Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 16:29
Tabular Output Report in Format: HTML
Building: US+MF+CZ2B+hp+heatedbsmt+IECC_2009
Environment: ANNUAL ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2024-06-27 16:29:26
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Values gathered over 8760.00 hours| Total Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
| Total Site Energy | 819847.05 | 21.02 | 27.88 |
| Net Site Energy | 819847.05 | 21.02 | 27.88 |
| Total Source Energy | 2596455.59 | 66.57 | 88.30 |
| Net Source Energy | 2596455.59 | 66.57 | 88.30 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [ft2] | |
| Total Building Area | 39005.22 |
| Net Conditioned Building Area | 29404.35 |
| Unconditioned Building Area | 9600.87 |
| Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
| Heating | 36872.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 139566.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 61803.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 373262.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 50768.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 136970.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370400.12 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 819847.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370400.12 |
| Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
| Heating | General | 36872.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 139566.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | General | 61803.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Exterior-Lights | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_mels | 171606.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| IECC_adj | 71011.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Ventilation | 24355.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| General | 26412.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370400.12 | |
| Water Heater | 136970.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
| Heating | Unassigned | 36872.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 139566.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 61803.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 373262.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 50768.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 136970.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370400.12 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
| Lighting | 2.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 12.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 |
| Other | 12.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 27.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 |
| Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
| Lighting | 2.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 9.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
| Other | 9.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
| Electricity [kBtu] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 819847.045 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 819847.045 | 100.00 |
| Total On-Site and Utility Electric Sources | 819847.045 | 100.00 |
| Total Electricity End Uses | 819847.045 | 100.00 |
| Heat [kBtu] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | |
| Air to Air Heat Recovery for Cooling | 0.00 | |
| Air to Air Heat Recovery for Heating | 0.00 | |
| High-Temperature Geothermal* | 0.00 | |
| Solar Water Thermal | 0.00 | |
| Solar Air Thermal | 0.00 | |
| Total On-Site Thermal Sources | 0.00 |
| Water [gal] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 370400.12 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 370400.12 | 100.00 |
| Total Water End Uses | 370400.12 | 100.00 |
| Degrees [deltaF] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 351.50 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNITHEATEDBSMT | SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| HEATEDBSMT | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
General| Value | |
| Program Version and Build | EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 16:29 |
| RunPeriod | ANNUAL |
| Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
| Latitude [deg] | 32.17 |
| Longitude [deg] | -110.9 |
| Elevation [ft] | 2654.33 |
| Time Zone | -7.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
| Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
| Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
| Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
| Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
| Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
| Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
| Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
| Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
| Total | |
| Gross Roof Area [ft2] | 8451.30 |
| Skylight Area [ft2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
| HEATEDBSMT | 7794.39 | Yes | Yes | 58539.52 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.4972 | 1.5385 | |
| BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7516 | 600.28 | 2.9151 |
| ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7516 | 600.28 | 2.9151 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7516 | 600.28 | 2.9151 |
| Total | 39005.22 | 325627.71 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.5158 | 1083.48 | 1.9225 | |||
| Conditioned Total | 29404.35 | 242278.90 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.6842 | 816.79 | 2.5502 | |||
| Unconditioned Total | 9600.87 | 83348.81 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | Tags | |
| HEATEDBSMT | 7794.39 | Yes | Yes | 1.00 | HEATEDBSMT | GENERAL | HEATEDBSMT | 0.4972 | 0.00 | 1.5385 | |
| BREEZEWAY | 1798.16 | No | Yes | 1.00 | BREEZEWAY | GENERAL | BREEZEWAY | 0.0000 | 0.00 | 0.0000 | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.7516 | 600.28 | 2.9151 | |
| ATTIC | 7802.71 | No | Yes | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.7516 | 600.28 | 2.9151 | |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.7516 | 600.28 | 2.9151 | |
| Total | 39005.22 | 0.5158 | 1083.48 | 1.9225 | |||||||
| Conditioned Total | 29404.35 | 0.6842 | 816.79 | 2.5502 | |||||||
| Unconditioned Total | 9600.87 | 0.0000 | 0.00 | 0.0000 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [ft2] | Conditioned Area [ft2] | Unconditioned Area [ft2] | Not Part of Total Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
| GENERAL | 39005.22 | 29404.35 | 9600.87 | 0.00 | 0.5158 | 1083.48 | 1.9225 |
| Total | 39005.22 | 29404.35 | 9600.87 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
End Uses| Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
| Time of Peak | 30-JUL-19:00 | - | - | - | - | - | - | - | - | - | - | - | 01-JAN-08:19 |
| Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 61.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 18.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 4.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 64.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 12.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 127.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 288.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
| Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
| Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 61.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | General | 18.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Exterior-Lights | 4.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Interior Equipment | dishwasher | 2.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| clotheswasher | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_mels | 27.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| IECC_adj | 11.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Ventilation | 2.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| General | 9.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | |
| Water Heater | 127.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Values gathered over 8760.00 hours| Source Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
| Heating | 116774.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 442006.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 195732.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 65251.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1182122.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 160782.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 433784.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 2596455.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
| Heating | 3.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 15.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 6.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 2.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 40.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 5.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 14.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 88.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
| Heating | 2.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 11.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 5.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 1.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 30.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 4.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 11.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 66.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
AirTerminal:SingleDuct:ConstantVolume:NoReheat| Design Size Maximum Air Flow Rate [ft3/min] | |
| ZONEDIRECTAIR_UNITHEATEDBSMT | 619.23 |
| ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 633.07 |
| ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 392.58 |
| ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 513.83 |
| ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 622.96 |
| ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 381.38 |
| ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 496.64 |
| ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 617.90 |
| ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 362.00 |
| ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 495.78 |
| ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 609.74 |
| ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 360.75 |
| ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 470.56 |
| ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 600.56 |
| ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 607.09 |
| ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 737.59 |
| ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 482.74 |
| ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 479.95 |
| ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 738.49 |
| Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 633.07 | 633.07 | 633.07 | 633.07 | 633.07 | 633.07 | 1.00 | 1.00 | 633.07 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 392.58 | 392.58 | 392.58 | 392.58 | 392.58 | 392.58 | 1.00 | 1.00 | 392.58 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 513.83 | 513.83 | 513.83 | 513.83 | 513.83 | 513.83 | 1.00 | 1.00 | 513.83 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 622.96 | 622.96 | 622.96 | 622.96 | 622.96 | 622.96 | 1.00 | 1.00 | 622.96 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 381.38 | 381.38 | 381.38 | 381.38 | 381.38 | 381.38 | 1.00 | 1.00 | 381.38 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 496.64 | 496.64 | 496.64 | 496.64 | 496.64 | 496.64 | 1.00 | 1.00 | 496.64 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 617.90 | 617.90 | 617.90 | 617.90 | 617.90 | 617.90 | 1.00 | 1.00 | 617.90 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 362.00 | 362.00 | 362.00 | 362.00 | 362.00 | 362.00 | 1.00 | 1.00 | 362.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 495.78 | 495.78 | 495.78 | 495.78 | 495.78 | 495.78 | 1.00 | 1.00 | 495.78 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 609.74 | 609.74 | 609.74 | 609.74 | 609.74 | 609.74 | 1.00 | 1.00 | 609.74 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 360.75 | 360.75 | 360.75 | 360.75 | 360.75 | 360.75 | 1.00 | 1.00 | 360.75 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 470.56 | 470.56 | 470.56 | 470.56 | 470.56 | 470.56 | 1.00 | 1.00 | 470.56 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 737.59 | 737.59 | 737.59 | 737.59 | 737.59 | 737.59 | 1.00 | 1.00 | 737.59 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 479.95 | 479.95 | 479.95 | 479.95 | 479.95 | 479.95 | 1.00 | 1.00 | 479.95 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 607.09 | 607.09 | 607.09 | 607.09 | 607.09 | 607.09 | 1.00 | 1.00 | 607.09 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 738.49 | 738.49 | 738.49 | 738.49 | 738.49 | 738.49 | 1.00 | 1.00 | 738.49 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 482.74 | 482.74 | 482.74 | 482.74 | 482.74 | 482.74 | 1.00 | 1.00 | 482.74 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 600.56 | 600.56 | 600.56 | 600.56 | 600.56 | 600.56 | 1.00 | 1.00 | 600.56 |
| CENTRAL SYSTEM_UNITHEATEDBSMT | 619.23 | 619.23 | 619.23 | 619.23 | 619.23 | 619.23 | 1.00 | 1.00 | 619.23 |
| Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 633.07 | 1.96 | 0.724595 |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 392.58 | 1.31 | 0.701083 |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 513.83 | 1.70 | 0.703411 |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 622.96 | 1.92 | 0.725492 |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 381.38 | 1.21 | 0.716314 |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 496.64 | 1.66 | 0.701083 |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 617.90 | 1.91 | 0.725834 |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 362.00 | 1.17 | 0.711019 |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 495.78 | 1.65 | 0.702934 |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 609.74 | 1.87 | 0.728994 |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 360.75 | 1.13 | 0.720050 |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 470.56 | 1.57 | 0.701083 |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 737.59 | 2.24 | 0.730368 |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 479.95 | 1.51 | 0.720147 |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 607.09 | 1.96 | 0.710604 |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 738.49 | 2.24 | 0.731622 |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 482.74 | 1.49 | 0.725597 |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 600.56 | 1.94 | 0.711051 |
| DX COOLING COIL_UNITHEATEDBSMT | 619.23 | 1.66 | 0.776338 |
| Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Supplemental Heating Coil Nominal Capacity [Btu/h] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | 633.07 | 633.07 | 633.07 | 23539.67 | 1.96 | 11098.00 | 1.00 |
| HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | 392.58 | 392.58 | 392.58 | 15700.01 | 1.31 | 9027.18 | 1.00 |
| HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | 513.83 | 513.83 | 513.83 | 20438.13 | 1.70 | 11093.99 | 1.00 |
| HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | 622.96 | 622.96 | 622.96 | 23084.95 | 1.92 | 11103.24 | 1.00 |
| HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | 381.38 | 381.38 | 381.38 | 14527.13 | 1.21 | 9028.38 | 1.00 |
| HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | 496.64 | 496.64 | 496.64 | 19861.31 | 1.66 | 11091.18 | 1.00 |
| HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | 617.90 | 617.90 | 617.90 | 22868.01 | 1.91 | 10018.95 | 1.00 |
| HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | 362.00 | 362.00 | 362.00 | 14022.84 | 1.17 | 7785.75 | 1.00 |
| HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | 495.78 | 495.78 | 495.78 | 19758.43 | 1.65 | 10019.78 | 1.00 |
| HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | 609.74 | 609.74 | 609.74 | 22383.21 | 1.87 | 10023.58 | 1.00 |
| HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | 360.75 | 360.75 | 360.75 | 13596.84 | 1.13 | 7786.25 | 1.00 |
| HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | 470.56 | 470.56 | 470.56 | 18818.44 | 1.57 | 10016.17 | 1.00 |
| HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | 737.59 | 737.59 | 737.59 | 26938.11 | 2.24 | 12667.19 | 1.00 |
| HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | 479.95 | 479.95 | 479.95 | 18082.61 | 1.51 | 10433.32 | 1.00 |
| HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | 607.09 | 607.09 | 607.09 | 23555.80 | 1.96 | 12670.43 | 1.00 |
| HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | 738.49 | 738.49 | 738.49 | 26845.46 | 2.24 | 12669.91 | 1.00 |
| HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | 482.74 | 482.74 | 482.74 | 17881.74 | 1.49 | 10433.02 | 1.00 |
| HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | 600.56 | 600.56 | 600.56 | 23261.27 | 1.94 | 12667.13 | 1.00 |
| HEAT PUMP_UNITHEATEDBSMT | 619.23 | 619.23 | 619.23 | 19942.35 | 1.66 | 9602.00 | 1.00 |
| Design Size Maximum Flow Rate [ft3/min] | |
| SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 633.07 |
| SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 392.58 |
| SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 513.83 |
| SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 622.96 |
| SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 381.38 |
| SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 496.64 |
| SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 617.90 |
| SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 362.00 |
| SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 495.78 |
| SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 609.74 |
| SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 360.75 |
| SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 470.56 |
| SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 737.59 |
| SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 479.95 |
| SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 607.09 |
| SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 738.49 |
| SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 482.74 |
| SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 600.56 |
| SUPPLY FAN_UNITHEATEDBSMT | 619.23 |
| Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Heating Capacity [Btu/h] | |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 633.07 | 25317.69 |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 392.58 | 15700.01 |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 513.83 | 20548.82 |
| MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 622.96 | 24913.06 |
| MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 381.38 | 15252.09 |
| MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 496.64 | 19861.31 |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 617.90 | 24710.94 |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 362.00 | 14476.88 |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 495.78 | 19827.03 |
| MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 609.74 | 24384.34 |
| MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 360.75 | 14427.15 |
| MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 470.56 | 18818.44 |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 737.59 | 29497.42 |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 479.95 | 19194.03 |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 607.09 | 24278.61 |
| MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 738.49 | 29533.37 |
| MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 482.74 | 19305.48 |
| MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 600.56 | 24017.47 |
| MAIN DX HEATING COIL_UNITHEATEDBSMT | 619.23 | 24763.91 |
| Design Size Nominal Capacity [Btu/h] | |
| SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 12762.70 |
| SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 10381.26 |
| SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 12758.09 |
| SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 12768.72 |
| SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 10382.63 |
| SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 12754.86 |
| SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 11521.79 |
| SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 8953.61 |
| SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 11522.75 |
| SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 11527.12 |
| SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 8954.18 |
| SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 11518.60 |
| SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 14567.27 |
| SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 11998.32 |
| SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 14570.99 |
| SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 14570.40 |
| SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 11997.98 |
| SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 14567.20 |
| SUPP HEATING COIL_UNITHEATEDBSMT | 12002.50 |
| Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
| DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
| Design Flow Rate [ft3/min] | |
| MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
| Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| Possible Shadow Receivers | |
| OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| BGWALL_UPPER_LDF | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| BGWALL_UPPER_SDR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| BGWALL_UPPER_LDB | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| BGWALL_UPPER_SDL | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| Possible Shadow Receivers | |
| WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Version| Version ID | |
| 1 | 23.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | Yes | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.200 | 0.200 |
| Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
| 1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
| Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
| 1 | 55.29 | 58.26 | 64.02 | 69.48 | 79.79 | 85.23 | 86.72 | 83.97 | 77.59 | 69.67 | 61.86 | 56.70 |
| Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
| 1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
| Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
| 1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
| 1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 2654.33 | 13. | 1.0932 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
| 1 | Correlation | NA | 70.99 | 34.74 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | US+MF+CZ2B+hp+heatedbsmt+IECC_2009 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | DOE-2 |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Algorithm {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
Space Heat Balance Sizing |
Space Heat Balance Simulation |
|
| 1 | ThirdOrderBackwardDifference | No | No |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
| 1 | 0.220 | 1213.970 | 0.003566 |
| Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
| 1 | SHEATHING_CONSOL_LAYER | 0.1351 | Rough | 0.0417 | 9.402E-002 | 42.764 | 0.280 | 0.9000 | 0.7000 | 0.7000 |
| 2 | CEIL_CONSOL_LAYER | 4.9646 | Rough | 1.0053 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
| 3 | FLOOR_CONSOL_LAYER | 1.9554E-005 | Rough | 0.0008 | 12.990 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
| 4 | BSMTWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
| 5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
| 6 | WALL_CONSOL_LAYER | 1.5339 | Rough | 0.2917 | 5.796E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
| 7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
| 8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
| 9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
| 10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
| 11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
| 12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
| 13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
| 14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
| 15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
| 16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.7000 | 0.7000 | 0.7000 |
| 17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
| 18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
| 19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
| 20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
| 23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
| 25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
| 28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
| 29 | DOOR_CONST | 0.2709 | Smooth | 0.0640 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
| 30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
| 31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
| 32 | PIPE INSULATION | 0.3830 | VeryRough | 0.0417 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
| 33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
| 34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
| 35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
| 36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
| 37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
| 38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
| 39 | GLASS | 0.1020 | VerySmooth | 0.0066 | 1.962E-002 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
| Material Name | ThermalResistance {m2-K/w} | |
| 1 | AIR_4_IN_VERT | 0.1585 |
| 2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
| 3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
| 4 | AIR_4_IN_VERT | 0.1585 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
| 1 | SURFPROPOTHSDCOEFBASEMENTAVGWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTWALLSURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
| 2 | SURFPROPOTHSDCOEFBASEMENTAVGFLOOR | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTFLOORTEMP | NO | 24.000 | 0.000 | N/A | N/A |
| 3 | SURFPROPOTHSDCOEFBASEMENTUPPERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTUPPERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
| 4 | SURFPROPOTHSDCOEFBASEMENTLOWERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTLOWERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
| 1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 60 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 21 | 186 | 48 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | HEATEDBSMT | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.51 | -3.4 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | -7.0 | 0.49 | 7.51 | 58539.45 | TARP | DOE-2 | 7794.37 | 185.05 | 185.05 | 0.00 | 15 | 0 | 0 | Yes |
| 2 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
| 3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 15 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
| 16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
| 1 | HEATEDBSMT | 7794.37 | 0.0 | N/A | 0.000 | 0.497 | 1.538 | 0.000 | 0.000 | 0.000 | 0.000 | 2.036 | No |
| 2 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
| 3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 15 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
| 16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| 21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.751 | 2.915 | 0.000 | 0.000 | 0.000 | 0.000 | 3.667 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
| 1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 683.529 | 0.569 | 100.165 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 46.993 | 683.529 |
| 36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 37 | BASEMENT HARDWIRED LIGHTING | INTERIORLIGHTINGHE | HEATEDBSMT | 7794.37 | 0.0 | 2935.480 | 0.377 | N/A | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 201.813 | 2935.480 |
| 38 | BASEMENT PLUG-IN LIGHTING | INTERIORLIGHTINGHE | HEATEDBSMT | 7794.37 | 0.0 | 939.713 | 0.120 | N/A | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 64.606 | 939.713 |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
| 1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 4 | ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 5 | ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 7 | ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 8 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 9 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 10 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 11 | ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 12 | ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 13 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 14 | ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 15 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 16 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 17 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 18 | ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 19 | ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 20 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 21 | ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 22 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 23 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 24 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 25 | ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 26 | ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 27 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 28 | ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 29 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 30 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 31 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 32 | ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 33 | ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 34 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 35 | ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 36 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 37 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 38 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 39 | ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 40 | ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 41 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 42 | ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 43 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 44 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 45 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 46 | ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 47 | ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 48 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 49 | ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 50 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 51 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 52 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 53 | ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 54 | ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 55 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 56 | ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 57 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 58 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 59 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 60 | ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 61 | ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 62 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 63 | ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 64 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 65 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 66 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 67 | ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 68 | ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 69 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 70 | ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 71 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 72 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 73 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 74 | ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 75 | ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 76 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 77 | ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 78 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 79 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 80 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 81 | ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 82 | ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 83 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 84 | ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 85 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 86 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 87 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 88 | ELECTRIC_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 89 | ELECTRIC_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 90 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 91 | ELECTRIC_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 92 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 93 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 94 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 95 | ELECTRIC_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 96 | ELECTRIC_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 97 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 98 | ELECTRIC_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 99 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 100 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 101 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 102 | ELECTRIC_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 103 | ELECTRIC_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 104 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 105 | ELECTRIC_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 106 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 107 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 108 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 109 | ELECTRIC_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 110 | ELECTRIC_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 111 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 112 | ELECTRIC_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 113 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 114 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 115 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 116 | ELECTRIC_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 117 | ELECTRIC_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 118 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 119 | ELECTRIC_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 120 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 121 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 122 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 123 | ELECTRIC_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 124 | ELECTRIC_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 125 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 126 | ELECTRIC_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1609.918 | 1.341 | 235.920 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 832.364 | 1609.918 |
| 127 | IECC_ADJ_HEATEDBSMT | MISCPLUGLOAD | HEATEDBSMT | 7794.37 | 0.0 | 11991.491 | 1.538 | N/A | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 6199.880 | 11991.491 |
| Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
| 1 | EXTERIOR WALL | 1 | 5 | 10 | 0.167 | 0.0937 | 0.700 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 3 | EXTERIOR FLOOR | 4 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 4 | INTERIOR CEILING | 6 | 2 | 8 | 0.167 | 0.0349 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 5 | ATTIC FLOOR | 7 | 2 | 8 | 0.167 | 0.0349 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 6 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 7 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
| 8 | EXTERIOR DOOR | 14 | 1 | 4 | 0.167 | 0.650 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 9 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 10 | BASEMENT WALL | 24 | 3 | 4 | 0.167 | 0.534 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 11 | iz-EXTERIOR FLOOR | 25 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
| 1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
| 2 | SHEATHING_CONSOL_LAYER | 0.0417 | 0.094 | 42.764 | 0.280 | 0.1351 |
| 3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
| 4 | WALL_CONSOL_LAYER | 0.2917 | 0.058 | 7.541 | 0.248 | 1.534 |
| 5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
| 7 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
| 8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
| 9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
| 10 | CEIL_CONSOL_LAYER | 1.0053 | 0.062 | 2.618 | 0.185 | 4.965 |
| 11 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 12 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 13 | CEIL_CONSOL_LAYER | 1.0053 | 0.062 | 2.618 | 0.185 | 4.965 |
| 14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 15 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
| 16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 17 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
| 18 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
| 19 | DOOR_CONST | 0.0640 | 0.072 | 32.003 | 0.183 | 0.2709 |
| 20 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
| 21 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
| 22 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
| 23 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 24 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
| 25 | BSMTWALL_CONSOL_LAYER | 0.0010 | 10.844 | 7.541 | 0.248 | 0.2342E-04 |
| 26 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
| 27 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
| 28 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
| 29 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
| Material Name | ThermalResistance {m2-K/w} | |
| 1 | AIR_4_IN_VERT | 0.1585 |
| 2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
| 3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
| 4 | AIR_4_IN_VERT | 0.1585 |
| Time | Outside | Cross | Inside | Flux (except final one) | |
| 1 | 10 | 0.53690791E-10 | -0.14086767E-13 | 0.12185568E-09 | -0.56142619E-15 |
| 2 | 9 | -0.78969438E-07 | 0.37271083E-11 | -0.12786746E-06 | 0.41607738E-10 |
| 3 | 8 | 0.15644920E-04 | 0.57233592E-08 | 0.24713380E-04 | -0.42390053E-07 |
| 4 | 7 | -0.11010334E-02 | 0.13458163E-05 | -0.17770580E-02 | 0.73075693E-05 |
| 5 | 6 | 0.34256138E-01 | 0.71913801E-04 | 0.57800664E-01 | -0.42770275E-03 |
| 6 | 5 | -0.50970556 | 0.10561809E-02 | -0.91414050 | 0.10365322E-01 |
| 7 | 4 | 3.8008141 | 0.46021679E-02 | 7.1669335 | -0.11749215 |
| 8 | 3 | -14.731927 | 0.58137860E-02 | -27.604869 | 0.65172867 |
| 9 | 2 | 29.625503 | 0.18019171E-02 | 52.431474 | -1.7640469 |
| 10 | 1 | -28.806601 | 0.81323549E-04 | -47.206921 | 2.1946319 |
| 11 | 0 | 10.602175 | 0.49952751E-07 | 16.084904 | |
| 12 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
| 13 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
| 14 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
| 15 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
| 16 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
| 17 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
| 18 | 4 | 0.29631924E-13 | -0.40788276E-14 | 0.60443234E-14 | -0.77798347E-16 |
| 19 | 3 | -0.11254351E-04 | 0.79669069E-06 | -0.23145793E-05 | 0.39394231E-13 |
| 20 | 2 | 0.49771861 | 0.29587917E-01 | 0.78801895E-01 | -0.76025120E-05 |
| 21 | 1 | -8.3915550 | 0.80192706 | -1.1535996 | 0.21114735 |
| 22 | 0 | 9.2367617 | 0.51139848 | 2.4177143 | |
| 23 | 8 | -0.19955962E-17 | 0.73322287E-16 | 0.22297369E-07 | 0.32822528E-16 |
| 24 | 7 | -0.41677264E-07 | 0.10019220E-10 | -0.10904919E-01 | 0.29209175E-07 |
| 25 | 6 | 0.51656634E-02 | 0.11264243E-06 | 0.41501785 | -0.36203283E-02 |
| 26 | 5 | -0.90145565E-01 | 0.13848923E-04 | -4.5221814 | 0.64991548E-01 |
| 27 | 4 | 0.61381812 | 0.20608367E-03 | 22.362906 | -0.45855939 |
| 28 | 3 | -2.0715279 | 0.66281990E-03 | -57.676573 | 1.6179231 |
| 29 | 2 | 3.6382511 | 0.50785658E-03 | 80.070402 | -3.0000438 |
| 30 | 1 | -3.1552904 | 0.73826575E-04 | -56.558927 | 2.7719184 |
| 31 | 0 | 1.0611943 | 0.67997522E-06 | 15.921725 | |
| 32 | 8 | 0.22297369E-07 | 0.73322287E-16 | -0.19955962E-17 | 0.32822528E-16 |
| 33 | 7 | -0.10904919E-01 | 0.10019220E-10 | -0.41677264E-07 | 0.29209175E-07 |
| 34 | 6 | 0.41501785 | 0.11264243E-06 | 0.51656634E-02 | -0.36203283E-02 |
| 35 | 5 | -4.5221814 | 0.13848923E-04 | -0.90145565E-01 | 0.64991548E-01 |
| 36 | 4 | 22.362906 | 0.20608367E-03 | 0.61381812 | -0.45855939 |
| 37 | 3 | -57.676573 | 0.66281990E-03 | -2.0715279 | 1.6179231 |
| 38 | 2 | 80.070402 | 0.50785658E-03 | 3.6382511 | -3.0000438 |
| 39 | 1 | -56.558927 | 0.73826575E-04 | -3.1552904 | 2.7719184 |
| 40 | 0 | 15.921725 | 0.67997522E-06 | 1.0611943 | |
| 41 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
| 42 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
| 43 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
| 44 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
| 45 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
| 46 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
| 47 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
| 48 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
| 49 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
| 50 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
| 51 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
| 52 | 4 | 0.12293178E-12 | 0.98102787E-13 | 0.12293178E-12 | -0.78082297E-22 |
| 53 | 3 | -0.55367102E-05 | 0.39956238E-05 | -0.55367102E-05 | 0.32471634E-11 |
| 54 | 2 | 0.81692253E-01 | 0.46949549E-01 | 0.81692253E-01 | -0.22376130E-04 |
| 55 | 1 | -4.1649776 | 1.8043782 | -4.1649776 | 0.77761216E-01 |
| 56 | 0 | 7.4874398 | 1.5528172 | 7.4874398 | |
| 57 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
| 58 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
| 59 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
| 60 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
| 61 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
| 62 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
| 63 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 | |
| 64 | 4 | 0.69987904E-07 | 0.26228811E-07 | 0.69987904E-07 | -0.89457852E-14 |
| 65 | 3 | -0.30987589E-02 | 0.10225415E-02 | -0.30987589E-02 | 0.11234143E-06 |
| 66 | 2 | 0.81559891 | 0.24124884 | 0.81559891 | -0.23762713E-02 |
| 67 | 1 | -7.9329461 | 1.4912083 | -7.9329461 | 0.29351368 |
| 68 | 0 | 9.2684202 | 0.41449462 | 9.2684202 | |
| 69 | 4 | 0.60443234E-14 | -0.40788276E-14 | 0.29631924E-13 | -0.77798347E-16 |
| 70 | 3 | -0.23145793E-05 | 0.79669069E-06 | -0.11254351E-04 | 0.39394231E-13 |
| 71 | 2 | 0.78801895E-01 | 0.29587917E-01 | 0.49771861 | -0.76025120E-05 |
| 72 | 1 | -1.1535996 | 0.80192706 | -8.3915550 | 0.21114735 |
| 73 | 0 | 2.4177143 | 0.51139848 | 9.2367617 |
| Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | Conductance (Before Adjusted) {Btu/h-ft2-F} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
| 1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.651 | 0.651 | 1.000 | 0.259 | ||
| 2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.651 | 0.651 | 1.000 | 0.259 | ||
| 3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.651 | 0.651 | 1.000 | 0.244 | ||
| 4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 1.071 | 1.000 | 0.929 | ||
| 5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 1.077 | 1.000 | 0.906 |
| Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
| 1 | GLASS | SpectralAverage | 0.00656 | 0.15422 | 0.55843 | 0.55843 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 1.96172E-002 | 1.00000 | No | |
| 2 | GLASS | SpectralAverage | 0.00656 | 0.15422 | 0.55843 | 0.55843 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 1.96172E-002 | 1.00000 | No | |
| 3 | GLASS | SpectralAverage | 0.00656 | 0.15422 | 0.55843 | 0.55843 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 1.96172E-002 | 1.00000 | No | |
| 4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
| 5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
| Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
| 1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 2 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 3 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 4 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 5 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 6 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 7 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 8 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 9 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 10 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 11 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 12 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 13 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 14 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 15 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 16 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 17 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 18 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
| 1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 60.000 | 0.050 | 30.000 | 0.353 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 19 | VENTILATION_UNITHEATEDBSMT | ALWAYS_OFF | HEATEDBSMT | 7794.37 | 0.0 | 60.000 | 0.008 | N/A | 6.151E-002 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | HEATEDBSMT | Mixing/Well-Stirred |
| 2 | BREEZEWAY | Mixing/Well-Stirred |
| 3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 15 | ATTIC | Mixing/Well-Stirred |
| 16 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
| 17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
| 18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
| 19 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
| 20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
| 21 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.0000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.0000 |
| Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
| 1 | HEATEDBSMT | Cooling | 13204.36268 | 13204.36268 | 619.23721 | 619.23721 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 96.10340 | 0.00562 | 7794.38637 | 0.00000 | 59.99321 | 0.00000 |
| 2 | HEATEDBSMT | Heating | 7404.35667 | 7404.35667 | 412.54232 | 412.54232 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 32.90000 | 0.00432 | 7794.38637 | 0.00000 | 59.99321 | 0.00000 |
| 3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 13500.40606 | 13500.40606 | 633.07195 | 633.07195 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 101.68939 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 4 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 8922.71977 | 8922.71977 | 497.01265 | 497.01265 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 5 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 8372.11871 | 8372.11871 | 392.58470 | 392.58470 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 104.96120 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 6 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 6821.27555 | 6821.27555 | 379.97877 | 379.97877 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 7 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 10957.61613 | 10957.61613 | 513.83468 | 513.83468 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 105.44000 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 8 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 8918.65413 | 8918.65413 | 496.80078 | 496.80078 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 9 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 13284.62586 | 13284.62586 | 622.96602 | 622.96602 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 101.29041 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 10 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 8928.03426 | 8928.03426 | 497.30926 | 497.30926 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 11 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 8132.88786 | 8132.88786 | 381.37707 | 381.37707 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 99.09590 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 12 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 6822.48985 | 6822.48985 | 380.04232 | 380.04232 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 13 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 10419.64217 | 10419.64217 | 488.60163 | 488.60163 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 105.44000 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 14 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 8915.79975 | 8915.79975 | 496.63129 | 496.63129 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 15 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 13176.57952 | 13176.57952 | 617.90246 | 617.90246 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 101.29041 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 16 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 7827.65464 | 7827.65464 | 436.05927 | 436.05927 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 17 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 7719.41225 | 7719.41225 | 361.99148 | 361.99148 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 100.09341 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 18 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 5561.42649 | 5561.42649 | 309.80928 | 309.80928 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 19 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 10572.48189 | 10572.48189 | 495.78384 | 495.78384 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 105.44000 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 20 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 7828.49949 | 7828.49949 | 436.10164 | 436.10164 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 21 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 13002.37873 | 13002.37873 | 609.74569 | 609.74569 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 100.49239 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 22 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 7832.35000 | 7832.35000 | 436.31350 | 436.31350 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 23 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 7692.83393 | 7692.83393 | 360.76267 | 360.76267 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 97.89890 | 0.00562 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 24 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 5561.93208 | 5561.93208 | 309.83047 | 309.83047 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 25 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 10034.69743 | 10034.69743 | 470.55079 | 470.55079 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 105.44000 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 26 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 7824.83282 | 7824.83282 | 435.88978 | 435.88978 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 27 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 12807.56210 | 12807.56210 | 600.57196 | 600.57196 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 104.72180 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 28 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 10515.04629 | 10515.04629 | 585.72026 | 585.72026 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 29 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 12946.80773 | 12946.80773 | 607.09738 | 607.09738 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 104.96120 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 30 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 10518.38828 | 10518.38828 | 585.91094 | 585.91094 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 31 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 15729.18802 | 15729.18802 | 737.58465 | 737.58465 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 101.29041 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 32 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 10515.10447 | 10515.10447 | 585.72026 | 585.72026 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 33 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 10294.28303 | 10294.28303 | 482.73299 | 482.73299 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 99.09590 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 34 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 8247.89639 | 8247.89639 | 459.44909 | 459.44909 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 35 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 10234.92399 | 10234.92399 | 479.95757 | 479.95757 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 100.49239 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 36 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 8248.19541 | 8248.19541 | 459.44909 | 459.44909 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 37 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 15748.32736 | 15748.32736 | 738.49567 | 738.49567 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 100.89140 | 0.00563 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| 38 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 10517.86494 | 10517.86494 | 585.86857 | 585.86857 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 59.99321 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
| 1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 4363.87 | 633.07195 | 633.07195 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 3252.64 | 497.01265 | 497.01265 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2937.93 | 392.58470 | 392.58470 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 2645.72 | 379.97877 | 379.97877 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 3693.62 | 513.83468 | 513.83468 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 3251.46 | 496.80078 | 496.80078 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 4294.60 | 622.96602 | 622.96602 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 3254.17 | 497.30926 | 497.30926 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2767.43 | 381.37707 | 381.37707 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 2646.07 | 380.04232 | 380.04232 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 3538.10 | 488.60163 | 488.60163 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 3250.64 | 496.63129 | 496.63129 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 4263.38 | 617.90246 | 617.90246 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 2936.39 | 436.05927 | 436.05927 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2665.15 | 361.99148 | 361.99148 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 2281.87 | 309.80928 | 309.80928 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 3582.29 | 495.78384 | 495.78384 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 2936.63 | 436.10164 | 436.10164 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 4199.23 | 609.74569 | 609.74569 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 2937.74 | 436.31350 | 436.31350 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2619.54 | 360.76267 | 360.76267 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 2282.02 | 309.83047 | 309.83047 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 3426.83 | 470.55079 | 470.55079 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 2935.57 | 435.88978 | 435.88978 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 5001.27 | 737.58465 | 737.58465 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 3712.54 | 585.72026 | 585.72026 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 3399.21 | 479.95757 | 479.95757 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 3057.83 | 459.44909 | 459.44909 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 4260.37 | 607.09738 | 607.09738 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 3713.49 | 585.91094 | 585.91094 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 4999.91 | 738.49567 | 738.49567 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 3713.34 | 585.86857 | 585.86857 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 3392.24 | 482.73299 | 482.73299 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 3057.74 | 459.44909 | 459.44909 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 4215.98 | 600.57196 | 600.57196 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 3712.52 | 585.72026 | 585.72026 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 37 | CENTRAL SYSTEM_UNITHEATEDBSMT | Cooling | Sensible | 4181.78 | 619.23721 | 619.23721 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 38 | CENTRAL SYSTEM_UNITHEATEDBSMT | Heating | Sensible | 2814.19 | 412.54232 | 412.54232 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNITHEATEDBSMT | Design Size Maximum Air Flow Rate [ft3/min] | 619.23721 |
| 2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 633.07195 |
| 3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 392.58470 |
| 4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 513.83468 |
| 5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 622.96602 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 381.37707 |
| 7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 496.63129 |
| 8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 617.90246 |
| 9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 361.99148 |
| 10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 495.78384 |
| 11 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 609.74569 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 360.76267 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 470.55079 |
| 14 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 600.57196 |
| 15 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 607.09738 |
| 16 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 737.58465 |
| 17 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 482.73299 |
| 18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 479.95757 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 738.49567 |
| 20 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 633.07195 |
| 21 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 633.07195 |
| 22 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 633.07195 |
| 23 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 633.07195 |
| 24 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 633.07195 |
| 25 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 633.07195 |
| 26 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 27 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 28 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 392.58470 |
| 29 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 392.58470 |
| 30 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 392.58470 |
| 31 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 392.58470 |
| 32 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 392.58470 |
| 33 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 392.58470 |
| 34 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 35 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 36 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 513.83468 |
| 37 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 513.83468 |
| 38 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 513.83468 |
| 39 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 513.83468 |
| 40 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 513.83468 |
| 41 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 513.83468 |
| 42 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 43 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 44 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 622.96602 |
| 45 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 622.96602 |
| 46 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 622.96602 |
| 47 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 622.96602 |
| 48 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 622.96602 |
| 49 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 622.96602 |
| 50 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 51 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 52 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 381.37707 |
| 53 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 381.37707 |
| 54 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 381.37707 |
| 55 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 381.37707 |
| 56 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 381.37707 |
| 57 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 381.37707 |
| 58 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 59 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 60 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 496.63129 |
| 61 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 496.63129 |
| 62 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 496.63129 |
| 63 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 496.63129 |
| 64 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 496.63129 |
| 65 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 496.63129 |
| 66 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 67 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 68 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 617.90246 |
| 69 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 617.90246 |
| 70 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 617.90246 |
| 71 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 617.90246 |
| 72 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 617.90246 |
| 73 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 617.90246 |
| 74 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 75 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 76 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 361.99148 |
| 77 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 361.99148 |
| 78 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 361.99148 |
| 79 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 361.99148 |
| 80 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 361.99148 |
| 81 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 361.99148 |
| 82 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 83 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 84 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 495.78384 |
| 85 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 495.78384 |
| 86 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 495.78384 |
| 87 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 495.78384 |
| 88 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 495.78384 |
| 89 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 495.78384 |
| 90 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 91 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 92 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 609.74569 |
| 93 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 609.74569 |
| 94 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 609.74569 |
| 95 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 609.74569 |
| 96 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 609.74569 |
| 97 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 609.74569 |
| 98 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 99 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 100 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 360.76267 |
| 101 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 360.76267 |
| 102 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 360.76267 |
| 103 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 360.76267 |
| 104 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 360.76267 |
| 105 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 360.76267 |
| 106 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 107 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 108 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 470.55079 |
| 109 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 470.55079 |
| 110 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 470.55079 |
| 111 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 470.55079 |
| 112 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 470.55079 |
| 113 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 470.55079 |
| 114 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 737.58465 |
| 117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 737.58465 |
| 118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 737.58465 |
| 119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 737.58465 |
| 120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 737.58465 |
| 121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 737.58465 |
| 122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 479.95757 |
| 125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 479.95757 |
| 126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 479.95757 |
| 127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 479.95757 |
| 128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 479.95757 |
| 129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 479.95757 |
| 130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 607.09738 |
| 133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 607.09738 |
| 134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 607.09738 |
| 135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 607.09738 |
| 136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 607.09738 |
| 137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 607.09738 |
| 138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 738.49567 |
| 141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 738.49567 |
| 142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 738.49567 |
| 143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 738.49567 |
| 144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 738.49567 |
| 145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 738.49567 |
| 146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 482.73299 |
| 149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 482.73299 |
| 150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 482.73299 |
| 151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 482.73299 |
| 152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 482.73299 |
| 153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 482.73299 |
| 154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 600.57196 |
| 157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 600.57196 |
| 158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 600.57196 |
| 159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 600.57196 |
| 160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 600.57196 |
| 161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 600.57196 |
| 162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 619.23721 |
| 165 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 619.23721 |
| 166 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 619.23721 |
| 167 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Heating Design Air Flow Rate [ft3/min] | 619.23721 |
| 168 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Cooling Design Air Flow Rate [ft3/min] | 619.23721 |
| 169 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Main Design Air Flow Rate [ft3/min] | 619.23721 |
| 170 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 633.07195 |
| 173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 392.58470 |
| 174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 513.83468 |
| 175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 622.96602 |
| 176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 381.37707 |
| 177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 496.63129 |
| 178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 617.90246 |
| 179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 361.99148 |
| 180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 495.78384 |
| 181 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 609.74569 |
| 182 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 360.76267 |
| 183 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 470.55079 |
| 184 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 737.58465 |
| 185 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 479.95757 |
| 186 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 607.09738 |
| 187 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 738.49567 |
| 188 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 482.73299 |
| 189 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 600.57196 |
| 190 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Design Supply Air Flow Rate [ft3/min] | 619.23721 |
| 191 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 633.07195 |
| 192 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.96164 |
| 193 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.72460 |
| 194 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 633.07195 |
| 195 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 633.07195 |
| 196 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 633.07195 |
| 197 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 23539.66782 |
| 198 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.96164 |
| 199 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11098.00103 |
| 200 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 201 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 633.07195 |
| 202 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 633.07195 |
| 203 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 25317.68763 |
| 204 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 12762.70119 |
| 205 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 392.58470 |
| 206 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.30833 |
| 207 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
| 208 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 392.58470 |
| 209 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 392.58470 |
| 210 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 392.58470 |
| 211 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 15700.00614 |
| 212 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.30833 |
| 213 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 9027.18146 |
| 214 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 215 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 392.58470 |
| 216 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 392.58470 |
| 217 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 15700.00614 |
| 218 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 10381.25870 |
| 219 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 513.83468 |
| 220 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.70318 |
| 221 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70341 |
| 222 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 513.83468 |
| 223 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 513.83468 |
| 224 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 513.83468 |
| 225 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 20438.12880 |
| 226 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.70318 |
| 227 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11093.99462 |
| 228 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 229 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 513.83468 |
| 230 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 513.83468 |
| 231 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 20548.81968 |
| 232 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 12758.09383 |
| 233 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 622.96602 |
| 234 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.92375 |
| 235 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.72549 |
| 236 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 622.96602 |
| 237 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 622.96602 |
| 238 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 622.96602 |
| 239 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 23084.94519 |
| 240 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.92375 |
| 241 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11103.23811 |
| 242 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 243 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 622.96602 |
| 244 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 622.96602 |
| 245 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 24913.06411 |
| 246 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 12768.72381 |
| 247 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 381.37707 |
| 248 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.21059 |
| 249 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.71631 |
| 250 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 381.37707 |
| 251 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 381.37707 |
| 252 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 381.37707 |
| 253 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 14527.12643 |
| 254 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.21059 |
| 255 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 9028.37808 |
| 256 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 257 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 381.37707 |
| 258 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 381.37707 |
| 259 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 15252.08875 |
| 260 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 10382.63479 |
| 261 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 496.63129 |
| 262 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.65511 |
| 263 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
| 264 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 496.63129 |
| 265 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 496.63129 |
| 266 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 496.63129 |
| 267 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 19861.30799 |
| 268 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.65511 |
| 269 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11091.18184 |
| 270 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 271 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 496.63129 |
| 272 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 496.63129 |
| 273 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 19861.30799 |
| 274 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 12754.85912 |
| 275 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 617.90246 |
| 276 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.90567 |
| 277 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.72583 |
| 278 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 617.90246 |
| 279 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 617.90246 |
| 280 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 617.90246 |
| 281 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 22868.01139 |
| 282 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.90567 |
| 283 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 10018.95159 |
| 284 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 285 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 617.90246 |
| 286 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 617.90246 |
| 287 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 24710.93580 |
| 288 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 11521.79436 |
| 289 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 361.99148 |
| 290 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.16857 |
| 291 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.71102 |
| 292 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 361.99148 |
| 293 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 361.99148 |
| 294 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 361.99148 |
| 295 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 14022.83587 |
| 296 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.16857 |
| 297 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 7785.74921 |
| 298 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 299 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 361.99148 |
| 300 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 361.99148 |
| 301 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 14476.88183 |
| 302 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 8953.61161 |
| 303 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 495.78384 |
| 304 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.64654 |
| 305 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70293 |
| 306 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 495.78384 |
| 307 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 495.78384 |
| 308 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 495.78384 |
| 309 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 19758.43452 |
| 310 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.64654 |
| 311 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 10019.78412 |
| 312 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 313 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 495.78384 |
| 314 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 495.78384 |
| 315 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 19827.03438 |
| 316 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 11522.75176 |
| 317 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 609.74569 |
| 318 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.86527 |
| 319 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.72899 |
| 320 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 609.74569 |
| 321 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 609.74569 |
| 322 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 609.74569 |
| 323 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 22383.21119 |
| 324 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.86527 |
| 325 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 10023.57857 |
| 326 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 327 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 609.74569 |
| 328 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 609.74569 |
| 329 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 24384.34018 |
| 330 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 11527.11534 |
| 331 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 360.76267 |
| 332 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.13307 |
| 333 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.72005 |
| 334 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 360.76267 |
| 335 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 360.76267 |
| 336 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 360.76267 |
| 337 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 13596.84433 |
| 338 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.13307 |
| 339 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 7786.24743 |
| 340 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 341 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 360.76267 |
| 342 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 360.76267 |
| 343 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 14427.15228 |
| 344 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 8954.18455 |
| 345 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 470.55079 |
| 346 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.56820 |
| 347 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
| 348 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 470.55079 |
| 349 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 470.55079 |
| 350 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 470.55079 |
| 351 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 18818.43981 |
| 352 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.56820 |
| 353 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 10016.17088 |
| 354 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 355 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 470.55079 |
| 356 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 470.55079 |
| 357 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 18818.43981 |
| 358 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 11518.59649 |
| 359 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 737.58465 |
| 360 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 2.24484 |
| 361 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73037 |
| 362 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 737.58465 |
| 363 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 737.58465 |
| 364 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 737.58465 |
| 365 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 26938.11065 |
| 366 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 2.24484 |
| 367 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 12667.19180 |
| 368 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 369 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 737.58465 |
| 370 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 737.58465 |
| 371 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 29497.41861 |
| 372 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 14567.27056 |
| 373 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 479.95757 |
| 374 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.50688 |
| 375 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.72015 |
| 376 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 479.95757 |
| 377 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 479.95757 |
| 378 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 479.95757 |
| 379 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 18082.61178 |
| 380 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.50688 |
| 381 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 10433.31750 |
| 382 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 383 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 479.95757 |
| 384 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 479.95757 |
| 385 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 19194.03049 |
| 386 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 11998.31513 |
| 387 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 607.09738 |
| 388 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.96298 |
| 389 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.71060 |
| 390 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 607.09738 |
| 391 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 607.09738 |
| 392 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 607.09738 |
| 393 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 23555.80006 |
| 394 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.96298 |
| 395 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 12670.42778 |
| 396 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 397 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 607.09738 |
| 398 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 607.09738 |
| 399 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 24278.61466 |
| 400 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 14570.99196 |
| 401 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 738.49567 |
| 402 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 2.23712 |
| 403 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73162 |
| 404 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 738.49567 |
| 405 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 738.49567 |
| 406 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 738.49567 |
| 407 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 26845.45628 |
| 408 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 2.23712 |
| 409 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 12669.91205 |
| 410 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 411 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 738.49567 |
| 412 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 738.49567 |
| 413 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 29533.36765 |
| 414 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 14570.39889 |
| 415 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 482.73299 |
| 416 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.49014 |
| 417 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.72560 |
| 418 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 482.73299 |
| 419 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 482.73299 |
| 420 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 482.73299 |
| 421 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 17881.73806 |
| 422 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.49014 |
| 423 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 10433.02284 |
| 424 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 425 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 482.73299 |
| 426 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 482.73299 |
| 427 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 19305.47780 |
| 428 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 11997.97628 |
| 429 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 600.57196 |
| 430 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.93844 |
| 431 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.71105 |
| 432 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 600.57196 |
| 433 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 600.57196 |
| 434 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 600.57196 |
| 435 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 23261.27312 |
| 436 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.93844 |
| 437 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 12667.13448 |
| 438 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 439 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 600.57196 |
| 440 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 600.57196 |
| 441 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 24017.47089 |
| 442 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 14567.20464 |
| 443 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Rated Air Flow Rate [ft3/min] | 619.23721 |
| 444 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Gross Rated Total Cooling Capacity [ton] | 1.66186 |
| 445 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Gross Rated Sensible Heat Ratio | 0.77634 |
| 446 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNITHEATEDBSMT | Supply Air Flow Rate [ft3/min] | 619.23721 |
| 447 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNITHEATEDBSMT | Supply Air Flow Rate During Heating Operation [ft3/min] | 619.23721 |
| 448 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNITHEATEDBSMT | Supply Air Flow Rate During Cooling Operation [ft3/min] | 619.23721 |
| 449 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNITHEATEDBSMT | Nominal Heating Capacity [Btu/h] | 19942.35272 |
| 450 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNITHEATEDBSMT | Nominal Cooling Capacity [ton] | 1.66186 |
| 451 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNITHEATEDBSMT | Supplemental Heating Coil Nominal Capacity [Btu/h] | 9601.99987 |
| 452 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNITHEATEDBSMT | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 453 | Fan:OnOff | SUPPLY FAN_UNITHEATEDBSMT | Design Size Maximum Flow Rate [ft3/min] | 619.23721 |
| 454 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNITHEATEDBSMT | Design Size Rated Air Flow Rate [ft3/min] | 619.23721 |
| 455 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNITHEATEDBSMT | Design Size Gross Rated Heating Capacity [Btu/h] | 24763.90939 |
| 456 | Coil:Heating:Electric | SUPP HEATING COIL_UNITHEATEDBSMT | Design Size Nominal Capacity [Btu/h] | 12002.49984 |
| 457 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 458 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 459 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 460 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 461 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 462 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 463 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 464 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 465 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 466 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 467 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 468 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 469 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 470 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 471 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 472 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 473 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 474 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 475 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 476 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 477 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 478 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 479 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 480 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 481 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 482 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 483 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 484 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 485 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 486 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 487 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 488 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 489 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 490 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 491 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 492 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 493 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 494 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 495 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 496 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 497 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 498 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 499 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 500 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 501 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 502 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 503 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 504 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 505 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 506 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 507 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 508 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 509 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 510 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 511 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 512 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 513 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 514 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 515 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 516 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 517 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 518 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 519 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 520 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 521 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 522 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 523 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 524 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 525 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 526 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 527 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 528 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 529 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 530 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 531 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 532 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 533 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 534 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 535 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 536 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 537 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 538 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 539 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 540 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 541 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 542 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 543 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 544 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 545 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 546 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.9 | 3.63 | 12.39 | 13.00 | 12.29 | 12.44 |
| 2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.9 | 3.51 | 11.99 | 12.55 | 12.21 | -99999. |
| 3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 1.3 | 3.67 | 12.54 | 13.15 | 12.44 | 12.66 |
| 4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 1.3 | 3.56 | 12.15 | 12.73 | 12.39 | -99999. |
| 5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 1.6 | 3.67 | 12.52 | 13.14 | 12.43 | 12.64 |
| 6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 1.6 | 3.56 | 12.14 | 12.72 | 12.37 | -99999. |
| 7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.9 | 3.63 | 12.39 | 12.99 | 12.29 | 12.43 |
| 8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.8 | 3.51 | 11.98 | 12.54 | 12.20 | -99999. |
| 9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 1.2 | 3.65 | 12.44 | 13.05 | 12.34 | 12.51 |
| 10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 1.2 | 3.53 | 12.04 | 12.61 | 12.27 | -99999. |
| 11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 1.6 | 3.67 | 12.54 | 13.15 | 12.44 | 12.66 |
| 12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 1.6 | 3.56 | 12.15 | 12.73 | 12.39 | -99999. |
| 13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.8 | 3.63 | 12.38 | 12.99 | 12.29 | 12.42 |
| 14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.8 | 3.51 | 11.98 | 12.54 | 12.20 | -99999. |
| 15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 1.1 | 3.66 | 12.47 | 13.09 | 12.38 | 12.56 |
| 16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 1.1 | 3.54 | 12.08 | 12.65 | 12.31 | -99999. |
| 17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 1.6 | 3.67 | 12.53 | 13.15 | 12.44 | 12.65 |
| 18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 1.6 | 3.56 | 12.14 | 12.72 | 12.38 | -99999. |
| 19 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.8 | 3.62 | 12.37 | 12.97 | 12.27 | 12.40 |
| 20 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.8 | 3.51 | 11.96 | 12.52 | 12.18 | -99999. |
| 21 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 1.1 | 3.64 | 12.42 | 13.03 | 12.32 | 12.48 |
| 22 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 1.1 | 3.52 | 12.02 | 12.58 | 12.24 | -99999. |
| 23 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 1.5 | 3.67 | 12.54 | 13.15 | 12.44 | 12.66 |
| 24 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 1.5 | 3.56 | 12.15 | 12.73 | 12.39 | -99999. |
| 25 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 2.2 | 3.62 | 12.36 | 12.96 | 12.26 | 12.38 |
| 26 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 2.2 | 3.50 | 11.95 | 12.51 | 12.17 | -99999. |
| 27 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 1.5 | 3.64 | 12.42 | 13.03 | 12.32 | 12.48 |
| 28 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 1.4 | 3.52 | 12.02 | 12.58 | 12.24 | -99999. |
| 29 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.9 | 3.66 | 12.48 | 13.09 | 12.38 | 12.57 |
| 30 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.9 | 3.54 | 12.09 | 12.66 | 12.31 | -99999. |
| 31 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 2.2 | 3.62 | 12.35 | 12.95 | 12.25 | 12.37 |
| 32 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 2.1 | 3.50 | 11.94 | 12.49 | 12.16 | -99999. |
| 33 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 1.4 | 3.63 | 12.39 | 12.99 | 12.29 | 12.43 |
| 34 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 1.4 | 3.51 | 11.98 | 12.54 | 12.20 | -99999. |
| 35 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.9 | 3.66 | 12.47 | 13.09 | 12.38 | 12.56 |
| 36 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.9 | 3.54 | 12.08 | 12.65 | 12.31 | -99999. |
| 37 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | 1.6 | 3.54 | 12.09 | 12.66 | 11.98 | 11.98 |
| 38 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | 1.6 | 3.41 | 11.64 | 12.17 | 11.84 | -99999. |
| Component Type | Component Name | High Temperature Heating (net) Rating Capacity {Btu/h} | Low Temperature Heating (net) Rating Capacity {Btu/h} | HSPF {Btu/W-h} | Region Number | |
| 1 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 26136.9 | 14381.9 | 8.36 | 4 |
| 2 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 26301.1 | 14546.0 | 7.36 | 4 |
| 3 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 16208.0 | 8918.6 | 8.38 | 4 |
| 4 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 16309.7 | 9020.3 | 7.36 | 4 |
| 5 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 21213.8 | 11672.8 | 8.36 | 4 |
| 6 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 21346.8 | 11806.2 | 7.36 | 4 |
| 7 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 25719.0 | 14152.0 | 8.35 | 4 |
| 8 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 25880.7 | 14313.7 | 7.36 | 4 |
| 9 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 15745.7 | 8664.1 | 8.36 | 4 |
| 10 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 15844.6 | 8763.0 | 7.36 | 4 |
| 11 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 20503.7 | 11282.5 | 8.34 | 4 |
| 12 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 20632.7 | 11411.1 | 7.36 | 4 |
| 13 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 25510.5 | 14037.3 | 8.34 | 4 |
| 14 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 25670.9 | 14197.7 | 7.36 | 4 |
| 15 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 14945.2 | 8223.6 | 8.33 | 4 |
| 16 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 15039.1 | 8317.8 | 7.36 | 4 |
| 17 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 20468.6 | 11263.0 | 8.34 | 4 |
| 18 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 20597.2 | 11391.6 | 7.36 | 4 |
| 19 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 25173.4 | 13851.7 | 8.34 | 4 |
| 20 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 25331.4 | 14010.0 | 7.36 | 4 |
| 21 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 14894.1 | 8195.6 | 8.33 | 4 |
| 22 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 14987.6 | 8289.1 | 7.36 | 4 |
| 23 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 19427.2 | 10690.1 | 8.32 | 4 |
| 24 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 19549.4 | 10811.9 | 7.36 | 4 |
| 25 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 30451.8 | 16756.3 | 8.34 | 4 |
| 26 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 30643.2 | 16947.7 | 7.36 | 4 |
| 27 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 19814.8 | 10903.4 | 8.33 | 4 |
| 28 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 19939.4 | 11027.9 | 7.36 | 4 |
| 29 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 25064.2 | 13791.6 | 8.33 | 4 |
| 30 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 25221.5 | 13949.3 | 7.36 | 4 |
| 31 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 30488.9 | 16776.8 | 8.34 | 4 |
| 32 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 30680.4 | 16968.2 | 7.36 | 4 |
| 33 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 19930.2 | 10966.5 | 8.33 | 4 |
| 34 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 20055.4 | 11091.7 | 7.36 | 4 |
| 35 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 24794.7 | 13643.2 | 8.33 | 4 |
| 36 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 24950.2 | 13799.2 | 7.36 | 4 |
| 37 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNITHEATEDBSMT | 25565.1 | 14067.3 | 8.34 | 4 |
| 38 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNITHEATEDBSMT | 25725.8 | 14228.0 | 7.36 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 12/21 | 12/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
| 2 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 07/21 | 07/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
| 3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | No | SizingPeriod:DesignDay | ||
| 2 | No | SizingPeriod:DesignDay | ||
| 3 | No |
| NumberofWarmupDays | |
| 1 | 6 |
| 2 | 6 |
| 3 | 6 |
| Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
| 1 | 32.90 | 0.00 | DefaultMultipliers | Wetbulb | 0.50 | {C} | 13. | 140 | 413.4 | 0.00 | No | No |
| 2 | 105.44 | 13.30 | DefaultMultipliers | Wetbulb | 18.50 | {C} | 13. | 310 | 944.9 | 0.00 | No | No |
| DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
| 1 | 355 | 1232.8 | 0.1424 | 5.7719E-002 | 1.0 | 2.45 | -24. | ASHRAEClearSky |
| 2 | 202 | 1084.4 | 0.2082 | 0.1365 | 1.0 | -6.23 | 20.6 | ASHRAETau |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | HEATEDBSMT | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000157 | 0.000000297 | Pass | Pass | 0.079410458 | 0.148243747 | Pass | Pass |
| 2 | BREEZEWAY | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000005574 | 0.000003611 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000088 | 0.000000182 | Pass | Pass | 0.011177082 | 0.019710477 | Pass | Pass |
| 4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000042 | 0.000000062 | Pass | Pass | 0.014543346 | 0.025697447 | Pass | Pass |
| 5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000045 | 0.000000059 | Pass | Pass | 0.011183523 | 0.019724421 | Pass | Pass |
| 6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000080 | 0.000000170 | Pass | Pass | 0.011169582 | 0.019695212 | Pass | Pass |
| 7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000055 | 0.000000074 | Pass | Pass | 0.014539028 | 0.025690268 | Pass | Pass |
| 8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000065 | 0.000000092 | Pass | Pass | 0.011185755 | 0.019726863 | Pass | Pass |
| 9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000135 | 0.000000246 | Pass | Pass | 0.012337095 | 0.021611673 | Pass | Pass |
| 10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000077 | 0.000000164 | Pass | Pass | 0.017597188 | 0.030996307 | Pass | Pass |
| 11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000041 | 0.000000098 | Pass | Pass | 0.012336391 | 0.021609872 | Pass | Pass |
| 12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000130 | 0.000000239 | Pass | Pass | 0.012329242 | 0.021597630 | Pass | Pass |
| 13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000075 | 0.000000161 | Pass | Pass | 0.017594755 | 0.030992225 | Pass | Pass |
| 14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000028 | 0.000000059 | Pass | Pass | 0.012341709 | 0.021619657 | Pass | Pass |
| 15 | ATTIC | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000169003 | 0.000142525 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 16 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000049 | 0.000000068 | Pass | Pass | 0.009087287 | 0.015129265 | Pass | Pass |
| 17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000042 | 0.000000058 | Pass | Pass | 0.009084419 | 0.015124358 | Pass | Pass |
| 18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000075 | 0.000000139 | Pass | Pass | 0.009087296 | 0.015129405 | Pass | Pass |
| 19 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000032 | 0.000000043 | Pass | Pass | 0.011700095 | 0.019412717 | Pass | Pass |
| 20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000034 | 0.000000044 | Pass | Pass | 0.011699613 | 0.019411900 | Pass | Pass |
| 21 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000076 | 0.000000140 | Pass | Pass | 0.009085009 | 0.015125457 | Pass | Pass |
| 22 | HEATEDBSMT | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000017644 | 0.000087736 | Pass | Pass | 0.049609190 | 0.068841643 | Pass | Pass |
| 23 | BREEZEWAY | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.408135950 | 0.243954479 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 24 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003364 | 0.000007189 | Pass | Pass | 0.075002650 | 0.034046641 | Pass | Pass |
| 25 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000031734 | 0.000170229 | Pass | Pass | 0.057403250 | 0.031864934 | Pass | Pass |
| 26 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000025668 | 0.000151388 | Pass | Pass | 0.064238599 | 0.056038050 | Pass | Pass |
| 27 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000014527 | 0.000096421 | Pass | Pass | 0.074122667 | 0.034348128 | Pass | Pass |
| 28 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000022954 | 0.000145910 | Pass | Pass | 0.055455947 | 0.032191065 | Pass | Pass |
| 29 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000084238 | 0.000298393 | Pass | Pass | 0.062966854 | 0.057678895 | Pass | Pass |
| 30 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000022285 | 0.000116171 | Pass | Pass | 0.071659050 | 0.029693657 | Pass | Pass |
| 31 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000028022 | 0.000140881 | Pass | Pass | 0.052395387 | 0.029739345 | Pass | Pass |
| 32 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000061661 | 0.000285627 | Pass | Pass | 0.060764200 | 0.051449363 | Pass | Pass |
| 33 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003749 | 0.000008414 | Pass | Pass | 0.070768773 | 0.029127736 | Pass | Pass |
| 34 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000045728 | 0.000163167 | Pass | Pass | 0.050388395 | 0.029196276 | Pass | Pass |
| 35 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000095157 | 0.000292123 | Pass | Pass | 0.059162576 | 0.053095981 | Pass | Pass |
| 36 | ATTIC | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.561608536 | 0.419123669 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 37 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000075320 | 0.000271362 | Pass | Pass | 0.064161443 | 0.049994107 | Pass | Pass |
| 38 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000028583 | 0.000152973 | Pass | Pass | 0.064790368 | 0.049299645 | Pass | Pass |
| 39 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000046286 | 0.000260456 | Pass | Pass | 0.074259312 | 0.031300355 | Pass | Pass |
| 40 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003003 | 0.000006478 | Pass | Pass | 0.058165115 | 0.029588888 | Pass | Pass |
| 41 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000033919 | 0.000210840 | Pass | Pass | 0.058442846 | 0.031337416 | Pass | Pass |
| 42 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.000033221 | 0.000236600 | Pass | Pass | 0.074175028 | 0.030261486 | Pass | Pass |
| 43 | HEATEDBSMT | RunPeriod: ANNUAL | 0.019081958 | 0.034482699 | Pass | Pass | 0.177064220 | 0.546347812 | Pass | Pass |
| 44 | BREEZEWAY | RunPeriod: ANNUAL | 0.341907285 | 0.205794411 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 45 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.041668742 | 0.095100181 | Pass | Pass | 0.357333658 | 0.719039665 | Pass | Pass |
| 46 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.041681824 | 0.077793983 | Pass | Pass | 0.499554885 | 1.757821381 | Pass | Pass |
| 47 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.041667915 | 0.076504934 | Pass | Pass | 0.347503643 | 1.079184651 | Pass | Pass |
| 48 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.041349305 | 0.102558118 | Pass | Pass | 0.197085078 | 0.533533880 | Pass | Pass |
| 49 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000118134 | 0.000428948 | Pass | Pass | 0.142710131 | 0.170858091 | Pass | Pass |
| 50 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000128133 | 0.000487946 | Pass | Pass | 0.112886430 | 0.088314917 | Pass | Pass |
| 51 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.041668910 | 0.098125186 | Pass | Pass | 0.552010568 | 2.300920267 | Pass | Pass |
| 52 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.041668150 | 0.084884256 | Pass | Pass | 0.352453002 | 0.990934899 | Pass | Pass |
| 53 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.041698087 | 0.078519130 | Pass | Pass | 0.689924089 | 3.492837325 | Pass | Pass |
| 54 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.042062178 | 0.088401168 | Pass | Pass | 0.176869945 | 0.421320488 | Pass | Pass |
| 55 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000081257 | 0.000302600 | Pass | Pass | 0.267135026 | 0.890892600 | Pass | Pass |
| 56 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000088168 | 0.000333922 | Pass | Pass | 0.132687920 | 0.111958991 | Pass | Pass |
| 57 | ATTIC | RunPeriod: ANNUAL | 0.543643617 | 0.404751077 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 58 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000121367 | 0.000448336 | Pass | Pass | 0.131619109 | 0.096183821 | Pass | Pass |
| 59 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.041702793 | 0.073316636 | Pass | Pass | 0.279553843 | 0.773479557 | Pass | Pass |
| 60 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.041669113 | 0.096918975 | Pass | Pass | 0.449950887 | 1.956572242 | Pass | Pass |
| 61 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000113658 | 0.000402545 | Pass | Pass | 0.187594944 | 0.277991316 | Pass | Pass |
| 62 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.041668179 | 0.081545323 | Pass | Pass | 0.356368728 | 0.981410705 | Pass | Pass |
| 63 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.036562078 | 0.084173326 | Pass | Pass | 0.514606503 | 4.040103356 | Pass | Pass |
Report: Annual Heat Emissions Report
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Annual Heat Emissions Summary| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [kBtu] | 2593800.45 | 240115.70 | 82617.69 | 0.00 | 653530.53 | 3570075.63 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Heat Index Hours| Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
| HEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 5626.67 | 1747.33 | 1294.00 | 92.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 5783.67 | 1340.83 | 1000.17 | 635.33 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 5626.67 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 1747.33 | 1294.00 | 635.33 | 0.00 |
| Average | 8469.06 | 147.06 | 109.25 | 34.63 | 0.00 |
| Sum | 177850.33 | 3088.17 | 2294.17 | 727.33 | 0.00 |
| Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
| HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 10339.18 | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 217122.86 | 0.00 | 0.00 | 0.00 | 0.00 |
| Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
| HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 7508.57 | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 157680.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| HEATEDBSMT | 4533.67 | 4226.33 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 6512.83 | 2054.50 | 190.50 | 2.17 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8705.67 | 54.33 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8709.00 | 51.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8707.83 | 52.17 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8702.00 | 58.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8702.33 | 57.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8715.17 | 44.83 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8721.83 | 38.17 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8710.83 | 49.17 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8722.00 | 38.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8720.33 | 39.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8705.67 | 54.33 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8716.33 | 43.67 | 0.00 | 0.00 | 0.00 |
| ATTIC | 6026.17 | 1869.67 | 538.83 | 280.50 | 44.83 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8715.33 | 44.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8713.17 | 46.83 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8709.00 | 51.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8707.33 | 52.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8712.83 | 47.17 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8709.50 | 50.50 | 0.00 | 0.00 | 0.00 |
| Min | 4533.67 | 38.00 | 0.00 | 0.00 | 0.00 |
| Max | 8722.00 | 4226.33 | 538.83 | 280.50 | 44.83 |
| Average | 8279.94 | 429.73 | 34.73 | 13.46 | 2.13 |
| Sum | 173878.83 | 9024.33 | 729.33 | 282.67 | 44.83 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 11969.06 | 93.32 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 11978.11 | 84.27 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 11973.00 | 89.38 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11963.69 | 98.69 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 11964.72 | 97.66 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 11981.76 | 80.62 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12001.15 | 61.23 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 11991.01 | 71.37 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12002.41 | 59.97 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11999.89 | 62.49 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 11981.42 | 80.96 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 11991.02 | 71.36 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 11986.35 | 76.03 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 11983.75 | 78.63 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 11977.38 | 85.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 11976.84 | 85.54 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 11987.56 | 74.82 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 11978.42 | 83.96 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 12002.41 | 98.69 | 0.00 | 0.00 | 0.00 |
| Average | 10270.84 | 68.35 | 0.00 | 0.00 | 0.00 |
| Sum | 215687.55 | 1435.31 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8705.67 | 54.33 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8709.00 | 51.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8707.83 | 52.17 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8702.00 | 58.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8702.33 | 57.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8715.17 | 44.83 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8721.83 | 38.17 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8710.83 | 49.17 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8722.00 | 38.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8720.33 | 39.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8705.67 | 54.33 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8716.33 | 43.67 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8715.33 | 44.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8713.17 | 46.83 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8709.00 | 51.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8707.33 | 52.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8712.83 | 47.17 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8709.50 | 50.50 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8722.00 | 58.00 | 0.00 | 0.00 | 0.00 |
| Average | 7466.96 | 41.61 | 0.00 | 0.00 | 0.00 |
| Sum | 156806.17 | 873.83 | 0.00 | 0.00 | 0.00 |
| Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
| HEATEDBSMT | 0.00 | - | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| Average | 7508.57 | - | 0.00 | 0.00 | 0.00 |
| Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
| Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
| HEATEDBSMT | 0.00 | - | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| Average | 7508.57 | - | 0.00 | 0.00 | 0.00 |
| Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
| Cooling Setpoint Unmet Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] | Heating Setpoint Unmet Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupied Degree-Hours [°C·hr] | |
| HEATEDBSMT | 0.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.44 | 0.39 | 0.44 | 0.01 | 0.01 | 0.01 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.46 | 0.39 | 0.46 | 0.01 | 0.01 | 0.01 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.58 | 0.42 | 0.58 | 0.01 | 0.02 | 0.01 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.37 | 0.36 | 0.37 | 0.01 | 0.01 | 0.01 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.36 | 0.37 | 0.36 | 0.01 | 0.01 | 0.01 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.45 | 0.35 | 0.45 | 0.01 | 0.01 | 0.01 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.43 | 0.40 | 0.43 | 0.01 | 0.02 | 0.01 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.56 | 0.51 | 0.56 | 0.01 | 0.01 | 0.01 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.65 | 0.47 | 0.65 | 0.00 | 0.01 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.36 | 0.38 | 0.36 | 0.01 | 0.01 | 0.01 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.36 | 0.42 | 0.36 | 0.02 | 0.02 | 0.02 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.55 | 0.44 | 0.55 | 0.01 | 0.02 | 0.01 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.55 | 0.45 | 0.55 | 0.01 | 0.01 | 0.01 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.62 | 0.49 | 0.62 | 0.01 | 0.02 | 0.01 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.49 | 0.44 | 0.49 | 0.01 | 0.01 | 0.01 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.47 | 0.46 | 0.47 | 0.01 | 0.01 | 0.01 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.55 | 0.50 | 0.55 | 0.01 | 0.01 | 0.01 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.45 | 0.44 | 0.45 | 0.01 | 0.02 | 0.01 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 0.65 | 0.51 | 0.65 | 0.02 | 0.02 | 0.02 |
| Average | 0.42 | 0.37 | 0.41 | 0.01 | 0.01 | 0.01 |
| Sum | 8.91 | 7.70 | 8.71 | 0.18 | 0.24 | 0.18 |
| Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
| HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 0.00 | 0.00 | 0.00 | 0.00 |
| Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
| HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
SizingPeriod:DesignDay| Maximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
| TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 32.90 | 0.00 | 32.90 | Wetbulb [F] | 413.41 | 140.00 |
| TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 105.44 | 23.94 | 65.30 | Wetbulb [F] | 944.93 | 310.00 |
| Monthly Total Precipitation from .epw [in] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [in] | Monthly Total Roof Irrigation Depth [in] | Monthly Total Rain Collection Volume [ft3] | |
| Jan | 0.12 | 2 | |||
| Feb | 1.34 | 28 | |||
| Mar | 1.57 | 18 | |||
| Apr | 0.00 | 0 | |||
| May | 0.00 | 0 | |||
| Jun | 0.00 | 0 | |||
| Jul | 3.19 | 18 | |||
| Aug | 2.80 | 20 | |||
| Sep | 1.06 | 12 | |||
| Oct | 0.35 | 6 | |||
| Nov | 1.38 | 14 | |||
| Dec | 0.00 | 0 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Opaque Exterior| Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 180.00 | 90.00 | S |
| BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 90.00 | 90.00 | E |
| BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 0.00 | 90.00 | N |
| BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 270.00 | 90.00 | W |
| BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
| BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
| BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
| WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
| ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
| ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
| ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
| WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| BGWALL_LOWER_LDF | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 839.40 | 839.40 | 180.00 | 90.00 | S |
| BGWALL_LOWER_SDR | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 455.77 | 455.77 | 90.00 | 90.00 | E |
| BGWALL_LOWER_LDB | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 839.40 | 839.40 | 0.00 | 90.00 | N |
| BGWALL_LOWER_SDL | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 455.77 | 455.77 | 270.00 | 90.00 | W |
| BGFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
| iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 599.39 | 599.39 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
| WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
| FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
| WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
| FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 599.39 | 599.39 | 0.00 | 180.00 | |
| iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 180.00 | 0.00 |
| Construction | Frame and Divider | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.259 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.259 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.259 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.259 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.259 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.259 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.259 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.259 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.259 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.259 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.259 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.259 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.259 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
| Total or Average | 2126.74 | 0.651 | 0.259 | 0.883 | |||||||||||||||||
| North Total or Average | 531.68 | 0.651 | 0.259 | 0.883 | |||||||||||||||||
| Non-North Total or Average | 1595.05 | 0.651 | 0.259 | 0.883 |
| Frame and Divider | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
| DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
| DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
| DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
| DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
| DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
| DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
| DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
| DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
| DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
| DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
| DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
| DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
| DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
| DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
| DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
| DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
| DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
| DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
| Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
| WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
| WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
| WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
| WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.96 | 0.00 | 1.00 | 0.97 | 0.00 |
| WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
| WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.96 | 0.00 | 1.00 | 0.97 | 0.00 |
| WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
| WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
| WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
| WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
| WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.96 | 0.00 | 1.00 | 0.97 | 0.00 |
| WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
| WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.96 | 0.00 | 1.00 | 0.97 | 0.00 |
| WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.96 | 0.00 | 1.00 | 0.97 | 0.00 |
| WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
| WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.96 | 0.00 | 1.00 | 0.97 | 0.00 |
| WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
| WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
| WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
| WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [Btu/h-ft2] | Space Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
| LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.5693 | 1200.55 | 683.53 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 615.01 |
| LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| BASEMENT HARDWIRED LIGHTING | HEATEDBSMT | HEATEDBSMT | GENERAL | 0.3766 | 7794.39 | 2935.48 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 2641.24 |
| BASEMENT PLUG-IN LIGHTING | HEATEDBSMT | HEATEDBSMT | GENERAL | 0.1206 | 7794.39 | 939.71 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 845.52 |
| Interior Lighting Total | 0.3421 | 58808.69 | 20117.33 | 18100.85 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
| EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| Exterior Lighting Total | 1377.69 | 6034.31 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Central Plant| Type | Reference Capacity [Btu/h] | Reference Efficiency [Btuh/Btuh] | Rated Capacity [Btu/h] | Rated Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 23539.67 | 17056.73 | 6482.94 | 0.72 | 4.30 | |||
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 15700.01 | 11007.01 | 4693.00 | 0.70 | 4.30 | |||
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 20438.13 | 14376.40 | 6061.73 | 0.70 | 4.30 | |||
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 23084.95 | 16747.93 | 6337.01 | 0.73 | 4.30 | |||
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 14527.13 | 10405.98 | 4121.14 | 0.72 | 4.30 | |||
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 19861.31 | 13924.43 | 5936.88 | 0.70 | 4.30 | |||
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 22868.01 | 16598.39 | 6269.62 | 0.73 | 4.30 | |||
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 14022.84 | 9970.50 | 4052.34 | 0.71 | 4.30 | |||
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 19758.43 | 13888.88 | 5869.56 | 0.70 | 4.30 | |||
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 22383.21 | 16317.24 | 6065.98 | 0.73 | 4.30 | |||
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 13596.84 | 9790.40 | 3806.44 | 0.72 | 4.30 | |||
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 18818.44 | 13193.29 | 5625.15 | 0.70 | 4.30 | |||
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 26938.11 | 19674.73 | 7263.38 | 0.73 | 4.30 | |||
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 18082.61 | 13022.14 | 5060.48 | 0.72 | 4.30 | |||
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 23555.80 | 16738.84 | 6816.96 | 0.71 | 4.30 | |||
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 26845.46 | 19640.73 | 7204.72 | 0.73 | 4.30 | |||
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 17881.74 | 12974.93 | 4906.81 | 0.73 | 4.30 | |||
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 23261.27 | 16539.94 | 6721.33 | 0.71 | 4.30 | |||
| DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 19942.35 | 15482.01 | 4460.34 | 0.78 | 4.30 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.9 | 3.63 | 12.39 | 13.00 | 12.29 | 12.44 | |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 1.3 | 3.67 | 12.54 | 13.15 | 12.44 | 12.66 | |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 1.6 | 3.67 | 12.52 | 13.14 | 12.43 | 12.64 | |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.9 | 3.63 | 12.39 | 12.99 | 12.29 | 12.43 | |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 1.2 | 3.65 | 12.44 | 13.05 | 12.34 | 12.51 | |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 1.6 | 3.67 | 12.54 | 13.15 | 12.44 | 12.66 | |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.8 | 3.63 | 12.38 | 12.99 | 12.29 | 12.42 | |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 1.1 | 3.66 | 12.47 | 13.09 | 12.38 | 12.56 | |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 1.6 | 3.67 | 12.53 | 13.15 | 12.44 | 12.65 | |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.8 | 3.62 | 12.37 | 12.97 | 12.27 | 12.40 | |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 1.1 | 3.64 | 12.42 | 13.03 | 12.32 | 12.48 | |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 1.5 | 3.67 | 12.54 | 13.15 | 12.44 | 12.66 | |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 2.2 | 3.62 | 12.36 | 12.96 | 12.26 | 12.38 | |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 1.5 | 3.64 | 12.42 | 13.03 | 12.32 | 12.48 | |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.9 | 3.66 | 12.48 | 13.09 | 12.38 | 12.57 | |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 2.2 | 3.62 | 12.35 | 12.95 | 12.25 | 12.37 | |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 1.4 | 3.63 | 12.39 | 12.99 | 12.29 | 12.43 | |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.9 | 3.66 | 12.47 | 13.09 | 12.38 | 12.56 | |
| DX COOLING COIL_UNITHEATEDBSMT | 1.6 | 3.54 | 12.09 | 12.66 | 11.98 | 11.98 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP2 [Btuh/Btuh] | EER2 [Btu/W-h] | SEER2 User [Btu/W-h] | SEER2 Standard [Btu/W-h] | IEER2 [Btu/W-h] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.9 | 3.51 | 11.99 | 12.55 | 12.21 | |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.3 | 3.56 | 12.15 | 12.73 | 12.39 | |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.6 | 3.56 | 12.14 | 12.72 | 12.37 | |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.8 | 3.51 | 11.98 | 12.54 | 12.20 | |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.2 | 3.53 | 12.04 | 12.61 | 12.27 | |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.6 | 3.56 | 12.15 | 12.73 | 12.39 | |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.8 | 3.51 | 11.98 | 12.54 | 12.20 | |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.1 | 3.54 | 12.08 | 12.65 | 12.31 | |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.6 | 3.56 | 12.14 | 12.72 | 12.38 | |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.8 | 3.51 | 11.96 | 12.52 | 12.18 | |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.1 | 3.52 | 12.02 | 12.58 | 12.24 | |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.5 | 3.56 | 12.15 | 12.73 | 12.39 | |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 2.2 | 3.50 | 11.95 | 12.51 | 12.17 | |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.4 | 3.52 | 12.02 | 12.58 | 12.24 | |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.9 | 3.54 | 12.09 | 12.66 | 12.31 | |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 2.1 | 3.50 | 11.94 | 12.49 | 12.16 | |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.4 | 3.51 | 11.98 | 12.54 | 12.20 | |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.9 | 3.54 | 12.08 | 12.65 | 12.31 | |
| DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 1.6 | 3.41 | 11.64 | 12.17 | 11.84 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
| Coil Type | Rated Total Capacity [Btu/h] | Rated Sensible Capacity [Btu/h] | Rated Power[Btu/h] | Rated COP [Btuh/Btuh] | Rated Air Dry-bulb Temperature [F] | Rated Air Wet-bulb Temperature [F] | Rated Water Temperature [F] | Design Day used for Sizing | |
| None |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 26136.8 | 14381.9 | 8.36 | 4 |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 16208.0 | 8918.5 | 8.38 | 4 |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 21213.6 | 11672.9 | 8.36 | 4 |
| MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 25719.1 | 14152.1 | 8.35 | 4 |
| MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 15745.5 | 8664.1 | 8.36 | 4 |
| MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 20503.9 | 11282.4 | 8.34 | 4 |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 25510.4 | 14037.3 | 8.34 | 4 |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 14945.3 | 8223.7 | 8.33 | 4 |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 20468.5 | 11262.9 | 8.34 | 4 |
| MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 25173.3 | 13851.7 | 8.34 | 4 |
| MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 14893.9 | 8195.5 | 8.33 | 4 |
| MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 19427.3 | 10690.0 | 8.32 | 4 |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 30451.8 | 16756.3 | 8.34 | 4 |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 19815.0 | 10903.3 | 8.33 | 4 |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 25064.1 | 13791.7 | 8.33 | 4 |
| MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 30488.9 | 16776.7 | 8.34 | 4 |
| MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 19930.1 | 10966.6 | 8.33 | 4 |
| MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 24794.5 | 13643.3 | 8.33 | 4 |
| MAIN DX HEATING COIL_UNITHEATEDBSMT | Coil:Heating:DX:SingleSpeed | 25565.1 | 14067.4 | 8.34 | 4 |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF2 [Btu/W-h] | Region Number | |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 26301.0 | 14546.2 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 16309.8 | 9020.4 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 21346.9 | 11806.2 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 25880.7 | 14313.7 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 15844.5 | 8763.0 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 20632.7 | 11411.2 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 25670.7 | 14197.6 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 15039.2 | 8317.6 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 20597.1 | 11391.6 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 25331.4 | 14009.9 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 14987.5 | 8289.1 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 19549.4 | 10812.1 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 30643.1 | 16947.6 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 19939.5 | 11027.9 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 25221.6 | 13949.2 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 30680.5 | 16968.3 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 20055.3 | 11091.9 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 24950.3 | 13799.2 | 7.36 | 4 |
| MAIN DX HEATING COIL_UNITHEATEDBSMT | Coil:Heating:DX:SingleSpeed | 25725.8 | 14228.0 | 7.36 | 4 |
| Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 25317.69 | 3.84 | |
| SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 12762.70 | 1.00 | |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 15700.01 | 3.84 | |
| SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 10381.26 | 1.00 | |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 20548.82 | 3.84 | |
| SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 12758.09 | 1.00 | |
| MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 24913.06 | 3.84 | |
| SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 12768.72 | 1.00 | |
| MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 15252.09 | 3.84 | |
| SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 10382.63 | 1.00 | |
| MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 19861.31 | 3.84 | |
| SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 12754.86 | 1.00 | |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 24710.94 | 3.84 | |
| SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 11521.79 | 1.00 | |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 14476.88 | 3.84 | |
| SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 8953.61 | 1.00 | |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 19827.03 | 3.84 | |
| SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 11522.75 | 1.00 | |
| MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 24384.34 | 3.84 | |
| SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 11527.12 | 1.00 | |
| MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 14427.15 | 3.84 | |
| SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 8954.18 | 1.00 | |
| MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 18818.44 | 3.84 | |
| SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 11518.60 | 1.00 | |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 29497.42 | 3.84 | |
| SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 14567.27 | 1.00 | |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 19194.03 | 3.84 | |
| SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 11998.32 | 1.00 | |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 24278.61 | 3.84 | |
| SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 14570.99 | 1.00 | |
| MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 29533.37 | 3.84 | |
| SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | 14570.40 | 1.00 | |
| MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 19305.48 | 3.84 | |
| SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | 11997.98 | 1.00 | |
| MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 24017.47 | 3.84 | |
| SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | 14567.20 | 1.00 | |
| MAIN DX HEATING COIL_UNITHEATEDBSMT | Coil:Heating:DX:SingleSpeed | 24763.91 | 3.84 | |
| SUPP HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Electric | 12002.50 | 1.00 |
| Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| ZONE EXHAUST FAN_UNITHEATEDBSMT | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 59.99 | 42.86 | 0.71 | 1.00 | 8.10 | Ventilation | ||
| SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 633.07 | 238.79 | 0.38 | 1.00 | 1.94 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 392.58 | 148.08 | 0.38 | 1.00 | 2.40 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 513.83 | 193.81 | 0.38 | 1.00 | 2.11 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 622.96 | 234.97 | 0.38 | 1.00 | 1.95 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 381.38 | 143.85 | 0.38 | 1.00 | 2.43 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 496.64 | 187.33 | 0.38 | 1.00 | 2.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 617.90 | 233.07 | 0.38 | 1.00 | 1.96 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 362.00 | 136.54 | 0.38 | 1.00 | 2.50 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 495.78 | 187.00 | 0.38 | 1.00 | 2.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 609.74 | 229.99 | 0.38 | 1.00 | 1.97 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 360.75 | 136.07 | 0.38 | 1.00 | 2.50 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 470.56 | 177.49 | 0.38 | 1.00 | 2.20 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 737.59 | 278.21 | 0.38 | 1.00 | 1.83 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 479.95 | 181.03 | 0.38 | 1.00 | 2.18 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 607.09 | 228.99 | 0.38 | 1.00 | 1.97 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 738.49 | 278.55 | 0.38 | 1.00 | 1.83 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 482.74 | 182.09 | 0.38 | 1.00 | 2.17 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 600.56 | 226.53 | 0.38 | 1.00 | 1.98 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.50 | 0.06 | 619.23 | 233.57 | 0.38 | 1.00 | 1.96 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 |
| Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
| MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Zone Sensible Cooling| Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 13500.41 | 13500.41 | 11.25 | 633.074 | 633.074 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 75.00 | 75.00 | 0.00730 | 101.69 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8372.12 | 8372.12 | 6.97 | 392.582 | 392.582 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 75.00 | 75.00 | 0.00718 | 104.96 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 10957.62 | 10957.62 | 9.13 | 513.828 | 513.828 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 75.00 | 75.00 | 0.00722 | 105.44 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 13284.63 | 13284.63 | 11.07 | 622.956 | 622.956 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 75.00 | 75.00 | 0.00731 | 101.29 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8132.89 | 8132.89 | 6.77 | 381.382 | 381.382 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00730 | 99.10 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 10419.64 | 10419.64 | 8.68 | 488.598 | 488.598 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 75.00 | 75.00 | 0.00721 | 105.44 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 13176.58 | 13176.58 | 10.98 | 617.902 | 617.902 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 75.00 | 75.00 | 0.00740 | 101.29 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7719.41 | 7719.41 | 6.43 | 361.998 | 361.998 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 75.00 | 0.00741 | 100.09 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 10572.48 | 10572.48 | 8.81 | 495.779 | 495.779 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 75.00 | 75.00 | 0.00731 | 105.44 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 13002.38 | 13002.38 | 10.83 | 609.736 | 609.736 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00743 | 100.49 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7692.83 | 7692.83 | 6.41 | 360.754 | 360.754 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 75.00 | 75.00 | 0.00745 | 97.90 | 0.00562 | 59.993 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 10034.70 | 10034.70 | 8.36 | 470.559 | 470.559 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 75.00 | 75.00 | 0.00731 | 105.44 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 12807.56 | 12807.56 | 10.67 | 600.562 | 600.562 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 75.00 | 75.00 | 0.00726 | 104.72 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 12946.81 | 12946.81 | 10.78 | 607.092 | 607.092 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 75.00 | 75.00 | 0.00726 | 104.96 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 15729.19 | 15729.19 | 13.10 | 737.589 | 737.589 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 75.00 | 75.00 | 0.00734 | 101.29 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 10294.28 | 10294.28 | 8.57 | 482.738 | 482.738 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00733 | 99.10 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 10234.92 | 10234.92 | 8.53 | 479.951 | 479.951 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00732 | 100.49 | 0.00563 | 59.993 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 15748.33 | 15748.33 | 13.12 | 738.488 | 738.488 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 75.00 | 75.00 | 0.00736 | 100.89 | 0.00563 | 59.993 | 0.00 |
| HEATEDBSMT | 13204.36 | 13204.36 | 1.69 | 619.227 | 619.227 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00774 | 96.10 | 0.00562 | 59.993 | 0.00 |
| Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8922.72 | 8922.72 | 7.43 | 497.022 | 497.022 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00731 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6821.28 | 6821.28 | 5.68 | 379.971 | 379.971 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00720 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8918.65 | 8918.65 | 7.43 | 496.795 | 496.795 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00731 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8928.03 | 8928.03 | 7.44 | 497.318 | 497.318 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00732 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 6822.49 | 6822.49 | 5.68 | 380.038 | 380.038 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00720 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8915.80 | 8915.80 | 7.43 | 496.636 | 496.636 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00731 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7827.65 | 7827.65 | 6.52 | 436.050 | 436.050 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00745 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5561.43 | 5561.43 | 4.63 | 309.811 | 309.811 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00733 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7828.50 | 7828.50 | 6.52 | 436.097 | 436.097 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00745 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7832.35 | 7832.35 | 6.52 | 436.312 | 436.312 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00745 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5561.93 | 5561.93 | 4.63 | 309.840 | 309.840 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00733 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7824.83 | 7824.83 | 6.52 | 435.893 | 435.893 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00745 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 10515.05 | 10515.05 | 8.76 | 585.719 | 585.719 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00740 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 10518.39 | 10518.39 | 8.76 | 585.905 | 585.905 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00740 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 10515.10 | 10515.10 | 8.76 | 585.723 | 585.723 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00740 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8247.90 | 8247.90 | 6.87 | 459.439 | 459.439 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00731 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8248.20 | 8248.20 | 6.87 | 459.456 | 459.456 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00731 | 32.90 | 0.00432 | 59.993 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 10517.86 | 10517.86 | 8.76 | 585.876 | 585.876 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00740 | 32.90 | 0.00432 | 59.993 | 0.00 |
| HEATEDBSMT | 7404.36 | 7404.36 | 0.95 | 412.540 | 412.540 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 72.00 | 72.00 | 0.00832 | 32.90 | 0.00432 | 59.993 | 0.00 |
| Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 633.07 | 633.07 | 497.02 | 497.02 | 633.0742 | 633.0742 | 633.0742 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 392.58 | 392.58 | 379.97 | 379.97 | 392.5820 | 392.5820 | 392.5820 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 513.83 | 513.83 | 496.80 | 496.80 | 513.8276 | 513.8276 | 513.8276 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 622.96 | 622.96 | 497.32 | 497.32 | 622.9565 | 622.9565 | 622.9565 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 381.38 | 381.38 | 380.04 | 380.04 | 381.3817 | 381.3817 | 381.3817 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 488.60 | 488.60 | 496.64 | 496.64 | 496.6362 | 496.6362 | 496.6362 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 617.90 | 617.90 | 436.05 | 436.05 | 617.9022 | 617.9022 | 617.9022 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 362.00 | 362.00 | 309.81 | 309.81 | 361.9975 | 361.9975 | 361.9975 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 495.78 | 495.78 | 436.10 | 436.10 | 495.7792 | 495.7792 | 495.7792 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 609.74 | 609.74 | 436.31 | 436.31 | 609.7356 | 609.7356 | 609.7356 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 360.75 | 360.75 | 309.84 | 309.84 | 360.7540 | 360.7540 | 360.7540 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 470.56 | 470.56 | 435.89 | 435.89 | 470.5591 | 470.5591 | 470.5591 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 737.59 | 737.59 | 585.72 | 585.72 | 737.5892 | 737.5892 | 737.5892 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 479.95 | 479.95 | 459.46 | 459.46 | 479.9508 | 479.9508 | 479.9508 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 607.09 | 607.09 | 585.91 | 585.91 | 607.0919 | 607.0919 | 607.0919 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 738.49 | 738.49 | 585.88 | 585.88 | 738.4881 | 738.4881 | 738.4881 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 482.74 | 482.74 | 459.44 | 459.44 | 482.7376 | 482.7376 | 482.7376 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 600.56 | 600.56 | 585.72 | 585.72 | 600.5620 | 600.5620 | 600.5620 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNITHEATEDBSMT | 619.23 | 619.23 | 412.54 | 412.54 | 619.2268 | 619.2268 | 619.2268 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 23539.668 | 17056.727 | 633.074165 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 19875.82 | 19875.82 | 633.074165 | 78.82 | 58.91 | 0.00713867 | 53.60 | 49.16 | 0.00713867 | 101.69 | 0.00562786 | 64.28 | 9.4765 | 75.00 | 0.00729180 | 35.9414 | 13491.85 | 0.00 | 23535.63 | 16346.64 |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 25317.688 | 25317.688 | 633.074165 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 25317.69 | 13704.51 | 633.074165 | 68.29 | 54.88 | 0.00703073 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 9.4765 | 72.00 | 0.00731497 | 39.8863 | 8922.72 | 0.00 | 25350.96 | 25350.96 |
| SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 12762.701 | 12762.701 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 12762.70 | 12762.70 | -999. | 68.29 | 54.88 | 0.00703073 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00731497 | 39.8863 | 8922.72 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 15700.006 | 11007.011 | 392.581994 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 13000.83 | 13000.83 | 392.581994 | 80.87 | 59.32 | 0.00694177 | 53.60 | 48.79 | 0.00694177 | 104.96 | 0.00563070 | 65.30 | 15.2817 | 75.00 | 0.00717569 | 35.3748 | 8353.09 | 0.00 | 15697.31 | 10582.05 |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 15700.006 | 15700.006 | 392.581994 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 15700.01 | 9387.02 | 392.581994 | 66.02 | 53.55 | 0.00676106 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 15.2817 | 72.00 | 0.00720218 | 39.2780 | 6821.28 | 0.00 | 15720.64 | 15720.64 |
| SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 10381.259 | 10381.259 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 10381.26 | 10381.26 | -999. | 66.02 | 53.55 | 0.00676106 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00720218 | 39.2780 | 6821.28 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 20438.129 | 14376.396 | 513.827607 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 16784.58 | 16784.58 | 513.827607 | 79.85 | 59.10 | 0.00703348 | 53.60 | 48.96 | 0.00703348 | 105.44 | 0.00563111 | 65.44 | 11.6758 | 75.00 | 0.00721886 | 35.5851 | 10957.62 | 0.00 | 20434.62 | 13816.38 |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 20548.820 | 20548.820 | 513.827607 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 20548.82 | 11563.75 | 513.827607 | 67.43 | 54.44 | 0.00696455 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 11.6758 | 72.00 | 0.00731472 | 39.8850 | 8918.65 | 0.00 | 20575.82 | 20575.82 |
| SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 12758.094 | 12758.094 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 12758.09 | 12758.09 | -999. | 67.43 | 54.44 | 0.00696455 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00731472 | 39.8850 | 8918.65 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 23084.945 | 16747.934 | 622.956468 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 19560.65 | 19560.65 | 622.956468 | 78.83 | 58.93 | 0.00715208 | 53.60 | 49.18 | 0.00715208 | 101.29 | 0.00562752 | 64.15 | 9.6304 | 75.00 | 0.00729408 | 35.9525 | 13274.43 | 0.00 | 23080.99 | 16050.97 |
| MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 24913.064 | 24913.064 | 622.956468 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 24913.06 | 13522.87 | 622.956468 | 68.23 | 54.85 | 0.00702641 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 9.6304 | 72.00 | 0.00731529 | 39.8880 | 8928.03 | 0.00 | 24945.80 | 24945.80 |
| SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 12768.724 | 12768.724 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 12768.72 | 12768.72 | -999. | 68.23 | 54.85 | 0.00702641 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00731529 | 39.8880 | 8928.03 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 14527.126 | 10405.982 | 381.381724 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 12569.99 | 12569.99 | 381.381724 | 80.08 | 59.19 | 0.00703347 | 53.60 | 48.96 | 0.00703347 | 99.10 | 0.00562563 | 63.46 | 15.7305 | 75.00 | 0.00716618 | 35.3285 | 7909.15 | 0.00 | 14524.63 | 9981.23 |
| MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 15252.089 | 15252.089 | 381.381724 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 15252.09 | 9185.95 | 381.381724 | 65.85 | 53.46 | 0.00674820 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 15.7305 | 72.00 | 0.00720229 | 39.2786 | 6822.49 | 0.00 | 15272.13 | 15272.13 |
| SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 10382.635 | 10382.635 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 10382.63 | 10382.63 | -999. | 65.85 | 53.46 | 0.00674820 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00720229 | 39.2786 | 6822.49 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 19861.308 | 13924.430 | 496.636232 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 16321.28 | 16321.28 | 496.636232 | 80.03 | 59.14 | 0.00701348 | 53.60 | 48.92 | 0.00701348 | 105.44 | 0.00563111 | 65.44 | 12.0799 | 75.00 | 0.00720697 | 35.5271 | 10419.64 | 0.00 | 19857.90 | 13386.84 |
| MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 19861.308 | 19861.308 | 496.636232 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 19861.31 | 11255.12 | 496.636232 | 67.27 | 54.36 | 0.00695227 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 12.0799 | 72.00 | 0.00731455 | 39.8840 | 8915.80 | 0.00 | 19887.41 | 19887.41 |
| SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 12754.859 | 12754.859 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 12754.86 | 12754.86 | -999. | 67.27 | 54.36 | 0.00695227 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00731455 | 39.8840 | 8915.80 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 22868.011 | 16598.389 | 617.902207 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 19420.18 | 19420.18 | 617.902207 | 78.85 | 59.05 | 0.00722920 | 53.60 | 49.33 | 0.00722920 | 101.29 | 0.00562752 | 64.15 | 9.7092 | 75.00 | 0.00738084 | 36.3757 | 13155.05 | 0.00 | 22864.09 | 15899.52 |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 24710.936 | 24710.936 | 617.902207 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 24710.94 | 13431.52 | 617.902207 | 68.20 | 55.04 | 0.00714167 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 9.7092 | 72.00 | 0.00744556 | 40.5885 | 7827.65 | 0.00 | 24743.41 | 24743.41 |
| SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 11521.794 | 11521.794 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 11521.79 | 11521.79 | -999. | 68.20 | 55.04 | 0.00714167 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00744556 | 40.5885 | 7827.65 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 14022.836 | 9970.500 | 361.997510 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 12098.65 | 12098.65 | 361.997510 | 80.45 | 59.44 | 0.00711639 | 53.60 | 49.12 | 0.00711639 | 100.09 | 0.00562649 | 63.77 | 16.5729 | 75.00 | 0.00728684 | 35.9172 | 7619.44 | 0.00 | 14020.43 | 9570.44 |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 14476.882 | 14476.882 | 361.997510 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 14476.88 | 8837.62 | 361.997510 | 65.52 | 53.47 | 0.00683103 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 16.5729 | 72.00 | 0.00733073 | 39.9694 | 5561.43 | 0.00 | 14495.91 | 14495.91 |
| SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 8953.612 | 8953.612 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 8953.61 | 8953.61 | -999. | 65.52 | 53.47 | 0.00683103 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00733073 | 39.9694 | 5561.43 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 19758.435 | 13888.878 | 495.779213 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 16276.75 | 16276.75 | 495.779213 | 79.98 | 59.27 | 0.00711036 | 53.60 | 49.11 | 0.00711036 | 105.44 | 0.00563111 | 65.44 | 12.1008 | 75.00 | 0.00731400 | 36.0494 | 10572.48 | 0.00 | 19755.05 | 13347.87 |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 19827.034 | 19827.034 | 495.779213 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 19827.03 | 11239.26 | 495.779213 | 67.27 | 54.55 | 0.00706685 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 12.1008 | 72.00 | 0.00744561 | 40.5887 | 7828.50 | 0.00 | 19853.09 | 19853.09 |
| SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 11522.752 | 11522.752 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 11522.75 | 11522.75 | -999. | 67.27 | 54.55 | 0.00706685 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00744561 | 40.5887 | 7828.50 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 22383.211 | 16317.236 | 609.735613 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 19130.47 | 19130.47 | 609.735613 | 78.80 | 59.07 | 0.00724957 | 53.60 | 49.37 | 0.00724957 | 100.49 | 0.00562683 | 63.90 | 9.8392 | 75.00 | 0.00741800 | 36.5569 | 12987.86 | 0.00 | 22379.37 | 15628.26 |
| MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 24384.340 | 24384.340 | 609.735613 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 24384.34 | 13284.92 | 609.735613 | 68.15 | 55.01 | 0.00713784 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 9.8392 | 72.00 | 0.00744584 | 40.5899 | 7832.35 | 0.00 | 24416.38 | 24416.38 |
| SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 11527.115 | 11527.115 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 11527.12 | 11527.12 | -999. | 68.15 | 55.01 | 0.00713784 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00744584 | 40.5899 | 7832.35 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 13596.844 | 9790.401 | 360.754012 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 11900.21 | 11900.20 | 360.754012 | 80.10 | 59.37 | 0.00714616 | 53.60 | 49.17 | 0.00714616 | 97.90 | 0.00562460 | 63.07 | 16.6300 | 75.00 | 0.00741689 | 36.5517 | 7627.26 | 0.00 | 13594.51 | 9388.88 |
| MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 14427.152 | 14427.152 | 360.754012 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 14427.15 | 8815.30 | 360.754012 | 65.50 | 53.46 | 0.00682935 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 16.6300 | 72.00 | 0.00733077 | 39.9696 | 5561.93 | 0.00 | 14446.11 | 14446.11 |
| SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 8954.185 | 8954.185 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 8954.18 | 8954.18 | -999. | 65.50 | 53.46 | 0.00682935 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00733077 | 39.9696 | 5561.93 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 18818.440 | 13193.292 | 470.559091 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 15514.31 | 15514.31 | 470.559091 | 80.17 | 59.31 | 0.00709183 | 53.60 | 49.07 | 0.00709183 | 105.44 | 0.00563111 | 65.44 | 12.7494 | 75.00 | 0.00730528 | 36.0069 | 10034.70 | 0.00 | 18815.21 | 12683.93 |
| MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 18818.440 | 18818.440 | 470.559091 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 18818.44 | 10786.52 | 470.559091 | 67.01 | 54.42 | 0.00704637 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 12.7494 | 72.00 | 0.00744540 | 40.5876 | 7824.83 | 0.00 | 18843.17 | 18843.17 |
| SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 11518.597 | 11518.597 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 11518.60 | 11518.60 | -999. | 67.01 | 54.42 | 0.00704637 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00744540 | 40.5876 | 7824.83 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 26938.111 | 19674.729 | 737.589227 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 22800.80 | 22800.80 | 737.589227 | 78.43 | 58.87 | 0.00720216 | 53.60 | 49.28 | 0.00720216 | 101.29 | 0.00562752 | 64.15 | 8.1337 | 75.00 | 0.00732242 | 36.0906 | 15711.28 | 0.00 | 26933.49 | 18844.56 |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 29497.419 | 29497.419 | 737.589227 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 29497.42 | 15580.79 | 737.589227 | 68.82 | 55.28 | 0.00714878 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 8.1337 | 72.00 | 0.00739963 | 40.3425 | 10515.10 | 0.00 | 29536.18 | 29536.18 |
| SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 14567.271 | 14567.271 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 14567.27 | 14567.27 | -999. | 68.82 | 55.28 | 0.00714878 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00739963 | 40.3425 | 10515.10 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 18082.612 | 13022.136 | 479.950815 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 15460.12 | 15460.12 | 479.950815 | 79.48 | 59.09 | 0.00710767 | 53.60 | 49.10 | 0.00710767 | 100.49 | 0.00562683 | 63.90 | 12.4999 | 75.00 | 0.00722774 | 35.6292 | 10129.28 | 0.00 | 18079.51 | 12488.09 |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 19194.030 | 19194.030 | 479.950815 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 19194.03 | 10955.47 | 479.950815 | 67.11 | 54.27 | 0.00693654 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 12.4999 | 72.00 | 0.00731095 | 39.8643 | 8248.20 | 0.00 | 19219.25 | 19219.25 |
| SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 11998.315 | 11998.315 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 11998.32 | 11998.32 | -999. | 67.11 | 54.27 | 0.00693654 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00731095 | 39.8643 | 8248.20 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 23555.800 | 16738.837 | 607.091924 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 19385.30 | 19385.30 | 607.091924 | 79.25 | 58.99 | 0.00709569 | 53.60 | 49.08 | 0.00709569 | 104.96 | 0.00563070 | 65.30 | 9.8821 | 75.00 | 0.00725426 | 35.7575 | 12928.37 | 0.00 | 23551.76 | 16067.19 |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 24278.615 | 24278.615 | 607.091924 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 24278.61 | 13238.06 | 607.091924 | 68.13 | 54.93 | 0.00709500 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 9.8821 | 72.00 | 0.00739978 | 40.3433 | 10518.39 | 0.00 | 24310.52 | 24310.52 |
| SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 14570.992 | 14570.992 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 14570.99 | 14570.99 | -999. | 68.13 | 54.93 | 0.00709500 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00739978 | 40.3433 | 10518.39 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 26845.456 | 19640.734 | 738.488141 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 22796.93 | 22796.93 | 738.488141 | 78.40 | 58.88 | 0.00721646 | 53.60 | 49.30 | 0.00721646 | 100.89 | 0.00562717 | 64.03 | 8.1238 | 75.00 | 0.00734178 | 36.1850 | 15740.31 | 0.00 | 26840.85 | 18802.38 |
| MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 29533.368 | 29533.368 | 738.488141 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 29533.37 | 15596.93 | 738.488141 | 68.82 | 55.28 | 0.00714921 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 8.1238 | 72.00 | 0.00739976 | 40.3432 | 10517.86 | 0.00 | 29572.18 | 29572.18 |
| SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 14570.399 | 14570.399 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 14570.40 | 14570.40 | -999. | 68.82 | 55.28 | 0.00714921 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00739976 | 40.3432 | 10517.86 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 17881.738 | 12974.930 | 482.737579 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 15434.84 | 15434.84 | 482.737579 | 79.29 | 59.04 | 0.00712136 | 53.60 | 49.13 | 0.00712136 | 99.10 | 0.00562563 | 63.46 | 12.4277 | 75.00 | 0.00725459 | 35.7602 | 10142.82 | 0.00 | 17878.67 | 12435.00 |
| MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 19305.478 | 19305.478 | 482.737579 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 19305.48 | 11005.50 | 482.737579 | 67.14 | 54.29 | 0.00693868 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 12.4277 | 72.00 | 0.00731094 | 39.8642 | 8247.90 | 0.00 | 19330.85 | 19330.85 |
| SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 11997.976 | 11997.976 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 11997.98 | 11997.98 | -999. | 67.14 | 54.29 | 0.00693868 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00731094 | 39.8642 | 8247.90 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 23261.273 | 16539.942 | 600.561968 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 19182.93 | 19182.93 | 600.561968 | 79.26 | 58.99 | 0.00709384 | 53.60 | 49.07 | 0.00709384 | 104.72 | 0.00563048 | 65.22 | 9.9895 | 75.00 | 0.00725400 | 35.7562 | 12797.40 | 0.00 | 23257.28 | 15876.28 |
| MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 24017.471 | 24017.471 | 600.561968 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 24017.47 | 13120.83 | 600.561968 | 68.09 | 54.91 | 0.00709155 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 9.9895 | 72.00 | 0.00739963 | 40.3425 | 10515.05 | 0.00 | 24049.03 | 24049.03 |
| SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 14567.205 | 14567.205 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 14567.20 | 14567.20 | -999. | 68.09 | 54.91 | 0.00709155 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00739963 | 40.3425 | 10515.05 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | 19942.353 | 15482.009 | 619.226822 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 17657.16 | 17574.35 | 619.226822 | 78.34 | 59.34 | 0.00753283 | 53.60 | 49.83 | 0.00750000 | 96.10 | 0.00562306 | 62.49 | 9.6884 | 75.00 | 0.00773572 | 38.1041 | 13171.35 | 0.00 | 19938.93 | 14756.63 |
| MAIN DX HEATING COIL_UNITHEATEDBSMT | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | 24763.909 | 24763.909 | 619.226822 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 24763.91 | 13453.59 | 619.226822 | 68.21 | 56.34 | 0.00793065 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 9.6884 | 72.00 | 0.00831847 | 45.2795 | 7404.36 | 0.00 | 24796.45 | 24796.45 |
| SUPP HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | 12002.500 | 12002.500 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 12002.50 | 12002.50 | -999. | 68.21 | 56.34 | 0.00793065 | 90.00 | 63.89 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | -999.000 | 72.00 | 0.00831847 | 45.2795 | 7404.36 | 0.00 | -999.0 | -999.0 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 23539.668 | 17056.727 | 633.074165 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 633.074165 | 0.72015134 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | Sensible | 19875.82 | 19875.82 | 0.8444 | 0.72015134 | 633.074165 | 78.82 | 58.91 | 0.00713867 | 10.6 | 53.60 | 49.16 | 0.00713867 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 814.755 | 19061.06 | 101.69 | 0.00562786 | 64.28 | 59.99331119 | 9.4765 | 75.00 | 0.00729683 | 75.00 | 0.00729180 | 35.9414 | 13491.85 | 0.00 | 23535.63 | 16346.64 | 0.69171081 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.07 | 53.06 | 0.00855175 | 8.0 | |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 25317.688 | 25317.688 | 633.074165 | -999. | -999.00 | -999.0000 | 1.00000 | 0.93525 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 633.074165 | 0.72015134 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 25317.69 | 13704.51 | 1.0000 | 0.72015134 | 633.074165 | 68.29 | 54.88 | 0.00703073 | 9.1 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 25317.69 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 9.4765 | 72.00 | 0.00731497 | 72.00 | 0.00731497 | 39.8863 | 8922.72 | 0.00 | 25350.96 | 25350.96 | 0.70742604 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 12762.701 | 12762.701 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 633.074165 | 0.72015134 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 12762.70 | 12762.70 | 1.0000 | -0.240765E+04 | -999. | 68.29 | 54.88 | 0.00703073 | 9.1 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 12762.70 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00731497 | 72.00 | 0.00731497 | 39.8863 | 8922.72 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15700.006 | 11007.011 | 392.581994 | -999. | -999.00 | -999.0000 | 1.00000 | 0.97585 | 0.2431 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 392.581994 | 0.44658030 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 13000.83 | 13000.83 | 0.8281 | 0.44658030 | 392.581994 | 80.87 | 59.32 | 0.00694177 | 10.7 | 53.60 | 48.79 | 0.00694177 | 7.1 | -999. | -999.0 | -999.0 | -999.0 | 505.246 | 12495.59 | 104.96 | 0.00563070 | 65.30 | 59.99331119 | 15.2817 | 75.00 | 0.00717827 | 75.00 | 0.00717569 | 35.3748 | 8353.09 | 0.00 | 15697.31 | 10582.05 | 0.42894375 | 80.00 | 67.00 | 0.01118466 | 13.2 | 51.87 | 51.83 | 0.00816359 | 7.6 | |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 15700.006 | 15700.006 | 392.581994 | -999. | -999.00 | -999.0000 | 1.00000 | 0.86957 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 392.581994 | 0.44658030 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 15700.01 | 9387.02 | 1.0000 | 0.44658030 | 392.581994 | 66.02 | 53.55 | 0.00676106 | 8.6 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 15700.01 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 15.2817 | 72.00 | 0.00720218 | 72.00 | 0.00720218 | 39.2780 | 6821.28 | 0.00 | 15720.64 | 15720.64 | 0.43868909 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 10381.259 | 10381.259 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 392.581994 | 0.44658030 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 10381.26 | 10381.26 | 1.0000 | -0.240765E+04 | -999. | 66.02 | 53.55 | 0.00676106 | 8.6 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10381.26 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00720218 | 72.00 | 0.00720218 | 39.2780 | 6821.28 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 20438.129 | 14376.396 | 513.827607 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2431 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 513.827607 | 0.58450283 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 16784.58 | 16784.58 | 0.8212 | 0.58450283 | 513.827607 | 79.85 | 59.10 | 0.00703348 | 10.7 | 53.60 | 48.96 | 0.00703348 | 7.1 | -999. | -999.0 | -999.0 | -999.0 | 661.287 | 16123.30 | 105.44 | 0.00563111 | 65.44 | 59.99331119 | 11.6758 | 75.00 | 0.00721886 | 75.00 | 0.00721886 | 35.5851 | 10957.62 | 0.00 | 20434.62 | 13816.38 | 0.56141938 | 80.00 | 67.00 | 0.01118466 | 13.2 | 51.94 | 51.92 | 0.00819826 | 7.6 | |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 20548.820 | 20548.820 | 513.827607 | -999. | -999.00 | -999.0000 | 1.00000 | 0.87427 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 513.827607 | 0.58450283 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 20548.82 | 11563.75 | 1.0000 | 0.58450283 | 513.827607 | 67.43 | 54.44 | 0.00696455 | 8.9 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 20548.82 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 11.6758 | 72.00 | 0.00731472 | 72.00 | 0.00731472 | 39.8850 | 8918.65 | 0.00 | 20575.82 | 20575.82 | 0.57417448 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 12758.094 | 12758.094 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 513.827607 | 0.58450283 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 12758.09 | 12758.09 | 1.0000 | -0.240765E+04 | -999. | 67.43 | 54.44 | 0.00696455 | 8.9 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 12758.09 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00731472 | 72.00 | 0.00731472 | 39.8850 | 8918.65 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 23084.945 | 16747.934 | 622.956468 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 622.956468 | 0.70864199 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | Sensible | 19560.65 | 19560.65 | 0.8473 | 0.70864199 | 622.956468 | 78.83 | 58.93 | 0.00715208 | 10.6 | 53.60 | 49.18 | 0.00715208 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 801.733 | 18758.92 | 101.29 | 0.00562752 | 64.15 | 59.99331119 | 9.6304 | 75.00 | 0.00731454 | 75.00 | 0.00729408 | 35.9525 | 13274.43 | 0.00 | 23080.99 | 16050.97 | 0.68065599 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.13 | 53.11 | 0.00856816 | 8.0 | |
| MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 24913.064 | 24913.064 | 622.956468 | -999. | -999.00 | -999.0000 | 1.00000 | 0.93843 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 622.956468 | 0.70864199 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 24913.06 | 13522.87 | 1.0000 | 0.70864199 | 622.956468 | 68.23 | 54.85 | 0.00702641 | 9.1 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 24913.06 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 9.6304 | 72.00 | 0.00731529 | 72.00 | 0.00731529 | 39.8880 | 8928.03 | 0.00 | 24945.80 | 24945.80 | 0.69612006 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 12768.724 | 12768.724 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 622.956468 | 0.70864199 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 12768.72 | 12768.72 | 1.0000 | -0.240765E+04 | -999. | 68.23 | 54.85 | 0.00702641 | 9.1 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 12768.72 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00731529 | 72.00 | 0.00731529 | 39.8880 | 8928.03 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 14527.126 | 10405.982 | 381.381724 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2431 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 381.381724 | 0.43383947 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 12569.99 | 12569.99 | 0.8653 | 0.43383947 | 381.381724 | 80.08 | 59.19 | 0.00703347 | 10.7 | 53.60 | 48.96 | 0.00703347 | 7.1 | -999. | -999.0 | -999.0 | -999.0 | 490.831 | 12079.16 | 99.10 | 0.00562563 | 63.46 | 59.99331119 | 15.7305 | 75.00 | 0.00729627 | 75.00 | 0.00716618 | 35.3285 | 7909.15 | 0.00 | 14524.63 | 9981.23 | 0.41670609 | 80.00 | 67.00 | 0.01118466 | 13.2 | 52.70 | 52.66 | 0.00842253 | 7.8 | |
| MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 15252.089 | 15252.089 | 381.381724 | -999. | -999.00 | -999.0000 | 1.00000 | 0.91296 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 381.381724 | 0.43383947 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 15252.09 | 9185.95 | 1.0000 | 0.43383947 | 381.381724 | 65.85 | 53.46 | 0.00674820 | 8.6 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 15252.09 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 15.7305 | 72.00 | 0.00720229 | 72.00 | 0.00720229 | 39.2786 | 6822.49 | 0.00 | 15272.13 | 15272.13 | 0.42617339 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 10382.635 | 10382.635 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 381.381724 | 0.43383947 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 10382.63 | 10382.63 | 1.0000 | -0.240765E+04 | -999. | 65.85 | 53.46 | 0.00674820 | 8.6 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10382.63 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00720229 | 72.00 | 0.00720229 | 39.2786 | 6822.49 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 19861.308 | 13924.430 | 496.636232 | -999. | -999.00 | -999.0000 | 1.00000 | 0.99910 | 0.2431 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 496.636232 | 0.56494684 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 16321.28 | 16321.28 | 0.8218 | 0.56494684 | 496.636232 | 80.03 | 59.14 | 0.00701348 | 10.7 | 53.60 | 48.92 | 0.00701348 | 7.1 | -999. | -999.0 | -999.0 | -999.0 | 639.162 | 15682.12 | 105.44 | 0.00563111 | 65.44 | 59.99331119 | 12.0799 | 75.00 | 0.00720697 | 75.00 | 0.00720697 | 35.5271 | 10419.64 | 0.00 | 19857.90 | 13386.84 | 0.54263571 | 80.00 | 67.00 | 0.01118466 | 13.2 | 51.87 | 51.83 | 0.00816359 | 7.6 | |
| MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 19861.308 | 19861.308 | 496.636232 | -999. | -999.00 | -999.0000 | 1.00000 | 0.86957 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 496.636232 | 0.56494684 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 19861.31 | 11255.12 | 1.0000 | 0.56494684 | 496.636232 | 67.27 | 54.36 | 0.00695227 | 8.9 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 19861.31 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 12.0799 | 72.00 | 0.00731455 | 72.00 | 0.00731455 | 39.8840 | 8915.80 | 0.00 | 19887.41 | 19887.41 | 0.55496405 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 12754.859 | 12754.859 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 496.636232 | 0.56494684 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 12754.86 | 12754.86 | 1.0000 | -0.240765E+04 | -999. | 67.27 | 54.36 | 0.00695227 | 8.9 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 12754.86 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00731455 | 72.00 | 0.00731455 | 39.8840 | 8915.80 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 22868.011 | 16598.389 | 617.902207 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 617.902207 | 0.70289253 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | Sensible | 19420.18 | 19420.18 | 0.8492 | 0.70289253 | 617.902207 | 78.85 | 59.05 | 0.00722920 | 10.6 | 53.60 | 49.33 | 0.00722920 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 795.229 | 18624.95 | 101.29 | 0.00562752 | 64.15 | 59.99331119 | 9.7092 | 75.00 | 0.00740143 | 75.00 | 0.00738084 | 36.3757 | 13155.05 | 0.00 | 22864.09 | 15899.52 | 0.67513359 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.17 | 53.13 | 0.00857131 | 8.0 | |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 24710.936 | 24710.936 | 617.902207 | -999. | -999.00 | -999.0000 | 1.00000 | 0.93964 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 617.902207 | 0.70289253 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 24710.94 | 13431.52 | 1.0000 | 0.70289253 | 617.902207 | 68.20 | 55.04 | 0.00714167 | 9.2 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 24710.94 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 9.7092 | 72.00 | 0.00744556 | 72.00 | 0.00744556 | 40.5885 | 7827.65 | 0.00 | 24743.41 | 24743.41 | 0.69047220 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 11521.794 | 11521.794 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 617.902207 | 0.70289253 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 11521.79 | 11521.79 | 1.0000 | -0.240765E+04 | -999. | 68.20 | 55.04 | 0.00714167 | 9.2 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11521.79 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00744556 | 72.00 | 0.00744556 | 40.5885 | 7827.65 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 14022.836 | 9970.500 | 361.997510 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 361.997510 | 0.41178902 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 12098.65 | 12098.65 | 0.8628 | 0.41178902 | 361.997510 | 80.45 | 59.44 | 0.00711639 | 10.8 | 53.60 | 49.12 | 0.00711639 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 465.884 | 11632.76 | 100.09 | 0.00562649 | 63.77 | 59.99331119 | 16.5729 | 75.00 | 0.00741236 | 75.00 | 0.00728684 | 35.9172 | 7619.44 | 0.00 | 14020.43 | 9570.44 | 0.39552647 | 80.00 | 67.00 | 0.01118466 | 13.2 | 52.42 | 52.38 | 0.00833445 | 7.7 | |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 14476.882 | 14476.882 | 361.997510 | -999. | -999.00 | -999.0000 | 1.00000 | 0.89772 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 361.997510 | 0.41178902 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 14476.88 | 8837.62 | 1.0000 | 0.41178902 | 361.997510 | 65.52 | 53.47 | 0.00683103 | 8.6 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14476.88 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 16.5729 | 72.00 | 0.00733073 | 72.00 | 0.00733073 | 39.9694 | 5561.43 | 0.00 | 14495.91 | 14495.91 | 0.40451258 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 8953.612 | 8953.612 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 361.997510 | 0.41178902 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 8953.61 | 8953.61 | 1.0000 | -0.240765E+04 | -999. | 65.52 | 53.47 | 0.00683103 | 8.6 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8953.61 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00733073 | 72.00 | 0.00733073 | 39.9694 | 5561.43 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 19758.435 | 13888.878 | 495.779213 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 495.779213 | 0.56397194 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 16276.75 | 16276.75 | 0.8238 | 0.56397194 | 495.779213 | 79.98 | 59.27 | 0.00711036 | 10.7 | 53.60 | 49.11 | 0.00711036 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 638.059 | 15638.69 | 105.44 | 0.00563111 | 65.44 | 59.99331119 | 12.1008 | 75.00 | 0.00731400 | 75.00 | 0.00731400 | 36.0494 | 10572.48 | 0.00 | 19755.05 | 13347.87 | 0.54169931 | 80.00 | 67.00 | 0.01118466 | 13.2 | 51.91 | 51.89 | 0.00818825 | 7.6 | |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 19827.034 | 19827.034 | 495.779213 | -999. | -999.00 | -999.0000 | 1.00000 | 0.87258 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 495.779213 | 0.56397194 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 19827.03 | 11239.26 | 1.0000 | 0.56397194 | 495.779213 | 67.27 | 54.55 | 0.00706685 | 9.0 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 19827.03 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 12.1008 | 72.00 | 0.00744561 | 72.00 | 0.00744561 | 40.5887 | 7828.50 | 0.00 | 19853.09 | 19853.09 | 0.55400638 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 11522.752 | 11522.752 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 495.779213 | 0.56397194 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 11522.75 | 11522.75 | 1.0000 | -0.240765E+04 | -999. | 67.27 | 54.55 | 0.00706685 | 9.0 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11522.75 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00744561 | 72.00 | 0.00744561 | 40.5887 | 7828.50 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 22383.211 | 16317.236 | 609.735613 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 609.735613 | 0.69360265 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 19130.47 | 19130.47 | 0.8547 | 0.69360265 | 609.735613 | 78.80 | 59.07 | 0.00724957 | 10.7 | 53.60 | 49.37 | 0.00724957 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 784.718 | 18345.76 | 100.49 | 0.00562683 | 63.90 | 59.99331119 | 9.8392 | 75.00 | 0.00742666 | 75.00 | 0.00741800 | 36.5569 | 12987.86 | 0.00 | 22379.37 | 15628.26 | 0.66621059 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.27 | 53.26 | 0.00861748 | 8.0 | |
| MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 24384.340 | 24384.340 | 609.735613 | -999. | -999.00 | -999.0000 | 1.00000 | 0.94731 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 609.735613 | 0.69360265 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 24384.34 | 13284.92 | 1.0000 | 0.69360265 | 609.735613 | 68.15 | 55.01 | 0.00713784 | 9.1 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 24384.34 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 9.8392 | 72.00 | 0.00744584 | 72.00 | 0.00744584 | 40.5899 | 7832.35 | 0.00 | 24416.38 | 24416.38 | 0.68134648 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 11527.115 | 11527.115 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 609.735613 | 0.69360265 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 11527.12 | 11527.12 | 1.0000 | -0.240765E+04 | -999. | 68.15 | 55.01 | 0.00713784 | 9.1 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11527.12 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00744584 | 72.00 | 0.00744584 | 40.5899 | 7832.35 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 13596.844 | 9790.401 | 360.754012 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 360.754012 | 0.41037449 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 11900.21 | 11900.20 | 0.8752 | 0.41037449 | 360.754012 | 80.10 | 59.37 | 0.00714616 | 10.8 | 53.60 | 49.17 | 0.00714616 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 464.284 | 11435.92 | 97.90 | 0.00562460 | 63.07 | 59.99331119 | 16.6300 | 75.00 | 0.00744967 | 75.00 | 0.00741689 | 36.5517 | 7627.26 | 0.00 | 13594.51 | 9388.88 | 0.39416780 | 80.00 | 67.00 | 0.01118466 | 13.2 | 52.86 | 52.84 | 0.00848168 | 7.9 | |
| MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 14427.152 | 14427.152 | 360.754012 | -999. | -999.00 | -999.0000 | 1.00000 | 0.92267 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 360.754012 | 0.41037449 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 14427.15 | 8815.30 | 1.0000 | 0.41037449 | 360.754012 | 65.50 | 53.46 | 0.00682935 | 8.6 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14427.15 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 16.6300 | 72.00 | 0.00733077 | 72.00 | 0.00733077 | 39.9696 | 5561.93 | 0.00 | 14446.11 | 14446.11 | 0.40312304 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 8954.185 | 8954.185 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 360.754012 | 0.41037449 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 8954.18 | 8954.18 | 1.0000 | -0.240765E+04 | -999. | 65.50 | 53.46 | 0.00682935 | 8.6 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8954.18 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00733077 | 72.00 | 0.00733077 | 39.9696 | 5561.93 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 18818.440 | 13193.292 | 470.559091 | -999. | -999.00 | -999.0000 | 1.00000 | 0.99681 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 470.559091 | 0.53528288 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 15514.31 | 15514.31 | 0.8244 | 0.53528288 | 470.559091 | 80.17 | 59.31 | 0.00709183 | 10.7 | 53.60 | 49.07 | 0.00709183 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 605.601 | 14908.71 | 105.44 | 0.00563111 | 65.44 | 59.99331119 | 12.7494 | 75.00 | 0.00730528 | 75.00 | 0.00730528 | 36.0069 | 10034.70 | 0.00 | 18815.21 | 12683.93 | 0.51414325 | 80.00 | 67.00 | 0.01118466 | 13.2 | 51.87 | 51.83 | 0.00816359 | 7.6 | |
| MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 18818.440 | 18818.440 | 470.559091 | -999. | -999.00 | -999.0000 | 1.00000 | 0.86957 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 470.559091 | 0.53528288 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 18818.44 | 10786.52 | 1.0000 | 0.53528288 | 470.559091 | 67.01 | 54.42 | 0.00704637 | 8.9 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 18818.44 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 12.7494 | 72.00 | 0.00744540 | 72.00 | 0.00744540 | 40.5876 | 7824.83 | 0.00 | 18843.17 | 18843.17 | 0.52582426 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 11518.597 | 11518.597 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 470.559091 | 0.53528288 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 11518.60 | 11518.60 | 1.0000 | -0.240765E+04 | -999. | 67.01 | 54.42 | 0.00704637 | 8.9 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11518.60 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00744540 | 72.00 | 0.00744540 | 40.5876 | 7824.83 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 26938.111 | 19674.729 | 737.589227 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 737.589227 | 0.83904209 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | Sensible | 22800.80 | 22800.80 | 0.8464 | 0.83904209 | 737.589227 | 78.43 | 58.87 | 0.00720216 | 10.6 | 53.60 | 49.28 | 0.00720216 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 949.264 | 21851.54 | 101.29 | 0.00562752 | 64.15 | 59.99331119 | 8.1337 | 75.00 | 0.00734158 | 75.00 | 0.00732242 | 36.0906 | 15711.28 | 0.00 | 26933.49 | 18844.56 | 0.80590627 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.36 | 53.34 | 0.00864194 | 8.1 | |
| MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 29497.419 | 29497.419 | 737.589227 | -999. | -999.00 | -999.0000 | 1.00000 | 0.95218 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 737.589227 | 0.83904209 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 29497.42 | 15580.79 | 1.0000 | 0.83904209 | 737.589227 | 68.82 | 55.28 | 0.00714878 | 9.2 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 29497.42 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 8.1337 | 72.00 | 0.00739963 | 72.00 | 0.00739963 | 40.3425 | 10515.10 | 0.00 | 29536.18 | 29536.18 | 0.82421596 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 14567.271 | 14567.271 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 737.589227 | 0.83904209 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 14567.27 | 14567.27 | 1.0000 | -0.240765E+04 | -999. | 68.82 | 55.28 | 0.00714878 | 9.2 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14567.27 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00739963 | 72.00 | 0.00739963 | 40.3425 | 10515.10 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 18082.612 | 13022.136 | 479.950815 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 479.950815 | 0.54596640 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 15460.12 | 15460.12 | 0.8550 | 0.54596640 | 479.950815 | 79.48 | 59.09 | 0.00710767 | 10.7 | 53.60 | 49.10 | 0.00710767 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 617.688 | 14842.43 | 100.49 | 0.00562683 | 63.90 | 59.99331119 | 12.4999 | 75.00 | 0.00731922 | 75.00 | 0.00722774 | 35.6292 | 10129.28 | 0.00 | 18079.51 | 12488.09 | 0.52440485 | 80.00 | 67.00 | 0.01118466 | 13.2 | 52.86 | 52.84 | 0.00848351 | 7.9 | |
| MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 19194.030 | 19194.030 | 479.950815 | -999. | -999.00 | -999.0000 | 1.00000 | 0.92301 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 479.950815 | 0.54596640 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 19194.03 | 10955.47 | 1.0000 | 0.54596640 | 479.950815 | 67.11 | 54.27 | 0.00693654 | 8.9 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 19194.03 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 12.4999 | 72.00 | 0.00731095 | 72.00 | 0.00731095 | 39.8643 | 8248.20 | 0.00 | 19219.25 | 19219.25 | 0.53631900 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 11998.315 | 11998.315 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 479.950815 | 0.54596640 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 11998.32 | 11998.32 | 1.0000 | -0.240765E+04 | -999. | 67.11 | 54.27 | 0.00693654 | 8.9 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11998.32 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00731095 | 72.00 | 0.00731095 | 39.8643 | 8248.20 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 23555.800 | 16738.837 | 607.091924 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 607.091924 | 0.69059533 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 19385.30 | 19385.30 | 0.8230 | 0.69059533 | 607.091924 | 79.25 | 58.99 | 0.00709569 | 10.6 | 53.60 | 49.08 | 0.00709569 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 781.316 | 18603.98 | 104.96 | 0.00563070 | 65.30 | 59.99331119 | 9.8821 | 75.00 | 0.00725633 | 75.00 | 0.00725426 | 35.7575 | 12928.37 | 0.00 | 23551.76 | 16067.19 | 0.66332204 | 80.00 | 67.00 | 0.01118466 | 13.2 | 52.39 | 52.35 | 0.00832618 | 7.7 | |
| MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 24278.615 | 24278.615 | 607.091924 | -999. | -999.00 | -999.0000 | 1.00000 | 0.89625 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 607.091924 | 0.69059533 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 24278.61 | 13238.06 | 1.0000 | 0.69059533 | 607.091924 | 68.13 | 54.93 | 0.00709500 | 9.1 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 24278.61 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 9.8821 | 72.00 | 0.00739978 | 72.00 | 0.00739978 | 40.3433 | 10518.39 | 0.00 | 24310.52 | 24310.52 | 0.67839230 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 14570.992 | 14570.992 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 607.091924 | 0.69059533 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 14570.99 | 14570.99 | 1.0000 | -0.240765E+04 | -999. | 68.13 | 54.93 | 0.00709500 | 9.1 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14570.99 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00739978 | 72.00 | 0.00739978 | 40.3433 | 10518.39 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 26845.456 | 19640.734 | 738.488141 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 738.488141 | 0.84006465 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | Sensible | 22796.93 | 22796.93 | 0.8492 | 0.84006465 | 738.488141 | 78.40 | 58.88 | 0.00721646 | 10.6 | 53.60 | 49.30 | 0.00721646 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 950.421 | 21846.51 | 100.89 | 0.00562717 | 64.03 | 59.99331119 | 8.1238 | 75.00 | 0.00735699 | 75.00 | 0.00734178 | 36.1850 | 15740.31 | 0.00 | 26840.85 | 18802.38 | 0.80688844 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00866087 | 8.1 | |
| MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 29533.368 | 29533.368 | 738.488141 | -999. | -999.00 | -999.0000 | 1.00000 | 0.95663 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 738.488141 | 0.84006465 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 29533.37 | 15596.93 | 1.0000 | 0.84006465 | 738.488141 | 68.82 | 55.28 | 0.00714921 | 9.2 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 29533.37 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 8.1238 | 72.00 | 0.00739976 | 72.00 | 0.00739976 | 40.3432 | 10517.86 | 0.00 | 29572.18 | 29572.18 | 0.82522044 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 14570.399 | 14570.399 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 738.488141 | 0.84006465 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 14570.40 | 14570.40 | 1.0000 | -0.240765E+04 | -999. | 68.82 | 55.28 | 0.00714921 | 9.2 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14570.40 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00739976 | 72.00 | 0.00739976 | 40.3432 | 10517.86 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 17881.738 | 12974.930 | 482.737579 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 482.737579 | 0.54913647 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 15434.84 | 15434.84 | 0.8632 | 0.54913647 | 482.737579 | 79.29 | 59.04 | 0.00712136 | 10.6 | 53.60 | 49.13 | 0.00712136 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 621.274 | 14813.57 | 99.10 | 0.00562563 | 63.46 | 59.99331119 | 12.4277 | 75.00 | 0.00733362 | 75.00 | 0.00725459 | 35.7602 | 10142.82 | 0.00 | 17878.67 | 12435.00 | 0.52744973 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.14 | 53.12 | 0.00857007 | 8.0 | |
| MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 19305.478 | 19305.478 | 482.737579 | -999. | -999.00 | -999.0000 | 1.00000 | 0.93880 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 482.737579 | 0.54913647 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 19305.48 | 11005.50 | 1.0000 | 0.54913647 | 482.737579 | 67.14 | 54.29 | 0.00693868 | 8.9 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 19305.48 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 12.4277 | 72.00 | 0.00731094 | 72.00 | 0.00731094 | 39.8642 | 8247.90 | 0.00 | 19330.85 | 19330.85 | 0.53943306 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 11997.976 | 11997.976 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 482.737579 | 0.54913647 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 11997.98 | 11997.98 | 1.0000 | -0.240765E+04 | -999. | 67.14 | 54.29 | 0.00693868 | 8.9 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11997.98 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00731094 | 72.00 | 0.00731094 | 39.8642 | 8247.90 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 23261.273 | 16539.942 | 600.561968 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 600.561968 | 0.68316720 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 19182.93 | 19182.93 | 0.8247 | 0.68316720 | 600.561968 | 79.26 | 58.99 | 0.00709384 | 10.6 | 53.60 | 49.07 | 0.00709384 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 772.912 | 18410.01 | 104.72 | 0.00563048 | 65.22 | 59.99331119 | 9.9895 | 75.00 | 0.00725625 | 75.00 | 0.00725400 | 35.7562 | 12797.40 | 0.00 | 23257.28 | 15876.28 | 0.65618726 | 80.00 | 67.00 | 0.01118466 | 13.2 | 52.42 | 52.38 | 0.00833508 | 7.7 | |
| MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 24017.471 | 24017.471 | 600.561968 | -999. | -999.00 | -999.0000 | 1.00000 | 0.89783 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 600.561968 | 0.68316720 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 24017.47 | 13120.83 | 1.0000 | 0.68316720 | 600.561968 | 68.09 | 54.91 | 0.00709155 | 9.1 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 24017.47 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 9.9895 | 72.00 | 0.00739963 | 72.00 | 0.00739963 | 40.3425 | 10515.05 | 0.00 | 24049.03 | 24049.03 | 0.67109543 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 14567.205 | 14567.205 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 600.561968 | 0.68316720 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 14567.20 | 14567.20 | 1.0000 | -0.240765E+04 | -999. | 68.09 | 54.91 | 0.00709155 | 9.1 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14567.20 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00739963 | 72.00 | 0.00739963 | 40.3425 | 10515.05 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | HEATEDBSMT | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 19942.353 | 15482.009 | 619.226822 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0682 | SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 619.226822 | 0.70439934 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 17657.16 | 17574.35 | 0.8854 | 0.70439934 | 619.226822 | 78.34 | 59.34 | 0.00753283 | 10.8 | 53.60 | 49.83 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 796.933 | 16860.23 | 96.10 | 0.00562306 | 62.49 | 59.99331119 | 9.6884 | 75.00 | 0.00773771 | 75.00 | 0.00773572 | 38.1041 | 13171.35 | 0.00 | 19938.93 | 14756.63 | 0.67658089 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.18 | 55.16 | 0.00924424 | 8.7 | |
| MAIN DX HEATING COIL_UNITHEATEDBSMT | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | HEATEDBSMT | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | unknown | No | 24763.909 | 24763.909 | 619.226822 | -999. | -999.00 | -999.0000 | 1.00000 | 0.99342 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 619.226822 | 0.70439934 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | Sensible | 24763.91 | 13453.59 | 1.0000 | 0.70439934 | 619.226822 | 68.21 | 56.34 | 0.00793065 | 9.6 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 24763.91 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | 9.6884 | 72.00 | 0.00831847 | 72.00 | 0.00831847 | 45.2795 | 7404.36 | 0.00 | 24796.45 | 24796.45 | 0.69195239 | 70.00 | 60.00 | 0.00875166 | 10.4 | 110.82 | 73.03 | 0.00875166 | 15.9 | |
| SUPP HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | HEATEDBSMT | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 12002.500 | 12002.500 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 619.226822 | 0.70439934 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | Sensible | 12002.50 | 12002.50 | 1.0000 | -0.240765E+04 | -999. | 68.21 | 56.34 | 0.00793065 | 9.6 | 90.00 | 63.89 | 0.00800000 | 12.6 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 12002.50 | 32.90 | 0.00431558 | 32.90 | 59.99331119 | -999.000 | 72.00 | 0.00831847 | 72.00 | 0.00831847 | 45.2795 | 7404.36 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. |
Report: System Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2471.50 | 4415.67 | 249.83 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1749.33 | 4568.33 | 186.83 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2238.17 | 4113.00 | 218.17 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2207.33 | 5016.67 | 263.67 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1674.17 | 5512.17 | 201.67 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2082.00 | 4940.00 | 222.67 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2785.67 | 3933.33 | 173.17 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1906.33 | 3844.00 | 116.83 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2556.33 | 3608.83 | 149.83 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2463.50 | 4579.17 | 198.50 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1805.67 | 4883.00 | 132.33 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2333.67 | 4485.67 | 163.67 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 2659.83 | 4423.83 | 250.17 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 2812.50 | 3811.17 | 231.50 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 3015.17 | 4113.33 | 264.17 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 2098.83 | 4779.00 | 197.83 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 2173.50 | 4086.67 | 179.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 2785.83 | 4534.33 | 302.50 |
| HEATEDBSMT | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 |
| Facility | 3417.67 | 5684.83 | 351.50 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.294 | 0.000 | 0.355 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.259 | 0.000 | 0.355 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.294 | 0.000 | 0.355 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.293 | 0.000 | 0.355 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.258 | 0.000 | 0.355 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.293 | 0.000 | 0.355 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.129 | 0.000 | 0.355 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.094 | 0.000 | 0.355 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.129 | 0.000 | 0.355 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.129 | 0.000 | 0.355 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.094 | 0.000 | 0.355 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.129 | 0.000 | 0.355 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.294 | 0.000 | 0.355 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.295 | 0.000 | 0.355 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.294 | 0.000 | 0.355 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.259 | 0.000 | 0.355 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.260 | 0.000 | 0.355 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.293 | 0.000 | 0.355 |
| HEATEDBSMT | 58539.52 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.002 | 0.000 | 0.006 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.002 | 0.000 | 0.006 |
| HEATEDBSMT | 58539.52 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 58539.52 | 7794.39 | 0.0000 | 0.000 | |
| Total Facility | 24.79 | 36.00 | 242278.90 | 29404.35 | 0.0000 | 0.000 |
| Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 31315656.65 | 31315656.65 | 25954995.41 | 57270652.05 | 31713442.25 | 4639.33 | 1833.50 | 2335.17 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 31315656.65 | 31315656.65 | 22895822.32 | 54211478.97 | 31713442.25 | 4639.33 | 1833.50 | 2335.17 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 31315656.65 | 31315656.65 | 25989315.13 | 57304971.78 | 31713442.25 | 4639.33 | 1833.50 | 2335.17 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 31315656.65 | 31315656.65 | 25876309.76 | 57191966.40 | 31713442.25 | 4639.33 | 1833.50 | 2335.17 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 31315656.65 | 31315656.65 | 22790219.69 | 54105876.34 | 31713442.25 | 4639.33 | 1833.50 | 2335.17 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 31315656.65 | 31315656.65 | 25900537.36 | 57216194.01 | 31713442.25 | 4639.33 | 1833.50 | 2335.17 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 31317447.65 | 31317447.65 | 11394473.68 | 42711921.33 | 31713442.25 | 4634.17 | 1834.17 | 2339.67 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 31317447.65 | 31317447.65 | 8307580.99 | 39625028.64 | 31713442.25 | 4634.17 | 1834.17 | 2339.67 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 31317447.65 | 31317447.65 | 11410436.56 | 42727884.20 | 31713442.25 | 4634.17 | 1834.17 | 2339.67 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 31317447.65 | 31317447.65 | 11359368.56 | 42676816.21 | 31713442.25 | 4634.17 | 1834.17 | 2339.67 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 31317447.65 | 31317447.65 | 8268712.91 | 39586160.56 | 31713442.25 | 4634.17 | 1834.17 | 2339.67 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 31317447.65 | 31317447.65 | 11373644.78 | 42691092.43 | 31713442.25 | 4634.17 | 1834.17 | 2339.67 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 31319240.53 | 31319240.53 | 25935669.39 | 57254909.92 | 31713442.25 | 4629.67 | 1831.83 | 2346.50 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 31319240.53 | 31319240.53 | 26005007.35 | 57324247.88 | 31713442.25 | 4629.67 | 1831.83 | 2346.50 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 31319240.53 | 31319240.53 | 25969317.81 | 57288558.34 | 31713442.25 | 4629.67 | 1831.83 | 2346.50 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 31319240.53 | 31319240.53 | 22833600.58 | 54152841.11 | 31713442.25 | 4629.67 | 1831.83 | 2346.50 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 31319240.53 | 31319240.53 | 22910032.17 | 54229272.70 | 31713442.25 | 4629.67 | 1831.83 | 2346.50 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 31319240.53 | 31319240.53 | 25912454.52 | 57231695.05 | 31713442.25 | 4629.67 | 1831.83 | 2346.50 | 0.00 |
| HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31713442.25 | 8808.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 0.00 | 0.563714E+09 | 0.563714E+09 | 0.361087E+09 | 0.924802E+09 | 0.602555E+09 | 8808.00 | 1843.17 | 2346.50 | 0.00 |
| Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 59.2408 | 59.2408 | 49.0999 | 108.3407 | 59.9933 | 4639.33 | 1833.50 | 2335.17 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 59.2408 | 59.2408 | 43.3127 | 102.5536 | 59.9933 | 4639.33 | 1833.50 | 2335.17 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 59.2408 | 59.2408 | 49.1648 | 108.4056 | 59.9933 | 4639.33 | 1833.50 | 2335.17 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 59.2408 | 59.2408 | 48.9510 | 108.1918 | 59.9933 | 4639.33 | 1833.50 | 2335.17 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 59.2408 | 59.2408 | 43.1130 | 102.3538 | 59.9933 | 4639.33 | 1833.50 | 2335.17 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 59.2408 | 59.2408 | 48.9969 | 108.2377 | 59.9933 | 4639.33 | 1833.50 | 2335.17 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 59.2442 | 59.2442 | 21.5553 | 80.7995 | 59.9933 | 4634.17 | 1834.17 | 2339.67 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 59.2442 | 59.2442 | 15.7157 | 74.9599 | 59.9933 | 4634.17 | 1834.17 | 2339.67 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 59.2442 | 59.2442 | 21.5855 | 80.8297 | 59.9933 | 4634.17 | 1834.17 | 2339.67 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 59.2442 | 59.2442 | 21.4889 | 80.7331 | 59.9933 | 4634.17 | 1834.17 | 2339.67 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 59.2442 | 59.2442 | 15.6422 | 74.8864 | 59.9933 | 4634.17 | 1834.17 | 2339.67 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 59.2442 | 59.2442 | 21.5159 | 80.7601 | 59.9933 | 4634.17 | 1834.17 | 2339.67 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 59.2476 | 59.2476 | 49.0633 | 108.3109 | 59.9933 | 4629.67 | 1831.83 | 2346.50 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 59.2476 | 59.2476 | 49.1945 | 108.4421 | 59.9933 | 4629.67 | 1831.83 | 2346.50 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 59.2476 | 59.2476 | 49.1270 | 108.3746 | 59.9933 | 4629.67 | 1831.83 | 2346.50 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 59.2476 | 59.2476 | 43.1950 | 102.4426 | 59.9933 | 4629.67 | 1831.83 | 2346.50 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 59.2476 | 59.2476 | 43.3396 | 102.5872 | 59.9933 | 4629.67 | 1831.83 | 2346.50 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 59.2476 | 59.2476 | 49.0194 | 108.2670 | 59.9933 | 4629.67 | 1831.83 | 2346.50 |
| Total Facility | 0.0000 | 1066.3955 | 1066.3955 | 683.0805 | 1749.4761 | 1079.8796 | 8808.00 | 1843.17 | 2346.50 |
| Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 31315656.65 | 31315656.65 | 31713442.25 | 4639.33 | 1833.50 | 2335.17 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 31315656.65 | 31315656.65 | 31713442.25 | 4639.33 | 1833.50 | 2335.17 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 31315656.65 | 31315656.65 | 31713442.25 | 4639.33 | 1833.50 | 2335.17 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 31315656.65 | 31315656.65 | 31713442.25 | 4639.33 | 1833.50 | 2335.17 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 31315656.65 | 31315656.65 | 31713442.25 | 4639.33 | 1833.50 | 2335.17 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 31315656.65 | 31315656.65 | 31713442.25 | 4639.33 | 1833.50 | 2335.17 | 0.00 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 31317447.65 | 31317447.65 | 31713442.25 | 4634.17 | 1834.17 | 2339.67 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 31317447.65 | 31317447.65 | 31713442.25 | 4634.17 | 1834.17 | 2339.67 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 31317447.65 | 31317447.65 | 31713442.25 | 4634.17 | 1834.17 | 2339.67 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 31317447.65 | 31317447.65 | 31713442.25 | 4634.17 | 1834.17 | 2339.67 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 31317447.65 | 31317447.65 | 31713442.25 | 4634.17 | 1834.17 | 2339.67 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 31317447.65 | 31317447.65 | 31713442.25 | 4634.17 | 1834.17 | 2339.67 | 0.00 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 31319240.53 | 31319240.53 | 31713442.25 | 4629.67 | 1831.83 | 2346.50 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 31319240.53 | 31319240.53 | 31713442.25 | 4629.67 | 1831.83 | 2346.50 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 31319240.53 | 31319240.53 | 31713442.25 | 4629.67 | 1831.83 | 2346.50 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 31319240.53 | 31319240.53 | 31713442.25 | 4629.67 | 1831.83 | 2346.50 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 31319240.53 | 31319240.53 | 31713442.25 | 4629.67 | 1831.83 | 2346.50 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 31319240.53 | 31319240.53 | 31713442.25 | 4629.67 | 1831.83 | 2346.50 | 0.00 |
| CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.00 | 0.00 | 31713442.25 | 8808.00 | 0.00 | 0.00 | 0.00 |
| Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 59.2408 | 59.2408 | 59.9933 | 4639.33 | 1833.50 | 2335.17 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 59.2408 | 59.2408 | 59.9933 | 4639.33 | 1833.50 | 2335.17 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 59.2408 | 59.2408 | 59.9933 | 4639.33 | 1833.50 | 2335.17 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 59.2408 | 59.2408 | 59.9933 | 4639.33 | 1833.50 | 2335.17 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 59.2408 | 59.2408 | 59.9933 | 4639.33 | 1833.50 | 2335.17 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 59.2408 | 59.2408 | 59.9933 | 4639.33 | 1833.50 | 2335.17 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 59.2442 | 59.2442 | 59.9933 | 4634.17 | 1834.17 | 2339.67 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 59.2442 | 59.2442 | 59.9933 | 4634.17 | 1834.17 | 2339.67 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 59.2442 | 59.2442 | 59.9933 | 4634.17 | 1834.17 | 2339.67 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 59.2442 | 59.2442 | 59.9933 | 4634.17 | 1834.17 | 2339.67 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 59.2442 | 59.2442 | 59.9933 | 4634.17 | 1834.17 | 2339.67 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 59.2442 | 59.2442 | 59.9933 | 4634.17 | 1834.17 | 2339.67 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 59.2476 | 59.2476 | 59.9933 | 4629.67 | 1831.83 | 2346.50 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 59.2476 | 59.2476 | 59.9933 | 4629.67 | 1831.83 | 2346.50 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 59.2476 | 59.2476 | 59.9933 | 4629.67 | 1831.83 | 2346.50 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 59.2476 | 59.2476 | 59.9933 | 4629.67 | 1831.83 | 2346.50 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 59.2476 | 59.2476 | 59.9933 | 4629.67 | 1831.83 | 2346.50 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 59.2476 | 59.2476 | 59.9933 | 4629.67 | 1831.83 | 2346.50 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Surfaces by Class| Total | Outdoors | |
| Wall | 82 | 54 |
| Floor | 29 | 3 |
| Roof | 27 | 2 |
| Internal Mass | 0 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 30 | 30 |
| Door | 18 | 18 |
| Glass Door | 0 | 0 |
| Shading | 60 | 60 |
| Overhang | 30 | 30 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 19 |
| Conditioned Zones | 19 |
| Unconditioned Zones | 2 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1950 |
| Defaulted Fields | 1882 |
| Fields with Defaults | 6466 |
| Autosized Fields | 395 |
| Autosizable Fields | 600 |
| Autocalculated Fields | 161 |
| Autocalculatable Fields | 349 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Annual and Peak Values - Electricity| Electricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 240113.31 | 10554.69 | 03-APR-03:50 | 84605.73 | 30-JUL-18:50 |
| Electricity:Building | 127420.42 | 8362.71 | 02-JAN-03:10 | 24143.95 | 01-JAN-18:10 |
| Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 127420.42 | 8362.71 | 02-JAN-03:10 | 24143.95 | 01-JAN-18:10 |
| InteriorLights:Electricity | 18100.85 | 405.35 | 01-JAN-00:10 | 5896.05 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 18100.85 | 405.35 | 01-JAN-00:10 | 5896.05 | 01-JAN-19:10 |
| General:InteriorLights:Electricity | 18100.85 | 405.35 | 01-JAN-00:10 | 5896.05 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:SpaceType:GENERAL | 18100.85 | 405.35 | 01-JAN-00:10 | 5896.05 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5729.78 | 353.83 | 02-JAN-03:10 | 1101.52 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.89 | 18.18 | 01-JAN-00:10 | 264.46 | 01-JAN-19:10 |
| Electricity:Zone:HEATEDBSMT | 24284.35 | 1963.49 | 01-JAN-09:10 | 4650.26 | 01-JAN-20:10 |
| InteriorLights:Electricity:Zone:HEATEDBSMT | 3486.76 | 78.08 | 01-JAN-00:10 | 1135.75 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:HEATEDBSMT | 3486.76 | 78.08 | 01-JAN-00:10 | 1135.75 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 109319.57 | 7858.10 | 02-JAN-04:10 | 18823.69 | 01-JAN-18:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 109319.57 | 7858.10 | 02-JAN-04:10 | 18823.69 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:10 | 985.58 | 01-JAN-19:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 3088.82 | 28.28 | 02-JAN-03:10 | 985.58 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:10 | 427.18 | 01-JAN-09:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 1577.30 | 15.15 | 02-JAN-02:10 | 427.18 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| television:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity | 50259.25 | 4391.14 | 01-JAN-09:10 | 8493.12 | 01-JAN-20:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL | 50259.25 | 4391.14 | 01-JAN-09:10 | 8493.12 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4917.89 | 334.16 | 02-JAN-04:10 | 862.89 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 2792.18 | 243.95 | 01-JAN-09:10 | 471.84 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:HEATEDBSMT | 20797.59 | 1817.08 | 01-JAN-09:10 | 3514.51 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity | 20797.59 | 1817.08 | 01-JAN-09:10 | 3514.51 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:HEATEDBSMT | 20797.59 | 1817.08 | 01-JAN-09:10 | 3514.51 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL | 20797.59 | 1817.08 | 01-JAN-09:10 | 3514.51 | 01-JAN-20:10 |
| Fans:Electricity | 14868.77 | 814.29 | 07-JAN-00:30 | 4216.88 | 16-JUN-17:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 240113.31 | 10554.69 | 03-APR-03:50 | 84605.73 | 30-JUL-18:50 |
| ElectricityPurchased:Plant | 240113.31 | 10554.69 | 03-APR-03:50 | 84605.73 | 30-JUL-18:50 |
| Cogeneration:ElectricityPurchased | 240113.31 | 10554.69 | 03-APR-03:50 | 84605.73 | 30-JUL-18:50 |
| General:Cogeneration:ElectricityPurchased | 240113.31 | 10554.69 | 03-APR-03:50 | 84605.73 | 30-JUL-18:50 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 240113.31 | 10554.69 | 03-APR-03:50 | 84605.73 | 30-JUL-18:50 |
| ElectricityNet:Plant | 240113.31 | 10554.69 | 03-APR-03:50 | 84605.73 | 30-JUL-18:50 |
| Cogeneration:ElectricityNet | 240113.31 | 10554.69 | 03-APR-03:50 | 84605.73 | 30-JUL-18:50 |
| General:Cogeneration:ElectricityNet | 240113.31 | 10554.69 | 03-APR-03:50 | 84605.73 | 30-JUL-18:50 |
| Electricity:HVAC | 66543.37 | 814.29 | 07-JAN-00:30 | 26974.89 | 28-JUN-17:10 |
| Ventilation:Fans:Electricity | 7133.15 | 814.29 | 13-JAN-09:50 | 814.29 | 01-JAN-00:10 |
| General:Fans:Electricity | 7735.62 | 0.00 | 07-JAN-00:30 | 3402.59 | 16-JUN-17:10 |
| ExteriorLights:Electricity | 6034.31 | 0.00 | 01-JAN-06:10 | 1377.69 | 01-JAN-00:10 |
| Exterior-Lights:ExteriorLights:Electricity | 6034.31 | 0.00 | 01-JAN-06:10 | 1377.69 | 01-JAN-00:10 |
| Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 40875.60 | 0.00 | 01-JAN-00:10 | 22844.39 | 28-JUN-17:10 |
| General:Cooling:Electricity | 40875.60 | 0.00 | 01-JAN-00:10 | 22844.39 | 28-JUN-17:10 |
| Heating:Electricity | 10799.01 | 0.00 | 02-JAN-13:10 | 20091.99 | 01-JAN-06:00 |
| General:Heating:Electricity | 10799.01 | 0.00 | 02-JAN-13:10 | 20091.99 | 01-JAN-06:00 |
| Electricity:Plant | 40115.21 | 0.00 | 01-JAN-00:10 | 55590.07 | 05-JAN-07:20 |
| WaterSystems:Electricity | 40115.21 | 0.00 | 01-JAN-00:10 | 55590.07 | 05-JAN-07:20 |
| Water Heater:WaterSystems:Electricity | 40115.21 | 0.00 | 01-JAN-00:10 | 55590.07 | 05-JAN-07:20 |
| Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 01-JAN-08:10 |
| Water:Plant | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 01-JAN-08:10 |
| WaterSystems:Water | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 01-JAN-08:10 |
| Domestic Hot Water:WaterSystems:Water | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 01-JAN-08:10 |
| MainsWater:Facility | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 01-JAN-08:10 |
| MainsWater:Plant | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 01-JAN-08:10 |
| WaterSystems:MainsWater | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 01-JAN-08:10 |
| Domestic Hot Water:WaterSystems:MainsWater | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 01-JAN-08:10 |
| Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 1292799.65 | 453.73 | 28-APR-02:40 | 511118.64 | 15-JUN-18:10 |
| EnergyTransfer:Building | 584609.92 | 0.00 | 07-JAN-00:30 | 246575.36 | 15-JUN-18:10 |
| EnergyTransfer:Zone:HEATEDBSMT | 36035.16 | 0.00 | 01-JAN-14:10 | 14479.56 | 28-JUN-18:30 |
| Heating:EnergyTransfer | 90198.85 | 0.00 | 02-JAN-13:10 | 159885.02 | 07-DEC-05:00 |
| Heating:EnergyTransfer:Zone:HEATEDBSMT | 5469.71 | 0.00 | 01-JAN-14:10 | 7461.06 | 07-DEC-04:00 |
| General:Heating:EnergyTransfer | 90198.85 | 0.00 | 02-JAN-13:10 | 159885.02 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:HEATEDBSMT | 5469.71 | 0.00 | 01-JAN-14:10 | 7461.06 | 07-DEC-04:00 |
| Cooling:EnergyTransfer | 494411.08 | 0.00 | 01-JAN-00:10 | 246575.36 | 15-JUN-18:10 |
| Cooling:EnergyTransfer:Zone:HEATEDBSMT | 30565.45 | 0.00 | 01-JAN-00:10 | 14479.56 | 28-JUN-18:30 |
| General:Cooling:EnergyTransfer | 494411.08 | 0.00 | 01-JAN-00:10 | 246575.36 | 15-JUN-18:10 |
| General:Cooling:EnergyTransfer:Zone:HEATEDBSMT | 30565.45 | 0.00 | 01-JAN-00:10 | 14479.56 | 28-JUN-18:30 |
| EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 33208.10 | 0.00 | 01-JAN-12:40 | 15665.35 | 28-JUN-17:20 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5547.48 | 0.00 | 01-JAN-12:40 | 9281.17 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5547.48 | 0.00 | 01-JAN-12:40 | 9281.17 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 27660.62 | 0.00 | 01-JAN-00:10 | 15665.35 | 28-JUN-17:20 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 27660.62 | 0.00 | 01-JAN-00:10 | 15665.35 | 28-JUN-17:20 |
| EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 24713.28 | 0.00 | 01-JAN-12:00 | 9719.74 | 30-JUN-16:10 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 3455.72 | 0.00 | 01-JAN-12:00 | 6913.24 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 3455.72 | 0.00 | 01-JAN-12:00 | 6913.24 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 21257.55 | 0.00 | 01-JAN-00:10 | 9719.74 | 30-JUN-16:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 21257.55 | 0.00 | 01-JAN-00:10 | 9719.74 | 30-JUN-16:10 |
| EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 32703.91 | 0.00 | 01-JAN-11:40 | 12201.42 | 30-JUN-16:10 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5136.93 | 0.00 | 01-JAN-11:40 | 9313.34 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5136.93 | 0.00 | 01-JAN-11:40 | 9313.34 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27566.98 | 0.00 | 01-JAN-00:10 | 12201.42 | 30-JUN-16:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27566.98 | 0.00 | 01-JAN-00:10 | 12201.42 | 30-JUN-16:10 |
| EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 30389.30 | 0.00 | 01-JAN-14:50 | 15852.98 | 15-JUN-18:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6370.07 | 0.00 | 01-JAN-14:50 | 9368.04 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6370.07 | 0.00 | 01-JAN-14:50 | 9368.04 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 24019.23 | 0.00 | 01-JAN-00:10 | 15852.98 | 15-JUN-18:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 24019.23 | 0.00 | 01-JAN-00:10 | 15852.98 | 15-JUN-18:00 |
| EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 22007.39 | 0.00 | 02-JAN-13:00 | 9921.91 | 15-JUN-18:10 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4248.01 | 0.00 | 02-JAN-13:00 | 7027.67 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4248.01 | 0.00 | 02-JAN-13:00 | 7027.67 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 17759.38 | 0.00 | 01-JAN-00:10 | 9921.91 | 15-JUN-18:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 17759.38 | 0.00 | 01-JAN-00:10 | 9921.91 | 15-JUN-18:10 |
| EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 29572.45 | 0.00 | 02-JAN-10:20 | 11987.11 | 30-JUN-16:10 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5775.26 | 0.00 | 02-JAN-10:20 | 9386.36 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5775.26 | 0.00 | 02-JAN-10:20 | 9386.36 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 23797.19 | 0.00 | 01-JAN-00:10 | 11987.11 | 30-JUN-16:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 23797.19 | 0.00 | 01-JAN-00:10 | 11987.11 | 30-JUN-16:10 |
| EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 33069.59 | 0.00 | 01-JAN-12:30 | 15158.43 | 28-JUN-17:30 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 3734.36 | 0.00 | 01-JAN-12:30 | 7728.11 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 3734.36 | 0.00 | 01-JAN-12:30 | 7728.11 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29335.22 | 0.00 | 01-JAN-00:10 | 15158.43 | 28-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29335.22 | 0.00 | 01-JAN-00:10 | 15158.43 | 28-JUN-17:30 |
| EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 24496.13 | 0.00 | 01-JAN-11:40 | 8744.32 | 25-AUG-17:10 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1786.47 | 0.00 | 01-JAN-11:40 | 5164.51 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1786.47 | 0.00 | 01-JAN-11:40 | 5164.51 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 22709.66 | 0.00 | 01-JAN-00:10 | 8744.32 | 25-AUG-17:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 22709.66 | 0.00 | 01-JAN-00:10 | 8744.32 | 25-AUG-17:10 |
| EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 32964.62 | 0.00 | 01-JAN-11:20 | 11260.99 | 25-AUG-14:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 3405.19 | 0.00 | 01-JAN-11:20 | 7772.29 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 3405.19 | 0.00 | 01-JAN-11:20 | 7772.29 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 29559.42 | 0.00 | 01-JAN-00:10 | 11260.99 | 25-AUG-14:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 29559.42 | 0.00 | 01-JAN-00:10 | 11260.99 | 25-AUG-14:00 |
| EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 29581.74 | 0.00 | 01-JAN-14:50 | 15437.09 | 28-JUN-18:10 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4537.99 | 0.00 | 01-JAN-14:50 | 7857.72 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4537.99 | 0.00 | 01-JAN-14:50 | 7857.72 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 25043.75 | 0.00 | 01-JAN-00:10 | 15437.09 | 28-JUN-18:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 25043.75 | 0.00 | 01-JAN-00:10 | 15437.09 | 28-JUN-18:10 |
| EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 20803.34 | 0.00 | 02-JAN-13:00 | 9156.38 | 28-JUN-18:30 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2473.48 | 0.00 | 02-JAN-13:00 | 5349.23 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2473.48 | 0.00 | 02-JAN-13:00 | 5349.23 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 18329.86 | 0.00 | 01-JAN-00:10 | 9156.38 | 28-JUN-18:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 18329.86 | 0.00 | 01-JAN-00:10 | 9156.38 | 28-JUN-18:30 |
| EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 29004.01 | 0.00 | 02-JAN-10:20 | 11282.02 | 28-JUN-18:10 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4002.32 | 0.00 | 02-JAN-10:20 | 7912.40 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4002.32 | 0.00 | 02-JAN-10:20 | 7912.40 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 25001.69 | 0.00 | 01-JAN-00:10 | 11282.02 | 28-JUN-18:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 25001.69 | 0.00 | 01-JAN-00:10 | 11282.02 | 28-JUN-18:10 |
| EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 35779.92 | 0.00 | 02-JAN-11:40 | 14530.25 | 30-JUN-16:10 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 6468.48 | 0.00 | 02-JAN-11:40 | 10869.41 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 6468.48 | 0.00 | 02-JAN-11:40 | 10869.41 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 29311.44 | 0.00 | 01-JAN-00:10 | 14530.25 | 30-JUN-16:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 29311.44 | 0.00 | 01-JAN-00:10 | 14530.25 | 30-JUN-16:10 |
| EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 38066.31 | 0.00 | 01-JAN-12:50 | 14513.10 | 30-JUN-16:10 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5737.02 | 0.00 | 01-JAN-12:50 | 10765.76 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5737.02 | 0.00 | 01-JAN-12:50 | 10765.76 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 32329.29 | 0.00 | 01-JAN-00:10 | 14513.10 | 30-JUN-16:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 32329.29 | 0.00 | 01-JAN-00:10 | 14513.10 | 30-JUN-16:10 |
| EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 38604.11 | 0.00 | 01-JAN-13:20 | 18195.66 | 15-JUN-18:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 6248.31 | 0.00 | 01-JAN-13:20 | 10721.46 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 6248.31 | 0.00 | 01-JAN-13:20 | 10721.46 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 32355.81 | 0.00 | 01-JAN-00:10 | 18195.66 | 15-JUN-18:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 32355.81 | 0.00 | 01-JAN-00:10 | 18195.66 | 15-JUN-18:00 |
| EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 27470.79 | 0.00 | 02-JAN-13:10 | 12212.78 | 15-JUN-18:10 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4774.85 | 0.00 | 02-JAN-13:10 | 8297.08 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4774.85 | 0.00 | 02-JAN-13:10 | 8297.08 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 22695.94 | 0.00 | 01-JAN-00:10 | 12212.78 | 15-JUN-18:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 22695.94 | 0.00 | 01-JAN-00:10 | 12212.78 | 15-JUN-18:10 |
| EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 29512.89 | 0.00 | 01-JAN-13:00 | 11853.61 | 15-JUN-18:10 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 3884.43 | 0.00 | 01-JAN-13:00 | 8151.12 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 3884.43 | 0.00 | 01-JAN-13:00 | 8151.12 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 25628.46 | 0.00 | 01-JAN-00:10 | 11853.61 | 15-JUN-18:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 25628.46 | 0.00 | 01-JAN-00:10 | 11853.61 | 15-JUN-18:10 |
| EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 36626.89 | 0.00 | 01-JAN-15:10 | 18538.23 | 15-JUN-18:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 7142.77 | 0.00 | 01-JAN-15:10 | 10822.84 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 7142.77 | 0.00 | 01-JAN-15:10 | 10822.84 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 29484.12 | 0.00 | 01-JAN-00:10 | 18538.23 | 15-JUN-18:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 29484.12 | 0.00 | 01-JAN-00:10 | 18538.23 | 15-JUN-18:00 |
| PlantLoopHeatingDemand:Facility | 61457.29 | -319.0 | 27-JUL-06:10 | 20518.70 | 08-JAN-09:00 |
| PlantLoopHeatingDemand:Plant | 61457.29 | -319.0 | 27-JUL-06:10 | 20518.70 | 08-JAN-09:00 |
| WaterSystems:PlantLoopHeatingDemand | 61457.29 | -319.0 | 27-JUL-06:10 | 20518.70 | 08-JAN-09:00 |
| General:WaterSystems:PlantLoopHeatingDemand | 61457.29 | -319.0 | 27-JUL-06:10 | 20518.70 | 08-JAN-09:00 |
| EnergyTransfer:HVAC | 646732.44 | 0.00 | 07-JAN-00:30 | 261522.10 | 20-JUL-17:30 |
| CoolingCoils:EnergyTransfer | 559877.42 | 0.00 | 01-JAN-00:10 | 261522.10 | 20-JUL-17:30 |
| HeatingCoils:EnergyTransfer | 86855.02 | 0.00 | 02-JAN-13:10 | 151745.51 | 07-DEC-05:00 |
| EnergyTransfer:Plant | 61457.29 | -319.0 | 27-JUL-06:10 | 20518.70 | 08-JAN-09:00 |
| WaterSystems:EnergyTransfer | 61457.29 | -319.0 | 27-JUL-06:10 | 20518.70 | 08-JAN-09:00 |
| Domestic Hot Water:WaterSystems:EnergyTransfer | 61457.29 | -319.0 | 27-JUL-06:10 | 20518.70 | 08-JAN-09:00 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 5547.431 | -2303.51 | 0.000 | 0.000 | 2977.681 | 2772.145 | 10495.311 | 14398.870 | 0.000 | 4915.845 | 0.069 | 0.000 | -5039.31 | 0.000 | -7928.96 | -478.40 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 3455.689 | -1770.28 | 0.000 | 0.000 | 2966.163 | 2772.145 | 10495.311 | 6380.887 | 0.000 | 4624.178 | 187.354 | 0.000 | -2040.05 | 0.000 | -7584.09 | -0.01 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 5136.879 | -2295.71 | 0.000 | 0.000 | 2976.173 | 2772.145 | 10495.311 | 14763.901 | 0.000 | 4915.644 | 0.073 | 0.000 | -4809.95 | 0.000 | -7992.65 | -690.49 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 6370.012 | -2000.27 | 0.000 | 0.000 | 2986.463 | 2772.145 | 10495.311 | 10672.852 | 0.000 | 4918.195 | 0.024 | 0.000 | -5206.25 | 0.000 | -7785.38 | -1204.08 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 4247.973 | -1478.96 | 0.000 | 0.000 | 2981.046 | 2772.145 | 10495.311 | 2446.913 | 0.000 | 4626.548 | 0.084 | 0.000 | -2153.98 | 0.000 | -7366.38 | -290.13 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 5775.205 | -1981.78 | 0.000 | 0.000 | 2987.718 | 2772.145 | 10495.311 | 10875.735 | 0.000 | 4915.660 | 0.059 | 0.000 | -4792.80 | 0.000 | -7808.89 | -1422.87 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 3734.331 | -2442.97 | 0.000 | 0.000 | 2959.768 | 2772.145 | 10495.311 | 14272.570 | 0.000 | 3534.644 | 2818.662 | 0.000 | -5262.59 | 0.000 | -5989.58 | -0.05 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 1786.453 | -1891.21 | 0.000 | 0.000 | 2942.837 | 2772.145 | 10495.311 | 6327.157 | 0.000 | 3243.738 | 2922.009 | 0.000 | -2138.06 | 0.000 | -5641.86 | -0.16 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 3405.159 | -2461.64 | 0.000 | 0.000 | 2958.375 | 2772.145 | 10495.311 | 14605.481 | 0.000 | 3534.462 | 2848.340 | 0.000 | -5020.63 | 0.000 | -6039.20 | -0.15 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 4537.950 | -2085.59 | 0.000 | 0.000 | 2969.489 | 2772.145 | 10495.311 | 10604.268 | 0.000 | 3537.490 | 1411.852 | 0.000 | -5404.96 | 0.000 | -5879.72 | -0.32 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 2473.459 | -1526.47 | 0.000 | 0.000 | 2959.293 | 2772.145 | 10495.311 | 2445.132 | 0.000 | 3246.129 | 1657.468 | 0.000 | -2238.95 | 0.000 | -5480.05 | -0.12 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 4002.279 | -2082.09 | 0.000 | 0.000 | 2971.117 | 2772.145 | 10495.311 | 10770.294 | 0.000 | 3534.469 | 1343.163 | 0.000 | -4977.96 | 0.000 | -5909.08 | -0.44 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 6468.417 | -2440.99 | 0.000 | 0.000 | 2979.271 | 2772.145 | 10495.311 | 10672.764 | 0.000 | 4889.782 | 3918.182 | 0.000 | -4975.63 | 0.000 | -7908.75 | -0.25 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 5736.963 | -2692.31 | 0.000 | 0.000 | 2970.187 | 2772.145 | 10495.311 | 14534.765 | 0.000 | 4889.750 | 3962.114 | 0.000 | -4982.71 | 0.000 | -8049.21 | -0.31 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 6248.252 | -2694.52 | 0.000 | 0.000 | 2971.634 | 2772.145 | 10495.311 | 14188.980 | 0.000 | 4890.945 | 3987.154 | 0.000 | -5209.30 | 0.000 | -7989.26 | -0.31 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 4774.811 | -1890.07 | 0.000 | 0.000 | 2970.654 | 2772.145 | 10495.311 | 2403.941 | 0.000 | 4603.821 | 4389.371 | 0.000 | -2226.28 | 0.000 | -7487.75 | -0.12 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 3884.397 | -2134.28 | 0.000 | 0.000 | 2959.159 | 2772.145 | 10495.311 | 6295.192 | 0.000 | 4600.310 | 4384.087 | 0.000 | -2114.51 | 0.000 | -7647.56 | -0.09 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 7142.705 | -2455.37 | 0.000 | 0.000 | 2978.519 | 2772.145 | 10495.311 | 10470.538 | 0.000 | 4895.087 | 3978.560 | 0.000 | -5365.55 | 0.000 | -7883.12 | -0.22 |
| HEATEDBSMT | 0.000 | 0.000 | 5469.712 | -2545.42 | 0.000 | 0.000 | 0.000 | 11905.243 | 48750.612 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -35560.13 |
| BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30558.586 | 173959.266 | 0.000 | 0.000 | 0.000 | -204517.85 | -1.02 |
| Total Facility | 0.000 | 0.000 | 90198.074 | -41173.47 | 0.000 | 0.000 | 53465.547 | 61803.859 | 237666.213 | 177130.240 | 0.000 | 108875.285 | 211767.890 | 0.000 | -73959.46 | 0.000 | -332889.36 | -39649.68 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 28-JUN-17:19 | 0.00 | 0.00 | 0.00 | -1.3 | 0.00 | 0.00 | 263.14 | 604.85 | 1668.50 | 8343.55 | 0.00 | 4009.60 | 774.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 30-JUN-16:15 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 140.34 | 434.25 | 1354.24 | 1433.06 | 0.00 | 4502.75 | 1857.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 30-JUN-16:15 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 140.35 | 434.25 | 1354.24 | 3503.13 | 0.00 | 4884.86 | 1893.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 15-JUN-17:04 | 0.00 | 0.00 | 0.00 | -1.3 | 0.00 | 0.00 | 263.16 | 604.85 | 1668.50 | 7946.47 | 0.00 | 4216.28 | 1153.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 15-JUN-18:10 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 426.75 | 814.22 | 1729.84 | 1778.08 | 0.00 | 3748.12 | 1425.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 30-JUN-16:15 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 140.34 | 434.25 | 1354.24 | 3599.92 | 0.00 | 4884.88 | 1576.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 28-JUN-17:30 | 0.00 | 0.00 | 0.00 | -1.3 | 0.00 | 0.00 | 263.14 | 604.85 | 1668.50 | 8264.83 | 0.00 | 2687.54 | 1669.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 25-AUG-17:10 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 263.15 | 604.85 | 1668.50 | 1140.43 | 0.00 | 2370.02 | 2698.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 25-AUG-13:05 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 115.09 | 116.32 | 1087.42 | 4434.21 | 0.00 | 2505.58 | 3002.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 28-JUN-18:10 | 0.00 | 0.00 | 0.00 | -1.3 | 0.00 | 0.00 | 426.74 | 814.22 | 1729.84 | 7855.69 | 0.00 | 2507.43 | 2104.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 28-JUN-18:30 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 426.74 | 814.22 | 1729.84 | 1856.71 | 0.00 | 2235.28 | 2094.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 28-JUN-18:15 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 426.75 | 814.22 | 1729.84 | 3383.71 | 0.00 | 2507.50 | 2419.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 30-JUN-16:15 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 140.34 | 434.25 | 1354.24 | 3551.85 | 0.00 | 4875.04 | 4177.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 30-JUN-16:15 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 140.34 | 434.25 | 1354.24 | 3456.78 | 0.00 | 4875.01 | 4255.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 15-JUN-17:00 | 0.00 | 0.00 | 0.00 | -1.5 | 0.00 | 0.00 | 263.15 | 604.85 | 1668.50 | 7104.66 | 0.00 | 4207.16 | 4347.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 15-JUN-18:10 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 426.75 | 814.22 | 1729.84 | 1754.10 | 0.00 | 3739.93 | 3748.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 15-JUN-18:10 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 426.73 | 814.22 | 1729.84 | 1009.89 | 0.00 | 3739.79 | 4133.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 15-JUN-17:00 | 0.00 | 0.00 | 0.00 | -1.5 | 0.00 | 0.00 | 263.16 | 604.85 | 1668.50 | 7797.88 | 0.00 | 4207.21 | 3996.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HEATEDBSMT | 28-JUN-18:30 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 0.00 | 3496.75 | 7710.48 | 0.00 | 0.00 | 0.00 | 3272.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 15-JUN-18:10 | 0.00 | 0.00 | 0.00 | -20.5 | 0.00 | 0.00 | 7681.53 | 18152.75 | 38847.64 | 68572.42 | 0.00 | 62602.57 | 82918.53 | 0.00 | 0.00 | 0.00 | -32193.9 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 07-DEC-04:00 | 0.00 | 0.00 | 9281.14 | 0.00 | 0.00 | 0.00 | 526.24 | 186.11 | 834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3229.3 | 0.00 | -5688.9 | -1909.9 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 07-DEC-04:00 | 0.00 | 0.00 | 6913.21 | 0.00 | 0.00 | 0.00 | 526.24 | 186.11 | 834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1321.9 | 0.00 | -5326.8 | -1811.5 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 07-DEC-04:00 | 0.00 | 0.00 | 9313.30 | 0.00 | 0.00 | 0.00 | 526.24 | 186.11 | 834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3232.9 | 0.00 | -5688.9 | -1938.4 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 07-DEC-04:00 | 0.00 | 0.00 | 9368.00 | 0.00 | 0.00 | 0.00 | 526.24 | 186.11 | 834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3223.0 | 0.00 | -5688.9 | -2003.0 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 07-DEC-04:00 | 0.00 | 0.00 | 7027.65 | 0.00 | 0.00 | 0.00 | 526.24 | 186.11 | 834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1316.6 | 0.00 | -5326.8 | -1931.2 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 07-DEC-04:00 | 0.00 | 0.00 | 9386.32 | 0.00 | 0.00 | 0.00 | 526.24 | 186.11 | 834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3226.8 | 0.00 | -5688.9 | -2017.5 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 07-DEC-05:00 | 0.00 | 0.00 | 7728.11 | 0.00 | 0.00 | 0.00 | 526.24 | 387.72 | 919.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3252.4 | 0.00 | -3967.6 | -2341.4 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 07-DEC-05:00 | 0.00 | 0.00 | 5164.51 | 0.00 | 0.00 | 0.00 | 526.24 | 387.72 | 919.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1340.2 | 0.00 | -3607.3 | -2050.3 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 07-DEC-05:00 | 0.00 | 0.00 | 7772.29 | 0.00 | 0.00 | 0.00 | 526.24 | 387.72 | 919.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3267.0 | 0.00 | -3967.6 | -2371.0 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 07-DEC-04:00 | 0.00 | 0.00 | 7857.67 | 0.00 | 0.00 | 0.00 | 526.24 | 186.11 | 834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3256.2 | 0.00 | -3988.3 | -2160.2 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 07-DEC-04:00 | 0.00 | 0.00 | 5349.20 | 0.00 | 0.00 | 0.00 | 526.24 | 186.11 | 834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1333.6 | 0.00 | -3625.8 | -1936.8 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 07-DEC-04:00 | 0.00 | 0.00 | 7912.36 | 0.00 | 0.00 | 0.00 | 526.24 | 186.11 | 834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3270.3 | 0.00 | -3988.3 | -2200.7 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 07-DEC-04:00 | 0.00 | 0.00 | 10869.36 | 0.00 | 0.00 | 0.00 | 526.24 | 186.11 | 834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3252.2 | 0.00 | -5699.5 | -3464.6 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 07-DEC-05:00 | 0.00 | 0.00 | 10765.78 | 0.00 | 0.00 | 0.00 | 526.24 | 387.72 | 919.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3251.2 | 0.00 | -5668.2 | -3679.7 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 07-DEC-05:00 | 0.00 | 0.00 | 10721.47 | 0.00 | 0.00 | 0.00 | 526.24 | 387.72 | 919.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3230.5 | 0.00 | -5668.2 | -3656.1 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 07-DEC-04:00 | 0.00 | 0.00 | 8297.04 | 0.00 | 0.00 | 0.00 | 526.24 | 186.11 | 834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1321.6 | 0.00 | -5336.6 | -3185.8 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 07-DEC-05:00 | 0.00 | 0.00 | 8151.13 | 0.00 | 0.00 | 0.00 | 526.24 | 387.72 | 919.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1331.3 | 0.00 | -5307.5 | -3345.6 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 07-DEC-04:00 | 0.00 | 0.00 | 10822.80 | 0.00 | 0.00 | 0.00 | 526.24 | 186.11 | 834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3231.9 | 0.00 | -5699.5 | -3438.4 |
| HEATEDBSMT | 07-DEC-03:00 | 0.00 | 0.00 | 7461.10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.42 | 4487.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12214.7 |
| BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 07-DEC-04:00 | 0.00 | 0.00 | 159884.30 | 0.00 | 0.00 | 0.00 | 9472.35 | 4149.20 | 19340.45 | 0.00 | 0.00 | 9381.81 | 0.00 | 0.00 | -46991.4 | 0.00 | -90085.3 | -65151.4 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 633.0742 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 633.0742 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 392.5820 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 392.5820 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 513.8276 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 513.8276 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 622.9565 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 622.9565 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 381.3817 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 381.3817 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 496.6362 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 496.6362 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 617.9022 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 617.9022 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 361.9975 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 361.9975 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 495.7792 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 495.7792 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 609.7356 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 609.7356 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 360.7540 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 360.7540 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 470.5591 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 470.5591 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 737.5892 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 737.5892 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 479.9508 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 479.9508 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 607.0919 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 607.0919 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 738.4881 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 738.4881 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 482.7376 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 482.7376 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 600.5620 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 600.5620 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNITHEATEDBSMT | 619.2268 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 619.2268 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
| Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 633.0742 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 633.0742 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 392.5820 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 392.5820 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 513.8276 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 513.8276 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 622.9565 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 622.9565 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 381.3817 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 381.3817 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 496.6362 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 496.6362 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 617.9022 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 617.9022 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 361.9975 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 361.9975 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 495.7792 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 495.7792 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 609.7356 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 609.7356 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 360.7540 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 360.7540 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 470.5591 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 470.5591 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 737.5892 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 737.5892 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 479.9508 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 479.9508 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 607.0919 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 607.0919 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 738.4881 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 738.4881 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 482.7376 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 482.7376 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 600.5620 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 600.5620 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNITHEATEDBSMT | 619.2268 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 619.2268 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
| AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.0000 | 0.000000 | 7794.39 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.3864 | 0.0000 | 0.0000 | 0.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 633.0742 | 633.0742 | 633.0742 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 392.5820 | 392.5820 | 392.5820 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 513.8276 | 513.8276 | 513.8276 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 622.9565 | 622.9565 | 622.9565 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 381.3817 | 381.3817 | 381.3817 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 496.6362 | 496.6362 | 496.6362 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 617.9022 | 617.9022 | 617.9022 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 361.9975 | 361.9975 | 361.9975 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 495.7792 | 495.7792 | 495.7792 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 609.7356 | 609.7356 | 609.7356 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 360.7540 | 360.7540 | 360.7540 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 470.5591 | 470.5591 | 470.5591 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 600.5620 | 600.5620 | 600.5620 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 607.0919 | 607.0919 | 607.0919 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 737.5892 | 737.5892 | 737.5892 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 482.7376 | 482.7376 | 482.7376 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 479.9508 | 479.9508 | 479.9508 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 738.4881 | 738.4881 | 738.4881 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 619.2268 | 619.2268 | 619.2268 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 633.0742 | 633.0742 | 633.0742 | 633.0742 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 392.5820 | 392.5820 | 392.5820 | 392.5820 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 513.8276 | 513.8276 | 513.8276 | 513.8276 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 622.9565 | 622.9565 | 622.9565 | 622.9565 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 381.3817 | 381.3817 | 381.3817 | 381.3817 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 496.6362 | 496.6362 | 496.6362 | 496.6362 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 617.9022 | 617.9022 | 617.9022 | 617.9022 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 361.9975 | 361.9975 | 361.9975 | 361.9975 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 495.7792 | 495.7792 | 495.7792 | 495.7792 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 609.7356 | 609.7356 | 609.7356 | 609.7356 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 360.7540 | 360.7540 | 360.7540 | 360.7540 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 470.5591 | 470.5591 | 470.5591 | 470.5591 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 737.5892 | 737.5892 | 737.5892 | 737.5892 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 479.9508 | 479.9508 | 479.9508 | 479.9508 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 607.0919 | 607.0919 | 607.0919 | 607.0919 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 738.4881 | 738.4881 | 738.4881 | 738.4881 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 482.7376 | 482.7376 | 482.7376 | 482.7376 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 600.5620 | 600.5620 | 600.5620 | 600.5620 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNITHEATEDBSMT | 619.2268 | 619.2268 | 619.2268 | 619.2268 | 0.0000 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 633.0742 | 633.0742 | 633.0742 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 392.5820 | 392.5820 | 392.5820 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 513.8276 | 513.8276 | 513.8276 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 622.9565 | 622.9565 | 622.9565 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 381.3817 | 381.3817 | 381.3817 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 496.6362 | 496.6362 | 496.6362 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 617.9022 | 617.9022 | 617.9022 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 361.9975 | 361.9975 | 361.9975 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 495.7792 | 495.7792 | 495.7792 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 609.7356 | 609.7356 | 609.7356 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 360.7540 | 360.7540 | 360.7540 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 470.5591 | 470.5591 | 470.5591 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 600.5620 | 600.5620 | 600.5620 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 607.0919 | 607.0919 | 607.0919 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 737.5892 | 737.5892 | 737.5892 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 482.7376 | 482.7376 | 482.7376 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 479.9508 | 479.9508 | 479.9508 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 738.4881 | 738.4881 | 738.4881 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 619.2268 | 619.2268 | 619.2268 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 633.0742 | 633.0742 | 633.0742 | 633.0742 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 392.5820 | 392.5820 | 392.5820 | 392.5820 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 513.8276 | 513.8276 | 513.8276 | 513.8276 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 622.9565 | 622.9565 | 622.9565 | 622.9565 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 381.3817 | 381.3817 | 381.3817 | 381.3817 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 496.6362 | 496.6362 | 496.6362 | 496.6362 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 617.9022 | 617.9022 | 617.9022 | 617.9022 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 361.9975 | 361.9975 | 361.9975 | 361.9975 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 495.7792 | 495.7792 | 495.7792 | 495.7792 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 609.7356 | 609.7356 | 609.7356 | 609.7356 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 360.7540 | 360.7540 | 360.7540 | 360.7540 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 470.5591 | 470.5591 | 470.5591 | 470.5591 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 737.5892 | 737.5892 | 737.5892 | 737.5892 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 479.9508 | 479.9508 | 479.9508 | 479.9508 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 607.0919 | 607.0919 | 607.0919 | 607.0919 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 738.4881 | 738.4881 | 738.4881 | 738.4881 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 482.7376 | 482.7376 | 482.7376 | 482.7376 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 600.5620 | 600.5620 | 600.5620 | 600.5620 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNITHEATEDBSMT | 619.2268 | 619.2268 | 619.2268 | 619.2268 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Sec1.1A-General Information| Data | |
| Weather File | ANNUAL ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
| Total gross floor area [ft2] | 39005.22 |
| Principal Heating Source | Electricity |
| Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
| BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
| ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
| Totals | 39005.22 | 29404.35 | 9600.87 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.00 |
| Number of hours not met | 0.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
| Heating -- General | 10799.01 | 20091.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 40875.60 | 22844.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- General | 18100.85 | 5896.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- Exterior-Lights | 6034.31 | 1377.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- dishwasher | 3088.82 | 985.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- refrigerator | 12036.11 | 1639.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- clotheswasher | 1577.30 | 427.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- electric_dryer | 12502.11 | 3196.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- electric_range | 9058.39 | 3721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- electric_mels | 50259.25 | 8493.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- IECC_adj | 20797.59 | 3514.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation | 7133.15 | 814.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 7735.62 | 3402.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 40115.21 | 55590.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
| Electricity | 373262.64 | 819847.05 |
| Natural Gas | 0.00 | 0.00 |
| Additional | 0.00 | 0.00 |
| Total | 373262.64 | 819847.05 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [kWh/ft2] | |
| Interior Lighting (All) | 0.46 |
| Space Heating | 0.28 |
| Space Cooling | 1.05 |
| Fans (All) | 0.38 |
| Service Water Heating | 1.03 |
| Receptacle Equipment | 2.80 |
| Miscellaneous (All) | 6.16 |
| Subtotal | 6.16 |
| Natural Gas [kWh/ft2] | |
| Space Heating | 0.00 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 0.00 |
| Subtotal | 0.00 |
| Additional [kBtu/ft2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 7.54 |
| Space Heating | 4.50 |
| Space Cooling | 17.02 |
| Fans (All) | 6.19 |
| Service Water Heating | 16.71 |
| Receptacle Equipment | 45.53 |
| Miscellaneous | 2.51 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCCUPANCY | 6031. | 8760. |
| INTERIORLIGHTING | 2852. | 8760. |
| INTERIORLIGHTINGHE | 3070. | 8760. |
| INTERIORLIGHTINGHE_OS | 2910. | 8760. |
| INTERIORLIGHTINGHE_VS | 2149. | 8760. |
| EXTERIORLIGHTING | 4380. | 4380. |
| REFRIGERATOR | 7343. | 8760. |
| MISCPLUGLOAD | 5918. | 8760. |
| COOKINGRANGE | 2434. | 8760. |
| DISHWASHER_FLOW_SCH | 3134. | 8760. |
| CLOTHESWASHER_FLOW_SCH | 3692. | 8760. |
| DISHWASHER_EQUIP_SCH | 3134. | 8760. |
| CLOTHESWASHER_EQUIP_SCH | 3692. | 8760. |
| CLOTHESDRYER | 3911. | 8760. |
| SHADING_2012IECC | 0. | 0. |
| SHADING_2012IECC_HERS | 7007. | 8760. |
| SINKSENSSCHEDULE | 6025. | 8760. |
| SINKLATSCHEDULE | 2735. | 8760. |
| SHOWERSENSSCHEDULE | 4492. | 8760. |
| SHOWERLATSCHEDULE | 4268. | 8760. |
| BATHSENSSCHEDULE | 8760. | 8760. |
| BATHLATSCHEDULE | 0. | 0. |
| First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
| HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
| COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 16:29:26
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 271.944 | 13.142 | 337.956 | 23.651 | 23.651 |
| February | 119.639 | 3.437 | 413.667 | 14.055 | 14.055 |
| March | 238.961 | 8.886 | 341.861 | 18.817 | 18.817 |
| April | 476.264 | 31.200 | 84.378 | 32.108 | 32.108 |
| May | 622.833 | 42.719 | 8.000 | 42.764 | 42.764 |
| June | 717.508 | 62.954 | 0.000 | 62.954 | 62.954 |
| July | 740.472 | 63.104 | 0.000 | 63.104 | 63.104 |
| August | 741.000 | 60.404 | 0.000 | 60.404 | 60.404 |
| September | 703.792 | 50.319 | 0.000 | 50.319 | 50.319 |
| October | 464.211 | 28.153 | 125.389 | 30.373 | 30.373 |
| November | 262.225 | 11.924 | 287.733 | 19.619 | 19.619 |
| December | 195.181 | 7.595 | 411.708 | 26.018 | 26.018 |
| Annual Sum or Average | 5554.031 | 383.838 | 2010.692 | 444.186 | 444.186 |
| Minimum of Months | 119.639 | 3.437 | 0.000 | 14.055 | 14.055 |
| Maximum of Months | 741.000 | 63.104 | 413.667 | 63.104 | 63.104 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 295.997 | 9.116 | 295.250 | 15.697 | 15.697 |
| February | 122.250 | 1.832 | 378.875 | 8.596 | 8.596 |
| March | 242.503 | 5.255 | 303.708 | 11.683 | 11.683 |
| April | 506.617 | 20.527 | 46.542 | 20.900 | 20.900 |
| May | 674.783 | 29.458 | 0.667 | 29.459 | 29.459 |
| June | 720.000 | 44.254 | 0.000 | 44.254 | 44.254 |
| July | 744.000 | 47.298 | 0.000 | 47.298 | 47.298 |
| August | 744.000 | 45.783 | 0.000 | 45.783 | 45.783 |
| September | 714.389 | 39.251 | 0.000 | 39.251 | 39.251 |
| October | 508.044 | 21.561 | 77.528 | 22.641 | 22.641 |
| November | 287.531 | 8.241 | 228.567 | 12.892 | 12.892 |
| December | 212.906 | 5.209 | 371.450 | 17.371 | 17.371 |
| Annual Sum or Average | 5773.019 | 277.785 | 1702.586 | 315.825 | 315.825 |
| Minimum of Months | 122.250 | 1.832 | 0.000 | 8.596 | 8.596 |
| Maximum of Months | 744.000 | 47.298 | 378.875 | 47.298 | 47.298 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 294.764 | 10.634 | 311.667 | 20.438 | 20.438 |
| February | 135.806 | 2.709 | 387.333 | 12.505 | 12.505 |
| March | 268.464 | 7.392 | 313.344 | 16.501 | 16.501 |
| April | 517.958 | 28.613 | 66.917 | 29.377 | 29.377 |
| May | 644.833 | 40.275 | 6.000 | 40.313 | 40.313 |
| June | 718.000 | 59.367 | 0.000 | 59.367 | 59.367 |
| July | 742.000 | 61.351 | 0.000 | 61.351 | 61.351 |
| August | 741.667 | 58.495 | 0.000 | 58.495 | 58.495 |
| September | 705.667 | 48.298 | 0.000 | 48.298 | 48.298 |
| October | 490.486 | 26.525 | 109.222 | 28.511 | 28.511 |
| November | 275.053 | 9.587 | 268.083 | 16.714 | 16.714 |
| December | 207.392 | 5.864 | 387.333 | 23.248 | 23.248 |
| Annual Sum or Average | 5742.089 | 359.111 | 1849.900 | 415.118 | 415.118 |
| Minimum of Months | 135.806 | 2.709 | 0.000 | 12.505 | 12.505 |
| Maximum of Months | 742.000 | 61.351 | 387.333 | 61.351 | 61.351 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 170.722 | 4.728 | 402.306 | 16.634 | 16.634 |
| February | 40.875 | 0.662 | 490.583 | 12.880 | 12.880 |
| March | 188.625 | 5.596 | 378.347 | 16.110 | 16.110 |
| April | 467.747 | 27.164 | 86.875 | 28.081 | 28.081 |
| May | 627.453 | 41.769 | 7.500 | 41.812 | 41.812 |
| June | 717.750 | 63.595 | 0.000 | 63.595 | 63.595 |
| July | 741.417 | 62.917 | 0.000 | 62.917 | 62.917 |
| August | 741.250 | 58.112 | 0.000 | 58.112 | 58.112 |
| September | 703.444 | 46.119 | 0.000 | 46.119 | 46.119 |
| October | 423.619 | 20.780 | 145.278 | 23.280 | 23.280 |
| November | 173.583 | 5.043 | 344.444 | 13.944 | 13.944 |
| December | 82.528 | 1.638 | 510.333 | 22.734 | 22.734 |
| Annual Sum or Average | 5079.014 | 338.124 | 2365.667 | 406.218 | 406.218 |
| Minimum of Months | 40.875 | 0.662 | 0.000 | 12.880 | 12.880 |
| Maximum of Months | 741.417 | 63.595 | 510.333 | 63.595 | 63.595 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 130.806 | 1.319 | 370.736 | 9.150 | 9.150 |
| February | 3.833 | 0.005 | 502.042 | 8.409 | 8.409 |
| March | 158.849 | 2.540 | 353.431 | 9.555 | 9.555 |
| April | 496.375 | 17.394 | 47.528 | 17.770 | 17.770 |
| May | 679.942 | 29.863 | 0.667 | 29.863 | 29.863 |
| June | 720.000 | 46.606 | 0.000 | 46.606 | 46.606 |
| July | 744.000 | 48.657 | 0.000 | 48.657 | 48.657 |
| August | 744.000 | 44.980 | 0.000 | 44.980 | 44.980 |
| September | 714.333 | 36.287 | 0.000 | 36.287 | 36.287 |
| October | 452.953 | 14.852 | 96.583 | 16.136 | 16.136 |
| November | 141.972 | 2.021 | 304.236 | 7.803 | 7.803 |
| December | 44.722 | 0.344 | 519.428 | 15.234 | 15.234 |
| Annual Sum or Average | 5031.785 | 244.868 | 2194.650 | 290.452 | 290.452 |
| Minimum of Months | 3.833 | 0.005 | 0.000 | 7.803 | 7.803 |
| Maximum of Months | 744.000 | 48.657 | 519.428 | 48.657 | 48.657 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 166.431 | 2.038 | 358.306 | 12.833 | 12.833 |
| February | 17.083 | 0.074 | 476.783 | 11.120 | 11.120 |
| March | 202.119 | 3.938 | 338.125 | 13.428 | 13.428 |
| April | 517.078 | 24.491 | 66.917 | 25.257 | 25.257 |
| May | 647.347 | 39.003 | 6.000 | 39.041 | 39.041 |
| June | 718.167 | 59.369 | 0.000 | 59.369 | 59.369 |
| July | 742.000 | 60.637 | 0.000 | 60.637 | 60.637 |
| August | 741.667 | 55.926 | 0.000 | 55.926 | 55.926 |
| September | 705.583 | 44.063 | 0.000 | 44.063 | 44.063 |
| October | 457.544 | 19.094 | 118.833 | 21.208 | 21.208 |
| November | 155.917 | 2.839 | 317.083 | 10.937 | 10.937 |
| December | 56.597 | 0.573 | 516.414 | 20.436 | 20.436 |
| Annual Sum or Average | 5127.533 | 312.046 | 2198.461 | 374.256 | 374.256 |
| Minimum of Months | 17.083 | 0.074 | 0.000 | 10.937 | 10.937 |
| Maximum of Months | 742.000 | 60.637 | 516.414 | 60.637 | 60.637 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 315.572 | 16.066 | 284.206 | 23.099 | 23.099 |
| February | 168.278 | 5.293 | 363.583 | 12.571 | 12.571 |
| March | 287.658 | 11.450 | 275.889 | 18.032 | 18.032 |
| April | 528.544 | 34.840 | 42.708 | 35.205 | 35.205 |
| May | 669.619 | 44.394 | 3.000 | 44.401 | 44.401 |
| June | 720.000 | 63.135 | 0.000 | 63.135 | 63.135 |
| July | 744.000 | 63.083 | 0.000 | 63.083 | 63.083 |
| August | 742.000 | 61.058 | 0.000 | 61.058 | 61.058 |
| September | 712.347 | 51.551 | 0.000 | 51.551 | 51.551 |
| October | 497.253 | 29.627 | 102.056 | 31.280 | 31.280 |
| November | 309.883 | 14.506 | 223.222 | 19.642 | 19.642 |
| December | 234.544 | 9.751 | 362.319 | 23.173 | 23.173 |
| Annual Sum or Average | 5929.700 | 404.755 | 1656.983 | 446.230 | 446.230 |
| Minimum of Months | 168.278 | 5.293 | 0.000 | 12.571 | 12.571 |
| Maximum of Months | 744.000 | 63.135 | 363.583 | 63.135 | 63.135 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 357.664 | 12.499 | 216.167 | 15.805 | 15.805 |
| February | 204.222 | 4.004 | 286.806 | 7.549 | 7.549 |
| March | 314.778 | 7.906 | 203.375 | 11.192 | 11.192 |
| April | 583.022 | 24.328 | 11.792 | 24.395 | 24.395 |
| May | 716.542 | 31.235 | 0.000 | 31.235 | 31.235 |
| June | 720.000 | 44.079 | 0.000 | 44.079 | 44.079 |
| July | 744.000 | 47.002 | 0.000 | 47.002 | 47.002 |
| August | 744.000 | 46.148 | 0.000 | 46.148 | 46.148 |
| September | 718.500 | 40.382 | 0.000 | 40.382 | 40.382 |
| October | 555.475 | 23.448 | 59.278 | 24.059 | 24.059 |
| November | 361.514 | 11.315 | 155.317 | 13.672 | 13.672 |
| December | 277.622 | 7.814 | 295.167 | 15.030 | 15.030 |
| Annual Sum or Average | 6297.339 | 300.161 | 1227.900 | 320.548 | 320.548 |
| Minimum of Months | 204.222 | 4.004 | 0.000 | 7.549 | 7.549 |
| Maximum of Months | 744.000 | 47.002 | 295.167 | 47.002 | 47.002 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 341.642 | 13.611 | 258.917 | 20.117 | 20.117 |
| February | 198.053 | 4.827 | 333.942 | 11.469 | 11.469 |
| March | 325.514 | 10.159 | 241.917 | 16.091 | 16.091 |
| April | 568.164 | 32.497 | 30.250 | 32.788 | 32.788 |
| May | 686.897 | 41.968 | 2.167 | 41.973 | 41.973 |
| June | 720.000 | 59.461 | 0.000 | 59.461 | 59.461 |
| July | 743.833 | 61.169 | 0.000 | 61.169 | 61.169 |
| August | 742.167 | 58.907 | 0.000 | 58.907 | 58.907 |
| September | 713.667 | 49.244 | 0.000 | 49.244 | 49.244 |
| October | 524.589 | 27.992 | 86.167 | 29.426 | 29.426 |
| November | 326.919 | 12.145 | 203.889 | 16.852 | 16.852 |
| December | 252.578 | 8.068 | 336.444 | 20.655 | 20.655 |
| Annual Sum or Average | 6144.022 | 380.048 | 1493.692 | 418.152 | 418.152 |
| Minimum of Months | 198.053 | 4.827 | 0.000 | 11.469 | 11.469 |
| Maximum of Months | 743.833 | 61.169 | 336.444 | 61.169 | 61.169 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 212.500 | 5.894 | 349.139 | 14.334 | 14.334 |
| February | 77.458 | 1.179 | 434.639 | 9.957 | 9.957 |
| March | 242.060 | 7.445 | 311.233 | 14.564 | 14.564 |
| April | 520.042 | 30.653 | 44.044 | 31.024 | 31.024 |
| May | 674.486 | 43.657 | 2.833 | 43.663 | 43.663 |
| June | 720.000 | 64.096 | 0.000 | 64.096 | 64.096 |
| July | 744.000 | 63.105 | 0.000 | 63.105 | 63.105 |
| August | 742.000 | 58.830 | 0.000 | 58.830 | 58.830 |
| September | 712.083 | 47.238 | 0.000 | 47.238 | 47.238 |
| October | 449.572 | 21.632 | 126.875 | 23.604 | 23.604 |
| November | 219.444 | 6.208 | 280.056 | 12.541 | 12.541 |
| December | 111.417 | 2.116 | 464.039 | 18.341 | 18.341 |
| Annual Sum or Average | 5425.062 | 352.052 | 2012.858 | 401.297 | 401.297 |
| Minimum of Months | 77.458 | 1.179 | 0.000 | 9.957 | 9.957 |
| Maximum of Months | 744.000 | 64.096 | 464.039 | 64.096 | 64.096 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 188.500 | 2.210 | 296.317 | 6.666 | 6.666 |
| February | 39.861 | 0.223 | 387.917 | 5.126 | 5.126 |
| March | 230.260 | 4.074 | 249.431 | 7.831 | 7.831 |
| April | 575.300 | 20.532 | 12.467 | 20.600 | 20.600 |
| May | 718.778 | 31.099 | 0.000 | 31.099 | 31.099 |
| June | 720.000 | 45.731 | 0.000 | 45.731 | 45.731 |
| July | 744.000 | 47.694 | 0.000 | 47.694 | 47.694 |
| August | 744.000 | 44.597 | 0.000 | 44.597 | 44.597 |
| September | 718.500 | 36.631 | 0.000 | 36.631 | 36.631 |
| October | 490.136 | 15.609 | 81.511 | 16.440 | 16.440 |
| November | 203.736 | 3.068 | 225.833 | 6.443 | 6.443 |
| December | 63.417 | 0.622 | 457.489 | 10.489 | 10.489 |
| Annual Sum or Average | 5436.488 | 252.090 | 1710.964 | 279.346 | 279.346 |
| Minimum of Months | 39.861 | 0.223 | 0.000 | 5.126 | 5.126 |
| Maximum of Months | 744.000 | 47.694 | 457.489 | 47.694 | 47.694 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 212.917 | 3.100 | 303.833 | 10.616 | 10.616 |
| February | 55.942 | 0.418 | 395.972 | 8.122 | 8.122 |
| March | 264.986 | 5.875 | 264.067 | 12.135 | 12.135 |
| April | 566.872 | 28.179 | 30.417 | 28.473 | 28.473 |
| May | 688.764 | 40.710 | 2.167 | 40.715 | 40.715 |
| June | 720.000 | 59.525 | 0.000 | 59.525 | 59.525 |
| July | 744.000 | 60.459 | 0.000 | 60.459 | 60.459 |
| August | 742.167 | 56.248 | 0.000 | 56.248 | 56.248 |
| September | 713.667 | 44.820 | 0.000 | 44.820 | 44.820 |
| October | 483.628 | 19.910 | 97.056 | 21.502 | 21.502 |
| November | 202.158 | 3.801 | 251.833 | 9.474 | 9.474 |
| December | 76.333 | 0.908 | 470.636 | 16.030 | 16.030 |
| Annual Sum or Average | 5471.433 | 323.952 | 1815.981 | 368.118 | 368.118 |
| Minimum of Months | 55.942 | 0.418 | 0.000 | 8.122 | 8.122 |
| Maximum of Months | 744.000 | 60.459 | 470.636 | 60.459 | 60.459 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 280.639 | 15.448 | 328.622 | 27.009 | 27.009 |
| February | 135.917 | 4.514 | 405.583 | 16.413 | 16.413 |
| March | 257.375 | 11.617 | 329.361 | 22.349 | 22.349 |
| April | 499.250 | 39.074 | 70.167 | 39.934 | 39.934 |
| May | 630.239 | 50.931 | 9.200 | 50.988 | 50.988 |
| June | 718.100 | 74.895 | 0.000 | 74.895 | 74.895 |
| July | 741.167 | 74.349 | 0.000 | 74.349 | 74.349 |
| August | 739.500 | 70.736 | 0.000 | 70.736 | 70.736 |
| September | 701.767 | 58.261 | 0.000 | 58.261 | 58.261 |
| October | 453.956 | 31.202 | 145.472 | 34.380 | 34.380 |
| November | 266.397 | 13.805 | 278.250 | 22.539 | 22.539 |
| December | 201.208 | 8.826 | 409.972 | 29.606 | 29.606 |
| Annual Sum or Average | 5625.514 | 453.658 | 1976.628 | 521.460 | 521.460 |
| Minimum of Months | 135.917 | 4.514 | 0.000 | 16.413 | 16.413 |
| Maximum of Months | 741.167 | 74.895 | 409.972 | 74.895 | 74.895 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 307.300 | 11.758 | 281.806 | 18.917 | 18.917 |
| February | 146.972 | 3.083 | 366.750 | 10.659 | 10.659 |
| March | 267.581 | 8.030 | 281.806 | 14.874 | 14.874 |
| April | 536.931 | 28.575 | 39.764 | 28.911 | 28.911 |
| May | 677.861 | 37.796 | 1.333 | 37.799 | 37.799 |
| June | 720.000 | 55.999 | 0.000 | 55.999 | 55.999 |
| July | 744.000 | 58.537 | 0.000 | 58.537 | 58.537 |
| August | 744.000 | 56.165 | 0.000 | 56.165 | 56.165 |
| September | 712.931 | 47.427 | 0.000 | 47.427 | 47.427 |
| October | 490.883 | 24.947 | 98.292 | 26.642 | 26.642 |
| November | 294.042 | 10.437 | 220.497 | 15.739 | 15.739 |
| December | 221.792 | 6.698 | 364.917 | 20.500 | 20.500 |
| Annual Sum or Average | 5864.292 | 349.452 | 1655.164 | 392.169 | 392.169 |
| Minimum of Months | 146.972 | 3.083 | 0.000 | 10.659 | 10.659 |
| Maximum of Months | 744.000 | 58.537 | 366.750 | 58.537 | 58.537 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 304.708 | 12.823 | 302.556 | 23.593 | 23.593 |
| February | 152.292 | 3.759 | 379.658 | 14.710 | 14.710 |
| March | 281.458 | 10.057 | 299.083 | 19.834 | 19.834 |
| April | 542.419 | 36.526 | 52.333 | 37.213 | 37.213 |
| May | 655.342 | 48.465 | 6.583 | 48.511 | 48.511 |
| June | 718.500 | 71.190 | 0.000 | 71.190 | 71.190 |
| July | 742.000 | 72.621 | 0.000 | 72.621 | 72.621 |
| August | 740.333 | 68.877 | 0.000 | 68.877 | 68.877 |
| September | 704.653 | 56.253 | 0.000 | 56.253 | 56.253 |
| October | 481.678 | 29.509 | 124.250 | 32.291 | 32.291 |
| November | 282.033 | 11.351 | 258.083 | 19.436 | 19.436 |
| December | 212.358 | 7.002 | 386.944 | 26.618 | 26.618 |
| Annual Sum or Average | 5817.775 | 428.434 | 1809.492 | 491.149 | 491.149 |
| Minimum of Months | 152.292 | 3.759 | 0.000 | 14.710 | 14.710 |
| Maximum of Months | 742.000 | 72.621 | 386.944 | 72.621 | 72.621 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 204.028 | 7.342 | 383.339 | 20.508 | 20.508 |
| February | 78.681 | 1.654 | 460.583 | 15.154 | 15.154 |
| March | 231.033 | 9.204 | 351.083 | 20.427 | 20.427 |
| April | 492.892 | 36.965 | 71.886 | 37.835 | 37.835 |
| May | 634.208 | 50.851 | 8.417 | 50.905 | 50.905 |
| June | 718.250 | 75.947 | 0.000 | 75.947 | 75.947 |
| July | 741.861 | 74.813 | 0.000 | 74.813 | 74.813 |
| August | 739.667 | 69.886 | 0.000 | 69.886 | 69.886 |
| September | 701.358 | 55.868 | 0.000 | 55.868 | 55.868 |
| October | 419.361 | 25.526 | 165.750 | 29.108 | 29.108 |
| November | 202.056 | 7.366 | 328.347 | 17.477 | 17.477 |
| December | 113.583 | 2.839 | 486.319 | 26.605 | 26.605 |
| Annual Sum or Average | 5276.978 | 418.262 | 2255.725 | 494.534 | 494.534 |
| Minimum of Months | 78.681 | 1.654 | 0.000 | 15.154 | 15.154 |
| Maximum of Months | 741.861 | 75.947 | 486.319 | 75.947 | 75.947 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 190.472 | 3.347 | 352.111 | 12.042 | 12.042 |
| February | 52.167 | 0.439 | 442.167 | 9.688 | 9.688 |
| March | 224.327 | 5.647 | 311.333 | 13.001 | 13.001 |
| April | 531.486 | 26.750 | 41.044 | 27.092 | 27.092 |
| May | 681.753 | 38.157 | 0.833 | 38.158 | 38.158 |
| June | 720.000 | 57.610 | 0.000 | 57.610 | 57.610 |
| July | 744.000 | 59.481 | 0.000 | 59.481 | 59.481 |
| August | 744.000 | 55.765 | 0.000 | 55.765 | 55.765 |
| September | 712.833 | 45.392 | 0.000 | 45.392 | 45.392 |
| October | 442.336 | 19.320 | 121.917 | 21.357 | 21.357 |
| November | 185.264 | 3.975 | 285.194 | 10.659 | 10.659 |
| December | 74.667 | 1.062 | 493.333 | 18.040 | 18.040 |
| Annual Sum or Average | 5303.305 | 316.945 | 2047.933 | 368.284 | 368.284 |
| Minimum of Months | 52.167 | 0.439 | 0.000 | 9.688 | 9.688 |
| Maximum of Months | 744.000 | 59.481 | 493.333 | 59.481 | 59.481 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 208.819 | 4.373 | 348.850 | 16.377 | 16.377 |
| February | 67.694 | 0.818 | 436.833 | 13.107 | 13.107 |
| March | 247.828 | 7.513 | 315.292 | 17.648 | 17.648 |
| April | 541.150 | 34.394 | 52.500 | 35.084 | 35.084 |
| May | 657.069 | 48.221 | 6.417 | 48.265 | 48.265 |
| June | 718.667 | 71.879 | 0.000 | 71.879 | 71.879 |
| July | 742.167 | 72.765 | 0.000 | 72.765 | 72.765 |
| August | 740.500 | 67.849 | 0.000 | 67.849 | 67.849 |
| September | 704.431 | 53.846 | 0.000 | 53.846 | 53.846 |
| October | 448.314 | 23.748 | 138.167 | 26.767 | 26.767 |
| November | 190.450 | 4.905 | 303.347 | 14.170 | 14.170 |
| December | 88.667 | 1.431 | 497.444 | 23.931 | 23.931 |
| Annual Sum or Average | 5355.756 | 391.742 | 2098.850 | 461.687 | 461.687 |
| Minimum of Months | 67.694 | 0.818 | 0.000 | 13.107 | 13.107 |
| Maximum of Months | 742.167 | 72.765 | 497.444 | 72.765 | 72.765 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 0.000 | 0.000 | 342.928 | 10.341 | 10.341 |
| February | 0.000 | 0.000 | 450.750 | 14.992 | 14.992 |
| March | 0.000 | 0.000 | 376.628 | 10.683 | 10.683 |
| April | 217.833 | 9.953 | 18.333 | 10.062 | 10.062 |
| May | 741.500 | 57.231 | 0.000 | 57.231 | 57.231 |
| June | 720.000 | 95.065 | 0.000 | 95.065 | 95.065 |
| July | 744.000 | 94.015 | 0.000 | 94.015 | 94.015 |
| August | 744.000 | 91.544 | 0.000 | 91.544 | 91.544 |
| September | 720.000 | 75.225 | 0.000 | 75.225 | 75.225 |
| October | 679.194 | 45.241 | 0.000 | 45.241 | 45.241 |
| November | 38.681 | 0.728 | 172.125 | 3.579 | 3.579 |
| December | 0.000 | 0.000 | 437.389 | 18.608 | 18.608 |
| Annual Sum or Average | 4605.208 | 469.002 | 1798.153 | 526.588 | 526.588 |
| Minimum of Months | 0.000 | 0.000 | 0.000 | 3.579 | 3.579 |
| Maximum of Months | 744.000 | 95.065 | 450.750 | 95.065 | 95.065 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1285.59 | 0.00 | 0.00 |
| February | 1482.08 | 0.00 | 0.00 |
| March | 1193.91 | 0.00 | 0.00 |
| April | 130.42 | 0.00 | 0.00 |
| May | 6.43 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 285.95 | 0.00 | 0.00 |
| November | 972.12 | 0.00 | 0.00 |
| December | 1996.72 | 0.00 | 0.00 |
| Annual Sum or Average | 609.32 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1996.72 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 797.97 | 0.00 | 0.00 |
| February | 940.06 | 0.00 | 0.00 |
| March | 765.09 | 0.00 | 0.00 |
| April | 52.40 | 0.00 | 0.00 |
| May | 0.11 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 136.07 | 0.00 | 0.00 |
| November | 579.20 | 0.00 | 0.00 |
| December | 1307.48 | 0.00 | 0.00 |
| Annual Sum or Average | 379.39 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1307.48 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1197.30 | 0.00 | 0.00 |
| February | 1368.51 | 0.00 | 0.00 |
| March | 1088.08 | 0.00 | 0.00 |
| April | 108.67 | 0.00 | 0.00 |
| May | 5.42 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 255.42 | 0.00 | 0.00 |
| November | 899.79 | 0.00 | 0.00 |
| December | 1884.50 | 0.00 | 0.00 |
| Annual Sum or Average | 564.18 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1884.50 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1482.79 | 0.00 | 0.00 |
| February | 1729.28 | 0.00 | 0.00 |
| March | 1278.59 | 0.00 | 0.00 |
| April | 131.81 | 0.00 | 0.00 |
| May | 6.06 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 326.00 | 0.00 | 0.00 |
| November | 1144.73 | 0.00 | 0.00 |
| December | 2352.84 | 0.00 | 0.00 |
| Annual Sum or Average | 700.14 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2352.84 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 971.49 | 0.00 | 0.00 |
| February | 1192.70 | 0.00 | 0.00 |
| March | 849.29 | 0.00 | 0.00 |
| April | 52.81 | 0.00 | 0.00 |
| May | 0.07 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 164.39 | 0.00 | 0.00 |
| November | 738.54 | 0.00 | 0.00 |
| December | 1668.26 | 0.00 | 0.00 |
| Annual Sum or Average | 466.83 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1668.26 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1330.32 | 0.00 | 0.00 |
| February | 1557.48 | 0.00 | 0.00 |
| March | 1141.65 | 0.00 | 0.00 |
| April | 109.25 | 0.00 | 0.00 |
| May | 5.32 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 272.77 | 0.00 | 0.00 |
| November | 1033.22 | 0.00 | 0.00 |
| December | 2209.21 | 0.00 | 0.00 |
| Annual Sum or Average | 634.58 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2209.21 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 845.75 | 0.00 | 0.00 |
| February | 1002.75 | 0.00 | 0.00 |
| March | 772.07 | 0.00 | 0.00 |
| April | 51.14 | 0.00 | 0.00 |
| May | 0.98 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 211.34 | 0.00 | 0.00 |
| November | 634.83 | 0.00 | 0.00 |
| December | 1425.84 | 0.00 | 0.00 |
| Annual Sum or Average | 409.84 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1425.84 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 388.19 | 0.00 | 0.00 |
| February | 481.41 | 0.00 | 0.00 |
| March | 374.84 | 0.00 | 0.00 |
| April | 8.92 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 76.27 | 0.00 | 0.00 |
| November | 282.76 | 0.00 | 0.00 |
| December | 749.56 | 0.00 | 0.00 |
| Annual Sum or Average | 195.85 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 749.56 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 777.21 | 0.00 | 0.00 |
| February | 913.07 | 0.00 | 0.00 |
| March | 684.97 | 0.00 | 0.00 |
| April | 40.09 | 0.00 | 0.00 |
| May | 0.72 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 181.90 | 0.00 | 0.00 |
| November | 578.71 | 0.00 | 0.00 |
| December | 1330.54 | 0.00 | 0.00 |
| Annual Sum or Average | 373.60 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1330.54 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1040.03 | 0.00 | 0.00 |
| February | 1230.03 | 0.00 | 0.00 |
| March | 847.72 | 0.00 | 0.00 |
| April | 52.14 | 0.00 | 0.00 |
| May | 0.83 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 257.15 | 0.00 | 0.00 |
| November | 802.21 | 0.00 | 0.00 |
| December | 1785.77 | 0.00 | 0.00 |
| Annual Sum or Average | 498.49 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1785.77 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 540.68 | 0.00 | 0.00 |
| February | 683.24 | 0.00 | 0.00 |
| March | 438.23 | 0.00 | 0.00 |
| April | 9.07 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 106.57 | 0.00 | 0.00 |
| November | 420.00 | 0.00 | 0.00 |
| December | 1079.39 | 0.00 | 0.00 |
| Annual Sum or Average | 271.54 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1079.39 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 908.06 | 0.00 | 0.00 |
| February | 1067.52 | 0.00 | 0.00 |
| March | 728.07 | 0.00 | 0.00 |
| April | 40.64 | 0.00 | 0.00 |
| May | 0.71 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 202.89 | 0.00 | 0.00 |
| November | 707.19 | 0.00 | 0.00 |
| December | 1645.44 | 0.00 | 0.00 |
| Annual Sum or Average | 439.36 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1645.44 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1416.01 | 0.00 | 0.00 |
| February | 1663.34 | 0.00 | 0.00 |
| March | 1290.70 | 0.00 | 0.00 |
| April | 123.51 | 0.00 | 0.00 |
| May | 8.33 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 416.53 | 0.00 | 0.00 |
| November | 1105.54 | 0.00 | 0.00 |
| December | 2258.02 | 0.00 | 0.00 |
| Annual Sum or Average | 686.36 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2258.02 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 867.45 | 0.00 | 0.00 |
| February | 1053.80 | 0.00 | 0.00 |
| March | 812.64 | 0.00 | 0.00 |
| April | 47.33 | 0.00 | 0.00 |
| May | 0.32 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 218.38 | 0.00 | 0.00 |
| November | 660.78 | 0.00 | 0.00 |
| December | 1485.50 | 0.00 | 0.00 |
| Annual Sum or Average | 426.47 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1485.50 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1310.92 | 0.00 | 0.00 |
| February | 1527.01 | 0.00 | 0.00 |
| March | 1159.60 | 0.00 | 0.00 |
| April | 96.69 | 0.00 | 0.00 |
| May | 6.48 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 361.07 | 0.00 | 0.00 |
| November | 1017.81 | 0.00 | 0.00 |
| December | 2122.10 | 0.00 | 0.00 |
| Annual Sum or Average | 630.02 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2122.10 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1642.96 | 0.00 | 0.00 |
| February | 1908.49 | 0.00 | 0.00 |
| March | 1360.78 | 0.00 | 0.00 |
| April | 125.17 | 0.00 | 0.00 |
| May | 7.78 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 475.82 | 0.00 | 0.00 |
| November | 1303.02 | 0.00 | 0.00 |
| December | 2650.65 | 0.00 | 0.00 |
| Annual Sum or Average | 785.10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2650.65 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1079.25 | 0.00 | 0.00 |
| February | 1306.80 | 0.00 | 0.00 |
| March | 883.28 | 0.00 | 0.00 |
| April | 48.13 | 0.00 | 0.00 |
| May | 0.23 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 267.33 | 0.00 | 0.00 |
| November | 854.23 | 0.00 | 0.00 |
| December | 1894.15 | 0.00 | 0.00 |
| Annual Sum or Average | 524.69 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1894.15 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1475.22 | 0.00 | 0.00 |
| February | 1725.65 | 0.00 | 0.00 |
| March | 1208.00 | 0.00 | 0.00 |
| April | 97.24 | 0.00 | 0.00 |
| May | 6.30 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 393.52 | 0.00 | 0.00 |
| November | 1179.05 | 0.00 | 0.00 |
| December | 2490.45 | 0.00 | 0.00 |
| Annual Sum or Average | 710.64 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2490.45 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNITHEATEDBSMT
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1296.95 | 0.00 | 0.00 |
| February | 2179.14 | 0.00 | 0.00 |
| March | 1344.62 | 0.00 | 0.00 |
| April | 14.91 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 352.82 | 0.00 | 0.00 |
| December | 2116.76 | 0.00 | 0.00 |
| Annual Sum or Average | 601.52 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2179.14 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNITHEATEDBSMT
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.12 |
| February | 0.00 | 0.00 | 0.04 |
| March | 0.00 | 0.00 | 0.08 |
| April | 0.00 | 0.00 | 0.29 |
| May | 0.00 | 0.00 | 0.37 |
| June | 0.00 | 0.00 | 0.56 |
| July | 0.00 | 0.00 | 0.58 |
| August | 0.00 | 0.00 | 0.56 |
| September | 0.00 | 0.00 | 0.49 |
| October | 0.00 | 0.00 | 0.26 |
| November | 0.00 | 0.00 | 0.11 |
| December | 0.00 | 0.00 | 0.07 |
| Annual Sum or Average | 0.00 | 0.00 | 0.30 |
| Minimum of Months | 0.00 | 0.00 | 0.04 |
| Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.09 |
| February | 0.00 | 0.00 | 0.02 |
| March | 0.00 | 0.00 | 0.05 |
| April | 0.00 | 0.00 | 0.20 |
| May | 0.00 | 0.00 | 0.28 |
| June | 0.00 | 0.00 | 0.43 |
| July | 0.00 | 0.00 | 0.48 |
| August | 0.00 | 0.00 | 0.46 |
| September | 0.00 | 0.00 | 0.41 |
| October | 0.00 | 0.00 | 0.21 |
| November | 0.00 | 0.00 | 0.08 |
| December | 0.00 | 0.00 | 0.05 |
| Annual Sum or Average | 0.00 | 0.00 | 0.23 |
| Minimum of Months | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 0.00 | 0.00 | 0.48 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.10 |
| February | 0.00 | 0.00 | 0.03 |
| March | 0.00 | 0.00 | 0.07 |
| April | 0.00 | 0.00 | 0.28 |
| May | 0.00 | 0.00 | 0.38 |
| June | 0.00 | 0.00 | 0.57 |
| July | 0.00 | 0.00 | 0.61 |
| August | 0.00 | 0.00 | 0.58 |
| September | 0.00 | 0.00 | 0.50 |
| October | 0.00 | 0.00 | 0.26 |
| November | 0.00 | 0.00 | 0.10 |
| December | 0.00 | 0.00 | 0.06 |
| Annual Sum or Average | 0.00 | 0.00 | 0.30 |
| Minimum of Months | 0.00 | 0.00 | 0.03 |
| Maximum of Months | 0.00 | 0.00 | 0.61 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.04 |
| February | 0.00 | 0.00 | 0.01 |
| March | 0.00 | 0.00 | 0.05 |
| April | 0.00 | 0.00 | 0.25 |
| May | 0.00 | 0.00 | 0.37 |
| June | 0.00 | 0.00 | 0.57 |
| July | 0.00 | 0.00 | 0.58 |
| August | 0.00 | 0.00 | 0.54 |
| September | 0.00 | 0.00 | 0.44 |
| October | 0.00 | 0.00 | 0.19 |
| November | 0.00 | 0.00 | 0.05 |
| December | 0.00 | 0.00 | 0.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.26 |
| Minimum of Months | 0.00 | 0.00 | 0.01 |
| Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.01 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.02 |
| April | 0.00 | 0.00 | 0.16 |
| May | 0.00 | 0.00 | 0.27 |
| June | 0.00 | 0.00 | 0.43 |
| July | 0.00 | 0.00 | 0.47 |
| August | 0.00 | 0.00 | 0.43 |
| September | 0.00 | 0.00 | 0.37 |
| October | 0.00 | 0.00 | 0.14 |
| November | 0.00 | 0.00 | 0.02 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.20 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.47 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.02 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.04 |
| April | 0.00 | 0.00 | 0.24 |
| May | 0.00 | 0.00 | 0.37 |
| June | 0.00 | 0.00 | 0.58 |
| July | 0.00 | 0.00 | 0.61 |
| August | 0.00 | 0.00 | 0.56 |
| September | 0.00 | 0.00 | 0.46 |
| October | 0.00 | 0.00 | 0.19 |
| November | 0.00 | 0.00 | 0.03 |
| December | 0.00 | 0.00 | 0.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.26 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.61 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.15 |
| February | 0.00 | 0.00 | 0.05 |
| March | 0.00 | 0.00 | 0.10 |
| April | 0.00 | 0.00 | 0.32 |
| May | 0.00 | 0.00 | 0.39 |
| June | 0.00 | 0.00 | 0.56 |
| July | 0.00 | 0.00 | 0.58 |
| August | 0.00 | 0.00 | 0.56 |
| September | 0.00 | 0.00 | 0.50 |
| October | 0.00 | 0.00 | 0.27 |
| November | 0.00 | 0.00 | 0.14 |
| December | 0.00 | 0.00 | 0.09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.31 |
| Minimum of Months | 0.00 | 0.00 | 0.05 |
| Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.12 |
| February | 0.00 | 0.00 | 0.04 |
| March | 0.00 | 0.00 | 0.08 |
| April | 0.00 | 0.00 | 0.24 |
| May | 0.00 | 0.00 | 0.29 |
| June | 0.00 | 0.00 | 0.42 |
| July | 0.00 | 0.00 | 0.46 |
| August | 0.00 | 0.00 | 0.45 |
| September | 0.00 | 0.00 | 0.42 |
| October | 0.00 | 0.00 | 0.23 |
| November | 0.00 | 0.00 | 0.11 |
| December | 0.00 | 0.00 | 0.07 |
| Annual Sum or Average | 0.00 | 0.00 | 0.25 |
| Minimum of Months | 0.00 | 0.00 | 0.04 |
| Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.13 |
| February | 0.00 | 0.00 | 0.05 |
| March | 0.00 | 0.00 | 0.10 |
| April | 0.00 | 0.00 | 0.32 |
| May | 0.00 | 0.00 | 0.40 |
| June | 0.00 | 0.00 | 0.58 |
| July | 0.00 | 0.00 | 0.61 |
| August | 0.00 | 0.00 | 0.59 |
| September | 0.00 | 0.00 | 0.51 |
| October | 0.00 | 0.00 | 0.28 |
| November | 0.00 | 0.00 | 0.12 |
| December | 0.00 | 0.00 | 0.08 |
| Annual Sum or Average | 0.00 | 0.00 | 0.32 |
| Minimum of Months | 0.00 | 0.00 | 0.05 |
| Maximum of Months | 0.00 | 0.00 | 0.61 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.05 |
| February | 0.00 | 0.00 | 0.01 |
| March | 0.00 | 0.00 | 0.07 |
| April | 0.00 | 0.00 | 0.28 |
| May | 0.00 | 0.00 | 0.38 |
| June | 0.00 | 0.00 | 0.57 |
| July | 0.00 | 0.00 | 0.58 |
| August | 0.00 | 0.00 | 0.54 |
| September | 0.00 | 0.00 | 0.45 |
| October | 0.00 | 0.00 | 0.20 |
| November | 0.00 | 0.00 | 0.06 |
| December | 0.00 | 0.00 | 0.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.27 |
| Minimum of Months | 0.00 | 0.00 | 0.01 |
| Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.02 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.04 |
| April | 0.00 | 0.00 | 0.19 |
| May | 0.00 | 0.00 | 0.28 |
| June | 0.00 | 0.00 | 0.42 |
| July | 0.00 | 0.00 | 0.46 |
| August | 0.00 | 0.00 | 0.43 |
| September | 0.00 | 0.00 | 0.37 |
| October | 0.00 | 0.00 | 0.15 |
| November | 0.00 | 0.00 | 0.03 |
| December | 0.00 | 0.00 | 0.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.20 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.03 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.06 |
| April | 0.00 | 0.00 | 0.28 |
| May | 0.00 | 0.00 | 0.39 |
| June | 0.00 | 0.00 | 0.58 |
| July | 0.00 | 0.00 | 0.61 |
| August | 0.00 | 0.00 | 0.56 |
| September | 0.00 | 0.00 | 0.47 |
| October | 0.00 | 0.00 | 0.20 |
| November | 0.00 | 0.00 | 0.04 |
| December | 0.00 | 0.00 | 0.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.27 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.61 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.14 |
| February | 0.00 | 0.00 | 0.05 |
| March | 0.00 | 0.00 | 0.10 |
| April | 0.00 | 0.00 | 0.36 |
| May | 0.00 | 0.00 | 0.44 |
| June | 0.00 | 0.00 | 0.66 |
| July | 0.00 | 0.00 | 0.67 |
| August | 0.00 | 0.00 | 0.64 |
| September | 0.00 | 0.00 | 0.55 |
| October | 0.00 | 0.00 | 0.28 |
| November | 0.00 | 0.00 | 0.13 |
| December | 0.00 | 0.00 | 0.08 |
| Annual Sum or Average | 0.00 | 0.00 | 0.34 |
| Minimum of Months | 0.00 | 0.00 | 0.05 |
| Maximum of Months | 0.00 | 0.00 | 0.67 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.11 |
| February | 0.00 | 0.00 | 0.03 |
| March | 0.00 | 0.00 | 0.07 |
| April | 0.00 | 0.00 | 0.27 |
| May | 0.00 | 0.00 | 0.34 |
| June | 0.00 | 0.00 | 0.51 |
| July | 0.00 | 0.00 | 0.56 |
| August | 0.00 | 0.00 | 0.53 |
| September | 0.00 | 0.00 | 0.47 |
| October | 0.00 | 0.00 | 0.23 |
| November | 0.00 | 0.00 | 0.10 |
| December | 0.00 | 0.00 | 0.06 |
| Annual Sum or Average | 0.00 | 0.00 | 0.28 |
| Minimum of Months | 0.00 | 0.00 | 0.03 |
| Maximum of Months | 0.00 | 0.00 | 0.56 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.12 |
| February | 0.00 | 0.00 | 0.04 |
| March | 0.00 | 0.00 | 0.10 |
| April | 0.00 | 0.00 | 0.35 |
| May | 0.00 | 0.00 | 0.45 |
| June | 0.00 | 0.00 | 0.67 |
| July | 0.00 | 0.00 | 0.70 |
| August | 0.00 | 0.00 | 0.67 |
| September | 0.00 | 0.00 | 0.57 |
| October | 0.00 | 0.00 | 0.28 |
| November | 0.00 | 0.00 | 0.11 |
| December | 0.00 | 0.00 | 0.07 |
| Annual Sum or Average | 0.00 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.04 |
| Maximum of Months | 0.00 | 0.00 | 0.70 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.06 |
| February | 0.00 | 0.00 | 0.02 |
| March | 0.00 | 0.00 | 0.08 |
| April | 0.00 | 0.00 | 0.33 |
| May | 0.00 | 0.00 | 0.44 |
| June | 0.00 | 0.00 | 0.67 |
| July | 0.00 | 0.00 | 0.68 |
| August | 0.00 | 0.00 | 0.63 |
| September | 0.00 | 0.00 | 0.53 |
| October | 0.00 | 0.00 | 0.23 |
| November | 0.00 | 0.00 | 0.07 |
| December | 0.00 | 0.00 | 0.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.31 |
| Minimum of Months | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 0.00 | 0.00 | 0.68 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.03 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.05 |
| April | 0.00 | 0.00 | 0.25 |
| May | 0.00 | 0.00 | 0.34 |
| June | 0.00 | 0.00 | 0.52 |
| July | 0.00 | 0.00 | 0.56 |
| August | 0.00 | 0.00 | 0.52 |
| September | 0.00 | 0.00 | 0.44 |
| October | 0.00 | 0.00 | 0.18 |
| November | 0.00 | 0.00 | 0.04 |
| December | 0.00 | 0.00 | 0.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.25 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.56 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.04 |
| February | 0.00 | 0.00 | 0.01 |
| March | 0.00 | 0.00 | 0.07 |
| April | 0.00 | 0.00 | 0.33 |
| May | 0.00 | 0.00 | 0.44 |
| June | 0.00 | 0.00 | 0.68 |
| July | 0.00 | 0.00 | 0.70 |
| August | 0.00 | 0.00 | 0.66 |
| September | 0.00 | 0.00 | 0.54 |
| October | 0.00 | 0.00 | 0.23 |
| November | 0.00 | 0.00 | 0.05 |
| December | 0.00 | 0.00 | 0.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.32 |
| Minimum of Months | 0.00 | 0.00 | 0.01 |
| Maximum of Months | 0.00 | 0.00 | 0.70 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.09 |
| May | 0.00 | 0.00 | 0.47 |
| June | 0.00 | 0.00 | 0.81 |
| July | 0.00 | 0.00 | 0.78 |
| August | 0.00 | 0.00 | 0.76 |
| September | 0.00 | 0.00 | 0.65 |
| October | 0.00 | 0.00 | 0.38 |
| November | 0.00 | 0.00 | 0.01 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.33 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.81 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1092.01 | 813.03 |
| February | 0.00 | 0.00 | 1081.44 | 727.24 |
| March | 0.00 | 0.00 | 1009.31 | 751.46 |
| April | 0.00 | 0.00 | 904.03 | 651.36 |
| May | 0.00 | 0.00 | 783.61 | 583.42 |
| June | 0.00 | 0.00 | 689.57 | 496.84 |
| July | 0.00 | 0.00 | 645.00 | 480.22 |
| August | 0.00 | 0.00 | 656.50 | 488.78 |
| September | 0.00 | 0.00 | 728.28 | 524.73 |
| October | 0.00 | 0.00 | 838.27 | 624.12 |
| November | 0.00 | 0.00 | 954.10 | 687.44 |
| December | 0.00 | 0.00 | 1049.38 | 781.29 |
| Annual Sum or Average | 0.00 | 0.00 | 868.10 | 7609.93 |
| Minimum of Months | 0.00 | 0.00 | 645.00 | 480.22 |
| Maximum of Months | 0.00 | 0.00 | 1092.01 | 813.03 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1091.94 | 812.98 |
| February | 0.00 | 0.00 | 1079.29 | 725.80 |
| March | 0.00 | 0.00 | 1011.45 | 753.05 |
| April | 0.00 | 0.00 | 903.71 | 651.13 |
| May | 0.00 | 0.00 | 783.18 | 583.10 |
| June | 0.00 | 0.00 | 689.26 | 496.62 |
| July | 0.00 | 0.00 | 644.65 | 479.96 |
| August | 0.00 | 0.00 | 656.51 | 488.79 |
| September | 0.00 | 0.00 | 728.24 | 524.70 |
| October | 0.00 | 0.00 | 836.13 | 622.52 |
| November | 0.00 | 0.00 | 954.31 | 687.59 |
| December | 0.00 | 0.00 | 1049.59 | 781.45 |
| Annual Sum or Average | 0.00 | 0.00 | 867.84 | 7607.70 |
| Minimum of Months | 0.00 | 0.00 | 644.65 | 479.96 |
| Maximum of Months | 0.00 | 0.00 | 1091.94 | 812.98 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1092.01 | 813.03 |
| February | 0.00 | 0.00 | 1079.32 | 725.81 |
| March | 0.00 | 0.00 | 1011.38 | 753.00 |
| April | 0.00 | 0.00 | 903.71 | 651.13 |
| May | 0.00 | 0.00 | 783.19 | 583.11 |
| June | 0.00 | 0.00 | 689.26 | 496.62 |
| July | 0.00 | 0.00 | 644.78 | 480.06 |
| August | 0.00 | 0.00 | 656.50 | 488.78 |
| September | 0.00 | 0.00 | 728.27 | 524.73 |
| October | 0.00 | 0.00 | 838.21 | 624.07 |
| November | 0.00 | 0.00 | 952.20 | 686.07 |
| December | 0.00 | 0.00 | 1051.46 | 782.84 |
| Annual Sum or Average | 0.00 | 0.00 | 868.02 | 7609.26 |
| Minimum of Months | 0.00 | 0.00 | 644.78 | 480.06 |
| Maximum of Months | 0.00 | 0.00 | 1092.01 | 813.03 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1094.16 | 814.63 |
| February | 0.00 | 0.00 | 1079.33 | 725.82 |
| March | 0.00 | 0.00 | 1011.66 | 753.21 |
| April | 0.00 | 0.00 | 903.75 | 651.16 |
| May | 0.00 | 0.00 | 783.28 | 583.17 |
| June | 0.00 | 0.00 | 689.49 | 496.78 |
| July | 0.00 | 0.00 | 644.99 | 480.21 |
| August | 0.00 | 0.00 | 656.50 | 488.78 |
| September | 0.00 | 0.00 | 728.28 | 524.73 |
| October | 0.00 | 0.00 | 838.43 | 624.23 |
| November | 0.00 | 0.00 | 953.81 | 687.23 |
| December | 0.00 | 0.00 | 1051.54 | 782.90 |
| Annual Sum or Average | 0.00 | 0.00 | 868.43 | 7612.87 |
| Minimum of Months | 0.00 | 0.00 | 644.99 | 480.21 |
| Maximum of Months | 0.00 | 0.00 | 1094.16 | 814.63 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1094.22 | 814.68 |
| February | 0.00 | 0.00 | 1079.56 | 725.98 |
| March | 0.00 | 0.00 | 1011.77 | 753.29 |
| April | 0.00 | 0.00 | 903.56 | 651.03 |
| May | 0.00 | 0.00 | 783.10 | 583.04 |
| June | 0.00 | 0.00 | 689.34 | 496.68 |
| July | 0.00 | 0.00 | 644.97 | 480.20 |
| August | 0.00 | 0.00 | 656.50 | 488.78 |
| September | 0.00 | 0.00 | 728.26 | 524.72 |
| October | 0.00 | 0.00 | 838.23 | 624.09 |
| November | 0.00 | 0.00 | 954.25 | 687.55 |
| December | 0.00 | 0.00 | 1051.43 | 782.82 |
| Annual Sum or Average | 0.00 | 0.00 | 868.43 | 7612.85 |
| Minimum of Months | 0.00 | 0.00 | 644.97 | 480.20 |
| Maximum of Months | 0.00 | 0.00 | 1094.22 | 814.68 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1092.07 | 813.08 |
| February | 0.00 | 0.00 | 1081.58 | 727.34 |
| March | 0.00 | 0.00 | 1011.42 | 753.03 |
| April | 0.00 | 0.00 | 903.80 | 651.20 |
| May | 0.00 | 0.00 | 783.19 | 583.11 |
| June | 0.00 | 0.00 | 689.25 | 496.61 |
| July | 0.00 | 0.00 | 644.78 | 480.06 |
| August | 0.00 | 0.00 | 656.50 | 488.78 |
| September | 0.00 | 0.00 | 728.27 | 524.73 |
| October | 0.00 | 0.00 | 838.27 | 624.11 |
| November | 0.00 | 0.00 | 954.18 | 687.50 |
| December | 0.00 | 0.00 | 1051.34 | 782.75 |
| Annual Sum or Average | 0.00 | 0.00 | 868.37 | 7612.30 |
| Minimum of Months | 0.00 | 0.00 | 644.78 | 480.06 |
| Maximum of Months | 0.00 | 0.00 | 1092.07 | 813.08 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1091.93 | 812.98 |
| February | 0.00 | 0.00 | 1079.32 | 725.82 |
| March | 0.00 | 0.00 | 1009.56 | 751.65 |
| April | 0.00 | 0.00 | 904.04 | 651.37 |
| May | 0.00 | 0.00 | 783.37 | 583.24 |
| June | 0.00 | 0.00 | 689.47 | 496.77 |
| July | 0.00 | 0.00 | 644.98 | 480.21 |
| August | 0.00 | 0.00 | 656.50 | 488.78 |
| September | 0.00 | 0.00 | 728.27 | 524.72 |
| October | 0.00 | 0.00 | 838.29 | 624.13 |
| November | 0.00 | 0.00 | 952.17 | 686.05 |
| December | 0.00 | 0.00 | 1049.49 | 781.38 |
| Annual Sum or Average | 0.00 | 0.00 | 867.77 | 7607.09 |
| Minimum of Months | 0.00 | 0.00 | 644.98 | 480.21 |
| Maximum of Months | 0.00 | 0.00 | 1091.93 | 812.98 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1091.77 | 812.85 |
| February | 0.00 | 0.00 | 1079.09 | 725.66 |
| March | 0.00 | 0.00 | 1009.26 | 751.42 |
| April | 0.00 | 0.00 | 903.67 | 651.10 |
| May | 0.00 | 0.00 | 783.31 | 583.20 |
| June | 0.00 | 0.00 | 689.41 | 496.73 |
| July | 0.00 | 0.00 | 644.90 | 480.15 |
| August | 0.00 | 0.00 | 656.41 | 488.71 |
| September | 0.00 | 0.00 | 728.02 | 524.54 |
| October | 0.00 | 0.00 | 835.92 | 622.36 |
| November | 0.00 | 0.00 | 954.11 | 687.44 |
| December | 0.00 | 0.00 | 1049.12 | 781.10 |
| Annual Sum or Average | 0.00 | 0.00 | 867.57 | 7605.27 |
| Minimum of Months | 0.00 | 0.00 | 644.90 | 480.15 |
| Maximum of Months | 0.00 | 0.00 | 1091.77 | 812.85 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1091.92 | 812.96 |
| February | 0.00 | 0.00 | 1078.94 | 725.56 |
| March | 0.00 | 0.00 | 1009.38 | 751.51 |
| April | 0.00 | 0.00 | 903.86 | 651.24 |
| May | 0.00 | 0.00 | 783.08 | 583.02 |
| June | 0.00 | 0.00 | 689.34 | 496.68 |
| July | 0.00 | 0.00 | 644.97 | 480.20 |
| August | 0.00 | 0.00 | 656.50 | 488.78 |
| September | 0.00 | 0.00 | 728.26 | 524.72 |
| October | 0.00 | 0.00 | 836.10 | 622.50 |
| November | 0.00 | 0.00 | 954.12 | 687.45 |
| December | 0.00 | 0.00 | 1049.25 | 781.20 |
| Annual Sum or Average | 0.00 | 0.00 | 867.63 | 7605.84 |
| Minimum of Months | 0.00 | 0.00 | 644.97 | 480.20 |
| Maximum of Months | 0.00 | 0.00 | 1091.92 | 812.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1092.09 | 813.09 |
| February | 0.00 | 0.00 | 1081.81 | 727.49 |
| March | 0.00 | 0.00 | 1009.20 | 751.37 |
| April | 0.00 | 0.00 | 903.96 | 651.31 |
| May | 0.00 | 0.00 | 783.35 | 583.23 |
| June | 0.00 | 0.00 | 689.46 | 496.76 |
| July | 0.00 | 0.00 | 644.98 | 480.21 |
| August | 0.00 | 0.00 | 656.50 | 488.78 |
| September | 0.00 | 0.00 | 728.27 | 524.72 |
| October | 0.00 | 0.00 | 838.30 | 624.14 |
| November | 0.00 | 0.00 | 954.15 | 687.48 |
| December | 0.00 | 0.00 | 1049.56 | 781.42 |
| Annual Sum or Average | 0.00 | 0.00 | 868.11 | 7610.01 |
| Minimum of Months | 0.00 | 0.00 | 644.98 | 480.21 |
| Maximum of Months | 0.00 | 0.00 | 1092.09 | 813.09 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1092.14 | 813.13 |
| February | 0.00 | 0.00 | 1081.69 | 727.41 |
| March | 0.00 | 0.00 | 1009.09 | 751.30 |
| April | 0.00 | 0.00 | 904.05 | 651.38 |
| May | 0.00 | 0.00 | 783.15 | 583.07 |
| June | 0.00 | 0.00 | 689.26 | 496.62 |
| July | 0.00 | 0.00 | 644.64 | 479.95 |
| August | 0.00 | 0.00 | 656.51 | 488.79 |
| September | 0.00 | 0.00 | 728.23 | 524.70 |
| October | 0.00 | 0.00 | 836.26 | 622.62 |
| November | 0.00 | 0.00 | 954.33 | 687.61 |
| December | 0.00 | 0.00 | 1051.56 | 782.91 |
| Annual Sum or Average | 0.00 | 0.00 | 868.05 | 7609.49 |
| Minimum of Months | 0.00 | 0.00 | 644.64 | 479.95 |
| Maximum of Months | 0.00 | 0.00 | 1092.14 | 813.13 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1092.09 | 813.09 |
| February | 0.00 | 0.00 | 1081.60 | 727.35 |
| March | 0.00 | 0.00 | 1009.71 | 751.75 |
| April | 0.00 | 0.00 | 903.46 | 650.95 |
| May | 0.00 | 0.00 | 783.32 | 583.20 |
| June | 0.00 | 0.00 | 689.42 | 496.73 |
| July | 0.00 | 0.00 | 644.90 | 480.15 |
| August | 0.00 | 0.00 | 656.41 | 488.71 |
| September | 0.00 | 0.00 | 728.02 | 524.55 |
| October | 0.00 | 0.00 | 835.97 | 622.40 |
| November | 0.00 | 0.00 | 954.47 | 687.70 |
| December | 0.00 | 0.00 | 1051.51 | 782.88 |
| Annual Sum or Average | 0.00 | 0.00 | 868.05 | 7609.49 |
| Minimum of Months | 0.00 | 0.00 | 644.90 | 480.15 |
| Maximum of Months | 0.00 | 0.00 | 1092.09 | 813.09 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1092.07 | 813.08 |
| February | 0.00 | 0.00 | 1079.35 | 725.84 |
| March | 0.00 | 0.00 | 1011.67 | 753.22 |
| April | 0.00 | 0.00 | 903.87 | 651.25 |
| May | 0.00 | 0.00 | 783.02 | 582.98 |
| June | 0.00 | 0.00 | 689.32 | 496.66 |
| July | 0.00 | 0.00 | 644.97 | 480.20 |
| August | 0.00 | 0.00 | 656.50 | 488.78 |
| September | 0.00 | 0.00 | 728.28 | 524.74 |
| October | 0.00 | 0.00 | 838.36 | 624.18 |
| November | 0.00 | 0.00 | 954.15 | 687.48 |
| December | 0.00 | 0.00 | 1049.32 | 781.25 |
| Annual Sum or Average | 0.00 | 0.00 | 868.07 | 7609.65 |
| Minimum of Months | 0.00 | 0.00 | 644.97 | 480.20 |
| Maximum of Months | 0.00 | 0.00 | 1092.07 | 813.08 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1091.96 | 812.99 |
| February | 0.00 | 0.00 | 1079.42 | 725.89 |
| March | 0.00 | 0.00 | 1011.32 | 752.96 |
| April | 0.00 | 0.00 | 901.42 | 649.48 |
| May | 0.00 | 0.00 | 784.29 | 583.93 |
| June | 0.00 | 0.00 | 690.93 | 497.82 |
| July | 0.00 | 0.00 | 642.95 | 478.69 |
| August | 0.00 | 0.00 | 658.41 | 490.20 |
| September | 0.00 | 0.00 | 726.21 | 523.25 |
| October | 0.00 | 0.00 | 838.26 | 624.11 |
| November | 0.00 | 0.00 | 954.01 | 687.37 |
| December | 0.00 | 0.00 | 1049.21 | 781.16 |
| Annual Sum or Average | 0.00 | 0.00 | 867.86 | 7607.85 |
| Minimum of Months | 0.00 | 0.00 | 642.95 | 478.69 |
| Maximum of Months | 0.00 | 0.00 | 1091.96 | 812.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1091.96 | 812.99 |
| February | 0.00 | 0.00 | 1079.44 | 725.90 |
| March | 0.00 | 0.00 | 1011.29 | 752.93 |
| April | 0.00 | 0.00 | 903.60 | 651.06 |
| May | 0.00 | 0.00 | 783.69 | 583.48 |
| June | 0.00 | 0.00 | 689.62 | 496.88 |
| July | 0.00 | 0.00 | 643.13 | 478.83 |
| August | 0.00 | 0.00 | 658.29 | 490.12 |
| September | 0.00 | 0.00 | 726.19 | 523.23 |
| October | 0.00 | 0.00 | 838.19 | 624.06 |
| November | 0.00 | 0.00 | 953.87 | 687.27 |
| December | 0.00 | 0.00 | 1049.33 | 781.25 |
| Annual Sum or Average | 0.00 | 0.00 | 867.88 | 7607.99 |
| Minimum of Months | 0.00 | 0.00 | 643.13 | 478.83 |
| Maximum of Months | 0.00 | 0.00 | 1091.96 | 812.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1092.19 | 813.16 |
| February | 0.00 | 0.00 | 1081.97 | 727.60 |
| March | 0.00 | 0.00 | 1009.40 | 751.53 |
| April | 0.00 | 0.00 | 903.68 | 651.11 |
| May | 0.00 | 0.00 | 783.83 | 583.58 |
| June | 0.00 | 0.00 | 691.58 | 498.29 |
| July | 0.00 | 0.00 | 642.61 | 478.44 |
| August | 0.00 | 0.00 | 657.94 | 489.86 |
| September | 0.00 | 0.00 | 727.08 | 523.87 |
| October | 0.00 | 0.00 | 838.18 | 624.05 |
| November | 0.00 | 0.00 | 954.16 | 687.48 |
| December | 0.00 | 0.00 | 1051.54 | 782.90 |
| Annual Sum or Average | 0.00 | 0.00 | 868.32 | 7611.87 |
| Minimum of Months | 0.00 | 0.00 | 642.61 | 478.44 |
| Maximum of Months | 0.00 | 0.00 | 1092.19 | 813.16 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1092.12 | 813.11 |
| February | 0.00 | 0.00 | 1081.97 | 727.60 |
| March | 0.00 | 0.00 | 1009.30 | 751.45 |
| April | 0.00 | 0.00 | 903.95 | 651.31 |
| May | 0.00 | 0.00 | 783.32 | 583.20 |
| June | 0.00 | 0.00 | 689.45 | 496.76 |
| July | 0.00 | 0.00 | 644.98 | 480.21 |
| August | 0.00 | 0.00 | 656.50 | 488.78 |
| September | 0.00 | 0.00 | 728.27 | 524.72 |
| October | 0.00 | 0.00 | 838.31 | 624.15 |
| November | 0.00 | 0.00 | 954.24 | 687.54 |
| December | 0.00 | 0.00 | 1049.65 | 781.49 |
| Annual Sum or Average | 0.00 | 0.00 | 868.14 | 7610.32 |
| Minimum of Months | 0.00 | 0.00 | 644.98 | 480.21 |
| Maximum of Months | 0.00 | 0.00 | 1092.12 | 813.11 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1092.08 | 813.09 |
| February | 0.00 | 0.00 | 1081.89 | 727.55 |
| March | 0.00 | 0.00 | 1009.15 | 751.34 |
| April | 0.00 | 0.00 | 903.93 | 651.29 |
| May | 0.00 | 0.00 | 783.39 | 583.25 |
| June | 0.00 | 0.00 | 689.49 | 496.79 |
| July | 0.00 | 0.00 | 644.99 | 480.21 |
| August | 0.00 | 0.00 | 656.50 | 488.78 |
| September | 0.00 | 0.00 | 728.28 | 524.73 |
| October | 0.00 | 0.00 | 838.35 | 624.18 |
| November | 0.00 | 0.00 | 954.20 | 687.51 |
| December | 0.00 | 0.00 | 1049.78 | 781.59 |
| Annual Sum or Average | 0.00 | 0.00 | 868.14 | 7610.31 |
| Minimum of Months | 0.00 | 0.00 | 644.99 | 480.21 |
| Maximum of Months | 0.00 | 0.00 | 1092.08 | 813.09 |
Report: HEATING AND COOLING LOADS
For: HEATEDBSMT
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.00 | 1000.93 |
| February | 0.00 | 1516.62 |
| March | 0.00 | 1037.58 |
| April | 32.49 | 11.11 |
| May | 303.02 | 0.00 |
| June | 525.40 | 0.00 |
| July | 521.68 | 0.00 |
| August | 507.44 | 0.00 |
| September | 414.57 | 0.00 |
| October | 238.88 | 0.00 |
| November | 1.93 | 263.95 |
| December | 0.00 | 1639.52 |
| Annual Sum or Average | 2545.42 | 5469.71 |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 525.40 | 1639.52 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 85.52 | 993.04 |
| February | 21.86 | 1032.92 |
| March | 57.01 | 922.81 |
| April | 197.68 | 97.07 |
| May | 266.68 | 4.94 |
| June | 384.77 | 0.00 |
| July | 358.81 | 0.00 |
| August | 343.80 | 0.00 |
| September | 288.17 | 0.00 |
| October | 174.23 | 220.48 |
| November | 75.66 | 726.70 |
| December | 49.34 | 1549.52 |
| Annual Sum or Average | 2303.51 | 5547.48 |
| Minimum of Months | 21.86 | 0.00 |
| Maximum of Months | 384.77 | 1549.52 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 63.51 | 616.58 |
| February | 12.09 | 655.27 |
| March | 35.47 | 591.58 |
| April | 139.62 | 39.03 |
| May | 198.64 | 0.08 |
| June | 291.23 | 0.00 |
| July | 284.06 | 0.00 |
| August | 274.67 | 0.00 |
| September | 236.95 | 0.00 |
| October | 142.06 | 104.99 |
| November | 55.54 | 433.20 |
| December | 36.44 | 1014.99 |
| Annual Sum or Average | 1770.28 | 3455.72 |
| Minimum of Months | 12.09 | 0.00 |
| Maximum of Months | 291.23 | 1014.99 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 73.32 | 924.90 |
| February | 17.64 | 953.75 |
| March | 49.70 | 841.20 |
| April | 193.87 | 80.90 |
| May | 270.81 | 4.16 |
| June | 390.19 | 0.00 |
| July | 372.65 | 0.00 |
| August | 354.68 | 0.00 |
| September | 293.57 | 0.00 |
| October | 174.26 | 196.95 |
| November | 64.42 | 672.65 |
| December | 40.60 | 1462.42 |
| Annual Sum or Average | 2295.71 | 5136.93 |
| Minimum of Months | 17.64 | 0.00 |
| Maximum of Months | 390.19 | 1462.42 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 30.05 | 1144.63 |
| February | 4.16 | 1204.62 |
| March | 35.51 | 987.85 |
| April | 170.58 | 98.10 |
| May | 259.75 | 4.66 |
| June | 388.29 | 0.00 |
| July | 356.76 | 0.00 |
| August | 328.13 | 0.00 |
| September | 260.32 | 0.00 |
| October | 125.34 | 251.25 |
| November | 30.97 | 855.18 |
| December | 10.40 | 1823.78 |
| Annual Sum or Average | 2000.27 | 6370.07 |
| Minimum of Months | 4.16 | 0.00 |
| Maximum of Months | 388.29 | 1823.78 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 8.52 | 750.04 |
| February | 0.03 | 830.76 |
| March | 16.28 | 656.27 |
| April | 112.02 | 39.33 |
| May | 192.11 | 0.05 |
| June | 295.38 | 0.00 |
| July | 282.24 | 0.00 |
| August | 258.74 | 0.00 |
| September | 208.09 | 0.00 |
| October | 90.93 | 126.78 |
| November | 12.40 | 551.87 |
| December | 2.22 | 1292.90 |
| Annual Sum or Average | 1478.96 | 4248.01 |
| Minimum of Months | 0.03 | 0.00 |
| Maximum of Months | 295.38 | 1292.90 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 13.80 | 1027.32 |
| February | 0.44 | 1085.09 |
| March | 26.24 | 882.39 |
| April | 165.58 | 81.33 |
| May | 263.74 | 4.09 |
| June | 393.31 | 0.00 |
| July | 370.09 | 0.00 |
| August | 338.63 | 0.00 |
| September | 265.19 | 0.00 |
| October | 122.40 | 210.31 |
| November | 18.48 | 772.09 |
| December | 3.88 | 1712.64 |
| Annual Sum or Average | 1981.77 | 5775.26 |
| Minimum of Months | 0.44 | 0.00 |
| Maximum of Months | 393.31 | 1712.64 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 104.42 | 653.70 |
| February | 33.38 | 699.18 |
| March | 73.27 | 597.30 |
| April | 221.32 | 38.09 |
| May | 277.05 | 0.75 |
| June | 386.03 | 0.00 |
| July | 361.28 | 0.00 |
| August | 350.10 | 0.00 |
| September | 297.47 | 0.00 |
| October | 183.63 | 162.99 |
| November | 91.68 | 474.94 |
| December | 63.32 | 1107.41 |
| Annual Sum or Average | 2442.97 | 3734.36 |
| Minimum of Months | 33.38 | 0.00 |
| Maximum of Months | 386.03 | 1107.41 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 85.08 | 300.31 |
| February | 25.72 | 335.84 |
| March | 52.19 | 290.30 |
| April | 162.36 | 6.66 |
| May | 205.66 | 0.00 |
| June | 284.12 | 0.00 |
| July | 279.66 | 0.00 |
| August | 274.66 | 0.00 |
| September | 242.01 | 0.00 |
| October | 152.05 | 58.87 |
| November | 74.27 | 211.78 |
| December | 53.43 | 582.71 |
| Annual Sum or Average | 1891.21 | 1786.47 |
| Minimum of Months | 25.72 | 0.00 |
| Maximum of Months | 284.12 | 582.71 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 94.45 | 600.87 |
| February | 31.68 | 636.70 |
| March | 68.65 | 530.23 |
| April | 222.27 | 29.88 |
| May | 283.90 | 0.55 |
| June | 393.07 | 0.00 |
| July | 377.22 | 0.00 |
| August | 362.75 | 0.00 |
| September | 303.94 | 0.00 |
| October | 185.47 | 140.33 |
| November | 81.95 | 433.04 |
| December | 56.29 | 1033.60 |
| Annual Sum or Average | 2461.64 | 3405.19 |
| Minimum of Months | 31.68 | 0.00 |
| Maximum of Months | 393.07 | 1033.60 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 37.17 | 803.15 |
| February | 7.24 | 857.14 |
| March | 46.90 | 655.46 |
| April | 192.18 | 38.83 |
| May | 270.21 | 0.64 |
| June | 390.03 | 0.00 |
| July | 359.33 | 0.00 |
| August | 333.64 | 0.00 |
| September | 267.79 | 0.00 |
| October | 130.19 | 198.19 |
| November | 37.54 | 599.62 |
| December | 13.35 | 1384.95 |
| Annual Sum or Average | 2085.59 | 4537.99 |
| Minimum of Months | 7.24 | 0.00 |
| Maximum of Months | 390.03 | 1384.95 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 14.17 | 417.76 |
| February | 1.29 | 476.20 |
| March | 25.92 | 339.10 |
| April | 132.27 | 6.77 |
| May | 199.18 | 0.00 |
| June | 288.76 | 0.00 |
| July | 277.92 | 0.00 |
| August | 257.88 | 0.00 |
| September | 211.19 | 0.00 |
| October | 95.52 | 82.18 |
| November | 18.37 | 314.14 |
| December | 4.01 | 837.33 |
| Annual Sum or Average | 1526.47 | 2473.48 |
| Minimum of Months | 1.29 | 0.00 |
| Maximum of Months | 288.76 | 837.33 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 21.09 | 701.74 |
| February | 2.58 | 744.19 |
| March | 39.23 | 563.44 |
| April | 192.12 | 30.29 |
| May | 276.75 | 0.55 |
| June | 396.58 | 0.00 |
| July | 374.69 | 0.00 |
| August | 345.87 | 0.00 |
| September | 273.75 | 0.00 |
| October | 128.56 | 156.49 |
| November | 24.69 | 528.91 |
| December | 6.19 | 1276.71 |
| Annual Sum or Average | 2082.08 | 4002.32 |
| Minimum of Months | 2.58 | 0.00 |
| Maximum of Months | 396.58 | 1276.71 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 28.90 | 1139.33 |
| February | 5.11 | 1202.42 |
| March | 49.31 | 933.99 |
| April | 227.13 | 72.42 |
| May | 315.82 | 4.84 |
| June | 462.21 | 0.00 |
| July | 436.56 | 0.00 |
| August | 405.13 | 0.00 |
| September | 320.59 | 0.00 |
| October | 149.55 | 303.30 |
| November | 31.24 | 881.15 |
| December | 9.46 | 1931.03 |
| Annual Sum or Average | 2440.99 | 6468.48 |
| Minimum of Months | 5.11 | 0.00 |
| Maximum of Months | 462.21 | 1931.03 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 86.32 | 1012.80 |
| February | 24.20 | 1064.27 |
| March | 66.51 | 896.74 |
| April | 242.40 | 72.01 |
| May | 317.90 | 4.98 |
| June | 457.67 | 0.00 |
| July | 435.91 | 0.00 |
| August | 412.65 | 0.00 |
| September | 337.62 | 0.00 |
| October | 189.44 | 278.33 |
| November | 74.40 | 760.95 |
| December | 47.27 | 1646.94 |
| Annual Sum or Average | 2692.31 | 5737.02 |
| Minimum of Months | 24.20 | 0.00 |
| Maximum of Months | 457.67 | 1646.94 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 98.66 | 1093.74 |
| February | 28.21 | 1159.19 |
| March | 73.50 | 997.61 |
| April | 244.28 | 91.92 |
| May | 313.01 | 6.40 |
| June | 451.41 | 0.00 |
| July | 420.77 | 0.00 |
| August | 400.68 | 0.00 |
| September | 331.69 | 0.00 |
| October | 190.10 | 320.97 |
| November | 85.95 | 826.37 |
| December | 56.25 | 1752.11 |
| Annual Sum or Average | 2694.52 | 6248.31 |
| Minimum of Months | 28.21 | 0.00 |
| Maximum of Months | 451.41 | 1752.11 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 21.20 | 833.22 |
| February | 2.64 | 910.37 |
| March | 35.77 | 682.73 |
| April | 169.47 | 35.84 |
| May | 239.17 | 0.18 |
| June | 355.72 | 0.00 |
| July | 340.92 | 0.00 |
| August | 318.36 | 0.00 |
| September | 259.09 | 0.00 |
| October | 116.97 | 205.99 |
| November | 24.04 | 638.30 |
| December | 6.73 | 1468.22 |
| Annual Sum or Average | 1890.07 | 4774.85 |
| Minimum of Months | 2.64 | 0.00 |
| Maximum of Months | 355.72 | 1468.22 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 77.36 | 670.29 |
| February | 19.44 | 734.52 |
| March | 51.92 | 628.40 |
| April | 184.73 | 35.25 |
| May | 240.98 | 0.25 |
| June | 350.57 | 0.00 |
| July | 339.85 | 0.00 |
| August | 325.86 | 0.00 |
| September | 276.51 | 0.00 |
| October | 156.45 | 168.38 |
| November | 66.50 | 494.21 |
| December | 44.12 | 1153.13 |
| Annual Sum or Average | 2134.28 | 3884.43 |
| Minimum of Months | 19.44 | 0.00 |
| Maximum of Months | 350.57 | 1153.13 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:29:26
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 45.95 | 1268.18 |
| February | 10.16 | 1329.51 |
| March | 57.72 | 1051.46 |
| April | 229.47 | 93.16 |
| May | 311.01 | 5.97 |
| June | 456.15 | 0.00 |
| July | 421.69 | 0.00 |
| August | 393.34 | 0.00 |
| September | 314.89 | 0.00 |
| October | 152.64 | 366.49 |
| November | 44.61 | 973.36 |
| December | 17.74 | 2054.63 |
| Annual Sum or Average | 2455.37 | 7142.77 |
| Minimum of Months | 10.16 | 0.00 |