Table of Contents

Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 16:06

Tabular Output Report in Format: HTML

Building: US+MF+CZ1AWH+elecres+crawlspace+IECC_2006

Environment: ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2024-06-27 16:06:20


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 753639.17 19.32 34.87
Net Site Energy 753639.17 19.32 34.87
Total Source Energy 2386775.24 61.19 110.45
Net Source Energy 2386775.24 61.19 110.45


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.22
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.26


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 11621.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 190785.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 60500.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 47628.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 120995.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370400.12
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 753639.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370400.12
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 11621.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 190785.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 60500.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 17305.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 30323.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370400.12
  Water Heater 120995.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Unassigned 11621.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 190785.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 60500.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 47628.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 120995.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370400.12
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 3.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 17.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.14
Other 13.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 34.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.14


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 9.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.50
Other 7.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 19.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.50


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 753639.168 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 753639.168 100.00
     
Total On-Site and Utility Electric Sources 753639.168 100.00
Total Electricity End Uses 753639.168 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 370400.12 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 370400.12 100.00
Total Water End Uses 370400.12 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 20.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 3230.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Annual Thermal Resilience Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| CRAWLSPACE | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

General

Value
Program Version and Build EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 16:06
RunPeriod ANNUAL
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [ft] 36.09
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19513.17 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.9113 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.9113 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.9113 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.9113 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.9113 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.9113 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
Total 39005.22     286601.37   16363.00 740.10 2126.74 2126.74 0.5049 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.9113 600.28 2.9092
Unconditioned Total 17395.26     102861.98   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2] Tags
CRAWLSPACE 7794.39 No Yes 1.00 CRAWLSPACE GENERAL CRAWLSPACE 0.0000 0.00 0.0000  
BREEZEWAY 1798.16 No Yes 1.00 BREEZEWAY GENERAL BREEZEWAY 0.0000 0.00 0.0000  
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.9113 600.28 2.9092  
ATTIC 7802.71 No Yes 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL LIVING_UNIT3_BACKROW_TOPFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT3_FRONTROW_TOPFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT1_FRONTROW_TOPFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL LIVING_UNIT2_BACKROW_TOPFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT2_FRONTROW_TOPFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL LIVING_UNIT1_BACKROW_TOPFLOOR 0.9113 600.28 2.9092  
Total 39005.22             0.5049 1083.48 1.6118  
Conditioned Total 21609.96             0.9113 600.28 2.9092  
Unconditioned Total 17395.26             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [ft2] Conditioned Area [ft2] Unconditioned Area [ft2] Not Part of Total Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
GENERAL 39005.22 21609.96 17395.26 0.00 0.5049 1083.48 1.6118
Total 39005.22 21609.96 17395.26 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 06-JAN-19:40 - - - - - - - - - - - 01-JAN-08:19
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 22.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 19.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 47.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 179.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.34
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 280.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.34


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 22.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 19.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 3.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 5.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 5.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 26.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 1.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 3.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.34
  Water Heater 179.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 36806.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 604217.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 191605.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65251.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 150840.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 383192.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2386775.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 1.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 27.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 3.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 17.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 110.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 15.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 24.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 9.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 61.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 558.81
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 268.18
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 424.61
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 567.38
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 285.80
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 431.47
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 532.00
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 253.44
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 406.00
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 541.29
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 269.96
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 412.65
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 435.93
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 433.89
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 602.10
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 336.47
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 323.49
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 610.26
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 558.81 558.81 558.81 558.81 558.81 558.81 1.00 1.00 558.81
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 268.18 268.18 268.18 268.18 268.18 268.18 1.00 1.00 268.18
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 424.61 424.61 424.61 424.61 424.61 424.61 1.00 1.00 424.61
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 567.38 567.38 567.38 567.38 567.38 567.38 1.00 1.00 567.38
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 285.80 285.80 285.80 285.80 285.80 285.80 1.00 1.00 285.80
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 431.47 431.47 431.47 431.47 431.47 431.47 1.00 1.00 431.47
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 532.00 532.00 532.00 532.00 532.00 532.00 1.00 1.00 532.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 253.44 253.44 253.44 253.44 253.44 253.44 1.00 1.00 253.44
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 406.00 406.00 406.00 406.00 406.00 406.00 1.00 1.00 406.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 541.29 541.29 541.29 541.29 541.29 541.29 1.00 1.00 541.29
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 269.96 269.96 269.96 269.96 269.96 269.96 1.00 1.00 269.96
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 412.65 412.65 412.65 412.65 412.65 412.65 1.00 1.00 412.65
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 602.10 602.10 602.10 602.10 602.10 602.10 1.00 1.00 602.10
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 323.49 323.49 323.49 323.49 323.49 323.49 1.00 1.00 323.49
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 433.89 433.89 433.89 433.89 433.89 433.89 1.00 1.00 433.89
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 610.26 610.26 610.26 610.26 610.26 610.26 1.00 1.00 610.26
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 336.47 336.47 336.47 336.47 336.47 336.47 1.00 1.00 336.47
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 435.93 435.93 435.93 435.93 435.93 435.93 1.00 1.00 435.93
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 558.81 1.86 0.701083
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 268.18 0.893763 0.701083
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 424.61 1.42 0.701083
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 567.38 1.89 0.701083
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 285.80 0.952478 0.701083
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 431.47 1.44 0.701083
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 532.00 1.77 0.701083
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 253.44 0.844613 0.701083
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 406.00 1.35 0.701083
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 541.29 1.80 0.701083
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 269.96 0.899674 0.701083
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 412.65 1.38 0.701083
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 602.10 2.01 0.701083
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 323.49 1.08 0.701083
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 433.89 1.45 0.701083
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 610.26 2.03 0.701083
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 336.47 1.12 0.701083
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 435.93 1.45 0.701083
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 558.81 558.81 558.81 7689.60 1.86 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 268.18 268.18 268.18 5770.39 0.893763 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 424.61 424.61 424.61 7676.70 1.42 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 567.38 567.38 567.38 7703.55 1.89 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 285.80 285.80 285.80 5779.45 0.952478 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 431.47 431.47 431.47 7680.01 1.44 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 532.00 532.00 532.00 6362.15 1.77 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 253.44 253.44 253.44 4397.88 0.844613 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 406.00 406.00 406.00 6335.51 1.35 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 541.29 541.29 541.29 6381.93 1.80 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 269.96 269.96 269.96 4413.29 0.899674 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 412.65 412.65 412.65 6345.44 1.38 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 602.10 602.10 602.10 7830.86 2.01 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 323.49 323.49 323.49 5857.88 1.08 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 433.89 433.89 433.89 7796.02 1.45 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 610.26 610.26 610.26 7855.23 2.03 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 336.47 336.47 336.47 5879.58 1.12 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 435.93 435.93 435.93 7813.31 1.45 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 558.81
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 268.18
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 424.61
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 567.38
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 285.80
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 431.47
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 532.00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 253.44
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 406.00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 541.29
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 269.96
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 412.65
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 602.10
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 323.49
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 433.89
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 610.26
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 336.47
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 435.93
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 8843.04
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 6635.95
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 8828.21
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 8859.09
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 6646.37
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 8832.01
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 7316.48
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 5057.56
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 7285.84
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 7339.22
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 5075.28
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 7297.25
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 9005.49
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 6736.56
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 8965.42
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR 9033.52
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR 6761.52
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR 8985.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDF OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
BGWALL_UPPER_SDR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDB OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_SDL OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Version

Version ID
1 23.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 72.07 69.64 68.99 69.55 72.82 76.50 79.95 82.44 83.17 82.00 79.18 75.61


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 Miami Intl Ap FL USA TMY3 WMO#=722020 25.82 -80.30 -5.00 36.09 15. 1.2027


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 76.08 15.66 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ1AWH+elecres+crawlspace+IECC_2006 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Algorithm {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
Space Heat Balance Sizing

Space Heat Balance Simulation

1 ThirdOrderBackwardDifference No No


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.1351 Rough 0.0417 9.402E-002 42.764 0.280 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 4.9646 Rough 1.0053 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 1.9128 Rough 0.2917 4.648E-002 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 1.5339 Rough 0.2917 5.796E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.7000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.1467 Smooth 0.0347 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 5.1086E-003 VerySmooth 0.0066 0.391 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFSLABAVERAGE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABAVERAGESURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFSLABPERIMETER N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABPERIMETERTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFSLABCORE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABCORETEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 21 186 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CRAWLSPACE 0.0 0.00 0.00 0.00 59.94 32.51 -0.8 1 1 1 0.00 119.89 0.00 65.10 -2.0 0.49 2.49 19513.15 TARP DOE-2 7794.37 185.05 185.05 0.00 15 0 0 Yes
2 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
15 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
16 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
19 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
21 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 CRAWLSPACE 7794.37 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
15 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
16 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
19 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
21 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
4 ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
5 ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
12 ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
13 ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
20 ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
21 ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
28 ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
29 ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
36 ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
37 ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
44 ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
45 ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
52 ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
53 ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
60 ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
61 ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
68 ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
69 ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
76 ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
77 ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
84 ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
85 ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
92 ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
93 ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
100 ELECTRIC_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
101 ELECTRIC_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 ELECTRIC_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
108 ELECTRIC_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
109 ELECTRIC_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 ELECTRIC_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
116 ELECTRIC_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
117 ELECTRIC_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 ELECTRIC_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
124 ELECTRIC_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
125 ELECTRIC_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 ELECTRIC_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
132 ELECTRIC_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
133 ELECTRIC_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 ELECTRIC_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
140 ELECTRIC_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
141 ELECTRIC_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 ELECTRIC_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 10 0.167 0.0937 0.700 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 8 0.167 0.0704 0.900 0.900 0.700 0.700 Rough
4 INTERIOR FLOOR 5 2 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
5 INTERIOR CEILING 6 2 8 0.167 0.0349 0.900 0.900 0.700 0.700 Rough
6 ATTIC FLOOR 7 2 8 0.167 0.0349 0.900 0.900 0.700 0.700 MediumSmooth
7 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
8 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
9 EXTERIOR DOOR 14 1 3 0.167 1.200 0.900 0.900 0.700 0.700 Smooth
10 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth
11 CRAWL WALL 24 1 5 0.167 2.28 0.900 0.900 0.700 0.700 Rough
12 iz-EXTERIOR FLOOR 25 3 8 0.167 0.0704 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.0417 0.094 42.764 0.280 0.1351
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.2917 0.058 7.541 0.248 1.534
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.2917 0.046 3.438 0.219 1.913
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
11 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
12 CEIL_CONSOL_LAYER 1.0053 0.062 2.618 0.185 4.965
13 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 CEIL_CONSOL_LAYER 1.0053 0.062 2.618 0.185 4.965
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
18 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
19 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
20 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
21 DOOR_CONST 0.0348 0.072 32.003 0.183 0.1467
22 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
23 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
24 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
25 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
26 CONCRETE_4IN 0.3330 1.312 140.014 0.111 0.7736E-01
27 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
28 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
29 FLOOR_CONSOL_LAYER 0.2917 0.046 3.438 0.219 1.913


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 10 0.53690791E-10 -0.14086767E-13 0.12185568E-09 -0.56142619E-15
2 9 -0.78969438E-07 0.37271083E-11 -0.12786746E-06 0.41607738E-10
3 8 0.15644920E-04 0.57233592E-08 0.24713380E-04 -0.42390053E-07
4 7 -0.11010334E-02 0.13458163E-05 -0.17770580E-02 0.73075693E-05
5 6 0.34256138E-01 0.71913801E-04 0.57800664E-01 -0.42770275E-03
6 5 -0.50970556 0.10561809E-02 -0.91414050 0.10365322E-01
7 4 3.8008141 0.46021679E-02 7.1669335 -0.11749215
8 3 -14.731927 0.58137860E-02 -27.604869 0.65172867
9 2 29.625503 0.18019171E-02 52.431474 -1.7640469
10 1 -28.806601 0.81323549E-04 -47.206921 2.1946319
11 0 10.602175 0.49952751E-07 16.084904  
12 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
13 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
14 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
15 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
16 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
17 0 6.2472388 0.62260140E-03 6.2472388  
18 8 0.40635119E-15 0.16097338E-15 0.12402889E-12 -0.18568750E-15
19 7 -0.13383138E-10 0.15348756E-11 -0.13520613E-08 0.33293701E-12
20 6 0.10349336E-06 0.12392166E-07 0.19248154E-05 -0.38982260E-08
21 5 -0.82149362E-04 0.79233028E-05 -0.48611710E-03 0.53597054E-05
22 4 0.12410049E-01 0.62034537E-03 0.29187611E-01 -0.11998552E-02
23 3 -0.37605246 0.74510413E-02 -0.43184492 0.61361740E-01
24 2 2.1274249 0.15302681E-01 2.2910521 -0.59986906
25 1 -3.6069062 0.46322951E-02 -4.2736753 1.4694940
26 0 1.8712868 0.66704619E-04 2.4138456  
27 4 0.50405178E-13 0.16668152E-13 0.29402090E-13 -0.58636069E-16
28 3 -0.78967347E-05 0.18486376E-05 -0.51544008E-05 0.20741056E-12
29 2 0.37655193 0.34407043E-01 0.80677627E-01 -0.16328896E-04
30 1 -8.0349315 0.81344511 -1.1624309 0.21506451
31 0 8.9946927 0.48845120 2.4180636  
32 8 -0.19955962E-17 0.73322287E-16 0.22297369E-07 0.32822528E-16
33 7 -0.41677264E-07 0.10019220E-10 -0.10904919E-01 0.29209175E-07
34 6 0.51656634E-02 0.11264243E-06 0.41501785 -0.36203283E-02
35 5 -0.90145565E-01 0.13848923E-04 -4.5221814 0.64991548E-01
36 4 0.61381812 0.20608367E-03 22.362906 -0.45855939
37 3 -2.0715279 0.66281990E-03 -57.676573 1.6179231
38 2 3.6382511 0.50785658E-03 80.070402 -3.0000438
39 1 -3.1552904 0.73826575E-04 -56.558927 2.7719184
40 0 1.0611943 0.67997522E-06 15.921725  
41 8 0.22297369E-07 0.73322287E-16 -0.19955962E-17 0.32822528E-16
42 7 -0.10904919E-01 0.10019220E-10 -0.41677264E-07 0.29209175E-07
43 6 0.41501785 0.11264243E-06 0.51656634E-02 -0.36203283E-02
44 5 -4.5221814 0.13848923E-04 -0.90145565E-01 0.64991548E-01
45 4 22.362906 0.20608367E-03 0.61381812 -0.45855939
46 3 -57.676573 0.66281990E-03 -2.0715279 1.6179231
47 2 80.070402 0.50785658E-03 3.6382511 -3.0000438
48 1 -56.558927 0.73826575E-04 -3.1552904 2.7719184
49 0 15.921725 0.67997522E-06 1.0611943  
50 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
51 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
52 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
53 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
54 1 -19.904252 0.86481321 -19.904252 0.58144210
55 0 16.688993 0.62060609E-01 16.688993  
56 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
57 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
58 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
59 1 -11.299243 2.8799011 -8.6239668 0.15905732
60 0 15.219762 1.4410112 12.640375  
61 3 -0.18909144E-16 0.13700832E-16 -0.18909148E-16 0.0000000
62 2 0.92395679E-04 0.54616847E-04 0.92395679E-04 -0.14125355E-15
63 1 -2.1827077 1.2819567 -2.1827077 0.16364295E-03
64 0 8.9958201 5.5311936 8.9958201  
65 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
66 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
67 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
68 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
69 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
70 1 -64.420211 0.46601667 -21.697519 0.64629334
71 0 46.121323 0.20873329E-01 15.867130  
72 5 -0.15664505E-06 0.43005807E-07 -0.15664505E-06 0.11899247E-09
73 4 0.10791049E-02 0.34140917E-03 0.10791049E-02 -0.15677434E-05
74 3 -0.39592122 0.90314630E-01 -0.39592122 0.13116776E-02
75 2 11.651569 1.6702487 11.651569 -0.78737360E-01
76 1 -51.506798 3.1050242 -51.506798 0.66829999
77 0 45.538973 0.42297268 45.538973  
78 8 0.12402889E-12 0.16097338E-15 0.40635119E-15 -0.18568750E-15
79 7 -0.13520613E-08 0.15348756E-11 -0.13383138E-10 0.33293701E-12
80 6 0.19248154E-05 0.12392166E-07 0.10349336E-06 -0.38982260E-08
81 5 -0.48611710E-03 0.79233028E-05 -0.82149362E-04 0.53597054E-05
82 4 0.29187611E-01 0.62034537E-03 0.12410049E-01 -0.11998552E-02
83 3 -0.43184492 0.74510413E-02 -0.37605246 0.61361740E-01
84 2 2.2910521 0.15302681E-01 2.1274249 -0.59986906
85 1 -4.2736753 0.46322951E-02 -3.6069062 1.4694940
86 0 2.4138456 0.66704619E-04 1.8712868  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} Conductance (Before Adjusted) {Btu/h-ft2-F} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 1.200 1.027 1.168 0.335    
2 INTERIOR WINDOW 13 1 VerySmooth 1.200 1.027 1.168 0.335    
3 WINDOW_W_BLINDS 18 2 VerySmooth 1.200 1.027 1.168 0.309    
4 TDD DOME 22 1 VerySmooth 1.071 1.071 1.000 0.929    
5 TDD DIFFUSER 23 1 VerySmooth 1.077 1.077 1.000 0.906    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.00656 0.17310 0.28394 0.28394 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.39149 1.00000 No
2 GLASS SpectralAverage   0.00656 0.17310 0.28394 0.28394 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.39149 1.00000 No
3 GLASS SpectralAverage   0.00656 0.17310 0.28394 0.28394 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.39149 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
2 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
3 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
4 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
5 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
6 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
7 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
8 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
9 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
10 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
11 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
12 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
13 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
14 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
15 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
16 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
17 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
18 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
20 CRAWLVENT ALWAYS_AVAIL CRAWLSPACE 7794.37 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CRAWLSPACE Mixing/Well-Stirred
2 BREEZEWAY Mixing/Well-Stirred
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
15 ATTIC Mixing/Well-Stirred
16 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
21 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 13106.31886 13106.31886 558.81349 558.81349 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 89.87059 0.01717 1200.55323 2.00000 44.99491 0.00000
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 6601.56585 6601.56585 120.32096 120.32096 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 6290.16865 6290.16865 268.17793 268.17793 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 88.56410 0.01716 1200.55323 2.00000 44.99491 0.00000
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 4653.97527 4653.97527 84.82414 84.82414 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 9958.80288 9958.80288 424.59740 424.59740 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 88.38320 0.01716 1200.55323 2.00000 44.99491 0.00000
6 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 6588.47875 6588.47875 120.08240 120.08240 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
7 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 13307.09961 13307.09961 567.37281 567.37281 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 89.46860 0.01716 1200.55323 2.00000 44.99491 0.00000
8 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 6615.72667 6615.72667 120.57901 120.57901 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
9 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 6703.34185 6703.34185 285.80505 285.80505 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 87.96110 0.01716 1200.55323 2.00000 44.99491 0.00000
10 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 4663.17095 4663.17095 84.99194 84.99194 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
11 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 10119.65384 10119.65384 431.46181 431.46181 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 88.38320 0.01716 1200.55323 2.00000 44.99491 0.00000
12 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 6591.83336 6591.83336 120.14363 120.14363 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
13 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 12478.29645 12478.29645 531.99146 531.99146 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 89.66961 0.01716 1200.55323 2.00000 44.99491 0.00000
14 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 5254.47253 5254.47253 95.76969 95.76969 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
15 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 5944.60159 5944.60159 253.43217 253.43217 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 87.65960 0.01716 1200.55323 2.00000 44.99491 0.00000
16 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 3261.15725 3261.15725 59.43898 59.43898 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
17 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 9522.94168 9522.94168 405.99571 405.99571 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 88.68470 0.01716 1200.55323 2.00000 44.99491 0.00000
18 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 5227.44007 5227.44007 95.27689 95.27689 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
19 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 12696.17572 12696.17572 541.29230 541.29230 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 89.26759 0.01716 1200.55323 2.00000 44.99491 0.00000
20 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 5274.54536 5274.54536 96.13537 96.13537 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
21 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 6332.11318 6332.11318 269.95759 269.95759 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 87.65960 0.01716 1200.55323 2.00000 44.99491 0.00000
22 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 3276.79517 3276.79517 59.72414 59.72414 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
23 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 9678.94589 9678.94589 412.64825 412.64825 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 88.68470 0.01716 1200.55323 2.00000 44.99491 0.00000
24 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 5237.50933 5237.50933 95.46037 95.46037 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
25 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 10224.47877 10224.47877 435.93215 435.93215 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 88.98620 0.01716 1200.55323 2.00000 44.99491 0.00000
26 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 6727.10483 6727.10483 122.60888 122.60888 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
27 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 10176.53911 10176.53911 433.89825 433.89825 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 89.18721 0.01716 1200.55323 2.00000 44.99491 0.00000
28 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 6709.55599 6709.55599 122.28918 122.28918 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
29 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 14121.44926 14121.44926 602.09738 602.09738 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 89.46860 0.01716 1200.55323 2.00000 44.99491 0.00000
30 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 6744.91707 6744.91707 122.93367 122.93367 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
31 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 7891.75800 7891.75800 336.48301 336.48301 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 87.96110 0.01716 1200.55323 2.00000 44.99491 0.00000
32 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 4764.78625 4764.78625 86.84384 86.84384 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
33 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 7587.35052 7587.35052 323.49572 323.49572 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 88.26260 0.01716 1200.55323 2.00000 44.99491 0.00000
34 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 4742.75650 4742.75650 86.44236 86.44236 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000
35 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 14312.86829 14312.86829 610.25416 610.25416 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 89.46860 0.01716 1200.55323 2.00000 44.99491 0.00000
36 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 6769.64715 6769.64715 123.38431 123.38431 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 47.66000 0.00699 1200.55323 2.00000 44.99491 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 4000.89 558.81349 558.81349 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 2253.69 120.32096 120.32096 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 2011.85 268.17793 268.17793 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 1691.20 84.82414 84.82414 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 3069.80 424.59740 424.59740 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 2249.91 120.08240 120.08240 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 4053.20 567.37281 567.37281 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 2257.78 120.57901 120.57901 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 2122.69 285.80505 285.80505 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 1693.86 84.99194 84.99194 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 3116.29 431.46181 431.46181 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 2250.88 120.14363 120.14363 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 3816.45 531.99146 531.99146 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 1864.64 95.76969 95.76969 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 1899.04 253.43217 253.43217 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 1288.95 59.43898 59.43898 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 2948.08 405.99571 405.99571 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 1856.83 95.27689 95.27689 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 3873.70 541.29230 541.29230 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 1870.44 96.13537 96.13537 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 2011.06 269.95759 269.95759 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 1293.46 59.72414 59.72414 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 2993.17 412.64825 412.64825 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 1859.74 95.46037 95.46037 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 4288.61 602.09738 602.09738 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 2295.09 122.93367 122.93367 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 2382.54 323.49572 323.49572 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 1716.84 86.44236 86.44236 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 3144.20 433.89825 433.89825 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 2284.88 122.28918 122.28918 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 4343.94 610.25416 610.25416 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 2302.24 123.38431 123.38431 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 2466.24 336.48301 336.48301 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 1723.21 86.84384 86.84384 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 3155.20 435.93215 435.93215 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 2289.95 122.60888 122.60888 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 558.81349
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 268.17793
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 424.59740
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 567.37281
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 285.80505
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 431.46181
7 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 531.99146
8 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 253.43217
9 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 405.99571
10 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 541.29230
11 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 269.95759
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 412.64825
13 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 435.93215
14 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 433.89825
15 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 602.09738
16 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 336.48301
17 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 323.49572
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 610.25416
19 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 558.81349
20 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 558.81349
21 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 558.81349
22 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 558.81349
23 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 558.81349
24 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 558.81349
25 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
26 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
27 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 268.17793
28 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 268.17793
29 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 268.17793
30 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 268.17793
31 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 268.17793
32 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 268.17793
33 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
34 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
35 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 424.59740
36 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 424.59740
37 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 424.59740
38 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 424.59740
39 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 424.59740
40 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 424.59740
41 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
42 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
43 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 567.37281
44 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 567.37281
45 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 567.37281
46 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 567.37281
47 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 567.37281
48 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 567.37281
49 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
50 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
51 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 285.80505
52 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 285.80505
53 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 285.80505
54 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 285.80505
55 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 285.80505
56 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 285.80505
57 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
58 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
59 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 431.46181
60 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 431.46181
61 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 431.46181
62 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 431.46181
63 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 431.46181
64 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 431.46181
65 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
66 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
67 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 531.99146
68 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 531.99146
69 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 531.99146
70 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 531.99146
71 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 531.99146
72 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 531.99146
73 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
74 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
75 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 253.43217
76 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 253.43217
77 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 253.43217
78 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 253.43217
79 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 253.43217
80 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 253.43217
81 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
82 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
83 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 405.99571
84 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 405.99571
85 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 405.99571
86 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 405.99571
87 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 405.99571
88 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 405.99571
89 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
90 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
91 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 541.29230
92 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 541.29230
93 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 541.29230
94 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 541.29230
95 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 541.29230
96 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 541.29230
97 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
98 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
99 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 269.95759
100 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 269.95759
101 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 269.95759
102 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 269.95759
103 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 269.95759
104 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 269.95759
105 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
106 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
107 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 412.64825
108 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 412.64825
109 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 412.64825
110 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 412.64825
111 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 412.64825
112 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 412.64825
113 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
114 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
115 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 602.09738
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 602.09738
117 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 602.09738
118 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 602.09738
119 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 602.09738
120 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 602.09738
121 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
122 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
123 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 323.49572
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 323.49572
125 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 323.49572
126 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 323.49572
127 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 323.49572
128 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 323.49572
129 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
130 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
131 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 433.89825
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 433.89825
133 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 433.89825
134 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 433.89825
135 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 433.89825
136 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 433.89825
137 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
138 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
139 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 610.25416
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 610.25416
141 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 610.25416
142 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 610.25416
143 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 610.25416
144 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 610.25416
145 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
146 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
147 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 336.48301
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 336.48301
149 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 336.48301
150 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 336.48301
151 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 336.48301
152 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 336.48301
153 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
154 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
155 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 435.93215
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 435.93215
157 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 435.93215
158 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 435.93215
159 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 435.93215
160 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 435.93215
161 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
162 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
163 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 558.81349
164 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 268.17793
165 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 424.59740
166 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 567.37281
167 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 285.80505
168 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 431.46181
169 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 531.99146
170 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 253.43217
171 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 405.99571
172 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 541.29230
173 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 269.95759
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 412.64825
175 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 602.09738
176 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 323.49572
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 433.89825
178 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 610.25416
179 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 336.48301
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 435.93215
181 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 558.81349
182 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.86233
183 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
184 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 558.81349
185 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 558.81349
186 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 558.81349
187 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7689.59997
188 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.86233
189 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
190 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 558.81349
191 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 8843.03995
192 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 268.17793
193 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.89376
194 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
195 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 268.17793
196 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 268.17793
197 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 268.17793
198 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 5770.38733
199 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.89376
200 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
201 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 268.17793
202 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 6635.94544
203 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 424.59740
204 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.41506
205 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
206 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 424.59740
207 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 424.59740
208 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 424.59740
209 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7676.70350
210 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.41506
211 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
212 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 424.59740
213 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 8828.20904
214 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 567.37281
215 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.89086
216 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
217 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 567.37281
218 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 567.37281
219 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 567.37281
220 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7703.55447
221 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.89086
222 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
223 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 567.37281
224 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 8859.08764
225 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 285.80505
226 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.95248
227 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
228 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 285.80505
229 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 285.80505
230 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 285.80505
231 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 5779.44906
232 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.95248
233 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
234 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 285.80505
235 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 6646.36643
236 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 431.46181
237 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.43792
238 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
239 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 431.46181
240 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 431.46181
241 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 431.46181
242 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7680.00925
243 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.43792
244 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
245 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 431.46181
246 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 8832.01062
247 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 531.99146
248 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.77296
249 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
250 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 531.99146
251 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 531.99146
252 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 531.99146
253 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6362.15274
254 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.77296
255 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
256 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 531.99146
257 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 7316.47563
258 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 253.43217
259 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.84461
260 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
261 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 253.43217
262 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 253.43217
263 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 253.43217
264 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 4397.88037
265 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.84461
266 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
267 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 253.43217
268 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5057.56243
269 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 405.99571
270 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.35304
271 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
272 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 405.99571
273 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 405.99571
274 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 405.99571
275 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6335.51406
276 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.35304
277 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
278 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 405.99571
279 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 7285.84115
280 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 541.29230
281 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.80392
282 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
283 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 541.29230
284 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 541.29230
285 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 541.29230
286 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6381.93313
287 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.80392
288 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
289 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 541.29230
290 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 7339.22312
291 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 269.95759
292 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.89967
293 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
294 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 269.95759
295 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 269.95759
296 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 269.95759
297 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 4413.29047
298 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.89967
299 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
300 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 269.95759
301 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5075.28405
302 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 412.64825
303 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.37520
304 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
305 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 412.64825
306 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 412.64825
307 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 412.64825
308 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6345.43663
309 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.37520
310 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
311 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 412.64825
312 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 7297.25211
313 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 602.09738
314 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 2.00657
315 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
316 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 602.09738
317 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 602.09738
318 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 602.09738
319 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7830.86274
320 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 2.00657
321 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
322 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 602.09738
323 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 9005.49216
324 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 323.49572
325 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.07809
326 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
327 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 323.49572
328 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 323.49572
329 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 323.49572
330 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 5857.87507
331 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.07809
332 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
333 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 323.49572
334 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 6736.55634
335 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 433.89825
336 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.44600
337 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
338 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 433.89825
339 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 433.89825
340 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 433.89825
341 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7796.01684
342 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.44600
343 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
344 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 433.89825
345 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 8965.41938
346 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 610.25416
347 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 2.03378
348 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
349 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 610.25416
350 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 610.25416
351 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 610.25416
352 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7855.23254
353 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 2.03378
354 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
355 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 610.25416
356 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 9033.51744
357 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 336.48301
358 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.12135
359 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
360 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 336.48301
361 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 336.48301
362 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 336.48301
363 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 5879.58389
364 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.12135
365 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
366 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 336.48301
367 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 6761.52147
368 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 435.93215
369 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.45281
370 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
371 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 435.93215
372 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 435.93215
373 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 435.93215
374 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7813.31001
375 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.45281
376 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
377 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 435.93215
378 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 8985.30653
379 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
380 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
381 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
382 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
383 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
384 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
385 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
386 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
387 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
388 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
389 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
390 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
391 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
392 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
393 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
394 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
395 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
396 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
397 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
398 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
399 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
400 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
401 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
402 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
403 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
404 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
405 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
406 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
407 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
408 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
409 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
410 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
411 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
412 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
413 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
414 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
415 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
416 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
417 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
418 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
419 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
420 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
421 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
422 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
423 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
424 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
425 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
426 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
427 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
428 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
429 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
430 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
431 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
432 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
433 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
434 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
435 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
436 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
437 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
438 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
439 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
440 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
441 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
442 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
443 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
444 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
445 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
446 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
447 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
448 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
449 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
450 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
451 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
452 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
453 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
454 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
455 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
456 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
457 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
458 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
459 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
460 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
461 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
462 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
463 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
464 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
465 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
466 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
467 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
468 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.8 3.68 12.55 13.31 12.80 13.19
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.8 3.56 12.16 12.89 12.74 -99999.
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.9 3.68 12.55 13.31 12.80 13.19
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.9 3.56 12.16 12.89 12.74 -99999.
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 1.4 3.68 12.55 13.31 12.80 13.19
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 1.4 3.56 12.16 12.89 12.74 -99999.
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.8 3.68 12.55 13.31 12.80 13.19
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.8 3.56 12.16 12.89 12.74 -99999.
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.9 3.68 12.55 13.31 12.80 13.19
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.9 3.56 12.16 12.89 12.74 -99999.
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 1.4 3.68 12.55 13.31 12.80 13.19
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 1.4 3.56 12.16 12.89 12.74 -99999.
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.7 3.68 12.55 13.31 12.80 13.19
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.7 3.56 12.16 12.89 12.74 -99999.
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.8 3.68 12.55 13.31 12.80 13.19
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.8 3.56 12.16 12.89 12.74 -99999.
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 1.3 3.68 12.55 13.31 12.80 13.19
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 1.3 3.56 12.16 12.89 12.74 -99999.
19 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.7 3.68 12.55 13.31 12.80 13.19
20 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.7 3.56 12.16 12.89 12.74 -99999.
21 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.9 3.68 12.55 13.31 12.80 13.19
22 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.9 3.56 12.16 12.89 12.74 -99999.
23 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 1.3 3.68 12.55 13.31 12.80 13.19
24 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 1.3 3.56 12.16 12.89 12.74 -99999.
25 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.9 3.68 12.55 13.31 12.80 13.19
26 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.9 3.56 12.16 12.89 12.74 -99999.
27 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 1.0 3.68 12.55 13.31 12.80 13.19
28 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 1.0 3.56 12.16 12.89 12.74 -99999.
29 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1.4 3.68 12.55 13.31 12.80 13.19
30 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1.4 3.56 12.16 12.89 12.74 -99999.
31 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 2.0 3.68 12.55 13.31 12.80 13.19
32 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 2.0 3.56 12.16 12.89 12.74 -99999.
33 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 1.1 3.68 12.55 13.31 12.80 13.19
34 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 1.1 3.56 12.16 12.89 12.74 -99999.
35 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1.4 3.68 12.55 13.31 12.80 13.19
36 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1.4 3.56 12.16 12.89 12.74 -99999.


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 MIAMI INTL AP ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 01/21 01/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 07/21 07/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 6
2 6
3 6


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 47.66 0.00 DefaultMultipliers Wetbulb 8.70 {C} 15. 340 748.1 0.00 No No
2 91.76 6.70 DefaultMultipliers Wetbulb 25.30 {C} 15. 140 885.9 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 21 1229.0 0.1415 5.7310E-002 1.0 -11.15 -20. ASHRAEClearSky
2 202 1084.4 0.2082 0.1365 1.0 -6.23 20.6 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CRAWLSPACE SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000547740 0.000447901 Pass Pass 0.000000000 0.000000000 Pass Pass
2 BREEZEWAY SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000006547 0.000002734 Pass Pass 0.000000000 0.000000000 Pass Pass
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.016678748 0.029784849 Pass Pass
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.024933648 0.044208198 Pass Pass
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.016722281 0.029857764 Pass Pass
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.016635633 0.029710314 Pass Pass
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.024869461 0.044096968 Pass Pass
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.016707584 0.029834952 Pass Pass
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.020681481 0.036444680 Pass Pass
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.036521498 0.065180747 Pass Pass
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.020818559 0.036679596 Pass Pass
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.020582621 0.036274054 Pass Pass
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.036280945 0.064741805 Pass Pass
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.020761457 0.036585261 Pass Pass
15 ATTIC SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000153021 0.000128592 Pass Pass 0.000000000 0.000000000 Pass Pass
16 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015781819 0.026290265 Pass Pass
17 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015836151 0.026375987 Pass Pass
18 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015731386 0.026208663 Pass Pass
19 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.023377066 0.038911650 Pass Pass
20 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.023515416 0.039140772 Pass Pass
21 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015660393 0.026094133 Pass Pass
22 CRAWLSPACE SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.127360659 0.076648332 Pass Pass 0.000000000 0.000000000 Pass Pass
23 BREEZEWAY SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.117319717 0.059506975 Pass Pass 0.000000000 0.000000000 Pass Pass
24 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000054014 0.000286570 Pass Pass 0.083030260 0.040832428 Pass Pass
25 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000039063 0.000146767 Pass Pass 0.054279567 0.035027553 Pass Pass
26 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000047004 0.000182005 Pass Pass 0.067912818 0.072207860 Pass Pass
27 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000054102 0.000290227 Pass Pass 0.083873641 0.044963668 Pass Pass
28 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000041009 0.000161602 Pass Pass 0.055729627 0.037161674 Pass Pass
29 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000048387 0.000186970 Pass Pass 0.068789090 0.075783811 Pass Pass
30 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000051609 0.000290276 Pass Pass 0.077199028 0.035676858 Pass Pass
31 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000037207 0.000149374 Pass Pass 0.047857567 0.032592455 Pass Pass
32 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000064477 0.000245381 Pass Pass 0.062681134 0.064847794 Pass Pass
33 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000053903 0.000301630 Pass Pass 0.078164735 0.038844183 Pass Pass
34 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000039273 0.000180312 Pass Pass 0.049925327 0.033304265 Pass Pass
35 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000046235 0.000172548 Pass Pass 0.063807681 0.068056382 Pass Pass
36 ATTIC SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.402472870 0.333938090 Pass Pass 0.000000000 0.000000000 Pass Pass
37 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000046939 0.000173645 Pass Pass 0.063874257 0.065746961 Pass Pass
38 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000046768 0.000175393 Pass Pass 0.063294696 0.063034951 Pass Pass
39 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000057038 0.000309675 Pass Pass 0.079277578 0.033899061 Pass Pass
40 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000048458 0.000216304 Pass Pass 0.055859249 0.030762077 Pass Pass
41 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000046052 0.000201581 Pass Pass 0.054128017 0.031257546 Pass Pass
42 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000056912 0.000310563 Pass Pass 0.080197127 0.035736495 Pass Pass
43 CRAWLSPACE RunPeriod: ANNUAL 0.160788082 0.161806739 Pass Pass 0.000000000 0.000000000 Pass Pass
44 BREEZEWAY RunPeriod: ANNUAL 0.098174259 0.062067359 Pass Pass 0.000000000 0.000000000 Pass Pass
45 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.020516408 0.048262013 Pass Pass 0.242174460 0.738122256 Pass Pass
46 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.003686052 0.013110767 Pass Pass 0.254279575 0.475151841 Pass Pass
47 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.020912532 0.073847233 Pass Pass 0.197477205 0.466876854 Pass Pass
48 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.021849464 0.049035933 Pass Pass 0.210554888 0.566193733 Pass Pass
49 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.005775422 0.017161472 Pass Pass 0.215805131 0.412335120 Pass Pass
50 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.021113195 0.069066437 Pass Pass 0.217620621 0.745560744 Pass Pass
51 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.006383478 0.022077461 Pass Pass 0.237995370 0.429504138 Pass Pass
52 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000037657 0.000123223 Pass Pass 0.140514353 0.133013157 Pass Pass
53 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.006682839 0.028629757 Pass Pass 0.247984503 0.603496266 Pass Pass
54 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.007893097 0.022270795 Pass Pass 0.231410602 0.493817115 Pass Pass
55 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000000962 0.000002610 Pass Pass 0.140096760 0.174880083 Pass Pass
56 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.007001063 0.026906290 Pass Pass 0.217017196 0.484493825 Pass Pass
57 ATTIC RunPeriod: ANNUAL 0.456000830 0.444623602 Pass Pass 0.000000000 0.000000000 Pass Pass
58 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.017861235 0.058051013 Pass Pass 0.223550219 0.691009958 Pass Pass
59 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.017610639 0.061168847 Pass Pass 0.198976800 0.450937198 Pass Pass
60 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.017282190 0.040415138 Pass Pass 0.238568972 0.649145580 Pass Pass
61 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.002851112 0.010316854 Pass Pass 0.252835552 0.607871534 Pass Pass
62 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.001299962 0.006230366 Pass Pass 0.250354108 0.476616149 Pass Pass
63 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.018705626 0.042780349 Pass Pass 0.213344887 0.504114741 Pass Pass



Table of Contents

Report: Annual Heat Emissions Report

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Annual Heat Emissions Summary

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 2809971.77 -194097.8 -125472.8 0.00 1052790.64 3543196.44



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Heat Index Hours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
CRAWLSPACE 7024.33 1560.50 175.17 0.00 0.00
BREEZEWAY 4293.67 4411.00 55.33 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 4939.17 1707.83 1279.33 833.67 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 4293.67 0.00 0.00 0.00 0.00
Max 8760.00 4411.00 1279.33 833.67 0.00
Average 8282.72 365.68 71.90 39.70 0.00
Sum 173937.17 7679.33 1509.83 833.67 0.00


Heat Index OccupantHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 0.00 0.00 0.00 0.00
Average 10339.18 0.00 0.00 0.00 0.00
Sum 217122.86 0.00 0.00 0.00 0.00


Heat Index OccupiedHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 7508.57 0.00 0.00 0.00 0.00
Sum 157680.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CRAWLSPACE 2902.00 5831.67 26.33 0.00 0.00
BREEZEWAY 4329.50 4430.50 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 6007.83 2752.17 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5833.50 2926.50 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6267.83 2492.17 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5880.67 2879.33 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5573.33 3186.67 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6167.50 2592.50 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7234.67 1525.33 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7426.67 1333.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7409.33 1350.67 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7138.33 1621.67 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7302.67 1457.33 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7356.83 1403.17 0.00 0.00 0.00
ATTIC 2432.00 4642.83 989.67 601.17 94.33
LIVING_UNIT3_BACKROW_TOPFLOOR 6706.33 2053.67 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 6764.67 1995.33 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 6515.50 2244.50 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6394.67 2365.33 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6518.00 2242.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 6428.83 2331.17 0.00 0.00 0.00
Min 2432.00 1333.33 0.00 0.00 0.00
Max 7426.67 5831.67 989.67 601.17 94.33
Average 6123.37 2555.13 48.38 28.63 4.49
Sum 128590.67 53657.83 1016.00 601.17 94.33


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 7353.06 4709.33 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7331.16 4731.22 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7492.91 4569.47 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7237.19 4825.19 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 7096.95 4965.43 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7360.86 4701.52 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9425.19 2637.19 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9857.17 2205.21 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9586.68 2475.71 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9339.50 2722.88 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 9761.63 2300.76 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9517.40 2544.98 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8372.97 3689.41 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8444.10 3618.28 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8261.39 3801.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8377.03 3685.35 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8477.44 3584.95 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8188.39 3873.99 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 9857.17 4965.43 0.00 0.00 0.00
Average 7213.38 3125.80 0.00 0.00 0.00
Sum 151481.00 65641.86 0.00 0.00 0.00


Humidex OccupiedHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 6007.83 2752.17 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5833.50 2926.50 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6267.83 2492.17 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5880.67 2879.33 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5573.33 3186.67 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6167.50 2592.50 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7234.67 1525.33 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7426.67 1333.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7409.33 1350.67 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7138.33 1621.67 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7302.67 1457.33 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7356.83 1403.17 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 6706.33 2053.67 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 6764.67 1995.33 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 6515.50 2244.50 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6394.67 2365.33 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6518.00 2242.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 6428.83 2331.17 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 7426.67 3186.67 0.00 0.00 0.00
Average 5663.20 1845.37 0.00 0.00 0.00
Sum 118927.17 38752.83 0.00 0.00 0.00


Hours of Safety for Cold Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
CRAWLSPACE 0.00 - 0.00 0.00 0.00
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7508.57 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Hours of Safety for Heat Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
CRAWLSPACE 0.00 - 0.00 0.00 0.00
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7508.57 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Unmet Degree-Hours

Cooling Setpoint Unmet Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] Heating Setpoint Unmet Degree-Hours [°F·hr] Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Heating Setpoint Unmet Occupied Degree-Hours [°C·hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.63 0.42 0.63 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 21.10 12.09 21.10 0.01 0.01 0.01
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.55 0.91 1.55 0.00 0.01 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.37 0.29 0.37 0.01 0.01 0.01
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.02 0.97 1.02 0.01 0.01 0.01
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.01 0.63 1.01 0.02 0.03 0.02
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.49 0.35 0.49 0.00 0.01 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6.12 3.79 6.12 0.01 0.01 0.01
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.45 0.82 1.45 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.28 0.24 0.28 0.01 0.01 0.01
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.96 1.04 0.96 0.01 0.01 0.01
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.83 0.52 0.83 0.00 0.01 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1.61 1.02 1.61 0.01 0.01 0.01
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.88 1.15 1.88 0.00 0.01 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.56 0.41 0.56 0.01 0.01 0.01
LIVING_UNIT2_BACKROW_TOPFLOOR 1.10 1.04 1.10 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.66 1.44 1.66 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.42 0.33 0.42 0.01 0.01 0.01
Min 0.00 0.00 0.00 0.00 0.00 0.00
Max 21.10 12.09 21.10 0.02 0.03 0.02
Average 2.05 1.31 2.05 0.00 0.01 0.00
Sum 43.02 27.47 43.02 0.10 0.15 0.10


Discomfort-weighted Exceedance OccupantHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00


Discomfort-weighted Exceedance OccupiedHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 47.66 0.00 47.66 Wetbulb [F] 748.07 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 91.76 12.06 77.54 Wetbulb [F] 885.87 140.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [in] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [in] Monthly Total Roof Irrigation Depth [in] Monthly Total Rain Collection Volume [ft3]
Jan 2.56 29      
Feb 0.00 0      
Mar 0.00 0      
Apr 1.50 14      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 15.39 83      
Sep 0.00 0      
Oct 8.86 40      
Nov 0.00 0      
Dec 0.20 10      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.064 0.070 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.064 0.070 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.064 0.070 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.064 0.070 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.064 0.070 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.064 0.070 1200.55 1200.55 180.00 0.00  
BREEZEWAYROOF INTERIOR CEILING 0.30 0.033 0.035 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.064 0.070 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.064 0.070 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.064 0.070 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.064 0.070 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.064 0.070 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.064 0.070 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.033 0.035 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.033 0.035 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.033 0.035 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.033 0.035 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.033 0.035 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.033 0.035 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.033 0.035 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.033 0.035 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.033 0.035 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.033 0.035 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.033 0.035 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.033 0.035 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.033 0.035 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Frame and Divider Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 1.200 0.335 0.885             Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 1.200 0.335 0.885             Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 1.200 0.335 0.885             Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 1.200 0.335 0.885             Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 1.200 0.335 0.885             Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 1.200 0.335 0.885             Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 1.200 0.335 0.885             Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 1.200 0.335 0.885             Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 1.200 0.335 0.885             Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 1.200 0.335 0.885             Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 1.200 0.335 0.885             Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 1.200 0.335 0.885             Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 1.200 0.335 0.885             Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average             2126.74 1.200 0.335 0.885                      
North Total or Average             531.68 1.200 0.335 0.885                      
Non-North Total or Average             1595.05 1.200 0.335 0.885                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.594 1.200 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.78 0.00 1.00 0.99 0.99
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.78 0.00 1.00 0.99 0.99
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.78 0.00 1.00 0.99 0.99
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.96 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.96 0.00 0.74 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.96 0.00 0.74 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.96 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.96 0.00 0.74 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.78 0.00 1.00 0.99 0.99
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.78 0.00 1.00 0.99 0.99
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.78 0.00 1.00 0.99 0.99
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.96 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.96 0.00 0.74 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.96 0.00 0.74 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.96 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.96 0.00 0.74 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.96 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.96 0.00 0.74 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.78 0.00 1.00 0.99 0.99
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.96 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.78 0.00 1.00 0.99 0.99
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.96 0.00 0.74 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.78 0.00 1.00 0.99 0.99
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.96 0.00 0.74 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [Btu/h-ft2] Space Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total       0.4556 43219.92 19693.13               17719.17


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1377.69           6034.31



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Central Plant

Type Reference Capacity [Btu/h] Reference Efficiency [Btuh/Btuh] Rated Capacity [Btu/h] Rated Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   22347.92 15667.75 6680.17 0.70 4.30    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10725.16 7519.23 3205.93 0.70 4.30    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   16980.74 11904.91 5075.83 0.70 4.30    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   22690.32 15907.80 6782.52 0.70 4.30    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11429.74 8013.20 3416.54 0.70 4.30    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   17255.01 12097.20 5157.81 0.70 4.30    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   21275.50 14915.89 6359.60 0.70 4.30    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10135.36 7105.73 3029.63 0.70 4.30    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   16236.44 11383.10 4853.35 0.70 4.30    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   21647.04 15176.37 6470.66 0.70 4.30    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10796.09 7568.96 3227.13 0.70 4.30    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   16502.42 11569.57 4932.85 0.70 4.30    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   24078.90 16881.31 7197.59 0.70 4.30    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12937.07 9069.97 3867.11 0.70 4.30    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   17352.00 12165.20 5186.80 0.70 4.30    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   24405.32 17110.16 7295.16 0.70 4.30    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13456.17 9433.89 4022.27 0.70 4.30    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   17433.75 12222.51 5211.24 0.70 4.30    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.8 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.9 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   1.4 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.8 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.9 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   1.4 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.7 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.8 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   1.3 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.7 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.9 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   1.3 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.9 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   1.0 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.4 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   2.0 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   1.1 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.4 3.68 12.55 13.31 12.80 13.19
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coils [ SEER2 ]

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP2 [Btuh/Btuh] EER2 [Btu/W-h] SEER2 User [Btu/W-h] SEER2 Standard [Btu/W-h] IEER2 [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.8 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.4 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.8 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.4 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.7 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.7 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.9 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.4 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 2.0 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.4 3.56 12.16 12.89 12.74  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER2 User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER2 Standard is calculated using AHRI Std 210/240-2023 default PLF curve and cooling coefficient of degradation. IEER Calculation was removed from the 2023 Version of the Standard.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


Water-to-Air Heat Pumps at Rated Temperatures Report

Coil Type Rated Total Capacity [Btu/h] Rated Sensible Capacity [Btu/h] Rated Power[Btu/h] Rated COP [Btuh/Btuh] Rated Air Dry-bulb Temperature [F] Rated Air Wet-bulb Temperature [F] Rated Water Temperature [F] Design Day used for Sizing
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


DX Heating Coils [ HSPF2 ]

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF2 [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   8843.04 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   6635.95 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   8828.21 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   8859.09 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   6646.37 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   8832.01 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   7316.48 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   5057.56 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   7285.84 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   7339.22 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   5075.28 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   7297.25 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   9005.49 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   6736.56 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   8965.42 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   9033.52 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   6761.52 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   8985.31 1.00


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 558.81 210.78 0.38 1.00 2.04 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 268.18 101.16 0.38 1.00 2.94 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 424.61 160.16 0.38 1.00 2.31 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 567.38 214.01 0.38 1.00 2.03 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 285.80 107.80 0.38 1.00 2.84 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 431.47 162.75 0.38 1.00 2.29 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 532.00 200.67 0.38 1.00 2.08 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 253.44 95.59 0.38 1.00 3.04 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 406.00 153.14 0.38 1.00 2.36 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 541.29 204.17 0.38 1.00 2.07 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 269.96 101.83 0.38 1.00 2.93 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 412.65 155.65 0.38 1.00 2.34 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 602.10 227.11 0.38 1.00 1.98 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 323.49 122.02 0.38 1.00 2.65 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 433.89 163.66 0.38 1.00 2.28 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 610.26 230.19 0.38 1.00 1.97 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 336.47 126.92 0.38 1.00 2.60 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 435.93 164.43 0.38 1.00 2.28 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 13106.32 13106.32 10.92 558.815 558.815 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 75.00 74.99 0.00895 89.87 0.01717 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6290.17 6290.17 5.24 268.185 268.185 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 74.99 0.01009 88.56 0.01716 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 9958.80 9958.80 8.30 424.607 424.607 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 75.00 74.99 0.00927 88.38 0.01716 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 13307.10 13307.10 11.08 567.376 567.376 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 74.99 0.00896 89.47 0.01716 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 6703.34 6703.34 5.58 285.803 285.803 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 74.99 0.00999 87.96 0.01716 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 10119.65 10119.65 8.43 431.465 431.465 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 75.00 74.99 0.00924 88.38 0.01716 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12478.30 12478.30 10.39 531.998 531.998 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 75.00 75.00 0.00866 89.67 0.01717 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5944.60 5944.60 4.95 253.437 253.437 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 75.00 75.00 0.00963 87.66 0.01716 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9522.94 9522.94 7.93 405.996 405.996 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 75.00 75.00 0.00890 88.68 0.01716 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12696.18 12696.18 10.58 541.289 541.289 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 74.99 0.00866 89.27 0.01716 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6332.11 6332.11 5.27 269.959 269.959 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 75.00 75.00 0.00953 87.66 0.01716 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9678.95 9678.95 8.06 412.647 412.647 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 75.00 75.00 0.00888 88.68 0.01716 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 10224.48 10224.48 8.52 435.935 435.935 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 75.00 74.99 0.00923 88.99 0.01716 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 10176.54 10176.54 8.48 433.891 433.891 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 75.00 74.99 0.00924 89.19 0.01716 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 14121.45 14121.45 11.76 602.098 602.098 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 74.99 0.00888 89.47 0.01716 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 7891.76 7891.76 6.57 336.474 336.474 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 74.99 0.00969 87.96 0.01716 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 7587.35 7587.35 6.32 323.494 323.494 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 75.00 74.99 0.00975 88.26 0.01716 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 14312.87 14312.87 11.92 610.260 610.260 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 74.99 0.00887 89.47 0.01716 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 6601.57 6601.57 5.50 120.321 120.321 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00775 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4653.98 4653.98 3.88 84.824 84.824 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00772 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6588.48 6588.48 5.49 120.082 120.082 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00775 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 6615.73 6615.73 5.51 120.579 120.579 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00775 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4663.17 4663.17 3.88 84.992 84.992 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00772 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6591.83 6591.83 5.49 120.144 120.144 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00775 47.66 0.00699 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5254.47 5254.47 4.38 95.770 95.770 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00785 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 3261.16 3261.16 2.72 59.439 59.439 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00785 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5227.44 5227.44 4.35 95.277 95.277 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00785 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5274.55 5274.55 4.39 96.135 96.135 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00785 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3276.80 3276.80 2.73 59.724 59.724 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00785 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5237.51 5237.51 4.36 95.460 95.460 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00785 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 6727.10 6727.10 5.60 122.609 122.609 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00775 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 6709.56 6709.56 5.59 122.289 122.289 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00775 47.66 0.00699 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 6744.92 6744.92 5.62 122.934 122.934 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00775 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 4764.79 4764.79 3.97 86.844 86.844 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00773 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 4742.76 4742.76 3.95 86.442 86.442 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00773 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 6769.65 6769.65 5.64 123.384 123.384 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00775 47.66 0.00699 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 558.81 558.81 120.32 120.32 558.8145 558.8145 558.8145 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 268.18 268.18 84.82 84.82 268.1850 268.1850 268.1850 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 424.61 424.61 120.08 120.08 424.6071 424.6071 424.6071 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 567.38 567.38 120.58 120.58 567.3762 567.3762 567.3762 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 285.80 285.80 84.99 84.99 285.8031 285.8031 285.8031 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 431.47 431.47 120.14 120.14 431.4651 431.4651 431.4651 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 532.00 532.00 95.77 95.77 531.9983 531.9983 531.9983 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 253.44 253.44 59.44 59.44 253.4367 253.4367 253.4367 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 406.00 406.00 95.28 95.28 405.9958 405.9958 405.9958 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 541.29 541.29 96.14 96.14 541.2888 541.2888 541.2888 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 269.96 269.96 59.72 59.72 269.9586 269.9586 269.9586 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 412.65 412.65 95.46 95.46 412.6466 412.6466 412.6466 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 602.10 602.10 122.93 122.93 602.0980 602.0980 602.0980 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 323.49 323.49 86.44 86.44 323.4943 323.4943 323.4943 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 433.89 433.89 122.29 122.29 433.8905 433.8905 433.8905 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 610.26 610.26 123.38 123.38 610.2601 610.2601 610.2601 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 336.47 336.47 86.84 86.84 336.4743 336.4743 336.4743 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 435.93 435.93 122.61 122.61 435.9347 435.9347 435.9347 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 22347.922 15667.753 558.814531 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 21965.56 16382.87 558.814531 77.36 63.90 0.00960850 53.60 51.31 0.00750000 89.87 0.01716522 77.10 8.0519 74.99 0.00894676 48.4025 13106.32 0.00 22357.25 15656.91
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 8843.040 8843.040 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8843.04 8843.04 -999. 70.04 58.28 0.00768523 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00774587 46.4319 6601.57 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 10725.162 7519.231 268.184962 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 11081.82 6976.26 268.184962 78.44 66.63 0.01128043 53.60 51.31 0.00750000 88.56 0.01716384 76.77 16.7776 74.99 0.01007396 54.4023 6275.70 0.00 10729.64 7514.03
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 6635.945 6635.945 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6635.95 6635.95 -999. 67.92 57.33 0.00760068 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00772322 46.2975 4653.98 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 16980.744 11904.914 424.607104 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 17029.61 12013.25 424.607104 77.58 64.69 0.01010393 53.60 51.31 0.00750000 88.38 0.01716364 76.72 10.5969 74.99 0.00926905 50.1199 9955.16 0.00 16987.83 11896.67
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 8828.209 8828.209 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8828.21 8828.21 -999. 69.42 58.01 0.00766583 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00774559 46.4303 6588.48 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 22690.317 15907.800 567.376192 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 22348.62 16662.60 567.376192 77.31 63.88 0.00960772 53.60 51.31 0.00750000 89.47 0.01716479 77.00 7.9304 74.99 0.00894269 48.3810 13305.40 0.00 22699.78 15896.79
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 8859.088 8859.088 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8859.09 8859.09 -999. 70.07 58.29 0.00768642 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00774616 46.4336 6615.73 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 11429.741 8013.199 285.803096 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 11791.63 7523.12 285.803096 78.20 66.33 0.01111550 53.60 51.31 0.00750000 87.96 0.01716319 76.61 15.7434 74.99 0.00998621 53.9363 6697.03 0.00 11434.51 8007.65
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 6646.366 6646.366 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6646.37 6646.37 -999. 68.17 57.44 0.00760845 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00772348 46.2990 4663.17 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 17255.007 12097.196 431.465132 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 17289.90 12241.85 431.465132 77.56 64.64 0.01006942 53.60 51.31 0.00750000 88.38 0.01716364 76.72 10.4284 74.99 0.00924347 49.9836 10119.65 0.00 17262.21 12088.82
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 8832.011 8832.011 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8832.01 8832.01 -999. 69.46 58.03 0.00766716 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00774566 46.4307 6591.83 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 21275.495 14915.893 531.998291 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 20841.82 15998.30 531.998291 77.41 63.57 0.00937631 53.60 51.31 0.00750000 89.67 0.01716500 77.05 8.4577 75.00 0.00865670 46.8525 12478.30 0.00 21284.37 14905.57
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 7316.476 7316.476 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 7316.48 7316.48 -999. 69.94 58.39 0.00777386 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00784602 47.0239 5254.47 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 10135.355 7105.727 253.436710 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 10451.20 6783.76 253.436710 78.41 66.19 0.01096970 53.60 51.31 0.00750000 87.66 0.01716288 76.53 17.7539 75.00 0.00962176 51.9954 5930.31 0.00 10139.58 7100.81
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 5057.562 5057.562 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 5057.56 5057.56 -999. 67.68 57.40 0.00769674 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00784868 47.0394 3261.16 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 16236.445 11383.099 405.995754 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 16162.25 11800.38 405.995754 77.68 64.30 0.00981319 53.60 51.31 0.00750000 88.68 0.01716396 76.80 11.0826 75.00 0.00889744 48.1365 9515.14 0.00 16243.22 11375.22
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 7285.841 7285.841 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 7285.84 7285.84 -999. 69.30 58.11 0.00775107 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00784558 47.0213 5227.44 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 21647.037 15176.374 541.288759 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 21247.22 16314.02 541.288759 77.35 63.54 0.00937044 53.60 51.31 0.00750000 89.27 0.01716457 76.95 8.3126 74.99 0.00865421 46.8393 12695.87 0.00 21656.07 15165.87
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 7339.223 7339.223 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 7339.22 7339.22 -999. 69.98 58.41 0.00777539 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00784634 47.0258 5274.55 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 10796.093 7568.960 269.958602 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 11082.45 7303.87 269.958602 78.27 65.92 0.01080469 53.60 51.31 0.00750000 87.66 0.01716288 76.53 16.6674 75.00 0.00952986 51.5064 6321.36 0.00 10800.60 7563.72
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 5075.284 5075.284 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 5075.28 5075.28 -999. 67.94 57.52 0.00770630 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00784899 47.0413 3276.80 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 16502.423 11569.572 412.646595 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 16413.78 12027.15 412.646595 77.66 64.25 0.00978050 53.60 51.31 0.00750000 88.68 0.01716396 76.80 10.9040 75.00 0.00887688 48.0268 9678.95 0.00 16509.31 11561.56
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 7297.252 7297.252 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 7297.25 7297.25 -999. 69.35 58.13 0.00775274 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00784574 47.0223 5237.51 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 24078.899 16881.312 602.097986 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 23658.51 17854.05 602.097986 77.24 63.70 0.00950334 53.60 51.31 0.00750000 89.47 0.01716479 77.00 7.4730 74.99 0.00887043 47.9956 14119.48 0.00 24088.95 16869.63
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 9005.492 9005.492 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 9005.49 9005.49 -999. 70.18 58.35 0.00769216 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00774864 46.4483 6744.92 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 12937.075 9069.966 323.494303 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 13207.80 8698.67 323.494303 78.01 65.80 0.01078095 53.60 51.31 0.00750000 88.26 0.01716351 76.69 13.9090 74.99 0.00974608 52.6594 7581.03 0.00 12942.47 9063.69
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 6736.556 6736.556 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6736.56 6736.56 -999. 68.61 57.64 0.00762358 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00772548 46.3109 4742.76 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 17352.003 12165.198 433.890517 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 17309.31 12276.49 433.890517 77.63 64.65 0.01006124 53.60 51.31 0.00750000 89.19 0.01716449 76.93 10.3701 74.99 0.00923940 49.9620 10176.54 0.00 17359.24 12156.78
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 8965.419 8965.419 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8965.42 8965.42 -999. 69.48 58.04 0.00766962 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00774792 46.4440 6709.56 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 24405.317 17110.158 610.260147 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 23965.94 18137.14 610.260147 77.23 63.66 0.00947931 53.60 51.31 0.00750000 89.47 0.01716479 77.00 7.3731 74.99 0.00886755 47.9803 14312.87 0.00 24415.50 17098.31
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 9033.517 9033.517 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 9033.52 9033.52 -999. 70.20 58.36 0.00769338 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00774914 46.4513 6769.65 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 13456.167 9433.893 336.474317 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 13724.44 9117.76 336.474317 77.90 65.63 0.01068550 53.60 51.31 0.00750000 87.96 0.01716319 76.61 13.3725 74.99 0.00968465 52.3328 7882.67 0.00 13461.78 9427.36
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 6761.521 6761.521 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6761.52 6761.52 -999. 68.74 57.69 0.00762803 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00772608 46.3144 4764.79 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 17433.753 12222.512 435.934714 -999. -999.00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 17404.71 12356.39 435.934714 77.61 64.62 0.01005004 53.60 51.31 0.00750000 88.99 0.01716428 76.87 10.3215 74.99 0.00923340 49.9299 10218.67 0.00 17441.03 12214.05
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 8985.307 8985.307 -999. -999. -999.00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8985.31 8985.31 -999. 69.49 58.05 0.00767030 122.00 75.14 0.00800000 47.66 0.00699286 47.66 -999.000 72.00 0.00774827 46.4461 6727.10 0.00 -999.0 -999.0



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 22347.922 15667.753 558.814531 -999. -999.00 -999.0000 1.00000 0.86261 0.2443 0.2400 0.0751 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 558.814531 0.69937631   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 Sensible 21965.56 16382.87 0.9829 0.69937631 558.814531 77.36 63.90 0.00960850 11.9 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 719.184 21246.38 89.87 0.01716522 77.10 44.99498340 8.0519 74.99 0.00894676 74.99 0.00894676 48.4025 13106.32 0.00 22357.25 15656.91 0.67175623 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8843.040 8843.040 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 558.814531 0.69937631   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 8843.04 8843.04 1.0000 -0.264891E+04 -999. 70.04 58.28 0.00768523 9.7 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8843.04 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00774587 72.00 0.00774587 46.4319 6601.57 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10725.162 7519.231 268.184962 -999. -999.00 -999.0000 1.00000 0.72031 0.2450 0.2400 0.0751 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 268.184962 0.33564304   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 11081.82 6976.26 1.0333 0.33564304 268.184962 78.44 66.63 0.01128043 13.1 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 345.149 10736.67 88.56 0.01716384 76.77 44.99498340 16.7776 74.99 0.01009434 74.99 0.01007396 54.4023 6275.70 0.00 10729.64 7514.03 0.32238768 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6635.945 6635.945 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 268.184962 0.33564304   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 6635.95 6635.95 1.0000 -0.264891E+04 -999. 67.92 57.33 0.00760068 9.4 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6635.95 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00772322 72.00 0.00772322 46.2975 4653.98 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 16980.744 11904.914 424.607104 -999. -999.00 -999.0000 1.00000 0.81972 0.2445 0.2400 0.0751 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 424.607104 0.53141093   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 Sensible 17029.61 12013.25 1.0029 0.53141093 424.607104 77.58 64.69 0.01010393 12.2 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 546.461 16483.14 88.38 0.01716364 76.72 44.99498340 10.5969 74.99 0.00926715 74.99 0.00926905 50.1199 9955.16 0.00 16987.83 11896.67 0.51042422 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8828.209 8828.209 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 424.607104 0.53141093   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 8828.21 8828.21 1.0000 -0.264891E+04 -999. 69.42 58.01 0.00766583 9.6 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8828.21 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00774559 72.00 0.00774559 46.4303 6588.48 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 22690.317 15907.800 567.376192 -999. -999.00 -999.0000 1.00000 0.86581 0.2443 0.2400 0.0751 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 567.376192 0.71009153   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 22348.62 16662.60 0.9849 0.71009153 567.376192 77.31 63.88 0.00960772 11.9 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 730.203 21618.42 89.47 0.01716479 77.00 44.99498340 7.9304 74.99 0.00895680 74.99 0.00894269 48.3810 13305.40 0.00 22699.78 15896.79 0.68204829 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8859.088 8859.088 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 567.376192 0.71009153   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 8859.09 8859.09 1.0000 -0.264891E+04 -999. 70.07 58.29 0.00768642 9.7 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8859.09 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00774616 72.00 0.00774616 46.4336 6615.73 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11429.741 8013.199 285.803096 -999. -999.00 -999.0000 1.00000 0.73643 0.2449 0.2400 0.0751 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 285.803096 0.35769276   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 11791.63 7523.12 1.0317 0.35769276 285.803096 78.20 66.33 0.01111550 12.9 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 367.823 11423.81 87.96 0.01716319 76.61 44.99498340 15.7434 74.99 0.00998549 74.99 0.00998621 53.9363 6697.03 0.00 11434.51 8007.65 0.34356660 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6646.366 6646.366 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 285.803096 0.35769276   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 6646.37 6646.37 1.0000 -0.264891E+04 -999. 68.17 57.44 0.00760845 9.4 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6646.37 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00772348 72.00 0.00772348 46.2990 4663.17 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 17255.007 12097.196 431.465132 -999. -999.00 -999.0000 1.00000 0.82312 0.2445 0.2400 0.0751 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 431.465132 0.53999400   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 Sensible 17289.90 12241.85 1.0020 0.53999400 431.465132 77.56 64.64 0.01006942 12.2 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 555.288 16734.61 88.38 0.01716364 76.72 44.99498340 10.4284 74.99 0.00924347 74.99 0.00924347 49.9836 10119.65 0.00 17262.21 12088.82 0.51866832 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8832.011 8832.011 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 431.465132 0.53999400   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 8832.01 8832.01 1.0000 -0.264891E+04 -999. 69.46 58.03 0.00766716 9.6 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8832.01 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00774566 72.00 0.00774566 46.4307 6591.83 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 21275.495 14915.893 531.998291 -999. -999.00 -999.0000 1.00000 0.88638 0.2442 0.2400 0.0751 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 531.998291 0.66581483   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 Sensible 20841.82 15998.30 0.9796 0.66581483 531.998291 77.41 63.57 0.00937631 11.8 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 684.672 20157.15 89.67 0.01716500 77.05 44.99498340 8.4577 75.00 0.00865670 75.00 0.00865670 46.8525 12478.30 0.00 21284.37 14905.57 0.63952018 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7316.476 7316.476 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 531.998291 0.66581483   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 7316.48 7316.48 1.0000 -0.264891E+04 -999. 69.94 58.39 0.00777386 9.8 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7316.48 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00784602 72.00 0.00784602 47.0239 5254.47 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10135.355 7105.727 253.436710 -999. -999.00 -999.0000 1.00000 0.74420 0.2449 0.2400 0.0751 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 253.436710 0.31718508   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 10451.20 6783.76 1.0312 0.31718508 253.436710 78.41 66.19 0.01096970 12.9 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 326.168 10125.03 87.66 0.01716288 76.53 44.99498340 17.7539 75.00 0.00963282 75.00 0.00962176 51.9954 5930.31 0.00 10139.58 7100.81 0.30465867 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 5057.562 5057.562 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 253.436710 0.31718508   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 5057.56 5057.56 1.0000 -0.264891E+04 -999. 67.68 57.40 0.00769674 9.4 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5057.56 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00784868 72.00 0.00784868 47.0394 3261.16 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 16236.445 11383.099 405.995754 -999. -999.00 -999.0000 1.00000 0.84212 0.2444 0.2400 0.0751 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 405.995754 0.50811816   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 Sensible 16162.25 11800.38 0.9954 0.50811816 405.995754 77.68 64.30 0.00981319 12.1 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 522.509 15639.74 88.68 0.01716396 76.80 44.99498340 11.0826 75.00 0.00889699 75.00 0.00889744 48.1365 9515.14 0.00 16243.22 11375.22 0.48805134 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7285.841 7285.841 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 405.995754 0.50811816   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 7285.84 7285.84 1.0000 -0.264891E+04 -999. 69.30 58.11 0.00775107 9.7 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7285.84 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00784558 72.00 0.00784558 47.0213 5227.44 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 21647.037 15176.374 541.288759 -999. -999.00 -999.0000 1.00000 0.89036 0.2442 0.2400 0.0751 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 541.288759 0.67744218   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 21247.22 16314.02 0.9815 0.67744218 541.288759 77.35 63.54 0.00937044 11.7 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 696.629 20550.60 89.27 0.01716457 76.95 44.99498340 8.3126 75.00 0.00866380 74.99 0.00865421 46.8393 12695.87 0.00 21656.07 15165.87 0.65068834 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7339.223 7339.223 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 541.288759 0.67744218   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 7339.22 7339.22 1.0000 -0.264891E+04 -999. 69.98 58.41 0.00777539 9.8 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7339.22 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00784634 72.00 0.00784634 47.0258 5274.55 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10796.093 7568.960 269.958602 -999. -999.00 -999.0000 1.00000 0.75736 0.2448 0.2400 0.0751 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 269.958602 0.33786282   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 11082.45 7303.87 1.0265 0.33786282 269.958602 78.27 65.92 0.01080469 12.7 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 347.432 10735.02 87.66 0.01716288 76.53 44.99498340 16.6674 75.00 0.00953299 75.00 0.00952986 51.5064 6321.36 0.00 10800.60 7563.72 0.32451979 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 5075.284 5075.284 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 269.958602 0.33786282   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 5075.28 5075.28 1.0000 -0.264891E+04 -999. 67.94 57.52 0.00770630 9.5 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5075.28 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00784899 72.00 0.00784899 47.0413 3276.80 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 16502.423 11569.572 412.646595 -999. -999.00 -999.0000 1.00000 0.84565 0.2443 0.2400 0.0751 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 412.646595 0.51644193   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 Sensible 16413.78 12027.15 0.9946 0.51644193 412.646595 77.66 64.25 0.00978050 12.0 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 531.069 15882.71 88.68 0.01716396 76.80 44.99498340 10.9040 75.00 0.00887688 75.00 0.00887688 48.0268 9678.95 0.00 16509.31 11561.56 0.49604637 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7297.252 7297.252 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 412.646595 0.51644193   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 7297.25 7297.25 1.0000 -0.264891E+04 -999. 69.35 58.13 0.00775274 9.7 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7297.25 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00784574 72.00 0.00784574 47.0223 5237.51 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 24078.899 16881.312 602.097986 -999. -999.00 -999.0000 1.00000 0.87787 0.2442 0.2400 0.0751 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 602.097986 0.75354710   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 23658.51 17854.05 0.9825 0.75354710 602.097986 77.24 63.70 0.00950334 11.8 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 774.889 22883.62 89.47 0.01716479 77.00 44.99498340 7.4730 74.99 0.00888455 74.99 0.00887043 47.9956 14119.48 0.00 24088.95 16869.63 0.72378768 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9005.492 9005.492 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 602.097986 0.75354710   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 9005.49 9005.49 1.0000 -0.264891E+04 -999. 70.18 58.35 0.00769216 9.8 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9005.49 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00774864 72.00 0.00774864 46.4483 6744.92 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 12937.075 9069.966 323.494303 -999. -999.00 -999.0000 1.00000 0.76044 0.2448 0.2400 0.0751 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 323.494303 0.40486465   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 Sensible 13207.80 8698.67 1.0209 0.40486465 323.494303 78.01 65.80 0.01078095 12.7 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 416.331 12791.47 88.26 0.01716351 76.69 44.99498340 13.9090 74.99 0.00974976 74.99 0.00974608 52.6594 7581.03 0.00 12942.47 9063.69 0.38887556 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6736.556 6736.556 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 323.494303 0.40486465   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 6736.56 6736.56 1.0000 -0.264891E+04 -999. 68.61 57.64 0.00762358 9.5 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6736.56 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00772548 72.00 0.00772548 46.3109 4742.76 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 17352.003 12165.198 433.890517 -999. -999.00 -999.0000 1.00000 0.81854 0.2445 0.2400 0.0751 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 433.890517 0.54302945   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 Sensible 17309.31 12276.49 0.9975 0.54302945 433.890517 77.63 64.65 0.01006124 12.2 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 558.409 16750.90 89.19 0.01716449 76.93 44.99498340 10.3701 74.99 0.00923940 74.99 0.00923940 49.9620 10176.54 0.00 17359.24 12156.78 0.52158389 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8965.419 8965.419 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 433.890517 0.54302945   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 8965.42 8965.42 1.0000 -0.264891E+04 -999. 69.48 58.04 0.00766962 9.6 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8965.42 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00774792 72.00 0.00774792 46.4440 6709.56 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 24405.317 17110.158 610.260147 -999. -999.00 -999.0000 1.00000 0.88069 0.2442 0.2400 0.0751 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 610.260147 0.76376233   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 23965.94 18137.14 0.9820 0.76376233 610.260147 77.23 63.66 0.00947931 11.8 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 785.393 23180.55 89.47 0.01716479 77.00 44.99498340 7.3731 74.99 0.00886755 74.99 0.00886755 47.9803 14312.87 0.00 24415.50 17098.31 0.73359949 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9033.517 9033.517 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 610.260147 0.76376233   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 9033.52 9033.52 1.0000 -0.264891E+04 -999. 70.20 58.36 0.00769338 9.8 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9033.52 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00774914 72.00 0.00774914 46.4513 6769.65 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13456.167 9433.893 336.474317 -999. -999.00 -999.0000 1.00000 0.77035 0.2447 0.2400 0.0751 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 336.474317 0.42110960   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 13724.44 9117.76 1.0199 0.42110960 336.474317 77.90 65.63 0.01068550 12.6 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 433.036 13291.40 87.96 0.01716319 76.61 44.99498340 13.3725 74.99 0.00968556 74.99 0.00968465 52.3328 7882.67 0.00 13461.78 9427.36 0.40447896 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6761.521 6761.521 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 336.474317 0.42110960   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 6761.52 6761.52 1.0000 -0.264891E+04 -999. 68.74 57.69 0.00762803 9.5 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6761.52 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00772608 72.00 0.00772608 46.3144 4764.79 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 17433.753 12222.512 435.934714 -999. -999.00 -999.0000 1.00000 0.82099 0.2445 0.2400 0.0751 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 435.934714 0.54558784   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 Sensible 17404.71 12356.39 0.9983 0.54558784 435.934714 77.61 64.62 0.01005004 12.2 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 561.040 16843.67 88.99 0.01716428 76.87 44.99498340 10.3215 74.99 0.00923123 74.99 0.00923340 49.9299 10218.67 0.00 17441.03 12214.05 0.52404124 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865782 8.1
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8985.307 8985.307 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 435.934714 0.54558784   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 8985.31 8985.31 1.0000 -0.264891E+04 -999. 69.49 58.05 0.00767030 9.7 122.00 75.14 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8985.31 47.66 0.00699286 47.66 44.99498340 -999.000 72.00 0.00774827 72.00 0.00774827 46.4461 6727.10 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 7416.17 3512.83 2630.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7336.83 3531.67 2739.17
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7418.33 3191.33 2375.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7230.17 3812.50 2751.67
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 7106.00 4041.17 2978.83
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7208.67 3481.33 2467.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7410.33 2159.00 1397.67
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7344.83 1728.00 1151.83
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7425.33 1928.00 1240.83
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7229.67 2419.83 1490.33
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7091.67 2101.00 1266.33
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7210.83 2159.50 1289.83
LIVING_UNIT3_BACKROW_TOPFLOOR 7327.00 2841.83 1933.50
LIVING_UNIT3_FRONTROW_TOPFLOOR 7488.17 2651.17 1880.67
LIVING_UNIT1_FRONTROW_TOPFLOOR 7458.83 2951.67 2110.17
LIVING_UNIT2_BACKROW_TOPFLOOR 7243.00 3067.33 2168.33
LIVING_UNIT2_FRONTROW_TOPFLOOR 7447.67 2774.83 2061.00
LIVING_UNIT1_BACKROW_TOPFLOOR 7337.33 3165.00 2196.83
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 7640.83 4400.83 3230.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 20.17 0.00 20.17
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 4.00 0.00 4.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 20.17 0.00 20.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.253 0.000 0.262
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.223 0.000 0.262
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.253 0.000 0.262
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.253 0.000 0.262
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.223 0.000 0.262
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.253 0.000 0.262
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.111 0.000 0.262
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.081 0.000 0.262
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.111 0.000 0.262
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.111 0.000 0.262
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.081 0.000 0.262
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.111 0.000 0.262
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.253 0.000 0.262
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.253 0.000 0.262
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.253 0.000 0.262
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.223 0.000 0.262
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.223 0.000 0.262
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.253 0.000 0.262
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
Total Facility   24.79 36.00 183739.38 21609.96 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 23032711.24 23032711.24 22247970.62 45280681.86 23785081.69 7458.83 808.67 540.50 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 23032711.24 23032711.24 19614036.17 42646747.41 23785081.69 7458.83 808.67 540.50 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 23032711.24 23032711.24 22255916.72 45288627.96 23785081.69 7458.83 808.67 540.50 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 23032711.24 23032711.24 22230550.14 45263261.38 23785081.69 7458.83 808.67 540.50 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 23032711.24 23032711.24 19592744.11 42625455.36 23785081.69 7458.83 808.67 540.50 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 23032711.24 23032711.24 22240021.84 45272733.08 23785081.69 7458.83 808.67 540.50 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 23034014.39 23034014.39 9754206.78 32788221.17 23785081.69 7453.50 812.17 542.33 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 23034014.39 23034014.39 7102981.25 30136995.64 23785081.69 7453.50 812.17 542.33 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 23034014.39 23034014.39 9757337.14 32791351.54 23785081.69 7453.50 812.17 542.33 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 23034014.39 23034014.39 9747482.84 32781497.23 23785081.69 7453.50 812.17 542.33 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 23034014.39 23034014.39 7096777.71 30130792.10 23785081.69 7453.50 812.17 542.33 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 23034014.39 23034014.39 9752036.70 32786051.09 23785081.69 7453.50 812.17 542.33 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 23035318.91 23035318.91 22251242.63 45286561.54 23785081.69 7448.17 816.00 543.83 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 23035318.91 23035318.91 22262284.06 45297602.97 23785081.69 7448.17 816.00 543.83 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 23035318.91 23035318.91 22254161.44 45289480.34 23785081.69 7448.17 816.00 543.83 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 23035318.91 23035318.91 19605481.85 42640800.76 23785081.69 7448.17 816.00 543.83 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 23035318.91 23035318.91 19619764.58 42655083.48 23785081.69 7448.17 816.00 543.83 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 23035318.91 23035318.91 22241420.83 45276739.74 23785081.69 7448.17 816.00 543.83 0.00
Total Facility 0.00 0.414612E+09 0.414612E+09 0.309626E+09 0.724239E+09 0.428131E+09 7458.83 819.33 543.83 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 43.5717 43.5717 42.0872 85.6589 44.9950 7458.83 808.67 540.50
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 43.5717 43.5717 37.1045 80.6762 44.9950 7458.83 808.67 540.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 43.5717 43.5717 42.1022 85.6739 44.9950 7458.83 808.67 540.50
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 43.5717 43.5717 42.0542 85.6259 44.9950 7458.83 808.67 540.50
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 43.5717 43.5717 37.0642 80.6359 44.9950 7458.83 808.67 540.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 43.5717 43.5717 42.0721 85.6438 44.9950 7458.83 808.67 540.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 43.5742 43.5742 18.4523 62.0265 44.9950 7453.50 812.17 542.33
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 43.5742 43.5742 13.4369 57.0111 44.9950 7453.50 812.17 542.33
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 43.5742 43.5742 18.4583 62.0324 44.9950 7453.50 812.17 542.33
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 43.5742 43.5742 18.4396 62.0138 44.9950 7453.50 812.17 542.33
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 43.5742 43.5742 13.4252 56.9994 44.9950 7453.50 812.17 542.33
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 43.5742 43.5742 18.4482 62.0224 44.9950 7453.50 812.17 542.33
LIVING_UNIT3_BACKROW_TOPFLOOR 0.0000 43.5766 43.5766 42.0934 85.6700 44.9950 7448.17 816.00 543.83
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0000 43.5766 43.5766 42.1143 85.6909 44.9950 7448.17 816.00 543.83
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0000 43.5766 43.5766 42.0989 85.6755 44.9950 7448.17 816.00 543.83
LIVING_UNIT2_BACKROW_TOPFLOOR 0.0000 43.5766 43.5766 37.0883 80.6649 44.9950 7448.17 816.00 543.83
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0000 43.5766 43.5766 37.1153 80.6920 44.9950 7448.17 816.00 543.83
LIVING_UNIT1_BACKROW_TOPFLOOR 0.0000 43.5766 43.5766 42.0748 85.6514 44.9950 7448.17 816.00 543.83
Total Facility 0.0000 784.3350 784.3350 585.7300 1370.0650 809.9097 7458.83 819.33 543.83


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 23032711.24 23032711.24 23785081.69 7458.83 808.67 540.50 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 23032711.24 23032711.24 23785081.69 7458.83 808.67 540.50 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 23032711.24 23032711.24 23785081.69 7458.83 808.67 540.50 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 23032711.24 23032711.24 23785081.69 7458.83 808.67 540.50 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 23032711.24 23032711.24 23785081.69 7458.83 808.67 540.50 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 23032711.24 23032711.24 23785081.69 7458.83 808.67 540.50 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 23034014.39 23034014.39 23785081.69 7453.50 812.17 542.33 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 23034014.39 23034014.39 23785081.69 7453.50 812.17 542.33 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 23034014.39 23034014.39 23785081.69 7453.50 812.17 542.33 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 23034014.39 23034014.39 23785081.69 7453.50 812.17 542.33 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 23034014.39 23034014.39 23785081.69 7453.50 812.17 542.33 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 23034014.39 23034014.39 23785081.69 7453.50 812.17 542.33 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 23035318.91 23035318.91 23785081.69 7448.17 816.00 543.83 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 23035318.91 23035318.91 23785081.69 7448.17 816.00 543.83 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 23035318.91 23035318.91 23785081.69 7448.17 816.00 543.83 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 23035318.91 23035318.91 23785081.69 7448.17 816.00 543.83 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 23035318.91 23035318.91 23785081.69 7448.17 816.00 543.83 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 23035318.91 23035318.91 23785081.69 7448.17 816.00 543.83 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 43.5717 43.5717 44.9950 7458.83 808.67 540.50
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 43.5717 43.5717 44.9950 7458.83 808.67 540.50
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 43.5717 43.5717 44.9950 7458.83 808.67 540.50
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 43.5717 43.5717 44.9950 7458.83 808.67 540.50
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 43.5717 43.5717 44.9950 7458.83 808.67 540.50
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 43.5717 43.5717 44.9950 7458.83 808.67 540.50
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 43.5742 43.5742 44.9950 7453.50 812.17 542.33
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 43.5742 43.5742 44.9950 7453.50 812.17 542.33
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 43.5742 43.5742 44.9950 7453.50 812.17 542.33
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 43.5742 43.5742 44.9950 7453.50 812.17 542.33
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 43.5742 43.5742 44.9950 7453.50 812.17 542.33
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 43.5742 43.5742 44.9950 7453.50 812.17 542.33
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 43.5766 43.5766 44.9950 7448.17 816.00 543.83
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 43.5766 43.5766 44.9950 7448.17 816.00 543.83
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 43.5766 43.5766 44.9950 7448.17 816.00 543.83
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 43.5766 43.5766 44.9950 7448.17 816.00 543.83
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 43.5766 43.5766 44.9950 7448.17 816.00 543.83
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 43.5766 43.5766 44.9950 7448.17 816.00 543.83


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1922
Defaulted Fields 1699
Fields with Defaults 6199
Autosized Fields 342
Autosizable Fields 504
Autocalculated Fields 161
Autocalculatable Fields 349



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 220722.63 8374.61 05-JAN-03:20 82096.44 06-JAN-19:30
Electricity:Building 106022.24 6418.34 02-JAN-03:10 20705.41 01-JAN-18:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
Electricity:SpaceType:GENERAL 106022.24 6418.34 02-JAN-03:10 20705.41 01-JAN-18:10
InteriorLights:Electricity 17719.17 396.81 01-JAN-00:10 5771.73 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
InteriorLights:Electricity:SpaceType:GENERAL 17719.17 396.81 01-JAN-00:10 5771.73 01-JAN-19:10
General:InteriorLights:Electricity 17719.17 396.81 01-JAN-00:10 5771.73 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:SpaceType:GENERAL 17719.17 396.81 01-JAN-00:10 5771.73 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
InteriorEquipment:Electricity:SpaceType:GENERAL 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
Fans:Electricity 13949.28 578.57 05-JAN-03:20 3285.78 04-FEB-07:00
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 220722.63 8374.61 05-JAN-03:20 82096.44 06-JAN-19:30
ElectricityPurchased:Plant 220722.63 8374.61 05-JAN-03:20 82096.44 06-JAN-19:30
Cogeneration:ElectricityPurchased 220722.63 8374.61 05-JAN-03:20 82096.44 06-JAN-19:30
General:Cogeneration:ElectricityPurchased 220722.63 8374.61 05-JAN-03:20 82096.44 06-JAN-19:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 220722.63 8374.61 05-JAN-03:20 82096.44 06-JAN-19:30
ElectricityNet:Plant 220722.63 8374.61 05-JAN-03:20 82096.44 06-JAN-19:30
Cogeneration:ElectricityNet 220722.63 8374.61 05-JAN-03:20 82096.44 06-JAN-19:30
General:Cogeneration:ElectricityNet 220722.63 8374.61 05-JAN-03:20 82096.44 06-JAN-19:30
Electricity:HVAC 73229.45 578.57 05-JAN-03:20 35982.27 04-FEB-07:00
Ventilation:Fans:Electricity 5068.29 578.57 01-JAN-00:10 578.57 01-JAN-00:10
General:Fans:Electricity 8880.99 0.00 05-JAN-03:20 2707.21 04-FEB-07:00
ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 3403.77 0.00 01-JAN-00:10 32696.49 04-FEB-07:00
General:Heating:Electricity 3403.77 0.00 01-JAN-00:10 32696.49 04-FEB-07:00
Cooling:Electricity 55876.40 0.00 05-JAN-03:20 18225.06 29-JUL-16:10
General:Cooling:Electricity 55876.40 0.00 05-JAN-03:20 18225.06 29-JUL-16:10
Electricity:Plant 35436.63 0.00 01-JAN-00:10 54379.41 01-JAN-07:10
WaterSystems:Electricity 35436.63 0.00 01-JAN-00:10 54379.41 01-JAN-07:10
Water Heater:WaterSystems:Electricity 35436.63 0.00 01-JAN-00:10 54379.41 01-JAN-07:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
Water:Plant 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
WaterSystems:Water 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
Domestic Hot Water:WaterSystems:Water 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
MainsWater:Facility 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
MainsWater:Plant 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
WaterSystems:MainsWater 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
Domestic Hot Water:WaterSystems:MainsWater 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 1493769.63 355.20 02-APR-04:00 447681.55 29-JUL-16:20
EnergyTransfer:Building 573457.36 0.00 05-JAN-03:20 194547.63 29-JUL-16:20
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer 12596.73 0.00 01-JAN-00:10 120809.64 04-FEB-07:00
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 12596.73 0.00 01-JAN-00:10 120809.64 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 560860.63 0.00 05-JAN-03:20 194547.63 29-JUL-16:20
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer 560860.63 0.00 05-JAN-03:20 194547.63 29-JUL-16:20
General:Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 34591.16 0.00 01-JAN-01:30 13852.31 29-JUL-16:20
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1000.68 0.00 01-JAN-00:10 8284.28 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1000.68 0.00 01-JAN-00:10 8284.28 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 33590.48 0.00 01-JAN-01:30 13852.31 29-JUL-16:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 33590.48 0.00 01-JAN-01:30 13852.31 29-JUL-16:20
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 26331.01 0.00 01-JAN-03:40 8224.34 07-NOV-14:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 468.35 0.00 01-JAN-00:10 5624.94 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 468.35 0.00 01-JAN-00:10 5624.94 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 25862.66 0.00 01-JAN-03:40 8224.34 07-NOV-14:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 25862.66 0.00 01-JAN-03:40 8224.34 07-NOV-14:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 34678.64 0.00 01-JAN-01:20 11324.94 13-OCT-10:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 876.86 0.00 01-JAN-00:10 8225.55 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 876.86 0.00 01-JAN-00:10 8225.55 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 33801.77 0.00 01-JAN-01:20 11324.94 13-OCT-10:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 33801.77 0.00 01-JAN-01:20 11324.94 13-OCT-10:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 31082.81 0.00 01-JAN-01:20 13766.86 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1215.93 0.00 01-JAN-00:10 8372.71 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1215.93 0.00 01-JAN-00:10 8372.71 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 29866.88 0.00 01-JAN-01:20 13766.86 29-JUL-16:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 29866.88 0.00 01-JAN-01:20 13766.86 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 22634.47 0.00 01-JAN-03:30 7649.48 29-JUL-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 655.17 0.00 01-JAN-00:10 5756.55 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 655.17 0.00 01-JAN-00:10 5756.55 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 21979.30 0.00 01-JAN-03:30 7649.48 29-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 21979.30 0.00 01-JAN-03:30 7649.48 29-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 30873.97 0.00 01-JAN-01:20 11264.75 25-JUL-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1014.07 0.00 01-JAN-00:10 8245.13 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1014.07 0.00 01-JAN-00:10 8245.13 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29859.91 0.00 01-JAN-01:20 11264.75 25-JUL-10:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29859.91 0.00 01-JAN-01:20 11264.75 25-JUL-10:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 35666.43 0.00 01-JAN-03:30 13291.86 30-SEP-15:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 536.32 0.00 01-JAN-00:10 6162.43 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 536.32 0.00 01-JAN-00:10 6162.43 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 35130.11 0.00 01-JAN-03:30 13291.86 30-SEP-15:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 35130.11 0.00 01-JAN-03:30 13291.86 30-SEP-15:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 27835.99 0.00 05-JAN-03:20 8111.68 07-NOV-15:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 146.51 0.00 01-JAN-00:10 3430.09 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 146.51 0.00 01-JAN-00:10 3430.09 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 27689.48 0.00 05-JAN-03:20 8111.68 07-NOV-15:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 27689.48 0.00 05-JAN-03:20 8111.68 07-NOV-15:10
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 35898.49 0.00 01-JAN-03:30 11011.09 30-AUG-11:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 459.31 0.00 01-JAN-00:10 6106.16 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 459.31 0.00 01-JAN-00:10 6106.16 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 35439.19 0.00 01-JAN-03:30 11011.09 30-AUG-11:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 35439.19 0.00 01-JAN-03:30 11011.09 30-AUG-11:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 32034.34 0.00 01-JAN-03:20 13014.16 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 686.36 0.00 01-JAN-00:10 6288.24 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 686.36 0.00 01-JAN-00:10 6288.24 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 31347.98 0.00 01-JAN-03:20 13014.16 29-JUL-16:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 31347.98 0.00 01-JAN-03:20 13014.16 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 23889.63 0.00 05-JAN-03:10 7112.28 29-JUL-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 245.02 0.00 01-JAN-00:10 3618.95 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 245.02 0.00 01-JAN-00:10 3618.95 04-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 23644.61 0.00 05-JAN-03:10 7112.28 29-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 23644.61 0.00 05-JAN-03:10 7112.28 29-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 31982.18 0.00 01-JAN-03:20 10920.80 25-JUL-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 547.21 0.00 01-JAN-00:10 6226.67 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 547.21 0.00 01-JAN-00:10 6226.67 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 31434.97 0.00 01-JAN-03:20 10920.80 25-JUL-10:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 31434.97 0.00 01-JAN-03:20 10920.80 25-JUL-10:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 35539.38 0.00 01-JAN-02:10 11873.34 29-JUL-16:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 920.02 0.00 01-JAN-00:10 8329.02 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 920.02 0.00 01-JAN-00:10 8329.02 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 34619.36 0.00 01-JAN-02:10 11873.34 29-JUL-16:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 34619.36 0.00 01-JAN-02:10 11873.34 29-JUL-16:10
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 38337.39 0.00 01-JAN-02:10 11888.43 29-JUL-16:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 806.65 0.00 01-JAN-00:10 8211.79 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 806.65 0.00 01-JAN-00:10 8211.79 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 37530.74 0.00 01-JAN-02:10 11888.43 29-JUL-16:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 37530.74 0.00 01-JAN-02:10 11888.43 29-JUL-16:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 38316.27 0.00 01-JAN-02:20 14962.90 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 939.01 0.00 01-JAN-00:10 8284.62 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 939.01 0.00 01-JAN-00:10 8284.62 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 37377.26 0.00 01-JAN-02:20 14962.90 29-JUL-16:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 37377.26 0.00 01-JAN-02:20 14962.90 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 27607.31 0.00 01-JAN-06:00 9053.39 29-JUL-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 553.49 0.00 01-JAN-00:10 5715.95 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 553.49 0.00 01-JAN-00:10 5715.95 04-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 27053.81 0.00 01-JAN-06:00 9053.39 29-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 27053.81 0.00 01-JAN-06:00 9053.39 29-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 30418.82 0.00 01-JAN-06:00 9059.07 14-OCT-14:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 410.01 0.00 01-JAN-00:10 5532.31 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 410.01 0.00 01-JAN-00:10 5532.31 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 30008.80 0.00 01-JAN-06:00 9059.07 14-OCT-14:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 30008.80 0.00 01-JAN-06:00 9059.07 14-OCT-14:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 35739.08 0.00 01-JAN-02:10 14995.64 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 1115.76 0.00 01-JAN-00:10 8403.43 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 1115.76 0.00 01-JAN-00:10 8403.43 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 34623.32 0.00 01-JAN-02:10 14995.64 29-JUL-16:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 34623.32 0.00 01-JAN-02:10 14995.64 29-JUL-16:30
PlantLoopHeatingDemand:Facility 46685.09 -32.9 18-JUL-06:00 14155.87 14-JAN-10:00
PlantLoopHeatingDemand:Plant 46685.09 -32.9 18-JUL-06:00 14155.87 14-JAN-10:00
WaterSystems:PlantLoopHeatingDemand 46685.09 -32.9 18-JUL-06:00 14155.87 14-JAN-10:00
General:WaterSystems:PlantLoopHeatingDemand 46685.09 -32.9 18-JUL-06:00 14155.87 14-JAN-10:00
EnergyTransfer:HVAC 873627.18 0.00 05-JAN-03:20 252565.73 27-JUL-16:20
HeatingCoils:EnergyTransfer 11621.89 0.00 01-JAN-00:10 111560.44 04-FEB-07:00
CoolingCoils:EnergyTransfer 862005.30 0.00 05-JAN-03:20 252565.73 27-JUL-16:20
EnergyTransfer:Plant 46685.09 -32.9 18-JUL-06:00 14155.87 14-JAN-10:00
WaterSystems:EnergyTransfer 46685.09 -32.9 18-JUL-06:00 14155.87 14-JAN-10:00
Domestic Hot Water:WaterSystems:EnergyTransfer 46685.09 -32.9 18-JUL-06:00 14155.87 14-JAN-10:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 1000.659 -2797.31 0.000 0.000 2902.741 3361.146 10464.601 16375.305 0.000 3201.635 1080.440 0.000 -2715.64 0.000 -2080.69 -0.03
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 468.343 -2153.78 0.000 0.000 2894.260 3361.146 10464.601 7000.209 0.000 3004.632 1789.857 0.000 -1107.40 0.000 -2013.03 -0.06
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 876.848 -2814.94 0.000 0.000 2902.191 3361.146 10464.601 16697.047 0.000 3201.536 1017.992 0.000 -2614.98 0.000 -2104.47 -0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 1215.906 -2487.22 0.000 0.000 2905.811 3361.146 10464.601 13106.401 0.000 3202.311 401.379 0.000 -2756.83 0.000 -2034.08 -0.25
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 655.157 -1830.39 0.000 0.000 2898.910 3361.146 10464.601 3581.814 0.000 3007.395 1111.927 0.000 -1152.12 0.000 -1949.52 -0.03
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 1014.048 -2486.68 0.000 0.000 2905.642 3361.146 10464.601 13371.391 0.000 3201.593 194.397 0.000 -2595.00 0.000 -2057.74 -0.05
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 536.311 -2925.54 0.000 0.000 2894.043 3361.146 10464.601 15961.664 0.000 2273.478 4133.550 0.000 -2946.25 0.000 -1548.64 -0.24
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 146.504 -2305.91 0.000 0.000 2884.895 3361.146 10464.601 6817.455 0.000 2079.362 4594.866 0.000 -1194.88 0.000 -1464.47 -0.27
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 459.301 -2951.30 0.000 0.000 2893.461 3361.146 10464.601 16246.430 0.000 2273.407 4131.100 0.000 -2826.11 0.000 -1564.01 -0.14
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 686.351 -2610.57 0.000 0.000 2896.753 3361.146 10464.601 12790.023 0.000 2273.754 3394.087 0.000 -2999.39 0.000 -1519.49 -0.08
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 245.013 -1969.07 0.000 0.000 2888.578 3361.146 10464.601 3495.626 0.000 2079.857 3792.595 0.000 -1253.42 0.000 -1429.33 -0.02
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 547.204 -2617.85 0.000 0.000 2896.413 3361.146 10464.601 13008.506 0.000 2273.453 3235.494 0.000 -2812.63 0.000 -1539.04 -0.09
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 920.010 -2883.03 0.000 0.000 2901.005 3361.146 10464.601 12736.929 0.000 3169.005 6013.532 0.000 -2835.20 0.000 -2111.49 -0.12
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 806.632 -3125.49 0.000 0.000 2898.660 3361.146 10464.601 15968.788 0.000 3168.977 5829.295 0.000 -2822.52 0.000 -2144.67 -0.22
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 938.992 -3112.67 0.000 0.000 2899.259 3361.146 10464.601 15691.642 0.000 3169.130 5909.752 0.000 -2936.20 0.000 -2121.29 -0.25
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 553.485 -2252.98 0.000 0.000 2893.876 3361.146 10464.601 3405.113 0.000 2976.682 6671.877 0.000 -1262.79 0.000 -2010.17 -0.06
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 410.009 -2499.06 0.000 0.000 2890.902 3361.146 10464.601 6700.489 0.000 2976.264 6450.873 0.000 -1192.13 0.000 -2053.38 -0.17
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 1115.741 -2883.33 0.000 0.000 2901.485 3361.146 10464.601 12516.462 0.000 3169.744 6186.863 0.000 -3006.11 0.000 -2086.82 -0.02
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 122869.539 0.000 0.000 0.000 0.000 -8763.76 -114105.78
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 25313.575 160010.529 0.000 0.000 0.000 -185324.10 -8.09
Total Facility 0.000 0.000 12596.513 -46707.14 0.000 0.000 52148.886 60500.637 188362.826 205471.293 0.000 198885.329 225950.405 0.000 -41029.59 0.000 -227920.18 -114115.97


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29-JUL-16:19 0.00 0.00 0.00 -1.2 0.00 0.00 140.35 526.52 1371.36 8590.82 0.00 1952.15 1271.10 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 07-NOV-13:00 0.00 0.00 0.00 -0.7 0.00 0.00 115.09 141.03 1084.63 4750.60 0.00 641.40 1490.77 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 13-OCT-10:35 0.00 0.00 0.00 -0.9 0.00 0.00 115.09 141.03 1089.80 9611.40 0.00 1003.98 0.00 0.00 0.00 0.00 0.00 -634.6
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 29-JUL-16:34 0.00 0.00 0.00 -1.1 0.00 0.00 140.35 526.52 1371.36 8639.02 0.00 1914.27 1175.65 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUL-18:10 0.00 0.00 0.00 -0.6 0.00 0.00 426.76 987.22 1748.06 948.89 0.00 1646.85 1891.96 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 25-JUL-09:03 0.00 0.00 0.00 -0.9 0.00 0.00 115.09 141.03 1096.02 8666.15 0.00 1365.16 0.00 0.00 0.00 0.00 0.00 -118.7
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 30-SEP-15:30 0.00 0.00 0.00 -1.1 0.00 0.00 115.08 244.45 1168.29 9695.56 0.00 889.25 1181.28 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 07-NOV-15:20 0.00 0.00 0.00 -0.7 0.00 0.00 114.96 244.45 1147.45 3523.31 0.00 452.83 2634.67 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 30-AUG-10:03 0.00 0.00 0.00 -0.9 0.00 0.00 115.09 141.03 1089.80 7971.93 0.00 868.80 825.04 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 29-JUL-16:34 0.00 0.00 0.00 -1.1 0.00 0.00 140.35 526.52 1371.36 8524.47 0.00 1357.79 1093.96 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29-JUL-18:10 0.00 0.00 0.00 -0.6 0.00 0.00 426.76 987.22 1748.06 967.45 0.00 1089.21 1893.70 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 25-JUL-09:03 0.00 0.00 0.00 -0.9 0.00 0.00 115.09 141.03 1096.02 8595.12 0.00 1019.94 0.00 0.00 0.00 0.00 0.00 -46.1
LIVING_UNIT3_BACKROW_TOPFLOOR 29-JUL-16:10 0.00 0.00 0.00 -1.0 0.00 0.00 140.35 526.52 1371.36 4283.12 0.00 1983.78 3569.03 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 29-JUL-16:10 0.00 0.00 0.00 -1.0 0.00 0.00 140.35 526.52 1371.36 4189.83 0.00 1983.79 3678.77 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 29-JUL-16:34 0.00 0.00 0.00 -1.2 0.00 0.00 140.35 526.52 1371.36 8216.90 0.00 1907.91 2800.14 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 29-JUL-18:15 0.00 0.00 0.00 -0.8 0.00 0.00 426.76 987.22 1748.06 936.78 0.00 1640.53 3314.52 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 14-OCT-13:00 0.00 0.00 0.00 -0.8 0.00 0.00 115.09 141.03 1109.73 4004.54 0.00 1221.70 2465.81 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 29-JUL-16:34 0.00 0.00 0.00 -1.2 0.00 0.00 140.35 526.52 1371.36 8372.64 0.00 1907.90 2677.16 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-JUL-16:19 0.00 0.00 0.00 -16.2 0.00 0.00 2525.33 9477.32 24684.52 86540.31 0.00 70865.29 73552.95 0.00 0.00 0.00 -73094.8 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 04-FEB-06:00 0.00 0.00 8284.17 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -3853.3 0.00 -4047.4 -2521.9
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 04-FEB-06:00 0.00 0.00 5624.90 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -1555.7 0.00 -3756.8 -2450.9
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 04-FEB-06:00 0.00 0.00 8225.47 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -3779.2 0.00 -4046.7 -2538.0
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 04-FEB-06:00 0.00 0.00 8372.60 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -3898.7 0.00 -4047.4 -2565.0
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 04-FEB-06:00 0.00 0.00 5756.50 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -1604.2 0.00 -3756.8 -2533.9
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 04-FEB-06:00 0.00 0.00 8245.04 0.00 0.00 0.00 526.62 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -3823.4 0.00 -4041.2 -2519.3
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 04-FEB-06:00 0.00 0.00 6162.31 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -4026.7 0.00 -2682.9 -1591.1
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 04-FEB-06:00 0.00 0.00 3430.03 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -1620.3 0.00 -2392.0 -1556.2
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 04-FEB-06:00 0.00 0.00 6106.04 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -3924.2 0.00 -2682.9 -1637.4
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 04-FEB-06:00 0.00 0.00 6288.10 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -4088.2 0.00 -2682.9 -1655.4
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 04-FEB-07:10 0.00 0.00 3618.91 0.00 0.00 0.00 464.72 470.11 1225.98 0.00 0.00 0.00 0.00 0.00 -1599.3 0.00 -2361.7 -1818.8
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 04-FEB-06:00 0.00 0.00 6226.55 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -3986.2 0.00 -2682.9 -1695.9
LIVING_UNIT3_BACKROW_TOPFLOOR 04-FEB-06:00 0.00 0.00 8328.93 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -3998.7 0.00 -4056.7 -2412.0
LIVING_UNIT3_FRONTROW_TOPFLOOR 04-FEB-06:00 0.00 0.00 8211.71 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -3927.9 0.00 -4056.7 -2365.5
LIVING_UNIT1_FRONTROW_TOPFLOOR 04-FEB-06:00 0.00 0.00 8284.51 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -4042.0 0.00 -4056.7 -2324.2
LIVING_UNIT2_BACKROW_TOPFLOOR 04-FEB-07:10 0.00 0.00 5715.95 0.00 0.00 0.00 464.72 470.11 1225.98 0.00 0.00 0.00 0.00 0.00 -1608.1 0.00 -3730.9 -2537.7
LIVING_UNIT2_FRONTROW_TOPFLOOR 04-FEB-06:00 0.00 0.00 5532.27 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -1618.9 0.00 -3765.4 -2286.4
LIVING_UNIT1_BACKROW_TOPFLOOR 04-FEB-06:00 0.00 0.00 8403.32 0.00 0.00 0.00 526.24 526.52 1085.68 0.00 0.00 0.00 0.00 0.00 -4112.4 0.00 -4056.7 -2372.6
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 04-FEB-06:00 0.00 0.00 120808.04 0.00 0.00 0.00 9472.74 9477.32 19542.30 0.00 0.00 4443.33 0.00 0.00 -57240.6 0.00 -104205.9 -2297.2



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 558.8145 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 558.8145 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 268.1850 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 268.1850 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 424.6071 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 424.6071 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 567.3762 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 567.3762 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 285.8031 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 285.8031 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 431.4651 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 431.4651 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 531.9983 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 531.9983 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 253.4367 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 253.4367 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 405.9958 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 405.9958 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 541.2888 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 541.2888 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 269.9586 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 269.9586 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 412.6466 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 412.6466 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 602.0980 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 602.0980 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 323.4943 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 323.4943 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 433.8905 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 433.8905 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 610.2601 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 610.2601 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 336.4743 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 336.4743 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 435.9347 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 435.9347 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 558.8145 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 558.8145 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 268.1850 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 268.1850 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 424.6071 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 424.6071 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 567.3762 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 567.3762 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 285.8031 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 285.8031 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 431.4651 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 431.4651 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 531.9983 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 531.9983 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 253.4367 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 253.4367 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 405.9958 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 405.9958 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 541.2888 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 541.2888 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 269.9586 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 269.9586 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 412.6466 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 412.6466 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 602.0980 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 602.0980 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 323.4943 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 323.4943 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 433.8905 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 433.8905 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 610.2601 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 610.2601 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 336.4743 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 336.4743 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 435.9347 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 435.9347 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 558.8145 558.8145 558.8145 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 268.1850 268.1850 268.1850 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 424.6071 424.6071 424.6071 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 567.3762 567.3762 567.3762 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 285.8031 285.8031 285.8031 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 431.4651 431.4651 431.4651 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 531.9983 531.9983 531.9983 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 253.4367 253.4367 253.4367 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 405.9958 405.9958 405.9958 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 541.2888 541.2888 541.2888 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 269.9586 269.9586 269.9586 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 412.6466 412.6466 412.6466 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 435.9347 435.9347 435.9347 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 433.8905 433.8905 433.8905 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 602.0980 602.0980 602.0980 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 336.4743 336.4743 336.4743 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 323.4943 323.4943 323.4943 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 610.2601 610.2601 610.2601 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 558.8145 558.8145 558.8145 558.8145 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 268.1850 268.1850 268.1850 268.1850 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 424.6071 424.6071 424.6071 424.6071 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 567.3762 567.3762 567.3762 567.3762 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 285.8031 285.8031 285.8031 285.8031 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 431.4651 431.4651 431.4651 431.4651 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 531.9983 531.9983 531.9983 531.9983 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 253.4367 253.4367 253.4367 253.4367 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 405.9958 405.9958 405.9958 405.9958 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 541.2888 541.2888 541.2888 541.2888 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 269.9586 269.9586 269.9586 269.9586 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 412.6466 412.6466 412.6466 412.6466 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 602.0980 602.0980 602.0980 602.0980 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 323.4943 323.4943 323.4943 323.4943 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 433.8905 433.8905 433.8905 433.8905 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 610.2601 610.2601 610.2601 610.2601 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 336.4743 336.4743 336.4743 336.4743 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 435.9347 435.9347 435.9347 435.9347 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 558.8145 558.8145 558.8145 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 268.1850 268.1850 268.1850 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 424.6071 424.6071 424.6071 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 567.3762 567.3762 567.3762 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 285.8031 285.8031 285.8031 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 431.4651 431.4651 431.4651 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 531.9983 531.9983 531.9983 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 253.4367 253.4367 253.4367 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 405.9958 405.9958 405.9958 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 541.2888 541.2888 541.2888 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 269.9586 269.9586 269.9586 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 412.6466 412.6466 412.6466 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 435.9347 435.9347 435.9347 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 433.8905 433.8905 433.8905 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 602.0980 602.0980 602.0980 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 336.4743 336.4743 336.4743 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 323.4943 323.4943 323.4943 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 610.2601 610.2601 610.2601 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 558.8145 558.8145 558.8145 558.8145 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 268.1850 268.1850 268.1850 268.1850 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 424.6071 424.6071 424.6071 424.6071 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 567.3762 567.3762 567.3762 567.3762 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 285.8031 285.8031 285.8031 285.8031 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 431.4651 431.4651 431.4651 431.4651 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 531.9983 531.9983 531.9983 531.9983 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 253.4367 253.4367 253.4367 253.4367 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 405.9958 405.9958 405.9958 405.9958 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 541.2888 541.2888 541.2888 541.2888 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 269.9586 269.9586 269.9586 269.9586 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 412.6466 412.6466 412.6466 412.6466 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 602.0980 602.0980 602.0980 602.0980 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 323.4943 323.4943 323.4943 323.4943 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 433.8905 433.8905 433.8905 433.8905 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 610.2601 610.2601 610.2601 610.2601 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 336.4743 336.4743 336.4743 336.4743 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 435.9347 435.9347 435.9347 435.9347 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Sec1.1A-General Information

Data
Weather File ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020
Total gross floor area [ft2] 39005.22
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 39005.22 21609.96 17395.26  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 20.17
Number of hours not met 20.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 3403.77 32696.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 55876.40 18225.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 17719.17 5771.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 6034.31 1377.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 3088.82 985.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1577.30 427.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_dryer 12502.11 3196.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_range 9058.39 3721.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_mels 46926.68 7929.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 3113.66 526.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 5068.29 578.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 8880.99 2707.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 35436.63 54379.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 753639.17
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 301503.54 753639.17


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.45
Space Heating 0.09
Space Cooling 1.43
Fans (All) 0.36
Service Water Heating 0.91
Receptacle Equipment 2.26
Miscellaneous (All) 5.66
Subtotal 5.66


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 8.03
Space Heating 1.54
Space Cooling 25.32
Fans (All) 6.32
Service Water Heating 16.05
Receptacle Equipment 40.01
Miscellaneous 2.73


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DISHWASHER_FLOW_SCH 3134. 8760.
CLOTHESWASHER_FLOW_SCH 3692. 8760.
DISHWASHER_EQUIP_SCH 3134. 8760.
CLOTHESWASHER_EQUIP_SCH 3692. 8760.
CLOTHESDRYER 3911. 8760.
SHADING_2012IECC 0. 0.
SHADING_2012IECC_HERS 7007. 8760.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupiedHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 16:06:20

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupiedHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 428.350 20.452 150.500 26.699 26.699
February 450.317 23.769 99.167 29.278 29.278
March 581.806 29.695 85.667 34.739 34.739
April 675.792 38.323 9.056 38.516 38.516
May 743.000 52.705 0.000 52.705 52.705
June 720.000 57.491 0.000 57.491 57.491
July 744.000 62.330 0.000 62.330 62.330
August 744.000 61.860 0.000 61.860 61.860
September 720.000 58.619 0.000 58.619 58.619
October 744.000 53.652 0.000 53.652 53.652
November 614.125 37.720 36.583 39.746 39.746
December 481.122 24.758 101.667 30.804 30.804
           
Annual Sum or Average 7646.511 521.374 482.639 546.439 546.439
Minimum of Months 428.350 20.452 0.000 26.699 26.699
Maximum of Months 744.000 62.330 150.500 62.330 62.330



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 492.533 17.199 94.264 18.854 18.854
February 488.033 18.790 58.917 20.598 20.598
March 610.597 22.139 66.556 23.773 23.773
April 694.042 28.078 3.667 28.095 28.095
May 744.000 39.079 0.000 39.079 39.079
June 720.000 43.435 0.000 43.435 43.435
July 744.000 46.225 0.000 46.225 46.225
August 744.000 46.538 0.000 46.538 46.538
September 720.000 45.111 0.000 45.111 45.111
October 744.000 42.394 0.000 42.394 42.394
November 645.444 30.928 28.167 31.553 31.553
December 533.461 20.351 69.083 22.354 22.354
           
Annual Sum or Average 7880.111 400.268 320.653 408.009 408.009
Minimum of Months 488.033 17.199 0.000 18.854 18.854
Maximum of Months 744.000 46.538 94.264 46.538 46.538



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 453.317 20.460 136.000 24.792 24.792
February 464.853 23.146 89.083 27.000 27.000
March 598.500 28.318 64.833 31.259 31.259
April 681.778 37.676 8.167 37.827 37.827
May 742.667 51.941 0.000 51.941 51.941
June 720.000 57.996 0.000 57.996 57.996
July 744.000 62.061 0.000 62.061 62.061
August 744.000 60.481 0.000 60.481 60.481
September 720.000 58.455 0.000 58.455 58.455
October 744.000 53.048 0.000 53.048 53.048
November 623.475 37.059 33.917 38.438 38.438
December 491.467 22.992 96.500 27.401 27.401
           
Annual Sum or Average 7728.056 513.633 428.500 530.699 530.699
Minimum of Months 453.317 20.460 0.000 24.792 24.792
Maximum of Months 744.000 62.061 136.000 62.061 62.061



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 362.500 12.570 188.528 20.669 20.669
February 419.028 17.612 115.875 24.213 24.213
March 561.528 25.381 97.083 31.367 31.367
April 673.625 35.826 9.167 36.023 36.023
May 742.667 52.895 0.000 52.895 52.895
June 720.000 58.498 0.000 58.498 58.498
July 744.000 62.985 0.000 62.985 62.985
August 744.000 60.953 0.000 60.953 60.953
September 720.000 55.311 0.000 55.311 55.311
October 744.000 47.380 0.000 47.380 47.380
November 596.069 30.515 42.333 32.864 32.864
December 425.903 17.133 127.417 24.734 24.734
           
Annual Sum or Average 7453.319 477.059 580.403 507.892 507.892
Minimum of Months 362.500 12.570 0.000 20.669 20.669
Maximum of Months 744.000 62.985 188.528 62.985 62.985



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 391.722 9.145 140.222 11.855 11.855
February 446.125 12.519 81.875 15.090 15.090
March 572.917 17.777 85.861 20.062 20.062
April 692.958 25.614 3.667 25.632 25.632
May 744.000 39.460 0.000 39.460 39.460
June 720.000 44.665 0.000 44.665 44.665
July 744.000 47.143 0.000 47.143 47.143
August 744.000 45.887 0.000 45.887 45.887
September 720.000 42.132 0.000 42.132 42.132
October 744.000 36.378 0.000 36.378 36.378
November 626.958 23.717 34.083 24.541 24.541
December 450.458 12.563 104.167 15.636 15.636
           
Annual Sum or Average 7597.139 357.001 449.875 368.482 368.482
Minimum of Months 391.722 9.145 0.000 11.855 11.855
Maximum of Months 744.000 47.143 140.222 47.143 47.143



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 384.278 12.165 162.167 17.330 17.330
February 448.983 16.815 105.000 21.364 21.364
March 570.272 23.773 71.083 26.973 26.973
April 681.667 35.221 8.167 35.375 35.375
May 742.667 52.032 0.000 52.032 52.032
June 720.000 58.806 0.000 58.806 58.806
July 744.000 62.565 0.000 62.565 62.565
August 744.000 59.571 0.000 59.571 59.571
September 720.000 55.321 0.000 55.321 55.321
October 744.000 47.076 0.000 47.076 47.076
November 611.222 29.929 36.583 31.452 31.452
December 425.297 15.197 122.944 20.633 20.633
           
Annual Sum or Average 7536.386 468.471 505.944 488.496 488.496
Minimum of Months 384.278 12.165 0.000 17.330 17.330
Maximum of Months 744.000 62.565 162.167 62.565 62.565



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 493.028 22.587 97.667 26.153 26.153
February 497.275 25.392 59.950 28.820 28.820
March 620.167 31.641 66.333 34.730 34.730
April 696.333 39.890 3.667 39.931 39.931
May 744.000 51.922 0.000 51.922 51.922
June 720.000 55.950 0.000 55.950 55.950
July 744.000 61.026 0.000 61.026 61.026
August 744.000 59.992 0.000 59.992 59.992
September 720.000 57.331 0.000 57.331 57.331
October 744.000 53.456 0.000 53.456 53.456
November 647.500 38.781 27.333 39.971 39.971
December 542.461 26.928 71.750 30.876 30.876
           
Annual Sum or Average 7912.764 524.895 326.700 540.156 540.156
Minimum of Months 493.028 22.587 0.000 26.153 26.153
Maximum of Months 744.000 61.026 97.667 61.026 61.026



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 569.267 20.242 40.833 20.705 20.705
February 551.669 21.097 33.333 21.909 21.909
March 646.742 24.586 30.556 25.189 25.189
April 706.333 29.930 0.000 29.930 29.930
May 744.000 38.522 0.000 38.522 38.522
June 720.000 42.081 0.000 42.081 42.081
July 744.000 45.092 0.000 45.092 45.092
August 744.000 44.893 0.000 44.893 44.893
September 720.000 44.050 0.000 44.050 44.050
October 744.000 42.333 0.000 42.333 42.333
November 676.889 32.356 14.556 32.550 32.550
December 611.597 23.319 43.167 24.210 24.210
           
Annual Sum or Average 8178.498 408.502 162.444 411.465 411.465
Minimum of Months 551.669 20.242 0.000 20.705 20.705
Maximum of Months 744.000 45.092 43.167 45.092 45.092



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 515.947 22.845 84.389 25.295 25.295
February 512.919 24.893 52.889 27.265 27.265
March 642.528 30.461 47.333 32.182 32.182
April 702.611 39.206 3.500 39.244 39.244
May 744.000 51.123 0.000 51.123 51.123
June 720.000 56.414 0.000 56.414 56.414
July 744.000 60.776 0.000 60.776 60.776
August 744.000 58.683 0.000 58.683 58.683
September 720.000 57.175 0.000 57.175 57.175
October 744.000 52.849 0.000 52.849 52.849
November 652.828 38.157 23.333 38.953 38.953
December 551.994 25.284 66.056 28.157 28.157
           
Annual Sum or Average 7994.828 517.866 277.500 528.115 528.115
Minimum of Months 512.919 22.845 0.000 25.295 25.295
Maximum of Months 744.000 60.776 84.389 60.776 60.776



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 430.431 14.417 130.167 19.354 19.354
February 464.431 19.262 75.250 23.535 23.535
March 601.750 27.454 78.667 31.312 31.312
April 695.708 37.559 3.667 37.602 37.602
May 744.000 52.133 0.000 52.133 52.133
June 720.000 56.919 0.000 56.919 56.919
July 744.000 61.675 0.000 61.675 61.675
August 744.000 59.166 0.000 59.166 59.166
September 720.000 54.214 0.000 54.214 54.214
October 744.000 47.488 0.000 47.488 47.488
November 630.167 31.752 32.000 33.203 33.203
December 490.772 19.173 93.833 24.393 24.393
           
Annual Sum or Average 7729.258 481.211 413.583 500.994 500.994
Minimum of Months 430.431 14.417 0.000 19.354 19.354
Maximum of Months 744.000 61.675 130.167 61.675 61.675



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 474.500 11.701 76.208 12.761 12.761
February 507.944 14.790 50.367 16.088 16.088
March 613.250 20.254 46.889 21.237 21.237
April 705.792 27.676 0.000 27.676 27.676
May 744.000 38.910 0.000 38.910 38.910
June 720.000 43.250 0.000 43.250 43.250
July 744.000 45.968 0.000 45.968 45.968
August 744.000 44.305 0.000 44.305 44.305
September 720.000 41.198 0.000 41.198 41.198
October 744.000 36.616 0.000 36.616 36.616
November 663.083 25.396 19.167 25.696 25.696
December 542.611 15.274 70.222 16.869 16.869
           
Annual Sum or Average 7923.181 365.337 262.853 370.574 370.574
Minimum of Months 474.500 11.701 0.000 12.761 12.761
Maximum of Months 744.000 45.968 76.208 45.968 45.968



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 456.683 14.294 98.583 17.297 17.297
February 490.758 18.703 67.583 21.588 21.588
March 616.292 25.934 50.667 27.841 27.841
April 702.444 36.925 3.500 36.963 36.963
May 744.000 51.235 0.000 51.235 51.235
June 720.000 57.193 0.000 57.193 57.193
July 744.000 61.274 0.000 61.274 61.274
August 744.000 57.847 0.000 57.847 57.847
September 720.000 54.214 0.000 54.214 54.214
October 744.000 47.166 0.000 47.166 47.166
November 640.917 31.263 25.000 32.162 32.162
December 493.264 17.334 90.333 20.978 20.978
           
Annual Sum or Average 7816.358 473.382 335.667 485.759 485.759
Minimum of Months 456.683 14.294 0.000 17.297 17.297
Maximum of Months 744.000 61.274 98.583 61.274 61.274



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 448.225 22.289 130.889 28.454 28.454
February 466.222 25.756 82.667 31.132 31.132
March 596.778 32.767 80.667 37.779 37.779
April 688.667 42.730 7.333 42.871 42.871
May 744.000 58.293 0.000 58.293 58.293
June 720.000 63.723 0.000 63.723 63.723
July 744.000 69.192 0.000 69.192 69.192
August 744.000 67.664 0.000 67.664 67.664
September 720.000 64.159 0.000 64.159 64.159
October 744.000 58.369 0.000 58.369 58.369
November 624.375 41.090 33.167 43.070 43.070
December 500.608 27.026 88.833 33.116 33.116
           
Annual Sum or Average 7740.875 573.058 423.556 597.821 597.821
Minimum of Months 448.225 22.289 0.000 28.454 28.454
Maximum of Months 744.000 69.192 130.889 69.192 69.192



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 521.006 19.827 81.722 21.517 21.517
February 505.425 21.499 49.833 23.377 23.377
March 620.639 25.921 56.931 27.566 27.566
April 698.208 33.085 1.167 33.087 33.087
May 744.000 45.160 0.000 45.160 45.160
June 720.000 50.042 0.000 50.042 50.042
July 744.000 53.492 0.000 53.492 53.492
August 744.000 52.788 0.000 52.788 52.788
September 720.000 51.154 0.000 51.154 51.154
October 744.000 47.678 0.000 47.678 47.678
November 655.083 34.909 23.375 35.522 35.522
December 561.736 23.392 61.583 25.532 25.532
           
Annual Sum or Average 7978.097 458.947 274.611 466.915 466.915
Minimum of Months 505.425 19.827 0.000 21.517 21.517
Maximum of Months 744.000 53.492 81.722 53.492 53.492



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 472.900 22.209 114.333 26.200 26.200
February 479.814 24.988 75.806 28.538 28.538
March 612.822 31.155 60.333 33.849 33.849
April 695.625 41.735 6.500 41.841 41.841
May 744.000 56.967 0.000 56.967 56.967
June 720.000 63.503 0.000 63.503 63.503
July 744.000 68.232 0.000 68.232 68.232
August 744.000 65.705 0.000 65.705 65.705
September 720.000 63.420 0.000 63.420 63.420
October 744.000 57.342 0.000 57.342 57.342
November 634.806 40.166 30.333 41.436 41.436
December 509.861 25.158 82.167 29.339 29.339
           
Annual Sum or Average 7821.828 560.579 369.472 576.370 576.370
Minimum of Months 472.900 22.209 0.000 26.200 26.200
Maximum of Months 744.000 68.232 114.333 68.232 68.232



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 396.444 15.780 161.556 23.563 23.563
February 440.500 21.086 99.500 27.421 27.421
March 584.639 30.036 88.333 35.728 35.728
April 688.125 41.368 7.333 41.511 41.511
May 744.000 58.557 0.000 58.557 58.557
June 720.000 64.431 0.000 64.431 64.431
July 744.000 69.729 0.000 69.729 69.729
August 744.000 67.255 0.000 67.255 67.255
September 720.000 62.259 0.000 62.259 62.259
October 744.000 54.008 0.000 54.008 54.008
November 610.292 35.363 37.833 37.640 37.640
December 456.678 20.622 108.125 28.094 28.094
           
Annual Sum or Average 7592.678 540.494 502.681 570.197 570.197
Minimum of Months 396.444 15.780 0.000 23.563 23.563
Maximum of Months 744.000 69.729 161.556 69.729 69.729



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 452.417 12.879 112.250 15.493 15.493
February 474.278 16.645 67.000 19.179 19.179
March 599.500 23.080 68.167 25.185 25.185
April 697.542 31.762 1.000 31.764 31.764
May 744.000 45.532 0.000 45.532 45.532
June 720.000 50.881 0.000 50.881 50.881
July 744.000 54.173 0.000 54.173 54.173
August 744.000 52.524 0.000 52.524 52.524
September 720.000 49.407 0.000 49.407 49.407
October 744.000 43.420 0.000 43.420 43.420
November 640.250 29.070 28.167 29.861 29.861
December 505.250 16.633 86.861 19.708 19.708
           
Annual Sum or Average 7785.236 426.006 363.444 437.126 437.126
Minimum of Months 452.417 12.879 0.000 15.493 15.493
Maximum of Months 744.000 54.173 112.250 54.173 54.173



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 425.267 15.373 129.389 19.949 19.949
February 463.761 20.267 91.833 24.378 24.378
March 595.700 28.298 65.083 31.165 31.165
April 695.458 40.415 6.667 40.522 40.522
May 744.000 57.120 0.000 57.120 57.120
June 720.000 64.033 0.000 64.033 64.033
July 744.000 68.607 0.000 68.607 68.607
August 744.000 65.247 0.000 65.247 65.247
September 720.000 61.611 0.000 61.611 61.611
October 744.000 53.246 0.000 53.246 53.246
November 624.222 34.572 32.583 35.964 35.964
December 459.858 18.643 105.500 23.643 23.643
           
Annual Sum or Average 7680.267 527.433 431.056 545.485 545.485
Minimum of Months 425.267 15.373 0.000 19.949 19.949
Maximum of Months 744.000 68.607 129.389 68.607 68.607



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 306.33 0.00 0.00
February 299.09 0.00 0.00
March 247.33 0.00 0.00
April 9.79 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 102.64 0.00 0.00
December 296.46 0.00 0.00
       
Annual Sum or Average 104.39 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 306.33 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 126.85 0.00 0.00
February 153.49 0.00 0.00
March 125.32 0.00 0.00
April 1.34 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 49.49 0.00 0.00
December 153.56 0.00 0.00
       
Annual Sum or Average 50.41 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 153.56 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 279.11 0.00 0.00
February 274.88 0.00 0.00
March 189.47 0.00 0.00
April 10.05 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 91.79 0.00 0.00
December 284.06 0.00 0.00
       
Annual Sum or Average 93.38 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 284.06 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 391.85 0.00 0.00
February 353.54 0.00 0.00
March 289.59 0.00 0.00
April 9.89 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 117.41 0.00 0.00
December 367.78 0.00 0.00
       
Annual Sum or Average 126.70 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 391.85 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 195.28 0.00 0.00
February 205.14 0.00 0.00
March 164.64 0.00 0.00
April 1.35 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 61.36 0.00 0.00
December 221.42 0.00 0.00
       
Annual Sum or Average 70.27 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 221.42 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 327.58 0.00 0.00
February 319.45 0.00 0.00
March 202.97 0.00 0.00
April 10.09 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 99.80 0.00 0.00
December 344.75 0.00 0.00
       
Annual Sum or Average 107.88 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 344.75 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 151.97 0.00 0.00
February 161.70 0.00 0.00
March 131.63 0.00 0.00
April 1.81 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 52.38 0.00 0.00
December 168.26 0.00 0.00
       
Annual Sum or Average 55.24 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 168.26 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 28.59 0.00 0.00
February 55.60 0.00 0.00
March 37.28 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 12.35 0.00 0.00
December 55.14 0.00 0.00
       
Annual Sum or Average 15.56 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 55.60 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 136.24 0.00 0.00
February 146.04 0.00 0.00
March 95.70 0.00 0.00
April 2.14 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 45.73 0.00 0.00
December 159.73 0.00 0.00
       
Annual Sum or Average 48.40 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 159.73 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 207.41 0.00 0.00
February 198.80 0.00 0.00
March 162.11 0.00 0.00
April 1.84 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 63.00 0.00 0.00
December 219.31 0.00 0.00
       
Annual Sum or Average 70.59 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 219.31 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 61.75 0.00 0.00
February 83.72 0.00 0.00
March 57.30 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 18.08 0.00 0.00
December 92.91 0.00 0.00
       
Annual Sum or Average 25.91 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 92.91 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 164.54 0.00 0.00
February 175.07 0.00 0.00
March 104.55 0.00 0.00
April 2.15 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 50.89 0.00 0.00
December 199.67 0.00 0.00
       
Annual Sum or Average 57.60 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 199.67 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 285.70 0.00 0.00
February 275.85 0.00 0.00
March 232.29 0.00 0.00
April 6.73 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 94.80 0.00 0.00
December 282.25 0.00 0.00
       
Annual Sum or Average 97.47 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 285.70 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 109.05 0.00 0.00
February 134.19 0.00 0.00
March 106.15 0.00 0.00
April 0.09 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 40.84 0.00 0.00
December 138.14 0.00 0.00
       
Annual Sum or Average 43.67 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 138.14 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 255.50 0.00 0.00
February 251.66 0.00 0.00
March 172.48 0.00 0.00
April 7.01 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 83.98 0.00 0.00
December 267.66 0.00 0.00
       
Annual Sum or Average 85.87 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 267.66 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 356.99 0.00 0.00
February 321.69 0.00 0.00
March 261.09 0.00 0.00
April 6.81 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 107.93 0.00 0.00
December 342.71 0.00 0.00
       
Annual Sum or Average 115.71 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 356.99 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 162.77 0.00 0.00
February 174.71 0.00 0.00
March 131.06 0.00 0.00
April 0.10 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 50.84 0.00 0.00
December 191.49 0.00 0.00
       
Annual Sum or Average 58.81 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 191.49 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 292.25 0.00 0.00
February 290.69 0.00 0.00
March 183.09 0.00 0.00
April 7.05 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 91.85 0.00 0.00
December 319.32 0.00 0.00
       
Annual Sum or Average 97.92 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 319.32 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.22
February 0.00 0.00 0.29
March 0.00 0.00 0.33
April 0.00 0.00 0.43
May 0.00 0.00 0.58
June 0.00 0.00 0.66
July 0.00 0.00 0.69
August 0.00 0.00 0.69
September 0.00 0.00 0.67
October 0.00 0.00 0.59
November 0.00 0.00 0.43
December 0.00 0.00 0.27
       
Annual Sum or Average 0.00 0.00 0.49
Minimum of Months 0.00 0.00 0.22
Maximum of Months 0.00 0.00 0.69



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.20
February 0.00 0.00 0.24
March 0.00 0.00 0.25
April 0.00 0.00 0.33
May 0.00 0.00 0.46
June 0.00 0.00 0.53
July 0.00 0.00 0.54
August 0.00 0.00 0.55
September 0.00 0.00 0.55
October 0.00 0.00 0.50
November 0.00 0.00 0.38
December 0.00 0.00 0.24
       
Annual Sum or Average 0.00 0.00 0.40
Minimum of Months 0.00 0.00 0.20
Maximum of Months 0.00 0.00 0.55



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.23
February 0.00 0.00 0.28
March 0.00 0.00 0.32
April 0.00 0.00 0.43
May 0.00 0.00 0.59
June 0.00 0.00 0.68
July 0.00 0.00 0.70
August 0.00 0.00 0.69
September 0.00 0.00 0.69
October 0.00 0.00 0.60
November 0.00 0.00 0.44
December 0.00 0.00 0.26
       
Annual Sum or Average 0.00 0.00 0.49
Minimum of Months 0.00 0.00 0.23
Maximum of Months 0.00 0.00 0.70



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.14
February 0.00 0.00 0.21
March 0.00 0.00 0.28
April 0.00 0.00 0.40
May 0.00 0.00 0.58
June 0.00 0.00 0.67
July 0.00 0.00 0.69
August 0.00 0.00 0.68
September 0.00 0.00 0.63
October 0.00 0.00 0.52
November 0.00 0.00 0.35
December 0.00 0.00 0.19
       
Annual Sum or Average 0.00 0.00 0.45
Minimum of Months 0.00 0.00 0.14
Maximum of Months 0.00 0.00 0.69



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.10
February 0.00 0.00 0.16
March 0.00 0.00 0.20
April 0.00 0.00 0.30
May 0.00 0.00 0.46
June 0.00 0.00 0.54
July 0.00 0.00 0.55
August 0.00 0.00 0.54
September 0.00 0.00 0.51
October 0.00 0.00 0.42
November 0.00 0.00 0.28
December 0.00 0.00 0.14
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.10
Maximum of Months 0.00 0.00 0.55



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.13
February 0.00 0.00 0.20
March 0.00 0.00 0.27
April 0.00 0.00 0.40
May 0.00 0.00 0.59
June 0.00 0.00 0.69
July 0.00 0.00 0.71
August 0.00 0.00 0.68
September 0.00 0.00 0.65
October 0.00 0.00 0.53
November 0.00 0.00 0.35
December 0.00 0.00 0.17
       
Annual Sum or Average 0.00 0.00 0.45
Minimum of Months 0.00 0.00 0.13
Maximum of Months 0.00 0.00 0.71



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.25
February 0.00 0.00 0.30
March 0.00 0.00 0.34
April 0.00 0.00 0.45
May 0.00 0.00 0.57
June 0.00 0.00 0.63
July 0.00 0.00 0.66
August 0.00 0.00 0.66
September 0.00 0.00 0.65
October 0.00 0.00 0.58
November 0.00 0.00 0.44
December 0.00 0.00 0.30
       
Annual Sum or Average 0.00 0.00 0.49
Minimum of Months 0.00 0.00 0.25
Maximum of Months 0.00 0.00 0.66



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.23
February 0.00 0.00 0.26
March 0.00 0.00 0.28
April 0.00 0.00 0.35
May 0.00 0.00 0.44
June 0.00 0.00 0.50
July 0.00 0.00 0.52
August 0.00 0.00 0.52
September 0.00 0.00 0.53
October 0.00 0.00 0.49
November 0.00 0.00 0.39
December 0.00 0.00 0.27
       
Annual Sum or Average 0.00 0.00 0.40
Minimum of Months 0.00 0.00 0.23
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.25
February 0.00 0.00 0.30
March 0.00 0.00 0.34
April 0.00 0.00 0.45
May 0.00 0.00 0.57
June 0.00 0.00 0.65
July 0.00 0.00 0.68
August 0.00 0.00 0.66
September 0.00 0.00 0.66
October 0.00 0.00 0.59
November 0.00 0.00 0.44
December 0.00 0.00 0.28
       
Annual Sum or Average 0.00 0.00 0.49
Minimum of Months 0.00 0.00 0.25
Maximum of Months 0.00 0.00 0.68



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.16
February 0.00 0.00 0.23
March 0.00 0.00 0.30
April 0.00 0.00 0.42
May 0.00 0.00 0.57
June 0.00 0.00 0.64
July 0.00 0.00 0.67
August 0.00 0.00 0.65
September 0.00 0.00 0.61
October 0.00 0.00 0.52
November 0.00 0.00 0.36
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.44
Minimum of Months 0.00 0.00 0.16
Maximum of Months 0.00 0.00 0.67



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.13
February 0.00 0.00 0.18
March 0.00 0.00 0.23
April 0.00 0.00 0.32
May 0.00 0.00 0.44
June 0.00 0.00 0.51
July 0.00 0.00 0.53
August 0.00 0.00 0.51
September 0.00 0.00 0.49
October 0.00 0.00 0.42
November 0.00 0.00 0.30
December 0.00 0.00 0.17
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.13
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.16
February 0.00 0.00 0.23
March 0.00 0.00 0.29
April 0.00 0.00 0.42
May 0.00 0.00 0.57
June 0.00 0.00 0.66
July 0.00 0.00 0.68
August 0.00 0.00 0.65
September 0.00 0.00 0.63
October 0.00 0.00 0.52
November 0.00 0.00 0.36
December 0.00 0.00 0.19
       
Annual Sum or Average 0.00 0.00 0.45
Minimum of Months 0.00 0.00 0.16
Maximum of Months 0.00 0.00 0.68



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.24
February 0.00 0.00 0.31
March 0.00 0.00 0.36
April 0.00 0.00 0.48
May 0.00 0.00 0.64
June 0.00 0.00 0.73
July 0.00 0.00 0.76
August 0.00 0.00 0.75
September 0.00 0.00 0.73
October 0.00 0.00 0.64
November 0.00 0.00 0.47
December 0.00 0.00 0.30
       
Annual Sum or Average 0.00 0.00 0.54
Minimum of Months 0.00 0.00 0.24
Maximum of Months 0.00 0.00 0.76



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.22
February 0.00 0.00 0.27
March 0.00 0.00 0.29
April 0.00 0.00 0.39
May 0.00 0.00 0.52
June 0.00 0.00 0.60
July 0.00 0.00 0.62
August 0.00 0.00 0.61
September 0.00 0.00 0.61
October 0.00 0.00 0.55
November 0.00 0.00 0.42
December 0.00 0.00 0.27
       
Annual Sum or Average 0.00 0.00 0.45
Minimum of Months 0.00 0.00 0.22
Maximum of Months 0.00 0.00 0.62



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.25
February 0.00 0.00 0.31
March 0.00 0.00 0.35
April 0.00 0.00 0.48
May 0.00 0.00 0.64
June 0.00 0.00 0.75
July 0.00 0.00 0.77
August 0.00 0.00 0.75
September 0.00 0.00 0.75
October 0.00 0.00 0.65
November 0.00 0.00 0.47
December 0.00 0.00 0.28
       
Annual Sum or Average 0.00 0.00 0.54
Minimum of Months 0.00 0.00 0.25
Maximum of Months 0.00 0.00 0.77



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.17
February 0.00 0.00 0.25
March 0.00 0.00 0.33
April 0.00 0.00 0.46
May 0.00 0.00 0.64
June 0.00 0.00 0.73
July 0.00 0.00 0.76
August 0.00 0.00 0.74
September 0.00 0.00 0.71
October 0.00 0.00 0.59
November 0.00 0.00 0.40
December 0.00 0.00 0.23
       
Annual Sum or Average 0.00 0.00 0.50
Minimum of Months 0.00 0.00 0.17
Maximum of Months 0.00 0.00 0.76



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.14
February 0.00 0.00 0.21
March 0.00 0.00 0.26
April 0.00 0.00 0.37
May 0.00 0.00 0.52
June 0.00 0.00 0.61
July 0.00 0.00 0.62
August 0.00 0.00 0.61
September 0.00 0.00 0.59
October 0.00 0.00 0.50
November 0.00 0.00 0.34
December 0.00 0.00 0.19
       
Annual Sum or Average 0.00 0.00 0.41
Minimum of Months 0.00 0.00 0.14
Maximum of Months 0.00 0.00 0.62



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.17
February 0.00 0.00 0.25
March 0.00 0.00 0.32
April 0.00 0.00 0.46
May 0.00 0.00 0.65
June 0.00 0.00 0.75
July 0.00 0.00 0.78
August 0.00 0.00 0.74
September 0.00 0.00 0.72
October 0.00 0.00 0.60
November 0.00 0.00 0.40
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.51
Minimum of Months 0.00 0.00 0.17
Maximum of Months 0.00 0.00 0.78



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.67 652.71
February 0.00 0.00 866.00 582.37
March 0.00 0.00 826.57 615.41
April 0.00 0.00 774.57 558.09
May 0.00 0.00 717.25 534.01
June 0.00 0.00 674.88 486.26
July 0.00 0.00 658.70 490.42
August 0.00 0.00 668.15 497.45
September 0.00 0.00 708.36 510.38
October 0.00 0.00 759.87 565.75
November 0.00 0.00 816.59 588.36
December 0.00 0.00 862.16 641.90
         
Annual Sum or Average 0.00 0.00 766.93 6723.10
Minimum of Months 0.00 0.00 658.70 486.26
Maximum of Months 0.00 0.00 876.67 652.71



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.72 652.74
February 0.00 0.00 863.73 580.84
March 0.00 0.00 828.44 616.80
April 0.00 0.00 774.58 558.09
May 0.00 0.00 717.12 533.91
June 0.00 0.00 674.94 486.30
July 0.00 0.00 658.68 490.41
August 0.00 0.00 668.12 497.43
September 0.00 0.00 706.43 508.99
October 0.00 0.00 761.93 567.28
November 0.00 0.00 816.27 588.13
December 0.00 0.00 860.22 640.46
         
Annual Sum or Average 0.00 0.00 766.74 6721.38
Minimum of Months 0.00 0.00 658.68 486.30
Maximum of Months 0.00 0.00 876.72 652.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.57 652.63
February 0.00 0.00 865.94 582.33
March 0.00 0.00 826.39 615.27
April 0.00 0.00 774.53 558.06
May 0.00 0.00 717.15 533.94
June 0.00 0.00 674.86 486.25
July 0.00 0.00 658.71 490.43
August 0.00 0.00 668.15 497.46
September 0.00 0.00 708.55 510.52
October 0.00 0.00 759.70 565.62
November 0.00 0.00 816.54 588.32
December 0.00 0.00 862.13 641.88
         
Annual Sum or Average 0.00 0.00 766.89 6722.70
Minimum of Months 0.00 0.00 658.71 486.25
Maximum of Months 0.00 0.00 876.57 652.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 877.03 652.97
February 0.00 0.00 866.31 582.57
March 0.00 0.00 826.46 615.32
April 0.00 0.00 774.71 558.19
May 0.00 0.00 718.87 535.22
June 0.00 0.00 673.13 485.00
July 0.00 0.00 658.78 490.48
August 0.00 0.00 668.15 497.46
September 0.00 0.00 708.41 510.42
October 0.00 0.00 759.94 565.79
November 0.00 0.00 816.69 588.44
December 0.00 0.00 862.14 641.89
         
Annual Sum or Average 0.00 0.00 767.01 6723.75
Minimum of Months 0.00 0.00 658.78 485.00
Maximum of Months 0.00 0.00 877.03 652.97



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.78 652.78
February 0.00 0.00 866.04 582.39
March 0.00 0.00 826.35 615.24
April 0.00 0.00 774.64 558.14
May 0.00 0.00 718.50 534.94
June 0.00 0.00 673.50 485.26
July 0.00 0.00 658.78 490.48
August 0.00 0.00 668.16 497.46
September 0.00 0.00 708.40 510.41
October 0.00 0.00 759.94 565.79
November 0.00 0.00 816.60 588.37
December 0.00 0.00 862.13 641.88
         
Annual Sum or Average 0.00 0.00 766.94 6723.16
Minimum of Months 0.00 0.00 658.78 485.26
Maximum of Months 0.00 0.00 876.78 652.78



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.83 652.82
February 0.00 0.00 866.12 582.45
March 0.00 0.00 826.40 615.28
April 0.00 0.00 774.64 558.14
May 0.00 0.00 717.30 534.05
June 0.00 0.00 674.90 486.27
July 0.00 0.00 658.69 490.42
August 0.00 0.00 668.15 497.46
September 0.00 0.00 708.34 510.37
October 0.00 0.00 759.89 565.76
November 0.00 0.00 816.62 588.38
December 0.00 0.00 862.10 641.86
         
Annual Sum or Average 0.00 0.00 766.95 6723.25
Minimum of Months 0.00 0.00 658.69 486.27
Maximum of Months 0.00 0.00 876.83 652.82



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.70 652.73
February 0.00 0.00 863.61 580.76
March 0.00 0.00 828.52 616.86
April 0.00 0.00 774.58 558.09
May 0.00 0.00 717.11 533.91
June 0.00 0.00 674.94 486.30
July 0.00 0.00 658.69 490.41
August 0.00 0.00 668.12 497.43
September 0.00 0.00 706.41 508.97
October 0.00 0.00 761.95 567.29
November 0.00 0.00 816.22 588.10
December 0.00 0.00 860.05 640.33
         
Annual Sum or Average 0.00 0.00 766.71 6721.17
Minimum of Months 0.00 0.00 658.69 486.30
Maximum of Months 0.00 0.00 876.70 652.73



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 874.63 651.19
February 0.00 0.00 866.21 582.50
March 0.00 0.00 826.52 615.36
April 0.00 0.00 774.63 558.13
May 0.00 0.00 717.34 534.08
June 0.00 0.00 674.70 486.13
July 0.00 0.00 658.57 490.32
August 0.00 0.00 668.07 497.40
September 0.00 0.00 706.64 509.14
October 0.00 0.00 761.93 567.28
November 0.00 0.00 816.37 588.20
December 0.00 0.00 859.98 640.28
         
Annual Sum or Average 0.00 0.00 766.58 6720.01
Minimum of Months 0.00 0.00 658.57 486.13
Maximum of Months 0.00 0.00 874.63 651.19



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.84 652.83
February 0.00 0.00 863.86 580.93
March 0.00 0.00 826.17 615.10
April 0.00 0.00 775.81 558.98
May 0.00 0.00 718.42 534.88
June 0.00 0.00 672.79 484.75
July 0.00 0.00 658.78 490.48
August 0.00 0.00 668.15 497.46
September 0.00 0.00 708.41 510.42
October 0.00 0.00 759.94 565.79
November 0.00 0.00 816.49 588.29
December 0.00 0.00 860.02 640.31
         
Annual Sum or Average 0.00 0.00 766.60 6720.22
Minimum of Months 0.00 0.00 658.78 484.75
Maximum of Months 0.00 0.00 876.84 652.83



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.62 652.67
February 0.00 0.00 865.99 582.36
March 0.00 0.00 826.47 615.33
April 0.00 0.00 774.51 558.04
May 0.00 0.00 717.14 533.93
June 0.00 0.00 674.86 486.24
July 0.00 0.00 658.71 490.43
August 0.00 0.00 668.15 497.46
September 0.00 0.00 708.54 510.51
October 0.00 0.00 759.71 565.62
November 0.00 0.00 816.51 588.31
December 0.00 0.00 862.13 641.88
         
Annual Sum or Average 0.00 0.00 766.90 6722.78
Minimum of Months 0.00 0.00 658.71 486.24
Maximum of Months 0.00 0.00 876.62 652.67



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.85 652.84
February 0.00 0.00 863.91 580.96
March 0.00 0.00 826.29 615.19
April 0.00 0.00 776.97 559.82
May 0.00 0.00 717.30 534.05
June 0.00 0.00 672.75 484.72
July 0.00 0.00 658.79 490.49
August 0.00 0.00 668.05 497.38
September 0.00 0.00 708.47 510.46
October 0.00 0.00 759.97 565.82
November 0.00 0.00 816.51 588.31
December 0.00 0.00 860.08 640.36
         
Annual Sum or Average 0.00 0.00 766.62 6720.38
Minimum of Months 0.00 0.00 658.79 484.72
Maximum of Months 0.00 0.00 876.85 652.84



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.69 652.72
February 0.00 0.00 863.71 580.83
March 0.00 0.00 828.58 616.90
April 0.00 0.00 774.55 558.07
May 0.00 0.00 717.09 533.89
June 0.00 0.00 674.96 486.31
July 0.00 0.00 658.67 490.40
August 0.00 0.00 668.11 497.43
September 0.00 0.00 706.41 508.97
October 0.00 0.00 761.95 567.29
November 0.00 0.00 816.22 588.10
December 0.00 0.00 860.12 640.38
         
Annual Sum or Average 0.00 0.00 766.73 6721.29
Minimum of Months 0.00 0.00 658.67 486.31
Maximum of Months 0.00 0.00 876.69 652.72



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.58 652.64
February 0.00 0.00 865.99 582.36
March 0.00 0.00 826.45 615.32
April 0.00 0.00 774.54 558.07
May 0.00 0.00 717.16 533.95
June 0.00 0.00 674.87 486.25
July 0.00 0.00 658.71 490.43
August 0.00 0.00 668.15 497.45
September 0.00 0.00 708.40 510.41
October 0.00 0.00 759.82 565.71
November 0.00 0.00 816.55 588.33
December 0.00 0.00 862.12 641.88
         
Annual Sum or Average 0.00 0.00 766.90 6722.78
Minimum of Months 0.00 0.00 658.71 486.25
Maximum of Months 0.00 0.00 876.58 652.64



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.86 652.84
February 0.00 0.00 863.82 580.90
March 0.00 0.00 826.27 615.18
April 0.00 0.00 777.00 559.84
May 0.00 0.00 717.29 534.04
June 0.00 0.00 672.75 484.72
July 0.00 0.00 658.79 490.48
August 0.00 0.00 668.05 497.38
September 0.00 0.00 708.46 510.45
October 0.00 0.00 759.97 565.82
November 0.00 0.00 816.52 588.31
December 0.00 0.00 860.07 640.35
         
Annual Sum or Average 0.00 0.00 766.62 6720.32
Minimum of Months 0.00 0.00 658.79 484.72
Maximum of Months 0.00 0.00 876.86 652.84



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.67 652.71
February 0.00 0.00 863.78 580.87
March 0.00 0.00 828.66 616.96
April 0.00 0.00 774.58 558.09
May 0.00 0.00 717.12 533.91
June 0.00 0.00 674.94 486.30
July 0.00 0.00 658.69 490.41
August 0.00 0.00 668.12 497.43
September 0.00 0.00 706.41 508.97
October 0.00 0.00 761.95 567.29
November 0.00 0.00 816.25 588.12
December 0.00 0.00 860.17 640.42
         
Annual Sum or Average 0.00 0.00 766.75 6721.48
Minimum of Months 0.00 0.00 658.69 486.30
Maximum of Months 0.00 0.00 876.67 652.71



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.85 652.84
February 0.00 0.00 866.08 582.42
March 0.00 0.00 826.58 615.41
April 0.00 0.00 774.58 558.09
May 0.00 0.00 717.24 534.01
June 0.00 0.00 674.88 486.26
July 0.00 0.00 658.70 490.42
August 0.00 0.00 668.15 497.45
September 0.00 0.00 708.36 510.38
October 0.00 0.00 759.87 565.75
November 0.00 0.00 816.61 588.38
December 0.00 0.00 861.99 641.78
         
Annual Sum or Average 0.00 0.00 766.94 6723.18
Minimum of Months 0.00 0.00 658.70 486.26
Maximum of Months 0.00 0.00 876.85 652.84



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.56 652.63
February 0.00 0.00 863.95 580.98
March 0.00 0.00 828.73 617.01
April 0.00 0.00 774.63 558.13
May 0.00 0.00 717.13 533.92
June 0.00 0.00 674.93 486.30
July 0.00 0.00 658.69 490.41
August 0.00 0.00 668.12 497.43
September 0.00 0.00 706.41 508.97
October 0.00 0.00 761.95 567.29
November 0.00 0.00 816.24 588.11
December 0.00 0.00 860.17 640.42
         
Annual Sum or Average 0.00 0.00 766.76 6721.61
Minimum of Months 0.00 0.00 658.69 486.30
Maximum of Months 0.00 0.00 876.56 652.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 876.63 652.67
February 0.00 0.00 865.96 582.33
March 0.00 0.00 826.47 615.33
April 0.00 0.00 774.53 558.06
May 0.00 0.00 717.14 533.93
June 0.00 0.00 674.86 486.24
July 0.00 0.00 658.72 490.44
August 0.00 0.00 668.15 497.46
September 0.00 0.00 708.60 510.55
October 0.00 0.00 759.72 565.63
November 0.00 0.00 816.49 588.29
December 0.00 0.00 862.22 641.95
         
Annual Sum or Average 0.00 0.00 766.91 6722.89
Minimum of Months 0.00 0.00 658.72 486.24
Maximum of Months 0.00 0.00 876.63 652.67



Table of Contents

Report: HEATING AND COOLING LOADS

For: CRAWLSPACE

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 120.52 249.41
February 139.89 219.95
March 167.24 201.37
April 216.87 7.71
May 278.44 0.00
June 293.51 0.00
July 326.24 0.00
August 318.00 0.00
September 306.72 0.00
October 287.00 0.00
November 203.45 80.87
December 139.44 241.37
     
Annual Sum or Average 2797.34 1000.68
Minimum of Months 120.52 0.00
Maximum of Months 326.24 249.41



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 101.94 100.09
February 110.55 109.39
March 122.11 98.88
April 155.88 1.03
May 204.82 0.00
June 222.52 0.00
July 241.24 0.00
August 239.88 0.00
September 239.12 0.00
October 230.44 0.00
November 170.00 37.79
December 115.29 121.17
     
Annual Sum or Average 2153.78 468.35
Minimum of Months 101.94 0.00
Maximum of Months 241.24 121.17



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 121.60 222.60
February 136.65 198.01
March 158.92 151.11
April 215.42 7.76
May 280.45 0.00
June 306.67 0.00
July 335.52 0.00
August 319.62 0.00
September 316.00 0.00
October 291.62 0.00
November 203.33 70.84
December 129.14 226.55
     
Annual Sum or Average 2814.93 876.86
Minimum of Months 121.60 0.00
Maximum of Months 335.52 226.55



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 67.20 319.40
February 97.39 260.29
March 137.23 236.05
April 198.88 7.80
May 278.90 0.00
June 299.60 0.00
July 329.85 0.00
August 310.60 0.00
September 282.41 0.00
October 242.25 0.00
November 154.50 92.61
December 88.44 299.78
     
Annual Sum or Average 2487.24 1215.93
Minimum of Months 67.20 0.00
Maximum of Months 329.85 319.40



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 46.52 154.64
February 66.06 146.73
March 91.51 130.38
April 137.13 1.04
May 205.26 0.00
June 228.69 0.00
July 244.96 0.00
August 232.12 0.00
September 214.13 0.00
October 183.78 0.00
November 118.13 47.03
December 62.10 175.35
     
Annual Sum or Average 1830.38 655.17
Minimum of Months 46.52 0.00
Maximum of Months 244.96 175.35



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 64.07 261.53
February 91.41 230.35
March 126.78 162.04
April 196.81 7.80
May 280.24 0.00
June 311.78 0.00
July 338.20 0.00
August 311.65 0.00
September 291.01 0.00
October 245.92 0.00
November 152.24 77.11
December 76.56 275.24
     
Annual Sum or Average 2486.66 1014.07
Minimum of Months 64.07 0.00
Maximum of Months 338.20 275.24



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 135.76 125.33
February 152.48 120.44
March 183.87 108.55
April 232.45 1.44
May 285.53 0.00
June 298.60 0.00
July 332.32 0.00
August 321.87 0.00
September 312.44 0.00
October 297.01 0.00
November 217.13 41.80
December 156.08 138.76
     
Annual Sum or Average 2925.55 536.32
Minimum of Months 135.76 0.00
Maximum of Months 332.32 138.76



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 124.08 22.87
February 128.19 40.16
March 142.46 29.81
April 173.32 0.00
May 211.86 0.00
June 226.71 0.00
July 246.39 0.00
August 242.80 0.00
September 244.69 0.00
October 240.95 0.00
November 186.57 9.56
December 137.89 44.10
     
Annual Sum or Average 2305.92 146.51
Minimum of Months 124.08 0.00
Maximum of Months 246.39 44.10



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 139.13 109.80
February 150.55 106.31
March 177.45 77.13
April 231.40 1.67
May 287.41 0.00
June 311.73 0.00
July 341.86 0.00
August 323.51 0.00
September 321.92 0.00
October 301.85 0.00
November 217.76 35.66
December 146.72 128.74
     
Annual Sum or Average 2951.29 459.31
Minimum of Months 139.13 0.00
Maximum of Months 341.86 128.74



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 79.10 171.28
February 109.03 148.28
March 153.74 133.87
April 215.04 1.47
May 286.20 0.00
June 304.65 0.00
July 336.02 0.00
August 314.86 0.00
September 288.77 0.00
October 252.99 0.00
November 167.60 50.35
December 102.59 181.11
     
Annual Sum or Average 2610.59 686.36
Minimum of Months 79.10 0.00
Maximum of Months 336.02 181.11



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 62.68 49.59
February 81.57 60.73
March 110.37 46.02
April 155.13 0.00
May 212.52 0.00
June 232.86 0.00
July 250.11 0.00
August 235.43 0.00
September 219.90 0.00
October 194.67 0.00
November 133.77 14.06
December 80.06 74.62
     
Annual Sum or Average 1969.07 245.02
Minimum of Months 62.68 0.00
Maximum of Months 250.11 74.62



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 77.99 132.76
February 104.95 127.58
March 144.23 84.35
April 213.45 1.68
May 287.42 0.00
June 316.82 0.00
July 344.64 0.00
August 315.96 0.00
September 297.64 0.00
October 257.01 0.00
November 166.50 39.74
December 91.20 161.10
     
Annual Sum or Average 2617.83 547.21
Minimum of Months 77.99 0.00
Maximum of Months 344.64 161.10



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 84.02 233.21
February 113.64 209.52
March 155.78 146.10
April 231.63 5.44
May 314.42 0.00
June 348.14 0.00
July 381.23 0.00
August 351.09 0.00
September 335.34 0.00
October 287.91 0.00
November 182.19 70.93
December 97.64 254.81
     
Annual Sum or Average 2883.02 920.02
Minimum of Months 84.02 0.00
Maximum of Months 381.23 254.81



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 132.21 203.86
February 147.78 181.36
March 176.41 137.61
April 241.88 5.41
May 313.64 0.00
June 344.50 0.00
July 378.80 0.00
August 355.10 0.00
September 349.99 0.00
October 319.86 0.00
November 222.96 64.85
December 142.34 213.56
     
Annual Sum or Average 3125.47 806.65
Minimum of Months 132.21 0.00
Maximum of Months 378.80 213.56



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 131.09 233.76
February 151.14 203.86
March 185.16 190.06
April 243.99 5.33
May 312.61 0.00
June 332.54 0.00
July 370.13 0.00
August 353.92 0.00
September 341.09 0.00
October 315.45 0.00
November 223.16 75.06
December 152.40 230.94
     
Annual Sum or Average 3112.69 939.01
Minimum of Months 131.09 0.00
Maximum of Months 370.13 233.76



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 68.79 130.11
February 91.36 126.14
March 123.92 104.76
April 175.83 0.08
May 241.90 0.00
June 266.30 0.00
July 288.70 0.00
August 272.43 0.00
September 259.69 0.00
October 227.67 0.00
November 150.34 39.33
December 86.05 153.07
     
Annual Sum or Average 2252.98 553.49
Minimum of Months 68.79 0.00
Maximum of Months 288.70 153.07



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 117.12 86.96
February 125.91 96.66
March 144.27 84.65
April 186.27 0.07
May 240.79 0.00
June 262.09 0.00
July 285.76 0.00
August 276.37 0.00
September 274.67 0.00
October 260.79 0.00
November 192.45 31.51
December 132.57 110.16
     
Annual Sum or Average 2499.06 410.01
Minimum of Months 117.12 0.00
Maximum of Months 285.76 110.16



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:06:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 86.74 292.36
February 118.82 237.96
March 165.97 213.83
April 233.99 5.40
May 313.79 0.00
June 336.72 0.00
July 373.10 0.00
August 350.22 0.00
September 326.76 0.00
October 283.98 0.00
November 183.94 85.54
December 109.33 280.67
     
Annual Sum or Average 2883.35 1115.76