 0.26 0.00 0.00 0.00
July 14.96 0.25 14.72 85.43 0.77 0.00 0.00 0.00
August 17.41 1.98 15.44 88.87 0.26 0.00 0.00 0.00
September 22.50 6.21 16.29 107.81 1.49 0.00 0.00 0.00
October 30.38 14.62 15.75 118.39 2.76 0.00 0.00 0.00
November 33.60 18.68 14.92 114.28 12.19 0.00 0.00 0.00
December 36.45 22.77 13.68 109.20 25.63 0.00 0.00 0.00
                 
Annual Sum or Average 25.31 10.53 14.78 96.19 10.60 0.00 0.00 0.00
Minimum of Months 13.90 0.05 13.47 73.95 0.26 0.00 0.00 0.00
Maximum of Months 37.98 24.52 16.29 118.39 30.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CF850A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.98 24.52 13.47 109.58 30.94 0.00 0.00 0.00
February 35.10 20.44 14.66 106.96 24.81 0.00 0.00 0.00
March 27.98 12.57 15.41 86.88 18.72 0.00 0.00 0.00
April 19.26 4.29 14.97 74.12 8.50 0.00 0.00 0.00
May 14.78 0.55 14.24 73.92 1.65 0.00 0.00 0.00
June 13.90 0.05 13.85 79.47 0.26 0.00 0.00 0.00
July 14.96 0.25 14.72 85.41 0.77 0.00 0.00 0.00
August 17.41 1.98 15.44 88.87 0.26 0.00 0.00 0.00
September 22.50 6.21 16.29 107.81 1.49 0.00 0.00 0.00
October 30.38 14.62 15.75 118.39 2.76 0.00 0.00 0.00
November 33.60 18.68 14.92 114.28 12.19 0.00 0.00 0.00
December 36.45 22.77 13.68 109.20 25.63 0.00 0.00 0.00
                 
Annual Sum or Average 25.31 10.53 14.78 96.18 10.60 0.00 0.00 0.00
Minimum of Months 13.90 0.05 13.47 73.92 0.26 0.00 0.00 0.00
Maximum of Months 37.98 24.52 16.29 118.39 30.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: A6BA23

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 72.61 41.42 0.00 0.00 0.00
February 30.33 14.02 16.31 90.38 32.68 0.00 0.00 0.00
March 36.81 17.27 19.55 107.76 24.09 0.00 0.00 0.00
April 40.05 17.77 22.28 137.97 11.25 0.00 0.00 0.00
May 37.92 15.02 22.91 152.83 2.19 0.00 0.00 0.00
June 37.44 14.30 23.14 164.46 0.37 0.00 0.00 0.00
July 38.54 13.85 24.68 172.40 1.05 0.00 0.00 0.00
August 35.20 11.70 23.50 152.66 0.37 0.00 0.00 0.00
September 33.93 12.20 21.73 151.68 2.03 0.00 0.00 0.00
October 31.22 13.38 17.83 126.15 3.79 0.00 0.00 0.00
November 25.46 10.17 15.29 91.85 16.12 0.00 0.00 0.00
December 20.68 7.40 13.29 61.84 34.29 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 123.68 14.06 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 61.84 0.37 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 172.40 41.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: D10D28

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 72.27 41.55 0.00 0.00 0.00
February 30.33 14.02 16.31 90.19 32.70 0.00 0.00 0.00
March 36.81 17.27 19.55 107.75 24.09 0.00 0.00 0.00
April 40.05 17.77 22.28 137.97 11.25 0.00 0.00 0.00
May 37.92 15.02 22.91 152.83 2.19 0.00 0.00 0.00
June 37.44 14.30 23.14 164.46 0.37 0.00 0.00 0.00
July 38.54 13.85 24.68 172.40 1.05 0.00 0.00 0.00
August 35.20 11.70 23.50 152.66 0.37 0.00 0.00 0.00
September 33.93 12.20 21.73 151.68 2.03 0.00 0.00 0.00
October 31.22 13.38 17.83 126.09 3.79 0.00 0.00 0.00
November 25.46 10.17 15.29 91.58 16.12 0.00 0.00 0.00
December 20.68 7.40 13.29 61.34 34.38 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 123.57 14.08 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 61.34 0.37 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 172.40 41.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 591336

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 73.54 41.28 0.00 0.00 0.00
February 30.33 14.02 16.31 91.46 32.56 0.00 0.00 0.00
March 36.81 17.27 19.55 108.56 24.23 0.00 0.00 0.00
April 40.05 17.77 22.28 138.58 11.45 0.00 0.00 0.00
May 37.92 15.02 22.91 153.66 2.24 0.00 0.00 0.00
June 37.44 14.30 23.14 165.86 0.37 0.00 0.00 0.00
July 38.54 13.85 24.68 174.25 1.01 0.00 0.00 0.00
August 35.20 11.70 23.50 155.12 0.32 0.00 0.00 0.00
September 33.93 12.20 21.73 154.66 1.85 0.00 0.00 0.00
October 31.22 13.38 17.83 128.96 3.46 0.00 0.00 0.00
November 25.46 10.17 15.29 93.77 15.83 0.00 0.00 0.00
December 20.68 7.40 13.29 62.81 33.98 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 125.24 13.97 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 62.81 0.32 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 174.25 41.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 38B811

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 73.54 41.28 0.00 0.00 0.00
February 30.33 14.02 16.31 91.46 32.56 0.00 0.00 0.00
March 36.81 17.27 19.55 108.56 24.23 0.00 0.00 0.00
April 40.05 17.77 22.28 138.58 11.45 0.00 0.00 0.00
May 37.92 15.02 22.91 153.66 2.24 0.00 0.00 0.00
June 37.44 14.30 23.14 165.86 0.37 0.00 0.00 0.00
July 38.54 13.85 24.68 174.25 1.01 0.00 0.00 0.00
August 35.20 11.70 23.50 155.12 0.32 0.00 0.00 0.00
September 33.93 12.20 21.73 154.66 1.85 0.00 0.00 0.00
October 31.22 13.38 17.83 128.96 3.46 0.00 0.00 0.00
November 25.46 10.17 15.29 93.77 15.83 0.00 0.00 0.00
December 20.68 7.40 13.29 62.81 33.98 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 125.24 13.97 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 62.81 0.32 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 174.25 41.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: C044D6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 73.54 41.28 0.00 0.00 0.00
February 30.33 14.02 16.31 91.46 32.56 0.00 0.00 0.00
March 36.81 17.27 19.55 108.56 24.23 0.00 0.00 0.00
April 40.05 17.77 22.28 138.58 11.45 0.00 0.00 0.00
May 37.92 15.02 22.91 153.66 2.24 0.00 0.00 0.00
June 37.44 14.30 23.14 165.86 0.37 0.00 0.00 0.00
July 38.54 13.85 24.68 174.25 1.01 0.00 0.00 0.00
August 35.20 11.70 23.50 155.12 0.32 0.00 0.00 0.00
September 33.93 12.20 21.73 154.66 1.85 0.00 0.00 0.00
October 31.22 13.38 17.83 128.96 3.46 0.00 0.00 0.00
November 25.46 10.17 15.29 93.77 15.83 0.00 0.00 0.00
December 20.68 7.40 13.29 62.81 33.98 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 125.24 13.97 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 62.81 0.32 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 174.25 41.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 1D94BE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.05 0.00 10.05 22.79 43.44 0.00 0.00 0.00
February 11.90 0.00 11.90 34.22 33.22 0.00 0.00 0.00
March 14.19 0.00 14.19 41.14 24.98 0.00 0.00 0.00
April 15.69 0.02 15.67 61.60 9.10 0.00 0.00 0.00
May 17.82 0.75 17.07 92.05 1.48 0.00 0.00 0.00
June 19.40 1.58 17.82 111.84 0.09 0.00 0.00 0.00
July 19.41 1.03 18.38 116.51 0.26 0.00 0.00 0.00
August 17.09 0.12 16.97 102.03 0.06 0.00 0.00 0.00
September 15.38 0.00 15.38 97.30 0.39 0.00 0.00 0.00
October 12.90 0.00 12.90 71.24 1.73 0.00 0.00 0.00
November 11.22 0.00 11.22 47.68 15.64 0.00 0.00 0.00
December 9.94 0.00 9.94 27.16 35.22 0.00 0.00 0.00
                 
Annual Sum or Average 14.59 0.29 14.30 68.96 13.72 0.00 0.00 0.00
Minimum of Months 9.94 0.00 9.94 22.79 0.06 0.00 0.00 0.00
Maximum of Months 19.41 1.58 18.38 116.51 43.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 18748E

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.94 0.00 9.94 22.63 43.23 0.00 0.00 0.00
February 11.77 0.00 11.77 34.02 33.04 0.00 0.00 0.00
March 14.04 0.00 14.04 40.88 24.82 0.00 0.00 0.00
April 15.55 0.03 15.53 61.40 8.96 0.00 0.00 0.00
May 17.38 0.61 16.77 90.92 1.44 0.00 0.00 0.00
June 18.77 1.36 17.42 110.04 0.08 0.00 0.00 0.00
July 18.84 0.83 18.01 114.87 0.24 0.00 0.00 0.00
August 16.87 0.11 16.76 101.72 0.05 0.00 0.00 0.00
September 15.20 0.00 15.20 97.02 0.36 0.00 0.00 0.00
October 12.76 0.00 12.76 71.12 1.67 0.00 0.00 0.00
November 11.09 0.00 11.09 47.50 15.52 0.00 0.00 0.00
December 9.83 0.00 9.83 26.97 35.07 0.00 0.00 0.00
                 
Annual Sum or Average 14.35 0.25 14.10 68.42 13.63 0.00 0.00 0.00
Minimum of Months 9.83 0.00 9.83 22.63 0.05 0.00 0.00 0.00
Maximum of Months 18.84 1.36 18.01 114.87 43.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 137A56

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 40.23 24.49 15.74 104.96 65.37 0.00 0.00 0.00
February 39.30 21.82 17.48 108.52 52.64 0.00 0.00 0.00
March 33.18 14.24 18.94 91.14 41.61 0.00 0.00 0.00
April 24.24 5.40 18.83 82.47 20.67 0.00 0.00 0.00
May 18.78 0.79 17.99 83.40 5.15 0.00 0.00 0.00
June 17.43 0.08 17.34 92.74 1.04 0.00 0.00 0.00
July 18.89 0.35 18.54 103.65 1.92 0.00 0.00 0.00
August 21.87 2.54 19.33 105.58 1.46 0.00 0.00 0.00
September 27.13 7.20 19.93 125.22 3.97 0.00 0.00 0.00
October 34.78 15.82 18.95 126.97 7.87 0.00 0.00 0.00
November 37.25 19.68 17.57 116.21 27.71 0.00 0.00 0.00
December 41.67 25.65 16.03 112.34 54.45 0.00 0.00 0.00
                 
Annual Sum or Average 29.52 11.46 18.06 104.40 23.53 0.00 0.00 0.00
Minimum of Months 17.43 0.08 15.74 82.47 1.04 0.00 0.00 0.00
Maximum of Months 41.67 25.65 19.93 126.97 65.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 8D508E

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.98 24.52 13.47 101.15 34.87 0.00 0.00 0.00
February 35.10 20.44 14.66 99.23 27.08 0.00 0.00 0.00
March 27.98 12.57 15.41 81.28 19.74 0.00 0.00 0.00
April 19.26 4.29 14.97 71.57 7.39 0.00 0.00 0.00
May 14.78 0.55 14.24 75.60 1.10 0.00 0.00 0.00
June 13.90 0.05 13.85 83.94 0.05 0.00 0.00 0.00
July 14.96 0.25 14.72 91.31 0.17 0.00 0.00 0.00
August 17.41 1.98 15.44 93.56 0.03 0.00 0.00 0.00
September 22.50 6.21 16.29 109.81 0.32 0.00 0.00 0.00
October 30.38 14.62 15.75 115.57 1.91 0.00 0.00 0.00
November 33.60 18.68 14.92 107.72 13.21 0.00 0.00 0.00
December 36.45 22.77 13.68 101.13 29.07 0.00 0.00 0.00
                 
Annual Sum or Average 25.31 10.53 14.78 94.29 11.18 0.00 0.00 0.00
Minimum of Months 13.90 0.05 13.47 71.57 0.03 0.00 0.00 0.00
Maximum of Months 37.98 24.52 16.29 115.57 34.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: B2D381

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.98 24.52 13.47 101.15 34.87 0.00 0.00 0.00
February 35.10 20.44 14.66 99.23 27.08 0.00 0.00 0.00
March 27.98 12.57 15.41 81.28 19.74 0.00 0.00 0.00
April 19.26 4.29 14.97 71.57 7.39 0.00 0.00 0.00
May 14.78 0.55 14.24 75.60 1.10 0.00 0.00 0.00
June 13.90 0.05 13.85 83.94 0.05 0.00 0.00 0.00
July 14.96 0.25 14.72 91.31 0.17 0.00 0.00 0.00
August 17.41 1.98 15.44 93.56 0.03 0.00 0.00 0.00
September 22.50 6.21 16.29 109.81 0.32 0.00 0.00 0.00
October 30.38 14.62 15.75 115.57 1.91 0.00 0.00 0.00
November 33.60 18.68 14.92 107.72 13.21 0.00 0.00 0.00
December 36.45 22.77 13.68 101.13 29.07 0.00 0.00 0.00
                 
Annual Sum or Average 25.31 10.53 14.78 94.29 11.18 0.00 0.00 0.00
Minimum of Months 13.90 0.05 13.47 71.57 0.03 0.00 0.00 0.00
Maximum of Months 37.98 24.52 16.29 115.57 34.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 1DA13A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.98 24.52 13.47 101.15 34.87 0.00 0.00 0.00
February 35.10 20.44 14.66 99.23 27.08 0.00 0.00 0.00
March 27.98 12.57 15.41 81.28 19.74 0.00 0.00 0.00
April 19.26 4.29 14.97 71.57 7.39 0.00 0.00 0.00
May 14.78 0.55 14.24 75.60 1.10 0.00 0.00 0.00
June 13.90 0.05 13.85 83.94 0.05 0.00 0.00 0.00
July 14.96 0.25 14.72 91.31 0.17 0.00 0.00 0.00
August 17.41 1.98 15.44 93.56 0.03 0.00 0.00 0.00
September 22.50 6.21 16.29 109.81 0.32 0.00 0.00 0.00
October 30.38 14.62 15.75 115.57 1.91 0.00 0.00 0.00
November 33.60 18.68 14.92 107.72 13.21 0.00 0.00 0.00
December 36.45 22.77 13.68 101.13 29.07 0.00 0.00 0.00
                 
Annual Sum or Average 25.31 10.53 14.78 94.29 11.18 0.00 0.00 0.00
Minimum of Months 13.90 0.05 13.47 71.57 0.03 0.00 0.00 0.00
Maximum of Months 37.98 24.52 16.29 115.57 34.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 44E54A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.98 24.52 13.47 101.15 34.87 0.00 0.00 0.00
February 35.10 20.44 14.66 99.23 27.08 0.00 0.00 0.00
March 27.98 12.57 15.41 81.28 19.74 0.00 0.00 0.00
April 19.26 4.29 14.97 71.57 7.39 0.00 0.00 0.00
May 14.78 0.55 14.24 75.60 1.10 0.00 0.00 0.00
June 13.90 0.05 13.85 83.94 0.05 0.00 0.00 0.00
July 14.96 0.25 14.72 91.31 0.17 0.00 0.00 0.00
August 17.41 1.98 15.44 93.56 0.03 0.00 0.00 0.00
September 22.50 6.21 16.29 109.81 0.32 0.00 0.00 0.00
October 30.38 14.62 15.75 115.57 1.91 0.00 0.00 0.00
November 33.60 18.68 14.92 107.72 13.21 0.00 0.00 0.00
December 36.45 22.77 13.68 101.13 29.07 0.00 0.00 0.00
                 
Annual Sum or Average 25.31 10.53 14.78 94.29 11.18 0.00 0.00 0.00
Minimum of Months 13.90 0.05 13.47 71.57 0.03 0.00 0.00 0.00
Maximum of Months 37.98 24.52 16.29 115.57 34.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 757D10

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.17 4.20 2.97 18.93 12.65 0.00 0.00 0.00
February 7.06 3.75 3.31 20.15 9.84 0.00 0.00 0.00
March 6.07 2.45 3.62 17.38 7.49 0.00 0.00 0.00
April 4.46 0.85 3.61 16.60 2.99 0.00 0.00 0.00
May 3.60 0.12 3.47 18.87 0.47 0.00 0.00 0.00
June 3.38 0.01 3.36 21.61 0.03 0.00 0.00 0.00
July 3.65 0.06 3.59 23.77 0.13 0.00 0.00 0.00
August 4.08 0.40 3.68 23.57 0.07 0.00 0.00 0.00
September 4.87 1.14 3.72 26.05 0.24 0.00 0.00 0.00
October 6.28 2.71 3.57 25.60 0.78 0.00 0.00 0.00
November 6.70 3.41 3.29 22.46 4.83 0.00 0.00 0.00
December 7.74 4.71 3.03 21.34 10.44 0.00 0.00 0.00
                 
Annual Sum or Average 5.41 1.98 3.44 21.37 4.14 0.00 0.00 0.00
Minimum of Months 3.38 0.01 2.97 16.60 0.03 0.00 0.00 0.00
Maximum of Months 7.74 4.71 3.72 26.05 12.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: E33BAE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.58 7.69 8.90 40.81 35.26 0.00 0.00 0.00
February 20.75 9.99 10.75 57.53 27.20 0.00 0.00 0.00
March 25.82 12.46 13.37 72.75 19.92 0.00 0.00 0.00
April 28.39 13.84 14.55 94.68 7.28 0.00 0.00 0.00
May 25.68 10.56 15.12 105.60 1.07 0.00 0.00 0.00
June 21.39 6.53 14.86 105.03 0.04 0.00 0.00 0.00
July 24.13 8.10 16.03 117.04 0.18 0.00 0.00 0.00
August 24.09 8.48 15.61 108.85 0.06 0.00 0.00 0.00
September 20.43 6.56 13.87 97.03 0.37 0.00 0.00 0.00
October 20.62 8.63 11.99 81.14 1.90 0.00 0.00 0.00
November 16.99 6.77 10.23 57.58 13.31 0.00 0.00 0.00
December 17.21 8.26 8.94 45.73 28.97 0.00 0.00 0.00
                 
Annual Sum or Average 21.85 8.99 12.86 82.11 11.23 0.00 0.00 0.00
Minimum of Months 16.58 6.53 8.90 40.81 0.04 0.00 0.00 0.00
Maximum of Months 28.39 13.84 16.03 117.04 35.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 24167A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.98 24.52 13.47 100.81 34.79 0.00 0.00 0.00
February 35.10 20.44 14.66 98.33 27.39 0.00 0.00 0.00
March 27.98 12.57 15.41 79.69 20.50 0.00 0.00 0.00
April 19.26 4.29 14.97 68.74 8.69 0.00 0.00 0.00
May 14.78 0.55 14.24 71.07 1.41 0.00 0.00 0.00
June 13.90 0.05 13.85 79.31 0.09 0.00 0.00 0.00
July 14.96 0.25 14.72 85.77 0.31 0.00 0.00 0.00
August 17.41 1.98 15.44 87.63 0.11 0.00 0.00 0.00
September 22.50 6.21 16.29 104.52 0.70 0.00 0.00 0.00
October 30.38 14.62 15.75 111.46 2.64 0.00 0.00 0.00
November 33.60 18.68 14.92 105.59 13.83 0.00 0.00 0.00
December 36.45 22.77 13.68 100.24 29.34 0.00 0.00 0.00
                 
Annual Sum or Average 25.31 10.53 14.78 91.06 11.59 0.00 0.00 0.00
Minimum of Months 13.90 0.05 13.47 68.74 0.09 0.00 0.00 0.00
Maximum of Months 37.98 24.52 16.29 111.46 34.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 2C0938

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.98 24.52 13.47 100.81 34.79 0.00 0.00 0.00
February 35.10 20.44 14.66 98.33 27.39 0.00 0.00 0.00
March 27.98 12.57 15.41 79.69 20.50 0.00 0.00 0.00
April 19.26 4.29 14.97 68.75 8.69 0.00 0.00 0.00
May 14.78 0.55 14.24 71.08 1.41 0.00 0.00 0.00
June 13.90 0.05 13.85 79.31 0.09 0.00 0.00 0.00
July 14.96 0.25 14.72 85.78 0.31 0.00 0.00 0.00
August 17.41 1.98 15.44 87.64 0.11 0.00 0.00 0.00
September 22.50 6.21 16.29 104.52 0.70 0.00 0.00 0.00
October 30.38 14.62 15.75 111.46 2.64 0.00 0.00 0.00
November 33.60 18.68 14.92 105.59 13.83 0.00 0.00 0.00
December 36.45 22.77 13.68 100.24 29.34 0.00 0.00 0.00
                 
Annual Sum or Average 25.31 10.53 14.78 91.06 11.59 0.00 0.00 0.00
Minimum of Months 13.90 0.05 13.47 68.75 0.09 0.00 0.00 0.00
Maximum of Months 37.98 24.52 16.29 111.46 34.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 8600DD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.98 24.52 13.47 101.18 35.45 0.00 0.00 0.00
February 35.10 20.44 14.66 98.29 28.42 0.00 0.00 0.00
March 27.98 12.57 15.41 78.71 22.19 0.00 0.00 0.00
April 19.26 4.29 14.97 66.63 10.48 0.00 0.00 0.00
May 14.78 0.55 14.24 66.38 2.02 0.00 0.00 0.00
June 13.90 0.05 13.85 73.17 0.28 0.00 0.00 0.00
July 14.96 0.25 14.72 80.51 0.74 0.00 0.00 0.00
August 17.41 1.98 15.44 83.53 0.24 0.00 0.00 0.00
September 22.50 6.21 16.29 102.30 1.51 0.00 0.00 0.00
October 30.38 14.62 15.75 111.39 3.25 0.00 0.00 0.00
November 33.60 18.68 14.92 105.67 14.10 0.00 0.00 0.00
December 36.45 22.77 13.68 100.75 29.69 0.00 0.00 0.00
                 
Annual Sum or Average 25.31 10.53 14.78 88.99 12.30 0.00 0.00 0.00
Minimum of Months 13.90 0.05 13.47 66.38 0.24 0.00 0.00 0.00
Maximum of Months 37.98 24.52 16.29 111.39 35.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: A1ED60

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 22.90 36.16 0.00 0.00 0.00
February 12.10 0.00 12.10 32.58 28.60 0.00 0.00 0.00
March 14.43 0.00 14.43 37.03 23.08 0.00 0.00 0.00
April 16.23 0.13 16.10 51.77 12.79 0.00 0.00 0.00
May 18.80 1.16 17.64 74.26 3.67 0.00 0.00 0.00
June 20.18 1.87 18.31 88.70 1.11 0.00 0.00 0.00
July 20.32 1.33 18.99 91.90 2.39 0.00 0.00 0.00
August 17.76 0.25 17.51 78.17 1.07 0.00 0.00 0.00
September 15.68 0.00 15.67 75.16 3.44 0.00 0.00 0.00
October 13.13 0.00 13.13 55.29 4.89 0.00 0.00 0.00
November 11.42 0.00 11.42 39.71 15.79 0.00 0.00 0.00
December 10.11 0.00 10.11 25.19 30.03 0.00 0.00 0.00
                 
Annual Sum or Average 15.05 0.40 14.65 56.16 13.52 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 22.90 1.07 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 91.90 36.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: E8D997

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 22.90 36.16 0.00 0.00 0.00
February 12.10 0.00 12.10 32.58 28.60 0.00 0.00 0.00
March 14.43 0.00 14.43 37.03 23.08 0.00 0.00 0.00
April 16.23 0.13 16.10 51.77 12.79 0.00 0.00 0.00
May 18.80 1.16 17.64 74.26 3.67 0.00 0.00 0.00
June 20.18 1.87 18.31 88.70 1.11 0.00 0.00 0.00
July 20.32 1.33 18.99 91.90 2.39 0.00 0.00 0.00
August 17.76 0.25 17.51 78.17 1.07 0.00 0.00 0.00
September 15.68 0.00 15.67 75.16 3.44 0.00 0.00 0.00
October 13.13 0.00 13.13 55.29 4.89 0.00 0.00 0.00
November 11.42 0.00 11.42 39.71 15.79 0.00 0.00 0.00
December 10.11 0.00 10.11 25.19 30.03 0.00 0.00 0.00
                 
Annual Sum or Average 15.05 0.40 14.65 56.16 13.52 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 22.90 1.07 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 91.90 36.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 88E1FC

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 22.90 36.16 0.00 0.00 0.00
February 12.10 0.00 12.10 32.58 28.60 0.00 0.00 0.00
March 14.43 0.00 14.43 37.03 23.08 0.00 0.00 0.00
April 16.23 0.13 16.10 51.77 12.79 0.00 0.00 0.00
May 18.80 1.16 17.64 74.26 3.67 0.00 0.00 0.00
June 20.18 1.87 18.31 88.70 1.11 0.00 0.00 0.00
July 20.32 1.33 18.99 91.90 2.39 0.00 0.00 0.00
August 17.76 0.25 17.51 78.17 1.07 0.00 0.00 0.00
September 15.68 0.00 15.67 75.16 3.44 0.00 0.00 0.00
October 13.13 0.00 13.13 55.29 4.89 0.00 0.00 0.00
November 11.42 0.00 11.42 39.71 15.79 0.00 0.00 0.00
December 10.11 0.00 10.11 25.19 30.03 0.00 0.00 0.00
                 
Annual Sum or Average 15.05 0.40 14.65 56.16 13.52 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 22.90 1.07 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 91.90 36.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: F83F33

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.17 16.90 18.27 83.83 59.29 0.00 0.00 0.00
February 40.44 18.70 21.75 105.82 46.33 0.00 0.00 0.00
March 49.09 23.02 26.06 127.60 35.81 0.00 0.00 0.00
April 53.40 23.69 29.71 165.27 19.58 0.00 0.00 0.00
May 50.56 20.02 30.54 181.54 4.67 0.00 0.00 0.00
June 49.92 19.07 30.85 196.46 1.11 0.00 0.00 0.00
July 51.38 18.47 32.91 207.94 2.53 0.00 0.00 0.00
August 46.93 15.60 31.33 182.98 1.20 0.00 0.00 0.00
September 45.23 16.26 28.97 182.59 4.48 0.00 0.00 0.00
October 41.62 17.84 23.78 149.94 7.68 0.00 0.00 0.00
November 33.95 13.56 20.38 106.02 24.19 0.00 0.00 0.00
December 27.58 9.86 17.71 69.87 49.37 0.00 0.00 0.00
                 
Annual Sum or Average 43.78 17.74 26.04 146.82 21.25 0.00 0.00 0.00
Minimum of Months 27.58 9.86 17.71 69.87 1.11 0.00 0.00 0.00
Maximum of Months 53.40 23.69 32.91 207.94 59.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: B1F5EE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.18 12.68 13.50 63.03 43.55 0.00 0.00 0.00
February 30.10 14.02 16.08 79.40 34.00 0.00 0.00 0.00
March 36.54 17.27 19.27 95.39 26.43 0.00 0.00 0.00
April 39.76 17.77 21.99 123.31 14.76 0.00 0.00 0.00
May 37.60 15.02 22.58 134.88 3.74 0.00 0.00 0.00
June 37.10 14.30 22.80 146.32 0.99 0.00 0.00 0.00
July 38.19 13.85 24.33 154.95 2.03 0.00 0.00 0.00
August 34.85 11.70 23.15 136.62 0.98 0.00 0.00 0.00
September 33.60 12.20 21.41 136.23 3.48 0.00 0.00 0.00
October 30.95 13.38 17.57 111.83 5.74 0.00 0.00 0.00
November 25.22 10.17 15.05 79.02 18.15 0.00 0.00 0.00
December 20.48 7.40 13.08 52.22 36.17 0.00 0.00 0.00
                 
Annual Sum or Average 32.55 13.30 19.25 109.55 15.76 0.00 0.00 0.00
Minimum of Months 20.48 7.40 13.08 52.22 0.98 0.00 0.00 0.00
Maximum of Months 39.76 17.77 24.33 154.95 43.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: F52F3D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 56.90 48.04 1.50 0.00 0.00
February 30.33 14.02 16.31 71.45 38.75 0.00 0.00 0.00
March 36.81 17.27 19.55 87.39 30.45 0.00 0.00 0.00
April 40.05 17.77 22.28 117.19 17.00 0.00 0.00 0.00
May 37.92 15.02 22.91 129.71 4.62 0.00 0.00 0.00
June 37.44 14.30 23.14 142.32 1.27 0.00 0.00 0.00
July 38.54 13.85 24.68 152.11 2.40 0.00 0.00 0.00
August 35.20 11.70 23.50 132.62 1.42 0.00 0.00 0.00
September 33.93 12.20 21.73 131.42 4.25 0.00 0.00 0.00
October 31.22 13.38 17.83 105.44 7.65 0.00 0.00 0.00
November 25.46 10.17 15.29 72.07 20.76 0.00 0.00 0.00
December 20.68 7.40 13.29 46.12 41.07 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 103.86 18.05 1.50 0.00 0.00
Minimum of Months 20.68 7.40 13.29 46.12 1.27 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 152.11 48.04 1.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 80885D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 113.95 73.55 40.41 285.10 107.66 1.50 0.00 0.00
February 105.30 61.33 43.97 273.07 89.01 0.00 0.00 0.00
March 83.95 37.70 46.24 215.14 72.14 0.00 0.00 0.00
April 57.78 12.86 44.92 180.94 39.90 0.00 0.00 0.00
May 44.35 1.64 42.71 176.52 10.89 0.00 0.00 0.00
June 41.70 0.16 41.54 194.78 2.93 0.00 0.00 0.00
July 44.89 0.74 44.15 215.93 5.54 0.00 0.00 0.00
August 52.24 5.93 46.31 224.35 3.23 0.00 0.00 0.00
September 67.50 18.62 48.88 278.77 9.76 0.00 0.00 0.00
October 91.14 43.87 47.26 305.32 17.37 0.00 0.00 0.00
November 100.79 56.03 44.77 292.67 47.63 0.00 0.00 0.00
December 109.36 68.32 41.05 282.50 91.54 0.00 0.00 0.00
                 
Annual Sum or Average 75.94 31.59 44.35 243.59 41.26 1.50 0.00 0.00
Minimum of Months 41.70 0.16 40.41 176.52 2.93 0.00 0.00 0.00
Maximum of Months 113.95 73.55 48.88 305.32 107.66 1.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FEEF06

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.98 24.52 13.47 97.09 36.09 0.00 0.00 0.00
February 35.10 20.44 14.66 92.49 30.34 0.00 0.00 0.00
March 27.98 12.57 15.41 72.56 25.39 0.00 0.00 0.00
April 19.26 4.29 14.97 60.63 14.81 0.00 0.00 0.00
May 14.78 0.55 14.24 59.29 4.00 0.00 0.00 0.00
June 13.90 0.05 13.85 66.71 0.90 0.00 0.00 0.00
July 14.96 0.25 14.72 73.56 1.78 0.00 0.00 0.00
August 17.41 1.98 15.44 76.03 1.06 0.00 0.00 0.00
September 22.50 6.21 16.29 95.21 3.05 0.00 0.00 0.00
October 30.38 14.62 15.75 103.87 5.61 0.00 0.00 0.00
November 33.60 18.68 14.92 99.41 16.06 0.00 0.00 0.00
December 36.45 22.77 13.68 95.67 30.89 0.00 0.00 0.00
                 
Annual Sum or Average 25.31 10.53 14.78 82.65 14.09 0.00 0.00 0.00
Minimum of Months 13.90 0.05 13.47 59.29 0.90 0.00 0.00 0.00
Maximum of Months 37.98 24.52 16.29 103.87 36.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 2BE8DE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.87 7.69 9.18 39.74 38.05 0.00 0.00 0.00
February 21.08 9.99 11.09 54.57 31.45 0.00 0.00 0.00
March 26.22 12.46 13.76 67.49 25.86 0.00 0.00 0.00
April 28.79 13.84 14.95 86.78 13.64 0.00 0.00 0.00
May 26.16 10.56 15.59 93.63 3.51 0.00 0.00 0.00
June 21.91 6.53 15.38 92.72 0.69 0.00 0.00 0.00
July 24.63 8.10 16.53 105.01 1.47 0.00 0.00 0.00
August 24.60 8.48 16.13 97.71 0.85 0.00 0.00 0.00
September 20.91 6.56 14.35 89.31 2.62 0.00 0.00 0.00
October 20.99 8.63 12.36 75.43 4.99 0.00 0.00 0.00
November 17.35 6.77 10.58 54.15 16.32 0.00 0.00 0.00
December 17.52 8.26 9.25 43.98 31.72 0.00 0.00 0.00
                 
Annual Sum or Average 22.26 8.99 13.27 75.15 14.19 0.00 0.00 0.00
Minimum of Months 16.87 6.53 9.18 39.74 0.69 0.00 0.00 0.00
Maximum of Months 28.79 13.84 16.53 105.01 38.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 513E2A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.84 7.69 8.15 38.20 36.41 0.00 0.00 0.00
February 19.88 9.99 9.88 52.62 29.87 0.00 0.00 0.00
March 24.80 12.46 12.34 64.96 24.41 0.00 0.00 0.00
April 26.17 12.99 13.18 81.02 12.34 0.00 0.00 0.00
May 21.40 8.35 13.05 81.92 2.76 0.00 0.00 0.00
June 17.49 4.65 12.84 82.08 0.47 0.00 0.00 0.00
July 20.15 6.29 13.87 93.99 1.06 0.00 0.00 0.00
August 21.54 7.71 13.83 91.62 0.68 0.00 0.00 0.00
September 19.21 6.56 12.66 86.13 1.90 0.00 0.00 0.00
October 19.64 8.63 11.02 73.54 3.89 0.00 0.00 0.00
November 16.11 6.77 9.34 52.15 15.06 0.00 0.00 0.00
December 16.44 8.26 8.17 42.09 30.41 0.00 0.00 0.00
                 
Annual Sum or Average 19.89 8.35 11.54 70.11 13.20 0.00 0.00 0.00
Minimum of Months 15.84 4.65 8.15 38.20 0.47 0.00 0.00 0.00
Maximum of Months 26.17 12.99 13.87 93.99 36.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BA5CD9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.54 7.69 8.85 39.20 37.60 0.00 0.00 0.00
February 20.69 9.99 10.70 53.93 30.95 0.00 0.00 0.00
March 25.76 12.46 13.30 66.67 25.39 0.00 0.00 0.00
April 28.31 13.84 14.47 85.89 13.18 0.00 0.00 0.00
May 24.87 10.11 14.76 90.53 3.26 0.00 0.00 0.00
June 20.51 5.96 14.54 89.35 0.61 0.00 0.00 0.00
July 23.26 7.64 15.62 101.68 1.34 0.00 0.00 0.00
August 23.97 8.46 15.51 96.73 0.78 0.00 0.00 0.00
September 20.37 6.56 13.80 88.29 2.38 0.00 0.00 0.00
October 20.55 8.63 11.93 74.80 4.62 0.00 0.00 0.00
November 16.95 6.77 10.18 53.46 15.92 0.00 0.00 0.00
December 17.17 8.26 8.90 43.31 31.33 0.00 0.00 0.00
                 
Annual Sum or Average 21.59 8.86 12.73 73.76 13.87 0.00 0.00 0.00
Minimum of Months 16.54 5.96 8.85 39.20 0.61 0.00 0.00 0.00
Maximum of Months 28.31 13.84 15.62 101.68 37.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 1AD478

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 63.31 40.86 22.45 163.70 63.72 0.00 0.00 0.00
February 58.50 34.07 24.43 157.82 52.31 0.00 0.00 0.00
March 46.64 20.95 25.69 126.08 41.55 0.00 0.00 0.00
April 32.10 7.14 24.96 110.53 20.37 0.00 0.00 0.00
May 24.64 0.91 23.73 114.30 4.34 0.00 0.00 0.00
June 23.17 0.09 23.08 129.41 0.74 0.00 0.00 0.00
July 24.94 0.41 24.53 142.50 1.56 0.00 0.00 0.00
August 29.02 3.29 25.73 146.16 0.71 0.00 0.00 0.00
September 37.50 10.34 27.16 176.04 3.17 0.00 0.00 0.00
October 50.63 24.37 26.26 186.30 6.53 0.00 0.00 0.00
November 56.00 31.13 24.87 172.39 26.78 0.00 0.00 0.00
December 60.76 37.95 22.80 162.82 54.09 0.00 0.00 0.00
                 
Annual Sum or Average 42.19 17.55 24.64 148.95 22.86 0.00 0.00 0.00
Minimum of Months 23.17 0.09 22.45 110.53 0.71 0.00 0.00 0.00
Maximum of Months 63.31 40.86 27.16 186.30 63.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 27F0AC

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 101.29 65.37 35.92 263.41 98.05 0.00 0.00 0.00
February 93.60 54.52 39.08 254.47 79.61 0.00 0.00 0.00
March 74.62 33.52 41.10 204.37 62.09 0.00 0.00 0.00
April 51.36 11.43 39.93 180.67 28.21 0.00 0.00 0.00
May 39.42 1.46 37.96 189.26 5.32 0.00 0.00 0.00
June 37.07 0.14 36.93 213.53 0.78 0.00 0.00 0.00
July 39.90 0.65 39.24 234.51 1.89 0.00 0.00 0.00
August 46.43 5.27 41.16 240.61 0.63 0.00 0.00 0.00
September 60.00 16.55 43.45 287.16 3.67 0.00 0.00 0.00
October 81.01 39.00 42.01 303.20 8.32 0.00 0.00 0.00
November 89.59 49.80 39.79 279.19 39.73 0.00 0.00 0.00
December 97.21 60.73 36.49 262.44 82.72 0.00 0.00 0.00
                 
Annual Sum or Average 67.50 28.08 39.42 242.67 34.06 0.00 0.00 0.00
Minimum of Months 37.07 0.14 35.92 180.67 0.63 0.00 0.00 0.00
Maximum of Months 101.29 65.37 43.45 303.20 98.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 724114

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.98 24.52 13.47 95.80 35.94 0.00 0.00 0.00
February 35.10 20.44 14.66 92.28 29.30 0.00 0.00 0.00
March 27.98 12.57 15.41 73.60 22.99 0.00 0.00 0.00
April 19.26 4.29 14.97 63.54 11.32 0.00 0.00 0.00
May 14.78 0.55 14.24 64.32 2.42 0.00 0.00 0.00
June 13.90 0.05 13.85 71.86 0.46 0.00 0.00 0.00
July 14.96 0.25 14.72 79.22 1.01 0.00 0.00 0.00
August 17.41 1.98 15.44 81.63 0.45 0.00 0.00 0.00
September 22.50 6.21 16.29 99.05 2.07 0.00 0.00 0.00
October 30.38 14.62 15.75 106.00 4.17 0.00 0.00 0.00
November 33.60 18.68 14.92 99.72 15.08 0.00 0.00 0.00
December 36.45 22.77 13.68 95.06 30.42 0.00 0.00 0.00
                 
Annual Sum or Average 25.31 10.53 14.78 85.13 12.90 0.00 0.00 0.00
Minimum of Months 13.90 0.05 13.47 63.54 0.45 0.00 0.00 0.00
Maximum of Months 37.98 24.52 16.29 106.00 35.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: D538C4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.14 16.90 18.24 81.38 61.01 0.00 0.00 0.00
February 40.41 18.70 21.71 100.62 49.62 0.00 0.00 0.00
March 49.04 23.02 26.02 119.77 39.94 0.00 0.00 0.00
April 53.36 23.69 29.66 158.10 23.53 0.00 0.00 0.00
May 50.51 20.02 30.49 175.25 6.97 0.00 0.00 0.00
June 49.87 19.07 30.80 193.50 2.16 0.00 0.00 0.00
July 51.33 18.47 32.86 206.79 3.59 0.00 0.00 0.00
August 46.88 15.60 31.28 182.33 2.03 0.00 0.00 0.00
September 45.18 16.26 28.92 183.12 5.53 0.00 0.00 0.00
October 41.58 17.84 23.74 149.02 8.77 0.00 0.00 0.00
November 33.91 13.56 20.35 103.28 26.35 0.00 0.00 0.00
December 27.55 9.86 17.68 67.88 51.11 0.00 0.00 0.00
                 
Annual Sum or Average 43.74 17.74 26.00 143.60 23.27 0.00 0.00 0.00
Minimum of Months 27.55 9.86 17.68 67.88 2.03 0.00 0.00 0.00
Maximum of Months 53.36 23.69 32.86 206.79 61.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 5635BC

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 34.48 16.90 17.58 80.29 59.93 0.00 0.00 0.00
February 39.64 18.70 20.95 99.31 48.70 0.00 0.00 0.00
March 48.14 23.02 25.12 118.09 39.11 0.00 0.00 0.00
April 52.40 23.69 28.70 156.28 22.75 0.00 0.00 0.00
May 49.45 20.02 29.42 173.24 6.53 0.00 0.00 0.00
June 48.75 19.07 29.68 191.48 1.94 0.00 0.00 0.00
July 50.19 18.47 31.72 204.67 3.27 0.00 0.00 0.00
August 45.74 15.60 30.14 180.59 1.87 0.00 0.00 0.00
September 44.13 16.26 27.87 181.09 5.11 0.00 0.00 0.00
October 40.72 17.84 22.88 147.75 8.18 0.00 0.00 0.00
November 33.14 13.56 19.57 102.00 25.59 0.00 0.00 0.00
December 26.87 9.86 17.01 66.62 50.25 0.00 0.00 0.00
                 
Annual Sum or Average 42.81 17.74 25.07 141.96 22.66 0.00 0.00 0.00
Minimum of Months 26.87 9.86 17.01 66.62 1.87 0.00 0.00 0.00
Maximum of Months 52.40 23.69 31.72 204.67 59.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 831C1D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.34 0.00 15.34 32.36 66.79 0.00 0.00 0.00
February 18.16 0.00 18.16 47.52 53.66 0.00 0.00 0.00
March 21.65 0.00 21.65 55.30 43.39 0.00 0.00 0.00
April 24.34 0.19 24.15 83.23 21.12 0.00 0.00 0.00
May 28.20 1.74 26.47 122.52 5.33 0.00 0.00 0.00
June 30.28 2.81 27.46 149.18 1.26 0.00 0.00 0.00
July 30.48 2.00 28.48 157.54 2.41 0.00 0.00 0.00
August 26.63 0.38 26.26 136.00 1.10 0.00 0.00 0.00
September 23.50 0.00 23.50 131.05 4.08 0.00 0.00 0.00
October 19.70 0.00 19.70 95.40 6.61 0.00 0.00 0.00
November 17.13 0.00 17.13 63.89 27.39 0.00 0.00 0.00
December 15.17 0.00 15.17 37.47 54.95 0.00 0.00 0.00
                 
Annual Sum or Average 22.57 0.60 21.97 92.84 23.88 0.00 0.00 0.00
Minimum of Months 15.17 0.00 15.17 32.36 1.10 0.00 0.00 0.00
Maximum of Months 30.48 2.81 28.48 157.54 66.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 9BB95F

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 21.12 48.61 0.00 0.00 0.00
February 12.10 0.00 12.10 31.32 39.07 0.00 0.00 0.00
March 14.43 0.00 14.43 37.13 31.33 0.00 0.00 0.00
April 16.22 0.12 16.10 57.09 14.30 0.00 0.00 0.00
May 18.80 1.16 17.64 85.70 3.24 0.00 0.00 0.00
June 20.18 1.87 18.31 105.09 0.64 0.00 0.00 0.00
July 20.32 1.33 18.99 110.97 1.26 0.00 0.00 0.00
August 17.76 0.25 17.50 95.79 0.54 0.00 0.00 0.00
September 15.66 0.00 15.66 91.96 2.29 0.00 0.00 0.00
October 13.13 0.00 13.13 66.35 4.15 0.00 0.00 0.00
November 11.42 0.00 11.42 43.25 19.64 0.00 0.00 0.00
December 10.11 0.00 10.11 24.78 40.11 0.00 0.00 0.00
                 
Annual Sum or Average 15.05 0.40 14.65 64.37 17.00 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 21.12 0.54 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 110.97 48.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: C0778D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 21.12 48.61 0.00 0.00 0.00
February 12.10 0.00 12.10 31.32 39.07 0.00 0.00 0.00
March 14.43 0.00 14.43 37.13 31.33 0.00 0.00 0.00
April 16.20 0.11 16.09 57.01 14.30 0.00 0.00 0.00
May 18.80 1.16 17.64 85.70 3.24 0.00 0.00 0.00
June 20.18 1.87 18.31 105.09 0.64 0.00 0.00 0.00
July 20.32 1.33 18.99 110.97 1.26 0.00 0.00 0.00
August 17.76 0.25 17.50 95.79 0.54 0.00 0.00 0.00
September 15.66 0.00 15.66 91.96 2.29 0.00 0.00 0.00
October 13.13 0.00 13.13 66.35 4.15 0.00 0.00 0.00
November 11.42 0.00 11.42 43.25 19.64 0.00 0.00 0.00
December 10.11 0.00 10.11 24.78 40.11 0.00 0.00 0.00
                 
Annual Sum or Average 15.04 0.40 14.65 64.37 17.00 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 21.12 0.54 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 110.97 48.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 7D2D69

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 20.50 47.81 0.00 0.00 0.00
February 12.10 0.00 12.10 30.30 38.64 0.00 0.00 0.00
March 14.43 0.00 14.43 35.50 31.34 0.00 0.00 0.00
April 16.11 0.07 16.04 53.93 15.36 0.00 0.00 0.00
May 18.80 1.16 17.64 80.24 4.10 0.00 0.00 0.00
June 20.18 1.87 18.31 98.24 0.98 0.00 0.00 0.00
July 20.32 1.33 18.99 104.19 1.75 0.00 0.00 0.00
August 17.75 0.25 17.50 89.40 0.91 0.00 0.00 0.00
September 15.66 0.00 15.66 86.40 3.04 0.00 0.00 0.00
October 13.13 0.00 13.13 62.22 5.04 0.00 0.00 0.00
November 11.42 0.00 11.42 40.94 19.96 0.00 0.00 0.00
December 10.11 0.00 10.11 23.76 39.58 0.00 0.00 0.00
                 
Annual Sum or Average 15.04 0.39 14.64 60.61 17.28 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 20.50 0.91 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 104.19 47.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 2EF63B

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 20.50 47.81 0.00 0.00 0.00
February 12.10 0.00 12.10 30.30 38.64 0.00 0.00 0.00
March 14.43 0.00 14.43 35.50 31.34 0.00 0.00 0.00
April 16.07 0.05 16.02 53.82 15.39 0.00 0.00 0.00
May 18.80 1.16 17.64 80.24 4.10 0.00 0.00 0.00
June 20.18 1.87 18.31 98.24 0.98 0.00 0.00 0.00
July 20.32 1.33 18.99 104.18 1.75 0.00 0.00 0.00
August 17.70 0.23 17.47 89.23 0.91 0.00 0.00 0.00
September 15.66 0.00 15.66 86.40 3.04 0.00 0.00 0.00
October 13.13 0.00 13.13 62.22 5.04 0.00 0.00 0.00
November 11.42 0.00 11.42 40.94 19.96 0.00 0.00 0.00
December 10.11 0.00 10.11 23.76 39.58 0.00 0.00 0.00
                 
Annual Sum or Average 15.03 0.39 14.64 60.59 17.29 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 20.50 0.91 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 104.18 47.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: C417C0

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.11 0.00 10.11 20.52 49.75 0.00 0.00 0.00
February 11.96 0.00 11.96 30.64 40.06 0.00 0.00 0.00
March 14.27 0.00 14.27 36.30 32.22 0.00 0.00 0.00
April 15.87 0.04 15.83 55.52 15.04 0.00 0.00 0.00
May 18.13 0.87 17.26 82.66 3.52 0.00 0.00 0.00
June 19.81 1.77 18.04 102.82 0.73 0.00 0.00 0.00
July 19.80 1.16 18.64 108.10 1.39 0.00 0.00 0.00
August 17.29 0.15 17.14 93.23 0.66 0.00 0.00 0.00
September 15.48 0.00 15.48 90.26 2.56 0.00 0.00 0.00
October 12.98 0.00 12.98 64.82 4.59 0.00 0.00 0.00
November 11.28 0.00 11.28 42.20 20.38 0.00 0.00 0.00
December 9.99 0.00 9.99 24.04 41.14 0.00 0.00 0.00
                 
Annual Sum or Average 14.76 0.33 14.43 62.75 17.57 0.00 0.00 0.00
Minimum of Months 9.99 0.00 9.99 20.52 0.66 0.00 0.00 0.00
Maximum of Months 19.81 1.77 18.64 108.10 49.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: EB042B

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 59.57 46.71 0.00 0.00 0.00
February 30.33 14.02 16.31 74.17 37.73 0.00 0.00 0.00
March 36.81 17.27 19.55 88.83 30.33 0.00 0.00 0.00
April 40.05 17.77 22.28 117.14 18.10 0.00 0.00 0.00
May 37.92 15.02 22.91 128.96 5.45 0.00 0.00 0.00
June 37.44 14.30 23.14 141.01 1.74 0.00 0.00 0.00
July 38.54 13.85 24.68 150.53 3.13 0.00 0.00 0.00
August 35.20 11.70 23.50 132.45 1.76 0.00 0.00 0.00
September 33.93 12.20 21.73 132.78 4.62 0.00 0.00 0.00
October 31.22 13.38 17.83 108.54 7.29 0.00 0.00 0.00
November 25.46 10.17 15.29 75.40 19.86 0.00 0.00 0.00
December 20.68 7.40 13.29 49.18 39.26 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 105.00 17.91 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 49.18 1.74 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 150.53 46.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 4C1F71

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 59.57 46.71 0.00 0.00 0.00
February 30.33 14.02 16.31 74.17 37.73 0.00 0.00 0.00
March 36.81 17.27 19.55 88.83 30.33 0.00 0.00 0.00
April 40.05 17.77 22.28 117.14 18.10 0.00 0.00 0.00
May 37.92 15.02 22.91 128.96 5.45 0.00 0.00 0.00
June 37.44 14.30 23.14 141.01 1.74 0.00 0.00 0.00
July 38.54 13.85 24.68 150.53 3.13 0.00 0.00 0.00
August 35.20 11.70 23.50 132.45 1.76 0.00 0.00 0.00
September 33.93 12.20 21.73 132.78 4.62 0.00 0.00 0.00
October 31.22 13.38 17.83 108.54 7.29 0.00 0.00 0.00
November 25.46 10.17 15.29 75.40 19.86 0.00 0.00 0.00
December 20.68 7.40 13.29 49.18 39.26 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 105.00 17.91 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 49.18 1.74 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 150.53 46.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: D23C8B

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 59.57 46.71 0.00 0.00 0.00
February 30.33 14.02 16.31 74.17 37.73 0.00 0.00 0.00
March 36.81 17.27 19.55 88.83 30.33 0.00 0.00 0.00
April 40.05 17.77 22.28 117.14 18.10 0.00 0.00 0.00
May 37.92 15.02 22.91 128.96 5.45 0.00 0.00 0.00
June 37.44 14.30 23.14 141.01 1.74 0.00 0.00 0.00
July 38.54 13.85 24.68 150.53 3.13 0.00 0.00 0.00
August 35.20 11.70 23.50 132.45 1.76 0.00 0.00 0.00
September 33.93 12.20 21.73 132.78 4.62 0.00 0.00 0.00
October 31.22 13.38 17.83 108.54 7.29 0.00 0.00 0.00
November 25.46 10.17 15.29 75.40 19.86 0.00 0.00 0.00
December 20.68 7.40 13.29 49.18 39.26 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 105.00 17.91 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 49.18 1.74 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 150.53 46.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: B4E4BE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 59.57 46.71 0.00 0.00 0.00
February 30.33 14.02 16.31 74.17 37.73 0.00 0.00 0.00
March 36.81 17.27 19.55 88.83 30.33 0.00 0.00 0.00
April 40.05 17.77 22.28 117.14 18.10 0.00 0.00 0.00
May 37.92 15.02 22.91 128.96 5.45 0.00 0.00 0.00
June 37.44 14.30 23.14 141.01 1.74 0.00 0.00 0.00
July 38.54 13.85 24.68 150.53 3.13 0.00 0.00 0.00
August 35.20 11.70 23.50 132.45 1.76 0.00 0.00 0.00
September 33.93 12.20 21.73 132.78 4.62 0.00 0.00 0.00
October 31.22 13.38 17.83 108.54 7.29 0.00 0.00 0.00
November 25.46 10.17 15.29 75.40 19.86 0.00 0.00 0.00
December 20.68 7.40 13.29 49.18 39.26 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 105.00 17.91 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 49.18 1.74 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 150.53 46.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: EEF55D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.68 67.28 37.40 262.53 126.50 0.00 0.00 0.00
February 98.65 57.48 41.17 255.59 105.44 0.00 0.00 0.00
March 80.07 36.20 43.87 203.15 86.36 0.00 0.00 0.00
April 55.74 12.84 42.89 171.53 50.20 0.00 0.00 0.00
May 42.24 1.64 40.60 163.80 16.87 0.00 0.00 0.00
June 39.53 0.16 39.37 181.13 5.19 0.00 0.00 0.00
July 42.59 0.74 41.86 202.15 8.52 0.00 0.00 0.00
August 49.98 5.90 44.08 209.37 5.80 0.00 0.00 0.00
September 64.79 18.24 46.55 264.23 12.98 0.00 0.00 0.00
October 86.02 41.46 44.56 284.78 22.91 0.00 0.00 0.00
November 93.63 51.87 41.76 270.02 58.86 0.00 0.00 0.00
December 103.12 64.83 38.29 263.40 106.67 0.00 0.00 0.00
                 
Annual Sum or Average 71.62 29.76 41.86 227.48 50.28 0.00 0.00 0.00
Minimum of Months 39.53 0.16 37.40 163.80 5.19 0.00 0.00 0.00
Maximum of Months 104.68 67.28 46.55 284.78 126.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: E55A57

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 45.28 28.51 16.76 114.56 63.88 0.00 0.00 0.00
February 43.54 25.01 18.53 114.58 52.86 0.00 0.00 0.00
March 36.09 16.17 19.92 93.35 43.42 0.00 0.00 0.00
April 25.73 6.09 19.64 82.02 24.19 0.00 0.00 0.00
May 19.40 0.82 18.58 79.93 7.58 0.00 0.00 0.00
June 17.97 0.08 17.89 88.90 2.12 0.00 0.00 0.00
July 19.46 0.37 19.09 99.28 3.59 0.00 0.00 0.00
August 22.94 2.82 20.12 102.87 2.56 0.00 0.00 0.00
September 29.30 8.25 21.05 126.14 5.80 0.00 0.00 0.00
October 38.23 18.12 20.11 131.27 10.34 0.00 0.00 0.00
November 41.24 22.51 18.73 122.14 28.89 0.00 0.00 0.00
December 45.77 28.68 17.09 118.34 53.73 0.00 0.00 0.00
                 
Annual Sum or Average 32.02 13.06 18.96 106.06 24.79 0.00 0.00 0.00
Minimum of Months 17.97 0.08 16.76 79.93 2.12 0.00 0.00 0.00
Maximum of Months 45.77 28.68 21.05 131.27 63.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 93D018

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 52.50 23.06 29.44 116.30 129.87 0.00 0.00 0.00
February 65.44 29.98 35.46 161.14 107.24 0.00 0.00 0.00
March 81.24 37.37 43.87 200.95 88.24 0.00 0.00 0.00
April 89.27 41.53 47.74 258.42 49.46 0.00 0.00 0.00
May 81.47 31.69 49.79 274.93 17.25 0.00 0.00 0.00
June 68.98 19.70 49.28 267.63 5.33 0.00 0.00 0.00
July 77.25 24.32 52.93 305.55 8.79 0.00 0.00 0.00
August 76.96 25.44 51.53 281.97 5.79 0.00 0.00 0.00
September 65.61 19.68 45.93 258.12 13.29 0.00 0.00 0.00
October 65.46 25.88 39.59 218.41 23.31 0.00 0.00 0.00
November 54.15 20.30 33.85 156.99 60.12 0.00 0.00 0.00
December 54.40 24.79 29.61 128.58 109.55 0.00 0.00 0.00
                 
Annual Sum or Average 69.43 26.97 42.46 219.38 51.27 0.00 0.00 0.00
Minimum of Months 52.50 19.68 29.44 116.30 5.33 0.00 0.00 0.00
Maximum of Months 89.27 41.53 52.93 305.55 129.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DD9F5D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 60.60 43.82 0.00 0.00 0.00
February 30.33 14.02 16.31 75.34 35.20 0.00 0.00 0.00
March 36.81 17.27 19.55 89.97 28.09 0.00 0.00 0.00
April 40.05 17.77 22.28 118.40 16.21 0.00 0.00 0.00
May 37.92 15.02 22.91 130.95 4.40 0.00 0.00 0.00
June 37.44 14.30 23.14 143.58 1.29 0.00 0.00 0.00
July 38.54 13.85 24.68 152.77 2.45 0.00 0.00 0.00
August 35.20 11.70 23.50 135.28 1.23 0.00 0.00 0.00
September 33.93 12.20 21.73 135.24 3.80 0.00 0.00 0.00
October 31.22 13.38 17.83 110.72 5.91 0.00 0.00 0.00
November 25.46 10.17 15.29 77.10 18.14 0.00 0.00 0.00
December 20.68 7.40 13.29 50.45 36.42 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 106.83 16.33 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 50.45 1.23 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 152.77 43.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 15B02B

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.03 0.00 10.03 17.31 55.84 0.00 0.00 0.00
February 11.87 0.00 11.87 26.63 45.81 0.00 0.00 0.00
March 14.16 0.00 14.16 31.73 37.73 0.00 0.00 0.00
April 15.75 0.04 15.71 48.81 20.16 0.00 0.00 0.00
May 17.60 0.67 16.93 70.70 6.56 0.00 0.00 0.00
June 18.85 1.30 17.54 86.17 2.00 0.00 0.00 0.00
July 19.00 0.84 18.16 91.53 3.34 0.00 0.00 0.00
August 17.11 0.14 16.97 78.57 2.18 0.00 0.00 0.00
September 15.35 0.00 15.35 76.64 5.11 0.00 0.00 0.00
October 12.87 0.00 12.87 53.91 8.45 0.00 0.00 0.00
November 11.19 0.00 11.19 35.07 24.60 0.00 0.00 0.00
December 9.91 0.00 9.91 20.01 46.86 0.00 0.00 0.00
                 
Annual Sum or Average 14.49 0.25 14.24 53.21 21.45 0.00 0.00 0.00
Minimum of Months 9.91 0.00 9.91 17.31 2.00 0.00 0.00 0.00
Maximum of Months 19.00 1.30 18.16 91.53 55.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 820282

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.06 0.00 9.06 15.86 54.36 0.00 0.00 0.00
February 10.75 0.00 10.75 24.79 44.51 0.00 0.00 0.00
March 12.84 0.00 12.84 29.32 36.55 0.00 0.00 0.00
April 14.34 0.04 14.30 46.07 18.94 0.00 0.00 0.00
May 16.00 0.66 15.34 67.47 5.73 0.00 0.00 0.00
June 17.00 1.24 15.76 82.42 1.58 0.00 0.00 0.00
July 17.20 0.80 16.40 87.84 2.72 0.00 0.00 0.00
August 15.45 0.14 15.31 75.87 1.85 0.00 0.00 0.00
September 13.80 0.00 13.80 73.55 4.42 0.00 0.00 0.00
October 11.61 0.00 11.61 51.86 7.41 0.00 0.00 0.00
November 10.05 0.00 10.05 33.13 23.42 0.00 0.00 0.00
December 8.92 0.00 8.92 18.32 45.75 0.00 0.00 0.00
                 
Annual Sum or Average 13.10 0.24 12.85 50.66 20.50 0.00 0.00 0.00
Minimum of Months 8.92 0.00 8.92 15.86 1.58 0.00 0.00 0.00
Maximum of Months 17.20 1.24 16.40 87.84 54.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 9BA05A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 16.68 50.15 0.00 0.00 0.00
February 12.10 0.00 12.10 25.62 39.96 0.00 0.00 0.00
March 14.43 0.00 14.43 30.44 31.96 0.00 0.00 0.00
April 16.23 0.13 16.10 47.35 14.21 0.00 0.00 0.00
May 18.80 1.16 17.64 72.48 3.28 0.00 0.00 0.00
June 20.18 1.87 18.31 88.50 0.63 0.00 0.00 0.00
July 20.32 1.33 18.99 93.17 1.56 0.00 0.00 0.00
August 17.76 0.25 17.51 79.56 0.81 0.00 0.00 0.00
September 15.67 0.00 15.67 75.80 2.70 0.00 0.00 0.00
October 13.13 0.00 13.13 53.97 4.59 0.00 0.00 0.00
November 11.42 0.00 11.42 35.46 19.44 0.00 0.00 0.00
December 10.11 0.00 10.11 19.61 41.34 0.00 0.00 0.00
                 
Annual Sum or Average 15.05 0.40 14.65 53.35 17.46 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 16.68 0.63 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 93.17 50.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: C639E8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 16.68 50.15 0.00 0.00 0.00
February 12.10 0.00 12.10 25.62 39.96 0.00 0.00 0.00
March 14.43 0.00 14.43 30.44 31.96 0.00 0.00 0.00
April 16.23 0.13 16.10 47.35 14.21 0.00 0.00 0.00
May 18.80 1.16 17.64 72.48 3.28 0.00 0.00 0.00
June 20.18 1.87 18.31 88.50 0.63 0.00 0.00 0.00
July 20.32 1.33 18.99 93.17 1.56 0.00 0.00 0.00
August 17.76 0.25 17.51 79.56 0.81 0.00 0.00 0.00
September 15.67 0.00 15.67 75.80 2.70 0.00 0.00 0.00
October 13.13 0.00 13.13 53.97 4.59 0.00 0.00 0.00
November 11.42 0.00 11.42 35.46 19.44 0.00 0.00 0.00
December 10.11 0.00 10.11 19.61 41.34 0.00 0.00 0.00
                 
Annual Sum or Average 15.05 0.40 14.65 53.35 17.46 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 16.68 0.63 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 93.17 50.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: A2790A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.34 0.00 15.34 32.84 54.81 0.00 0.00 0.00
February 18.16 0.00 18.16 49.08 41.10 0.00 0.00 0.00
March 21.65 0.00 21.65 57.46 30.70 0.00 0.00 0.00
April 24.34 0.19 24.15 85.81 8.48 0.00 0.00 0.00
May 28.20 1.74 26.47 131.54 1.10 0.00 0.00 0.00
June 30.28 2.81 27.46 157.14 0.03 0.00 0.00 0.00
July 30.48 2.00 28.48 162.27 0.27 0.00 0.00 0.00
August 26.64 0.38 26.26 144.93 0.01 0.00 0.00 0.00
September 23.51 0.00 23.50 136.25 0.22 0.00 0.00 0.00
October 19.70 0.00 19.70 103.57 1.21 0.00 0.00 0.00
November 17.13 0.00 17.13 69.98 17.60 0.00 0.00 0.00
December 15.17 0.00 15.17 39.07 43.72 0.00 0.00 0.00
                 
Annual Sum or Average 22.57 0.60 21.98 97.73 16.51 0.00 0.00 0.00
Minimum of Months 15.17 0.00 15.17 32.84 0.01 0.00 0.00 0.00
Maximum of Months 30.48 2.81 28.48 162.27 54.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 79FCEE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.15 16.90 18.25 72.17 71.69 0.00 0.00 0.00
February 40.42 18.70 21.72 89.47 58.35 0.00 0.00 0.00
March 49.06 23.02 26.04 108.00 46.35 0.00 0.00 0.00
April 53.37 23.69 29.68 144.80 27.22 0.00 0.00 0.00
May 50.53 20.02 30.51 158.59 9.93 0.00 0.00 0.00
June 49.89 19.07 30.82 173.21 3.33 0.00 0.00 0.00
July 51.35 18.47 32.88 187.26 5.55 0.00 0.00 0.00
August 46.90 15.60 31.30 162.49 3.71 0.00 0.00 0.00
September 45.21 16.26 28.94 163.49 7.35 0.00 0.00 0.00
October 41.60 17.84 23.75 133.75 12.07 0.00 0.00 0.00
November 33.92 13.56 20.36 91.30 31.05 0.00 0.00 0.00
December 27.56 9.86 17.70 58.16 61.05 0.00 0.00 0.00
                 
Annual Sum or Average 43.76 17.74 26.02 128.72 28.01 0.00 0.00 0.00
Minimum of Months 27.56 9.86 17.70 58.16 3.33 0.00 0.00 0.00
Maximum of Months 53.37 23.69 32.88 187.26 71.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: EDE617

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 34.64 16.90 17.74 71.32 70.95 0.00 0.00 0.00
February 39.83 18.70 21.13 88.44 57.71 0.00 0.00 0.00
March 48.36 23.02 25.33 106.68 45.79 0.00 0.00 0.00
April 52.61 23.69 28.92 143.28 26.64 0.00 0.00 0.00
May 49.71 20.02 29.68 156.88 9.48 0.00 0.00 0.00
June 49.03 19.07 29.96 171.53 3.08 0.00 0.00 0.00
July 50.46 18.47 31.99 185.41 5.18 0.00 0.00 0.00
August 46.02 15.60 30.42 160.99 3.49 0.00 0.00 0.00
September 44.39 16.26 28.13 161.84 7.01 0.00 0.00 0.00
October 40.93 17.84 23.08 132.55 11.52 0.00 0.00 0.00
November 33.33 13.56 19.77 90.21 30.43 0.00 0.00 0.00
December 27.04 9.86 17.18 57.19 60.46 0.00 0.00 0.00
                 
Annual Sum or Average 43.04 17.74 25.30 127.35 27.52 0.00 0.00 0.00
Minimum of Months 27.04 9.86 17.18 57.19 3.08 0.00 0.00 0.00
Maximum of Months 52.61 23.69 31.99 185.41 70.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: C61F0D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 17.31 47.48 0.00 0.00 0.00
February 12.10 0.00 12.10 26.41 37.80 0.00 0.00 0.00
March 14.43 0.00 14.43 31.12 30.49 0.00 0.00 0.00
April 16.22 0.12 16.10 48.08 13.68 0.00 0.00 0.00
May 18.80 1.16 17.64 73.15 3.12 0.00 0.00 0.00
June 20.18 1.87 18.31 89.12 0.61 0.00 0.00 0.00
July 20.32 1.33 18.99 93.59 1.54 0.00 0.00 0.00
August 17.76 0.25 17.51 80.28 0.73 0.00 0.00 0.00
September 15.67 0.00 15.67 76.40 2.63 0.00 0.00 0.00
October 13.13 0.00 13.13 54.77 4.35 0.00 0.00 0.00
November 11.42 0.00 11.42 36.26 18.34 0.00 0.00 0.00
December 10.11 0.00 10.11 20.25 39.25 0.00 0.00 0.00
                 
Annual Sum or Average 15.05 0.40 14.65 54.03 16.58 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 17.31 0.61 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 93.59 47.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 7248C5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.40 0.00 9.40 16.01 46.44 0.00 0.00 0.00
February 11.14 0.00 11.14 24.77 36.90 0.00 0.00 0.00
March 13.30 0.00 13.30 29.01 29.70 0.00 0.00 0.00
April 14.81 0.04 14.77 45.19 12.98 0.00 0.00 0.00
May 16.70 0.73 15.97 68.17 2.69 0.00 0.00 0.00
June 17.97 1.40 16.58 83.96 0.47 0.00 0.00 0.00
July 18.07 0.92 17.15 88.14 1.28 0.00 0.00 0.00
August 16.07 0.15 15.93 77.12 0.63 0.00 0.00 0.00
September 14.37 0.00 14.37 73.78 2.19 0.00 0.00 0.00
October 12.05 0.00 12.05 53.02 3.77 0.00 0.00 0.00
November 10.47 0.00 10.47 34.68 17.60 0.00 0.00 0.00
December 9.28 0.00 9.28 18.80 38.47 0.00 0.00 0.00
                 
Annual Sum or Average 13.65 0.27 13.38 51.18 16.01 0.00 0.00 0.00
Minimum of Months 9.28 0.00 9.28 16.01 0.47 0.00 0.00 0.00
Maximum of Months 18.07 1.40 17.15 88.14 46.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 29FA28

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 17.31 47.48 0.00 0.00 0.00
February 12.10 0.00 12.10 26.41 37.80 0.00 0.00 0.00
March 14.43 0.00 14.43 31.12 30.49 0.00 0.00 0.00
April 16.19 0.10 16.08 48.01 13.73 0.00 0.00 0.00
May 18.80 1.16 17.64 73.15 3.12 0.00 0.00 0.00
June 20.18 1.87 18.31 89.12 0.61 0.00 0.00 0.00
July 20.32 1.33 18.99 93.59 1.54 0.00 0.00 0.00
August 17.76 0.25 17.51 80.28 0.73 0.00 0.00 0.00
September 15.67 0.00 15.67 76.40 2.63 0.00 0.00 0.00
October 13.13 0.00 13.13 54.77 4.35 0.00 0.00 0.00
November 11.42 0.00 11.42 36.26 18.34 0.00 0.00 0.00
December 10.11 0.00 10.11 20.25 39.25 0.00 0.00 0.00
                 
Annual Sum or Average 15.04 0.40 14.65 54.02 16.58 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 17.31 0.61 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 93.59 47.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: F0B23F

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 17.31 47.48 0.00 0.00 0.00
February 12.10 0.00 12.10 26.41 37.80 0.00 0.00 0.00
March 14.43 0.00 14.43 31.12 30.49 0.00 0.00 0.00
April 16.15 0.09 16.06 47.95 13.77 0.00 0.00 0.00
May 18.80 1.16 17.64 73.15 3.12 0.00 0.00 0.00
June 20.18 1.87 18.31 89.12 0.61 0.00 0.00 0.00
July 20.32 1.33 18.99 93.59 1.54 0.00 0.00 0.00
August 17.75 0.25 17.50 80.26 0.73 0.00 0.00 0.00
September 15.67 0.00 15.66 76.40 2.63 0.00 0.00 0.00
October 13.13 0.00 13.13 54.77 4.35 0.00 0.00 0.00
November 11.42 0.00 11.42 36.26 18.34 0.00 0.00 0.00
December 10.11 0.00 10.11 20.25 39.25 0.00 0.00 0.00
                 
Annual Sum or Average 15.04 0.39 14.65 54.01 16.59 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 17.31 0.61 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 93.59 47.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: EEC10E

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.16 0.00 10.16 17.19 47.42 0.00 0.00 0.00
February 12.03 0.00 12.03 26.26 37.74 0.00 0.00 0.00
March 14.34 0.00 14.34 30.94 30.45 0.00 0.00 0.00
April 16.02 0.07 15.94 47.65 13.73 0.00 0.00 0.00
May 18.63 1.12 17.51 72.73 3.09 0.00 0.00 0.00
June 20.08 1.87 18.20 88.90 0.60 0.00 0.00 0.00
July 20.19 1.33 18.87 93.31 1.52 0.00 0.00 0.00
August 17.56 0.22 17.33 79.81 0.72 0.00 0.00 0.00
September 15.56 0.00 15.56 76.17 2.60 0.00 0.00 0.00
October 13.04 0.00 13.04 54.60 4.31 0.00 0.00 0.00
November 11.34 0.00 11.34 36.13 18.29 0.00 0.00 0.00
December 10.05 0.00 10.05 20.13 39.20 0.00 0.00 0.00
                 
Annual Sum or Average 14.93 0.39 14.54 53.78 16.55 0.00 0.00 0.00
Minimum of Months 10.05 0.00 10.05 17.19 0.60 0.00 0.00 0.00
Maximum of Months 20.19 1.87 18.87 93.31 47.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 944FCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.12 0.00 10.12 17.12 47.37 0.00 0.00 0.00
February 11.98 0.00 11.98 26.18 37.71 0.00 0.00 0.00
March 14.29 0.00 14.29 30.83 30.42 0.00 0.00 0.00
April 15.91 0.05 15.86 47.40 13.71 0.00 0.00 0.00
May 18.26 0.96 17.30 71.67 3.07 0.00 0.00 0.00
June 19.73 1.71 18.02 87.92 0.59 0.00 0.00 0.00
July 19.83 1.19 18.64 92.22 1.51 0.00 0.00 0.00
August 17.42 0.19 17.22 79.47 0.72 0.00 0.00 0.00
September 15.50 0.00 15.50 76.03 2.58 0.00 0.00 0.00
October 12.99 0.00 12.99 54.50 4.29 0.00 0.00 0.00
November 11.30 0.00 11.30 36.04 18.26 0.00 0.00 0.00
December 10.01 0.00 10.01 20.06 39.17 0.00 0.00 0.00
                 
Annual Sum or Average 14.79 0.34 14.45 53.42 16.53 0.00 0.00 0.00
Minimum of Months 10.01 0.00 10.01 17.12 0.59 0.00 0.00 0.00
Maximum of Months 19.83 1.71 18.64 92.22 47.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: C41399

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.23 0.00 10.23 17.31 47.48 0.00 0.00 0.00
February 12.10 0.00 12.10 26.41 37.80 0.00 0.00 0.00
March 14.43 0.00 14.43 31.12 30.49 0.00 0.00 0.00
April 16.23 0.13 16.10 48.09 13.68 0.00 0.00 0.00
May 18.80 1.16 17.64 73.15 3.12 0.00 0.00 0.00
June 20.18 1.87 18.31 89.12 0.61 0.00 0.00 0.00
July 20.32 1.33 18.99 93.59 1.54 0.00 0.00 0.00
August 17.76 0.25 17.51 80.28 0.73 0.00 0.00 0.00
September 15.67 0.00 15.67 76.41 2.63 0.00 0.00 0.00
October 13.13 0.00 13.13 54.77 4.35 0.00 0.00 0.00
November 11.42 0.00 11.42 36.26 18.34 0.00 0.00 0.00
December 10.11 0.00 10.11 20.25 39.25 0.00 0.00 0.00
                 
Annual Sum or Average 15.05 0.40 14.65 54.03 16.58 0.00 0.00 0.00
Minimum of Months 10.11 0.00 10.11 17.31 0.61 0.00 0.00 0.00
Maximum of Months 20.32 1.87 18.99 93.59 47.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 95BA33

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.95 15.84 17.11 71.53 46.71 0.00 0.00 0.00
February 37.88 17.51 20.37 89.32 34.76 0.00 0.00 0.00
March 45.98 21.57 24.41 108.82 24.04 0.00 0.00 0.00
April 50.02 22.19 27.83 147.07 7.65 0.00 0.00 0.00
May 47.36 18.75 28.61 170.58 0.82 0.00 0.00 0.00
June 46.77 17.86 28.90 187.84 0.02 0.00 0.00 0.00
July 48.13 17.30 30.83 198.91 0.20 0.00 0.00 0.00
August 43.96 14.61 29.35 176.91 0.07 0.00 0.00 0.00
September 42.37 15.23 27.14 172.28 0.22 0.00 0.00 0.00
October 38.99 16.72 22.27 140.11 1.42 0.00 0.00 0.00
November 31.80 12.71 19.09 95.41 14.75 0.00 0.00 0.00
December 25.83 9.24 16.59 58.80 38.32 0.00 0.00 0.00
                 
Annual Sum or Average 41.01 16.62 24.39 135.00 14.01 0.00 0.00 0.00
Minimum of Months 25.83 9.24 16.59 58.80 0.02 0.00 0.00 0.00
Maximum of Months 50.02 22.19 30.83 198.91 46.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: F27282

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.95 15.84 17.11 71.32 46.98 0.00 0.00 0.00
February 37.88 17.51 20.37 88.97 34.81 0.00 0.00 0.00
March 45.98 21.57 24.41 108.73 24.06 0.00 0.00 0.00
April 50.02 22.19 27.83 147.07 7.65 0.00 0.00 0.00
May 47.36 18.75 28.61 170.58 0.82 0.00 0.00 0.00
June 46.77 17.86 28.90 187.84 0.02 0.00 0.00 0.00
July 48.13 17.30 30.83 198.91 0.20 0.00 0.00 0.00
August 43.96 14.61 29.35 176.91 0.07 0.00 0.00 0.00
September 42.37 15.23 27.14 172.26 0.22 0.00 0.00 0.00
October 38.99 16.72 22.27 139.90 1.42 0.00 0.00 0.00
November 31.80 12.71 19.09 95.09 14.79 0.00 0.00 0.00
December 25.83 9.24 16.59 58.47 38.49 0.00 0.00 0.00
                 
Annual Sum or Average 41.01 16.62 24.39 134.87 14.05 0.00 0.00 0.00
Minimum of Months 25.83 9.24 16.59 58.47 0.02 0.00 0.00 0.00
Maximum of Months 50.02 22.19 30.83 198.91 46.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 3DB407

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.96 61.29 33.67 233.30 68.55 0.00 0.00 0.00
February 87.75 51.11 36.64 223.27 52.72 0.00 0.00 0.00
March 69.96 31.42 38.53 176.57 37.93 0.00 0.00 0.00
April 48.15 10.71 37.44 151.79 12.05 0.00 0.00 0.00
May 36.96 1.37 35.59 161.14 1.30 0.00 0.00 0.00
June 34.75 0.14 34.62 178.36 0.02 0.00 0.00 0.00
July 37.41 0.61 36.79 193.78 0.31 0.00 0.00 0.00
August 43.53 4.94 38.59 203.56 0.11 0.00 0.00 0.00
September 56.25 15.51 40.73 242.51 0.34 0.00 0.00 0.00
October 75.95 36.56 39.39 263.20 2.06 0.00 0.00 0.00
November 83.99 46.69 37.31 247.39 22.48 0.00 0.00 0.00
December 91.14 56.93 34.20 231.84 55.76 0.00 0.00 0.00
                 
Annual Sum or Average 63.28 26.33 36.96 208.82 21.01 0.00 0.00 0.00
Minimum of Months 34.75 0.14 33.67 151.79 0.02 0.00 0.00 0.00
Maximum of Months 94.96 61.29 40.73 263.20 68.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 3DADE2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.96 61.29 33.67 233.30 68.55 0.00 0.00 0.00
February 87.75 51.11 36.64 223.27 52.72 0.00 0.00 0.00
March 69.96 31.42 38.53 176.57 37.93 0.00 0.00 0.00
April 48.15 10.71 37.44 151.79 12.05 0.00 0.00 0.00
May 36.96 1.37 35.59 161.16 1.29 0.00 0.00 0.00
June 34.75 0.14 34.62 178.38 0.02 0.00 0.00 0.00
July 37.41 0.61 36.79 193.80 0.31 0.00 0.00 0.00
August 43.53 4.94 38.59 203.56 0.11 0.00 0.00 0.00
September 56.25 15.51 40.73 242.51 0.34 0.00 0.00 0.00
October 75.95 36.56 39.39 263.20 2.06 0.00 0.00 0.00
November 83.99 46.69 37.31 247.39 22.48 0.00 0.00 0.00
December 91.14 56.93 34.20 231.84 55.76 0.00 0.00 0.00
                 
Annual Sum or Average 63.28 26.33 36.96 208.82 21.01 0.00 0.00 0.00
Minimum of Months 34.75 0.14 33.67 151.79 0.02 0.00 0.00 0.00
Maximum of Months 94.96 61.29 40.73 263.20 68.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DF3E2C

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.96 61.29 33.67 233.30 68.55 0.00 0.00 0.00
February 87.75 51.11 36.64 223.27 52.72 0.00 0.00 0.00
March 69.96 31.42 38.53 176.57 37.93 0.00 0.00 0.00
April 48.15 10.71 37.44 151.79 12.04 0.00 0.00 0.00
May 36.96 1.37 35.59 161.16 1.29 0.00 0.00 0.00
June 34.75 0.14 34.62 178.38 0.02 0.00 0.00 0.00
July 37.41 0.61 36.79 193.80 0.31 0.00 0.00 0.00
August 43.53 4.94 38.59 203.57 0.11 0.00 0.00 0.00
September 56.25 15.51 40.73 242.51 0.34 0.00 0.00 0.00
October 75.95 36.56 39.39 263.20 2.06 0.00 0.00 0.00
November 83.99 46.69 37.31 247.39 22.48 0.00 0.00 0.00
December 91.14 56.93 34.20 231.84 55.76 0.00 0.00 0.00
                 
Annual Sum or Average 63.28 26.33 36.96 208.82 21.01 0.00 0.00 0.00
Minimum of Months 34.75 0.14 33.67 151.79 0.02 0.00 0.00 0.00
Maximum of Months 94.96 61.29 40.73 263.20 68.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 5031C8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.96 61.29 33.67 233.30 68.55 0.00 0.00 0.00
February 87.75 51.11 36.64 223.27 52.72 0.00 0.00 0.00
March 69.96 31.42 38.53 176.57 37.93 0.00 0.00 0.00
April 48.15 10.71 37.44 151.79 12.05 0.00 0.00 0.00
May 36.96 1.37 35.59 161.24 1.29 0.00 0.00 0.00
June 34.75 0.14 34.62 178.58 0.02 0.00 0.00 0.00
July 37.41 0.61 36.79 193.92 0.31 0.00 0.00 0.00
August 43.53 4.94 38.59 203.57 0.11 0.00 0.00 0.00
September 56.25 15.51 40.73 242.51 0.34 0.00 0.00 0.00
October 75.95 36.56 39.39 263.20 2.06 0.00 0.00 0.00
November 83.99 46.69 37.31 247.39 22.48 0.00 0.00 0.00
December 91.14 56.93 34.20 231.84 55.76 0.00 0.00 0.00
                 
Annual Sum or Average 63.28 26.33 36.96 208.86 21.01 0.00 0.00 0.00
Minimum of Months 34.75 0.14 33.67 151.79 0.02 0.00 0.00 0.00
Maximum of Months 94.96 61.29 40.73 263.20 68.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: C087D0

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.96 61.29 33.67 230.86 85.42 0.00 0.00 0.00
February 87.75 51.11 36.64 219.63 69.99 0.00 0.00 0.00
March 69.96 31.42 38.53 171.37 55.85 0.00 0.00 0.00
April 48.15 10.71 37.44 143.21 28.63 0.00 0.00 0.00
May 36.96 1.37 35.59 140.77 6.14 0.00 0.00 0.00
June 34.75 0.14 34.62 156.63 1.01 0.00 0.00 0.00
July 37.41 0.61 36.79 172.58 2.82 0.00 0.00 0.00
August 43.53 4.94 38.59 181.45 1.39 0.00 0.00 0.00
September 56.25 15.51 40.73 225.55 5.09 0.00 0.00 0.00
October 75.95 36.56 39.39 249.09 9.31 0.00 0.00 0.00
November 83.99 46.69 37.31 238.72 34.35 0.00 0.00 0.00
December 91.14 56.93 34.20 227.78 72.30 0.00 0.00 0.00
                 
Annual Sum or Average 63.28 26.33 36.96 196.34 30.85 0.00 0.00 0.00
Minimum of Months 34.75 0.14 33.67 140.77 1.01 0.00 0.00 0.00
Maximum of Months 94.96 61.29 40.73 249.09 85.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: D2CA75

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.96 61.29 33.67 230.86 85.42 0.00 0.00 0.00
February 87.75 51.11 36.64 219.63 69.99 0.00 0.00 0.00
March 69.96 31.42 38.53 171.37 55.85 0.00 0.00 0.00
April 48.15 10.71 37.44 143.21 28.62 0.00 0.00 0.00
May 36.96 1.37 35.59 140.75 6.14 0.00 0.00 0.00
June 34.75 0.14 34.62 156.60 1.01 0.00 0.00 0.00
July 37.41 0.61 36.79 172.55 2.82 0.00 0.00 0.00
August 43.53 4.94 38.59 181.45 1.39 0.00 0.00 0.00
September 56.25 15.51 40.73 225.55 5.09 0.00 0.00 0.00
October 75.95 36.56 39.39 249.09 9.31 0.00 0.00 0.00
November 83.99 46.69 37.31 238.72 34.35 0.00 0.00 0.00
December 91.14 56.93 34.20 227.78 72.30 0.00 0.00 0.00
                 
Annual Sum or Average 63.28 26.33 36.96 196.33 30.85 0.00 0.00 0.00
Minimum of Months 34.75 0.14 33.67 140.75 1.01 0.00 0.00 0.00
Maximum of Months 94.96 61.29 40.73 249.09 85.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: B0FB49

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 75.97 49.03 26.94 184.69 68.33 0.00 0.00 0.00
February 70.20 40.89 29.31 175.70 55.99 0.00 0.00 0.00
March 55.96 25.14 30.83 137.09 44.68 0.00 0.00 0.00
April 38.52 8.57 29.95 114.57 22.90 0.00 0.00 0.00
May 29.57 1.10 28.47 112.63 4.91 0.00 0.00 0.00
June 27.80 0.11 27.69 125.29 0.81 0.00 0.00 0.00
July 29.92 0.49 29.43 138.06 2.25 0.00 0.00 0.00
August 34.82 3.95 30.87 145.17 1.11 0.00 0.00 0.00
September 45.00 12.41 32.59 180.44 4.07 0.00 0.00 0.00
October 60.76 29.25 31.51 199.27 7.45 0.00 0.00 0.00
November 67.20 37.35 29.84 190.98 27.48 0.00 0.00 0.00
December 72.91 45.54 27.36 182.23 57.84 0.00 0.00 0.00
                 
Annual Sum or Average 50.63 21.06 29.56 157.07 24.68 0.00 0.00 0.00
Minimum of Months 27.80 0.11 26.94 112.63 0.81 0.00 0.00 0.00
Maximum of Months 75.97 49.03 32.59 199.27 68.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FE9BC9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.06 11.53 14.54 56.66 55.02 0.00 0.00 0.00
February 32.50 14.99 17.51 78.57 44.42 0.00 0.00 0.00
March 40.36 18.68 21.68 97.79 35.36 0.00 0.00 0.00
April 44.32 20.76 23.56 125.90 16.29 0.00 0.00 0.00
May 40.46 15.84 24.61 136.03 3.51 0.00 0.00 0.00
June 34.15 9.81 24.34 133.45 0.54 0.00 0.00 0.00
July 38.26 12.15 26.11 151.02 1.56 0.00 0.00 0.00
August 38.20 12.72 25.48 141.86 0.71 0.00 0.00 0.00
September 32.56 9.84 22.71 128.49 2.86 0.00 0.00 0.00
October 32.48 12.94 19.54 109.47 5.34 0.00 0.00 0.00
November 26.89 10.15 16.75 78.99 21.66 0.00 0.00 0.00
December 27.04 12.40 14.64 63.29 45.50 0.00 0.00 0.00
                 
Annual Sum or Average 34.45 13.48 20.97 108.61 19.29 0.00 0.00 0.00
Minimum of Months 26.06 9.81 14.54 56.66 0.54 0.00 0.00 0.00
Maximum of Months 44.32 20.76 26.11 151.02 55.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 9DF7DE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.67 11.53 14.14 55.77 55.05 0.00 0.00 0.00
February 32.04 14.99 17.05 77.59 44.27 0.00 0.00 0.00
March 39.82 18.68 21.14 96.72 35.08 0.00 0.00 0.00
April 43.72 20.76 22.95 124.59 15.94 0.00 0.00 0.00
May 39.35 15.59 23.76 133.44 3.33 0.00 0.00 0.00
June 33.23 9.64 23.59 131.41 0.49 0.00 0.00 0.00
July 37.21 11.99 25.23 148.57 1.47 0.00 0.00 0.00
August 37.47 12.69 24.77 140.48 0.67 0.00 0.00 0.00
September 31.95 9.84 22.11 127.19 2.68 0.00 0.00 0.00
October 31.96 12.94 19.02 108.37 5.09 0.00 0.00 0.00
November 26.46 10.15 16.31 77.89 21.48 0.00 0.00 0.00
December 26.65 12.40 14.25 62.30 45.34 0.00 0.00 0.00
                 
Annual Sum or Average 33.81 13.43 20.38 107.18 19.13 0.00 0.00 0.00
Minimum of Months 25.67 9.64 14.14 55.77 0.49 0.00 0.00 0.00
Maximum of Months 43.72 20.76 25.23 148.57 55.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: D0BE44

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.68 11.53 13.15 54.29 53.75 0.00 0.00 0.00
February 30.89 14.99 15.90 75.66 43.03 0.00 0.00 0.00
March 38.46 18.68 19.78 94.21 33.97 0.00 0.00 0.00
April 41.31 20.06 21.24 119.37 14.98 0.00 0.00 0.00
May 36.58 14.78 21.80 127.28 2.78 0.00 0.00 0.00
June 30.59 8.96 21.63 125.84 0.36 0.00 0.00 0.00
July 34.57 11.38 23.19 142.84 1.18 0.00 0.00 0.00
August 35.17 12.38 22.79 136.31 0.57 0.00 0.00 0.00
September 30.36 9.84 20.52 124.09 2.10 0.00 0.00 0.00
October 30.66 12.94 17.72 106.41 4.29 0.00 0.00 0.00
November 25.29 10.15 15.15 75.99 20.49 0.00 0.00 0.00
December 25.63 12.40 13.24 60.51 44.27 0.00 0.00 0.00
                 
Annual Sum or Average 32.03 13.17 18.86 103.71 18.38 0.00 0.00 0.00
Minimum of Months 24.68 8.96 13.15 54.29 0.36 0.00 0.00 0.00
Maximum of Months 41.31 20.06 23.19 142.84 53.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 6B5226

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.22 15.37 19.85 76.94 75.25 0.00 0.00 0.00
February 43.88 19.99 23.89 107.14 60.65 0.00 0.00 0.00
March 54.46 24.91 29.55 133.45 48.40 0.00 0.00 0.00
April 59.82 27.69 32.13 171.69 23.53 0.00 0.00 0.00
May 54.68 21.12 33.56 184.43 5.81 0.00 0.00 0.00
June 46.38 13.13 33.25 180.56 1.15 0.00 0.00 0.00
July 51.88 16.21 35.67 204.21 2.90 0.00 0.00 0.00
August 51.70 16.96 34.74 191.47 1.39 0.00 0.00 0.00
September 44.11 13.12 30.99 173.39 4.96 0.00 0.00 0.00
October 43.93 17.25 26.67 147.41 8.75 0.00 0.00 0.00
November 36.37 13.53 22.84 106.78 30.65 0.00 0.00 0.00
December 36.50 16.53 19.98 85.76 62.24 0.00 0.00 0.00
                 
Annual Sum or Average 46.60 17.98 28.62 147.14 27.00 0.00 0.00 0.00
Minimum of Months 35.22 13.12 19.85 76.94 1.15 0.00 0.00 0.00
Maximum of Months 59.82 27.69 35.67 204.21 75.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 8F59F7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 75.07 48.56 26.51 186.00 70.40 0.00 0.00 0.00
February 69.53 40.66 28.88 177.42 57.52 0.00 0.00 0.00
March 55.53 25.08 30.46 138.31 45.72 0.00 0.00 0.00
April 38.15 8.57 29.58 115.33 24.21 0.00 0.00 0.00
May 29.19 1.10 28.09 112.44 5.72 0.00 0.00 0.00
June 27.42 0.11 27.31 124.70 1.15 0.00 0.00 0.00
July 29.51 0.49 29.02 137.30 2.90 0.00 0.00 0.00
August 34.43 3.95 30.48 144.81 1.48 0.00 0.00 0.00
September 44.62 12.40 32.22 180.39 4.93 0.00 0.00 0.00
October 60.27 29.16 31.11 199.39 8.72 0.00 0.00 0.00
November 66.47 37.08 29.39 191.67 29.09 0.00 0.00 0.00
December 72.40 45.44 26.96 183.45 59.05 0.00 0.00 0.00
                 
Annual Sum or Average 50.12 20.96 29.16 157.49 25.77 0.00 0.00 0.00
Minimum of Months 27.42 0.11 26.51 112.44 1.15 0.00 0.00 0.00
Maximum of Months 75.07 48.56 32.22 199.39 70.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 44F571

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 69.61 45.29 24.32 172.99 70.38 0.00 0.00 0.00
February 65.21 38.55 26.66 167.55 57.37 0.00 0.00 0.00
March 52.42 24.19 28.23 131.55 45.27 0.00 0.00 0.00
April 35.93 8.53 27.40 110.45 22.93 0.00 0.00 0.00
May 26.97 1.10 25.87 107.89 5.01 0.00 0.00 0.00
June 25.14 0.11 25.04 120.24 0.89 0.00 0.00 0.00
July 27.08 0.49 26.59 132.23 2.42 0.00 0.00 0.00
August 32.05 3.92 28.13 140.52 1.29 0.00 0.00 0.00
September 42.02 12.13 29.88 174.22 4.24 0.00 0.00 0.00
October 56.55 27.78 28.77 189.80 7.71 0.00 0.00 0.00
November 62.01 34.89 27.12 180.67 28.52 0.00 0.00 0.00
December 68.33 43.44 24.89 173.47 58.40 0.00 0.00 0.00
                 
Annual Sum or Average 46.86 19.95 26.91 150.03 25.23 0.00 0.00 0.00
Minimum of Months 25.14 0.11 24.32 107.89 0.89 0.00 0.00 0.00
Maximum of Months 69.61 45.29 29.88 189.80 70.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 6BD844

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 58.15 39.74 0.00 0.00 0.00
February 30.33 14.02 16.31 71.84 30.72 0.00 0.00 0.00
March 36.81 17.27 19.55 85.54 23.11 0.00 0.00 0.00
April 40.05 17.77 22.28 113.34 11.11 0.00 0.00 0.00
May 37.92 15.02 22.91 127.13 1.96 0.00 0.00 0.00
June 37.44 14.30 23.14 139.81 0.32 0.00 0.00 0.00
July 38.54 13.85 24.68 148.45 1.07 0.00 0.00 0.00
August 35.20 11.70 23.50 132.33 0.41 0.00 0.00 0.00
September 33.93 12.20 21.73 130.82 1.68 0.00 0.00 0.00
October 31.22 13.38 17.83 107.95 3.00 0.00 0.00 0.00
November 25.46 10.17 15.29 75.46 14.26 0.00 0.00 0.00
December 20.68 7.40 13.29 47.95 32.67 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 103.36 13.27 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 47.95 0.32 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 148.45 39.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 86D536

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 58.15 39.74 0.00 0.00 0.00
February 30.33 14.02 16.31 71.84 30.72 0.00 0.00 0.00
March 36.81 17.27 19.55 85.54 23.11 0.00 0.00 0.00
April 40.05 17.77 22.28 113.34 11.11 0.00 0.00 0.00
May 37.92 15.02 22.91 127.13 1.96 0.00 0.00 0.00
June 37.44 14.30 23.14 139.81 0.32 0.00 0.00 0.00
July 38.54 13.85 24.68 148.45 1.07 0.00 0.00 0.00
August 35.20 11.70 23.50 132.33 0.41 0.00 0.00 0.00
September 33.93 12.20 21.73 130.82 1.68 0.00 0.00 0.00
October 31.22 13.38 17.83 107.95 3.00 0.00 0.00 0.00
November 25.46 10.17 15.29 75.46 14.26 0.00 0.00 0.00
December 20.68 7.40 13.29 47.95 32.67 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 103.36 13.27 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 47.95 0.32 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 148.45 39.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BAF71D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 58.15 39.74 0.00 0.00 0.00
February 30.33 14.02 16.31 71.84 30.72 0.00 0.00 0.00
March 36.81 17.27 19.55 85.54 23.11 0.00 0.00 0.00
April 40.05 17.77 22.28 113.34 11.11 0.00 0.00 0.00
May 37.92 15.02 22.91 127.13 1.96 0.00 0.00 0.00
June 37.44 14.30 23.14 139.81 0.32 0.00 0.00 0.00
July 38.54 13.85 24.68 148.45 1.07 0.00 0.00 0.00
August 35.20 11.70 23.50 132.33 0.41 0.00 0.00 0.00
September 33.93 12.20 21.73 130.82 1.68 0.00 0.00 0.00
October 31.22 13.38 17.83 107.95 3.00 0.00 0.00 0.00
November 25.46 10.17 15.29 75.46 14.26 0.00 0.00 0.00
December 20.68 7.40 13.29 47.95 32.67 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 103.36 13.27 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 47.95 0.32 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 148.45 39.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 3833A2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.38 12.68 13.70 58.15 39.74 0.00 0.00 0.00
February 30.33 14.02 16.31 71.84 30.72 0.00 0.00 0.00
March 36.81 17.27 19.55 85.54 23.11 0.00 0.00 0.00
April 40.05 17.77 22.28 113.34 11.11 0.00 0.00 0.00
May 37.92 15.02 22.91 127.13 1.96 0.00 0.00 0.00
June 37.44 14.30 23.14 139.81 0.32 0.00 0.00 0.00
July 38.54 13.85 24.68 148.45 1.07 0.00 0.00 0.00
August 35.20 11.70 23.50 132.33 0.41 0.00 0.00 0.00
September 33.93 12.20 21.73 130.82 1.68 0.00 0.00 0.00
October 31.22 13.38 17.83 107.95 3.00 0.00 0.00 0.00
November 25.46 10.17 15.29 75.46 14.26 0.00 0.00 0.00
December 20.68 7.40 13.29 47.95 32.67 0.00 0.00 0.00
                 
Annual Sum or Average 32.84 13.30 19.53 103.36 13.27 0.00 0.00 0.00
Minimum of Months 20.68 7.40 13.29 47.95 0.32 0.00 0.00 0.00
Maximum of Months 40.05 17.77 24.68 148.45 39.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 2111A1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 8.79 4.23 4.57 21.33 11.82 0.00 0.00 0.00
February 10.11 4.67 5.44 26.36 9.36 0.00 0.00 0.00
March 12.27 5.76 6.52 31.52 7.36 0.00 0.00 0.00
April 13.35 5.92 7.43 39.97 4.64 0.00 0.00 0.00
May 12.64 5.01 7.64 42.32 1.79 0.00 0.00 0.00
June 12.48 4.77 7.71 45.15 0.66 0.00 0.00 0.00
July 12.85 4.62 8.23 48.08 1.16 0.00 0.00 0.00
August 11.73 3.90 7.83 42.19 0.62 0.50 0.00 0.00
September 11.31 4.07 7.24 42.26 1.55 0.00 0.00 0.00
October 10.41 4.46 5.94 35.16 2.32 0.00 0.00 0.00
November 8.49 3.39 5.10 25.34 5.40 2.33 0.00 0.00
December 6.89 2.47 4.43 17.15 9.98 0.00 0.00 0.00
                 
Annual Sum or Average 10.95 4.43 6.51 34.77 4.70 2.83 0.00 0.00
Minimum of Months 6.89 2.47 4.43 17.15 0.62 0.00 0.00 0.00
Maximum of Months 13.35 5.92 8.23 48.08 11.82 2.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 9BC521

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.94 0.00 20.94 36.78 75.93 0.00 0.00 0.00
February 24.79 0.00 24.79 55.53 59.69 0.00 0.00 0.00
March 29.56 0.00 29.56 64.85 47.75 0.00 0.00 0.00
April 33.23 0.26 32.97 97.16 25.05 0.00 0.00 0.00
May 38.50 2.37 36.13 142.57 8.10 0.00 0.00 0.00
June 41.33 3.84 37.50 171.04 2.89 0.00 0.00 0.00
July 41.62 2.73 38.88 179.34 5.53 0.00 0.00 0.00
August 36.37 0.52 35.85 152.82 2.96 0.50 0.00 0.00
September 32.10 0.01 32.10 144.29 8.16 0.00 0.00 0.00
October 26.89 0.00 26.89 103.41 11.60 0.00 0.00 0.00
November 23.38 0.00 23.38 70.88 32.57 2.50 0.00 0.00
December 20.71 0.00 20.71 42.28 62.54 0.00 0.00 0.00
                 
Annual Sum or Average 30.82 0.81 30.00 105.31 28.43 3.00 0.00 0.00
Minimum of Months 20.71 0.00 20.71 36.78 2.89 0.00 0.00 0.00
Maximum of Months 41.62 3.84 38.88 179.34 75.93 2.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 142781

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.45 0.00 20.45 36.83 73.22 0.00 0.00 0.00
February 24.21 0.00 24.21 55.44 57.55 0.00 0.00 0.00
March 28.87 0.00 28.87 64.88 46.06 0.00 0.00 0.00
April 32.45 0.25 32.20 96.30 24.56 0.00 0.00 0.00
May 37.60 2.32 35.29 140.25 8.17 0.00 0.00 0.00
June 40.37 3.75 36.62 167.69 2.91 0.00 0.00 0.00
July 40.64 2.67 37.98 175.65 5.53 0.00 0.00 0.00
August 35.52 0.50 35.01 149.20 2.89 0.50 0.00 0.00
September 31.34 0.00 31.34 140.93 8.07 0.00 0.00 0.00
October 26.27 0.00 26.27 101.14 11.61 0.00 0.00 0.00
November 22.84 0.00 22.84 69.92 31.66 2.33 0.00 0.00
December 20.23 0.00 20.23 42.29 60.13 0.00 0.00 0.00
                 
Annual Sum or Average 30.10 0.80 29.30 103.60 27.57 2.83 0.00 0.00
Minimum of Months 20.23 0.00 20.23 36.83 2.89 0.00 0.00 0.00
Maximum of Months 40.64 3.75 37.98 175.65 73.22 2.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: E74902

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.45 0.00 20.45 38.44 78.44 0.00 0.00 0.00
February 24.21 0.00 24.21 56.53 63.01 0.00 0.00 0.00
March 28.87 0.00 28.87 65.13 51.82 0.00 0.00 0.00
April 32.45 0.25 32.20 94.74 30.60 0.00 0.00 0.00
May 37.60 2.32 35.29 136.81 12.22 0.00 0.00 0.00
June 40.37 3.75 36.62 163.23 4.33 0.00 0.00 0.00
July 40.64 2.67 37.98 171.86 7.84 0.00 0.00 0.00
August 35.52 0.50 35.02 144.50 4.60 0.50 0.00 0.00
September 31.35 0.00 31.35 138.35 10.18 0.00 0.00 0.00
October 26.27 0.00 26.27 99.86 15.16 0.00 0.00 0.00
November 22.84 0.00 22.84 69.44 35.90 0.00 0.00 0.00
December 20.23 0.00 20.23 42.37 65.92 0.00 0.00 0.00
                 
Annual Sum or Average 30.10 0.80 29.30 101.98 31.54 0.50 0.00 0.00
Minimum of Months 20.23 0.00 20.23 38.44 4.33 0.00 0.00 0.00
Maximum of Months 40.64 3.75 37.98 171.86 78.44 0.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: 93BBC3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.45 0.00 20.45 37.55 79.44 0.00 0.00 0.00
February 24.21 0.00 24.21 55.34 63.89 0.00 0.00 0.00
March 28.87 0.00 28.87 63.57 52.52 0.00 0.00 0.00
April 32.45 0.25 32.20 93.28 30.61 0.00 0.00 0.00
May 37.60 2.32 35.29 135.65 11.96 0.00 0.00 0.00
June 40.37 3.75 36.62 162.45 4.23 0.00 0.00 0.00
July 40.64 2.67 37.98 171.25 7.70 0.00 0.00 0.00
August 35.52 0.50 35.02 144.41 4.58 0.50 0.00 0.00
September 31.35 0.00 31.35 138.22 10.09 0.00 0.00 0.00
October 26.27 0.00 26.27 99.63 14.87 0.00 0.00 0.00
November 22.84 0.00 22.84 68.67 36.09 0.00 0.00 0.00
December 20.23 0.00 20.23 41.38 66.99 0.00 0.00 0.00
                 
Annual Sum or Average 30.10 0.80 29.30 101.16 31.78 0.50 0.00 0.00
Minimum of Months 20.23 0.00 20.23 37.55 4.23 0.00 0.00 0.00
Maximum of Months 40.64 3.75 37.98 171.25 79.44 0.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: C635A6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.13 11.74 6.39 47.80 17.91 0.00 0.00 0.00
February 16.46 9.55 6.91 45.16 14.65 0.00 0.00 0.00
March 13.40 6.02 7.37 36.32 11.99 0.00 0.00 0.00
April 9.36 2.14 7.22 29.94 7.19 0.00 0.00 0.00
May 7.11 0.27 6.84 27.70 2.51 0.00 0.00 0.00
June 6.66 0.03 6.64 29.85 0.74 0.00 0.00 0.00
July 7.18 0.12 7.06 32.96 1.41 0.00 0.00 0.00
August 8.41 0.98 7.42 34.68 0.86 0.50 0.00 0.00
September 10.87 3.04 7.83 43.80 2.06 0.00 0.00 0.00
October 14.39 6.90 7.49 48.40 3.73 0.00 0.00 0.00
November 15.81 8.76 7.05 47.31 8.49 0.00 0.00 0.00
December 17.84 11.27 6.57 47.85 15.03 0.00 0.00 0.00
                 
Annual Sum or Average 12.11 5.05 7.07 39.28 7.18 0.50 0.00 0.00
Minimum of Months 6.66 0.03 6.39 27.70 0.74 0.00 0.00 0.00
Maximum of Months 18.13 11.74 7.83 48.40 17.91 0.50 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: 78F987

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101737E+09 65661223.82 36075611.73 0.275047E+09 88603161.56
February 84915699.29 49459508.55 35456190.74 0.243643E+09 61867722.89
March 74947388.71 33662616.98 41284771.73 0.220978E+09 49864155.19
April 49921288.83 11108213.35 38813075.48 0.188018E+09 17459296.50
May 39597774.01 1467330.04 38130443.97 0.205551E+09 2644974.87
June 36032133.23 140670.24 35891462.98 0.220186E+09 85307.17
July 40074932.30 657614.49 39417317.81 0.247316E+09 374610.37
August 46636007.53 5290557.83 41345449.69 0.254731E+09 38513.96
September 58318190.90 16085710.26 42232480.64 0.289564E+09 546372.92
October 81369349.95 39171335.94 42198014.01 0.316014E+09 3999604.16
November 87085456.26 48407152.59 38678303.67 0.284772E+09 31613095.67
December 97638493.76 60992629.69 36645864.07 0.274996E+09 73523138.75
           
Annual Sum or Average 0.798274E+09 0.332105E+09 0.466169E+09 0.302082E+10 0.330620E+09
Minimum of Months 36032133.23 140670.24 35456190.74 0.188018E+09 38513.96
Maximum of Months 0.101737E+09 65661223.82 42232480.64 0.316014E+09 88603161.56



Table of Contents

Report: WindowEnergyReportMonthly

For: D8037E

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.351052E+09 0.222010E+09 0.129041E+09 0.892302E+09 0.476855E+09
February 0.296567E+09 0.168856E+09 0.127710E+09 0.788548E+09 0.354761E+09
March 0.272453E+09 0.120240E+09 0.152213E+09 0.715356E+09 0.317017E+09
April 0.188733E+09 43281373.40 0.145452E+09 0.588263E+09 0.180561E+09
May 0.148655E+09 5869261.93 0.142786E+09 0.560938E+09 72033186.90
June 0.134324E+09 562680.98 0.133761E+09 0.564683E+09 24495657.68
July 0.149810E+09 2626553.45 0.147183E+09 0.657169E+09 40532444.07
August 0.175358E+09 20587735.90 0.154770E+09 0.671183E+09 32050421.23
September 0.215692E+09 59342191.00 0.156350E+09 0.831349E+09 54725737.09
October 0.289058E+09 0.135337E+09 0.153721E+09 0.936284E+09 0.102539E+09
November 0.302865E+09 0.164091E+09 0.138774E+09 0.873086E+09 0.224169E+09
December 0.355363E+09 0.222495E+09 0.132868E+09 0.925123E+09 0.401808E+09
           
Annual Sum or Average 0.287993E+10 0.116530E+10 0.171463E+10 0.900428E+10 0.228155E+10
Minimum of Months 0.134324E+09 562680.98 0.127710E+09 0.560938E+09 24495657.68
Maximum of Months 0.355363E+09 0.222495E+09 0.156350E+09 0.936284E+09 0.476855E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 4A8120

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 21186716.46 0.00 21186716.46 39206270.38 0.102278E+09
February 22681496.38 0.00 22681496.38 55354467.30 71713102.09
March 29972029.19 0.00 29972029.19 73175283.04 61299995.91
April 32241609.08 69690.65 32171918.42 0.106503E+09 28934321.97
May 37021224.92 1338560.83 35682664.09 0.155814E+09 7609053.00
June 38160255.95 2594172.46 35566083.49 0.181475E+09 1795476.11
July 39776659.29 1658212.69 38118446.60 0.196305E+09 3830281.62
August 35975636.35 275136.91 35700499.44 0.169454E+09 2408959.60
September 31267894.68 668.87 31267225.80 0.157378E+09 7399971.39
October 27172038.60 0.00 27172038.60 0.115698E+09 13165264.04
November 22804310.29 0.00 22804310.29 75136024.98 41603346.99
December 20894937.27 0.00 20894937.27 44716318.63 85343852.69
           
Annual Sum or Average 0.359155E+09 5936442.43 0.353218E+09 0.137022E+10 0.427381E+09
Minimum of Months 20894937.27 0.00 20894937.27 39206270.38 1795476.11
Maximum of Months 39776659.29 2594172.46 38118446.60 0.196305E+09 0.102278E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: AAE778

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.187218E+09 82335982.30 0.104882E+09 0.439019E+09 0.446507E+09
February 0.210806E+09 96702861.51 0.114103E+09 0.547938E+09 0.330237E+09
March 0.289780E+09 0.133446E+09 0.156334E+09 0.751223E+09 0.300203E+09
April 0.308172E+09 0.143523E+09 0.164650E+09 0.913193E+09 0.168352E+09
May 0.290536E+09 0.113155E+09 0.177381E+09 0.990264E+09 62496768.99
June 0.237956E+09 68079193.73 0.169877E+09 0.920015E+09 18035389.38
July 0.275422E+09 86842515.09 0.188579E+09 0.108393E+10 31529555.81
August 0.274394E+09 90838446.41 0.183556E+09 0.100141E+10 20059617.11
September 0.226344E+09 68023261.12 0.158321E+09 0.892044E+09 44009457.28
October 0.233458E+09 92415543.91 0.141043E+09 0.792017E+09 80609661.45
November 0.186830E+09 70144857.63 0.116685E+09 0.562965E+09 0.197690E+09
December 0.194017E+09 88540459.63 0.105476E+09 0.484819E+09 0.374834E+09
           
Annual Sum or Average 0.291493E+10 0.113405E+10 0.178089E+10 0.937884E+10 0.207456E+10
Minimum of Months 0.186830E+09 68023261.12 0.104882E+09 0.439019E+09 18035389.38
Maximum of Months 0.308172E+09 0.143523E+09 0.188579E+09 0.108393E+10 0.446507E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 3AAD8B

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 23756986.91 0.00 23756986.91 41210998.07 0.148627E+09
February 25461508.99 0.00 25461508.99 59377425.51 0.107874E+09
March 33670747.63 0.00 33670747.63 79012676.55 95681832.09
April 36015505.73 66581.35 35948924.38 0.118534E+09 46637660.78
May 42019852.76 1547330.51 40472522.25 0.180014E+09 13878047.12
June 42780633.71 2337330.38 40443303.32 0.210603E+09 3158343.87
July 45004521.80 1822981.54 43181540.26 0.233514E+09 5394516.25
August 40331770.36 238424.03 40093346.33 0.200040E+09 4010503.26
September 35087158.61 0.00 35087158.61 0.188373E+09 9605887.87
October 30380881.41 0.00 30380881.41 0.135796E+09 18450163.82
November 25606315.44 0.00 25606315.44 84537433.23 60822208.03
December 23458811.92 0.00 23458811.92 48244649.01 0.123873E+09
           
Annual Sum or Average 0.403575E+09 6012647.81 0.397562E+09 0.157926E+10 0.638013E+09
Minimum of Months 23458811.92 0.00 23458811.92 41210998.07 3158343.87
Maximum of Months 45004521.80 2337330.38 43181540.26 0.233514E+09 0.148627E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 8128A9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25950690.05 0.00 25950690.05 44725601.80 0.151677E+09
February 27767481.86 0.00 27767481.86 63452476.45 0.110405E+09
March 36683038.92 0.00 36683038.92 84906427.82 98282258.40
April 39155019.30 41332.82 39113686.48 0.125208E+09 49301506.79
May 46440268.54 2102920.42 44337348.12 0.190632E+09 15563734.17
June 48397193.66 3720218.57 44676975.10 0.225136E+09 3916723.82
July 50400065.31 2736215.34 47663849.97 0.247305E+09 6507546.01
August 44200061.48 298753.56 43901307.92 0.206945E+09 4576205.36
September 38438857.98 6.57 38438851.41 0.195458E+09 10983200.37
October 33263115.84 0.00 33263115.84 0.140947E+09 20697087.44
November 28057796.56 0.00 28057796.56 89114672.79 63385512.89
December 25681187.27 0.00 25681187.27 52285363.98 0.126258E+09
           
Annual Sum or Average 0.444435E+09 8899447.27 0.435535E+09 0.166612E+10 0.661554E+09
Minimum of Months 25681187.27 0.00 25681187.27 44725601.80 3916723.82
Maximum of Months 50400065.31 3720218.57 47663849.97 0.247305E+09 0.151677E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 9B1541

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101737E+09 65661223.82 36075611.73 0.293494E+09 82867641.62
February 84915699.29 49459508.55 35456190.74 0.258763E+09 60012653.28
March 74947388.71 33662616.98 41284771.73 0.232710E+09 50149172.41
April 49921288.83 11108213.35 38813075.48 0.192122E+09 22022200.55
May 39597774.01 1467330.04 38130443.97 0.198069E+09 4397488.89
June 36032133.23 140670.24 35891462.98 0.206061E+09 677617.45
July 40074932.30 657614.49 39417317.81 0.228812E+09 2066365.32
August 46636007.53 5290557.83 41345449.69 0.238030E+09 698837.45
September 58318190.90 16085710.26 42232480.64 0.279437E+09 3852712.46
October 81369349.95 39171335.94 42198014.01 0.317103E+09 7394533.87
November 87085456.26 48407152.59 38678303.67 0.296219E+09 31591156.63
December 97638493.76 60992629.69 36645864.07 0.292479E+09 68659641.96
           
Annual Sum or Average 0.798274E+09 0.332105E+09 0.466169E+09 0.303330E+10 0.334390E+09
Minimum of Months 36032133.23 140670.24 35456190.74 0.192122E+09 677617.45
Maximum of Months 0.101737E+09 65661223.82 42232480.64 0.317103E+09 82867641.62



Table of Contents

Report: WindowEnergyReportMonthly

For: CF850A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101737E+09 65661223.82 36075611.73 0.293494E+09 82867641.62
February 84915699.29 49459508.55 35456190.74 0.258763E+09 60012653.28
March 74947388.71 33662616.98 41284771.73 0.232710E+09 50149172.41
April 49921288.83 11108213.35 38813075.48 0.192122E+09 22022200.55
May 39597774.01 1467330.04 38130443.97 0.198000E+09 4406684.93
June 36032133.23 140670.24 35891462.98 0.205996E+09 677617.45
July 40074932.30 657614.49 39417317.81 0.228749E+09 2066365.32
August 46636007.53 5290557.83 41345449.69 0.238017E+09 698837.45
September 58318190.90 16085710.26 42232480.64 0.279437E+09 3852712.46
October 81369349.95 39171335.94 42198014.01 0.317103E+09 7394533.87
November 87085456.26 48407152.59 38678303.67 0.296219E+09 31591156.63
December 97638493.76 60992629.69 36645864.07 0.292479E+09 68659641.96
           
Annual Sum or Average 0.798274E+09 0.332105E+09 0.466169E+09 0.303309E+10 0.334399E+09
Minimum of Months 36032133.23 140670.24 35456190.74 0.192122E+09 677617.45
Maximum of Months 0.101737E+09 65661223.82 42232480.64 0.317103E+09 82867641.62



Table of Contents

Report: WindowEnergyReportMonthly

For: A6BA23

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.194474E+09 0.110952E+09
February 73380118.53 33924372.54 39455745.99 0.218651E+09 79063592.58
March 98604584.71 46249407.74 52355176.96 0.288628E+09 64526476.76
April 0.103815E+09 46059140.94 57755855.00 0.357620E+09 29165850.86
May 0.101570E+09 40218118.41 61351436.62 0.409338E+09 5867364.09
June 97050161.53 37072682.97 59977478.57 0.426283E+09 954096.28
July 0.103218E+09 37108915.32 66108616.44 0.461756E+09 2801823.39
August 94271106.47 31339436.79 62931669.67 0.408888E+09 987703.67
September 87934116.79 31613674.19 56320442.61 0.393159E+09 5269431.03
October 83611947.41 35845426.47 47766520.94 0.337887E+09 10156496.60
November 65989252.20 26367438.26 39621813.94 0.238073E+09 41783579.97
December 55401550.76 19815667.15 35585883.61 0.165629E+09 91854733.19
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.390039E+10 0.443383E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.165629E+09 954096.28
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.461756E+09 0.110952E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: D10D28

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.193572E+09 0.111283E+09
February 73380118.53 33924372.54 39455745.99 0.218197E+09 79097707.81
March 98604584.71 46249407.74 52355176.96 0.288593E+09 64527750.73
April 0.103815E+09 46059140.94 57755855.00 0.357620E+09 29165850.86
May 0.101570E+09 40218118.41 61351436.62 0.409338E+09 5867364.09
June 97050161.53 37072682.97 59977478.57 0.426283E+09 954096.28
July 0.103218E+09 37108915.32 66108616.44 0.461756E+09 2801823.39
August 94271106.47 31339436.79 62931669.67 0.408888E+09 987703.67
September 87934116.79 31613674.19 56320442.61 0.393151E+09 5269431.03
October 83611947.41 35845426.47 47766520.94 0.337727E+09 10156502.77
November 65989252.20 26367438.26 39621813.94 0.237372E+09 41792143.65
December 55401550.76 19815667.15 35585883.61 0.164292E+09 92082765.98
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.389679E+10 0.443986E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.164292E+09 954096.28
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.461756E+09 0.111283E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 591336

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.196961E+09 0.110570E+09
February 73380118.53 33924372.54 39455745.99 0.221269E+09 78777739.63
March 98604584.71 46249407.74 52355176.96 0.290779E+09 64884754.38
April 0.103815E+09 46059140.94 57755855.00 0.359195E+09 29681177.26
May 0.101570E+09 40218118.41 61351436.62 0.411564E+09 5991846.99
June 97050161.53 37072682.97 59977478.57 0.429902E+09 958635.27
July 0.103218E+09 37108915.32 66108616.44 0.466700E+09 2706936.99
August 94271106.47 31339436.79 62931669.67 0.415476E+09 860165.82
September 87934116.79 31613674.19 56320442.61 0.400888E+09 4804103.28
October 83611947.41 35845426.47 47766520.94 0.345406E+09 9279290.89
November 65989252.20 26367438.26 39621813.94 0.243040E+09 41026609.59
December 55401550.76 19815667.15 35585883.61 0.168238E+09 91001500.14
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.394942E+10 0.440543E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.168238E+09 860165.82
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.466700E+09 0.110570E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 38B811

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.196961E+09 0.110570E+09
February 73380118.53 33924372.54 39455745.99 0.221269E+09 78777739.63
March 98604584.71 46249407.74 52355176.96 0.290779E+09 64884754.38
April 0.103815E+09 46059140.94 57755855.00 0.359195E+09 29681177.26
May 0.101570E+09 40218118.41 61351436.62 0.411564E+09 5991846.99
June 97050161.53 37072682.97 59977478.57 0.429902E+09 958635.27
July 0.103218E+09 37108915.32 66108616.44 0.466700E+09 2706936.99
August 94271106.47 31339436.79 62931669.67 0.415476E+09 860165.82
September 87934116.79 31613674.19 56320442.61 0.400888E+09 4804103.28
October 83611947.41 35845426.47 47766520.94 0.345406E+09 9279290.89
November 65989252.20 26367438.26 39621813.94 0.243040E+09 41026609.59
December 55401550.76 19815667.15 35585883.61 0.168238E+09 91001500.14
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.394942E+10 0.440543E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.168238E+09 860165.82
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.466700E+09 0.110570E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C044D6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.196961E+09 0.110570E+09
February 73380118.53 33924372.54 39455745.99 0.221269E+09 78777739.63
March 98604584.71 46249407.74 52355176.96 0.290779E+09 64884754.38
April 0.103815E+09 46059140.94 57755855.00 0.359195E+09 29681177.26
May 0.101570E+09 40218118.41 61351436.62 0.411564E+09 5991846.99
June 97050161.53 37072682.97 59977478.57 0.429902E+09 958635.27
July 0.103218E+09 37108915.32 66108616.44 0.466700E+09 2706936.99
August 94271106.47 31339436.79 62931669.67 0.415476E+09 860165.82
September 87934116.79 31613674.19 56320442.61 0.400888E+09 4804103.28
October 83611947.41 35845426.47 47766520.94 0.345406E+09 9279290.89
November 65989252.20 26367438.26 39621813.94 0.243040E+09 41026609.59
December 55401550.76 19815667.15 35585883.61 0.168238E+09 91001500.14
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.394942E+10 0.440543E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.168238E+09 860165.82
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.466700E+09 0.110570E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 1D94BE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 26914288.86 0.00 26914288.86 61028339.40 0.116337E+09
February 28782028.03 0.00 28782028.03 82777828.75 80364330.14
March 38008947.93 0.00 38008947.93 0.110182E+09 66908493.33
April 40667625.17 56788.43 40610836.74 0.159665E+09 23595787.19
May 47717041.65 1999597.21 45717444.44 0.246554E+09 3962262.59
June 50282054.03 4096469.80 46185584.23 0.289893E+09 235811.39
July 51988274.92 2754683.34 49233591.57 0.312050E+09 686284.13
August 45766134.59 308869.42 45457265.18 0.273290E+09 151658.02
September 39861573.78 162.93 39861410.86 0.252192E+09 1006552.43
October 34543924.56 0.00 34543924.56 0.190819E+09 4630360.68
November 29091012.48 0.00 29091012.48 0.123584E+09 40542766.95
December 26626485.87 0.00 26626485.87 72751994.16 94335868.18
           
Annual Sum or Average 0.460249E+09 9216571.12 0.451033E+09 0.217479E+10 0.432758E+09
Minimum of Months 26626485.87 0.00 26626485.87 61028339.40 151658.02
Maximum of Months 51988274.92 4096469.80 49233591.57 0.312050E+09 0.116337E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 18748E

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 26623510.93 0.00 26623510.93 60606523.25 0.115782E+09
February 28476947.57 0.00 28476947.57 82306774.40 79936248.74
March 37610637.07 0.00 37610637.07 0.109484E+09 66480151.79
April 40318124.47 72533.34 40245591.13 0.159158E+09 23233670.27
May 46551622.75 1641954.14 44909668.61 0.243525E+09 3851548.28
June 48659877.81 3514274.56 45145603.25 0.285214E+09 220222.07
July 50458845.76 2224991.20 48233854.55 0.307663E+09 650793.84
August 45182832.79 304016.51 44878816.28 0.272445E+09 143446.74
September 39402522.96 385.89 39402137.07 0.251466E+09 933586.08
October 34167119.52 0.00 34167119.52 0.190489E+09 4477538.61
November 28750595.02 0.00 28750595.02 0.123126E+09 40229027.40
December 26320948.35 0.00 26320948.35 72248761.48 93933752.79
           
Annual Sum or Average 0.452524E+09 7758155.65 0.444765E+09 0.215773E+10 0.429872E+09
Minimum of Months 26320948.35 0.00 26320948.35 60606523.25 143446.74
Maximum of Months 50458845.76 3514274.56 48233854.55 0.307663E+09 0.115782E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 137A56

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.107760E+09 65598671.76 42161496.37 0.281114E+09 0.175095E+09
February 95086078.67 52795953.87 42290124.80 0.262537E+09 0.127357E+09
March 88866022.68 38130217.01 50735805.68 0.244099E+09 0.111447E+09
April 62821461.12 14003162.04 48818299.08 0.213772E+09 53586302.30
May 50288004.53 2105679.26 48182325.27 0.223366E+09 13782722.85
June 45166647.37 210719.42 44955927.95 0.240378E+09 2686809.36
July 50608088.10 939284.79 49668803.30 0.277620E+09 5148518.83
August 58586836.41 6801179.70 51785656.72 0.282792E+09 3897491.41
September 70315072.44 18668341.27 51646731.18 0.324582E+09 10293988.51
October 93141565.02 42378918.09 50762646.93 0.340076E+09 21071190.79
November 96558123.58 51014584.54 45543539.03 0.301224E+09 71829210.68
December 0.111622E+09 68691395.59 42930509.60 0.300895E+09 0.145826E+09
           
Annual Sum or Average 0.930820E+09 0.361338E+09 0.569482E+09 0.329246E+10 0.742021E+09
Minimum of Months 45166647.37 210719.42 42161496.37 0.213772E+09 2686809.36
Maximum of Months 0.111622E+09 68691395.59 51785656.72 0.340076E+09 0.175095E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 8D508E

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101737E+09 65661223.82 36075611.73 0.270908E+09 93403230.37
February 84915699.29 49459508.55 35456190.74 0.240058E+09 65508646.33
March 74947388.71 33662616.98 41284771.73 0.217698E+09 52881858.38
April 49921288.83 11108213.35 38813075.48 0.185520E+09 19147409.20
May 39597774.01 1467330.04 38130443.97 0.202498E+09 2950838.70
June 36032133.23 140670.24 35891462.98 0.217584E+09 119650.00
July 40074932.30 657614.49 39417317.81 0.244573E+09 466836.36
August 46636007.53 5290557.83 41345449.69 0.250601E+09 81941.24
September 58318190.90 16085710.26 42232480.64 0.284623E+09 838308.38
October 81369349.95 39171335.94 42198014.01 0.309534E+09 5110551.02
November 87085456.26 48407152.59 38678303.67 0.279208E+09 34243120.39
December 97638493.76 60992629.69 36645864.07 0.270875E+09 77855612.63
           
Annual Sum or Average 0.798274E+09 0.332105E+09 0.466169E+09 0.297368E+10 0.352608E+09
Minimum of Months 36032133.23 140670.24 35456190.74 0.185520E+09 81941.24
Maximum of Months 0.101737E+09 65661223.82 42232480.64 0.309534E+09 93403230.37



Table of Contents

Report: WindowEnergyReportMonthly

For: B2D381

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101737E+09 65661223.82 36075611.73 0.270908E+09 93403230.37
February 84915699.29 49459508.55 35456190.74 0.240058E+09 65508646.33
March 74947388.71 33662616.98 41284771.73 0.217698E+09 52881858.38
April 49921288.83 11108213.35 38813075.48 0.185520E+09 19147409.20
May 39597774.01 1467330.04 38130443.97 0.202498E+09 2950838.70
June 36032133.23 140670.24 35891462.98 0.217584E+09 119650.00
July 40074932.30 657614.49 39417317.81 0.244573E+09 466836.36
August 46636007.53 5290557.83 41345449.69 0.250601E+09 81941.24
September 58318190.90 16085710.26 42232480.64 0.284623E+09 838308.38
October 81369349.95 39171335.94 42198014.01 0.309534E+09 5110551.02
November 87085456.26 48407152.59 38678303.67 0.279208E+09 34243120.39
December 97638493.76 60992629.69 36645864.07 0.270875E+09 77855612.63
           
Annual Sum or Average 0.798274E+09 0.332105E+09 0.466169E+09 0.297368E+10 0.352608E+09
Minimum of Months 36032133.23 140670.24 35456190.74 0.185520E+09 81941.24
Maximum of Months 0.101737E+09 65661223.82 42232480.64 0.309534E+09 93403230.37



Table of Contents

Report: WindowEnergyReportMonthly

For: 1DA13A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101737E+09 65661223.82 36075611.73 0.270908E+09 93403230.37
February 84915699.29 49459508.55 35456190.74 0.240058E+09 65508646.33
March 74947388.71 33662616.98 41284771.73 0.217698E+09 52881858.38
April 49921288.83 11108213.35 38813075.48 0.185520E+09 19147409.20
May 39597774.01 1467330.04 38130443.97 0.202498E+09 2950838.70
June 36032133.23 140670.24 35891462.98 0.217584E+09 119650.00
July 40074932.30 657614.49 39417317.81 0.244573E+09 466836.36
August 46636007.53 5290557.83 41345449.69 0.250601E+09 81941.24
September 58318190.90 16085710.26 42232480.64 0.284623E+09 838308.38
October 81369349.95 39171335.94 42198014.01 0.309534E+09 5110551.02
November 87085456.26 48407152.59 38678303.67 0.279208E+09 34243120.39
December 97638493.76 60992629.69 36645864.07 0.270875E+09 77855612.63
           
Annual Sum or Average 0.798274E+09 0.332105E+09 0.466169E+09 0.297368E+10 0.352608E+09
Minimum of Months 36032133.23 140670.24 35456190.74 0.185520E+09 81941.24
Maximum of Months 0.101737E+09 65661223.82 42232480.64 0.309534E+09 93403230.37



Table of Contents

Report: WindowEnergyReportMonthly

For: 44E54A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101737E+09 65661223.82 36075611.73 0.270908E+09 93403230.37
February 84915699.29 49459508.55 35456190.74 0.240058E+09 65508646.33
March 74947388.71 33662616.98 41284771.73 0.217698E+09 52881858.38
April 49921288.83 11108213.35 38813075.48 0.185520E+09 19147409.20
May 39597774.01 1467330.04 38130443.97 0.202498E+09 2950838.70
June 36032133.23 140670.24 35891462.98 0.217584E+09 119650.00
July 40074932.30 657614.49 39417317.81 0.244573E+09 466836.36
August 46636007.53 5290557.83 41345449.69 0.250601E+09 81941.24
September 58318190.90 16085710.26 42232480.64 0.284623E+09 838308.38
October 81369349.95 39171335.94 42198014.01 0.309534E+09 5110551.02
November 87085456.26 48407152.59 38678303.67 0.279208E+09 34243120.39
December 97638493.76 60992629.69 36645864.07 0.270875E+09 77855612.63
           
Annual Sum or Average 0.798274E+09 0.332105E+09 0.466169E+09 0.297368E+10 0.352608E+09
Minimum of Months 36032133.23 140670.24 35456190.74 0.185520E+09 81941.24
Maximum of Months 0.101737E+09 65661223.82 42232480.64 0.309534E+09 93403230.37



Table of Contents

Report: WindowEnergyReportMonthly

For: 757D10

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 19204090.60 11246719.39 7957371.20 50707183.10 33871272.81
February 17088414.95 9078636.05 8009778.89 48736890.94 23805939.41
March 16255035.00 6551197.27 9703837.73 46551261.58 20049440.39
April 11563824.63 2195482.40 9368342.23 43019973.89 7752096.30
May 9629382.17 327088.49 9302293.69 50537065.84 1258134.92
June 8749085.10 35772.55 8713312.55 56022431.99 81458.01
July 9774193.22 147389.51 9626803.71 63654853.28 345222.43
August 10933586.52 1079962.72 9853623.81 63130006.51 191955.73
September 12613282.59 2964793.20 9648489.39 67523066.91 615230.59
October 16824306.39 7268740.09 9555566.30 68560088.15 2088049.17
November 17370189.31 8834560.97 8535628.34 58227024.47 12526136.06
December 20731956.35 12610818.37 8121137.98 57158348.90 27964863.41
           
Annual Sum or Average 0.170737E+09 62341161.02 0.108396E+09 0.673828E+09 0.130550E+09
Minimum of Months 8749085.10 35772.55 7957371.20 43019973.89 81458.01
Maximum of Months 20731956.35 12610818.37 9853623.81 68560088.15 33871272.81



Table of Contents

Report: WindowEnergyReportMonthly

For: E33BAE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 44413765.70 20583995.58 23829770.12 0.109313E+09 94434024.07
February 50187958.65 24175715.38 26012243.27 0.139185E+09 65803093.85
March 69161593.40 33361436.11 35800157.29 0.194843E+09 53358697.22
April 73586971.55 35880649.76 37706321.80 0.245400E+09 18876294.64
May 68780553.96 28287938.09 40492615.87 0.282832E+09 2859556.26
June 55454290.05 16929697.56 38524592.49 0.272226E+09 109449.21
July 64626688.14 21687560.37 42939127.77 0.313470E+09 477655.59
August 64529762.93 22709611.60 41820151.32 0.291544E+09 153426.41
September 52945337.47 17005815.28 35939522.19 0.251514E+09 954276.78
October 55220253.62 23103885.98 32116367.64 0.217337E+09 5101573.70
November 44045288.56 17536214.41 26509074.16 0.149248E+09 34496313.34
December 46088982.14 22135114.91 23953867.23 0.122478E+09 77599664.12
           
Annual Sum or Average 0.689041E+09 0.283398E+09 0.405644E+09 0.258939E+10 0.354224E+09
Minimum of Months 44045288.56 16929697.56 23829770.12 0.109313E+09 109449.21
Maximum of Months 73586971.55 35880649.76 42939127.77 0.313470E+09 94434024.07



Table of Contents

Report: WindowEnergyReportMonthly

For: 24167A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101737E+09 65661223.82 36075611.73 0.270016E+09 93187696.79
February 84915699.29 49459508.55 35456190.74 0.237881E+09 66270061.67
March 74947388.71 33662616.98 41284771.73 0.213435E+09 54911660.14
April 49921288.83 11108213.35 38813075.48 0.178183E+09 22524975.64
May 39597774.01 1467330.04 38130443.97 0.190357E+09 3776435.97
June 36032133.23 140670.24 35891462.98 0.205571E+09 232049.74
July 40074932.30 657614.49 39417317.81 0.229739E+09 840018.64
August 46636007.53 5290557.83 41345449.69 0.234713E+09 301791.53
September 58318190.90 16085710.26 42232480.64 0.270923E+09 1818664.17
October 81369349.95 39171335.94 42198014.01 0.298532E+09 7082465.31
November 87085456.26 48407152.59 38678303.67 0.273688E+09 35858219.00
December 97638493.76 60992629.69 36645864.07 0.268485E+09 78574247.39
           
Annual Sum or Average 0.798274E+09 0.332105E+09 0.466169E+09 0.287152E+10 0.365378E+09
Minimum of Months 36032133.23 140670.24 35456190.74 0.178183E+09 232049.74
Maximum of Months 0.101737E+09 65661223.82 42232480.64 0.298532E+09 93187696.79



Table of Contents

Report: WindowEnergyReportMonthly

For: 2C0938

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101737E+09 65661223.82 36075611.73 0.270016E+09 93187696.79
February 84915699.29 49459508.55 35456190.74 0.237881E+09 66270061.67
March 74947388.71 33662616.98 41284771.73 0.213435E+09 54911660.14
April 49921288.83 11108213.35 38813075.48 0.178190E+09 22523206.07
May 39597774.01 1467330.04 38130443.97 0.190385E+09 3776435.90
June 36032133.23 140670.24 35891462.98 0.205567E+09 232049.74
July 40074932.30 657614.49 39417317.81 0.229748E+09 840018.64
August 46636007.53 5290557.83 41345449.69 0.234722E+09 301789.49
September 58318190.90 16085710.26 42232480.64 0.270923E+09 1818664.17
October 81369349.95 39171335.94 42198014.01 0.298532E+09 7082465.31
November 87085456.26 48407152.59 38678303.67 0.273688E+09 35858219.00
December 97638493.76 60992629.69 36645864.07 0.268485E+09 78574247.39
           
Annual Sum or Average 0.798274E+09 0.332105E+09 0.466169E+09 0.287157E+10 0.365377E+09
Minimum of Months 36032133.23 140670.24 35456190.74 0.178190E+09 232049.74
Maximum of Months 0.101737E+09 65661223.82 42232480.64 0.298532E+09 93187696.79



Table of Contents

Report: WindowEnergyReportMonthly

For: 8600DD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101737E+09 65661223.82 36075611.73 0.271010E+09 94959573.62
February 84915699.29 49459508.55 35456190.74 0.237792E+09 68759926.35
March 74947388.71 33662616.98 41284771.73 0.210815E+09 59428230.37
April 49921288.83 11108213.35 38813075.48 0.172701E+09 27167062.12
May 39597774.01 1467330.04 38130443.97 0.177794E+09 5417916.62
June 36032133.23 140670.24 35891462.98 0.189667E+09 738319.64
July 40074932.30 657614.49 39417317.81 0.215643E+09 1986713.09
August 46636007.53 5290557.83 41345449.69 0.223733E+09 633655.76
September 58318190.90 16085710.26 42232480.64 0.265159E+09 3921466.03
October 81369349.95 39171335.94 42198014.01 0.298349E+09 8703327.82
November 87085456.26 48407152.59 38678303.67 0.273904E+09 36548992.59
December 97638493.76 60992629.69 36645864.07 0.269839E+09 79509489.33
           
Annual Sum or Average 0.798274E+09 0.332105E+09 0.466169E+09 0.280641E+10 0.387775E+09
Minimum of Months 36032133.23 140670.24 35456190.74 0.172701E+09 633655.76
Maximum of Months 0.101737E+09 65661223.82 42232480.64 0.298349E+09 94959573.62



Table of Contents

Report: WindowEnergyReportMonthly

For: A1ED60

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 61331050.22 96860117.11
February 29281056.49 0.00 29281056.49 78809272.85 69184690.91
March 38661147.87 0.00 38661147.87 99178441.98 61829872.28
April 42059850.16 324037.08 41735813.08 0.134179E+09 33163712.26
May 50359892.88 3101759.59 47258133.28 0.198898E+09 9831968.17
June 52317151.58 4858419.83 47458731.75 0.229902E+09 2877267.16
July 54430580.28 3573055.21 50857525.06 0.246153E+09 6409033.41
August 47568584.43 675051.23 46893533.20 0.209384E+09 2864572.80
September 40635245.93 6436.37 40628809.56 0.194804E+09 8916436.27
October 35174346.25 0.00 35174346.25 0.148087E+09 13097026.80
November 29597707.26 0.00 29597707.26 0.102920E+09 40938128.92
December 27090367.29 0.00 27090367.29 67469637.85 80419244.97
           
Annual Sum or Average 0.474564E+09 12538759.32 0.462025E+09 0.177112E+10 0.426392E+09
Minimum of Months 27090367.29 0.00 27090367.29 61331050.22 2864572.80
Maximum of Months 54430580.28 4858419.83 50857525.06 0.246153E+09 96860117.11



Table of Contents

Report: WindowEnergyReportMonthly

For: E8D997

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 61331050.22 96860117.11
February 29281056.49 0.00 29281056.49 78809272.85 69184690.91
March 38661147.87 0.00 38661147.87 99178441.98 61829872.28
April 42059850.16 324037.08 41735813.08 0.134179E+09 33163712.26
May 50359892.88 3101759.59 47258133.28 0.198898E+09 9831968.17
June 52317151.58 4858419.83 47458731.75 0.229902E+09 2877267.16
July 54430580.28 3573055.21 50857525.06 0.246153E+09 6409033.41
August 47568584.43 675051.23 46893533.20 0.209384E+09 2864572.80
September 40635245.93 6436.37 40628809.56 0.194804E+09 8916436.27
October 35174346.25 0.00 35174346.25 0.148087E+09 13097026.80
November 29597707.26 0.00 29597707.26 0.102920E+09 40938128.92
December 27090367.29 0.00 27090367.29 67469637.85 80419244.97
           
Annual Sum or Average 0.474564E+09 12538759.32 0.462025E+09 0.177112E+10 0.426392E+09
Minimum of Months 27090367.29 0.00 27090367.29 61331050.22 2864572.80
Maximum of Months 54430580.28 4858419.83 50857525.06 0.246153E+09 96860117.11



Table of Contents

Report: WindowEnergyReportMonthly

For: 88E1FC

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 61331050.22 96860117.11
February 29281056.49 0.00 29281056.49 78809272.85 69184690.91
March 38661147.87 0.00 38661147.87 99178441.98 61829872.28
April 42059850.16 324037.08 41735813.08 0.134179E+09 33163712.26
May 50359892.88 3101759.59 47258133.28 0.198898E+09 9831968.17
June 52317151.58 4858419.83 47458731.75 0.229902E+09 2877267.16
July 54430580.28 3573055.21 50857525.06 0.246153E+09 6409033.41
August 47568584.43 675051.23 46893533.20 0.209384E+09 2864572.80
September 40635245.93 6436.37 40628809.56 0.194804E+09 8916436.27
October 35174346.25 0.00 35174346.25 0.148087E+09 13097026.80
November 29597707.26 0.00 29597707.26 0.102920E+09 40938128.92
December 27090367.29 0.00 27090367.29 67469637.85 80419244.97
           
Annual Sum or Average 0.474564E+09 12538759.32 0.462025E+09 0.177112E+10 0.426392E+09
Minimum of Months 27090367.29 0.00 27090367.29 61331050.22 2864572.80
Maximum of Months 54430580.28 4858419.83 50857525.06 0.246153E+09 96860117.11



Table of Contents

Report: WindowEnergyReportMonthly

For: F83F33

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94201598.82 45276954.40 48924644.41 0.224528E+09 0.158804E+09
February 97840158.04 45232496.71 52607661.32 0.255989E+09 0.112081E+09
March 0.131473E+09 61665876.99 69806902.62 0.341769E+09 95911024.44
April 0.138420E+09 61412187.93 77007806.66 0.428375E+09 50753620.94
May 0.135426E+09 53624157.88 81801915.50 0.486227E+09 12518241.16
June 0.129400E+09 49430243.95 79969971.42 0.509223E+09 2888482.95
July 0.137623E+09 49478553.76 88144821.92 0.556959E+09 6779203.17
August 0.125695E+09 41785915.73 83908892.90 0.490090E+09 3204391.13
September 0.117245E+09 42151565.58 75093923.48 0.473276E+09 11619653.24
October 0.111483E+09 47793901.96 63688694.58 0.401596E+09 20564949.59
November 87985669.60 35156584.35 52829085.26 0.274799E+09 62687584.96
December 73868734.35 26420889.54 47447844.81 0.187132E+09 0.132233E+09
           
Annual Sum or Average 0.138066E+10 0.559429E+09 0.821232E+09 0.462996E+10 0.670045E+09
Minimum of Months 73868734.35 26420889.54 47447844.81 0.187132E+09 2888482.95
Maximum of Months 0.138420E+09 61665876.99 88144821.92 0.556959E+09 0.158804E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: B1F5EE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70113579.34 33957715.80 36155863.53 0.168816E+09 0.116657E+09
February 72815356.47 33924372.54 38890983.94 0.192095E+09 82260391.47
March 97866974.88 46249407.74 51617567.14 0.255484E+09 70785362.60
April 0.103053E+09 46059140.94 56993359.33 0.319621E+09 38259077.65
May 0.100697E+09 40218118.41 60478879.27 0.361253E+09 10013565.85
June 96164093.61 37072682.97 59091410.64 0.379260E+09 2555035.24
July 0.102284E+09 37108915.32 65174877.34 0.415017E+09 5449181.16
August 93345188.96 31339436.79 62005752.17 0.365936E+09 2619273.52
September 87100743.19 31613674.19 55487069.00 0.353113E+09 9026626.92
October 82908953.52 35845426.47 47063527.05 0.299530E+09 15383164.03
November 65378513.92 26367438.26 39011075.65 0.204825E+09 47032577.36
December 54849860.25 19815667.15 35034193.10 0.139867E+09 96864463.94
           
Annual Sum or Average 0.102658E+10 0.419572E+09 0.607005E+09 0.345482E+10 0.496906E+09
Minimum of Months 54849860.25 19815667.15 35034193.10 0.139867E+09 2555035.24
Maximum of Months 0.103053E+09 46249407.74 65174877.34 0.415017E+09 0.116657E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: F52F3D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.152403E+09 0.128669E+09
February 73380118.53 33924372.54 39455745.99 0.172840E+09 93741138.91
March 98604584.71 46249407.74 52355176.96 0.234070E+09 81563850.84
April 0.103815E+09 46059140.94 57755855.00 0.303763E+09 44070084.54
May 0.101570E+09 40218118.41 61351436.62 0.347420E+09 12383779.72
June 97050161.53 37072682.97 59977478.57 0.368897E+09 3304456.02
July 0.103218E+09 37108915.32 66108616.44 0.407418E+09 6422702.31
August 94271106.47 31339436.79 62931669.67 0.355217E+09 3806259.70
September 87934116.79 31613674.19 56320442.61 0.340650E+09 11012535.98
October 83611947.41 35845426.47 47766520.94 0.282420E+09 20498103.21
November 65989252.20 26367438.26 39621813.94 0.186799E+09 53814819.62
December 55401550.76 19815667.15 35585883.61 0.123531E+09 0.110012E+09
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.327543E+10 0.569299E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.123531E+09 3304456.02
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.407418E+09 0.128669E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 80885D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.305211E+09 0.196984E+09 0.108227E+09 0.763608E+09 0.288369E+09
February 0.254747E+09 0.148379E+09 0.106369E+09 0.660600E+09 0.215342E+09
March 0.224842E+09 0.100988E+09 0.123854E+09 0.576229E+09 0.193221E+09
April 0.149764E+09 33324640.05 0.116439E+09 0.468986E+09 0.103423E+09
May 0.118793E+09 4401990.13 0.114391E+09 0.472800E+09 29171289.80
June 0.108096E+09 422010.73 0.107674E+09 0.504858E+09 7594963.17
July 0.120225E+09 1972843.48 0.118252E+09 0.578338E+09 14841662.23
August 0.139908E+09 15871673.50 0.124036E+09 0.600887E+09 8652131.83
September 0.174955E+09 48257130.77 0.126697E+09 0.722575E+09 25292494.92
October 0.244108E+09 0.117514E+09 0.126594E+09 0.817768E+09 46535754.90
November 0.261256E+09 0.145221E+09 0.116035E+09 0.758605E+09 0.123465E+09
December 0.292915E+09 0.182978E+09 0.109938E+09 0.756658E+09 0.245194E+09
           
Annual Sum or Average 0.239482E+10 0.996314E+09 0.139851E+10 0.768191E+10 0.130110E+10
Minimum of Months 0.108096E+09 422010.73 0.106369E+09 0.468986E+09 7594963.17
Maximum of Months 0.305211E+09 0.196984E+09 0.126697E+09 0.817768E+09 0.288369E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FEEF06

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101737E+09 65661223.82 36075611.73 0.260044E+09 96659764.25
February 84915699.29 49459508.55 35456190.74 0.223751E+09 73387166.24
March 74947388.71 33662616.98 41284771.73 0.194353E+09 68000289.75
April 49921288.83 11108213.35 38813075.48 0.157165E+09 38381148.22
May 39597774.01 1467330.04 38130443.97 0.158811E+09 10719783.30
June 36032133.23 140670.24 35891462.98 0.172910E+09 2330163.16
July 40074932.30 657614.49 39417317.81 0.197030E+09 4775737.24
August 46636007.53 5290557.83 41345449.69 0.203634E+09 2844400.47
September 58318190.90 16085710.26 42232480.64 0.246786E+09 7894865.33
October 81369349.95 39171335.94 42198014.01 0.278212E+09 15034011.49
November 87085456.26 48407152.59 38678303.67 0.257662E+09 41619794.53
December 97638493.76 60992629.69 36645864.07 0.256238E+09 82740922.99
           
Annual Sum or Average 0.798274E+09 0.332105E+09 0.466169E+09 0.260660E+10 0.444388E+09
Minimum of Months 36032133.23 140670.24 35456190.74 0.157165E+09 2330163.16
Maximum of Months 0.101737E+09 65661223.82 42232480.64 0.278212E+09 96659764.25



Table of Contents

Report: WindowEnergyReportMonthly

For: 2BE8DE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 45184082.23 20583995.58 24600086.65 0.106438E+09 0.101918E+09
February 50995402.26 24175715.38 26819686.88 0.132028E+09 76090965.72
March 70215501.42 33361436.11 36854065.32 0.180778E+09 69258482.96
April 74622245.38 35880649.76 38741595.63 0.224922E+09 35356822.53
May 70056898.00 28287938.09 41768959.91 0.250768E+09 9407064.59
June 56788509.95 16929697.56 39858812.40 0.240321E+09 1790003.28
July 65959615.13 21687560.37 44272054.76 0.281266E+09 3948837.53
August 65899156.99 22709611.60 43189545.39 0.261703E+09 2283951.65
September 54196670.88 17005815.28 37190855.60 0.231496E+09 6786218.48
October 56211569.44 23103885.98 33107683.47 0.202030E+09 13356319.89
November 44967485.69 17536214.41 27431271.28 0.140362E+09 42290779.43
December 46912834.14 22135114.91 24777719.23 0.117783E+09 84963913.31
           
Annual Sum or Average 0.702010E+09 0.283398E+09 0.418612E+09 0.236989E+10 0.447451E+09
Minimum of Months 44967485.69 16929697.56 24600086.65 0.106438E+09 1790003.28
Maximum of Months 74622245.38 35880649.76 44272054.76 0.281266E+09 0.101918E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 513E2A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 42412691.40 20583995.58 21828695.83 0.102327E+09 97509666.56
February 48086636.24 24175715.38 23910920.87 0.127301E+09 72260668.42
March 66417442.54 33361436.11 33056006.44 0.173982E+09 65388862.35
April 67843775.17 33673163.61 34170611.56 0.210000E+09 31980613.78
May 57308933.87 22363410.30 34945523.57 0.219401E+09 7399733.66
June 45329864.36 12041866.67 33287997.68 0.212740E+09 1210762.69
July 53974397.67 16834741.53 37139656.14 0.251750E+09 2843263.06
August 57701338.57 20650988.97 37050349.60 0.245404E+09 1811035.92
September 49801639.34 16999619.83 32802019.51 0.223255E+09 4931075.74
October 52610681.44 23103885.98 29506795.46 0.196978E+09 10406645.65
November 41751265.92 17536214.41 24215051.52 0.135183E+09 39033816.75
December 44020805.27 22135114.91 21885690.37 0.112722E+09 81452019.13
           
Annual Sum or Average 0.627259E+09 0.263460E+09 0.363799E+09 0.221104E+10 0.416228E+09
Minimum of Months 41751265.92 12041866.67 21828695.83 0.102327E+09 1210762.69
Maximum of Months 67843775.17 33673163.61 37139656.14 0.251750E+09 97509666.56



Table of Contents

Report: WindowEnergyReportMonthly

For: BA5CD9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 44291765.72 20583995.58 23707770.15 0.105005E+09 0.100719E+09
February 50058853.52 24175715.38 25883138.14 0.130475E+09 74881081.68
March 68992622.62 33361436.11 35631186.51 0.178580E+09 68006284.91
April 73383227.94 35880649.76 37502578.18 0.222638E+09 34171969.41
May 66613295.32 27076441.99 39536853.33 0.242483E+09 8725208.05
June 53150544.06 15452902.79 37697641.27 0.231592E+09 1576853.10
July 62301133.68 20454521.58 41846612.11 0.272330E+09 3581111.52
August 64197405.90 22658579.18 41538826.73 0.259092E+09 2091704.03
September 52786937.43 17005815.28 35781122.15 0.228841E+09 6171783.15
October 55052167.48 23103885.98 31948281.50 0.200357E+09 12380317.21
November 43931971.47 17536214.41 26395757.06 0.138566E+09 41271347.67
December 45981693.53 22135114.91 23846578.62 0.116012E+09 83905723.81
           
Annual Sum or Average 0.680742E+09 0.279425E+09 0.401316E+09 0.232597E+10 0.437483E+09
Minimum of Months 43931971.47 15452902.79 23707770.15 0.105005E+09 1576853.10
Maximum of Months 73383227.94 35880649.76 41846612.11 0.272330E+09 0.100719E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 1AD478

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.169561E+09 0.109435E+09 60126019.55 0.438443E+09 0.170668E+09
February 0.141526E+09 82432514.26 59093651.23 0.381805E+09 0.126551E+09
March 0.124912E+09 56104361.63 68807952.89 0.337705E+09 0.111287E+09
April 83202148.06 18513688.91 64688459.14 0.286490E+09 52794152.69
May 65996290.02 2445550.07 63550739.94 0.306145E+09 11627754.05
June 60053555.38 234450.41 59819104.97 0.335443E+09 1910558.83
July 66791553.84 1096024.16 65695529.68 0.381663E+09 4186387.45
August 77726679.21 8817596.39 68909082.82 0.391469E+09 1891170.05
September 97196984.83 26809517.10 70387467.73 0.456289E+09 8205054.13
October 0.135616E+09 65285559.90 70330023.34 0.498990E+09 17497361.17
November 0.145142E+09 80678587.65 64463839.45 0.446831E+09 69421681.98
December 0.162731E+09 0.101654E+09 61076440.12 0.436109E+09 0.144881E+09
           
Annual Sum or Average 0.133046E+10 0.553508E+09 0.776948E+09 0.469738E+10 0.720922E+09
Minimum of Months 60053555.38 234450.41 59093651.23 0.286490E+09 1891170.05
Maximum of Months 0.169561E+09 0.109435E+09 70387467.73 0.498990E+09 0.170668E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 27F0AC

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.271298E+09 0.175097E+09 96201631.28 0.705512E+09 0.262624E+09
February 0.226442E+09 0.131892E+09 94549841.96 0.615619E+09 0.192593E+09
March 0.199860E+09 89766978.61 0.110093E+09 0.547391E+09 0.166309E+09
April 0.133123E+09 29621902.26 0.103502E+09 0.468292E+09 73124125.63
May 0.105594E+09 3912880.12 0.101681E+09 0.506921E+09 14248439.38
June 96085688.60 375120.65 95710567.95 0.553475E+09 2021774.23
July 0.106866E+09 1753638.65 0.105113E+09 0.628112E+09 5058962.34
August 0.124363E+09 14108154.23 0.110255E+09 0.644444E+09 1676575.86
September 0.155515E+09 42895227.35 0.112620E+09 0.744318E+09 9523125.30
October 0.216985E+09 0.104457E+09 0.112528E+09 0.812096E+09 22270944.60
November 0.232228E+09 0.129086E+09 0.103142E+09 0.723666E+09 0.102974E+09
December 0.260369E+09 0.162647E+09 97722304.19 0.702915E+09 0.221560E+09
           
Annual Sum or Average 0.212873E+10 0.885612E+09 0.124312E+10 0.765276E+10 0.107398E+10
Minimum of Months 96085688.60 375120.65 94549841.96 0.468292E+09 1676575.86
Maximum of Months 0.271298E+09 0.175097E+09 0.112620E+09 0.812096E+09 0.262624E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 724114

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101737E+09 65661223.82 36075611.73 0.256591E+09 96257221.39
February 84915699.29 49459508.55 35456190.74 0.223237E+09 70885989.26
March 74947388.71 33662616.98 41284771.73 0.197126E+09 61581485.37
April 49921288.83 11108213.35 38813075.48 0.164708E+09 29333922.36
May 39597774.01 1467330.04 38130443.97 0.172286E+09 6493868.35
June 36032133.23 140670.24 35891462.98 0.186269E+09 1180837.09
July 40074932.30 657614.49 39417317.81 0.212180E+09 2698055.11
August 46636007.53 5290557.83 41345449.69 0.218649E+09 1217232.56
September 58318190.90 16085710.26 42232480.64 0.256728E+09 5357158.62
October 81369349.95 39171335.94 42198014.01 0.283907E+09 11181976.13
November 87085456.26 48407152.59 38678303.67 0.258463E+09 39091749.06
December 97638493.76 60992629.69 36645864.07 0.254617E+09 81481216.18
           
Annual Sum or Average 0.798274E+09 0.332105E+09 0.466169E+09 0.268476E+10 0.406761E+09
Minimum of Months 36032133.23 140670.24 35456190.74 0.164708E+09 1180837.09
Maximum of Months 0.101737E+09 65661223.82 42232480.64 0.283907E+09 96257221.39



Table of Contents

Report: WindowEnergyReportMonthly

For: D538C4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94119534.64 45276954.40 48842580.24 0.217974E+09 0.163416E+09
February 97753928.19 45232496.71 52521431.48 0.243411E+09 0.120041E+09
March 0.131360E+09 61665876.99 69694273.35 0.320793E+09 0.106981E+09
April 0.138303E+09 61412187.93 76890683.34 0.409791E+09 60988012.16
May 0.135293E+09 53624157.88 81669059.83 0.469386E+09 18679542.85
June 0.129266E+09 49430243.95 79835546.81 0.501554E+09 5586460.52
July 0.137481E+09 49478553.76 88002229.17 0.553858E+09 9622633.19
August 0.125554E+09 41785915.73 83768104.70 0.488351E+09 5432224.09
September 0.117119E+09 42151565.58 74967447.73 0.474652E+09 14330861.76
October 0.111375E+09 47793901.96 63581182.79 0.399132E+09 23480218.07
November 87893047.84 35156584.35 52736463.49 0.267712E+09 68302973.99
December 73784949.86 26420889.54 47364060.32 0.181816E+09 0.136886E+09
           
Annual Sum or Average 0.137930E+10 0.559429E+09 0.819873E+09 0.452843E+10 0.733748E+09
Minimum of Months 73784949.86 26420889.54 47364060.32 0.181816E+09 5432224.09
Maximum of Months 0.138303E+09 61665876.99 88002229.17 0.553858E+09 0.163416E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 5635BC

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 92359838.81 45276954.40 47082884.41 0.215062E+09 0.160520E+09
February 95905477.26 45232496.71 50672980.55 0.240256E+09 0.117804E+09
March 0.128946E+09 61665876.99 67280128.00 0.316293E+09 0.104765E+09
April 0.135810E+09 61412187.93 74397698.97 0.405075E+09 58968398.51
May 0.132436E+09 53624157.88 78811813.71 0.464017E+09 17490043.81
June 0.126362E+09 49430243.95 76932223.42 0.496324E+09 5025167.33
July 0.134425E+09 49478553.76 84946224.90 0.548179E+09 8766380.06
August 0.122521E+09 41785915.73 80735404.83 0.483705E+09 5016609.55
September 0.114389E+09 42151565.58 72236955.07 0.469373E+09 13257166.13
October 0.109075E+09 47793901.96 61280965.62 0.395723E+09 21903324.09
November 85891756.43 35156584.35 50735172.09 0.264387E+09 66338078.95
December 71977590.99 26420889.54 45556701.45 0.178439E+09 0.134594E+09
           
Annual Sum or Average 0.135010E+10 0.559429E+09 0.790669E+09 0.447683E+10 0.714449E+09
Minimum of Months 71977590.99 26420889.54 45556701.45 0.178439E+09 5016609.55
Maximum of Months 0.135810E+09 61665876.99 84946224.90 0.548179E+09 0.160520E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 831C1D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41082308.58 0.00 41082308.58 86668392.20 0.178884E+09
February 43921584.73 0.00 43921584.73 0.114965E+09 0.129812E+09
March 57991721.80 0.00 57991721.80 0.148107E+09 0.116218E+09
April 63089775.24 486055.62 62603719.62 0.215728E+09 54747639.40
May 75539839.32 4652639.39 70887199.92 0.328165E+09 14280710.11
June 78475727.37 7287629.75 71188097.62 0.386684E+09 3263809.05
July 81645870.41 5359582.82 76286287.60 0.421961E+09 6465465.25
August 71335590.22 1011078.68 70324511.55 0.364251E+09 2949687.76
September 60905715.25 5546.26 60900168.99 0.339684E+09 10577625.82
October 52761519.37 0.00 52761519.37 0.255518E+09 17702238.65
November 44396560.89 0.00 44396560.89 0.165600E+09 70985864.35
December 40635550.93 0.00 40635550.93 0.100370E+09 0.147170E+09
           
Annual Sum or Average 0.711782E+09 18802532.51 0.692979E+09 0.292770E+10 0.753057E+09
Minimum of Months 40635550.93 0.00 40635550.93 86668392.20 2949687.76
Maximum of Months 81645870.41 7287629.75 76286287.60 0.421961E+09 0.178884E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 9BB95F

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 56575886.61 0.130186E+09
February 29281056.49 0.00 29281056.49 75777665.02 94517197.68
March 38661147.87 0.00 38661147.87 99443551.06 83901629.86
April 42049436.45 318847.95 41730588.50 0.147979E+09 37067279.80
May 50359892.88 3101759.59 47258133.28 0.229537E+09 8673570.47
June 52317151.58 4858419.83 47458731.75 0.272391E+09 1650800.14
July 54430580.28 3573055.21 50857525.06 0.297228E+09 3375932.11
August 47555667.40 674029.86 46881637.54 0.256565E+09 1437192.51
September 40602006.48 3626.11 40598380.38 0.238355E+09 5944535.01
October 35174346.25 0.00 35174346.25 0.177714E+09 11112409.49
November 29597707.26 0.00 29597707.26 0.112109E+09 50910070.27
December 27090367.29 0.00 27090367.29 66379104.94 0.107444E+09
           
Annual Sum or Average 0.474508E+09 12529738.56 0.461978E+09 0.203005E+10 0.536220E+09
Minimum of Months 27090367.29 0.00 27090367.29 56575886.61 1437192.51
Maximum of Months 54430580.28 4858419.83 50857525.06 0.297228E+09 0.130186E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C0778D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 56575886.61 0.130186E+09
February 29281056.49 0.00 29281056.49 75777665.02 94517197.68
March 38661147.87 0.00 38661147.87 99443551.06 83901629.86
April 41980525.92 284323.63 41696202.29 0.147767E+09 37077550.05
May 50359892.88 3101759.59 47258133.28 0.229537E+09 8673570.47
June 52317151.58 4858419.83 47458731.75 0.272391E+09 1650800.14
July 54430580.28 3573055.21 50857525.06 0.297228E+09 3375932.11
August 47555667.40 674029.86 46881637.54 0.256565E+09 1437192.51
September 40602006.48 3626.11 40598380.38 0.238355E+09 5944535.01
October 35174346.25 0.00 35174346.25 0.177714E+09 11112409.49
November 29597707.26 0.00 29597707.26 0.112109E+09 50910070.27
December 27090367.29 0.00 27090367.29 66379104.94 0.107444E+09
           
Annual Sum or Average 0.474439E+09 12495214.23 0.461943E+09 0.202984E+10 0.536230E+09
Minimum of Months 27090367.29 0.00 27090367.29 56575886.61 1437192.51
Maximum of Months 54430580.28 4858419.83 50857525.06 0.297228E+09 0.130186E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 7D2D69

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 54898634.72 0.128051E+09
February 29281056.49 0.00 29281056.49 73295684.81 93487734.15
March 38661147.87 0.00 38661147.87 95089368.84 83938785.47
April 41759184.52 177236.66 41581947.86 0.139782E+09 39817397.30
May 50359892.88 3101759.59 47258133.28 0.214910E+09 10969778.22
June 52317151.58 4858419.83 47458731.75 0.254633E+09 2530131.73
July 54429629.10 3572690.13 50856938.97 0.279071E+09 4691407.46
August 47543499.15 668613.84 46874885.31 0.239459E+09 2429140.55
September 40602006.48 3626.11 40598380.38 0.223943E+09 7875472.27
October 35174346.25 0.00 35174346.25 0.166639E+09 13495398.34
November 29597707.26 0.00 29597707.26 0.106116E+09 51741718.04
December 27090367.29 0.00 27090367.29 63649744.07 0.106007E+09
           
Annual Sum or Average 0.474204E+09 12382346.16 0.461822E+09 0.191149E+10 0.545035E+09
Minimum of Months 27090367.29 0.00 27090367.29 54898634.72 2429140.55
Maximum of Months 54429629.10 4858419.83 50856938.97 0.279071E+09 0.128051E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 2EF63B

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 54898634.72 0.128051E+09
February 29281056.49 0.00 29281056.49 73295684.81 93487734.15
March 38661147.87 0.00 38661147.87 95089368.84 83938785.47
April 41644478.11 123308.73 41521169.38 0.139504E+09 39897513.55
May 50359892.88 3101759.59 47258133.28 0.214910E+09 10969778.22
June 52317151.58 4858419.83 47458731.75 0.254633E+09 2530131.73
July 54419019.16 3568354.35 50850664.81 0.279036E+09 4691407.46
August 47399145.72 604922.18 46794223.54 0.238989E+09 2432849.24
September 40602006.48 3626.11 40598380.38 0.223943E+09 7875472.27
October 35174346.25 0.00 35174346.25 0.166639E+09 13495398.34
November 29597707.26 0.00 29597707.26 0.106116E+09 51741718.04
December 27090367.29 0.00 27090367.29 63649744.07 0.106007E+09
           
Annual Sum or Average 0.473935E+09 12260390.80 0.461674E+09 0.191070E+10 0.545119E+09
Minimum of Months 27090367.29 0.00 27090367.29 54898634.72 2432849.24
Maximum of Months 54419019.16 4858419.83 50850664.81 0.279036E+09 0.128051E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C417C0

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27068841.59 0.00 27068841.59 54961261.04 0.133261E+09
February 28945269.21 0.00 28945269.21 74116870.63 96924190.74
March 38222479.81 0.00 38222479.81 97238500.58 86309926.48
April 41125210.29 100281.71 41024928.59 0.143905E+09 38971436.31
May 48565841.06 2325244.51 46240596.55 0.221396E+09 9416572.56
June 51341311.61 4586021.98 46755289.63 0.266518E+09 1882132.24
July 53035513.35 3109085.50 49926427.85 0.289543E+09 3736240.04
August 46300869.20 399335.01 45901534.20 0.249710E+09 1769609.37
September 40116687.37 3626.11 40113061.26 0.233954E+09 6645231.85
October 34754032.37 0.00 34754032.37 0.173613E+09 12285607.94
November 29242917.52 0.00 29242917.52 0.109381E+09 52826240.03
December 26768318.19 0.00 26768318.19 64390418.20 0.110183E+09
           
Annual Sum or Average 0.465487E+09 10523594.82 0.454964E+09 0.197873E+10 0.554212E+09
Minimum of Months 26768318.19 0.00 26768318.19 54961261.04 1769609.37
Maximum of Months 53035513.35 4586021.98 49926427.85 0.289543E+09 0.133261E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: EB042B

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.159565E+09 0.125109E+09
February 73380118.53 33924372.54 39455745.99 0.179441E+09 91287267.16
March 98604584.71 46249407.74 52355176.96 0.237917E+09 81247218.14
April 0.103815E+09 46059140.94 57755855.00 0.303637E+09 46911748.59
May 0.101570E+09 40218118.41 61351436.62 0.345395E+09 14596563.36
June 97050161.53 37072682.97 59977478.57 0.365500E+09 4516948.41
July 0.103218E+09 37108915.32 66108616.44 0.403175E+09 8391421.85
August 94271106.47 31339436.79 62931669.67 0.354743E+09 4725069.57
September 87934116.79 31613674.19 56320442.61 0.344171E+09 11982816.47
October 83611947.41 35845426.47 47766520.94 0.290715E+09 19524225.68
November 65989252.20 26367438.26 39621813.94 0.195425E+09 51481099.71
December 55401550.76 19815667.15 35585883.61 0.131737E+09 0.105142E+09
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.331142E+10 0.564915E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.131737E+09 4516948.41
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.403175E+09 0.125109E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 4C1F71

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.159565E+09 0.125109E+09
February 73380118.53 33924372.54 39455745.99 0.179441E+09 91287267.16
March 98604584.71 46249407.74 52355176.96 0.237917E+09 81247218.14
April 0.103815E+09 46059140.94 57755855.00 0.303637E+09 46911748.59
May 0.101570E+09 40218118.41 61351436.62 0.345395E+09 14596563.36
June 97050161.53 37072682.97 59977478.57 0.365500E+09 4516948.41
July 0.103218E+09 37108915.32 66108616.44 0.403175E+09 8391421.85
August 94271106.47 31339436.79 62931669.67 0.354743E+09 4725069.57
September 87934116.79 31613674.19 56320442.61 0.344171E+09 11982816.47
October 83611947.41 35845426.47 47766520.94 0.290715E+09 19524225.68
November 65989252.20 26367438.26 39621813.94 0.195425E+09 51481099.71
December 55401550.76 19815667.15 35585883.61 0.131737E+09 0.105142E+09
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.331142E+10 0.564915E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.131737E+09 4516948.41
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.403175E+09 0.125109E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: D23C8B

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.159565E+09 0.125109E+09
February 73380118.53 33924372.54 39455745.99 0.179441E+09 91287267.16
March 98604584.71 46249407.74 52355176.96 0.237917E+09 81247218.14
April 0.103815E+09 46059140.94 57755855.00 0.303637E+09 46911748.59
May 0.101570E+09 40218118.41 61351436.62 0.345395E+09 14596563.36
June 97050161.53 37072682.97 59977478.57 0.365500E+09 4516948.41
July 0.103218E+09 37108915.32 66108616.44 0.403175E+09 8391421.85
August 94271106.47 31339436.79 62931669.67 0.354743E+09 4725069.57
September 87934116.79 31613674.19 56320442.61 0.344171E+09 11982816.47
October 83611947.41 35845426.47 47766520.94 0.290715E+09 19524225.68
November 65989252.20 26367438.26 39621813.94 0.195425E+09 51481099.71
December 55401550.76 19815667.15 35585883.61 0.131737E+09 0.105142E+09
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.331142E+10 0.564915E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.131737E+09 4516948.41
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.403175E+09 0.125109E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: B4E4BE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.159565E+09 0.125109E+09
February 73380118.53 33924372.54 39455745.99 0.179441E+09 91287267.16
March 98604584.71 46249407.74 52355176.96 0.237917E+09 81247218.14
April 0.103815E+09 46059140.94 57755855.00 0.303637E+09 46911748.59
May 0.101570E+09 40218118.41 61351436.62 0.345395E+09 14596563.36
June 97050161.53 37072682.97 59977478.57 0.365500E+09 4516948.41
July 0.103218E+09 37108915.32 66108616.44 0.403175E+09 8391421.85
August 94271106.47 31339436.79 62931669.67 0.354743E+09 4725069.57
September 87934116.79 31613674.19 56320442.61 0.344171E+09 11982816.47
October 83611947.41 35845426.47 47766520.94 0.290715E+09 19524225.68
November 65989252.20 26367438.26 39621813.94 0.195425E+09 51481099.71
December 55401550.76 19815667.15 35585883.61 0.131737E+09 0.105142E+09
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.331142E+10 0.564915E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.131737E+09 4516948.41
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.403175E+09 0.125109E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: EEF55D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.280385E+09 0.180207E+09 0.100178E+09 0.703151E+09 0.338816E+09
February 0.238664E+09 0.139059E+09 99604919.14 0.618325E+09 0.255080E+09
March 0.214457E+09 96960902.05 0.117496E+09 0.544121E+09 0.231300E+09
April 0.144466E+09 33287409.78 0.111178E+09 0.444606E+09 0.130129E+09
May 0.113138E+09 4401990.13 0.108736E+09 0.438723E+09 45185519.16
June 0.102462E+09 422010.73 0.102040E+09 0.469491E+09 13463444.24
July 0.114078E+09 1972843.41 0.112105E+09 0.541427E+09 22831667.81
August 0.133866E+09 15799194.43 0.118067E+09 0.560789E+09 15523329.05
September 0.167936E+09 47289013.75 0.120647E+09 0.684879E+09 33647403.80
October 0.230386E+09 0.111036E+09 0.119350E+09 0.762754E+09 61350613.85
November 0.242694E+09 0.134460E+09 0.108234E+09 0.699904E+09 0.152572E+09
December 0.276204E+09 0.173643E+09 0.102562E+09 0.705500E+09 0.285717E+09
           
Annual Sum or Average 0.225874E+10 0.938538E+09 0.132020E+10 0.717367E+10 0.158562E+10
Minimum of Months 0.102462E+09 422010.73 99604919.14 0.438723E+09 13463444.24
Maximum of Months 0.280385E+09 0.180207E+09 0.120647E+09 0.762754E+09 0.338816E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: E55A57

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121272E+09 76371547.14 44900874.16 0.306837E+09 0.171091E+09
February 0.105332E+09 60499741.07 44832297.96 0.277182E+09 0.127888E+09
March 96674089.68 43309578.83 53364510.85 0.250034E+09 0.116307E+09
April 66683991.36 15780960.98 50903030.38 0.212594E+09 62687928.19
May 51955576.12 2196699.35 49758876.77 0.214090E+09 20303642.06
June 46583614.88 211005.31 46372609.58 0.230417E+09 5499606.40
July 52118284.92 979444.67 51138840.25 0.265904E+09 9623466.80
August 61444260.33 7544840.24 53899420.09 0.275525E+09 6863611.09
September 75946716.79 21394426.73 54552290.06 0.326959E+09 15031735.76
October 0.102394E+09 48519487.62 53874473.98 0.351592E+09 27694705.90
November 0.106903E+09 58346610.14 48556435.09 0.316577E+09 74886907.00
December 0.122581E+09 76803799.63 45777325.50 0.316964E+09 0.143918E+09
           
Annual Sum or Average 0.100989E+10 0.411958E+09 0.597931E+09 0.334468E+10 0.781795E+09
Minimum of Months 46583614.88 211005.31 44832297.96 0.212594E+09 5499606.40
Maximum of Months 0.122581E+09 76803799.63 54552290.06 0.351592E+09 0.171091E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 93D018

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.140604E+09 61751986.73 78851672.23 0.311498E+09 0.347845E+09
February 0.158304E+09 72527146.13 85776387.42 0.389824E+09 0.259436E+09
March 0.217595E+09 0.100084E+09 0.117511E+09 0.538228E+09 0.236343E+09
April 0.231385E+09 0.107642E+09 0.123743E+09 0.669819E+09 0.128203E+09
May 0.218217E+09 84866112.87 0.133351E+09 0.736365E+09 46191322.73
June 0.178796E+09 51059395.30 0.127737E+09 0.693704E+09 13822466.01
July 0.206895E+09 65131886.32 0.141763E+09 0.818391E+09 23551244.30
August 0.206133E+09 68128834.81 0.138005E+09 0.755230E+09 15496003.57
September 0.170067E+09 51017445.84 0.119049E+09 0.669035E+09 34451676.25
October 0.175338E+09 69311657.94 0.106027E+09 0.584998E+09 62422251.95
November 0.140350E+09 52608643.22 87741268.26 0.406919E+09 0.155822E+09
December 0.145716E+09 66405344.72 79310661.23 0.344395E+09 0.293407E+09
           
Annual Sum or Average 0.218940E+10 0.850535E+09 0.133887E+10 0.691841E+10 0.161699E+10
Minimum of Months 0.140350E+09 51017445.84 78851672.23 0.311498E+09 13822466.01
Maximum of Months 0.231385E+09 0.107642E+09 0.141763E+09 0.818391E+09 0.347845E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: DD9F5D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.162313E+09 0.117370E+09
February 73380118.53 33924372.54 39455745.99 0.182266E+09 85151191.40
March 98604584.71 46249407.74 52355176.96 0.240972E+09 75235835.46
April 0.103815E+09 46059140.94 57755855.00 0.306899E+09 42014514.79
May 0.101570E+09 40218118.41 61351436.62 0.350728E+09 11774044.32
June 97050161.53 37072682.97 59977478.57 0.372154E+09 3340620.49
July 0.103218E+09 37108915.32 66108616.44 0.409188E+09 6549779.74
August 94271106.47 31339436.79 62931669.67 0.362321E+09 3304929.99
September 87934116.79 31613674.19 56320442.61 0.350555E+09 9844810.22
October 83611947.41 35845426.47 47766520.94 0.296564E+09 15818459.43
November 65989252.20 26367438.26 39621813.94 0.199846E+09 47017281.09
December 55401550.76 19815667.15 35585883.61 0.135120E+09 97548009.89
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.336893E+10 0.514970E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.135120E+09 3304929.99
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.409188E+09 0.117370E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 15B02B

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 26859887.16 0.00 26859887.16 46371993.50 0.149552E+09
February 28725854.92 0.00 28725854.92 64421896.50 0.110822E+09
March 37935946.19 0.00 37935946.19 84981340.55 0.101066E+09
April 40831757.98 100281.71 40731476.27 0.126515E+09 52246537.15
May 47130111.61 1788330.55 45341781.06 0.189369E+09 17572864.14
June 48853405.79 3379752.91 45473652.88 0.223364E+09 5192734.52
July 50878386.40 2239151.03 48639235.37 0.245154E+09 8945243.45
August 45836911.11 377614.75 45459296.36 0.210444E+09 5833087.80
September 39789879.76 3626.11 39786253.65 0.198649E+09 13245418.33
October 34481611.80 0.00 34481611.80 0.144400E+09 22631435.72
November 29003154.84 0.00 29003154.84 90912572.45 63756406.06
December 26552202.23 0.00 26552202.23 53590401.27 0.125519E+09
           
Annual Sum or Average 0.456879E+09 7888757.06 0.448990E+09 0.167818E+10 0.676382E+09
Minimum of Months 26552202.23 0.00 26552202.23 46371993.50 5192734.52
Maximum of Months 50878386.40 3379752.91 48639235.37 0.245154E+09 0.149552E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 820282

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 24270055.19 0.00 24270055.19 42472064.29 0.145590E+09
February 26005482.65 0.00 26005482.65 59970505.67 0.107682E+09
March 34383070.96 0.00 34383070.96 78517907.97 97901414.49
April 37165468.49 100281.71 37065186.79 0.119422E+09 49090330.20
May 42851804.18 1766044.23 41085759.95 0.180705E+09 15352973.28
June 44061031.07 3205880.84 40855150.24 0.213644E+09 4094535.77
July 46059274.58 2140341.62 43918932.95 0.235271E+09 7292111.07
August 41371053.76 377603.98 40993449.78 0.203223E+09 4964804.04
September 35768517.95 3626.11 35764891.84 0.190649E+09 11469487.04
October 31097036.68 0.00 31097036.68 0.138912E+09 19855616.24
November 26055483.54 0.00 26055483.54 85865812.01 60695139.78
December 23890613.42 0.00 23890613.42 49061030.15 0.122527E+09
           
Annual Sum or Average 0.412979E+09 7593778.49 0.405385E+09 0.159771E+10 0.646515E+09
Minimum of Months 23890613.42 0.00 23890613.42 42472064.29 4094535.77
Maximum of Months 46059274.58 3205880.84 43918932.95 0.235271E+09 0.145590E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 9BA05A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 44670000.82 0.134335E+09
February 29281056.49 0.00 29281056.49 61987457.21 96679403.11
March 38661147.87 0.00 38661147.87 81522298.81 85604472.21
April 42059850.16 324037.08 41735813.08 0.122733E+09 36835196.31
May 50359892.88 3101759.59 47258133.28 0.194135E+09 8783665.46
June 52317151.58 4858419.83 47458731.75 0.229399E+09 1644547.74
July 54430580.28 3573055.21 50857525.06 0.249555E+09 4166513.63
August 47564789.75 674613.61 46890176.13 0.213092E+09 2156662.30
September 40623451.38 5414.93 40618036.45 0.196483E+09 7003199.04
October 35174346.25 0.00 35174346.25 0.144561E+09 12296034.87
November 29597707.26 0.00 29597707.26 91913359.38 50379370.69
December 27090367.29 0.00 27090367.29 52519803.45 0.110737E+09
           
Annual Sum or Average 0.474549E+09 12537300.26 0.462011E+09 0.168257E+10 0.550621E+09
Minimum of Months 27090367.29 0.00 27090367.29 44670000.82 1644547.74
Maximum of Months 54430580.28 4858419.83 50857525.06 0.249555E+09 0.134335E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C639E8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 44670000.82 0.134335E+09
February 29281056.49 0.00 29281056.49 61987457.21 96679403.11
March 38661147.87 0.00 38661147.87 81522298.81 85604472.21
April 42059850.16 324037.08 41735813.08 0.122733E+09 36835196.31
May 50359892.88 3101759.59 47258133.28 0.194135E+09 8783665.46
June 52317151.58 4858419.83 47458731.75 0.229399E+09 1644547.74
July 54430580.28 3573055.21 50857525.06 0.249555E+09 4166513.63
August 47564263.61 674557.24 46889706.37 0.213090E+09 2156662.30
September 40621764.39 5255.65 40616508.73 0.196478E+09 7003261.42
October 35174346.25 0.00 35174346.25 0.144561E+09 12296034.87
November 29597707.26 0.00 29597707.26 91913359.38 50379370.69
December 27090367.29 0.00 27090367.29 52519803.45 0.110737E+09
           
Annual Sum or Average 0.474546E+09 12537084.61 0.462009E+09 0.168256E+10 0.550621E+09
Minimum of Months 27090367.29 0.00 27090367.29 44670000.82 1644547.74
Maximum of Months 54430580.28 4858419.83 50857525.06 0.249555E+09 0.134335E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: A2790A

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41082308.58 0.00 41082308.58 87971421.83 0.146798E+09
February 43921584.73 0.00 43921584.73 0.118735E+09 99429074.23
March 57991721.80 0.00 57991721.80 0.153894E+09 82214297.09
April 63089775.24 486055.62 62603719.62 0.222431E+09 21977738.10
May 75539839.32 4652639.39 70887199.92 0.352312E+09 2955512.97
June 78475727.37 7287629.75 71188097.62 0.407318E+09 73442.37
July 81645870.41 5359582.82 76286287.60 0.434620E+09 713343.05
August 71345472.64 1011739.15 70333733.48 0.388187E+09 34764.05
September 60929661.89 7595.28 60922066.60 0.353163E+09 571595.74
October 52761519.37 0.00 52761519.37 0.277413E+09 3239840.42
November 44396560.89 0.00 44396560.89 0.181393E+09 45618133.98
December 40635550.93 0.00 40635550.93 0.104657E+09 0.117097E+09
           
Annual Sum or Average 0.711816E+09 18805242.01 0.693010E+09 0.308210E+10 0.520723E+09
Minimum of Months 40635550.93 0.00 40635550.93 87971421.83 34764.05
Maximum of Months 81645870.41 7287629.75 76286287.60 0.434620E+09 0.146798E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 79FCEE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94153034.50 45276954.40 48876080.10 0.193308E+09 0.192011E+09
February 97789042.84 45232496.71 52556546.12 0.216441E+09 0.141152E+09
March 0.131406E+09 61665876.99 69740106.47 0.289271E+09 0.124156E+09
April 0.138348E+09 61412187.93 76935711.88 0.375314E+09 70542285.58
May 0.135349E+09 53624157.88 81724563.25 0.424780E+09 26586039.91
June 0.129324E+09 49430243.95 79893563.05 0.448948E+09 8634213.59
July 0.137539E+09 49478553.76 88060196.60 0.501557E+09 14864883.94
August 0.125614E+09 41785915.73 83827652.94 0.435224E+09 9925571.19
September 0.117173E+09 42151565.58 75021860.15 0.423755E+09 19048600.17
October 0.111418E+09 47793901.96 63624295.26 0.358235E+09 32318254.99
November 87933147.72 35156584.35 52776563.37 0.236639E+09 80470957.47
December 73820774.33 26420889.54 47399884.79 0.155787E+09 0.163522E+09
           
Annual Sum or Average 0.137987E+10 0.559429E+09 0.820437E+09 0.405926E+10 0.883232E+09
Minimum of Months 73820774.33 26420889.54 47399884.79 0.155787E+09 8634213.59
Maximum of Months 0.138348E+09 61665876.99 88060196.60 0.501557E+09 0.192011E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: EDE617

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 92778813.77 45276954.40 47501859.37 0.191029E+09 0.190035E+09
February 96344645.64 45232496.71 51112148.93 0.213945E+09 0.139607E+09
March 0.129519E+09 61665876.99 67853348.32 0.285728E+09 0.122641E+09
April 0.136373E+09 61412187.93 74960784.43 0.371382E+09 69042975.11
May 0.133130E+09 53624157.88 79506016.78 0.420184E+09 25395304.41
June 0.127088E+09 49430243.95 77657904.96 0.444598E+09 7996198.37
July 0.135150E+09 49478553.76 85671203.58 0.496606E+09 13868811.86
August 0.123266E+09 41785915.73 81480217.70 0.431187E+09 9339435.88
September 0.115069E+09 42151565.58 72917554.70 0.419481E+09 18166951.54
October 0.109614E+09 47793901.96 61820142.12 0.355024E+09 30842940.00
November 86393338.98 35156584.35 51236754.63 0.233815E+09 78886400.43
December 72425683.72 26420889.54 46004794.18 0.153185E+09 0.161935E+09
           
Annual Sum or Average 0.135715E+10 0.559429E+09 0.797723E+09 0.401616E+10 0.867757E+09
Minimum of Months 72425683.72 26420889.54 46004794.18 0.153185E+09 7996198.37
Maximum of Months 0.136373E+09 61665876.99 85671203.58 0.496606E+09 0.190035E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C61F0D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 46355305.83 0.127158E+09
February 29281056.49 0.00 29281056.49 63881847.01 91439640.49
March 38661147.87 0.00 38661147.87 83354959.07 81672283.18
April 42053766.35 321072.86 41732693.49 0.124625E+09 35463705.24
May 50359892.88 3101759.59 47258133.28 0.195936E+09 8353894.23
June 52317151.58 4858419.83 47458731.75 0.230988E+09 1575916.41
July 54430580.28 3573055.21 50857525.06 0.250676E+09 4126806.28
August 47561891.61 674336.65 46887554.96 0.215030E+09 1949871.52
September 40614650.06 4581.20 40610068.86 0.198039E+09 6812770.03
October 35174346.25 0.00 35174346.25 0.146700E+09 11660494.70
November 29597707.26 0.00 29597707.26 93998368.68 47541490.00
December 27090367.29 0.00 27090367.29 54247403.99 0.105123E+09
           
Annual Sum or Average 0.474531E+09 12533225.35 0.461998E+09 0.170383E+10 0.522878E+09
Minimum of Months 27090367.29 0.00 27090367.29 46355305.83 1575916.41
Maximum of Months 54430580.28 4858419.83 50857525.06 0.250676E+09 0.127158E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 7248C5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25180683.96 0.00 25180683.96 42872730.46 0.124393E+09
February 26960001.17 0.00 26960001.17 59924391.66 89267487.61
March 35628947.11 0.00 35628947.11 77701207.00 79535905.72
April 38393046.66 101379.16 38291667.50 0.117141E+09 33638425.54
May 44734554.48 1949788.53 42784765.95 0.182600E+09 7214347.00
June 46582473.32 3616552.34 42965920.98 0.217618E+09 1212615.82
July 48390448.40 2464672.91 45925775.49 0.236078E+09 3431766.60
August 43052970.59 396348.45 42656622.15 0.206561E+09 1685137.77
September 37247779.64 3626.11 37244153.53 0.191232E+09 5673588.31
October 32268919.68 0.00 32268919.68 0.142009E+09 10101702.19
November 27145657.27 0.00 27145657.27 89885498.68 45609127.79
December 24864528.72 0.00 24864528.72 50346889.61 0.103034E+09
           
Annual Sum or Average 0.430450E+09 8532367.49 0.421918E+09 0.161397E+10 0.504797E+09
Minimum of Months 24864528.72 0.00 24864528.72 42872730.46 1212615.82
Maximum of Months 48390448.40 3616552.34 45925775.49 0.236078E+09 0.124393E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 29FA28

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 46355305.83 0.127158E+09
February 29281056.49 0.00 29281056.49 63881847.01 91439640.49
March 38661147.87 0.00 38661147.87 83354959.07 81672283.18
April 41952241.28 271116.99 41681124.29 0.124436E+09 35576369.64
May 50359892.88 3101759.59 47258133.28 0.195936E+09 8353894.23
June 52317151.58 4858419.83 47458731.75 0.230988E+09 1575916.41
July 54430580.28 3573055.21 50857525.06 0.250676E+09 4126806.28
August 47560603.21 674246.90 46886356.31 0.215027E+09 1949871.52
September 40611446.62 4302.86 40607143.76 0.198029E+09 6812798.06
October 35174346.25 0.00 35174346.25 0.146700E+09 11660494.70
November 29597707.26 0.00 29597707.26 93998368.68 47541490.00
December 27090367.29 0.00 27090367.29 54247403.99 0.105123E+09
           
Annual Sum or Average 0.474425E+09 12482901.39 0.461942E+09 0.170363E+10 0.522991E+09
Minimum of Months 27090367.29 0.00 27090367.29 46355305.83 1575916.41
Maximum of Months 54430580.28 4858419.83 50857525.06 0.250676E+09 0.127158E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: F0B23F

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 46355305.83 0.127158E+09
February 29281056.49 0.00 29281056.49 63881847.01 91439640.49
March 38661147.87 0.00 38661147.87 83354959.07 81672283.18
April 41859368.08 223587.49 41635780.59 0.124279E+09 35692619.25
May 50359892.88 3101759.59 47258133.28 0.195936E+09 8353894.23
June 52317151.58 4858419.83 47458731.75 0.230988E+09 1575916.41
July 54429208.85 3572460.78 50856748.07 0.250672E+09 4126806.28
August 47539477.50 666434.99 46873042.50 0.214963E+09 1950267.23
September 40607488.93 3994.66 40603494.27 0.198018E+09 6812826.10
October 35174346.25 0.00 35174346.25 0.146700E+09 11660494.70
November 29597707.26 0.00 29597707.26 93998368.68 47541490.00
December 27090367.29 0.00 27090367.29 54247403.99 0.105123E+09
           
Annual Sum or Average 0.474305E+09 12426657.35 0.461879E+09 0.170339E+10 0.523107E+09
Minimum of Months 27090367.29 0.00 27090367.29 46355305.83 1575916.41
Maximum of Months 54429208.85 4858419.83 50856748.07 0.250672E+09 0.127158E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: EEC10E

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27208065.49 0.00 27208065.49 46047235.63 0.126997E+09
February 29091371.10 0.00 29091371.10 63534573.88 91309764.60
March 38413240.57 0.00 38413240.57 82870022.79 81548817.38
April 41512848.54 185904.65 41326943.89 0.123498E+09 35595532.01
May 49902246.86 3004025.80 46898221.06 0.194805E+09 8274981.51
June 52036402.95 4858218.58 47178184.37 0.230419E+09 1549397.86
July 54088851.13 3560744.19 50528106.94 0.249909E+09 4075407.88
August 47020763.41 597946.51 46422816.89 0.213757E+09 1934496.34
September 40339744.03 3766.58 40335977.45 0.197432E+09 6737395.68
October 34934717.06 0.00 34934717.06 0.146247E+09 11555437.36
November 29405107.83 0.00 29405107.83 93640351.44 47414921.41
December 26914041.62 0.00 26914041.62 53920472.52 0.104999E+09
           
Annual Sum or Average 0.470867E+09 12210606.31 0.458657E+09 0.169608E+10 0.521991E+09
Minimum of Months 26914041.62 0.00 26914041.62 46047235.63 1549397.86
Maximum of Months 54088851.13 4858218.58 50528106.94 0.249909E+09 0.126997E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 944FCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27097445.37 0.00 27097445.37 45861926.84 0.126888E+09
February 28974932.46 0.00 28974932.46 63324903.54 91222591.47
March 38261078.29 0.00 38261078.29 82575394.37 81465026.38
April 41238438.62 134837.04 41103601.58 0.122855E+09 35546646.30
May 48905836.65 2573090.57 46332746.08 0.191970E+09 8229628.57
June 51149250.53 4439930.10 46709320.43 0.227889E+09 1534382.21
July 53099628.87 3186019.10 49913609.77 0.246995E+09 4055925.36
August 46648293.78 520590.15 46127703.64 0.212839E+09 1925745.23
September 40173774.83 3636.36 40170138.47 0.197076E+09 6688213.58
October 34787954.70 0.00 34787954.70 0.145980E+09 11487389.05
November 29285689.14 0.00 29285689.14 93423704.56 47332277.64
December 26804950.97 0.00 26804950.97 53720246.58 0.104915E+09
           
Annual Sum or Average 0.466427E+09 10858103.31 0.455569E+09 0.168451E+10 0.521291E+09
Minimum of Months 26804950.97 0.00 26804950.97 45861926.84 1534382.21
Maximum of Months 53099628.87 4439930.10 49913609.77 0.246995E+09 0.126888E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C41399

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27388205.72 0.00 27388205.72 46355305.83 0.127158E+09
February 29281056.49 0.00 29281056.49 63881847.01 91439640.49
March 38661147.87 0.00 38661147.87 83354959.07 81672283.18
April 42059850.16 324037.08 41735813.08 0.124640E+09 35460145.73
May 50359892.88 3101759.59 47258133.28 0.195936E+09 8353894.23
June 52317151.58 4858419.83 47458731.75 0.230988E+09 1575916.41
July 54430580.28 3573055.21 50857525.06 0.250676E+09 4126806.28
August 47562912.51 674422.04 46888490.47 0.215033E+09 1949871.52
September 40617506.45 4845.74 40612660.71 0.198047E+09 6812742.02
October 35174346.25 0.00 35174346.25 0.146700E+09 11660494.70
November 29597707.26 0.00 29597707.26 93998368.68 47541490.00
December 27090367.29 0.00 27090367.29 54247403.99 0.105123E+09
           
Annual Sum or Average 0.474541E+09 12536539.50 0.462004E+09 0.170386E+10 0.522874E+09
Minimum of Months 27090367.29 0.00 27090367.29 46355305.83 1575916.41
Maximum of Months 54430580.28 4858419.83 50857525.06 0.250676E+09 0.127158E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 95BA33

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 88242763.32 42412791.66 45829971.66 0.191576E+09 0.125111E+09
February 91651175.68 42371146.31 49280029.37 0.216086E+09 84088744.59
March 0.123156E+09 57764971.78 65391358.28 0.291455E+09 64395592.37
April 0.129664E+09 57527330.77 72136783.44 0.381193E+09 19838699.07
May 0.126860E+09 50231961.63 76627628.65 0.456894E+09 2189591.20
June 0.121215E+09 46303349.38 74911540.88 0.486894E+09 45575.30
July 0.128918E+09 46348603.17 82569305.18 0.532762E+09 538663.80
August 0.117744E+09 39142591.67 78601300.25 0.473824E+09 194116.39
September 0.109829E+09 39485110.98 70343901.52 0.446549E+09 581330.54
October 0.104431E+09 44770520.31 59660125.68 0.375281E+09 3801042.66
November 82420042.55 32932623.39 49487419.16 0.247305E+09 38244940.65
December 69196112.34 24749537.56 44446574.78 0.157503E+09 0.102639E+09
           
Annual Sum or Average 0.129333E+10 0.524041E+09 0.769286E+09 0.425732E+10 0.441669E+09
Minimum of Months 69196112.34 24749537.56 44446574.78 0.157503E+09 45575.30
Maximum of Months 0.129664E+09 57764971.78 82569305.18 0.532762E+09 0.125111E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: F27282

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 88242763.32 42412791.66 45829971.66 0.191026E+09 0.125818E+09
February 91651175.68 42371146.31 49280029.37 0.215247E+09 84218550.92
March 0.123156E+09 57764971.78 65391358.28 0.291223E+09 64433101.60
April 0.129664E+09 57527330.77 72136783.44 0.381193E+09 19838699.07
May 0.126860E+09 50231961.63 76627628.65 0.456894E+09 2189591.20
June 0.121215E+09 46303349.38 74911540.88 0.486894E+09 45575.30
July 0.128918E+09 46348603.17 82569305.18 0.532762E+09 538663.80
August 0.117744E+09 39142591.67 78601300.25 0.473823E+09 194116.39
September 0.109829E+09 39485110.98 70343901.52 0.446506E+09 581330.54
October 0.104431E+09 44770520.31 59660125.68 0.374721E+09 3801703.51
November 82420042.55 32932623.39 49487419.16 0.246464E+09 38325677.79
December 69196112.34 24749537.56 44446574.78 0.156603E+09 0.103080E+09
           
Annual Sum or Average 0.129333E+10 0.524041E+09 0.769286E+09 0.425336E+10 0.443066E+09
Minimum of Months 69196112.34 24749537.56 44446574.78 0.156603E+09 45575.30
Maximum of Months 0.129664E+09 57764971.78 82569305.18 0.532762E+09 0.125818E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 3DB407

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.254342E+09 0.164153E+09 90189029.32 0.624884E+09 0.183607E+09
February 0.212289E+09 0.123649E+09 88640476.84 0.540135E+09 0.127536E+09
March 0.187368E+09 84156542.45 0.103212E+09 0.472920E+09 0.101600E+09
April 0.124803E+09 27770533.37 97032688.71 0.393429E+09 31224221.57
May 98994435.02 3668325.11 95326109.91 0.431601E+09 3471874.47
June 90080333.06 351675.61 89728657.45 0.462319E+09 64713.26
July 0.100187E+09 1644036.23 98543294.53 0.519031E+09 830022.08
August 0.116590E+09 13226394.59 0.103364E+09 0.545222E+09 298077.46
September 0.145795E+09 40214275.64 0.105581E+09 0.628594E+09 888717.47
October 0.203423E+09 97928339.85 0.105495E+09 0.704949E+09 5522641.50
November 0.217714E+09 0.121018E+09 96695759.17 0.641224E+09 58259205.93
December 0.244096E+09 0.152482E+09 91614660.18 0.620954E+09 0.149343E+09
           
Annual Sum or Average 0.199568E+10 0.830261E+09 0.116542E+10 0.658526E+10 0.662645E+09
Minimum of Months 90080333.06 351675.61 88640476.84 0.393429E+09 64713.26
Maximum of Months 0.254342E+09 0.164153E+09 0.105581E+09 0.704949E+09 0.183607E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 3DADE2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.254342E+09 0.164153E+09 90189029.32 0.624884E+09 0.183607E+09
February 0.212289E+09 0.123649E+09 88640476.84 0.540135E+09 0.127536E+09
March 0.187368E+09 84156542.45 0.103212E+09 0.472920E+09 0.101600E+09
April 0.124803E+09 27770533.37 97032688.71 0.393435E+09 31222240.96
May 98994435.02 3668325.11 95326109.91 0.431642E+09 3459091.63
June 90080333.06 351675.61 89728657.45 0.462368E+09 64713.26
July 0.100187E+09 1644036.23 98543294.53 0.519086E+09 830022.08
August 0.116590E+09 13226394.59 0.103364E+09 0.545210E+09 298077.46
September 0.145795E+09 40214275.64 0.105581E+09 0.628594E+09 888717.47
October 0.203423E+09 97928339.85 0.105495E+09 0.704949E+09 5522641.50
November 0.217714E+09 0.121018E+09 96695759.17 0.641224E+09 58259205.93
December 0.244096E+09 0.152482E+09 91614660.18 0.620954E+09 0.149343E+09
           
Annual Sum or Average 0.199568E+10 0.830261E+09 0.116542E+10 0.658540E+10 0.662631E+09
Minimum of Months 90080333.06 351675.61 88640476.84 0.393435E+09 64713.26
Maximum of Months 0.254342E+09 0.164153E+09 0.105581E+09 0.704949E+09 0.183607E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: DF3E2C

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.254342E+09 0.164153E+09 90189029.32 0.624884E+09 0.183607E+09
February 0.212289E+09 0.123649E+09 88640476.84 0.540135E+09 0.127536E+09
March 0.187368E+09 84156542.45 0.103212E+09 0.472920E+09 0.101600E+09
April 0.124803E+09 27770533.37 97032688.71 0.393441E+09 31219882.76
May 98994435.02 3668325.11 95326109.91 0.431661E+09 3462872.73
June 90080333.06 351675.61 89728657.45 0.462358E+09 64713.26
July 0.100187E+09 1644036.23 98543294.53 0.519064E+09 830022.08
August 0.116590E+09 13226394.59 0.103364E+09 0.545247E+09 298077.46
September 0.145795E+09 40214275.64 0.105581E+09 0.628593E+09 888717.47
October 0.203423E+09 97928339.85 0.105495E+09 0.704949E+09 5522641.50
November 0.217714E+09 0.121018E+09 96695759.17 0.641224E+09 58259205.93
December 0.244096E+09 0.152482E+09 91614660.18 0.620954E+09 0.149343E+09
           
Annual Sum or Average 0.199568E+10 0.830261E+09 0.116542E+10 0.658543E+10 0.662632E+09
Minimum of Months 90080333.06 351675.61 88640476.84 0.393441E+09 64713.26
Maximum of Months 0.254342E+09 0.164153E+09 0.105581E+09 0.704949E+09 0.183607E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 5031C8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.254342E+09 0.164153E+09 90189029.32 0.624884E+09 0.183607E+09
February 0.212289E+09 0.123649E+09 88640476.84 0.540135E+09 0.127536E+09
March 0.187368E+09 84156542.45 0.103212E+09 0.472920E+09 0.101600E+09
April 0.124803E+09 27770533.37 97032688.71 0.393431E+09 31223731.86
May 98994435.02 3668325.11 95326109.91 0.431869E+09 3444801.18
June 90080333.06 351675.61 89728657.45 0.462867E+09 64713.26
July 0.100187E+09 1644036.23 98543294.53 0.519406E+09 830022.08
August 0.116590E+09 13226394.59 0.103364E+09 0.545252E+09 298077.46
September 0.145795E+09 40214275.64 0.105581E+09 0.628593E+09 888717.47
October 0.203423E+09 97928339.85 0.105495E+09 0.704949E+09 5522641.50
November 0.217714E+09 0.121018E+09 96695759.17 0.641224E+09 58259205.93
December 0.244096E+09 0.152482E+09 91614660.18 0.620954E+09 0.149343E+09
           
Annual Sum or Average 0.199568E+10 0.830261E+09 0.116542E+10 0.658648E+10 0.662618E+09
Minimum of Months 90080333.06 351675.61 88640476.84 0.393431E+09 64713.26
Maximum of Months 0.254342E+09 0.164153E+09 0.105581E+09 0.704949E+09 0.183607E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C087D0

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.254342E+09 0.164153E+09 90189029.32 0.618348E+09 0.228785E+09
February 0.212289E+09 0.123649E+09 88640476.84 0.531323E+09 0.169315E+09
March 0.187368E+09 84156542.45 0.103212E+09 0.458993E+09 0.149579E+09
April 0.124803E+09 27770533.37 97032688.71 0.371188E+09 74206233.61
May 98994435.02 3668325.11 95326109.91 0.377033E+09 16440905.43
June 90080333.06 351675.61 89728657.45 0.405993E+09 2616675.58
July 0.100187E+09 1644036.23 98543294.53 0.462227E+09 7544550.27
August 0.116590E+09 13226394.59 0.103364E+09 0.485991E+09 3722959.93
September 0.145795E+09 40214275.64 0.105581E+09 0.584624E+09 13196910.80
October 0.203423E+09 97928339.85 0.105495E+09 0.667167E+09 24935983.24
November 0.217714E+09 0.121018E+09 96695759.17 0.618775E+09 89026660.72
December 0.244096E+09 0.152482E+09 91614660.18 0.610091E+09 0.193646E+09
           
Annual Sum or Average 0.199568E+10 0.830261E+09 0.116542E+10 0.619175E+10 0.973015E+09
Minimum of Months 90080333.06 351675.61 88640476.84 0.371188E+09 2616675.58
Maximum of Months 0.254342E+09 0.164153E+09 0.105581E+09 0.667167E+09 0.228785E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: D2CA75

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.254342E+09 0.164153E+09 90189029.32 0.618348E+09 0.228785E+09
February 0.212289E+09 0.123649E+09 88640476.84 0.531323E+09 0.169315E+09
March 0.187368E+09 84156542.45 0.103212E+09 0.458993E+09 0.149579E+09
April 0.124803E+09 27770533.37 97032688.71 0.371199E+09 74180230.39
May 98994435.02 3668325.11 95326109.91 0.376990E+09 16441291.69
June 90080333.06 351675.61 89728657.45 0.405910E+09 2617145.93
July 0.100187E+09 1644036.23 98543294.53 0.462165E+09 7545237.88
August 0.116590E+09 13226394.59 0.103364E+09 0.485999E+09 3722953.22
September 0.145795E+09 40214275.64 0.105581E+09 0.584624E+09 13196910.80
October 0.203423E+09 97928339.85 0.105495E+09 0.667167E+09 24935983.24
November 0.217714E+09 0.121018E+09 96695759.17 0.618775E+09 89026660.72
December 0.244096E+09 0.152482E+09 91614660.18 0.610091E+09 0.193646E+09
           
Annual Sum or Average 0.199568E+10 0.830261E+09 0.116542E+10 0.619158E+10 0.972991E+09
Minimum of Months 90080333.06 351675.61 88640476.84 0.371199E+09 2617145.93
Maximum of Months 0.254342E+09 0.164153E+09 0.105581E+09 0.667167E+09 0.228785E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: B0FB49

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.203474E+09 0.131322E+09 72151223.46 0.494679E+09 0.183028E+09
February 0.169831E+09 98919017.11 70912381.47 0.425058E+09 0.135452E+09
March 0.149895E+09 67325233.96 82569543.47 0.367195E+09 0.119663E+09
April 99842577.67 22216426.70 77626150.97 0.296956E+09 59347675.87
May 79195548.02 2934660.09 76260887.93 0.301669E+09 13152438.70
June 72064266.45 281340.49 71782925.96 0.324753E+09 2093704.26
July 80149864.61 1315228.99 78834635.62 0.369770E+09 6035795.16
August 93272015.05 10581115.67 82690899.39 0.388817E+09 2978341.87
September 0.116636E+09 32171420.52 84464961.28 0.467699E+09 10557528.64
October 0.162739E+09 78342671.88 84396028.01 0.533733E+09 19948786.60
November 0.174171E+09 96814305.18 77356607.34 0.495020E+09 71221328.58
December 0.195277E+09 0.121985E+09 73291728.15 0.488073E+09 0.154917E+09
           
Annual Sum or Average 0.159655E+10 0.664209E+09 0.932338E+09 0.495342E+10 0.778395E+09
Minimum of Months 72064266.45 281340.49 70912381.47 0.296956E+09 2093704.26
Maximum of Months 0.203474E+09 0.131322E+09 84464961.28 0.533733E+09 0.183028E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FE9BC9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 69807528.87 30875993.36 38931535.51 0.151757E+09 0.147375E+09
February 78628950.11 36263573.07 42365377.04 0.190071E+09 0.107453E+09
March 0.108113E+09 50042154.16 58071331.39 0.261921E+09 94708816.69
April 0.114876E+09 53820974.64 61054659.89 0.326338E+09 42221210.30
May 0.108355E+09 42432159.72 65923024.84 0.364340E+09 9398411.02
June 88511399.01 25423757.69 63087641.32 0.345900E+09 1399947.58
July 0.102474E+09 32531590.58 69941949.76 0.404502E+09 4181427.22
August 0.102302E+09 34064417.40 68237280.50 0.379954E+09 1897374.66
September 84382757.68 25508722.92 58874034.75 0.333042E+09 7419836.16
October 86990672.14 34655828.97 52334843.17 0.293216E+09 14296342.62
November 69708579.56 26304321.61 43404257.95 0.204731E+09 56151897.42
December 72418168.00 33202672.36 39215495.64 0.169504E+09 0.121859E+09
           
Annual Sum or Average 0.108657E+10 0.425126E+09 0.661441E+09 0.342528E+10 0.608363E+09
Minimum of Months 69708579.56 25423757.69 38931535.51 0.151757E+09 1399947.58
Maximum of Months 0.114876E+09 53820974.64 69941949.76 0.404502E+09 0.147375E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 9DF7DE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 68755996.84 30875993.36 37880003.48 0.149367E+09 0.147443E+09
February 77522165.20 36263573.07 41258592.13 0.187707E+09 0.107096E+09
March 0.106667E+09 50042154.16 56625003.49 0.259055E+09 93952170.20
April 0.113314E+09 53820974.64 59492985.10 0.322943E+09 41327700.70
May 0.105406E+09 41761388.04 63644548.57 0.357412E+09 8914628.55
June 86126599.18 24987681.91 61138917.27 0.340611E+09 1276775.53
July 99670709.38 32104079.47 67566629.91 0.397922E+09 3930374.78
August 0.100350E+09 33998948.49 66351480.07 0.376261E+09 1786747.35
September 82823069.10 25508722.92 57314346.18 0.329682E+09 6949321.32
October 85596092.91 34655828.97 50940263.95 0.290260E+09 13624428.92
November 68571893.76 26304321.61 42267572.15 0.201902E+09 55678180.62
December 71380100.66 33202672.36 38177428.30 0.166856E+09 0.121440E+09
           
Annual Sum or Average 0.106618E+10 0.423526E+09 0.642658E+09 0.337998E+10 0.603420E+09
Minimum of Months 68571893.76 24987681.91 37880003.48 0.149367E+09 1276775.53
Maximum of Months 0.113314E+09 53820974.64 67566629.91 0.397922E+09 0.147443E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: D0BE44

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66094271.62 30875993.36 35218278.26 0.145401E+09 0.143972E+09
February 74725560.00 36263573.07 38461986.93 0.183038E+09 0.104096E+09
March 0.103014E+09 50042154.16 52972299.31 0.252340E+09 90979928.10
April 0.107065E+09 52008037.49 55056686.47 0.309410E+09 38831656.41
May 97962619.57 39579127.89 58383491.68 0.340903E+09 7434052.66
June 79293560.53 23215885.90 56077674.63 0.326170E+09 930803.32
July 92591901.36 30483738.11 62108163.26 0.382592E+09 3148835.46
August 94205707.30 33167349.79 61038357.51 0.365097E+09 1534966.44
September 78688526.72 25499429.74 53189096.98 0.321629E+09 5454733.22
October 82111084.92 34655828.97 47455255.95 0.285014E+09 11484300.54
November 65561526.03 26304321.61 39257204.43 0.196970E+09 53115919.60
December 68658178.07 33202672.36 35455505.71 0.162077E+09 0.118568E+09
           
Annual Sum or Average 0.100997E+10 0.415298E+09 0.594674E+09 0.327064E+10 0.579552E+09
Minimum of Months 65561526.03 23215885.90 35218278.26 0.145401E+09 930803.32
Maximum of Months 0.107065E+09 52008037.49 62108163.26 0.382592E+09 0.143972E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 6B5226

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94323916.22 41167991.15 53155925.07 0.206084E+09 0.201553E+09
February 0.106152E+09 48351430.76 57800830.79 0.259193E+09 0.146732E+09
March 0.145868E+09 66722872.21 79145452.99 0.357435E+09 0.129627E+09
April 0.155050E+09 71761299.51 83288225.98 0.445033E+09 60985028.91
May 0.146451E+09 56577408.58 89873901.76 0.493985E+09 15555273.87
June 0.120213E+09 34039596.86 86173540.57 0.468006E+09 2989440.55
July 0.138948E+09 43421257.54 95526816.51 0.546951E+09 7766235.15
August 0.138466E+09 45419223.20 93046659.69 0.512841E+09 3716887.59
September 0.114331E+09 34011630.56 80318915.68 0.449414E+09 12847668.92
October 0.117650E+09 46207771.96 71442170.15 0.394818E+09 23432851.31
November 94268520.39 35072428.81 59196091.58 0.276766E+09 79443881.26
December 97771468.87 44270229.81 53501239.06 0.229710E+09 0.166716E+09
           
Annual Sum or Average 0.146949E+10 0.567023E+09 0.902470E+09 0.464024E+10 0.851365E+09
Minimum of Months 94268520.39 34011630.56 53155925.07 0.206084E+09 2989440.55
Maximum of Months 0.155050E+09 71761299.51 95526816.51 0.546951E+09 0.201553E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 8F59F7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.201062E+09 0.130069E+09 70993143.75 0.498172E+09 0.188563E+09
February 0.168216E+09 98356127.81 69860261.60 0.429206E+09 0.139161E+09
March 0.148743E+09 67171663.36 81571803.06 0.370462E+09 0.122446E+09
April 98882530.31 22216426.70 76666103.61 0.298931E+09 62758346.45
May 78180155.53 2934660.09 75245495.45 0.301155E+09 15323315.51
June 71067770.00 281340.49 70786429.51 0.323214E+09 2987625.57
July 79033381.61 1315228.99 77718152.62 0.367753E+09 7762973.25
August 92208140.66 10581107.18 81627033.49 0.387863E+09 3972006.10
September 0.115660E+09 32149291.34 83510394.66 0.467581E+09 12772622.46
October 0.161420E+09 78098789.39 83320988.45 0.534056E+09 23342463.41
November 0.172290E+09 96103607.20 76186838.41 0.496822E+09 75392437.91
December 0.193915E+09 0.121708E+09 72207156.44 0.491348E+09 0.158162E+09
           
Annual Sum or Average 0.158068E+10 0.660985E+09 0.919694E+09 0.496656E+10 0.812645E+09
Minimum of Months 71067770.00 281340.49 69860261.60 0.298931E+09 2987625.57
Maximum of Months 0.201062E+09 0.130069E+09 83510394.66 0.534056E+09 0.188563E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 44F571

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.186449E+09 0.121310E+09 65139121.34 0.463350E+09 0.188505E+09
February 0.157753E+09 93267554.21 64485457.21 0.405349E+09 0.138798E+09
March 0.140404E+09 64781774.99 75622073.98 0.352339E+09 0.121241E+09
April 93130292.16 22101124.83 71029167.33 0.286275E+09 59426309.44
May 72227334.32 2934557.92 69292776.40 0.288982E+09 13417976.56
June 65174314.71 281340.49 64892974.22 0.311657E+09 2319206.07
July 72533935.95 1314718.01 71219217.94 0.354152E+09 6494259.24
August 85848101.95 10510399.73 75337702.22 0.376367E+09 3463218.78
September 0.108910E+09 31452156.12 77457381.63 0.451588E+09 10993580.83
October 0.151455E+09 74408498.87 77046488.01 0.508373E+09 20663531.06
November 0.160738E+09 90435800.62 70301762.56 0.468285E+09 73929382.19
December 0.183020E+09 0.116354E+09 66665583.26 0.464621E+09 0.156416E+09
           
Annual Sum or Average 0.147764E+10 0.629152E+09 0.848490E+09 0.473134E+10 0.795667E+09
Minimum of Months 65174314.71 281340.49 64485457.21 0.286275E+09 2319206.07
Maximum of Months 0.186449E+09 0.121310E+09 77457381.63 0.508373E+09 0.188505E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 6BD844

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.155761E+09 0.106442E+09
February 73380118.53 33924372.54 39455745.99 0.173792E+09 74316471.73
March 98604584.71 46249407.74 52355176.96 0.229101E+09 61899061.60
April 0.103815E+09 46059140.94 57755855.00 0.293785E+09 28807900.74
May 0.101570E+09 40218118.41 61351436.62 0.340506E+09 5237658.97
June 97050161.53 37072682.97 59977478.57 0.362398E+09 840824.19
July 0.103218E+09 37108915.32 66108616.44 0.397613E+09 2862525.65
August 94271106.47 31339436.79 62931669.67 0.354432E+09 1097631.75
September 87934116.79 31613674.19 56320442.61 0.339084E+09 4358522.25
October 83611947.41 35845426.47 47766520.94 0.289120E+09 8024352.39
November 65989252.20 26367438.26 39621813.94 0.195580E+09 36950562.85
December 55401550.76 19815667.15 35585883.61 0.128440E+09 87497406.54
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.325961E+10 0.418335E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.128440E+09 840824.19
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.397613E+09 0.106442E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 86D536

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.155761E+09 0.106442E+09
February 73380118.53 33924372.54 39455745.99 0.173792E+09 74316471.73
March 98604584.71 46249407.74 52355176.96 0.229101E+09 61899061.60
April 0.103815E+09 46059140.94 57755855.00 0.293785E+09 28807900.74
May 0.101570E+09 40218118.41 61351436.62 0.340506E+09 5237658.97
June 97050161.53 37072682.97 59977478.57 0.362398E+09 840824.19
July 0.103218E+09 37108915.32 66108616.44 0.397613E+09 2862525.65
August 94271106.47 31339436.79 62931669.67 0.354432E+09 1097631.75
September 87934116.79 31613674.19 56320442.61 0.339084E+09 4358522.25
October 83611947.41 35845426.47 47766520.94 0.289120E+09 8024352.39
November 65989252.20 26367438.26 39621813.94 0.195580E+09 36950562.85
December 55401550.76 19815667.15 35585883.61 0.128440E+09 87497406.54
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.325961E+10 0.418335E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.128440E+09 840824.19
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.397613E+09 0.106442E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BAF71D

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.155761E+09 0.106442E+09
February 73380118.53 33924372.54 39455745.99 0.173792E+09 74316471.73
March 98604584.71 46249407.74 52355176.96 0.229101E+09 61899061.60
April 0.103815E+09 46059140.94 57755855.00 0.293785E+09 28807900.74
May 0.101570E+09 40218118.41 61351436.62 0.340506E+09 5237658.97
June 97050161.53 37072682.97 59977478.57 0.362398E+09 840824.19
July 0.103218E+09 37108915.32 66108616.44 0.397613E+09 2862525.65
August 94271106.47 31339436.79 62931669.67 0.354432E+09 1097631.75
September 87934116.79 31613674.19 56320442.61 0.339084E+09 4358522.25
October 83611947.41 35845426.47 47766520.94 0.289120E+09 8024352.39
November 65989252.20 26367438.26 39621813.94 0.195580E+09 36950562.85
December 55401550.76 19815667.15 35585883.61 0.128440E+09 87497406.54
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.325961E+10 0.418335E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.128440E+09 840824.19
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.397613E+09 0.106442E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 3833A2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70651199.11 33957715.80 36693483.31 0.155761E+09 0.106442E+09
February 73380118.53 33924372.54 39455745.99 0.173792E+09 74316471.73
March 98604584.71 46249407.74 52355176.96 0.229101E+09 61899061.60
April 0.103815E+09 46059140.94 57755855.00 0.293785E+09 28807900.74
May 0.101570E+09 40218118.41 61351436.62 0.340506E+09 5237658.97
June 97050161.53 37072682.97 59977478.57 0.362398E+09 840824.19
July 0.103218E+09 37108915.32 66108616.44 0.397613E+09 2862525.65
August 94271106.47 31339436.79 62931669.67 0.354432E+09 1097631.75
September 87934116.79 31613674.19 56320442.61 0.339084E+09 4358522.25
October 83611947.41 35845426.47 47766520.94 0.289120E+09 8024352.39
November 65989252.20 26367438.26 39621813.94 0.195580E+09 36950562.85
December 55401550.76 19815667.15 35585883.61 0.128440E+09 87497406.54
           
Annual Sum or Average 0.103550E+10 0.419572E+09 0.615924E+09 0.325961E+10 0.418335E+09
Minimum of Months 55401550.76 19815667.15 35585883.61 0.128440E+09 840824.19
Maximum of Months 0.103815E+09 46249407.74 66108616.44 0.397613E+09 0.106442E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 2111A1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 23550399.70 11319238.60 12231161.10 57120844.71 31661723.07
February 24460039.51 11308124.18 13151915.33 63770191.41 22651174.23
March 32868194.90 15416469.25 17451725.65 84428228.83 19706022.12
April 34604998.65 15353046.98 19251951.67 0.103594E+09 12027444.51
May 33856518.34 13406039.47 20450478.87 0.113338E+09 4789376.45
June 32350053.84 12357560.99 19992492.86 0.117027E+09 1716195.38
July 34405843.92 12369638.44 22036205.48 0.128771E+09 3116267.12
August 31423702.16 10446478.93 20977223.22 0.113011E+09 1672492.37
September 29311372.26 10537891.40 18773480.87 0.109527E+09 4028613.54
October 27870649.14 11948475.49 15922173.65 94172232.13 6203795.60
November 21996417.40 8789146.09 13207271.31 65676733.92 13996463.81
December 18467183.59 6605222.38 11861961.20 45933709.48 26728554.24
           
Annual Sum or Average 0.345165E+09 0.139857E+09 0.205308E+09 0.109637E+10 0.148298E+09
Minimum of Months 18467183.59 6605222.38 11861961.20 45933709.48 1672492.37
Maximum of Months 34604998.65 15416469.25 22036205.48 0.128771E+09 31661723.07



Table of Contents

Report: WindowEnergyReportMonthly

For: 9BC521

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 56086816.08 0.00 56086816.08 98513718.91 0.203363E+09
February 59963082.16 0.00 59963082.16 0.134330E+09 0.144399E+09
March 79172060.85 0.00 79172060.85 0.173687E+09 0.127890E+09
April 86132078.32 663577.90 85468500.42 0.251838E+09 64916746.97
May 0.103129E+09 6351924.68 96777359.45 0.381864E+09 21692790.06
June 0.107137E+09 9949293.59 97188154.12 0.443332E+09 7490450.89
July 0.111465E+09 7317065.33 0.104148E+09 0.480350E+09 14805849.49
August 97413115.47 1382400.68 96030714.78 0.409322E+09 7929877.68
September 83214708.84 13180.69 83201528.15 0.373999E+09 21160589.88
October 72031629.56 0.00 72031629.56 0.276985E+09 31078476.65
November 60611534.04 0.00 60611534.04 0.183708E+09 84427370.95
December 55476888.96 0.00 55476888.96 0.113251E+09 0.167515E+09
           
Annual Sum or Average 0.971834E+09 25677442.87 0.946157E+09 0.332118E+10 0.896669E+09
Minimum of Months 55476888.96 0.00 55476888.96 98513718.91 7490450.89
Maximum of Months 0.111465E+09 9949293.59 0.104148E+09 0.480350E+09 0.203363E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 142781

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54776411.44 0.00 54776411.44 98646107.16 0.196124E+09
February 58562112.98 0.00 58562112.98 0.134130E+09 0.139228E+09
March 77322295.74 0.00 77322295.74 0.173784E+09 0.123372E+09
April 84119700.32 648074.16 83471626.16 0.249606E+09 63665930.21
May 0.100720E+09 6203519.19 94516266.57 0.375644E+09 21874554.72
June 0.104634E+09 9716839.66 94917463.49 0.434660E+09 7534244.29
July 0.108861E+09 7146110.42 0.101715E+09 0.470457E+09 14815750.06
August 95124507.98 1348999.74 93775508.24 0.399629E+09 7750391.58
September 81234062.68 9464.68 81224598.00 0.365301E+09 20927284.42
October 70348692.50 0.00 70348692.50 0.270886E+09 31086394.75
November 59195414.51 0.00 59195414.51 0.181239E+09 82068144.05
December 54180734.58 0.00 54180734.58 0.113266E+09 0.161046E+09
           
Annual Sum or Average 0.949079E+09 25073007.85 0.924006E+09 0.326725E+10 0.869493E+09
Minimum of Months 54180734.58 0.00 54180734.58 98646107.16 7534244.29
Maximum of Months 0.108861E+09 9716839.66 0.101715E+09 0.470457E+09 0.196124E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: E74902

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54776411.44 0.00 54776411.44 0.102960E+09 0.210086E+09
February 58562112.98 0.00 58562112.98 0.136745E+09 0.152444E+09
March 77322295.74 0.00 77322295.74 0.174444E+09 0.138796E+09
April 84119700.32 648074.16 83471626.16 0.245575E+09 79307378.37
May 0.100720E+09 6203519.19 94516266.57 0.366441E+09 32732043.80
June 0.104634E+09 9716839.66 94917463.49 0.423082E+09 11220623.54
July 0.108861E+09 7146110.42 0.101715E+09 0.460310E+09 21007972.03
August 95137168.87 1350102.46 93787066.41 0.387024E+09 12325058.01
September 81270491.86 12872.74 81257619.12 0.358612E+09 26399154.54
October 70348692.50 0.00 70348692.50 0.267461E+09 40609513.64
November 59195414.51 0.00 59195414.51 0.179980E+09 93044085.11
December 54180734.58 0.00 54180734.58 0.113495E+09 0.176550E+09
           
Annual Sum or Average 0.949128E+09 25077518.63 0.924051E+09 0.321613E+10 0.994523E+09
Minimum of Months 54180734.58 0.00 54180734.58 0.102960E+09 11220623.54
Maximum of Months 0.108861E+09 9716839.66 0.101715E+09 0.460310E+09 0.210086E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 93BBC3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54776411.44 0.00 54776411.44 0.100574E+09 0.212781E+09
February 58562112.98 0.00 58562112.98 0.133870E+09 0.154565E+09
March 77322295.74 0.00 77322295.74 0.170278E+09 0.140681E+09
April 84119700.32 648074.16 83471626.16 0.241791E+09 79339983.34
May 0.100720E+09 6203519.19 94516266.57 0.363330E+09 32037702.82
June 0.104634E+09 9716839.66 94917463.49 0.421062E+09 10955825.11
July 0.108861E+09 7146110.42 0.101715E+09 0.458668E+09 20611116.84
August 95137168.87 1350102.46 93787066.41 0.386800E+09 12254792.45
September 81270491.86 12872.74 81257619.12 0.358272E+09 26161665.24
October 70348692.50 0.00 70348692.50 0.266836E+09 39836493.22
November 59195414.51 0.00 59195414.51 0.177996E+09 93538109.19
December 54180734.58 0.00 54180734.58 0.110836E+09 0.179428E+09
           
Annual Sum or Average 0.949128E+09 25077518.63 0.924051E+09 0.319031E+10 0.100219E+10
Minimum of Months 54180734.58 0.00 54180734.58 0.100574E+09 10955825.11
Maximum of Months 0.108861E+09 9716839.66 0.101715E+09 0.458668E+09 0.212781E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C635A6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 48552487.07 31441635.85 17110851.23 0.128039E+09 47982823.78
February 39812493.36 23099732.61 16712760.75 0.109244E+09 35450765.82
March 35880546.23 16133107.88 19747438.35 97282484.86 32108115.65
April 24272093.33 5550451.28 18721642.05 77610442.56 18638571.48
May 19053975.98 733665.02 18320310.96 74180596.32 6712499.35
June 17268998.92 70335.12 17198663.80 77370167.53 1922257.43
July 19232226.07 328807.25 18903418.82 88286076.27 3766228.02
August 22517371.04 2633114.47 19884256.57 92879712.14 2296625.09
September 28162467.11 7877878.55 20284588.57 0.113534E+09 5342993.10
October 38543566.81 18491974.11 20051592.70 0.129628E+09 9985124.10
November 40969950.12 22702754.04 18267196.08 0.122628E+09 21993731.37
December 47777629.48 30175651.15 17601978.33 0.128155E+09 40251187.32
           
Annual Sum or Average 0.382044E+09 0.159239E+09 0.222805E+09 0.123884E+10 0.226451E+09
Minimum of Months 17268998.92 70335.12 16712760.75 74180596.32 1922257.43
Maximum of Months 48552487.07 31441635.85 20284588.57 0.129628E+09 47982823.78



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 102.69 33.08 37.98 24.52 13.47 0.00 0.00
February 100.71 25.57 35.10 20.44 14.66 0.00 0.00
March 82.50 18.62 27.98 12.57 15.41 0.00 0.00
April 72.54 6.74 19.26 4.29 14.97 0.00 0.00
May 76.74 0.99 14.78 0.55 14.24 0.00 0.00
June 84.95 0.03 13.90 0.05 13.85 0.00 0.00
July 92.34 0.14 14.96 0.25 14.72 0.00 0.00
August 95.11 0.01 17.41 1.98 15.44 0.00 0.00
September 111.71 0.21 22.50 6.21 16.29 0.00 0.00
October 117.99 1.49 30.38 14.62 15.75 0.00 0.00
November 109.87 12.20 33.60 18.68 14.92 0.00 0.00
December 102.67 27.45 36.45 22.77 13.68 0.00 0.00
               
Annual Sum or Average 95.79 10.48 25.31 10.53 14.78 0.00 0.00
Minimum of Months 72.54 0.01 13.90 0.05 13.47 0.00 0.00
Maximum of Months 117.99 33.08 37.98 24.52 16.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 333.15 178.04 131.07 82.89 48.18 0.00 0.00
February 325.95 146.64 122.59 69.80 52.79 0.00 0.00
March 267.08 118.36 101.72 44.89 56.83 0.00 0.00
April 226.95 69.66 72.81 16.70 56.12 0.00 0.00
May 209.43 26.89 55.50 2.19 53.31 0.00 0.00
June 217.86 9.45 51.82 0.22 51.61 0.00 0.00
July 245.36 15.13 55.93 0.98 54.95 0.00 0.00
August 250.59 11.97 65.47 7.69 57.78 0.00 0.00
September 320.74 21.11 83.21 22.89 60.32 0.00 0.00
October 349.57 38.28 107.92 50.53 57.39 0.00 0.00
November 336.84 86.48 116.85 63.31 53.54 0.00 0.00
December 345.40 150.02 132.68 83.07 49.61 0.00 0.00
               
Annual Sum or Average 285.52 72.35 91.32 36.95 54.37 0.00 0.00
Minimum of Months 209.43 9.45 51.82 0.22 48.18 0.00 0.00
Maximum of Months 349.57 178.04 132.68 83.07 60.32 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 CLEAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 14.64 38.19 7.91 0.00 7.91 0.00 0.00
February 22.88 29.64 9.38 0.00 9.38 0.00 0.00
March 27.32 22.89 11.19 0.00 11.19 0.00 0.00
April 41.09 11.16 12.44 0.03 12.41 0.00 0.00
May 58.17 2.84 13.82 0.50 13.32 0.00 0.00
June 70.01 0.69 14.72 1.00 13.72 0.00 0.00
July 73.29 1.43 14.85 0.62 14.23 0.00 0.00
August 63.27 0.90 13.43 0.10 13.33 0.00 0.00
September 60.72 2.85 12.06 0.00 12.06 0.00 0.00
October 43.20 4.92 10.14 0.00 10.14 0.00 0.00
November 28.99 16.05 8.80 0.00 8.80 0.00 0.00
December 16.70 31.86 7.80 0.00 7.80 0.00 0.00
               
Annual Sum or Average 43.45 13.55 11.39 0.19 11.20 0.00 0.00
Minimum of Months 14.64 0.69 7.80 0.00 7.80 0.00 0.00
Maximum of Months 73.29 38.19 14.85 1.00 14.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 IT HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 LOBBY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 163.91 166.71 69.90 30.74 39.16 0.00 0.00
February 226.50 136.51 87.14 39.97 47.17 0.00 0.00
March 280.47 112.08 108.19 49.82 58.37 0.00 0.00
April 352.31 64.95 118.89 55.37 63.52 0.00 0.00
May 369.72 23.33 108.47 42.25 66.23 0.00 0.00
June 354.94 6.96 91.80 26.27 65.54 0.00 0.00
July 404.69 11.77 102.83 32.42 70.41 0.00 0.00
August 373.89 7.49 102.45 33.92 68.53 0.00 0.00
September 344.15 16.98 87.32 26.24 61.08 0.00 0.00
October 295.71 30.10 87.16 34.50 52.66 0.00 0.00
November 217.19 76.27 72.08 27.06 45.02 0.00 0.00
December 181.01 139.95 72.44 33.06 39.38 0.00 0.00
               
Annual Sum or Average 297.40 65.78 92.43 35.96 56.47 0.00 0.00
Minimum of Months 163.91 6.96 69.90 26.24 39.16 0.00 0.00
Maximum of Months 404.69 166.71 118.89 55.37 70.41 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 32.07 112.11 18.56 0.00 18.56 0.00 0.00
February 50.77 90.22 22.00 0.00 22.00 0.00 0.00
March 61.19 72.41 26.27 0.00 26.27 0.00 0.00
April 94.03 37.00 29.00 0.04 28.96 0.00 0.00
May 138.36 10.97 33.03 1.36 31.66 0.00 0.00
June 168.09 2.72 35.18 2.34 32.84 0.00 0.00
July 179.50 4.43 35.62 1.70 33.92 0.00 0.00
August 151.94 3.20 31.56 0.20 31.36 0.00 0.00
September 148.08 7.94 28.37 0.00 28.37 0.00 0.00
October 103.31 14.61 23.76 0.00 23.76 0.00 0.00
November 66.99 47.91 20.70 0.00 20.70 0.00 0.00
December 37.53 93.38 18.35 0.00 18.35 0.00 0.00
               
Annual Sum or Average 102.90 41.20 26.89 0.47 26.42 0.00 0.00
Minimum of Months 32.07 2.72 18.35 0.00 18.35 0.00 0.00
Maximum of Months 179.50 112.11 35.62 2.34 33.92 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 MED GAS

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 362.81 143.62 128.72 74.39 54.34 0.00 0.00
February 393.89 114.38 130.87 68.94 61.93 0.00 0.00
March 387.69 84.05 129.59 59.67 69.92 0.00 0.00
April 424.00 39.31 118.62 44.11 74.51 0.00 0.00
May 453.50 7.63 105.41 31.13 74.28 0.00 0.00
June 487.89 1.26 102.69 28.71 73.97 0.00 0.00
July 515.63 3.63 107.00 28.20 78.80 0.00 0.00
August 483.06 1.26 105.22 27.35 77.87 0.00 0.00
September 518.97 7.04 112.85 36.81 76.04 0.00 0.00
October 489.03 13.10 123.19 56.02 67.18 0.00 0.00
November 411.86 56.48 118.11 57.70 60.42 0.00 0.00
December 340.74 119.10 114.28 60.34 53.94 0.00 0.00
               
Annual Sum or Average 439.22 48.96 116.30 47.67 68.63 0.00 0.00
Minimum of Months 340.74 1.26 102.69 27.35 53.94 0.00 0.00
Maximum of Months 518.97 143.62 130.87 74.39 78.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 220.61 123.85 79.13 38.04 41.10 0.00 0.00
February 274.39 97.69 91.00 42.07 48.93 0.00 0.00
March 325.69 72.68 110.44 51.80 58.64 0.00 0.00
April 415.74 34.35 120.16 53.31 66.85 0.00 0.00
May 460.98 6.71 113.77 45.05 68.72 0.00 0.00
June 497.57 1.11 112.33 42.91 69.42 0.00 0.00
July 522.74 3.03 115.61 41.56 74.05 0.00 0.00
August 465.36 0.96 105.59 35.10 70.49 0.00 0.00
September 463.99 5.56 101.78 36.59 65.19 0.00 0.00
October 386.88 10.39 93.65 40.15 53.50 0.00 0.00
November 281.30 47.48 76.38 30.52 45.86 0.00 0.00
December 188.44 101.93 62.05 22.19 39.86 0.00 0.00
               
Annual Sum or Average 375.71 41.91 98.51 39.91 58.59 0.00 0.00
Minimum of Months 188.44 0.96 62.05 22.19 39.86 0.00 0.00
Maximum of Months 522.74 123.85 120.16 53.31 74.05 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 PACU

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 45.41 86.66 19.99 0.00 19.99 0.00 0.00
February 68.24 66.26 23.67 0.00 23.67 0.00 0.00
March 82.01 49.80 28.23 0.00 28.23 0.00 0.00
April 123.00 18.07 31.24 0.05 31.19 0.00 0.00
May 182.97 2.91 35.20 1.36 33.84 0.00 0.00
June 221.88 0.18 38.17 2.94 35.24 0.00 0.00
July 231.37 0.50 38.25 1.86 36.39 0.00 0.00
August 203.75 0.11 33.96 0.23 33.73 0.00 0.00
September 194.31 0.75 30.58 0.00 30.58 0.00 0.00
October 142.36 3.40 25.65 0.00 25.65 0.00 0.00
November 95.18 31.16 22.32 0.00 22.32 0.00 0.00
December 54.14 70.29 19.77 0.00 19.77 0.00 0.00
               
Annual Sum or Average 137.38 27.35 28.94 0.54 28.41 0.00 0.00
Minimum of Months 45.41 0.11 19.77 0.00 19.77 0.00 0.00
Maximum of Months 231.37 86.66 38.25 2.94 36.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 104.96 65.37 40.23 24.49 15.74 0.00 0.00
February 108.52 52.64 39.30 21.82 17.48 0.00 0.00
March 91.14 41.61 33.18 14.24 18.94 0.00 0.00
April 82.47 20.67 24.24 5.40 18.83 0.00 0.00
May 83.40 5.15 18.78 0.79 17.99 0.00 0.00
June 92.74 1.04 17.43 0.08 17.34 0.00 0.00
July 103.65 1.92 18.89 0.35 18.54 0.00 0.00
August 105.58 1.46 21.87 2.54 19.33 0.00 0.00
September 125.22 3.97 27.13 7.20 19.93 0.00 0.00
October 126.97 7.87 34.78 15.82 18.95 0.00 0.00
November 116.21 27.71 37.25 19.68 17.57 0.00 0.00
December 112.34 54.45 41.67 25.65 16.03 0.00 0.00
               
Annual Sum or Average 104.40 23.53 29.52 11.46 18.06 0.00 0.00
Minimum of Months 82.47 1.04 17.43 0.08 15.74 0.00 0.00
Maximum of Months 126.97 65.37 41.67 25.65 19.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 404.58 139.49 151.94 98.06 53.88 0.00 0.00
February 396.92 108.31 140.40 81.78 58.62 0.00 0.00
March 325.12 78.98 111.93 50.27 61.66 0.00 0.00
April 286.30 29.55 77.04 17.14 59.90 0.00 0.00
May 302.42 4.41 59.14 2.19 56.95 0.00 0.00
June 335.78 0.18 55.61 0.22 55.39 0.00 0.00
July 365.25 0.70 59.85 0.98 58.87 0.00 0.00
August 374.26 0.12 69.65 7.90 61.75 0.00 0.00
September 439.23 1.29 90.00 24.82 65.17 0.00 0.00
October 462.27 7.63 121.52 58.50 63.02 0.00 0.00
November 430.88 52.84 134.39 74.70 59.69 0.00 0.00
December 404.53 116.27 145.82 91.09 54.73 0.00 0.00
               
Annual Sum or Average 377.18 44.72 101.25 42.12 59.13 0.00 0.00
Minimum of Months 286.30 0.12 55.61 0.22 53.88 0.00 0.00
Maximum of Months 462.27 139.49 151.94 98.06 65.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 18.93 12.65 7.17 4.20 2.97 0.00 0.00
February 20.15 9.84 7.06 3.75 3.31 0.00 0.00
March 17.38 7.49 6.07 2.45 3.62 0.00 0.00
April 16.60 2.99 4.46 0.85 3.61 0.00 0.00
May 18.87 0.47 3.60 0.12 3.47 0.00 0.00
June 21.61 0.03 3.38 0.01 3.36 0.00 0.00
July 23.77 0.13 3.65 0.06 3.59 0.00 0.00
August 23.57 0.07 4.08 0.40 3.68 0.00 0.00
September 26.05 0.24 4.87 1.14 3.72 0.00 0.00
October 25.60 0.78 6.28 2.71 3.57 0.00 0.00
November 22.46 4.83 6.70 3.41 3.29 0.00 0.00
December 21.34 10.44 7.74 4.71 3.03 0.00 0.00
               
Annual Sum or Average 21.37 4.14 5.41 1.98 3.44 0.00 0.00
Minimum of Months 16.60 0.03 3.38 0.01 2.97 0.00 0.00
Maximum of Months 26.05 12.65 7.74 4.71 3.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 SCRUB

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 SOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 240.25 102.66 92.55 56.72 35.84 0.00 0.00
February 253.02 80.81 90.95 50.88 40.06 0.00 0.00
March 230.90 59.70 81.79 37.59 44.19 0.00 0.00
April 232.04 24.53 66.91 22.41 44.50 0.00 0.00
May 247.72 3.86 55.25 11.66 43.59 0.00 0.00
June 263.64 0.21 49.20 6.64 42.56 0.00 0.00
July 288.57 0.79 54.05 8.59 45.47 0.00 0.00
August 284.09 0.25 58.92 12.43 46.49 0.00 0.00
September 306.04 1.73 65.43 18.97 46.45 0.00 0.00
October 303.99 7.12 81.38 37.88 43.50 0.00 0.00
November 268.16 40.38 84.19 44.12 40.07 0.00 0.00
December 244.95 86.39 90.12 53.81 36.31 0.00 0.00
               
Annual Sum or Average 263.66 33.84 72.48 30.05 42.43 0.00 0.00
Minimum of Months 230.90 0.21 49.20 6.64 35.84 0.00 0.00
Maximum of Months 306.04 102.66 92.55 56.72 46.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 101.18 35.45 37.98 24.52 13.47 0.00 0.00
February 98.29 28.42 35.10 20.44 14.66 0.00 0.00
March 78.71 22.19 27.98 12.57 15.41 0.00 0.00
April 66.63 10.48 19.26 4.29 14.97 0.00 0.00
May 66.38 2.02 14.78 0.55 14.24 0.00 0.00
June 73.17 0.28 13.90 0.05 13.85 0.00 0.00
July 80.51 0.74 14.96 0.25 14.72 0.00 0.00
August 83.53 0.24 17.41 1.98 15.44 0.00 0.00
September 102.30 1.51 22.50 6.21 16.29 0.00 0.00
October 111.39 3.25 30.38 14.62 15.75 0.00 0.00
November 105.67 14.10 33.60 18.68 14.92 0.00 0.00
December 100.75 29.69 36.45 22.77 13.68 0.00 0.00
               
Annual Sum or Average 88.99 12.30 25.31 10.53 14.78 0.00 0.00
Minimum of Months 66.38 0.24 13.90 0.05 13.47 0.00 0.00
Maximum of Months 111.39 35.45 37.98 24.52 16.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 68.70 108.49 30.68 0.00 30.68 0.00 0.00
February 97.73 85.79 36.31 0.00 36.31 0.00 0.00
March 111.09 69.25 43.30 0.00 43.30 0.00 0.00
April 155.30 38.38 48.68 0.38 48.31 0.00 0.00
May 222.78 11.01 56.41 3.47 52.93 0.00 0.00
June 266.09 3.33 60.55 5.62 54.93 0.00 0.00
July 275.71 7.18 60.97 4.00 56.96 0.00 0.00
August 234.52 3.21 53.28 0.76 52.52 0.00 0.00
September 225.47 10.32 47.03 0.01 47.02 0.00 0.00
October 165.87 14.67 39.40 0.00 39.40 0.00 0.00
November 119.12 47.38 34.26 0.00 34.26 0.00 0.00
December 75.57 90.08 30.34 0.00 30.34 0.00 0.00
               
Annual Sum or Average 168.49 40.56 45.14 1.19 43.95 0.00 0.00
Minimum of Months 68.70 3.21 30.34 0.00 30.34 0.00 0.00
Maximum of Months 275.71 108.49 60.97 5.62 56.96 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 83.83 59.29 35.17 16.90 18.27 0.00 0.00
February 105.82 46.33 40.44 18.70 21.75 0.00 0.00
March 127.60 35.81 49.09 23.02 26.06 0.00 0.00
April 165.27 19.58 53.40 23.69 29.71 0.00 0.00
May 181.54 4.67 50.56 20.02 30.54 0.00 0.00
June 196.46 1.11 49.92 19.07 30.85 0.00 0.00
July 207.94 2.53 51.38 18.47 32.91 0.00 0.00
August 182.98 1.20 46.93 15.60 31.33 0.00 0.00
September 182.59 4.48 45.23 16.26 28.97 0.00 0.00
October 149.94 7.68 41.62 17.84 23.78 0.00 0.00
November 106.02 24.19 33.95 13.56 20.38 0.00 0.00
December 69.87 49.37 27.58 9.86 17.71 0.00 0.00
               
Annual Sum or Average 146.82 21.25 43.78 17.74 26.04 0.00 0.00
Minimum of Months 69.87 1.11 27.58 9.86 17.71 0.00 0.00
Maximum of Months 207.94 59.29 53.40 23.69 32.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 63.03 43.55 26.18 12.68 13.50 0.00 0.00
February 79.40 34.00 30.10 14.02 16.08 0.00 0.00
March 95.39 26.43 36.54 17.27 19.27 0.00 0.00
April 123.31 14.76 39.76 17.77 21.99 0.00 0.00
May 134.88 3.74 37.60 15.02 22.58 0.00 0.00
June 146.32 0.99 37.10 14.30 22.80 0.00 0.00
July 154.95 2.03 38.19 13.85 24.33 0.00 0.00
August 136.62 0.98 34.85 11.70 23.15 0.00 0.00
September 136.23 3.48 33.60 12.20 21.41 0.00 0.00
October 111.83 5.74 30.95 13.38 17.57 0.00 0.00
November 79.02 18.15 25.22 10.17 15.05 0.00 0.00
December 52.22 36.17 20.48 7.40 13.08 0.00 0.00
               
Annual Sum or Average 109.55 15.76 32.55 13.30 19.25 0.00 0.00
Minimum of Months 52.22 0.98 20.48 7.40 13.08 0.00 0.00
Maximum of Months 154.95 43.55 39.76 17.77 24.33 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 340.52 154.23 140.33 86.22 54.11 0.00 0.00
February 343.50 126.75 135.63 75.36 60.28 0.00 0.00
March 299.65 99.72 120.76 54.97 65.79 0.00 0.00
April 297.29 56.07 97.83 30.63 67.20 0.00 0.00
May 305.96 15.24 82.27 16.66 65.61 0.00 0.00
June 337.03 4.14 79.15 14.47 64.68 0.00 0.00
July 367.98 7.88 83.42 14.59 68.83 0.00 0.00
August 356.95 4.63 87.43 17.63 69.81 0.00 0.00
September 410.11 13.92 101.42 30.81 70.61 0.00 0.00
October 410.66 24.92 122.36 57.26 65.10 0.00 0.00
November 364.48 68.13 126.25 66.20 60.05 0.00 0.00
December 327.51 131.50 130.05 75.71 54.33 0.00 0.00
               
Annual Sum or Average 346.77 58.63 108.77 44.90 63.88 0.00 0.00
Minimum of Months 297.29 4.14 79.15 14.47 54.11 0.00 0.00
Maximum of Months 410.66 154.23 140.33 86.22 70.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 209.05 142.96 87.23 47.57 39.66 0.00 0.00
February 251.24 120.23 96.75 50.42 46.33 0.00 0.00
March 269.31 98.67 104.75 49.94 54.82 0.00 0.00
April 313.91 53.55 102.53 44.96 57.57 0.00 0.00
May 325.29 13.46 87.21 29.57 57.64 0.00 0.00
June 330.76 2.57 73.80 17.19 56.61 0.00 0.00
July 374.16 5.58 83.00 22.26 60.74 0.00 0.00
August 362.01 3.29 87.53 26.62 60.90 0.00 0.00
September 358.91 9.91 82.99 25.89 57.10 0.00 0.00
October 327.51 18.97 91.56 40.50 51.06 0.00 0.00
November 257.76 61.94 84.00 38.97 45.03 0.00 0.00
December 221.83 121.14 87.57 47.56 40.01 0.00 0.00
               
Annual Sum or Average 300.38 54.06 89.05 36.73 52.32 0.00 0.00
Minimum of Months 209.05 2.57 73.80 17.19 39.66 0.00 0.00
Maximum of Months 374.16 142.96 104.75 50.42 60.90 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 163.70 63.72 63.31 40.86 22.45 0.00 0.00
February 157.82 52.31 58.50 34.07 24.43 0.00 0.00
March 126.08 41.55 46.64 20.95 25.69 0.00 0.00
April 110.53 20.37 32.10 7.14 24.96 0.00 0.00
May 114.30 4.34 24.64 0.91 23.73 0.00 0.00
June 129.41 0.74 23.17 0.09 23.08 0.00 0.00
July 142.50 1.56 24.94 0.41 24.53 0.00 0.00
August 146.16 0.71 29.02 3.29 25.73 0.00 0.00
September 176.04 3.17 37.50 10.34 27.16 0.00 0.00
October 186.30 6.53 50.63 24.37 26.26 0.00 0.00
November 172.39 26.78 56.00 31.13 24.87 0.00 0.00
December 162.82 54.09 60.76 37.95 22.80 0.00 0.00
               
Annual Sum or Average 148.95 22.86 42.19 17.55 24.64 0.00 0.00
Minimum of Months 110.53 0.71 23.17 0.09 22.45 0.00 0.00
Maximum of Months 186.30 63.72 63.31 40.86 27.16 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 263.41 98.05 101.29 65.37 35.92 0.00 0.00
February 254.47 79.61 93.60 54.52 39.08 0.00 0.00
March 204.37 62.09 74.62 33.52 41.10 0.00 0.00
April 180.67 28.21 51.36 11.43 39.93 0.00 0.00
May 189.26 5.32 39.42 1.46 37.96 0.00 0.00
June 213.53 0.78 37.07 0.14 36.93 0.00 0.00
July 234.51 1.89 39.90 0.65 39.24 0.00 0.00
August 240.61 0.63 46.43 5.27 41.16 0.00 0.00
September 287.16 3.67 60.00 16.55 43.45 0.00 0.00
October 303.20 8.32 81.01 39.00 42.01 0.00 0.00
November 279.19 39.73 89.59 49.80 39.79 0.00 0.00
December 262.44 82.72 97.21 60.73 36.49 0.00 0.00
               
Annual Sum or Average 242.67 34.06 67.50 28.08 39.42 0.00 0.00
Minimum of Months 180.67 0.63 37.07 0.14 35.92 0.00 0.00
Maximum of Months 303.20 98.05 101.29 65.37 43.45 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 95.80 35.94 37.98 24.52 13.47 0.00 0.00
February 92.28 29.30 35.10 20.44 14.66 0.00 0.00
March 73.60 22.99 27.98 12.57 15.41 0.00 0.00
April 63.54 11.32 19.26 4.29 14.97 0.00 0.00
May 64.32 2.42 14.78 0.55 14.24 0.00 0.00
June 71.86 0.46 13.90 0.05 13.85 0.00 0.00
July 79.22 1.01 14.96 0.25 14.72 0.00 0.00
August 81.63 0.45 17.41 1.98 15.44 0.00 0.00
September 99.05 2.07 22.50 6.21 16.29 0.00 0.00
October 106.00 4.17 30.38 14.62 15.75 0.00 0.00
November 99.72 15.08 33.60 18.68 14.92 0.00 0.00
December 95.06 30.42 36.45 22.77 13.68 0.00 0.00
               
Annual Sum or Average 85.13 12.90 25.31 10.53 14.78 0.00 0.00
Minimum of Months 63.54 0.45 13.90 0.05 13.47 0.00 0.00
Maximum of Months 106.00 35.94 37.98 24.52 16.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 161.68 120.94 69.62 33.81 35.81 0.00 0.00
February 199.93 98.31 80.05 37.39 42.66 0.00 0.00
March 237.86 79.06 97.19 46.05 51.14 0.00 0.00
April 314.38 46.28 105.75 47.39 58.37 0.00 0.00
May 348.49 13.50 99.96 40.04 59.92 0.00 0.00
June 384.98 4.09 98.62 38.14 60.48 0.00 0.00
July 411.45 6.86 101.52 36.95 64.57 0.00 0.00
August 362.92 3.90 92.62 31.20 61.42 0.00 0.00
September 364.20 10.64 89.32 32.52 56.79 0.00 0.00
October 296.76 16.94 82.31 35.69 46.62 0.00 0.00
November 205.28 51.94 67.05 27.13 39.92 0.00 0.00
December 134.50 101.36 54.42 19.73 34.69 0.00 0.00
               
Annual Sum or Average 285.55 45.92 86.55 35.48 51.07 0.00 0.00
Minimum of Months 134.50 3.90 54.42 19.73 34.69 0.00 0.00
Maximum of Months 411.45 120.94 105.75 47.39 64.57 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 32.36 66.79 15.34 0.00 15.34 0.00 0.00
February 47.52 53.66 18.16 0.00 18.16 0.00 0.00
March 55.30 43.39 21.65 0.00 21.65 0.00 0.00
April 83.23 21.12 24.34 0.19 24.15 0.00 0.00
May 122.52 5.33 28.20 1.74 26.47 0.00 0.00
June 149.18 1.26 30.28 2.81 27.46 0.00 0.00
July 157.54 2.41 30.48 2.00 28.48 0.00 0.00
August 136.00 1.10 26.63 0.38 26.26 0.00 0.00
September 131.05 4.08 23.50 0.00 23.50 0.00 0.00
October 95.40 6.61 19.70 0.00 19.70 0.00 0.00
November 63.89 27.39 17.13 0.00 17.13 0.00 0.00
December 37.47 54.95 15.17 0.00 15.17 0.00 0.00
               
Annual Sum or Average 92.84 23.88 22.57 0.60 21.97 0.00 0.00
Minimum of Months 32.36 1.10 15.17 0.00 15.17 0.00 0.00
Maximum of Months 157.54 66.79 30.48 2.81 28.48 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 42.25 97.21 20.45 0.00 20.45 0.00 0.00
February 62.65 78.14 24.21 0.00 24.21 0.00 0.00
March 74.26 62.65 28.87 0.00 28.87 0.00 0.00
April 114.10 28.61 32.42 0.23 32.19 0.00 0.00
May 171.40 6.48 37.60 2.32 35.29 0.00 0.00
June 210.18 1.27 40.37 3.75 36.62 0.00 0.00
July 221.94 2.52 40.64 2.67 37.98 0.00 0.00
August 191.58 1.07 35.51 0.50 35.01 0.00 0.00
September 183.92 4.59 31.33 0.00 31.33 0.00 0.00
October 132.70 8.30 26.27 0.00 26.27 0.00 0.00
November 86.50 39.28 22.84 0.00 22.84 0.00 0.00
December 49.57 80.23 20.23 0.00 20.23 0.00 0.00
               
Annual Sum or Average 128.74 34.01 30.09 0.79 29.30 0.00 0.00
Minimum of Months 42.25 1.07 20.23 0.00 20.23 0.00 0.00
Maximum of Months 221.94 97.21 40.64 3.75 37.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 40.99 95.62 20.45 0.00 20.45 0.00 0.00
February 60.59 77.29 24.21 0.00 24.21 0.00 0.00
March 71.00 62.68 28.87 0.00 28.87 0.00 0.00
April 107.75 30.75 32.18 0.12 32.06 0.00 0.00
May 160.48 8.19 37.60 2.32 35.29 0.00 0.00
June 196.48 1.95 40.37 3.75 36.62 0.00 0.00
July 208.37 3.50 40.64 2.67 37.97 0.00 0.00
August 178.63 1.82 35.45 0.48 34.97 0.00 0.00
September 172.80 6.08 31.33 0.00 31.33 0.00 0.00
October 124.43 10.08 26.27 0.00 26.27 0.00 0.00
November 81.88 39.92 22.84 0.00 22.84 0.00 0.00
December 47.53 79.16 20.23 0.00 20.23 0.00 0.00
               
Annual Sum or Average 121.20 34.57 30.07 0.78 29.28 0.00 0.00
Minimum of Months 40.99 1.82 20.23 0.00 20.23 0.00 0.00
Maximum of Months 208.37 95.62 40.64 3.75 37.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 20.52 49.75 10.11 0.00 10.11 0.00 0.00
February 30.64 40.06 11.96 0.00 11.96 0.00 0.00
March 36.30 32.22 14.27 0.00 14.27 0.00 0.00
April 55.52 15.04 15.87 0.04 15.83 0.00 0.00
May 82.66 3.52 18.13 0.87 17.26 0.00 0.00
June 102.82 0.73 19.81 1.77 18.04 0.00 0.00
July 108.10 1.39 19.80 1.16 18.64 0.00 0.00
August 93.23 0.66 17.29 0.15 17.14 0.00 0.00
September 90.26 2.56 15.48 0.00 15.48 0.00 0.00
October 64.82 4.59 12.98 0.00 12.98 0.00 0.00
November 42.20 20.38 11.28 0.00 11.28 0.00 0.00
December 24.04 41.14 9.99 0.00 9.99 0.00 0.00
               
Annual Sum or Average 62.75 17.57 14.76 0.33 14.43 0.00 0.00
Minimum of Months 20.52 0.66 9.99 0.00 9.99 0.00 0.00
Maximum of Months 108.10 49.75 19.81 1.77 18.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 238.30 186.84 105.51 50.71 54.80 0.00 0.00
February 296.69 150.94 121.33 56.09 65.24 0.00 0.00
March 355.31 121.34 147.26 69.07 78.19 0.00 0.00
April 468.58 72.39 160.21 71.08 89.13 0.00 0.00
May 515.82 21.80 151.69 60.06 91.62 0.00 0.00
June 564.04 6.97 149.77 57.21 92.56 0.00 0.00
July 602.11 12.53 154.15 55.42 98.73 0.00 0.00
August 529.78 7.06 140.79 46.80 93.98 0.00 0.00
September 531.13 18.49 135.70 48.79 86.91 0.00 0.00
October 434.16 29.16 124.87 53.53 71.34 0.00 0.00
November 301.58 79.45 101.84 40.69 61.14 0.00 0.00
December 196.74 157.02 82.74 29.59 53.14 0.00 0.00
               
Annual Sum or Average 420.02 71.65 131.34 53.22 78.12 0.00 0.00
Minimum of Months 196.74 6.97 82.74 29.59 53.14 0.00 0.00
Maximum of Months 602.11 186.84 160.21 71.08 98.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 489.40 316.26 202.46 118.85 83.61 0.00 0.00
February 529.50 263.74 207.63 112.47 95.16 0.00 0.00
March 493.46 214.03 197.40 89.74 107.67 0.00 0.00
April 510.66 122.55 170.73 60.46 110.27 0.00 0.00
May 518.60 41.64 143.11 34.15 108.96 0.00 0.00
June 537.61 12.60 126.48 19.94 106.54 0.00 0.00
July 606.92 20.86 139.30 25.42 113.88 0.00 0.00
August 594.09 14.02 149.88 34.15 115.73 0.00 0.00
September 648.45 32.04 159.70 46.18 113.52 0.00 0.00
October 634.41 56.50 189.71 85.45 104.26 0.00 0.00
November 548.41 147.13 189.02 94.68 94.34 0.00 0.00
December 507.15 266.77 203.29 118.30 84.99 0.00 0.00
               
Annual Sum or Average 551.63 125.06 173.07 69.79 103.28 0.00 0.00
Minimum of Months 489.40 12.60 126.48 19.94 83.61 0.00 0.00
Maximum of Months 648.45 316.26 207.63 118.85 115.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 60.60 43.82 26.38 12.68 13.70 0.00 0.00
February 75.34 35.20 30.33 14.02 16.31 0.00 0.00
March 89.97 28.09 36.81 17.27 19.55 0.00 0.00
April 118.40 16.21 40.05 17.77 22.28 0.00 0.00
May 130.95 4.40 37.92 15.02 22.91 0.00 0.00
June 143.58 1.29 37.44 14.30 23.14 0.00 0.00
July 152.77 2.45 38.54 13.85 24.68 0.00 0.00
August 135.28 1.23 35.20 11.70 23.50 0.00 0.00
September 135.24 3.80 33.93 12.20 21.73 0.00 0.00
October 110.72 5.91 31.22 13.38 17.83 0.00 0.00
November 77.10 18.14 25.46 10.17 15.29 0.00 0.00
December 50.45 36.42 20.68 7.40 13.29 0.00 0.00
               
Annual Sum or Average 106.83 16.33 32.84 13.30 19.53 0.00 0.00
Minimum of Months 50.45 1.23 20.68 7.40 13.29 0.00 0.00
Maximum of Months 152.77 43.82 40.05 17.77 24.68 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 33.16 110.18 19.09 0.00 19.09 0.00 0.00
February 51.41 90.32 22.62 0.00 22.62 0.00 0.00
March 61.04 74.28 27.00 0.00 27.00 0.00 0.00
April 94.88 39.09 30.09 0.08 30.01 0.00 0.00
May 138.15 12.27 33.60 1.33 32.27 0.00 0.00
June 168.59 3.57 35.85 2.54 33.31 0.00 0.00
July 179.35 6.04 36.19 1.64 34.56 0.00 0.00
August 154.43 4.02 32.56 0.28 32.28 0.00 0.00
September 150.19 9.53 29.15 0.00 29.15 0.00 0.00
October 105.76 15.85 24.48 0.00 24.48 0.00 0.00
November 68.19 48.00 21.24 0.00 21.24 0.00 0.00
December 38.32 92.60 18.83 0.00 18.83 0.00 0.00
               
Annual Sum or Average 103.87 41.94 27.58 0.49 27.09 0.00 0.00
Minimum of Months 33.16 3.57 18.83 0.00 18.83 0.00 0.00
Maximum of Months 179.35 110.18 36.19 2.54 34.56 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 X-RAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 LOCKER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 33.36 100.31 20.45 0.00 20.45 0.00 0.00
February 51.25 79.93 24.21 0.00 24.21 0.00 0.00
March 60.87 63.92 28.87 0.00 28.87 0.00 0.00
April 94.70 28.42 32.45 0.25 32.20 0.00 0.00
May 144.96 6.56 37.60 2.32 35.29 0.00 0.00
June 177.01 1.27 40.37 3.75 36.62 0.00 0.00
July 186.35 3.11 40.64 2.67 37.98 0.00 0.00
August 159.12 1.61 35.52 0.50 35.01 0.00 0.00
September 151.61 5.40 31.34 0.00 31.34 0.00 0.00
October 107.95 9.18 26.27 0.00 26.27 0.00 0.00
November 70.92 38.87 22.84 0.00 22.84 0.00 0.00
December 39.22 82.69 20.23 0.00 20.23 0.00 0.00
               
Annual Sum or Average 106.71 34.92 30.10 0.80 29.30 0.00 0.00
Minimum of Months 33.36 1.27 20.23 0.00 20.23 0.00 0.00
Maximum of Months 186.35 100.31 40.64 3.75 37.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 32.84 54.81 15.34 0.00 15.34 0.00 0.00
February 49.08 41.10 18.16 0.00 18.16 0.00 0.00
March 57.46 30.70 21.65 0.00 21.65 0.00 0.00
April 85.81 8.48 24.34 0.19 24.15 0.00 0.00
May 131.54 1.10 28.20 1.74 26.47 0.00 0.00
June 157.14 0.03 30.28 2.81 27.46 0.00 0.00
July 162.27 0.27 30.48 2.00 28.48 0.00 0.00
August 144.93 0.01 26.64 0.38 26.26 0.00 0.00
September 136.25 0.22 23.51 0.00 23.50 0.00 0.00
October 103.57 1.21 19.70 0.00 19.70 0.00 0.00
November 69.98 17.60 17.13 0.00 17.13 0.00 0.00
December 39.07 43.72 15.17 0.00 15.17 0.00 0.00
               
Annual Sum or Average 97.73 16.51 22.57 0.60 21.98 0.00 0.00
Minimum of Months 32.84 0.01 15.17 0.00 15.17 0.00 0.00
Maximum of Months 162.27 54.81 30.48 2.81 28.48 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 143.49 142.64 69.79 33.81 35.98 0.00 0.00
February 177.90 116.05 80.25 37.39 42.85 0.00 0.00
March 214.68 92.14 97.42 46.05 51.37 0.00 0.00
April 288.08 53.85 105.99 47.39 58.60 0.00 0.00
May 315.47 19.40 100.24 40.04 60.20 0.00 0.00
June 344.73 6.41 98.92 38.14 60.78 0.00 0.00
July 372.67 10.72 101.81 36.95 64.86 0.00 0.00
August 323.48 7.19 92.92 31.20 61.72 0.00 0.00
September 325.32 14.36 89.60 32.52 57.08 0.00 0.00
October 266.30 23.58 82.52 35.69 46.84 0.00 0.00
November 181.50 61.48 67.26 27.13 40.13 0.00 0.00
December 115.36 121.51 54.60 19.73 34.87 0.00 0.00
               
Annual Sum or Average 256.07 55.52 86.79 35.48 51.31 0.00 0.00
Minimum of Months 115.36 6.41 54.60 19.73 34.87 0.00 0.00
Maximum of Months 372.67 142.64 105.99 47.39 64.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 119.54 331.12 70.58 0.00 70.58 0.00 0.00
February 182.83 263.54 83.56 0.00 83.56 0.00 0.00
March 215.26 212.52 99.67 0.00 99.67 0.00 0.00
April 332.30 95.23 111.52 0.60 110.92 0.00 0.00
May 505.18 21.31 128.80 7.44 121.36 0.00 0.00
June 617.22 4.08 138.52 12.48 126.04 0.00 0.00
July 648.01 10.46 139.37 8.78 130.60 0.00 0.00
August 557.49 4.97 122.07 1.57 120.50 0.00 0.00
September 531.58 17.88 108.11 0.01 108.10 0.00 0.00
October 381.20 29.77 90.61 0.00 90.61 0.00 0.00
November 251.89 127.50 78.79 0.00 78.79 0.00 0.00
December 139.99 273.82 69.80 0.00 69.80 0.00 0.00
               
Annual Sum or Average 374.45 115.41 103.55 2.59 100.96 0.00 0.00
Minimum of Months 119.54 4.08 69.80 0.00 69.80 0.00 0.00
Maximum of Months 648.01 331.12 139.37 12.48 130.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1072.04 363.87 445.73 276.82 168.91 0.00 0.00
February 1068.90 277.97 426.78 239.47 187.30 0.00 0.00
March 916.54 192.55 371.78 168.82 202.97 0.00 0.00
April 900.06 62.26 292.65 87.24 205.40 0.00 0.00
May 985.68 6.61 242.57 42.99 199.58 0.00 0.00
June 1089.39 0.13 232.54 36.27 196.27 0.00 0.00
July 1173.13 1.64 245.89 37.06 208.82 0.00 0.00
August 1168.08 0.59 262.04 48.98 213.06 0.00 0.00
September 1314.55 1.77 309.74 92.53 217.21 0.00 0.00
October 1332.66 10.94 381.78 179.68 202.10 0.00 0.00
November 1179.51 118.92 399.57 212.17 187.41 0.00 0.00
December 1041.43 296.65 416.21 246.20 170.01 0.00 0.00
               
Annual Sum or Average 1103.59 110.51 335.15 138.54 196.61 0.00 0.00
Minimum of Months 900.06 0.13 232.54 36.27 168.91 0.00 0.00
Maximum of Months 1332.66 363.87 445.73 276.82 217.21 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 801.74 391.61 342.30 206.19 136.11 0.00 0.00
February 841.03 321.94 341.14 188.08 153.06 0.00 0.00
March 760.91 253.13 314.53 144.03 170.50 0.00 0.00
April 769.05 125.56 264.16 91.59 172.57 0.00 0.00
May 790.83 26.73 219.87 50.05 169.83 0.00 0.00
June 829.16 4.16 195.28 28.79 166.49 0.00 0.00
July 925.52 12.00 214.78 37.23 177.55 0.00 0.00
August 926.56 5.68 232.72 51.62 181.10 0.00 0.00
September 1011.27 21.87 252.36 72.96 179.40 0.00 0.00
October 1021.46 40.53 307.75 141.19 166.56 0.00 0.00
November 898.24 156.74 313.83 161.17 152.65 0.00 0.00
December 816.95 330.61 334.50 196.59 137.91 0.00 0.00
               
Annual Sum or Average 866.15 140.09 277.48 113.80 163.68 0.00 0.00
Minimum of Months 760.91 4.16 195.28 28.79 136.11 0.00 0.00
Maximum of Months 1021.46 391.61 342.30 206.19 181.10 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 431.49 211.59 179.90 109.22 70.67 0.00 0.00
February 449.95 173.39 178.62 99.20 79.43 0.00 0.00
March 399.91 135.98 162.42 74.18 88.24 0.00 0.00
April 396.41 69.61 133.90 44.78 89.11 0.00 0.00
May 404.71 16.48 110.83 23.31 87.52 0.00 0.00
June 425.47 3.18 98.94 13.35 85.59 0.00 0.00
July 473.69 8.17 108.47 17.19 91.27 0.00 0.00
August 476.73 4.09 118.18 24.83 93.34 0.00 0.00
September 527.99 14.11 130.75 37.66 93.09 0.00 0.00
October 536.55 25.12 160.74 74.19 86.55 0.00 0.00
November 478.04 87.18 164.85 85.50 79.35 0.00 0.00
December 439.92 176.93 177.24 105.41 71.82 0.00 0.00
               
Annual Sum or Average 453.39 76.73 143.58 58.89 84.69 0.00 0.00
Minimum of Months 396.41 3.18 98.94 13.35 70.67 0.00 0.00
Maximum of Months 536.55 211.59 179.90 109.22 93.34 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 232.62 158.96 105.51 50.71 54.80 0.00 0.00
February 287.35 122.88 121.33 56.09 65.24 0.00 0.00
March 342.15 92.44 147.26 69.07 78.19 0.00 0.00
April 453.37 44.46 160.21 71.08 89.13 0.00 0.00
May 508.52 7.82 151.69 60.06 91.62 0.00 0.00
June 559.26 1.30 149.77 57.21 92.56 0.00 0.00
July 593.81 4.27 154.15 55.42 98.73 0.00 0.00
August 529.32 1.64 140.79 46.80 93.98 0.00 0.00
September 523.28 6.73 135.70 48.79 86.91 0.00 0.00
October 431.78 11.98 124.87 53.53 71.34 0.00 0.00
November 301.82 57.02 101.84 40.69 61.14 0.00 0.00
December 191.82 130.67 82.74 29.59 53.14 0.00 0.00
               
Annual Sum or Average 413.45 53.06 131.34 53.22 78.12 0.00 0.00
Minimum of Months 191.82 1.30 82.74 29.59 53.14 0.00 0.00
Maximum of Months 593.81 158.96 160.21 71.08 98.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: NE STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 90.40 156.44 50.18 4.23 45.96 0.00 0.00
February 134.23 123.50 59.10 4.67 54.43 0.00 0.00
March 156.42 96.33 70.70 5.76 64.94 0.00 0.00
April 233.16 53.98 79.03 6.43 72.60 0.00 0.00
May 325.08 18.00 88.75 9.69 79.06 0.00 0.00
June 383.85 6.43 94.18 12.35 81.83 0.00 0.00
July 403.04 12.19 95.11 10.02 85.09 0.00 0.00
August 344.20 6.45 83.62 4.92 78.70 0.00 0.00
September 327.42 17.73 74.75 4.07 70.68 0.00 0.00
October 239.47 25.29 63.56 4.46 59.10 0.00 0.00
November 164.65 68.15 54.71 3.39 51.32 0.00 0.00
December 99.86 130.78 47.84 2.47 45.37 0.00 0.00
               
Annual Sum or Average 242.31 59.33 71.86 6.04 65.81 0.00 0.00
Minimum of Months 90.40 6.43 47.84 2.47 45.37 0.00 0.00
Maximum of Months 403.04 156.44 95.11 12.35 85.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: NW ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: NW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 75.99 157.88 40.90 0.00 40.90 0.00 0.00
February 111.86 126.90 48.41 0.00 48.41 0.00 0.00
March 128.70 104.34 57.74 0.00 57.74 0.00 0.00
April 188.03 61.21 64.91 0.50 64.41 0.00 0.00
May 272.46 24.18 75.21 4.63 70.58 0.00 0.00
June 325.67 8.55 80.74 7.50 73.24 0.00 0.00
July 343.11 15.54 81.29 5.34 75.95 0.00 0.00
August 288.91 9.18 71.04 1.01 70.03 0.00 0.00
September 276.57 20.28 62.71 0.01 62.70 0.00 0.00
October 199.48 30.03 52.53 0.00 52.53 0.00 0.00
November 138.10 71.98 45.68 0.00 45.68 0.00 0.00
December 83.75 132.90 40.46 0.00 40.46 0.00 0.00
               
Annual Sum or Average 203.14 63.31 60.19 1.59 58.60 0.00 0.00
Minimum of Months 75.99 8.55 40.46 0.00 40.46 0.00 0.00
Maximum of Months 343.11 157.88 81.29 7.50 75.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: SW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 47.80 17.91 18.13 11.74 6.39 0.00 0.00
February 45.16 14.65 16.46 9.55 6.91 0.00 0.00
March 36.32 11.99 13.40 6.02 7.37 0.00 0.00
April 29.94 7.19 9.36 2.14 7.22 0.00 0.00
May 27.70 2.51 7.11 0.27 6.84 0.00 0.00
June 29.85 0.74 6.66 0.03 6.64 0.00 0.00
July 32.96 1.41 7.18 0.12 7.06 0.00 0.00
August 34.68 0.86 8.41 0.98 7.42 0.00 0.00
September 43.80 2.06 10.87 3.04 7.83 0.00 0.00
October 48.40 3.73 14.39 6.90 7.49 0.00 0.00
November 47.31 8.49 15.81 8.76 7.05 0.00 0.00
December 47.85 15.03 17.84 11.27 6.57 0.00 0.00
               
Annual Sum or Average 39.28 7.18 12.11 5.05 7.07 0.00 0.00
Minimum of Months 27.70 0.74 6.66 0.03 6.39 0.00 0.00
Maximum of Months 48.40 17.91 18.13 11.74 7.83 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.275047E+09 88603161.56 0.101737E+09 65661223.82 36075611.73 0.00 0.00
February 0.243643E+09 61867722.89 84915699.29 49459508.55 35456190.74 0.00 0.00
March 0.220978E+09 49864155.19 74947388.71 33662616.98 41284771.73 0.00 0.00
April 0.188018E+09 17459296.50 49921288.83 11108213.35 38813075.48 0.00 0.00
May 0.205551E+09 2644974.87 39597774.01 1467330.04 38130443.97 0.00 0.00
June 0.220186E+09 85307.17 36032133.23 140670.24 35891462.98 0.00 0.00
July 0.247316E+09 374610.37 40074932.30 657614.49 39417317.81 0.00 0.00
August 0.254731E+09 38513.96 46636007.53 5290557.83 41345449.69 0.00 0.00
September 0.289564E+09 546372.92 58318190.90 16085710.26 42232480.64 0.00 0.00
October 0.316014E+09 3999604.16 81369349.95 39171335.94 42198014.01 0.00 0.00
November 0.284772E+09 31613095.67 87085456.26 48407152.59 38678303.67 0.00 0.00
December 0.274996E+09 73523138.75 97638493.76 60992629.69 36645864.07 0.00 0.00
               
Annual Sum or Average 0.302082E+10 0.330620E+09 0.798274E+09 0.332105E+09 0.466169E+09 0.00 0.00
Minimum of Months 0.188018E+09 38513.96 36032133.23 140670.24 35456190.74 0.00 0.00
Maximum of Months 0.316014E+09 88603161.56 0.101737E+09 65661223.82 42232480.64 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.892302E+09 0.476855E+09 0.351052E+09 0.222010E+09 0.129041E+09 0.00 0.00
February 0.788548E+09 0.354761E+09 0.296567E+09 0.168856E+09 0.127710E+09 0.00 0.00
March 0.715356E+09 0.317017E+09 0.272453E+09 0.120240E+09 0.152213E+09 0.00 0.00
April 0.588263E+09 0.180561E+09 0.188733E+09 43281373.40 0.145452E+09 0.00 0.00
May 0.560938E+09 72033186.90 0.148655E+09 5869261.93 0.142786E+09 0.00 0.00
June 0.564683E+09 24495657.68 0.134324E+09 562680.98 0.133761E+09 0.00 0.00
July 0.657169E+09 40532444.07 0.149810E+09 2626553.45 0.147183E+09 0.00 0.00
August 0.671183E+09 32050421.23 0.175358E+09 20587735.90 0.154770E+09 0.00 0.00
September 0.831349E+09 54725737.09 0.215692E+09 59342191.00 0.156350E+09 0.00 0.00
October 0.936284E+09 0.102539E+09 0.289058E+09 0.135337E+09 0.153721E+09 0.00 0.00
November 0.873086E+09 0.224169E+09 0.302865E+09 0.164091E+09 0.138774E+09 0.00 0.00
December 0.925123E+09 0.401808E+09 0.355363E+09 0.222495E+09 0.132868E+09 0.00 0.00
               
Annual Sum or Average 0.900428E+10 0.228155E+10 0.287993E+10 0.116530E+10 0.171463E+10 0.00 0.00
Minimum of Months 0.560938E+09 24495657.68 0.134324E+09 562680.98 0.127710E+09 0.00 0.00
Maximum of Months 0.936284E+09 0.476855E+09 0.355363E+09 0.222495E+09 0.156350E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 CLEAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 39206270.38 0.102278E+09 21186716.46 0.00 21186716.46 0.00 0.00
February 55354467.30 71713102.09 22681496.38 0.00 22681496.38 0.00 0.00
March 73175283.04 61299995.91 29972029.19 0.00 29972029.19 0.00 0.00
April 0.106503E+09 28934321.97 32241609.08 69690.65 32171918.42 0.00 0.00
May 0.155814E+09 7609053.00 37021224.92 1338560.83 35682664.09 0.00 0.00
June 0.181475E+09 1795476.11 38160255.95 2594172.46 35566083.49 0.00 0.00
July 0.196305E+09 3830281.62 39776659.29 1658212.69 38118446.60 0.00 0.00
August 0.169454E+09 2408959.60 35975636.35 275136.91 35700499.44 0.00 0.00
September 0.157378E+09 7399971.39 31267894.68 668.87 31267225.80 0.00 0.00
October 0.115698E+09 13165264.04 27172038.60 0.00 27172038.60 0.00 0.00
November 75136024.98 41603346.99 22804310.29 0.00 22804310.29 0.00 0.00
December 44716318.63 85343852.69 20894937.27 0.00 20894937.27 0.00 0.00
               
Annual Sum or Average 0.137022E+10 0.427381E+09 0.359155E+09 5936442.43 0.353218E+09 0.00 0.00
Minimum of Months 39206270.38 1795476.11 20894937.27 0.00 20894937.27 0.00 0.00
Maximum of Months 0.196305E+09 0.102278E+09 39776659.29 2594172.46 38118446.60 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 IT HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 LOBBY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.439019E+09 0.446507E+09 0.187218E+09 82335982.30 0.104882E+09 0.00 0.00
February 0.547938E+09 0.330237E+09 0.210806E+09 96702861.51 0.114103E+09 0.00 0.00
March 0.751223E+09 0.300203E+09 0.289780E+09 0.133446E+09 0.156334E+09 0.00 0.00
April 0.913193E+09 0.168352E+09 0.308172E+09 0.143523E+09 0.164650E+09 0.00 0.00
May 0.990264E+09 62496768.99 0.290536E+09 0.113155E+09 0.177381E+09 0.00 0.00
June 0.920015E+09 18035389.38 0.237956E+09 68079193.73 0.169877E+09 0.00 0.00
July 0.108393E+10 31529555.81 0.275422E+09 86842515.09 0.188579E+09 0.00 0.00
August 0.100141E+10 20059617.11 0.274394E+09 90838446.41 0.183556E+09 0.00 0.00
September 0.892044E+09 44009457.28 0.226344E+09 68023261.12 0.158321E+09 0.00 0.00
October 0.792017E+09 80609661.45 0.233458E+09 92415543.91 0.141043E+09 0.00 0.00
November 0.562965E+09 0.197690E+09 0.186830E+09 70144857.63 0.116685E+09 0.00 0.00
December 0.484819E+09 0.374834E+09 0.194017E+09 88540459.63 0.105476E+09 0.00 0.00
               
Annual Sum or Average 0.937884E+10 0.207456E+10 0.291493E+10 0.113405E+10 0.178089E+10 0.00 0.00
Minimum of Months 0.439019E+09 18035389.38 0.186830E+09 68023261.12 0.104882E+09 0.00 0.00
Maximum of Months 0.108393E+10 0.446507E+09 0.308172E+09 0.143523E+09 0.188579E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 85905198.82 0.300272E+09 49707676.96 0.00 49707676.96 0.00 0.00
February 0.122820E+09 0.218270E+09 53228990.85 0.00 53228990.85 0.00 0.00
March 0.163902E+09 0.193947E+09 70353786.55 0.00 70353786.55 0.00 0.00
April 0.243715E+09 95912450.98 75170525.03 107914.17 75062610.86 0.00 0.00
May 0.370592E+09 29388310.13 88460121.30 3650250.93 84809870.37 0.00 0.00
June 0.435702E+09 7038159.01 91177827.37 6057548.95 85120278.42 0.00 0.00
July 0.480776E+09 11858466.09 95404587.11 4559196.88 90845390.23 0.00 0.00
August 0.406957E+09 8559667.35 84531831.84 537177.59 83994654.25 0.00 0.00
September 0.383826E+09 20584025.68 73526016.60 6.57 73526010.03 0.00 0.00
October 0.276715E+09 39119507.68 63643997.25 0.00 63643997.25 0.00 0.00
November 0.173627E+09 0.124182E+09 53664111.99 0.00 53664111.99 0.00 0.00
December 0.100517E+09 0.250118E+09 49139999.20 0.00 49139999.20 0.00 0.00
               
Annual Sum or Average 0.324506E+10 0.129925E+10 0.848009E+09 14912095.08 0.833097E+09 0.00 0.00
Minimum of Months 85905198.82 7038159.01 49139999.20 0.00 49139999.20 0.00 0.00
Maximum of Months 0.480776E+09 0.300272E+09 95404587.11 6057548.95 90845390.23 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 MED GAS

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.971737E+09 0.384672E+09 0.344776E+09 0.199238E+09 0.145538E+09 0.00 0.00
February 0.952905E+09 0.276717E+09 0.316592E+09 0.166768E+09 0.149824E+09 0.00 0.00
March 0.103840E+10 0.225108E+09 0.347104E+09 0.159824E+09 0.187280E+09 0.00 0.00
April 0.109901E+10 0.101901E+09 0.307473E+09 0.114335E+09 0.193138E+09 0.00 0.00
May 0.121465E+10 20445436.73 0.282335E+09 83370896.91 0.198964E+09 0.00 0.00
June 0.126462E+10 3262598.67 0.266165E+09 74426706.42 0.191738E+09 0.00 0.00
July 0.138107E+10 9729975.00 0.286585E+09 75533059.63 0.211052E+09 0.00 0.00
August 0.129382E+10 3368553.73 0.281814E+09 73259989.26 0.208554E+09 0.00 0.00
September 0.134518E+10 18241811.97 0.292505E+09 95398768.89 0.197106E+09 0.00 0.00
October 0.130981E+10 35089190.86 0.329963E+09 0.150034E+09 0.179929E+09 0.00 0.00
November 0.106753E+10 0.146403E+09 0.306149E+09 0.149549E+09 0.156600E+09 0.00 0.00
December 0.912633E+09 0.319010E+09 0.306080E+09 0.161617E+09 0.144463E+09 0.00 0.00
               
Annual Sum or Average 0.138514E+11 0.154395E+10 0.366754E+10 0.150335E+10 0.216419E+10 0.00 0.00
Minimum of Months 0.912633E+09 3262598.67 0.266165E+09 73259989.26 0.144463E+09 0.00 0.00
Maximum of Months 0.138107E+10 0.384672E+09 0.347104E+09 0.199238E+09 0.211052E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.590884E+09 0.331711E+09 0.211954E+09 0.101873E+09 0.110080E+09 0.00 0.00
February 0.663808E+09 0.236333E+09 0.220140E+09 0.101773E+09 0.118367E+09 0.00 0.00
March 0.872338E+09 0.194654E+09 0.295814E+09 0.138748E+09 0.157066E+09 0.00 0.00
April 0.107759E+10 89043531.77 0.311445E+09 0.138177E+09 0.173268E+09 0.00 0.00
May 0.123469E+10 17975540.96 0.304709E+09 0.120654E+09 0.184054E+09 0.00 0.00
June 0.128971E+10 2875905.80 0.291150E+09 0.111218E+09 0.179932E+09 0.00 0.00
July 0.140010E+10 8120810.96 0.309653E+09 0.111327E+09 0.198326E+09 0.00 0.00
August 0.124643E+10 2580497.46 0.282813E+09 94018310.38 0.188795E+09 0.00 0.00
September 0.120266E+10 14412309.85 0.263802E+09 94841022.56 0.168961E+09 0.00 0.00
October 0.103622E+10 27837872.67 0.250836E+09 0.107536E+09 0.143300E+09 0.00 0.00
November 0.729120E+09 0.123080E+09 0.197968E+09 79102314.79 0.118865E+09 0.00 0.00
December 0.504714E+09 0.273005E+09 0.166205E+09 59447001.46 0.106758E+09 0.00 0.00
               
Annual Sum or Average 0.118483E+11 0.132163E+10 0.310649E+10 0.125872E+10 0.184777E+10 0.00 0.00
Minimum of Months 0.504714E+09 2580497.46 0.166205E+09 59447001.46 0.106758E+09 0.00 0.00
Maximum of Months 0.140010E+10 0.331711E+09 0.311445E+09 0.138748E+09 0.198326E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 PACU

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.121635E+09 0.232120E+09 53537799.79 0.00 53537799.79 0.00 0.00
February 0.165084E+09 0.160300E+09 57258975.61 0.00 57258975.61 0.00 0.00
March 0.219666E+09 0.133388E+09 75619585.01 0.00 75619585.01 0.00 0.00
April 0.318821E+09 46827005.24 80985749.64 129321.76 80856427.87 0.00 0.00
May 0.490072E+09 7806263.34 94268664.41 3641551.36 90627113.05 0.00 0.00
June 0.575107E+09 455787.60 98941931.84 7610744.36 91331187.48 0.00 0.00
July 0.619713E+09 1336728.88 0.102447E+09 4979674.55 97467446.13 0.00 0.00
August 0.545734E+09 294756.09 90948967.39 612885.93 90336081.46 0.00 0.00
September 0.503657E+09 1939101.43 79264096.74 548.81 79263547.92 0.00 0.00
October 0.381307E+09 9106952.28 68711044.08 0.00 68711044.08 0.00 0.00
November 0.246709E+09 80771284.39 57841607.50 0.00 57841607.50 0.00 0.00
December 0.145001E+09 0.188269E+09 52947434.22 0.00 52947434.22 0.00 0.00
               
Annual Sum or Average 0.433251E+10 0.862616E+09 0.912773E+09 16974726.77 0.895798E+09 0.00 0.00
Minimum of Months 0.121635E+09 294756.09 52947434.22 0.00 52947434.22 0.00 0.00
Maximum of Months 0.619713E+09 0.232120E+09 0.102447E+09 7610744.36 97467446.13 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.281114E+09 0.175095E+09 0.107760E+09 65598671.76 42161496.37 0.00 0.00
February 0.262537E+09 0.127357E+09 95086078.67 52795953.87 42290124.80 0.00 0.00
March 0.244099E+09 0.111447E+09 88866022.68 38130217.01 50735805.68 0.00 0.00
April 0.213772E+09 53586302.30 62821461.12 14003162.04 48818299.08 0.00 0.00
May 0.223366E+09 13782722.85 50288004.53 2105679.26 48182325.27 0.00 0.00
June 0.240378E+09 2686809.36 45166647.37 210719.42 44955927.95 0.00 0.00
July 0.277620E+09 5148518.83 50608088.10 939284.79 49668803.30 0.00 0.00
August 0.282792E+09 3897491.41 58586836.41 6801179.70 51785656.72 0.00 0.00
September 0.324582E+09 10293988.51 70315072.44 18668341.27 51646731.18 0.00 0.00
October 0.340076E+09 21071190.79 93141565.02 42378918.09 50762646.93 0.00 0.00
November 0.301224E+09 71829210.68 96558123.58 51014584.54 45543539.03 0.00 0.00
December 0.300895E+09 0.145826E+09 0.111622E+09 68691395.59 42930509.60 0.00 0.00
               
Annual Sum or Average 0.329246E+10 0.742021E+09 0.930820E+09 0.361338E+09 0.569482E+09 0.00 0.00
Minimum of Months 0.213772E+09 2686809.36 45166647.37 210719.42 42161496.37 0.00 0.00
Maximum of Months 0.340076E+09 0.175095E+09 0.111622E+09 68691395.59 51785656.72 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.108363E+10 0.373613E+09 0.406947E+09 0.262645E+09 0.144302E+09 0.00 0.00
February 0.960233E+09 0.262035E+09 0.339663E+09 0.197838E+09 0.141825E+09 0.00 0.00
March 0.870791E+09 0.211527E+09 0.299790E+09 0.134650E+09 0.165139E+09 0.00 0.00
April 0.742081E+09 76589636.80 0.199685E+09 44432853.39 0.155252E+09 0.00 0.00
May 0.809991E+09 11803354.81 0.158391E+09 5869320.18 0.152522E+09 0.00 0.00
June 0.870337E+09 478599.98 0.144129E+09 562680.98 0.143566E+09 0.00 0.00
July 0.978294E+09 1867345.46 0.160300E+09 2630457.98 0.157669E+09 0.00 0.00
August 0.100241E+10 327764.96 0.186544E+09 21162231.34 0.165382E+09 0.00 0.00
September 0.113849E+10 3353233.52 0.233273E+09 64342841.03 0.168930E+09 0.00 0.00
October 0.123814E+10 20442204.08 0.325477E+09 0.156685E+09 0.168792E+09 0.00 0.00
November 0.111683E+10 0.136972E+09 0.348342E+09 0.193629E+09 0.154713E+09 0.00 0.00
December 0.108350E+10 0.311422E+09 0.390554E+09 0.243971E+09 0.146583E+09 0.00 0.00
               
Annual Sum or Average 0.118947E+11 0.141043E+10 0.319309E+10 0.132842E+10 0.186468E+10 0.00 0.00
Minimum of Months 0.742081E+09 327764.96 0.144129E+09 562680.98 0.141825E+09 0.00 0.00
Maximum of Months 0.123814E+10 0.373613E+09 0.406947E+09 0.262645E+09 0.168930E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 50707183.10 33871272.81 19204090.60 11246719.39 7957371.20 0.00 0.00
February 48736890.94 23805939.41 17088414.95 9078636.05 8009778.89 0.00 0.00
March 46551261.58 20049440.39 16255035.00 6551197.27 9703837.73 0.00 0.00
April 43019973.89 7752096.30 11563824.63 2195482.40 9368342.23 0.00 0.00
May 50537065.84 1258134.92 9629382.17 327088.49 9302293.69 0.00 0.00
June 56022431.99 81458.01 8749085.10 35772.55 8713312.55 0.00 0.00
July 63654853.28 345222.43 9774193.22 147389.51 9626803.71 0.00 0.00
August 63130006.51 191955.73 10933586.52 1079962.72 9853623.81 0.00 0.00
September 67523066.91 615230.59 12613282.59 2964793.20 9648489.39 0.00 0.00
October 68560088.15 2088049.17 16824306.39 7268740.09 9555566.30 0.00 0.00
November 58227024.47 12526136.06 17370189.31 8834560.97 8535628.34 0.00 0.00
December 57158348.90 27964863.41 20731956.35 12610818.37 8121137.98 0.00 0.00
               
Annual Sum or Average 0.673828E+09 0.130550E+09 0.170737E+09 62341161.02 0.108396E+09 0.00 0.00
Minimum of Months 43019973.89 81458.01 8749085.10 35772.55 7957371.20 0.00 0.00
Maximum of Months 68560088.15 33871272.81 20731956.35 12610818.37 9853623.81 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 SCRUB

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 SOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.643496E+09 0.274961E+09 0.247887E+09 0.151906E+09 95980993.58 0.00 0.00
February 0.612109E+09 0.195505E+09 0.220019E+09 0.123095E+09 96924624.74 0.00 0.00
March 0.618430E+09 0.159899E+09 0.219056E+09 0.100687E+09 0.118370E+09 0.00 0.00
April 0.601436E+09 63587690.86 0.173430E+09 58097076.45 0.115332E+09 0.00 0.00
May 0.663501E+09 10338887.80 0.147976E+09 31222598.18 0.116754E+09 0.00 0.00
June 0.683343E+09 552522.84 0.127519E+09 17211038.05 0.110308E+09 0.00 0.00
July 0.772918E+09 2119461.93 0.144777E+09 23002789.36 0.121774E+09 0.00 0.00
August 0.760902E+09 680450.91 0.157802E+09 33290727.27 0.124511E+09 0.00 0.00
September 0.793260E+09 4492350.73 0.169582E+09 49177235.80 0.120404E+09 0.00 0.00
October 0.814212E+09 19078134.89 0.217959E+09 0.101447E+09 0.116512E+09 0.00 0.00
November 0.695074E+09 0.104662E+09 0.218216E+09 0.114351E+09 0.103866E+09 0.00 0.00
December 0.656086E+09 0.231387E+09 0.241366E+09 0.144120E+09 97245595.38 0.00 0.00
               
Annual Sum or Average 0.831477E+10 0.106726E+10 0.228559E+10 0.947607E+09 0.133798E+10 0.00 0.00
Minimum of Months 0.601436E+09 552522.84 0.127519E+09 17211038.05 95980993.58 0.00 0.00
Maximum of Months 0.814212E+09 0.274961E+09 0.247887E+09 0.151906E+09 0.124511E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.271010E+09 94959573.62 0.101737E+09 65661223.82 36075611.73 0.00 0.00
February 0.237792E+09 68759926.35 84915699.29 49459508.55 35456190.74 0.00 0.00
March 0.210815E+09 59428230.37 74947388.71 33662616.98 41284771.73 0.00 0.00
April 0.172701E+09 27167062.12 49921288.83 11108213.35 38813075.48 0.00 0.00
May 0.177794E+09 5417916.62 39597774.01 1467330.04 38130443.97 0.00 0.00
June 0.189667E+09 738319.64 36032133.23 140670.24 35891462.98 0.00 0.00
July 0.215643E+09 1986713.09 40074932.30 657614.49 39417317.81 0.00 0.00
August 0.223733E+09 633655.76 46636007.53 5290557.83 41345449.69 0.00 0.00
September 0.265159E+09 3921466.03 58318190.90 16085710.26 42232480.64 0.00 0.00
October 0.298349E+09 8703327.82 81369349.95 39171335.94 42198014.01 0.00 0.00
November 0.273904E+09 36548992.59 87085456.26 48407152.59 38678303.67 0.00 0.00
December 0.269839E+09 79509489.33 97638493.76 60992629.69 36645864.07 0.00 0.00
               
Annual Sum or Average 0.280641E+10 0.387775E+09 0.798274E+09 0.332105E+09 0.466169E+09 0.00 0.00
Minimum of Months 0.172701E+09 633655.76 36032133.23 140670.24 35456190.74 0.00 0.00
Maximum of Months 0.298349E+09 94959573.62 0.101737E+09 65661223.82 42232480.64 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.183993E+09 0.290580E+09 82164617.17 0.00 82164617.17 0.00 0.00
February 0.236428E+09 0.207554E+09 87843169.46 0.00 87843169.46 0.00 0.00
March 0.297535E+09 0.185490E+09 0.115983E+09 0.00 0.115983E+09 0.00 0.00
April 0.402537E+09 99491136.78 0.126180E+09 972111.23 0.125207E+09 0.00 0.00
May 0.596694E+09 29495904.50 0.151080E+09 9305278.78 0.141774E+09 0.00 0.00
June 0.689705E+09 8631801.47 0.156951E+09 14575259.50 0.142376E+09 0.00 0.00
July 0.738459E+09 19227100.22 0.163292E+09 10719165.63 0.152573E+09 0.00 0.00
August 0.628151E+09 8593718.39 0.142706E+09 2025153.70 0.140681E+09 0.00 0.00
September 0.584413E+09 26749308.81 0.121906E+09 19309.11 0.121886E+09 0.00 0.00
October 0.444260E+09 39291080.39 0.105523E+09 0.00 0.105523E+09 0.00 0.00
November 0.308761E+09 0.122814E+09 88793121.77 0.00 88793121.77 0.00 0.00
December 0.202409E+09 0.241258E+09 81271101.87 0.00 81271101.87 0.00 0.00
               
Annual Sum or Average 0.531335E+10 0.127918E+10 0.142369E+10 37616277.95 0.138608E+10 0.00 0.00
Minimum of Months 0.183993E+09 8593718.39 81271101.87 0.00 81271101.87 0.00 0.00
Maximum of Months 0.738459E+09 0.290580E+09 0.163292E+09 14575259.50 0.152573E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.224528E+09 0.158804E+09 94201598.82 45276954.40 48924644.41 0.00 0.00
February 0.255989E+09 0.112081E+09 97840158.04 45232496.71 52607661.32 0.00 0.00
March 0.341769E+09 95911024.44 0.131473E+09 61665876.99 69806902.62 0.00 0.00
April 0.428375E+09 50753620.94 0.138420E+09 61412187.93 77007806.66 0.00 0.00
May 0.486227E+09 12518241.16 0.135426E+09 53624157.88 81801915.50 0.00 0.00
June 0.509223E+09 2888482.95 0.129400E+09 49430243.95 79969971.42 0.00 0.00
July 0.556959E+09 6779203.17 0.137623E+09 49478553.76 88144821.92 0.00 0.00
August 0.490090E+09 3204391.13 0.125695E+09 41785915.73 83908892.90 0.00 0.00
September 0.473276E+09 11619653.24 0.117245E+09 42151565.58 75093923.48 0.00 0.00
October 0.401596E+09 20564949.59 0.111483E+09 47793901.96 63688694.58 0.00 0.00
November 0.274799E+09 62687584.96 87985669.60 35156584.35 52829085.26 0.00 0.00
December 0.187132E+09 0.132233E+09 73868734.35 26420889.54 47447844.81 0.00 0.00
               
Annual Sum or Average 0.462996E+10 0.670045E+09 0.138066E+10 0.559429E+09 0.821232E+09 0.00 0.00
Minimum of Months 0.187132E+09 2888482.95 73868734.35 26420889.54 47447844.81 0.00 0.00
Maximum of Months 0.556959E+09 0.158804E+09 0.138420E+09 61665876.99 88144821.92 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.168816E+09 0.116657E+09 70113579.34 33957715.80 36155863.53 0.00 0.00
February 0.192095E+09 82260391.47 72815356.47 33924372.54 38890983.94 0.00 0.00
March 0.255484E+09 70785362.60 97866974.88 46249407.74 51617567.14 0.00 0.00
April 0.319621E+09 38259077.65 0.103053E+09 46059140.94 56993359.33 0.00 0.00
May 0.361253E+09 10013565.85 0.100697E+09 40218118.41 60478879.27 0.00 0.00
June 0.379260E+09 2555035.24 96164093.61 37072682.97 59091410.64 0.00 0.00
July 0.415017E+09 5449181.16 0.102284E+09 37108915.32 65174877.34 0.00 0.00
August 0.365936E+09 2619273.52 93345188.96 31339436.79 62005752.17 0.00 0.00
September 0.353113E+09 9026626.92 87100743.19 31613674.19 55487069.00 0.00 0.00
October 0.299530E+09 15383164.03 82908953.52 35845426.47 47063527.05 0.00 0.00
November 0.204825E+09 47032577.36 65378513.92 26367438.26 39011075.65 0.00 0.00
December 0.139867E+09 96864463.94 54849860.25 19815667.15 35034193.10 0.00 0.00
               
Annual Sum or Average 0.345482E+10 0.496906E+09 0.102658E+10 0.419572E+09 0.607005E+09 0.00 0.00
Minimum of Months 0.139867E+09 2555035.24 54849860.25 19815667.15 35034193.10 0.00 0.00
Maximum of Months 0.415017E+09 0.116657E+09 0.103053E+09 46249407.74 65174877.34 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.912059E+09 0.413087E+09 0.375862E+09 0.230941E+09 0.144920E+09 0.00 0.00
February 0.830994E+09 0.306637E+09 0.328127E+09 0.182303E+09 0.145824E+09 0.00 0.00
March 0.802595E+09 0.267082E+09 0.323447E+09 0.147237E+09 0.176209E+09 0.00 0.00
April 0.770588E+09 0.145331E+09 0.253579E+09 79383780.99 0.174195E+09 0.00 0.00
May 0.819473E+09 40808071.53 0.220363E+09 44620108.54 0.175743E+09 0.00 0.00
June 0.873579E+09 10723111.68 0.205147E+09 37494693.70 0.167652E+09 0.00 0.00
July 0.985604E+09 21111385.76 0.223442E+09 39081758.80 0.184361E+09 0.00 0.00
August 0.956052E+09 12406917.71 0.234179E+09 47211110.30 0.186968E+09 0.00 0.00
September 0.106301E+10 36092297.55 0.262889E+09 79870804.96 0.183018E+09 0.00 0.00
October 0.109991E+10 66751121.47 0.327720E+09 0.153359E+09 0.174361E+09 0.00 0.00
November 0.944721E+09 0.176597E+09 0.327246E+09 0.171589E+09 0.155657E+09 0.00 0.00
December 0.877197E+09 0.352214E+09 0.348317E+09 0.202794E+09 0.145523E+09 0.00 0.00
               
Annual Sum or Average 0.109358E+11 0.184884E+10 0.343032E+10 0.141589E+10 0.201443E+10 0.00 0.00
Minimum of Months 0.770588E+09 10723111.68 0.205147E+09 37494693.70 0.144920E+09 0.00 0.00
Maximum of Months 0.109991E+10 0.413087E+09 0.375862E+09 0.230941E+09 0.186968E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.559920E+09 0.382912E+09 0.233625E+09 0.127413E+09 0.106212E+09 0.00 0.00
February 0.607799E+09 0.290865E+09 0.234057E+09 0.121987E+09 0.112070E+09 0.00 0.00
March 0.721316E+09 0.264278E+09 0.280573E+09 0.133747E+09 0.146826E+09 0.00 0.00
April 0.813643E+09 0.138808E+09 0.265771E+09 0.116543E+09 0.149228E+09 0.00 0.00
May 0.871261E+09 36049467.60 0.233577E+09 79195120.43 0.154382E+09 0.00 0.00
June 0.857317E+09 6662518.48 0.191301E+09 44565137.26 0.146736E+09 0.00 0.00
July 0.100216E+10 14934578.04 0.222310E+09 59634437.97 0.162676E+09 0.00 0.00
August 0.969607E+09 8804135.30 0.234434E+09 71309737.59 0.163124E+09 0.00 0.00
September 0.930284E+09 25690024.21 0.215103E+09 67096960.65 0.148006E+09 0.00 0.00
October 0.877212E+09 50813134.89 0.245244E+09 0.108483E+09 0.136761E+09 0.00 0.00
November 0.668108E+09 0.160551E+09 0.217736E+09 0.101016E+09 0.116720E+09 0.00 0.00
December 0.594149E+09 0.324457E+09 0.234554E+09 0.127398E+09 0.107156E+09 0.00 0.00
               
Annual Sum or Average 0.947278E+10 0.170482E+10 0.280828E+10 0.115839E+10 0.164990E+10 0.00 0.00
Minimum of Months 0.559920E+09 6662518.48 0.191301E+09 44565137.26 0.106212E+09 0.00 0.00
Maximum of Months 0.100216E+10 0.382912E+09 0.280573E+09 0.133747E+09 0.163124E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.438443E+09 0.170668E+09 0.169561E+09 0.109435E+09 60126019.55 0.00 0.00
February 0.381805E+09 0.126551E+09 0.141526E+09 82432514.26 59093651.23 0.00 0.00
March 0.337705E+09 0.111287E+09 0.124912E+09 56104361.63 68807952.89 0.00 0.00
April 0.286490E+09 52794152.69 83202148.06 18513688.91 64688459.14 0.00 0.00
May 0.306145E+09 11627754.05 65996290.02 2445550.07 63550739.94 0.00 0.00
June 0.335443E+09 1910558.83 60053555.38 234450.41 59819104.97 0.00 0.00
July 0.381663E+09 4186387.45 66791553.84 1096024.16 65695529.68 0.00 0.00
August 0.391469E+09 1891170.05 77726679.21 8817596.39 68909082.82 0.00 0.00
September 0.456289E+09 8205054.13 97196984.83 26809517.10 70387467.73 0.00 0.00
October 0.498990E+09 17497361.17 0.135616E+09 65285559.90 70330023.34 0.00 0.00
November 0.446831E+09 69421681.98 0.145142E+09 80678587.65 64463839.45 0.00 0.00
December 0.436109E+09 0.144881E+09 0.162731E+09 0.101654E+09 61076440.12 0.00 0.00
               
Annual Sum or Average 0.469738E+10 0.720922E+09 0.133046E+10 0.553508E+09 0.776948E+09 0.00 0.00
Minimum of Months 0.286490E+09 1891170.05 60053555.38 234450.41 59093651.23 0.00 0.00
Maximum of Months 0.498990E+09 0.170668E+09 0.169561E+09 0.109435E+09 70387467.73 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.705512E+09 0.262624E+09 0.271298E+09 0.175097E+09 96201631.28 0.00 0.00
February 0.615619E+09 0.192593E+09 0.226442E+09 0.131892E+09 94549841.96 0.00 0.00
March 0.547391E+09 0.166309E+09 0.199860E+09 89766978.61 0.110093E+09 0.00 0.00
April 0.468292E+09 73124125.63 0.133123E+09 29621902.26 0.103502E+09 0.00 0.00
May 0.506921E+09 14248439.38 0.105594E+09 3912880.12 0.101681E+09 0.00 0.00
June 0.553475E+09 2021774.23 96085688.60 375120.65 95710567.95 0.00 0.00
July 0.628112E+09 5058962.34 0.106866E+09 1753638.65 0.105113E+09 0.00 0.00
August 0.644444E+09 1676575.86 0.124363E+09 14108154.23 0.110255E+09 0.00 0.00
September 0.744318E+09 9523125.30 0.155515E+09 42895227.35 0.112620E+09 0.00 0.00
October 0.812096E+09 22270944.60 0.216985E+09 0.104457E+09 0.112528E+09 0.00 0.00
November 0.723666E+09 0.102974E+09 0.232228E+09 0.129086E+09 0.103142E+09 0.00 0.00
December 0.702915E+09 0.221560E+09 0.260369E+09 0.162647E+09 97722304.19 0.00 0.00
               
Annual Sum or Average 0.765276E+10 0.107398E+10 0.212873E+10 0.885612E+09 0.124312E+10 0.00 0.00
Minimum of Months 0.468292E+09 1676575.86 96085688.60 375120.65 94549841.96 0.00 0.00
Maximum of Months 0.812096E+09 0.262624E+09 0.271298E+09 0.175097E+09 0.112620E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.256591E+09 96257221.39 0.101737E+09 65661223.82 36075611.73 0.00 0.00
February 0.223237E+09 70885989.26 84915699.29 49459508.55 35456190.74 0.00 0.00
March 0.197126E+09 61581485.37 74947388.71 33662616.98 41284771.73 0.00 0.00
April 0.164708E+09 29333922.36 49921288.83 11108213.35 38813075.48 0.00 0.00
May 0.172286E+09 6493868.35 39597774.01 1467330.04 38130443.97 0.00 0.00
June 0.186269E+09 1180837.09 36032133.23 140670.24 35891462.98 0.00 0.00
July 0.212180E+09 2698055.11 40074932.30 657614.49 39417317.81 0.00 0.00
August 0.218649E+09 1217232.56 46636007.53 5290557.83 41345449.69 0.00 0.00
September 0.256728E+09 5357158.62 58318190.90 16085710.26 42232480.64 0.00 0.00
October 0.283907E+09 11181976.13 81369349.95 39171335.94 42198014.01 0.00 0.00
November 0.258463E+09 39091749.06 87085456.26 48407152.59 38678303.67 0.00 0.00
December 0.254617E+09 81481216.18 97638493.76 60992629.69 36645864.07 0.00 0.00
               
Annual Sum or Average 0.268476E+10 0.406761E+09 0.798274E+09 0.332105E+09 0.466169E+09 0.00 0.00
Minimum of Months 0.164708E+09 1180837.09 36032133.23 140670.24 35456190.74 0.00 0.00
Maximum of Months 0.283907E+09 96257221.39 0.101737E+09 65661223.82 42232480.64 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.433033E+09 0.323934E+09 0.186479E+09 90553908.81 95925464.65 0.00 0.00
February 0.483664E+09 0.237843E+09 0.193659E+09 90464993.43 0.103194E+09 0.00 0.00
March 0.637082E+09 0.211743E+09 0.260306E+09 0.123332E+09 0.136974E+09 0.00 0.00
April 0.814862E+09 0.119952E+09 0.274113E+09 0.122824E+09 0.151288E+09 0.00 0.00
May 0.933389E+09 36156003.95 0.267729E+09 0.107248E+09 0.160481E+09 0.00 0.00
June 0.997866E+09 10599324.97 0.255628E+09 98860487.91 0.156768E+09 0.00 0.00
July 0.110203E+10 18377784.09 0.271906E+09 98957107.52 0.172948E+09 0.00 0.00
August 0.972048E+09 10440796.41 0.248075E+09 83571831.45 0.164504E+09 0.00 0.00
September 0.944018E+09 27580554.47 0.231508E+09 84303131.16 0.147204E+09 0.00 0.00
October 0.794841E+09 45368898.45 0.220450E+09 95587803.92 0.124862E+09 0.00 0.00
November 0.532089E+09 0.134632E+09 0.173785E+09 70313168.70 0.103472E+09 0.00 0.00
December 0.360253E+09 0.271478E+09 0.145763E+09 52841779.08 92920761.77 0.00 0.00
               
Annual Sum or Average 0.900517E+10 0.144811E+10 0.272940E+10 0.111886E+10 0.161054E+10 0.00 0.00
Minimum of Months 0.360253E+09 10440796.41 0.145763E+09 52841779.08 92920761.77 0.00 0.00
Maximum of Months 0.110203E+10 0.323934E+09 0.274113E+09 0.123332E+09 0.172948E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 86668392.20 0.178884E+09 41082308.58 0.00 41082308.58 0.00 0.00
February 0.114965E+09 0.129812E+09 43921584.73 0.00 43921584.73 0.00 0.00
March 0.148107E+09 0.116218E+09 57991721.80 0.00 57991721.80 0.00 0.00
April 0.215728E+09 54747639.40 63089775.24 486055.62 62603719.62 0.00 0.00
May 0.328165E+09 14280710.11 75539839.32 4652639.39 70887199.92 0.00 0.00
June 0.386684E+09 3263809.05 78475727.37 7287629.75 71188097.62 0.00 0.00
July 0.421961E+09 6465465.25 81645870.41 5359582.82 76286287.60 0.00 0.00
August 0.364251E+09 2949687.76 71335590.22 1011078.68 70324511.55 0.00 0.00
September 0.339684E+09 10577625.82 60905715.25 5546.26 60900168.99 0.00 0.00
October 0.255518E+09 17702238.65 52761519.37 0.00 52761519.37 0.00 0.00
November 0.165600E+09 70985864.35 44396560.89 0.00 44396560.89 0.00 0.00
December 0.100370E+09 0.147170E+09 40635550.93 0.00 40635550.93 0.00 0.00
               
Annual Sum or Average 0.292770E+10 0.753057E+09 0.711782E+09 18802532.51 0.692979E+09 0.00 0.00
Minimum of Months 86668392.20 2949687.76 40635550.93 0.00 40635550.93 0.00 0.00
Maximum of Months 0.421961E+09 0.178884E+09 81645870.41 7287629.75 76286287.60 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.113152E+09 0.260371E+09 54776411.44 0.00 54776411.44 0.00 0.00
February 0.151555E+09 0.189034E+09 58562112.98 0.00 58562112.98 0.00 0.00
March 0.198887E+09 0.167803E+09 77322295.74 0.00 77322295.74 0.00 0.00
April 0.295746E+09 74144571.50 84029962.37 603171.58 83426790.79 0.00 0.00
May 0.459074E+09 17347140.94 0.100720E+09 6203519.19 94516266.57 0.00 0.00
June 0.544781E+09 3301600.27 0.104634E+09 9716839.66 94917463.49 0.00 0.00
July 0.594456E+09 6751864.22 0.108861E+09 7146110.42 0.101715E+09 0.00 0.00
August 0.513131E+09 2874385.01 95111334.79 1348059.72 93763275.08 0.00 0.00
September 0.476709E+09 11889070.03 81204012.97 7252.21 81196760.76 0.00 0.00
October 0.355429E+09 22224818.97 70348692.50 0.00 70348692.50 0.00 0.00
November 0.224218E+09 0.101820E+09 59195414.51 0.00 59195414.51 0.00 0.00
December 0.132758E+09 0.214888E+09 54180734.58 0.00 54180734.58 0.00 0.00
               
Annual Sum or Average 0.405990E+10 0.107245E+10 0.948946E+09 25024952.78 0.923921E+09 0.00 0.00
Minimum of Months 0.113152E+09 2874385.01 54180734.58 0.00 54180734.58 0.00 0.00
Maximum of Months 0.594456E+09 0.260371E+09 0.108861E+09 9716839.66 0.101715E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.109797E+09 0.256102E+09 54776411.44 0.00 54776411.44 0.00 0.00
February 0.146591E+09 0.186975E+09 58562112.98 0.00 58562112.98 0.00 0.00
March 0.190179E+09 0.167878E+09 77322295.74 0.00 77322295.74 0.00 0.00
April 0.279276E+09 79705191.55 83403662.63 300545.39 83103117.24 0.00 0.00
May 0.429819E+09 21939556.44 0.100720E+09 6203519.19 94516266.57 0.00 0.00
June 0.509266E+09 5060263.45 0.104634E+09 9716839.66 94917463.49 0.00 0.00
July 0.558107E+09 9382814.92 0.108849E+09 7141044.48 0.101708E+09 0.00 0.00
August 0.478448E+09 4861989.79 94942644.87 1273536.02 93669108.85 0.00 0.00
September 0.447887E+09 15750944.53 81204012.97 7252.21 81196760.76 0.00 0.00
October 0.333278E+09 26990796.67 70348692.50 0.00 70348692.50 0.00 0.00
November 0.212233E+09 0.103483E+09 59195414.51 0.00 59195414.51 0.00 0.00
December 0.127299E+09 0.212014E+09 54180734.58 0.00 54180734.58 0.00 0.00
               
Annual Sum or Average 0.382218E+10 0.109014E+10 0.948139E+09 24642736.96 0.923496E+09 0.00 0.00
Minimum of Months 0.109797E+09 4861989.79 54180734.58 0.00 54180734.58 0.00 0.00
Maximum of Months 0.558107E+09 0.256102E+09 0.108849E+09 9716839.66 0.101708E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 54961261.04 0.133261E+09 27068841.59 0.00 27068841.59 0.00 0.00
February 74116870.63 96924190.74 28945269.21 0.00 28945269.21 0.00 0.00
March 97238500.58 86309926.48 38222479.81 0.00 38222479.81 0.00 0.00
April 0.143905E+09 38971436.31 41125210.29 100281.71 41024928.59 0.00 0.00
May 0.221396E+09 9416572.56 48565841.06 2325244.51 46240596.55 0.00 0.00
June 0.266518E+09 1882132.24 51341311.61 4586021.98 46755289.63 0.00 0.00
July 0.289543E+09 3736240.04 53035513.35 3109085.50 49926427.85 0.00 0.00
August 0.249710E+09 1769609.37 46300869.20 399335.01 45901534.20 0.00 0.00
September 0.233954E+09 6645231.85 40116687.37 3626.11 40113061.26 0.00 0.00
October 0.173613E+09 12285607.94 34754032.37 0.00 34754032.37 0.00 0.00
November 0.109381E+09 52826240.03 29242917.52 0.00 29242917.52 0.00 0.00
December 64390418.20 0.110183E+09 26768318.19 0.00 26768318.19 0.00 0.00
               
Annual Sum or Average 0.197873E+10 0.554212E+09 0.465487E+09 10523594.82 0.454964E+09 0.00 0.00
Minimum of Months 54961261.04 1769609.37 26768318.19 0.00 26768318.19 0.00 0.00
Maximum of Months 0.289543E+09 0.133261E+09 53035513.35 4586021.98 49926427.85 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.638259E+09 0.500434E+09 0.282605E+09 0.135831E+09 0.146774E+09 0.00 0.00
February 0.717763E+09 0.365149E+09 0.293520E+09 0.135697E+09 0.157823E+09 0.00 0.00
March 0.951667E+09 0.324989E+09 0.394418E+09 0.184998E+09 0.209421E+09 0.00 0.00
April 0.121455E+10 0.187647E+09 0.415260E+09 0.184237E+09 0.231023E+09 0.00 0.00
May 0.138158E+10 58386253.44 0.406278E+09 0.160872E+09 0.245406E+09 0.00 0.00
June 0.146200E+10 18067793.65 0.388201E+09 0.148291E+09 0.239910E+09 0.00 0.00
July 0.161270E+10 33565687.40 0.412870E+09 0.148436E+09 0.264434E+09 0.00 0.00
August 0.141897E+10 18900278.29 0.377084E+09 0.125358E+09 0.251727E+09 0.00 0.00
September 0.137669E+10 47931265.88 0.351736E+09 0.126455E+09 0.225282E+09 0.00 0.00
October 0.116286E+10 78096902.71 0.334448E+09 0.143382E+09 0.191066E+09 0.00 0.00
November 0.781700E+09 0.205924E+09 0.263957E+09 0.105470E+09 0.158487E+09 0.00 0.00
December 0.526948E+09 0.420568E+09 0.221606E+09 79262668.62 0.142344E+09 0.00 0.00
               
Annual Sum or Average 0.132457E+11 0.225966E+10 0.414198E+10 0.167829E+10 0.246370E+10 0.00 0.00
Minimum of Months 0.526948E+09 18067793.65 0.221606E+09 79262668.62 0.142344E+09 0.00 0.00
Maximum of Months 0.161270E+10 0.500434E+09 0.415260E+09 0.184998E+09 0.264434E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.131082E+10 0.847083E+09 0.542261E+09 0.318331E+09 0.223931E+09 0.00 0.00
February 0.128098E+10 0.638049E+09 0.502299E+09 0.272086E+09 0.230214E+09 0.00 0.00
March 0.132168E+10 0.573245E+09 0.528726E+09 0.240355E+09 0.288371E+09 0.00 0.00
April 0.132364E+10 0.317644E+09 0.442534E+09 0.156710E+09 0.285824E+09 0.00 0.00
May 0.138902E+10 0.111519E+09 0.383310E+09 91464802.35 0.291845E+09 0.00 0.00
June 0.139349E+10 32660054.75 0.327842E+09 51692411.34 0.276150E+09 0.00 0.00
July 0.162558E+10 55862118.40 0.373092E+09 68084174.40 0.305008E+09 0.00 0.00
August 0.159122E+10 37557886.97 0.401444E+09 91472869.48 0.309971E+09 0.00 0.00
September 0.168079E+10 83050251.46 0.413949E+09 0.119701E+09 0.294248E+09 0.00 0.00
October 0.169920E+10 0.151320E+09 0.508118E+09 0.228867E+09 0.279251E+09 0.00 0.00
November 0.142147E+10 0.381351E+09 0.489947E+09 0.245415E+09 0.244531E+09 0.00 0.00
December 0.135834E+10 0.714526E+09 0.544501E+09 0.316852E+09 0.227650E+09 0.00 0.00
               
Annual Sum or Average 0.173962E+11 0.394387E+10 0.545802E+10 0.220103E+10 0.325699E+10 0.00 0.00
Minimum of Months 0.128098E+10 32660054.75 0.327842E+09 51692411.34 0.223931E+09 0.00 0.00
Maximum of Months 0.169920E+10 0.847083E+09 0.544501E+09 0.318331E+09 0.309971E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.162313E+09 0.117370E+09 70651199.11 33957715.80 36693483.31 0.00 0.00
February 0.182266E+09 85151191.40 73380118.53 33924372.54 39455745.99 0.00 0.00
March 0.240972E+09 75235835.46 98604584.71 46249407.74 52355176.96 0.00 0.00
April 0.306899E+09 42014514.79 0.103815E+09 46059140.94 57755855.00 0.00 0.00
May 0.350728E+09 11774044.32 0.101570E+09 40218118.41 61351436.62 0.00 0.00
June 0.372154E+09 3340620.49 97050161.53 37072682.97 59977478.57 0.00 0.00
July 0.409188E+09 6549779.74 0.103218E+09 37108915.32 66108616.44 0.00 0.00
August 0.362321E+09 3304929.99 94271106.47 31339436.79 62931669.67 0.00 0.00
September 0.350555E+09 9844810.22 87934116.79 31613674.19 56320442.61 0.00 0.00
October 0.296564E+09 15818459.43 83611947.41 35845426.47 47766520.94 0.00 0.00
November 0.199846E+09 47017281.09 65989252.20 26367438.26 39621813.94 0.00 0.00
December 0.135120E+09 97548009.89 55401550.76 19815667.15 35585883.61 0.00 0.00
               
Annual Sum or Average 0.336893E+10 0.514970E+09 0.103550E+10 0.419572E+09 0.615924E+09 0.00 0.00
Minimum of Months 0.135120E+09 3304929.99 55401550.76 19815667.15 35585883.61 0.00 0.00
Maximum of Months 0.409188E+09 0.117370E+09 0.103815E+09 46249407.74 66108616.44 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 88808898.19 0.295106E+09 51129942.34 0.00 51129942.34 0.00 0.00
February 0.124383E+09 0.218494E+09 54731337.57 0.00 54731337.57 0.00 0.00
March 0.163480E+09 0.198947E+09 72319017.15 0.00 72319017.15 0.00 0.00
April 0.245926E+09 0.101326E+09 77997226.47 200563.41 77796663.06 0.00 0.00
May 0.370025E+09 32876761.39 89981915.80 3554374.78 86427541.01 0.00 0.00
June 0.436975E+09 9254273.59 92914436.87 6585633.75 86328803.12 0.00 0.00
July 0.480367E+09 16179105.97 96937660.98 4379492.66 92558168.32 0.00 0.00
August 0.413629E+09 10759737.66 87207964.87 755218.73 86452746.13 0.00 0.00
September 0.389287E+09 24703473.18 75558397.70 7252.21 75551145.49 0.00 0.00
October 0.283278E+09 42451906.13 65578648.48 0.00 65578648.48 0.00 0.00
November 0.176740E+09 0.124413E+09 55058638.38 0.00 55058638.38 0.00 0.00
December 0.102625E+09 0.248019E+09 50442815.65 0.00 50442815.65 0.00 0.00
               
Annual Sum or Average 0.327552E+10 0.132253E+10 0.869858E+09 15482535.55 0.854375E+09 0.00 0.00
Minimum of Months 88808898.19 9254273.59 50442815.65 0.00 50442815.65 0.00 0.00
Maximum of Months 0.480367E+09 0.295106E+09 96937660.98 6585633.75 92558168.32 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 X-RAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 LOCKER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 89340001.64 0.268670E+09 54776411.44 0.00 54776411.44 0.00 0.00
February 0.123975E+09 0.193359E+09 58562112.98 0.00 58562112.98 0.00 0.00
March 0.163045E+09 0.171209E+09 77322295.74 0.00 77322295.74 0.00 0.00
April 0.245467E+09 73670392.62 84119700.32 648074.16 83471626.16 0.00 0.00
May 0.388270E+09 17567330.91 0.100720E+09 6203519.19 94516266.57 0.00 0.00
June 0.458798E+09 3289095.48 0.104634E+09 9716839.66 94917463.49 0.00 0.00
July 0.499109E+09 8333027.26 0.108861E+09 7146110.42 0.101715E+09 0.00 0.00
August 0.426182E+09 4313324.60 95129053.36 1349170.86 93779882.50 0.00 0.00
September 0.392960E+09 14006460.46 81245215.76 10670.58 81234545.18 0.00 0.00
October 0.289121E+09 24592069.74 70348692.50 0.00 70348692.50 0.00 0.00
November 0.183827E+09 0.100759E+09 59195414.51 0.00 59195414.51 0.00 0.00
December 0.105040E+09 0.221473E+09 54180734.58 0.00 54180734.58 0.00 0.00
               
Annual Sum or Average 0.336513E+10 0.110124E+10 0.949095E+09 25074384.87 0.924020E+09 0.00 0.00
Minimum of Months 89340001.64 3289095.48 54180734.58 0.00 54180734.58 0.00 0.00
Maximum of Months 0.499109E+09 0.268670E+09 0.108861E+09 9716839.66 0.101715E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 87971421.83 0.146798E+09 41082308.58 0.00 41082308.58 0.00 0.00
February 0.118735E+09 99429074.23 43921584.73 0.00 43921584.73 0.00 0.00
March 0.153894E+09 82214297.09 57991721.80 0.00 57991721.80 0.00 0.00
April 0.222431E+09 21977738.10 63089775.24 486055.62 62603719.62 0.00 0.00
May 0.352312E+09 2955512.97 75539839.32 4652639.39 70887199.92 0.00 0.00
June 0.407318E+09 73442.37 78475727.37 7287629.75 71188097.62 0.00 0.00
July 0.434620E+09 713343.05 81645870.41 5359582.82 76286287.60 0.00 0.00
August 0.388187E+09 34764.05 71345472.64 1011739.15 70333733.48 0.00 0.00
September 0.353163E+09 571595.74 60929661.89 7595.28 60922066.60 0.00 0.00
October 0.277413E+09 3239840.42 52761519.37 0.00 52761519.37 0.00 0.00
November 0.181393E+09 45618133.98 44396560.89 0.00 44396560.89 0.00 0.00
December 0.104657E+09 0.117097E+09 40635550.93 0.00 40635550.93 0.00 0.00
               
Annual Sum or Average 0.308210E+10 0.520723E+09 0.711816E+09 18805242.01 0.693010E+09 0.00 0.00
Minimum of Months 87971421.83 34764.05 40635550.93 0.00 40635550.93 0.00 0.00
Maximum of Months 0.434620E+09 0.146798E+09 81645870.41 7287629.75 76286287.60 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.384335E+09 0.382044E+09 0.186932E+09 90553908.81 96377939.47 0.00 0.00
February 0.430383E+09 0.280756E+09 0.194134E+09 90464993.43 0.103669E+09 0.00 0.00
March 0.574994E+09 0.246793E+09 0.260925E+09 0.123332E+09 0.137593E+09 0.00 0.00
April 0.746695E+09 0.139584E+09 0.274721E+09 0.122824E+09 0.151896E+09 0.00 0.00
May 0.844957E+09 51973959.53 0.268479E+09 0.107248E+09 0.161231E+09 0.00 0.00
June 0.893540E+09 16625130.39 0.256412E+09 98860487.91 0.157551E+09 0.00 0.00
July 0.998150E+09 28720489.92 0.272689E+09 98957107.52 0.173731E+09 0.00 0.00
August 0.866402E+09 19255351.44 0.248880E+09 83571831.45 0.165308E+09 0.00 0.00
September 0.843231E+09 37210685.04 0.232243E+09 84303131.16 0.147939E+09 0.00 0.00
October 0.713250E+09 63152906.22 0.221032E+09 95587803.92 0.125444E+09 0.00 0.00
November 0.470449E+09 0.159352E+09 0.174326E+09 70313168.70 0.104013E+09 0.00 0.00
December 0.308969E+09 0.325454E+09 0.146246E+09 52841779.08 93404678.97 0.00 0.00
               
Annual Sum or Average 0.807535E+10 0.175092E+10 0.273702E+10 0.111886E+10 0.161816E+10 0.00 0.00
Minimum of Months 0.308969E+09 16625130.39 0.146246E+09 52841779.08 93404678.97 0.00 0.00
Maximum of Months 0.998150E+09 0.382044E+09 0.274721E+09 0.123332E+09 0.173731E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.320175E+09 0.886880E+09 0.189039E+09 0.00 0.189039E+09 0.00 0.00
February 0.442302E+09 0.637549E+09 0.202151E+09 0.00 0.202151E+09 0.00 0.00
March 0.576544E+09 0.569216E+09 0.266948E+09 0.00 0.266948E+09 0.00 0.00
April 0.861329E+09 0.246829E+09 0.289070E+09 1561935.27 0.287508E+09 0.00 0.00
May 0.135306E+10 57078289.10 0.344982E+09 19933943.28 0.325048E+09 0.00 0.00
June 0.159984E+10 10562503.44 0.359037E+09 32348380.34 0.326688E+09 0.00 0.00
July 0.173562E+10 28008619.59 0.373300E+09 23503062.62 0.349797E+09 0.00 0.00
August 0.149317E+10 13302862.36 0.326947E+09 4204325.69 0.322743E+09 0.00 0.00
September 0.137786E+10 46342044.53 0.280212E+09 28753.51 0.280184E+09 0.00 0.00
October 0.102100E+10 79746682.20 0.242689E+09 0.00 0.242689E+09 0.00 0.00
November 0.652909E+09 0.330488E+09 0.204227E+09 0.00 0.204227E+09 0.00 0.00
December 0.374946E+09 0.733410E+09 0.186945E+09 0.00 0.186945E+09 0.00 0.00
               
Annual Sum or Average 0.118088E+11 0.363941E+10 0.326555E+10 81580400.71 0.318397E+10 0.00 0.00
Minimum of Months 0.320175E+09 10562503.44 0.186945E+09 0.00 0.186945E+09 0.00 0.00
Maximum of Months 0.173562E+10 0.886880E+09 0.373300E+09 32348380.34 0.349797E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.287136E+10 0.974585E+09 0.119385E+10 0.741438E+09 0.452416E+09 0.00 0.00
February 0.258589E+10 0.672472E+09 0.103246E+10 0.579337E+09 0.453122E+09 0.00 0.00
March 0.245486E+10 0.515729E+09 0.995787E+09 0.452156E+09 0.543630E+09 0.00 0.00
April 0.233294E+10 0.161390E+09 0.758541E+09 0.226137E+09 0.532404E+09 0.00 0.00
May 0.264005E+10 17711864.35 0.649697E+09 0.115137E+09 0.534560E+09 0.00 0.00
June 0.282370E+10 349348.22 0.602751E+09 94013401.21 0.508738E+09 0.00 0.00
July 0.314211E+10 4395921.29 0.658585E+09 99273351.29 0.559312E+09 0.00 0.00
August 0.312858E+10 1579785.08 0.701848E+09 0.131191E+09 0.570657E+09 0.00 0.00
September 0.340731E+10 4599517.56 0.802840E+09 0.239827E+09 0.563013E+09 0.00 0.00
October 0.356941E+10 29301072.37 0.102255E+10 0.481254E+09 0.541300E+09 0.00 0.00
November 0.305728E+10 0.308229E+09 0.103569E+10 0.549937E+09 0.485758E+09 0.00 0.00
December 0.278938E+10 0.794547E+09 0.111478E+10 0.659425E+09 0.455352E+09 0.00 0.00
               
Annual Sum or Average 0.348029E+11 0.348489E+10 0.105694E+11 0.436913E+10 0.620026E+10 0.00 0.00
Minimum of Months 0.233294E+10 349348.22 0.602751E+09 94013401.21 0.452416E+09 0.00 0.00
Maximum of Months 0.356941E+10 0.974585E+09 0.119385E+10 0.741438E+09 0.570657E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.214739E+10 0.104888E+10 0.916816E+09 0.552257E+09 0.364559E+09 0.00 0.00
February 0.203462E+10 0.778827E+09 0.825287E+09 0.455007E+09 0.370279E+09 0.00 0.00
March 0.203801E+10 0.677975E+09 0.842427E+09 0.385765E+09 0.456662E+09 0.00 0.00
April 0.199338E+10 0.325464E+09 0.684703E+09 0.237407E+09 0.447296E+09 0.00 0.00
May 0.211817E+10 71604780.57 0.588908E+09 0.134044E+09 0.454864E+09 0.00 0.00
June 0.214918E+10 10775502.20 0.506156E+09 74612017.22 0.431544E+09 0.00 0.00
July 0.247892E+10 32131342.00 0.575261E+09 99722709.62 0.475538E+09 0.00 0.00
August 0.248169E+10 15211327.63 0.623310E+09 0.138265E+09 0.485045E+09 0.00 0.00
September 0.262120E+10 56679468.11 0.654122E+09 0.189117E+09 0.465005E+09 0.00 0.00
October 0.273588E+10 0.108546E+09 0.824283E+09 0.378167E+09 0.446116E+09 0.00 0.00
November 0.232823E+10 0.406278E+09 0.813440E+09 0.417763E+09 0.395677E+09 0.00 0.00
December 0.218813E+10 0.885513E+09 0.895926E+09 0.526556E+09 0.369369E+09 0.00 0.00
               
Annual Sum or Average 0.273148E+11 0.441788E+10 0.875064E+10 0.358868E+10 0.516196E+10 0.00 0.00
Minimum of Months 0.199338E+10 10775502.20 0.506156E+09 74612017.22 0.364559E+09 0.00 0.00
Maximum of Months 0.273588E+10 0.104888E+10 0.916816E+09 0.552257E+09 0.485045E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.115570E+10 0.566717E+09 0.481835E+09 0.292547E+09 0.189288E+09 0.00 0.00
February 0.108851E+10 0.419453E+09 0.432122E+09 0.239975E+09 0.192147E+09 0.00 0.00
March 0.107113E+10 0.364208E+09 0.435016E+09 0.198676E+09 0.236339E+09 0.00 0.00
April 0.102751E+10 0.180437E+09 0.347062E+09 0.116079E+09 0.230983E+09 0.00 0.00
May 0.108397E+10 44143383.12 0.296859E+09 62446626.58 0.234412E+09 0.00 0.00
June 0.110281E+10 8230378.04 0.256455E+09 34602277.84 0.221853E+09 0.00 0.00
July 0.126872E+10 21887914.18 0.290515E+09 46051204.55 0.244464E+09 0.00 0.00
August 0.127686E+10 10944308.26 0.316522E+09 66510730.11 0.250011E+09 0.00 0.00
September 0.136855E+10 36576663.03 0.338900E+09 97613078.02 0.241287E+09 0.00 0.00
October 0.143709E+10 67280527.02 0.430525E+09 0.198715E+09 0.231810E+09 0.00 0.00
November 0.123909E+10 0.225981E+09 0.427297E+09 0.221612E+09 0.205685E+09 0.00 0.00
December 0.117828E+10 0.473894E+09 0.474706E+09 0.282332E+09 0.192374E+09 0.00 0.00
               
Annual Sum or Average 0.142982E+11 0.241975E+10 0.452781E+10 0.185716E+10 0.267065E+10 0.00 0.00
Minimum of Months 0.102751E+10 8230378.04 0.256455E+09 34602277.84 0.189288E+09 0.00 0.00
Maximum of Months 0.143709E+10 0.566717E+09 0.481835E+09 0.292547E+09 0.250011E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.623045E+09 0.425768E+09 0.282605E+09 0.135831E+09 0.146774E+09 0.00 0.00
February 0.695169E+09 0.297266E+09 0.293520E+09 0.135697E+09 0.157823E+09 0.00 0.00
March 0.916406E+09 0.247596E+09 0.394418E+09 0.184998E+09 0.209421E+09 0.00 0.00
April 0.117514E+10 0.115232E+09 0.415260E+09 0.184237E+09 0.231023E+09 0.00 0.00
May 0.136202E+10 20950635.89 0.406278E+09 0.160872E+09 0.245406E+09 0.00 0.00
June 0.144959E+10 3363296.75 0.388201E+09 0.148291E+09 0.239910E+09 0.00 0.00
July 0.159045E+10 11450102.61 0.412870E+09 0.148436E+09 0.264434E+09 0.00 0.00
August 0.141773E+10 4390527.00 0.377084E+09 0.125358E+09 0.251727E+09 0.00 0.00
September 0.135633E+10 17434089.01 0.351736E+09 0.126455E+09 0.225282E+09 0.00 0.00
October 0.115648E+10 32097409.55 0.334448E+09 0.143382E+09 0.191066E+09 0.00 0.00
November 0.782318E+09 0.147802E+09 0.263957E+09 0.105470E+09 0.158487E+09 0.00 0.00
December 0.513760E+09 0.349990E+09 0.221606E+09 79262668.62 0.142344E+09 0.00 0.00
               
Annual Sum or Average 0.130384E+11 0.167334E+10 0.414198E+10 0.167829E+10 0.246370E+10 0.00 0.00
Minimum of Months 0.513760E+09 3363296.75 0.221606E+09 79262668.62 0.142344E+09 0.00 0.00
Maximum of Months 0.159045E+10 0.425768E+09 0.415260E+09 0.184998E+09 0.264434E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: NE STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.242129E+09 0.418998E+09 0.134414E+09 11319238.60 0.123094E+09 0.00 0.00
February 0.324731E+09 0.298780E+09 0.142985E+09 11308124.18 0.131677E+09 0.00 0.00
March 0.418949E+09 0.258016E+09 0.189363E+09 15416469.25 0.173946E+09 0.00 0.00
April 0.604338E+09 0.139910E+09 0.204857E+09 16664699.03 0.188192E+09 0.00 0.00
May 0.870702E+09 48212544.75 0.237706E+09 25961483.34 0.211744E+09 0.00 0.00
June 0.994944E+09 16665817.10 0.244122E+09 32023694.24 0.212098E+09 0.00 0.00
July 0.107950E+10 32662125.10 0.254732E+09 26832814.19 0.227900E+09 0.00 0.00
August 0.921897E+09 17288027.75 0.223961E+09 13177879.35 0.210783E+09 0.00 0.00
September 0.848679E+09 45969035.92 0.193760E+09 10560536.77 0.183200E+09 0.00 0.00
October 0.641401E+09 67727378.42 0.170251E+09 11948475.49 0.158302E+09 0.00 0.00
November 0.426779E+09 0.176647E+09 0.141803E+09 8789146.09 0.133014E+09 0.00 0.00
December 0.267454E+09 0.350293E+09 0.128125E+09 6605222.38 0.121520E+09 0.00 0.00
               
Annual Sum or Average 0.764151E+10 0.187117E+10 0.226608E+10 0.190608E+09 0.207547E+10 0.00 0.00
Minimum of Months 0.242129E+09 16665817.10 0.128125E+09 6605222.38 0.121520E+09 0.00 0.00
Maximum of Months 0.107950E+10 0.418998E+09 0.254732E+09 32023694.24 0.227900E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: NW ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: NW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.203528E+09 0.422862E+09 0.109553E+09 0.00 0.109553E+09 0.00 0.00
February 0.270608E+09 0.307001E+09 0.117124E+09 0.00 0.117124E+09 0.00 0.00
March 0.344708E+09 0.279463E+09 0.154645E+09 0.00 0.154645E+09 0.00 0.00
April 0.487363E+09 0.158644E+09 0.168239E+09 1296148.31 0.166943E+09 0.00 0.00
May 0.729768E+09 64766008.66 0.201440E+09 12407038.38 0.189033E+09 0.00 0.00
June 0.844141E+09 22173050.46 0.209269E+09 19433679.33 0.189835E+09 0.00 0.00
July 0.918974E+09 41615336.35 0.217722E+09 14292220.84 0.203430E+09 0.00 0.00
August 0.773820E+09 24575470.02 0.190274E+09 2700204.93 0.187574E+09 0.00 0.00
September 0.716881E+09 52557798.11 0.162541E+09 25745.48 0.162515E+09 0.00 0.00
October 0.534288E+09 80436871.15 0.140697E+09 0.00 0.140697E+09 0.00 0.00
November 0.357965E+09 0.186571E+09 0.118391E+09 0.00 0.118391E+09 0.00 0.00
December 0.224323E+09 0.355969E+09 0.108361E+09 0.00 0.108361E+09 0.00 0.00
               
Annual Sum or Average 0.640637E+10 0.199663E+10 0.189826E+10 50155037.26 0.184810E+10 0.00 0.00
Minimum of Months 0.203528E+09 22173050.46 0.108361E+09 0.00 0.108361E+09 0.00 0.00
Maximum of Months 0.918974E+09 0.422862E+09 0.217722E+09 19433679.33 0.203430E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: SW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.128039E+09 47982823.78 48552487.07 31441635.85 17110851.23 0.00 0.00
February 0.109244E+09 35450765.82 39812493.36 23099732.61 16712760.75 0.00 0.00
March 97282484.86 32108115.65 35880546.23 16133107.88 19747438.35 0.00 0.00
April 77610442.56 18638571.48 24272093.33 5550451.28 18721642.05 0.00 0.00
May 74180596.32 6712499.35 19053975.98 733665.02 18320310.96 0.00 0.00
June 77370167.53 1922257.43 17268998.92 70335.12 17198663.80 0.00 0.00
July 88286076.27 3766228.02 19232226.07 328807.25 18903418.82 0.00 0.00
August 92879712.14 2296625.09 22517371.04 2633114.47 19884256.57 0.00 0.00
September 0.113534E+09 5342993.10 28162467.11 7877878.55 20284588.57 0.00 0.00
October 0.129628E+09 9985124.10 38543566.81 18491974.11 20051592.70 0.00 0.00
November 0.122628E+09 21993731.37 40969950.12 22702754.04 18267196.08 0.00 0.00
December 0.128155E+09 40251187.32 47777629.48 30175651.15 17601978.33 0.00 0.00
               
Annual Sum or Average 0.123884E+10 0.226451E+09 0.382044E+09 0.159239E+09 0.222805E+09 0.00 0.00
Minimum of Months 74180596.32 1922257.43 17268998.92 70335.12 16712760.75 0.00 0.00
Maximum of Months 0.129628E+09 47982823.78 48552487.07 31441635.85 20284588.57 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 19.42 15.96 13.59 3.30 9.49 57.21 169.93 0.03
February 20.87 16.70 13.89 5.53 11.19 68.99 182.59 0.00
March 21.57 17.63 15.09 5.59 12.13 85.97 199.13 0.00
April 24.11 19.68 17.40 4.69 15.31 97.05 212.67 0.01
May 26.41 22.40 20.67 5.05 18.50 110.67 177.92 0.00
June 27.68 24.06 22.67 3.87 20.33 120.35 147.07 0.00
July 28.13 24.25 22.77 2.86 20.30 124.71 163.26 0.00
August 27.97 24.38 23.03 3.45 20.36 120.27 145.14 0.08
September 27.49 23.91 22.56 3.39 20.13 107.67 134.94 0.00
October 26.35 22.68 21.10 3.72 17.49 81.44 160.40 0.04
November 23.59 20.24 18.46 4.39 14.74 70.67 140.11 0.00
December 20.30 17.47 15.75 3.70 12.21 59.50 147.31 0.00
                 
Annual Sum or Average 24.51 20.80 18.94 4.12 16.04 92.16 164.97 0.01
Minimum of Months 19.42 15.96 13.59 2.86 9.49 57.21 134.94 0.00
Maximum of Months 28.13 24.38 23.03 5.59 20.36 124.71 212.67 0.08



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 28.90 02-JAN-14:20 24.35 22.57 2.37 19.46 142.33 666.50
February 29.40 11-FEB-13:00 24.15 22.20 4.60 20.75 178.50 682.00
March 29.40 13-MAR-15:00 22.41 19.40 6.20 21.27 178.00 499.00
April 32.20 17-APR-14:00 19.76 12.80 5.20 21.27 367.00 219.50
May 34.40 22-MAY-12:00 23.24 18.30 5.70 25.99 382.50 457.50
June 32.20 11-JUN-12:00 23.83 20.60 3.60 23.15 181.50 762.50
July 35.60 29-JUL-15:00 24.39 20.00 3.60 25.66 281.50 374.50
August 33.90 23-AUG-12:00 25.44 22.20 5.70 24.50 261.50 640.00
September 32.20 08-SEP-14:00 23.42 20.00 2.10 21.61 221.50 576.00
October 32.20 09-OCT-10:00 23.83 20.60 3.10 25.16 286.50 457.50
November 30.00 17-NOV-14:00 22.20 18.90 4.10 19.35 178.50 412.50
December 28.90 10-DEC-14:20 22.91 20.40 7.87 19.82 162.67 585.17
                 
Annual Sum or Average                
Minimum of Months 28.90   19.76 12.80 2.10 19.35 142.33 219.50
Maximum of Months 35.60   25.44 22.57 7.87 25.99 382.50 762.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.40 25-JAN-04:00 4.59 -1.7 3.10 -7.3 0.00 0.00
February 5.00 04-FEB-06:00 1.99 -2.8 5.70 -11.9 0.00 0.00
March 6.70 16-MAR-04:00 4.49 1.70 4.60 -9.2 0.00 0.00
April 14.40 02-APR-05:49 13.38 12.70 1.60 0.69 0.00 0.00
May 20.60 01-MAY-04:00 19.45 18.90 1.00 7.95 0.00 0.00
June 22.80 05-JUN-14:00 20.57 19.40 2.10 18.46 245.00 55.00
July 22.80 02-JUL-15:00 21.59 21.10 4.60 20.92 155.00 8.50
August 22.20 12-AUG-06:00 21.85 21.70 2.60 20.40 65.50 0.00
September 22.20 05-SEP-05:00 21.37 21.10 2.60 13.54 0.00 0.00
October 21.10 28-OCT-02:00 20.29 20.00 2.60 8.54 0.00 0.00
November 10.00 27-NOV-02:00 8.82 7.80 3.10 -4.6 0.00 0.00
December 7.80 15-DEC-05:40 5.61 3.13 6.37 -7.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 5.00   1.99 -2.8 1.00 -11.9 0.00 0.00
Maximum of Months 22.80   21.85 21.70 6.37 20.92 245.00 55.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 24.83 02-JAN-13:00 28.90 23.30 1.50 19.87 151.00 613.50
February 24.15 11-FEB-13:00 29.40 22.20 4.60 20.75 178.50 682.00
March 23.83 14-MAR-09:00 26.70 22.80 11.30 19.52 243.50 478.00
April 24.58 01-APR-15:00 28.30 23.30 3.60 16.30 93.50 759.50
May 26.05 28-MAY-14:00 28.90 25.00 5.20 25.66 289.00 98.50
June 26.06 28-JUN-11:00 28.90 25.00 1.50 22.98 404.50 373.50
July 26.39 12-JUL-10:00 30.60 25.00 4.60 23.82 287.50 574.00
August 26.46 21-AUG-15:00 32.20 24.40 3.60 24.50 205.50 366.00
September 26.31 22-SEP-16:00 30.00 25.00 6.20 28.91 54.00 21.00
October 26.52 01-OCT-11:00 29.40 25.60 6.20 28.43 283.50 0.00
November 25.31 04-NOV-13:00 27.80 24.40 2.10 26.48 199.00 3.00
December 24.31 24-DEC-14:00 27.20 23.30 2.10 23.66 201.50 114.50
                 
Annual Sum or Average                
Minimum of Months 23.83   26.70 22.20 1.50 16.30 54.00 0.00
Maximum of Months 26.52   32.20 25.60 11.30 28.91 404.50 759.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 23.30 02-JAN-13:00 28.90 24.83 1.50 19.87 151.00 613.50
February 22.80 11-FEB-16:19 27.60 24.09 5.70 18.94 101.33 565.33
March 22.80 14-MAR-09:20 25.57 23.60 9.63 22.18 176.17 527.17
April 23.30 01-APR-14:00 27.80 24.57 5.70 15.76 108.00 831.00
May 25.00 28-MAY-12:00 27.80 25.74 6.70 22.98 249.50 244.50
June 25.00 06-JUN-18:00 27.20 25.59 3.60 23.99 17.50 0.00
July 25.00 12-JUL-03:00 27.20 25.59 1.50 19.70 0.00 0.00
August 25.60 21-AUG-11:00 28.90 26.35 2.60 23.15 567.00 173.50
September 25.00 22-SEP-00:00 27.80 25.31 3.60 20.92 0.00 0.00
October 25.60 01-OCT-11:00 29.40 26.52 6.20 28.43 283.50 0.00
November 24.40 05-NOV-01:19 26.10 24.93 2.03 16.37 0.00 0.00
December 23.90 24-DEC-08:00 23.90 23.90 2.60 17.75 168.50 167.00
                 
Annual Sum or Average                
Minimum of Months 22.80   23.90 23.60 1.50 15.76 0.00 0.00
Maximum of Months 25.60   29.40 26.52 9.63 28.43 567.00 831.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 24.73 28.77 0.00
February 18.00 13.00 16.00 25.06 35.04 0.00
March 18.00 13.00 16.00 26.11 42.49 0.00
April 18.00 13.00 16.00 27.63 49.05 0.00
May 18.00 13.00 16.00 29.20 48.15 0.00
June 18.00 13.00 16.00 30.41 45.99 0.00
July 18.00 13.00 16.00 30.92 49.88 0.00
August 18.00 13.00 16.00 30.58 45.60 0.00
September 18.00 13.00 16.00 29.50 40.49 0.00
October 18.00 13.00 16.00 27.97 35.89 0.00
November 18.00 13.00 16.00 26.40 29.31 0.00
December 18.00 13.00 16.00 25.21 26.63 0.00
             
Annual Sum or Average 18.00 13.00 16.00 27.83 39.80 0.00
Minimum of Months 18.00 13.00 16.00 24.73 26.63 0.00
Maximum of Months 18.00 13.00 16.00 30.92 49.88 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.680896E+10 -0.586617E+10 0.00 0.00 744.00 0.00 -942787276.7 60.05 0.00 0.00
February 0.614229E+10 -0.528888E+10 0.00 0.00 672.00 0.00 -853410585.0 60.05 0.00 0.00
March 0.707883E+10 -0.613417E+10 0.00 0.00 744.00 0.00 -944661458.7 60.05 0.00 0.00
April 0.612888E+10 -0.521661E+10 0.00 0.00 720.00 0.00 -912273410.8 60.05 0.00 0.00
May 0.629550E+10 -0.535500E+10 0.00 0.00 744.00 0.00 -940495107.8 60.05 0.00 0.00
June 0.604228E+10 -0.513368E+10 0.00 0.00 720.00 0.00 -908596318.3 60.05 0.00 0.00
July 0.562280E+10 -0.468684E+10 0.00 0.00 744.00 0.00 -935956596.8 60.05 0.00 0.00
August 0.626501E+10 -0.532503E+10 0.00 0.00 744.00 0.00 -939986339.7 60.05 0.00 0.00
September 0.582695E+10 -0.491907E+10 0.00 0.00 720.00 0.00 -907874260.1 60.05 0.00 0.00
October 0.627086E+10 -0.532968E+10 0.00 0.00 744.00 0.00 -941179497.5 60.05 0.00 0.00
November 0.642018E+10 -0.550718E+10 0.00 0.00 720.00 0.00 -913003023.3 60.05 0.00 0.00
December 0.654997E+10 -0.560614E+10 0.00 0.00 744.00 0.00 -943827532.0 60.05 0.00 0.00
                     
Annual Sum or Average 0.754525E+11 -0.643685E+11 0.00 0.00 8760.00 0.00 -0.110841E+11 60.05 0.00 0.00
Minimum of Months 0.562280E+10 -0.613417E+10 0.00 0.00 672.00 0.00 -944661458.7 60.05 0.00 0.00
Maximum of Months 0.707883E+10 -0.468684E+10 0.00 0.00 744.00 0.00 -853410585.0 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 287.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 304.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 362.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 357.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 389.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 388.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 403.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 348.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 349.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 323.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 314.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 282.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 4111.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 282.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 403.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AHU-1 HEATING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.131440E+09 1573.38 31-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.138289E+09 1609.07 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.197818E+09 1657.53 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.236312E+09 1334.28 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.277768E+09 1196.93 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.286883E+09 1351.59 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.281661E+09 1465.12 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.255354E+09 1448.12 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.206387E+09 1415.00 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.155450E+09 1254.88 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.119058E+09 1587.69 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.139092E+09 1607.62 27-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.242551E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.119058E+09 1196.93   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.286883E+09 1657.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 BIO HAZ VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 119997.19 194.08 23-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 865801.45 193.01 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 127226.54 43.65 21-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1113025.18     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 865801.45 194.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 CLEAN VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.250475E+09 1557.63 09-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.243804E+09 1545.48 22-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.290615E+09 1561.81 20-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.328675E+09 1314.97 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.402015E+09 1233.41 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.435815E+09 1541.49 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.464727E+09 1702.60 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.461680E+09 1706.47 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.445551E+09 1683.18 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.397256E+09 1460.51 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.307312E+09 1545.93 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.269939E+09 1572.33 12-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.429786E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.243804E+09 1233.41   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.464727E+09 1706.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.385830E+09 2178.10 09-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.371729E+09 2137.39 22-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.439294E+09 2178.63 20-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.483926E+09 1810.27 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.584586E+09 1835.52 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.622319E+09 2069.54 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.661823E+09 2247.47 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.655946E+09 2243.65 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.633908E+09 2222.17 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.573048E+09 1960.06 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.453693E+09 2182.92 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.407766E+09 2159.64 12-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.627387E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.371729E+09 1810.27   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.661823E+09 2247.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 DICTATION VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 160185.08 309.37 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 1661317.08 430.13 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 797454.86 416.77 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 407132.57 407.79 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3026089.59     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1661317.08 430.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 HUMID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 IT HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 IT ROOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 LOBBY VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 504266.55 943.37 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 504266.55     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 504266.55 943.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.158818E+09 811.44 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.141203E+09 803.02 03-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.165295E+09 837.85 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.136585E+09 652.52 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.133810E+09 430.62 10-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 0.134231E+09 646.84 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.118412E+09 659.99 11-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.126612E+09 649.19 17-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.117763E+09 641.65 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.120178E+09 552.03 04-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.122453E+09 803.42 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.149369E+09 828.00 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.162473E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.117763E+09 430.62   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.165295E+09 837.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 LOUNGE VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 MED GAS VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 33212041.54 643.40 10-JAN-06:12 0.00 0.00 0.00 0.00 0.00
February 22013229.98 640.22 21-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 20313996.25 641.24 20-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 1974645.39 638.64 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 108847.23 180.84 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 4118617.02 639.25 13-NOV-06:12 0.00 0.00 0.00 0.00 0.00
December 28326350.16 642.06 27-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.110068E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 33212041.54 643.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 MRI HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 MRI TOILET VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.160607E+09 661.57 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.146255E+09 715.91 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.177402E+09 698.28 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.159512E+09 655.33 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.158096E+09 481.01 15-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 0.154327E+09 651.45 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.147085E+09 655.61 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.156730E+09 655.68 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.145257E+09 655.59 11-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.147035E+09 628.61 30-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.139413E+09 655.01 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.154695E+09 683.44 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.184641E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.139413E+09 481.01   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.177402E+09 715.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 NURSE HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 NURSE STATION VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.160556E+09 626.11 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.153296E+09 620.27 21-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.185243E+09 660.87 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.197154E+09 620.20 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.235588E+09 622.72 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.249008E+09 623.59 06-JUN-05:02 0.00 0.00 0.00 0.00 0.00
July 0.256939E+09 620.46 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.261148E+09 623.77 07-AUG-04:01 0.00 0.00 0.00 0.00 0.00
September 0.245337E+09 620.43 11-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.225863E+09 620.13 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.185514E+09 619.90 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.166298E+09 646.82 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.252195E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.153296E+09 619.90   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.261148E+09 660.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 OFFICE VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 PACU VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.208663E+09 1396.66 09-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.205152E+09 1372.68 22-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.246401E+09 1400.20 20-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.289534E+09 1182.24 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.361446E+09 1192.12 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.395280E+09 1369.07 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.429864E+09 1497.92 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.416390E+09 1494.74 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.402281E+09 1473.71 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.349183E+09 1294.69 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.259991E+09 1400.04 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.226226E+09 1395.37 27-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.379041E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.205152E+09 1182.24   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.429864E+09 1497.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.362377E+09 2295.72 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.333107E+09 2272.19 22-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.400716E+09 2423.16 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.397817E+09 2055.46 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.450506E+09 1640.62 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.477583E+09 2260.57 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.478374E+09 2274.99 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.479409E+09 2275.21 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.458344E+09 2274.20 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.421160E+09 2109.26 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.360062E+09 2272.95 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.370700E+09 2371.66 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.499015E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.333107E+09 1640.62   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.479409E+09 2423.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.618341E+09 4065.96 17-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.596201E+09 4063.49 22-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.710788E+09 4237.20 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.777153E+09 3577.48 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.933939E+09 3097.37 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.100332E+10 4042.71 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.104553E+10 4068.50 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.105987E+10 4068.89 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.100948E+10 4067.09 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.917598E+09 3848.09 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.731334E+09 4064.86 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.656156E+09 4150.20 27-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.100597E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.596201E+09 3097.37   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.105987E+10 4237.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.154810E+09 685.24 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.131746E+09 741.42 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.166182E+09 723.19 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.135583E+09 678.84 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.130421E+09 511.54 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.131081E+09 674.83 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.114248E+09 679.15 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.111505E+09 679.21 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.107301E+09 678.91 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.105066E+09 635.93 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.109388E+09 678.47 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.147420E+09 707.87 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.154475E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.105066E+09 511.54   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.166182E+09 741.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.322355E+10 5681.46 09-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.298483E+10 5619.27 03-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.348075E+10 5842.30 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.342999E+10 4972.87 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.374899E+10 4852.49 20-MAY-04:03 0.00 0.00 0.00 0.00 0.00
June 0.380590E+10 5013.66 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.391310E+10 5323.57 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.400191E+10 5324.10 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.383865E+10 5304.97 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.372324E+10 4909.39 07-OCT-04:03 0.00 0.00 0.00 0.00 0.00
November 0.329493E+10 5682.92 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.325338E+10 5729.71 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.426992E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.298483E+10 4852.49   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.400191E+10 5842.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 RECEPTION VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.362079E+09 7261.20 31-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.389725E+09 7747.89 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.579473E+09 7720.45 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.732032E+09 6113.73 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.899746E+09 5278.97 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.950233E+09 6235.74 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.919413E+09 6717.19 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.792844E+09 6655.41 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.617181E+09 6492.35 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.427850E+09 5697.27 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.306292E+09 7265.41 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.382857E+09 7443.48 27-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.735972E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.306292E+09 5278.97   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.950233E+09 7747.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 SCHEDULING VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 SCRUB VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 SOIL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.310532E+09 1665.44 09-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.299613E+09 1638.82 22-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.356241E+09 1665.87 20-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.395555E+09 1406.29 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.480785E+09 1437.04 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.514771E+09 1613.72 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.549861E+09 1754.81 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.544002E+09 1758.39 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.526655E+09 1740.37 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.474309E+09 1533.42 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.371762E+09 1665.85 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.329487E+09 1664.85 12-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.515357E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.299613E+09 1406.29   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.549861E+09 1758.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.183889E+09 810.09 17-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.163374E+09 776.84 22-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.180010E+09 796.58 20-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.164643E+09 631.49 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.178250E+09 486.00 13-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.182557E+09 681.11 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.184848E+09 730.56 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.194501E+09 734.20 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.188823E+09 733.87 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.184728E+09 654.94 30-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.168723E+09 801.64 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.179720E+09 792.96 21-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.215407E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.163374E+09 486.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.194501E+09 810.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 SOIL WORK VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.430471E+09 2406.67 09-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.416268E+09 2346.22 22-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.493431E+09 2415.43 20-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.547561E+09 1998.19 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.665664E+09 2113.06 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.709481E+09 2279.25 15-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.758843E+09 2465.13 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.744603E+09 2457.61 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.717424E+09 2432.77 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.642260E+09 2151.72 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.505413E+09 2407.08 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.454553E+09 2378.29 27-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.708597E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.416268E+09 1998.19   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.758843E+09 2465.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 STEP DOWN VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.128423E+09 3972.18 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.136537E+09 4311.18 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.183476E+09 4205.08 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.186107E+09 3231.32 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.186457E+09 2530.11 31-MAY-04:01 0.00 0.00 0.00 0.00 0.00
June 0.190253E+09 3223.21 06-JUN-05:02 0.00 0.00 0.00 0.00 0.00
July 0.179894E+09 3393.10 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.153859E+09 3332.17 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.124742E+09 3169.69 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 81924483.90 2641.43 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 73125801.39 3944.90 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.130616E+09 4027.69 27-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.175542E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 73125801.39 2530.11   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.190253E+09 4311.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 STERILE HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 STORAGE VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.197984E+09 6031.59 26-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.111809E+09 5960.41 06-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 95876591.17 6044.92 21-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 242927.88 2368.04 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 19468298.93 5926.17 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.134903E+09 6045.82 21-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.560284E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.197984E+09 6045.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 387652.97 1507.83 23-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 1539369.91 1345.91 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 573707.74 1607.13 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 55759.59 482.12 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 1296802.18 954.74 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3853292.39     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1539369.91 1607.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 75216590.90 2775.37 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 36165187.29 3003.28 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 12842002.22 2929.24 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 190800.67 1181.98 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 8523498.51 2748.00 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 63198328.34 2867.19 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.196136E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 75216590.90 3003.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1355062.11 2370.80 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 3397622.99 2490.82 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 949543.88 2501.46 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 68097.07 633.70 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 3287599.29 2448.82 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 9057925.33     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 3397622.99 2501.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 VESTIBULE VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.182721E+09 433.17 25-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 73906105.20 467.73 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.104501E+09 457.90 16-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 18343973.24 430.12 26-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 351241.02 429.74 01-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 31211195.36 430.29 07-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.187086E+09 448.03 15-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.598120E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.187086E+09 467.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AHU-2 HEATING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 CONFERENCE VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 671543.19 1702.03 21-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 7384754.29 3519.67 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 391214.87 1874.38 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 19801.99 132.01 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 2732856.31 2085.15 16-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 11200170.64     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 7384754.29 3519.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 25485138.51 506.63 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 21407537.07 408.27 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 15123013.31 552.77 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 14471007.05 146.32 03-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 21232553.94 248.40 15-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 25551062.57 281.07 12-JUN-06:02 0.00 0.00 0.00 0.00 0.00
July 38016505.78 379.59 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 32456304.78 344.22 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 29556512.50 316.89 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 29925253.36 233.25 10-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 24333103.13 346.57 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 25204756.59 424.96 27-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.302763E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 14471007.05 146.32   0.00 0.00 0.00 0.00 0.00
Maximum of Months 38016505.78 552.77   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 DICTATION VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 6867804.05 3920.47 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 20958052.90 3993.07 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 8388774.72 4144.47 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 28932.46 86.43 01-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 17691.53 58.44 06-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 53279.36 152.91 24-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 43090.97 150.13 15-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 47479.84 96.18 12-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 56577.19 164.06 30-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 91232.51 380.02 28-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 1927190.06 3190.08 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 12820293.22 4052.91 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 51300398.80     0.00 0.00 0.00 0.00 0.00
Minimum of Months 17691.53 58.44   0.00 0.00 0.00 0.00 0.00
Maximum of Months 20958052.90 4144.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 20499562.65 3224.47 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 36693071.25 3447.29 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 20081362.06 4238.73 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 29667720.98 2436.65 15-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 48104361.11 3015.94 20-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 67552838.56 3270.99 10-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.111297E+09 3303.16 22-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 66973876.81 3207.83 05-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 57734724.12 3124.69 09-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 24624209.01 2990.27 07-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 15320076.47 2691.77 04-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 31771922.68 3190.24 16-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.530321E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 15320076.47 2436.65   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.111297E+09 4238.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 42810545.57 5653.91 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 63597904.42 4705.70 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 47473833.49 7473.45 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 74423016.73 4525.28 15-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.111422E+09 5074.52 20-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.142150E+09 5178.30 10-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.243268E+09 6662.42 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.144370E+09 6423.69 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.119244E+09 5635.42 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 54600904.09 5039.41 07-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 36577318.58 5205.69 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 60730079.52 5929.52 27-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.114067E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 36577318.58 4525.28   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.243268E+09 7473.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 787768.67 820.17 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 2871230.52 844.37 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 1521461.47 1027.65 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 35818.25 82.19 19-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 39404.87 84.41 20-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 51816.50 108.08 10-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 67345.78 124.97 22-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 46612.45 89.49 05-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 34113.64 65.00 30-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 24055.58 79.30 07-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 299790.53 621.01 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 1794395.47 874.99 27-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 7573813.74     0.00 0.00 0.00 0.00 0.00
Minimum of Months 24055.58 65.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2871230.52 1027.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 5 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 58420107.91 4904.18 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 35015083.69 4314.31 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 13721231.40 5074.05 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 3802516.25 1589.95 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 1292037.72 1013.94 27-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 447317.19 950.80 10-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 893457.46 940.25 01-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 5187524.76 1225.87 26-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 1913668.04 1283.60 30-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 3225990.27 1591.04 07-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 7479898.67 4685.05 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 76645386.12 5008.74 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.208044E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 447317.19 940.25   0.00 0.00 0.00 0.00 0.00
Maximum of Months 76645386.12 5074.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.109609E+09 3027.15 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 70125173.67 2523.64 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 37329643.68 3200.55 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 10203533.32 998.48 01-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 4705272.29 902.93 13-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 4398418.56 951.61 10-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 10646372.36 978.39 22-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 11434593.01 988.81 26-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 13130939.68 1110.16 30-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 15400471.83 1307.65 07-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 25481707.34 2995.36 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 88872878.78 3129.46 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.401338E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4398418.56 902.93   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.109609E+09 3200.55   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 7 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.263980E+09 7063.81 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.211687E+09 5094.14 25-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 92177759.11 7256.40 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 73276835.87 4105.04 15-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 74184769.93 4461.48 20-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 93205992.91 4791.25 10-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.172948E+09 4814.94 22-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 0.143095E+09 4815.10 05-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 0.181685E+09 5097.89 09-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.218919E+09 5326.75 07-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.179188E+09 6371.77 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.239343E+09 6228.85 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.194369E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 73276835.87 4105.04   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.263980E+09 7256.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 8 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 73710864.94 3526.23 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 49934490.50 2490.66 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 21610135.19 3728.37 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 6319698.43 1022.43 15-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 2437805.59 916.55 13-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 3228799.58 1042.06 10-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 9704713.21 1067.81 22-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 10343679.88 1061.49 05-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 11956715.18 1226.20 30-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 11679988.12 1426.73 07-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 11514328.92 2997.66 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 59876241.75 3645.42 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.272317E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2437805.59 916.55   0.00 0.00 0.00 0.00 0.00
Maximum of Months 73710864.94 3728.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 9 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.114675E+09 3107.26 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 93427216.52 2553.05 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 35388704.95 3292.53 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 28102516.10 1666.58 15-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 30238338.66 1945.91 20-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 38987465.66 2093.12 10-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 72711554.45 2129.16 22-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 58585761.00 2115.05 05-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 75297529.45 2252.53 09-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 88341404.57 2332.81 07-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 70904241.50 2236.82 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.102813E+09 2699.19 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.809473E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 28102516.10 1666.58   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.114675E+09 3292.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 257671.51 303.74 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 257671.51     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 257671.51 303.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 5042.12 33.61 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 5042.12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 5042.12 33.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 17483.05 81.44 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 17483.05     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 17483.05 81.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 JANITOR VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1640384.02 515.37 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 3105600.90 472.03 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 1193784.67 516.89 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 402764.38 338.58 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 2924901.06 517.89 21-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 9267435.03     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 3105600.90 517.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 LOUNGE VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 OFFICE VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1192825.56 4680.24 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 6269851.82 4623.51 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 1198597.19 4950.65 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 203546.59 2338.41 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 4424676.33 4839.77 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 13289497.48     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 6269851.82 4950.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 23971.75 159.81 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 23971.75     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 23971.75 159.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 RECEPTION VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 3858273.28 4551.54 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3858273.28     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 3858273.28 4551.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 24573929.73 275.08 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 22178995.50 675.66 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 9455974.54 338.07 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 7652435.05 90.24 15-APR-13:20 0.00 0.00 0.00 0.00 0.00
May 15192217.49 223.40 20-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 24118211.19 269.43 17-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 42884600.05 257.48 08-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 33811786.00 264.10 19-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 32166816.08 279.84 09-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 33619770.21 223.41 07-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 23630283.85 184.79 04-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 22412877.17 217.79 16-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.291698E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 7652435.05 90.24   0.00 0.00 0.00 0.00 0.00
Maximum of Months 42884600.05 675.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 UTILITY VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 2344797.45 1226.16 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 2554515.54 1131.40 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 1557804.27 1241.79 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 453194.68 1213.80 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 4184823.11 1241.98 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 11095135.04     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 4184823.11 1241.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 WORK VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 WORK HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 WORK TOILET VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 57637602.86 729.96 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 39827615.86 699.71 03-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 31644866.72 771.67 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 7701129.42 263.00 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 4018341.73 110.20 27-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 5769430.09 107.62 03-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 9867004.01 158.20 15-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 8807680.43 103.31 26-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 10461155.73 123.75 30-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 19162232.33 127.07 07-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 27750680.65 721.69 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 49477391.50 754.62 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.272125E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4018341.73 103.31   0.00 0.00 0.00 0.00 0.00
Maximum of Months 57637602.86 771.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: NE STAIR VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.132006E+09 3388.12 23-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.119730E+09 3386.18 03-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.105536E+09 3387.55 20-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 4172943.18 3361.83 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 13603.03 54.05 01-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 21715204.44 3384.07 27-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.129294E+09 3387.58 21-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.512467E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.132006E+09 3388.12   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: NW ELEVATOR VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 61000226.78 2791.96 11-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 48225825.93 2784.56 22-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 51104970.39 2791.57 22-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 1254913.41 2513.92 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 10132705.24 2783.85 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 50634234.79 2808.78 27-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.222353E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 61000226.78 2808.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: NW STAIR VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.156800E+09 3915.35 26-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.127054E+09 3905.34 03-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.124866E+09 3916.04 20-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 3252671.49 3879.87 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 23578664.31 3912.03 27-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.136228E+09 3916.08 21-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.571779E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.156800E+09 3916.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: SW STAIR VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 19415104.31 2018.23 17-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 24236075.48 2017.23 22-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 25800833.21 2018.34 22-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 529254.25 1481.55 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 4164954.64 2012.29 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 20577509.93 2023.46 15-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 94723731.81     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 25800833.21 2023.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AHU-3 HEATING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 2406344.55 1877.52 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 218900.30 222.89 16-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2625244.85     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2406344.55 1877.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 HUMID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 JANITOR VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 18737285.10 517.61 17-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 13796209.87 518.33 27-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 11553150.40 515.49 02-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 332428.00 515.33 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 7128.48 47.52 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 45296.12 23.21 28-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 3971175.86 515.60 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 16634261.51 519.08 15-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 65076935.34     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 18737285.10 519.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 LOCKER VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 41471.50 237.24 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 41471.50     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 41471.50 237.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 LOUNGE VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 1798814.38 4032.75 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1798814.38     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1798814.38 4032.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.187536E+09 2537.57 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.124466E+09 2623.24 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.114698E+09 2681.02 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 64946024.14 2338.31 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 30016892.46 1382.91 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 16156854.62 1252.03 07-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 18496764.91 1508.33 31-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 34052026.37 1626.05 09-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 37743716.18 1441.94 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 64095460.08 1584.15 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 89041852.07 2511.55 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.166147E+09 2622.86 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.947397E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 16156854.62 1252.03   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.187536E+09 2681.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 MECHANICAL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 1588085.40 1769.47 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1588085.40     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1588085.40 1769.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 1687248.22 1728.40 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1687248.22     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1687248.22 1728.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 OFFICE VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 17621518.66 15083.01 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 378684.06 2524.56 16-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 18000202.72     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 17621518.66 15083.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 2799685.96 2906.11 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2799685.96     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2799685.96 2906.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 72741010.23 788.87 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 53357618.71 780.48 24-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 49353187.35 826.26 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 26132130.67 679.45 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 15312817.77 404.72 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 9968137.86 323.91 07-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 9374837.22 324.42 15-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 12682331.42 375.27 09-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 13804063.17 329.84 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 25256815.24 339.63 14-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 37016164.61 780.89 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 63772421.08 815.36 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.388772E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 9374837.22 323.91   0.00 0.00 0.00 0.00 0.00
Maximum of Months 72741010.23 826.26   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.119448E+09 15475.96 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.119394E+09 16189.56 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.103849E+09 16351.16 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 72575905.79 13629.63 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 29922240.67 7117.02 06-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 21676480.98 6671.69 24-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 29579099.14 6880.78 15-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 39463264.37 6851.28 12-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 31908111.87 7033.44 16-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 47074908.13 7525.42 28-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 54168923.06 15316.95 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.145725E+09 15996.15 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.814785E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 21676480.98 6671.69   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145725E+09 16351.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 34974083.96 3297.83 07-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 38507816.89 3566.47 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 27531114.37 3321.00 25-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 40252749.23 3355.53 15-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 31503488.70 3343.64 06-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 27686447.54 3341.05 17-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 33308447.25 3400.60 08-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 32947699.79 3705.89 19-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 32679354.95 3889.69 09-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 32589588.40 3344.69 14-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 25443502.02 3355.59 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 40549392.96 3344.08 02-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.397974E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 25443502.02 3297.83   0.00 0.00 0.00 0.00 0.00
Maximum of Months 40549392.96 3889.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 27579583.21 676.23 17-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 23700917.48 750.28 27-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 18460919.55 533.50 27-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 22642200.10 558.59 10-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 22405316.53 596.50 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 19027094.73 615.08 26-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 20601303.25 695.19 31-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 23376450.27 661.14 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 27535430.26 675.11 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 36609356.99 802.14 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 30199236.97 623.57 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 25948559.59 691.37 04-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.298086E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 18460919.55 533.50   0.00 0.00 0.00 0.00 0.00
Maximum of Months 36609356.99 802.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 64797409.82 1087.66 17-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 56164512.35 1089.10 27-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 52428523.38 1085.91 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 53831021.79 1069.50 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 57365179.01 900.20 15-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 54458766.01 1072.99 26-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 54335921.25 1080.38 03-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 62537361.79 1084.68 09-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 65258569.79 1073.36 11-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 78083591.39 1075.12 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 68043773.90 1087.15 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 63202098.31 1085.15 12-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.730507E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 52428523.38 900.20   0.00 0.00 0.00 0.00 0.00
Maximum of Months 78083591.39 1089.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 350738.34 241.18 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 350738.34     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 350738.34 241.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 TREATMENT VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 20807235.97 2318.81 07-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 23456866.32 2780.09 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 15609179.12 2375.03 25-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 23407801.28 2576.18 15-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 17607059.37 2565.68 06-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 15411793.01 2369.98 24-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 17850322.43 2481.50 15-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 18672247.98 2387.57 19-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 18041358.69 2425.11 09-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 18547201.68 2566.46 14-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 14319145.01 2555.94 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 23387044.71 2451.38 02-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.227117E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 14319145.01 2318.81   0.00 0.00 0.00 0.00 0.00
Maximum of Months 23456866.32 2780.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 262126.32 1747.51 21-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 20350878.77 13298.11 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 2573805.39 4728.56 16-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 23186810.48     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 20350878.77 13298.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1008823.04 2541.10 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 16814688.90 7458.36 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 1010501.64 5070.69 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 24542.97 409.05 13-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 3721984.94 4242.64 16-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 22580541.49     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 16814688.90 7458.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 UTILITY VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 251457.37 345.61 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 251457.37     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 251457.37 345.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 WORK VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 10382955.12 5593.00 25-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 17021975.31 5775.96 04-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 7212414.63 5911.23 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 128077.04 1153.61 19-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 174739.21 605.44 28-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 2045553.71 5535.15 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 18413612.70 5782.11 15-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 55379327.71     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 18413612.70 5911.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_CAFE HEATING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 14449543.61 3604.28 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 75146.98 1252.45 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 434.75 2.90 16-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 14525125.35     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 14449543.61 3604.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_ELEVATOR HEATING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_MRI_CONTROL HEATING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_MRI HEATING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_OR_1 HEATING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 44951.23 599.35 22-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 1809375.53 4306.98 04-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 1166.69 15.56 02-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 53002.80 706.70 12-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1908496.25     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1809375.53 4306.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_OR_2 HEATING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 45345.71 451.80 22-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 983122.68 4261.16 04-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 29671.80 395.62 12-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1058140.19     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 983122.68 4261.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_OR_3 HEATING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 59471.97 640.03 01-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 248932.12 3319.09 04-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 11101.20 148.02 09-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 319505.28     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 248932.12 3319.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_XRAY HEATING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_CAFE_SUPPHEATCOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_ELEVATOR_SUPPHEATCOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_MRI_CONTROL_SUPPHEATCOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_MRI_SUPPHEATCOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_OR_1_SUPPHEATCOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_OR_2_SUPPHEATCOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_OR_3_SUPPHEATCOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_XRAY_SUPPHEATCOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AHU-1 COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.788082E+11 0.596961E+11 104395.80 06-JAN-07:03 70468.29 0.00
February 0.00 0.00 0.790498E+11 0.593655E+11 110329.19 02-FEB-07:03 70957.31 0.00
March 0.00 0.00 0.960909E+11 0.701939E+11 119817.72 14-MAR-06:03 70002.25 0.00
April 0.00 0.00 0.107733E+12 0.763986E+11 121869.64 12-APR-06:02 75200.08 0.00
May 0.00 0.00 0.141800E+12 0.915818E+11 137682.24 31-MAY-06:02 77413.41 0.00
June 0.00 0.00 0.158950E+12 0.956793E+11 143582.94 07-JUN-06:01 81677.92 0.00
July 0.00 0.00 0.166176E+12 0.999218E+11 144051.17 26-JUL-06:01 81420.49 0.00
August 0.00 0.00 0.170495E+12 0.101619E+12 143680.61 04-AUG-06:01 82422.38 0.00
September 0.00 0.00 0.156833E+12 0.945372E+11 143614.25 22-SEP-06:01 83382.62 0.00
October 0.00 0.00 0.141179E+12 0.891972E+11 145162.72 04-OCT-06:01 78451.82 0.00
November 0.00 0.00 0.113665E+12 0.746941E+11 141745.57 30-NOV-07:02 81229.86 0.00
December 0.00 0.00 0.859434E+11 0.622099E+11 115924.66 07-DEC-07:03 72224.10 0.00
                 
Annual Sum or Average 0.00 0.00 0.149672E+13 0.975095E+12       0.00
Minimum of Months 0.00 0.00 0.788082E+11 0.593655E+11 104395.80   70002.25 0.00
Maximum of Months 0.00 0.00 0.170495E+12 0.101619E+12 145162.72   83382.62 0.00



Table of Contents

Report: CoilReportMonthly

For: AHU-2 COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.668292E+11 0.545641E+11 151751.18 14-JAN-05:01 89213.06 0.00
February 0.00 0.00 0.684467E+11 0.554487E+11 142715.32 11-FEB-05:01 83923.03 0.00
March 0.00 0.00 0.824539E+11 0.653460E+11 147278.46 14-MAR-06:03 79491.02 0.00
April 0.00 0.00 0.931693E+11 0.721028E+11 145957.45 12-APR-06:02 82427.52 0.00
May 0.00 0.00 0.123714E+12 0.877551E+11 153205.28 27-MAY-04:01 87079.34 0.00
June 0.00 0.00 0.141005E+12 0.935806E+11 151287.01 06-JUN-05:02 90823.75 0.00
July 0.00 0.00 0.145270E+12 0.964765E+11 150493.92 26-JUL-06:01 81358.73 0.00
August 0.00 0.00 0.149729E+12 0.980999E+11 150589.95 24-AUG-06:02 80744.86 0.00
September 0.00 0.00 0.136615E+12 0.908561E+11 151576.31 22-SEP-05:01 79333.89 0.00
October 0.00 0.00 0.121733E+12 0.845012E+11 151440.75 30-OCT-06:02 75788.97 0.00
November 0.00 0.00 0.969734E+11 0.691341E+11 150446.54 30-NOV-07:02 81860.59 0.00
December 0.00 0.00 0.713335E+11 0.564732E+11 140889.79 07-DEC-07:03 79907.28 0.00
                 
Annual Sum or Average 0.00 0.00 0.129727E+13 0.924338E+12       0.00
Minimum of Months 0.00 0.00 0.668292E+11 0.545641E+11 140889.79   75788.97 0.00
Maximum of Months 0.00 0.00 0.149729E+12 0.980999E+11 153205.28   90823.75 0.00



Table of Contents

Report: CoilReportMonthly

For: AHU-3 COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.739216E+11 0.608576E+11 112198.93 02-JAN-14:00 73553.87 0.00
February 0.00 0.00 0.773034E+11 0.632426E+11 117357.44 02-FEB-07:03 73167.14 0.00
March 0.00 0.00 0.952590E+11 0.762521E+11 135530.52 14-MAR-06:03 74965.70 0.00
April 0.00 0.00 0.107673E+12 0.846196E+11 137829.19 12-APR-06:02 80197.69 0.00
May 0.00 0.00 0.135758E+12 0.982106E+11 145699.89 31-MAY-06:02 79766.93 0.00
June 0.00 0.00 0.149077E+12 0.100861E+12 145698.23 22-JUN-06:03 79458.17 0.00
July 0.00 0.00 0.154013E+12 0.104525E+12 145739.61 26-JUL-06:01 79974.60 0.00
August 0.00 0.00 0.157166E+12 0.105114E+12 145763.15 24-AUG-06:02 78891.49 0.00
September 0.00 0.00 0.143650E+12 0.973883E+11 145955.62 20-SEP-06:03 78107.77 0.00
October 0.00 0.00 0.131979E+12 0.935859E+11 146564.25 04-OCT-06:01 77194.47 0.00
November 0.00 0.00 0.108130E+12 0.790413E+11 145523.96 30-NOV-07:02 80080.06 0.00
December 0.00 0.00 0.800836E+11 0.636429E+11 123965.19 07-DEC-07:03 74165.85 0.00
                 
Annual Sum or Average 0.00 0.00 0.141401E+13 0.102734E+13       0.00
Minimum of Months 0.00 0.00 0.739216E+11 0.608576E+11 112198.93   73167.14 0.00
Maximum of Months 0.00 0.00 0.157166E+12 0.105114E+12 146564.25   80197.69 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_CAFE HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.628952E+10 0.409426E+10 9909.20 02-JAN-14:10 5139.17 0.00
February 0.00 0.00 0.648578E+10 0.424443E+10 9657.39 02-FEB-06:12 4984.87 0.00
March 0.00 0.00 0.764072E+10 0.480881E+10 9809.06 14-MAR-10:10 4783.43 0.00
April 0.00 0.00 0.827811E+10 0.512660E+10 9839.30 14-APR-15:10 5394.87 0.00
May 0.00 0.00 0.105355E+11 0.605684E+10 10006.97 31-MAY-17:00 4790.49 0.00
June 0.00 0.00 0.114276E+11 0.599643E+10 10155.72 28-JUN-12:00 4515.15 0.00
July 0.00 0.00 0.112753E+11 0.599940E+10 10186.81 25-JUL-14:55 4471.96 0.00
August 0.00 0.00 0.121429E+11 0.638169E+10 10212.13 21-AUG-12:00 4423.86 0.00
September 0.00 0.00 0.111707E+11 0.596234E+10 10184.02 22-SEP-17:00 4682.29 0.00
October 0.00 0.00 0.106770E+11 0.605647E+10 10188.03 02-OCT-12:00 4389.47 0.00
November 0.00 0.00 0.914389E+10 0.525877E+10 10044.52 30-NOV-12:00 4473.82 0.00
December 0.00 0.00 0.671285E+10 0.425071E+10 9814.40 23-DEC-06:12 4504.50 0.00
                 
Annual Sum or Average 0.00 0.00 0.111780E+12 0.642367E+11       0.00
Minimum of Months 0.00 0.00 0.628952E+10 0.409426E+10 9657.39   4389.47 0.00
Maximum of Months 0.00 0.00 0.121429E+11 0.638169E+10 10212.13   5394.87 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_ELEVATOR HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.101084E+10 0.980532E+09 1759.46 14-JAN-05:01 1339.45 0.00
February 0.00 0.00 0.967407E+09 0.923668E+09 1764.24 11-FEB-05:01 1332.75 0.00
March 0.00 0.00 0.115599E+10 0.109829E+10 1713.02 10-MAR-06:12 1286.14 0.00
April 0.00 0.00 0.122489E+10 0.116894E+10 1578.07 22-APR-05:12 1281.35 0.00
May 0.00 0.00 0.145824E+10 0.136246E+10 1768.38 27-MAY-04:01 1298.78 0.00
June 0.00 0.00 0.147608E+10 0.138818E+10 1735.42 17-JUN-04:01 1399.72 0.00
July 0.00 0.00 0.155102E+10 0.147750E+10 1659.02 13-JUL-04:01 1397.73 0.00
August 0.00 0.00 0.160268E+10 0.151615E+10 1721.14 18-AUG-04:01 1388.76 0.00
September 0.00 0.00 0.152165E+10 0.144104E+10 1718.77 20-SEP-04:01 1405.54 0.00
October 0.00 0.00 0.147015E+10 0.139092E+10 1729.60 04-OCT-04:01 1395.55 0.00
November 0.00 0.00 0.124671E+10 0.118286E+10 1713.09 22-NOV-06:12 1338.05 0.00
December 0.00 0.00 0.110840E+10 0.106258E+10 1720.13 09-DEC-05:01 1387.23 0.00
                 
Annual Sum or Average 0.00 0.00 0.157941E+11 0.149931E+11       0.00
Minimum of Months 0.00 0.00 0.967407E+09 0.923668E+09 1578.07   1281.35 0.00
Maximum of Months 0.00 0.00 0.160268E+10 0.151615E+10 1768.38   1405.54 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_MRI_CONTROL HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.337930E+10 0.293173E+10 3999.13 05-JAN-07:01 3278.87 0.00
February 0.00 0.00 0.321111E+10 0.277048E+10 4029.80 21-FEB-07:01 3281.36 0.00
March 0.00 0.00 0.380135E+10 0.325252E+10 4100.02 14-MAR-06:03 2980.90 0.00
April 0.00 0.00 0.385709E+10 0.324551E+10 4123.98 12-APR-06:02 3079.10 0.00
May 0.00 0.00 0.445859E+10 0.363316E+10 4160.38 31-MAY-06:02 2951.13 0.00
June 0.00 0.00 0.465985E+10 0.366892E+10 4159.44 22-JUN-06:03 2975.01 0.00
July 0.00 0.00 0.466292E+10 0.368393E+10 4161.19 24-JUL-06:03 2968.76 0.00
August 0.00 0.00 0.489144E+10 0.382867E+10 4165.79 24-AUG-06:02 2930.12 0.00
September 0.00 0.00 0.448758E+10 0.354012E+10 4164.92 20-SEP-06:03 2947.04 0.00
October 0.00 0.00 0.435602E+10 0.351679E+10 4179.09 04-OCT-06:01 2853.93 0.00
November 0.00 0.00 0.392944E+10 0.322007E+10 4149.84 30-NOV-07:02 2976.38 0.00
December 0.00 0.00 0.346820E+10 0.297699E+10 4025.43 19-DEC-07:01 3266.86 0.00
                 
Annual Sum or Average 0.00 0.00 0.491629E+11 0.402689E+11       0.00
Minimum of Months 0.00 0.00 0.321111E+10 0.277048E+10 3999.13   2853.93 0.00
Maximum of Months 0.00 0.00 0.489144E+10 0.382867E+10 4179.09   3281.36 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_MRI HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.907536E+10 0.799149E+10 9825.84 05-JAN-07:01 8051.00 0.00
February 0.00 0.00 0.850843E+10 0.743962E+10 9946.55 02-FEB-07:03 7570.70 0.00
March 0.00 0.00 0.994873E+10 0.860970E+10 10109.62 06-MAR-06:12 8218.06 0.00
April 0.00 0.00 0.982933E+10 0.832308E+10 10109.30 14-APR-05:12 8221.45 0.00
May 0.00 0.00 0.110642E+11 0.901450E+10 10158.27 31-MAY-06:02 7132.27 0.00
June 0.00 0.00 0.114386E+11 0.896330E+10 10157.43 12-JUN-06:02 7113.36 0.00
July 0.00 0.00 0.113668E+11 0.892310E+10 10161.14 24-JUL-06:03 7164.01 0.00
August 0.00 0.00 0.120283E+11 0.937019E+10 10175.16 28-AUG-06:02 7060.51 0.00
September 0.00 0.00 0.110324E+11 0.866703E+10 10167.78 20-SEP-06:03 7121.05 0.00
October 0.00 0.00 0.108633E+11 0.878076E+10 10210.25 04-OCT-06:01 6885.34 0.00
November 0.00 0.00 0.100682E+11 0.830541E+10 10138.33 10-NOV-06:12 8137.36 0.00
December 0.00 0.00 0.919071E+10 0.799196E+10 10094.08 08-DEC-06:12 8286.29 0.00
                 
Annual Sum or Average 0.00 0.00 0.124414E+12 0.102380E+12       0.00
Minimum of Months 0.00 0.00 0.850843E+10 0.743962E+10 9825.84   6885.34 0.00
Maximum of Months 0.00 0.00 0.120283E+11 0.937019E+10 10210.25   8286.29 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_OR_1 HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.145064E+11 0.109454E+11 18286.31 02-JAN-14:10 10736.81 0.00
February 0.00 0.00 0.143195E+11 0.107113E+11 18295.56 11-FEB-06:02 12231.09 0.00
March 0.00 0.00 0.168083E+11 0.122568E+11 18259.77 06-MAR-06:01 12176.92 0.00
April 0.00 0.00 0.180153E+11 0.128651E+11 18168.13 12-APR-05:02 12651.18 0.00
May 0.00 0.00 0.217552E+11 0.146054E+11 18473.06 27-MAY-05:02 11705.49 0.00
June 0.00 0.00 0.234461E+11 0.147732E+11 18750.14 28-JUN-11:40 9953.90 0.00
July 0.00 0.00 0.236129E+11 0.150865E+11 18946.67 26-JUL-16:03 10521.15 0.00
August 0.00 0.00 0.247646E+11 0.155398E+11 18877.56 21-AUG-12:00 9916.55 0.00
September 0.00 0.00 0.230017E+11 0.146649E+11 18792.99 22-SEP-16:03 11084.36 0.00
October 0.00 0.00 0.218564E+11 0.145715E+11 18827.52 04-OCT-08:00 9444.02 0.00
November 0.00 0.00 0.189403E+11 0.128770E+11 18562.35 29-NOV-12:00 9850.94 0.00
December 0.00 0.00 0.151781E+11 0.111584E+11 18292.86 23-DEC-06:01 12060.33 0.00
                 
Annual Sum or Average 0.00 0.00 0.236205E+12 0.160055E+12       0.00
Minimum of Months 0.00 0.00 0.143195E+11 0.107113E+11 18168.13   9444.02 0.00
Maximum of Months 0.00 0.00 0.247646E+11 0.155398E+11 18946.67   12651.18 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_OR_2 HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.145619E+11 0.109578E+11 19018.16 02-JAN-14:00 10888.21 0.00
February 0.00 0.00 0.144427E+11 0.107967E+11 18975.26 11-FEB-06:02 13083.92 0.00
March 0.00 0.00 0.171573E+11 0.125358E+11 18950.81 06-MAR-06:01 12999.54 0.00
April 0.00 0.00 0.185045E+11 0.132398E+11 18889.19 12-APR-05:02 13388.66 0.00
May 0.00 0.00 0.222900E+11 0.149829E+11 19216.11 31-MAY-07:00 10412.64 0.00
June 0.00 0.00 0.240653E+11 0.151394E+11 19533.86 28-JUN-11:40 10329.86 0.00
July 0.00 0.00 0.242082E+11 0.154096E+11 19657.60 25-JUL-14:55 10305.41 0.00
August 0.00 0.00 0.253311E+11 0.158189E+11 19644.13 21-AUG-12:00 10250.87 0.00
September 0.00 0.00 0.233290E+11 0.147620E+11 19602.95 22-SEP-16:03 11526.20 0.00
October 0.00 0.00 0.219443E+11 0.145158E+11 19618.77 04-OCT-08:00 9811.37 0.00
November 0.00 0.00 0.189692E+11 0.128231E+11 19325.45 29-NOV-12:00 10216.52 0.00
December 0.00 0.00 0.151484E+11 0.111032E+11 18984.95 23-DEC-06:01 12879.52 0.00
                 
Annual Sum or Average 0.00 0.00 0.239952E+12 0.162085E+12       0.00
Minimum of Months 0.00 0.00 0.144427E+11 0.107967E+11 18889.19   9811.37 0.00
Maximum of Months 0.00 0.00 0.253311E+11 0.158189E+11 19657.60   13388.66 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_OR_3 HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.141936E+11 0.107145E+11 18661.09 07-JAN-06:01 13263.27 0.00
February 0.00 0.00 0.139118E+11 0.104343E+11 18645.73 11-FEB-06:02 13447.88 0.00
March 0.00 0.00 0.163426E+11 0.119562E+11 18652.43 06-MAR-06:01 13289.81 0.00
April 0.00 0.00 0.171892E+11 0.122123E+11 18665.55 14-APR-05:02 13332.42 0.00
May 0.00 0.00 0.205230E+11 0.136250E+11 18896.48 31-MAY-05:02 12839.03 0.00
June 0.00 0.00 0.222528E+11 0.137093E+11 19259.78 28-JUN-11:40 10045.89 0.00
July 0.00 0.00 0.223601E+11 0.138555E+11 19360.29 25-JUL-14:55 9996.73 0.00
August 0.00 0.00 0.236061E+11 0.144111E+11 19320.53 21-AUG-12:05 9900.85 0.00
September 0.00 0.00 0.214629E+11 0.132585E+11 19214.83 22-SEP-07:20 9982.78 0.00
October 0.00 0.00 0.202515E+11 0.131746E+11 19383.57 04-OCT-08:00 9606.12 0.00
November 0.00 0.00 0.179276E+11 0.120604E+11 18881.50 30-NOV-06:02 12936.66 0.00
December 0.00 0.00 0.147783E+11 0.108809E+11 18677.01 23-DEC-06:01 13197.84 0.00
                 
Annual Sum or Average 0.00 0.00 0.224800E+12 0.150293E+12       0.00
Minimum of Months 0.00 0.00 0.139118E+11 0.104343E+11 18645.73   9606.12 0.00
Maximum of Months 0.00 0.00 0.236061E+11 0.144111E+11 19383.57   13447.88 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ_XRAY HP COOLING COIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.167659E+11 0.146760E+11 22306.77 14-JAN-05:01 12185.86 0.00
February 0.00 0.00 0.158539E+11 0.137547E+11 24501.65 11-FEB-05:01 12081.04 0.00
March 0.00 0.00 0.186412E+11 0.159707E+11 21889.04 22-MAR-06:01 18760.43 0.00
April 0.00 0.00 0.185137E+11 0.154100E+11 22787.43 12-APR-04:01 11920.54 0.00
May 0.00 0.00 0.215804E+11 0.168644E+11 25222.30 31-MAY-04:01 10686.73 0.00
June 0.00 0.00 0.230358E+11 0.169699E+11 25480.32 23-JUN-04:01 11482.46 0.00
July 0.00 0.00 0.227365E+11 0.167966E+11 25618.20 12-JUL-04:01 11299.45 0.00
August 0.00 0.00 0.242702E+11 0.177694E+11 25510.38 15-AUG-04:01 12360.41 0.00
September 0.00 0.00 0.219777E+11 0.162879E+11 25572.22 22-SEP-04:02 12168.95 0.00
October 0.00 0.00 0.210626E+11 0.162897E+11 25717.65 04-OCT-04:01 9850.60 0.00
November 0.00 0.00 0.193104E+11 0.154295E+11 25295.92 30-NOV-05:02 11441.45 0.00
December 0.00 0.00 0.169758E+11 0.146111E+11 24607.42 09-DEC-05:01 12742.19 0.00
                 
Annual Sum or Average 0.00 0.00 0.240724E+12 0.190830E+12       0.00
Minimum of Months 0.00 0.00 0.158539E+11 0.137547E+11 21889.04   9850.60 0.00
Maximum of Months 0.00 0.00 0.242702E+11 0.177694E+11 25717.65   18760.43 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 3501.33 153822.85 17-JAN-07:01
February 0.00 0.00 01-FEB-00:10 3544.13 152531.91 22-FEB-07:01
March 0.00 0.00 01-MAR-00:05 3532.59 155683.52 16-MAR-06:01
April 0.00 0.00 01-APR-00:03 3519.51 123465.48 19-APR-06:01
May 0.00 0.00 01-MAY-00:02 3835.10 67571.56 13-MAY-06:03
June 0.00 0.00 01-JUN-00:01 4141.94 71053.85 15-JUN-06:01
July 0.00 0.00 01-JUL-00:01 4226.27 96984.74 10-JUL-06:01
August 0.00 0.00 01-AUG-00:01 4135.29 96420.48 21-AUG-06:01
September 0.00 0.00 01-SEP-00:03 4039.34 92857.57 18-SEP-06:01
October 0.00 0.00 01-OCT-00:03 3613.67 75689.86 02-OCT-06:01
November 0.00 0.00 01-NOV-00:03 3209.09 153753.64 13-NOV-07:01
December 0.00 0.00 01-DEC-00:01 3529.75 154988.85 12-DEC-07:01
             
Annual Sum or Average 0.00     3737.33    
Minimum of Months 0.00 0.00   3209.09 67571.56  
Maximum of Months 0.00 0.00   4226.27 155683.52  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 2176.21 7629.67 18-JAN-11:50
February 0.00 0.00 01-FEB-00:10 2172.13 7609.83 01-FEB-13:30
March 0.00 0.00 01-MAR-00:05 2275.62 7459.37 01-MAR-11:35
April 0.00 0.00 01-APR-00:03 1998.62 7137.53 03-APR-12:30
May 0.00 0.00 01-MAY-00:02 1985.34 6813.74 01-MAY-11:00
June 0.00 0.00 01-JUN-00:01 1966.40 6494.68 01-JUN-10:20
July 0.00 0.00 01-JUL-00:01 1736.45 6298.97 03-JUL-10:20
August 0.00 0.00 01-AUG-00:01 1973.90 6445.75 31-AUG-12:40
September 0.00 0.00 01-SEP-00:03 1883.99 6724.31 29-SEP-13:00
October 0.00 0.00 01-OCT-00:03 1976.14 7092.83 31-OCT-11:00
November 0.00 0.00 01-NOV-00:03 2110.84 7401.88 30-NOV-14:00
December 0.00 0.00 01-DEC-00:01 2079.25 7589.75 29-DEC-11:50
             
Annual Sum or Average 0.00     2027.14    
Minimum of Months 0.00 0.00   1736.45 6298.97  
Maximum of Months 0.00 0.00   2275.62 7629.67  



Table of Contents

Report: FanReportMonthly

For: AHU-1 FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.613489E+10 0.63 9832.72 11-JAN-07:01 1.64
February 0.580143E+10 0.65 9857.17 23-FEB-07:01 1.64
March 0.688813E+10 0.69 9857.17 01-MAR-07:01 1.64
April 0.694279E+10 0.73 9057.76 19-APR-06:01 1.59
May 0.790020E+10 0.80 9852.28 19-MAY-06:02 1.64
June 0.807049E+10 0.84 11186.57 09-JUN-06:01 1.73
July 0.822360E+10 0.84 11043.27 14-JUL-06:01 1.72
August 0.848201E+10 0.86 10910.18 18-AUG-06:01 1.72
September 0.790651E+10 0.84 10846.13 22-SEP-06:01 1.71
October 0.764488E+10 0.79 10599.92 04-OCT-06:01 1.69
November 0.681398E+10 0.71 9989.71 30-NOV-07:02 1.65
December 0.623983E+10 0.64 9857.17 12-DEC-07:01 1.65
           
Annual Sum or Average 0.870487E+11 0.75      
Minimum of Months 0.580143E+10 0.63 9057.76   1.59
Maximum of Months 0.848201E+10 0.86 11186.57   1.73



Table of Contents

Report: FanReportMonthly

For: AHU-2 FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.931759E+10 0.67 11655.37 14-JAN-05:01 1.70
February 0.903028E+10 0.71 11452.85 17-FEB-07:03 1.69
March 0.109958E+11 0.76 11722.63 14-MAR-06:03 1.70
April 0.112662E+11 0.80 11834.19 12-APR-06:02 1.71
May 0.129086E+11 0.88 13374.77 27-MAY-04:01 1.80
June 0.134142E+11 0.96 13374.77 02-JUN-06:02 1.80
July 0.130145E+11 0.93 13374.77 11-JUL-06:01 1.80
August 0.135877E+11 0.95 13374.77 02-AUG-06:01 1.80
September 0.126654E+11 0.93 13374.77 01-SEP-06:01 1.80
October 0.118542E+11 0.85 13374.77 03-OCT-06:01 1.80
November 0.102429E+11 0.75 13374.77 30-NOV-07:02 1.80
December 0.947606E+10 0.69 11937.99 01-DEC-07:03 1.72
           
Annual Sum or Average 0.137773E+12 0.82      
Minimum of Months 0.903028E+10 0.67 11452.85   1.69
Maximum of Months 0.135877E+11 0.96 13374.77   1.80



Table of Contents

Report: FanReportMonthly

For: AHU-3 FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.101215E+11 0.84 11092.10 03-JAN-17:03 1.69
February 0.100887E+11 0.91 11357.26 09-FEB-17:20 1.71
March 0.123782E+11 0.98 11713.98 31-MAR-16:20 1.73
April 0.126252E+11 1.04 12551.31 16-APR-14:51 1.79
May 0.138350E+11 1.08 12081.15 18-MAY-15:00 1.76
June 0.139142E+11 1.10 12649.10 08-JUN-06:01 1.79
July 0.139325E+11 1.08 12751.63 16-JUL-13:21 1.80
August 0.142842E+11 1.10 12600.33 18-AUG-06:01 1.79
September 0.132162E+11 1.08 12600.52 22-SEP-06:01 1.79
October 0.129316E+11 1.05 12382.82 04-OCT-06:01 1.78
November 0.116998E+11 0.98 11905.48 30-NOV-07:02 1.75
December 0.103960E+11 0.88 11298.18 01-DEC-17:00 1.71
           
Annual Sum or Average 0.149423E+12 1.01      
Minimum of Months 0.100887E+11 0.84 11092.10   1.69
Maximum of Months 0.142842E+11 1.10 12751.63   1.80



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 ANESTHESIA EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:03 0.00
May 0.00 0.00 0.00 01-MAY-00:02 0.00
June 0.00 -0.0 0.00 01-JUN-00:01 0.00
July 0.00 0.00 0.00 01-JUL-00:01 -0.0
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 -0.0 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 -0.0 0.00 01-NOV-00:03 0.00
December 0.00 0.00 0.00 01-DEC-00:01 -0.0
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 LOBBY TOILET EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:03 0.00
May 0.00 -0.0 0.00 01-MAY-00:02 0.00
June 0.00 -0.0 0.00 01-JUN-00:01 0.00
July 0.00 -0.0 0.00 01-JUL-00:01 -0.0
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 0.00 0.00 01-SEP-00:03 0.00
October 0.00 -0.0 0.00 01-OCT-00:03 0.00
November 0.00 0.00 0.00 01-NOV-00:03 0.00
December 0.00 0.00 0.00 01-DEC-00:01 -0.0
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 MRI TOILET EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:03 0.00
May 0.00 0.00 0.00 01-MAY-00:02 0.00
June 0.00 0.00 0.00 01-JUN-00:01 0.00
July 0.00 0.00 0.00 01-JUL-00:01 0.00
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 0.00 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 -0.0 0.00 01-NOV-00:03 0.00
December 0.00 0.00 0.00 01-DEC-00:01 -0.0
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 NURSE TOILET EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:03 0.00
May 0.00 -0.0 0.00 01-MAY-00:02 0.00
June 0.00 0.00 0.00 01-JUN-00:01 0.00
July 0.00 0.00 0.00 01-JUL-00:01 -0.0
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 -0.0 0.00 01-SEP-00:03 0.00
October 0.00 -0.0 0.00 01-OCT-00:03 0.00
November 0.00 0.00 0.00 01-NOV-00:03 0.00
December 0.00 0.00 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 PRE-OP TOILET EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:03 0.00
May 0.00 -0.0 0.00 01-MAY-00:02 0.00
June 0.00 0.00 0.00 01-JUN-00:01 0.00
July 0.00 0.00 0.00 01-JUL-00:01 -0.0
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 0.00 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 0.00 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 SOIL EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:03 0.00
May 0.00 -0.0 0.00 01-MAY-00:02 0.00
June 0.00 -0.0 0.00 01-JUN-00:01 0.00
July 0.00 -0.0 0.00 01-JUL-00:01 -0.0
August 0.00 0.00 0.00 01-AUG-00:01 0.00
September 0.00 0.00 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 0.00 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:01 -0.0
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 SOIL HOLD EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:03 0.00
May 0.00 0.00 0.00 01-MAY-00:02 0.00
June 0.00 -0.0 0.00 01-JUN-00:01 0.00
July 0.00 0.00 0.00 01-JUL-00:01 -0.0
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 -0.0 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 -0.0 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:01 -0.0
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 SOIL WORK EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:03 0.00
May 0.00 -0.0 0.00 01-MAY-00:02 0.00
June 0.00 -0.0 0.00 01-JUN-00:01 0.00
July 0.00 -0.0 0.00 01-JUL-00:01 0.00
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 -0.0 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 0.00 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 2 CONFERENCE TOILET EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:03 0.00
May 0.00 0.00 0.00 01-MAY-00:02 0.00
June 0.00 -0.0 0.00 01-JUN-00:01 0.00
July 0.00 -0.0 0.00 01-JUL-00:01 0.00
August 0.00 0.00 0.00 01-AUG-00:01 0.00
September 0.00 0.00 0.00 01-SEP-00:03 -0.0
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 0.00 0.00 01-NOV-00:03 0.00
December 0.00 0.00 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 2 RECEPTION TOILET EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:03 0.00
May 0.00 0.00 0.00 01-MAY-00:02 0.00
June 0.00 0.00 0.00 01-JUN-00:01 0.00
July 0.00 -0.0 0.00 01-JUL-00:01 0.00
August 0.00 0.00 0.00 01-AUG-00:01 0.00
September 0.00 0.00 0.00 01-SEP-00:03 -0.0
October 0.00 -0.0 0.00 01-OCT-00:03 0.00
November 0.00 0.00 0.00 01-NOV-00:03 0.00
December 0.00 0.00 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 2 WORK TOILET EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:03 0.00
May 0.00 -0.0 0.00 01-MAY-00:02 0.00
June 0.00 0.00 0.00 01-JUN-00:01 0.00
July 0.00 0.00 0.00 01-JUL-00:01 0.00
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 0.00 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 -0.0 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 3 LOUNGE TOILET EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:03 -0.0
May 0.00 0.00 0.00 01-MAY-00:02 0.00
June 0.00 -0.0 0.00 01-JUN-00:01 0.00
July 0.00 0.00 0.00 01-JUL-00:01 0.00
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 -0.0 0.00 01-SEP-00:03 0.00
October 0.00 -0.0 0.00 01-OCT-00:03 0.00
November 0.00 0.00 0.00 01-NOV-00:03 -0.0
December 0.00 -0.0 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 3 OFFICE TOILET EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:10 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:03 0.00
May 0.00 -0.0 0.00 01-MAY-00:02 0.00
June 0.00 -0.0 0.00 01-JUN-00:01 -0.0
July 0.00 -0.0 0.00 01-JUL-00:01 0.00
August 0.00 -0.0 0.00 01-AUG-00:01 -0.0
September 0.00 -0.0 0.00 01-SEP-00:03 -0.0
October 0.00 -0.0 0.00 01-OCT-00:03 -0.0
November 0.00 0.00 0.00 01-NOV-00:03 -0.0
December 0.00 -0.0 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:03 0.00
May 0.00 -0.0 0.00 01-MAY-00:02 0.00
June 0.00 0.00 0.00 01-JUN-00:01 0.00
July 0.00 -0.0 0.00 01-JUL-00:01 0.00
August 0.00 0.00 0.00 01-AUG-00:01 0.00
September 0.00 -0.0 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 -0.0 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 MRI CONTROL ROOM EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:10 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:03 0.00
May 0.00 0.00 0.00 01-MAY-00:02 0.00
June 0.00 0.00 0.00 01-JUN-00:01 0.00
July 0.00 0.00 0.00 01-JUL-00:01 0.00
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 -0.0 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 -0.0 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 MRI ROOM EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:03 0.00
May 0.00 -0.0 0.00 01-MAY-00:02 0.00
June 0.00 0.00 0.00 01-JUN-00:01 0.00
July 0.00 0.00 0.00 01-JUL-00:01 0.00
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 0.00 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 0.00 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: FLOOR 2 X-RAY EXHAUST FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:03 0.00
May 0.00 -0.0 0.00 01-MAY-00:02 0.00
June 0.00 -0.0 0.00 01-JUN-00:01 0.00
July 0.00 -0.0 0.00 01-JUL-00:01 0.00
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 0.00 0.00 01-SEP-00:03 0.00
October 0.00 -0.0 0.00 01-OCT-00:03 0.00
November 0.00 -0.0 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: PSZ_CAFE_ADDAQ FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.778550E+09 1.20 625.10 03-JAN-07:05 1.41
February 0.714832E+09 1.30 625.10 01-FEB-06:05 1.41
March 0.836133E+09 1.40 625.10 01-MAR-09:50 1.42
April 0.790042E+09 1.57 625.10 01-APR-14:09 1.40
May 0.850114E+09 1.63 625.10 05-MAY-17:07 1.41
June 0.869325E+09 1.63 625.10 01-JUN-17:09 1.41
July 0.861139E+09 1.64 625.10 01-JUL-05:08 1.41
August 0.920261E+09 1.62 625.10 01-AUG-17:06 1.41
September 0.870191E+09 1.63 625.10 01-SEP-17:10 1.41
October 0.865454E+09 1.64 625.10 11-OCT-05:05 1.41
November 0.796170E+09 1.54 625.10 01-NOV-07:30 1.42
December 0.795516E+09 1.29 625.10 02-DEC-08:40 1.41
           
Annual Sum or Average 0.994773E+10 1.51      
Minimum of Months 0.714832E+09 1.20 625.10   1.40
Maximum of Months 0.920261E+09 1.64 625.10   1.42



Table of Contents

Report: FanReportMonthly

For: PSZ_ELEVATOR_ADDAQ FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.243711E+09 1.59 168.10 02-JAN-06:02 1.42
February 0.225122E+09 1.52 168.10 01-FEB-08:20 1.42
March 0.267038E+09 1.54 168.10 01-MAR-15:30 1.42
April 0.268440E+09 1.60 168.10 01-APR-11:00 1.42
May 0.301428E+09 1.57 168.10 01-MAY-09:00 1.42
June 0.303375E+09 1.56 168.10 01-JUN-05:07 1.42
July 0.311751E+09 1.56 168.10 01-JUL-06:10 1.42
August 0.321296E+09 1.55 168.10 01-AUG-06:20 1.42
September 0.306626E+09 1.56 168.10 01-SEP-06:25 1.42
October 0.302035E+09 1.57 168.10 02-OCT-06:05 1.42
November 0.265611E+09 1.58 168.10 01-NOV-08:00 1.42
December 0.257897E+09 1.55 168.10 01-DEC-10:50 1.42
           
Annual Sum or Average 0.337433E+10 1.56      
Minimum of Months 0.225122E+09 1.52 168.10   1.42
Maximum of Months 0.321296E+09 1.60 168.10   1.42



Table of Contents

Report: FanReportMonthly

For: PSZ_MRI_CONTROL_ADDAQ FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.532836E+09 1.61 337.29 07-JAN-09:10 1.42
February 0.488551E+09 1.61 337.29 03-FEB-15:20 1.42
March 0.567686E+09 1.60 337.29 01-MAR-07:06 1.42
April 0.547990E+09 1.60 337.29 04-APR-05:40 1.42
May 0.584958E+09 1.59 337.29 03-MAY-05:40 1.42
June 0.582781E+09 1.58 337.29 08-JUN-14:40 1.42
July 0.585937E+09 1.58 337.29 12-JUL-12:05 1.42
August 0.604357E+09 1.57 337.29 01-AUG-17:03 1.41
September 0.571641E+09 1.58 337.29 02-SEP-15:40 1.41
October 0.572590E+09 1.59 337.29 02-OCT-04:02 1.42
November 0.537072E+09 1.60 337.29 02-NOV-08:65 1.42
December 0.540265E+09 1.61 337.29 13-DEC-11:40 1.42
           
Annual Sum or Average 0.671666E+10 1.59      
Minimum of Months 0.488551E+09 1.57 337.29   1.41
Maximum of Months 0.604357E+09 1.61 337.29   1.42



Table of Contents

Report: FanReportMonthly

For: PSZ_MRI_ADDAQ FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.135260E+10 1.58 799.35 17-JAN-07:20 1.41
February 0.123306E+10 1.57 799.35 03-FEB-10:40 1.41
March 0.141381E+10 1.56 799.35 15-MAR-13:40 1.41
April 0.134509E+10 1.57 799.35 27-APR-06:10 1.40
May 0.140861E+10 1.56 799.35 01-MAY-06:00 1.40
June 0.139023E+10 1.56 799.35 02-JUN-05:40 1.40
July 0.139049E+10 1.57 799.35 15-JUL-12:00 1.40
August 0.144116E+10 1.55 799.35 01-AUG-06:30 1.40
September 0.136307E+10 1.56 799.35 01-SEP-05:05 1.40
October 0.138201E+10 1.57 799.35 06-OCT-05:07 1.40
November 0.132579E+10 1.57 799.35 01-NOV-05:20 1.40
December 0.135780E+10 1.57 799.35 15-DEC-08:50 1.41
           
Annual Sum or Average 0.164037E+11 1.57      
Minimum of Months 0.123306E+10 1.55 799.35   1.40
Maximum of Months 0.144116E+10 1.58 799.35   1.41



Table of Contents

Report: FanReportMonthly

For: PSZ_OR_1_ADDAQ FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.192961E+10 1.60 1244.34 10-JAN-16:10 1.41
February 0.176868E+10 1.60 1244.34 01-FEB-06:10 1.41
March 0.203553E+10 1.59 1244.34 13-MAR-05:50 1.40
April 0.196608E+10 1.59 1244.34 26-APR-07:00 1.40
May 0.208770E+10 1.58 1244.34 01-MAY-07:05 1.40
June 0.208550E+10 1.57 1244.34 01-JUN-05:40 1.40
July 0.210816E+10 1.58 1244.34 01-JUL-05:07 1.40
August 0.217631E+10 1.57 1244.34 01-AUG-05:10 1.40
September 0.207287E+10 1.57 1244.34 01-SEP-07:30 1.40
October 0.208382E+10 1.58 1244.34 02-OCT-05:30 1.40
November 0.194588E+10 1.59 1244.34 01-NOV-05:03 1.40
December 0.195240E+10 1.60 1244.34 01-DEC-06:07 1.41
           
Annual Sum or Average 0.242125E+11 1.58      
Minimum of Months 0.176868E+10 1.57 1244.34   1.40
Maximum of Months 0.217631E+10 1.60 1244.34   1.41



Table of Contents

Report: FanReportMonthly

For: PSZ_OR_2_ADDAQ FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.199638E+10 1.60 1298.45 02-JAN-06:07 1.40
February 0.183026E+10 1.60 1298.45 01-FEB-07:40 1.41
March 0.211399E+10 1.59 1298.45 01-MAR-07:07 1.41
April 0.203993E+10 1.59 1298.45 01-APR-05:09 1.40
May 0.215203E+10 1.58 1298.45 01-MAY-16:04 1.40
June 0.214440E+10 1.57 1298.45 01-JUN-11:50 1.40
July 0.216241E+10 1.58 1298.45 01-JUL-05:20 1.40
August 0.222708E+10 1.57 1298.45 01-AUG-06:10 1.40
September 0.210865E+10 1.58 1298.45 01-SEP-06:15 1.40
October 0.211656E+10 1.59 1298.45 02-OCT-06:30 1.40
November 0.199114E+10 1.59 1298.45 01-NOV-05:50 1.40
December 0.201007E+10 1.60 1298.45 01-DEC-07:05 1.41
           
Annual Sum or Average 0.248929E+11 1.59      
Minimum of Months 0.183026E+10 1.57 1298.45   1.40
Maximum of Months 0.222708E+10 1.60 1298.45   1.41



Table of Contents

Report: FanReportMonthly

For: PSZ_OR_3_ADDAQ FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.198674E+10 1.60 1287.62 02-JAN-06:17 1.40
February 0.181481E+10 1.60 1287.62 01-FEB-06:02 1.41
March 0.208344E+10 1.59 1287.62 01-MAR-06:02 1.41
April 0.197052E+10 1.60 1287.62 01-APR-05:02 1.40
May 0.205074E+10 1.59 1287.62 01-MAY-05:08 1.40
June 0.202386E+10 1.59 1287.62 01-JUN-11:40 1.40
July 0.201223E+10 1.60 1287.62 01-JUL-06:00 1.40
August 0.209673E+10 1.59 1287.62 01-AUG-06:04 1.40
September 0.197475E+10 1.59 1287.62 01-SEP-06:40 1.40
October 0.200400E+10 1.60 1287.62 02-OCT-06:06 1.40
November 0.193570E+10 1.60 1287.62 01-NOV-06:00 1.40
December 0.199384E+10 1.60 1287.62 01-DEC-07:20 1.41
           
Annual Sum or Average 0.239474E+11 1.60      
Minimum of Months 0.181481E+10 1.59 1287.62   1.40
Maximum of Months 0.209673E+10 1.60 1287.62   1.41



Table of Contents

Report: FanReportMonthly

For: PSZ_XRAY_ADDAQ FAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.279276E+10 1.54 1773.77 02-JAN-07:30 1.36
February 0.255137E+10 1.54 1773.77 06-FEB-13:00 1.36
March 0.293517E+10 1.53 1773.77 04-MAR-06:02 1.35
April 0.276773E+10 1.54 1773.77 12-APR-17:17 1.34
May 0.292075E+10 1.53 1773.77 15-MAY-17:09 1.34
June 0.291551E+10 1.52 1773.77 03-JUN-08:20 1.35
July 0.288081E+10 1.53 1773.77 11-JUL-06:40 1.35
August 0.301997E+10 1.52 1773.77 16-AUG-05:10 1.35
September 0.283189E+10 1.53 1773.77 09-SEP-10:30 1.35
October 0.284119E+10 1.54 1773.77 10-OCT-05:15 1.35
November 0.272911E+10 1.54 1773.77 09-NOV-07:30 1.36
December 0.279706E+10 1.54 1773.77 11-DEC-09:40 1.36
           
Annual Sum or Average 0.339833E+11 1.53      
Minimum of Months 0.255137E+10 1.52 1773.77   1.34
Maximum of Months 0.301997E+10 1.54 1773.77   1.36



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 51464507.58 46318056.82 363.95 09-JAN-07:01 327.56 327.56 34.14 1.17
February 46287817.18 41659035.46 363.95 03-FEB-07:01 327.56 327.56 34.62 1.17
March 52080651.38 46872586.25 363.95 01-MAR-07:01 327.56 327.56 34.25 1.17
April 50150137.83 45135124.05 296.80 19-APR-06:01 267.12 267.12 32.59 0.89
May 56432695.40 50789425.86 244.43 13-MAY-06:03 219.99 219.99 29.85 0.45
June 58980506.87 53082456.18 250.56 10-JUN-06:03 225.50 225.50 30.45 0.48
July 62054861.55 55849375.40 274.25 10-JUL-06:01 246.82 246.82 30.67 0.66
August 60921402.38 54829262.14 273.85 21-AUG-06:01 246.47 246.47 30.65 0.66
September 57750381.70 51975343.53 270.60 18-SEP-06:01 243.54 243.54 30.16 0.63
October 53401128.68 48061015.81 253.80 07-OCT-06:03 228.42 228.42 30.23 0.50
November 45849272.62 41264345.36 363.95 13-NOV-07:01 327.56 327.56 34.13 1.17
December 51875788.78 46688209.90 363.95 12-DEC-07:01 327.56 327.56 33.88 1.17
                 
Annual Sum or Average 0.647249E+09 0.582524E+09            
Minimum of Months 45849272.62 41264345.36 244.43   219.99 219.99 29.85 0.45
Maximum of Months 62054861.55 55849375.40 363.95   327.56 327.56 34.62 1.17



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 18997338.61 5699201.58 8.07 01-JAN-08:65 2.42 2.42 59.70 0.06
February 17341607.26 5202482.18 8.07 01-FEB-00:10 2.42 2.42 59.70 0.06
March 19897824.08 5969347.22 8.07 01-MAR-00:05 2.42 2.42 59.72 0.06
April 18735907.35 5620772.20 8.07 01-APR-00:03 2.42 2.42 59.71 0.06
May 19433057.39 5829917.22 8.07 01-MAY-00:02 2.42 2.42 59.73 0.06
June 19171626.12 5751487.84 8.07 01-JUN-00:01 2.42 2.42 59.74 0.06
July 18997338.61 5699201.58 8.07 01-JUL-00:01 2.42 2.42 59.78 0.06
August 19868776.16 5960632.85 8.07 01-AUG-00:01 2.42 2.42 59.75 0.06
September 18706859.43 5612057.83 8.07 01-SEP-00:03 2.42 2.42 59.76 0.06
October 19026386.53 5707915.96 8.07 01-OCT-07:03 2.42 2.42 59.76 0.06
November 18300188.57 5490056.57 8.07 01-NOV-00:03 2.42 2.42 59.71 0.06
December 18997338.61 5699201.58 8.07 01-DEC-00:01 2.42 2.42 59.73 0.06
                 
Annual Sum or Average 0.227474E+09 68242274.62            
Minimum of Months 17341607.26 5202482.18 8.07   2.42 2.42 59.70 0.06
Maximum of Months 19897824.08 5969347.22 8.07   2.42 2.42 59.78 0.06



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 24.10 24.10 3501.33 153822.85 17-JAN-07:01
February 0.00 0.00 01-FEB-00:10 27.39 27.39 3544.13 152531.91 22-FEB-07:01
March 0.00 0.00 01-MAR-00:05 24.05 24.05 3532.59 155683.52 16-MAR-06:01
April 0.00 0.00 01-APR-00:03 24.13 24.13 3519.51 123465.48 19-APR-06:01
May 0.00 0.00 01-MAY-00:02 24.04 24.04 3835.10 67571.56 13-MAY-06:03
June 0.00 0.00 01-JUN-00:01 24.14 24.14 4141.94 71053.85 15-JUN-06:01
July 0.00 0.00 01-JUL-00:01 23.74 23.74 4226.27 96984.74 10-JUL-06:01
August 0.00 0.00 01-AUG-00:01 23.79 23.79 4135.29 96420.48 21-AUG-06:01
September 0.00 0.00 01-SEP-00:03 24.22 24.22 4039.34 92857.57 18-SEP-06:01
October 0.00 0.00 01-OCT-00:03 23.69 23.69 3613.67 75689.86 02-OCT-06:01
November 0.00 0.00 01-NOV-00:03 24.34 24.34 3209.09 153753.64 13-NOV-07:01
December 0.00 0.00 01-DEC-00:01 24.32 24.32 3529.75 154988.85 12-DEC-07:01
                 
Annual Sum or Average 0.00         3737.33    
Minimum of Months 0.00 0.00   23.69 23.69 3209.09 67571.56  
Maximum of Months 0.00 0.00   27.39 27.39 4226.27 155683.52  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 59.68 59.68 2176.21 7629.67 18-JAN-11:50
February 0.00 0.00 01-FEB-00:10 59.70 60.04 2172.13 7609.83 01-FEB-13:30
March 0.00 0.00 01-MAR-00:05 59.72 60.07 2275.62 7459.37 01-MAR-11:35
April 0.00 0.00 01-APR-00:03 59.71 60.02 1998.62 7137.53 03-APR-12:30
May 0.00 0.00 01-MAY-00:02 59.73 60.02 1985.34 6813.74 01-MAY-11:00
June 0.00 0.00 01-JUN-00:01 59.74 60.02 1966.40 6494.68 01-JUN-10:20
July 0.00 0.00 01-JUL-00:01 59.78 60.05 1736.45 6298.97 03-JUL-10:20
August 0.00 0.00 01-AUG-00:01 59.75 60.09 1973.90 6445.75 31-AUG-12:40
September 0.00 0.00 01-SEP-00:03 59.76 60.03 1883.99 6724.31 29-SEP-13:00
October 0.00 0.00 01-OCT-00:03 59.75 59.75 1976.14 7092.83 31-OCT-11:00
November 0.00 0.00 01-NOV-00:03 59.71 60.02 2110.84 7401.88 30-NOV-14:00
December 0.00 0.00 01-DEC-00:01 59.73 60.05 2079.25 7589.75 29-DEC-11:50
                 
Annual Sum or Average 0.00         2027.14    
Minimum of Months 0.00 0.00   59.68 59.68 1736.45 6298.97  
Maximum of Months 0.00 0.00   59.78 60.09 2275.62 7629.67  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 CLEAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 IT HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 LOBBY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 MED GAS

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 PACU

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 SCRUB

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 SOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 X-RAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 LOCKER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: NE STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: NW ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: NW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: SW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AHU-1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.772202E+10 0.00 0.00 0.254089E+11 0.00 0.06
February 0.710299E+10 0.00 0.00 0.253305E+11 0.00 0.08
March 0.848899E+10 0.00 0.00 0.305212E+11 0.00 0.07
April 0.861889E+10 0.00 0.00 0.335704E+11 0.00 0.00
May 0.982853E+10 0.00 0.00 0.434667E+11 0.00 0.00
June 0.102430E+11 0.00 0.00 0.480179E+11 0.00 0.00
July 0.105046E+11 0.00 0.00 0.505346E+11 0.00 0.00
August 0.104164E+11 0.00 0.00 0.515955E+11 0.00 0.00
September 0.978509E+10 0.00 0.00 0.473871E+11 0.00 0.00
October 0.894615E+10 0.00 0.00 0.428691E+11 0.00 0.00
November 0.757191E+10 0.00 0.00 0.347060E+11 0.00 0.00
December 0.783691E+10 0.00 0.00 0.271200E+11 0.00 0.03
             
Annual Sum or Average 0.107066E+12 0.00 0.00 0.460528E+12 0.00 0.24
Minimum of Months 0.710299E+10 0.00 0.00 0.253305E+11 0.00 0.00
Maximum of Months 0.105046E+11 0.00 0.00 0.515955E+11 0.00 0.08



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AHU-2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.117413E+10 0.00 0.00 0.256513E+11 0.00 0.00
February 0.101045E+10 0.00 0.00 0.258200E+11 0.00 0.00
March 0.645566E+09 0.00 0.00 0.311505E+11 0.00 0.00
April 0.264895E+09 0.00 0.00 0.343519E+11 0.00 0.00
May 0.312898E+09 0.00 0.00 0.440438E+11 0.00 0.00
June 0.405515E+09 0.00 0.00 0.490543E+11 0.00 0.00
July 0.712348E+09 0.00 0.00 0.504288E+11 0.00 0.00
August 0.515160E+09 0.00 0.00 0.517657E+11 0.00 0.00
September 0.533237E+09 0.00 0.00 0.473677E+11 0.00 0.00
October 0.499614E+09 0.00 0.00 0.424602E+11 0.00 0.00
November 0.485078E+09 0.00 0.00 0.341079E+11 0.00 0.00
December 0.112276E+10 0.00 0.00 0.269060E+11 0.00 0.00
             
Annual Sum or Average 0.768165E+10 0.00 0.00 0.463108E+12 0.00 0.00
Minimum of Months 0.264895E+09 0.00 0.00 0.256513E+11 0.00 0.00
Maximum of Months 0.117413E+10 0.00 0.00 0.517657E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AHU-3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.558274E+09 0.00 0.00 0.285405E+11 0.00 0.00
February 0.535578E+09 0.00 0.00 0.293970E+11 0.00 0.00
March 0.401706E+09 0.00 0.00 0.361049E+11 0.00 0.00
April 0.304248E+09 0.00 0.00 0.398228E+11 0.00 0.00
May 0.204140E+09 0.00 0.00 0.484893E+11 0.00 0.00
June 0.164386E+09 0.00 0.00 0.519676E+11 0.00 0.00
July 0.183547E+09 0.00 0.00 0.539049E+11 0.00 0.00
August 0.223731E+09 0.00 0.00 0.547253E+11 0.00 0.00
September 0.226971E+09 0.00 0.00 0.500299E+11 0.00 0.00
October 0.302477E+09 0.00 0.00 0.465587E+11 0.00 0.00
November 0.324274E+09 0.00 0.00 0.387803E+11 0.00 0.00
December 0.570673E+09 0.00 0.00 0.303619E+11 0.00 0.00
             
Annual Sum or Average 0.400000E+10 0.00 0.00 0.508683E+12 0.00 0.00
Minimum of Months 0.164386E+09 0.00 0.00 0.285405E+11 0.00 0.00
Maximum of Months 0.570673E+09 0.00 0.00 0.547253E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ_CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.251025E+10 0.00 0.00
February 0.00 0.00 0.00 0.252969E+10 0.00 0.00
March 0.00 0.00 0.00 0.296238E+10 0.00 0.00
April 0.00 0.00 0.00 0.312935E+10 0.00 0.00
May 0.00 0.00 0.00 0.387743E+10 0.00 0.00
June 0.00 0.00 0.00 0.411351E+10 0.00 0.00
July 0.00 0.00 0.00 0.409660E+10 0.00 0.00
August 0.00 0.00 0.00 0.438105E+10 0.00 0.00
September 0.00 0.00 0.00 0.405586E+10 0.00 0.00
October 0.00 0.00 0.00 0.392059E+10 0.00 0.00
November 0.00 0.00 0.00 0.336685E+10 0.00 0.00
December 0.00 0.00 0.00 0.264672E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.415903E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.251025E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.438105E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ_ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.531845E+09 0.00 0.00
February 0.00 0.00 0.00 0.503509E+09 0.00 0.00
March 0.00 0.00 0.00 0.599912E+09 0.00 0.00
April 0.00 0.00 0.00 0.630659E+09 0.00 0.00
May 0.00 0.00 0.00 0.745086E+09 0.00 0.00
June 0.00 0.00 0.00 0.758494E+09 0.00 0.00
July 0.00 0.00 0.00 0.799486E+09 0.00 0.00
August 0.00 0.00 0.00 0.820072E+09 0.00 0.00
September 0.00 0.00 0.00 0.776329E+09 0.00 0.00
October 0.00 0.00 0.00 0.748392E+09 0.00 0.00
November 0.00 0.00 0.00 0.632355E+09 0.00 0.00
December 0.00 0.00 0.00 0.575432E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.812157E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.503509E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.820072E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ_MRI_CONTROL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.148133E+10 0.00 0.00
February 0.00 0.00 0.00 0.140403E+10 0.00 0.00
March 0.00 0.00 0.00 0.164768E+10 0.00 0.00
April 0.00 0.00 0.00 0.167471E+10 0.00 0.00
May 0.00 0.00 0.00 0.193379E+10 0.00 0.00
June 0.00 0.00 0.00 0.200814E+10 0.00 0.00
July 0.00 0.00 0.00 0.204257E+10 0.00 0.00
August 0.00 0.00 0.00 0.211548E+10 0.00 0.00
September 0.00 0.00 0.00 0.194760E+10 0.00 0.00
October 0.00 0.00 0.00 0.188795E+10 0.00 0.00
November 0.00 0.00 0.00 0.168443E+10 0.00 0.00
December 0.00 0.00 0.00 0.151917E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.213469E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.140403E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.211548E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ_MRI

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.390286E+10 0.00 0.00
February 0.00 0.00 0.00 0.366060E+10 0.00 0.00
March 0.00 0.00 0.00 0.423907E+10 0.00 0.00
April 0.00 0.00 0.00 0.421519E+10 0.00 0.00
May 0.00 0.00 0.00 0.475279E+10 0.00 0.00
June 0.00 0.00 0.00 0.488555E+10 0.00 0.00
July 0.00 0.00 0.00 0.493582E+10 0.00 0.00
August 0.00 0.00 0.00 0.515229E+10 0.00 0.00
September 0.00 0.00 0.00 0.474177E+10 0.00 0.00
October 0.00 0.00 0.00 0.466013E+10 0.00 0.00
November 0.00 0.00 0.00 0.426433E+10 0.00 0.00
December 0.00 0.00 0.00 0.395248E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.533629E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.366060E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.515229E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ_OR_1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.603434E+10 0.00 0.00
February 0.00 0.00 0.00 0.586530E+10 0.00 0.00
March 0.00 0.00 0.00 0.683898E+10 0.00 0.00
April 0.00 0.00 0.00 0.722195E+10 0.00 0.00
May 0.00 0.00 0.00 0.864969E+10 0.00 0.00
June 0.00 0.00 0.00 0.919934E+10 0.00 0.00
July 0.00 0.00 0.00 0.939801E+10 0.00 0.00
August 0.00 0.00 0.00 0.974050E+10 0.00 0.00
September 0.00 0.00 0.00 0.906500E+10 0.00 0.00
October 0.00 0.00 0.00 0.865576E+10 0.00 0.00
November 0.00 0.00 0.00 0.746587E+10 0.00 0.00
December 0.00 0.00 0.00 0.625493E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.943897E+11 0.00 0.02
Minimum of Months 0.00 0.00 0.00 0.586530E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.974050E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ_OR_2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.612027E+10 0.00 0.01
February 0.00 0.00 0.00 0.595909E+10 0.00 0.00
March 0.00 0.00 0.00 0.701393E+10 0.00 0.00
April 0.00 0.00 0.00 0.743321E+10 0.00 0.00
May 0.00 0.00 0.00 0.887131E+10 0.00 0.00
June 0.00 0.00 0.00 0.944412E+10 0.00 0.00
July 0.00 0.00 0.00 0.963759E+10 0.00 0.00
August 0.00 0.00 0.00 0.996426E+10 0.00 0.00
September 0.00 0.00 0.00 0.919822E+10 0.00 0.00
October 0.00 0.00 0.00 0.870927E+10 0.00 0.00
November 0.00 0.00 0.00 0.751131E+10 0.00 0.00
December 0.00 0.00 0.00 0.630474E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.961673E+11 0.00 0.02
Minimum of Months 0.00 0.00 0.00 0.595909E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.996426E+10 0.00 0.01



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ_OR_3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.600811E+10 0.00 0.01
February 0.00 0.00 0.00 0.579087E+10 0.00 0.00
March 0.00 0.00 0.00 0.674554E+10 0.00 0.00
April 0.00 0.00 0.00 0.696428E+10 0.00 0.00
May 0.00 0.00 0.00 0.821185E+10 0.00 0.00
June 0.00 0.00 0.00 0.875040E+10 0.00 0.00
July 0.00 0.00 0.00 0.890780E+10 0.00 0.00
August 0.00 0.00 0.00 0.929258E+10 0.00 0.00
September 0.00 0.00 0.00 0.847523E+10 0.00 0.00
October 0.00 0.00 0.00 0.806654E+10 0.00 0.00
November 0.00 0.00 0.00 0.713960E+10 0.00 0.00
December 0.00 0.00 0.00 0.617937E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.905322E+11 0.00 0.03
Minimum of Months 0.00 0.00 0.00 0.579087E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.929258E+10 0.00 0.01



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ_XRAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.694166E+10 0.00 0.00
February 0.00 0.00 0.00 0.652445E+10 0.00 0.00
March 0.00 0.00 0.00 0.758859E+10 0.00 0.00
April 0.00 0.00 0.00 0.750231E+10 0.00 0.00
May 0.00 0.00 0.00 0.857655E+10 0.00 0.00
June 0.00 0.00 0.00 0.898092E+10 0.00 0.00
July 0.00 0.00 0.00 0.899649E+10 0.00 0.00
August 0.00 0.00 0.00 0.946999E+10 0.00 0.00
September 0.00 0.00 0.00 0.864205E+10 0.00 0.00
October 0.00 0.00 0.00 0.835615E+10 0.00 0.00
November 0.00 0.00 0.00 0.764245E+10 0.00 0.00
December 0.00 0.00 0.00 0.701123E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.962328E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.652445E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.946999E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AHU-1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.613489E+10 0.788082E+11 0.772202E+10 0.00 0.00 0.148727E+09 0.00 0.00
February 0.580143E+10 0.790498E+11 0.710299E+10 0.00 0.00 0.207130E+09 0.00 0.00
March 0.688813E+10 0.960909E+11 0.848899E+10 0.00 0.00 0.194667E+09 0.00 0.00
April 0.694279E+10 0.107733E+12 0.861889E+10 0.00 0.00 0.00 0.00 0.00
May 0.790020E+10 0.141800E+12 0.982853E+10 0.00 0.00 0.00 0.00 0.00
June 0.807049E+10 0.158950E+12 0.102430E+11 0.00 0.00 0.00 0.00 0.00
July 0.822360E+10 0.166176E+12 0.105046E+11 0.00 0.00 0.00 0.00 0.00
August 0.848201E+10 0.170495E+12 0.104164E+11 0.00 0.00 0.00 0.00 0.00
September 0.790651E+10 0.156833E+12 0.978509E+10 0.00 0.00 0.00 0.00 0.00
October 0.764488E+10 0.141179E+12 0.894615E+10 0.00 0.00 0.00 0.00 0.00
November 0.681398E+10 0.113665E+12 0.757191E+10 0.00 0.00 10104136.10 0.00 0.00
December 0.623983E+10 0.859434E+11 0.783691E+10 0.00 0.00 75386310.31 0.00 0.00
                 
Annual Sum or Average 0.870487E+11 0.149672E+13 0.107066E+12 0.00 0.00 0.636015E+09 0.00 0.00
Minimum of Months 0.580143E+10 0.788082E+11 0.710299E+10 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.848201E+10 0.170495E+12 0.105046E+11 0.00 0.00 0.207130E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AHU-2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.931759E+10 0.668292E+11 0.117413E+10 0.00 0.00 0.00 0.00 0.00
February 0.903028E+10 0.684467E+11 0.101045E+10 0.00 0.00 0.00 0.00 0.00
March 0.109958E+11 0.824539E+11 0.645566E+09 0.00 0.00 0.00 0.00 0.00
April 0.112662E+11 0.931693E+11 0.264895E+09 0.00 0.00 0.00 0.00 0.00
May 0.129086E+11 0.123714E+12 0.312898E+09 0.00 0.00 0.00 0.00 0.00
June 0.134142E+11 0.141005E+12 0.405515E+09 0.00 0.00 0.00 0.00 0.00
July 0.130145E+11 0.145270E+12 0.712348E+09 0.00 0.00 0.00 0.00 0.00
August 0.135877E+11 0.149729E+12 0.515160E+09 0.00 0.00 0.00 0.00 0.00
September 0.126654E+11 0.136615E+12 0.533237E+09 0.00 0.00 0.00 0.00 0.00
October 0.118542E+11 0.121733E+12 0.499614E+09 0.00 0.00 0.00 0.00 0.00
November 0.102429E+11 0.969734E+11 0.485078E+09 0.00 0.00 0.00 0.00 0.00
December 0.947606E+10 0.713335E+11 0.112276E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.137773E+12 0.129727E+13 0.768165E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.903028E+10 0.668292E+11 0.264895E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135877E+11 0.149729E+12 0.117413E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AHU-3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.101215E+11 0.739216E+11 0.558274E+09 0.00 0.00 0.00 0.00 0.00
February 0.100887E+11 0.773034E+11 0.535578E+09 0.00 0.00 0.00 0.00 0.00
March 0.123782E+11 0.952590E+11 0.401706E+09 0.00 0.00 0.00 0.00 0.00
April 0.126252E+11 0.107673E+12 0.304248E+09 0.00 0.00 0.00 0.00 0.00
May 0.138350E+11 0.135758E+12 0.204140E+09 0.00 0.00 0.00 0.00 0.00
June 0.139142E+11 0.149077E+12 0.164386E+09 0.00 0.00 0.00 0.00 0.00
July 0.139325E+11 0.154013E+12 0.183547E+09 0.00 0.00 0.00 0.00 0.00
August 0.142842E+11 0.157166E+12 0.223731E+09 0.00 0.00 0.00 0.00 0.00
September 0.132162E+11 0.143650E+12 0.226971E+09 0.00 0.00 0.00 0.00 0.00
October 0.129316E+11 0.131979E+12 0.302477E+09 0.00 0.00 0.00 0.00 0.00
November 0.116998E+11 0.108130E+12 0.324274E+09 0.00 0.00 0.00 0.00 0.00
December 0.103960E+11 0.800836E+11 0.570673E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.149423E+12 0.141401E+13 0.400000E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.100887E+11 0.739216E+11 0.164386E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.142842E+11 0.157166E+12 0.570673E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ_CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.778550E+09 0.628952E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.714832E+09 0.648578E+10 14449543.61 0.00 0.00 0.00 0.00 0.00
March 0.836133E+09 0.764072E+10 75146.98 0.00 0.00 0.00 0.00 0.00
April 0.790042E+09 0.827811E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.850114E+09 0.105355E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.869325E+09 0.114276E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.861139E+09 0.112753E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.920261E+09 0.121429E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.870191E+09 0.111707E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.865454E+09 0.106770E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.796170E+09 0.914389E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.795516E+09 0.671285E+10 434.75 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.994773E+10 0.111780E+12 14525125.35 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.714832E+09 0.628952E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.920261E+09 0.121429E+11 14449543.61 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ_ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.243711E+09 0.101084E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.225122E+09 0.967407E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.267038E+09 0.115599E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.268440E+09 0.122489E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.301428E+09 0.145824E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.303375E+09 0.147608E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.311751E+09 0.155102E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.321296E+09 0.160268E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.306626E+09 0.152165E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.302035E+09 0.147015E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.265611E+09 0.124671E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.257897E+09 0.110840E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.337433E+10 0.157941E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.225122E+09 0.967407E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.321296E+09 0.160268E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ_MRI_CONTROL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.532836E+09 0.337930E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.488551E+09 0.321111E+10 0.00 0.00 0.00 181323.10 0.00 0.00
March 0.567686E+09 0.380135E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.547990E+09 0.385709E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.584958E+09 0.445859E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.582781E+09 0.465985E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.585937E+09 0.466292E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.604357E+09 0.489144E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.571641E+09 0.448758E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.572590E+09 0.435602E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.537072E+09 0.392944E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.540265E+09 0.346820E+10 0.00 0.00 0.00 71143.84 0.00 0.00
                 
Annual Sum or Average 0.671666E+10 0.491629E+11 0.00 0.00 0.00 252466.94 0.00 0.00
Minimum of Months 0.488551E+09 0.321111E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.604357E+09 0.489144E+10 0.00 0.00 0.00 181323.10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ_MRI

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.135260E+10 0.907536E+10 0.00 0.00 0.00 987885.45 0.00 0.00
February 0.123306E+10 0.850843E+10 0.00 0.00 0.00 1591074.25 0.00 0.00
March 0.141381E+10 0.994873E+10 0.00 0.00 0.00 355753.36 0.00 0.00
April 0.134509E+10 0.982933E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140861E+10 0.110642E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139023E+10 0.114386E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.139049E+10 0.113668E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144116E+10 0.120283E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.136307E+10 0.110324E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138201E+10 0.108633E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132579E+10 0.100682E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.135780E+10 0.919071E+10 0.00 0.00 0.00 943468.21 0.00 0.00
                 
Annual Sum or Average 0.164037E+11 0.124414E+12 0.00 0.00 0.00 3878181.26 0.00 0.00
Minimum of Months 0.123306E+10 0.850843E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144116E+10 0.120283E+11 0.00 0.00 0.00 1591074.25 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ_OR_1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.192961E+10 0.145064E+11 44951.23 0.00 0.00 12477606.08 0.00 0.00
February 0.176868E+10 0.143195E+11 1809375.53 0.00 0.00 7377192.56 0.00 0.00
March 0.203553E+10 0.168083E+11 0.00 0.00 0.00 8209081.87 0.00 0.00
April 0.196608E+10 0.180153E+11 1166.69 0.00 0.00 1457608.27 0.00 0.00
May 0.208770E+10 0.217552E+11 0.00 0.00 0.00 483203.48 0.00 0.00
June 0.208550E+10 0.234461E+11 0.00 0.00 0.00 404978.16 0.00 0.00
July 0.210816E+10 0.236129E+11 0.00 0.00 0.00 101258.28 0.00 0.00
August 0.217631E+10 0.247646E+11 0.00 0.00 0.00 478275.91 0.00 0.00
September 0.207287E+10 0.230017E+11 0.00 0.00 0.00 652360.11 0.00 0.00
October 0.208382E+10 0.218564E+11 0.00 0.00 0.00 592548.36 0.00 0.00
November 0.194588E+10 0.189403E+11 53002.80 0.00 0.00 2292182.93 0.00 0.00
December 0.195240E+10 0.151781E+11 0.00 0.00 0.00 7762303.13 0.00 0.00
                 
Annual Sum or Average 0.242125E+11 0.236205E+12 1908496.25 0.00 0.00 42288599.15 0.00 0.00
Minimum of Months 0.176868E+10 0.143195E+11 0.00 0.00 0.00 101258.28 0.00 0.00
Maximum of Months 0.217631E+10 0.247646E+11 1809375.53 0.00 0.00 12477606.08 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ_OR_2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.199638E+10 0.145619E+11 45345.71 0.00 0.00 13632516.66 0.00 0.00
February 0.183026E+10 0.144427E+11 983122.68 0.00 0.00 8523279.31 0.00 0.00
March 0.211399E+10 0.171573E+11 0.00 0.00 0.00 9550554.93 0.00 0.00
April 0.203993E+10 0.185045E+11 0.00 0.00 0.00 1762844.09 0.00 0.00
May 0.215203E+10 0.222900E+11 0.00 0.00 0.00 1201216.12 0.00 0.00
June 0.214440E+10 0.240653E+11 0.00 0.00 0.00 1104014.46 0.00 0.00
July 0.216241E+10 0.242082E+11 0.00 0.00 0.00 1338112.82 0.00 0.00
August 0.222708E+10 0.253311E+11 0.00 0.00 0.00 648959.37 0.00 0.00
September 0.210865E+10 0.233290E+11 0.00 0.00 0.00 1067515.11 0.00 0.00
October 0.211656E+10 0.219443E+11 0.00 0.00 0.00 1947817.70 0.00 0.00
November 0.199114E+10 0.189692E+11 29671.80 0.00 0.00 3645173.12 0.00 0.00
December 0.201007E+10 0.151484E+11 0.00 0.00 0.00 9147904.38 0.00 0.00
                 
Annual Sum or Average 0.248929E+11 0.239952E+12 1058140.19 0.00 0.00 53569908.07 0.00 0.00
Minimum of Months 0.183026E+10 0.144427E+11 0.00 0.00 0.00 648959.37 0.00 0.00
Maximum of Months 0.222708E+10 0.253311E+11 983122.68 0.00 0.00 13632516.66 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ_OR_3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.198674E+10 0.141936E+11 59471.97 0.00 0.00 14738203.27 0.00 0.00
February 0.181481E+10 0.139118E+11 248932.12 0.00 0.00 10149274.82 0.00 0.00
March 0.208344E+10 0.163426E+11 0.00 0.00 0.00 10561903.33 0.00 0.00
April 0.197052E+10 0.171892E+11 0.00 0.00 0.00 3336411.27 0.00 0.00
May 0.205074E+10 0.205230E+11 0.00 0.00 0.00 3966755.99 0.00 0.00
June 0.202386E+10 0.222528E+11 0.00 0.00 0.00 2326946.93 0.00 0.00
July 0.201223E+10 0.223601E+11 0.00 0.00 0.00 4399790.19 0.00 0.00
August 0.209673E+10 0.236061E+11 0.00 0.00 0.00 2491916.02 0.00 0.00
September 0.197475E+10 0.214629E+11 0.00 0.00 0.00 3202274.89 0.00 0.00
October 0.200400E+10 0.202515E+11 11101.20 0.00 0.00 3754514.20 0.00 0.00
November 0.193570E+10 0.179276E+11 0.00 0.00 0.00 5005735.46 0.00 0.00
December 0.199384E+10 0.147783E+11 0.00 0.00 0.00 10379277.49 0.00 0.00
                 
Annual Sum or Average 0.239474E+11 0.224800E+12 319505.28 0.00 0.00 74313003.87 0.00 0.00
Minimum of Months 0.181481E+10 0.139118E+11 0.00 0.00 0.00 2326946.93 0.00 0.00
Maximum of Months 0.209673E+10 0.236061E+11 248932.12 0.00 0.00 14738203.27 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ_XRAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.279276E+10 0.167659E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.255137E+10 0.158539E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.293517E+10 0.186412E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.276773E+10 0.185137E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.292075E+10 0.215804E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.291551E+10 0.230358E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.288081E+10 0.227365E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.301997E+10 0.242702E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.283189E+10 0.219777E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.284119E+10 0.210626E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.272911E+10 0.193104E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.279706E+10 0.169758E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.339833E+11 0.240724E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.255137E+10 0.158539E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.301997E+10 0.242702E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AHU-1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.613489E+10 0.772202E+10 0.00 0.00 0.191246E+11 0.00 0.00 0.00 0.149397E+09 0.00 0.00 0.00
February 0.580143E+10 0.710299E+10 0.00 0.00 0.193210E+11 0.00 0.00 0.00 0.208063E+09 0.00 0.00 0.00
March 0.688813E+10 0.848899E+10 0.00 0.00 0.234376E+11 0.00 0.00 0.00 0.195543E+09 0.00 0.00 0.00
April 0.694279E+10 0.861889E+10 0.00 0.00 0.266276E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.790020E+10 0.982853E+10 0.00 0.00 0.355665E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.807049E+10 0.102430E+11 0.00 0.00 0.399474E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.822360E+10 0.105046E+11 0.00 0.00 0.423110E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.848201E+10 0.104164E+11 0.00 0.00 0.431135E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.790651E+10 0.978509E+10 0.00 0.00 0.394806E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.764488E+10 0.894615E+10 0.00 0.00 0.352243E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.681398E+10 0.757191E+10 0.00 0.00 0.278818E+11 0.00 0.00 0.00 10149618.91 0.00 0.00 0.00
December 0.623983E+10 0.783691E+10 0.00 0.00 0.208045E+11 0.00 0.00 0.00 75725654.65 0.00 0.00 0.00
                         
Annual Sum or Average 0.870487E+11 0.107066E+12 0.00 0.00 0.372841E+12 0.00 0.00 0.00 0.638878E+09 0.00 0.00 0.00
Minimum of Months 0.580143E+10 0.710299E+10 0.00 0.00 0.191246E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.848201E+10 0.105046E+11 0.00 0.00 0.431135E+11 0.00 0.00 0.00 0.208063E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AHU-2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.931759E+10 0.117413E+10 0.00 0.00 0.163338E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.903028E+10 0.101045E+10 0.00 0.00 0.167897E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.109958E+11 0.645566E+09 0.00 0.00 0.201547E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.112662E+11 0.264895E+09 0.00 0.00 0.230857E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.129086E+11 0.312898E+09 0.00 0.00 0.311352E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134142E+11 0.405515E+09 0.00 0.00 0.356401E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.130145E+11 0.712348E+09 0.00 0.00 0.374143E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.135877E+11 0.515160E+09 0.00 0.00 0.381780E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.126654E+11 0.533237E+09 0.00 0.00 0.347023E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.118542E+11 0.499614E+09 0.00 0.00 0.306060E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.102429E+11 0.485078E+09 0.00 0.00 0.238650E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.947606E+10 0.112276E+10 0.00 0.00 0.174300E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.137773E+12 0.768165E+10 0.00 0.00 0.325335E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.903028E+10 0.264895E+09 0.00 0.00 0.163338E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135877E+11 0.117413E+10 0.00 0.00 0.381780E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AHU-3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.101215E+11 0.558274E+09 0.00 0.00 0.184190E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.100887E+11 0.535578E+09 0.00 0.00 0.193083E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.123782E+11 0.401706E+09 0.00 0.00 0.237267E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.126252E+11 0.304248E+09 0.00 0.00 0.271976E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.138350E+11 0.204140E+09 0.00 0.00 0.346542E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139142E+11 0.164386E+09 0.00 0.00 0.380534E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.139325E+11 0.183547E+09 0.00 0.00 0.399723E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.142842E+11 0.223731E+09 0.00 0.00 0.404410E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.132162E+11 0.226971E+09 0.00 0.00 0.368137E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.129316E+11 0.302477E+09 0.00 0.00 0.336271E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.116998E+11 0.324274E+09 0.00 0.00 0.270806E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.103960E+11 0.570673E+09 0.00 0.00 0.199660E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.149423E+12 0.400000E+10 0.00 0.00 0.359260E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.100887E+11 0.164386E+09 0.00 0.00 0.184190E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.142842E+11 0.570673E+09 0.00 0.00 0.404410E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ_CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.778550E+09 0.00 0.00 0.00 0.173170E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.714832E+09 0.00 0.00 4891725.88 0.180997E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.836133E+09 0.00 0.00 25569.14 0.212623E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.790042E+09 0.00 0.00 0.00 0.233931E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.850114E+09 0.00 0.00 0.00 0.302731E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.869325E+09 0.00 0.00 0.00 0.324418E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.861139E+09 0.00 0.00 0.00 0.323546E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.920261E+09 0.00 0.00 0.00 0.346079E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.870191E+09 0.00 0.00 0.00 0.318567E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.865454E+09 0.00 0.00 0.00 0.305513E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.796170E+09 0.00 0.00 0.00 0.257068E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.795516E+09 0.00 0.00 141.82 0.185120E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.994773E+10 0.00 0.00 4917436.83 0.316376E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.714832E+09 0.00 0.00 0.00 0.173170E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.920261E+09 0.00 0.00 4891725.88 0.346079E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ_ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.243711E+09 0.00 0.00 0.00 0.288134E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.225122E+09 0.00 0.00 0.00 0.278387E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.267038E+09 0.00 0.00 0.00 0.332874E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.268440E+09 0.00 0.00 0.00 0.362220E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.301428E+09 0.00 0.00 0.00 0.443657E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.303375E+09 0.00 0.00 0.00 0.455119E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.311751E+09 0.00 0.00 0.00 0.487736E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.321296E+09 0.00 0.00 0.00 0.498776E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.306626E+09 0.00 0.00 0.00 0.469703E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.302035E+09 0.00 0.00 0.00 0.446356E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.265611E+09 0.00 0.00 0.00 0.366744E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.257897E+09 0.00 0.00 0.00 0.317535E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.337433E+10 0.00 0.00 0.00 0.474724E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.225122E+09 0.00 0.00 0.00 0.278387E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.321296E+09 0.00 0.00 0.00 0.498776E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ_MRI_CONTROL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.532836E+09 0.00 0.00 0.00 0.948497E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.488551E+09 0.00 0.00 0.00 0.915294E+09 0.00 0.00 0.00 182139.31 0.00 0.00 0.00
March 0.567686E+09 0.00 0.00 0.00 0.107999E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.547990E+09 0.00 0.00 0.00 0.112672E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.584958E+09 0.00 0.00 0.00 0.134884E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.582781E+09 0.00 0.00 0.00 0.142535E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.585937E+09 0.00 0.00 0.00 0.145664E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.604357E+09 0.00 0.00 0.00 0.151113E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.571641E+09 0.00 0.00 0.00 0.137596E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.572590E+09 0.00 0.00 0.00 0.131536E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.537072E+09 0.00 0.00 0.00 0.114736E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.540265E+09 0.00 0.00 0.00 0.978834E+09 0.00 0.00 0.00 71464.08 0.00 0.00 0.00
                         
Annual Sum or Average 0.671666E+10 0.00 0.00 0.00 0.146300E+11 0.00 0.00 0.00 253603.39 0.00 0.00 0.00
Minimum of Months 0.488551E+09 0.00 0.00 0.00 0.915294E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.604357E+09 0.00 0.00 0.00 0.151113E+10 0.00 0.00 0.00 182139.31 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ_MRI

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.135260E+10 0.00 0.00 0.00 0.254927E+10 0.00 0.00 0.00 992332.32 0.00 0.00 0.00
February 0.123306E+10 0.00 0.00 0.00 0.242593E+10 0.00 0.00 0.00 1598236.32 0.00 0.00 0.00
March 0.141381E+10 0.00 0.00 0.00 0.282490E+10 0.00 0.00 0.00 357354.75 0.00 0.00 0.00
April 0.134509E+10 0.00 0.00 0.00 0.287011E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140861E+10 0.00 0.00 0.00 0.334419E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139023E+10 0.00 0.00 0.00 0.349532E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.139049E+10 0.00 0.00 0.00 0.354533E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144116E+10 0.00 0.00 0.00 0.371113E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.136307E+10 0.00 0.00 0.00 0.337870E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138201E+10 0.00 0.00 0.00 0.327813E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132579E+10 0.00 0.00 0.00 0.293854E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.135780E+10 0.00 0.00 0.00 0.259373E+10 0.00 0.00 0.00 947715.15 0.00 0.00 0.00
                         
Annual Sum or Average 0.164037E+11 0.00 0.00 0.00 0.369553E+11 0.00 0.00 0.00 3895638.53 0.00 0.00 0.00
Minimum of Months 0.123306E+10 0.00 0.00 0.00 0.242593E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144116E+10 0.00 0.00 0.00 0.371113E+10 0.00 0.00 0.00 1598236.32 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ_OR_1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.192961E+10 0.00 0.00 14312.93 0.409218E+10 0.00 0.00 0.00 12538653.61 0.00 0.00 0.00
February 0.176868E+10 0.00 0.00 646301.04 0.408856E+10 0.00 0.00 0.00 7412337.92 0.00 0.00 0.00
March 0.203553E+10 0.00 0.00 0.00 0.479520E+10 0.00 0.00 0.00 8246452.02 0.00 0.00 0.00
April 0.196608E+10 0.00 0.00 365.39 0.525440E+10 0.00 0.00 0.00 1465305.73 0.00 0.00 0.00
May 0.208770E+10 0.00 0.00 0.00 0.656151E+10 0.00 0.00 0.00 485530.79 0.00 0.00 0.00
June 0.208550E+10 0.00 0.00 0.00 0.711343E+10 0.00 0.00 0.00 406805.15 0.00 0.00 0.00
July 0.210816E+10 0.00 0.00 0.00 0.728974E+10 0.00 0.00 0.00 101714.08 0.00 0.00 0.00
August 0.217631E+10 0.00 0.00 0.00 0.756370E+10 0.00 0.00 0.00 480616.98 0.00 0.00 0.00
September 0.207287E+10 0.00 0.00 0.00 0.699147E+10 0.00 0.00 0.00 656330.92 0.00 0.00 0.00
October 0.208382E+10 0.00 0.00 0.00 0.657134E+10 0.00 0.00 0.00 595369.42 0.00 0.00 0.00
November 0.194588E+10 0.00 0.00 16558.15 0.551767E+10 0.00 0.00 0.00 2303798.26 0.00 0.00 0.00
December 0.195240E+10 0.00 0.00 0.00 0.429473E+10 0.00 0.00 0.00 7800288.31 0.00 0.00 0.00
                         
Annual Sum or Average 0.242125E+11 0.00 0.00 677537.51 0.701339E+11 0.00 0.00 0.00 42493203.21 0.00 0.00 0.00
Minimum of Months 0.176868E+10 0.00 0.00 0.00 0.408856E+10 0.00 0.00 0.00 101714.08 0.00 0.00 0.00
Maximum of Months 0.217631E+10 0.00 0.00 646301.04 0.756370E+10 0.00 0.00 0.00 12538653.61 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ_OR_2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.199638E+10 0.00 0.00 14330.45 0.411018E+10 0.00 0.00 0.00 13700212.69 0.00 0.00 0.00
February 0.183026E+10 0.00 0.00 348241.50 0.411992E+10 0.00 0.00 0.00 8564653.42 0.00 0.00 0.00
March 0.211399E+10 0.00 0.00 0.00 0.489034E+10 0.00 0.00 0.00 9597195.36 0.00 0.00 0.00
April 0.203993E+10 0.00 0.00 0.00 0.539151E+10 0.00 0.00 0.00 1774065.30 0.00 0.00 0.00
May 0.215203E+10 0.00 0.00 0.00 0.671807E+10 0.00 0.00 0.00 1208617.05 0.00 0.00 0.00
June 0.214440E+10 0.00 0.00 0.00 0.729862E+10 0.00 0.00 0.00 1112788.13 0.00 0.00 0.00
July 0.216241E+10 0.00 0.00 0.00 0.747383E+10 0.00 0.00 0.00 1345055.86 0.00 0.00 0.00
August 0.222708E+10 0.00 0.00 0.00 0.773652E+10 0.00 0.00 0.00 653007.38 0.00 0.00 0.00
September 0.210865E+10 0.00 0.00 0.00 0.708849E+10 0.00 0.00 0.00 1074206.73 0.00 0.00 0.00
October 0.211656E+10 0.00 0.00 0.00 0.659074E+10 0.00 0.00 0.00 1962061.27 0.00 0.00 0.00
November 0.199114E+10 0.00 0.00 9316.01 0.551649E+10 0.00 0.00 0.00 3670888.71 0.00 0.00 0.00
December 0.201007E+10 0.00 0.00 0.00 0.428548E+10 0.00 0.00 0.00 9192032.61 0.00 0.00 0.00
                         
Annual Sum or Average 0.248929E+11 0.00 0.00 371887.96 0.712202E+11 0.00 0.00 0.00 53854784.52 0.00 0.00 0.00
Minimum of Months 0.183026E+10 0.00 0.00 0.00 0.411018E+10 0.00 0.00 0.00 653007.38 0.00 0.00 0.00
Maximum of Months 0.222708E+10 0.00 0.00 348241.50 0.773652E+10 0.00 0.00 0.00 13700212.69 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ_OR_3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.198674E+10 0.00 0.00 17315.90 0.400654E+10 0.00 0.00 0.00 14812266.60 0.00 0.00 0.00
February 0.181481E+10 0.00 0.00 85410.16 0.396576E+10 0.00 0.00 0.00 10207130.90 0.00 0.00 0.00
March 0.208344E+10 0.00 0.00 0.00 0.465148E+10 0.00 0.00 0.00 10615115.06 0.00 0.00 0.00
April 0.197052E+10 0.00 0.00 0.00 0.499040E+10 0.00 0.00 0.00 3360540.14 0.00 0.00 0.00
May 0.205074E+10 0.00 0.00 0.00 0.615711E+10 0.00 0.00 0.00 4000261.04 0.00 0.00 0.00
June 0.202386E+10 0.00 0.00 0.00 0.672420E+10 0.00 0.00 0.00 2342979.65 0.00 0.00 0.00
July 0.201223E+10 0.00 0.00 0.00 0.689113E+10 0.00 0.00 0.00 4431903.85 0.00 0.00 0.00
August 0.209673E+10 0.00 0.00 0.00 0.719334E+10 0.00 0.00 0.00 2507216.56 0.00 0.00 0.00
September 0.197475E+10 0.00 0.00 0.00 0.649725E+10 0.00 0.00 0.00 3225704.97 0.00 0.00 0.00
October 0.200400E+10 0.00 0.00 3143.82 0.605876E+10 0.00 0.00 0.00 3782741.85 0.00 0.00 0.00
November 0.193570E+10 0.00 0.00 0.00 0.519886E+10 0.00 0.00 0.00 5039840.20 0.00 0.00 0.00
December 0.199384E+10 0.00 0.00 0.00 0.417509E+10 0.00 0.00 0.00 10433959.92 0.00 0.00 0.00
                         
Annual Sum or Average 0.239474E+11 0.00 0.00 105869.88 0.665099E+11 0.00 0.00 0.00 74759660.74 0.00 0.00 0.00
Minimum of Months 0.181481E+10 0.00 0.00 0.00 0.396576E+10 0.00 0.00 0.00 2342979.65 0.00 0.00 0.00
Maximum of Months 0.209673E+10 0.00 0.00 85410.16 0.719334E+10 0.00 0.00 0.00 14812266.60 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ_XRAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.279276E+10 0.00 0.00 0.00 0.414890E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.255137E+10 0.00 0.00 0.00 0.397308E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.293517E+10 0.00 0.00 0.00 0.465342E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.276773E+10 0.00 0.00 0.00 0.473458E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.292075E+10 0.00 0.00 0.00 0.565581E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.291551E+10 0.00 0.00 0.00 0.606541E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.288081E+10 0.00 0.00 0.00 0.611568E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.301997E+10 0.00 0.00 0.00 0.645002E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.283189E+10 0.00 0.00 0.00 0.581016E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.284119E+10 0.00 0.00 0.00 0.551496E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.272911E+10 0.00 0.00 0.00 0.491334E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.279706E+10 0.00 0.00 0.00 0.421417E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.339833E+11 0.00 0.00 0.00 0.622495E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.255137E+10 0.00 0.00 0.00 0.397308E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.301997E+10 0.00 0.00 0.00 0.645002E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 26532967.57 0.197955E+09 699748.68 268309.47 0.149742E+09 228620.39 55463544.93 1757.59 1.50
February 25565588.43 0.227300E+09 716968.31 123672.84 0.165919E+09 355611.45 23261833.01 1935.51 1.57
March 19221746.79 0.289579E+09 1077060.53 123634.14 0.243953E+09 240034.73 47194142.25 1841.01 1.65
April 891000.18 0.372378E+09 1868863.58 28627.03 0.366600E+09 13240.40 3588884.11 4887.04 1.75
May 0.00 0.597554E+09 3095125.70 0.00 0.662256E+09 0.00 0.00 7834.66 1.90
June 0.00 0.745036E+09 3516135.44 0.00 0.864781E+09 0.00 0.00 12361.11 2.00
July 0.00 0.777960E+09 3836996.51 0.00 0.984487E+09 0.00 0.00 13133.31 2.02
August 0.00 0.828724E+09 2941006.46 0.00 0.937267E+09 0.00 0.00 13431.15 2.03
September 0.00 0.727437E+09 3464572.57 0.00 0.892348E+09 0.00 0.00 8214.00 2.03
October 0.00 0.612430E+09 2362835.77 0.00 0.700674E+09 0.00 0.00 5249.23 1.89
November 5613667.49 0.459147E+09 1659919.60 15694.29 0.426286E+09 64474.44 3946337.34 2224.60 1.70
December 18905570.96 0.223334E+09 662287.10 229550.19 0.248498E+09 217822.60 41670975.43 2725.81 1.55
                   
Annual Sum or Average 96730541.42 0.605884E+10 25901520.24 789487.95 0.664281E+10 1119804.02 0.175126E+09 75595.01 1.80
Minimum of Months 0.00 0.197955E+09 662287.10 0.00 0.149742E+09 0.00 0.00 1757.59 1.50
Maximum of Months 26532967.57 0.828724E+09 3836996.51 268309.47 0.984487E+09 355611.45 55463544.93 13431.15 2.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4878114.58 9803498.98 0.00 2205.99 14140978.79 3935.93 714153.28 0.00 0.20
February 2424645.32 15329963.31 381.31 3212.82 12344312.43 7283.45 912424.04 113.54 0.21
March 3290447.79 22188582.29 0.00 5390.41 17023011.65 0.00 1243611.55 0.00 0.23
April 56911.60 34161819.94 0.00 8889.52 23752290.29 0.00 295134.97 0.00 0.26
May 0.00 59811322.03 0.00 0.00 43279695.46 0.00 0.00 0.00 0.30
June 0.00 77842166.19 0.00 0.00 56360522.00 0.00 0.00 0.00 0.32
July 0.00 81198838.94 0.00 0.00 64534553.83 0.00 0.00 0.00 0.32
August 0.00 83634464.22 0.00 0.00 61423523.13 0.00 0.00 0.00 0.32
September 0.00 67780215.80 0.00 0.00 59057039.57 0.00 0.00 0.00 0.31
October 0.00 51301966.97 0.00 0.00 46632342.55 0.00 0.00 0.00 0.27
November 654002.14 35716196.71 0.00 46.88 28995414.80 0.00 169.16 0.00 0.24
December 3013223.64 12717222.56 0.00 4385.38 20350237.54 0.00 1123702.05 0.00 0.21
                   
Annual Sum or Average 14317345.08 0.551486E+09 381.31 24131.00 0.447894E+09 11219.38 4289195.04 113.54 0.27
Minimum of Months 0.00 9803498.98 0.00 0.00 12344312.43 0.00 0.00 0.00 0.20
Maximum of Months 4878114.58 83634464.22 381.31 8889.52 64534553.83 7283.45 1243611.55 113.54 0.32



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 CAFE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 80220851.82 0.107425E+10 0.00 3959229.55 5052422.71 0.00 0.967414E+09 0.00 2.48
February 58953155.14 0.129990E+10 0.00 2647218.97 5810441.55 536623.73 0.488841E+09 0.00 2.52
March 35002288.96 0.170915E+10 0.00 2731985.03 7850172.88 0.00 0.714065E+09 0.00 2.67
April 2192984.38 0.229638E+10 0.00 962674.21 11164952.81 0.00 0.104734E+09 0.00 2.56
May 0.00 0.393805E+10 0.00 8414.00 14439891.16 0.00 120422.02 0.00 2.59
June 0.00 0.487505E+10 0.00 0.00 12995838.30 0.00 0.00 0.00 2.68
July 0.00 0.499477E+10 0.00 1395.68 13657846.83 0.00 18415.57 0.00 2.50
August 0.00 0.520316E+10 0.00 0.00 13774656.07 0.00 0.00 0.00 2.70
September 0.00 0.466131E+10 0.00 0.00 11925584.30 0.00 0.00 0.00 2.59
October 0.00 0.389338E+10 0.00 4319.25 12574282.86 0.00 204013.94 0.00 2.50
November 6804360.73 0.281102E+10 0.00 672120.98 10895229.81 0.00 0.101437E+09 0.00 2.47
December 49504422.47 0.127229E+10 0.00 3750202.32 7211498.87 0.00 0.778450E+09 0.00 2.48
                   
Annual Sum or Average 0.232678E+09 0.380287E+11 0.00 14737559.98 0.127353E+09 536623.73 0.315528E+10 0.00 2.56
Minimum of Months 0.00 0.107425E+10 0.00 0.00 5052422.71 0.00 0.00 0.00 2.47
Maximum of Months 80220851.82 0.520316E+10 0.00 3959229.55 14439891.16 536623.73 0.967414E+09 0.00 2.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 CLEAN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 28420152.20 0.219172E+09 433967.10 204785.81 0.169353E+09 180538.96 63292200.81 1115.27 1.44
February 23697800.92 0.252056E+09 334121.09 86073.51 0.187409E+09 275951.86 30987374.65 1220.86 1.50
March 19696752.90 0.322550E+09 509352.23 139270.09 0.273793E+09 158181.80 54560111.66 571.77 1.58
April 974262.43 0.418562E+09 1277475.03 29489.81 0.407263E+09 14781.91 4029659.04 2095.43 1.67
May 0.00 0.663488E+09 4623270.04 0.00 0.741828E+09 0.00 0.00 7339.61 1.82
June 0.00 0.809971E+09 6736823.73 0.00 0.984455E+09 0.00 0.00 14855.68 1.91
July 0.00 0.838900E+09 8366218.87 0.00 0.112465E+10 0.00 0.00 16957.24 1.93
August 0.00 0.897930E+09 6696119.58 0.00 0.107025E+10 0.00 0.00 16994.84 1.94
September 0.00 0.770715E+09 9134939.50 0.00 0.103238E+10 0.00 0.00 13088.08 1.94
October 0.00 0.666107E+09 4651032.49 0.00 0.797859E+09 0.00 0.00 7848.05 1.81
November 6074697.22 0.505289E+09 2150100.65 16050.61 0.482933E+09 37836.04 4633939.46 2822.08 1.63
December 19664713.51 0.247114E+09 801290.30 172134.15 0.279589E+09 139186.82 48152547.43 1957.37 1.48
                   
Annual Sum or Average 98528379.19 0.661185E+10 45714710.62 647803.97 0.755177E+10 806477.39 0.205656E+09 86866.28 1.72
Minimum of Months 0.00 0.219172E+09 334121.09 0.00 0.169353E+09 0.00 0.00 571.77 1.44
Maximum of Months 28420152.20 0.897930E+09 9134939.50 204785.81 0.112465E+10 275951.86 63292200.81 16994.84 1.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 37098798.58 0.267789E+09 1092116.68 206928.46 0.217872E+09 225931.89 77722143.61 3232.70 1.37
February 32394650.10 0.306120E+09 1178093.08 82977.09 0.243079E+09 345334.45 36064760.39 3392.21 1.44
March 25388047.20 0.398439E+09 1510353.36 139918.43 0.346968E+09 197953.46 67573593.70 2994.41 1.51
April 1244840.27 0.508583E+09 2670945.64 30261.40 0.523803E+09 18498.52 5023860.52 7140.88 1.60
May 0.00 0.800417E+09 6073917.99 0.00 0.957943E+09 0.00 0.00 15213.28 1.74
June 0.00 0.995081E+09 6510069.09 0.00 0.125243E+10 0.00 0.00 24327.65 1.83
July 0.00 0.103222E+10 9623095.85 0.00 0.142587E+10 0.00 0.00 25724.97 1.84
August 0.00 0.111501E+10 7750527.33 0.00 0.134866E+10 0.00 0.00 28295.98 1.86
September 0.00 0.955980E+09 9689713.22 0.00 0.130221E+10 0.00 0.00 21518.34 1.85
October 0.00 0.801825E+09 6012772.66 0.00 0.103003E+10 0.00 0.00 16900.73 1.73
November 7885027.55 0.622176E+09 2903348.84 12853.63 0.614298E+09 47349.15 5523314.90 7254.65 1.55
December 25138545.97 0.297999E+09 1315828.27 177733.74 0.360817E+09 174182.57 59767693.16 5457.77 1.42
                   
Annual Sum or Average 0.129150E+09 0.810163E+10 56330782.00 650672.74 0.962397E+10 1009250.04 0.251675E+09 161453.58 1.65
Minimum of Months 0.00 0.267789E+09 1092116.68 0.00 0.217872E+09 0.00 0.00 2994.41 1.37
Maximum of Months 37098798.58 0.111501E+10 9689713.22 206928.46 0.142587E+10 345334.45 77722143.61 28295.98 1.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2704512.29 60000230.58 0.00 290606.86 23209929.40 0.00 22161849.82 0.00 0.34
February 2624201.24 72231120.97 0.00 143559.25 25054046.01 0.00 9737261.16 0.00 0.34
March 1650076.81 88879653.59 0.00 209077.71 37376753.94 0.00 18147791.81 0.00 0.36
April 90538.48 0.106345E+09 0.00 36274.32 56431475.17 0.00 1067826.95 0.00 0.34
May 0.00 0.155747E+09 0.00 0.00 0.106746E+09 0.00 0.00 0.00 0.34
June 0.00 0.185040E+09 0.00 0.00 0.140139E+09 0.00 0.00 0.00 0.35
July 0.00 0.179614E+09 0.00 0.00 0.160675E+09 0.00 0.00 0.00 0.33
August 0.00 0.201963E+09 0.00 0.00 0.152629E+09 0.00 0.00 0.00 0.35
September 0.00 0.170895E+09 0.00 0.00 0.146681E+09 0.00 0.00 0.00 0.34
October 0.00 0.151799E+09 0.00 0.00 0.114897E+09 0.00 0.00 0.00 0.33
November 575564.71 0.131549E+09 0.00 33267.93 68218311.82 0.00 1819287.09 0.00 0.34
December 1767437.99 65942814.72 0.00 222306.55 39329606.16 0.00 16248159.27 0.00 0.34
                   
Annual Sum or Average 9412331.52 0.157000E+10 0.00 935092.63 0.107139E+10 0.00 69182176.10 0.00 0.34
Minimum of Months 0.00 60000230.58 0.00 0.00 23209929.40 0.00 0.00 0.00 0.33
Maximum of Months 2704512.29 0.201963E+09 0.00 290606.86 0.160675E+09 0.00 22161849.82 0.00 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 3286434.17 34583544.49 0.00 45210.86 12850810.00 5186.24 4472952.60 0.00 0.43
February 2500714.16 42706928.44 0.00 25767.52 14021601.17 604862.63 1393250.04 0.00 0.50
March 3804905.94 55900444.91 0.00 25643.92 20384773.00 70271.12 2009222.70 0.00 0.52
April 76966.02 78413449.40 0.00 15639.06 29956722.73 0.00 478001.51 0.00 0.60
May 0.00 0.154863E+09 0.00 0.00 51879795.10 0.00 0.00 0.00 0.75
June 0.00 0.213541E+09 0.00 0.00 64968570.44 0.00 0.00 0.00 0.84
July 0.00 0.242633E+09 0.00 0.00 67315368.59 0.00 0.00 0.00 0.84
August 0.00 0.242331E+09 0.00 0.00 67713195.44 0.00 0.00 0.00 0.86
September 0.00 0.208824E+09 0.00 0.00 64892515.88 0.00 0.00 0.00 0.82
October 0.00 0.153802E+09 0.00 0.00 55476486.62 0.00 0.00 0.00 0.73
November 765545.30 0.103208E+09 0.00 2563.28 35361317.67 0.00 118612.60 0.00 0.62
December 2410773.30 42678402.11 0.00 46481.63 21200943.23 9959.26 3390047.19 0.00 0.47
                   
Annual Sum or Average 12845338.88 0.157349E+10 0.00 161306.27 0.506022E+09 690279.25 11862086.65 0.00 0.67
Minimum of Months 0.00 34583544.49 0.00 0.00 12850810.00 0.00 0.00 0.00 0.43
Maximum of Months 3804905.94 0.242633E+09 0.00 46481.63 67713195.44 604862.63 4472952.60 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 3213124.29 0.126742E+09 0.00 469715.47 26032175.03 0.00 35428636.29 0.00 0.75
February 3260553.44 0.148179E+09 0.00 254424.47 28781325.80 0.00 15226460.14 0.00 0.78
March 1938336.02 0.197814E+09 0.00 354906.56 40776945.17 0.00 30239901.62 0.00 0.84
April 80588.01 0.267688E+09 0.00 88092.66 59217087.24 0.00 2461498.68 0.00 0.87
May 0.00 0.455563E+09 0.00 0.00 0.103079E+09 0.00 0.00 0.00 0.94
June 0.00 0.594738E+09 0.00 0.00 0.126880E+09 0.00 0.00 0.00 1.00
July 0.00 0.633730E+09 0.00 0.00 0.140552E+09 0.00 0.00 0.00 0.97
August 0.00 0.663776E+09 0.00 0.00 0.136583E+09 0.00 0.00 0.00 1.02
September 0.00 0.571656E+09 0.00 0.00 0.136378E+09 0.00 0.00 0.00 0.98
October 0.00 0.465038E+09 0.00 0.00 0.110670E+09 0.00 0.00 0.00 0.93
November 635199.38 0.327652E+09 0.00 57947.82 69735509.20 0.00 2986152.58 0.00 0.85
December 2171986.13 0.143504E+09 0.00 368537.13 44212934.12 0.00 26342602.24 0.00 0.74
                   
Annual Sum or Average 11299787.28 0.459608E+10 0.00 1593624.10 0.102290E+10 0.00 0.112685E+09 0.00 0.89
Minimum of Months 0.00 0.126742E+09 0.00 0.00 26032175.03 0.00 0.00 0.00 0.74
Maximum of Months 3260553.44 0.663776E+09 0.00 469715.47 0.140552E+09 0.00 35428636.29 0.00 1.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1317213.29 32811062.29 0.00 159358.30 11310074.94 0.00 11913162.39 0.00 0.42
February 1282948.47 39140185.59 0.00 80238.84 12265793.57 0.00 5388108.29 0.00 0.43
March 799710.96 49546285.85 0.00 115227.36 17799948.11 0.00 9922103.34 0.00 0.45
April 40586.10 60621264.03 0.00 21181.52 26922601.64 0.00 614707.65 0.00 0.42
May 0.00 91347351.57 0.00 0.00 50561340.24 0.00 0.00 0.00 0.43
June 0.00 0.109721E+09 0.00 0.00 66004502.37 0.00 0.00 0.00 0.44
July 0.00 0.106658E+09 0.00 0.00 77147149.09 0.00 0.00 0.00 0.42
August 0.00 0.119201E+09 0.00 0.00 72499423.75 0.00 0.00 0.00 0.44
September 0.00 0.100544E+09 0.00 0.00 70275235.58 0.00 0.00 0.00 0.43
October 0.00 89525662.37 0.00 0.00 54506290.43 0.00 0.00 0.00 0.42
November 276837.27 74263532.70 0.00 20126.66 32334071.38 0.00 1088636.50 0.00 0.42
December 863181.15 36648226.49 0.00 121207.14 18889165.55 0.00 8771397.72 0.00 0.42
                   
Annual Sum or Average 4580477.24 0.910028E+09 0.00 517339.83 0.510516E+09 0.00 37698115.90 0.00 0.43
Minimum of Months 0.00 32811062.29 0.00 0.00 11310074.94 0.00 0.00 0.00 0.42
Maximum of Months 1317213.29 0.119201E+09 0.00 159358.30 77147149.09 0.00 11913162.39 0.00 0.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 IT HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 3678348.40 43930391.82 0.00 154464.82 22106764.68 0.00 12732145.97 0.00 0.22
February 3559413.34 55523941.29 0.00 82064.17 24283219.15 0.00 5811692.75 0.00 0.24
March 2440924.75 72887992.53 0.00 131154.48 35552863.03 0.00 11716071.32 0.00 0.27
April 100475.69 96705317.49 0.00 32895.99 52446920.03 0.00 970419.55 0.00 0.28
May 0.00 0.157268E+09 0.00 0.00 96234713.64 0.00 0.00 0.00 0.30
June 0.00 0.194534E+09 0.00 0.00 0.126104E+09 0.00 0.00 0.00 0.31
July 0.00 0.194910E+09 0.00 0.00 0.144324E+09 0.00 0.00 0.00 0.30
August 0.00 0.211416E+09 0.00 0.00 0.137436E+09 0.00 0.00 0.00 0.31
September 0.00 0.175868E+09 0.00 0.00 0.131848E+09 0.00 0.00 0.00 0.30
October 0.00 0.145119E+09 0.00 0.00 0.103705E+09 0.00 0.00 0.00 0.28
November 795208.86 0.114131E+09 0.00 15663.18 63125201.79 0.00 787421.89 0.00 0.26
December 2515960.33 50881047.60 0.00 135827.89 36816502.76 0.00 10240842.72 0.00 0.23
                   
Annual Sum or Average 13090331.37 0.151318E+10 0.00 552070.53 0.973983E+09 0.00 42258594.19 0.00 0.28
Minimum of Months 0.00 43930391.82 0.00 0.00 22106764.68 0.00 0.00 0.00 0.22
Maximum of Months 3678348.40 0.211416E+09 0.00 154464.82 0.144324E+09 0.00 12732145.97 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 3307989.90 46428837.61 0.00 162209.06 20452714.80 0.00 13022322.71 0.00 0.28
February 2603226.27 59108783.72 0.00 88901.00 21936271.12 0.00 6475651.60 0.00 0.31
March 1969911.15 79182229.11 0.00 134144.34 32029923.61 0.00 12085778.70 0.00 0.34
April 77023.85 0.106558E+09 0.00 35726.15 47765732.35 0.00 1067648.81 0.00 0.36
May 0.00 0.178225E+09 0.00 0.00 86973810.85 0.00 0.00 0.00 0.39
June 0.00 0.223928E+09 0.00 0.00 0.112725E+09 0.00 0.00 0.00 0.41
July 0.00 0.227176E+09 0.00 0.00 0.131180E+09 0.00 0.00 0.00 0.40
August 0.00 0.243369E+09 0.00 0.00 0.123397E+09 0.00 0.00 0.00 0.41
September 0.00 0.201930E+09 0.00 0.00 0.120452E+09 0.00 0.00 0.00 0.39
October 0.00 0.165686E+09 0.00 0.00 94607220.97 0.00 0.00 0.00 0.37
November 774731.12 0.125304E+09 0.00 18264.90 57169516.81 0.00 930896.96 0.00 0.34
December 2109757.38 54634977.08 0.00 140017.88 34069210.20 0.00 10572594.51 0.00 0.30
                   
Annual Sum or Average 10842639.67 0.171153E+10 0.00 579263.32 0.882759E+09 0.00 44154893.30 0.00 0.36
Minimum of Months 0.00 46428837.61 0.00 0.00 20452714.80 0.00 0.00 0.00 0.28
Maximum of Months 3307989.90 0.243369E+09 0.00 162209.06 0.131180E+09 0.00 13022322.71 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 LOBBY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 20419854.25 0.510703E+09 0.00 1584437.02 0.140857E+09 0.00 0.126096E+09 0.00 0.48
February 23538046.25 0.622796E+09 0.00 863773.12 0.141598E+09 93203.37 48942657.48 0.00 0.52
March 13163314.35 0.859729E+09 0.00 1197303.49 0.206389E+09 0.00 0.101630E+09 0.00 0.57
April 464412.00 0.121812E+10 0.00 342958.07 0.264533E+09 0.00 9628088.22 0.00 0.61
May 0.00 0.201947E+10 0.00 0.00 0.520413E+09 0.00 0.00 0.00 0.67
June 0.00 0.251063E+10 0.00 0.00 0.698805E+09 0.00 0.00 0.00 0.70
July 0.00 0.278488E+10 0.00 0.00 0.740703E+09 0.00 0.00 0.00 0.70
August 0.00 0.289539E+10 0.00 0.00 0.734736E+09 0.00 0.00 0.00 0.73
September 0.00 0.245392E+10 0.00 0.00 0.727613E+09 0.00 0.00 0.00 0.69
October 0.00 0.199548E+10 0.00 0.00 0.589384E+09 0.00 0.00 0.00 0.65
November 3770827.54 0.136770E+10 0.00 172102.50 0.394327E+09 0.00 9692010.21 0.00 0.59
December 14482400.73 0.619070E+09 0.00 1297125.10 0.229644E+09 0.00 95272346.86 0.00 0.50
                   
Annual Sum or Average 75838855.11 0.198579E+11 0.00 5457699.31 0.538900E+10 93203.37 0.391261E+09 0.00 0.62
Minimum of Months 0.00 0.510703E+09 0.00 0.00 0.140857E+09 0.00 0.00 0.00 0.48
Maximum of Months 23538046.25 0.289539E+10 0.00 1584437.02 0.740703E+09 93203.37 0.126096E+09 0.00 0.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4402323.25 0.156842E+09 0.00 655925.77 36092413.35 0.00 47331365.22 0.00 0.39
February 3866371.40 0.180793E+09 0.00 352159.08 39434911.75 0.00 21737772.57 0.00 0.40
March 2726555.39 0.238244E+09 0.00 478135.02 58634058.45 0.00 39687687.81 0.00 0.43
April 133993.55 0.307645E+09 0.00 104339.71 87249696.74 0.00 2965171.82 0.00 0.43
May 0.00 0.498699E+09 0.00 0.00 0.158555E+09 0.00 0.00 0.00 0.45
June 0.00 0.629378E+09 0.00 0.00 0.204887E+09 0.00 0.00 0.00 0.47
July 0.00 0.657297E+09 0.00 0.00 0.237293E+09 0.00 0.00 0.00 0.46
August 0.00 0.707649E+09 0.00 0.00 0.223232E+09 0.00 0.00 0.00 0.49
September 0.00 0.610053E+09 0.00 0.00 0.218271E+09 0.00 0.00 0.00 0.47
October 0.00 0.520042E+09 0.00 0.00 0.170754E+09 0.00 0.00 0.00 0.45
November 773216.91 0.382914E+09 0.00 89999.09 0.104453E+09 0.00 4607847.99 0.00 0.43
December 2911449.69 0.178872E+09 0.00 516767.80 61074074.16 0.00 36341739.62 0.00 0.40
                   
Annual Sum or Average 14813910.19 0.506843E+10 0.00 2197326.47 0.159993E+10 0.00 0.152672E+09 0.00 0.44
Minimum of Months 0.00 0.156842E+09 0.00 0.00 36092413.35 0.00 0.00 0.00 0.39
Maximum of Months 4402323.25 0.707649E+09 0.00 655925.77 0.237293E+09 0.00 47331365.22 0.00 0.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 19549668.21 82580117.78 220095.97 14661.82 72670271.34 102021.11 17146080.23 1092.72 1.34
February 17116824.83 95283769.46 286545.76 7790.69 80221399.86 339168.39 4539173.76 1447.26 1.40
March 20883535.02 0.123190E+09 410215.88 6948.66 0.114967E+09 82320.73 8827356.94 1111.57 1.47
April 684639.52 0.158164E+09 535298.60 4084.29 0.171902E+09 5908.49 1323184.76 1498.88 1.56
May 0.00 0.258640E+09 954947.99 0.00 0.303974E+09 0.00 0.00 2062.40 1.70
June 0.00 0.322070E+09 1013953.67 0.00 0.396861E+09 0.00 0.00 4791.09 1.79
July 0.00 0.339171E+09 910583.87 0.00 0.448118E+09 0.00 0.00 4813.71 1.80
August 0.00 0.358400E+09 958539.71 0.00 0.430022E+09 0.00 0.00 5599.22 1.82
September 0.00 0.309488E+09 999515.98 0.00 0.413883E+09 0.00 0.00 2801.39 1.81
October 0.00 0.255779E+09 852755.18 0.00 0.330391E+09 0.00 0.00 2218.23 1.69
November 4159085.66 0.192355E+09 600557.76 193.89 0.202906E+09 15123.47 127493.19 1457.61 1.52
December 14073526.44 92631347.60 310779.90 15975.37 0.117906E+09 83172.76 13059051.65 1730.17 1.38
                   
Annual Sum or Average 76467279.68 0.258775E+10 8053790.27 49654.71 0.308382E+10 627714.94 45022340.53 30624.24 1.61
Minimum of Months 0.00 82580117.78 220095.97 0.00 72670271.34 0.00 0.00 1092.72 1.34
Maximum of Months 20883535.02 0.358400E+09 1013953.67 15975.37 0.448118E+09 339168.39 17146080.23 5599.22 1.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 15388834.13 0.661671E+09 0.00 2677259.05 0.131162E+09 0.00 0.192812E+09 0.00 0.58
February 15620654.35 0.789576E+09 0.00 1382832.87 0.141902E+09 0.00 83410294.42 0.00 0.61
March 9652384.28 0.102795E+10 0.00 1920009.24 0.205921E+09 0.00 0.159164E+09 0.00 0.65
April 452724.23 0.133336E+10 0.00 434093.70 0.307450E+09 0.00 12127431.74 0.00 0.65
May 0.00 0.226559E+10 0.00 0.00 0.543951E+09 0.00 0.00 0.00 0.70
June 0.00 0.286824E+10 0.00 0.00 0.703945E+09 0.00 0.00 0.00 0.74
July 0.00 0.293514E+10 0.00 0.00 0.836306E+09 0.00 0.00 0.00 0.70
August 0.00 0.314900E+10 0.00 0.00 0.773136E+09 0.00 0.00 0.00 0.74
September 0.00 0.267186E+10 0.00 0.00 0.771170E+09 0.00 0.00 0.00 0.71
October 0.00 0.223814E+10 0.00 0.00 0.596536E+09 0.00 0.00 0.00 0.68
November 2813414.90 0.166418E+10 0.00 368464.94 0.359525E+09 0.00 17768568.14 0.00 0.65
December 10343901.13 0.761071E+09 0.00 2085796.38 0.219150E+09 0.00 0.145731E+09 0.00 0.59
                   
Annual Sum or Average 54271913.02 0.223658E+11 0.00 8868456.18 0.559016E+10 0.00 0.611014E+09 0.00 0.67
Minimum of Months 0.00 0.661671E+09 0.00 0.00 0.131162E+09 0.00 0.00 0.00 0.58
Maximum of Months 15620654.35 0.314900E+10 0.00 2677259.05 0.836306E+09 0.00 0.192812E+09 0.00 0.74



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 7574349.48 0.196510E+09 0.00 889238.14 64401374.13 0.00 65416799.40 0.00 0.26
February 7338457.76 0.237093E+09 0.00 457335.70 69046051.31 0.00 30025718.62 0.00 0.27
March 4524958.93 0.301393E+09 0.00 669411.04 0.101337E+09 0.00 55921318.21 0.00 0.29
April 232147.42 0.375235E+09 0.00 128648.67 0.153822E+09 0.00 3681451.50 0.00 0.28
May 0.00 0.581819E+09 0.00 0.00 0.287064E+09 0.00 0.00 0.00 0.29
June 0.00 0.706705E+09 0.00 0.00 0.372720E+09 0.00 0.00 0.00 0.30
July 0.00 0.698236E+09 0.00 0.00 0.434533E+09 0.00 0.00 0.00 0.28
August 0.00 0.768763E+09 0.00 0.00 0.410374E+09 0.00 0.00 0.00 0.30
September 0.00 0.650795E+09 0.00 0.00 0.395706E+09 0.00 0.00 0.00 0.29
October 0.00 0.567781E+09 0.00 0.00 0.307158E+09 0.00 0.00 0.00 0.28
November 1584876.07 0.460788E+09 0.00 107427.60 0.184164E+09 0.00 5530251.26 0.00 0.28
December 4916178.74 0.221666E+09 0.00 699565.72 0.107632E+09 0.00 49635098.78 0.00 0.26
                   
Annual Sum or Average 26170968.38 0.576678E+10 0.00 2951626.88 0.288796E+10 0.00 0.210211E+09 0.00 0.28
Minimum of Months 0.00 0.196510E+09 0.00 0.00 64401374.13 0.00 0.00 0.00 0.26
Maximum of Months 7574349.48 0.768763E+09 0.00 889238.14 0.434533E+09 0.00 65416799.40 0.00 0.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 8296943.66 0.343779E+09 0.00 1513747.64 72739366.63 0.00 0.109373E+09 0.00 0.58
February 7524673.64 0.413629E+09 0.00 804814.39 78295647.29 0.00 50242175.41 0.00 0.60
March 4665072.29 0.535802E+09 0.00 1159631.97 0.116746E+09 0.00 94543894.51 0.00 0.64
April 216536.68 0.691098E+09 0.00 249519.09 0.174374E+09 0.00 6805058.23 0.00 0.63
May 0.00 0.113493E+10 0.00 0.00 0.316719E+09 0.00 0.00 0.00 0.67
June 0.00 0.141235E+10 0.00 0.00 0.411717E+09 0.00 0.00 0.00 0.69
July 0.00 0.142578E+10 0.00 0.00 0.482340E+09 0.00 0.00 0.00 0.65
August 0.00 0.154096E+10 0.00 0.00 0.452374E+09 0.00 0.00 0.00 0.69
September 0.00 0.130582E+10 0.00 0.00 0.443120E+09 0.00 0.00 0.00 0.66
October 0.00 0.111170E+10 0.00 0.00 0.344402E+09 0.00 0.00 0.00 0.64
November 1405966.30 0.841119E+09 0.00 208260.17 0.209559E+09 0.00 10370602.84 0.00 0.62
December 5364925.55 0.389534E+09 0.00 1213308.46 0.123163E+09 0.00 83680717.26 0.00 0.58
                   
Annual Sum or Average 27474118.12 0.111465E+11 0.00 5149281.72 0.322555E+10 0.00 0.355015E+09 0.00 0.64
Minimum of Months 0.00 0.343779E+09 0.00 0.00 72739366.63 0.00 0.00 0.00 0.58
Maximum of Months 8296943.66 0.154096E+10 0.00 1513747.64 0.482340E+09 0.00 0.109373E+09 0.00 0.69



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 MED GAS

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6191429.95 19488812.97 137495.12 148.36 23060181.04 3088987.87 11099.98 2047.30 0.34
February 2238493.14 30315388.34 99096.84 9035.29 22174418.13 3305043.20 213175.46 2785.91 0.38
March 3962242.73 46025124.40 108024.71 7914.67 31476850.90 3188370.63 402320.36 1066.20 0.43
April 245054.86 80977449.36 27531.32 12055.91 42046634.30 28792.62 342263.08 365.23 0.54
May 0.00 0.174404E+09 5604.41 0.00 63915927.27 0.00 0.00 98.69 0.69
June 0.00 0.254140E+09 0.00 0.00 76472508.41 0.00 0.00 0.00 0.79
July 0.00 0.314245E+09 0.00 0.00 72868457.22 0.00 0.00 0.00 0.84
August 0.00 0.286816E+09 0.00 0.00 81871690.66 0.00 0.00 0.00 0.81
September 0.00 0.254364E+09 0.00 0.00 74591695.65 0.00 0.00 0.00 0.79
October 0.00 0.164040E+09 0.00 0.00 70115774.69 0.00 0.00 0.00 0.65
November 507530.11 88031455.26 7269.10 69.31 49162477.70 585125.18 286.72 361.09 0.49
December 4086358.26 28296608.28 137922.20 2179.31 32672355.96 2552274.60 231954.96 3122.72 0.37
                   
Annual Sum or Average 17231109.05 0.174114E+10 522943.69 31402.86 0.640429E+09 12748594.11 1201100.56 9847.14 0.60
Minimum of Months 0.00 19488812.97 0.00 0.00 22174418.13 0.00 0.00 0.00 0.34
Maximum of Months 6191429.95 0.314245E+09 137922.20 12055.91 81871690.66 3305043.20 402320.36 3122.72 0.84



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 320867.57 0.231204E+09 0.00 1850740.56 892039.49 0.00 97158469.26 0.00 0.80
February 716577.21 0.275212E+09 0.00 1141324.35 948626.42 0.00 56579253.16 0.00 0.81
March 154750.41 0.358549E+09 0.00 1289694.42 1288396.45 0.00 81446410.35 0.00 0.86
April 14086.15 0.472188E+09 0.00 305671.34 1709316.80 0.00 4756473.83 0.00 0.82
May 0.00 0.756038E+09 0.00 0.00 2619060.43 0.00 0.00 0.00 0.83
June 0.00 0.951617E+09 0.00 0.00 3153787.42 0.00 0.00 0.00 0.86
July 0.00 0.988235E+09 0.00 0.00 3077049.80 0.00 0.00 0.00 0.80
August 0.00 0.104220E+10 0.00 0.00 3398429.74 0.00 0.00 0.00 0.86
September 0.00 0.915435E+09 0.00 0.00 3077368.80 0.00 0.00 0.00 0.83
October 0.00 0.761525E+09 0.00 0.00 2657666.78 0.00 0.00 0.00 0.80
November 846.88 0.566585E+09 0.00 244565.27 2310516.85 0.00 9139940.63 0.00 0.79
December 220895.25 0.272904E+09 0.00 1419679.89 1033517.09 0.00 68444054.55 0.00 0.80
                   
Annual Sum or Average 1428023.48 0.759169E+10 0.00 6251675.83 26165776.07 0.00 0.317525E+09 0.00 0.82
Minimum of Months 0.00 0.231204E+09 0.00 0.00 892039.49 0.00 0.00 0.00 0.79
Maximum of Months 716577.21 0.104220E+10 0.00 1850740.56 3398429.74 0.00 97158469.26 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 3101807.74 79528665.55 0.00 303511.49 24626351.94 0.00 23476872.98 0.00 0.34
February 2913984.70 93683082.82 0.00 160372.97 26879497.24 0.00 10453958.80 0.00 0.35
March 1895991.20 0.121706E+09 0.00 222228.19 39448970.91 0.00 19557657.38 0.00 0.38
April 90400.30 0.156381E+09 0.00 50442.31 58812647.21 0.00 1474744.38 0.00 0.38
May 0.00 0.254489E+09 0.00 0.00 0.109133E+09 0.00 0.00 0.00 0.41
June 0.00 0.317510E+09 0.00 0.00 0.142567E+09 0.00 0.00 0.00 0.42
July 0.00 0.323953E+09 0.00 0.00 0.166032E+09 0.00 0.00 0.00 0.41
August 0.00 0.350659E+09 0.00 0.00 0.155507E+09 0.00 0.00 0.00 0.43
September 0.00 0.299269E+09 0.00 0.00 0.151339E+09 0.00 0.00 0.00 0.42
October 0.00 0.255834E+09 0.00 0.00 0.116563E+09 0.00 0.00 0.00 0.40
November 629413.10 0.193417E+09 0.00 37517.03 71187521.46 0.00 2047395.36 0.00 0.38
December 2067895.63 90351834.52 0.00 246131.41 41594640.31 0.00 18088687.54 0.00 0.35
                   
Annual Sum or Average 10699492.66 0.253678E+10 0.00 1020203.40 0.110369E+10 0.00 75099316.43 0.00 0.39
Minimum of Months 0.00 79528665.55 0.00 0.00 24626351.94 0.00 0.00 0.00 0.34
Maximum of Months 3101807.74 0.350659E+09 0.00 303511.49 0.166032E+09 0.00 23476872.98 0.00 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 720359.88 0.634988E+09 0.00 4984041.30 2420808.68 0.00 0.229358E+09 0.00 0.80
February 762341.53 0.750122E+09 0.00 2869663.26 2620127.09 0.00 0.135142E+09 0.00 0.81
March 349032.57 0.971256E+09 0.00 3446546.64 3536291.86 0.00 0.194149E+09 0.00 0.86
April 24640.21 0.126723E+10 0.00 663359.38 4630984.27 0.00 9653324.96 0.00 0.82
May 0.00 0.200027E+10 0.00 0.00 6978644.92 0.00 0.00 0.00 0.83
June 0.00 0.250328E+10 0.00 0.00 8345175.00 0.00 0.00 0.00 0.86
July 0.00 0.259479E+10 0.00 0.00 8118834.77 0.00 0.00 0.00 0.80
August 0.00 0.274263E+10 0.00 0.00 8988445.81 0.00 0.00 0.00 0.86
September 0.00 0.241075E+10 0.00 0.00 8139739.79 0.00 0.00 0.00 0.83
October 0.00 0.201892E+10 0.00 0.00 7089435.18 0.00 0.00 0.00 0.80
November 0.00 0.151262E+10 0.00 661104.82 6208377.56 0.00 21658736.50 0.00 0.79
December 504241.03 0.745055E+09 0.00 3584551.28 2867963.42 0.00 0.160129E+09 0.00 0.80
                   
Annual Sum or Average 2360615.22 0.201519E+11 0.00 16209266.67 69944828.33 0.00 0.750090E+09 0.00 0.82
Minimum of Months 0.00 0.634988E+09 0.00 0.00 2420808.68 0.00 0.00 0.00 0.79
Maximum of Months 762341.53 0.274263E+10 0.00 4984041.30 8988445.81 0.00 0.229358E+09 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 24517090.15 48201442.95 189897.25 1726.95 86366782.28 96099.80 7293431.82 1825.10 1.16
February 17062565.90 58100476.68 280189.84 1272.40 93991300.40 334608.94 1673317.93 2362.05 1.21
March 24856542.43 72309918.17 390502.48 573.68 0.134084E+09 80240.63 892883.33 2489.10 1.28
April 1383537.07 83625812.30 640129.48 448.17 0.202291E+09 5121.37 359900.67 3865.53 1.35
May 0.00 0.158434E+09 1197501.39 0.00 0.328857E+09 0.00 0.00 4915.14 1.47
June 0.00 0.208321E+09 1346954.37 0.00 0.414365E+09 0.00 0.00 7138.54 1.55
July 0.00 0.202402E+09 1347577.51 0.00 0.479444E+09 0.00 0.00 7307.46 1.56
August 0.00 0.221529E+09 1097099.08 0.00 0.461592E+09 0.00 0.00 8035.43 1.57
September 0.00 0.180823E+09 1201374.58 0.00 0.445844E+09 0.00 0.00 5198.80 1.57
October 0.00 0.152053E+09 830638.22 0.00 0.355935E+09 0.00 0.00 4439.34 1.46
November 3714465.61 0.133371E+09 561162.75 27.41 0.209192E+09 13108.75 1203.94 3190.28 1.31
December 17310834.05 55346652.49 268010.66 2871.76 0.127143E+09 84253.48 6206007.73 2867.41 1.20
                   
Annual Sum or Average 88845035.22 0.157452E+10 9351037.62 6920.37 0.333910E+10 613432.97 16426745.43 53634.17 1.39
Minimum of Months 0.00 48201442.95 189897.25 0.00 86366782.28 0.00 0.00 1825.10 1.16
Maximum of Months 24856542.43 0.221529E+09 1347577.51 2871.76 0.479444E+09 334608.94 7293431.82 8035.43 1.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4513429.00 0.150624E+09 0.00 696745.33 39231864.81 0.00 51989310.80 0.00 0.53
February 4077082.87 0.179010E+09 0.00 349790.74 42695575.64 0.00 23285483.04 0.00 0.54
March 2834074.43 0.226619E+09 0.00 504087.61 62578125.92 0.00 43306453.59 0.00 0.57
April 142416.90 0.281367E+09 0.00 95693.30 93255643.36 0.00 2743198.26 0.00 0.54
May 0.00 0.435332E+09 0.00 0.00 0.173244E+09 0.00 0.00 0.00 0.55
June 0.00 0.528335E+09 0.00 0.00 0.226014E+09 0.00 0.00 0.00 0.56
July 0.00 0.521875E+09 0.00 0.00 0.263544E+09 0.00 0.00 0.00 0.53
August 0.00 0.577790E+09 0.00 0.00 0.246878E+09 0.00 0.00 0.00 0.57
September 0.00 0.489994E+09 0.00 0.00 0.240208E+09 0.00 0.00 0.00 0.54
October 0.00 0.431121E+09 0.00 0.00 0.185384E+09 0.00 0.00 0.00 0.53
November 864873.85 0.345737E+09 0.00 85753.19 0.112359E+09 0.00 4623255.33 0.00 0.54
December 3007399.68 0.166714E+09 0.00 537969.89 66189525.08 0.00 38603951.91 0.00 0.53
                   
Annual Sum or Average 15439276.72 0.433452E+10 0.00 2270040.07 0.175158E+10 0.00 0.164552E+09 0.00 0.55
Minimum of Months 0.00 0.150624E+09 0.00 0.00 39231864.81 0.00 0.00 0.00 0.53
Maximum of Months 4513429.00 0.577790E+09 0.00 696745.33 0.263544E+09 0.00 51989310.80 0.00 0.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 10162686.65 0.192206E+09 0.00 766710.79 74623168.90 0.00 61708798.50 0.00 0.27
February 9453366.09 0.218581E+09 0.00 382165.72 82668994.02 0.00 25678852.30 0.00 0.27
March 8098190.01 0.262558E+09 0.00 508423.28 0.123042E+09 0.00 44079706.69 0.00 0.27
April 403994.94 0.304086E+09 0.00 92872.62 0.182276E+09 0.00 2655648.83 0.00 0.25
May 0.00 0.442934E+09 0.00 0.00 0.337008E+09 0.00 0.00 0.00 0.26
June 0.00 0.525645E+09 0.00 0.00 0.445757E+09 0.00 0.00 0.00 0.26
July 0.00 0.508864E+09 0.00 0.00 0.518902E+09 0.00 0.00 0.00 0.26
August 0.00 0.598335E+09 0.00 0.00 0.480170E+09 0.00 0.00 0.00 0.27
September 0.00 0.532596E+09 0.00 0.00 0.457411E+09 0.00 0.00 0.00 0.27
October 0.00 0.489017E+09 0.00 0.00 0.358168E+09 0.00 0.00 0.00 0.27
November 2583800.58 0.428615E+09 0.00 72630.49 0.216778E+09 0.00 3780701.28 0.00 0.27
December 7284901.32 0.212512E+09 0.00 607747.87 0.125369E+09 0.00 45715110.07 0.00 0.26
                   
Annual Sum or Average 37986939.59 0.471595E+10 0.00 2430550.77 0.340217E+10 0.00 0.183619E+09 0.00 0.27
Minimum of Months 0.00 0.192206E+09 0.00 0.00 74623168.90 0.00 0.00 0.00 0.25
Maximum of Months 10162686.65 0.598335E+09 0.00 766710.79 0.518902E+09 0.00 61708798.50 0.00 0.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1048733.80 24834359.77 0.00 116528.77 9006234.25 0.00 8645262.15 0.00 0.32
February 1007390.15 29541310.22 0.00 59604.00 9770763.00 0.00 4075634.47 0.00 0.32
March 627862.27 37188239.91 0.00 85301.31 14310850.77 0.00 7319721.48 0.00 0.34
April 36084.14 45347104.76 0.00 15012.92 21767307.91 0.00 437471.12 0.00 0.32
May 0.00 66598820.80 0.00 0.00 41364595.20 0.00 0.00 0.00 0.33
June 0.00 78660511.49 0.00 0.00 54570662.70 0.00 0.00 0.00 0.33
July 0.00 77042527.40 0.00 0.00 62464313.39 0.00 0.00 0.00 0.32
August 0.00 85549511.68 0.00 0.00 59430415.59 0.00 0.00 0.00 0.34
September 0.00 72563143.98 0.00 0.00 57065288.29 0.00 0.00 0.00 0.33
October 0.00 64520757.32 0.00 0.00 44716729.96 0.00 0.00 0.00 0.32
November 214768.73 54805651.09 0.00 14443.17 26382785.44 0.00 776174.40 0.00 0.32
December 684510.47 27844893.61 0.00 89043.21 15093819.17 0.00 6443494.33 0.00 0.31
                   
Annual Sum or Average 3619349.56 0.664497E+09 0.00 379933.37 0.415944E+09 0.00 27697757.94 0.00 0.32
Minimum of Months 0.00 24834359.77 0.00 0.00 9006234.25 0.00 0.00 0.00 0.31
Maximum of Months 1048733.80 85549511.68 0.00 116528.77 62464313.39 0.00 8645262.15 0.00 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6152135.25 0.200332E+09 0.00 893373.04 52004372.85 0.00 67381247.37 0.00 0.49
February 5981792.09 0.236574E+09 0.00 451430.63 57263510.10 0.00 29394832.02 0.00 0.50
March 3863846.37 0.299182E+09 0.00 644596.59 82803864.68 0.00 55458402.80 0.00 0.52
April 189641.25 0.366957E+09 0.00 124531.70 0.124442E+09 0.00 3558147.12 0.00 0.49
May 0.00 0.565145E+09 0.00 0.00 0.230248E+09 0.00 0.00 0.00 0.50
June 0.00 0.682719E+09 0.00 0.00 0.300164E+09 0.00 0.00 0.00 0.51
July 0.00 0.672236E+09 0.00 0.00 0.349942E+09 0.00 0.00 0.00 0.48
August 0.00 0.750737E+09 0.00 0.00 0.328204E+09 0.00 0.00 0.00 0.52
September 0.00 0.641515E+09 0.00 0.00 0.318553E+09 0.00 0.00 0.00 0.50
October 0.00 0.568955E+09 0.00 0.00 0.246500E+09 0.00 0.00 0.00 0.49
November 1262297.35 0.461469E+09 0.00 105587.43 0.149136E+09 0.00 5668329.32 0.00 0.50
December 4068453.60 0.222079E+09 0.00 697297.26 87770297.83 0.00 50383573.56 0.00 0.49
                   
Annual Sum or Average 21518165.90 0.566790E+10 0.00 2916816.64 0.232703E+10 0.00 0.211845E+09 0.00 0.50
Minimum of Months 0.00 0.200332E+09 0.00 0.00 52004372.85 0.00 0.00 0.00 0.48
Maximum of Months 6152135.25 0.750737E+09 0.00 893373.04 0.349942E+09 0.00 67381247.37 0.00 0.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 19149382.53 21541924.14 368737.99 2520.24 0.107634E+09 60130.45 11462089.59 2709.09 1.12
February 13864446.68 24209031.42 418941.16 921.29 0.121850E+09 91908.74 4376786.03 2896.27 1.17
March 21158078.53 11967610.63 543359.10 690.66 0.186273E+09 68594.11 3603754.20 4345.00 1.23
April 1676431.80 808820.22 1088095.34 0.00 0.273572E+09 4923.27 0.00 7399.57 1.30
May 0.00 0.00 3229019.16 0.00 0.466357E+09 0.00 0.00 11741.98 1.41
June 0.00 0.00 4563831.35 0.00 0.595323E+09 0.00 0.00 15043.06 1.49
July 0.00 0.00 6629952.59 0.00 0.650128E+09 0.00 0.00 16647.13 1.50
August 0.00 0.00 5150791.45 0.00 0.652592E+09 0.00 0.00 17319.74 1.51
September 0.00 0.00 5710803.29 0.00 0.597862E+09 0.00 0.00 14377.60 1.51
October 0.00 0.00 2846831.48 0.00 0.486283E+09 0.00 0.00 11163.49 1.40
November 3570788.81 9042866.40 1068251.95 4.09 0.319737E+09 12601.70 1179.64 6718.52 1.26
December 14410422.22 17940117.92 462636.28 2131.13 0.157285E+09 48602.71 8229801.39 4363.26 1.15
                   
Annual Sum or Average 73829550.57 85510370.73 32081251.13 6267.42 0.461490E+10 286760.97 27673610.86 114724.71 1.34
Minimum of Months 0.00 0.00 368737.99 0.00 0.107634E+09 0.00 0.00 2709.09 1.12
Maximum of Months 21158078.53 24209031.42 6629952.59 2520.24 0.652592E+09 91908.74 11462089.59 17319.74 1.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 8566155.66 0.249743E+09 0.00 1135494.87 68957186.36 0.00 81877008.40 0.00 0.33
February 8121131.72 0.295967E+09 0.00 587413.92 74973345.57 0.00 37415295.67 0.00 0.34
March 5266505.61 0.380511E+09 0.00 836706.70 0.111364E+09 0.00 69128075.67 0.00 0.36
April 266869.09 0.480602E+09 0.00 170222.63 0.165401E+09 0.00 4823499.03 0.00 0.35
May 0.00 0.761704E+09 0.00 0.00 0.304370E+09 0.00 0.00 0.00 0.36
June 0.00 0.928114E+09 0.00 0.00 0.399065E+09 0.00 0.00 0.00 0.37
July 0.00 0.930522E+09 0.00 0.00 0.466065E+09 0.00 0.00 0.00 0.36
August 0.00 0.102079E+10 0.00 0.00 0.435701E+09 0.00 0.00 0.00 0.38
September 0.00 0.869251E+09 0.00 0.00 0.424584E+09 0.00 0.00 0.00 0.36
October 0.00 0.759190E+09 0.00 0.00 0.326107E+09 0.00 0.00 0.00 0.36
November 1721139.51 0.591511E+09 0.00 151461.19 0.200224E+09 0.00 7591165.05 0.00 0.35
December 5673912.05 0.281682E+09 0.00 884096.70 0.116730E+09 0.00 61965298.77 0.00 0.33
                   
Annual Sum or Average 29615713.63 0.754958E+10 0.00 3765396.00 0.309354E+10 0.00 0.262800E+09 0.00 0.35
Minimum of Months 0.00 0.249743E+09 0.00 0.00 68957186.36 0.00 0.00 0.00 0.33
Maximum of Months 8566155.66 0.102079E+10 0.00 1135494.87 0.466065E+09 0.00 81877008.40 0.00 0.38



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 508955.92 0.360756E+10 0.00 3594052.98 8714579.66 0.00 0.264060E+09 0.00 2.89
February 2737649.06 0.418278E+10 0.00 1543956.97 9878359.03 398867.49 0.180908E+09 0.00 2.94
March 65258.57 0.518156E+10 0.00 2998371.59 12267542.19 0.00 0.276230E+09 0.00 3.11
April 0.00 0.650306E+10 0.00 76646.83 15129228.45 0.00 1178505.95 0.00 2.98
May 0.00 0.929569E+10 0.00 0.00 20596158.10 0.00 0.00 0.00 3.01
June 0.00 0.110526E+11 0.00 0.00 21937057.82 0.00 0.00 0.00 3.11
July 0.00 0.111903E+11 0.00 0.00 21498395.50 0.00 0.00 0.00 2.90
August 0.00 0.118366E+11 0.00 0.00 23912792.79 0.00 0.00 0.00 3.13
September 0.00 0.106339E+11 0.00 0.00 20599663.47 0.00 0.00 0.00 3.00
October 0.00 0.926067E+10 0.00 0.00 18947262.40 0.00 0.00 0.00 2.91
November 0.00 0.728810E+10 0.00 498973.97 17335896.76 0.00 27271392.78 0.00 2.87
December 500355.36 0.421224E+10 0.00 2498884.79 11179609.59 0.00 0.227174E+09 0.00 2.88
                   
Annual Sum or Average 3812218.92 0.942451E+11 0.00 11210887.12 0.201997E+09 398867.49 0.976822E+09 0.00 2.98
Minimum of Months 0.00 0.360756E+10 0.00 0.00 8714579.66 0.00 0.00 0.00 2.87
Maximum of Months 2737649.06 0.118366E+11 0.00 3594052.98 23912792.79 398867.49 0.276230E+09 0.00 3.13



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 536683.78 0.370511E+10 0.00 3670150.08 8958172.29 0.00 0.275272E+09 0.00 2.89
February 2504220.62 0.431779E+10 0.00 1629476.11 10162468.29 425762.83 0.188962E+09 0.00 2.94
March 211018.08 0.536720E+10 0.00 3136972.11 12641259.36 0.00 0.284922E+09 0.00 3.11
April 0.00 0.676432E+10 0.00 74785.00 15679634.40 0.00 1234102.46 0.00 2.98
May 0.00 0.968443E+10 0.00 0.00 21394972.45 0.00 0.00 0.00 3.01
June 0.00 0.115527E+11 0.00 0.00 22921070.69 0.00 0.00 0.00 3.11
July 0.00 0.117195E+11 0.00 0.00 23446376.73 0.00 0.00 0.00 2.90
August 0.00 0.124091E+11 0.00 0.00 25199222.31 0.00 0.00 0.00 3.13
September 0.00 0.111327E+11 0.00 0.00 25409454.27 0.00 0.00 0.00 3.00
October 0.00 0.963914E+10 0.00 0.00 20329050.41 0.00 0.00 0.00 2.90
November 0.00 0.753548E+10 0.00 539949.36 17898133.58 0.00 28050477.52 0.00 2.87
December 459338.23 0.431800E+10 0.00 2605465.75 12103392.67 0.00 0.237185E+09 0.00 2.88
                   
Annual Sum or Average 3711260.72 0.981455E+11 0.00 11656798.40 0.216143E+09 425762.83 0.101562E+10 0.00 2.98
Minimum of Months 0.00 0.370511E+10 0.00 0.00 8958172.29 0.00 0.00 0.00 2.87
Maximum of Months 2504220.62 0.124091E+11 0.00 3670150.08 25409454.27 425762.83 0.284922E+09 0.00 3.13



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 533464.79 0.362858E+10 0.00 3680999.64 8845355.28 0.00 0.269792E+09 0.00 2.89
February 558232.82 0.422577E+10 0.00 1722731.59 9981169.42 428635.87 0.188828E+09 0.00 2.94
March 272872.58 0.523259E+10 0.00 3133519.75 12367977.84 0.00 0.281333E+09 0.00 3.11
April 0.00 0.656835E+10 0.00 71400.73 15929278.07 0.00 1329387.09 0.00 2.98
May 0.00 0.942257E+10 0.00 0.00 20863975.59 0.00 0.00 0.00 3.01
June 0.00 0.113602E+11 0.00 0.00 23978018.37 0.00 0.00 0.00 3.11
July 0.00 0.116542E+11 0.00 0.00 25651509.29 0.00 0.00 0.00 2.90
August 0.00 0.123295E+11 0.00 0.00 27075703.98 0.00 0.00 0.00 3.13
September 0.00 0.109489E+11 0.00 0.00 24961455.14 0.00 0.00 0.00 3.00
October 0.00 0.942407E+10 0.00 0.00 20609301.33 0.00 0.00 0.00 2.90
November 0.00 0.735531E+10 0.00 568628.36 17543084.43 0.00 27278574.85 0.00 2.87
December 387663.72 0.423761E+10 0.00 2714127.72 11816945.60 0.00 0.229634E+09 0.00 2.88
                   
Annual Sum or Average 1752233.91 0.963876E+11 0.00 11891407.79 0.219624E+09 428635.87 0.998195E+09 0.00 2.98
Minimum of Months 0.00 0.362858E+10 0.00 0.00 8845355.28 0.00 0.00 0.00 2.87
Maximum of Months 558232.82 0.123295E+11 0.00 3680999.64 27075703.98 428635.87 0.281333E+09 0.00 3.13



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 PACU

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 25790198.24 0.195172E+09 468750.40 194681.07 0.148068E+09 159535.54 55238865.13 1149.66 1.48
February 21425948.93 0.224003E+09 541682.99 84302.49 0.164090E+09 243848.36 26889056.86 1344.07 1.55
March 17632840.14 0.286363E+09 827554.10 133171.86 0.240225E+09 139779.36 47975075.10 854.19 1.63
April 860919.34 0.370051E+09 1969052.07 28948.47 0.358859E+09 13062.22 3557969.84 3154.54 1.73
May 0.00 0.578825E+09 3666509.66 0.00 0.663418E+09 0.00 0.00 7991.67 1.88
June 0.00 0.717306E+09 4943592.09 0.00 0.869369E+09 0.00 0.00 15013.15 1.97
July 0.00 0.738702E+09 6524556.02 0.00 0.997285E+09 0.00 0.00 16128.56 1.99
August 0.00 0.794782E+09 5975174.39 0.00 0.944365E+09 0.00 0.00 17492.85 2.00
September 0.00 0.685630E+09 6359607.01 0.00 0.909410E+09 0.00 0.00 12713.83 2.00
October 0.00 0.584985E+09 3979700.29 0.00 0.708796E+09 0.00 0.00 8721.51 1.86
November 5484527.91 0.448281E+09 1731762.49 14841.66 0.425142E+09 33434.29 3977636.25 2807.60 1.68
December 17671710.60 0.218671E+09 739680.88 167736.83 0.246725E+09 122994.19 42240243.08 2161.28 1.53
                   
Annual Sum or Average 88866145.16 0.584277E+10 37727622.36 623682.39 0.667575E+10 712653.96 0.179879E+09 89532.90 1.78
Minimum of Months 0.00 0.195172E+09 468750.40 0.00 0.148068E+09 0.00 0.00 854.19 1.48
Maximum of Months 25790198.24 0.794782E+09 6524556.02 194681.07 0.997285E+09 243848.36 55238865.13 17492.85 2.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 9429841.05 0.203353E+09 0.00 815549.54 74616545.31 0.00 63640305.00 0.00 0.26
February 8849810.58 0.242694E+09 0.00 425657.84 80166753.78 0.00 28187946.59 0.00 0.27
March 6265427.11 0.306027E+09 0.00 588868.06 0.120355E+09 0.00 51839053.51 0.00 0.28
April 293807.13 0.377662E+09 0.00 119591.06 0.182326E+09 0.00 3521993.43 0.00 0.27
May 0.00 0.575934E+09 0.00 0.00 0.340158E+09 0.00 0.00 0.00 0.29
June 0.00 0.691953E+09 0.00 0.00 0.444610E+09 0.00 0.00 0.00 0.29
July 0.00 0.692525E+09 0.00 0.00 0.508841E+09 0.00 0.00 0.00 0.28
August 0.00 0.773507E+09 0.00 0.00 0.484048E+09 0.00 0.00 0.00 0.30
September 0.00 0.655111E+09 0.00 0.00 0.464453E+09 0.00 0.00 0.00 0.29
October 0.00 0.575364E+09 0.00 0.00 0.364974E+09 0.00 0.00 0.00 0.28
November 1944937.69 0.471821E+09 0.00 95595.55 0.218558E+09 0.00 5335876.31 0.00 0.28
December 6502528.56 0.227970E+09 0.00 638525.71 0.125494E+09 0.00 47682704.56 0.00 0.26
                   
Annual Sum or Average 33286352.11 0.579392E+10 0.00 2683787.77 0.340860E+10 0.00 0.200208E+09 0.00 0.28
Minimum of Months 0.00 0.203353E+09 0.00 0.00 74616545.31 0.00 0.00 0.00 0.26
Maximum of Months 9429841.05 0.773507E+09 0.00 815549.54 0.508841E+09 0.00 63640305.00 0.00 0.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 37543672.52 0.258317E+09 776662.80 134131.44 0.215905E+09 220476.09 74572374.55 4008.77 1.17
February 37003393.38 0.298439E+09 991048.88 58461.76 0.237655E+09 336995.32 29825371.39 4890.98 1.22
March 30327344.93 0.386973E+09 1252160.32 78565.67 0.340654E+09 193173.29 60447433.00 4542.00 1.29
April 1372951.45 0.488546E+09 1661669.71 22210.77 0.519854E+09 18051.82 4751692.67 7228.82 1.36
May 0.00 0.769859E+09 4150389.26 0.00 0.947818E+09 0.00 0.00 13883.81 1.48
June 0.00 0.966703E+09 7087614.55 0.00 0.122580E+10 0.00 0.00 25697.98 1.56
July 0.00 0.983228E+09 7531654.17 0.00 0.141736E+10 0.00 0.00 26720.89 1.57
August 0.00 0.107616E+10 6826622.54 0.00 0.132875E+10 0.00 0.00 27749.00 1.58
September 0.00 0.923981E+09 6725318.34 0.00 0.128241E+10 0.00 0.00 17766.56 1.58
October 0.00 0.772353E+09 3302516.77 0.00 0.101783E+10 0.00 0.00 12734.09 1.47
November 8020999.39 0.604238E+09 2173396.80 6112.90 0.603036E+09 46205.77 5069988.85 7550.34 1.32
December 25581032.02 0.292775E+09 1071267.12 118280.21 0.350343E+09 178208.14 57321821.78 6794.09 1.21
                   
Annual Sum or Average 0.139849E+09 0.782157E+10 43550321.27 417762.74 0.948742E+10 993110.42 0.231989E+09 159567.34 1.40
Minimum of Months 0.00 0.258317E+09 776662.80 0.00 0.215905E+09 0.00 0.00 4008.77 1.17
Maximum of Months 37543672.52 0.107616E+10 7531654.17 134131.44 0.141736E+10 336995.32 74572374.55 27749.00 1.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 65016221.62 0.469182E+09 1389546.92 326047.72 0.378897E+09 394290.57 0.135401E+09 6574.74 1.17
February 57928265.10 0.542762E+09 1952576.60 129002.13 0.415787E+09 602668.87 61561159.06 7821.39 1.22
March 46370628.44 0.695086E+09 2240072.69 211854.24 0.606173E+09 345463.34 0.115896E+09 7363.21 1.29
April 2172463.48 0.885538E+09 3232768.17 43244.86 0.917584E+09 32283.15 8777079.77 12827.45 1.36
May 0.00 0.136252E+10 8818632.61 0.00 0.170790E+10 0.00 0.00 28390.70 1.48
June 0.00 0.169728E+10 15215447.04 0.00 0.222116E+10 0.00 0.00 50687.60 1.56
July 0.00 0.166220E+10 14161297.56 0.00 0.263023E+10 0.00 0.00 53278.74 1.57
August 0.00 0.183851E+10 15603542.54 0.00 0.245892E+10 0.00 0.00 57724.43 1.58
September 0.00 0.156949E+10 14281153.31 0.00 0.237406E+10 0.00 0.00 41182.52 1.58
October 0.00 0.133979E+10 9421757.16 0.00 0.185818E+10 0.00 0.00 29958.63 1.47
November 13760748.93 0.108048E+10 4392217.42 19963.22 0.107805E+10 82632.54 9641616.87 14904.37 1.32
December 44534496.51 0.524670E+09 2239696.84 272282.49 0.625134E+09 318700.28 0.103665E+09 11446.04 1.21
                   
Annual Sum or Average 0.229783E+09 0.136675E+11 92948708.87 1002394.65 0.172721E+11 1776038.74 0.434942E+09 322159.83 1.40
Minimum of Months 0.00 0.469182E+09 1389546.92 0.00 0.378897E+09 0.00 0.00 6574.74 1.17
Maximum of Months 65016221.62 0.183851E+10 15603542.54 326047.72 0.263023E+10 602668.87 0.135401E+09 57724.43 1.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 27056455.58 45535637.61 184976.27 3060.44 85635457.63 129528.67 3913788.40 1906.12 1.13
February 16365844.05 53972785.01 272917.97 4131.75 94279485.86 1677191.38 543137.64 2501.00 1.18
March 23848917.24 71643421.25 413594.38 1398.20 0.129507E+09 527837.39 800011.45 2572.14 1.25
April 1424492.67 90143674.17 525712.05 961.95 0.188653E+09 4992.08 274407.47 3664.54 1.32
May 0.00 0.162784E+09 1053023.33 0.00 0.312319E+09 0.00 0.00 5220.21 1.44
June 0.00 0.197710E+09 1364373.45 0.00 0.409204E+09 0.00 0.00 7318.16 1.51
July 0.00 0.218668E+09 1246950.97 0.00 0.446032E+09 0.00 0.00 7444.70 1.52
August 0.00 0.245827E+09 1086368.94 0.00 0.420032E+09 0.00 0.00 8026.05 1.53
September 0.00 0.203774E+09 1161203.44 0.00 0.407083E+09 0.00 0.00 5207.87 1.53
October 0.00 0.171503E+09 761223.66 0.00 0.323710E+09 0.00 0.00 4205.78 1.43
November 3609163.93 0.137675E+09 528285.84 74.19 0.196258E+09 24309.06 1126.08 3150.83 1.28
December 19682138.02 56646688.42 261081.02 2945.69 0.121236E+09 82126.53 3240882.51 2958.82 1.17
                   
Annual Sum or Average 91987011.49 0.165588E+10 8859711.32 12572.22 0.313395E+10 2445985.11 8773353.55 54176.21 1.36
Minimum of Months 0.00 45535637.61 184976.27 0.00 85635457.63 0.00 0.00 1906.12 1.13
Maximum of Months 27056455.58 0.245827E+09 1364373.45 4131.75 0.446032E+09 1677191.38 3913788.40 8026.05 1.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.134637E+09 0.101929E+10 7623839.18 421958.61 0.763756E+09 2535667.64 0.286402E+09 11303.78 2.92
February 0.131100E+09 0.117206E+10 6416940.13 189951.17 0.846252E+09 3415626.13 0.118719E+09 11751.27 3.05
March 91487972.31 0.149124E+10 9350269.30 278813.96 0.124717E+10 2393605.77 0.249071E+09 15510.89 3.21
April 4391877.73 0.195251E+10 16919627.78 84088.20 0.183835E+10 161454.82 18603299.00 26297.10 3.40
May 0.00 0.313208E+10 35888684.99 0.00 0.332306E+10 0.00 0.00 45735.53 3.70
June 0.00 0.391282E+10 36976845.44 0.00 0.434236E+10 0.00 0.00 49353.19 3.89
July 0.00 0.407765E+10 41466757.04 0.00 0.495917E+10 0.00 0.00 51788.43 3.92
August 0.00 0.431716E+10 37377964.51 0.00 0.473737E+10 0.00 0.00 51701.89 3.95
September 0.00 0.377837E+10 37261489.44 0.00 0.452748E+10 0.00 0.00 38677.18 3.94
October 0.00 0.314596E+10 37958073.43 0.00 0.357725E+10 0.00 0.00 38609.53 3.67
November 28210057.33 0.235975E+10 21633680.57 28202.07 0.217805E+10 537822.43 20772098.96 26026.24 3.30
December 91749538.53 0.115214E+10 9319879.18 385076.37 0.126704E+10 1786539.56 0.219727E+09 16943.26 3.02
                   
Annual Sum or Average 0.481576E+09 0.315110E+11 0.298194E+09 1388090.37 0.336073E+11 10830716.34 0.913295E+09 383698.29 3.50
Minimum of Months 0.00 0.101929E+10 6416940.13 0.00 0.763756E+09 0.00 0.00 11303.78 2.92
Maximum of Months 0.134637E+09 0.431716E+10 41466757.04 421958.61 0.495917E+10 3415626.13 0.286402E+09 51788.43 3.95



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 13011022.94 0.539355E+09 0.00 2126233.72 0.103812E+09 0.00 0.161183E+09 0.00 0.63
February 12657906.69 0.626361E+09 0.00 1101658.53 0.113785E+09 0.00 66665762.20 0.00 0.64
March 7915708.06 0.809958E+09 0.00 1497919.69 0.167432E+09 0.00 0.128291E+09 0.00 0.67
April 399720.56 0.102857E+10 0.00 334030.73 0.252007E+09 0.00 9593168.69 0.00 0.66
May 0.00 0.168106E+10 0.00 0.00 0.458491E+09 0.00 0.00 0.00 0.69
June 0.00 0.211541E+10 0.00 0.00 0.594401E+09 0.00 0.00 0.00 0.73
July 0.00 0.218729E+10 0.00 0.00 0.693434E+09 0.00 0.00 0.00 0.70
August 0.00 0.240391E+10 0.00 0.00 0.643658E+09 0.00 0.00 0.00 0.75
September 0.00 0.208931E+10 0.00 0.00 0.630156E+09 0.00 0.00 0.00 0.73
October 0.00 0.180215E+10 0.00 0.00 0.485219E+09 0.00 0.00 0.00 0.71
November 2452271.61 0.135395E+10 0.00 256537.60 0.290407E+09 0.00 13487874.35 0.00 0.68
December 8571517.56 0.619175E+09 0.00 1717577.39 0.174136E+09 0.00 0.123648E+09 0.00 0.63
                   
Annual Sum or Average 45008147.42 0.172565E+11 0.00 7033957.65 0.460694E+10 0.00 0.502869E+09 0.00 0.68
Minimum of Months 0.00 0.539355E+09 0.00 0.00 0.103812E+09 0.00 0.00 0.00 0.63
Maximum of Months 13011022.94 0.240391E+10 0.00 2126233.72 0.693434E+09 0.00 0.161183E+09 0.00 0.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2314428.17 57655460.06 0.00 249160.81 19467022.78 0.00 18799845.79 0.00 0.30
February 2186920.78 67579061.41 0.00 130106.52 21135253.01 0.00 8436529.35 0.00 0.30
March 1424018.70 86457435.39 0.00 180052.53 30898502.83 0.00 15630594.64 0.00 0.32
April 77164.42 0.106377E+09 0.00 35042.10 46870723.32 0.00 1026971.34 0.00 0.31
May 0.00 0.161931E+09 0.00 0.00 87829395.58 0.00 0.00 0.00 0.32
June 0.00 0.192426E+09 0.00 0.00 0.116981E+09 0.00 0.00 0.00 0.33
July 0.00 0.192221E+09 0.00 0.00 0.134663E+09 0.00 0.00 0.00 0.32
August 0.00 0.213658E+09 0.00 0.00 0.127792E+09 0.00 0.00 0.00 0.33
September 0.00 0.183376E+09 0.00 0.00 0.122424E+09 0.00 0.00 0.00 0.32
October 0.00 0.163963E+09 0.00 0.00 94458417.50 0.00 0.00 0.00 0.32
November 475119.82 0.133699E+09 0.00 32701.70 55565995.51 0.00 1700919.56 0.00 0.31
December 1486214.94 64649374.94 0.00 195852.05 32614793.04 0.00 14300972.20 0.00 0.30
                   
Annual Sum or Average 7963866.81 0.162399E+10 0.00 822915.70 0.890700E+09 0.00 59895832.87 0.00 0.32
Minimum of Months 0.00 57655460.06 0.00 0.00 19467022.78 0.00 0.00 0.00 0.30
Maximum of Months 2314428.17 0.213658E+09 0.00 249160.81 0.134663E+09 0.00 18799845.79 0.00 0.33



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.114943E+09 0.890331E+09 1974891.99 1587863.87 0.655680E+09 823447.21 0.248448E+09 6408.22 1.34
February 0.111472E+09 0.101363E+10 2969541.18 738139.60 0.728401E+09 1192327.97 0.104941E+09 7931.07 1.40
March 79939097.24 0.128839E+10 3965806.53 686688.82 0.107415E+10 816574.82 0.214158E+09 5401.47 1.46
April 3944025.05 0.168061E+10 6373179.76 152847.34 0.159239E+10 58608.83 15860117.50 16967.22 1.55
May 0.00 0.269443E+10 16296868.48 0.00 0.287954E+10 0.00 0.00 34334.29 1.68
June 0.00 0.335242E+10 20170267.17 0.00 0.376885E+10 0.00 0.00 59083.42 1.77
July 0.00 0.350531E+10 17106801.16 0.00 0.429607E+10 0.00 0.00 61959.24 1.79
August 0.00 0.370929E+10 15077344.91 0.00 0.410583E+10 0.00 0.00 62339.91 1.80
September 0.00 0.326716E+10 16688933.07 0.00 0.390148E+10 0.00 0.00 34999.36 1.80
October 0.00 0.273734E+10 9488633.69 0.00 0.307719E+10 0.00 0.00 21414.07 1.68
November 24554033.47 0.206100E+10 3558701.06 101196.15 0.187482E+10 150016.24 17867120.35 7776.00 1.51
December 80072422.37 0.100992E+10 1707131.52 1301957.11 0.108760E+10 892928.03 0.188125E+09 10850.19 1.38
                   
Annual Sum or Average 0.414925E+09 0.272098E+11 0.115378E+09 4568692.89 0.290420E+11 3933903.10 0.789400E+09 329464.47 1.60
Minimum of Months 0.00 0.890331E+09 1707131.52 0.00 0.655680E+09 0.00 0.00 5401.47 1.34
Maximum of Months 0.114943E+09 0.370929E+10 20170267.17 1587863.87 0.429607E+10 1192327.97 0.248448E+09 62339.91 1.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2752466.56 72660895.51 0.00 272336.60 21754599.03 0.00 20940245.34 0.00 0.38
February 3353142.99 83257406.21 0.00 135773.53 23596921.56 0.00 7730730.92 0.00 0.39
March 2096621.46 0.104408E+09 0.00 173078.09 34677498.26 0.00 14622877.24 0.00 0.40
April 87190.31 0.129277E+09 0.00 38749.46 52421681.51 0.00 1153854.40 0.00 0.39
May 0.00 0.207664E+09 0.00 0.00 95815691.01 0.00 0.00 0.00 0.42
June 0.00 0.258298E+09 0.00 0.00 0.124779E+09 0.00 0.00 0.00 0.44
July 0.00 0.270812E+09 0.00 0.00 0.144833E+09 0.00 0.00 0.00 0.43
August 0.00 0.304900E+09 0.00 0.00 0.134714E+09 0.00 0.00 0.00 0.46
September 0.00 0.267722E+09 0.00 0.00 0.131035E+09 0.00 0.00 0.00 0.45
October 0.00 0.234987E+09 0.00 0.00 0.101216E+09 0.00 0.00 0.00 0.45
November 552034.03 0.182557E+09 0.00 31310.20 61638425.91 0.00 1713266.40 0.00 0.43
December 1966467.31 85679772.40 0.00 217834.25 36492214.65 0.00 15737078.70 0.00 0.39
                   
Annual Sum or Average 10807922.65 0.220222E+10 0.00 869082.12 0.962973E+09 0.00 61898053.00 0.00 0.42
Minimum of Months 0.00 72660895.51 0.00 0.00 21754599.03 0.00 0.00 0.00 0.38
Maximum of Months 3353142.99 0.304900E+09 0.00 272336.60 0.144833E+09 0.00 20940245.34 0.00 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 SCRUB

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2320902.93 33033539.12 0.00 108040.71 13806594.53 0.00 8863025.05 0.00 0.26
February 2367974.27 39423234.26 0.00 58802.80 15145391.15 0.00 3691197.65 0.00 0.28
March 1554587.68 52982757.15 0.00 87037.75 21990112.23 0.00 7804523.74 0.00 0.30
April 75368.88 70919586.20 0.00 22679.20 32479289.99 0.00 678653.99 0.00 0.32
May 0.00 0.115760E+09 0.00 0.00 59584894.87 0.00 0.00 0.00 0.34
June 0.00 0.152053E+09 0.00 0.00 76582641.43 0.00 0.00 0.00 0.37
July 0.00 0.159968E+09 0.00 0.00 88911615.96 0.00 0.00 0.00 0.36
August 0.00 0.172554E+09 0.00 0.00 83236431.73 0.00 0.00 0.00 0.38
September 0.00 0.146817E+09 0.00 0.00 80606776.15 0.00 0.00 0.00 0.37
October 0.00 0.119427E+09 0.00 0.00 63511227.54 0.00 0.00 0.00 0.34
November 511375.59 86437486.59 0.00 9685.38 38607335.59 0.00 501645.81 0.00 0.31
December 1605597.44 37217901.24 0.00 88885.60 22921707.17 0.00 6676209.04 0.00 0.26
                   
Annual Sum or Average 8435806.79 0.118659E+10 0.00 375131.44 0.597384E+09 0.00 28215255.27 0.00 0.33
Minimum of Months 0.00 33033539.12 0.00 0.00 13806594.53 0.00 0.00 0.00 0.26
Maximum of Months 2367974.27 0.172554E+09 0.00 108040.71 88911615.96 0.00 8863025.05 0.00 0.38



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 SOIL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 29531746.45 0.214887E+09 806663.62 167614.49 0.172979E+09 180406.52 62150347.35 2173.42 1.44
February 24642808.02 0.245648E+09 813240.31 67353.86 0.193015E+09 275749.42 30020906.95 2267.42 1.50
March 20087304.59 0.319177E+09 1156755.59 113486.27 0.276080E+09 158065.76 54140766.70 2026.17 1.58
April 994004.45 0.407476E+09 2269514.20 23696.24 0.416748E+09 14771.06 4012018.06 5150.55 1.67
May 0.00 0.638767E+09 4393385.00 0.00 0.765740E+09 0.00 0.00 11347.45 1.82
June 0.00 0.794118E+09 6277936.09 0.00 0.999442E+09 0.00 0.00 19160.33 1.91
July 0.00 0.821153E+09 8836870.85 0.00 0.114048E+10 0.00 0.00 20355.03 1.93
August 0.00 0.889110E+09 7476019.72 0.00 0.107684E+10 0.00 0.00 22406.81 1.94
September 0.00 0.762825E+09 7472262.10 0.00 0.104060E+10 0.00 0.00 16939.13 1.94
October 0.00 0.639528E+09 5491911.06 0.00 0.822515E+09 0.00 0.00 13223.85 1.81
November 6296191.32 0.496751E+09 2385772.01 10883.46 0.490506E+09 37808.28 4409744.88 5283.02 1.62
December 20028742.59 0.238508E+09 1011473.91 142994.19 0.287596E+09 139084.71 47767781.22 3849.23 1.48
                   
Annual Sum or Average 0.101581E+09 0.646795E+10 48391804.46 526028.51 0.768254E+10 805885.75 0.202502E+09 124182.42 1.72
Minimum of Months 0.00 0.214887E+09 806663.62 0.00 0.172979E+09 0.00 0.00 2026.17 1.44
Maximum of Months 29531746.45 0.889110E+09 8836870.85 167614.49 0.114048E+10 275749.42 62150347.35 22406.81 1.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 14623348.65 96963638.99 312299.36 43883.16 84051701.81 96819.86 28170803.69 1043.14 1.51
February 16394978.08 0.113273E+09 334863.51 20019.93 91421187.91 141617.21 9105743.13 1026.79 1.58
March 10055998.17 0.147947E+09 479075.37 33528.17 0.129820E+09 73742.50 24593077.59 661.61 1.66
April 463733.39 0.194132E+09 689454.17 11326.58 0.190764E+09 6891.15 1871457.23 1018.38 1.76
May 0.00 0.308190E+09 1481177.54 0.00 0.347627E+09 0.00 0.00 2047.41 1.91
June 0.00 0.379767E+09 1730129.59 0.00 0.458187E+09 0.00 0.00 4527.14 2.01
July 0.00 0.392156E+09 1666739.20 0.00 0.525466E+09 0.00 0.00 5016.09 2.02
August 0.00 0.418025E+09 1444659.89 0.00 0.501197E+09 0.00 0.00 5741.69 2.04
September 0.00 0.359473E+09 1479710.73 0.00 0.483891E+09 0.00 0.00 3231.15 2.03
October 0.00 0.301895E+09 1227913.28 0.00 0.381530E+09 0.00 0.00 2644.89 1.90
November 3061958.25 0.231653E+09 861711.76 1922.94 0.229185E+09 17638.72 1935842.03 1370.12 1.70
December 10155640.40 0.107586E+09 409968.09 43571.84 0.137919E+09 68029.66 21493502.58 1669.14 1.56
                   
Annual Sum or Average 54755656.95 0.305106E+10 12117702.51 154252.62 0.356106E+10 404739.10 87170426.25 29997.54 1.81
Minimum of Months 0.00 96963638.99 312299.36 0.00 84051701.81 0.00 0.00 661.61 1.51
Maximum of Months 16394978.08 0.418025E+09 1730129.59 43883.16 0.525466E+09 141617.21 28170803.69 5741.69 2.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 39351055.69 0.275677E+09 1226797.41 202297.52 0.239400E+09 239648.15 82457825.52 4381.93 1.34
February 40068975.08 0.319344E+09 1279710.08 80082.04 0.263165E+09 366299.60 32554518.58 4547.61 1.40
March 28356470.30 0.421053E+09 1912860.86 133451.86 0.369296E+09 209971.16 70263805.37 4586.44 1.47
April 1320414.15 0.525807E+09 3643742.83 28575.74 0.568440E+09 19621.56 5332380.43 11282.64 1.55
May 0.00 0.839739E+09 7450771.41 0.00 0.102436E+10 0.00 0.00 20902.46 1.69
June 0.00 0.105077E+10 11331984.30 0.00 0.132875E+10 0.00 0.00 31134.37 1.78
July 0.00 0.106396E+10 13788730.77 0.00 0.153977E+10 0.00 0.00 32374.72 1.79
August 0.00 0.116511E+10 11884765.27 0.00 0.144445E+10 0.00 0.00 35353.28 1.80
September 0.00 0.100370E+10 11851233.67 0.00 0.139000E+10 0.00 0.00 26870.13 1.80
October 0.00 0.842669E+09 7727321.24 0.00 0.109904E+10 0.00 0.00 22153.79 1.68
November 8489554.79 0.651854E+09 3692530.04 10878.88 0.659070E+09 50223.71 5735559.26 10453.04 1.51
December 26655752.13 0.312914E+09 1685413.83 174161.08 0.385608E+09 193704.69 63410535.00 7191.91 1.38
                   
Annual Sum or Average 0.144242E+09 0.847260E+10 77475861.73 629447.12 0.103114E+11 1079468.86 0.259755E+09 211232.31 1.60
Minimum of Months 0.00 0.275677E+09 1226797.41 0.00 0.239400E+09 0.00 0.00 4381.93 1.34
Maximum of Months 40068975.08 0.116511E+10 13788730.77 202297.52 0.153977E+10 366299.60 82457825.52 35353.28 1.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 57928319.06 0.465348E+09 654441.22 892851.33 0.330647E+09 511973.30 0.127352E+09 3042.34 1.24
February 55932980.03 0.523121E+09 830098.62 419937.52 0.365767E+09 1443476.73 52994700.73 3523.56 1.29
March 41577593.44 0.661657E+09 936628.48 406444.00 0.539280E+09 413110.72 0.107149E+09 2155.10 1.34
April 1912159.51 0.864242E+09 2299097.58 103764.36 0.793952E+09 29650.60 8080452.26 5159.22 1.41
May 0.00 0.138085E+10 4706900.90 0.00 0.144260E+10 0.00 0.00 9580.07 1.54
June 0.00 0.172300E+10 6020705.78 0.00 0.188389E+10 0.00 0.00 22149.39 1.62
July 0.00 0.180050E+10 4894586.35 0.00 0.215178E+10 0.00 0.00 24266.41 1.63
August 0.00 0.191903E+10 4186288.03 0.00 0.205056E+10 0.00 0.00 22391.24 1.65
September 0.00 0.169884E+10 3634014.07 0.00 0.196343E+10 0.00 0.00 8586.51 1.65
October 0.00 0.145292E+10 1995945.61 0.00 0.154494E+10 0.00 0.00 5159.31 1.56
November 12612195.55 0.109753E+10 1134848.55 51188.53 0.942105E+09 75894.23 8850115.59 2392.76 1.41
December 41334176.24 0.533149E+09 730728.01 762443.81 0.546353E+09 451738.33 95011785.44 5383.26 1.28
                   
Annual Sum or Average 0.211297E+09 0.141202E+11 32024283.21 2636629.54 0.145553E+11 2925843.92 0.399439E+09 113789.17 1.47
Minimum of Months 0.00 0.465348E+09 654441.22 0.00 0.330647E+09 0.00 0.00 2155.10 1.24
Maximum of Months 57928319.06 0.191903E+10 6020705.78 892851.33 0.215178E+10 1443476.73 0.127352E+09 24266.41 1.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 14299108.40 0.244473E+09 0.00 859207.61 85071256.74 0.00 69103382.77 0.00 0.26
February 13438459.77 0.284574E+09 0.00 452883.09 93257919.39 0.00 27607648.37 0.00 0.27
March 9569140.24 0.357863E+09 0.00 606837.37 0.137751E+09 0.00 52981887.29 0.00 0.28
April 474235.73 0.446887E+09 0.00 136865.93 0.207804E+09 0.00 3981972.68 0.00 0.27
May 0.00 0.701716E+09 0.00 0.00 0.381507E+09 0.00 0.00 0.00 0.29
June 0.00 0.890274E+09 0.00 0.00 0.497566E+09 0.00 0.00 0.00 0.31
July 0.00 0.932475E+09 0.00 0.00 0.567731E+09 0.00 0.00 0.00 0.30
August 0.00 0.103267E+10 0.00 0.00 0.538305E+09 0.00 0.00 0.00 0.32
September 0.00 0.908723E+09 0.00 0.00 0.516888E+09 0.00 0.00 0.00 0.31
October 0.00 0.784307E+09 0.00 0.00 0.403529E+09 0.00 0.00 0.00 0.30
November 3137255.44 0.612687E+09 0.00 81377.83 0.241047E+09 0.00 4001912.99 0.00 0.29
December 9869922.34 0.281511E+09 0.00 704151.21 0.141547E+09 0.00 52269681.81 0.00 0.26
                   
Annual Sum or Average 50788121.92 0.747816E+10 0.00 2841323.04 0.381200E+10 0.00 0.209946E+09 0.00 0.29
Minimum of Months 0.00 0.244473E+09 0.00 0.00 85071256.74 0.00 0.00 0.00 0.26
Maximum of Months 14299108.40 0.103267E+10 0.00 859207.61 0.567731E+09 0.00 69103382.77 0.00 0.32



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 5665342.82 0.126773E+09 0.00 578563.57 47518651.60 0.00 43680845.19 0.00 0.22
February 5358444.17 0.152158E+09 0.00 296167.29 50956104.90 0.00 20422052.47 0.00 0.23
March 3583769.21 0.187426E+09 0.00 428703.45 77464525.54 0.00 36669774.72 0.00 0.24
April 223157.24 0.228101E+09 0.00 75598.57 0.117107E+09 0.00 2170091.35 0.00 0.23
May 0.00 0.340349E+09 0.00 0.00 0.214775E+09 0.00 0.00 0.00 0.23
June 0.00 0.406755E+09 0.00 0.00 0.280609E+09 0.00 0.00 0.00 0.24
July 0.00 0.398791E+09 0.00 0.00 0.321314E+09 0.00 0.00 0.00 0.22
August 0.00 0.444047E+09 0.00 0.00 0.305604E+09 0.00 0.00 0.00 0.24
September 0.00 0.376840E+09 0.00 0.00 0.293504E+09 0.00 0.00 0.00 0.23
October 0.00 0.332298E+09 0.00 0.00 0.230391E+09 0.00 0.00 0.00 0.22
November 1237506.42 0.280924E+09 0.00 64923.37 0.139307E+09 0.00 3502804.70 0.00 0.22
December 3870128.32 0.141514E+09 0.00 449022.36 80015731.09 0.00 32483160.39 0.00 0.22
                   
Annual Sum or Average 19938348.19 0.341598E+10 0.00 1892978.61 0.215857E+10 0.00 0.138929E+09 0.00 0.23
Minimum of Months 0.00 0.126773E+09 0.00 0.00 47518651.60 0.00 0.00 0.00 0.22
Maximum of Months 5665342.82 0.444047E+09 0.00 578563.57 0.321314E+09 0.00 43680845.19 0.00 0.24



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 STORAGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 71954137.74 0.156951E+09 381150.05 381.59 0.228044E+09 14268523.88 69468.53 11632.59 0.19
February 38008337.64 0.255849E+09 261978.22 39001.89 0.207153E+09 12595481.57 1151180.92 19870.30 0.21
March 53761710.92 0.422702E+09 28769.83 53225.56 0.279092E+09 11787870.79 4331990.69 3517.76 0.24
April 1645935.25 0.770202E+09 0.00 134511.79 0.367958E+09 7685.66 4284106.22 0.00 0.31
May 0.00 0.159356E+10 0.00 0.00 0.628094E+09 0.00 0.00 0.00 0.39
June 0.00 0.227081E+10 0.00 0.00 0.759688E+09 0.00 0.00 0.00 0.44
July 0.00 0.268423E+10 0.00 0.00 0.769813E+09 0.00 0.00 0.00 0.46
August 0.00 0.247561E+10 0.00 0.00 0.826422E+09 0.00 0.00 0.00 0.44
September 0.00 0.197057E+10 0.00 0.00 0.850382E+09 0.00 0.00 0.00 0.41
October 0.00 0.129176E+10 0.00 0.00 0.702599E+09 0.00 0.00 0.00 0.34
November 8750882.97 0.747032E+09 3769.18 390.71 0.451991E+09 1360820.31 2917.06 1508.10 0.26
December 52112886.87 0.237433E+09 248731.27 29225.10 0.313799E+09 9657319.60 2021819.77 25283.89 0.20
                   
Annual Sum or Average 0.226234E+09 0.148767E+11 924398.55 256736.63 0.638504E+10 49677701.81 11861483.19 61812.64 0.33
Minimum of Months 0.00 0.156951E+09 0.00 0.00 0.207153E+09 0.00 0.00 0.00 0.19
Maximum of Months 71954137.74 0.268423E+10 381150.05 134511.79 0.850382E+09 14268523.88 4331990.69 25283.89 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 9325219.09 96265552.76 0.00 205456.56 45832480.08 25952.36 19828436.94 0.00 0.32
February 8547839.65 0.116922E+09 0.00 131821.19 50452990.13 229343.71 7992150.29 0.00 0.36
March 6940654.73 0.166583E+09 0.00 199121.11 74348412.94 37577.25 19090438.74 0.00 0.40
April 261609.62 0.252163E+09 0.00 67908.90 0.108836E+09 0.00 2214120.28 0.00 0.47
May 0.00 0.437411E+09 0.00 0.00 0.194013E+09 0.00 0.00 0.00 0.53
June 0.00 0.594192E+09 0.00 0.00 0.243170E+09 0.00 0.00 0.00 0.58
July 0.00 0.654962E+09 0.00 0.00 0.276586E+09 0.00 0.00 0.00 0.58
August 0.00 0.666661E+09 0.00 0.00 0.263028E+09 0.00 0.00 0.00 0.59
September 0.00 0.574730E+09 0.00 0.00 0.255364E+09 0.00 0.00 0.00 0.57
October 0.00 0.436244E+09 0.00 0.00 0.205440E+09 0.00 0.00 0.00 0.51
November 2087837.90 0.276101E+09 0.00 20147.10 0.127862E+09 10572.24 1040475.67 0.00 0.42
December 7504704.01 0.110018E+09 0.00 149761.57 77642659.07 29513.89 12662038.14 0.00 0.32
                   
Annual Sum or Average 34667864.99 0.438225E+10 0.00 774216.42 0.192258E+10 332959.45 62827660.07 0.00 0.47
Minimum of Months 0.00 96265552.76 0.00 0.00 45832480.08 0.00 0.00 0.00 0.32
Maximum of Months 9325219.09 0.666661E+09 0.00 205456.56 0.276586E+09 229343.71 19828436.94 0.00 0.59



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 42840783.64 79960276.63 58121.28 316.60 0.112596E+09 1984635.82 482159.37 2829.30 0.35
February 21386623.61 0.120883E+09 49855.20 15841.13 0.100711E+09 4811313.51 906961.33 4117.07 0.37
March 25153205.73 0.198376E+09 16550.65 60024.74 0.135921E+09 1264396.76 10604586.38 991.99 0.42
April 608811.50 0.382705E+09 0.00 92552.41 0.191538E+09 4048.41 3216675.04 0.00 0.57
May 0.00 0.710059E+09 0.00 0.00 0.343590E+09 0.00 0.00 0.00 0.68
June 0.00 0.967900E+09 0.00 0.00 0.426482E+09 0.00 0.00 0.00 0.73
July 0.00 0.109301E+10 0.00 0.00 0.466924E+09 0.00 0.00 0.00 0.75
August 0.00 0.101648E+10 0.00 0.00 0.474586E+09 0.00 0.00 0.00 0.72
September 0.00 0.786915E+09 0.00 0.00 0.464979E+09 0.00 0.00 0.00 0.66
October 0.00 0.501630E+09 0.00 0.00 0.377420E+09 0.00 0.00 0.00 0.53
November 5129852.53 0.296385E+09 2485.01 135.51 0.237653E+09 172472.31 1606.85 294.79 0.43
December 30146756.21 0.105060E+09 126062.93 5515.89 0.161508E+09 2212662.43 1144395.32 7173.10 0.37
                   
Annual Sum or Average 0.125266E+09 0.625936E+10 253075.07 174386.27 0.349391E+10 10449529.23 16356384.30 15406.24 0.55
Minimum of Months 0.00 79960276.63 0.00 0.00 0.100711E+09 0.00 0.00 0.00 0.35
Maximum of Months 42840783.64 0.109301E+10 126062.93 92552.41 0.474586E+09 4811313.51 10604586.38 7173.10 0.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1245089.87 16581857.12 0.00 52513.87 7387762.57 0.00 4241444.32 0.00 0.26
February 1341005.25 19584103.32 0.00 28676.54 8114327.20 0.00 1751561.24 0.00 0.28
March 831572.25 26502631.40 0.00 42449.34 11787143.32 0.00 3755777.04 0.00 0.31
April 37481.59 35846920.37 0.00 11502.83 17380015.81 0.00 345063.05 0.00 0.33
May 0.00 58988551.38 0.00 0.00 31825444.65 0.00 0.00 0.00 0.36
June 0.00 77208154.41 0.00 0.00 40970865.78 0.00 0.00 0.00 0.38
July 0.00 81597258.57 0.00 0.00 47331205.81 0.00 0.00 0.00 0.38
August 0.00 86910427.26 0.00 0.00 44398733.15 0.00 0.00 0.00 0.39
September 0.00 73791205.78 0.00 0.00 43133106.87 0.00 0.00 0.00 0.38
October 0.00 60079153.35 0.00 0.00 33842214.79 0.00 0.00 0.00 0.35
November 270484.70 43215755.96 0.00 5393.16 20689559.39 0.00 268901.02 0.00 0.31
December 842150.53 18596331.38 0.00 43368.98 12332685.78 0.00 3269831.20 0.00 0.27
                   
Annual Sum or Average 4567784.19 0.598902E+09 0.00 183904.72 0.319193E+09 0.00 13632577.87 0.00 0.33
Minimum of Months 0.00 16581857.12 0.00 0.00 7387762.57 0.00 0.00 0.00 0.26
Maximum of Months 1341005.25 86910427.26 0.00 52513.87 47331205.81 0.00 4241444.32 0.00 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 16868369.84 0.125609E+09 0.00 157802.85 64879217.12 71154.18 20271543.21 0.00 0.23
February 14657007.15 0.151387E+09 2401.93 136229.59 72041801.01 347157.37 7771217.44 604.91 0.26
March 11485347.39 0.222775E+09 0.00 204151.54 0.105479E+09 55072.16 20662566.47 0.00 0.29
April 370935.67 0.341088E+09 0.00 89559.20 0.154275E+09 0.00 2931214.91 0.00 0.35
May 0.00 0.601175E+09 0.00 0.00 0.278192E+09 0.00 0.00 0.00 0.40
June 0.00 0.812691E+09 0.00 0.00 0.349347E+09 0.00 0.00 0.00 0.44
July 0.00 0.893560E+09 0.00 0.00 0.395573E+09 0.00 0.00 0.00 0.44
August 0.00 0.900645E+09 0.00 0.00 0.375923E+09 0.00 0.00 0.00 0.44
September 0.00 0.778388E+09 0.00 0.00 0.367517E+09 0.00 0.00 0.00 0.43
October 0.00 0.586990E+09 0.00 0.00 0.296851E+09 0.00 0.00 0.00 0.38
November 3539238.23 0.369973E+09 0.00 16380.66 0.183806E+09 14990.36 717389.40 0.00 0.31
December 13869274.17 0.143548E+09 0.00 118182.89 0.111725E+09 70928.06 13407422.54 0.00 0.24
                   
Annual Sum or Average 60790172.45 0.592783E+10 2401.93 722306.73 0.275561E+10 559302.13 65761353.97 604.91 0.35
Minimum of Months 0.00 0.125609E+09 0.00 0.00 64879217.12 0.00 0.00 0.00 0.23
Maximum of Months 16868369.84 0.900645E+09 2401.93 204151.54 0.395573E+09 347157.37 20662566.47 604.91 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1792712.56 83976744.48 3275614.84 673.55 20831794.38 21487210.01 18433.29 541151.38 0.66
February 2222141.77 0.115461E+09 2384650.55 359593.40 21061174.19 7996789.55 782727.32 419845.07 0.81
March 1646043.74 0.159560E+09 1910166.36 26728.55 29803278.28 16963712.91 215475.52 110019.97 0.85
April 111935.19 0.220444E+09 912414.66 62537.56 37177211.18 842701.63 433109.65 50540.40 0.92
May 0.00 0.405708E+09 99504.85 0.00 65771655.49 0.00 0.00 1529.99 1.10
June 0.00 0.537639E+09 0.00 0.00 82606176.05 0.00 0.00 0.00 1.20
July 0.00 0.552777E+09 0.00 0.00 92892833.97 0.00 0.00 0.00 1.13
August 0.00 0.608018E+09 0.00 0.00 84970943.12 0.00 0.00 0.00 1.24
September 0.00 0.498826E+09 0.00 0.00 86140498.19 0.00 0.00 0.00 1.13
October 0.00 0.408613E+09 0.00 0.00 71742937.54 0.00 0.00 0.00 1.07
November 360612.44 0.269953E+09 2712512.08 186.54 47823802.37 2163116.52 480.32 161842.38 0.93
December 1223538.62 96864800.87 3880834.43 0.00 32415664.27 16239688.38 0.00 688208.69 0.66
                   
Annual Sum or Average 7356984.32 0.395784E+10 15175697.76 449719.60 0.673238E+09 65693218.98 1450226.09 1973137.89 0.98
Minimum of Months 0.00 83976744.48 0.00 0.00 20831794.38 0.00 0.00 0.00 0.66
Maximum of Months 2222141.77 0.608018E+09 3880834.43 359593.40 92892833.97 21487210.01 782727.32 688208.69 1.24



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 32937117.07 0.326729E+09 0.00 1745127.15 35254813.86 34634.59 0.175684E+09 0.00 0.83
February 21642420.35 0.385449E+09 0.00 1005118.39 38006036.06 3598465.84 65426442.90 0.00 0.85
March 20762379.51 0.502097E+09 0.00 1253178.53 56770644.19 82870.60 0.117661E+09 0.00 0.87
April 2127041.19 0.683049E+09 0.00 365450.71 98039878.20 0.00 21193916.27 0.00 0.85
May 0.00 0.126499E+10 0.00 0.00 0.152118E+09 0.00 0.00 0.00 0.89
June 0.00 0.170980E+10 0.00 0.00 0.204081E+09 0.00 0.00 0.00 0.93
July 0.00 0.181464E+10 0.00 0.00 0.232772E+09 0.00 0.00 0.00 0.86
August 0.00 0.194253E+10 0.00 0.00 0.217736E+09 0.00 0.00 0.00 0.94
September 0.00 0.174144E+10 0.00 0.00 0.201637E+09 0.00 0.00 0.00 0.93
October 0.00 0.144128E+10 0.00 0.00 0.132587E+09 0.00 0.00 0.00 0.90
November 5675757.11 0.979789E+09 0.00 336703.37 95604107.19 0.00 16652908.01 0.00 0.86
December 28793741.33 0.393637E+09 0.00 1455460.38 64270841.00 54296.12 0.148689E+09 0.00 0.80
                   
Annual Sum or Average 0.111938E+09 0.131854E+11 0.00 6161038.53 0.152888E+10 3770267.16 0.545308E+09 0.00 0.88
Minimum of Months 0.00 0.326729E+09 0.00 0.00 35254813.86 0.00 0.00 0.00 0.80
Maximum of Months 32937117.07 0.194253E+10 0.00 1745127.15 0.232772E+09 3598465.84 0.175684E+09 0.00 0.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 19970811.61 30942883.68 0.00 16025.62 28806265.27 24121.48 17493548.26 0.00 0.74
February 13312079.19 37768846.68 0.00 7793.36 30576113.13 31427.95 6171740.43 0.00 0.75
March 15750867.05 52586703.58 0.00 12390.71 37729628.71 19941.59 11157621.41 0.00 0.77
April 1732329.69 61934460.95 0.00 4956.70 67854617.05 0.00 2180575.39 0.00 0.75
May 0.00 0.115325E+09 0.00 0.00 0.116292E+09 0.00 0.00 0.00 0.77
June 0.00 0.152644E+09 37973.32 0.00 0.161262E+09 0.00 0.00 49.61 0.81
July 0.00 0.150413E+09 42657.84 0.00 0.196073E+09 0.00 0.00 178.46 0.78
August 0.00 0.166207E+09 13396.79 0.00 0.185361E+09 0.00 0.00 121.37 0.82
September 0.00 0.140023E+09 27994.73 0.00 0.172634E+09 0.00 0.00 130.95 0.79
October 0.00 0.122641E+09 0.00 0.00 0.124330E+09 0.00 0.00 0.00 0.75
November 3946113.32 93536689.68 0.00 2613.15 74008160.12 15456.59 613241.96 0.00 0.72
December 15922384.08 36804707.06 0.00 16345.23 42394475.70 23262.72 16772858.23 0.00 0.74
                   
Annual Sum or Average 70634584.94 0.116083E+10 122022.69 60124.75 0.123732E+10 114210.32 54389585.68 480.39 0.77
Minimum of Months 0.00 30942883.68 0.00 0.00 28806265.27 0.00 0.00 0.00 0.72
Maximum of Months 19970811.61 0.166207E+09 42657.84 16345.23 0.196073E+09 31427.95 17493548.26 178.46 0.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 DICTATION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2091121.24 28108475.59 0.00 208314.07 4316643.06 0.00 21070300.52 0.00 0.39
February 1638050.95 33905190.42 0.00 114530.38 5108828.45 0.00 9325229.30 0.00 0.39
March 1132158.83 43282560.13 0.00 157210.51 7358103.76 0.00 16402947.65 0.00 0.41
April 190643.44 56522576.98 0.00 38988.94 12148141.61 0.00 2233594.97 0.00 0.37
May 0.00 97821648.24 0.00 0.00 21616928.73 0.00 0.00 0.00 0.36
June 0.00 0.124168E+09 0.00 0.00 31070740.93 0.00 0.00 0.00 0.37
July 0.00 0.125026E+09 0.00 0.00 35854880.29 0.00 0.00 0.00 0.33
August 0.00 0.137719E+09 0.00 0.00 33904740.79 0.00 0.00 0.00 0.36
September 0.00 0.116900E+09 0.00 0.00 32899769.03 0.00 0.00 0.00 0.35
October 0.00 98363586.46 0.00 0.00 23322455.57 0.00 0.00 0.00 0.34
November 290356.85 74433120.24 0.00 37215.97 14303991.09 0.00 2327581.67 0.00 0.36
December 1790201.65 32182162.21 0.00 182348.11 8165517.99 0.00 18759129.31 0.00 0.39
                   
Annual Sum or Average 7132532.97 0.968432E+09 0.00 738607.98 0.230071E+09 0.00 70118783.42 0.00 0.37
Minimum of Months 0.00 28108475.59 0.00 0.00 4316643.06 0.00 0.00 0.00 0.33
Maximum of Months 2091121.24 0.137719E+09 0.00 208314.07 35854880.29 0.00 21070300.52 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 61836001.92 0.271818E+09 0.00 1015382.78 64226102.38 212235.14 0.128784E+09 0.00 0.71
February 41456575.86 0.332203E+09 0.00 588099.55 67137611.67 9457340.24 45390045.80 0.00 0.75
March 53333162.76 0.451530E+09 0.00 800867.79 92406672.45 358898.22 83923275.64 0.00 0.79
April 4529924.40 0.667029E+09 0.00 277245.32 0.115789E+09 0.00 16712776.32 0.00 0.79
May 0.00 0.116081E+10 0.00 0.00 0.249654E+09 0.00 0.00 0.00 0.83
June 0.00 0.147940E+10 0.00 0.00 0.379173E+09 0.00 0.00 0.00 0.85
July 0.00 0.163552E+10 0.00 0.00 0.386628E+09 0.00 0.00 0.00 0.80
August 0.00 0.173566E+10 0.00 0.00 0.375754E+09 0.00 0.00 0.00 0.86
September 0.00 0.146557E+10 0.00 0.00 0.373996E+09 0.00 0.00 0.00 0.82
October 0.00 0.118411E+10 0.00 0.00 0.272778E+09 0.00 0.00 0.00 0.78
November 13103020.52 0.793532E+09 0.00 181340.38 0.200230E+09 74487.00 9503371.74 0.00 0.74
December 57759057.33 0.333177E+09 0.00 914538.50 0.114307E+09 193673.27 0.109120E+09 0.00 0.72
                   
Annual Sum or Average 0.232018E+09 0.115104E+11 0.00 3777474.32 0.269208E+10 10296633.86 0.393433E+09 0.00 0.79
Minimum of Months 0.00 0.271818E+09 0.00 0.00 64226102.38 0.00 0.00 0.00 0.71
Maximum of Months 61836001.92 0.173566E+10 0.00 1015382.78 0.386628E+09 9457340.24 0.128784E+09 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.106358E+09 0.423144E+09 0.00 1310851.77 0.130432E+09 181651.84 0.239629E+09 0.00 0.82
February 85752497.40 0.480096E+09 0.00 705090.41 0.153120E+09 659383.62 93764147.76 0.00 0.82
March 68327715.17 0.601849E+09 0.00 932771.53 0.234933E+09 239347.42 0.180107E+09 0.00 0.84
April 10380024.72 0.809335E+09 173054.57 249084.95 0.392989E+09 0.00 25669908.75 55.55 0.83
May 0.00 0.145506E+10 462137.84 0.00 0.690410E+09 0.00 0.00 1266.99 0.85
June 0.00 0.190459E+10 1330470.86 0.00 0.100277E+10 0.00 0.00 3449.53 0.89
July 0.00 0.210125E+10 2077104.45 0.00 0.110727E+10 0.00 0.00 4805.04 0.86
August 0.00 0.218091E+10 1462961.37 0.00 0.107503E+10 0.00 0.00 3283.32 0.90
September 0.00 0.188993E+10 1642220.87 0.00 0.100545E+10 0.00 0.00 3387.86 0.87
October 0.00 0.156158E+10 327530.44 0.00 0.726275E+09 0.00 0.00 660.36 0.83
November 18359597.74 0.111277E+10 485263.93 242255.02 0.439048E+09 0.00 23808023.94 452.24 0.79
December 87971772.18 0.494336E+09 0.00 1209678.87 0.239445E+09 329482.52 0.213778E+09 0.00 0.82
                   
Annual Sum or Average 0.377149E+09 0.150149E+11 7960744.32 4649732.56 0.719717E+10 1409865.40 0.776756E+09 17360.89 0.84
Minimum of Months 0.00 0.423144E+09 0.00 0.00 0.130432E+09 0.00 0.00 0.00 0.79
Maximum of Months 0.106358E+09 0.218091E+10 2077104.45 1310851.77 0.110727E+10 659383.62 0.239629E+09 4805.04 0.90



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.148028E+09 0.553576E+09 447820.18 1583655.35 0.184077E+09 527704.59 0.313166E+09 1032.48 0.82
February 0.117453E+09 0.626295E+09 530524.84 791451.96 0.217462E+09 898340.13 0.122032E+09 993.63 0.82
March 0.107084E+09 0.785450E+09 132981.78 1062796.81 0.330124E+09 533830.16 0.224129E+09 973.19 0.84
April 14056808.74 0.105904E+10 963269.74 261504.14 0.543325E+09 0.00 34080378.35 3987.59 0.83
May 0.00 0.188036E+10 1780471.48 0.00 0.979100E+09 0.00 0.00 8135.40 0.85
June 0.00 0.246854E+10 2261513.75 0.00 0.140744E+10 0.00 0.00 13870.68 0.89
July 0.00 0.271335E+10 3822040.42 0.00 0.156359E+10 0.00 0.00 24403.94 0.86
August 0.00 0.282582E+10 3396473.90 0.00 0.151398E+10 0.00 0.00 14151.89 0.90
September 0.00 0.243176E+10 2903766.68 0.00 0.142803E+10 0.00 0.00 15724.75 0.87
October 0.00 0.203545E+10 2028571.77 0.00 0.101343E+10 0.00 0.00 6917.09 0.83
November 26290776.94 0.144007E+10 739885.25 260028.38 0.628929E+09 190940.56 29804756.39 3380.49 0.79
December 0.118515E+09 0.639947E+09 572569.01 1435220.00 0.337853E+09 496463.59 0.283938E+09 2632.04 0.82
                   
Annual Sum or Average 0.531427E+09 0.194597E+11 19579888.80 5394656.65 0.101473E+11 2647279.04 0.100715E+10 96203.17 0.84
Minimum of Months 0.00 0.553576E+09 132981.78 0.00 0.184077E+09 0.00 0.00 973.19 0.79
Maximum of Months 0.148028E+09 0.282582E+10 3822040.42 1583655.35 0.156359E+10 898340.13 0.313166E+09 24403.94 0.90



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 14283091.97 76422563.83 0.00 369108.14 15749243.76 44339.00 39642020.85 0.00 0.85
February 9561611.23 87336469.43 0.00 199218.75 18672611.67 1702915.24 14125242.40 0.00 0.85
March 11953866.18 0.107489E+09 0.00 237333.50 27194597.89 65020.80 23439738.92 0.00 0.85
April 1288698.13 0.137757E+09 0.00 61086.98 46044790.13 0.00 3806530.53 0.00 0.80
May 0.00 0.238683E+09 0.00 0.00 80690936.14 0.00 0.00 0.00 0.80
June 0.00 0.313992E+09 0.00 0.00 0.113007E+09 0.00 0.00 0.00 0.83
July 0.00 0.332881E+09 0.00 0.00 0.128731E+09 0.00 0.00 0.00 0.79
August 0.00 0.365063E+09 0.00 0.00 0.123967E+09 0.00 0.00 0.00 0.86
September 0.00 0.338022E+09 0.00 0.00 0.115364E+09 0.00 0.00 0.00 0.87
October 0.00 0.289835E+09 0.00 0.00 83291261.94 0.00 0.00 0.00 0.86
November 2573563.48 0.209509E+09 0.00 64885.34 51085695.08 18167.37 3258543.04 0.00 0.84
December 12634834.90 91471162.12 0.00 313557.66 28658870.41 47236.90 34459673.54 0.00 0.84
                   
Annual Sum or Average 52295665.88 0.258846E+10 0.00 1245190.36 0.832457E+09 1877679.31 0.118732E+09 0.00 0.84
Minimum of Months 0.00 76422563.83 0.00 0.00 15749243.76 0.00 0.00 0.00 0.79
Maximum of Months 14283091.97 0.365063E+09 0.00 369108.14 0.128731E+09 1702915.24 39642020.85 0.00 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 80080941.13 0.287135E+09 859.41 631466.08 93943665.32 768919.57 0.156804E+09 1034.79 0.87
February 55759728.81 0.329978E+09 0.00 544817.67 0.110089E+09 5361761.42 63390147.04 0.00 0.88
March 48333735.16 0.445123E+09 4300.43 791105.88 0.152589E+09 623515.95 0.125834E+09 856.09 0.93
April 7008892.90 0.644986E+09 0.00 283598.12 0.249990E+09 0.00 20175783.79 0.00 0.95
May 0.00 0.120154E+10 0.00 0.00 0.415677E+09 0.00 0.00 0.00 0.99
June 0.00 0.162593E+10 0.00 0.00 0.557302E+09 0.00 0.00 0.00 1.03
July 0.00 0.173238E+10 0.00 0.00 0.632498E+09 0.00 0.00 0.00 0.97
August 0.00 0.175611E+10 0.00 0.00 0.634262E+09 0.00 0.00 0.00 1.02
September 0.00 0.147452E+10 0.00 0.00 0.634769E+09 0.00 0.00 0.00 0.98
October 0.00 0.115068E+10 0.00 0.00 0.481373E+09 0.00 0.00 0.00 0.91
November 14801786.59 0.781477E+09 72713.11 154502.15 0.294244E+09 98174.93 14052330.30 34.84 0.85
December 73272764.01 0.334771E+09 127339.19 450672.72 0.170505E+09 837524.27 0.133360E+09 1030.19 0.87
                   
Annual Sum or Average 0.279258E+09 0.117646E+11 205212.14 2856162.62 0.442724E+10 7689896.14 0.513616E+09 2955.91 0.94
Minimum of Months 0.00 0.287135E+09 0.00 0.00 93943665.32 0.00 0.00 0.00 0.85
Maximum of Months 80080941.13 0.175611E+10 127339.19 791105.88 0.634769E+09 5361761.42 0.156804E+09 1034.79 1.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 68022877.36 0.175895E+09 61790.11 149923.45 66577796.47 390100.11 83676480.85 797.56 0.86
February 45413314.27 0.204042E+09 109350.80 82842.97 73276410.69 4648633.64 29103702.73 23.07 0.87
March 53606476.25 0.257363E+09 2726.74 139480.32 0.109249E+09 413401.77 55199602.17 568.70 0.89
April 4547745.65 0.357211E+09 0.00 92099.06 0.169633E+09 0.00 11263653.36 0.00 0.87
May 0.00 0.651467E+09 0.00 0.00 0.288721E+09 0.00 0.00 0.00 0.89
June 0.00 0.864321E+09 0.00 0.00 0.410054E+09 0.00 0.00 0.00 0.93
July 0.00 0.952833E+09 0.00 0.00 0.453809E+09 0.00 0.00 0.00 0.90
August 0.00 0.975894E+09 0.00 0.00 0.451255E+09 0.00 0.00 0.00 0.94
September 0.00 0.840770E+09 135603.40 0.00 0.428356E+09 0.00 0.00 67.16 0.92
October 0.00 0.681985E+09 143502.22 0.00 0.320384E+09 0.00 0.00 286.29 0.87
November 14216410.85 0.477980E+09 243875.56 35630.05 0.201879E+09 62741.84 4266033.54 356.77 0.83
December 53546384.75 0.206774E+09 293310.57 172509.14 0.114420E+09 469859.95 78689499.14 536.53 0.86
                   
Annual Sum or Average 0.239353E+09 0.664653E+10 990159.40 672484.99 0.308761E+10 5984737.30 0.262199E+09 2636.06 0.89
Minimum of Months 0.00 0.175895E+09 0.00 0.00 66577796.47 0.00 0.00 0.00 0.83
Maximum of Months 68022877.36 0.975894E+09 293310.57 172509.14 0.453809E+09 4648633.64 83676480.85 797.56 0.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.174022E+09 0.599350E+09 207627.74 877514.25 0.212353E+09 474492.41 0.334262E+09 1890.79 0.82
February 0.146409E+09 0.679965E+09 365627.39 441008.42 0.248386E+09 1033588.69 0.117409E+09 512.62 0.82
March 0.114976E+09 0.860541E+09 10233.76 786627.48 0.366727E+09 351042.88 0.249977E+09 798.06 0.84
April 15462489.61 0.118343E+10 640888.81 315952.96 0.579588E+09 0.00 37460117.78 860.26 0.83
May 0.00 0.213503E+10 1154920.76 0.00 0.101118E+10 0.00 0.00 1991.19 0.85
June 0.00 0.281386E+10 1675104.91 0.00 0.145055E+10 0.00 0.00 4489.49 0.89
July 0.00 0.310066E+10 2852691.91 0.00 0.160536E+10 0.00 0.00 6081.92 0.86
August 0.00 0.319849E+10 2144624.88 0.00 0.157689E+10 0.00 0.00 5867.32 0.90
September 0.00 0.272657E+10 2606491.94 0.00 0.151979E+10 0.00 0.00 9474.22 0.87
October 0.00 0.222840E+10 1450796.28 0.00 0.112615E+10 0.00 0.00 3149.02 0.83
November 37565965.41 0.159448E+10 815301.09 162658.83 0.681416E+09 104537.90 24367990.36 2291.22 0.79
December 0.142564E+09 0.697066E+09 982027.85 894743.82 0.378162E+09 546109.95 0.300818E+09 1654.87 0.82
                   
Annual Sum or Average 0.630999E+09 0.218178E+11 14906337.33 3478505.76 0.107565E+11 2509771.84 0.106429E+10 39060.99 0.84
Minimum of Months 0.00 0.599350E+09 10233.76 0.00 0.212353E+09 0.00 0.00 512.62 0.79
Maximum of Months 0.174022E+09 0.319849E+10 2852691.91 894743.82 0.160536E+10 1033588.69 0.334262E+09 9474.22 0.90



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 70556018.27 0.217607E+09 1072.79 275857.32 72779425.65 264973.96 0.111179E+09 376.60 0.86
February 54524987.53 0.250457E+09 0.00 150482.99 81708280.22 1573877.00 38634930.18 0.00 0.86
March 50433258.72 0.318873E+09 3720.17 245882.52 0.120088E+09 431661.47 79824758.39 225.47 0.88
April 5439287.82 0.434430E+09 0.00 134377.64 0.196361E+09 0.00 13467604.07 0.00 0.87
May 0.00 0.794118E+09 0.00 0.00 0.333315E+09 0.00 0.00 0.00 0.89
June 0.00 0.104663E+10 0.00 0.00 0.480525E+09 0.00 0.00 0.00 0.93
July 0.00 0.114619E+10 0.00 0.00 0.538010E+09 0.00 0.00 0.00 0.90
August 0.00 0.117197E+10 0.00 0.00 0.536761E+09 0.00 0.00 0.00 0.94
September 0.00 0.100955E+10 0.00 0.00 0.510138E+09 0.00 0.00 0.00 0.92
October 0.00 0.821407E+09 171964.34 0.00 0.378731E+09 0.00 0.00 193.75 0.87
November 15425577.55 0.581336E+09 0.00 63462.54 0.232951E+09 75120.85 6682663.59 0.00 0.83
December 59326976.24 0.257293E+09 0.00 301332.64 0.127624E+09 218824.16 99248093.64 0.00 0.86
                   
Annual Sum or Average 0.255706E+09 0.804986E+10 176757.29 1171395.65 0.360899E+10 2564457.44 0.349038E+09 795.82 0.88
Minimum of Months 0.00 0.217607E+09 0.00 0.00 72779425.65 0.00 0.00 0.00 0.83
Maximum of Months 70556018.27 0.117197E+10 171964.34 301332.64 0.538010E+09 1573877.00 0.111179E+09 376.60 0.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 86528870.81 0.321177E+09 2128.38 523391.74 0.108057E+09 140850.85 0.182239E+09 14.04 0.86
February 76638711.71 0.365875E+09 0.00 278807.74 0.125114E+09 511278.85 62824445.56 0.00 0.87
March 57331629.83 0.464054E+09 0.00 460457.00 0.184778E+09 185587.37 0.135565E+09 0.00 0.89
April 8095199.89 0.631664E+09 0.00 177084.09 0.300739E+09 0.00 19873578.37 0.00 0.88
May 0.00 0.113565E+10 359166.60 0.00 0.527925E+09 0.00 0.00 152.44 0.90
June 0.00 0.149908E+10 683059.28 0.00 0.755604E+09 0.00 0.00 590.20 0.94
July 0.00 0.164588E+10 1137211.09 0.00 0.842439E+09 0.00 0.00 946.61 0.91
August 0.00 0.169569E+10 816475.99 0.00 0.829246E+09 0.00 0.00 681.89 0.95
September 0.00 0.145941E+10 971254.76 0.00 0.785939E+09 0.00 0.00 1681.78 0.92
October 0.00 0.119303E+10 253936.97 0.00 0.580952E+09 0.00 0.00 538.59 0.87
November 15549062.85 0.849779E+09 294099.45 100146.49 0.353567E+09 55266.51 17179679.25 238.62 0.83
December 71965692.06 0.373057E+09 201360.70 521163.82 0.195707E+09 255477.14 0.162424E+09 67.02 0.86
                   
Annual Sum or Average 0.316109E+09 0.116344E+11 4718693.23 2061050.90 0.559007E+10 1148460.74 0.580106E+09 4911.18 0.89
Minimum of Months 0.00 0.321177E+09 0.00 0.00 0.108057E+09 0.00 0.00 0.00 0.83
Maximum of Months 86528870.81 0.169569E+10 1137211.09 523391.74 0.842439E+09 511278.85 0.182239E+09 1681.78 0.95



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6980827.53 77247613.41 0.00 422383.56 9515589.21 0.00 42306170.19 0.00 0.37
February 6655092.19 91147580.69 0.00 240422.26 11621626.16 26177.15 16154919.19 0.00 0.38
March 4426340.05 0.118686E+09 0.00 314702.98 17043559.16 0.00 29380079.49 0.00 0.39
April 483855.08 0.157051E+09 0.00 90238.68 27188602.91 0.00 5199090.35 0.00 0.38
May 0.00 0.270264E+09 0.00 0.00 49559884.02 0.00 0.00 0.00 0.37
June 0.00 0.340769E+09 0.00 0.00 72868399.97 0.00 0.00 0.00 0.38
July 0.00 0.352743E+09 0.00 0.00 83396029.89 0.00 0.00 0.00 0.34
August 0.00 0.390432E+09 0.00 0.00 77853074.73 0.00 0.00 0.00 0.38
September 0.00 0.340109E+09 0.00 0.00 75658856.38 0.00 0.00 0.00 0.37
October 0.00 0.289514E+09 0.00 0.00 52449610.61 0.00 0.00 0.00 0.37
November 1436338.49 0.214815E+09 0.00 74005.24 32756039.32 0.00 3667905.15 0.00 0.37
December 5737750.80 90721580.19 0.00 371577.34 18753159.79 0.00 38120108.35 0.00 0.37
                   
Annual Sum or Average 25720204.14 0.273350E+10 0.00 1513330.07 0.528664E+09 26177.15 0.134828E+09 0.00 0.37
Minimum of Months 0.00 77247613.41 0.00 0.00 9515589.21 0.00 0.00 0.00 0.34
Maximum of Months 6980827.53 0.390432E+09 0.00 422383.56 83396029.89 26177.15 42306170.19 0.00 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6247497.63 73572090.10 0.00 451132.56 9902466.29 0.00 45190612.42 0.00 0.37
February 6090267.38 86710785.87 0.00 241548.85 11741777.28 0.00 17462163.44 0.00 0.37
March 4035810.53 0.108370E+09 0.00 322878.89 17098724.82 0.00 31058346.49 0.00 0.38
April 510758.88 0.135644E+09 0.00 80643.39 29514006.73 0.00 4754685.01 0.00 0.34
May 0.00 0.225651E+09 0.00 0.00 55666919.44 0.00 0.00 0.00 0.33
June 0.00 0.279226E+09 0.00 0.00 82185859.65 0.00 0.00 0.00 0.33
July 0.00 0.283996E+09 0.00 0.00 90813594.03 0.00 0.00 0.00 0.30
August 0.00 0.316615E+09 0.00 0.00 88683571.35 0.00 0.00 0.00 0.33
September 0.00 0.282035E+09 0.00 0.00 83513275.40 0.00 0.00 0.00 0.33
October 0.00 0.247344E+09 0.00 0.00 58491541.00 0.00 0.00 0.00 0.33
November 1451989.49 0.196032E+09 0.00 76439.89 34066718.68 0.00 3917127.63 0.00 0.35
December 5511876.99 85165400.34 0.00 392764.13 18933614.78 0.00 40028132.08 0.00 0.36
                   
Annual Sum or Average 23848200.89 0.232036E+10 0.00 1565407.71 0.580612E+09 0.00 0.142411E+09 0.00 0.34
Minimum of Months 0.00 73572090.10 0.00 0.00 9902466.29 0.00 0.00 0.00 0.30
Maximum of Months 6247497.63 0.316615E+09 0.00 451132.56 90813594.03 0.00 45190612.42 0.00 0.38



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6558203.59 65572877.84 0.00 396578.58 10343216.37 0.00 40238214.92 0.00 0.34
February 6579283.31 77439793.77 0.00 207174.88 11792768.85 0.00 14819851.89 0.00 0.34
March 4473033.74 94456566.44 0.00 280395.58 17931951.40 0.00 26668703.32 0.00 0.34
April 788460.71 0.118427E+09 0.00 69103.21 30317388.03 0.00 3865211.36 0.00 0.31
May 0.00 0.200182E+09 0.00 0.00 55470793.65 0.00 0.00 0.00 0.30
June 0.00 0.253912E+09 0.00 0.00 80337772.64 0.00 0.00 0.00 0.31
July 0.00 0.259134E+09 0.00 0.00 88748446.45 0.00 0.00 0.00 0.28
August 0.00 0.288544E+09 0.00 0.00 86512823.13 0.00 0.00 0.00 0.31
September 0.00 0.256191E+09 0.00 0.00 82010888.77 0.00 0.00 0.00 0.30
October 0.00 0.222343E+09 0.00 0.00 58286222.39 0.00 0.00 0.00 0.30
November 1384530.91 0.176999E+09 0.00 63895.48 34663510.74 0.00 3195669.82 0.00 0.32
December 5493649.29 76268909.83 0.00 345760.40 19079331.44 0.00 35984287.71 0.00 0.33
                   
Annual Sum or Average 25277161.55 0.208947E+10 0.00 1362908.12 0.575495E+09 0.00 0.124772E+09 0.00 0.31
Minimum of Months 0.00 65572877.84 0.00 0.00 10343216.37 0.00 0.00 0.00 0.28
Maximum of Months 6579283.31 0.288544E+09 0.00 396578.58 88748446.45 0.00 40238214.92 0.00 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 7118275.41 63478412.23 0.00 355944.42 10764578.25 0.00 37245038.85 0.00 0.29
February 7091319.30 81539289.59 0.00 194784.68 12366270.47 0.00 15392675.04 0.00 0.31
March 3897799.48 0.107067E+09 0.00 297644.72 18379943.20 0.00 31055834.44 0.00 0.34
April 522812.45 0.147526E+09 0.00 91853.64 29383815.21 0.00 5354219.40 0.00 0.34
May 0.00 0.275660E+09 0.00 0.00 52355839.93 0.00 0.00 0.00 0.35
June 0.00 0.356988E+09 0.00 0.00 75363679.53 0.00 0.00 0.00 0.36
July 0.00 0.360295E+09 0.00 0.00 87263692.11 0.00 0.00 0.00 0.32
August 0.00 0.379297E+09 0.00 0.00 82792010.11 0.00 0.00 0.00 0.35
September 0.00 0.312873E+09 0.00 0.00 81377817.23 0.00 0.00 0.00 0.32
October 0.00 0.247649E+09 0.00 0.00 59209260.82 0.00 0.00 0.00 0.30
November 1546400.88 0.180863E+09 0.00 66308.96 35649903.78 0.00 3493011.46 0.00 0.30
December 5843741.34 73854219.94 0.00 327561.71 20548331.81 0.00 34644486.84 0.00 0.30
                   
Annual Sum or Average 26020348.86 0.258709E+10 0.00 1334098.13 0.565455E+09 0.00 0.127185E+09 0.00 0.32
Minimum of Months 0.00 63478412.23 0.00 0.00 10764578.25 0.00 0.00 0.00 0.29
Maximum of Months 7118275.41 0.379297E+09 0.00 355944.42 87263692.11 0.00 37245038.85 0.00 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6697031.02 71313157.46 0.00 411555.64 10769718.28 0.00 42394986.54 0.00 0.32
February 6774918.31 90533058.10 0.00 224877.19 12436617.69 0.00 17640868.69 0.00 0.34
March 3524614.21 0.119282E+09 0.00 336820.88 18402077.16 0.00 35098550.69 0.00 0.37
April 494476.95 0.162951E+09 0.00 102793.24 29512047.53 0.00 5873125.56 0.00 0.37
May 0.00 0.304531E+09 0.00 0.00 51815545.80 0.00 0.00 0.00 0.38
June 0.00 0.392828E+09 0.00 0.00 74840245.50 0.00 0.00 0.00 0.39
July 0.00 0.398357E+09 0.00 0.00 86495401.19 0.00 0.00 0.00 0.35
August 0.00 0.419033E+09 0.00 0.00 81248949.76 0.00 0.00 0.00 0.37
September 0.00 0.346508E+09 0.00 0.00 80949300.47 0.00 0.00 0.00 0.35
October 0.00 0.278777E+09 0.00 0.00 56193255.07 0.00 0.00 0.00 0.33
November 1124026.80 0.200521E+09 0.00 81439.92 35704898.26 0.00 4662602.05 0.00 0.33
December 6027514.96 83232460.51 0.00 374857.01 20329876.23 0.00 38488245.13 0.00 0.32
                   
Annual Sum or Average 24642582.25 0.286787E+10 0.00 1532343.88 0.558698E+09 0.00 0.144158E+09 0.00 0.35
Minimum of Months 0.00 71313157.46 0.00 0.00 10769718.28 0.00 0.00 0.00 0.32
Maximum of Months 6774918.31 0.419033E+09 0.00 411555.64 86495401.19 0.00 42394986.54 0.00 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6911517.95 67097091.01 0.00 380996.79 10882005.42 0.00 39618653.59 0.00 0.31
February 7129911.24 85224899.42 0.00 208772.03 12638752.26 0.00 16225599.07 0.00 0.32
March 3767281.69 0.112670E+09 0.00 311145.82 18386074.09 0.00 32514145.47 0.00 0.35
April 520550.71 0.152961E+09 0.00 94667.06 29790429.37 0.00 5479905.72 0.00 0.35
May 0.00 0.284263E+09 0.00 0.00 53260979.06 0.00 0.00 0.00 0.36
June 0.00 0.366342E+09 0.00 0.00 76891157.33 0.00 0.00 0.00 0.37
July 0.00 0.370403E+09 0.00 0.00 88549169.61 0.00 0.00 0.00 0.33
August 0.00 0.389164E+09 0.00 0.00 84807251.36 0.00 0.00 0.00 0.35
September 0.00 0.322808E+09 0.00 0.00 82327641.01 0.00 0.00 0.00 0.33
October 0.00 0.258568E+09 0.00 0.00 59161859.89 0.00 0.00 0.00 0.31
November 1126261.46 0.188502E+09 0.00 75021.42 35906243.54 0.00 4350916.96 0.00 0.31
December 5985648.16 78213465.66 0.00 347137.00 20458009.92 0.00 36181099.05 0.00 0.31
                   
Annual Sum or Average 25441171.21 0.267622E+10 0.00 1417740.12 0.573060E+09 0.00 0.134370E+09 0.00 0.33
Minimum of Months 0.00 67097091.01 0.00 0.00 10882005.42 0.00 0.00 0.00 0.31
Maximum of Months 7129911.24 0.389164E+09 0.00 380996.79 88549169.61 0.00 39618653.59 0.00 0.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 9853711.07 22222827.47 0.00 32822.92 4838611.21 150060.52 3178462.81 0.00 0.30
February 4737194.66 29395622.29 0.00 19451.73 5131081.65 1019542.14 961655.80 0.00 0.34
March 7436741.23 42423558.41 0.00 30369.42 7157235.92 442317.36 1630265.32 0.00 0.37
April 310787.25 65279049.69 0.00 25114.41 9791114.40 0.00 1461692.43 0.00 0.42
May 0.00 0.134290E+09 0.00 0.00 15083177.92 0.00 0.00 0.00 0.50
June 0.00 0.184509E+09 0.00 0.00 20585336.85 0.00 0.00 0.00 0.53
July 0.00 0.205378E+09 0.00 0.00 19955079.46 0.00 0.00 0.00 0.51
August 0.00 0.201735E+09 0.00 0.00 22547786.18 0.00 0.00 0.00 0.52
September 0.00 0.168303E+09 0.00 0.00 23163375.13 0.00 0.00 0.00 0.49
October 0.00 0.119734E+09 0.00 0.00 18525615.42 0.00 0.00 0.00 0.42
November 1349641.42 77131738.17 0.00 11153.50 13193501.04 5523.59 279397.44 0.00 0.37
December 7704460.35 29277455.91 0.00 37591.60 7978759.43 341918.43 3720369.59 0.00 0.31
                   
Annual Sum or Average 31392535.99 0.127968E+10 0.00 156503.59 0.167951E+09 1959362.04 11231843.40 0.00 0.42
Minimum of Months 0.00 22222827.47 0.00 0.00 4838611.21 0.00 0.00 0.00 0.30
Maximum of Months 9853711.07 0.205378E+09 0.00 37591.60 23163375.13 1019542.14 3720369.59 0.00 0.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2759035.37 56063956.02 0.00 404248.92 5804985.96 0.00 40710395.82 0.00 0.65
February 2210728.01 67146938.61 0.00 229386.92 6879972.74 0.00 17920779.52 0.00 0.65
March 1453881.28 87869174.71 0.00 307935.86 10401159.48 0.00 32290111.28 0.00 0.69
April 275157.86 0.118040E+09 0.00 82095.82 16519972.63 0.00 4604205.45 0.00 0.64
May 0.00 0.213806E+09 0.00 0.00 27396783.15 0.00 0.00 0.00 0.64
June 0.00 0.276965E+09 0.00 0.00 39056180.78 0.00 0.00 0.00 0.65
July 0.00 0.282873E+09 0.00 0.00 45066748.95 0.00 0.00 0.00 0.58
August 0.00 0.306695E+09 0.00 0.00 42355526.06 0.00 0.00 0.00 0.65
September 0.00 0.258652E+09 0.00 0.00 42556343.21 0.00 0.00 0.00 0.61
October 0.00 0.214975E+09 0.00 0.00 29193263.90 0.00 0.00 0.00 0.60
November 355057.49 0.152533E+09 0.00 77623.13 19376366.41 0.00 4797496.58 0.00 0.60
December 2338915.05 63703721.81 0.00 359357.53 11222937.98 0.00 36371859.91 0.00 0.63
                   
Annual Sum or Average 9392775.05 0.209932E+10 0.00 1460648.18 0.295830E+09 0.00 0.136695E+09 0.00 0.63
Minimum of Months 0.00 56063956.02 0.00 0.00 5804985.96 0.00 0.00 0.00 0.58
Maximum of Months 2759035.37 0.306695E+09 0.00 404248.92 45066748.95 0.00 40710395.82 0.00 0.69



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4278480.21 91484402.24 0.00 648909.23 9138465.83 0.00 64613832.81 0.00 0.55
February 3483400.96 0.110465E+09 0.00 369026.50 10841343.79 0.00 28545209.77 0.00 0.56
March 2250525.03 0.146010E+09 0.00 503245.98 16271331.45 0.00 52233132.69 0.00 0.60
April 418331.60 0.198022E+09 0.00 140511.08 25850310.32 0.00 7689949.17 0.00 0.57
May 0.00 0.365007E+09 0.00 0.00 42449950.88 0.00 0.00 0.00 0.58
June 0.00 0.475982E+09 0.00 0.00 59547405.41 0.00 0.00 0.00 0.59
July 0.00 0.489672E+09 0.00 0.00 67456953.22 0.00 0.00 0.00 0.53
August 0.00 0.524150E+09 0.00 0.00 64358424.00 0.00 0.00 0.00 0.58
September 0.00 0.439961E+09 0.00 0.00 64534650.75 0.00 0.00 0.00 0.55
October 0.00 0.360821E+09 0.00 0.00 45180324.43 0.00 0.00 0.00 0.53
November 559314.50 0.252863E+09 0.00 127018.24 30126242.24 0.00 7664028.83 0.00 0.53
December 3673271.13 0.104467E+09 0.00 581330.17 17625949.68 0.00 58195905.80 0.00 0.55
                   
Annual Sum or Average 14663323.43 0.355891E+10 0.00 2370041.20 0.453381E+09 0.00 0.218942E+09 0.00 0.56
Minimum of Months 0.00 91484402.24 0.00 0.00 9138465.83 0.00 0.00 0.00 0.53
Maximum of Months 4278480.21 0.524150E+09 0.00 648909.23 67456953.22 0.00 64613832.81 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 5139098.95 0.114278E+09 0.00 822437.91 10922103.54 0.00 81006461.99 0.00 0.57
February 4160090.53 0.137955E+09 0.00 468924.29 12935141.72 0.00 35834719.71 0.00 0.58
March 2694033.46 0.182409E+09 0.00 632610.26 19688085.02 0.00 65348013.03 0.00 0.62
April 500593.08 0.246351E+09 0.00 177643.02 31151336.53 0.00 9520444.08 0.00 0.59
May 0.00 0.455361E+09 0.00 0.00 50890514.69 0.00 0.00 0.00 0.60
June 0.00 0.591801E+09 0.00 0.00 71480886.08 0.00 0.00 0.00 0.61
July 0.00 0.608245E+09 0.00 0.00 81155510.74 0.00 0.00 0.00 0.55
August 0.00 0.650005E+09 0.00 0.00 77254998.80 0.00 0.00 0.00 0.60
September 0.00 0.545459E+09 0.00 0.00 77143211.60 0.00 0.00 0.00 0.56
October 0.00 0.448479E+09 0.00 0.00 54348495.24 0.00 0.00 0.00 0.54
November 631680.63 0.314232E+09 0.00 166669.76 36303808.59 0.00 10024273.87 0.00 0.55
December 4454264.09 0.130602E+09 0.00 735350.46 21201344.18 0.00 72646802.67 0.00 0.57
                   
Annual Sum or Average 17579760.76 0.442518E+10 0.00 3003635.71 0.544475E+09 0.00 0.274381E+09 0.00 0.58
Minimum of Months 0.00 0.114278E+09 0.00 0.00 10922103.54 0.00 0.00 0.00 0.54
Maximum of Months 5139098.95 0.650005E+09 0.00 822437.91 81155510.74 0.00 81006461.99 0.00 0.62



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 45977865.29 0.271243E+09 0.00 1093476.18 47066039.19 130090.59 0.121995E+09 0.00 0.41
February 29971478.33 0.340638E+09 0.00 801050.46 54890008.24 3262118.93 53248956.35 0.00 0.46
March 30158086.47 0.494706E+09 0.00 1135482.83 78153628.87 97983.28 0.117080E+09 0.00 0.53
April 3084676.63 0.769833E+09 0.00 372511.15 0.123360E+09 0.00 23807730.32 0.00 0.59
May 0.00 0.145389E+10 0.00 0.00 0.206030E+09 0.00 0.00 0.00 0.62
June 0.00 0.200065E+10 0.00 0.00 0.274460E+09 0.00 0.00 0.00 0.66
July 0.00 0.216221E+10 0.00 0.00 0.291569E+09 0.00 0.00 0.00 0.62
August 0.00 0.214609E+10 0.00 0.00 0.301338E+09 0.00 0.00 0.00 0.64
September 0.00 0.182845E+10 0.00 0.00 0.297616E+09 0.00 0.00 0.00 0.61
October 0.00 0.137014E+10 0.00 0.00 0.219133E+09 0.00 0.00 0.00 0.55
November 8382358.25 0.838225E+09 0.00 234057.37 0.145604E+09 56171.48 11644745.49 0.00 0.47
December 41410103.71 0.318861E+09 0.00 845963.38 87231438.07 177124.75 94702829.16 0.00 0.40
                   
Annual Sum or Average 0.158985E+09 0.139949E+11 0.00 4482541.36 0.212645E+10 3723489.03 0.422480E+09 0.00 0.55
Minimum of Months 0.00 0.271243E+09 0.00 0.00 47066039.19 0.00 0.00 0.00 0.40
Maximum of Months 45977865.29 0.216221E+10 0.00 1135482.83 0.301338E+09 3262118.93 0.121995E+09 0.00 0.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 18654153.52 0.146294E+09 0.00 761868.20 23367875.74 0.00 80003409.32 0.00 0.29
February 16933708.29 0.179961E+09 0.00 457076.26 27762150.42 0.00 33132652.58 0.00 0.31
March 11030517.55 0.246679E+09 0.00 670862.18 40217740.39 0.00 69042860.88 0.00 0.34
April 1122512.65 0.348698E+09 0.00 212105.36 64024707.91 0.00 12591638.07 0.00 0.35
May 0.00 0.644766E+09 0.00 0.00 0.111058E+09 0.00 0.00 0.00 0.36
June 0.00 0.856640E+09 0.00 0.00 0.156461E+09 0.00 0.00 0.00 0.37
July 0.00 0.894617E+09 0.00 0.00 0.177365E+09 0.00 0.00 0.00 0.34
August 0.00 0.940392E+09 0.00 0.00 0.168219E+09 0.00 0.00 0.00 0.37
September 0.00 0.791765E+09 0.00 0.00 0.166510E+09 0.00 0.00 0.00 0.35
October 0.00 0.624697E+09 0.00 0.00 0.120120E+09 0.00 0.00 0.00 0.33
November 3432434.66 0.423753E+09 0.00 139943.54 77442036.60 0.00 7482061.97 0.00 0.31
December 14874974.78 0.167588E+09 0.00 669955.16 44835938.62 0.00 72033451.17 0.00 0.29
                   
Annual Sum or Average 66048301.46 0.626585E+10 0.00 2911810.70 0.117738E+10 0.00 0.274286E+09 0.00 0.33
Minimum of Months 0.00 0.146294E+09 0.00 0.00 23367875.74 0.00 0.00 0.00 0.29
Maximum of Months 18654153.52 0.940392E+09 0.00 761868.20 0.177365E+09 0.00 80003409.32 0.00 0.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 39536497.20 0.796548E+09 0.00 4541709.72 64399258.33 0.00 0.450153E+09 0.00 0.67
February 39911560.29 0.956561E+09 0.00 2586929.51 61484225.74 200132.03 0.174190E+09 0.00 0.68
March 22518025.70 0.127358E+10 0.00 3364635.00 97076873.64 0.00 0.323960E+09 0.00 0.72
April 2219075.35 0.177077E+10 0.00 1023660.58 0.124124E+09 0.00 56285656.05 0.00 0.71
May 0.00 0.323102E+10 0.00 0.00 0.224353E+09 0.00 0.00 0.00 0.74
June 0.00 0.425660E+10 0.00 0.00 0.324888E+09 0.00 0.00 0.00 0.76
July 0.00 0.456838E+10 0.00 0.00 0.323532E+09 0.00 0.00 0.00 0.70
August 0.00 0.484353E+10 0.00 0.00 0.342943E+09 0.00 0.00 0.00 0.77
September 0.00 0.421791E+10 0.00 0.00 0.316677E+09 0.00 0.00 0.00 0.74
October 0.00 0.345233E+10 0.00 0.00 0.218199E+09 0.00 0.00 0.00 0.71
November 5187878.74 0.233666E+10 0.00 888906.45 0.176003E+09 0.00 47191861.92 0.00 0.69
December 38998038.35 0.960640E+09 0.00 4031789.82 0.109700E+09 0.00 0.403848E+09 0.00 0.67
                   
Annual Sum or Average 0.148371E+09 0.326645E+11 0.00 16437631.08 0.238338E+10 200132.03 0.145563E+10 0.00 0.71
Minimum of Months 0.00 0.796548E+09 0.00 0.00 61484225.74 0.00 0.00 0.00 0.67
Maximum of Months 39911560.29 0.484353E+10 0.00 4541709.72 0.342943E+09 200132.03 0.450153E+09 0.00 0.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 15013690.60 0.232433E+09 0.00 1628721.92 29182893.91 0.00 0.160523E+09 0.00 0.38
February 11666861.29 0.278869E+09 0.00 909124.19 34823083.79 0.00 70061492.63 0.00 0.38
March 8331104.25 0.359494E+09 0.00 1225471.53 52460201.08 0.00 0.123845E+09 0.00 0.41
April 1352243.08 0.477291E+09 0.00 319488.49 83550280.21 0.00 17771780.18 0.00 0.38
May 0.00 0.833695E+09 0.00 0.00 0.148697E+09 0.00 0.00 0.00 0.37
June 0.00 0.106140E+10 0.00 0.00 0.214194E+09 0.00 0.00 0.00 0.37
July 0.00 0.107839E+10 0.00 0.00 0.247917E+09 0.00 0.00 0.00 0.34
August 0.00 0.118350E+10 0.00 0.00 0.230228E+09 0.00 0.00 0.00 0.37
September 0.00 0.100538E+10 0.00 0.00 0.226625E+09 0.00 0.00 0.00 0.35
October 0.00 0.846057E+09 0.00 0.00 0.156098E+09 0.00 0.00 0.00 0.35
November 2091480.88 0.623467E+09 0.00 300329.66 99523030.75 0.00 17876217.42 0.00 0.36
December 12837678.15 0.267506E+09 0.00 1425487.89 57020333.07 0.00 0.143290E+09 0.00 0.38
                   
Annual Sum or Average 51293058.26 0.824748E+10 0.00 5808623.68 0.158032E+10 0.00 0.533368E+09 0.00 0.37
Minimum of Months 0.00 0.232433E+09 0.00 0.00 29182893.91 0.00 0.00 0.00 0.34
Maximum of Months 15013690.60 0.118350E+10 0.00 1628721.92 0.247917E+09 0.00 0.160523E+09 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 27156530.73 73742141.86 0.00 73585.07 35940094.71 0.00 41617361.99 0.00 0.69
February 19551983.19 86613514.35 0.00 40072.49 38848156.35 57692.66 16188934.40 0.00 0.70
March 17638042.01 0.110982E+09 0.00 56116.61 54812968.44 0.00 31761432.43 0.00 0.72
April 2139892.93 0.150428E+09 0.00 21934.63 87827498.53 0.00 5030238.76 0.00 0.70
May 0.00 0.255752E+09 0.00 0.00 0.169431E+09 0.00 0.00 0.00 0.72
June 0.00 0.303651E+09 0.00 0.00 0.272660E+09 0.00 0.00 0.00 0.75
July 0.00 0.346780E+09 0.00 0.00 0.289348E+09 0.00 0.00 0.00 0.73
August 0.00 0.361808E+09 0.00 0.00 0.283595E+09 0.00 0.00 0.00 0.76
September 0.00 0.307226E+09 0.00 0.00 0.266774E+09 0.00 0.00 0.00 0.74
October 0.00 0.264385E+09 0.00 0.00 0.188982E+09 0.00 0.00 0.00 0.70
November 3833448.11 0.198769E+09 0.00 12991.03 0.108795E+09 0.00 4556395.40 0.00 0.67
December 24875466.36 88009156.70 0.00 72343.17 57377742.55 0.00 35143951.65 0.00 0.69
                   
Annual Sum or Average 95195363.33 0.254814E+10 0.00 277043.01 0.185439E+10 57692.66 0.134298E+09 0.00 0.71
Minimum of Months 0.00 73742141.86 0.00 0.00 35940094.71 0.00 0.00 0.00 0.67
Maximum of Months 27156530.73 0.361808E+09 0.00 73585.07 0.289348E+09 57692.66 41617361.99 0.00 0.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 7231975.81 0.133417E+09 0.00 1012510.67 15287346.41 0.00 98141356.42 0.00 0.39
February 5857871.88 0.160490E+09 0.00 572763.68 18099637.75 0.00 44179007.83 0.00 0.39
March 3807316.81 0.209065E+09 0.00 774917.38 27385126.14 0.00 78836995.25 0.00 0.41
April 742169.46 0.281905E+09 0.00 199576.88 43363261.62 0.00 11008764.46 0.00 0.39
May 0.00 0.505641E+09 0.00 0.00 72865603.27 0.00 0.00 0.00 0.38
June 0.00 0.651374E+09 0.00 0.00 0.105054E+09 0.00 0.00 0.00 0.38
July 0.00 0.667455E+09 0.00 0.00 0.119738E+09 0.00 0.00 0.00 0.35
August 0.00 0.721291E+09 0.00 0.00 0.112362E+09 0.00 0.00 0.00 0.38
September 0.00 0.606990E+09 0.00 0.00 0.113225E+09 0.00 0.00 0.00 0.36
October 0.00 0.503022E+09 0.00 0.00 77494244.73 0.00 0.00 0.00 0.35
November 937469.78 0.360008E+09 0.00 193910.04 51293817.11 0.00 11667407.60 0.00 0.36
December 6142248.11 0.152504E+09 0.00 895500.43 29791281.89 0.00 87827413.77 0.00 0.38
                   
Annual Sum or Average 24719051.84 0.495316E+10 0.00 3649179.10 0.785959E+09 0.00 0.331661E+09 0.00 0.38
Minimum of Months 0.00 0.133417E+09 0.00 0.00 15287346.41 0.00 0.00 0.00 0.35
Maximum of Months 7231975.81 0.721291E+09 0.00 1012510.67 0.119738E+09 0.00 98141356.42 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 7502487.80 0.148367E+09 0.00 1125872.06 16113069.50 0.00 0.107369E+09 0.00 0.40
February 6128560.21 0.177008E+09 0.00 647258.40 19151024.16 0.00 47934724.36 0.00 0.40
March 3988059.57 0.233790E+09 0.00 844981.35 28759751.79 0.00 84968880.29 0.00 0.43
April 745758.86 0.313173E+09 0.00 225041.08 45887571.61 0.00 12086292.40 0.00 0.40
May 0.00 0.561587E+09 0.00 0.00 75486473.61 0.00 0.00 0.00 0.40
June 0.00 0.721187E+09 0.00 0.00 0.107924E+09 0.00 0.00 0.00 0.40
July 0.00 0.741156E+09 0.00 0.00 0.122840E+09 0.00 0.00 0.00 0.36
August 0.00 0.801116E+09 0.00 0.00 0.115984E+09 0.00 0.00 0.00 0.40
September 0.00 0.675069E+09 0.00 0.00 0.117696E+09 0.00 0.00 0.00 0.38
October 0.00 0.564084E+09 0.00 0.00 80266976.28 0.00 0.00 0.00 0.37
November 926595.28 0.400646E+09 0.00 222617.24 53452535.16 0.00 13376848.71 0.00 0.38
December 6520400.41 0.170205E+09 0.00 984039.83 31094793.42 0.00 95113019.61 0.00 0.39
                   
Annual Sum or Average 25811862.13 0.550739E+10 0.00 4049809.96 0.814657E+09 0.00 0.360849E+09 0.00 0.39
Minimum of Months 0.00 0.148367E+09 0.00 0.00 16113069.50 0.00 0.00 0.00 0.36
Maximum of Months 7502487.80 0.801116E+09 0.00 1125872.06 0.122840E+09 0.00 0.107369E+09 0.00 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2406552.74 14966142.85 0.00 86022.52 3293203.97 0.00 8896287.07 0.00 0.26
February 2256912.62 17792368.37 0.00 46958.17 3887762.66 0.00 3406950.39 0.00 0.27
March 1598921.76 21815037.61 0.00 63092.19 6036639.30 0.00 6240455.99 0.00 0.27
April 254425.41 28022598.22 0.00 16610.57 9660156.86 0.00 938660.34 0.00 0.25
May 0.00 48403437.30 0.00 0.00 17321783.95 0.00 0.00 0.00 0.25
June 0.00 61847619.24 0.00 0.00 24992597.80 0.00 0.00 0.00 0.26
July 0.00 63653342.40 0.00 0.00 28052990.87 0.00 0.00 0.00 0.24
August 0.00 69624455.50 0.00 0.00 26755723.62 0.00 0.00 0.00 0.26
September 0.00 61201253.35 0.00 0.00 25206598.32 0.00 0.00 0.00 0.25
October 0.00 51246809.38 0.00 0.00 18450944.83 0.00 0.00 0.00 0.24
November 484660.25 40410089.08 0.00 13259.99 11073108.79 0.00 710149.12 0.00 0.25
December 2036192.83 17493354.83 0.00 75007.34 6024813.34 0.00 7921421.37 0.00 0.26
                   
Annual Sum or Average 9037665.62 0.496477E+09 0.00 300950.78 0.180756E+09 0.00 28113924.27 0.00 0.25
Minimum of Months 0.00 14966142.85 0.00 0.00 3293203.97 0.00 0.00 0.00 0.24
Maximum of Months 2406552.74 69624455.50 0.00 86022.52 28052990.87 0.00 8896287.07 0.00 0.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4256441.37 30808480.74 0.00 171821.20 5703252.37 0.00 17775197.86 0.00 0.24
February 3812857.14 39093095.35 0.00 96019.02 6596458.80 0.00 7646417.72 0.00 0.25
March 2453598.68 51813168.75 0.00 146412.56 9667953.50 0.00 15100147.60 0.00 0.27
April 274030.62 71723204.88 0.00 45488.59 15819794.71 0.00 2678415.51 0.00 0.28
May 0.00 0.133308E+09 0.00 0.00 27781978.34 0.00 0.00 0.00 0.28
June 0.00 0.173559E+09 0.00 0.00 39797591.68 0.00 0.00 0.00 0.29
July 0.00 0.177245E+09 0.00 0.00 45811457.15 0.00 0.00 0.00 0.27
August 0.00 0.185931E+09 0.00 0.00 44625274.19 0.00 0.00 0.00 0.29
September 0.00 0.154093E+09 0.00 0.00 43517291.25 0.00 0.00 0.00 0.27
October 0.00 0.121668E+09 0.00 0.00 31609979.44 0.00 0.00 0.00 0.25
November 809498.04 87531587.18 0.00 31315.07 19167963.79 0.00 1696098.13 0.00 0.24
December 3290906.48 36064363.11 0.00 157421.99 10805268.58 0.00 16736459.17 0.00 0.24
                   
Annual Sum or Average 14897332.33 0.126284E+10 0.00 648478.43 0.300904E+09 0.00 61632735.99 0.00 0.26
Minimum of Months 0.00 30808480.74 0.00 0.00 5703252.37 0.00 0.00 0.00 0.24
Maximum of Months 4256441.37 0.185931E+09 0.00 171821.20 45811457.15 0.00 17775197.86 0.00 0.29



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4227085.35 43202047.56 0.00 258980.25 6637027.14 0.00 26259931.00 0.00 0.27
February 4208827.12 54392927.68 0.00 143206.70 7564071.60 0.00 11116502.31 0.00 0.28
March 2192136.39 71552835.72 0.00 211762.64 11521862.41 0.00 21992055.02 0.00 0.31
April 301254.23 97804097.93 0.00 63034.65 18371975.95 0.00 3591437.52 0.00 0.31
May 0.00 0.182283E+09 0.00 0.00 31526689.75 0.00 0.00 0.00 0.32
June 0.00 0.233999E+09 0.00 0.00 46251561.68 0.00 0.00 0.00 0.32
July 0.00 0.239564E+09 0.00 0.00 52577567.83 0.00 0.00 0.00 0.29
August 0.00 0.251806E+09 0.00 0.00 50188885.86 0.00 0.00 0.00 0.31
September 0.00 0.208331E+09 0.00 0.00 50266327.48 0.00 0.00 0.00 0.29
October 0.00 0.168154E+09 0.00 0.00 35020856.84 0.00 0.00 0.00 0.28
November 722341.27 0.120156E+09 0.00 51399.48 22304998.24 0.00 2977542.89 0.00 0.27
December 3772029.69 50562157.69 0.00 233849.26 12642205.26 0.00 23801572.91 0.00 0.27
                   
Annual Sum or Average 15423674.05 0.172181E+10 0.00 962232.98 0.344874E+09 0.00 89739041.64 0.00 0.29
Minimum of Months 0.00 43202047.56 0.00 0.00 6637027.14 0.00 0.00 0.00 0.27
Maximum of Months 4227085.35 0.251806E+09 0.00 258980.25 52577567.83 0.00 26259931.00 0.00 0.32



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 14018734.99 48705613.95 0.00 120825.01 11867686.28 249638.70 18517585.10 0.00 0.35
February 9247471.91 62140945.60 0.00 125247.70 13889134.44 1296328.13 7242101.86 0.00 0.40
March 8131829.94 92732669.99 0.00 190653.62 20610263.26 335746.90 19633383.03 0.00 0.46
April 936344.57 0.151596E+09 0.00 66450.11 31892123.27 0.00 4375573.94 0.00 0.53
May 0.00 0.287647E+09 0.00 0.00 54397502.54 0.00 0.00 0.00 0.57
June 0.00 0.401264E+09 0.00 0.00 69802063.32 0.00 0.00 0.00 0.61
July 0.00 0.434368E+09 0.00 0.00 76999176.01 0.00 0.00 0.00 0.57
August 0.00 0.424002E+09 0.00 0.00 79183688.88 0.00 0.00 0.00 0.58
September 0.00 0.356634E+09 0.00 0.00 78946339.73 0.00 0.00 0.00 0.55
October 0.00 0.258335E+09 0.00 0.00 60718804.81 0.00 0.00 0.00 0.49
November 2521300.14 0.153099E+09 0.00 33885.09 37621421.91 36208.37 1437836.67 0.00 0.40
December 13877411.90 56889892.62 1295.27 63054.39 22222060.78 883039.49 12355451.17 85.63 0.34
                   
Annual Sum or Average 48733093.46 0.272742E+10 1295.27 600115.91 0.558150E+09 2800961.59 63561931.77 85.63 0.49
Minimum of Months 0.00 48705613.95 0.00 0.00 11867686.28 0.00 0.00 0.00 0.34
Maximum of Months 14018734.99 0.434368E+09 1295.27 190653.62 79183688.88 1296328.13 19633383.03 85.63 0.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 36209423.60 0.643261E+09 0.00 4050776.71 66997527.40 0.00 0.383766E+09 0.00 0.32
February 30410593.09 0.783298E+09 0.00 2349587.13 79364976.21 0.00 0.167429E+09 0.00 0.34
March 19807967.79 0.105572E+10 0.00 3161761.95 0.120922E+09 0.00 0.306776E+09 0.00 0.37
April 3240618.94 0.147297E+10 0.00 998878.76 0.191143E+09 0.00 51829981.07 0.00 0.37
May 0.00 0.280339E+10 0.00 0.00 0.310129E+09 0.00 0.00 0.00 0.39
June 0.00 0.373272E+10 0.00 0.00 0.431787E+09 0.00 0.00 0.00 0.40
July 0.00 0.390853E+10 0.00 0.00 0.489873E+09 0.00 0.00 0.00 0.37
August 0.00 0.409006E+10 0.00 0.00 0.467389E+09 0.00 0.00 0.00 0.40
September 0.00 0.343184E+10 0.00 0.00 0.465309E+09 0.00 0.00 0.00 0.37
October 0.00 0.272481E+10 0.00 0.00 0.332152E+09 0.00 0.00 0.00 0.35
November 5060840.65 0.184938E+10 0.00 798411.50 0.221352E+09 0.00 44211024.89 0.00 0.34
December 31950419.74 0.753109E+09 0.00 3656303.84 0.129987E+09 0.00 0.348853E+09 0.00 0.33
                   
Annual Sum or Average 0.126680E+09 0.272491E+11 0.00 15015719.89 0.330641E+10 0.00 0.130287E+10 0.00 0.36
Minimum of Months 0.00 0.643261E+09 0.00 0.00 66997527.40 0.00 0.00 0.00 0.32
Maximum of Months 36209423.60 0.409006E+10 0.00 4050776.71 0.489873E+09 0.00 0.383766E+09 0.00 0.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 21279176.87 0.344509E+09 0.00 2363035.11 41153281.57 0.00 0.232334E+09 0.00 0.37
February 16179701.75 0.415998E+09 0.00 1354364.57 48665390.73 0.00 0.103940E+09 0.00 0.38
March 11318221.96 0.549477E+09 0.00 1828564.66 74051866.65 0.00 0.187284E+09 0.00 0.41
April 1948742.39 0.745916E+09 0.00 506788.76 0.117086E+09 0.00 28105559.50 0.00 0.39
May 0.00 0.135598E+10 0.00 0.00 0.191873E+09 0.00 0.00 0.00 0.39
June 0.00 0.175133E+10 0.00 0.00 0.270111E+09 0.00 0.00 0.00 0.40
July 0.00 0.181492E+10 0.00 0.00 0.306127E+09 0.00 0.00 0.00 0.36
August 0.00 0.193407E+10 0.00 0.00 0.290836E+09 0.00 0.00 0.00 0.40
September 0.00 0.163085E+10 0.00 0.00 0.292023E+09 0.00 0.00 0.00 0.37
October 0.00 0.133848E+10 0.00 0.00 0.204997E+09 0.00 0.00 0.00 0.36
November 2847437.76 0.945445E+09 0.00 462374.42 0.136155E+09 0.00 27526863.57 0.00 0.36
December 18247795.32 0.399320E+09 0.00 2094260.97 79082362.90 0.00 0.209165E+09 0.00 0.37
                   
Annual Sum or Average 71821076.05 0.132263E+11 0.00 8609388.49 0.205216E+10 0.00 0.788354E+09 0.00 0.38
Minimum of Months 0.00 0.344509E+09 0.00 0.00 41153281.57 0.00 0.00 0.00 0.36
Maximum of Months 21279176.87 0.193407E+10 0.00 2363035.11 0.306127E+09 0.00 0.232334E+09 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 29612874.43 25526734.35 235.67 4499.15 28057633.25 138633.47 3879038.05 31.79 0.79
February 14413156.62 34081178.72 0.00 3484.57 27212409.45 2123972.35 968171.80 0.00 0.80
March 22145899.31 47073421.17 715.41 5357.81 33923953.49 143117.13 1866874.47 12.67 0.82
April 1761765.16 64475942.84 0.00 3709.18 51922374.14 4142.84 1744026.06 0.00 0.80
May 0.00 0.130932E+09 0.00 0.00 76787946.34 0.00 0.00 0.00 0.82
June 0.00 0.175292E+09 0.00 0.00 0.106262E+09 0.00 0.00 0.00 0.86
July 0.00 0.193803E+09 0.00 0.00 0.116973E+09 0.00 0.00 0.00 0.83
August 0.00 0.191812E+09 0.00 0.00 0.123496E+09 0.00 0.00 0.00 0.87
September 0.00 0.159845E+09 0.00 0.00 0.120580E+09 0.00 0.00 0.00 0.84
October 0.00 0.115000E+09 0.00 0.00 0.106490E+09 0.00 0.00 0.00 0.80
November 3811421.30 88760342.74 0.00 1662.67 61498360.25 31052.27 261020.95 0.00 0.76
December 24682819.18 31465294.44 7364.04 4930.38 39555264.87 172514.59 4497225.22 22.30 0.79
                   
Annual Sum or Average 96427936.01 0.125807E+10 8315.12 23643.74 0.892758E+09 2613432.66 13216356.54 66.76 0.81
Minimum of Months 0.00 25526734.35 0.00 0.00 27212409.45 0.00 0.00 0.00 0.76
Maximum of Months 29612874.43 0.193803E+09 7364.04 5357.81 0.123496E+09 2123972.35 4497225.22 31.79 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 X-RAY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 65597326.11 0.129316E+10 0.00 9496831.61 25033695.60 0.00 0.666660E+09 0.00 1.15
February 30874099.46 0.154175E+10 0.00 5614783.21 27083166.15 0.00 0.380082E+09 0.00 1.18
March 18495562.93 0.206810E+10 0.00 6615763.80 33914906.84 0.00 0.496577E+09 0.00 1.24
April 361947.71 0.282300E+10 0.00 1431681.24 37275193.92 0.00 49495761.06 0.00 1.20
May 0.00 0.496975E+10 0.00 0.00 52600752.29 0.00 0.00 0.00 1.34
June 0.00 0.662428E+10 0.00 0.00 60878620.20 0.00 0.00 0.00 1.45
July 0.00 0.681103E+10 0.00 0.00 50949311.85 0.00 0.00 0.00 1.34
August 0.00 0.724555E+10 0.00 0.00 59924742.75 0.00 0.00 0.00 1.45
September 0.00 0.627274E+10 0.00 0.00 52253028.57 0.00 0.00 0.00 1.37
October 0.00 0.494662E+10 0.00 0.00 50474488.71 0.00 0.00 0.00 1.26
November 0.00 0.357844E+10 0.00 1309627.43 51421092.79 0.00 63685620.89 0.00 1.19
December 52602331.70 0.156385E+10 0.00 6898635.03 26113528.46 0.00 0.524369E+09 0.00 1.15
                   
Annual Sum or Average 0.167931E+09 0.497383E+11 0.00 31367322.31 0.527923E+09 0.00 0.218087E+10 0.00 1.28
Minimum of Months 0.00 0.129316E+10 0.00 0.00 25033695.60 0.00 0.00 0.00 1.15
Maximum of Months 65597326.11 0.724555E+10 0.00 9496831.61 60878620.20 0.00 0.666660E+09 0.00 1.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2195080.28 17650880.81 0.00 113241.68 9108911.87 0.00 11499184.61 0.00 0.49
February 1928787.53 22109053.07 0.00 56015.96 9931465.72 0.00 4389885.43 0.00 0.50
March 1241854.32 29653798.80 0.00 93860.75 15187591.10 0.00 9390186.00 0.00 0.54
April 227043.99 42065608.78 0.00 21190.66 21056301.58 0.00 919474.42 0.00 0.52
May 0.00 75903417.65 0.00 0.00 33590907.49 0.00 0.00 0.00 0.53
June 0.00 99788929.45 0.00 0.00 42020285.32 0.00 0.00 0.00 0.54
July 0.00 0.104506E+09 0.00 0.00 45681318.18 0.00 0.00 0.00 0.51
August 0.00 0.109986E+09 0.00 0.00 45307754.10 0.00 0.00 0.00 0.54
September 0.00 91952104.80 0.00 0.00 42420502.09 0.00 0.00 0.00 0.51
October 0.00 71086054.87 0.00 0.00 36960230.06 0.00 0.00 0.00 0.49
November 505846.34 51656012.47 0.00 18988.28 24341742.67 0.00 989886.06 0.00 0.49
December 1574964.62 20595774.32 0.00 99885.77 15197286.96 0.00 10645332.01 0.00 0.49
                   
Annual Sum or Average 7673577.07 0.736953E+09 0.00 403183.10 0.340804E+09 0.00 37833948.53 0.00 0.51
Minimum of Months 0.00 17650880.81 0.00 0.00 9108911.87 0.00 0.00 0.00 0.49
Maximum of Months 2195080.28 0.109986E+09 0.00 113241.68 45681318.18 0.00 11499184.61 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 17673466.86 0.113752E+09 0.00 464736.54 46630569.04 0.00 45818691.89 0.00 0.30
February 13420597.29 0.145386E+09 0.00 253105.83 50719461.27 829441.93 15880990.65 0.00 0.32
March 11522425.89 0.207582E+09 0.00 414307.79 75988784.06 0.00 36085115.67 0.00 0.36
April 1215417.65 0.308494E+09 0.00 134072.38 0.101930E+09 0.00 5777803.92 0.00 0.38
May 0.00 0.582675E+09 0.00 0.00 0.159569E+09 0.00 0.00 0.00 0.41
June 0.00 0.786355E+09 0.00 0.00 0.193861E+09 0.00 0.00 0.00 0.42
July 0.00 0.845952E+09 0.00 0.00 0.209761E+09 0.00 0.00 0.00 0.41
August 0.00 0.863231E+09 0.00 0.00 0.208348E+09 0.00 0.00 0.00 0.42
September 0.00 0.717865E+09 0.00 0.00 0.201536E+09 0.00 0.00 0.00 0.40
October 0.00 0.541686E+09 0.00 0.00 0.174791E+09 0.00 0.00 0.00 0.37
November 3909071.14 0.365205E+09 0.00 78718.98 0.122081E+09 0.00 3137864.85 0.00 0.35
December 13910945.77 0.140360E+09 0.00 424204.00 77033008.53 0.00 43082221.13 0.00 0.31
                   
Annual Sum or Average 61651924.60 0.561854E+10 0.00 1769145.52 0.162225E+10 829441.93 0.149783E+09 0.00 0.37
Minimum of Months 0.00 0.113752E+09 0.00 0.00 46630569.04 0.00 0.00 0.00 0.30
Maximum of Months 17673466.86 0.863231E+09 0.00 464736.54 0.209761E+09 829441.93 45818691.89 0.00 0.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 HUMID

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4439444.53 49038105.61 0.00 314960.48 20061042.28 0.00 31759682.75 0.00 0.49
February 4087704.76 61365066.71 0.00 161707.19 21962450.97 0.00 12129723.97 0.00 0.50
March 2342890.61 82248948.38 0.00 258882.82 34194607.38 0.00 25747493.47 0.00 0.55
April 509226.10 0.116368E+09 0.00 58596.45 46661845.46 0.00 2569436.92 0.00 0.53
May 0.00 0.209257E+09 0.00 0.00 75040176.70 0.00 0.00 0.00 0.53
June 0.00 0.277457E+09 0.00 0.00 91375570.58 0.00 0.00 0.00 0.55
July 0.00 0.289696E+09 0.00 0.00 0.100062E+09 0.00 0.00 0.00 0.51
August 0.00 0.305169E+09 0.00 0.00 99505551.77 0.00 0.00 0.00 0.55
September 0.00 0.254090E+09 0.00 0.00 95084183.83 0.00 0.00 0.00 0.52
October 0.00 0.198972E+09 0.00 0.00 81925737.60 0.00 0.00 0.00 0.50
November 934214.56 0.143281E+09 0.00 53098.69 54525882.41 0.00 2992490.41 0.00 0.50
December 3253795.81 57505723.06 0.00 275627.03 33845455.56 0.00 29117882.92 0.00 0.49
                   
Annual Sum or Average 15567276.37 0.204445E+10 0.00 1122872.65 0.754244E+09 0.00 0.104317E+09 0.00 0.52
Minimum of Months 0.00 49038105.61 0.00 0.00 20061042.28 0.00 0.00 0.00 0.49
Maximum of Months 4439444.53 0.305169E+09 0.00 314960.48 0.100062E+09 0.00 31759682.75 0.00 0.55



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 JANITOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6624496.72 13536046.58 74868.13 20853.38 16697952.65 3627218.59 1692022.06 1147.18 0.32
February 3261180.40 21137376.29 17457.54 10746.31 15559720.47 2736940.26 189237.52 801.50 0.36
March 4390040.45 32524584.53 3608.73 24782.13 22221400.73 3446048.80 997654.92 170.59 0.39
April 669433.95 55191694.35 0.00 13441.58 27778598.93 14405.93 450377.18 0.00 0.44
May 0.00 0.117779E+09 0.00 0.00 39740874.30 0.00 0.00 0.00 0.50
June 0.00 0.167214E+09 0.00 0.00 45661320.96 0.00 0.00 0.00 0.54
July 0.00 0.190621E+09 0.00 0.00 44963057.77 0.00 0.00 0.00 0.53
August 0.00 0.177982E+09 0.00 0.00 51957714.67 0.00 0.00 0.00 0.53
September 0.00 0.147539E+09 0.00 0.00 48076571.32 0.00 0.00 0.00 0.49
October 0.00 95535050.27 0.00 0.00 48101071.49 0.00 0.00 0.00 0.43
November 532214.84 60761580.18 18848.32 7273.38 35205487.77 899334.30 163115.91 249.36 0.39
December 5180731.77 20005030.12 70974.36 16295.70 23522316.33 3404867.04 1584538.73 2133.39 0.34
                   
Annual Sum or Average 20658098.13 0.109983E+10 185757.08 93392.48 0.419486E+09 14128814.93 5076946.32 4502.02 0.44
Minimum of Months 0.00 13536046.58 0.00 0.00 15559720.47 0.00 0.00 0.00 0.32
Maximum of Months 6624496.72 0.190621E+09 74868.13 24782.13 51957714.67 3627218.59 1692022.06 2133.39 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 LOCKER

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 5148686.98 88824216.79 0.00 533305.05 24428225.50 0.00 52191175.58 0.00 0.71
February 5164787.45 0.110812E+09 0.00 281463.30 26444046.11 22656.16 20062453.93 0.00 0.74
March 2835890.17 0.150732E+09 0.00 430217.48 40727425.14 0.00 41973964.63 0.00 0.81
April 515552.04 0.208969E+09 0.00 106497.80 55854042.29 0.00 4750855.43 0.00 0.78
May 0.00 0.383600E+09 0.00 0.00 87433402.28 0.00 0.00 0.00 0.80
June 0.00 0.506812E+09 0.00 0.00 0.106069E+09 0.00 0.00 0.00 0.82
July 0.00 0.529938E+09 0.00 0.00 0.113454E+09 0.00 0.00 0.00 0.76
August 0.00 0.554885E+09 0.00 0.00 0.114998E+09 0.00 0.00 0.00 0.82
September 0.00 0.459807E+09 0.00 0.00 0.113472E+09 0.00 0.00 0.00 0.77
October 0.00 0.366710E+09 0.00 0.00 95595101.55 0.00 0.00 0.00 0.74
November 888442.11 0.258539E+09 0.00 95535.18 65503910.05 0.00 5522978.15 0.00 0.73
December 4046993.78 0.104052E+09 0.00 452720.26 42022564.41 0.00 47187906.46 0.00 0.72
                   
Annual Sum or Average 18600352.53 0.372368E+10 0.00 1899739.07 0.886001E+09 22656.16 0.171689E+09 0.00 0.77
Minimum of Months 0.00 88824216.79 0.00 0.00 24428225.50 0.00 0.00 0.00 0.71
Maximum of Months 5164787.45 0.554885E+09 0.00 533305.05 0.114998E+09 22656.16 52191175.58 0.00 0.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 29624262.29 0.561849E+09 0.00 3145588.53 0.138481E+09 0.00 0.302916E+09 0.00 0.68
February 30247382.38 0.701014E+09 0.00 1691945.42 0.150593E+09 189578.78 0.114783E+09 0.00 0.71
March 16103043.52 0.975190E+09 0.00 2521194.56 0.218462E+09 0.00 0.238287E+09 0.00 0.78
April 2509478.77 0.139471E+10 0.00 655136.28 0.267105E+09 0.00 29455481.67 0.00 0.77
May 0.00 0.259606E+10 0.00 0.00 0.406284E+09 0.00 0.00 0.00 0.81
June 0.00 0.349136E+10 0.00 0.00 0.459304E+09 0.00 0.00 0.00 0.84
July 0.00 0.369549E+10 0.00 0.00 0.473205E+09 0.00 0.00 0.00 0.78
August 0.00 0.377841E+10 0.00 0.00 0.528435E+09 0.00 0.00 0.00 0.83
September 0.00 0.319010E+10 0.00 0.00 0.486484E+09 0.00 0.00 0.00 0.78
October 0.00 0.247140E+10 0.00 0.00 0.467238E+09 0.00 0.00 0.00 0.74
November 5099744.96 0.167432E+10 0.00 573730.92 0.356588E+09 0.00 32009160.46 0.00 0.72
December 23427626.20 0.662075E+09 0.00 2657341.35 0.239109E+09 0.00 0.271807E+09 0.00 0.68
                   
Annual Sum or Average 0.107012E+09 0.251920E+11 0.00 11244937.08 0.419129E+10 189578.78 0.989258E+09 0.00 0.76
Minimum of Months 0.00 0.561849E+09 0.00 0.00 0.138481E+09 0.00 0.00 0.00 0.68
Maximum of Months 30247382.38 0.377841E+10 0.00 3145588.53 0.528435E+09 189578.78 0.302916E+09 0.00 0.84



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 89262656.88 94559317.16 712709.33 19009.86 0.146376E+09 1605766.62 16828298.23 8414.97 0.89
February 42214787.29 0.128164E+09 566576.80 14281.98 0.143119E+09 8852817.27 5079326.51 8331.84 0.92
March 63810196.81 0.173771E+09 737077.55 31668.24 0.211908E+09 2192552.49 12735954.55 9370.15 0.97
April 5448127.23 0.240184E+09 1129333.98 18963.09 0.294271E+09 60322.26 3601367.05 12004.78 0.98
May 0.00 0.468186E+09 1481852.20 0.00 0.439297E+09 0.00 0.00 6452.18 0.98
June 0.00 0.631138E+09 1312001.15 0.00 0.533865E+09 0.00 0.00 5524.92 0.99
July 0.00 0.661652E+09 1646377.34 0.00 0.585805E+09 0.00 0.00 9822.19 0.96
August 0.00 0.664758E+09 1544314.91 0.00 0.618765E+09 0.00 0.00 11609.94 1.00
September 0.00 0.565340E+09 1829397.61 0.00 0.583583E+09 0.00 0.00 10352.09 0.98
October 0.00 0.418513E+09 1816817.25 0.00 0.534986E+09 0.00 0.00 14068.61 0.96
November 12159553.17 0.309548E+09 1050998.46 6791.10 0.346265E+09 582278.27 1343068.32 11359.96 0.92
December 72900760.23 0.114664E+09 705707.25 13431.55 0.221893E+09 2789919.48 16182573.23 12811.46 0.91
                   
Annual Sum or Average 0.285796E+09 0.447048E+10 14533163.82 104145.81 0.466013E+10 16083656.39 55770587.88 120123.08 0.95
Minimum of Months 0.00 94559317.16 566576.80 0.00 0.143119E+09 0.00 0.00 5524.92 0.89
Maximum of Months 89262656.88 0.664758E+09 1829397.61 31668.24 0.618765E+09 8852817.27 16828298.23 14068.61 1.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 23381417.44 0.509470E+09 0.00 2633594.68 77895185.81 0.00 0.249801E+09 0.00 1.21
February 18483287.94 0.625358E+09 0.00 1591952.24 77261638.05 197904.72 0.104687E+09 0.00 1.29
March 8348339.26 0.890541E+09 0.00 2219085.14 0.118198E+09 0.00 0.214925E+09 0.00 1.43
April 1635836.01 0.130633E+10 0.00 574655.12 0.143334E+09 0.00 26048383.97 0.00 1.46
May 0.00 0.236492E+10 0.00 0.00 0.212204E+09 0.00 0.00 0.00 1.51
June 0.00 0.316865E+10 0.00 0.00 0.236598E+09 0.00 0.00 0.00 1.57
July 0.00 0.341135E+10 0.00 0.00 0.235591E+09 0.00 0.00 0.00 1.49
August 0.00 0.344540E+10 0.00 0.00 0.260554E+09 0.00 0.00 0.00 1.55
September 0.00 0.297199E+10 0.00 0.00 0.237105E+09 0.00 0.00 0.00 1.47
October 0.00 0.229845E+10 0.00 0.00 0.252844E+09 0.00 0.00 0.00 1.39
November 3271441.48 0.150141E+10 0.00 573785.00 0.187009E+09 0.00 28829100.48 0.00 1.31
December 17940816.75 0.636647E+09 0.00 2011875.61 0.122271E+09 0.00 0.207351E+09 0.00 1.19
                   
Annual Sum or Average 73061138.89 0.231305E+11 0.00 9604947.78 0.216086E+10 197904.72 0.831642E+09 0.00 1.41
Minimum of Months 0.00 0.509470E+09 0.00 0.00 77261638.05 0.00 0.00 0.00 1.19
Maximum of Months 23381417.44 0.344540E+10 0.00 2633594.68 0.260554E+09 197904.72 0.249801E+09 0.00 1.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 16667357.45 0.113216E+09 0.00 529998.03 48264890.87 0.00 53028184.17 0.00 0.38
February 13429739.72 0.142985E+09 0.00 291268.21 53088635.27 312499.28 19139655.93 0.00 0.41
March 9988959.18 0.201039E+09 0.00 481711.61 81997784.72 0.00 45413625.35 0.00 0.46
April 1260792.02 0.296822E+09 0.00 134568.50 0.110350E+09 0.00 5997949.22 0.00 0.47
May 0.00 0.553849E+09 0.00 0.00 0.171525E+09 0.00 0.00 0.00 0.49
June 0.00 0.747820E+09 0.00 0.00 0.208348E+09 0.00 0.00 0.00 0.51
July 0.00 0.793954E+09 0.00 0.00 0.227405E+09 0.00 0.00 0.00 0.48
August 0.00 0.813726E+09 0.00 0.00 0.224800E+09 0.00 0.00 0.00 0.50
September 0.00 0.677640E+09 0.00 0.00 0.217948E+09 0.00 0.00 0.00 0.48
October 0.00 0.512397E+09 0.00 0.00 0.191884E+09 0.00 0.00 0.00 0.45
November 3403917.68 0.347188E+09 0.00 91126.66 0.130212E+09 0.00 4163577.80 0.00 0.42
December 12937902.67 0.134498E+09 0.00 456864.24 81138282.86 0.00 47290394.59 0.00 0.38
                   
Annual Sum or Average 57688668.72 0.533513E+10 0.00 1985537.24 0.174696E+10 312499.28 0.175033E+09 0.00 0.45
Minimum of Months 0.00 0.113216E+09 0.00 0.00 48264890.87 0.00 0.00 0.00 0.38
Maximum of Months 16667357.45 0.813726E+09 0.00 529998.03 0.227405E+09 312499.28 53028184.17 0.00 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 OFFICE

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.137888E+09 0.122619E+10 0.00 5523280.47 0.392393E+09 0.00 0.531567E+09 0.00 0.37
February 0.117283E+09 0.156442E+10 0.00 3058798.34 0.421950E+09 2989169.82 0.189928E+09 0.00 0.40
March 84814554.84 0.217372E+10 0.00 4736116.82 0.647390E+09 0.00 0.423081E+09 0.00 0.44
April 9874114.32 0.316407E+10 0.00 1416490.30 0.868417E+09 0.00 61691231.82 0.00 0.46
May 0.00 0.597918E+10 0.00 0.00 0.136607E+10 0.00 0.00 0.00 0.49
June 0.00 0.817892E+10 0.00 0.00 0.155655E+10 0.00 0.00 0.00 0.51
July 0.00 0.884503E+10 0.00 0.00 0.154633E+10 0.00 0.00 0.00 0.49
August 0.00 0.878525E+10 0.00 0.00 0.174266E+10 0.00 0.00 0.00 0.50
September 0.00 0.724218E+10 0.00 0.00 0.174903E+10 0.00 0.00 0.00 0.47
October 0.00 0.549442E+10 0.00 0.00 0.151804E+10 0.00 0.00 0.00 0.44
November 27037870.31 0.375881E+10 0.00 990776.55 0.104376E+10 0.00 45823702.37 0.00 0.42
December 0.108829E+09 0.147452E+10 0.00 4834775.28 0.669962E+09 212933.03 0.487632E+09 0.00 0.38
                   
Annual Sum or Average 0.485727E+09 0.578867E+11 0.00 20560237.76 0.135225E+11 3202102.85 0.173972E+10 0.00 0.45
Minimum of Months 0.00 0.122619E+10 0.00 0.00 0.392393E+09 0.00 0.00 0.00 0.37
Maximum of Months 0.137888E+09 0.884503E+10 0.00 5523280.47 0.174903E+10 2989169.82 0.531567E+09 0.00 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 40227628.52 0.303044E+09 0.00 1508955.31 0.118975E+09 0.00 0.145746E+09 0.00 0.36
February 34500694.15 0.379768E+09 0.00 803505.57 0.131013E+09 101304.90 51571069.71 0.00 0.39
March 23567438.00 0.526334E+09 0.00 1290972.68 0.200124E+09 0.00 0.117010E+09 0.00 0.42
April 3147173.99 0.762031E+09 0.00 352537.67 0.270890E+09 0.00 15245139.76 0.00 0.43
May 0.00 0.140741E+10 0.00 0.00 0.423708E+09 0.00 0.00 0.00 0.45
June 0.00 0.187453E+10 0.00 0.00 0.521976E+09 0.00 0.00 0.00 0.46
July 0.00 0.199630E+10 0.00 0.00 0.568410E+09 0.00 0.00 0.00 0.44
August 0.00 0.206064E+10 0.00 0.00 0.561738E+09 0.00 0.00 0.00 0.46
September 0.00 0.172162E+10 0.00 0.00 0.540461E+09 0.00 0.00 0.00 0.43
October 0.00 0.132039E+10 0.00 0.00 0.471629E+09 0.00 0.00 0.00 0.41
November 7875836.55 0.917129E+09 0.00 251715.16 0.322502E+09 0.00 11667283.20 0.00 0.39
December 31288682.83 0.363549E+09 0.00 1320502.01 0.200594E+09 0.00 0.134178E+09 0.00 0.37
                   
Annual Sum or Average 0.140607E+09 0.136328E+11 0.00 5528188.40 0.433202E+10 101304.90 0.475417E+09 0.00 0.42
Minimum of Months 0.00 0.303044E+09 0.00 0.00 0.118975E+09 0.00 0.00 0.00 0.36
Maximum of Months 40227628.52 0.206064E+10 0.00 1508955.31 0.568410E+09 101304.90 0.145746E+09 0.00 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 26705663.86 18271595.96 143349.97 5787.19 52020792.80 1756303.87 2929136.97 2187.33 0.92
February 12494635.68 24602123.64 163833.41 4264.48 54472441.89 3413743.12 457180.41 2462.75 0.95
March 19683693.06 38256016.01 200055.57 8079.07 74177079.01 1515008.94 1753141.49 1902.38 1.00
April 2079939.57 60715315.55 252505.92 3956.02 95145334.95 11100.33 565853.17 1963.44 1.01
May 0.00 0.124647E+09 224026.61 0.00 0.140074E+09 0.00 0.00 712.31 1.01
June 0.00 0.171110E+09 195921.70 0.00 0.168652E+09 0.00 0.00 383.52 1.03
July 0.00 0.179738E+09 195332.44 0.00 0.184156E+09 0.00 0.00 431.40 0.99
August 0.00 0.181156E+09 235687.69 0.00 0.193181E+09 0.00 0.00 649.61 1.03
September 0.00 0.150580E+09 256305.22 0.00 0.184587E+09 0.00 0.00 567.75 1.01
October 0.00 0.106566E+09 395078.00 0.00 0.171496E+09 0.00 0.00 1381.88 1.00
November 3356192.97 77756893.00 308153.08 1765.25 0.113398E+09 528372.37 221103.74 2257.13 0.96
December 21543736.38 25479567.94 210122.95 3674.89 72615825.81 2638129.14 2597514.00 3417.48 0.94
                   
Annual Sum or Average 85863861.53 0.115888E+10 2780372.56 27526.91 0.150398E+10 9862657.76 8523929.78 18316.98 0.99
Minimum of Months 0.00 18271595.96 143349.97 0.00 52020792.80 0.00 0.00 383.52 0.92
Maximum of Months 26705663.86 0.181156E+09 395078.00 8079.07 0.193181E+09 3413743.12 2929136.97 3417.48 1.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.238305E+09 0.102967E+10 1882396.73 4638939.62 0.688051E+09 1746706.88 0.516803E+09 21533.18 0.94
February 0.152663E+09 0.121986E+10 1603649.71 2396378.64 0.745049E+09 32776082.70 0.180413E+09 14991.19 0.97
March 0.195458E+09 0.159232E+10 1306173.69 3339183.10 0.113684E+10 1914499.84 0.332346E+09 13974.87 1.01
April 19017734.45 0.219221E+10 3408856.35 813414.80 0.157657E+10 142928.18 41736908.28 26116.71 1.00
May 0.00 0.386502E+10 2481866.06 0.00 0.250451E+10 0.00 0.00 15298.13 1.00
June 0.00 0.508966E+10 2392370.07 0.00 0.312120E+10 0.00 0.00 13475.68 1.02
July 0.00 0.552428E+10 3825276.20 0.00 0.333907E+10 0.00 0.00 17784.45 0.99
August 0.00 0.582742E+10 2841234.98 0.00 0.339591E+10 0.00 0.00 12965.75 1.04
September 0.00 0.521288E+10 3601873.07 0.00 0.312810E+10 0.00 0.00 13973.48 1.04
October 0.00 0.426232E+10 2826385.13 0.00 0.267075E+10 0.00 0.00 17785.72 1.02
November 53564720.07 0.298276E+10 2132857.30 781958.11 0.181601E+10 304371.95 36845022.58 13214.00 0.99
December 0.203801E+09 0.121969E+10 2392482.64 3890805.22 0.115361E+10 2350254.56 0.436568E+09 40620.87 0.95
                   
Annual Sum or Average 0.862809E+09 0.400181E+11 30695421.92 15860679.49 0.252757E+11 39234844.10 0.154471E+10 221734.03 1.00
Minimum of Months 0.00 0.102967E+10 1306173.69 0.00 0.688051E+09 0.00 0.00 12965.75 0.94
Maximum of Months 0.238305E+09 0.582742E+10 3825276.20 4638939.62 0.339591E+10 32776082.70 0.516803E+09 40620.87 1.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 98933228.62 0.348935E+09 638525.05 1558273.44 0.312217E+09 171421.28 0.196286E+09 6475.16 0.80
February 81811220.41 0.412577E+09 511949.92 717610.25 0.337423E+09 609989.79 70976863.14 4071.53 0.82
March 64616373.99 0.550102E+09 472490.75 1294246.09 0.510234E+09 132753.79 0.155375E+09 5988.78 0.87
April 7903012.73 0.764850E+09 1161847.25 318529.85 0.708290E+09 0.00 17254284.46 10553.44 0.87
May 0.00 0.136279E+10 1348284.29 0.00 0.113317E+10 0.00 0.00 8587.12 0.87
June 0.00 0.177717E+10 1516787.96 0.00 0.141924E+10 0.00 0.00 8382.40 0.88
July 0.00 0.186337E+10 2374681.21 0.00 0.155080E+10 0.00 0.00 11050.28 0.85
August 0.00 0.198703E+10 1770813.17 0.00 0.153059E+10 0.00 0.00 8316.10 0.88
September 0.00 0.168320E+10 1842132.83 0.00 0.144782E+10 0.00 0.00 10297.95 0.86
October 0.00 0.137943E+10 2052150.94 0.00 0.121808E+10 0.00 0.00 9829.35 0.85
November 20191530.42 0.982294E+09 778252.94 256407.74 0.814722E+09 67069.58 17717592.35 6283.88 0.82
December 74524234.87 0.399048E+09 951490.07 1461487.20 0.519955E+09 143153.91 0.177856E+09 8889.44 0.81
                   
Annual Sum or Average 0.347980E+09 0.135108E+11 15419406.39 5606554.57 0.115025E+11 1124388.35 0.635465E+09 98725.42 0.85
Minimum of Months 0.00 0.348935E+09 472490.75 0.00 0.312217E+09 0.00 0.00 4071.53 0.80
Maximum of Months 98933228.62 0.198703E+10 2374681.21 1558273.44 0.155080E+10 609989.79 0.196286E+09 11050.28 0.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 24100553.16 35999911.37 199481.17 32197.69 68437624.17 67701.83 22440962.32 1510.94 0.88
February 16763448.30 49314462.94 176540.83 13958.94 68223699.94 92770.94 7447889.43 958.32 0.91
March 17675242.98 69121898.93 289924.94 36560.69 97911090.13 25154.92 16370980.52 1236.01 0.96
April 1989116.05 97659101.31 428384.11 10046.98 0.133826E+09 10650.64 1942990.56 2343.89 0.97
May 0.00 0.178240E+09 471705.44 0.00 0.214875E+09 0.00 0.00 2149.91 0.97
June 0.00 0.238562E+09 607884.10 0.00 0.265850E+09 0.00 0.00 2849.31 0.98
July 0.00 0.246735E+09 713032.74 0.00 0.293419E+09 0.00 0.00 4109.39 0.94
August 0.00 0.258896E+09 669551.03 0.00 0.296875E+09 0.00 0.00 4171.70 0.99
September 0.00 0.211144E+09 721706.92 0.00 0.286417E+09 0.00 0.00 2708.46 0.97
October 0.00 0.161800E+09 712908.16 0.00 0.251146E+09 0.00 0.00 3541.31 0.95
November 4999917.02 0.124726E+09 431238.06 3983.32 0.159270E+09 21372.80 1076494.83 2091.48 0.91
December 18085047.17 45084344.94 271231.97 30016.67 0.100685E+09 21346.24 21650953.57 2010.41 0.90
                   
Annual Sum or Average 83613324.67 0.171728E+10 5693589.46 126764.28 0.223694E+10 238997.38 70930271.24 29681.13 0.94
Minimum of Months 0.00 35999911.37 176540.83 0.00 68223699.94 0.00 0.00 958.32 0.88
Maximum of Months 24100553.16 0.258896E+09 721706.92 36560.69 0.296875E+09 92770.94 22440962.32 4171.70 0.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 41447100.31 27382551.64 315645.23 7893.86 89836535.36 121109.95 10815682.29 4570.38 0.77
February 23695499.86 33768388.68 262530.02 3382.05 98193081.01 206862.24 3410472.66 4703.53 0.79
March 30281199.41 47754614.25 432198.44 13450.47 0.139761E+09 99727.57 7918693.89 6043.54 0.84
April 3325056.40 75835829.55 531057.04 3738.53 0.184133E+09 11963.75 1099382.66 8185.86 0.84
May 0.00 0.137855E+09 829501.01 0.00 0.303421E+09 0.00 0.00 9346.17 0.84
June 0.00 0.178724E+09 907916.19 0.00 0.387642E+09 0.00 0.00 12247.37 0.85
July 0.00 0.186278E+09 906717.32 0.00 0.420357E+09 0.00 0.00 13874.16 0.82
August 0.00 0.182817E+09 841008.63 0.00 0.441376E+09 0.00 0.00 15269.78 0.86
September 0.00 0.160431E+09 928740.83 0.00 0.398348E+09 0.00 0.00 10921.47 0.84
October 0.00 0.111316E+09 978292.44 0.00 0.352357E+09 0.00 0.00 11459.11 0.83
November 6447300.17 96231568.46 567157.58 625.99 0.222691E+09 24007.83 382114.59 7970.75 0.80
December 35760163.13 33140188.28 355537.12 4004.96 0.130545E+09 102084.10 8826454.03 6946.51 0.79
                   
Annual Sum or Average 0.140956E+09 0.127153E+10 7856301.86 33095.86 0.316866E+10 565755.44 32452800.12 111538.62 0.82
Minimum of Months 0.00 27382551.64 262530.02 0.00 89836535.36 0.00 0.00 4570.38 0.77
Maximum of Months 41447100.31 0.186278E+09 978292.44 13450.47 0.441376E+09 206862.24 10815682.29 15269.78 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4280764.39 25928282.45 0.00 123538.42 12655109.38 0.00 12451719.99 0.00 0.33
February 3672965.59 33307245.73 0.00 64010.66 13751671.23 23879.83 4495232.93 0.00 0.35
March 2431022.14 45506074.18 0.00 112969.07 21378186.50 0.00 10549172.71 0.00 0.39
April 327785.87 66897398.26 0.00 31210.60 29012207.42 0.00 1347021.45 0.00 0.40
May 0.00 0.122567E+09 0.00 0.00 47328646.94 0.00 0.00 0.00 0.41
June 0.00 0.164076E+09 0.00 0.00 57778963.51 0.00 0.00 0.00 0.42
July 0.00 0.172992E+09 0.00 0.00 63687798.76 0.00 0.00 0.00 0.40
August 0.00 0.176637E+09 0.00 0.00 63208290.35 0.00 0.00 0.00 0.42
September 0.00 0.146669E+09 0.00 0.00 59715567.03 0.00 0.00 0.00 0.39
October 0.00 0.111186E+09 0.00 0.00 51154285.69 0.00 0.00 0.00 0.37
November 994276.93 78425325.85 0.00 20098.53 34139830.94 0.00 872986.93 0.00 0.36
December 3312805.08 31307122.25 0.00 111140.84 21104067.03 0.00 11500036.42 0.00 0.33
                   
Annual Sum or Average 15019619.99 0.117550E+10 0.00 462968.12 0.474915E+09 23879.83 41216170.42 0.00 0.38
Minimum of Months 0.00 25928282.45 0.00 0.00 12655109.38 0.00 0.00 0.00 0.33
Maximum of Months 4280764.39 0.176637E+09 0.00 123538.42 63687798.76 23879.83 12451719.99 0.00 0.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 80972536.34 0.296841E+09 426170.74 1432444.02 0.258450E+09 67610.47 0.168421E+09 3365.08 0.84
February 66487362.23 0.352347E+09 427181.54 679349.73 0.280132E+09 484381.68 61803520.65 2480.11 0.86
March 52792906.40 0.468769E+09 395181.61 1164752.00 0.424213E+09 110536.51 0.132631E+09 3221.01 0.92
April 6502702.45 0.651040E+09 886922.08 286697.69 0.588293E+09 0.00 14664915.44 6574.92 0.92
May 0.00 0.116220E+10 802691.47 0.00 0.938801E+09 0.00 0.00 4824.12 0.91
June 0.00 0.151325E+10 872024.47 0.00 0.117511E+10 0.00 0.00 4820.64 0.92
July 0.00 0.158527E+10 1394511.15 0.00 0.128258E+10 0.00 0.00 6147.62 0.88
August 0.00 0.168736E+10 1035724.82 0.00 0.127116E+10 0.00 0.00 4529.72 0.93
September 0.00 0.142898E+10 1168767.75 0.00 0.119735E+10 0.00 0.00 5009.55 0.90
October 0.00 0.116402E+10 1030866.31 0.00 0.101388E+10 0.00 0.00 5732.69 0.88
November 15432622.82 0.834976E+09 563119.82 241356.66 0.675566E+09 0.00 16315053.67 4087.71 0.86
December 60892476.66 0.339276E+09 753422.81 1322653.64 0.431246E+09 119196.10 0.153476E+09 4888.47 0.85
                   
Annual Sum or Average 0.283081E+09 0.114843E+11 9756584.57 5127253.74 0.953678E+10 781724.77 0.547312E+09 55681.65 0.89
Minimum of Months 0.00 0.296841E+09 395181.61 0.00 0.258450E+09 0.00 0.00 2480.11 0.84
Maximum of Months 80972536.34 0.168736E+10 1394511.15 1432444.02 0.128258E+10 484381.68 0.168421E+09 6574.92 0.93



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.119413E+09 0.107968E+10 0.00 5006353.02 0.323782E+09 0.00 0.472422E+09 0.00 0.43
February 86322655.43 0.134992E+10 0.00 2705189.27 0.320641E+09 8963275.56 0.157284E+09 0.00 0.46
March 87976394.90 0.181181E+10 0.00 3816730.55 0.503627E+09 0.00 0.309135E+09 0.00 0.49
April 8518585.62 0.263495E+10 0.00 1046139.01 0.612475E+09 0.00 44112621.69 0.00 0.49
May 0.00 0.462608E+10 0.00 0.00 0.102401E+10 0.00 0.00 0.00 0.50
June 0.00 0.613262E+10 0.00 0.00 0.123687E+10 0.00 0.00 0.00 0.52
July 0.00 0.678855E+10 0.00 0.00 0.120459E+10 0.00 0.00 0.00 0.50
August 0.00 0.696275E+10 0.00 0.00 0.130837E+10 0.00 0.00 0.00 0.53
September 0.00 0.610084E+10 0.00 0.00 0.119082E+10 0.00 0.00 0.00 0.51
October 0.00 0.480781E+10 0.00 0.00 0.110137E+10 0.00 0.00 0.00 0.49
November 23908177.33 0.327531E+10 0.00 892280.47 0.843820E+09 0.00 35139904.54 0.00 0.48
December 99546826.65 0.136327E+10 0.00 4163640.61 0.521479E+09 172317.98 0.415729E+09 0.00 0.44
                   
Annual Sum or Average 0.425686E+09 0.469336E+11 0.00 17630332.94 0.101919E+11 9135593.53 0.143382E+10 0.00 0.49
Minimum of Months 0.00 0.107968E+10 0.00 0.00 0.320641E+09 0.00 0.00 0.00 0.43
Maximum of Months 0.119413E+09 0.696275E+10 0.00 5006353.02 0.130837E+10 8963275.56 0.472422E+09 0.00 0.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 70313408.56 0.587865E+09 0.00 2539899.68 0.165516E+09 104538.87 0.231378E+09 0.00 0.45
February 43063176.92 0.729073E+09 0.00 1352220.57 0.163088E+09 9755692.22 75183261.53 0.00 0.48
March 58383853.50 0.982933E+09 0.00 1872966.70 0.257024E+09 63825.40 0.139788E+09 0.00 0.51
April 4494559.77 0.143365E+10 0.00 538067.20 0.311556E+09 0.00 22859607.76 0.00 0.52
May 0.00 0.253729E+10 0.00 0.00 0.512307E+09 0.00 0.00 0.00 0.54
June 0.00 0.339227E+10 0.00 0.00 0.613257E+09 0.00 0.00 0.00 0.56
July 0.00 0.379881E+10 0.00 0.00 0.581640E+09 0.00 0.00 0.00 0.54
August 0.00 0.387536E+10 0.00 0.00 0.647026E+09 0.00 0.00 0.00 0.57
September 0.00 0.344153E+10 0.00 0.00 0.575933E+09 0.00 0.00 0.00 0.55
October 0.00 0.270204E+10 0.00 0.00 0.541703E+09 0.00 0.00 0.00 0.53
November 14928274.93 0.180561E+10 0.00 482731.60 0.432436E+09 0.00 15111396.88 0.00 0.51
December 59568187.71 0.751814E+09 0.00 2127458.92 0.264253E+09 201602.91 0.206534E+09 0.00 0.46
                   
Annual Sum or Average 0.250751E+09 0.260382E+11 0.00 8913344.67 0.506574E+10 10125659.40 0.690854E+09 0.00 0.52
Minimum of Months 0.00 0.587865E+09 0.00 0.00 0.163088E+09 0.00 0.00 0.00 0.45
Maximum of Months 70313408.56 0.387536E+10 0.00 2539899.68 0.647026E+09 9755692.22 0.231378E+09 0.00 0.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 UTILITY

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 9508940.60 50302120.01 0.00 267231.53 30437336.04 0.00 27347531.45 0.00 0.27
February 8219502.49 64718762.90 0.00 133869.18 31835621.51 23199.65 9638857.27 0.00 0.29
March 5630156.65 88361553.01 0.00 239304.73 48700968.15 0.00 23106421.77 0.00 0.32
April 762524.07 0.129962E+09 0.00 60448.40 67595523.40 0.00 2655782.70 0.00 0.32
May 0.00 0.237822E+09 0.00 0.00 0.105981E+09 0.00 0.00 0.00 0.32
June 0.00 0.314851E+09 0.00 0.00 0.132813E+09 0.00 0.00 0.00 0.33
July 0.00 0.335174E+09 0.00 0.00 0.144017E+09 0.00 0.00 0.00 0.32
August 0.00 0.343890E+09 0.00 0.00 0.143347E+09 0.00 0.00 0.00 0.33
September 0.00 0.285415E+09 0.00 0.00 0.135145E+09 0.00 0.00 0.00 0.31
October 0.00 0.214303E+09 0.00 0.00 0.118730E+09 0.00 0.00 0.00 0.30
November 2131844.74 0.152897E+09 0.00 42806.65 78376989.71 0.00 1951649.84 0.00 0.29
December 7284131.13 59148764.29 0.00 241039.66 50098446.57 0.00 25247022.84 0.00 0.27
                   
Annual Sum or Average 33537099.68 0.227685E+10 0.00 984700.16 0.108708E+10 23199.65 89947265.87 0.00 0.31
Minimum of Months 0.00 50302120.01 0.00 0.00 30437336.04 0.00 0.00 0.00 0.27
Maximum of Months 9508940.60 0.343890E+09 0.00 267231.53 0.144017E+09 23199.65 27347531.45 0.00 0.33



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 WORK

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 57357325.54 0.294506E+09 24165.86 1178335.29 0.144920E+09 783557.53 0.118541E+09 2126.31 0.52
February 35547036.71 0.381445E+09 0.00 777066.01 0.153852E+09 7415506.64 43012365.26 0.00 0.58
March 37700610.32 0.560171E+09 24630.81 1207295.80 0.237562E+09 1592927.31 0.112528E+09 1085.92 0.67
April 3905786.07 0.900690E+09 0.00 344866.14 0.306220E+09 15362.87 17095209.34 0.00 0.72
May 0.00 0.168708E+10 0.00 0.00 0.463438E+09 0.00 0.00 0.00 0.76
June 0.00 0.233966E+10 0.00 0.00 0.527107E+09 0.00 0.00 0.00 0.80
July 0.00 0.259368E+10 0.00 0.00 0.510558E+09 0.00 0.00 0.00 0.77
August 0.00 0.250598E+10 0.00 0.00 0.583656E+09 0.00 0.00 0.00 0.78
September 0.00 0.212458E+10 0.00 0.00 0.555986E+09 0.00 0.00 0.00 0.74
October 0.00 0.153465E+10 0.00 0.00 0.534496E+09 0.00 0.00 0.00 0.69
November 12163587.13 0.947621E+09 85463.07 226852.51 0.375756E+09 107983.12 9147087.36 505.50 0.61
December 50002365.88 0.347158E+09 174054.12 892389.79 0.246814E+09 2392490.80 88192249.38 2949.57 0.51
                   
Annual Sum or Average 0.196677E+09 0.162172E+11 308313.86 4626805.54 0.464037E+10 12307828.28 0.388516E+09 6667.30 0.68
Minimum of Months 0.00 0.294506E+09 0.00 0.00 0.144920E+09 0.00 0.00 0.00 0.51
Maximum of Months 57357325.54 0.259368E+10 174054.12 1207295.80 0.583656E+09 7415506.64 0.118541E+09 2949.57 0.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: NE STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 47051969.67 0.146316E+09 95337.45 86926.62 43593298.41 27175345.06 9041302.97 2846.62 0.25
February 18768791.46 0.198522E+09 23806.02 135137.64 42922070.70 22277662.93 3497607.71 3218.39 0.28
March 25082840.97 0.274396E+09 41709.89 180883.23 63125644.61 28594142.37 7013252.70 2854.65 0.30
April 4280626.25 0.457411E+09 8995.28 116307.00 88349869.34 479915.96 6157613.06 37.58 0.37
May 0.00 0.102927E+10 0.00 0.00 0.114695E+09 0.00 0.00 0.00 0.47
June 0.00 0.153826E+10 0.00 0.00 0.122994E+09 0.00 0.00 0.00 0.53
July 0.00 0.176192E+10 0.00 0.00 0.114254E+09 0.00 0.00 0.00 0.52
August 0.00 0.161956E+10 0.00 0.00 0.143358E+09 0.00 0.00 0.00 0.50
September 0.00 0.139500E+10 0.00 0.00 0.128961E+09 0.00 0.00 0.00 0.47
October 0.00 0.926441E+09 0.00 0.00 0.127701E+09 0.00 0.00 0.00 0.39
November 3302352.59 0.537060E+09 29014.30 60352.50 0.106151E+09 5869361.29 1290046.33 1143.30 0.32
December 37263254.45 0.189283E+09 69457.47 61401.23 67552489.37 25989012.64 9547077.62 5146.83 0.25
                   
Annual Sum or Average 0.135750E+09 0.100734E+11 268320.40 641008.22 0.116366E+10 0.110385E+09 36546900.39 15247.37 0.39
Minimum of Months 0.00 0.146316E+09 0.00 0.00 42922070.70 0.00 0.00 0.00 0.25
Maximum of Months 47051969.67 0.176192E+10 95337.45 180883.23 0.143358E+09 28594142.37 9547077.62 5146.83 0.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: NW ELEVATOR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 46598896.45 0.107750E+09 226.71 289022.34 39325553.81 8493895.45 21474040.50 320.02 0.25
February 21440037.53 0.143474E+09 0.00 123029.19 31371606.62 11110752.77 4523326.83 0.00 0.27
March 27943540.25 0.188093E+09 1276.30 226707.17 47097601.67 14755630.07 11212008.28 212.03 0.28
April 4868747.71 0.307440E+09 0.00 83765.92 55749827.22 12711.75 3680471.00 0.00 0.30
May 0.00 0.595458E+09 0.00 0.00 94781856.99 0.00 0.00 0.00 0.34
June 0.00 0.806808E+09 0.00 0.00 0.130723E+09 0.00 0.00 0.00 0.36
July 0.00 0.971681E+09 0.00 0.00 0.114819E+09 0.00 0.00 0.00 0.36
August 0.00 0.965892E+09 0.00 0.00 0.126111E+09 0.00 0.00 0.00 0.38
September 0.00 0.850119E+09 0.00 0.00 0.107964E+09 0.00 0.00 0.00 0.36
October 0.00 0.609027E+09 0.00 0.00 95326596.56 0.00 0.00 0.00 0.32
November 5172248.37 0.387337E+09 0.00 60543.33 88081260.48 2548077.34 1240387.82 0.00 0.29
December 32547880.82 0.155165E+09 2989.32 248098.29 51052015.44 10892955.43 23305527.33 102.40 0.26
                   
Annual Sum or Average 0.138571E+09 0.608824E+10 4492.33 1031166.25 0.982404E+09 47814022.81 65435761.76 634.45 0.32
Minimum of Months 0.00 0.107750E+09 0.00 0.00 31371606.62 0.00 0.00 0.00 0.25
Maximum of Months 46598896.45 0.971681E+09 2989.32 289022.34 0.130723E+09 14755630.07 23305527.33 320.02 0.38



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: NW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 61415408.33 0.147858E+09 50879.54 48678.93 49121563.25 31119400.69 3600537.73 1538.71 0.24
February 23193179.07 0.201935E+09 9528.86 85353.55 50247452.10 25355250.52 1907273.26 1349.99 0.26
March 28334780.50 0.281264E+09 19238.66 137375.33 71449688.59 35608160.72 5802199.01 2334.12 0.28
April 5788745.47 0.498360E+09 0.00 122363.49 87071464.29 154894.03 6036739.77 0.00 0.35
May 0.00 0.115072E+10 0.00 0.00 0.110407E+09 0.00 0.00 0.00 0.45
June 0.00 0.169981E+10 0.00 0.00 0.118928E+09 0.00 0.00 0.00 0.51
July 0.00 0.196031E+10 0.00 0.00 0.107236E+09 0.00 0.00 0.00 0.50
August 0.00 0.178559E+10 0.00 0.00 0.137860E+09 0.00 0.00 0.00 0.48
September 0.00 0.147293E+10 0.00 0.00 0.136188E+09 0.00 0.00 0.00 0.44
October 0.00 0.945239E+09 0.00 0.00 0.144156E+09 0.00 0.00 0.00 0.35
November 3909256.05 0.553983E+09 5576.99 61784.30 0.120757E+09 6792287.20 1272529.35 50.40 0.29
December 46053284.62 0.195284E+09 19629.67 56955.16 76772535.88 28353041.36 9500552.65 2376.33 0.24
                   
Annual Sum or Average 0.168695E+09 0.108933E+11 104853.73 512510.76 0.121020E+10 0.127383E+09 28119831.78 7649.55 0.37
Minimum of Months 0.00 0.147858E+09 0.00 0.00 49121563.25 0.00 0.00 0.00 0.24
Maximum of Months 61415408.33 0.196031E+10 50879.54 137375.33 0.144156E+09 35608160.72 9500552.65 2376.33 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: SW STAIR

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 27597390.43 0.133191E+09 0.00 509068.79 16173874.58 3565550.09 36959946.95 0.00 0.36
February 14282356.23 0.156898E+09 0.00 207566.47 16292997.12 6557989.51 8801054.80 0.00 0.37
March 19010681.12 0.195165E+09 0.00 295926.68 23838931.77 8505738.55 16250527.23 0.00 0.37
April 2241675.06 0.290870E+09 0.00 86574.26 30419581.91 7498.26 4747643.30 0.00 0.38
May 0.00 0.522982E+09 0.00 0.00 58069946.43 0.00 0.00 0.00 0.42
June 0.00 0.714089E+09 0.00 0.00 74295155.51 0.00 0.00 0.00 0.44
July 0.00 0.852253E+09 0.00 0.00 61883975.14 0.00 0.00 0.00 0.44
August 0.00 0.874108E+09 0.00 0.00 68257497.79 0.00 0.00 0.00 0.47
September 0.00 0.819716E+09 0.00 0.00 57234797.54 0.00 0.00 0.00 0.48
October 0.00 0.633635E+09 0.00 0.00 44860439.24 0.00 0.00 0.00 0.44
November 3804721.17 0.415446E+09 0.00 120873.16 46413865.50 1243869.62 1810803.50 0.00 0.41
December 19056811.03 0.181050E+09 0.00 399802.05 23467464.72 5667394.90 35934610.67 0.00 0.37
                   
Annual Sum or Average 85993635.03 0.578940E+10 0.00 1619811.41 0.521209E+09 25548040.94 0.104505E+09 0.00 0.41
Minimum of Months 0.00 0.133191E+09 0.00 0.00 16173874.58 0.00 0.00 0.00 0.36
Maximum of Months 27597390.43 0.874108E+09 0.00 509068.79 74295155.51 8505738.55 36959946.95 0.00 0.48



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:39:14

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.224958E+12 -893582703.0 -0.201718E+11 -0.299568E+11 0.381219E+12
February 0.263828E+12 -0.224268E+10 -0.282991E+11 -0.497353E+11 0.385111E+12
March 0.364657E+12 -0.403033E+10 -0.374299E+11 -0.716842E+11 0.464347E+12
April 0.388883E+12 -0.591892E+10 -0.592114E+11 -0.119466E+12 0.514171E+12
May 0.384805E+12 -0.121129E+11 -0.992554E+11 -0.202512E+12 0.656596E+12
June 0.332529E+12 -0.121711E+11 -0.126346E+12 -0.253308E+12 0.727610E+12
July 0.349590E+12 -0.105230E+11 -0.134416E+12 -0.267661E+12 0.750985E+12
August 0.378095E+12 -0.122245E+11 -0.138221E+12 -0.275071E+12 0.773447E+12
September 0.288468E+12 -0.111585E+11 -0.123819E+12 -0.245652E+12 0.708005E+12
October 0.277389E+12 -0.101611E+11 -0.102508E+12 -0.208067E+12 0.646424E+12
November 0.214139E+12 -0.628734E+10 -0.709482E+11 -0.141096E+12 0.531158E+12
December 0.222947E+12 -0.234429E+10 -0.303211E+11 -0.563181E+11 0.406998E+12
           
Annual Sum or Average 0.369029E+13 -0.900683E+11 -0.970947E+12 -0.192053E+13 0.694607E+13
Minimum of Months 0.214139E+12 -0.122245E+11 -0.138221E+12 -0.275071E+12 0.381219E+12
Maximum of Months 0.388883E+12 -893582703.0 -0.201718E+11 -0.299568E+11 0.773447E+12